920 Installation Manual - Pentair Thermal Management

Transcription

920 Installation Manual - Pentair Thermal Management
920 Series Heat Trace Controller
Installation, Operating and Maintenance Instructions
Firmware versions # up to V3.2X
Ra
yc
he
A
m
92
0
B
SH
IFT
AL
CK
RI
AR
A/B
LO
SE
M
MO
NIT
OR
BA
CK
CO
ES
PR
O
HE GRAM
AT
TR MAB
AC LE
ING DU
CO AL
NT PO
RO INT
LLE
R
Tx
NF
IG
EN
TER
Rx
ST
AT
U
S
AL
AR
OU
M
TP
UT
Ra
yc
he
m
92
0
SH
IFT
AL
CK
RI
ES
AR
A/B
LO
SE
M
MO
NIT
OR
BA
CK
CO
NF
IG
EN
TER
ST
AT
U
S
AL
AR
OU
M
TP
INDUSTRIAL HEAT TRACING SOLUTIONS
EN- Raychem920series-IM-H56874 05/15
UT
1 / 82
Contents
Introduction......................................................................................................................................................4
Certification........................................................................................................................................... 4
Limited Warranty................................................................................................................................... 4
Warranty Exclusion/Disclaimer............................................................................................................ 4
Exclusive Remedies.............................................................................................................................. 4
Conducted and Radiated Emissions—FCC/DOC Statement of Compliance........................................ 4
What’s New.......................................................................................................................................................5
New Controller Features....................................................................................................................... 5
New Operator Console Features........................................................................................................... 5
Section I – Overview..........................................................................................................................................6
1.1 Controllers Covered by this Manual............................................................................................... 6
1.2 Product Overview............................................................................................................................ 6
1.3 Modular Components..................................................................................................................... 8
1.4 Controller Assemblies.................................................................................................................... 9
1.5 Ordering and Configuration Guide................................................................................................. 9
Section 2 – Installation and Wiring.................................................................................................................11
2.1 Introduction.................................................................................................................................. 11
2.2 Initial Inspection........................................................................................................................... 11
2.3 Operator Safety Considerations................................................................................................... 11
2.4 Operating Environment................................................................................................................ 11
2.5 Installation Location..................................................................................................................... 11
2.6 Mounting Procedures................................................................................................................... 11
2.7 Wiring............................................................................................................................................ 13
2.8 Initial Power-up............................................................................................................................ 16
2.9 Setup for the 920.......................................................................................................................... 17
Section 3 – Programming and Configuration..................................................................................................18
3.1 Introduction.................................................................................................................................. 18
3.2 Front Panel Features.................................................................................................................... 18
3.3 920 Operator Console Display...................................................................................................... 19
3.4 920 Functions............................................................................................................................... 19
3.5 Control Point Setup...................................................................................................................... 19
3.6 Common Controller Setup........................................................................................................... 28
3.7 Temperature Alarms.................................................................................................................... 30
3.8 Other Alarms................................................................................................................................ 33
3.9 Communications Setup................................................................................................................ 40
3.10 Operator Console Functions....................................................................................................... 43
3.11 Copy Configuration Functions (V3.11 and up)............................................................................ 44
Section 4 – Monitored Parameters.................................................................................................................46
4.1 Introduction.................................................................................................................................. 46
4.2 Analog Readings........................................................................................................................... 46
4.3 Maintenance Data......................................................................................................................... 47
Section 5 – Control Modes..............................................................................................................................49
5.1 Introduction.................................................................................................................................. 49
5.2 Switch Control Modes................................................................................................................... 49
5.3 Load Shedding Control Mode....................................................................................................... 51
5.4 TEMPBUS™ Control Mode........................................................................................................... 52
INDUSTRIAL HEAT TRACING SOLUTIONS
EN- Raychem920series-IM-H56874 05/15
2 / 82
Section 6 – Troubleshooting...........................................................................................................................53
6.1 Operator Checks .......................................................................................................................... 53
6.2 Common Problem Areas.............................................................................................................. 53
6.3 Common Alarms—What to look for ............................................................................................. 56
6.3 Common Alarms—What to look for (Continued).......................................................................... 57
6.3 Common Alarms—What to look for (Continued).......................................................................... 58
Section 7 – Maintenance.................................................................................................................................59
7.1 Operator Maintenance.................................................................................................................. 59
7.2 Replaceable Parts........................................................................................................................ 59
Appendix A Specifications...............................................................................................................................60
Appendix B Typical Enclosure Dimensions....................................................................................................62
B.1 Single-Point Assemblies #10160-003 and #10160-009.............................................................. 62
B.2 Dual-Point Assemblies #10160-120 and #10160-121................................................................. 63
B.3 Four-Point Assembly #10160-125................................................................................................ 64
B.4 Eight-Point Assembly #10160-035............................................................................................... 65
B.5 Twenty-Point Assembly #10160-045............................................................................................ 66
Appendix C Wiring Diagrams..........................................................................................................................67
C.1 TS Wiring...................................................................................................................................... 67
C.1.2 100Ω NICKEL IRON RTD WIRING............................................................................................... 68
C.2 Power Wiring................................................................................................................................. 69
C.3 Communication Wiring C.3 Communication Wiring..................................................................... 70
C.4 Alarm Output Wiring..................................................................................................................... 70
C.5 External Input/Output Port Wiring................................................................................................ 72
Appendix D HTC Load Shedding Sequence.....................................................................................................73
Appendix E 100 Ω Platinum RTD Table...........................................................................................................74
Appendix F 100 Ω Nickel-Iron RTD Table........................................................................................................75
Appendix G Factory Default/Configuration Sheets.........................................................................................76
G.1 Configuration Sheet V3.00............................................................................................................ 76
G.2 920 Series HTC Configuration Sheet V3.1X and V3.2X................................................................. 79
INDUSTRIAL HEAT TRACING SOLUTIONS
EN- Raychem920series-IM-H56874 05/15
3 / 82
Introduction
Installation and Maintenance Instructions for Firmware Versions up to and Including V3.2X
This manual provides information pertaining to the installation, operation, testing, adjustment,
and maintenance of the Raychem Model 920 Series Heat Trace Control and Monitoring products.
Additional copies of the operating manual may be ordered separately through your Pentair
Thermal Managament representative or online at www.thermal.pentair.com using the document
number H56874.
Notice: The information contained in this document is subject to change without notice.
Certification
Pentair Thermal Managament certifies that this product met its published specifications at the
time of shipment from the Factory.
Limited Warranty
This Pentair Thermal Managament product is warranted against defects in material and
workmanship for a period of 18 months from the date of installation or 24 months from the date of
purchase, whichever occurs first. During the warranty period, Pentair Thermal Managament will,
at its option, either repair or replace products that prove to be defective.
For warranty service or repair, this product must be returned to a service facility designated by
Pentair Thermal Managament. The Buyer shall prepay shipping charges to Pentair Thermal
Managament and Pentair Thermal Managament shall pay shipping charges to return the product
to the Buyer. However, the Buyer shall pay all shipping charges, duties, and taxes for products
returned to Pentair Thermal Managament from another country.
Pentair Thermal Managament warrants that the software and firmware designated by Pentair
Thermal Managament for use with the Raychem 920 Controller will execute its programming
instructions properly. Pentair Thermal Managament does not warrant that the operation of the
hardware, or software, or firmware will be uninterrupted or error-free
Warranty Exclusion/Disclaimer
The foregoing warranty shall not apply to defects resulting from improper or inadequate
maintenance by the Buyer, Buyer-supplied software or interfacing, unauthorized modification or
misuse, operation outside of the specifications for the product, or improper installation.
No other warranty is expressed or implied. Pentair Thermal Managament disclaims the implied
warranties of merchantability and fitness for a particular purpose.
Exclusive Remedies
The remedies provided herein are the buyer’s sole and exclusive remedies. Pentair Industrial Heat
Tracing Solutions shall not be liable for any direct, indirect, special, incidental, or consequential
damages, whether based on contract, tort, or any other legal theory.
Conducted and Radiated Emissions—FCC/DOC Statement of Compliance
This equipment has been tested and found to comply with the limits for a Class A digital device,
pursuant to Part 15 of the FCC rules. These limits are designed to provide reasonable protection
against harmful interference when the equipment is operated in a commercial envi-ronment.
This equipment generates, uses, and can radiate radio frequency energy and, if not installed
and used in accordance with the instruction manual, may cause harmful interference to radio
communications. Operation of this equipment in a residential area is likely to cause harmful
interference, in which case the user will be required to correct the interference at his own
expense.
This equipment does not exceed Class A limits for radio emissions as set out in Schedule V to VIII
of the Radio Interference Regulations of Communication Canada.
Cet apparel respecte les limites de bruits radioelectriques applicables aux appareils numeriques
de Classe A prescrites dans la norme sur le materiel brouilleur: “Appareils Numeriques,” NMB003 edictee par le Ministre des Communications.
INDUSTRIAL HEAT TRACING SOLUTIONS
EN- Raychem920series-IM-H56874 05/15
4 / 82
What’s New
This section provides a summary of the new features that have been added since the last version
of this manual was printed. It is assumed that the reader is already familiar with the earlier
versions of the 920 Controller.
New Controller Features
• Alarm filtering is now available for:
– LOW and HIGH TS ALARMS (see sections 3.7.7 on page 33 and 3.7.8 on page 34)
– LOW and HIGH CURRENT ALARMS (see sections 3.8.2 on page 35 and 3.8.4 on page 36)
– HIGH GFI ALARMS (see section 3.8.6 on page 36)
– LOW and HIGH VOLTAGE ALARMS (see sections 3.8.9 on page 37 and 3.8.11 on page 38)
– LOW and HIGH RESISTANCE ALARMS (see sections 3.8.13 on page 38 and 3.8.15 on page 39).
Alarm filtering will prevent an alarm from being indicated until the alarm condition has existed for
the duration of the alarm filter time.
• Two new SWITCH CONTROL MODES have been added for use with Ambient Temperature control:
– Proportional Ambient SSR
– Proportional Ambient Contactor (see sections 3.5.3 on page 21 and 5.2 on page 50).
• ASCII and RTU ModBus™ communications protocol support (see section 3.9.1 on page 42).
• Support for an isolated, 2-wire RS-485 communications interface (see section 1.4.5).
• A 3-phase power calculation feature has been included for use with balanced, Y-connected
heating loads (see section 3.5.10 on page 23).
• A Temperature Sensor (TS) Fail Mode feature is now available to allow the output to be forced
ON or OFF when a control temperature failure occurs (see section 3.5.11 on page 23).
• A TEMPBUS™ feature to allow one “master” 920 controller to share its temperature sensor
information with up to 25 “slave” controllers (up to 50 control points). This includes the addition
of three TS CONTROL MODES (see sections 3.5.12 on page 24 and 5.4 on page 53).
• Support for 100 ohm nickel-iron RTDs along with the standard 100 ohm platinum types (see
sections 3.5.13 on page 24 and 3.5.16 on page 25).
• Manual voltage source selection (see section 3.5.19 on page 26).
• Support for FORCE ON and FORCE OFF modes using the EXTERNAL input (see sections 3.5.27
on page 28 and 3.6.3 on page 29).
• Features to reload factory default parameters as well as copy configuration parameters from
one point to another are now included (see section 3.11 on page 46).
• New maintenance alarming to track contactor wear (see section 3.8.23 on page 42).
• Monitor PEAK LOAD CURRENT, PEAK GFI, and the EXTERNAL INPUT STATUS through
communications (see sections 4.3.6 on page 50, 4.3.7 on page 50, and 4.3.8 on page 50).
New Operator Console Features
• The ability to adjust the display scroll rate is now available (see section 3.6.10 on page 31).
• Maintenance data resetting is now supported (see section 4.3 on page 49).
• Display and reset the CONTACTOR CYCLE COUNTER (see section 4.3.3 on page 49).
• Limit the range of the CONTROL SETPOINT setting for 920 Operator Console users
(see sections 3.5.29 on page 29 and 3.5.30 on page 29).
• An UNLOCK DATABASE feature was added to the 920 Operator Console’s “Configuration Mode
Main Menu” (see section 3.10.3 on page 46).
• The display test no longer occurs at startup; instead, the user may activate it from a menu
option (see section 3.10.5 on page 46).
IMPORTANT WARNINGS AND NOTES
The following icons are used extensively throughout this manual to alert you to important
that affect safety and to important notes
that affect the proper operation of the
warnings
unit.
Be sure to read and follow them carefully.
INDUSTRIAL HEAT TRACING SOLUTIONS
EN- Raychem920series-IM-H56874 05/15
5 / 82
Section I – Overview
1.1 Controllers Covered by this Manual
This document covers the 920 Series of heat trace controllers and available options. The
information coincides with the specific releases of firmware for the 920 product which are listed
on the cover. As Pentair Thermal Managament releases new firmware to modify or enhance
the product significantly, new documentation will accompany these releases. To ensure that
you are using the correct documentation for your particular version of controller, please check
the firmware version number of the 920 against the version number listed on the front of this
manual. This can be displayed using the optional 920 Operator Console or a communicating
device. As subsequent changes are made, supplements to this document will be included in
manuals shipped after the firmware is released. Supplements will make specific reference to the
operational or functional changes.
1.2 Product Overview
1.2.1 DESCRIPTION
The 920 Series Heat-Tracing Controller controls, monitors, and communicates alarms and data
for one or two heating circuits. As a dual-point device, it offers a complete range of control and
monitoring features, as well as superior reliability compared to multipoint systems. Its modular,
scalable architecture yields cost-effective multipoint assemblies without the expense of additional
control points that are not required. Available for use with external solid-state relays (SSRs) or
contactors in either one-, two-, or three-pole configurations and the ability to switch loads up to
600 Vac makes the 920 the most versatile product on the market.
1.2.2 FEATURES
A detailed description of available features can be found in Section III of this manual. Highlights of
specific features are included in the following text.
Front Display
The control module includes LED status indicators to show output and alarm conditions. Using
the optional 920 Operator Console, the setpoint temperature, actual control temperature, and load
current are immediately accessible to plant operators and maintenance staff. The display units are
field selectable for °F or °C.
–40°F to 140°F (–40°C to 60°C) Operation
Extended temperature operation permits installation in all but the harshest environments. SSR
output modules are limited to operating ambient temperatures of 104°F (40°C) without derating.
Single or Dual Temperature Sensor Inputs
The ability to use one or two temperature sensor (TS) inputs for each control point allows the
selection of one of eleven control modes and programming of all temperature parameters.
High and Low Temperature Alarms
High and low temperature alarms are offered for both inputs of each control point.
High and Low Current Alarms
Low current alarm is more than just a continuity level alarm. The 920 offers full adjustment over
the entire current measurement range for both high and low current alarm limits.
Solid State or Contactor Output
The 920 is available with externally-mounted solid-state relay (SSR) output switches or contactors.
With the SSR option, the user may select a time-proportional control algorithm, a simple
deadband mode, or one of two ambient control algorithms. The contactor versions always use
either the deadband mode or the proportional ambient contactor mode. Switching device failure
alarms are supported for both types of output devices.
INDUSTRIAL HEAT TRACING SOLUTIONS
EN- Raychem920series-IM-H56874 05/15
6 / 82
Ground-Fault Alarm and Trip
Ground-fault (GF) current levels are monitored and displayed in milliamps. The availability of the
actual ground-fault level gives the user the choice of both alarm and trip levels suitable for the
particular installation. Using multiple SSRs or a multipole contactor allows all powered legs of
non-neutral circuits to be switched off under GF conditions.
Overcurrent Protection
A unique overcurrent protection algorithm greatly reduces the possibility of damage to the circuit
or the controller in the event of a temporary overload while allowing for initially high in-rush
currents (SSR options only).
Soft Starting
Given the circuit breaker size, the 920 will limit the energy let-through to help prevent nuisance
breaker trips due to cable in-rush. This feature makes the controller particularly attractive for use
with self-regulating cables (SSR options only).
Minimum/Maximum Temperature Tracking
The controller maintains the minimum and maximum temperature values seen by the controller
since the last reset of these values. This is helpful in determining causes of temperature alarms.
Latching/Non-Latching Temperature Alarms
User-selectable, non-latching temperature alarms allow the controller to automatically clear the
alarm when the condition no longer exists.
High and Low Voltage Alarms
Operating at voltages less than design can cause serious loss of heater output. The alarming of
preset voltage deviations ensures availability of sufficient wattage output.
Power Limiting
The 920 will control the maximum output wattage if the full load power exceeds the specified
maximum power setpoint. This feature eliminates the need for low voltage transformers in many
applications and can assist in standardization of heating cable types (SSR options only).
Autocycling
The controller will energize the circuit for 10 seconds at a programmable interval. Circuit alarms
will be generated at the time of autocycle instead of when the heat is required. This feature
eliminates the need for a preventive maintenance program as these tests are performed at regular
intervals by the controller.
Temperature Sensor Failure Alarm
Both open and shorted sensors are detected and alarmed by the controller.
Random Start
A startup delay between 0 and 9 seconds ensures that all units do not come on line at the same
time.
Full Digital Communications
An optional internal communications interface allows the communication of alarms and analog
data to a monitoring system. Industry-standard RS-232 or RS-485 serial communications are
available for applications requiring direct interfacing to other devices. The modem version
maintains compatibility with legacy products including the GCC-9000/780 Series (Group
Communications Controller). With the availability of the heat trace data at the user’s fingertips,
historical trending of temperatures, power consumption, or other parameters are available for
analysis and system optimization.
INDUSTRIAL HEAT TRACING SOLUTIONS
EN- Raychem920series-IM-H56874 05/15
7 / 82
CSA C/US and c-ETL-us Approved
The 920 series of controllers is approved for Class I, Division 2, Groups A,B,C,D and Zone 2
hazardous locations, making it ideal for direct installation in the field. This can save the significant
expense of wiring back to a central-ly-located electrical distribution center.
1.3 Modular Components
The 920 series controller is made up of a number of building blocks, allowing the ultimate in
design flexibility. Each component’s primary function is described below.
1.3.1 CONTROL MODULE
The 920 control module forms the heart of a single- or dual-point heat trace control solution. Each
plug-in module provides all of the intel-ligence required to control and monitor two independent
heat trace circuits. It includes indicators for alarm and output status and a connector for use with
a 920 Operator Console. An internal connector is provided to plug into an optional communications
interface.
The control module packaging provides a rugged, vibration-proof design. Once it is plugged into a
terminal board, the module is fastened using the two captive screws included as part of the rear
cover. It is important that these two screws be securely fastened whenever the module is powered.
1.3.2 TERMINAL BOARD
The terminal board eases maintenance and troubleshooting by providing a termination point for all
of the low-voltage signals. The 920 control module may be installed or removed without disturbing
the field wiring. Temperature sensor, communications, and alarm control wiring are connected to
the lever-operated spring terminals, providing gas-tight, vibration-resistant connections.
1.3.3 OPERATOR CONSOLE
A large, easy-to-read alphanumeric display and menu-driven interface ease controller
configuration and eliminate the need for an external programmer. The console may be left
installed permanently or may be installed temporarily for display/setup during maintenance and
trou-bleshooting. Access is available for all monitored parameters, programmed values, and
alarm information. Enhanced security is provided by password protection.
The unique design of the operator console allows it to be installed or removed under power, even
in hazardous areas.
1.3.4 SWITCH INTERFACE
Universal single-phase current monitoring, single- or 3-phase ground-fault detection, and voltage
monitoring are provided by the Switch Interface (SIS/SIC) module. One device is required for each
control point, and two versions are available: SIS for use with SSRs, and SIC for use with the
contactor. Both units also incorporate a universal power supply, allowing operation directly from
100 Vac to 277 Vac. Use with higher trace voltages is also possible, using a separate power source
or a small step-down transformer.
Redundant operation is supported, allowing a control module to automatically power itself from
either of two switch interface modules or both. This permits one heat-trace circuit to be turned off
for maintenance without affecting the operation of the other circuit.
1.3.5 COMMUNICATIONS INTERFACE
In applications where the user wishes remote configuration capability or wants to communicate
trace information and/or alarms to another device such as the GCC (Group Communications
Controller), an optional communications interface may be installed in the control module.
A modem version that maintains compatibility with legacy products is available, or other industrystandard interfaces such as RS-232 and RS-485 may be specified.
INDUSTRIAL HEAT TRACING SOLUTIONS
EN- Raychem920series-IM-H56874 05/15
8 / 82
1.3.6 SOLID-STATE RELAY OUTPUT MODULE
In applications where the benefits of solid-state control are desired, a modular solid-state relay
(SSR) is available. This component is easily installed on the outside of an enclosure using a single
3/4 NPT knockout and locknut providing a weatherproof seal. This allows the heat generated by
the SSR to be dissipated directly to the ambient air, without increasing the internal temperature of
the enclosure. When appli-cations require two-pole or 3-phase switching, multiple SSR modules
may be ganged together, allowing the same component to be used.
1.4 Controller Assemblies
Due to its modular packaging, the 920 easily supports single-, dual-, or multi-point configurations.
Factory standard assemblies are available in a variety of enclosure types, and panels made up
of multiple points are also available. Refer to the Ordering Guide in section 1.5 on page 10 for
a sample listing of available configurations. If your application requires a customized solution,
please contact your Pentair Thermal Managament representative for help in specifying an
assembly suited to your particular requirements.
1.5 Ordering and Configuration Guide
920 series control assemblies are ordered as three separate items:
Ra
yc
h
em
92
0S
ER
IES
Ra
SH
yc
A
he
m
B
SH
IFT
AL
CK
M
920
SE
NIT
OR
CO
LO
RIE
MO
S
CK
PRO
HEA GRAMM
T TRA ABL
CIN E DUA
G CON
L
TRO POINT
LLE
R
Tx
NF
BA
AL
AR
A/B
AR
A/B
LO
IFT
IG
CK
EN
TER
Rx
STA
TU
S
AL
M
MON
ITOR
CO
PROG
HEAT RAMM
TRAC ABLE
ING DUAL
CONT PO
ROLL INT
ER
NF
BA
IG
CK
EN
TE
R
ST
AT
US
AL
AR
OU
M
TP
UT
AR
OU
M
TP
Enclosure assembly
UT
Control module(s)
(One for every two circuits)
Optional operator
console(s)
Fig. 1.6 920 series control assemblies
Pentair Thermal Managament maintains a shelf stock of enclosure assemblies, control modules,
and consoles. All other enclosure assemblies are built to order. Not all options may be listed.
Contact your local representative for any special applications you may have.
INDUSTRIAL HEAT TRACING SOLUTIONS
EN- Raychem920series-IM-H56874 05/15
9 / 82
1.5.1 ENCLOSURE ASSEMBLY
Enclosure Assemblies
Description
Catalog number
Part number
Weight/lbs
10160-010
27
Raychem 920 controller–2 Pt in a 14" x 12" x 8" FRP 920*E4FWL*SIS302*SS3102*HTC485*CON 10160-011
enclosure with window and quick-release latches,
control module, and operator console. Includes an
isolated 2-wire RS-485 communication option. 1P
30 A 277 V SSR/pt. Controls two circuits, each with
a 1-pole solid-state relay. (Approved for Class 1, Div.
2 areas)
27
Raychem 920 controller–2 Pt in a 14" x 12" x 8" FRP 920*E4FWL*SIS302*SS3202*HTC*CON
enclosure with window and quick-release latches,
control module, and operator console. 2P 30 A 277 V SSR/pt. Controls two circuits, each with a 2-pole
solid-state relay. (Approved for Class 1, Div. 2 areas)
10160-012
32
Raychem 920 controller–2 Pt in a 14" x 12" x 8" FRP 920*E4FWL*SIS302*SS3202*HTC485*CON 10160-013
enclosure with window and quick-release latches,
control module, and operator console. Includes an
isolated 2-wire RS-485 communication option. 2P
30 A 277 V SSR/pt. Controls two circuits, each with
a 2-pole solid-state relay. (Approved for Class 1, Div.
2, areas)
32
Raychem–Raychem Supervisory Software
1
Raychem 920 controller–2 Pt in a 14" x 12" x 8" FRP 920*E4FWL*SIS302*SS3102*HTC*CON
enclosure with window and quick-release latches,
control module, and operator console. 1P 30 A 277 V
SSR/pt. Controls two circuits, each with a 1-pole
solid-state relay. (Approved for Class 1, Div. 2 areas)
Raychem Supervisor
10391-002
IMPORTANT: The NEC (and CEC) rules specify that all ungrounded—i.e., hot—legs of a circuit, must be switched in the event of a
ground fault. This means for 207 V single-phase applications, you must specify a 2-pole (2P) version if you are not using external GFI
breakers.
Control Modules
Raychem 920 controller–Control module only
920HTC
10260-001
1
920HTC*485
10260-004
1
920HTC*MDM
10260-002
1
920CON
10260-005
1
(No communications options installed)
Raychem 920 controller–Control module
with an isolated
2-wire RS-485 communication option installed
Raychem 920 controller–Control module
with modem
communications option installed
Operator Console
Raychem 920 controller–Operator console
Contact your local representative for other available configurations that are not
listed above.
INDUSTRIAL HEAT TRACING SOLUTIONS
EN- Raychem920series-IM-H56874 05/15
10 / 82
Section 2 – Installation and Wiring
CAUTION:
Be sure all personnel involved in installation, servicing, and programming are qualified and
familiar with electrical equipment, their ratings and proper practices and codes. Multiple voltages
and signal levels may be present during the installation, operation, and servicing of this product.
