Levitor II Air Cooled Condenser

Transcription

Levitor II Air Cooled Condenser
Levitor II
AIR COOLED CONDENSER AND FLUID COOLER
Technical Bulletin
Products that provide lasting solutions.
Levitor II Air Cooled Condenser
Table of Contents
Benefits and Features
1
System Selection
2
Levitor Application
3
Model Key
4
LAVE/LEVE Condenser Performance Data, One and Two Fans Wide
5
LAVA/LEVA Condenser Performance Data, One and Two Fans Wide
7
LAVC/LEVC Condenser Performance Data, One and Two Fans Wide
9
LAVF/LEVF Condenser Performance Data, One and Two Fans Wide
11
Dimensional Drawings
13
LAVB Condenser Performance Data, One and Two Fans Wide
14
Dimensional and Electrical Data
15
Control Panel Nomenclature
16
Standard Fan Cycling/Control Arrangements
17
Low Ambient Controls
18
Fan Cycling Sequence
18
Mounted Receivers
19
Mounted Receiver Diagrams
20
Wiring Diagram
22
Replacement Parts
23
LEVITOR II AIR COOLED CONDENSER
Specifications subject to change without notice.
Levitor II Air Cooled Condenser
Benefits and Features
The LEVITOR system addresses refrigerant coil wear
and leaks due to vibration and thermal stress.
Rooftop condensers have to operate in some of the
toughest conditions imaginable. Temperature extremes
result in constant expansion and contraction of refrigerant
tubes as fans cycle and loads vary.
The consequences are costly: rapid tube wear results in
leaks, system breakdown and loss of costly refrigerant.
LEVITOR Coil Design Eliminates Refrigerant Tube Wear
Environmental concerns and spiraling cost of refrigerants have led to
the development of direct drive remote air-cooled condensers with the
LEVITOR coil support system. This innovative design uses dedicated
stainless steel tubes and a unique coil support system to isolate
refrigerant tubes from the unit. Coil support is transferred from the fins
to the stainless tubes and truncated tube plates which ride freely in “C”
channels. Tubes expand and contract without interference. The result,
contact and friction wear are eliminated.
Quiet by Design
LEVITOR coil design does more than just eliminate tube wear. Sound
reduction is an added benefit. Unlike traditional air-cooled condensers,
fan and coil vibration are isolated from the cabinet, so it is not
transmitted to the unit frame and building supports.
Low Sound Quietor Fan
n The “swept-wing” blade design offers lower noise levels at
the same fan speed. For example, the QUIETOR fan blade
on a 575-rpm motor will be much quieter (8 dBA) than the
old 575-rpm fan.
n Lower noise condensers can translate into savings for your
customer by minimizing the need of costly noise barriers.
n Quietor fan not available on 18” models.
Exclusive 3-year Limited Warranty
n We’re so confident about our new suspended coil
design that it is protected by a 3-year limited warranty
on workmanship and material. It gives you extra
protection from premature tube wear. See
www.krack.ingersollrand.com for complete warranty.
Computerized Circuiting
Our computerized coil circuiting program is designed to
minimize the condenser refrigerant charge and maximize
subcooling. Every condenser will be custom circuited to
precisely meet your application needs.
n
Modular Design
Arranged for vertical or horizontal air discharge.
Multi-fan sections compartmented to allow individual fan
cycling while preventing off-fan “windmilling”. Large
clean-out access doors standard.
n
Corrosion Resistant
All models employ mill galvanized steel fan sections and
coil side baffles. Legs are heavy gauge mill galvanized steel.
n
High Efficiency Coil
Copper tubes are mechanically expanded into
corrugated full collared aluminum fins spaced 8, 10
or 12 per inch. Coils are helium leak and pressure
tested with 400 psig. dry air, shipped pressurized
with dry nitrogen.
n Optional fin materials are copper, heresite, electrofin
or polyester coated aluminum. Multi-circuited coils are
available. Liquid subcooling circuits are available.
n
Direct Driven Propeller Fans
n Quiet multi-bladed propeller fans provide uniform air
distribution through the coil. Venturi fan orifices
optimize efficiency.
Weather Resistant Fan Motors
n Outdoor condenser motors designed with ball bearings
inherent overheat protection in each phase; shaft
slingers; enclosure, hardware, and lubrication for all
weather conditions. Each motor lead is wired to
terminals in an electrical enclosure.
Versatile Fan Cycling Control Methods
n Temperature fan cycling.
n Pressure fan cycling.
n Temperature and pressure fan cycling.
n Electronic relay boards.
n Variable speed header end fans.
n Inverter ready motors.
US
LEVITOR II AIR COOLED CONDENSER
Specifications subject to change without notice.
1
Levitor II Air Cooled Condenser
System Selection
THR Total Heat of Rejection
n Condenser total heat of rejection (BTU/h) is the sum of the evaporator refrigeration effect and the heat
of compression which varies with compressor type and operating conditions.
TABLE 1
THR Calculation Method
n THR = Open Reciprocating Compressor Capacity
(BTU/h) + (2545 x BHP)
n THR = Suction Gas Cooled Hermetic Reciprocating
Compressor Capacity (BTU/h) + (3413 x kW)
EVAPORATOR
TEMP (˚F)
THR Estimated Method
THR may be estimated by multiplying the rated
compressor BTU/h capacity by the compressor
operating condition factor shown in Table 1 or 2.
Multiply result by altitude factor when applicable.
n
TABLE 2
EVAPORATOR
TEMP (˚F)
-30
-20
-10
0
10
20
30
40
50
OPEN COMPRESSOR
CONDENSING TEMPERATURE (˚F)
90
100
110
120
130
140
1.37
1.33
1.28
1.24
1.21
1.17
1.14
1.12
1.09
1.42
1.37
1.32
1.28
1.24
1.20
1.17
1.15
1.12
1.47
1.42
1.37
1.32
1.28
1.24
1.20
1.17
1.14
*
1.47
1.42
1.37
1.32
1.28
1.24
1.20
1.17
*
*
1.47
1.41
1.36
1.32
1.27
1.23
1.20
*
*
*
1.47
1.42
1.37
1.32
1.28
1.24
-40
-30
-20
-10
0
5
10
15
20
25
30
40
50
HERMETIC COMPRESSOR
CONDENSING TEMPERATURE (˚F)
90
100
110
120
130
140
1.66
1.57
1.49
1.42
1.36
1.33
1.31
1.28
1.26
1.24
1.22
1.18
1.14
1.73
1.62
1.53
1.46
1.40
1.37
1.34
1.32
1.29
1.27
1.25
1.21
1.17
1.80
1.68
1.58
1.50
1.44
1.41
1.38
1.35
1.33
1.31
1.28
1.24
1.20
2.00
1.80
1.65
1.57
1.50
1.46
1.43
1.40
1.37
1.35
1.32
1.27
1.23
*
*
*
1.64
1.56
1.52
1.49
1.46
1.43
1.40
1.37
1.31
1.26
*
*
*
*
1.62
1.59
1.55
1.52
1.49
1.45
1.42
1.35
1.29
*Beyond the normal limits for single stage compressor application.
TABLE 3
FEET
1,000
2,000
3,000
4,000
ALTITUDE
FACTOR
FEET
1.02
1.05
1.07
1.10
5,000
6,000
7,000
8,000
FACTOR
1.12
1.15
1.17
1.24
*Beyond the normal limits for single stage compressor application.
Multi-Circuit Selection
n Condenser coils may be divided into several individual refrigeration circuits or systems; each sized for a specific refrigerant,
THR capacity and TD. Systems are tagged for identification from left to right; facing the connection end. Avoid locating
high TD sections next to low TD sections. Add excess circuits to low TD sections next to High TD sections. Add excess
circuits to outboard sections. Thermal Fantrol fan cycling is recommended with multi-circuited condensers.
SAMPLE CALCuLATIOn: 95°F AMBIEnT-SuCTIOn COOLED SEMI-HERMETIC RECIPROCATInG COMPRESSORS
COMP
NOM
HP
6
9
10
12
DESIGN
TD
REF °F
134a 15
404A 10
404A 10
22 15
Selection
BASED ON R-22 AT 15°FTD
COMPRESSOR RATING
SYSTEM ACTUAL
CAP
SAT SAT
SELECT PER CIRCUIT # NUMBER TD
TD
REF
TOTAL
SUCT COND NET MOTOR
THR CIRCUIT REQ’D CIR L TO R
°F BTU/h kW BTU BTU/h FACTOR FACTOR
°F
°F
4.3
4
1
110 40090 4.3 14676 54,766 ÷ 0.95 x 1.0 = 57648 13503
+20
16.1
8.3
10
2
105 45900 8.1 27645 73,545 ÷ 0.98 x 1.5 = 112569 13503
-20
8.3
9.5
10
3
105 50640 9.6 32765 83,405 ÷ 0.98 x 1.5 = 127661 13503
-20
9.5
10
4
110 104000 9.7 33106 137,106 ÷ 1.00 x 1.0 = 137106 13503 10.1
+20
15.1
34
UNIT THR REQ’D 434984
n
LAVA-15310 Rated at THR of 459.1 MBH with R-22 at 15°F TD.
LAVA-15310 Unit lists 34 Circuits.
n
Sample Calculation: THR Req’d./Circuit = 434984 ÷ 34 = 12784.
LAVA-15310 = 459100 ÷ 34 = 13503 (Available THR/Circuit).
n
Circuits Req’d. = Select THR ÷ THR/Circuit. Example: 57648 ÷ 13503 = 4.3 Circuits.
n
Assign Number of Circuits System and System Number Left to Right.
Actual TD = (Circuits Req’d ÷ Assign Circuits) x Design TD.
Example: 4.3 ÷ 4 x 15 = 16.1.
REF FACTOR
R-22- 1.00
* R-134a- 0.95
**R-404A- 0.98
*Usable for R-12
**Usable for R-502, R-507
TD FACTOR
10°F-1.50
15°F-1.00
20°F-0.75
25°F-0.60
Levitor II Air Cooled Condenser
Levitor Application
Locate Condensers no closer than their width from walls
or other condensers. Avoid locations near exhaust fans,
plumbing vents, flues or chimneys.
Gravity Liquid Drain Lines should drop from each
outlet as low as possible before headering or running
horizontally. Pitch downhill to receiver.
Parallel Condensers should be the same models resulting
in the same refrigerant side pressure drops. Compressor
discharge lines should have equal pressure drops to each
condenser.
Off-Line Coil Sections will have refrigerant pressures
corresponding to the ambient. Check valves or isolating
valves should be installed in the liquid line drains to
prevent refrigerant migration and receiver pressure loss.
Condenser Charge will approximate 30% of the
maximum flooding charge listed under “Specifications” for
summer design conditions. Low ambient head pressure
controls require an additional charge, which is difficult to
predict with fan cycling and is maximized with holdback.
Liquid Subcooling may be accomplished with a section
of circuits in the coil. Liquid outlet temperature will
approach the entering air temperature by approximately
5°F. Benefit is not economical unless TD is 15°F or
higher.
Receiver Capacity should be sized to store condenser
summer charge, plus the condenser low ambient
allowance, plus the evaporator charge, plus an allowance
for piping and heat reclaim coil charges.
