Kolpak Refrigeration Systems Installation Manual

Transcription

Kolpak Refrigeration Systems Installation Manual
Refrigeration Systems
Installation, Use & Care Manual
This manual is updated as new information and models are released.
Visit our website for the latest manual. www.manitowocfsg.com
Specified #1 Among Walk-ins
Part Number 11325 03/08
Safety Notices
Read These Before Proceeding:
As you work on Manitowoc equipment, be sure to pay
close attention to the safety notices in this manual.
Disregarding the notices may lead to serious injury and/
or damage to the equipment.
Throughout this manual, you will see the following types
of safety notices:
! Warning
Text in a Warning box alerts you to a potential
personal injury situation. Be sure to read the
Warning statement before proceeding, and work
carefully.
! Caution
Text in a Caution box alerts you to a situation in
which you could damage the equipment. Be sure to
read the Caution statement before proceeding, and
work carefully.
! Caution
Proper installation, care and maintenance are
essential for maximum performance and troublefree operation of your Manitowoc equipment. Read
and understand this manual. It contains valuable
care and maintenance information. If you encounter
problems not covered by this manual, do not
proceed, contact Manitowoc Foodservice Group.
We will be happy to provide assistance.
Important
Routine adjustments and maintenance procedures
outlined in this manual are not covered by the
warranty.
! Warning
PERSONAL INJURY POTENTIAL
Procedural Notices
As you work on Manitowoc equipment, be sure to read
the procedural notices in this manual. These notices
supply helpful information which may assist you as you
work.
Do not operate equipment that has been misused,
abused, neglected, damaged, or altered/modified
from that of original manufactured specifications.
NOTE: SAVE THESE INSTRUCTIONS.
Throughout this manual, you will see the following types
of procedural notices:
Important
Text in an Important box provides you with
information that may help you perform a procedure
more efficiently. Disregarding this information will
not cause damage or injury, but it may slow you
down as you work.
NOTE: Text set off as a Note provides you with simple,
but useful, extra information about the procedure you
are performing.
We reserve the right to make product improvements at any time.
Specifications and design are subject to change without notice.
Table of Contents
Section 1
General Information
Model Numbers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-1
Serial Number Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-1
Section 2
Installation Instructions
Part Number 11325 03/08
Pre-installation Checklist. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-1
Location of Equipment. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-1
Condensing Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-1
Multiple Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-2
Walls or Obstructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-2
Electrical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-2
Field Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-2
Multiple Evaporator Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-2
Refrigerant Piping Hanger Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-3
Installing Model PR Field-charged Lines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-3
Installation Guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-3
Oil Traps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-3
Installing Model PCL Pre-charged Lines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-4
Installation Guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-4
Evaporator Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-4
Condenser Unit Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-4
Drain Lines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-5
Walk-in Coolers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-5
Walk-in Freezers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-5
Panel Penetrations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-5
Charging Refrigeration System. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-6
Polyol Ester (POE) Lubricants (Used with HFC Refrigerants) . . . . . . . . . .
2-6
Refrigerant Charging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-6
Leak Testing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-7
Compressor Mounts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-7
Mounting Defrost Time Clock . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-8
Post Installation Checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-8
i
Table of Contents (continued)
Section 3
Operation
Component Identification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-1
Start-up Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-2
Sequence of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-2
Defrost Time Clock . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-2
Operational Checks and Adjustments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-3
Compressor Superheat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-3
Evaporator Superheat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-4
Temperature Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-4
Evaporator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-4
Defrost Time Clock . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-4
Refrigerant Evacuation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-4
Cleaning Condensing Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-1
Maintenance Chart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-1
Section 4
Maintenance
Section 5
Before Calling for Service
ii
Checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-1
Evaporator Checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-1
Compressor Checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-2
Equipment/Service Data Sheet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-4
System Reference Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-4
Part Number 11325 03/08
Section 1
General Information
Model Numbers
This manual covers the following models:
Pre-charged Lines
PCL
Field-charged Lines
PR
Serial Number Location
This number is required when requesting information
from your local distributor. The serial number is listed on
the SERIAL NUMBER DECAL affixed to the condensing
unit assembly.
Serial Number
KS1005
Serial Number Location
Part Number 11325 03/08
1-1
General Information
Section 1
THIS PAGE INTENTIONALLY LEFT BLANK
1-2
Part Number 11325 03/08
Section 2
Installation Instructions
Pre-installation Checklist
Location of Equipment
Follow these guidelines during the installation process:
CONDENSING UNIT
Check the selected installation location to
ensure that racks, braces, floor, foundations,
etc., are adequate to support the weight of the
unit.