Do not power the product until the safety provisions outlined in this section have been observed.
2.1 Introduction
This section includes information on the initial inspection, preparation for use, and storage
instructions for the 920 series heat trace controller.
CAUTION:
Solid-state relay (SSR) modules may be extremely hot immediately after power is removed.
Exercise care when handling SSRs.
2.2 Initial Inspection
Inspect the shipping container for damage. If the shipping container or cushioning material is
damaged, it should be kept until the contents of the shipment have been verified for completeness
and the equipment has been checked mechanically and electrically. Procedures for configuring
and operating the heat trace controller are given in Section 3 on page 18. If the shipment is
incomplete there is mechanical damage, a defect, or the controller does not pass the electrical
performance tests, notify your Pentair Thermal Managament representative. If the shipping
container is damaged, or the cushioning material shows signs of stress, notify the carrier as
well as your Pentair Thermal Managament representative. Keep the shipping materials for the
carrier’s inspection.
2.3 Operator Safety Considerations
The standard 920 controller using solid-state relays is suitable for Class I, Division 2, Groups A,
B, C, D and Zone 2 hazardous areas. Haz-ardous areas are defined by Article 500 of the National
Electrical Code and Section 18 of the Canadian Electrical Code. Contactor-based assemblies are
suitable for use in ordinary (non-hazardous) areas only.
CAUTION:
Many wiring configurations will use more than one power source and all must be de-energized
prior to performing any maintenance on a controller circuit.
2.4 Operating Environment
The operating environment should be within the limitations described in the 920 heat trace
controller specifications outlined in Appendix A on page 61.
2.5 Installation Location
The wide ambient operating temperature range of the controller permits installation in any
convenient location. Considerations should include expected atmospheric conditions, accessibility
for maintenance and testing, the location of existing conduits, and hazardous area rating. Ambient
temperature conditions may affect load current ratings.
CAUTION:
Always be sure that the intended location is classified as an area that the product is approved for
as defined by Article 500 of the National Electrical Code and/or Part I, Section 18 of the Canadian
Electrical Code.
2.6 Mounting Procedures
Mounting hole dimensions for the standard enclosures are shown in Appendix B on page 63. If
possible, conduit entries should be made in the bottom of the enclosure to reduce the possibility
of water entry or leakage. Conduit entries must be drilled/punched following the enclosure
manufacturer’s recommendations. Use bushings suitable for the enclosure type and install
such that the completed installation remains waterproof. Grounding hubs and conductors must
be installed in accordance with Article 501-4(b) of the National Electrical Code and Part I of the
Canadian Electrical Code.
INDUSTRIAL HEAT TRACING SOLUTIONS
EN- Raychem920series-IM-H56874 05/15
11 / 82
The user may want to consider enclosure drain holes in applications where moisture is a problem;
drill 0.125" holes in the bottom of the enclosure on both the left and right sides. Two holes reduce
the possibility that one will plug and ensures drainage if the enclosure is not perfectly level.
Note that drilling holes in the enclosure compromises the NEMA 4 rating. Controllers should be
removed from the enclosure before any holes are drilled or cut to prevent damage due to flying
debris.
2.6.1 CONTROL MODULE INSTALLATION AND REMOVAL
CAUTION:
Always ensure that the power to the unit is turned off during installation or removal to avoid the
risk of injury and damage to the controllers.
WARNING:
Explosion Hazard! Do not install or remove the control module while the unit is powered.
Fig 2.1 Control module installation
The 920 series controller is designed to be mounted to a flat back plate/panel using a terminal
board. This plug-in design simplifies installation and maintenance by allowing all of the lowvoltage field wiring to remain undisturbed while a control module is installed or removed.
Installation of the control module is easily accomplished by plugging it into the connector on the
terminal board.
• The module is fully inserted once its rear cover is flush to the top surface of the terminal board.
The connectors are designed to be self-aligning, so no undue force should be required.
• Next, secure the module using the two captive screws provided (one located on each side of
the rear cover). These should thread easily into the terminal board. Be sure to align the screws
properly to avoid cross-threading them.
To remove the control module, loosen the two captive screws. Once they have been completely
loosened, they will float freely in their re-spective retaining collars without falling out. The module
may now simply be pulled straight out of its connection.
2.6.2 OPERATOR CONSOLE INSTALLATION AND REMOVAL
The operator console is designed to be easily installed or removed while the controller is
powered—even in Class I Division 2 and Zone 2 hazardous areas. It may be temporarily or
permanently installed.
The console is installed in three steps:
Step  “Hook” the lip provided on the rear cover of the console over the top edge of the control
module front plate.
Fig. 2.2 Console installation – Step 1
INDUSTRIAL HEAT TRACING SOLUTIONS
EN- Raychem920series-IM-H56874 05/15
12 / 82
Step  “Hinge” the bottom of the console downwards until it is flush with the front of the control
module.
Fig. 2.3 Console installation – Step 2
Step  If the console is to be permanently installed, secure it to the control module using the
captive screw provided. It should be finger tight only. Do not over-tighten the screw or damage to
the console housing may occur.
Fig. 2.4 Console installation – Step 3
To remove the console, follow the three steps outlined above in reverse order.
2.7 Wiring
Wiring diagrams for typical configurations are included in Appendix C on page 68.
CAUTION:
Always verify wiring connections before applying power to the controller or connected circuits. To
avoid injury or equipment damage, do not install or remove wiring while controller power is on.
To minimize the chance of loose connections, the terminal board uses lever-operated, springloaded terminals. See Appendix A on page 61 for allowable wire sizes and recommended
insulation strip lengths.
2.7.1 TEMPERATURE SENSOR CONNECTIONS
Use shielded, twisted, three-conductor wire for the extension of RTD leads. The wire size should
ensure that the maximum allowable lead resistance is not exceeded. Shields on RTD wiring should
be grounded at the controller end only, using the terminals provided.
INDUSTRIAL HEAT TRACING SOLUTIONS
EN- Raychem920series-IM-H56874 05/15
13 / 82
Temperature Sensors Terminal No.
Point A – Shield 25
Point A TS 1 Source (WHT) 26
Point A TS 1 Sense (WHT) 27
Point A TS 1 Common (RED) 28
Point A – Shield 9
Point A TS 2 Source (WHT) 10
Point A TS 2 Sense (WHT) 11
Point A TS 2 Common (RED) 12
Point B – Shield 29
Point B TS 1 Source (WHT) 30
Point B TS 1 Sense (WHT) 31
Point B TS 1 Common (RED) 32
Point B – Shield 13
Point B TS 2 Source (WHT) 14
Point B TS 2 Sense (WHT) 15
Point B TS 2 Common (RED) 16
IMPORTANT: Some RTDs may be constructed with the Sense wire color-coded as Black.
2.7.2 ALARM RELAY CONNECTIONS
The alarm output relay is a programmable dry contact output. It may be programmed for N.O.,
N.C., steady or flashing operation, and is typically used to annunciate an alarm to an external
device such as a DCS, PLC, etc.
IMPORTANT: The alarm relay is intended to be used for switching low-voltage, low-current
signals. Do not use this relay to directly switch line voltages. Ensure that your application stays
within the ratings of the relay contacts as defined in Appendix A on page 61.
The alarm relay may also be used in conjunction with the +9 Vdc source to switch an external,
line-voltage relay to drive a local pilot light, etc. Refer to the wiring diagrams in Appendix C on
page 68 for example connection details.
Alarm and Control Signals Terminal No.
Alarm relay dry contact output 17
Alarm relay dry contact output 18
Ground 19
+9 Vdc nominal Out (100 mAmps maximum) 1
Common 2
Common 3
2.7.3 EXTERNAL INPUT/OUTPUT
These input and output terminals are used to implement the Override and Ambient Temperature
Control Mode features. Refer to Section 3 on page 18 for programming details, and Appendix C on
page 68 for example wiring diagrams.
Miscellaneous SignalsTerminal No.
External input (+) 20
External input (-) 21
External output (+) 4
External output(-) 5
2.7.4 COMMUNICATION SIGNAL CONNECTIONS
The communications terminal assignments change based on the type of option installed. If present
in a control module, the type of communications interface will be identified by a label located next
to the module’s rating label.
INDUSTRIAL HEAT TRACING SOLUTIONS
EN- Raychem920series-IM-H56874 05/15
14 / 82
Communications wiring should use twisted conductor, shielded cable. Shields on communications
wiring should be grounded at one end only, using the terminals provided.
The following tables define the appropriate signal connections for the various types of interfaces:
RS-485 (2-Wire) Connections
Communication Signal Terminal No.
Receive/transmit data (+) 6
Receive/transmit data (-) 22
Shield 8
Shield 24
RS-232 Connections
Communication Signal Terminal No.
Receive data 6
Data carrier detect 7
Clear to send 8
Transmit data 22
Request to send 23
Common 24
Modem Interface Connections
(Note that these particular signals are not polarity sensitive)
Communication Signal Terminal No.
Modem 6
Modem 22
Shield 8
Shield 24
2.7.5 POWER CONNECTIONS
All of the power terminals are numbered for easy identification. Do not attempt to use wire sizes
that exceed the marked terminal ratings and avoid terminating two wires on the same terminal
whenever possible.
Always be sure that all terminals are adequately tightened according to the terminal anufacturer’s
specification. See Appendix A on page 61 for allowable wire sizes, recommended insulation strip
lengths, and tightening torque. A loose terminal can cause arcing and damage to the terminal or
incorrect operation of the controller.
IMPORTANT: Make sure that power terminals are re-tightened several days after installation.
Stranded wire will tend to compress when initially installed; therefore, these terminals should be
checked for tightness several times after the system is installed to ensure that a good con-nection
is maintained. Be certain to use the proper size screwdriver for the terminal blocks to minimize
the chance of damage to the termi-nals.
If the controllers are installed in either a metallic or non-metallic enclosure, follow the enclosure
manufacturer’s recommendations for proper grounding. Do not rely on conduit connections to
provide a suitable ground.
Grounding terminals/screws are provided for connection of system ground leads. Proper system
grounding is required for safe and correct operation of the controller’s protection features.
INDUSTRIAL HEAT TRACING SOLUTIONS
EN- Raychem920series-IM-H56874 05/15
15 / 82
2.7.6 INPUT POWER
The 920 controller may be powered directly from the trace voltage (120 Vac to 277 Vac), through a
step-down transformer, or from a sepa-rate circuit. The same wiring terminal assignments are
used in all configurations, as defined below:
Power Connections Terminal No.
Line/L1 power input 1
Line/L1 Control Power Input 2
Neutral/L2 Power Input 3
Neutral/L2 Control Power Input 4
L3 Power Input (3Ph only) 5
Line/L1 Output to Trace 6
Neutral/L2 Output to Trace 7
L3 Output to Trace (3Ph only) 8
IMPORTANT: that terminals 5 and 8 are only used for implementing 3-phase switching (this is true
for both SSR and contactor configurations).
When powering the controller directly from the incoming trace power (120 Vac to 277 Vac), jumpers
are installed between terminals 1 and 2 and 3 and 4. This is the standard factory configuration.
When the controller is to be powered from another voltage source, the jumpers between terminals
1 and 2 and 3 and 4 should be removed, and the controller power connected to terminals 2 and 4.
In applications where a neutral-based 4-wire 3-phase source is available, the controller may be
powered from one line to neutral connec-tion, while the trace is operated from the line-to-line
connection, eliminating the need for step-down transformers or separate power sources. This can
be accomplished by removing the jumper between terminals 3 and 4 only. Controller power can
then be derived from the L1 trace power on terminals 1 and 2 and the incoming neutral connection
for controller power would be connected to terminal 4.
Wiring diagrams for typical 1- and 2-pole configurations are included in Appendix C on page 68.
IMPORTANT: The contactor version Switch Interface modules provide a switched line voltage
signal to drive the contactor coil. This is derived from the control power and, as such, requires that
the contactor coil voltage be specified to match the control voltage present on terminals 2 and 4.
CAUTION:
Many wiring configurations will use more than one power source and all must be de-energized
prior to performing any maintenance on a controller circuit. When servicing one control point,
remember that power may also be present on the second control point.
2.8 Initial Power-up
CAUTION:
Before applying power to the controller, ensure that powering the circuit will not damage it if power
limiting or the setpoint temperature have not been set correctly. If there is any doubt, the load
should be disconnected until the 920 has been suitably programmed for correct and safe operation.
2.8.1 INITIAL CABLE TEST
To minimize the risk of damage to the controller due to a cable fault, the integrity of the heating
cable should be verified by:
1. Using a megger to perform a high-voltage insulation test
2. Using an ohmmeter to ensure that the heating cable is not shorted
These tests must be performed with the controller output disconnected. Once the cable has been
checked, it may be reconnected to the controller and power applied.
2.8.2 RANDOM START DELAY
All 920 series control modules incorporate a RANDOM START-UP DELAY feature, ensuring that
all units do not power on at the same time. When power is first applied to a controller, it will
hold its output off for a random time (0 to 9 seconds), equal to the last digit of the HTCBUS™
communications address (see section 3.9.2 on page 43). Once the start-up delay has timed out, the
controller will begin normal operation.
INDUSTRIAL HEAT TRACING SOLUTIONS
EN- Raychem920series-IM-H56874 05/15
16 / 82
2.9 Setup for the 920
The 920 may be programmed using the optional 920 Operator Console, or a Group
Communications Controller (GCC) if the modem commu-nications option is installed. For
instructions on the operation of these devices, refer to the corresponding operating manuals.
For complete instructions on programming the 920, see the Section 3 on page 18.
2.9.1 VOLTAGE READING SETUP
The 920 series control module is tested, calibrated, and ordered separately from the switch
interface modules which contain the voltage sensing circuitry. This prevents Pentair Industrial
Heat Tracing Solutions from calibrating the control modules to specific switch interfaces and
removing any component inaccuracies. Generally, the voltage readings will be within 3 Vac to 5 Vac
when shipped from Pentair Thermal Managament. If more accurate voltage readings are desired,
they may be adjusted as part of the initial setup of the controller. This requires measurement of
the trace voltage using a multimeter and adjusting the VOLTAGE TURNS RATIO setting to arrive at
more accurate voltage readings. See section 3.5.21 on page 26.
2.9.2 SWITCH RATING SETUP (SSR ONLY)
The 920 series control module is ordered and shipped as a separate item from the enclosure
assembly. This prevents Pentair Thermal Managament from predetermining the SWITCH
CURRENT RATING settings since various types of output switches are available.
The user should verify that the switch current ratings are set properly for the rating of the solidstate relays that are included as part of the enclosure assembly. Refer to section 3.5.7 on page 22
for more information on the SWITCH CURRENT RATING setting. Pentair Thermal Managament
default setting is defined in Appendix F on page 76.
INDUSTRIAL HEAT TRACING SOLUTIONS
EN- Raychem920series-IM-H56874 05/15
17 / 82
Section 3 – Programming and Configuration
3.1 Introduction
This section provides complete operating and setup instructions for the 920 Series Heat-Tracing
Controller. The text describes each available function in detail, its purpose, valid range settings,
the procedure for use, and some operational tips and suggestions.
While configuring the controller, it is important to remember that the 920 series controller is a
two control point device. Both control points allow completely independent operation and, as such,
have their own individual settings that must be configured. Throughout the text, the first control
point is referred to “Point A” and the second as “Point B.”
“Power On” LED
920 SERIES
Communications status
indicators
PROGRAMMABLE DUAL POINT
HEAT TRACING CONTROLLER
CONSOLE INTERFACE
Operator
console
connection
POWER
Alarm status
indicators
ALARM
A
B
OUTPUT
Output status
indicators
TRANSMIT
RECEIVE
ADDRESS
A - 20910
B - 20911
Communications addresses
for Control Point A and
Control Point B
Fig 3.1 Raychem 920 front panel
3.2 Front Panel Features
Front panel features of the heat trace controller are shown in Figure 3.1. The remainder of this
Section describes the front panel status and display LEDs.
3.2.1 920 FRONT PANEL DISPLAY
The basic 920 series control module front panel includes seven LED indicators. Four of these are
used to indicate the “Output” and “Alarm” status of control points A and B.
Status LEDs
OUTPUT The OUTPUT LED, when illuminated steadily, indicates that the output of the controller
is turned on and is allowing current to flow in the trace circuit. For SSR versions, a flashing LED
indicates that the controller is pulsing its output on and off to maintain the setpoint temperature
and/or control the average amount of current/power the tracer uses. A separate LED is provided
for Point A and Point B.
ALARM The ALARM LEDs will flash (approximately once per second) when the controller has
detected an alarm condition. A separate LED is provided for Point A and Point B.
TRANSMIT The TRANSMIT LED (“Tx”) flashes when the controller is sending information over its
communications port to another device. This LED is only used when an optional communications
interface is installed.
RECEIVE The “RECEIVE” LED (“Rx”) flashes when the controller is receiving information
over its communications port from another device. This LED is only used when an optional
communications interface is installed.
POWER Indicates the module is powered on.
IMPORTANT: Older versions of the controller may not have this LED.
INDUSTRIAL HEAT TRACING SOLUTIONS
EN- Raychem920series-IM-H56874 05/15
18 / 82
3.3 920 Operator Console Display
The optional 920 Operator Console provides a menu-driven, alphanumeric interface to
ease configuration and troubleshooting. The following features are part of the controller’s
programming, but are only used in conjunction with the 920 Operator Console. For a detailed
description of each of the console features and operating instructions, refer to the separate
Raychem 920 Series HTC Operator Console—Installation and Operating Instructions (Pentair
Thermal Managament reference H56903).
3.4 920 Functions
The sections that follow explain the various functions of the 920 controller and how they can be
accessed. The first line of each section identifies the function to be described. Each section goes
on to explain the Purpose of the function, the Range over which it may be set, the Procedure for
setting or enabling the feature, and finally any Notes or Cautions that pertain to the particular
function.
Setting and using the alarming functions of the 920 controller is a two step procedure:
1. The alarm must be enabled or disabled accordingly. When using the 920 Operator Console,
access to all alarming functions is available using the CONFIGURE mode sub-menus. When
using the Model 780/GCC-9000 Group Communications Controller, the alarm masks may be
found in the HTC SETUP Section. Please see the appropriate operating manual for instructions
on accessing these parameters.
2. The corresponding alarm point value may be modified appropriately for the application.
When using the 920 Operator Console, access to the alarm points is also available using the
CONFIGURE mode sub-menus. Modification of the alarm setpoint values is found in the HTC
SETPOINTS Section of the Model 780/GCC-9000 Group Communications Controller. Please see
the appropriate operating manual for in-structions on accessing this feature.
IMPORTANT: The 920 Operator Console or the Model 780/GCC-9000 will not allow modification
of an alarm point value if the alarm has been disabled (DIS) with the exception of the HIGH TS
ALARM temperature settings. These may still be modified if the corresponding HIGH LIMIT
CUTOUT has been enabled (ENA).
3.5 Control Point Setup
This Section describes the setup parameters that relate to a specific control point—either Point A
or Point B. These parameters must be configured for each of the two control points that are used.
3.5.1 CONTROL SETPOINT TEMPERATURE
Purpose: The CONTROL SETPOINT temperature is the value at which the heat trace controller
maintains the circuit temperature through either proportional, proportional ambient SSR,
proportional ambient contactor, or deadband control, depending on the controllers’ configuration.
The CONTROL SETPOINT temperature is compared to the temperature measured by the control
temperature sensor (TS). A decision is then made to turn on or turn off the output to control power
to the tracer.
Range: –76°F to 1058°F (–60°C to 570°C)
Procedure: Adjust the CONTROL SETPOINT temperature value to the desired maintain
temperature. The HTC will switch the output ON and OFF in an attempt to maintain this
temperature.
IMPORTANT:
• See section 5.2 on page 50 of this manual for an explanation of Proportional, Proportional
Ambient SSR, Proportional Ambient Contactor and Deadband Control algorithms.
• When using an optional 920 Operator Console (for V3.11 and up) the CONTROL SETPOINT
temperature range may be limited to the CON-SOLE SETPOINT MAXIMUM and MINIMUM
values (see sections 3.5.29 on page 29 and 3.5.30 on page 29). This is a safety feature to prevent users in the field from modifying the CONTROL SETPOINT temperature setting to a
dangerous level.
INDUSTRIAL HEAT TRACING SOLUTIONS
EN- Raychem920series-IM-H56874 05/15
19 / 82
3.5.2 ALPHANUMERIC TAG ASSIGNMENT
Purpose: A 19-character alphanumeric TAG may be assigned to a control point to allow it to be
easily associated with a pipe, vessel, process, circuit, drawing name or number.
Setting: Any combination of 19 characters from A-Z, 0-9, /, -, ., (,) or #.
Procedure: Using the 920 Operator Console, enter the desired text. Refer to the separate
Raychem 920 Series HTC Operator Console—Installation and Operating Instructions (Pentair
Thermal Managament reference H56903) for TAG entry information.
3.5.3 SWITCH CONTROL MODE
Purpose: This allows selection of the type of algorithm to be used by the HTC to maintain the
CONTROL SETPOINT temperature. There are four different control algorithms available in the HTC—
proportional, proportional ambient SSR, proportional ambient contactor, and deadband. See section
5.2 on page 50 for a complete explanation of these controlling techniques as implemented in the HTC.
Setting: PROPORTIONAL, PROPORTIONAL AMBIENT SSR (V3.11+), PROPORTIONAL AMBIENT
CONTACTOR (V3.11+), or DEADBAND
Procedure: Select the desired control technique. Note that deadband control and proportional
ambient contactor should be selected when using contactors or when precise control and
advanced current handling functions are not required.
IMPORTANT: If deadband is selected, a DEADBAND setting will be available in the HTC
configuration menu, else a PROPORTIONAL BAND setting will be available. No MAXIMUM POWER,
SWITCH CURRENT RATING or CIRCUIT BREAKER CURRENT RATING settings are available when
the controller is set to operate in either contactor mode. If proportional ambient contactor is
selected, the CYCLE TIME setting will also be available.
3.5.4 PROPORTIONAL BAND SETTING
(For use with the three proportional control modes only)
Purpose: When an HTC equipped with SSRs is used to control a heating circuit, proportional or
proportional ambient SSR modes are normally used, allowing for more precise temperature control.
When using contactors, the proportional ambient contactor mode should be selected.
This programmable proportional band acts to vary the on to off time of the output based on the
difference between the measured control temperature and the desired CONTROL SETPOINT
temperature.
Range: 2°F to 90°F (1°C to 50°C)
2°F to 630°F (1°C to 350°C) V3.2x and up
Procedure: Adjust the PROPORTIONAL BAND setting to the desired differential from the
CONTROL SETPOINT temperature.
IMPORTANT:
• See section 5.2 on page 50 for an explanation of how the three proportional modes use the
PROPORTIONAL BAND setting.
• When using series-type, constant wattage, or self-regulating tracers in an ambient
temperature control application, significant energy savings may be realized by setting the
PROPORTIONAL BAND to match the expected range of operating ambient temperatures.
Tracer design is normally done assuming worst-case conditions, where 100% of the design
output power is required to maintain the desired minimum temperature. When the ambient
temperature is above the design minimum but some heat is still required, adjusting the
PROPORTIONAL BAND width accordingly will allow only the amount of power required by the
application to be consumed, while maintaining the minimum required temperature.
Example: A water line must be protected from freezing when the ambient temperature falls below
10°C. Either the proportional ambient SSR or proportional ambient contactor mode is selected
as the control method (depending on the type of switch being used). The heater and insulation
are chosen to impart enough heat to the line to keep it from freezing at a worst-case ambient
temperature of –40°C. At 10°C, the heater should be completely off, since no heat is required at
this temperature to guarantee that the product will not freeze. It follows that the amount of heat
required by the water line decreases as the ambient temperature increases from –40°C to 10°C
(theoretically, at –15°C the heater output should be approximately 50%). Setting the CONTROL
SETPOINT temperature to 10°C, and the PROPORTIONAL BAND to 50°C, will force the controller’s
output to be 100% on at –40°C, 50% on at –15°C, and off at 10°C.
INDUSTRIAL HEAT TRACING SOLUTIONS
EN- Raychem920series-IM-H56874 05/15
20 / 82
3.5.5 DEADBAND SETTING
(Deadband control mode only or if a point controls an INHIBIT output signal)
Purpose: When an HTC equipped with a contactor is used to control a trace circuit, it is necessary
to use deadband rather than proportional control. This is done to prevent the contactor from
switching on and off rapidly and being worn out prematurely. This deadband acts as an on/
off control where the decision to turn the output off or on is based upon a window of difference
between the measured control temperature and the desired CONTROL SETPOINT temperature.
Range: 2°F to 90°F (1°C to 50°C)
Procedure: Adjust the DEADBAND setting to the desired differential from the desired CONTROL
SETPOINT temperature. When the control tem-perature is above the setpoint + deadband value,
the controller will turn off the output to the tracer. If the control temperature drops down below
the setpoint, the output will be turned back on. Note that the smaller the DEADBAND setting, the
more often the contactor will cycle on and off, decreasing its operational life.
