Refrigerant R407C
CW-AR
Water Source Heat Pumps - Vertical Mounting Version
Models 07 to 12
2.4 to 3.1kW
1.9 to 2.7kW
Some advantages...
RAL 9010 painted cabinet
3-fan speeds
G2 filter is supplied as standard.
Front or bottom access to the filter.
Temperature range : 13 to 45 °C
EC version is available
as optional
Front panel is very easy to remove in order to
facilitate access to internal components.
Direct external access Schrader valves
(HP&LP) available for a pressure tap on
the refrigerant circuit.
STORM 2 electronic board and RCL remote control are delivered as standard
1 RCL
x 10
units
2
Unit Description
Generalities
Water connections
 RAL 9010 painted cabinet with optimal compactness.
 High efficiency units with high COP values.
The water source outlet and return connectors are located on the outside of
the unit in several configurable positions. They are of female gas threaded
type (1/2").
 Complete access to the compressor, fan and electrical box, through front
removable panel.
The condensate drain connection is of smooth tube type with an outside
diameter of 16 mm.
Condensate drain pan with anti-corrosion treatment by oven-baked
epoxy paint..
Water feeding sides : BACK / RIGHT / LEFT / MIDDLE.
 Fan motor equipped with 3 ventilation speed, or optional EC version.
A flow switch of SIKA type will be factory supplied as standard in order to
avoid any compressor damage.
 Heat exchanger with brazed stainless steel plates on the water/
refrigerant side, for improved efficiency.
Electrical box
Stand-alone control by a STORM 2 electronic board which can be
configured using the RCL user remote control, which comprises a digtal
display and essential control keys.
Holes are provided in the casing for entry of electrical power supply and
remote control cables.
 Optional TAC branded XENTIA type LON control associated to TH STR
106.
The electrical power supply for CW-AR units is 230V/1Ph/50Hz. Compressor
is standard equipped with an internal thermal protection with an automatic
reset function.
Introduction
Refrigerant circuit
The new generation of CW-AR water source heat pumps is the fruit of our
considerable product experience and our awareness of the market, all combined
with a technology based on the energy efficiency of machines, in order to
provide on the market units with the highest performance in terms of COP.
The refrigerant circuit comprises a rotary type hermetic compressor, a cycle
reversal valve, a water/refrigerant heat exchanger, a liquid receiver, and a
finned coil. The refrigerant circuit also comprises an HP pressure switch
with automatic reset function (range 29-24 bar) and an LP pressure switch
with an automatic reset function (range 1.4-2.4 bar). Two direct external
access Schrader valves (HP & LP) are available for pressure tapping on the
refrigerant circuit.
Operating range
To enable a much wider operating range and installation using a water source
in an application with a dry cooler, the standard CW-AR units are designed to
operate in a water source temperature range between 13 and 45 °C.
The water/refrigerant heat exchanger is of the brazed stainless steel plate
type, for increased efficiency. The anti-freeze safety of the heat exchanger
is provided by a water pipe sensor located on the water outlet of the unit
monitored by the electronic board. Maximum service pressure water side
(27.5 bar) and refrigerant side (30 bar). The heat exchangers are particularly
well adapted to the operation of reversible heat pumps with high thermal
transfer rates for a low water flow rate.
Cabinet
The cabinet is made of galvanised sheet steel painted RAL 9010.
To facilitate access to the main components, front removable panel provides
access to the compressor, the fan and the electrical box.
The air/refrigerant coil is made of aluminium fins which are mechanically
crimped onto copper tubes. The geometry of the coil and of the fin profile
have been carefully designed to provide maximum efficiency in the operation
of the units.
The condensate drain pan has anti-corrosion treatment consisting of ovenbaked epoxy paint.
The inside of the cabinet, on the fan compartment side, is coated with 15 mm
thick closed cell polyurethane foam thermal-acoustic insulation, classified M1.
The cycle reversal valve is designed to be normally energised in heating mode.
This logic enables the heat pump to continue to operate in cooling mode if
this valve fails.
On the compressor compartment side, the thermal-acoustic insulation is of
20 mm thick Isofeutre type with heavy mass.
The liquid receiver enables the charge of HFC 407C refrigerant to be optimised,
in order to maintain a high COP value.
Versions
Ventilation section
The CW-AR range is available in several versions :
The fan compartment contains the fan-motor assembly, the air/refrigerant coil
and the condensate drain pan. The ventilation section is completely isolated
from compressor compartment by a thermally and acoustically insulated
partition wall.
 CW-AR CAR : standard version with cabinet,
 CW-AR CARB : low height version with cabinet,
 CW-AR NU : standard version without cabinet,
Wide removable panels provide access to the various internal components.