For optimum air-cooled equipment performance, these
are the most critical clearance requirements:
•
a sufficient supply of ambient air to the condenser
•
adequate space for removal of the heated
discharged air from the condensing unit area
Verify that system piping is in accordance with
good refrigeration practices.
When brazing refrigerant lines, pass an inert
gas through the line at low pressure to prevent
scaling and oxidation of the tubing. Nitrogen is
recommended.
! Caution
Do not lift the condensing unit assembly by the
refrigerant tubing. Damage may result.
Part Number 11325 03/08
! Caution
If either clearance requirement is ignored, higher
system head pressure will result, causing poor
system operation, shorter equipment life and an
increased risk of equipment failure.
Position the condensing unit:
•
in a clean, dry, level area
•
away from steam or hot air exhaust sources
•
away from corrosive atmospheres
•
away from noise-sensitive areas
•
with adequate support to minimize undesirable
vibration and noise transmission
2-1
Installation Instructions
Section 2
MULTIPLE UNITS
Electrical
Separate side-by-side units with a minimum distance
equal to the width of the largest unit.
FIELD WIRING
AIR FLOW
AIR FLOW
The field wiring must enter through the knockouts
provided. All field wiring must be properly connected
according to the wiring diagram.
MINIMUM
DISTANCE
MINIMUM
DISTANCE
All electrical connections and routing must conform to
local and national codes. Do not modify the factoryinstalled wiring without written factory approval.
BUILDING WALL
(VIEWED FROM ABOVE)
NOTE: The wiring diagram for each unit is located on the
inside of the electrical box within the unit.
MINIMUM
DISTANCE
KS1002
Multiple Units with Horizontal Airflow
Refer to the nameplate rating label on the unit to
determine the correct electrical power supply. Consult
the wiring diagram for proper electrical connections.
WALLS OR OBSTRUCTIONS
To avoid re-circulation of condenser air, and to allow for
proper airflow and access, all sides of the unit should be
positioned a distance equal to the total width of the
condensing unit away from any wall or obstruction.
Increase this distance where possible to increase airflow
and access to the unit.
! Caution
Use copper conductors only. The unit must be
grounded.
If a remote defrost timer is used, the timer must be
located outside the refrigerated space.
The power supply to the unit must meet the following
conditions:
BUILDING
WALL
AIR FLOW
•
Single-phase must be within + 10% or – 5% of
nameplate ratings.
•
Three-phase voltages must be ± 10% of nameplate
ratings.
•
Phase imbalance cannot exceed 2%.
MINIMUM
DISTANCE
MOUNTING SURFACE
KS1003
Space Requirements Near Walls and Obstructions
Important
Connections can become loose during shipment.
Check all wiring connections before operation.
! Caution
Do not position multiple units in a way that would
permit discharge air from one unit to enter the air
inlet of another unit. This could cause system
overheating and equipment failure.
2-2
MULTIPLE EVAPORATOR SYSTEMS
To assure complete defrost with multiple evaporator
systems, wire the defrost termination controls in series.
Part Number 11325 03/08
Section 2
Installation Instructions
Refrigerant Piping Hanger Requirements
INSTALLATION GUIDELINES
Follow these hanger requirements:
Follow these guidelines during the installation process:
•
All tubing must be supported in at least two locations
(near each end of the tubing run).
•
•
Long runs will require additional support. As a guide,
support 3/8" to 7/8" pipe every 5 feet; 1-1/8" to 1-3/8"
every 7 feet; and 1-5/8" to 2-1/8" every 9 to 10 feet.
Purge the dry air charge from the unit by opening the
liquid line service valve or by removing the liquid line
outlet fitting (as applicable).
•
The maximum air exposure for dehydrated
condensing units or filter-driers is 15 minutes. (See
page 2-6 for more information.)
•
Use only refrigeration-grade copper tubing that is
properly sealed against contamination.
•
Suction lines must slope 1/4" per 10 feet toward the
compressor.
•
Install P-type oil traps at the base of each suction
riser of four feet or more to ensure proper oil return to
the compressor.
•
When brazing refrigerant lines, pass an inert gas
through the line at low pressure to prevent scaling
and oxidation of the tubing. Nitrogen is
recommended. Use only silver solder alloys when
brazing.
•
To prevent internal contamination, minimize the use
of flux. Flux only the male portion of the connection.
Remove excess flux after brazing.
•
•
Do not leave a corner unsupported when changing
directions in a run of tubing. Place supports a
maximum of 2 feet in each direction from the corner
of the unit.
