AIR CONDITIONING SYSTEM

Transcription

AIR CONDITIONING SYSTEM
PCS0911A
AIR CONDITIONING SYSTEM
COOLING ONLY [50Hz ]
The match for tastefully designed offices and stores.
P eo pl e ar e dr aw n to b e a u tifu lly d e sig n e d stores that ex pres s the lates t. People work bes t in offices
i m bued w i t h f unc tio n a l b e a u ty.
Dai ki n’s SkyAi r i s th e ch o ice to b rin g h ig h quality air c onditioning to s tores and offic es lik e this .
T ha nks t o i t s man y a d va n ta g e s su ch a s q u iet operation, eas e of us e and flex ible ins tallation, the SkyAir
enj o ys an excel l e n t re p u ta tio n th ro u g h o u t the world wherev er it is us ed.
Cooling only
HP
1
Capacity *
Btu/h
kW
The values given for
2 HP–6 HP is for FHC type,
6.5 HP–7 HP is for FDMG type.
kcal/h
2
2.5
3
3.5
18,000
21,000
26,000
30,000
5.3
6.2
7.6
8.8
4,560
5,290
6,550
7,570
FHC18NUV1
FHC21NUV1
FHC26NUV1
FHC30NUV1
R18NUV1
R21NUV1
R26NUV1 / Y1
R30NUV1 / Y1
CEILING MOUNTED
CASSETTE TYPE
Indoor unit
Outdoor unit
CEILING SUSPENDED TYPE
FH21NUV1
FH26NUV1
FH30NUV1
R21NUV1
R26NUV1 / Y1
R30NUV1 / Y1
FDBG18PUV1
FDBG21PUV1
FDBG26PUV1
R18NUV1
R21NUV1
R26NUV1 / Y1
Indoor unit
Outdoor unit
LOW STATIC
PRESSURE TYPE
Indoor unit
Outdoor unit
DUCT
CONNECTION
MIDDLE STATIC
PRESSURE TYPE
Indoor unit
Outdoor unit
Indoor unit
Outdoor unit
FDMG26PUV1
FDMG30PUV1
R26NUV1 / Y1
R30NUV1 / Y1
FDMG26NUV1
FDMG30NUV1
R26NUV1 / Y1
R30NUV1 / Y1
R26NUV1 / Y1
R30NUV1 / Y1
OUTDOOR UNIT
R18NUV1
R21NUV1
*1. Note : Rated cooling capacities are based on the following conditions: Return air temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 7.5 m (horizontal)
1
CEILING SUSPENDED TYPE
Simple design and quiet
operation auto-swing air flow
brings comfort to each and
every corner of the room.
Installation and
maintenance are easy.
CEILING MOUNTED CASSETTE TYPE
DUCT CONNECTION TYPE
The
Theindoor
indoorunit
unitisisinstall
instaled
led
inside
insidethe
theceiling
ceilingand
andduc
d uctsts
discharge
dischargeair
airininany
anydirec
direction.
tion.
Comfort
Comfortisisprovided
providedwithout
without
even
evenknowing
knowingthat
thatan
anair
ai r
conditioner
conditionerisisinstalled.
installed.
Th is u n it is in st a lle d a t center
Thilin
is gu.n A
it irisisinbstloawn
lle dina tfour
center
ce
ce
ilin
g
.
A
ir
is
b
lo
wn
in
four
d ire ct io n s t o b rin g co mfort.
cttio
t o qburin
Odpire
e ra
ionns is
ie tg. co mfort.
O p e ra t io n is q u ie t .
4
5
6
6.5
7
36,000
42,000
48,000
51,000
56,000
10.6
12.3
14.1
15.0
16.4
9,100
10,600
12,100
12,900
14,100
FHC36NUV1
FHC42NUV1
FHC48NUV1
R36NUV1 / Y1
R42NUY1
R48NUY1
FH36NUV1
FH42NUV1
FH48NUV1
R36NUV1 / Y1
R42NUY1
R48NUY1
FDMG36PUV1
FDMG42PUV1
FDMG48PUV1
FDMG51PUV1
FDMG56PUV1
R36NUV1 / Y1
R42NUY1
R48NUY1
R51NUY1
R56NUY1
FDMG36NUV1
FDMG42NUV1
FDMG48NUV1
FDMG51NUV1
FDMG56NUV1
R36NUV1 / Y1
R42NUY1
R48NUY1
R51NUY1
R56NUY1
R36NUV1 / Y1
R42NUY1
R48NUY1
R51NUY1
R56NUY1
2
CEILING MOUNTED
FHC-NU
CASSETTE TYPE
Quiet, decor-blending form and easy installation
Sound level
42/36
Cooling only
dB(A)
High
FHC18NU–48NU
Low
FHC36NU
(220V)
Option
Accessory required for indoor unit
Wired LCD remote controller
BRC1C61
Note: Remote controller cable not
included. Cables must be
procured locally.
Wireless LCD remote controller
A signal receiver must be added to the indoor unit.
BRC7C613W
Signal receiver unit
(Installed type)
Wireless remote controller and signal
receiver unit are sold as a set.
Features
3
Fresh air intake kit
Long-life filter
PE fin
*2
High-efficiency filter
•
Ultra long-life filter
•
Auto-restart
•
Others
Ceiling soiling prevention
*1
Options
Filter sign
•
Pre charged for
up to 15 m
•
Drain pump mechanism
High ceiling application
•
Mould resistant treatment
for filter
Programme "Dry"
•
Control
features
Work & Servicing
Timer selector
Switchable fan speed
•
*1Applicable when wired remote controller is used
*2Applicable to R36NU–R48NU outdoor units
Two selectable
temperature-sensors
Swing pattern selection
Cooling only
Auto swing
Model
Mould
prevention
Comfort
Feature
•
•
•
•
•
•
•
•
Compact body and quiet operation
All models from the 18NU to 48NU
use the same size panel. Multiple
unit installations maintain a physical
uniformity that is aesthetically
pleasing and make it easier to plan
ceiling lighting systems and to
design interiors.
Indoor units use an
aerodynamically designed
Diffuser Turbo Fan
950 mm
Unified square panels
Draft resistance has been reduced
by incorporating, into a single unit,
an impeller and a diffuser to control
air flow inside the unit. The Diffuser
Turbo Fan is both quiet during
operation and compact.
Diffuser
(220V) dB(A)
Same for
all models
Blade
950 mm
Optimal comfort and convenience assured by 3 air discharge modes
Air direction
Desired situation
Draft prevention setting
When drafts are unwanted
Standard setting
Setting to prevent soiling of ceiling
For gentle drafts(Ceiling is soiled.)
When ceilings must be kept spotless
Auto-swing
Auto-swing between
10° and 40°
Auto-swing between
10° and 65°
Auto-swing between
30° and 65°
5-levels
air direction
setting
Settable to 5 different
levels between
10° and 40°
Settable to 5 different
levels between
10° and 65°
Settable to 5 different
levels between
30° and 65°
Draft prevention
(In heating mode)
At heating startup and thermo OFF*, air discharge is
automatically set to a near horizontal 10˚ to prevent direct
exposure to cool air drafts.
Auto air
direction control
The air direction is set automatically to the memorised position of the previous air direction.
(Initial setting is 65˚ for heating and 30˚ for cooling.)
At heating startup and thermo
OFF*, air discharge is
automatically set to 30˚ to prevent both direct
exposure to cool air drafts and contact with ceilings.
*When the thermostat turns off.
