Technical Specification

Transcription

Technical Specification
Edition 1
Specification Guide
Smoke, Fire & Carbon Monoxide
Safety Products
The Home of Safety Products
Providing market leading domestic safety
products throughout Europe.
Our comprehensive range of products offer a level of protection and performance few can match.
We provide branded products and services of superior quality and value that improve the lives
of customers, from the electrical contractors who install them to the families who rely on them.
2014
Launched SONA range to UK trade sector
2013
noCO launched
2012
Appointed as CO alarm supplier to British Gas
2012
Achieved FastTrack 100 listing for 5th consecutive year
2010
Appointed as BRK Brands Europe Limited exclusive European distributor
2010
Launched thermally enhanced optical Thermoptek smoke alarm
2010
Sprue Safety Products launched
2009
Acquired control of Pace Sensors
2007
Launched affordable wireless safety products for the hard of hearing as Wi-Safe brand
2006
Agreement to supply the Fire and Rescue Services with a 10-year optical smoke alarm
2002
Secured first Public Sector deal with London Borough of Islington
1998
Sprue was formed
2
Contents
Specification Guide
Sensing Technologies Explained
4-5 CO Alarm Solutions 52-53
54-55
Thermoptek Sensing Technology
6
Section Overview
Thermistek Sensing Technology
7
SONA Wireless Battery CO Alarm
56
Wi-Safe 2 Technology
8
BRK Wireless Mains CO Alarm
57
Sensing Technologies Comparison
9
FireAngel Wireless Battery CO Alarm
58
FireAngel Battery CO Alarm
59
FireAngel Battery CO Alarm
60
10-11 FireAngel Battery CO Alarm
61
Hallway, Landing, Living Room &
Bedroom Solutions
Section Overview
12-13
SONA Wireless Mains Smoke Alarm
14-15
SONA Mains Smoke Alarm
16-17
Boiler Shut-Off Solutions
BRK Mains Smoke Alarm
18-19
Section Overview
66
FireAngel Wireless Battery Smoke Alarm
20-21
noCO Boiler Shutdown Control Unit
67
FireAngel Battery Smoke Alarm
22-23
noCO In Room CO Alarm
68
noCO In Void CO Alarm
69
Bedroom & Living Room Solutions
24-25
CO Alarm Product Specification
62-63
64-65
Section Overview
26-27
Firefighting Equipment Solutions
BRK Mains Smoke Alarm
28-29
Dry Powder Fire Extinguisher
72
Dry Powder Fire Extinguisher
72
30-31 Dry Powder Fire Extinguisher
73
Kitchen & Garage Solutions
70-71
Section Overview
32-33
Dry Powder Fire Extinguisher
73
SONA Wireless Mains Heat Alarm
34-35
Carbon Dioxide Fire Extinguisher
74
SONA Mains Heat Alarm
36-37
Foam Fire Extinguisher
74
BRK Mains Heat Alarm
38-39
Super Foam Fire Extinguisher
74
FireAngel Wireless Battery Heat Alarm
40-41
Fire Blanket
75
FireAngel Battery Heat Alarm
42-43
Fire Blanket
75
Accessories44-45 Appendices76-77
SONA Battery Alarm Control Unit
46
Siting of Smoke Alarms
78
FireAngel Wireless Vibrating Pad & Strobe
47
Siting of Heat Alarms
79
FireAngel Wireless Low Frequency Sounder
48
Siting of CO Alarms
BRK RF Base 49
Example Risk Assessment
82
Minimum Grade & Level of Detection
83
System Grades & Categories Explained
84
Specification Generator
85
Accessories Product Specification
50-51
80-81
Contacting Sprue86
3
4
Technologies
Explained
5
Sensing Technology
Smoke Alarm Sensing Technology
Improved performance less complication!
Large sensing chamber increases
stability and alarm accuracy.
Thermoptek is the smoke alarm technology
of choice for UK Fire and Rescue Services.
Two sensors provide heat readings,
to enable early warning of fire.
It provides an alternative to using separate
ionisation and optical alarms; for detection
of fast flaming and slow smouldering fires
in a single alarm.
Thermoptek technology combines the very
latest in optical sensing with a thermal
enhancement. It constantly monitors for
temperature change, and if a sudden
temperature rise is detected the
sensitivity of the alarm is increased.
This provides a much faster reaction
to both fast flaming and slow
smouldering fires in a single alarm.
Unlike ionisation technology,
Thermoptek technology has no
storage or disposal issues relating
to radioactive materials.
Precision optical sensors
reduce false alarms.
Thermoptek Performance
Fire Severity
Earlier response time
54 Sec
Thermoptek
Smoke Alarm
Reaction
Optical
Smoke Alarm
Reaction
30 Sec
1 Min
Time to reaction
6
90 Sec
2 Min
Sensing Technology
Heat Alarm Sensing Technology
Class A1 detection for a
faster response under all
conditions.
Thermistek technology constantly monitors for
temperature change. If a temperature increase is
detected, and predicted to exceed an alarm trigger
threshold, the alarm will sound.
Unique radiant heat dish
reflects heat from a fire onto
the thermistor, reducing the
time to alarm and alerting you
to the danger earlier.
Thermistek
ection Curre
nv
nt
Co
ant Energy
Radi
High performance
thermistor.
s
ection Curre
nv
nt
Co
ection Curre
nv
nt
Co
Conventional
Heat Alarm
s
s
Predictive algorithm determines
the rate of temperature rise
more quickly overcoming the
temperature lag between the
ceilings and the thermistor.
ant Energy
Radi
The thermistor is heated by convection and also by the radiant
heat of the fire.
Thermistek Performance
Fire Severity
Earlier response and
smaller reaction window
Thermistek
Heat Alarm
Reaction
Conventional
Heat Alarm
Reaction
1 Min
2 Min
3 Min
4 Min
Time to reaction
7
Wireless Technology
Wi-Safe 2
Intelligent wireless
communication with any
other product with Wi-Safe 2
technology inside.
Closed network
Unique identity codes (16 million different combinations)
are hard coded into the memory of the network upon
interlinking so they will be retained, even if the mains
is turned off and the battery discharges.
Alarms cannot be triggered by wireless products such
as doorbells, cordless phones etc. due to the Wi-Safe 2
encryption, and the EMC (Electro Magnetic Compatibility)
testing / compliance.
Wi-Safe 2 will not be compatible with
competitors products.
Create a perfectly tailored system to suit the changing
needs of the property or the tenants
The radio
frequency band
of the Wi-Safe 2
is 868 MHz.
The system can be adapted if the requirements for the
individual change. Additional smoke, heat, CO and deaf
alert accessories can be added or removed at anytime.
Wi-Safe 2 provides flexible wireless solutions for
both hardwired and battery systems.
Up to 50 alarms can be interlinked for maximum coverage.
Test and locate from anywhere in the home
The alarm control unit can be added to any
Wi-Safe 2 network.
Wi-Safe 2 simplifies installation
Wi-Safe 2 products can be linked together in a matter
of seconds with a simple two step connection
process. Eliminating the time and expense of
channelling wiring around a building.
Meshed network
In a meshed network, each unit can communicate
with any other alarm in the network (it does not
have to be directly in range). Units are constantly
transmitting and receiving a radio frequency signal.
Any danger, reported by every alarm
When an alarm detects smoke, heat or CO, all
alarms and accessories in the network will
sound. This means that you are alerted
anywhere in the property.
Each unit will make a differentiated
sound pattern for either a smoke / heat
or CO incident.
8
Sensing Technologies Explained
Sensor Types
Thermally Enhanced Optical
Traditionally optical smoke alarm sensitivity
can change with ambient temperature that is
the sensitivity in winter will be different than
the sensitivity in summer. Thermal enhancement
removes this variance by making slow adjustment
to the sensitivity settings dependent upon
background temperature.
Thermoptek technology combines the latest
in optical sensing technology with a thermal
enhancement system which provides the fastest
reaction to all fire types in a single alarm.
Ionisation
Ionisation technology is generally more sensitive
than optical technology at detecting small particles
of smoke which tend to be produced in greater
amounts by fast flaming fires which consume
combustible materials rapidly and spread quickly.
Sources of these fires may include paper burning
in a wastebasket or chip pan fires.
Thermistek heat detection technology constantly
monitors for temperature change. If a dangerous rate
of rise in the temperature is detected, and predicted to
exceed an alarm trigger threshold (54 to 65 degrees),
the alarm will sound. This predictive quality provides
a much quicker response to fast flaming fires. Heat
alarms with Thermistek technology are approved to
class A1.
Electrochemical CO Sensing
Thermistor
Electrochemical technology is an accurate and
proven method of sensing CO. Our patented sensor
protects against leakage - the most common failure
of other sensors.
Alarms with Thermistor sensors will activate
when the temperature reaches the pre-set range
of 54°C to 70°C.
All CO alarms are 100% tested and calibrated using
carbon monoxide during the manufacturing process.
Smart Silence
Sleep Easy
‘Smart Silence’ technology allows the user to silence
the alarm for up to 10 minutes in the event of a known
false alarm. After 10 minutes the alarm shall return to
full sensitivity. During these 10 minutes, if additional
heat / smoke is detected the alarm silence will be
overridden and the alarm will sound.
A low battery ‘chirp’ can be silenced for a period of
8 hours by pressing the test button. After this period
the audible chirp will start again. This process can be
repeated for a maximum of 10 times. The alarm will
still detect heat /smoke during this time, however the
alarm must be replaced within 30 days. A chirp which
indicates a fault cannot be silenced.
Summary of our Sensor Types*
 Excellent

Immunity
to:
Heat
Sources
Smoke
Sources
Smoke Alarms
Fast Flaming
Slow Smouldering
Heat Alarms
Thermoptek
Thermally
Enhanced Optical
Ionisation






Response
Temperature
Rapidly Rising
Temperature
Thermistek
Thermistor
Class A1
(54°C - 62°C)
Class A2
(54°C - 70°C)


Contamination





Kitchen Fumes





* For full guidance on what type of alarm to install and where consult BS5839-6
Poor
9
10
Hallway
Landing
Living Room
& Bedroom
11
Solutions for:
Hallway, Landing, Living Room & Bedroom
Positioning of Smoke alarms
Smoke Alarms
Product Selector Table
Mains Powered
Wireless Smoke Alarm
12
Mains Powered
Smoke Alarm
Mains Powered
Smoke Alarm
Product code
WSM-SN-1
SM-SN-1
760 MRL
Brand
SONA
SONA
BRK
Technology
Thermoptek and Wi-Safe 2
Thermoptek
Thermally enhanced optical
Supply Voltage
230V AC, 50Hz
230V AC, 50Hz
230V AC, 50Hz
Battery
10 year sealed for life lithium
battery back-up
10 year sealed for life lithium
battery back-up
Rechargeable lithium battery
back-up
Warranty
5 years
5 years
5 years
Grade
D
D
D
Page
14
16
18
Hallway, Landing,
Living Room & Bedroom
This section is designed to provide smoke alarm solutions for hallways, landings,
living rooms and bedrooms. The alarm selections have been made based on the
sensing technologies used in each of the alarms and how effective they are at
detecting fires that most commonly occur in each of the rooms.
Included in this section are comprehensive alarm ranges including both mains and battery options,
providing solutions for most installation scenarios.
Bedroom & Living Room
Mains:
• SONA mains powered wireless smoke alarm
• SONA mains powered smoke alarm
• BRK mains powered smoke alarm (with optional RF base)
Battery:
• FireAngel battery powered wireless smoke alarm
Summary of our Sensor Types*
 Excellent

Heat
Sources
Slow Smouldering
Thermoptek
Ionisation






Response
Temperature
Rapidly Rising
Temperature
Thermistek
Thermistor
Class A1
(54°C - 62°C)
Class A2
(54°C - 70°C)


