AAMA 507-12 THERMAL PERFORMANCE REPORT Rendered to

Transcription

AAMA 507-12 THERMAL PERFORMANCE REPORT Rendered to
Architectural Testing
AAMA 507-12 THERMAL PERFORMANCE REPORT
Rendered to:
TORO ALUMINUM
SERIES/MODEL: 4487 Series Door
TYPE: Swinging Door - Single
Report No:
Report Date:
130 Derry Court
York, PA 17406-8405
phone: 717-764-7700
fax: 717-764-4129
www.archtest.com
B0651.03-116-45
04/02/14
Architectural Testing
AAMA 507-12 THERMAL PERFORMANCE REPORT
Rendered to:
TORO ALUMINUM
330 Applewood Crescent
Concord, Ontario L4K 4V2
Report No:
Report Date:
Simulation Date:
B0651.03-116-45
04/02/14
08/09/11
Project Summary:
Architectural Testing, Inc. was contracted by Toro Aluminum to provide U-Factor and Solar
Heat Gain Coefficient thermal performance ratings on the 4487 Series Door Swinging Door Single. The thermal performance ratings were determined in accordance with AAMA 507-12,
Standard Practice for Determining the Thermal Performance Characteristics of Fenestration
Systems Installed in Commercial Building.
Reference Documents:
AAMA 507-12, Standard Practice for Determining the Thermal Performance
Characteristics of Fenestration Systems Installed in Commercial Buildings
NFRC 100-2010, Procedure for Determining Fenestration Product U-Factors
NFRC 200-2010, Procedure for Determining Fenestration Product Solar Heat Gain
Coefficient and Visible Transmittance at Normal Incidence
Simulation Specimen Description:
Series/Model:
Type:
Frame Material:
Material Finish:
Specimen Size:
Configuration:
Drawing Reference:
4487 Series Door
Swinging Door - Single
Aluminum Thermally Broken Framing System
Painted Aluminum
960mm wide by 2090mm high (37-3/4" by 82-3/8")
Single vision lite
Toro Aluminum Drawing D305-1 & 2, dated 2/17/2011
130 Derry Court
York, PA 17406-8405
phone: 717-764-7700
fax: 717-764-4129
www.archtest.com
B0651.03-116-45
Page 2 of 9
Architectural Testing
Toro Aluminum
4487 Series Door - Swinging Door - Single
System U-Factor vs. Percentage of Vision Area
0.65
0.60
COG
U-Factor
0.55
0.48
0.50
0.46
0.44
0.40
0.45
0.38
0.36
0.34
0.40
0.32
0.30
0.28
0.26
0.35
0.24
0.22
0.20
0.30
0.18
0.16
0.14
0.12
0.25
0.10
0.20
0.15
75
70
65
60
55
50
Vision Area / Total Area (%)
Note: 1 inch Overall - Dual Glazed Glass (0.48-0.20 COG) with Aluminum Spacer, Dual Glazed Glass with Heat Mirror (0.18-0.10 COG)
with Aluminum Spacer
System U-Factor (Btu/h∙ft2∙ºF)
0.42
B0651.03-116-45
Page 3 of 9
Architectural Testing
