Kolpak Refrigeration Systems Installation Manual
Transcription
Kolpak Refrigeration Systems Installation Manual
Refrigeration Systems Installation, Use & Care Manual This manual is updated as new information and models are released. Visit our website for the latest manual. www.manitowocfsg.com Specified #1 Among Walk-ins Part Number 11325 03/08 Safety Notices Read These Before Proceeding: As you work on Manitowoc equipment, be sure to pay close attention to the safety notices in this manual. Disregarding the notices may lead to serious injury and/ or damage to the equipment. Throughout this manual, you will see the following types of safety notices: ! Warning Text in a Warning box alerts you to a potential personal injury situation. Be sure to read the Warning statement before proceeding, and work carefully. ! Caution Text in a Caution box alerts you to a situation in which you could damage the equipment. Be sure to read the Caution statement before proceeding, and work carefully. ! Caution Proper installation, care and maintenance are essential for maximum performance and troublefree operation of your Manitowoc equipment. Read and understand this manual. It contains valuable care and maintenance information. If you encounter problems not covered by this manual, do not proceed, contact Manitowoc Foodservice Group. We will be happy to provide assistance. Important Routine adjustments and maintenance procedures outlined in this manual are not covered by the warranty. ! Warning PERSONAL INJURY POTENTIAL Procedural Notices As you work on Manitowoc equipment, be sure to read the procedural notices in this manual. These notices supply helpful information which may assist you as you work. Do not operate equipment that has been misused, abused, neglected, damaged, or altered/modified from that of original manufactured specifications. NOTE: SAVE THESE INSTRUCTIONS. Throughout this manual, you will see the following types of procedural notices: Important Text in an Important box provides you with information that may help you perform a procedure more efficiently. Disregarding this information will not cause damage or injury, but it may slow you down as you work. NOTE: Text set off as a Note provides you with simple, but useful, extra information about the procedure you are performing. We reserve the right to make product improvements at any time. Specifications and design are subject to change without notice. Table of Contents Section 1 General Information Model Numbers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1 Serial Number Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1 Section 2 Installation Instructions Part Number 11325 03/08 Pre-installation Checklist. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1 Location of Equipment. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1 Condensing Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1 Multiple Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2 Walls or Obstructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2 Electrical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2 Field Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2 Multiple Evaporator Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2 Refrigerant Piping Hanger Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3 Installing Model PR Field-charged Lines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3 Installation Guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3 Oil Traps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3 Installing Model PCL Pre-charged Lines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-4 Installation Guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-4 Evaporator Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-4 Condenser Unit Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-4 Drain Lines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-5 Walk-in Coolers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-5 Walk-in Freezers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-5 Panel Penetrations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-5 Charging Refrigeration System. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-6 Polyol Ester (POE) Lubricants (Used with HFC Refrigerants) . . . . . . . . . . 2-6 Refrigerant Charging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-6 Leak Testing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-7 Compressor Mounts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-7 Mounting Defrost Time Clock . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-8 Post Installation Checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-8 i Table of Contents (continued) Section 3 Operation Component Identification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1 Start-up Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2 Sequence of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2 Defrost Time Clock . