PA C KA G E D G A S E L E C T R I C
LGH
E-Series Rooftop Units
60 HZ
P R O D U C T S P E C I F I C AT I O N S
Bulletin No. LGH-242-360 (09/2012)
ASHRAE 90.1
COMPLIANT
20 to 30 Tons
Net Cooling Capacity - 238,000 to 354,000 Btuh
Gas Input Heat Capacity - 260,000 to 480,000 Btuh
MODEL NUMBER IDENTIFICATION
L G H 300 H 4 B S 1 Y
Voltage
Y = 208/230V-3 phase-60hz
G = 460V-3 phase-60hz
J = 575V-3 phase-60hz
Brand/Family
L = E-Series
Unit Type
G = Packaged Gas Heat w/ Electric Cooling
Major Design Sequence
H = 1st Generation
Nominal Cooling Capacity - Tons
242 = 20 Tons
300 = 25 Tons
360 = 30 Tons
Cooling Efficiency
H = High Efficiency
Minor Design Sequence
1 = 1st Revision
2 = 2nd Revision
3 = 3rd Revision
Heating Type
S = Standard Gas Heat, 2 Stage
M = Medium Gas Heat, 2 Stage
H = High Gas Heat, 2 Stage
Blower Type
B = Constant Air Volume (CAV) Belt Drive
V = Variable Air Volume (VAV) Belt Drive
Refrigerant Type
4 = R-410A
FEATURES AND BENEFITS
H
M
O
K
G
N
D
E
L
C
J
L
E
N
N
O
X
B
F
I
E-Series packaged rooftop unit product line was created to save energy with intelligence by offering some
of the highest energy efficiency ratings available with a powerful, easy to use unit controller. This makes
E-Series rooftop units perfect for business owners looking for an HVAC product with the lowest total cost of
ownership. E-Series rooftop units feature:
•
Hinged Access Panels - Provide quick access to components and protect panels and roof from damage
during servicing.
• Isolated Compressor Compartment - Allows performance check during normal compressor operation
without disrupting airflow.
• Corrosion-Resistant Removable Drain Pan - Provides improved serviceability.
• Thermostatic Expansion Valves - Provide peak cooling performance across the entire application range.
• Scroll Compressors - Standard on all units for reliable, long-term operation.
• Eco-last™ Coil System - Smaller, lighter condenser coil.
• Constant Air Volume (CAV) or Variable Air Volume (VAV) Blower Option - Allows constant or variable
air delivery.
• Auto-Tensioner for Blower Belt - Factory option ensures blower is delivering the proper airflow for comfort, while maximizing efficiency and belt life.
• MERV 13 Filters - Available as factory or field option, provide an enhanced level of indoor air quality, and
can help the building qualify for additional LEED credits.
• Foil-Faced Insulation - Insulation on all internal surfaces that have contact with airflow helps minimize
airborne fibers and improve IAQ.
Intelli-guide™ Control System
Standard on every E-Series rooftop unit, the new Intelli-guide™ unit controller is
the heart of the Allied controls offering. The intuitive user interface makes setup,
troubleshooting and service easier than ever. Each unit tracks the runtime of every
major component and records the date and time when service or maintenance is
performed.
WireRight™ System
The WireRight system simplifies field sensor or thermostat installation through advanced connectors that are
keyed and color-coded to help prevent miswiring. Not only is the wire coloring scheme standardized across all
models, each connection is intuitively labeled to make troubleshooting and servicing quick and easy.
E-Series Packaged Gas / Electric 20 to 30 Ton / Page 2
FEATURES AND BENEFITS
Contents
Accessory Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Blower Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Electrical Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Features And Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
High Altitude Derate . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Intelli-Guide™ Control System . . . . . . . . . . . . . . . . . . . . . . . .8
Model Number Identification . . . . . . . . . . . . . . . . . . . . . . . . .1
Options / Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Outdoor Sound Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
Specifications - Gas Heat . . . . . . . . . . . . . . . . . . . . . . . . . 16
Unit Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Weight Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
APPROVALS
242 models are AHRI Certified to
AHRI Standard 340/360-2007.
300 and 360 models are tested
at conditions included in AHRI
Standard 340/360-2007.
ETL listed
Units are certified by CSA
International.
Components bonded for grounding
to meet safety standards for
servicing required by UL, ULC and
National and Canadian Electrical
Codes..
All models are ASHRAE 90.1-2010
energy efficiency compliant and
meet or exceed requirements of
Section 6.8.
ENERGY STAR® certified units are
designed to use less energy, help
save money on utility bills, and
help protect the environment.
ISO 9001 Registered
Manufacturing Quality System.
WARRANTY
Limited ten years aluminized
heat exchanger, limited fifteen
years optional stainless steel heat
exchanger.
Limited five years on compressors.
Limited three years on the Ecolast™ Coil System.
HEATING SYSTEM
B Aluminized steel inshot burners,
direct spark ignition, electronic
flame sensor, combustion air
inducer, redundant automatic
single or dual stage gas valve with
manual shut-off.
Heat Exchanger
Tubular construction, aluminized
steel, life cycle tested.
Optional Stainless Steel Heat
Exchanger is required if mixed air
temperature is below 45°F.
Electronic Pilot Ignition
Electronic spark igniter provides
positive direct ignition of burners
on each operating cycle. The
system permits main gas valve to
stay open only when the burners
are proven to be lit. Should a
loss of flame occur, the gas valve
closes, shutting off the gas to
the burners. Ignition module has
LED to indicate status and aid in
troubleshooting.
Ignition control is factory installed
in the controls section.
Limit Controls
Factory installed, redundant limit
controls with fixed temperature
setting. Heat limit controls
protect heat exchanger and other
components from overheating.
Safety Switches
Flame roll-out switch, flame sensor
and combustion air inducer proving
switch protect system operation.
REQUIRED SELECTIONS
Limited three years on
Intelli-guide™ Unit Controller.
Gas Input Choice - Order one:
Standard Gas Heat, 2 Stage
(169,000/260,000 Btuh)
Limited one year all other covered
components.
Medium Gas Heat, 2 Stage
(234,000/360,000 Btuh)
High Gas Heat, 2 Stage
(312,000/480,000 Btuh)
E-Series Packaged Gas / Electric 20 to 30 Ton / Page 3
FEATURES AND BENEFITS
HEATING SYSTEM
(CONTINUED)
OPTIONS/ACCESSORIES
Factory Installed
Stainless Steel Heat Exchanger
Required if mixed air temperature
is below 45°F.
Factory or Field Installed
Low Temperature Vestibule
Heater
Electric heater automatically
controls minimum temperature in
gas burner compartment when
temperature is below -40°F. CSA
certified to allow operation of unit
down to -60°F.
Field Installed
Combustion Air Intake
Extensions
Recommended for use with
existing flue extension kits in areas
where high snow areas can block
intake air. Order two kits.
LPG/Propane Kits
Conversion kit to field change over
units from Natural Gas to LPG/
Propane. Order two kits.
Vertical Vent Extension Kit
Use to exhaust flue gases
vertically above unit. Required
when unit vent is too close to fresh
air intakes per building codes. The
vent kit also prevents ice formation
on intake louvers. Order two kits.
Kit contains vent transition, vent
tee, drain cap and installation
hardware.
NOTE - Straight vent pipes (4 in.
B-Vent) and caps are not furnished
and must be field supplied. Refer
to kit instructions for additional
information.
COOLING SYSTEM
Designed to maximize sensible
and latent cooling performance at
design conditions.
System can operate from 0°F
to 125°F without any additional
controls.
R-410A Refrigerant
Non-chlorine
based, ozone
friendly, R-410A.
C Scroll Compressors
Scroll compressors on all models
for high performance, reliability and
quiet operation.
Resiliently mounted on rubber
grommets for quiet operation.
Compressor Crankcase Heaters
Protects against refrigerant
migration that can occur during low
ambient operation.
D Thermal Expansion Valves
Assures optimal performance
throughout the application range.
Removable element head.
E Filter/Driers
High capacity filter/drier protects
the system from dirt and moisture.
High Pressure Switches
Protects the compressors from
overload conditions such as
dirty condenser coils, blocked
refrigerant flow, or loss of outdoor
fan operation. Automatic reset.
Low Pressure Switches
Protects the compressors from low
pressure conditions such as low
refrigerant charge, or low/no airflow.
Freezestats
Protects the evaporator coil from
damaging ice build-up due to
conditions such as low/no airflow,
or low refrigerant charge.
F
Eco-last™ Coil System
Condenser
coil features
lightweight,
all aluminum
brazed fin
construction.
Constructed
of three
components:
a flat extrusion tube, fins inbetween the flat extrusion tube and
two refrigerant manifolds.
Eco-last™ System Features:
• I mproved heat transfer
performance due to high
primary surface area (flat
tubes) versus secondary
surface (fins).
• S
maller internal volume
(reduced refrigerant charge).
• H
igh durability (all aluminum
construction).
• Fewer brazed joints.
• C
ompact design (reduces unit
weight).
• Easy maintenance/cleaning.
Face split design.
Mounting brackets with rubber
inserts secure coil to unit providing
vibration dampening and corrosion
protection.
Angled design in cabinet helps
protect coil from possible contact
or hail damage.
Evaporator Coil
Copper tube construction,
enhanced rippled-edge aluminum
fins, flared shoulder tubing
connections, silver soldered
construction for improved heat
transfer. Factory leak tested. Cross
row circuiting with rifled tubing
optimizes both sensible and latent
cooling capacity. Low fin per inch
count minimizes air pressure drop.
Constant air volume (CAV) models
have face-split evaporator coils.
Variable air volume (VAV) models
have row-split evaporator coils
designed to keep condensate
water off of an inactive part of the
coil so the condensate will not reenter the air stream.
E-Series Packaged Gas / Electric 20 to 30 Ton / Page 4
FEATURES AND BENEFITS
COOLING SYSTEM
(CONTINUED)
Condensate Drain Pan
Plastic pan, sloped to meet
drainage requirements of ASHRAE
62.1.
Side drain connections.
Stainless steel drain pan available
as a factory installed option.
G Outdoor Coil Fan Motors
Thermal overload protected, totally
enclosed, permanently lubricated
ball bearings, shaft up, wire basket
mount.
Outdoor Coil Fans
PVC coated fan guard furnished.
REQUIRED SELECTIONS
Cooling Capacity
Specify nominal cooling capacity of
the unit
OPTIONS/ACCESSORIES
Factory Installed
Discharge Air Temperature
Sensor
Sensor sends information to the
unit controller to cycle up to 2
stages of heating or 4 stages of
cooling to maintain the discharge
air setpoints for heating or cooling.
Optional for CAV units (single
zone or bypass zoning control).
Automatically furnished with all
Variable Air Volume (VAV) units.
Sensor is shipped with the unit
for remote field installation in the
supply duct.
OPTIONS/ACCESSORIES
Factory or Field Installed
Condensate Drain Trap
Field installed only, may be factory
enclosed to ship with unit.
Available in copper or PVC.
Drain Pan Overflow Switch
Monitors condensate level in
drain pan, shuts down unit if drain
becomes clogged.
Stainless Steel Drain Pan
Non-corrosive drain pan.
CABINET
OPTIONS/ACCESSORIES
Factory Installed
H Construction
Heavy-gauge steel panels and full
perimeter heavy-gauge galvanized
steel base rail provides structural
integrity for transportation,
handling, and installation.
Base rails have rigging holes.
Three sides of the base rail have
forklift slots.
Raised edges around duct and
power entry openings in the bottom
of the unit provide additional
protection against water entering
the building.
Airflow Choice
Units are available in downflow
(vertical) or horizontal return air
flow configuration.
Horizontal air flow requires
Horizontal Roof Curb.
Horizontal Return Air Panel Kit
is also required if converting
a downflow configured unit to
horizontal air flow.
Power/Gas Entry
Electrical and gas lines can be
brought through the unit base or
through horizontal access knockouts
Exterior Panels
Constructed of heavy-gauge,
galvanized steel with a two-layer
enamel paint finish.
Insulation
All panels adjacent to conditioned
air are fully insulated with nonhygroscopic fiberglass insulation.
Unit base is fully insulated. The
insulation also serves as an air
seal to the roof curb, eliminating
the need to add a seal during
installation.
Corrosion Protection
A completely flexible immersed
coating with an electrodeposited
dry film process. (AST ElectroFin
E-Coat) Meets Mil Spec
MIL-P-53084, ASTM B117
Standard Method Salt Spray
Testing.
Indoor Corrosion Protection:
- Coated coil
- Painted blower housing
- Painted indoor base
Outdoor Corrosion Protection:
- Coated coil
- Painted outdoor base
Field Installed
Coil Guards
Painted, galvanized steel wire
guards to protect outdoor coil.
Not used with Hail Guards.
Grille Guards
Protects the space between
outdoor coils and main cabinet.
Hail Guards
Constructed of heavy gauge steel,
painted to match cabinet, helps
protect outdoor coils from hail
damage.
Not used with Coil Guards.
Horizontal Return Air Panel Kit
Required for horizontal
applications with Horizontal Roof
Curb, contains panel with return
air opening for field replacement
of existing unit panel and panel to
cover bottom return air opening in
unit, see dimension drawings.
I Hinged Access Panels
Hinged tool-less access panels are
provided for the filter section, the
blower section and compressor/
controls section.
All hinged panels have seals and
quarter-turn latching handles to
provide a tight air and water seal.
E-Series Packaged Gas / Electric 20 to 30 Ton / Page 5
FEATURES AND BENEFITS
J BLOWER
A wide selection of supply air
blower options are available
to meet a variety of airflow
requirements.
Motor
Overload protected, equipped with
ball bearings.
Belt drive motors are offered on
all models and are available in
several different sizes to maximize
air performance.
Motor Efficiency
All blower motors 5 hp and above
meet minimum energy efficiency
standards in accordance with the
Energy Independence and Security
Act (EISA).of 2007.
Supply Air Blower
Forward curved blades, double
inlet, blower wheel is statically and
dynamically balanced. Belt drive
motors with adjustable pulley for
speed change on CAV units..
OPTIONS/ACCESSORIES
Factory Installed
Blower Belt Auto-Tensioner
Provides proper tension to belt
drive blower belt without the need
for regular adjustments. Maintains
airflow and proper performance.
Supply Static Transducer
Transducer sends information to
the Intelli-guide™ Unit Controller to
control VFD blower speed.
Automatically furnished with all
VAV units. Transducer is shipped
with the unit for remote field
installation in the supply duct.
Manual Supply VFD Blower
Bypass Control
Allows variable air volume (VAV)
unit to operate as a constant
air volume (CAV) unit in case of
variable frequency drive (VFD)
failure.
Blower assembly slides out of unit
for servicing.
NOTE - Bypass control is a
manual operation. All supply air
duct registers must be opened
manually.
Grease fittings furnished.
Field Installed
REQUIRED SELECTIONS
Supply Static Limit Switch
Field installed manual reset switch
for supply static high pressure
limit. Prevents exceeding pressure
limit in supply air duct. Optional
Mounting Kit includes tubing and
adaptors.
Supply Air Blower
Specify Constant Air Volume (CAV)
or Variable Air Volume (VAV).
Order Standard or High Efficiency
Blower motor (See Blower Data
Table for specifications).
NOTE - 575V VAV models are
only available with high efficiency
blower motors.
Order one drive kit, see Drive Kit
Specifications Table.
ELECTRICAL
REQUIRED SELECTIONS
Voltage Choice
Specify when ordering base unit.
Circuit Breakers
HACR type. For overload and short
circuit protection. Factory wired and
mounted in the power entry panel.
Current sensitive and temperature
activated. Manual reset.
OPTIONS/ACCESSORIES
Factory Installed
Circuit Breakers
HACR type. For overload and
short circuit protection. Factory
wired and mounted in the power
entry panel. Current sensitive and
temperature activated. Manual
reset.
Phase/Voltage Detection
Phase detection monitors power
supply to assure phase is correct
at unit start-up. If phase is
incorrect, the unit will not start
and an alarm code is reported to
the unit controller. Protects unit
from being started with incorrect
phasing which could lead to
issues such as compressors
running backwards.
Voltage detection monitors power
supply voltage to assure proper
voltage. If voltage is not correct
(over/under voltage conditions)
the unit will not start and an
alarm code is reported to the unit
controller.
Factory or Field Installed
Disconnect Switch
Accessible from outside of unit,
spring loaded weatherproof cover
furnished.
GFI Service Outlets (2)
115V ground fault circuit interrupter
(GFCI) type, non-powered,
field-wired or factory-wired and
powered.
E-Series Packaged Gas / Electric 20 to 30 Ton / Page 6
FEATURES AND BENEFITS
INDOOR AIR QUALITY
K Air Filters
Disposable 2 inch filters furnished
as standard.
OPTIONS/ACCESSORIES
Factory Installed
UVC Germicidal Light Kit
Germicidal lamps emit ultra-violet
(UV-C) energy, which has been
proven to be effective in reducing
microbes such as viruses, bacteria,
yeasts, and molds. This process
either destroys the organism or
controls its ability to reproduce.
UV-C energy greatly reduces the
growth and proliferation of mold
and other bioaerosols (bacteria
and viruses) on illuminated
surfaces (particularly coil and drain
pan).
Lamps are field installed in the
blower/evaporator coil section.
All necessary hardware for
installation is included.
Lamps operate on 110/230V, single
phase power supply. Step-down
transformer is furnished with lamps
when used with 460V and 575V
rooftop units.
Approved by ETL.
Factory or Field Installed
High Efficiency Air Filters
Disposable MERV 8 or MERV 13
(Minimum Efficiency Reporting
Value based on ASHRAE 52.2)
efficiency 2 inch pleated filters.
