Valtek Logix 1200e/1210e Digital Positioner
Transcription
Valtek Logix 1200e/1210e Digital Positioner
Valtek Logix 1200e/1210e Digital Positioner GENERAL INFORMATION The following instructions are designed to assist in unpacking, installing and performing maintenance as required on Valtek® Logix® 1200e digital positioners. Series 1000 is the term used for all the positioners herein; however, specific numbers indicate features specific to a model (i.e. Logix 1200e indicates that the positioner uses HART® protocol). Product users and maintenance personnel should thoroughly review this bulletin prior to installing, operating, or performing any maintenance on the valve. Separate Valtek Flow Control Products Installation, Operation, Maintenance instructions cover the valve (such as IOM 1 or IOM 27) and actuator (such as IOM 2 or IOM 31) portions of the system and other accessories. Refer to the appropriate instructions when this information is needed. WARNING: To avoid possible injury to personnel or damage to valve parts, users must strictly adhere to WARNING and CAUTION notes. Modifying this product, substituting non-factory or inferior parts, or using maintenance procedures other than outlined could drastically affect performance and be hazardous to personnel and equipment, and may void existing warranties. V ltek SKU 138430 WARNING: Standard industry safety practices must be adhered to when working on this or any process control product. Specifically, personal protective and lifting devices must be used as warranted. Valve and Instrumentation Storage Procedures Storage Control valve packages (a control valve and its instrumentation) can be safely stored in an enclosed building that affords environmental protection; heating is not required. Control valve packages must be stored on suitable skids, not directly on the floor. The storage location must also be free from flooding, dust, dirt, etc. Pre-installation Inspection If a valve control package has been stored for more than one year, inspect one actuator by disassembling it per the appropriate Installation, Operation, and Maintenance Instructions (IOM) prior to valve installation. If O-rings are out-of-round, deteriorated, or both, they must be replaced and the actuator rebuilt. All actuators must then be disassembled and inspected. If the actuator O-rings are replaced, complete the following steps: 1. Replace the pressure-balanced plug O-rings. 2. Inspect the solenoid and positioner soft goods and replace as necessary. 44 1 Table of Contents General Information ................................................... 1 Valve and Instrumentation Storage Procedures .... 1 Logix 1200e Positioner Overview............................... 3 Specifications ............................................................. 3 Positioner Operation .................................................. 4 Detailed Sequence of Positioner Operations......... 4 Logix 1000 Series Positioner Vented-design Conversion ................................................................. 5 Tubing Positioner to Actuator ................................ 6 Wiring and Grounding Guidelines.......................... 6 Available Spare Part Kits for Logix 1200e digital postioner .............................................................. 22 4 to 20 mA Analog Output Retrofit....................... 24 General Information ............................................. 24 Calibration............................................................ 25 Troubleshooting........................................................ 30 Introduction .......................................................... 30 Theory of Operation............................................. 30 Mounting and Installation..................................... 31 Calibration............................................................ 33 Control and Tuning .............................................. 34 HART Communication ......................................... 35 Alarms.................................................................. 37 Alerts.................................................................... 38 Advanced Features .................................................. 40 Logix 1200e Digital Positioner on Valtek Mark One Control Valve 44 2 Flowserve Corpor tion V ltek Control Prod cts Tel USA 801 489 8611 Unpacking Logix 1200e Positioner Overview 1. While unpacking the Logix 1200e positioner, check the packing list against the materials received. Lists describing the system and accessories are included in each shipping container. The Logix 1200e digital positioner is a two-wire, 4-20 mA input, digital valve positioner. The Logix 1200e positioner also utilizes the HART protocol to allow two-way remote communications with the positioner. The Logix 1200e positioner can control both double and single-acting actuators with linear and rotary mountings. Start up current must be at least 3.5 mA but once started, the Logix 1200e digital positioner operates with a signal as low as 2.8 mA. Below 2.8 mA, the operation and communication are suspended. 2. When lifting the system from the shipping container, position lifting straps to avoid damage to mounted accessories. Systems with valves up to six inches may be lifted by actuator lifting ring. On larger systems, lift unit using lifting straps or hooks through the yoke legs and outer end of body. WARNING: When lifting a valve/actuator assembly with lifting straps, be aware the center of gravity may be above the lifting point. Therefore, support must be given to prevent the valve/actuator from rotating. Failure to do so can cause serious injury to personnel or damage to nearby equipment. 3. In the event of shipping damage, contact the shipper immediately. 4. Should any problem arise, contact a Flowserve Flow Control Division representative. Since the positioner is insensitive to supply pressure changes and can handle supply pressures from 30 to 150 psig, a supply regulator is usually not required; however, in applications where the supply pressure is higher than the maximum actuator pressure rating a supply regulator is required to lower the pressure to the actuator’s maximum rating (not to be confused with operating range). An air filter is required for all applications due to the close clearances in the spool. NOTE: The air supply must conform to ISA Standard ISA 7.0.01 (a dew point at least 18 degrees Fahrenheit below ambient temperature, particle size below five microns – one micron recommended – and oil content not to exceed one part per million). Specifications Table III: Physical Specifications Table I: Electrical Specifications Power supply Two-wire, 4-20 mA 12.0 VDC Compliance voltage 12.0 VDC Effective resistance 625 Ω @ 20 mA Communications HART Protocol Minimum required start-up current 3.5 mA Minimum operating current 2.8 mA Maximum voltage 40.0 VDC Table II: SoftTools Suite Software Specifications Computer Minimum Pentium processor running Windows 95 or NT, 16-MB total memory (32-MB recommended), 20-MB available hard disk space, one CD-ROM drive HART Modem RS-232 Modem or PCMCIA card HART Filter May be required in conjunction with some DCSs HART MUX MTL 4840 system Flowserve Corpor tion V ltek Control Prod cts Tel USA 801 489 8611 Operating Temperature Range -40° F to +185° F (-40° C to +85° C) Housing Cast, powder-painted aluminum, stainless steel Weight 8.3 pounds (3.9 kg) aluminum 20.5 pounds (9.3 kg) stainless steel Table IV: Positioner Specifications Dead band <0.1% full scale Repeatability < 0.05% full scale Linearity < 0.5% (rotary), < 0.8% (sliding stem) full scale Air Consumption at < 0.3 SCFM (0.5 Nm3/hr)@60 psig (4 barg) Table V: Hazardous Area Certifications Explosion Proof FM/CSA Class 1, Div 1, Groups B, C, D CENELEC EExd IIB+H2 T5, IP-65 Non-incendive FM/CSA Class 1, Div 2, Groups A, B, C, D; CENELEC IIC Exn, T6,BS 6941, IP-65, T Intrinsically Safe FM/CSA Class 1, Div 1, Groups A, B, C, D; CENELEC EExib, T4 & T5, IP-65 44 3 . Digital Position Algorithm Collector Board Pressure Sensor Air-to-open Configuration Flame Arrestors Spool Valve Air Supply LED Display Exhaust OUTPUT 1 OUTPUT 2 Main PCB Tray Exhaust Ribbon Cable Flame Arrestor Flame Arrestor Filter Stem Position Sensor Regulator Hall Effect Sensor Electromagnetic Coil Nozzle Orifice Flapper Figure 1: Logix 1200e Digital Positioner Schematic Positioner Operation The Logix 1200e positioner is an electric feedback instrument. Figure 1 shows a Logix 1200e positioner installed on a double-acting actuator for air-to-open action. Positioning is based on a balance of two signals: one proportional to the command input signal and the other proportional to the valve stem position. The supply pressure for the positioner pressure modulator is tapped off the main supply. Next it passes through an internal pressure regulator that regulates it to approximately 22 psig. The air then passes through an orifice that restricts the flow and air consumption. The pressure modulator further controls the air to 6-10 psig, when operating current is applied, using a spring-diaphragm flapper that is attracted by an electromagnet to a nozzle. A temperature compensated hall effect sensor mounted on a circuit board senses the spool valve position. The hall effect sensor and circuitry create an inner feedback loop, which determines how much current to send to the electromagnet for a desired spool valve position. The electro-magnet in the feedback loop varies the nozzle-flapper spacing, which regulates the output pressure to 6-10 psig, proportional to the digital position algorithm. When the command and stem position signals are equal, the system will be in equilibrium and the valve stem will be in the position called for by the command signal. If these opposing signals are not equal, the spool valve will move up (or down) and, by means of 44 4 the pressure modulator, change output pressures and flow rate. This will cause the actuator piston to move until the signal of the position sensor equalizes with the command signal. Detailed Sequence of Positioner Operations The detailed sequence of positioner operations is as follows: An increase in the command signal causes the modulator pressure to increase, pushing the spool assembly upward from its equilibrium position. This opens the spool valve ports, supplying air to Output 1 and exhausting air from Output 2. This causes the actuator piston to move upward. The upward motion of the piston is transmitted back to the positioner through the stem position feedback linkage, changing proportionally to the valve stem position. The piston continues to stroke upward until the stem position signal of the sensor increases sufficiently to counter the signal being sent to the control algorithm. At this point, the spool is at its equilibrium position as the pressures in the cylinder stabilize and the air flow to the actuator decreases. The positioner will then make small null adjustments to fine-tune the desired position and compensate for changes in dynamic loading. A decrease in the command signal reverses the described actions, causing a proportional downward movement of the actuator piston and stem. Flowserve Corpor tion V ltek Control Prod cts Tel USA 801 489 8611 Logix 1000 Series Positioner Vented-design Conversion A standard Logix 1000 series positioner is vented directly to the atmosphere. When supply air is substituted with sweet natural gas, the following changes and considerations must be met. Piping must be used to route the exhausted natural gas to a safe environment. This piping system may cause some positioner back pressure in the main chamber (from modulator) and spool chambers (from actuator). This increase in pressure is due to restrictions caused by piping losses from the pipe and fittings Two chambers must be vented on the Logix 1000 series positioners: the main housing chamber and the spool valve chamber (Figures 1 and 2). The main chamber vent is located on the backside of the positioner (see Figure 1). There is a small, silver-colored cover (item 24, SKU 10097867), protecting the vent which must be removed and can be discarded. A fitting may now be threaded into the 1/8-inch NPT hole and tubing/piping attached. NOTE: On rotary products, the mounting bracket covers the main housing vent. An adequate size access hole must be drilled in the bracket at the time of assembly to allow access to the main housing vent. Maximum Allowable Housing Back Pressure 1 psi (0.07 bar) NPT x 1⁄4-inch Swagelok Tube Fitting 1⁄4-inch 1⁄4-inch FNTP x MNPT Reducer 1⁄8-inch Figure 3: Main Housing Vent The maximum allowable back pressure from the collection device on the main housing vent is 1.0 psi (0.07 bar). Vent flow rate is 244 standard in3/min. WARNING: The back pressure must never rise above 2.0 psi (0.14 bar). If this occurs the weather seal boot (SKU 130884), found on the early versions of the Logix 1000 positioner, identified by the diagonal window in the main cover, must be checked for proper sealing, as overpressure will move the seal out of place. (See Figure 4). Damage will not occur to the seal, only seal alignment will be affected. A typical sign of boot leakage is a dramatic deterioration of positioner performance. To correct the seal, remove the driver module and simply re-align back into its groove. If back pressure of 3.5 psi (0.24 bar) is reached, total valve control will be lost. Field Terminations HART Connection Terminals 4-20 mA Feedback Terminals (optional) Housing EARTH Terminal Seal Boot Shielded Cable Connect Shield at Source Ground 4-20 mA Current Source Figure 2: Field Termination Flowserve Corpor tion V ltek Control Prod cts Tel USA 801 489 8611 Figure 4: Seal on Modulator 44 5 will cause problems with overshoot but permanent damage will not occur until pressures exceed 20 psi (1.4 bar). Tubing Positioner to Actuator Maximum Allowable spool Back Pressure 8 psi (0.55 bar) 3 /8-inch NPT x 3/8-inch Swagelok Tube Fitting Proper tubing orientation is critical for the positioner to function correctly and have the proper failure mode. Refer to Figure 1 and note that for air-to-open valves, the Output 1 port of the positioner manifold is tubed to the bottom side of the actuator. The Output 2 port of the positioner manifold is tubed to the top side of the actuator. For air-to-close valves the above configuration is reversed. For single-acting actuators Output 1 port is always tubed to the actuator regardless of air action. Output 2 port must be plugged. WARNING: This product has electrical conduit connections in either thread sizes 0.5-inch NPT or M20 which appear identical but are not interchangeable. Forcing dissimilar threads together will damage equipment, cause personal injury and void hazardous location certifications. Conduit fittings must match equipment housing threads before installation. If threads do not match, obtain suitable adapters or contact a Flowserve office. Wiring and Grounding Guidelines Input Cable Shielding (Figure 2) Customer Connection 3/8-inch Tubing Figure 5: Spool Cover