Toro Aluminum
4487 Series Door - Swinging Door - Single
System SHGC vs. Percentage of Vision Area
COG SHGC
0.70
0.65
0.60
0.75
0.65
0.50
0.60
0.45
0.55
0.40
0.50
0.45
0.35
0.40
0.30
0.35
0.25
0.30
0.25
0.20
0.20
0.15
0.15
System SHGC
0.55
0.70
0.10
0.10
0.05
0.05
0.00
75
70
65
60
55
50
Vision Area / Total Area (%)
System VT vs. Percentage of Vision Area
COG VT
0.70
0.65
0.60
0.75
0.55
0.70
0.60
0.45
0.55
0.40
0.50
0.35
0.45
0.40
0.30
0.35
0.25
0.30
0.20
0.25
0.20
0.15
0.15
0.10
0.10
0.05
0.05
0.00
75
70
65
60
Vision Area / Total Area (%)
55
50
System VT
0.50
0.65
B0651.03-116-45
Page 4 of 9
Architectural Testing
Toro Aluminum
4487 Series Door - Swinging Door - Single
Size Specific U-Factor Matrix*
Glazing Option
Center of Glass U-Factor
1
0.48
2
0.46
3
0.44
4
0.42
5
0.40
6
0.38
7
0.36
8
0.34
9
0.32
10
0.30
11
0.28
12
0.26
13
0.24
14
0.22
15
0.20
16
0.18
17
0.16
18
0.14
19
0.12
20
0.10
Overall U-Factor
0.54
0.53
0.52
0.51
0.50
0.48
0.47
0.46
0.45
0.44
0.43
0.42
0.41
0.40
0.38
0.37
0.36
0.35
0.33
0.32
Note: 1 inch Overall - Dual Glazed Glass (0.48-0.20 COG) with Aluminum Spacer, Dual Glazed Glass with Heat Mirror (0.18-0.10 COG)
with Aluminum Spacer
Architectural Testing
B0651.03-116-45
Page 5 of 9
Toro Aluminum
4487 Series Door - Swinging Door - Single
Size Specific SHGC Matrix*
Center of Glass SHGC Overall SHGC
0.75
0.47
0.70
0.44
0.65
0.41
0.60
0.38
0.55
0.35
0.50
0.32
0.45
0.29
0.40
0.26
0.35
0.23
0.30
0.20
0.25
0.17
0.20
0.14
0.15
0.11
0.10
0.08
0.05
0.05
Size Specific VT Matrix*
Center of Glass VT Overall VT
0.75
0.46
0.70
0.43
0.65
0.40
0.60
0.37
0.55
0.33
0.50
0.30
0.45
0.27
0.40
0.24
0.35
0.21
0.30
0.18
0.25
0.15
0.20
0.12
0.15
0.09
0.10
0.06
0.05
0.03
*Size Specific U-Factor, SHGC, and VT Matrices are based on the standard Swinging
Door - Single specimen size of 960mm wide by 2090mm high (37-3/4" by 82-3/8").
This represents 60.9% Vision Area / Total Area.
B0651.03-116-45
Page 6 of 9
Architectural Testing
3
0.44
4
0.42
5
0.40
6
0.38
7
0.36
8
0.34
9
0.32
10
0.30
Edge U-Factor
0.46
Frame U-Factor
2
43.7 Head
L. Jamb
R. Jamb
Sill
44.8 Head
L. Jamb
R. Jamb
Sill
45.8 Head
L. Jamb
R. Jamb
Sill
46.8 Head
L. Jamb
R. Jamb
Sill
47.9 Head
L. Jamb
R. Jamb
Sill
48.9 Head
L. Jamb
R. Jamb
Sill
50.0 Head
L. Jamb
R. Jamb
Sill
51.0 Head
L. Jamb
R. Jamb
Sill
52.0 Head
L. Jamb
R. Jamb
Sill
53.1 Head
L. Jamb
R. Jamb
Sill
Frame Height
0.48
Cross Section
COG U-Factor
1
COG Temperature
Option No.
