O-Calc® Pro Capacity Summary Report
Transcription
O-Calc® Pro Capacity Summary Report
O-Calc® Pro Capacity Summary Report Pole Group: Rocheport Interconnect Report Created: 7/15/2013 Pole:1539-1309-NT Moment Groundline 15,698 ft-lb Maximum 13,991 ft-lb Percent at Height Wind Angle Load Angle Max 82.4 29.0 ft 267.2° 267.3° GL 30.3 0.0 ft 25.6° 24.5° Buckling 51.1 25.6 ft 67.8° Guys are adequate O-Calc® Pro Capacity Summary Info Pole Identification: NT Report Created: 7/15/2013 File: 1539-1309-NT.pplx BOONE ELECTRIC COOP Pole Analysis Report for Charter Communications File Name: Pole Num: 1539-1309NT.pplx NT Pole Length / Class: Pole Species: 40 / 4 PONDEROSA PINE NESC NESC Rule: N38°58.322' Setting Depth (ft): Longitude: W92°25.567' G/L Circumference (in): 36.50 Loading District: Elevation: 616' G/L Fiber Stress (psi): 6,600 Ice Thickness (in): 0.50 Unset Allowable Stress (psi): 5,610 Wind Speed (mph): 39.53 Fiber Stress Ht. Reduction: No Structure Type: Rule 250B Latitude: Project: 6.00 Code: Construction Grade: Wind Pressure (psf): Guyed Tangent N/A Status: C Pole Strength Factor: 0.85 Heavy Transverse Wind LF: 1.75 Wire Tension LF: 1.30 Vertical LF: 1.90 4.00 Pole Midspans North South East West 25'8" 21'7" 22'0" 24'9" Pole Capacity Utilization * includes Load Factor(s) Page 1 of 7 Wind Angle Maximum: 82.4% 29.0 ft 267.2° Groundline: 30.3% 0.0 ft 25.6° Vertical: 51.1% 25.6 ft 67.8° Load Angle Wind Angle Max Capac. Util: 13,991 ft-lb 267.3° 267.2° Groundline: 15,698 ft-lb 24.5° 25.6° Pole Moments Version: 4 / 4.08 Height ² Worst Wind per Guy Wire ³ Wind at 25.6° BOONE ELECTRIC COOP Pole Analysis Report for Charter Communications Guy Summary Guy Tensions Attach % Allowable Height (ft) Tension Maximum Guy Tensions Wind Angle % Allowable Tension Wind Angle Anchor Summary Lead Length Max. % Allow. (ft) Capacity Guy 1 31.8 40.9% 25.6° 42.7% 70.0° Anchor 1 21.0 14.8% Guy 2 31.3 23.6% 25.6° 23.9% 10.0° Anchor 2 20.0 8.3% Guy 3 31.3 0.0% 25.6° 0.0% 0.0° Anchor 3 21.0 0.0% Guy 4 30.5 46.6% 25.6° 47.7% 50.0° Anchor 4 18.0 16.5% Guy 5 28.4 52.9% 25.6° 53.8% 50.0° Anchor 5 16.0 38.9% Guy 6 26.4 57.8% 25.6° 58.7% 70.0° Anchor 6 14.0 18.8% Guy 7 20.1 54.2% 25.6° 54.2% 25.6° Anchor 7 11.0 24.7% Guy 8 19.4 52.5% 25.6° 53.7% 36.9° Anchor 8 16.0 3.1% Guy 9 19.1 8.5% 25.6° 8.8% 10.0° Anchor 9 9.0 2.2% Guy 10 18.2 6.0% 25.6° 6.4% 10.0° Anchor 10 8.0 33.5% Guy 11 17.6 72.7% 25.6° 72.8% 22.8° Anchor 11 8.0 20.6% Guy 12 17.0 44.2% 25.6° 44.7% 