Danfoss VLT Micro Drive FC 51 Manual
Transcription
Danfoss VLT Micro Drive FC 51 Manual
VLT® Micro Drive FC 51 Operating Instructions Contents Contents 1 Safety 5 Safety instructions 5 Software Version and Approvals 6 General Warning 7 Avoid unintended Start 7 Before Commencing Repair Work 8 2 Mechanical Installation Before Starting 9 9 Mechanical Dimensions 3 Electrical Installation 10 11 How to Connect 11 Electrical Installation in General 11 EMC-Correct Installation 12 Mains Connection 12 Motor Connection 13 Control Terminals 14 Connecting to Control Terminals 15 Switches 15 Power Circuit - Overview 15 Load sharing/Brake 16 4 Programming 17 How to Programme 17 Programming with MCT-10 Set-up Software 17 Programming with the LCP 11 or LCP 12 17 Status Menu 19 Quick Menu 19 Quick Menu Parameters 20 Main Menu 24 5 Modbus RTU 25 Modbus RTU Overview 25 Modbus RTU Message Framing Structure 26 Remote Terminal Unit 26 Modbus RTU Message Structure 26 Start/Stop Field 26 Address Field 27 Function Field 27 Data Field 27 MG.02.A4.02 - VLT® is a registered Danfoss trademark 1 VLT® Micro Drive FC 51 Operating Instructions Contents CRC Check Field 27 Coil/Register Addressing 27 How to Control the frequency converter 29 Function Codes Supported by Modbus RTU 29 Exception and Error Codes 29 How to Access Parameters 30 Parameter Handling 30 Storage of Data 30 IND 30 Text Blocks 30 Conversion Factor 30 Parameter Values 30 Examples 30 Read Coil Status (01HEX) 31 Force/Write Single Coil (05HEX) 31 Force/Write Multiple Coils (0FHEX) 32 Read Holding Registers (03HEX) 32 Preset Single Register (06HEX) 33 Preset Multiple Registers (10HEX) 34 Danfoss FC Control Profile 35 Control Word According to FC Profile 35 Explanation of the Control Bits 35 Status Word According to FC Profile (STW) 37 Explanation of the Status Bits 38 Bus Speed Reference Value 39 6 Parameter Overview 2 41 Conversion Index 45 Change during operation 45 2-Set-up 45 Type 45 0-** Operation/Display 46 1-** Load/Motor 47 2-** Brakes 48 3-** Reference/Ramps 49 4-** Limits/Warnings 50 5-** Digital In/Out 51 6-** Analog In/Out 52 7-** Controllers 53 8-** Comm. and Options 54 13-** Smart Logic 55 MG.02.A4.02 - VLT® is a registered Danfoss trademark VLT® Micro Drive FC 51 Operating Instructions Contents 14-** Special Functions 56 15-** Drive Information 57 16-** Data Readouts 58 7 Troubleshooting Alarm, Warning and Extended Status Word 8 Specifications 59 60 61 Mains Supply 61 Other Specifications 63 Special Conditions 65 The Purpose of Derating 65 Derating for Ambient Temperature 65 Derating for Low Air Pressure 65 Derating for Running at Low Speeds 65 Options for VLT Micro Drive FC 51 66 Index 67 MG.02.A4.02 - VLT® is a registered Danfoss trademark 3 1 Safety VLT® Micro Drive FC 51 Operating Instructions 1 4 MG.02.A4.02 - VLT® is a registered Danfoss trademark VLT® Micro Drive FC 51 Operating Instructions 1 Safety 1 Safety 1 1.1.1 High Voltage Warning The voltage of the frequency converter is dangerous whenever it is connected to mains. Incorrect installation of the motor or frequency converter may cause damage to the equipment, serious injury or death. Consequently, it is essential to comply with the instructions in this manual as well as local and national rules and safety regulations. 1.1.2 Safety instructions Prior to using functions directly or indirectly influencing personal safety (e.g. Safe Stop, Fire Mode or other functions either forcing the motor to stop or attempting to keep it functioning) a thorough risk analysis and system test must be carried through. The system tests must include testing failure modes regarding the control signalling (analog and digital signals and serial communication. NB! Before using Fire Mode, contact Danfoss • Make sure the frequency converter is properly connected to earth. • Do not remove mains connections, motor connections or other power connections while the frequency converter is connected to power. • Protect users against supply voltage. • Protect the motor against overloading according to national and local regulations. • The earth leakage current exceeds 3.5 mA. • The [OFF] key is not a safety switch. It does not disconnect the frequency converter from mains. MG.02.A4.02 - VLT® is a registered Danfoss trademark 5 VLT® Micro Drive FC 51 Operating Instructions 1 Safety 1.1.3 Software Version and Approvals 1 Software Version Operating Instructions VLT Micro Drive FC 51 Series This Operating Instructions can be used for all VLT Micro Drive FC 51 frequency converters with software version 2.2x. The software version number can be read in parameter 15-43. 6 MG.02.A4.02 - VLT® is a registered Danfoss trademark VLT® Micro Drive FC 51 Operating Instructions 1 Safety 1.1.4 General Warning 1 Warning: Touching the electrical parts may be fatal - even after the equipment has been disconnected from mains. Also make sure that other voltage inputs have been disconnected (linkage of DC intermediate circuit). Be aware that there may be high voltage on the DC link even when the LEDs are turned off. Before touching any potentially live parts of the frequency converter, wait at least 4 minutes for all sizes. Shorter time is allowed only if indicated on the nameplate for the specific unit. Leakage Current The earth leakage current from the frequency converter exceeds 3.5 mA. According to IEC 61800-5-1 a reinforced Protective Earth connection must be ensured by means of a min. 10mm² Cu or an addtional PE wire - with the same cable cross section as the Mains wiring - must be terminated separately. Residual Current Device This product can cause a DC current in the protective conductor. Where a residual current device (RCD) is used for extra protection, only an RCD of Type B (time delayed) shall be used on the supply side of this product. See also Danfoss Application Note on RCD, MN. 90.GX.YY. Protective earthing of the frequency converter and the use of RCDs must always follow national and local regulations. Motor overload protection is possible by setting Parameter 1-90 Motor thermal protection to the value ETR trip. For the North American market: ETR functions provide class 20 motor overload protection, in accordance with NEC. Installation in high altitudes: For altitudes above 2 km, please contact Danfoss regarding PELV. 1.1.5 IT Mains IT Mains Installation on isolated mains source, i.e. IT mains. Max. supply voltage allowed when connected to mains: 440 V. As an option, Danfoss offers line filters for improved harmonics performance. 1.1.6 Avoid unintended Start While the frequency converter is connected to mains, the motor can be started/stopped using digital commands, bus commands, references or via the Local Control Panel. • Disconnect the frequency converter from mains whenever personal safety considerations make it necessary to avoid unintended start of any motors. • To avoid unintended start, always activate the [OFF] key before changing parameters. MG.02.A4.02 - VLT® is a registered Danfoss trademark 7 VLT® Micro Drive FC 51 Operating Instructions 1 Safety 1.1.7 Disposal instruction 1 Equipment containing electrical components must not be disposed of together with domestic waste. It must be separately collected with electrical and electronic waste according to local and currently valid legislation. 1.1.8 Before Commencing Repair Work 1. Disconnect FC 51 from mains (and external DC supply, if present.) 2. Wait for 4 minutes for discharge of the DC-link. 3. Disconnect DC bus terminals and brake terminals (if present) 4. Remove motor cable 8 MG.02.A4.02 - VLT® is a registered Danfoss trademark VLT® Micro Drive FC 51 Operating Instructions 2 Mechanical Installation 2 Mechanical Installation 2.1 Before Starting 2 2.1.1 Checklist When unpacking the frequency converter, make sure that the unit is undamaged and complete. Check that the packaging contains the following: • VLT Micro Drive FC 51 • Quick Guide Optional: LCP and/or de-coupling plate. Illustration 2.1: Content of box. 2.2 Side-by-Side Installation The frequency converter can be mounted side-by-side for IP 20 rating units and requires 100 mm clearance above and below for cooling. Regarding surroundings in general, please see chapter 7. Specifications. Illustration 2.1: Side-by-side installation. MG.02.A4.02 - VLT® is a registered Danfoss trademark 9 VLT® Micro Drive FC 51 Operating Instructions 2 Mechanical Installation 2.3.1 Mechanical Dimensions 2 Illustration 2.1: Mechanical dimensions. NB! A template for drilling can be found on the flap of the packaging. Power (kW) Frame M1 M2 M3 1 X 200-240 V 0.18 - 0.75 1.5 2.2 3X 200 -240 V 0.25 - 0.75 1.5 2.2 -3.7 Height (mm) 3X 380-480 V 0.37 - 0.75 1.5 - 2.2 3.0 - 7.5 A 150 176 239 A (incl. decoupling plate) 205 230 294 Width (mm) Max. Weight a B b C Kg 70 75 90 55 59 69 148 168 194 1.1 1.6 3.0 For LCP with potentiometer, please add 7.6 mm. NB! DIN rail mounting kit is available for M1 frame . Please use ordering number 132B0111. 10 1) 140.4 166.4 226 Table 2.1: Mechanical Dimensions 1) Depth (mm) MG.02.A4.02 - VLT® is a registered Danfoss trademark VLT® Micro Drive FC 51 Operating Instructions 3 Electrical Installation 3 Electrical Installation 3.1 How to Connect 3.1.1 Electrical Installation in General NB! All cabling must comply with national and local regulations on cable cross-sections and ambient temperature. Copper conductors 3 required, (60-75° C) recommended. Details of terminal tightening torques. Power (kW) 1 x 200-240 3 x 200-240 3 x 380-480 V V V 0.18 - 0.75 0.25 - 0.75 0.37 - 0.75 1.5 1.5 1.5 - 2.2 2.2 2.2 - 3.7 3.0 - 7.5 connectors (6.3 mm Faston plugs) Frame 1) M1 M2 M3 Spade Line Motor 1.4 1.4 1.4 0.7 0.7 0.7 Torque (Nm) DC connec- Control Terminals tion/Brake1) 0.15 0.15 0.15 Earth Relay 3 3 3 0.5 0.5 0.5 Table 3.1: Tightening of terminals. 3.1.2 Fuses Branch circuit protection: In order to protect the installation against electrical and fire hazard, all branch circuits in an installation, switch gear, machines etc., must be short-circuited and overcurrent protected according to national/international regulations. Short circuit protection: Danfoss recommends using the fuses mentioned in the following tables to protect service personnel or other equipment in case of an internal failure in the unit or short-circuit on DC-link. The frequency converter provides full short circuit protection in case of a short-circuit on the motor or brake output. a circuit capable of supplying a maximum of 100,000 Arms (symmetrical), 480 V maximum. Overcurrent protection: Provide overload protection to avoid overheating of the cables in the installation. Overcurrent protection must always be carried out according to national regulations. Fuses must be designed for protection in a circuit capable of supplying a maximum of 100,000 Arms (symmetrical), 480 V maximum. Non UL compliance: If UL/cUL is not to be complied with, Danfoss recommends using the fuses mentioned in the below table, which will ensure compliance with EN50178/ IEC61800-5-1: In case of malfunction, not following the fuse recommendation may result in damage to the frequency converter. MG.02.A4.02 - VLT® is a registered Danfoss trademark 11 VLT® Micro Drive FC 51 Operating Instructions 3 Electrical Installation UL FC 51 3 Bussmann 1 X 200-240 V kW 0K18 - 0K37 0K75 1K5 2K2 3 x 200-240 V 0K25 0K37 0K75 1K5 2K2 3K7 3 x 380-480 V 0K37 - 0K75 1K5 2K2 3K0 4K0 5K5 7K5 FerrazShawmut FerrazShawmut Max. fuses non UL Type RK1 KLN-R15 KLN-R25 KLN-R35 KLN-R45 Type CC ATM-R15 ATM-R25 - Type RK1 A2K-15R A2K-25R A2K-35R A2K-45R Type gG 15A 25A 35A 45A JJN-10 JJN-15 JJN-20 JJN-25 JJN-40 JJN-40 KLN-R10 KLN-R15 KLN-R20 KLN-R25 KLN-R40 KLN-R40 ATM-R10 ATM-R15 ATM-R20 ATM-R25 ATM-R40 - A2K-10R A2K-15R A2K-20R A2K-25R A2K-40R A2K-40R 10A 15A 20A 25A 40A 40A JJS-10 JJS-15 JJS-20 JJS-40 JJS-40 JJS-40 JJS-40 KLS-R10 KLS-R15 KLS-R20 KLS-R40 KLS-R40 KLS-R40 KLS-R40 ATM-R10 ATM-R15 ATM-R20 ATM-R40 ATM-R40 - A6K-10R A2K-15R A6K-20R A6K405R A6K-40R A6K-40R A6K-40R 10A 15A 20A 40A 40A 40A 40A Bussmann Bussmann Type RK1 KTN-R15 KTN-R25 KTN-R35 KTN-R45 Type J JKS-15 JKS-25 JKS-35 JKS-45 Type T JJN-15 JJN-25 JJN-35 JJN-45 KTN-R10 KTN-R15 KTN-R20 KTN-R25 KTN-R40 KTN-R40 JKS-10 JKS-15 JKS-20 JKS-25 JKS-40 JKS-40 KTS-R10 KTS-R15 KTS-R20 KTS-R40 KTS-R40 KTS-R40 KTS-R40 JKS-10 JKS-15 JKS-20 JKS-40 JKS-40 JKS-40 JKS-40 Littel fuse Table 3.3: Fuses 3.1.3 EMC-Correct Installation Following these guidelines is advised, where compliance with EN 61000-6-3/4, EN 55011 or EN 61800-3 First environment is required. If the installation is in EN 61800-3 Second environment, then it is acceptable to deviate from these guidelines. It is however not recommended. Good engineering practice to ensure EMC-correct electrical installation: • Use only braided screened/armoured motor cables and control cables. The screen should provide a minimum coverage of 80%.The screen material must be metal, not limited to but typically copper, aluminium, steel or lead. There are no special requirements for the mains cable. • Installations using rigid metal conduits are not required to use screened cable, but the motor cable must be installed in conduit separate from the control and mains cables. Full connection of the conduit from the drive to the motor is required. The EMC performance of flexible conduits varies a lot and information from the manufacturer must be obtained. • • Connect the screen/armour/conduit to earth at both ends for motor cables and control cables. Avoid terminating the screen/armour with twisted ends (pigtails). Such a termination increases the high frequency impedance of the screen, which reduces its effectiveness at high frequencies. Use low impedance cable clamps or glands instead. • Ensure good electrical contact between the de-coupling plate and the metal chassis of the frequency converter, see Instruction MI.02.BX.YY. • Avoid using unscreened/unarmoured motor or control cables inside cabinets housing the drive(s), where possible. 3.2 Mains Connection 3.2.1 Connecting to Mains Step 1: First mount earth cable. Step 2: Mount wires in terminals L1/L, L2 and L3/N and tighten. Illustration 3.1: Mounting of earth cable and mains wires. 12 MG.02.A4.02 - VLT® is a registered Danfoss trademark VLT® Micro Drive FC 51 Operating Instructions 3 Electrical Installation For 3-phase connection, connect wires to all three terminals. For single-phase connection, connect wires to terminals L1/L and L3/N. Illustration 3.2: Three-phase and single-phase wire connections. 