The condensate drain pan has an anti-corrosion treatment.
 CW-AR NUB : low height version without cabinet.
Each version can be supplied, as standard, with feet or with front air intake
RF (optional).
All the units are equipped with a 3 speed direct-drive fan motor with ipsothermal
protection against overheating during operation. The motor ipsothermal
protection fault is displayed in the form of a coded signal on the LED of the
RCL remote control.
Filtration
All units are equipped as standard with a disposable G2 filter.
The 3 fan speeds can be controlled either manually or automatically by the
electronic management board of the unit.
Access to the filter can be realized by the front or the bottom (according to the
version CW-AR RF or CW-AR with feet).
EC optional motor available on request.
3
Versions
CW-AR CAR with feet
CW-AR CAR with front air intake RF
CW-AR CARB with feet
CW-AR CARB with front air intake RF
CW-AR NU with feet
CW-AR NU with front air intake RF
CW-AR NUB with feet
CW-AR NUB with front air intake RF
4
Control Features
STORM 2 electronic board
RCL user remote control
All CW-AR water source heat pumps are, in their standard version, equipped
with a STORM 2 electronic board which manages their operation and their
safety devices.
STORM 2 electronic board
Master/slaves control : the standard version of the STORM 2 electronic board
enables operation in master/slaves regulation mode for up to 10 water source
heat pumps using a single RCL user remote control.
This configuration enables the installer to save on the purchase and wiring of
equipment such as auxiliary relays and multi-wire cables between the various
water source heat pumps. Only a bus cable with 2 twisted pairs is necessary
between the master and slave units.
RCL user remote control
When a request for operation in cooling mode is received, the fan-motor
assembly is started up immediately and the compressor does not start until
after an effective time delay of 180 seconds. The RCL remote control enables
operation in cooling-only mode or in automatic cooling/heating mode with, at a
given temperature set-point used as a switch-over point, a neutral switch-over
range of +/-3 °C from cooling to heating mode. In cooling mode, the fan runs
permanently and the 3 speed ventilation can be implemented in automatic or
manual mode : HS, MS, or LS.
An RCL user remote control is supplied as standard in the electrical control
box of the units.
It enables individually controlled operation as stand-alone regulation.
The RCL remote control is ergonomically designed and discreet. It comprises
a digital display and essential functions such as :
On/Off,
When a request for operation in heating mode is received, the fan-motor
startup is controlled by the electronic board and the temperature of the ICT
sensor; the reversal valve is activated before the compressor and the latter
does not start until after an effective time delay of 180 seconds. The RCL
remote control enables operation in heating-only mode or in automatic heating/
cooling mode with, at a given temperature set-point used as a switch-over
point, a neutral switch-over range of +/-3 °C from heating to cooling mode.
In heating mode, the fan can operate either cyclically (the fan stops when the
set temperature is reached) or permanently and the 3 speed ventilation can be
implemented in automatic or manual mode: HS, MS, or LS.
Selection of operating mode,
Room temperature display,
Fan speed selection,
Temperature set-point adjustment.
A keypad locking function is also available.
The RCL user remote control comprises a Display LED which shows the
operating status of the water source heat pump (Lit : On - Unlit : Off), and it
also enables an operational fault to be identified by flashing a specific code.
Measurement of the room air temperature : the STORM 2 card electronic
regulation enables the selection of a room temperature measurement mode
which uses an ambient temperature sensor (RCT) in the RCL remote control,
or a return temperature sensor (RAT) located directly on the water source
heat pump.
Anti-short cycle : after each compressor shut-down, a time delay of 180
seconds is introduced by the electronic board. This time delay constitutes an
anti-short cycle device and therefore helps to protect the compressor.
5
Control Features (continued)
Variable sequential start-up function : when the system is first energised, or
after a power cut, or after opening the "CLK" contact, a random time delay of 0
to 30 seconds is introduced by the electronic board to prevent the water source
heat pumps from all starting up simultaneously, thus avoiding a power surge.
µBMS mini-supervision station
Emergency shut-down / stand-by / night setback : the electronic board has
two "CLK" terminals which shut the unit down immediately.
32 water source heat pumps in 15 zones from a single point, in addition to
This centralised control unit is proposed as an option, and can be connected to
the STORM 2 electronic board as a supervision station to monitor and manage
the local RCL remote controls.
By incorporating a zone thermostat in series, the "CLK" contact can also be used
as a night setback and the water source heat pump will start up again as soon
as the ambient temperature drops below the set point of the setback thermostat.