Contamination





Kitchen Fumes





* For full guidance on what type of alarm to install and where consult BS5839-6
Battery Powered Wireless Smoke
Alarm
Battery Powered
Smoke Alarm
760 MBX
WST-630T
ST-622T
BRK
FireAngel
FireAngel
Technology
Thermally enhanced optical
Thermoptek and Wi-Safe 2
Thermoptek
Supply Voltage
230V AC, 50Hz
3V DC
3V DC
9V alkaline battery back-up
10 year sealed for life lithium
battery
10 year sealed for life lithium
battery
Warranty
5 years
5 years
10 years
Grade
D
F
F
Page
18
20
22
Battery
Firefighting Equipment
Product code
Brand
Boiler Shut-off
Mains Powered
Smoke Alarm
CO Alarm
Immunity
to:
Fast Flaming
Heat Alarms
Thermally
Enhanced Optical
Accessories
Smoke
Sources
Smoke Alarms
Poor
Kitchen & Garage
• FireAngel battery powered smoke alarm
13
WSM-SN-1
Mains Powered Wireless Smoke Alarm
Grade
D - Mains powered with battery back-up
Sensor type
Thermoptek
Battery back-up type
10 year sealed for life lithium
Key Features
• T
hermoptek sensing technology for fast detection
of both fast flaming and slow smouldering fires.
• 10 year sealed for life lithium battery back-up.
• L
ow energy usage - typically less than 10%
of the average 230V AC smoke alarm.
• Wi-Safe 2 technology - up to 50 Wi-Safe 2 alarms
can be interlinked on a single network.
• Ultra slim, integrated mounting base.
• Centralised button - test / Smart Silence / locate.
• Secondary buzzer.
• Mixed system compatibility:
• Wireless and hardwired.
• Mains and battery powered alarms.
BS EN 14604:2005
Licence No: KM557789
Technical Specification
0086
0086-CPR-557790
EN 14604:2005
DOP:SADOP-WSM-SN-01
Wi-Safe 2 module contained within WSM-SN-1
independently tested to RF standard ETSI EN
300 220-2 V2.3.2 (2010-02) byTRaC Global Ltd
EN300489-1 &-3 / EN300220-2 - Radio
141.5mm
14
Dimensions
141.5mm (diameter) x 43mm (depth)
Supply voltage
230V AC, 50Hz
Battery back-up
10 year sealed for life lithium battery
Technology
Thermoptek and Wi-Safe 2
Alarm sound level
85dB(A) at 3m (minimum)
Installation positions
Ceiling / Wall
Operating temperature
+4°C to +38°C
Operating humidity
Up to 90% RH non-condensing
Storage temperature
-20°C to +60°C
Storage humidity
Up to 93% RH non-condensing
Plastic material
ABS, UL94 VO fire retardant
Warranty
5 years
Master pack quantity
4
Weight
284g
Certified to
BS EN 14604: 2005
Independently tested to
ETSI EN 300 220-2 V2.3.2 (2010-02), EN300489-1 &-3, EN300220-2 – Radio
Maximum number of connected units
50 wireless units
Operating Frequency
868 MHz
Range
35m (over 200m in clear air)
43mm
• The smoke alarm shall carry the BSI Kitemark
to indicate type testing to BS EN14604: 2005.
It will meet the requirements of Grade D as
defined in BS 5839 Pt.6: 2013. The alarm shall
carry the CE mark to indicate conformance
to all of the applicable EC directives
including Low Voltage and Electromagnetic
Compatibility Directives.
• The alarm shall incorporate ‘Sleep Easy’
functionality whereby a low battery chirp can
be silenced for a period of 8 hours by pressing
the test button on the alarm. This function can
be used up to 10 times.
• The alarm shall utilise multiple sensing
elements. Incorporating thermally enhanced
optical sensing technology (Thermoptek)
which constantly monitors for temperature
change. If a rate of temperature rise is
predicted to rise above a predetermined
threshold the sensitivity of the alarm is
increased, providing a quicker response time
to both slow smouldering and fast flaming
fires in a single alarm.
• The wireless Wi-Safe 2 module shall have
a separate 10 year sealed for life lithium
battery designed to outlast the usable life
of the alarm.
• The alarm shall have a low battery warning
signal, which will ‘chirp’ every 45 seconds
for at least 30 days to indicate when a
replacement of the alarm is required. All other
alarms on the network shall also emit an
audible low battery chirp once every 4 hours.
• The alarm shall have a secondary buzzer
fitted to ensure fail-safe operation in all
circumstances.
• The alarm shall feature an intelligent locate
feature whereby pressing the test / silence
button on any alarm in the network will
silence all but the initiating alarm.
• The alarm shall be capable of working on
a mixed system to include both hardwire
interconnect and wireless interlink alarms,
across both mains and battery powered
products of a similar type.
• The alarm shall be supplied with a quickfitting surface mounting base with a depth
of no more than 5mm with integral terminal
block and cable cover. Cable knock outs allow
for compatibility with YT2 cable trunking.
Universal screw holes provide backwards
compatibility for ease of install and less
drilling on installation.
• The alarm shall feature ‘Smart Silence’
technology which allows the alarm to be
silenced for up to 10 minutes in the event of a
known false alarm. During these 10 minutes if
additional smoke is detected the alarm silence
will be overridden and the alarm will sound.
• The alarm shall be supplied with a dust cover
fitted to protect it from contaminants during
installation.
Low energy usage
typically less than
10% of the average
AC smoke alarm
Accessories
Key Technology
Slim integrated
mounting base
Kitchen & Garage
• The alarm shall operate on a 230V mains
power supply and have a single built in,
sealed for life, 10 year lithium battery back-up
to power the alarm in the event of a mains
failure from installation.
• The alarm shall have a built in sounder giving
a minimum sound output of 85dB(A) at 3m.
• The alarm shall incorporate a large central
test / silence button to test circuitry, sensor
and sounder and activate all interconnected
alarms in the system.
• The Wi-Safe 2 radio frequency shall be
868 MHz band in accordance with R&TTE
Directive 1999/5/EC.
• The alarm shall be energy efficient with an
operational power consumption of no more
than 4.29kW over its 10 year lifetime.
• The mounting base shall have a factory fitted
foam gasket to prevent air draughts and dust
ingress into the rear of the unit.
Bedroom & Living Room
• The alarm shall incorporate a Wi-Safe
2 intelligent communication module as
standard, which wirelessly interlinks with up
to 50 other units with Wi-Safe 2 technology
inside on a single network. All units shall have
the ability to be learnt into a single network by
an easy 2 button process.
• The alarm shall automatically connect to the
mains as it locks onto the mounting base and
disconnect from the mains as soon as it is
removed from the mounting base with a tool.
Hallway, Landing,
Living Room & Bedroom
Product Specification
Large concave button
for test, Smart Silence
and locate
Precision optical
sensors ensures
reduced false alarms
CO Alarm
10 year sealed for
life lithium battery
back-up
Secondary
buzzer
Two heat sensors
provide readings, to
enable early warning
of fire
Compatibility
Hallway
Non-Wireless
p14
SM-SN-1
Mains Smoke
p16
WSM-SN-1
Mains Wireless
Smoke
p14
SM-SN-1
Mains Smoke
p16
Living Room
WSM-SN-1
Mains Wireless
Smoke
p14
SM-SN-1
Mains Smoke
p16
Bedroom
WSM-SN-1
Mains Wireless
Smoke
p14
SM-SN-1
Mains Smoke
p16
Kitchen
WHM-SN-1
Mains Wireless
Heat
p34
HM-SN-1
Mains Heat
p36
Garage
Large sensing chamber
increases stability and
alarm accuracy
CO
WHM-SN-1
Mains Wireless
Heat
p34
HM-SN-1
Mains Heat
Accessories
WCOB-SN-1
W2-SVP-630
Battery Wireless
CO
Vibrating Pad &
Strobe
p56
p47
W2-LFS-630
Low Frequency
Sounder
p48
Firefighting Equipment
Wireless
WSM-SN-1
Mains Wireless
Smoke
Landing
Boiler Shut-off
Intelligent wireless communication
with up to 50 other Wi-Safe 2 products
p36
15
SM-SN-1
Mains Powered Smoke Alarm
Grade
D - Mains powered with battery back-up
Sensor type
Thermoptek
Battery back-up type
10 year sealed for life lithium
Key Features
• T
hermoptek sensing technology for fast detection
of fast flaming and slow smouldering fires.
• 10 year sealed for life lithium battery back-up.
• L
ow energy usage - typically less than 10% of the
average 230V AC smoke alarm.
• Hardwire interconnection with up to 30 units.
• Ultra slim, integrated mounting base.
• Centralised button - test / Smart Silence / locate.
• Mixed system compatibility:
• Wireless and hardwired.
• Mains and battery powered alarms.
BS EN 14604:2005
Licence No: KM557789
0086-CPR-557790
DOP:SADOP-SM-SN-01
Technical Specification
141.5mm
16
Dimensions
141.5mm (diameter) x 43mm (depth)
Supply voltage
230V AC, 50Hz
Battery back-up
10 year sealed for life lithium battery
Technology
Thermoptek
Alarm sound level
85dB(A) at 3m (minimum)
Installation positions
Ceiling / Wall
Operating temperature
+4°C to +38°C
Operating humidity
Up to 90% RH non-condensing
Storage temperature
-20°C to +60°C
Storage humidity
Up to 93% RH non-condensing
Plastic material
ABS, UL94 VO fire retardant
Warranty
5 years
Master pack quantity
4
Weight
258g
Certified to
BS EN 14604: 2005
Independently tested to
N/A
Maximum number of connected units
30 hardwired units
Operating Frequency
N/A
Range
N/A
43mm
• The smoke alarm shall carry the BSI Kitemark
to indicate type testing to BS EN14604: 2005.
It will meet the requirements of Grade D as
defined in BS 5839 Pt.6: 2013. The alarm shall
carry the CE mark to indicate conformance
to all of the applicable EC directives
including Low Voltage and Electromagnetic
Compatibility Directives.
• The alarm shall have a low battery warning
signal, which will ‘chirp’ every 45 seconds for
at least 30 days to indicate when a replacement
of the alarm is required. All other alarms on the
network shall also emit an audible low battery
chirp once every 4 hours.
• The alarm shall be energy efficient with an
operational power consumption of no more
than 4.29kW over its 10 year lifetime.
• The alarm shall operate on a 230V mains
power supply and have a single built in,
sealed for life, 10 year lithium battery back-up
to power the alarm in the event of a mains
failure from installation.
• The alarm shall have a built in sounder giving a
minimum sound output of 85dB(A) at 3m.
• The alarm shall have a secondary buzzer
fitted to ensure fail-safe operation in all
circumstances.
• The alarm shall incorporate a large central test
/ silence button to test circuitry, sensor and
sounder and activate all interconnected alarms
in the system.
• The alarm shall be capable of working on
a mixed system to include both hardwire
interconnect and wireless interlink alarms,
across both mains and battery powered
products of a similar type.
• The alarm shall feature an intelligent locate
feature whereby pressing the test / silence
button on any alarm in the network will silence
all but the initiating alarm.
• The alarm shall be supplied with a quickfitting surface mounting base with a depth
of no more than 5mm with integral terminal
block and cable cover. Cable knock outs allow
for compatibility with YT2 cable trunking.
Universal screw holes provide backwards
compatibility for ease of install and less drilling
on installation.
• The alarm shall feature ‘Smart Silence’
technology which allows the alarm to be
silenced for up to 10 minutes in the event of a
known false alarm. During these 10 minutes if
additional smoke is detected the alarm silence
will be overridden and the alarm will sound.
Kitchen & Garage
• The alarm shall carry a proven carbon footprint
of 13.9kgCO2e over its 10 year lifetime.
• The alarm shall have the ability to hardwire
interconnect with up to 30 other smoke and
heat alarms of a similar type on a single
network. When one alarm sound all other
alarms on the network will sound.
• The mounting base shall have a factory fitted
foam gasket to prevent air draughts and dust
ingress into the rear of the unit.
Bedroom & Living Room
• The alarm shall utilise multiple sensing
elements. Incorporating thermally enhanced
optical sensing technology (Thermoptek)
which constantly monitors for temperature
change. If a rate of temperature rise is
predicted to rise above a predetermined
threshold the sensitivity of the alarm is
increased, providing a quicker response time
to both slow smouldering and fast flaming fires
in a single alarm.
• The alarm shall incorporate ‘Sleep Easy’
functionality whereby a low battery chirp can
be silenced for a period of 8 hours by pressing
the test button on the alarm. This function can
be used up to 10 times.
• The alarm shall automatically connect to the
mains as it locks onto the mounting base
and disconnect from the mains as soon as it
removed from the mounting base with a tool.
Hallway, Landing,
Living Room & Bedroom
Product Specification
• The alarm shall be supplied with a dust
cover fitted to protect it from contaminants
during installation.
Key Technology
Precision optical
sensors ensure
reduced false alarms
Low energy usage
typically less than
10% of the average
AC smoke alarm
Accessories
Slim integrated
mounting base
Large concave button
for test, Smart Silence
and locate
CO Alarm
Secondary
buzzer
Compatibility
Hallway
Non-Wireless
p14
SM-SN-1
Mains Smoke
p16
WSM-SN-1
Mains Wireless
Smoke
p14
SM-SN-1
Mains Smoke
p16
Living Room
WSM-SN-1
Mains Wireless
Smoke
p14
SM-SN-1
Mains Smoke
p16
Bedroom
WSM-SN-1
Mains Wireless
Smoke
p14
SM-SN-1
Mains Smoke
p16
Kitchen
WHM-SN-1
Mains Wireless
Heat
p34
HM-SN-1
Mains Heat
p36
Garage
Large sensing chamber
increases stability and
alarm accuracy
CO
WHM-SN-1
Mains Wireless
Heat
p34
HM-SN-1
Mains Heat
Accessories
WCOB-SN-1
W2-SVP-630
Battery Wireless
CO
Vibrating Pad &
Strobe
p56
p47
W2-LFS-630
Low Frequency
Sounder
p48
Firefighting Equipment
Wireless
WSM-SN-1
Mains Wireless
Smoke
Landing
Two heat sensors
provide readings, to
enable early warning
of fire
Boiler Shut-off
10 year sealed for life
lithium battery back-up
p36
17
760 MRL & 760 MBX
Mains Powered Smoke Alarm
Grade
D - Mains Powered with battery back-up
Sensor type
Thermally enhanced optical
Battery back-up type
MRL - Rechargeable lithium / MBX - 9V alkaline
Key Features
• Thermally enhanced optical sensing technology
for fast detection of all fire types.
• 230V mains powered.
• Battery back-up:
• MRL - 10 year sealed for life rechargeable
lithium battery.
• MBX- 9V alkaline battery.
• Hardwire interconnect with up to 12 units
of a similar type.
• Compatible with wireless interlink base.
• Supplied with PUSH-FIT mounting base.
• Central test and silence button.
EN14604:2005
Licence No: 14LHK0078
Technical Specification
140mm
0359
0359-CPR-00253
EN14604: 2005
DoP: 14/11
53mm
140mm
53mm
Dimensions
Product Code
18
140mm (diameter) x 53mm (depth)
140mm (diameter) x 53mm (depth)
760 MRL
760 MBX
Supply voltage
230V AC, 50Hz
230V AC, 50Hz
Battery back-up
Rechargeable lithium battery
9V alkaline battery
Technology
Thermally enhanced optical
Thermally enhanced optical
Alarm sound level
85dB(A) at 3m (minimum)
85dB(A) at 3m (minimum)
Installation positions
Ceiling / Wall
Ceiling / Wall
Operating temperature
+5°C to +38°C
+5°C to +38°C
Operating humidity
10% to 85% relative
10% to 85% relative
Storage temperature
+5°C to +38°C
+5°C to +38°C
Storage humidity
10% to 85% relative
10% to 85% relative
Plastic material
ABS, UL94 VO fire retardant
ABS, UL94 VO fire retardant
Warranty
5 years
5 years
Master pack quantity
10
10
Weight
340g
377g
Certified to
BS EN 14604: 2005
BS EN 14604: 2005
Independently tested to
N/A
N/A
Maximum number of connected units
12 hardwired units
12 hardwired units
Operating Frequency
N/A
N/A
Range
N/A
N/A
• The alarm shall automatically connect
to the mains as it locks onto the mounting
base without the need to use a separate
wired connector.
• The alarm shall utilise thermally enhanced
optical technology which incorporates
an optical sensing chamber and thermal
enhancement components which make
adjustments to the sensitivity settings of
the alarm dependent upon background
temperature. Providing a quicker response
time to both slow smouldering, and fast
flaming fires.
• The alarm shall have the ability to hardwire
interconnect with up to 12 other smoke,
heat and CO alarms of a similar type on
a single network.
• MRL – The alarm shall operate on a 230V mains
power supply and have a built-in, sealed for
life, rechargeable lithium battery back-up to
power the alarm in the event of a mains failure.
• The alarm shall have a green LED mains
indicator to confirm mains power supply is on.
• The alarm is supplied with a PUSH-FIT
mounting base for ease of installation.
• The alarm shall disconnect from the mains
supply as it’s removed from the mounting
base with the use of a tool.
• The alarm shall have a low battery warning
signal, which will ‘chirp’ approximately
every 45 seconds. This will continue until
the alarm which has the low battery
condition is removed.
• The alarm shall be supplied with a dust
cover that can be fitted to protect it from
contamination during installation.
• The alarm shall have wireless interconnect
capability with the DS700RF wireless interlink
base, allowing up to 50 alarms of a similar
type to be wirelessly interlinked on a
single network.
• The alarm has a built in sounder giving a
minimum sound output of 85dB(A) at 3m.
• The alarm shall be supplied with installation /
user instructions.
• The alarm and base shall have the following
combined dimensions: 140mm dia. x 53mm
depth.
• The alarm shall have a separate red LED that
will flash approximately every 45 seconds to
confirm circuitry integrity.
• The alarm shall have an integral test / silence
button in order to test circuitry, sensor and
sounder and activate all interconnected alarms
in the system.
• The alarm shall have a silence feature which
allows the alarm to be silenced for up to 10
• MRL - The alarm and base shall have the
following combined weight: 304g.
• MBX - The alarm and base shall have the
following combined weight: 332g.
• The alarm shall have a 5 year warranty.
Kitchen & Garage
• MBX - The alarm shall operate on a 230V mains
power supply and shall be supplied with 9V
PP3 alkaline battery back-up to power the
alarm in the event of a mains failure.
minutes in the event of a known false alarm.
A red LED shall flash every 10 seconds to
indicate that the alarm is in ‘silence’ mode
and will automatically reset after
approximately 10 minutes.
Bedroom & Living Room
• The smoke alarm shall carry the BSI Kitemark
to indicate type testing to BS EN14604: 2005
and will meet the requirements of Grade D as
defined in BS 5839 Pt.6: 2013. The alarm shall
carry the CE mark to indicate conformance
to all of the applicable EC directives
including Low Voltage and Electromagnetic
Compatibility Directives.
Hallway, Landing,
Living Room & Bedroom
Product Specification
Key Technology
Test and alarm silence button
Two sensors provide
heat readings, to enable
early warning of fire
Accessories
PUSH-FIT
mounting base
CO Alarm
MRL - rechargeable lithium battery back-up
MBX - 9V alkaline battery back-up
Boiler Shut-off
Thermally enhanced
optical sensing chamber
Compatibility
Hallway
Landing
Living Room
Bedroom
Kitchen
Garage
CO
760
(MRL/MBX)
760
(MRL/MBX)
760
(MRL/MBX)
760
(MRL/MBX)
790
(MRL/MBX)
790
(MRL/MBX)
CO850
(MRLi/MBXi)
p18
Mains Smoke
p18
Mains Smoke
p18
770
(MRL/MBX)
Mains Smoke
p28
Mains Smoke
p18
770
(MRL/MBX)
Mains Smoke
Mains Heat
p38
Mains Heat
p38
Mains CO
p57
DS700RF
Wireless Interlink
Base
p49
Firefighting Equipment
Mains Smoke
Accessories
p28
19
WST-630T
Battery Powered Wireless Smoke Alarm
Grade
F - Battery powered
Sensor type
Thermoptek
Battery type
10 year sealed for life lithium
Key Features
• T
hermoptek sensing technology for fast detection of fires.
• 10 year sealed for life lithium battery.
• Large central button - test / Smart Silence / locate.
• Smart Silence - allows the alarm to be silenced for up to
10 minutes in the event of a known false alarm. During
these 10 minutes if additional smoke is detected the
alarm will sound.
• Locate feature - when the network goes into alarm
pressing the test button of any alarm will silence all but
the initiating alarm.
• Wi-Safe 2 technology - up to 50 Wi-Safe 2 alarms can be
interlinked on a single network.
EN14604:2005
C651d-09
0832
0832-CPD-1926
Smoke alarm devices
EN14604: 2005
Technical Specification
132mm
20
Dimensions
132mm (diameter) x 40.50mm (depth)
Supply voltage
3V DC
Battery
10 year sealed for life lithium
Technology
Thermoptek and Wi-Safe 2
Alarm sound level
85dB(A) at 3m (minimum)
Installation positions
Wall / Ceiling
Operating temperature
+4°C to +38°C
Operating humidity
Up to 90% RH non-condensing
Storage temperature
-20°C to +60°C
Storage humidity
Up to 93% RH non-condensing
Plastic material
ABS, UL94 VO fire retardant
Warranty
5 years
Master pack quantity
10
Weight
210g
Certified to
EN 14604: 2005
Independently tested to
ETSI EN 300 220-2 V2.3.2 (2010-02)
Maximum number of connected units
50 wireless units
Operating Frequency
868 MHz
Range
35m (over 200m in clear air)
40.50mm
• The smoke alarm shall carry the BSI Kitemark
to indicate type testing to BS EN14604: 2005
and will meets the requirements of Grade F as
defined in BS 5839 Pt.6: 2013. The alarm shall
carry the CE mark to indicate conformance
to all of the applicable EC directives
including Low Voltage and Electromagnetic
Compatibility Directives.
• Should the alarm enter a low power pack
condition, the unit will emit an audible ‘chirp’
approximately once every 45 seconds and the
amber LED will flash at around the same time.
• The alarm shall include a non-removable
integrated lithium battery which has a 10 year
life in normal operating conditions.
• The Wi-Safe 2 radio frequency shall be 868
MHz band in accordance with R&TTE Directive
1999/5/EC.
• The alarm shall have a built in sounder giving a
minimum sound output of 85dB(A) at 3m.
• The alarm shall be manufactured from ABS,
UL94 V0 fire retardant plastic.
• The alarm shall be supplied with installation /
user instructions.
• A simple 2 button process enables alarms to
communicate with each other on a unique
coded network. Additional units can be added
on the network using the same procedure.
• The alarm shall have the following dimensions:
132mm diam. x 40.50mm depth.
• The alarm shall feature ‘Smart Silence’
technology which allows the alarm to be
• The alarm shall have a 5 year warranty.
• The alarm shall have the following weight:
210g (including power pack).
Kitchen & Garage
• The alarm shall have a red LED on the front
which will flash approximately every 45
seconds to show that the alarm is active.
• The wireless Wi-Safe 2 module shall have a
separate 10 year sealed for life lithium battery
designed to outlast the usable life of the alarm.
• The alarm shall feature an intelligent locate
feature whereby pressing the test / silence
button on any alarm in the network will silence
all but the initiating alarm.
Bedroom & Living Room
• The alarm shall utilise multiple sensing
elements. Incorporating thermally enhanced
optical sensing technology (Thermoptek)
which constantly monitors for temperature
change. If a rate of temperature rise is
predicted to rise above a predetermined
threshold the sensitivity of the alarm is
increased, providing a quicker response time
to both slow smouldering and fast flaming fires
in a single alarm.
• The alarm shall incorporate a Wi-Safe 2
intelligent communication module as standard,
which wirelessly interlinks with up to 50 other
units with Wi-Safe 2 technology inside on a
single network. All units shall have the ability
to be learnt into a single network by an easy 2
button process.
silenced for up to 10 minutes in the event of a
known false alarm. After 10 minutes the alarm
shall return to full sensitivity. During these 10
minutes, if additional smoke is detected the
alarm silence will be overridden and the alarm
will sound.
Hallway, Landing,
Living Room & Bedroom
Product Specification
Key Technology
Two heat sensors
provide readings, to
enable early warning
of fire
Accessories
Mounting base
Large concave button
for test, smart silence
and locate
CO Alarm
Intelligent wireless
communication with up to
50 other Wi-Safe 2 products
Precision optical
sensors ensure
reduced false alarms
Boiler Shut-off
10 year sealed for life
lithium battery
Large sensing chamber
increases stability and
alarm accuracy
Hallway
Living Room
Bedroom
Kitchen
Garage
CO
Accessories
Battery Wireless
Smoke
Battery Wireless
Smoke
Battery Wireless
Smoke
Battery Wireless
Smoke
Battery Wireless
Heat
Battery Wireless
Heat
Battery Wireless
CO
Vibrating Pad &
Strobe
W2-SVP-630
W2-LFS-630
p20
p20
p20
p20
p40
p40
p58
p47
p48
WST-630T
Wireless
Landing
WST-630T
WST-630T
WST-630T
WHT-630
WHT-630
W2-CO-10X
Low Frequency
Sounder
Firefighting Equipment
Compatibility
21
ST-622T
Battery Powered Smoke Alarm
Grade
F - Battery powered
Sensor type
Thermoptek
Battery type
10 year sealed for life lithium
Key Features
• T
hermoptek sensing technology for fast detection
of fires.
• 10 year sealed for life lithium battery.
• Large central button - test / Smart Silence.
• Easy to install with automatic battery engagement
on base plate.
• Used and endorsed by UK Fire and Rescue Service.
•
Smart Silence - allows the alarm to be silenced for
up to 10 minutes in the event of a known false alarm.
During these 10 minutes if additional smoke is
detected the alarm will sound.
• Sleep Easy - allows a low battery chirp to be silenced
for 8 hours, this function can be used up to 10 times.
BSEN14604:2005
Licence No: KM 557789
Technical Specification
0086
0086-CPR-557790
Smoke alarm devices
EN14604: 2005
132mm
22
Dimensions
130mm (diameter) x 34mm (depth)
Supply voltage
3V DC
Battery
10 year sealed for life lithium battery
Technology
Thermoptek
Alarm sound level
85dB(A) at 3m (minimum)
Installation positions
Ceiling / Wall
Operating temperature
+4°C to +38°C
Operating humidity
Up to 90% RH non-condensing
Storage temperature
-20°C to +60°C
Storage humidity
Up to 93% RH non-condensing
Plastic material
ABS, UL94 VO fire retardant
Warranty
10 years
Master pack quantity
20
Weight
155g
Certified to
BS EN 14604: 2005
Independently tested to
N/A
Maximum number of connected units
N/A
Operating Frequency
N/A
Range
N/A
60mm
• The smoke alarm shall carry the BSI Kitemark
to indicate type testing to BS EN14604: 2005
and will meets the requirements of Grade F as
defined in BS 5839 Pt.6: 2013. The alarm shall
carry the CE mark to indicate conformance
to all of the applicable EC directives
including Low Voltage and Electromagnetic
Compatibility Directives.
• The alarm shall include a non-removable
integrated lithium battery which has a 10 year
life in normal operating conditions.
• The alarm shall have a low battery indication
in the form of an audible ‘chirp’ approximately
once every 40 seconds.
• The alarm shall incorporate ‘Sleep Easy’
functionality whereby a low battery chirp can
be silenced for a period of 8 hours by pressing
the test button on the smoke/heat alarm. This
function can be used up to 10 times.
• The alarm shall feature ‘Smart Silence’
technology which allows the alarm to be
silenced for up to 10 minutes in the event of a
known false alarm. After 10 minutes the alarm
shall return to full sensitivity. During these 10
minutes, if additional heat / smoke is detected
the alarm silence will be overridden and the
alarm will sound.
• The alarm shall have a built in sounder giving a
minimum sound output of 85dB(A) at 3m.
• The alarm shall be manufactured from ABS,
UL94 V0 fire retardant plastic.
• The alarm shall be supplied with installation /
user instructions.
• The alarm shall have the following dimensions:
130mm diam. x 34mm depth.
• The alarm shall have the following weight:
155g (including power pack).
• The alarm shall have a 10 year warranty.
Kitchen & Garage
Key Technology
Mounting base
Bedroom & Living Room
• The alarm shall utilise multiple sensing
elements. Incorporating thermally enhanced
optical sensing technology (Thermoptek)
which constantly monitors for temperature
change. If a rate of temperature rise is
predicted to rise above a predetermined
threshold the sensitivity of the alarm is
increased, providing a quicker response time
to both slow smouldering and fast flaming fires
in a single alarm.
• The alarm shall have a red LED on the front and
will flash approximately every 40 seconds to
show that the alarm is active.
Hallway, Landing,
Living Room & Bedroom
Product Specification
10 year sealed for life
lithium battery
Precision optical
sensors ensures
reduced false alarms
Large concave button
for test, smart silence
Accessories
CO Alarm
Two heat sensors provide
readings, to enable early
warning of fire
Large sensing chamber increases
stability and alarm accuracy
Boiler Shut-off
Firefighting Equipment
23
24
Bedroom &
Living Room
25
Solutions for:
Bedroom & Living Room (not suitable for Hallways & Landings)
Positioning of Smoke alarms
Smoke Alarms
Product Selector Table
Product code
26
Mains Powered Smoke Alarm
Mains Powered Smoke Alarm
770 MRL
770 MBX
Brand
BRK
BRK
Technology
Ionisation
Ionisation
Supply Voltage
230V AC, 50Hz
230V AC, 50Hz
Battery
Rechargeable lithium battery
9V alkaline battery
Warranty
5 years
5 years
Grade
D
D
Page
28
28
Hallway, Landing,
Living Room & Bedroom
This section is designed to provide smoke alarm solutions for living rooms and
bedrooms. The alarm selection has been made based on the sensing technology
used in the alarm and how effective it is at detecting fires that most commonly
occur in each of the rooms.
Mains:
• BRK mains powered smoke alarm (with optional RF base)
Bedroom & Living Room
 Excellent