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2 Operational Checks and Adjustments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3 Compressor Superheat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3 Evaporator Superheat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4 Temperature Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4 Evaporator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4 Defrost Time Clock . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4 Refrigerant Evacuation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4 Cleaning Condensing Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1 Maintenance Chart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1 Section 4 Maintenance Section 5 Before Calling for Service ii Checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1 Evaporator Checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1 Compressor Checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-2 Equipment/Service Data Sheet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-4 System Reference Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-4 Part Number 11325 03/08 Section 1 General Information Model Numbers This manual covers the following models: Pre-charged Lines PCL Field-charged Lines PR Serial Number Location This number is required when requesting information from your local distributor. The serial number is listed on the SERIAL NUMBER DECAL affixed to the condensing unit assembly. Serial Number KS1005 Serial Number Location Part Number 11325 03/08 1-1 General Information Section 1 THIS PAGE INTENTIONALLY LEFT BLANK 1-2 Part Number 11325 03/08 Section 2 Installation Instructions Pre-installation Checklist Location of Equipment Follow these guidelines during the installation process: CONDENSING UNIT Check the selected installation location to ensure that racks, braces, floor, foundations, etc., are adequate to support the weight of the unit. For optimum air-cooled equipment performance, these are the most critical clearance requirements: • a sufficient supply of ambient air to the condenser • adequate space for removal of the heated discharged air from the condensing unit area Verify that system piping is in accordance with good refrigeration practices. When brazing refrigerant lines, pass an inert gas through the line at low pressure to prevent scaling and oxidation of the tubing. Nitrogen is recommended. ! Caution Do not lift the condensing unit assembly by the refrigerant tubing. Damage may result. Part Number 11325 03/08 ! Caution If either clearance requirement is ignored, higher system head pressure will result, causing poor system operation, shorter equipment life and an increased risk of equipment failure. Position the condensing unit: • in a clean, dry, level area • away from steam or hot air exhaust sources • away from corrosive atmospheres • away from noise-sensitive areas • with adequate support to minimize undesirable vibration and noise transmission 2-1 Installation Instructions Section 2 MULTIPLE UNITS Electrical Separate side-by-side units with a minimum distance equal to the width of the largest unit. FIELD WIRING AIR FLOW AIR FLOW The field wiring must enter through the knockouts provided. All field wiring must be properly connected according to the wiring diagram. MINIMUM DISTANCE MINIMUM DISTANCE All electrical connections and routing must conform to local and national codes. Do not modify the factoryinstalled wiring without written factory approval. BUILDING WALL (VIEWED FROM ABOVE) NOTE: The wiring diagram for each unit is located on the inside of the electrical box within the unit. MINIMUM DISTANCE KS1002 Multiple Units with Horizontal Airflow Refer to the nameplate rating label on the unit to determine the correct electrical power supply. Consult the wiring diagram for proper electrical connections. WALLS OR OBSTRUCTIONS To avoid re-circulation of condenser air, and to allow for proper airflow and access, all sides of the unit should be positioned a distance equal to the total width of the condensing unit away from any wall or obstruction. Increase this distance where possible to increase airflow and access to the unit. ! Caution Use copper conductors only. The unit must be grounded. If a remote defrost timer is used, the timer must be located outside the refrigerated space. The power supply to the unit must meet the following conditions: BUILDING WALL AIR FLOW • Single-phase must be within + 10% or – 5% of nameplate ratings. • Three-phase voltages must be ± 10% of nameplate ratings. • Phase imbalance cannot exceed 2%. MINIMUM DISTANCE MOUNTING SURFACE KS1003 Space Requirements Near Walls and Obstructions Important Connections can become loose during shipment. Check all wiring connections before operation. ! Caution Do not position multiple units in a way that would permit discharge air from one unit to enter the air inlet of another unit. This could cause system overheating and equipment failure. 