The µBMS mini-supervision station enables the zones to be programmed
with global control for all zones, or with individual control of each zone
Anti-freeze safety function : this is provided by two temperature sensors. In
cooling mode an "ICT" temperature sensor located in the finned coil protects
the water source heat pump against accidental freezing.
with programming of the operating time ranges over a 7 day period, with
In heating mode, the safety function is provided by an "LWT" minimum water
outlet temperature sensor. The anti-freeze fault read by the temperature sensor
is displayed by a coded signal on the LED of the RCL remote control.
It also provides the possibility of having different set-points in different zones.
management of the heating, cooling and night setback modes.
µBMS mini-supervision station
High temperature safety function : the "ICT & LWT" temperature sensors
check that the condensation temperature at the finned coil and the water
temperature at the outlet of the water/refrigerant heat exchanger do not exceed
the authorised limits.
The manual reset HP pressure switch completes the high temperature safety
function. The high temperature safety fault read by the ICT and LWT sensors
and the HP pressure switch cut-off is displayed by a coded signal on the LED
of the RCL remote control.
Fault reports : the electronic regulation carried out by the STORM 2 board
uses coded signals to remotely report four different possible machine faults
on the display LED of the RCL remote control :
- HP pressure switch triggering,
- Water temperature fault in low limit,
- Water temperature fault in high limit,
- Anti-freeze protection.
The STORM 2 electronic board also enables the general machine fault to be
sent to a remote fault relay via a dry contact.
Motorized valve : The STORM 2 electronic board has a 230 volt output for an
(optional) motorized valve controlled by the operation of the compressor, in
order to enable the flow-rate of the hydraulic pump(s) to be regulated according
to the manometric pressure in the water source.
6
Operating Limits
Environment
This equipment is designed for an internal installation only.
In general, the sheltered locations, such as garages, attic, etc, do not provide sufficient protection against extreme temperatures and/or humidity, and the performance,
the reliability and the life span of the equipment can be decreased.
Temperature limits
Cooling
Return air temperature
Entering water
temperature
Heating
Minimum
21 °C dry bulb / 15 °C wet bulb
15 °C
Nominal *
27 °C dry bulb / 19 °C wet bulb
20 °C
Maximum
32 °C dry bulb / 23 °C wet bulb
27 °C
Minimum
23 °C
12 °C
Nominal *
30 °C
20 °C
Maximum
42 °C
34 °C **
Temperature and water flow limits are independant of fan speed.
* Nominal conditions according to EN 14511-2.
** 32 °C for model CW-AR 07 at LS (low speed).
Flow limits
CW-AR 07
Water flow (l/h)
650
600
550
500
450
400
350
300
250
200
150
100
50
0
20
22
24
26
28
30
32
34
36
Entering water temperature (°C)
38
40
42
44
650
600
550
Low Speed
500
Water flow (l/h)
450
400
350
Medium Speed and
High Speed
300
250
200
150
100
50
0
10
12
14
16
18
20
22
24
26
Entering water temperature (°C)
7
28
30
32
34
36
Operating Limits (continued)
Flow limits
Water flow (l/h)
CW-AR 09
650
600
550
500
450
400
350
300
250
200
150
100
50
0
20
22
24
26
28
30
32
34
36
38
40
42
44
Entering water temperature (°C)
650
600
Water flow (l/h)
550
500
450
400
350
300
250
200
150
100
50
0
10
12
14
16
18
20
22
24
26
28
30
32
34
36
Entering water temperature (°C)
Water flow (l/h)
CW-AR 12
650
600
550
500
450
400
350
300
250
200
150
100
50
0
20
22
24
26
28
30
32
34
36
38
40
42
44
Entering water temperature (°C)
650
600
550
Water flow (l/h)
500
450
400
350
300
250
200
150
100
50
0
10
12
14
16
18
20
22
24
26
28
Entering water temperature (°C)
8
30
32
34
36
Physical Data
Models
CAPACITIES
Total cooling capacities (1)
Sensible cooling capacities (1)
Heating capacities (2)
VENTILATION
Air flow (Low Speed)
Air flow (Medium Speed)
Air flow (High Speed)
Motor power
Fan speeds
Air filter - Number / Efficiency
Air filter (front) - Dimensions / Thickness
Air filter (bottom) - Dimensions / Thickness
HYDRAULIC CIRCUIT
Water heat exchanger
Maximum water pressure
Nominal water flow (1)
Cutoff water flow versus nominal water flow
WPD at nominal water flow
Hydraulic connections - Inlet / Outlet
Condensate outlet Ø
REFRIGERANT CIRCUIT
Number of circuit
Compressor
WEIGHT WITHOUT CABINET / WITH CABINET
Operating weight
SOUND DATA
Sound power Lw (Low Speed)
Sound power Lw (Medium Speed)
Sound power Lw (High Speed)
ELECTRICAL DATA
Power input - Cooling mode (3)
Power input - Heating mode (3)
Electrical power supply
Fan max. current
Compressor nominal current (4)
Compressor starting current (5)
CWAR 07
CWAR 09
CWAR 12
W
W
W
1942
1526
2431
2136
1775
2542
2743
2340
3156
m3/h
m3/h
m3/h
W
Nbr
250
340
400
75
3
340
400
460
75
3
1 / G2
660 x 205 mm / 6 mm
595 x 187 mm / 6 mm
400
460
510
75
3
mm
mm
Nbr
bar
l/s
%
kPa
Inches
mm
0.119
44
5
0.171
31
12
1
Rotary
Type
kg
1
3
0.133
40
3,4
ISO G 1/2'' INT
15 x 20
55 / 70
58 / 73
60 /75
dB(A)
dB(A)
dB(A)
49
50
51
50
51
53
51
53
54
W
W
598
710
892
954
A
A
A
0.2
2.8
16
647
720
230V/1Ph/50Hz ±10%
0.25
3
16
0.3
4
18.9
(1) Nominal cooling capacities based on : entering air temperature of 27 °C dry bulb, 19 °C wet bulb with entering water temperature of 30 °C.