3 3.3 Motor Connection 3.3.1 How to Connect the Motor See the chapter Specifications for correct dimensioning of motor cable cross-section and length. • Use a shielded/armored motor cable to comply with EMC emission specifications, and connect this cable to both the decoupling plate and the motor metal. • Keep motor cable as short as possible to reduce the noise level and leakage currents. For further details on mounting of the decoupling plate, please see instruction MI.02.BX.YY. All types of three-phased asynchronous standard motors can be connected to the frequency converter. Normally, small motors are star-connected (230/400 V, Δ/Y). Large motors are delta-connected (400/690 V, Δ/ Y). Refer to motor nameplate for correct connection and voltage. Illustration 3.3: Star and delta connections. Step 1: First, mount the earth cable. Step 2: Connect wires to terminals either in star or delta-connection. See motor nameplate for further information. Illustration 3.4: Mounting of earth cable and motor wires. MG.02.A4.02 - VLT® is a registered Danfoss trademark 13 VLT® Micro Drive FC 51 Operating Instructions 3 Electrical Installation For EMC correct installation, use optional de-coupling plate, see chapter Options for frequency converter. 3 Illustration 3.5: Frequency converter with de-coupling plate 3.4 Control Terminals 3.4.1 Access to Control Terminals All control cable terminals are located underneath the terminal cover in front of the frequency converter. Remove the terminal cover using a screwdriver. Illustration 3.6: Removing terminal cover. NB! See back of terminal cover for outlines of control terminals and switches. 14 MG.02.A4.02 - VLT® is a registered Danfoss trademark VLT® Micro Drive FC 51 Operating Instructions 3 Electrical Installation 3.4.2 Connecting to Control Terminals This illustration shows all control terminals of the frequency converter. Applying Start (term. 18) and an analog reference (term. 53 or 60) make the frequency converter run. 3 Illustration 3.7: Overview of control terminals in PNP-configuration and factory setting. 3.5 Switches NB! Do not operate switches with power on the frequency converter. Bus termination: Switch BUS TER pos. ON terminates the RS485 port, terminals 68, 69. See power circuit drawing. Default setting = Off. Illustration 3.8: S640 Bus termination. S200 Switches 1-4: Switch 1: *OFF = PNP terminals 29 ON = NPN terminals 29 Switch 2: *OFF = PNP terminal 18, 19, 27 and 33 Switch 3: No function Switch 4: *OFF = Terminal 53 0 - 10 V ON = NPN terminal 18, 19, 27 and 33 ON = Terminal 53 0/4 - 20 mA * = default setting Table 3.5: Settings for S200 Switches 1-4 Illustration 3.9: S200 Switches 1-4. NB! Parameter 6-19 must be set according to Switch 4 position. MG.02.A4.02 - VLT® is a registered Danfoss trademark 15 VLT® Micro Drive FC 51 Operating Instructions 3 Electrical Installation 3.6 Power Circuit - Overview 3.6.1 Power Circuit - Overview 3 Illustration 3.10: Diagram showing all electrical terminals. Brake not applicable for frame M1. Brake resistors are available from Danfoss. Improved power factor and EMC performance can be achieved by installing optional Danfoss line filters. Danfoss power filters can also be used for load sharing. 3.6.2 Load sharing/Brake Use 6.3 mm insulated Faston Plugs designed for high voltage for DC (Load Sharing and brake). Contact Danfoss or see instruction no. MI.50.Nx.02 for load sharing and instruction no. MI.90.Fx.02 for brake. Load sharing: Connect terminals UDC- and UDC/BR+. Brake: Connect terminals BR- and UDC/BR+. Note that voltage levels of up to 850 V DC may occur between terminals UDC+/BR+ and UDC-. Not short circuit protected. 16 MG.02.A4.02 - VLT® is a registered Danfoss trademark VLT® Micro Drive FC 51 Operating Instructions 4 Programming 4 Programming 4.1 How to Programme 4.1.1 Programming with MCT-10 Set-up Software The frequency converter can be programmed from a PC via RS485 com-port by installing the MCT-10 Set-up Software. This software can either be ordered using code number 130B1000 or downloaded from the Danfoss Web site: www.danfoss.com, Business Area: Motion 4 Controls. Please refer to manual MG.10.RX.YY. 4.1.2 Programming with the LCP 11 or LCP 12 The LCP is divided into four functional groups: 1. Numeric display. 2. Menu key. 3. Navigation keys. 4. Operation keys and indicator lights (LEDs). Illustration 4.2: LCP 11 without potentiometer Illustration 4.1: LCP 12 with potentiometer The display: A number of information can be read from the display. Set-up number shows the active set-up and the edit set-up. If the same set-up acts as both active and edit set-up, only that set-up number is shown (factory setting). When active and edit set-up differ, both numbers are shown in the display (Setup 12). The number flashing, indicates the edit set-up. Illustration 4.3: Indicating Set-up MG.02.A4.02 - VLT® is a registered Danfoss trademark 17 VLT® Micro Drive FC 51 Operating Instructions 4 Programming The small digits to the left are the selected parameter number. Illustration 4.4: Indicating selected par. no. The large digits in the middle of the display show the value of the se- 4 lected parameter. Illustration 4.5: Indicating value of selected par. The right side of the display shows the unit of the selected parameter. This can be either Hz, A, V, kW, HP, %, s or RPM. Illustration 4.6: Indicating unit of selected par. Motor direction is shown to the bottom left of the display - indicated by a small arrow pointing either clockwise or counterclockwise. Illustration 4.7: Indicating motor direction Use the [MENU] key to select one of the following menus: Status Menu: The Status Menu is either in Readout Mode or Hand on Mode. In Readout Mode the value of the currently selected readout parameter is shown in the display. In Hand on Mode the local LCP reference is displayed. Quick Menu: Displays Quick Menu parameters and their settings. Parameters in the Quick Menu can be accessed and edited from here. Most applications can be run by setting the parameters in the Quick Menus. Main Menu: Displays Main Menu parameters and their settings. All parameters can be accessed and edited here. A parameter overview is found later in this manual. Indicator lights: • Green LED: The frequency converter is on. • Yellow LED: Indicates a warning. Please see section Troubleshooting • Flashing red LED: Indicates an alarm. Please see section Troubleshooting 18 MG.02.A4.02 - VLT® is a registered Danfoss trademark VLT® Micro Drive FC 51 Operating Instructions 4 Programming Navigation Keys: [Back]: For moving to the previous step or layer in the navigation structure. Arrows [▲] [▼]: For maneuvering between parameter groups, parameters and within parameters. [OK]: For selecting a parameter and for accepting changes to parameter settings. Operation Keys: A yellow light above the operation keys indicates the active key. [Hand on]: Starts the motor and enables control of the frequency converter via the LCP. [Off/Reset]: The motor stops except in alarm mode. In that case the motor will be reset. [Auto on]: The frequency converter is controlled either via control terminals or serial communication. [Potentiometer] (LCP12): The potentiometer works in two ways depending on the mode in which the frequency converter is running. In Auto Mode the potentiometer acts as an extra programmable analog input. In Hand on Mode the potentiometer controls local reference. 4 4.2 Status Menu After power up the Status Menu is active. Use the [MENU] key to toggle between Status, Quick Menu and Main Menu. Arrows [▲] and [▼] toggles between the choices in each menu. The display indicates the status mode with a small arrow above “Status”. Illustration 4.8: Indicating Status mode 4.3 Quick Menu The Quick Menu gives easy access to the most frequently used parameters. 1. To enter the Quick Menu, press [MENU] key until indicator in display is placed above Quick Menu. 2. Use [▲] [▼] to select either QM1 or QM2, then press [OK]. 3. Use [▲] [▼] to browse through the parameters in the Quick Menu. 4. Press [OK] to select a parameter. 5. Use [▲] [▼] to change the value of a parameter setting. 6. Press [OK] to accept the change. 7. To exit, press either [Back] twice to enter Status, or press [Menu] once to enter Main Menu. Illustration 4.9: Indicating Quick Menu mode MG.02.A4.02 - VLT® is a registered Danfoss trademark 19 VLT® Micro Drive FC 51 Operating Instructions 4 Programming 4.4 Quick Menu Parameters 4.4.1 Quick Menu Parameters - Basic Settings QM1 Below are descriptions of all parameters found in the Quick Menu. * = Factory setting. 4 1-20 Motor Power [kW]/[HP] (Pm.n) Option: Function: Enter motor power from nameplate data. Two sizes down, one size up from nominal VLT rating. [1] 0.09 kW/0.12 HP [2] 0.12 kW/0.16 HP [3] 0.18kW/0.25 HP [4] 0.25 kW/0.33 HP [5] 0.37kW/0.50 HP [6] 0.55 kW/0.75 HP [7] 0.75 kW/1.00 HP [8] 1.10 kW/1.50 HP [9] 1.50 kW/2.00 HP [10] 2.20 kW/3.00 HP [11] 3.00 kW/4.00 HP [12] 3.70 kW/5.00 HP [13] 4.00 kW/5.40 HP [14] 5.50 kW/7.50 HP [15] 7.50 kW/10.0 HP [16] 11.00 kW/15.00 HP NB! Changing this parameter affects par. 1-22 to 1-25, 1-30, 1-33 and 1-35. 1-22 Motor Voltage (U m.n) Range: 230/400 V Function: [50 - 999 V] Enter motor voltage from nameplate data. 1-23 Motor Frequency (f m.n) Range: 50 Hz* 20 Function: [20-400 Hz] Enter motor frequency from nameplate data. MG.02.A4.02 - VLT® is a registered Danfoss trademark VLT® Micro Drive FC 51 Operating Instructions 4 Programming 1-24 Motor Current (I m.n) Range: Function: M-type de- [0.01 - 26.00 A] Enter motor current from nameplate data. pendent* 1-25 Motor Nominal Speed (n m.n) Range: Function: M-type De- [100 - 9999 RPM] Enter motor nominal speed from nameplate data. pendent* 4 1-29 Automatic Motor Tuning (AMT) Option: Function: Use AMT to optimize motor performance. NB! This parameter cannot be changed while motor runs. 1. Stop the frequency converter – make sure motor is at standstill 2. Choose [2] Enable AMT 3. Apply start signal – Via LCP: Press Hand On - Or in Remote On mode: Apply start signal on terminal 18 [0] * Off AMT function is disabled. [2] Enable AMT AMT function starts running. NB! To gain optimum tuning of frequency converter, run AMT on a cold motor. 3-02 Minimum Reference Range: 0.00* Function: [-4999 - 4999] Enter value for minimum reference. The sum of all internal and external references are clamped (limited) to the minimum reference value, par. 3-02. 3-03 Maximum Reference Range: Function: Maximum Reference is adjustable in the range Minimum Reference - 4999. 50.00* [-4999 - 4999] Enter value for Maximum Reference. The sum of all internal and external references are clamped (limited) to the maximum reference value, par. 3-03. MG.02.A4.02 - VLT® is a registered Danfoss trademark 21 VLT® Micro Drive FC 51 Operating Instructions 4 Programming 3-41 Ramp1 Ramp-up Time Range: 3.00 s* Function: [0.05 - 3600.00 s ] Enter ramp-up time from 0 Hz to rated motor frequency (fM,N) set in par. 1-23. Choose a ramp-up time ensuring that torque limit is not exceeded, see par. 4-16. 3-42 Ramp1 Ramp-down Time Range: 3.00* Function: [0.05 - 3600.00 s] Enter ramp down time from rated motor frequency (fM,N) in par. 1-23 to 0 Hz. Choose a ramp down time that does not cause over-voltage in inverter due to regenerative operation 4 of motor. Furthermore, regenerative torque must not exceed limit set in par. 4-17. 4.4.2 Quick Menu Parameters - PI Basic Settings QM2 The following is a brief description of the parameters for the PI Basic Settings. For a more detailed description, please see VLT Micro Drive Programming Guide, MG.02.CX.YY. 1-00 Configuration Mode Range: Function: [] Choose [3] Process Closed Loop 3-02 Min. Reference Range: Function: [-4999 - 4999] Sets limits for set-point and feedback. 3-03 Max. Reference Range: Function: [-4999 - 4999] Sets limits for set-point and feedback. 3-10 Preset Reference Range: Function: [-100.00 - 100.00] Preset [0] works as set-point. 4-12 Motor Speed Low Limit Range: Function: [0.0 - 400 Hz] Lowest possible output frequency. 4-14 Motor Speed High Limit Range: Function: [0.0 - 400.00 Hz] Highest possible output frequency. NB! Default 65 Hz should normally be reduced to 50 - 55 Hz. 22 MG.02.A4.02 - VLT® is a registered Danfoss trademark VLT® Micro Drive FC 51 Operating Instructions 4 Programming 6-22 Terminal 60 Low Current Range: Function: [0.00 - 19.99 mA] Normally set to 0 or 4 mA. 6-23 Terminal 60 High Current Range: Function: [0.01 - 20.00 mA] Normally (default) set to 20 mA. 6-24 Terminal 60 Low Feedback Value Range: Function: [-4999 - 4999] 4 Value corresponding to P. 6-22 setting. 6-25 Terminal 60 High Feedback Value Range: Function: [-4999 - 4999] Value corresponding to P. 6-23 setting. 6-26 Terminal 60 Filter Time Constant Range: Function: [0.01 - 10.00 s] Filter for suppressing electrical noise. 7-20 Process CL Feedback Resource Range: Function: [] Choose [2] analog input 60. 7-30 Process PI Normal/Inverse Range: Function: [] Most PI controllers are “Normal”. 7-31 Process PI Anti Windup Range: Function: [] Leave Enabled normally. 7-32 Process PI Start Speed Range: Function: [0.0 - 200.0 Hz] Choose expected normal running speed. 7-33 Process PI Proportional Gain Range: Function: [0.00 - 10.00] Enter the P-factor. 7-34 Process PI Integral Time Range: Function: [0.10 - 9999.00 s] Enter the I-factor. MG.02.A4.02 - VLT® is a registered Danfoss trademark 23 VLT® Micro Drive FC 51 Operating Instructions 4 Programming 7-38 Process Feed Forward Factor Range: Function: [0 - 400%] Only applicable with changing set-points. 4.5 Main Menu The Main Menu gives access to all parameters. 4 1. To enter the Main Menu, press [MENU] key until indicator in display is placed above Main Menu. 2. Use [▲] [▼] to browse through the parameter groups. 3. Press [OK] to select a parameter group. 4. Use [▲] [▼] to browse through the parameters in the specific group. Illustration 4.10: Indicating Main Menu mode 5. Press [OK] to select the parameter. 6. Use [▲] [▼] to set/change the parameter value. 7. Press [OK] to accept the value. 8. To exit, press either [Back] twice to enter Quick Menu, or press [Menu] once to enter Status. 24 MG.02.A4.02 - VLT® is a registered Danfoss trademark VLT® Micro Drive FC 51 Operating Instructions 5 Modbus RTU 5 Modbus RTU 5.1 Modbus RTU Overview 5.1.1 Assumptions These operating instructions assume that the installed controller supports the interfaces in this document and that all the requirements stipulated in the controller, as well as the frequency converter, are strictly observed, along with all limitations therein. 