Heat
Sources
Slow Smouldering
Thermoptek
Ionisation






Response
Temperature
Rapidly Rising
Temperature
Thermistek
Thermistor
Class A1
(54°C - 62°C)
Class A2
(54°C - 70°C)


Contamination





Kitchen Fumes





* For full guidance on what type of alarm to install and where consult BS5839-6
CO Alarm
Immunity
to:
Fast Flaming
Heat Alarms
Thermally
Enhanced Optical
Accessories
Smoke
Sources
Smoke Alarms
Poor
Kitchen & Garage
Summary of our Sensor Types*
Boiler Shut-off
Firefighting Equipment
27
770 MRL & 770 MBX
Mains Powered Smoke Alarm
Grade
D - Mains powered with battery back-up
Sensor type
Ionisation
Battery back-up type
MRL - Rechargeable lithium / MBX - 9V alkaline
Key Features
• Ionisation sensing technology.
• 230V mains powered.
• Battery back-up:
• MRL - 10 year sealed for life rechargeable
lithium battery.
• MBX- 9V alkaline battery.
• Hardwire interconnect with up to 12 units
of a similar type.
• Compatible with wireless interlink base.
• Supplied with PUSH-FIT mounting base.
• Central test and silence button.
BSEN14604:2005
Licence No: KM597992
Technical Specification
140mm
0086
0086-CPR-597993
EN14604: 2005
DoP 13/05
53mm
140mm
53mm
Dimensions
Product Code
28
140mm (diameter) x 53mm (depth)
140mm (diameter) x 53mm (depth)
770 MRL
770 MBX
Supply voltage
230V AC, 50Hz
230V AC, 50Hz
Battery back-up
Rechargeable lithium battery
9V alkaline battery
Technology
Ionisation
Ionisation
Alarm sound level
85dB(A) at 3m (minimum)
85dB(A) at 3m (minimum)
Installation positions
Ceiling / Wall
Ceiling / Wall
Operating temperature
+5°C to +38°C
+5°C to +38°C
Operating humidity
10% to 85% relative
10% to 85% relative
Storage temperature
+5°C to +38°C
+5°C to +38°C
Storage humidity
10% to 85% relative
10% to 85% relative
Plastic material
ABS, UL94 VO fire retardant
ABS, UL94 VO fire retardant
Warranty
5 years
5 years
Master pack quantity
10
10
Weight
262g
316g
Certified to
BS EN 14604: 2005
BS EN 14604: 2005
Independently tested to
N/A
N/A
Maximum number of connected units
12 hardwired units
12 hardwired units
Operating Frequency
N/A
N/A
Range
N/A
N/A
•
The smoke alarm shall carry the BSI Kitemark
to indicate type testing to BS EN14604: 2005
and will meet the requirements of Grade D as
defined in BS 5839 Pt.6: 2013. The alarm shall
carry the CE mark to indicate conformance
to all of the applicable EC directives
including Low Voltage and Electromagnetic
Compatibility Directives.
The alarm shall have a dual ionisation
chamber sensor, with corrosion resistant
electrodes and an insect resistant cover.
•
MRL - The alarm shall operate on a 230V
mains power supply and shall be supplied
with a built-in, sealed for life, rechargeable
lithium battery back-up to power the alarm in
the event of a mains failure.
•
MBX - The alarm shall operate on a 230V
mains power supply and shall be supplied
with 9V PP3 alkaline battery back-up to
power the alarm in the event of a mains
failure.
The alarm is supplied with a PUSH-FIT
mounting base for ease of installation.
•
The alarm shall automatically connect
to the mains as it lock onto the mounting
base without the need to use a separate
wired connector.
•
The alarm shall have the ability to hardwire
interconnect with up to 12 other smoke,
heat and CO alarms of a similar type on
a single network.
•
The alarm shall have wireless interconnect
capability with the DS700RF wireless
interlink base, increasing the number of
connected alarms to a maximum of 50.
•
The alarm shall have a green LED mains
indicator to confirm mains power supply
is on.
•
The alarm shall have a separate red LED
that will flash approximately every 45
seconds to confirm circuitry integrity.
•
The alarm shall have an integral test / silence
button in order to test circuitry, sensor and
sounder and activate all interconnected
alarms in the system.
•
The alarm shall have a silence feature which
allows the alarm to be silenced for up to 10
minutes in the event of a known false alarm.
A red LED shall flash every 10 seconds
to indicate that the alarm is in ‘silence’
mode and will automatically reset after
approximately 10 minutes.
•
The alarm shall have a low battery warning
signal, which will ‘chirp’ approximately
every 45 seconds. This will continue until
the alarm which has the low battery
condition is removed.
•
The alarm shall be supplied with a dust
cover fitted to protect it from contamination
during installation.
•
The alarm has a built in sounder giving a
minimum sound output of 85dB(A) at 3m.
•
The alarm shall be supplied with installation
/ user instructions.
•
The alarm and base shall have the following
combined dimensions: 140mm dia. x 53mm
depth.
•
MRL – The alarm and base shall have the
following combined weight: 262g.
•
MBX - The alarm and base shall have the
following combined weight: 316g.
Kitchen & Garage
•
The alarm shall disconnect from the mains
supply as it’s removed from the mounting
base with the use of a tool.
Bedroom & Living Room
•
•
Hallway, Landing,
Living Room & Bedroom
Product Specification
Key Technology
Accessories
PUSH-FIT
mounting base
Test and alarm
silence button
CO Alarm
Dual ionisation chamber
Boiler Shut-off
MRL - rechargeable lithium battery back-up
MBX - 9V alkaline battery back-up
Compatibility
Hallway
Landing
Living Room
Bedroom
Kitchen
Garage
CO
760
(MRL/MBX)
760
(MRL/MBX)
760
(MRL/MBX)
760
(MRL/MBX)
790
(MRL/MBX)
790
(MRL/MBX)
CO850
(MRLi/MBXi)
p18
Mains Smoke
p18
Mains Smoke
p18
770
(MRL/MBX)
Mains Smoke
p28
Mains Smoke
p18
770
(MRL/MBX)
Mains Smoke
Mains Heat
p38
Mains Heat
p38
Mains CO
p57
DS700RF
Wireless Interlink
Base
p49
Firefighting Equipment
Mains Smoke
Accessories
p28
29
30
Kitchen &
Garage
31
Solutions for:
Kitchen & Garage
Positioning of Heat alarms
Heat Alarms
Product Selector Table
Mains Powered
Wireless Heat Alarm
32
Mains Powered
Heat Alarm
Mains Powered
Heat Alarm
Product code
WHM-SN-1
HM-SN-1
790 MRL
Brand
SONA
SONA
BRK
Technology
Thermistek and Wi-Safe 2
Thermistek
Advanced Thermistor
Supply Voltage
230V AC, 50Hz
230V AC, 50Hz
230V AC, 50Hz
Battery
10 year sealed for life lithium
battery back-up
10 year sealed for life lithium
battery back-up
Rechargeable lithium battery
back-up
Warranty
5 years
5 years
5 years
Grade
D
D
D
Page
34
36
38
Bedroom & Living Room
Included in this section are comprehensive alarm ranges including both mains and battery options,
providing solutions for most installation scenarios.
Hallway, Landing,
Living Room & Bedroom
This section is designed to provide heat alarm solutions for kitchens and garages.
The alarm selections have been made based on the sensing technologies used in each
of the alarms and how effective they are at detecting fires that most commonly occur
in each of these rooms.
Mains:
• SONA mains powered wireless heat alarm
• SONA mains powered heat alarm
• BRK mains powered heat alarm (with optional RF base)
Battery:
• FireAngel battery powered wireless heat alarm
Summary of our Sensor Types*
 Excellent

Heat
Sources
Slow Smouldering
Thermoptek
Ionisation






Response
Temperature
Rapidly Rising
Temperature
Thermistek
Thermistor
Class A1
(54°C - 62°C)
Class A2
(54°C - 70°C)


