Multi-Channel Measuring and Control System DULCOMARIN® II
Transcription
Multi-Channel Measuring and Control System DULCOMARIN® II
Complete operating instructions Multi-Channel Measuring and Control System DULCOMARIN® II Swimming Pool Controller and Disinfection Controller DXCa A0204 Please enter the identity code of your device here! DXCa _ _ _ _ _ _ _ _ _ _ _ _ _ Please carefully read these operating instructions before use! · Do not discard! The operator shall be liable for any damage caused by installation or operating errors! Technical changes reserved. 986880 BA DC 078 04/12 EN ProMinent Dosiertechnik GmbH Im Schuhmachergewann 5 - 11 69123 Heidelberg Telephone: +49 6221 842-0 Fax: +49 6221 842-419 email: [email protected] Internet: www.prominent.com 986880, 2, en_GB © 2012 2 Supplemental instructions General non-discriminatory approach In order to make it easier to read, this document uses the male form in grammatical structures but with an implied neutral sense. It is aimed equally at both men and women. We kindly ask female readers for their understanding in this simplification of the text. Supplementary information Read the following supplementary information in its entirety! The following are highlighted separately in the document: n Enumerated lists Instructions ð Results of the instructions Information This provides important information relating to the cor‐ rect operation of the system or is intended to make your work easier. Safety information Safety information are provided with detailed descriptions of the endangering situation, see Ä Chapter 2.1 ‘Explanation of the safety information’ on page 15 3 Overall Table of Contents Overall Table of Contents 4 EN Multi-Channel Measuring and Control System DULCO‐ MARIN® II Swimming Pool Controller and Disinfection Controller DXCa ................................................................... 8 1 Device identification / identity code................................ 12 2 Introduction.................................................................... 15 2.1 Explanation of the safety information.......................... 15 2.2 Users' qualifications.................................................... 16 3 Safety and responsibility................................................ 18 3.1 General safety information.......................................... 18 3.2 Correct and proper use............................................... 18 4 Planning aids and requirements for the installation site ................................................................................ 20 4.1 Requirements for the installation site.......................... 20 4.2 Determine the requirement for cables and accesso‐ ries.............................................................................. 21 4.3 Allocate power supply modules (DULCOMARIN® II DULCO-Net)............................................................... 25 4.4 Routing the CAN bus backbone................................. 26 5 Assembly and installation.............................................. 27 5.1 Procedure with DXC housing (large).......................... 27 5.2 Procedure with DXM housing (small)......................... 34 5.3 install the CAN bus cable............................................ 37 6 Device overview and operating elements...................... 43 7 Functional description (general).................................... 45 8 Maintenance, repairs and disposal................................ 48 8.1 Disposal of used parts................................................ 49 9 Technical data spare parts and accessories................. 50 10 EC Declaration of Conformity and fulfilled standards. . 51 11 Wiring diagram DULCOMARIN® II compact ............... 52 EN Multi-Channel Measuring and Control System DULCO‐ MARIN® II Swimming Pool Controller and Disinfection Controller DXCa ................................................................. 1 Further applicable documents....................................... 2 Introduction.................................................................... 2.1 Explanation of the safety information.......................... 2.2 Users' qualifications.................................................... 3 Safety and responsibility................................................ 3.1 General Safety Information......................................... 3.2 Correct and Proper Use ............................................. 4 Functional description.................................................... 5 Control elements ........................................................... 5.1 Function of the buttons............................................... 5.2 Access code (password)............................................. 6 Commissioning: Configuring the CAN modules............. 6.1 Logging modules on and off....................................... 6.2 Commissioning CAN-Beta pump................................ 6.3 Commissioning R module........................................... 7 Structure of the of the operating menu.......................... 7.1 Structural principle...................................................... 7.2 Permanent display...................................................... 7.3 Central menu item...................................................... 57 61 62 62 63 65 65 66 67 68 68 70 72 72 74 77 79 79 80 81 Overall Table of Contents 7.4 Log off SD card safely................................................ 82 7.5 Generally applicable states......................................... 83 7.6 Menus underneath the central menu item.................. 85 7.7 Submenus of the parametric assignment menu......... 87 8 Calibration...................................................................... 88 8.1 Calibration of pH measured variable.......................... 89 8.2 Redox measured variable........................................... 93 8.3 Calibrate measured variable "chlorine free"............... 94 8.4 Calibrate measured variable "Total chlorine".............. 99 8.5 Calibrate measured variable for fluoride (F-)............ 105 8.6 Calibrate measured variable for chlorine dioxide (CIO2)........................................................................ 107 8.7 Calibrate measured variable hydrogen peroxide (H2O2)....................................................................... 111 8.8 Measured variable chlorite (CIO2 -)........................... 114 8.9 Calibrate measured variable for peracetic acid (PES)........................................................................ 8.10 Calibration measured variable temperature............ 9 Assign parameters....................................................... 9.1 All parameters........................................................... 9.2 Measurement............................................................ 9.3 Control...................................................................... 9.4 Set mA output........................................................... 9.5 Alarm settings........................................................... 9.6 Parametric assignment flow meter........................... 9.7 Setting Eco!Mode..................................................... 9.8 Chlorine dosing redox dependent............................. 10 Configure................................................................... 10.1 Configuring module DXMaM................................... 10.2 Configuring module DXMaA................................... 10.3 Configuring module DXMaP................................... 10.4 Configuration for free chlorine module.................... 10.5 Configuration for total chlorine module................... 10.6 Configuration for chlorine module........................... 10.7 Configuration of R module (control module for chlorine gas metering device) ................................ 10.8 Configuration for P1 module (metering pump module) .................................................................. 10.9 G module (limit value module) configuration.......... 10.10 I module (current input module) configuration ..... 11 Maintenance ............................................................. 11.1 Configure maintenance timer.................................. 12 Troubleshooting......................................................... EN DULCOMARIN® II, Screen Plotter Operation................... 1 About this product........................................................ 1.1 Storage and transport............................................... 2 Setting up the screen plotter........................................ 3 Layout and function of the screen plotter..................... 4 Using an SD card......................................................... 5 Troubleshooting........................................................... 6 Technical data and accessories.................................. 117 119 120 120 120 127 141 142 144 145 146 148 149 156 162 164 165 166 167 168 170 171 175 175 177 193 198 198 199 201 203 206 207 5 Overall Table of Contents 6 EN DULCOMARIN® II, A-Module (Control Module, Pump and Standard Signal Outputs mA) DXMaA.............................. 1 Identity code................................................................ 2 About this device......................................................... 2.1 Safety chapter........................................................... 2.2 Storage and transport............................................... 3 Assembly and installation............................................ 4 Technical data............................................................. EN DULCOMARIN® II, G-Module (Limit Value and Alarm Gen‐ erator Module DXMaG)..................................................... 221 1 Identity code................................................................ 226 2 About this device......................................................... 227 2.1 Safety chapter........................................................... 227 2.2 Storage and transport............................................... 227 3 Assembly and installation............................................ 228 4 Technical data............................................................. 230 EN DULCOMARIN® II, I-Module (Current Input Module, Standard Signal Inputs mA) DXMaI.................................. 1 Identity code................................................................ 2 About this device......................................................... 2.1 Safety chapter........................................................... 2.2 Storage and transport............................................... 3 Assembly and installation............................................ 4 Technical data............................................................. 231 236 238 238 238 239 241 EN DULCOMARIN® II, M-Module DXMaM (Measurement Module for pH, Redox, Temperature)............................... 1 Identity code................................................................ 2 Safety and responsibility.............................................. 3 Handling the device..................................................... 4 Terminal Wiring Diagram............................................. 5 Control elements.......................................................... 5.1 Layout of the operating menu................................... 6 Adjustment................................................................... 6.1 Basic settings............................................................ 6.2 Calibration................................................................. 243 248 250 251 252 255 256 259 259 260 EN DULCOMARIN® II, N-Module (Power Supply Module without Relay) DXMaN...................................................... 1 Identity code................................................................ 2 About this device......................................................... 2.1 Safety chapter........................................................... 2.2 Storage and transport............................................... 3 Assembly and installation............................................ 3.1 Repairs (fuse change only)....................................... 269 274 276 276 276 277 279 EN DULCOMARIN® II, P-Module (Power Supply Module with Relay) DXMaP.................................................................. 1 Identity code................................................................ 2 About this device......................................................... 2.1 Safety chapter........................................................... 2.2 Storage and transport............................................... 3 Assembly and installation............................................ 3.1 Repairs (fuse change only)....................................... 281 286 288 288 288 289 291 209 214 216 216 216 217 220 Overall Table of Contents 3.2 Arrangement of LEDs............................................... 292 3.3 Example for connection of a solenoid valve............. 293 4 Technical data............................................................. 294 EN DULCOMARIN® II, R-Module (Control Unit for Chlorine Gas Metering Device) DXMaR.......................................... 1 Identity code................................................................ 2 Safety and responsibility.............................................. 3 Handling the device..................................................... 4 Terminal Wiring Diagram............................................. EN DULCOMARIN® II Function extension with M, A and P module.............................................................................. 1 Function MAP.............................................................. 2 Circulation quantity allocation...................................... 2.1 Specification of the respective circulating operating conditions.................................................................. 3 Flow control [water flow] ............................................. 4 Timer settings.............................................................. 5 Water top-up................................................................ 6 Control of the backwashing valves.............................. 295 298 300 301 302 305 310 311 313 314 317 319 320 7 Assembly instructions Multi-Channel Measuring and Control System DULCOMARIN® II Swimming Pool Controller and Disinfection Controller DXCa Part 1: Assembly and installation A0507 Please enter the identity code of your device here! DXCa _ _ _ _ _ _ _ _ _ _ _ _ _ Please carefully read these operating instructions before use! · Do not discard! The operator shall be liable for any damage caused by installation or operating errors! Technical changes reserved. Part no. 986907 BA DC 080 04/12 EN ProMinent Dosiertechnik GmbH Im Schuhmachergewann 5 - 11 69123 Heidelberg Telephone: +49 6221 842-0 Fax: +49 6221 842-419 email: [email protected] Internet: www.prominent.com 986907, 2, en_GB © 2012 9 Supplemental instructions Further applicable documents These operating instructions and supplementary instructions are only valid in combination with the following operating and supple‐ mentary instructions: n Multi-channel measuring and control system operating instruc‐ tions DULCOMARIN® II , Swimming Pool Controller and Disin‐ fection Controller DXCa Part 2: Operation n Supplementary instructions DULCOMARIN® II, Screen plotter operation n Supplementary instructions DULCOMARIN® II, M-Module (measuring module for pH, redox [ORP], temperature) DXMaM connection n Supplementary instructions DULCOMARIN® II, A-Module (con‐ trol module, pump and standard signal outputs mA) DXMaA n Supplementary instructions DULCOMARIN® II, N-Module (power supply module without relay) DXMaN n Supplementary instructions DULCOMARIN® II, P-Module (power supply module with relay) DXMaP n Supplementary instructions DULCOMARIN® II, I-Module (cur‐ rent input module, standard signal inputs mA) DXMal 10 Table of contents Table of contents 1 Device identification / identity code..................................... 12 2 Introduction......................................................................... 15 2.1 Explanation of the safety information.......................... 15 2.2 Users' qualifications.................................................... 16 3 Safety and responsibility..................................................... 18 3.1 General safety information.......................................... 18 3.2 Correct and proper use............................................... 18 4 Planning aids and requirements for the installation site ..... 4.1 Requirements for the installation site.......................... 4.2 Determine the requirement for cables and accesso‐ ries.............................................................................. 4.3 Allocate power supply modules (DULCOMARIN® II DULCO-Net)............................................................... 4.4 Routing the CAN bus backbone................................. 21 5 Assembly and installation................................................... 5.1 Procedure with DXC housing (large).......................... 5.1.1 Wall mounting.......................................................... 5.1.2 Control panel mounting............................................ 5.1.3 Installation (electrical).............................................. 5.1.4 Connect the coaxial cable........................................ 5.1.5 Connecting the terminals......................................... 5.2 Procedure with DXM housing (small)......................... 5.2.1 Mounting (mechanical)............................................ 5.2.2 Installation (electrical).............................................. 5.3 install the CAN bus cable............................................ 5.3.1 Connections outside the housing............................. 5.3.2 Connections inside the DXC housing...................... 27 27 27 29 30 33 33 34 34 35 37 38 41 6 Device overview and operating elements........................... 43 7 Functional description (general).......................................... 45 8 Maintenance, repairs and disposal..................................... 48 8.1 Disposal of used parts................................................ 49 9 Technical data spare parts and accessories....................... 50 10 EC Declaration of Conformity and fulfilled standards......... 51 11 Wiring diagram DULCOMARIN® II compact ...................... 52 12 Index................................................................................... 56 20 20 25 26 11 Device identification / identity code 1 Device identification / identity code The identity code describes the DULCOMARIN® II, compact controller 1) The supplied cable is for connection to a hub, switch, router or an intranet. For direct connection of the DULCOMARIN® II to a PC/ MAC, the supplied LAN coupling and category 5 crossover cable are required. The maximum LAN cable length is approximately 100 m. To operate the web server on a PC we recommend Microsoft® Internet Explorer 5 or higher as the browser. The scope of supply of the DXCa includes: – – – – – DXCa Multi-channel measuring and control system - DULCOMARIN® 1 T-coupler 1 CAN connection cable 1 terminating resistance coupling and 1 terminating resistance plug 1 SD memory card 64 MB or greater 1 card reader suitable for PCs II Series DXC Mounting type: W Wall mounted (IP 65) S Control cabinet (IP 54) Version: 0 With operating elements D With operating elements for use in drinking water/disinfection applications Communication interfaces: 0 none 5 Embedded Web-Server, LAN incl. 5 m LAN patch cable 1:1, LAN coupling, 5 m cross-over cable 1) 6 OPC-Server + Embedded Web-Server, LAN incl. 5 m LAN patch cable 1:1, LAN coupling, 5 m cross-over cable 1) Option: 1 Screen plotter with data logger incl. SD card and USB card reader for PC Module 1: M M module, measuring module pH, redox, temperature I I module, current input module, 3x mA, 0/4 ... 20 mA Module 2: 12 0 not occupied A A module, control module: 3 pumps and 4 analog out‐ puts Device identification / identity code DXCa Multi-channel measuring and control system - DULCOMARIN® I II Series DXC I module, current input module, 3x mA, 0/4 ... 20 mA Application: S Swimming Pools D Disinfection, general Preset language: DE German EN English ES Spanish FR French IT Italian PL Polish Certification: 01 CE mark The identity code describes the complete DULCO‐ MARIN® II DULCO® Net Central Unit. If the central unit is populated with modules, then the following applies: Module 1 preferably as M module Module 2 preferably allocated to the A module. Module 3 must always be allocated to the P or N module. DXCa Multi-channel measuring and control system - DULCOMARIN® 1) Module 1 preferably as M module 2) only in version: "2" without controls II Series DXC Mounting type: W Wall mounted (IP 65) S Control cabinet (IP 54) Version: 0 With operating elements 2 Without operating elements Communication interfaces: 0 none 5 Embedded Web-Server, LAN incl. 5 m LAN patch cable 1:1, LAN-coupling, 5 m cross-over-cable 1) 6 OPC-Server + Embedded Web-Server, LAN incl. 5 m LAN patch cable 1:1, LANcoupling, 5 m cross-over-cable 1) 13 Device identification / identity code DXCa Multi-channel measuring and control system - DULCOMARIN® II Series DXC Option: 0 Without screen plotter 2) 1 Screen plotter with data logger incl. SD card and USB card reader for PC Module 1: 0 not occupied M M module, measuring module pH, redox, temperature A A module, control module: 3 pumps and 4 analog outputs I I module, current input module, 3x mA, 0/4 ... 20 mA Module 2: 0 not occupied A A module, control module: 3 pumps and 4 analog outputs M M module, measuring module: pH, redox, temperature I I module, current input module, 3x mA, 0/4 ... 20 mA Module 3: 0 not occupied P P module, power supply, 1 alarm relay, 3 solenoid valve relays N N module, power supply without relay A A module, control module: 3 pumps and 4 analog out‐ puts M M module, measuring module: pH, redox, temperature Application: S Swimming Pools D Disinfection, general Preset language: DE German EN English ES Spanish FR French IT Italian PL Polish Certification: 01 14 CE mark Introduction 2 Introduction The operating instructions describe the technical data and func‐ tions of the multi-channel measuring and control system DULCOMARIN® II Swimming Pool Controller and Disinfection Con‐ troller DXCa. The operating instructions subsequently refer to the system merely as DXCa. 2.1 Explanation of the safety information Introduction These operating instructions provide information on the technical data and functions of the product. These operating instructions pro‐ vide detailed safety information and are provided as clear step-bystep instructions. The safety information and notes are categorised according to the following scheme. A number of different symbols are used to denote different situations. The symbols shown here serve only as examples. DANGER! Nature and source of the danger Consequence: Fatal or very serious injuries. Measure to be taken to avoid this danger Danger! – Denotes an immediate threatening danger. If this is disregarded, it will result in fatal or very serious injuries. WARNING! Nature and source of the danger Possible consequence: Fatal or very serious injuries. Measure to be taken to avoid this danger Warning! – Denotes a possibly hazardous situation. If this is disregarded, it could result in fatal or very serious injuries. CAUTION! Nature and source of the danger Possible consequence: Slight or minor injuries, mate‐ rial damage. Measure to be taken to avoid this danger Caution! – Denotes a possibly hazardous situation. If this is disregarded, it could result in slight or minor inju‐ ries. May also be used as a warning about material damage. 15 Introduction NOTICE! Nature and source of the danger Damage to the product or its surroundings Measure to be taken to avoid this danger Note! – Denotes a possibly damaging situation. If this is disregarded, the product or an object in its vicinity could be damaged. Type of information Hints on use and additional information Source of the information, additional measures Information! – Denotes hints on use and other useful information. It does not indicate a hazardous or damaging sit‐ uation. 2.2 Users' qualifications WARNING! Danger of injury with inadequately qualified personnel! The operator of the plant / device is responsible for ensuring that the qualifications are fulfilled. If inadequately qualified personnel work on the unit or loiter in the hazard zone of the unit, this could result in dangers that could cause serious injuries and material damage. – – All work on the unit should therefore only be con‐ ducted by qualified personnel. Unqualified personnel should be kept away from the hazard zone Training Definition Instructed personnel An instructed person is deemed to be a person who has been instructed and, if required, trained in the tasks assigned to him/her and possible dangers that could result from improper behaviour, as well as having been instructed in the required protective equipment and protective measures. Trained user A trained user is a person who fulfils the requirements made of an instructed person and who has also received additional training specific to the system from ProMinent or another authorised distribution partner. Trained qualified per‐ sonnel A qualified employee is deemed to be a person who is able to assess the tasks assigned to him and recognize possible hazards based on his/her training, knowledge and experience, as well as knowledge of pertinent regula‐ tions. The assessment of a person's technical training can also be based on several years of work in the relevant field. 16 Introduction Training Definition Electrician Electricians are deemed to be people, who are able to complete work on elec‐ trical systems and recognize and avoid possible hazards independently based on his/her technical training and experience, as well as knowledge of pertinent standards and regulations. Electricians should be specifically trained for the working environment in which the are employed and know the relevant standards and regulations. Electricians must comply with the provisions of the applicable statutory direc‐ tives on accident prevention. Customer Service depart‐ ment Customer Service department refers to service technicians, who have received proven training and have been authorised by ProMinent to work on the system. Note for the system operator The pertinent accident prevention regulations, as well as all other generally acknowledged safety regulations, must be adhered to! 17 Safety and responsibility 3 Safety and responsibility 3.1 General safety information WARNING! Unexpected start-up The DULCOMARIN® II has no on/off switch. It starts working as soon as voltage is supplied to the mains cable. Possible consequence: Fatal or very serious injuries – – Measure: Ensure that there can be no unauthor‐ ised access to the device Match your actions to this particular feature – Only connect the device to the mains if all pre‐ paratory tasks have been completed and the device can be placed in service without any danger WARNING! Possibility of overdosing of feed chemicals Prevent overdosing of feed chemicals in the event of sensor failure or removal. Possible consequence: Fatal or very serious injuries – Measure: Configure your processes so that uncon‐ trolled dosing during sensor selection or malfunc‐ tion is not possible WARNING! Maintenance of the degree of protection Screw the transparent interface cover in place over the LEDs so that leak-tightness is recreated, if it has been opened. Otherwise the IP 65 rating is not achieved. CAUTION! Only use the devices which are described in these operating instructions with CANopen third party devices which are certified. 3.2 Correct and proper use NOTICE! Compensation for control deviations Damage to the product or its surroundings – 18 The controller can be used in processes, which require compensation of > 30 seconds Safety and responsibility NOTICE! Correct and proper use The unit is intended to measure and regulate liquid media. The marking of the measured variables is located on the controller and is absolutely binding. The unit may only be used in accordance with the technical details and specifications provided in this operating manual and in the operating manuals for the individual components (such as, for example, sensors, fittings, calibration devices, metering pumps etc.). Any other uses or modifications are prohibited. 19 Planning aids and requirements for the installation site 4 Planning aids and requirements for the installation site Ambient conditions CAUTION! Protect the module against moisture and the effects of chemicals, even while still packaged. The DULCOMARIN® II is resistant to the normal atmospheres in plant rooms Store and transport the module it its original packaging. Ambient conditions for storage and transportation: n Temperature: -10 °C ... 70 °C n Max. permissible relative humidity: 95 %, non-condensing (DIN IEC 60068-2-30) Ambient conditions for operation: n Temperature: 0 °C ... 50 °C n Max. permissible relative humidity: 95 %, non-condensing (DIN IEC 60068-2-30) 4.1 Requirements for the installation site n n n n 20 Do not position the DULCOMARIN® II outside Protect the DULCOMARIN® II against sun and frost Secure the DULCOMARIN® II against unauthorized access A mains connection is necessary Planning aids and requirements for the installation site 4.2 Determine the requirement for cables and accessories Fig. 1: A typical complete measuring point could appear as shown: Item. Quantity Description Part no. 1 3 T-coupler M12 5-pole CAN 1022155 2 1 M module DXMa M W 0 S DE 01 3 4 Connecting cable - CAN, M12, 5 pole, 0.5 m 1022137 4 1 Chlorine sensor CLE 3.1-CAN-10 ppm 1023426 5 1 Chlorine sensor CTE 1 CAN-10 ppm 1023427 6 1 Redox sensor RHES-Pt-SE 150703 7 1 pH sensor PHES 112 SE 150702 Coaxial cable 2 m - SN6 - pre-assembled 1024106 8 9 2 Control lead 2 x 0.25 mm2 725122 10 2 Connecting cable - CAN, M12, 5 pole, 0.5 m 1022137 - 1 In-line probe housing DGMa 3 2 2 T 0 0 0 The central unit and each external module includes enclosed accessories. 21 Planning aids and requirements for the installation site Fig. 2: Central unit DXCa Accessories, supplied Item. Quantity Description Part no. 1 1 Connecting cable - CAN, M12, 5 pole, 0.5 m 1022137 2 1 T-coupler, M12,5-pole CAN 1022155 - 1 Terminating resistance M12 socket [male ] 1022154 - 1 Terminating resistance M 12 plug [female] 1022592 22 Planning aids and requirements for the installation site A0487 Fig. 3: External modules DXMa Accessories, supplied Item. Quantity Description Part no. 1 1 T-coupler, M12,5-pole CAN 1022155 2 1 Connecting cable - CAN, M12, 5 pole 0.5 m 1022137 23 Planning aids and requirements for the installation site Fig. 4: Beta/4 CANopen Accessories, supplied Item. Quantity Description Part no. 1 1 T-coupler, M12,5-pole CAN 1022155 2 1 Connecting cable - CAN, M12, 5 pole 1 m 1022139 Fig. 5: Sensors DXUa Accessories, supplied Item. Quantity Description Part no. 1 1 T-coupler, M12,5-pole CAN 1022155 2 1 Connecting cable - CAN, M12, 5 pole 0.5 m 1022137 24 Planning aids and requirements for the installation site 1. Determine the requirement for power supply modules, see 2. Determine the requirement for connection cables between the external modules 3. Determine the requirement for holding clamps for the con‐ nection cables (ASV pipe clips, 16 mm, order no. 359904 Ä Chapter 4.3 ‘Allocate power supply modules (DULCO‐ MARIN® II DULCO-Net)’ on page 25 4.3 Allocate power supply modules (DULCOMARIN® II DULCO-Net) Determine the number of additionally required power supply mod‐ ules (N modules and P modules). 1. Ensure that for each power supply module there is a power outlet The distance between the power supply modules should not exceed 50 m. 2. Distribute the power supply modules as uniformly as possible over the CAN bus line. 3. With an A module with connected plotters: arrange one of the power supply modules as close as possible to the A module Locate the power supply module in the CAN bus backbone (main line) (DULCOMARIN® II DULCO-Net) The central unit always contains a power supply module. Number of pools Additional N- or P-mod‐ ules Number of pools Additional N- or P-mod‐ ules 1 - 9 4 2 - 10 5 3 1 11 5 4 2 12 6 5 2 13 6 6 3 14 7 7 3 15 7 8 4 16 8 Divide the number of pools by ‘2’ . If a remainder is obtained, round down: (Exception: number of pools = 2) 25 Planning aids and requirements for the installation site 4.4 Routing the CAN bus backbone CAUTION! Maximum backbone length Possible consequence: Malfunctions. – The maximum backbone length (without branching cables) must be less than 400 m CAUTION! Maximum length of branching cables Possible consequence: Malfunctions. The T-pieces and connecting cables (branching cables) enclosed with the modules (M-, A-, G-, N-, R-, I- modules, CAN sensors and metering pumps with CAN bus must be used. Branching cables are the connections branching from the CAN bus backbone to the modules. The external modules can be placed in any sequence along the CAN bus backbone. The operating instruc‐ tions show for example possible sequences of the external modules. Each CAN cable has a plug or coupling on each end so that these can be coupled together in sequence to create longer cables. Rule Arrange the external modules in groups for each pool. First assemble and install the external modules and their attachments. Only then should you connect the external modules with the CAN bus backbone and with each other via the the shortest route. 26 Description Part no. Connecting cable - CAN, M12, 5 pole, 0.5 m 1022137 Connecting cable - CAN, M12, 5 pole, 1 m 1022139 Connecting cable - CAN, M12, 5 pole, 2 m 1022140 Connecting cable - CAN, M12, 5 pole, 5 m 1022141 Connecting cable - CAN sold by the metre 1022160 Assembly and installation 5 Assembly and installation 5.1 Procedure with DXC housing (large) The DXC housing is suitable for mounting on a wall or in a control panel 5.1.1 Wall mounting Mounting materials (contained in the scope of delivery) n n n n Wall mounting 1 x wall bracket 4 x PT screws 5 x 35 mm 4 x washers 5.3 4 x rawl plug Ø 8 mm, plastic Take the wall bracket out of the DXC housing A0490 Fig. 6: Removing the wall bracket 1. Pull the two snap hooks (1) outwards ð The wall brackets snaps slightly downwards. 2. Push the wall bracket downwards (2) from the DXC housing and fold (3) it out 3. Use the wall bracket as a drilling template to mark the posi‐ tions of four drill holes 4. Drill the holes: Ø 8 mm, d = 50 mm 27 Assembly and installation A0491 Fig. 7: Fitting the wall bracket 5. Screw the wall bracket into position using the washers, see Fig. 7 A0492 Fig. 8: Fitting the wall bracket 28 6. Hook the bottom of the DXC housing (1) into the wall bracket 7. Lightly press the DXC housing at the top (2) against the wall bracket 8. Then check that the DXC housing is hooked in at the top and press down (3) until it audibly engages Assembly and installation 5.1.2 Control panel mounting CAUTION! Thickness of the control panel The control panel must be sufficiently thick to ensure that after fitting it does not bend. With steel panels it must be at least 2 mm thick; select plastic correspond‐ ingly thicker. Only in this way can the IP 54 rating be attained. When fitted, the DXC housing extends approx. 45 mm from the control panel. A drilling template is enclosed. A0493 Fig. 9: Control panel mounting 1. Establish the exact position of the DXC housing using the drilling template on the control panel and secure it 2. Mark the holes for the attachment screws using a centre punch and the drilling holes for the cut-out using the drilling template 3. Drill four securing holes using a 5 mm Ø drill bit CAUTION! Take care not to cut yourself on the resulting edges. 4. Either punch the cut-out out or drill four inner holes using a 5 mm Ø drill bit and then cut the cut-out using a jigsaw 5. De-burr the resulting edges 6. Undo the four housing screws 7. Lift the front part out and disconnect the P module ribbon cable 29 Assembly and installation 8. Remove the front part 9. Now break out the necessary threaded holes of the lower series, see Ä Chapter 5.1.3 ‘Installation (electrical)’ on page 30 10. Screw the back part to the control panel (using the supplied PT screws) 11. Plug the ribbon cable back on 12. Move the front part into the ‘park position’ ð Now first electrically install the DULCOMARIN® II and then complete the control panel mounting. 13. Place the front part on the rear part of the DXC housing and screw it in 14. CAUTION! Protection class IP 54 Once again check the seating of the seal. Pro‐ tection class IP 54 is only achieved if the control panel mounting is correct. 5.1.3 Installation (electrical) WARNING! Failure of the circulating pumps In the event that the circulating pump fails, it is not suf‐ ficient to use the sample water limit contact of the inline probe housing on its own in order to stop the con‐ trol for the corresponding pool (contact K1 of the M module). The pool controller must also be set to Pause using the contact K2 ‘Pause control ’ of the M module. Suitable triggers are: – – – the zero volt contact of the filter control the zero volt contact of the circulation pump's motor protection switch a flow monitor in the circulation line WARNING! Safe operating status Both hardware and software safety precautions must be taken to ensure that the DULCOMARIN® II adopts a safe operating status in the event of a fault. E.g. use limit switches, mechanical locks, ... During installation the device must not be electrically live. The installation must only be carried out by technically trained personnel. Observe the technical data in these instructions. 30 Assembly and installation NOTICE! Cable strain relief With control panel mounting, the cables must be routed in a site-provided cable duct to ensure strain relief. 1. Plan which threaded holes shall be broken out (mark the desired threaded holes) CAUTION! When breaking open the threaded holes, avoid pushing the screwdriver deep into the housing. Parts inside the device could be damaged. A0494 Fig. 10: Breaking out threaded holes 2. To break out the threaded holes, punch the slit in the middle of the threaded holes using a screwdriver (tip width 3.5 - 4 mm, see Fig. 10) and lever the material out 3. De-burr the resulting edges 31 Assembly and installation 5. 4. 3. 2. 1. A0495 Fig. 11: Fitting the threaded cable glands 1. 2. 3. 4. 5. 4. Screw in the appropriate threaded cable glands (4) using suitable lock nuts (5) and tighten firmly 5. Insert multiple seal inserts (3) depending on the cable diam‐ eter being used 6. Guide the cables into the threaded cable glands 7. Further steps are contained in Ä Chapter 5.1.4 ‘Connect the coaxial cable’ on page 33 and Ä Chapter 5.1.5 ‘Connecting the terminals’ on page 33. 8. Tighten the union nuts (2) of the threaded cable glands so that they are properly sealed 9. Place the front part on the rear part 10. Manually tighten the four housing screws 11. 32 Blanking plug Union nut Multiple seal insert Threaded cable gland Lock nut CAUTION! Protection class IP 54 Once again check the seating of the seal. Pro‐ tection class IP 54 is only achieved if the control panel mounting is correct. Assembly and installation 5.1.4 Connect the coaxial cable The pH or redox sensor is connected using a coaxial cable A0496 Fig. 12: Removing the cable insulation 1. Uncover the cable shielding according to Fig. 12 2. Tightly clamp the shielding 5.1.5 Connecting the terminals The wiring diagram is contained in the appendix. Additionally there is an info field on the modules adja‐ cent to the terminals containing connection informa‐ tion. A0508 Fig. 13: Removing the cable insulation 1. Remove the insulation from the fork ends according to Fig. 13 and press on the corresponding cable end sleeves 2. Pull off the terminal blocks P1 to P4 for installation 3. To fit the cable, push the supplied screwdriver right into the square opening of the corresponding terminal in order to plug the cable end into the terminal block 4. Connect the cables according to the wiring diagram 5. Push the pulled-off terminal blocks back onto the circuit board after connecting the cables 33 Assembly and installation 6. Check the cabling using the wiring diagram 5.2 Procedure with DXM housing (small) 5.2.1 Mounting (mechanical) For wall mounting, please observe the following steps: Mounting materials (contained in the scope of delivery): n n n n n n 1 x wall/pipe bracket 2 x half-round head screws 5x45 mm 2 x washers 5.3 2 x rawl plug Ø 8 mm, plastic 1 x sealing cap 1 x safety screw (PT) 2 1 A0273 34 1. Remove the wall/pipe bracket from the DXM 2. Pull the two snap hooks outwards and push them upwards (1) 3. Fold the wall/pipe bracket away and pull it out (2) in a down‐ wards direction 4. Mark two drill holes diagonal to each other by using the wall/ pipe bracket as a drilling template 5. Drill the holes: Ø 8 mm, d = 50 mm Assembly and installation A0274 6. Tighten the wall/pipe bracket 7. Hook in the housing at the top in the wall/pipe bracket and push it using light pressure at the bottom against the wall/ pipe bracket. Then press the housing upwards, until it audibly engages 5.2.2 Installation (electrical) WARNING! Safe operating status During installation the device must not be electrically live. The installation must only be carried out by technically trained personnel. Observe the technical data in these instructions. NOTICE! Cable strain relief With control panel mounting, the cables must be routed in a site-provided cable duct to ensure strain relief. For wall mounting 1. 2. Undo the four housing screws. NOTICE! The hinge between the front and rear part of the housing cannot absorb high mechanical loading. When working on the front part of the housing you must support it. Raise the front part slightly forwards and then fold out to the left. 35 Assembly and installation A0272 3. The large threaded cable gland (M20 x 1.5) is only for use with the coaxial cable. Punch out as many threaded holes on the bottom side of the rear part as required A0497 Fig. 14 1. 