2-2 MULTIPLE EVAPORATOR SYSTEMS To assure complete defrost with multiple evaporator systems, wire the defrost termination controls in series. Part Number 11325 03/08 Section 2 Installation Instructions Refrigerant Piping Hanger Requirements INSTALLATION GUIDELINES Follow these hanger requirements: Follow these guidelines during the installation process: • All tubing must be supported in at least two locations (near each end of the tubing run). • • Long runs will require additional support. As a guide, support 3/8" to 7/8" pipe every 5 feet; 1-1/8" to 1-3/8" every 7 feet; and 1-5/8" to 2-1/8" every 9 to 10 feet. Purge the dry air charge from the unit by opening the liquid line service valve or by removing the liquid line outlet fitting (as applicable). • The maximum air exposure for dehydrated condensing units or filter-driers is 15 minutes. (See page 2-6 for more information.) • Use only refrigeration-grade copper tubing that is properly sealed against contamination. • Suction lines must slope 1/4" per 10 feet toward the compressor. • Install P-type oil traps at the base of each suction riser of four feet or more to ensure proper oil return to the compressor. • When brazing refrigerant lines, pass an inert gas through the line at low pressure to prevent scaling and oxidation of the tubing. Nitrogen is recommended. Use only silver solder alloys when brazing. • To prevent internal contamination, minimize the use of flux. Flux only the male portion of the connection. Remove excess flux after brazing. • • Do not leave a corner unsupported when changing directions in a run of tubing. Place supports a maximum of 2 feet in each direction from the corner of the unit. Piping attached to a vibrating object (such as a compressor or compressor base) must be supported in a manner that will not restrict the movement of the vibrating object. Rigid mounting will fatigue the copper tubing. • Do not use short radius elbows. Short radius elbows have points of excessive stress concentration and are subject to breakage at these points. • Once the equipment is in operation, thoroughly inspect all piping. Add supports as needed. Installing Model PR Field-charged Lines Although the condensing unit was thoroughly cleaned and dehydrated at the factory, take care to prevent contamination when installing the piping. Install all refrigeration system components and piping in accordance with applicable local and national codes. Follow industry refrigeration guidelines to maintain proper operation of the system. NOTE: The interconnecting pipe size is not necessarily the same size as the stub-out on the condensing unit or the evaporator. OIL TRAPS Install a suction line trap at the evaporator outlet if the suction line rises to a point higher than the connection on the evaporator. To ensure proper oil return, position a suction trap at the base of all suction risers of four feet or more. The suction trap must be the same size as the suction line. Additional traps are necessary for long vertical risers. Add a trap for each length of pipe (approximately 20 feet) to ensure proper oil return. ! Caution Refrigerant lines exposed to high ambient conditions must be insulated to reduce heat pick-up. This will prevent the formation of flash gas in the liquid lines. Part Number 11325 03/08 2-3 Installation Instructions Section 2 Installing Model PCL Pre-charged Lines INSTALLATION GUIDELINES 1. Use the evaporator for a template to locate and drill evaporator mounting holes (1/2" diameter). Follow these installation guidelines: • Route the suction and liquid lines between the condensing unit and the evaporator. Install lines in accordance with industry refrigeration guidelines. • Remove the dust caps from the quick connect fittings and verify that the O-rings are intact. DIAPHRAGMS Evaporator Mounting 2. Place the four nylon bolts with washers through the 1/2" diameter holes as shown. Note the location of the 1-5/8" diameter washers. 3. Place the evaporator below the installation location and lift it straight upward toward the ceiling of the walk-in. 4. Continue lifting the evaporator toward the ceiling until the four nylon bolts extend through the mounting brackets. CUTTER 5. Install washers and secure in place with nuts. NOTE: For additional information, refer to the installation manual supplied with the evaporator. NYLON BOLT 1” O.D. WASHER 1-5/8” O.D. WASHER KS1006 Quick Connect Fittings • Wipe the coupling seals and threaded surfaces with a clean cloth to prevent contamination. • Lubricate the threads and O-rings on the quick connect fitting with Polyol Ester oil. • Thread the coupling halves together by hand to ensure proper thread mating. • Tighten with a wrench until the coupling bodies “bottom” or until there is definite resistance. Tighten an additional 1/4 turn to ensure proper brass-to-brass seating. • After connection, check the quick connect fittings for refrigerant leaks. If a leak is found, tighten the fitting until the leak is stopped. ! Caution Refrigerant quick connect fittings will not reseal. Remove all refrigerant before attempting to disconnect the fittings. Once disconnected, the coupling cannot be re-used. CEILING PANEL 1” O.D. WASHER EVAPORATOR MOUNTING BRACKET NUT NOTE: FASTENERS ARE SUPPLIED IN THE MOUNTING KIT EVAPORATOR KS1008 Evaporator Mounting Detail Condenser Unit Mounting 1. Position the condensing unit assembly on the walkin ceiling. 