Vent The spool valve chamber has two parts: the spool valve cover, (item 9, SKU 130811) and spool valve shroud (item 10, SKU 130825). The spool valve cover is replaced by SKU 10134649 for early versions of the Logix 1000 positioner or SKU 10160335 for later versions (identified by the 1200e or the round window in the main cover). This new cover has a 3/8-inch NPT hole where tubing/piping must be attached. The spool valve shroud is discarded and not replaced with anything. The maximum allowable back pressure while stroking the valve is 8 psi (0.55 bar). Higher pressures 44 6 The input loop current signal to the Logix 1200e digital positioner should be in shielded cable. Shields must be tied to a ground at only one end of the cable to provide a place for environmental electrical noise to be removed from the cable. In general, shield wire should be connected at the source. Grounding Screw The green grounding screw, located inside the termination cap, should be used to provide the unit with an adequate and reliable earth ground reference. This ground should be tied to the same ground as the electrical conduit. Additionally, the electrical conduit should be earth grounded at both ends of its run. The green grounding screw must not be used to terminate signal shield wires. Flowserve Corpor tion V ltek Control Prod cts Tel USA 801 489 8611 Figure 6: Compliance Voltage Compliance Voltage (Figure 6) Cable Requirements Output compliance voltage refers to the voltage limit that can be provided by the current source. A current loop system consists of the current source, wiring resistance, barrier resistance (if present), and the Logix 1200e positioner impedance. The Logix 1200e digital positioner requires that the current loop system allows for a 12.0 VDC drop across the positioner at maximum loop current. The 12.0 VDC drop across the Logix 1200e positioner terminals is generated by the positioner from the 4-20 mA loop current input. The Logix 1200e digital positioner utilizes the HART Communication protocol. This communication signal is superimposed on the DC 4-20 mA current signal. The two frequencies used by the HART protocol are 1200e Hz and 2200 Hz. In order to prevent distortion of the HART communication, cable capacitance and cable length restrictions must be calculated. The cable length must be limited if the capacitance is too high. Selecting a cable with lower capacitance/foot rating will allow longer cable runs. In addition to the cable capacitance, the network resistance also affects the allowable cable length. CAUTION: Never connect a voltage source directly across the positioner terminals. This could cause permanent circuit board damage. In order to calculate the maximum network capacitance, use the following formula. Determine if the loop will support the Logix 1200e digital positioner by performing the following calculation. Voltage = Compliance Voltage (@Current ) - Current *(R +R ) MAX MAX barrier 65 C network ( µF ) ≤ -------------------------------------------------------------- – 0.0032 ( R barrier + R wire + 390 ) Example: R barrier = 300 Ω wire The calculated voltage must be greater than 12 VDC in order to support the Logix 1200e digital positioner. R = 50 Ω wire 22ρF 0.000022µF C cable = -------------- = -------------------------------foot foot Example: DCS Compliance Voltage = 19 V R barrier = 300 Ω 65 --------------------------------------- – 0.0032 = 0.08µF = C network ( µF ) ( Max ) 300 + 50 + 390 R = 25 Ω wire CURRENT MAX = 20 mA C network ( µF ) Max Cable Length = ---------------------------------C network Voltage = 19 V - 0.020 A*(300 Ω + 25 Ω) = 12.5 V The voltage 12.5 V is greater than the required 12.0 V; therefore, this system will support the Logix 1200e digital positioner. The Logix 1200e positioner has an input resistance equivalent to 625 Ω at a 20 mA input current. Flowserve Corpor tion V ltek Control Prod cts Tel USA 801 489 8611 0.08µF Max Cable Length = ----------------------------------------------0.000022µF ⁄ foot To control cable resistance, No. 24 AWG cable should be used for runs less than 5000 feet. For cable runs longer than 5000 feet, No. 20 AWG cable should be used. 44 7 Collector Board Pressure Modulator Connection Hall Sensor Connection O-ring Driver Module Assembly Minimum Pressure Set Screw (factory calibrated) Install orifice before driver module is in housing Position wires to the rear of Modulator Hall Sensor Connector Pressure Modulator Connector Figure 7: Driver Module Assembly Driver Module Assembly The driver module assembly moves the spool valve by means of differential pressures on its diaphragm. Air is routed to the module from the regulator through a hose that connects to the assembly through a hose barb with an integral orifice. Wires from the module connect the hall effect sensor and the pressure modulator coil to the collector board. Driver Module Assembly Replacement To replace the driver module assembly, refer to Figure 7, 8, 9, 11, 20 and proceed as outlined below. The following tools are required: Flat plate/bar about 1/8-inch thick Phillips screwdriver 1. Make sure valve is bypassed or in a safe condition. 2. Disconnect the power and air supply to the unit. 3. Remove the driver module cover (Figure 9), using flat bar/plate in slot. 44 8 4. Remove the spool valve cover by removing the screw and sliding the cover assembly backwards until the tab is clear of the slot. Removing the sheet metal cap, hydrophobic filter, or O-ring from this assembly is not necessary (Figure 11). 5. Being careful not to lose the nylon washer, remove the Phillips-head screw that attaches the driver module to the main housing (Figure 8). 6. Remove the spool valve block by removing the two Phillips-head screws and carefully sliding the block off the spool (Figure 8). CAUTION: The spool (extending from the driver assembly) is easily damaged. Use extreme caution when handling the spool and spool valve block. 7. Carefully remove spool by sliding end of spool out of connecting clip. Excessive force may bend spool. 8. Remove main cover. Flowserve Corpor tion V ltek Control Prod cts Tel USA 801 489 8611 Housing Spool Valve Block opening. This will allow the driver module to thread out without tangling or cutting the wires. 12. Grasp the driver module pressure modulator cap to rotate the entire driver module. Turn it counter clockwise to remove. After it is threaded out, carefully retract the driver module from the housing. 13. Take new driver module, and verify that the O-ring is in place. Lay the wires back and along modulator as shown in Figure 7, and hold in place by hand. Spool Spool Valve Screws Nylon Gaskets Driver to Housing Screws Figure 8: Spool and Block Orifice 14. Gently direct the driver module into the housing bore. Turn the driver module clockwise to thread it into the housing. Continue rotating the module until it bottoms out. 15. Once the threads are fully engaged, rotate the driver module counter clockwise until the flat on the driver module and the flat on the housing are aligned. This will align the screw holes for the next step. 16. Verify that nylon gasket is in the counter bore in the driver module retaining screw hole as shown in Figure 8. 17. Insert a driver-to-housing screw into the driver housing through the counter-bored hole in positioner main housing. Tighten with a phillips screwdriver. 18. Feed the driver module wires into the main chamber of the housing, and connect them to the collector board. 19. Verify that the three O-rings are in the counterbores on the machined platform where the spool valve block is to be placed (Figure 20). 20. Carefully slide the spool into the connecting clip of the driver module assembly. Driver Module Cover Figure 9: Driver Module Orifice 9. Remove the tubing from the orifice in the driver module assembly (Figure 9). 21. Carefully slide the block over the spool, using the machined surface of the housing base as a register (Figure 8). Slide the block toward the driver module until the two retaining holes line up with the threaded holes in the base. 22. Install two spool-valve screws and tighten securely with a Phillips screwdriver. 10. Remove the two wiring connections that link the driver module assembly to the collector board. 23. Slide the spool valve cover assembly over the spool valve until the tang engages into housing slot. Install spool valve cover screw and tighten securely. 11. Feed the wires back through the housing so they extend backward, out toward the driver module 24. Thread main cover and driver module cover into the main housing. Flowserve Corpor tion V ltek Control Prod cts Tel USA 801 489 8611 44 9 Spool Valve To replace the spool valve, refer to Figure 8, 10 & 11 and proceed as outlined below. 1. Make sure valve is bypassed or in a safe condition. 2. Disconnect the power and air supply to the unit. 3. Remove the spool valve cover by removing the screw and sliding the cover assembly backwards until the tab is clear of the slot. It is not necessary to remove the sheet metal cap, hydrophobic filter, or O-ring from this assembly (Figure 11). 4. Remove the spool valve block by removing the two phillips-head screws and carefully sliding the block off the spool (Figure 8). CAUTION: Spool (extending from driver assembly) is easily damaged. Use extreme caution when handling spool and spool valve block. 5. Grasp the bottom of the regulator and unscrew it from the interface plate. 6. Verify that the O-rings are in place on the base of the new regulator and thread it into the hole in interface plate. 7. Install four screws to fasten the collector board into the housing. Replace the four wire connections. 8. Attach the flexible tubing to the orifice. 9. Re-install all covers. O-ring Hydrophobic Filter 5. Carefully remove spool by sliding end of spool out of connecting clip. Excessive force may bend the spool. 6. Verify that the three O-rings are in the counterbores on the machined platform where the new spool valve block is to be placed (Figure 20). 7. Careful slide the spool into the connecting clip of the driver module assembly. 8. Carefully slide the block over the spool, using the machined surface of the housing base as a register (Figure 8). Slide the block toward the driver module until the two retaining holes line up with the threaded holes in the base. 9. Install two spool-valve screws and tighten securely with a phillips screwdriver. 10. Slide the spool valve cover assembly over the spool valve until the tang engages into housing slot. Install the spool valve cover screw and tighten securely. Regulator The regulator reduces the pressure of the incoming supply air to a level that the driver module can use. Replacing Regulator 1. Make sure valve is bypassed or in a safe condition. 2. Disconnect the power and air supply to the unit. 3. Remove the main cover. 4. Remove the four wire connections from the collector board. Next remove the four screws that fasten the collector board to the housing. 44 10 Spool Valve Cover Spool Valve Shroud Figure 10: Spool Valve Cover Assembly Spool Valve Cover The spool valve cover incorporates a coalescing filter element in a two-piece cover. This protects the spool valve chamber from moisture and provides a low back pressure vent for exhaust air from the spool valve. Replacing Filter in Spool Valve Cover 1. Make sure valve is bypassed or in a safe condition. 2. Disconnect the power and air supply to the unit. 3. Remove the spool cover by removing the screw and sliding the cover assembly backwards until the tab is clear of the slot. The sheet metal cover may be removed and cleaned with a brush or by blowing out with compressed air (Figure 11). 4. Remove the O-ring from around hydrophobic filter element and set aside (Figure 10). 5. Remove the molded filter element by pulling straight out of chamber cover vent piece. 6. Install O-ring into base of chamber cover vent piece as shown in Figure 10. Flowserve Corpor tion V ltek Control Prod cts Tel USA 801 489 8611 7. Place new molded filter element into the chamber cover vent piece. This element provides part of the track to secure the O-ring installed in the last step. 8. Place spool valve shroud onto spool valve cover. 9. Place the spool valve cover assembly in place by setting it on the ramp and sliding it until the tab seats in the slot (Figure 11) and secure with No. 8-32 screw. Main PCB Assembly The main PCB assembly contains the circuit board and processor that perform control functions of the positioner. The board is encapsulated in a tray with a protective silicon coating. This module can be easily replaced if necessary. None of the components inside the tray are serviceable. This module is to be replaced as a unit. Replacing Main PCB Assembly (Figure 12) 1. Make sure valve is bypassed or in a safe condition. 2. Disconnect the power and air supply to the unit. 3. Remove the main cover and disconnect the ribbon cable from the collector board. CAUTION: To avoid damaging any components, exercise caution by gently raising the locking tab to release the ribbon cable. 4. Remove the PCB assembly by removing the three No. 6-32 screws and lifting the tray out of housing. Spool Valve Cover 5. Place the new PCB assembly on the bosses inside the positioner housing. Screw Figure 11: Spool Valve Cover Assembly 6. Insert three No. 6-32 screws through the tray into the threaded bosses and tighten evenly, using a phillips screwdriver. Do not overtighten. 7. Reconnect the ribbon cable to the collector board Ribbon Cable Main PCB Assembly Screws (3) Figure 12: Main PCB Assembly Flowserve Corpor tion V ltek Control Prod cts Tel USA 801 489 8611 44 11 Collector Board The collector board assembly provides a central routing for all electronic connections in the positioner, linking the pressure modulator coil, hall effect sensor and field inputs to the main electronics. The collector board assembly also provides for mounting of the pressure sensors used in the advanced model. NOTE: The two screws through the stiffener plate are longer. 5. Tighten all four screws. 6. Connect the main ribbon from the electronics tray. 7. Reconnect wiring to the collector board. Field Terminations Removing Collector Board (Figure 20) 1. Make sure valve is bypassed or in a safe condition. 2. Disconnect the power and air supply to the unit. The customer interface board provides a connection point inside the explosion proof housing for all hookups to positioner. While the board is not likely to experience a failure, it can easily be replaced. 3. Remove the main cover and disconnect the wiring to the collector board. Each cable has its own unique connector to prevent mistakes in reconnecting. Replacing Customer Interface Board (Figure 2 & 20) 4. Remove the four No. 8-32 screws holding the collector board to the housing. 2. Disconnect the power and air supply to the unit. 5. Remove the collector board. 