Blower Access
Supply air blower parts are located
near the access door for easy
servicing and adjustment.
Blower assembly slides out of unit
for servicing.
Replacement Filter Media Kit
With Frame
Replaces existing pleated filter
media. Includes washable metal
mesh screen and metal frame with
clip for holding replaceable nonpleated filter.
Thermal Expansion Valves
Thermal expansion valves are
located near the perimeter of the
unit for easier access.
Field Installed
Coil Cleaning
Slab condenser coils provided for
easier cleaning.
Indoor Air Quality (CO2)
Sensors
Monitors CO2 levels, reports to the
Intelli-guide™ Unit Controller which
adjusts economizer dampers as
needed.
SERVICEABILITY
Designed to streamline general
maintenance and decrease
troubleshooting time.
Diagnostics
Intelli-guide™ Unit Controller
diagnostic scrolling text
pinpoints problems, minimizing
troubleshooting time.
WireRight™ System
Advanced wiring connectors are
keyed and color-coded to prevent
miswiring. Wire coloring scheme
is standardized across all models.
Each connection is intuitively
labeled to make troubleshooting
and servicing quick and easy.
Removable element head allows
change out of element and bulb
without removing the TXV.
Standard Components
A large number of common
maintenance parts are standard
throughout the entire range of
sizes (3-30 tons), reducing the
need to carry a lot of different parts
to the job or maintain in inventory.
Compressor Compartment
Compressors are located near
the perimeter of the unit for easier
access.
Compressors are isolated from the
condenser airflow allowing system
operation checks to be done
without changing the airflow across
the outdoor coils.
Electrical Plugs
Positive connection electrical plugs
are used to connect common
accessories or maintenance parts
for easy removal or installation.
Toolless, Hinged Access
Panels
Large access panels are hinged
and have quarter-turn, latching
handles for quick and easy access
to maintenance areas (filter,
compressor / controls/ blower /
heat section).
E-Series Packaged Gas / Electric 20 to 30 Ton / Page 7
INTELLI-GUIDE™ CONTROL SYSTEM
L INTELLI-GUIDE CONTROLLER
The Intelli-guide Unit Controller is
a microprocessor-based control
board that provides flexible control
of all unit functions.
Intelli-guide™ Features:
Scrolling Display - Scrolls full text
instead of numerical codes.
Push Buttons - Simplified
navigation during setup and
diagnostics.
Guided Setup Procedure Insures proper installation and
setup of the rooftop unit.
Profile setup - Copy key setpoints
between units with the same
configuration greatly reducing
setup time.
USB Port - Easily download and
transfer unit
information via a USB
flash drive and also
interface with Allied
Unit Controller
Software.
Self Test Mode - Confirm proper
component and system operation.
Time Clock with Run-time
Information
Built-In Functions Include:
Adjustable Blower On/Off Delay
Blower Air Delivery Options
Built-in Control Parameter
Defaults
Compressor Time-Off Delay
DDC Compatible
Dirty Filter Switch Input
Discharge Air Temperature
Control
Display/Sensor Readout
Economizer Control Options See Economizer / Outdoor Air /
Exhaust Options.
Fresh Air Tempering
Extensive Unit Diagnostics Over 100 diagnostic and status
messages in English.
Exhaust Fan Control Modes Fresh air damper position.
Permanent Diagnostic Code Storage
Field Changeable Control
Setpoints - Over 200 different
control setpoints.
Indoor Air Quality Input Demand Control Ventilation ready
Low Ambient Controls - Cooling
operation down to 0°F.
Gas Valve Time Delay Between
First and Second Stage
Minimum Compressor Run Time
Network Capable - Can be daisy
chained to other units or controls.
Night Setback Mode
Return Air Temperature Limit
Control
Safety Switch Input - Allows
Controller to respond to a external
safety switch trip.
Service Relay Output
Smoke Alarm Mode - Four choices.
Staging - up to 2 heat / 2 cool with
standard Intelli-guide unit controller.
Up to 2 heat / 4 cool with add-on
control board.
“Strike Three” Protection
Gas Reheat Control Simultaneous heating and cooling
operation for controlling humidity
for process air applications such as
supermarkets.
Thermostat Bounce Delay
Warm Up Mode Delay
LED Indicators
PC Interface - For use with PC
with optional Unit Controller
software.
VAV Control
Zone Sensor Operation - Controls
zone temperature.
CONTROLS OPTIONS
Factory or Field Installed
OPTIONS / ACCESSORIES
Factory or Field Installed
Humidity Sensor Kit
Humidity sensor required
with Supermarket reheat field
selectable option.
Blower Proving Switch
Monitors blower operation, shuts
down unit if blower fails.
Dirty Filter Switch
Senses static pressure increase
indicating dirty filter condition.
NOTE - Intelli-guide Control System
features shown vary with the type of
rooftop unit the control is installed in.
NOTE - See separate Intelli-guide
Control System Product Specifications
Bulletin for additional information.
E-Series Packaged Gas / Electric 20 to 30 Ton / Page 8
Fresh Air Tempering
Used in applications with high
outside air requirements. The
Controller energizes the first stage
heat as needed to maintain a
minimum supply air temperature
for comfort, regardless of the
thermostat demand. When ordered
as a factory option, the sensor
ships with the unit but must be field
installed.
Smoke Detector
Photoelectric type, installed in
supply air section, return air
section or both sections. Available
with power board and single
sensor (supply or return) or power
board and two sensors (supply and
return). Power board located in unit
control compartment.
Interoperability via BACnet® or
LonTalk® Protocols
Communication compatible with
third-party automation systems that
support the BACnet Application
Specific Controller device
profile, LonMark® Space Comfort
Controller functional profile, or
LonMark Discharge Air Controller
functional profile.
Commercial Control Systems
Aftermarket DDC
Novar® Unit Controller and options.
Thermostats
Control system and thermostat
options. Aftermarket unit controller
options.
Field Installed
OPTIONS / ACCESSORIES
N ECONOMIZER/EXHAUST
OPTIONS
Factory or Field Installed
Economizer - Downflow or
Horizontal With Air Hood
Parallel gear-driven action return
air and outdoor air dampers,
plug-in connections to unit, nylon
bearings, neoprene seals, 24volt, fully-modulating, spring
return motor, adjustable minimum
damper position. Outdoor air hoods
for economizer and downflow
barometric relief dampers furnished.
Choice of economizer control
options:
1. Differential Sensible Control
Factory setting. Uses outdoor
air and return air sensors that
are furnished with the unit. The
Intelli-guide™ Unit Controller
compares outdoor air and
return air and using setpoints,
enables the economizer when
the outdoor air temperature is
below the configured setpoint
and cooler than return air.
NOTE - Differential Sensible
Control can be configured in the
field to provide Offset Differential
Sensible Control or Single
Sensible Control.
In Offset Differential Sensible
Control mode, the economizer
is enabled if the temperature
differential (offset) between
outdoor air and return air reaches
the configured setpoint.
In Single Sensible Control mode,
the economizer is enabled when
outdoor air temperature falls below
the configured setpoint.
2. Global Control
The unit controller
communicates with a DDC
system with one global sensor
(enthalpy or sensible) to
determine whether outside air
is suitable for free cooling on all
units connected to the control
system. Sensor must be field
provided.
3. Single Enthalpy Control
Outdoor air enthalpy sensor
enables economizer if the
outdoor enthalpy is less than the
setpoint of the board.
4. Differential Enthalpy Control
Two solid-state enthalpy sensors
allow the economizer control to
select between outdoor air or
return air, whichever has lower
enthalpy.
Outdoor Air CFM Control
Maintains constant outdoor air
CFM levels for VAV units with
variable frequency drives on
the supply fan and varying unit
airflows. Using information from a
velocity sensor located in the units’
outdoor air section, the Intelliguide™ Unit Controller changes
the economizer position to help
minimize the effect of supply fan
speed changes on outdoor air
CFM levels. Setpoint for outdoor
air CFM is established by field
testing.
NOTE - Not available with Demand
Control Ventilation (CO2 Sensor).
Downflow Barometric Relief
Dampers
O Allow relief of excess air, aluminum
blade dampers prevent blow back
and outdoor air infiltration during
off cycle, bird screen furnished.
Hood for downflow barometric
relief dampers is factory installed
when dampers are factory installed
with economizer. Hood is furnished
with dampers when ordered for
field installation.
P Standard Static Power Exhaust
Fans
Three, 1/3 hp motors with 20 in.,
five blade propeller-type fans with
a total power input of 1125 Watts
and a total air volume of 12,800
cfm at 0 in. w.g.
Motor is inherently protected and
enclosed for maximum protection
from weather, dust and corrosion.
Installs internal to unit for downflow
applications only with economizer
option, provides exhaust air
pressure relief, interlocked to
run when return air dampers are
closed and supply air blower is
operating, fan runs when outdoor
air dampers are 50% open
(adjustable), motor is overload
protected, steel cabinet and hood
painted to match unit, requires
optional Downflow Economizer
Barometric Relief Dampers. See
Standard Static Power Exhaust
Blower Tables.
High Static Power Exhaust
Fans
Choice of 50% (two, 2 hp motors)
or 100% (three, 2 hp motors)
centrifugal-type power exhaust.
Overload and sub-fuse protected,
equipped with ball bearings.
Forward curved blades, blower
wheel is statically and dynamically
balanced. Constant volume high
static power exhaust fans have
adjustable pulleys for speed
adjustments and are controlled by
damper position.
Variable air volume units (with
variable frequency drive) have
100% capacity and can be ordered
with an optional VFD bypass. Fans
feature solid-state analog pressure
transducer control which senses
differential pressure between
conditioned space and outdoor
air to regulate fan speed. See
High Static Power Exhaust Blower
Tables.
NOTE - High Static Power Exhaust
is field installed but must be
ordered at the same time as the
rooftop unit so the unit can be
factory configured for this option.
Power Exhaust Control Options:
Damper Position Control
Intelli-guide™ Unit Controller
controls exhaust fan based on
economizer damper position. For
Standard or High Static Power
Exhaust (without VFD) Fans only.
Differential Pressure
Transducer
Differential pressure transducer
compares atmospheric pressure
to conditioned space static
pressure for controlling exhaust
fan. Transducer is factory installed
in the power exhaust section. For
High Static Power Exhaust (with
VFD) fans only.
E-Series Packaged Gas / Electric 20 to 30 Ton / Page 9
FEATURES AND BENEFITS
ECONOMIZER/EXHAUST
OPTIONS (CONTINUED)
Field Installed
Horizontal Barometric Relief
Dampers
For use when unit is configured for
horizontal applications requiring an
economizer.
Allows relief of excess air.
Aluminum blade dampers prevent
blow back and outdoor air
infiltration during off cycle.
Field installed in return air duct.
Bird screen and hood furnished.
OUTDOOR AIR OPTIONS
Factory or Field Installed
Outdoor Air Damper Downflow or Horizontal With
Air Hood
Linked mechanical dampers, 0 to
25% (fixed) outdoor air adjustable,
installs in unit. Includes outdoor air
hood.
Automatic model features fully
modulating spring return damper
motor with plug-in connection.
Manual model features parallel
blade, gear-driven dampers with
adjustable fixed position.
ROOF CURBS
Nailer strip furnished, mates
to unit, US National Roofing
Contractors Approved, shipped
knocked down.
Downflow
Clip Curbs (Full Perimeter) Uses interlocking tabs to fasten
corners together. No tools required.
Available in 14 inch, 18 inch and
24 inch heights.
Standard Curbs - Curb corners
fasten together with furnished
hardware. Full perimeter curbs are
also available.
Available in 14 inch and 24 inch
heights
Horizontal
Converts unit from downflow to
horizontal (side) air flow, return air
is on unit, supply air is on curb, see
dimension drawings.
Requires Horizontal Return Air
Panel Kit.
Available in 37 inch and 41 inch
heights.
Optional Insulation Kit is available
to help prevent sweating.
Minimum mixed air temperature in
heating mode is 30°F. Maximum
mixed air temperature in cooling
mode is 90°F.
E-Series Packaged Gas / Electric 20 to 30 Ton / Page 10
CEILING DIFFUSERS
Ceiling Diffusers
(Flush or Step-Down)
Aluminum grilles, large center
grille, insulated diffuser box with
flanges, hanging rings furnished,
interior transition (even air flow),
internally sealed (prevents
recirculation), adapts to T-bar
ceiling grids or plaster ceilings.
Transitions (Supply and
Return)
Used with diffusers, installs
in roof curb, galvanized steel
construction, flanges furnished for
duct connection to diffusers, fully
insulated.
OPTIONS / ACCESSORIES
Model
Number
Unit Model No.
Catalog
Number
242
300
360
PVC - C1TRAP20AD2
76M26
OX
OX
OX
Copper - C1TRAP10AD2
76W27
OX
OX
OX
Factory
O
O
O
E1SNSR71AD1
68W88
OX
OX
OX
High
Factory
O
O
O
R-410A
Factory
O
O
O
Item Description
COOLING SYSTEM
Condensate Drain Trap
Corrosion Protection
Drain Pan Overflow Switch
Efficiency
Refrigerant Type
Plastic Condensate Drain Pan
Stainless Steel Condensate Drain Pan
C1DPAN10D-1-
Factory
O
O
O
84W76
OX
OX
OX
GAS HEAT
Combustion Air Intake Extensions (Order 2 Kits)
Gas Heat Input
LPG/Propane Conversion Kits (Order 2 Kits)
Low Temperature Vesibule Heater
C1EXTN10FF1
89L97
X
X
X
Standard - 260 kBtuh input
Factory
O
O
O
Medium - 360 kBtuh input
Factory
O
O
O
High - 480 kBtuh input
Factory
O
O
O
Standard Heat - LTALPGK-130
72M94
X
X
X
Medium Heat - LTALPGK-180
72M95
X
X
X
High Heat - LTALPGK-240
72M96
X
X
X
208/230V-3ph - C1LTVH10C-1Y
58W28
OX
OX
OX
460V-3ph - C1LTVH10C-1G
58W29
OX
OX
OX
575V-3ph - C1LTVH10C-1J
58W30
OX
OX
OX
Factory
O
O
O
C1EXTN20FF1
42W16
X
X
X
Belt Drive (standard efficiency) - 5 hp
Factory
O
O
O
Stainless Steel Heat Exchanger
Vertical Vent Extension
BLOWER - SUPPLY AIR
Motors
Belt Drive (standard efficiency) - 7.5 hp
Factory
O
O
O
Belt Drive (standard efficiency) - 10 hp
Factory
O
O
O
Manual Supply VFD Blower Bypass (VAV units w/VFD only)
Factory
O
O
O
Drive Kits
See Blower Data Tables for usage and
selection
Kit #1 740-895 rpm
Factory
O
O
O
Kit #2 870-1045 rpm
Factory
O
O
O
Kit #3 715-880 rpm
Factory
O
O
O
Kit #4 770-965 rpm
Factory
O
O
O
Kit #5 660-810 rpm
Factory
O
O
O
Kit #6 770-965 rpm
Factory
O
O
O
Kit #7 570-720 rpm
Factory
O
O
O
Kit #8 480-630 rpm
Factory
O
O
O
Kit #9 410-535 rpm
Factory
O
O
O
Blower Belt Auto-Tensioner
Factory
O
O
O
CABINET
Coil Guards
Grille Guards
Hail Guards
Horizontal Return Air Panel Kit
C1GARD29D-1
84W63
X
X
X
C1GARD39D-1-
86K30
X
X
X
C1GARD19D-1
84W62
X
X
X
38K48
X
X
X
NOTE - Catalog and model numbers shown are for ordering field installed accessories.