4-way flow
1 pattern
3-way flow
4 pattern
Wide air distribution
Air discharge opening increases flow
without increasing wind speed, hence
discharged air reaches farther than
before.
Air discharge distribution comparison
•42NU
2-way flow
3 pattern
Note: For 3-way or 2-way flow installation, the sealing
member for air discharge outlet (option) must be
used to close off the unused outlet(s).
Air direction can be selected
according to installation.
Note: Operation sound
increases when
using 2-way or
3-way flow.
Two selectable temperature-sensors
Both indoor unit and wired remote
controller (option) contain temperaturesensors. Temperature sensing can be
set at the unit or, to further improve
comfort level, closer to the target area
at the wired remote control.This feature
require initial setting by the installer.
4 (m)
(m)
3.2
3
Super Cassette
(m) Conventional model
2.7
2.5 m/sec
2.0 m/sec
2
1.5 m/sec
1.0 m/sec
1
2.5 m/sec
2
2.0 m/sec
1.5 m/sec
1.0 m/sec 1
0.5 m/sec
0.5 m/sec
" " denotes piping direction. "
" denotes sealing
member for air discharge outlet (option) .
High
Low
18NU
21NU
26NU
30NU
36NU
42NU
48NU
33
35
35
39
42
42
42
29
30
30
34
36
36
36
Quick and easy to install
Just 240 mm high. Installable in
tight ceiling spaces (18NU–26NU)
240 mm *1
245 mm *2
*1 298 mm high with 30NU–48NU
*2 303 mm high with 30NU–48NU
Easy height adjustment
Note: Air direction is set to the standard position when the unit is shipped from the factory.
The position can be changed from the remote controller.
Multi-Flow System
Indoor unit
3
2
1
0
1
2
3
4 (m)
Each corner of the unit has an
Adjuster Pocket that
lets you easily adjust
the unit's suspended
height.
Note: If the wireless remote control
option is installed, a light
receptor unit is housed in
one of the adjuster pockets.
All models suspended
without lift
Installable in
any direction
Suitable for high ceilings
Criteria for ceiling height and number of
air discharge outlets
Number of air discharge outlets used
18NU–26NU
4-way
flow
Standard
Ceiling High ceiling
height
High ceiling
3-way
flow
2-way
flow
30NU–48NU
4-way
flow
3-way
flow
2-way
flow
2.7 m 3.0 m 3.5 m 3.2 m 3.6 m 4.2 m
3.0 m 3.3 m 3.8 m 3.6 m 4.0 m 4.2 m
3.5 m 3.5 m 4.2 m 4.2 m -
Note: Initial settings are for standard ceiling height and
4-way flow. High ceiling settings 1 and 2 are
set from the remote controller.
Provided with drain pump
mechanism
750 mm
Programme "Dry"
Dehumidification is microprocessor
controlled to prevent abrupt and
uncomfortable changes in air
temperature.
Switchable fan speed:
High/Low
Easy installation of options
The high-performance filter and
other options are easily clipped into
place. There is no need for a
screwdriver.
*Temperature-sensor on indoor unit must be used when
the air conditioner is controlled from another room.
**Wireless remote controller does not have a
temperature-sensor.
4
CEILING SUSPENDED TYPE
FH-NU
Upgrade to a quiet and compact system.
Sound level
46/40
Cooling only
High
FH21NU–48NU
dB(A)
Low
FH36NU
(220V)
Option
Accessory required for indoor unit
Wired LCD remote controller
BRC1NU61
Note: Remote controller cable not
included. Cables must be
procured locally.
Wireless LCD remote controller
A signal receiver must be added to the indoor unit.
BRC7NU66
Signal receiver unit (Installed type)
Wireless remote controller and signal
receiver unit are sold as a set.
Features
Mould resistant treatment
for filter
Mould proofing
drain pan
Pre charged for
up to 15 m
•
•
•
•
*1
5
Others
PE fin
Timer selector
•
Options
Long-life filter
Programme "Dry"
•
*1Applicable to R36NU–R48NU outdoor units
Control
features
Auto-restart
Switchable fan speed
Cooling only
Work &
Servicing
Auto swing
Model
Mould
prevention
Comfort
Feature
•
•
•
Spreads comfortable air throughout the room
Auto-swing (up&down)
brings comfort to the room.
Wide air discharge openings
produce a spreading 100°
airflow
Installable
on ceilings
3.5 m high
Switchable fan speed:
High/Middle/Low
Quiet operation
Sound operation has been reduced
on the exposed ceiling suspended
type unit.
(220V) dB(A)
Indoor unit
High
Low
21NU
44
44
45
46
48
49
40
40
40
40
42
43
26NU
30NU
36NU
42NU
Programme "Dry"
Dehumidification is microprocessor
controlled to prevent abrupt and
uncomfortable changes in air
temperature.
100°
Air is blown up to 50° in
the downward direction.
Installation flexibility for freedom of design
Uniform height and depth.
Compact design for smallcapacity models to meet tighter
dimensional constraints.
(mm)
Indoor unit 21NU 26NU 30NU 36NU 42NU 48NU
195
1,160
1,400
Uses quiet stream fan
and other quiet
technologies.
Turbulent flow Straightening
is produced
vane
50°
Height
Width
Depth
48NU
Note : Anechoic chamber conversion value, measured
according to JIS parameters and criteria.
1,590
680
Weight of all models reduced (down 10% compared
with previous models). Transfer and installation work is
less arduous.
Reduced edge space,
flexible installation
All wiring and internal
servicing done from below
the unit
Pipes more easily rigged, too
Plastic panels are used to conceal
piping holes. Holes can be easily
punched out without requiring
special tools.
Quiet
stream fan
Easier to maintain
Long-life filter lasts about half
year * maintenance not required
* For dust concentration of 0.15 mg/m3
Non-dew flap without bristles
Absence of bristles minimises clinging
dirt and simplifies
cleaning.
Non-dew flap
Easy-clean, flat surfaces
It is easy to wipe dirt off the flat
side and lower surfaces of the unit.
For all maintenance tasks,
access is from bottom
surface
The unit fits more snugly into tight
spaces.
For 48NU indoor unit
30 mm
or more
1,590 mm
30 mm
or more
*Water used in the test-run can now be drained from the air discharge
opening rather than from the side as was formerly the case.
Improved-oil resistant
grille
Oil-resistant plastic is used for the air
discharge grille. This improves
durability in restaurants and other
similar environments.
Note: Intended for use in salons, dining rooms, and
ordinary sales floors, this specification is not
suitable for kitchens or other harsh environments.
6
FDMG-PU
FDMG-NU
DUCT CONNECTION
MIDDLE STATIC PRESSURE TYPE
Unit can be mounted in the
ceiling and air can be delivered
freely by duct.
Superior freedom of layout
The duct system allows the efficient location of
discharge outlets in accordance with the room
layout
Middle static pressure type, usable in a larger than
standard space
Duct connection is simpler with standard rear
intake chambers
Ordinary duct
(procured locally)
Air conditioner
295 mm
Ordinary duct
(procured locally)
305 mm or more
Air intake
Air discharge
Quiet operation
(220V) dB(A)
FDMG36PU
Sound level
Cooling only
FDMG26PU–56PU
FDMG26NU–56NU
45/37dB(A)
High
LOW
42
44
45
46
46
47
47
38
36
37
37
37
37
37
FDMG36PU
Low
FDMG42PU
FDMG36PU
FDMG48PU
FDMG51PU
Accessory required for indoor unit
FDMG56PU
For FDMG-PU
Wired LCD remote controller
High
FDMG30PU
(220V)
Option
Indoor unit
FDMG26PU
Switchable fan speed: High/Middle/Low (FDMG26NU–56NU)
(FDMG26PU–56PU is switchable fan speed: High/Low)
Signal receiver unit
(Separate type)
Wireless remote controller
and signal receiver unit
are sold as a set.