2. 3. 4. 36 Threaded cable gland Reducing insert Clamping nut Terminal diagram 4. Screw the corresponding threaded cable glands (1) in and tighten 5. Insert the reducing inserts (2) in the threaded cable glands according to the cable cross section used 6. Guide the cables into the threaded cable glands Assembly and installation 7. Further steps are contained in Ä Chapter 5.1.4 ‘Connect the coaxial cable’ on page 33 and Ä Chapter 5.1.5 ‘Connecting the terminals’ on page 33 ð Thereafter please continue with the following steps: 8. Tighten the union nuts (3) of the threaded cable glands so that they are properly sealed 9. Fold the front part onto the rear part 10. NOTICE! Protection class IP 65 Once again check the seating of the seal. Pro‐ tection class IP 65 is only achieved if the control panel mounting is correct. As necessary, pull the front part slightly forwards to relieve the strain on the seal. Manually tighten the housing screws For control panel mounting (internal module) NOTICE! Cable strain relief With control panel mounting, the cables must be routed in a site-provided cable duct to ensure strain relief. Connect the cables as follows: Ä Chapter 5.1.4 ‘Connect the coaxial cable’ on page 33 and Ä Chapter 5.1.5 ‘Connecting the terminals’ on page 33 5.3 install the CAN bus cable CAUTION! Maximum backbone length Possible consequence: Malfunctions. – The maximum backbone length (without branching cables) must be less than 400 m CAUTION! Maximum length of branching cables Possible consequence: Malfunctions. The T-pieces and connecting cables (branching cables) enclosed with the modules (M-, A-, G-, N-, R-, I- modules, CAN sensors and metering pumps with CAN bus must be used. Branching cables are the connections branching from the CAN bus backbone to the modules. 37 Assembly and installation 5.3.1 Connections outside the housing CAUTION! T-coupling Never connect a T-coupling directly to the housing. The panel plug at the housing can break off. CAUTION! IP65 protection rating Screw in the CAN cable threaded cable glands by hand up to the stop. Otherwise the IP65 rating is not achieved. NOTICE! Sequentially screw together the individual parts of the CAN bus line starting from one side. Otherwise it can occur that at one or several points socket is aligned with socket or plug with plug. CAN devices always have plugs, never sockets. CAN bus line External modules, CAN version of chlorine sensor and DULCOMARIN® II are connected with each other via a CAN bus line. The individual CAN devices are inserted in this CAN bus line. There is a terminating resistance at each end of the CAN bus line. 38 1. Connect the supplied branching cables (e.g. 0.5 m) with a Tpiece on the end to each module and the DULCOMARIN® II 2. Screw the T-pieces of the CAN modules sequentially together using CAN cables or directly one after the other 3. On each of the remaining ends of the CAN bus line screw on a terminating resistance (1 x with a plug connector, 1 x with a socket connector). Assembly and installation Fig. 15: Inserting modules in the CAN bus line, compact version 1. 2. 3. 4. 5. CAN connection cable (branching cable 0.5 m) Terminating resistance, M12 socket T-coupling CAN connection cable Chlorine sensor CTE 6. 7. 8. 9. Chlorine sensor CLE CAN connection cable (branching cable 0.5 m) T-coupling Terminating resistance, M12 plug 39 Assembly and installation I. II. III. A0499 Fig. 16: Inserting modules in the CAN bus line I. II. 40 Control room Plant room, e.g. pool 1 III. A. Plant room, e.g. pool 2 Terminating resistance at the end of the CAN bus line (the system can be extended from here) Assembly and installation 5.3.2 Connections inside the DXC housing In general it is not necessary to make modification to the cable connectors inside the DXC housing All CAN bus cables end at the P module (power supply module with relay) or the N module (power supply module): n the 5 conductors of the panel plug CAN 1 (4) at (3) n the 16 pole ribbon cable of the display and operating module (not shown) at (2) n the 10 pole ribbon cable from the A module (control module) (6) and from the M module (measurement module) (5) at (1) A0500 Fig. 17: CAN cabling inside the DXC housing 1. 2. 3. 4. Cable connection to the display and operating module Cable connection to the A and M modules Cable connection to the panel plug CAN 1 Panel plug CAN 1 5. 6. 7. M module (measurement module) A module (control module) P module (power supply module with relay) 41 Assembly and installation If there is no P module or N module in the DXC housing: n Use a so-called L circuit board as a distributor for the CAN bus lines 2. 1. 4. 3. A0501 Fig. 18: Use of an L circuit board 1. 2. 42 Cable connection to the A and M modules Cable connection to the display and operating module 3. 4. Cable connection to the panel plug CAN 1 Panel plug CAN 1 Device overview and operating elements 6 Device overview and operating elements Keys A0502 Fig. 19: Keys 1. 2. 3. Enter key Start/Stop key ESC key 4. 5. Arrow keys Function keys, variably assigned 43 Device overview and operating elements Displays A0503 Fig. 20: Displays 1. LCD display 2. CAN 1-LED 3. Device LED 44 Functional description (general) 7 Functional description (general) A0504 Fig. 21: Measurement and control system for a filter circuit 1. 2. 3. 4. 5. 6. 7. 8. Multi-channel measuring and control system DULCOMARIN® II In-line probe housing DGMa Chlorine sensor CLE Chlorine sensor CTE T-coupling Terminating resistance, M12 socket Terminating resistance, M12 plug CAN connection cable 9. 10. 11. 12. 13. 14. 15. I. pH sensor ORP sensor Coaxial cable Control line Metering pump 1 Metering pump 2 Signal horn Plant room The multi-channel measuring and control system DULCOMARIN® II is suitable for controlling one or more systems (filtration circuits, pools ...) (version dependent). The base functions are distributed over the following modules: n n n n M module (measurement module) I module (current input module) A module (control module) R module (control module for chlorine gas metering devices) 45 Functional description (general) n P module (power supply module with relay) n N module (power supply module) M module (measurement module) n n n n n n n n n Measuring and control of the pH value Measuring and display (optional rules) of the redox potential Measuring and display of the temperature of the sample water Measuring and display of the circulating flow Monitoring the sample water Measuring the temperature of the sample water Measuring of free chlorine Measuring of total chlorine chlorine Displaying of combined chlorine – optional; calculated from total chlorine and free chlorine Chlorine sensors: n Measuring of free chlorine and temperature n Measuring of total available chlorine and temperature n Measuring of combined chlorine as a chlorine difference meas‐ urement I module (current input module) n Measurement monitoring and pause (2 contact inputs) n Connection of 3 sensors – (3 standard signal inputs 0/4...20 mA, of which 2 as 2-con‐ ductor connection) n Measuring and control of fluoride n Measuring and control of ClO2 n Measuring and control of chlorite n Measuring and control of H2O2 n Measuring of PES (peracetic acid) n Measuring and display of dissolved oxygen2 n Measuring and display of ammonia n Measuring and display of conductive conductivity n Measuring and display of flow n Measuring and display of turbidity n Measuring and display of UV intensity A module (control module) n Control of metering pumps for pH correction and disinfectant metering (over 3 frequency outputs, 3 contact inputs for pump errors or container level monitoring) n Output of measured values for pH value, redox potential, free chlorine or total chlorine or combined chlorine or temperature (4 analog outputs 0/4...20 mA, freely programmable and scal‐ able) R module (control module for chlorine gas metering devices) n Control of a servomotor with response signal for disinfectant metering (2 relay outputs, position feedback input) P module (power supply module with relay) n Control of solenoid valve or hose pump for pH correction (via pulse length output) n Control of solenoid valve or hose pump for disinfectant (via pulse length output) n Control of hose pump for flocculant (via pulse length output) on minimisation of the combined chlorine (via relay output) 46 Functional description (general) n Alarm (via relay output) n Provision of the CAN bus with supply voltage N module (power supply module) n Provision of the CAN bus with supply voltage CANopen metering pumps (Beta/4a, delta DLTa, Sigma S1CaS2Ca-S3Ca) n Metering of pH correction agents, disinfectants or flocculants 47 Maintenance, repairs and disposal 8 Maintenance, repairs and disposal Maintenance CAUTION! Solvent Do not under any circumstances use solvent to clean the surfaces. Solvent can attack the surfaces. Clean the housing with a damp cloth. Then rub dry. The DULCOMARIN® II is maintenance free. Replace the batteries after 10 years as a precautionary measure. The DULCOMARIN® II displays a warning should replacement be necessary sooner. Battery type: CR2032, 3 V approx. 190 mAh The battery is clamped in a holder on the rear side of the DXC housing upper section. A0505 Fig. 22: Removing the battery 1. Unscrew the four retaining screws at the front on the housing upper section and take the housing upper section off from the housing lower section. NOTICE! Hazardous waste The battery is hazardous waste. It must be disposed of separately. Observe the conditions which apply on your site. 2. Press on the holder lug to release the battery from the holder, see Fig. 22 3. Insert a new battery in the holder ð In so doing avoid pressing with the fingers on the battery poles. This will result in poor contacts. Repairs 48 4. Place the housing upper section on the housing lower section 5. Manually tighten the four retaining screws For repair please send the DULCOMARIN® II to the manufacturer. Maintenance, repairs and disposal 8.1 Disposal of used parts n Users' qualification: instructed persons, see Ä Chapter 2.2 ‘Users' qualifications’ on page 16 NOTICE! Regulations governing disposal of used parts – Note the current national regulations and legal standards which apply in your country ProMinent Dosiertechnik GmbH, Heidelberg will take back decon‐ taminated used devices providing that they are covered by ade‐ quate postage. 49 Technical data spare parts and accessories 9 Technical data spare parts and accessories Technical data You can find the technical data in the operating instructions of the individual modules, see also the section "Further applicable docu‐ ments". Spare parts and accessories Description: Part no. T-coupler M12 5-pole CAN 1022155 Terminating resistance, M12 socket 1022154 Terminating resistance, M12 plug 1022592 Connecting cable - CAN M12, 5 pole 0.5 m 1022137 Connecting cable - CAN M12, 5 pole 1m 1022139 Connecting cable - CAN M12, 5 pole 2 m 1022140 Connecting cable - CAN M12, 5 pole 5 m 1022141 Connecting cable - CAN M12, 5 pole Sold by the metre 1022160 Plug-CAN M12 5 pole Screwed connection 1022156 Coupling - CAN M12 5 pole Screwed connection 1022157 Cable combination coaxial 0.8 m-SN6, pre-assembled 1024105 Cable combination coaxial 2 m-SN6, pre-assembled 1024106 Cable combination coaxial 5 m-SN6, pre-assembled 1024107 Control cable by the metre 2x0.25 mm2 725122 Fuse 5x20 slow-acting 0.63 AT VDE 712030 Battery 3 V approx. 190 mAh Li cell BR2032 732829 Buffer solution pH 4, red, 50 ml 506251 Buffer solution pH 7, green, 50 ml 506253 Buffer solution redox 465 mV, 50 ml 506240 Redox sensor RHES-Pt-SE 150703 pH sensor PHES 112 SE 150702 Chlorine sensor CLE 3-CAN-10 ppm* 1023425 Chlorine sensor CLE 3.1-CAN-10 ppm* 1023426 Chlorine sensor CTE 1 CAN-10 ppm* 1023427 Chlorine sensor CGE 2-CAN-10 ppm* 1024420 * Membrane caps and electrolyte for chlorine sensors, see the respective operating instructions of the sensor 50 EC Declaration of Conformity and fulfilled standards 10 EC Declaration of Conformity and fulfilled standards EC Declaration of Conformity We, ProMinent Dosiertechnik GmbH Im Schuhmachergewann 5 - 11 D - 69123 Heidelberg hereby declare that the product identified below conforms to the basic health and safety requirementsof the EC Directive, by virtueof its design and construction, and in the configuration placed on the market by us. This declaration is no longerapplicable if changesare madetothe product without our authorisation. Productdescription: DULCOMARIN II measuring and control unit Producttype: Serial no.: see type plate on the unit Applicable EC Directives: EC Low Voltage Directive (2006/95/EC) EC EMC Directive (2004/108/EC) Applied harmonised standards, especially: Date/ Manufacturer signature: Name/ positionof the signatory: Joachim Schall, Manager Innovation and Technology Fig. 23: EC Declaration of Conformity 51 Wiring diagram DULCOMARIN® II compact 11 Wiring diagram DULCOMARIN® II compact A0506 Fig. 24: Wiring diagram DULCOMARIN® II compact (typical arrangement of modules) I. M module (measurement module) DXMaM II. A module (control module) DXMaA III. P module (power supply module with relay) DXMaP 52 Wiring diagram DULCOMARIN® II compact Comprehensive module populating options are listed in the "Sup‐ plementary instructions DULCOMARIN® II, DXMa Modules". M module (measurement module) DXMaM Description Terminal identifier Temp. input Pt1000/100 RTD Redox input 1 ORP(pH) Ter‐ minal no. Pole 1 + 2 - 3 Ref. 4 meas sig. Pot.1 5 Potential equali‐ sation 2 Pot.2 6 pH input 2 ORP(pH) 7 Ref. 8 meas sig. 9 + 10 - 11 + 12 - 13 + 14 - Contact input 2 Contact input 3 K1 K2 K3 Cable ⌀ Drill hole no. Remarks Size Potential equali‐ sation 1 Contact input 1 Function Temp.- sensor d5 1/M16 Redox - sensor d3/d5 2/M20 Guide cable through multiple seal inserts 2x5 or 2x4 11/M12 pH - sensor 11/M12 d3/d5 2/M20 Guide cable through multiple seal inserts 2x5 Fault sample water d4 3/M16 Guide cable through multiple seal inserts 2x4 Pause (back‐ washing) d4 3/M16 " ECO!Mode d4 12/M12 53 Wiring diagram DULCOMARIN® II compact A module (control module) DXMaA Description Relay output 1 Terminal identifier R1 Ter‐ minal no. Pole Function* Cable ⌀ 1 + Control acid pump d5 2 - or Drill hole no. Remarks Size 13/M12 Control alkali pump Relay output 2 R2 3 + 4 - Control chlorine pump d5 14/M12 d5 15/M12 d4 4/M20 Guide 2 cables through multiple seal inserts 2x4 d4 4/M20 Guide 2 cables through multiple seal inserts 2x4 d4 5/M16 Guide 2 cables through multiple seal inserts 2x4 pH plotter connec‐ d4 tion 6/M16 Guide 2 cables through multiple seal inserts 2x4 Redox plotter con‐ d4 nection 6/M16 Guide 2 cables through multiple seal inserts 2x4 Chlorine free plotter connection d4 /M16 Guide 2 cables through multiple seal inserts 2x4 Comb. chlorine plotter connection d4 7/M16 Guide 2 cables through multiple seal inserts 2x4 Control acid pump Control redox pump Relay output 3 R3 5 + 6 - Control flocculant pump Control chlorine pump Control redox pump Contact input 1 K1 7 + Pump error 8 - or Filling level Contact input 2 K2 9 + Pump error 10 - or Filling level Contact input 3 K3 11 + Pump error 12 - or Filling level Current output 0/4-20mA 1 I out 1 Current output 0/4-20mA 2 I out 2 Current output 0/4-20mA 3 I out 3 Current output 0/4-20mA 4 I out 4 13 + 14 - 15 + 16 - 17 + 18 - 19 + 20 - or Temperature plotter connection 54 Wiring diagram DULCOMARIN® II compact P module (power supply module with relay) DXMaP Description Terminal identifier Terminal Pole no. Function Cable ⌀ Drill hole no. Size Alarm relay P1 1 Horn control d6.5 8/M16 4 Control acid solenoid valve d6.5 9/M16 5 or d6.5 18/M12 d6.5 19/M12 d6.5 10/M16 2 3 Power relay 1 P2 Control alkali solenoid valve Power relay 2 P3 6 Control chlorine solenoid valve 7 or Control redox solenoid valve or Control acid solenoid valve or Control alkali solenoid valve Power relay 3 P4 8 Control UV (ozone, active carbon) 9 or Control redox solenoid valve or Control chlorine solenoid valve or Control heating Mains X1 10 PE 11 N 12 L(1) CAN connection module Description Terminal iden‐ tifier CAN 1 - bus connection CAN 1 Terminal no. Pole Cable ⌀ Drill hole no. Size 1 Shielding Plug 2 24 V A coding 3 ground 4 CAN high 5 CAN low 16/M12 55 Index 12 Index 1, 2, 3 ... 10 pole ribbon cable............................................. 16 pole ribbon cable............................................. A Accessories.......................................................... Ambient conditions............................................... Automatic start-up................................................ B Battery type: CR2032, 3 V approx. 190 mAh....... Branching cables.................................................. C Cable strain relief................................................. CAN bus backbone.............................................. CAN bus line........................................................ CANopen third party devices............................... Central unit........................................................... CR2032................................................................ D Degree of protection............................................. DIN IEC 60068-2-30............................................. Displays................................................................ Disposal............................................................... DULCO-Net.......................................................... E External modules in the CAN bus backbone....... F Failure of the circulating pumps........................... H Hazardous substances......................................... Hazardous waste................................................. I Identity code......................................................... Internet Explorer................................................... 56 41 41 50 20 18 48 26 30 26 38 18 25 48 18 20 44 48 25 26 30 18 48 12 12 IP 54..................................................................... IP65 protection rating........................................... K Keys..................................................................... L LAN coupling........................................................ L circuit board....................................................... M Maximum length of branching cables.................. Microsoft Internet Explorer................................... Mounting materials (contained in the scope of delivery)................................................................ P Power supply module........................................... R Repairs................................................................. Requirements for the installation site .................. S Safe operating status........................................... Safety information................................................ Screwdriver.......................................................... Sold by the metre................................................. Spare parts........................................................... T T-coupling............................................................ Terminating resistance......................................... U Users' qualifications............................................. W Wall/pipe bracket.................................................. Wall mounting...................................................... 32 38 43 12 42 26 12 34 25 48 20 30 15 30 26 50 38 39 16 35 34 Operating instructions Multi-Channel Measuring and Control System DULCOMARIN® II Swimming Pool Controller and Disinfection Controller DXCa Part 2: Operation A0204 Please carefully read these operating instructions before use! · Do not discard! The operator shall be liable for any damage caused by installation or operating errors! Technical changes reserved. Part no. 986206 BA DC 067 02/11 EN ProMinent Dosiertechnik GmbH Im Schuhmachergewann 5 - 11 69123 Heidelberg Telephone: +49 6221 842-0 Fax: +49 6221 842-419 email: [email protected] Internet: www.prominent.com 986206, 3, en_GB © 2011 58 Table of contents Table of contents 1 Further applicable documents............................................. 61 2 Introduction......................................................................... 62 2.1 Explanation of the safety information.......................... 62 2.2 Users' qualifications.................................................... 63 3 Safety and responsibility..................................................... 65 3.1 General Safety Information......................................... 65 3.2 Correct and Proper Use ............................................. 66 4 Functional description......................................................... 67 5 Control elements ................................................................ 68 5.1 Function of the buttons............................................... 68 5.2 Access code (password)............................................. 70 6 Commissioning: Configuring the CAN modules.................. 6.1 Logging modules on and off....................................... 6.2 Commissioning CAN-Beta pump................................ 6.3 Commissioning R module........................................... 72 72 74 77 7 Structure of the of the operating menu............................... 7.1 Structural principle...................................................... 7.2 Permanent display...................................................... 7.3 Central menu item...................................................... 7.4 Log off SD card safely................................................ 7.5 Generally applicable states......................................... 7.6 Menus underneath the central menu item.................. 7.7 Submenus of the parametric assignment menu......... 79 79 80 81 82 83 85 87 8 Calibration........................................................................... 88 8.1 Calibration of pH measured variable.......................... 89 8.1.1 1-Point calibration pH.............................................. 89 8.1.2 2-Point calibration pH.............................................. 91 8.2 Redox measured variable........................................... 93 8.3 Calibrate measured variable "chlorine free"............... 94 8.4 Calibrate measured variable "Total chlorine".............. 99 8.5 Calibrate measured variable for fluoride (F-)............ 105 8.6 Calibrate measured variable for chlorine dioxide (CIO2)........................................................................ 107 8.7 Calibrate measured variable hydrogen peroxide (H2O2)....................................................................... 111 8.8 Measured variable chlorite (CIO2 -)........................... 114 8.9 Calibrate measured variable for peracetic acid (PES)........................................................................ 117 8.10 Calibration measured variable temperature............ 119 9 Assign parameters............................................................ 9.1 All parameters........................................................... 9.2 Measurement............................................................ 9.2.1 Parametric assignment pH.................................... 9.2.2 Parametric assignment redox................................ 9.2.3 Parametric assignment "chlorine free"................... 9.2.4 Parametric assignment "chlorine bound"............... 9.2.5 Parametric assignment fluoride (F−)...................... 9.2.6 Parametric assignment ClO2 ................................ 120 120 120 121 122 123 124 125 126 59 Table of contents 9.2.7 Parametric assignment H2O2 ................................ 126 9.3 Control...................................................................... 9.3.1 pH Control.............................................................. 9.3.2 Redox control......................................................... 9.3.3 Free chlorine control.............................................. 9.3.4 Control for bound chlorine..................................... 9.3.5 Control temperature............................................... 9.3.6 Control flocculants................................................. 9.3.7 Control fluoride (F−)............................................... 9.3.8 Control chlorine dioxide (CIO2).............................. 127 128 130 132 133 134 135 136 138 9.3.9 Control H2O2 ......................................................... 139 9.4 9.5 9.6 9.7 9.8 10 60 Set mA output........................................................... Alarm settings........................................................... Parametric assignment flow meter........................... Setting Eco!Mode..................................................... Chlorine dosing redox dependent............................. 141 142 144 145 146 Configure.......................................................................... 10.1 Configuring module DXMaM................................... 10.1.1 Configuring module DXMaM ECO mode............. 10.2 Configuring module DXMaA................................... 10.2.1 Configuring module DXMaA circulation pump..... 10.3 Configuring module DXMaP................................... 10.4 Configuration for free chlorine module.................... 10.5 Configuration for total chlorine module................... 10.6 Configuration for chlorine module........................... 10.7 Configuration of R module (control module for chlorine gas metering device) ................................ 10.8 Configuration for P1 module (metering pump module) .................................................................. 10.9 G module (limit value module) configuration.......... 10.10 I module (current input module) configuration ..... 148 149 150 156 159 162 164 165 166 167 168 170 171 11 Maintenance .................................................................... 175 11.1 Configure maintenance timer.................................. 175 12 Troubleshooting................................................................ 177 13 Glossary of technical terms............................................... 184 14 Index................................................................................. 191 Further applicable documents 1 Further applicable documents These operating instructions and supplementary instructions are only valid in combination with the following operating and supple‐ mentary instructions: n Multi-channel measuring and control system operating instruc‐ tions DULCOMARIN® II Swimming Pool Controller and Disin‐ fection Controller DXCa – Part 1: Assembly and installation n Supplementary instructions DULCOMARIN® II Screen writer operation n Supplementary instructions DULCOMARIN® II, M-Module (measuring module for pH, redox [ORP], temperature) DXMaM operation n Supplementary instructions DULCOMARIN® II, I-Module (cur‐ rent input module, standard signal inputs mA) DXMal 61 Introduction 2 Introduction The operating instructions describe the technical data and func‐ tions of the multi-channel measuring and control system DULCOMARIN® II Swimming Pool Controller and Disinfection Con‐ troller DXCa. The operating instructions subsequently refer to the system merely as DXCa. 2.1 Explanation of the safety information Introduction These operating instructions provide information on the technical data and functions of the product. These operating instructions pro‐ vide detailed safety information and are provided as clear step-bystep instructions. The safety information and notes are categorised according to the following scheme. A number of different symbols are used to denote different situations. The symbols shown here serve only as examples. DANGER! Nature and source of the danger Consequence: Fatal or very serious injuries. Measure to be taken to avoid this danger Danger! – Denotes an immediate threatening danger. If this is disregarded, it will result in fatal or very serious injuries. WARNING! Nature and source of the danger Possible consequence: Fatal or very serious injuries. Measure to be taken to avoid this danger Warning! – Denotes a possibly hazardous situation. If this is disregarded, it could result in fatal or very serious injuries. CAUTION! Nature and source of the danger Possible consequence: Slight or minor injuries, mate‐ rial damage. Measure to be taken to avoid this danger Caution! – 62 Denotes a possibly hazardous situation. If this is disregarded, it could result in slight or minor inju‐ ries. May also be used as a warning about material damage. Introduction NOTICE! Nature and source of the danger Damage to the product or its surroundings Measure to be taken to avoid this danger Note! – Denotes a possibly damaging situation. If this is disregarded, the product or an object in its vicinity could be damaged. Type of information Hints on use and additional information Source of the information, additional measures Information! – Denotes hints on use and other useful information. It does not indicate a hazardous or damaging sit‐ uation. 2.2 Users' qualifications WARNING! Danger of injury with inadequately qualified personnel! The operator of the plant / device is responsible for ensuring that the qualifications are fulfilled. If inadequately qualified personnel work on the unit or loiter in the hazard zone of the unit, this could result in dangers that could cause serious injuries and material damage. – – All work on the unit should therefore only be con‐ ducted by qualified personnel. Unqualified personnel should be kept away from the hazard zone Training Definition Instructed personnel An instructed person is deemed to be a person who has been instructed and, if required, trained in the tasks assigned to him/her and possible dangers that could result from improper behaviour, as well as having been instructed in the required protective equipment and protective measures. Trained user A trained user is a person who fulfils the requirements made of an instructed person and who has also received additional training specific to the system from ProMinent or another authorised distribution partner. Trained qualified per‐ sonnel A qualified employee is deemed to be a person who is able to assess the tasks assigned to him and recognize possible hazards based on his/her training, knowledge and experience, as well as knowledge of pertinent regula‐ tions. The assessment of a person's technical training can also be based on several years of work in the relevant field. 63 Introduction Training Definition Electrician Electricians are deemed to be people, who are able to complete work on elec‐ trical systems and recognize and avoid possible hazards independently based on his/her technical training and experience, as well as knowledge of pertinent standards and regulations. Electricians should be specifically trained for the working environment in which the are employed and know the relevant standards and regulations. Electricians must comply with the provisions of the applicable statutory direc‐ tives on accident prevention. Customer Service depart‐ ment Customer Service department refers to service technicians, who have received proven training and have been authorised by ProMinent to work on the system. Note for the system operator The pertinent accident prevention regulations, as well as all other generally acknowledged safety regulations, must be adhered to! 64 Safety and responsibility 3 Safety and responsibility 3.1 General Safety Information WARNING! Live parts! Possible consequence: Fatal or very serious injuries – – Measure: Disconnect the mains power supply prior to opening the housing De-energise damaged, defective or manipulated units by disconnecting the mains plug WARNING! Unauthorised access! Possible consequence: Fatal or very serious injuries – Measure: Ensure that there can be no unauthor‐ ised access to the unit WARNING! Operating errors! Possible consequence: Fatal or very serious injuries – – – The unit should only be operated by adequately qualified and technically expert personnel Please also observe the operating instructions for controllers and fittings and any other component groups, such as sensors, measuring water pumps ... The operator is responsible for ensuring that per‐ sonnel are qualified CAUTION! Electronic malfunctions Possible consequence: Material damage to destruction of the unit – – The mains connection cable and data cable should not be laid together with cables that are prone to interference Measure: Take appropriate interference suppres‐ sion measures NOTICE! Correct and proper use Damage to the product or its surroundings – – The unit is not intended to measure or regulate gaseous or solid media The unit may only be used in accordance with the technical details and specifications provided in these operating instructions and in the operating instructions for the individual components 65 Safety and responsibility NOTICE! Correct sensor operation / Run-in time Damage to the product or its surroundings – – – – – Correct measuring and dosing is only possible if the sensor is working perfectly It is imperative that the run-in times of the sensors are adhered to The run-in times should be allowed for when plan‐ ning initial operation It may take a whole working day to run-in the sensor Please read the operating instructions for the sensor NOTICE! Correct sensor operation Damage to the product or its surroundings – – Correct measuring and dosing is only possible if the sensor is working perfectly Check and calibrate the sensor regularly NOTICE! Compensation of control deviations Damage to the product or its surroundings – This controller cannot be used in control circuits which require rapid compensation (< 30 s) 3.2 Correct and Proper Use NOTICE! Compensation for control deviations Damage to the product or its surroundings – The controller can be used in processes, which require compensation of > 30 seconds NOTICE! Correct and Proper Use The unit is intended to measure and regulate liquid media. The unit may only be used in accordance with the technical details and specifications provided in this operating manual and in the operating manuals for the individual components (such as, for example, sensors, fittings, calibration devices, metering pumps etc.). Any other uses or modifications are prohibited. 66 Functional description 4 Functional description The DXCa is a measuring and control unit designed to handle the specific requirements of drinking water treatment. For this reason it is extremely versatile when combined with a var‐ ious different measuring and actuating modules. ProMinent uses a bus system in the DXCa in order to network the sensors and actuators with the controller. The standard bus system CANopen® is used. All of the modules work according to Plug & Play principles. This is a flexible system that can be realised to meet the requirements of a compact or decentralised modular system and which is ready for any future requirements that may be needed. The DXCa can process measured values from up to 16 systems / pools. The I-Module enables up to 3 (third-party)-sensors with mA signals to be connected per system / pool, e.g. for flow, turbidity and UV intensity. Metering pumps, chlorine gas metering systems or chlorine dioxide production plants can be controlled directly in relation to these measured parameters. There is also the option of using the flow signal as interference value for the controlled measured variables. The DXCa is equipped with an integrated data logger and option‐ ally an embedded web server and OPC server, which enables the measured values and messages to be transferred to a control panel via LAN/Ethernet. Possible measured variables Measured variable pH compensated pH Free chlorine (CI) X total available chlorine (CI) X Oxygen (02) Fluoride (F−) X Chlorine dioxide (CIO2) Chlorite (HClO2) Ammonia (NH3) /Ammonium (NH4 +) X Turbidity Hydrogen peroxide (H2O2) Temperature Peracetic acid (PES) (C2H4O3) Conductivity Ultra violet rays (UV) 67 Control elements 5 Control elements Fig. 1: Buttons and displays 1 2 3 4 5 ENTER button LAN LED CAN 1-LED DXC-LED System LED 6 7 8 9 10 START/STOP key ESC button Arrow keys Function keys, variably assigned LCD display 5.1 Function of the buttons Navigation within the operating menu Function of the ENTER button: n Moving from menu item to menu item in the operating menu into deeper tiers of the operating menu n Selection within a file card of a menu item and confirming changes Function of the ESC button: n Moving from menu item to menu item in the operating menu upwards into higher tiers of the operating menu ESC button Repeatedly press the ESC button in order return from any menu item of the operating menu and back to the permanent display. Function of the buttons: UP, DOWN, LEFT, RIGHT: n Move in a menu item between the file cards of a menu item n Change between the selections in a file card 68 Control elements MEAS pH CTRL OUTP ALARM Measurement parameters Redox Cl free Cl tot Sensor check: ON Temp.input: Entry Temp. value = 25.6 °C Temp Flock 11 HELP DATE HOME TIME LANGUAG A0130 Fig. 2: Change between the file cards M DXMaM RTD POT ORP 1 2 pH Sensor terminals RTD: Pt1000/100 (pH)ORP: Redox sensor POT1 free POT2 free pH(ORP): pH sensor K1 K2 K3 Digital inputs K1: Sampling water K1 Type: NO K2: Pause K2 Type: NO K3: frei K3 Type: NO DEFAULT SAVE A0131 Fig. 3: Selection within a file card The UP and DOWN arrow keys can be used in a selection to change the displayed numerical value or displayed variable. The arrow keys LEFT and RIGHT can be used to select the decimal place of a numerical value which is to be changed. A0132 Fig. 4: Changing a numerical value The SAVE function enables you to store the numerical values or variables in a file card. Some numerical values such as PASSW, TIME or DATE are stored with the ENTER button. HELP CAL PARAM CONFIG A0133 Fig. 5: Example assignment for the function keys 69 Control elements WARNING! Function of the START/STOP key The START / STOP key can be used to switch the system currently shown in the display off or on. The START / STOP button has no influence on other systems that are not shown in the display. First select the respective system, before you work with the START / STOP key. Function of the START/STOP key n The START / STOP key can be used to start or stop regulating or metering. Subsequently the permanent display and the cen‐ tral menu item is shown ‘Metering ON’ or ‘Metering OFF’ 5.2 Access code (password) Access to the device can be granted in steps by setting up an access code. The DXCa system is supplied with access codes according to the following table. Replace the factory-set access codes with your own access codes. Otherwise protection to the following menus will be extremely weak. When toggling back to the permanent display, the DXCa automatically resets to level ‘0’ for ‘every user’ You can set the level immediately to ‘0’ by pressing the following key combination from the central menu item: F4 (CONFIG), F2 (OPTION), F5 (RESTART) - this causes module detection to be manually started You can freely calibrate level ‘0’ and ‘1’ if you set for level ‘1’ (user) the password to ‘0000’ . – – – – The various levels enable the following: Level 0 1 2 3 4 5 (every user) (user) (Installation engineer) (Service) (Supervisor) (ProMinent) 0000 1111 2222 3333 4444 confidential View X X X X X X Calibration X X X X X X Assign parameters X X X X Configure X X X X Calibrate Cl NP X X X X Password (Default) 70 Control elements Level 0 1 2 3 4 5 (every user) (user) (Installation engineer) (Service) (Supervisor) (ProMinent) Configure bus X X X Update all modules X X X X X Update indi‐ vidual mod‐ ules Update cen‐ tral unit X Areas protected by access codes: – – – – – Central menu item Permanent display pH 7.12 654 Cl free mg/l Clcomb. Cltotal mg/l Temp 1.12 1.25 Q 1 Temp 4-20 mA 10.0 °C mV Redox 0.13 Calibrate sensor! PT1000/100 34.2 System ClO210.00 7.12 pH mg/l °C 1 Dosage: OFF 01.04.10 16:19:21 Cl Temp Dosage: 90 % 0.92 PT 1000/100 20. 0 1! Redox HELP mg/l °C Cl Q CAL pH Sensor calibration pH Redox 1.12 mg/l free comb. Set 0.00 01.04.05 654 mV Redox Cl Calibration menu 16:28:57 Pool 1 Childrens pool Permanent display Central menu item Calibration menu Parameter menu Configuration menu total Set 0.00 1.32 Sensor value = Zero point = Slope = Cl free Dosage: OFF Cl tot mg/l Temp CAL1Pt: Calibrate with reference value or buffer solution 1 --> Value too low CAL PARAM CONFIG pH 7.12 0.24 mV 59.23 mV/pH CAL1Pt: Calibration with 2 buffer solutions LIST HELP OFF HOME CAL1Pt CAL1Pt Parameter menu Pool MEAS pH Redox Cl free Cl tot CTRL OUTP 1 MEAS ALARM pH Measurement parameters Sensor check: ON Temp. input: ENTRY Temp. value = 25.6 °C Measurement parameters Sensor check: ON Temp. erfass.: ENTRY Temp. value = 25.6 °C Temp Flock Request password HELP HOME DATE TIME DEFAULT LANGUAG SAVE Configuration menu Pool 1 M DXMaM Pool 1 RTD POT ORP 1 2 pH Sensor terminals RTD: Pt1000/100 (pH)ORP: Redox sensor POT1 free POT2 free pH(ORP): pH sensor K1 K2 M DXMaM K3 Digital inputs K1: Sampling water K1 Type: NO Delay=0000s K2: Pause K2 Type: NO Delay=0000s K3: free K3 Type: NO DEFAULT SAVE RTD POT ORP 1 2 pH Sensor terminals RTD: Pt1000/100 (pH)ORP: Redox sensor POT1 free POT2 free pH(ORP): pH sensor K1 K2 K3 Digital inputs K1: Sampling water K1 Type: NO Delay=0000s K2: Pause K2 Type: NO Delay=0000s K3: free K3 Type: NO DEFAULT SAVE A0261 Fig. 6: Access code (password) Language You can set the language in submenu [LANGUAGE] . In order to do so, press function key F5 (LANGUAGE) in the parameter menu. 71 Commissioning: Configuring the CAN modules 6 Commissioning: Configuring the CAN modules CAUTION! Delayed data processing For these actions, you must always allow a few sec‐ onds to elapse between the last message or the last progress bar and the subsequent action. You can also use the BUS menu to log modules on and off, but not temporarily. The central unit does not store all of the data required for seamlessly restoring operation of the modules. Updating software The corresponding update instructions for available updates can be requested from ProMinent Dosier‐ technik GmbH. 6.1 Logging modules on and off Adding a new module If a new module is inserted into the CAN-configuration for DXCa or a module has been deleted from the central unit: The central unit has no data relating to the module. 