shock arrestor schedule plumbing general notes plumbing fixture

Transcription

shock arrestor schedule plumbing general notes plumbing fixture
PLUMBING GENERAL NOTES
I. GENERAL REQUIREMENTS:
1.
2.
3.
4.
5.
PLUMBING CONTRACTOR IS TO FURNISH AND PAY FOR ALL LABOR, MATERIAL,
EQUIPMENT, PERMITS & FEES REQUIRED FOR THE COMPLETE INSTALLATION OF ALL
SYSTEMS IN THIS SECTION OF WORK.
1.
ALL WORK IS TO BE PERFORMED IN ACCORDANCE WITH NC PLUMBING CODE
AND ALL OTHER APPLICABLE CODES. PC IS TO COORDINATE W/ G.C. IN
REGARDS TO PROJECT TIMELINE, WORK HOURS, AS WELL AS ANY BONDING OR
INSURANCE REQUIREMENTS.
2.
ALL PLUMBING FIXTURES AND PLUMBING SYSTEM EQUIPMENT SHALL BE PROVIDED
COMPLETE WITH ALL ACCESSORIES, HANGERS, VALVES, STOPS, TAILPIECES, TRAPS,
FAUCETS, STRAINERS, ETC REGARDLESS OF PRESENCE ON PLANS. SEE FIXTURE
SCHEDULE.
3.
ALL EQUIPMENT, MATERIALS AND INSTALLATION SHALL BE GUARANTEED TO BE
FREE OF DEFECTS FOR A PERIOD OF ONE (1) YEAR AFTER FINAL ACCEPTANCE OF
WORK OR IN ACCORDANCE WITH THE MANUFACTURER'S STANDARD
GUARANTEE, IF LONGER. EXISTING EQUIPMENT IS EXCLUDED FROM WARRANTY
REQUIREMENT.
THESE DRAWINGS ARE DIAGRAMMATIC AND SHOW GENERAL LOCATION AND
ARRANGEMENT OF ALL MATERIALS AND EQUIPMENT. THE DRAWINGS SHALL BE
FOLLOWED AS CLOSELY AS BUILDING CONSTRUCTION AND ALL OTHER WORK
WILL PERMIT.
6.
DO NO SCALE DRAWINGS FOR MEASUREMENT.
7.
INFORMATION GIVEN IN SCHEDULES INCLUDES BOTH DESCRIPTION OF PRODUCT
AND MANUFACTURER'S MODEL #. IF CONFLICT IS PRESENT BETWEEN DESCRIPTION
AND MODEL #, EQUIPMENT DESCRIPTION SHALL TAKE PRECEDENT. IN CASE OF
CONFLICT BETWEEN THE PLANS AND NOTES/SPECIFICATIONS OR CONFLICT
BETWEEN INFORMATION PRESENTED ON THE PLANS OR IN THE
NOTES/SPECIFICATIONS, THEN THE MOST RESTRICTIVE SHALL TAKE PRECEDENT.
8.
9.
10.
11.
IV. COORDINATION:
BEFORE BID PC IS RESPONSIBLE FOR CLARIFYING W/ G.C. ANY CONFUSION IN
REGARDS TO RESPONSIBILITY OF WORK TO BE PERFORMED OR MATERIALS TO BE
PROVIDED. THE SUBMITTAL OF THE BID BY THE CONTRACTOR WILL BE HELD AS
PROOF THAT THE CONTRACTOR UNDERSTANDS THOROUGHLY AND COMPLETELY
THE SCOPE OF THE WORK INVOLVED, AND HAS INCLUDED ON THE BID ALL THE
NECESSARY ITEMS TO CARRY OUT THIS SECTION OF WORK.
ALL EXISTING EQUIPMENT AND SYSTEMS ARE ASSUMED BY ENGINEER TO BE IN
GOOD WORKING ORDER. BEFORE BEGINNING WORK P.C. IS TO ENSURE ANY
EQUIPMENT & SYSTEMS TO REMAIN ARE PROPERLY FUNCTIONING. NOTIFY G.C.
IMMEDIATELY IF PROBLEMS ARE DISCOVERED.
ALL QUESTIONS MUST BE SUBMITTED IN RFI FORMAT TO THE ARCHITECT AND MUST
BE ADDRESSED BY THE APPROPRIATE DESIGNER OF RECORD PROIR TO BECOMING
A PROPOSED CHANGE ORDER.
P.C. IS TO REVIEW COMPLETE DRAWING SET. P.C. IS RESPONSIBLE FOR WORK
EXPLICITLY SHOWN AND WORK IMPLIED. UNLESS OTHERWISE NOTED FINAL
PLUMBING CONNECTION TO ALL EQUIPMENT, FIXTURES, ETC IS THE RESPONSIBILITY
OF THE P.C..
2.
3.
4.
5.
6.
ALL ROOF PENETRATIONS, FLASHING, ETC ARE TO BE PERFORMED BY ROOFING
CONTRACTOR.
ALL LOW VOLTAGE WIRING RELATED TO PLUMBING EQUIPMENT AND SYSTEMS IS
THE RESPONSIBILITY OF THE PLUMBING CONTRACTOR. ALL HIGH VOLTAGE
CONNECTIONS TO PLUMBING EQUIPMENT, INCLUDING DISCONNECTS TO BE
PROVIDED AND INSTALLED BY E.C.
G.C. TO BE RESPONSIBLE FOR PROVIDING AND INSTALLING ANY ACCESS DOORS
RELATED TO PLUMBING SYSTEM (W/ EXCEPTION OF CLEANOUT COVERS, BY P.C.).
P.C. RESPONSIBLE FOR COMMUNICATING TO G.C. SIZE AND LOCATION OF REQ'D
ACCESS DOOR(S).
ALL GAS PIPING IS BY PLUMBING CONTRACTOR.
8.
WATER HEATER VENT BY MECHANICAL CONTRACTOR.
III. MATERIALS:
1.
ALL MATERIALS SHALL BE NEW UNLESS OTHERWISE SHOWN OR SPECIFIED.
2.
ALL MATERIALS INSTALLED IN RETURN PLENUM ARE TO BE PLENUM RATED.
3.
4.
PIPING MATERIALS AND FITTINGS SHALL BE AS FOLLOWS:
WASTE & VENT (ABOVE & BELOW SLAB):
PVC PIPE, PVC SOCKET FITTINGS, AND SOLVENT-CEMENTED
FITTINGS.
DOMESTIC WATER (BELOW SLAB):
TYPE 'K' COPPER.
DOMESTIC WATER (ABOVE SLAB):
TYPE 'L' COPPER WITH SWEATED SOCKET FITTINGS. THREADED
FITTINGS MAY BE USED AT VALVES, FIXTURES & SIMILAR.
OR
CPVC PIPING WITH SOLVENT-CEMENTED FITTINGS. THREADED
FITTINGS MAY BE USED AT VALVES, FIXTURES & SIMILAR
OR
PEX PIPING WITH FLARED OR MECHANICAL JOINTS/FITTINGS.
GAS PIPING (ABOVE SLAB):
SCHEDULE 40 BLACK STEEL PIPE W/ THREADED FITTINGS.
APPROVED FLEXIBLE GAS PIPING MAY BE USED AT
CONNECTION TO EQUIPMENT.
INSULATION IS REQUIRED ON THE FIRST 8 FEET OF HOT WATER PIPING FROM WATER
HEATERS ON NON-CIRCULATING SYSTEMS. INSULATION IS REQUIRED ON ALL HOT
WATER PIPING THAT IS PART OF A HOT WATER CIRCULATION LOOP & THE FIRST 8
FEET OF BRANCH LINES FROM CIRCULATION LOOP. INSULATION TO BE EQUAL TO
"ARMAFLEX" PIPE INSULATION W/ SEALED OR TAPED SEAMS. INSULATION TO BE
MIN. 12" THICK FOR NON CIRCULATING SYSTEMS AND MIN. 1" THICK FOR
CIRCULATING SYSTEMS. INSULATION TO HAVE A CONDUCTIVITY NOT EXCEEDING
WHICHEVER IS MORE STRINGENT.
5.
6.
PROVIDE HANGERS & SUPPORTS APPROVED FOR USE BY 2012 NC PLUMBING
CODE.
ANY PLUMBING FIXTURES WITH A COMMON SHUT-OFF VALVE (I.E. PRE-RINSE,
KITCHEN SINK, MOP SINK) ARE TO INCLUDE A CHECK VALVE ON THE HOT & COLD
WATER VALVES TO PREVENT INTERCONNECTION OF HOT & COLD WATER LINES.
MANUFACTURER
MODEL NO.
MATERIAL
STYLE
MANUFACT.
MODEL NO.
SPOUT
DRAIN
HANDLES CENTERS
TYPE
SIZE
-
P-1
WATER
CLOSET
FLUSH
TANK
AMERICAN
STANDARD
2835.128
VITREOUS
CHINA
ADA
ELONGATED
-
-
-
-
-
P-2
LAVATORY
WALL
MOUNT
AMERICAN
STANDARD
0355.012
VITREOUS
CHINA
ADA
D-SHAPE
AMER. STD.
6055.202
(W/ MIX VALVE)
CENTER
AUTO
4"
3-HOLE
P-3
MOP SINK
FLOOR
MOUNT
FIAT
MSB-3624
MOLDED
STONE
ONE-PIECE
36x24
CENTER
2
(W/ CHECK VALVES)
FIAT
830-AA
SUPPLIES
AND STOPS
PIPE SIZES
MOUNTING
WASTE VENT CW
WATTS
Q894AC12
FLOOR
GRID
WATTS
Q894AB20
WALL
8"
2-HOLE
DOME
-
FLOOR
ZURN
FD-2211-ST
PVC
ADJUSTABLE
-
-
-
-
-
-
-
SEE
PLAN
FLOOR
FS
FLOOR
SINK
6" DEEP
ZURN
FD-2375
CAST-IRON,
PORCELAIN
ENAMEL
ANTI-SPLASH
-
-
-
-
-
-
-
SEE
PLAN
FLOOR
HB
HOSE
BIB
ANGLE
ZURN
Z1341-BFP
BRONZE
-
-
-
-
-
-
-
-
HD
HUB
DRAIN
FUNNEL
ZURN
Z326
CAST-IRON
THREADED
-
-
-
-
-
-
-
RP-1
RECIRC.
PUMP
MAGNETIC
DRIVE
WILO
STAR-Z
ECO BRASS
MAINT.
FREE
-
-
-
-
-
-
-
TD-1
TRENCH
DRAIN
FLOOR
MOUNT
ADVANCE
TABCO
FRG-24
STAINLESS
STEEL
FLOOR
TROUGH
DRAIN
-
-
-
-
GRATE
3"
-
P.C. RESPONSIBLE FOR EXECUTING ALL CODE REQUIRED TESTS AND INSPECTIONS,
INCLUDING BUT NOT LIMITED TO, LEAK & PRESSURE TESTING OF GAS, WASTE, VENT
& WATER PIPING AND SANITIZING OF WATER PIPING.
WCO
WALL
CLEANOUT
TEE
CHARLOTTE
PIPE
PVC-445
PVC
FLUSH
PLUG
-
-
-
-
-
-
-
3.
ENSURE PIPING LOCATED ON EXTERIOR WALLS (OR OTHER WALLS EXPOSED TO
FREEZING CONDITIONS) IS INSTALLED ON WARM-SIDE OF WALL INSULATION.
WH-1
WATER
HEATER
DIR. VENT
GAS
STATE
WATER HEATERS
SBD100 199NE
GLASS
LINED
UPRIGHT
-
-
-
-
-
-
-
4.
ANY NOTCHING, DRILLING, BORING OR OTHER ALTERATION TO BUILDING
STRUCTURE SHALL BE PERFORMED IN A CODE APPROVED METHOD AND NOT
THREATEN THE INTEGRITY OF THE BUILDING STRUCTURE.
5.
SUPPORT ALL PIPING IN ACCORDANCE W/ 2012 NC PLUMBING CODE. ANY
SUSPENDED MATERIALS SHALL BE DIRECTLY SUPPORTED BY THE BUILDING
STRUCTURE.
6.
PENETRATIONS OF ALL EXTERIOR WALLS, FLOORS AND CEILINGS SHALL BE SEALED
IN AN AIR TIGHT MANNER AND IN ACCORDANCE W/ 2012 NCECC APPENDIX 2
DETAILS.
5.
6.
THE PLUMBING CONTRACTOR SHALL COORDINATE CLOSELY WITH ALL OTHER
TRADES TO AVOID CONFLICT AND ENSURE OTHER TRADES PROVIDE MEASURES TO
ACCOMMODATE PLUMBING WORK (I.E. ACCESS DOORS, SLAB/WALL/ROOF
OPENINGS, ELECTRICAL CONNECTIONS, ETC)
PIPING SHOULD BE COORDINATED WITH ALL STRUCTURAL FOOTINGS AND
FOUNDATIONS. PIPE SHOULD BE OFFSET TO AVOID CONTACT WITH FOOTINGS
AND FOUNDATION WALLS. IF PIPING MUST RUN UNDERNEATH A FOOTING OR
THROUGH A FOUNDATION WALL, THE PIPE MUST BE INSTALLED WITH A RELIEVING
ARCH OR IN A PIPE SLEEVE.
P.C. TO REFER TO ARCHITECTURAL DRAWINGS FOR MOUNTING HEIGHTS OF
PLUMBING FIXTURES.
V. EXECUTION:
1.
2.
7.
8.
9.
10.
11.
12.
13.
14.
P.C. TO FOLLOW MANUFACTURER'S INSTRUCTIONS WHEN INSTALLING PLUMBING
EQUIPMENT. ENSURE REQUIRED MAINTENANCE ACCESS AND CLEARANCES ARE
MAINTAINED. IF CONFLICT EXISTS BETWEEN THESE PLANS AND MFG INSTRUCTIONS
CONTACT ENGINEER.
CLEANOUT PLUGS SHALL BE INSTALLED IN ACCORDANCE WITH PLUMBING CODE
REQUIREMENTS. PROVIDE CLEANOUTS AS PLANS INDICATED AND AT THE BASE OF
ALL WASTE STACKS, AT EVERY FOUR 45 DEGREE TURNS, AT EVERY 100 FEET, AND AT
THE BASE OF ALL ROOF LEADERS. CLEANOUTS SHALL BE PLACED IN READILY
ACCESSIBLE LOCATIONS.
SUPPLY BRANCH LINES SERVING MORE THAN (1) FIXTURE SHALL INCLUDE SHUT-OFF
VALVE. LABEL VALVE AND LOCATE AS CLOSE TO RISER/MAIN AS POSSIBLE. (NCPC
606.2.1)
VALVES NOT DIRECTLY AT EQUIPMENT SHALL BE LABELED INDICATING THE FIXTURE
OR AREA SERVED. (NCPC 606.4)
WATER HEATER SHALL BE FILLED WITH WATER AND PURGED AS SOON AS INSTALLED
OR IN NO EVENT LATER THAN GAS/ELECTRIC HOOK-UP.
COPPER PIPING SHALL BE PROTECTED AGAINST CONTACT WITH MASONRY OR
DISSIMILAR METALS. ALL HANGERS, SUPPORTS, ANCHORS, AND CLIPS SHALL BE
COPPER OR COPPER PLATED. WHERE COPPER PIPING IS CARRIED ON IRON
TRAPEZE HANGERS WITH OTHER PIPING, SATISFACTORY AND PERMANENT
ELECTROLYTIC ISOLATION MATERIAL SHALL PROTECT THE COPPER AGAINST
CONTACT WITH OTHER METALS.
WHERE COPPER PIPING IS SLEEVED THROUGH MASONRY, SLEEVES SHALL BE
COPPER OR RED BRASS. WHERE COPPER MUST BE CONCEALED IN A MASONRY
PARTITION OR AGAINST MASONRY, CONTACT SHALL BE PREVENTED BY COATING
THE COPPER HEAVILY WITH ASPHALTIC ENAMEL AND PROVIDING 15# ASPHALT
SATURATED FELT BETWEEN THE PIPE AND MASONRY.
ALL PIPE INSULATION SHALL RUN CONTINUOUSLY THROUGH FLOORS, WALLS, AND
PARTITIONS. PIPE INSULATION SHALL BE MITERED AT ELBOWS AND TEES TO ENSURE
COMPLETE COVERAGE OF PIPING.
PROVIDE SHUT OFF VALVES ON THE FIXTURE SUPPLY TO EACH PLUMBING FIXTURE,
APPLIANCE, OR MECHANICAL EQUIPMENT.
15.
VACUUM BREAKERS SHALL BE PROVIDED FOR ALL FIXTURES TO WHICH HOSES MAY
BE ATTACHED. VACUUM BREAKERS SHALL BE PERMANENTLY ATTACHED.
16.
THE PLUMBING CONTRACTOR SHALL PROVIDE WATER HAMMER PROTECTION ON
ALL WATER DISTRIBUTION PIPING SERVING EQUIPMENT W/ QUICK CLOSING
VALVES (ICE MAKERS, DISHWASHERS, FLUSH VALVES, WASHING MACHINES, WATER
COOLERS, ETC.) SEE SHOCK ARRESTOR SCHEDULE.
17.
ACCESS DOORS TO BE PROVIDED FOR ALL VALVES AND DEVICES REQUIRING
ACCESS WHEN LOCATED IN WALLS OR ABOVE INACCESSIBLE CEILING
CONSTRUCTION. ACCESS DOORS TO BE RATED WHERE INSTALLED IN RATED
ASSEMBLIES.
18.
THE PLUMBING CONTRACTOR SHALL BE RESPONSIBLE FOR PROTECTING ALL
PLUMBING EQUIPMENT FROM FOREIGN MATERIAL DURING CONSTRUCTION
(PAINT, SPACKLE, ETC.). UPON COMPLETION OF WORK THE PLUMBING
CONTRACTOR SHALL CLEAN, WASH, ETC ALL ITEMS AND EQUIPMENT WITHIN HIS
SCOPE OF WORK AND LEAVE ALL ITEMS BRIGHT AND CLEAN.
19.
PROVIDE PRESSURE REDUCING VALVE IF INCOMING WATER PRESSURE EXCEEDS 80
PSI.
20.
NO INSULATION PERMITTED ON BACKFLOW PREVENTOR ASSEMBLY.
21.
GAS FIRED COOKING EQUIPMENT TO BE INSTALLED IN ACCORDANCE W/ NCFGC
SEC 411.1.1. INSTALLATION TO INCLUDE FULL-SIZE SHUT OFF VALVE, COMMERCIAL
GRADE ANSI RATED FLEXIBLE CONNECTION EQUAL TO EQUIPMENT CONNECTION
SIZE W/ SWIVEL (6' MAX) AND RESTRAINING CABLE(S).
SHOCK ARRESTOR SCHEDULE
MFG & MODEL (OR EQUAL)
IND. FIXTURE
SEE FIXTURE SCHEDULE
SIOUX CHIEF "MINI-RESTER"
1-11
A (1/2")
SIOUX CHIEF "HYDRA-RESTER"
12 - 32
B (3/4")
SIOUX CHIEF "HYDRA-RESTER"
33-60
C (1")
SIOUX CHIEF "HYDRA-RESTER"
61-113
D (1")
SIOUX CHIEF "HYDRA-RESTER"
114-154
E (1")
DOMESTIC HOT WATER PIPING
HWR
WASTE (SANITARY SEWER)
GW
WASTE (GREASE)
G
GAS PIPING
SIOUX CHIEF "HYDRA-RESTER"
BV-1
FULL-PORT BALL VALVE
MFG & MODEL (OR EQUAL)
CV-1
DBL CHECK VALVE
CV-2
BRONZE CHECK VALVE
WATTS CV
PRV-1
PRESS. RED. VALVE
WATTS 223-S
(SET TO 40 PSI)
TV-1
IND. TEMP. VALVE
LEONARD 270-LF
TV-2
MASTER TEMP. VALVE
N170-M3 CSUT
GBV-1
GAS BALL VALVE
APOLLO 80 SERIES
GSV-1
GAS SOLENOID VALVE
BY OTHERS
W/ DOME STRAINER.
W/ DEEP SEAL TRAP.
W/ HALF GRATE
W/ VACUUM BREAKER.
WALL
W/ DEEP SEAL TRAP.
SEE
PLAN
FLOOR
MAX 1.2 GPM @ 3FT TDH.
IN-LINE
W/ TYPE 304 S.S. GRATE
FLOOR
SEE
PLAN
WALL
W/ ZURN CO-2530 WALL COVER.
W/ PVC PLUG W/ THREADED TAP.
100 GALLON, 199 MBH INPUT.
PLATFORM
AIR ADMITTANCE VALVE
ABV
ABOVE
AHJ
AUTHORITY HAVING JURISDICTION
AFF
ABOVE FINISHED FLOOR
BFP
BACK FLOW PREVENTER
BV
BALL OR BALANCING VALVE (SEE SCHED)
CV
CHECK VALVE
CW
COLD WATER
DN
DOWN
E.C.
ELECTRICAL SUB-CONTRACTOR
FCO
FLOOR CLEAN OUT
FLOOR DRAIN
FROM
DEMO PIPING/EQUIPMENT
FS
FLOOR SINK
VALVE
GBV
G.C.
GAS BALL VALVE
GENERAL CONTRACTOR
VALVE
GSV
HB
GAS SOLENOID VALVE
HOSE BIBB
HD
HUB DRAIN
HW
HOT WATER
PIPE UP
M.C.
MECHANICAL SUB-CONTRACTOR
PIPE DOWN
P.C.
PLUMBING SUB-CONTRACTOR
PRV
PRESSURE REDUCING VALVE
SS
SANITARY SEWER
TV
TEMPERING VALVE
V
VENT
W
WASTE
WF
WALL FAUCET
WH
WATER HEATER
WHD
WALL HYDRANT
CLEANOUT
CONNECT TO EXISTING POINT
DEMO TO POINT
###
AAV
FR
FLOOR SINK
BELL & GOSSETT CB
(CIRCUIT SETTER PLUS, W/ TEST PORTS)
WATTS SD-2-MF (<1/2"), WATTS 9D (1/2"+)
(ASSE 1022 APPROVED)
BALANCING VALVE
W/ NICKEL GRATE.
W/ DEEP SEAL TRAP.
FD
FLOOR DRAIN
WATTS LFB6081
BV-2
W/ WALL BRACKET. W/ MOP HANG.
W/ HOSE & HOSE BRACKET.
W/ VACUUM BREAKER.