3. Remove the main cover and disconnect the customer interface cable from collector board. Replacing Collector Board 4. Remove the customer interface cover and the three No. 8-32 screws. NOTE: A Logix 120X (standard model) cannot be upgraded to a Logix 1210e (advanced model) by changing out the collector board. The Logix 120X and Logix 1210e use different positioner housings. 1. Advanced collector board only – Verify that pressures sensors are in place on back of collector board, and that the two O-rings are in place. 2. Set collector board assembly in place. 3. Advanced collector boards require a stiffener plate above the pressure sensors (Figure 20). 4. Insert four No. 8-32 screws through the collector board into the threaded holes of the housing. 44 12 1. Make sure valve is bypassed or in a safe condition. 5. Remove customer interface board, carefully pulling wiring through bore. 6. Verify that the O-ring is in place in the counter bore in the positioner housing. 7. Feed wiring through passageway into main chamber of housing. 8. Set the circuit board in place and secure with three No. 8-32 screws. 9. Connect customer interface cable to collector board. 10. Replace covers. Flowserve Corpor tion V ltek Control Prod cts Tel USA 801 489 8611 Stem Position Sensor The position feedback assembly transmits valve position information to the processor. This is accomplished by means of a rotary position sensor that connects to the valve stem through a feedback linkage. To provide for accurate tracking of the pin in the slot, the follower arm is biased against one side of the slot with a rotary spring. This spring also automatically moves the position feedback assembly to its limit in the unlikely event of failure of any component in the linkage. Housing Stem Position Sensor Sensor Cable 8. Route wires along the position sensor and reconnect to collector board. Mounting to Linear Mark One Valves (See Figure 14) The tools required for the following procedure are: 9/16-inch open-end wrench box wrench 3/8-inch open-end wrench 7/16-inch 1. Remove washer and nut first from follower pin assembly. Insert pin into the appropriate hole in follower arm, based on stroke length. The stroke lengths are stamped next to their corresponding holes in the follower arms. Make sure the unthreaded end of the pin is on the stamped side of the arm. Reinsert lock washer and tighten nut to complete follower arm assembly. 2. Slide the double-D slot in the follower arm assembly over the flats on the position feedback shaft in the back of the positioner. Make sure the arm is pointing toward the customer interface side of the positioner. Slide lock washer over the threads on the shaft and tighten down the nut. Bearing Stem Position Sensor Dot 3. Align the bracket with the three outer mounting holes on the positioner. Fasten with 1/4-inch bolts. Feedback Shaft Figure 13: Stem Position Sensor Orientation Stem Position Sensor Replacement (Figure 13, 20) 1. Make sure valve is bypassed or in a safe condition. 2. Disconnect the power and air supply to the unit. 3. Remove the main cover and disconnect rotary position sensor wires from collector board. 4. Remove the two screws from rotary position sensor and remove the sensor from the housing. 5. Turn position sensor shaft until the dot on the slot is oriented with the wires on the pot (Figure 13). 6. Insert the position sensor into the shaft with wires pointing toward the main PCB assembly. Turn the position sensor clockwise until bolting slots align with the housing screw holes and the wires on the sensor protrude over the main PCB assembly tray. 7. Carefully center position sensor on the shaft bore, insert and tighten the screws. Do not over tighten. Flowserve Corpor tion V ltek Control Prod cts Tel USA 801 489 8611 4. Screw mounting bolt into the hole on the yoke mounting pad nearest the cylinder. Stop when the bolt is approximately 3/16-inch from being flush with mounting pad. 5. Slip the large end of teardrop shaped mounting hole in the back of the positioner/bracket assembly over mounting bolt. Slide the small end of teardrop under mounting bolt and align the lower mounting holes. 6. Insert lower mounting bolt and tighten bolting. 7. Slide appropriate pin slot on the take-off arm, based on stroke length, over follower arm pin. The appropriate stroke lengths are stamped by each pin slot. 8. Position the take-off arm mounting slot against the stem clamp mounting pad. Apply Loctite 222 to take off arm bolting and insert through washers into stem clamp. Torque to 120 in-lbs. 9. Center the take-off arm on the rolling sleeve of the follower pin. 10. Align take-off arm with top plane of the stem clamp and tighten bolting. 44 13 Logix 1200 Positioner Bracket Bolts Bracket Locknut Washer Follower Arm Positioner Bolts Nut Nut Lock Washer Nut Follower Pin Stem Clamp Take-off Arm Bolts Metal Washers Figure 14: Linear Mark One Control Valve Mounting Standard Rotary Mounting Procedure (See Figure 15) The standard rotary mounting applies to valve/actuator assemblies that do not have mounted volume tanks or handwheels. The standard mounting uses a linkage directly coupled to the valve shaft. This linkage has been designed to allow for minimal misalignment between the positioner and the actuator. The tools required for the following procedure are: 5/32 allen wrench end wrench 7/16-inch end wrench 3/8-inch socket with extension 3/16 nutdriver 1/2-inch 1. Fasten spline lever adapter to splined lever using two No. 6 x 0.50-inch self tapping screws. 2. Slide take-off arm assembly onto spline lever adapter shaft. Insert screw with star washer through take-off arm and add second star washer and nut. Tighten nut with socket so arm is lightly snug on shaft but still able to rotate. This will be tightened after linkage is correctly oriented. 44 14 3. Attach follower arm to positioner feedback shaft using the star washer and No. 10-32 nut. NOTE: Arm will point up when feedback shaft is in the free position. 4. Using four 0.25-20 x 0.50 L. bolts, fasten positioner to universal bracket using appropriate hole pattern (stamped on bracket). 5. Using a 1/2-inch end wrench and two 0.3125-18 x 0.50 L. bolts, attach bracket to actuator transfer case pad. Leave these bolts slightly loose until final adjustments are made. 6. Rotate take-off arm so the follower pin will slide into its slot. Adjust bracket position noting the engagement of the follower pin and the take-off arm slot. The pin should extend approximately 1/16-inch past take-off arm. When properly adjusted, securely tighten the bracketing bolts. Orienting the Take-off Arm for Final Lock Down Tube positioner to valve in the following manner: 1. OUTPUT 1 port of the manifold to the bottom side of the Actuator. Flowserve Corpor tion V ltek Control Prod cts Tel USA 801 489 8611 Positioner Bolts 1/4-20 (4)* Bracket Bolts 5/16-18 (2) (not shown) Take off Arm, Rotary Lock Washer (2) Bolt No.10-32 Nut No.10-32 Logix 1200 Digital Positioner Self Tapping Screws (2) Spline Lever Adapter Nut No.10-32 Lock Washer Follower Arm * Located in appropriate hole pattern as indicated on bracket. (25, 50, 100/200) Figure 15: Standard Rotary Mounting 2. OUTPUT 2 port of the manifold to the topside of the actuator. 3. With supply pressure off, rotate the follower arm in the same direction the shaft would rotate upon a loss of supply pressure. When the mechanical stop of the follower arm (positioner) is reached, rotate back approximately 15 degrees. 4. Hold the take-off arm in place; tighten the screw of the take-off arm. NOTE: The take-off arm should be snug enough to hold the follower arm in place but allow movement when pushed. 8. Press the Quick-Cal button for 5 to 10 seconds or until positioner begins to move. The positioner will now perform a stroke calibration. 9. If the calibration was successful the green LED will blink and the valve will be in control mode. Continue with step 10. If calibration failed the A/D feedback values were exceeded and the arm must be adjusted away from the positioners limits. Return to step 3 and back off approximately 10 degrees. NOTE: Remember to remove the air supply before re-adjusting take-off-arm. 10. Tighten the nut on the take-off arm. The socket head screw of the take-off arm must be tight, about 40 in-lbs. 5. Connect regulated air supply to appropriate port in manifold. NOTE: If the take-off arm slips, the positioner must be re-calibrated. 6. Remove main cover and locate DIP switches and Quick-Cal button WARNING: Failure to follow this procedure will result in positioner and/or linkage damage. Check air-action and stroke carefully before lockdown of take-off arm to spline lever adapter. 7. Refer to sticker on main board tray and set DIP switches accordingly Flowserve Corpor tion V ltek Control Prod cts Tel USA 801 489 8611 44 15 Tripper Tripper Clamp Bracket Bolts 5/16-18 (2) Ball Joint Ends Follower Arm Bolts (2) Rotate Positioner 90° Locknuts (2) *Tie Rod Mounting Bolts 1 /4-20 (4) Nut No. 10-32 Lock Washer * Tie Rod must be cut to desired length Figure 16: Optional Rotary Mounting Optional Rotary Mounting Procedure The optional rotary mounting applies to valve/actuator assemblies that are equipped with mounted volume tanks or handwheels. The optional mounting uses a four-bar linkage coupled to the valve shaft. The following tools are required: 3/8-inch box wrench 7/16-inch 1/2-inch box wrench box wrench 1. Using a 1/2-inch box end wrench and two 0.3125-18 x 0.50 L. bolts, attach bracket to actuator transfer case pads. Leave bracket loose to allow for adjustment. 2. Using four 0.25-20 x 0.50 L. bolts and a 7/16-inch box wrench, fasten positioner to universal bracket, using the four-hole pattern that locates the positioner the farthest from the valve. Rotate positioner 44 16 90 degrees from normal so gauges are facing upward. 3. Attach follower arm to positioner feedback shaft, using the star washer and No. 10-32 nut. 4. Attach tripper and tripper clamp to shaft, using two 0.25-20 L. bolts and two 0.25-20 locknuts. Leave tripper loose on shaft until final adjustment. 5. Thread ball joint linkage end to tripper and tighten (Thread locking compound such as Loctite is recommended to prevent back threading). Adjust length of tie rod so follower arm and tripper rotate parallel to each other (the rod must be cut to the desired length). Connect other ball joint end to follower arm using a star washer and a No. 10-32 nut. 6. Tighten bracket and tripper bolting. 7. Check for proper operation, note direction of rotation. Flowserve Corpor tion V ltek Control Prod cts Tel USA 801 489 8611 WARNING: If rotating in wrong direction, serious damage will occur to the positioner and/or linkage. Check air action and stroke direction carefully. LED Indicators The Logix 1200e has three LED indicators that are visible through a window in the main cover. Only one LED will blink at any given time. Each LED has a different color to convey basic information about the positioner status. Green indicates that the positioner is operating normally. Yellow indicates that a ‘customer defined limit’ or ‘alert’ has been reached. Red indicates that an error condition exists. The HART hand held communicator, ValTalk or SoftTools PC software must be used to determine the specific reason for a yellow or red LED status. During stroke and actuator calibration, no LED will blink. After calibration is complete, the green LED indicates that the calibration was completed successfully. If the yellow or red LED blinks after a calibration process, a warning or error was detected and the HART communication to the device must be used to identify the specific calibration error. NOTE: If the LED indicator changes from green to yellow after a calibration process, the user may have set a warning limit (position alert, cycle counter alert, etc.). Use HART communications to monitor status. Stroke Calibration using the Quick-Cal Button For cases when the HART hand held communicator, ValTalk or SoftTools PC software is not available, the Logix 1200e has a Quick-Cal feature that performs a stroke calibration and allows basic operation of the positioner. The Quick-Cal routine applies full supply pressure to the upper and lower mechanical limits to determine the valve stroke. Valve systems without mechanical stops must use the ValTalk or SoftTools software to manually calibrate the valve. WARNING: The calibration routines are only to be used on systems which have mechanical stops. The calibration routines apply full supply pressure to determine stroke length and may cause damage to the valve, actuator or positioner. NOTE: The Quick-Cal operation retains all previously configured information except for the three DIP switch settings and stroke parameters. The settings of ATO/ATC, Linear/Rotary, Linear/Custom and stroke parameters are overridden and rest to the DIP switch settings when the Quick-Cal button is used. If the device is being installed for the first time, factory default parameters are used. The Quick-Cal button and DIP switch settings are located on the collector board inside the main housing chamber as shown in Figure 17. Flowserve Corpor tion V ltek Control Prod cts Tel USA 801 489 8611 Quick-Cal DIP Switch Quick-Cal Button Figure 17: Quick-Cal Button WARNING: Accessing this function requires removal of the main cover. The user must take all precautions if this operation is performed in explosion-proof areas. Make the appropriate configuration settings, using the DIP switches on the collector board. ATO/ATC selects air-to-open or air-to-close (this is determined by the mechanical tubing of the actuator). The LIN_VALV/ROT_VALV button allows the user to select linear or rotary feedback linkage. The LIN_VALV switch enables the feedback potentiometer to utilize the entire resolution through a maximum of 60 degrees rotation (45 degrees is typical). The ROT_VALV switch increases the rotation of the potentiometer up to 105 degrees (90 degrees is typical). Thus a long stroke sliding stem valve may require this dip switch to be set on ROT_VALV if the stroke rotates the feedback potentiometer more than 60 degrees. The LIN/CUSTOM option allows selection of linear or custom control characterization. If Custom is selected, the positioner activates custom characterization. If the device is being installed for the first time, the default custom characterization is equal percent. However, if a custom curve has been previously loaded, the previous curve will be used. The DIP switch settings are only read after the Quick-Cal button is pressed for 5 seconds; otherwise, the settings do not have any effect. The DIP switch settings will override any previous configuration done using HART communications. Press the Quick-Cal button for five to ten seconds. If the button is released before five seconds have elapsed, no action will be taken. After approximately five seconds, the positioner will begin a 44 17 stroke calibration. Release the Quick-Cal button once calibration has started. The positioner will automatically stroke the valve. The stroke sequence will be to the extremes (open to close), to the mid stroke, then to the signal position. No LED will blink during this process. Rotate Stem Position Sensor slowly