1. Connect the module to the CAN bus system. ð The following message appears on the central menu item [Configuration service started – LSS node detected ...] with progress bar. 2. The following message appears on the permanent display [New module reported! Press ENTER.]. 3. Press the ENTER button ð The following message appears on the central menu item [New module reported! Press ENTER.]. 4. Press the ENTER button ð The menu [Reconfiguration complete. Press ESC.] appears. 5. Press the ESC button ð the central menu item appears. Temporarily disconnect a module 72 Temporarily disconnect a module from the CAN bus system without intermediate replacement: Commissioning: Configuring the CAN modules The central unit stores all of the data required for reassigning the module. 1. Disconnect the module from the CAN bus system. ð The following message appears on the central menu item [Module disconnected! Press ENTER]. 2. Press the ENTER button ð The menu [Logged off modules] appears. 3. Press F4 (SAVE), in order that the module remains stored in the CAN configuration ð The message [Reconfiguration complete. Press ESC.] appears. 4. Press the ESC button In the configuring menu, the overview at the start of the submenu [BUS] indicates that the module [is missing.]. ð the central menu item appears. Re-assign a temporarily disconnected module Re-connect a module that has been temporarily disconnected from the CAN bus system without intermediate replacement back into the original CAN bus system: The central unit will have stored all of the data required for re-assigning the module. 1. Connect the module to the CAN bus system. ð The following message appears on the central menu item [Configuration service started – LSS node detected … ] with progress bar. 2. The following message appears on the permanent display [Module re-registered! Press ENTER]. 3. Press the ENTER button ð The following message appears on the central menu item [Module re-registered! Press ENTER]. 4. Press the ENTER button ð The menu [Re-registered module detected] appears. 5. Press F4 (ACCEPT), in order that the module will recom‐ mence operation in accordance with the stored CAN configu‐ ration ð A progress bar is shown followed by the message [Reconfiguration complete. Press ESC.]. 6. Press the ESC button ð The central menu item appears. The module is assigned to the CAN bus again. 73 Commissioning: Configuring the CAN modules Permanently disconnect a module Permanently disconnect a module from its pool or the DXCa or insert it into another pool or another DXCa: (The central unit will delete all of your data related to the module.) The central unit will delete all of your data related to the module. 1. Disconnect the module from the CAN bus system. ð The following message appears on the central menu item [Module disconnected! Press ENTER]. 2. Press the ENTER button 3. Press F2 (DELETE) 4. Press the ESC button ð The central menu item appears. The module is logged off from the CAN bus and all of the module data is deleted from the central unit. The module will now be detected as a new module if it is re-connected to the CAN bus. 6.2 Commissioning CAN-Beta pump Follow the instructions precisely in order to ensure cor‐ rect detection of the CAN-Beta pump in the CAN bus. Commissioning a new or non-saved CAN-Beta pump Preparation 1. Start up the central unit if this has not already been done. 2. Set the pumps to the required stroke length (default 95%) 3. Check that the multifunctional switch is positioned to BUS 4. Connect the pump to the CAN bus system 5. Connect the pump to the supply voltage ð The following message appears on the central menu item [Configuration service started – LSS node detected …] with progress bar. 6. The following message appears on the permanent display [New module reported! Press ENTER.]. 7. Press the ENTER button ð the central menu item appears. 8. Press the ENTER button ð The menu [New module detected 1] appears. 74 Commissioning: Configuring the CAN modules Assign a system (pool, filtration circuit, etc.) DXMaM DXMaR DXMaG DXMaA Cl DXMaI DXMaP CL tot Pump 1 Pump 2 Allocated DXMaS1 DXMaS2 DXMaS3 1 System Pump 3 Pump 4 Expected New module detected Free 1 New module detected Pump 1 Serial number 1 2006036753 Module will be configured in: System 1 No: 1 HELP DELETE OK ACCEPT A0266 Fig. 7: New module detected 1 Assign a pump number 1. With the arrow keys select [System] and press the ENTER key 2. Enter the desired system number with the arrow keys and press the ENTER key 1. With the arrow keys select [No.] and press the ENTER button 2. Enter the desired number for the pump (1 - 4) with the arrow keys and press the ENTER button Save CAN configuration System 1 Name: Childrens pool DXMaM DXMaA DXMaP DXMaR Cl Cl tot Pump 1 Pump 2 Pump 3 Pump 4 DXMaS1 DXMaS2 DXMaS3 DXMaG DXMaI 2004106040 1254552546 5445454444 1212144665 2154545665 5442121212 1121121212 not connected not connected not connected not connected not connected not connected not connected 16554323565 17 14 13 16 11 12 10 15 SAVE A0267 Fig. 8: Save assignment 1. Press F4 (ACCEPT) in order to store the CAN configuration or press the ENTER button in order to change the entry 2. Press the ENTER button in order to change the name of the system (e.g. from ‘Children's pool’ to ‘swimming pool’ .) 3. F5 (SAVE) in display, see Fig. 8 ð Data will be saved 4. Press the ESC button ð Permanent display appears. The CAN configuration is now saved 75 Commissioning: Configuring the CAN modules Assign the pump a purpose 1. Press the following key combination in the central menu item in order to assign the pump a purpose: F4 (CONFIG) 2. LEFT/RIGHT (file card P1 or P2 ...) ð The file card with the assignment number of the respec‐ tive pump has been selected. 3. Press the ENTER button 4. Press the ENTER button 5. Enter the desired purpose by means of the vertical arrow keys and press the ENTER key ð For example [P1 Bus metering pump] appears on the dis‐ play 6. Press F5 (SAVE) ð Prompt [Save dialog, really save?; no=ESC, yes=ENTER] appears on the display 7. Press the ENTER button 8. Subsequently press the ESC button ð The pump has been assigned and saved. You can now exit the menu with the ESC button Commissioning a stored CAN-Beta pump Preparation 1. Start up the central unit if this has not already been done 2. Set the pumps to the required stroke length (default 95%) 3. Check that the multifunctional switch is positioned to BUS 4. Connect the pump to the CAN bus system 5. Connect the pump to the supply voltage ð The following message appears on the central menu item [Configuration service started – LSS node detected …] with progress bar. 6. The following message appears on the permanent display [ Module re-registered! Press ENTER.]. 7. Press the ENTER button ð the central menu item appears. 8. Press the ENTER button ð The menu [Module redetected] appears. 9. Press F4 (ACCEPT) ð The module will be accepted 10. Press the ESC button ð Permanent display appears 76 Commissioning: Configuring the CAN modules 6.3 Commissioning R module WARNING! Emergency measures The plant operator is responsible for establishing a set of emergency measures for the event of a chloric gas leak. All persons who are able to do so are responsible for carrying out such emergency measures in the event of a chloric gas leak. WARNING! Chloric gas can leak Possible consequence: Fatal or very serious injuries Shut off the chloric gas metering system before com‐ missioning. Otherwise chloric gas can leak out. Check and enable an emergency stop system for the chloric gas metering system and emergency measures before commissioning. Test the connection to R module Shut off chloric gas metering The test can be aborted at any time with F2 (STOP) this causes the chloric gas metering unit to shut down. The chloric gas supply is then stopped. 1. Press F4 (TEST) ð The TEST menu appears. Calibrate R module 2. Manually control the chloric gas metering unit with the keys F3 (CLOSE) and F4 (OPEN) in order to test it 3. Press the F5 key (QUIT) in order to exit the menu Shut off chloric gas metering The test can be aborted at any time with F2 (STOP) this causes the chloric gas metering unit to shut down. The chloric gas supply is then stopped. 77 Commissioning: Configuring the CAN modules At every point in time, the file card indicates the current opening angle of the chloric gas metering unit (= posi‐ tion in %; low number = valve relatively closed, large number = valve relatively open). 1. Successively press the buttons (CAL) and F2 (START) ð The following message appears [Calibration is running]. The DXCa initially closes the chloric gas metering unit. Subsequently it carries out two calibration cycles (open and close). At each end position, the DXCa waits briefly in order to evaluate the consistency of the potentiometer signal. When calibration has been completed, the following appears [Calibration completed] [Press QUIT]. 2. Press the F5 key (QUIT) in order to exit the calibration menu. ð After pressing the F5 key (SAVE) and the ENTER key, the DXCa opens the chloric gas metering unit in accord‐ ance with the current actuating variable. 78 Structure of the of the operating menu 7 Structure of the of the operating menu 7.1 Structural principle Daueranzeige pH Cl free 1.12 Cltotal 1.25 Q 1 mg/l Clcomb. 654 10.00 mg/l Sensor kalibrieren! PT1000/100 34.2 System 1 Childrens pool Dosage: °C ERROR OFF 01.04.10 16:19:21 10.0 °C Cl Set 0.00 7.12 1.12 mg/l free Cl comb. 1! Redox HELP 01.04.05 Dosage: 90 % 0.92 PT 1000/100 20. 0 mg/l °C Cl total Q CAL pH 654 mV Redox Temp Calibration menu 16:28:57 Pool 1 Childrens pool pH 0.13 mg/l Temp ClO2- Temp 4-20 mA Central menu item mV Redox 7.12 Sensor calibration pH Redox Set 0.00 Dosage: OFF Cl tot mg/l 1.32 Sensor value = Zero point = Slope = Cl free Temp CAL1Pt: Calibration with reference value or buffer solution 1 --> Value too low CAL PARAM CONFIG pH 7.12 0.24 mV 59.23 mV/pH CAL2Pt: Calibration with 2 buffer solutions LIST HELP OFF 10 HOME CAL1Pt CAL2Pt Parameter menu Pool MEAS pH Request password Redox Cl free Cl tot CTRL OUTP 1 Pool MEAS ALARM pH Measurement parameters Sensor check: Temp. input: Temp. value = 1 MEAS Measurement parameters ON Entry 25.6 °C Sensor check: Temp. input: Temp. value = pH Measurement parameters ON Entry 25.6 °C Sensor check: Temp. input: Temp. value = ON Entry 25.6 °C Temp Flock ? Request YES / NO HELP HOME DATE TIME 11 111 LANGUAG DEFAULT SICHERN Sensor check: ? Configuration menu Pool 1 Pool 1 Pool 1 M DXMaM RTD POT ORP 1 2 pH K1 Sensor terminals RTD: Pt1000/100 (pH)ORP: Redox sensor POT1 free POT2 free pH(ORP): pH sensor K2 M DXMaM K3 RTD Digital inputs K1: Sampling water K1 Type: NO Delay = 0000s K2: Pause K2 Type: NO Delay = 0000s K3: free K3 Type: NO POT ORP 1 2 pH Sensor terminals RTD: Pt1000/100 (pH)ORP: Redox sensor POT1 free POT2 free pH(ORP): pH sensor 101 M DXMaM K1 K2 RTD K3 POT ORP 1 2 pH Sensor terminals Digital inputs K1: Sampling water K1 Type: NO Delay = 0000s K2: Pause K2 Type: NO Delay = 0000s K3: free K3 Type: NO RTD: Pt1000/100 (pH)ORP: Redox sensor POT1 free POT2 free pH(ORP): pH sensor K1 K2 K3 Digital inputs K1: Sampling water K1 Type: NO Delay = 0000s K2: Pause K2 Type: NO Delay = 0000s K3: free K3 Type: NO 101 DEFAULT SICHERN DEFAULT SICHERN ? A0134 Fig. 9: Structural principle of the of the operating menu You can toggle over from the permanent display to the central menu item. At this point the operating menu branches off into the settings menus: n Calibration, see Ä Chapter 8 ‘Calibration’ on page 88 n Parametric assignment, see Ä Chapter 9 ‘Assign parameters’ on page 120 n Configuration, see Ä Chapter 10 ‘Configure’ on page 148 79 Structure of the of the operating menu 7.2 Permanent display pH mV mg/l Cl comb. mg/l 7.12 Clfree 1.12 Cl total 1.25 Q Redox 654 0.13 Calibrate sensor! mg/l Temp PT1000/100 ClO2- 1 10.00 Temp 4-20 mA 10.0 °C °C System 1 ERROR Childrens pool Dosage: OFF 01.04.05 16:19:21 A0140 Fig. 10: The permanent display for all measured variables The permanent display shows you all available measured values from the sampled water on a system. In the event that a limit value is exceeded (red) or undershot (blue), then a red or blue chevron is shown next to the measured value and the measured value is shown in the same colour. In the event that a sensor-related fault occurs or the calibration is faulty, then an error message appears in the corresponding meas‐ ured variable field. In the field at the bottom right-hand side, the permanent display shows the system number, the date and time and whether or not the metering system has been switched on or off by means of the START/STOP key. ‘ON’ or ‘OFF’ . By pressing F4 (GLOBAL), you can obtain an overview of all meas‐ ured values and the set points for all systems / pools, if numerous systems / pools have been configured. – – – 80 The DXCa calculates the displayed value for bonded chlorine as the difference between the measured values from the free chlorine and total chlorine sensors. Each measured variable is assigned a fixed colour (e.g. pH = orange, redox = yellow, etc. ) You can toggle from any menu item back to the operating menu by pressing the ESC key until the preeminent display is shown. Structure of the of the operating menu 7.3 Central menu item System 1 7.12 pH mg/l Redox Cl free 1.12 mg/l Cl comb. 0.92 Temp PT 1000/100 1! Redox HELP/SD 20. 0 CAL mg/l °C Cl total Set 6.00 Dosage: OFF Set 680 Dosage: not active Set 1.20 Dosage: OFF 1.32 Q mg/l 1 --> Value too low PARAM CONFIG QUIT A0338 Fig. 11: The central menu item for all measured variables The central menu item shows you the same data as the permanent display. However, it can additionally show the set points, the switching point for bonded chlorine or the temperature. If a measured variable is controlled, then the coloured bars cover the entire width of the display. If a measured variable is only being displayed, then the coloured bars only cover half the width of the display. In the event that there is insufficient space on the display for all of the measured variables, then you must subdivide them. This can be achieved by classifying a set of measured variables and assigning them to a second, virtual pool. These two pools will be defined as subsystems and you can name them in the same way, but, for example, with extensions to the names ‘_A’ and ‘_B’ in order to tell them apart. In contrast to the permanent display, the central menu point for the individual measured variables on a system indicates whether the metering system is set to ‘OFF’ or ‘ ON’ . Then it shows you the value of the actuating variable. If you have set the metering system to ‘OFF’ then it cannot be switched on by means of the START/ STOP key. Underneath the field with the measured variables, the central menu item shows you the fault messages. In the event that more than one fault message is pending, then after acknowledging the alarm via F5, the function ‘LIST is shown’ : When you press the F5 key, a list of the errors appears. Here you have the option of toggling over to an archive of previous fault messages with the F5 key (ARCHIVE) if an SD card is available for storage. You can return to the previous display by pressing the ESC key. For each event, the following can be detailed: n 1. Block: Number, date, time, COMES / GOES* – * Designates whether the error occurred or disappeared at this point in time n 2. Block: Node-ID, system number n 3. Block: Error message On the SD card, this data is stored in file ‘eventlog.txt’ . This can be read on a PC using a word processing application. The central menu item braches off into the settings menus n Calibration, see Ä Chapter 8 ‘Calibration’ on page 88 81 Structure of the of the operating menu n Parametric assignment, see Ä Chapter 9 ‘Assign parameters’ on page 120 n Configuration, see Ä Chapter 10 ‘Configure’ on page 148 7.4 Log off SD card safely Log off SD card safely System 1 7.12 pH mg/l Redox Cl free 1.12 mg/l Cl comb. 0.92 Temp 20. 0 1! Redox HELP/SD PT 1000/100 CAL mg/l °C Cl total Q Set 6.00 Dosage: OFF Set 680 Dosage: not active Set 1.20 Dosage: OFF 1.32 mg/l 1 --> Value too low PARAM CONFIG QUIT A0338 Fig. 12: Log off SD card safely 1. 82 Press the F1 key from the central menu item ‘HELP/SD’ Structure of the of the operating menu HELP: CAL - calibration of sensors PARAM - process parameter settings CONFIG - terminal configuration Info about DULCOMARIN: DXCAW061MAPDDR 1404143403 Version: 1006 Software date: 31.02.2010 13.62.00 Service: Company: Specimen Name: Specimen Landline: 6 Mobile: 8 HELP OFF Eject SD CARD HELP VER. SYSTEM A0138 Fig. 13: Eject SD CARD 2. Press the F2 button ‘Eject SD CARD’ Now you can remove the SD CARD! A0339 Fig. 14: Remove SD CARD ð Now you can safely remove the SD CARD. 7.5 Generally applicable states The controller states are signalised as follows: Display Information not active If the parameter settings ‘Control’ are set to inactive 100,0 % If the plant is set to ‘on’ and the parameter settings ‘Control’ are set to ‘active’ . PAUSE If relay ‘K2 ’ is connected STOP If the measured value and calibration are invalid Q! 10.5 % interference value is active for the measured variable Q min! 0.0 % for all controllers because Q < Qmin ORP! 12.0 % only for chlorine ECO 20.8 % for all controllers 83 Structure of the of the operating menu The controller states are signalised as follows: Display Information checkout time Par. invalid! If the parameter settings ‘Par’ are outside of the permissible range (e.g. Xp = 0) The measured value states are signalised as follows: Display Display colour Information 0,00 black Normal measured value without error 0,00 blue Measured value is lower than the lower limit value 0,00 red Measured value is higher than the upper limit value --,-- black < 0.10 Measurement error black. red background if the measured value is invalid Reasons: Measured water error (all meas‐ ured variables indicate incorrect values) Calibration is faulty A correction value is invalid (e.g. pH) Calibrate sensor! black Calibration is faulty Sensor not ready black Negative sensor power pH correction value black. red background for the CLE sensor the value is > 8.5 pH; for all other sensors there is an invalid pH value System 1 7.12 pH mg/l Redox Cl free 1.12 mg/l Cl comb. 0.92 Temp 20. 0 1! Redox HELP/SD PT 1000/100 mg/l °C Cl total Q Set 6.00 Dosage: OFF Set 680 Dosage: not active Set 1.20 Dosage: OFF 1.32 mg/l 1 --> Value too low CAL PARAM CONFIG QUIT A0338 Fig. 15: Generally applicable states Wide display bar Measured value with control Narrow display bar Measured value without control 84 Structure of the of the operating menu 7.6 Menus underneath the central menu item Calibration menu CAL pH Sensor calibration pH Redox Sensor value = Zero point = Slope = Cl free Cl tot Temp pH 7.12 0.24 mV 59.23 mV/pH CA1Pt: Calibration with reference value or buffer solution Q ClO2 CAL2Pt: Calibration with 2 buffer solutions HELP CAL1Pt CAL2Pt A0135 Fig. 16: First menu item of the calibration menu You can call up the calibration menu for all measured variable in the central menu item via function key F2 (CAL). Parametric assignment menu MEAS pH Redox Cl free Cl tot CTRL OUTP ALARM ECO Measurement parameters Sensor check: Temp.input: Temp. value = ON Entry 25.6 °C Temp Flock HELP HOME DATE TIME LANGUAG A0136 Fig. 17: First menu item of the parametric assignment menu You can call up the parametric assignment menu in the central menu item via function key F3 (PARAM). The structure of the parametric assignment menu is similar to that of a card file (with horizontal and vertical tabs): n The vertical labelling forms the measured variables (pH, Redox, etc.) n The horizontal labels for the groups of parameters (such as measurements, controls, etc) 85 Structure of the of the operating menu Configuration menu M A P Cl Cl R POT ORP 1 2 pH RTD K1 K2 Sensor terminals RTD: Pt1000/100 (pH)ORP: Redox sensor POT1 : free POT2 : free pH(ORP): pH sensor Soft. vers. 2903 I P1 K3 Digital inputs K1: Sampling water K1 Type: NO K2: Pause K2 Type: NO K3: free K3 Type: NO Serial no. Node - ID 14 2004033100 1 HELP OPTION PASSW UPDATE BUS A0137 Fig. 18: First menu item of the configuration menu You can call up the configuration menu in the central menu item via function key F4 (CONFIG). The structure of the configuration menu reflects the configuration of the existing hardware modules. There is a file card for each module. Example of a help display HELP: CAL - calibration of sensors PARAM - process parameter settings CONFIG - terminal configuration Info about DULCOMARIN: DXCAW061MAPDDR 1404143403 Version: 1006 Software date: 31.02.2010 13.62.00 Service: Company: Specimen Name: Specimen Landline: 6 Mobile: 8 HELP OFF Eject SD CARD HELP VER. SYSTEM A0138 Fig. 19: Example of a help display You can call up the help menu in the central menu item via function key F1 (HELP) when the F1 ‘ HELP’ key is available in the menu. The help display called up from the central menu item additionally indicates the software version of the central unit and the date of manufacture. In the calibration menu you can choose to view or hide mutual help texts in the file cards for all menu items of the cal‐ ibration menu via the F1 (help) key. 86 Structure of the of the operating menu 7.7 Submenus of the parametric assignment menu MEAS pH Redox Cl free Cl tot CTRL OUTP ALARM Measurement parameters Sensor check: Temp.input: Temp. value = ON Entry 25.6 °C HOME DATE Temp Flock HELP 1 TIME 2 LANGUAG 3 A0139 Fig. 20: Access to the submenus 1 2 3 Submenu DATE (F3) Submenu TIME (F4) Submenu LANGUAGE (F5) The submenus DATE, TIME and LANGUAGE can be reached via the function keys in the parametric assignment menu. Switchover to summer time The DXCa does not have a function to automatically switch over to summer time. 87 Calibration 8 Calibration NOTICE! Operating instructions Always observe the operating instructions and other technical documentation for the installed sensors and flow gauges when calibrating the equipment. CAL pH Sensor calibration pH Redox Cl free Cl tot Temp Q ClO2 Sensor value = Zero point = Slope = pH 7.12 0.24 mV 59.23 mV/pH CA1Pt: Calibration with reference value or buffer solution CAL2Pt: Calibration with 2 buffer solutions HELP CAL1Pt CAL2Pt A0135 Fig. 21: Calibration menu The DXCa sets the actuating outputs to ‘0’ . Exception to this: When a basic load or a manual actuating vari‐ able has been set, this remains active during the cali‐ bration process. The mA standard signal outputs are frozen. When calibration has been completed success‐ fully, all of the error checks relating to the reading are restarted. The DXCa stores the recorded data for zero point and slope. Start calibration (for all measured variables): n Shut down the measured water (acknowledge possible alarm with the ENTER button) n Press the F2 key (CAL) from the central menu item n Enter the access code, see Ä Chapter 5.2 ‘Access code (pass‐ word)’ on page 70 n Select a card file with the desired measured variable (arrow keys) Support texts You can choose to show or hide the support texts with the F1 key (HELP). 88 Calibration 8.1 Calibration of pH measured variable CAL pH Sensor calibration pH Redox Sensor value = Zero point = Slope = Cl free Cl tot Temp Q ClO2 pH 7.12 0.24 mV 59.23 mV/pH CA1Pt: Calibration with reference value or buffer solution CAL2Pt: Calibration with 2 buffer solutions HELP CAL1Pt CAL2Pt A0135 Fig. 22: Calibration of pH measured variable Dispose of the used buffer solution 8.1.1 1-Point calibration pH CAL pH Sensor calibration pH Redox Sensor value = Zero point = Slope = Cl free Cl tot Temp pH 7.12 0.24 mV 59.23 mV/pH CAL 1Pt: Calibration with reference value or buffer solution CAL2Pt: Calibration with 2 buffer solutions 10 HILFE OFF HOME CAL 1Pt KAL2Pkt Spring 1 Spring 1 CAL pH pH Sensor value = Buffer temp. = Buffer value = pH pH 7.12 26.7 °C 7.00 pH Buffer recognition runnin Clean probe and put in buffer Start buffer recognition with BUFFER key Adjust buffer temperature and value Push CAL key A0142 PUFFER CAL pH pH Sensor value = Buffer temp. = Buffer value = pH 7.12 26.7 °C 7.00 pH Clean probe and put in buffer Start buffer recognition with BUFFER key Adjust buffer temperature and value Push CAL key HILFE OFF Spring 1 CAL CAL HELP OFF Sensor value = Buffer temp. = Buffer value = pH 7.12 26.7 °C 7.00 pH Clean probe and put in buffer Start buffer recognition with BUFFER key Adjust buffer temperature and value Push CAL key A0143 PUFFER pH CAL HILFE OFF A0142 BUFFER CAL A0144 Fig. 23: 1-Point calibration pH 89 Calibration 1-Point calibration pH The DXCa calibrates: n the zero point if the buffer values lies between 6.8 and 7.5 pH n the slope, if the buffer value is less than 6.8 pH or greater than 7.5 pH 1. Shut down the measured water (acknowledge possible alarm with the ENTER button) 2. Unscrew the coaxial cable from the pH sensor 3. Remove the pH sensor (measured water shut off?) 4. Rinse the pH sensor with distilled water 5. Carefully pad the pH sensor dry with a cloth (free of grease, lint free) 6. Screw the coaxial cable back onto the pH sensor 7. Select 1-point calibration with F4 (CAL1Pt) 8. Dip the Ph sensor in a buffer solution (e.g. pH 7) and stir If you are measuring with an equipotential bonding pin, then also dip this into the buffer sol‐ ution. 9. Select the desired buffer temperature in the file card (arrow keys) and press the ENTER key 10. Enter the temperature of the buffer solution (arrow keys) and press the ENTER key 11. Press F4 (Buffer) (buffer detection) ð The progress bar and ‘buffer recognition running’ appears on the display 12. Press the ESC key in order to repeat the calibration process 13. Press F5 (CAL) in order to conclude the calibration process 14. If you do not want to carry out any more calibrations, press the ESC key to return to the permanent display or central menu item 15. Unscrew the coaxial cable from the pH sensor 16. Re-install the pH sensor into the flow gauge 17. Screw the coaxial cable back onto the pH sensor 18. Re-install the equipotential bonding pin 19. Open the shut-off valves for the measured water ð First open the outlet, then the inlet. 90 Calibration 8.1.2 2-Point calibration pH CAL pH Sensor calibration pH Redox Sensor value = Nullpunkt = Slope = Cl free Cl tot Temp pH 7.12 0.24 mV 59.23 mV/pH CAL1Pt: Calibration with reference value or buffer solution CAL2Pt: Calibration with 2 buffer solutions HELP OFF 10 HOME CAL1Pt CAL2Pt Spring 1 Spring 1 Spring 1 CAL pH Buffer 1 Sensor value = Buffer temp. = Buffer value = pH 4.57 26.7 °C 4.00 pH Buffer 1 pH pH Sensor value = Buffer temp. = Buffer value = pH 4.57 26.7 °C 7.00 pH Buffer recognition running Clean probe and put in buffer Start buffer recognition with BUFFER key Adjust buffer temperature and value Push CAL key BUFFER HELP OFF CAL BUFFER CAL Sensor value = Buffer temp. = Buffer value = pH pH BUFFER Buffer 2 pH HELP OFF CAL BUFFER CAL CAL pH BUFFER CAL Buffer 2 Sensor value = Buffer temp. = Buffer value = pH 7.12 26,7 °C 7.00 pH Buffer recognition running Clean probe and put in buffer Start buffer recognition with BUFFER key Adjust buffer temperature and value Push CAL key Clean probe and put in buffer Start buffer recognition with BUFFER key Adjust buffer temperature and value Push CAL key HELP OFF HELP OFF Sensor value = Buffer temp. = Buffer value = pH 7.12 26.7 °C 7.00 pH pH 4.57 26.7 °C 4.00 pH Quelle 1 CAL CAL Buffer 2 pH Clean probe and put in buffer Start buffer recognition with BUFFER key Adjust buffer temperature and value Push CAL key Spring 1 Spring 1 pH Buffer 1 Sensor value = Buffer temp. = Buffer value = Clean probe and put in buffer Start buffer recognition with BUFFER key Adjust buffer temperature and value Push CAL key HELP OFF CAL CAL pH pH pH pH 7.12 26.7 °C 7.00 pH Clean probe and put in buffer Start buffer recognition with BUFFER key Adjust buffer temperature and value Push CAL key HELP OFF BUFFER CAL A0145 Fig. 24: 2-Point calibration pH 2-Point calibration pH 1. Shut down the measured water (acknowledge possible alarm with the ENTER button) 2. Unscrew the coaxial cable from the pH sensor 3. Remove the pH sensor (measured water shut off?) 4. Rinse the pH sensor with distilled water 5. Carefully pad the pH sensor dry with a cloth (free of grease, lint free) 6. Screw the coaxial cable back onto the pH sensor 7. Select 2-point calibration with F5 (CAL2Pt) 8. Dip the Ph sensor in a buffer solution (e.g. pH 7) and stir If you are measuring with an equipotential bonding pin, then also dip this into the buffer sol‐ ution. 9. Select the desired buffer temperature (arrow keys) in the file card (buffer 1) and press the ENTER key 10. Enter the temperature of the buffer solution (arrow keys) and press the ENTER key 91 Calibration 11. Press F4 (Buffer) (buffer detection) ð The progress bar and ‘buffer recognition running’ appears on the display The DXCa has detected and stored the value of the buffer solution pH 7 (buffer 1) 12. Press the ESC key in order to repeat the calibration process 13. Press the F5 key (CAL) in order to continue with calibration 14. Take the pH sensor out of the buffer pH7 (buffer 1) and rinse it with distilled water 15. Carefully pad the pH sensor dry with a cloth (free of grease, lint free) 16. Dip the Ph sensor in the buffer solution pH 4 (buffer 2) and stir If you are measuring with an equipotential bonding pin, then also dip this into the buffer sol‐ ution. 17. Select the desired buffer temperature (arrow keys) in the cur‐ rently displayed file card (buffer 2) and press the ENTER key 18. Enter the temperature of the buffer solution (arrow keys) and press the ENTER key 19. Press F4 (Buffer) (buffer detection) ð The progress bar and ‘buffer recognition running’ appears on the display The DXCa has detected and stored the value of the buffer solution pH 4 (buffer 2) 20. Press the ESC key in order to repeat calibration 21. Press F5 (CAL) in order to conclude the calibration process and store the values. ð If calibration is successful, the following appears briefly: ‘Calibration OK’ . 22. If you do not want to carry out any more calibrations, press the ESC key to return to the permanent display or central menu item 23. Unscrew the coaxial cable from the pH sensor 24. Re-install the pH sensor into the flow gauge 25. Screw the coaxial cable back onto the pH sensor 26. Re-install the equipotential bonding pin 27. Open the shut-off valves for the measured water ð First open the outlet, then the inlet. 92 Calibration 8.2 Redox measured variable Check redox sensor You cannot calibrate a redox sensor. A redox sensor can only be tested. If the value of the redox sensor deviates more than ± 50 mV from the value of the buffer solution, then the redox sensor is to be tested as described in its operating instructions and replaced if necessary. CAL pH Sensor check Redox Cl free Sensor value = 459 mV Cl tot Set value = 465 mV Temp The value can only be adjusted within a range of ± 50 mV CAL A0146 Fig. 25: Redox measured variable You can only compare deviations between the redox sensor and buffer solution within a bandwidth of ± 50 mV. In the event that the displayed value deviates by more than ± 50 mV from the mV-value of the buffer solution, then the buffer solution and redox sensor should be checked and replaced if necessary. Dispose of the used buffer solution 1. Select the file card [Redox ](arrow keys) and press the CAL button (F5) 2. Shut down the measured water (acknowledge possible alarm with the ENTER button) 3. Unscrew the coaxial cable from the redox sensor 4. Remove the redox sensor (measured water shut off?) 5. Rinse the redox sensor with distilled water 6. Carefully pad the redox sensor dry with a cloth (free of grease, lint free) 7. Screw the coaxial cable back onto the redox sensor 8. Dip the redox sensor in a buffer solution (e.g. with 465 mV). If you are measuring with an equipotential bonding pin, then also dip this into the buffer sol‐ ution. 93 Calibration 9. If the displayed value is stable, compare it with the specified mV value detailed on the buffer solution bottle - it may not vary more than ± 50 mV from the buffer value 10. Press the ENTER button 11. Adjust the set value with the arrow keys. You can only com‐ pare deviations between the redox sensor and buffer solution within a bandwidth of ± 50 mV. 12. Press the ENTER button 13. Press the F5 key (ACCEPT) 14. If you do not want to carry out any more tests, press the ESC key to return to the permanent display or central menu item 15. Unscrew the coaxial cable from the redox sensor 16. Re-install the redox sensor into the flow gauge 17. Screw the coaxial cable back onto the redox sensor 18. Re-install the equipotential bonding pin 19. Open the shut-off valves for the measured water ð First open the outlet, then the inlet. 8.3 Calibrate measured variable "chlorine free" CAL pH Sensor calibration Redox Cl free Cl tot Sensor value = 1,12 mg/l Slope = 110,43 % Calibration : DPD <photometer> Temp Push CAL key before tapping sampling water HELP OFF 30 HOME CAL A0147 Fig. 26: Calibrate measured variable "chlorine free" 94 Calibration Calibrate zero point for measured var‐ iable "chlorine free" CAUTION! – Please also observe the operating instructions for the sensor and flow gauge – You may only set up a chlorine differential meas‐ urement in combination with a calibrated pH sensor – If you calibrated with pH correction, then you may only measure with pH correction! If you calibrated without pH correction, then you may only measure without pH correction – Following the replacement of a sensor membrane cap or electrolyte, the slope has to be calibrated – The slope has to be calibrated at regular intervals to ensure the optimal operation of the sensor. Cali‐ brating the sensor every 3-4 weeks suffices with swimming pool or potable water – Avoid air bubbles in the measured water. Air bub‐ bles, which adhere to the membrane of the sensor, can result in too low a reading and thus lead to over-metering. – Please note the applicable national guidelines for calibration intervals Prerequisites n Constant flow on flow gauge - minimum 40 l/h n The sensor have been run-in CAL CAL pH pH Sensor calibration Redox Redox Cl free Cl tot Temp Cl free Sensor value = 1.12 mg/l Slope = 110.43 % Zero point = 0.00 pA Calibration : DPD <photometer> Cl tot Temp 30 CAL DPD Sensor calibration Redox Sensor value = 0.00 mg/l Slope = 110.43 % Zero point = 0.00 pA Calibration : DPD <photometer> Cl free Cl tot Temp Push CAL key before tapping sampling water Push CAL key before tapping sampling water HELP OFF CAL pH Sensor calibration Calibration Zero point Sensor value = Zero point = Slope = Calibration : Zero point 0.00 mg/l 10.00 pA 110.43 % Immerse sensor in chlorine free water Wait until value has stabilised at approx. 0 mg/l Push CAL key HELP OFF CAL Zero point CAL Zero point Calibration INFO Sensor calibration CAL pH Sensor calibration Redox Cl free Sensor value = Sensor current = Temp. value = 0.00 mg/l 10 pA 25.6 °C Sensor value = Slope = Zero point = 0.00 mg/l 142.26 % 10.00 pA Cl free Cl tot Temp Calibration started. the calibration is finished with CAL! ESC cancels the calibration! Calibration completed CAL HOME Sensor value = Zero point = Slope = Calibration : Zero point 0.00 mg/l 10.00 pA 142.26 % Immerse sensor in chlorine free water Wait until value has stabilised at approx. 0 mg/l Push CAL key HELP OFF CAL Zero point ESC Central menu item A0148 Fig. 27: Calibrate zero point for "chlorine free" 95 Calibration – – The sensor have been run-in Only carry out a zero point calibration if: – you are using the sensor in the lower limit of the measuring range – you want to measure bonded chlorine (chlorine differential measurement) 1. Select the file card ‘Cl free’ - ‘Calibrate sensor’ (arrow keys) and press the ENTER button 2. Select the ‘Zero point’ (arrow keys) and press the ENTER button 3. Shut down the measured water (acknowledge possible alarm with the ENTER button) ð - First inlet, then the outlet. 4. Dismantle the sensor ð Unscrew the CAN cable from the CLE sensor. 5. Rinse the sensor with chlorine free water Examine the tap water for chlorine with an appropriate sampling instrument 6. Dip the CLE sensor in a bucket of clean, chlorine free tap water (or in still mineral water or distilled water) ð The chlorine free water must be the same temperature as the sample water. 7. Stir with the sensor until the measured value of the sensor is stable and near zero for approx. 5 mins. 8. Press F4 (CAL zero point) in order to conclude the calibration process and store the values ð Enter the access codes as prompted. 9. Conclude calibration with the F5 key (CAL) ð Display: [zero point calibration completed] 10. Press F2 (HOME) ð Zero point calibration is completed. 11. You can now exit the menu with the ESC button 12. Re-install the sensor into the flow gauge 13. Open the shut-off valves for the measured water ð First open the outlet, then the inlet. 14. 15. 96 Before calibrating the slope, wait until the measured value is constant (minimum 15 mins) CAUTION! Now it is imperative to calibrate the ‘slope’ Calibration Calibrate slope for measured variable "chlorine free" Cl tot Temp DPD Calibration DPD Calibration Sensor calibration Redox Cl free CAL CAL CAL pH Cl free Sensor value = 0.96 mg/l Slope = 110.43 % Zero point = 10.00 pA Calibration : DPD <photometer> 1.01 mg/l 1.11 mg/l 27.4 °C Cl free CAL DPD HELP OFF DEFAULT INFO MESS KAL DPD value : Sensor value = Temp. Value = 1.01 mg/l 1.01 mg/l 27.4 °C Measure chlorine concentration with photometer Enter value and push CAL key Calibration started, the calibration is finished with CAL! ESC cancels the calibration! Measure chlorine concentration with photometer Enter value and push CAL key Calibration started, the calibration is finished with CAL! ESC cancels the calibration! Push CAL key before tapping sampling water HELP OFF DPD value : Sensor value = Temp. Value = DPD VALUE = 01.01 mg/l Rng: 0.01 .. 10.00 mg/l CAL Cl free DPD value : Sensor value = Temp. Value = 1.30 mg/l 0.90 mg/l 27.4 °C DEFAULT INFO MEAS CAL pH Sensor calibration Redox Measure chlorine concentration with photometer Enter value and push CAL key Calibration started, the calibration is finished with CAL! ESC cancels the calibration! HELP OFF INFO Sensor calibration DPD Calibration Sensor value = Slope = Zero point = 1.01 mg/l 132.71 % 10.00 pA Cl free Cl tot Temp Sensor value = 1.01 mg/l Slope = 132.71 % Zero point = 10.00 pA Calibration : DPD <photometer> Push CAL key before tapping sampling water Calibration completed HELP OFF HOME CAL CAL ESC Central menu item A0149 Fig. 28: Calibrate slope "chlorine free" CAUTION! Chlorine must be permanently present in the sample water (approx 0.5 mg/l). Otherwise the measuring system cannot calibrate. 1. Select the file card [Cl free] [Sensor calibration] (arrow keys) and press the ENTER button 2. Select [DPD (photometer)] (arrow keys) and press the ENTER button 3. If the [Sensor value] is stable, press F5 (CAL DPD) 4. Immediately afterwards, take a water sample from the flow gauge 5. Immediately afterwards, determine the chlorine content of the sample water with a photometer and a suitable sampling instrument (e.g. DPD 1 for free chlorine (CLE sensor CLE)) 6. Press the ENTER button 7. Enter the chlorine content (arrow keys) and press the ENTER key 8. Press F5 (CAL) in order to conclude the calibration process ð The following appears [Calibration completed]. 9. Press the F2 key (HOME) in order to return to the calibration menu screen 10. If you do not want to carry out any more calibrations, press the ESC key to return to the permanent display 97 Calibration If you also want to measure the total chlorine, then calibrate this measured variable with the same sample (see Ä Chapter 8.4 ‘Cali‐ brate measured variable "Total chlorine"’ on page 99). Repeat the calibration after one day. You can display the pH value, the sensor current and the temperature at the time of pressing the button with F4 (MESS). – In the event that an error message is shown when calibrating a chlorine sensor, you can call up detailed information with F3 INFO. This data will also help when discussing the matter with a tech‐ nical consultant. In the event that the DXCa indicates an excessively low measured value or cannot be calibrated after the sensor has been run in (for CLE 3.1 and CTE/CGE approx. 2-6 h, for CLE 3 approx. 2 h) (in the sample water there must be approx. 1 mg/l of free chlorine, the pH-value 7.2 and the sample water and circulation pumps must be running), then the run-in times should be doubled and extended into the following day. If the sensor still cannot not be calibrated, then please phone ProMinent customer service. Please have the following data ready: n DPD1-value (free chlorine) n DPD 1 + 3-value (total chlorine) n Primary sensor current in pA (via F4 MESS in calibration menu for slope) n pH value n Redox value (if redox measurement is available) n Volume of sample water in cubic metres Set the CLE sensor for free chlorine to "DEFAULT" values 1. Select the file card [Cl free] [Sensor calibration] (arrow keys) and press the F5 button (CAL DPD) 2. Press the F2 key (DEFAULT) key, see Fig. 29 ð The zero point is now set to 0 pA and the slope at 100%. All previous calibrated values will now have been over‐ written 3. Now you must re-calibrate the measured variable ‘chlorine free’ , see Fig. 30 ð In order to do so, press the ESC button. 4. 