Energy Meters All our know-how - is now yours

Transcription

Energy Meters All our know-how - is now yours
MAKING MODERN LIVING POSSIBLE
Your Personal Catalog
Energy Meters
All our know-how - is now yours
Index
3
Sonometer™2100
20
Infocal 8
32
SONO 1500 CT
40
Sonometer™1100
Data sheet
SONOMETERTM2100
Ultrasonic energy meter
Description/Application
- Insensitive against magnetite
- Installation in any position
- Free selectable pulse values from 1 ml
MID examination certificate
no.: DE-10-MI004-PTB008
and DE-09-MI004-PTB011
The SONOMETERTM2100 is an ultrasonic energy
meter especially designed for heating, cooling
or combined heating/cooling application in local
and district heating systems.
The SONOMETERTM2100 consists of:
- Ultrasonic flow sensor, type SONO 1500 CT;
- Energy calculator, type INFOCAL 8;
- Pairs of temperature sensors.
The SONOMETERTM2100 has been approved
according to MID.
Features of SONO 1500 CT
- 1st approval in Europe for ultrasonic flow sensor
with dynamic range of qi/qp 1:250 in class 2 (qp
1.5 / 2.5 / 6 / 10 / 15 / 25 / 40 / 60 m³/h)
- Complete dynamic range: ≥ 1:1500
- Lithium battery with a lifetime of 11 years or
external supply
- Temperature range: 5 - 90 °C / 130 °C / 150 °C
- Overload temperature up to 150 °C (sizes qp 0.6
up to 2.5 m³/h)
- Available in nominal sizes: qp 0.6 / 1.0 / 1.5 / 2.5 /
3.5 / 6 / 10 / 15 / 25 / 40 / 60 m³/h
- Unique free-beam principle
- Swirl-free flow around reflector
- Robust stainless steel reflector
- All sizes also available in PN 25
- No calming sections necessary in the inlet and/
or outlet (standard installation)
- NOWA test capability
- Connection to calculator with pulse defined
values
DEN-SMT/PL
VD.SH.L2.02 © Danfoss 08/2011
Features of INFOCAL 8
- Lithium battery with lifetime typical 11 years
or 16 years optional (depending on selected
functionality and connected flow sensor)
- Temperature range: –20 to +190 °C
- Power save mode
- NOWA test capability
- Connection possibility of 2- and 4-wire
temperature sensor pairs
- Remote reading via M-Bus, L-Bus, RS 232,
RS 485, Radio or optical interface
- Integrated Radio (868 or 434 Hz), Real Data or
Open Metering Standard (OMS)
- Individual remote reading (Automatic Meter
Reading) with add on modules Plug&Play
- 2 communication ports (e.g. M-Bus + M-Bus)
- Improved radio performance
- Individual tariff functions
- History memory for 24 months
- Extensive diagnostic displays
- IZAR@SET parameterization software
on Windows basis guarantees optimum
adaptation to the user’s specific needs
1
Data Sheet
SONOMETERTM2100 – Ultrasonic energy meter
Description/Application,
continued
The SONOMETERTM2100 is able to handle 3 types of applications:
DEN-SMT/PL
District heating/boiler application
Combined heating/cooling application
Chilled water application
VD.SH.L2.02 © Danfoss 08/2011
2
SONOMETERTM2100 – Ultrasonic energy meter
Data Sheet
Ordering:
The ordering code no. consists of both dummy code and ordering code.
Dummy code: 087G6012
Ordering code
AAA BB - C D E F G H P AAA - application
only temperature sensors 4
energy meter for heating
energy meter for cooling 1,2
energy meter for heating / cooling 1,2,3
only flow sensor for heating
only flow sensor for cooling 1,3
1
I
J
K
-
-
4TS
2HE
2CO
2HC
15H
15C
0
1
4
00
AT
BA
BG
CN
DK
CZ
DE
GB
HR
IE
IT
KZ
LV
MD
PL
RO
RU
CS
SK
SI
TR
UA
00
1A
1B
1C
1D
1E
1F
1G
1H
1I
1J
1K
1L
1M
1N
2A
2B
2C
2D
2E
2F
2G
2H
2I
2J
2K
2L
2M
0
1
2
3
4
only PN 25 possible
flow sensors for external power supply
C - pressure
not relevant
PN 16
PN 251
0
C
D
1
flange versions must be PN 25
D - flow sensor cable
not relevant
2.5 m
5m
10 m
0
A
B
C
E - installation
not relevant
low temperature
high temperature
0
L
H
F - power supply
not relevant / with external power supply 1
battery 3.6 V DC (A-cell)
battery 3.6 V DC (D-cell) 2
mains unit 230 V AC
mains unit 24 V AC
0
1
2
3
4
1
2
GH - interface modules
modules slot 1
no module in slot 1
Analogue output module (4-20 mA) 1
Combined module (2 pulse inputs / 1 pulse output)
Pulse input module (2 inputs)
M-Bus module
L-Bus module (use for external radio)
RS232 module
RS485 module
modules slot 2
no module in slot 2
Pulse output module 2
Combined module (2 pulse inputs / 1 pulse output) 2
Pulse input module (2 inputs) 2
M-Bus module 2
L-Bus module (use for external radio) 2
RS232 module 2
RS485 module 2
2
P - version of communication
without integrated radio (standard)
Radio 868 MHz Real Data
Radio 434 MHz Real Data
Radio 868 MHz Open Metering Standard
Radio 434 MHz Open Metering Standard
only for flow sensor
for integrated radio
1
2
3
4
0
A
B
C
D
E
F
G
0
A
B
C
D
E
F
G
1
only one module possible
integrated radio is not available
0
1
2
3
4
VD.SH.L2.02 © Danfoss 08/2011
test reports on request
NN - country code
Neutral code with docs in English (standard)
Austria
Bosnia
Bulgaria
China
Denmark
Czech Republic
Germany
United Kingdom
Croatia
Ireland
Italy
Kazakhstan
Latvia
Moldova
Poland
Romania
Russia
Serbia
Slovak Republic
Slovenia
Turkey
Ukraine
M - connections (sets)
without
screwing set R ½” x G ¾ B
screwing set R ¾” x G 1 B
screwing set R 1” x G 1¼ B
screwing set R 1½” x G 2 B
screwing sets are packaged in an extra box
L - accessories / pocket
0
without
for ø 5.2 mm temperature sensors (pair1)
F
brass-pockets, 35 mm, MID 2
DN 15-32
G
brass-pockets, 52 mm, MID
DN 40-65
H
brass-pockets, 85 mm, MID
DN 80-125
I
brass-pockets, 120 mm, MID DN 150-200
3
stainless steel-pockets, 85 mm, MID
DN 80-125
4
stainless steel-pockets, 120 mm, MID DN 150-200
5
stainless steel-pockets, 155 mm, MID
DN 200-250
6
stainless steel-pockets, 210 mm, MID
DN 300
1
versions with one sensor pocket on request
2
max temperature: 105°C
temperature sensor pockets are packaged in an extra box
for ø 6.0 mm temperature sensors (pair)
V
brass-pockets, 40 mm MID DN 25-65
W brass-pockets, 85 mm MID
DN 80-125
X
brass-pockets, 120 mm MID
DN 150-200
Y
stainless steel-pockets, 85 mm MID
DN 80-125
Z
stainless steel-pockets, 120 mm MID DN 150-200
1
stainless steel-pockets, 155 mm MID
DN 200-250
2
stainless steel-pockets, 210 mm MID
DN 300
temperature sensor pockets are packaged in an extra box
Accessories (1 piece) 3
R
ball valve DN 15 - ½” for direct sensor
S
ball valve DN 20 - ¾” for direct sensor
T
ball valve DN 25 - 1” for direct sensor
U
adapter for mounting direct sensor R½” M 10x1
3
not possible for ø 6.0 mm sensors
ball valves packaged in an extra box
1
2
O - verification
without approval mark, no test reports
compliant according to national regulations
PTB K 7.2 for cooling
compliant to MID. With letter of conformity 1
1
includes potting and special temperature sensors for cooling or heating/cooling application
2
meter without type approval
3
120° maximum operation temperature
4
prices in the accessories list valid
BB - (for) flow sensor (type SONO 1500 CT)
not relevant / no flow sensor
qp 0.6 m³/h / 110 mm thread / DN 15 / G¾B / 1 litre / pulse 2
qp 0.6 m³/h / 130 mm thread / DN 20 / G1B / 1 litre / pulse 2
qp 0.6 m³/h / 190 mm thread / DN 20 / G1B / 1 litre / pulse 2
qp 1.0 m³/h / 110 mm thread / DN 15 / G¾B / 1 litre / pulse 2
qp 1.0 m³/h / 130 mm thread / DN 20 / G1B / 1 litre / pulse 2
qp 1.0 m³/h / 190 mm thread / DN 20 / G1B / 1 litre / pulse 2
qp 1.5 m³/h / 110 mm thread / DN 15 / G¾B / 1 litre / pulse 2
qp 1.5 m³/h / 130 mm thread / DN 20 / G1B / 1 litre / pulse 2
qp 1.5 m³/h / 190 mm thread / DN 20 / G1B / 1 litre / pulse 2
qp 2.5 m³/h / 130 mm thread / DN 20 / G1B / 1 litre / pulse 2
qp 2.5 m³/h / 190 mm thread / DN 20 / G1B / 1 litre / pulse 2
qp 3.5 m³/h / 260 mm thread / DN 25 / G1¼B / 10 litre / pulse 2
qp 6 m³/h / 260 mm thread / DN 25 / G1¼B / 10 litre / pulse 2
qp 10 m³/h / 300 mm thread / DN 40 / G2B 2
qp 0.6 m³/h / 190 mm flange DN 20 / 1 litre / pulse 1,2
qp 1.0 m³/h / 190 mm flange DN 20 / 1 litre / pulse 1,2
qp 1.5 m³/h / 190 mm flange DN 20 / 1 litre / pulse 1,2
qp 2.5 m³/h / 190 mm flange DN 20 / 1 litre / pulse 1,2
qp 3.5 m³/h / 260 mm flange DN 25 / 10 litre / pulse 1,2
qp 3.5 m³/h / 260 mm flange DN 32 / 10 litre / pulse 1,2
qp 6 m³/h / 260 mm flange DN 25 / 10 litre / pulse 1,2
qp 6 m³/h / 260 mm flange DN 32 / 10 litre / pulse 1,2
qp 10 m³/h / 300 mm flange / DN 401 / 10 litre / pulse 1,2
qp 15 m³/h / 270 mm flange / DN 501 / 10 litre / pulse 1,2
qp 25 m³/h / 300 mm flange / DN 651 / 10 litre / pulse 1,2
qp 40 m³/h / 300 mm flange / DN 801 / 100 litre / pulse 1,2
qp 60 m³/h / 360 mm flange / DN 1001 / 100 litre / pulse 1,2
3
L M - NN O
N
O
P
Q
T
U
V
W
A
B
C
D
E
F
G
H
I
J
K
L
M
K - temperature sensor mounting
Direct sensor mounting (qp 0.6 - qp 2.5) 1 (standard)
Direct sensor mounting (qp 3.5 - qp 15) 1
Pocket sensor mounting (2 free sensors) (qp 0.6 - qp 2.5) 2
Pocket sensor mounting (2 free sensors) (qp 3.5 - qp 60) (standard)
1
one temperature sensor mounted in the body
2
2 free sensors, temperature sensor drill in the body closed
J - temperature sensors (pair)
Pt 500 / ø 5.2 mm / 2 m cable, MID and 22.77/08.04 (standard)
Pt 500 / ø 5.2 mm / 3 m cable, MID and 22.77/08.04
Pt 500 / ø 5.2 mm / 5 m cable, MID and 22.77/08.04
Pt 500 / ø 5.2 mm / 10 m cable, MID and 22.77/08.04 1
Pt 500 / ø 6.0 mm / 2 m cable, MID 2
Pt 500 / ø 6.0 mm / 3 m cable, MID 2
Pt 500 / ø 6.0 mm / 5 m cable, MID 2
Pt 500 / ø 6.0 mm / 10 m cable, MID 1, 2
1
only available as an accessory
2
not available for Heating/Cooling and Cooling
I - energy units
kWh (without digit after comma)
MWh (with 1 digit after comma)
MWh (with 2 digit after comma)
MWh (with 3 digit after comma)
GJ (with 1 digit after comma)
GJ (with 2 digit after comma)
GJ (with 3 digit after comma)
Gcal (with 1 digit after comma) 1
Gcal (with 2 digit after comma) 1
Gcal (with 3 digit after comma) 1
MBtu (with 1 digit after comma) 1
MBtu (with 2 digit after comma) 1
MBtu (with 3 digit after comma) 1
1
not applicable for MID approved meters
DEN-SMT/PL
Data Sheet
SONOMETERTM2100 – Ultrasonic energy meter
Ordering continued
Modules
Communication
Function
Supply voltage
Code No.