(2) Nominal heating capacities based on : entering air temperature of 20 °C dry bulb, 15 °C wet bulb with entering water temperature of 20 °C.
(3) Absorbed power (compressor + fan) at nominal conditions.
(4) Nominal currents are given at +/- 5%.
(5) Starting currents are given at +/- 10%.
Dimensions (in mm) - All Sizes
Versions
Length
Width
Height with feet
Height with front air intake
With cabinet CAR
1138
251
821
720÷750
With cabinet CARB
1323
251
683
580÷610
9
Without cabinet NU
1086
229
769
667÷697
Without cabinet NUB
1184.5
229
624
525÷555
Cooling Performance Data - CW-AR 07
Nominal airflow 340 m3/h - Medium Speed
Entering
Water Temp.
(°C)
20
27
30
32
38
40
Water
Water flow Pressure
Drop
(l/s)
(kPa)
0.119
5.0
0.089
2.8
0.060
1.3
0.119
5.0
0.089
2.8
0.060
1.3
0.119
5.0
0.089
2.8
0.060
1.3
0.119
5.0
0.089
2.8
0.060
1.3
0.119
5.0
0.089
2.8
0.060
1.3
0.119
5.0
0.089
2.8
0.060
1.3
Cooling mode
TEA (°C)
TSE (°C)
Pt (W)
Ps (W)
Pabs (W)
CR (W)
EER
24/17
27/19
30/21
24/17
27/19
30/21
24/17
27/19
30/21
24/17
27/19
30/21
24/17
27/19
30/21
24/17
27/19
30/21
24/17
27/19
30/21
24/17
27/19
30/21
24/17
27/19
30/21
24/17
27/19
30/21
24/17
27/19
30/21
24/17
27/19
30/21
24/17
27/19
30/21
24/17
27/19
30/21
24/17
27/19
30/21
24/17
27/19
30/21
24/17
27/19
30/21
24/17
27/19
30/21
24.9
25.1
25.3
26.5
26.8
27.1
29.8
30.2
30.7
31.8
32.1
32.2
27.8
33.7
34.0
36.7
37.1
37.6
34.8
35.0
35.3
36.4
36.7
37.0
39.5
40.0
40.5
36.8
37.0
37.1
38.3
38.6
38.9
41.4
41.8
42.3
42.7
42.9
43.2
44.3
44.6
44.9
47.3
47.8
48.1
44.7
44.8
45.1
46.2
46.4
46.8
49.2
49.7
50.1
1967
2071
2170
1942
2052
2151
1935
2016
2138
1864
1992
2072
1850
1959
2054
1840
1929
2065
1829
1942
2047
1820
1928
2031
1779
1892
2012
1802
1922
1972
1776
1863
1963
1732
1835
1941
1711
1810
1915
1704
1803
1907
1650
1755
1837
1669
1748
1875
1645
1734
1852
1613
1719
1815
1538
1602
1663
1526
1595
1666
1520
1558
1652
1485
1565
1616
1474
1548
1563
1458
1533
1620
1465
1526
1608
1454
1514
1604
1441
1516
1596
1451
1530
1568
1438
1501
1520
1412
1493
1539
1404
1477
1491
1404
1477
1555
1371
1454
1493
1387
1455
1525
1366
1436
1519
1356
1430
1493
485
486
492
491
495
497
511
516
521
541
542
543
546
550
551
574
581
583
568
570
571
575
578
579
592
596
602
587
591
592
594
599
602
611
618
622
648
650
653
657
660
663
668
674
682
660
664
667
669
672
674
686
691
697
2452
2557
2662
2433
2547
2649
2446
2532
2659
2405
2534
2615
2396
2509
2605
2414
2510
2649
2397
2512
2618
2395
2506
2610
2371
2488
2614
2389
2513
2564
2370
2462
2565
2343
2453
2563
2359
2460
2568
2361
2463
2570
2318
2429
2519
2329
2412
2542
2314
2405
2526
2299
2410
2512
4.06
4.26
4.41
3.95
4.14
4.32
3.79
3.91
4.10
3.45
3.68
3.82
3.39
3.56
3.73
3.20
3.32
3.54
3.22
3.41
3.58
3.16
3.33
3.51
3.01
3.17
3.34
3.07
3.25
3.33
2.99
3.11
3.26
2.83
2.97
3.12
2.64
2.79
2.93
2.59
2.73
2.88
2.47
2.61
2.69
2.53
2.63
2.81
2.46
2.58
2.75
2.35
2.49
2.60
TEA : Entering air temperature (dry bulb/wet bulb).
