Screw Compressor
Transcription
Screw Compressor
R Form No: MES0446A Products That Perform...By People Who Care Screw Compressor Air Cooled Flooded Chillers AFHX Series (High Ambient) 90 to 636 Tons 50Hz TABLE OF CONTENT DESCRIPTION PAGE NO Nomenclature.................................................................................................................................... 2 Advantages of Flooded Chiller............................................................................................................ 3 Unit Features .................................................................................................................................... 5 Operating Benefits............................................................................................................................. 8 Typical Sequence of Operation........................................................................................................... 9 Physical Data...................................................................................................................................10 Performance Data ............................................................................................................................12 Dimensional Data.............................................................................................................................14 Typical Wiring Schematic..................................................................................................................19 Sound Data......................................................................................................................................24 NOMENCLATURE A F HX 110 T - 5 S R Air Cooled Chiller Blank = R22 R = R134a Flooded Evaporator Horizontal Screw Compressor Nominal Tons Single Compressor = 90, 120, 140, 160, 180 Two Compressors = 90T, 110T, 125T, 160T, 190, 220, 250, 295, 315, 340, 375, 435,490 Three Compressors = 545, 595, 635 S Q = Standard = Special 5 6 = 50Hz = 60Hz T = Optional Two Compressors Blank = Standard -2- ADVANTAGES OF FLOODED CHILLER In a flooded cooler the refrigerant surrounds the tubes in the shell and the water to be cooled flows through the tubes. The level of liquid refrigerant in the shell is maintained by the combined action of an electronic level controller and a mod-motor actuated ball valve which modulates the subcooled liquid refrigerant into the cooler. This ensures that all the cooler tubes are completely immersed in the liquid refrigerant for better heat transfer efficiency. For a Direct Expansion (DX) cooler the refrigerant is expanded into the tubes while the chilled water is circulated through the shell. Thermostatic expansion valve is used to throttle the refrigerant in maintaining constant superheat of suction gas to the compressor. input curve over the same conditions. It can be noted that the same compressor when operating with a flooded cooler will generate approximately 8% more cooling capacity while kw input increases negligibly by about 1.8%. Therefore, the same compressor when coupled to a flooded cooler will typically achieved higher cooling capacity performance with correspondingly higher Energy Efficiency Ratio (EER) i.e. (Btu/watt) or lower kw/Ton. FIGURE 1 The following are the advantages of using flooded chiller: 1. Higher Capacity and Higher EER Achievable with the Same Compressor The flooded cooler with all the copper tubes immersed in the “boiling” liquid refrigerant enables a small approach temperature between the “boiling” liquid refrigerant temperature in the shell and the outlet chilled water temperature in the cooler tubes to be achieved. This approach temperature or temperature difference between the evaporating temperature of the boiling liquid refrigerant and the chilled water outlet temperature, for a flooded cooler, is typically less than 3°F. On the contrary, for a DX or Direct Expansion Cooler, the typical approach temperature is between 8°F to 10°F. This simply means that the same compressor in a flooded cooler system will operate at a higher saturated evaporating temperature when compared to the same compressor in a DX-Cooler system, when outlet chilled water temperatures in both cases are set at the same temperature. Figure 1 shows the typical screw compressor capacity performance curve at a particular condensing temperature over saturated evaporating temperature of between 30°F to 50°F, and the typical power -3- A DX cooler uses TXV throttling to maintain about 10 to 15°F suction superheat to prevent liquid flood back to the compressor. In a flooded cooler, the refrigerant boils off in the shell and gas can be sucked out from the top of cooler back to compressor. The suction superheat is usually about 2 to 3°F. Reduction in suction superheat will further increase the capacity performance of the compressor. ADVANTAGES OF FLOODED CHILLER DX coolers are typically designed with higher tube velocities to ensure proper oil return to compressor both at full load and at reduced load. This will contribute to higher refrigerant pressure drop through the cooler. On the contrary, there is very little shell side pressure losses for a flooded cooler. Therefore, lower suction pressure drop in the flooded design will impose less capacity penalty on the compressor and this will further enable the compressor in a flooded cooler to generate more capacity than one with a DX Cooler. 