Contamination





Kitchen Fumes





* For full guidance on what type of alarm to install and where consult BS5839-6
Battery Powered
Wireless Heat Alarm
Battery Powered
Heat Alarm
790 MBX
WHT-630
HT-630
BRK
FireAngel
FireAngel
Technology
Advanced Thermistor
Thermistek and Wi-Safe 2
Thermistek
Supply Voltage
230V AC, 50Hz
3V DC
3V DC
Battery
9V alkaline battery
back-up
10 year sealed for life lithium
battery
10 year sealed for life lithium
battery
Warranty
5 years
5 years
10 years
Grade
D
F
F
Page
38
40
42
Firefighting Equipment
Product code
Brand
Boiler Shut-off
Mains Powered
Heat Alarm
CO Alarm
Immunity
to:
Fast Flaming
Heat Alarms
Thermally
Enhanced Optical
Accessories
Smoke
Sources
Smoke Alarms
Poor
Kitchen & Garage
• FireAngel battery powered heat alarm
33
WHM-SN-1
Mains Powered Wireless Heat Alarm
Grade
D - Mains powered with battery back-up
Sensor type
Thermistek
Battery back-up type
10 year sealed for life lithium
Key Features
• Thermistek technology, incorporating a unique
radiant heat dish.
• 10 year sealed for life lithium battery back-up.
• L
ow energy usage - typically less than 10% of the
average 230V AC alarm.
• Wi-Safe 2 technology - up to 50 Wi-Safe 2 alarms
can be interlinked on a single network.
• Ultra slim, integrated mounting base.
• Centralised button - test / silence / locate.
• Secondary buzzer.
• Mixed system compatibility:
• Wireless and hardwired.
• Mains and battery powered alarms.
Technical Specification
BS 5446-2: 2003
Licence No: KM607094
Wi-Safe 2 module contained within WHM-SN-1
independently tested to RF standard ETSI EN 300
220-2 V2.3.2 (2010-02) byTRaC Global Ltd
EN300489-1 &-3 / EN300220-2 - Radio
141.5mm
34
Dimensions
141.5mm (diameter) x 53mm (height)
Supply voltage
230V AC, 50Hz
Battery back-up
10 year sealed for life lithium battery
Technology
Thermistek and Wi-Safe 2
Alarm sound level
85dB(A) at 3m (minimum)
Installation positions
Ceiling
Alarms at temperature range
+54°C to +62°C
Operating temperature
+4°C to +38°C
Operating humidity
Up to 90% RH non-condensing
Storage temperature
-20°C to +60°C
Storage humidity
Up to 93% RH non condensing
Plastic material
ABS, UL94 VO fire retardant
Warranty
5 years
Master pack quantity
4
Weight
290g
Certified to
BS 5446-2: 2003
Independently tested to
ETSI EN 300 220-2 V2.3.2 (2010-02), EN300489-1 &-3, EN300220-2 – Radio
Maximum number of connected units
50 wireless units
Operating Frequency
868 MHz
Range
35m (over 200m in clear air)
53mm
• The heat alarm shall carry the BSI Kitemark
to indicate type testing to BS 5446-2: 2003.
It will meet the requirements of Grade D as
defined in BS 5839 Pt.6: 2013 for a Class A1
device. The alarm shall carry the CE mark to
indicate conformance to all of the applicable
EC directives including; Low Voltage and
Electromagnetic Compatibility Directives.
• The alarm shall have Thermistek technology
which incorporates a unique radiant heat
dish to heighten the performance of the alarm
when exposed to a radiant heat source in real
fire situations.
• The alarm shall automatically connect to the
mains as it locks onto the mounting base and
disconnect from the mains as soon as it’s
removed from the mounting base with a tool.
• The wireless Wi-Safe 2 module shall have a
separate 10 year sealed for life lithium battery
designed to outlast the usable life of the alarm.
• The mounting base shall have a factory fitted
foam gasket to prevent air draughts and dust
ingress into the rear of the unit.
• The Wi-Safe 2 radio frequency shall be 868
MHz band in accordance with R&TTE Directive
1999/5/EC.
• The alarm shall have a built in sounder giving a
minimum sound output of 85dB(A) at 3m.
• The alarm shall be capable of working on
a mixed system to include both hardwire
interconnect and wireless interlink alarms,
across both mains and battery powered
products of a similar type.
• The alarm shall incorporate a large central test
/ silence button to test circuitry, sensor and
sounder and activate all interconnected alarms
in the system.
• The alarm shall have a low battery warning
signal, which will ‘chirp’ every 45 seconds for
at least 30 days to indicate when a replacement
of the alarm is required. All other alarms on the
network shall also emit an audible low battery
chirp once every 4 hours.
• The alarm shall be energy efficient with an
operational power consumption of no more
than 4.29kW over its 10 year lifetime.
• The alarm shall operate on a 230V mains
power supply and have a single built in, tamper
proof, sealed for life 10 year lithium battery
back-up to power the alarm in the event of
a mains failure.
• The alarm shall have a secondary buzzer fitted
to ensure fail-safe operation.
• The alarm shall incorporate ‘Sleep Easy’
functionality whereby a low battery chirp can
be silenced for a period of 8 hours by pressing
the test button on the alarm. This function can
be used up to 10 times.
• The alarm shall feature an intelligent locate
feature whereby pressing the test / silence
button on any alarm in the network will silence
all but the initiating alarm.
• The alarm shall feature a silence function
which allows the alarm to be silenced in the
event of a known false alarm.
• The alarm shall be supplied with a dust cover
fitted to protect it from contaminants during
installation.
• The alarm shall be supplied with a quick-fitting
surface mounting base with a depth of no
more than 5mm with integral terminal block
Low energy usage
typically less than
10% of the average
AC smoke alarm
Predictive algorithm
determines the rate
of rise to decrease
time to alarm
Radiant heat dish,
increasing the
alarms reaction time
Accessories
Key Technology
Slim integrated
mounting base
Kitchen & Garage
• The alarm shall incorporate a predictive
rate of rise algorithm that constantly monitors
for temperature change. If an increase
in temperature is detected and predicted
to exceed a predetermined threshold the
alarm shall activate. This feature provides
a quicker response time in rapidly
increasing temperatures.
and cable cover. Cable knock outs allow for
compatibility with YT2 cable trunking.
Bedroom & Living Room
• The alarm shall be a fixed point heat alarm,
with a temperature range of 54°C to 62°C.
• The alarm shall incorporate a Wi-Safe 2
intelligent communication module as standard,
which wirelessly interlinks with up to 50 other
units with Wi-Safe 2 technology inside on a
single network. All units shall have the ability
to be learnt into a single network by an easy 2
button process.
Hallway, Landing,
Living Room & Bedroom
Product Specification
Central button
combined with
durable sensor
shield
CO Alarm
Intelligent wireless communication with
up to 50 other Wi-Safe 2 products
Secondary buzzer
Boiler Shut-off
10 year sealed for life
lithium battery back-up
High performance
thermistor
Compatibility
Hallway
Non-Wireless
p14
SM-SN-1
Mains Smoke
p16
WSM-SN-1
Mains Wireless
Smoke
p14
SM-SN-1
Mains Smoke
p16
Living Room
WSM-SN-1
Mains Wireless
Smoke
p14
SM-SN-1
Mains Smoke
p16
Bedroom
WSM-SN-1
Mains Wireless
Smoke
p14
SM-SN-1
Mains Smoke
p16
Kitchen
WHM-SN-1
Mains Wireless
Heat
p34
HM-SN-1
Mains Heat
p36
Garage
CO
WHM-SN-1
Mains Wireless
Heat
p34
HM-SN-1
Mains Heat
Accessories
WCOB-SN-1
W2-SVP-630
Battery Wireless
CO
Vibrating Pad &
Strobe
p56
p47
W2-LFS-630
Low Frequency
Sounder
p48
Firefighting Equipment
Wireless
WSM-SN-1
Mains Wireless
Smoke
Landing
p36
35
HM-SN-1
Mains Powered Heat Alarm
Grade
D - Mains powered with battery back-up
Sensor type
Thermistek
Battery back-up type
10 year sealed for life lithium
Key Features
• Thermistek technology, incorporating a unique
radiant heat dish.
• 10 year sealed for life lithium battery back-up.
• L
ow energy usage - typically less than 10% of the
average 230V AC alarm.
• Ultra slim, integrated mounting base.
• Centralised button - test / Smart Silence / locate.
• Secondary buzzer.
• Mixed system compatibility:
• Wireless and hardwired
• Mains and battery powered alarms
BS 5446 part 2:2003
Licence No: KM 607094
Technical Specification
141.5mm
36
Dimensions
141.5mm (diameter) x 53mm (depth)
Supply voltage
230V AC, 50Hz
Battery back-up
10 year sealed for life lithium battery
Technology
Thermistek
Alarm sound level
85dB(A) at 3m (minimum)
Installation positions
Ceiling
Alarms at temperature range
+54°C to +62°C
Operating temperature
+4°C to +38°C
Operating humidity
Up to 90% RH non-condensing
Storage temperature
-20°C to +60°C
Storage humidity
Up to 93% RH non-condensing
Plastic material
ABS, UL94 VO fire retardant
Warranty
5 years
Master pack quantity
4
Weight
264g
Certified to
BS 5446-2: 2003
Independently tested to
N/A
Maximum number of connected units
30 hardwired units
Operating Frequency
N/A
Range
N/A
53mm
• The heat alarm shall carry the BSI Kitemark
to indicate type testing to BS 5446-2: 2003.
It will meet the requirements of Grade D as
defined in BS 5839 Pt.6: 2013 for a Class A1
device. The alarm shall carry the CE mark to
indicate conformance to all of the applicable
EC directives including; Low Voltage and
Electromagnetic Compatibility Directives.
• The alarm shall operate on a 230V mains
power supply and have a single built in, tamper
proof, sealed for life, 10 year lithium battery
back-up to power the alarm in the event of
a mains failure.
• The alarm shall be capable of working on
a mixed system to include both hardwire
interconnect and wireless interlink alarms,
across both mains and battery powered
products of a similar type.
• The alarm shall incorporate a predictive
rate of rise algorithm that constantly
monitors for temperature change. If an
increase in temperature is detected
and predicted to exceed a predetermined
threshold the alarm shall activate. This
feature provides a quicker response time
in rapidly increasing temperatures.
• The alarm shall have a low battery warning
signal, which will ‘chirp’ every 45 seconds for
at least 30 days to indicate when a replacement
of the alarm is required. All other alarms on the
network shall also emit an audible low battery
chirp once every 4 hours.
• The alarm shall be energy efficient with an
operational power consumption of no more
than 4.29kW over its 10 year lifetime. Ensuring
low running costs over the alarms 10 year life.
• The alarm shall carry a proven carbon footprint
of 13.6kgCO2e over its 10 year lifetime.
• The alarm shall incorporate a diagnostic
function which monitors alarm activations
and facilitates fault finding.
• The alarm shall have a built in sounder giving
a minimum sound output of 85dB(A) at 3m.
• The alarm shall have a secondary buzzer
fitted to ensure fail-safe operation in all
circumstances.
• The alarm shall incorporate ‘Sleep Easy’
functionality whereby a low battery chirp can
be silenced for a period of 8 hours by pressing
the test button on the alarm. This function can
be used up to 10 times.
• The alarm shall be supplied with a quick-fitting
surface mounting base with a depth of no
more than 5mm with integral terminal block
and cable cover. Cable knock outs allow for
compatibility with YT2 cable trunking.
• The alarm shall incorporate a large central test
/ silence button to test circuitry, sensor and
sounder and activate all interconnected alarms
in the system.
• The alarm shall feature an intelligent locate
feature whereby pressing the test / silence
button on any alarm in the network will silence
all but the initiating alarm.
• The alarm shall feature a silence function
which allows the alarm to be silenced in the
event of a known false alarm.
• The alarm shall be supplied with a dust cover
fitted to protect it from contaminants during
installation.
Slim integrated
mounting base
Low energy usage
typically less than
10% of the average
AC smoke alarm
Secondary buzzer
Radiant heat dish,
increasing the
alarms reaction time
Accessories
Key Technology
Kitchen & Garage
• The alarm shall have Thermistek technology
which incorporates a unique radiant heat dish
to heighten the performance of the alarm when
exposed to a radiant heat source in real fire
situations.
• The mounting base shall have a factory fitted
foam gasket to prevent air draughts and dust
ingress into the rear of the unit.
Bedroom & Living Room
• The alarm shall be a fixed point heat alarm,
with a temperature range of 54°C to 62°C.
• The alarm shall have the ability to hardwire
interconnect with up to 30 other smoke and
heat alarms of a similar type on a single
network. When one alarm sound all other
alarms on the network will sound.
• The alarm shall automatically connect to the
mains as it locks onto the mounting base and
disconnect from the mains as soon as it’s
removed from the mounting base with a tool.
Hallway, Landing,
Living Room & Bedroom
Product Specification
Central button
combined with
durable sensor
shield
CO Alarm
Predictive algorithm determines
the rate of rise to decrease time
to alarm
Compatibility
Hallway
Non-Wireless
p14
SM-SN-1
Mains Smoke
p16
WSM-SN-1
Mains Wireless
Smoke
p14
SM-SN-1
Mains Smoke
p16
Living Room
WSM-SN-1
Mains Wireless
Smoke
p14
SM-SN-1
Mains Smoke
p16
Bedroom
WSM-SN-1
Mains Wireless
Smoke
p14
SM-SN-1
Mains Smoke
p16
Kitchen
WHM-SN-1
Mains Wireless
Heat
p34
HM-SN-1
Mains Heat
p36
Garage
CO
WHM-SN-1
Mains Wireless
Heat
p34
HM-SN-1
Mains Heat
Accessories
WCOB-SN-1
W2-SVP-630
Battery Wireless
CO
Vibrating Pad &
Strobe
p56
p47
W2-LFS-630
Low Frequency
Sounder
p48
Firefighting Equipment
Wireless
WSM-SN-1
Mains Wireless
Smoke
Landing
High performance
thermistor
Boiler Shut-off
10 year sealed for life
lithium battery back-up
p36
37
790 MRL & 790 MBX
Mains Powered Heat Alarm
Grade
D - Mains powered with battery back-up
Sensor type
Thermistor
Battery back-up type
MRL - Rechargeable lithium / MBX - 9V alkaline
Key Features
• Advanced Class A2 thermistor sensing technology.
• 230V mains powered.
• Battery back-up:
• MRL - 10 year sealed for life rechargeable
lithium battery.
• MBX- 9V alkaline battery.
• Hardwire interconnect with up to 12 units
of a similar type.
• Compatible with wireless interlink base.
• Supplied with PUSH-FIT mounting base.
• Central test and silence button.
BS5446-2:20035
Licence No: 14LHK0079
Technical Specification
140mm
68mm
140mm
68mm
Dimensions
140mm (diameter) x 68mm (depth)
38
140mm (diameter) x 68mm (depth)
Product Code
790 MRL
790 MBX
Supply voltage
230V AC, 50Hz
230V AC, 50Hz
Battery back-up
Rechargeable lithium battery
9V alkaline battery
Technology
Advanced Thermistor
Advanced Thermistor
Alarm sound level
85dB(A) at 3m (minimum)
85dB(A) at 3m (minimum)
Installation positions
Ceiling
Ceiling
Alarms at temperature range
+54°C to +70°C
+54°C to +70°C
Operating temperature
+5°C to +38°C
+5°C to +38°C
Operating humidity
10% to 85% relative
10% to 85% relative
Storage temperature
+5°C to +38°C
+5°C to +38°C
Storage humidity
10% to 85% relative
10% to 85% relative
Plastic material
ABS, UL94 VO fire retardant
ABS, UL94 VO fire retardant
Warranty
5 years
5 years
Master pack quantity
10
10
Weight
340g
377g
Certified to
BS 5446-2: 2003
BS 5446-2: 2003
Independently tested to
N/A
N/A
Maximum number of connected units
12 hardwired units
12 hardwired units
Operating Frequency
N/A
N/A
Range
N/A
N/A
•
•
The alarm shall disconnect from the mains
supply as it’s removed from the mounting
base with the use of a tool.
•
The alarm shall have the ability to hardwire
interconnect with up to 12 other smoke, heat
and CO alarms of a similar type on a single
network.
•
The alarm shall be a fixed point heat alarm,
with a temperature range of 54°C to 70°C.
•
•
MRL – The alarm shall operate on a 230V
mains power supply and have a built-in,
sealed for life, rechargeable lithium battery
back-up to power the alarm in the event of a
mains failure.
The alarm shall have wireless interconnect
capability with the DS700RF wireless
interlink base, allowing up to 50 alarms of a
similar type to be wirelessly interlinked on a
single network.
•
The alarm shall have a green LED mains
indicator to confirm mains power supply
is on.
•
MBX – The alarm shall operate on a 230V
mains power supply and shall be supplied
with 9V PP3 alkaline battery back-up
to power the alarm in the event of a
mains failure.
The alarm is supplied with a PUSH-FIT
mounting base for ease of installation.
•
The alarm shall automatically connect to the
mains as it locks onto the mounting base
without the need to use a separate wired
connector.
•
The alarm shall have a separate red LED that
will flash approximately every 45 seconds to
confirm circuitry integrity.
•
The alarm shall have an integral test / silence
button in order to test circuitry, sensor and
sounder and activate all interconnected
alarms in the system.
•
The alarm shall have a silence feature which
allows the alarm to be silenced for up to 10
minutes in the event of a known false alarm.
A red LED shall flash every 10 seconds
•
The alarm shall have a low battery warning
signal, which will ‘chirp’ approximately
every 45 seconds. This will continue until
the alarm which has the low battery
condition is removed.
•
The alarm shall be supplied with a dust
cover that can be fitted to protect it from
contamination during installation.
•
The alarm has a built in sounder giving a
minimum sound output of 85dB(A) at 3m.
•
The alarm shall be supplied with installation
/ user instructions.
•
The alarm and base shall have the following
combined dimensions: 140mm dia. x 68mm
depth.
•
MRL – The alarm and base shall have the
following combined weight: 286g.
•
MBX – The alarm and base shall have the
following combined weight: 304g.
•
The alarm shall have a 5 year warranty.
Kitchen & Garage
•
to indicate that the alarm is in ‘silence’
mode and will automatically reset after
approximately 10 minutes.
Bedroom & Living Room
The heat alarm shall carry the BSI Kitemark
to indicate type testing to BS 5446-2: 2003.
It will meet the requirements of Grade D as
defined in BS 5839 Pt.6: 2013 for a Class A2
device. The alarm shall carry the CE mark to
indicate conformance to all of the applicable
EC directives including; Low Voltage and
Electromagnetic Compatibility Directives.
Hallway, Landing,
Living Room & Bedroom
Product Specification
Key Technology
Accessories
PUSH-FIT
mounting base
Central test button and
robust sensor shield
CO Alarm
High performance
thermistor
Boiler Shut-off
MRL - rechargeable
lithium battery back-up
MBX - 9V alkaline battery
back-up
Compatibility
Hallway
Landing
Living Room
Bedroom
Kitchen
Garage
CO
760
(MRL/MBX)
760
(MRL/MBX)
760
(MRL/MBX)
760
(MRL/MBX)
790
(MRL/MBX)
790
(MRL/MBX)
CO850
(MRLi/MBXi)
p18
Mains Smoke
p18
Mains Smoke
p18
770
(MRL/MBX)
Mains Smoke
p28
Mains Smoke
p18
770
(MRL/MBX)
Mains Smoke
Mains Heat
p38
Mains Heat
p38
Mains CO
p57
DS700RF
Wireless Interlink
Base
p49
Firefighting Equipment
Mains Smoke
Accessories
p28
39
WHT-630T
Battery Powered Wireless Heat Alarm
Grade
F - Battery powered
Sensor type
Thermistek
Battery type
10 year sealed for life lithium
Key Features
• T
hermistek technology, incorporating a unique
radiant heat dish.
• Class A1 device.
• 10 year sealed for life lithium battery.
• Large central button - test / silence / locate.
• Silence function - allows the alarm to be silenced in
the event of a known false alarm.
• Locate function -when the network goes into alarm
pressing the test button will silence all but the
initiating alarm.
• Wi-Safe 2 technology - up to 50 Wi-Safe 2 alarms can
be interlinked on a single network.
Technical Specification
BS 5446 part 2:2003
KM 607094
132mm
40
Dimensions
132mm (diameter) x 60mm (depth)
Supply voltage
3V DC
Battery
10 year sealed for life lithium battery
Technology
Thermistek and Wi-Safe 2
Alarm sound level
85dB(A) at 3m (minimum)
Installation positions
Ceiling
Alarms at temperature range
+54°C to +62°C
Operating temperature
+4°C to +38°C
Operating humidity
Up to 90% RH non-condensing
Storage temperature
-20°C to +60°C
Storage humidity
Up to 93% RH non-condensing
Plastic material
ABS, UL94 VO fire retardant
Warranty
5 years
Master pack quantity
10
Weight
204g
Certified to
BS 5446-2: 2003
Independently tested to
ETSI EN 300 220-2 V2.3.2 (2010-02)
Maximum number of connected units
50 wireless units
Operating Frequency
868MHz
Range
35m (over 200m in clear air)
60mm
•
The heat alarm shall carry the BSI Kitemark
to indicate type testing to BS 5446-2: 2003
and will meet the requirements of Grade F as
defined in BS 5839 Pt.6: 2013 for a class A1
device. The alarm shall carry the CE mark to
indicate conformance to all of the applicable
EC directives including Low Voltage and
Electromagnetic Compatibility Directives.
The alarm shall be a fixed point heat alarm,
with a temperature range of 54°C to 62°C.
•
The alarm shall have Thermistek technology
which incorporates a unique radiant heat
dish to heighten the performance of the
alarm when exposed to a radiant heat source
in real fire situations.
•
•
Should the alarm enter a low power pack
condition, the unit will emit an audible
‘chirp’ approximately once every 45 seconds
and the amber LED will flash at around the
same time.
•
The alarm shall incorporate a predictive rate
of rise algorithm that constantly monitors
for temperature change. If an increase in
temperature is detected and predicted
to exceed a predetermined threshold the
alarm shall activate. This feature provides a
quicker response time in rapidly increasing
temperatures.
•
A simple 2 button process enables alarms to
communicate with each other on a unique
coded network. Additional units can be
added to the network using the
same procedure.
• The alarm shall feature a silence function
which allows the alarm to be silenced in the
event of a known false alarm.
The alarm shall incorporate a Wi-Safe 2
intelligent communication module as
standard, which wirelessly interlinks with up
to 50 other units with Wi-Safe 2 technology
inside on a single network. All units shall
have the ability to be learnt into a single
network by an easy 2 button process.
•
The alarm shall have a built in sounder giving
a minimum sound output of 85dB(A) at 3m.
•
The alarm shall be manufactured from ABS,
UL94 V0 fire retardant plastic.
•
The alarm shall be supplied with installation
/ user instructions.
•
The wireless Wi-Safe 2 module shall have
a separate 10 year sealed for life lithium
battery designed to outlast the usable life of
the alarm.
•
The alarm shall have the following
dimensions: 132mm diam. x 60mm depth.
•
•
The Wi-Safe 2 radio frequency shall be
868 MHz band in accordance with R&TTE
Directive 1999/5/EC.
The alarm shall have the following weight:
204g (including power pack).
•
The alarm shall have a 5 year warranty.
Kitchen & Garage
•
The alarm shall have a red LED on the front
which will flash approximately every 45
seconds to show that the alarm is active.
Bedroom & Living Room
•
•
Hallway, Landing,
Living Room & Bedroom
Product Specification
The alarm shall include a non-removable
integrated lithium battery which has a 10
year life in normal operating conditions.
Key Technology
Mounting base
Radiant heat dish, increasing
the alarms reaction time
Central button combined
with durable sensor shield
Accessories
CO Alarm
10 year sealed for life
lithium battery
Intelligent wireless
communication with
up to 50 other Wi-Safe
2 products
Predictive algorithm
determines the rate
of rise to decrease
time to alarm
High performance thermistor
Boiler Shut-off
Hallway
Living Room
Bedroom
Kitchen
Garage
CO
Accessories
Battery Wireless
Smoke
Battery Wireless
Smoke
Battery Wireless
Smoke
Battery Wireless
Smoke
Battery Wireless
Heat
Battery Wireless
Heat
Battery Wireless
CO
Vibrating Pad &
Strobe
W2-SVP-630
W2-LFS-630
p20
p20
p20
p20
p40
p40
p58
p47
p48
WST-630T
Wireless
Landing
WST-630T
WST-630T
WST-630T
WHT-630
WHT-630
W2-CO-10X
Low Frequency
Sounder
Firefighting Equipment
Compatibility
41
HT-630T
Battery Powered Heat Alarm
Grade
F - Battery powered
Sensor type
Thermistek
Battery type
10 year sealed for life lithium
Key Features
• T
hermistek technology, incorporating a unique
radiant heat dish.
• Class A1 device.
• 10 year sealed for life lithium battery.
• Large central button - test or silence.
• Silence function - allows the alarm to be silenced
in the event of a known false alarm.
BS 5446 part 2:2003
KM 607094
Technical Specification
132mm
42
Dimensions
132mm (diameter) x 60mm (depth)
Supply voltage
3V DC
Battery
10 year sealed for life lithium battery
Technology
Thermistek
Alarm sound level
85dB(A) at 3m (minimum)
Installation positions
Ceiling
Alarms at temperature range
+54°C to +62°C
Operating temperature
+4°C to +38°C
Operating humidity
Up to 90% RH non-condensing
Storage temperature
-20°C to +60°C
Storage humidity
Up to 93% RH non-condensing
Plastic material
ABS, UL94 VO fire retardant
Warranty
10 years
Master pack quantity
10
Weight
177g
Certified to
BS 5446-2: 2003
Independently tested to
N/A
Maximum number of connected units
N/A
Operating Frequency
N/A
Range
N/A
60mm
•
The heat alarm shall carry the BSI Kitemark
to indicate type testing to BS 5446-2: 2003
and will meet the requirements of Grade F as
defined in BS 5839 Pt.6: 2013 for a class A1