TSE : Leaving water temperature.
Pt : Total cooling capacity.
Ps : Sensible cooling capacity.
Pabs : Compressor power input.
CR : Total heat rejection.
10
Heating Performance Data - CW-AR 07
Nominal airflow 340 m3/h - Medium Speed
Entering
Water Temp.
(°C)
Water
Water flow Pressure
Drop
(l/s)
(kPa)
0.119
5.0
0.089
2.8
0.119
5.0
0.089
2.8
0.060
1.3
0.119
5.0
0.089
2.8
0.060
1.3
0.119
5.0
0.089
2.8
0.060
1.3
0.119
5.0
0.089
2.8
0.060
1.3
0.119
5.0
0.089
2.8
0.060
1.3
13
16
20
27
30
32
Heating mode
TEA (°C)
Pc (W)
Pabs (W)
CA (W)
COP
16
20
27
16
20
27
16
20
27
16
20
27
16
20
27
16
20
27
16
20
27
16
20
27
16
20
27
16
20
27
16
20
27
16
20
27
16
20
27
16
20
27
16
20
27
16
20
27
16
20
27
2204
2055
2246
1994
1977
1952
2251
2280
2329
2158
2166
2110
2046
2035
2012
2457
2431
2395
2386
2363
2326
2264
2238
2055
2896
2864
2811
2805
2778
2727
2638
2609
2582
3090
3054
2992
3000
2959
2904
2819
2785
2738
2974
2937
2875
2868
2842
2789
2703
2685
2622
611
660
752
575
613
689
614
664
766
599
675
722
583
625
702
636
682
769
628
672
758
612
656
739
665
719
820
661
714
811
652
700
795
671
727
832
671
723
827
661
713
813
606
659
758
607
659
753
605
653
745
1593
1394
1494
1419
1364
1264
1637
1616
1563
1558
1491
1387
1463
1410
1310
1821
1749
1626
1758
1691
1568
1652
1582
1315
2231
2145
1991
2143
2064
1916
1986
1909
1788
2420
2327
2159
2330
2236
2078
2157
2072
1925
2368
2279
2117
2262
2183
2036
2099
2031
1877
3.61
3.11
2.99
3.47
3.22
2.83
3.66
3.44
3.04
3.60
3.21
2.92
3.51
3.26
2.87
3.86
3.56
3.11
3.80
3.52
3.07
3.70
3.41
2.78
4.36
3.98
3.43
4.24
3.89
3.36
4.05
3.73
3.25
4.61
4.20
3.59
4.47
4.09
3.51
4.26
3.91
3.37
4.91
4.46
3.79
4.73
4.31
3.70
4.47
4.11
3.52
TEA : Entering air temperature.
Pc: Heating capacity.
Pabs : Compressor power input.
CA : Total heat absorption.
11
Cooling Performance Data - CW-AR 09
Nominal airflow 400 m3/h - Medium Speed
Entering
Water Temp.