36.9° GROUNDLINE LOAD SUMMARY:*Wind at 25.6°, Applied Moment 15,698 ft-lb at 24.5°, Allowable Moment 71,980 ft-lb Shear Load (lbs)* Percent Applied Load Powers: 6,112 693.3 Comms: 3,524 399.7 -9,031 -1024.3 18 2.1 181 20.6 Crossarms: 61 7.0 Insulators: 15 1.8 Pole Load: 882 100.0 Guys/Braces: Power Equipment: Pole: Pole Reserve Capacity: Version: 4 / 4.08 Bending Moment (ft-lb) 172,179 64,436 -227,332 1,077 2,808 2,027 502 15,698 56,282 * includes Load Factor(s) Percent of Applied Moment** Percent of Pole Capacity -343.8 91.6 -328.2 10.2 26.7 15.1 0.4 149.4 Page 2 of 7 -50.2 13.4 -47.9 1.5 3.9 2.2 0.1 21.8 78.2 Bending Stress (+/-psi) 13,419 5,022 -17,718 84 219 158 39 1,223 4,387 Vertical Load (lbs) Vertical Stress (psi) 2,897 27 1,544 15 43,636 412 475 4 1,511 14 403 4 148 1 50,614 477 ² Worst Wind per Guy Wire Total Stress (psi) Percent of Pole Capacity 13,447 5,037 -17,306 88 233 162 41 1,701 3,909 ³ Wind at 25.6° 239.7 89.8 -308.5 1.6 4.2 2.9 0.7 30.3 69.7 BOONE ELECTRIC COOP Pole Analysis Report for Charter Communications LOAD SUMMARY BY OWNER BEC: -256 -318 1,926 3,097 -816 -2,665 39,824 376 1,079 10 522 5 2,766 26 -1,865 -4,078 24,711 39,737 -10,476 -34,196 6,423 882 15,698 1,223 50,614 <Undefined>: 1,251 CHARTER COMM: 2,273 MEDIA COMM: CHARTER COMM PROPOSED: -522 Totals 61 58 1,936 3,102 -790 -2,605 1.0 34.5 55.3 -14.1 -46.4 477 1,701 30.3 Detailed Load Components Owner Power: Height (ft) Horiz. Offset (in) Cable Dia. (in) Rotate Angle (deg) Cable Lead/Sp Span Weight an Angle (lbs/ft) Length (deg) (ft) Wire Length (ft) Tension Tension (lbs) Moment (ft-lb)* Offset Moment (ft-lb)* Wind Moment (ft-lb)* Moment at GL (ft-lb)* Primary ACSR 1 AWG 6/1 ROBIN BEC 34.62 2.00 0.3550 - 0.115 400.0 182.0 400.0 888 -36,929 -35 839 -36,125 Primary ACSR 1 AWG 6/1 ROBIN BEC 34.62 2.00 0.3550 - 0.115 310.0 352.0 310.0 888 33,715 27 1,262 35,004 Primary ACSR 1 AWG 6/1 ROBIN BEC 33.15 40.34 0.3550 - 0.115 400.0 182.0 400.0 888 -35,352 -519 803 -35,067 Primary ACSR 1 AWG 6/1 ROBIN BEC 33.15 40.34 0.3550 - 0.115 400.0 182.0 400.0 888 -35,352 337 803 -34,212 Primary ACSR 1 AWG 6/1 ROBIN BEC 33.15 40.34 0.3550 - 0.115 310.0 352.0 310.0 888 32,275 -261 1,208 33,222 Primary ACSR 1 AWG 6/1 ROBIN BEC 33.15 40.34 0.3550 - 0.115 310.0 352.0 310.0 888 32,275 402 1,208 33,885 Primary ACSR 266.8 KCM 26/7 PARTRIDGE BEC 29.74 16.40 0.6420 - 0.367 253.0 92.0 253.0 2,825 41,752 30 3,050 44,832 Primary ACSR 266.8 KCM 26/7 PARTRIDGE BEC 28.99 43.95 0.6420 - 0.367 