087G6027
087G6035
087G6029
087G6032
087G6034
087G6041
087G6037
087G6039
087G6020
087G6022
087G6024
087G6025
Designation
M-Bus module
L-Bus module (use for external radio)
RS232 module
RS485 module
Analogue output module (4-20mA)
Combined module (2 pulse inputs/ 1 pulse output)
Pulse input module (2 inputs)
Pulse output module (2 outputs)
battery 3.6 V DC (A-cell)
battery 3.6 V DC (D-cell)
mains unit 230 V AC
mains unit 24 V AC
Accessories
Temperature sensors
Temperature sensors
(pair)
Pt 500 / ø 5.2 mm /
10 m cable, MID
Pt 500 / ø 6.0 mm /
10 m cable, MID
Ball valves
Adapter for mounting
temperature sensors
pair
Code No.
1
087G6048
1
087G6052
Dimension (IG)
G ½’’
G ¾’’
Set
12 pcs
12 pcs
Code No.
087G6068
087G6069
G 1’’
12 pcs
087G6070
Coupling
thread
Sensor
thread
Set
Code No.
R ½’’
M 10 x 1
32 pcs
087G6076
Tailpieces
Threaded
Software
The IZAR@SET parameterization software on
windows basis is a convenient tool for handling
the energy meter.
The IZAR@SET software is available on web site
www.hydrometer.de.
DEN-SMT/PL
VD.SH.L2.02 © Danfoss 08/2011
Dimension
(AGR x IG)
R ½” x G ¾ B
R ¾” x G 1 B
R 1” x G 1¼ B
Set
Code No.
1 pc
1 pc
1 pc
087G6071
087G6072
087G6073
R 1½” x G 2 B
1 pc
087G6074
It is used for:
- commissioning
- reading out measured values
- printing out energy meter logs
- energy meter configuration
- application analysis
- print the meter protocol
4
SONOMETERTM2100 – Ultrasonic energy meter
Data Sheet
Technical data
INFOCAL 8
Basic data
Display indication
Temperature
Ambient class
Protection class
Display
Units
Total values
Values displayed
Ambient
Storage
Temperature sensors
Sensor current
Measuring cycle
Input
Max. temp. difference
Min. temp. difference
Starting temp. difference
Absolute temp. measuring range
Battery supply
Mains supply
EN 1434 class E1 +M1
IP 54
LCD, 8-digit
MWh - kWh - GJ - Gcal - MBtu - gal - GMP - °C - °F - m³ - m³/h
99 999 999 - 9999 999.9 - 999 999.99 - 99 999.999
Power - energy - flow rate - temperature - volume
0 - 55
°C
-25 - +70
Pt 500 with 2-wire leads
Type
< 10 m
mA
Pt 500 peak < 2; rms < 0.012
Mains unit supply: 2
T
s
A-cell battery: 16; D-cell battery: 4
177
∆θmax K
3
∆θmin K
∆θ
K
0.125
θ
°C
-20...190
3.6 VDC, A cell, 11 years lifetime
3.6 VDC, D cell, 16 years lifetime
24 VAC, 230 VAC / 0.15 W
SONO 1500 CT
Flow rate
Nominal
Maximum
Minimum
Starting
Nominal
qp m3/h
qs m3/h
l/h
q i
l/h
DN mm
0.6
1.2
6
1
1.0 / 1.5
2/3
10 / 6
2.5
2.5
5
10
4
20
Diameter
15
20
15
20
Operating
Maximum
PN bar
16 / 25
25
16 / 25
25 16 / 25 25
pressure
Temperature range heating 5 ... 90 / 5 ... 105 1
battery supplied
Temperature range heating - °C
5 ... 130
external supplied
Temperature range cooling
5 ... 90 / 5 ... 105 1
Medium
circulation water (pH: 7 - 10)
Δp mbar
85
36 / 75
100
Pressure loss At qp
130
190
Overall length
mm 110 130
190
110
130
190
Volume
l/imp.
0.001...5000 (depend on qp)
Pulse value
Test
ml/imp.
5
10
20
battery supply: 3.0 V DC
Supply
Operating
UN
external supply: 3.0..5.5 V DC 2
voltage
Enviro. class
EN 1434 class C / MID class E1 + M1
Basic data
Protect. class
IP 54 (heating) / IP 68 (cooling)
1
Only in rising or falling pipes or tilted installation.
2
For medium temperatures above 90 °C, the flow sensor must be equipped with an external supply.
Pressure loss graph
5
3.5
7
35
7
25
6
12
24
7
32
16 / 25
25
25
32
16 / 25
25
5 ... 150 1
44
260
128
260
20
50
Measuring accuracy to EN 1434 Class 2 for SONO 1500 CT
VD.SH.L2.02 © Danfoss 08/2011
DEN-SMT/PL
Data Sheet
SONOMETERTM2100 – Ultrasonic energy meter
Technical data, continued
SONO 1500 / CT
Flow rate
Diameter
Operating pressure
Temperature range heating battery supplied
Temperature range heating external supplied
Temperature range cooling
Medium
Pressure loss 3
Overall length
Pulse value
Nominal
Maximum
Minimum
Starting
Nominal
Maximum
qp m3/h
qs m3/h
l/h
qi
l/h
DN mm
PN bar
10
20
40 4/100
20
40
15
30
60 4/150
40
50
25
50
250
50
65
25
40
80
160 4/400
80
80
60
120
240 4/600
120
100
5 ... 90 / 5 ... 105 1
Flow sensor
At qp
Volume
Test
Supply voltage
°C
∆p mbar
mm
l/imp.
ml/imp
UN
5 ... 150 1
95
300
100
5 ... 90 / 5 ... 105 1
circulation water (pH - value: 7 -10)
80
75
80
270
300
300
0.001...5000 (depend on qp)
150
250
250
battery supply: 3.0 V DC
external supply: 3.0..5.5 V DC 2
EN 1434 class C / MID class E1 + M1
IP 54 (heating) / IP 68 (cooling)
75
360
500
Environmental class
Protection class
1
Only in rising or falling pipes or tilted installation.
2
For medium temperatures above 90 °C, the flow sensor must be equipped with an external supply.
3
Acc. to EN 1434 6.17.
4
Only for horizontal installation.
Basic data
Temperature sensors (pair)
Direct mounted
(EN 1434)
Pt 500, 2-wire (EN 60751)
Type
Element
Pairing
Medium temperature
Medium
°C
°C
Response time t 0.5
Pressure rating PN
bar
Protection class
Pipe material
Pocket sensor
(EN 1434)
Pt 500, 2-wire (EN 60751)
10, 80, 130
0...180
0...150
District heating water
acc. to sensor pocket technical data
Typically 0.8 s / 0.4 m/s
table
acc. to sensor pocket technical data
16
table
IP 67
IP 65
W 2.4816
W 1.4303
Temperature sensor pockets
Type
Medium temperature
Medium
Brass
°C
Response time t 0.5
Pressure rating PN
Material
Adapter
bar
Stainless steel
0...180
District heating water
Typically 9 s / 0.4 m/s
Typically 13 s / 0.4 m/s
Typically 5 s / 0.4 m/s with pasta
Typically 5 s / 0.4 m/s with pasta
25
CuZn40Pb2 (Ms 58)
W 1.4571
CuZn40Pb2 (Ms 58)
Design and function
The SONOMETERTM2100 is an ultrasonic energy
meter especially designed for heating, cooling
or combined heating/cooling application in local
and district heating systems.
DEN-SMT/PL
VD.SH.L2.02 © Danfoss 08/2011
The SONOMETERTM2100 consists of:
- Ultrasonic flow sensor, type SONO 1500 CT;
- Thermal energy calculator, type INFOCAL 8;
- Pairs of temperature sensors.
6
Data Sheet
SONOMETERTM2100 – Ultrasonic energy meter
INFOCAL 8
Calculator
The calculator contains all the necessary circuits
for recording the flow rate and temperature as
well as for calculating, logging and displaying
the data. The calculator housing can be mounted
directly on the flow sensor or on the wall. At application with medium temperature above 90 °C
or at temperatures Twater < Tenvironment the calculator
has to be removed from the flow sensor.
The calculator can be conveniently read from a
single line 8-digit display with units and symbols.
A push-button provides user-friendly control of
the various display loops. All failures and faults
are recorded automatically and shown on the
LC display. To protect the reading data, all the
relevant data are saved in a non-volatile memory
(EEPROM). This memory saves the measured
values, device parameters and types of error at
regular intervals.
Temperature Sensors
Pairs of Pt 500 temperature sensors with 2-wire
or 4-wire leads are used.
Integrated Radio
Integrated Radio is an interface for communication with radio receiver.
- Frequency band: 868 or 434 MHz
- Type of radio telegram: Real Data or Open
Metering Standard (OMS)
- Transmission data updating: Online - no time
delay between value measurement and data
transmission
- Data transmission: Unidirectional
- Sending interval: 12...20 s; depending on length
of telegram (duty cycle)
Interfaces
- Optical: ZVEI interface as standard, for communication and testing, M-Bus protocol.
- M-Bus: Configurable telegram, according to
EN1434-3. Data reading and parametrization are
via two wires with polarity reversal protection.
- L-Bus: Adapter for external radio module; configurable telegram, according to EN1434-3.
Data reading and parametrization are via two
wires with polarity reversal protection. M-Bus
protocol.
- RS232: Serial interface for communication with
external devices. A special data cable is required.
M-Bus protocol.
- RS485: Serial interface for communication with
external devices. Power supply with 12V ± 5V.
M-Bus protocol.
- Pulse output: Module with 2 Open Collector
pulse outputs (potential-free), 4 Hz (pulse width
125ms), 100 Hz (pulse width ≥5ms), ratio: pulse
duration / pulse break ~ 1:1. Configurable via
IZAR@SET software. Possible pulse output values are Energy, Volume, Tariff energy 1, Tariff
energy 2, Tariff condition 1, Tariff condition 2,
Energy error and Volume error.
- Pulse input: Module with 2 pulse inputs, max.
20 Hz with minimum pulse duration of 10 msec,
input resistance 2.2 M Ohms, terminal voltage
3 V DC, cable length up to maximum 10m. The
pulse value and the unit is configurable for
energy, water, gas or electrical meter by IZAR@
SET. Data can be transferred remotely. Also two
accounting day’s are available for both inputs.
7
VD.SH.L2.02 © Danfoss 08/2011
- Combined pulse input / output: Module with 2
pulse inputs and 1 pulse output. Configurable
via IZAR@SET software.
- Analogue output: Module for 4...20 mA with 2
programmable passive outputs, programmable
value in case of error. Output values can be
power, flow rate, temperatures. Configurable
via IZAR@SET software.
Slot 1
- Analogue output module (4-20mA)
- Combined module (2 pulse inputs / 1 pulse
output)
- Pulse input module (2 inputs)
- M-Bus module
- L-Bus module (use for external radio)
- RS232 module
- RS485 module
Slot 2
- Pulse output module
- Combined module (2 pulse inputs / 1 pulse
output)
- Pulse input module (2 inputs)
- M-Bus module
- L-Bus module (use for external radio)
- RS232 module
- RS485 module
Event Memory
Events such as changes and faults are stored in a
non-volatile memory with a capacity of up to 127
entries. The following events are recorded:
- Checksum error
- Temperature measurement error
- Start and end of test mode
- Changing of the main configuration
Monthly Memory
The INFOCAL 8 has a history memory of 24
months. The following values are stored in the
EEPROM on the programmable interval (daily,
weekly, monthly):
- Date/ Time
- Cumulated energy
- Tariff energy 1
- Tariff energy 2
- Tariff definition 1
- Tariff definition 2
- Cumulated volume
- Error hour counter
- Value of max. flow
- Time max. flow
- Date max. flow
- Value of max. power
- Time max. power
- Date max. power
- Pulse input counter 1
- Pulse input counter 2
- Pulse 1 definition
- Pulse 2 definition
- Operating days
- Max. forward temperature
- Time max. forward temperature
- Date max. forward temperature
- Max. return temperature
- Time max. return temperature
- Date max. return temperature
DEN-SMT/PL
Data Sheet
SONOMETERTM2100 – Ultrasonic energy meter
Design and function,
continued
Log Memory
The large two log memory blocks are used
to store consumption values. The storage
frequency can be selected from various storage
intervals (1, 2, 3, 4, 5, 6, 10, 12, 15, 20, 30, 60
minutes or the default setting of 24 hours, Day in
the month, Day of the week, (1024 seconds), 15th
or end of month).