(°C)
20
27
30
32
38
40
Water
Water flow Pressure
Drop
(l/s)
(kPa)
0.133
3.4
0.100
1.2
0.067
0.5
0.133
3.4
0.100
1.2
0.067
0.5
0.133
3.4
0.100
1.2
0.067
0.5
0.133
3.4
0.100
1.2
0.067
0.5
0.133
3.4
0.100
1.2
0.067
0.5
0.133
3.4
0.100
1.2
0.067
0.5
Cooling mode
TEA (°C)
TSE (°C)
Pt (W)
Ps (W)
Pabs (W)
CR (W)
EER
24/17
27/19
30/21
24/17
27/19
30/21
24/17
27/19
30/21
24/17
27/19
30/21
24/17
27/19
30/21
24/17
27/19
30/21
24/17
27/19
30/21
24/17
27/19
30/21
24/17
27/19
30/21
24/17
27/19
30/21
24/17
27/19
30/21
24/17
27/19
30/21
24/17
27/19
30/21
24/17
27/19
30/21
24/17
27/19
30/21
24/17
27/19
30/21
24/17
27/19
30/21
24/17
27/19
30/21
24.8
25.0
25.2
26.4
26.7
26.9
29.6
29.9
30.4
31.7
32.0
32.1
27.8
33.6
33.8
36.5
36.8
37.4
34.7
35.0
35.1
36.3
36.6
36.8
39.3
39.8
40.3
36.7
36.9
37.0
38.2
38.4
38.7
41.2
41.6
42.0
42.6
42.8
43.0
44.2
44.4
44.7
47.1
47.5
47.9
44.6
44.7
45.0
46.0
46.3
46.6
49.0
49.4
49.8
2164
2278
2387
2136
2257
2366
2128
2217
2352
2050
2191
2279
2035
2155
2259
2024
2122
2271
2012
2136
2252
2002
2121
2234
1957
2081
2213
1982
2114
2169
1953
2049
2159
1905
2018
2135
1882
1991
2106
1874
1983
2097
1815
1930
2020
1836
1923
2062
1809
1907
2037
1774
1891
1996
1789
1864
1934
1775
1855
1938
1768
1812
1922
1727
1821
1880
1715
1801
1818
1696
1784
1885
1704
1775
1870
1691
1761
1866
1676
1764
1856
1688
1780
1824
1673
1745
1768
1642
1737
1790
1633
1718
1734
1633
1718
1808
1595
1691
1737
1614
1692
1774
1589
1670
1766
1577
1663
1737
517
518
524
523
528
530
544
550
555
576
577
578
582
586
587
611
619
621
605
607
608
613
616
617
630
635
641
625
629
630
632
638
641
651
658
662
690
692
695
700
703
706
712
717
726
703
707
711
713
715
717
731
736
743
2680
2796
2911
2659
2785
2896
2672
2767
2907
2626
2768
2857
2616
2741
2846
2635
2741
2893
2616
2743
2860
2614
2736
2851
2587
2716
2854
2607
2743
2799
2586
2687
2800
2556
2676
2797
2572
2683
2802
2574
2686
2804
2527
2648
2747
2539
2630
2773
2522
2622
2754
2505
2627
2739
4.19
4.40
4.55
4.08
4.28
4.47
3.91
4.03
4.24
3.56
3.80
3.94
3.50
3.68
3.85
3.31
3.43
3.66
3.33
3.52
3.70
3.27
3.44
3.62
3.10
3.28
3.45
3.17
3.36
3.44
3.09
3.21
3.37
2.93
3.07
3.22
2.73
2.88
3.03
2.68
2.82
2.97
2.55
2.69
2.78
2.61
2.72
2.90
2.54
2.67
2.84
2.43
2.57
2.69
TEA : Entering air temperature (dry bulb/wet bulb).
TSE : Leaving water temperature.
Pt : Total cooling capacity.
Ps : Sensible cooling capacity.
Pabs : Compressor power input.
CR : Total heat rejection.
12
Heating Performance Data - CW-AR 09
Nominal airflow 400 m3/h - Medium Speed
Entering
Water Temp.
(°C)
Water
Water flow Pressure
Drop
(l/s)
(kPa)
0.133
3.4
0.100
1.2
0.133
3.4
0.100
1.2
0.067
0.5
0.133
3.4
0.100
1.2
0.067
0.5
0.133
3.4
0.100
1.2
0.067
0.5
0.133
3.4
0.100
1.2
0.067
0.5
0.133
3.4
0.100
1.2
0.067
0.5
13
16
20
27
30
32
Heating mode
TEA (°C)
Pc (W)
Pabs (W)
CA (W)
COP
16
20
27
16
20
27
16
20
27
16
20
27
16
20
27
16
20
27
16
20
27
16
20
27
16
20
27
16
20
27
16
20
27
16
20
27
16
20
27
16
20
27
16
20
27
16
20
27
16
20
27
2305
2148
2348
2085
2067
2042
2354
2384
2435
2256
2265
2206
2139
2127
2104
2569
2542
2505
2495
2471
2432
2368
2340
2148
3028
2995
2939
2933
2904
2852
2758
2728
2700
3231
3193
3128
3137
3094
3037
2947
2912
2863
3370
3329
3259
3251
3220
3161
3063
3042
2971
609
658
750
574
611
687
612
662
764
598
673
720
582
623
699
634
680
767
626
670
756
610
654
737
663
717
817
659
712
808
650
698
792
669
725
830
669
721
824
659
711
811
667
726
836
669
726
830
666
720
821
1696
1490
1599
1512
1456
1355
1741
1722
1672
1659
1592
1486
1558
1505
1404
1935
1862
1738
1869
1801
1677
1757
1687
1411
2365
2278
2122
2273
2192
2043
2108
2030
1908
2563
2468
2298
2469
2373
2213
2288
2201
2053
2703
2603
2423
2582
2495
2331
2397
2322
2150
3.78
3.26
3.13
3.64
3.38
2.97
3.84
3.60
3.19
3.78
3.37
3.06
3.68
3.42
3.01
4.05
3.74
3.27
3.99
3.69
3.22
3.88
3.58
2.91
4.57
4.18
3.60
4.45
4.08
3.53
4.24
3.91
3.41
4.83
4.41
3.77
4.69
4.29
3.68
4.47
4.10
3.53
5.05
4.59
3.90
4.86
4.44
3.81
4.60
4.23
3.62
TEA : Entering air temperature.