Piping attached to a vibrating object (such as a
compressor or compressor base) must be supported
in a manner that will not restrict the movement of the
vibrating object. Rigid mounting will fatigue the
copper tubing.
•
Do not use short radius elbows. Short radius elbows
have points of excessive stress concentration and
are subject to breakage at these points.
•
Once the equipment is in operation, thoroughly
inspect all piping. Add supports as needed.
Installing Model PR Field-charged Lines
Although the condensing unit was thoroughly cleaned
and dehydrated at the factory, take care to prevent
contamination when installing the piping.
Install all refrigeration system components and piping in
accordance with applicable local and national codes.
Follow industry refrigeration guidelines to maintain
proper operation of the system.
NOTE: The interconnecting pipe size is not necessarily
the same size as the stub-out on the condensing unit or
the evaporator.
OIL TRAPS
Install a suction line trap at the evaporator outlet if the
suction line rises to a point higher than the connection
on the evaporator.
To ensure proper oil return, position a suction trap at the
base of all suction risers of four feet or more. The
suction trap must be the same size as the suction line.
Additional traps are necessary for long vertical risers.
Add a trap for each length of pipe (approximately
20 feet) to ensure proper oil return.
! Caution
Refrigerant lines exposed to high ambient
conditions must be insulated to reduce heat pick-up.
This will prevent the formation of flash gas in the
liquid lines.
Part Number 11325 03/08
2-3
Installation Instructions
Section 2
Installing Model PCL Pre-charged Lines
INSTALLATION GUIDELINES
1. Use the evaporator for a template to locate and drill
evaporator mounting holes (1/2" diameter).
Follow these installation guidelines:
•
Route the suction and liquid lines between the
condensing unit and the evaporator. Install lines in
accordance with industry refrigeration guidelines.
•
Remove the dust caps from the quick connect fittings
and verify that the O-rings are intact.
DIAPHRAGMS
Evaporator Mounting
2. Place the four nylon bolts with washers through the
1/2" diameter holes as shown. Note the location of
the 1-5/8" diameter washers.
3. Place the evaporator below the installation location
and lift it straight upward toward the ceiling of the
walk-in.
4. Continue lifting the evaporator toward the ceiling
until the four nylon bolts extend through the
mounting brackets.
CUTTER
5. Install washers and secure in place with nuts.
NOTE: For additional information, refer to the installation
manual supplied with the evaporator.
NYLON BOLT
1” O.D. WASHER
1-5/8” O.D. WASHER
KS1006
Quick Connect Fittings
•
Wipe the coupling seals and threaded surfaces with
a clean cloth to prevent contamination.
•
Lubricate the threads and O-rings on the quick
connect fitting with Polyol Ester oil.
•
Thread the coupling halves together by hand to
ensure proper thread mating.
•
Tighten with a wrench until the coupling bodies
“bottom” or until there is definite resistance. Tighten
an additional 1/4 turn to ensure proper
brass-to-brass seating.
•
After connection, check the quick connect fittings for
refrigerant leaks. If a leak is found, tighten the fitting
until the leak is stopped.
! Caution
Refrigerant quick connect fittings will not reseal.
Remove all refrigerant before attempting to
disconnect the fittings. Once disconnected, the
coupling cannot be re-used.
CEILING PANEL
1” O.D. WASHER
EVAPORATOR
MOUNTING
BRACKET
NUT
NOTE: FASTENERS ARE
SUPPLIED IN THE
MOUNTING KIT
EVAPORATOR
KS1008
Evaporator Mounting Detail
Condenser Unit Mounting
1. Position the condensing unit assembly on the walkin ceiling.
2. Use a sharp punch to pierce four 1/8" diameter
holes, using the condensing unit mounting holes as
a template.
3. Perform operational start-up. See page 3-2.
2-4
Part Number 11325 03/08
Section 2
Installation Instructions
Drain Lines
Panel Penetrations
WALK-IN COOLERS
! Caution
Follow these guidelines:
•
Provide a minimum 4" per one-foot pitch for proper
drainage.
•
A copper drain is recommended.
•
Locate the drain line P-trap outside of the
refrigerated space.
•
Wrap any traps exposed to low ambient
temperatures with a drain line heater.
•
Provide a heater with 20 watts of heat per foot of
drain line.
WALK-IN FREEZERS
All walk-ins must have an air-tight seal. Check that
all penetrations (refrigeration, electrical, etc.),
through the walk-in panels are properly sealed.