Model
For FDMG-NU
7
Cooling only
Digital remote
controller
Remote
controller
KRC47-2A
KRC47-1A
•
*1
*2
*1Applicable when wired remote controller is used (FDMG-PU)
*2Applicable to R36NU–R51NU outdoor units
Others
PE fin
BRC4C64
Work & Servicing Control features
Comfort
Feature
Auto-restart
A signal receiver must be added to the indoor unit.
Features
Pre charged for
up to 15 m
Wireless LCD remote controller
Drain pipe connection can be done inside the
unit. Coolant and drain pipe outlets are at the
same opening.
Two selectable
temperature-sensors
Note: Remote controller cable not included.
Cables must be procured locally.
Switchable fan speed
BRC1C61
•
•
DUCT CONNECTION
FDBG-PU
LOW STATIC PRESSURE TYPE
Ideal for quiet, beautiful living
spaces
Suitable for condominiums and
apartments, houses and hotels
Compact
Small, lightweight, and easy-to-install indoor unit.
or more
Suction chamber
Air filter
[Duct connection]
To prevent increased operation sound, avoid installing the air suction grille
directly below the suction chamber.
Quiet operation
Sound level
Cooling only
FDBG18PU–26PU
43/40dB(A)
High
Indoor unit
High
Low
FDBG18PU
41
43
43
38
40
40
FDBG21PU
Low
FDBG26PU
FDBG26PU
(220V) dB(A)
(220V)
Accessory required for indoor unit
Features
Cooling only
A signal receiver must be added to the indoor unit.
BRC4C64
•
*1
PE fin
Model
Wireless LCD remote controller
Others
Auto-restart
Note: Remote controller cable not included.
Cables must be procured locally.
Two selectable
temperature-sensors
BRC1C61
Work & Servicing Control features
Comfort
Feature
Pre charged for
up to 10 m
Wired LCD remote controller
Switchable fan speed
Option
•
•
•
*1Applicable when wired remote controller is used
Signal receiver unit
(Separate type)
Wireless remote controller
and signal receiver unit
are sold as a set.
Simultaneous air conditioning of two rooms and ventilation grille (ventilation opening)
(This feature also applies to duct connection middle static pressure type.)
When air conditioning two rooms simultaneously, the
air discharged into each room must be circulated back
to the air conditioner. To achieve this, a ventilation
duct should be installed for each room or one of the
indicated ventilation grilles should be installed on the
partitioning wall or under the door between the rooms.
Partitioning wall
Door-installed
ventilation grille
Wall-installed
ventilation grille
Under-door cutout
Ventilation grille
Ventilation grille
Under-door cutout
Ventilates air through
the partitioning wall.
(See right)
Note: The under-door cutout method should be used only when there is a small volume of airflow.
8
OUTDOOR UNIT
R18NU
R21NU
Quiet Operation
Fitted with wide inlet fan
(Applies to R26NU–51NU)
Fully shaped
aerodynamic
propellers are
designed to
push air with a
large wing
Wide inlet fan
surface. This
provides both high blow volume and
quiet operation with minimal
turbulence.
R26/30NU
R36NU
Slim-design and low-profile
compact outdoor units
Pre charged for up to
15 metres (Applies to R36NU–51NU)
(Applies to R26NU–51NU)
If refrigerant piping length does not exceed
5m (R56NU), 10m (R18NU,R21NU, R26NU),
15m (R36NU, R42NU, R48NU, R51NU),
there is no need for on-site gas charging.
Compactly designed outdoor unit
with interior layout optimised for the
smooth airflow.
Allowed refrigerant pipe length and level difference
Curved Super Aero Grille
restricts the spread of exhaust
gas and fits in the same space
as conventional outdoor units.
Smooth running,
minimal vibration,
low operating sound.
(Equivalent length 50 m)
R21NU
10 m
(Equivalent length 50 m)
R26NU
10 m
(Equivalent length 50 m)
10 m
15 m
15 m
500
30 m
15 m
30 m
15 m
30 m
20m
30 m
20m
30 m
20 m
30 m
20 m
30 m
(Equivalent length 50 m)
(Equivalent length 50 m)
(Equivalent length 50 m)
R48NU
15 m
(Equivalent length 50 m)
20 m
R51NU
15 m
30 m
(Equivalent length 50 m)
20 m
R56NU
5m
(Equivalent length 70 m)
50 m
30 m
(mm)
(Applies to R26NU–36NU)
Max. level
difference
Note:
1Additional
refrigerant charging is required if the
refrigerant pipe is longer than the length.
4-direction piping offers
greater layout freedom
(Applies to R26NU–56NU)
Piping can be run from the front,
bottom, right or rear surface
according to how the unit is installed.
Takes installation environment into consideration
Even less operation sound
(In case of V1: 220V, Y1: 380V) dB(A)
9
10 m
R42NU
(Applies to R36NU–56NU)
Outdoor unit
Sound level
R18NUV1
49
54
57
55
57
59
59
R51NUY1
R18NU
50
Equipped with scroll
compressor for
quiet operation
R48NUY1
Max. length
R36NU
To suppress
turbulence and
achieve quiet
operation, the
curved ribs of
the grille are
optimised to meet the outflow of air.
R42NUY1
Pre charged
*1
R30NU
(Applies to R26NU–51NU)
R30NUV1
R30NUY1
R36NUV1
R36NUY1
R48/51NU
Installation and maintenance
Compact
Fitted with Super Aero Grille
R21NUV1
R42NU
Durability
Heat exchange fins provided with anti-corrosion treatment
To achieve increased durability by
improved resistance to salt corrosion
and atmospheric pollution, coated
PE fins (with special acryl
pretreatment) are used for the heat
exchanger of the outdoor unit.
Construction
Non-treated fin
Aluminium
PE fin
Hydrophilic film
Aluminium
Corrosion resistant
acrylic resin
Abundance of functions that provide comfortable
air-conditioning in stores and offices.
See the list of main functions given on the page introducing each indoor unit.
Work and Servicing
Comfort
Drain pump mechanism
Auto-swing
Delivers comfortable airconditioning to all areas,
near to and far from the airconditioner.
Air discharge direction angle can
be set (fixed setting)
Steeper gradient realises more
efficient condensate drainage.
High-lift is especially useful for
long lengths of drain piping.
Pre charged for up to 15 metres
Swing pattern selection
If refrigerant piping length does not exceed 15 m, there is no
need for on-site gas charging. (Applies to R36NU–51NU)
(draft prevention, standard, ceiling soiling prevention)
You can freely set 3 air discharge positions by remote
controller.
(1) Air direction range in
standard position
(2) Air direction range in draft
prevention position
Ceiling soiling prevention function
Daikin's innovative air discharge mechanism keeps airflow
away from the ceiling. Ceiling cleaning is less frequently
required.
Filter sign
The filter sign warns you when it is time to clean the filter.
(3) Air direction range in ceiling
soiling prevention position
Switchable fan speed
High setting provides maximum reach while low setting
minimises drafts.