2. Better Part Load Performance The Dunham-Bush Air Cooled Flooded Chiller with its sophisticated microcomputer control and patented oil management system has all cooler tubes completely immersed in the “boiling” liquid refrigerant to achieve superior heat transfer efficiency while ensuring adequate oil return to the compressor(s). This ensures superior fullload efficiency and even better part-load efficiency as the full heat transfer surface areas of the cooler tubes are utilized even at part-load conditions. On the contrary, in the Direct Expansion Cooler, because of the need to maintain adequate refrigerant gas velocities in the cooler tubes for proper oil return, it is typical for certain bundle of cooler tubes to be “blocked” or “baffled off” at part-load conditions. Thus not utilizing the full heat transfer surface areas of the cooler tubes and therefore have a lower efficiency when compared with a flooded cooler chiller at part-load conditions. 3. Excellent Capacity Modulation in Response to Building Loads Dunham-Bush utilizes its state-of-the-art NC25-4 microcomputer controller in combination with the electronic level controller and mod-motor actuated ball valve to ensure instantaneous and precise feeding of liquid refrigerant to the flooded cooler in response to changes in building demand; -4- and maintains precise (±1/2°F) preset outlet chilled water temperatures even at very low load conditions; whereas most of DunhamBush’s competitors, in screw chillers, still utilizes the conventional “centrifugal chiller” method of using orifice plates to modulate refrigerant feed to the cooler; and as such their machines do not function efficiently at low-load conditions and can encounter oil return problem! 4. Cleanable Cooler For a single pass cooler, the end plates at both ends of the water boxes (2 pass only at return end) can be removed easily without dismantling the chilled water piping connections, for inspection and for mechanical tubes cleaning with brushes or auto-brush. This will enable low tube fouling factor in the cooler to be ensured, thus maintaining system efficiency. 5. Lower Water Side Pressure Drop In a DX cooler, the water flows transversely over the outside of the tubes. The water flow is guided with vertical baffles. This will have a higher-pressure drop as compared with the water flow in the tubes of a flooded cooler. In other words, the equivalent flooded chiller will require smaller water pump to operate at lower power consumption. 6. Commonly Used In Large Tonnage Chillers Where Efficiency Is Critical As a general rule, DX-cooler are typically used in small and medium tonnage chillers where efficiency is not important and the low initial cost is the main consideration! However, with increasing energy cost and the drive to reduce global warming, flooded cooler chillers will increasingly become more popular not only in the large tonnage but also in the small and medium tonnage chillers. Dunham-Bush, again, leads the industry in this respect! UNIT FEATURES Microcomputer Control ] Advanced Microcomputer control is a standard feature for all Dunham-Bush rotary screw air cooled chillers monitoring analog and digital inputs to achieve precise control of the major operational and protective functions of the unit. Optional entering chilled water temperature is available. With this option the operator can quickly and accurately read all significant water temperatures and eliminate the need for ofteninaccurate thermometers. External start/ stop command status. Direct Digital Control (DDC) allows fingertip user interaction. Its simple-to-use push button keyboard and menu-driven software provide access to operating conditions, control setpoints and alarm history clearly displayed on a prominent multi-line 80 character alphanumeric display. An easy-to-install, inexpensive modem option allows remote reading of operating parameter updates. The Dunham-Bush microcomputer insures its owner state-of-the-art efficiency and reliability. Display Information The 80 character alphanumeric liquid crystal