IMPORTANT:
• See section 5.2 on page 50 for an explanation of deadband control. Note that the MAXIMUM
POWER, SWITCH CURRENT RATING, and CIR-CUIT BREAKER CURRENT RATING settings are
not available when the HTC is set to deadband mode (typically when switching a contactor).
• The DEADBAND parameter is also available for Point A when the EXTERNAL OUTPUT is
configured for use as an INHIBIT output. See section 3.6.4 on page 30 for additional details.
3.5.6 CYCLE TIME SETTING (V3.11 AND UP)
(For proportional ambient contactor control mode only)
Purpose: This parameter determines the minimum amount of time it will take for a complete
contactor ON-OFF-ON cycle.
Range: 10 to 255 minutes
Procedure: Adjust the CYCLE TIME setting to yield the desired contactor ON+OFF time for a
particular duty cycle. For instance, if the contactor should remain on for five minutes with a 50%
duty cycle, then the CYCLE TIME should be 10 minutes. A new duty cycle (based on measured
control temperature, PROPORTIONAL BAND and CONTROL SETPOINT) is calculated every time
the contactor is required to change state.
IMPORTANT:
• If the calculated duty cycle is 0% or 100%, then the contactor will not change state and the duty
cycle will not be calculated again for a time period = CYCLE TIME/30.
• The minimum cycle time setting is 10 minutes, and the minimum controller output duty cycle is
3%. This results in a minimum contactor ON time of 18 seconds.
3.5.7 SWITCH CURRENT RATING SETTING (SSR ONLY)
Purpose: The SWITCH CURRENT RATING setting defines the current rating of the output switch.
It is used by the controller to limit the maximum average current that will be allowed to flow
to the load before it begins to adjust the output duty cycle, limiting the amount of current to an
acceptable level.
Range: 0.3 to 100.0 amps
(CURRENT TURNS RATIO = 1.00)
Procedure: Adjust the SWITCH CURRENT RATING setting to match the current rating of the
output device (i.e. 30.0 amps). Note that the SWITCH CURRENT RATING setting is affected by
the CURRENT TURNS RATIO setting. The absolute maximum adjusted SWITCH CURRENT RATING
setting is 300.0 amps. The absolute minimum adjusted SWITCH CURRENT RATING setting is 0.1
amps. See section 3.5.22 on page 26 for more information regarding the CURRENT TURNS RATIO
function.
3.5.8 CIRCUIT BREAKER CURRENT RATING SETTING (SSR ONLY)
Purpose: The CIRCUIT BREAKER CURRENT RATING setting helps prevent in-rush induced
nuisance tripping of the circuit breaker immediately upstream of the controller. The HTC evaluates
the square of the current related to time (I2T) and adjusts the output duty cycle accordingly,
limiting the amount of current to an acceptable level.
INDUSTRIAL HEAT TRACING SOLUTIONS
EN- Raychem920series-IM-H56874 05/15
21 / 82
Range:0.3 to 100.0 amps
(CURRENT TURNS RATIO = 1.00)
Procedure: Adjust the CIRCUIT BREAKER CURRENT RATING setting to the heating circuit breaker
size (i.e. 30.0 amps). Note that the CIRCUIT BREAKER CURRENT RATING setting is affected by the
CURRENT TURNS RATIO setting. The absolute maximum adjusted CIRCUIT BREAKER CURRENT
RATING setting is 300.0 amps. The absolute minimum adjusted CIRCUIT BREAKER CURRENT
RATING setting is 0.1 amps. See section 3.5.22 on page 26 for more information regarding the
CURRENT TURNS RATIO function.
IMPORTANT: This feature should not be used to reduce the size of a circuit breaker or increase
the maximum heating cable length. It can be quite effective in preventing nuisance trips due to
incorrect design or factors outside those considered by the design.
3.5.9 MAXIMUM POWER SETTING (SSR ONLY)
Purpose: This user-selectable level limits the maximum amount of power applied to a heat
trace circuit. This is an average power calculated by the controller using the average current
and applied voltage. The HTC switches the output on and off rapidly to limit the average current
to an appropriate level. The MAXIMUM POWER level may be adjusted to eliminate step-down
transformers, lower the effective output wattage of a cable, or implement energy management of
the heat trace circuit.
Range:3 to 33,000 Watts
(VOLTAGE and CURRENT TURNS RATIOS = 1.00)
Procedure: Adjust the MAXIMUM POWER level to the desired value (watts). Use the TEST TRACING
function to observe the power limiting oper-ation.
IMPORTANT:
• This function may be set within reasonable limits for the particular tracer being powered. The
effective resolution of the setting is limited to 1/30th of the calculated full on power.
• Do not set the MAXIMUM POWER below full output for applications that do not require control
of power.
• This feature is affected by the VOLTAGE and CURRENT TURNS RATIO settings. The maximum
range using adjusted values of voltage and current is 65,535 watts. See sections 3.5.21 on page
26 and 3.5.22 on page 26 for more information regarding the turns ratio functions.
3.5.10 3-PHASE POWER CALCULATION (V3.11 AND UP)
Purpose: This parameter selects the type of power calculation that the HTC is to perform.
Setting: NO or YES
Procedure: If an automatic 3-phase power calculation is desired, select YES. If a normal power
calculation is desired, select NO.
IMPORTANT: For the total 3-phase power calculation to be accurate the following conditions must
be met:
• All three phases must be balanced and star (“Y”) connected
• The measured corrected current is one of the phase currents
• The measured corrected voltage is the line to line voltage
The formula used to calculate this total power is: Ptotal = √3 x Iphase x Vline-line
3.5.11 TS FAIL MODE (V3.11 AND UP)
Purpose: This parameter determines whether the HTC turns the output switch ON or OFF if all
selected temperature sensors fail to provide a control temperature.
Setting: OFF or ON
Procedure: If the HTC should turn the output switch off when it cannot read a valid control
temperature, then select OFF; otherwise, if the output switch should turn on, then select ON.
IMPORTANT: This parameter is part of the TS CONTROL MODE.
INDUSTRIAL HEAT TRACING SOLUTIONS
EN- Raychem920series-IM-H56874 05/15
22 / 82
3.5.12 TEMPERATURE SENSOR CONTROL MODE
Purpose: The TS CONTROL MODE allows the selection of one of eleven possible temperature
control modes for the controller. The different modes allow redundant fail-safe temperature
sensing, averaging, or minimum maintain temperature control.
Setting: Select one of the following eleven possible modes:
Control TS and Description
CONTROL USING TS 1, FAIL OFF/ON
CONTROL USING TS 1, FAIL TO TS 2
CONTROL USING TS 2, FAIL OFF/ON
CONTROL USING TS 2, FAIL TO TS 1
CONTROL ON AVERAGE, FAIL OFF/ON
CONTROL ON AVERAGE, FAIL TO GOOD
CONTROL ON LOWEST, FAIL OFF/ON
CONTROL ON LOWEST, FAIL TO GOOD
The following are only available in V3.11+:
CONTROL USING EXT. INPUT, FAIL OFF/ON
CONTROL USING EXT. INPUT, FAIL TO TS 1
CONTROL USING EXT. INPUT, FAIL TO TS 2
Where OFF/ON = Controller’s output switch turned OFF or ON as determined by the TS FAIL MODE.
Example: With a TS CONTROL MODE of CONTROL ON AVERAGE, FAIL TO GOOD, the controller
will measure both sensors (TS 1 and TS 2), averaging the two temperature value;, display the
results; and cycle the heater ON or OFF to maintain the CONTROL SETPOINT temperature. This
is the primary control mode. If either sensor should fail, the controller will transfer control to the
remaining “good” sensor and generate the appropriate TS 1 or TS 2 FAILURE ALARM (assuming
that the alarm is enabled). The temperature will now be maintained based on this measured value.
If the remaining good sensor fails, the controller will turn the heater OFF or ON as determined
by the TS FAIL MODE setting. The appropriate TS 1 or TS 2 FAILURE ALARM will be also be
generated.
Procedure: Select the control mode that best suits the application.
IMPORTANT:
• Ensure that TS FAILURE ALARMS are enabled. See sections 3.7.1 on page 32, 3.7.4 on page 32,
and 3.7.10 on page 34 for a complete explanation of RTD failure detection in the HTC.
• If the selected TS CONTROL MODE uses the EXTERNAL INPUT then the EXTERNAL INPUT
must be set to TEMPBUS™ (see Section 3.6.3). Also, the CONTROL TS FAILURE ALARM is nonlatching in this mode.
• Fail safe mode is always disabled if the TS CONTROL MODE = EXT. INPUT, FAIL OFF/ON.
3.5.13 TS 1 TYPE (V3.11 AND UP)
Purpose: This parameter specifies the type of RTD that is connected to the HTC’s TS 1 input.
Setting: 3-wire 100 Ω platinum or 2-(or 3-) wire 100 Ω nickel-iron (Ni-Fe)
Procedure: Select the type of RTD that is connected to the TS 1 input.
IMPORTANT: If a 2-wire 100 Ω nickel-iron (Ni-Fe) RTD is selected then the TS 1 LEAD RESISTANCE
must be entered manually (see section 3.5.14 on page 24).
3.5.14 TS 1 LEAD RESISTANCE (V3.11 AND UP)
(For Ni-Fe RTDs only)
Purpose: This parameter specifies the lead resistance of a 2-wire nickel-iron RTD connected to
the HTC’s TS 1 input.
Range: 0 to 20.00 Ω
Procedure: Measure the resistance of one of the nickel-iron RTD leads (from the RTD to the HTC’s
TS 1 input) and use this value as the TS 1 LEAD RESISTANCE.
INDUSTRIAL HEAT TRACING SOLUTIONS
EN- Raychem920series-IM-H56874 05/15
23 / 82
3.5.15 TS 1 HIGH LIMIT CUTOUT
Purpose: When enabled, the TS 1 HIGH LIMIT CUTOUT feature will override the CONTROL
SETPOINT temperature and force the controller output off if the TS 1 reading exceeds the HIGH
TS 1 ALARM temperature setting. This is a non-latching condition, so once the TS 1 reading drops
below the HIGH TS 1 ALARM temperature setting, the controller will resume normal operation.
Setting: ENABLE or DISABLE
Procedure: Enable or disable the cutout feature as desired.
IMPORTANT:
• The TS 1 HIGH LIMIT CUTOUT feature overrides an autocycle test. A pending autocycle will
be initiated immediately after the TS 1 tempera-ture drops below the HIGH TS 1 ALARM
temperature setting.
• If a TS 1 failure occurs and the TS 1 HIGH LIMIT CUTOUT feature is enabled, the switch output
will latch off regardless of the TS CONTROL MODE setting or the TS FAIL MODE setting.
• If the TS 1 HIGH LIMIT CUTOUT feature is enabled, then the HIGH TS 1 ALARM temperature
setting can be set, regardless of whether the HIGH TS 1 ALARM is enabled.
3.5.16 TS 2 TYPE (V3.11 AND UP)
Purpose: This parameter specifies the type of RTD that is connected to the HTC’s TS 2 input.
Setting: 3-wire 100 Ω platinum or 2- (or 3-) wire 100 Ω nickel-iron (Ni-Fe)
Procedure: Select the type of RTD that is connected to the TS 2 input.
IMPORTANT: If a 2-wire 100 Ω nickel-iron (Ni-Fe) RTD is selected then the TS 2 LEAD RESISTANCE
must be entered (see section 3.5.17 on page 25).
3.5.17 TS 2 LEAD RESISTANCE (V3.11 AND UP)
(For Ni-Fe RTDs only)
Purpose: This parameter specifies the lead resistance of a 2-wire nickel-iron RTD connected to
the HTC’s TS 2 input.
Range: 0 to 20.00 Ω
Procedure: Measure the resistance of one of the nickel-iron RTD leads (from the RTD to the HTC’s
TS 2 input) and use this value as the TS 2 LEAD RESISTANCE.
3.5.18 TS 2 HIGH LIMIT CUTOUT
Purpose: When enabled, the TS 2 HIGH LIMIT CUTOUT feature will override the CONTROL
SETPOINT temperature and force the controller output off if the TS 2 reading exceeds the HIGH
TS 2 ALARM temperature setting. This is a non-latching condition, so once the TS 2 reading drops
below the HIGH TS 2 ALARM temperature setting, the controller will resume normal operation.
Setting: ENABLE or DISABLE
Procedure: Enable or disable the cutout feature as desired.
IMPORTANT:
• The TS 2 HIGH LIMIT CUTOUT feature overrides an autocycle test. A pending autocycle will
be initiated immediately after the TS 2 tempera-ture drops below the HIGH TS 2 ALARM
temperature setting.
• If a TS 2 failure occurs and the TS 2 HIGH LIMIT CUTOUT feature is enabled, the switch output
will latch off regardless of the TS CONTROL MODE setting or the TS FAIL MODE setting.
• If the TS 2 HIGH LIMIT CUTOUT feature is enabled, then the HIGH TS 2 ALARM temperature
setting can be set, regardless of whether the HIGH TS 2 ALARM is enabled.
3.5.19 VOLTAGE SOURCE (V3.11 AND UP)
Purpose: This parameter specifies which voltage source the HTC should use for its voltage
measurements.
Setting: POINT A or POINT B or FIXED
Procedure: If the HTC is not powered from a dedicated switch interface an alternate voltage source
can be selected. If a fixed constant voltage value is to be used then that FIXED VOLTAGE SETTING
must also be entered (see section 3.5.20 on page 26).
INDUSTRIAL HEAT TRACING SOLUTIONS
EN- Raychem920series-IM-H56874 05/15
24 / 82
IMPORTANT:
• If an alternate voltage source is selected, then all voltage alarming features are disabled for
this HTC and the VOLTAGE TURNS RATIO is not used.
• It is not possible to set both points to use the others’ voltage source.
3.5.20 FIXED VOLTAGE SETTING (V3.11 AND UP)
(Only if VOLTAGE SOURCE = FIXED)
Purpose: This parameter specifies the voltage value that the HTC should use when the VOLTAGE
SOURCE = FIXED.
Range: 0 to 1000 Volts
Procedure: Adjust the FIXED VOLTAGE setting to the desired level.
IMPORTANT: All voltage alarming features are disabled for this HTC and the VOLTAGE TURNS
RATIO is not used when the VOLTAGE SOURCE is set to FIXED.
3.5.21 VOLTAGE TURNS RATIO ADJUSTMENT
Purpose: The VOLTAGE TURNS RATIO adjusts voltage readings for applications where a controller
is switching a load through a step-up or step-down transformer, or is being powered from a source
with a different voltage level than the trace voltage.
Range: 0.10 to 9.90 (TO 1)
Procedure: Adjust the VOLTAGE TURNS RATIO to equal the ratio of the circuit voltage to the
controller input voltage. Compare the indicated voltage to the measured voltage after setting the
turns ratio and adjust until the two readings are as close as possible.
e.g.: Heating Circuit Voltage:
480 Volts
Module Input Voltage:
120 Volts
VOLTAGE TURNS RATIO Setting:
4.00
IMPORTANT:
• When the VOLTAGE TURNS RATIO has been set appropriately, the HTC will calculate the circuit
power using the adjusted current and voltage readings. Voltage alarms also use the adjusted
circuit voltages.
• The VOLTAGE TURNS RATIO is not used if the selected VOLTAGE SOURCE is not from the
dedicated switch interface.
3.5.22 CURRENT TURNS RATIO ADJUSTMENT
Purpose: The CURRENT TURNS RATIO adjusts current readings for applications where a
controller is monitoring a load through an external step-up or step-down current transformer.
Range: 0.10 to 60.00 (TO 1)
Procedure: Adjust the CURRENT TURNS RATIO to equal the ratio of the primary to secondary
windings of the external current transformer. Compare the indicated current to the measured
current after setting of the CURRENT TURNS RATIO and adjust until the two readings are as close
as possible.
IMPORTANT: When the CURRENT TURNS RATIO has been set appropriately, the HTC will calculate
the circuit power using the adjusted current and voltage readings. Current alarms, as well as the
switch and circuit breaker limiting functions, also use the adjusted circuit currents.
3.5.23 AUTOCYCLE ENABLING
Purpose: The autocycle function momentarily (approximately 10 seconds) applies power to the
heating circuit at the selected interval. It is used to test the integrity of the heating circuit. Alarms
present at the time of autocycle then become latched and remain active after the completion of
the autocycle function. Auto-cycling effectively eliminates the need for preventive maintenance by
automatically verifying the heating circuit integrity.
Setting: ENABLE or DISABLE
Procedure: Enable or disable the auto-cycling feature as desired. If the feature is disabled, you will
not be prompted to enter the AUTOCYCLE INTERVAL or AUTOCYCLE UNITS.
INDUSTRIAL HEAT TRACING SOLUTIONS
EN- Raychem920series-IM-H56874 05/15
25 / 82
IMPORTANT:
• Auto-cycling should always be enabled for normal operation. Disabling this feature should only
be required where the HTC system is monitoring a circuit exercised by some other device or
means. Although this function defeats temperature control and forces output on, the controller
will continue to adjust the output for protection purposes or power limiting (SSR option only).
• Auto-cycling is inhibited if the controller is in the load shedding mode. See section 5.3
on page 52.
• If auto-cycling is enabled, the HTC will always autocycle for 10 seconds when power is initially
applied.
• If auto-cycling is enabled, TS FAIL MODE = OFF and all the control temperature sensors have
failed, the HTC will still perform an autocycle.
• If an alarm condition, with an alarm filter time greater than 0, appears during the auto-cycling,
then the autocycle may be extended (past the 10 seconds) until the alarm filter time has
expired.
3.5.24 AUTOCYCLE TIME INTERVAL
Purpose: AUTOCYCLE INTERVAL is the number of hours/minutes between successive heating
circuit integrity tests depending on the AUTOCYCLE UNITS specified.
Range: 1 to 240
Procedure: Set the AUTOCYCLE INTERVAL to the desired time period.
IMPORTANT:
• When using proportional ambient contactor mode, the CYCLE TIME setting should be less than
the AUTOCYCLE INTERVAL otherwise au-to-cycling could affect the duty cycle.
• If an AC ALARM becomes active during an autocycle, but the AUTOCYCLE INTERVAL expires
prior to the corresponding ALARM FILTER time, then auto-cycling will continue until the
ALARM FILTER time has elapsed.
• For the earliest possible alarming of heating circuit problems the AUTOCYCLE INTERVAL
should be set to a small value.
3.5.25 AUTOCYCLE TIME UNITS
Purpose: The autocycle time units parameter allows selection of minutes or hours for the
AUTOCYCLE INTERVAL setting.
Setting: HOURS or MINUTES
Procedure: Set the AUTOCYCLE UNITS to the desired time units.
3.5.26 INHIBIT CONTROL (V3.00 ONLY)
Purpose: This feature allows the HTC’s EXTERNAL INPUT to override the controller’s temperature
control and force the output switch off. This is especially useful when the user wishes to turn a
controller or a group of controllers off over the summer months, during maintenance, or when a
line is flowing and does not require heating.
Setting: ENABLE or DISABLE
Procedure: Enable or disable the INHIBIT CONTROL for the control point being programmed.
IMPORTANT:
• The EXTERNAL INPUT must also be programmed as INHIBIT before this parameter can be set.
See section 3.6.3 on page 29 for further details.
• If the autocycle feature is enabled, it will continue to function even when the INHIBIT mode is
active.
• Fail-safe mode is inactive if the INHIBIT mode is active.
• Both of the LOW TS ALARMS are inactive if the INHIBIT mode is active.
3.5.27 OVERRIDE SOURCE (V3.11 AND UP)
Purpose: An override signal can be sent to the HTC from one of two sources. This override signal
can be used to override the controller’s temperature control and force the output switch off or on.
This is especially useful when the user wishes to turn a controller or a group of controllers off over
the summer months, during maintenance, or when a line is flowing and does not require heating.
INDUSTRIAL HEAT TRACING SOLUTIONS
EN- Raychem920series-IM-H56874 05/15
26 / 82
Setting: REMOTE or EXT. INPUT
Procedure: If the override signal will be generated remotely and received by the HTC via the
optional communications interface, select REMOTE as the OVERRIDE SOURCE. If the override
signal will be received by the HTC via the external input terminals on the 920 terminal board,
select EXTERNAL INPUT as the OVERRIDE SOURCE.
IMPORTANT:
• If the EXTERNAL INPUT is not configured as either INHIBIT or FORCE ON then OVERRIDE
SOURCE will always automatically be set to REMOTE. See section 3.6.3 on page 29 for further
details.
• If the autocycle feature is enabled, it will continue to function even when an INHIBIT override
signal is being received as long as load shedding is not active.
• Fail-safe mode is inactive if an INHIBIT override signal is being received.
• Load shedding and fail-safe mode are inactive if a FORCE ON override signal is being received.
• Only the LOW TS ALARMS for temperature sensors used by the TS CONTROL MODE are inactive
if an INHIBIT override signal is being re-ceived.
3.5.28 LOAD SHEDDING ENABLING
Purpose: The load shedding function allows the controller output to be forced OFF by way of a
remote contact input on the 780 Group Com-munications Controller or using the communications
port and an upstream device. It may be used to turn OFF the output of one or more con-trollers
in order to reduce energy consumption to avoid peak demand surcharges, remove power from
unused circuits, or remove power from circuits that may be subjected to steam cleaning.
Setting: ENABLE or DISABLE
Procedure: Enable or disable the load shedding control mode as desired.
IMPORTANT:
• To completely configure the HTC for load shedding operation, the following additional
parameters must be set up if using the Model 780/GCC-9000:
– Fail-safe mode
– Load shedding GCC contact association
• These additional parameters may only be accessed using the Group Communications
Controller. See the appropriate section of the GCC manual for further details.
• Fail-safe mode is not supported when using proportional ambient SSR mode or proportional
ambient contactor mode.
• Fail-safe mode is not supported if the TS CONTROL MODE = EXT. INPUT, FAIL OFF/ON.
• For fail-safe mode to function, at least one LOW TS ALARM of the controlling temperature
sensor(s) must be enabled and the corresponding LOW TS ALARM temperature setting must be
less than the CONTROL SETPOINT temperature.
3.5.29 CONSOLE SETPOINT MAXIMUM (V3.11 AND UP)
IMPORTANT: The CONSOLE SETPOINT MAXIMUM is not displayed on the optional 920 Operator
Console.
Purpose: When using an optional 920 Operator Console (for V3.11 and up) the maximum setting of
the CONTROL SETPOINT temperature may be limited to the CONSOLE SETPOINT MAXIMUM value.
This is a safety feature to prevent users in the field from modifying the CONTROL SET-POINT
temperature setting to a dangerous level.
Range: –76°F to 1058°F (–60°C to 570°C)
Procedure: Adjust the CONSOLE SETPOINT MAXIMUM temperature value to limit the maximum
allowable CONTROL SETPOINT TEMPERATURE that may be set using the optional 920 Operator
Console. The CONSOLE SETPOINT MAXIMUM may only be set using a communicating device such
as the Model 780/GCC-9000. See the 780/GCC-9000 manual for the proper procedure.
3.5.30 CONSOLE SETPOINT MINIMUM (V3.11 AND UP)
IMPORTANT: The CONSOLE SETPOINT MINIMUM is not displayed on the optional 920 Operator
Console.
Purpose: When using an optional 920 Operator Console (for V3.11 and up) the minimum setting of
the CONTROL SETPOINT temperature may be limited to the CONSOLE SETPOINT MINIMUM value.
INDUSTRIAL HEAT TRACING SOLUTIONS
EN- Raychem920series-IM-H56874 05/15
27 / 82
This is a safety feature to prevent users in the field from modifying the CONTROL SET-POINT
temperature setting to a dangerous level.
Range: –76°F to 1058°F (–60°C to 570°C)
Procedure: Adjust the CONSOLE SETPOINT MINIMUM temperature value to limit the minimum
allowable CONTROL SETPOINT TEMPERATURE that may be set using the optional 920 Operator
Console. The CONSOLE SETPOINT MINIMUM may only be set using a communicating device such
as the Model 780/GCC-9000. See the 780/GCC-9000 manual for the proper procedure.
3.6 Common Controller Setup
The following section describes the setup parameters that are common for both of the two control
points—Point A and Point B. These pa-rameters need only be configured once to define their
operation for both control points.
3.6.1 TEMPERATURE DISPLAY UNITS
Purpose: This allows selection of the type of temperature units to display when using the 920
Operator Console. All temperature-related values will be displayed in the selected units.
IMPORTANT: This setting will not affect the temperature units displayed at a 780/GCC-9000 Group
Communications Controller. The GCC may be set independently.
Setting: DEGREES C or DEGREES F
Procedure: Adjust the setting to the desired temperature units (°F or °C).
IMPORTANT: To minimize possible confusion, temperature units should be set the same on the
HTC and any other communicating devices.
3.6.2 VERSION OF FIRMWARE AND HARDWARE
Purpose: The first three digits of the version number indicate the revision level of the firmware
programmed into the controller. As new fea-tures are added to the HTC, the firmware revision
level is incremented to allow the user to determine which features are available for the particular
unit being used. The fourth digit (V3.11 and up only) indicates the type of 920 hardware. A “0”
indicates that an EPROM is being used, which means the firmware cannot be upgraded without
replacing the EPROM. A “1” indicates that the firmware is stored in a FLASH memory device and
can be upgraded via the optional communications interface.