98 Press the F5 key (CAL) Calibration CAL DPD Calibration ▶DPD value = Cl free Sensor value = Temp.value = 1.00 mg/l 1.00 mg/l 25.0 °C Calibration started, the calibration is finished with CAL! ESC cancels the calibration! HELP DEFAULT INFO MEAS CAL A0335 Fig. 29: [DEFAULT] . Warning: Calibrate sensor ESC Key - Return to the menu A0336 Fig. 30: Press the ESC button 8.4 Calibrate measured variable "Total chlorine" CAL pH Sensor calibration Redox Cl free Cl tot Temp Sensor value = 1.12 mg/l Slope = 110.43 % Zero point = 0.00 pA Calibration : DPD <photometer> Push CAL key before tapping sampling water HELP OFF CAL DPD A0150 Fig. 31: Calibrate measured variable "Total chlorine" 99 Calibration Calibrate zero point for measured var‐ iable "total chlorine" CAUTION! – Here you calibrate the CTE sensor for total chlorine – The DXCa calculates the displayed value for bonded chlorine as the difference between the measured values from the free chlorine and total chlorine sensors. – The sensor for ‘Free chlorine’ must be a CLE 3.1 sensor for the chlorine differential measurement – Please also observe the operating instructions for the sensor and flow gauge – You may only set up a chlorine differential meas‐ urement in combination with a calibrated pH sensor – If you calibrated with pH correction, then you may only measure with pH correction! If you calibrated without pH correction, then you may only measure without pH correction – Following the replacement of a sensor membrane cap or electrolyte, the slope has to be calibrated – The slope has to be calibrated at regular intervals to ensure the optimal operation of the sensor. Cali‐ brating the sensor every 3-4 weeks suffices with swimming pool or potable water – Avoid air bubbles in the measured water. Air bub‐ bles, which adhere to the membrane of the sensor, can result in too low a reading and thus lead to over-metering. – Please note the applicable national guidelines for calibration intervals Prerequisites n Constant flow on flow gauge - minimum 40 l/h n The sensor have been run-in n A CLE 3.1 sensor for free chlorine must be available in the system (pools, filtration circuit, etc.) 100 Calibration CAL CAL pH pH Sensor calibration Redox Redox Cl free Cl tot Temp Sensor value = 0.00 mg/l Slope = 145.06 % Zero point = 0.00 pA Calibration : DPD <photometer> Cl tot Temp Cl free Cl tot Temp Push CAL key before tapping sampling water 30 CAL DPD Sensor calibration Redox Sensor value = 0.00 mg/l Slope = 145.06 % Zero point = 0.00 pA Calibration : DPD <photometer> Cl free Push CAL key before tapping sampling water HELP OFF CAL pH Sensor calibration Calibration Zero point Sensor value = Zero point = Slope = Calibration : Zero point 0.00 mg/l 0.00 pA 145.06 % Immerse sensor in chlorine free water Wait until value has stabilised at approx. 0 mg/l Push CAL key HELP OFF CAL Zero point CAL Cl tot Zero point calibration INFO Sensor calibration CAL pH Sensor calibration Redox Sensor value = Sensor current = 0.00 mg/l 100 pA Sensor value = Slope = Zero point = 0.00 mg/l 142.26 % 0.00 pA Cl free Cl tot Temp Calibration started. the calibration is finished with CAL! ESC cancels the calibration! Calibration completed OFF Sensor value = Zero point = Slope = Calibration : Zero point Immerse sensor in chlorine free water Wait until value has stabilised at approx. 0 mg/l Push CAL key HELP OFF HOME 0.00 mg/l 0.00 pA 142.26 % CAL Zero point ESC Central menu item A0151 Fig. 32: Calibrate zero point for "Total chlorine" – – The sensor have been run-in Only carry out a zero point calibration if: – you are using the sensor in the lower limit of the measuring range – you want to measure bonded chlorine (chlorine differential measurement) 1. Select the file card ‘Cl comb’ - ‘Calibrate sensor’ (arrow keys) and press the ENTER button 2. Select the ‘Zero point’ (arrow keys) and press the ENTER button 3. Shut down the measured water (acknowledge possible alarm with the ENTER button) ð - First inlet, then the outlet. 4. Dismantle the sensor ð Do not unscrew the CAN cable from the CTE sensor. 5. Rinse the sensor with chlorine free water Examine the tap water for chlorine with an appropriate sampling instrument 6. Dip the CTE sensor in a bucket of clean, chlorine free tap water (or in still mineral water or distilled water) ð The chlorine free water must be the same temperature as the sample water. 7. Stir with the sensor until the measured value of the sensor is stable and near zero for approx. 5 mins. 101 Calibration 8. Press F4 (CAL zero point) in order to conclude the calibration process and store the values ð Enter the access codes as prompted. 9. Conclude calibration with the F5 key (CAL) ð Display: [zero point calibration completed] 10. Re-install the sensor into the flow gauge 11. Open the shut-off valves for the measured water ð First open the outlet, then the inlet. 12. Before calibrating the slope, wait until the measured value is constant (minimum 15 mins) 13. CAUTION! Now it is imperative to calibrate the ‘slope’ Calibrate slope for measured variable "total chlorine" CAL CAL pH Cl tot Sensor calibration Redox Cl free Cl tot Temp DPD value: Sensor value = Temp. Value = Sensor value = 1.65 mg/l Slope = 160.43 % Zero point = 10.00 pA Calibration: DPD <photometer> Cl tot CAL DPD HELP OFF DEFAULT DPD value: Sensor value = Temp. Value = 1.01 mg/l 1.65 mg/l 27.4 °C INFO MEAS CAL DPD-Calibration CAL 1.01 mg/l 1.01 mg/l 27.4 °C Measure chlorine concentration with photometer nter value and push CAL key Calibration started, the calibration is finished with CAL! ESC cancels the calibration! DPD VALUE = 01.01 mg/l Rng: 0.01 .. 10.00 mg/l CAL 1.30 mg/l 0.90 mg/l 27.4 °C INFO MEAS CAL pH Sensor calibration Redox Measure chlorine concentration with photometer nter value and push CAL key Calibration started, the calibration is finished with CAL! ESC cancels the calibration! DEFAULT INFO Sensor calibration DPD-Calibration DPD value: Sensor value = Temp. Value = HELP OFF Cl tot Measure chlorine concentration with photometer nter value and push CAL key Calibration started, the calibration is finished with CAL! ESC cancels the calibration! Push CAL key before tapping sampling water HELP OFF DPD-Calibration Sensor value = Slope = Zero point = 1.70 mg/l 232.71 % 10.00 pA Cl free Cltot Temp Sensor value = 1.01 mg/l Slope = 132.71 % Zero point = 10.00 pA Calibration: DPD <photometer> Push CAL key before tapping sampling water Calibration completed HOME CAL HELP OFF CAL DPD ESC Central menu item A0152 Fig. 33: Calibrate slope for "total chlorine" CAUTION! Chlorine must be permanently present in the sample water (approx 0.5 mg/l). Otherwise the measuring system cannot calibrate. 102 1. Select the file card [Cl comb] [Sensor calibration] (arrow keys) and press the ENTER button 2. Select [DPD (photometer)] (arrow keys) and press the ENTER button Calibration 3. If the [Sensor value] is stable, press F5 (CAL DPD) 4. Immediately afterwards, take a water sample from the flow gauge 5. Immediately afterwards, determine the chlorine content of the sample water with a photometer and a suitable sampling instrument (e.g. DPD 1 + 3 for total chlorine (CTE sensor)) 6. Press the ENTER button 7. Enter the chlorine content (arrow keys) and press the ENTER key 8. Press F5 (CAL) in order to conclude the calibration process ð The following appears [Calibration completed]. 9. Press the F2 key (HOME) in order to return to the calibration menu screen 10. If you do not want to carry out any more calibrations, press the ESC key to return to the permanent display Repeat the calibration after one day. You can display the pH value, the sensor current and the temperature at the time of pressing the button with F4 (MESS). – Set the CTE sensor for total chlorine to "DEFAULT" values In the event that an error message is shown when calibrating a chlorine sensor, you can call up detailed information with F3 INFO. This data will also help when discussing the matter with a tech‐ nical consultant. 1. Select the file card [Clges] [Sensor calibration] (arrow keys) and press the F5 button (CAL DPD) 2. Press the F2 key (DEFAULT) key, see Fig. 34 ð The zero point is now set to 0 pA and the slope at 100%. All previous calibrated values will now have been over‐ written 3. Now you must re-calibrate the measured variable ‘chlorine free’ , see Fig. 35 ð In order to do so, press the ESC button. 4. Press the F5 key (CAL) 103 Calibration CAL Cl tot DPD Calibration ▶DPD value = Sensor value = Temp.value = 1.00 mg/l 1.00 mg/l 25.0 °C Calibration started, the calibration is finished with CAL! ESC cancels the calibration! HELP DEFAULT INFO MEAS CAL A0337 Fig. 34: [DEFAULT] . Warning: Calibrate sensor ESC Key - Return to the menu A0336 Fig. 35: Press the ESC button 104 Calibration 8.5 Calibrate measured variable for fluoride (F-) CAL pH Sensor calibration Fluor. Redox Temp F Sensor value = Slope = 1.25 mg/l 59.20 mV/dec Cal1Pt: Calibration with reference value or buffer solution Cal2Pt: Calibration with 2 buffer solutions HELP OFF HOME CAL1Pt CAL2Pt A0153 Fig. 36: Calibrate measured variable for fluoride (F-) 1-Point calibration (via photometer) CAUTION! – Please also observe the operating instructions for the sensor and flow gauges, etc. – The sensor must be checked at regular intervals to ensure optimal operation of the sensor and re-cali‐ brated if necessary – Avoid air bubbles in the measured water. Air bub‐ bles, which adhere to the membrane of the sensor, can result in too low a reading and thus lead to over-metering. – A 2-point calibration must be carried out during the initial commissioning process – Please note the applicable national guidelines for calibration intervals Prerequisites n The sensor must be run-in (min. 1 h) 105 Calibration CAL pH Sensor calibration Fluor. Redox Temp F Sensor value = Slope = 1.12 mg/l 59.20 mV/dec CAL1Pt: Calibration with reference value or buffer solution CalPt: Calibration with 2 buffer solutions HELP OFF Home CAL1Pt: CAL2Pt: CAL F CAL F Fluor. Sensor value = Sensor current = Calibration value = Temp. Value = 0.00 mg/l 0.000 mA 1.00 mg/l 50.0 °C Sensor value = Sensor current = Calibration value = Temp. Value = Enter value and push CAL key Clean probe and put in buffer Adjust buffer temperature and value Push CAL key HELP OFF Fluor. CAL F Sensor value = Sensor current = Calibration value = Temp. Value = 1.00 mg/l 0.000 mA 1.00 mg/l 50.0 °C Calibration value 01.00 mg/l Range 0.00 ... 99.99 mg/l 0.00 mg/l 0.000 mA 1.00 mg/l 50.0 °C Enter value and push CAL key Clean probe and put in buffer Adjust buffer temperature and value Push CAL key Enter value and push CAL key Clean probe and put in buffer Adjust buffer temperature and value Push CAL key CAL Fluor. HELP OFF CAL A0154 Fig. 37: 1-Point calibration (via photometer) 106 1. Take a water sample from the sampling cock for purposes of calibration 2. Measure the water sample in accordance with the photo‐ meter manufacturer's instructions 3. Subsequently switch directly to the calibration menu with F2 CAL 4. Select the file card "F-" (arrow keys) and press F4 CAL 1Pt 5. Select [Temp.value ] (arrow keys), in the event that the tem‐ perature of the water is incorrect, and press the ENTER button 6. Enter the current measured temperature of the water (arrow keys) and press the ENTER key 7. Select the [ Calibration value] (arrow keys) and press the ENTER button 8. Enter the measured fluoride concentration ascertained by the photometer (arrow keys) and press the ENTER key 9. Then press the F5 key (CAL) 10. If you do not want to carry out any more calibrations, press the ESC key to return to the permanent display Calibration 2-Point calibration (via photometer) CAL pH Sensor calibration Fluor. Redox Temp F Sensor value = Slope = 1.12 mg/l 59.20 mV/dec CAL1Pt: Calibration with reference value or buffer solution CalPt: Calibration with 2 buffer solutions HELP OFF Home CAL1Pt: CAL2Pt: CAL F Buffer 1 Sensor value = Sensor current = Calibration value = Temp. Value = Fluor. CAL F 0.00 mg/l 0.000 mA 1.00 mg/l 50.0 °C Sensor value = Sensor current = Calibration value = Temp. Value = Enter value and push CAL key Clean probe and put in buffer Adjust buffer temperature and value Push CAL key HELP OFF Buffer 1 Fluor. Kalibrierwert 00.00 mg/l Bereich Buffer 2 Sensor value = Sensor current = Calibration value = Temp. Value = Fluor. 0.00 mg/l 0.000 mA 1.00 mg/l 50.0 °C Sensor value = Sensor current = Calibration value = Temp. Value = Enter value and push CAL key Clean probe and put in buffer Adjust buffer temperature and value Push CAL key HELP OFF CAL Buffer 2 Fluor. Calibration value 01.00 mg/l Bereich Buffer 2 Sensor value = Sensor current = Calibration value = Temp. Value = 1.00 mg/l 0.000 mA 1.00 mg/l 50.0 °C 0.00 ... 99.99 mg/l CAL CAL F Fluor. 0.00 mg/l 0.000 mA 1.00 mg/l 50.0 °C Enter value and push CAL key Clean probe and put in buffer Adjust buffer temperature and value Push CAL key Enter value and push CAL key Clean probe and put in buffer Adjust buffer temperature and value Push CAL key CAL 0.00 mg/l 0.000 mA 0.00 mg/l 50.0 °C HELP OFF 0.00 ... 99.99 mg/l F Fluor. Enter value and push CAL key Clean probe and put in buffer Adjust buffer temperature and value Push CAL key Enter value and push CAL key Clean probe and put in buffer Adjust buffer temperature and value Push CAL key CAL Buffer 1 Sensor value = Sensor current = Calibration value = Temp. Value = 1.00 mg/l 0.000 mA 1.00 mg/l 50.0 °C CAL F CAL F HELP OFF CAL A0155 Fig. 38: 2-Point calibration (via photometer) 8.6 Calibrate measured variable for chlorine dioxide (CIO2). Calibrating at a higher temperature As chlorine dioxide in the sample water is only physi‐ cally dissolved, unlike chlorine, it gasses out of the sample water very quickly at high temperatures (> 30 °C). It is therefore essential that the DPD measure‐ ments are performed quickly. There should on no account be more than 1 minute between taking the sample and mixing it with the reagents. In this case you must generate the red dye by the addition of the reagent directly at the sampling point and then the measurement should be conducted in the laboratory as quickly as possible. In the event that the DXCa indicates an excessively low measured value or cannot be calibrated after the sensor has been run in (for CDE approx. 2 - 6 hrs) then the run-in times should be doubled and extended into the following day. If the sensor still cannot not be calibrated, then please phone ProMinent customer service. 107 Calibration CAL pH Sensor calibration Redox Cl free Temp Sensor value = Slope = Zero value = 4,8 mg/l 4,008 mA 0,004 mA ClO2 Push CAL key before tapping sampling water HELP OFF CAL A0156 Fig. 39: Calibrate measured variable for chlorine dioxide (CIO2). Measured variable chlorine dioxide (CIO2). CAUTION! – Please also observe the operating instructions for the sensor and flow gauge – Following the replacement of a sensor membrane cap or electrolyte, the slope has to be calibrated – Avoid air bubbles in the measured water. Air bub‐ bles, which adhere to the membrane of the sensor, can result in too low a reading and thus lead to over-metering. – The slope has to be re-calibrated at regular inter‐ vals to ensure the optimal operation of the sensor. – Please note the applicable national guidelines for calibration intervals Prerequisites n Constant flow on flow gauge - minimum 20 l/h n Constant temperature of the sample water n Identical temperature of sample water and sensor (wait approx. 15 minutes) n The sensor have been run-in 108 Calibration CAL pH Temp Sensor value = Slope = Zero value = Calibration value = Temp. value = 4.8 mg/l 4.008 mA 0.004 mA 1.8 mg/l 32.0 °C ClO2 ClO2 Sensor current = ClO2 Push CAL key before tapping sampling water HELP OFF Sensor calibration Sensor calibration Redox Cl free CAL CAL Sensor calibration 0.003 mA 1.12 mg/l 32.0 °C Sensor current = 4.030 mA ero point calibration Push CAL key Wert eingeben und KAL drücken CAL Calibration value = Temp. value = CAL Calibration value = 0.000 mg/l Bereich: 0.000...9.999 mg/l CAL CAL pH Sensor calibration Sensor calibration Redox ClO2 Calibration value = Temp. value: 0.0 mg/l 32.0 °C Cl free Sensor current = 0.003 mA ClO2 Temp ero point calibration Push CAL key Sensor value = Slope Zero value = 4.6 mg/l 4.006 mA 0.004 mA Push CAL key before tapping sampling water CAL HELP OFF CAL A0157 Fig. 40: Chlorine dioxide (CIO2). CAUTION! – The sensor have been run-in – Only carry out a zero point calibration if: – you are using the sensor in the lower limit of the measuring range – Use the 0.5 ppm variant 1. Select the file card "CIO2“ - ‘Calibrate sensor’ (arrow keys) F5 CAL and press the ENTER button 2. Under [DPD value] enter the value 0.00 mg/l and press the ENTER-key - the following is now shown on the file card [Zero point calibration] 3. Shut down the measured water (acknowledge possible alarm with the ENTER button) ð - First inlet, then the outlet. 4. Dismantle the sensor 5. Rinse the sensor with chlorine free water 6. Dip the CDE sensor in a container of still mineral water or distilled water. The water must be the same temperature as the sample water. 7. Stir with the sensor until the measured value of the sensor is stable and near zero for approx. 5 mins. 8. Then press the F5 key (CAL) 9. Re-install the sensor into the flow gauge 10. Open the shut-off valves for the measured water ð First open the outlet, then the inlet. 109 Calibration CAUTION! Now it is imperative to calibrate the ‘slope’ Measured variable chlorine dioxide (CIO2). CAL pH Temp Sensor value = Slope = Zero value = Calibration value = Temp. Value = 4.8 mg/l 4.008 mA 0.004 mA 1.8 mg/l 32.0 °C ClO2 ClO2 Sensor current = ClO2 Push CAL key before tapping sampling water HELP OFF Sensor calibration Sensor calibration Redox Cl free CAL CAL Sensor calibration 4.030 mA Calibration value = Temp. Value = 1.80 mg/l 32.0 °C Sensor current = 4.030 mA Zero point calib. Push CAL key Enter value and push CAL key CAL CAL Calibration value = 1.800 mg/l Range: 0.000...9.999 mg/l CAL CAL pH Sensor calibration Sensor calibration Redox ClO2 Calibration value = Temp. Value = 1.8 mg/l 32.0 °C Cl free Sensor current = 4.003 mA ClO2 Temp Zero point calib. Push CAL key Sensor value = Slope Zero value = 4.6 mg/l 4.006 mA 0.004 mA Push CAL key before tapping sampling water CAL HELP OFF CAL ESC Central menu item A0158 Fig. 41: Chlorine dioxide (CIO2). CAUTION! – Before calibrating the slope, wait until the meas‐ ured value is constant (wait minimum 15 mins.) – Chlorine dioxide must be permanently present in the sample water (approx 0.5 mg/l). – Otherwise the measuring system cannot cali‐ brate. – Check the calibration 24 hrs after initial commis‐ sioning by means of DPD 110 1. Select the file card "CIO2“ - ‘Calibrate sensor’ off (arrow keys) 2. If the [Sensor value] is stable, press F5 (CAL DPD) 3. Immediately afterwards, take a water sample from the flow gauge 4. Immediately afterwards, determine the chlorine dioxide con‐ tent of the sample water with a photometer and a suitable sampling instrument (e.g. DPD) 5. Enter the chlorine dioxide content (arrow keys) and press F5 CAL 6. If you do not want to carry out any more calibrations, press the ESC key to return to the permanent display Calibration 8.7 Calibrate measured variable hydrogen peroxide (H2O2). Calibrate measured variable hydrogen peroxide (H2O2). CAL pH Sensor calibration Redox Cl free Temp Sensor value = Slope = Zero value = 4.8 mg/l 4.008 mA 0.004 mA H2O2 Push CAL key before tapping sampling water HELP OFF CAL A0159 Fig. 42: Calibrate measured variable hydrogen peroxide (H2O2). CAUTION! – Please also observe the operating instructions for the sensor and flow gauge – Following the replacement of a sensor membrane cap or electrolyte, the slope has to be calibrated – The slope has to be re-calibrated at regular inter‐ vals to ensure the optimal operation of the sensor. – Please note the applicable national guidelines for calibration intervals Prerequisites n The H2O2-concentration of the sample water is simultaneously sufficiently constant (observe the response time of the sensor over 8 mins) n Constant, permissible flow rate at the flow gauge n Identical temperature of sample water and sensor (wait approx. 15 minutes) n The sensor have been run-in 111 Calibration CAL pH Temp Sensor value = Slope = Zero value = Calibration value = Temp. value = 4.8 mg/l 4.008 mA 0.004 mA 1.8 mg/l 32.0 °C H2O2 H2O2 Sensor current = H2O2 Push CAL key before tapping sampling water HELP OFF Sensor calibration Sensor calibration Redox Cl free CAL CAL Sensor calibration 4.030 mA Calibration value = Temp. value = 1.80 mg/l 32.0 °C Sensor current = 4.030 mA Zero point calibration Push CAL key Enter value and push CAL key CAL CAL Calibration value = 0.000 mg/l Range: 0.000...9.999 mg/l CAL CAL pH Sensor calibration Sensor calibration Redox H2O2 Calibration value = Temp. value: 0.0 mg/l 32.0 °C Cl free Sensor current = 0.003 mA H2O2 Temp Zero point calibration Push CAL key Sensor value = Slope Zero value = 4.6 mg/l 4.006 mA 0.004 mA Push CAL key before tapping sampling water CAL HELP OFF CAL A0160 Fig. 43: Calibrate zero point CAUTION! – The sensor have been run-in – Only carry out a zero point calibration if: – you are using the sensor in the lower limit of the measuring range 1. Select the file card "H2O2“ [Sensor calibration] (arrow keys), F5 CAL and press the ENTER button 2. Under [DPD value] enter the value 0.00 mg/l and press the ENTER-key - the following is now shown on the file card [Zero point calibration] 3. Shut down the measured water (acknowledge possible alarm with the ENTER button) ð - First inlet, then the outlet. 4. Dismantle the sensor 5. Rinse the sensor with H2O2-free water 6. Dip the PER sensor in a container of still mineral water or distilled water. The water must be the same temperature as the sample water. 7. Stir with the sensor until the measured value of the sensor is stable and near zero for approx. 5 mins. 8. Then press the F5 key (CAL) 9. Re-install the sensor into the flow gauge 10. Open the shut-off valves for the measured water ð First open the outlet, then the inlet. 112 Calibration CAUTION! Now it is imperative to calibrate the ‘slope’ Calibrate measured variable hydrogen peroxide (H2O2). CAL pH Temp Sensor value = Slope = Zero value = Sensor calibration Sensor calibration Redox Cl free CAL CAL Sensor calibration Calibration value = Temp. value = 4.8 mg/l 4.008 mA 0.004 mA H2O2 Sensor current = H2O2 Push CAL key before tapping sampling water HELP OFF 1.8 mg/l 32.0 °C H2O2 4.030 mA Calibration value = Temp. value = 1.80 mg/l 32.0 °C Sensor current = 4.030 mA Zero point calibration Push CAL key Enter value and push CAL key CAL CAL Calibration value = 1.800 mg/l Range: 0.000...9.999 mg/l CAL CAL pH Sensor calibration Sensor calibration Redox H2O2 Calibration value = Temp. value: 1.8 mg/l 32.0 °C Cl free Sensor current = 4.003 mA H2O2 Temp Zero point calibration Push CAL key Sensor value = Slope Zero value = 4.6 mg/l 4.006 mA 0.004 mA Push CAL key before tapping sampling water CAL HELP OFF CAL ESC Central menu item A0161 Fig. 44: Calibrate slope CAUTION! – Before calibrating the slope, wait until the meas‐ ured value is constant (wait minimum 15 mins.) – Check the calibration 24 hrs after initial commis‐ sioning by means of DPD – Repeat calibration if the H2O2-concentration varies by more than 15 % from the reference value 1. Select the file card "H2O2“ [Sensor calibration] off (arrow keys) 2. If the [Sensor value] is stable, press F5 3. Immediately afterwards, take a water sample from the flow gauge 4. Immediately afterwards determine the H2O2-content of the sample water with a photometer and a suitable sampling instrument (e.g. DPD) 5. Enter the H2O2-content (arrow keys) and press F5 CAL 6. If you do not want to carry out any more calibrations, press the ESC key to return to the permanent display 113 Calibration In the event that the DXCa indicates an excessively low measured value or cannot be calibrated after the sensor has been run in (for H2O2 approx . 6-12 h) then the run-in times should be doubled and extended into the following day. If the sensor still cannot not be calibrated, then please phone ProMinent customer service. 8.8 Measured variable chlorite (CIO2 -) Measured variable chlorite (CIO2 -) zero point calibration CAL pH Sensor calibration Redox Cl free Temp Sensor value = Slope = Zero value = 4.8 mg/l 4.008 mA 0.004 mA ClO2Push CAL key before tapping sampling water HELP OFF CAL A0162 Fig. 45: Calibrate measured variable chlorite (CIO2 -) CAUTION! – Please also observe the operating instructions for the sensor and flow gauge – Following the replacement of a sensor membrane cap or electrolyte, the slope has to be calibrated – Avoid air bubbles in the measured water. Air bub‐ bles, which adhere to the membrane of the sensor, can result in too low a reading and thus lead to over-metering. – The slope has to be re-calibrated at regular inter‐ vals to ensure the optimal operation of the sensor. – Please note the applicable national guidelines for calibration intervals Prerequisites n Constant flow on flow gauge - minimum 20 l/h n Constant temperature of the sample water n Identical temperature of sample water and sensor (wait approx. 15 minutes) n The sensor have been run-in n There is a constant pH value in the permitted range (pH 6.5 9.5) 114 Calibration CAL pH Temp ClO2- Sensor value = Slope = Zero value= Calibration value = Temp. value = 4.8 mg/l 4.008 mA 0.004 mA 1.8 mg/l 32.0 °C Calibration value = 0.000 mg/l Sensor current = 0.000 mA ClO2- ClO2Sensor current = Push CAL key before tapping sampling water HELP OFF Sensor calibration Sensor calibration Redox Cl free CAL CAL Sensor calibration 4.030 mA Zero point calibration Push CAL key Enter value and push CAL key CAL CAL Calibration value = 0.000 mg/l Range: 0.000...9.999 mg/l CAL CAL pH Sensor calibration Sensor calibration Redox ClO2- Calibration value = Temp. value: Sensor current = Cl free 0.0 mg/l 32.0 °C Temp ClO2- 0.003 mA Zero point calibration Push CAL key Sensor value = Slope Zero value= 4.6 mg/l 4.006 mA 0.004 mA Push CAL key before tapping sampling water CAL HELP OFF CAL A0163 Fig. 46: Chlorite (ClO2 -) zero point calibration CAUTION! – The sensor have been run-in – Only carry out a zero point calibration if: – you are using the sensor in the lower limit of the measuring range 1. Select the file card "CIO2 -“ - ‘Calibrate sensor’ (arrow keys) F5 CAL and press the ENTER button 2. Under [DPD value] enter the value 0.00 mg/l and press the ENTER-key - the following is now shown on the file card [Zero point calibration] 3. Shut down the measured water (acknowledge possible alarm with the ENTER button) ð - First inlet, then the outlet. 4. Dismantle the sensor 5. Rinse the sensor with chlorine free water 6. Dip the CLT sensor in a container of still mineral water or dis‐ tilled water. The water must be the same temperature as the sample water. 7. Stir with the sensor until the measured value of the sensor is stable and near zero for approx. 5 mins. 8. Then press the F5 key (CAL) 9. Re-install the sensor into the flow gauge 10. Open the shut-off valves for the measured water ð First open the outlet, then the inlet. 115 Calibration CAUTION! Now it is imperative to calibrate the ‘slope’ Calibrate slope for measured variable chlorite (CIO2 -) CAL pH Temp ClO2- Sensor value = Slope = Zero value = Sensor calibration Sensor calibration Redox Cl free CAL CAL Sensor calibration Calibration value = Temp. value = 4.8 mg/l 4.008 mA 0.004 mA ClO2Sensor current = Push CAL key before tapping sampling water HELP OFF 1.8 mg/l 32.0 °C ClO24.030 mA Calibration value = Temp. value = 1.80 mg/l 32.0 °C Sensor current = 4.030 mA Zero point calibration Push CAL key Enter value and push CAL key CAL CAL Calibration value = 1,800 mg/l Range: 0,000...9,999 mg/l CAL CAL pH Sensor calibration Sensor calibration Redox ClO2- Calibration value = Temp. value: Sensor current = 1.8 mg/l 32.0 °C Cl free 4.003 mA ClO2- Temp Zero point calibration Push CAL key Sensor value = Slope Zero value = 4.6 mg/l 4.006 mA 0.004 mA Push CAL key before tapping sampling water CAL HELP OFF CAL ESC Central menu item A0164 Fig. 47: Chlorite (ClO2 -) CAUTION! – Before calibrating the slope, wait until the meas‐ ured value is constant (minimum 15 mins) – Chlorite must be permanently present in the sample water (approx 0.5 mg/l)! Otherwise the measuring system cannot calibrate. – Check the calibration 24 hrs after initial commis‐ sioning by means of DPD 116 1. Select the file card "CIO2 -“ - ‘Calibrate sensor’ off (arrow keys) 2. If the [Sensor value] is stable, press F5 3. Immediately afterwards, take a water sample from the flow gauge 4. Immediately afterwards determine the CIO2 - content of the sample water with a photometer and a suitable sampling instrument (e.g. DPD) 5. Enter the CIO2 --content (arrow keys) and press F5 CAL 6. If you do not want to carry out any more calibrations, press the ESC key to return to the permanent display Calibration In the event that the DXCa indicates an excessively low measured value or cannot be calibrated after the sensor has been run in (for CLT approx. 2 - 6 hrs) then the run-in times should be doubled and extended into the following day. If the sensor still cannot not be calibrated, then please phone ProMinent customer service. 8.9 Calibrate measured variable for peracetic acid (PES) Calibrate measured variable slope for peracetic acid (PES) CAL pH Sensor calibration Redox Cl free Temp Sensor value = Slope = Zero value = 4.8 mg/l 4.008 mA 0.004 mA PES Push CAL key before tapping sampling water HELP OFF CAL A0165 Fig. 48: Calibrate measured variable for peracetic acid (PES) CAUTION! – Please also observe the operating instructions for the sensor and flow gauge – Following the replacement of a sensor membrane cap or electrolyte, the slope has to be calibrated – Avoid air bubbles in the measured water. Air bub‐ bles, which adhere to the membrane of the sensor, can result in too low a reading and thus lead to over-metering. – The slope has to be re-calibrated at regular inter‐ vals to ensure the optimal operation of the sensor. – Please note the applicable national guidelines for calibration intervals Prerequisites n Constant flow on flow gauge - minimum 20 l/h n Constant temperature of the sample water n The sensor have been run-in It is not necessary to carry out zero point calibration 117 Calibration CAL pH Temp Sensor value = Slope = Zero value = Calibration value = Temp. value = 4.8 mg/l 4.008 mA 0.004 mA 1.8 mg/l 32.0 °C PES PES Sensor current = PES Push CAL key before tapping sampling water HELP OFF Sensor calibration Sensor calibration Redox Cl free CAL CAL Sensor calibration 4.030 mA Calibration value = Temp. value = 1.80 mg/l 32.0 °C Sensor current = 4.030 mA Enter value and push CAL key Enter value and push CAL key CAL CAL Calibration value= 1.800 mg/l Range: 0.000...9.999 mg/l CAL CAL pH Sensor calibration Sensor calibration Redox PES Calibration value = Temp. value: Sensor current = Cl free 1.8 mg/l 32.0 °C Temp Sensor value = Slope Zero value = 4.6 mg/l 4.006 mA 0.004 mA PES 4.003 mA Enter value and push CAL key Push CAL key before tapping sampling water CAL HELP OFF CAL ESC Central menu item A0166 Fig. 49: Calibrate slope for peracetic acid (PES) CAUTION! – Check the calibration 24 hrs after initial commis‐ sioning – Repeat the calibration process in the event that the PES concentration varies by more than 15 % from the reference value 1. Select the file card[PES] - ‘Calibrate sensor’ (arrow keys) F5 CAL and press the ENTER button 2. Press F5 CAL if the sensor value is stable 3. Shut down the measured water (acknowledge possible alarm with the ENTER button) ð - First inlet, then the outlet. 4. Fill a standard solution with a known PES concentration e.g. into the DLG III flow gauge container 5. Stir the contents of the container with a magnetic stirring bar 6. Dip the sensor into the container until the measured value remains constant (15 mins). Enter the PES content (arrow keys) and press F5 CAL. 7. Open the shut-off valves for the measured water ð First open the outlet, then the inlet. 8. If you do not want to carry out any more calibrations, press the ESC key to return to the permanent display In the event that the DXCa indicates an excessively low measured value or cannot be calibrated after the sensor has been run in (for PAA approx. 1 - 2 hrs) then the run-in times should be doubled and extended into the following day. 118 Calibration If the sensor still cannot not be calibrated, then please phone ProMinent customer service. 8.10 Calibration measured variable temperature Calibration measured variable tem‐ perature CAL pH Redox Cl free Cl tot Sensor check Temp.meas with Pt1000/100 Sensor value = 24.9 °C Set value = 26.2 °C Temp The value can only be adjusted within a range of ± 4 °C deviating from the factory calibration HOME CAL A0167 Fig. 50: Calibration measured variable temperature – – – You should only calibrate an external temperature sensor if: – you are using the temperature measurement from chlorine sensors – you are using type PT100 temperature sensors – you have a precise reference instrument Do not exchange the temperature sensors during the calibration process The temperature value can only be adjusted within a range of ± 4 °C from the factory set calibrated value 1. Take a water sample of minimum 250 ml 2. Dip the external PT100 temperature sensor from the DXCa and the reference instrument sensor into the sample simulta‐ neously 3. Press the ENTER key when the sensor value is stable 4. Under [set value] enter the reference instrument value (arrow keys) and press the ENTER key 5. Press F5 (SAVE) in order to conclude the calibration process and store the values 6. If you do not want to carry out any more calibrations, press the ESC key to return to the permanent display 119 Assign parameters 9 Assign parameters MEAS pH Redox Cl free Cl tot CTRL OUTP ALARM ECO Measurement parameters Sensor check: Temp.input: Temp. value = ON Entry 25.6 °C Temp Flock HELP HOME DATE TIME LANGUAG A0136 Fig. 51: Assign parameters This chapter describes the menu items for the parameter groups: n n n n n Measurement Control mA Output Alarm Eco!Mode for the individual DXCa measured variables and flocculants. 9.1 All parameters Default values The default values can be loaded in the second menu item for the current file card with F4 (DEFAULT) Exit a file card in the parameter menu: 1. without saving: press the ESC key repeatedly until the DXCa returns to the permanent display 2. with saving: Press F5, if SAVE is shown above. Confirm the prompt ‘Really save?’ with the ENTER button. If you do not want to carry out any more parametric assignments, press the ESC key to return to the permanent display or central menu item. 9.2 Measurement Access to measurement settings 1. Back with ESC You can return back to the previous menu by pressing the ESC key. Access to the settings is realised from the central menu item 2. 120 Press the F3 button (PARAM) Assign parameters 3. Select the desired measured variable with the vertical arrow keys 4. Then select file card [MESS] with the horizontal arrow keys 5. Then press the ENTER button ð You are now in the control system settings area. 6. Select the desired parameter with the vertical arrow keys 7. Then press the ENTER button 8. Adjust the parameter with the vertical or horizontal arrow keys 9. Move the cursor to the left or right with the help of the hori‐ zontal arrow keys 10. Conclude your entry with the ENTER key 11. Exit the file card without saving: Press the ESC button. Exit the file card with saving: press F5 if [SAVE] is visible. Confirm the prompt [Really save?] with the ENTER button. 9.2.1 Parametric assignment pH MEAS pH Measurement parameters Sensor check: Temp. input: Temp. value = ON Entry 25.6 °C DEFAULT SAVE A0168 Fig. 52: Measurement pH Adjustable variables Increment Sensor check Off Remarks on liquid ref. Pot: Temp.input: Off appears only with configured equipotential bonding pin on Equipotential bonding pin must be connected PT1000 (100) Chlorine sensor or separate temperature sensor Entry Temp.value Sensor monitoring 0,0 ... 99.9 °C At [Temp.input. Entry ] Under "Sensor check" select [on] or [off], in order to switch the sensor monitoring system on or off. 121 Assign parameters The resistance of the pH sensor is measured if sensor monitoring is activated. If the resistance value remains under 2 MΩ for longer than 1 minute during operation, an error message appears in the central menu item. [pH sensor defective!]. However, if the value is above 200 MΩ and the measured signal fluctuates considerably, then error message [Fault pH input!] is triggered. 9.2.2 Parametric assignment redox System 1 MEAS Redox Measurement parameters Sensor check: Liquid ref. Pot: EIN EIN DEFAULT SAVE A0170 Fig. 53: Redox measurement Adjustable variables Increment Remarks Sensor check off The device van display a pH-corrected value for free chlorine on liquid ref. Pot: Sensor monitoring off appears only with configured equipotential bonding pin on Equipotential bonding pin must be connected Select under [Sensor check] [ON] or [ OFF], in order to switch the redox sensor monitoring system on or off. The resistance of the redox sensor is measured if sensor moni‐ toring is activated. If the resistance value remains under 2 MΩ for longer than 1 minute during operation, an error message appears in the central menu item. [Redox sensor defective!]. However, if the value is above 200 MΩ and the measured signal fluctuates considerably, then error message [Fault redox input!] is triggered. 122 Assign parameters 9.2.3 Parametric assignment "chlorine free" MEAS Measurement parameters pH correction: ON Cl free DEFAULT SAVE A0169 Fig. 54: Measurement for free chlorine Adjustable variables Increment Remarks pH correction on The device van display a pH-corrected value for free chlorine off NOTICE! If you calibrated with pH correction, then you may only measure with pH correction! If you calibrated without pH correction, then you may only measure without pH correction 123 Assign parameters 9.2.4 Parametric assignment "chlorine bound" System 1 MEAS Measurement parameters pH correction: ON Cl comb. DEFAULT SAVE A0171 Fig. 55: Measurement for bound chlorine Adjustable variables Increment Remarks pH correction on The device van display a pH-corrected value for bound chlorine off NOTICE! If you calibrated with pH correction, then you may only measure with pH correction. If you calibrated without pH correction, then you may only measure without pH correction. The DXCa calculates the displayed value for bonded chlorine as the difference between the measured values from the free chlorine and total chlorine sensors (CLE and CTE). 124 Assign parameters 9.2.5 Parametric assignment fluoride (F−) Pool 1 MEAS Measurement parameters Temp.input: Temp.value = Entry 32.0 °C F DEFAULT SAVE A0172 Fig. 56: Measurement fluoride (F−) Only available when the terminal [I in 2 ] on the I module is config‐ ured for measured variable "F-". Adjustable variables Increment Remarks Temp.input: switched off The device van display a pH-corrected value for free chlorine Entry Sensor * Temp.value 0,0 ... 99.9 °C At [ Temp.input. Entry] * Only available when the terminal [I in 3] on the I module is configured for measured variable [Temperature] 125 Assign parameters 9.2.6 Parametric assignment ClO2 Pool 1 MEAS Measurement parameters Temp.input: Temp.value = Entry 32.0 °C ClO2 DEFAULT SAVE A0173 Fig. 57: Measurement ClO2 Only available when the terminal [ I in 2] on the I module is config‐ ured for measured variable CIO2 and no chlorine sensor is con‐ nected. Adjustable variables Increment Remarks Temp.input: switched off The device van display a pH-corrected value for free chlorine Entry Sensor * Temp.value At [Temp.input. Entry] 0,0 ... 99.9 °C * Only available when the terminal [I in 3] on the I module is configured for measured variable [Temperature] 9.2.7 Parametric assignment H2O2 System 1 MEAS Measurement parameters Temp.input: Temp.value = Entry 32.0 °C H2O2 DEFAULT SAVE A0174 Fig. 58: Measurement H2O2 126 Assign parameters Only available when the terminal [I in 2] on the I module is config‐ ured for measured variable "CIO"2 and no chlorine sensor is con‐ nected. Adjustable variables Increment Remarks Temp.input: switched off The device van display a pH-corrected value for free chlorine Entry Sensor * Temp.value At [Temp.input. Entry] 0,0 ... 99.9 °C * Only available when the terminal[ I in 3] on the I module is configured for measured variable [Temperature] 9.3 Control Access to control settings 1. Back with ESC You can return back to the previous menu by pressing the ESC key. Access to the settings is realised from the central menu item 2. Press the F3 button (PARAM) 3. Select the desired measured variable with the vertical arrow keys 4. Then select file card [MESS] with the horizontal arrow keys 5. Then press the ENTER button ð You are now in the control system settings area. 6. Select the desired parameter with the vertical arrow keys 7. Then press the ENTER button 8. Adjust the parameter with the vertical or horizontal arrow keys 9. Move the cursor to the left or right with the help of the hori‐ zontal arrow keys 10. Conclude your entry with the ENTER key 11. Exit the file card without saving: Press the ESC button. Exit the file card with saving: press F5 if [SAVE] is visible. Confirm the prompt [Really save?] with the ENTER button. 127 Assign parameters 9.3.1 pH Control CAUTION! Always check if for the settings under [Control] or [control direction] the requirements have actually been set in the configuration menu. System 1 CTRL pH Control parameters Control type: Set point = Basic load = Neutral zone = Xp = Tn = Tv = Checkout time = Disturbance feedfwd: Control: 2-way PID 7.20 pH 0.0 % 0.05 pH 1.5 pH 0s 0s 0 min not active active DEFAULT SAVE A0175 Fig. 59: pH Control Adjustable variables Increment Control type Manual Remarks 2-way PID refer to Fig. 60 1-way PID refer to Fig. 61 2-way P 1-way P Set point 0,00 ... 12.00 pH Basic load -100,0 ... 100,0 % Neutral zone 0,00 ... 1.00 pH xp* 0,01 ... 70.00 pH Tn 0 ... 9999 s At [Control] [PID] Tv 0 ... 2500 s At [Control] [PID] control direction Acid pump Acid, under one-way control pH-raise Alkali, under one-way control checkout time 0 ... 999 min Not for [Control] [Manual] Cut-in interference vari‐ able not active man. metering mult. Multiplicative interference value from[ I in 1] add. Additive -100,0 ... 100,0 % under [Control] [Manual] * For definition xp see glossary 128 Assign parameters Adjustable variables Increment Remarks Control active The control circuit can be switched off independently from the START/STOP key. The START/STOP-key stops all control circuits in the selected system not active * For definition xp see glossary We recommend a pH value of 7.2, as chlorine offers an excellent level of disinfection in this range. In addi‐ tion, skin tolerance is good at this pH value. Fig. 60: Control type 2-way PID, without and with neutral zone I. Actuating variable II. Neutral Zone III. Set point A0177 Fig. 61: Control type 1-way PID, direction pH lower and direction pH raiser I. Actuating variable II. Set point 129 Assign parameters 9.3.2 Redox control Redox is not applicable if chlorine is controlled. System 1 CTRL Control parameters Redox Control type: Set point = Basic load = Xp = Tn = Tv = Checkout time = Control: 2-way PID 750 mV 0,0 % 20 mV 0 s 0 s 0 min active DEFAULT SAVE A0178 Fig. 62: Redox control Adjustable variables Increment Control type 2-way PID Disinfection controller 2-way P 2-Pt. contact Remarks refer to Fig. 63 Manual Control type 1-way PID Swimming pool con‐ troller 1-way P 2-Pt. contact refer to Fig. 63 Manual Set point 700 ... 