2. Use a sharp punch to pierce four 1/8" diameter holes, using the condensing unit mounting holes as a template. 3. Perform operational start-up. See page 3-2. 2-4 Part Number 11325 03/08 Section 2 Installation Instructions Drain Lines Panel Penetrations WALK-IN COOLERS ! Caution Follow these guidelines: • Provide a minimum 4" per one-foot pitch for proper drainage. • A copper drain is recommended. • Locate the drain line P-trap outside of the refrigerated space. • Wrap any traps exposed to low ambient temperatures with a drain line heater. • Provide a heater with 20 watts of heat per foot of drain line. WALK-IN FREEZERS All walk-ins must have an air-tight seal. Check that all penetrations (refrigeration, electrical, etc.), through the walk-in panels are properly sealed. Sealing discs are supplied on PCL models to seal electrical and refrigerant line holes. PR models are not supplied with sealing discs. The sealing discs are approximately 3-1/2" in diameter and white in color. The discs are packaged in the evaporator carton with the evaporator mounting kit. To apply a disc to the interior of the walk-in: 1. Slit the disc to the center. Follow these guidelines: 2. Remove appropriate center sections to reach the correct hole size. • Provide a minimum 4" per one-foot pitch for proper drainage. • A copper drain is recommended. 3. Remove the backing and place the disc in position around the conduit and copper tubing. • Insulate the drain line and seal where it passes through the wall. 4. Seal the disc in place with sealant. • Locate the drain line P-trap outside the refrigerated space. • Wrap any traps exposed to low ambient temperatures with a drain line heater. • To apply a disc to the exterior of the walk-in: 1. Fill the hole with the fiberglass provided. 2. Remove the backing and place the disc in position. 3. Seal the disc in place with sealant. Provide a heater with 20 watts of heat per foot of drain line at 0°F, 30 watts per foot at –20°F. Open Drain KS1010 Typical Drain Installation Part Number 11325 03/08 2-5 Installation Instructions Section 2 Charging Refrigeration System REFRIGERANT CHARGING POLYOL ESTER (POE) LUBRICANTS (USED WITH HFC REFRIGERANTS) Follow these instructions: 1. Install a liquid line drier in the refrigerant supply line, between the service gauge and the liquid service port of the receiver. The liquid line drier will ensure that all refrigerant is clean and dry. Polyol Ester (POE) lubricants quickly absorb moisture from the ambient surroundings. POE lubricants absorb moisture more rapidly and in greater quantity than conventional mineral oils. Because moisture levels greater than 100 PPM will result in system corrosion and component failure, it is essential that system exposure to ambient conditions be kept to a minimum. 2. Add liquid refrigerant directly into the receiver tank when first charging a system that is in a vacuum. 3. Start the system and charge by weight and sight glass indication. 4. If refrigerant must be added to the system through the suction side of the compressor, charge in vapor form only. When charging with R-404A, the refrigerant must exit the charging cylinder in the liquid phase. Connect a sight glass between the charging hose and the compressor suction service valve to be sure the refrigerant entering the compressor is in the vapor state. ! Caution Do not leave a refrigeration system or compressor using POE oil open to the atmosphere for more than 15 minutes. System corrosion and component failure could result. If a system is left open to the atmosphere for more than 15 minutes, the liquid line drier and compressor oil must be replaced. Drain at least 95% of the oil from the compressor suction port. Measure the amount of removed oil, and replace it with exactly the same amount of new POE oil. Lubricants are packaged in specially designed, sealed containers. Once opened, use the lubricant immediately. Properly dispose of any unused lubricant. ! Caution Do not leave the system or the compressor open or unattended. Mobil EAL™ ARCTIC 22 CC is the preferred Polyol Ester lubricant because of its particular additives. ICI Emkarate RL 32S is an acceptable alternative when the Mobil is not available. These POE lubricants must be used with HFC refrigerants. ! Caution Charge with liquid through the high side only. Introducing liquid refrigerant into the motorcompressor can damage the valves, rods, pistons, etc. When charging the system to a clear sight glass (as an indication of proper charge): • Verify the condensing temperature is above 105°F. If not, reduce the effective condenser face area to raise the