Sealing discs are supplied on PCL models to seal
electrical and refrigerant line holes. PR models are not
supplied with sealing discs. The sealing discs are
approximately 3-1/2" in diameter and white in color. The
discs are packaged in the evaporator carton with the
evaporator mounting kit.
To apply a disc to the interior of the walk-in:
1. Slit the disc to the center.
Follow these guidelines:
2. Remove appropriate center sections to reach the
correct hole size.
•
Provide a minimum 4" per one-foot pitch for proper
drainage.
•
A copper drain is recommended.
3. Remove the backing and place the disc in position
around the conduit and copper tubing.
•
Insulate the drain line and seal where it passes
through the wall.
4. Seal the disc in place with sealant.
•
Locate the drain line P-trap outside the refrigerated
space.
•
Wrap any traps exposed to low ambient
temperatures with a drain line heater.
•
To apply a disc to the exterior of the walk-in:
1. Fill the hole with the fiberglass provided.
2. Remove the backing and place the disc in position.
3. Seal the disc in place with sealant.
Provide a heater with 20 watts of heat per foot of
drain line at 0°F, 30 watts per foot at –20°F.
Open Drain
KS1010
Typical Drain Installation
Part Number 11325 03/08
2-5
Installation Instructions
Section 2
Charging Refrigeration System
REFRIGERANT CHARGING
POLYOL ESTER (POE) LUBRICANTS
(USED WITH HFC REFRIGERANTS)
Follow these instructions:
1. Install a liquid line drier in the refrigerant supply line,
between the service gauge and the liquid service
port of the receiver. The liquid line drier will ensure
that all refrigerant is clean and dry.
Polyol Ester (POE) lubricants quickly absorb moisture
from the ambient surroundings. POE lubricants absorb
moisture more rapidly and in greater quantity than
conventional mineral oils. Because moisture levels
greater than 100 PPM will result in system corrosion and
component failure, it is essential that system exposure to
ambient conditions be kept to a minimum.
2. Add liquid refrigerant directly into the receiver tank
when first charging a system that is in a vacuum.
3. Start the system and charge by weight and sight
glass indication.
4. If refrigerant must be added to the system through
the suction side of the compressor, charge in vapor
form only. When charging with R-404A, the
refrigerant must exit the charging cylinder in the
liquid phase. Connect a sight glass between the
charging hose and the compressor suction service
valve to be sure the refrigerant entering the
compressor is in the vapor state.
! Caution
Do not leave a refrigeration system or compressor
using POE oil open to the atmosphere for more than
15 minutes. System corrosion and component
failure could result.
If a system is left open to the atmosphere for more than
15 minutes, the liquid line drier and compressor oil must
be replaced. Drain at least 95% of the oil from the
compressor suction port. Measure the amount of
removed oil, and replace it with exactly the same
amount of new POE oil.
Lubricants are packaged in specially designed, sealed
containers. Once opened, use the lubricant immediately.
Properly dispose of any unused lubricant.
! Caution
Do not leave the system or the compressor open or
unattended.
Mobil EAL™ ARCTIC 22 CC is the preferred Polyol Ester
lubricant because of its particular additives. ICI
Emkarate RL 32S is an acceptable alternative when the
Mobil is not available. These POE lubricants must be
used with HFC refrigerants.
! Caution
Charge with liquid through the high side only.
Introducing liquid refrigerant into the motorcompressor can damage the valves, rods, pistons,
etc.
When charging the system to a clear sight glass (as an
indication of proper charge):
•
Verify the condensing temperature is above 105°F. If
not, reduce the effective condenser face area to raise
the discharge pressure above the equivalent 105°F.
Proceed to charge to clear the sight glass.
•
Adjust the evaporator superheat at this time. (See
“Evaporator Superheat,” page 3-4.)
•
Return to full condenser face area and allow the
system to balance.
! Caution
Verify that there is not an overcharge of refrigerant.
An overcharge may permit liquid refrigerant to enter
the motor-compressor and damage the valves,
rods, pistons, etc.
2-6
Part Number 11325 03/08
Section 2
Installation Instructions
LEAK TESTING
Compressor Mounts
After making all of the connections, perform a leak test
on the entire system. This must include:
•
the condensing unit
On most semi-hermetic compressors with external
spring mounts, the grommets are factory-assembled and
it is only necessary to loosen the nuts.
•
the evaporator
If field assembly is required:
•
all connecting tubing
1. Remove the hold-down nuts.
•
all fittings
2. Place the rubber grommets provided on the studs.
•
all brazed joints
3. Remove the spring steel clips from the mounting
springs
Leak check the entire system, by pressurizing to the low
side test pressure marked on the unit rating label. Repair
all leaks found.