NOTE: If Quick-Cal is interrupted during calibration the mode of the positioner may stay in digital, requiring HART communications to place it back into analog. If calibration was successful, upon completion the green LED will blink and the valve will be in control mode. If the yellow LED blinks immediately after a stroke calibration, this usually indicates that the valve did not stroke. Check the air supply and cable connections. If a calibration error occurred, the red LED will blink. The cause of a red LED is generally a stem position linkage/feedback sensor alignment problem. For linear linkage, the active electrical feedback angle is 65 degrees. For rotary linkage, the active electrical feedback angle is 95 degrees. The red LED indicates that the mechanical travel is not centered within the electrical sensor travel. If a red LED is blinking after a stroke calibration, loosen the feedback sensor mounting screws as shown in Figure 18. Turn the stem position sensor slowly while watching the LED indicators. Try small movements, both clockwise and counterclockwise. If the yellow LED begins to blink, the feedback sensor has been correctly moved into range. Tighten the feedback sensor mounting screws and repeat the Quick-Cal procedure. If the LED remains red even after moving the full length of the sensor slot, verify the following items are correctly set: LIN_VALV/ROT_VALV DIP switch setting, stem clamp and take-off arm height. NOTE: If the stroke calibration stops in the closed position, the error occurred when the position sensor/linkage was at closed position. If the stroke calibration stops in the open position, the error occurred when position sensor/linkage was at the open position. No calibration parameters are saved if an error occurs. If the power to the positioner is removed, the unit will power-up with the previous configuration parameters. A successful calibration will save parameters. If the valve does not stroke after pressing the QuickCal button, this may be an indication that the internal regulator pressure and/or the driver module minimum pressure is low. Refer to the following instructions to check and set the internal regulator and minimum pressure settings. NOTE: Ensure that all linkages are tight and correctly mounted before attempting to calibrate. Loose or incorrectly mounted linkage will cause calibration failure and difficulty in troubleshooting. 44 18 Stem Position Sensor Mounting Screws (2) Figure 18: Stem Position Sensor Adjustment Checking or Setting Internal Regulator Pressure The tools and equipment used in the next procedure are from indicated vendors. 1. Make sure valve is bypassed or in a safe condition. 2. Disconnect the air supply from the positioner. 3. Remove the main cover and the 1/16 inch flexible tubing from the driver module orifice. 4. Obtain a barbed tee (Pneumadyne part No. SBF16T or equivalent) and two pieces of 1/16 inch flexible tubing, a few inches in length each. 5. Connect the 1/16 inch flexible tubing, found in the positioner, to the barbed tee. Using one of the new flexible tubing pieces connect the barbed tee to the orifice. Connect the remaining tee port to a 0 to 30 psi pressure gauge. 6. Reconnect the air supply to the positioner and read the internal regulator pressure on the 0 to 30 gauge. The internal pressure should be set to 21.5 ±0.5 psi. If adjustment in needed, scrape off the silicon compound covering the screw. Then adjust the regulator pressure by turning the setscrew on top of the regulator with a small screwdriver. 7. Once the regulator pressure is set, remove the air supply to the positioner, remove the barbed tee, and reconnect the positioner's flexible tubing to the orifice. 8. Reconnect air supply to positioner. Flowserve Corpor tion V ltek Control Prod cts Tel USA 801 489 8611 No. 10-32 Extension (Clippard Part No. 15010) Minimum Pressure Test Port 5. Remove the No. 10-32 x 0.016 orifice and gasket (Figure 9) from the driver module using a 1/2-inch nut driver. Take care to not misplace the gasket. 6. Screw in the 10-32 extension followed by the 10-32 x swivel elbow. 7. Direct the swivel elbow so the minimum pressure test port is accessible. 1 No.10-32 x /16 Barb 8. Screw a No. 10-32 x 1/16-inch barb fitting into the test port, and screw the No. 10-32 x 0.016 orifice into the end of the elbow as shown. 9. Connect the tubing from the internal regulator output port to the orifice. 10. Using some 1/16-inch flexible tubing, connect a 0 to 30 psi gauge to the minimum pressure set port. No.10-32 x .016 Orifice Pressure from Internal Regulator to be tubed to this orifice No.10-32 x Swivel TEE (Pneumadyne Part No. SFL-10) Figure 19: Driver Module Minimum Pressure Check Checking or Setting the Driver Module Minimum Pressure 11. Once the gauge is connected, reapply the positioner air supply. The minimum pressure should now be registering on the gauge and must be 3.8 to 4.2 psi. If the minimum pressure is not correct, take a 9/64 allen wrench and turn the minimum pressure set screw located at the bottom of the driver module (Figure 7) until the pressure is in the range indicated. Cycle the positioner air supply several times and recheck the minimum pressure and re-adjust, if necessary, to ensure that the pressure has settled within the range specified. 12. When the pressure is set, remove the air supply. Refer to Figure 19, proceed as follows: 1. Make sure valve is bypassed or in a safe condition. 2. Disconnect power from the positioner. 3. Remove the main cover and remove the 1/16 flexible tubing from the orifice. 4. Obtain a No. 10-32 x swivel elbow (Pneumadyne part No. SFL-10 or equivalent) and a No. 10-32 extension (Clippard part No. 15010 or equivalent). Flowserve Corpor tion V ltek Control Prod cts Tel USA 801 489 8611 13. Remove the No. 10-32 x 1/16 barb and orifice from the swivel elbow and then remove swivel elbow and extension. 14. Replace the orifice and gasket as shown in Figure 9 and reconnect the 1/16 inch flexible tubing from the internal regulator output port to the orifice. Reconnect the positioner air supply and power. The positioner should now be ready to calibrate. 44 19 PROTOCOL Selection HART 1 ns ec tio nn ial ec Sp tio n Op Co Ac uit nd Co ial os rtif ic De ation sig s Sh n Ve aft rsi on Ce ter Ma gn Dia Pr oto co l tic s tio ns LOGIX 1200 Model Numbers e Code *2 DIAGNOSTICS Selection Standard Advanced Code *0 1 MATERIAL Selection Aluminum, Valtek (White Paint) Stainless Steel, Valtek (No Paint) Aluminum, Automax (Black Paint) Aluminum, Automax (Food Grade White Paint) Aluminum, Accord (Black Paint) Aluminum, Automax (Food Grade White Paint) CERTIFICATIONS Selection Explosion proof EEx d IIB + H2 (CENELEC SCS) Nonincendive Class I, Div. 2, (Factory Mutual), Class I, Div. 2 (CSA) Explosion proof Class I, Div. 1, Groups B,C,D Intrinsically Safe Class I, Div. 1, Groups A thru G (FM, CSA) FM Nonincendive. CSA Class I, Div. 2 Class I, Zone 1, Group IIB + H2 and Exia Class 1, Zone 0, Group IIC (CSA ONLY) Intrinsically Safe EEx ib, Nonincendive EEx n (CENELEC SCS) General Purpose SHAFT Selection DD Shaft NAMUR CONDUIT CONNECTIONS Selection 1/2” NPT M20 ACTION Selection 4 way 3 way 4 way Vented 3 way Vented SPECIAL OPTIONS Selection No Specials 4-20 mA Position Feedback Note: 44 20 *Product Default Value Code *0 1 2 3 4 5 Code 07 08 10 13 14 Code *Blank N Code *Blank M Code *Blank 3 V W Code *Blank F 1 = Logix Product Line Flowserve Corpor tion V ltek Control Prod cts Tel USA 801 489 8611 Item No. 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. 15. 16. 17. 18. 19. 20. 21. 22. 23. 24. 25. 26. 27. Part Housing Logix 1200 Positioner Main Housing Cover O-ring, Main Housing Cover LED Display Window O-ring, Window 2 Washer, Seal ring Retaining Ring Screw, Anti-Rotation Spool Valve Cover Spool Valve Shroud Hydrophobic Filter, Spool Valve Chamber O-ring, Spool Valve Cover 8 Screw, Spool Valve Cover Driver Module Cover 13 O-ring, Driver Module Cover 10 Regulator, 5 to 30 psi (Includes O-ring) Internal Filter O-ring, interface plate to housing seal Screw, interface plate to housing (4) Interface Plate Orifice, Barbed Fitting Flexible Tubing Hex Barbed Fitting W/Captive O-ring Main vent cover Screw, Main vent Cover Customer Interface Cover 44 O-ring, Customer Interface Cover 29 28. 29. 30. 31. 32. 33. 34. 35. 36. Screw, Anti-Rotation Pressure Gauge, 0-160 psi (2) Customer Interface Board Screw, Customer Interface Bboard (3) O-ring, Customer Interface Board Grounding Screw (2) Main PCB Assembly Screw, Main PCB Assembly (3) Collector Board Assembly (Standard / Advanced Model) 37. O-ring, Sensor to Housing (2) 38. Collector Board Stiffener (Advanced only) 39. Screw, Pressure Sencors to Housing (2 Advanced only) 5 16 6 9 7 3 19 21 4 11 12 39 18 36 38 17 40 20 43 41 44 42 37 35 48 47 49 34 51 57 27 50 46 26 31 32 52 1 53 54 30 33 55 28 25 56 22 45 24 23 15 14 *Aluminum or Stainless Steel 40. Screw, Collector Board to Housing (4 Standard - 2 Advanced) 41. Spool Valve Block 42. Spool Valve 43. Screw, Spool Valve to Housing (2) 44. O-ring, Spool Valve (3) 45. Driver Module Assembly 46. Nylon Washer (1) 47. Screw, Driver to Housing (1) 48. Stem Position Sensor 49. Screw, Potentiometer to Housing (2) 50. Metal washers (2) 51. Screw, Spring to Feedback Shaft 52. Feedback Shaft 53. O-ring, Feedback Shaft 54. Bearing 55. Torsion Spring 56. E-ring 57. Air Screens Figure 20: Exploded View Flowserve Corpor tion V ltek Control Prod cts Tel USA 801 489 8611 44 21 Available Spare Part Kits for Logix 1200e digital postioner Kit 1 – Driver Module Assembly SKU 10130943 Item No. 45 47 46 23 16 Kit 5 – Advanced Collector Board Assembly SKU 10130946 Description Driver module Screw, driver to housing Nylon washer Orifice barbed fitting and gasket Regulator and captive O-ring(s) Quantity 1 1 1 1 1 Item No. 36 37 38 39 40 Description Spool valve Block Spool valve Screw, spool valve to housing O-ring, spool valve Item No. 30 31 32 33 Quantity 1 1 2 3 Description Customer interface board Screw, customer interface board O-ring, customer interface board Grounding screw Quantity 1 3 1 1 Kit 7 – Main PCB Assembly SKU 10130948 Kit 3 – Soft Goods Kit SKU 10130944 Item No. 3 15 27 32 37 44 53 5 18 12 17 Quantity 1 2 1 2 2 Kit 6 – Customer Interface Assembly SKU 10130947 Kit 2 – Spool Valve Kit SKU 10130950 Item No. 41 42 43 44 Description Collector board O-ring, sensor to housing Collector board stiffener Screw, pressure sensors to housing Screw, collector board to standoffs Description O-ring, main housing cover O-ring, driver module cover O-ring, customer interface cover O-ring, customer interface board O-ring, pressure sensor to housing O-ring, spool valve O-ring, feedback shaft O-ring, main cover window O-ring, interface plate O-ring, spool valve cover Internal filter Item No. Description 34 Main PCB assembly 35 Screw, main PCB assembly Quantity 1 1 1 1 2 3 1 1 1 1 1 Kit 8 – Regulator SKU 10070875 Item No. Description 6 Regulator and captive O-ring(s) Quantity 1 Kit 9 – Stem Position Sensor SKU 10061643 Item No. Description 48 Stem position sensor Kit 4 – Standard Collector Board Assembly SKU 10130945 Item No. Description 36 Collector board 40 Screw, collector board Quantity 1 3 Quantity 1 HART Filter SKU 10079944 Quantity 1 4 4-20 mA Position Feedback Kit SKU 10125599 Table VI: Valtek Linear Mounting Kits 50 Square-inch* 25 Square-inch Spud Standard Handwheel Standard Handwheel 2.00 10067289 10067368 10091897 10067368 10067316 10067384 100-200 Square-inch Standard Handwheel 10067329† 10067384 2.88 10067329 10067386 3.38 10067351 10067389 4.75 10067351 10067389 2.62 * A 50 square-inch, 2.00 spud with live loading requires kit number 10067301. † Live loading is not available on a 100 square-inch, 2.62 spud. 44 22 Flowserve Corpor tion V ltek Control Prod cts Tel USA 801 489 8611 Table VII: Valtork Rotary Mounting Kits* 25 Square-inch 50 Square-inch 100-200 Square-inch Shaft Diameter Standard Optional Standard Optional Optional 0.44 10067418 10067527 1006790 0.63 10067418 10067565 1006790 10067573 10067502 0.75 10067418 10067569 10067490 10067574 10067502 0.88 10067418 10067572 10067490 10067575 10067502 1.12 10067418 10067490 10067580 10067502 10067616 1.50 10067418 10067490 10067502 10067617 1.75 10067418 10067490 10067502 10067618 Standard 10067502 10067615 * Standard: All Rotary Valves with Standard Accessories (End of Shaft Mount) Optional: All Rotary Valves with Handwheels or Volume Tanks (Linkage Design) Table VIII: Logix Mounting Kits Model Size Table VIII: Logix Mounting Kits (Continued) Mounting Kit 50 60 1250 L – M5-.8 Metric Bolting 10124070 0.5 – 1.5-in. stroke 10124085 2-in. stroke 10124070 0.5 – 1.5-in. stroke 10124085 2-in. stroke Notes Example: NK313A Kits designed for the following O.E.M.'s Air-torque AT Series AT0 — AT6 SNA Series SNA3 — SNA2000 N Series N250. 300 225 R Series R2 — R5 450 RPC Series RP — TPC11000 70 10124086 80 10124087 4-in. stroke 1052 33 657-8 40 Bettis 10124203 Rotary 10126736 EL-O-Matic Neles RC 10124060 RD 10131247 Foxboro Slid-Std 10131247 10119289 R314 10094495 10406329 E25 — E350 P Series P35 — P4000 XL Series XL45 — XL4580 Unitorq M Series Worcester 39 Series 2539 — 4239 VST-VA3R 17-in. dia. 10126736 M20 — M2958 0.75 – 1.5-in. Std HD 9 11 37 NAMUR Mounting Kits Prefix NK – NAMUR Accessory Mounting Kit Bracket Option 28 – 20mm Pinion x 80mm Bolt Spacing 38 – 38mm Pinion x 80mm Bolt Spacing 313 – 30mm Pinion x 80mm Bolt Spacing 12-in. dia. 10126736 Masoneilan (Linear Actuators) Automax SNA115 G2009-M11 — G3020-M11 E Series Hytork VSL-VA1D Valtek Trooper G Series Honeywell 10126255 Linear Automax 10125818 675 Automax Mounting Kit B – 10-32 UNF Bolting 10100780 40 657 & 667 Size A – 10-24 UNC Bolting 30 34 Model Bolt Option Fisher 38 10124594 13 10124593 18 10125747 24 10126826 11 10125402 13 10125401 15 10140783 18 10125747* 24 10126826 513 – 50mm Pinion x 130mm Bolt Spacing Flowserve Corpor tion V ltek Control Prod cts Tel USA 801 489 8611 44 23 Table VIII: Logix Mounting Kits (Continued) Model Size Mounting Kit Masoneilan (Linear Actuators, cont.) 25 10125644 50 10125645 100 10125646 6 10124595 16 10126752 47 B 10125702 48 B 10125702 “D” Domotor 200 71 Domotor vided between the supplies powering the Logix unit and the analog output board. • Available for explosion-proof and safe applications (CSA, FM). Specifications Potentiometer Range of Rotation 40° to 95° Power Supply Range 12.5 to 40 VDC (24V DC typical) 10127467 Maximum Load Resistance (ohms) (Supply Voltage - 12.5) / 0.02 71-2057AB-D 10129359 Current Signal Output 4-20 mA 71-40413BD 10129461 Linearity 88 Masoneilan (Rotary Actuators) 33 B 10125542 4 35 6 10125542 7 70 10 10125542 1.0% F.S. Repeatability 0.25% F.S. Hysteresis 1.0% FS Operating Temperature -40° to 185° F (-40° to 85° C) Ambient Temperature For a 100° F (38° C) change in ambient temperature, maximum zero shift is 0.4% FS, maximum span shift is 0.7% FS Power Supply Effects Out put signal change is less than 0.05% FS when supply voltage is varied between 12.5 and 40 VDC Vanguard 37/64 10127426 * Adjustable Mounting kit 10126736 may be needed if handwheels are used. 4 to 20 mA Analog Output Retrofit General Information The Logix 1200e digital positioner/controller can be retrofitted to provide an analog feedback signal of the stem position. This position feedback option has the following features and specifications: • Does not interfere with positioner operation. + – + – • Zero and span adjustments of the feedback signal are independent of the positioner and can be adjusted manually. • Output follows actual position of valve, including all failure modes of positioner except loss of power. An output of 3.15 mA is transmitted with loss of power to the analog output board. Position Feedback Current Loop (Logix Output) R Load – 12.5 to 40 VDC Power Supply + • Immune to RFI/EMI disturbances. • Can be retrofitted in the field. CAUTION: Because the analog output board shares common signals with the Logix internal circuitry, the two units cannot be powered by the same external power supply or by power supplies that share a common reference.Galvanic isolation of at least 50 VDC must be pro- 44 24 Positioner Command Current Loop (Logix Input) – 4 to 20 mA Current Source + CAUTION: Isolated power sources required. Figure 21: Analog Output Board Power Flowserve Corpor tion V ltek Control Prod cts Tel USA 801 489 8611 Span Adjustment Zero Adjustment DIR/REV Switch Potentiometer Connections Terminal Board Connection Control Board Connection Figure 22: 4-20 mA Analog Output Board Calibration To calibrate the Logix 1200e or 1200e digital positioner equipped with analog output, follow the procedure outlined below: 1. Wire the position transmitter in series with a 12.5 to 40 VDC power supply and a milliamp meter. CAUTION: Do not apply a voltage greater than 40 volts to transmitter terminals or the circuit will be damaged. 