display utilizes easy to understand menu-driven software. Inexperienced operators can quickly work through these menus to obtain the information they require or to modify control parameters. More experienced operators can bypass the menu systems, if desired, and move directly to their requested control function. At all times, assistance is available to the operator by simply pressing the help key. Easily accessible measurements include: ] Leaving chilled water temperature. ] Evaporator pressure. ] Condenser pressure. Capacity Control ] System voltage. ] Compressor amp compressor. draw of each ] Compressor elapsed run time of each compressor. ] Compressor starts status. ] Oil level switch status. ] Water temperature reset value. ] Water flow switch status. -5- Leaving chilled water temperature control is accomplished by entering the water temperature setpoint and placing the microcomputer in automatic control. The unit will monitor all control functions and move the slide valve to the required operating position. The compressor ramp (loading) cycle is programmable and may be set for specific building requirements. Remote adjustment of the leaving chilled water setpoint is UNIT FEATURES accomplished through either direct connection of other DB control packages to the microcomputer through either the RS485 long distance differential communications port, via terminal or modem connected to the RS232 communication port, or from an external Building Automation System supplying a simple 0 to 5VDC signal. Remote reset of compressor current limit may be accomplished in a similar fashion. System Control The unit may be started or stopped manually, or through the use of an external signal from a Building Automation System. In addition, the microcomputer may be programmed with seven-day operating cycle or other DB control packages may start and stop the system through inter-connecting wiring. System Protection communications port and all hardware or software necessary for remote monitoring and controlled from a simple terminal and optional phone modem. This sophisticated feature makes servicing easier and more convenient to the system. The microcomputer as standard is additionally equipped with history files which may be used to take logs which may be retrieved via the phone modem periodically. Now owners of multiple buildings have a simple and inexpensive method of investigating potential problems quickly and in a highly cost effective manner. Dunham-Bush has an open protocol on its microcomputer to allow direct interface with Building Management Systems. Refrigerating Cycle The refrigerant management system, is very similar to centrifugal water chillers and is shown in the refrigerant cycle diagram below. Liquid refrigerant enters the flooded evaporator uniformly where it absorbs heat from water flowing through the evaporator tubes. The vaporized refrigerant is then drawn into the suction port of the compressor where the compression begins. The following system protection controls will automatically act to insure system reliability: ] Low suction pressure ] High discharge pressure ] Freeze protection ] Low differential pressure ] Low oil level ] Compressor run error ] Power loss ] Chilled water flow loss ] Sensor error ] Compressor over current ] Anti-recycle This partially compressed gas is then joined by additional gas from the flash economizer as the rotors rotate past the vapor injection port at an intermediate pressure. Compressed gaseous refrigerant is then discharged into the integral oil separator where oil, which is contained in the refrigerant vapor, is removed and returned to the oil sump. The microcomputer will retain the latest eight alarm conditions complete with time of failure in an alarm history. This tool will aid service technicians in troubleshooting tasks enabling downtime and nuisance trip-outs to be minimized. Remote Monitoring Fully compressed and superheated refrigerant is then discharged into the condenser, where air is being drawn through the condenser tube by the propeller fan cools and condenses the refrigerant. Liquid refrigerant then passes through the first expansion device and into the flash economizer where flash gas and liquid refrigerant are separated. The gaseous refrigerant is then drawn out of the flash economizer and into the vapor The microcomputer is complete with an RS232 -6- UNIT FEATURES injection port of the compressor. The remaining liquid refrigerant then passes through a second expansion device which reduces refrigerant pressure to evaporator levels where it is then distributed evenly into the evaporator. By removing the flash gas from the flash economizer at an intermediate pressure, the enthalpy of the refrigerant flowing into the evaporator