See Installation & Operating instructions for piping,
holdback and fan cycling details.
Compressor Discharge lines should be sized to minimize
pressure drops and maintain oil return gas velocities. Each
connection should be looped to the top of the condenser.
REFRIGERAnT LInE CAPACITY DATA
COPPER
LINE
SIZE
O.D.
5/8
7/8
1-1/8
1-3/8
1-5/8
2-1/8
2-5/8
n
n
n
LINE CAPACITY IN TONS
CONDENSER TO RECEIVER
COMPRESSOR DISCHARGE LINE
LIQUID LINE 100'
LBS. OF REFRIGERANT
LIQUID PER 100'
OF LENGTH
R-22
R-404A
R-134A
R-22
R-404A
R-134A
R-22
R-404A
R-134A
1.0
3.0
6.5
15.0
20.0
45.0
75.0
0.5
2.0
4.5
7.0
15.0
30.0
45.0
0.5
2.0
4.5
7.0
11.0
28.0
43.0
3.6
7.4
12.7
19.2
29.0
47.0
73.0
3.0
6.0
10.4
16.0
23.0
40.0
62.0
3.7
7.7
13.0
20.0
28.5
46.0
72.0
13.0
25.0
42.0
64.0
90.0
160.0
245.0
11.0
22.0
36.0
55.0
78.0
138.0
212.0
13.0
26.0
43.0
65.0
92.0
163.0
250.0
Capacity is compressor suction tons for application between -40°F and +40°F suction at condensing
temperatures between 80°F and 120°F sat.
For multiple or unloading compressor applications, the vertical discharge riser from the compressor
may need to be one size smaller.
This table data is only to be used as a guide. For exact values, please calculate to your specific job line
lengths and design pressure/temp values using ASHRAE handbook or ARI refrigerant tables.
LEVITOR II AIR COOLED CONDENSER
Specifications subject to change without notice.
3
Levitor II Air Cooled Condenser
Model Key
L
A
V
A
UNIT TYPE:
L = Levitor Condenser
F = Fluid Cooler
TUBE DIAMETER:
A = 3/8 O.D.
E = 1/2 O.D.
FAN DISCHARGE DIRECTIONS:
H = Horizontal
V = Vertical
X = Hinged Vertical*
E = Hinged Horizontal*
FAN / MOTOR COMBINATION:
A = 1 HP 850 RPM 30"
B = 1/2 HP 1140 RPM 24"
C = 1-1/2 HP 850 RPM 30"
E = 1/2 HP 575 RPM 30"
F = 1-1/2 HP 1140 RPM 30"
FANS WIDE: 1, 2
NOTE:
* Levitor only.
** B units only.
4
LEVITOR II AIR COOLED CONDENSER
Specifications subject to change without notice.
1
2
4
10
M
VOLTAGE:
A = 230/1/60**
K = 208-230/3/60
M = 460/3/60
P = 575/3/60
U = 380/3/50
FIN SPACING:
08 = 8 FPI
10 = 10 FPI
12 = 12 FPI
ROWS DEEP:
2
3
4
FANS IN LINE:
1
2
3
4
5
6
7 = 24" Fan Only
Levitor II Air Cooled Condenser
LAVE/LEVE Performance Data
1/2 H.P. 575 RPM - OnE FAn WIDE
TOTAL HEAT OF REJECTION (MBH)
R-22
R-404A, R-507
TEMPERATURE DIFFERENCE
TEMPERATURE DIFFERENCE
MODEL
LAVE
LAVE
LAVE
LAVE
LAVE
LAVE
LAVE
LAVE
LAVE
LAVE
LAVE
LAVE
LAVE
LAVE
LAVE
LAVE
LAVE
LAVE
LAVE
LAVE
LAVE
LAVE
LAVE
LAVE
LAVE
LAVE
LAVE
LAVE
LAVE
LAVE
LAVE
LAVE
LAVE
LAVE
LAVE
LAVE
LAVE
LAVE
LEVE
LEVE
LEVE
LEVE
LEVE
LEVE
112 08
112 10
112 12
113 08
113 10
113 12
114 08
114 10
114 12
122 08
122 10
122 12
123 08
123 10
123 12
124 08
124 10
124 12
132 10
132 12
133 08
133 10
133 12
134 08
134 10
134 12
143 08
143 10
143 12
144 08
144 10
144 12
153 08
153 10
153 12
154 08
154 10
154 12
163 08
163 10
163 12
164 08
164 10
164 12
10°F
33.2
37.2
40.4
43.8
47.9
50.6
53.1
55.9
58.1
66.5
74.4
80.9
87.5
95.8
101.2
106.3
111.7
116.3
111.5
121.3
138.1
143.6
152.0
159.6
167.6
174.7
174.8
191.5
202.4
212.5
223.4
233.1
231.9
254.0
270.3
270.9
289.8
300.3
278.4
304.9
324.5
325.1
347.8
360.4
15°F
49.8
55.8
60.6
65.7
71.8
75.9
79.6
83.8
87.1
99.7
111.6
121.3
131.2
143.7
151.8
159.4
167.5
174.4
167.2
181.9
207.1
215.4
228.0
239.4
251.4
262.0
262.2
287.2
303.6
318.7
335.1
349.6
347.8
381.0
405.4
406.3
434.7
450.4
417.6
457.3
486.7
487.6
521.7
540.6
20°F
66.4
74.4
80.8
87.6
95.8
101.2
106.2
111.8
116.2
133.0
148.8
161.8
175.0
191.6
202.4
212.6
223.4
232.6
223.0
242.6
276.2
287.2
304.0
319.2
335.2
349.4
349.6
383.0
404.8
425.0
446.8
466.2
463.8
508.0
540.6
541.8
579.6
600.6
556.8
609.8
649.0
650.2
695.6
720.8
25°F
83.0
93.0
101.0
109.5
119.7
126.5
132.7
139.7
145.2
166.2
186.0
202.2
218.7
239.5
253.0
265.7
279.2
290.7
278.7
303.5
345.2
359.0
380.0
399.0
419.0
436.7
437.0
478.7
506.0
531.2
558.5
582.7
579.7
635.0
675.7
677.2
724.5
750.7
696.0
762.2
811.2
812.7
869.5
901.0
10°F
32.3
36.2
39.3
42.6
46.6
47.2
51.7
54.4
56.6
64.7
72.3
78.7
85.1
93.2
98.4
103.4
108.7
113.2
108.5
118.0
134.3
139.8
147.9
155.3
163.0
170.0
170.0
186.3
197.0
206.8
217.4
226.8
225.6
247.1
263.0
263.6
282.0
292.2
270.8
296.6
315.7
316.3
338.4
350.6
15°F
48.4
54.3
58.9
63.9
69.9
70.8
77.5
81.6
84.9
97.0
108.4
118.0
127.6
139.8
147.6
155.1
163.0
169.8
162.7
177.0
201.4
209.7
221.8
232.9
244.5
255.0
255.0
279.4
295.5
310.2
326.1
340.2
338.4
370.6
394.5
395.4
423.0
438.3
406.2
444.9
473.5
474.4
507.6
525.9
20°F
64.6
72.4
78.6
85.2
93.2
94.4
103.4
108.8
113.2
129.4
144.6
157.4
170.2
186.4
196.8
206.8
217.4
226.4
217.0
236.0
268.6
279.6
295.8
310.6
326.0
340.0
340.0
372.6
394.0
413.6
434.8
453.6
451.2
494.2
526.0
527.2
564.0
584.4
541.6
593.2
631.4
632.6
676.8
701.2
25°F
80.7
90.5
98.2
106.5
116.5
118.0
129.2
136.0
141.5
161.7
180.7
196.7
212.7
233.0
246.0
258.5
271.7
283.0
271.2
295.0
335.7
349.5
369.7
388.2
407.5
425.0
425.0
465.7
492.5
517.0
543.5
567.0
564.0
617.7
657.5
659.0
705.0
730.5
677.0
741.5
789.2
790.7
846.0
876.5
AIR
FLOW
(CFM)
6480
6420
6360
6300
6200
6100
6105
5975
5835
12960
12840
12720
12600
12400
12200
12260
11950
11670
19260
19080
18900
18600
18300
18315
17925
17505
25200
24800
24400
24420
23900
23340
31500
31000
30500
30525
28875
29175
37800
37200
36600
36630
35850
35010
EST
CONDENSER
CHARGE R-404A SOUND SHIP
WEIGHT AVAIL
(LBS)
10’
(LBS) CIRCUITS
SUMMER WINTER (dBA)
5
5
5
7
7
7
8
8
8
9
9
9
12
12
12
15
15
15
14
14
18
18
18
23
23
23
23
23
23
29
29
29
27
27
27
35
35
35
58
58
58
75
75
75
17
17
17
24
24
24
31
31
31
31
31
31
45
45
45
58
58
58
46
46
67
67
67
87
87
87
87
87
87
114
114
114
107
107
107
141
141
141
235
235
235
310
310
310
52
52
52
52
52
52
52
52
52
55
55
55
55
55
55
55
55
55
57
57
57
57
57
57
57
57
58
58
58
58
58
58
59
59
59
59
59
59
60
60
60
60
60
60
437
439
444
466
469
478
495
499
508
718
721
729
773
779
792
830
838
855
1041
1060
1126
1135
1153
1210
1223
1247
1437
1449
1474
1550
1566
1599
2020
2035
2066
2160
2181
2222
2554
2573
2610
2784
2808
2858
34
34
34
34
34
34
34
34
34
34
34
34
34
34
34
34
34
34
34
34
34
34
34
34
34
34
34
34
34
34
34
34
34
34
34
34
34
34
34
34
34
34
34
34
NOTE: Ratings are based on 85°F-115°F entering air temperature. The temperature difference is between the saturated condensing temp. and the entering air temp.
to the condenser. Multiply R-22 rating by 0.95 for R-134a. Summer charge based on 25% of condenser volume with 86°F liquid. Multiply by 1.14 for R-22.
Winter charge based on 90% of condenser volume with -20°F liquid. Multiply by 1.10 for R-22.
Levitor II Air Cooled Condenser
LAVE/LEVE Performance Data
1/2 H.P. 575 RPM - TWO FAnS WIDE
TOTAL HEAT OF REJECTION (MBH)
R-22
R-404A, R-507
TEMPERATURE DIFFERENCE
TEMPERATURE DIFFERENCE
MODEL
LAVE
LAVE
LAVE
LAVE
LAVE
LAVE
LAVE
LAVE
LAVE
LAVE
LAVE
LAVE
LAVE
LAVE
LAVE
LAVE
LAVE
LAVE
LAVE
LAVE
LAVE
LAVE
LAVE
LAVE
LAVE
LAVE
LAVE
LAVE
LAVE
LEVE
LEVE
LEVE
LEVE
LEVE
LEVE
222 08
222 10
222 12
223 08
223 10
223 12
224 08
224 10
224 12
232 10
232 12
233 08
233 10
233 12
234 08
234 10
234 12
243 08
243 10
243 12
244 08
244 10
244 12
253 08
253 10
253 12
254 08
254 10
254 12
263 08
263 10
263 12
264 08
264 10
264 12
10°F
133.0
148.8
161.8
175.0
191.6
202.4
212.6
223.4
232.6
223.0
242.6
276.2
287.2
304.0
319.2
335.2
349.4
349.6
383.0
404.8
425.0
446.8
466.2
463.8
508.0
540.6
541.8
579.6
600.6
556.8
609.8
649.0
650.2
695.6
720.8
15°F
199.5
223.2
242.7
262.5
287.4
303.6
318.9
335.1
348.9
334.5
363.9
414.3
430.8
456.0
478.8
502.8
524.1
524.4
574.5
607.2
637.5
670.2
699.3
695.7
762.0
810.9
812.7
869.4
900.9
835.2
914.7
973.5
975.3
1043.4
1081.2
NOTE: Ratings are based on
85°F-115°F entering air
temperature. The temperature
difference is between the
saturated condensing temp. and
the entering air temp. to the
condenser. Multiply R-22 rating
by 0.95 for R-134a. Summer
charge based on 25% of
condenser volume with 86°F
liquid. Multiply by 1.14 for R22.Winter charge based on 90%
of condenser volume with -20°F
liquid. Multiply by 1.10 for R-22.
