Cookson ColorCoteTM and CycleCoteTM Finishes

Transcription

Cookson ColorCoteTM and CycleCoteTM Finishes
Cookson ColorCote TM
and CycleCote TM Finishes
Quality, powder-coated surface treatments
X
08/13/15
JDF
Division 8 - Overhead Coiling Door - Product Data #08335 - par. 1.3
TT HH EE PP RR EE FF EE RR RR EE DD
ROLLING DOOR AND GRILLE
The Cookson Company, Inc.
www.cooksondoor.com
Due to individual computer monitor limitations, colors seen here may not accurately reflect the selected color.
To confirm your color choice, contact us for a printed ColorCote Chart or color sample.
Due to individual computer monitor limitations, colors seen here may not accurately reflect the selected color.
To confirm your color choice, contact us for a printed ColorCote Chart or color sample.
ColorCoteTM Benefits
CycleCoteTM Benefits
Eliminates Field Painting
Same Benefits as ColorCote, plus:
180 Standard Colors
Added Durability for High Cycle Applications
Unlimited Custom Colors
Low Coefficient of Friction Wear Resistance
More Durable
Tan, Gray, White, and Silver Standard
Prolonged Life
180 RAL Colors
Greater Protection
Unlimited Custom Colors
Less Maintenance
P.O. Box 23880
Phoenix, AZ 85063
The Cookson Company, Inc.
Phone: (800) 390-8590
Fax: (866) 448-6804
Visit our website at Cooksondoor.com
Or e-mail us at [email protected]
Facebook.com/The.Cookson.Company © 2012
Firefly™ RELEASING DEVICES
Releasing Devices
Firefly III™
A releasing device is an electro-mechanical device that allows a manually
released fire door to be connected to a smoke detector or central building
alarm system. Upon activation of a smoke detector or central building alarm
system, the releasing device will release the fire door and allow it to
automatically close. All releasing devices must be listed by an independent
testing laboratory and comply with UL-864 (Control Units and Accessories
for Fire Alarm Systems). The full line of Cookson Firefly™ releasing devices
are failsafe in design.
The Firefly III™ releasing device is made to connect to a building central
alarm system. It is powered by 24V DC power wired directly into the building
alarm control panel and is supported by the building alarm control panel
emergency power source. In case of building power failure, the fire alarm
control panel emergency power source will power the Firefly III™ and the
door will not close unless there is an alarm activation.
Firefly™ Releasing Devices
The Cookson Company offers 3 Firefly™ releasing devices to meet the
various needs of building alarm systems. Firefly™ releasing devices are
solid state and come with a variable alarm time delay factory preset to 10
seconds, but can be field set to a maximum of 60 seconds. Upon the
activation of a smoke detector or central alarm system, the Firefly™
releasing device will not release the fire door until the time delay has elapsed.
If the smoke detector or central alarm system is reset before the time delay
has elapsed, the door will not automatically close. This time delay feature is
to prevent the closing of fire doors due to power brownouts.
The Cookson Company, Inc.
Firefly III Plus™
The Firefly III Plus™ releasing device is made to be a stand alone releasing
device that does not need to, but can, be connected to a building central
alarm system. It has all of the features of the Firefly III™ plus a built in battery
that can power up to 2 smoke detectors and / or sounder strobes for as long
as 72 hours in the event of a power failure. This provides fire protection
during power failures, preventing unnecessary door closings, without the
expense of a central battery back-up system. The Firefly III™ Plus is
multivoltage 120 VAC, 24 VAC and 24 VDC.
Firefly IV MV™
The Firefly IV MV™ releasing device is made as a stand alone releasing
device or one that can be connected to a building central alarm system. It is
multivoltage 115 VAC, 24 VAC and 24 VDC and can power a 24 VDC closing
warning device. The Firefly IV MV™ will allow the door to close in the event of
a power failure that lasts longer than the 10 second time delay to assure
there is fire protection during sustained power failures.
Dimensions shown are for initial design. For final design, specifications,
and to view the complete Cookson Product line, visit cooksondoor.com.
THE PREFERRED
Built to Last
RELEASING DEVICE
Firefly III™ - 24 VDC Power Required
Firefly III Plus™ - Multi-voltage with integral battery back-up:
120 VAC, 24 VAC or 24 VDC Power Required
Firefly IV MV™ - Multi-voltage:
115 AC, 24 VAC or 24 VDC Power Required
Mechanical Reset
Indicator Lights are under the units.
Test Button is under the units.
7 21
5 21
10 87
Firefly III™
Firefly III Plus™
RESET
BUTTON
9 43
Firefly IV MV™
9 87
TEST BUTTON
YELLOW LED
Fire Fly III™ Release Device
TYPICAL RELEASE DEVICE INSTALLATION
Voltage:
SMOKE DETECTOR
24VDC
Stand By Current:
0.1A
Alarm Current:
0.15A
Battery: Not Applicable
FIREFLY RELEASING DEVICE
Minimum 12”
Fire Fly III Plus™ Release Device
Voltage:
FUSIBLE LINKS
120VAC 24VAC 24VDC
Stand By Current:
0.06A
0.3A
0.2A
Alarm Current:
0.06A
0.3A
0.25A
Battery: 12V 4.5 AHR
FIRE DOOR
Fire Fly IV™ Release Device
Voltage:
115VAC 24VAC 24VDC
Full Load:
1.1A
1.8A
1.8A
Stand By Current:
0.5A
0.5A
0.2A
Battery: Not Applicable
Alternate Mounting
The Cookson Company, Inc.
© 2010
2417 S. 50th Avenue
Phone: (800) 390-8590
Phoenix, AZ 85043
FAX: (866) 448-6804
[email protected]