850 mV Basic load 0,0 ... 100,0 % xp* 1 ... 1000 mV Tn 0 ... 9999 s At [Control] [PID] Tv 0 ... 2500 s At [Control] [PID] Switch diff. = 0 ... 50 mV MIN switch-on time 0 ... 6000 s MIN switch-off time 0 ... 6000 s checkout time 0 ... 999 min * For definition xp see glossary 130 Not for [Control] [Manual] Assign parameters Adjustable variables Increment Remarks Control active The control circuit can be switched off independently from the START/STOP key. The START/STOP-key stops all control circuits in the selected system not active * For definition xp see glossary CAUTION! Always check if for the settings under [Control] or [control direction] the requirements have actually been set in the configuration menu. A0179 Fig. 63: Example control type 2-point contact I. II. III. IV. Actuating variable Switching points Set point Switch diff. = 131 Assign parameters 9.3.3 Free chlorine control System 1 CTRL Control parameters Cl free 2 Pt.Contact Control type: 1.50 mg/l Set point = 0.05 mg/l Switch diff. = 120 s MIN ON-time = MIN OFF-time = 120 s 0 min Checkout time = not active Disturbance feedfwd: active Control: DEFAULT SAVE A0181 Fig. 64: Free chlorine control Adjustable variables Increment Control type 2-way PID Disinfection controller 2-way P 2-Pt. contact Remarks refer to Fig. 65 Manual Control type 1-way PID Swimming pool con‐ troller 1-way P 2-Pt. contact refer to Fig. 65 Manual Set point 0,00 ... 20.00 mg/l Basic load 0,0 ... 100,0 % xp* 0,10 ... 99.99 mg/l Tn 0 ... 9999 s At [Control] [PID] Tv 0 ... 2500 s At [Control] [PID] Switch diff. = 0,00 ... 0.50 mg/l MIN switch-on time 0 ... 6000 s MIN switch-off time 0 ... 6000 s checkout time 0 ... 999 min Not for [Control] [Manual] Control active The control circuit can be switched off independently from the START/STOP key. The START/STOP-key stops all control circuits in the selected system not active * For definition xp see glossary 132 Assign parameters CAUTION! Always check if for the settings under [Control] or [control direction] the requirements have actually been set in the configuration menu. A0180 Fig. 65: Example control type 2-point contact and PID controller for chlorine I. II. III. Actuating variable Switching points Set point IV. V Switch diff. = Control difference 9.3.4 Control for bound chlorine System 1 CTRL Control parameters Cl geb Control type: Set point = Switch diff. = Switch-on time = Switch-off time = Control = 2-Pt. contact 1.50 mg/l 0.05 mg/l 120 s 600 s ON DEFAULT SAVE A0182 Fig. 66: Control for bound chlorine Adjustable variables Increment Remarks Switching point 0,00 ... 20.00 mg/l Relay P4 can switch a UV plant above the switching point Switch diff. = 0,00 ... 0.50 mg/l MIN switch-on time 0 ... 9999 s MIN switch-off time 0 ... 9999 s Only [Control type] [2-Pt. contact] possible 133 Assign parameters Adjustable variables Increment Remarks Control active The control circuit can be switched off independently from the START/STOP key. The START/STOP-key stops all control circuits in the selected system not active Only [Control type] [2-Pt. contact] possible NOTICE! – A power relay must be configured in order that the entries can make effect – Control Cl geb serves to minimise the bound chlorine e.g. via a UV plant For explanation please refer to [limit value] in the glossary (the switching point corresponds to [max. Limit].) A0179 Fig. 67: Example control type 2-point contact I. II. III. IV. Actuating variable Switching points Set point Switch diff. = 9.3.5 Control temperature Adjustable variables Increment Remarks Switching point 0,0 ... 40.0 °C Comparable with set point. Relay P4 can switch the hot water solenoid valve of a heat exchanger Switch diff. = 0,0 ... 1.5 °C MIN switch-on time 0 ... 9999 s MIN switch-off time 0 ... 9999 s Control active not active Only [Control type] [2-Pt. contact ]possible 134 The control circuit can be switched off independently from the START/STOP key. The START/STOP-key stops all control circuits in the selected system Assign parameters NOTICE! – A power relay must be configured in order that the entries can make effect For explanation please refer to [limit value] in the glossary (the switching point corresponds to [max. Limit].) A0179 Fig. 68: Example control type 2-point contact I. II. III. IV. Actuating variable Switching points Set point Switch diff. = 9.3.6 Control flocculants System 1 CTRL Flock Dosing parameters Circulation = 100,00 Concentration = 0,1 mg/l Disturbance feedfwd: not active active Control: DEFAULT SAVE A0183 Fig. 69: Control flocculants Adjustable variables Increment Circulation 0,0 ... 500.0 m 3/h Concentration 0,1 ... 9.9 mg/l Remarks Desired concentration of flocculent Only [Control type] [2-Pt. contact] possible 135 Assign parameters Adjustable variables Increment Remarks Control active The control circuit can be switched off independently from the START/STOP key. The START/STOP-key stops all control circuits in the selected system. not active Cut-in interference vari‐ able not active mul. Only [Control type] [2-Pt. contact] possible Pump output If a flocculent pump is configured, the the DXCa indicates its metering capacity under pump capacity after it has been saved (calculated from circulation and concentration, realised via the stroke rate) - as a percentage of the max. output. Under max. output, the DXCa indicates the maximum mathemat‐ ical metering output of the pump type - for the set stroke length, 100% stroke rate and 1.5 bar counter pressure (identical with output in card file P1, P2 or P3 in the configuring menu). 9.3.7 Control fluoride (F−) System 1 CTRL Control parameters F Control type: Set point = Xp = Tn = Tv = Basic load = Checkout time = Control: PID controller 7.50 00.50 0s 0s 0.0 % 0 min not active A0184 Fig. 70: Control fluoride Adjustable variables Increment Control type PID controller (F−) Remarks P controller 2 Pt.Contact Manual Set point 0,00 ... 9.99 ppm Basic load 0,0 ... 100,0 % xp* 0 ... 1000 ppm * For definition xp see glossary 136 refer to Ä on page 136 Assign parameters Adjustable variables Increment Remarks Tn 0 ... 9999 s At [Control] [ PID] Tv 0 ... 2500 s At [Control] [PID] Switch diff. = 0 ... 50 ppm MIN switch-on time 0 ... 6000 s MIN switch-off time 0 ... 6000 s checkout time 0 ... 999 min Cut-in interference vari‐ able not active Control Not for [Control] [Manual] mult. Multiplicative interference value from [ I in 1] add. Additive interference value from [I in 1] active Control only with metering pumps with CANopen bus. The control circuit can be switched off independently from the START/STOP key. The START/STOP-key stops all control circuits in the selected system. not active * For definition xp see glossary CAUTION! Always check if for the settings under [Control] or [control direction] the requirements have actually been set in the configuration menu. A0179 Fig. 71: Example control type 2-point contact I. II. III. IV. Actuating variable Switching points Set point Switch diff. = 137 Assign parameters 9.3.8 Control chlorine dioxide (CIO2) Spring 1 CTRL Control parameters ClO2 Control type: Set point = Xp = Tn = Tv = Basic load = Checkout time = Control: PID controller 7.50 00.50 0s 0s 0.0 % 0 min not active A0185 Fig. 72: Control chlorine dioxide (CIO2) Adjustable variables Increment Control type PID controller Remarks P controller 2 Pt.Contact refer to Fig. 73 Manual Set point 0,00 ... 9.99 ppm Basic load 0,0 ... 100,0 % xp* 0 ... 1000 ppm Tn 0 ... 9999 s At [Control] [PID] Tv 0 ... 2500 s At [Control] [PID] Switch diff. = 0 ... 50 ppm MIN switch-on time 0 ... 6000 s MIN switch-off time 0 ... 6000 s checkout time 0 ... 999 min Cut-in interference vari‐ able not active Control mult. Multiplicative interference value from [I in 1] add. Additive interference value from[ I in 1] active Control only with metering pumps with CANopen bus. The control circuit can be switched off independently from the START/STOP key. The START/STOP-key stops all control circuits in the selected system. not active * For definition xp see glossary 138 Not for [Control] [Manual] Assign parameters CAUTION! Always check if for the settings under [Control] or [control direction] the requirements have actually been set in the configuration menu. A0179 Fig. 73: Example control type 2-point contact I. II. III. IV. Actuating variable Switching points Set point Switch diff. = 9.3.9 Control H2O2 Spring 1 CTRL Control parameters H2O2 Control type: Set point = Xp = Tn = Tv = Basic load = Checkout time = Control: PID controller 7.50 00.50 0s 0s 0.0 % 0 min not active A0186 Fig. 74: Control H2O2 Adjustable variables Increment Control type PID controller Remarks P controller 2 Pt.Contact refer to Fig. 75 Manual * For definition xp see glossary 139 Assign parameters Adjustable variables Increment Set point 0,00 ... 1999 ppm Basic load 0,0 ... 100,0 % xp* 0 ... 1000 ppm Tn 0 ... 9999 s At [Control ] [PID] Tv 0 ... 2500 s At [Control] [PID] Switch diff. = 0 ... 50 ppm MIN switch-on time 0 ... 6000 s MIN switch-off time 0 ... 6000 s checkout time 0 ... 999 min Cut-in interference vari‐ able not active Control Remarks Not for [Control] [Manual] mult. Multiplicative interference value from [I in 1] add. Additive interference value from [l in 1] active Control only with metering pumps with CANopen bus. The control circuit can be switched off independently from the START/STOP key. The START/STOP-key stops all control circuits in the selected system. not active * For definition xp see glossary CAUTION! Always check if for the settings under [Control] or [control direction] the requirements have actually been set in the configuration menu. A0179 Fig. 75: Example control type 2-point contact I. II. III. IV. 140 Actuating variable Switching points Set point Switch diff. = Assign parameters 9.4 Set mA output To be carried out in a uniform manner for all measured variables Access to settings for mA output 1. Back with ESC You can return back to the previous menu by pressing the ESC key. Access to the settings is realised from the central menu item 2. Press the F3 button (PARAM) 3. Select the desired measured variable with the vertical arrow keys 4. Then select file card [OUTP] with the horizontal arrow keys 5. Then press the ENTER button ð You are now in the control system settings area. 6. Select the desired parameter with the vertical arrow keys 7. Then press the ENTER button 8. Adjust the parameter with the vertical or horizontal arrow keys 9. Move the cursor to the left or right with the help of the hori‐ zontal arrow keys 10. Conclude your entry with the ENTER key 11. Exit the file card without saving: Press the ESC button. Exit the file card with saving: press F5 if [SAVE] is visible. Confirm the prompt [Really save?] with the ENTER button. System 1 OUTP pH Parameters mA-output Value 0/4 mA = Value 20 mA = Range: Value on error = 0.00 pH 14.00 pH 0-20 mA 23 mA DEFAULT SAVE A0187 Fig. 76: Set mA output for example pH Adjustable variables Increment Remarks Value 0/4 mA 0,00 ... xx,xx Y * mA-value dependent on [Range] Value 20 mA 0,00 ... xx,xx Y * * "xx,xx Y" stands for the value and the unit of measurement for a measured variable on this controller 141 Assign parameters Adjustable variables Increment Remarks Range 0-20 mA Not for [Iout ] [free] (see configuration) 4-20 mA Value on error Not for [Iout] [free] (see configuration) 23 mA OFF 3.7 mA 22 mA * "xx,xx Y" stands for the value and the unit of measurement for a measured variable on this controller 9.5 Alarm settings To be carried out in a uniform manner for all measured variables Access to alarm settings 1. Back with ESC You can return back to the previous menu by pressing the ESC key. Access to the settings is realised from the central menu item 2. Press the F3 button (PARAM) 3. Select the desired measured variable with the vertical arrow keys 4. Then select file card [ALARM] with the horizontal arrow keys 5. Then press the ENTER button ð You are now in the control system settings area. 6. Select the desired parameter with the vertical arrow keys 7. Then press the ENTER button 8. Adjust the parameter with the vertical or horizontal arrow keys 9. Move the cursor to the left or right with the help of the hori‐ zontal arrow keys 10. Conclude your entry with the ENTER key 11. Exit the file card without saving: Press the ESC button. Exit the file card with saving: press F5 if [SAVE] is visible. Confirm the prompt [Really save?] with the ENTER button. 142 Assign parameters System 1 AL pH Alarm parameters min. limit = min. alarm: max. limit = max. Alarm: Delay = 5.00 pH not active 8.00 pH active 10 s DEFAULT SAVE A0188 Fig. 77: Set alarm for example pH ALARM Q Alarm parameters min. limit = min. alarm: max. limit = max. alarm: Delay = Switching off controller: 20,0 not active 80,0 not active 0s not active DEFAULT SAVE A0270 Fig. 78: Set alarm for an example flow meter Adjustable variables Increment Remarks Min.Limit 0,00 ... xx,xx Y * Min.Alarm Inactive Only fault alert in the event of error Active In the event of fault, fault alert, signal horn, relay Must be acknowledged Max.Limit 0,00 ... xx,xx Y * Max.Alarm Inactive Only fault alert in the event of error Active In the event of fault, fault alert, signal horn, relay Must be acknowledged Delay 0 ... 3600 s * "xx,xx Y" stands for the value and the unit of measurement for a measured variable on this controller 143 Assign parameters 9.6 Parametric assignment flow meter ALARM Q Alarm parameters min. limit = min. alarm: max. limit = max. alarm: Delay = Switching off controller: 20,0 not active 80,0 not active 0s not active DEFAULT SAVE A0270 Fig. 79: Alarm flow meter Adjustable variables Increment min. Limit 0,00 ... 99.99 m 3/h min. Alarm active not active max. Limit 0,00 ... 99.99 m 3/h Max. Alarm active not active Delay 0 ... 3600 seconds Switching off controller active not active 144 Remarks Assign parameters 9.7 Setting Eco!Mode For detailed information about the configurable varia‐ bles see Ä Chapter 9.1 ‘All parameters’ on page 120 Access to settings for ECO mode 1. Back with ESC You can return back to the previous menu by pressing the ESC key. Access to the settings is realised from the central menu item 2. Press the F3 button (PARAM) 3. Select the desired measured variable with the vertical arrow keys 4. Then select file card [ECO] with the horizontal arrow keys 5. Then press the ENTER button ð You are now in the control system settings area. 6. Select the desired parameter with the vertical arrow keys 7. Then press the ENTER button 8. Adjust the parameter with the vertical or horizontal arrow keys 9. Move the cursor to the left or right with the help of the hori‐ zontal arrow keys 10. Conclude your entry with the ENTER key 11. Exit the file card without saving: Press the ESC button. Exit the file card with saving: press F5 if [SAVE] is visible. Confirm the prompt [Really save?] with the ENTER button. System pH 1 ECO ECO-mode parameters Control type: Set E = XpE = TnE = TvE = 2-way PID 7.20 pH 1.50 pH 0s 0s SAVE A0189 Fig. 80: Setting Eco!Mode 145 Assign parameters Eco!Mode enables a 2nd set of parameters to be temporarily acti‐ vated in order to save power. This can, for example, be carried out synchronously with a reduction in the circulating output. Eco!Mode is activated or deactivated as soon as a contact is switched on contact input K3 of the M module. Eco!Mode is available for all M module measured variables, if they are controlled: n n n n n n pH Redox chlorine free chlorine bound Temperature Flocculent As soon as the 2nd set of parameters is activated, the central menu item indicates a green ECO identifier. In order to activate it, open the file card DXMaM in the configuration menu and set con‐ nection K3 to "Eco!Mode". 9.8 Chlorine dosing redox dependent System 1 AL Redox Alarm parameters min. limit = min. alarm : max. limit = max. alarm : Delay = 5,00 pH not active 8,00 pH active 10 s Chlorine dosing redox dependent: Factor F = Redox -> Cl limit = Xp Redox -> Cl = DEFAULT active 1,00 800 mV 100 mV SAVE A0340 Fig. 81: Chlorine dosing redox dependent This setting under Parameter > Redox > Alarm enables the ‘Chlorine’ metering to be influenced by the ‘Redox’ measured var‐ iable. Example: ‘Chlorine dosing redox dependent’ is active and set value Chlorine is 100% k=0.5 and redox ➨ "Cl Limit" = 800 mV n Reading ‘Redox’ is < than redox ➨ ‘Cl Limit’ = 800 mV – then the ‘Cl’ set value remains unchanged at 100% n Reading ‘Redox’ is > than redox ➨ ‘Cl Limit’ = 800 mV – then the ‘Cl’ set value is multiplied by ‘k’ – ➨ 100 % * 0,50 ➨ 50 % reduction in ‘Cl’ metering If k=1 then Xp = 100 mV value for proportional metering n Reading ‘Redox’ is < than redox ➨ ‘Cl Limit’ = 800 mV – then the ‘Cl’ set value remains unchanged at 100% n Reading ‘Redox’ (801 mV) is > than redox ➨ ‘Cl Limit’ = 800 mV – then the ‘Cl’ Set value 100 % - (801-800) * 100 % / 100 = 99 % 146 Assign parameters n Reading ‘Redox’ (900 mV) is > than redox ➨ ‘Cl Limit’ = 800 mV – then the ‘Cl’ Set value 100 % - (900-800) * 100 % / 100 = 0 % n Reading ‘Redox’ (910 mV) is > than redox ➨ ‘Cl Limit’ = 800 mV – then the ‘Cl’ Set value 100 % - (910-800) * 100 % / 100 = 0 % This behaviour enables a reduction in chlorine metering, despite the fact that according to the chlorine measurement, the proportion of ‘Chlorine’ in the sample water is too low. However, due to the high redox potential, a sufficient level of disinfection is still ensured. 147 Configure 10 Configure Pool Sensor RTD: (pH)ORP: POT1: POT2: (pH)ORP: terminals free Redox sensor free free pH sensor Soft. vers. 0967 OPTION HELP Digital inputs K1: Sampling water K1: Type: NO Delay = 0s K2: Pause K2: Type: NO Delay = 0s K3: Eco!Mode K3: Type: NO Node - ID 15 Serial no. 2004106040 PASSW UPDATE BUS A0190 Fig. 82: Configure The file cards of the individual CAN modules show the software version of the module on the left-hand side and, to the right, the assigned CAN node number (Node ID) and the serial number (R. no. on the module type plate). – – – Access to configuration settings 1. The CAN-chlorine sensors and CAN-pumps are also modules Terminals that are not occupied must be config‐ ured as ‘free ’ Each file card indicates the alignment of the module terminals with a coloured background at the top as a mnemonic aid Back with ESC You can return to the previous menu by pressing the ESC key. Access to the settings is realised from the central menu item 2. Then press the F4 button (CONFIG) 3. Select the desired measured variable with the horizontal arrow keys 4. Then press the ENTER button ð You are now in the control system settings area. 5. Select the desired parameter with the vertical / horizontal arrow keys ð The selected parameter will be shown with a black back‐ ground 148 6. Then press the ENTER button 7. Adjust the parameter with the vertical or horizontal arrow keys 8. Move the cursor to the left or right with the help of the hori‐ zontal arrow keys 9. Conclude your entry with the ENTER key Configure 10. Exit the file card without saving: press the ESC key Exit the file card with saving: Press F5 if [SAVE ]is displayed. Confirm the query [Save changes?] by pressing the ENTER key 10.1 Configuring module DXMaM M module (measurement module) Becken Sensor terminals RTD: Pt1000/100 (pH)ORP: ORP-Sensor POT1: not used POT2: not used (pH)ORP: pH-sensor Digital inputs K1: Sampling water K1: type: NO delay= 0s K2: Pause K2: type: NO delay= 0s K3: Eco!Mode K3: type: NO Eco!Mode CONFIG DEFAULT SAVE Fig. 83: M module (measurement module) Sensor terminals Terminals / adjustable variables Increment Remarks RTD (Temperature) PT1000/PT100 PT1000/PT100 (self detection) if no chlorine sensor is used not used not occupied (pH) ORP POT1 POT2 pH (ORP) ORP sensor free not occupied Flow.potential* Closed [(pH) ORP] free not occupied Liquid ref. pot* Closed [pH (ORP)] free not occupied pH sensor free not occupied * For equipotential bonding pin. Do not connect to earth! No jumper necessary. Digital inputs Terminals / adjustable variables Increment Remarks K1 Sampling water Sample water monitoring K1 type NC K1 – K3 are the digital inputs on the M module DXMaM (the A module DXMaA has the same identifiers!). 149 Configure Terminals / adjustable variables Increment Remarks NO Delay (contact) 0 ... 3600 s K2 NC NO Delay (contact) 0 ... 3600 s K3 Eco!Mode 2. Set of parameters for all controlled varia‐ bles not assigned Excess chlorination Excess chlorination & Eco!Mode free K3 type NC NO K1 – K3 are the digital inputs on the M module DXMaM (the A module DXMaA has the same identifiers!). Filter backflushing Excess chlorination functional description: n Filter backflushing is started by an external controller n The control circuits for pH, chlorine, ORP and flocculent are set to pause via the M module contact K2. ‘K2 ACTIVE’ n M module contact K3 (this must be set to ‘Excess chlorination’ or ‘Excess chlorination & Eco!Mode’ ) serves to force the chlorine actuator ‘active’ if K2 and K3 are both ‘active’ . n Controllable with a configurable percentage input (0-100%) and duration limited from 1 - 20 minutes n This only applies to the chlorine actuating variable - all others are set to pause. n The control is realised without controller and without considera‐ tion of error messages relating to the sample water n The following message is shown on the display: ‘Pool No. "n" chlorine: Excess chlorination’ n Filter backflushing does not work with the R module n Stop / start by pressing the STOP/START button, but the time for Excess chlorination continues to run, regardless of whether stop is pressed or not. After start, the remaining time will still be metered. All messages are written to the ‘Event File’ . 10.1.1 150 Configuring module DXMaM ECO mode 1. Select the menu ‘Configure’ , see Ä ‘Access to configuration settings’ on page 148 2. Select the menu ‘Configuring module DXMaM’ , see Ä Chapter 10.1 ‘Configuring module DXMaM’ on page 149 Configure ECO-mode parameters 3. In the menu ‘Configuring module DXMaM’ press key F2 [Eco!Mode CONFIG] ð The following display appears: System 1 ECO-mode parameters ECO ISO: ECO Contact: ECO 0-24 h: ECO time: active inactive inactive active every day ECO start-time: from: 10 : 11 clock ECO End-time: until: 12 : 10 clock ECO takes: 02 h ISO NORM SAVE CONFIG A0614 Fig. 84: Display: Configuring DXMaM ECO-mode parameters 4. Select the desired parameter using the vertical/horizontal arrow keys and confirm by pressing the ENTER key ð The following display appears: System 1 ECO-mode parameters ECO ISO: ECO Contakt: ECO 0-24 h: ECO time: active inactive inactive active every day ECO start-time: from: 10 : 11 Uhr ECO End-time: until: 12 : 10 clock ECO takes: 02 h ECO ISO: active A0617 Fig. 85: Parameter adjustment 151 Configure 5. Select the desired state, e.g. active/inactive, using the ver‐ tical/horizontal arrow keys and confirm by pressing the ENTER key ð The following display appears: System 1 ECO-mode parameters ECO ISO: ECO Contact: ECO 0-24 h: ECO time: every day ECO start-time: from: 10 : 11 clock ECO End-time: until: 12 : 10 clock active inactive inactive active ECO takes: 02 h ISO NORM SAVE CONFIG A0614 Fig. 86: Display: Configuring DXMaM ECO-mode parameters You can carry this process out for all displayed parame‐ ters DIN parameter 6. In the ECO-mode parameters menu press key F2[ ISO standard CONFIG] ð The following display appears: System 1 Parameter ISO ISO value ON/OFF pH ORP Cl comb. Cl Temp MINIMAL WERTE pH = 6,50 pH active inactive inactive inactive inactive MAXIMAL WERTE pH = 7,60 pH SAVE A0615 Fig. 87: Display: ISO parameter 152 Configure 7. Select the desired parameter using the vertical/horizontal arrow keys and confirm by pressing the ENTER key ð The following display appears: System 1 Parameter ISO ISO value ON/OFF pH ORP Cl comb. Cl Temp MINIMAL WERTE pH = 6,50 pH pH = 06.50 pH Rng. : active inactive inactive inactive inactive MAXIMAL WERTE pH = 7,60 pH 0,00 ... 14,00 pH A0618 Fig. 88: Parameter adjustment 8. Select the desired value, e.g. 06.51 pH using the vertical/hor‐ izontal arrow keys and confirm by pressing the ENTER key ð The following display appears: System 1 Parameter ISO ISO value ON/OFF pH ORP Cl comb. Cl Temp MINIMAL WERTE pH = 6,50 pH active inactive inactive inactive inactive MAXIMAL WERTE pH = 7,60 pH SAVE A0615 Fig. 89: Display: ISO parameter 153 Configure 9. Further procedure: n You can now repeat this process as often as necessary for the selectable parameter n or exit the menu by pressing the ESC key, so that the set parameter is not adopted n or you can press the F5 [SAVE]key, whereupon the set parameters are adopted F5 [SAVE]: The parameters are written to the controller. ð After pressing the ESC or F5 key, the following display appears: System 1 ECO-mode parameters ECO ISO: ECO Contact: ECO 0-24 h: ECO time: active inactive inactive active every day ECO start-time: from: 10 : 11 clock ECO End-time: until: 12 : 10 clock ECO takes: 02 h ISO NORM CONFIG SAVE A0614 Fig. 90: Display: Configuring DXMaM ECO-mode parameters 10. Further procedure: n You can now repeat this process as often as necessary for the selectable parameter n or exit the menu by pressing the ESC key, so that the set parameter is not adopted n or you can press the F5 [SAVE]key, whereupon the set parameters are adopted F5 [SAVE]: The parameters are written to the controller. ð After pressing the ESC or F5 key, you return here Ä Chapter 10.1 ‘Configuring module DXMaM’ on page 149 154 # Parameter 0 NO ECO 1 ISO + contact +24 h 2 ISO + contact + time 3 ISO + contact 4 ISO + time 5 ISO + 24 h 6 Contact + time 7 Contact + 24 h 8 Contact Configure # Parameter 9 Time 10 24 h - not allowed 11 ISO 155 Configure 10.2 Configuring module DXMaA A module (control module) System 1 A DXMaA R1 R2 R3 K1 K2 K3 Iout1 Iout2 Iout3 Iout4 Pump terminals Recorder R1: Acid pump Iout1: pH Value Max . freq. = 180 Str/min Iout2 :ORP value K1 type NO Iout3 :free chlorine R2: ORP pump Iout4 :ph lower dosing Max . freq. = 180 Str/min K2 type NO R3: Flocculant pump = 180 Str/min Max . freq. Capacity= 1,40 l/h K3 type NO Circulation SERVICE CONFIG DEFAULT SAVE A0192 Fig. 91: Configuring module DXMaA Pump terminals: Terminals / adjustable variables Increment Remarks R1 Acid pump For external input acid pump Alkaline pump For external input alkali pump free not occupied max. freq. 0 ... 500 strokes Only if the pump is selected K1 type NO Only if the pump is selected NC Only if the pump is selected free not occupied Chlorine pump For external input sodium hypochlorite pump Acid pump For external input acid pump ORP pump For external input free not occupied Ctrl.out 12 mA If DXMaI is selected on the bus 0 ... 500 strokes Only if the pump is selected NO Only if the pump is selected NC Only if the pump is selected free not occupied Flocculent pump For external input flocculent pump Chlorine pump For external input sodium hypochlorite pump ORP pump For external input R2 max. freq. R3 R1 – R3 are frequency outputs; K1 – K3 are digital inputs. K1 – K3 are the digital inputs of the A module DXMaA (the M module DXMaM has the same identifiers!). 156 Configure Terminals / adjustable variables Increment Remarks free not occupied max. freq. 0 ... 500 strokes Only if the pump is selected Performance 0,10 ... 18.00 l/h Only if the pump is selected K3 type NO Only if the pump is selected NC Only if the pump is selected R1 – R3 are frequency outputs; K1 – K3 are digital inputs. K1 – K3 are the digital inputs of the A module DXMaA (the M module DXMaM has the same identifiers!). 157 Configure Outputs 0/4-20 mA (standard signal outputs): Terminals / adjustable variables Increment Remarks lout1 pH value for recorder pH lower dosing Control variable pH lift dosing Control variable Cl. dosing Control variable Flocc.dosing Control variable Ctrl. out ORP Control variable Value I2 Ctrl.out I2 Value I3 Cl. dosing ORP dosing Iout2 free not occupied ORP value for recorder Variable pH-lower Setpoint Variable pH-raise Setpoint Variable chlorination Setpoint Variable flocculent Setpoint Ctrl. out ORP Setpoint Value I2 Ctrl.out 12 mA Value I3 Variable chlorinationORP dosing Dosing circulation Iout3 frei nicht belegt Wert Chlor für Schreiber Stell. pH-Senker Stellgröße Stell. pH-Heber Stellgröße Stell. Chlorung Stellgröße Stell. Flockung Stellgröße Ctrl. out ORP Stellgröße Wert I2 Ctrl.out I2 Value I3 Cl. dosing ORP dosing free 158 not occupied Configure Terminals / adjustable variables Increment Remarks lout4 Comb. chlorine for recorder, "Comb. chlorine value" is the difference between the measured values from CLE and CTE Stell. pH-Senker Stellgröße Stell. pH-Heber Stellgröße Stell. Chlorung Stellgröße Ctrl. out ORP Control variable Temperat. val. For recorder (plotting): temperature value comes from the chlorine sensor or PT1000/ PT100 Value I2 Ctrl.out I2 Value I3 Cl. dosing ORP dosing free 10.2.1 not occupied Configuring module DXMaA circulation pump Configure circulation pump parameter 1. Select the menu ‘Configure’ , see Ä ‘Access to configuration 2. Select the menu ‘Configuring module DXMaA’ , see 3. In the menu ‘Configuring module DXMaA’ press key F3 settings’ on page 148 Ä Chapter 10.2 ‘Configuring module DXMaA’ on page 156 [Circulation CONFIG] ð The following display appears: System 1 parameter circulation Range : Value 0/4 mA= Value 20 mA= 0-20 mA 0 m3/h 1000 m3/h circul. act. normal operation = circulation activity backwash = circul. activity ECO Mode min = ISO error -> circul. act. -> 100 % : 70 % 85 % 40 % inactive ORP -> circulation dependence: circulation reduction = circulation lowering time = inactive 5% 20 s SAVE A0620 Fig. 92: Display: Configure DXMaA parameter recirculation 159 Configure 4. Select the desired parameter using the vertical/horizontal arrow keys and confirm by pressing the ENTER key ð The following display appears: System 1 parameter circulation Range : Value 0/4 mA= Value 20 mA= 0-20 mA 0 m3/h 1000 m3/h circul. act. normal operation = cirlculation activity backwash = circul. activity ECO mode min. = ISO error -> circul. act. -> 100 % : 70 % 85 % 40 % inactive ORP-> cirlculation dependence: inactive cirlculation reduction = cirlculation lowering time = 5% 20 s circul. activity ECO mode min. = 040 % Rng : 0 .. 100 % A0619 Fig. 93: Parameter adjustment 5. Select the desired value, e.g. 040 % using the vertical/hori‐ zontal arrow keys and confirm by pressing the ENTER key ð The following display appears: System 1 parameter circulation Range : Value 0/4 mA= Value 20 mA= 0-20 mA 0 m3/h 1000 m3/h circul. act. normal operation = circulation activity backwash = circul. activity ECO Mode min = ISO error -> circul. act. -> 100 % : 70 % 85 % 40 % inactive ORP -> circulation dependence: circulation reduction = circulation lowering time = inactive 5% 20 s SAVE A0620 Fig. 94: Display: Configure DXMaA parameter recirculation You can carry this process out for all displayed parame‐ ters 160 Configure 6. Further procedure: n You can now repeat this process as often as necessary for the selectable parameter n or exit the menu by pressing the ESC key, so that the set parameter is not adopted n or you can press the F5 [SAVE]key, whereupon the set parameters are adopted F5 [SAVE]: The parameters are written to the controller. ð After pressing the ESC or F5 key, the following display appears: System 1 A DXMaA R1 R2 R3 K1 K2 K3 Iout1 Iout2 Iout3 Iout4 Pump terminals Recorder R1: Acid pump Iout1: pH Value Max . freq. = 180 Str/min Iout2 :ORP value K1 type NO Iout3 :free chlorine R2: ORP pump Iout4 :ph lower dosing Max . freq. = 180 Str/min K2 type NO R3: Flocculant pump = 180 Str/min Max . freq. Capacity= 1,40 l/h K3 type NO Circulation SERVICE CONFIG DEFAULT SAVE A0192 Fig. 95: Configuring module DXMaA Allowable set values Parameter Factory setting Possible value Range 4-20 mA 0-20 mA/4-20 mA Value 0/4 mA 0 m 3/h 0 ... 9,999 m 3/h value 20 mA 1,000 m 3/h 0 ... 9,999 m 3/h Circulation capacity normal operation 70 % 0 % ... 100 % Backwashing circulation capacity 85 % 0 % ... 100 % ECO circulation capacity 40 % 0 % ... 100 % Circulation DIN error Inactive Active / inactive ORP circulation Inactive Active / inactive Circulation reduction 5% 0 % ... 100 % Circulation reduction time 20 s 0 ... 9999 s 161 Configure 10.3 Configuring module DXMaP P module (power supply module) Pool 1 P DXMaP Relay outputs P1 P1: Alarm horn P2: PWM Acid pump P3: PWM chlorine P4: Enabling UV P2 P3 P4 L N PE Cycle time= min.switch-on time= Cycle time= min.switch-on time= DEFAULT 10.0 1.0 10.0 1.0 s s s s SAVE A0193 Fig. 96: Configuring module DXMaP The power relays P1 (alarm) from all P modules always open and close together. Pump terminals: Terminals / adjustable variables Increment P1 Signal horn P2 PWM acid Solenoid valve or activation of pump (acid) PWM alkaline Solenoid valve or activation of pump (alkali) free not occupied PWM alkaline Solenoid valve or activation of pump (alkali) PWM chlorine Solenoid valve or activation of pump (sodium hypochlorite) PWM ORP Solenoid valve or activation of pump PWM acid Solenoid valve or activation of pump (acid P3 Remarks PWM I2 mA Backwashing P4 free not occupied UV enable Releases lock PWM chlorine Solenoid valve or activation of pump (sodium hypochlorite) PWM ORP Solenoid valve or activation of pump Heating enable free not occupied The cycle times are to be taken into consideration when controlling solenoid valves (PWM = pulse width modulation). 162 Configure Terminals / adjustable variables Increment Cycle time 0.0...999.0 s MIN ON-time 0.0..0.500.0 s Remarks The cycle times are to be taken into consideration when controlling solenoid valves (PWM = pulse width modulation). Solenoid valve relay Solenoid valve Cycle t on min. time t Actuating variable: 80 % t on = 0.80 Cycle t Actuating variable: 50 % t on = 0.50 Cycle on off Cycle t on on off A0025_GB Fig. 97: Solenoid valves The switching times of the DXCa (solenoid valve) depend on the actuating variable and the ‘min. time’ (smallest permissible switchon time for the connected device). The actuating variable deter‐ mines the ratio ton/cycle and thus also the switching times (see Fig. 97). The ‘min. time’ affects the switching times in two situa‐ tions: Theoretical switching time < min. time Cycle Cycle Cycle min. time on theoretical off Cycle Cycle Cycle t min. time on actual off t A0026_GB Fig. 98: Theoretical switching time < min. time DXCa does not switch on for a certain number of cycles until the sum of the theoretical switching times exceeds ‘min. time’ . Then it switches for the duration of this total time. 163 Configure Theoretical switching time > (cycle min. time) and calculated switching time < cycle Cycle Cycle Cycle min. time on theoretical off Cycle Cycle Cycle t min. time on actual off t A0027_GB Fig. 99: Theoretical switching time > (cycle - min. time) and calculated switching time < cycle DXCa does not switch off for a certain number of cycles until the differences between the cycle and the theoretical switching time exceed ‘min. time’ . 10.4 Configuration for free chlorine module Sensor CLE From software version 3014, the free chlorine sensor CLE3 can be set to a high measurement range of up to 100 ppm. As supplied, the measuring range is up to 10 ppm. WARNING! Danger of over-metering Possible consequence: Fatal or very serious injuries. Measure: If the high measuring range is activated or deactivated, then the control parameters and alarm threshold must be matched to the changed circum‐ stances. 164 Configure Pool l P3 M A P Cl Cl R free High range: inactive after activate or deactivate high range set again all parameters(alarms, control...) Soft. vers. 0967 HELP HOME Node - ID 15 Serial nr. 2004106040 PASSW UPDATE BUS A0194 Fig. 100: Module Cl free The file cards only show the software version, the CAN node number (node ID) and the serial number (R. no. on the module type plate), as the CAN connection of the chlorine sensor does not have to be configured. 10.5 Configuration for total chlorine module Sensor CTE Pool total Display: Cl total: Cl comb.: Soft. vers. 0967 HELP HOME l P3 M A P Cl Cl R not active active Node - ID 15 Serial no. 2004106040 PASSW UPDATE BUS A0195 Fig. 101: Configuration for total chlorine module The file cards only show the software version, the CAN node number (node ID) and the serial number (R. no. on the module type plate). In addition, under [Display] you can set which concen‐ tration the DXCa should display. Adjustable variables Increment Cl total Remarks not active active Cl bound not active active 165 Configure 10.6 Configuration for chlorine module Sensor CGE Pool M A P Cl Cl R Soft. vers. 0967 HELP HOME l P3 Node - ID 15 Serial no. 2004106040 PASSW UPDATE BUS A0196 Fig. 102: Configuration for chlorine module The file cards only show the software version, the CAN node number (node ID) and the serial number (R. no. on the module type plate), as the CAN connection of the chlorine sensor does not have to be configured. 166 Configure 10.7 Configuration of R module (control module for chlorine gas metering device) Module DXMaR Close Control: Open Closed Opened Position Chlorine control Closed Position A0197 Fig. 103: Configuration of R module (control module for chlorine gas metering device) Adjustable variable Increment Control Chlorine control Remarks Redox control Error message at the Dulcomarin II Cause Remedy Upper calibration point exceeded Upper camshaft switch was not triggered Check mechanism in chlorine gas metering device Lower calibration point exceeded Lower camshaft switch was not triggered Check mechanism in chlorine gas metering device Potentiometer not connected No positioning check-back signal to R module Check the wiring of the potentiom‐ eter in the chlorine gas metering device and the wiring in the R module for correct connection Incorrect direction of rotation The motor direction of rotation does not correspond with the potentiometer direction of rotation Check the wiring of the potentiom‐ eter and the relay control in the chlorine gas metering device and R module for correct connection Position not reached The chlorine gas metering device has not reached the calculated position Voltage supply interrupted, check wiring, excessive mechanism play Communication time-out The M module fails to answer within the allowed time window Module has not answered, check BUS cabling Lower stop too low Camshaft switch was not triggered Check mechanism, fasten cam Upper stop too high Camshaft switch was not triggered Check mechanism, fasten cam Calibration cycles unequal There are differences between the Check mechanism, replace cam if two calibration cycles necessary Calibration points outside permis‐ sible range Lower point < 2 %, upper > 98 % Adjust cam for limit switch. 167 Configure 10.8 Configuration for P1 module (metering pump module) CAN-Beta® Bus-connected pump Chlorine pump DEFAULT SAVE A0198 Fig. 104: Configuration for P1 module (metering pump module) Pump utilisation Adjustable variables Increment Remarks P1 Acid pump for acid Chlorine pump Flocculent pump Pump pH-raise for alkali Redox pump Chlorine pump Chlorine standby pump only with I module and chlorine sensor Pump NH4OH only with I module and chlorine sensor Redox pump Pump I2 Pump F- only if configured on I module Pump ClO2 only if configured on I module, without chlorine sensor Pump H2O2 only if configured on I module, without chlorine sensor free If there are numerous pumps connected to the CAN bus, a file card is displayed for each pump: P1, P2 and P3. The file card also displays the current values for the following variables: Variable Increment Remarks Pump output 0 ... 100 % Data about the current, relative pump output Stroke length 0 ... 100 % The metering accuracy reduces under 30% Filling level > 10 % Filling level OK 168 Configure Variable Increment Remarks < 10 % Prepare container exchange Container empty Exchange container Power Pump status Maximum mathematical metering output of the pump type for the set stroke length, 100% stroke rate and 1.5 bar OFF Multifunctional switch on Beta set to STOP ON Multifunctional switch on Beta not set to STOP Bus Multifunctional switch on Beta set to BUS Manual Multifunctional switch on Beta not set to BUS Calibrate pump! Calibration OK! CAN pumps must also be assigned to the pool even for systems with only a single pool. The metering output curves are stored for each stroke length at a constant back pressure of 1.5 bar in each Beta/4-CANopen. In the event that the stroke length varies by more than ±10 %, the DXCa signals an alarm and a message is shown on the display. However, the pump continues to operate. After the settings are stored (calibration), the message disappears and the DXCa will match the pump output to the new metering output curve. Chlorine standby pump The DXCa can control up to 4 metering pumps with CAN bus con‐ nection. It is possible to configure a metering pump for chlorine next to the main chlorine pump as a standby pump. In this case, the screen writer must be activated and an SD card must be inserted, as this stores the operating states in an event file on the SD card (see supplementary instructions screen writer). The following situations cause switchover to the standby pump: n Fault in the main chlorine pump n Chlorine chemical reservoir on the main pump is empty n The multifunctional switch on the main pump is set to ‘Stop’ . However, a power failure or disconnection of the bus connection to the main pump will not cause switchover to the standby pump. Pump NH4OH In the event that CAN-pumps are configured for chlorine regulation, then a pump can also be configured via "Pump NH4OH" for pur‐ poses of chloramination. In order to do so, an ammonia solution is metered in parallel to the chlorine solution. In order to achieve the correct stoichiometry, the concentration of the ammonia solution and the stroke length of the ammonia pump must be matched to the chlorine concentration in the treated water. 