3.6.3 EXTERNAL INPUT PORT
Purpose: This input port may be used as an OVERRIDE SOURCE or a TEMPBUS™ temperature
source for either point. As an OVERRIDE SOURCE, it can sense a remote dry contact closure
and override the controller’s temperature control and force its output switch off or on. As a
TEMPBUS™ temperature source, either controller can control its output switch using the
TEMPBUS™ temperature rather than temperatures from TS 1 or TS 2.
Setting: NOT USED, TEMPBUS (V3.11+), INHIBIT or FORCE ON (V3.11+)
Procedure: If the EXTERNAL INPUT is not being used by either point, select NOT USED. If
either point requires a TEMPBUS™ temperature signal, select TEMPBUS™ and set the point
TS CONTROL MODE to a mode using the EXTERNAL INPUT (see section 3.5.12 on page 24). For
TEMPBUS™ operation description see section 5.4 on page 53.
If a remote dry contact closure should force either point’s output switch off, select INHIBIT. If a
remote dry contact closure should force either point’s output switch on, select FORCE ON.
If the EXTERNAL INPUT is set to INHIBIT or FORCE ON, the point’s OVERRIDE SOURCE (for V3.11+)
must be set to EXT. INPUT or its INHIBIT CONTROL (for V3.00) must be enabled.
IMPORTANT:
• When used with the INHIBIT/FORCE ON feature, a contact closure sensed by the EXTERNAL
INPUT will initiate the INHIBIT/FORCE ON mode. An open input will cause the controller to
revert to normal temperature control operation. One possible use of the INHIBIT feature is to
use an external device (such as a flow meter) to provide a contact closure if there is flow in a
line. As long as the line has adequate flow, the heating will be off (INHIBITed from operating).
See Appendix C on page 68 for typical connection diagrams when using this input.
• EXTERNAL INPUT must be set to INHIBIT or FORCE ON before OVERRIDE SOURCE (for V3.11+)
can be set to EXT. INPUT; or INHIBIT CONTROL (for V3.00) can be edited. For V3.11 and up,
INDUSTRIAL HEAT TRACING SOLUTIONS
EN- Raychem920series-IM-H56874 05/15
28 / 82
setting EXTERNAL INPUT to NOT USED or TEMPBUS™ will automatically set OVERRIDE
SOURCE to REMOTE.
3.6.4 EXTERNAL OUTPUT PORT
Purpose: The EXTERNAL OUTPUT port can be programmed to allow Point A to function as a
“master” 920 HTC to control up to 25 “slave” 920 HTC units. A “master” can either force its
“slaves” to override their temperature control and force their output switch off (INHIBIT), or it can
send its control temperature to its “slaves” so they can do their own temperature control using
this temperature (TEMPBUS™).
An INHIBIT “master” may be useful when a number of “slave” controllers use their own RTDs,
but are to be turned off based on the ambient temperature. This will allow disabling of the “slave”
controllers during the summer months, during a maintenance shutdown, etc.
A TEMPBUS™ “master” may be useful when a number of “slave” controllers do not have their own
temperature sensors and are set to control the ambient temperature.
Setting: NOT USED, TEMPBUS (V3.11+) or INHIBIT
Procedure: Select NOT USED if Point A is not a “master” controlling the EXTERNAL OUTPUT port.
Select INHIBIT if Point A will be controlling the EXTERNAL OUTPUT port as an INHIBIT “master.”
Select TEMPBUS™ if Point A will be sending its control temperature out the EXTERNAL OUTPUT
port. For TEMPBUS™ operation description see section 5.4 on page 53.
IMPORTANT:
• The “master” and “slave” controllers must be installed in the same enclosure. The EXTERNAL
OUTPUT PORT signal is not intended to be connected over extended distances or between
enclosures.
• If EXTERNAL OUTPUT is set to INHIBIT, then the DEADBAND parameter for Point A will
be used to define the operation of the EXTERNAL OUT-PUT port, even though the SWITCH
CONTROL MODE for Point A may not be set for DEADBAND operation. See section 3.5.5 on
page 22 for additional details regarding the DEADBAND mode.
• If the EXTERNAL INPUT PORT input is not being used, Point B may be configured as a “slave”
for a controller with its Point A configured as a “master.”
3.6.5 FLASH ALARM OUTPUT SETTING
Purpose: Programs the alarm output relay for flashing or steady output in case of an alarm
condition.
Setting: YES (Flash) or NO (Steady)
Procedure: Set the alarm output relay to flash or not to flash on an alarm condition, whichever
suits the application.
IMPORTANT:
• If the alarm output is used to drive a pilot light, select YES to enable flashing operation. When
the output is also configured for normally closed operation, the pilot light will be on steady for
normal operation, flash in case of alarm and be extinguished due to a bulb failure or loss of
power.
• If multiple alarm outputs from different controllers are wired in series (i.e.: multipoint panels),
set this parameter to NO (steady).
3.6.6 ALARM OUTPUT NORMAL STATE
Purpose: Configures the alarm output relay for normally open or normally closed operation. The
normal condition is assumed to be when the HTC is powered and no alarms exist.
Setting: N.O. (Normally Open) or N.C. (Normally Closed)
Procedure: Set the alarm output relay to normally open or normally closed to suit the application.
IMPORTANT: If a pilot light is used for indication of alarms, normally closed operation provides a
steady illumination of the lamp when the circuit is operating correctly. A light that is flashing or
out indicates a fault condition. A burned out lamp is readily identified if the HTC is set to flash the
alarm output relay in case of alarm. See the section 3.6.5 on page 31.
3.6.7 LANGUAGE
Purpose: Defines which language the optional 920 Operator Console uses when prompting the
INDUSTRIAL HEAT TRACING SOLUTIONS
EN- Raychem920series-IM-H56874 05/15
29 / 82
user for input and/or displaying messages and status.
Setting: ENGLISH or FRANCAIS
Procedure: Select the language of choice—ENGLISH for English prompts and messages, or
FRANCAIS for French prompts and messages.
3.6.8 POINT B USED
Purpose: Allows the second control point (Point B) to be disabled when it is not being used. This is
an easy method of disabling all ALARMS, etc. without having to set each parameter.
Setting: YES or NO
Procedure: Select NO to disable Point B, choose YES to use Point B.
IMPORTANT:
• Selecting NO has the following effect on Point B parameters:
– All relevant ALARMS are masked
– The control output is held off
– No programming, configuration, or messages are available using the optional
920 Operator Console
• Complete Point B access remains available using the optional communications interface.
3.6.9 PASSCODE
See section 3.10.1 on page 45.
3.6.10 SCROLL DELAY SETTING (V3.11 AND UP)
Purpose: For ease of viewing, allows the user to modify the speed at which information is scrolled
on the optional Operator Console.
Range: 0.07 to 0.25 seconds
Procedure: Decreasing the scroll delay value will cause the information on the display to scroll
faster. Increasing the scroll delay value will cause the information on the display to scroll slower.
3.7 Temperature Alarms
This section defines the temperature-related alarming functions of the 920 controller. These
parameters must be set up individually for both Point A and Point B.
3.7.1 TEMPERATURE SENSOR 1 FAILURE ALARM
Purpose: Enabling TS 1 FAILURE will provide indication of an open or shorted failure of TS 1.
Alarm Mask: ENABLE or DISABLE
Procedure: Enable or disable alarming of a failed first temperature sensor (TS 1) as required.
IMPORTANT:
• This failure alarm should be enabled if a temperature sensor is connected to the TS 1 input.
• This alarm is always latched and must be reset by the user.
3.7.2 LOW TEMPERATURE SENSOR 1 ALARM
Purpose: If enabled, the LOW TS 1 ALARM allows for alarming of low temperature conditions as
sensed by the first temperature sensor (TS 1).
Alarm Mask: ENABLE or DISABLE
Range: –76°F to 1058°F (–60°C to 570°C)
Procedure: Adjust the LOW TS 1 ALARM temperature setpoint to the desired value. Note that the
LOW TS 1 ALARM must be enabled in order to adjust the LOW TS 1 ALARM temperature setpoint.
IMPORTANT:
• This alarm should normally be enabled and the setpoint should be appropriate for the heating
application. Maintaining a minimum 5°C differential between low temperature alarming and
the CONTROL SETPOINT temperature will minimize nuisance alarming due to momen-tary
dips in temperature. Another alternative to this is to configure the controller for non-latching
temperature alarms.
INDUSTRIAL HEAT TRACING SOLUTIONS
EN- Raychem920series-IM-H56874 05/15
30 / 82
• This alarm must be enabled and its setpoint must be below the CONTROL SETPOINT
temperature if fail-safe mode uses the temperature from TS 1.
3.7.3 HIGH TEMPERATURE SENSOR 1 ALARM
Purpose: If enabled, the HIGH TS 1 ALARM allows for alarming of high temperature conditions as
sensed by the first temperature sensor (TS 1).
Alarm Mask: ENABLE or DISABLE
Range: –76°F to 1058°F (–60°C to 570°CF)
Procedure: Adjust the HIGH TS 1 ALARM temperature setpoint to the desired value. Note that the
HIGH TS 1 ALARM must be enabled in order to adjust the HIGH TS 1 ALARM temperature setpoint
unless the TS 1 HIGH LIMIT CUTOUT feature is enabled.
IMPORTANT: This alarm should only be used for applications involving a product that is sensitive
to over temperature. General use may result in nuisance alarms due to the outflow of hot product
or steam. This may be a case where the alarm should be enabled and nonlatching temperature
alarming used. A high temperature condition resulting from a forced on failure of the heating
circuit should first be alarmed by the SWITCH FAILURE ALARM. See section 3.8.18 on page 40 for
more information.
3.7.4 TEMPERATURE SENSOR 2 FAILURE ALARM
Purpose: Enabling TS 2 FAILURE provides indication of an open or shorted failure of TS 2.
Alarm Mask: ENABLE or DISABLE
Procedure: Enable or disable alarming of a failed second temperature sensor (TS 2) as required.
IMPORTANT:
• If no second sensor is installed, disable this alarm. This failure alarm should be enabled if a
second temperature sensor is connected to the TS 2 input.
• This alarm is always latched and must be reset by the user.
3.7.5 LOW TEMPERATURE SENSOR 2 ALARM
Purpose: If enabled, the LOW TS 2 ALARM allows for alarming of low temperature conditions as
sensed by the second temperature sensor (TS 2).
Alarm Mask: ENABLE or DISABLE
Range: –76°F to 1058°F (–60°C to 570°C)
Procedure: Adjust LOW TS 2 ALARM temperature setpoint to the desired value. Note that the LOW
TS 2 ALARM must be enabled in order to adjust the LOW TS 2 ALARM temperature setpoint.
IMPORTANT:
• If no second sensor is installed, this alarm should be disabled. This alarm should be enabled
and the setpoint should be appropriate for the heating application. Maintaining a minimum
5°C differential between low temperature alarming and the CONTROL SETPOINT temperature
minimizes nuisance alarming due to momentary dips in temperature. Another alternative to
this is to configure the controller for non-latching temperature alarms.
• This alarm must be enabled and its setpoint must be below the CONTROL SETPOINT
temperature if fail-safe mode uses the temperature from TS 2.
3.7.6 HIGH TEMPERATURE SENSOR 2 ALARM
Purpose: If enabled, the HIGH TS 2 ALARM allows for alarming of high temperature conditions as
sensed by the second temperature sensor (TS 2).
Alarm Mask: ENABLE or DISABLE
Range: –76°F to 1058°F (–60°C to 570°C)
Procedure: Adjust the HIGH TS 2 ALARM temperature setpoint to the desired value. Note that the
HIGH TS 2 ALARM must be enabled in order to adjust the HIGH TS 2 ALARM temperature setpoint
unless the TS 2 HIGH LIMIT CUTOUT feature is enabled.
IMPORTANT: If no second sensor is installed, disable this alarm. This alarm may be used for
applications where a product that is sensitive to over temperature is involved. General usage could
result in nuisance alarms due to the flow of hot product or steam out. This may be a case where
the alarm could be enabled and non-latching temperature alarming used. A high temperature
INDUSTRIAL HEAT TRACING SOLUTIONS
EN- Raychem920series-IM-H56874 05/15
31 / 82
condition resulting from a forced on failure of the heating circuit should first be alarmed by the
SWITCH FAILURE ALARM. See section 3.8.18 on page 40 for more information.
3.7.7 LOW TEMPERATURE SENSOR ALARM FILTER TIME SETTING (V3.11 AND UP)
Purpose: The LOW TS ALARM FILTER will prevent LOW TS 1 and/or LOW TS 2 ALARMS from being
indicated until their corresponding alarm condition has existed for the duration of the LOW TS
ALARM FILTER time.
Range: 0 to 999 Minutes
Procedure: Adjust the LOW TS ALARM FILTER time to the desired value. Note that either the LOW
TS 1 ALARM and/or the LOW TS 2 ALARM must be enabled in order to adjust the LOW TS ALARM
FILTER time.
IMPORTANT:
• If an alarm condition appears and then disappears before the alarm filter time has expired, the
filter timer is reset and the alarm condition must exist again for the entire alarm filter time
before the corresponding alarm will be indicated.
• If the user resets an alarm while the alarm condition is still exists, then the alarm will not be
indicated again until the entire alarm filter time has expired.
3.7.8 HIGH TEMPERATURE SENSOR ALARM FILTER TIME SETTING (V3.11 AND UP)
Purpose: The HIGH TS ALARM FILTER will prevent HIGH TS 1 and/or HIGH TS 2 ALARMS from
being indicated until their corresponding alarm condition has existed for the duration of the HIGH
TS ALARM FILTER time.
Range: 0 to 999 minutes
Procedure: Adjust the HIGH TS ALARM FILTER time to the desired value. Note that either the
HIGH TS 1 ALARM and/or the HIGH TS 2 ALARM must be enabled in order to adjust the HIGH TS
ALARM FILTER time.
IMPORTANT:
• If an alarm condition appears and then disappears before the alarm filter time has expired, the
filter timer is reset and the alarm condition must exist again for the entire alarm filter time
before the corresponding alarm will be indicated.
• If the user resets an alarm while the alarm condition is still exists, the alarm will not be
indicated again until the entire alarm filter time has expired.
• The HIGH TS ALARM FILTER time setting does not affect the cutout time when the HIGH LIMIT
CUTOUT feature is enabled.
3.7.9 LATCH TEMPERATURE SENSOR ALARMS SETTING
Purpose: This allows for the selection of automatic clearing of all HIGH and LOW TS ALARMS
(non-latching) when a temperature alarm condi-tion no longer exists or permanent alarming of
such a condition (latching) until the alarm is manually reset.
Setting: YES (LATCHING) or NO (NONLATCHING)
Procedure: Adjust the LATCH TS ALARMS setting to the desired mode (latching or nonlatching).
IMPORTANT:
• If your application is subject to periodic situations where cold or hot product is part of the
process, it may be appropriate to configure the HTC for nonlatching temperature alarms to
avoid nuisance alarms. If it is important to be aware of any temperature alarm conditions that
may have existed in a pipe, the HTC should be configured for latching temperature alarms.
• This setting does not affect the TS FAILURE ALARMS; these are always latching.
3.7.10 CONTROL TEMPERATURE SENSOR FAILURE ALARM
Purpose: CONTROL TS FAILURE ALARM indicates a failure of the temperature sensor designated
as the control sensor.
One of eleven TS CONTROL MODES may be selected. These modes determine which TS INPUT
and/or EXT. INPUT is designated to provide the control temperature. See section 3.5.12 on page 24
for a full description of the temperature sensor control designations.
Alarm Mask: ENABLE or DISABLE
INDUSTRIAL HEAT TRACING SOLUTIONS
EN- Raychem920series-IM-H56874 05/15
32 / 82
Procedure: Enable or disable the alarming of a failure of the designated control temperature
sensor as required.
IMPORTANT: This alarm should always be enabled. If the controller experiences a CONTROL
TS FAILURE it will turn the output off or on (as spec-ified by TS FAIL MODE) until this alarm is
cleared. If the TS CONTROL MODE uses the EXTERNAL INPUT, a CONTROL TS FAILURE is selfclearing (i.e., is nonlatching).
3.8 Other Alarms
This Section defines the nontemperature-related alarming functions of the 920 controller: current,
ground fault, voltage and resistance. These parameters must be set up individually for both Point
A and Point B.
3.8.1 LOW LOAD CURRENT ALARM
Purpose: Alarms current levels that are lower than a preset limit for the application. Monitoring
for lower-than-expected current levels may be an effective means of continuity monitoring. See
also HIGH RESISTANCE ALARM in section 3.8.14 on page 39.
Alarm Mask: ENABLE or DISABLE
Range:0.3 to 100.0 amps
(CURRENT TURNS RATIO = 1.00)
Procedure: Adjust the LOW CURRENT ALARM level to the desired value. Note that the LOW
CURRENT ALARM must be enabled in order to adjust the LOW CURRENT ALARM level. Also note
that the LOW CURRENT ALARM level is affected by the CURRENT TURNS RATIO setting. The
absolute maximum adjusted LOW CURRENT ALARM level is 300.0 amps. The absolute minimum
adjusted LOW CURRENT ALARM level is 0.1 amps. See section 3.5.22 on page 26 for more
information regarding the CURRENT TURNS RATIO function.
Notes (V3.00 only):
• To minimize nuisance LOW CURRENT ALARMS, the HTC must detect a current level less than
the LOW CURRENT ALARM setpoint for a period longer than approximately 20 consecutive
seconds.
• For series-type heating cables, adjusting the LOW CURRENT ALARM to 50% of full load current
will properly alarm a problem and reduce nuisance alarms due to voltage dips. Parallel heaters
should be adjusted to a level as close as possible to full load current but lower than the current
at worst-case voltage. The low current setting as a percentage of full load current will vary
depending on the facility and its power system.
• A LOW CURRENT ALARM may also result from a switch failed open. The controller cannot
detect a switch failure due to no current. A no current condition would be identified by a LOW
CURRENT ALARM (if enabled) and the analog value reported with the alarm will be 0.0 A.
• It may be advantageous to consider using the HIGH RESISTANCE ALARM to indicate a cable
fault when using certain types of heaters. See sections 3.8.12 on page 38 and 3.8.14 on page 39
for an explanation of the resistance alarming feature.
3.8.2 LOW LOAD CURRENT ALARM FILTER TIME SETTING (V3.11 AND UP)
Purpose: The LOW CURRENT ALARM FILTER will prevent LOW LOAD CURRENT ALARMS from
being indicated until a low current condition has existed for the duration of the LOW CURRENT
ALARM FILTER time.
Range: 0 to 12 seconds
Procedure: Adjust the LOW CURRENT ALARM FILTER time to the desired value. Note that the LOW
CURRENT ALARM must be enabled in order to adjust the LOW CURRENT ALARM FILTER time.
IMPORTANT:
• If an alarm condition appears and then disappears before the alarm filter time has expired, the
filter timer is reset and the alarm condition must exist again for the entire alarm filter time
before the corresponding alarm will be indicated.
INDUSTRIAL HEAT TRACING SOLUTIONS
EN- Raychem920series-IM-H56874 05/15
33 / 82
• If the user resets an alarm while the alarm condition is still exists, the alarm will not be
indicated again until the entire alarm filter time has expired.
3.8.3 HIGH LOAD CURRENT ALARM
Purpose: Alarms current levels that are higher than a preset limit for the application.
Alarm Mask: ENABLE or DISABLE
Range:0.3 to 100.0 amps
(CURRENT TURNS RATIO = 1.00)
Procedure: Adjust the HIGH CURRENT ALARM level to the desired value. Note that the HIGH
CURRENT ALARM must be enabled in order to adjust the HIGH CURRENT ALARM level. Also note
that the HIGH CURRENT ALARM level is affected by the CURRENT TURNS RATIO setting. The
absolute maximum adjusted HIGH CURRENT ALARM level is 300.0 amps. The absolute minimum
adjusted HIGH CURRENT ALARM level is 0.1 amps. See section 3.5.22 on page 26 for more
information regarding the CURRENT TURNS RATIO function.
IMPORTANT: As the HTC automatically protects itself from overload, it would not normally be
necessary to enable this alarm. This automatic protection can be used effectively to guard against
accidental paralleling of heating circuits. In-rush or cold start currents typically associated with
self- regulating cables may cause nuisance HIGH CURRENT ALARMS. If this is undesirable the
alarm should be disabled.
3.8.4 HIGH LOAD CURRENT ALARM FILTER TIME SETTING (V3.11 AND UP)
Purpose: The HIGH CURRENT ALARM FILTER will prevent HIGH LOAD CURRENT ALARMS from
being indicated until a high current condition has existed for the duration of the HIGH CURRENT
ALARM FILTER time.
Range: 0 to 12 seconds
Procedure: Adjust the HIGH CURRENT ALARM FILTER time to the desired value. Note that the
HIGH CURRENT ALARM must be enabled in order to adjust the HIGH CURRENT ALARM FILTER
time.
IMPORTANT:
• If an alarm condition appears and then disappears before the alarm filter time has expired, the
filter timer is reset and the alarm condition must exist again for the entire alarm filter time
before the corresponding alarm will be indicated.
• If the user resets an alarm while the alarm condition is still exists, the alarm will not be
indicated again until the entire alarm filter time has expired.
3.8.5 HIGH GROUND-FAULT CURRENT ALARM
Purpose: Alarms ground-fault current levels which are higher than a preset limit for the
application.
Alarm Mask: ENABLE or DISABLE
Range: 20 to 250 mAmps
Procedure: Adjust the HIGH GFI ALARM level to the desired value. Note that the HIGH GFI ALARM
must be enabled in order to adjust the HIGH GFI level.
3.8.6 HIGH GROUND-FAULT CURRENT ALARM FILTER TIME SETTING (V3.11 AND UP)
Purpose: The HIGH GFI ALARM FILTER will prevent HIGH GFI ALARMS from being indicated until a
high GFI condition has existed for the duration of the HIGH GFI ALARM FILTER time.
Range: 0 to 12 seconds
Procedure: Adjust the HIGH GFI ALARM FILTER time to the desired value. Note that the HIGH GFI
ALARM must be enabled in order to adjust the HIGH GFI ALARM FILTER time.
IMPORTANT:
• If an alarm condition appears and then disappears before the alarm filter time has expired, the
filter timer is reset and the alarm condition must exist again for the entire alarm filter time
before the corresponding alarm will be indicated.
INDUSTRIAL HEAT TRACING SOLUTIONS
EN- Raychem920series-IM-H56874 05/15
34 / 82
• If the user resets an alarm while the alarm condition is still exists, the alarm will not be
indicated again until the entire alarm filter time has expired.
3.8.7 GROUND-FAULT TRIP ALARM
Purpose: This value sets the upper limit of allowable ground-fault leakage current. Exceeding this
limit will result in the output switch being latched off and the GFI TRIP ALARM activated to indicate
a ground fault condition.
Alarm Mask: ENABLE or DISABLE
Range: 20 to 250 mAmps
Procedure: If ground-fault tripping is desired, enable the GFI TRIP ALARM and adjust the GF TRIP
CURRENT to the desired value. To disable ground-fault tripping, disable the alarm. Note that the
GFI TRIP ALARM must be enabled in order to adjust the G.F. TRIP CURRENT level.
Caution: In order to implement a ground-fault trip function, all nongrounded power conductors
must be opened upon detec-tion of a ground-fault condition.
IMPORTANT: National Electrical Codes require that all legs of non-neutral based power sources
be opened upon detection of a ground fault. Multipole switch configurations should be used on
non-neutral based power systems. Check the requirements with your local electrical au-thority.
3.8.8 LOW VOLTAGE ALARM
Purpose: Alarms voltage levels that are lower than a preset limit for the application.
Alarm Mask: ENABLE or DISABLE
Range: 10 to 330 volts (VOLTAGE TURNS RATIO = 1.00)
Procedure: Adjust the LOW VOLTAGE ALARM level to the desired value. The LOW VOLTAGE ALARM
must be enabled to adjust the LOW VOLTAGE ALARM level. Also, the LOW VOLTAGE ALARM level
is affected by the VOLTAGE TURNS RATIO setting. The absolute maximum adjusted LOW VOLTAGE
ALARM level is 1000 volts. The absolute minimum adjusted LOW VOLTAGE ALARM level is 1 volt.
See section 3.5.21 on page 26 for more information regarding the VOLTAGE TURNS RATIO.
IMPORTANT:
• The LOW VOLTAGE ALARM is only available if VOLTAGE SOURCE is set to the Point being used.
• The LOW VOLTAGE ALARM should always be enabled. Since the HTC may be powered from
either of two switch interface modules (assum-ing a dual-point installation), the loss of power on
one circuit will not necessarily be indicated at the alarm output or as a communications failure.
3.8.9 LOW VOLTAGE ALARM FILTER TIME SETTING (V3.11 AND UP)
Purpose: The LOW VOLTAGE ALARM FILTER will prevent LOW VOLTAGE ALARMS from being indicated
until a low voltage condition has existed for the duration of the LOW VOLTAGE ALARM FILTER time.
Range: 0 to 12 seconds
Procedure: Adjust the LOW VOLTAGE ALARM FILTER time to the desired value. The LOW VOLTAGE
ALARM must be enabled to adjust the LOW VOLTAGE ALARM FILTER time. Also, the LOW VOLTAGE
ALARM FILTER is only available if VOLTAGE SOURCE is set to the Point being used.