is reduced. This increases the refrigeration effect and improves the efficiency of the refrigeration cycle. Refrigerant flow into and out of the flash economizer is controlled by modulating valves which eliminate the energy wasting hot gas bypass effect inherent with fixed orifices. Part-Load Performance Through the use of flash economizer modulating flow control and multiple compressors, Dunham-Bush air-cooled chillers -7- have best part-load performance characteristics in the industry when measured in accordance with ARI Standard 550/590-98. In most cases, actual building system loads are significantly less than full load design conditions, therefore chillers operate at part load most of the time. Dunham-Bush air-cooled chillers combine the efficient operation of multiple compressors with an economizer cycle and microprocessor control to yield the best total energy efficiency and significant operating saving under any load. When specifying air conditioning equipment, it is important to consider the system load characteristics for the building application. In a typical city, the air conditioning load will vary according to changes in the ambient temperature. Weather data compiled over many years will predict the number of hours that equipment will operate at various load percentages. OPERATING BENEFITS Efficiency and Reliability ] ASHRAE Standard 15 Safety Code for Mechanical Refrigeration. ] IEEE. ENERGY EFFICIENCY ] Designed to provide the greatest amount of REFRIGERANT COMPATIBILITY cooling for the least kilowatt input over the entire operating range of your building. ] Designed to operate with environmentally ] Delivers outstanding efficiency and total energy savings through the utilization of economizer cycle and microcomputercontrolled staging producing greater capacity with fewer compressors. safe and economically smart HCFC-22 with proven efficiency and reliability. ] Consult Factory for use of other HFC refrigerants. ] Maximized performance through computer- matched components and multiple compressors on a single refrigerant circuit. CONTROL FLEXIBILITY ] Microcomputer-based with DDC (direct digital control) features precise push button control over every aspect of operation with built-in standard features that allow extra energy savings on start-up and throughout the life of your equipment. ] High efficiency oil recovery system guarantees removal of oil carried over in the refrigerant and maintains the heat exchangers at their maximum efficiency at both full and part load. ] Insured uniform compressor loading and optimal energy efficiency through microcomputer controls which utilize pressure transducers to measure evaporator and condenser pressure. INSTALLATION EASE ] Dramatic payback in reduced maintenance and overhaul costs both in down time and in labor expenditures. ] Ease of troubleshooting microprocessor retention of functions. ] Lower energy costs resulting from automatic through monitored load monitoring and increased accuracy and efficiency in compressor staging. ] Monitor your chiller's key functions from a ] Factory run tested. remote location with a simple, low cost, phone modem option. ] Proactive control by microcomputer that anticipates problems and takes corrective action before they occur. Controls will unload compressor(s) if head or suction pressure approach limits. This will enable unit to stay on the line while warning operator of potential problems. SAFETY CODE ] ASME Boiler and Pressure Vessel Code, Section VIII Division 1 "Unfired Pressure Vessels". ] JKKP Code. ] ASME Standard B31.5 Refrigeration Piping. -8- TYPICAL SEQUENCE OF OPERATION The Dunham-Bush air-cooled water chiller depends mainly on its on-board microcomputer for control. Operation described is for a twocompressor units and is very similar for single, four-compressor units. and hold leaving chilled water temperature at setpoint. If the applied load is greater than one compressor can handle, it will load fully and then the microcomputer will call for a second compressor. After one minute, the second compressor will start in the same manner as the first. Then both compressors will be commanded to adjust load to 50%. They are gradually loaded up together until the applied load is satisfied. In this way the two compressors share the load equally. For initial start-up, the following conditions must be met: ] Power supply to unit energized. ] Unit circuit breakers in the "on" position. ] Control power switch on for at least 15 minutes. Compressor switches on. ] Reset pressed on microcomputer keypad. If the applied load decreases to the point that both compressors are running at about 40% capacity, the computer shuts down the lag compressor and loads the remaining compressor to