The data saved in the log memory can be used
for the following analyses:
- Reading the calculator on a certain day.
Example: If the day for reading is 01.10,
the calculator reading is displayed for the
period from 01.10 of the previous year to
30.09 of the current year.
- Comparison of the last consumption period
with the preceding period
Extract of possible log memory settings
Memory Storage
block
interval
area 1 1 hour
24
area 2
hours
area 1 1 hour
area 2
24
hours
Values
Error status, overload time temperature,
overload time flow rate, supply
temperature, return temperature,
date and time, energy, tariff energy 1,
tariff energy 2, tariff definition 1, tariff
definition 2, volume, error day counter
Accounting date
The calculator includes two independent
memories in which the accumulated energy at
two programmable dates is stored.
- Last Accounting Date;
- Last but one Accounting Date;
- Values stored:
- Energy;
- Volume;
- Tariff counter 1;
- Tariff counter 2;
- Pulse counter 1;
- Pulse counter 2;
- Date.
Max. Actual Values Memories
The calculator creates maximum values for
power, flow rate and temperatures based on
consumption time, which are stored in the
EEPROM. The integration intervals are adjustable
to 6, 15, 30 or 60 minutes, 24 hours (and 1024
seconds). Default setting is 60 minutes.
Date block size
example
16 byte
Number of
data records
556
Recording
period
23 days
16 byte
299
299 days
8 byte
1113
46 days
8 byte
599
599 days
Tariff Function
The calculator offers four optional tariff
memories for monitoring plant load states for
limit tariffs. Here it concerns threshold value
tariffs. Extensive tariff conditions make it
possible to adapt the calculator individually to
the required customer-specific applications.
The tariffs are separately configurable and
independent from each other. Energy or time
can be measured alternatively per tariff register
dependent on the tariff mode adjusted in each
case.
With the “time triggered tariff function” (type Z)
the switch-on time and the switch-off time are
adjustable independent from each other for each
day of the week in steps of 15 minutes.
The following limit types are possible:
(This example applies to the display at 3 digit
after volume comma)
Type
∆T
-∆T
TR
TF
P
Q
Description
LIMIT
LIMIT resolution
Temperature difference
1 ... 255 °C
1 °C
Negative temperature difference
1 ... 255 °C
1 °C
Low temperature (low)
1 ... 255 °C
1 °C
High temperature (high)
1 ... 255 °C
1 °C
Power
1 ... 255 kW
1 kW
Flow
100 ... 25 500 l/h
100 l/h
“Theoretically Supply Energy” with return
FE
temperature of 0 °C
Z
“Time triggered” counting energy
E
“External” counting energy
More detailed description concerning tariff functions on request.
Leakage Function - on request
Display Control
The readings are displayed on the calculator by a
8-digit LCD with units and symbols.
DEN-SMT/PL
VD.SH.L2.02 © Danfoss 08/2011
8
Data Sheet
SONOMETERTM2100 – Ultrasonic energy meter
Design and function,
continued
Loop Structure
The INFOCAL 8 display has six loops. Some
display windows consist of two (to maximum
seven) displays that are shown alternately at
4-second intervals. Some pictures in loops or a
complete loop can be deactivated separately.
The main loop with the current data, e.g. for
energy, volume and flow rate, is programmed as
default setting.
In the standard setting the loop no. 5 (tariff loop)
is not activated.
For quick visual guidance, the loops in the
display are numbered from 1 to 6.
Overview of Loops
DEN-SMT/PL
VD.SH.L2.02 © Danfoss 08/2011
9
SONOMETERTM2100 – Ultrasonic energy meter
Data Sheet
Informative Displays (Standard)
Loop
“1”
Main loop
Loop
Sequence
1.1
1.2
1.3
1.4
2.8
Sequence
3.1
3.2
3.3
3.4
3.5
3.6
Window 1
Accumulated energy
Volume
Flow
Power
Forward / - return
temperature
Difference temperature
Operating days
Error status
Display test
Window 1
Accounting date 1 date
Next accounting date
1 date
Previous accounting
date 1 date
,Accd 1'
Accounting date 2 date
Next accounting date
2 date
Previous accounting
date 2 date
,Accd 2'
Window 1
Current date
,SEC_Adr'
,Pri_Adr 1'
,Pri_Adr 2'
Installation position
,In0'
3.7
,Port 1'
3.8
,Port 2'
3.9
Status integrated radio
3.10
1.5
1.6
1.7
1.9
1.10
Sequence
2.1
2.2
2.3
“2”
Accounting
date loop
2.4
2.5
2.6
2.7
Loop
“3“
Info loop
Loop
Sequence
No. of error hours
,F01-001' (software
version)
Window 1
“4”
Pulse input
loop
4.1
,In1'
4.2
,In2'
3.11
Window 2
Window 3
Window 4
Window 2
Accounting date 1 energy
Window 3 [off]
Accounting date 1 volume
Window 4
,Accd 1A'
Next accounting date 1 energy
Next accounting date 1 volume
,Accd 1L'
Previous accounting date 1 volume
,Accd 1'
Accounting date 2 volume
,Accd 2A'
Next accounting date 2 volume
,Accd 2L'
Previous accounting date 2 volume
,Accd 2'
Window 3
Window 4
Window 3
Window 4
Previous accounting date 1
energy
Date of next accounting date 1
Accounting date 2 energy
Next accounting date 2 energy
Previous accounting date 2
energy
Date of next accounting date 2
Window 2
Secondary address
Primary address 1
Primary address 2
Configuration (pulse value)
No. of the mounted module at
port 1
No. of the mounted module at
port 2
(Sequence will be shown only in
meters with integrated radio)
Checksum
Window 2
Accumulated values pulse input
1
Accumulated values pulse input
2
,PPI' pulse value 1
,PPI' pulse value 2
[off] = not active
10
VD.SH.L2.02 © Danfoss 08/2011
DEN-SMT/PL
SONOMETERTM2100 – Ultrasonic energy meter
Data Sheet
Loop
“5”
Tariff loop
Sequence
Window 1
Window 2
Window 3
Window 4
Window 5
Window 6
Window 7
Window 4
[off]
Window 5
Window 6
Window 7
energy
energy
energy
volume
volume
volume
energy
volume
The tariff loop is switched off as a standard at the heat meter or meter for cooling.
Loop
Sequence
Window 1
Window 2
“6”
Monthly value
loop
6.1
6.2
6.3
...
6.24
,LOG’
,LOG’
,LOG’
date last month
date month - 1
date month - 2
,LOG’
date month - 23
Window 3
[off]
...
[off] = not active
Simple operation
A push-button mounted on the front of the
calculator is used to switch to the various
displays. The button can be pressed for a short
or long time. A short press of the button ( < 3
seconds) switches to the next display within a
loop and a long press ( > 3 seconds) switches
to the next display loop. The “Energy” window
(sequence 1.1) in the main loop is the basic
display.
DEN-SMT/PL
VD.SH.L2.02 © Danfoss 08/2011
The calculator switches automatically to power
save mode if the button is not pressed for
approx. 4 minutes and returns to the basic
display when the button is pressed again. The
loop settings can be programmed to suit the
customer’s individual requirements using the
IZAR@SET software.
11
Data Sheet
SONOMETERTM2100 – Ultrasonic energy meter
SONO 1500 CT
Power supply
The standard version contains a 3.0 VDC lithium
battery (max. 90 °C) with a lifetime of 11 years
(depends on configuration). It’s also possible to
use an external supply e.g. from a calculator.
Characteristic for ext. power supply:
- Power supply 3.0 ... 5.5 V DC;
- Power consumption < 130 mAh per year;
- Impulse current < 10 mA.
Pulse output
The flow sensor has two pulse output.
- Volume pulse output;
- Output for testing (high resolution pulse
output for test laboratories, temporary limited)
and for communication.
The output for testing is a combined impulse
output. That means the flow sensor can emit a
high resolution test impulse or the flow sensor
can communicate via the same output.
By using an adapter the flow sensor can be read
out via the IZAR@SET Software.
The electrical information for the volume pulses
of the model for heating is described as follows:
The pulse output is by default not galvanic. A
galvanic pulse output is as an option available.
The flow sensor has, by default, a 4-pin impulse
cable with a length of 2.5 m. The maximal length
is 10 m.
Specification of the pulse output:
Volume impulse
output
Power Supply
Contact load
Output frequency
Pulse description
Pulse values
Pulse duration
Battery supply
External supply
No galvanic insulation
Galvanic insulation
(standard)
3.0 V DC
battery
UCE ≤ 30 V
UCE ≤ 30 V
IC ≤ 20 mA with residual
IC ≤ 1 mA with residual
voltage of ≤ 0.5 V
voltage of ≤ 0.5 V
≤ 20 Hz
*
Open Collector
1 ml ... 5000 l
*
(depends on qp)
1 ... 250 ms ± 10% pulse
*
duration ≤ pulse pause
No galvanic insulation
3.0 – 5.5 V DC
external supply
UCE ≤ 30 V
IC ≤ 20 mA with residual
voltage of ≤ 0.5 V
≤ 150 Hz
1 ml ... 5000 l
(depends on qp)
1 ... 250 ms ± 10% pulse
duration ≤ pulse pause
Cable allocation
White core
+ volume impulse
Yellow core
test impulse / communication
Blue core
GND
Brown core
reserved
- volume impulse
+ power supply
*depends on the average flow during the lifetime of the flow sensor, on the pulse duration and on the pulse
value.
12
VD.SH.L2.02 © Danfoss 08/2011
DEN-SMT/PL
Data Sheet
Mounting
SONO 1500 CT
DEN-SMT/PL
SONOMETERTM2100 – Ultrasonic energy meter
The flow sensor is installed either in the high
temperature pipe or low temperature pipe as
indicated on the data plate. The flow sensor
has to be installed so that the direction of flow
corresponds to the direction of the arrow on the
flow sensor housing. Ensure that the flow sensor
is always filled with liquid after installation.
Calming sections before and after the flow
sensor are not necessary. The flow sensor can
be installed in both horizontal and vertical pipe
sections, but always so, that air bubbles cannot
collect in the flow sensor.
VD.SH.L2.02 © Danfoss 08/2011
Make sure the flow sensor is installed
sufficiently far away from possible sources
of electromagnetic interference (switches,
electric motors, fluorescent lamps, etc.). It is
recommended that stop valves are fitted before
and after the flow sensor to simplify dismantling.
The flow sensor should be installed in a
convenient position for service and operating
personnel.