253.0 92.0 253.0 2,825 40,705 -55 2,974 43,624 Primary ACSR 266.8 KCM 26/7 PARTRIDGE BEC 28.99 43.95 0.6420 - 0.367 253.0 92.0 253.0 2,825 40,705 80 2,974 43,758 Neutral ACSR 1 AWG 6/1 ROBIN BEC 26.98 6.10 0.3550 - 0.115 400.0 182.0 400.0 888 -28,766 -65 654 -28,178 Neutral ACSR 1 AWG 6/1 ROBIN BEC 26.98 6.10 0.3550 - 0.115 310.0 352.0 310.0 888 26,262 -51 983 27,195 Primary ACSR 266.8 KCM 26/7 PARTRIDGE BEC 25.95 6.18 0.6420 - 0.367 253.0 92.0 253.0 2,825 36,438 51 2,662 39,151 Secondary TRIPLEX 4 AWG BEC 23.65 6.34 0.6800 - 0.164 137.0 313.0 137.1 372 3,634 20 1,437 5,090 Totals: 151,361 -39 Version: 4 / 4.08 * includes Load Factor(s) Page 3 of 7 ² Worst Wind per Guy Wire 20,856 172,179 ³ Wind at 25.6° BOONE ELECTRIC COOP Pole Analysis Report for Charter Communications Owner Comm: Height (ft) Horiz. Offset (in) Cable Dia. (in) Rotate Angle (deg) Cable Lead/Sp Span Weight an Angle (lbs/ft) Length (deg) (ft) Wire Length (ft) Overlashed Span Bundle 20.11 6.85 0.2500 - 0.121 253.0 92.0 253.0 CATV BELOPTIX DT096 - 72 FIBERS DIELECTRIC (0.516) 20.11 6.85 0.5160 - 0.097 253.0 92.0 253.0 Overlashed Span Bundle 19.40 6.90 0.2500 - 0.121 253.0 92.0 253.0 CATV BELOPTIX 2-60 CT FIBER ARMORED 19.37 6.90 0.5300 - 0.120 253.0 92.0 253.0 Overlashed Span Bundle 19.05 6.93 0.2500 - 0.121 400.0 182.0 400.1 CATV BELOPTIX DT096 - 72 FIBERS DIELECTRIC (0.516) 19.05 6.93 0.5160 - 0.097 400.0 182.0 400.1 Overlashed Span Bundle 19.05 6.93 0.2500 - 0.121 310.0 352.0 310.0 CATV BELOPTIX DT096 - 72 FIBERS DIELECTRIC (0.516) 19.05 6.93 0.5160 - 0.097 310.0 352.0 310.0 Overlashed Span Bundle CHARTER COMM 17.60 7.03 0.2500 - 0.121 310.0 352.0 310.0 CATV BELOPTIX 2-60 CT FIBER (NEW ATTACHMENT) CHARTER COMM 17.57 7.03 0.4600 - 0.063 310.0 352.0 310.0 Overlashed Span Bundle CHARTER COMM 17.00 7.08 0.2500 - 0.121 253.0 92.0 253.0 CATV BELOPTIX 2-60 CT FIBER (NEW ATTACHMENT) CHARTER COMM 16.97 7.08 0.4600 - 0.063 253.0 92.0 253.0 Tension Tension (lbs) Moment (ft-lb)* 800 1,330 800 800 1,330 1,330 Totals: Owner PowerEquipment: Transformer 1PH-15KVA BEC Owner Crossarm: Height (ft) 24.90 Height (ft) Horiz. Offset (in) 18.50 Horiz. Offset (in) Offset Angle (deg) 353.0 Offset Angle (deg) Rotate Angle (deg) 353.0 Rotate Angle (deg) Unit Weight (lbs) 250.00 Unit Weight (lbs) Unit Height (in) 22.00 Unit Height (in) Unit Depth (in) - Unit Depth (in) Unit Diameter (in) 17.00 Unit Diameter (in) Offset Moment (ft-lb)* Wind Moment (ft-lb)* Moment at GL (ft-lb)* 7,996 32 