Pc: Heating capacity.
Pabs : Compressor power input.
CA : Total heat absorption.
13
Cooling Performance Data - CW-AR 12
Nominal airflow 460 m3/h - Medium Speed
Entering
Water Temp.
(°C)
20
27
30
32
38
40
Water
Water flow Pressure
Drop
(l/s)
(kPa)
0.171
12.0
0.128
6.8
0.086
3.0
0.171
12.0
0.128
6.8
0.086
3.0
0.171
12.0
0.128
6.8
0.086
3.0
0.171
12.0
0.128
6.8
0.086
3.0
0.171
12.0
0.128
6.8
0.086
3.0
0.171
12.0
0.128
6.8
0.086
3.0
Cooling mode
TEA (°C)
TSE (°C)
Pt (W)
Ps (W)
Pabs (W)
CR (W)
EER
24/17
27/19
30/21
24/17
27/19
30/21
24/17
27/19
30/21
24/17
27/19
30/21
24/17
27/19
30/21
24/17
27/19
30/21
24/17
27/19
30/21
24/17
27/19
30/21
24/17
27/19
30/21
24/17
27/19
30/21
24/17
27/19
30/21
24/17
27/19
30/21
24/17
27/19
30/21
24/17
27/19
30/21
24/17
27/19
30/21
24/17
27/19
30/21
24/17
27/19
30/21
24/17
27/19
30/21
24.9
25.1
25.3
26.5
26.8
27.0
29.7
30.1
30.6
31.8
32.1
32.2
28.1
33.7
33.9
36.6
37.0
37.6
34.8
35.0
35.2
36.4
36.7
36.9
39.5
39.9
40.4
36.8
37.0
37.1
38.3
38.6
38.8
41.4
41.8
42.2
42.7
42.9
43.1
44.3
44.6
44.8
47.3
47.7
48.1
44.7
44.8
45.1
46.2
46.4
46.7
49.2
49.6
50.0
2778
2925
3065
2743
2898
3038
2733
2848
3020
2633
2814
2927
2613
2767
2901
2599
2725
2917
2583
2743
2891
2571
2723
2869
2513
2672
2842
2545
2715
2785
2508
2631
2773
2446
2592
2742
2417
2556
2705
2407
2547
2694
2330
2479
2595
2357
2469
2648
2323
2449
2616
2278
2428
2564
2358
2457
2549
2340
2446
2554
2330
2389
2533
2277
2400
2478
2260
2374
2397
2236
2351
2485
2246
2340
2465
2230
2322
2460
2210
2325
2447
2225
2346
2405
2205
2301
2330
2165
2290
2359
2153
2265
2286
2153
2265
2384
2103
2230
2290
2127
2231
2338
2095
2202
2329
2079
2192
2290
717
719
728
727
733
736
756
763
771
800
802
803
808
814
815
849
860
863
840
843
845
851
855
857
875
881
891
868
874
875
878
886
891
904
914
920
958
961
966
972
976
981
989
996
1009
976
982
987
990
993
996
1015
1022
1032
3496
3644
3793
3470
3631
3774
3489
3611
3791
3433
3615
3730
3421
3581
3717
3448
3584
3780
3423
3586
3736
3421
3578
3726
3388
3554
3732
3413
3588
3661
3387
3517
3663
3351
3505
3661
3375
3517
3670
3378
3523
3674
3319
3475
3603
3334
3451
3635
3313
3442
3612
3293
3450
3595
3.87
4.07
4.21
3.78
3.96
4.13
3.62
3.73
3.92
3.29
3.51
3.64
3.23
3.40
3.56
3.06
3.17
3.38
3.08
3.25
3.42
3.02
3.18
3.35
2.87
3.03
3.19
2.93
3.11
3.18
2.86
2.97
3.11
2.71
2.84
2.98
2.52
2.66
2.80
2.48
2.61
2.75
2.36
2.49
2.57
2.41
2.51
2.68
2.35
2.47
2.63
2.25
2.37
2.49
TEA : Entering air temperature (dry bulb/wet bulb).
