SYSTEM DESCRIPTION
The ST Lumiere decorative facing is a perforated panel made of stainless or pre-coated galvanized steed with a
nominal thickness of 1 mm or in aluminum alloy with a thickness of 1.5 mm. These panels fit together by their
longitudinal edges.
This facing panel can be used as roofing cover, sunbreaker, interior decoration or aesthetic façade facing. This
product can be used on new or renovated public or private buildings used for commercial or lodging purposes.
(technical drawings – fig. 9 to 13)
ST Lumiere facting does not participate in the general stability of the building (no wind bracing or anti-buckling
functions). The support wall must provide the strength functions and stability of the façade and meet
requirements in the matter of air and water permeability.
A special version can be used for installing grating. (finish in C) (technical drawings – fig. 3 to 8)
TECHNICAL CHARACTERISTICS
Planview of perforation
•
•
•
•
•
Manufacture by bending. (technical drawings – fig. 1 & 2)
Useful width: 300 mm  1 mm.
Nominal height: 30 mm +0mm/-1 mm conventional finish
30 to 60 mm +0mm/-1 mm finish in C.
Perforation module: de 61.15 mm to 61.4 mm
Length 1000 mm – about 6000 mm maximum +1mm / - 2 mm multiple of perforation pitch.
3
MATERIALS
Thick.(mm)
1
Steel
Grade
S320GD + Z 225
Standard
NF EN 10326
P 34310
Stainless Steel
1
1.4301
1.4404
NF EN 10088-2
Aluminium Alloy
1 to 1.2
3003
NF A 50-451
Coating
Standard
Pre-coated as ARVAL
Colorissime chart
XP P34301
Post-coated by polyester
powdering
P 24351
Pre-coated
Post-coated by polyester
NF P 34-601
PMA should be consulted concerning the feasibility of various colors and surface appearances:
•
•
•
•
Pre-coated and pearly steel: Colorissime or Novolac color chart.
Steel post-coated by dusting: RAL color chart.
Pre-coated aluminum alloy: Alcan color chart.
Post-coated aluminum alloy: RAL color chart.
FINISHING ELEMENTS
These are manufactured from the same plates (same thickness, same material quality) as the panels, in
maximum lengths of 6 m.
•
•
•
•
Acroterion crown (technical drawings – fig. 14 & 18)
Flaps (technical drawings – fig. 15 & 20)
Outside and inside corners (technical drawings – fig. 16 & 22 to 24)
Various connections. (technical drawings – fig. 19)
COMPONENTS AND PARTICULAR FEATURES
ST Lumiere panels are designed to be installed on a ruled secondary frame. This frame serves as bearing and
attachment support for the ST Lumiere panels.
This secondary frame is a construction element by itself and is not an integral part of the ST Lumiere process.
Nevertheless, proper execution is a condition for the final result, notably as concerns the appearance of the
facing.
The separation of frames is to be determined by the loads applied to the panels. The table of allowable loads in
normal wind as a function of the spans given in the appendix determines this separation for ST Lumiere panels
in 10/10ths steel (consult us for other materials and thicknesses).
No frame alignment or flatness errors can be compensated by the ST Lumiere panels themselves.
The allowable loads and spans of the ST Lumiere panels under normal climatic conditions have been
determined by tests considering the following criteria:
•
•
Deflections of at most 1/200th of the span
Safety coefficient with respect to ruin greater than 2 for panels from steel sheet.
For aesthetic considerations, it is also advised to limit the spans to 1.5 m.
4
ST Lumiere panels are installed and attached on metal rails with the following characteristics:
•
•
Bearing width of at least 40 mm.
The thickness of the secondary frame sections must notably allow construction of assemblies with a
minimum characteristic strength of 300 daN.
Normal allowable wind loads on ST Lumiere panels in
10/10ths steel, in daN/m², Pressure & Vacuum
Installation of panels by male-female fit
Simple span – 2 supports
Pressure/Vacuum
Span
(m)
120
120
113
101
90
81
74
67
61
57
49
1.50
1.60
1.70
1.80
1.90
2.00
2.10
2.20
2.30
2.40
2.50
Continuity – 3 or more
supports
Pressure/Vacuum
120
120
120
120
120
100
96
93
90
86
83
Weight: 11.1 kg/m²
For the installation of grating type panels, consult P.M.A. for the allowable loads.
ATTACHMENTS
ST Lumiere panels in C are installed with special brackets secured to the frame by self-drilling screws.
As these brackets are attached through the panel by passing the tool through a perforation opening, the carrier
frame separation thus has to be a multiple of the peroration step.
Frame aligned on perforation opening
5
ORGANIZATION
The PMA company is the product manufacturer and does not install the product. The panels are to be installed
by contractors having the required professional qualifications.
Design and studies prior to executing the facade are not incumbent on the maker PMA nor on the distributor
companies. On request, PMA can provide technical assistance.
