BATTERY COOLER
BATTERY COOLER
Batteries in telecom cabinets function as a backup in case of power
failure and are essential to assure the continuity
of the data flow.
The best working temperature range
for battery banks is around 25 °C; is
very important to maintain the correct
temperature for the battery banks, in
fact, if the cabinet temperature goes
too higher the batteries life could be
shortened .
In Telecom cabinets and electronic facility rooms are, however,
present some devices which can work at higher temperature.
In this case the best solution is to separate the cabinet in two areas with
a different temperature control: one area dedicated to the batteries
and maintained the correct temperature and protect from dust , wind,
etc.; whereas the other area can be maintened at higher temperature.
In this way is possible to significantly reduce the energy consumption
for cooling.
Stulz range of air conditioners fulfill the requirements of battery
banks cooling :
EVE04
EVO04
air conditioner
for installation
inside the cabinet
air conditioner
for installation
outside the cabinet
Furthermore, both EVE and EVO units
are powered at 48VDC, like the
battery banks, so there’s no need
to have an inverter to transform the
Direct current in Alternate Current,
with considerably energy costs
savings.
EVE04
• Powder painted steel plate
• Alternative hermetic compressor including protection
• Centrifugal condenser fan with thermic protection
• Axial evaporator fan with thermic protection
• Refrigerant R134a
• Condenser coil in copper pipe and hydrophillic aluminium fins
• Evaporator coil in copper pipe and aluminium fins
• Refrigerant high pressure safety switches
• Regulation electronic thermostat set at 25°C, regulation range 25-35°C, differential 2°C
• Outputs:
- high temperature alarm
- low temperature alarm
- high pressure alarm
- probe malfunctioning alarm
• Input:
- remote enable
CODE
POWER SUPPLY
COOLING CAPACITY L35L35
AIR FLOW
EXTERNAL OPERATING CONDITIONS
INTERNAL OPERATING CONDITIONS
NOISE LEVEL
DIMENSIONS (H X W X D)
EVE0400212
V DC
48
W
400
mc/h
290
°C
+20 / +55
°C
+25 / +35
db(A)
65
mm
634 / 308 / 221
EVO04
• Powder painted steel plate
• Alternative hermetic compressor including protection
• Centrifugal condenser fan with thermic protection
• Axial evaporator fan with thermic protection
• Refrigerant R134a
• Condenser coil in copper pipe and hydrophillic aluminium fins
• Evaporator coil in copper pipe and aluminium fins
• Dehidrating filter and capillary tube
• Refrigerant high pressure safety switches
• Low temperature (ambient) device
• Regulation mechanical thermostat set at 25°C, regulation
range 25-35°C, differential 4°C
CODE
POWER SUPPLY
COOLING CAPACITY L35L35
AIR FLOW
EVO0400212
V DC
48
W
400
mc/h
290
EXTERNAL OPERATING CONDITIONS
°C
-20 / +55
INTERNAL OPERATING CONDITIONS
°C
+25 / +35
NOISE LEVEL
DIMENSIONS (H x W x D)
db(A)
65
mm
634 / 308 / 221