2. Be certain the direct/reverse switch is set to provide the desired output signal action. In the DIR position, a counterclockwise rotation of the potentiometer shaft (when looking at the label side of the potentiometer) will cause the output signal to increase. In the REV position, a clockwise stem rotation causes the signal to increase. Perform a stroke calibration whenever the direct/reverse switch is changed. WARNING: Keep hands, hair, clothing, etc. away from moving parts when operating the valve. Failure to do so can cause serious injury. 3. Stroke the valve to the close position. 4. Referring to Figure 22, adjust the zero adjusting screw with a small, flathead screwdriver until the meter reads 4 mA DC. 5. Stroke the valve to the open position. 6. Adjust the span adjusting screw until the meter reads 20 mA DC. Flowserve Corpor tion V ltek Control Prod cts Tel USA 801 489 8611 7. Stroke the valve to the closed position and recheck the meter for 4 mA DC. Some fine tuning of the calibration may be required. Repeat steps 3 through 7 until satisfied. Retrofitting to a Logix 1200e Digital Positioner (with Circular Window in the Main Cover) As shown in Figure 23, the newer model of the Logix digital positioner has a circular window in the main cover (as opposed to a diagonal, oblong window in the earlier model). To retrofit Logix digital positioner to 420 mA analog output, use the following procedure: 1. Remove the main cover (Figure 29). 2. Remove the lower and middle screws holding the control board in place; discard these screws. 3. Place the analog output board on the lower portion of the control board and secure with the two longer screws (6 x 32 1.25-in.) provided (Figure 33). 4. Unplug the orange/red/brown or brown/red/orange three-wire-set from the collector board. 5. Plug the orange/red/brown or brown/red/orange three-wire-set into the correct receiver in the analog output board (Figure 26). 6. Plug the three-wire set from the analog output board into the receiver on the collector board (that previously had held the orange/red/brown or brown/red/orange wire-set). 44 25 7. Connect the blue/yellow two-wire-set from the user interface board to the remaining receiver on the analog output board (Figure 27). NOTE: On some boards both set of wires are red/black but have different connectors - only one set will be able to be plugged into the analog output board. 8. Replace the main cover. Retrofitting to a Logix Digital Positioner (with Diagonal Window in the Main Cover) As shown in Figure 28, the earlier model of the Logix digital positioner has an oblong, diagonal window (as opposed to a circular window in the newer model). To retrofit an existing Logix digital positioner to 4-20 mA analog output, use the following procedure: 1. Remove the main cover and the user interface cover from the Logix unit (Figure 29). 2. Disconnect the ribbon cable that connects the control board from the collector board. 3. Remove the three screws holding the control board in place. Discard two of the screws. 4. Remove the control board from the Logix unit (Figure 30). 5. Disconnect the cable that goes from the user interface board to the collector board. 9. Feed the user interface two-wire-sets in the housing, placing the wires in the trough at the bottom of the housing. Connect the red/black two-wire-set to the collector board where the old user interface wire-set was connected. Pull the new blue/yellow feedback two-wire-set so that it is next to the red/black two-wire-set on the collector board. NOTE: With some boards both sets of wires are red/black but have different connectors. The feedback wire-set will be connected later to the analog output board. 10. Carefully replace the control board, ensuring that the clear pressure hose found inside the Logix unit is not pinched. 11. Place the analog output board on the lower portion of the control board and secure with the two longer screws provided. Secure the top of the control board with the original shorter screw (Figure 33). 12. Connect the control board ribbon cable to the collector board. 13. Unplug the orange/red/brown or brown/red/orange wire set from the collector board. 14. Plug the orange/red/brown or brown/red/orange wire set into the correct receiver in the analog output board. 15. Plug the three-wire-set from the analog output board into the receiver on the collector board that previously held the orange / red / brown or brown / red / orange three-wire-set. 7. Install the new user interface board with its two connectors inserted into the cavity of the housing. Make sure the O-ring is between the user interface board and the housing (Figure 32). 16. Connect the blue/yellow two-wire-set from the user interface board to the remaining receiver on the analog output board. NOTE: With some boards, both two-wire-sets are red/black but have different connectors - only one set will be able to be plugged into the analog output board. Complete the installation by placing the Quick-Cal sticker on the control board can and the user interface sticker in the user interface cover (Figures 14 and 15). 8. Install the three screws to secure the user interface into the housing. Tighten to hand-tight. 17. Replace the main cover and the user interface cover. 6. Remove the three screws holding the user interface board in place. Save these screws as well as the O-ring that goes between the user interface board and the housing (Figure 31). 44 26 Flowserve Corpor tion V ltek Control Prod cts Tel USA 801 489 8611 Figure 23: Logix 1200e Positioner with Circular Window Design Figure 26: Installation of Three-wire-set to Analog Output Board Figure 24: Logix Positioner with Cover Removed Figure 27: Completed Installation of Analog Output Board Figure 25: Installation of Analog Output Board Flowserve Corpor tion V ltek Control Prod cts Tel USA 801 489 8611 44 27 Figure 28: Logix Positioner with Diagonal Window Design Figure 31: Removal of Old User Interface Board Figure 29: Logix Positioner with Cover Removed Figure 32: Installation of New User Interface Board Figure 30: Removal of Control Board Figure 33: Installation of Analog Output 44 28 Flowserve Corpor tion V ltek Control Prod cts Tel USA 801 489 8611 Figure 34: Sticker Application Flowserve Corpor tion V ltek Control Prod cts Tel USA 801 489 8611 Figure 35: Completed Installation of Analog Output Board and User Interface Board 44 29 Troubleshooting Introduction With the analog source, the 4-20 mA signal is converted to a percentage. During loop calibration, the signals corresponding to 0 percent and 100 percent are defined. This guide is designed to assist the user in troubleshooting the Logix™ 1200e digital positioner. The Logix 1200e positioner is a two-wire, HART communication-based device, and is used in conjunction with ValTalk™ and SoftTools™ software or the HART 275 handheld communicator. As part of this troubleshooting guide, a number of recommendations are provided, which should improve operation and allow for accurate configuration. At this point, the command value is passed through a characterization/limits modifier block. The positioner no longer uses cams or other mechanical means to characterize the output of the positioner. This function is performed by the software, which allows for user adjustment in the field. The positioner has two basic modes: Linear and Custom characterization. In the Linear mode, the command signal is passed straight through to the control algorithm in a 1:1 transfer. If Custom characterization is enabled, the command source is mapped to a new output curve through a 21-point, user-defined curve. In addition, two user-defined features, Soft Limits and MPC (Minimum Position Cutoff), may affect the final command signal. The actual command being used to position the stem is called Control Command. The Control Command is the actual positioning command after any characterization or user limits have been evaluated. Theory of Operation NOTE: Variable names found in Figure 18 are used in ValTalk and SoftTools software and can be found in the Measured Values Status screen. The Logix 1200e digital positioner receives power from the two-wire, 4-20 mA input signal. However, since this positioner utilizes HART communications, two sources can be used for the command signal: analog or digital. With the analog source, the 4-20 mA signal is used for the command source. With the digital source, the level of the input 4-20 mA signal is ignored and a digital signal (sent via HART) is used as the command source. The command source can be accessed with ValTalk or SoftTools software, or the HART 275 communicator. The Logix 1200e positioner uses a two-stage, stempositioning algorithm. The two stages are comprised of an inner-loop, spool control and an outer-loop stem position control. Referring to Figure 18, the stem position sensor provides a measurement of the stem movement. The Control Command is compared against the Stem Position. If any deviation exists, the control algorithm sends a signal to the inner-loop control to move the spool up or down, depending on the Whether in analog or a digital source, 0 percent is always defined as the valve’s closed position and 100 percent is always defined as the valve’s open position. Tubed ATO Air Supply Control Algorithm Command Source 4–20 (Analog Mode) Analog Digital Command in (Digital mode) Linear Mode Characterization Soft Limits MPC Control + Deviation Command Pmax Pmin Gmult Integration Summer Inner Loop Offset Inner-Loop Hall Sensor Output Sensor Modulator Coil Current D/A Output Percentage Inner Loop Spool Control Stem Position Sensor Position 44 30 Flowserve Corpor tion V ltek Control Prod cts Tel USA 801 489 8611 deviation. The inner-loop then quickly adjusts the spool position. At that point, the actuator pressures change and the stem begins to move. The stem movement reduces the deviation between Control Command and Stem Position. This process continues until the deviation goes to zero. The control algorithm is both proportional and integral. (This algorithm will be further explained later in this guide.) The following detailed example explains the control function: Given: Unit is in Analog command source Custom characterization is disabled (therefore characterization is Linear) Soft limits and MPC are disabled Valve has zero deviation with a present input signal of 12 mA Loop calibration: 4 mA = 0% command, 20 mA = 100% command Actuator is tubed ATO (Air-to-Open) Given these conditions, 12 mA represents a Command Source of 50 percent. Custom characterization is disabled, so the Command Source is passed 1:1 to the Control Command. Since zero deviation exists, the Stem Position is also at 50 percent. With the stem at the desired position, the spool valve will be positioned so that no airflow is allowed to either side of the actuator. This is commonly called the null or balanced spool position. At this point, change the input signal from 12 mA to 16 mA. The positioner sees this as a Command Source of 75 percent. With Linear characterization, the Control Command becomes 75 percent. Deviation is the difference between Control Command and Stem Position, i.e. Deviation = 75% - 50%= +25%, where 50 percent is the present stem position. With a positive deviation, the control algorithm sends a signal to move the spool up from its present position. As the spool moves up, the supply air is applied to the bottom of the actuator and air is exhausted from the top of the actuator. This new pressure differential causes the stem to start moving towards the desired position of 75 percent. As the stem moves, the Deviation begins to decrease. The control algorithm begins to reduce the spool opening. This process continues until the Deviation goes to zero. At this point, the spool will return to its null or balanced position. Stem movement stops and the desired stem position is now achieved. One important parameter is now introduced – the inner loop offset. Referring to Figure 18, a number designated as the Inner Loop Offset is added to the output of the control algorithm. For the spool to remain Flowserve Corpor tion V ltek Control Prod cts Tel USA 801 489 8611 in its null or balanced position, the control algorithm must output a non-zero spool command. This is the purpose of the inner loop offset. The value of this number is equivalent to the signal that must be sent to the spool position control to bring it to a null position with zero deviation. This parameter is important for proper control and will be discussed further in the Control and Tuning section. Mounting and Installation Air Supply Requirements NOTE: The Logix 1200e positioner requires an external air filter (preferably the Valtek coalescing air filter). The air supply must conform to ISA Standard S7.3 (a dew point at least 18° F/10° C below ambient temperature, particle size below 5-microns and oil content not to exceed one part per million); however, filtering for 1micron particle size is recommended. For a model with advanced diagnostics (Logix 121X), the internal pressure sensors are rated for continuous operation up to 150 psig (10.3 barg). Electrical Wiring First, verify the polarity when making the field termination connection. The Logix 1200e positioner is reverse polarity protected. With a 4-20 mA source connected, verify that the positioner’s LED is blinking to determine if the electronics are running. Only one LED will blink at any given time. Remember the 4-20 mA input current signal must be greater than 3.5 mA to power-up the Logix 1200e positioner. Never connect a voltage source directly across the Logix 1200e terminals. The current must always be limited for 4-20 mA operation. NOTE: The Logix 1200e positioners carries an intrinsically safe barrier rating of 125 mA. Currents up to 125 mA will not damage the device. Frequently Asked Questions Q: My DCS uses 24 VDC. Can I run a Logix 1200e positioner? A: A DCS output current card does run from 24 VDC but the card regulates the actual current output. However, if the 24 VDC were applied directly across the terminals, nothing would limit the current and the Logix 1200e field termination board could be damaged. The important point to remember is that it does not matter what the current source voltage supply is as long as the current is limited in the 4-20 mA range. 