OX - Configure To Order (Factory Installed) or Field Installed
O = Configure To Order (Factory Installed)
X = Field Installed
E-Series Packaged Gas / Electric 20 to 30 Ton / Page 11
OPTIONS / ACCESSORIES
242
300
360
C1SNSR35FF1
53W65
OX
OX
OX
Intelli-guide™ System - BACnet® Module - C0CTRL60AE1L
Intelli-guide™ System - LonTalk® Module - C0CTRL65FF1
Novar® ETM-2051 Unit Controller - E0CTRL30C1 Novar® LSE
Dirty Filter Switch
E1SNSR55C-1
Discharge Air Temperature Sensor
Fresh Air Tempering
C1SNSR75AD1
Smoke Detector - Supply or Return (Power board and one sensor)
C1SNSR44C-1
Smoke Detector - Supply and Return (Power board and two sensors)
C1SNSR43C-1
Supply Static Limit Switch
C0SNSR11AE1
Supply Static Limit Switch - Mounting Kit
C0SNSR12AE1
Supply Static Transducer
C0SNSR20AE1
INDOOR AIR QUALITY
Air Filters
High Efficiency Air Filters
MERV 8 - C1FLTR15D-120 x 20 x 2 - order 12 per unit
MERV 13 - C1FLTR40D-1Replaceable Media Filter with Metal Mesh Frame (includes NonC1FLTR30D-1Pleated Filter Media) 20 x 20 x 2- order 12 per unit
Indoor Air Quality (CO2) Sensors
Sensor - Wall-mount, off-white plastic cover with LCD display
C0SNSR50AE1L
Sensor - Wall-mount, off-white plastic cover, no display
C0SNSR52AE1L
C0SNSR51AE1L
Sensor - Black plastic case with LCD display, rated for plenum mounting
Sensor - Wall-mount, black plastic case, no display, rated for plenum
C0MISC19AE1
mounting
C0MISC19AE1CO2 Sensor Duct Mounting Kit - for downflow applications
C0MISC16AE1Aspiration Box - for duct mounting non-plenum rated CO2 sensors
(87N53 or 77N39)
UVC Germicidal Light Kit
1
UVC Light Kit (110/230v-1ph)
C1UVCL10C-1
ELECTRICAL
Voltage 60 hz
208/230V - 3 phase
460V - 3 phase
575V - 3 phase
Disconnect Switch - See Electrical
80 amp
Accessories Tables on page 31 for selection
150 amp
250 amp
GFI Service
15 amp non-powered, field-wired (208/230V, 460V only) LTAGFIK10/15
Outlets
15 amp factory-wired and powered (208/230V, 460V only)
20 amp non-powered, field-wired (575V only)
Phase/Voltage Detection
ECONOMIZER
Economizer
Economizer - (Hood Furnished)
E1ECON15D-1
Economizer Controls
Differential Enthalpy
Order 2 - C1SNSR64FF1
Sensible Control
Sensor is Furnished
Single Enthalpy
C1SNSR64FF1
Global, Enthalpy
Sensor Field Provided
Sensor is Furnished
Differential Sensible
Outdoor Air CFM Control
Barometric Relief
Downflow Barometric Relief Dampers - (Hood Furnished)
E1DAMP60D-1
Horizontal Barometric Relief Dampers - (Hood Furnished)
LAGEDH30/36
59W51
54W27
64W74
Factory
53W68
Factory
58W63
83W40
83W41
79M80
79M81
78M19
OX
OX
OX
O
OX
O
OX
OX
OX
X
X
X
OX
OX
OX
O
OX
O
OX
OX
OX
X
X
X
OX
OX
OX
O
OX
O
OX
OX
OX
X
X
X
54W21
52W39
44N60
OX
OX
X
OX
OX
X
OX
OX
X
77N39
87N53
87N52
87N54
X
X
X
X
X
X
X
X
X
X
X
X
85L43
90N43
X
X
X
X
X
X
Factory
O
O
O
Factory
Factory
Factory
54W88
54W89
90W82
74M70
Factory
Factory
Factory
O
O
O
OX
OX
OX
OX
O
O
O
O
O
O
OX
OX
OX
OX
O
O
O
O
O
O
OX
OX
OX
OX
O
O
O
74W43
OX
OX
OX
53W64
Factory
53W64
Factory
Factory
Factory
OX
O
OX
O
O
O
OX
O
OX
O
O
O
OX
O
OX
O
O
O
76W17
33K78
OX
OX
OX
OX
OX
OX
CONTROLS
Blower Proving Switch
1
Model
Number
Unit Model No.
Catalog
Number
Item Description
Lamps operate on 110/230V, single phase power supply. Step-down transformer is furnished with lamps when used with 460V and 575V rooftop units.
NOTE - Catalog and model numbers shown are for ordering field installed accessories.
OX - Configure To Order (Factory Installed) or Field Installed
O = Configure To Order (Factory Installed)
X = Field Installed
E-Series Packaged Gas / Electric 20 to 30 Ton / Page 12
OPTIONS / ACCESSORIES
Model
Number
Item Description
Catalog
Number
Unit Model No.
242
300
360
OUTDOOR AIR
Outdoor Air Dampers - Motorized - (Hood Furnished)
E1DAMP25D-1-
74W44
OX
OX
OX
Outdoor Air Dampers - Manual - (Hood Furnished)
E1DAMO15D-1-
74W45
OX
OX
OX
208/230V - E1PWRE40D-1Y
74W21
OX
OX
OX
460V - E1PWRE40D-1G
74W22
OX
OX
OX
575V - E1PWRE40D-1J
74W23
OX
OX
OX
POWER EXHAUST
Standard Static
High Static - 50%
High Static - 100%
100% with VFD
100% with VFD and Bypass
208/230V - Drive Kit #1 (405-533 rpm) - LAPEB30/36AY
83M83
X
X
X
208/230V - Drive Kit #2 (531-731 rpm) - LAPEB30/36BY
84M34
X
X
X
208/230V - Drive Kit #3 (731-932 rpm) - LAPEB30/36CY
84M35
X
X
X
460V - Drive Kit #1 (405-533 rpm) - LAPEB30/36AG
83M84
X
X
X
460V - Drive Kit #2 (531-731 rpm) - LAPEB30/36BG
84M36
X
X
X
460V - Drive Kit #3 (731-932 rpm) - LAPEB30/36CG
84M37
X
X
X
575V - Drive Kit #1 (405-533 rpm) - LAPEB30/36AJ
83M85
X
X
X
575V - Drive Kit #2 (531-731 rpm) - LAPEB30/36BJ
84M38
X
X
X
575V - Drive Kit #3 (731-932 rpm) - LAPEB30/36CJ
84M39
X
X
X
208/230V - Drive Kit #1 (406-533 rpm) - LAPEB30/36DY
83M86
X
X
X
208/230V - Drive Kit #2 (531-731 rpm) - LAPEB30/36EY
84M40
X
X
X
208/230V - Drive Kit #3 (731-932 rpm) - LAPEB30/36FY
84M41
X
X
X
460V - Drive Kit #1 (406-533 rpm) - LAPEB30/36DG
83M87
X
X
X
460V - Drive Kit #2 (531-731 rpm) - LAPEB30/36EG
84M42
X
X
X
460V - Drive Kit #3 (731-932 rpm) - LAPEB30/36FG
84M43
X
X
X
575V - Drive Kit #1 (406-533 rpm) - LAPEB30/36DJ
83M88
X
X
X
575V - Drive Kit #2 (531-731 rpm) - LAPEB30/36EJ
84M44
X
X
X
575V - Drive Kit #3 (731-932 rpm) - LAPEB30/36FJ
84M45
X
X
X
208/230V - LAPEV30/36GY
83M89
X
X
X
460V - LAPEV30/36GG
83M90
X
X
X
575V - LAPEV30/36GJ
83M91
X
X
X
208/230V - LAPEV30/36HY
83M92
X
X
X
460V - LAPEV30/36HG
83M93
X
X
X
575V - LAPEV30/36HJ
83M94
X
X
X
NOTE - Catalog and model numbers shown are for ordering field installed accessories.
OX - Configure To Order (Factory Installed) or Field Installed
O = Configure To Order (Factory Installed)
X = Field Installed
E-Series Packaged Gas / Electric 20 to 30 Ton / Page 13
OPTIONS / ACCESSORIES
Model
Number
Item Description
Unit Model No.
Catalog
Number
242
300
360
ROOF CURBS - DOWNFLOW
Clip Curbs
14 in. height
LARMF30/36S-14
54K58
X
X
18 in. height
LARMF30/36S-18
54K59
X
X
24 in. height
LARMF30/36S-24
Standard Curbs
14 in. height
LARMF18/36-14
24 in. height
LARMF18/36-24
Standard Curbs - Full Perimeter
14 in. height
S6CURB1012124 in. height
S6CURB11121ROOF CURBS - HORIZONTAL (REQUIRES (HORIZONTAL AIR PANEL KIT)
Standard Curbs
30 in. height - slab applications
LARMFH30/36-30
41 in. height - rooftop applications
LARMFH30/36-41
Clip Curbs
30 in. height - slab applications
LARMFH30/36S-30 (Canada Only)
41 in. height - rooftop applications
LARMFH30/36S-41 (Canada Only)
Horizontal Return Air Panel Kit (Required)
54K60
X
X
X
16K87
16K88
X
X
X
X
X
X
30W15
30W16
X
X
X
X
X
X
33K79
38K54
X
X
X
X
X
X
45K71
45K72
38K48
X
X
X
X
X
X
X
X
X
for LARMFH30/36-30
73K33
X
X
X
for LARMFH30/36-41
73K35
X
X
X
Insulation Kit For Standard Horizontal Curbs
CEILING DIFFUSERS
Step-Down - Order one
LARTD30/36
35K25
X
X
X
LARTD30/36S (Canada Only)
45K74
X
X
X
LAFD30/36
35K24
X
X
X
LAFD30/36S (Canada Only)
45K75
X
X
X
LASRT30/36
33K80
X
X
X
Flush - Order one
Transitions (Supply and Return) - Order one
NOTE - Catalog and model numbers shown are for ordering field installed accessories.
OX - Configure To Order (Factory Installed) or Field Installed
O = Configure To Order (Factory Installed)
X = Field Installed
E-Series Packaged Gas / Electric 20 to 30 Ton / Page 14
SPECIFICATIONS
General Data
Nominal Tonnage
Model Number
Efficiency Type
Blower Type
20 Ton
LGH242H4V
High
Variable Air
Volume VAV
244,000
238,000
6800
19.3
12.3
15.5
R-410A
8 lbs. 0 oz.
8 lbs. 0 oz.
8 lbs. 8 oz.
8 lbs. 8 oz.
25 Ton
LGH300H4B
High
Constant Air
Volume CAV
310,000
300,000
8100
25.9
11.6
12.5
R-410A
9 lbs. 4 oz.
9 lbs. 0 oz.
9 lbs. 0 oz.
9 lbs. 0 oz.
25 Ton
30 Ton
30 Ton
LGH300H4V
LGH360H4B
LGH360H4V
High
High
High
Variable Air
Constant Air
Variable Air
Volume VAV
Volume CAV
Volume VAV
310,000
370,000
370,000
300,000
354,000
354,000
8100
9600
9600
25.4
33.4
33.4
11.6
10.6
10.6
14.3
11.5
13.5
R-410A
R-410A
R-410A
8 lbs. 0 oz.
9 lbs. 0 oz.
8 lbs. 0 oz.
8 lbs. 0 oz.
8 lbs. 0 oz.
8 lbs. 0 oz.
8 lbs. 0 oz.
9 lbs. 0 oz.
8 lbs. 0 oz.
8 lbs. 8 oz.
7 lbs. 8 oz.
8 lbs. 0 oz.
See page 16
Scroll (4)
Scroll (4)
Scroll (4)
Scroll (4)
68.3
68.3
68.3
68.3
1
1
1
1
23
23
23
23
(6) 1/3
(6) 1/3
(6) 1/3
(6) 1/3
1075
1075
1075
1075
2500
2500
2500
2500
(6) 24
(6) 24
(6) 24
(6) 24
3
3
3
3
21,500
21,500
21,500
21,500
31.40
31.40
31.40
31.40
3/8
3/8
3/8
3/8
4
4
4
4
14
14
14
14
(1) 1 in. NPT
(1) 1 in. NPT
(1) 1 in. NPT
(1) 1 in. NPT
Balance port TXV, removable head
5 hp, 7.5 hp, 10 hp
5 hp, 7.5 hp, 10 hp
Gross Cooling Capacity - Btuh
1
Net Cooling Capacity - Btuh
AHRI Rated Air Flow - cfm
Total Unit Power - kW
1
EER (Btuh/Watt)
2
IEER (Btuh/Watt)
Refrigerant Type
Refrigerant
Circuit 1
Charge
Circuit 2
Circuit 3
Circuit 4
Gas Heating Options Available
Compressor Type (number)
Scroll (4)
Outdoor
Net face area (total) - sq. ft.
68.3
Coils
Number of rows
1
23
Fins per inch
Outdoor Coil
Motor - (No.) horsepower
(6) 1/3
Fans
Motor rpm
1075
Total Motor watts
2500
Diameter - (No.) in.
(6) 24
Number of blades
3
Total Air volume - cfm
21,500
Indoor Coils
Net face area (total) - sq. ft.
31.40
Tube diameter - in.
3/8
Number of rows
4
Fins per inch
14
Drain connection - No. and size
(1) 1 in. NPT
Expansion device type
3
Indoor
Nominal motor output 5 hp, 7.5 hp, 10
Blower
hp
and
Maximum usable motor output
5.75 hp,
5.75 hp, 8.63 hp, 11.5 hp
5.75 hp, 8.63 hp, 11.5 hp
Kit
(US Only) 8.63 hp, 11.5 hp
Selection
5 hp
5 hp
Motor - Kit kit number
5 hp
Kit 5 660-810 rpm
Kit 5 660-810 rpm
Kit 5 660-810 rpm
Kit 6 770-965 rpm
Kit 6 770-965 rpm
Kit 6 770-965 rpm
Kit 7 570-720 rpm
Kit 7 570-720 rpm
Kit 7 570-720 rpm
Kit 8 480-630 rpm
Kit 8 480-630 rpm
Kit 8 480-630 rpm
Kit 9 410-535 rpm
Kit 9 410-535 rpm
Kit 9 410-535 rpm
7.5 hp
7.5 hp
7.5 hp
Kit 3 715-880 rpm
Kit 3 715-880 rpm
Kit 3 715-880 rpm
Kit 4 770-965 rpm
Kit 4 770-965 rpm
Kit 4 770-965 rpm
10 hp
10 hp
10 hp
Kit 1 740-895 rpm
Kit 1 740-895 rpm
Kit 1 740-895 rpm
Kit 2 870-1045 rpm
Kit 2 870-1045 rpm
Kit 2 870-1045
rpm
Blower wheel nom. D x W - in.
(2) 18 x 15
(2) 18 x 15
(2) 18 x 15
Filters
Type of filter
Fiberglass, disposable
Number and size - in.
(12) 20 x 20 x 2
Electrical characteristics
208/230V, 460V or 575V - 60 hertz - 3 phase
Cooling
Performance
NOTE - Net capacity includes evaporator blower motor heat deduction. Gross capacity does not include evaporator blower motor heat deduction.
1
AHRI Certified to AHRI Standard 340/360; 95°F outdoor air temperature and 80°F db/67°F wb entering evaporator air; minimum external duct static pressure.
2
Integrated Energy Efficiency Ratio tested at according to AHRI Standard 340/360.
3
Using total air volume and system static pressure requirements determine from blower performance tables rpm and motor output required. Maximum usable output of
motors furnished are shown. In Canada, nominal motor output is also maximum usable motor output. If motors of comparable output are used, be sure to keep within
the service factor limitations outlined on the motor nameplate.
E-Series Packaged Gas / Electric 20 to 30 Ton / Page 15
SPECIFICATIONS - GAS HEAT
LGH242
LGH300
LGH360
Model Number
Usage Data
Heat Input Type
Standard (S)
Medium (M)
High (H)
2
2
2
First Stage
169,000
234,000
312,000
Second Stage
260,000
360,000
480,000
---
---
---
Second Stage
208,000
288,000
384,000
Temperature Rise Range - °F
10 - 40
15 - 45
20 - 50
Thermal Efficiency
80.0%
80.0%
80.0%
1 in. NPT
1 in. NPT
1 in. NPT
Natural
7
7
7
LPG/Propane
11
11
11
Number of Gas Heat Stages
Gas Heating Input - Btuh
Performance
Output - Btuh
First Stage
Gas Supply Connections
Recommended Gas Supply
Pressure - in. w.g.
HIGH ALTITUDE DERATE
Units may be installed at altitudes up to 2000 feet above sea level without any modification. At altitudes above 2000
feet, units must be derated to match gas manifold pressures shown in table below.
At altitudes above 4500 feet unit must be derated 2% for each 1000 feet above sea level.
NOTE - This is the only permissible derate for these units.
Gas Heat
Type
Altitude - ft.
Standard (S)
Gas Manifold Pressure - in. w.g.
Input Rate
Natural Gas or LPG/Propane - Btuh
Natural Gas
LPG/Propane Gas
First Stage
Second Stage
2001 - 4500
3.4
9.6
169,000
249,000
Medium (M)
2001 - 4500
3.4
9.6
234,000
345,000
High (H)
2001 - 4500
3.4
9.6
312,000
460,000
E-Series Packaged Gas / Electric 20 to 30 Ton / Page 16
RATINGS
NOTE − For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.
