AAMA 507-12 THERMAL PERFORMANCE REPORT Rendered to
Transcription
AAMA 507-12 THERMAL PERFORMANCE REPORT Rendered to
Architectural Testing AAMA 507-12 THERMAL PERFORMANCE REPORT Rendered to: TORO ALUMINUM SERIES/MODEL: 4487 Series Door TYPE: Swinging Door - Single Report No: Report Date: 130 Derry Court York, PA 17406-8405 phone: 717-764-7700 fax: 717-764-4129 www.archtest.com B0651.03-116-45 04/02/14 Architectural Testing AAMA 507-12 THERMAL PERFORMANCE REPORT Rendered to: TORO ALUMINUM 330 Applewood Crescent Concord, Ontario L4K 4V2 Report No: Report Date: Simulation Date: B0651.03-116-45 04/02/14 08/09/11 Project Summary: Architectural Testing, Inc. was contracted by Toro Aluminum to provide U-Factor and Solar Heat Gain Coefficient thermal performance ratings on the 4487 Series Door Swinging Door Single. The thermal performance ratings were determined in accordance with AAMA 507-12, Standard Practice for Determining the Thermal Performance Characteristics of Fenestration Systems Installed in Commercial Building. Reference Documents: AAMA 507-12, Standard Practice for Determining the Thermal Performance Characteristics of Fenestration Systems Installed in Commercial Buildings NFRC 100-2010, Procedure for Determining Fenestration Product U-Factors NFRC 200-2010, Procedure for Determining Fenestration Product Solar Heat Gain Coefficient and Visible Transmittance at Normal Incidence Simulation Specimen Description: Series/Model: Type: Frame Material: Material Finish: Specimen Size: Configuration: Drawing Reference: 4487 Series Door Swinging Door - Single Aluminum Thermally Broken Framing System Painted Aluminum 960mm wide by 2090mm high (37-3/4" by 82-3/8") Single vision lite Toro Aluminum Drawing D305-1 & 2, dated 2/17/2011 130 Derry Court York, PA 17406-8405 phone: 717-764-7700 fax: 717-764-4129 www.archtest.com B0651.03-116-45 Page 2 of 9 Architectural Testing Toro Aluminum 4487 Series Door - Swinging Door - Single System U-Factor vs. Percentage of Vision Area 0.65 0.60 COG U-Factor 0.55 0.48 0.50 0.46 0.44 0.40 0.45 0.38 0.36 0.34 0.40 0.32 0.30 0.28 0.26 0.35 0.24 0.22 0.20 0.30 0.18 0.16 0.14 0.12 0.25 0.10 0.20 0.15 75 70 65 60 55 50 Vision Area / Total Area (%) Note: 1 inch Overall - Dual Glazed Glass (0.48-0.20 COG) with Aluminum Spacer, Dual Glazed Glass with Heat Mirror (0.18-0.10 COG) with Aluminum Spacer System U-Factor (Btu/h∙ft2∙ºF) 0.42 B0651.03-116-45 Page 3 of 9 Architectural Testing Toro Aluminum 4487 Series Door - Swinging Door - Single System SHGC vs. Percentage of Vision Area COG SHGC 0.70 0.65 0.60 0.75 0.65 0.50 0.60 0.45 0.55 0.40 0.50 0.45 0.35 0.40 0.30 0.35 0.25 0.30 0.25 0.20 0.20 0.15 0.15 System SHGC 0.55 0.70 0.10 0.10 0.05 0.05 0.00 75 70 65 60 55 50 Vision Area / Total Area (%) System VT vs. Percentage of Vision Area COG VT 0.70 0.65 0.60 0.75 0.55 