20°F
266.0
297.6
323.6
350.0
383.2
404.8
425.2
446.8
465.2
446.0
485.2
552.4
574.4
608.0
638.4
670.4
698.8
699.2
766.0
809.6
850.0
893.6
932.4
927.6
1016.0
1081.2
1083.6
1159.2
1201.2
1113.6
1219.6
1298.0
1300.4
1391.2
1441.6
25°F
332.5
372.0
404.5
437.5
479.0
506.0
531.5
558.5
581.5
557.5
606.5
690.5
718.0
760.0
798.0
838.0
873.5
874.0
957.5
1012.0
1062.5
1117.0
1165.5
1159.5
1270.0
1351.5
1354.5
1449.0
1501.5
1392.0
1524.5
1622.5
1625.5
1739.0
1802.0
10°F
129.4
144.6
157.4
170.2
186.4
196.8
206.8
217.4
226.4
217.0
236.0
268.6
279.6
295.8
310.6
326.0
340.0
340.0
372.6
394.0
413.6
434.8
453.6
451.2
494.2
526.0
527.2
564.0
584.4
541.6
593.2
631.4
632.6
676.8
701.2
15°F
194.1
216.9
236.1
255.3
279.6
295.2
310.2
326.1
339.6
325.5
354.0
402.9
419.4
443.7
465.9
489.0
510.0
510.0
558.9
591.0
620.4
652.2
680.4
676.8
741.3
789.0
790.8
846.0
876.6
812.4
889.8
947.1
948.9
1015.2
1051.8
20°F
258.8
289.2
314.8
340.4
372.8
393.6
413.6
434.8
452.8
434.0
472.0
537.2
559.2
591.6
621.2
652.0
680.0
680.0
745.2
788.0
827.2
869.6
907.2
902.4
988.4
1052.0
1054.4
1128.0
1168.8
1083.2
1186.4
1262.8
1265.2
1353.6
1402.4
25°F
323.5
361.5
393.5
425.5
466.0
492.0
517.0
543.5
566.0
542.5
590.0
671.5
699.0
739.5
776.5
815.0
850.0
850.0
931.5
985.0
1034.0
1087.0
1134.0
1128.0
1235.5
1315.0
1318.0
1410.0
1461.0
1354.0
1483.0
1578.5
1581.5
1692.0
1753.0
ELECTRICAL DATA - OnE FAn WIDE
FAN MOTOR TOTAL FULL LOAD AMPS
208/230/3/60 460/3/60 575/3/60
LAVE-11***
LAVE-12***
LAVE-13***
LAVE-14***
LAVE-15***
LEVE-16***
3.4
6.8
10.2
13.6
17.0
20.4
1.7
3.4
5.1
6.8
8.5
10.2
1.2
2.4
3.6
4.8
6.0
7.2
***Rows & FPI (1) Minimum Unit Circuit Amps = 1.25 x FLA of One
Motor + FLA of All Remaining Motors. (2) Maximum Unit Overload
Protection = 2.25 x FLA of One Motor + FLA of All Remaining Motors.
AIR
FLOW
(CFM)
25920
25680
25440
25200
24800
24400
24420
23900
23340
38520
38160
37800
37200
36600
36630
35950
35010
50400
49600
48800
48840
47800
46680
63000
62000
61000
61050
59750
58350
75600
74400
73200
73260
71700
70020
EST
SHIP
SOUND
WEIGHT AVAIL
10’
(LBS) CIRCUITS
SUMMER WINTER (dBA)
1311
58
18
62
68
1320
58
18
62
68
1336
58
18
62
68
1437
58
24
89
68
1425
58
24
89
68
1462
58
24
89
68
1539
58
30
117
68
1555
58
30
117
68
1588
58
30
117
68
1875
60
27
93
68
1912
60
27
93
68
2044
60
37
134
68
2063
60
37
134
68
2100
60
37
134
68
2214
60
46
174
68
2238
60
46
174
68
2287
60
46
174
68
2526
61
46
174
68
2651
61
46
174
68
2700
61
46
174
68
2851
61
58
228
68
2884
61
58
228
68
2950
61
58
228
68
3725
62
55
214
68
3755
62
55
214
68
3817
62
55
214
68
4005
62
70
281
68
4046
62
70
281
68
4129
62
70
281
68
4759
63
116
469
68
4796
63
116
469
68
4870
63
116
469
68
5218
63
150
620
68
5268
63
150
620
68
5366
63
150
620
68
CONDENSER
CHARGE R-404A
(LBS)
ELECTRICAL DATA - TWO FAnS WIDE
FAN MOTOR TOTAL FULL LOAD AMPS
208/230/3/60 460/3/60 575/3/60
LAVE-22***
LAVE-23***
LAVE-24***
LAVE-25***
LEVE-26***
13.6
20.4
27.2
34.0
40.8
6.8
10.2
13.6
17.0
20.4
4.8
7.2
9.6
12.0
14.4
Levitor II Air Cooled Condenser
LAVA/LEVA Performance Data
1 H.P. 850 RPM - OnE FAn WIDE
TOTAL HEAT OF REJECTION (MBH)
R-22
R-404A, R-507
TEMPERATURE DIFFERENCE
TEMPERATURE DIFFERENCE
MODEL
LAVA
LAVA
LAVA
LAVA
LAVA
LAVA
LAVA
LAVA
LAVA
LAVA
LAVA
LAVA
LAVA
LAVA
LAVA
LAVA
LAVA
LAVA
LAVA
LAVA
LAVA
LAVA
LAVA
LAVA
LAVA
LAVA
LAVA
LAVA
LAVA
LAVA
LAVA
LAVA
LAVA
LAVA
LAVA
LAVA
LAVA
LAVA
LEVA
LEVA
LEVA
LEVA
LEVA
LEVA
112 08
112 10
112 12
113 08
113 10
113 12
114 08
114 10
114 12
122 08
122 10
122 12
123 08
123 10
123 12
124 08
124 10
124 12
132 10
132 12
133 08
133 10
133 12
134 08
134 10
134 12
143 08
143 10
143 12
144 08
144 10
144 12
153 08
153 10
153 12
154 08
154 10
154 12
163 08
163 10
163 12
164 08
164 10
164 12
10°F
42.4
47.5
51.7
56.0
61.2
65.3
65.3
69.7
72.3
85.0
95.1
103.4
111.8
122.4
130.3
130.5
139.4
144.6
142.6
155.1
176.6
183.6
195.4
195.8
209.1
217.0
223.6
244.9
260.6
261.1
278.8
289.2
279.5
306.1
325.7
326.4
348.5
361.5
335.3
367.3
390.9
391.6
418.2
433.8
15°F
63.7
71.3
77.6
83.8
91.8
97.7
97.9
104.8
108.5
127.3
142.6
155.1
183.7
183.6
195.4
195.8
209.1
216.9
213.9
232.7
251.5
275.5
293.1
293.7
313.7
325.4
335.3
367.3
390.3
391.6
418.2
433.8
419.2
459.1
488.6
489.6
522.8
542.5
509.2
550.9
586.3
587.4
627.3
650.7
20°F
84.9
95.1
103.4
111.8
122.4
130.3
130.5
139.4
144.6
169.8
190.2
206.8
223.6
244.9
260.6
261.1
278.8
289.2
285.3
310.3
335.3
367.3
390.9
391.6
418.2
433.8
447.1
489.7
521.1
522.2
557.7
578.4
588.9
612.2
651.4
652.7
697.1
723.0
670.7
734.6
781.7
783.3
836.5
867.6
25°F
106.1
118.9
129.3
139.7
153.0
162.9
163.2
174.3
180.8
212.2
237.7
258.6
279.5
306.1
325.7
326.4
348.5
361.5
356.6
387.8
419.2
459.1
488.6
489.6
522.8
542.3
588.9
612.2
651.4
652.7
697.1
723.0
698.6
765.2
814.3
815.9
871.3
903.8
838.4
918.2
977.1
979.1
1045.6
1084.5
10°F
41.6
48.6
50.7
54.9
60.0
64.0
64.0
68.3
70.9
83.3
93.2
101.3
109.6
120.0
127.7
127.9
136.6
141.7
139.7
152.0
173.1
179.9
191.5
191.9
204.9
212.7
219.1
240.0
255.4
255.9
273.2
283.4
273.0
300.0
319.2
319.9
341.5
354.3
328.6
360.0
383.1
383.8
409.8
425.1
15°F
62.4
69.9
76.0
82.1
90.0
95.7
95.9
102.7
106.3
124.8
139.7
152.0
180.0
179.9
191.5
191.9
204.9
212.6
209.6
228.0
246.5
270.0
287.2
287.8
307.4
318.9
328.6
360.0
382.5
383.8
409.8
425.1
410.8
449.9
478.8
479.8
512.3
531.5
492.9
539.9
574.6
575.8
614.9
637.7
20°F
83.2
93.2
101.3
109.6
120.0
127.7
127.9
136.6
141.7
166.4
186.4
202.7
219.1
240.0
255.4
255.9
273.2
283.4
279.6
304.1
328.6
360.0
383.1
383.8
409.8
425.1
438.2
479.9
510.7
511.8
546.5
566.8
547.7
600.0
638.4
639.6
683.2
708.5
657.3
719.9
766.1
767.6
819.8
850.2
25°F
104.0
116.5
126.7
136.9
149.9
159.6
159.9
170.8
177.2
208.0
232.9
253.4
273.9
300.0
319.2
319.9
341.5
354.3
349.5
380.0
410.8
449.9
478.8
479.8
512.3
531.5
547.7
600.0
638.4
639.6
683.2
708.5
684.6
749.9
798.0
799.6
853.9
885.7
821.6
899.8
957.6
959.5
1024.7
1062.8
AIR
FLOW
(CFM)
9260
9151
9040
8933
8760
8574
8582
8314
8025
18520
18302
18080
17866
17520
17148
17164
16628
16050
27453
27120
26799
26280
25722
25746
24942
24075
35732
35040
34296
34328
33256
32100
44665
43800
42870
42910
41570
40125
53598
52560
51444
51492
49884
48150
EST
CONDENSER
CHARGE R-404A SOUND SHIP
WEIGHT AVAIL
(LBS)
10’
(LBS) CIRCUITS
SUMMER WINTER (dBA)
5
5
5
7
7
7
8
8
8
9
9
9
12
12
12
15
15
15
14
14
18
18
18
23
23
23
23
23
23
29
29
29
27
27
27
35
35
35
58
58
58
75
75
75
17
17
17
24
24
24
31
31
31
31
31
31
45
45
45
58
58
58
46
46
67
67
67
87
87
87
87
87
87
114
114
114
107
107
107
141
141
141
235
235
235
310
310
310
63
63
63
63
63
63
63
63
63
66
66
66
66
66
66
66
66
66
68
68
68
68
68
68
68
68
69
69
69
69
69
69
70
70
70
70
70
70
71
71
71
71
71
71
437
439
444
466
469
478
495
499
508
718
721
729
773
779
792
830
838
855
1041
1060
1126
1135
1153
1210
1223
1247
1437
1449
1474
1550
1566
1599
2020
2035
2066
2160
2181
2222
2554
2573
2610
2784
2808
2858
34
34
34
34
34
34
34
34
34
34
34
34
34
34
34
34
34
34
34
34
34
34
34
34
34
34
34
34
34
34
34
34
34
34
34
34
34
34
34
34
34
34
34
34
NOTE: Ratings are based on 85°F 115°F entering air temperature. The temperature difference is between the saturated condensing temp. and the
entering air temp. to the condenser. Multiply R-22 rating by 0.95 for R-134a. Summer charge based on 25% of condenser volume with 86°F liquid.