Because HFCs have a smaller molecule size, they tend
to leak more readily than CFCs. Consequently, it is
important to employ proper system evacuation and leak
detection procedures.
4. Install the nuts. Allow approximately 1/16" between
the nut and the rubber grommet for the compressor
to float freely on the springs.
Important
Hermetic compressor springs are mounted
internally in the compressor. Check the compressor
mounting bolts to make certain the securing nuts
have not loosened during shipment.
MOUNTING NUT
(UPPER)
COMPRESSOR
MOUNTING FOOT
MOUNTING
STUD
RUBBER
SPACER
MOUNTING
SPRING
MOUNTING
BASE
LOCKING
DEVICE
MOUNTING NUT
(LOWER)
KS1013
Properly Adjusted Compressor Mount
Part Number 11325 03/08
2-7
Installation Instructions
Section 2
Mounting Defrost Time Clock
Post Installation Checklist
NOTE: Do not locate the timer in the refrigerated area.
Check the following before energizing the equipment:
Walk-in freezers are supplied with a timer for controlling
the initiation and frequency of the defrost cycle.
The timer is shipped loose. Mount it in a convenient
location outside of the refrigerated area.
Verify that the suction, discharge and receiver
service valves are open.
Make sure all electrical and refrigerant
connections are tight.
Check/adjust the room thermostat for desired
temperature.
Check condenser fan motor(s) and evaporator
fan motor(s) for proper operation.
Examine the fan motor mounts carefully for
tightness and proper alignment.
Verify that all refrigerant tubing is properly
insulated, routed and secured.
Verify that all wire routing is appropriate and
properly secured.
Defrost Time Clock
Check the defrost controls for initiation and termination
settings.
Set the fail safe at the length of defrost + 25%.
Example:
24 min. defrost + 25% (6 min.) = 30 min. fail safe
NOTE: If the defrost termination thermostat fails to
close, the fail safe setting on the timer will terminate the
defrost.
2-8
Part Number 11325 03/08
Section 3
Operation
Component Identification
Condenser Fan
and Motor
Condenser Coil
Compressor
Ceiling Panel
Condensing
Unit
Evaporator
Part Number 11325 03/08
3-1
Operation
Section 3
Start-up Procedure
Example:
24 min. defrost + 25% (6 min.) = 30 min. fail safe
! Caution
Do not start the compressor while it is in a vacuum.
7. Check crankcase heater operation (if applicable).
Sequence of Operation
DEFROST TIME CLOCK
! Caution
Do not leave the unit unattended until the system
has reached normal operating conditions.
Operate the system for at least two hours at normal
conditions. If there is no indication of malfunction,
operate the system overnight on automatic controls.
Perform a thorough re-check of the entire system:
1. Check compressor discharge and suction
pressures. If not within system design limits,
determine the cause and take corrective action.
2. Check liquid line sight glass and expansion valve
operation. If there are indications that more
refrigerant is required, leak-test all connections and
system components and repair any leaks before
adding refrigerant.
3. For semi-hermetics, observe the oil level in the
compressor crankcase sight glass. Add oil as
necessary to bring the level to 3/4 of the sight glass
while idle, or 1/2 of the sight glass when running.
4. Check the thermostatic expansion valve(s) for the
proper superheat setting. Verify that the sensing
bulb is insulated, properly located and in positive
contact with the suction line.
NOTE: High superheat causes low refrigeration
capacity. Low superheat promotes liquid slugging and
compressor bearing washout.
The timer starts the defrost cycle automatically at
predetermined times. A setting of two to four defrost
cycles per day is typical. For heavier frost loads,
additional cycles may be required.
When the defrost cycle begins:
1. Switch 2 to 4 opens in the time clock, breaking the
circuit to the room thermostat, liquid line solenoid,
and evaporator fan motors. This allows the
compressor to pump down and shut off.
Simultaneously, switch 1 to 3 closes in the timer,
energizing the defrost heaters.
2. The heaters increase the coil temperature above
32°F, melting the frost off the coil.
3. When the coil warms to 45-55°F, the defrost
termination thermostat closes and energizes the
switching solenoid in the timer. At this time, switch 1
to 3 in the timer opens, terminating the defrost
heaters. Simultaneously, switch 2 to 4 closes in the
time clock, energizing the temperature control
circuit.
4. Suction pressure rises, the low pressure control
closes, and the compressor starts.
5. The fan relay closes when the coil temperature
reaches 23-30°F. This energizes the fan motors.
6. The system operates in the refrigeration cycle until
another defrost cycle is initiated by the timer.