Programme "Dry"
Dehumidification is microprocessor controlled to prevent
abrupt and uncomfortable changes in air temperature. Useful
for reducing uncomfortable humidity without uncomfortable
cooling of the room.
High-ceiling application
Delivers air-conditioning comfort all the way down to the floor
in air-conditioning zones with high ceilings.
*When using a wired remote controller the sign is displayed in the LCD. When using a
wireless remote controller the filter sign lamp illuminates on the signal receiver unit.
Control features
Auto-restart
If there is a power outage while the equipment is operating,
operations will restart in the same mode as before the power
cut when electricity is restored.
Others
PE fin
To achieve increased durability by improved resistance to salt
corrosion and atmospheric pollution, coated PE fins (with
special acryl pretreatment) are used for the heat exchanger of
the outdoor unit. In high corrosive areas, regular maintenance
needs to be carried out.
Options
Note:When units are installed on high ceilings, depending on the model, various restrictions
concerning maximum height, air discharge direction, and choice of options may apply.
Timer selector
Operation starts when the preset time of the ON timer elapses
and stops when the preset time of the OFF timer elapses.
High-efficiency filter unit
Two types are available: 65% and 90% colorimetry.
Ultra long-life filter
Requires no maintenance for about 4 years* (10,000 h) in
stores and offices. * For dust concentration of 0.15 mg/m3
Long-life filter
Mould prevention
Mould resistant treatment for filter
Sanitary filter has mould resistant treatment.
Mould proofing drain pan
Mould proofing maintains hygiene by preventing growth in
highly humid conditions.
Maintenance is not required for one year (two years when a
ceiling mounted cassette type is used).
Fresh-air intake kit
You can provide air-conditioning with fresh air from outside.
Convenient for places where a ventilation fan cannot be installed.
Note: *Connecting ducts, insect nets, fire dampers, air filters, and other parts
should, as required, be procured locally.
**Outside Air fan interlocked with air conditioning unit is necessary. Optional
PCB(KRP1C63)is required for interlocking.
***It is recommended that the volume of outdoor air introduced through the kit
is limited to 10% of the maximum airflow rate of the indoor unit. Introducing
higher quantities will increase the operating noise and may also influence
temperature sending.
10
CEILING MOUNTED CASSETTE TYPE
Outdoor unit
Power supply
Cooling capacity 1a/1b
Btu/h
kW
kcal/h
kW
Power consumption 1a/1b
Colour
Indoor
unit
Outdoor
unit
Unit
Decoration panel
m3/min
Airflow rate (H/L)
cfm
Sound level (H/L) (220V) 2
dB(A)
mm
Dimensions Unit
(HXWXD)
mm
Decoration panel
kg
Unit
Machine weight
kg
Decoration panel
°CWB
Operation range
Colour
Compressor Type
Motor output
kW
Refrigerant charge (R-22)
Sound level 2, 3
Dimensions (HXWXD)
Machine weight
Operation range
Liquid (Flare)
Piping
connections
Gas (Flare)
Drain
Indoor unit
Outdoor unit
Max. interunit piping length
Max. installation level difference
Heat insulation
30
26
48
36
42
FHC30NUV1
FHC26NUV1
FHC48NUV1
FHC36NUV1
FHC42NUV1
R30NUV1
R26NUV1
R36NUV1
R48NUY1
R42NUY1
R18NUV1
R21NUV1
R30NUY1
R26NUY1
R36NUY1
V1: 1 Phase, 220–240 V, 50 Hz Y1: 3 Phase, 380–415 V, 50 Hz
18,100/18,000 21,200/21,000 26,300/26,000 30,400/30,000 36,500/36,000 42,700/42,000 49,100/48,000
5.3/5.3
6.2/6.2
7.7/7.6
8.9/8.8
10.7/10.6
12.5/12.3
14.4/14.1
4,580/4,560
5,340/5,290
6,630/6,550
7,670/7,570
9,200/9,100
10,800/10,600 12,400/12,100
2.03/2.02
2.46/2.45
3.07/3.07
3.45/3.45
4.04/4.04
4.79/4.79
5.49/5.49
---------White
15/11
19/14
19/14
28/21
33/24
33/24
33/24
529/388
670/494
670/494
988/741
1,164/847
1,164/847
1,164/847
33/29
35/30
35/30
39/34
42/36
42/36
42/36
230X840X840 230X840X840 230X840X840 288X840X840 288X840X840 288X840X840 288X840X840
40X950X950
40X950X950
40X950X950
40X950X950
40X950X950
40X950X950
40X950X950
28
28
24
24
24
28
28
5
5
5
5
5
5
5
14 to 28
Ivory white
Ivory
Hermetically sealed scroll type
Hermetically sealed rotary type
4.50
1.7
2.2
2.5
3.00
2.5
3.75
2.6
1.20
1.50
2.3
2.0
2.3
2.4
(Charged for 10 m) (Charged for 10 m) (Charged for 10 m) (Charged for 10 m) (Charged for 15 m) (Charged for 15 m) (Charged for 15 m)
18
FHC18NUV1
Indoor unit
Model
Name
kg
21
FHC21NUV1
59
57
57
49
54
55
57
dB(A)
mm
540X750X270 685X800X300 770X900X320 770X900X320 1,170X900X320 1,170X900X320 1,345X900X320
92
kg
42
61
70 (V1), 69 (Y1) 70 (V1), 69 (Y1) 81 (V1), 79 (Y1)
87
°CDB
21 to 46
o/ 9.5
mm
o/ 6.4
o/ 6.4
o/ 9.5
o/ 9.5
o/ 9.5
o/ 9.5
o/ 19.1
mm
o/ 15.9
o/ 15.9
o/ 15.9
o/ 15.9
o/ 19.1
o/ 19.1
mm I.Do/ 25XO.Do/ 32 I.Do/ 25XO.Do/ 32 I.Do/ 25XO.Do/ 32 I.Do/ 25XO.Do/ 32 I.Do/ 25XO.Do/ 32 I.Do/ 25XO.Do/ 32 I.Do/ 25XO.Do/ 32
mm
o/ 26.0 (Hole)
o/ 18.0 (Hole)
o/ 18.0 (Hole)
o/ 26.0 (Hole)
o/ 26.0 (Hole)
o/ 26.0 (Hole)
o/ 26.0 (Hole)
30 (equivalent length 50 m)
m
20
m
15
Both liquid and gas piping
Note :
1
Rated cooling capacities are based on the following conditions:
1a
Indoor temp., 27°CDB, 19.5°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 7.5 m (horizontal).
1b
Indoor temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 7.5 m (horizontal).
2
Anechoic chamber conversion value, measured according to JIS parameters and criteria.
During operation these values are somewhat higher owing to ambient conditions.
3
In case of V1: 220V, Y1: 380V.