Vision Area Data
5.6176
5.6180
5.6180
5.3677
5.6176
5.6180
5.6180
5.3677
5.6176
5.6180
5.6180
5.3677
5.6176
5.6180
5.6180
5.3677
5.6176
5.6180
5.6180
5.3677
5.6176
5.6180
5.6180
5.3677
5.6176
5.6180
5.6180
5.3677
5.6176
5.6180
5.6180
5.3677
5.6176
5.6180
5.6180
5.3677
5.6176
5.6180
5.6180
5.3677
0.6185
0.6066
0.6066
0.6735
0.6181
0.6062
0.6062
0.6732
0.6178
0.6058
0.6058
0.6728
0.6174
0.6055
0.6055
0.6725
0.6170
0.6051
0.6051
0.6721
0.6167
0.6047
0.6047
0.6718
0.6163
0.6043
0.6043
0.6715
0.6160
0.6012
0.6012
0.6712
0.6157
0.6009
0.6009
0.6709
0.6153
0.6005
0.6005
0.6706
0.5558
0.5560
0.5560
0.5568
0.5420
0.5421
0.5421
0.5430
0.5282
0.5283
0.5283
0.5291
0.5147
0.5149
0.5149
0.5157
0.5009
0.5012
0.5012
0.5020
0.4875
0.4878
0.4878
0.4886
0.4740
0.4743
0.4743
0.4751
0.4608
0.4600
0.4600
0.4619
0.4475
0.4466
0.4466
0.4486
0.4344
0.4335
0.4335
0.4355
50%
Vision Area
Total Product U-Factor
NFRC
100-2010
75%
Vision Area
28.60"
37.80"
61.44"
by
by
by
62.26"
0.5598
82.28"
0.5394
133.75"
0.5091
0.5509
0.5285
0.4956
0.5420
0.5175
0.4821
0.5332
0.5066
0.4687
0.5243
0.4956
0.4552
0.5155
0.4846
0.4416
0.5066
0.4737
0.4281
0.4967
0.4619
0.4139
0.4879
0.4509
0.4003
0.4791
0.4399
0.3866
B0651.03-116-45
Page 7 of 9
Architectural Testing
13
0.24
14
0.22
15
0.20
16
0.18
17
0.16
18
0.14
19
0.12
20
0.10
Edge U-Factor
0.26
Frame U-Factor
12
54.2 Head
L. Jamb
R. Jamb
Sill
55.2 Head
L. Jamb
R. Jamb
Sill
56.3 Head
L. Jamb
R. Jamb
Sill
57.3 Head
L. Jamb
R. Jamb
Sill
58.4 Head
L. Jamb
R. Jamb
Sill
59.5 Head
L. Jamb
R. Jamb
Sill
60.6 Head
L. Jamb
R. Jamb
Sill
61.7 Head
L. Jamb
R. Jamb
Sill
62.8 Head
L. Jamb
R. Jamb
Sill
63.9 Head
L. Jamb
R. Jamb
Sill
Frame Height
0.28
Cross Section
COG U-Factor
11
COG Temperature
Option No.
Vision Area Data
5.6176
5.6180
5.6180
5.3677
5.6176
5.6180
5.6180
5.3677
5.6176
5.6180
5.6180
5.3677
5.6176
5.6180
5.6180
5.3677
5.6176
5.6180
5.6180
5.3677
5.6176
5.6180
5.6180
5.3677
5.6176
5.6180
5.6180
5.3677
5.6176
5.6180
5.6180
5.3677
5.6176
5.6180
5.6180
5.3677
5.6176
5.6180
5.6180
5.3677
0.6150
0.6002
0.6002
0.6702
0.6147
0.5999
0.5999
0.6700
0.6144
0.5996
0.5996
0.6697
0.6142
0.5993
0.5993
0.6695
0.6139
0.5990
0.5990
0.6692
0.6049
0.5895
0.5895
0.6604
0.6046
0.5892
0.5892
0.6601
0.6044
0.5891
0.5891
0.6600
0.6042
0.5888
0.5888
0.6597
0.6039
0.5885
0.5885
0.6595
0.4212
0.4203
0.4203
0.4223
0.4081
0.4072
0.4072
0.4093
0.3951
0.3941
0.3941
0.3963
0.3819
0.3809
0.3809
0.3830
0.3689
0.3679
0.3679
0.3701
0.3401
0.3387
0.3387
0.3419
0.3270
0.3256
0.3256
0.3288
0.3126
0.3111
0.3111
0.3143
0.2993
0.2979
0.2979
0.3011
0.2860
0.2845
0.2845
0.2878
50%
Vision Area
Total Product U-Factor
NFRC
100-2010
75%
Vision Area
28.60"
37.80"
61.44"
by
by
by
62.26"
0.4702
82.28"
0.4289
133.75"
0.3728
0.4614
0.4179
0.3591
0.4527
0.4070
0.3454
0.4439
0.3960
0.3316
0.4351
0.3849
0.3178
0.4189
0.3681
0.3002
0.4101
0.3569
0.2861
0.4011
0.3457
0.2720
0.3922
0.3345
0.2579
0.3832
0.3233
0.2437
Architectural Testing
B0651.03-116-45
Page 8 of 9
Architectural Testing will service this report for the entire test record retention period. Test
records that are retained such as detailed drawings, datasheets, representative samples of test
specimens, or other pertinent project documentation will be retained by Architectural Testing,
Inc. for the entire test record retention period. The test record retention end date for this report
is August 9, 2015.