0.70 0.60 0.45 0.55 0.40 0.50 0.35 0.45 0.40 0.30 0.35 0.25 0.30 0.20 0.25 0.20 0.15 0.15 0.10 0.10 0.05 0.05 0.00 75 70 65 60 Vision Area / Total Area (%) 55 50 System VT 0.50 0.65 B0651.03-116-45 Page 4 of 9 Architectural Testing Toro Aluminum 4487 Series Door - Swinging Door - Single Size Specific U-Factor Matrix* Glazing Option Center of Glass U-Factor 1 0.48 2 0.46 3 0.44 4 0.42 5 0.40 6 0.38 7 0.36 8 0.34 9 0.32 10 0.30 11 0.28 12 0.26 13 0.24 14 0.22 15 0.20 16 0.18 17 0.16 18 0.14 19 0.12 20 0.10 Overall U-Factor 0.54 0.53 0.52 0.51 0.50 0.48 0.47 0.46 0.45 0.44 0.43 0.42 0.41 0.40 0.38 0.37 0.36 0.35 0.33 0.32 Note: 1 inch Overall - Dual Glazed Glass (0.48-0.20 COG) with Aluminum Spacer, Dual Glazed Glass with Heat Mirror (0.18-0.10 COG) with Aluminum Spacer Architectural Testing B0651.03-116-45 Page 5 of 9 Toro Aluminum 4487 Series Door - Swinging Door - Single Size Specific SHGC Matrix* Center of Glass SHGC Overall SHGC 0.75 0.47 0.70 0.44 0.65 0.41 0.60 0.38 0.55 0.35 0.50 0.32 0.45 0.29 0.40 0.26 0.35 0.23 0.30 0.20 0.25 0.17 0.20 0.14 0.15 0.11 0.10 0.08 0.05 0.05 Size Specific VT Matrix* Center of Glass VT Overall VT 0.75 0.46 0.70 0.43 0.65 0.40 0.60 0.37 0.55 0.33 0.50 0.30 0.45 0.27 0.40 0.24 0.35 0.21 0.30 0.18 0.25 0.15 0.20 0.12 0.15 0.09 0.10 0.06 0.05 0.03 *Size Specific U-Factor, SHGC, and VT Matrices are based on the standard Swinging Door - Single specimen size of 960mm wide by 2090mm high (37-3/4" by 82-3/8"). This represents 60.9% Vision Area / Total Area. B0651.03-116-45 Page 6 of 9 Architectural Testing 3 0.44 4 0.42 5 0.40 6 0.38 7 0.36 8 0.34 9 0.32 10 0.30 Edge U-Factor 0.46 Frame U-Factor 2 43.7 Head L. Jamb R. Jamb Sill 44.8 Head L. Jamb R. Jamb Sill 45.8 Head L. Jamb R. Jamb Sill 46.8 Head L. Jamb R. Jamb Sill 47.9 Head L. Jamb R. Jamb Sill 48.9 Head L. Jamb R. Jamb Sill 50.0 Head L. Jamb R. Jamb Sill 51.0 Head L. Jamb R. Jamb Sill 52.0 Head L. Jamb R. Jamb Sill 53.1 Head L. Jamb R. Jamb Sill Frame Height 0.48 Cross Section COG U-Factor 1 COG Temperature Option No. Vision Area Data 5.6176 5.6180 5.6180 5.3677 5.6176 5.6180 5.6180 5.3677 5.6176 5.6180 5.6180 5.3677 5.6176 5.6180 5.6180 5.3677 5.6176 5.6180 5.6180 5.3677 5.6176 5.6180 5.6180 5.3677 5.6176 5.6180 5.6180 5.3677 5.6176 5.6180 5.6180 5.3677 5.6176 5.6180 5.6180 5.3677 5.6176 5.6180 5.6180 5.3677 0.6185 0.6066 0.6066 0.6735 0.6181 0.6062 0.6062 0.6732 0.6178 0.6058 0.6058 0.6728 0.6174 0.6055 0.6055 0.6725 0.6170 0.6051 0.6051 0.6721 0.6167 0.6047 0.6047 0.6718 0.6163 0.6043 0.6043 0.6715 0.6160 0.6012 0.6012 0.6712 0.6157 0.6009 0.6009 0.6709 0.6153 0.6005 0.6005 0.6706 0.5558 0.5560 0.5560 0.5568 0.5420 0.5421 0.5421 0.5430 0.5282 0.5283 0.5283 0.5291 0.5147 0.5149 0.5149 0.5157 0.5009 0.5012 0.5012 0.5020 0.4875 0.4878 0.4878 0.4886 0.4740 0.4743 0.4743 0.4751 0.4608 0.4600 0.4600 