CEILING SUSPENDED TYPE
Outdoor unit
Power supply
Cooling capacity 1a/1b
Power consumption 1a/1b
Colour
Airflow rate (H/L)
Indoor
unit
Outdoor
unit
Sound level (H/L) (220V) 2
Dimensions (HXWXD)
Machine weight
Operation range
Colour
Compressor Type
Motor output
Refrigerant charge (R-22)
Sound level
Dimensions (HXWXD)
Machine weight
Operation range
Piping
Liquid (Flare)
connections
Gas (Flare)
Drain
Indoor unit
Outdoor unit
Max. interunit piping length
Max. installation level difference
Heat insulation
2, 3
48
36
42
26
30
FH48NUV1
FH36NUV1
FH42NUV1
FH26NUV1
FH30NUV1
R36NUV1
R26NUV1
R30NUV1
R21NUV1
R42NUY1
R48NUY1
R36NUY1
R26NUY1
R30NUY1
V1: 1 Phase, 220–240 V, 50 Hz Y1: 3 Phase, 380–415 V, 50 Hz
36,500/36,000
30,400/30,000
42,700/42,000
49,100/48,000
21,200/21,000
26,300/26,000
10.7/10.6
8.9/8.8
12.5/12.3
14.4/14.1
6.2/6.2
7.7/7.6
9,200/9,100
7,670/7,570
10,800/10,600
12,400/12,100
5,340/5,290
6,630/6,550
5.50/5.50
2.72/2.71
3.48/3.48
4.06/4.06
4.83/4.83
3.10/3.10
White
42-44/24-26
22-23/9-20
26-27/22-23
32-34/22-24
38-40/23-25
22-23/9-20
776-811/317-706 776-811/317-706 917-953/776-811 1,129-1,200/776-847 1,341-1,412/811-882 1,482-1,553/847-917
49/43
46/40
45/40
48/42
44/40
44/40
195X1,590X680
195X1,400X680
195X1,590X680
195X1,590X680
195X1,160X680
195X1,160X680
35
26
26
32
35
35
14 to 28
Ivory white
Ivory
Hermetically sealed scroll type
Hermetically sealed rotary type
4.50
2.2
2.5
2.5
3.00
3.75
2.6
1.50
2.3
2.3
2.0
2.4
(Charged for 10 m) (Charged for 10 m) (Charged for 10 m) (Charged for 15 m) (Charged for 15 m) (Charged for 15 m)
21
FH21NUV1
Indoor unit
Model
Name
Btu/h
kW
kcal/h
kW
m3/min
cfm
dB(A)
mm
kg
°CWB
kW
kg
dB(A)
mm
kg
°CDB
mm
mm
mm
mm
m
m
54
685X800X300
61
57
770X900X320
70 (V1), 69 (Y1)
o/ 6.4
o/ 15.9
I.D o/ 20XO.D o/ 26
o/ 18.0 (Hole)
o/ 9.5
o/ 15.9
I.Do/ 20XO.D o/ 26
o/ 26.0 (Hole)
15
Note :
1
Rated cooling capacities are based on the following conditions:
1a
Indoor temp., 27°CDB, 19.5°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 7.5 m (horizontal).
1b
Indoor temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 7.5 m (horizontal).
2
Anechoic chamber conversion value, measured according to JIS parameters and criteria.
During operation these values are somewhat higher owing to ambient conditions.
3
In case of V1: 220V, Y1: 380V.
11
57
55
770X900X320
1,170X900X320
70 (V1), 69 (Y1)
81 (V1), 79 (Y1)
21 to 46
o/ 9.5
o/ 9.5
o/ 15.9
o/ 19.1
I.D o/ 20XO.Do/ 26 I.Do/ 20XO.D o/ 26
o/ 26.0 (Hole)
o/ 26.0 (Hole)
30 (equivalent length 50 m)
20
Both liquid and gas piping
57
1,170X900X320
87
59
1,345X900X320
92
o/ 9.5
o/ 19.1
I.D o/ 20XO.D o/ 26
o/ 26.0 (Hole)
o/ 9.5
o/ 19.1
I.Do/ 20XO.D o/ 26
o/ 26.0 (Hole)
DUCT CONNECTION MIDDLE STATIC PRESSURE TYPE
Indoor unit
Model
Name
Outdoor unit
Power supply
Cooling capacity 1a/1b
Power consumption 1a/1b
Colour
Fan Airflow rate (H)
Indoor
unit
Rated external static pressure
Sound level (H/L) (220V) 2
Dimensions (HXWXD)
Machine weight
Operation range
Colour
Outdoor
Compressor Type
unit
Motor output
Refrigerant charge (R-22)
Sound level 2, 3
Dimensions (HXWXD)
Machine weight
Operation range
Piping
Liquid (Flare)
connections
Gas (Flare)
Drain
Indoor unit
Outdoor unit
Max. interunit piping length
Max. installation level difference
Heat insulation
Btu/h
kW
kcal/h
kW
m3/min
cfm
mmH2O
dB(A)
mm
kg
°CWB
kW
kg
dB(A)
mm
kg
°CDB
mm
mm
mm
mm
m
m
26
48
51
30
36
42
FDMG26PUV1 FDMG30PUV1 FDMG36PUV1 FDMG42PUV1 FDMG48PUV1 FDMG51PUV1
FDMG26NUV1 FDMG30NUV1 FDMG36NUV1 FDMG42NUV1 FDMG48NUV1 FDMG51NUV1
R30NUV1
R36NUV1
R26NUV1
R48NUY1
R51NUY1
R42NUY1
R30NUY1
R36NUY1
R26NUY1
V1: 1 Phase, 220–240 V, 50 Hz Y1: 3 Phase, 380–415 V, 50 Hz
26,300/26,000 30,400/30,000 36,500/36,000 42,700/42,000 49,100/48,000 52,200/51,000
8.9/8.8
12.5/12.3
7.7/7.6
15.3/15.0
14.4/14.1
10.7/10.6
7,670/7,570
10,800/10,600 12,400/12,100 13,200/12,900
6,630/6,550
9,200/9,100
3.15/3.15
3.46/3.46
4.16/4.16
4.84/4.84
5.55/5.55
5.90/5.90
---------42
42
23
34
37
42
1,482
1,482
811
1,200
1,306
1,482
8.5
10.1
9.8
8.0
8.0
9.8
46/37
47/37
42/38
44/36
45/37
46/37
305X1,350X680 305X1,550X680 305X1,550X680 305X1,550X680 305X1,550X680 305X1,900X680
43
51
52
52
52
58
14 to 28
Ivory
Hermetically sealed rotary type
Hermetically sealed scroll type
2.5
4.50
4.50
2.5
3.00
3.75
2.3(Charged for 10 m) 2.3(Charged for 10 m) 2.0(Charged for 15 m) 2.4(Charged for 15 m) 2.6(Charged for 15 m) 2.7 (Charged for 15 m)
57
57
59
59
55
57
770X900X320 1,170X900X320 1,170X900X320 1,345X900X320 1,345X900X320
770X900X320
87
92
93
70 (V1), 69 (Y1) 70 (V1), 69 (Y1) 81 (V1), 79(Y1)
21 to 46
o/ 9.5
o/ 9.5
o/ 9.5
o/ 9.5
o/ 9.5
o/ 9.5
o/ 15.9
o/ 19.1
o/ 19.1
o/ 19.1
o/ 19.1
o/ 15.9
3/4B (I.D o/ 21.6XO.D o/ 27.2)
o/ 26.0 (Hole)
o/ 26.0 (Hole)
o/ 26.0 (Hole)
o/ 26.0 (Hole)
o/ 26.0 (Hole)
o/ 26.0 (Hole)
30 (equivalent length 50 m)
20
Both liquid and gas piping
56
FDMG56PUV1
FDMG56NUV1
R56NUY1
57,000/56,000
16.7/16.4
14,400/14,100
6.45/6.45
42
1,482
9.8
47/37
305X1,900X680
58
4.50
2.8 (Charged for 5 m)
56
1,345X880X370
114
o/ 9.5
o/ 19.1
o/ 26.0 (Hole)
50 (equivalent length 70 m)
30
Note :
1
Rated cooling capacities are based on the following conditions:
1a
Suction temp., 27°CDB, 19.5°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 7.5 m (horizontal).