44 31 Q: I accidentally placed a voltage supply across the Logix 1200e positioner. How do I know if I damaged something? A: The typical failure in an over-current situation is a short circuit. Your loop current will be maintained but the Logix 1200e control board will receive no power. With power removed from the Logix 1200e positioner, use an ohmmeter to measure the ohms across the terminals. If the reading indicates a short (close to zero ohms), the field termination board must be replaced. Make sure the positive lead is on the ‘+’ terminal and negative lead is on the ‘-’ terminal when measuring the resistance. Q: What is the input resistance of the Logix 1200e positioner? A: The Logix 1200e positioner does not have a simple resistive input. When measuring the voltage across the Logix 1200e positioner, it only varies slightly when the current is changed from 4 mA to 20 mA (11.7 VDC to 12 VDC nominal). This is because the Logix 1200e positioner is an active device. For the Logix 1200e positioner, effective resistance is commonly referred to. (Effective resistance is the resistance at a given current.) To explain further: Effective Resistance = (Terminal Voltage)/Current For example, at 20 mA: Effective resistance = 12 VDC/0.02 A = 600 Ω The Logix 1200e positioner has a specification of 600 Ω @ 20 mA. NOTE: One cannot measure across the terminals of an unpowered Logix 1200e positioner and find the effective resistance. Air Action Air-to-open and air-to-close are determined by the actuator tubing and not the software. When air-action selection is chosen during configuration, that selection tells the control which way the actuator is tubed. Verify that the actuator tubing is correct prior to a stroke calibration. The top output port is called Output 1. It should be tubed to the side of the actuator that must receive air to begin the correct action. For example, for an air-to-open linear actuator, Output 1 should be tubed to the bottom of the actuator. Linear vs. Rotary The positioner has two configuration settings: Linear and Rotary. For better resolution, stem position sensor gains are adjusted based on the linkage angle of rotation. The linear setting allows for linkage rotation up to 65°. The rotary setting allows for linkage rotation up to 44 32 95°. These settings only determine the angle of sensor rotation and do not affect control parameters. If a positioner is set to linear configuration and a red LED blinks after calibration, the most common cause is the sensor movement was greater than 65°. This can occur if the roller pin was placed in the wrong hole on the follower arm or the stem clamp is placed too high on the actuator stem. The take-off arm should always be level with the stem clamp on linear mountings. The Logix 1200e positioner has an electrical measurement range of 95°. That is, the electronics will sense stem position over a 95° range. With a rotary valve, the typical rotation is 90°. When connecting a Logix 1200e positioner to a rotary valve, the 90° valve rotation is centered within the 100° electrical range. If mechanical movement falls outside the electrical measurement range, the positioner can have a dead band at one end of travel in which valve movement cannot be sensed. Frequently Asked Questions Q: How do I know if the rotary linkage is centered within the 95° electrical range? A: The slot in the take-off arm has enough clearance around the roller pin to move the follower arm slightly. Move the valve to the fully closed position. At this position, move the follower arm within the slot clearance. If the valve does not respond by making an adjustment, linkage adjustment is necessary. Repeat this test at the fully open position. To adjust the stem position linkage, use the Logix variable number 2. This can be viewed as A/D feedback in the Measured Value screen in ValTalk software or the Hall pot sensor A/D value in the Condition screen under View Variables in SoftTools TechCheck. It can also be viewed from the HART 275 communicator in the Status/Technician menu. With the valve in its mechanical fail position (no pressure applied), slightly move the follower arm while watching variable number 2. If the number does not change, the arm is not centered in the electrical range. (The number will jump one or two counts due to noise at a fixed position and should not be considered a change. It should move greater than 10 to 20 counts if the linkage is centered correctly.) If necessary, rotate the take-off arm or feedback sensor to bring the linkage in range. NOTE: Due to the speed of HART communication, allow two to three seconds for the display to update after each adjustment. This procedure is only necessary on a rotary mounting. For linear mountings, the red LED will blink if 65° travel is exceeded. Refer to the Calibration section for further information on stroke calibration errors. Flowserve Corpor tion V ltek Control Prod cts Tel USA 801 489 8611 Calibration Quick-Cal Function The Quick-Cal™ function is a method by which the valve can be stroke calibrated without using ValTalk or SoftTools software or the HART 275 communicator. NOTE: This feature is provided to allow stroke calibration in the event a HART interface is not available. This allows the valve to be placed in operation. However, full configuration can only be accomplished through ValTalk, SoftTools or the HART 275 handheld communicator. The Quick-Cal function only affects the stroke calibration parameters. Any previous configuration or stored information is not affected. If the positioner loop current has not been calibrated in the field, it defaults to a loop calibration of 4 mA being a 0 percent command and 20 mA being a 100 percent command. This cannot be changed without HART interface. If the loop has been calibrated in the field, these settings will not be affected by the Quick-Cal function. Regarding the Linear vs. Custom DIP switch setting: If the third Quick-Cal DIP switch is set to Linear, the transfer characteristic from 4-20 mA input signal to Control Command will be 1:1. If the DIP switch is set to Custom, custom characterization will be enabled. The factory custom characterization curve is equal percent. If the characterization curve has been modified in the field, the modified curve will be used. NOTE: The DIP switch settings only become effective if the Quick-Cal button is pressed for five seconds. If the Quick-Cal function is not used, the DIP switch settings have no effect on positioner operation. Command 0% Calibration Flag During loop calibration, the Logix 1200e positioner checks if the value read with the current at the desired 0 percent command level is within range. This error normally indicates that the loop current was set above 21 mA during this part of the calibration procedure. (See How to Clear Flags section on page X.) Command 100% Calibration Flag During loop calibration, the Logix 1200e positioner checks if the value read with the current at the desired 100 percent command level is within range. This error normally indicates that the loop current was set above 21 mA during this part of the calibration procedure. (See How to Clear Flags section on page X.) Flowserve Corpor tion V ltek Control Prod cts Tel USA 801 489 8611 Position 0% Calibration Flag During stroke calibration, the Logix 1200e positioner checks if the linkage is placing the stem position sensor in range. If the valve stroke causes stem position measurement to move out of range in the closed position, a Position 0% flag will be generated. The valve stem will stop in the closed position and the red LED will blink. The linkage must then be adjusted to bring the sensor in range. (See How to Clear Flags section on page X.) NOTE: The Logix 1200e positioner has a special LED indication. If the linkage is out of range, the LEDs can be used as an adjustment guide. The LED will change from red to yellow when the linkage is brought into range. Refer to Stroke Calibration Section. Position 100% Calibration Flag During stroke calibration, the Logix 1200e positioner checks if the linkage is placing the stem position sensor in range. If the valve stroke causes stem position measurement to move out of range in the open position, a Position 100% flag will be generated. The valve stem will stop in the open position and the red LED will blink. Linkage must be adjusted to bring the sensor in range. (See How to Clear Flags section on page X.) NOTE: The Logix 1200e positioner has a special LED indication. If the linkage is out of range, the LEDs can be used as an adjustment guide. The LED will change from red to yellow when the linkage is brought into range. Refer to Stroke Calibration section. Command Span Flag Command span is a check during loop calibration to verify that the input signal changed between a 0 percent reading and a 100 percent reading. The most common cause for a Command Span flag is forgetting to change the current source when asked to set the 100 percent current level. Clear a Command Span Flag by performing a Command calibration correctly. Position Span Flag Position span is a check during stroke calibration to verify that the valve stem moved. The algorithm waits to detect if no movement is detected when the valve is automatically stroked open. Although the algorithm waits for valve movement, if a large actuator (size 200 or 300) is run at low pressures, it may not detect movement and stop with a Position Span Error. Anything that could prevent the valve from stroking will generate a Position Span Error (no supply pressure or malfunctioning spool valve). Clear a Position Span flag signal by correcting the problem that is preventing the valve to stroke and re-calibrate the stroke. 44 33 Control and Tuning Setting P+I Parameters Using ValTalk or SoftTools software, default tuning parameters can be selected: Factory A, Factory B, etc. (with Factory A beginning at the smallest actuator size and the lowest gain settings). Using the Advanced option, one can set individual tuning parameters. The software manuals outline the procedure to adjust these tuning parameters; however, a few key points are mentioned below. Maximum Gain, Minimum Gain, and Gain Multiplier: These three parameters are related by the following formulas: Proportional Gain = Maximum Gain - |deviation| x Gain Multiplier If Proportional Gain < Minimum Gain, then Proportional Gain = Minimum Gain tion, it can add overshoot as well as cause the positioner to hunt if too large. The recommendation is that maximum and minimum gains be adjusted while leaving Integral Gain fixed at 10. Integration is disabled below a stem position of 5 percent and above a stem position of 95 percent. This is to prevent integration windup from calibration shifts due to lower pressure or a damaged seat, which may prevent fully closing the valve. The Integral Summer within the Logix 1200e positioner is clamped at +20.00% and -20.00%. If the integration summer (Variable No.15 in ValTalk or SoftTools software) is fixed at +20% or -20%, it usually indicates a control problem. Some reasons for a clamped integration summer are listed below: • Stroke calibration incorrect • Any failure which prevents stem position movement, such as stuck spool, handwheel override, low pressure • Incorrect inner loop offset • Loss of air supply on a fail in place actuator Writing a zero to Integral Gain will clear the Integration Summer. The Integral Gain can then be returned to its original value. Proportional Gain Maximum Gain Gain Multiplier (Determines Slope) Minimum Gain Small Steps Large Steps | deviation | Figure 19: Logix 1200e Proportional Gain This algorithm allows for quicker response to smaller steps yet stable control for large steps. Setting the Gain Multiplier to zero or Max Gain = Min Gain results in a typical fixed proportional gain. The higher the Gain Multiplier, the smaller the required deviation before the gain increases. Default values upon initiating a RESET are Maximum Gain = 2.0, Minimum Gain = 1.0, and Gain Multiplier = 0.05. These values will allow stable control on all Valtek actuator sizes. The Integral Gain is used primarily for deviations due to temperature drift within the inner loop spool control. The factory default value is 10. Although higher numbers can speed the time it takes to reach zero devia44 34 Referring to Figure 1 under Theory of Operation, three control numbers are summed to drive the inner loop spool position control: proportional gain, integral summer, and inner loop offset. Inner Loop Offset is the parameter that holds the spool in the ‘null’ or ‘balance’ position with a control deviation of zero. This value is written by the factory during production and is a function of the mechanical and electrical spool sensing tolerances. However, if the driver module assembly is replaced or if the software Reset is performed, adjusting this value may be necessary. The method outlined below should be used to adjust the Inner Loop Offset: NOTE: Logix 1200e positioners with embedded code (revision 0.2 and higher) will automatically calculate this value during a stroke calibration. ValTalk and SoftTools Software 1. From the Advanced Tuning Screen send a 50 percent command using 4-20 mA signal or digital mode. NOTE: Digital mode must be set in Instrument Status screen prior to entering Advanced Tuning screen. 2. Allow the position to stabilize. 3. Record the D/A output % reading (displayed on the upper right hand side). This number will vary slightly; therefore, estimate an average over a brief period of time. Flowserve Corpor tion V ltek Control Prod cts Tel USA 801 489 8611 4. Write this number to the Inner Loop Offset. SoftTools TechCheck Software 1. From the Custom Tuning screen, select the Adjust ILO button. 2. Allow the position to stabilize. 3. Write the value shown for D/A Average to Inner Loop Offset. NOTE: The actuator must not be saturated (D/A output = 0) while setting the Inner Loop Offset. HART 275 Handheld Communicator 1. Send a 50 percent command using 4-20 mA signal or digital mode. 2. Proceed to the Status/Technician menu. 3. Locate the D/A Output Voltage. 