1,598 9,626 0 30 342 372 12,824 27 1,678 14,529 0 27 465 493 -18,308 -83 433 -17,958 0 -79 93 14 16,713 65 652 17,430 0 61 139 201 25,671 73 643 26,387 0 65 169 234 11,238 26 1,443 12,706 0 23 380 403 56,134 267 8,035 64,436 Unit Length (in) Tension Moment (ft-lb)* Offset Moment (ft-lb)* Wind Moment (ft-lb)* Moment at GL (ft-lb)* - - 625 453 1,077 Totals: 0 625 453 1,077 Unit Length (in) Tension Moment (ft-lb)* Offset Moment (ft-lb)* Wind Moment (ft-lb)* Moment at GL (ft-lb)* Normal CROSSARM 3-1/2 X 4-1/2 X 8 BEC 32.33 5.21 173.0 173.0 53.00 4.50 3.50 - 96.00 - 9 1,583 1,592 Normal CROSSARM 3-1/2 X 4-1/2 X 8 BEC 29.08 5.45 92.0 92.0 53.00 4.50 3.50 - 96.00 - 76 360 435 Totals: 0 85 1,943 2,027 Version: 4 / 4.08 * includes Load Factor(s) Page 4 of 7 ² Worst Wind per Guy Wire ³ Wind at 25.6° BOONE ELECTRIC COOP Pole Analysis Report for Charter Communications Owner Insulator: Height (ft) Horiz. Offset (in) Offset Angle (deg) Rotate Angle (deg) Unit Weight (lbs) Unit Height (in) Unit Depth (in) Unit Diameter (in) Unit Length (in) Tension Moment (ft-lb)* Offset Moment (ft-lb)* Wind Moment (ft-lb)* Moment at GL (ft-lb)* Pin Pin Insulator - 5 kV BEC 34.00 2.00 173.0 0.0 6.00 7.50 - 3.50 - - -2 44 42 Pin Pin Insulator - 5 kV BEC 34.00 2.00 353.0 180.0 6.00 7.50 - 3.50 - - 2 44 45 Pin Pin Insulator - 5 kV BEC 32.52 40.00 255.6 0.0 6.00 7.50 - 3.50 - - -24 42 18 Pin Pin Insulator - 5 kV BEC 32.52 -40.00 90.4 0.0 6.00 7.50 - 3.50 - - 16 42 57 Pin Pin Insulator - 5 kV BEC 32.52 40.00 270.4 180.0 6.00 7.50 - 3.50 - - -16 42 26 Pin Pin Insulator - 5 kV BEC 32.52 -40.00 75.6 180.0 6.00 7.50 - 3.50 - - 24 42 66 Deadend Deadend Insulator - 15 kV BEC 29.74 3.65 92.0 279.0 3.00 12.75 - 3.80 - - 3 70 73 Deadend Deadend Insulator - 15 kV BEC 29.08 40.00 174.2 0.0 3.00 12.75 - 3.80 - - -14 68 54 Deadend Deadend Insulator - 15 kV BEC 29.08 -40.00 9.8 0.0 3.00 12.75 - 3.80 - - 21 68 89 Spool Spool Insulator - 20 kV BEC 26.98 3.85 263.0 0.0 1.00 2.12 - 2.50 - - -1 7 6 Spool Spool Insulator - 20 kV BEC 25.95 3.93 92.0 279.0 1.00 2.12 - 2.50 - - 0 7 7 Spool Spool Insulator - 20 kV BEC 23.65 4.09 313.0 140.0 1.00 2.12 - 2.50 - - 0 6 6 Bolt Three Bolt 20.11 4.35 83.0 270.0 5.00 0.00 - 3.00 - - 3 0 3 Bolt Three Bolt 19.40 4.40 92.0 279.0 5.00 0.00 - 3.00 - - 2 0 2 Bolt Three Bolt 19.05 4.43 173.0 0.0 5.00 0.00 - 3.00 - - -5 0 -5 Bolt Three Bolt 19.05 4.43 353.0 180.0 5.00 0.00 - 3.00 - - 5 0 5 Bolt Charter Three Bolt CHARTER COMM 17.60 4.53 353.0 180.0 5.00 