1b
Suction temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 7.5 m (horizontal).
2
Anechoic chamber conversion value, measured according to JIS parameters and criteria.
During operation these values are somewhat higher owing to ambient conditions.
3
In case of V1: 220V, Y1: 380V.
DUCT CONNECTION LOW STATIC PRESSURE TYPE
Indoor unit
Model
Name
Outdoor unit
Power supply
Cooling capacity 1a/1b
Power consumption 1a/1b
Colour
Airflow rate (H/L)
Indoor
unit
Outdoor
unit
Rated external static pressure
Sound level (H/L) (220V) 2
Dimensions (HXWXD)
Machine weight
Operation range
Colour
Compressor Type
Motor output
Refrigerant charge (R-22)
Sound level 2, 3
Dimensions (HXWXD)
Machine weight
Operation range
Liquid (Flare)
Piping
connections
Gas (Flare)
Drain
Indoor unit
Outdoor unit
Max. interunit piping length
Max. installation level difference
Heat insulation
Btu/h
kW
kcal/h
kW
m3/min
cfm
mmH2O
dB(A)
mm
kg
°CWB
kW
kg
dB(A)
mm
kg
°CDB
mm
mm
mm
mm
m
m
18
FDBG18PUV1
21
FDBG21PUV1
26
FDBG26PUV1
R26NUV1
R18NUV1
R21NUV1
R26NUY1
V1: 1 Phase, 220–240 V, 50 Hz Y1: 3 Phase, 380–415 V, 50 Hz
18,100/18,000
21,200/21,000
26,300/26,000
5.3/5.3
6.2/6.2
7.7/7.6
4,580/4,560
5,340/5,290
6,630/6,550
2.12/2.11
2.73/2.72
3.33/3.33
---------13/11
18/15
18/15
458/388
635/529
635/529
2.0
2.0
2.0
41/38
43/40
43/40
260X900X580
260X1,300X580
260X1,300X580
25
32
32
14 to 28
Ivory white
Ivory
Hermetically sealed rotary type
1.7
2.5
2.2
1.13
2.3
1.55
(Charged for 10 m)
(Charged for 10 m)
(Charged for 10 m)
49
540X750X270
42
54
685X800X300
61
21 to 46
o/ 6.4
o/ 15.9
3/4B (I.D o/ 21.6XO.D o/ 27.2)
o/ 18.0 (Hole)
30 (equivalent length 50 m)
o/ 6.4
o/ 15.9
o/ 18.0 (Hole)
15
57
770X900X320
70 (V1), 69 (Y1)
o/ 9.5
o/ 15.9
o/ 26.0 (Hole)
20
Both liquid and gas piping
Note :
1
Rated cooling capacities are based on the following conditions:
1a
Suction temp., 27°CDB, 19.5°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 7.5 m (horizontal).
1b
Suction temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 7.5 m (horizontal).
2
Anechoic chamber conversion value, measured according to JIS parameters and criteria.
During operation these values are somewhat higher owing to ambient conditions.
3
In case of V1: 220V, Y1: 380V.
12
Indoor unit
CEILING MOUNTED CASSETTE TYPE
Type
Item
Decoration panel
Sealing member for air discharge outlet
Panel spacer
Fresh air intake kit Chamber Without the T-joint pipe and fan
type
With the T-joint pipe,without fan
Direct installation type
High-efficiency filter
(Colorimetric method 65%)
(Colorimetric method 90%)
Replacement
(Colorimetric method 65%)
high-efficiency filter
(Colorimetric method 90%)
High-efficiency filter chamber
Replacement long-life filter
Ultra long-life filter
Replacement ultra long-life filter
Branch duct chamber
Remote controller
Wired type2
Wireless type
Central remote controller3
Unified ON/OFF controller3
Schedule timer3
Adaptor for wiring4
Wiring adaptor for electrical appendices3
Interface adaptor for SkyAir series
Installation box for adaptor PCB
FHC18NU
FHC21NU
FHC26NU
FHC30NU
FHC36NU
FHC42NU
FHC48NU
BYC125K-W1, BYC125K-W2
KDBH55D160W
KDBP55H160WA
KDD55DA160
KDD55DA160K
KDDJ55X160
KAF556DA160
KAF557DA160
KAFP552B160
KAFP553B160
KAF556DA80
KAF557DA80
KAFP552B80
KAFP553B80
KDDF55D160
KAF551K160
KAFP55D160
KAF55K160H
KDJ55K160
KDJ55K80
BRC1C61
BRC7C613W
DCS302CA61
DCS301BA61
DST301BA61
KRP1BA57
KRP4AA53
DTA102A52
KRP1B98
Note:
1
Required for installing high-efficiency filter or ultra long-life filter.
2
Wiring for wired remote controller to be procured locally.
3
This optional accessory requires DTA102A52.
4
Installation box for adaptor PCB (KRP1B98) is necessary.
CEILING SUSPENDED TYPE
Item
Replacement long-life filter Resin net
L-type piping kit (for upward direction)
Wired type1
Remote controller
Wireless type
Type
FH21NU
FH26NU
FH30NU
FH36NU
KAF501DA112
KAF501DA80
KHFJ5F80
FH42NU
FH48NU
KAF501DA160
KHFJ5F160
BRC1NU61
BRC7NU66
Note:
1
Wiring for wired remote controller to be procured locally.
DUCT CONNECTION
Item
Remote controller
MIDDLE STATIC PRESSURE TYPE
Type
FDMG26PU
FDMG30PU
FDMG36PU
Wired type1
Wireless type
FDMG42PU
FDMG48PU
FDMG51PU
FDMG56PU
FDMG48NU
FDMG51NU
FDMG56NU
BRC1C61
BRC4C64
Note:
1
Wiring for wired remote controller to be procured locally.
Type
Item
FDMG26NU
FDMG30NU
FDMG36NU
KRC47-1A
KRC47-2A
Remote controller
Digital remote controller
DUCT CONNECTION
Item
Remote controller
FDMG42NU
LOW STATIC PRESSURE TYPE
Type
FDBG18PU
FDBG21PU
Wired type1
Wireless type
FDBG26PU
BRC1C61
BRC4C64
Note:
1
Wiring for wired remote controller to be procured locally.
Outdoor unit
Item
Drain piping kit
Central drain plug
13
Type
R18NU
R21NU
-------
KIS95
-------
R26NU
R30NU
R36NU
R42NU
------KKPJ5F180
R48NU
R51NU
R56NU
DIMENSIONS (Unit: mm)
CEILING MOUNTED CASSETTE TYPE
FHC18NUV1 / 21NUV1 / 26NUV1 / 30NUV1 / 36NUV1 / 42NUV1 / 48NUV1
! "
#$$ %
[FHC30NUV1-48NUV1]
**
*
A
B
C
D
E
----
----
FHC18NUV1-26NUV1
230 240 165
FHC30NUV1-48NUV1
288 298 195 165 195
! "
#$$ %
Notes:
1
Location of unit's Name Plate
For Main body: Switch Box Cover inside surface of suction grille.
For decoration panel: Panel frame inside surface of suction grille.
2
When installing an optional accessory, refer to the
installation drawings.
For fresh air intake kit
Inspection port is necessary.
For high efficiency filter unit
Inspection port is not necessary.
3
In case of using wireless remote controller, this position will
be a signal receiver. Refer to the drawing of wireless remote
controller in detail.