5.1.2 What the User Should Already Know The Modbus RTU (Remote Terminal Unit) is designed to communicate with any controller that supports the interfaces defined in this document. It is assumed that the user has full knowledge of the capabilities and limitations of the controller. 5 5.1.3 Modbus RTU Overview Regardless of the type of physical communication networks, the Modbus RTU Overview describes the process a controller uses to request access to another device. This includes i.a. how it will respond to requests from another device, and how errors will be detected and reported. It also establishes a common format for the layout and contents of message fields. During communications over a Modbus RTU network, the protocol determines how each controller will learn its device address, recognise a message addressed to it, determine the kind of action to be taken, and extract any data or other information contained in the message. If a reply is required, the controller will construct the reply message and send it. Controllers communicate using a master-slave technique in which only one device (the master) can initiate transactions (called queries). The other devices (slaves) respond by supplying the requested data to the master, or by taking the action requested in the query. The master can address individual slaves, or can initiate a broadcast message to all slaves. Slaves return a message (called a response) to queries that are addressed to them individually. No responses are returned to broadcast queries from the master. The Modbus RTU protocol establishes the format for the master’s query by placing into it the device (or broadcast) address, a function code defining the requested action, any data to be sent, and an error-checking field. The slave’s response message is also constructed using Modbus protocol. It contains fields confirming the action taken, any data to be returned, and an error-checking field. If an error occurs in receipt of the message, or if the slave is unable to perform the requested action, the slave will construct an error message and send it in response, or a time-out will occur. 5.1.4 Frequency Converter with Modbus RTU The frequency converter communicates in Modbus RTU format over the built-in RS-485 interface. Modbus RTU provides access to the Control Word and Bus Reference of the frequency converter. The Control Word allows the Modbus master to control several important functions of the frequency converter: • Start • Stop of the frequency converter in various ways: Coast stop Quick stop DC Brake stop Normal (ramp) stop • Reset after a fault trip • Run at a variety of preset speeds • Run in reverse • Change the active set-up • Control the frequency converter’s built-in relay The Bus Reference is commonly used for speed control. It is also possible to access the parameters, read their values, and where possible, write values to them. This permits a range of control options, including controlling the setpoint of the frequency converter when its internal PI controller is used. MG.02.A4.02 - VLT® is a registered Danfoss trademark 25 VLT® Micro Drive FC 51 Operating Instructions 5 Modbus RTU 5.2 Modbus RTU Message Framing Structure 5.2.1 Remote Terminal Unit The controllers are set up to communicate on the Modbus network using RTU (Remote Terminal Unit) mode, with each 8-bit byte in a message containing two 4-bit hexadecimal characters. The format for each byte is shown below. Start bit 5 Data bit Stop/parity Stop Coding system: 8-bit binary, hexadecimal 0-9, A-F. Two hexadecimal characters contained in each 8-bit field of the message. Bits per byte: 1 start bit 8 data bits, least significant bit sent first Parity: 1 bit for even/odd parity is used; 1 or 2 stop bits if no parity is selected (see par. 8-33). Error Check Field: Cyclical Redundancy Check (CRC). 5.2.2 Modbus RTU Message Structure The transmitting device places a Modbus RTU message into a frame with a known beginning and ending point. This allows receiving devices to begin at the start of the message, read the address portion, determine which device is addressed (or all devices, if the message is broadcast), and to recognise when the message is completed. Partial messages are detected and errors set as a result - or timeouts occur. Characters for transmission must be in hexadecimal 00 to FF format in each field. The frequency converter continuously monitors the network bus, also during “silent” intervals. When the first field (the address field) is received, each frequency converter or device decodes it to determine which device is being addressed. Modbus RTU messages addressed to zero are broadcast messages. No response is permitted for boradcast messages. A typical message frame is shown below. Start Address Function Data CRC check End T1-T2-T3-T4 1 byte 1 byte N x 1 byte 2 bytes T1-T2-T3-T4 Table 5.1: Typical Modbus RTU Message Structure 5.2.3 Start/Stop Field Messages start with a silent period of at least 3.5 character intervals. This is implemented as a multiple of character intervals at the selected network baud rate (shown as Start T1-T2-T3-T4). The first field to be transmitted is the device address. Following the last transmitted character, a similar period of at least 3.5 character intervals marks the end of the message. A new message can begin after this period. The entire message frame must be transmitted as a continuous stream. If a silent period of more than 1.5 character intervals occurs before completion of the frame, the receiving device flushes the incomplete message and assumes that the next byte will be the address field of a new message. Similarly, if a new message begins prior to 3.5 character intervals after a previous message, the receiving device will ignore both messages. This will cause a timeout (no response from the slave). 26 MG.02.A4.02 - VLT® is a registered Danfoss trademark VLT® Micro Drive FC 51 Operating Instructions 5 Modbus RTU 5.2.4 Address Field The address field of a message frame contains 1 byte. Valid slave device addresses are in the range of 0 - 247 decimal. The individual slave devices are assigned addresses in the range of 1 - 247 (0 is reserved for broadcast mode, which all slaves recognise). A master addresses a slave by placing the slave address in the address field of the message. When the slave sends its response, it places its own address in this address field to let the master know which slave is responding. 5.2.5 Function Field The function field of a message frame contains 1 byte. Function fields are used to send messages between master and slave. When a message is sent from a master to a slave device, the function code field tells the slave what kind of action to perform. When the slave responds to the master, it uses the function code field to indicate either a normal (error-free) response, or that some kind of error occurred (called an exception response). For a normal response, the slave simply echoes the original function code. For an exception response, the slave returns a code that is equivalent to the 5 original code with its most significant bit set to logic 1. In addition, the slave places a unique code into the data field of the response message. This tells the master what kind of error occurred, or the reason for the exception. Please also refer to the sections Function Codes Supported by Modbus RTU and Exception Codes. 5.2.6 Data Field The data field is constructed using sets of two hexidecimal digits in the range of 00 to FF hexidecimal. These are made up of one RTU character. The data field of messages sent from a master to a slave device contains additional information which the slave must use to take the action defined by the function code. This can include items such as addresses of coils or registers, the quantity of items to be handled. and the count of actual data bytes in the field. 5.2.7 CRC Check Field Messages include an error-checking field, operating on the basis of a Cyclical Redundancy Check (CRC) method. The CRC field checks the content of the entire message. It is applied regardless of any parity check method used for the individual characters of the message. The CRC value is calculated by the transmitting device, which appends the CRC as the last field in the message. The receiving device recalculates a CRC during receipt of the message and compares the calculated value to the actual value received in the CRC field. If the two values are unequal, a bus timeout occurs. The error-checking field contains a 16-bit binary value implemented as two 8-bit bytes. When this is done, the low-order byte of the field is appended first, followed by the high-order byte. The CRC high-order byte is the last byte sent in the message. 5.2.8 Coil/Register Addressing In Modbus, all data are organised in coils and holding registers. Coils hold a single bit, whereas holding registers hold a 2-byte word (i.e. 16 bits). All data addresses in Modbus messages are referenced to zero. The first occurrence of a data item is addressed as item number zero. Example: The coil known as “coil 1” in programmable controller is addressed as coil 0000 in the data address field of a Modbus message. Coil 127 decimal is addressed as coil 007EHEX (126 decimal). Holding register 40001 is addressed as register 0000 in the data address field of the message. The function code field already specifies a “holding register” operation. Therefore, the “4XXXX” reference is implicit. Holding register 40108 is addressed as register 006BHEX (107 decimal). MG.02.A4.02 - VLT® is a registered Danfoss trademark 27 VLT® Micro Drive FC 51 Operating Instructions 5 Modbus RTU Coil number Description 1 - 16 Frequency converter control word (see table below) Master to slave Signal direction 17 - 32 Frequency converter speed or set-point reference Master to slave Range 0x0 - 0xFFFF (-200% ... ~ 200%) 33 - 48 Frequency converter status word (see table below) Slave to master 49 - 64 Open loop mode: Frequency converter output fre- Slave to master quency Closed loop mode: Frequency converter feedback signal 65 Parameter write control (master to slave) Master to slave 0 = Parameter changes are written to the RAM of the frequency converter 1 = Parameter changes are written to the RAM and 5 EEPROM of the frequency converter 66 - 65536 Reserved Coil 0 01 Preset reference LSB 1 Coil 0 33 02 Preset reference MSB 03 DC brake No DC brake Control not ready 1 Control ready 34 Unit not ready Unit ready 35 Coasted Not coasted 04 Coast stop No coast stop 36 Error, tripped 05 Quick stop No quick stop 37 Error, no trip 06 Freeze outp No freeze outp 38 07 Ramp stop Start 39 Not used Not used 08 No function Reset 40 No warning Warning 09 No jog Jog 10 Ramp 1 Ramp 2 41 Not on reference On reference 42 Hand mode 11 Data not valid Auto mode Data valid 43 Out of freq. range 12 In frequency range Relay 1 off Relay 1 on 44 Not running Running 13 Not used Not used 45 No res. brake fault Resistor brake fault Error, trip locked 14 Setup 1 Setup 2 46 No voltage warning Voltage warning 15 Not used Not used 47 Not in current limit Current limit 16 No reversing Reversing 48 No thermal warning Thermal warning Frequency converter control word (FC profile) Frequency converter status word (FC profile) Register number Description 00001 – 00006 Reserved 00007 Last error code. See sectionException and Error Codes. 00008 Reserved 00009 Parameter index* 00100 – 00999 000 parameter group (parameters 001 through 099) 01000 – 01999 100 parameter group (parameters 100 through 199) 02000 – 02999 200 parameter group (parameters 200 through 299) 03000 – 03999 300 parameter group (parameters 300 through 399) 04000 – 04999 400 parameter group (parameters 400 through 499) … … 49000 – 49999 4900 parameter group (parameters 4900 through 4999) 50000 Input data: Frequency converter control word register (CTW). 50010 Input data: Bus reference register (REF). … … 50200 Output data: Frequency converter status word register (STW). 50210 Output data: Frequency converter main actual value register (MAV). Table 5.1: Holding Registers * Used to specify the index number to be used when accessing an indexed parameter 28 MG.02.A4.02 - VLT® is a registered Danfoss trademark VLT® Micro Drive FC 51 Operating Instructions 5 Modbus RTU 5.3 How to Control the frequency converter This section describes codes which can be used in the function and data fields of a Modbus RTU message. For a complete description of all the message fields please refer to the section Modbus RTU Message Framing Structure. 5.3.1 Function Codes Supported by Modbus RTU Modbus RTU supports use of the following function codes in the function field of a message: Function Function Code Read coils 1 hex Read holding registers 3 hex Write single coil 5 hex Write single register 6 hex Write multiple coils F hex Write multiple registers 10 hex Get comm. event counter B hex Report slave ID 11 hex Function Function code Diagnostics 5 Sub-function code 8 1 Sub-function Restart communication 2 Return diagnostic register 10 Clear counters and diagnostic register 11 Return bus message count 12 Return bus communication error count 13 Return bus exception error count 14 Return slave message count 5.3.2 Exception and Error Codes In the event of an error, the following exception codes may appear in the data field of a response message. For a full explanation of the structure of an exception (i.e. error) response, please refer to Function Field in section Modbus RTU Message Framing Structure. MODBUS Exception Codes Code Name 1 Illegal function Meaning The function code received in the query is not an allowable action for the server (or slave). This may be because the function code is only applicable to newer devices, and was not implemented in the unit selected. It could also indicate that the server (or slave) is in the wrong state to process a request of this type, for example it is not configured and is being asked to return register values. 2 Illegal data address The data address received in the query is not an allowable address for the server (or slave). More specifically, the combination of reference number and transfer length is invalid. For a controller with 100 registers, a register with offset 96 and length 4 would succeed, a request with offset 96 and length 5 will generate exception 02. 