about 80%. If applied load decreases further, the remaining compressor unloads proportionately. If applied load decreases to less than the minimum capacity of one compressor, the leaving chilled water temperature will decline to 2°F below setpoint, at which time the lead compressor will shut down. It will restart automatically if leaving chilled water temperature rises to 2°F above setpoint and both 15 minute anti-recycle and one minute start delay timers are satisfied. ] Chilled water pump running and chilled water flow switch made. ] Leaving chilled water temperature at least 2°F above setpoint. ] All safety conditions satisfied. After all above conditions are met, the microcomputer will call for the lead compressor to start. The compressor 15-minute anti-recycle timer is initiated at compressor start. The microcomputer monitors compressor amps, volts, leaving water temperature and suction and discharge pressures. The compressor and cooling capacity is controlled by pulsed signals to load and unload solenoid valves on the compressor. When the compressor starts, it is fully unloaded, yielding about 25% of its full load capacity. As the computer gives it load signals, capacity gradually increases. The rate of compressor loading is governed by ramp control which is adjustable in the computer. During start-up operation, the computer monitors the difference between discharge and suction pressures to ensure that minimum of 30 psi differential is available for compressor lubrication. If the difference falls below a minimum of 30psi, the computer closes refrigerant flow control valves, starving the evaporator, causing evaporator pressure to drop, increasing differential pressure. This is especially helpful at startup, when warm chilled water and low ambient temperature would cause a low head situation. This feature is called EPCAS: Evaporator Pressure Control at Startup. It is one of several proactive control features of the microcomputer which overcome potential problems while continuing operation. The computer responds to leaving chilled water temperature and its rate of change which is proportional and derivative control. If leaving chilled water temperature is within the deadband (+/-0.8°F from setpoint), no load or unload commands are given. If chilled water temperature is above deadband, the computer will continue loading the compressor until a satisfactory rate of decline is observed. If leaving chilled water temperature is below the deadband, the compressor is commanded to unload. Thus the compressor capacity is continuously modulated to match applied load Two additional proactive features are low suction and high discharge pressure override. If operating pressures approach trip level, compressors are unloaded as necessary to continue operation. -9- PHYSICAL SPECIFICATIONS MODEL AFHX 90-5 90T-5 120-5 110T-5 140-5 125T-5 160-5 160T-5 180-5 190-5 220-5 COMPRESSOR MODEL (QTY) HISC 1512 HISC 1309 HISC 1709 HISC 1311 HISC 1711 HISC 1311 HISC 1811 HISC 1509 HISC 1813 HISC 1512 HISC 1512 x1 x2 x1 x2 x1 x 1, x1 x1 x1 x2 x 1, HISC 1509 HISC 1512 HISC 1709 x1 x1 x1 RPM NOMINAL CAPACITY TR MIN. % UNIT CAPACITY REDUCTION 2950 2950 2950 2950 2950 2950 2950 2950 2950 2950 2950 90.0 90.0 120.0 110.0 140.0 125.0 160.0 160.0 180.0 190.0 220.0 25% 12.5% 25% 12.5% 25% 12.5% 25% 12.5% 25% 12.5% 12.5% EVAPORATOR MODEL (QTY) WATER CONNECTOR INCH NOM. WATER FLOW / P D GPM / FT IN WG MIN/ MAX WATER FLOW GPM MIN/ MAX WATER PD FT IN WG B1(1) B1(1) C1(1) C1(1) D1(1) D1(1) D2(1) D2(1) D2(1) B1(2) C1(2) 5 5 5 5 6 6 6 6 6 6 6 216/9.92 216/9.92 288/10.8 264/9.2 336/8.7 300/7.1 384/9.0 384/9.0 432/11.2 456/11.8 528/10.38 74/372 74/372 96/480 96/480 125/577 125/577 140/703 140/703 140/703 148/743 193/958 1.5/26.5 1.5/26.5 1.5/27.0 1.5/27.0 1.5/23.1 1.5/23.1 1.5/27.0 1.5/27.0 1.5/27.0 1.6/28.8 1.7/30.9 CONDENSER COIL ROWS DEEP/ TOTAL FA (SQ.FT) 3/141.2 3/141.2 4/141.2 4/141.2 4/188.2 3/94.1, 4/94.1 4/188.2 4/188.2 3/235.3 3/282.3 3/282.3 6 6 6 6 8 8 8 8 8 12 12 800 800 800 800 800 800 800 800,860 860 800 800,860 MOTOR HP (QTY) 1.5(6) 1.5(6) 1.5(6) 1.5(6) 1.5(8) 1.5(8) 1.5(8) 15.