169 Configure 10.9 G module (limit value module) configuration Module DXMaG Relais outputs Alarm source relay1 Sampling water pHmin pHmax Clmin Clmax free free Delay=30 min norm. Inactive Alarm source relay2 Pool free free free free free free Delay= 0 min norm. Inactive A0199 Fig. 105: G module (limit value module) configuration Variable Increment Remarks Alarm sources Pool With ‘Pool’ it is possible to select all alarm sources. Only for alarm source 1 Sampling water Sample water monitoring pH min pH max Cl min Cl max I1 min I1 max I2 min I2 max I3min I3 max free Delay (error) 0 ... 999 min P1 type norm. Inactive (NO) Power relay P1 all norm. active (NC) P2 type P module norm. Inactive (NO) Power relay P2 all norm. active (NC) P module It is possible to select up to 7 alarm sources per power relay (the alarm sources are then OR linked). 170 Configure 10.10 I module (current input module) configuration Module DXMaI Pool XE2 123 +24V IN GND XE1 12 IN GND Flow EDIT 1111 Temp 0-20mA 4-20mA 4-20mA K1: Sampling water K1 Type: NO Soft. vers. 0967 HELP OPTION XE3 123 +24V IN GND 0.0 - 100.0 m3/h 0.00 - 27.0 xyz 0.0 - 100.0 °C K2: K2 Type: free NO Node - ID 15 Serial no. 2004106040 PASSW UPDATE BUS A0269 Fig. 106: Flow configuration Adjustable variables Increment Remarks Measured variable Sampling water Only on K1 Pause Only on K2 Flow Q only on ‘ I in 1’ ; can be used for measured variables ‘I in 2’ as interference value Turbidity only on ‘ I in 1’ or ‘ I in 3’ Conductivity only on ‘I in 2’ F- only on ‘I in 2’ O2 only on ‘I in 2’ ClO2 - only on ‘I in 2’ or ‘ I in 3’ H2O2 only on ‘I in 2’ UV only on ‘ I in 3’ Temp. only on ‘ I in 3’ PES only on ‘ I in 3’ ; peracetic acid Range 0-20 mA 4-20 mA Unit / adjustable variables Increment Flow Q m3/h Remarks l/h Turbidity NTU FNU FTU FAU 171 Configure Unit / adjustable variables Increment Remarks EBC Conductivity μS/cm mS/cm S/cm UV W/m2 mW/cm2 Others mg/l For F-, O2, ClO2, ClO2 -, H2O2, PES ppm Adjustable varia‐ bles Decimal points Increment Value range for 0/4 mA 20 mA 0 0...9000 0...9999 1 0...900,0 0...999,9 2 0...90,00 0...99,99 3 0...9,000 0...9,999 Unit / adjustable variables Increment Remarks Value 0/4 mA 0...9999 for 0 decimal points 0...999,9 for 1 decimal points 0...99,99 for 2 decimal points 0...9,999 for 3 decimal points 0...9999 for 0 decimal points 0...999,9 for 1 decimal points 0...99,99 for 2 decimal points 0...9,999 for 3 decimal points Value 20 mA Configuration of measured variables The I module can be used to process signals from sensors or devices which supply an mA standard signal for the following measured variables: Measured variable Sensor or device Fluoride (F-) Transducer 4-20 mA FP V1 dissolved oxygen (O2) DULCOMETER® controller type D1C for dissolved oxygen Chlorine dioxide (ClO2 DULCOTEST® amperometric sensor Chlorite (ClO2 -) DULCOTEST® amperometric sensor Ammonia (NH3) Transducer 4-20 mA A V1 172 Configure Measured variable Sensor or device Hydrogen peroxide (H2O2) DULCOTEST® amperometric sensor Peracetic acid (PES) DULCOTEST® amperometric sensor Conductive conductivity DMT transducer Temperature Transducer 4-20 mA Pt 100 V1 Flow Suitable third-party device UV intensity (UV) Suitable third-party device Turbidity Suitable third-party device Displays and limit values The signals are displayed and can be monitored by means of limit values (PARAM - AL). Temperature compensation For fluoride you can select temperature compensation under PARAM - MESS. In order to do so, you have to connect a tempera‐ ture sensor to input ‘ I in 3’ . Configure All of the selectable measured variables are subdivided over 3 lines which can be selected by means of the arrow keys. The sen‐ sors for the measured variables in line 1 must be connected to ter‐ minal XE1, the sensors for the measured variables in row 2 must be connected to terminal XE2, etc. . Configuring a sensor or a device: 1. Select the correct line corresponding to the terminal (arrow key UP/DOWN; for KE1 - row 1, etc. ) and press the ENTER button ð A display appears for selecting the measured variables 2. Press the ENTER button 3. Select the correct measured variable and press the ENTER key 4. Accept the settings with F5 ACCEPT ð A progress bar appears. Default settings will now be loaded for the new measured variable. Possibly change certain parameters in the configuration: 5. Select under ‘Range’ the correct range for the standard signal 6. Select the next parameter block with the RIGHT key 7. Select under ‘Unit’ the correct unit 8. Select under ‘Decimal points’ the desired number of decimal places after the decimal point that should be displayed. 9. Select the next parameter block with the RIGHT key 10. Under ‘0/4 mA’ set the correct zero point for the measured variable. 11. Under ‘20 mA’ set the correct maximum value for the meas‐ ured variable. 12. Store all of the settings with F5 SAVE 13. Press the enter button in the following dialog for ‘Yes’ 173 Configure 14. Check whether there are still parameters in the PARAM menu that have to be matched up, such as alarms or tem‐ perature compensation. ð You must now calibrate the new measured variable. Editing the names of the mA inputs System XE2 123 +24V IN GND Input 0/4-20 mA Measured variable: Measured variable name: Unit name: EDIT 1111 xyz Edit the name of the measured variables and the unit! ACCEPT A0334 Fig. 107: Editing the names of the mA inputs The names of all three mA inputs as shown in the display can be edited. Unit / adjustable variables Increment Measured variable EDIT Remarks no sensor F- Fluoride (F-) O2 dissolved oxygen (O2) ClO2 Chlorine dioxide (ClO2 ClO2- Chlorite (ClO2 -) H2O2 Hydrogen peroxide (H2O2) NH3 Ammonia (NH3) Name measured variable freely editable to 4 places All numerals, letters and special characters are avail‐ able Name unit freely editable to 4 places All numerals, letters and special characters are avail‐ able 174 Maintenance 11 Maintenance Maintenance work DXCa Maintenance timer The DXCa is equipped with a maintenance timer. This timer serves to indicate pending maintenance tasks. In this case, the contact details of the authorised engi‐ neer are also displayed. INFO Maintenance timer reminder Maintenance due! Contact data: Company: Name: Landline: Mobile: Musterfrima GmbH & Co. KGaA Musti Mustermann +49 0 6221 XXXXXXX +49 0 177 XXXXXXX F1 Confirm service! ESC Remind again A0263 Fig. 108: INFO Maintenance timer reminder F1 Confirm service!: ESC remind again: 11.1 Confirms the service work carried out and reset the maintenance timer (password required) Suppresses the message. The message is dis‐ played again after one week. Configure maintenance timer PLOT WEB SRV Maintenance timer Company: Musterfirma GmbH & Co. KGaA Name: Musti Mustermann Landline: +49 0 6221 XXXXXXX Mobile: +49 0 177 XXXXXXX Interval: 12 months Last maintenance on 30.02.2009 0 Valid for the entire system. Sound off RESET RESTART A0262 Fig. 109: Configure maintenance timer Maintenance timer configuration 1. Press the F4 button (CONFIG) in the central menu item ð The configuration menu appears 175 Maintenance 2. Press the F2 key (OPTION) ð The options menu appears 3. Select the file card [SRV] with the horizontal arrow keys 4. Press the ENTER button 5. Enter the password [PW Installation] on ð The display with the configurable parameters appears. 6. Select the parameter which you want to change with the hori‐ zontal arrow keys. ð The selected parameter will be shown with a black back‐ ground. 7. Press the ENTER button SRV Maintenance timer Company: Name: Landline: Mobile: Interval: Musterfirma GmbH & Co. KGaA Musti Mustermann +49 0 6221 XXXXXXX +49 0 177 XXXXXXX 12 months Company: Musterfirma GmbH & Co. KGaA A0268 Fig. 110: Maintenance timer change display 8. The parameter to be changed appears at the bottom lefthand side 9. Adjust the parameter with the horizontal and vertical arrow keys ð Confirm the changes with the ENTER button 10. Repeat the process from point 6 until all of the respective parameters have been changed 11. Press F5 (SAVE) in order to save all of the changes 12. You can return to the central menu item by pressing the ESC key Adjustable variables Increment Remarks Interval Switches the main‐ tenance timer off Inactive 1 month 3 months 6 months 9 months 12 months 176 Troubleshooting 12 Troubleshooting The number shown before the error message on Dulco Net indicates the pool number (system number) of the respective pool (system). You can display the pH value, the sensor current and the temperature at the time of pressing the button with F4 (MESS). In the event that an error message is shown when cali‐ brating a chlorine sensor, you can call up detailed information with F3 INFO. This data will also help when discussing the matter with a technical consultant. Error messages central menu item and remedies Fault Messages Reaction DXCa and remedy Fault sample water Metering on basic load, measured values incorrect, check sample water flow pH sensor defective Metering on basic load, measured values incorrect, replace sensor pH value too low Metering on basic load, locate cause of fault, possibly switch over to manual metering pH–value too high Metering on basic load, locate cause of fault, possibly switch over to manual metering pH-input short circuited Metering on basic load, measured values incorrect, identify cause (incorrect connection) pH sensor not connected Metering on basic load, measured values incorrect, identify cause (incorrect connection Fault pump pH lower Check container, check pump, vent, measured value OK pH lower container empty Replace container, vent, measured value OK Fault pump pH-raise Check container, check pump, vent, measured value OK pH raise container empty Replace container, vent, measured value OK Redox sensor defective Measured values incorrect, metering on basic load (if redox control active) Redox value too low Measured values incorrect, metering on basic load (if redox control active) Redox value too high Measured values incorrect, metering on basic load (if redox control active) Redox input short circuited Measured values incorrect, metering on basic load (if redox control active) Redox sensor not connected Measured values incorrect, metering on basic load (if redox control active Free chlorine CLE - sensor faulty Measured value incorrect, replace sensor Free chlorine CLE - value too low Metering on basic load, locate cause of fault, possibly switch over to manual metering 177 Troubleshooting Fault Messages Reaction DXCa and remedy Free chlorine CLE - value too high Metering on basic load, locate cause of fault, possibly switch over to manual metering Free chlorine CLE - sensor not con‐ Connect sensor nected Free chlorine CLE - correction temp Metering on basic load, measured values incorrect, replace sensor missing Free chlorine CLE - correction value missing No pH-sensor, switch pH-correction to manual pH Fault chlorine pump Check container, check pump, vent, measured value OK Chlorine container empty Replace container, vent, measured value OK Total chlorine CTE - sensor faulty Measured value incorrect, replace sensor Bound chlorine - value too low Recalibrate the chlorine sensor Bound chlorine - value too high Fresh water supply required Total chlorine CTE - correction temp missing Measured value incorrect, replace sensor Total chlorine CTE - correction value pH missing No pH-sensor, switch pH-correction to manual Total chlorine CTE - sensor not connected Connect sensor Temperature - sensor defective Measured value incorrect, replace PT1000 (100) Temperature - value too low Identify cause Temperature - value too high Identify cause Temperature - input short circuited Metering incorrect, identify cause (incorrect connection) Temperature - sensor not con‐ nected Metering incorrect, identify cause (incorrect connection) Fault flocculent pump Check container, check pump, vent Flocculent container empty Replace container, vent DXMaM module bus error Contact customer service DXMaA module bus error Contact customer service DXMaP module bus error Contact customer service Free chlorine CLE - sensor bus error Contact customer service Total chlorine CLE - sensor bus error Contact customer service Pump MANUAL Manual is not allowed. Pump stopped (it will run again if discon‐ nected from bus) Pump STOP Manual is not allowed. Pump stopped Pump TEST Manual is not allowed. Pump runs Pump stroke length adjustment Stroke length adjusted >10 % Servo motor not ready Basic load? For further information see "Specific errors..." Ä ‘Specific 178 servomotor errors in file card "Operating errors"’ Table on page 179 Troubleshooting Error messages in the fields for measured variables and remedies Fault Messages Reaction DXCa and remedy Sensor fault Identify cause, replace sensor if necessary Calibrate sensor Calibrate sensor Rectify servo motor fault Write down the servo motor calibration data prior to calling ProMinent Service: In order to do so, in the file card ‘R module’ press the F1 key (HELP) - the table containing the calibrated values appears 1. In the event the the error message ‘ Servomotor: not ready’ appears in the permanent display, press the F4 key (FAULT) in the R module file card ð ‘Operating error’ appears. 2. Make a note of the specific error message for the servomotor 3. Rectify the fault in accordance with Ä ‘Specific servomotor errors in file card "Operating errors"’ Table on page 179 . 4. Press the F2 key (RESET) in order to exit the menu and acknowledge the fault. Specific servomotor errors in file card "Operating errors" Error message Cause Remedy Upper calibration point exceeded Upper camshaft switch has not triggered Check mechanism in chlorine gas metering unit Lower calibration point exceeded Lower camshaft switch has not triggered Check mechanism in chlorine gas metering unit Potentiometer not connected No positioning check-back signal to R module Check the wiring of the potentiom‐ eter in the chlorine gas metering unit and the wiring in the R module for correct connection Incorrect direction of rotation The servomotor direction of rota‐ tion does not correspond with the potentiometer direction of rotation Check the wiring of the potentiom‐ eter and the relay control in the chlorine gas metering unit and the wiring in the R module for correct connection Position not reached The servomotor has not achieved the calculated position Voltage feed interrupted, check wiring, excessive mechanism play Communication time-out The R module fails to answer within the specified period of time Check BUS-connection for M module Heartbeat time-out Module not correctly connected Check BUS cabling Lower stop too low Camshaft switch has not triggered Check mechanism, fasten cam Upper stop too high Camshaft switch has not triggered Check mechanism, fasten cam 179 Troubleshooting Error message Cause Remedy Calibration cycles unequal There are differences between the Check mechanism, replace cam if two calibration cycles necessary Motor too fast Potentiometer or mechanism jumps Replace potentiometer or mecha‐ nism Metering characteristics for various controller states metering STOP START Param‐ eter Sample water Menu Error Pause contact Sample water Display metering metering Actuating variable Remarks Error Control: OFF Controller 60 % X metering 0% for all measured variables of the dis‐ played pool 0% for a measured variable OFF X metering OFF X metering 0% OFF Error message X metering 0% Pause X metering 10% Manual man. metering 20 % X man. metering Basic load Configu‐ rable Config‐ ured value Configu‐ rable 0% for all measured variables of the dis‐ played pool 0% for a measured variable OFF X man. metering OFF 180 Troubleshooting metering STOP START Param‐ eter Sample water Menu Error Pause contact Sample water Display metering man. metering 0% Remarks Error Control: OFF X OFF Error message X X man. metering 0% man. metering Config‐ ured value Configu‐ rable Left LED (device LED) Colour Flash code Cause Consequence Remedy red illuminated any Warning or acknowl‐ edged fault mes‐ sages For troubleshooting see Ä ‘Error mes‐ sages central menu item and rem‐ edies’ Table on page 177 red flashing unacknowledged error message Alarm Acknowledge alarm, rectify fault green illuminated No device error pending Normal Mode - DXCa Right LED (CANopen LED) Colour Flash code Cause Consequence Remedy green illuminated Bus status Normal bus mode - OPERATIONAL green flashing Bus status PRE-OPERA‐ TIONAL currently no meas‐ Wait briefly ured value communi‐ cation Ignore the flash codes for approx. 2 minutes after connecting the DXCa. Acknowledge possibly occurring alarms. If the LEDs keep repeating the same sequence of flash codes, then the bus must be supplying too many devices. In this case, add an (additional) N or P module into the bus (see part 1 of the oper‐ ating instructions). Contact customer service in the event of all other flash codes. 181 Troubleshooting Flash code LEDs DXCa (central unit DXCa) Left LED (device LED) Colour Flash code Cause Consequence Remedy red illuminated Electronic fault Sensor defective Return the sensor or contact customer service red flashing* Start-up phase no measured value communication Wait briefly red Single flashing** Calibration is faulty Measured value is incorrect Re-calibrate red Double flashing*** 0 ppm > measured value Measured value too high / too low Check the chlorine content of the sample water Limit value transgres‐ sion Clarify cause; poss. set new values > 10 ppm Reading ≠ limit value No pH correction value pH correction value transferred missing Check parameters and configuration. Check pH sensor green illuminated No device error pending Normal mode sensor - - off No supply voltage Sensor not func‐ tioning Check cable con‐ nections * ** *** A0203 Fig. 111: Flash code Flash code LEDs DXCa (central unit DXCa) Right LED (CANopen LED) Colour Flash code Cause Consequence Remedy red any Bus-error no measured value communication Contact customer service green illuminated Bus status Normal bus mode - Currently no meas‐ ured value communi‐ cation Bus-error OPERATIONAL green flashing Bus status PRE-OPERATIONAL Ignore the flash codes for approx. 2 minutes after connecting the sensor. Acknowledge possibly occurring alarms. If the LEDs keep repeating the same sequence of flash codes, then the bus must be supplying too many devices. In this case, add an (additional) N or P module into the bus (see part 1 of the oper‐ ating instructions). Contact customer service in the event of all other flash codes. 182 Troubleshooting LEDs on the power supply module The two LEDS (LED 1 and LED 2) (see power supply module sup‐ plementary instructions) indicate the load of the 24V power supply for the CAN bus. Flash code LEDs power supply monitoring DXCa (N and P module) Mode LED 1 LED 2 (H2, power) (H3, power) Normal off Limit load red Overload / short cir‐ red, flashing cuit Power Remarks green < 1.1 A All OK off > 1.1 A Insert another power supply module into the loop off > 1.35 A Check wiring 183 Glossary of technical terms 13 Glossary of technical terms Abbreviations for control-relevant values: x: Control variable, actual value e.g. pH value) KPR: Proportional coefficient xp: 100 %/KPR (reciprocal proportional coefficient) Xmax: Maximum actual value of control (e.g. pH 14) y: Actuating variable (e.g. pulse frequency - pump) Yh: Actuating range (e.g. 180 pulses/min) yp: Actuating variable of proportional controller [%] w: Primary variable or set point (e.g. pH 7.2) e: Control difference, e = w-x xw: Control deviation, xw = x-w TN: Reset time of I-control [s] TV: Derivative time of D-control [s] Access code (password) Access to the device can be granted in steps by setting up an access code. Refer also to: Ä Chapter 5.2 ‘Access code (password)’ on page 70 Actuating variable An actuating variable is considered to be the value (e.g. fre‐ quency, mA signal) that the controller emits to the actuator e.g. a metering pump in order to achieve the set point again (at actuating variable 100% a pump will run at full power). Additive interference variable The additive interference variable switch is suitable for metering tasks, in which the metering volume is dependent in the first place on the interference variable (e.g. flow) and requires only minimal recorrection. This nature of interfer‐ ence variable processing is used, for example, in the chlori‐ nation of water with approximately constant chlorine uptake. An interference value-related base load metering value will be added or subtracted from the first "determined actuating variable" from the controller. The actuating variable can be a maximum of 100 %. Actuating variable to actuator [%] = (recorded actuating vari‐ able [%] +max. additive actuating variable [%]*current inter‐ ference variable [mA]) / nominal interference variable [mA] Legends: The maximum additive interference variable indi‐ cates which maximum interference variable is to be added (where current interference variable = nominal interference variable). For further legends see ‘multiplicative interference value’ . CAUTION: If there is no current interference variable (flow = 0), but a recorded actuating variable of the PID control, then the final actuating variable corresponds to the recorded actuating variable of the PID control. If a current interference variable (flow = 0) is given and the detected interference value of the PID controller is the same ‘0’ , then the final actuating variable will correspond to the 2nd term from the above formula: (max. additive actuating variable * current interference variable) / nominal interference variable Calibration Transducers require calibration (alignment of the zero point and slope). For 1-point calibration, this is undertaken with a buffer solu‐ tion pH 7. I.e. only the zero point is calibrated in this case. 184 Glossary of technical terms For 2-point calibration it is necessary to select a second value in order to calibrate the slope: e.g. pH 4 or pH 10. The second value is dependent on the actual measurement range (alkali or acid). In swimming pool technology it is sufficient to carry out a zero point calibration (at pH 7) and merely to check the sensor function with a buffer solution at pH 4 or pH 10. As the measurement is undertaken around the zero point, mod‐ erate errors in the slope are immaterial The slope of the sensor can change as a result of aging and soiling. checkout time CAUTION: The function ‘checkout time control’ can be con‐ fused with ‘Control time of reading’ on the DULCOMETER® D1C! The function ‘checkout time control’ offers a protection option against the risk of over-metering. It switches the respective control circuit to metering 0% after expiration of the checkout time and triggers an error message if: On a pure P control: the P proportion of the actuating vari‐ able is greater than 40%. for PID control: the PID actuating variable Y is greater than 90%. Press the start / stop button twice in order to restart the respective control circuit and to delete the error message for the control circuit. Control equations: Normal A measured value is compared with a set point. In the event of a control difference (difference of set point minus actual value), an actuating value is determined which will counter the control difference. Controller The DXCa controller be used as a P-, PI-, or PID-controller. This depends on the settings of the control parameters. The actuating variable is calculated once per second. This controller cannot be used in control circuits that require quicker reactions to control deviations (less than 30 sec‐ onds). The control function (output of actuating variables) can be switched off by means of the Pause control input. Actuating variable calculation is resumed as soon as Pause is ceased. Control variable (measured value, actual value) The control variable is the variable which is to be measured and recorded (e.g. pH value, redox value). Delay (alarm limits) In the event that the alarm threshold is violated, the DXCa will trigger an error message only after the configured delay set here. This means that brief alarm threshold violations will not trigger an error message. Delay (contact) As soon as a contact is connected to a contact input K of the M module, the DXCa sets the actuating outputs to ‘0’ for as long as the contact is made and for a subsequent delay period (contact) (if it has been configured). While the contact is made, the DXCa suppresses error treatment. As soon as the contact is opened, the DXCa commences with error treatment again - after the delay period has expired (contact) (if it has been configured). Once the contact has been opened, the actuating outputs remain - for the duration of the delay (contact) - at ‘0’ . The delay (contact) has to be set in 185 Glossary of technical terms such a way that, for example, during this time sample water with the current concentration relative to the process flows to the sensor. The delay (contact) from "pause control" has a higher priority that the delay (contact) from ‘ Sampling water’ . The 0/4-20 mA outputs (standard signal outputs) for the reading or correction value are unaffected by this func‐ tion. Delay (error) In the event of a limit value violation, the limit value relay of the G module will trip after the delay period entered here has elapsed. This means that brief limit value violations will not trigger an error message. Determining the checkout time Prerequisites: The system has achieved the set points for chlorine concen‐ tration (0.45 mg/l) and pH value. Stop the system using the Start/Stop key. Wait until the chlorine concentration has dropped to 0.1 mg/l. Restart the controller using the Start/Stop key. Measure the time needed until the set point has been ach‐ ieved. Enter this time multiplied by 1.5 as the checkout time for chlorine concentration. If the pump capacities are correctly selected, then this checkout time can also be entered for the pH value. Eco!Mode ‘Eco!Mode’ enables a 2nd set of parameters to be tempora‐ rily activated in order to save power. This can, for example, be carried out synchronously with a reduction in the circu‐ lating output. As soon as a contact is switched on contact input K3 of the M module, ‘Eco!Mode’ is activated or deacti‐ vated. Eco!Mode is available for all M module measured var‐ iables, if they are controlled: pH Redox chlorine free chlorine bound Temperature Flocculent As soon as the 2nd set of parameters is activated, the cen‐ tral menu item indicates a green ECO identifier. Interference value The controller can process a signal from a flow measure‐ ment on the analogue input ‘I in 1’ of the DXMaI module as an interference value for the controlled measured variables of the I module. This interference value influences the actuating variables calculated by the controller in relation to the external signal. Depending on the nature of the effect on the actuating vari‐ able, it is referred to either as a multiplicative interference variable (flow-proportional effect) or an additive interference variable (interference variable-related effect) When ‘Commissioning’ the zero point signal of the flow gauge has to be checked without flow (must be ≥ 0). 186 Glossary of technical terms Limit values ‘min. limit’ means that the limit criterion has been trans‐ gressed by dropping below the lower limit ‘max. limit’ means that the limit criterion has been trans‐ gressed by exceeding the upper limit Multiplicative interference variable This type of interference variable processing is used, for example, with flow neutralisation. The actuating variables determined by the controller are multiplied by a factor F. The factor lies in the range of 0 ≤ F ≤ 1 (0 ~= 0 %, 1 ~= 100 %). The actuating variable can therefore be a maximum of 100 %. Actuating variable to actuator [%] = recorded actuating variable [%] * current inter‐ ference variable [mA] / nominal interference variable [mA] A ‘current interference variable’ greater than or equal to the ‘Interference variable nominal value’ does not affect the control variable. Legends: The determined actuating variable is the actuating variable which is issued by the controller without an interfer‐ ence value. The nominal interference variable limits the range that can be used. Example: A flow meter is used, for example, which can measure a maximum flow of Q = 250 m3/h. The analogue output of the flow meter supplies a signal corresponding to 4 mA = 0 m3/h, 20 mA = 250 m3/h. The maximum flow that can be achieved in the application is however only 125 m3/h. If the standard signal-output signal of the flow meter is now not adjusted to the 4...20 mA range of the D1C (possible with the majority of flow meters), then the standard signal at 125 m3/h is only12 mA. Is this value then to be entered into the ‘interference value menu?’ Enter under ‘Interference variable nominal value’ . The interference variable is the current analogue flow, which the flow meter supplies. The final actuating variable is trans‐ ferred to the actuator. The multiplicative interference value is not designed to per‐ manently switch off the actuating variable! In this case you should realise deactivation via the pause function. Pause When the Pause contact is closed, the DXCa sets all actuating outputs to ‘0’ for as long as the pause contact is closed. While the Pause contact is closed, the DXC records the P-proportion in the background. pH value pH-value refers to a measurement for the concentration (activity) of hydrogen ions or, put simply, is a measurement for the acidity or alkalinity of water. The pH value is of great importance in terms of swimming pool water treatment. It influences: the degree of disinfection: the disinfection effect of chlorine reduces as the pH value rises the flocculent: every flocculent has only a certain pH range in which it is able to work optimally the corrosiveness: the corrosiveness of the water increases as the pH value drops. Mechanical materials will corrode The skin tolerance: The acidic protection layer of our skin is pH 5.5. Excessive pH values in the swimming pool water attack the protective layers of skin and this leads to skin irri‐ tation. 187 Glossary of technical terms An excessively low pH value increases the likelihood of trichloramine formation. This can lead to eye irritation (inflamed, stringing eyes) and mucous membrane irritation (e.g. coughing). For these reasons, the pH value of swim‐ ming pool water should always be in the range between 6.5 and 7.6 (optimal: pH-optimum of the flocculent used). In pri‐ vate swimming pools, where generally no flocculants are uses, the pH value should lie between 7 and 7.2. On the other hand, the pH measurement is influenced by the following factors: chlorination: all chlorine products will change the pH value the water distribution: carbon dioxide (CO2) outgassing from the pool water will raise the pH value. This effect can be amplified by an unfavourable water distribution or by aera‐ tors, fungi or similar. For these reasons, the pH value must be constantly meas‐ ured and controlled. Redox voltage The redox voltage is dependent on the sum total of reductive and oxidising substances contained in the water. It repre‐ sents a measurement for the disinfecting efficiency of the water. The higher the concentration of oxidising substances, the greater the redox voltage (oxidation = disinfection). In a swimming pool, hypochlorous acid is the determining oxidising substance. Contaminating substances are mini‐ mised. pH-value and temperature have the following influences on the redox value: Increasing pH-value--> decreasing redox voltage Increasing temperature--> increasing redox voltage A stable pH value is extremely important! There is no unequivocal relationship between disinfectant concentration and redox voltage. At a redox voltage of 750 mV it is assured that introduced microorganisms are destroyed or made inactive in a matter of seconds. At values lower than 600 mV the disinfection period can amount to minutes or hours. Set point Set point refers to a value which is to be maintained at a constant level by means of the controllers in a process. Slope / sensitivity This value is, for example, given in mV/pH at 25 °C. Types of controller: P controller: Is used in controlled systems which work in an integrated manner (e.g. batch neutralisation). PI controller: Can be used in non-integrated controlled systems (e.g. flow neutralisation). PID controller: Is used in controlled systems where peaks occur that have to be compensated for. With dead zone: With dead zone control (neutral zone control) two set points have to be specified. If the reading is located within the dead zone, then no control variable will be issued. Set point 2 must be greater than set point 1! 188 Glossary of technical terms Manual ATTENTION: The controller will not exit this mode automati‐ cally. Manual mode may only be used for commissioning and for test purposes. There is no control. An actuating variable will be specified manually: Actuating variable: 0...+100 % (actuating output rise active) Actuating variable: -100...0 % (actuating output lower active) This function is used to monitor actuators. Additive basic load: A basic load is added to the current actuating variable. The additive basic load means that, for example, constant attri‐ tion can be compensated for. YTot = Yp + 15 % (additive basic load = 15 %) Example 1 (one-way control): YTot = 85 % + 15 %; YTot = 100 % Example 2 (one-way control): YTot = -75 % + 15 %; YTot = -60 % xp value This value influences the proportional control behaviour. For example, an xp of 1.4 pH with a deviation of +1.4 pH leads to an actuating variable of -100% or at a deviation of -1.4 pH to an actuating variable of +100%. In other words, if a devia‐ tion occurs to the size of xp, then an actuating variable of 100% follows. Zero point This refers to, for example, the voltage that a pH sensor emits at pH value 7. The zero point of the sensor can change as a result of aging and soiling. The zero point of pH sensors is theoretically 0 mV. In prac‐ tical terms, a zero point between -30 mV and +30 mV is acceptable for good sensor operation. New sensors have a zero point tolerance of max. ±30 mV. 189 Glossary of technical terms 190 Index 14 Index " "Calibrate" pump.................................................. 75 A Access code level................................................ 71 Access to the submenus...................................... 87 Actuating outputs to "0"........................................ 88 Adding a new module........................................... 72 Areas protected by access codes........................ 71 Arrow key DOWN................................................. 69 Arrow key UP....................................................... 69 Assign a pump number.................................. 75, 76 Assign a pump to a system (pool, filtration cir‐ cuit, etc.)......................................................... 75, 76 Assign the pump a purpose................................. 76 B Blue chevron........................................................ 80 Buffer detection.................................................... 92 Buffer solution................................................ 90, 92 Buffer solutions ................................................... 89 Buttons and displays............................................ 68 C Calibrate pump .................................................... 76 Calibrate R module.............................................. 78 Calibration menu.................................................. 79 Calibration menu for all measured variables........ 85 Call up help function............................................. 86 CANopen.............................................................. 67 Central menu item................................................ 79 Changing numerical values.................................. 69 Changing the language........................................ 71 Commissioning a pump........................................ 76 Commissioning a stored CAN-Beta pump........... 76 Commissioning CAN-Beta pump................... 74, 76 Configuration menu.............................................. 79 Configuration menu, first menu item.................... 86 Configuring the CAN modules.............................. 72 Control panel........................................................ 67 D Data logger........................................................... 67 Displays and buttons............................................ 68 DOWN key........................................................... 69 DULCO-Net........................................................ 177 E Editing the names of the mA inputs................... 174 ENTER button...................................................... 68 Equipotential bonding pin..................................... 90 ESC button........................................................... 68 eventlog.txt........................................................... 81 F F1 (Help).............................................................. 88 F2 (CAL)............................................................... 88 F4 (CAL1Pt)......................................................... 90 F4 (GLOBAL)....................................................... 80 F5 (ARCHIVE)...................................................... 81 F5 Function key.................................................... 71 Fault Messages.................................................... 81 I Insert a module which has been temporarily disconnected........................................................ 74 L LAN/Ethernet ....................................................... 67 LEFT key.............................................................. 69 LSS nodes............................................................ 72 M mA input editing................................................. 174 Maximum number of mA sensors per system / pool...................................................................... 67 Maximum number of systems / pools................... 67 Measured variable colour..................................... 80 Metering OFF....................................................... 70 Metering ON......................................................... 70 Module logged off................................................. 74 Module re-registered............................................ 74 O OPC server.......................................................... 67 Opening angle of the chloric gas metering unit valve..................................................................... 78 P Parametric assignment menu.............................. 79 Parametric assignment menu, first menu item..... 85 Password............................................................. 70 Permanently disconnect a module....................... 74 Plug & Play principle............................................ 67 Pool number....................................................... 177 R Red chevron......................................................... 80 Replacing access codes...................................... 70 RIGHT key........................................................... 69 S Safety information................................................ 62 SAVE.................................................................... 69 Save CAN configuration....................................... 75 SD card................................................................ 81 Shut off chloric gas metering................................ 77 Software update................................................... 72 191 Index START/STOP key................................................ 70 Submenu access.................................................. 87 Summer time switchover...................................... 87 Switchover to summer time.................................. 87 T Temporarily disconnect a module........................ 73 To change the name of the system...................... 75 192 U Updating software................................................ UP key.................................................................. Users' qualifications............................................. V Virtual pools......................................................... 72 69 63 81 Operating instructions DULCOMARIN® II, Screen Plotter Operation A0469 Please carefully read these operating instructions before use! · Do not discard! The operator shall be liable for any damage caused by installation or operating errors! Technical changes reserved. Part no. 986790 BA DC 068 02/11 EN ProMinent Dosiertechnik GmbH Im Schuhmachergewann 5-11 69123 Heidelberg Telephone: +49 6221 842-0 Fax: +49 6221 842-419 email: [email protected] Internet: www.prominent.com 986790, 1, en_GB © 2011 194 Supplemental instructions Further applicable documents These operating instructions and supplementary instructions are only valid in combination with the following operating and supple‐ mentary instructions: n Multi-channel measuring and control system operating instruc‐ tions DULCOMARIN® II Swimming Pool Controller and Disin‐ fection Controller DXCa Part 2: Operation n Supplementary instructions DULCOMARIN® II M-module product type: DXMaM (measurement module for pH, redox, temperature) n Supplementary instructions DULCOMARIN® II I-module product type: DXMaI (current input module, standard signal inputs mA) 195 Supplemental instructions 196 Table of contents Table of contents 1 About this product............................................................. 198 1.1 Storage and transport............................................... 198 2 Setting up the screen plotter............................................. 199 3 Layout and function of the screen plotter.......................... 201 4 Using an SD card.............................................................. 203 5 Troubleshooting................................................................ 206 6 Technical data and accessories........................................ 