13
SONOMETERTM2100 – Ultrasonic energy meter
Data Sheet
Dimensions
SONO 1500 CT
Nominal size
L [mm]
L1 [mm]
L2 [mm]
B [mm]
H [mm]
h [mm]
AGZ
qp = 0.6 m³/h
qp = 3.5 m³/h
qp = 2.5 m³/h
110
190
130
230
190
290
190
190
110
190
130
230
190
290
190
190
54.5
14.5
56.5
18
56.5
18
56.5
47.5
54.5
14.5
56.5
18
56.5
18
G¾B
DN 15
G1B
DN 20
G1B
DN 20
FL
DN 20
G¾B
DN 15
G1B
DN 20
R¾
0.63
105
14
95
75
2.7
R½
0.6
R¾
0.61
AGV
R½
R¾
D [mm]
d [mm]
F [mm]
K [mm]
Weight [kg]
0.6
0.61
FL - flanged connection
DEN-SMT/PL
qp = 1.0 / 1.5 m³/h
qp = 6.0 m³/h
190
290
190
190
260
380
260
260
260
260
260
380
260
260
260
260
56.5
47.5
130
230
90
65.5
56.5
18
56.5
18
56.5
47.5
61
23
61
50
61
62.5
61
23
61
50
61
62.5
G1B
DN 20
FL
DN 20
G1B
DN 20
G1B
DN 20
FL
DN 25
FL
DN 32
G1¼B
DN25
FL
DN 25
FL
DN 32
R¾
0.63
105
14
95
75
2.7
R¾
0.61
R¾
0.63
114
14
100
85
3.35
139
18
125
100
4.65
R1
1.35
114
14
100
85
3.35
139
18
125
100
4.65
VD.SH.L2.02 © Danfoss 08/2011
FL
G1¼B
DN 20 DN 25
105
14
95
75
2.7
R1
1.35
14
SONOMETERTM2100 – Ultrasonic energy meter
Data Sheet
Dimensions, continued
SONO 1500 CT
Nominal size
qp = 10 m³/h
L [mm]
300
L1 [mm]
400
L2 [mm]
B [mm]
H [mm]
66.5
h [mm]
33
AGZ
G2B DN40
AGV
R1½
D [mm]
d [mm]
F [mm]
K [mm]
Weight [kg]
2.6
FL- flanged connection
300
300
qp = 15 m³/h
qp = 25 m³/h
qp = 40 m³/h
qp = 60 m³/h
270
270
300
300
300
300
360
360
79
85
FL DN 65
184
18
170
145
9.45
86.5
92.5
FL DN80
200
19
185
160
11.1
96.5
108
FL DN100
235
22
216
190
16.9
90
65.5
66
69
FL DN 40
148
18
138
110
6.6
71.5
73.5
FL DN 50
163
18
147
125
7.45
Temperature sensors
Designation
Type
Dimension
D (mm)
L (mm)
Direct mounted
Pt 500
ø 5.2
45
ø 5.2
45
ø 6.0
50
Pocket sensor
Pt 500
Sensor pockets
Type
Sensor
dimension
Brass
(mm)
Stainless steel
ø 5.2
ø 6.0
ø 6.0
L1 (mm)
47
60
93
128
47
92
128
98
133
168
223
L (mm)
35
52
85
120
40
85
120
85
120
155
210
Length
15
VD.SH.L2.02 © Danfoss 08/2011
DEN-SMT/PL
Data Sheet
SONOMETERTM2100 – Ultrasonic energy meter
INFOCAL 8
16
VD.SH.L1.02
Produced by Danfoss A/S © 08/2011
Data sheet
INFOCAL 8
Energy calculator
Description/Application
The INFOCAL 8 is an energy calculator e.g. for
combination with SONO 1500 CT especially
designed for heating, cooling or combined
heating/cooling application in local and district
energy systems.
MID examination certificate
no.: DE-10-MI004-PTB008
The INFOCAL 8 has been approved according to
MID.
Features
- Lithium battery with lifetime typical 11 years
or 16 years optional (depending on selected
functionality and connected flow sensor)
- Temperature range: –20 to +190 °C
- Power save mode
- NOWA test capability
- connection possibility of 2- and 4-wire
temperature sensor pairs
- Remote reading via M-Bus, L-Bus, RS 232,
RS 485, Radio or optical interface
- Integrated Radio 868 MHz, Open Metering
Standard (OMS)
- Individual remote reading (Automatic Meter
Reading) with add on modules Plug&Play
- 2 communication ports (e.g. M-Bus + pulse
input)
- Improved radio performance
- Individual tariff functions
- History memory for 24 months
- Extensive diagnostic displays
- Dedicated district energy application
telegram
- Suitable for Danfoss ECL Comfort controller
and ECL 310 internet portal connection
- IZAR@SET parameterization software
on Windows basis guarantees optimum
adaptation to the user’s specific needs
DEN-SMT/PL
VDSHK202_INFOCAL_8-DS-1303-EN.indd 1
VD.SH.K2.02 © Danfoss 03/2013
1
2013-03-04 09:13:54
Data Sheet
INFOCAL 8 – Energy calculator
Description/Application,
continued
The INFOCAL 8 is able to handle 3 types of applications:
DEN-SMT/PL
VDSHK202_INFOCAL_8-DS-1303-EN.indd 2
District heating/boiler application
Combined heating/cooling application
Chilled water application
VD.SH.K2.02 © Danfoss 03/2013
2
2013-03-04 09:13:55
INFOCAL 8 – Energy calculator
Data Sheet
Ordering:
The standard codes are used for ordering.
Heating application INFOCAL 8 standard codes 1⁾:
Code no.
Norminal flow rate
range of flow sensor
Pulse value
Installation
Module
Energy unit
Temperature
sensor cable
length
087G6220
qp 0.6 - 2.5 m³/h
1 liter / pulse
low temperature
Pulse output
kWh (without digit after comma)
2m
087G6221
qp 3.5 - 25 m³/h
10 liter / pulse
low temperature
Pulse output
MWh (with 2 digit after comma)
2m
087G6222
qp 40 - 60 m³/h
100 liter / pulse
low temperature
Pulse output
MWh (with 1 digit after comma)
2m
087G1307
qp 60 – 200 m³/h
2.5 liter / pulse
low temperature
M-Bus
MWh (with 1 digit after comma)
5m
087G1308
qp 150 - 800 m³/h
10 liter / pulse
low temperature
M-Bus
MWh (with 1 digit after comma)
5m
087G1311
qp 560 -1900 m³/h
50 liter / pulse
low temperature
M-Bus
MWh (with 1 digit after comma)
5m
087G1324
qp 1475 – 7600 m³/h
100 liter / pulse
low temperature
M-Bus
MWh (with 1 digit after comma)
5m
1⁾These codes are EN version with A-cell battery. For more characteristics of each code, please contact Danfoss local sales company.
More standard codes are available regarding cooling meter, combined heating/cooling meter, high temperature installation, power
supply and modules.
3
VDSHK202_INFOCAL_8-DS-1303-EN.indd 3
VD.SH.K2.02 © Danfoss 03/2013
DEN-SMT/PL
2013-03-04 09:13:55
Data Sheet
INFOCAL 8 – Energy calculator
Ordering continued
Modules
Communication
Function
Supply voltage
Code No.
087G6027
087G6035
087G6029
087G6032
087G6034
087G6041
087G6037
087G6039
087G6020
087G6022
087G6024
087G6025
Designation
M-Bus module
L-Bus module (use for external radio)
RS232 module
RS485 module
Analogue output module (4-20 mA)
Combined module (2 pulse inputs/ 1 pulse output)
Pulse input module (2 inputs)
Pulse output module (2 outputs)
battery 3.6 V DC (A-cell)
battery 3.6 V DC (D-cell)
mains unit 230 V AC
mains unit 24 V AC
Accessories
Temperature sensors
Temperature sensors
(pair)
Pt 500 / ø 5.2 mm / 10 m
cable, MID
Ball valves
Adapter for mounting
temperature sensors
Software
The IZAR@SET parameterization software on
windows basis is a convenient tool for handling
the energy meter.
DEN-SMT/PL
VD.SH.K2.02 © Danfoss 03/2013
VDSHK202_INFOCAL_8-DS-1303-EN.indd 4
pair
Code No.
1
087G6048
Dimension (IG)
G ½’’
G ¾’’
Set
12 pcs
12 pcs
Code No.
087G6068
087G6069
G 1’’
12 pcs
087G6070
Coupling
thread
Sensor
thread
Set
Code No.
R ½’’
M 10 x 1
32 pcs
087G6076
It is used for:
-commissioning
- reading out measured values
- printing out energy meter logs
- energy meter configuration
- application analysis
- print the meter protocol
4
2013-03-04 09:13:56
INFOCAL 8 – Energy calculator
Data Sheet
Technical data
INFOCAL 8
Basic data
Display indication
Temperature
Ambient class
Protection class
Display
Units
Total values
Values displayed
Ambient
Storage
Temperature sensors
Sensor current
Input
Measuring cycle
Max. temp. difference
Min. temp. difference
Starting temp. difference
Absolute temp. measuring range
Battery supply
Mains supply
Design and function
class E1 +M1
IP 54
LCD, 8-digit
MWh - kWh - GJ - Gcal - MBtu - gal - GMP - °C - °F - m³ - m³/h
99 999 999 - 9999 999.9 - 999 999.99 - 99 999.999
Power - energy - flow rate - temperature - volume
0 - 55
°C
-25 - +70
Pt 500 with 2-wire leads
Type
< 10 m
mA
Pt 500 peak < 2; rms < 0.012
Mains unit supply: 1
Ts
A-cell battery: 16; D-cell battery: 4
∆θmaxK
177
∆θminK
3
∆θK
0.125
θ°C
-20...190
3.6 VDC, A cell, 11 years lifetime
3.6 VDC, D cell, 16 years lifetime
24 VAC, 230 VAC / 0.15 W
The INFOCAL 8 is an ultrasonic energy meter
especially designed for heating, cooling or
combined heating/cooling application in local
and district heating systems.
Calculator
The calculator contains all the necessary circuits
for recording the flow rate and temperature as
well as for calculating, logging and displaying
the data. The calculator housing can be mounted
directly on the volume measuring component
or on the wall. At application with medium
temperature above 90 °C or at temperatures Twater
< Tenvironment the calculator has to be removed from
the flowmeter.
5
VDSHK202_INFOCAL_8-DS-1303-EN.indd 5
VD.SH.K2.02 © Danfoss 03/2013
The calculator can be conveniently read from a
single line 8-digit display with units and symbols.
A push-button provides user-friendly control of
the various display loops. All failures and faults
are recorded automatically and shown on the
LC display. To protect the reading data, all the
relevant data are saved in a non-volatile memory
(EEPROM). This memory saves the measured
values, device parameters and types of error at
regular intervals.
DEN-SMT/PL
2013-03-04 09:13:56
Data Sheet
INFOCAL 8 – Energy calculator
Design and function,
continued
Temperature Sensors
Pairs of Pt 500 ø5.2 mm temperature sensors
with 2-wire or 4-wire leads are used. Cable length
2 m, 3 m, 5 m or 10 m are available.
Integrated Radio
Integrated Radio is an interface for
communication with radio receiver.
- Frequency band: 868 MHz
- Type of radio telegram: Open Metering
Standard (OMS)
- Transmission data updating: Online - no time
delay between value measurement and data
transmission
- Data transmission: Unidirectional
- Sending interval: 12...20 s; depending on length
of telegram (duty cycle)
Interfaces
- Optical: ZVEI interface as standard, for
communication and testing, M-Bus protocol.
- M-Bus: Configurable telegram, according to
EN13757-3. Data reading and parametrization are
via two wires with polarity reversal protection.
- L-Bus: Adapter for external radio module;
configurable telegram, according to EN13757-3.
Data reading and parametrization are via two
wires with polarity reversal protection. M-Bus
protocol.
- RS232: Serial interface for communication with
external devices. A special data cable is required.
M-Bus protocol.
- RS485: Serial interface for communication with
external devices. Power supply with 12V ± 5V.
M-Bus protocol.
- Pulse output: Module with 2 Open Collector
pulse outputs (potential-free), 4 Hz (pulse width
125ms), 100 Hz (pulse width ≥5ms), ratio: pulse
duration / pulse break ~ 1:1. Configurable via
IZAR@SET software. Possible pulse output values
are Energy, Volume, Tariff energy 1, Tariff energy
2, Tariff condition 1, Tariff condition 2, Energy
error and Volume error.
- Pulse input: Module with 2 pulse inputs, max.
20 Hz with minimum pulse duration of 10 msec,
input resistance 2.2 M Ohms, terminal voltage
3V DC, cable length up to maximum 10m. The
pulse value and the unit is configurable for
energy, water, gas or electrical meter by IZAR@
SET. Data can be transferred remotely. Also two
accounting day’s are available for both inputs.
- Combined pulse input / output: Module with 2
pulse inputs and 1 pulse output. Configurable via
IZAR@SET software.
- Analogue output: Module for 4...20 mA with 2
programmable passive outputs, programmable
value in case of error. Output values can be
power, flow rate, temperatures. Configurable via
IZAR@SET software.