20 TON HIGH EFFICIENCY LGH242H4V (1 COMRESSOR OPERATING) - VARIABLE AIR VOLUME
Outdoor Air Temperature Entering Outdoor Coil
Entering
65°F
75°F
85°F
95°F
Total
Wet
Air
Total Comp. Sensible To Total Total Comp. Sensible To Total Total Comp. Sensible To Total Total Comp. Sensible To Total
Bulb
Volume Cool Motor
Ratio (S/T)
Ratio (S/T)
Ratio (S/T)
Ratio (S/T)
Cool Motor
Cool Motor
Cool Motor
TemperCap. Input
Cap. Input
Cap. Input
Cap. Input
Dry Bulb
Dry Bulb
Dry Bulb
Dry Bulb
ature
cfm
kBtuh
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F
1600
47.7
2.44
.63
.71
.79
46.4
2.83
.64
.71
.79
45.0
3.25
.63
.71
.80
43.5
3.72
.63
.72
.81
63°F
2000
51.4
2.44
.63
.73
.82
50.3
2.83
.64
.74
.83
49.0
3.26
.64
.74
.84
47.2
3.73
.65
.75
.85
2400
54.8
2.44
.65
.76
.86
53.6
2.84
.66
.77
.87
52.1
3.27
.66
.77
.88
50.1
3.75
.67
.79
.90
1600
49.3
2.44
.52
.59
.67
48.3
2.83
.52
.59
.67
47.0
3.25
.52
.60
.68
45.5
3.73
.52
.61
.69
67°F
2000
53.8
2.44
.53
.61
.70
52.7
2.83
.53
.61
.70
51.2
3.27
.53
.62
.71
49.4
3.74
.53
.63
.72
2400
57.3
2.44
.54
.63
.72
56.1
2.84
.54
.63
.73
54.5
3.28
.54
.64
.74
52.5
3.75
.55
.64
.75
1600
51.3
2.44
.42
.50
.57
50.2
2.83
.42
.50
.57
48.9
3.26
.42
.50
.58
47.3
3.74
.42
.50
.58
71°F
2000
56.0
2.44
.42
.51
.58
54.8
2.84
.42
.51
.59
53.3
3.27
.42
.51
.60
51.4
3.75
.42
.52
.60
2400
59.7
2.43
.42
.52
.60
58.4
2.84
.42
.52
.61
56.7
3.28
.42
.52
.61
54.6
3.75
.42
.53
.62
20 TON HIGH EFFICIENCY LGH242H4V (2 COMRESSORS OPERATING) - VARIABLE AIR VOLUME
Entering
Total
Wet
Air
Bulb
Volume
Temperature
cfm
3200
63°F
4000
4800
3200
67°F
4000
4800
3200
71°F
4000
4800
Total
Cool
Cap.
kBtuh
104.1
111.4
117.5
110.3
118.4
124.7
116.5
125.2
131.9
Outdoor Air Temperature Entering Outdoor Coil
65°F
75°F
85°F
95°F
Comp. Sensible To Total Total Comp. Sensible To Total Total Comp. Sensible To Total Total Comp. Sensible To Total
Ratio (S/T)
Ratio (S/T)
Ratio (S/T)
Ratio (S/T)
Motor
Cool Motor
Cool Motor
Cool Motor
Input
Cap. Input
Cap. Input
Cap. Input
Dry Bulb
Dry Bulb
Dry Bulb
Dry Bulb
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F
4.89
.63
.71
.78 101.4 5.67
.63
.71
.78
98.3
6.52
.63
.72
.79
94.6
7.46
.63
.72
.80
4.89
.64
.72
.81 108.5 5.68
.64
.73
.82 105.2 6.54
.63
.74
.83 101.0 7.48
.65
.75
.84
4.89
.65
.76
.85 114.3
5.69
.65
.76
.85
110.4
6.55
.66
.77
.87 106.3 7.50
.67
.79
.88
4.89
.52
.59
.67 107.2 5.68
.52
.59
.67 104.2 6.54
.52
.59
.68 100.4 7.48
.52
.60
.68
4.89
.52
.60
.69 115.2
5.69
.52
.61
.70
111.6
6.56
.53
.62
.70 107.3 7.50
.53
.62
.72
4.89
.53
.63
.72 121.2 5.69
.53
.63
.73
117.1
6.57
.54
.64
.74 112.6
7.52
.55
.64
.75
4.89
.42
.50
.56 113.5
5.69
.42
.50
.57
110.3
6.56
.42
.50
.57 106.3 7.50
.42
.50
.57
4.89
.42
.50
.58 121.9 5.69
.42
.50
.58
118.1
6.57
.41
.51
.59 113.7
7.53
.42
.51
.60
4.88
.42
.51
.60 128.4 5.70
.42
.51
.61 124.1 6.58
.42
.52
.61 119.2
7.54
.42
.52
.62
20 TON HIGH EFFICIENCY LGH242H4V (3 COMRESSORS OPERATING) - VARIABLE AIR VOLUME
Entering
Total
Wet
Air
Bulb
Volume
Temperature
cfm
4800
63°F
6000
7200
4800
67°F
6000
7200
4800
71°F
6000
7200
Total
Cool
Cap.
kBtuh
185.8
195.8
204.9
196.3
206.1
213.1
206.6
216.6
221.5
Outdoor Air Temperature Entering Outdoor Coil
65°F
75°F
85°F
95°F
Comp. Sensible To Total Total Comp. Sensible To Total Total Comp. Sensible To Total Total Comp. Sensible To Total
Ratio (S/T)
Ratio (S/T)
Ratio (S/T)
Ratio (S/T)
Motor
Cool Motor
Cool Motor
Cool Motor
Input
Cap. Input
Cap. Input
Cap. Input
Dry Bulb
Dry Bulb
Dry Bulb
Dry Bulb
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F
7.35
.69
.82
.90 180.3 8.57
.70
.83
.90 173.8 9.86
.71
.84
.91 166.8 11.27
.72
.86
.92
7.35
.73
.87
.93 190.3 8.57
.74
.87
.94 183.9 9.88
.76
.88
.95 176.8 11.31
.77
.89
.96
7.34
.77
.89
.96 199.1 8.58
.78
.90
.97 192.3 9.90
.80
.91
.98 184.5 11.33
.82
.92
.99
7.35
.56
.67
.78 190.6 8.57
.56
.67
.79 183.6 9.88
.56
.68
.81 176.1 11.30
.57
.69
.82
7.34
.58
.71
.84 199.7 8.58
.59
.72
.85 192.5 9.90
.59
.73
.86 183.9 11.32
.59
.74
.87
7.34
.60
.75
.87 206.5 8.58
.61
.76
.88 198.8 9.91
.62
.77
.89 190.0 11.34
.63
.79
.90
7.34
.43
.54
.65 200.6 8.58
.43
.54
.65 193.6 9.90
.43
.55
.66 185.6 11.33
.43
.56
.67
7.34
.44
.55
.66 210.6 8.58
.44
.57
.70 202.9 9.91
.44
.57
.70 194.2 11.35
.45
.59
.72
7.34
.45
.56
.68 217.8 8.58
.45
.60
.73 209.5 9.92
.45
.61
.75 200.3 11.37
.46
.62
.77
20 TON HIGH EFFICIENCY LGH242H4V (All COMRESSORS OPERATING) - VARIABLE AIR VOLUME
Entering
Total
Wet
Air
Bulb
Volume
Temperature
cfm
6400
63°F
8000
9600
6400
67°F
8000
9600
6400
71°F
8000
9600
Total
Cool
Cap.
kBtuh
242.1
255.3
265.0
252.7
263.7
272.2
267.2
278.7
286.6
Outdoor Air Temperature Entering Outdoor Coil
85°F
95°F
105°F
115°F
Comp. Sensible To Total Total Comp. Sensible To Total Total Comp. Sensible To Total Total Comp. Sensible To Total
Ratio (S/T)
Ratio (S/T)
Ratio (S/T)
Ratio (S/T)
Motor
Cool Motor
Cool Motor
Cool Motor
Input
Cap. Input
Cap. Input
Cap. Input
Dry Bulb
Dry Bulb
Dry Bulb
Dry Bulb
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F
13.17 .71
.83
.94 232.8 15.08
.72
.84
.96 222.2 17.18 .74
.86
.98 210.4 19.57
.75
.88
1.00
13.19 .75
.89 1.00 244.9 15.10
.77
.91
1.00 233.4 17.21 .79
.93 1.00 220.8 19.61
.81
.96
1.00
13.21 .80
.95 1.00 254.0 15.13
.82
.97
1.00 242.0 17.25 .84
.99 1.00 229.0 19.65
.86
1.00 1.00
13.19 .55
.68
.80 241.9 15.09
.57
.70
.81 230.5 17.20 .57
.71
.83 217.4 19.59
.58
.72
.85
13.21 .58
.72
.86 252.3 15.13
.59
.74
.88 239.9 17.24 .61
.77
.90 226.6 19.63
.61
.78
.93
13.22 .61
.78
.92 260.5 15.15
.62
.79
.94 247.9 17.27 .64
.81
.97 234.3 19.68
.66
.84
.99
13.21 .43
.55
.66 256.0 15.13
.43
.55
.67 243.5 17.26 .43
.56
.68 230.0 19.65
.43
.57
.70
13.23 .43
.57
.70 266.5 15.17
.43
.58
.72 253.2 17.29 .44
.60
.74 238.3 19.70
.44
.61
.76
13.24 .43
.60
.76 273.6 15.18
.44
.62
.78 259.6 17.32 .45
.63
.80 244.0 19.72
.46
.64
.82
E-Series Packaged Gas / Electric 20 to 30 Ton / Page 17
RATINGS
NOTE - For Temperatures and Capacities not shown in tables, see bulletin - Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.
25 TON HIGH EFFICIENCY LGH300H4B (1ST STAGE) - CONSTANT AIR VOLUME
Outdoor Air Temperature Entering Outdoor Coil
Entering
65°F
75°F
85°F
95°F
Total
Wet
Air
Total Comp. Sensible To Total Total Comp. Sensible To Total Total Comp. Sensible To Total Total Comp. Sensible To Total
Bulb
Volume Cool Motor
Ratio (S/T)
Ratio (S/T)
Ratio (S/T)
Ratio (S/T)
Cool Motor
Cool Motor
Cool Motor
TemperCap. Input
Cap. Input
Cap. Input
Cap. Input
Dry Bulb
Dry Bulb
Dry Bulb
Dry Bulb
ature
cfm
kBtuh
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F
8000
157.5 7.35
.71
.83
.95 152.9 8.21
.72
.84
.96 147.7 9.16
.73
.86
.97 142.1 10.27
.74
.87
.99
63°F
10,000 166.1 7.48
.76
.89 1.00 160.7 8.33
.77
.91
1.00 155.1 9.29
.78
.92 1.00 149.2 10.38
.79
.94
1.00
12,000 172.3 7.58
.80
.95 1.00 166.6 8.42
.81
.96
1.00 161.0 9.38
.82
.98 1.00 154.8 10.47
.84
.99
1.00
8000
167.0 7.50
.57
.69
.80 162.0 8.35
.57
.70
.81 156.5 9.30
.58
.70
.82 150.5 10.39
.59
.72
.84
67°F
10,000 175.4 7.63
.60
.73
.86 169.5 8.47
.60
.75
.88 163.5 9.42
.61
.75
.89 157.4 10.51
.62
.77
.91
12,000 181.0 7.73
.62
.78
.92 175.3 8.57
.63
.79
.94 168.9 9.51
.64
.80
.95 162.2 10.59
.65
.82
.97
8000
177.4 7.67
.44
.56
.67 171.9 8.51
.44
.56
.67 166.0 9.46
.44
.56
.68 159.9 10.55
.45
.57
.69
71°F
10,000 185.7 7.80
.45
.58
.71 179.9 8.64
.45
.59
.72 173.6 9.59
.46
.59
.74 166.8 10.67
.46
.60
.75
12,000 191.7 7.91
.46
.61
.76 185.6 8.74
.46
.62
.77 179.3 9.69
.47
.63
.78 171.7 10.77
.47
.64
.80
25 TON HIGH EFFICIENCY LGH300H4B (2ND STAGE) - CONSTANT AIR VOLUME
Entering
Total
Wet
Air
Bulb
Volume
Temperature
cfm
8000
63°F
10,000
12,000
8000
67°F
10,000
12,000
8000
71°F
10,000
12,000
Total
Cool
Cap.
kBtuh
297.0
311.1
322.4
314.5
328.8
339.5
332.9
348.0
359.1
Outdoor Air Temperature Entering Outdoor Coil
85°F
95°F
105°F
115°F
Comp. Sensible To Total Total Comp. Sensible To Total Total Comp. Sensible To Total Total Comp. Sensible To Total
Ratio (S/T)
Ratio (S/T)
Ratio (S/T)
Ratio (S/T)
Motor
Cool Motor
Cool Motor
Cool Motor
Input
Cap. Input
Cap. Input
Cap. Input
Dry Bulb
Dry Bulb
Dry Bulb
Dry Bulb
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F
18.34 .73
.86
.98 286.0 20.54
.74
.88
.99 273.7 23.12 .76
.90 1.00 258.8 26.15
.78
.92
1.00
18.57 .79
.93 1.00 299.8 20.78
.80
.95
1.00 286.9 23.34 .82
.97 1.00 271.4 26.33
.84
.99
1.00
18.75 .83
.99 1.00 310.6 20.94
.85
1.00 1.00 298.6 23.53 .87 1.00 1.00 284.7 26.56
.89
1.00 1.00
18.62 .58
.71
.83 303.4 20.82
.59
.72
.84 290.4 23.40 .60
.73
.86 274.7 26.40
.61
.75
.89
18.86 .61
.76
.90 316.7 21.05
.62
.78
.92 303.1 23.61 .63
.79
.94 286.3 26.57
.64
.81
.97
19.04 .65
.81
.96 326.4 21.22
.65
.83
.98 312.3 23.78 .66
.84 1.00 295.1 26.73
.68
.87
1.00
18.93 .44
.57
.68 321.2 21.12
.45
.57
.70 308.2 23.70 .45
.58
.71 291.7 26.66
.45
.59
.73
19.19 .46
.60
.74 335.4 21.38
.46
.61
.75 321.5 23.94 .46
.62
.77 304.1 26.89
.47
.63
.79
19.39 .47
.64
.79 345.3 21.55
.47
.64
.80 330.3 24.10 .48
.66
.82 312.3 27.06
.48
.67
.85
E-Series Packaged Gas / Electric 20 to 30 Ton / Page 18
RATINGS
NOTE − For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.
25 TON HIGH EFFICIENCY LGH300H4V (1 COMRESSOR OPERATING) - VARIABLE AIR VOLUME
Outdoor Air Temperature Entering Outdoor Coil
Entering
65°F
75°F
85°F
95°F
Total
Wet
Air
Total Comp. Sensible To Total Total Comp. Sensible To Total Total Comp. Sensible To Total Total Comp. Sensible To Total
Bulb
Volume Cool Motor
Ratio (S/T)
Ratio (S/T)
Ratio (S/T)
Ratio (S/T)
Cool Motor
Cool Motor
Cool Motor
TemperCap. Input
Cap. Input
Cap. Input
Cap. Input
Dry Bulb
Dry Bulb
Dry Bulb
Dry Bulb
ature
cfm
kBtuh
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F
2000
62.5
3.65
.63
.71
.78
60.6
4.07
.63
.71
.79
58.3
4.57
.64
.71
.80
55.9
5.13
.63
.72
.81
63°F
2500
67.8
3.68
.63
.72
.81
65.7
4.10
.63
.73
.82
63.5
4.59
.64
.74
.83
60.9
5.15
.65
.75
.84
3000
72.4
3.73
.64
.74
.84
70.1
4.15
.65
.75
.85
67.6
4.63
.66
.76
.87
64.9
5.19
.67
.78
.88
2000
65.5
3.67
.53
.60
.67
62.9
4.09
.53
.60
.67
60.8
4.58
.52
.60
.68
58.6
5.15
.52
.61
.68
67°F
2500
71.0
3.72
.52
.60
.69
68.8
4.14
.53
.61
.69
66.5
4.62
.53
.62
.70
63.9
5.18
.53
.62
.71
3000
75.9
3.76
.53
.62
.71
73.5
4.17
.53
.62
.72
71.0
4.64
.54
.63
.73
68.1
5.20
.54
.64
.74
2000
67.4
3.68
.42
.50
.56
65.4
4.11
.42
.50
.57
63.4
4.59
.42
.50
.58
61.0
5.16
.42
.50
.58
71°F
2500
73.8
3.73
.42
.51
.58
71.6
4.15
.42
.51
.59
69.2
4.63
.42
.51
.59
66.6
5.19
.42
.51
.60
3000
79.1
3.79
.42
.51
.59
76.7
4.20
.42
.52
.60
73.9
4.67
.42
.52
.61
71.0
5.23
.43
.53
.62
25 TON HIGH EFFICIENCY LGH300H4V (2 COMRESSORS OPERATING) - VARIABLE AIR VOLUME
Entering
Total
Wet
Air
Bulb
Volume
Temperature
cfm
4000
63°F
5000
6000
4000
67°F
5000
6000
4000
71°F
5000
6000
Total
Cool
Cap.
kBtuh
136.4
147.1
154.8
144.9
155.8
164.5
153.0
165.0
174.2
Outdoor Air Temperature Entering Outdoor Coil
65°F
75°F
85°F
95°F
Comp. Sensible To Total Total Comp. Sensible To Total Total Comp. Sensible To Total Total Comp. Sensible To Total
Ratio (S/T)
Ratio (S/T)
Ratio (S/T)
Ratio (S/T)
Motor
Cool Motor
Cool Motor
Cool Motor
Input
Cap. Input
Cap. Input
Cap. Input
Dry Bulb
Dry Bulb
Dry Bulb
Dry Bulb
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F
7.46
.60
.68
.75 132.1 8.29
.62
.71
.78 127.4 9.23
.63
.71
.79 122.1 10.31
.63
.71
.80
7.52
.64
.72
.80 141.9 8.37
.63
.72
.81 136.6 9.31
.64
.74
.83 130.8 10.40
.64
.74
.84
7.59
.64
.74
.84 149.7 8.44
.65
.75
.85
144.0 9.38
.66
.77
.86 137.7 10.44
.67
.77
.87
7.51
.53
.60
.67 140.4 8.35
.52
.60
.67 135.2 9.31
.52
.60
.68 129.7 10.37
.52
.60
.68
7.61
.52
.60
.68 150.9 8.44
.53
.61
.69 145.3 9.39
.52
.61
.70 139.2 10.46
.52
.62
.70
7.70
.53
.62
.71 159.1 8.53
.53
.62
.72 153.0 9.46
.53
.63
.73 146.3 10.53
.54
.64
.74
7.58
.43
.50
.56 148.3 8.42
.42
.49
.57 143.2 9.37
.42
.49
.57 137.7 10.45
.42
.50
.57
7.71
.42
.50
.58 159.7 8.52
.42
.50
.58 154.2 9.47
.42
.50
.59 147.8 10.55
.42
.50
.59
7.79
.42
.51
.59 168.5 8.62
.42
.51
.60 161.9 9.56
.42
.52
.60 155.1 10.63
.42
.52
.61
25 TON HIGH EFFICIENCY LGH300H4V (3 COMRESSORS OPERATING) - VARIABLE AIR VOLUME
Entering
Total
Wet
Air
Bulb
Volume
Temperature
cfm
6000
63°F
7500
9000
6000
67°F
7500
9000
6000
71°F
7500
9000
Total
Cool
Cap.