Multiply by 1.14 for R-22. Winter charge based on 90% of condenser volume with -20°F liquid. Multiply by 1.10 for R-22.
LEVITOR II AIR COOLED CONDENSER
Specifications subject to change without notice.
7
Levitor II Air Cooled Condenser
LAVA/LEVA Performance Data
1 H.P. 850 RPM - TWO FAnS WIDE
TOTAL HEAT OF REJECTION (MBH)
R-22
R-404A, R-507
TEMPERATURE DIFFERENCE
TEMPERATURE DIFFERENCE
MODEL
LAVA
LAVA
LAVA
LAVA
LAVA
LAVA
LAVA
LAVA
LAVA
LAVA
LAVA
LAVA
LAVA
LAVA
LAVA
LAVA
LAVA
LAVA
LAVA
LAVA
LAVA
LAVA
LAVA
LAVA
LAVA
LAVA
LAVA
LAVA
LAVA
LEVA
LEVA
LEVA
LEVA
LEVA
LEVA
222 08
222 10
222 12
223 08
223 10
223 12
224 08
224 10
224 12
232 10
232 12
233 08
233 10
233 12
234 08
234 10
234 12
243 08
243 10
243 12
244 08
244 10
244 12
253 08
253 10
253 12
254 08
254 10
254 12
263 08
263 10
263 12
264 08
264 10
264 12
10°F
169.8
190.2
206.8
223.6
244.9
260.6
261.1
278.8
289.2
285.3
310.3
335.3
367.3
390.9
391.6
418.2
433.8
447.1
489.7
521.1
522.2
557.6
578.4
558.9
612.2
651.4
652.7
697.1
723.0
670.7
734.6
781.6
783.3
836.5
867.6
15°F
254.7
285.3
310.3
335.3
367.3
390.9
391.6
418.2
433.8
427.9
465.4
503.0
550.9
586.3
587.5
627.4
650.7
670.7
734.6
781.7
783.3
836.5
867.6
838.4
918.2
977.1
979.1
1045.6
1084.5
1006.0
1101.9
1172.6
1174.9
1254.7
1301.5
NOTE: Ratings are based on
85°F-115°F entering air
temperature. The temperature
difference is between the
saturated condensing temp. and
the entering air temp. to the
condenser. Multiply R-22 rating
by 0.95 for R-134a. Summer
charge based on 25% of
condenser volume with 86°F
liquid. Multiply by 1.14 for R22.Winter charge based on 90%
of condenser volume with -20°F
liquid. Multiply by 1.10 for R-22.
20°F
339.6
380.3
413.7
447.1
489.7
521.1
522.2
557.7
578.4
570.5
620.5
670.7
734.6
781.7
783.3
836.5
867.6
894.3
979.4
1042.3
1044.4
1115.3
1156.8
1117.8
1224.3
1302.8
1305.5
1394.1
1446.1
1341.4
1469.2
1563.4
1566.6
1673.0
1735.3
25°F
424.5
475.4
517.1
558.9
612.2
651.4
652.7
697.1
723.0
713.1
775.7
838.4
918.2
977.1
979.1
1045.6
1084.5
1117.8
1224.3
1302.8
1305.5
1394.1
1446.1
1397.3
1530.4
1628.6
1631.9
1742.7
1807.6
1676.7
1836.5
1954.3
1958.2
2091.2
2169.1
10°F
166.4
186.4
202.7
219.1
240.0
255.4
255.9
273.2
283.4
279.6
304.1
328.6
360.0
383.1
383.8
409.8
425.1
438.2
479.9
510.7
511.8
546.4
566.8
547.7
600.0
638.4
639.6
683.2
708.5
657.3
719.9
766.0
767.6
819.8
850.2
15°F
249.6
279.6
304.1
328.6
360.0
383.1
383.8
409.8
425.1
419.3
456.1
492.9
539.9
574.6
575.8
614.9
637.7
657.3
719.9
766.1
767.6
819.8
850.2
821.6
899.8
957.6
959.5
1024.7
1062.8
985.9
1079.9
1149.1
1151.4
1229.6
1275.5
20°F
322.8
372.7
405.4
438.2
479.9
510.7
511.8
546.5
566.8
559.1
608.1
657.3
719.9
766.1
767.6
819.8
850.2
876.4
959.8
1021.5
1023.5
1093.0
1133.7
1095.4
1199.8
1276.7
1279.4
1366.2
1417.2
1314.6
1439.8
1532.1
1535.3
1639.5
1700.6
25°F
416.0
465.9
506.8
547.7
600.0
638.4
639.6
683.2
708.5
698.8
760.2
821.6
899.8
957.6
959.5
1024.7
1062.8
1095.4
1199.8
1276.7
1279.4
1366.2
1417.2
1369.4
1499.8
1596.0
1599.3
1707.8
1771.4
1643.2
1799.8
1915.2
1919.0
2049.4
2125.7
ELECTRICAL DATA - OnE FAn WIDE
FAN MOTOR TOTAL FULL LOAD AMPS
208/230/3/60 460/3/60 575/3/60
LAVA-11***
LAVA-12***
LAVA-13***
LAVA-14***
LAVA-15***
LEVA-16***
4.4
8.8
13.2
17.6
22.0
26.4
2.0
4.0
6.0
8.0
10.0
12.0
1.45
2.9
4.35
5.8
7.25
8.7
***Rows & FPI (1) Minimum Unit Circuit Amps = 1.25 x FLA of One
Motor + FLA of All Remaining Motors. (2) Maximum Unit Overload
Protection = 2.25 x FLA of One Motor + FLA of All Remaining Motors.
AIR
FLOW
(CFM)
37040
36604
36160
35732
35040
34296
34328
33256
32100
54906
54240
53598
52560
51444
51492
49884
48150
71464
70080
68592
68656
66512
64200
89300
87600
85740
85820
83140
80250
107196
105120
102888
102984
99768
96300
EST
CONDENSER
CHARGE R-404A SOUND SHIP
WEIGHT AVAIL
(LBS)
10’
(LBS) CIRCUITS
SUMMER WINTER (dBA)
18
18
18
24
24
24
30
30
30
27
27
37
37
37
46
46
46
46
46
46
58
58
58
55
55
55
70
70
70
116
116
116
150
150
150
62
62
62
89
89
89
117
117
117
93
93
134
134
134
174
174
174
174
174
174
228
228
228
214
214
214
281
281
281
469
469
469
620
620
620
69
69
69
69
69
69
69
69
69
71
71
71
71
71
71
71
71
72
72
72
72
72
72
73
73
73
73
73
73
74
74
74
74
74
74
1311
1320
1336
1437
1425
1462
1539
1555
1588
1875
1912
2044
2063
2100
2214
2238
2287
2526
2651
2700
2851
2884
2950
3725
3755
3817
4005
4046
4129
4759
4796
4870
5218
5268
5366
68
68
68
68
68
68
68
68
68
68
68
68
68
68
68
68
68
68
68
68
68
68
68
68
68
68
68
68
68
68
68
68
68
68
68
ELECTRICAL DATA - TWO FAnS WIDE
FAN MOTOR TOTAL FULL LOAD AMPS
208/230/3/60 460/3/60 575/3/60
LAVA-22***
LAVA-23***
LAVA-24***
LAVA-25***
LEVA-26***
17.6
26.4
35.2
44.0
52.8
8.0
12.0
16.0
20.0
24.0
5.8
8.7
11.6
14.5
17.4
Levitor II Air Cooled Condenser
LAVC/LEVC Performance Data
1-1/2 H.P. 850 RPM - OnE FAn WIDE
TOTAL HEAT OF REJECTION (MBH)
R-22
R-404A, R-507
TEMPERATURE DIFFERENCE
TEMPERATURE DIFFERENCE
MODEL
LAVC 112 08
LAVC 112 10
LAVC 112 12
LAVC 113 08
LAVC 113 10
LAVC 113 12
LAVC 114 08
LAVC 114 10
LAVC 114 12
LAVC 122 08
LAVC 122 10
LAVC 122 12
LAVC 123 08
LAVC 123 10
LAVC 123 12
LAVC 124 08
LAVC 124 10
LAVC 124 12
LAVC 132 10
LAVC 132 12
LAVC 133 08
LAVC 133 10
LAVC 133 12
LAVC 134 08
LAVC 134 10
LAVC 134 12
LAVC 143 08
LAVC 143 10
LAVC 143 12
LAVC 144 08
LAVC 144 10
LAVC 144 12
LAVC 153 08
LAVC 153 10
LAVC 153 12
LAVC 154 08
LAVC 154 10
LAVC 154 12
LEVC 163 08
LEVC 163 10
LEVC 163 12
LEVC 164 08
LEVC 164 10
LEVC 164 12
10°F
46.2
51.5
55.6
60.1
65.3
69.1
69.4
73.7
76.3
92.3
102.9
111.3
120.3
130.7
138.2
138.8
147.3
152.5
154.3
166.9
180.4
196.0
207.3
208.1
221.0
238.7
240.5
261.3
276.3
277.5
294.6
305.0
300.6
326.7
345.5
346.9
368.3
381.3
360.7
392.1
414.5
416.3
441.9
457.5
15°F
69.3
77.2
83.4
90.2
98.0
103.6
104.1
110.5
114.4
138.5
154.3
166.9
180.4
196.0
207.3
208.2
221.0
228.8
231.5
250.3
270.6
294.0
310.9
312.2
331.5
343.1
360.8
392.0
414.5
416.3
441.9
457.5
430.9
490.1
518.2
520.4
552.4
571.9
541.1
588.1
621.8
624.5
662.9
686.3
20°F
92.4
102.9
111.3
120.3
130.7
138.2
138.8
147.3
152.5
184.7
205.7
222.5
240.5
261.4
276.4
277.6
294.6
305.0
308.6
333.8
360.8
392.0
414.5
416.2
441.9
457.5
481.0
522.7
552.7
555.1
589.2
610.0
601.3
653.4
690.9
693.9
736.6
762.5
721.5
784.1
829.1
832.7
883.9
915.0
25°F
115.4
128.6
139.1
150.3
163.4
172.7
173.5
184.1
190.6
230.9
257.2
278.1
300.6
326.7
345.5
346.9
368.3
381.3
385.8
417.2
450.9
490.1
518.2
520.4
552.4
571.9
601.3
653.4
690.9
693.9
736.6
762.5
751.6
816.8
863.6
867.4
920.7
953.2
901.9
980.1
1036.4
1040.8
1104.8
1143.8
10°F
45.3
50.4
54.5
58.9
64.0
67.7
68.0
72.2
74.7
90.5
100.8
108.0
117.9
128.1
135.4
136.0
144.4
149.5
151.2
163.5
176.8
192.1
203.1
204.0
216.6
224.2
235.7
256.1
270.8
272.0
288.7
298.9
294.6
320.2
338.6
340.0
360.9
373.6
353.5
384.2
406.2