EXISTING PIPING/EQUIPMENT
CHECK VALVE
VALVE SCHEDULE
DESCRIPTION
DOMESTIC HOT WATER RETURN
VENT PIPING
NOTES:
1. LOCATED SHOCK ARRESTORS IN ACCESSIBLE LOCATION OR PROVIDE SIOUX CHIEF
BRAND ARRESTORS ONLY.
2. SEE PLAN, RISERS, SCHEDULES FOR ARRESTER LOCATIONS. IF LOCATION NOT INDICATED
INSTALL IN ACCORDNCE W/ MFG GUIDELINES.
TAG
W/ WALL BRACKET. 0.25 GPM.
MOUNT AT ADA HEIGHT.
DC PWR.
PLUMBING LEGEND
DOMESTIC COLD WATER PIPING
UNIT SIZE (CONN. SIZE)
PROVIDE OPEN FRONT SEAT
WITH NO LID.
W/ TIMER.
NOTES:
1. ALL FIXTURE COLORS & FINISHES TO BE APPROVED BY OWNER & ARCHITECT BEFORE PURCHASING.
2. PROVIDE P-TRAP AND SUPPLY LINE SAFETY COVERS FOR ALL ADA SINK AND LAVATORY INSTALLATIONS.
3. WATER CLOSET HANDLES TO BE LOCATED ON "WIDE SIDE" OF STALL FOR ADA FIXTURES.
4. SEE DETAIL SHEET FOR ADDITIONAL ITEMS TO BE PROVIDED/INSTALLED W/ FIXTURES LISTED ABOVE.
FIXTURE UNITS
REMARKS
HW
FINISHED
FLOOR
G.C. TO BE RESPONSIBLE FOR PROVIDING AND INSTALLING ANY WATER HEATER
PLATFORMS, EITHER FLOOR/WALL MOUNTED OR SUSPENDED. P.C. TO
COMMUNICATE REQ'S TO G.C.
7.
P.C. TO COORDINATE W/ G.C. AND ARCH PLANS TO ENSURE NECESSARY
BACKING/SUPPORTS ARE INSTALLED TO ALLOW INSTALLATION OF PLUMBING
FIXTURES.
TYPE
FLOOR
DRAIN
PLUMBING CONTRACTOR IS TO EMPLOY THE SERVICES OF THE G.C. FOR CUTTING
AND PATCHING OF WALLS, FLOORS & CEILINGS RELATED TO THE INSTALLATION OF
PLUMBING EQUIPMENT & SYSTEMS.
G.C. RESPONSIBLE FOR PAINTING OF GAS PIPING ON EXTERIOR OF BUILDING. P.C.
RESPONSIBLE FOR CLEANING AND PREPARING PIPING FOR PAINT, COORDINATE
W/ G.C.
P.C. TO COORDINATE LOCATION OF ALL ROOF PENETRATIONS W/ ROOFING
CONTRACTOR & MECHANICAL CONTRACTOR. P.C. & M.C. TO COORDINATE TO
ENSURE NO PLUMBING VENTS ARE LOCATED WITHIN 10' OF ANY OUTSIDE AIR
INTAKES.
FAUCET/VALVE
FIXTURE
MARK
FD
4.
II. DIVISION OF WORK:
1.
BEFORE BEGINNING WORK INVERT ELEVATIONS SHALL BE ESTABLISHED. PC IS TO
ENSURE PROPER SLOPES OF ALL WASTE AND STORM PIPING CAN BE MAINTAINED,
CONTACT ENGINEER IMMEDIATELY IF PROBLEM/ISSUE IS DISCOVERED.
PLUMBING FIXTURE SPECIFICATIONS AND CONNECTION SCHEDULE
6/16/14
maple
ENGINEERING, pllc
1405 HILLSBOROUGH ST
RALEIGH, NC 27605
LIC.#: P-0990
P:919-341-4247
F:919-890-3797
plumbing mechanical electrical
KITCHEN EQUIPMENT TAG
NOTES:
1. SEE PLAN FOR SIZE. VALVE SIZE TO EQUAL LINE SIZE.
2. BALL VALVES TO INCLUDE REMOVABLE HANDLES.
3. IF AVAILABLE, VALVES MAY BE THREADED OR SWEATED CONNECTIONS. USE EXTREME
CARE AND LOW TEMP SOLDER TO PROTECT VALVE SEATS IF SWEATED CONNECTIONS
ARE USED.
4. VERIFY SOLENOID VALVE DETAILS W/ E.C. & KITCHEN EQUIPMENT/HOOD MFG.
Project Number :LAG-1404
Drawn By: MJL, RDG, RSA
Date: 06-16-14
P-1
PLUMBING
SCHEDULES
& NOTES
FIRE RATING LEGEND
1-HR WALL
CV
CW MAKE-UP
TIME CLOCK
TC
BV
G
CV
GAS
FROM
GAS MAIN
RP-1
H.W. RETURN
UN
UN
HW TO FIXTURES
THER.
SHUT-OFF
VALVE (TYP)
ITEM
#
QTY.
DESCRIPTION
DIRECT DRAIN SIZE
(IN)
EXPANSION
TANK
INDIR. DRAIN SIZE
(IN)
VACUUM
BREAKER
COLD WATER SIZE
(IN.)
TYPE 'B' FLUE
THRU ROOF BY
MC.
HOT WATER SIZE
(IN.)
EQUIPMENT SCHEDULE
10
3
HAND SINK
0.5
0.5
-
1.5
17
1
KETTLE ON STAND
0.5
0.5
1.0
-
DRAIN TO TRENCH DRAIN W/ AIR GAP.
18
1
WORKTABLE W/ SINK
0.5
0.5
1.5
-
DRAIN TO FLOOR SINK W/ AIR GAP.
19
1
3-COMPARTMENT SINK
0.5
0.5
1.5
-
DRAIN TO FLOOR SINK W/ AIR GAP. W/ SPRAYER.
20
1
ICE MAKER W/ BIN
-
0.5
1.0
-
DRAIN TO HUB DRAIN W/ AIR GAP. W/ CV-1 & SHOCK ARRESTOR.
26
1
BAG-IN-BOX SYSTEM
-
0.5
1.0
-
LOCATE AT 18" AFF. W/ CV-1 & SHOCK ARRESTOR. DRAIN TO HUB DRAIN W/ AIR GAP.
26A
1
BAG-IN-BOX SYSTEM
-
0.5
-
-
LOCATE AT 24" AFF. W/ CV-1 & SHOCK ARRESTOR.
36
1
DISHWASER
0.75
-
1.0
-
DRAIN TO FLOOR SINK W/ AIR GAP. W/ CV-1 & SHOCK ARRESTOR.
PLUMBING NOTES
PROVIDE TV-1
NOTE:
P.C. TO VERIFY EXACT TYPE, QTY, LOCATION OF EQUIPMENT PLUMBING CONNECTIONS BEFORE BEGINNING WORK. P.C. RESPONSIBLE FOR PROVIDING AND
INSTALLING ALL REQUIRED FITTINGS, ACCESSORIES AND SIMILAR. FINAL CONNECTION TO EQUIPMENT BY P.C.
TEMPERATURE AND
PRESSURE RELIEF VALVE
G
UNION (TYP)
GENERAL NOTES - THIS SHEET
GAS SHUT-OFF
VALVE
DISCHARGE FULL SIZE
OF VALVE DISCHARGE.
ROUTE DISCHARGE TO
MOP SINK.
WH-1
6" DIRT
LEG
HB
PLATFORM
1.
ITEMS SHOWN IN FAINT & HATCHED ARE TO BE DEMO'D OR
RELOCATED. ITEMS SHOWN IN FAINT ARE EXISTING TO
REMAIN. NEW OR RELOCATED ITEMS ARE SHOWN IN BOLD.
SEE LEGEND.
P.C. TO VERIFY EXACT SIZE, LOCATION, INVERT & DIRECTION
OF EXISTING LINES BEFORE BEGINNING WORK.
P.C. TO VERIFY THAT NO FIXTURES ARE CONNECTED
UPSTREAM OF BACK FLOW PREVENTER.
2.
WATER HEATER ON PLATFORM BY
G.C. SIZE PER LOCAL SIESMIC
REQUIREMTNS AND TOTAL WEIGHT
OF WATER HEATER FULL OF
WATER.
3.
1" DRAIN LINE
TO CAN WASH.
TAGGED NOTES - THIS SHEET
NOTE:
1. INSTALL H.W. HEATER PER MANUFACTURER RECOMMENDATION.
2. PROVIDE HEAT TRAP ON CW AND HW LINES PER ENERGY CODE.
WATER HEATER DETAIL
2
1
1-1/2" CW UP FR SLAB. PROVIDE SHUT-OFF VALVE.
2
PROVIDE TEMPERING VALVE, TV-1, UNDER SINK. SET TO
NO SCALE
6/16/14
maple
STORAGE
ENGINEERING, pllc
1405 HILLSBOROUGH ST
RALEIGH, NC 27605
LIC.#: P-0990
P:919-341-4247
F:919-890-3797
MEN
plumbing mechanical electrical
2
P-1
P-2
HALL
WOMEN
DINING AREA 4
DINING AREA 3
DINING AREA 2
2
P-1
BACK
HALL
P-2
CAN
WASH
WH-1 ABV
CAN WASH
TO GO
ORDERS
CUSTOMER QUEUE
26A
P-3
HWR
TO
RP-1
@ WH-1
FRONT KITCHEN
OFFICE
20
EXIST. 1-1/2"
CW FR METER
2
HB
1
BFP-1
10
2
10
DINING AREA 1
10
36
CATERING
STORAGE
2
19
HB
18
17
Project Number :LAG-1404
Drawn By: MJL, RDG, RSA
Date: 06-16-14
PREP KITCHEN/
DRY STORAGE
26
1
PLUMBING PLAN - WATER
SCALE: 1/4" = 1'-0"
P-2
PLUMBING
PLAN WATER
FIRE RATING LEGEND
1-HR WALL
QTY.
DESCRIPTION
COLD WATER SIZE
(IN.)
INDIR. DRAIN SIZE
(IN)
DIRECT DRAIN SIZE
(IN)
10
3
HAND SINK
0.5
0.5
-
1.5
13
2
HOT FOOD COUNTER
-
-
1.5
-
DRAIN TO FLOOR SINK W/ AIR GAP.
17
1
KETTLE ON STAND
0.5
0.5
1.0
-
DRAIN TO FLOOR SINK W/ AIR GAP.
18
1
WORKTABLE W/ SINK
0.5
0.5
1.5
-
DRAIN TO FLOOR SINK W/ AIR GAP.
19
1
3-COMPARTMENT SINK
0.5
0.5
1.5
-
DRAIN TO FLOOR SINK W/ AIR GAP. W/ SPRAYER.
20
1
ICE MAKER W/ BIN
-
0.5
1.0
-
DRAIN TO HUB DRAIN W/ AIR GAP. W/ CV-1 & SHOCK ARRESTOR.
DRAIN LINE,
SUPPORT ABV HUB
AIR GAP
HUB
ADAPTER
FLOOR
TO DRAIN
DEEP SEAL
TRAP
5
ITEM
#
HOT WATER SIZE
(IN.)
EQUIPMENT SCHEDULE
HUB DRAIN DETAIL
PLUMBING NOTES
PROVIDE TV-1
21
1
ICE DISPENSER
-
-
1.0
-
DRAIN TO HUB DRAIN W/ AIR GAP.
26
1
BAG-IN-BOX SYSTEM
-
0.5
1.0
-
(2) 0.5" CW CONNECTIONS. LOCATE AT 18" AFF & 24" AFF. W/ CV-1 & SHOCK ARRESTOR.
36
1
DISHWASER
0.75
-
1.0
-
DRAIN TO FLOOR SINK W/ AIR GAP. W/ CV-1 & SHOCK ARRESTOR.
NOTE:
P.C. TO VERIFY EXACT TYPE, QTY, LOCATION OF EQUIPMENT PLUMBING CONNECTIONS BEFORE BEGINNING WORK. P.C. RESPONSIBLE FOR PROVIDING AND
INSTALLING ALL REQUIRED FITTINGS, ACCESSORIES AND SIMILAR. FINAL CONNECTION TO EQUIPMENT BY P.C.
NO SCALE
STACK, VENT, OR
END CAP. SEE
PLAN/RISER.
STRAINER
THREADED
CLEANOUT
PLUG
COVER PLATE WITH
SECURING SCREW
(APPX. 18" AFF)
SEE NOTE
TEST TEE
TOP OF QUARRY TILE
FLUSH WITH TOP OF
DRAIN GRATE
GRATE - SEE FIXTURE
SCHEDULE FOR TYPE
1.
FINISHED
FLOOR
DOME STRAINER
ITEMS SHOWN IN FAINT & HATCHED ARE TO BE DEMO'D OR
RELOCATED. ITEMS SHOWN IN FAINT ARE EXISTING TO
REMAIN. NEW OR RELOCATED ITEMS ARE SHOWN IN BOLD.
SEE LEGEND.
P.C. TO VERIFY EXACT SIZE, LOCATION, INVERT & DIRECTION
OF EXISTING LINES BEFORE BEGINNING WORK.
2.
TAGGED NOTES - THIS SHEET
6" MIN.
FINISHED
WALL
GENERAL NOTES - THIS SHEET
FLASHING COLLAR
SEEPAGE HOLES
1
PORTION OF BRANCH LINE IS PART OF CIRCUIT VENT
SYSTEM, MAXIMUM SLOPE 8%. TURN DOWN AS
NECESSARY AFTER MOST DOWNSTREAM FIXTURE. IF
SLOPE REQ'S CANNOT BE MAINTAINED ADDITIONAL
VENTS WILL BE REQUIRED.
2
BRANCH DRAIN FROM TRENCH DRAIN TO BE CAST
3
REMOVE & REPLACE IF NECESSARY FOR FLOOR
INSTALLATION.
TO DRAIN
NOTE:
EXTEND TEST TEE OPENING IF PLUG IS GREATER THAN
8" FROM FINISHED WALL.
SEE FLOOR PLAN
FOR PIPE SIZE
WALL CLEANOUT DETAIL
4
3
NO SCALE
FLOOR SINK DETAIL
FLOOR DRAIN DETAIL
2
NO SCALE
NO SCALE
4
COORD. EXACT LOCATION OF TRENCH DRAIN W/
OWNER & KETTLE POSITION.
STORAGE
maple
MEN
VENT
&
WCO
6/16/14
ENGINEERING, pllc
1405 HILLSBOROUGH ST
RALEIGH, NC 27605
LIC.#: P-0990
P:919-341-4247
F:919-890-3797
P-1
P-2
plumbing mechanical electrical
HALL
1
WOMEN
P-1
TO EXIST.
2,000 GAL.
GREASE
SEPERATOR
DINING AREA 4
DINING AREA 3
P-2
3
GW
GW
GW
EXIST.
FCO
TO GO
ORDERS
NOTE:
P.C. TO VERIFY EXISTING
LINES. P.C. TO TAKE ALL
MEASURES POSSIBLE TO
ENSURE GREASY WASTE
AND SANITARY SEWER
SYSTEMS DO NOT BECOME
INTERCONNECTED. P.C.
RESPONSIBLE FOR ANY
INTERCONNECTION THAT
OCCURS.
CUSTOMER QUEUE
CAN WASH
BACK
HALL
2" HD
26
3" FS
P-3
13
3" FD
OFFICE
EXIST. 4"
TO S.S.
DINING AREA 2
13
3" FD
FRONT KITCHEN
EXIST.
FCO
3
20
21
1
10
2" HD
10
DINING AREA 1
19
17
18
36
CATERING
STORAGE
10
3" FS
3" FD
VENT
& WCO
2
3" FS
4
PREP KITCHEN/
DRY STORAGE
3" TD
Project Number :LAG-1404
Drawn By: MJL, RDG, RSA
Date: 06-16-14
P-3
EXIST. 4"
GREASY
WASTE
1
PLUMBING PLAN - WASTE
SCALE: 1/4" = 1'-0"
PLUMBING
PLAN WASTE
6/16/14
maple
ENGINEERING, pllc
1405 HILLSBOROUGH ST
RALEIGH, NC 27605
LIC.#: P-0990
P:919-341-4247
F:919-890-3797
2
1
METALLIC PIPE (GYPSUM WALL) DETAIL
plumbing mechanical electrical
NO SCALE
WASTE/VENT RISER
NO SCALE
Project Number :LAG-1404
Drawn By: MJL, RDG, RSA
Date: 06-16-14
P-4
PLUMBING
RISERS
FIRE RATING LEGEND
1-HR WALL
PIPING
PIPE CLAMPS: "UNISTRUT"
#P2600 WITH CUSHION
BETWEEN PIPING &
CLAMP. SIZE TO MATCH
PIPING SIZE
EQUAL TO PIPE PIER:
CLOSED CELL BLACK POLYETHYLENE FOAM,
14 GAUGE CHANNEL STRUT
ROOF WALK PAD BELOW
SUPPORT PER ROOF MFG. REQMT'S.
NATURAL GAS CALCULATIONS
TABLE 402.4(3)
NOTE:
MAX CAPACITY OF PIPE IN MBH
SUPPORT PIPE AT MAXIMUM OF 6'-0" O.C.
SEE ARCH. DWGS. FOR ROOF PENETRATION DETAILS.
5
BY P.C.
BY M.C.
NOTE:
PROVIDE REGULATOR AT EACH ROOF TOP UNIT
TO PROVIDE GAS PRESSURE AND CAPACITY AS
REQUIRED BY UNIT MANUFACTURER
GAS PIPING SUPPORT DETAIL
NO SCALE
ROOF TOP UNIT
SHUT-OFF VALVE
PIPE SIZE (IN.)
EQUIV. LENGTH = 325 FT
?? FT
?? FT
1/2"
243 MBH
?? MBH
?? MBH
3/4"
507 MBH
?? MBH
?? MBH
1"
907 MBH
?? MBH
?? MBH
BASED UPON CHAPTER 4 OF THE 2012 NORTH CAROLINA FUEL GAS CODE,
2.0 PSI INLET PRESSURE, 1.0 PSI PRESSURE DROP.
PITCH BACK TO SOURCE
UNION (OPTIONAL). CONFIRM
W/ MFG'S INSTRUCTIONS.
ROOF
GAS CONNECTION DETAIL
NO SCALE
1
CHAR-BROILER
0.75
72.0
1
2-BURNER RANGE W/ GRIDDLE
0.75
138.0
1
COUNTER TOP GRIDDLE
0.75
84.0
GAS PIPE SUPPORT
DIRT LEG
3
DESCRIPTION
GAS LINE SIZE (IN)
12" MAX.
FLEX CONNECTION FROM SHUT-OFF
VALVE(S) & REGULATOR
2
GAS PIPING RTU CONNECTION
GAS INPUT (MBTUH)
EQUIPMENT SCHEDULE
ITEM
#
QTY.
2
4
5
NO SCALE
NOTE:
P.C. TO VERIFY EXACT TYPE, QTY, LOCATION OF EQUIPMENT PLUMBING
CONNECTIONS BEFORE BEGINNING WORK. P.C. RESPONSIBLE FOR
PROVIDING AND INSTALLING ALL REQUIRED FITTINGS, ACCESSORIES AND
SIMILAR. FINAL CONNECTION TO EQUIPMENT BY P.C.
6/16/14
maple
ENGINEERING, pllc
1405 HILLSBOROUGH ST
RALEIGH, NC 27605
LIC.#: P-0990
P:919-341-4247
F:919-890-3797
plumbing mechanical electrical
WH-1
(199 MBH)
4
GAS DWN
TO WH-1
(120 MBH)
(60 MBH)
GAS RISER
SCALE: 1/4" = 1'-0"
5
(84 MBH)
2
(72 MBH)
4
(138 MBH)
1" GAS LINE DWN THRU
ROOF. EXTEND 3/4" LINE
ON TO COOKLINE W/
GSV-1 IN RISER.
OPPOSITE END
OF BUILDING
GENERAL NOTES - THIS SHEET
APPX.
110'
1
GAS FR BLW
GRADE TO EXIST.
GAS HEADER
NEW GAS METER W/ 2.0
PSI REGULATOR.
COORDINATE LOCATION
WITH UTILITY. TOTAL LOAD
= 823 MBH. EQUIVALENT
LENGTH = 325 FEET.
GAS PIPING PLAN
1.
SCALE: 1/4" = 1'-0"
2.
3.
P.C. IS TO PROVIDE REGULATOR, FLEX CONNECTION &
SHUT-OFF VALVE AT EACH EQUIPMENT CONNECTION.
COORDINATE AND VERIFY EXACT SIZE AND LOCATION OF
EQUIPMENT GAS CONNECTION(S) BEFORE BEGINNING
WORK.
PROVIDE LABELING ON GAS PIPING AS REQUIRED BY 2012
NCFGC SEC. 401.5 & 401.7.
P.C. IS RESPONSIBLE FOR VENTING REGULATORS TO
EXTERIOR AS REQ'D.
Project Number :LAG-1404
Drawn By: MJL, RDG, RSA
Date: 06-16-14
P-5
GAS PLAN
& RISER
PACKAGED DX COOLING/GAS-ELEC HEATING ROOF TOP UNIT SCHEDULE
HVAC GENERAL NOTES
EVAPORATOR FAN DATA
I. GENERAL REQUIREMENTS:
5.
NO FLEXIBLE DUCT ALLOWED FOR NEGATIVE PRESSURE EXHAUST APPLICATIONS.
1.
6.
ALL SUPPLY AND RETURN DUCTWORK AND PLENUMS SHALL BE INSULATED.
INSULATION OF DUCTWORK IN UNCONDITIONED SPACE SHALL BE MINIMUM R-5 PER
2012 NCECC. INSULATION OF DUCTWORK OUTSIDE BUILDING THERMAL ENVELOPE
(I.E. ROOF, ATTIC, CRAWLSPACE) SPACE SHALL BE MINIMUM R-8 PER 2012 NCECC.
2.
3.
4.
5.
MECHANICAL CONTRACTOR IS TO FURNISH AND PAY FOR ALL LABOR, MATERIAL,
EQUIPMENT, PERMITS & FEES REQUIRED FOR THE COMPLETE INSTALLATION OF ALL
SYSTEMS IN THIS SECTION OF WORK.
ALL WORK IS TO BE PERFORMED IN ACCORDANCE WITH NC MECHANICAL CODES
AND ALL OTHER APPLICABLE CODES. MC IS TO COORDINATE W/ G.C. IN REGARDS
TO PROJECT TIMELINE, WORK HOURS, AS WELL AS ANY BONDING OR INSURANCE
REQUIREMENTS.