device. The alarm shall carry the CE mark to
indicate conformance to all of the applicable
EC directives including Low Voltage and
Electromagnetic Compatibility Directives.
The alarm shall be a fixed point heat alarm,
with a temperature range of 54 °C to 62 °C.
•
The alarm shall have Thermistek technology
which incorporates a unique radiant heat
dish to heighten the performance of the
alarm when exposed to a radiant heat source
in real fire situations.
•
•
The alarm shall have a red LED on the front
which will flash approximately every 45
seconds to show that the alarm is active.
•
•
The alarm shall have the following
dimensions: 132mm diam. x 60mm depth.
•
The alarm shall have the following weight:
177g (including power pack).
•
The alarm shall have a 10 year warranty.
Should the alarm enter a low power pack
condition, the unit will emit an audible
‘chirp’ approximately once every 45 seconds
and the amber LED will flash at around the
same time.
• The alarm shall feature a silence function
which allows the alarm to be silenced in the
event of a known false alarm.
•
The alarm shall have a built in sounder giving
a minimum sound output of 85dB(A) at 3m.
•
The alarm shall be manufactured from ABS,
UL94 V0 fire retardant plastic.
•
The alarm shall be supplied with installation
/ user instructions.
Kitchen & Garage
The alarm shall incorporate a predictive rate
of rise algorithm that constantly monitors
for temperature change. If an increase in
temperature is detected and predicted to
exceed a pre-determined threshold the
alarm shall activate. This feature provides
a quicker response time in rapidly
increasing temperatures.
The alarm shall include a non-removable
integrated lithium battery which has a 10
year life in normal operating conditions.
Bedroom & Living Room
•
•
Hallway, Landing,
Living Room & Bedroom
Product Specification
Key Technology
Mounting base
Radiant heat dish, increasing
the alarms reaction time
Central button combined
with durable sensor shield
Accessories
CO Alarm
10 year sealed for life
lithium battery
Predictive algorithm
determines the rate of
rise to decrease time to
alarm
High performance thermistor
Boiler Shut-off
Firefighting Equipment
43
44
Accessories
45
WTSL-SN-1
Wireless Alarm Control Unit
Key Features
• 10 year sealed for life alkaline battery.
• A remote interface between up to 50 Wi-Safe 2 units.
• T
est function - allows you to test all interlinked alarms from
one centralised location.
• Silence function - silence all interlinked smoke and
heat alarms.
An alarm cannot be silenced if CO has been detected,
however the locate function allows the initiating CO
alarm to be located.
• L
ocate function - silence all wirelessly interlinked alarms
except the initiating alarm.
• M
emory function - if one of the alarm indicators is flashing
every 10 seconds a smoke, heat or CO alarm
has been activated.
• Separate fire and CO alarm identifications.
Wi-Safe 2 module contained within WTSL-SN-1
independently tested to RF standard ETSI EN 300
220-2 V2.3.2 (2010-02) byTRaC Global Ltd
EN300489-1 &-3 / EN300220-2 - Radio
Technical Specification
90mm
46
90mm (width) x 90mm (height) x 22.5mm (depth)
Supply voltage
3V DC
Battery
10 year sealed for life alkaline battery
Installation positions
Wall / Portable
Operating temperature
+4°C to +38°C
Operating humidity
Up to 90% RH non-condensing
Storage temperature
-20°C to +60°C
Storage humidity
Up to 93% RH non-condensing
Plastic material
ABS, UL94 VO fire retardant
Warranty
5 years
Master pack quantity
4
Weight
142g
Certified to
BS EN 60065: 2002
Independently tested to
IEC 600: 2001 (seventh edition) + A11: 2008 + A12: 2011
Maximum number of connected units
50 wireless units
Operating Frequency
868 MHz
Range
35m (over 200m in clear air)
90mm
Dimensions
22.5mm
W2-SVP-630
Strobe & Vibrating Pad
• Compatible with and activated by any Wi-Safe 2 product.
• Mains powered with rechargeable battery back-up.
• Designed to provide additional protection to those with
hearing loss, who may not hear the audible alarm from
a smoke, heat or carbon monoxide alarm.
• Will activate if smoke or CO triggers any alarm in
the network.
• Will detect and indicate a low battery warning with any
smoke, heat or CO alarm within the network.
• Enables low level testing of all interlinked products in the
network, avoiding the need to reach up to ceiling mounted
alarms to test.
Kitchen & Garage
• Can be wall mounted or free standing, offering flexibility
in positioning.
Bedroom & Living Room
• The flashing strobe provides a visual warning for waking
hours, while the vibrating pad may be placed under a
pillow or mattress, and is suitable for waking someone
to alert them when a smoke alarm sounds.
Hallway, Landing,
Living Room & Bedroom
Key Features
Technical Specification
Pad:
98mm (diameter)
x 34mm (depth)
98mm
34mm
150mm
Dimensions
39.3mm
Accessories
102mm
Strobe:
102mm (height)
x 150mm (width)
x 39.3mm (depth)
Rechargeable 5 year NI-MH battery
Technology
Wi-Safe 2
Alarm sound level
N/A
Installation positions
Flashing strobe: wall or free-standing
Vibrating pad: under pillow, mattress or seating cushion
Operating temperature
+4°C to +38°C
Operating humidity
Up to 90% RH non-condensing
Storage temperature
-20°C to 60°C
Storage humidity
Up to 93% RH non condensing
Plastic material
ABS, UL94 VO fire retardant
Warranty
5 years
Master pack quantity
10
Weight
460g
Certified to
N/A
Independently tested to
EN 301489-1 v1.9.2 (2011-09)
EN 301489-3 v1.4.1 (2002-08)
EN 300220-2 v2.3.2 (2010-12)
Maximum number of connected units
50 wireless units
Operating Frequency
868 MHz
Range
35m (over 200m in clear air)
Firefighting Equipment
Battery back-up
Boiler Shut-off
230V AC, 50Hz
CO Alarm
Supply voltage
47
W2-LFS-630
Low Frequency Sounder
Key Features
• Compatible with any Wi-Safe 2 product.
• Mains powered with rechargeable battery back-up.
• Provides additional protection by sounding loud blasts
at a low frequency signal more likely to wake up high risk
individuals including children, those with mild to moderate
hearing loss, older people and people under the influence
of alcohol than a regular smoke alarm.*
• Emits a 520HZ square wave at a volume of 85dB(A)
at 3m and the red ‘alarm’ LED will also illuminate.
• Will activate if smoke or CO triggers any alarm in the
network.
• Will detect and indicate a low battery warning with
any smoke, heat or CO alarm within the network.
• Can be wall mounted or free standing, offering flexibility
in positioning.
• Enables low level testing of all interlinked products in the
network, avoiding the need to reach up to ceiling mounted
alarms to test.
Technical Specification
*(Bruck, D. & Thomas, I (2007) Waking effectiveness of alarms (auditory,visual
and tactile) for adults who are hard of hearing. Optimizing FireAlarm Notification
for High Risk Groups Research Project. pp.43.
198mm
48
198mm (width) x
108mm (height) x
57.8mm (depth)
Supply voltage
230V AC, 50Hz
Battery back-up
Rechargeable 5 year NI-MH battery
Technology
Wi-Safe 2
Alarm sound level
85dB(A) at 3m (minimum)
Installation positions
Free-standing or wall mounted vertically or horizontally
Operating temperature
+4°C to +38°C
Operating humidity
Up to 90% RH non-condensing
Storage temperature
-20°C to 60°C
Storage humidity
Up to 93% RH non condensing
Plastic material
ABS, UL94 VO fire retardant
Warranty
5 years
Master pack quantity
10
Weight
635g
Certified to
N/A
Independently tested to
EN 301489-1 v1.9.2 (2011-09)
EN 301489-3 v1.4.1 (2002-08)
EN 300220-2 v2.3.2 (2010-12)
Maximum number of connected units
50 wireless units
Operating Frequency
868 MHz
Range
35m (over 200m in clear air)
108mm
Dimensions
57.8mm
DS700RF
Wireless Interlink Base
• 10 year lithium battery.
• PUSH-FIT mounting base.
• Automatic ID coding.
• Wirelessly interlink up to 50 smoke and heat alarms
of a similar type.
Bedroom & Living Room
• Visual LED and audible fault warnings.
Hallway, Landing,
Living Room & Bedroom
Key Features
• 5 year guarantee.
Kitchen & Garage
Accessories
Technical Specification
140mm
3V DC
Battery back-up
10 year sealed for life lithium battery
Technology
Wireless technology
Alarm sound level
N/A
Installation positions
Ceiling / Wall
Operating temperature
+5°C to +38°C
Operating humidity
10% to 85% RH non-condensing
Storage temperature
-20°C to 60°C
Storage humidity
10% to 85% RH non condensing
Plastic material
ABS, UL94 VO fire retardant
Warranty
5 years
Master pack quantity
10
Weight
145g
Certified to
N/A
Independently tested to
ETSI EN 300 220-2 V2.3.2 (2010-02), EN300489-1 &-3, EN50130-4, EN60065
Maximum number of connected units
50 wireless units
Operating Frequency
868 MHz
Range
35m (over 200m in clear air)
Firefighting Equipment
Supply voltage
Boiler Shut-off
140mm (diameter) x 30mm (depth)
CO Alarm
Dimensions
30mm
49
Accessories
Product Specification
WTSL-SN-1
• The Alarm Control Unit shall be compatible
with all Wi-Safe 2 products. The unit shall
have the ability to be used as a remote
interface between up to 50 Wi-Safe 2
devices. The unit shall carry the CE mark to
indicate conformance to all of the applicable
EC directives including Low Voltage and
Electromagnetic Compatibility Directives.
• The unit shall visually indicate whether it is
a fire or carbon monoxide (CO) incident.
• The unit shall be powered by a non-removable
integrated battery which has a 10 year life in
normal operating conditions.
• Test Function: Pressing the ‘test’ button shall
cause all alarms on the network to sound for 3
minutes. This shall allow testing of the entire
system without having to press the central
test button on each of the alarms.
• The unit shall incorporate a Wi-Safe 2
intelligent communication module as
standard, which wirelessly interlinks with up
to 50 other units with Wi-Safe 2 technology
inside on a single network. All units shall have
the ability to be learnt into a single network by
an easy 2 button process.
• The Wi-Safe 2 Radio frequency shall be
868 MHz band in accordance with R&TTE
Directive 1999/5/EC.
• A simple 2 button process enables the Control
Unit to communicate with other Wi-Safe
2 products on a unique coded network.
Additional units can be added on the network
using the same procedure.
• The unit shall feature an optional tamper proof
function where required that can securely
lock the unit into place after installation and
thereafter it can only be removed with a tool.
• The unit shall incorporate 4 functions; Test,
Silence, Locate and Memory.
• Silence Function: Pressing the ‘silence’ button
shall silence all of the interlinked alarms for
up to 10 minutes in the event of a known
false alarm. After 10 minutes the alarms shall
return to full sensitivity. During these 10
minutes if additional smoke/heat is detected
the alarm silence function will be overridden
and the alarms will sound.
• An alarm cannot be silenced using the alarm
control unit if CO has been detected, however
the locate function will allow the initiating CO
alarm to be located.
To make locating the alarm easier, the control
unit shall be removable from its bracket
enabling it to be carried around the property
(providing the tamper proof function has not
been engaged), allowing the user to press
the Locate or Test button whilst moving from
room to room.
• Memory Function: Where an alarm has
previously gone into full alarm a fire or
CO indicator shall flash on the control
unit every 10 seconds. This indicator will
continue to flash until the Locate button is
pressed. Pressing the Locate button shall
sound the initiating alarm to enable further
investigation.
• The unit shall be manufactured from ABS,
UL94 V0 fire retardant plastic.
• The unit shall be supplied with installation /
user instructions.
• The unit shall have the following dimensions:
90mm height. x 90mm width. x 22.5mm depth.
• The unit shall have the following weight:
142g (including power pack).
• Locate Function: Pressing the ‘locate’ button
shall silence all wirelessly interlinked alarms
except for the initiating alarm which has
sensed smoke, heat or carbon monoxide.
• The unit shall have a 5 year warranty.
• The Wi-Safe 2 radio frequency shall be
868 MHz band in accordance with R&TTE
Directive 1999/5/EC.
• There shall be an integrated test button on the
front of the unit. Pressing this shall check the
strobe, vibrating pad and control circuitry and
also send out an RF alarm signal to all other
Wi-Safe 2 units in the network.
W2-SVP-630
• The unit shall carry the CE mark to indicate
conformance to all of the applicable EC
directives including Low Voltage and
Electromagnetic Compatibility Directives.
• The unit for the hearing impaired shall
consist of a strobe and vibrating pad. The
unit shall be for use with all Wi-Safe 2 devices
/ accessories, including smoke, heat and
CO alarms.
• The unit shall eliminate the need for any
cabling between it and the smoke, heat or
CO alarms used in the network.
• The unit shall have a built in high-intensity
ultra-bright LED array (flash rate 1.0Hz) with a
180° output angle.
• There shall be comprehensive indicating
lights on the front of the unit as follows:
• The unit shall be powered by a 230V mains
power supply and shall be supplied with an
AC-DC 12V05A AC mains adaptor suitable for
use with standard mains sockets.
• Power (green) – constant green to indicate
mains is present
• The unit shall be supplied with a replaceable,
rechargeable 5 year life battery, to provide
back-up power in the event of mains failure for
up to 72 hours.
• CO Alarm (red) – flashes every second
when unit has been triggered.
• The rechargeable battery shall have a lifespan
of 5 years in normal use. The battery shall be
connected by plugging it into the socket in
the unit.
• The unit shall incorporate a Wi-Safe 2
intelligent communication module as
standard, which wirelessly interlinks with up
to 50 other units with Wi-Safe 2 technology
inside on a single network. All units shall have
the ability to be learnt into a single network by
an easy 2 button process.
• The wireless Wi-Safe 2 module shall have a
separate 10 year sealed for life lithium battery
designed to outlast the usable life of the unit.
50
• Unit shall comply with: EN 301489-1 v1.9.2
(2011-09), EN 301489-3 v1.4.1 (2002-08), EN
300220-2 v2.3.2 (2010-12).
• Smoke Alarm (red) – flashes every second
when unit has been triggered.
• Fault (amber):
i. Double flashes every 5 seconds if not
connected to the mains.
ii. Flashes once per second if the pad is not
connected to the strobe.
iii. Flashes once every 5 seconds if not
connected the mains and battery power
is low.
iv. Flashes rapidly if a fault is detected in
the unit.
v. Double flashes every second if a network
fault is detected.
vi. Constantly illuminated if the unit is not
‘learned-in’ to a network.
• The vibrating pad shall be suitable for placing
under mattresses or pillows and produce
strong, pulsed vibrations suitable for waking
sleepers.
• There shall be connecting sockets on the rear
of strobe unit as follows:
• Vibrating pad socket – Wiring is monitored
so if it is not connected or the cable is
damaged the fault light will flash.
• Power supply socket – a power supply
socket is available on the rear of the unit to
allow connection to the mains.
• The unit shall be designed for wall or surface
mounting.
• The unit shall have the following dimensions:
Strobe: 102mm (height) x 150mm (width) x
39.3mm (depth) .
Pad: 98mm (diameter) x 34mm (depth).
• The unit shall have the following weight:
460g.
• The unit shall have a 5 year guarantee.
• The unit shall carry the CE mark to indicate
conformance to all of the applicable EC
directives including Low Voltage and
Electromagnetic Compatibility Directives.
• The unit shall eliminate the need for any
cabling between it and the smoke, heat or
CO alarms used in the network.
• The unit shall be powered by a 230V mains
power supply and shall be supplied with an
AC-DC 12V05A AC mains adaptor suitable for
use with standard mains sockets.
• Unit shall comply with: EN 301489-1 v1.9.2
(2011-09), EN 301489-3 v1.4.1 (2002-08), EN
300220-2 v2.3.2 (2010-12).
• There shall be comprehensive indicating
lights on the front of the unit as follows:
• Power (green) – constant green to indicate
mains is present
• Fire Alarm (red) – flashes every second
when unit has been triggered by a smoke
or CO alarm.
• CO (red) – flashes every second when unit
has been triggered by a CO alarm.
• Fault (amber):
• The rechargeable battery shall have a lifespan
of 5 years in normal use. The battery shall be
connected by plugging it into the socket in
the unit.
ii.Flashes once every 5 seconds if not
connected to the mains and battery
power is low.
• The unit shall incorporate a Wi-Safe 2
intelligent communication module as
standard, which wirelessly interlinks with up
to 50 other units with Wi-Safe 2 technology
inside on a single network. All units shall have
the ability to be learnt into a single network by
an easy 2 button process.
iii.Double flashes every second if a network
fault is detected.
iv.Double flashes every second if a network
fault is detected.
• The low frequency sounder shall be suitable
for placing in sleeping rooms, close to a
power socket, where LEDs can be seen and
will produce a low frequency audible sound
suitable for waking high-risk individuals.
• There shall be connecting sockets on the rear
of strobe unit as follows:
• Power supply socket – power supply
socket is available on the rear of the unit
to allow connection to the mains. Wiring
is monitored so if it is not connected or the
cable is damaged the fault light will flash.
• The unit shall be designed for wall or surface
mounting.
• The unit shall have the following dimensions:
198mm (width) x 108mm (height) x 57.8mm
(depth)
• The unit shall have the following weight: 635g
• The unit shall have a 5 year guarantee.
v. Constantly illuminated if the unit is not
‘learned-in’ to a network.
• There shall be an integrated test button on the
front of the unit. Pressing this shall check the
low frequency circuitry and sounder and shall
also send out an RF alarm signal to all other
Accessories
• The wireless Wi-Safe 2 module shall have a
separate 10 year sealed for life lithium battery
designed to outlast the usable life of the unit.
i.Double flashes every 5 seconds if not
connected to the mains.
• The unit shall emit a 520Hz square wave at a
volume of 85dB at 3m.
Kitchen & Garage
• The unit shall be supplied with a replaceable,
rechargeable 5 year life battery, to provide
back-up power in the event of mains failure
For up to 72 hours.
Wi-Safe 2 units in the network enabling a low
level test of all interlinked units.
Bedroom & Living Room
• The unit for the hearing impaired
shall consist of a low frequency sounder.
The unit shall be for use with all Wi-Safe 2
devices / accessories, including smoke,
heat and CO alarms.
• The Wi-Safe 2 radio frequency shall be
868 MHz band in accordance with R&TTE
Directive 1999/5/EC.
Hallway, Landing,
Living Room & Bedroom
W2-LFS-630
CO Alarm
Boiler Shut-off
Firefighting Equipment
51
52
CO Alarms
53
Solutions for:
CO Alarms
Product Selector Table
Battery Powered
CO Alarm
54
Mains Powered
CO Alarm
Mains Powered
CO Alarm
Product code
WCOB-SN-1
CO850MRLi
C0850MBXi
Brand
SONA
BRK
BRK
Technology
Electrochemical
Electrochemical
Electrochemical
Supply Voltage
3V DC
230V
230V
Battery
Sealed for life 10 year lithium
Rechargeable lithium back-up
9V alkaline back-up
Warranty
5 years
5 years
5 years
Page
56
57
57
Common sources of CO:
Open fires
BBQ’s
Car exhausts
Broken flues
Blocked Chimneys
Even adjoining
properties
Kitchen & Garage
Ovens
Bedroom & Living Room
Boilers
Hallway, Landing,
Living Room & Bedroom
Ideally, an alarm should be installed in every room containing a fuel-burning appliance. Additional
alarms may be installed to provide adequate warning for occupants in other rooms, by placing alarms
in rooms in which they spend considerable time whilst awake.
Accessories
CO Alarm
Boiler Shut-off
Battery Powered
CO Alarm
Battery Powered
Digital CO Alarm
Product code
CO-9X-10T-FF
CO-9XT-FF
CO-9D
Brand
FireAngel
FireAngel
FireAngel
Technology
Electrochemical
Electrochemical
Electrochemical
Supply Voltage
3V DC
3V DC
3V DC
Battery
10 year sealed for life lithium
7 year Sealed for life lithium
7 year Sealed for life lithium
Warranty
10 years
7 years
7 years
Page
59
60
61
Firefighting Equipment
Battery Powered
CO Alarm
55
WCOB-SN-1
Battery Powered Wireless CO Alarm
Sensor type
Advanced electrochemical
Battery type
10 year sealed for life lithium
Key Features
• A
dvanced electrochemical sensor - calibrated and
tested in CO gas.
• 10 year sealed for life lithium battery.
• Wi-Safe 2 technology - up to 50 Wi-Safe 2 alarms can
be interlinked on a single network.
• Centralised button - test / silence / locate.
• Sleep Easy - a low battery chirp can be silenced for 8
hours by pressing the test button, this can be used up
to 10 times.
• Integrated flip down bracket with single pin or 2 screw
fitting options.
• Mixed system compatibility:
• Wireless and hardwired.
• Mains and battery powered alarms.
Technical Specification
BS EN50291-1:2010
BS EN 50291-2:2010
Licence No: KM 551504
Wi-Safe 2 module contained within WCOB-SN-1
independently tested to RF standard
ETSI EN 300 220-2 V2.3.2 (2010-02) byTRaC Global Ltd
EN300489-1 &-3 / EN300220-2 - Radio
114mm
56
94 mm (height)
x 114mm (diameter)
x 39.5mm (depth)
Supply voltage
3V DC
Battery
10 year sealed for life lithium
Technology
Advanced electrochemical and Wi-Safe 2
Alarm sound level
85dB(A) at 3m (minimum)
Installation positions
Wall / Free-standing
Operating temperature
-10°C to +40°C
Operating humidity
30% to 90% RH non-condensing
Storage temperature
-20°C to +60°C
Storage humidity
30% to 90% RH non-condensing
Plastic material
ABS, UL94 VO fire retardant
Warranty
5 years
Master pack quantity
4
Weight
189g
Certified to
BS EN 50291-1 & 2: 2010
Independently tested to
ETSI EN 300 220-2 V2.3.2 (2010-02), EN 300489-1 &-3, EN300220-2-Radio
Maximum number of connected units
50 wireless units
Operating Frequency
868 MHz
Range
35m (over 200m in clear air)
94mm
Dimensions
39.5mm
CO850 (MRLi/ MBXi)
Mains Powered CO Alarm
Electrochemical
Battery back-up type
MRLi - Rechargeable lithium / MBXi - 9V alkaline
Key Features
Hallway, Landing,
Living Room & Bedroom
Sensor type
Bedroom & Living Room
• A
dvanced electrochemical sensor - calibrated
and tested in CO gas.
• 230V mains powered.
• Battery back-up:
• MRL - 10 year sealed for life rechargeable
lithium battery.
• MBX- 9V alkaline battery.
Kitchen & Garage
• Hardwire interconnect with up to 12 units
of a similar type.
• Power, alarm and fault indicators.
• Instant test / reset feature.
BSEN50291-1:2010
Licence No: KM554921
Product code
CO850 MRLi
69mm
134mm (height)
x 69mm (width)
x 60mm (depth)
CO850 MBXi
Supply voltage
230V AC, 50Hz
230V AC, 50Hz
Battery back-up
Rechargeable lithium battery
9V alkaline battery
Technology
Electrochemical
Electrochemical
Alarm sound level
85dB(A) at 1m (minimum)
85dB(A) at 1m (minimum)
Wall
Wall
-10°C to +40°C
-10°C to +40°C
Operating humidity
30% to 90% RH non-condensing
30% to 90% RH non-condensing
Storage temperature
0°C to +40°C
0°C to +40°C
Storage humidity
30% to 90% RH non-condensing
30% to 90% RH non-condensing
Plastic material
ABS, UL94 VO fire retardant
ABS, UL94 VO fire retardant
Warranty
5 years
5 years
10
10
226g
226g
Certified to
BS EN 50291-1:2010
BS EN 50291-1:2010
Independently tested to
N/A
N/A
Maximum number of connected units
12 hardwired units
12 hardwired units
Operating Frequency
N/A
N/A
Range
N/A
N/A
Firefighting Equipment
Master pack quantity
Weight
Boiler Shut-off
Installation positions
Operating temperature
60mm
134mm
134mm (height)
x 69mm (width)
x 60mm (depth)
60mm
CO Alarm
Dimensions
134mm
69mm
Accessories
Technical Specification
57
W2-CO-10XT
Battery Powered Wireless CO Alarm
Sensor type
Advanced electrochemical
Battery type
10 year sealed for life lithium
Key Features
• Advanced electrochemical sensor calibrated and tested
in CO gas.
• 10 year sealed for life lithium battery.
• Wi-Safe 2 technology - up to 50 Wi-Safe 2 alarms can
be interlinked on a single network.
• Large central button - test / silence / locate.
• Integrated flip down bracket with information in the
event of alarm.
• Single pin or 2 screw fitting options.
• Optional tamper resistant feature to prevent
unauthorised removal.
• Sleep Easy - a low battery chirp can be silenced for 8 hours
by pressing the test button, this can be used up to 10 times.
Technical Specification
BS EN50291-1:2010
BS EN 50291-2:2010
Licence No: KM 551504
Wi-Safe 2 module contained within W2-CO-10X
independently tested to RF standard ETSI EN
300 220-2 V2.3.2 (2010-02) byTRaC Global Ltd
EN300489-1 &-3 / EN300220-2 - Radio
114mm
58
114mm (width) x 94.5mm (height)
x 40mm (depth)
Supply voltage
3V DC
Battery
10 year sealed for life lithium battery
Technology
Advanced electrochemical and Wi-Safe 2
Alarm sound level
85dB(A) at 3m (minimum)
Installation positions
Wall / Free-standing
Operating temperature