408.0
433.1
448.4
15°F
67.9
75.7
81.7
88.4
96.0
101.5
102.0
103.8
112.3
135.7
151.2
163.6
176.8
192.1
203.2
204.0
216.6
224.2
226.9
245.3
265.2
288.1
304.7
306.0
324.9
336.2
353.6
384.2
406.2
408.0
433.1
448.4
441.9
480.3
507.8
510.0
541.4
560.5
530.3
576.3
609.4
612.0
649.6
672.6
20°F
90.6
100.8
109.1
117.9
128.1
135.4
136.0
144.4
149.5
181.0
201.6
218.1
235.7
256.2
270.9
272.0
288.7
298.9
302.4
327.1
353.6
384.2
406.2
408.0
433.1
448.4
471.4
512.2
541.6
544.0
577.4
597.8
589.3
640.3
677.1
680.0
721.9
747.3
707.1
768.4
812.5
816.0
866.2
896.7
25°F
113.1
126.0
136.3
147.3
160.1
169.2
170.0
180.4
186.8
226.3
252.1
272.5
294.6
320.2
338.6
340.0
360.9
373.7
378.1
408.9
441.9
480.3
507.8
510.0
541.4
560.5
589.3
640.3
677.1
680.0
721.9
747.3
736.6
800.5
846.3
850.1
902.3
934.1
883.9
960.5
1015.7
1020.0
1082.7
1120.9
AIR
FLOW
(CFM)
10967
10682
10409
10159
9785
9441
9449
9031
8660
21934
21364
20818
20318
19570
18882
18898
18062
17320
32046
31227
30477
29355
28323
28347
27093
25980
40636
39140
37764
37796
36124
34640
25998
28247
29861
30005
31850
32974
60954
57710
56646
56694
54186
51960
CONDENSER
EST
CHARGE R-404A SOUND SHIP
WEIGHT AVAIL
(LBS)
10’
(LBS) CIRCUITS
SUMMER WINTER (dBA)
34
5
17
437
65
34
5
17
439
65
34
5
17
444
65
34
7
24
466
65
34
7
24
469
65
34
7
24
478
65
34
8
31
495
65
34
8
31
499
65
34
8
31
508
65
34
9
31
718
68
34
9
31
721
68
34
9
31
729
68
34
12
45
773
68
34
12
45
779
68
34
12
45
792
68
34
15
58
830
68
34
15
58
838
68
34
15
58
855
68
34
14
46
1041
70
34
14
46
1060
70
34
18
67
1126
70
34
18
67
1135
70
34
18
67
1153
70
34
23
87
1210
70
34
23
87
1223
70
34
23
87
1247
70
34
23
87
1437
71
34
23
87
1449
71
34
23
87
1474
71
34
29
114
1550
71
34
29
114
1566
71
34
29
114
1599
71
34
27
107
2020
72
34
27
107
2035
72
34
27
107
2066
72
34
35
141
2160
72
34
35
141
2181
72
34
35
141
2222
72
34
58
235
2554
73
34
58
235
2573
73
34
58
235
2610
73
34
75
310
2784
73
34
75
310
2808
73
34
75
310
2858
73
NOTE: Ratings are based on 85°F 115°F entering air temperature. The temperature difference is between the saturated condensing temp. and the
entering air temp. to the condenser. Multiply R-22 rating by 0.95 for R-134a. Summer charge based on 25% of condenser volume with 86°F liquid.
Multiply by 1.14 for R-22. Winter charge based on 90% of condenser volume with -20°F liquid. Multiply by 1.10 for R-22.
LEVITOR II AIR COOLED CONDENSER
Specifications subject to change without notice.
9
Levitor II Air Cooled Condenser
LAVC/LEVC Performance Data
1-1/2 H.P. 850 RPM - TWO FAnS WIDE
TOTAL HEAT OF REJECTION (MBH)
R-22
R-404A, R-507
TEMPERATURE DIFFERENCE
TEMPERATURE DIFFERENCE
MODEL
LAVC 222 08
LAVC 222 10
LAVC 222 12
LAVC 223 08
LAVC 223 10
LAVC 223 12
LAVC 224 08
LAVC 224 10
LAVC 224 12
LAVC 232 10
LAVC 232 12
LAVC 233 08
LAVC 233 10
LAVC 233 12
LAVC 234 08
LAVC 234 10
LAVC 234 12
LAVC 243 08
LAVC 243 10
LAVC 243 12
LAVC 244 08
LAVC 244 10
LAVC 244 12
LAVC 253 08
LAVC 253 10
LAVC 253 12
LAVC 254 08
LAVC 254 10
LAVC 254 12
LEVC 263 08
LEVC 263 10
LEVC 263 12
LEVC 264 08
LEVC 264 10
LEVC 264 12
10°F
184.7
205.7
222.5
240.5
261.3
276.3
277.5
294.6
305.0
308.6
333.7
360.7
392.1
414.5
416.3
441.9
457.5
481.0
522.7
552.7
555.1
589.3
610.0
601.3
653.4
690.9
693.9
736.5
762.5
721.5
784.1
829.1
832.7
883.9
915.0
15°F
277.1
308.6
333.8
360.8
392.0
414.5
416.3
441.9
457.5
462.9
500.6
541.1
588.1
621.8
624.5
662.9
686.3
721.6
784.1
829.1
832.7
883.9
915.0
901.9
980.1
1036.4
1040.8
1104.8
1143.8
1082.3
1176.1
1243.6
1249.0
1325.8
1372.5
NOTE: Ratings are based on
85°F-115°F entering air
temperature. The temperature
difference is between the
saturated condensing temp. and
the entering air temp. to the
condenser. Multiply R-22 rating
by 0.95 for R-134a. Summer
charge based on 25% of
condenser volume with 86°F
liquid. Multiply by 1.14 for R22.Winter charge based on 90%
of condenser volume with -20°F
liquid. Multiply by 1.10 for R-22.
CONDENSER
CHARGE R-404A
(LBS)
25°F
452.6
504.1
545.2
589.3
640.3
677.1
680.0
721.9
747.3
756.1
817.7
883.9
960.5
1015.7
1020.0
1082.7
1120.9
1178.6
1280.7
1354.2
1360.0
1443.6
1494.5
1473.1
1600.8
1692.8
1700.0
1804.6
1868.2
1767.7
1921.0
2031.2
2040.0
2165.5
2241.8
EST
SHIP
SOUND
WEIGHT AVAIL
10’
(LBS) CIRCUITS
(dBA)
SUMMER WINTER
43868
68
18
62
1311
71
42728
68
18
62
1320
71
41636
68
18
62
1336
71
40636
68
24
89
1437
71
39140
68
24
89
1425
71
37764
68
24
89
1462
71
37796
68
30
117
1539
71
36124
68
30
117
1555
71
34640
68
30
117
1588
71
64092
68
27
93
1875
73
62454
68
27
93
1912
73
60954
68
37
134
2044
73
58710
68
37
134
2063
73
56646
68
37
134
2100
73
56694
68
46
174
2214
73
54186
68
46
174
2238
73
51960
68
46
174
2287
73
81272
68
46
174
2526
74
78280
68
46
174
2651
74
75528
68
46
174
2700
74
75592
68
58
228
2851
74
72248
68
58
228
2884
74
69280
68
58
228
2950
74
101590
68
55
214
3725
75
97850
68
55
214
3755
75
94410
68
55
214
3817
75
94490
68
70
281
4005
75
90310
68
70
281
4046
75
86600
68
70
281
4129
75
121908
68
116
469
4759
76
117420
68
116
469
4796
76
113292
68
116
469
4870
76
113388
68
150
620
5218
76
108372
68
150
620
5268
76
103920
68
150
620
5366
76
ELECTRICAL DATA - OnE FAn WIDE
ELECTRICAL DATA - TWO FAnS WIDE
20°F
369.4
411.5
445.0
481.0
522.7
552.7
555.1
589.2
610.0
617.2
667.5
721.5
784.1
829.1
832.7
883.9
915.0
962.0
1045.4
1105.5
1110.2
1178.5
1220.0
1202.5
1306.8
1381.8
1387.8
1473.1
1525.0
1443.0
1568.2
1658.2
1665.3
1767.7
1830.0
25°F
461.8
514.4
556.3
601.3
653.4
690.9
693.9
736.6
762.5
771.5
834.4
901.9
980.1
1036.4
1040.8
1104.8
1143.8
1202.6
1306.8
1381.8
1387.8
1473.1
1525.0
1503.2
1633.5
1727.3
1734.7
1841.4
1906.3
1803.8
1960.2
2072.7
2081.6
2209.7
2287.6
10°F
181.0
201.6
218.1
235.7
256.1
270.8
272.0
288.7
298.9
302.4
327.1
353.5
384.2
406.2
408.0
433.1
448.4
471.4
512.3
541.7
544.0
577.5
597.8
589.2
640.3
677.1
680.8
721.8
747.3
707.0
768.4
812.5
816.0
866.2
896.7
15°F
271.6
302.4
327.1
353.6
384.2
406.2
408.0
433.1
448.4
453.6
490.6
530.3
576.3
609.4
612.0
649.6
672.6
707.2
768.4
812.5
816.0
866.2
896.7
883.9
960.5
1015.7
1020.0
1082.7
1120.9
1060.7
1152.6
1218.7
1224.0
1299.3
1345.1
20°F
362.0
403.3
436.1
471.4
512.2
541.6
544.0
577.4
597.8
604.9
654.2
707.1
768.4
812.5
816.0
866.2
896.7
942.8
1024.5
1083.4
1088.0
1154.9
1195.6
1178.5
1280.7
1354.2
1360.0
1443.6
1494.5
1414.1
1536.8
1625.0
1632.0
1732.3
1793.4
FAN MOTOR TOTAL FULL LOAD AMPS
208/230/3/60 460/3/60 575/3/60
LAVC-11***
LAVC-12***
LAVC-13***
LAVC-14***
LAVC-15***
LEVC-16***
6.0
12.0
18.0
24.0
30.0
36.0
3.0
6.0
9.0
12.0
15.0
18.0
2.5
5.0
7.5
10.0
12.5
15.0
***Rows & FPI (1) Minimum Unit Circuit Amps = 1.25 x FLA of One
Motor + FLA of All Remaining Motors. (2) Maximum Unit Overload
Protection = 2.25 x FLA of One Motor + FLA of All Remaining Motors.