** *
** *
+ , , - . $ ** */
' ( ) )
# &$%
**
*
1 Liquid pipe connection
2 Gas pipe connection
3 Drain pipe connection
4 Power supply connection
0. $
5 Remote control code and control wiring connection
6 Air discharge grille
*
0. $
*
0. $ 1$
2
!
!
! "
#$$ %
[FHC18NUV1-26NUV1]
52#6%
4
1$ $
6
, $,
3/
6
, $,
1$ $
7 Air suction grille
8 Port for water supply
9 Corner decoration cover
10 Drain hose
CEILING SUSPENDED TYPE
FH21NUV1 / 26NUV1 / 30NUV1 / 36NUV1 / 42NUV1 / 48NUV1
10
Hanging bolt
4-M8~M10
115 60
8
15
1
5 11
195
6
300 or more
(Required space)
55
B
30 or more
(Service space)
30 or more
(Service space)
The Front
Obstacle
Floor side
Brand name plate
(Note.2)
Drain pipe connection VP20
(For left piping)
225
275
300
275
6
80
3
2
Notes:
1
Location of unit's Name Plate: Bottom of fan housing inside the suction grille.
2
In case of using wireless remote controller, this position will be a signal receiver.
Refer to the drawing of wireless remote controller in detail.
3
The remote control code is the standard <about 3 m outside the machine> attached.
(0.5 mm2 2 wicks O.D. 5.4)
(It is attached to VRV.)
7
5
80
105
170
4
65
Position slit hole for taking out in piping back
(View from the front)
127
A
(Hanging position)
680
65
60
80
105
5
135 (Required space)
1550 1590
50
Position : Hole of wall for taking out in piping back
(View from the front)
40
FH48NUV1
145 60
90
155
1550 1590
40 135
FH42NUV1
9
12
85
102
160
185
192 36
1550 1590
For height installaion
From the floor side 2500 or more 155 5
(Required space)
1360 1400
FH36NUV1
210
1120 1160
FH30NUV1
260
FH26NUV1
13
170
105
90
18 17 16 142 58
B
1120 1160
(Hanging
position)
A
FH21NUV1
4 o/ 45
55
14
1 Air discharge grille
2 Air suction grille
3 Air filter
4 Gas pipe connection
5 Liquid pipe connection
6 Drain pipe conneciton
7 Earth terminal (inside the electric components box) (M4)
8 Suspension bracket
9 Backward piping and wiring connection opening lid
10 Upward piping and wiring connection opening lid
11 Right side pipe connection
12 Left back drain pipe connection
13 Left side drain pipe connection
14 Right side drain pipe connection
15 Hole of wall for taking out in piping back
16 Upward drain pipe connection
17 Upward gas pipe connection
18 Upward liquid pipe connection
14
DIMENSIONS (Unit: mm)
DUCT CONNECTION MIDDLE STATIC PRESSURE TYPE
FDMG26PUV1
$
!"#
!"#
& %
1
2
3
4
5
6
7
8
Note: 1Location of unit's Name Plate: Chamber cap
Liquid pipe connection
Gas pipe connection
Drain pipe connection
Ground terminal
Switch box
Control wiring intake (for remote controller)
Control wiring intake (for outdoor unit)
Suspension bracket
FDMG30PUV1 / 36PUV1 / 42PUV1 / 48PUV1 / 51PUV1 / 56PUV1
"
Liquid pipe connection
Gas pipe connection
Drain pipe connection
Ground terminal
5
6
7
8
)
Switch box
Control wiring intake (for remote controller)
Control wiring intake (for outdoor unit)
Suspension bracket
Note: 1Location of unit's Name Plate: Chamber cap
A
B
C
E
F
D
FDMG30NUV1/36NUV1/42NUV1/48NUV1 1550 1353 1403 1334 1314 7XP150=1050
FDMG51NUV1/56NUV1
1900 1703 1753 1684 1664 9XP150=1350
15
G
18-M4
Holes
22-M4
Holes
H
J
K
M
L
1550 1353 1337 1321 7XP150=1050
1900 1703 1687 1671 9XP150=1350
N
O
20-M4
263
24-M4
269
Holes
Holes
$
!
'
(
&
#
*
+
1
2
3
4
, -
%
DUCT CONNECTION MIDDLE STATIC PRESSURE TYPE
FDMG26NUV1
# %#
#& "
! "#$
! "#$
1
2
3
4
5
6
7
8
Note: 1Location of unit's Name Plate: Chamber cap
Liquid pipe connection
Gas pipe connection
Drain pipe connection
Ground terminal
Switch box
Control wiring intake (for remote controller)
Control wiring intake (for outdoor unit)
Suspension bracket
FDMG30NUV1 / 36NUV1 / 42NUV1 / 48NUV1 / 51NUV1 / 56NUV1
'
&
(
$
"
%
)
#
+
!
' '*
,
' '*
1
2
3
4
Liquid pipe connection
Gas pipe connection
Drain pipe connection
Ground terminal
5
6
7
8
Switch box
Control wiring intake (for remote controller)
Control wiring intake (for outdoor unit)
Suspension bracket
Note: 1Location of unit's Name Plate: Chamber cap
A
B
C
E
F
D
FDMG30NUV1/36NUV1/42NUV1/48NUV1 1550 1353 1403 1334 1314 7XP150=1050
FDMG51NUV1/56NUV1
1900 1703 1753 1684 1664 9XP150=1350
G
18-M4
Holes
22-M4
Holes
H
J
K
M
L
1550 1353 1337 1321 7XP150=1050
1900 1703 1687 1671 9XP150=1350
N
20-M4
Holes
24-M4
Holes
16
DIMENSIONS (Unit: mm)
DUCT CONNECTION LOW STATIC PRESSURE TYPE
FDBG18PUV1 / 21PUV1 / 26PUV1
(
5
6
7
8
Liquid pipe connection
Gas pipe connection
Drain pipe connection
Ground terminal
'
#
"
!
$
%
&
Switch box
Control wiring intake (for remote controller)
Control wiring intake (for outdoor unit)
Suspension bracket
Note: 1Location of unit's Name Plate: Chamber cap
FDBG18PUV1
FDBG21PUV1/26PUV1
17
.
1
2
3
4
/ A
B
C
F
D
E
900 704 755 684 664 3XP150=450
1300 1104 1155 1084 1064 6XP150=900
G
500
700
H
127
102
I
)
*
+
,
J
K
L
M
3XP150=450 674 688 704 900
6XP150=900 1074 1088 1104 1300
N
O
10-M4 12-M4
Holes
Holes
16-M4 18-M4
Holes
Holes
OUTDOOR UNIT
R18NUV1
*
+)
-
*
.
)*
-+
)*
)
!
)-
.
!
*)
+
+
+!
*+
)*
/
!
"# $
% +
!
&'( +
)*
& ,
.
,
+
+
,
+
+
R21NUV1
Holes for anchor bolts
(M8 or M10)
330
350
98
31
269
540
130
2-Drain outlet
800
Outdoor
air thermostat
300
15
Earth terminal
(M4)
Power intake
Name plate
685
645
Liquid
stop valve
Liquid pipe
95 70
Service port
Gas
stop valve
75
100
Gas pipe
A
50
50
A
100
50
150
H
Minimum space for air passage
H
H 1000
H 1000
A
300
600
18
DIMENSIONS (Unit: mm)
OUTDOOR UNIT
R26NUV1/Y1
R30NUV1/Y1
1 Gas pipe connection
2 Liquid pipe connection
3 Grounding terminal M5(in switch box)
4 Refrigerant piping intake
5 Power supply wiring intake
6 Control wiring intake
7 Drain connection
Note: In some circumstances, with certain machine types,
it may not be possible to attach the supplied piping.