kBtuh
244.0
257.4
268.0
258.2
271.7
281.6
271.7
285.8
296.5
Outdoor Air Temperature Entering Outdoor Coil
65°F
75°F
85°F
95°F
Comp. Sensible To Total Total Comp. Sensible To Total Total Comp. Sensible To Total Total Comp. Sensible To Total
Ratio (S/T)
Ratio (S/T)
Ratio (S/T)
Ratio (S/T)
Motor
Cool Motor
Cool Motor
Cool Motor
Input
Cap. Input
Cap. Input
Cap. Input
Dry Bulb
Dry Bulb
Dry Bulb
Dry Bulb
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F
11.46 .68
.80
.89 235.6 12.72
.69
.81
.90 226.3 14.12 .70
.83
.91 216.2 15.72
.71
.84
.92
11.61 .71
.85
.92 248.3 12.85
.72
.87
.93 238.2 14.24 .74
.88
.94 228.3 15.86
.75
.88
.95
11.73 .75
.88
.95 259.1 12.98
.76
.89
.96 249.3 14.38 .78
.90
.97 238.7 16.00
.80
.91
.98
11.63 .55
.66
.76 249.3 12.87
.56
.67
.78 239.4 14.27 .56
.68
.79 228.9 15.87
.57
.69
.81
11.78 .57
.69
.82 261.9 13.01
.57
.70
.84 251.3 14.41 .58
.71
.85 239.7 16.00
.59
.73
.86
11.89 .59
.73
.86 271.1 13.12
.60
.74
.87 259.6 14.52 .60
.76
.88 247.2 16.11
.62
.78
.89
11.78 .43
.54
.63 262.5 13.03
.43
.54
.64 252.1 14.43 .43
.55
.65 241.3 16.03
.43
.55
.66
11.95 .44
.56
.67 275.7 13.19
.44
.56
.68 264.9 14.59 .44
.57
.69 252.7 16.18
.44
.58
.71
12.08 .44
.58
.71 285.5 13.32
.44
.59
.72 273.8 14.71 .45
.60
.73 261.0 16.30
.45
.60
.75
25 TON HIGH EFFICIENCY LGH300H4V (All COMRESSORS OPERATING) - VARIABLE AIR VOLUME
Entering
Total
Wet
Air
Bulb
Volume
Temperature
cfm
8000
63°F
10,000
12,000
8000
67°F
10,000
12,000
8000
71°F
10,000
12,000
Total
Cool
Cap.
kBtuh
313.6
331.2
343.8
329.7
343.7
353.8
348.3
362.9
374.1
Outdoor Air Temperature Entering Outdoor Coil
85°F
95°F
105°F
115°F
Comp. Sensible To Total Total Comp. Sensible To Total Total Comp. Sensible To Total Total Comp. Sensible To Total
Ratio (S/T)
Ratio (S/T)
Ratio (S/T)
Ratio (S/T)
Motor
Cool Motor
Cool Motor
Cool Motor
Input
Cap. Input
Cap. Input
Cap. Input
Dry Bulb
Dry Bulb
Dry Bulb
Dry Bulb
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F
18.86 .70
.82
.92 300.2 21.00
.72
.84
.94 286.1 23.49 .73
.85
.97 271.0 26.45
.74
.87
.99
19.10 .75
.88
.99 316.5 21.24
.76
.89
1.00 300.8 23.69 .78
.92 1.00 284.4 26.62
.80
.94
1.00
19.26 .79
.93 1.00 327.9 21.39
.81
.95
1.00 311.9 23.86 .83
.98 1.00 294.8 26.79
.85
1.00 1.00
19.08 .56
.68
.79 314.1 21.18
.56
.69
.81 297.8 23.65 .57
.70
.82 280.9 26.56
.58
.72
.84
19.27 .58
.72
.85 327.1 21.38
.59
.74
.86 310.3 23.83 .60
.75
.89 292.8 26.74
.61
.77
.91
19.41 .60
.77
.90 337.3 21.53
.62
.78
.92 320.3 24.00 .62
.80
.95 302.4 26.91
.64
.82
.97
19.33 .42
.54
.66 332.0 21.45
.43
.55
.66 315.2 23.91 .43
.56
.68 298.3 26.83
.43
.56
.70
19.55 .43
.57
.70 345.7 21.65
.44
.58
.72 328.1 24.11 .43
.58
.74 309.1 27.00
.43
.60
.75
19.72 .43
.59
.75 356.2 21.83
.44
.60
.76 336.6 24.26 .44
.62
.78 317.0 27.15
.45
.63
.81
E-Series Packaged Gas / Electric 20 to 30 Ton / Page 19
RATINGS
NOTE − For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.
30 TON HIGH EFFICIENCY LGH360H4B (1ST STAGE) - CONSTANT AIR VOLUME
Outdoor Air Temperature Entering Outdoor Coil
Entering
65°F
75°F
85°F
95°F
Total
Wet
Air
Total Comp. Sensible To Total Total Comp. Sensible To Total Total Comp. Sensible To Total Total Comp. Sensible To Total
Bulb
Volume Cool Motor
Ratio (S/T)
Ratio (S/T)
Ratio (S/T)
Ratio (S/T)
Cool Motor
Cool Motor
Cool Motor
TemperCap. Input
Cap. Input
Cap. Input
Cap. Input
Dry Bulb
Dry Bulb
Dry Bulb
Dry Bulb
ature
cfm
kBtuh
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F
9440
188.9 9.57
.70
.82
.94 183.2 10.61
.71
.83
.95 177.5 11.79 .72
.84
.97 171.1 13.16
.73
.86
.98
63°F
11,800 198.4 9.73
.74
.88 1.00 192.0 10.76
.75
.90
1.00 185.9 11.95 .77
.91 1.00 179.1 13.31
.78
.93
1.00
14,160 205.4 9.86
.79
.94 1.00 198.6 10.89
.80
.96
1.00 192.2 12.07 .81
.98 1.00 185.4 13.44
.82
.99
1.00
9440
200.0 9.76
.56
.68
.79 193.9 10.80
.56
.69
.80 187.6 11.98 .57
.69
.82 181.0 13.35
.58
.70
.83
67°F
11,800 208.7 9.92
.58
.72
.85 201.9 10.95
.59
.73
.87 195.3 12.13 .60
.74
.88 188.1 13.50
.60
.75
.90
14,160 214.9 10.04 .61
.77
.91 207.8 11.07
.62
.78
.93 201.0 12.24 .63
.79
.95 193.7 13.61
.64
.81
.97
9440
211.2
9.97
.43
.55
.66 204.6 11.00
.43
.55
.66 198.0 12.19 .44
.55
.67 190.9 13.55
.44
.56
.68
71°F
11,800 220.0 10.14 .44
.57
.70 212.9 11.17
.45
.58
.71 206.2 12.35 .45
.59
.72 198.7 13.72
.45
.59
.74
14,160 226.9 10.27 .45
.60
.74 219.3 11.30
.45
.61
.76 212.1 12.47 .46
.62
.77 204.8 13.83
.46
.63
.79
30 TON HIGH EFFICIENCY LGH360H4B (2ND STAGE) - CONSTANT AIR VOLUME
Entering
Total
Wet
Air
Bulb
Volume
Temperature
cfm
9440
63°F
11,800
14,160
9440
67°F
11,800
14,160
9440
71°F
11,800
14,160
Total
Cool
Cap.
kBtuh
357.8
374.0
386.3
377.9
394.0
405.1
397.8
414.7
426.1
Outdoor Air Temperature Entering Outdoor Coil
85°F
95°F
105°F
115°F
Comp. Sensible To Total Total Comp. Sensible To Total Total Comp. Sensible To Total Total Comp. Sensible To Total
Ratio (S/T)
Ratio (S/T)
Ratio (S/T)
Ratio (S/T)
Motor
Cool Motor
Cool Motor
Cool Motor
Input
Cap. Input
Cap. Input
Cap. Input
Dry Bulb
Dry Bulb
Dry Bulb
Dry Bulb
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F
23.62 .72
.85
.98 344.2 26.32
.73
.86
.99 329.7 29.45 .74
.88 1.00 312.8 33.05
.76
.91
1.00
23.92 .77
.92 1.00 359.3 26.61
.78
.94
1.00 344.3 29.76 .80
.96 1.00 326.5 33.33
.82
.99
1.00
24.16 .82
.98 1.00 371.9 26.86
.83
.99
1.00 356.7 30.00 .85 1.00 1.00 339.4 33.62
.88
1.00 1.00
24.00 .57
.70
.82 363.8 26.69
.58
.70
.83 348.6 29.83 .58
.72
.85 330.1 33.41
.59
.74
.88
24.30 .60
.75
.89 378.6 27.01
.61
.76
.91 362.1 30.12 .62
.78
.93 342.8 33.70
.63
.80
.96
24.53 .63
.80
.96 389.4 27.22
.64
.81
.98 372.2 30.34 .65
.83
.99 351.5 33.90
.66
.86
1.00
24.40 .44
.56
.67 383.1 27.09
.44
.56
.68 367.4 30.23 .44
.57
.69 348.2 33.82
.44
.58
.71
24.72 .45
.59
.73 398.8 27.42
.45
.60
.74 381.6 30.55 .45
.61
.76 361.3 34.12
.46
.62
.78
24.95 .46
.62
.78 410.7 27.65
.46
.63
.79 391.6 30.75 .47
.64
.81 370.0 34.32
.47
.66
.84
E-Series Packaged Gas / Electric 20 to 30 Ton / Page 20
RATINGS
NOTE − For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.
30 TON HIGH EFFICIENCY LGH360H4V (1 COMRESSOR OPERATING) - VARIABLE AIR VOLUME
Outdoor Air Temperature Entering Outdoor Coil
Entering
65°F
75°F
85°F
95°F
Total
Wet
Air
Total Comp. Sensible To Total Total Comp. Sensible To Total Total Comp. Sensible To Total Total Comp. Sensible To Total
Bulb
Volume Cool Motor
Ratio (S/T)
Ratio (S/T)
Ratio (S/T)
Ratio (S/T)
Cool Motor
Cool Motor
Cool Motor
TemperCap. Input
Cap. Input
Cap. Input
Cap. Input
Dry Bulb
Dry Bulb
Dry Bulb
Dry Bulb
ature
cfm
kBtuh
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F
2360
73.4
4.44
.64
.72
.79
71.1
4.96
.64
.72
.80
68.6
5.54
.65
.73
.80
65.8
6.19
.64
.73
.82
63°F
2950
78.9
4.53
.65
.73
.82
76.5
5.05
.65
.74
.83
73.9
5.63
.66
.75
.84
71.0
6.29
.66
.76
.86
3540
83.8
4.60
.66
.76
.85
81.1
5.13
.67
.77
.87
78.2
5.70
.67
.78
.88
75.1
6.36
.68
.79
.90
2360
76.2
4.49
.54
.61
.68
73.7
5.00
.53
.61
.68
71.3
5.59
.53
.61
.69
68.7
6.25
.53
.62
.70
67°F
2950
82.4
4.58
.54
.62
.70
79.9
5.10
.54
.62
.71
77.2
5.68
.54
.63
.72
74.3
6.35
.54
.64
.73
3540
87.5
4.66
.54
.64
.73
84.8
5.19
.55
.64
.73
81.9
5.77
.55
.65
.75
78.5
6.43
.55
.66
.76
2360
78.8
4.53
.43
.51
.58
76.6
5.05
.43
.51
.58
74.2
5.64
.43
.51
.59
71.4
6.29
.42
.51
.59
71°F
2950
85.6
4.63
.43
.51
.59
83.1
5.16
.43
.52
.60
80.3
5.74
.43
.52
.61
77.1
6.40
.43
.52
.61
3540
90.9
4.72
.43
.53
.61
88.2
5.25
.43
.53
.62
85.1
5.83
.43
.53
.62
81.7
6.49
.43
.54
.63
30 TON HIGH EFFICIENCY LGH360H4V (2 COMRESSORS OPERATING) - VARIABLE AIR VOLUME
Entering
Total
Wet
Air
Bulb
Volume
Temperature
cfm
4720
63°F
5900
7080
4720
67°F
5900
7080
4720
71°F
5900
7080
Total
Cool
Cap.
kBtuh
186.4
196.1
203.0
194.7
205.3
212.6
202.3
213.3
221.4
Outdoor Air Temperature Entering Outdoor Coil
65°F
75°F
85°F
95°F
Comp. Sensible To Total Total Comp. Sensible To Total Total Comp. Sensible To Total Total Comp. Sensible To Total
Ratio (S/T)
Ratio (S/T)
Ratio (S/T)
Ratio (S/T)
Motor
Cool Motor
Cool Motor
Cool Motor
Input
Cap. Input
Cap. Input
Cap. Input
Dry Bulb
Dry Bulb
Dry Bulb
Dry Bulb
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F
9.54
.69
.81
.92 180.5 10.59
.70
.82
.93 173.7 11.74 .71
.83
.95 165.8 13.04
.72
.85
.97
9.70
.72
.86
.98 189.6 10.74
.73
.87
1.00 182.0 11.90 .75
.89 1.00 173.6 13.19
.76
.91
1.00
9.82
.76
.91 1.00 196.3 10.86
.77
.93
1.00 188.4 12.02 .79
.95 1.00 179.5 13.31
.80
.97
1.00
9.68
.56
.67
.77 188.7 10.73
.56
.68
.78 181.5 11.89 .57
.69
.80 173.7 13.20
.58
.70
.82
9.86
.58
.70
.83 198.5 10.91
.59
.71
.84 190.5 12.06 .59
.72
.86 181.9 13.36
.60
.74
.88
9.99
.60
.74
.88 205.5 11.03
.61
.75
.90 197.1 12.19 .62
.76
.92 188.1 13.48
.63
.78
.94
9.81
.44
.54
.65 196.1 10.87
.44
.55
.65 188.9 12.03 .44
.55
.66 180.6 13.33
.44
.56
.67
10.01 .44
.57
.68 206.5 11.05
.45
.57
.69 198.4 12.21 .45
.58
.70 189.5 13.51
.45
.59
.72
10.15 .45
.59
.72 214.2 11.20
.46
.60
.73 205.6 12.36 .46
.60
.74 196.2 13.66
.47
.62
.76
30 TON HIGH EFFICIENCY LGH360H4V (3 COMRESSORS OPERATING) - VARIABLE AIR VOLUME
Entering
Total
Wet
Air
Bulb
Volume
Temperature
cfm
7080
63°F
8850
10,620
7080
67°F
8850
10,620
7080
71°F
8850
10,620
Total
Cool
Cap.
kBtuh
284.0
297.7
308.5
298.7
312.7
322.7
313.1
327.5
338.1
Outdoor Air Temperature Entering Outdoor Coil
65°F
75°F
85°F
95°F
Comp. Sensible To Total Total Comp. Sensible To Total Total Comp. Sensible To Total Total Comp. Sensible To Total
Ratio (S/T)
Ratio (S/T)
Ratio (S/T)
Ratio (S/T)
Motor
Cool Motor
Cool Motor
Cool Motor
Input
Cap. Input
Cap. Input
Cap. Input
Dry Bulb
Dry Bulb
Dry Bulb
Dry Bulb
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F
14.37 .70
.81
.90 276.6 15.96
.70
.82
.91 266.5 17.72 .71
.83
.91 254.1 19.67
.72
.85
.92
14.60 .73
.86
.93 289.8 16.19
.74
.87
.94 278.4 17.94 .75
.88
.95 266.3 19.90
.76
.89
.96
14.79 .76
.90
.96 300.6 16.39
.78
.90
.97 289.6 18.15 .79
.91
.98 277.1 20.12
.81
.92
.99
14.62 .56
.67
.78 291.1 16.22
.56
.67
.79 280.2 17.97 .57
.68
.80 267.6 19.93
.57
.70
.82
14.87 .58
.71
.83 304.4 16.46
.59
.71
.85 292.6 18.21 .59
.73
.86 279.0 20.16
.60
.74
.87
15.04 .60
.74
.88 313.8 16.63
.61
.76
.89 301.3 18.37 .62
.77
.89 286.6 20.31
.63
.79
.90
14.87 .44
.55
.65 305.1 16.47
.44
.55
.66 294.0 18.24 .44
.55
.66 280.9 20.21
.44
.56
.68
15.13 .44
.57
.68 319.0 16.72
.44
.57
.69 306.9 18.49 .45
.58
.71 292.5 20.44
.44
.59
.72
15.34 .44
.59
.70 329.0 16.92
.44
.60
.73 316.1 18.66 .44
.61
.75 301.3 20.61
.45
.62
.77
30 TON HIGH EFFICIENCY LGH360H4V (All COMRESSORS OPERATING) - VARIABLE AIR VOLUME
Entering
Total
Wet
Air
Bulb
Volume
Temperature
cfm
9440
63°F
11,800
14,160
9440
67°F
11,800
14,160
9440
71°F
11,800
14,160
Total
Cool
Cap.