DEN-SMT/PL
VDSHK202_INFOCAL_8-DS-1303-EN.indd 6
VD.SH.K2.02 © Danfoss 03/2013
Slot 1
-Analogue output module (4-20mA)
- Combined module (2 pulse inputs / 1 pulse output)
- Pulse input module (2 inputs)
- M-Bus module
- L-Bus module (use for external radio)
- RS232 module
- RS485 module
Slot 2
- Pulse output module
- Combined module (2 pulse inputs / 1 pulse output)
- Pulse input module (2 inputs)
- M-Bus module
- L-Bus module (use for external radio)
- RS232 module
- RS485 module
Event Memory
Events such as changes and faults are stored in a
non-volatile memory with a capacity of up to 127
entries. The following events are recorded:
- Checksum error
- Temperature measurement error
- Start and end of test mode
- Changing of the main configuration
Monthly Memory
The INFOCAL 8 has a history memory of 24
months. The following values are stored in the
EEPROM on the programmable interval (daily,
weekly, monthly):
- Date/ Time
- Cumulated energy
- Tariff energy 1
- Tariff energy 2
- Tariff definition 1
- Tariff definition 2
- Cumulated volume
- Error hour counter
- Value of max. flow
- Time max. flow
- Date max. flow
- Value of max. power
- Time max. power
- Date max. power
- Pulse input counter 1
- Pulse input counter 2
- Pulse 1 definition
- Pulse 2 definition
- Operating days
- Max. forward temperature
- Time max. forward temperature
- Date max. forward temperature
- Max. return temperature
- Time max. return temperature
- Date max. return temperature
6
2013-03-04 09:13:56
Data Sheet
INFOCAL 8 – Energy calculator
Design and function,
continued
Log Memory
The large two log memory blocks are used
to store consumption values. The storage
frequency can be selected from various storage
intervals (1, 2, 3, 4, 5, 6, 10, 12, 15, 20, 30, 60
minutes or the default setting of 24 hours, Day in
the month, Day of the week, (1024 seconds), 15th
or end of month).
The data saved in the log memory can be used
for the following analyses:
- Reading the calculator on a certain day.
Example: If the day for reading is 01.10,
the calculator reading is displayed for the
period from 01.10 of the previous year to
30.09 of the current year.
- Comparison of the last consumption period
with the preceding period
Extract of possible log memory settings
Memory Storage
block
interval
area 1 1 hour
24
area 2
hours
area 1 1 hour
area 2
24
hours
Values
Error status, overload time temperature,
overload time flow rate, supply
temperature, return temperature, date
and time, energy, tariff energy 1, tariff
energy 2, tariff definition 1, tariff definition
2, volume, error day counter
Accounting date
The calculator includes two independent
memories in which the accumulated energy at
two programmable dates is stored.
- Last Accounting Date;
- Last but one Accounting Date;
- Values stored:
- Energy;
- Volume;
- Tariff counter 1;
- Tariff counter 2;
- Pulse counter 1;
- Pulse counter 2;
- Date.
Max. Actual Values Memories
The calculator creates maximum values for
power, flow rate and temperatures based on
consumption time, which are stored in the
EEPROM. The integration intervals are adjustable
to 6, 15, 30 or 60 minutes, 24 hours (and 1024
seconds). Default setting is 60 minutes.
Date block size
example
16 byte
Number of
data records
556
Recording
period
23 days
16 byte
299
299 days
8 byte
1113
46 days
8 byte
599
599 days
Tariff Function
The calculator offers four optional tariff
memories for monitoring plant load states for
limit tariffs. Here it concerns threshold value
tariffs. Extensive tariff conditions make it possible
to adapt the calculator individually to the
required customer-specific applications.
The tariffs are separately configurable and
independent from each other. Energy or time
can be measured alternatively per tariff register
dependent on the tariff mode adjusted in each
case.
With the “time triggered tariff function” (type Z)
the switch-on time and the switch-off time are
adjustable independent from each other for each
day of the week in steps of 15 minutes.
The following limit types are possible:
(This example applies to the display at 3 digit
after volume comma)
Type
∆T
-∆T
TR
TF
P
Q
Description
LIMIT
LIMIT resolution
Temperature difference
1 ... 255 °C
1 °C
Negative temperature difference
1 ... 255 °C
1 °C
Low temperature (low)
1 ... 255 °C
1 °C
High temperature (high)
1 ... 255 °C
1 °C
Power
1 ... 255 kW
1 kW
Flow
100 ... 25 500 l/h
100 l/h
“Theoretically Supply Energy” with return
FE
temperature of 0 °C
Z
“Time triggered” counting energy
E
“External” counting energy
More detailed description concerning tariff functions on request.
Display Control
The readings are displayed on the calculator by a
8-digit LCD with units and symbols.
7
VDSHK202_INFOCAL_8-DS-1303-EN.indd 7
VD.SH.K2.02 © Danfoss 03/2013
DEN-SMT/PL
2013-03-04 09:13:56
Data Sheet
INFOCAL 8 – Energy calculator
Design and function,
continued
Loop Structure
The INFOCAL 8 display has six loops. Some
display windows consist of two (to maximum
seven) displays that are shown alternately at
4-second intervals. Some pictures in loops or a
complete loop can be deactivated separately.
The main loop with the current data, e.g. for
energy, volume and flow rate, is programmed as
default setting.
In the standard setting the loop no. 5 (tariff loop)
is not activated.
For quick visual guidance, the loops in the
display are numbered from 1 to 6.
Overview of Loops
DEN-SMT/PL
VDSHK202_INFOCAL_8-DS-1303-EN.indd 8
VD.SH.K2.02 © Danfoss 03/2013
8
2013-03-04 09:13:57
INFOCAL 8 – Energy calculator
Data Sheet
Informative Displays (Standard)
Loop
“1”
Main loop
Loop
Sequence
1.1
1.2
1.3
1.4
2.8
Sequence
3.1
3.2
3.3
3.4
3.5
3.6
Window 1
Accumulated energy
Volume
Flow
Power
Forward / - return
temperature
Difference temperature
Operating days
Error status
Display test
Window 1
Accounting date 1 date
Next accounting date
1 date
Previous accounting
date 1 date
,Accd 1'
Accounting date 2 date
Next accounting date
2 date
Previous accounting
date 2 date
,Accd 2'
Window 1
Current date
,SEC_Adr'
,Pri_Adr 1'
,Pri_Adr 2'
Installation position
,In0'
3.7
,Port 1'
3.8
,Port 2'
3.9
Status integrated radio
3.10
3.11
Sequence
No. of error hours
software version
Window 1
4.1
,In1'
4.2
,In2'
1.5
1.6
1.7
1.9
1.10
Sequence
2.1
2.2
2.3
“2”
Accounting
date loop
2.4
2.5
2.6
2.7
Loop
“3“
Info loop
Loop
“4”
Pulse input
loop
Window 2
Window 3
Window 4
Window 2
Accounting date 1 energy
Window 3 [off]
Accounting date 1 volume
Window 4
,Accd 1A'
Next accounting date 1 energy
Next accounting date 1 volume
,Accd 1L'
Previous accounting date 1 volume
,Accd 1'
Accounting date 2 volume
,Accd 2A'
Next accounting date 2 volume
,Accd 2L'
Previous accounting date 2 volume
,Accd 2'
Window 3
Window 4
Window 3
Window 4
Previous accounting date 1
energy
Date of next accounting date 1
Accounting date 2 energy
Next accounting date 2 energy
Previous accounting date 2
energy
Date of next accounting date 2
Window 2
Secondary address
Primary address 1
Primary address 2
Configuration (pulse value)
No. of the mounted module at
port 1
No. of the mounted module at
port 2
(Sequence will be shown only in
meters with integrated radio)
Checksum
Window 2
Accumulated values pulse input
1
Accumulated values pulse input
2
,PPI' pulse value 1
,PPI' pulse value 2
[off] = not active
9
VDSHK202_INFOCAL_8-DS-1303-EN.indd 9
VD.SH.K2.02 © Danfoss 03/2013
DEN-SMT/PL
2013-03-04 09:13:57
INFOCAL 8 – Energy calculator
Data Sheet
Loop
“5”
Tariff loop
Sequence
Window 1
Window 2
Window 3
Window 4
Window 5
Window 6
Window 7
Window 4
[off]
Window 5
Window 6
Window 7
energy
energy
energy
volume
volume
volume
energy
volume
The tariff loop is switched off as a standard at the heat meter or meter for cooling.
Loop
Sequence
Window 1
Window 2
“6”
Monthly value
loop
6.1
6.2
6.3
...
6.24
,LOG’
,LOG’
,LOG’
date last month
date month - 1
date month - 2
,LOG’
date month - 23
Window 3
[off]
...
[off] = not active
Simple operation
A push-button mounted on the front of the
calculator is used to switch to the various
displays. The button can be pressed for a short
or long time. A short press of the button ( < 3
seconds) switches to the next display within a
loop and a long press ( > 3 seconds) switches
to the next display loop. The “Energy” window
(sequence 1.1) in the main loop is the basic
display.
DEN-SMT/PL
VDSHK202_INFOCAL_8-DS-1303-EN.indd 10
VD.SH.K2.02 © Danfoss 03/2013
The calculator switches automatically to power
save mode if the button is not pressed for
approx. 4 minutes and returns to the basic
display when the button is pressed again. The
loop settings can be programmed to suit the
customer’s individual requirements using the
IZAR@SET software.
10
2013-03-04 09:13:57
Data Sheet
INFOCAL 8 – Energy calculator
Dimensions
INFOCAL 8
Temperature sensors
Designation
Type
Dimension
D (mm)
L (mm)
Direct mounted
Pt 500
ø 5.2
45
Pocket sensor
Pt 500
ø 5.2
45
Sensor pockets
Type
Sensor
dimension
(mm)
Brass
Stainless steel
ø 5.2
ø 5.2
L1
(mm)
47
60
93
128
98
133
168
223
L
(mm)
35
52
85
120
85
120
155
210
Length
11
VDSHK202_INFOCAL_8-DS-1303-EN.indd 11
VD.SH.K2.02 © Danfoss 03/2013
DEN-SMT/PL
2013-03-04 09:13:57
Data Sheet
INFOCAL 8 – Energy calculator
12
VD.SH.K2.02 © Danfoss 03/2013
VDSHK202_INFOCAL_8-DS-1303-EN.indd 12
Produced by Danfoss A/S © 03/2013
2013-03-04 09:14:01
Data sheet
SONO 1500 CT
Ultrasonic flow sensor
Description/Application
The SONO 1500 CT is an ultrasonic flow sensor
especially designed for heating, cooling or
combined heating/cooling application in local
and district energy systems.
The SONO 1500 CT has been approved according
to MID in class 2 and 3.
MID examination certificate
no.: DE-09-MI004-PTB011
DEN-SMT/PL
Features:
-1st approval in Europe for ultrasonic flow sensor
with dynamic range of qi/qp 1:250 in class 2 (qp
1.5 / 2.5 / 6 / 10 / 15 / 25 / 40 / 60 m³/h)
- Complete dynamic range: ≥ 1:1500
- Lithium battery with a lifetime of 11 years or
external supply
- Temperature range: 5 - 90 °C / 130 °C / 150 °C
- Overload temperature up to 150 °C (sizes qp 0.6
up to 2.5 m³/h)
- Available in nominal sizes: qp 0.6 / 1.0 / 1.5 / 2.5 /
3.5 / 6 / 10 / 15 / 25 / 40 / 60 m³/h
- Unique free-beam principle
- Swirl-free flow around reflector
- Robust stainless steel reflector
- All sizes also available in PN 25
- No calming sections necessary in the inlet and/
or outlet (standard installation)
- NOWA test capability
- Connection to calculator with pulse defined
values
- Insensitive against magnetite
- Installation in any position
- Free selectable pulse values
VD.SH.M1.02 © Danfoss 03/2013
1
Data Sheet
SONO 1500 CT - Ultrasonic flow sensor
Ordering:
The standard codes are used for ordering.
Heating application SONO 1500 CT standard codes 1⁾ :
Code no.
Flow sensor
Nominal pressure
Cable length of
flow sensor
087G1350
qp 0.6 m³/h / 110mm thread / DN 15 / G¾B / 1 liter/pulse
PN16
2.5m
087G1351
qp 1.5 m³/h / 110mm thread / DN 15 / G¾B / 1 liter/pulse
PN16
2.5m
087G1352
qp 1.5 m³/h / 130mm thread / DN 20 / G1B / 1 liter/pulse
PN16
2.5m
087G1353
qp 2.5 m³/h / 130mm thread / DN 20 / G1B / 1 liter/pulse
PN16
2.5m
087G1354
qp 3.5 m³/h / 260mm thread / DN 25 / G1¼B / 10 liter/pulse
PN16
2.5m
087G1355
qp 6 m³/h / 260mm thread / DN 25 / G1¼B / 10 liter/pulse
PN16
2.5m
087G1356
qp 10 m³/h / 300mm thread / DN 40 / G2B / 10 liter/pulse
PN16
2.5m
087G1357
qp 6 m³/h / 260mm flange DN 32 / 10 liter/pulse
PN25
2.5m
087G1358
qp 10 m³/h / 300mm flange DN 40 / 10 liter/pulse
PN25
2.5m
087G1359
qp 15 m³/h / 270mm flange DN 50 / 10 liter/pulse
PN25
5m
087G1360
qp 25 m³/h / 300mm flange DN 65 / 10 liter/pulse
PN25
5m
087G1361
qp 40 m³/h / 300mm flange DN 80 / 100 liter/pulse
PN25
5m
087G1362
qp 60 m³/h / 360mm flange DN 100 / 100 liter/pulse
PN25
5m
1⁾ These codes are EN version flow sensor with external power supply. For more characteristics of each code, please contact
Danfoss local sales company.