3 Illegal data value A value contained in the query data field is not an allowable value for server (or slave). This indicates a fault in the structure of the remainder of a complex request, such as an incorrect implied length. It specifically does NOT mean that a data item submitted for storage in a register has a value outside the expectation of the application program, since the MODBUS protocol is unaware of the significance of any particular value of any particular register. 4 Slave device failure An unrecoverable error occurred while the server (or slave) was attempting to perform the requested action In case of an exception code 4 while accessing parameter values in the drive, detailed information about the latest exception can be read from the drives Holding Register 0007. This register may contain one of the following, detailed error codes regarding the latest occurring MODBUS Exception. MG.02.A4.02 - VLT® is a registered Danfoss trademark 29 VLT® Micro Drive FC 51 Operating Instructions 5 Modbus RTU Error code in holding register 0007 Description 00 The parameter number does not exist 01 There is no write access to the parameter 02 The data value exceeds the parameter limits 03 The sub-index in use does not exist 05 The data type does not match the parameter called 17 Data change in the parameter called is not possible in the present mode 18 Other error 130 There is no bus access to the parameter called 5.4 How to Access Parameters 5 5.4.1 Parameter Handling The PNU (Parameter Number) is translated from the register address contained in the Modbus read or write message. The parameter number is translated to Modbus register address as (10 x parameter number -1)DECIMAL. 5.4.2 Storage of Data The Coil 65 decimal determines whether data written to the frequency converter are stored in EEPROM and RAM (coil 65 = 1) or only in RAM (coil 65 = 0). 5.4.3 IND The array index is set in Holding Register 9 and used when accessing array parameters. 5.4.4 Text Blocks Parameters stored as text strings are accessed in the same way as the other parameters. The maximum text block size is 20 characters. If a read request for a parameters is for more characters than the parameter stores, the response is truncated. If the read request for a parameter is for fewer characters than the parameter stores, the response is space filled. 5.4.5 Conversion Factor The different attributes for each parameter can be seen in the section on factory settings. Since a parameter value can only be transferred as a whole number, a conversion factor must be used to transfer decimals. Please refer to the section Conversion Index. 5.4.6 Parameter Values Standard Data Type Standard data types are int16, int32, uint8, uint16 and uint32. They are stored as 4x registers (40001 - 4FFFF). The parameters are read using function 03HEX “Read Holding Registers”. Parameters are writtein using the function 6HEX “Preset Single Register” for 1 register (16 bits), and the function 10HEX “Preset Multiple Registers” for 2 registers (32 bits). Readable sizes range from 1 register (16 bits) up to 10 registers (20 characters). Non Standard Data Types Non standard data types are text strings and are stored as 4x registers (40001 - 4FFFF). The parameters are read using function 03HEX “Read Holding Registers” and written using function 10HEX “Preset Multiple Registers”. Readable sizes range from 1 register (2 characters) up to 10 registers (20 characters). 5.5 Examples The following examples illustrate various Modbus RTU commands. If an error occurs, please refer to the Exception Codes section. 30 MG.02.A4.02 - VLT® is a registered Danfoss trademark VLT® Micro Drive FC 51 Operating Instructions 5 Modbus RTU 5.5.1 Read Coil Status (01HEX) Description This function reads the ON/OFF status of discrete outputs (coils) in the frequency converter. Broadcast is never supported for reads. Query The query messages specifies the staring coil and quantity of coils to be read. Coil addresses start at zero, i.e. coil 33 is addressed as 32. Example of a request to read coils 33-48 (Status Word) from slave device 01: Field Name Example (HEX) Slave address 01 (frequency converter address) Function 01 (read address) Starting Address HI 00 Starting Address LO 20 (32 decimal) No. of Points HI 00 No. of Points LO 10 (16 decimal) Error Check (CRC) - 5 Response The coil status in the response message is packed as one coil per bit of the data field. Status is indicated as: 1 = ON; 0 = OFF. The LSB of the first data byte contains the coil addressed in the query. The other coils follow toward the high order end of this byte, and from “low order to high order” in subsequent bytes. If the returned coil quantity is not a multiple of eight, the remaining bits in the final data byte will padded with zeros (toward the high order and of the byte). The Byte Count field specifies the number of complete bytes of data. Field Name Example (HEX) Slave address 01 (frequency converter address) Function 01 (read coils) Byte count 02 (2 bytes of data) Data (Coils 40-33) 07 Data (Coils 48-41) 06 (STW = 0607hex) Error Check (CRC) - 5.5.2 Force/Write Single Coil (05HEX) Description This function forces a coil to either ON or OFF. When broadcast the function forces the same coil references in all attached slaves. Query The query message specifies the coil 65 (parameter write control) to be forced. Coil addresses start at zero, i.e. coil 65 is addressed as 64. Force Data = 00 00HEX (OFF) or FF 00HEX (ON). Field Name Example (HEX) Slave address 01 (frequency converter address) Function 05 (write single coil) Coil Address HI 00 Coil Address LO 40 (coil no. 65) Force Data HI FF Force Data LO 00 (FF 00 = ON) Error Check (CRC) - Response The normal response is an echo of the query, returned after the coil state has been forced. MG.02.A4.02 - VLT® is a registered Danfoss trademark 31 VLT® Micro Drive FC 51 Operating Instructions 5 Modbus RTU Field Name Example (HEX) Slave address 01 Function 05 Coil Address HI 00 Coil Address LO 40 Data HI FF Data LO 00 Error Check (CRC) - 5.5.3 Force/Write Multiple Coils (0FHEX) 5 Description This function forces each coil in a sequence of coils to either ON or OFF. When broadcast the function forces the same coil references in all attached slaves. Query The query message specifies the coils 17 to 32 (speed set-point) to be forced. Coil addresses start at zero, i.e. coil 17 is addressed as 16. Field Name Example (HEX) Slave address 01 (frequency converter address) Function 0F (write multiple coil) Coil Address HI 00 Coil Address LO 10 (coil address 17) Quantity of coils HI 00 Quantity of coils LO 10 (16 coils) Byte count 02 Force Data HI (coils 8-1) 20 Force Data LO (coils 10-9) 00 (ref. = 2000hex) Error Check (CRC) - Response The normal response returns the slave address, function code, starting address, and quantity of coils forced. Field Name Example (HEX) Slave address 01 (frequency converter address) Function 0F (write multiple coils) Coil Address HI 00 Coil Address LO 10 (coil address 17) Quantity of coils HI 00 Quantity of coils LO 10 (16 coils) Error Check (CRC) - 5.5.4 Read Holding Registers (03HEX) Description This function reads the content of holding registers in the slave. Query The query message specifies the starting register and quantity to be read. Register addresses start at zero, i.e. registers 1-4 are addressed as 0-3. 32 MG.02.A4.02 - VLT® is a registered Danfoss trademark VLT® Micro Drive FC 51 Operating Instructions 5 Modbus RTU Example Read PNU 342 which is mapped to register 0x0D5B(RegAdr = 342 x 10 - 1) Field Name Example (HEX) Slave address 01 Function 03 Starting Address HI 0D Starting Address LO 5B No. of Points HI 00 No. of Points LO 02 Error Check (CRC) - Table 5.1: Request frame Response The register data in the response message are packed as two bytes per register, with the binary contents right justified within each byte. For each register, the first byte contains the high order bits and the second contains the low order bits. Field Name 5 Example (HEX) Slave address 01 Function 03 Byte count 04 Data HI (Register 3419) 00 Data LO (Register 3419) 00 Data HI (Register 3420) 00 Data LO (Register 3420) 03 Error Check (CRC) - Table 5.1: Normal response frame 5.5.5 Preset Single Register (06HEX) Description This function presets a value into a single holding register. Query The query message specifies the register reference to be preset. Register addresses start at zero, i.e. register 1 is addressed as 0. Example Write 1 to PNU3 which is mapped to register 0x001D (3 x 10-1 = 29 = 001DHex) Field Name Example (HEX) Slave address 01 Function 06 Starting Address HI 00 Starting Address LO 1D No. of Points HI 00 No. of Points LO 01 Error Check (CRC) - Table 5.1: Request frame MG.02.A4.02 - VLT® is a registered Danfoss trademark 33 VLT® Micro Drive FC 51 Operating Instructions 5 Modbus RTU Response The normal response is an echo of the query, returned after the register contents have been passed. Field Name Example (HEX) Slave address 01 Function 06 Starting Address HI 00 Starting Address LO 1D No. of Points HI 00 No. of Points LO 01 Error Check (CRC) - Table 5.1: Normal response frame 5 5.5.6 Preset Multiple Registers (10HEX) Description This function presets a value into a sequence of holding registers. Query The query message specifies the register references to be preset. Register addresses start at zero, i.e. register 1 is addressed as 0. Example Write 65535 (655.35s) to PNU734 (4-bytes) mapped to 0 x 1CAB Field Name Example (HEX) Slave address 01 Function 10 Starting Address HI 1C Starting Address LO AB No. of Registers HI 00 No. of Registers LO 02 Byte count 04 Write Data HI (Register 7339) 00 Write Data LO (Register 7339) 00 Write Data HI (Register 7340) FF Write Data LO (Register 7340) FF Error Check (CRC) - Table 5.1: Request frame Response The normal response returns the slave address, function code, starting address, and quantity of registers preset. Field Name Example (HEX) Slave address 01 Function 10 Starting Address HI 1C Starting Address LO AB No. of Registers HI 00 No. of Registers LO 02 Error Check (CRC) - Table 5.1: Normal response frame 34 MG.02.A4.02 - VLT® is a registered Danfoss trademark VLT® Micro Drive FC 51 Operating Instructions 5 Modbus RTU 5.6 Danfoss FC Control Profile 5.6.1 Control Word According to FC Profile 5 Bit Bit value = 0 Bit value = 1 00 Preset reference select - lsb Preset reference select - lsb Preset reference select - msb 01 Preset reference select - msb 02 DC brake Ramp 03 Coasting No coasting 04 Quick stop Ramp 05 Freeze output No freeze output 06 Ramp stop Start 07 No function Reset 08 No function Jog 09 Ramp 1 Ramp 2 10 Data invalid Data valid 11 No function Relay 01 active 12 No function No function 13 Setup 1 Setup 2 14 No function No function 15 No function Reverse 5.6.2 Explanation of the Control Bits Bits 00/01 Bits 00 and 01 are used to choose between the four reference values, which are pre-programmed in par. 3-10 Preset Reference according to the following table: Programmed ref. value Parameter Bit 01 Bit 02 1 3-10 [0] 0 2 3-10 [1] 0 0 1 3 3-10 [2] 1 0 4 3-10 [3] 1 1 NB! In par. 8-56 Preset reference a selection is made to define how Bit 00/01 gates with the corresponding function on the digital inputs. Bit 02, DC brake: Bit 02 = “0” leads to DC braking and stop. Braking current and duration are set in par. 2-01 DC Brake current and 2-02 Braking time. Bit 02 = “1” leads to ramping. MG.02.A4.02 - VLT® is a registered Danfoss trademark 35 VLT® Micro Drive FC 51 Operating Instructions 5 Modbus RTU Bit 03, Coasting: Bit 03 = “0” shuts off the output transistors causing the motor to coast to a standstill. Bit 03 = “1” enables the frequency converter to start the motor if the other starting conditions have been fulfilled. NB! In par. 8-50 Coasting select a selection is made to define how Bit 03 gates with the corresponding function on a digital input. Bit 04, Quick stop: Bit 04 = “0” causes a stop, in which the motor speed is ramped down to stop via 9ar. 3-81 Quick stop ramp time. Bit 05, Hold output frequency: 5 Bit 05 = “0” causes the present output frequency (in Hz) to freeze. The frozen output frequency can then be changed only by means of the digital inputs (par. 5-10 to 5-15) programmed to Speed up and Speed down. NB! If Freeze output is active, the frequency converter can only be stopped by the following: • Bit 03 Coasting stop • Bit 02 DC braking • Digital input (par. 5-10 to 5-15) programmed to DC braking, Coasting stop or Reset and coasting stop. Bit 06, Ramp stop/start: Bit 06 = “0” causes a stop, in which the motor speed is ramped down to stop via the selected ramp down parameter. Bit 06 = “1” permits the frequency converter to start the motor, if the other starting conditions have been fulfilled. NB! In par. 8-53 Start select a selection is made to define how Bit 06 Ramp stop/start gates with the corresponding function on a digital input. Bit 07, Reset: Bit 07 = “0” does not cause a reset. Bit 07 = “1” causes the reset of a trip. Reset is activated on the signal's leading edge, i.e. when changing from logic “0” to logic “1”. Bit 08, Jog: Bit 08 = “1” causes the output frequency to be determined by par. 3-19 Jog speed. Bit 09, Selection of ramp 1/2: Bit 09 = “0” means the ramp 1 is active (par. 3-40 to 3-47). Bit 09 = ”1” means that ramp 2 (par. 3-50 to 3-57) is active. Bit 10, Data not valid/Data valid: Is used to tell the frequency converter whether the control word is to be used or ignored. Bit 10 = “0” causes the control word to be ignored. Bit 10 =”1” causes the control word to be used. Bit 11, Relay 01: Bit 11 = “0” Relay 01 not activated Bit 11 = “1” Relay 01 is activated, provided Control word Bit 11 has been chosen in par. 5-40 Function relay. 36 MG.02.A4.02 - VLT® is a registered Danfoss trademark VLT® Micro Drive FC 51 Operating Instructions 5 Modbus RTU Bit 12: Not used. Bit 13, Selection of set-up: Bit 13 = is used to choose the active set-up. The function is only possible when Multi set-ups is selected in par. 0-10 Active Set-up. NB! In par. 8-55 Set-up select a selection is made to define how Bit 13 gates with the corresponding function on the digital inputs. Bit 14: Not used. 5 Bit 15, Reverse: Bit 15 = “0” causes no reversing. Bit 15 = “1” causes reversing. NB! Depends on par. 8-54 Reversing select. 