discharge pressure above the equivalent 105°F. Proceed to charge to clear the sight glass. • Adjust the evaporator superheat at this time. (See “Evaporator Superheat,” page 3-4.) • Return to full condenser face area and allow the system to balance. ! Caution Verify that there is not an overcharge of refrigerant. An overcharge may permit liquid refrigerant to enter the motor-compressor and damage the valves, rods, pistons, etc. 2-6 Part Number 11325 03/08 Section 2 Installation Instructions LEAK TESTING Compressor Mounts After making all of the connections, perform a leak test on the entire system. This must include: • the condensing unit On most semi-hermetic compressors with external spring mounts, the grommets are factory-assembled and it is only necessary to loosen the nuts. • the evaporator If field assembly is required: • all connecting tubing 1. Remove the hold-down nuts. • all fittings 2. Place the rubber grommets provided on the studs. • all brazed joints 3. Remove the spring steel clips from the mounting springs Leak check the entire system, by pressurizing to the low side test pressure marked on the unit rating label. Repair all leaks found. Because HFCs have a smaller molecule size, they tend to leak more readily than CFCs. Consequently, it is important to employ proper system evacuation and leak detection procedures. 4. Install the nuts. Allow approximately 1/16" between the nut and the rubber grommet for the compressor to float freely on the springs. Important Hermetic compressor springs are mounted internally in the compressor. Check the compressor mounting bolts to make certain the securing nuts have not loosened during shipment. MOUNTING NUT (UPPER) COMPRESSOR MOUNTING FOOT MOUNTING STUD RUBBER SPACER MOUNTING SPRING MOUNTING BASE LOCKING DEVICE MOUNTING NUT (LOWER) KS1013 Properly Adjusted Compressor Mount Part Number 11325 03/08 2-7 Installation Instructions Section 2 Mounting Defrost Time Clock Post Installation Checklist NOTE: Do not locate the timer in the refrigerated area. Check the following before energizing the equipment: Walk-in freezers are supplied with a timer for controlling the initiation and frequency of the defrost cycle. The timer is shipped loose. Mount it in a convenient location outside of the refrigerated area. Verify that the suction, discharge and receiver service valves are open. Make sure all electrical and refrigerant connections are tight. Check/adjust the room thermostat for desired temperature. Check condenser fan motor(s) and evaporator fan motor(s) for proper operation. Examine the fan motor mounts carefully for tightness and proper alignment. Verify that all refrigerant tubing is properly insulated, routed and secured. Verify that all wire routing is appropriate and properly secured. Defrost Time Clock Check the defrost controls for initiation and termination settings. Set the fail safe at the length of defrost + 25%. Example: 24 min. defrost + 25% (6 min.) = 30 min. fail safe NOTE: If the defrost termination thermostat fails to close, the fail safe setting on the timer will terminate the defrost. 2-8 Part Number 11325 03/08 Section 3 Operation Component Identification Condenser Fan and Motor Condenser Coil Compressor Ceiling Panel Condensing Unit Evaporator Part Number 11325 03/08 3-1 Operation Section 3 Start-up Procedure Example: 24 min. defrost + 25% (6 min.) = 30 min. fail safe ! Caution Do not start the compressor while it is in a vacuum. 7. Check crankcase heater operation (if applicable). Sequence of Operation DEFROST TIME CLOCK ! Caution Do not leave the unit unattended until the system has reached normal operating conditions. Operate the system for at least two hours at normal conditions. If there is no indication of malfunction, operate the system overnight on automatic controls. Perform a thorough re-check of the entire system: 1. Check compressor discharge and suction pressures. If not within system design limits, determine the cause and take corrective action. 2. Check liquid line sight glass and expansion valve operation. If there are indications that more refrigerant is required, leak-test all connections and system components and repair any leaks before adding refrigerant. 3. For semi-hermetics, observe the oil level in the compressor crankcase sight glass. Add oil as necessary to bring the level to 3/4 of the sight glass while idle, or 1/2 of the sight glass when running. 4. Check the thermostatic expansion valve(s) for the proper superheat setting. Verify that the sensing bulb is insulated, properly located and in positive contact with the suction line. NOTE: High superheat causes low refrigeration capacity. Low superheat promotes liquid slugging and compressor bearing washout. The timer starts the defrost cycle automatically at predetermined times. A setting of two to four defrost cycles per day is typical. For heavier frost loads, additional cycles may be required. When the defrost cycle begins: 1. Switch 2 to 4 opens in the time clock, breaking the circuit to the room thermostat, liquid line solenoid, and evaporator fan motors. This allows the compressor to pump down and shut off. Simultaneously, switch 1 to 3 closes in the timer, energizing the defrost heaters. 