Results obtained are simulated values and were secured by using the designated test methods.
This report does not constitute certification of this product nor an opinion or endorsement by
this laboratory. It is the exclusive property of the client so named herein and relates only to the
product simulated. This report may not be reproduced, except in full, without the written
approval of Architectural Testing, Inc.
For ARCHITECTURAL TESTING, INC.:
SIMULATED BY:
REVIEWED BY:
Eric S. Leitner
Simulation Technician
Michael J. Thoman
Director - Simulations and Thermal Testing
ESL:ESL
B0651.03-116-45
Attachments (pages): This report is complete only when all attachments listed are included.
Appendix A: Drawings and Bills of Material (18)
Architectural Testing
B0651.03-116-45
Page 9 of 9
Revision Log
Rev. #
Date
Page(s)
Revision(s)
.01R0
04/02/14
All
Original Report Issued to Toro Aluminum
Architectural Testing
All drawings and Bills of Material used in simulating this product are enclosed in this Appendix.
Appendix A
B0651.03-116-45
Report #:
Date:
Verified by:
B0651‐116‐45
4/2/2014
Report #:
Date:
Verified by:
B0651‐116‐45
4/2/2014
PARTS LIST
4000 Series Swing Dr
Sample #305
Toro No
Drawings
Material
Description
01/03/2011
Vendor
Vendor Part No
Extrudex
S-21008
Alfa Solare
A9174
A
021008
B
67
C
021007
Alum
Concealed Door Stop Channel
Extrudex
S-21007
D
021006
Alum
Sash Rail
Extrudex
H-21006
E
021009
Alum
Glass Stop 1" for Swing Door
Extrudex
S-21009
F
021029
Alum
Head/Jamb (4487)
Extrudex
S-21029
G
021013
Alum
Rail
Extrudex
S-21013
H
020998
Alum
Sill
Extrudex
H-20998
I
74
Rigid PVC
2"x1"x1/4" Setting Block
Signature
16
J
000100
Flex PVC
Bulb Gasket
Anplex
AP151
K
020999
Alum
Sill
Extrudex
H-20999
L
000208
Foam
Backer Rod 3/8"
Tremco
—
M
000372
Flex PVC
4000 - 25mm ISO glazing spline
Prasad
FH-2949
N
000205
Silicone
Tremsill 600, 50 US GL/ 189L
Tremco
944806
O
021012
Extrudex
S-21012
P
000096
Q
010101
R
021014
Alum
Ext. Head
Polyamide 24mm ISO Bar
Alum
Jamb
Polybond
w/Ethelene Pile 260_270_45 GYWF
Santo Prene Door Spline
Alum
Stile
S
T
U
V
W
X
Y
Z
SAMPLE # 305
Report #:
Date:
Verified by:
B0651‐116‐45
4/2/2014
1/1
Amesbury
Prasad
DHS-2980
Extrudex
H-21014
Report #:
Date:
Verified by:
B0651‐116‐45
4/2/2014
Report #:
Date:
Verified by:
B0651‐116‐45
4/2/2014
Report #:
Date:
Verified by:
B0651‐116‐45
4/2/2014
Report #:
Date:
Verified by:
B0651‐116‐45
4/2/2014
Report #:
Date:
Verified by:
B0651‐116‐45
4/2/2014
Report #:
Date:
Verified by:
B0651‐116‐45
4/2/2014
Report #:
Date:
Verified by:
B0651‐116‐45
4/2/2014
Report #:
Date:
Verified by:
B0651‐116‐45
4/2/2014
Report #:
Date:
Verified by:
B0651‐116‐45
4/2/2014
Report #:
Date:
Verified by:
B0651‐116‐45
4/2/2014
Report #:
Date:
Verified by:
B0651‐116‐45
4/2/2014
Report #:
Date:
Verified by:
B0651‐116‐45
4/2/2014
Report #:
Date:
Verified by:
B0651‐116‐45
4/2/2014
Report #:
Date:
Verified by:
B0651‐116‐45
4/2/2014
Report #:
Date:
Verified by:
B0651‐116‐45
4/2/2014