IMPORTANT:
• If an alarm condition appears and then disappears before the alarm filter time has expired, the
filter timer is reset and the alarm condition must exist again for the entire alarm filter time
before the corresponding alarm will be indicated.
• If the user resets an alarm while the alarm condition is still exists, the alarm will not be
indicated again until the entire alarm filter time has expired.
3.8.10 HIGH VOLTAGE ALARM
Purpose: Alarms voltage levels that are higher than a preset limit for the application. Serves as a
monitor of the voltage used to power the trace circuit.
Alarm Mask: ENABLE or DISABLE
Range: 10 to 330 volts (VOLTAGE TURNS RATIO = 1.00)
Procedure: Adjust the HIGH VOLTAGE ALARM level to the desired value. The HIGH VOLTAGE
ALARM must be enabled in order to adjust the HIGH VOLTAGE ALARM level. Also, the HIGH
VOLTAGE ALARM level is affected by the VOLTAGE TURNS RATIO setting. The absolute maximum
INDUSTRIAL HEAT TRACING SOLUTIONS
EN- Raychem920series-IM-H56874 05/15
35 / 82
adjusted HIGH VOLTAGE ALARM level is 1000 volts. The absolute minimum adjusted HIGH
VOLTAGE ALARM level is 1 volt. See section 3.5.21 on page 26 for more information regarding the
VOLTAGE TURNS RATIO function.
IMPORTANT: The HIGH VOLTAGE ALARM is only available if VOLTAGE SOURCE is set to the Point
being used.
3.8.11 HIGH VOLTAGE ALARM FILTER TIME SETTING (V3.11 AND UP)
Purpose: The HIGH VOLTAGE ALARM FILTER will prevent HIGH VOLTAGE ALARMS from being
indicated until a high voltage condition has existed for the duration of the HIGH VOLTAGE ALARM
FILTER time.
Range: 0 to 12 seconds
Procedure: Adjust the HIGH VOLTAGE ALARM FILTER time to the desired value. The HIGH
VOLTAGE ALARM must be enabled to adjust the HIGH VOLTAGE ALARM FILTER time. Also, the
HIGH VOLTAGE ALARM FILTER is only available if VOLTAGE SOURCE is set to the Point being used.
IMPORTANT:
• If an alarm condition appears and then disappears before the alarm filter time has expired, the
filter timer is reset and the alarm condition must exist again for the entire alarm filter time
before the corresponding alarm will be indicated.
• If the user resets an alarm while the alarm condition is still exists, the alarm will not be
indicated again until the entire alarm filter time has expired.
3.8.12 LOW RESISTANCE ALARM
Purpose: Alarms heater resistance levels that have decreased from the NOMINAL RESISTANCE
setting by more than the selected amount.
Alarm Mask: ENABLE or DISABLE
Range: 1 to 100% (deviation from NOMINAL RESISTANCE)
Procedure: Adjust the LOW RESISTANCE ALARM deviation to the desired value. The LOW
RESISTANCE ALARM must be enabled in order to adjust the LOW RESISTANCE deviation.
IMPORTANT:
• This feature is not normally enabled. It can be used effectively to guard against accidental
paralleling of heating circuits. Be careful when using this alarm feature with heating cables
that exhibit a variable resistance with temperature. Low resistance alarming may not be
practical when the load has an increasing resistance with temperature (such as self-regulating
cables).
• Use of the LOW RESISTANCE ALARM assumes that the controller power is derived from
the same circuit as the tracing power (either by direct connection or through a step-down
transformer). Disable this alarm if the controller is powered from a separate circuit.
• No LOW RESISTANCE ALARMS will be generated if the measured voltage is below the LOW
VOLTAGE ALARM setpoint, regardless of whether the LOW VOLTAGE ALARM is enabled. This
stops an alarm from being generated when the circuit power is turned off. If the LOW VOLTAGE
ALARM is disabled ensure that the LOW VOLTAGE setpoint is set to a relevant level otherwise
no LOW RESISTANCE ALARMS will occur.
• LOW RESISTANCE ALARMS will only be generated if the output switch is on.
3.8.13 LOW RESISTANCE ALARM FILTER TIME SETTING (V3.11 AND UP)
Purpose: The LOW RESISTANCE ALARM FILTER will prevent LOW RESISTANCE ALARMS
from being indicated until a low resistance condition has existed for the duration of the LOW
RESISTANCE ALARM FILTER time.
Range: 0 to 12 seconds
Procedure: Adjust the LOW RESISTANCE ALARM FILTER time to the desired value. The LOW
RESISTANCE ALARM must be enabled to adjust the LOW RESISTANCE ALARM FILTER time.
IMPORTANT:
• If an alarm condition appears and then disappears before the alarm filter time has expired, the
filter timer is reset and the alarm condition must exist again for the entire alarm filter time
INDUSTRIAL HEAT TRACING SOLUTIONS
EN- Raychem920series-IM-H56874 05/15
36 / 82
before the corresponding alarm will be indicated.
• If the user resets an alarm while the alarm condition is still exists, the alarm will not be
indicated again until the entire alarm filter time has expired.
3.8.14 HIGH RESISTANCE ALARM
Purpose: Alarms heater resistance levels that have increased from the NOMINAL RESISTANCE
setting by more than the selected amount. The HIGH RESISTANCE ALARM may be used to indicate
an open or a high resistance connection or, when using constant-wattage parallel cables, may
indicate the failure of one or more heating zones. It may also be used to monitor a failed seriestype cable or connection in 3-phase applications while minimizing nuisance alarms created by
voltage fluctuations.
Alarm Mask: ENABLE or DISABLE
Range: 1 to 250% (deviation from NOMINAL RESISTANCE)
Procedure: Adjust the HIGH RESISTANCE ALARM level to the desired value. The HIGH
RESISTANCE ALARM must be enabled to adjust the HIGH RESISTANCE deviation.
IMPORTANT:
• Using the LOW CURRENT ALARM feature to ensure that unexpected decreases in current
consumption by the heating cable are alarmed is a reliable method of monitoring the integrity
of series-type heating cables. When using parallel-type heaters (zoned constant-wattage or
self-regulating) or in 3-phase installations, the LOW CURRENT ALARM setting must be chosen
as close as possible to the lowest expected current to detect failed zones, cable degradation,
or a lost phase. The problem with such a close setting is that it inevitably leads to nui-sance
alarms, particularly when voltage fluctuations are present. By using the HIGH RESISTANCE
ALARM, nuisance alarms due to voltage dips may be minimized.
• Use of the HIGH RESISTANCE ALARM assumes that the controller power is derived from
the same circuit as the tracing power (either by direct connection or through a step-down
transformer). Disable this alarm if the controller is powered from a separate circuit.
• Be careful when using this alarm feature with heating cables that exhibit a variable resistance
with temperature. High resistance alarming may not be as effective if the load has a decreasing
resistance with temperature.
• No HIGH RESISTANCE ALARMS will be generated if the measured voltage is below the LOW
VOLTAGE ALARM setpoint, regardless of whether the LOW VOLTAGE ALARM is enabled. This
stops an alarm from being generated when the circuit power is turned off. If the LOW VOLTAGE
ALARM is disabled ensure that the LOW VOLTAGE setpoint is set to a relevant level, otherwise
no HIGH RESISTANCE ALARMS will occur.
• HIGH RESISTANCE ALARMS will only be generated if the output switch is on.
3.8.15 HIGH RESISTANCE ALARM FILTER TIME SETTING (V3.11 AND UP)
Purpose: The HIGH RESISTANCE ALARM FILTER will prevent HIGH RESISTANCE ALARMS
from being indicated until a high resistance condition has existed for the duration of the HIGH
RESISTANCE ALARM FILTER time.
Range: 0 to 12 seconds
Procedure: Adjust the HIGH RESISTANCE ALARM FILTER time to the desired value. The HIGH
RESISTANCE ALARM must be enabled to adjust the HIGH RESISTANCE ALARM FILTER time.
IMPORTANT:
• If an alarm condition appears and then disappears before the alarm filter time has expired, the
filter timer is reset and the alarm condition must exist again for the entire alarm filter time
INDUSTRIAL HEAT TRACING SOLUTIONS
EN- Raychem920series-IM-H56874 05/15
37 / 82
before the corresponding alarm will be indicated.
• If the user resets an alarm while the alarm condition is still exists, the alarm will not be
indicated again until the entire alarm filter time has expired.
3.8.16 NOMINAL RESISTANCE SETTING
Purpose: This parameter defines the nominal expected heater resistance. A value must be
entered by the user to allow the HIGH and LOW RESISTANCE ALARMS to be used. In installations
where the power source may experience periodic fluctuations (surges and/or brown-out conditions), alarming on resistance deviation offers an improved method of monitoring tracer integrity
over simple LOW and HIGH CURRENT ALARMS. Since the ratio of voltage to current is monitored,
the HIGH and LOW RESISTANCE ALARMS offer cable monitoring that is relatively immune to
voltage fluctuations.
Range: 2.00 to 2000.00 Ω
Procedure: The NOMINAL RESISTANCE value can only be set if either the LOW RESISTANCE and/
or the HIGH RESISTANCE ALARMS are enabled. Once the controller and the heating cable have
been installed, the following procedure should be used to determine the NOMINAL RESISTANCE
setting:
• Adjust the CONTROL SETPOINT temperature to turn on the output switch.
• Allow the load to come up to design temperature and its power consumption to stabilize.
• Using the 920 Operator Console, access the RESISTANCE reading and record its value. Return
the CONTROL SETPOINT temperature to its proper setting.
• Enter the recorded resistance value as the NOMINAL RESISTANCE setting.
IMPORTANT: The setup procedure outlined above may have to be repeated a number of times
to arrive at a correct nominal resistance setting. This value will be affected by the heating cable
temperature, which in turn is affected by ambient temperature, insulation level, a full or empty
pipe or vessel, etc.
3.8.17 OVERCURRENT TRIP ALARM (SSR ONLY)
Purpose: The overcurrent trip feature is always enabled when using an SSR output switch and is
used to provide protection for the output switch. Enabling this alarm will only inform the user of an
excessively high current condition and that the output switch has been latched off. During a high
current condition, the controller attempts to soft start a heating cable by a technique involving
measured in-rush current and the SWITCH CURRENT RATING. If the controller is unable to start
the cable, it will eventually trip its output switch off and will not retry or pulse its output switch
again. At this point the OVERCURRENT TRIP ALARM is latched on.
IMPORTANT:
• The controller is not a safety cutout or an overcurrent protective device as defined by the
National and Canadian Electrical Codes (NEC and CEC). A protective device such as a circuit
breaker or fuse must be included as part of a proper design and be selected in accordance with
the requirements defined in the National Electrical Code (NEC) and/or the Canadian Electrical
Code (CEC).
• The controller cannot protect the SSR from short circuits or excessive overcurrent conditions.
Always ensure that the power is off prior to performing any maintenance or troubleshooting of
the heating circuit. Verify that no damage has occurred to the cable or the controller prior to
re-energizing the circuit.
Alarm Mask: ENABLE or DISABLE
Procedure: Adjust the SWITCH CURRENT RATING setting to the actual current rating of the SSR.
Enable or disable the alarm as required. Note that the OVERCURRENT TRIP ALARM does not have
to be enabled in order to adjust the SWITCH CURRENT RATING setting.
IMPORTANT: This alarm should be left enabled since an overcurrent trip condition would
normally represent a serious problem. This is a fac-tory-set alarm value and disabling the alarm
does not disable the overcurrent trip function. In some applications the use of self-regulating
cables will produce very high in-rush currents during cold startup. These currents may exceed
INDUSTRIAL HEAT TRACING SOLUTIONS
EN- Raychem920series-IM-H56874 05/15
38 / 82
the overcurrent trip limit and the controller will not be able to soft start the trace circuit. If this
condition persists, please contact your nearest sales office for recommendations and solutions to
this problem.
3.8.18 SWITCH FAILURE ALARM
Purpose: The purpose of the SWITCH FAILURE ALARM is to indicate that an output switch failure
has occurred. The controller determines that if the output switch is turned off and there is load
current present, then the output switch has failed closed and the alarm is latched on.
Alarm Mask: ENABLE or DISABLE
Procedure: Enable or disable the alarming of an output switch that has failed in the closed
position.
IMPORTANT: The SWITCH FAILURE ALARM should always be enabled. A high temperature
condition as a result of a failed circuit can only be caused if the output switch fails closed. When an
output switch fails closed, the controller cannot turn the tracer power off, therefore no protection
features are available (ground-fault trip, power limiting, etc.). If a SWITCH FAILURE ALARM is
detected, the unit should be serviced immediately.
3.8.19 HTC RESET ALARM
Purpose: The HTC RESET ALARM is used to indicate:
1. Power to the HTC has been interrupted and subsequently restored.
2. A transient has caused the HTC’s microprocessor to restart.
3. An internal condition has caused the HTC’s microprocessor to restart its program.
Alarm Mask: ENABLE or DISABLE
Procedure: Enable or disable alarming on reset as desired.
IMPORTANT: Normally the HTC RESET ALARM is left disabled since powering the controller off
and on for maintenance or troubleshooting would require the user to reset this alarm every time.
If the particular installation includes a Model 780/GCC-9000, this alarm may be left enabled
since resets are not considered normal occurrences and the Model 780/GCC-9000 provides the
capability to easily log and reset alarms such as these. The difference in time between when a
COMMUNICATIONS FAIL ALARM and an HTC RESET ALARM are logged provide an indication of
how long the circuit has been “OFF.”
3.8.20 CIRCUIT BREAKER LIMITING STATUS (SSR ONLY)
Purpose: The circuit breaker limiting feature is always enabled when using an SSR output switch
and is intended to prevent the circuit breaker immediately upstream of the controller from tripping
during a temporary overcurrent condition. Enabling this alarm will only inform the user that circuit
breaker limiting is currently active.
Alarm Mask: ENABLE or DISABLE
Procedure: Adjust the CIRCUIT BREAKER CURRENT RATING setting to the heating circuit breaker
size (i.e. 15.0 or 20.0 amps). Enable or disable the alarm as required. The CIRCUIT BREAKER
LIMITING ALARM need not be enabled in order to adjust the CIRCUIT BREAKER CURRENT RATING
setting.
IMPORTANT:
• This is a non-latching alarm.
• This alarm is advisory. If the measured current exceeds the level that would cause the
upstream circuit breaker to release, the HTC will begin to switch the SSR ON and OFF rapidly to
limit the average current to an acceptable level.
3.8.21 POWER-LIMITING STATUS (SSR ONLY)
Purpose: The power-limiting feature is always enabled when using an SSR output switch and is
intended to limit the average amount of power that is applied to the trace circuit. The controller
measures the voltage and current of the trace circuit and will vary its output switch to limit the
amount of power applied to the trace to the value set by the MAXIMUM POWER setting. Enabling
this alarm will only inform the user that power limiting is currently active.
Alarm Mask: ENABLE or DISABLE
INDUSTRIAL HEAT TRACING SOLUTIONS
EN- Raychem920series-IM-H56874 05/15
39 / 82
Procedure: Adjust the MAXIMUM POWER setting to the desired value. Enable or disable the alarm
as required. The POWER LIMITING ALARM need not be enabled to adjust the MAXIMUM POWER
setting.
IMPORTANT:
• This is a non-latching alarm.
• This alarm is advisory and is normally disabled. It will be active if the MAXIMUM POWER setting
is set below the power output level required for temperature maintenance. In other words, if
the circuit demands the maximum power allowed and the alarm is enabled, then this alarm will
be indicated and the output switch will pulse ON and OFF to limit the average power output to a
value approximately equal to the MAXIMUM POWER setting
3.8.22 SWITCH LIMITING STATUS (SSR ONLY)
Purpose: The switch limiting feature is always enabled when using an SSR output switch and
provides protection for the output switch. Enabling this alarm will only inform the user that switch
limiting is currently active and an excessively high current condition is present. The controller
pulses its output switch for a small number of cycles and reads the resulting current. If the
measured current exceeds the SWITCH RATING setting, the duty cycle of its output switch will be
varied so that an average current not exceeding the SWITCH RATING setting is maintained.
Alarm Mask: ENABLE or DISABLE
Procedure: Adjust the SWITCH CURRENT RATING setting to the actual current rating of the SSR.
Enable or disable the alarm as required. The SWITCH LIMITING ALARM need not be enabled to
adjust the SWITCH CURRENT rating setting.
IMPORTANT:
• This is a non-latching alarm.
• This alarm is normally enabled. Currents in this range cannot be considered normal and should
be investigated.
3.8.23 CONTACTOR COUNT ALARM (V3.11 AND UP)
Purpose: Generates an alarm if the number of off-to-on transitions of a contactor reaches or
exceeds the CONTACTOR COUNT ALARM setting. This serves as a method to perform preventative
maintenance on the contactor before a failure is likely to occur.
Alarm Mask: ENABLE or DISABLE
Range: 0 to 999999 off-to-on transitions
Procedure: Adjust the CONTACTOR ALARM setting to the desired value. The CONTACTOR ALARM
must be enabled to adjust the CONTACTOR ALARM setting.
IMPORTANT: The CONTACTOR ALARM is only available if the SWITCH CONTROL MODE is set to
either DEADBAND or PROPORTIONAL AMBIENT CONTACTOR.
3.8.24 EEROM DATA FAILURE ALARM
Purpose: The EEROM DATA FAILURE ALARM indicates that the controller has detected a failure in
its nonvolatile memory.
Alarm Mask: ENABLE or DISABLE
Procedure: Enable or disable alarming of a nonvolatile memory failure as desired.
IMPORTANT: The EEROM DATA FAILURE ALARM should always be enabled. This memory
stores all of the controller’s configuration and calibra-tion settings and the alarm will only be
generated if the microprocessor cannot bypass the failed area of its memory. This indicates an
internal problem, and the control module should be replaced and returned to Pentair Thermal
Managament for repair.
3.9 Communications Setup
The following section describes the setup parameters that relate to the way the controller
communicates with another device. If the optional communications interface is not installed in
INDUSTRIAL HEAT TRACING SOLUTIONS
EN- Raychem920series-IM-H56874 05/15
40 / 82
the 920 control module, these parameters need not be configured. All these parameters are
common for both of the two control points—Point A and Point B, except the HTCBUS™ ADDRESS,
MODBUS™ ADDRESS, and MODBUS™ SUB ADDRESS settings, as applicable.
3.9.1 PROTOCOL
Purpose: Defines the communications language used by the controller to communicate with other
devices.
Setting: HTCBUS or MODBUS ASCII (V3.11+) or MODBUS RTU (V3.11+)
Procedure: Select the HTCBUS™ protocol when communicating with existing Pentair
Thermal Managament Heat Trace Control products, including the Model 780/GCC-9000 Group
Communications Controller.
If you are communicating directly with the controller using a different device, select the MODBUS
protocol. For a detailed description of the controller’s MODBUS mapping, please refer to the
separate Raychem 920 Series Heat Trace Controller—Modbus Protocol Interface Mapping
document (Pentair Thermal Managament reference H57366 ).
3.9.2 HTCBUS™ ADDRESS
Purpose: Defines the communications address to be used by the controller when using
the HTCBUS™ protocol to communicate with a Model 780/GCC-9000. When in the Point A
configuration menu, this sets the Point A HTCBUS™ ADDRESS; when in the Point B configuration
menu, this sets the Point B HTCBUS™ ADDRESS. Either may be set independently of the other.
Range: 1 to 16,777,215
Procedure: Set the communications address as desired. This must be an address unique to the
entire communications network to avoid messaging conflicts. The HTCBUS™ protocol must be
selected in order to set the HTCBUS™ ADDRESS.
IMPORTANT: A unique HTCBUS™ communications address is always assigned by Pentair Thermal
Managament and identified by the label on the front of the 920 control module (see Figure 3.1).
Use the preassigned address whenever possible to minimize the chances of an address being
duplicated in the user’s system.
3.9.3 MODBUS ADDRESS (V3.11 AND UP)
Purpose: The MODBUS™ ADDRESS, along with the MODBUS™ SUB ADDRESS, defines the
communications address to be used by the controller when using either MODBUS™ protocol to
communicate with a MODBUS™ compatible device. When in the Point A configuration menu, this
sets the Point A MODBUS™ ADDRESS; when in the Point B configuration menu, this sets the Point
B MODBUS™ ADDRESS. Either may be set independently of the other.
Range: 1 to 247
Procedure: Set the communications address as desired. Together with the MODBUS™ SUB
ADDRESS, this combination must be unique to the entire communications network to avoid
messaging conflicts. Either MODBUS™ protocol must be selected in order to set the MODBUS™
AD-DRESS.
3.9.4 MODBUS SUB ADDRESS (V3.11 AND UP)
Purpose: The MODBUS™ SUB ADDRESS, along with the MODBUS™ ADDRESS, defines the
communications address to be used by the controller when using either MODBUS™ protocol to
communicate with a MODBUS™ compatible device. When in the Point A configuration menu, this
sets the Point A MODBUS™ SUB ADDRESS; when in the Point B configuration menu, this sets the
Point B MODBUS™ SUB ADDRESS. Either may be set independently of the other.
Range: 0 to 31
Procedure: Set the communications sub address as desired. Together with the MODBUS™
ADDRESS, this combination must be unique to the entire communications network to avoid
messaging conflicts. Either MODBUS™ protocol must be selected in order to set the MODBUS™
SUB ADDRESS.
IMPORTANT: Since a 920 HTC does not use all 65,535 data addresses available for each
MODBUS™ ADDRESS, this data address range is subdi-vided to allow up to 32 HTCs to share the
INDUSTRIAL HEAT TRACING SOLUTIONS
EN- Raychem920series-IM-H56874 05/15
41 / 82
same MODBUS™ ADDRESS. This increases the number of HTCs allowed on a single MODBUS™
port from 247 to 7,904 (=247 x 32). This requires that any HTC sharing the same MODBUS™
ADDRESS as another HTC must have its own unique MODBUS™ SUB ADDRESS.
3.9.5 BAUD RATE
Purpose: Defines the data rate at which communications occur.
Setting: AUTO or 9600 or 4800 or 2400 or 1200 or 600 or 300
Procedure: Select the data rate to be compatible with other devices that will be connected to the
controller for communications purposes.
IMPORTANT: Not all communications interfaces support the various data rates, so the data rate
should be set to AUTO. The controller will au-tomatically select a BAUD RATE that is compatible
with the communications interface installed. If BAUD RATE = AUTO and a MODEM communi-cation
interface is used, a data rate of 300 is selected. Otherwise, if BAUD RATE = AUTO and a nonMODEM communications interface is used, a data rate of 9600 is used.
3.9.6 PARITY (MODBUS™) (V3.11 AND UP)
Purpose: Defines the type of parity bit used with MODBUS™ communications.
Setting: NONE or ODD or EVEN
Procedure: Select the desired type of parity. Note that PARITY can only be selected when using
either MODBUS™ protocol.
3.9.7 HARDWARE
Purpose: Identifies the type of communications interface installed in the 920 control module.
The controller automatically determines and displays which communications interface type is
available.
Values: NONE, MODEM or RS-232 or RS-485
3.9.8 DRIVER
Purpose: Defines the way the controller’s program communicates with the communications
interface.
Setting: AUTO or RS-232 or RS-485 or MODEM
Procedure: Select AUTO to enable the controller to choose the setting that matches the
communications interface installed.
3.9.9 PROFILE
Purpose: Defines the way the controller’s program supports communications handshaking and
communication interface signals.
Setting: AUTO or
FLOW CONTROL RS-232 or
STANDARD RS-232 or
3-WIRE RS-232 or
RS-485 or
EXTERNAL MODEM or
1200 BAUD MODEM or
300 BAUD MODEM
Procedure: Select the PROFILE to be compatible with other devices connected to the controller for
communications purposes. The setting should be AUTO. The controller will automatically select a
profile based on the type of communications interface installed in the 920 control module.
IMPORTANT:
• AUTO: Selects a communications profile based on the data rate and the type of communications
interface installed in the control module.
• FLOW CONTROL RS-232: Continuously asserts RTS (Request To Send), CTS (Clear To Send) is
required to enable any data transmitted, uses DCD (Data Carrier Detect) to qualify receive data.
• STANDARD RS-232: Continuously asserts RTS, CTS is required to initiate a transmit sequence,
INDUSTRIAL HEAT TRACING SOLUTIONS
EN- Raychem920series-IM-H56874 05/15
42 / 82
but is ignored once transmitting has begun, uses DCD to qualify receive data. This is the profile
used when PROFILE = AUTO and an RS-232 communication interface is used with 920 V3.00.
• 3-WIRE RS-232: Continuously asserts RTS, CTS and DCD are ignored. This is the profile used
when PROFILE = AUTO and an RS-232 commu-nication interface is used with 920 V3.11+.
• RS-485: Uses RTS and the Tx Delay timer, CTS and DCD are ignored. This is the profile used
when PROFILE = AUTO and an RS-485 commu-nication interface is used.
• EXTERNAL MODEM: Uses RTS and the Tx Delay timer, ignores CTS, uses DCD to qualify each
receive data character and to sense an idle channel condition.