More standard codes are available regarding cooling application.
DEN-SMT/PL
VD.SH.M1.02 © Danfoss 03/2013
2
Data Sheet
SONO 1500 CT - Ultrasonic flow sensor
Technical data
Flow rate
Nominal
Maximum
Standard
minimum
Extended
minimum 5⁾
Starting
Nominal
Diameter
Operating
Maximum
pressure
Temperature range heating battery supplied
Temperature range heating external supplied
Temperature range cooling
Medium
Pressure loss At qp
Overall length
Volume
Pulse value
Test
Supply
Operating
voltage
Enviromental class
Protect.ion class
Ambient temperature
Flow rate
Nominal
Maximum
Standard
minimum
Extended
minimum 5⁾
Starting
Nominal
qpm3/h
qsm3/h
0.6
1.2
1.5
3
2.5
5
3.5
7
6
12
qil/h
6
15
25
35
60
qi
−
6
10
−
24
l/h
l/h
DNmm
PNbar
Pulse value
Volume
Test
Supply
Operating
voltage
Enviromental class
2.5
20
16 / 25
15
4
20
20
25
16 / 25
25
16 / 25
7
25
25
7
32
16 / 25
25
25
32
16 / 25
25
5 ... 90 / 5 ... 105 1⁾
°C
Δpmbar
mm
l/imp.
ml/imp.
5 ... 150 1⁾
5 ... 130
110
85
130
190
110
5
UN
°C
5 ... 90 / 5 ... 105 1⁾
circulation water (pH: 7 - 10)
75
100
130
190
130
190
0.001...5000 (depend on qp)
10
20
battery supply: 3.0 V DC
external supply: 3.0..5.5 V DC 2⁾
EN 1434 class C / MID class E1 + M1
IP 54 (heating) / IP 65 (cooling)
5...55
44
260
128
260
20
50
qp m3/h
qsm3/h
10
20
15
30
25
50
40
80
60
120
qil/h
100
150
250
400
600
qil/h
404⁾ / 100
604⁾ / 150
1004⁾ / 250
1604⁾ / 400
2404⁾ / 600
l/h
DNmm
20
40
40
50
50
65
80
80
120
100
Diameter
Operating
Maximum
PNbar
pressure
Temperature range heating battery supplied
Temperature range heating - °C
external supplied
Temperature range cooling
Medium
Δpmbar
Pressure loss At qp
Overall length
1
15
25
5 ... 90 / 5 ... 105 1⁾
5 ... 150 1⁾
95
80
5 ... 90 / 5 ... 105 1⁾
circulation water (pH: 7 - 10)
75
mm
300
270
300
l/imp.
ml/imp.
100
150
UN
0.001...5000 (depend on qp)
250
battery supply: 3.0 V DC
external supply: 3.0..5.5 V DC 2⁾
EN 1434 class C / MID class E1 + M1
80
75
300
360
250
500
⁾Only in rising or falling pipes or tilted installation.
⁾For medium temperatures above 90 °C, the flow sensor must be equipped with an external supply.
⁾Acc. to EN 1434 6.17.
4
⁾Only for horizontal installation.
⁵⁾ Extended minimum flow rate for dynamic range of 1:250. Available on request.
1
2
3
3
VD.SH.M1.02 © Danfoss 03/2013
DEN-SMT/PL
Data Sheet
SONO 1500 CT - Ultrasonic flow sensor
Pressure loss graph
Function
Measuring accuracy Class 2
Power supply
The standard version contains a 3.0 VDC lithium
battery (max. 90 °C) with a lifetime of 11 years
(depends on configuration). It’s also possible to
use an external supply e.g. from a calculator.
Characteristic for ext. power supply:
- Power supply 3.0 ... 5.5 V DC;
- Power consumption < 130 mAh per year;
- Impulse current < 10 mA.
Pulse output
The flow sensor has two pulse output.
- Volume pulse output;
- Output for testing (high resolution pulse
output for test laboratories, temporary limited)
and for communication.
The output for testing is a combined impulse
output. That means the flow sensor can emit a
high resolution test impulse or the flow sensor
can communicate via the same output.
By using an adapter the flow sensor can be read
out via the IZAR@SET Software.
The electrical information for the volume pulses
of the model for heating is described as follows:
The pulse output is by default not galvanic. A
galvanic pulse output is as an option available.
The flow sensor has, by default, a 4-pin impulse
cable with a length of 2.5 m. The maximal length
is 10 m.
Specification of the pulse output:
Volume impulse
output
Power Supply
Contact load
Output frequency
Pulse description
Pulse values
Pulse duration
Battery supply
External supply
No galvanic insulation
Galvanic insulation
(standard)
3.0 V DC
battery
UCE ≤ 30 V
UCE ≤ 30 V
IC ≤ 20 mA with residual
IC ≤ 1 mA with residual
voltage of ≤ 0.5 V
voltage of ≤ 0.5 V
≤ 20 Hz
*
Open Collector
1 ml ... 5000 l
*
(depends on qp)
1 ... 250 ms ± 10% pulse
*
duration ≤ pulse pause
No galvanic insulation
3.0 – 5.5 V DC
external supply
UCE ≤ 30 V
IC ≤ 20 mA with residual
voltage of ≤ 0.5 V
≤ 150 Hz
1 ml ... 5000 l
(depends on qp)
1 ... 250 ms ± 10% pulse
duration ≤ pulse pause
Cable allocation
White core
+ volume impulse
Yellow core
test impulse / communication
Blue core
GND
Brown core
reserved
- volume impulse
+ power supply
*depends on the average flow during the lifetime of the flow sensor, on the pulse duration and on the pulse
value.
DEN-SMT/PL
VD.SH.M1.02 © Danfoss 03/2013
4
Data Sheet
SONO 1500 CT - Ultrasonic flow sensor
Mounting
The flow sensor is installed either in the high
temperature pipe or low temperature pipe as
indicated on the data plate. The flow sensor
has to be installed so that the direction of flow
corresponds to the direction of the arrow on the
flow sensor housing. Ensure that the flow sensor
is always filled with liquid after installation.
Calming sections before and after the flow
sensor are not necessary. The flow sensor can
be installed in both horizontal and vertical pipe
sections, but always so, that air bubbles cannot
collect in the flow sensor.
5
VD.SH.M1.02 © Danfoss 03/2013
Make sure the flow sensor is installed
sufficiently far away from possible sources
of electromagnetic interference (switches,
electric motors, fluorescent lamps, etc.). It is
recommended that stop valves are fitted before
and after the flow sensor to simplify dismantling.
The flow sensor should be installed in a
convenient position for service and operating
personnel.
DEN-SMT/PL
Data Sheet
SONO 1500 CT - Ultrasonic flow sensor
Dimensions
Nominal size
qp = 0.6 m³/h
qp = 1.5 m³/h
L [mm]
L1 [mm]
L2 [mm]
B [mm]
H [mm]
h [mm]
110
190
130
230
190
290
190
190
110
190
130
230
190
290
190
190
54.5
14.5
56.5
18
56.5
18
56.5
47.5
54.5
14.5
56.5
18
56.5
18
AGZ
G¾B
DN 15
G1B
DN 20
G1B
DN 20
FL
DN 20
G¾B
DN 15
G1B
DN 20
R¾
0.63
105
14
95
75
2.7
R½
0.6
R¾
0.61
AGV
R½
R¾
D [mm]
d [mm]
F [mm]
K [mm]
Weight [kg]
0.6
0.61
FL - flanged connection
DEN-SMT/PL
qp = 3.5 m³/h
qp = 2.5 m³/h
qp = 6.0 m³/h
190
290
190
190
260
380
260
260
260
260
260
380
260
260
260
260
56.5
47.5
130
230
90
65.5
56.5
18
56.5
18
56.5
47.5
61
23
61
50
61
62.5
61
23
61
50
61
62.5
G1B
DN 20
FL
DN 20
G1B
DN 20
G1B
DN 20
FL
DN 25
FL
DN 32
G1¼B
DN25
FL
DN 25
FL
DN 32
R¾
0.63
105
14
95
75
2.7
R¾
0.61
R¾
0.63
114
14
100
85
3.35
139
18
125
100
4.65
R1
1.35
114
14
100
85
3.35
139
18
125
100
4.65
VD.SH.M1.02 © Danfoss 03/2013
FL
G1¼B
DN 20 DN 25
105
14
95
75
2.7
R1
1.35
6
Data Sheet
SONO 1500 CT - Ultrasonic flow sensor
Dimensions, continued
7
VD.SH.M1.02 © Danfoss 03/2013
DEN-SMT/PL
Data Sheet
8
SONO 1500 CT - Ultrasonic flow sensor
VD.SH.M1.02
Produced by Danfoss A/S © 03/2013
Data sheet
SONOMETERTM1100
Ultrasonic compact energy meter
Description/Application
The SONOMETER™1100 is an ultrasonic static
compact energy meter especially designed for
heating, cooling or combined heating/cooling
application in local and district energy systems.
MID examination certificate
no. : DE-10-MI004-PTB003
The SONOMETER™1100 as a compact energy
meter consists of the following components:
- Ultrasonic flow sensor;
- Calculator with integral hardware and software
for measuring flow rate, temperature and
energy consumption;
- Pair of temperature sensors.
Features
- 1st. approval in Europe for ultrasonic energy
meter with dynamic range of qi/qp 1 : 250 in
class 2 (qp 1.5 / 2.5 / 6 / 10 / 15 / 25 / 40 / 60 m³/h)
- Complete dynamic range: ≥ 1 : 1500
- Lithium battery, 230 V AC or 24 V AC mains
unit
- Battery lifetime 11 years (16 years optional)
- Unique free- beam principle
- Improved service-friendly energy meter
design
- Housings with thread and flange (PN 16 / 25)
- Can be configured for heating, cooling or
combined heating/cooling application
- Temperature range: 5 - 130 / 150 °C
- Overload temperature up to 150 °C
(qp= 0.6 - 2.5 m3/h)
- Swirl-free flow around reflector
- Lower pressure loss
- Robust stainless steel reflector
- Insensitive to dirt
- Available in nominal sizes
qp 0.6 / 1.0 / 1.5 / 2.5 / 3.5 / 6 / 10 / 15 / 25 / 40 /
60 m³/h
Special Features
- Power save mode
- NOWA test capability
- Remote reading via M-Bus, L-Bus, RS 232, RS
485, Radio or optical interface
- Integrated Radio 868 MHz, Open Metering
Standard (OMS)
- Individual remote reading (Automatic Meter
Reading) with add on modules Plug&Play
- 2 communication ports (e.g. M-Bus + pulse
input)
- Improved radio performance
- Individual tariff functions
- History memory for 24 months
- Extensive diagnostic displays
- Dedicated district energy application
telegram
- Suitable for Danfoss ECL Comfort controller
and ECL 310 internet portal connection
- IZAR@SET parameterization software
on Windows basis guarantees optimum
adaptation to the user’s specific needs
- Approved according to MID in class 2 and 3,
and PTB K 7.2 for cooling
- No calming sections necessary in the inlet
and/or outlet (standard installation)
DEN-SMT/PL
VD.SH.J5.02 © Danfoss 03/2013
1
SONOMETERTM1100 – Ultrasonic energy meter
Data Sheet
Ordering:
The standard codes are used for ordering.
Heat meter standard codes 1⁾:
Code no.