AIR
FLOW
(CFM)
FAN MOTOR TOTAL FULL LOAD AMPS
208/230/3/60 460/3/60 575/3/60
LAVC-22***
LAVC-23***
LAVC-24***
LAVC-25***
LEVC-26***
24.0
36.0
48.0
60.0
72.0
12.0
18.0
24.0
30.0
36.0
10.0
15.0
20.0
25.0
30.0
Levitor II Air Cooled Condenser
LAVF/LEVF Performance Data
1-1/2 H.P. 1140 RPM - OnE FAn WIDE
TOTAL HEAT OF REJECTION (MBH)
R-22
R-404A, R-507
TEMPERATURE DIFFERENCE
TEMPERATURE DIFFERENCE
MODEL
LAVF
LAVF
LAVF
LAVF
LAVF
LAVF
LAVF
LAVF
LAVF
LAVF
LAVF
LAVF
LAVF
LAVF
LAVF
LAVF
LAVF
LAVF
LAVF
LAVF
LAVF
LAVF
LAVF
LAVF
LAVF
LAVF
LAVF
LAVF
LAVF
LAVF
LAVF
LAVF
LAVF
LAVF
LAVF
LAVF
LAVF
LAVF
LEVF
LEVF
LEVF
LEVF
LEVF
LEVF
112 08
112 10
112 12
113 08
113 10
113 12
114 08
114 10
114 12
122 08
122 10
122 12
123 08
123 10
123 12
124 08
124 10
124 12
132 10
132 12
133 08
133 10
133 12
134 08
134 10
134 12
143 08
143 10
143 12
144 08
144 10
144 12
153 08
153 10
153 12
154 08
154 10
154 12
163 08
163 10
163 12
164 08
164 10
164 12
10°F
47.5
53.4
58.3
63.8
70.3
75.5
76.0
82.3
86.7
95.1
106.8
116.5
127.6
140.7
150.9
152.1
164.5
173.3
160.3
174.8
191.4
211.1
226.3
228.1
246.7
259.9
255.3
281.4
301.7
304.1
329.0
346.5
319.1
351.8
377.2
380.1
411.3
433.2
382.9
422.1
452.6
456.2
493.5
519.8
15°F
20°F
71.3
95.1
80.1 106.8
87.4 116.5
95.7 127.6
105.5 140.7
113.2 150.9
114.0 152.1
123.4 164.5
130.0 173.3
142.6 190.2
160.2 213.7
174.8 233.1
191.4 255.2
211.1 281.4
226.3 301.8
228.1 304.1
246.7 329.0
259.9 346.5
240.4 320.5
262.2 349.6
287.1 382.9
316.6 422.1
339.5 452.6
342.1 456.2
370.1 493.5
389.9 519.8
382.9 510.5
422.1 565.8
452.6 603.5
456.2 608.3
493.5 658.0
519.8 693.1
478.6 638.1
527.7 703.6
565.8 754.4
570.2 760.3
616.9 822.5
649.8 866.4
574.3 765.7
633.2 844.3
678.9 905.3
684.3 912.4
740.2 987.0
779.7 1039.6
25°F
118.9
135.5
145.7
159.5
175.9
188.8
190.1
205.6
216.6
237.7
267.1
291.3
319.1
351.8
377.2
380.2
411.2
433.2
400.6
437.0
478.6
527.7
565.8
570.2
616.9
649.8
638.1
703.6
754.4
760.3
822.5
866.4
797.6
879.5
943.0
950.4
1028.1
1083.0
957.2
1055.3
1131.6
1140.5
1233.7
1299.5
10°F
46.6
52.3
57.1
62.5
68.9
74.0
74.5
80.6
84.9
93.2
104.7
114.2
125.0
137.9
147.8
149.0
161.2
169.8
157.1
171.3
187.6
206.8
221.8
223.5
241.8
254.7
250.2
275.8
295.7
298.1
322.4
339.6
312.7
344.8
369.7
372.5
403.0
424.5
375.2
413.7
433.5
447.1
483.6
509.4
15°F
20°F
69.9
93.2
78.5 104.7
85.7 114.2
93.8 125.0
103.4 137.9
110.9 147.9
111.7 149.1
120.9 161.2
127.4 169.8
139.7 186.4
157.0 209.4
171.3 228.4
187.6 250.1
206.9 275.8
221.8 295.8
223.5 298.0
241.8 322.4
254.7 339.6
235.6 314.1
257.0 342.6
281.4 375.2
310.3 413.7
332.7 443.5
335.3 447.1
362.7 483.6
382.1 509.4
375.2 500.3
413.7 551.5
443.5 591.4
447.1 596.1
483.6 644.8
509.4 679.2
469.0 625.3
517.1 689.5
554.5 739.3
558.8 745.1
604.6 806.1
636.8 849.1
562.8 750.4
620.5 827.4
665.3 887.2
670.6 894.2
725.4 967.3
764.1 1018.8
25°F
116.5
130.8
142.8
156.3
172.4
184.8
186.3
201.5
212.3
232.9
261.8
285.5
312.7
344.8
369.7
372.6
403.0
424.5
392.6
428.3
469.0
517.1
554.5
558.8
604.6
636.8
625.3
689.5
739.3
745.1
806.1
849.1
781.6
861.9
924.1
931.4
1007.5
1061.3
938.1
1034.2
1109.0
1117.7
1209.0
1273.5
AIR
FLOW
(CFM)
11649
11541
11430
11323
11147
10969
10974
10730
10486
23298
23082
22860
22646
22294
21938
21948
21460
20972
34623
34290
33969
33441
32907
32922
32190
31458
45292
44588
43876
43896
42920
41944
56615
55735
54845
54870
53650
52430
67938
66882
65814
65844
64380
62916
CONDENSER
EST
CHARGE R-404A SOUND SHIP
WEIGHT AVAIL
(LBS)
10’
(LBS) CIRCUITS
SUMMER WINTER (dBA)
437
34
5
17
72
439
34
5
17
72
444
34
5
17
72
466
34
7
24
72
469
34
7
24
72
478
34
7
24
72
495
34
8
31
72
499
34
8
31
72
508
34
8
31
72
718
34
9
31
75
721
34
9
31
75
729
34
9
31
75
773
34
12
45
75
779
34
12
45
75
792
34
12
45
75
830
34
15
58
75
838
34
15
58
75
855
34
15
58
75
1041
34
14
46
77
1060
34
14
46
77
1126
34
18
67
77
1135
34
18
67
77
1153
34
18
67
77
1210
34
23
87
77
1223
34
23
87
77
1247
34
23
87
77
1437
34
23
87
78
1449
34
23
87
78
1474
34
23
87
78
1550
34
29
114
78
1566
34
29
114
78
1599
34
29
114
78
2020
34
27
107
79
2035
34
27
107
79
2066
34
27
107
79
2160
34
35
141
79
2181
34
35
141
79
2222
34
35
141
79
2554
34
58
235
80
2573
34
58
235
80
2610
34
58
235
80
2784
34
75
310
80
2808
34
75
310
80
2858
34
75
310
80
NOTE: Ratings are based on 85°F 115°F entering air temperature. The temperature difference is between the saturated condensing temp. and the
entering air temp. to the condenser. Multiply R-22 rating by 0.95 for R-134a. Summer charge based on 25% of condenser volume with 86°F liquid.
Multiply by 1.14 for R-22. Winter charge based on 90% of condenser volume with -20°F liquid. Multiply by 1.10 for R-22.
LEVITOR II AIR COOLED CONDENSER
Specifications subject to change without notice.
11
Levitor II Air Cooled Condenser
LAVF/LEVF Performance Data
1-1/2 H.P. 1140 RPM - TWO FAnS WIDE
TOTAL HEAT OF REJECTION (MBH)
R-22
R-404A, R-507
TEMPERATURE DIFFERENCE
TEMPERATURE DIFFERENCE
MODEL
LAVF
LAVF
LAVF
LAVF
LAVF
LAVF
LAVF
LAVF
LAVF
LAVF
LAVF
LAVF
LAVF
LAVF
LAVF
LAVF
LAVF
LAVF
LAVF
LAVF
LAVF
LAVF
LAVF
LAVF
LAVF
LAVF
LAVF
LAVF
LAVF
LEVF
LEVF
LEVF
LEVF
LEVF
LEVF
222 08
222 10
222 12
223 08
223 10
223 12
224 08
224 10
224 12
232 10
232 12
233 08
233 10
233 12
234 08
234 10
234 12
243 08
243 10
243 12
244 08
244 10
244 12
253 08
253 10
253 12
254 08
254 10
254 12
263 08
263 10
263 12
264 08
264 10
264 12
10°F
190.2
213.7
233.1
255.3
281.4
301.7
304.1
329.0
346.5
320.5
349.6
382.9
442.1
452.6
456.2
493.5
519.8
510.5
562.9
603.5
608.3
658.0
693.1
638.1
703.5
754.4
760.3
822.5
866.3
765.7
884.3
905.3
912.4
986.9
1039.6
15°F
285.3
320.5
349.6
382.9
422.1
452.6
456.2
493.5
519.8
480.7
524.4
574.3
633.2
678.9
684.3
740.2
779.7
765.7
844.3
905.3
912.4
987.0
1039.6
957.2
1055.3
1131.6
1140.5
1233.7
1299.5
1148.6
1266.4
1357.9
1368.6
1480.4
1559.4
NOTE: Ratings are based on
85°F-115°F entering air
temperature. The temperature
difference is between the
saturated condensing temp. and
the entering air temp. to the
condenser. Multiply R-22 rating
by 0.95 for R-134a. Summer
charge based on 25% of
condenser volume with 86°F
liquid. Multiply by 1.14 for R22.Winter charge based on 90%
of condenser volume with -20°F
liquid. Multiply by 1.10 for R-22.