• 1200 BAUD MODEM: Uses RTS with a fixed 10 msec Tx Delay time, ignores CTS, uses DCD to
qualify each receive data character. This is the profile used when PROFILE = AUTO,
BAUD RATE = 1200 and a MODEM communication interface is used.
• 300 BAUD MODEM: Uses RTS with a fixed 30 msec Tx Delay time, ignores CTS, uses DCD to
qualify each receive data character. This is the profile used when PROFILE = AUTO,
BAUD RATE ¦ 1200 and a MODEM communication interface is used.
3.9.10 TX DELAY
Purpose: Allows a programmable delay between the receipt of a communications message and
the controller’s reply. In some applications, it may be necessary to delay the controller’s response
to an inquiry for a short period of time to allow external devices to start up, stabilize, and/or
synchronize.
Range: 0.00 to 2.50 seconds
Procedure: Set the amount of delay between the receipt of a message and the controller’s
response as required.
IMPORTANT: This selectable TX DELAY is only used if the PROFILE is set to either RS-485 or AUTO
and an RS-485 interface is installed.
3.10 Operator Console Functions
The following features are part of the controller’s programming, but are only used in conjunction
with the optional 920 Operator Console. For a detailed description of each of the console features
and operating instructions, refer to the separate document Raychem 920 Series HTC Operator
Console—Installation and Operating Instructions (Pentair Thermal Managament reference
H56903) for the particular version of controller firmware that you are using.
3.10.1 PASSCODE
Purpose: The four-digit PASSCODE feature prevents unauthorized users from modifying the
controller’s configuration parameters via a 920 Operator Console.
Range: 0000 to 9999
Procedure: Enter the desired PASSCODE (in the “Common Setup” sub-menu) using the optional
920 Operator Console keypad. A PASSCODE of 0000 disables the lockout feature and allows all
configuration parameters to be modified using the 920 Operator Console without requiring a
PASSCODE. Setting the PASSCODE to any other value will require the database to be unlocked,
by entering the correct PASSCODE, prior to modifying any of the controller’s configuration
parameters using the optional 920 Operator Console.
IMPORTANT: The PASSCODE can only be edited if it is set to 0 or the database has been unlocked
by entering the proper PASSCODE.
3.10.2 LOCK DATABASE
Purpose: If the PASSCODE has been enabled (PASSCODE is not set to 0) and the user has
unlocked console modification access to the control-ler’s configuration parameters, the LOCK
DATABASE feature allows the user to re-lock this modification access once programming has been
completed.
Procedure: Select the LOCK DATABASE function (at the end of the “Configuration Mode Main
Menu”) to lock out 920 Operator Console config-uration modification access. The display will
INDUSTRIAL HEAT TRACING SOLUTIONS
EN- Raychem920series-IM-H56874 05/15
43 / 82
confirm the operation by displaying a “DATABASE LOCKED” message.
IMPORTANT: 920 Operator Console configuration modification access will automatically re-lock
after approximately 5 minutes of keypad inactivity.
3.10.3 UNLOCK DATABASE
Purpose: If a PASSCODE has been enabled (PASSCODE is not set to 0) and the user wants to
modify any of the controller’s configuration pa-rameters using a 920 Operator Console, the
database must first be unlocked.
Procedure: Try modifying any configuration parameter, or select the UNLOCK DATABASE function
(at the end of the “Configuration Mode Main Menu” for V3.11 and up), and a prompt for the
PASSCODE will appear. If the correct PASSCODE is entered, the display will confirm the opera-tion
by displaying a DATABASE UNLOCKED message.
3.10.4 TEST TRACING
Purpose: The TEST TRACING feature provides an easy method of temporarily overriding the
temperature control, without having to modify the CONTROL SETPOINT temperature or any other
configuration parameter.
Procedure: Select the TEST TRACING function to force the output switch on for approximately 30
seconds. After the test time has expired, the unit will automatically revert to normal operation.
IMPORTANT:
• This feature only overrides temperature control; it does not override other control parameters
such as power limiting.
• This feature is inhibited if the point is in load-shedding mode.
3.10.5 DISPLAY TEST (V3.11 AND UP)
Purpose: The DISPLAY TEST feature provides an easy method of illuminating each display
segment and all the LEDs of the 920 Operator Con-sole to ensure that they are functioning
properly.
Procedure: Select the DISPLAY TEST and watch the 920 console to verify that each display
segment and each LED is illuminated during the test sequence.
IMPORTANT: Pressing any key on the 920 Operator Console keypad during the DISPLAY TEST
causes the DISPLAY TEST to abort.
3.11 Copy Configuration Functions (V3.11 and up)
The following functions provide a quick method of setting all of the controller’s configuration
parameters to a predefined state.
3.11.1 COPY DEFAULTS TO COMMON (V3.11 AND UP)
Purpose: Loads Pentair Thermal Managament’ default configuration parameters that are common
to both Point A and Point B as defined in Appendix G.
Procedure: Enter the “Copy Configuration Sub-Menu” and select DEFAULTS TO COMMON.
IMPORTANT:
• This function overwrites the communication configuration parameters, which could affect
existing communications to the controller.
• This function causes the OVERRIDE SOURCE for each point to be set to REMOTE. This is
because the EXTERNAL INPUT setting is set to NOT USED.
3.11.2 COPY DEFAULTS TO POINT A (V3.11 AND UP)
Purpose: Loads the point-specific Pentair Thermal Managament default configuration
parameters, as defined in Appendix G, for Point A. As well, all of Point A’s maintenance data are
INDUSTRIAL HEAT TRACING SOLUTIONS
EN- Raychem920series-IM-H56874 05/15
44 / 82
reset. All load-shedding parameters (including fail-safe) are configured with default values. The
CONSOLE SETPOINT MAXIMUM and MINIMUM are also configured with default values.
Procedure: Enter the “Copy Configuration Sub-Menu” and select DEFAULTS TO A.
3.11.3 COPY DEFAULTS TO POINT B (V3.11 AND UP)
Purpose: Loads the point-specific Pentair Thermal Managament default configuration
parameters, as defined in Appendix G, for Point B. As well, all of Point B’s maintenance data are
reset. All load-shedding parameters (including fail safe) are configured with default values. The
CONSOLE SETPOINT MAXIMUM and MINIMUM are also configured with default values.
Procedure: Enter the “Copy Configuration Sub-Menu” and select DEFAULTS TO B.
3.11.4 COPY POINT A TO POINT B (V3.11 AND UP)
Purpose: Copies the point-specific configuration parameters of Point A to Point B. Point A’s
configuration parameters are not changed.
Procedure: Enter the “Copy Configuration Sub-Menu” and select A TO B.
IMPORTANT:
• To ensure that the TAGs for both points are not the same, Point A’s TAG is copied, the last
character incremented by one, and then written to Point B’s TAG.
• None of the communications addresses or the maintenance data values are copied.
3.11.5 COPY POINT B TO POINT A (V3.11 AND UP)
Purpose: Copies the point-specific configuration parameters of Point B to Point A. Point B’s
configuration parameters are not changed.
Procedure: Enter the “Copy Configuration Sub-Menu” and select B TO A.
IMPORTANT:
• To ensure that the TAGs for both points are not the same, Point B’s TAG is copied, the last
character incremented by one, and then written to Point A’s TAG.
• None of the communications addresses or the maintenance data values are copied.
INDUSTRIAL HEAT TRACING SOLUTIONS
EN- Raychem920series-IM-H56874 05/15
45 / 82
Section 4 – Monitored Parameters
4.1 Introduction
The following is a brief summary of each of the measured and calculated parameters the 920
series control module provides to the user. Detailed information regarding settings, alarms limits,
etc. may be found in Section 3 on page 18. For detailed information regarding the display of these
variables using the 920 Operator Console, Model 780/GCC-9000, Raychem Supervisor or other
interface, refer to the ap-propriate user manuals.
4.2 Analog Readings
4.2.1 CONTROL TEMPERATURE
Purpose: This is the temperature the controller uses to determine whether its output switch
should be on or off. Depending on the TS CONTROL MODE setting, whether one or two RTDs are
installed, and TEMPBUS™ is being used, the CONTROL TEMPERATURE may be derived from TS
1, TS 2, TEMPBUS™ or a combination of the three temperatures. See section 3.5.12 on page 24 of
this manual for further details regarding the TS CONTROL MODE settings.
4.2.2 TS 1 TEMPERATURE
Purpose: This temperature is the value the controller reads from the RTD connected to its
TS 1 input. Depending on the TS CONTROL MODE, it may be used to determine the CONTROL
TEMPERATURE (see section 4.2.1 on page 47).
IMPORTANT: (V3.11 and up): If the TS 1 input is not being used by the controller, the TS 1
TEMPERATURE is not displayed.
IMPORTANT: Changing the TS Type will affect the temperature reading.
4.2.3 TS 2 TEMPERATURE
Purpose: This temperature is the value that the controller is reading from the RTD connected to
its TS 2 input. Depending on the TS CONTROL MODE, it may be used to determine the CONTROL
TEMPERATURE (see section 4.2.1 on page 47).
IMPORTANT: (V3.11 and up): If the TS 2 input is not being used by the controller, the TS 2
TEMPERATURE is not displayed.
IMPORTANT: Changing the TS Type will affect the temperature reading.
4.2.4 LOAD CURRENT
Purpose: The LOAD CURRENT reading indicates the average current being drawn by the heating
cable.
IMPORTANT: The controller calculates the LOAD CURRENT using the current sensed by the switch
interface module multiplied by the CURRENT TURNS RATIO to yield an adjusted current value.
4.2.5 RESISTANCE
Purpose: Resistance is calculated using the average adjusted voltage reading divided by the
average adjusted current reading to yield a load resistance in ohms. If the controller’s output
switch is on but no current is present, the RESISTANCE will read “open circuit.”
IMPORTANT: If the controller’s output switch is off, the RESISTANCE will display the last
resistance which was calculated while the output switch was on.
4.2.6 GROUND FAULT CURRENT
Purpose: If the controller detects any leakage current in the output circuit, it will indicate the level
in milliamps.
IMPORTANT: To minimize nuisance alarms, the controller will not report a leakage current of less
than 20 mAmps.
4.2.7 VOLTAGE
Purpose: The voltage reading indicates the average circuit voltage being measured by the switch
INDUSTRIAL HEAT TRACING SOLUTIONS
EN- Raychem920series-IM-H56874 05/15
46 / 82
interface.
IMPORTANT: The controller calculates this parameter using the voltage sensed by the switch
interface module and multiplying it by the VOLTAGE TURNS RATIO to yield an adjusted voltage
value.
4.2.8 POWER
Purpose: Load power provides an indication of the average power being consumed by the
heat trace cable or the total 3-phase power being consumed by a balanced 3-phase star (“Y”)
connected load.
IMPORTANT:
• The controller calculates load power by multiplying the average adjusted voltage reading by the
average adjusted current reading.
• The controller may be set up to calculate total 3-phase power for a balanced star (“Y”)
connected load if the 3-PHASE POWER CALCULATION parameter is enabled. In this case, total
3-phase power is calculated using the following equation:
Ptotal = √3 x Iphase x Vline-line
Where Iphase = the adjusted phase current being measured, and Vline-line = the adjusted
voltage reading being measured. The VOLTAGE and CURRENT TURNS RATIOS affect both
calculations.
4.3 Maintenance Data
4.3.1 MAX / MIN TEMPERATURE VALUES
MAX CONTROL TEMP
MIN CONTROL TEMP
TS 1 MAX TEMP
TS 1 MIN TEMP
TS 2 MAX TEMP
TS 2 MIN TEMP
Purpose: This feature indicates the maximum and minimum temperatures ever recorded by the
HTC since the last time the values were reset. It may be useful to log the maximum/minimum
temperatures ever experienced on a particular trace circuit for the purposes of troubleshooting
or gathering data for future design criteria. The temperature values are written to the controller’s
nonvolatile memory once every 24 hours or whenever any maintenance data is reset by the user.
maximum/minimum temperatures are recorded for TS 1, TS 2 and the CONTROL TS.
Range: Can only be reset (cleared) by the operator.
Procedure: The maximum/minimum temperatures can be reset using the optional 920 Operator
Console (V3.11+) or a communicating device. Resetting any one of the temperatures will reset all
of them.
4.3.2 POWER ACCUMULATOR
Purpose: This feature indicates the total power consumption of the trace circuit since the last time
the POWER ACCUMULATOR was reset. It may be useful to log the amount of power consumed on a
particular trace circuit for the purposes of energy management or gathering data for future design
criteria. The value of this accumulator is written to the controller’s nonvolatile memory once every
24 hours or whenever any maintenance data is reset by the user.
Procedure: The POWER ACCUMULATOR may be reset to zero using the optional 920 Operator
Console (V3.11+) or a communicating device.
IMPORTANT: The POWER ACCUMULATOR value will roll over to zero when the upper limit of the
POWER ACCUMULATOR has been exceeded. This upper limit is 429,496,729.5 kW-hours for V3.00,
and 214,748,364.7 kW-hours for V3.11 and up.
4.3.3 CONTACTOR CYCLE COUNTER (V3.11 AND UP)
Purpose: This feature indicates the total number of off-to-on transitions a contactor has
completed since the last time the CONTACTOR CYCLE COUNTER was reset. This serves as
INDUSTRIAL HEAT TRACING SOLUTIONS
EN- Raychem920series-IM-H56874 05/15
47 / 82
a method to do preventative maintenance on the contactor according to the manufacturer’s
specifications. The count value is written to the controller’s nonvolatile memory once every 24
hours or whenever any maintenance data is reset by the user.
Procedure: The CONTACTOR CYCLE COUNTER may be reset to zero using the optional 920
Operator Console or a communicating device.
IMPORTANT:
• Once the CONTACTOR CYCLE COUNTER reaches 999,999,999 it stops counting.
• The CONTACTOR CYCLE COUNTER is only indicated if the SWITCH CONTROL MODE is set to
either DEADBAND or PROPORTIONAL AMBIENT CONTACTOR.
4.3.4 TIME IN USE
Purpose: The purpose of this feature is to indicate the total hours of controller use since its initial
operation. It may be useful to log the amount of time a controller has been in service for the
purposes of maintenance planning or reliability testing. The value of this accumulator is written
to the controller’s nonvolatile memory once every 24 hours or whenever any maintenance data is
reset by the user.
Procedure: The IN USE hours accumulator can be reset to zero using the optional 920 Operator
Console (V3.11+) or a communicating device.
IMPORTANT: The IN USE hours accumulator value will roll over to zero when the upper limit of the
accumulator has been exceeded. This limit is 4,294,967,295 hours for V3.00, and 999,999,999 hours
for V3.11 and up.
4.3.5 TIME SINCE LAST RESET
Purpose: This feature indicates the total hours of controller use since the last reset. It may be
useful to log the amount of time a particular controller has been in service since the last time the
controller’s power was cycled for troubleshooting purposes.
Procedure: The TIME SINCE LAST RESET hours accumulator can only be reset by cycling the
controller’s power.
IMPORTANT: The TIME SINCE LAST RESET will roll over to zero when the upper limit of 65,535
hours has been exceeded.
4.3.6 PEAK LOAD CURRENT (V3.11 AND UP)
IMPORTANT: The PEAK LOAD CURRENT is not displayed on the optional 920 Operator Console.
Purpose: This feature indicates the highest instantaneous load current measured since the last
time the PEAK LOAD CURRENT was reset. This value is written to the controller’s nonvolatile
memory once every 24 hours or whenever any maintenance data is reset by the user.
Procedure: The PEAK LOAD CURRENT may only be reset to zero using a communicating device.
4.3.7 PEAK GROUND-FAULT CURRENT (V3.11 AND UP)
IMPORTANT: The PEAK GROUND-FAULT CURRENT is not displayed on the optional 920 Operator
Console.
Purpose: This feature indicates the highest instantaneous ground-fault current measured since
the last time the PEAK GROUND-FAULT CUR-RENT was reset. This current value is written to the
controller’s nonvolatile memory once every 24 hours or whenever any maintenance data is reset
by the user.
Procedure: The PEAK LOAD CURRENT may only be reset to zero using a communicating device.
4.3.8 EXTERNAL INPUT STATUS (V3.11 AND UP)
IMPORTANT: The EXTERNAL INPUT STATUS is not displayed on the optional 920 Operator
Console.
Purpose: This feature indicates the actual status of the external input regardless of the controller’s
configuration. This can assist the operator who wishes to use the controller’s external input to
monitor the status of an external dry contact and pass this on to another device.
Procedure: The EXTERNAL INPUT STATUS may only be viewed using a MODBUS™-capable
software package.
INDUSTRIAL HEAT TRACING SOLUTIONS
EN- Raychem920series-IM-H56874 05/15
48 / 82
Section 5 – Control Modes
5.1 Introduction
There are several types of control modes in the controller. Some of these modes require further
explanation in order to fully understand and implement their operation.
This section describes the control modes available in the HTC and how to set their associated
parameters.
5.2 Switch Control Modes
There are four SWITCH CONTROL modes associated with the HTC. The following is an explanation
of their implementation in the controller and the differences between them.
5.2.1 PROPORTIONAL CONTROL (FOR USE WITH SSRS ONLY)
Proportional control on the HTC is implemented as follows:
When using SSRs to directly control the power applied to a trace circuit, the output may be
switched on/off very rapidly. The controller im-plements proportional temperature control on a
cycle-by-cycle basis (50 or 60 Hz power line cycle). This algorithm monitors the temperature of the
heating circuit and compares it to the CONTROL SETPOINT temperature. If the temperature of the
control sensor is at or below the CONTROL SETPOINT temperature, power is applied to the trace
with a duty cycle of 100%—the controller output is full on. If the temperature sensed by the control
sensor is equal to or greater than the CONTROL SETPOINT temperature + the PROPORTIONAL
BAND setting, the controller output will have a duty cycle of 0%—the output will be off. The
temperature of the control sensor is constantly monitored and the output duty cycle is adjusted
proportionally according to where the temperature falls within the 0%–100% band.
Proportional Control Temperature Band
Control Sensor Temperature Duty Cycle
Setpoint + proportional band 0%
Setpoint + proportional band/2 50%
Setpoint 100%
5.2.2 DEADBAND CONTROL (FOR USE WITH EXTERNAL CONTACTORS)
Deadband control on the HTC is implemented as follows:
When using the HTC in an application where the controller is used to open and close a contactor,
proportional control cannot be used. In these cases a deadband control algorithm is used. The
output duty cycle is not controlled; instead, the output is either fully on or completely off. The user
can set the DEADBAND value. The controller monitors the temperature of the trace circuit and
compares it to the CONTROL SETPOINT temperature as in the proportional control. If the control
sensor temperature is above the CONTROL SETPOINT temperature by more than the DEADBAND
value, the output is turned off. If the control sensor temperature falls below the CONTROL
SETPOINT temperature the output is turned on. This is a simple control algorithm but it works
very effectively in heat trace applications where the temperature of a traced system changes
relatively slowly.
Deadband Control Temperature Band
Control Sensor Temperature Output State
Setpoint + deadband Off
SetpointOn
When the control sensor temperature is within the deadband, the output does not change its
state. Also, when using deadband control a contactor is not allowed to toggle faster than every two
seconds. If an AC alarm with an alarm filter time greater than 0 is detected, the contactor will not
toggle until the alarm filter time has expired.
INDUSTRIAL HEAT TRACING SOLUTIONS
EN- Raychem920series-IM-H56874 05/15
49 / 82
5.2.3 PROPORTIONAL AMBIENT SSR CONTROL (FOR USE WITH SSRS ONLY)
When an HTC using an SSR is used to control the output using the ambient temperature, this
control mode should be used.
Proportional ambient SSR control on the HTC is implemented as follows:
• When using SSRs to directly control the power applied to a heating circuit, the output may be
switched on/off very rapidly. The controller implements proportional temperature control on a
cycle-by-cycle basis (50 or 60 Hz power line cycle).
• This algorithm monitors ambient temperature and compares it to the CONTROL SETPOINT
temperature. If the temperature of the control sensor is at or below the CONTROL SETPOINT
temperature minus the PROPORTIONAL BAND setting, power is applied to the trace with a duty
cycle of 100%—the controller output is fully on.
• If the temperature sensed by the control sensor is equal to or greater than the CONTROL
SETPOINT temperature, the output will have a duty cycle of 0%—the controller output will be
off.
• The temperature of the control sensor is constantly monitored and the output duty cycle is
adjusted proportionally according to where the temperature falls within the 0%–100% band.
Proportional Ambient SSR Control Temperature Band
Control Sensor Temperature Duty Cycle
Setpoint 0%
Setpoint - proportional band/2 50%
Setpoint - proportional band 100%
IMPORTANT: The load shedding fail-safe mode is not supported when using proportional ambient
SSR control, since ambient temperature is being monitored rather than pipe temperature.\
5.2.4 PROPORTIONAL AMBIENT CONTACTOR CONTROL
(FOR USE WITH EXTERNAL CONTACTORS)
When an HTC using a contactor is used to control the output based on the ambient temperature
this control mode should be used.
Proportional ambient contactor control on the HTC is implemented as follows:
• The output may not be switched on/off rapidly when using a contactor, so proportional
temperature control is implemented by applying the required duty cycle over the selected
CYCLE TIME.
• The output is fully on for a portion of the CYCLE TIME as determined by the calculated duty
cycle, and it will be completely off for the re-mainder of the CYCLE TIME.
• The duty cycle is calculated each time the output toggles, based on the ambient temperature,
PROPORTIONAL BAND setting, and the CON-TROL SETPOINT temperature setting.
• The controller monitors the ambient temperature and compares it to the CONTROL SETPOINT
temperature as in proportional ambient SSR control. If the temperature of the control sensor
is at or below the CONTROL SETPOINT temperature minus the PROPORTIONAL BAND setting,
power is applied to the trace with a duty cycle of 100%. The controller output will be fully on for
1/30th of the CYCLE TIME setting before the duty cycle is calculated again.
• If the temperature sensed by the control sensor is equal to or greater than the CONTROL
SETPOINT temperature, the output will have a duty cycle of 0%. The controller output will be off
for 1/30th of the CYCLE TIME setting before the duty cycle is calculated again.
Proportional Ambient Contactor Control Temperature Band
Control Sensor Temperature Duty Cycle
Setpoint 0%
Setpoint - proportional band/2 50%
Setpoint - proportional band 100%
IMPORTANT: The load shedding fail-safe mode is not supported when using proportional ambient
contactor control, since ambient temperature is being monitored rather than pipe temperature.
If an AC alarm with an alarm filter time greater than 0 is detected, the contactor will not toggle
until the alarm filter time has expired.
INDUSTRIAL HEAT TRACING SOLUTIONS
EN- Raychem920series-IM-H56874 05/15
50 / 82
5.3 Load Shedding Control Mode
Load shedding is a control mode that can be programmed and initiated only by an external
communicating device, or by the Model 780/GCC-9000 Group Communications Controller, which
overrides temperature control and forces the output of the controller OFF until reset by the 780/
GCC. When using a GCC, load shedding is initiated by a contact closure (or opening) on one of
the four contact inputs. Each contact input initiates a load shedding command for the group of
controllers associated with that contact input. Each controller may be associated with one or more
groups. Refer to the Load Shedding Section in the GCC manual for details on setting up the load
shedding features of the HTC when using a GCC.
When power is applied to the controller, it determines if load shedding mode has been enabled.
If enabled, the controller immediately enters load shedding operation (holding its output off)
and waits to see if the GCC or an external communicating device has initiated a load shedding
command. If no command is present the controller resumes normal operation. If a load shedding
command is present, the controller will continue to hold the output OFF, until one of three
conditions occurs:
1. The GCC contact input or zone definition bits of an external communicating device which
initiated load shedding clears and the command to terminate load shedding mode is issued.
2. Communications are interrupted between the controller and its communicating device, as in
the case of a damaged communications wire. Approximately 30 seconds after communications
ceases the controller will return to normal operation.
3. Communications between the controllers and the external communicating device goes off-line
for approximately two minutes, as occurs when the 760 Hand Held Programmer is used to
communicate with the controller.
IMPORTANT: The controller will return to normal operation if communications between the 780
or external communicating device and the controller are disrupted in any way. This will return
temperature control to the HTC. Also, the HTC does not perform a periodic autocycle test while
operating in load shed mode. When using a GCC, it must be configured for load shedding operation
before the controller can be set up for load shedding control.
Three parameters must be set in the controller to configure it for load shedding operation:
1. The load shedding feature must be enabled.
2. The FAIL SAFE MODE parameter must be enabled or disabled depending on the application
requirements. If FAIL SAFE MODE is enabled, then at least one LOW TS ALARM (of a TS used
in the TS CONTROL MODE) must be enabled. If the alarm temperature exceeds the CONTROL
SETPOINT temperature, fail-safe mode will be disabled.
3. The GCC contact input(s) or zone definition bits of an external communicating device that are to
be associated with the load shedding action for the controller must be defined.
These parameters can only be configured using an external communicating device or the
Model 780/GCC-9000 Group Communications Con-troller. Refer to the Model 780/GCC-9000
user manual for details on how to set up these options. The optional 920 Operator Console can
be used to enable or disable the load shedding feature, but not to set any other load-shedding
parameters.