ALL MECHANICAL EQUIPMENT SHALL BE PROVIDED COMPLETE WITH ALL
ACCESSORIES, HANGERS, SUPPORTS, CONTROLS, ETC FOR A FULLY FUNCTIONING
SYSTEM REGARDLESS OF PRESENCE ON PLANS.
ALL EQUIPMENT, MATERIALS AND INSTALLATION SHALL BE GUARANTEED TO BE FREE
OF DEFECTS FOR A PERIOD OF ONE (1) YEAR AFTER FINAL ACCEPTANCE OF WORK
OR IN ACCORDANCE WITH THE MANUFACTURER'S STANDARD GUARANTEE, IF
LONGER. ALL COMPRESSORS ARE TO INCLUDE FIVE (5) YEAR WARRANTY. EXISTING
EQUIPMENT IS EXCLUDED FROM WARRANTY REQUIREMENT.
THESE DRAWINGS ARE DIAGRAMMATIC AND SHOW GENERAL LOCATION AND
ARRANGEMENT OF ALL MATERIALS AND EQUIPMENT. THE DRAWINGS SHALL BE
FOLLOWED AS CLOSELY AS BUILDING CONSTRUCTION AND ALL OTHER WORK WILL
PERMIT.
6.
DO NO SCALE DRAWINGS FOR MEASUREMENT.
7.
ALL DUCT DIMENSIONS SHOWN ARE INTERIOR DUCT DIMENSIONS.
8.
9.
INFORMATION GIVEN IN SCHEDULES INCLUDES BOTH DESCRIPTION OF PRODUCT
AND MANUFACTURER'S MODEL #. IF CONFLICT IS PRESENT BETWEEN DESCRIPTION
AND MODEL #, EQUIPMENT DESCRIPTION SHALL TAKE PRECEDENT. IN CASE OF
CONFLICT BETWEEN THE PLANS AND NOTES/SPECIFICATIONS OR CONFLICT BETWEEN
INFORMATION PRESENTED ON THE PLANS OR IN THE NOTES/SPECIFICATIONS, THEN
THE MOST RESTRICTIVE SHALL TAKE PRECEDENT.
BEFORE BID MC IS RESPONSIBLE FOR CLARIFYING W/ G.C. ANY CONFUSION IN
REGARDS TO RESPONSIBILITY OF WORK TO BE PERFORMED OR MATERIALS TO BE
PROVIDED. THE SUBMITTAL OF THE BID BY THE CONTRACTOR WILL BE HELD AS
PROOF THAT THE CONTRACTOR UNDERSTANDS THOROUGHLY AND COMPLETELY
THE SCOPE OF THE WORK INVOLVED, AND HAS INCLUDED ON THE BID ALL THE
NECESSARY ITEMS TO CARRY OUT THIS SECTION OF WORK.
7.
8.
9.
CONCEALED SHEET METAL SUPPLY & RETURN DUCT MAY BE EXTERNALLY INSULATED
WITH MINERAL FIBER BOARD OR BLANKET OR MAY BE INTERNALLY INSULATED WITH
ACOUSTICAL DUCT LINER. EXPOSED SPIRAL DUCTWORK DOES NOT REQUIRE
INSULATION UNLESS OTHERWISE NOTED (WHEN INSTALLED IN CONDITIONED SPACE).
ALL MAIN DUCTWORK (INCLUDING EXHAUST) TO BE SEALED ACCORDING TO 2012
NCECC AND AT A MINIMUM INCLUDE SEALING OF ALL DUCT SEAMS W/
NON-HARDENING MASTIC. SEALING BY TAPE ALONE NOT ALLOWED.
CONDENSATE DRAIN PIPING AND FITTINGS SHALL BE SCHEDULE 40 PVC. DRAINS
FROM AIR HANDLING UNITS SHALL BE TRAPPED (2" MINIMUM). TRAPS ON INTERIOR
OF BUILDINGS TO BE INSULATED.
10. KITCHEN HOOD EXHAUST DUCT SHALL BE 16 GAUGE CARBON STEEL OR 18 GAUGE
STAINLESS STEEL. ALL JOINTS AND SEAMS SHALL BE CONSTRUCTED WITH A
CONTINUOUS LIQUID-TIGHT EXTERNAL WELD. PRE-APPROVED U.L. LISTED FACTORY
BUILD EXHAUST SYSTEM (SUBMIT FOR APPROVAL BY ENGINEER BEFORE PURCHASE).
COOLING SECTION
OA, MAX OA, MIN
ESP
MOTOR
(CFM)
(CFM) (" OF WG) (HP)
UNIT
TAG
AREA
SERVED
FAN
CFM
RTU-1
DINING
3000
-
700
0.55"
RTU-2
DINING
2000
-
400
RTU-3
KITCHEN
4000
-
1000
FAN
RPM
AMBIENT
ENT. AIR
TOTAL
(MBH)
SENS.
(MBH)
# OF
STAGES
REHEAT
(MBH)
INPUT
(MBH)
3.0
MFG.
93/76
80/67
89.0
67.3
1
60.6
120.0
96.0
N/A
0.58"
1.0
MFG.
93/76
80/67
62.3
48.1
1
N/A
60.0
48.0
0.69"
3.75
MFG.
93/76
80/67
119.0
92.7
2
N/A
150.0
120.0
ELECTRICAL DATA
OUTPUT ELEC HEAT
# OF
(MBH)
(KW)
STAGES
VOLTAGE
(V/PH)
GENERAL DATA
MCA
(A)
MOCP
(A)
MANUF.
MODEL
NOM. EER
TON. (SEER)
WT.
(LBS)
1
44.0
60
TRANE
YSC090
7.5
11.2
784
1,2,3,4,5,6,7,8,9
N/A
1
29.5
45
TRANE
YSC060
5.0
11.0
962
1,2,3,4,5,6,8,9
N/A
2
49.6
60
TRANE
YSC120
10.0
11.3
1291
1,2,3,4,5,6,8,9
NOTES
NOTES:
1.
COOLING CAPACITIES ARE RATED IN ACCORDANCE WITH AT LEAST ONE OF THE FOLLOWING ARI STANDARDS;
5.
W/ FACTORY MOUNTED DISCONNECT.
6.
W/ FACTORY POWERED GFI CONVENIENCE RECEPTACLE.
7.
W/ REHEAT COIL/HUMIDITY CONTROL. SET TO 45% RH.
8.
W/ THRU THE BASE ELECTRICAL CONNECTION.
9.
RTU SUPPLY FAN TO BE INTERLOCKED W/ HOOD OPERATION.
TEMP., AND AIR QUANTITY LISTED BY MFG.
2.
PROVIDE MANUFACTURER'S 7 DAY PROGRAMMABLE THERMOSTAT W/ REMOTE SENSOR.
3.
PROVIDE 3 SETS OF NEW FILTERS FOR EACH UNIT. PROVIDE ONE AT INSTALLATION, ONE PRIOR TO AIR BALANCE
AND ONE AT TURNOVER TO OWNER.
4.
PROVIDE FACTORY ROOF CURB AND AIR SIDE DIFFERENTIAL ENTHALPY ECONOMIZER SECTION WITH
BAROMETRIC RELIEF DAMPER FOR EACH UNIT.
11. "FIRE WRAP" OR OTHER CLEARANCE REDUCING INSULATION INSTALLED ON GREASE
EXHAUST DUCT TO BE EQUAL TO "3M FIRE BARRIER DUCT WRAP 615+".
12. VENT MATERIAL SERVING ANY GAS FIRED APPLIANCE TO BE LISTED & LABELED, PER
MFG'S INSTRUCTIONS AND 2012 NC MECHANICAL CODE. IF CONFLICT IS NOTED
CONTACT ENGINEER.
HEATING SECTION
NOTE:
HUMIDITY
CONTROL/REHEAT MUST BE
PROVIDED TO AVOID
DUCT SWEATING IN
DINING AREA.
FAN SCHEDULE
UNIT
NO.
SERVICE
AREA
SERVED
CFM
S.P.
RPM
EF-1
EXHAUST
BATHROOM
150
0.23"
MFG
DOWNBLAST,
CENTRIFUGAL
1/60 HP
FF-1
AIR CURTAIN
BACK DOOR
2550
N/A
1750
OVERDOOR,
CENTRIFUGAL
1/2 HP
13. PLASTIC PIPE IS NOT ACCEPTABLE FOR GAS FIRED APPLIANCE VENTING UNLESS
PIPING IS LISTED & LABELED FOR SUCH INSTALLATIONS.
14. ALL DAMPERS TO INCLUDE SET SCREW OR SIMILAR FEATURE FOR LOCKING IN
POSITION.
TYPE &
MIN. MOTOR HP
ARRANGEMENT
& VOLTAGE
MANUFACTURER
& MODEL NO.
GREENHECK
G-070-G
MARS
N36-1U
DRIVE
CONTROL SCHEME
DIRECT
A
1,2,3,4,5.6
DIRECT
B
4,7
NOTES:
15. ALL FIRE SEALANTS TO BE U.L. LISTED AND APPROVED FOR USE W/ APPROPRIATE U.L.
PENETRATION DETAIL.
16. ALL PROGRAMMABLE THERMOSTATS TO INCLUDE BATTERY BACK-UP AND HAVE
NOTES
MECHANICAL LEGEND
CONTROL OPTIONS:
1.
SCREEN
4.
INTEGRAL DISCONNECT SWITCH
2.
BACKDRAFT DAMPER
5.
PROVIDE WITH FACTORY ROOF CURB
3.
COLOR BY ARCHITECT
6.
SPEED CONTROLLER
7.
A. CONTROL W/ ROOM LIGHTS (COORD. W/ E.C.)
B. CONTROL W/ DOOR SWITCH
W/ DOOR SWITCH
18x14
RECTANGULAR DUCT
ROUND METAL DUCT
FLEX/RIGID ROUND DUCT
10. AS SOON AS POSSIBLE (AND NOT MORE THAN 30 DAYS) AFTER CONTRACT IS
SIGNED, THE MC SHALL PROVIDE SUBMITTALS OF MECHANICAL EQUIPMENT HE/SHE
INTENDS TO PURCHASE FOR REVIEW AND COMMENT BY THE ENGINEER. ENGINEER IS
TO APPROVE SUBMITTALS BEFORE EQUIPMENT IS ORDERED.
IV. COORDINATION:
1.
11. ALL QUESTIONS MUST BE SUBMITTED IN RFI FORMAT TO THE ARCHITECT AND MUST BE
ADDRESSED BY THE APPROPRIATE DESIGNER OF RECORD PROIR TO BECOMING A
PROPOSED CHANGE ORDER.
2.
12. UPON COMPLETION OF WORK M.C. IS TO PROVIDE OWNER W/ COMPLETE BOUND
SET OF ALL EQUIPMENT OPERATION & MAINTENANCE MANUALS. PACKAGE IS ALSO
TO INCLUDE AND WARRANTY & GUARANTEE INFORMATION.
1.
2.
3.
4.
ALL ROOF WORK INCLUDING PENETRATIONS, OPENINGS, FLASHING, CURB INSTALLS,
ETC ARE TO BE PERFORMED BY ROOFING CONTRACTOR. M.C. RESPONSIBLE FOR
PROVIDING ANY ROOF CURBS, EQUIPMENT RAILS, VENTS, ETC AND
COMMUNICATING ALL REQ'S WITH G.C. & ROOFING CONTRACTOR.
M.C. TO COORDINATE LOCATION OF ALL ROOF PENETRATIONS W/ ROOFING
CONTRACTOR. P.C. & M.C. TO COORDINATE TO ENSURE NO PLUMBING VENTS OR
ANY OTHER SOURCES OF BUILDING EXHAUST ARE LOCATED WITHIN 10' OF ANY
OUTSIDE AIR INTAKES.
ALL MATERIALS INSTALLED IN RETURN PLENUM ARE TO BE PLENUM RATED.
3.
PROVIDE HANGERS & SUPPORTS APPROVED FOR USE BY 2012 NC MECHANICAL
CODE.
ALL MAIN DUCTWORK (SUPPLY, RETURN, EXHAUST, OUTSIDE AIR) SHALL BE
GALVANIZED SHEET METAL CONSTRUCTED IN ACCORDANCE WITH SMACNA
STANDARDS. RUNOUTS FROM MAIN/BRANCH DUCTS MAY BE FLEXIBLE DUCT
CONFORMING TO THE REQUIREMENTS OF UL 181 FOR CLASS 1 FLEXIBLE AIR DUCTS.
MAX. LENGTH OF FLEX PER RUNOUT TO BE 6'-0" UNLESS SHOWN OTHERWISE.
N/A
B
AS NOTED
AS NOTED
24x12
DUCT MTD. DBL. DEFL.
LAY-IN
PERF.
SERVICE
FINISH
MANUFACTURER
& MODEL NO.
VOLUME DAMPER
NOTES
SUPPLY TAP WITH VOLUME DAMPER
YES
WITH
EXTRACTOR
ALUM.
SUPPLY
NOTE 2
TITUS S300FS
NO
ALUM.
SUPPLY
NOTE 2
TITUS PAS-AA
1,2,3
SUPPLY TAP
6/16/14
1,2,3
ALUM.
SUPPLY
NOTE 2
TITUS PAS-AA
1,2,3
D
AS NOTED
N/A
AS NOTED
SURFACE
LOUVERED
NO
STEEL
RETURN
NOTE 2
TITUS 350RL
1,2,3
EXHAUST REGISTER/GRILLE OR RISER
V. EXECUTION:
E
AS NOTED
AS NOTED
24x12
LAY-IN
PERF.
NO
ALUM.
RETURN
NOTE 2
TITUS PAR-AA
1,2,3
SIDEWALL DIFFUSER/GRILLE
1.
F
AS NOTED
N/A
24x12
LAY-IN
PERF.
NO
ALUM.
EXHAUST
NOTE 2
TITUS PAR-AA
1,2,3
H
AS NOTED
AS NOTED
24x12
LAY-IN
PERF.
NO
ALUM.
HOOD
SUPPLY
NOTE 2
TITUS PAR-AA
1,2,3,4
M.C. TO FOLLOW MANUFACTURER'S INSTRUCTIONS WHEN INSTALLING MECHANICAL
EQUIPMENT. ENSURE REQUIRED MAINTENANCE ACCESS AND CLEARANCES ARE
MAINTAINED. IF CONFLICT EXISTS BETWEEN THESE PLANS AND MFG INSTRUCTIONS
CONTACT ENGINEER.
RETURN REGISTER/GRILLE OR RISER
CEILING EXHAUST FAN
T
maple
T-STAT
ENGINEERING, pllc
2.
ALL PENETRATIONS THROUGH EXTERIOR WALLS & ROOF SHALL BE FLASHED &
COUNTER-FLASHED IN A WATERPROOF MANNER.
INDEPENDENT CERTIFIED TEST AND BALANCE CONTRACTOR SHALL BALANCE SYSTEM
TO AIR QUANTITIES INDICATED ON PLANS AND IN ACCORDANCE W/ 2012 NCECC
SEC. 503.2.9. M.C. TO PROVIDE OWNER'S REPRESENTATIVE & ENGINEER WITH
COMPLETE BALANCE REPORT. MC RESPONSIBLE FOR PROVIDING ANY DAMPERS,
VALVES, PORTS, ETC. NECESSARY FOR A COMPLETE SYSTEM BALANCE.
6.
PENETRATIONS OF NON-RATED WALLS, PARTITIONS AND FLOOR OF COMBUSTIBLE
CONSTRUCTION SHALL BE FIRESTOPPED WITH MATERIALS EQUIVALENT TO TWO
INCHES OF WOOD. FIRESTOPPING SHALL COMPLY WITH ASTM E-814.
7.
ANY NOTCHING, DRILLING, BORING OR OTHER ALTERATION TO BUILDING
STRUCTURE SHALL BE PERFORMED IN A CODE APPROVED METHOD AND NOT
THREATEN THE INTEGRITY OF THE BUILDING STRUCTURE.
III. MATERIALS:
2.
AS NOTED
DAMPER MATERIAL
NO
5.
ALL MATERIALS SHALL BE NEW UNLESS OTHERWISE SHOWN OR SPECIFIED.
AS NOTED
PATTERN
PERF.
MECHANICAL CONTRACTOR IS TO EMPLOY THE SERVICES OF THE G.C. FOR CUTTING
AND PATCHING OF WALLS, FLOORS & CEILINGS RELATED TO THE INSTALLATION OF
MECHANICAL EQUIPMENT & SYSTEMS.
1.
A
FRAME
TYPE
LAY-IN
INSTALL ALL CONTROL DEVICES, INCLUDING THERMOSTATS AND SWITCHES, 4'-0"
ABOVE FINISHED FLOOR.
WATER HEATER VENT BY MECHANICAL CONTRACTOR.
MODULE
SIZE
24x24
4.
6.
NECK
SIZE
AS NOTED
SEAL ALL PENETRATIONS OF RATED WALLS, CEILING, FLOORS IN ACCORDANCE W/
APPROPRIATE U.L. PENETRATION DETAIL.
ALL GAS PIPING IS BY PLUMBING CONTRACTOR.
CFM
AS NOTED
3.
5.
4.
MECHANICAL CONTRACTOR SHALL VERIFY LOCATION OF ALL PENETRATIONS FOR
RELIEF HOODS, OUTSIDE AIR HOODS, LOUVERS, AND WALL CAPS WITH ARCHITECT &
OWNER PRIOR TO INSTALLATION.
ALL LOW VOLTAGE WIRING RELATED TO MECHANICAL EQUIPMENT AND SYSTEMS IS
THE RESPONSIBILITY OF THE MECHANICAL CONTRACTOR (ANY LOW VOLTAGE FIRE
ALARM WIRING TO BE BY E.C.). ALL HIGH VOLTAGE CONNECTIONS TO
MECHANICAL EQUIPMENT, TO BE PROVIDED AND INSTALLED BY E.C. (SEE
EQUIPMENT SCHEDULE FOR DISCONNECT RESPONSIBILITY).
G.C. RESPONSIBLE FOR PAINTING OF ANY EXPOSED DUCT, PIPING, GRILLES, ETC.
M.C. RESPONSIBLE FOR CLEANING AND PREPARING ITEMS FOR PAINT, COORDINATE
W/ G.C.
SYMBOL
C
13. M.C. IS TO PROVIDE TRAINING TO OWNER OR OWNER'S REPRESENTATIVE IN
REGARDS TO OPERATION, FUNCTION, AND MAINTENANCE OF ALL MECHANICAL
EQUIPMENT, CONTROLS, ETC.
II. DIVISION OF WORK:
DIFFUSER SCHEDULE
SUPPLY DIFFUSER/GRILLE OR RISER
3.
14. M.C. IS TO REVIEW COMPLETE DRAWING SET. M.C. IS RESPONSIBLE FOR WORK
EXPLICITLY SHOWN AND WORK IMPLIED.
THE MECHANICAL CONTRACTOR SHALL COORDINATE CLOSELY WITH ALL OTHER
TRADES TO AVOID CONFLICT AND ENSURE OTHER TRADES PROVIDE MEASURES TO
ACCOMMODATE MECHANICAL WORK (I.E. ACCESS DOORS, SLAB/WALL/ROOF
OPENINGS, ELECTRICAL CONNECTIONS, ETC).
ELBOW WITH TURNING VANES
8.
9.
SUPPORT ALL DUCTWORK AND PIPING IN ACCORDANCE W/ 2012 NC MECHANICAL
CODE. ANY SUSPENDED MATERIALS SHALL BE DIRECTLY SUPPORTED BY THE BUILDING
STRUCTURE.
PENETRATIONS OF ALL EXTERIOR WALLS, FLOORS AND CEILINGS SHALL BE SEALED IN
AN AIR TIGHT MANNER AND IN ACCORDANCE W/ 2012 NCECC APPENDIX 2
DETAILS. ALL PENETRATIONS OF WALLS, FLOORS & CEILINGS IN RETURN OR EXHAUST
PLENUMS SHALL BE SEALED IN AN AIR TIGHT MANNER.
10. DUCT ACCESS DOORS TO BE PROVIDED AT ALL FIRE, RADIATION & SMOKE
DAMPERS, SMOKE DETECTORS, CLEANOUTS AND ANY OTHER CODE REQUIRED
LOCATIONS.
11. THE MECHANICAL CONTRACTOR SHALL BE RESPONSIBLE FOR PROTECTING ALL
MECHANICAL EQUIPMENT FROM FOREIGN MATERIAL DURING CONSTRUCTION
(PAINT, SPACKLE, ETC.). UPON COMPLETION OF WORK THE MECHANICAL
CONTRACTOR SHALL CLEAN, WASH, ETC ALL ITEMS AND EQUIPMENT WITHIN HIS
SCOPE OF WORK AND LEAVE ALL ITEMS BRIGHT AND CLEAN.
NOTES:
GENERAL - MC RESPONSIBLE FOR VERIFYING QTY, COLOR & FRAME TYPE
OF DIFFUSERS/GRILLES BEFORE ORDERING. PROVIDE SQR TO RND
TRANSTIONS & PLENUMS AS NECESSARY.
2.
FINISH TO MATCH / BE ABLE MATCH CEILING OR WALL OR DOOR.
3.
FACTORY INSULATION BACKING ON GRILLES EXPOSED TO NON-CONDITIONED AREAS.
ALTERNATELY, FIELD SUPPLY AND INSTALL.
1.
4.
RETURN GRILLE TO BE USED AS A SUPPLY DEVICE FOR "AIR-DROP" EFFECT.
DIFFUSER DESIGNATIONS ON PLANS AS FOLLOWS:
DIFFUSER OR
DIFFUSER TYPE
NECK SIZE.
8x4
AS NOTED ABOVE
A
75
AIR QUANTITY
SD
DUCT SMOKE DETECTOR
AV
AUDIO/VISUAL ALARM
(W/ REMOTE TEST KEY SWITCH)
S
REMOTE TEMP SENSOR
P
REMOTE PULL STATION
1405 HILLSBOROUGH ST
RALEIGH, NC 27605
LIC.#: P-0990
P:919-341-4247
F:919-890-3797
plumbing mechanical electrical
3/4" DOOR UNDER CUT
EXISTING EQUIP. OR DUCT TO BE REMOVED
ENERGY REQUIREMENTS:
MECHANICAL SYSTEMS, SERVICE SYSTEMS AND EQUIPMENT
NOTE:
SEE HOOD & FAN
DRAWINGS FOR
ADDITIONAL INFO.