kBtuh
366.3
384.4
397.6
383.7
397.9
409.2
404.0
418.6
428.9
Outdoor Air Temperature Entering Outdoor Coil
85°F
95°F
105°F
115°F
Comp. Sensible To Total Total Comp. Sensible To Total Total Comp. Sensible To Total Total Comp. Sensible To Total
Ratio (S/T)
Ratio (S/T)
Ratio (S/T)
Ratio (S/T)
Motor
Cool Motor
Cool Motor
Cool Motor
Input
Cap. Input
Cap. Input
Cap. Input
Dry Bulb
Dry Bulb
Dry Bulb
Dry Bulb
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F
23.80 .71
.83
.93 350.4 26.42
.72
.84
.95 334.3 29.43 .74
.86
.97 318.4 33.05
.75
.88
.99
24.14 .76
.88
.99 367.3 26.75
.77
.90
1.00 349.4 29.75 .79
.92 1.00 332.3 33.36
.81
.94
1.00
24.39 .80
.94 1.00 379.4 27.00
.82
.96
1.00 360.6 29.98 .84
.98 1.00 343.1 33.60
.86
1.00 1.00
24.13 .56
.68
.80 366.0 26.73
.57
.70
.82 347.3 29.71 .58
.71
.83 329.4 33.30
.59
.73
.85
24.40 .59
.73
.86 379.2 26.99
.59
.75
.88 359.9 29.97 .61
.77
.90 341.4 33.56
.62
.78
.92
24.62 .61
.79
.91 389.2 27.19
.63
.80
.93 369.7 30.18 .64
.82
.95 350.8 33.77
.65
.84
.98
24.52 .42
.55
.66 385.1 27.11
.42
.55
.67 365.8 30.10 .43
.56
.70 347.0 33.68
.43
.57
.70
24.81 .43
.58
.71 398.9 27.39
.44
.58
.73 377.9 30.37 .43
.60
.75 358.4 33.92
.44
.61
.77
25.02 .44
.61
.76 408.3 27.60
.44
.62
.78 386.6 30.55 .46
.64
.81 365.8 34.09
.47
.65
.83
E-Series Packaged Gas / Electric 20 to 30 Ton / Page 21
E-Series Packaged Gas / Electric 20 to 30 Ton / Page 22
680
704
727
750
13,500
14,500
15,000
657
13,000
14,000
613
635
12,000
12,500
572
592
11,000
11,500
553
10,500
2.36
516
534
9500
10,000
2.11
499
9000
1.66
7.23
6.55
5.92
5.35
4.83
4.37
3.95
3.58
3.24
2.93
2.64
1.88
467
483
1.46
8000
453
7500
1.26
1.07
0.89
0.73
0.56
0.41
0.26
BHP
8500
426
439
6500
7000
402
414
5500
392
5000
6000
372
382
4500
RPM
0.20
4000
Air
Volume
cfm
797
777
757
736
715
695
674
653
634
615
596
578
561
544
528
513
499
486
473
462
451
441
433
RPM
8.07
7.34
6.67
6.06
5.50
4.98
4.53
4.12
3.74
3.39
3.06
2.75
2.47
2.22
2.00
1.79
1.60
1.41
1.24
1.08
0.93
0.79
0.65
BHP
0.40
834
818
801
784
766
748
729
711
692
674
657
640
624
608
593
579
565
551
539
527
516
506
497
RPM
8.92
8.16
7.44
6.78
6.18
5.62
5.14
4.70
4.31
3.95
3.60
3.26
2.95
2.65
2.38
2.14
1.93
1.74
1.56
1.40
1.25
1.12
0.99
BHP
0.60
868
854
839
824
808
792
776
760
744
727
711
696
681
667
653
641
628
616
605
594
584
574
565
RPM
9.75
8.97
8.23
7.53
6.89
6.29
5.75
5.27
4.83
4.44
4.07
3.73
3.41
3.10
2.81
2.55
2.31
2.10
1.90
1.72
1.55
1.41
1.27
BHP
0.80
9.75
9.00
8.29
7.61
6.98
6.39
5.85
5.35
4.90
4.48
4.10
3.76
3.44
3.15
2.88
2.64
2.42
2.21
2.02
1.85
1.69
1.54
BHP
907
9.66
7.16
9.56
8.91
8.30
7.71
4.82
894
989
978
967
957
946
936
927
918
909
901
---
---
---
---
3.56
916
992
982
972
962
953
945
937
929
922
997
988
979
971
964
957
951
944
938
932
RPM
---
---
994
987
980
974
---
RPM
4.91
4.60
4.30
4.01
---
BHP
6.39 1034 6.81
5.96 1025 6.37
5.56 1016 5.97
5.19 1008 5.59
4.85 1001 5.24
4.52
4.22
3.93
3.66
3.40
BHP
7.43 1028 7.86 1066 8.32
6.93 1018 7.34 1055 7.78
6.46 1007 6.85 1044 7.28
6.01
5.59
5.20
4.83
4.49
4.18
3.88
3.61
3.35
3.10
BHP
2.60
8.65 1025 9.10 1062 9.59 1101 10.12
8.09 1013 8.51 1050 8.98 1089 9.49
7.55 1003 7.96 1039 8.40 1077 8.89
7.03
6.54
6.07
5.63
5.22
4.83
4.48
4.15
3.84
909
903
897
RPM
2.40
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
9.42 1011 9.87 1048 10.35 1085 10.86 1124 11.42
8.80 1000 9.25 1036 9.71 1073 10.22 1112 10.77
8.21
7.65
7.12
6.61
6.12
5.65
5.22
880
887
3.30
3.05
2.82
BHP
2.20
988 10.06 1023 10.52 1059 11.00 - - -
976
965
954
943
932
921
910
900
890
4.45
4.11
3.80
3.51
874
868
861
RPM
2.00
965 10.24 1000 10.74 1035 11.20 - - -
953
941
8.98
930
8.33
918
6.62
6.12
895
5.64
884
5.19
4.78
881
872
4.04
4.39
864
857
850
3.24
3.00
837
843
2.77
2.56
BHP
831
824
RPM
3.72
3.43
3.16
2.92
2.70
2.50
2.30
BHP
873
862
852
843
833
825
817
809
802
796
790
784
RPM
7.71
7.13
6.58
6.06
5.57
5.11
4.69
4.30
3.95
3.63
3.34
3.07
2.83
2.61
2.41
2.22
2.04
BHP
1.80
943 10.38 977 10.94 1012 11.43 - - -
930
918
906
894
881
869
857
845
834
823
812
801
792
782
774
766
758
751
744
738
RPM
1.60
---
9.72
9.00
8.32
7.67
7.06
6.49
5.95
5.46
5.00
4.58
4.20
3.85
3.53
3.24
2.97
2.73
2.51
2.31
2.12
1.95
1.79
BHP
1.40
922 10.48 955 11.12 - - -
909
896
883
870
857
843
830
817
805
792
780
768
757
747
737
727
718
710
702
694
687
RPM
1.20
TOTAL STATIC PRESSURE - In. w.g.
902 10.54 935 11.26
889
875
861
847
832
818
803
789
775
760
746
733
720
708
696
685
675
665
655
646
638
630
RPM
1.00
Then determine from blower table blower motor output and drive required.
See page 23 for wet coil and option/accessory air resistance data.
See page 23 for factory installed drive kit specifications.
1 - Wet indoor coil air resistance of selected unit.
2 - Any factory installed options air resistance (heat section, economizer, etc.)
3 - Any field installed accessories air resistance (duct resistance, diffuser, etc.)
BLOWER TABLE INCLUDES RESISTANCE FOR BASE UNIT ONLY WITH DRY INDOOR COIL & AIR FILTERS IN PLACE
FOR ALL UNITS ADD:
BLOWER DATA
BLOWER DATA
FACTORY INSTALLED BELT DRIVE KIT SPECIFICATIONS
Motor Efficiency
Nominal
hp
Maximum
hp
Drive Kit Number
RPM Range
Standard
5
5.75
5
660 - 810
Standard
5
5.75
6
770 - 965
Standard
5
5.75
7
570 - 720
Standard
5
5.75
8
480 - 630
Standard
5
5.75
9
410 - 535
Standard
7.5
8.63
3
715 - 880
Standard
7.5
8.63
4
770 - 965
Standard
10
11.50
1
740 - 895
Standard
10
11.50
2
870 - 1045
NOTE - Using total air volume and system static pressure requirements determine from blower performance tables rpm and motor output required. Maximum usable
output of motors furnished are shown. In Canada, nominal motor output is also maximum usable motor output. If motors of comparable output are used, be sure to keep
within the service factor limitations outlined on the motor nameplate.
FACTORY INSTALLED OPTIONS/FIELD INSTALLED ACCESSORY AIR RESISTANCE
Wet Indoor
Coil
Gas Heat Exchanger
Filters
MERV 8
MERV 13
Horizontal
Roof Curb
in. w.g.
in. w.g.
in. w.g.
in. w.g.
0.11
0.00
0.00
0.00
0.04
0.10
0.13
0.00
0.00
0.00
0.05
0.10
0.12
0.15
0.00
0.00
0.00
0.06
0.13
0.11
0.14
0.17
0.01
0.00
0.01
0.07
6000
0.14
0.12
0.16
0.19
0.01
0.00
0.02
0.08
6500
0.16
0.13
0.18
0.21
0.01
0.01
0.02
0.09
7000
0.18
0.14
0.20
0.24
0.02
0.01
0.03
0.10
7500
0.20
0.15
0.21
0.25
0.02
0.01
0.04
0.11
8000
0.22
0.17
0.24
0.28
0.02
0.01
0.04
0.13
8500
0.24
0.20
0.27
0.31
0.03
0.01
0.04
0.15
9000
0.27
0.22
0.29
0.34
0.04
0.01
0.04
0.17
9500
0.29
0.24
0.32
0.38
0.04
0.02
0.06
0.19
10000
0.31
0.27
0.36
0.42
0.05
0.02
0.06
0.21
10500
0.33
0.30
0.40
0.46
0.06
0.02
0.06
0.24
11000
0.36
0.33
0.43
0.50
0.07
0.02
0.07
0.27
11500
0.39
0.37
0.48
0.55
0.08
0.02
0.08
0.30
12000
0.41
0.40
0.52
0.60
0.10
0.02
0.08
0.33
12500
0.44
0.44
0.57
0.65
0.11
0.03
0.10
0.37
13000
0.47
0.48
0.61
0.70
0.13
0.03
0.10
0.40
13500
0.49
0.53
0.67
0.76
0.14
0.03
0.11
0.44
14000
0.52
0.57
0.72
0.82
0.16
0.03
0.12
0.49
14500
0.55
0.62
0.78
0.89
0.18
0.04
0.13
0.53
15000
0.58
0.68
0.84
0.95
0.21
0.04
0.13
0.58
Air
Volume
cfm
Standard
Heat
Medium
Heat
High
Heat
Economizer
in. w.g.
in. w.g.
in. w.g.
in. w.g.
4000
0.07
0.08
0.08
4500
0.09
0.09
5000
0.10
5500
E-Series Packaged Gas / Electric 20 to 30 Ton / Page 23
BLOWER DATA
POWER EXHAUST FAN PERFORMANCE - STANDARD STATIC
Return Duct Negative Static Pressure
Air Volume Exhausted
in. w.g.
cfm
0.00
12,800
0.05
12,200
0.10
11,500
0.15
10,800
0.20
9900
0.25
9000
0.30
7900
0.35
6750
0.40
5450
0.45
4150
0.50
2900
POWER EXHAUST FANS - 50% HIGH STATIC OPERATION
Air
Volume
cfm
4000
RETURN DUCT NEGATIVE STATIC PRESSURE - In. w.g.
0
0.10
0.20
0.30
0.40
0.50
0.60
0.70
0.80
0.90
1.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
---
---
---
---
430 0.40 475 0.45 520 0.50 570 0.55 615 0.65 665 0.70 710 0.75 755 0.85
---
---
4500
---
---
415 0.45 460 0.55 500 0.60 545 0.65 585 0.70 625 0.80 670 0.85 710 0.95 750 1.00 795 1.10
5000
415 0.55 455 0.65 490 0.70 530 0.75 570 0.85 605 0.90 645 1.00 680 1.05 720 1.15 755 1.20 795 1.30
5500
460 0.75 495 0.85 525 0.90 560 0.95 595 1.05 630 1.10 665 1.20 700 1.30 735 1.35 765 1.45 800 1.55
6000
500 1.00 530 1.05 565 1.15 595 1.20 625 1.30 660 1.40 690 1.45 720 1.55 750 1.65 785 1.70 815 1.80
6500
540 1.25 570 1.30 600 1.40 630 1.50 660 1.60 685 1.65 715 1.75 745 1.85 775 1.95 805 2.05 830 2.10
7000
585 1.55 610 1.65 635 1.70 665 1.85 690 1.90 720 2.00 745 2.10 770 2.20 800 2.30 825 2.40 855 2.50
7500
625 1.90 650 2.00 675 2.10 700 2.20 725 2.30 750 2.40 775 2.50 800 2.60 825 2.70 850 2.80 875 2.90
8000
665 2.30 690 2.40 715 2.55 735 2.60 760 2.70 785 2.85 810 2.95 830 3.05 855 3.15 880 3.25 905 3.40
8500
710 2.80 730 2.90 755 3.00 775 3.10 795 3.20 820 3.35 840 3.45 865 3.55 885 3.65 910 3.80 930 3.90
POWER EXHAUST FANS - 100% HIGH STATIC OPERATION
Air
Volume
cfm
8500
RETURN DUCT NEGATIVE STATIC PRESSURE - In. w.g.
0
0.10
0.20
0.30
0.40
0.50
0.60
0.70
0.80
0.90
1.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
475 1.30 500 1.30 525 1.40 550 1.50 585 1.60 625 1.75 670 1.90 710 2.10 745 2.30 780 2.50 815 2.70
9000
520 1.55 535 1.60 550 1.65 570 1.70 605 1.85 640 1.95 685 2.15 720 2.35 760 2.55 790 2.75 825 3.00
9500
550 1.80 560 1.85 575 1.90 600 2.00 620 2.10 655 2.20 695 2.40 735 2.60 770 2.80 800 3.00 835 3.25
10,000
575 2.10 590 2.15 605 2.20 620 2.30 645 2.40 675 2.50 710 2.65 745 2.85 780 3.05 815 3.30 845 3.50
10,500
605 2.45 615 2.45 625 2.50 645 2.60 670 2.75 690 2.80 725 3.00 755 3.15 790 3.35 825 3.60 855 3.80
11,000
630 2.80 645 2.85 660 2.95 675 3.00 685 3.05 715 3.20 740 3.30 770 3.50 805 3.70 835 3.90 870 4.20
11,500
665 3.25 675 3.30 680 3.30 695 3.40 715 3.50 735 3.60 755 3.70 785 3.85 815 4.05 850 4.30 880 4.50
12,000
685 3.60 700 3.70 710 3.75 725 3.85 740 3.95 755 4.00 780 4.15 805 4.30 830 4.45 860 4.65 890 4.90
12,500
720 4.10 730 4.20 740 4.25 750 4.30 765 4.40 780 4.50 800 4.60 820 4.75 845 4.90 875 5.10 905 5.35
13,000
745 4.60 750 4.65 765 4.75 780 4.85 790 4.90 805 5.00 820 5.10 840 5.25 865 5.40 890 5.60 915 5.80
13,500
775 5.15 785 5.25 795 5.35 805 5.40 815 5.50 830 5.60 845 5.70 865 5.80 880 5.95 905 6.10 930 6.30
14,000
805 5.80 810 5.80 820 5.90 830 6.00 845 6.10 855 6.20 870 6.30 885 6.40 905 6.55 925 6.70
---
HIGH STATIC POWER EXHAUST FANS WITH CONSTANT AIR VOLUME − DRIVE KIT SPECIFICATIONS
Power Exhaust Fan Model No.
Motor HP
Drive Kit Number
RPM Range
LAPEB30/36A (50%)
(2) 2 hp
1
406 - 533
LAPEB30/36B (50%)
(2) 2 hp
2
531 - 731
LAPEB30/36C (50%)
(2) 2 hp
3
731 - 932
LAPEB30/36D (100%)
(3) 2 hp
1
406 - 533
LAPEB30/36E (100%)
(3) 2 hp
2
531 - 731
LAPEB30/36F (100%)
(3) 2 hp
3
731 - 932
NOTE − Using total air volume and system static pressure requirements, determine from blower performance tables rpm and motor output required.
E-Series Packaged Gas / Electric 20 to 30 Ton / Page 24
---
BLOWER DATA
CEILING DIFFUSER AIR RESISTANCE - in. w.g.
Step-Down Diffuser
Air
Volume
cfm
Flush Diffuser
LARTD30/36
LAFD30/36
2 Ends Open
1 Side/2 Ends Open
All Ends & Sides Open
7500
0.37
0.31
0.25
0.29
8000
0.42
0.36
0.29
0.34
8500
0.48
0.41
0.34
0.39
9000
0.55
0.47
0.39
0.44
9500
0.62
0.53
0.45
0.51
10,000
0.70
0.60
0.51
0.57
10,500
0.78
0.68
0.58
0.65
11,000
0.87
0.76
0.65
0.72
11,500
0.97
0.85
0.73
0.81
12,000
1.08
0.94
0.82
0.9
12,500
1.19
1.04
0.91
0.99
13,000
1.30
1.15
1.00
1.10
13,500
1.43
1.26
1.10
1.20
14,000
1.56
1.38
1.20
1.31
14,500
1.69
1.50
1.31
1.43
15,000
1.84
1.63
1.43
1.56
CEILING DIFFUSER AIR THROW DATA - ft.
1
1
Effective Throw Range - ft.
Air Volume
cfm
Step-Down
Flush
9000
40 - 47
29 - 35
9500
43 - 50
33 - 41
10,000
46 - 54
37 - 46
10,500
50 - 58
42 - 51
11,000
53 - 61
46 - 56
11,500
55 - 64
50 - 61
12,000
58 - 67
54 - 66
12,500
61 - 71
58 - 71
13,000
64 - 74
62 - 75
13,500
67 - 77
66 - 79
Throw is the horizontal or vertical distance an airstream travels on leaving the outletor diffuser before the maximum velocity is reduced
to 50 ft. per minute. Four sides open.