5.6.3 Status Word According to FC Profile (STW) Bit Bit value = 0 00 Control not ready Bit value = 1 Control ready 01 Unit not ready Unit ready 02 Coasting Enable 03 No error Error, trip 04 No error Error (no trip) 05 Reserved - 06 Not trip locked Trip locked 07 No warning Warning 08 Speed ≠ reference Speed = reference 09 Local operation Bus control 10 Out of frequency limit Frequency limit OK 11 Not running Running 12 No resistor brake fault Resistor brake fault 13 Voltage OK Voltage exceeded 14 Torque OK Torque exceeded 15 No thermal warning Thermal warning MG.02.A4.02 - VLT® is a registered Danfoss trademark 37 VLT® Micro Drive FC 51 Operating Instructions 5 Modbus RTU 5.6.4 Explanation of the Status Bits Bit 00, Control not ready/ready: Bit 00 = “0” means that the frequency converter has tripped. Bit 00 = “1” means that the frequency converter controls are ready, but that the power component is not necessarily receiving any power supply (in case of external 24 V supply to controls). Bit 01, Frequency converter ready: Bit 01 = “1”. The frequency converter is ready for operation, but there is an active coasting command via the digital inputs or via serial communication. Bit 02, Coasting stop: Bit 02 = “0”. The frequency converter released the motor. Bit 02 = “1”. The frequency converter can start the motor when a start command is given. 5 Bit 03, No error/trip: Bit 03 = “0” means that the frequency converter is not in fault mode. Bit 03 = “1” means that the frequency converter is tripped, and that a reset signal is required to re-establish operation. Bit 04, No error/error (trip): Bit 04 = “0” means that the frequency converter is not in fault mode. Bit 04 = “1” means that there is a frequency converter error but no trip. Bit 05: Not used. Bit 06, No error/trip lock: Bit 06 = “0” means that the frequency converter is not in fault mode. Bit 06 = “1” means that the frequency converter is tripped and locked. Bit 07, No warning/warning: Bit 07 = “0” means that there are no warnings. Bit 07 = “1” means that a warning has occurred. Bit 08, Speed ≠ reference/speed = reference: Bit 08 = “0” means that the motor is running, but that the present speed is different from the preset speed reference. For example, this might occur while the speed is being ramped up/down during start/stop. Bit 08 = “1” means that the present motor speed matches the preset speed reference. Bit 09, Local operation/bus control: Bit 09 = “0” means that [Stop/Reset] is activated on the control unit. It is not possible to control the frequency converter via serial communication. Bit 09 = “1” means that it is possible to control the frequency converter via serial communication. Bit 10, Out of frequency limit: Bit 10 = “0”, if the output frequency has reached the value in par. 4-12 Motor speed low limit or par . 4-13 Motor speed high limit. Bit 10 = “1” means that the output frequency is within the defined limits. Bit 11, Running: Bit 11 = “0” means that the motor is not running. Bit 11 = “1” means that the frequency converter has a start signal or that the output frequency is higher than 0 Hz. Bit 12, Resistor brake fault: Bit 12 = “0” means that there is no resistor brake fault. Bit 12 = “1” means that there is a resistor brake fault. 38 MG.02.A4.02 - VLT® is a registered Danfoss trademark VLT® Micro Drive FC 51 Operating Instructions 5 Modbus RTU Bit 13, Voltage OK/limit exceeded: Bit 13 = “0” means that there are no voltage warnings. Bit 13 = “1” means that the DC voltage in the frequency converter's intermediate circuit is too low or too high. Bit 14, Torque OK/limit exceeded: Bit 14 = “0” means that there are no current/torque warnings or errors. Bit 14 = “1” means that there is a current/torque warning or error. Bit 15, Thermal warning: Bit 15 = “0” means that there is no thermal warning or error. Bit 15 = “1” means that one of the thermal limits has been exceeded. 5.6.5 Bus Speed Reference Value The speed reference value is transmitted to the frequency converter in a 5 relative value in %. The value is transmitted in the form of a 16-bit word; in integers (0-32767) the value 16384 (4000 Hex) corresponds to 100%. Negative figures are formatted by means of 2's complement. The Actual Output Frequency (MAV) is scaled in the same way as the bus reference. The reference and MAV are scaled as follows: MG.02.A4.02 - VLT® is a registered Danfoss trademark 39 6 Parameter Overview VLT® Micro Drive FC 51 Operating Instructions 6 40 MG.02.A4.02 - VLT® is a registered Danfoss trademark MG.02.A4.02 - VLT® is a registered Danfoss trademark 1-** Load/Motor 0-60 (Main) Menu Password 0 - 999 * 0 0-6* Password 0-50 LCP Copy *[0] No copy [1] All to LCP [2] All from LCP [3] Size indep. from LCP 0-51 Set-up Copy *[0] No copy [1] Copy from setup 1 [2] Copy from setup 2 [9] Copy from Factory setup 0-5* Copy/Save 0-40 [Hand on] Key on LCP [0] Disabled *[1] Enabled 0-41 [Off / Reset] Key on LCP [0] Disable All *[1] Enable All [2] Enable Reset Only 0-42 [Auto on] Key on LCP [0] Disabled *[1] Enabled 0-4* LCP Keypad 0-10 Active Set-up *[1] Setup 1 [2] Setup 2 [9] Multi Setup 0-11 Edit Set-up *[1] Setup 1 [2] Setup 2 [9] Active Setup 0-12 Link Setups [0] Not Linked *[20] Linked 0-31 Custom Readout Min Scale 0.00 – 9999.00 *0.00 0-32 Custom Readout Max Scale 0.00 – 9999.00 *100.0 0-1* Set-up Handling 0-03 Regional Settings *[0] International [1] US 0-04 Oper. State at Power-up (Hand) [0] Resume *[1] Forced stop, ref = old [2] Forced stop, ref = 0 0-** Operation/Display 0-0* Basic Settings 1-30 Stator Resistance (Rs) [Ohm] * Dep. on motor data 1-3* Adv. Motor Data 1-20 Motor Power [kW] [HP] [1] 0.09 kW/0.12 HP [2] 0.12 kW/0.16 HP [3] 0.18 kW/0.25 HP [4] 0.25 kW/0.33 HP [5] 0.37 kW/0.50 HP [6] 0.55 kW/0.75 HP [7] 0.75 kW/1.00 HP [8] 1.10 kW/1.50 HP [9] 1.50 kW/2.00 HP [10] 2.20 kW/3.00 HP [11] 3.00 kW/4.00 HP [12] 3.70 kW/5.00 HP [13] 4.00 kW/5.40 HP [14] 5.50 kW/7.50 HP [15] 7.50 kW/10.00 HP [16] 11.00 kW/15.00 HP 1-22 Motor Voltage 50 - 999 V * 230 - 400 V 1-23 Motor Frequency 20 - 400 Hz * 50 Hz 1-24 Motor Current 0.01 - 26.00 A * Motortype dep. 1-25 Motor Nominal Speed 100 - 9999 rpm * Motortype dep. 1-29 Automatic Motor Tuning (AMT) *[0] Off [2] Enable AMT 1-2* Motor Data 1-00 Configuration Mode *[0] Speed open loop [3] Process 1-01 Motor Control Principle [0] U/f *[1] VVC+ 1-03 Torque Characteristics *[0] Constant torque [2] Automatic Energy Optim. 1-05 Local Mode Configuration [0] Speed Open Loop *[2] As config in param. 1-00 1-0* General Settings 1-90 Motor Thermal Protection *[0] No protection [1] Termistor warning [2] Thermistor trip [3] Etr warning [4] Etr trip 1-93 Thermistor Resource *[0] None 1-9* Motor Temperature 1-80 Function at Stop *[0] Coast [1] DC hold 1-82 Min Speed for Funct. at Stop [Hz] 0.0 - 20.0 Hz * 0.0 Hz 1-8* Stop Adjustments 1-71 Start Delay 0.0 - 10.0 s * 0.0 s 1-72 Start Function [0] DC hold / delay time [1] DC brake / delay time *[2] Coast / delay time 1-73 Flying Start *[0] Disabled [1] Enabled 1-7* Start Adjustments 1-60 Low Speed Load Compensation 0 - 199 % * 100 % 1-61 High Speed Load Compensation 0 - 199 % * 100 % 1-62 Slip Compensation -400 - 399 % * 100 % 1-63 Slip Compensation Time Constant 0.05 - 5.00 s * 0.10 s 1-6* Load Depen. Setting 1-50 Motor Magnetisation at 0 Speed 0 - 300 % * 100 % 1-52 Min Speed Norm. Magnet. [Hz] 0.0 - 10.0 Hz * 0.0 Hz 1-55 U/f Characteristic - U 0 - 999.9 V 1-56 U/f Characteristic - F 0 - 400 Hz 1-5* Load Indep. Setting Parameter Overwiev 1-33 Stator Leakage Reactance (X1) [Ohm] * Dep. on motor data 1-35 Main Reactance (Xh) [Ohm] * Dep. on motor data 3-10 Preset Reference -100.0 - 100.0 % * 0.00 % 3-11 Jog Speed [Hz] 0.0 - 400.0 Hz * 5.0 Hz 3-12 Catch up/slow Down Value 0.00 - 100.0 % * 0.00 % 3-1* References 3-00 Reference Range *[0] Min - Max [1] -Max - +Max 3-02 Minimum Reference -4999 - 4999 * 0.000 3-03 Maximum Reference -4999 - 4999 * 50.00 3-** Reference / Ramps 3-0* Reference Limits 2-20 Release Brake Current 0.00 - 100.0 A * 0.00 A 2-22 Activate Brake Speed [Hz] 0.0 - 400.0 Hz * 0.0 Hz 2-2* Mechanical Brake 2-10 Brake Function *[0] Off [1] Resistor brake [2] AC brake 2-11 Brake Resistor (ohm) 5 - 5000 * 5 2-16 AC Brake, Max current 0 - 150 % * 100 % 2-17 Over-voltage Control *[0] Disabled [1] Enabled (not at stop) [2] Enabled 2-1* Brake Energy Funct. 2-00 DC Hold Current 0 - 150 % * 50 % 2-01 DC Brake Current 0 - 150 % * 50 % 2-02 DC Braking Time 0.0 - 60.0 s * 10.0 s 2-04 DC Brake Cut In Speed 0.0 - 400.0 Hz * 0.0 Hz 2-** Brakes 2-0* DC-Brake [1] Analog input 53 [6] Digital input 29 VLT® Micro Drive FC 51 Operating Instructions 6 Parameter Overview 6 Parameter Overview 6 41 42 MG.02.A4.02 - VLT® is a registered Danfoss trademark 3-8* Other Ramps 3-50 Ramp 2 Type *[0] Linear [2] Sine2 ramp 3-51 Ramp 2 Ramp up Time 0.05 - 3600 s * 3.00 s 3-52 Ramp 2 Ramp down Time 0.05 - 3600 s * 3.00 s 3-5* Ramp 2 5-10 Terminal 18 Digital Input [0] No function [1] Reset [2] Coast inverse [3] Coast and reset inv. [4] Quick stop inverse [5] DC-brake inv. [6] Stop inv *[8] Start [9] Latched start [10] Reversing [11] Start reversing [12] Enable start forward [13] Enable start reverse [14] Jog 5-1* Digital Inputs 4-61 Bypass Speed From [Hz] 0.0 - 400.0 Hz * 0.0 Hz 4-63 Bypass Speed To [Hz] 0.0 - 400.0 Hz * 0.0 Hz 4-6* Speed Bypass 4-50 Warning Current Low 0.00 - 26.00 A * 0.00 A 4-51 Warning Current High 0.00 - 26.00 A * 26.00 A 4-58 Missing Motor Phase Function [0] Off *[1] On 4-5* Adj. Warnings 4-10 Motor Speed Direction [0] Clockwise [1] CounterClockwise *[2] Both 4-12 Motor Speed Low Limit [Hz] 0.0 - 400.0 Hz * 0.0 Hz 4-14 Motor Speed High Limit [Hz] 0.1 - 400.0 Hz * 65.0 Hz 4-16 Torque Limit Motor Mode 0 - 400 % * 150 % 4-17 Torque Limit Generator Mode 0 - 400 % * 100 % 4-** Limits / Warnings 4-1* Motor Limits 3-80 Jog Ramp Time 0.05 - 3600 s * 3.00 s 3-81 Quick Stop Ramp Time 0.05 - 3600 s * 3.00 s 5-40 Function Relay *[0] No opreation [1] Control ready [2] Drive ready [3] Drive ready, Remote [4] Enable / No warning [5] Drive running [6] Running / No warning [7] Run in range / No warning [8] Run on ref / No warning [9] Alarm [10] Alarm or warning [12] Out of current range [13] Below current, low [14] Above current, high [21] Thermal warning [22] Ready, No thermal warning [23] Remote ready, No thermal warning [24] Ready, Voltage ok 5-4* Relays [16-18] Preset ref bit 0-2 [19] Freeze reference [20] Freeze output [21] Speed up [22] Speed down [23] Setup select bit 0 [28] Catch up [29] Slow down [34] Ramp bit 0 [60] Counter A (up) [61] Counter A (down) [62] Reset counter A [63] Counter B (up) [64] Counter B (down) [65] ResetCounter B 5-11 Terminal 19 Digital Input See par. 5-10. * [10] Reversing 5-12 Terminal 27 Digital Input See par. 5-10. * [1] Reset 5-13 Terminal 29 Digital Input See par. 5-10. * [14] Jog 5-15 Terminal 33 Digital Input See par. 5-10. * [16] Preset ref bit 0 [26] Precise Stop Inverse [27] Start, Precise Stop [32] Pulse Input 6 3-40 Ramp 1 Type *[0] Linear [2] Sine2 ramp 3-41 Ramp 1 Ramp up Time 0.05 - 3600 s * 3.00 s 3-42 Ramp 1 Ramp Down Time 0.05 - 3600 s * 3.00 s 3-4* Ramp 1 3-14 Preset Relative Reference -100.0 - 100.0 % * 0.00 % 3-15 Reference Resource 1 [0] No function *[1] Analog Input 53 [2] Analog input 60 [8] Pulse input 33 [11] Local bus ref [21] LCP Potentiometer 3-16 Reference Resource 2 [0] No function [1] Analog Input 53 *[2] Analog input 60 [8] Pulse input 33 [11] Local bus ref [21] LCP Potentiometer 3-17 Reference Resource 3 [0] No function [1] Analog Input 53 [2] Analog input 60 [8] Pulse input 33 *[11] Local bus ref [21] LCP Potentiometer 3-18 Relative Scaling Ref. Resource *[0] No function [1] Analog Input 53 [2] Analog input 60 [8] Pulse input 33 [11] Local bus ref [21] LCP Potentiometer 6-10 Terminal 53 Low Voltage 0.00 - 9.99 V * 0.07 V 6-11 Terminal 53 High Voltage 0.01 - 10.00 V * 10.00 V 6-12 Terminal 53 Low Current 0.00 - 19.99 mA * 0.14 mA 6-1* Analog Input 1 6-00 Live Zero Timeout Time 1 - 99 s * 10 s 6-01 Live Zero TimeoutFunction *[0] Off [1] Freeze output [2] Stop [3] Jogging [4] Max speed [5] Stop and trip 6-** Analog In/Out 6-0* Analog I/O Mode 5-55 Terminal 33 Low Frequency 20 - 4999 Hz * 20 Hz 5-56 Terminal 33 High Frequency 21 - 5000 Hz * 5000 Hz 5-57 Term. 33 Low Ref./Feedb. Value -4999 - 4999 * 0.000 5-58 Term. 33 High Ref./Feedb. Value -4999 - 4999 * 50.000 5-5* Pulse Input [25] Reverse [26] Bus ok [28] Brake,NoWarn [29] Brake ready/NoFault [30] BrakeFault (IGBT) [32] Mech.brake control [36] Control word bit 11 [51] Local ref. active [52] Remote ref. active [53] No alarm [54] Start cmd active [55] Running reverse [56] Drive in hand mode [57] Drive in auto mode [60-63] Comparator 0-3 [70-73] Logic rule 0-3 [81] SL digital output B 6 Parameter Overview VLT® Micro Drive FC 51 Operating Instructions 6-90 Terminal 42 Mode *[0] 0-20 mA [1] 4-20 mA [2] Digital Output 6-91 Terminal 42 Analog Output *[0] No operation [10] Output Frequency [11] Reference [12] Feedback [13] Motor Current [16] Power [20] BusControl 6-92 Terminal 42 Digital Output See par. 5-40 * [0] No Operation [80] SL Digital Output A 6-9* Analog Output xx 6-81 LCP potm. Low Reference -4999 - 4999 * 0.000 6-82 LCP potm. High Reference -4999 - 4999 * 50.00 6-8* LCP potentiometer 6-22 Terminal 60 Low Current 0.00 - 19.99 mA * 0.14 mA 6-23 Terminal 60 High Current 0.01 - 20.00 mA * 20.00 mA 6-24 Term. 60 Low Ref./Feedb. Value -4999 - 4999 * 0.000 6-25 Term. 60 High Ref./Feedb. Value -4999 - 4999 * 50.00 6-26 Terminal 60 Filter Time Constant 0.01 - 10.00 s * 0.01 s 6-2* Analog Input 2 6-13 Terminal 53 High Current 0.01 - 20.00 mA * 20.00 mA 6-14 Term. 53 Low Ref./Feedb. Value -4999 - 4999 * 0.000 6-15 Term. 53 High Ref./Feedb. Value -4999 - 4999 * 50.000 6-16 Terminal 53 Filter Time Constant 0.01 - 10.00 s * 0.01 s 6-19 Terminal 53 mode *[0] Voltage mode [1] Current mode 8-01 Control Site *[0] Digital and ControlWord [1] Digital only [2] ControlWord only 8-02 Control Word Source [0] None *[1] FC RS485 8-03 Control Word Timeout Time 0.1 - 6500 s * 1.0 s 8-04 Control Word Timeout Function *[0] Off [1] Freeze Output [2] Stop [3] Jogging 8-** Comm. and Options 8-0* General Settings Ctrl. 7-30 Process PI Normal/ Inverse Ctrl *[0] Normal [1] Inverse 7-31 Process PI Anti Windup [0] Disable *[1] Enable 7-32 Process PI Start Speed 0.0 - 200.0 Hz * 0.0 Hz 7-33 Process PI Proportional Gain 0.00 - 10.00 * 0.01 7-34 Process PI Integral Time 0.10 - 9999 s * 9999 s 7-38 Process PI Feed Forward Factor 0 - 400 % * 0 % 7-39 On Reference Bandwidth 0 - 200 % * 5 % 7-3* Process PI 8-50 Coasting Select [0] DigitalInput [1] Bus [2] LogicAnd *[3] LogicOr 8-51 Quick Stop Select See par. 8-50 * [3] LogicOr 8-52 DC Brake Select See par. 8-50 * [3] LogicOr 