2. The heaters increase the coil temperature above 32°F, melting the frost off the coil. 3. When the coil warms to 45-55°F, the defrost termination thermostat closes and energizes the switching solenoid in the timer. At this time, switch 1 to 3 in the timer opens, terminating the defrost heaters. Simultaneously, switch 2 to 4 closes in the time clock, energizing the temperature control circuit. 4. Suction pressure rises, the low pressure control closes, and the compressor starts. 5. The fan relay closes when the coil temperature reaches 23-30°F. This energizes the fan motors. 6. The system operates in the refrigeration cycle until another defrost cycle is initiated by the timer. 5. Check the line voltage and amperage carefully at the compressor terminals. Use suitable instruments. - Voltage must be within + 10% or – 5% of the voltage rating indicated on the condensing unit nameplate. If high or low voltage is indicated, notify the Power Company. - If amperage draw is excessive, immediately determine the cause and take corrective action. - On three-phase motor compressors verify there is a balanced load. 6. Check the defrost control initiation and termination settings, and set the length of defrost period. Set the fail safe at the length of the defrost + 25%. 3-2 Part Number 11325 03/08 Section 3 Operation Operational Checks and Adjustments COMPRESSOR SUPERHEAT Important The system must be balanced to obtain maximum capacity and ensure trouble-free operation. Suction superheat is the critical value that must be checked. Check the suction superheat at the compressor as follows: 1. Determine the suction pressure at the suction service valve of the compressor. Use an accurate gauge. 2. Determine the saturation temperature at the observed suction pressure using refrigeration pressure temperature tables. 3. Measure the temperature of the suction line (using an accurate thermometer) 6-10 inches away from the compressor. ! Caution A high suction superheat will cause excessive discharge temperatures, which cause a breakdown of the oil. This causes piston ring wear, and piston and cylinder wall damage. System capacity decreases as the suction superheat increases. For maximum system capacity, keep the suction superheat as low as practical. Copeland requires a minimum compressor superheat of 20°F. Kolpak recommends a compressor superheat between 25°F and 40°F. Adjust the expansion valve at the evaporator when adjustments to the suction superheat are necessary. Refer to “Evaporator Superheat” on the next page for more information. CHECK THE TEMPERATURE AND PRESSURE. THEN, CONSULT A PRESSURE/TEMPERATURE CHART. 4. Subtract the saturation temperature reading (Step 2) from the measured temperature (Step 3). The difference is the superheat of suction gas. P/T CHART TEMPERATURE, MINUS PRESSURE CONVERTED TO TEMPERATURE, EQUALS SUPERHEAT Temperature ! Caution A low suction superheat can cause liquid to return to the compressor. This will cause dilution of the oil and eventual failure of the bearings, rings and valves. Pressure KS1011 Determining Compressor Superheat Part Number 11325 03/08 3-3 Operation Section 3 EVAPORATOR SUPERHEAT TEMPERATURE CONTROL Check the evaporator superheat once the box has reached the desired temperature. Generally, systems with a design TD of 10°F should have a superheat value of 6-10°F for maximum efficiency. A temperature control thermostat, a solenoid valve and a low-pressure switch control all systems. NOTE: A minimum compressor suction superheat of 20°F may override these recommendations on systems with short line runs. Important The condensing unit must have the discharge pressure above the equivalent 105°F condensing pressure. See “Refrigerant Charging,” on page 2-6. Set the temperature control to the desired temperature. Use a thermometer to verify accuracy at the set point. When the temperature reaches the set point, the temperature control contacts will open. This de-energizes the solenoid valve and stops the flow of refrigerant. The compressor continues to lower the pressure in the evaporator. When the pressure reaches the set point of the low pressure switch, the contacts will open, and the compressor and condenser fan motor(s) cycle off. EVAPORATOR To determine the evaporator superheat: Frost build-up on the evaporator depends on: 1. Determine the suction pressure at the evaporator outlet. Use an accurate gauge. • the temperature of the room 2. Determine the saturation temperature at the observed suction pressure using the refrigeration pressure temperature tables. • the type of product being stored • how often a new product is brought into the room • the percentage of time the door to the room is open 3. Measure the temperature of the suction line at the expansion valve bulb with an accurate thermometer. It may be necessary to periodically change the number of defrost cycles per day. 4. Subtract the saturation temperature reading (Step 2) from the measured temperature (Step 3). The difference is the superheat of suction gas. DEFROST TIME CLOCK Instructions for setting the timer are on the inside cover of the time clock. REFRIGERANT EVACUATION CHECK THE TEMPERATURE AND PRESSURE. THEN, CONSULT A PRESSURE/TEMPERATURE CHART. TEMPERATURE, MINUS PRESSURE CONVERTED TO TEMPERATURE, EQUALS SUPERHEAT 1. Connect a reliable vacuum pump to both the low and high side valves with copper tubing or a high vacuum hose (1/4" minimum inside diameter). 