0.4619 0.4475 0.4466 0.4466 0.4486 0.4344 0.4335 0.4335 0.4355 50% Vision Area Total Product U-Factor NFRC 100-2010 75% Vision Area 28.60" 37.80" 61.44" by by by 62.26" 0.5598 82.28" 0.5394 133.75" 0.5091 0.5509 0.5285 0.4956 0.5420 0.5175 0.4821 0.5332 0.5066 0.4687 0.5243 0.4956 0.4552 0.5155 0.4846 0.4416 0.5066 0.4737 0.4281 0.4967 0.4619 0.4139 0.4879 0.4509 0.4003 0.4791 0.4399 0.3866 B0651.03-116-45 Page 7 of 9 Architectural Testing 13 0.24 14 0.22 15 0.20 16 0.18 17 0.16 18 0.14 19 0.12 20 0.10 Edge U-Factor 0.26 Frame U-Factor 12 54.2 Head L. Jamb R. Jamb Sill 55.2 Head L. Jamb R. Jamb Sill 56.3 Head L. Jamb R. Jamb Sill 57.3 Head L. Jamb R. Jamb Sill 58.4 Head L. Jamb R. Jamb Sill 59.5 Head L. Jamb R. Jamb Sill 60.6 Head L. Jamb R. Jamb Sill 61.7 Head L. Jamb R. Jamb Sill 62.8 Head L. Jamb R. Jamb Sill 63.9 Head L. Jamb R. Jamb Sill Frame Height 0.28 Cross Section COG U-Factor 11 COG Temperature Option No. Vision Area Data 5.6176 5.6180 5.6180 5.3677 5.6176 5.6180 5.6180 5.3677 5.6176 5.6180 5.6180 5.3677 5.6176 5.6180 5.6180 5.3677 5.6176 5.6180 5.6180 5.3677 5.6176 5.6180 5.6180 5.3677 5.6176 5.6180 5.6180 5.3677 5.6176 5.6180 5.6180 5.3677 5.6176 5.6180 5.6180 5.3677 5.6176 5.6180 5.6180 5.3677 0.6150 0.6002 0.6002 0.6702 0.6147 0.5999 0.5999 0.6700 0.6144 0.5996 0.5996 0.6697 0.6142 0.5993 0.5993 0.6695 0.6139 0.5990 0.5990 0.6692 0.6049 0.5895 0.5895 0.6604 0.6046 0.5892 0.5892 0.6601 0.6044 0.5891 0.5891 0.6600 0.6042 0.5888 0.5888 0.6597 0.6039 0.5885 0.5885 0.6595 0.4212 0.4203 0.4203 0.4223 0.4081 0.4072 0.4072 0.4093 0.3951 0.3941 0.3941 0.3963 0.3819 0.3809 0.3809 0.3830 0.3689 0.3679 0.3679 0.3701 0.3401 0.3387 0.3387 0.3419 0.3270 0.3256 0.3256 0.3288 0.3126 0.3111 0.3111 0.3143 0.2993 0.2979 0.2979 0.3011 0.2860 0.2845 0.2845 0.2878 50% Vision Area Total Product U-Factor NFRC 100-2010 75% Vision Area 28.60" 37.80" 61.44" by by by 62.26" 0.4702 82.28" 0.4289 133.75" 0.3728 0.4614 0.4179 0.3591 0.4527 0.4070 0.3454 0.4439 0.3960 0.3316 0.4351 0.3849 0.3178 0.4189 0.3681 0.3002 0.4101 0.3569 0.2861 0.4011 0.3457 0.2720 0.3922 0.3345 0.2579 0.3832 0.3233 0.2437 Architectural Testing B0651.03-116-45 Page 8 of 9 Architectural Testing will service this report for the entire test record retention period. Test records that are retained such as detailed drawings, datasheets, representative samples of test specimens, or other pertinent project documentation will be retained by Architectural Testing, Inc. for the entire test record retention period. The test record retention end date for this report is August 9, 2015. Results obtained are simulated values and were secured by using the designated test methods. This report does not constitute certification of this product nor an opinion or endorsement by this laboratory. It is the exclusive property of the client so named