METHOD OF COMPLIANCE
PRESCRIPTIVE
ENERGY COST BUDGET
THERMAL ZONE
4A
EXTERIOR DESIGN CONDITIONS
WINTER DRY BULB
SUMMER DRY BULB
14
93
INTERIOR DESIGN CONDITIONS
WINTER DRY BULB
SUMMER DRY BULB
RELATIVE HUMIDITY
70
76
50%
BLDG 1
BUILDING HEATING LOAD (MBH)
145.9
BUILDING COOLING LOAD (MBH)
243.3
MECHANICAL SPACING CONDITIONING SYSTEM
UNITARY
DESCRIPTION OF UNIT
HEATING EFFICIENCY
COOLING EFFICIENCY
HEAT OUTPUT OF UNIT
COOLING OUTPUT OF UNIT
BOILER
TOTAL BOILER OUTPUT
CHILLER
TOTAL CHILLER OUTPUT
LIST EQUIPMENT EFFICIENCIES
SEE SCHEDULES
SEE SCHEDULES
SEE SCHEDULES
SEE SCHEDULES
SEE SCHEDULES
NA
NA
SEE SCHEDULES
DESIGNER'S STATEMENT:
TO THE BEST OF MY KNOWLEDGE AND BELIEF, THE DESIGN OF THIS BUILDING
COMPLIES WITH THE MECHANICAL SYSTEMS, SERVICE SYSTEMS AND EQUIPMENT
REQUIREMENTS OF THE N.C.S. ENERGY CODE.
SIGNED:
NAME: ZACK L. TOMLIN, PE
TITLE:
MECHANICAL ENGINEER
Project Number :LAG-1404
Drawn By: MJL, RDG, RSA
Date: 06-16-14
M-1
MECHANICAL
SCHEDULES
DETAILS
& NOTES
FIRE RATING LEGEND
1-HR WALL
GENERAL NOTES - THIS SHEET
1.
2.
3.
4.
5.
TAGGED NOTES - THIS SHEET
ITEMS SHOWN IN FAINT & HATCHED ARE TO BE DEMO'D OR
RELOCATED. ITEMS SHOWN IN FAINT ARE EXISTING TO
REMAIN. NEW OR RELOCATED ITEMS ARE SHOWN IN BOLD.
SEE LEGEND.
ENSURE THAT ALL SOURCES OF BUILDING EXHAUST ARE A
MINIMUM OF 10' HORIZONTALLY FROM OR A MINIMUM OF
3' ABOVE ANY AREA OUTSIDE AIR INTAKES.
M.C. TO SEE HOOD & FAN DRAWINGS FOR ADDITIONAL
INFORMATION.
M.C. TO SEE ROOF PLAN FOR ADDITIONAL INFORMATION.
CENTERLINE OF EXPOSED DUCTWORK TO BE AT EQUAL
ELEVATION. CONFIRM ELEVATION W/ ARCHITECT.
1
3/4" DOOR UNDERCUT.
2
PROVIDE DUCT MOUNTED SMOKE DETECTOR. SEE
DETAIL.
3
8x8 EXHAUST DUCT UP TO FAN ON ROOF.
4
COORDINATE EXACT LOCATION OF ROOF EQUIPMENT W/
STRUCTURE BELOW.
5
INSTALL WATER HEATER VENT TO ROOF. SIZE AND INSTALL
PER WATER HEATER MFG'S INSTRUCTIONS.
6
REMOVE EXISTING SHELL SPACE UNIT HEATER.
TURNOVER TO LANDLORD.
7
PROVIDE DRAIN FROM COOLER EVAPORATOR TO
GRADE AWAY FROM FOOT TRAFFIC.
8
REMOTE PULL STATION FOR HOOD FIRE SUPPRESSION
SYSTEM. SEE DETAIL. COORD. EXACT LOCATION W/
LOCAL AHJ.
9
NO CEILING AT WATER HEATER. COORDINATE W/ G.C..
10
RETURNS ON BULKHEAD. MOUNT AS HIGH AS POSSIBLE.
11
SUPPLY DIFFUSERS HIDDEN FROM VIEW BY RTU-1. SEE
FRONT KITCHEN MECHANICAL PLAN FOR MORE DETAIL.
12
FLY FAN ABOVE REAR DOOR.
13
18x16 DN FROM KSF ON ROOF. PROVIDE MITERED
ELBOW W/ TURNING VANES AT VERTICAL TO
HORIZONTAL BEND.
14
10x10 GREASE EXHAUST DOWN TO HOOD. TRANSITION
AT HOOD AS NECESSARY.
15
16x16 GREASE EXHAUST DOWN TO HOOD. TRANSITION
AT HOOD AS NECESSARY.
16
SUPPLY TAP DOWN TO HOOD CONNECTION.
COORDINATE EXACT QTY, SIZE AND CFM OF TAPS W/
HOOD MFG AND DRAWINGS. TYPICAL.
17
SEE ENLARGED DRAWING FOR HOOD LAYOUT.
EQUIPMENT SCHEDULE
ITEM
#
QTY.
DESCRIPTION
2
1
CHAR-BROILER
2.1
1
COUNTER TOP GRIDDLE
3
1
REFRIGERATED EQUIPMENT STAND
4
1
2-BURNER RANGE W/ GRIDDLE
5
1
COUNTER TOP GRIDDLE
16
1
DOUBLE DECK CONVECTION OVEN
17
1
KETTLE ON STAND
18
B 50
16
18x16
F
75
3
5
2.1
(RTU-2)
C 150
DINING AREA 3
DINING AREA 4
WOMEN
1
B 50
17
18
A 12x6
300
KEF-2
18
A 12x6
300
F
16
A 24x4
400
A 24x4
400
A 12x6
300
18
C 180
WH-1
A 20x4
350
14x4 A
200
10
D 24x14
1600
EMG
12
FF-1
SCALE: 1/4" = 1'-0"
BACK
HALL
10
6
5
9
FRONT KITCHEN
H 500
KSF-3
11
C 400
RTU-1
11
KEF-2
(RTU-1)
(RTU-2)
(RTU-3)
(RTU-3)
HD-2
DINING AREA 1
17
(HD-1&2)
(RTU-1)
24x20
1
C 120
2
11
2
OFFICE
16x14
24x18
20x14
400 C
4
22x18
(2) E
750
(RTU-1)
(RTU-2)
(RTU-3)
D 30x18
2300
24x18
4
RTU-2
PARTIAL MECH. PLAN - KITCHEN
CUSTOMER QUEUE
EXIST
UH
20x14
8
A 24x4
400
18
A 24x4
400
H 500
7
KEF-1
CATERING
STORAGE
14x14
14x14
20x18
HD-2
RTU-3
2
(2) E
750
C 200
C 200
H 300
4
A 12x6
300
18
A 12x6
300
H 300
Project Number :LAG-1404
Drawn By: MJL, RDG, RSA
Date: 06-16-14
M-2
FROM RTU-3
MECH. PLAN - FRONT KITCHEN
PREP KITCHEN/
DRY STORAGE
HD-1
200 C
SCALE: 1/4" = 1'-0"
A 24x4
400
plumbing mechanical electrical
75
CAN WASH
2
18
A 24x4
400
18
TO GO
ORDERS
H 500
DINING AREA 2
14
HD-1
H 500
1405 HILLSBOROUGH ST
RALEIGH, NC 27605
LIC.#: P-0990
P:919-341-4247
F:919-890-3797
EF-1
18
KEF-1
3
ENGINEERING, pllc
4
2
15
HD-2
maple
HALL
MEN
3
KSF-3
STORAGE
1
16x14
13
6/16/14
1
MECHANICAL PLAN
SCALE: 1/4" = 1'-0"
MECHANICAL
PLAN
TAGGED NOTES - THIS SHEET
1
KSF DUCT UP/DOWN FROM SUPPLY FAN ON ROOF.
2
GREASE EXHAUST DUCT UP TO FAN ON ROOF. MAINTAIN
REQ'D CLEARANCES OR WRAP DUCT, SEE DETAIL. PROVIDE
WINDBAND EXTENSION(S) TO BRING EXHAUST A MINIMUM
OF 3' ABOVE AREA OUTSIDE AIR INTAKES.
3
GREASE EXHAUST DUCT UP TO FAN ON ROOF. MAINTAIN
REQ'D CLEARANCES OR WRAP DUCT, SEE DETAIL. PROVIDE
WINDBAND EXTENSION(S) TO BRING EXHAUST A MINIMUM
OF 3' ABOVE AREA OUTSIDE AIR INTAKES.
4
EXHAUST DUCT UP TO FAN ON ROOF. SEE DETAIL.
5
ENSURE THAT ROOF MOUNTED EQUIPMENT IS A MINIMUM
OF 6' FROM ROOF EDGE IF PARAPET WALL IS LESS THAN
42" IN HEIGHT.
GENERAL NOTES - THIS SHEET
1.
2.
ENSURE THAT ALL SOURCES OF BUILDING EXHAUST ARE A
MINIMUM OF 10' HORIZONTALLY FROM OR A MINIMUM OF
3' ABOVE ANY AREA OUTSIDE AIR INTAKES.
M.C. TO SEE HOOD & FAN DRAWINGS FOR ADDITIONAL
INFORMATION.
6/16/14
maple
ENGINEERING, pllc
1405 HILLSBOROUGH ST
RALEIGH, NC 27605
LIC.#: P-0990
P:919-341-4247
F:919-890-3797
EF-1
4
plumbing mechanical electrical
5
WH-1
VENT
RTU-2
RTU-1
1
KSF-3
3
2
KEF-2
KEF-1
RTU-3
Project Number :LAG-1404
Drawn By: MJL, RDG, RSA
Date: 06-16-14
M-3
1
MECH. PLAN - ROOF
SCALE: 1/4" = 1'-0"
MECHANICAL
PLAN ROOF
WINDBAND EXTENSION.
EXTENSION(S) TO BRING
EXHAUST A MINIMUM OF 3'
ABV AREA OA INTAKES.
BOLTED, FLANGED,
GASKETED DUCT
CONNECTION.
ADJUSTABLE AIR
SCOOP/DAMPER.
FURNISHED W/ REGISTER.
VENTED CURB
EXTENSION
EXHAUST DUCT FLANGE
FASTENED TO NAILOR
ADJUSTABLE DEFLECTION
BLADES (DOUBLE) FRONT
BLADES PARALLEL TO SHORT
DIMENSION.
FLASHING
G
GAS PIPING ON ROOF
DRIP LEG BY P.C.
SD
SEAL ALL DUCTWORK
OPENINGS WITH NONHARDENING MASTIC.
DUCT MOUNTED SMOKE
PROVIDED BY E.C., INSTALLED IN
DUCT BY M.C., WIRED TO BLDG
FA SYSTEM BY E.C. ENSURE
DETECTOR IS DOWN STREAM OF
ALL RETURN TAPS, UPSTREAM OF
OA CONNECTION AND WIRED
TO UNIT SHUT DOWN, SPACE AV
ALARM & BLDG FIRE ALARM
SYSTEM.
FLEX CONN.
NOTED.
BACK DRAFT DAMPER
TWO (2) SETS OF ADJUSTABLE
FINS.
GRILLE HEIGHT
3"
4"
6"
8"
10"
12"
FLUSH MOUNTED SUPPLY AIR
REGISTER.
GASKET
EXHAUST DUCT
SUPPLY AIR DUAL OR SINGLE
WALL DUCT.
7
GAS SHUT-OFF VALVE
BY PLUMBING CONTR.
FLASHING
LIQUID TIGHT FLEX.
CONDUIT (BY E.C.)
FLASHING
& COUNTER-FLASHING
NOTE:
REGISTER(S) TO BE
LOCATED AT THE 3 & 9
O'CLOCK POSITIONS.
BLADE SPREAD TO BE SET
1" CONDENSATE
TO SPLASH BLOCK
2" RIGID INSUL.
EXH. FAN DETAIL (ROOF)
6
NO SCALE
WELDED SEAM EXHAUST DUCT
(W/ FIRE WRAP IF NECESSARY)
6"
8"
10"
12"
14"
16"
ROOF STRUCTURE.
COORDINATE OPENING
SIZE W/ DUCT CLEARANCE
REQ'S.
NOTE:
FAN DISCHARGE TO BE A MIN. OF 10' AWAY
HORIZONTALLY FROM ANY NON-PARAPET
PARTS OF THE BUILDING STRUCTURE AND ANY
OUTSIDE AIR INTAKES.
SPIRAL DUCT REGISTER (FLUSH)
5
NO SCALE
PROVIDE ACOUSTIC
DUCT LINER FIRST 10' FROM
DISCHARGE AND INTAKE.
GREASE EXHAUST FAN DETAIL
4
NO SCALE
PROVIDE 3 ALT. LAYERS OF 5/8"
G.W.B. & 1" RIGID INSULATION.
SEAL AND STAGGER ALL SEAMS.
GAS/ELECTRIC ROOFTOP UNIT
NO SCALE
APPROVED
GRAVITY AND WIND
INDUCED VENTILATOR
KITCHEN HOOD NOTES
1.
DRAW BAND - 16GA. BLACK
STEEL OR WELDED SEAM
2.
KITCHEN EXHAUST DUCT TO BE CONSTRUCTED OF MIN. 16 GAUGE
STEEL. JOINTS TO BE CONTINUOUS EXTERNAL LIQUID-TIGHT WELDS.
3.
EXHAUST DUCT TO SLOPE BACK TO HOOD OR APPROVED GREASE
RESERVOIR. DUCT TO MAINTAIN MIN. 2% SLOPE FOR DUCT SYSTEMS 75'
OR LESS IN LENGTH AND 8.3% SLOPE FOR DUCT SYSTEMS GREATER
THAN 75' IN LENGTH.
11 GAUGE BLACK STEEL WELDED
CONSTRUCTION ROUND TO SQUARE
TRANSITION STORM COLLAR/FLASHING
MIN HEIGHT = 2'-0"
OR 2'-0" ABV ANY
PART OF BLDG WITHIN
10'-0". WHICHEVER IS GREATER.
ROOF
ALL GREASE EXHAUST WORK IS TO BE DONE IN ACCORDANCE W/
2012 NCMC SEC 506 & ALL OTHER APPLICABLE CODES. M.C. IS TO
REVIEW REQUIREMENTS OF 2012 NCMC SEC 506 BEFORE BEGINNING
WORK.
4.
ALL BENDS TO BE RADIUS THROAT AND RADIUS BACK TYPE. CENTER
LINE RADIUS 1.0 TIMES DUCT DIMENSION OR GREATER.
5.
CLEANOUTS TO BE PROVIDED WITHIN 10' OF ALL CHANGES IN DUCT
DIRECTION & EVERY 20' ON CENTER IN HORIZONTAL RUNS. CONSULT
LOCAL CODES REGARDING ADDITIONAL CLEANOUT LOCATIONS,
CLEANOUT PROTECT, SIZING, AND ORIENTATION ON DUCT.
6.
INSULATION
INSULATION SHIELD
COORD. EXACT CLEARANCE W/ FLUE MFG
ALL GREASE EXHAUST DUCT(S) IS TO BE INSTALLED PER CODE
REQUIREMENTS REGARDING CLEARANCE, DUCT ENCLOSURES, AND
ACCESS. 18" CLEARANCE IS TO BE MAINTAINED FROM DUCT TO
SURROUNDING COMBUSTIBLE CONSTRUCTION AND 3" CLEARANCE IS
TO BE MAINTAINED FROM NON-COMBUSTIBLE CONSTRUCTION (6"
REQ'Q FOR DUCT ENCLOSURES). SOME CLEARANCE OR DUCT
ENCLOSURE REQUIREMENTS MAY BE OMITTED THROUGH THE USE OF
APPROVED DUCTWRAP/FIREWRAP. DUCTWRAP USED FOR
CLEARANCE REDUCTION AROUND GREASE DUCT TO BE 2-LAYERS OF
"3M FIRE BARRIER DUCT WRAP 615+" OR EQUAL, CONSULT LOCAL AHJ.
NOTES:
1. EXTEND FLASHING TO "SEAM TO SEAM" FOR INSTALLATION
ON STANDING SEAM METAL ROOFS.
7.
ALL DUCTWRAP/FIREWRAP OR SIMILAR IS TO BE INSTALLED PER MFG.
RECOMMENDATIONS.
2.
ENSURE FLUE IS 10' FROM ANY BUILDING AIR INTAKES.
8.
3.
FLUE MAY REQUIRE ADDITIONAL BRACING IN HIGH WIND AREAS.
4.
SEAL AROUND FLUE & FLASHING AS REQUIRED.
GC IS TO PROVIDE RATED ENCLOSURE (WHEN NEEDED) WITH RATED
ACCESS DOORS AS REQUIRED. GC TO SPACE STRUCTURE TO
ACCOMMODATE DUCTS WITH WRAP, DUCT ENCLOSURES, AND
ACCESS DOORS AS NECESSARY.
9.
3
GAS FLUE DETAIL
NO SCALE
HOOD TO BE INSTALLED SUCH THAT CODE REQUIRED MIN. DISTANCE
BETWEEN LOWEST EDGE OF GREASE FILTER(S) AND
COOKING/HEATING SURFACE IS NOT VIOLATED. MIN. DISTANCE
EQUALS 12" FOR SURFACES WITH NO EXPOSED FLAME, 24" FOR
SURFACES WITH EXPOSED FLAME AND BURNERS & 42" FOR EXPOSED
CHARCOAL AND CHARBROIL TYPE SURFACES. LOWEST EDGE OF
HOOD MUST NOT BE MORE THAN 48" FROM COOKING SURFACE(S).
10. HOOD CAPTURE SIZED BASED UPON EQUIPMENT SCHEDULED TO BE
UNDER HOOD PLUS MIN. 6" OVERHANG ON ALL EXPOSED SIDES PER
CODE. FIELD VERIFY & COORDINATE ACTUAL FURNISHED EQUIPMENT
WITH SPECIFIED HOOD SIZE.
VOLUME DAMPER WITH
3/8" LOCKING QUADRANT
AND END BEARING.
(WHERE ACCESIBLE)
SUPPLY AIR DUCT.
ROUND SHEET
METAL DUCT.
FLEX DUCT
DIAMETER "D"
NOTE:
FLEX DUCT TURN INTO DIFFUSER TO BE REPLACED
BY INSULATED SHEET METAL ELBOW FOR (3)
FARTHEST CEILING DIFFUSERS FROM AIR
HANDLER.
11. EXHAUST DUCT CONNECTION TO HOOD TO BE CONTINUOUS LIQUID
TIGHT WELD. ALTERNATE GASKETED BOLT TYPE CONNECTION IS
PERMISSIBLE IF ALLOWED BY LOCAL CODES. ALTERNATE CONNECTION
MUST BE MADE EXACTLY AS DIRECTED BY LOCAL CODES.
12. MC TO VERIFY EXACT DIMENSIONS OF HOOD EXHAUST AND MAKE UP
AIR CONNECTION WITH HOOD MFG. PRIOR TO FABRICATION OR
ORDERING OF RELATED EQUIPMENT (BALANCING DAMPERS, ETC.)
13. HOOD MUST MEET U.L. 710.
FLARED SHOULDER &
SPIN IN COLLAR W/
INTEGRAL SCOOP.
CIRCULAR CLAMP
TYP.
FINISHED
CEILING SURFACE
REDUCER OR
SQUARE TO ROUND
TRANSITION
(IF NECESSARY)
DIFFUSER/GRILLE
(COORD. FRAME TYPE)
NOTES:
1. PROVIDE INSULATED REGISTER BOOT/PLENUM BOX IF NECESSARY.
2. RETURN APPLICATION IS SIMILAR. ALL ELBOWS IN RETURN APPLICATION
TO BE INSULATED SHEET METAL (NO FLEX ELBOWS).
2
DIFFUSER DETAIL
NO SCALE
14. KITCHEN EQUIPMENT SERVED BY HOOD INTERLOCKED WITH HOOD
CONTROLS. OPERATION OF KITCHEN EQUIPMENT TO BE IMPOSSIBLE
WITHOUT OPERATION OF HOOD EXHAUST FAN. HOOD ACTIVATION BY
TEMPERATURE SENSOR IS ACCEPTABLE ALTERNATIVE.
KITCHEN HOOD FIRE SUPPRESSION SYSTEM
EXHAUST FAN NOTES
PROVIDE A PRE-ENGINEERED, WET CHEMICAL W/ WATER ASSIST FIRE PROTECTION SYSTEM EQUAL TO
ANSUL R102 SYSTEM, DESIGNED IN COMPLIANCE WITH UL300 REQUIREMENTS. THE SYSTEM SHALL BE
CAPABLE OF AUTOMATIC DETECTION AND REMOTE ACTUATION. THE SYSTEM SHALL BE IN ACCORDANCE
WITH NFPA 96 AND LOCAL AHJ. DISCHARGE NOZZLES WILL PROVIDE COVERAGE OF, BUT NOT LIMITED TO,
THE HOOD AREA AND EXHAUST DUCT. FURNISH ELECTRIC OPERATED GAS SHUT OFF VALVE.
NORMAL TEMPERATURE TEST
EXHAUST FAN MUST OPERATE CONTINUOUSLY
UNTIL ALL FAN PARTS HAVE REACHED
THERMAL EQUILIBRIUM, AND WITHOUT ANY
DETERIORATING EFFECTS TO THE FAN WHICH
WOULD CAUSE UNSAFE OPERATION.
HOOD FIRE SUPPRESSION SEQUENCE OF OPERATION:
UPON ACTIVATION OF THE KITCHEN HOOD FIRE SUPPRESSION
SYSTEM ALL HOOD MAKE-UP AIR FANS AND KITCHEN RTU SUPPLY
FANS ARE TO SHUT DOWN, HOOD EXHAUST FANS ARE TO
ACTIVATE, GAS SOLENOID VALVE IS TO CLOSE, EQUIPMENT
SHUNT TRIP BREAKER(S)/CONTACTOR(S) ARE TO TURN "OFF" AND
A ALARM SIGNAL IS TO BE SENT TO THE BUILDING FIRE ALARM
SYSTEM CONTROL PANEL.
15 MINUTES WITHOUT THE FAN BECOMING
DAMAGED TO ANY EXTENT THAT COULD CAUSE
AN UNSAFE CONDITION.
U.L. LISTED HOOD EXHAUST FAN
W/ FACTORY CONTROL PACKAGE & STARTER
SEE SCHEDULE FOR SPECIFICATION.
AIR INLET OPENING
maple
10'-0" MIN.
ENGINEERING, pllc
1405 HILLSBOROUGH ST
RALEIGH, NC 27605
LIC.#: P-0990
P:919-341-4247
F:919-890-3797
KEF
U.L. LISTED HOOD MAKE-UP AIR FAN
W/ FACTORY CONTROL PACKAGE & STARTER
SEE SCHEDULE FOR SPECIFICATION.