(8) 1.5(8) 1.5(12) 1.5(12) FLA, AMP (QTY) 3.2(6) 3.2(6) 3.2(6) 3.2(6) 3.2(8) 3.2(8) 3.2(8) 3.2(8) 3.2(8) 3.2(12) 3.2(12) TOTAL CFM 77175 77175 72765 72765 98700 94710 94500 99960 101220 153405 157185 45 45 45 45 45 45 45 45 45 45 45 NO. OF FAN FAN DIA. MM MIN. AMBIENT TEMP. (F) AT MIN. LOAD ELECTRICAL NOM. VOLTAGE 415/3/50 415/3/50 415/3/50 415/3/50 415/3/50 415/3/50 415/3/50 415/3/50 415/3/50 415/3/50 415/3/50 UNIT RLA A 152 84(2) 204 96(2) 233 96(1), 127(1) 272 127(1), 159(1) 304 151(1), 152(1) 151(1), 198(1) UNIT MAX. INRUSH A 171 205 223 254 259 291 298 351 330 414 459 GENERAL UNIT LENGTH INCH 149.5 149.5 149.5 149.5 191.5 191.5 191.5 191.5 210 275.5 275.5 UNIT WIDTH INCH 88 88 88 88 88 88 88 88 88 88 88 UNIT HEIGHT INCH 94 94 94 94 94 94 94 94 96 96 96 SHIPPING WEIGHT LBS 8217 8637 9268 9647 10928 11290 11388 12077 12111 15661 16555 OPERATING WEIGHT LBS 8313 8732 9391 9770 11088 11451 11568 12257 12291 15847 16795 199 199 265 243 309 276 354 354 398 420 486 OPERATING CHARGE R-22 LBS - 10 - PHYSICAL SPECIFICATIONS MODEL AFHX 250-5 275-5 295-5 315-5 340-5 375-5 435-5 490-5 545-5 595-5 635-5 COMPRESSOR MODEL (QTY) HISC 1709 HISC 1709 HISC 1711 HISC 1711 HISC 1811 HISC 1813 HISC 1813 HISC 1816 HISC 1813 HISC 1813 HISC 1813 x2 x 1, x2 x 1, x2 x2 x 1, x2 x3 x2, x1 HISC 1711 HISC 1811 HISC 1816 HISC 1816 HISC 1816 x1 x1 x1 x1 x2 RPM NOMINAL CAPACITY TR MIN. % UNIT CAPACITY REDUCTION 2950 2950 2950 2950 2950 2950 2950 2950 2950 2950 2950 250.0 275.0 295.0 315.0 340.0 375.0 435.0 490.0 545.0 595.0 635.0 12.5% 12.5% 12.5% 12.5% 12.5% 12.5% 12.5% 12.5% 8.33% 8.33% 8.33% EVAPORATOR MODEL (QTY) WATER CONNECTOR INCH NOM. WATER FLOW / PD GPM / FT IN WG MIN/ MAX WATER FLOW GPM MIN/ MAX WATER PD FT IN WG. D1(2) D1(2) D1(2) D1(2) D2(2) E1(2) K1(2) K2(2) V2(1) V3(1) V4(1) 8 8 8 8 8 8 8 8 12 12 12 552/6.5 660/8.93 708/10.1 756/11.4 816/10.9 900/9.2 1308/18.2 1428/19.8 1524/28.1 250/1127 250/1127 250/1127 250/1127 283/1408 352/1408 311/1392 341/1361.2 369/1849 386/1931 427/2135 1.6/23.6 1.6/23.6 1.6/23.6 1.6/23.6 1.6/29.4 1.7/20.9 2.1/31.1 2.1/25.7 1.9/34.0 1.9/34.0 2.9/51.6 1044/18.44 1176/19.7 CONDENSER COIL ROWS DEEP/ TOTAL FA (SQ.FT) 4/141.2, 3/141.2 4/141.2, 3/188.2 3/376.4 4/188.2, 3/188.2 4/376.4 4/188.2, 3/235.3 4/577.5 6/577.5 6/577.5 6/641.7 6/641.7 12 14 16 16 16 18 18 18 18 20 20 860 860,800 800 800 860,800 860 860 860 860 860 860 MOTOR HP (QTY) 1.5(12) 1.5(14) 1.5(16) 1.5(16) 1.5(16) 1.5(18) 1.5(18) 4.0(8), 3.0(10) 4.0(18) 4.0(20) 4.0(20) FLA, AMP (QTY) 3.2(12) 3.2(14) 3.2(16) 3.2(16) 3.2(16) 3.2(18) 3.2(18) 7.1(8), 5.5(10) 7.1(18) 7.1(20) 7.1(20) TOTAL CFM 159075 179760 201600 194460 195720 236145 256095 284130 297675 334530 330750 45 45 45 45 45 45 45 45 45 45 45 NO. OF FAN FAN DIA. MM MIN. AMBIENT TEMP. (F) AT MIN. LOAD ELECTRICAL NOM. VOLTAGE 415/3/50 415/3/50 415/3/50 415/3/50 415/3/50 415/3/50 415/3/50 415/3/50 415/3/50 415/3/50 415/3/50 UNIT RLA A 198(2) 198(1), 231(1) 231(2) 231(1), 272(1) 274(1), 272(1) 297(1), 304(1) 298(1), 382(1) 387(1), 388(1) 301(3) 301(2), 388(1) 301(1), 406(2) UNIT MAX. INRUSH A 471 511 572 613 650 775 853 975 1143 1244 1367 GENERAL UNIT LENGTH INCH 275.5 317.5 359.5 359.5 359.5 401.5 401.5 401.5 414 456 456 UNIT WIDTH INCH 88 88 88 88 88 88 88 88 88 88 88 UNIT HEIGHT INCH 96 96 96 96 96 96 120 120 120 120 120 SHIPPING WEIGHT LBS 17337 20198 20866 21329 21855 25475 29245 32661 35138 37751 38221 OPERATING WEIGHT LBS 17689 20510 21179 21641 22207 25915 29719 33182 36378 39017 39453 553 608 652 696 751 829 961 1083 1204 1315 1403 OPERATING CHARGE R-22 LBS - 11 - PERFORMANCE DATA LWT o F 40.0 42.0 44.0 AMBIENT TEMPERATURE, oF MODEL AFHX 85.0 95.0 105.0 115.0 125.0 TR kW TR kW TR kW TR kW TR kW 90-5 90T-5 120-5 110T-5 140-5 125T-5 160-5 160T-5 180-5 190-5 220-5 250-5 275-5 295-5 315-5 340-5 375-5 435-5 490-5 545-5 595-5 635-5 90-5 90T-5 120-5 110T-5 140-5 125T-5 160-5 160T-5 180-5 190-5 220-5 250-5 275-5 295-5 315-5 340-5 375-5 435-5 490-5 545-5 595-5 635-5 86.7 86.6 113.8 107.2 134.9 122.6 155.4 153.2 174.1 183.9 214.6 242.0 265.9 286.5 307.2 331.9 363.1 423.7 475.3 530.2 576.0 616.9 90.1 90.1 118.4 111.5 140.3 127.5 161.6 159.4 181.1 191.3 223.2 251.7 276.6 298.0 319.5 345.2 377.7 440.7 494.3 551.5 599.2 641.7 87.5 91.6 115.4 107.4 130.6 117.4 156.8 155.0 171.8 168.2 195.9 224.4 237.4 256.7 282.0 307.6 338.0 385.0 435.3 504.9 553.0 618.7 88.0 92.1 116.1 108.1 131.3 118.1 157.7 155.8 172.8 169.1 197.1 225.7 238.8 258.2 283.6 309.4 340.1 387.2 438.0 508.0 556.2 622.3 82.0 82.0 107.7 101.5 127.6 116.0 147.0 145.0 164.7 174.3 203.3 229.4 252.0 271.5 291.0 314.5 344.2 401.5 450.5 501.7 545.0 583.7 85.4 85.4 112.2 105.7 132.9 120.8 153.1 151.0 171.6 181.5 211.7 238.8 262.3 282.7 303.0 327.5 358.3 418.0 469.0 522.5 567.6 608.0 97.4 102.0 128.5 119.6 145.4 130.6 174.6 172.5 191.3 187.1 218.0 249.7 264.3 285.8 313.9 342.4 376.3 428.7 484.7 562.3 615.9 689.1 98.0 102.7 129.2 120.3 146.3 131.4 175.6 173.6 192.4 188.2 219.2 251.1 265.8 287.4 315.6 344.3 378.4 431.0 487.4 565.5 619.3 692.9 78.5 78.5 103.1 97.1 122.2 111.1 140.7 138.8 157.7 167.3 195.1 220.2 241.8 260.6 279.3 301.9 330.4 385.3 432.4 480.2 521.7 558.8 81.9 81.9 107.7 101.4 127.5 116.0 146.9 144.9 164.6 174.5 203.6 229.7 252.3 271.9 291.4 315.0 344.6 401.9 451.1 501.4 544.7 583.3 108.3 113.5 142.8 132.9 161.6 145.3 194.1 191.9 212.8 208.3 242.6 277.9 294.0 317.9 349.2 381.0 418.8 476.9 539.4 625.4 684.9 766.2 109.1 114.2 143.8 