E-Series Packaged Gas / Electric 20 to 30 Ton / Page 25
ELECTRICAL DATA
20 TON
20 TON HIGH EFFICIENCY - VARIABLE AIR VOLUME (VAV)
1
Voltage - 60hz
Compressor 1
Compressor 2
Compressor 3
Compressor 4
LGH242H4V
208/230V - 3 Ph
460V - 3 Ph
575V - 3 Ph
13.5
8
5
Locked Rotor Amps
109
59
40
Rated Load Amps
13.5
8
5
Locked Rotor Amps
109
59
40
Rated Load Amps
Rated Load Amps
13.5
8
5
Locked Rotor Amps
109
59
40
Rated Load Amps
13.5
8
5
Locked Rotor Amps
109
59
40
Outdoor Fan
Motors (6)
Full Load Amps
2.4
1.3
1
(14.4)
(7.8)
(6)
Standard
Power Exhaust
(3) 0.33 HP
Full Load Amps
2.4
1.3
1
(7.2)
(3.9)
(3)
50% High Static
Power Exhaust
(2) 2 HP
Full Load Amps
7.5
3.4
2.7
(total)
(15)
(6.8)
(5.4)
100% High Static
Power Exhaust
(3) 2 HP
Full Load Amps
7.5
3.4
2.7
(22.5)
(10.2)
(8.1)
15
15
20
(total)
(total)
(total)
Service Outlet 115V GFI (amps)
Indoor Blower
Motor
2
3
Maximum
Overcurrent
Protection
Minimum
Circuit
Ampacity
Horsepower
5
7.5
10
5
7.5
10
5
Full Load Amps
16.7
24.2
30.8
Unit Only
100
110
125
With (3) 0.33 HP
Standard Power Exhaust
110
125
With 50% High Static
Power Exhaust (2) 2 HP
110
With 100% High Static
Power Exhaust (3) 2 HP
125
7.5
10
7.6
11
14
6.1
9
11
50
60
70
35
45
50
125
60
60
70
40
45
50
125
150
60
70
70
45
50
50
125
150
60
70
80
45
50
50
Unit Only
90
99
107
50
54
58
34
38
40
With (3) 0.33 HP
Standard Power Exhaust
97
106
115
54
58
62
37
41
43
With 50% High Static
Power Exhaust (2) 2 HP
105
114
122
57
61
65
40
43
46
With 100% High Static
Power Exhaust (3) 2 HP
112
122
130
60
64
68
42
46
48
NOTE - All units have a minimum Short Circuit Current Rating (SCCR) of 5000 amps.
1
Extremes of operating range are plus and minus 10% of line voltage.
2
HACR type breaker or fuse.
3
Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.
E-Series Packaged Gas / Electric 20 to 30 Ton / Page 26
ELECTRICAL DATA
25 TON
25 TON HIGH EFFICIENCY - CONSTANT AIR VOLUME (CAV)
1
Voltage - 60hz
Compressor 1
Compressor 2
Compressor 3
Compressor 4
Rated Load Amps
LGH300H4B
208/230V - 3 Ph
460V - 3 Ph
575V - 3 Ph
22.4
10.6
7.7
Locked Rotor Amps
149
75
54
Rated Load Amps
22.4
10.6
7.7
Locked Rotor Amps
149
75
54
Rated Load Amps
22.4
10.6
7.7
Locked Rotor Amps
149
75
54
Rated Load Amps
22.4
10.6
7.7
Locked Rotor Amps
149
75
54
Outdoor Fan
Motors (6)
Full Load Amps
2.4
1.3
1
(14.4)
(7.8)
(6)
Standard
Power Exhaust
(3) 0.33 HP
Full Load Amps
2.4
1.3
1
(7.2)
(3.9)
(3)
50% High Static
Power Exhaust
(2) 2 HP
Full Load Amps
7.5
3.4
2.7
(total)
(15)
(6.8)
(5.4)
100% High Static
Power Exhaust
(3) 2 HP
Full Load Amps
7.5
3.4
2.7
(22.5)
(10.2)
(8.1)
15
15
20
(total)
(total)
(total)
Service Outlet 115V GFI (amps)
Indoor Blower
Motor
2
3
Maximum
Overcurrent
Protection
Minimum
Circuit
Ampacity
Horsepower
5
7.5
10
5
7.5
10
5
Full Load Amps
16.7
24.2
30.8
Unit Only
150
150
150
With (3) 0.33 HP
Standard Power Exhaust
150
150
With 50% High Static
Power Exhaust (2) 2 HP
150
With 100% High Static
Power Exhaust (3) 2 HP
7.5
10
7.6
11
14
6.1
9
11
70
70
80
50
50
60
150
70
70
80
60
60
60
150
175
70
80
80
60
60
60
150
175
175
80
80
90
60
60
60
Unit Only
127
135
143
61
64
68
45
49
51
With (3) 0.33 HP
Standard Power Exhaust
128
134
142
62
65
68
46
48
52
With 50% High Static
Power Exhaust (2) 2 HP
142
150
158
68
71
75
51
54
56
With 100% High Static
Power Exhaust (3) 2 HP
149
157
165
71
75
78
53
57
59
NOTE - All units have a minimum Short Circuit Current Rating (SCCR) of 5000 amps.
1
Extremes of operating range are plus and minus 10% of line voltage.
2
HACR type breaker or fuse.
3
Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.
E-Series Packaged Gas / Electric 20 to 30 Ton / Page 27
ELECTRICAL DATA
25 TON
25 TON HIGH EFFICIENCY - VARIABLE AIR VOLUME (VAV)
1
Voltage - 60hz
Compressor 1
Compressor 2
Compressor 3
Compressor 4
Rated Load Amps
LGH300H4V
208/230V - 3 Ph
460V - 3 Ph
575V - 3 Ph
22.4
10.6
7.7
Locked Rotor Amps
149
75
54
Rated Load Amps
22.4
10.6
7.7
Locked Rotor Amps
149
75
54
Rated Load Amps
22.4
10.6
7.7
Locked Rotor Amps
149
75
54
Rated Load Amps
22.4
10.6
7.7
Locked Rotor Amps
149
75
54
Outdoor Fan
Motors (6)
Full Load Amps
2.4
1.3
1
(14.4)
(7.8)
(6)
Standard
Power Exhaust
(3) 0.33 HP
Full Load Amps
2.4
1.3
1
(7.2)
(3.9)
(3)
50% High Static
Power Exhaust
(2) 2 HP
Full Load Amps
7.5
3.4
2.7
(total)
(15)
(6.8)
(5.4)
100% High Static
Power Exhaust
(3) 2 HP
Full Load Amps
7.5
3.4
2.7
(22.5)
(10.2)
(8.1)
15
15
20
(total)
(total)
(total)
Service Outlet 115V GFI (amps)
Indoor Blower
Motor
2
3
Maximum
Overcurrent
Protection
Minimum
Circuit
Ampacity
Horsepower
5
7.5
10
5
7.5
10
5
Full Load Amps
16.7
24.2
30.8
Unit Only
150
150
150
With (3) 0.33 HP
Standard Power Exhaust
150
150
With 50% High Static
Power Exhaust (2) 2 HP
150
With 100% High Static
Power Exhaust (3) 2 HP
7.5
10
7.6
11
14
6.1
9
11
70
70
80
50
50
60
175
70
70
80
50
60
60
150
175
70
80
80
60
60
60
150
175
175
80
80
90
60
60
60
Unit Only
127
135
143
61
64
68
45
49
51
With (3) 0.33 HP
Standard Power Exhaust
134
142
150
65
68
72
48
52
54
With 50% High Static
Power Exhaust (2) 2 HP
142
150
158
68
71
75
51
54
56
With 100% High Static
Power Exhaust (3) 2 HP
149
157
165
71
75
78
53
57
59
NOTE - All units have a minimum Short Circuit Current Rating (SCCR) of 5000 amps.
1
Extremes of operating range are plus and minus 10% of line voltage.
2
HACR type breaker or fuse.
3
Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.
E-Series Packaged Gas / Electric 20 to 30 Ton / Page 28
ELECTRICAL DATA
30 TON
30 TON HIGH EFFICIENCY - CONSTANT AIR VOLUME (CAV)
1
Voltage - 60hz
Compressor 1
Compressor 2
Compressor 3
Compressor 4
LGH360H4B
208/230V - 3 Ph
460V - 3 Ph
575V - 3 Ph
Rated Load Amps
25
12.2
9
Locked Rotor Amps
164
100
78
Rated Load Amps
25
12.2
9
Locked Rotor Amps
164
100
78
Rated Load Amps
25
12.2
9
Locked Rotor Amps
164
100
78
Rated Load Amps
25
12.2
9
Locked Rotor Amps
164
100
78
Outdoor Fan
Motors (6)
Full Load Amps
2.4
1.3
1
(14.4)
(7.8)
(6)
Standard
Power Exhaust
(3) 0.33 HP
Full Load Amps
2.4
1.3
1
(7.2)
(3.9)
(3)
50% High Static
Power Exhaust
(2) 2 HP
Full Load Amps
7.5
3.4
2.7
(total)
(15)
(6.8)
(5.4)
100% High Static
Power Exhaust
(3) 2 HP
Full Load Amps
7.5
3.4
2.7
(22.5)
(10.2)
(8.1)
15
15
20
(total)
(total)
(total)
Service Outlet 115V GFI (amps)
Indoor Blower
Motor
2
3
Maximum
Overcurrent
Protection
Minimum
Circuit
Ampacity
Horsepower
5
7.5
10
5
7.5
10
5
Full Load Amps
16.7
24.2
30.8
Unit Only
150
150
175
With (3) 0.33 HP
Standard Power Exhaust
150
175
With 50% High Static
Power Exhaust (2) 2 HP
175
With 100% High Static
Power Exhaust (3) 2 HP
7.5
10
7.6
11
14
6.1
9
11
70
80
80
60
60
60
175
80
80
90
60
60
60
175
175
80
80
90
60
60
70
175
175
200
80
90
90
60
70
70
Unit Only
138
145
153
68
71
75
51
54
56
With (3) 0.33 HP
Standard Power Exhaust
145
153
161
72
75
78
54
57
59
With 50% High Static
Power Exhaust (2) 2 HP
153
160
168
75
78
81
56
59
62
With 100% High Static
Power Exhaust (3) 2 HP
160
168
176
78
81
85
59
62
64
NOTE - All units have a minimum Short Circuit Current Rating (SCCR) of 5000 amps.
1
Extremes of operating range are plus and minus 10% of line voltage.
2
HACR type breaker or fuse.
3
Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.
E-Series Packaged Gas / Electric 20 to 30 Ton / Page 29
ELECTRICAL DATA
30 TON
30 TON HIGH EFFICIENCY - VARIABLE AIR VOLUME (VAV)
1
Voltage - 60hz
Compressor 1
Compressor 2
Compressor 3
Compressor 4
LGH360H4V
208/230V - 3 Ph
460V - 3 Ph
575V - 3 Ph
Rated Load Amps
25
12.2
9
Locked Rotor Amps
164
100
78
Rated Load Amps
25
12.2
9
Locked Rotor Amps
164
100
78
Rated Load Amps
25
12.2
9
Locked Rotor Amps
164
100
78
Rated Load Amps
25
12.2
9
Locked Rotor Amps
164
100
78
Outdoor Fan
Motors (6)
Full Load Amps
2.4
1.3
1
(14.4)
(7.8)
(6)
Standard
Power Exhaust
(3) 0.33 HP
Full Load Amps
2.4
1.3
1
(7.2)
(3.9)
(3)
7.5
3.4
2.7
(15)
(6.8)
(5.4)
7.5
3.4
2.7
(22.5)
(10.2)
(8.1)
15
15
20
(total)
(total)
50% High Static
Power Exhaust
(2) 2 HP
100% High Static
Power Exhaust
(3) 2 HP
Service Outlet 115V GFI (amps)
Indoor Blower
Motor
2
3
Maximum
Overcurrent
Protection
Minimum
Circuit
Ampacity
Horsepower
5
7.5
10
5
7.5
10
5
Full Load Amps
16.7
24.2
30.8
Unit Only
150
150
175
With (3) 0.33 HP
Standard Power Exhaust
150
175
With 50% High Static
Power Exhaust (2) 2 HP
175
With 100% High Static
Power Exhaust (3) 2 HP
7.5
10
7.6
11
14
6.1
9
11
70
80
80
60
60
60
175
80
80
90
60
60
60
175
175
80
80
90
60
60
70
175
175
200
80
90
90
60
70
70
Unit Only
138
145
153
68
71
75
51
54
56
With (3) 0.33 HP
Standard Power Exhaust
145
153
161
72
75
78
54
57
59
With 50% High Static
Power Exhaust (2) 2 HP
153
160
168
75
78
81
56
59
62
With 100% High Static
Power Exhaust (3) 2 HP
160
168
176
78
81
85
59
62
64
NOTE - All units have a minimum Short Circuit Current Rating (SCCR) of 5000 amps.
1
Extremes of operating range are plus and minus 10% of line voltage.
2
HACR type breaker or fuse.
3
Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.
E-Series Packaged Gas / Electric 20 to 30 Ton / Page 30
ELECTRICAL ACCESSORIES
20 TON HIGH EFFICIENCY
LGH242H4
Voltage - 60hz - 3 phase
208/230V
Indoor Blower Motor Horsepower
460V
575V
5
7.5
10
5
7.5
10
5
7.5
10
Unit Only
54W86
54W86
54W86
54W85
54W85
54W85
54W85
54W85
54W85
Unit + Standard Power
Exhaust (3) 0.33 HP
54W86
54W86
54W86
54W85
54W85
54W85
54W85
54W85
54W85
Unit + 50% High Static
Power Exhaust (2) 2 HP
54W86
54W86
54W86
54W85
54W85
54W85
54W85
54W85
54W85
Unit + 100% High Static
Power Exhaust (3) 2 HP
54W86
54W86
54W86
54W85
54W85
54W85
54W85
54W85
54W85
30K75
30K75
30K75
30K75
30K75
30K75
30K75
30K75
30K75
Disconnect
Terminal Block
25 TON HIGH EFFICIENCY
LGH300H4
Voltage - 60hz - 3 phase
208/230V
Indoor Blower Motor Horsepower
460V
575V
5
7.5
10
5
7.5
10
5
7.5
10
Unit Only
54W86
54W86
54W87
54W85
54W85
54W85
54W85
54W85
54W85
Unit + Standard Power
Exhaust (3) 0.33 HP
54W86
54W87
54W87
54W85
54W85
54W85
54W85
54W85
54W85
Unit + 50% High Static
Power Exhaust (2) 2 HP
54W87
54W87
54W87
54W85
54W85
54W86
54W85
54W85
54W85
Unit + 100% High Static
Power Exhaust (3) 2 HP
54W7
54W87
54W87
54W85
54W86
54W86
54W85
54W85
54W85
30K75
30K75
30K75
30K75
30K75
30K75
30K75
30K75
30K75
Disconnect
Terminal Block
30 TON HIGH EFFICIENCY
LGH360H4
Voltage - 60hz - 3 phase
208/230V
Indoor Blower Motor Horsepower
Disconnect
Terminal Block
460V
575V
5
7.5
10
5
7.5
10
5
7.5
10
Unit Only
54W87
54W87
54W87
54W85
54W85
54W86
54W85
54W85
54W85
Unit + Standard Power
Exhaust (3) 0.33 HP
54W87
54W87
54W87
54W85
54W86
54W86
54W85
54W85
54W85
Unit + 50% High Static
Power Exhaust (2) 2 HP
54W87
54W87
54W87
54W86
54W86
54W86
54W85
54W85
54W85
Unit + 100% High Static
Power Exhaust (3) 2 HP
54W87
54W87
54W87
54W86
54W86
54W86
54W85
54W85
54W85
30K75
30K75
30K75
30K75
30K75
30K75
30K75
30K75
30K75
E-Series Packaged Gas / Electric 20 to 30 Ton / Page 31
UNIT CLEARANCES - INCHES (MM)
Unit With Economizer
C
OUTDOOR
AIR HOOD
D
B
A
1
Unit Clearance
Service Clearance
A
B
C
D
in.
mm
in.
mm
in.
mm
in.
mm
60
1524
36
914
36
914
66
1676
Clearance to Combustibles
36
914
1
25
1
25
1
25
Minimum Operation Clearance
45
1143
36
914
36
914
41
1041
Top
Clearance
Unobstructed
NOTE - Entire perimeter of unit base requires support when elevated above the mounting surface.
1
S
ervice Clearance - Required for removal of serviceable parts.
Clearance to Combustibles - Required clearance to combustible material.
Minimum Operation Clearance - Required clearance for proper unit operation.
Unit With High Static Power Exhaust Fans
C
OUTDOOR
AIR HOOD
D
B
A
1
Unit Clearance
A
B
C
D
in.
mm
in.
mm
in.
mm
in.
mm
Service Clearance
60
1524
36
914
80
2032
66
1676
Clearance to Combustibles
36
914
1
25
1
25
1
25
Minimum Operation Clearance
45
1143
36
914
80
2032
41
1041
NOTE - Entire perimeter of unit base requires support when elevated above the mounting surface.
1
S
ervice Clearance - Required for removal of serviceable parts.
Clearance to Combustibles - Required clearance to combustible material.
Minimum Operation Clearance - Required clearance for proper unit operation.