5. Check the line voltage and amperage carefully at the
compressor terminals. Use suitable instruments.
-
Voltage must be within + 10% or – 5% of the
voltage rating indicated on the condensing unit
nameplate. If high or low voltage is indicated,
notify the Power Company.
-
If amperage draw is excessive, immediately
determine the cause and take corrective action.
-
On three-phase motor compressors verify there is
a balanced load.
6. Check the defrost control initiation and termination
settings, and set the length of defrost period. Set the
fail safe at the length of the defrost + 25%.
3-2
Part Number 11325 03/08
Section 3
Operation
Operational Checks and Adjustments
COMPRESSOR SUPERHEAT
Important
The system must be balanced to obtain maximum
capacity and ensure trouble-free operation.
Suction superheat is the critical value that must be
checked. Check the suction superheat at the
compressor as follows:
1. Determine the suction pressure at the suction
service valve of the compressor. Use an accurate
gauge.
2. Determine the saturation temperature at the
observed suction pressure using refrigeration
pressure temperature tables.
3. Measure the temperature of the suction line (using
an accurate thermometer) 6-10 inches away from
the compressor.
! Caution
A high suction superheat will cause excessive
discharge temperatures, which cause a breakdown
of the oil. This causes piston ring wear, and piston
and cylinder wall damage.
System capacity decreases as the suction superheat
increases. For maximum system capacity, keep the
suction superheat as low as practical. Copeland requires
a minimum compressor superheat of 20°F. Kolpak
recommends a compressor superheat between 25°F
and 40°F.
Adjust the expansion valve at the evaporator when
adjustments to the suction superheat are necessary.
Refer to “Evaporator Superheat” on the next page for
more information.
CHECK THE TEMPERATURE AND
PRESSURE.
THEN, CONSULT A
PRESSURE/TEMPERATURE CHART.
4. Subtract the saturation temperature reading (Step 2)
from the measured temperature (Step 3). The
difference is the superheat of suction gas.
P/T
CHART
TEMPERATURE, MINUS
PRESSURE CONVERTED
TO TEMPERATURE,
EQUALS SUPERHEAT
Temperature
! Caution
A low suction superheat can cause liquid to return
to the compressor. This will cause dilution of the oil
and eventual failure of the bearings, rings and
valves.
Pressure
KS1011
Determining Compressor Superheat
Part Number 11325 03/08
3-3
Operation
Section 3
EVAPORATOR SUPERHEAT
TEMPERATURE CONTROL
Check the evaporator superheat once the box has
reached the desired temperature. Generally, systems
with a design TD of 10°F should have a superheat value
of 6-10°F for maximum efficiency.
A temperature control thermostat, a solenoid valve and a
low-pressure switch control all systems.
NOTE: A minimum compressor suction superheat of
20°F may override these recommendations on systems
with short line runs.
Important
The condensing unit must have the discharge
pressure above the equivalent 105°F condensing
pressure. See “Refrigerant Charging,” on page 2-6.
Set the temperature control to the desired temperature.
Use a thermometer to verify accuracy at the set point.
When the temperature reaches the set point, the
temperature control contacts will open. This
de-energizes the solenoid valve and stops the flow of
refrigerant.
The compressor continues to lower the pressure in the
evaporator. When the pressure reaches the set point of
the low pressure switch, the contacts will open, and the
compressor and condenser fan motor(s) cycle off.
EVAPORATOR
To determine the evaporator superheat:
Frost build-up on the evaporator depends on:
1. Determine the suction pressure at the evaporator
outlet. Use an accurate gauge.
•
the temperature of the room
2. Determine the saturation temperature at the
observed suction pressure using the refrigeration
pressure temperature tables.
•
the type of product being stored
•
how often a new product is brought into the room
•
the percentage of time the door to the room is open
3. Measure the temperature of the suction line at the
expansion valve bulb with an accurate thermometer.
It may be necessary to periodically change the number
of defrost cycles per day.
4. Subtract the saturation temperature reading (Step 2)
from the measured temperature (Step 3). The
difference is the superheat of suction gas.
DEFROST TIME CLOCK
Instructions for setting the timer are on the inside cover
of the time clock.
REFRIGERANT EVACUATION
CHECK THE TEMPERATURE AND PRESSURE.
THEN, CONSULT A PRESSURE/TEMPERATURE CHART.
TEMPERATURE, MINUS
PRESSURE CONVERTED TO
TEMPERATURE,
EQUALS SUPERHEAT
1. Connect a reliable vacuum pump to both the low and
high side valves with copper tubing or a high
vacuum hose (1/4" minimum inside diameter).