20°F
380.3
427.3
466.1
510.5
562.8
603.5
608.3
658.0
693.1
641.0
699.2
765.7
844.3
905.3
912.4
987.0
1039.6
1021.0
1125.7
1207.0
1216.5
1316.0
1386.2
1276.2
1407.1
1508.8
1520.6
1644.9
1732.7
1531.5
1688.5
1810.5
1824.8
1973.9
2079.3
25°F
475.4
534.2
582.7
638.1
703.6
754.4
760.3
822.5
866.4
801.2
874.0
957.2
1055.3
1131.6
1140.5
1233.7
1299.5
1276.2
1407.1
1508.8
1520.6
1644.9
1732.7
1595.3
1758.9
1886.0
1900.8
2056.2
2165.9
1914.3
2110.7
2263.1
2281.0
2467.4
2599.1
10°F
186.4
209.4
228.4
250.2
275.8
295.7
298.1
322.4
339.6
314.1
342.6
375.2
413.7
443.5
447.1
483.6
509.4
500.3
551.6
591.5
596.1
644.8
679.2
625.4
689.5
739.3
745.1
806.0
849.0
750.4
827.4
887.2
894.2
967.2
1018.9
15°F
279.6
314.1
342.6
375.2
413.7
443.5
447.1
483.6
509.4
471.1
513.9
562.8
620.5
665.3
670.6
725.4
764.1
750.4
827.4
887.2
894.2
967.3
1018.8
938.1
1034.2
1109.0
1117.7
1209.0
1273.5
1125.6
1241.1
1330.7
1341.2
1450.8
1528.2
20°F
372.7
418.8
456.8
500.3
551.5
591.4
596.1
644.8
679.2
628.2
685.2
750.4
827.4
887.2
894.2
967.3
1018.8
1000.6
1103.2
1182.9
1192.2
1289.7
1358.5
1250.7
1379.0
1478.6
1490.2
1612.0
1698.0
1500.9
1654.7
1774.3
1788.3
1934.4
2037.7
25°F
465.9
523.5
571.0
625.3
689.5
739.3
745.1
806.1
849.1
785.2
856.5
938.1
1034.2
1109.0
1117.7
1209.0
1273.5
1250.7
1379.0
1478.6
1490.2
1612.0
1698.0
1563.4
1723.7
1848.3
1862.8
2015.1
2122.6
1876.0
2068.5
2217.8
2235.4
2418.1
2547.1
ELECTRICAL DATA - OnE FAn WIDE
FAN MOTOR TOTAL FULL LOAD AMPS
208/230/3/60 460/3/60 575/3/60
LAVF-11***
LAVF-12***
LAVF-13***
LAVF-14***
LAVF-15***
LEVF-16***
7.0
14.0
21.0
28.0
35.0
42.0
3.5
7.0
10.5
14.0
17.5
21.0
2.4
4.8
7.2
9.6
12.0
14.4
***Rows & FPI (1) Minimum Unit Circuit Amps = 1.25 x FLA of One
Motor + FLA of All Remaining Motors. (2) Maximum Unit Overload
Protection = 2.25 x FLA of One Motor + FLA of All Remaining Motors.
AIR
FLOW
(CFM)
46556
45824
45096
44412
43364
42344
42376
41056
39808
68736
67644
66618
65046
63516
63564
61584
59712
88824
86728
84688
84752
82112
79616
111030
108410
105860
105940
102640
99520
133236
130092
127032
127128
123168
119424
CONDENSER
EST
CHARGE R-404A SOUND SHIP
WEIGHT AVAIL
(LBS)
10’
CIRCUITS
(dBA) (LBS)
SUMMER
WINTER
18
18
18
24
24
24
30
30
30
27
27
37
37
37
46
46
46
46
46
46
58
58
58
55
55
55
70
70
70
116
116
116
150
150
150
62
62
62
89
89
89
117
117
117
93
93
134
134
134
174
174
174
174
174
174
228
228
228
214
214
214
281
281
281
469
469
469
620
620
620
78
78
78
78
78
78
78
78
78
80
80
80
80
80
80
80
80
81
81
81
81
81
81
82
82
82
82
82
82
83
83
83
83
83
83
1311
1320
1336
1437
1425
1462
1539
1555
1588
1875
1912
2044
2063
2100
2214
2238
2287
2526
2651
2700
2851
2884
2950
3725
3755
3817
4005
4046
4129
4759
4796
4870
5218
5268
5366
68
68
68
68
68
68
68
68
68
68
68
68
68
68
68
68
68
68
68
68
68
68
68
68
68
68
68
68
68
68
68
68
68
68
68
ELECTRICAL DATA - TWO FAnS WIDE
FAN MOTOR TOTAL FULL LOAD AMPS
208/230/3/60 460/3/60 575/3/60
LAVF-22***
LAVF-23***
LAVF-24***
LAVF-25***
LEVF-26***
28.0
42.0
56.0
70.0
84.0
14.0
21.0
28.0
35.0
42.0
9.6
14.4
19.2
24.0
28.8
Levitor II Air Cooled Condenser
Dimensional Drawings
ELECTRICAL BOX
ELECTRICAL BOX
H
AIR
B
L
A
L
ELECTRICAL BOX
C
W
ELECTRICAL BOX
(2)
B
B
L
B
A
A
L
ELECTRICAL BOX
H
AIR
B
L
A
A
C
W
ELECTRICAL BOX
A
L
A
A
OnE FAn WIDE
TWO FAn WIDE
CONNECTIONS
OD IN(1)
W
LAV*-11***
LAV*-12***
LAV*-13***
LAV*-14***
LAV*-15***
LEV*-16***
58
112
166
220
274
328
W
H
A
B
C
45-1/4 54
- 54 41-1/4
45-1/4 54 108 - 41-1/4
45-1/4 54 108 54 41-1/4
45-1/4 54 108 - 41-1/4
45-1/4 58-1/2 108 54 41-1/4
45-1/4 58-1/2 108 - 41-1/4
2 columns of "W" need to
change one to L and W
CONNECTIONS
OD IN(1)
W
INLET OUTLET
1-3/8
1-5/8
2-1/8
2-1/8
2-1/8
2-5/8
1-3/8
1-5/8
2-1/8
2-1/8
2-1/8
2-5/8
LAV*-22***
LAV*-23***
LAV*-24***
LAV*-25***
LEV*-26***
112
166
220
274
328
W
H
A
B
C
INLET
OUTLET
90-1/2 54 108 - 86-1/2 (2)1-5/8 (2)1-5/8
90-1/2 54 108 54 86-1/2 (2)2-1/8 (2)2-1/8
90-1/2 54 108 - 86-1/2 (2)2-1/8 (2)2-1/8
90-1/2 58-1/2 108 54 86-1/2 (2)2-1/8 (2)2-1/8
90-1/2 58-1/2 108 - 86-1/2 (2)2-5/8 (2)2-5/8
*Indicates fan/motor combination. Includes standard 22" legs.
(1) Connections are approximate. Exact size is determined by computerized circuiting program.
(2) 1 X 3 has six legs; 2 x 3 has eight legs.
LEVITOR II AIR COOLED CONDENSER
Specifications subject to change without notice.
13
Levitor II Air Cooled Condenser
LAVB Performance Data
1/2 H.P. 1140 RPM
TOTAL HEAT OF REJECTION CAPACITY (MBH)
ONE FAN
MODEL
LAVB
LAVB
LAVB
LAVB
LAVB
LAVB
LAVB
LAVB
LAVB
LAVB
LAVB
LAVB
LAVB
LAVB
LAVB
LAVB
112
113
114
122
123
124
133
134
143
144
153
154
163
164
173
174
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
RATING BASED ON 85°-115°F ENTERING AIR TEMPERATURE
TD IS SATURATED CONDENSING TEMP. MINUS ENTERING AIR TEMP.
R-22 TD
R-404A, R-507A TD
# OF ROWS
FANS
1
1
1
2
2
2
3
3
4
4
5
5
6
6
7
7
DEEP
2
3
4
2
3
4
3
4
3
4
5
4
3
4
3
4
15°F
30.2
39.4
45.4
60.5
78.9
90.9
118.3
136.3
157.8
181.7
197.2
227.1
236.7
272.6
276.1
318.0
20°F
45.4
59.1
68.2
90.7
118.3
136.3
177.8
204.5
236.7
272.6
295.9
340.7
355.0
408.8
414.2
477.0
25°F
60.5
78.9
90.9
121.0
157.8
181.7
236.7
272.6
315.6
363.4
394.5
454.3
473.3
545.1
552.2
636.0
10°F
29.4
38.4
44.2
58.9
76.7
88.4
115.1
132.6
153.5
176.8
191.9
221.0
230.2
265.2
268.6
309.4
15°F
44.2
57.6
66.4
83.3
115.1
132.6
172.7
199.0
230.2
265.2
287.8
331.5
345.5
397.8
403.0
464.1
4
4
4
6
6
8
8
10
10
12
12
14
14
2
4
4
3
4
3
4
3
4
3
4
3
4
121.0
157.8
181.7
236.7
272.6
315.6
363.4
394.5
454.3
473.3
545.1
552.2
636.0
181.5
236.7
272.6
355.0
408.8
473.3
545.1
591.7
681.4
710.0
817.7
828.3
953.9
242.0
315.6
363.4
473.3
545.1
631.1
726.8
788.9
908.5
946.7
1090.2
1104.5
1271.9
117.8
153.5
176.8
230.2
265.2
307.1
353.6
383.8
441.9
460.6
530.4
537.3
618.8
176.5 235.4
230.2 307.1
265.2 353.6
345.5 460.6
397.8 530.4
460.6 614.1
530.4 707.1
575.7 767.6
663.0 884.0
690.8 921.2
795.6 1060.8
806.0 1074.7
928.2 1237.5
20°F
58.9
76.7
88.4
117.8
153.5
176.8
230.2
265.2
307.1
353.6
383.3
441.9
460.5
530.4
537.3
618.8
EST
SOUND
10’
(dBA)
65
65
65
68
68
68
70
70
71
71
72
72
73
73
74
74
AIR
FLOW
CFM
6750
6400
6000
13500
12800
12000
19200
18000
25600
24000
32000
30000
38400
36000
44800
42000
71
71
71
73
73
74
74
75
75
76
76
77
77
27000
25600
24000
38400
36000
51200
48000
64000
60000
76800
72000
89600
84000
WINTER WGT INCL
FLOOD
FLOOD
CHARGE CHARGE
(LBS)
(LBS)
181
10
185
14
200
19
352
19
372
29
400
39
559
43
600
58
840
64
900
86
861
62
950
97
1070
86
1150
116
1349
107
1450
144
AVAIL
CIRCUITS
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
TWO FAN
MODEL
LAVB
LAVB
LAVB
LAVB
LAVB
LAVB
LAVB
LAVB
LAVB
LAVB
LAVB
LAVB
LAVB
222
223
224
233
234
243
244
253
254
263
264
273
274
10
10
10
10
10
10
10
10
10
10
10
10
10
NOTE: Ratings are based on 85°F-115°F entering air temperature. The temperature difference is between the
saturated condensing temp. and the entering air temp. to the condenser. Multiply R-22 rating by 0.95 for R-134a.
Not available with Quietor fan blades.
14
LEVITOR II AIR COOLED CONDENSER
Specifications subject to change without notice.
