Medical Vacuum Systems: Lubricated Vane

Transcription

Medical Vacuum Systems: Lubricated Vane
Product Specification
Medical Vacuum Systems:
Lubricated Vane
GENERAL
The Chemetron® medical vacuum system is designed to
create a suction system to remove unwanted fluids or
gases from hospital/laboratory working areas. The
medical vacuum system package is compliant with the
NFPA 99 requirements for medical vacuum. Note that
larger systems are shipped on 2 or more skids and require
connection of clearly labeled wiring and piping between
skids once they are mounted on-site.
MEDICAL VACUUM SYSTEM
The package shall include multiple vacuum pumps and
associated equipment, one ASME tank and one medical
control panel. Each pump is factory piped to a common
intake manifold. The system shall be completely tested
prior to shipment. Vibration isolation pads are included
with the system.
ROTARY VANE VACUUM PUMP
The medical vacuum pumps shall be of the rotary vane air
cooled design, and manufactured in the USA. Each
vacuum pump shall be direct-driven through a shaft
coupling by a TEFC electric motor. Belt drives shall not
be permitted. Each vacuum pump shall be air cooled and
have absolutely no water requirements. Each vacuum
pump shall have an end (ultimate) vacuum of 29.3" Hg
(15 torr). Lubrication shall be provided by an integral,
fully recirculating oil supply that is filtered by an
automotive-type, spin-on oil filter. Non-recirculating
(once-through) or partial recirculating oil supply systems
shall not be permitted. Each vacuum pump shall be
capable of operation with standard SAE 30 weight oil.
The oil separation systems shall be integral and shall
consist of no less than three stages of internally installed
oil and smoke eliminators through which the exhaust gas
stream must pass. This system shall consist of bulk
separation, oil mist elimination, and smoke elimination,
and shall be capable of removing 99.9+ percent of all oil
and smoke particles from the exhaust gas stream. Each
vacuum pump shall include a built-in anti-suck-back
valve, mounted at the pump inlet, and three sliding vanes.
Each vacuum pump shall be equipped with a 10 micron
inlet filter for removal of particulates. The vacuum
pumps shall be mounted on vibration isolators.
MOTOR
The motor is continuous duty, NEMA rated, C-face,
TEFC, suitable for 208-230, or 460V, 3 phase, 60 hertz
electrical operation.
AIR RECEIVER
The system shall include an ASME rated air receiver
rated for 200 psi MAWP. The tank shall be equipped with
a vacuum gauge, block and by-pass valves, and a manual
drain.
CONTROL PANEL
The system shall include a UL listed control panel in a
NEMA 12 enclosure with the following accessories for
each pump: externally operable disconnect, magnetic
starter with 3-leg overload protection, Hand/Off/Auto
lighted selector switch, minimum run timer to prevent
short cycling of the pump, and hour meter.
Standard features shall also include a main power on
light, timed lead/lag pump alternation, a reserve pump-inuse alarm with visual and audible indications, and duplex
control circuit transformers with fused primary and
secondary protection. All alarms shall have dry contacts
on a labeled terminal strip for remote alarm monitoring,
and an acknowledge pushbutton for horn silencing. The
lag vacuum pump shall be able to start automatically if
the lead vacuum pump fails to operate.
AVAILABLE OPTIONS
 High discharge air temperature shutdown alarm with
visual and audible indicators and dry contacts
 Oil temperature gauges
 Internal tank lining for corrosion resistance
 Tank sight gauge
Product Specification
Medical Vacuum Systems:
Lubricated Vane
Duplex Lubricated Vane
Tankmount
1 - 10 hp
Duplex Lub ricated Vane
MODEL
HP1
DLV010-80T
DLV015-80T
DLV020-80T
DLV030-80T
DLV050-120T1
DLV050-120T2
DLV075-200T
DLV100-200T
1
1-1/2
2
3
5
5
7-1/2
10
No te s :
SCFM @
19" Hg
Each
4
7
11
17
26
38
52
77
NFPA
System
Capacity
4
7
11
17
26
38
52
77
TANK
SIZE
BTU/HR2
dB(A)3
LEVEL
80
80
80
80
120
120
200
200
2,546
3,819
5,092
7,638
12,730
12,730
19,095
25,460
70
70
70
70
71
71
79
81
SYSTEM F.L.A.
208V
10
11
14
19
30
35
44
55
230V
10
11
14
18
28
32
43
53
1 - HP a nd NF P A S ys te m C a pa c ity is s ho wn with o ne o r m o re pum ps in re s e rve pe r NF P A 99
2 - B TU/HR Le ve ls a re s ho wn with re s e rve pum p(s ) o n s ta ndby
3 - dB (A) is s ho wn with o ne pum p in re s e rve pe r NF P A99
460V
6
7
8
10
15
16
23
28
SYSTEM
WEIGHT
730
730
835
894
1,049
1,077
1,727
2,165
Product Specification
Medical Vacuum Systems:
Lubricated Vane
Duplex Lubricated Vane
Vertical
1 - 3 hp
Product Specification
Medical Vacuum Systems:
Lubricated Vane
Duplex Lubricated Vane
Vertical
5 hp
Product Specification
Medical Vacuum Systems:
Lubricated Vane
Duplex Lubricated Vane
Basemount
7-1/2 - 25 hp
Product Specification
Medical Vacuum Systems:
Lubricated Vane
Triplex Lubricated Vane
Basemount
5 - 10 hp
Product Specification
Medical Vacuum Systems:
Lubricated Vane
Triplex Lubricated Vane
Basemount
15 - 25 hp
Product Specification
Medical Vacuum Systems:
Lubricated Vane
Quad Lubricated Vane
Basemount
5 - 25 hp
All specifications are nominal and subject
to change without notice.
Warranty: See Allied Statement of Warranties
for details.
© 2009 Allied Healthcare Products, Inc.®
Construction Customer Service
USA: 800/444-3960
FAX: 314/771-7537
Canada/Mexico: 800/446-0552
FAX: 800/246-6201
International: 314/268-1683
FAX: 314/771-5183
1720 Sublette Avenue
St. Louis, MO 63110 USA
314/771-2400
800/444-3954
www.alliedhpi.com
ISO 13485: 2003
Product Specification
Medical Vacuum Systems: Lubricated Vane
Form 62-00-3800 June 2009

Similar documents