Flow sensor
Nominal
pressure
Cable
length 2⁾
Module
087G1040
qp 0.6 m³/h / 110mm thread / DN 15 / G¾B
PN16
1.5m
M-Bus
kWh (without digit after comma)
2m
087G1041
qp 1.5 m³/h / 110mm thread / DN 15 / G¾B
PN16
1.5m
M-Bus
kWh (without digit after comma)
2m
087G1042
qp 1.5 m³/h / 130mm thread / DN 20 / G1B
PN16
1.5m
M-Bus
kWh (without digit after comma)
2m
087G1043
qp 2.5 m³/h / 130mm thread / DN 20 / G1B
PN16
1.5m
M-Bus
kWh (without digit after comma)
2m
087G1044
qp 3.5 m³/h / 260mm thread / DN 25 / G1¼B
PN16
1.5m
M-Bus
kWh (without digit after comma)
2m
087G1045
qp 6 m³/h / 260mm thread / DN 25 / G1¼B
PN16
1.5m
M-Bus
kWh (without digit after comma)
2m
087G1046
qp 10 m³/h / 300mm thread / DN 40 / G2B
PN16
1.5m
M-Bus
MWh (with 3 digit after comma)
2m
087G1047
qp 6 m³/h / 260mm flange DN 32
PN25
1.5m
M-Bus
kWh (without digit after comma)
2m
087G1048
qp 10 m³/h / 300mm flange DN 40
PN25
1.5m
M-Bus
MWh (with 3 digit after comma)
2m
087G1049
qp 15 m³/h / 270mm flange DN 50
PN25
3m
M-Bus
MWh (with 3 digit after comma)
3m
087G1050
qp 25 m³/h / 300mm flange DN 65
PN25
3m
M-Bus
MWh (with 3 digit after comma)
3m
087G1051
qp 40 m³/h / 300mm flange DN 80
PN25
3m
M-Bus
MWh (with 2 digit after comma)
3m
087G1052
qp 60 m³/h / 360mm flange DN 100
PN25
3m
M-Bus
MWh (with 2 digit after comma)
3m
087G1118
qp 0.6 m³/h / 110mm thread / DN 15 / G¾B
PN16
1.5m
Radio OMS
kWh (without digit after comma)
2m
087G1119
qp 1.5 m³/h / 110mm thread / DN 15 / G¾B
PN16
1.5m
Radio OMS
kWh (without digit after comma)
2m
087G1120
qp 1.5 m³/h / 130mm thread / DN 20 / G1B
PN16
1.5m
Radio OMS
kWh (without digit after comma)
2m
087G1121
qp 2.5 m³/h / 130mm thread / DN 20 / G1B
PN16
1.5m
Radio OMS
kWh (without digit after comma)
2m
087G1122
qp 3.5 m³/h / 260mm thread / DN 25 / G1¼B
PN16
1.5m
Radio OMS
kWh (without digit after comma)
2m
087G1123
qp 6 m³/h / 260mm thread / DN 25 / G1¼B
PN16
1.5m
Radio OMS
kWh (without digit after comma)
2m
087G1124
qp 10 m³/h / 300mm thread / DN 40 / G2B
PN16
1.5m
Radio OMS
MWh (with 3 digit after comma)
2m
087G1125
qp 6 m³/h / 260mm flange DN 32
PN25
1.5m
Radio OMS
kWh (without digit after comma)
2m
087G1126
qp 10 m³/h / 300mm flange DN 40
PN25
1.5m
Radio OMS
MWh (with 3 digit after comma)
2m
087G1127
qp 15 m³/h / 270mm flange DN 50
PN25
3m
Radio OMS
MWh (with 3 digit after comma)
3m
087G1128
qp 25 m³/h / 300mm flange DN 65
PN25
3m
Radio OMS
MWh (with 3 digit after comma)
3m
087G1129
qp 40 m³/h / 300mm flange DN 80
PN25
3m
Radio OMS
MWh (with 2 digit after comma)
3m
087G1130
qp 60 m³/h / 360mm flange DN 100
PN25
3m
Radio OMS
MWh (with 2 digit after comma)
3m
Energy unit
Cable
length 3⁾
1⁾ These codes are EN version Heat meter with A-cell battery and ‘low temperature’ installation. For more characteristics of each code, please contact
Danfoss local sales company.
2⁾ Cable length between calculator and flow sensor.
3⁾ Cable lengh of temperature sensor.
More standard codes are available regarding cooling meter, combined heating/cooling meter, high temperature installation, power supply and
modules.
DEN-SMT/PL
VD.SH.J5.02 © Danfoss 03/2013
2
Data Sheet
SONOMETERTM1100 – Ultrasonic energy meter
Ordering continued
Modules
Communication
Function
Supply voltage
Code No.
087G6027
087G6035
087G6029
087G6032
087G6034
087G6041
087G6037
087G6039
087G6020
087G6022
087G6024
087G6025
Designation
M-Bus module
L-Bus module (use for external radio)
RS232 module
RS485 module
Analogue output module (4-20mA)
Combined module (2 pulse inputs/ 1 pulse output)
Pulse input module (2 inputs)
Pulse output module (2 outputs)
battery 3.6 V DC (A-cell)
battery 3.6 V DC (D-cell)
mains unit 230 V AC
mains unit 24 V AC
Accessories
Temperature sensors
Temperature sensors
(pair)
Pt 500 / ø 5.2 mm / 10 m
cable, MID
Ball valves
Adapter for mounting
temperature sensors
pair
Code No.
1
087G6048
Dimension (IG)
G ½’’
G ¾’’
Set
12 pcs
12 pcs
Code No.
087G6068
087G6069
G 1’’
12 pcs
087G6070
Coupling
thread
Sensor
thread
Set
Code No.
R ½’’
M 10 x 1
32 pcs
087G6076
Tailpieces
Threaded
Software
3
The IZAR@SET parameterization software on
windows basis is a convenient tool for handling
the energy meter.
VD.SH.J5.02 © Danfoss 03/2013
Dimension
(AGR x IG)
R 1/2” x G 3/4 B
R 3/4” x G 1 B
R 1” x G 11/4 B
Set
Code No.
1 pc
1 pc
1 pc
087G6071
087G6072
087G6073
R 11/2” x G 2 B
1 pc
087G6074
It is used for:
-commissioning
- reading out measured values
- printing out energy meter logs
- energy meter configuration
- application analysis
- print the meter protocol
DEN-SMT/PL
SONOMETERTM1100 – Ultrasonic energy meter
Data Sheet
Technical data
Flow rate
ranges
Diameter
Nominal
qp
m3/h
0.6
1.5
2.5
3.5
6
10
15
25
40
60
1.2
3
5
7
12
20
30
50
80
120
6
15
25
35
60
100
150
250
400
600
Maximum
qs
m3/h
Standard
minimum
qi
l/h
Extended
minimum 3⁾
qi
l/h
−
6
10
−
24
401) / 100
60 /
150
100 /
150
160
2401) /6002) / 1200
Starting
l/h
1
2.5
4
7
7
20
40
50
80
120
Nominal
DN
mm
15
50
65
80
100
Connection
AGZ
G ¾B
G 1B
FL
G ¾B
G 1B
FL
G 1B
FL
G 1¼B
FL
G 1¼B
FL
FL
FL
FL
FL
Tailpiece
AGV
R½
R¾
-
R½
R¾
-
R¾
-
R1
-
R1
-
-
-
-
-
25
16 / 25
25
16 / 25
25
16 / 25
25
25
25
25
25
Operating
Maximum
pressure
PN
bar
20
16 / 25
15
25
16 / 25
Flow sensor heating
Temp.
cooling
range
heat. /cool.
20
20
25
25
5...90
5...105
Δp
mbar
mm
85
110
130
36 / 75
190
110
130
100
190
130
190
Sensor
current
mA
Measuring
cycle
T
s
44
128
95
80
75
80
75
260
260
300
270
300
300
360
Pt 500 with 2-wire leads
Pt 500 peak < 2; rms < 0.012
Mains unit supply: 1
A-cell battery: 16; D-cell battery: 4
Max.
Δθmax
temperature
K
difference
177
Min.
Δθmin
temperature
K
difference
3
Starting
Δθ
temperature
K
difference
0.125
Absolute
temperature θ
measuring °C
range
1...180
Operating
voltage
UN
3.6 V DC (Lithium-battery) / 230 V AC / 24 V AC
class E1 + M1
calculator: IP 54
flow sensor: IP 54 (heating) / IP 68 (cooling)
Ambient storage
temperature
-25...+ 60 °C
Type
Static energy meter
Measuring process
Ultrasonic volume measurement
Display
LCD, 8-digit
Units
Display
indication Total values
MWh - kWh - GJ - Gcal - MBtu - gal - GMP - °C - °F - m³ - m³/h
99 999 999 - 9999 999.9 - 999 999.99 - 99 999.999
Values displayed
1)
-
5...105
Protection class
2)
R 1½
FL
5...150
Ambient class
Basic
features
40
G 2B
5...90
Temperature
Type
sensors
Supply
voltage
32
1)
circulation water (pH-value: 7 - 10)
At qp
Overall length
Input
25
5...130
°C
Medium
Pressure
loss
32
1)
Power - energy - flow rate - temperature - volume
Only for horizontal installation
Only in rising or falling pipes or tilted installation
3⁾ Extended minmum flow rate for dynamic range of 1:250. Available on request.
Pressure loss graph
DEN-SMT/PL
VD.SH.J5.02 © Danfoss 03/2013
Measuring accuracy Class 2
4
Data Sheet
SONOMETERTM1100 – Ultrasonic energy meter
Design and function
The SONOMETER™1100 as a compact energy meter
consists of the following components:
- Ultrasonic flow sensor;
- Calculator with integral hardware and software
for measuring flow rate, temperature and energy
consumption;
- Pair of temperature sensors.
The calculator contains all the necessary circuits for
recording the flow rate and temperature and for
calculating, logging and displaying the data. The
calculator housing can be mounted directly on the
flow sensor or on the wall. The energy meter can be
conveniently read from a single-line 8-digit display
with units and symbols. A push-button provides
user-friendly control of the various display loops.
All failures and faults are recorded automatically
and shown on the LC display. To protect the reading
data, all the relevant data are saved in a non-volatile
memory (EEPROM). This memory saves the measured
values, device parameters and types of error at regular
intervals.
Ultrasonic flow sensor
The ultrasonic technology of the flow sensor permits
very high measuring accuracy and can be used in
the supply or return line. The flow sensor meets the
requirements of MID in class 2 and 3. The standard
cable length between the calculator and the flow
sensor is 1.5 m or 3 m (optional 5 m).
Supply voltage:
- Lithium battery 3.6 V DC A-cell (11 years typical
lifetime)
- Lithium battery 3.6 V DC D-cell (16 years typical
lifetime)
- Mains unit 230 V AC or 24 V AC with changeable
backup battery
Temperature Sensors
Pairs of Pt 500 ø5.2 mm temperature sensors with
2-wire leads are used. Cable length 2 m, 3 m, 5 m or
10 m are available.
Integrated Radio
Integrated Radio is an interface for communication
with radio receiver.
- Frequency band: 868 MHz
- Type of radio telegram: Open Metering Standard
(OMS)
- Transmission data updating: Online - no time delay
between value measurement and data transmission
- Data transmission: Unidirectional
- Sending interval: 12...20 s; depending on length of
telegram (duty cycle)
Interfaces
- Optical: ZVEI interface as standard, for
communication and testing, M-Bus protocol.
- M-Bus: Configurable telegram, according to
EN13757-3. Data reading and parametrization are via
two wires with polarity reversal protection.
- L-Bus: Adapter for external radio module;
configurable telegram, according to EN13757-3. Data
reading and parametrization are via two wires with
polarity reversal protection. M-Bus protocol.
- RS232: Serial interface for communication with
external devices. A special data cable is required.
M-Bus protocol.
- RS485: Serial interface for communication with
external devices. Power supply with 12V ± 5V. M-Bus
protocol.
- Pulse output: Module with 2 Open Collector pulse
outputs (potential-free), 4 Hz (pulse width 125ms), 100
Hz (pulse width ≥5ms), ratio: pulse duration / pulse
break ~ 1:1. Configurable via IZAR@SET software.
Possible pulse output values are Energy, Volume,
Tariff energy 1, Tariff energy 2, Tariff condition 1, Tariff
condition 2, Energy error and Volume error.
5
VD.SH.J5.02 © Danfoss 03/2013
- Pulse input: Module with 2 pulse inputs, max. 20
Hz with minimum pulse duration of 10 msec, input
resistance 2.2 M Ohms, terminal voltage 3V DC, cable
length up to maximum 10m. The pulse value and the
unit is configurable for energy, water, gas or electrical
meter by IZAR@SET. Data can be transferred remotely.
Also two accounting day’s are available for both inputs.
- Combined pulse input / output: Module with 2 pulse
inputs and 1 pulse output. Configurable via IZAR@SET
software.
- Analogue output: Module for 4...20 mA with 2
programmable passive outputs, programmable value
in case of error. Output values can be power, flow rate,
temperatures. Configurable via IZAR@SET software.