2. Evacuate the system to 250 microns or lower.
P/T
CHART
NOTE: Kolpak strongly recommends a vacuum decay
test to assure the system is dry and free of leaks.
Pressure
! Caution
Temperature
Determining Evaporator Superheat
3-4
KS1012
Do not use the refrigeration compressor to evacuate
the system. This may cause damage to the
equipment.
Part Number 11325 03/08
Section 4
Maintenance
Cleaning Condensing Unit
! Caution
Failure to keep the condenser coil clean will result in
reduced airflow through the condenser, resulting in
poor system
performance
and
premature
compressor failure.
This will not be covered under your compressor
warranty.
Maintenance Chart
Area
Evaporator
Condenser
General
Task
Check for proper defrosting
Clean the coil and drain pan
Check for proper drainage
Inspect/clean the coil if the air supply is near polluting sources (such as cooking appliances)
Clean the coil surface
Check/tighten all electrical connections
Check all wiring and insulators
Check contactor for proper operation and contact point deterioration
Check all fan motors
Tighten fan set screws, and motor mount nuts and bolts
For semi-hermetics, check the oil level in the system
Check the operation of the control system
Make certain all safety controls are operating properly
Check operation of the drain line heater and examine for cuts and abrasions
Check/tighten all mechanical/flare connections
Part Number 11325 03/08
Frequency
Monthly
Every 6 months
Monthly
Every 3 months
Every 6 months
4-1
Maintenance
Section 4
THIS PAGE INTENTIONALLY LEFT BLANK
4-2
Part Number 11325 03/08
Section 5
Before Calling for Service
Checklist
If a problem arises during operation of your refrigeration system, follow the checklist below before calling service.
Routine adjustments and maintenance procedures are not covered by the warranty.
EVAPORATOR CHECKLIST
Problem
Fan(s) will not operate.
Walk-in temperature too high.
Possible Cause
Main switch open.
Blown fuse(s).
Defective motor.
Defective timer or defrost thermostat.
Unit in defrost cycle.
Thermostat set too high.
Superheat too high.
System low on refrigerant.
Coil iced up.
Ice accumulating on ceiling around
evaporator and/or on
fan guards, venturi, or blades.
Frost on coil after defrost cycle.
Defrost duration is too long.
Fan delay not delaying fans after defrost
period.
Defective defrost thermostat or timer.
Too many defrost cycles per day.
Coil temperature not getting above
freezing point during defrost.
Not enough defrost cycles per day.
Defrost cycle too short.
Ice accumulating in drain
pan.
Part Number 11325 03/08
Defective timer or defrost thermostat.
Defective heater.
Unit not pitched properly.
Drain line plugged.
Defective drain line heater.
Defective timer or thermostat.
To Correct
Close switch.
Replace fuse(s). Check for short circuits
or overload conditions.
Replace motor.
Replace defective component.
Wait for completion of cycle.
Adjust thermostat.
Adjust thermal expansion valve.
Locate and repair leak, recover, evacuate
and recharge.
Manually defrost coil. Check defrost
controls.
Adjust defrost termination thermostat
(if adjustable).
Replace defective defrost thermostat.
Replace defective component.
Reduce number of defrost cycles per
day.
Check heater operation.
Adjust timer for more defrost cycles per
day.
Adjust timer for longer cycle, check
defrost thermostat mounting.
Replace defective component.
Replace heater.
Check and adjust.
Clean drain line.
Replace heater.
Replace defective component.
5-1
Before Calling for Service
Section 5
COMPRESSOR CHECKLIST
Problem
Compressor will not run.
Possible Cause
Main switch open.
Fuse blown.
Thermal overloads tripped.
Defective contactor or coil.
System shut down by safety devices.
No cooling required.
Liquid line solenoid will not open.
Low pressure switch will not close.
Motor electrical trouble.
Loose wiring.
Compressor noisy or vibrating.
High discharge pressure.
Low discharge pressure.
High suction pressure.
Flooding of refrigerant into crankcase.
Improper pipe support.
Worn compressor.
Non-condensables in system.
System overcharged with refrigerant.
Discharge shutoff valve partially closed.
Fan not running.
Insufficient condenser air supply.
Dirty condenser coil.
Faulty head pressure control.
Suction shutoff valve partially closed.
Insufficient refrigerant in system.
Low suction pressure.
Excessive load.
Expansion valve overfeeding.
Low suction pressure.
Lack of refrigerant.
Evaporator dirty or iced.
Clogged liquid line or suction line
filter-drier.