2. Evacuate the system to 250 microns or lower. P/T CHART NOTE: Kolpak strongly recommends a vacuum decay test to assure the system is dry and free of leaks. Pressure ! Caution Temperature Determining Evaporator Superheat 3-4 KS1012 Do not use the refrigeration compressor to evacuate the system. This may cause damage to the equipment. Part Number 11325 03/08 Section 4 Maintenance Cleaning Condensing Unit ! Caution Failure to keep the condenser coil clean will result in reduced airflow through the condenser, resulting in poor system performance and premature compressor failure. This will not be covered under your compressor warranty. Maintenance Chart Area Evaporator Condenser General Task Check for proper defrosting Clean the coil and drain pan Check for proper drainage Inspect/clean the coil if the air supply is near polluting sources (such as cooking appliances) Clean the coil surface Check/tighten all electrical connections Check all wiring and insulators Check contactor for proper operation and contact point deterioration Check all fan motors Tighten fan set screws, and motor mount nuts and bolts For semi-hermetics, check the oil level in the system Check the operation of the control system Make certain all safety controls are operating properly Check operation of the drain line heater and examine for cuts and abrasions Check/tighten all mechanical/flare connections Part Number 11325 03/08 Frequency Monthly Every 6 months Monthly Every 3 months Every 6 months 4-1 Maintenance Section 4 THIS PAGE INTENTIONALLY LEFT BLANK 4-2 Part Number 11325 03/08 Section 5 Before Calling for Service Checklist If a problem arises during operation of your refrigeration system, follow the checklist below before calling service. Routine adjustments and maintenance procedures are not covered by the warranty. EVAPORATOR CHECKLIST Problem Fan(s) will not operate. Walk-in temperature too high. Possible Cause Main switch open. Blown fuse(s). Defective motor. Defective timer or defrost thermostat. Unit in defrost cycle. Thermostat set too high. Superheat too high. System low on refrigerant. Coil iced up. Ice accumulating on ceiling around evaporator and/or on fan guards, venturi, or blades. Frost on coil after defrost cycle. Defrost duration is too long. Fan delay not delaying fans after defrost period. Defective defrost thermostat or timer. Too many defrost cycles per day. Coil temperature not getting above freezing point during defrost. Not enough defrost cycles per day. Defrost cycle too short. Ice accumulating in drain pan. Part Number 11325 03/08 Defective timer or defrost thermostat. Defective heater. Unit not pitched properly. Drain line plugged. Defective drain line heater. Defective timer or thermostat. To Correct Close switch. Replace fuse(s). Check for short circuits or overload conditions. Replace motor. Replace defective component. Wait for completion of cycle. Adjust thermostat. Adjust thermal expansion valve. Locate and repair leak, recover, evacuate and recharge. Manually defrost coil. Check defrost controls. Adjust defrost termination thermostat (if adjustable). Replace defective defrost thermostat. Replace defective component. Reduce number of defrost cycles per day. Check heater operation. Adjust timer for more defrost cycles per day. Adjust timer for longer cycle, check defrost thermostat mounting. Replace defective component. Replace heater. Check and adjust. Clean drain line. Replace heater. Replace defective component. 5-1 Before Calling for Service Section 5 COMPRESSOR CHECKLIST Problem Compressor will not run. Possible Cause Main switch open. Fuse blown. Thermal overloads tripped. Defective contactor or coil. System shut down by safety devices. No cooling required. Liquid line solenoid will not open. Low pressure switch will not close. Motor electrical trouble. Loose wiring. Compressor noisy or vibrating. High discharge pressure. Low discharge pressure. High suction pressure. Flooding of refrigerant into crankcase. Improper pipe support. Worn compressor. Non-condensables in system. System overcharged with refrigerant. Discharge shutoff valve partially closed. Fan not running. Insufficient condenser air supply. Dirty condenser coil. Faulty head pressure control. Suction shutoff valve partially closed. Insufficient refrigerant in system. Low suction