Slot 1
- Analogue output module (4-20mA)
- Combined module (2 pulse inputs / 1 pulse output)
- Pulse input module (2 inputs)
- M-Bus module
- L-Bus module (use for external radio)
- RS232 module
- RS485 module
Slot 2
- Pulse output module
- Combined module (2 pulse inputs / 1 pulse output)
- Pulse input module (2 inputs)
- M-Bus module
- L-Bus module (use for external radio)
- RS232 module
- RS485 module
Event Memory
Events such as changes and faults are stored in a nonvolatile memory with a capacity of up to 127 entries.
The following events are recorded:
- Checksum error
- Temperature measurement error
- Ultrasonic operating time measurement errors
- Start and end of test mode
- Changing of the main configuration
Monthly Memory
The SONOMETER™1100 has a history memory of
24 months. The following values are stored in the
EEPROM on the programmable interval (daily, weekly,
monthly):
- Date/ Time
- Cumulated energy
- Tariff energy 1
- Tariff energy 2
- Tariff definition 1
- Tariff definition 2
- Cumulated volume
- Error hour counter
- Value of max. flow
- Time max. flow
- Date max. flow
- Value of max. power
- Time max. power
- Date max. power
- Pulse input counter 1
- Pulse input counter 2
- Pulse 1 definition
- Pulse 2 definition
- Operating days
- Max. forward temperature
- Time max. forward temperature
- Date max. forward temperature
- Max. return temperature
- Time max. return temperature
- Date max. return temperature
DEN-SMT/PL
Data Sheet
SONOMETERTM1100 – Ultrasonic energy meter
Design and function,
continued
Log Memory
The large two log memory blocks are used
to store consumption values. The storage
frequency can be selected from various storage
intervals (1, 2, 3, 4, 5, 6, 10, 12, 15, 20, 30, 60
minutes or the default setting of 24 hours, Day in
the month, Day of the week, (1024 seconds), 15th
or end of month).
The data saved in the log memory can be used
for the following analyses:
- Reading the calculator on a certain day.
Example: If the day for reading is 01.10,
the calculator reading is displayed for the
period from 01.10 of the previous year to
30.09 of the current year.
- Comparison of the last consumption period
with the preceding period
Extract of possible log memory settings
Memory Storage
Date block size
Values
block
interval
example
area 1 1 hour Error status, overload time temperature,
16 byte
24
overload
time
flow
rate,
supply
area 2
16 byte
hours temperature, return temperature, date
area 1 1 hour and time, energy, tariff energy 1, tariff
8 byte
energy 2, tariff definition 1, tariff definition
24
area 2
2, volume, error day counter
8 byte
hours
Max. Actual Values Memories
The calculator creates maximum values for
power, flow rate and temperatures based on
consumption time, which are stored in the
EEPROM. The integration intervals are adjustable
to 6, 15, 30 or 60 minutes, 24 hours (and 1024
seconds). Default setting is 60 minutes.
Tariff Function
The calculator offers four optional tariff
memories for monitoring plant load states for
limit tariffs. Extensive tariff conditions make it
possible to adapt the energy meter individually
to the required customer-specific applications.
The following limit types are possible:
(This example applies to the display with 3
decimal places)
Type
∆T
TR TF
P
Q
Z
LIMIT
LIMIT resolution
1 ... 255 °C
1 °C
1 ... 255 °C
1 °C
1 ... 255 kW
1 kW
100 ... 25 500 l/h
100 l/h
15 minutes
Number of
data records
556
Recording
period
23 days
299
299 days
1113
46 days
599
599 days
Display Control
The readings are displayed on the calculator by a
8-digit LCD with units and symbols.
Loop Structure
The SONOMETER™1100 display has six loops.
Some display windows consist of two (to
maximum seven) displays that are shown
alternately at 4-second intervals.
Some pictures in loops or a complete loop can
be deactivated separately.
For quick visual guidance, the loops in the
display are numbered from 1 to 6.
The main loop with the current data, e.g. for
energy, volume and flow rate is programmed as
default setting.
According to above table the energy or the time
(in hours) how long the tariff condition is fulfilled
will be stored in the tariff memories.
DEN-SMT/PL
VD.SH.J5.02 © Danfoss 03/2013
6
Data Sheet
SONOMETERTM1100 – Ultrasonic energy meter
Overview of Loops
7
VD.SH.J5.02 © Danfoss 03/2013
DEN-SMT/PL
SONOMETERTM1100 – Ultrasonic energy meter
Data Sheet
Informative Displays (Standard)
Loop
“1”
Main loop
Loop
Sequence
1.1
1.2
1.3
1.4
2.8
Sequence
3.1
3.2
3.3
3.4
3.5
Window 1
Accumulated energy
Volume
Flow
Power
Forward / - return
temperature
Difference temperature
Operating days
Error status
Display test
Window 1
Accounting date 1 date
Next accounting date
1 date
Previous accounting
date 1 date
,Accd 1'
Accounting date 2 date
Next accounting date
2 date
Previous accounting
date 2 date
,Accd 2'
Window 1
Current date
,SEC_Adr'
,Pri_Adr 1'
,Pri_Adr 2'
Installation position
3.6
,Port 1'
3.7
,Port 2'
3.8
Status integrated radio
3.9
3.10
Sequence
No. of error hours
software version
Window 1
4.1
,In1'
4.2
,In2'
1.5
1.6
1.7
1.9
1.10
Sequence
2.1
2.2
2.3
“2”
Accounting
date loop
2.4
2.5
2.6
2.7
Loop
“3“
Info loop
Loop
“4”
Pulse input
loop
Window 2
Window 3
Window 4
Window 2
Accounting date 1 energy
Window 3 [off]
Accounting date 1 volume
Window 4
,Accd 1A'
Next accounting date 1 energy
Next accounting date 1 volume
,Accd 1L'
Previous accounting date 1 volume
,Accd 1'
Accounting date 2 volume
,Accd 2A'
Next accounting date 2 volume
,Accd 2L'
Previous accounting date 2 volume
,Accd 2'
Window 3
Window 4
Window 3
Window 4
Previous accounting date 1
energy
Date of next accounting date 1
Accounting date 2 energy
Next accounting date 2 energy
Previous accounting date 2
energy
Date of next accounting date 2
Window 2
Secondary address
Primary address 1
Primary address 2
No. of the mounted module at
port 1
No. of the mounted module at
port 2
(Sequence will be shown only in
meters with integrated radio)
Checksum
Window 2
Accumulated values pulse input
1
Accumulated values pulse input
2
,PPI' pulse value 1
,PPI' pulse value 2
[off] = not active
DEN-SMT/PL
VD.SH.J5.02 © Danfoss 03/2013
8
SONOMETERTM1100 – Ultrasonic energy meter
Data Sheet
Loop
“5”
Tariff loop
Sequence
Window 1
Window 2
Window 3
Window 4
Window 5
Window 6
Window 7
Window 4
[off]
Window 5
Window 6
Window 7
energy
energy
energy
volume
volume
volume
energy
volume
The tariff loop is switched off as a standard at the heat meter or meter for cooling.
Loop
Sequence
Window 1
Window 2
“6”
Monthly value
loop
6.1
6.2
6.3
...
6.24
,LOG’
,LOG’
,LOG’
date last month
date month - 1
date month - 2
,LOG’
date month - 23
Window 3
[off]
...
[off] = not active
Simple operation
A push-button mounted on the front of the
calculator is used to switch to the various
displays. The button can be pressed for a short
or long time. A short press of the button ( < 3
seconds) switches to the next display within a
loop and a long press ( > 3 seconds) switches
to the next display loop. The “Energy” window
(sequence 1.1) in the main loop is the basic
display.
9
VD.SH.J5.02 © Danfoss 03/2013
The calculator switches automatically to power
save mode if the button is not pressed for
approx. 4 minutes and returns to the basic
display when the button is pressed again. The
loop settings can be programmed to suit the
customer’s individual requirements using the
IZAR@SET software.
DEN-SMT/PL
Data Sheet
SONOMETERTM1100 – Ultrasonic energy meter
Mounting
Depending on the design, the energy meter is
installed either in the low temperature or high
temperature line as indicated on the type plate.
The energy meter is to be installed so that the
direction of flow corresponds to the direction of
the arrow on the flow sensor.
Ensure that the flow sensor is always filled with
liquid on completion of installation. Straight
inlet/outlet pipes (calming sections) are not
required for the flow sensor. The energy meter
can be installed in both horizontal and vertical
pipe sections, but every time so that air bubbles
cannot collect in the flow sensor. For low flow we
recommend to mount the flow sensor tilted 90°
into the pipe.
Make sure the energy meter is installed
sufficiently far away from possible sources of
electromagnetic interference (switches, electric
motors, fluorescent lamps, etc.).
For cooling application and for medium
temperatures more than 90° C, the calculator
must be mounted on the wall at a sufficient
distance away from heat sources using the
holder supplied. It is recommended that stop
valves be fitted before and after the energy
meter to simplify dismantling the energy meter.
The energy meter should be installed in a
convenient position for service and operating
personnel.
For the further information pls. refer to the
SONOMETER™1100’s instructions.
DEN-SMT/PL
VD.SH.J5.02 © Danfoss 03/2013
10
SONOMETERTM1100 – Ultrasonic energy meter
Data Sheet
Dimensions
H
R
L2
AGZ
h
AGV
L
L1
B
DN
ØK
ØD
Ød
L1
L1
Nominal
size
qp = 0.6 m³/h
qp = 1.5 m³/h
qp = 3.5 m³/h
qp = 2.5 m³/h
qp = 6 m³/h
F
qp = 10 m³/h qp = 15 m³/h qp = 25 m³/h qp = 40 m³/h qp = 60 m³/h
L [mm]
110
130
190
190
110
130
190
190
130
190
190
260
260
260
260
260
260
300
300
270
300
300
360
L1 [mm]
190
230
290
190
190
230
290
190
230
290
190
380
260
260
380
260
260
440
300
270
300
300
360
L2 [mm]
150
150
150
B [mm]
100
100
100
R [mm]
54
54
54
H [mm]
82
84
84
84
82
84
84
84
84
84
84
88.5
88.5
88.5
88.5
88.5
88.5
94
94
99
106.5
114
119
h [mm]
14.5
18
18
47.5
14.5
18
18
47.5
18
18
47.5
23
50
62.5
23
50
62.5
33
39
73.5
85
92.5
108
G¾B
DN
15
G1B
DN
20
G1B
DN
20
FL
DN
20
G¾B
DN
15
G1B
DN
20
G1B
DN
20
FL
DN
20
FL
DN
25
FL
DN
32
G1¼B
DN
25
FL
DN
25
FL
DN
32
G2B
AGZ
FL
DN
40
FL
DN
50
FL
DN
65
FL
DN
80
FL
DN
100
AGV
R½
R¾
R¾
-
R½
R¾
R¾
-
R¾
R¾
-
R1
-
-
R1
-
-
R1½
-
-
-
-
-
-
-
-
105
-
-
-
105
-
-
105
-
114
139
-
114
139
-
148
163
184
200
235
D [mm]
G1B G1B
DN DN
20
20
FL G1¼B
DN DN
20
25
d [mm]
-
-
-
14
-
-
-
14
-
-
14
-
14
18
-
14
18
-
18
18
18
19
22
F [mm]
-
-
-
95
-
-
-
95
-
-
95
-
100
125
-
100
125
-
138
147
170
185
216
K [mm]
-
-
-
75
-
-
-
75
-
-
75
-
85
100
-
85
100
-
110
125
145
160
190
Weight
[kg]
0.76
0.85
1.5
3.5
4.8
1.5
3.5
4.8
3.1
6.4
7.0
8.9
10.9
16.4
11
0.96 2.75
0.76
0.85 0.96 2.75 0.85 0.96 2.75
VD.SH.J5.02 © Danfoss 03/2013
DEN-SMT/PL
Data Sheet
SONOMETERTM1100 – Ultrasonic energy meter
Dimensions, continued
Temperature sensors
Designation
Type
Dimension
D (mm)
L (mm)
Direct mounted
Pt 500
ø 5.2
45
Pocket sensor
Pt 500
ø 5.2
45
Sensor pockets
Type
Sensor
(mm)
dimension
Brass
Stainless steel
ø 5.2
ø 5.2
L1
(mm)
47
60
93
128
98
133
168
223
L
(mm)
35
52
85
120
85
120
155
210
Length
12
VD.SH.J5.02
Produced by Danfoss A/S © 03/2013