0.00 - 3.00 - - 5 0 5 Bolt Charter Three Bolt CHARTER COMM 17.00 4.58 93.0 280.0 5.00 0.00 - 3.00 - - 2 0 2 Totals: 0 21 481 502 Owner Guy Wire and Brace: Attach Height (ft) End Height (ft) Lead/Span Length (ft) Wire Dia. (in) Percent Solid Lead Angle Incline (%) (deg) Angle (deg) Wire Weight (lbs/ft) Rest Length Stretch (ft) Length (in) Guy 1: EHS 3/8 Down BEC 31.84 0.00 21.00 0.375 75.0 274.0 56.6 0.273 38.14 1.36 Guy 2: EHS 3/8 Down BEC 31.33 0.00 20.00 0.375 75.0 122.0 57.5 0.273 37.17 0.77 Guy 3: EHS 3/8 Down BEC 31.33 0.00 21.00 0.375 75.0 16.0 56.2 0.273 37.72 0.00 Guy 4: EHS 3/8 Down BEC 30.50 0.00 18.00 0.375 75.0 274.0 59.5 0.273 35.42 1.44 Guy 5: EHS 3/8 Down BEC 28.43 0.00 16.00 0.375 75.0 274.0 60.6 0.273 32.62 1.51 Guy 6: EHS 3/8 Down BEC 26.37 0.00 16.00 0.375 75.0 274.0 58.7 0.273 30.84 1.55 Guy 7: EHS 3/8 Down BEC 20.11 0.00 14.00 0.375 75.0 274.0 55.2 0.273 24.50 1.16 Guy 8: EHS 1/4 Down MEDIA COMM 19.39 0.00 11.00 0.250 75.0 274.0 60.4 0.121 22.29 0.99 Guy 9: EHS 3/8 Down BEC 19.06 0.00 16.00 0.375 75.0 122.0 50.0 0.273 24.88 0.19 Guy 10: EHS 3/8 Down BEC 18.22 0.00 9.00 0.375 75.0 122.0 63.7 0.273 20.32 0.11 Guy 11: EHS 1/4 Down CHARTER COMM PROPOSED 17.60 0.00 8.00 0.250 75.0 172.0 65.6 0.121 19.33 1.19 Guy 12: EHS 1/4 Down CHARTER COMM PROPOSED 17.00 0.00 8.00 0.250 75.0 272.0 64.8 0.121 18.79 0.70 Version: 4 / 4.08 * includes Load Factor(s) Page 5 of 7 ² Worst Wind per Guy Wire ³ Wind at 25.6° BOONE ELECTRIC COOP Pole Analysis Report for Charter Communications Elastic Modulus (psi) Guy Wire and Brace (Loads and Reactions) Rated Guy Allowable Initial Tensile Strength Tension Tension Strength (lbs) Factor (lbs) (lbs) Required Tension² (lbs) Required Tension³ (lbs) Applied Tension³ (lbs) Vertical Shear Load Load³ (lbs) in Guy Dir³ (lbs) Shear Load Moment at Report at GL³ (ftAngle³ (lbs) lb)* Guy 1: EHS 3/8 Down 23,000,000 15,400 0.90 13,860 700 5,923 5,669 5,669 4,733 3,121 -1,092 -34,494 Guy 2: EHS 3/8 Down 23,000,000 15,400 0.90 13,860 700 3,310 3,271 3,271 2,757 1,760 -230 -6,792 Guy 3: EHS 3/8 Down 23,000,000 15,400 0.90 13,860 700 0 0 0 0 0 12 Guy 4: EHS 3/8 Down 23,000,000 15,400 0.90 13,860 700 6,605 6,452 6,452 5,557 3,279 -1,147 -34,766 Guy 5: EHS 3/8 Down 23,000,000 15,400 0.90 13,860 700 7,450 7,333 7,333 6,390 3,596 -1,258 -35,614 Guy 6: EHS 3/8 Down 23,000,000 15,400 0.90 13,860 700 8,130 8,005 8,005 6,843 4,153 -1,453 -38,231 Guy 7: EHS 3/8 Down 23,000,000 15,400 0.90 13,860 700 7,517 7,517 7,517 