pressure. Excessive load. Expansion valve overfeeding. Low suction pressure. Lack of refrigerant. Evaporator dirty or iced. Clogged liquid line or suction line filter-drier. Expansion valve malfunctioning. Condensing temperature too low. Improper TXV. 5-2 To Correct Close switch. Check electrical circuits and motor winding for shorts or grounds. Investigate for possible overloading. Replace fuse after fault is corrected. Overloads are automatically reset. Check unit closely when unit comes back on line. Repair or replace. Determine type and cause of shutdown and correct. Wait until cooling is required. Repair or replace coil. Replace switch. Check motor for open windings or short circuit. Check all wire junctions. Tighten all terminal screws. Check superheat setting of expansion valve. Relocate or add hangers. Replace compressor. Recover, evacuate and charge. Remove excess charge. Open valve. Check electrical circuit or replace defective fan motor. Check for cause and correct. Clean coil. Check head pressure control operation. Open valve. Locate and repair leak, recover, evacuate and recharge. See “Low suction pressure” below. Reduce load or add additional equipment. Secure and insulate TXV bulb or if required adjust superheat. Locate and repair leak, recover, evacuate and charge. Clean. Replace filter-drier. Check and reset for proper superheat. Check head pressure control. Check for proper sizing. Part Number 11325 03/08 Section 5 Before Calling for Service COMPRESSOR CHECKLIST (Continued) Problem Compressor loses oil. Possible Cause Lack of refrigerant. Excessive compression ring blow-by. Refrigerant floodback. Compressor thermal protector switch open. Improper piping or traps. Operating beyond design. Discharge valve partially shut. Dirty condenser coil. Overcharged system. Part Number 11325 03/08 To Correct Locate and repair leak, recover, evacuate and recharge. Replace compressor. Maintain proper superheat at compressor. Correct piping. Add facilities so that operating conditions are within allowable limits. Open valve. Clean coil. Correct charge. 5-3 Before Calling for Service Section 5 Equipment/Service Data Sheet A permanent data sheet must be prepared on each installation. The owner, the installing contractor and the intended service agency, will retain a copy. System Reference Data The following information should be filled out and signed by Refrigeration Installation Contractor. Date System Installed: Installer and Address: Phone Number: Service Agency: Phone Number: / / ____________________________________________________________________ ____________________________________________________________________ ( ) ____________________________________________________________________ ____________________________________________________________________ ( ) - Condensing Unit: Model Number: _______________________________________________________ Serial Number: _______________________________________________________ Compressor Model Number: _______________________ Compressor Model Number: __________________ Compressor Serial Number: _______________________ Compressor Serial Number: ___________________ Electrical: ________________ Volts:___________ Phase: __________________ Voltage at Compressor: L1: ____________ L2: ____________ L3: ____________ Amperage at Compressor: L1: ____________ L2: ____________ L3: ____________ Evaporator(s): Quantity: _______ Evaporator Model Number: _____________________ Evaporator Model Number: ___________________ Evaporator Serial Number: ______________________ Evaporator Serial Number: ____________________ Electrical: ________________ Volts:___________ Phase: ___________________________________ Expansion Valve Manufacturer/Model Number: _____________________________________________________ Ambient at Start-Up: Design Box Temperature: Operating Box Temperature: Thermostat Setting: Defrost Settings: ______/day _______________ °F _______________ °F _______________ °F _______________ °F _______ minutes failsafe _______/day Compressor Discharge Pressure: ______________ PSIG Compressor Suction Pressure: ______________ PSIG Suction Line Temperature at Compressor: _________ °F Discharge Line Temperature at Compressor: _______ °F Superheat at Compressor: ______________ °F _______________ _______________ _______________ _______________ _______________ Suction Line Temperature at Evaporator: __________ °F Superheat at Evaporator: ______________ °F Evacuation: # Times ____ Final Micron ____ # Times _____ Evaporator Drain Line Trapped Outside of Box: 5-4 Yes ❏ _______________ °F _______________ °F _______________ °F ________ minutes failsafe _______________ _______________ Final Micron ____ PSIG PSIG °F °F °F °F °F No ❏ Part Number 11325 03/08 © 2008 Manitowoc Continuing product improvements may necessitate change of specifications without notice. Part Number 11325 03/08 Kolpak 2915 Tennessee Avenue North Parsons, TN 38363, USA Ph: 731-847-5365 Fax: 731-847-5387 Visit us online at: www.manitowocfsg.com