4. Divide this number by 2.5 V and multiple by 100 percent. Example: D/A Output Voltage = 1.25 V. Therefore: 1.25 V/2.5 V x 100% = 0.5 x 100% = 50%. 5. Write this percentage value to the Inner Loop Offset. Digital Filter This parameter controls a noise reduction filter used on the readings obtained from command and stem position sampling. This filter is internal to the positioner software and is not associated with the external HART filter. This parameter setting should remain at 0.5. Spool Valve The spool valve is a four-way directional valve with precision features to provide optimal control and lowair consumption. To help prevent a malfunction of the spool valve, the positioner supply air must conform to ISA Standard S7.3 (a dew point at least 18 degrees below ambient temperature, particle size below 5microns, oil content not to exceed one part per million). The standard Valtek coalescing filter is highly recommended to help meet these requirements. Small particles, oil that has varnished, corrosion, ice, burrs, and extreme wear could cause the spool valve to act abnormally. If the spool valve is suspected of sticking, check it by performing the following procedure: 1. Make sure the valve is bypassed or in a safe condition. 2. Disconnect the power and air supply to the unit. 3. Remove the spool valve cover by removing the screw and sliding the cover assembly backwards until the tab is clear of the slot. Flowserve Corpor tion V ltek Control Prod cts Tel USA 801 489 8611 4. Inspect the coalescing filter element in the spool valve cover for signs of oil, water and debris that may have come from the air supply. (A clean filter is white.) 5. Remove the two Phillips-head screws holding the spool valve to the housing. Inspect the free movement of the spool by carefully sliding the block up and down on the spool about 0.25 inches (6 mm). The block should slide on the spool with no resistance. Carefully remove the block from the spool, ensuring it is removed concentric with the spool. 6. Inspect the block and spool for oil, water, debris and wear. If oil, water and/or debris are found, the spool and block can be cleaned with a non-residue cleaner, lint-free cloth and soft-bristle brush. If wear is found, replace the driver module assembly or spool valve. Refer to Spool Valve and/or Driver Module sections. 7. Before re-assembly, verify the three O-rings are correctly placed in the counter-bores on the machined platform where the spool valve block is to be placed. 8. Carefully slide the block over the spool, using the machined surface of the housing base as a register. Slide the block toward the driver module until the two retaining holes line up with the threaded holes in the base. If resistance is still encountered, re-clean both parts or replace the driver module assembly or spool valve. HART Communication Current Source Interference HART communication superimposes two frequencies (1200e Hz and 2200 Hz) on the DC 4-20 mA current signal. Some current sources (DCS or 4-20 mA calibrator) can interfere with the HART signal. This may prevent communication with ValTalk or SoftTools software or the HART 275 handheld communicator. Intermittent communication may also be the result of a HART incompatible current source. In this case, a filter is necessary between the current source and Logix 1200e positioner to allow HART communication. Valtek HART Filter (VHF) Figure 20 & Figure 21 Flowserve offers a filter (Valtek part no. 10079944) that must be used on each 4-20 mA line if the current source interferes with communication. The filter does not affect the DC current but prevents the source from affecting the HART frequencies. The filter comes in a DIN rail mount package. 44 35 NOTE: This filter is not rated for use in hazardous areas. It should be located between the current source and the barrier in intrinsically safe applications. • Rochester Instrument Systems (RIS) CL-4002 • Unomat UPS-I HART Modem The HART modem is a device that connects to the serial communications port of a computer. This modem converts the RS-232 COM port signals to the HART signal. A HART modem is required to use ValTalk software, and is optional in SoftTools since a MUX can be used in its place. The HART modem takes power from the RS-232 COM port lines. If using a laptop computer that is operating on its internal battery, HART communication may become erratic as the batteries begin to lose their charge. This is due to a reduction in HART modem power. At this point, recharge the batteries or apply AC adapter power to correct the problem. Connections Figure 20: HART VHF Filter Frequently Asked Questions Q: How do I know if I need a VHF? A: If the current source is interfering with communication, it will affect the ValTalk or SoftTools software and the HART 275 handheld communicator. If the positioner communicates to ValTalk software or the HART 275 handheld communicator when using one current source (for example, a 4-20 mA current calibrator) and not the DCS, it indicates a filter is necessary with that current source. Some 4-20 mA calibrators that work without a filter are listed below. If one of these is available, try to connect with ValTalk or SoftTools software or the HART 275 handheld communicator again. If communications are established while using one of these sources, but fails on the original source, a filter is needed. The following handheld 4-20 mA calibrators do not require a filter: When using ValTalk or SoftTools software or the HART 275 handheld communicator, the leads can be connected anywhere across the 4-20 mA current signal. The leads are not polarity sensitive. When using a filter, the connection must be made between the filter output and the Logix 1200e positioner (Figure 21). Cabling Because HART protocol uses frequencies of 1200e Hz and 2200 Hz to communicate, cable type and length must be considered. High capacitance/foot cable or long runs can cause erratic communication. Refer to instructions for correct cable requirements. Intrinsically Safe Barriers When selecting an intrinsically safe barrier, make sure the barrier is HART-compatible. Although the barrier will pass the loop current and allow normal positioner control, if not compatible, it may prevent HART communication. • Altek Model 334 Figure 21: HART VFH Filter Schematic 44 36 Flowserve Corpor tion V ltek Control Prod cts Tel USA 801 489 8611 Alarms Introduction The Logix 1200e positioner has several internal alarms that monitor electronics operation. An internal alarm causes the red LED to blink. Alarms can be viewed in the Alarm screen of ValTalk software, View Alert display (by right-clicking on the alarm LED in the lower right-hand corner of any screen), Alert Details button with SoftTools TechCheck, or by using the Hot Key with the HART 275 handheld communicator. ‘Alarms’ differ from ‘alerts’ in that the action of the positioner may be erratic during the alarm conditions, while alerts warn a predefined, user-configured condition has occurred that may require service in the near future. Alarms cause the red LED to blink, while alerts cause the yellow LED to blink. 12-bit A/D Reference Alarm The Logix 1200e positioner utilizes a 12-bit analog-todigital (A/D) converter to acquire command and stem position readings. If the precision reference used by the A/D drifts outside rated tolerances, the 12-bit A/D Reference Alarm will become active. A reference error will cause change in calibration and control readings. If a continuous 12-bit A/D Reference Alarm exists, the main PCB assembly must be replaced. Refer to spare parts kit numbers section. 1.23 V Reference Alarm The 1.23 V Reference is used by the inner loop spool position control. If it drifts outside normal tolerances, the 1.23 V Reference Alarm will become active. If a continuous 1.23 V Reference Alarm exists, the main PCB assembly must be replaced. Refer to spare parts kit numbers section. 12 bit D/A Alarm The Logix 1200e positioner utilizes a 12-bit digital-toanalog (D/A) converter to send a control signal from the micro-controller to the inner loop spool positioning circuit. The output of the D/A converter is independently measured to verify correct operation. A 12-bit D/A Alarm indicates the D/A may be malfunctioning. If a continuous 12-bit D/A Alarm exists, the main PCB assembly must be replaced. Flowserve Corpor tion V ltek Control Prod cts Tel USA 801 489 8611 Temperature Alarm The main PCB assembly contains an ambient temperature sensor. If the ambient temperature reading moves outside the operating range (-40° F to 185° F/-40° C to 85° C), the Temperature alarm becomes active and the red LED blinks. If this alarm is present and the ambient temperature reading is incorrect, the main PCB assembly must be replaced. Refer to spare parts kit numbers section. Hall Sensor Alarm As described in the Theory of Operation, the Logix 1200e positioner incorporates an inner loop, spoolpositioning stage. A hall sensor is used for spool control. If the electronics sense a problem with the sensor, the Hall Sensor Alarm becomes active. Two common reasons for a Hall Sensor Alarm are a loose or missing cable connection to the Collector Board Assembly or a broken wire. In the rare event that the actual hall sensor is defective, the driver module assembly must be replaced. Refer to spare parts kit numbers section. Modulator Current Alarm The pressure modulator is an electro-pneumatic device that takes a current signal from the electronics control and generates a pressure that moves the spool. The Logix 1200e positioner is a loop-powered device that must run on very low power. During operation, the pressure modulator current is monitored. If the current draw is not within acceptable parameters for the given control mode, the Modulator Current Alarm becomes active and the red LED blinks. The magnitude of Modulator Coil Current can be viewed as Variable No. 97 in the Instrument Status screen (ValTalk software), the Condition screen under View Variables (SoftTools TechCheck software) or in the Status/Technician screen (HART 275 handheld communicator). Listed below are some reasons for a Modulator Current Alarm: • Pressure modulator minimum pressure too low • Clogged or restricted orifice • Malfunctioning or missing cable connection to collector board assembly • Stuck or sticky spool • Internal air leaks from tubing, orifice gasket or pressure modulator 44 37 Board Current Alarm The Logix 1200e positioner is a loop-powered device, which must run on very low power. During operation, the current draw of the electronics is monitored. If current draw is excessive and would prevent operation at 3.7 mA, the Board Current Alarm becomes active and the red LED blinks. The most common cause is a failed main PCB assembly. If the electronics’ current draw is excessive, the Logix 1200e positioner will most likely operate at higher currents (12 mA and above) but may lose power at lower currents. This error requires that the main PCB be replaced. Refer to spare parts kit numbers section. EEPROM Checksum Alarm Configuration data is stored in EEPROM. When power is lost, configuration information is retrieved from EEPROM and operation resumes. A check is done by the micro-controller after a power-up to make sure data saved in EEPROM has not been corrupted. The checksum is a number that is calculated based on configuration data. It is also saved in EEPROM every time data is stored. After a power-up, if this number does not match the data in memory, an EEPROM Checksum Alarm is generated and the red LED blinks. If this occurs, turn off the power to the Logix 1200e positioner, followed by turning on the power. If the error does not clear, try saving the configuration data again using ValTalk or SoftTools software, or a HART 275 handheld communicator. If the previous configuration has not been saved, reset the device and re-configure. If these steps still do not clear the error, the main PCB assembly must be replaced. Refer to spare parts kit numbers section. Pressure Alarms NOTE: Pressure alarms are only available on models with advanced diagnostics (Logix 121X). Advanced diagnostic models add top, bottom and supply pressure sensors on more current models (Logix 1210e) the supply sensor is not included, instead, supply is calculated using the other pressure sensors. These sensor readings and alarms are only accessible from ValTalk or SoftTools software, or a HART 275 handheld communicator when the configuration has been set to Advanced. The Loss of Pressure Alarm becomes active when the supply pressure is near the minimum positioner operating pressure of 30 psig (2.1 barg). If the LEDs alternate between red and green, the supply pressure may 44 38 be at the limit threshold. This alarm is meant to alert the user to low supply pressure as well as complete loss of pressure. Both the top and bottom sensors are checked during actuator calibration. If a calibration reading appears to be out of range, the appropriate alarm will become active. The pressure sensors are located on the collector board assembly. Alerts MPC (Minimum Position Cutoff) The Minimum Position Cutoff (MPC) or tight shutoff feature of the Logix 1200e positioner allows the user to control the level at which the command signal causes full actuator saturation in the closed position. This feature can be used to guarantee actuator saturation in the closed position or prevent throttling around the seat at small command signal levels. This features defaults to 1% from the factory (which means it is enabled). NOTE: The positioner automatically adds a 1 percent hysteresis value to the MPC setting to prevent jumping in and out of saturation when the command is close to the MPC setting. Frequently Asked Questions Q: I set the MPC at 5 percent. How will the positioner operate? A: Assume the present command signal is at 50 percent. If the command signal is decreased, the positioner will follow the command until it reaches 5 percent. At 5 percent, the spool will be driven in order to provide full actuator saturation. The positioner will maintain full saturation below 5 percent command signal. Now, as the command increases, the positioner will remain saturated until the command reaches 6 percent. (Remember the 1 percent hysteresis value added by the positioner). At this point, the stem position will follow the command signal. Q: I have MPC set to 3 percent but the valve will not go below 10 percent. A: Check to see if the lower soft limit is enabled. The lower soft limit must be less than or equal to 0 percent for the MPC to become active. If a positive lower soft limit is written, this limit will take priority over the MPC feature. Flowserve Corpor tion V ltek Control Prod cts Tel USA 801 489 8611 Soft Limits Unlike position alerts, soft limits prevent the stem position from moving below or above the configured limits. If the command signal is trying to drive the position past one of the limits, the yellow LED will blink but the stem position will remain at the set limit. Q: Will soft limits prevent the valve from going to its fail position? A: No. Position Alerts Position alerts notify the user the valve has traveled past a configured limit. The default settings are -10 percent and 110 percent, which are outside normal travel and therefore disabled. Position alerts only notify the user a limit has been exceeded and do not limit stem movement. Position alerts will cause the yellow LED to blink. and added to the travel accumulator. From this new position, dead band high and low limits are again calculated. For example, the Logix 1200e positioner has a default dead band configuration of 20 percent. The valve has a 4-inch (10 cm) linear stroke. When the valve first powers up, the command signal is 50 percent. The unit will calculate a high travel threshold of 70 percent (50 percent present position plus 20 percent dead band) and a low travel threshold of 30 percent (50 percent present position minus 20 percent dead band). As long as the stem position remains greater than 30 percent and less than 70 percent, no additions are made to the travel accumulator. At this point, assume the stem position moves to 80 percent, which is outside the present dead band. The Logix 1200e positioner calculates the stem movement and adds this number to the travel accumulator. 