+4°C to +38°C
Operating humidity
Up to 90% RH non-condensing
Storage temperature
-20°C to +60°C
Storage humidity
Up to 93% RH non-condensing
Plastic material
ABS, UL94 VO fire retardant
Warranty
5 years
Master pack quantity
10
Weight
190g
Certified to
BS EN 50291-1 & 2: 2010
Independently tested to
ETSI EN 300 220-2 V2.3.2 (2010-02), EN 300489-1 &-3, EN300220-2-Radio
Maximum number of connected units
50 wireless units
Operating Frequency
868 MHz
Range
35m (over 200m in clear air)
94.5mm
Dimensions
40mm
CO-9X-10T-FF
Battery Powered CO Alarm
Advanced electrochemical
Battery type
10 year sealed for life lithium
Bedroom & Living Room
Key Features
Hallway, Landing,
Living Room & Bedroom
Sensor type
• A
dvanced electrochemical sensor calibrated
and tested in CO gas.
• 10 year sealed for life lithium battery.
• Can be free-standing or wall mounted.
• Supplied with tamper resistant Fast-Fit bracket
with single pin or 2 screw fitting options.
• Test button - to test circuitry and sounder.
Kitchen & Garage
BS EN50291-1:2010
BS EN 50291-2:2010
Licence No: KM 551504
Accessories
Technical Specification
3V DC
Battery
10 year sealed for life lithium battery
Technology
Advanced electrochemical
Alarm sound level
85dB(A) at 1m (minimum)
Installation positions
Wall / Free-standing
Operating temperature
-10°C to +40°C
Operating humidity
30% to 90% RH non-condensing
Storage temperature
-20°C to +60°C
Storage humidity
Up to 93% RH non-condensing
Plastic material
ABS, UL94 VO fire retardant
Warranty
10 years
Master pack quantity
20
Weight
106g
Certified to
BS EN 50291-1 & 2: 2010
Independently tested to
N/A
Maximum number of connected units
N/A
Operating Frequency
N/A
Range
N/A
Firefighting Equipment
Supply voltage
Boiler Shut-off
112mm (width) x 72mm (height)
35mm (depth)
CO Alarm
Dimensions
35mm
72mm
112mm
59
CO-9XT-FF
Battery Powered CO Alarm
Sensor type
Advanced electrochemical
Battery type
7 year sealed for life lithium
Key Features
• A
dvanced electrochemical sensor - calibrated and
tested in CO gas.
• 7 year sealed for life lithium battery.
• Alarm can be free-standing or wall mounted.
• Supplied with tamper resistant Fast-Fit bracket
with single pin or 2 screw fitting options.
• Test button - to test circuitry and sounder.
BS EN50291-1:2010
BS EN 50291-2: 2010
Licence No: KM 551504
Technical Specification
60
Dimensions
112mm (width) x 72mm (height)
x 35mm (depth)
Supply voltage
3V DC
Battery back-up
7 year sealed for life lithium battery
Technology
Advanced electrochemical
Alarm sound level
85dB(A) at 1m (minimum)
Installation positions
Wall / Free-standing
Operating temperature
-10°C to +40°C
Operating humidity
30% to 90% RH non-condensing
Storage temperature
-20°C to +60°C
Storage humidity
Up to 93% RH non-condensing
Plastic material
ABS, UL94 VO fire retardant
Warranty
7 years
Master pack quantity
20
Weight
106g
Certified to
BS EN 50291-1 & 2: 2010
Independently tested to
N/A
Maximum number of connected units
N/A
Operating Frequency
N/A
Range
N/A
72mm
112mm
35mm
CO-9D
Battery Powered CO Alarm
Advanced electrochemical
Battery type
7 year sealed for life lithium
• A
dvanced electrochemical sensor - calibrated and
tested in CO gas.
• 7 year sealed for life lithium battery.
• Unique digital LCD screen.
• The alarm has a built in room temperature indicator.
Bedroom & Living Room
Key Features
Hallway, Landing,
Living Room & Bedroom
Sensor type
• Shows the peak levels of CO detected over a 4
week period.
Kitchen & Garage
• Can be free-standing or wall mounted.
• Test button - to test circuitry and sounder.
BS EN50291-1:2010
BS EN 50291-2: 2010
Licence No: KM 551504
Accessories
Technical Specification
125mm
125mm (width) x 72mm (height)
x 40mm (depth)
Supply voltage
3V DC
Battery back-up
7 year sealed for life lithium battery
Technology
Advanced electrochemical
Alarm sound level
85dB(A) at 1m (minimum)
Installation positions
Wall / Free-standing
Operating temperature
-10°C to +40°C
Operating humidity
30% to 90% RH non-condensing
Storage temperature
-20°C to +60°C
Storage humidity
30% to 90% RH non-condensing
Plastic material
ABS, UL94 VO fire retardant
Warranty
7 years
Master pack quantity
5
Weight
118g
Certified to
BS EN 50291-1 & 2: 2010
Independently tested to
N/A
Maximum number of connected units
N/A
Operating Frequency
N/A
Range
N/A
72mm
Dimensions
40mm
CO Alarm
Boiler Shut-off
Firefighting Equipment
61
CO Alarms
Product Specification
WCOB-SN-1
• The carbon monoxide alarm shall carry
the BSI Kitemark to indicate type testing
to BS EN50291-1: 2010 and BS EN50291-2:
2010. The alarm shall carry the CE mark to
indicate conformance to all of the applicable
EC directives including Low Voltage and
Electromagnetic Compatibility Directives.
• The alarm shall have an advanced
electrochemical sensor capable of lasting 10
years. Each sensor shall be calibrated and
tested in CO gas to ensure accuracy.
• The alarm shall include a non-removable
integrated lithium battery which has a 10 year
life in normal operating conditions.
• The alarm shall incorporate a diagnostic
function which monitors alarm activations and
facilitates fault finding.
• The alarm shall incorporate a Wi-Safe 2
intelligent communication module as standard,
which wirelessly interlinks with up to 50 other
units with Wi-Safe 2 technology inside on a
single network. All units shall have the ability
to be learnt into a single network by an easy 2
button process.
• The wireless Wi-Safe 2 module shall have a
separate 10 year sealed for life lithium battery
designed to outlast the usable life of the alarm.
• The Wi-Safe 2 radio frequency shall be 868
MHz band in accordance with R&TTE Directive
1999/5/EC.
CO850(MRLi/MBXi)
• The carbon monoxide alarm shall carry the
BSI Kitemark to indicate type testing to BS
EN50291-1: 2010. The alarm shall carry the
CE mark to indicate conformance to all of the
applicable EC directives including Low Voltage
and Electromagnetic Compatibility Directives.
• The alarm shall have an advanced
electrochemical sensor. Each sensor shall
be calibrated and tested in CO gas to
ensure accuracy.
• The alarm shall operate on a 230V mains power
supply with a battery back-up.
• CO850MRLi- The alarm shall operate on a 230V
mains power supply and have a built-in, sealed
for life, rechargeable lithium battery back-up to
power the alarm in the event of a mains failure.
• CO850MBXi- The alarm shall operate on a 230V
mains power supply and shall be supplied with
9V PP3 alkaline battery back-up to power the
alarm in the event of a mains failure.
W2-CO-10XT
• The carbon monoxide alarm shall carry
the BSI Kitemark to indicate type testing
to BS EN50291-1: 2010 and BS EN50291-2:
2010. The alarm shall carry the CE mark to
indicate conformance to all of the applicable
EC directives including Low Voltage and
Electromagnetic Compatibility Directives.
• The alarm shall have an advanced
electrochemical sensor capable of lasting 10
years. Each sensor shall be calibrated and
tested in CO gas to ensure accuracy.
• The alarm shall include a non-removable
integrated lithium battery which has a 10 year
life in normal operating conditions.
• The alarm shall incorporate a Wi-Safe
2 intelligent communication module as
standard, which wirelessly interlinks with up
to 50 other units with Wi-Safe 2 technology
inside on a single network. All units shall have
the ability to be learnt into a single network by
an easy 2 button process.
62
• A simple 2 button process enables alarms to
communicate with each other on a unique
coded network. Additional units can be added
on to the network using the same procedure.
• The alarm shall be capable of working on
a mixed system to include hard-wired and
wireless mains and battery alarms of a
similar type.
• On a mixed network of alarms (CO, smoke and
heat), all alarms will sound a CO alarm pattern
upon detection of CO.
• The alarm shall incorporate ‘Sleep Easy’
functionality whereby a low battery chirp can
be silenced for a period of 8 hours by pressing
the test button on the smoke / heat alarm. This
function can be used up to 10 times.
• The alarm shall have a built in sounder giving a
minimum sound output of 85dB(A) at 3m.
• The alarm shall incorporate a large central
concave test / silence button to test circuitry,
sensor and sounder and activate all
interconnected alarms in the system.
• The alarm shall be supplied with an integral flip
down bracket and can be fitted securely to the
wall either with screws or a single pin fitting
option for rapid installation. The alarm shall
also be capable of free standing for flexible
installations around a property.
• The alarm features an intelligent silence /
locate feature whereby pressing the test /
silence button on any alarm in the network will
silence all but the initiating alarm.
• The alarm shall feature an optional tamper
resistant function where required that can
securely lock the alarm into place after
installation and thereafter the alarm can only
be removed with a tool.
• The alarm shall be manufactured from ABS,
UL94 V0 fire retardant plastic.
• The alarm shall have a low battery warning
signal, which will ‘chirp’ every 45 seconds for
at least 30 days to indicate when a replacement
of the alarm is required. All other alarms on the
network shall also emit an audible low battery
chirp once every 4 hours. This will continue
until the alarm which has the low battery
condition is removed.
• The alarm shall have the ability to
hardwire interconnect with up to 12 other
smoke, heat and CO alarms of a similar type
on a single network.
• The alarm shall have a green LED mains
indicator to confirm mains power supply is on.
• In the event of a mains failure the green
LED will flash approximately once every 60
seconds, to indicate that the back-up battery
is in use.
• The alarm shall have a low battery warning
signal, which will ‘chirp’ approximately once
every 60 seconds. A yellow LED shall also flash
approximately once every 60 seconds.
• The alarm shall have a fault warning, which
will emit 2 short ‘chirps’ approximately once
every 60 seconds. A yellow LED shall also light
up and remain lit.
• The alarm shall have an end of life indication.
• The alarm shall be supplied with installation /
user instructions.
• The alarm shall have the following dimensions:
114mm width x 39.5mm depth x 94mm height.
• The alarm shall have the following weight:
189g.
• The alarm has a 5 year warranty.
• The alarm shall have an end of life warning,
which will emit 3 short ‘chirps’ approximately
once every 60 seconds.
• The alarm shall have an integral test / reset
button in order to test circuitry, sensor and
sounder and activate all interconnected alarms
in the system.
• The alarm has a built in sounder giving a
minimum sound output of 85dB(A) at 1m.
• The alarm shall be supplied with installation /
user instructions.
• The alarm and base shall have the following
combined dimensions: 140mm dia. x 71mm
depth.
• The alarm and base shall have the following
combined weight: 262g.
• The alarm shall have a 5 year warranty.
• The wireless Wi-Safe 2 module shall have
a separate 10 year sealed for life lithium
battery designed to outlast the usable life
of the alarm.
• The alarm shall have an optional tamper
resistant function to securely lock it into place
after installation and thereafter it can only be
removed with a tool.
• The Wi-Safe 2 radio frequency shall be
868 MHz band in accordance with R&TTE
Directive 1999/5/EC.
• The alarm shall have a low battery warning
signal, which will ‘chirp’ every 45 seconds
for at least 30 days to indicate when a
replacement of the alarm is required. All other
alarms on the network shall also emit an
audible low battery chirp once every 4 hours.
This will continue until the alarm which has
the low battery condition is removed.
• A simple 2 button process enables alarms to
communicate with each other on a unique
coded network. Additional units can be added
on the network using the same procedure.
• On a mixed network of alarms (CO, smoke
and heat), all alarms shall sound a CO alarm
pattern upon detection of CO.
• The alarm shall be supplied with an integral
flip down bracket and can be fitted securely
to the wall either with screws or a single pin
fitting option for rapid installation. The alarm
shall also be capable of free standing for
flexible installations around a property.
• The alarm shall incorporate ‘Sleep Easy’
functionality whereby a low battery chirp can
be silenced for a period of 8 hours by pressing
the test button on the alarm. This function can
be used up to 10 times.
• The alarm shall have a built in sounder giving
a minimum sound output of 85dB(A) at 3m.
continued at top of page 63
• The alarm has end of life indication.
• The alarm features an intelligent locate
feature whereby pressing the test / silence
button on any alarm in the network will
silence all but the initiating alarm.
• The alarm shall be supplied with installation /
user instructions.
• The alarm shall be supplied with a Fast-Fit
bracket with an option of a single pin or a 2
screw fixing.
• The alarm shall have an advanced
electrochemical sensor capable of lasting 10
years. Each sensor shall be calibrated and
tested in CO gas to ensure accuracy.
• The alarm shall have a manual test / silence
button to test circuitry and sounder. At levels
of CO above 50ppm the unit shall not be
silenced due to the increased danger.
• The alarm shall include a non-removable
integrated lithium battery which has a 10
year life in normal operating conditions.
• The alarm shall have a built in sounder giving
a minimum sound output of 85dB(A) at 1m.
• The alarm shall have a low battery / end of
life indication in the form of an audible ‘chirp’
approximately once every 45 seconds for at
least 30 days to indicate when replacement
of the alarm is required.
CO-9XT-FF
• When the alarm is attached to the Fast-Fit
bracket, the alarm shall lock into place and can
only be removed with the use of a tool.
• The alarm shall have a manual test / silence
button to test circuitry and sounder. At levels
of CO above 50ppm the unit shall not be
silenced due to the increased danger.
• The alarm shall include a non-removable
integrated lithium battery which has a 7 year
life in normal operating conditions.
• The alarm shall have a built in sounder giving
a minimum sound output of 85dB(A) at 1m.
• When the alarm is attached to the Fast-Fit
bracket, the alarm shall lock into place and can
only be removed with the use of a tool.
• The alarm shall have the following weight:
106g (including Fast-Fit bracket).
• The alarm shall have a 10 year warranty.
• The alarm shall have an end of life indication.
• The alarm shall be manufactured from ABS,
UL94 V0 fire retardant plastic.
• The alarm shall be supplied with installation /
user instructions.
• The alarm shall have the following
dimensions: 72mm height. x 112mm width. x
35mm depth.
• The alarm shall have the following weight:
106g (including Fast-Fit bracket).
• The alarm shall have a 7 year warranty.
• The alarm shall have an operating
temperature range of -10°C to +40°C.
• The alarm shall have an operating humidity of
30% to 90% RH (non-condensing).
• If the alarm is in the temperature view and CO
is detected then the alarm shall automatically
switch back to CO display mode.
• The alarm shall be capable of showing
the peak levels of CO detected over a 4
week period.
• The alarm shall have a low battery / end of
life indication in the form of an audible ‘chirp’
approximately once a minute and the low
power pack icon will flash on the screen.
• The alarm shall have a manual test / silence
button to test circuitry and sounder. At levels
of CO above 50ppm the unit shall not be
silenced due to the increased danger.
• The alarm shall have a digital LCD screen.
• The alarm shall have a built in sounder giving
a minimum sound output of 85dB(A) at 1m.
• The alarm shall have an operating humidity of
30% to 90% RH (non-condensing).
• The alarm shall be manufactured from ABS,
UL94 V0 fire retardant plastic.
• The alarm shall be supplied with installation /
user instructions.
• The alarm shall have the following
dimensions: 74mm height. x 125mm width. x
40mm depth.
• The alarm shall have the following weight:
118g.
• The alarm shall have a 7 year warranty.
Firefighting Equipment
• The alarm shall be capable of being free
standing or being fixed to a wall using the 2
screws that are supplied.
• The alarm shall have an operating
temperature range of -10°C to +40°C.
Boiler Shut-off
• The alarm shall be able to display 2 views in
normal standby mode, the current level of CO
or the indicative room temperature in degrees
centigrade (°C).
• The alarm shall include a non-removable
integrated lithium battery which has a 7 year
life in normal operating conditions.
• The alarm shall have a built in room
temperature indicator.
• The alarm shall have the following
dimensions: 72mm height. x 112mm width. x
35mm depth.
CO Alarm
• The alarm shall have an advanced
electrochemical sensor capable of lasting 7
years. Each sensor shall be calibrated and
tested in CO gas to ensure accuracy.
• The alarm shall be supplied with installation /
user instructions.
Accessories
• The alarm shall have an advanced
electrochemical sensor capable of lasting 7
years. Each sensor shall be calibrated and
tested in CO gas to ensure accuracy.
• The carbon monoxide alarm shall carry
the BSI Kitemark to indicate type testing
to BS EN50291-1: 2010 and BS EN50291-2:
2010. The alarm shall carry the CE mark to
indicate conformance to all of the applicable
EC directives including Low Voltage and
Electromagnetic Compatibility Directives.
• The alarm shall be manufactured from ABS,
UL94 V0 fire retardant plastic.
• The alarm shall have an operating humidity of
30% to 90% RH (non-condensing).
• The alarm shall be supplied with a Fast-Fit
bracket with an option of a single pin or a 2
screw fixing.
CO-9D
• The alarm shall have a 5 year warranty.
• The alarm shall have an operating
temperature range of -10°C to +40°C.
• The carbon monoxide alarm shall carry
the BSI Kitemark to indicate type testing
to BS EN50291-1: 2010 and BS EN50291-2:
2010. The alarm shall carry the CE mark to
indicate conformance to all of the applicable
EC directives including Low Voltage and
Electromagnetic Compatibility Directives.
• The alarm shall have a low battery / end of
life indication in the form of an audible ‘chirp’
approximately once every 45 seconds for at
least 30 days to indicate when replacement of
the alarm is required.
• The alarm shall have the following weight:
190g.
Kitchen & Garage
• The carbon monoxide alarm shall carry
the BSI Kitemark to indicate type testing
to BS EN50291-1: 2010 and BS EN50291-2:
2010. The alarm shall carry the CE mark to
indicate conformance to all of the applicable
EC directives including Low Voltage and
Electromagnetic Compatibility Directives.
• The alarm shall have the following
dimensions: 114mm width. x 39.5mm depth.
x 94mm height.
Bedroom & Living Room
CO-9X-10T-FF
• The alarm shall be manufactured from ABS,
UL94 V0 fire retardant plastic.
Hallway, Landing,
Living Room & Bedroom
• The alarm shall incorporate a large central
concave test / silence button to test circuitry,
sensor and sounder and activate all
interconnected alarms in the system.
63
64
Boiler
Shut-Off
65
Solutions for:
Boiler Shut-Off
Positioning of CO Alarms & Control Unit
The noCO boiler shut off system provides the highest level of protection against CO.
In the event of a CO leak the noCO wireless alarm will sound and automatically send a signal to the
boiler shut down control unit to shut off the boiler. The boiler will then need a Gas Safe registered boiler
engineer to restart it, ensuring the tenant is fully protected while the cause of CO is investigated.
Product Selector Table
66
Boiler Shut Down Control Unit
In Room CO Alarm
In Void CO Alarm
Product code
RLY-230-BX
CO-BX9RO
CO-BX9SN
Brand
FireAngel
FireAngel
FireAngel
Technology
Electrical unit with wireless
Electrochemical
Electrochemical
Supply Voltage
230V
3V DC
3V DC
Battery
N/A
7 year sealed lithium
7 year sealed lithium
Warranty
2 years
2 years
2 years
Page
67
68
69
RLY-230-BX
Mains Powered noCO Control Unit
• Mains wired between the boiler and the fused spur.
• Wirelessly links to all noCO units within the
network. If CO is detected then all the interlinked
alarms will sound and the boiler will be shut off.
• For use with all boiler makes.
• Four LED indicators to show:
Bedroom & Living Room
• Unit will shut off the boiler upon detection of CO in
the property. The boiler will then require a Gas Safe
registered engineer to restart it once the appliance
has been made safe.
Hallway, Landing,
Living Room & Bedroom
Key Features
• Boiler power
• Control unit power
Kitchen & Garage
• Fault
• Alarm
Dimensions
154mm (width)
x 36 mm (height)
x 80mm (depth)
80mm
36mm
154mm
Accessories
Technical Specification
N/A
Technology
Electrical unit with wireless technology
Alarm indication
Flashing LED (red) and boiler switch off
Installation positions
Wall mounted between fused spur and boiler
Operating temperature
-10°C to +40°C
Operating humidity
30% to 70% RH non-condensing
Storage temperature
-20°C to +5 0°C
Unpowered storage
5% to 95% RH non-condensing
Switching current
8A at 250v
Switching power
2000VA
Plastic material
ABS, UL94 VO fire retardant
Warranty
2 years
Master pack quantity
20
Weight
240g
Maximum number of connected units
Up to 50 noCO products
Operating Frequency
868 MHz
Compatibility
Compatible with all noCO products
Range
35m (over 200m in clear air)
Firefighting Equipment
Battery back-up
Boiler Shut-off
230V AC, 50Hz
CO Alarm
Supply voltage
67
CO-BX9RO
Wireless CO Alarm
Sensor type
Advanced electrochemical
Battery type
7 year sealed for life lithium
Key Features
• Advanced electrochemical sensor: calibrated and
tested in CO gas.
• 7 year sealed for life lithium battery.
• Continuous monitoring of CO levels.
• Wirelessly links to all noCO units within the
network, if CO gas is detected then all interlinked
alarms will sound and the boiler will be shut off.
• Sleep Easy- allows a low battery chirp to be silenced
for 8 hours. This function can be used up to 10 times.
• Suitable for use with all boiler makes.
• Designed to comply with EN:50291-1: 2010
Technical Specification
124mm
68
Dimensions
124mm (diameter) x 39mm (depth)
Supply voltage
3V DC
Battery
7 year lithium battery
Technology
Advanced electrochemical sensor and wireless enabled
Alarm sound level
85dB(A) at 3m (minimum)
Installation positions
Ceiling / Wall
Operating temperature
-10°C to +40°C
Operating humidity
30% to 90% RH non-condensing
Storage temperature
-10°C to +40°C
Storage humidity
30% to 90% RH non-condensing
Plastic material
ABS, UL94 VO fire retardant
Warranty
2 years
Master pack quantity
20
Weight
180g
Maximum number of connected units
Up to 50 noCO products
Operating Frequency
868 MHz
Compatibility
Compatible with all noCO products
Range
35m (over 200m in clear air)
39mm
CO-BX9SN
In Void CO Alarm
Advanced electrochemical
Battery type
7 year sealed for life lithium
• Advanced electrochemical sensor: calibrated and
tested in CO gas.
• 7 year sealed for life lithium battery.
• Designed to fit inside void spaces.
• Continuous monitoring of CO levels from boiler flues
located within a void space.
• Suitable for use with all boiler makes.
• Sleep Easy- allows a low battery chirp to be silenced
for 8 hours, this function can be used up to 10 times.
• Designed to comply with EN:50291-1: 2010
Kitchen & Garage
• Wirelessly links to all noCO units within the
network. If CO gas is detected then all interlinked
CO alarms will sound and the boiler will be shut off.
Bedroom & Living Room
Key Features
Hallway, Landing,
Living Room & Bedroom
Sensor type
Accessories
Technical Specification
124mm
39mm
Dimensions
7 year sealed for life lithium battery
Technology
Advanced electrochemical and wireless technology
Alarm sound level
85dB(A) at 3m (minimum)
Installation positions
Within void
Operating temperature
-10°C to +40°C
Operating humidity
30% to 90% RH non-condensing
Storage temperature
-10°C to +40°C
Storage humidity
30% to 90% RH non-condensing
Plastic material
ABS, UL94 VO fire retardant
Warranty
2 years
Master pack quantity
10
Weight
220g
Maximum number of connected units
50 wireless units
Operating Frequency
868 MHz
Compatibility
Compatible with all noCO
Range
35m (over 200m in clear air)
Firefighting Equipment
Battery
48.6mm
Boiler Shut-off
3V DC
CO Alarm
Neck
x 178.7mm (length)
x 42.2mm (depth)
Supply voltage
178.7mm
42.2mm
Pad
124mm (diameter)
x 39mm (depth)
69
70
Firefighting
Equipment
71
Solutions for:
Firefighting Equipment
Positioning of firefighting equipment
Fire extinguishers and blankets
Product Selector Table
Product code
600g Domestic Fire Extinguisher
1kg Domestic Fire Extinguisher
FA-600
FA-P1-UK
First Alert
First Alert
Class
Brand
72
Guarantee
5 years
2 years
Certified to
BS EN3 Kitemarked
BS EN3 Kitemarked
Extinguisher Type
Dry Powder
Dry Powder
Stored Pressure