8-53 Start Select See par. 8-50 * [3] LogicOr 8-54 Reversing Select See par. 8-50 * [3] LogicOr 8-55 Set-up Select See par. 8-50 * [3] LogicOr 8-56 Preset Reference Select See par. 8-50 * [3] LogicOr 8-5* Digital/Bus 8-30 Protocol *[0] FC [2] Modbus 8-31 Address 1 - 247 * 1 8-32 FC Port Baud Rate [0] 2400 Baud [1] 4800 Baud *[2] 9600 Baud [3] 19200 Baud *[4] 38400 Baud 8-33 FC Port Parity *[0] Even Parity, 1 Stop Bit [1] Odd Parity, 1 Stop Bit [2] No Parity, 1 Stop Bit [3] No Parity, 2 Stop Bits 8-35 Minimum Response Delay 0.001-0.5 * 0.010 s 8-36 Max Response Delay 0.100 - 10.00 s * 5.000 s 8-3* FC Port Settings 7-20 Process CL Feedback 1 Resource *[0] NoFunction [1] Analog Input 53 [2] Analog input 60 [8] PulseInput33 [11] LocalBusRef 7-** Controllers 7-2* Process Ctrl. Feedb [4] Max. Speed [5] Stop and trip 8-06 Reset Control Word Timeout *[0] No Function [1] Do reset 6-93 Terminal 42 Output Min Scale 0.00 - 200.0 % * 0.00 % 6-94 Terminal 42 Output Max Scale 0.00 - 200.0 % * 100.0 % 13-1* Comparators 13-00 SL Controller Mode *[0] Off [1] On 13-01 Start Event [0] False [1] True [2] Running [3] InRange [4] OnReference [7] OutOfCurrentRange [8] BelowILow [9] AboveIHigh [16] ThermalWarning [17] MainOutOfRange [18] Reversing [19] Warning [20] Alarm_Trip [21] Alarm_TripLock [22-25] Comparator 0-3 [26-29] LogicRule0-3 [33] DigitalInput_18 [34] DigitalInput_19 [35] DigitalInput_27 [36] DigitalInput_29 [38] DigitalInput_33 *[39] StartCommand [40] DriveStopped 13-02 Stop Event See par. 13-01 * [40] DriveStopped 13-03 Reset SLC *[0] Do not reset [1] Reset SLC 13-** Smart Logic 13-0* SLC Settings 8-94 Bus feedback 1 0x8000 - 0x7FFF * 0 8-9* Bus Jog / Feedback VLT® Micro Drive FC 51 Operating Instructions 6 Parameter Overview 6 MG.02.A4.02 - VLT® is a registered Danfoss trademark 43 44 MG.02.A4.02 - VLT® is a registered Danfoss trademark 13-51 SL Controller Event See par. 13-40 13-52 SL Controller Action *[0] Disabled 13-5* States 13-40 Logic Rule Boolean 1 See par. 13-01 * [0] False [30] - [32] SL Time-out 0-2 13-41 Logic Rule Operator 1 *[0] Disabled [1] And [2] Or [3] And not [4] Or not [5] Not and [6] Not or [7] Not and not [8] Not or not 13-42 Logic Rule Boolean 2 See par. 13-40 13-43 Logic Rule Operator 2 See par. 13-41 * [0] Disabled 13-44 Logic Rule Boolean 3 See par. 13-40 14-20 Reset Mode *[0] Manual reset [1-9] AutoReset 1-9 [10] AutoReset 10 [11] AutoReset 15 [12] AutoReset 20 [13] Infinite auto reset 14-21 Automatic Restart Time 0 - 600 s * 10 s 14-2* Trip Reset 14-12 Function at mains imbalance *[0] Trip [1] Warning [2] Disabled 14-1* Mains monitoring 14-01 Switching Frequency [0] 2 kHz *[1] 4 kHz [2] 8 kHz [4] 16 kHz 14-03 Overmodulation [0] Off *[1] On 13-4* Logic Rules 14-** Special Functions 14-0* Inverter Switching 16-00 Control Word 0 - 0XFFFF 16-01 Reference [Unit] -4999 - 4999 16-02 Reference % -200.0 - 200.0 % 16-03 Status Word 0 - 0XFFFF 16-05 Main Actual Value [%] -200.0 - 200.0 % 16-09 Custom Readout Dep. on par. 0-31, 0-32 and 4-14 16-** Data Readouts 16-0* General Status 15-40 FC Type 15-41 Power Section 15-42 Voltage 15-43 Software Version 15-46 Frequency Converter Order. No 15-48 LCP Id No 15-51 Frequency Converter Serial No 15-4* Drive Identification 15-30 Fault Log: Error Code 15-3* Fault Log 15-00 Operating Days 15-01 Running Hours 15-02 kWh Counter 15-03 Power Ups 15-04 Over Temps 15-05 Over Volts 15-06 Reset kWh Counter *[0] Do not reset [1] Reset counter 15-07 Reset Running Hours Counter *[0] Do not reset [1] Reset counter 15-** Drive Information 15-0* Operating Data 14-41 AEO Minimum Magnetisation 40 - 75 % * 66 % 14-4* Energy Optimising 14-22 Operation Mode *[0] Normal Operation [2] Initialisation 14-26 Action At Inverter Fault *[0] Trip [1] Warning 6 13-20 SL Controller Timer 0.0 - 3600 s * 0.0 s 13-2* Timers [1] NoAction [2] SelectSetup1 [3] SelectSetup2 [10-17] SelectPresetRef0-7 [18] SelectRamp1 [19] SelectRamp2 [22] Run [23] RunReverse [24] Stop [25] Qstop [26] DCstop [27] Coast [28] FreezeOutput [29] StartTimer0 [30] StartTimer1 [31] StartTimer2 [32] Set Digital Output A Low [33] Set Digital Output B Low [38] Set Digital Output A High [39] Set Digital Output B High [60] ResetCounterA [61] ResetCounterB 13-10 Comparator Operand *[0] Disabled [1] Reference [2] Feedback [3] MotorSpeed [4] MotorCurrent [6] MotorPower [7] MotorVoltage [8] DCLinkVoltage [12] AnalogInput53 [13] AnalogInput60 [18] PulseInput33 [20] AlarmNumber [30] CounterA [31] CounterB 13-11 Comparator Operator [0] Less Than *[1] Approximately equals [2] Greater Than 13-12 Comparator Value -9999 - 9999 * 0.0 16-90 Alarm Word 0 - 0XFFFFFFFF 16-92 Warning Word 0 - 0XFFFFFFFF 16-94 Ext. Status Word 0 - 0XFFFFFFFF 16-9* Diagnosis Readouts 16-86 FC Port REF 1 0x8000 - 0x7FFFF 16-8* Fieldbus / FC Port 16-60 Digital Input 18,19,27,33 0 - 1111 16-61 Digital Input 29 0-1 16-62 Analog Input 53 (volt) 16-63 Analog Input 53 (current) 16-64 Analog Input 60 16-65 Analog Output 42 [mA] 16-68 Pulse Input [Hz] 16-71 Relay Output [bin] 16-72 Counter A 16-73 Counter B 16-6* Inputs / Outputs 16-50 External Reference 16-51 Pulse Reference 16-52 Feedback [Unit] 16-5* Ref. / Feedb. 16-30 DC Link Voltage 16-34 Heatsink Temp. 16-35 Inverter Thermal 16-36 Inv.Nom. Current 16-37 Inv. Max. Current 16-38 SL Controller State 16-3* Drive Status 16-10 Power [kW] 16-11 Power [hp] 16-12 Motor Voltage [V] 16-13 Frequency [Hz] 16-14 Motor Current [A] 16-15 Frequency [%] 16-18 Motor Thermal [%] 16-1* Motor Status 6 Parameter Overview VLT® Micro Drive FC 51 Operating Instructions VLT® Micro Drive FC 51 Operating Instructions 6 Parameter Overview 6.2.1 Conversion Index The various attributes of each parameter are displayed in the section Factory Settings. Parameter values are transferred as whole numbers only. Conversion factors are therefore used to transfer decimals according to the table below. Example: Par. 1-24 Motor Current has a conversion index of -2 (i.e. conversion factor of 0.01 according to the table below). To set the parameter to 2.25 A, transfer the value 225 via Modbus. The Conversion Factor of 0.01 means that the value transferred is multiplied by 0.01 in the drive. The vale 225 transferred on the bus is thus perceived as 2.25 A in the drive. Conversion index Conversion factor 2 10 1 100 0 1 -1 0.1 -2 0.01 -3 0.001 -4 0.0001 -5 0.00001 6 Table 6.1: Conversion table 6.2.2 Change during operation “TRUE” means that the parameter can be changed while the frequency converter is in operation and “FALSE” means that the frequency converter must be stopped before a change can be made. 6.2.3 2-Set-up “All set-up”: The parameter can be set individually in each of the two set-ups, i.e. one single parameter can have two different data values. ”1 set-up”: Data value will be the same in both set-ups. 6.2.4 Type Data Type Description Type 2 Integer 8 Int8 3 Integer 16 Int16 4 Integer 32 Int32 5 Unsigned 8 Uint8 6 Unsigned 16 Uint16 7 Unsigned 32 Uint32 9 Visible string VisibleString MG.02.A4.02 - VLT® is a registered Danfoss trademark 45 Parameter Description Regional Settings Operating State at Power-up (Hand) Active Set-up Edit Set-up Link Setups [Hand on] Key on LCP [Off / Reset] Key on LCP [Auto on] Key on LCP LCP Copy Set-up Copy Main Menu Password 6.2.5 0-** Operation/Display Default Value [0] International [1] Forced stop ref=old [1] Set-up 1 [1] Set-up 1 [20] Linked [1] Enabled [1] Enable All [1] Enabled [0] No copy [0] No copy 0 2 Setup 1 set-up All set-ups 1 set-up 1 set-up All set-ups All set-ups All set-ups All set-ups 1 set-up 1 set-up 1 set-up Change During Operation FALSE TRUE TRUE TRUE FALSE TRUE TRUE TRUE FALSE FALSE TRUE 6 Parameter Number 0 - 03 0 - 04 0 - 10 0 - 11 0 - 12 0 - 40 0 - 41 0 - 42 0 - 50 0 - 51 0 - 60 Conversion Index 0 Type Uint8 Uint8 Uint8 Uint8 Uint8 Uint8 Uint8 Uint8 Uint8 Uint8 Uint16 6 Parameter Overview 46 VLT® Micro Drive FC 51 Operating Instructions MG.02.A4.02 - VLT® is a registered Danfoss trademark Parameter Number 1 - 00 1 - 01 1 - 03 1 - 05 1 - 20 1 - 22 1 - 23 1 - 24 1 - 25 1 - 29 1 - 30 1 - 33 1 - 35 1 - 50 1 - 52 1 - 55 1 - 56 1 - 60 1 - 61 1 - 62 1 - 63 1 - 71 1 - 72 1 - 73 1 - 80 1 - 82 1 - 90 1 - 93 Parameter Description Configuration Mode Motor Control Principle Torque Characteristics Hand Mode Configuration Motor Power Motor Voltage Motor Frequency Motor Current Motor Nominal Speed Automatic Motor Tuning (AMT) Stator Resistance (Rs) Stator Leakage Reactance (X1) Main Reactance (Xh) Motor Magnetisation at Zero Speed Min Speed Normal Magnetising [Hz] U/f Characteristic - U U/f Characteristic - F Low Speed Load Compensation High Speed Load Compensation Slip Compensation Slip Compensation Time Constant Start Delay Start Function Flying Start Function at Stop Min Speed for Function at Stop [Hz] Motor Thermal Protection Thermistor Resource 6.2.6 1-** Load/Motor 100% 100% 100% 0.1 s 0s [2] Coast/delay time [0] Disabled [0] Coast 0 Hz [0] No protection [0] None 100% 0 Hz [0] Off Default Value [0] Speed open loop [1] VVC+ [0] Constant torque [2] As mode par 1-00 2 Setup All set-ups All set-ups All set-ups All set-ups All set-ups All set-ups All set-ups All set-ups All set-ups 1 set-up All set-ups All set-ups All set-ups All set-ups All set-ups All set-ups All set-ups All set-ups All set-ups All set-ups All set-ups All set-ups All set-ups All set-ups All set-ups All set-ups All set-ups All set-ups Change During Operation TRUE FALSE TRUE TRUE FALSE FALSE FALSE FALSE FALSE FALSE FALSE FALSE FALSE TRUE TRUE TRUE TRUE TRUE TRUE TRUE TRUE TRUE TRUE FALSE TRUE TRUE TRUE FALSE Conversion Index 0 0 -2 0 -2 -2 -2 0 -1 0 0 0 0 0 -2 -1 -1 - Type Uint8 Uint8 Uint8 Uint8 Uint8 Uint16 Uint16 Uint16 Uint16 Uint8 Uint16 Uint32 Uint32 Uint16 Uint16 Uint16 Uint16 Uint16 Uint16 Int16 Uint16 Uint8 Uint8 Uint8 Uint8 Uint16 Uint8 Uint8 VLT® Micro Drive FC 51 Operating Instructions MG.02.A4.02 - VLT® is a registered Danfoss trademark 6 Parameter Overview 6 47 Parameter Description DC Hold Current DC Brake Current DC Braking Time DC Brake Cut In Speed Brake Function Brake Resistor (ohm) AC Brake, Max current Over-voltage Control Release Brake Current Activate Brake Speed [Hz] 6.2.7 2-** Brakes 48 100% [0] Disabled 0A 0 Hz Default Value 50% 50% 10 s 0 Hz [0] Off 2 Setup All set-ups All set-ups All set-ups All set-ups All set-ups All set-ups All set-ups All set-ups All set-ups All set-ups Change During Operation TRUE TRUE TRUE TRUE TRUE TRUE TRUE TRUE TRUE TRUE 6 Parameter Number 2 - 00 2 - 01 2 - 02 2 - 04 2 - 10 2 - 11 2 - 16 2 - 17 2 - 20 2 - 22 Conversion Index 0 0 -1 -1 0 0 -2 -1 Type Uint16 Uint16 Uint16 Uint16 Uint8 Uint16 Uint16 Uint8 Uint32 Uint16 6 Parameter Overview VLT® Micro Drive FC 51 Operating Instructions MG.02.A4.02 - VLT® is a registered Danfoss trademark Parameter Number 3 - 00 3 - 02 3 - 03 3 - 10 3 - 11 3 - 12 3 - 14 3 - 15 3 - 16 3 - 17 3 - 18 3 - 40 3 - 41 3 - 42 3 - 50 3 - 51 3 - 52 3 - 80 3 - 81 Parameter Description Reference Range Minimum Reference Maximum Reference Preset Reference Jog Speed [Hz] Catch up/slow Down Value Preset Relative Reference Reference Resource 1 Reference Resource 2 Reference Resource 3 Relative Scaling Reference Resource Ramp 1 Type Ramp 1 Ramp up Time Ramp 1 Ramp Down Time Ramp 2 Type Ramp 2 Ramp up Time Ramp 2 Ramp down Time Jog Ramp Time Quick Stop Ramp Time 6.2.8 3-** Reference/Ramps Default Value [0] Min - Max 0 50 0% 5 Hz 0% 0% [1] Analog in 53 [2] Analog in 60 [11] Local bus reference [0] No function [0] Linear 3s 3s [0] Linear 3s 3s 3s 3s 2 Setup All set-ups All set-ups All set-ups All set-ups All set-ups All set-ups All set-ups All set-ups All set-ups All set-ups All set-ups All set-ups All set-ups All set-ups All set-ups All set-ups All set-ups All set-ups 1 set-up Change During Operation TRUE TRUE TRUE TRUE TRUE TRUE TRUE TRUE TRUE TRUE TRUE TRUE TRUE TRUE TRUE TRUE TRUE TRUE TRUE Conversion Index -3 -3 -2 -1 -2 -2 -2 -2 -2 -2 -2 -2 Type Uint8 Int32 Int32 Int16 Uint16 Int16 Int16 Uint8 Uint8 Uint8 Uint8 Uint8 Uint32 Uint32 Uint8 Uint32 Uint32 Uint32 Uint32 VLT® Micro Drive FC 51 Operating Instructions MG.02.A4.02 - VLT® is a registered Danfoss trademark 6 Parameter Overview 6 49 Parameter Description Motor Speed Direction Motor Speed Low Limit [Hz] Motor Speed High Limit [Hz] Torque Limit Motor Mode Torque Limit Generator Mode Warning Current Low Warning Current High Missing Motor Phase Function Bypass Speed From [Hz] Bypass Speed To [Hz] 6.2.9 4-** Limits/Warnings Default Value [2] Both directions 0 Hz 65 Hz 150% 100% 0A 26 A [1] On 0 Hz 0 Hz 2 Setup All set-ups All set-ups All set-ups All set-ups All set-ups All set-ups All set-ups All set-ups All set-ups All set-ups Change During Operation FALSE FALSE FALSE TRUE TRUE TRUE TRUE FALSE TRUE TRUE 6 Parameter Number 4 - 10 4 - 12 4 - 14 4 - 16 4 - 17 4 - 50 4 - 51 4 - 58 4 - 61 4 - 63 Conversion Index -1 -1 0 0 -2 -2 -1 -1 Type Uint8 Uint16 Uint16 Uint16 Uint16 Uint32 Uint32 Uint8 Uint16 Uint16 6 Parameter Overview 50 VLT® Micro Drive FC 51 Operating Instructions MG.02.A4.02 - VLT® is a registered Danfoss trademark Parameter Number 5 - 10 5 - 11 5 - 12 5 - 13 5 - 15 5 - 40 5 - 55 5 - 56 5 - 57 5 - 58 Parameter Description Terminal 18 Digital Input Terminal 19 Digital Input Terminal 27 Digital Input Terminal 29 Digital Input Terminal 33 Digital Input Function Relay Terminal 33 Low Frequency Terminal 33 High Frequency Terminal 33 Low Ref./Feedb. Value Terminal 33 High Ref./Feedb. Value 6.2.10 5-** Digital In/Out Default Value [8] Start [10] Reversing [1] Reset [14] Jog [16] Preset ref bit 0 [0] No operation 20 Hz 5000 Hz 0 50 2 Setup All set-ups All set-ups All set-ups All set-ups All set-ups All set-ups All set-ups All set-ups All set-ups All set-ups Change During Operation TRUE TRUE TRUE TRUE TRUE TRUE TRUE TRUE TRUE TRUE Conversion Index 0 0 -3 -3 Type Uint8 Uint8 Uint8 Uint8 Uint8 Uint8 Uint16 Uint16 Int32 Int32 VLT® Micro Drive FC 51 Operating Instructions MG.02.A4.02 - VLT® is a registered Danfoss trademark 6 Parameter Overview 6 51 Parameter Description Live Zero Timeout Time Live Zero TimeoutFunction Terminal 53 Low Voltage Terminal 53 High Voltage Terminal 53 Low Current Terminal 53 High Current Terminal 53 Low Ref./Feedb. Value Terminal 53 High Ref./Feedb. Value Terminal 53 Filter Time Constant Terminal 53 mode Terminal 60 Low Current Terminal 60 High Current Terminal 60 Low Ref./Feedb. Value Terminal 60 High Ref./Feedb. Value Terminal 60 Filter Time Constant LCP potentiometer Low Ref. LCP potentiometer High Ref. Terminal 42 Mode Terminal 42 Analog Output