TSE : Leaving water temperature.
Pt : Total cooling capacity.
Ps : Sensible cooling capacity.
Pabs : Compressor power input.
CR : Total heat rejection.
14
Heating Performance Data - CW-AR 12
Nominal airflow 460 m3/h - Medium Speed
Entering
Water Temp.
(°C)
Water
Water flow Pressure
Drop
(l/s)
(kPa)
0.171
12.0
0.128
6.8
0.171
12.0
0.128
6.8
0.086
3.0
0.171
12.0
0.128
6.8
0.086
3.0
0.171
12.0
0.128
6.8
0.086
3.0
0.171
12.0
0.128
6.8
0.086
3.0
0.171
12.0
0.128
6.8
0.086
3.0
13
16
20
27
30
32
Heating mode
TEA (°C)
Pc (W)
Pabs (W)
CA (W)
COP
16
20
27
16
20
27
16
20
27
16
20
27
16
20
27
16
20
27
16
20
27
16
20
27
16
20
27
16
20
27
16
20
27
16
20
27
16
20
27
16
20
27
16
20
27
16
20
27
16
20
27
2861
2667
2916
2589
2567
2535
2922
2960
3023
2801
2813
2739
2656
2641
2612
3190
3156
3110
3098
3068
3020
2939
2905
2667
3759
3718
3649
3641
3606
3540
3425
3387
3352
4012
3964
3884
3895
3842
3770
3659
3615
3555
4184
4133
4046
4036
3998
3925
3803
3777
3689
811
876
998
763
814
914
815
881
1016
795
896
958
774
829
931
844
905
1021
833
891
1006
812
870
981
882
954
1088
878
948
1076
865
929
1054
890
964
1105
890
960
1097
878
946
1079
888
966
1112
890
966
1105
887
958
1092
2051
1791
1918
1826
1753
1621
2107
2079
2007
2006
1917
1781
1882
1813
1681
2346
2251
2089
2265
2176
2014
2127
2036
1686
2877
2765
2561
2764
2658
2465
2559
2458
2298
3122
3000
2779
3005
2882
2673
2782
2669
2476
3296
3167
2934
3146
3032
2820
2917
2819
2596
3.53
3.04
2.92
3.39
3.15
2.77
3.59
3.36
2.98
3.52
3.14
2.86
3.43
3.19
2.81
3.78
3.49
3.05
3.72
3.44
3.00
3.62
3.34
2.72
4.26
3.90
3.35
4.15
3.81
3.29
3.96
3.64
3.18
4.51
4.11
3.52
4.38
4.00
3.44
4.17
3.82
3.30
4.71
4.28
3.64
4.54
4.14
3.55
4.29
3.94
3.38
TEA : Entering air temperature.
Pc: Heating capacity.
Pabs : Compressor power input.
CA : Total heat absorption.
15
Dimensions - CW-AR CAR with Feet
251
105
716
1138
16
Dimensions - CW-AR CAR with Front Air Intake
251
716
720 mini
750 maxi
1138
17
Dimensions - CW-AR CARB Low Height with Feet
251
105
683
578
1323
18
Dimensions - CW-AR CARB Low Height with Front Air Intake
251
580 mini
610 maxi
1323
19
Dimensions - CW-AR NU with Feet
40.5
1005
40.50
24
92
105
624
769
522
142.5
229
54
530
20
Dimensions - CW-AR NU with Front Air Intake
502
525 mini
555 maxi
142.50
229
1005
24
92
38.50
54
530
21
Dimensions - CW-AR NUB Low Height with Feet
229
1005
139
105
624
522
40.5
18
100
1183
54
530
22
Dimensions - CW-AR NUB Low Height with Front Air Intake
229
38.50
1144
100
18
138.50
502
525 mini
555 maxi
1005
54
530
23
Systemair Airwell SAS · route de Verneuil, 27570 Tillières-sur- Avre · Tél. 02 32 60 61 00 · Fax 02 32 32 55 13
september 2014
Systemair · EDM CWAR-S-1GB/09.14
As part of our ongoing product improvement programme, our products are subject to change without prior notice. Non contractual photos.
www.systemair.fr