Dimensions
268mm (diameter) x 59mm (height)
35mm (diameter) x 80mm (height)
Weight
720kg
2.0kg
Features
• Manufactured to BS6165:2002
• Supplied with moulded transport bracket and
integrated locking strap. • The Non toxic fire fighting agent
• Light weight product
• Controlled discharge
• CE Marked
• Supplied with powder coated metal transport
bracket
• Brass valve with easy to read pressure gauge
• Controlled discharge
Fires involving paper, wood, textiles, rubber and plastics.
CLASS
Fires involving flammable liquids such as cooking liquids, oil,
gasoline, kerosene, or paint.
CLASS
Fires involving “live” electrical appliances and equipment such
as home wiring, TV’s and electronics.
CLASS
Fires involving cooking oil and fat e.g. olive oil, maize oil, lard and butter.
Bedroom & Living Room
CLASS
Hallway, Landing,
Living Room & Bedroom
Fire Classifications
It’s important to understand how fire extinguishers are classified in order
to choose the correct model type for a fire.
Kitchen & Garage
Accessories
CO Alarm
Product code
2kg Commercial Fire Extinguisher
6kg Commercial Fire Extinguisher
FA-P2000
FA-P6000
First Alert
First Alert
Class
Guarantee
2 years
5 years
Certified to
BS EN3 Kitemarked
BS EN3 Kitemarked
Extinguisher Type
Dry Powder
Dry Powder
Stored Pressure