207 197 About this product 1 About this product The screen plotter for the swimming pool controller DULCO‐ MARIN® II is a software solution, which makes an expensive addi‐ tional device superfluous. It is designed as a 16-times 2 x 5 channel plotter. It displays the measured values for pH value, redox value, free Cl and combined Cl and the temperature, as well as the corresponding control variables (not for temperature), and this for up to 16 pools. Without an SD-card it can save measure‐ ment results for 24 h, with an SD-card it can save measurement results from 35 days up to 12 years, dependent on requirements. Single TXT files from the SD card can be copied to a PC and, for example, processed with EXCEL to create graphics. 1.1 Storage and transport CAUTION! – Store and transport the card reader and the SD card in their original packaging – Protect the entire DXCa update kit against mois‐ ture and the effects of chemicals. The scope of supply of the DXCa update kit comprises: n SD card n Card reader Ambient conditions for storage and transportation n Temperature: 0 °C ... 45 °C n Air humidity: 10 % ... 90 % relative air humidity, non-con‐ densing 198 Setting up the screen plotter 2 Setting up the screen plotter Boot-up routines Only after the DULCOMARIN® II has completed the boot-up routine (duration approximately 4 minutes), does the screen plotter start to operate. PLOT Plotting settings Plotting : HELP inactive ToneOff SAVE A0470 Fig. 1: The file card [PLOT] with inactive screen plotter If the symbol for the screen plotter at the extreme left in the central menu item is not available, it is necessary to proceed as follows: 1. Press the [F4 CONFIG] key in the central menu item 2. Press the [F2 OPTION] key in the configure menu 3. In the file card [PLOT] press the [ENTER] key (if necessary, enter the access code) 4. Using the arrow keys [UP] or [DOWN] select ‘active’ and press the [ENTER] key 5. Press the function key [F5 SAVE] 6. Press the [ESC ]key to jump back to the central menu item 199 Setting up the screen plotter Adjusting the interface of the screen plotter PLOT Plotting settings Plotting : Pen width= Grid lines: HELP active 1 pixel turned on SAVE ToneOff A0471 Fig. 2: The file card [PLOT] with inactive screen plotter Viewing the charts 1. Press the [F4 CONFIG] key in the central menu item 2. Press the [F2 OPTION] key in the configure menu 3. In the file card [PLOT] select either ‘Line thickness ’ or ‘Grid lines’ (arrow keys) (if necessary, enter the access code) 4. Press the [ENTER] key 5. Using the arrow keys [UP] and [DOWN] make the required selection and then press the [ENTER] key 6. Press the function key [F5 SAVE] 7. Press the [ESC ]key to jump back to the central menu item Pool Children's pool Set Dosage: Dosage: OFF ORP Cl free Set Cl comb Switch Chlorine sensor Temp ORP HELP CAL Value too low PARAM CONFIG LIST A0472 Fig. 3: The central menu item with active screen plotter In the central menu item, press the arrow keys [UP] or [DOWN] ð The charts for pH-value appear first. 200 Layout and function of the screen plotter 3 Layout and function of the screen plotter A0473 Fig. 4: Plotter window layout The screen plotter comprises: n n n n n n Name of the measured variable Pool number and pool name (with more than one pool) Chart for the measured variable Chart for the control variable of the measured variable Information line for the selected measured value Bar with function keys Name of the measured variable Select the measured variable with the arrow keys [UP] and [DOWN]. Pool number and pool name Select the pool with the arrow keys [LEFT] and [RIGHT]. Measured variable chart The measured variable chart shows the y-axis and units on the extreme left. The time axis (x-axis) is located between the meas‐ ured variable chart and the control variable chart. It always shows 24 hours. It only shows hour times where there are measured values. Otherwise it shows ‘00:00’ . The red lines indicate the set limit values (in the parameter menu: Parameter Alarm). If the measured values exceed the limit values, the measurement curve appears red in this position. The blue line is a cursor, with which individual measured values can be approached, so that their precise value can be read off (see under ‘Info line for the selected measured value’ and ‘Bar with function keys’ ). Initially it is positioned exactly on the y-axis. Chart for the control variable of the measured variable The chart for the control variable of the measured variable shows the y-axis on the extreme left with ‘%’ units. The time axis (x-axis) is located between the chart for the measured variable and the chart for the control variable. It always shows 24 hours. 201 Layout and function of the screen plotter Information line for the selected measured value The information line for the selected measured value shows its pre‐ cise value. You select a measured value using the cursor (see under ‘Bar with function keys’ ). The sequence of displayed values is: n n n n n n Bar with function keys No. of the measured value Measured value Control variable value Date of the measurement Time of the measurement (Display number) Normal view If the plotter takes the next measured value, the view jumps back to the normal view (after no more than 5 minutes). Each change to another display resets the view to the normal view. Using the function key [ARCHIVE] you can check historical meas‐ ured values on the DULCOMARIN® II (values going back up to a week). For this, you require an SD card. The function key bar con‐ tains the [ARCHIVE] function key as well as the function key pairs [F2 ZOOM- ]/ [F3 ZOOM+] and[ F4 <CURSOR ]/ F5 CURSOR>: The function key pair [F2 ZOOM-] / [F3 ZOOM+] is used to zoom the y-axis for the measured variable. The function key pair [F4 <CURSOR] / [F5 CURSOR>] is used to move the blue cursor in the measured variable chart (it may pos‐ sibly initially be located on the y-axis). More information The time interval over which the DULCOMARIN® II plots the meas‐ ured values is 5 minutes. If the measurement curve has reached the chart width, then for each new value on the right, an old value disappears on the left. The DULCOMARIN® II saves the measured values for the current day. The DULCOMARIN® II saves the measured values of the last day from 00:00 to 24:00 h as a file for each measured variable and for each pool. If an SD card is inserted, then the DULCOMARIN® II saves these files on the SD card until it is full. Using the function key [ARCHIVE] you can check historical meas‐ ured values on the DULCOMARIN® II, for periods going back up to a week. In the archive you can use the function keys [<< ]and [>>] to jump from day to day. The display shows the numbers of the days in the top right corner. 202 Using an SD card 4 Using an SD card NOTICE! Before expiry of the number of maximum savable days you must replace the full SD card for an empty SD card. Otherwise, the data for further days are lost, as the DULCOMARIN® II cannot delete the data on the SD card. Requirement A PC with at least WIN98 and a USB port. If the measured values of the plotter are to be saved for longer than 24 h, you must use an SD card. The screen plotter shows the measured values for the last 24 h. You can call up older measured values using the [ARCHIVE] function key or load them on a PC The required memory capacity depends on the number of days and pools. Memory capacity 32 MB 64 MB 128 MB 256 MB Number of pools days days days days 1 564 1128 2256 4512 2 282 564 1128 2256 3 188 376 752 1504 4 141 282 564 1128 5 112 224 448 896 6 94 188 376 752 7 80 160 320 640 8 70 140 280 560 9 62 124 248 496 10 56 112 224 448 11 51 102 204 408 12 47 94 188 376 13 43 86 172 344 14 40 80 160 320 15 37 74 148 296 16 35 70 140 280 SD card format: FAT 16 or FAT 32 File name format: JJMMDDBB.txt where JJ = year, MM = month, DD = day, B or BB = pool number 203 Using an SD card SD card insertion A0474 Fig. 5: The interfaces with the interface cover of the DXCa shown open 1. Card slot 2. SD card 3. Interface cover 1. 2. To insert the SD card, open the transparent interface cover (3) at the bottom of the DXC housing of the DULCOMARIN® II (shown Fig. 5 opened) If you want to change one SD card for another, then you must without fail carry out a reset prior to the insertion. If you forget to carry our a reset prior to the inser‐ tion, you must completely delete the SD card contents and then carry out the reset. Sequentially press: [F4 CONFIG], [F2 OPTION] and [F3 RESET]. 3. If the DULCOMARIN® II has already saved data, then it copies the files of the last day and the measured values of the current day upon recording of the next measured value to the SD card (waiting time up to 5 min) - the identifier ‘SD’ appears, highlighted in red ð Do not pull out the SD card! 204 Using an SD card Protection class IP 65 The transparent interface cover (3) in Fig. 5 must be screwed in place again so that it is moisture-proof. Otherwise the IP 65 rating is not achieved. Evaluation of the SD card files 1. To remove the SD card open the transparent interface cover (3) at the bottom of the DXC housing of the DULCOMARIN® II (shown Fig. 5 opened) 2. Only pull out the SD card (2) from the card slot (1), if the identifier ‘SD’ , at the top right on the LCD screen is high‐ lighted in green. Not when it is highlighted in red! The plotter is then saving data. In this case wait briefly. ð Once you have pulled out the SD card, the identifier ‘SD’ at the top right of the LCD screen disappears. Moreover the error message ‘! Please insert SD card !!’ appears in the continuous display and in the central menu item. 3. Copy the files contained in the SD card to a PC via a card reader and then delete the the SD card contents. 4. Push the SD card (2) into the card slot (1) until it engages ð Then at the top right on the LCD screen, the ‘SD’ identi‐ fier appears highlighted in green. Moreover, the error message ‘! Please insert SD card !’ disappears. To protect the data, the DULCOMARIN® II saves the files with ‘write protection’ . When working, only use copies and clear the file write-protection on the PC under ‘Properties’ . If you have changed the clock of the DULCOMARIN® II from or to summer time, bear this in mind during data evaluation. 205 Troubleshooting 5 Troubleshooting Fault message Cause Remedy ! Please insert SD card!! Plotter is activated, but no SD card is inserted Insert SD card ! SD card unformatted!! SD card formatting is not FAT 16 or FAT 32 Format SD card using FAT 16 or FAT 32 This will delete all files on the SD card! ! SD card write-protected!! The slider on the side of the SD card is set to ‘LOCK’ Push the slider on the side of the SD card away from ‘LOCK’ ! SD card full. Please replace!! SD card is full After changing the SD card, the values directly after 24:00 hours are missing on the measurement curves 206 Copy all files from the SD card to the PC and delete the card con‐ tents Before changing the SD card, no reset Carry out a reset. Press the fol‐ was carried out lowing sequentially:[ F4 CONFIG], [F2 OPTION] and [F3 RESET] Technical data and accessories 6 Technical data and accessories Technical data Potter type: 16-times 2x5-channel plotter (16 pools, measured vari‐ able and control variable, 5 measured variables) Ambient conditions for storage and transportation: Update kit DXCa n Temperature: 0 °C ... 45 °C n Air humidity: 10 % ... 90 % relative air humidity, non-con‐ densing Ambient conditions for operation: Card reader n Temperature: 0 °C ... 45 °C n Air humidity: 20 % ... 85 % relative air humidity, non-con‐ densing Ambient conditions for operation: SD card n Temperature: -25 °C ... 85 °C Accessories Accessories Part number Update-Kit DXCa (in scope of supply), comprising SD card and card reader 1025885 SD memory card 64 MB or greater 732483 207 Technical data and accessories 208 Assembly and operating instructions DULCOMARIN® II, A-Module (Control Module, Pump and Standard Signal Out‐ puts mA) DXMaA Please enter the identity code of your device here! DXMa _ _ _ _ _ _ _ _ _ _ _ _ _ Please carefully read these operating instructions before use! · Do not discard! The operator shall be liable for any damage caused by installation or operating errors! Technical changes reserved. Part no. 986906 BA DC 069 02/11 EN ProMinent Dosiertechnik GmbH Im Schuhmachergewann 5 - 11 69123 Heidelberg Telephone: +49 6221 842-0 Fax: +49 6221 842-419 email: [email protected] Internet: www.prominent.com 986906, 1, en_GB © 2011 210 Supplemental instructions Further applicable documents These operating instructions and supplementary instructions are only valid in combination with the following operating and supple‐ mentary instructions: n Multi-channel measuring and control system operating instruc‐ tions DULCOMARIN® II Swimming Pool Controller and Disin‐ fection Controller DXCa Part 1: Assembly and installation n Multi-channel measuring and control system operating instruc‐ tions DULCOMARIN® II Swimming Pool Controller and Disin‐ fection Controller DXCa Part 2: Operation 211 Supplemental instructions 212 Table of contents Table of contents 1 Identity code...................................................................... 214 2 About this device............................................................... 216 2.1 Safety chapter........................................................... 216 2.2 Storage and transport............................................... 216 3 Assembly and installation................................................. 217 4 Technical data................................................................... 220 213 Identity code 1 Identity code The identity code describes the external modules for the DULCOMARIN® II, series DXM Only the M module of mounting type ‘W’ ‘Wall mounting’ can be ordered with operating elements and with different languages. DXMa External modules for the DULCOMARIN® II, series DXM Module: M M module, measuring module: pH, redox, temperature A A module, control module: 3 pumps and 4 analog outputs R R module, control module: Chlorine gas metering device with feedback 1) 2) N N module, power supply module without relay 1) 2) P P module, power supply module without relay, only mounting type ‘0)’ I I module, current input module, 3 mA inputs, 2 digital inputs 2) Mounting type: 0 Without housing, only P-module (IP 00) W Wall mounted (IP 65) H Mounting rail (IP 20) E Upgrade module (insert module for DXCa, IP 20) Version: 0 With controls 2 Without controls 3 Without controls (only mounting type ‘E’ ) Application: 0 Standard S Swimming pool (only m module) Language: 00 No controls 2) DE German EN English ES Spanish FR French IT Italian Certification: 214 00 No certification, only P-module without housing 01 CE mark Identity code only mounting type W wall mounting / 2) only in version ‘2’ without controls 1) 215 About this device 2 About this device The control module DXMaA allows the DULCOMARIN® II to control 3 metering pumps by pulse frequency, e.g. to increase or lower the pH value or to meter disinfectant. The DXMaA control module has the following outputs: n Four standard signal outputs 0/4...20 mA, freely programmable and scalable for measured values, e.g. of pH value, redox voltage, the concentration of free chlorine or total chlorine or combined chlorine or temperature. n Three frequency outputs for controlling metering pumps e.g. to increase or lower the pH value or to meter disinfectant and the following inputs: n Three contact inputs for evaluating the fault indicating relay of the metering pumps and monitoring the container fill level 2.1 Safety chapter The DXMaA control module must only be used as part of the DULCOMARIN® II. The installation must only be carried out by technically trained per‐ sonnel. 2.2 Storage and transport CAUTION! Protect the module against moisture and the effects of chemicals, even while still packaged. Store and transport the module it its original packaging. Ambient conditions for storage and transportation: n Temperature: -10 °C ... 70 °C n Max. permissible relative humidity: 95 %, non-condensing (DIN IEC 60068-2-30) 216 Assembly and installation 3 Assembly and installation NOTICE! The installation must only be carried out by technically trained personnel. When assembling and installing this device, observe the instructions in the operating instructions "Multichannel measuring and control system DULCOMARIN® II Swimming Pool Controller and Dis‐ infection Controller DXCa Part 1: Assembly and instal‐ lation". Incorrect measured values The standard signals can be falsified, possibly with consequences for the process. You may only directly connect devices with autono‐ mous galvanic isolation of the individual standard signal inputs to the standard signal outputs (e.g. the standard signal inputs of a plotter,...)! If you want to connect a multi-channel standard signal input module of a PLC to several standard signal out‐ puts of the DXMaA module, then you must route each standard signal wire via a 3-way standard signal iso‐ lator. A 3-way standard signal isolator galvanically iso‐ lates the input, the output and the supply voltage from each other. Where there are several standard signal wires, a multichannel isolating amplifier can be used. ProMinent rec‐ ommends 4-channel isolating amplifiers of type LCTV-4I.4I as supplied by Rinck www.rinck-electronic.de or of type 6185D supplied by PR Electronics www.prelectronics.de for the connection of up to 4 standard signal wires. Make the CAN connection according to the "Multi-channel meas‐ uring and control system operating instructions DULCOMARIN® II Swimming Pool Controller and Disinfection Controller DXCa Part 1, Assembly and Installation". 217 Assembly and installation A0476 Fig. 1: Terminal Wiring Diagram I. Small voltage relay outputs II. Contact inputs DXMa A III. Standard signal outputs 0/4 - 20 mA Terminal allocation Description Terminal identifier Terminal no. Pole Function Frequency output 1 R1 1 + pH lowering pump (control) 2 - pH raising pump 3 + Chlorine pump (control) Frequency output 2 R2 ORP pump Frequency output 3 R3 4 - pH lowering pump 5 + Flocculent pump ORP pump 6 - Chlorine pump 7 + Pump error 8 - 9 + 10 - 11 + 12 - I out 1 13 + pH value Current output 0/4-20 mA 1 14 - Control variable pH-lower Contact input 1 Contact input 2 Contact input 3 K1 K2 K3 Pump error Pump error Control variable pH-raise Control variable chlorination Control variable flocculent 218 Assembly and installation Description Terminal identifier Terminal no. Pole Function Control variable ORP (Plotter connection) Control circulation Current output 0/4-20 mA 2 I out 2 15 + ORP value 16 - Control variable pH-lower Control variable pH-raise Control variable chlorination Control variable flocculent Control variable ORP (Plotter connection) Current output 0/4-20 mA 3 I out 3 17 + Chlorine value 18 - Control variable pH-lower Control variable pH-raise Control variable chlorination Control variable flocculent Control variable ORP (Plotter connection) Current output 0/4-20 mA 4 I out 3 19 + chlorine bound 20 - Control variable pH-lower Control variable pH-raise Control variable chlorination Control variable flocculent Control variable ORP (Plotter connection) 219 Technical data 4 Technical data Electrical data Frequency outputs (Opto-MOS-relay) for pump control (R1, R2, R3): n Type of contact: N/O with interference-suppressed series inductances n Load capacity: 400 V peak, 250 mA switching current, max. 0.8 W n Maximum frequency: 8.33 Hz (500 strokes/min) n Closing time/opening time: 5 ms Contact inputs (K1, K2, K3) (term. 9 – 14): n n n n n Galvanically isolated from each other Insulation voltage: 500 V Max. contact frequency: 2 kHz Connectable contacts: mechanical relay Max. connectable cable length: 20 m Standard signal outputs mA (I out 1 - I out 4): n n n n n Material 220 Insulation voltage: 500 V Output range: 0/4-20 mA (programmable) 23 mA for error messaging Maximum apparent ohmic resistance: 400 Ω Accuracy: 0.5 % of output range Housing: PPE-GF 10 Installation instructions DULCOMARIN® II, G-Module (Limit Value and Alarm Generator Module DXMaG) A0787 Please enter the identity code of your device here! DXMa _ _ _ _ _ _ _ _ _ _ _ _ _ Please carefully read these operating instructions before use! · Do not discard! The operator shall be liable for any damage caused by installation or operating errors! Technical changes reserved. Part no. 986049 BA DC 70 02/11 EN ProMinent Dosiertechnik GmbH Im Schuhmachergewann 5 - 11 69123 Heidelberg Telephone: +49 6221 842-0 Fax: +49 6221 842-419 email: [email protected] Internet: www.prominent.com 986049, 1, en_GB © 2011 222 Supplemental instructions Further applicable documents These operating instructions and supplementary instructions are only valid in combination with the following operating and supple‐ mentary instructions: n Multi-channel measuring and control system operating instruc‐ tions DULCOMARIN® II Swimming Pool Controller and Disin‐ fection Controller DXCa Part 1: Assembly and installation n Multi-channel measuring and control system operating instruc‐ tions DULCOMARIN® II Swimming Pool Controller and Disin‐ fection Controller DXCa Part 2: Operation n Supplementary instructions DULCOMARIN® II, M-Module (measuring module for pH, redox [ORP], temperature) DXMaM operation n Supplementary instructions DULCOMARIN® II, I-Module (cur‐ rent input module, standard signal inputs mA) DXMal 223 Supplemental instructions 224 Table of contents Table of contents 1 Identity code...................................................................... 226 2 About this device............................................................... 227 2.1 Safety chapter........................................................... 227 2.2 Storage and transport............................................... 227 3 Assembly and installation................................................. 228 4 Technical data................................................................... 230 225 Identity code 1 Identity code The identity code describes the external modules for the DULCOMARIN® II, series DXM DXMa External modules for the DULCOMARIN® II, series DXM Module: G G-module, limit value and alarm module 1) 2) Mounting type: W Wall mounted (IP 65) Version: 2 Without controls Application: 0 Standard Language: 00 No controls 2) Certification: 01 CE mark only mounting type W wall mounting / 2) only in version ‘2’ without controls 1) 226 About this device 2 About this device The limit value and alarm generator module DXMaG with two limit or alarm relays signals alarm overshoots, general errors and sample water errors. 2.1 Safety chapter The DXMaG limit value and alarm generator module must only be used as part of the DULCOMARIN® II. The installation must only be carried out by technically trained per‐ sonnel. 2.2 Storage and transport CAUTION! Protect the module against moisture and the effects of chemicals, even while still packaged. Store and transport the module it its original packaging. Ambient conditions for storage and transportation: n Temperature: -10 °C ... 70 °C n Max. permissible relative humidity: 95 %, non-condensing (DIN IEC 60068-2-30) 227 Assembly and installation 3 Assembly and installation G module, DXMaG description The G module is a limit value or alarm generator module. It has two potential-free changer relays for signalling alarm states. Each of the two relays has different setting options, which can influence the relay effects. Both relays offer the same setting options. Hence through the use of different delay periods, pre-warning or shut-down signals can be generated. NOTICE! The installation must only be carried out by technically trained personnel. When assembling and installing this device, observe the instructions in the operating instructions "Multichannel measuring and control system DULCOMARIN® II Swimming Pool Controller and Dis‐ infection Controller DXCa Part 1: Assembly and instal‐ lation". Create the CAN connection in accordance with the Operating instructions DULCOMARIN ® II Swimming Pool Controller and Disinfection Controller DXCa , Part 1: Assembly and installation". 228 Assembly and installation A0788 Fig. 1: Wiring diagram, G module / power relay outputs I. Limit value / alarm generator 1 II. Limit value / alarm generator 2 Terminal allocation Description Power relay output 1 Power relay output 2 Terminals Terminals Identifier number P1 P2 Pole Function 1 C 2 to select NO Limit value / alarm gener‐ ator 1 3 NC 1 C 2 to select NO 3 NC Limit value / alarm gener‐ ator 2 The XR terminals have no function. 229 Technical data 4 Technical data Electrical data Power relay output (P1, P2): n Type of contact: Changeover contact with interference-sup‐ pressed varistors n Load capacity: 250 V AC, 3 A max., 700 VA n Contact operational lifetime: > 20 x 105 switching operations Material 230 Housing: PPE-GF 10 Operating instructions DULCOMARIN® II, I-Module (Current Input Module, Standard Signal Inputs mA) DXMaI A0483 Please enter the identity code of your device here! DXMA _ _ _ _ _ _ _ _ _ _ _ _ _ Please carefully read these operating instructions before use! · Do not discard! The operator shall be liable for any damage caused by installation or operating errors! Technical changes reserved. Part no. 986463 BA DC 071 02/11 EN ProMinent Dosiertechnik GmbH Im Schuhmachergewann 5 - 11 69123 Heidelberg Telephone: +49 6221 842-0 Fax: +49 6221 842-419 email: [email protected] Internet: www.prominent.com 986463, 1, en_GB © 2011 232 Supplemental instructions Further applicable documents These operating instructions and supplementary instructions are only valid in combination with the following operating and supple‐ mentary instructions: n Multi-channel measuring and control system operating instruc‐ tions DULCOMARIN® II Swimming Pool Controller and Disin‐ fection Controller DXCa Part 1: Assembly and installation n Multi-channel measuring and control system operating instruc‐ tions DULCOMARIN® II Swimming Pool Controller and Disin‐ fection Controller DXCa Part 2: Operation n Supplementary instructions DULCOMARIN® II Screen writer operation 233 Supplemental instructions 234 Table of contents Table of contents 1 Identity code...................................................................... 236 2 About this device............................................................... 238 2.1 Safety chapter........................................................... 238 2.2 Storage and transport............................................... 238 3 Assembly and installation................................................. 239 4 Technical data................................................................... 241 235 Identity code 1 Identity code The identity code describes the external modules for the DULCOMARIN® II, series DXM Only the M module of mounting type ‘W’ ‘Wall mounting’ can be ordered with operating elements and with different languages. DXMa External modules for the DULCOMARIN® II, series DXM Module: M M module, measuring module: pH, redox, temperature A A module, control module: 3 pumps and 4 analog outputs R R module, control module: Chlorine gas metering device with feedback 1) 2) N N module, power supply module without relay 1) 2) P P module, power supply module without relay, only mounting type ‘0)’ I I module, current input module, 3 mA inputs, 2 digital inputs 2) Mounting type: 0 Without housing, only P-module (IP 00) W Wall mounted (IP 65) H Mounting rail (IP 20) E Upgrade module (insert module for DXCa, IP 20) Version: 0 With controls 2 Without controls 3 Without controls (only mounting type ‘E’ ) Application: 0 Standard S Swimming pool (only m module) Language: 00 No controls 2) DE German EN English ES Spanish FR French IT Italian Certification: 236 00 No certification, only P-module without housing 01 CE mark Identity code only mounting type W wall mounting / 2) only in version ‘2’ without controls 1) 237 About this device 2 About this device The current input module DXMaI allows the DULCOMARIN® II to connect 2 switches / relays and 3 sensors via 0/4...20 mA inputs. The DXMaI control module has the following inputs: n Contact inputs for sample water monitoring and pause n 3 standard signal inputs 0/4...20 mA The mA values of the sensors for flow, turbidity, UV-intensity, con‐ ductive conductivity, dissolved oxygen and ammonia are received already processed (compensated and calibrated). The mA values for ClO2, H2O2, PES, fluoride and chlorite can be temperature compensated. To do this, a PT1000 sensor with mA transformer must be connected to an mA input. 2.1 Safety chapter The DXMaI current input module must only be used as part of the DULCOMARIN® II. The installation must only be carried out by technically trained per‐ sonnel. 2.2 Storage and transport CAUTION! Protect the module against moisture and the effects of chemicals, even while still packaged. Store and transport the module it its original packaging. Ambient conditions for storage and transportation: n Temperature: -10 °C ... 70 °C n Max. permissible relative humidity: 95 %, non-condensing (DIN IEC 60068-2-30) 238 Assembly and installation 3 Assembly and installation NOTICE! The installation must only be carried out by technically trained personnel. When assembling and installing this device, observe the instructions in the operating instructions "Multichannel measuring and control system DULCOMARIN® II Swimming Pool Controller and Dis‐ infection Controller DXCa Part 1: Assembly and instal‐ lation". Make the CAN connection according to the "Multi-channel meas‐ uring and control system operating instructions DULCOMARIN® II Swimming Pool Controller and Disinfection Controller DXCa Part 1, Assembly and Installation". Terminal allocation Description Terminal identifier Terminal no. Pol Function Contact input 1 K1 1 - Fault sample water 2 + 3 - 4 + 5 in 6 GND (-) 7 V+ Fluoride 8 in O2, ClO2, ClO2 -, 9 GND (-) H2O2, NH4OH) 10 V+ Temperature 11 in (UV, turbidity, 12 GND (-) conductivity, ClO2 -) Contact input 2 Analog input 1 Analog input 2 Analog input 3 K2 I in 1 I in 2 I in 3 Pause control (e.g. back‐ washing) Flow (turbidity) 239 Assembly and installation Fig. 1: Terminal Wiring Diagram I. Assignment variants II. ProMinent® Transducer/Sensor SPS PLC Programmable logic controller For the measured variables, which are input through terminal "I in 2", the following functionalities are avail‐ able in the software: F- O2 ClO2 ClO2- H2O2 Regulate ✱ - - X X X Calibrate X - X - X ✱ For this a pump must be previously configured (see "Operating instructions Multi-channel measuring and control system DULCOMARIN® II Disinfection Controller DXCa, Part 2: Opera‐ tion"). 240 Technical data 4 Technical data Electrical data Digital inputs (K1 - K2): n 2 inputs: for contacts, switching transistors and for PLC analog outputs as per DIN EN 61131-2 n Insulation voltage: 500 V n Input resistance: 3.5 kΩ n Open circuit voltage: 10 V ... 12 V n Switching point: – Passive: 1750 Ω, typical – Active: 3.15 mA, typical n Input current: – 4 mA (0 V) – 5.8 mA (30 V) n Input capacity: 100 nF n Switching hysteresis: 20 μA n Max.switching frequency: 1 kHz Standard signal outputs mA (I in 1 - I in 3): 3 inputs: 0/4 ... 20 mA, isolated Insulation voltage: 500 V Input resistance: 50 Ω Load capacity: 30 mA 2 inputs with 2-wire connector (sliding supply) (I in 2, I in 3): Supply voltage 22.0 V- 25.0 V n Measuring accuracy: ± 0.5 % of the measuring range (at 25 °C) n Resolution: 1/215 n n n n n Ambient conditions Storage temperature: -10...70 °C Protective system: n Degree of protection: as Internet module IP 20 n as external module, wall mounted IP 65, according to IEC 60529, DIN EN 60529, VDE 0470 n as external module, control panel mounted IP 54, according to IEC 60529, DIN EN 60529, VDE 0470 Material Housing: PPE-GF 10 241 Technical data 242 Assembly and operating instructions DULCOMARIN® II, M-Module DXMaM (Measurement Module for pH, Redox, Temperature) Please enter the identity code of your device here! DXMA _ _ _ _ _ _ _ _ _ _ _ _ _ Please carefully read these operating instructions before use! · Do not discard! The operator shall be liable for any damage caused by installation or operating errors! Technical changes reserved. Part no. 985989 BA DC 072 02/11 EN ProMinent Dosiertechnik GmbH Im Schuhmachergewann 5 - 11 69123 Heidelberg Telephone: +49 6221 842-0 Fax: +49 6221 842-419 email: [email protected] Internet: www.prominent.com 985989, 1, en_GB © 2011 244 Supplemental instructions Further applicable documents These operating instructions and supplementary instructions are only valid in combination with the following operating and supple‐ mentary instructions: n Multi-channel measuring and control system operating instruc‐ tions DULCOMARIN® II Swimming Pool Controller and Disin‐ fection Controller DXCa Part 2: Operation n Supplementary instructions DULCOMARIN® II Screen plotter operation 245 Supplemental instructions 246 Table of contents Table of contents 1 Identity code...................................................................... 248 2 Safety and responsibility................................................... 250 3 Handling the device.......................................................... 251 4 Terminal Wiring Diagram.................................................. 252 5 Control elements............................................................... 255 5.1 Layout of the operating menu................................... 256 6 Adjustment........................................................................ 6.1 Basic settings............................................................ 6.2 Calibration................................................................. 6.2.1 pH calibration......................................................... 6.2.2 Checking the redox sensor.................................... 6.2.3 Calibrating a temperature sensor.......................... 6.2.4 Calibrating a chlorine sensor for free chlorine....... 6.2.5 Calibrating a chlorine sensor for total chlorine....... 6.2.6 Chlorine sensor temperature................................. 259 259 260 260 264 265 266 267 268 247 Identity code 1 Identity code The identity code describes the external modules for the DULCOMARIN® II, series DXM Only the M module of mounting type ‘W’ ‘Wall mounting’ can be ordered with operating elements and with different languages. DXMa External modules for the DULCOMARIN® II, series DXM Module: M M module, measuring module: pH, redox, temperature A A module, control module: 3 pumps and 4 analog outputs R R module, control module: Chlorine gas metering device with feedback 1) 2) N N module, power supply module without relay 1) 2) P P module, power supply module without relay, only mounting type ‘0)’ I I module, current input module, 3 mA inputs, 2 digital inputs 2) Mounting type: 0 Without housing, only P-module (IP 00) W Wall mounted (IP 65) H Mounting rail (IP 20) E Upgrade module (insert module for DXCa, IP 20) Version: 0 With controls 2 Without controls 3 Without controls (only mounting type ‘E’ ) Application: 0 Standard S Swimming pool (only m module) Language: 00 No controls 2) DE German EN English ES Spanish FR French IT Italian Certification: 248 00 No certification, only P-module without housing 01 CE mark Identity code only mounting type W wall mounting / 2) only in version ‘2’ without controls 1) 249 Safety and responsibility 2 Safety and responsibility About this device The measurement module DXMaM typically allows the DULCO‐ MARIN® II to: n n n n measure and control the pH value measure and display the redox potential (optional controller) measure and display the temperature of the sample water monitor the sample water flow The DXMaM measurement module has the following inputs: n One Pt1000 temperature input (Pt100, automatic sensor detec‐ tion) n Two sensor inputs for pH or redox measurement with potential equalisation n Three contact inputs for pause, parameter set switching, sample water monitoring Safety NOTICE! Further applicable documents These operating instructions are only valid in conjunc‐ tion with the "Operating instructions DULCOMARIN® II, Part 1: Assembly and installation". All the safety instructions and explanations contained therein must be observed without exception. WARNING! Danger of malfunctions Only trained personnel may install the DXMaR M module. Only then can it be ensured that all compo‐ nents of the control circuit are matched to each other and operating correctly NOTICE! Registering and unregistering components to the CAN bus The chlorine sensor must be registered to the CAN bus. You can find further information in the "Operating instructions DULCOMARIN® II Swimming Pool Con‐ troller and Disinfection Controller DXCa Part 2: Opera‐ tion". 250 Handling the device 3 Handling the device Storage and transport CAUTION! Protect the module against moisture and the effects of chemicals, even while still packaged! Store and transport the module it its original packaging. Ambient conditions for storage and transport: n Temperature: -10 °C ... 70 °C n Max. permissible relative humidity: 95 %, non-condensing (DIN IEC 60068-2-30) Assembly and installation WARNING! Danger of malfunctions Only trained personnel may install the M module DXMaM. Only then can it be ensured that all compo‐ nents of the control circuit are matched to each other and operating correctly NOTICE! Terminal Wiring Diagram The wiring diagram can be found at the end of these operating instructions, see . Create the CAN connection in accordance with the operating instructions "DULCOMARIN® II, Part 1: Assembly and installation". 251 Terminal Wiring Diagram 4 Terminal Wiring Diagram Sensor "combination probe" Temp input + Input 1 Potential equalisation Digital inputs Input 2 - + W - + - + - X Pot.-equalisation pin ORP (pH)* Temperature External Pot.-equalisation pin pH (ORP)* Internal 3 4 Shielding open Shielding holder 7 8 A0451 Fig. 1: Sensor "combination probe" ✱ The "Potential equalisation" function must be activated in the software 252 Terminal Wiring Diagram Sensor: "Separate probe" Temp input Input 1 Input 2 Potential equalisation Digital inputs Signal Shielding 3 4 Ref. electrode Pot. equalisation pin Pot. equalisation pin Shielding Ref. electrode Temperature External Signal Internal Shielding open Shielding holder 7 8 Fig. 2: Sensor: "Separate probe" ✱ The "Potential equalisation" function must be activated in the software Terminal allocation Description Terminal identifier Terminal no. Pol. Function Temp. input RTD 1 + 2 - Pt1000(100 (temp. sensor) 3 Ref. 4 meas sig. Pt1000/100 pH/redox input 1 pH (ORP) Potential equalisation 1 POT 1 5 Potential equalisation 2 POT 2 6 pH/redox input 2 pH (ORP) 7 Ref. 8 meas sig. 9 + 10 - Contact input 1 K1 ORP sensor pH sensor Sample water (error) 253 Terminal Wiring Diagram Description Terminal identifier Terminal no. Pol. Function Contact input 2 K2 11 + 12 - Pause control (back‐ washing) 13 + 14 - Contact input 3 Electrical data K3 ECO!MODE Pt1000/Pt100 input (RTD) (Term. 1, 2): n Input range: -20 ... 150 °C n Accuracy: ± 0.5 °C n Resolution: 0.1 °C Sensor input (ORP) (term. 3, 4) for redox: n n n n n n n Input resistance: > 1012 Ohm All reference electrodes with diaphragms can be connected. Input range: Redox: -1200 mV ... +1200 mV Accuracy: 0.5 % of input range Resolution: 1 mV (0.01 pH) Reference electrode connection via shielding connection Connecting option for a equipotential bonding probe Sensor input (pH) (term. 7, 8) for pH: n n n n Input resistance: > 1012 Ohm Input range: pH: -1 ... 15 (0 ... 100 °C) Resolution: 0.01 pH Further data such as ‘Sensor input (ORP)’ . Contact inputs (K1, K2, K3) (term. 9 – 14): n n n n n Ambient conditions Galvanically isolated from each other Insulation voltage: 500 V Max. contact frequency: 2 kHz Connectable contacts: mechanical relay Max. connectable cable length: 20 m Storage temperature: -10...70 °C Protection rating: IP 20 (within the DXM housing: IP 65) Climate: Permissible relative humidity: 95 %, non-condensing (DIN IEC 60068-2-30) Material 254 Housing: PPE-GF 10 Control elements 5 Control elements Fig. 3: Control elements 1. 2. 3. 4. Module type label LCD display CAL key ENTER key Functions of the keys 5. 6. 7. 8. UP key DOWN key ESC key Change key You can use the keys to change the DULCOMARIN® II settings. The keys have the following functions: Key In the continuous display or in the info displays In the menu items Change key Change between continuous displays Change between the adjustable variables of the current menu item ESC key Jump back from the info displays to the continuous displays Jump back to the info display without saving of the adjustable variables Enter key Change to a menu item (from an info display) Save the adjustable variables of the current menu item and change to the info display CAL key Change to an info display of the calibra‐ tion menu (from the continuous display) Execution of the calibration step in the cali‐ bration menu (only for pH) Down key ------ Changing of an adjustable variable Up key 255 Control elements 5.1 Layout of the operating menu The operating menu comprises: n the continuous displays (continuous display level) n the info displays (info level) for the display of the set calibration parameters or basic settings n the calibration menu n the menu items (adjustment level) for changing the calibration parameters or basic settings Permanent display 1 Info display Menu point Permanent display 2 Info display Menu point * Permanent display X Info display Menu point = A0454 Fig. 4: Layout of the operating menu I. II. III. Calibration menu Continuous displays Info level Navigation through the operating menu IV. V. Adjustment level Querying of the access code (only if activated by the user) Using the ESC key it is essentially possible to abort the current selection in any window of the operating menu. Irrespective of where you are located in the operating menu, a jump back to the corresponding continuous display or info display occurs. If no key is pressed for 5 minutes, the display automatically jumps back to the continuous display (without saving the adjustable varia‐ bles). If an access code has been activated by the user, the menu items of the adjustment level are first locked. For ‘Unlocking’ , the access code must be entered in the corresponding query and confirmed with the Enter key. As soon as the DXMaM is again in a continuous display, this ‘Unlocking’ is removed. The access code is set to ‘0000’ ex-works and is thus inactive. 