herein and relates only to the product simulated. This report may not be reproduced, except in full, without the written approval of Architectural Testing, Inc. For ARCHITECTURAL TESTING, INC.: SIMULATED BY: REVIEWED BY: Eric S. Leitner Simulation Technician Michael J. Thoman Director - Simulations and Thermal Testing ESL:ESL B0651.03-116-45 Attachments (pages): This report is complete only when all attachments listed are included. Appendix A: Drawings and Bills of Material (18) Architectural Testing B0651.03-116-45 Page 9 of 9 Revision Log Rev. # Date Page(s) Revision(s) .01R0 04/02/14 All Original Report Issued to Toro Aluminum Architectural Testing All drawings and Bills of Material used in simulating this product are enclosed in this Appendix. Appendix A B0651.03-116-45 Report #: Date: Verified by: B0651‐116‐45 4/2/2014 Report #: Date: Verified by: B0651‐116‐45 4/2/2014 PARTS LIST 4000 Series Swing Dr Sample #305 Toro No Drawings Material Description 01/03/2011 Vendor Vendor Part No Extrudex S-21008 Alfa Solare A9174 A 021008 B 67 C 021007 Alum Concealed Door Stop Channel Extrudex S-21007 D 021006 Alum Sash Rail Extrudex H-21006 E 021009 Alum Glass Stop 1" for Swing Door Extrudex S-21009 F 021029 Alum Head/Jamb (4487) Extrudex S-21029 G 021013 Alum Rail Extrudex S-21013 H 020998 Alum Sill Extrudex H-20998 I 74 Rigid PVC 2"x1"x1/4" Setting Block Signature 16 J 000100 Flex PVC Bulb Gasket Anplex AP151 K 020999 Alum Sill Extrudex H-20999 L 000208 Foam Backer Rod 3/8" Tremco — M 000372 Flex PVC 4000 - 25mm ISO glazing spline Prasad FH-2949 N 000205 Silicone Tremsill 600, 50 US GL/ 189L Tremco 944806 O 021012 Extrudex S-21012 P 000096 Q 010101 R 021014 Alum Ext. Head Polyamide 24mm ISO Bar Alum Jamb Polybond w/Ethelene Pile 260_270_45 GYWF Santo Prene Door Spline Alum Stile S T U V W X Y Z SAMPLE # 305 Report #: Date: Verified by: B0651‐116‐45 4/2/2014 1/1 Amesbury Prasad DHS-2980 Extrudex H-21014 Report #: Date: Verified by: B0651‐116‐45 4/2/2014 Report #: Date: Verified by: B0651‐116‐45 4/2/2014 Report #: Date: Verified by: B0651‐116‐45 4/2/2014 Report #: Date: Verified by: B0651‐116‐45 4/2/2014 Report #: Date: Verified by: B0651‐116‐45 4/2/2014 Report #: Date: Verified by: B0651‐116‐45 4/2/2014 Report #: Date: Verified by: B0651‐116‐45 4/2/2014 Report #: Date: Verified by: B0651‐116‐45 4/2/2014 Report #: Date: Verified by: B0651‐116‐45 4/2/2014 Report #: Date: Verified by: B0651‐116‐45 4/2/2014 Report #: Date: Verified by: B0651‐116‐45 4/2/2014 Report #: Date: Verified by: B0651‐116‐45 4/2/2014 Report #: Date: Verified by: B0651‐116‐45 4/2/2014 Report #: Date: Verified by: B0651‐116‐45 4/2/2014 Report #: Date: Verified by: B0651‐116‐45 4/2/2014
Similar documents
Labeller - Monarch
L) Unwinder holder arm shows to the left. R) Unwinder holder arm shows to the right.
More information