R36NUV1/Y1
19
1
2
3
4
5
6
7
8
Gas pipe connection
Liquid pipe connection
Service port(in the unit)
Grounding terminal
Refrigerant piping intake
Power supply wiring intake
Control wiring intake
Drain pipe connection
OUTDOOR UNIT
R42NUY1, R48NUY1, R51NUY1
A
B
C
D
R42NUY1
1170
54
113
579
R48NUY1/51NUY1
1345
55
—
—
3 Service port (in the unit)
4 Grounding terminal M5 (in switch box)
5 Refrigerant piping intake
6 Power supply wiring intake
7 Control wiring intake
8 Drain pipe connection
1 Gas pipe connection
2 Liquid pipe connection
R56NUY1
1 Gas pipe connection
2 Liquid pipe connection
3 Service port(in the unit)
4 Grounding terminal M5(in switch box)
5 Refrigerant piping intake
6 Power supply wiring intake
7 Control wiring intake
8 Drain outlet
20
DIMENSIONS
(Unit: mm)
REMOTE CONTROLLER
*! # !##
*! # ,
## &
?2## $ &/@
)#!#- *= ## &
*=
"# #
+6& ! #
*! #
,
*= */-#
#- "# #
0
)#!#- *! # ,
## &
?2## $ &/@
*= ## &
), >#
*= *=
0
*! #
*! #
,
9
80
*= A; 8 0:
9;
$, #- ##-
/ & *! # !##
8
;
8
:8
8
: 8
9
*! # ## &
'()*'+ %'
( 0 *! # #
# ,0 , / & 0
/# / 1# $, ,, )
2#& ,3#4 !! !
.
00 !!
) #-,
!
5 &# 6&#- 7 4 , $
#& ,3#4 !! !
990
;
9
%
%
%
*
:
9
:8
90
(
), !## / ,0
9
),&-, ,
"# $#
! #
# # < !!
%
:
9
8
9
! #&
% ! ;
&
,
:
21
89
9
8
:
7 ,# ;
= 8:0
#- ##-
= / ###
(#4 # ! ,# :
"
= # , =# / #
#,0
, 9 ! &# , $ , /
!/&##
[Space required for outdoor unit installation] (Unit: mm)
Dimensions inside brackets [ ] indicate case where air direction adjustment guide is adjusted downward.
The values represent the case for the R26 type through R56 type.
The dimensions in ( ) are for the R36 and R56 type (The unit values is mm. )
In case of R56 model, the values in < > are those when the air discharge direction of the grille is downward.
For R26NU-56NU
When there is an obstruction
on the inlet side
When there is an obstruction
on the outlet side
When the overhead space is open
When the overhead space is open
1. For single unit installation
1. For single unit
installation
When there is an
obstruction only
on the inlet side
2. For series installation
(more than two units)
0)
0
0(1
or
ore
500
or m
re
mo
5
When there are
obstructions on
both sides
ore
rm
0o
or m
ore
100
or m
0
10
ore
When there is an obstruction
in the overhead space
re
mo
or
ss
500
or le
1000 or more
100
100
1. For single unit
installation
2. For series installation
(more than two units)
When there are
obstructions on
both sides
0o
ore
2. For series installation
(more than two units)
500
or m
ss
or le
500
1000 or more
100
An obstruction
in the overhead space
rm
ore
200
0)
or m
0
0(3
ore
or
An obstruction
in the overhead space
re
mo
20
ore
rm
0o
100
When there is an obstruction
in the overhead space
When there are obstructions on both
the inlet and outlet sides
1. For single unit installation
500
ss
or le
1000 or more
When there is an
obstruction on the
inlet side
An obstruction
in the overhead space
Pattern 1
When the obstruction on the outlet side is higher than
the unit itself (There is no limit to the height of the
obstruction on the outlet side.)
When the overhead space is open
ore
100
or m
1. For single unit installation
L
H
1000 or more
When there are obstructions
on the inlet side and
ss
or le
both lateral sides
500
For other patterns, please refer
to engineering databook.
An obstruction
in the overhead space
or
mo
L
re
150
or
ore
150
mo
re
or m
2. For series installation (more than two units)
ss
1000 or more
500
or le
An obstruction
in the overhead space
0o
ore
or m
500 1000>
<
)
100
50( more
or
2. For series installation
(more than two units)
L
When there are obstructions
on the inlet side and
both lateral
sides
100
H
L
rm
ore
200
or
re
(3
00
ore
rm
0o >
100 1500
<
0)
(30
200 more
or
ore
rm
)o
00
mo
H
H
150
2
22
Warning
Daikin products are manufactured for export to numerous countries throughout the world. Prior to
purchase, please confirm with your local authorised importer, distributor and/or retailer whether this
product conforms to the applicable standards, and is suitable for use, in the region where the product
will be used. This statement does not purport to exclude, restrict or modify the application of any local
legislation.
Ask a qualified installer or contractor to install this product. Do not try to install the product yourself.
Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion.
Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or
contractor to install those parts and accessories. Use of unauthorised parts and accessories or
improper installation of parts and accessories can result in water or refrigerant leakage, electrical
shock, fire or explosion.
Read the User's Manual carefully before using this product. The User's Manual provides important
safety instructions and warnings. Be sure to follow these instructions and warnings.
If you have any enquiries, please contact your local importer, distributor and/or retailer.
Cautions on product corrosion
1. Air conditioners should not be installed in areas where corrosive gases, such as acid gas or alkaline gas, are produced.
2. If the outdoor unit is to be installed close to the sea shore, direct exposure to the sea breeze should be avoided. If you need to install
the outdoor unit close to the sea shore, contact your local distributor.
Organization:
DAIKIN INDUSTRIES, LTD.
AIR CONDITIONING MANUFACTURING DIVISION
JMI-0107
Scope of Registration:
THE DESIGN/DEVELOPMENT AND MANUFACTURE OF
COMMERCIAL AIR CONDITIONING, HEATING, COOLING,
REFRIGERATING EQUIPMENT, COMMERCIAL HEATING
EQUIPMENT, RESIDENTIAL AIR CONDITIONING
EQUIPMENT, HEAT RECLAIM VENTILATION, AIR
CLEANING EQUIPMENT, MARINE TYPE CONTAINER
REFRIGERATION UNITS, COMPRESSORS AND VALVES.
Organization:
DAIKIN INDUSTRIES
(THAILAND) LTD.
JQA-1452
Scope of Registration:
THE DESIGN/DEVELOPMENT
AND MANUFACTURE OF AIR
CONDITIONERS AND THE
COMPONENTS INCLUDING
COMPRESSORS USED FOR THEM
Dealer
All of the Daikin Group’s business
facilities and subsidiaries in Japan
are certified under the ISO 14001
international standard for
environment management.
Head Office:
Umeda Center Bldg., 2-4-12, Nakazaki-Nishi,
Kita-ku, Osaka, 530-8323 Japan
Tokyo Office:
JR Shinagawa East Bldg., 2-18-1, Konan,
Minato-ku, Tokyo, 108-0075 Japan
http://www.daikin.com/global_ac/
c All rights reserved
Specifications, designs and other content appearing in this brochure are current as of April 2011 but subject to change without notice.
04/11/002 YW• SS