Expansion valve malfunctioning.
Condensing temperature too low.
Improper TXV.
5-2
To Correct
Close switch.
Check electrical circuits and motor
winding for shorts or grounds.
Investigate for possible overloading.
Replace fuse after fault is corrected.
Overloads are automatically reset. Check
unit closely when unit comes back on
line.
Repair or replace.
Determine type and cause of shutdown
and correct.
Wait until cooling is required.
Repair or replace coil.
Replace switch.
Check motor for open windings or short
circuit.
Check all wire junctions. Tighten all
terminal screws.
Check superheat setting of expansion
valve.
Relocate or add hangers.
Replace compressor.
Recover, evacuate and charge.
Remove excess charge.
Open valve.
Check electrical circuit or replace
defective fan motor.
Check for cause and correct.
Clean coil.
Check head pressure control operation.
Open valve.
Locate and repair leak, recover, evacuate
and recharge.
See “Low suction pressure” below.
Reduce load or add additional
equipment.
Secure and insulate TXV bulb or if
required adjust superheat.
Locate and repair leak, recover, evacuate
and charge.
Clean.
Replace filter-drier.
Check and reset for proper superheat.
Check head pressure control.
Check for proper sizing.
Part Number 11325 03/08
Section 5
Before Calling for Service
COMPRESSOR CHECKLIST (Continued)
Problem
Compressor loses oil.
Possible Cause
Lack of refrigerant.
Excessive compression ring blow-by.
Refrigerant floodback.
Compressor thermal protector switch
open.
Improper piping or traps.
Operating beyond design.
Discharge valve partially shut.
Dirty condenser coil.
Overcharged system.
Part Number 11325 03/08
To Correct
Locate and repair leak, recover, evacuate
and recharge.
Replace compressor.
Maintain proper superheat at
compressor.
Correct piping.
Add facilities so that operating conditions
are within allowable limits.
Open valve.
Clean coil.
Correct charge.
5-3
Before Calling for Service
Section 5
Equipment/Service Data Sheet
A permanent data sheet must be prepared on each installation. The owner, the installing contractor and the intended
service agency, will retain a copy.
System Reference Data
The following information should be filled out and signed by Refrigeration Installation Contractor.
Date System Installed:
Installer and Address:
Phone Number:
Service Agency:
Phone Number:
/
/
____________________________________________________________________
____________________________________________________________________
(
)
____________________________________________________________________
____________________________________________________________________
(
)
-
Condensing Unit:
Model Number: _______________________________________________________
Serial Number: _______________________________________________________
Compressor Model Number: _______________________ Compressor Model Number: __________________
Compressor Serial Number: _______________________ Compressor Serial Number: ___________________
Electrical: ________________ Volts:___________ Phase: __________________
Voltage at Compressor:
L1: ____________ L2: ____________ L3: ____________
Amperage at Compressor:
L1: ____________ L2: ____________ L3: ____________
Evaporator(s):
Quantity: _______
Evaporator Model Number: _____________________
Evaporator Model Number: ___________________
Evaporator Serial Number: ______________________
Evaporator Serial Number: ____________________
Electrical: ________________ Volts:___________ Phase: ___________________________________
Expansion Valve Manufacturer/Model Number: _____________________________________________________
Ambient at Start-Up:
Design Box Temperature:
Operating Box Temperature:
Thermostat Setting:
Defrost Settings: ______/day
_______________ °F
_______________ °F
_______________ °F
_______________ °F
_______ minutes failsafe
_______/day
Compressor Discharge Pressure: ______________ PSIG
Compressor Suction Pressure:
______________ PSIG
Suction Line Temperature at Compressor: _________ °F
Discharge Line Temperature at Compressor: _______ °F
Superheat at Compressor:
______________ °F
_______________
_______________
_______________
_______________
_______________
Suction Line Temperature at Evaporator: __________ °F
Superheat at Evaporator:
______________ °F
Evacuation: # Times ____ Final Micron ____
# Times _____
Evaporator Drain Line Trapped Outside of Box:
5-4
Yes ❏
_______________
°F
_______________
°F
_______________
°F
________ minutes failsafe
_______________
_______________
Final Micron ____
PSIG
PSIG
°F
°F
°F
°F
°F
No ❏
Part Number 11325 03/08
© 2008 Manitowoc
Continuing product improvements
may necessitate change of
specifications without notice.
Part Number 11325 03/08
Kolpak
2915 Tennessee Avenue North
Parsons, TN 38363, USA
Ph: 731-847-5365 Fax: 731-847-5387
Visit us online at: www.manitowocfsg.com