E-Series Packaged Gas / Electric 20 to 30 Ton / Page 32
Top
Clearance
Unobstructed
UNIT CLEARANCES - INCHES (MM)
Unit With Horizontal Barometric Relief Dampers
OPTIONAL BAROMETRIC
RELIEF EXHAUST
DAMPERS
(Field Installed
on Return Air Duct)
NOTE Allow adequate clearance for duct and
barometric relief damper installation.
NOTE Dampers may be installed on each side
of return air duct or end to end on one side of
return air duct.
OUTDOOR
AIR HOOD
C
B
A
1
Unit Clearance
A
B
C
in.
mm
in.
mm
in.
mm
Service Clearance
60
1524
36
914
66
1676
Clearance to Combustibles
36
914
1
25
1
25
Minimum Operation Clearance
45
1143
36
914
41
1041
Top
Clearance
Unobstructed
NOTE - Entire perimeter of unit base requires support when elevated above the mounting surface.
1
S
ervice Clearance - Required for removal of serviceable parts.
Clearance to Combustibles - Required clearance to combustible material.
Minimum Operation Clearance - Required clearance for proper unit operation.
E-Series Packaged Gas / Electric 20 to 30 Ton / Page 33
OUTDOOR SOUND DATA
Unit
Model Number
242, 300, 360
Octave Band Sound Power Levels dBA, re 10-12 Watts Center Frequency - HZ
1
125
250
500
1000
2000
4000
8000
Sound Rating
Number (dB)
84
85
90
90
85
80
72
95
Note - The octave sound power data does not include tonal corrections.
1
Sound Rating Number according to AHRI Standard 370-2001.
E-Series Packaged Gas / Electric 20 to 30 Ton / Page 34
WEIGHT DATA
Model Number
Net
Shipping
lbs.
kg
lbs.
kg
242 Base Unit
3107
1435
3317
1505
242 Max. Unit
3485
1581
3695
1676
300 Base Unit
3107
1435
3317
1505
300 Max. Unit
3485
1581
3695
1676
360 Base Unit
3107
1435
3317
1505
360 Max. Unit
3485
1581
3695
1676
OPTIONS / ACCESSORIES
Description
CEILING DIFFUSERS
Step-Down
LARTD30/36
Flush
LAFD30/36
Transitions
LASRT30/36
ECONOMIZER / OUTDOOR AIR / EXHAUST
Economizer
E1ECON15D-1
Barometric Relief
Downflow Barometric Relief Dampers
E1DAMP60D-1
Horizontal Barometric Relief Dampers
LAGEDH30/36
Outdoor Air Dampers
Damper Section (downflow)
Motorized - E1DAMP25D-1Damper Section (downflow)
Manual - E1DAMO15D-1Outdoor Air Hood (downflow)
LAOAH30/36
Power Exhaust
Standard Static - E1PWRE40D
50% High Static - LAPEB30/36
100% High Static with or without VFD - LAPEB30/36 or LAPEV30/36
GAS HEAT EXCHANGER (NET WEIGHT)
Medium Heat (adder over standard heat)
High Heat (adder over standard heat)
PACKAGING
LTL Packaging (less than truck load)
ROOF CURBS - CLIP CURB
Downflow
14 in. height
LARMF30/36S-14
18 in. height
LARMF30/36S-18
24 in. height
LARMF30/36S-24
Horizontal
30 in. height
LARMFH30/36S-30
41 in. height
LARMFH30/36S-41
ROOF CURBS - STANDARD
Downflow
14 in. height
LARMF18/36-14
24 in. height
LARMF18/36-24
Downflow - Full Perimeter
14 in. height
S6CURB1012124 in. height
S6CURB11121Horizontal
30 in. height
LARMFH30/36-30
41 in. height
LARMFH30/36-41
Shipping Weight
lbs.
kg
437
414
85
198
188
39
119
54
45
20
20
9
72
68
76
33
31
34
99
460
525
45
209
238
18
64
8
29
300
136
149
204
248
68
93
112
456
480
207
218
160
220
73
100
180
248
82
112
445
725
202
329
E-Series Packaged Gas / Electric 20 to 30 Ton / Page 35
DIMENSIONS - INCHES (MM)
CORNER WEIGHTS
Model No.
LGH242 Base Unit
LGH242 Max. Unit
LGH300 Base Unit
LGH300 Max. Unit
LGH360 Base Unit
LGH360 Max. Unit
AA
lbs.
632
709
632
709
632
709
BB
kg
287
322
287
322
287
322
lbs.
635
712
635
712
635
712
CC
kg
288
323
288
323
288
323
lbs.
912
1023
912
1023
912
1023
CENTER OF GRAVITY
EE
FF
in.
mm
in.
mm
60
1524
37
940
60
1524
37
940
60
1524
37
940
60
1524
37
940
60
1524
37
940
60
1524
37
940
DD
kg
414
464
414
464
414
464
lbs.
928
1041
928
1041
928
1041
kg
421
472
421
472
421
472
Base Unit - The unit with NO INTERNAL OPTIONS.
Max. Unit - The unit with ALL INTERNAL OPTIONS Installed. (Economizer, Standard Static Power Exhaust Fans, Controls, etc.). Does not include accessories external
to unit or high static power exhaust.
EE
4-1/4
(108)
AA
5-3/4
(146)
15 (381)
78-1/2 (1994)
18 (457)
17-1/2
(445)
BB
BOTTOM RETURN
AIR OPENING
CENTER OF
GRAVITY
28
28
(711)
(711)
4-1/2 20 (508)
20 (508)
(114)
FF
BOTTOM SUPPLY
AIR OPENINGS
4 (102)
DD
CC
BOTTOM POWER/GAS ENTRY 5 X 8 inches (127 X 203 mm)
TOP VIEW
9 (229)
OPTIONAL
115 VOLT OUTLET
(Factory Installed Inside Unit)
90-1/8 (2289)
145 (3683)
OPTIONAL
DISCONNECT
(Factory Installed)
65
(1651)
SIDE
ELECTRICAL
INLETS
61-3/4
(1568)
CONDENSATE DRAIN
90−3/4 (2305)
END VIEW
E-Series Packaged Gas / Electric 20 to 30 Ton / Page 36
FLUE
OUTLET
OPTIONAL
OUTDOOR
GRILLE KIT
(Field Installed)
(Both Sides)
5-3/4
(146)
5-3/8
(137)
31-1/2
(800)
GAS SUPPLY
INLET
(For Bottom
Gas Supply Only)
3-1/4
(83) 4
(102)
FORKLIFT SLOTS
(Front and Left Side Only)
119−3/4 (3042)
SIDE VIEW
LIFTING HOLES
(For Rigging
Front and Back)
25-3/4
(654)
ACCESSORY DIMENSIONS - INCHES (MM)
OPTIONAL OUTDOOR AIR HOOD DETAIL
WITH STANDARD STATIC POWER EXHAUST FANS
25−1/2
(648)
OPTIONAL
OUTDOOR AIR HOOD
(Factory or Field Installed)
Required with Economizer or
Outdoor Air Damper
1 OPTIONAL
STANDARD STATIC
POWER EXHAUST
FANS HOOD
(Field Installed)
1
Field Installed in Return Air Duct for Horizontal Applications.
OPTIONAL HIGH STATIC POWER EXHAUST FANS DETAIL
41−3/4
(1060)
OPTIONAL
HIGH STATIC
POWER EXHAUST FANS
(Field Installed)
HORIZONTAL BAROMETRIC RELIEF DAMPERS
(Field installed in horizontal return air duct adjacent to unit)
54−1/2 (1384)
52−1/2 (1334)
6-1/2
(165)
FRONT VIEW
SIDE VIEW
1
14-1/2
(368)
1 13
(330)
NOTE − Two furnished per order no.
1 NOTE − Opening size required in return air duct.
E-Series Packaged Gas / Electric 20 to 30 Ton / Page 37
ACCESSORY DIMENSIONS - INCHES (MM)
CLIP CURBS - DOUBLE DUCT OPENING
1-13/16
(46)
1-13/16
(46)
1-3/4
(44)
16 (406)
86-1/4
(2191)
81-1/2
(2070)
82-5/8
(2099) 17 (432)
21 (533)
CURB
RETURN AIR
OPENING
13-1/4
(337)
79-1/2
(2019)
110-1/2
(2807)
115-1/8
(2594)
14 (356)
18 (457)
24 (610)
CURB
SUPPLY AIR
OPENING
61-1/2
(1562)
TYPICAL FLASHING DETAIL FOR ROOF CURB
BASE BOTTOM
DETAIL ROOF CURB
1-13/16
(46)
PACKAGED
UNIT
1/2 (13)
FIBERGLASS
INSULATION
(Furnished)
COUNTER FLASHING
(Field Supplied)
FACTORY INSTALLED
PERIMETER WOOD
NAILER STRIP
NAILER STRIP
(Furnished)
ROOF CURB
(Extends around entire
perimeter of unit)
CANT STRIP
(Field Supplied)
ROOFING
MATERIAL
14 (356)
18 (457)
24 (610)
RIGID INSULATION
(Field Supplied)
1-13/16
(46)
E-Series Packaged Gas / Electric 20 to 30 Ton / Page 38
ACCESSORY DIMENSIONS - INCHES (MM)
STANDARD ROOF CURBS - DOUBLE DUCT OPENING
1-13/16 (46)
1-3/4 (44)
16 (406)
82-5/8
(2099)
86-1/4
(2191)
17 (432)
79-1/2
(2019)
21 (533)
98-1/2
(2502)
CURB
RETURN AIR
OPENING
1-13/16
(46)
13-1/4
(337)
102-1/8
(2594)
CURB
SUPPLY AIR
OPENING
14 (356)
or
24 (610)
61-1/2
(1562)
3/4 (19) Typ.
TYPICAL FLASHING DETAIL FOR ROOF CURB
BASE BOTTOM
DETAIL ROOF CURB
1-13/16
(46)
PACKAGED
UNIT
1 (25)
FIBERGLASS
INSULATION
(Furnished)
COUNTER FLASHING
(Field Supplied)
FACTORY INSTALLED
PERIMETER WOOD
NAILER STRIP
NAILER STRIP
(Furnished)
ROOF CURB
(Extends around entire
perimeter of unit)
CANT STRIP
(Field Supplied)
ROOFING
MATERIAL
14 (356)
24 (610)
RIGID INSULATION
(Field Supplied)
2 (51)
E-Series Packaged Gas / Electric 20 to 30 Ton / Page 39
ACCESSORY DIMENSIONS - INCHES (MM)
STANDARD ROOF CURBS - FULL PERIMETER - DOUBLE DUCT OPENING
1-13/16 (46)
1-3/4 (44)
16 (406)
82-5/8
(2099)
86-1/4
(2191)
17 (432)
79-1/2
(2019)
21 (533)
111-1/2
(2832)
CURB
RETURN AIR
OPENING
1-13/16
(46)
115-1/8
(2924)
13-1/4
(337)
CURB
SUPPLY AIR
OPENING
14 (356)
or
24 (610)
61-1/2
(1562)
3/4 (19) Typ.
TYPICAL FLASHING DETAIL FOR ROOF CURB
BASE BOTTOM
DETAIL ROOF CURB
1-13/16
(46)
PACKAGED
UNIT
1 (25)
FIBERGLASS
INSULATION
(Furnished)
COUNTER FLASHING
(Field Supplied)
FACTORY INSTALLED
PERIMETER WOOD
NAILER STRIP
NAILER STRIP
(Furnished)
ROOF CURB
(Extends around entire
perimeter of unit)
CANT STRIP
(Field Supplied)
ROOFING
MATERIAL
14 (356)
24 (610)
RIGID INSULATION
(Field Supplied)
2 (51)
E-Series Packaged Gas / Electric 20 to 30 Ton / Page 40
ACCESSORY DIMENSIONS - INCHES (MM)
ROOF CURBS WITH SUPPLY & RETURN AIR TRANSITIONS FOR CEILING DIFFUSERS
80-3/4 (2051)
60 (1524)
4-1/2 (114)
60 (1524)
SUPPLY AIR
OPENINGS
28
(711)
LASRT RETURN
TRANSITION
28
(711)
SUPPORT
ANGLE
(Furnished with
Transitions)
54
(1372)
LASRT SUPPLY
TRANSITION
RETURN
AIR OPENING
A
A
TRANSITION DETAIL
1-1/2
(38) Typ.
12
14
(356) (305)
2
(51)
3/4 Typ.
(19)
26-1/2
(673)
26-1/2
(673)
LASRT SUPPLY
TRANSITION
LASRT RETURN
TRANSITION
28
(711)
4-1/2
(114)
28
(711)
SECTION B-B
TOP VIEW
E-Series Packaged Gas / Electric 20 to 30 Ton / Page 41
ACCESSORY DIMENSIONS - INCHES (MM)
HORIZONTAL ROOF CURBS − Requires Optional Horizontal Return Air Panel Kit
102-1/8 (2594)
1-13/16 (46)
1-13/16
(46)
98-1/2 (2502)
Frame
Opening
NOTE LARMFH30/36-30 is designed for horizontal discharge
when unit is mounted on a slab.
LARMFH30/36-41 is designed for horizontal
discharge when unit is mounted on a rooftop.
1-13/16 (46)
Frame
30 (762)
41 (1041)
Opening
1
2
1 (25)
NAILER STRIP
(Furnished)
2 (51)
A
A
SECTION A-A
82-5/8
(2099)
PANEL TO COVER RETURN AIR OPENING IN BOTTOM OF UNIT
(Furnished With Optional Horizontal Return Air Panel Kit)
98-1/2 (2502)
86-1/4
(2191)
SUPPLY AIR
TURNING VANE
(Furnished)
54
(1372)
SIDE VIEW
NOTE − Roof deck may be omitted within confines of curb.
(PACKAGED UNIT)
1-13/16 (46)
TOP VIEW
1,2
NAILER STRIP
(Furnished)
13-1/4 (337)
102-1/8 (2594)
86-1/4 (2191)
5-1/2 (140)
1
2
30 (762)
41 (1041)
75 (1905)
CURB SUPPLY AIR OPENING
With 1-1/2 in. (38 mm) FLANGE
1, 2 18
1
2
SUPPLY AIR
TURNING VANE
(Furnished)
(457)
6-1/2 (165)
17-1/2 (445)
102-1/2 (2604)
86-5/8 (2200)
FRONT VIEW
1
SUPPLY
DUCT
PANELS
(Furnished)
SIDE VIEW
LARMFH30/36-30 2 LARMFH30/36-41
HORIZONTAL SUPPLY AND RETURN AIR OPENINGS
ROOFTOP UNIT WITH HORIZONTAL ROOF CURB
OPTIONAL RETURN AIR PANEL KIT
(Required For Horizontal Applications)
65
(1651)
91 (2311)
LARMFH30/36-30
102 (2591)
LARMFH30/36-41
78-1/2 (1994)
15 (381)
HORIZONTAL RETURN
AIR OPENING
2 (51)
1 26 (660)
LARMFH30/36-30
1 37 (940)
LARMFH30/36-41
1 NOTE − Top of Curb extends 4 inch (102 mm) inside
bottom of unit base. See Typical Flashing Detail.
75 (1905)
HORIZONTAL
SUPPLY AIR OPENING
42-7/8
(1089)
HORIZONTAL ROOF CURB
(Required For Horizontal Applications)
SIDE VIEW
(Horizontal Openings)
E-Series Packaged Gas / Electric 20 to 30 Ton / Page 42
18 (457)
5-1/4
(133)
13-1/4
(337)
6-1/2 (165)
LARMFH30/36-30
17-1/2 (445)
LARMFH30/36-41
ACCESSORY DIMENSIONS - INCHES (MM)
COMBINATION CEILING SUPPLY AND RETURN DIFFUSERS
STEP-DOWN CEILING DIFFUSER
F
E
G
H
G
FLUSH CEILING DIFFUSER
F
E
D
J
K
G
H
G
D
J
K
C
C
2 (51)
2 (51)
N
B
B
M
L
Model Number
A
in.
mm
B
in.
mm
C
in.
mm
D
in.
mm
E
F
G
H
J
K
in.
65-5/8
40-1/2
63-1/2
114
in.
28
mm
711
1-1/2
mm
38
in.
60
mm
1524
in.
1-3/4
in.
in.
in.
in.
mm
1613
in.
in.
mm
D
in.
mm
E
F
G
H
in.
65-5/8
1667
65-5/8
1667
40
1016
63-1/2
1613
63-1/2
mm
1613
in.
4-1/4
mm
108
in.
28
mm
711
in.
1-5/8
mm
32
J
in.
60
mm
1524
K
in.
1-3/4
44
63-1/2
in.
mm
C
1613
4-1/2
in.
B
1029
63-1/2
LAFD30/36
mm
1667
mm
mm
Duct Size
A
1667
in.
mm
N
Model Number
65-5/8
1613
mm
M
LARTD30/36
mm
mm
L
A
A
mm
Duct Size
in.
mm
44
28 x 60
711 x 1524
63-1/2
1613
12-1/8
308
28 x 60
711 x 1524
E-Series Packaged Gas / Electric 20 to 30 Ton / Page 43
Visit us at www.allied-commercial.com
For the latest technical information, visit us at www.allied-commercial.com
Contact us at 1-800-738-4000
NOTE - Due to Allied Commercial ongoing commitment to quality, Specifications, Ratings and Dimensions subject to change without notice and without incurring liability.
Improper installation, adjustment, alteration, service or maintenance can cause property damage or personal injury.
Installation and service must be performed by a qualified installer and servicing agency.
©2012 Allied Air Enterprises LLC, a Lennox International Inc. Company