GREASE DRAIN ON FAN
& APPROVED COLLECTION
RESEVOIR
plumbing mechanical electrical
PREFABRICATED CURB
MUA
SEAL OPENING AROUND
DUCT WITH KAOWOOL
FLANGED & GASKETED
DUCT TO FAN CONNECTION
AIR INTAKE
W/ FILTER
NOTE:
DETAIL IS SCHEMATIC IN
NATURE. SEE DWG'S FOR
LOCATION OF FAN'S AND
DUCT LAYOUT.
MAKE-UP AIR DUCT
EXHAUST
DUCT TO FAN
STEEL ANGLE
ATTACHED TO
STRUCTURE
KITCHEN CEILING
(NON-COMBUSTIBLE TILES
WITHIN 18" OF HOOD)
SUPPLY RISER WITH
INTERNAL VOLUME
DAMPERS
STEEL
HANGING RODS
MFG. SUPPLY PLENUM
PERF. PLATES
ACCESS DOOR
(SEE NOTES)
STAINLESS STEEL CLOSURE PANEL TO CLG.
STEEL HANGING
ANGLE
AIR FLOW
PERFORATED PLATES
U.L LISTED
BAFFLE TYPE
GREASE FILTERS
EXH. CONNECTION TO
HOOD (SEE NOTES)
GREASE DRAIN WITH
REMOVABLE CUP
3" STAND-OFF
TYPE I KITCHEN EXHAUST
HOOD W/ WET
CHEMICAL FIRE
SUPPRESSION SYSTEM.
BACK WALL TO BE
OF LIMITED OR
NON-COMBUSTIBLE CONST.
HOOD FAN AND LIGHT CONTROLS
FACTORY FIRE SYSTEM CONTROL
BOX TO BE MOUNTED WITHIN
75 FEET OF HOOD AND BELOW
CEILING LEVEL. CABINET MAY
BE INCLUDED IN CONTROL PANEL
ATTACHED TO END OF HOOD.
LIGHTS
PRE-WIRED BY HOOD MGF
(50 F.C. OF ILLUMINATION
REQ'D AT ALL COOKING
SURFACES)
P
REMOTE PULL STATION(S). COORDINATE
EXACT DEVICE & PLACEMENT WITH LOCAL
AHJ AND REQUIREMENTS OF 2012 NC FIRE
CODE SECTION 904.11
NOTE: ADDITIONAL STRUCTURAL BRACING
FOR HOOD SUPPORT PROVIDED BY OTHERS.
SEE ARCHITECTURAL DRAWINGS FOR MORE
INFORMATION.
15. MC RESPONSIBLE FOR VIEWING ALL OTHER APPLICABLE KITCHEN
PLANS FROM KITCHEN EQUIPMENT PROVIDER AND ARCHITECT PRIOR
TO BEGINNING WORK. MC TO MAKE KNOWN ANY SIGNIFICANT
DISCREPANCIES BETWEEN PLANS TO G.C., ARCHITECT OR ENGINEER.
STAINLESS STEEL PANEL TO FLOOR
BY OTHERS. SEE ARCH. DRAWINGS.
NOTE: GAS SOLENOID VALVE
TO BE PROVIDED BY FIRE SUPPRESSION CONTRACTOR
AND INSTALLED BY P.C.
FINAL CONNECTION BY FIRE SUP. CONTRACTOR.
16. PRIOR TO USE OR CONCEALMENT OF ANY PORTION OF THE GREASE
DUCT SYSTEM A LEAKAGE TEST SHALL BE PERFORMED IN THE PRESENCE
OF THE LOCAL AHJ. TEST TO BE PERFORMED AS OUTLINED IN 2012
NCMC SEC. 506.3.2.5.
17. AFTER INSTALLATION MC TO PERFORM BOTH "PERFORMANCE" AND
"CAPTURE AND CONTAINMENT" TESTS IN THE PRESENCE OF THE LOCAL
AHJ. SEE 2012 NCMC SEC. 507.16.
6/16/14
ABNORMAL FLARE-UP TEST
EXHAUST FAN MUST OPERATE CONTINUOUSLY
WHILE EXHAUSTING BURNING GREASE VAPORS
NOTE: SEE HOOD/FAN MFG DRAWINGS FOR MORE INFO.
40" MIN.
MFG. ROOF CURB
W/ 1" INSUL. & NAILOR
FRESH AIR INLET
PREFABRICATED
ROOF CURB.
18"
MIN.
MFG. ROOF CURB
W/ NAILOR
ANCHOR REGISTER TO DUCT
HIGH DENSITY
GASKET 2" WIDE.
MIN. DISTANCE = 40"
OR PARAPET HEIGHT
NEMA 3R
(IF WITHIN 5')
DISCONNECT WHICHEVER IS
GREATER.
GREASE TRAP
EXHAUST FAN
WEATHER HOOD WITH
FILTER ACCESS PANEL.
ROOF TOP MOUNTED
AIR HANDLING UNIT.
UP-BLAST KITCHEN
EXHAUST FAN
Project Number :LAG-1404
Drawn By: MJL, RDG, RSA
Date: 06-16-14
M-4
1
KITCEN HOOD DETAIL (TYPE 1, WALL)
NO SCALE
MECHANICAL
DETAILS
NOTE:
VERIFY WRAPPER HEIGHTS
W/ ARCHITECT & CEILING
HEIGHTS.
6/16/14
maple
ENGINEERING, pllc
1405 HILLSBOROUGH ST
RALEIGH, NC 27605
LIC.#: P-0990
P:919-341-4247
F:919-890-3797
plumbing mechanical electrical
NOTE:
SEE ADDITIONAL HOOD
DRAWINGS &
MECHANICAL DRAWINGS
FOR ADDITIONAL
INFORMATION.
NOTE:
HOOD & FAN DESIGN IS
BY OTHERS. HOOD & FAN
INFORMATION SUPPLIED
BY OTHERS AND
PRESENTED ON THIS
DRAWING HAS ONLY BEEN
REVIEWED TO THE EXTENT
OF IT'S ACCEPTABILITY
GIVEN THE REQUIREMENTS
OF THE OVERALL
MECHANICAL SYSTEM.
MASTER DRAWING
Project Number :LAG-1404
Drawn By: MJL, RDG, RSA
Date: 06-16-14
HD-1
HOOD
DRAWINGS
6/16/14
maple
ENGINEERING, pllc
1405 HILLSBOROUGH ST
RALEIGH, NC 27605
LIC.#: P-0990
P:919-341-4247
F:919-890-3797
plumbing mechanical electrical
NOTE:
SEE ADDITIONAL HOOD
DRAWINGS &
MECHANICAL DRAWINGS
FOR ADDITIONAL
INFORMATION.
NOTE:
HOOD & FAN DESIGN IS
BY OTHERS. HOOD & FAN
INFORMATION SUPPLIED
BY OTHERS AND
PRESENTED ON THIS
DRAWING HAS ONLY BEEN
REVIEWED TO THE EXTENT
OF IT'S ACCEPTABILITY
GIVEN THE REQUIREMENTS
OF THE OVERALL
MECHANICAL SYSTEM.
MASTER DRAWING
Project Number :LAG-1404
Drawn By: MJL, RDG, RSA
Date: 06-16-14
HD-2
HOOD
DRAWINGS
6/16/14
maple
ENGINEERING, pllc
1405 HILLSBOROUGH ST
RALEIGH, NC 27605
LIC.#: P-0990
P:919-341-4247
F:919-890-3797
plumbing mechanical electrical
NOTE:
SEE ADDITIONAL HOOD
DRAWINGS &
MECHANICAL DRAWINGS
FOR ADDITIONAL
INFORMATION.
NOTE:
HOOD & FAN DESIGN IS
BY OTHERS. HOOD & FAN
INFORMATION SUPPLIED
BY OTHERS AND
PRESENTED ON THIS
DRAWING HAS ONLY BEEN
REVIEWED TO THE EXTENT
OF IT'S ACCEPTABILITY
GIVEN THE REQUIREMENTS
OF THE OVERALL
MECHANICAL SYSTEM.
MASTER DRAWING
Project Number :LAG-1404
Drawn By: MJL, RDG, RSA
Date: 06-16-14
HD-3
HOOD
DRAWINGS
6/16/14
maple
ENGINEERING, pllc
1405 HILLSBOROUGH ST
RALEIGH, NC 27605
LIC.#: P-0990
P:919-341-4247
F:919-890-3797
plumbing mechanical electrical
NOTE:
SEE ADDITIONAL HOOD
DRAWINGS &
MECHANICAL DRAWINGS
FOR ADDITIONAL
INFORMATION.
NOTE:
HOOD & FAN DESIGN IS
BY OTHERS. HOOD & FAN
INFORMATION SUPPLIED
BY OTHERS AND
PRESENTED ON THIS
DRAWING HAS ONLY BEEN
REVIEWED TO THE EXTENT
OF IT'S ACCEPTABILITY
GIVEN THE REQUIREMENTS
OF THE OVERALL
MECHANICAL SYSTEM.
MASTER DRAWING
Project Number :LAG-1404
Drawn By: MJL, RDG, RSA
Date: 06-16-14
HD-4
HOOD
DRAWINGS
NOTE:
PROVIDE WINDBANDS AS
NECESSARY ON FANS TO
ENSURE THAT EXHAUST
TERMINATION IS AT LEAST
36" ABOVE AREA OUTSIDE
AIR INTAKES.
6/16/14
maple
ENGINEERING, pllc
1405 HILLSBOROUGH ST
RALEIGH, NC 27605
LIC.#: P-0990
P:919-341-4247
F:919-890-3797
plumbing mechanical electrical
NOTE:
SEE ADDITIONAL HOOD
DRAWINGS &
MECHANICAL DRAWINGS
FOR ADDITIONAL
INFORMATION.
NOTE:
HOOD & FAN DESIGN IS
BY OTHERS. HOOD & FAN
INFORMATION SUPPLIED
BY OTHERS AND
PRESENTED ON THIS
DRAWING HAS ONLY BEEN
REVIEWED TO THE EXTENT
OF IT'S ACCEPTABILITY
GIVEN THE REQUIREMENTS
OF THE OVERALL
MECHANICAL SYSTEM.
MASTER DRAWING
Project Number :LAG-1404
Drawn By: MJL, RDG, RSA
Date: 06-16-14
HD-5
HOOD
DRAWINGS
6/16/14
maple
ENGINEERING, pllc
1405 HILLSBOROUGH ST
RALEIGH, NC 27605
LIC.#: P-0990
P:919-341-4247
F:919-890-3797
plumbing mechanical electrical
NOTE:
SEE ADDITIONAL HOOD
DRAWINGS &
MECHANICAL DRAWINGS
FOR ADDITIONAL
INFORMATION.
NOTE:
HOOD & FAN DESIGN IS
BY OTHERS. HOOD & FAN
INFORMATION SUPPLIED
BY OTHERS AND
PRESENTED ON THIS
DRAWING HAS ONLY BEEN
REVIEWED TO THE EXTENT
OF IT'S ACCEPTABILITY
GIVEN THE REQUIREMENTS
OF THE OVERALL
MECHANICAL SYSTEM.
MASTER DRAWING
Project Number :LAG-1404
Drawn By: MJL, RDG, RSA
Date: 06-16-14
HD-6
HOOD
DRAWINGS
6/16/14
maple
ENGINEERING, pllc
1405 HILLSBOROUGH ST
RALEIGH, NC 27605
LIC.#: P-0990
P:919-341-4247
F:919-890-3797
plumbing mechanical electrical
NOTE:
SEE ADDITIONAL HOOD
DRAWINGS &
MECHANICAL DRAWINGS
FOR ADDITIONAL
INFORMATION.
NOTE:
HOOD & FAN DESIGN IS
BY OTHERS. HOOD & FAN
INFORMATION SUPPLIED
BY OTHERS AND
PRESENTED ON THIS
DRAWING HAS ONLY BEEN
REVIEWED TO THE EXTENT
OF IT'S ACCEPTABILITY
GIVEN THE REQUIREMENTS
OF THE OVERALL
MECHANICAL SYSTEM.
MASTER DRAWING
Project Number :LAG-1404
Drawn By: MJL, RDG, RSA
Date: 06-16-14
HD-7
HOOD
DRAWINGS
6/16/14
maple
ENGINEERING, pllc
1405 HILLSBOROUGH ST
RALEIGH, NC 27605
LIC.#: P-0990
P:919-341-4247
F:919-890-3797
plumbing mechanical electrical
NOTE:
SEE ADDITIONAL HOOD
DRAWINGS &
MECHANICAL DRAWINGS
FOR ADDITIONAL
INFORMATION.
NOTE:
HOOD & FAN DESIGN IS
BY OTHERS. HOOD & FAN
INFORMATION SUPPLIED
BY OTHERS AND
PRESENTED ON THIS
DRAWING HAS ONLY BEEN
REVIEWED TO THE EXTENT
OF IT'S ACCEPTABILITY
GIVEN THE REQUIREMENTS
OF THE OVERALL
MECHANICAL SYSTEM.
MASTER DRAWING
Project Number :LAG-1404
Drawn By: MJL, RDG, RSA
Date: 06-16-14
HD-8
HOOD
DRAWINGS
GENERAL ELECTRICAL NOTES
9.
SPLICING CONNECTORS, LUGS, ETC SHALL BE IDENTIFIED FOR USE
WITH THE MATERIAL (CU/AL) OF THE CONDUCTOR AND SHALL BE
PROPERLY INSTALLED.
10.
RECEPTACLES IN COMMERCIAL AREAS SHALL BE 20 AMP
COMMERCIAL SPECIFICATION GRADE EQUAL TO HUBBELL SERIES.
GROUND FAULT RECEPTACLES SHALL BE EQUAL TO COOPER VGF
SERIES.
A
LITHONIA
2SP8 G
3
32W T8
B
6.
DO NO SCALE DRAWINGS FOR MEASUREMENT.
7.
INFORMATION GIVEN IN SCHEDULES INCLUDES BOTH DESCRIPTION
OF PRODUCT AND MANUFACTURER'S MODEL #. IF CONFLICT IS
PRESENT BETWEEN DESCRIPTION AND MODEL #, EQUIPMENT
DESCRIPTION SHALL TAKE PRECEDENT. IN CASE OF CONFLICT
BETWEEN THE PLANS AND NOTES/SPECIFICATIONS OR CONFLICT
BETWEEN INFORMATION PRESENTED ON THE PLANS OR IN THE
NOTES/SPECIFICATIONS, THEN THE MOST RESTRICTIVE SHALL TAKE
PRECEDENT.
8.
9.
BEFORE BID EC IS RESPONSIBLE FOR CLARIFYING W/ G.C. ANY
CONFUSION IN REGARDS TO RESPONSIBILITY OF WORK TO BE
PERFORMED OR MATERIALS TO BE PROVIDED. THE SUBMITTAL OF THE
BID BY THE CONTRACTOR WILL BE HELD AS PROOF THAT THE
CONTRACTOR UNDERSTANDS THOROUGHLY AND COMPLETELY THE
SCOPE OF THE WORK INVOLVED, AND HAS INCLUDED ON THE BID
ALL THE NECESSARY ITEMS TO CARRY OUT THIS SECTION OF WORK.
AS SOON AS POSSIBLE (AND NOT MORE THAN 30 DAYS) AFTER
CONTRACT IS SIGNED, THE EC SHALL PROVIDE SUBMITTALS OF
EQUIPMENT HE/SHE INTENDS TO PURCHASE FOR REVIEW AND
COMMENT BY THE ENGINEER. ENGINEER IS TO APPROVE SUBMITTALS
BEFORE EQUIPMENT IS ORDERED.
10. ALL EXISTING EQUIPMENT AND SYSTEMS ARE ASSUMED BY ENGINEER
TO BE IN GOOD WORKING ORDER. BEFORE BEGINNING WORK E.C.
IS TO ENSURE ANY EQUIPMENT & SYSTEMS TO REMAIN ARE PROPERLY
FUNCTIONING. NOTIFY G.C. IMMEDIATELY IF PROBLEMS ARE
DISCOVERED.
11. ALL QUESTIONS MUST BE SUBMITTED IN RFI FORMAT TO THE
ARCHITECT AND MUST BE ADDRESSED BY THE APPROPRIATE
DESIGNER OF RECORD PRIOR TO BECOMING A PROPOSED CHANGE
ORDER.
12. E.C. IS TO REVIEW COMPLETE DRAWING SET. E.C. IS RESPONSIBLE FOR
WORK EXPLICITLY SHOWN AND WORK IMPLIED. UNLESS OTHERWISE
NOTED FINAL ELECTRICAL CONNECTION TO ALL EQUIPMENT,
FURNITURE (I.E. CUBICLES, WORKSTATIONS, ETC) IS THE RESPONSIBILITY
OF THE E.C..
11.
12.
2.
3.
ALL ROOF WORK INCLUDING PENETRATIONS, OPENINGS, FLASHING,
CURB INSTALLS, ETC ARE TO BE PERFORMED BY ROOFING
CONTRACTOR. E.C. RESPONSIBLE FOR PROVIDING ANY ROOF
CURBS, EQUIPMENT RAILS, VENTS, ETC AND COMMUNICATING ALL
REQ'S WITH G.C. & ROOFING CONTRACTOR.
ALL LOW VOLTAGE WIRING RELATED TO MECHANICAL EQUIPMENT
AND SYSTEMS IS THE RESPONSIBILITY OF THE MECHANICAL
CONTRACTOR (ANY LOW VOLTAGE FIRE ALARM WIRING TO BE BY
E.C.). ALL HIGH VOLTAGE CONNECTIONS TO MECHANICAL
EQUIPMENT, TO BE PROVIDED AND INSTALLED BY E.C. (SEE
EQUIPMENT SCHEDULE FOR DISCONNECT RESPONSIBILITY).
ELECTRICAL CONTRACTOR IS TO EMPLOY THE SERVICES OF THE G.C.
FOR CUTTING AND PATCHING OF WALLS, FLOORS & CEILINGS
RELATED TO THE INSTALLATION OF ELECTRICAL EQUIPMENT &
SYSTEMS.
1.
2.
3.
4.
5.
1.
2.
3.
4.
5.
6.
8.
G.C. RESPONSIBLE FOR PAINTING OF ANY EXPOSED CONDUIT, WIRE,
BOXES ETC. E.C. RESPONSIBLE FOR CLEANING AND PREPARING
ITEMS FOR PAINT, COORDINATE W/ G.C.
E.C. TO COORDINATE W/ G.C. PRIOR TO BID REGARDING HIRING OF
FIRE ALARM, DATA/TELE & SECURITY SUB-CONTRACTORS (IF
APPLICABLE).
ALL MATERIAL, DEVICES, APPLIANCES, AND EQUIPMENT SHALL BE
NEW UNLESS OTHERWISE NOTED AND SHALL CONFORM TO THE
STANDARDS OF THE UNDERWRITER'S LABORATORIES, INC., AND THE
NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION.
11.
12.
2.
3.
ALL MATERIALS INSTALLED IN RETURN PLENUM ARE TO BE PLENUM
RATED.
13.
ALL FIRE SEALANTS TO BE U.L. LISTED AND APPROVED FOR USE W/
APPROPRIATE U.L. PENETRATION DETAIL.
5.
CONDUCTORS SHALL BE COPPER RATED AT NOT LESS THAN 600
VOLTS.MINIMUM SIZE SHALL BE #12 AWG UNLESS OTHERWISE NOTED
ON THE DRAWINGS. ALL WIRE #8 AWG AND LARGER SHALL BE
STRANDED. ALL CONDUCTORS #10 AND SMALLER MAY BE SOLID OR
STRANDED, UNLESS OTHERWISE NOTED. CONDUCTOR INSULATION
SHALL BE TYPE THHN UNLESS OTHERWISE NOTED. ALL EXTERIOR CABLE
OR OTHER WIRE EXPOSED TO SUNLIGHT SHALL BE RATED FOR
EXTERIOR USE & SUNLIGHT RESISTANT.
6.
THE ELECTRICAL CONTRACTOR SHALL COORDINATE CLOSELY
WITH ALL OTHER TRADES TO AVOID CONFLICT AND ENSURE
OTHER TRADES PROVIDE MEASURES TO ACCOMMODATE
ELECTRICAL WORK (I.E. ACCESS DOORS, SLAB/WALL/ROOF
OPENINGS, ETC).
E.C. TO COORDINATE ELEVATION OF WALL MOUNTED LIGHTS
(INTERIOR & EXTERIOR) W/ ARCHITECT/ARCH PLANS.
E.C. TO COORDINATE W/ P.C. & M.C. REGARDING POWER AND
FIRE ALARM CONNECTIONS TO MECHANICAL AND PLUMBING
EQUIPMENT.
E.C. TO VERIFY ALL REQUIREMENTS AND COORDINATE EXACT
LOCATION OF INCOMING ELECTRICAL SERVICE WITH LOCAL
POWER COMPANY PRIOR TO PROJECT START-UP. NOTIFY
ENGINEER OF ANY CHANGES AS MAY BE REQUIRED.
E.C. TO VERIFY DEVICE PLATE COLOR AND MATERIAL WITH
ARCHITECT PRIOR TO PURCHASE.
ALL WIRING SHALL BE INSTALLED IN GALVANIZED RIGID CONDUIT,
INTERMEDIATE METAL CONDUIT, OR EMT, EXCEPT AS ALLOWED
BELOW. EMT SHALL NOT BE USED IN OR UNDER CONCRETE SLABS,
OR IN MASONRY WALLS. USE SCHEDULE 40 PVC OUTDOORS WHERE
NOT SUBJECT TO PHYSICAL DAMAGE OR BELOW FLOOR SLAB.
MINIMUM CONDUIT SIZE TO BE 1/2". TYPE MC AND AC CABLE MAY
BE USED WHERE PERMISSIBLE BY NEC. FLEXIBLE CONDUIT SHALL BE
USED FOR CONNECTIONS TO VIBRATING EQUIPMENT AND
LUMINAIRES, BUT SHALL NOT EXCEED 6' IN LENGTH.
GEB10RS
96
LAY-IN
2x4 3-LAMP ACRYLIC LENSED LAY-IN RECESSED
TROFFER
LAY-IN
2x2 3-LAMP ACRYLIC LENSED LAY-IN RECESSED
TROFFER
1
51
GEB10RS
C
LITHONIA
LF6N
1
26W TRT
MVOLT
1
ELECTRONIC
D
LITEFORMS
CF8P26TEB
1
26W TRT
120
-
-
26W
RECESSED
6" RECESSED CAN/DOWNLIGHT. CLEAR LENS
PENDANT
8" DIRECT PENDANT MOUNT CYLINDER. W/ 26W
FLUORESCENT LAMP. DIMMABLE.