80% (present position) – 50% (previous) = 30% movement x 4-inch stroke = 1.2 inches Cycle Counter The cycle counter is another means of monitoring valve travel. Unlike the travel accumulator, the stem position must do two things to count as a cycle: 1) exceed the cycle counter dead band and 2) change direction. A cycle counter limit can also be written into the positioner. If this limit is exceeded, the yellow LED blinks. The cycle counter must be reset to begin a new count sequence. This must be done after the alert has been triggered to reset the alert. Do this by clicking on the reset button in ValTalk or SoftTools software in the configuration section of the software. With the HART 275 handheld communicator, resetting is accomplished by choosing Configure (3) Cycle/Travel Inf. (9), Cycle/Travel, Cycle Information (2), Reset Cycle Counter (4). Therefore, 1.2 inches (3 cm) is added to the travel accumulator. New dead band thresholds of 100 percent (80 percent present position plus 20 percent dead band) and 60 percent (80 percent present position minus 20 percent dead band) are calculated. This process continues as the stem position moves throughout its stroke range. The travel accumulator will need to be reset to begin a new count sequence. This must be done after the alert has been triggered to reset the alert. Do this by clicking on the reset button in ValTalk or SoftTools software (in the Configuration section of the software) With the HART 275 handheld communicator, resetting is accomplished by choosing Configure (3) Cycle/Travel Inf. (9), Cycle/Travel, Travel Information (2), Reset Travel Accumulator (4). Travel Accumulator Position Deviation The travel accumulator is similar to an automobile odometer and sums the total valve movement. Using the user-defined stroke length and travel dead band, the Logix 1200e positioner keeps a running total of valve movement. When the positioner first powers up, high and low dead band limits are calculated around the present position. When the stem position exceeds the travel dead band, the movement from the center of the dead band region to the new position is calculated If the stem position differs from the control command by a certain amount for a given length of time, the yellow LED blinks to signify excess deviation. The trip point and settling times are set from the Configuration screen of ValTalk and SoftTools software. It is set in the HART 275 handheld communicator under Configure (3), Position Alerts (9), Deviation Deadband (3) and Time (4). Flowserve Corpor tion V ltek Control Prod cts Tel USA 801 489 8611 44 39 Advanced Features Standard vs. Advanced Diagnostics The Logix 1200e digital positioner is available with either standard or advanced diagnostics. The model with advanced diagnostics adds top, bottom and supply on more current models (Logix 1210e) the supply sensor is not included, instead, supply is calculated using the other pressure sensors. This allows for more diagnostic calculations such as loss of pressure, friction, advanced signatures, and troubleshooting. Frequently Asked Questions Stroke Length Stroke length is used by the travel accumulator. When the stroke length and units are set, the length is used to determine the total travel accumulated. The travel accumulator will have the units associated with stroke. Example: Stroke length is set to 4.0 inches (10 cm). If the valve is moved from 0 percent to 100 percent, 4 inches will be added to the travel accumulator. The travel accumulator units will be inches. If stroke length is 90 degrees for a rotary, the travel accumulator will now have units of degree. A 0 percent to 100 percent stroke will add 90 to the travel accumulator. NOTE: Stroke length is not set or used during calibration. Q: Can I upgrade from a model with standard diagnostics to advanced diagnostics? Answer: Yes, but only with the earlier model (the model characterized by an oblong LED window). The most current model (1200e, characterized by a round LED window) cannot be upgraded. A new advanced collector board assembly can be purchased. Simply replace the standard collector board with the advanced collector board. All connectors on the collector board are keyed and unique for easy cable reconnection. Using ValTalk or SoftTools software, or the HART 275 handheld communicator, configure the positioner for Advanced Diagnostics and perform an actuator pressure calibration. Temperature and Pressure Units The desired temperature and pressure units can be set during configuration. Once set, all readings will be displayed in the desired units. Custom Characterization Custom characterization can be thought of as a ‘soft CAM.’ The user can define a characterization curve using 21-points. The control will linearly interpolate between points. Points do not have to be equally spaced, which will allow more definition at critical curve areas. The Logix 1200e positioner has two modes: Linear and Custom Characterization. Linear is a straight 1:1 mapping of command to control command and does not use the 21-point curve definition. When Custom Characterization is disabled, the positioner is automatically in Linear mode. If custom characterization is enabled, the Logix 1200e positioner uses the 21-point user defined curve. Frequently Asked Questions Q: Is there a default custom characterization curve? A: Yes. The Logix 1200e positioner comes with a factory default equal-percent curve as shown in Table III 44 40 Flowserve Corpor tion V ltek Control Prod cts Tel USA 801 489 8611 . Table III: Equal Percentage Curve Data % Command % Control Command 0 0.00 5 1.00 10 2.00 15 3.00 20 4.00 25 5.24 30 6.47 35 8.02 40 9.57 45 11.86 50 14.15 55 17.54 60 20.93 65 25.94 70 30.95 75 38.36 80 45.77 85 55.66 90 67.68 95 82.31 100 100.00 NOTE: Custom characterization points can only be entered by using ValTalk or SoftTools software. The HART 275 handheld communicator will only allow the user to enable or disable the currently stored custom characterization. Table IV: Troubleshooting Logix 1200e Digital Positioner (1 of 3) Failure or Problem Probable Cause(s) Refer to Section(s) Mounting and Installation LED does not blink 1. 4-20 mA input polarity may be reversed 1. 4-20 mA input level may be too low 1. Calibration is in process 1. See Electrical Wiring on page 44-31. or Wiring and Grounding guidelines on page 44-6. 1. See overview on page 44-4. 1. See Calibration on page 44-33.. Valve moves in wrong direction with no 1. Actuator is tubed for wrong air input signal action 1. See Air Action on page 44-32. 1. See Spool Valve on page 44-35. 1. Spool is stuck Unit does not respond to analog 4-20 mA command 1. Unit is in digital command mode 1. See Theory of Operation on page 44-30. 1. Error occurred during calibration 1. See Calibration on page 44-33. Flowserve Corpor tion V ltek Control Prod cts Tel USA 801 489 8611 44 41 Table IV: Troubleshooting Logix 1200e Digital Positioner (2 of 3) Failure or Problem Probable Cause(s) Refer to Section(s) Calibration Red LED blinks after a Quick-Cal oper- 1. Positioner configured for Linear ation. Valve stays in fully open or operation, but mounted on a closed position. rotary actuator 1. Feedback linkage out of range 1. See Quick-Cal Function on page 44-33. 1. See Stem Position Sensor on page 44-12. Yellow LED blinks after a Quick-Cal operation 1. Valve did not fully stroke during 1. See Quick-Cal Function on calibration (low or no air supply) page 44-33. or 44-16. Rotary valve has a dead band at the fully open or closed position 1. Mechanical travel is not centered within the electrical measurement range. 1. See Linear vs. Rotary on page 44-32. or Stem Position Sensor on page 44-12. Red LED after loop current calibration 1. Applied Current is greater than 21 mA 1. See Command 100% Calibration Flag on page 44-33. 1. Current source changed between two values Control and Tuning Valve will not saturate at closed position 1. MPC may need to be enabled 1. See MPC (Minimum Position Cutoff) on page 44-38. Valve will not travel below or above a certain limit 1. Soft limits not enabled 1. See Advanced Features on page 44-40. Sticking or hunting operation of the positioner 1. Contamination of spool valve assembly 1. MPC not enabled 1. See Air Supply Requirements on page 44-31. See Spool Valve on page 44-35. 1. Incorrect adjustment of P+I setting 1. See Setting P+I Parameters on page 44-34. Large initial deviation. Only present on initial power-up. 1. Inner loop offset not correct 1. See Setting P+I Parameters on page 44-34. Stem position movement is not linear with command 1. Custom characterization not enabled 1. See Custom Characterization on page 44-40. 1. Current source problem; May need HART filter 1. See Current Source Interference on page 44-35. 1. Modem connection not operating correctly 1. See HART Modem on page 44-36. 1. HART module not enabled in ValTalk software 1. In Options, select HART protocol HART Communication Will not communicate HART 275 communicator indicates Generic after it connects to positioner 44 42 1. Handheld not programmed with 1. Contact Flowserve Flow ConValtek DD trol Division's Houston facility at 281.479.9500. Flowserve Corpor tion V ltek Control Prod cts Tel USA 801 489 8611 Table IV: Troubleshooting Logix 1200e Digital Positioner (3 of 3) Failure or Problem Erratic communications Probable Cause(s) 1. Maximum cable length or impedance exceeded Refer to Section(s) 1. See HART Communication on page 44-35. 1. HART modem not receiving enough power. (laptop batteries low) 1. Interference with I.S. barrier Alarms Temperature 1. Ambient temperature has exceeded electronics ratings 1. See Temperature Alarm on page 44-37. Hall sensor 1. Cable may have bad connection 1. See Hall Sensor Alarm on page 44-37. 1. Sensor may be damaged Modulator Current 1. Modulator minimum pressure may be too low 1. See Modulator Current Alarm on page 44-37. 1. Clogged orifice 1. Bad cable connection EEPROM checksum 1. Error when reading non-volatile 1. See EEPROM Checksum Alarm memory storage on page 44-38. Multiple Internal Flags 1. Bad micro-controller on main PCB assembly 1. Replace main PCB assembly 1. Modulator coil current may be too high 1. See Modulator Current Alarm on page 44-37. LEDs LED alternates between Green and Red in normal operation 1. Supply pressure may be close to minimum of 30 psig (2.1 barg) No LED blinks during calibration 1. Normal operation 1. Yellow LED is blinking but valve position is fine 1. User-defined limit may have been reached; check alarm screen 1. See Alerts on page 44-38. Red LED is blinking on advanced model, even though positioner has pressure 1. Pressure below 30 psi (2.1 bar) 1. See Pressure Alarms on page 44-38. Advanced Features Will not display pressure readings 1. Configuration not set to Advanced 1. See Standard vs. Advanced Diagnostics on page 44-40. MPC will not function 1. Lower soft limit >= 0%. 1. See MPC (Minimum Position Cutoff) on page 44-38. 1. 1% hysteresis around MPC setpoint being considered Flowserve Corpor tion V ltek Control Prod cts Tel USA 801 489 8611 44 43 Flowserve Corporation has established industry leadership in the design and manufacture of its products. When properly selected, this Flowserve product is designed to perform its intended function safely during its useful life. However, the purchaser or user of Flowserve products should be aware that Flowserve products might be used in numerous applications under a wide variety of industrial service conditions. Although Flowserve can (and often does) provide general guidelines, it cannot provide specific data and warnings for all possible applications. The purchaser/user must therefore assume the ultimate responsibility for the proper sizing and selection, installation, operation and maintenance of Flowserve products. The purchaser/user should read and understand the Installation Operation Maintenance (IOM) instructions included with the product, and train its employees and contractors in the safe use of Flowserve products in connection with the specific application. While the information and specifications presented in this literature are believed to be accurate, they are supplied for informative purposes only and should not be considered certified or as a guarantee of satisfactory results by reliance thereon. Nothing contained herein is to be construed as a warranty or guarantee, express or implied, regarding any matter with respect to this product. Because Flowserve is continually improving and upgrading its product design, the specifications, dimensions and information contained herein are subject to change without notice. Should any question arise concerning these provisions, the purchaser/user should contact Flowserve Corporation at any of its worldwide operations or offices. For more information, contact: For more information about Flowserve and its products, contact www.flowserve.com or call USA 972 443 6500 Manufacturing Facilities Quick Response Centers 1350 N. Mt. Springs Prkwy. Springville, UT 84663 Telephone 801 489 8611 Facsimile 801 489 3719 Manderscheidstr. 19 45141 Essen, Germany Telephone (49) 2 01 89 19 5 Facsimile (49) 2 01 891 9600 5114 Railroad Street Deer Park, TX 77536 USA Telephone 281 479 9500 Facsimile 281 479 8511 1300 Parkway View Drive Pittsburgh, PA 15205 USA Telephone 412 787 8803 Facsimile 412 787 1944 Alläe du Quartz 1 CH-2300 La Chaux-de-Fonds Switzerland Telephone (41) 32 925 9700 Facsimile (41) 32 926 5422 104 Chelsea Parkway Boothwyn, PA 19061 USA Telephone 610 497 8600 Facsimile 610 497 6680 FCD VLAIM044 04c© 2000 Flowserve Corpor tion Flowserve Corpor tion V ltek Control Prod cts Tel USA 801 489 8611