133.9 162.7 146.2 195.4 193.1 214.1 209.5 244.1 279.6 295.9 319.9 351.3 383.3 421.2 479.8 542.6 629.2 689.1 771.1 73.9 73.9 97.1 91.5 115.0 104.6 132.5 130.7 148.5 158.2 184.4 208.1 228.5 246.4 264.0 285.4 312.3 364.0 408.8 452.2 491.3 526.2 77.4 77.4 101.7 95.8 120.5 109.5 138.8 136.8 155.5 165.4 192.8 217.6 239.0 257.6 276.1 298.4 326.5 380.7 427.4 473.6 514.5 551.1 118.4 124.0 156.0 145.2 176.6 158.7 212.1 209.6 232.4 227.8 265.3 304.0 321.6 347.8 382.0 416.8 458.1 521.6 590.0 683.1 748.1 836.9 119.3 125.0 157.2 146.4 178.0 159.9 213.7 211.2 234.2 229.5 267.2 306.2 324.0 350.3 384.7 419.8 461.3 525.4 594.2 688.2 753.7 843.3 63.0 62.5 82.8 78.0 98.1 89.2 112.9 106.6 126.5 134.8 156.9 176.0 194.3 209.1 224.4 242.2 266.1 309.3 348.4 385.3 418.7 448.2 65.4 64.9 86.0 81.0 101.9 92.6 117.4 110.8 131.5 140.0 162.9 182.6 201.6 217.0 232.9 251.4 276.3 321.1 361.6 400.6 435.2 465.8 122.6 127.3 161.6 150.4 182.9 164.4 219.7 207.9 240.7 235.4 274.2 314.0 332.4 359.3 394.7 430.6 473.2 539.1 609.5 707.4 774.7 866.5 122.6 127.3 161.6 150.4 182.9 164.4 219.7 207.9 240.7 235.4 274.2 314.0 332.4 359.3 394.7 430.6 473.2 539.1 609.5 707.4 774.7 866.5 90-5 90T-5 115-5 110T-5 140-5 125T-5 160-5 160T-5 180-5 190-5 220-5 250-5 275-5 295-5 315-5 340-5 375-5 435-5 490-5 545-5 595-5 635-5 94.1 94.1 123.6 116.5 146.4 133.2 168.7 166.4 189.0 199.1 232.4 262.0 287.9 310.2 332.6 359.3 393.2 458.9 514.6 575.7 625.5 669.9 88.6 92.9 116.8 108.6 132.2 118.7 158.7 156.9 173.9 170.2 198.2 227.1 240.3 259.9 285.4 311.3 342.1 389.7 440.7 511.1 559.7 626.2 90.1 90.1 115.2 110.5 140.1 125.3 160.0 160.1 180.0 190.1 220.7 250.1 275.2 295.0 315.8 341.3 375.0 435.8 490.1 546.2 595.0 635.5 99.5 104.2 127.7 121.1 148.5 131.2 176.8 177.0 194.4 190.3 220.5 253.8 269.2 289.6 317.5 346.4 382.2 433.5 491.6 569.0 624.9 697.2 85.8 85.8 112.8 106.2 133.6 121.5 153.9 151.8 172.5 182.2 212.6 239.8 263.4 283.8 304.3 328.8 359.8 419.8 470.9 525.3 570.7 611.2 109.8 115.0 144.7 134.7 163.8 147.2 196.8 194.4 215.6 210.8 245.6 281.3 297.7 321.8 353.5 385.7 423.9 482.9 546.0 633.6 694.0 776.5 81.3 81.3 106.9 100.7 126.6 115.1 145.8 143.8 163.4 173.1 201.9 227.7 250.2 269.6 289.0 312.3 341.7 398.6 447.3 497.7 540.7 579.1 120.2 125.9 158.5 147.5 179.4 161.2 215.5 212.9 236.1 231.1 269.2 308.4 326.3 352.8 387.6 422.8 464.7 529.3 598.5 693.8 759.9 850.2 68.2 67.6 89.7 84.4 106.2 96.6 122.3 115.5 137.1 145.4 169.3 189.6 209.5 225.4 241.9 261.1 286.8 333.6 375.5 417.6 453.6 485.5 122.6 127.3 161.6 150.4 182.9 164.4 219.7 207.9 240.7 235.4 274.2 314.0 332.4 359.3 394.7 430.6 473.2 539.1 609.5 707.4 774.7 866.5 NOTE : UNIT IS RUNNING ON PART LOAD FOR AMBIENT TEMPERATURE OF 115oF AND ABOVE DUE TO CURRENT LIMITER. - 12 - PERFORMANCE DATA LWT o F 46.0 48.0 50.0 AMBIENT TEMPERATURE, oF MODEL AFHX 85.0 95.0 105.0 115.0 125.0 TR kW TR kW TR kW TR kW TR kW 90-5 90T-5 120-5 110T-5 140-5 125T-5 160-5 160T-5 180-5 190-5 220-5 250-5 275-5 295-5 315-5 340-5 375-5 435-5 490-5 545-5 595-5 635-5 90-5 90T-5 120-5 110T-5 140-5 125T-5 160-5 160T-5 180-5 190-5 220-5 250-5 275-5 295-5 315-5 340-5 375-5 435-5 490-5 545-5 595-5 635-5 97.9 97.9 128.6 121.2 152.4 138.6 175.5 173.1 196.7 206.9 241.5 272.2 299.1 322.2 345.6 373.3 408.4 476.8 534.5 599.2 650.9 697.1 101.7 101.7 133.7 125.9 158.4 144.0 182.4 179.9 204.4 214.6 250.6 282.3 310.3 334.2 358.5 387.2 423.6 494.7 554.5 622.6 676.4 724.4 89.1 93.4 117.5 109.3 133.0 119.4 159.7 157.8 175.0 171.2 199.4 228.5 241.8 261.5 287.2 313.3 344.2 392.1 443.4 514.2 563.2 630.1 89.7 93.9 118.2 110.0 133.8 120.2 160.7 158.7 176.0 172.2 200.6 229.9 243.3 263.1 288.9 315.2 346.3 394.5 446.2 517.3 566.6 634.0 93.0 93.0 122.2 115.1 144.7 131.6 166.7 164.4 186.8 196.6 229.5 258.7 284.3 306.2 328.4 354.7 388.1 453.1 508.0 568.9 618.0 661.9 96.7 96.7 127.0 119.6 150.5 136.8 173.3 170.9 194.2 204.1 238.3 268.5 295.1 317.8 340.9 368.2 402.9 470.4 527.3 591.6 642.7 688.3 99.1 103.8 130.7 121.7 148.0 132.9 177.7 175.5 194.7 190.3 221.7 254.0 268.8 290.7 319.3 348.2 382.7 435.9 492.9 572.1 626.6 701.0 99.7 104.4 131.4 122.3 148.8 133.6 178.7 176.5 195.7 191.4 223.0 255.4 270.3 292.2 321.0 350.1 384.7 438.2 495.5 575.2 630.0 704.8 89.5 89.5 117.7 110.8 139.4 126.7 160.5 158.3 179.9 189.7 221.4 249.6 274.3 295.5 316.8 342.3 374.5 437.1 490.2 548.0 595.3 637.5 93.3 93.3 122.5 115.4 145.2 132.0 167.2 164.9 187.4 197.2 230.2 259.4 285.1 307.1 329.3 355.7 389.2 454.4 509.5 570.6 619.9 663.9 110.4 115.7 145.6 135.5 164.7 148.0 197.9 195.5 216.8 212.0 246.9 282.9 299.3 323.6 355.5 387.8 426.2 485.5 548.9 637.1 697.8 780.7 111.0 116.3 146.4 136.2 165.6 148.8 199.0 196.6 218.0 213.1 248.3 284.5 301.0 325.4 357.4 389.9 428.5 488.1 551.9 640.6 701.6 785.0 85.0 85.0 111.7 105.2 132.3 120.3 152.4 149.0 170.8 180.5 210.6 237.5 260.9 281.1 301.4 325.7 356.3 