IMPORTANT:
• Fail-safe mode is always disabled if the SWITCH CONTROL MODE is set to either of the two
proportional ambient control modes, or the TS CONTROL MODE = EXT INPUT, FAIL OFF/ON
• Fail-safe mode is disabled if the TS CONTROL MODE is set to either EXT INPUT, FAIL TS 1 or
EXT INPUT, FAIL TS 2 and a control temperature failure occurs.
• The HTC will turn on its output switch when the control temperature becomes less than the
highest LOW TS ALARM temperature if the fol-lowing conditions are met:
– Fail-safe mode is enabled
– Load shedding is active
– The TS CONTROL MODE uses both TS 1 and TS 2
– Both TS 1 and TS 2 have their LOW TS ALARMS enabled
• A FORCE ON override signal has higher priority than a load shedding signal. An INHIBIT signal
has higher priority than fail safe mode.
INDUSTRIAL HEAT TRACING SOLUTIONS
EN- Raychem920series-IM-H56874 05/15
51 / 82
5.4 TEMPBUS™ Control Mode
TEMPBUS™ is short for Temperature Bus. This refers to a connection that allows one “master”
HTC to share its control temperature with a number of “slave” HTCs. Up to 25 “slave” HTCs can be
connected to this bus. Refer to the wiring diagrams in Appendix C for example con-nection details.
5.4.1 TEMPBUS™ MASTER
Only Point A of a 920 HTC can be configured as a TEMPBUS™ “master.” A TS CONTROL MODE
using either TS 1 and/or TS 2 should be selected and the EXTERNAL OUTPUT should be set to
TEMPBUS™. This will cause the measured control temperature of Point A to be sent out the
EX-TERNAL OUTPUT port.
IMPORTANT:
• If a TEMPBUS™ “master” has its temperature control overridden by an INHIBIT override or a
FORCE ON override signal, it will pass this override signal over the TEMPBUS™ to its “slaves.”
• Load shedding, fail-safe, or auto-cycling conditions are not passed over the TEMPBUS™ from a
“master” to its “slaves.”
5.4.2 TEMPBUS™ SLAVE
Both Point A and/or Point B of a 920 HTC can be configured as a TEMPBUS™ “slave.” The
EXTERNAL INPUT should be set to TEMPBUS™, then the point’s TS CONTROL MODE must be set
to a mode using the EXTERNAL INPUT. The “slave” controller will perform its own temperature
con-trol using the control temperature of the “master.”
If a TEMPBUS™ “slave” does not receive a control temperature from a TEMPBUS™ “master” at
least once every 15 seconds, then a CONTROL TS FAILURE ALARM will occur. This alarm is nonlatching for TEMPBUS™ “slaves” and will be cleared automatically once a control temperature is
received again. Point B can be a “slave” to Point A of the same controller.
IMPORTANT: Other features that require the use of the EXTERNAL INPUT (INHIBIT or OVERRIDE)
may not be used at the same time as the TEMPBUS “slave” feature.
INDUSTRIAL HEAT TRACING SOLUTIONS
EN- Raychem920series-IM-H56874 05/15
52 / 82
Section 6 – Troubleshooting
6.1 Operator Checks
Upon receipt of the controller, or to check the controller for an indication of normal operation,
follow the operational procedures shown below. These procedures are designed to familiarize the
operator with the controller and to provide an understanding of its operation.
To determine if a fault is associated with the heat tracing, wiring or the controller, it is necessary to
troubleshoot the wiring and tracer circuit. If the fault remains, remove power from the controller
and exchange it with another controller. This may require some reprogramming of the new HTC.
If the fault clears, exchange the controller on another circuit to determine if the fault moves
with the controller. If the fault moves with the controller, verify that the HTC has been configured
correctly for the application. If the configuration is correct, return the controller to Pentair
Thermal Managament for evaluation.
IMPORTANT: If the controller does not operate properly and is being returned to Pentair
Thermal Managament for service, information must be provided as to why the unit was removed
from service. Contact the Pentair Thermal Managament customer service department for an
authorization form and number prior to returning any units for repair.
6.1.1 GETTING STARTED
To access the functions of the 920 Series HTC, use the optional 920 Operator Console. If the
modem communications option is installed in the 920 control module, the Model 780/GCC-9000
Group Communications Controller may also be used to access controller parameters. Refer to the
operating manual for the particular device that you are using for operational details.
6.2 Common Problem Areas
The HTC can be used as an effective troubleshooting tool to pinpoint problem areas of heat trace
circuits. Described below are a few of the more common problem areas, their symptoms, and
parameters to check to determine the actual faulty portion of the heat trace circuit.
6.2.1 CONTROL POINT A VERSUS CONTROL POINT B
Remember that the 920 series controller is a two-point device!
One of the most common errors is to confuse settings, displays, or alarms for one control point
with the second control point. When pro-gramming or troubleshooting, always confirm that you
are referencing the control point of interest—either Point A or Point B.
6.2.2 RTDS
RTD failures after installation can generally be attributed to incorrect wiring or improper
installation of the sensor. Some specific RTD problems and troubleshooting methods follow.
1. TS Failure Alarm(s)
If the HTC controller indicates a failure of an RTD:
• Ensure that the RTD is a 3-wire 100 Ω Platinum Type (for V3.00). For V3.11 and up ensure that
the TS TYPE setting matches the RTD being used.
• Turn off the power to the controller before proceeding!
• Disconnect the RTD wiring from the input terminals.
• Measure the RTD’s resistance between the source (WHT) and sense (WHT) leads at the
controller. It should not exceed 40 Ω. Excessive lead resistance will cause a TS FAILURE ALARM
and must be corrected. Look for loose terminals, excessive lead length, or insufficient wire
gauge and correct as necessary.
• Measure the RTD’s resistance between the source (WHT) or sense (WHT) lead and the common
(RED) lead of the RTD at the controller. This should be between 60 Ω and 330 Ω depending on
the temperature and the lead resistance. See Appendix D on page 74 or Appendix E on page 75.
INDUSTRIAL HEAT TRACING SOLUTIONS
EN- Raychem920series-IM-H56874 05/15
53 / 82
• Verify that the RTD is wired correctly. The heat-tracing controllers will always be terminated in
the order: source (WHT), sense (WHT), common (RED). When using the terminal board, these
terminals are marked as follows:
Terminal No. Description
25 Point A, Shield
26 Point A, TS 1 Source (WHT)
27 Point A, TS 1 Sense (WHT)
28 Point A, TS 1 Common (RED)
9
Point A, Shield
10 Point A, TS 2 Source (WHT)
11 Point A, TS 2 Sense (WHT)
12 Point A, TS 2 Common (RED)
29 Point B, Shield
30 Point B, TS 1 Source (WHT)
31 Point B, TS 1 Sense (WHT)
32 Point B, TS 1 Common (RED)
13 Point B, Shield
14 Point B, TS 2 Source (WHT)
15 Point B, TS 2 Sense (WHT)
16 Point B, TS 2 Common (RED)
The RTD manufacturer will typically color code the leads with the source and sense being the
same color, and the common a different color. Ensure that the RTD extension wire shield is
terminated at one end only, normally using the terminal block provided at the terminal board.
IMPORTANT: Some RTDs may have the Sense wire color coded as Black.
2. Questionable Temperature
If you feel that the indicated or displayed temperature is not correct, the controller and the RTD
can be quickly checked for correct operation.
To verify the RTD:
Turn off the power to the controller before proceeding!
• Disconnect the RTD wiring from the input terminals.
• To calculate the temperature indicated by the RTD, measure the resistance from source
(white wire) or sense (white wire) to common (red wire) and subtract the resistance measured
between source and sense. This will give a compensated resistance value that can be crossreferenced to the RTD table, DIN Standard 43760 found in Appendix D on page 74 or Appendix
E on page 75. Compare the meas-ured resistance and cross-referenced temperature value
obtained from the RTD table to the indicated or displayed value. These should agree to within
the accuracy standards of the HTC and the RTD.
To verify the Controller:
Turn off the power to the controller before proceeding!
• Disconnect the RTD wiring from the input terminals.
• Connect a 100 Ω resistor across the source or sense terminal and common. Insert a jumper
between the source and sense terminals.
• Apply power to the controller. The indicated or displayed temperature should be about 0°C
(32°F) depending on the actual resistance of the test resistor if TS TYPE is set to 100 Ω
Platinum.
3. Unstable or Bouncing Temperature
An erratic indication of temperature can be caused by several factors external to the controller;
however, a bouncing temperature of a few degrees should not be confused with incorrect
operation. The controller’s accuracy and resolution will result in an indicated temperature
change of a couple of degrees if the measured resistance temperature falls between two
discrete values. This is sometimes referred to as quantization error.
INDUSTRIAL HEAT TRACING SOLUTIONS
EN- Raychem920series-IM-H56874 05/15
54 / 82
If the bounce or instability is excessive, check:
• Wire used for extension of the RTD should be three-wire, twisted and shielded with the shield
grounded at the controller only. Each of the three lead wires must be of the same gauge.
• The ideal installation has a separate conduit for the RTD leads (if they have been extended). It
is not usually a problem to run low signal levels in the same conduit as the power leads even in
high-power applications, as long as the RTD wire is a twisted, shielded type with an insulation
rating equal to or greater than the highest voltage in the conduit. Follow the proper Electrical
Code for your particular in-stallation.
• Terminal connections that are not tight can add resistance to an RTD circuit. Check the
tightness of all screw terminal connections at time of installation and during subsequent
maintenance checks.
• Check the specifications for the particular cable being used to ensure that it does not have
excessive capacitance when used in long lengths. This can cause a temperature offset between
what the controller reads and what the RTD actually measures. This again is normally not a
problem since the controller compensates for all but the worst cases of this.
• Lastly, it is possible for the RTD itself to fail on an intermittent basis but this failure mode
should be considered unusual. This kind of failure is probably the most difficult to find but
fortunately it is also the least likely as a failure mechanism.
6.2.3 GROUND FAULT
Ground-fault alarms can be due to incorrect installation as well as leakage resulting from wet
system components or faulted cables.
The 920 series switch interface detects ground faults by summing the outgoing and return trace
currents through an internal current trans-former. Under normal operating conditions (no ground
fault condition) this current will be zero. When there is a flow of current from one of the trace
supply wires to ground, a ground-fault condition occurs.
If a ground-fault alarm is present on start-up of a new installation, it is likely due to a wiring error
or damaged cable. To verify this condition:
• Check that the heating circuit neutrals return to the controller and are not connected directly to
the distribution panel. This can be a common problem if the installation is a retrofit situation.
• On paralleled circuits, be certain that ALL neutrals return. The late addition of a circuit may not
be obvious.
Use the monitoring feature available at the 920 Operator Console or the Model 780/GCC-9000
Group Communications Controller to view the measured ground-fault current at the heattrace controller. If this value is at the maximum that the controller can measure, it is usually an
indication that the wiring is incorrect. If the value is less than 250 mAmps, an actual ground-fault
condition may exist in the cable.
IMPORTANT: The controller monitors the integrity of the ground-fault (GF) detection transformer
and associated wiring. If a fault is detected, the controller will report a GF value of 300 mAmps.
INDUSTRIAL HEAT TRACING SOLUTIONS
EN- Raychem920series-IM-H56874 05/15
55 / 82
6.3 Common Alarms—What to look for Alarm
Description
Cause of Alarm
High TS 1/TS 2
Temperature
Appears when the temperature exceeds the
HIGH TS ALARM
• Alarm temperature setting too close to maintain
temperature
• Flow of hot product
• Steaming out lines
• Incorrect tracer wiring
• Incorrect RTD TYPE selected
Low TS 1/TS 2
Temperature
Appears when the temperature decreases
below the LOW TS ALARM temperature.
• Alarm temperature setting too close to maintain
temperature
• Flow of cold product
• Empty pipe
• Damaged, wet, or missing insulation
• Heating cable not sized properly for the application
• Heating cable damaged
• Incorrect RTD TYPE selected
TS 1/TS 2 Failure
Indicates that a sensor is operating
improperly.
• Incorrect or damaged field wiring—open leads or excess
resistance, either intermittent or continuous, may be
due to broken or damaged wires or loose terminals
• Damaged or inoperative temperature sensors
Control TS Failure
High Current
Alarms a failure of the temperature-sensing
element designated as the control element by
the TS CONTROL MODE setting. Depending
on the chosen TS FAIL MODE and TS
CONTROL MODE, the output switch may be
latched off or on until this failure is corrected.
• Incorrect or damaged field wiring—open leads or
excess resistance, either intermittent or continuous,
may be due to broken or damaged wires or loose
terminals
Alarms current levels that are greater than
the HIGH CURRENT ALARM setting for the
application.
• Alarm setting too close to normal operating
• Damaged or inoperative temperature sensors
• High in-rush current from cold start of
self-regulating cable
• Damaged or partially shorted heating cable
• “As built” cable length is greater than design value
• Incorrect CURRENT TURNS RATIO setting
Low Current
Alarms current levels that are less than the
LOW CURRENT ALARM setting
• Alarm setting too close to normal operating current
• Low source voltage
• Damaged or inoperative heating cable
• Open connection—wiring problem, SSR or contactor
failed open
• Incorrect CURRENT TURNS RATIO setting
High GFI
Alarms ground-fault current levels that are
greater than the HIGH GFI ALARM setting
• Alarm setting too close to normal leakage current
• Damaged cable insulation and/or moisture present
• Moisture in junction box
• Poor splice or termination
• Moisture provides conductive ground path that allows
ground-fault current
GFI Trip
This value sets the upper limit of allowable
ground-fault leakage. Exceeding this link
results in the output switch being latched off
and the alarm activated to indicate a groundfault condition.
• Trip setting too normal leakage current
• Damaged cable insulation and/or moisture present
• Moisture in junction box
• Poor splice or termination
• Moisture provides conductive ground path that allows
ground-fault current
INDUSTRIAL HEAT TRACING SOLUTIONS
EN- Raychem920series-IM-H56874 05/15
56 / 82
6.3 Common Alarms—What to look for (Continued)
Alarm
Description
Cause of Alarm
High Voltage
Alarms voltage levels that are greater than
the HIGH VOLTAGE ALARM setting
• Alarm setting too close to normal operating voltage
• Incorrect wiring
• Incorrect VOLTAGE TURNS RATIO
• Power surge
Low Voltage
This alarms voltage levels which are less
than the LOW VOLTAGE ALARM setting.
• Alarm setting too close to normal operating voltage
• Damaged power cable
• Incorrect VOLTAGE TURNS RATIO
• Brown-out conditions
• Loss of power to the circuit
Overcurrent Trip
If the controller is unable to start the cable
due to high current or after attempting to
soft start it, the controller trips off its output
switch.
• Excessive in-rush current
• Incorrect wiring
• Damaged cable
• Switch rating set too low
• Incorrect CURRENT TURNS RATIO setting
Switch Failure
HTC Reset
This alarm will indicate that the controller
senses current flow when the output switch
should be off.
• Some other device has energized the heat trace cable
This alarm is latched when power is restored
after an interruption. Used to identify
intermittent power losses.
• Circuit breaker tripped
• Output switch has failed
• Power line transient
Power Limiting
This alarm indicates that the solid-state
• Power applied to trace circuit is being limited to the
relay is limiting the average amount of power
MAXIMUM POWER setting
that is applied to the trace circuit as defined
• Incorrect VOLTAGE and/or CURRENT TURNS RATIO
by the MAXIMUM POWER setting.
setting
C B Limiting
This alarm indicates that the controller is
limiting the average current to the CIRCUIT
BREAKER CURRENT RATING setting.
• Excessive current caused by in-rush current
This alarm indicates that the controller is
limiting the average current that is applied
to the trace circuit based on the SWITCH
RATING setting to protect the solid-state
relay from excess current.
• Excessive current caused by in-rush current
This alarm indicates that the heating cable
resistance has deviated from the NOMINAL
RESISTANCE setting by more than the HIGH
RESISTANCE ALARM setting.
• Alarm setting too close to actual operating resistance
• C.B. CURRENT RATING setting too low for normal
heater current draw or not matched to actual circuit
breaker size
• Incorrect CURRENT TURNS RATIO setting
Switch Limiting
High Resistance
• Incorrect CURRENT TURNS RATIO setting
• NOMINAL RESISTANCE not set properly
• Open connection—wiring problem
• Damaged cable
• Incorrect VOLTAGE and/or CURRENT TURNS RATIO
setting
Low Resistance
This alarm indicates that the heating cable
resistance has deviated from the NOMINAL
RESISTANCE setting by more than the LOW
RESISTANCE ALARM setting.
• Alarm setting too close to actual operating resistance
• NOMINAL RESISTANCE not set properly
• Partial short—wiring problem
• Damaged cable
• Incorrect VOLTAGE and/or CURRENT TURNS RATIO
setting
INDUSTRIAL HEAT TRACING SOLUTIONS
EN- Raychem920series-IM-H56874 05/15
57 / 82
6.3 Common Alarms—What to look for (Continued)
Alarm
Description
Cause of Alarm
EEROM Data Failure
This alarm indicates that the controller
has detected a failure in its nonvolatile
memory (this is where all of the controller’s
configuration and calibration settings are
stored). This indicates an internal problem
and the HTC should be replaced and
returned to Pentair Thermal Managament
for repair.
• The HTC cannot bypass the failed area of its memory
and has loaded factory defaults into this failed area.
Contactor Count
(V3.11 and up)
This alarm indicates that the number of offto-on transitions of a contactor has exceeded
the CONTACTOR COUNT ALARM setting and
needs to be replaced.
• Contactor may be worn.
INDUSTRIAL HEAT TRACING SOLUTIONS
• Some configuration parameter (i.e. DEADBAND, AUTO
CYCLE INTERVAL, load shedding etc.) is causing the
contactor to toggle more than usual.
EN- Raychem920series-IM-H56874 05/15
58 / 82
Section 7 – Maintenance
7.1 Operator Maintenance
The 920 series controller is designed to be a maintenance-free product. Once installed properly,
the only maintenance required is retightening of the terminal connections approximately one week
after installation and inspection periodically thereafter. Also, alarm pilot lamps (if installed) and
contactors may need periodic replacement.
CAUTION:
Make sure that the power to the controller is OFF when replacing the pilot lamps! Also, be certain
power to the controller is OFF before attempting to test or service the heat tracing. Do not rely on
the controller as a disconnect device!
7.2 Replaceable Parts
There are no user-serviceable parts in the 920 series controller or accessories, except lamps in
optional alarm pilot lights. The unit is designed to be modular and easily changed out in the field.
Modules appearing inoperative should be returned to the nearest Pentair Thermal Managament
Service Center for service.
WARNING:
Tampering with the 920 components without approval from Pentair Thermal Managament could
result in the product’s warranty being void.
INDUSTRIAL HEAT TRACING SOLUTIONS
EN- Raychem920series-IM-H56874 05/15
59 / 82
Appendix A Specifications
Specifications are @ 25°C unless otherwise noted and are subject to change without notice.
System Ratings
Storage ambient –40°F to 185°F (–40°C to 85°C)
Approvals CSA C/US, c-ETL-us
IMPORTANT: Approval Agency mark will vary based on panel manufacturing facility
Classification • Cl I, Div 2, Grp A,B,C,D and Ex nA IIA, IIB, IIC (Zone 2)
• SSR Version T-code: T4 (T3A with optional pilot light)
• Ordinary locations (SSR and contactor versions)
920 Series Wiring Terminal Ratings
Terminal board 28-12 AWG, strip length: 0.22"
Switch interface 28-14 AWG, strip length: 0.33"
Power terminals 30 A: 22-8 AWG, strip length: 0.47", torque: 16.0 lb-in
60 A: 14-6 AWG, strip length: 0.47", torque: 26.5 lb-in
920 Series Control Module (per control point)
Operating temperature –40°F to 140°F (–40°C to 60°C)
Power requirement 9 Vdc nominal, 600 ma maximum
Control modes Proportional, deadband, proportional ambient (SSR), proportional ambient (contactor) modes, adjustable
2°F to 90°F (1°C to 50°C) above setpoint
Temperature inputs (2) RTD inputs: 3-wire 100 Ω Platinum (DIN 43760, Ω=0.00385 Ω/Ω/°C) or 2/3-wire 100 Ω Ni-Fe, open/
shorted sensor detection/protection, lead resistance compensated 0 to 20Ω per lead.
Temperature measurement range –76°F to 1058°F (–60°C to 570°C), accuracy: ± 0.5% of span ± 1LSD
Voltage measurement range 50 to 295 Vac (with voltage turns ratio @ 1:1), accuracy: ± 1% of span ± 2LSD, repeatability:
± 1.5% of span
Current measurement range 0.3 to 100 A (with current turns ratio @ 1:1), resolution: 0.1 A (0.3 to 11 A range), 0.3 A (11 to 40 A range), 0.7 A (40 to 100 A range), accuracy: ± 2.5% of reading ± resolution, repeatability: ± 3% of reading ± resolution
GF current measurement range 20 to 250 ma, accuracy: ± 2.5% of span ± 2 LSD at nominal load, repeatability: ± 4% of span
Alarm relay output Dry contact, 48 Vac/dc, 500 ma, 10 VA switching maximum
920 Series SSR Switch Interface Module
Operating temperature –40°F to 140°F (–40°C to 60°C)
Power requirements 100 to 277 Vac nominal, 1 PH, 60 Hz ±3 Hz or 50 Hz ±2 Hz, 100 ma. maximum
Output power +9 Vdc nominal, 650 ma maximum
SSR drive +9 Vdc nominal, 75 ma maximum
Current sense range 1000:1, 0.3 to 60 A, 50/60 Hz, 1 PH
GF current sense range 1000:1, 20 to 250 ma, 50/60 Hz, 1 or 3 PH
Wiring terminals 28-14 AWG, strip length: 0.33"
INDUSTRIAL HEAT TRACING SOLUTIONS
EN- Raychem920series-IM-H56874 05/15
60 / 82
920 Series SSR Output Modules
Operating Temperature –40°F to 104°F (–40°C to 40°C)
Switch Rating • 30 A resistive continuous @ 277Vac max. standard, 600 Vac max. optional, 1 PH, 50/60 Hz, 80 A 1 sec. in-rush, 625 A 1cycle in-rush
• 60 A resistive continuous @ 600 Vac max., 1 PH, 50/60 Hz, 120 A 1 sec. in-rush, 1000 A 1 cycle in-rush
Input Drive Requirement 4-32 Vdc, 1500 Ω nominal input resistance
Environment Type 4X / IP66
920 Series Contactor Ratings
Operating Temperature –40°F to 104°F (–40°C to 40°C)
Contact Rating 30 A resistive continuous @ 600 Vac max. standard,
60 A maximum opt., 50/60Hz, 3 pole Coil Rating 120 or 208/240 or 277 Vac, 50/60 Hz, 109 VA in-rush,
10 VA sealed
920 Series Operator Console
Operating Temperature –40°F to 104°F (–40°C to 60°C)
Power Requirement +9 Vdc nominal, 500 ma maximum
INDUSTRIAL HEAT TRACING SOLUTIONS
EN- Raychem920series-IM-H56874 05/15
61 / 82
Appendix B Typical Enclosure Dimensions
The following drawings provide the user with enclosure size and mounting dimensions for
the stock enclosure assemblies. Please contact your local Pentair Thermal Managament
representative for information regarding other available sizes and configurations.
B.1 Single-Point Assemblies #10160-003 and #10160-009
1 Point FRP
1- or 2-pole 30 A SSR assembly
1 Pole Model: 920*E2FWL*SIS301*SS3101
2 Pole Model: 920*E2FWL*SIS301*SS3201
6.25
33.68
10.50
12.50
13.08
7.95
Mounting holes 0.3" diameter,
4 places
A
B
1
2
3
4
6
7
INDUSTRIAL HEAT TRACING SOLUTIONS
EN- Raychem920series-IM-H56874 05/15
62 / 82
B.2 Dual-Point Assemblies #10160-120 and #10160-121
2 Point FRP
1- or 2-pole 30 A SSR assembly
1 Pole Model: 920*E4FWL*SIS302*SS3102
2 Pole Model: 920*E4FWL*SIS302*SS3202
8.31
18.00
12.55
14.55
14.94
10.00
Mounting holes 0.3" diameter,
4 places
1
2
3
4
6
7
1
2
3
4
6
7
INDUSTRIAL HEAT TRACING SOLUTIONS
EN- Raychem920series-IM-H56874 05/15
63 / 82
B.3 Four-Point Assembly #10160-125
4 Point FRP
1-pole 30 A SSR assembly
Model: 920*E6FWL*SIS304*SS3104
8.31
17.27
16.55
17.13
12.00
INDUSTRIAL HEAT TRACING SOLUTIONS
EN- Raychem920series-IM-H56874 05/15
Mounting holes 0.3" diameter,
4 places
64 / 82
B.4 Eight-Point Assembly #10160-035
8-Point FRP
1-pole 30 A SSR assembly
Model: 920*E10FWQ1*SIS308*SS3108
30.11
12.95
24.11
30.51
31.32
21.86
INDUSTRIAL HEAT TRACING SOLUTIONS
EN- Raychem920series-IM-H56874 05/15
Mounting holes 0.375" diameter,
4 places
65 / 82
B.5 Twenty-Point Assembly #10160-045
20-Point FRP
1-pole 30 A SSR assembly
Model: 920*E14FWQ1*SIS320*SS3120
38.48
12.95
32.48
40.35
41.17
30.24
INDUSTRIAL HEAT TRACING SOLUTIONS
EN- Raychem920series-IM-H56874 05/15
Mounting holes
0.375" diameter,
4 places
66 / 82
Appendix C Wiring Diagrams
The following drawings provide sample wiring diagrams for the 920 Series control products and
optional accessories. Please contact your local Pentair Thermal Managament representative for
information regarding other available options
C.1 TS Wiring
C.1.1 100 Ω PLATINUM RTD WIRING
Terminal board
Control
Point A
RTD 1
Control
Point A
RTD 2
Shield
Source
Sense
25
26
27
Drain
Wht
Wht
Common
28
Red
Shield
Source
Sense
9
10
11
Drain
Wht
Wht
Common
12
Red
Shield
Source
Sense
29
30
31
Drain
Wht
Wht
Common
32
Red
Shield
Source
Sense
13
14
15
Drain
Wht
Wht
Common
16
Red
100Ω
Pt RTD
100Ω
Pt RTD
Control Point A
TS1 and TS2 Wiring Diagram
Terminal board
Control
Point B
RTD 1
Control
Point B
RTD 2
100Ω
Pt RTD
100Ω
Pt RTD
Control Point B
TS1 and TS2 Wiring Diagram
IMPORTANT: Temperature sensor manufacturers may use different lead wire colors than those
shown in the diagram above. Some common color combinations are shown in the table below, but
others may also be available. See sections 3.7.1 on page 32 and 6.2.2 on page 55 for additional
details.