E
BARN LIGHT ELEC.
BLE-C-VSBA-PC
1
-
120
-
-
22W
PENDANT
F
BARN LIGHT ELEC.
BLE-G-AUS-PC
1
-
120
-
-
22W
WALL
TEGAN
TG-MPS-IT-AL-MP
1
120
12W LED
-
-
12W
WALL
H
LIGHTOLIER
1135/1101FTU
1
26W TRT
120
1
-
26W
RECESSED
J
LUMIERE
CAMBRIA 922
1
6W LED
120
1
-
6W
WALL
CAMBRIA 922 WALL MOUNTED SIGN LIGHT.
K
KASON
1810 EZ
2
32W T8
120
1
COLD TEMP
64
SURFACE
J
L
LITHONIA
LITHONIA
LITHONIA
LITHONIA
LF6N
1
LQC
1
LQC
1
ELM2
2
26W TRT
MVOLT
LED
120,
277
LED
120,
277
-
120,
277
-
5.4 W
1
ELECTRONIC
-
26W
-
1.2
-
1.2
-
1.2
RECESSED
SINGLE POLE SWITCH, 20A, 120/277 VOLT, 48" A.F.F. TO CENTER.
"3" INDICATES 3-WAY SWITCH.
"4" INDICATES 4-WAY SWITCH.
"D" INDICATES DIMMER SWITCH OF TYPE TO SUIT LOAD.
"M" INDICATES 120V, 20A MOTOR RATED TOGGLE SWITCH.
"DP" INDICATES DOUBLE POLE
INDICATES FLUORESCENT FIXTURES DUAL SWITCHED, INBOARD/OUTBOARD SWITCHED
SEPARATELY.
DUPLEX RECEPTACLE, 20 AMP (15 AMP RESIDENTIAL, UON), 120 VOLT, 18" A.F.F. TO CENTER.
"GFI" INDICATES GROUND FAULT CIRCUIT INTERRUPTER TYPE.
"WP" INDICATES WEATHERPROOF.
"EWC" INDICATES RECEPTACLE INSIDE ENCLOSURE OF ELECTRIC WATER COOLER PROVIDE
GFI BREAKER FOR CIRCUIT.
"ASW" INDICATES ABOVE SHOW WINDOW, PER NEC SHOW WINDOW REQ'S.
QUADRUPLEX RECEPTACLE, AS ABOVE, 18" A.F.F.
DUPLEX RECEPTACLE, AS ABOVE, SPLIT WIRED, TOP HALF SWITCHED, 18" A.F.F.
6" RECESSED CAN/DOWNLIGHT. NO LENS
CEILING
EXIT LIGHT W/ BATTERY BACK-UP. RED ILLUMINATED
EXIT SIGN. ALUM. FACE. HOUSING COLOR BY ARCH.
WALL
EXIT LIGHT W/ BATTERY BACK-UP. RED ILLUMINATED
EXIT SIGN. ALUM. FACE. HOUSING COLOR BY ARCH.
DUPLEX RECEPTACLE, AS ABOVE, MOUNTED 6" ABOVE COUNTER TOP OR 4" ABOVE
BACKSPLASH, AS APPROPRIATE, OR AT HEIGHT INDICATED.
DUPLEX RECEPTACLE, AS ABOVE, MOUNTED 6" ABOVE COUNTER TOP OR 4" ABOVE
BACKSPLASH, AS APPROPRIATE, OR AT HEIGHT INDICATED, WITH GFI PROTECTION.
RECESSED FLUSH FLOOR DUPLEX RECEPTACLE WITH BRASS COVERPLATE. COORDINATE
EXACT FINISH WITH ARCHITECT AND OWNER.
GEN. PURPOSE EMERGENCY LIGHT. (2) ADJ. HEADS.
BATTERY BACK-UP.
SEE PLAN
NOTES:
1. UNLESS OTHERWISE NOTED COLOR & FINISH OF FIXTURE HOUSING, BAFFLE, OR SIMILAR EXPOSED ELEMENTS TO BE BY ARCHITECT.
2. WHERE MASTER SLAVE WIRING CONFIGURATIONS IS INDICATED THE CONTRACTOR SHALL VERIFY THE QUANTITY AND TYPE OF BALLASTS REQUIRED TO PERMIT BI-LEVEL SWITCHING. WHERE
BI-LEVEL LIGHTING IS INDICATED INBOARD AND OUTBOARD LAMPS SHALL BE SWITCHED SEPARATELY.
3. EXIT AND EMERGENCY LIGHTING FIXTURES SHALL BE CIRCUITED TO AN UNSWITCHED LEG OF A NORMALLY ON LOCAL LIGHTING CIRCUIT (UNLESS NOTED OTHERWISE),INCLUDE 90 MINUTE BATTERY
BACKUP & TESTING MEANS.
4. PROVIDE DISCONNECT FOR LUMINAIRES WITH LINEAR FLUORESCENT LAMPS AND/OR SERVICEABLE BALLASTS PER NEC 410.130(G).
5. FIXTURES WITH A STANDARD FACTORY INSTALLED EMERGENCY OPTION SHOULD USE THAT WHERE "EMC" IS SHOWN.
6. ALL LAMPS OF A SINGLE FIXTURE TYPE INSTALLED IN EACH AREA/ROOM/SPACE ARE TO BE OF SAME TEMPERATURE/COLOR.
208V RECEPTACLE, SEE PLANS FOR NEMA CONFIGURATION.
TELEPHONE/DATA OUTLET, 18" A.F.F. TO CENTER OR ALIGN MOUNTING HEIGHT WITH
ADJACENT DEVICE, UNLESS OTHERWISE NOTED. COORDINATE EXACT DEVICE TYPE AND
REQUIRED FACEPLATE W/ OWNER/TENANT.
30/3/FPN
LIGHTING SYSTEMS
NCECC SECTION 505 & 506
INTERIOR LIGHTING POWER DENSITY CALCULATION PER TABLE 505.5.2. SEE LIGHTING
FIXTURE SCHEDULE FOR FIXTURE INFORMATION.
PROVIDE A PULLWIRE IN ALL EMPTY CONDUITS.
INTERIOR WATTAGE SPECIFIED VS. ALLOWED
TRADABLE EXTERIOR WATTAGE SPECIFIED VS. ALLOWED
NONTRADABLE EXTERIOR WATTAGE SPECIFIED VS. ALLOWED
EF
NAME:
ZACK L. TOMLIN, PE
TITLE:
ELECTRICAL ENGINEER
TRACK LIGHTING FIXTURE, SEE FIXTURE SCHEDULE FOR DETAILS.
SURFACE MOUNTED FLUORESCENT STRIP, SEE FIXTURE SCHEDULE FOR DETAILS.
WALL MOUNTED LIGHTING FIXTURE, SEE FIXTURE SCHEDULE FOR DETAILS.
ADDITIONAL PRESCRIPTIVE COMPLIANCE
506.2.4 HIGHER EFFICIENCY SERVICE WATER HEATING
506.2.5 ON-SITE SUPPLY OF RENEWABLE ENERGY
506.2.6 AUTOMATIC DAYLIGHTING CONTROL SYSTEMS
X
SURFACE, RECESSED OR GROUND MOUNTED LIGHTING FIXTURE, SEE FIXTURE SCHEDULE FOR
DETAILS.
M
PENETRATIONS OF NON-RATED WALLS, PARTITIONS AND FLOOR
OF COMBUSTIBLE CONSTRUCTION SHALL BE FIRESTOPPED WITH
MATERIALS EQUIVALENT TO TWO INCHES OF WOOD.
FIRESTOPPING SHALL COMPLY WITH ASTM E-814.
PENETRATIONS OF ALL EXTERIOR WALLS, FLOORS AND CEILINGS
SHALL BE SEALED IN AN AIR TIGHT MANNER AND IN
ACCORDANCE W/ 2012 NCECC APPENDIX 2 DETAILS.
THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR
PROTECTING ALL ELECTRICAL EQUIPMENT FROM FOREIGN
MATERIAL DURING CONSTRUCTION (PAINT, SPACKLE, ETC.).
UPON COMPLETION OF WORK THE ELECTRICAL CONTRACTOR
SHALL CLEAN, WASH, ETC ALL ITEMS AND EQUIPMENT WITHIN HIS
SCOPE OF WORK AND LEAVE ALL ITEMS BRIGHT AND CLEAN.
IN REQUIRED FIRE RATED WALLS AND PARTITIONS, OPENINGS FOR
INSTALLATION OF BOXES THAT ARE GREATER THAN 16 SQUARE
INCHES SHALL BE PROTECTED AS REQUIRED BY U.L.
UNLESS OTHERWISE INDICATED THE ELECTRICAL CONTRACTOR AT
HIS/HER DISCRETION MAY COMBINE MULTIPLE CIRCUITS INTO A
SINGLE CONDUIT AND DE-RATE WIRE. COMBINING AND
DE-RATING IS TO BE DONE IN STRICT ACCORDANCE W/ NEC.
14.
DEVICES INCLUDING GFCI PROTECTION MUST HAVE THEIR
TESTING MEANS READILY ACCESSIBLE. PROVIDE REMOTE TESTING
MEANS OR GFCI BREAKER FOR GFCI RECEPTACLES AND SIMILAR
DEVICES WHICH ARE NOT READILY ACCESSIBLE (I.E. BEHIND
EQUIPMENT, AT CEILING, ETC). (NEC 210.8).
COORDINATE WITH THE CABLE TV AND TELEPHONE UTILITIES FOR
SERVICE ENTRANCE AND CABLING REQUIREMENTS PRIOR TO
ANY PURCHASING. INSTALLATION MUST COMPLY WITH THEIR
RESPECTIVE REGULATIONS AND REQUIREMENTS.
15.
ALL EXIT & EMERGENCY LIGHTS ARE TO BE CIRCUITED TO
UN-SWITCHED LEG OF LOCAL NORMALLY ON LIGHTING CIRCUIT.
16.
RECEPTACLE, LIGHT SWITCHES AND OTHER CONTROL DEVICES
ARE TO BE INSTALLED IN ACCORDANCE W/ ANSI A117.1 AND
ADA REQ'S CONCERNING HEIGHT AND ACCESSIBILITY. FHA REQ'S
TO BE FOLLOWED FOR MULTI-FAMILY AND RESIDENTIAL
PROJECTS.
17.
E.C. IS TO CONFIRM EXACT ELECTRICAL NAMEPLATE DATA OF
ALL PLUMBING, MECHANICAL AND ELECTRICAL EQUIPMENT
INCLUDING, BUT NOT LIMITED TO, MCA, MOCP, VOLTAGE &
PHASE BEFORE BEGINNING WORK.
FAN, PROVIDED AND INSTALLED BY MECHANICAL CONTRACTOR, WIRED BY ELECTRICAL
CONTRACTOR. PROVIDE DISCONNECTING MEANS AS REQUIRED.
RECESSED MOUNTED 2x4 FLUORESCENT TROFFER, SEE FIXTURE SCHEDULE FOR DETAILS.
SIGNED:
EXIST. VS. EXIST.
NA VS. NA
NOT APPLICABLE (RENOVATION PROJECT)
506.2.1 MORE EFFICIENT MECHANICAL EQUIPMENT
506.2.2 REDUCED LIGHTING POWER DENSITY
506.2.3 ENERGY RECOVERY VENTILATION SYSTEM
6/16/14
480Y/277V PANEL, SURFACE OR RECESS MOUNTED, SEE SCHEDULE FOR DETAILS.
3080 VS. 3451
EXTERIOR LIGHTING POWER DENSITY CALCULATION PER TABLE 505.6.2. SEE LIGHTING
FIXTURE SCHEDULE FOR FIXTURE INFORMATION.
HEAVY DUTY FUSIBLE/NON-FUSIBLE DISCONNECT SWITCH, NUMBERS INDICATE FRAME SIZE,
NUMBER OF POLES AND FUSING. PROVIDE NEMA 1 ENCLOSURE INSIDE. PROVIDE NEMA 3
ENCLOSURE FOR ALL SWITCHES LOCATED OUTSIDE.
"FPN" INDICATES FUSE PER EQUIPMENT NAMEPLATE
"NF" INDICATES NON-FUSED.
"MS" INDICATES MOTOR STARTER OF TYPE TO SUIT LOAD.
208Y/120V PANEL, SURFACE OR RECESS MOUNTED, SEE SCHEDULE FOR DETAILS.
DESIGNER STATEMENT:
SUPPORT ALL CONDUIT AND EQUIPMENT IN ACCORDANCE W/
NEC. ANY SUSPENDED MATERIALS SHALL BE DIRECTLY SUPPORTED
BY THE BUILDING STRUCTURE.
JUNCTION BOX FLOOR MOUNTED.
JUNCTION BOX WALL MOUNTED AT HEIGHT INDICATED ON DRAWINGS.
4' 2-LAMP VAPOR PROOF GASKETED SURFACE
MOUNT FLUORESCENT COOLER FIXTURE.
TO THE BEST OF MY KNOWLEDGE AND BELIEF, THE DESIGN OF THIS BUILDING COMPLIES
WITH THE LIGHTING SYSTEMS REQUIREMENTS OF THE NORTH CAROLINA ENERGY
CONSERVATION CODE, SECTION 505 & 506 AND ANY LOCAL AMENDMENTS THEREOF.
SEAL ALL PENETRATIONS OF SMOKE PARTITIONS OR FIRE RATED
WALLS, CEILING, FLOORS IN ACCORDANCE W/ APPROPRIATE
U.L. PENETRATION DETAIL AND NC BUILDING CODE.
INDICATES HOT LEG OF CIRCUIT TO BE CARRIED OVER TO NEXT DEVICE. SEE PLANS FOR
CONTROL SCHEME.
SINGLE RECEPTACLE, 20 AMP, 120 VOLT, 18" A.F.F. TO CENTER.
LIGHTING POWER DENSITY CALCULATION COMPLIANCE
ALL PENETRATIONS THROUGH EXTERIOR WALLS & ROOF SHALL BE
FLASHED & COUNTER-FLASHED IN A WATERPROOF MANNER.
ARROWHEAD INDICATES HOMERUN TO PANEL NOTED.
WALL MOUNTED MONO POINT LIGHT
FIXTURE.LEDLAMP. W/ CLARO SPOTLIGHT.
A COMPLETE GROUNDING SYSTEM SHALL BE PROVIDED AND
INSTALLED IN ACCORDANCE WITH ARTICLE 250 OF THE NEC,
AND AS SHOWN ON THE DRAWINGS.
PROVIDE A TYPED DIRECTORY IN ALL PANELBOARDS CLEARLY
DESCRIBING THE LOCATION OF AND TYPE OF LOAD BEING
SERVED FOR ALL CIRCUITS. PROVIDE ENGRAVED PHENOLIC
NAMEPLATES FOR ALL PANELBOARDS AND DISCONNECT
SWITCHES, WHITE LETTERS ON BLACK BACKGROUND.
CIRCUIT CONDUCTORS CONCEALED IN FLOOR, WALL OR CEILING.
ASTRO SHALLOW BOWL VENTED PENDANT. CORD
HUNG. COORDINATE FINISH W/ OWNER. W/ PHILLIPS
22W LED BULB.
ALL WEATHER GOOSENECK FARM LIGHT WALL
MOUNTED FIXTURE. COORDINATE FINISH W/ OWNER.
W/ PHILLIPS 22W LED BULB.
6" RECESSED CAN/DOWNLIGHT. W/ SCOOP
REFLECTOR LENS.
E.C. TO FOLLOW MANUFACTURER'S INSTRUCTIONS WHEN
INSTALLING ELECTRICAL EQUIPMENT. ENSURE REQUIRED
MAINTENANCE ACCESS AND CLEARANCES ARE MAINTAINED. IF
CONFLICT EXISTS BETWEEN THESE PLANS AND MFG INSTRUCTIONS
CONTACT ENGINEER.
PROVIDE HANGERS & SUPPORTS APPROVED FOR USE BY NEC.
4.
1
DESCRIPTION
###
7.
III. MATERIALS:
1.
ALL EXTERIOR FIXTURES AND DEVICES SHALL BE RATED FOR
V. EXECUTION:
10.
5.
MVOLT
MOUNTING
IV. COORDINATION:
9.
4.
17W T8
INPUT
WATTS
LIGHTING SWITCHES SHALL BE 20 AMP COMMERCIAL
SPECIFICATION GRADE EQUAL TO HUBBELL SERIES.
REQUIRED.
II. DIVISION OF WORK:
1.
3
TYPE
maple
ENGINEERING, pllc
1405 HILLSBOROUGH ST
RALEIGH, NC 27605
LIC.#: P-0990
P:919-341-4247
F:919-890-3797
plumbing mechanical electrical
ELECTRIC UTILITY METER LOCATION.
KITCHEN EQUIPMENT TAG.
DEMO'D LIGHT FIXTURE OR SIMILAR.
DEMO'D RECEPTACLE OR SIMILAR.
CEILING
FIRE ALARM HORN,
HORN/STROBE OR
STROBE.
TV
NOTE:
DEVICE HEIGHTS ARE TO
BE AS INDICATED UNLESS
OTHERWISE NOTED.
FIRE
WALL
MOUNTED
TELEPHONE
RECEPTACLE
LIGHT SWITCH
OR DIMMER
TELE/DATA
SWITCH
FIRE ALARM
PULL STATION
RECEPTACLE
TELEPHONE OR
DATA JACK
TOP OF COUNTER
MAX COUNTER
DEPTH = 24"
FLOOR
NOTE:
MOUNTING LOCATIONS OF RECEPTACLES, SWITCHES AND ALL
OTHER CONTROL DEVICES SHALL BE IN ACCORDANCE WITH
ANSI A117.1 AND ADA REQUIREMENTS (FHA REQ'S FOR
MULTI-FAMILY AND RESIDENTIAL PROJECTS)
1
TYPICAL DEVICE MOUNTING HEIGHTS
CABLE TV OUTLET, 18" A.F.F. TO CENTER, UNLESS OTHERWISE NOTED.
ELECTRICAL ABBREVIATIONS
18"
ALIGN DEVICES WHEN
MOUNTED CLOSE ON
SAME WALL
36" MAX
THESE DRAWINGS ARE DIAGRAMMATIC AND SHOW GENERAL
LOCATION AND ARRANGEMENT OF ALL MATERIALS AND
EQUIPMENT. THE DRAWINGS SHALL BE FOLLOWED AS CLOSELY AS
BUILDING CONSTRUCTION AND ALL OTHER WORK WILL PERMIT.
2SP8 G
MVOLT
BALLAST DATA
NO.
JUNCTION BOX CEILING MOUNTED.
G
5.
LITHONIA
VOLTS
42"
ALL EQUIPMENT, MATERIALS AND INSTALLATION SHALL BE
GUARANTEED TO BE FREE OF DEFECTS FOR A PERIOD OF ONE (1)
YEAR AFTER FINAL ACCEPTANCE OF WORK OR IN ACCORDANCE
WITH THE MANUFACTURER'S STANDARD GUARANTEE, IF LONGER.
EXISTING EQUIPMENT IS EXCLUDED FROM WARRANTY REQUIREMENT.
FUSES 0 - 600 AMPS SHALL BE UL CLASS "RK-1" LOW PEAK DUAL
ELEMENT TIME DELAY WITH 200,000 AMPERE INTERRUPTING
RATING AS MANUFACTURED BY BUSSMANN, UNLESS NOTED
OTHERWISE.
TYPE
48"
4.
ALL ELECTRICAL & LIGHTING EQUIPMENT SHALL BE PROVIDED
COMPLETE WITH ALL ACCESSORIES, HANGERS, SUPPORTS,
CONTROLS, ETC FOR A FULLY FUNCTIONING SYSTEM REGARDLESS OF
PRESENCE ON PLANS.
8.
NO.
80"
3.
ALL WORK IS TO BE PERFORMED IN ACCORDANCE WITH NEC AND
ALL OTHER APPLICABLE CODES. EC IS TO COORDINATE W/ G.C. IN
REGARDS TO PROJECT TIMELINE, WORK HOURS, AS WELL AS ANY
BONDING OR INSURANCE REQUIREMENTS.
CATALOG
NUMBER
46"
2.
ELECTRICAL CONTRACTOR IS TO FURNISH AND PAY FOR ALL LABOR,
MATERIAL, EQUIPMENT, PERMITS & FEES REQUIRED FOR THE
COMPLETE INSTALLATION OF ALL SYSTEMS IN THIS SECTION OF
WORK.
METAL CONDUIT COUPLINGS TO BE COMPRESSION TYPE OR
THREADED WHEN ACCESSIBLE TO BUILDING OCCUPANTS. METAL
COUNDUIT COUPLINGS MAY BE SET-SCREW TYPE WHEN
CONCEALED IN BUILDING STRUCTURE OR LOCATED MORE THAN
10' AFF. PLASTIC CONDUIT COUPLINGS TO BE SOCKET GLUED
TYPE.
MANUF.
46"
1.
7.
LAMP DATA
MARK
18"
I. GENERAL REQUIREMENTS:
ELECTRICAL SYMBOL LEGEND
LIGHTING FIXTURE SCHEDULE
DIMENSION INDICATES HEIGHT ABOVE FINISHED FLOOR AT WHICH CENTER OF
DEVICE IS TO BE MOUNTED.
AFF
ABOVE FINISHED FLOOR.
AFG
ABOVE FINISHED GRADE.
E.C.
ELECTRICAL CONTRACTOR.
FPN
FUSE PER EQUIPMENT NAMEPLATE REQUIREMENTS.
G.C.
GENERAL CONTRACTOR.
M.C.
MECHANICAL CONTRACTOR.
P.C.
PLUMBING CONTRACTOR.
WP
INDICATES DEVICE TO HAVE WEATHERPROOF COVER.
UON
UNLESS OTHERWISE NOTED.
FACP
FIRE ALARM CONTROL PANEL.
SMP
SPRINKLER MONITORING PANEL.
NL
NIGHT LIGHT, LIGHT NOT SWITCHED.
WP
WEATHER PROOF
NO SCALE
Project Number :LAG-1404
Drawn By: MJL, RDG, RSA
Date: 06-16-14
MOTION SENSOR LEGEND
M0
WALL SWITCH DUAL TECH. (INFRARED AND ULTRASONIC) OCCUPANCY SENSOR EQUAL TO
SENSOR SWITCH MODEL WSX PDT. 120/277V. TIME DELAYS 15 MINUTES FOR ON/OFF. LINE
VOLTAGE.