108mm (diameter) x 408mm (height)
150mm (diameter) x 558mm (height)
3.4kg
9.7kg
• CE Marked
• Supplied with powder coated metal transport
bracket
• Brass valve with easy to read pressure gauge
• Controlled discharge
• CE marked
• Stored pressure
• Corrosion resistant epoxy coated cylinder
• Brass valve with durable steel operating
handles and easy to read pressure gauge
• Controllable squeeze grip operation
Features
Firefighting Equipment
Dimensions
Weight
Boiler Shut-off
Brand
73
Solutions for:
Firefighting Equipment
Positioning of firefighting equipment
Fire extinguishers and blankets
Product Selector Table
2kg Commercial Fire Extinguisher
6L Commercial Fire Extinguisher
14 Fl Oz TUNDRA Domestic Fire
Extinguisher
FA-CD-2
FA-F6000
AF400UK
Brand
First Alert
First Alert
First Alert
Guarantee
5 years
5 years
N/A
Certified to
BS EN3 Kitemarked
BS EN3 Kitemarked
N/A
Extinguisher
Type
Carbon Dioxide (CO2)
Spray Foam
Foam
Stored Pressure


N/A
Dimensions
100mm (diam) x 470mm (height)
150mm (diam) x 542mm (height)
66mm (diam) x 239mm (height)
Weight
6.4kg
9.6kg
626g
• CE marked
• Supplied with wall-mounting
bracket
• Controlled discharge
• Does not leave any residue
• CE Marked
• Spray Nozzle passed the
conductivity test at 35Kv
• Thermoplastic internal coating
• Corrosion resistant epoxy coated
cylinder
• Brass valve with durable steel
operating handles and easy to
read pressure gauge
• Controllable squeeze grip
operation
• Ideal for chip pan fires
• Familiar aerosol style nozzle
• Easy to use - simply point and
spray
• Small enough to fit in a drawer
• Non toxic fire fighting agent
• Easy to clean up after use
Product code
Class
Features
74
Fire blankets can be placed in any location around the home (typically within kitchens)
to fight small fires. They are most effective on frying and chip pan fires.
Chip pan fire
Fire Type
Waste paper bin fire
Fire Type
Clothing fire
Bedroom & Living Room
Fire Type
Hallway, Landing,
Living Room & Bedroom
Fire Blanket Guide
Kitchen & Garage
Accessories
CO Alarm
100 x 100cm Fire Blanket
120 x 180cm Fire Blanket
FB100DUK
FB120BXN
Brand
First Alert
First Alert
Guarantee
1 year
1 year
Certified to
BS EN 1869:1997
BS EN 1869:1997
Dimensions
25cm (h) x 16cm (w) x 4cm (d)
38cm (h) x 16cm (w) x 4cm (d)
Weight
480g (in packaging)
1032g (in packaging)
Features
• Ideal for chip pan, waste bin and
clothing fires
• Ideal for use in the office, warehouse, at home in the
large kitchen, the garage or next to the bbq
• Easy to install and use in an emergency
• Wipe-clean plastic holder
• Ideal for chip pan, waste bin and
clothing fires
• Ideal for use in the office, warehouse, at home in the
large kitchen, the garage or next to the bbq
• Easy to install and use in an emergency
• Wipe-clean plastic holder
Product code
Fire Type
Boiler Shut-off
Firefighting Equipment
75
76
Appendices
77
Siting of Smoke Alarms*
Flat ceiling
300mm
300mm
• Site at least 300mm from walls.
• Site at least 300mm from any
light fittings.
• Site as centrally as possible.
Flat ceilings with beams
300mm
150mm
• Site at least twice the depth of the
beam away e.g. 150mm beam depth:
site the alarm at least 300mm away
from the beam.
300mm
>10% ceiling
height
• If depth of beam is greater than 10% of
the ceiling height, the beam should be
treated as a wall (alarms need to be on
either side of the beam).
300mm
Pitched roof
• Site at no more than 600mm vertically
below apex.
600mm
Wall mounted
150-300mm
• The top of the detection element is
between 150mm and 300mm below
the ceiling.
• Site at least 300mm from a
perpendicular wall.
* For full guidance on what type of alarm to install and where consult BS5839-6
78
300mm
Siting of Heat Alarms*
Flat ceiling
300mm
300mm
• Site at least 300mm from walls.
• Site at least 300mm from any
light fittings.
• Site as centrally as possible.
Flat ceilings with beams
300mm
• Site at least twice the depth of the
beam away e.g. 150mm beam depth:
site the alarm at least 300mm away
from the beam.
300mm
>10% ceiling
height
• If depth of beam is greater than 10% of
the ceiling height, the beam should be
treated as a wall (alarms need to be on
either side of the beam).
150mm
300mm
Pitched roof
• Site at no more than 600mm vertically
below apex.
600mm
* For full guidance on what type of alarm to install and where consult BS5839-6
79
Siting of CO Alarms*
When installing a CO alarm in a room where there is an appliance fitted
Ceiling mounted
300mm
300mm
• Site at least 300mm from walls.
• Site at least 300mm from any
light fittings.
• Site between 1 to 3 metres from the
fuel burning appliance.
1-3m
• If the room has a partition, site the
alarm on the side of the appliance.
Wall mounted in a bedroom
• Site close to the ceiling but at least
150mm down.
• Site at least 300mm from a
perpendicular wall.
• Site between 1 to 3 metres from the
fuel burning appliance.
*The below guidance is taken from BS EN 50292-2013, for further advice please refer to the standard.
80
1-3m
150mm
300mm
Siting of CO Alarms*
When installing a CO alarm in a room where there is no appliance fitted
Wall mounted
• Site at the breathing height of the
occupants (bed height).
• Site at the breathing height of the
occupants (seated height).
*The below guidance is taken from BS EN 50292-2013, for further advice please refer to the standard.
81
Performing a Risk Assessment
An example of a Fire Risk Assessment structure
Identify fire hazards
Step 1:
• Sources of ignition
• Sources of fuel
• Sources of oxygen
Identify people at risk
Step 2:
•
•
•
•
People with disabilities
Parents with young children
Unaccompanied children and young people
Anyone who has difficulty understanding English
Evaluate, remove or reduce and protect against
remaining risk
Preventative measures
• Evaluate the risk of a fire occurring
• Evaluate the risk to people from fire starting in the premises
• Remove or reduce fire hazards that may cause a fire
Step 3:
• Remove or reduce the risks to people from a fire
Protective measures
•
•
•
•
•
•
Detection and warning
Fire fighting
Escape routes
Lighting
Signs and notices
Maintenance
Record, plan, instruct, inform and train
• Record significant findings and action taken
Step 4:
• Prepare an emergency plan
• I nform relevant people, provide instruction
and co-operate and co-ordinate with others
• Provide training
Review
Step 5:
82
• Keep assessment under constant review
• Revise where necessary
Minimum Grade and Category of Detection*
BS 5839 Pt.6:2013
Fire detection and fire alarm system for protection of life
in typical premises
New or materially altered
premises conforming to
guidance that supports
national building
regulations
Class of premises
Grade
Category
Existing premises
conforming to current
guidance that supports
national building
regulations
Grade
Existing premises where
structural fire precautions
are of a lower standard
than those recommended
in current guidance that
supports national building
regulations
Category
Grade
Category
Single-family dwellings and shared houses with no floor greater than 200m2 in area
Owner-occupied bungalow,
flat or other single-storey
unit
D
LD2
F
LD3
D
LD2
Rented bungalow, flat or
other single-storey unit
D
LD2
D
LD3
D
LD2
Owner-occupied
maisonette, or owneroccupied two-story house
D
LD2
F
LD3
D
LD2
Rented maisonette or
rented two-storey house
D
LD2
D
LD3
D
LD2
Three-storey house
D
LD2
D
LD3
D
LD2
Four (or more) storey house
A
LD2
D
LD2
A
LD2
Single-family dwellings and shared houses with one or more floors greater than 200m2 in area
Bungalow, flat or other
single-storey unit
D
LD2
D
LD3
D
LD2
Maisonette or two-storey
house
A
LD2
A
LD2
A
LD2
Three (or more) storey
house
Grade A, Category LD2, with detectors sited in accordance with the recommendations
of BS 5839-1 for Category L2 system
Houses in multiple occupation
HMOs of one or two-storeys
with no floor greater than
200m2 in area
D
LD2
D
LD3
D
LD2
Other HMOs: Individual
dwelling units, within the
HMO, comprising two or
more rooms
D
LD2
D
LD3
D
LD2
Communal areas of the
HMO
Grade A, Category LD2, with detectors sited in accordance with the recommendations
of BS 5839-1 for Category L2 system
Sheltered housing
Individual dwelling units
Communal area
D
LD2
D
LD3
D
LD2
Housing provided NHS supported living in the community
All premises
Grade A, Category LD1, with detectors sited in accordance with the recommendations
of BS 5839-1 for Category L1 system
*The below guidance is taken from BS 5839 Pt.6: 2013, for further advice please refer to the standard. However other relevant standards and guidance exist, for
example the Local Authority Co-ordinators of Regulatory Services (LACoRS).
83
BS 5839: Part 6 System Grades & Categories
System Grades
GRADE
A
A fire detection and fire alarm system which incorporates
control and indicating equipment installed to BS 5839: Part 1.
GRADE
A fire detection and fire alarm system comprising of fire detectors
other than smoke alarms and heat alarms, fire alarm sounders and
control and indicating equipment.
GRADE
A system of fire detection and alarm sounders (which may be
combined in the form of smoke alarms) connected to a common
mains power supply with back-up and indicating equipment.
B
C
GRADE
D
GRADE
E
GRADE
F
Mains powered alarms with an integral stand-by
power supply(battery back up).
Mains powered alarms with no stand-by power supply.
Battery powered alarms.
Categories
LD1
MAXIMUM
PROTECTION
LD2
ADDITIONAL
PROTECTION
LD3
MINIMUM
PROTECTION
84
Alarms in all circulation spaces that form part of escape routes and all areas
where a fire might start, but not bathrooms, shower rooms or toilets.
In all circulation spaces that form part of escape routes and rooms
or areas that present a high fire risk.
Alarms in all circulation spaces that form part of escape routes.
Specification Generator
Using our Specification Generator
On our website you can find a link to our online specification generator. In 4 simple steps
you can create a tailor made specification which produces a downloadable document.
Select property type
Step 1:
•
•
•
•
•
Single storey property
2-3 storey house
4+ storey house
1-2 storey HMO
3+ storey HMO
Select level of protection
Step 2:
•
•
•
•
LD1
LD2
LD3 + Kitchen
LD3
Select interconnection
Step 3:
• Hardwired
• Wireless
Select accessories
Step 4:
• Alarm control unit
• CO alarm
sonasafety.com/specgenerator
85
Contact Sprue
Contacting Sprue is easy
If you’d like to do business with Sprue, here’s how to get in touch with us:
LEICESTER
Sales Support
[email protected]
SUTTON
COLDFIELD
Head office
NUNEATON
Sprue Safety Products Ltd,
Vanguard Centre,
Sir William Lyons Road,
Coventry
CV4 7EZ UK
BIRMINGHAM
Main Switchboard
024 7771 7700
Fax
024 7669 3610
COVENTRY
RUGBY
ROYAL
LEAMINGTON SPA
REDDITCH
SANDHURST
Trade Sales
CHELTENHAM
[email protected]
Main Switchboard
024 7771 7700
Fax
01452 729525
M5
SHURDINGTON
A38
A4
M5
17
A4
6
Unit 6, Carter Court,
Davy Way,
Waterwells Business Park,
Quedgeley,
Gloucester,
GL2 2DE UK
TUFFLEY
M5
QUEDGELEY
86
BIRDLIP
CRANHAM
Notes
87
HEAD OFFICE
Sprue Safety Products Ltd.
Vanguard Centre, Sir William Lyons Road,
Coventry, CV4 7EZ UK.
TRADE SALES
Sprue Safety Products Ltd.
Unit 6, Carter Court, Davy Way, Waterwells Business Park,
Quedgeley, Gloucester, GL2 2DE UK.
[email protected]
MAIN SWITCHBOARD
024 7771 7700
CUSTOMER SERVICE / TECHNICAL ENQUIRIES
sprue.com
GN3567R2
0800 141 2561