Signal Description
Color Scheme #1
Lead Wire
Color Scheme #2
Source
White
White
Red
Sense
White
Black
Red
INDUSTRIAL HEAT TRACING SOLUTIONS
Lead Wire
EN- Raychem920series-IM-H56874 05/15
IEC 751
Color Scheme #3
67 / 82
Common
Red
Red
White
C.1.2 100Ω NICKEL IRON RTD WIRING
Terminal board
Control Point A
RTD 1
Shield
25
Drain
Source
26
Jumper
Sense
27
100 Ω
Ni-Fe RTD
Common 28
Control Point A
RTD 2
Shield
9
Source
10
Sense
11
Drain
Jumper
100 Ω
Ni-Fe RTD
Common 12
Terminal board
Control Point B
RTD 1
Shield
29
Drain
Source
30
Jumper
Sense
31
100 Ω
Ni-Fe RTD
Common 32
Control Point B
RTD 2
Shield
13
Source
14
Sense
15
Drain
Jumper
Common 16
100 Ω
Ni-Fe RTD
Control Point B
TS1 and TS2 wiring diagram
INDUSTRIAL HEAT TRACING SOLUTIONS
EN- Raychem920series-IM-H56874 05/15
68 / 82
C.2 Power Wiring
C.2.1 CONTROLLER POWERED DIRECTLY FROM 1 PH OR 3-WIRE 3 PH SOURCE
Trace power in (L1/line)
Control power in (L1/line)
Trace power in (L2/neutral)
Control power in (L2/neutral)
Trace power in (L3)
Trace power out (L1/line)
Trace power out (L2/neutral)
Trace power out (L3)
J1
J2
1
2
3
4
5
6
7
8
L1/line
L2/neutral
1PH or 3-wire 3PH
Input power
(Max. 277 Vac line-line)
L3
L1/line
L2/neutral
L3
Tracer(s)
Notes:
1. Jumpers J1 and J2 are normally supplied by the Factory
2. Terminals 5 and 8 are only supplied when 3 phase versions are
ordered from the Factory
C.2.2 CONTROLLER POWERED DIRECTLY FROM 4-WIRE 3 PH SOURCE
Trace power in (L1/line)
Control power in (L1/line)
Trace power in (L2/neutral)
Control power in (L2/neutral)
Trace power in (L3)
Trace power out (L1/line)
Trace power out (L2/neutral)
Trace power out (L3)
J1
1
2
3
L1
4
5
6
Neutral
7
L2
L3
8
L2
4 wire 3PH
Input power
(Max. 277 Vac line-neutral)
L3
L1
Tracer(s)
Notes:
1. Jumpers J1 and J2 are normally supplied by the Factory
2. Terminals 5 and 8 are only supplied when 3 phase versions are
ordered from the Factory
3. Remove jumper J2
C.2.3 CONTROLLER POWERED FROM A SEPARATE CIRCUIT
1PH
120–277 Vac
Control power input
Trace power in (L1/line)
Control power in (L1/line)
Trace power in (L2/neutral)
Control power in (L2/neutral)
Trace power in (L3)
Trace power out (L1/line)
Trace power out (L2/neutral)
Trace power out (L3)
1
2
3
4
L1/line
L1/line
L2/neutral
L2/neutral
5
6
7
8
L3
L1/line
L2/neutral
L3
1PH or 3PH
Trace power input
Tracer(s)
Notes:
1. Jumpers J1 and J2 are normally supplied by the Factory
2. Terminals 5 and 8 are only supplied when 3 phase versions are
ordered from the Factory
3. Remove jumpers J1 and J2
INDUSTRIAL HEAT TRACING SOLUTIONS
EN- Raychem920series-IM-H56874 05/15
69 / 82
C.3 Communication Wiring C.3 Communication Wiring
C.3.1 2-WIRE MODEM OPTION
Terminal board
Comm
Comm
1
2
6
7
Comm
3
8
Comm
4
22
Comm
5
23
Ground
Modem
Modem
Drain
24
C.3.2 2-WIRE RS-485 OPTION
Terminal board
Comm
Comm
1
2
6
7
Comm
3
8
Comm
4
22
Comm
5
23
Ground
RXD/TXD +
RXD/TXD –
Drain
24
C.3.3 RS-232 OPTION
Terminal board
Comm
1
6
Comm
2
7
Comm
3
8
Comm
4
22
Comm
5
23
Ground
24
RXD
DCD
CTS
TXD
RTS
Common
C.4 Alarm Output Wiring
C.4.1 USED AS A DRY CONTACT
Terminal board
+9Vdc Nom
Alarm
Relay
Common
INDUSTRIAL HEAT TRACING SOLUTIONS
1
17
Dry contact
18
Output
2
EN- Raychem920series-IM-H56874 05/15
70 / 82
C.4.2 USED AS A SWITCHED DC CONTACT
Terminal board
1
+ 9Vdc Nom
17
Alarm
Relay
18
Common
+ 9VDC (Switched
– on alarm)
2
C.4.3 USED TO DRIVE AN OPTIONAL EXTERNAL RELAY
Terminal board
+9Vdc Nom
1
17
Crydom MS11-CX240D5
Alarm relay
18
Common 2
3
4
AC alarm
Relay out
+Control
–Input
1
~2
1A 277Vac max switched
Alarm output
C.4.4 USED TO DRIVE AN OPTIONAL EXTERNAL PILOT LIGHT
Power terminals
Trace power in (L1/line)
J1
Control power on (L1/line)
Trace power in (L2/neutral)
J2
Control power on (L2/neutral)
1
2
3
4
Optional line
voltage alarm light
Terminal board
+9Vdc nom
1
17
Alarm
Relay
18
Common 2
Crydom MS11-CX240D5
3 +Control
4 –Input
AC alarm
Relay out
1
~2
Switched line/L1
INDUSTRIAL HEAT TRACING SOLUTIONS
EN- Raychem920series-IM-H56874 05/15
71 / 82
C.5 External Input/Output Port Wiring
C.5.1 EXTERNAL INHIBIT/OVERRIDE USING A DRY CONTACT
Terminal board
+9Vdc nom
1
+ 20
Ext. contact
Input
Common
External dry contact
(Close to activiate inhibit or override mode)
(2kΩ max total loop resistance)
– 21
2
C.5.2 EXTERNAL INHIBIT/OVERRIDE USING A DC SIGNAL
Terminal board
+9Vdc nom
Ext. contact
Input
Common
1
+ 20
+
– 21
2
–
+
+5VDC to 24VDC nominal, 10ma. max
–
C.5.3 TEMPBUS AND INHIBIT MASTER/SLAVE CONNECTIONS
Terminal board
Terminal board
Ext. contact
Output
+ 4
– 5
Ext. contact
Input
+ 20
20 + Ext. contact
21 – Input
“Slave” 920 controller #1
– 21
Terminal board
Ambient sensing “master” 920 controller
Up to 25 “slave” 920 controllers (50 points)
may be tied to one “master” 920 controller.
Note that the “master” and “slave”
controllers must be installed within the
same enclosure.
20 + Ext. contact
21 – Input
“Slave” 920 controller #2
Terminal board
20 + Ext. contact
21 – Input
INDUSTRIAL HEAT TRACING SOLUTIONS
EN- Raychem920series-IM-H56874 05/15
“Slave” 920 controller #25
72 / 82
Appendix D HTC Load Shedding Sequence
Load
shedding
command
received?
N
HTC
load shed
enabled?
N
All other
contact inputs
active?
[1]
N
Normal control
mode
Y
Y
HTC holds its output
OFF for 30 seconds
Y
Is
communications
active?
[2]
N
Y
Y
Has HTC
power been
reset?
N
Control at low
temp. alarm setpoint
Y
Y
Fail safe mode
enabled?
HTC temp. at
low temp.
alarm SP?
[3]
N
All matching HTCs set their
outputs to OFF
HTC display indicates load
shedding mode [4]
N
1. If an HTC is associated with more than one contact input, all inputs must be activated before
the HTC will go into a Load Shedding mode.
2. If communications between an HTC and an upstream device such as a GCC or supervisory
software are interrupted, or if the power has been reset to the HTC, the HTC will hold its
output OFF, waiting for a Load Shedding command
3. Only if the Low Temperature Alarm is ENABLED.
4. For 920 Series controllers, a “<Load Shedding>” message will displayed after the load
current reading.
INDUSTRIAL HEAT TRACING SOLUTIONS
EN- Raychem920series-IM-H56874 05/15
73 / 82
Appendix E 100 Ω Platinum RTD Table
IEC751 (1983)—100 W Platinum Resistance Temperature (RTD)—0.00385 Ohms/Ohm/°C
Ohms °F
°C
Ohms °F
°C
Ohms
°F
°C
62.28
64.30
66.31
68.33
70.33
72.33
74.33
76.33
78.32
80.31
82.29
84.27
86.25
88.22
90.19
92.16
94.12
96.09
98.04
100.0
101.95
103.90
105.85
107.79
109.73
111.67
113.61
115.54
117.47
119.40
121.32
123.24
125.16
127.07
128.98
130.89
132.80
134.70
136.60
138.50
140.39
142.29
144.17
146.06
147.94
149.82
151.70
153.58
155.45
248.76
250.48
252.19
253.90
255.61
257.32
259.02
260.72
262.42
264.11
265.80
267.49
269.18
270.86
272.54
274.22
275.89
277.56
279.23
280.90
282.56
284.22
285.87
287.53
289.18
290.83
292.47
294.11
295.75
297.39
299.02
300.65
302.28
303.91
305.53
307.15
308.76
310.38
311.99
313.59
315.20
316.80
318.40
319.99
321.59
323.18
324.76
326.35
327.93
761
770
779
788
797
806
815
824
833
842
851
860
869
878
887
896
905
914
923
932
941
950
959
968
977
986
995
1004
1013
1022
1031
1040
1049
1058
1067
1076
1085
1094
1103
1112
1121
1130
1139
1148
1157
1166
1175
1184
1193
405
410
415
420
425
430
435
440
445
450
455
460
465
470
475
480
485
490
495
500
505
510
515
520
525
530
535
540
545
550
555
560
565
570
575
580
585
590
595
600
605
610
615
620
625
630
635
640
645
–139
–130
–121
–112
–103
–94
–85
–76
–67
–58
–49
–40
–31
–22
–13
–4
5
14
23
32
41
50
59
68
77
86
95
104
113
122
131
140
149
158
167
176
185
194
203
212
221
230
239
248
257
266
275
284
293
–95
–90
–85
–80
–75
–70
–65
–60
–55
–50
–45
–40
–35
–30
–25
–20
–15
–10
–5
0
5
10
15
20
25
30
35
40
45
50
55
60
65
70
75
80
85
90
95
100
105
110
115
120
125
130
135
140
145
INDUSTRIAL HEAT TRACING SOLUTIONS
159.18
161.04
162.90
164.76
166.61
168.46
170.31
172.16
174.00
175.84
177.68
179.51
181.34
183.17
184.99
186.82
188.63
190.45
192.26
194.07
195.88
197.69
199.49
201.29
203.08
204.88
206.67
208.45
210.24
212.02
213.80
215.57
217.35
219.12
220.88
222.65
224.41
226.17
227.92
229.67
231.42
233.17
234.91
236.65
238.39
240.13
241.86
243.59
245.31
311
320
329
338
347
356
365
374
383
392
401
410
419
428
437
446
455
464
473
482
491
500
509
518
527
536
545
554
563
572
581
590
599
608
617
626
635
644
653
662
671
680
689
698
707
716
725
734
743
155
160
165
170
175
180
185
190
195
200
205
210
215
220
225
230
235
240
245
250
255
260
265
270
275
280
285
290
295
300
305
310
315
320
325
330
335
340
345
350
355
360
365
370
375
380
385
390
395
EN- Raychem920series-IM-H56874 05/15
74 / 82
Appendix F 100 Ω Nickel-Iron RTD Table
Ohms
°F
°C
Ohms
°F
°C
Ohms
°F
°C
69.8
71.1
72.3
73.1
74.3
75.5
76.7
78.0
78.8
80.0
81.2
82.2
82.9
84.2
85.7
86.9
88.1
88.9
90.1
91.4
92.2
93.4
94.5
95.8
97.1
98.3
99.5
100.8
102.0
103.3
104.5
105.9
107.2
108.5
109.8
111.1
112.5
113.8
115.2
116.5
117.9
119.2
120.6
122.0
123.4
124.8
126.2
127.6
129.0
130.5
131.9
–100
–95
–90
–85
–80
–75
–70
–65
–60
–55
–50
–45
–40
–35
–30
–25
–20
–15
–10
–5
0
5
10
15
20
25
30
35
40
45
50
55
60
65
70
75
80
85
90
95
100
105
110
115
120
125
130
135
140
145
150
–73
–70
–67
–65
–62
–59
–56
–53
–51
–48
–45
–42
–40
–37
–34
–31
–28
–26
–23
–20
–17
–15
–12
–9
–6
–3
–1
1
4
7
10
12
15
18
21
23
26
29
32
35
37
40
43
46
48
51
54
57
60
62
65
133.4
134.8
136.3
137.8
139.3
140.8
142.3
143.8
145.3
146.8
148.4
149.9
151.5
153.0
154.6
156.2
157.7
159.3
160.9
162.5
164.2
165.8
167.4
169.0
170.7
172.3
174.0
157.7
177.4
179.1
180.8
182.5
184.2
185.9
187.6
189.
191.1
192.9
194.5
196.4
198.2
199.9
201.7
203.5
205.3
207.2
109.0
210.8
212.7
214.5
216.4
155
160
165
170
175
180
185
190
195
200
205
210
215
220
225
230
235
240
245
250
255
260
265
270
275
280
285
290
295
300
305
310
315
320
325
330
335
340
345
350
355
360
365
370
375
380
385
390
395
400
405
68
71
73
76
79
82
85
87
90
93
96
98
101
104
107
110
112
115
118
121
123
126
129
132
135
137
140
143
146
148
515
154
157
160
162
165
168
171
173
176
179
182
185
187
190
193
196
198
201
204
207
218.2
220.1
222.0
223.9
225.8
227.7
229.6
231.5
233.5
235.4
237.4
239.3
241.3
243.3
245.3
247.2
249.3
251.2
253.3
255.2
257.3
259.3
261.4
263.4
265.5
267.6
269.6
271.7
273.8
275.9
278.0
280.1
282.3
284.4
286.5
288.6
290.8
293.1
295.2
297.5
299.8
301.4
303.7
306.0
308.3
310.6
312.2
314.5
316.8
319.1
320.6
410
415
420
425
430
435
440
445
450
455
460
465
470
475
480
485
490
495
500
505
510
515
520
525
530
535
540
545
550
555
560
565
570
575
580
585
590
595
600
605
610
615
620
625
630
635
640
645
650
655
660
210
212
215
218
221
223
226
229
232
235
237
240
243
246
248
251
254
257
260
262
265
268
271
273
276
279
282
285
287
290
293
296
298
301
304
307
310
312
315
318
321
323
326
329
332
335
337
340
343
346
348
INDUSTRIAL HEAT TRACING SOLUTIONS
EN- Raychem920series-IM-H56874 05/15
75 / 82
Appendix G Factory Default/Configuration Sheets
G.1 Configuration Sheet V3.00
The following defines the default 920 Series control module configuration as set by Pentair
Thermal Managament for firmware V3.00. These settings are subject to change without notice. It
is the user’s responsibility to verify that all configuration parameters are chosen appropriately for
the intended application. IMPORTANT: It is recommended that all parameters common to both
Control Points A and B be programmed first.
Common Setup Sub-Menu
Parameter Factory User
Temp. Units °F
Firmware Version V3.0 Ext. Contact Input Not used
Ext. Contact Output Not used
Flash Alarm Output Yes
Alarm Output State N.C.
Language English
Point B Used Yes
Passcode 0
n/a
Communication Setup Sub-Menu
Parameter Factory User
HTCBUS Addr (factory ID)
Protocol HTCBUS
Baud Rate AUTO
Hardware None, modem,
RS-232 (if installed)
Driver Auto
Profile Auto
Tx Delay 0.02 secs
Point Setup Sub-Menu
Parameter Factory User
Tag TAG-32768
Switch Control Mode Proportional
Prop Band 4°F (2°C)
Deadband n/a
Switch Rating 30.0 A
Circuit Breaker 30.0 A
Max Power 7200 W
TS CTL Mode TS1-Fail Off
TS1 – High Limit Disable
TS2 – High Limit Disable
Volt Turns Ratio 1.00 to 1
INDUSTRIAL HEAT TRACING SOLUTIONS
EN- Raychem920series-IM-H56874 05/15
76 / 82
Point Setup Sub-Menu (Continued)
Current Turns Ratio 1.00 to 1
Autocycle Enable
Autocycle Interval 8
Autocycle Units Hours
Inhibit Ctl Disable
Load Shedding Disable
Configuration Mode Main Menu
Parameter Factory User
Control Setpoint 68°F (20°C)
TS Alarms Configuration Sub-Menu
Parameter Factory User
TS 1 Fail Enable
Lo TS 1 Alarm Enable
Lo TS 1 14°F (–10°C)
Hi TS 1 Alarm Enable
Hi TS 1 212°F (100°C)
TS 2 Fail Disable
Lo TS 2 Alarm Disable
Lo TS 2 —
Hi TS 2 Alarm Disable
Hi TS 2 —
Latch TS Alarms Yes
TS CTL Fail Alarm Enable
INDUSTRIAL HEAT TRACING SOLUTIONS
EN- Raychem920series-IM-H56874 05/15
77 / 82
Other Alarms Configuration Sub-Menu
Parameter Factory User
Lo Load Alarm Enable
Lo Load 1.00 A
Hi Load Alarm Disable
Hi Load —
Hi GFI Alarm Enable
Hi GFI 50 ma
GFI Trip Alarm Enable
GFI Trip 75 ma
Lo Volt Alarm Enable
Lo Volt 90 V
High Volt Alarm Enable
Hi Volt 270 V
Nominal Resist 6.00 Ω
Lo Resist Alarm Disable
Lo Resist —
Hi Resist Alarm Disable
Hi Resist —
Overcurrent Trip Enable
Switch Fail Alarm Enable
HTC Reset Alarm Disable
C.B. Limit Alarm Disable
Power Limit Alarm Disable
Switch Limit Alarm Disable
EEROM Data Fail Disable
INDUSTRIAL HEAT TRACING SOLUTIONS
EN- Raychem920series-IM-H56874 05/15
78 / 82
G.2 920 Series HTC Configuration Sheet V3.1X and V3.2X
= Most commonly changed setting
IMPORTANT: Select temperature units before any other settings are entered.
Configuration Mode Main Menu
Parameter Factory User
Control Setpoint 68°F (20°C)
Lo TS 1 14°F (–10°C)
Lo Load 1.0 A
Hi GFI 50 mA
GFI Trip 75 mA
TS Alarms Configuration Sub-Menu
Parameter Factory User
TS 1 Fail Enable
Lo TS 1 Enable
Lo TS 1 14°F (–10°C)
Hi TS 1 Disable
Hi TS 1 *n/a (212°F (100°C))
TS 2 Fail Disable
Lo TS 2 Disable
Lo TS 2 *n/a (14°F (–10°C))
Hi TS 2 Disable
Hi TS 2 *n/a (212°F (100°C))
Lo TS Filter 0 min
Hi TS Filter *n/a (0 min)
Latch TS Alarms Yes
CTL TS Fail Enable
Other Alarms Configuration Sub-Menu
Parameter Factory User
Lo Load Enable
Lo Load 1.0 A
Lo Load Filter 0 sec
Hi Load Disable
Hi Load *n/a (30.0 A)
Hi Load Filter *n/a (0 sec)
Hi GFI Enable
Hi GFI 50 mA
Hi GFI Filter 0 sec
INDUSTRIAL HEAT TRACING SOLUTIONS
EN- Raychem920series-IM-H56874 05/15
79 / 82
Other Alarms Configuration Sub-Menu (Continued)
GFI Trip Enable
GFI Trip 75 mA
Lo Volt Enable
Lo Volt 90 V
Lo Volt Filter 0 sec
Hi Volt Disable
Hi Volt *n/a (270 V)
Hi Volt Filter *n/a (0 sec)
Lo Resist Disable
Lo Resist *n/a (50%)
Lo Resist Filter *n/a (0 sec)
Hi Resist Disable
Hi Resist *n/a (50%)
Hi Resist Filter *n/a (0 sec)
Nominal Resist *n/a (6.00 Ω)
Overcurrent Trip Enable
Switch Fail Enable
HTC Reset Disable
C.B. Limiting Disable
Power Limiting Disable
Switch Limiting Disable
Contactor Count *n/a (Enable)
Countactor Count *n/a (200,000)
EEROM Data Fail Enable
Point Setup Sub-Menu
Parameter Factory User
Tag TAG-(factory ID)
Switch Control Mode Proportional
Prop Band 4°F (2°C)
Deadband *n/a (5°F(3°C))
Cycle Time *n/a (10 min)
Switch Rating 30.0 A
Circuit Breaker 30.0 A
Max Power 7200 W
3 Ph Pwr Calc No
TS Fail Mode Off
TS CTL Mode TS1-Fail Off
TS 1 Type 100 Ω Plat
TS 1 Lead Resist *n/a (0 Ω)
TS 1 Hi Limit Disable
TS 2 Type 100 Ω Plat
TS 2 Lead Resist *n/a (0 Ω)
TS 2 Hi Limit Disable
Volt Source Pt A (or Pt B)
Fixed Volt *n/a (120V)
Volt Turns Ratio 1.00 to 1
INDUSTRIAL HEAT TRACING SOLUTIONS
EN- Raychem920series-IM-H56874 05/15
80 / 82
Parameter Factory User
Current Turns Ratio 1.00 to 1
Autocycle Enable
Autocycle Interval 8
Autocycle Units Hours
Override Source Remote
Load Shedding Disable
Common Setup Sub-Menu
Parameter Factory User
Temperature Units °F
Version V3.2x.xx Ext. Input Not used
Ext. Output Not used
Flash Alarm Output Yes
Alarm Output N.C.
Language English
Point B Used Yes
Passcode 0
Scroll Delay 0.15 secs
Copy Config… (see user manual)
n/a
Communication Setup Sub-Menu
Parameter Factory User
Protocol HTCBUS
HTCBUS Addr (factory ID)
Modbus Addr *n/a (1)
Modbus Sub Addr *n/a (0)
Baud Rate Auto
Parity *n/a (None)
Hardware None, modem, RS-232, RS-485 n/a
Driver Auto
Profile Auto
Tx Delay 0.06 secs
*n/a Parameter may only appear if certain features are enabled. Values shown in brackets are
Pentair Thermal Managament defaults if the settings are enabled.
This information defines the default 920 Series control module configuration as set by Pentair
Thermal Managament for firmware up to V3.2x. These settings are subject to change without
notice.
It is the user’s responsibility to verify that all configuration parameters are chosen appropriately
for the intended application.
INDUSTRIAL HEAT TRACING SOLUTIONS
EN- Raychem920series-IM-H56874 05/15
81 / 82
www.pentairthermal.com
NORTH AMERICA
Europe, Middle East, Africa
Asia Pacific
Latin America
Tel:+1.800.545.6258
Fax:+1.800.527.5703
Tel:+1.650.216.1526
Fax:+1.650.474.7711
[email protected]
Tel:+32.16.213.511
Fax:+32.16.213.603
[email protected]
Tel:+86.21.2412.1688
Fax:+86.21.5426.2937
[email protected]
Tel:+1.713.868.4800
Fax:+1.713.868.2333
[email protected]
Pentair is owned by Pentair or its global affiliates. All other trademarks are the property of their respective owners. Pentair reserves the right to change
specifications without prior notice.
© 2001-2015 Pentair.
INDUSTRIAL HEAT TRACING SOLUTIONS
EN- Raychem920series-IM-H56874 05/15
82 / 82