E-1
ELECTRICAL
SCHEDULES
DETAILS
& NOTES
FIRE RATING LEGEND
1-HR WALL
DIMMER SWITCH
TO ADDITIONAL CONTACTORS AS REQUIRED.
LIGHTING CONTACTOR
LIGHTING CIRCUITS
FR PANEL
SINGLE SWITCH
SINGLE SWITCH
SINGLE SWITCH
SINGLE SWITCH
OFF
OFF
OFF
DIMMER SWITCH
DIMMER SWITCH
DIMMER SWITCH
A
B
C
E
G
H
J
CUST. LINE
B-5
FRNT. COUNTER
B-3
FRNT. KITCHEN
B-1
BACK KITCHEN
B-1
DINING 1 WALL
B-11
DINING 1
B-11
DINING 2
B-9
SINGLE SWITCH
DIMMER SWITCH
DIMMER SWITCH
DIMMER SWITCH
DIMMER SWITCH
SINGLE SWITCH
DIMMER SWITCH
PROG. SWITCH
#:##
CIRCUITS
TO
FIXTURES
OFF
OFF
OFF
LINE
c
OVERRIDE
SWITCH
GENERAL NOTES - THIS SHEET
PROG.
SWITCH
(SEE SWITCH BANK DETAIL)
1.
2.
NOTE:
1. E.C. TO COORDINATE # OF CIRCUITS CONTROLLED AND NATURE OF LOADS
W/ CONTACTOR MFG. PROVIDE MULTIPLE CONTACTORS AS REQUIRED.
2. OVERRIDE SWITCH TO BE LOCATED AT LIGHTING CONTACTORS & CLEARLY
LABELED.
3. LOCATE ALL CONTACTORS NEXT TO PANEL. CLEARLY LABEL.
3
K
L
N
P
Q
R
T
V
ENTRY CANS
B-11
DINING 4
B-5
DINING 3 PENS
B-7
DINING 4 WALL
B-7
BACK HALL
B-7
FRONT DINING PENS
B-11
SIGNS
B-13
MONOPOINTS
B-5
LOAD
3.
4.
5.
6.
LIGHTING CONTACTOR DETAIL
TAGGED NOTES - THIS SHEET
ITEMS SHOWN IN FAINT ARE EXISTING TO REMAIN. NEW OR
RELOCATED ITEMS ARE SHOWN IN BOLD. SEE LEGEND.
E.C. TO VERIFY EXISTING CONDITIONS BEFORE BEGINNING
WORK.
E.C. TO TEST OPERATION & BATTERY LIFE OF ALL EXISTING
EXIT AND EMERGENCY LIGHTS.
CONDUITS ENTERING WALK-IN FREEZER AND/OR COOLER
ARE TO BE SEALED IN ACCORDANCE W/ NEC 300.7.
ENSURE THAT ALL EXIT AND EMERGENCY LIGHTS ARE
CONNECTED TO LOCAL NORMALLY ON LIGHTING CIRCUIT
AND ARE WIRED UPSTREAM OF ALL SWITCHES,
CONTACTORS, AND SIMILAR.
COORDINATE ELEVATION OF WALL MOUNTED &
PENDANT/SUSPENDED LIGHTS W/ ARCHITECT.
1.
COORDINATE EXACT SWITCH TYPE W/ OWNER AND FIXTURES & BALLAST(S) BEING CONTROLLED.
2.
LABEL SWITCHES W/ DESIGNATION SHOWN (I.E. "A", "AN", "W", ETC) & CIRCUIT #.
FIXTURE "J" INDICATES DECORATIVE SIGN LIGHT
CIRCUITED & SWITCHED AS SHOWN. COORDINATE
EXACT LOCATION & DETAILS W/ ARCH.
3.
PROVIDE PLACARD AT EACH SWITCH INDICATING AREA CONTROLLED.
4.
DIMMER SWITCH TO INCLUDE ON-OFF SWITCH AT BOTTOM TO ALLOW FOR ONE-TIME ADJUSTMENT OF
3
EXISTING EXTERIOR EMERGENCY LIGHT.
5.
HIGHEST POSITION OF HIGHEST SWITCH TO BE NO GREATER THAN 48" AFF (ANSI A117.1)
4
WIRE LIGHT FIXTURE AS NIGHT LIGHT.
6.
PROGRAMMABLE TIME SWITCH TO BE WIRED TO LIGHTING CONTACTOR. SEE DETAIL. SWITCH TO BE 7-DAY
5
VERIFY LOCATION OF SWITCH BANK W/
OWNER/ARCHITECT.
INTEGRAL HOOD LTS BY HOOD MFG.
2
6
NO SCALE
SWITCH BANK NOTES:
BATHROOM EXHAUST FAN TO BE ON WHEN LIGHTS IN
EITHER MEN'S OR WOMEN'S ARE ON. COORDINATE W/
M.C.. PROVIDE CONTACTORS AS NECESSARY.
1
LIGHT LEVELS.
PROGRAMMABLE W/ HOLIDAY SCHEDULING & DAYLIGHT SAVINGS TIME ADJUSTMENT. SWITCH TO
INCLUDE TIME OVERRIDE FEATURE (2-HOUR MAXIMUM).
SWITCH BANK DETAIL
2
STORAGE
NO SCALE
6/16/14
B-9
N
B-7
D
B
L
AREA CNTRLD
RESTARAUNT
H
H
H
E
E
E
D
D
R
E
maple
Q
P
MEN
E
ENGINEERING, pllc
C
B-5
1405 HILLSBOROUGH ST
RALEIGH, NC 27605
LIC.#: P-0990
P:919-341-4247
F:919-890-3797
L
plumbing mechanical electrical
F
1
HALL
H
D
D
D
D
D
D
D
D
D
E
L
C
H
DINING AREA 4
WOMEN
DINING AREA 3
DINING AREA 2
J
T
F
J
2
B-13
D
D
D
D
D
D
D
D
D
E
A
NL
D
4
E
B-35
E
TO GO
ORDERS
A
E
V
CEIL.
CUSTOMER QUEUE
E
E
E
E
CEIL.
CEIL.
H
G
B-11
G
B
NL
BACK
HALL
B
C
C
C
C
C
C
C
C
C
D
C
4
B-35
D
D
E
CAN WASH
OFFICE
3
EMG
C
H
C
FRONT KITCHEN
B-1
C
E
B-3
3
CEIL.
A
K
6
A
A
SWITCH BANK
A
A
C
A
A
E
D
D
D
C
5
M0
E
CATERING
STORAGE
DINING AREA 1
T
PREP KITCHEN/
DRY STORAGE
J
B-13
6
2
K
D
D
J
D
B-13
A
A
A
A
A
A
G
A
H
H
H
Project Number :LAG-1404
Drawn By: MJL, RDG, RSA
Date: 06-16-14
E-2
1
ELEC. LIGHTING PLAN
SCALE: 1/4" = 1'-0"
ELECTRICAL
LIGHTING
PLAN
FIRE RATING LEGEND
1-HR WALL
MUA EXH
FAN(S) FAN(S)
M
DISCONNECT
M
SWITCH & CIRCUIT
FOR HOOD LIGHTS
TO RTU INTERLOCK,
FIRE ALARM OR OTHER
AUX. INPUT/OUPUTS.
HOOD
CONTROLS
LIGHT CIRCUIT
FAN CIRCUIT
FAN CIRCUIT
NOTES:
1. HOOD(S) CONTROL PANELS BY OTHERS. CONFIRM INSTALLATION
W/ HOOD MFG. SEE HOOD DRAWINGS FOR ADDITIONAL INFO.
2. INSIDE FAN CIRCUIT DISCONNECTS MAY BE OMITTED IF BREAKER
PANEL IS WITHIN LINE OF SIGHT.
3. E.C. TO COORDINATE EXACT # OF FANS.
4. SEE PANEL SCHEDULES & HOOD DRAWINGS FOR CIRCUIT
INFORMATION.
PHASE
KW
AMPS
HOOD WIRING DETAIL
4
NO SCALE
CEILING
PLUG
VOLT
DIR. CONN.
EQUIPMENT SCHEDULE
1-1/2" CONDUIT SLEEVE
PULLSTRING
CONDUIT
(CONFIRM SIZE W/ OWNER)
GENERAL NOTES - THIS SHEET
ITEM
#
QTY.
DESCRIPTION
1
1
U/C MOBILE HEATED PAN CABINET
120
1
-
14.1
-
X
RECEPTACLE @ 18" AFF.
2.1
1
COUNTER TOP GRIDDLE
120
1
-
15.0
-
X
RECEPTACLE @ 30" AFF.
3
1
REFRIGERATED EQUIPMENT STAND
120
1
-
10.0
-
X
RECEPTACLE @ 18" AFF.
7
1
REFRIGERATED SANDWICH UNIT
120
1
-
12.0
-
X
RECEPTACLE @ 18" AFF.
8
1
REFRIGERATED SANDWICH UNIT
120
1
-
7.2
-
X
RECEPTACLE @ 18" AFF.
9
1
REFRIGERATED BACKBAR CABINET
120
1
-
5.0
-
X
RECEPTACLE @ 18" AFF.
13
1
HOT FOOD COUNTER
120
1
-
11.7
-
X
RECEPTACLE @ 18" AFF.
FLOOR TO
DECK WALL
ELECTRICAL NOTES
1.
E.C. TO VERIFY EXISTING CONDITIONS BEFORE BEGINNING
WORK.
E.C. TO COORDINATE EXACT LOCATION AND INSTALLATION
OF ALL KITCHEN EQUIPMENT W/ OWNER.
CONDUITS ENTERING WALK-IN FREEZER AND/OR COOLER
ARE TO BE SEALED IN ACCORDANCE W/ NEC 300.7.
2.
3.
16
2
CONVECTION OVEN
208
3
-
31.0
X
-
JUNCTION BOX @ 48" AFF.
17
1
KETTLE ON STAND
208
3
-
27.2
X
-
JUNCTION BOX @ 24" AFF.
20
1
ICE MAKER W/ BIN
120
1
-
18.3
X
-
JUNCTION BOX @ 64" AFF.
TAGGED NOTES - THIS SHEET
FLOOR
PROVIDE POWER FOR SIGN CIRCUIT. COORDINATE
EXACT LOCATION, SIGN REQUIREMENTS AND SCOPE
OF WORK W/ OWNER.
1
21
1
ICE DISPENSER
120
1
-
2.5
-
X
RECEPTACLE @ 50" AFF.
22
1
WALK-IN COOLER
120
1
-
4.0
X
-
COOLER LIGHTS
22-CC
1
WALK-IN COOLER COMPRESSOR
208
3
-
7.2
X
-
-
22-CE
1
WALK-IN COOLER EVAPORATOR
120
1
-
1.8
X
-
-
26
2
BAG-IN-BOX SYSTEM
120
1
-
3.0
-
X
-
34
1
AIR CURTAIN
120
1
-
9.0
X
-
-
36
1
DISHWASER
120
1
-
9.4
X
-
JUNCTION BOX @ 72" AFF.
43
1
WARMING CABINET
120
1
-
10.0
-
X
RECEPTACLE @ 72" AFF.
DATA/TELE/CATV OUTLET BOX.
COORDINATE SIZE W/
ELECTRICAL PLAN.
COORDINATE FACE PLATE W/
OWNER.
4
RTU TO INCLUDE FACTORY MOUNTED DISCONNECT &
FACTORY POWERED GFI SERVICE RECEPTACLE.
COORDINATE W/ M.C..
USE EXISTING CONDUIT TO TRANSFORMER. E.C. TO
CONFIRM.
WIRED VIA LTS & CONTACTOR. SEE LIGHTING PLAN.
5
WIRE VIA HOOD CONTROLS.
6
EVAPORATOR UNIT WIRED VIA CONDENSING UNIT.
2
3
NOTE:
E.C. TO VERIFY EXACT TYPE, QTY, LOCATION OF EQUIPMENT ELECTRICAL CONNECTIONS BEFORE BEGINNING WORK. E.C. TO ALSO VERIFY ACTUAL
EQUIPMENT NAMEPLATE VALUES. FINAL CONNECTION TO EQUIPMENT BY E.C..
NOTE:
FOR INTERIOR WALLS WITHOUT
INSULATION. E.C. MAY OMIT CONDUIT &
OUTLET BOX. PROVIDE PULL STRING &
PLASTER RING.
3
DATA/TELE/CATV OUTLET
NO SCALE
6/16/14
MEN
ASW
ASW
STORAGE
B-39
B-17
B-39
B-17
maple
ON ROOF
4
B-25
WP,M
ENGINEERING, pllc
1405 HILLSBOROUGH ST
RALEIGH, NC 27605
LIC.#: P-0990
P:919-341-4247
F:919-890-3797
EF-1
B-25
plumbing mechanical electrical
HALL
B-39
ASW
ELECTRICAL SERVICE.
(SEE RISER)
WOMEN
3
M
DINING AREA 4
B-25
DINING AREA 3
DINING AREA 2
B-25
B-23
B-23
RTU-2
M
B-40
+84",RP-1
B-10 B-40
B-40
1
13
J
A-20
34
B-2
B-38
B-23
B
21
7
9
OFFICE
B-38
B-4
B-6
B-33
+50"
B-8
KSF-3
B-12
B-18
+72"
5
5
43
A-8,10,12
WP,30/3/FPN
3
H-7
22
36
CU-1
A-19,21,23
WP,30/3/FPN
CATERING
STORAGE
8
A-8,10,12
WP,30/3/FPN
B-24
+30"
J
B-30
ON ROOF
KEF-2
2.1
H-8
M
+72"
6
B-41
1
FRONT KITCHEN
20
+64"
M
WP,M
B-31
B-27
26
A
EVAP
ASW
A-1,3,5
CUSTOMER QUEUE
B-19
CAN WASH
B-39
2
RTU-1
A-7,9,11
TO GO
ORDERS
BACK
HALL
2
B-28
+24"
H-2,4,6
B-28
PREP KITCHEN/
DRY STORAGE
17
J
+48"
J
B-17
DINING AREA 1
+48"
H-1,3,5 H-9,11,13
16
16
ON ROOF
KEF-1 5
A-2
H
WP,M
B-17
RTU-3
B-15
2
A-4
A-13,15,17
B-15
26
B-10
Project Number :LAG-1404
Drawn By: MJL, RDG, RSA
Date: 06-16-14
E-3
2
METALLIC PIPE (GYPSUM WALL) DETAIL
NO SCALE
1
ELEC. POWER PLAN
SCALE: 1/4" = 1'-0"
ELECTRICAL
POWER
PLAN
VOLTAGE: 208Y/120V
BACK WALL OF REAR KITCHEN
3 PHASE, 4 WIRE
PANEL: H
FLUSH MOUNTED
AMPS: 100-MLO
NOTES -DESCRIPTION-
POLE
BRK
SIZE
CKT
#
1
CONVECTION OVEN
3
8
40
A
3.7
B
C
GFI REF. EQUIP. STAND
1
20
12
3.7
3.2
3
8
40
1
-
-
3.7
0
11
13
3.3
3.7
3.7
15
0
NOTES
TOTAL CONNECTED kVA:
3
KETTLE
COUNTERTOP GRIDDLE GFI
POLE
BRK
SIZE
CKT
#
C LTS: KITCHEN/OFFICE
1
12
20
1
C LTS:FRNT KITCHEN/BCK HALL
1
12
20
3
C LTS:DINING4/CUST. LINE
1
12
20
5
C LTS:B-RMS/DINING 4-3
1
12
20
7
9
NOTES -DESCRIPTION-
20
12
1
10
-
-
1
SPACE
C LTS: DINING AREA 4-3
1
12
20
-
1
SPACE
C LTS: DINING 1/FRNT
1
12
20
11
-
-
1
SPACE
C DECORATIVE SIGNS
16
-
-
1
SPACE
10.7
DEMAND kVA: 24.5
PANEL RMS SYM. AMPS: SEE RISER
DEMAND AMPS: 68.0
PANEL SHALL BE EQUAL TO SQUARE D QO.
GFI - PROVIDE GFCI BREAKER FOR CIRCUIT. GFCI RECEPTACLES MAY BE USED IN LIEU OF GFCI
BREAKERS SO LONG AS THE DEVICE(S) CONFORM TO NEC CODE REQUIREMENTS FOR GFCI
PROTECTION & ACCESSIBILITY.
PANEL "H" LOAD SUMMARY
LOAD TYPE
kVA
CONN.
LOADS ON 100 AMP BREAKER @ PANEL A
DEM.
FACT.
kVA
DEM.
1
12
20
REC: BACK WORKTABLE
1
12
20
15
REC: DINING AREA
1
12
20
17
1
12
20
19
GFI RECIRC. PUMP
-
20
1
12
20
23
REC: BATHROOMS
1
12
20
25
1
12
20
27
1
-
20
29
1
12
20
31
REC: FRONT COUNTER
1
12
20
33
NIGHT LIGHTS
1
12
20
35
SPARE
1
-
20
37
REC: SHOW WINDOW
1
12
20
39
1
12
20
41
GFI MOBILE HEATED PAN
SPARE
GFI HOT FOOD COUNTER
TC SIGN
KITCHEN EQUIPMENT
# PIECES COOKING EQUIPMENT: 5
35.0
0.70
0.8
24.5
TOTAL AMPS @
35.0
AIR CURTAIN
4
30
10
1
ICE MAKER W/ BIN
6
20
12
1
ICE DISPENSER GFI
5
8
20
12
1
REFERIGERATER BACK BAR GFI
7
10
20
12
1
BAG-IN-BOX GFI
12
20
12
1
SANDWICH UNIT GFI
11
14
20
-
1
SPARE GFI
13
16
20
-
1
SPARE
18
20
12
1
20
1.4
1.2
0
0
0.6
0.4
0.8
0
1.7
0.4
0
1.4
1.1
0
0.4
0
0.2
0
0.4
0.6
0.6
1.2
6.7
8.6
TOTAL CONNECTED kVA:
TOTALS
1
0
0
0
12
0
0.2
1
20
0.3
0.6
SPARE
2
0.4
0.4
REC:CATERING/BACK HALL
POLE
0.6
0.5
21
CKT#
2.1
0
3 PHASE
NOTES
NOTES -DESCRIPTION-
POLE
WIRE
SIZE
BRK
SIZE
CKT
#
1
PANEL: A
FLUSH MOUNTED
RTU-1
3
RTU-2
3
RTU-3
3
60
4
8
2.8
0.8
4.7
SPARE
20
-
1
SPARE
24
20
12
1
26
-
-
1
SPACE
SPACE
1
-
-
25
28
20
12
1
REC: WORKTABLE
SPACE
1
-
-
27
30
20
12
1
DISHWASHER
SPACE
1
-
-
29
32
-
-
1
SPACE
SPACE
1
-
-
31
34
-
-
1
SPACE
SPACE
1
-
-
33
36
-
-
1
SPACE
SHUNT TRIP
38
20
12
1
REC: OFFICE
40
20
12
1
REC: TO GO AREA
42
-
-
1
SPACE
19
WALK IN COMPRESSOR
(CU-1)
3
12
20
0.8
0.8
0
23
0.9
0
0
0
0
3
PANEL H
2
100
0
0
0
13.7
0
6.7
39
2
20
12
1
KEF-1 #4
4
15
12
1
HOOD CONTROLS&LTS #4
6
20
-
1
NOTES
SPACE
#4
15
12
3
KSF-3 & KEF-2
14
-
-
1
SPACE
16
-
-
1
SPACE
18
-
-
1
SPACE
20
15
12
1
22
-
-
1
SPACE
24
-
-
1
SPACE
26
-
-
1
SPACE
28
-
-
1
SPACE
30
-
-
1
SPACE
32
-
-
1
SPACE
34
-
-
1
SPACE
36
-
-
1
SPACE
3
PANEL B
HOOD CONTROLS & LTS #4
10.6
8.6
10.7
34.7
TOTAL CONNECTED kVA:
150 1/0
40
32.7
9.2
42
32.9
100.3
DEMAND kVA: 97.2
24.5
DEMAND AMPS: 85.1
PANEL RMS SYM. AMPS: SEE RISER
DEMAND AMPS: 269.9
68.0
1.
2.
3.
4.
PANEL SHALL BE EQUAL TO SQUARE D NQ.
GFI - PROVIDE GFCI BREAKER FOR CIRCUIT. GFCI RECEPTACLES MAY BE USED IN LIEU OF GFCI
BREAKERS SO LONG AS THE DEVICE(S) CONFORM TO NEC CODE REQUIREMENTS FOR GFCI
PROTECTION & ACCESSIBILITY.
TC - CIRCUIT THROUGH 7-DAY PROGRAMMABLE ASTRONOMICAL TIME SWITCH WITH AUTO-DUSK.
C - CIRCUIT THROUGH LIGHTING CONTACTOR. SEE DETAIL.
1.
2.
3.
4.
PANEL SHALL BE EQUAL TO SQUARE D NQ.
PROVIDE HACR BREAKERS FOR HVAC EQUIPMENT.
WIRE SHUNT TRIP TO HOODS FIRE SUPRESSION SYSTEM.
WIRE VIA HOOD CONTROL PANEL.
PANEL "A" LOAD SUMMARY
LOAD TYPE
PANEL "B" LOAD SUMMARY
LOAD TYPE
LIGHTS (2,950 SQ FT @ 2W/SQ FT < CONN. LOAD)
kVA
CONN.
DEM.
FACT.
kVA
DEM.
6.2
1.25
7.8
1st 10 kVA
3.6
1.0
3.6
REMAINDER
0.0
0.5
0.0
SHOW-WINDOW (36 FEET @ 125%)
0.6
15.0
9.0
ELEC HEAT
0.0
1.0
0.0
LARGEST MOTOR
7.0
1.25
8.8
REMAINDER
26.7
1.0
26.7
47.4
0.65
30.8
SIGN CIRCUIT(S)
1.2
1.25
1.5
RECIRC. PUMP, EX. FAN
0.9
1.25
1.1
HOOD FANS & CONTROLS
4.4
1.25
5.5
LOADS ON 300 AMP FUSED DISC. @ METER
DEM.
FACT.
kVA
CONN.
LOADS ON 150 AMP BREAKER @ PANEL A
LIGHTS (2,950 SQ FT @ 2W/SQ FT < CONN. LOAD)
kVA
DEM.