6,169 4,295 -1,502 -30,300 Guy 8: EHS 1/4 Down 23,000,000 6,650 0.90 5,985 700 3,216 3,145 3,145 2,735 1,552 -543 -10,476 Guy 9: EHS 3/8 Down 23,000,000 15,400 0.90 13,860 700 1,225 1,183 1,183 906 760 -100 -1,730 Guy 10: EHS 3/8 Down 23,000,000 15,400 0.90 13,860 700 880 836 836 750 370 -48 -745 Guy 11: EHS 1/4 Down 23,000,000 6,650 0.90 5,985 700 4,359 4,350 4,350 3,960 1,800 -1,519 -26,904 Guy 12: EHS 1/4 Down 23,000,000 6,650 0.90 5,985 700 2,673 2,648 2,648 2,396 1,127 -431 -7,292 43,196 25,814 -9,323 227,332 Totals: Anchor/Rod Load Summary: Owner Rod Length AGL (in) Lead Length (ft) Lead Angle (deg) Strength of Assembly (lbs) Anchor/Rod Strength Factor Allowable Load (lbs) Max Load² (lbs) Load at Pole MCU³ (lbs) Max Required Capacity² (%) Expanding - 12" - Soil Class 3 BEC 0.00 21.00 101.0 40,000 1.00 40,000 5,923 5,669 14.8 Expanding - 12" - Soil Class 3 BEC 0.00 20.00 309.0 40,000 1.00 40,000 3,310 3,271 8.3 Expanding - 12" - Soil Class 3 BEC 0.00 21.00 203.0 40,000 1.00 40,000 0 0.0 Expanding - 12" - Soil Class 3 BEC 0.00 18.00 101.0 40,000 1.00 40,000 6,605 6,452 16.5 Expanding - 12" - Soil Class 3 BEC 0.00 16.00 101.0 40,000 1.00 40,000 15,578 15,335 38.9 Expanding - 12" - Soil Class 3 BEC 0.00 14.00 101.0 40,000 1.00 40,000 7,517 7,517 18.8 SCR - 6" - Soil Class 3 MEDIA COMM 0.00 11.00 101.0 13,000 1.00 13,000 3,216 3,145 24.7 Expanding - 12" - Soil Class 3 BEC 0.00 16.00 309.0 40,000 1.00 40,000 1,225 1,183 3.1 Expanding - 12" - Soil Class 3 BEC 0.00 9.00 309.0 40,000 1.00 40,000 880 836 2.2 SCR - 6" - Soil Class 3 CHARTER COMM PROPOSED 0.00 8.00 359.0 13,000 1.00 13,000 4,359 4,350 33.5 SCR - 6" - Soil Class 3 CHARTER COMM PROPOSED 0.00 8.00 99.0 13,000 1.00 13,000 2,673 2,648 20.6 Version: 4 / 4.08 * includes Load Factor(s) Page 6 of 7 ² Worst Wind per Guy Wire ³ Wind at 25.6° BOONE ELECTRIC COOP Pole Analysis Report for Charter Communications Pole Buckling Buckling Constant 0.71 Buckling Column Hgt Buckling Section Height Buckling Section Diam. (ft) (% Buckling Col. Hgt.) (in) 25.62 Version: 4 / 4.08 34.80 Min. Diameter Diameter Modulus of Buckling at Tip at GL Elasticity Diam. at GL (in) (in) (in) (psi) 10.32 * includes Load Factor(s) 37.84 6.69 11.62 1,000,000 Page 7 of 7 Pole Density Ice Density Pole Tip Height Buckling Load Capacity at Hgt. Buckling Load Applied at Hgt. (pcf) (pcf) (ft) (lbs) (lbs) 57.00 34.00 50.00 98,983 ² Worst Wind per Guy Wire Buckling Load Factor of Safety 50,614 ³ Wind at 25.6° 1.96