The purpose of the present specification is not to give details on all points of implementation but to state the
main technical definitions of the panels and their particular characteristics. To help in the study of the facades, it
is complemented in the appendix with particular design suggestions and finishing elements.
HANDLING AND CONDITIONING
A delivery invoice is glued to each package stating:
•
•
•
•
•
•
•
Customer order reference,
Batch reference,
Customer name
Type of product
Facing thickness
Bundle content (number and length)
Color reference of pre-coated steels.
ST Lumiere panels are packed on the production line.
The weight of the bundles may in no case exceed 2.5 tons.
ST Lumiere panels and their accessories are to be transported under conditions that preserve the integrity of the
characteristics (shimmed up packages, carefully stacked and strapped, tarpaulin-covered trucks).
Handling operations are carried out in consideration of the particular features of the products. They are to be
handled vertically on edge.
TRANSPORT, STORAGE AND MAINTENANCE
The panels are stored in bundles, slightly inclined in the longitudinal direction on a flat surface, without stacking
more than two packages. Storage time on the work site is to be reduced to the minimum.
The essential precaution consists in avoiding water from entering by runoff or condensation between the panels.
Store sheltered from sunlight.
The peel-off protective film covering the pre-coated panels is to be removed as work advances, at the latest 15
days after shipment.
Custom manufacture makes it possible to limit the cutting on the work site. As required, cutting operations on
site are performed using the appropriate equipment (jigsaw, nibbler, fine-tooth saw). It is strictly prohibited to
use a grinder wheel.
Watch out to avoid hot particles from being incrusted on the coating. All dirt (filings, drilling chips, etc.) are to be
eliminated immediately.
Metallic facades have to be normally maintained in accordance with the prescriptions of the Professional Rules
for Metallic Siding (article 4-2-91 exterior maintenance).
Although naturally cleanable by runoff of rainwater, if needed, they can be cleaned periodically with household
detergent, without chlorine added, with no use of abrasive or solvent, followed by rinsing with fresh water.
6
Maintenance notably consists of:
•
•
Eliminating various vegetation (such as moss) and any incompatible matter that might be deposited on
the facing surface.
Repair of any localized degradation as soon as detected, such as incipient corrosion caused, for
example, by exterior deterioration actions.
DRAWINGS OF DETAILS OF PRINCIPLE
The following drawings are examples of how singular point of ST Lumiere panels are treated on a facade.
Any other solutions can be considered and studied by the installing contractor in consideration of the specific
characteristics of the product.
7
For any further information, please consult us.
IMPORTANT
The content of this document is based on data relative to construction and to materials properties. It is designed
to assist PMA customers in implementing its products. Based on the construction processes and methods
known at the time of its publication, this Implementation Guide cannot be considered final and may be revised
and/or modified at any time.
8
TECHNICAL DRAWINGS
ST Lumiere
- « C »
finishfinish
ST Lumiere
- « C »
Ma
x le
ng
th
60
00
m
Ma
x le
ng
th
60
00
m
m
m
Length
multiple
pitchofofperforing
perforing
Length
asofpitch
ST Lumiere – Classic finish
fig.1
ST Lumiere – Classic finish
Vertical section
fig.2
9
ST Lumiere – « C » finish
Vertical section
fig.3
Attachment ST Lumiere – Classic finish
Vertical section
fig.4
Attachment ST Lumiere – « C » finish
Vertical section
fig.5
10
ST Lumiere – Duck-boards installation
fig.6
ST Lumiere – Duck-boards installation
Vertical section
ST Lumiere panel - « C » finish
Subframe
Self-drilling screw
Attach leg
fig.7
ST Lumiere – Attachment system for
duck-boards installation
Attach leg
Self-drilling screw
fig.8
11
ST Lumiere installed as sun-breaker
fig.9
ST Lumiere installed as sun-breaker
fig.10
12
Attachment system for ST Lumiere
installed as sun-breaker
Frame
Self-drilling screw
fig.11
ST Lumiere for facades
fig.12
13
ST Lumiere for facades
fig.13
Acroterion
Attach leg
Acroterion crown
ST lumiere panel
fig.14
Flap
Standard lower flap
fig.15
14
Re-entrant right corner
ST Lumiere - Vertical
installation
fig.16
Angle piece – horizontal section
Connecting plate
Subframe
Length max. 6000 mm
Folded angle piece
ST Lumiere panel
fig.17
fig.18
15
ST Lumiere for facades –
Horizontal installation
( from the top to the
bottom)
fig.19
Acroterion Crown
ST Lumiere panel
Attach leg
fig.20
Flap
ST Lumiere panel
Perforated lower flap
fig.21
16
ST Lumiere - Horizontal installation
( from the top to the bottom) –
Right angle
fig.22
Connecting plate
Folded piece
Length max. 6000 mm
X and Y as request
fig.23
fig.24