6.2
1.25
7.8
1st 10 kVA
3.6
1.0
3.6
REMAINDER
0.0
0.5
0.0
SHOW-WINDOW (36 FEET @ 125%)
0.6
15.0
9.0
RECEPTACLES
RECEPTACLES
HVAC & R
KITCHEN EQUIPMENT
# PIECES COOKING EQUIPMENT: 11
12.2
0.65
7.9
0.7
1.25
0.9
RECIRC. PUMP,
KITCHEN EQUIPMENT
# PIECES COOKING EQUIPMENT: 16
SIGN CIRCUIT(S)
1.2
TOTALS
TOTAL AMPS @
SERVICE ENTRANCE
EQUIP.
GROUND BUS
-DESCRIPTION-
38
41
DEMAND kVA: 30.7
0
0
35
#3
0
0
0
37
0
0.5
21
SANDWICH UNIT GFI
POLE
12
0
17
1
0.9
0
4.8
-
WIRE
SIZE
10
2.8
4.8
CKT#
BRK
SIZE
8
2.9
20
0
0.8
15
WARMING CABINET GFI
0.5
3.7
9
60
C
1.0
3.7
22
24.5
NEMA 1
B
3
45
4
A
3.6
9.2
PANEL RMS SYM. AMPS: SEE RISER
208 V
3 PHASE, 4 WIRE
LOAD PER PHASE
WIRE
SIZE
-DESCRIPTION-
NEXT TO BACK DOOR
AMPS: 400-MLO
BRK
SIZE
1.0
0.8
-
13
C
1.0
1.0
VOLTAGE: 208Y/120V
NEMA 1
B
1.2
12
35.0
FLUSH MOUNTED
A
1.2
14
0
10.6
10
PANEL: B
LOAD PER PHASE
WIRE
SIZE
8
0
0
13.7
1.
2.
-DESCRIPTION-
POLE
3 PHASE, 4 WIRE
AMPS: 200-MLO
6
1.8
9
CONVECTION OVEN
WIRE
SIZE
30
4
3.7
1.2
BRK
SIZE
2
3
7
CKT#
3.3
5
SPACE
NEMA 1
LOAD PER PHASE
WIRE
SIZE
VOLTAGE: 208Y/120V
NEXT TO BACK DOOR
208 V
1.25
24.5
1.5
30.7
3 PHASE
85.1
WALK IN COOLER COMPRESSOR/EVAP.
NEUTRAL BUS
208 V
TOTAL AMPS @
GROUNDING ELECTRODE CONDUCTOR TO PRIMARY
GROUNDING ELECTRODE SIZED AS INDICATED ON
POWER RISER DIAGRAM.
2.5
EXOTHERMIC WELD TO EFFECTIVELY
GROUNDED BUILDING STEEL WHERE
AVAILABLE, PER NEC 250.52(A)(2),
BONDING JUMPER #4 AWG CU.
CONNECTION TO GROUND
RING, PER NEC 250.66(C),
NOT REQUIRED TO BE LARGER
THAN THE GROUND RING
CONDUCTOR.
400/3/300
CONNECTION TO ROD, PIPE OR PLATE
ELECTRODE, PER NEC 250.66(A), NOT REQUIRED
TO BE LARGER THAN #6 AWG CU.
BOLTED TYPE CONNECTION
OR EXOTHERMIC WELD.
NOTE 5&13
NOTE 7
100.5
3 PHASE
2.5
97.2
1405 HILLSBOROUGH ST
RALEIGH, NC 27605
LIC.#: P-0990
P:919-341-4247
F:919-890-3797
plumbing mechanical electrical
269.9
NOTE 9
PANEL
A
PANEL
B
PANEL
H
400A MLO
208Y/120V
200A MLO
208Y/120V
100A MLO
208Y/120V
NOTE 13
NOTE 13
NOTE 13
M
CONNECTION TO CONCRETE ENCASED
ELECTRODE, PER NEC 250.66(B), NOT
REQUIRED TO BE LARGER THAN #4 AWG CU.
HAND HOLE FOR
INSPECTION.
1.0
NOTE 10
NOTE 14
GROUND CLAMP ON EFFECTIVELY
GROUNDED METALLIC WATER MAIN,
PER NEC 250.52(A)(1)
maple
ENGINEERING, pllc
TOTALS
INTERSYSTEM BONDING
TERMINATION BUS, PER
NEC 250.94, BONDED WITH
MINIMUM #6 AWG CU.
6/16/14
UTILITY
XFMR
300 kVA
NOTE 4
HAND HOLE FOR
INSPECTION.
GRADE
TAZIKIS, SUITE 250
FINISHED GRADE
20' MIN.
TO SERVICE #1
METER CENTER
NOTE 3 & 6
CU GROUND ROD
CONCRETE ENCASED ELECTRODE PER
NEC 250.52(A)(3). 1/2" REBAR OR #4
BARE COPPER (MINIMUM).
BARE COPPER #2 AWG MINIMUM
CONDUCTOR GROUND RING BURIED
AT LEAST 30" BELOW GRADE, MIN. 20'
LONG PER NEC 250.52(A)(4)
NOTE 8
BELOW FINISH
GRADE, NEC
250.52(A)(5)
1
ELECTRICAL POWER RISER
NO SCALE
RISER DIAGRAM NOTES:
NONMETALLIC PROTECTIVE SLEEVE
1.
ALL EXISTING ITEMS ARE SHOWN IN FAINT. NEW ITEMS ARE SHOWN IN BOLD.
2.
E.C. TO CONFIRM RISER BEFORE BEGINNING WORK. CONTACT ENGINEER IF SIGNIFICANT
DISCREPANCIES ARE FOUND.
3.
NOTE:
GROUNDING ELECTRODES SHALL BE PROVIDED IN ACCORDANCE WITH NEC
SECTION 250. ALL GROUNDING ELECTRODE CONDUCTORS SIZED AS
INDICATED ON POWER RISER DIAGRAM. ALL METHODS OF CREATING THE
GROUNDING SYSTEM MAY NOT BE REQUIRED OR AVAILABLE.
2
GROUNDING DETAIL
SECONDARY CONDUCTORS SIZED, PROVIDED & INSTALLED BY E.C.. CONFIRM INSTALLATION W/
UTILITY BEFORE BEGINNING WORK. RE-USE EXISTING 4" CONDUIT TO EXTENT POSSIBLE. FIELD
SHORT CIRCUIT CALCULATION
VERIFY.
4.
MAXIMUM AVAILABLE FAULT CURRENT IS BASED ON A THE TX KVA, IMPEDANCE (%Z),
WIRE SIZE & LENGTH SHOWN BELOW. CONTRACTOR SHALL NOTIFY ENGINEER
IMMEDIATELY IF TRANSFORMER CHARACTERISTIC INDICATE A HIGHER FAULT CURRENT
IS POSSIBLE (HIGHER KVA, LOWER IMPEDANCE, LARGER SECONDARY WIRE, SHORTER
SECONDARY LENGTH, ETC).
NO SCALE
TX KVA
TX %Z
VOLTAGE
PHASE
# COND. WIRE SIZE
(COPPER)
300
2.5
208
3
1
CURRENT
(L TO L)
MULT.
(ISC)
TX ISC
f
M
833
40.00
33309
350kcmil
WIRE L.
(FEET)
50
ISC (AMPS)
320A METER BASE PER UTILITY REQUIREMENTS. METER BY UTILITY.
5.
SERVICE ENTRANCE RATED WEATHERPROOF DISCONNECT SIZED AND FUSED AS INDICATED.
6.
(4)#350kcmil CU, USE EXISTING 4" CONDUIT.
7.
(4)#350 kcmil, 2 1/2" CONDUIT.
8.
#1/0 CU MAIN GROUNDING ELECTRODE CONDUCTOR TO GROUNDING SYSTEM (SEE DETAIL).
BUILDING SHALL HAVE ONE GROUNDING ELECTRODE SYSTEM.
WIRE "C"
22736
9.
(4)#1/0 CU, #8 GND, 1 1/4" CONDUIT.
10. (4)#2 CU, #8 GND, 1 1/4" CONDUIT.
11. PROVIDE PLACARD AT PANEL(S)/DISCONNECT(S) INDICATING SUITE/TENANT & PANEL SERVED.
12. PROVIDE PLACARD INDICATING AVAILABLE AIC FAULT CURRENT (NEC 110.24)
13. ELECTRICAL DISTRIBUTION SYSTEM TO HAVE AN OVERALL AIC AND SHORT CIRCUIT RATING OF
0.6100
0.6211
20689
Project Number :LAG-1404
Drawn By: MJL, RDG, RSA
Date: 06-16-14
22K AMPS. CIRCUIT BREAKERS WITH A LESSER LABELED AIC RATING MAY BE USED IF THOSE
BREAKERS ARE PAIRED WITH AN UPSTREAM BREAKER OR FUSE AS PART OF A UL SERIES RATED
COMBINATION. PAIRED DEVICES MUST BE IN ACCORDANCE WITH NEC 240.86. LABEL PER NEC
110.22(C). CONFIRM W/ EQUIPMENT MFG BEFORE PURCHASE. E.C. TO PROVIDE FIELD INSPECTOR
WITH MFG'S DOCUMENTATION REGARDING UL SERIES RATING OF PAIRED BREAKERS/FUSES.
14. (4) #350 kcmil CU, #3 CU GND, 2 1/2" CONDUIT.
E-4
PANEL
SCHEDULE
& RISER
FIRE RATING LEGEND
1-HR WALL
NOTIFICATION DEVICES
F
INPUT DEVICES
FS
TS
F
BACK FLOW
PREVENTER
FIRE ALARM
CONTROL
PANEL
FS
F
PULL
STATIONS
T
A
TEMPERATURE SENSOR
F
S
TWO DEDICATED
TEL. LINES
TS
SPRINKLER RISER
120V
A
S
ANSUL
(HOOD)
D
D
1.
SMOKE DETS.
RISER NOTES:
1.
2.
3.
FIRE ALARM SYMBOL LEGEND
GENERAL FIRE ALARM NOTES
2.
FIRE ALARM SYSTEM IS EXISTING. COORDINATE NEW DEVICES WITH EXISTING FA SYSTEM TYPE,
MODEL, AND REQUIREMENTS. PROVIDE ALL PROGRAMMING AND FINAL CONNECTION BY A
FACTORY TRAINED TECHNICIAN.
FIRE ALARM CONTROL PANEL, SEMI-FLUSH MOUNTED.
THE FIRE ALARM CONTRACTOR IS TO BE HELD TO THE SAME
REQUIREMENTS AS THE ELECTRICAL CONTRACTOR. FIRE ALARM
CONTRACTOR SHALL REVIEW ELECTRICAL PLANS AND
ELECTRICAL "GENERAL NOTES" BEFORE COMPLETING BID.
FIRE ALARM CONTRACTOR IS TO VERIFY EXISTING FIRE ALARM
SYSTEM HAS BATTERY AND VOLTAGE CAPACITY TO HANDLE
ADDITIONAL DEVICES. PROVIDE FIRE ALARM SHOP DRAWINGS IF
REQ'D TO LOCAL AHJ.
EXISTING FIRE ALARM DEVICES ARE SHOWN IN FAINT. NEW OR RELOCATED DEVICES ARE
SHOWN IN BOLD.
3.
RISER IS GENERIC IN NATURE. CONTRACTOR TO FIELD VERIFY EXACT LAYOUT AND
EQUIPMENT PRESENT.
4.
ELECTRICAL CONTRACTOR SHALL PROVIDE AN UPDATED FIRE
ALARM LAYOUT PLAN AT THE FACP.
5.
TESTING OF THE FIRE ALARM SYSTEM SHALL BE THE RESPONSIBILITY
OF THE ELECTRICAL CONTRACTOR.
FIRE ALARM RISER DIAGRAM
4
ALL FIRE ALARM WIRING SHALL BE IN CONDUIT OR AS ALLOWED
BY NEC OR LOCAL AHJ.
AN
FIRE ALARM SYSTEM ANNUNCIATOR PANEL, 48" A.F.F.
F
FIRE ALARM SYSTEM MANUAL PULL STATION, 48" A.F.F.
F
FIRE ALARM SYSTEM ALARM INDICATING DEVICE, HORN/STROBE, 80" A.F.F.
S
FIRE ALARM SYSTEM ALARM INDICATING DEVICE, STROBE, 80" A.F.F.
F
FIRE ALARM SYSTEM ALARM INDICATING DEVICE, HORN/STROBE, CEILING.
S
FIRE ALARM SYSTEM ALARM INDICATING DEVICE, STROBE, CEILING.
M
FIRE ALARM SYSTEM ALARM INDICATING DEVICE, MINI-HORN. 80" A.F.F.
H
FIRE ALARM SYSTEM ALARM INDICATING DEVICE, MINI-HORN/STROBE 80" A.F.F.
S
FIRE ALARM SYSTEM CEILING MOUNTED SMOKE DETECTOR, MULTI-MODE TYPE.
"R" INDICATES FOR ELEVATOR RECALL FUNCTION AND INTERLOCK WITH ELEVATOR
CONTROLLER.
D
FIRE ALARM SYSTEM DUCT SMOKE DETECTOR, PROVIDED AND WIRED BY E.C., INSTALLED BY
M.C.
NO SCALE
FIRE ALARM SYSTEM
INPUT/OUTPUT MATRIX
SYSTEM OUTPUTS
C
A
A
A
SYSTEM INPUTS
NOTIFICATION
B
C
D
E
F
G
H
I
J
MAGNETIC DOOR HOLDER (SUPPLIED WITH DOOR HARDWARE), CONNECT TO LOCAL
SMOKE DETECTOR.
TS
FIRE ALARM SYSTEM TAMPER SWITCH. FIELD COORDINATE EXACT QUANTITY AND
LOCATIONS.
FS
FIRE ALARM SYSTEM FLOW SWITCH. FIELD COORDINATE EXACT QUANTITY AND LOCATIONS.
REQUIRED FIRE SAFETY CONTROL
TU
A
C TE
TU
C
O
A
A
C TE MM
TU
O
A
U
A AT
D NA
C
TU E C IBL LA
E
R
M
A AT OM
A
C
TU E A MO LA SIG
R
U
N
N
M
A AT
D
A
S
C
TU E C IBL UP SIG L I
E
ER N ND
O
A
A
IC
VI AL
C TE MM SU
TU
A
PE SO
O
A
TO
A AT UD N T RV RY
R
C
I
E
R
B
I
TU
ZO LE OU SO SIG
D AT
N
B RY
N
T
IS
E
LE
R
SI AL
O
PL E G
O
G
U
S
IN
R
TR AY EN
D
D BL IGN NA
E
IC
E
E
L
C
A
R
A
V
A
H
S
N
TO
SM AN AL ICE IG L IN
N
E
R
D
G
A
IT
V
A
IC
FI E O AC DD L
A
R
R
U
TO
F
E
E
A
R
TI SS
A ST
LA A
O
R
R TU N S ALA
EL
M
S
IG
E
R
SI
M
N
R AS
G
A
EC E
N
L IND
A
M
A
IC
L
A
L
R
TO
A
EC L E GN
TO
C
LE ET
A
R
EN
VA IC
A LL
T
A
C
R
TU EL TO LL
A
Y
L
A EV R
TE A
ST
TO HE
A
LD
W TO
R
TI
R
EC
A
C
O
D
R
LO
N
O
A
N TO
O
L
I
SE
N
A
L
R
G
LT
U
S
F
A
LO
N
TO E
LO LL
R
EL NA OR
SH CK SM
EV TE
O
EX
U
K
A
T
TO RE
D ITS E D
A
O
R CA
C
A
A
W
TU
M
C
LL
N
N
A
PE
D
A
B
A
C
R
S FLO
C TE RE
O
S
S
TU
FL
O
N
P
R
O EC TR
A AT
O
C
TU E S R TIV OL
P
D
E
T
A
R
O
A
TE AIR
E
O
I
SM W SS R H RS
EL U
A
A
R
O
N
L
C
K
TI
P IZA D
E
VA
EX RE TI LIN
SS ON G
TE
H
EQ
A
H
U UR
O
U
ST
IZ
O
IP
A
D
M
TI
EX
EN
O
N
H
T
A
U
ST
,D
IS
A
B
LE
H
O
O
D
M
A
K
EU
P
FACP ANNUNCIATION
DH
N
O
TI
A
N
T
O
R
S
TI
L
A
TO
A
T
VA
TR L S
E
EN RA
EL
C
T
M
O
TO EN
C
L
FR
A
N
TO
ER
G
L
I
W
A
S
Y GN
PO
R
I
F
O
SO E S
I
L
V BL
R
VA
O
PE OU
M
U
R
E
S
T
R
IT
IT
ED
SM SM
Y
N
N
A
A
A
EL
TR TR
D
K
L
M N
O
P
Q
R
S
T
U
V W X
Y
1
FIRE ALARM SYSTEM AC POWER FAILURE
1
2
FIRE ALARM SYSTEM LOW BATTERY
2
3
OPEN CIRCUIT
3
4
GROUND FAULT
4
5
NOTIFICATION APPLIANCE CIRCUIT SHORT
5
6
BUILDING MANUAL PULL STATIONS
6
7
CORRIDOR SMOKE DETECTORS
7
8
AREA SMOKE DETECTORS
8
9
HVAC AIR DUCT SMOKE DETECTORS
9
10
AREA HEAT DETECTORS
10
11
HOOD OR ROOM FIRE SUPPRESSION SYSTEM ALARM
11
12
SPRINKLER TAMPER SWITCH
12
13
SPRINKLER WATER FLOW IN BUILDING
13
14
SPRINKLER WATER FLOW IN ELEV EQUIP RM OR SHAFT
14
15
ELEV EQUIP RM AREA SMOKE DETECTOR
15
16
ELEV SHAFT AND ELEV EQUIP RM HEAT DETECTORS
16
17
ELEV LOBBY SMOKE DETECTORS - UPPER FLOORS
17
18
ELEV LOBBY SMOKE DETECTOR - RECALL FLOOR
18
19
ELEV CONTROLLER POWER SHUNT TRIP STATUS
19
20
FIRE PUMP POWER FAILURE/PHASE REVERSAL
20
21
FIRE PUMP RUNNING
21
22
FIRE PUMP SYSTEM NOT IN AUTOMATIC
22
23
LEGALLY REQUIRED GENERATOR SYSTEM LOW FUEL
23
24
LEGALLY REQUIRED GENERATOR NOT IN AUTOMATIC
24
25
AREA OF REFUGE TWO-WAY COMMUNICATIONS STATUS
25
26
-
26
27
-
FIRE ALARM SYSTEM ROOM TEMPERATURE SUPERVISORY SWITCH. ALARM SHALL INDICATE A
T
COORDINATE EXACT QUANTITY AND LOCATIONS.
120V MULTI-STATION SMOKE DETECTOR WITH BATTERY BACK-UP. CONNECT TO NEAREST 120V
CIRCUIT. FOR UNITS WITH 2 OR MORE SMOKE DETECTORS, DETECTORS MUST BE INTERLOCKED
SUCH THAT THEY ALL ALARM AT ONE TIME.
"ADA" - UNITS SHALL HAVE 177CD STROBE NOTIFICATION IN SLEEPING AREAS.
SD
A
ANSUL HOOD SYSTEM "ALARM" OUTPUT.
F
NEW OR RELOCATED DEVICE
F
EXISTING DEVICE TO REMAIN
F
DEMO'D DEVICE OR DEVICE TO BE RELOCATED.
GENERAL NOTES - THIS SHEET
1.
3
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
Q
R
S
T
U
V
W
V
maple
TAGGED NOTES - THIS SHEET
FIRE ALARM NOTIFICATION DEVICES NOT PROVIDED AS FIRE
ALARM IS NOT REQUIRED FOR SPACE PER 2012 NC FIRE
CODE SECTION 904. BUILDING IS SEPARATED MIXED-USE.
W
FIRE ALARM DEVICE MATRIX
ENGINEERING, pllc
1405 HILLSBOROUGH ST
RALEIGH, NC 27605
LIC.#: P-0990
P:919-341-4247
F:919-890-3797
HOOD FIRE SUPPRESSION SYSTEM TO BE INTERLOCKED
TO BLDG FIRE ALARM SYSTEM. UPON ACTIVATION OF
HOOD SUPPRESSION SYSTEM BLDG FIRE ALARM
SYSTEM IS TO ACTIVATE.
1
27
A
6/16/14
2
MANUAL PULLSTATIONS OMITTED AS THEY ARE NOT
REQUIRED PER 2012 NCFC SEC (907.2.1 GROUP A
EXCEPTION). BUILDING FIRE SPRINKLER SYSTEM IS
INTERLOCKED WITH BLDG FA SYSTEM. CONTRACTOR
TO VERIFY INTERLOCK BEFORE BEGINNING WORK.
3
NEW FIRE ALARM INPUT DEVICE.
plumbing mechanical electrical
NO SCALE
ROOF DECK/FLOOR ABOVE
MEN
INSTALL PER NEC
MOUNT ON
APPROVED BOX
MOUNT NOTIFICATION
DEVICES ON
APPROVED BOXES
6" MIN.
SUPPLY DIFFUSER
OR RETURN/EXHAUST OPENING
SMOKE/HEAT
DETECTOR
2
STORAGE
CONDUIT
HALL
DINING AREA 4
WOMEN
DINING AREA 3
DINING AREA 2
1'-0" MAX.
CEILING
0'-4" MIN.
3'-0" MIN.
HORN STROBE
GRAPHIC
ANNUNCIATOR
EXIT
HORN
STROBE
4" MIN.
TO GO
ORDERS
SMOKE/HEAT
DETECTOR
FACP
BACK
HALL
CAN WASH
CUSTOMER QUEUE
RTU
3'-8"
(3'-6" MIN.
4'-0" MAX.)
8'-0" MAX.
(TOP OF DEVICE)
5'-0" MAX.
6'-8" MIN.
(BTM OF DEVICE)
HINGED
SIDE
D
3
2
2
3
MANUAL
PULL STATION
RTU
D
FRONT KITCHEN
A
1
OFFICE
3
DINING AREA 1
NOTE:
NFPA 72 & ADA DEVICES
INSTALLATION REQ'S
3
CATERING
STORAGE
RTU
D
A
1
Project Number :LAG-1404
Drawn By: MJL, RDG, RSA
Date: 06-16-14
FLOOR
2
FIRE ALARM DEVICE LOCATIONS
NO SCALE
3
PREP KITCHEN/
DRY STORAGE
1
FIRE ALARM PLAN
SCALE: 1/8" = 1'-0"
FA-1
FIRE
ALARM
PLAN