Terminal 42 Digital Output Terminal 42 Output Min Scale Terminal 42 Output Max Scale 6.2.11 6-** Analog In/Out Default Value 10 s [0] Off 0.07 V 10 V 0.14 mA 20 mA 0 50 0.01 s [0] Voltage mode 0.14 mA 20 mA 0 50 0.01 s 0 50 [0] 0-20 mA [0] No operation [0] No operation 0% 100% 2 Setup All set-ups All set-ups All set-ups All set-ups All set-ups All set-ups All set-ups All set-ups All set-ups 1 set-up All set-ups All set-ups All set-ups All set-ups All set-ups All set-ups All set-ups All set-ups All set-ups All set-ups All set-ups All set-ups Change During Operation TRUE TRUE TRUE TRUE TRUE TRUE TRUE TRUE TRUE TRUE TRUE TRUE TRUE TRUE TRUE TRUE TRUE TRUE TRUE TRUE TRUE TRUE 6 Parameter Number 6 - 00 6 - 01 6 - 10 6 - 11 6 - 12 6 - 13 6 - 14 6 - 15 6 - 16 6 - 19 6 - 22 6 - 23 6 - 24 6 - 25 6 - 26 6 - 81 6 - 82 6 - 90 6 - 91 6 - 92 6 - 93 6 - 94 Conversion Index 0 -2 -2 -2 -2 -3 -3 -2 -2 -2 -3 -3 -2 -3 -3 -2 -2 Type Uint8 Uint8 Uint16 Uint16 Uint16 Uint16 Int32 Int32 Uint16 Uint8 Uint16 Uint16 Int32 Int32 Uint16 Int32 Int32 Uint8 Uint8 Uint8 Uint16 Uint16 6 Parameter Overview 52 VLT® Micro Drive FC 51 Operating Instructions MG.02.A4.02 - VLT® is a registered Danfoss trademark Parameter Number 7 - 20 7 - 30 7 - 31 7 - 32 7 - 33 7 - 34 7 - 38 7 - 39 Parameter Description Process CL Feedback 1 Resource Process PI Normal/ Inverse Control Process PI Anti Windup Process PI Start Speed Process PI Proportional Gain Process PI Integral Time Process PI Feed Forward Factor On Reference Bandwidth 6.2.12 7-** Controllers Default Value [0] No function [0] Normal [1] Enabled 0 Hz 0.01 9999 s 0% 5% 2 Setup All set-ups All set-ups All set-ups All set-ups All set-ups All set-ups All set-ups All set-ups Change During Operation TRUE TRUE TRUE TRUE TRUE TRUE TRUE TRUE Conversion Index -1 -2 -2 0 0 Type Uint8 Uint8 Uint8 Uint16 Uint16 Uint32 Uint16 Uint8 VLT® Micro Drive FC 51 Operating Instructions MG.02.A4.02 - VLT® is a registered Danfoss trademark 6 Parameter Overview 6 53 Parameter Description Control Site Control Word Source Control Word Timeout Time Control Word Timeout Function Reset Control Word Timeout Protocol Address FC Port Baud Rate FC Port Parity Minimum Response Delay Max Response Delay Coasting Select Quick Stop Select DC Brake Select Start Select Reversing Select Set-up Select Preset Reference Select Bus feedback 1 6.2.13 8-** Comm. and Options Default Value [0] Digital and ctrl.word [1] FC RS485 1s [0] Off [0] No function [0] FC 1 [2] 9600 Baud [0] Even Parity 1 Stop Bit 0.01 s 5s [3] Logic OR [3] Logic OR [3] Logic OR [3] Logic OR [3] Logic OR [3] Logic OR [3] Logic OR 0 2 Setup All set-ups All set-ups 1 set-up 1 set-up 1 set-up 1 set-up 1 set-up 1 set-up 1 set-up 1 set-up 1 set-up All set-ups All set-ups All set-ups All set-ups All set-ups All set-ups All set-ups All set-ups Change During Operation TRUE TRUE TRUE TRUE TRUE TRUE TRUE TRUE TRUE TRUE TRUE TRUE TRUE TRUE TRUE TRUE TRUE TRUE TRUE 6 Parameter Number 8 - 01 8 - 02 8 - 03 8 - 04 8 - 06 8 - 30 8 - 31 8 - 32 8 - 33 8 - 35 8 - 36 8 - 50 8 - 51 8 - 52 8 - 53 8 - 54 8 - 55 8 - 56 8 - 94 Conversion Index -1 0 0 -3 -3 0 Type Uint8 Uint8 Uint16 Uint8 Uint8 Uint8 Uint8 Uint8 Uint8 Uint16 Uint16 Uint8 Uint8 Uint8 Uint8 Uint8 Uint8 Uint8 Int16 6 Parameter Overview 54 VLT® Micro Drive FC 51 Operating Instructions MG.02.A4.02 - VLT® is a registered Danfoss trademark 6.2.14 13-** Parameter Number 13 - 00 13 - 01 13 - 02 13 - 03 13 - 10 13 - 11 13 - 12 13 - 20 13 - 40 13 - 41 13 - 42 13 - 43 13 - 44 13 - 51 13 - 52 SL Controller Mode Start Event Stop Event Reset SLC Comparator Operand Comparator Operator Comparator Value SL Controller Timer Logic Rule Boolean 1 Logic Rule Operator 1 Logic Rule Boolean 2 Logic Rule Operator 2 Logic Rule Boolean 3 SL Controller Event SL Controller Action Smart Logic Parameter Description Default Value [0] Off [39] Start command [40] Drive stopped [0] Do not reset [0] Disabled [1] ApproxEqual 0 0s [0] False [0] Disabled [0] False [0] Disabled [0] False [0] False [0] Disabled 2 Setup 1 set-up 1 set-up 1 set-up 1 set-up 1 set-up 1 set-up 1 set-up 1 set-up 1 set-up 1 set-up 1 set-up 1 set-up 1 set-up 1 set-up 1 set-up Change During Operation TRUE TRUE TRUE TRUE TRUE TRUE TRUE TRUE TRUE TRUE TRUE TRUE TRUE TRUE TRUE Conversion Index -1 -1 - Type Uint8 Uint8 Uint8 Uint8 Uint8 Uint8 Int32 Uint32 Uint8 Uint8 Uint8 Uint8 Uint8 Uint8 Uint8 VLT® Micro Drive FC 51 Operating Instructions MG.02.A4.02 - VLT® is a registered Danfoss trademark 6 Parameter Overview 6 55 Parameter Description Switching Frequency Overmodulation Function at Mains Imbalance Reset Mode Automatic Restart Time Operation Mode Action At Inverter Fault AEO Minimum Magnetisation 6.2.15 14-** Special Functions Default Value [1] 4.0 kHz [1] On [0] Trip [0] Manual reset 10 s [0] Normal operation [0] Trip 66 % 2 Setup All set-ups All set-ups All set-ups All set-ups All set-ups 1 set-up All set-ups All set-ups Change During Operation TRUE FALSE TRUE TRUE TRUE TRUE TRUE TRUE 6 Parameter Number 14 - 01 14 - 03 14 - 12 14 - 20 14 - 21 14 - 22 14 - 26 14 - 41 Conversion Index 0 0 Type Uint8 Uint8 Uint8 Uint8 Uint16 Uint8 Uint8 Uint8 6 Parameter Overview 56 VLT® Micro Drive FC 51 Operating Instructions MG.02.A4.02 - VLT® is a registered Danfoss trademark Parameter Number 15 - 00 15 - 01 15 - 02 15 - 03 15 - 04 15 - 05 15 - 06 15 - 07 15 - 30 15 - 40 15 - 41 15 - 42 15 - 43 15 - 46 15 - 48 15 - 51 Parameter Description Operating Time Running Hours kWh Counter Power Up's Over Temp's Over Volt's Reset kWh Counter Reset Running Hours Counter Fault Log: Error Code FC Type Power Section Voltage SW ID Control Card Frequency Converter Ordering No LCP Id No Frequency Converter Serial Number 6.2.16 15-** Drive Information Default Value 0 0 0 0 0 0 [0] Do not reset [0] Do not reset 0 2 Setup 1 set-up 1 set-up 1 set-up 1 set-up 1 set-up 1 set-up 1 set-up 1 set-up 1 set-up 1 set-up 1 set-up 1 set-up 1 set-up 1 set-up 1 set-up 1 set-up Change During Operation TRUE TRUE TRUE TRUE TRUE TRUE TRUE TRUE TRUE FALSE FALSE FALSE FALSE FALSE FALSE FALSE Conversion Index 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Type Uint32 Uint32 Uint32 Uint32 Uint16 Uint16 Uint8 Uint8 Uint8 VisibleString VisibleString VisibleString VisibleString VisibleString VisibleString VisibleString VLT® Micro Drive FC 51 Operating Instructions MG.02.A4.02 - VLT® is a registered Danfoss trademark 6 Parameter Overview 6 57 Parameter Description Control Word Reference [Unit] Reference % Status Word Main Actual Value [%] Power [kW] Power [hp] Motor Voltage Frequency Motor Current Frequency [%] Motor Thermal DC Link Voltage Heatsink Temp. Inverter Thermal Inv. Nom. Current Inv. Max. Current SL Controller State External Reference Pulse Reference Feedback [Unit] Digital input 18,19,27,33 Digital input 29 Analog Input 53 (V) Analog Input 53 (mA) Analog Input 60 Analog Output 42 [mA] Pulse input 33 Relay Output [bin] Counter A Counter B FC Port REF 1 Alarm Word Warning Word Ext. Status Word 6.2.17 16-** Data Readouts Default Value 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 20 0 0 0 0 0 0 0 2 Setup 1 set-up 1 set-up 1 set-up 1 set-up 1 set-up 1 set-up 1 set-up 1 set-up 1 set-up 1 set-up 1 set-up 1 set-up 1 set-up 1 set-up 1 set-up 1 set-up 1 set-up 1 set-up 1 set-up 1 set-up 1 set-up 1 set-up 1 set-up 1 set-up 1 set-up 1 set-up 1 set-up 1 set-up 1 set-up 1 set-up 1 set-up 1 set-up 1 set-up 1 set-up 1 set-up Change During Operation TRUE TRUE TRUE TRUE TRUE TRUE TRUE TRUE TRUE TRUE TRUE TRUE TRUE TRUE TRUE TRUE TRUE TRUE TRUE TRUE TRUE TRUE TRUE TRUE TRUE TRUE TRUE TRUE TRUE TRUE TRUE TRUE TRUE TRUE TRUE 6 Parameter Number 16 - 00 16 - 01 16 - 02 16 - 03 16 - 05 16 - 10 16 - 11 16 - 12 16 - 13 16 - 14 16 - 15 16 - 18 16 - 30 16 - 34 16 - 35 16 - 36 16 - 37 16 - 38 16 - 50 16 - 51 16 - 52 16 - 60 16 - 61 16 - 62 16 - 63 16 - 64 16 - 65 16 - 68 16 - 71 16 - 72 16 - 73 16 - 86 16 - 90 16 - 92 16 - 94 Conversion Index 0 -3 -1 0 -2 -3 -3 0 -1 -2 -1 0 0 0 0 -2 -2 0 -1 -1 -3 0 0 -2 -2 -2 -2 0 0 0 0 0 0 0 0 Type Uint16 Int32 Int16 Uint16 Int16 Uint16 Uint16 Uint16 Uint16 Uint16 Uint16 Uint8 Uint16 Uint8 Uint8 Uint16 Uint16 Uint8 Int16 Int16 Int32 Uint16 Uint8 Uint16 Uint16 Uint16 Uint16 Uint16 Uint8 Int16 Int16 Int16 Uint32 Uint32 Uint32 6 Parameter Overview 58 VLT® Micro Drive FC 51 Operating Instructions MG.02.A4.02 - VLT® is a registered Danfoss trademark Drive Initialised to Default Value The connection between drive and LCP is lost Button disabled Copy fail LCP data invalid LCP data not compatible 80 84 85 86 87 88 X X X X Warning X X X X X X X X X X X X X X X X X X X X X X X X X X Alarm X X X X X X X X X X X X X X X X X X X Trip Lock MG.02.A4.02 - VLT® is a registered Danfoss trademark Code list Table 7.1: Warnings and Alarms 89 Parameter read only 90 Parameter database busy 91 Parameter value is not valid in this mode 92 Parameter value exceeds the min/max limits nw run Not While RUNning Err. A wrong password was entered 1) These faults may be caused by mains distortions. Installing Danfoss Line Filter may rectify this problem. Description Live zero error Mains phase loss1) DC over voltage1) DC under voltage1) Inverter overloaded Motor ETR over temperature Motor thermistor over temperature Torque limit Over Current Earth fault Short Circuit Control word timeout Brake resistor short-circuited Brake chopper short-circuited Brake check Power board over temp Motor phase U missing Motor phase V missing Motor phase W missing Internal fault Control Voltage Fault AMT check Unom and Inom AMT low Inom Current limit Mechanical Brake Low No. 2 4 7 8 9 10 11 12 13 14 16 17 25 27 28 29 30 31 32 38 47 51 52 59 63 X X X X X X X X X X X Error Cause of Problem Signal on terminal 53 or 60 is less than 50% of value set in par. 6-10, 6-12 and 6-22. Missing phase on supply side, or too high voltage imbalance. Check supply voltage. Intermediate circuit voltage exceeds limit. Intermediate circuit voltage drops below “voltage warning low” limit. More than 100% load for too long. Motor is too hot due to more than 100% load for too long. Thermistor or thermistor connection is disconnected. Torque exceeds value set in either par. 4-16 or 4-17. Inverter peak current limit is exceeded. Discharge from output phases to ground. Short-circuit in motor or on motor terminals. No communication to frequency converter. Brake resistor is short-circuited, thus brake function is disconnected. Brake transistor is short-circuited, thus brake function is disconnected. Brake resistor is not connected/working Heat-sink cut-out temperature has been reached. Motor phase U is missing. Check the phase. Motor phase V is missing. Check the phase. Motor phase W is missing. Check the phase. Contact local Danfoss supplier. 24 V DC may be overloaded. Wrong setting for motor voltage and/or motor current. Motor current is too low. Check settings. VLT overload. Actual motor current has not exceeded “release brake” current within “start delay” time window. All parameter settings are initialized to default settings. No communication between LCP and frequency converter See parameter group 0-4* LCP An error occurred while copying from frequency converter to LCP or vice versa. Occurs when copying from LCP if the LCP contains erroneous data - or if no data was uploaded to the LCP. Occurs when copying from LCP if data are moved between frequency converters with major differences in software versions. Occurs when trying to write to a read-only parameter. LCP and RS485 connection are trying to update parameters simultaneously. Occurs when trying to write an illegal value to a parameter. Occurs when trying to set a value outside the range. Parameter can only be changed when the motor is stopped. Occurs when using a wrong password for changing a password-protected parameter. VLT® Micro Drive FC 51 Operating Instructions 7 Troubleshooting 7 Troubleshooting 7 59 VLT® Micro Drive FC 51 Operating Instructions 7 Troubleshooting 7.1.1 Alarm, Warning and Extended Status Word Bit 7 Hex Dec Par 1690 Par 1692 Par 1694 AlarmWord WarningWord ExtendedStatusWord 0 1 1 Brake check 1 2 2 Pwr.card temp 2 4 4 Earth Fault 3 8 8 4 10 16 Ctrl.word TO Ctrl.word TO 5 20 32 Over Current Over Current 6 40 64 7 80 128 Motor th over Motor th over Output current high 8 100 256 Motor ETR over Motor ETR over Output current low 9 200 512 Inverter overload Inverter overload 10 400 1024 DC under volt DC under volt 11 800 2048 DC over volt DC over volt 12 1000 4096 Short Circuit 13 2000 8192 14 4000 16384 Braking Mains ph. loss 8000 32768 "AMT Not OK" 10000 65536 Live zero error 17 20000 131072 Internal fault 18 40000 262144 19 80000 524288 20 100000 1048576 V phase loss 21 200000 2097152 W phase loss 22 400000 4194304 23 800000 8388608 24 1000000 16777216 2000000 33554432 4000000 67108864 Brake resistor shortcircuit Brake IGBT shortcircuit 134217728 268435456 29 20000000 536870912 30 40000000 1073741824 31 80000000 2147483648 60 OVC active Live zero error AC brake Control Voltage Fault 25 8000000 Mains ph. loss U phase loss 26 10000000 Catch up Torque limit 15 27 Start CW/CCW Slow down 16 28 Ramping Pwr.card temp Current limit MotorPhaseMissing Drive initialised Undefined Mech. brake low MG.02.A4.02 - VLT® is a registered Danfoss trademark DatabaseBusy VLT® Micro Drive FC 51 Operating Instructions 8 Specifications 8 Specifications 8.1 Mains Supply 8.1.1 Mains Supply 1 x 200 - 240 VAC Normal overload 150% for 1 minute Frame M1 P0K18 0.18 0.25 Frame M1 P0K37 0.37 0.5 Frame M1 P0K75 0.75 1 Frame M2 P1K5 1.5 2 Frame M3 P2K2 2.2 3 Continuous (3 x 200-240 V ) [A] Intermittent (3 x 200-240 V ) [A] Max. cable size: (mains, motor) [mm2 /AWG] 1.2 1.8 2.2 3.3 4.2 6.3 6.8 10.2 9.6 14.4 Continuous (1 x 200-240 V ) [A] Intermittent (1 x 200-240 V ) [A] Max. pre-fuses [A] Environment Estimated power loss at rated load [W], Best case/Typical1) Weight enclosure IP20 [kg] Efficiency Best case/Typical1) 3.3 4.5 6.1 8.3 11.6 18.7 15.6 26.4 See Section Fuses 26.4 37.0 12.5/ 15.5 1.1 95.6/ 94.5 20.0/ 25.0 1.1 96.5/ 95.6 Frequency converter Typical Shaft Output [kW] Typical Shaft Output [HP] Output current 4/10 Max. input current 36.5/ 44.0 1.1 96.6/ 96.0 61.0/ 67.0 1.6 97.0/ 96.7 81.0/85.1 3.0 96.9/97.1 8 Table 8.1: Mains supply 1 x 200 - 240 VAC 8.1.2 Mains Supply 3 x 200 - 240 VAC Normal overload 150% for 1 minute Frequency converter Typical Shaft Output [kW] Typical Shaft Output [HP] Output current Continuous (3 x 200-240 V ) [A] Intermittent (3 x 200-240 V ) [A] Max. cable size: (mains, motor) [mm2 /AWG] Frame M1 Frame M1 Frame M1 Frame M2 Frame M3 Frame M3 P0K25 P0K37 P0K75 P1K5 P2K2 P3K7 0.25 0.37 0.75 1.5 2.2 3.7 0.33 0.5 1 2 3 5 1.5 2.3 2.2 3.3 4.2 6.3 6.8 10.2 9.6 14.4 15.2 22.8 6.7 10.9 8.3 14.4 See Section Fuses 15.4 23.4 24.3 35.3 31.5/ 39.5 1.1 97.1/ 96.3 72.0/ 77.1 3.0 97.2/ 97.4 115.0/ 122.8 3.0 97.3/ 97.4 4/10 Max. input current Continuous (3 x 200-240 V ) [A] Intermittent (3 x 200-240 V ) [A] Max. pre-fuses [A] Environment Estimated power loss at rated load [W], Best case/Typical1) Weight enclosure IP20 [kg] Efficiency Best case/Typical1) 2.4 3.2 3.5 4.6 14.0/ 20.0 1.1 96.4/ 94.9 19.0/ 24.0 1.1 96.7/ 95.8 51.0/ 57.0 1.6 97.4/ 97.2 Table 8.1: Mains supply 3 x 200 - 240 VAC 1. Power loss at rated load conditions. MG.02.A4.02 - VLT® is a registered Danfoss trademark 61 62 Table 8.1: Mains supply 3 x 380 - 480 VAC Continuous (3 x 380-440 V ) [A] Intermittent (3 x 380-440 V ) [A] Continuous (3 x 440-480 V ) [A] Intermittent (3 x 440-480 V ) [A] Max. pre-fuses [A] Environment Estimated power loss at rated load [W] Best case/Typical1) Weight enclosure IP20 [kg] Efficiency Best case/Typical1) 1. Power loss at rated load conditions. Max. input current 3.5 4.7 3.0 4.0 28.5/43.5 1.1 97.4/96.0 18.5/25.5 1.1 96.8/95.5 2.2 3.3 2.1 3.2 1.2 1.8 1.1 1.7 1.9 2.6 1.7 2.3 P0K75 0.75 1 Frame M1 P0K37 0.37 0.5 Frame M1 98.0/97.2 1.6 41.5/56.5 5.9 8.7 5.1 7.5 3.7 5.6 3.4 5.1 P1K5 1.5 2 Frame M2 8 (mains, motor) [mm2/ AWG] Normal overload 150% for 1 minute Frequency converter Typical Shaft Output [kW] Typical Shaft Output [HP] IP 20 Output current Continuous (3 x 380-440 V) [A] Intermittent (3 x 380-440 V) [A] Continuous (3 x 440-480 V) [A] Intermittent (3 x 440-480 V) [A] Max. cable size: 8.1.3 Mains Supply 3 x 380 - 480 VAC 4/10 7.2 10.8 6.3 9.5 P3K0 3.0 4 Frame M3 97.9/97.1 1.6 57.5/81.5 97.2/98.0 3.0 75.0/101.6 8.5 11.5 12.6 16.8 7.3 9.9 10.8 14.4 See Section Fuses 5.3 8.0 4.8 7.2 P2K2 2.2 3 Frame M2 97.3/98.0 3.0 98.5/133.5 14.4 20.2 12.4 17.5 9.0 13.7 8.2 12.3 P4K0 4.0 5 Frame M3 24.8 36.3 21.4 30.1 15.5 23.5 14.0 21.3 P7K5 7.5 10 Frame M3 97.5/98.0 3.0 97.5/98.0 3.0 131.0/166.8 175.0/217.5 19.2 27.4 16.6 23.6 12.0 18.0 11.0 16.5 P5K5 5.5 7.5 Frame M3 8 Specifications VLT® Micro Drive FC 51 Operating Instructions MG.02.A4.02 - VLT® is a registered Danfoss trademark VLT® Micro Drive FC 51 Operating Instructions 8 Specifications 8.2 Other Specifications Protection and Features: • Electronic thermal motor protection against overload. • Temperature monitoring of the heatsink ensures that the frequency converter trips in case of overtemperature • The frequency converter is protected against short-circuits on motor terminals U, V, W. • If a motor phase is missing, the frequency trips and issues an alarm. • If a mains phase is missing, the frequency converter trips or issues a warning (depending on the load). • Monitoring of the intermediate circuit voltage ensures that the frequency converter trips if the intermediate circuit voltage is too low or too high. • The frequency converter is protected against earth faults on motor terminals U, V, W. Mains supply (L1/L, L2, L3/N): Supply voltage 200-240 V ±10% Supply voltage 380-480 V ±10% Supply frequency 50/60 Hz Max. imbalance temporary between mains phases 3.0 % of rated supply voltage ≥ 0.4 nominal at rated load True Power Factor (λ) Displacement Power Factor (cosφ) near unity (> 0.98) Switching on input supply L1/L, L2, L3/N (power-ups) Environment according to EN60664-1 maximum 2 times/min. overvoltage category III/pollution degree 2 8 The unit is suitable for use on a circuit capable of delivering not more than 100.000 RMS symmetrical Amperes, 240/480 V maximum. Motor output (U, V, W): Output voltage 0 - 100% of supply voltage Output frequency 0-200 Hz (VVC+), 0-400 Hz (u/f) Switching on output Unlimited Ramp times 0.05 - 3600 sec. Cable lengths and cross sections: Max. motor cable length, screened/armoured (EMC correct installation) 15 m Max. motor cable length, unscreened/unarmoured 50 m Max. cross section to motor, mains, load sharing and brake * Maximum cross section to control terminals, rigid wire Maximum cross section to control terminals, flexible cable Maximum cross section to control terminals, cable with enclosed core 1.5 mm2/16 AWG (2 x 0.75 mm2) 1 mm2/18 AWG 0.5 mm2/20 AWG 0.25 mm2 Minimum cross section to control terminals * See tables for mains supply for more information! Digital inputs (Pulse/enocder inputs): Programmable digital inputs (Pulse/encoder) 5 (1) Terminal number 18, 19, 27, 29, 33, Logic PNP or NPN Voltage level 0 - 24 V DC Voltage level, logic'0' PNP < 5 V DC Voltage level, logic'1' PNP > 10 V DC Voltage level, logic '0' NPN > 19 V DC Voltage level, logic '1' NPN < 14 V DC Maximum voltage on input 28 V DC Input resistance, Ri approx. 4 k Max. pulse frequency at terminal 33 5000 Hz Min. pulse frequency at terminal 33 20 Hz MG.02.A4.02 - VLT® is a registered Danfoss trademark 63 VLT® Micro Drive FC 51 Operating Instructions 8 Specifications Analog inputs: Number of analog inputs 2 Terminal number 53, 60 Voltage level 0 -10 V Input resistance, Ri approx. 10 kΩ Max. voltage 20 V Current level 0/4 to 20 mA (scaleable) Input resistance, Ri approx. 200 Ω Max. current 30 mA Analog output: Number of programmable analog outputs 1 Terminal number 42 Current range at analog output 0/4 - 20 mA Max. resistor load to common at analog output 500 Ω Accuracy on analog output Max. error: 0.8 % of full scale Resolution on analog output 8 bit The analog output is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals. Control card, RS-485 serial communication: Terminal number 68 (P,TX+, RX+), 69 (N,TX-, RX-) Terminal number 61 8 Common for terminals 68 and 69 The RS-485 serial communication circuit is functionally separated from other central circuits and galvanically isolated from the supply voltage (PELV). Control card, 24 V DC output: Terminal number 12 Max. load 200 mA Relay output: Programmable relay output 1 Relay 01 Terminal number 01-03 (break), 01-02(make) Max. terminal load (AC-1)1) on 01-02 (NO) (Resistive load) 250 V AC, 2 A Max. terminal load (AC-15)1) on 01-02 (NO) (Inductive load @ cosφ 0.4) 250 V AC, 0.2 A Max. terminal load (DC-1)1) on 01-02 (NO) (Resistive load) 30 V DC, 2 A Max. terminal load (DC-13)1) on 01-02 (NO) (Inductive load) 24 V DC, 0.1A Max. terminal load (AC-1)1) on 01-03 (NC) (Resistive load) 250 V AC, 2 A Max. terminal load (AC-15)1) on 01-03 (NC) (Inductive load @ cosφ 0.4) 250 V AC, 0.2A Max. terminal load (DC-1)1) on 01-03 (NC) (Resistive load) 30 V DC, 2 A Min. terminal load on 01-03 (NC), 01-02 (NO) Environment according to EN 60664-1 24 V DC 10 mA, 24 V AC 20 mA overvoltage category III/pollution degree 2 1) IEC 60947 part 4 and 5 Control card, 10 V DC output: Terminal number 50 Output voltage 10.5 V ±0.5 V Max. load 25 mA The 10 V DC supply is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals. Surroundings: Enclosure IP 20 Enclosure kit available IP 21 Enclosure kit available TYPE 1 Vibration test Max. relative humidity 1.0 g 5% - 95%(IEC 60721-3-3; Class 3K3 (non-condensing) during operation Aggressive environment (IEC 60721-3-3), coated class 3C3 Test method according to IEC 60068-2-43 H2S (10 days) 64 MG.02.A4.02 - VLT® is a registered Danfoss trademark VLT® Micro Drive FC 51 Operating Instructions 8 Specifications Ambient temperature Max. 40 °C Derating for high ambient temperature, see section on special conditions Minimum ambient temperature during full-scale operation 0 °C Minimum ambient temperature at reduced performance - 10 °C Temperature during storage/transport -25 - +65/70 °C Maximum altitude above sea level without derating 1000 m Maximum altitude above sea level with derating 3000 m Derating for high altitude, see section on special conditions EMC standards, Emission EN 61800-3, EN 61000-6-3/4, EN 55011, IEC 61800-3 EN 61800-3, EN 61000-6-1/2, EN 61000-4-2, EN 61000-4-3, EMC standards, Immunity EN 61000-4-4, EN 61000-4-5, EN 61000-4-6 See section on special conditions 8.3 Special Conditions 8.3.1 The Purpose of Derating Derating must be taken into account when using the frequency converter at low air pressure (heights), at low speeds or at high ambient temperature. The required action is described in this section. 8.3.2 Derating for Ambient Temperature 8 The ambient temperature measured over 24 hours should be at least 5 °C lower than the max. ambient temperature. If the frequency converter is operated at high ambient temperature, the continuous output current should be decreased. The frequency converter has been designed for operation at max 50 °C ambient temperature with one motor size smaller than nominal. Continuous operation at full load at 50 °C ambient temperature will reduce the lifetime of the frequency converter. 8.3.3 Derating for Low Air Pressure The cooling capability of air is decreased at low air pressure. For altitudes above 2000 m, please contact Danfoss regarding PELV. Below 1000 m altitude no de-rating is necessary but above 1000 m the ambient temperature or the maximum output current should be decreased. Decrease the output by 1% per 100 m altitude above 1000 m or reduce the max. ambient temperature by 1 degree per 200 m 8.3.4 Derating for Running at Low Speeds When a motor is connected to at frequency converter, it is necessary to check that the cooling of the motor is adequate. A problem may occur at low speeds in constant torque applications. Running continuously at low speeds – below half the nominal motor speed – may require additional air cooling. Alternatively, choose a larger motor (one size up). MG.02.A4.02 - VLT® is a registered Danfoss trademark 65 VLT® Micro Drive FC 51 Operating Instructions 8 Specifications 8.4 Options for VLT Micro Drive FC 51 Ordering No Description 132B0100 VLT Control Panel LCP 11 w/o potentiometer 132B0101 VLT Control Panel LCP 12 with potentiometer 132B0102 Remote Mounting Kit for LCP incl. 3 m cable, IP55 with LCP 11, IP21 with LCP 12. 8 132B0103 Nema Type 1 kit for M1 frame 132B0104 Nema Type 1 kit for M2 frame 132B0105 Nema Type 1 kit for M3 frame 132B0106 De-coupling plate kit for M1 and M2 frames 132B0107 De-coupling plate kit for M3 frame 132B0108 IP21 for M1 frame 132B0109 IP21 for M2 frame 132B0110 IP21 for M3 frame 132B0111 DIN rail mounting kit for M1 frame Danfoss Line Filters and brake resistors are available upon request. 66 MG.02.A4.02 - VLT® is a registered Danfoss trademark VLT® Micro Drive FC 51 Operating Instructions Index Index A Active Set-up 17 Active Set-up 41, 46 Alarm, Warning And Extended Status Word 60 Ambient Temperature 65 Analog In/out 52 Analog Inputs 63 Analog Output 64 Automatic Motor Tuning (amt) 21 B Brake Resistor 48 Brake Resistor (ohm) 41 Brake Resistor Short-circuited 59 Brakes 48 Bus Termination 15 C Cable Lengths And Cross Sections 63 Clearance 9 Comm. And Options 54 Configuration Mode 22 Control Card, 10 V Dc Output 64 Control Card, 24 V Dc Output 64 Control Card, Rs-485 Serial Communication: 64 Control Terminals 15 Control Word According To Fc Profile 35 Controllers 53 Conversion Index 45 D Danfoss Fc Control Profile 35 Data Readouts 58 Dc-brake 42 Dc-brake 41 De-coupling Plate Kit 66 Derating For Ambient Temperature 65 Derating For Low Air Pressure 65 Derating For Running At Low Speeds 65 Digital In/out 51 Digital Inputs (pulse/enocder Inputs): 63 Digital Inputs: 63 Din Rail Mounting Kit 10, 66 Display 17 Disposal Instruction 8 Drive Information 57 E Earth Leakage Current 5, 7 Edit Set-up 17 Edit Set-up 41, 46 Electronic Waste 8 Emc-correct Installation 12 Explanation Of The Control Bits 35 Explanation Of The Status Bits 38 F Frequency Converter With Modbus Rtu 25 Function Codes Supported By Modbus Rtu 29 Fuses 11 MG.02.A4.02 - VLT® is a registered Danfoss trademark 67 Index VLT® Micro Drive FC 51 Operating Instructions H Hand Mode 42 Hand Mode 47 How To Connect 11 I Indicator Lights 18 Ip21 66 Isolated Mains Source 7 It Mains 7 L Lcp 11 17 Lcp 12 17 Leakage Current 7 Limits/warnings 50 Load Compensation 41, 47 Load Sharing/brake 16 Load/motor 47 M Main Menu 18, 24 Mains Connection 12 Mains Supply 61 Mains Supply (l1/l, L2, L3/n) 63 Mains Supply 1 X 200 - 240 Vac 61 Mains Supply 3 X 200 - 240 Vac 61 Mains Supply 3 X 380 - 480 Vac 62 Max. Reference 22 Maximum Reference 21 Mct-10 Set-up Software 17 Mechanical Dimensions 10 Mechanical Installation 9 Min. Reference 22 Minimum Reference 21 Modbus Rtu 25 Modbus Rtu Message Framing Structure 26 Modbus Rtu Overview 25 Motor Connection 13 Motor Current 20 Motor Direction 18 Motor Frequency 20 Motor Nominal Speed 21 Motor Output (u, V, W): 63 Motor Overload Protection 7 Motor Phase 42, 50 Motor Power 20 Motor Protection 63 Motor Speed High Limit 22 Motor Speed Low Limit 22 Motor Temperature 41 Motor Voltage 20 N Navigation Keys 19 O Operation Keys 19 Operation/display 46 Options 66 Options For Vlt Micro Drive Fc 51 66 Other Specifications 63 68 MG.02.A4.02 - VLT® is a registered Danfoss trademark VLT® Micro Drive FC 51 Operating Instructions Output Performance (u, V, W) Index 63 Overcurrent Protection 11 Over-voltage Control 41, 48 P Parameter Number 18 Parameter Overview 41 Power Circuit - Overview 16 Preset Reference 22 Process Cl Feedback Resource 23 Process Feed Forward Factor 23 Process Pi Anti Windup 23 Process Pi Integral Time 23 Process Pi Normal/inverse 23 Process Pi Proportional Gain 23 Process Pi Start Speed 23 Protection 11 Protection And Features 63 Q Quick Menu 18, 19 Quick Menu Parameters 20 R Ramp1 Ramp-down Time 22 Ramp1 Ramp-up Time 22 Readout Mode 18 Reference/ramps 49 Relay Output 64 Remote Mounting Kit 66 Residual Current Device 7 S S200 Switches 1-4 15 Serial Communication 19 Set-up Number 17 Set-up Software 17 Side-by-side Installation 9 Slip Compensation 41, 47 Smart Logic 55 Special Conditions 65 Special Functions 56 Specifications 61 Status Menu 18, 19 Status Word According To Fc Profile (stw) 37 Surroundings 64 Switches 15 T Template For Drilling 10 Terminal 60 Filter Time Constant 23 Terminal 60 High Current 23 Terminal 60 High Feedback Value 23 Terminal 60 Low Current 22 Terminal 60 Low Feedback Value 23 Thermistor 41 Thermistor Resource 47 Troubleshooting 59 U Ul Compliance 11 Unit 18 MG.02.A4.02 - VLT® is a registered Danfoss trademark 69 Index VLT® Micro Drive FC 51 Operating Instructions V Value 18 Vlt Control Panel Lcp 11 66 Vlt Control Panel Lcp 12 66 Voltage Level 63 W Warnings And Alarms 70 59 MG.02.A4.02 - VLT® is a registered Danfoss trademark