415.8 466.4 520.2 565.2 605.3 88.7 88.7 116.5 109.8 138.1 125.5 159.0 152.7 178.2 187.9 219.3 247.3 271.7 292.7 313.8 339.1 371.0 433.0 485.6 542.7 589.6 631.5 121.0 126.7 159.5 148.5 180.5 162.2 216.9 212.4 237.6 232.6 271.0 310.4 328.4 355.1 390.1 425.6 467.7 532.7 602.4 698.3 764.8 855.7 121.8 127.5 160.6 149.4 181.7 163.3 218.3 210.0 239.1 234.1 272.7 312.4 330.6 357.4 392.5 428.3 470.7 536.1 606.2 702.8 769.7 861.2 70.8 70.2 93.0 87.6 110.2 100.2 126.9 119.8 142.3 150.5 175.3 196.3 216.9 233.4 250.5 270.4 296.9 345.5 388.7 433.3 470.7 503.8 73.3 72.7 96.4 90.7 114.1 103.8 131.5 124.1 147.3 155.5 181.2 203.0 224.2 241.2 259.0 279.5 306.8 357.2 401.7 448.7 487.5 521.8 122.6 127.3 161.6 150.4 182.9 164.4 219.7 207.9 240.7 235.4 274.2 314.0 332.4 359.3 394.7 430.6 473.2 539.1 609.5 707.4 774.7 866.5 122.6 127.3 161.6 150.4 182.9 164.4 219.7 207.9 240.7 235.4 274.2 314.0 332.4 359.3 394.7 430.6 473.2 539.1 609.5 707.4 774.7 866.5 90-5 90T-5 120-5 110T-5 140-5 125T-5 160-5 160T-5 180-5 190-5 220-5 250-5 275-5 295-5 315-5 340-5 375-5 435-5 490-5 545-5 595-5 635-5 105.6 105.6 138.7 130.7 164.3 149.4 189.3 186.7 212.1 222.7 260.1 293.0 322.1 346.9 372.1 401.9 439.7 513.5 575.5 646.0 701.8 751.6 90.2 94.4 119.0 110.6 134.6 120.9 161.7 159.7 177.1 173.3 201.9 231.4 244.8 264.7 290.7 317.2 348.5 397.0 449.0 520.5 570.1 637.9 100.4 100.4 131.9 124.2 156.2 142.1 180.0 177.5 201.7 211.9 247.5 278.9 306.5 330.1 354.1 382.4 418.4 488.6 547.6 614.3 667.3 714.7 100.2 105.0 132.1 122.9 149.6 134.3 179.6 177.4 196.8 192.4 224.2 256.8 271.7 293.8 322.7 351.9 386.8 440.6 498.2 578.3 633.4 708.6 97.0 97.0 127.4 120.0 150.9 137.2 173.8 171.4 194.8 204.9 239.2 269.6 296.4 319.2 342.3 369.8 404.6 472.3 529.5 593.3 644.5 690.3 111.6 116.9 147.2 137.0 166.5 149.7 200.0 197.7 219.2 214.2 249.6 285.9 302.5 327.0 359.3 391.9 430.7 490.6 554.7 644.1 705.4 789.2 92.4 91.6 121.4 114.3 143.8 130.7 165.6 156.3 185.6 195.5 228.2 257.2 282.7 304.5 326.6 352.8 386.0 450.6 505.3 565.3 614.1 651.2 122.6 127.3 161.6 150.4 182.9 164.4 219.7 207.9 240.7 235.4 274.2 314.0 332.4 359.3 394.7 430.6 473.2 539.1 609.5 707.4 774.7 866.5 75.8 75.2 99.6 93.8 118.0 107.3 135.9 128.3 152.3 160.9 187.5 210.0 231.9 249.5 267.9 289.1 317.4 369.6 415.6 464.0 504.1 539.6 122.6 127.3 161.6 150.4 182.9 164.4 219.7 207.9 240.7 235.4 274.2 314.0 332.4 359.3 394.7 430.6 473.2 539.1 609.5 707.4 774.7 866.5 o NOTE : UNIT IS RUNNING ON PART LOAD FOR AMBIENT TEMPERATURE OF 115 F AND ABOVE DUE TO CURRENT LIMITER. - 13 - DIMENSIONAL DATA AFHX 90-5, 90T-5, 120-5, 110T-5 AFHX 140-5, 125T-5, 160-5, 160T-5 NOTE : ALL DIMENSIONS ARE IN INCHES(MM). - 14 - DIMENSIONAL DATA AFHX 180-5 AFHX 190-5, 220-5, 250-5 NOTE : ALL DIMENSIONS ARE IN INCHES(MM). - 15 - DIMENSIONAL DATA AFHX 275-5 AFHX 295-5, 315-5, 340-5 NOTE : ALL DIMENSIONS ARE IN INCHES(MM). - 16 - DIMENSIONAL DATA AFHX 375-5 AFHX 435-5, 490-5 NOTE : ALL DIMENSIONS ARE IN INCHES(MM). - 17 - DIMENSIONAL DATA AFHX 545-5 AFHX 595-5, 635-5 NOTE : ALL DIMENSIONS ARE IN INCHES(MM). - 18 - TYPICAL WIRING SCHEMATIC TWO COMPRESSORS UNIT - 19 - TYPICAL WIRING SCHEMATIC - 20 - TYPICAL WIRING SCHEMATIC Ω Ω - 21 - TYPICAL WIRING SCHEMATIC - 22 - TYPICAL WIRING SCHEMATIC - 23 - SOUND PRESSURE LEVEL AT 10 METER SPL dBA Model BAND (Hz) 63 125 250 500 1K 2K 4K 8K Total NC AFHX 90-5 36 40 50 57 57 54 50 45 62 55 AFHX 90T-5 36 40 50 58 58 54 50 45 62 60 AFHX 120-5 39 43 53 60 60 57 53 48 65 60 AFHX 110T-5 39 43 53 60 60 56 53 48 64 60 AFHX 140-5 40 45 54 61 61 58 54 49 66 60 AFHX 125T-5 42 47 56 62 62 60 57 51 67 60 AFHX 160-5 40 45 54 63 62 58 54 49 67 60 AFHX 160T-5 41 46 55 61 62 59 56 50 67 60 AFHX 180-5 40 45 58 63 62 58 54 49 67 60 AFHX 190-5 41 45 54 61 61 59 55 50 66 60 AFHX 220-5 43 47 57 63 63 61 57 52 68 60 AFHX 250-5 43 48 57 64 64 61 58 52 69 65 AFHX 275-5 43 48 57 64 64 61 57 52 69 65 AFHX 295-5 43 48 57 64 64 61 57 52 69 65 AFHX 315-5 43 48 57 65 65 61 57 52 69 65 AFHX 340-5 43 48 57 66 65 61 57 52 70 65 AFHX 375-5 44 49 61 66 66 62 58 53 71 65 AFHX 435-5 46 50 62 67 67 63 60 55 72 65 AFHX 490-5 44 55 63 68 68 64 61 56 73 70 AFHX 545-5 49 53 64 69 69 66 63 58 74 70 AFHX 595-5 49 53 65 70 70 67 63 58 75 70 AFHX 635-5 49 53 65 70 70 67 63 58 75 70 - 24 -
Similar documents
ACFX-A 203 to 522 Rotary Screw Flooded Chillers
its capacity range; but it is the most completely “packaged” rotary Screw Compressor for use in flooded chillers! The Dunham-Bush vertical screw compressor and motor assembly is completely housed i...
More informationChiller Water Cooled Liquid - POSEIDON (211-3517kW)
The following system protection controls will automatically act to ensure system reliability: D Low evaporator pressure D High condenser pressure D Freeze protection D Low suction discharge pressur...
More information