38
64
86
86
116
126
172
124
194
172
232
214
288
654
865
925
1118
1225
1705
1825
1722
1925
2095
2225
2725
2925
60
60
60
60
60
60
60
60
60
60
60
60
60
Levitor II Air Cooled Condenser
Dimensional and Electrical Data
Header End View
Side Views
ELECTRICAL BOX
H
49
B
W
A
L
H
B
W
11
12, 22
A
L
13, 23
A
L
14, 24
A
15, 25
A
16, 26
A
17, 27
A
A
L
L
A
A
L
A
A
A
DIMEnSIOnAL DATA
A
L
A
ELECTRICAL DATA
ONE FAN WIDE
ONE FAN WIDE
FAN MOTOR TOTAL RATED FULL LOAD AMPS
LAVB-11***
LAVB-12***
LAVB-13***
LAVB-14***
LAVB-15***
LAVB-16***
LAVB-17***
A
L
L
W
H
A
B
39
75
111
147
183
219
262
45-1/4
45-1/4
45-1/4
45-1/4
45-1/4
45-1/4
45-1/4
41-1/4
41-1/4
41-1/4
41-1/4
41-1/4
41-1/4
41-1/4
36
72
108
72/72
72/36/72
72/72/72
72/72/36/72
43-1/4
43-1/4
43-1/4
43-1/4
43-1/4
43-1/4
43-1/4
208/230/1 208/230/3
4.2
8.4
12.6
16.8
21.0
25.2
29.4
2.8
5.6
8.4
11.2
14.0
16.8
19.6
CONNECTIONS OD IN.(1)
460/3
575/3
INLET
OUTLET
1.3
2.6
3.9
5.2
6.5
7.8
9.1
0.76
1.52
2.28
3.04
3.8
4.56
5.32
1-1/8
1-3/8
1-3/8
1-5/8
2-1/8
2-1/8
2-5/8
1-1/8
1-3/8
1-3/8
1-5/8
2-1/8
2-1/8
2-5/8
Includes standard 18" legs.
(1) Connections are approximate. Exact size is determined by computerized circuiting program.
LEVITOR II AIR COOLED CONDENSER
Specifications subject to change without notice.
15
Levitor II Air Cooled Condenser
Control Panel Nomenclature
PT
A
2
6
RELAY BOARD
CONTROLS:
NC = No Controls
PT = Pressure Controls
TF = Temp. Controls
TP = Temperature and
Pressure Control
PV = Pressure Control
w/Variable Speed
Head Fans
TV = Temp. Control
w/Variable Speed
Header End Fans
VN = No Controls
w/Variable Speed
Header End Fans
FAN/MOTOR COMBINATION:
A = 1 HP 850 RPM 30"
B = 1/2 HP 1140 RPM 24"
C = 1-1/2 HP 850 RPM 30"
E = 1/2 HP 575 RPM 30"
F = 1-1/2 HP 1140 RPM 30"
FANS WIDE:
1 or 2
FANS IN LINE:
1 to 7
(7 Fans on “B” Units Only)
M
B
3
3
1
AMBIENT AIR SENSOR FOR SPLIT
(50% Winter Reduction):
T = Sensor Provided
N = Sensor Not Required
TYPE OF APPLICATION:
1 = Standard
2 = 50% Winter Reduction Relay
(Split Condenser)
3 = 50/50 Split Dual Panel
(for Two Indep. Slabs)
4 = No Control Operation
(Terminal Blocks Only)
FUSES AND BREAKERS:
1 = Individual Fuses and Contactors
2 = Individual Circuit Breakers
and Contactors per each Fan
3 = Fuses and Contactors per Pair of Fans
4 = Terminal Blocks Only
5 = Circuit Breaker and Contactor
per Pair of Fans
6 = Fuses per Motor
CONTROL MANUFACTURER:
1 = Johnson Mechanical
3 = Johnson Electronic
4 = No Controls
CONTROL VOLTAGE:
A = 208/230V
F =
B = 115V
G =
C = No Control Voltage
D = 24V
H =
E = 208/230V w/o Transformer
POWER VOLTAGE:
A = 208/230/1/60
K = 208/230/3/60
M = 460/3/60
P = 550/575/3/60
U = 380/3/50
16
LEVITOR II AIR COOLED CONDENSER
Specifications subject to change without notice.
N
115V w/o Transformer
No Control Voltage
w/o Transformer
24V w/o Transformer
Levitor II Air Cooled Condenser
Standard Fan Cycling/Control Arrangements
n
n
n
n
n
Thermal Fantrol-Electronic temperature control
cycles fans in response to entering air temperature.
Set points and differential for each step are
adjustable.
Pressurtrol-Electronic pressure control with single
point pressure transducer cycles fans in response to
condenser pressure. Set points and differential for
each step are adjustable.
Thermal Pressure Fantrol-Electronic temperature
control cycle fans in response to entering air
temperature, except for header end fan(s). Header
end fan(s) are controlled by pressure control.
Variable Speed Control-Header end fan(s) are
controlled with a speed controller in response to
head pressure. Electronic pressure control cycles the
balance of fans.
Fan cycling Sequence-Fans are cycled off
individually or side-by-side in pairs in sequence
from the end opposite the header to the header
end. Header end fans run continuously if
compressors are operating.
Control Panel
Standard weather resistant enclosure is mounted
on the opposite end of the unit when looking at the
headers.
n Control power is 24, 115 or 230 volts. A transformer is
factory installed when required.
n Fan contactor with branch circuit fuse protection.
Each motor or bank of motors protected by fuses.
n For horizontal airflow application, consult factory.
n Disconnect not included, but may be required to
meet local codes.
n
Optional Arrangements
n Fan motor contactor and fuses only.
n Fan motor contactor and fuses only which operate
via a customer specified solid state board. Circuit
board is factory mounted and wired.
n 50/50 split with two fan wide models. Each side is
controlled separately with individual control panels on
each side.
n 50% winter reduction with two fan wide models.
The right side fans are isolated in winter. Fans are
locked out via a relay or switch during shutdown.
LEVITOR II AIR COOLED CONDENSER
Specifications subject to change without notice.
17
Levitor II Air Cooled Condenser
Low Ambient Controls (Head Pressure Control System)
Piping Schematic For Winter Control
n Head Pressure Control for systems with air-cooled
condenser is accomplished with two pressure
regulating valves designed specifically for this type
of application. When low ambient conditions are
encountered during winter operation on air-cooled
systems with a resultant drop in condensing
pressure, the Head Pressure control’s purpose is
to hold back enough of the condenser liquid
refrigerant so that some of the condenser surface
is rendered inactive. This reduction of active
condensing surface results in a rise in the
condensing pressure and sufficient liquid line
pressure for normal system operation.
Eternal Equalizer
Evaporator
Distributor
Condenser
Solenoid
Valve
TEV
HM Valve
Gas Check Valve
Compressor
Fan Cycling Controls
Factory installed and tested fan cycling control
panels (optional, see below for details).
Receiver
n
Fan Cycling Sequence
TABLE A
1st Stage
(Not Cycling)
2nd Stage
3rd Stage
4th Stage
5th Stage
6th Stage
CAPACITY MULTIPLIER
WITH HEADER FANS
RUNNING
1.00 0.55 0.40 0.33 0.28 0.24
0.55
0.40
0.33
NOTE:
Data given in table “A” is based on zero wind velocity. If condensers are subjected to wind effect, these multipliers will increase.
18
LEVITOR II AIR COOLED CONDENSER
Specifications subject to change without notice.
0.28
0.24
LL
Drier
Levitor II Air Cooled Condenser
Mounted Receivers
Levitor is available with a mounted receiver for applications where a remote receiver is desired.
Included in the option are a heavy-duty base, extended legs, receiver, a 3-way valve, relief valve(s),
rotalocks, ball valves, and ORI/ORD valves. Optional heated and/or oversized receivers available.
RECEIVER CAPACITIES @ 80% FuLL
SIZE
R-22
(LBS)
R-404A
(LBS)
10-3/4” x 48”
10-3/4” x 60”
12-3/4” x 72”
14-3/4” x 96”
128
162
275
444
114
144
245
395
Receiver models are 12” taller than standard models. Add the following to weights:
ADDITIOnAL unIT WEIGHTS
# OF RECEIVERS
# OF FANS
1
2
1x1
1x2
1x3
1x4
1x5
1x6
1x7
2x2
2x3
2x4
2x5
2x6
2x7
350
440
530
620
820
910
1000
520
620
720
910
1020
1120
550
640
730
820
1120
1210
1300
700
800
910
1210
1320
1420
LEVITOR II AIR COOLED CONDENSER
Specifications subject to change without notice.
19
Levitor II Air Cooled Condenser
ELECTRICAL
BOX
Mounted Receiver Diagram (One Receiver)
20
LEVITOR II AIR COOLED CONDENSER
Specifications subject to change without notice.
Levitor II Air Cooled Condenser
Mounted Receiver Diagram (Two Receivers)
LEVITOR II AIR COOLED CONDENSER
Specifications subject to change without notice.
21
Levitor II Air Cooled Condenser
Wiring Diagram
(-311) Single Fans
(-331) Pairs of Fans
22
LEVITOR II AIR COOLED CONDENSER
Specifications subject to change without notice.
Levitor II Air Cooled Condenser
Replacement Parts
L_VA unIT
LAVB unIT
DESCRIPTION
PART #
DESCRIPTION
PART #
MOTOR: 1 HP, 850 RPM, 208-230/460/3/60
4410138
MOTOR: 1/2 HP, 1140 RPM, 208-230/460/3/60
4410179
MOTOR: 1 HP, 850 RPM, 575/3/60
4410180
MOTOR: 1/2 HP, 1140 RPM, 575/3/60
FAN: 30” DIA. CW 5/8” BORE
4780320
FAN: 24” DIA. CW 5/8” BORE
4780141
GUARD: FOR 30” FAN
4910218
GUARD: FOR 24” FAN
4914792
L_VC unIT
CALL
L_VE unIT
DESCRIPTION
PART #
DESCRIPTION
PART #
MOTOR: 1-1/2 HP, 850 RPM, 208-230/460/3/60
4410179
MOTOR: 1/2 HP, 575 RPM, 208-230/460/3/60
4410184
MOTOR: 1-1/2 HP, 850 RPM, 575/3/60
4410313
MOTOR: 1/2 HP, 575 RPM, 575/3/60
4410315
FAN: 30” DIA. CW 5/8” BORE
4780662
FAN: 30” DIA. CW 5/8” BORE
4780142
GUARD: FOR 30” FAN
4910218
GUARD: FOR 30” FAN
4910218
L_VF unIT
OTHER COMMOn PARTS
PART #
DESCRIPTION
PART #
MOTOR: 1-1/2 HP, 1140 RPM, 208-230/460/3/60
4410139
1/2 HP, 208-230/1/60 FOR VARIABLE SPEED
4410176
MOTOR: 1-1/2 HP, 1140 RPM, 575/3/60
4410314
3/4 HP, 208-230/1/60 FOR VARIABLE SPEED
CALL
FAN: 30” DIA. CW 5/8” BORE
4780142
MOTOR CONTACTOR WITH 24 VOLT COIL
4480824
GUARD: FOR 30” FAN
4910218
MOTOR CONTACTOR WITH 110 VOLT COIL
4481721
MOTOR CONTACTOR WITH 230 VOLT COIL
CALL
DESCRIPTION
P352AB-3C PRESSURE CONTROLLER
4481838
S352AA-2C ADDER MODULE (PRESSURE)
4481839
P399BAC-1C PRESSURE TRANSDUCER
4481840
A350AB-1 TEMPERATURE CONTROLLER
4481731
LEVITOR II AIR COOLED CONDENSER
Specifications subject to change without notice.
23
Levitor II Air Cooled Condenser
Notes
24
LEVITOR II AIR COOLED CONDENSER
Specifications subject to change without notice.
Krack Corporation
1300 North Arlington Heights Rd., Suite 130
Itasca, IL 60143
Ph: 630.629.7500
krack.com
Printed in U.S.A. ©2012 Krack Corporation
Levitor II_K_082012