256 Control elements Continuous displays Cl: pH Control value: free Cl Control: not activated comb. Cl (total Cl) Temp Cl sensor comb. Cl Control value: Chlore total: 0.45 ppm Cl sensor A0455 Fig. 5: Continuous displays I. Continuous Display 1 During operation you can monitor the measured values of the cor‐ responding pools via the continuous displays. Which continuous displays of the DXMaM are shown depends on which sensors are connected to the DULCOMARIN® II and configured. Continuous display 1 can display up to four measured variables. Alongside this, each measured variable has a further continuous display of its own. The continuous displays can display the following: n Measured variables [pH], [Redox], [Free chlorine], [Cl comb] ([Cl tot] in the footer), temperature (separate Pt1000 and Cl sensor) n Activity of the controller for a measured variable and corre‐ spondingly the control variable Info displays By pressing the Enter key or the CAL key in a continuous display, you enter the corresponding info display (info level). Calibration menu By pressing the CAL key in a continuous display, you enter the cor‐ responding calibration menu Menu items By pressing the Enter key in the info displays, you enter the corre‐ sponding menu items (adjustment level) Navigation in the menu item – – Your entries become effective and are perma‐ nently saved at the moment you press the Enter key If you do not want to save the set variables, then exit the menu item by pressing the ESC key: You move back to the corresponding info display 257 Control elements Capture Unit: Corr.± = measuring value A0457 Fig. 6: Navigation in the menu item I. Adjustable numerical value/expression flashes In a menu item, you can activate each adjustable variable with the ESC key. If the adjustable variable flashes, then it can be adjusted. Using the arrow keys, you can change the numerical values or expressions. Where: n 1x short press means that a numerical value will be decreased/ increased by 1 step or an expression changed n longer pressing causes changing of the numerical values to take place more quickly. n You can save the set variables of the menu item by pressing the Enter key. Simultaneously you change back to the info dis‐ play. 258 Adjustment 6 Adjustment pH: ORP: Temp: Cl: 7.12 654 mV 25 ˚C 1.12 mg/l Version: 2001 Number of permanent displays is dependent on the allocated sensors 7.12 Control value: Language:English Password: 4444 Base settings pH 24% Calibrate with CAL! Zero point=12 mV slope = 58.32 mV/pH Buffer temp=25.2 ˚C Buffer recogn. T. = 20.3 ˚C Buffer recogn. T. = 20.3 ˚C Buffer temp= 25.2 ˚C Calibrate with CAL! Calibration End= T. = 20.3 ˚C or cal2=CAL T. = 20.3 ˚C End calib. by Calibration T. = 20.3 ˚C T. = 20.3 ˚C Zero point Slope Accept measuring value 654 mV ORP Control: not activated 25.6 ˚C Temp: Pt1000 1.12 mg/l Cl Control value: 24% 0.13 total Cl: mg/l comb. Cl 0.45 ppm 25.3 °C Temp: Cl sensor Adjust with CAL! Offset = 2 mV accept Adj.value 654 mV measuring value = 654 mV measuring =value 652 mV Calibrate with CAL! Offset = 1.1 °C accept Adj.value measuring value = 20.6 ˚C measuring value = 20.6 ˚C Calibrate with CAL! Zero point = 5 pA slope = 105.22 % measuring=value 0.52 mg/l Calibrate with CAL! Zero point = 5 pA slope = 105.22 % measuring = value 0.52 mg/l 21.7 ˚C accept DPD-value: 0.56 mg/l measuring =value 0.52 mg/l accept DPD-value : 0.56 mg/l 0.52 mg/l measuring=value = I. A0458 Fig. 7: Menu overview I. Querying of the access code (only if activated by the user) 6.1 Basic settings NOTICE! Factory-set access code Replace the factory-set access code with your own access code. Otherwise protection of the following menus will be extremely weak. When jumping back in a continuous display the DULCOMARIN® II automatically removes the author‐ ised access. 259 Adjustment Access code (password) You can limit access to the device by setting an access code. Language and access code settings can be made in the ‘Basic settings’ menu: 1. In continuous display 1 press the Enter key 2x 2. Under ‘Language’ set the desired language using the arrow keys 3. Change to the selection ‘Password’ by pressing the Change key 4. Under ‘Password’ set the desired access code using the arrow keys 5. Press the ENTER key to accept the values or press the ESC key if you do not want to save the values ð The display changes to the info display. 6. Jump back to the continuous display by pressing the ESC key ð The menus are then password protected again 6.2 Calibration 6.2.1 pH calibration Calibration of pH measurement Automatic buffer detection The condition of a pH sensor is decisive for the quality of the measurement. Therefore each pH sensor must periodically be recalibrated using buffer solutions. The DXMaM has an automatic buffer detection system for the buffer solution being used. The following buffer table is stored in the program memory: Buffer temperature in °C pH 0 4.05 7.13 10.26 5 4.04 7.07 10.17 10 4.02 7.05 10.11 15 4.01 7.02 10.05 20 4.00 7.00 10.00 25 4.00 6.98 9.94 30 4.00 6.98 9.90 40 4.00 6.97 9.82 50 4.00 6.96 9.75 60 4.00 6.97 9.68 It is recommended that only ProMinent® buffer solutions are used for calibration. 260 Adjustment Buffer temperature in °C pH 70 4.01 6.98 9.62 80 4.02 6.99 9.55 It is recommended that only ProMinent® buffer solutions are used for calibration. Sequence of the pH calibration – – – – Using the ESC key you can always abort a calibra‐ tion from any menu item in the calibration menu. The screen jumps back to the continuous display The control variable is frozen for the duration of the calibration at the last value (HOLD) Unallowable values make the currently running cal‐ ibration invalid. The previous calibration values are retained Dispose of the used buffer solution Calibration menu overview 7.12 pH Control value: 24 % Sensor calibration Zero point= 12 mV slope = 58.32 mV/pH Buffer temp= 25.2 °C Buffer temp= 20.3 °C Buffer recogn. Calibration Buffer recogn. Calibration Zero point Slope Accept measuring value End calib. by I. II. A0459 Fig. 8: 2 point calibration I. The display change only takes place once the time bar is completely solid II. Querying of the access code (only if activated by the user) 261 Adjustment Sensor calibration Zero point=12 mV slope = 58.32 mV/pH Buffer temp= 25.2 °C pH Control value: 24% Buffer temp= 20.3 °C Buffer recogn. Calibration End= or cal2=CAL Zero point Slope Accept measuring value A0460 Fig. 9: 1 point calibration I. The display change only takes place once the time bar is completely solid II. Querying of the access code (only if activated by the user) Actuating variable: Sensor calibration Zero point=12 mV slope = 58.32 mV/pH Buffer temp = 25.2 °C Buffer temp = 25.2 °C A0461 Fig. 10: To call the calibration menu, proceed as follows: Start the calibration 1. In the ‘pH’ continuous display press the CAL key 2x, while the pH sensor is still in the sample water 2. Under ‘Buffer temp.’ set the buffer temperature using the arrow keys ð This setting is only valid during the calibration procedure. 3. Take the pH sensor out of the sample water, rinse and immerse in the first buffer solution (here pH 4) Calibration Buffer recogn. End or A0462 Fig. 11: Automatic buffer detection 4. Press the CAL key to start the automatic buffer detection ð The progress of the buffer detection is shown by a time bar. The manually set buffer temperature is displayed under ‘T’ . 5. 262 After buffer detection, calculation of the calibration parame‐ ters starts automatically (Calibration). This is likewise shown by a time bar Adjustment You can correct the buffer value during the calibration using the arrow keys. If the sensor signal is unstable, the time bar remains stationary until it becomes stable. After the calibration, the con‐ cluding menu item of the 1-point calibration appears. Once again you can correct the buffer value here using the arrow keys. The following procedure then depends on whether you wish to carry out a 1-point calibration or a 2-point calibration (recom‐ mended!). 1. 1 point calibration Press the ENTER key to end the 1-point calibration ð The zero point is calibrated if the buffer values lies between 5.5 and 8.0 pH. Zero point Slope Accept measuring value A0464 Fig. 12: Zero Point and Gradient 2. The calibration values (zero point and gradient) are now dis‐ played The check of the actual pH value is displayed under ‘Measured value’ . 3. Press the ENTER key to accept the values or press the ESC key if you do not want to save the values ð The display changes to the info display, the calibration is completed. 4. Jump back to the continuous display by pressing the ESC key ð The menus are then password protected again 1. 2 point calibration Buffer recogn. For a 2-point calibration, take the pH sensor out of the first buffer solution, rinse in clean water and immerse it in the second buffer solution Calibration End calib. by A0463 Fig. 13: Automatic buffer detection 2. Press the CAL key to start the automatic buffer detection 3. After the calibration, the concluding menu item of the 2-point calibration appears. ð Once again you can correct the buffer value using the arrow keys. 4. Press the ENTER key to end the 2-point calibration 263 Adjustment Zero point Slope Accept measuring value A0464 Fig. 14: Zero Point and Gradient 5. The calibration values (zero point and gradient) are now dis‐ played The check of the actual pH value is displayed under ‘Measured value’ . 6. Press the ENTER key to accept the values or press the ESC key if you do not want to save the values ð The display changes to the info display, the calibration is completed. 7. Jump back to the continuous display by pressing the ESC key ð The menus are then password protected again Error messages Unallowable values make the currently running calibra‐ tion invalid. The previous calibration values are retained. Fault message Cause Effect Zero point < -60 mV !!! N < -60 mV Old zero point and gradient remain Calibr. invalid Zero point > 60 mV !!! Replace sensor N > +60 mV Calibr. invalid Slope < 40 mV/pH ! Replace sensor S < 47 mV/pH Calibr. invalid Slope > 65 mV/pH ! Old zero point and gradient remain Replace sensor S > 63 mV/pH Calibr. invalid Buffer gap too small! Old zero point and gradient remain Old zero point and gradient remain Replace sensor Δ buffer < 2 pH Calibrate buffer 2 again Calibr. invalid 6.2.2 Checking the redox sensor NOTICE! No controller The control variable is frozen for the duration of the checking of the redox sensor at the last value (HOLD) 264 Adjustment Control: not activated Check sensor Offset = 2 mV Buffer with Adj.value 654 mV measuring value = 654 mV measuring value = 652 mV A0465 Fig. 15: Checking the redox sensor You can check the sensor by measuring the redox voltage in a buffer solution 1. In the "Redox" continuous display press the CAL key 2. If the ‘measured value’ is stable, press the CAL key 3. Under ‘Adjust. Value’ enter the specified redox voltage for the buffer solution (arrow keys) 4. Press the ENTER key - the buffer value is compared in the device with the measured value and the ‘Offset’ displayed in the next menu item. The offset may not be greater than ± 40 mV 5. Jump back to the continuous display by pressing the ESC key ð The menus are then password protected again Fault message Cause Effect Calibration invalid Redox voltage difference > 40 mV Replace sensor Offset too high 6.2.3 Calibrating a temperature sensor NOTICE! The temperature sensor of the chlorine sensor need not be calibrated (this continuous display does not appear with chlorine sensors). You should only calibrate the temperature sensor if: – – you are using a type PT100 temperature sensor you have a precise reference instrument Do not change the temperature sensor during the cali‐ bration: – – The temperature measured value can only be adjusted within a range of ± 4 °C about the exworks calibration value The continuous display ‘Temperature, Cl-Sensor’ does not have a calibration menu Calibrate sensor Offset = 1.1 adj. value: 26.7 measuring value = 26.7 measuring value = 25.6 A0466 Fig. 16: Calibrating a temperature sensor 265 Adjustment To call the calibration menu, proceed as follows: 1. In the ‘Temperature, Pt1000’ continuous display press the CAL key 2. Take a water sample of at least 250 ml Carry out the measurement immediately after sampling before the temperature of the water sample changes. 3. Immerse the external PT100 temperature sensor of the DUL‐ COMARIN® II and that of the reference instrument into the water sample 4. Once the ‘measured value’ is stable, press the ENTER key 5. Under ‘Adjust. Value’ enter the value of the reference instru‐ ment (arrow keys) and press the ENTER key 6. Jump back to the continuous display by pressing the ESC key ð The menus are then password protected again Fault message Cause Effect Calibration invalid Temperature difference > 4 °C Replace sensor Offset too high 6.2.4 Calibrating a chlorine sensor for free chlorine NOTICE! Measurement quality The condition of a chlorine sensor is decisive for the quality of the measurement. Therefore each chlorine sensor must periodically be recalibrated using a DPD measuring set. NOTICE! Further applicable documents Please also observe the operating instructions for the sensor and in-line probe housing! Actuating variable: 24 % Calibrate sensor Zero point = 5 pA slope = 105.22 % measuring value = 1.16 mg/l DPD-value: 1.16 mg/l measuring value = 1.12 mg/l A0467 Fig. 17: Calibrating a chlorine sensor for free chlorine To call the calibration menu, proceed as follows: 266 1. Block the sample water 2. In the ‘Cl’ continuous display press the CAL key Adjustment 3. If the ‘measured value’ is stable, press the CAL key 4. Immediately afterwards, take a water sample from the flow gauge 5. Immediately afterwards, determine the chlorine content of the sample water with a photometer and a suitable measuring set, e.g. DPD 1 for free chlorine (CLE sensor) 6. Enter the determined chlorine content immediately under ‘DPD value’ (arrow keys) 7. Press the ENTER key ð - now the new calibration values are displayed. 8. Press the ESC key to jump back to the continuous display ð the menus are then password protected again. 9. If total chlorine is also being measured, then also immedi‐ ately calibrate this measured variable Repeat the calibration after one day. 10. Open the stopcocks again for the sample water Fault message Cause Effect Calibration invalid Error upon calibration Old zero point and gradient remain, recalibrate 6.2.5 Calibrating a chlorine sensor for total chlorine NOTICE! Measurement quality The condition of a chlorine sensor is decisive for the quality of the measurement. Therefore each chlorine sensor must periodically be recalibrated using a DPD measuring set. NOTICE! Here you calibrate the CTE sensor for total chlorine. The DULCOMARIN® II calculates the displayed value for combined chlorine as the difference between the measured values for free chlorine and total chlorine The chlorine sensor for free chlorine must be a CLE 3.1 for differential measurement 267 Adjustment NOTICE! Further applicable documents Please also observe the operating instructions for the sensor and in-line probe housing! Calibrate sensor Zero point = 5 pA slope = 105.22 % measuring value = 0.48 mg/l comb. Cl Chlore total: 0.45 ppm DPD-value: 0.48 mg/l measuring value = 0.45 mg/l A0468 Fig. 18: Calibrating a chlorine sensor for total chlorine To call the calibration menu, proceed as follows: 1. Block the sample water 2. In the ‘Cl comb’ continuous display press the CAL key 3. If the ‘measured value’ is stable, press the CAL key 4. Immediately afterwards, take a water sample from the flow gauge 5. Immediately afterwards, determine the chlorine content of the sample water with a photometer and a suitable measuring set, e.g. DPD 1 for free chlorine (CLE sensor) 6. Enter the determined chlorine content immediately under ‘DPD value’ (arrow keys) 7. Press the ENTER key ð - now the new calibration values are displayed. 8. Press the ESC key to jump back to the continuous display ð the menus are then password protected again. 9. If total chlorine is also being measured, then also immedi‐ ately calibrate this measured variable Repeat the calibration after one day. 10. Open the stopcocks again for the sample water 6.2.6 Chlorine sensor temperature There is only one continuous display for the chlorine sensor. The temperature sensor of the chlorine sensor cannot be calibrated, no calibration menu follows from the continuous display. 268 Assembly and operating instructions DULCOMARIN® II, N-Module (Power Supply Module without Relay) DXMaN Please enter the identity code of your device here! DXMa _ _ _ _ _ _ _ _ _ _ _ _ _ Please carefully read these operating instructions before use! · Do not discard! The operator shall be liable for any damage caused by installation or operating errors! Technical changes reserved. Part no. 986528 BA DC 073 02/11 EN ProMinent Dosiertechnik GmbH Im Schuhmachergewann 5 - 11 69123 Heidelberg Telephone: +49 6221 842-0 Fax: +49 6221 842-419 email: [email protected] Internet: www.prominent.com 986528, 1, en_GB © 2011 270 Supplemental instructions Further applicable documents These operating instructions and supplementary instructions are only valid in combination with the following operating and supple‐ mentary instructions: n Multi-channel measuring and control system operating instruc‐ tions DULCOMARIN® II Swimming Pool Controller and Disin‐ fection Controller DXCa Part 1: Assembly and installation 271 Supplemental instructions 272 Table of contents Table of contents 1 Identity code...................................................................... 274 2 About this device............................................................... 276 2.1 Safety chapter........................................................... 276 2.2 Storage and transport............................................... 276 3 Assembly and installation................................................. 277 3.1 Repairs (fuse change only)....................................... 279 273 Identity code 1 Identity code The identity code describes the external modules for the DULCOMARIN® II, series DXM Only the M module of mounting type ‘W’ ‘Wall mounting’ can be ordered with operating elements and with different languages. DXMa External modules for the DULCOMARIN® II, series DXM Module: M M module, measuring module: pH, redox, temperature A A module, control module: 3 pumps and 4 analog outputs R R module, control module: Chlorine gas metering device with feedback 1) 2) N N module, power supply module without relay 1) 2) P P module, power supply module without relay, only mounting type ‘0)’ I I module, current input module, 3 mA inputs, 2 digital inputs 2) Mounting type: 0 Without housing, only P-module (IP 00) W Wall mounted (IP 65) H Mounting rail (IP 20) E Upgrade module (insert module for DXCa, IP 20) Version: 0 With controls 2 Without controls 3 Without controls (only mounting type ‘E’ ) Application: 0 Standard S Swimming pool (only m module) Language: 00 No controls 2) DE German EN English ES Spanish FR French IT Italian Certification: 274 00 No certification, only P-module without housing 01 CE mark Identity code only mounting type W wall mounting / 2) only in version ‘2’ without controls 1) 275 About this device 2 About this device The N-module DXMaN (power module without relay) supplies the modules of a DULCOMARIN® II system with electrical power. 2.1 Safety chapter The DXMaN module must only be used as a power supply for the DULCOMARIN® II. The DXMaN module must only be used as part of a DULCOMARIN® II. Only trained personnel may install the N module DXMaN. 2.2 Storage and transport CAUTION! Protect the module against moisture and the effects of chemicals, even while still packaged. Store and transport the module it its original packaging. Ambient conditions for storage and transportation: n Temperature: -10 °C ... 70 °C n Max. permissible relative humidity: 95 %, non-condensing (DIN IEC 60068-2-30) 276 Assembly and installation 3 Assembly and installation NOTICE! The installation must only be carried out by technically trained personnel. When assembling and installing this device, observe the instructions in the operating instructions "Multichannel measuring and control system DULCOMARIN® II Swimming Pool Controller and Dis‐ infection Controller DXCa Part 1: Assembly and instal‐ lation". The central unit does not allocate the N modules any ‘NodeIDs’ . They do not form an active part of the bus system. Make the CAN connection according to the "Multi-channel meas‐ uring and control system operating instructions DULCOMARIN® II Swimming Pool Controller and Disinfection Controller DXCa Part 1, Assembly and Installation". WARNING! Mains voltage Possible consequence: Fatal or very serious injuries. External fuse necessary. If mains voltage is connected to the device, then the fuse carrier is also under mains voltage. Before working on the device, disconnect the device from the mains voltage and secure to prevent switching back on. 277 Assembly and installation A0478 Fig. 1: Terminal Wiring Diagram 1. 2. 3. 4. Fuse 5x20 slow-acting CAN connector plug M12 5 pole. LED 2 LED 1 5. 6. ✱ Connector for central unit✱ CAN bus connector to the modules✱ If used as an Internet module Terminal allocation Description Terminal identifier Terminal no. Pol Mains X1 11 N 12 L(1) The two LEDS (LED 1 and LED 2) indicate the load of the 24V power supply for the CAN bus. Flash code LEDs power supply monitoring DULCOMARIN® II (N and P module) Operating status LED 1 LED 2 (H2, power) (H3, power) Normal off Limit load Overload / short circuit 278 Power Remarks green < 1.1 A All OK red off > 1.1 A Insert another power supply module into the loop red, flashing off > 1.35 A Check wiring Assembly and installation Power supply module Locate the power supply module in the CAN bus backbone (DUL‐ COMARIN® II DULCO-Net) The central unit always contains a power supply module. Number of pools Additional N- or P-mod‐ ules Number of pools Additional N- or P-mod‐ ules 1 - 9 4 2 - 10 5 3 1 11 5 4 2 12 6 5 2 13 6 6 3 14 7 7 3 15 7 8 4 16 8 (Exception: number of pools = 2) Electrical data n Nominal voltage (X1): 90 - 253 V AC (50/60 Hz) n Maximum power consumption: 500 mA at 90 V AC // 180 mA at 253 V AC n Internal fusing with: Micro fuse 5 x 20 mm, 630 mA, 250 V, slow-acting The N module DXMaN is a 24 V direct current power supply module (24 V DC, 1 A). Degree of protection: IP 20 (within the DXM housing: IP 65) 3.1 Repairs (fuse change only) WARNING! Mains voltage Possible consequence: Fatal or very serious injuries. External fuse necessary. If mains voltage is connected to the device, then the fuse carrier is also under mains voltage. Before working on the device, disconnect the device from the mains voltage and secure to prevent switching back on. NOTICE! The fuse only may be replaced by technically trained personnel. All other repair work may only be carried out by Customer Service. Otherwise, general safety regulations apply. Use only original fuses: Micro fuse 5 x 20 mm, 630 mA, 250 V, slow-acting (Order No. 712030). 279 Assembly and installation 280 Assembly and operating instructions DULCOMARIN® II, P-Module (Power Supply Module with Relay) DXMaP A0479 Please enter the identity code of your device here! DXMa _ _ _ _ _ _ _ _ _ _ _ _ _ Please carefully read these operating instructions before use! · Do not discard! The operator shall be liable for any damage caused by installation or operating errors! Technical changes reserved. Part no. 986903 BA DC 074 02/11 EN ProMinent Dosiertechnik GmbH Im Schuhmachergewann 5 - 11 69123 Heidelberg Telephone: +49 6221 842-0 Fax: +49 6221 842-419 email: [email protected] Internet: www.prominent.com 986903, 1, en_GB © 2011 282 Supplemental instructions Further applicable documents These operating instructions and supplementary instructions are only valid in combination with the following operating and supple‐ mentary instructions: n Multi-channel measuring and control system operating instruc‐ tions DULCOMARIN® II Swimming Pool Controller and Disin‐ fection Controller DXCa Part 1: Assembly and installation n Multi-channel measuring and control system operating instruc‐ tions DULCOMARIN® II Swimming Pool Controller and Disin‐ fection Controller DXCa Part 2: Operation 283 Supplemental instructions 284 Table of contents Table of contents 1 Identity code...................................................................... 286 2 About this device............................................................... 288 2.1 Safety chapter........................................................... 288 2.2 Storage and transport............................................... 288 3 Assembly and installation................................................. 3.1 Repairs (fuse change only)....................................... 3.2 Arrangement of LEDs............................................... 3.3 Example for connection of a solenoid valve............. 4 Technical data................................................................... 294 289 291 292 293 285 Identity code 1 Identity code The identity code describes the external modules for the DULCOMARIN® II, series DXM Only the M module of mounting type ‘W’ ‘Wall mounting’ can be ordered with operating elements and with different languages. DXMa External modules for the DULCOMARIN® II, series DXM Module: M M module, measuring module: pH, redox, temperature A A module, control module: 3 pumps and 4 analog outputs R R module, control module: Chlorine gas metering device with feedback 1) 2) N N module, power supply module without relay 1) 2) P P module, power supply module without relay, only mounting type ‘0)’ I I module, current input module, 3 mA inputs, 2 digital inputs 2) Mounting type: 0 Without housing, only P-module (IP 00) W Wall mounted (IP 65) H Mounting rail (IP 20) E Upgrade module (insert module for DXCa, IP 20) Version: 0 With controls 2 Without controls 3 Without controls (only mounting type ‘E’ ) Application: 0 Standard S Swimming pool (only m module) Language: 00 No controls 2) DE German EN English ES Spanish FR French IT Italian Certification: 286 00 No certification, only P-module without housing 01 CE mark Identity code only mounting type W wall mounting / 2) only in version ‘2’ without controls 1) 287 About this device 2 About this device The power supply module with relay DXMaP with alarm relay and solenoid valve relay supplies the DULCOMARIN® II compact with mains voltage and allows it to control 3 solenoid valves or hose pumps via pulse frequency e.g. to: n n n n raise / lower the pH value meter disinfectant meter flocculant minimise combined chlorine The DXMaP power supply module has the following outputs: n power relay for alarm output n power relay output for solenoid valve or hose pump (pH correc‐ tion) n power relay output for solenoid valve or hose pump (disinfec‐ tant) n power relay output for hose pump (flocculant) or relay output (minimising of combined chlorine) n one mains input 2.1 Safety chapter CAUTION! Safety when using the P module – – – The DXMaP power supply module with relay must only be used to control alarm horns, solenoid valves and hose pumps as well as to provide the power supply for the DULCOMARIN® II DXCa. The DXMaP power supply module with relay must only be used as part of the DULCOMARIN® II. The installation must only be carried out by techni‐ cally trained personnel. 2.2 Storage and transport CAUTION! Protect the module against moisture and the effects of chemicals, even while still packaged. Store and transport the module it its original packaging. Ambient conditions for storage and transportation: n Temperature: -10 °C ... 70 °C n Max. permissible relative humidity: 95 %, non-condensing (DIN IEC 60068-2-30) 288 Assembly and installation 3 Assembly and installation NOTICE! The installation must only be carried out by technically trained personnel. When assembling and installing this device, observe the instructions in the operating instructions "Multichannel measuring and control system DULCOMARIN® II Swimming Pool Controller and Dis‐ infection Controller DXCa Part 1: Assembly and instal‐ lation". Make the CAN connection according to the "Multi-channel meas‐ uring and control system operating instructions DULCOMARIN® II Swimming Pool Controller and Disinfection Controller DXCa Part 1, Assembly and Installation". Terminal allocation Description Terminal identifier Terminal no. Alarm relay P1 1 Pol Function Alarm horn (control) 2 3 Power relay 1 P2 4 PWM pH-lowerer (control sole‐ noid valve DULCO®flex) 5 Power relay 2 P3 PWM pH-raiser (control) 6 free 7 PWM chlorine PWM ORP PWM alkaline PWM acid Backwashing Power relay 3 P4 8 UV system enable 9 PWM chlorine (control) PWM ORP (control) Heating enable Power supply X1 10 PE 11 N 12 L(1) 289 Assembly and installation A0480 Fig. 1: Terminal Wiring Diagram I. II. Power relay Fuse 0.63 A, slow-acting III. IV. Supply Voltage Alarm (horn) Locate the power supply module in the CAN bus backbone (DUL‐ COMARIN® II DULCO-Net) Power supply module The central unit always contains a power supply module. Number of pools Additional N- or P-mod‐ ules Number of pools Additional N- or P-mod‐ ules 1 - 9 4 2 - 10 5 3 1 11 5 4 2 12 6 5 2 13 6 6 3 14 7 7 3 15 7 8 4 16 8 (Exception: number of pools = 2) 290 Assembly and installation The two LEDS (LED 1 and LED 2) indicate the load of the 24V power supply for the CAN bus. Flash code LEDs power supply monitoring DULCOMARIN® II (N and P module) Operating status LED 1 LED 2 Power Remarks (H2, power) (H3, power) Normal off green < 1.1 A All OK Limit load red off > 1.1 A Insert another power supply module into the loop Overload / short circuit red, flashing off > 1.35 A Check wiring 3.1 Repairs (fuse change only) WARNING! Mains voltage Possible consequence: Fatal or very serious injuries. External fuse necessary. If mains voltage is connected to the device, then the fuse carrier is also under mains voltage. Before working on the device, disconnect the device from the mains voltage and secure to prevent switching back on. NOTICE! The fuse only may be replaced by technically trained personnel. All other repair work may only be carried out by Customer Service. Otherwise, general safety regulations apply. Use only original fuses: Micro fuse 5 x 20 mm, 630 mA, 250 V, slow-acting (Order No. 712030). 291 Assembly and installation 3.2 Arrangement of LEDs A0481 Fig. 2: Arrangement of LEDs 292 Assembly and installation 3.3 Example for connection of a solenoid valve WARNING! External fuse necessary Example for connection of a solenoid valve (or hose pump DULCO®flex DF2a or alpha motor-driven metering pump). A0482 Fig. 3: Example for connection of a solenoid valve I. Fuse 0.63 A, slow-acting II. Mains connection 293 Technical data 4 Technical data Electrical data The DXMaP power supply module with relay contains the 24 V DC, 1 A direct current power supply unit. Power relay for alarm output (P1): n Type of contact: Changeover contact with interference-sup‐ pressed varistors n Load capacity: 250 V AC, 3 A max., 700 VA n Contact lifespan: > 105 switching operations (at 3 A) Power relay output for control variable output or limit value reporting (P2 - P4): n Type of contact: N/O contact with varistors, interference-sup‐ pressed n Load capacity: 250 V AC, 3 A max., 700 VA n Contact lifespan: > 20 x 106 switching operations Nominal voltage (X1): n 90 - 253 V AC (50 / 60 Hz) n Maximum power consumption: 500 mA at 90 V AC // 180 mA at 253 V AC n Internal fusing with: Micro fuse 5 x 20 mm, 630 mA, 250 V, slow-acting n Electrical power consumption: 30 W Degree of protection: IP 20 Ambient conditions: Storage temperature: -10...70 °C 294 Assembly and operating instructions DULCOMARIN® II, R-Module (Control Unit for Chlorine Gas Metering Device) DXMaR A0448 Please enter the identity code of your device here! DXMA _ _ _ _ _ _ _ _ _ _ _ _ _ These operating instructions are only valid in conjunction with the "Operating instructions DULCOMARIN® II, Part 1: Assembly and installation". Please carefully read these operating instructions before use! · Do not discard! The operator shall be liable for any damage caused by installation or operating errors! Technical changes reserved. 986539 BA DC 075 02/11 EN ProMinent Dosiertechnik GmbH Im Schuhmachergewann 5 - 11 69123 Heidelberg Telephone: +49 6221 842-0 Fax: +49 6221 842-419 email: [email protected] Internet: www.prominent.com 986539, 1, en_GB © 2011 296 Table of contents Table of contents 1 Identity code...................................................................... 298 2 Safety and responsibility................................................... 300 3 Handling the device.......................................................... 301 4 Terminal Wiring Diagram.................................................. 302 297 Identity code 1 Identity code The identity code describes the external modules for the DULCOMARIN® II, series DXM Only the M module of mounting type ‘W’ ‘Wall mounting’ can be ordered with operating elements and with different languages. DXMa External modules for the DULCOMARIN® II, series DXM Module: M M module, measuring module: pH, redox, temperature A A module, control module: 3 pumps and 4 analog outputs R R module, control module: Chlorine gas metering device with feedback 1) 2) N N module, power supply module without relay 1) 2) P P module, power supply module without relay, only mounting type ‘0)’ I I module, current input module, 3 mA inputs, 2 digital inputs 2) Mounting type: 0 Without housing, only P-module (IP 00) W Wall mounted (IP 65) H Mounting rail (IP 20) E Upgrade module (insert module for DXCa, IP 20) Version: 0 With controls 2 Without controls 3 Without controls (only mounting type ‘E’ ) Application: 0 Standard S Swimming pool (only m module) Language: 00 No controls 2) DE German EN English ES Spanish FR French IT Italian Certification: 298 00 No certification, only P-module without housing 01 CE mark Identity code only mounting type W wall mounting / 2) only in version ‘2’ without controls 1) 299 Safety and responsibility 2 Safety and responsibility NOTICE! Further applicable documents These operating instructions are only valid in conjunc‐ tion with the "Operating instructions DULCOMARIN® II, Part 1: Assembly and installation". All the safety instructions and explanations contained therein must be observed without exception. NOTICE! Correct and proper use – You many only use the DXMaR R module to con‐ trol a servomotor – You many only use the DXMaR R module as part of a DULCOMARIN® II – Any other uses or module conversions are pro‐ hibited WARNING! Danger of malfunctions Only trained personnel may install the DXMaR R module. Only then can it be ensured that all compo‐ nents of the control circuit are matched to each other and operating correctly 300 Handling the device 3 Handling the device Storage and transport CAUTION! Protect the module against moisture and the effects of chemicals, even while still packaged! Store and transport the module it its original packaging. Ambient conditions for storage and transport: n Temperature: -10 °C ... 70 °C n Max. permissible relative humidity: 95 %, non-condensing (DIN IEC 60068-2-30) Assembly and installation WARNING! Danger of malfunctions Only trained personnel may install the DXMaR R module. Only then can it be ensured that all compo‐ nents of the control circuit are matched to each other and operating correctly NOTICE! Terminal Wiring Diagram The wiring diagram can be found at the end of these operating instructions, see Ä Chapter 4 ‘Terminal Wiring Diagram’ on page 302. Create the CAN connection in accordance with the ‘Operating instructions DULCOMARIN ® II, Part 1: Assembly and installation.’ . 301 Terminal Wiring Diagram 4 Terminal Wiring Diagram WARNING! Danger to life due to chlorine gas Large quantities of chlorine gas can escape if an uncontrolled chlorine gas metering device is set to ‘ON’ . Chlorine gas can escape into the swimming pool hall. Possible consequence: Fatal or very serious injuries Measure: Lock the power supply to the chlorine gas metering device to allow for a power failure occurring; do likewise with the power supplies to the booster pump and the circulating pump, to ensure these pumps remain inactive. Power relay outputs Position feedback input Internal opened closed open close External Supply voltage A0449 Fig. 1: Terminal Wiring Diagram 302 Terminal Wiring Diagram Terminal allocation Description Terminal identifier Terminal no. Pol. Function Power relay output 1 P1 1 C Servomotor shut 2 NO 3 NC 4 C 5 NO 6 NC 7 - 8 S 9 + Power relay output 2 Response signal input Electrical data P2 XR Servomotor open Feedback servomotor position Power relay output (P1, P2): n Type of contact: Changeover contact with interference-sup‐ pressed varistors n Load capacity: 250 V AC, 3 A max., 700 VA n Contact lifespan: > 20 x 105 switching operations Position feedback input: XR n n n n n n Galvanically isolated from the power relay contacts Insulation voltage: 500 V Potentiometer to be connected: 0 Ω ... 1 kΩ Accuracy (without potentiometer errors): 1 % of input range Resolution: 0.5 % of input range Manipulating time: min.: 25 s / max.: 180 s 303 Terminal Wiring Diagram 304 Supplementary instructions DULCOMARIN® II Function extension with M, A and P module Please carefully read these operating instructions before use! · Do not discard! The operator shall be liable for any damage caused by installation or operating errors! Technical changes reserved. 985558 Only valid with the complete operating instructions DULCOMARIN® II BA DC 079 04/12 EN ProMinent Dosiertechnik GmbH Im Schuhmachergewann 5 - 11 69123 Heidelberg Telephone: +49 6221 842-0 Fax: +49 6221 842-419 email: [email protected] Internet: www.prominent.com 985558, 1, en_GB © 2012 306 Supplemental instructions General non-discriminatory approach In order to make it easier to read, this document uses the male form in grammatical structures but with an implied neutral sense. It is aimed equally at both men and women. We kindly ask female readers for their understanding in this simplification of the text. Supplementary information Please read the supplementary information in its entirety. The following are highlighted separately in the document: n Enumerated lists Instructions ð Outcome of the instructions Information This provides important information relating to the cor‐ rect operation of the device or is intended to make your work easier. Safety information The safety information includes detailed descriptions of the haz‐ ardous situation. 307 Supplemental instructions 308 Table of contents Table of contents 1 Function MAP................................................................... 310 2 Circulation quantity allocation........................................... 311 2.1 Specification of the respective circulating operating conditions.................................................................. 313 3 Flow control [water flow] .................................................. 314 4 Timer settings................................................................... 317 5 Water top-up..................................................................... 319 6 Control of the backwashing valves................................... 320 7 Index................................................................................. 321 309 Function MAP 1 Function MAP Function extension with M, A and P module With the standard modules M, A, and P it is possible to activate the following additional functions: n n n n n Water level (4) with topping up (5) Sensor cap (3) with/without paddle switch (2) Automatic backwashing (1) Heating control (7) Gutter cleaning function (6) 6. 7. 5. 1. 2. 4. 3. A1103 Fig. 1: Function extension with M, A and P module The following software versions (from and including) must be installed so that these functions can be activated: n n n n 310 DXCa 3021 M-Module 3010 A-Module 3010 P-Module 3000 Circulation quantity allocation 2 Circulation quantity allocation The following circulation operating points are specified under this menu item. The setting options in this menu item include: n Normal mode n Backwashing n [ECO min] circulation For an efficient and ecological operation you must match the data of the circulating pump to the analog signal. Configuring module DXMaA System 1 A DXMaA R1 R2 R3 K1 K2 K3 Iout1 Iout2 Iout3 Iout4 Pump terminals Recorder R1: Acid pump Iout1: pH Value Max . freq. = 180 Str/min Iout2 :ORP value K1 type NO Iout3 :free chlorine R2: ORP pump Iout4 :ph lower dosing Max . freq. = 180 Str/min K2 type NO R3: Flocculant pump = 180 Str/min Max . freq. Capacity= 1,40 l/h K3 type NO Circulation SERVICE CONFIG DEFAULT SAVE A0192 Fig. 2: Configuring module DXMaA (configuration menu) 1. In the [continuous display] press the [ENTER] key ð You can now see the [Central menu item]. 2. In the [Central menu item] display press the [F4] [CONFIG] key ð The configuration menu is now displayed. 3. Using the horizontal arrow keys, select the [A] tab and then press the [ENTER] key ð You must now enter your password. 4. Using the arrow keys enter your password and then press the [ENTER] key ð The configuration menu for your A module is now dis‐ played. 311 Circulation quantity allocation Now you must first activate the analog outputs: – – Analog output 2 [Iout2] for circulation 1 (UW1) Analog output 4 [Iout4] for circulation 2 (UW1) System 1 DXMaA R1 R2 R3 K1 K2 K3 Iout1 Iout2 Iout3 Iout4 Pump connectors recorder R1: pH lowering pump Iout1: pH value max. freq. = 180 stroke/min Iout2 : ControlCirculation 1 K1 temp NO Iout3 :Chlorine value R2: chlorine pump Iout4 : ControlCirculation 2 max. freq. = 180 stroke/min K2 Type NO R3: flocculant pump = 180 stroke/min max. freq. Capacity= 1.40 l/h K3 Type NO Circ. 2 CONFIG Circ. 1 SERVICE CONFIG DEFAULT SAVE A1129 Fig. 3: Configuring module DXMaA (configuration menu) 5. If analog output 2 [Iout2] and analog output 4 [Iout4] have not yet been activated for the circulating pumps, this must be done now. Move to the analog output [lout] to be set using the arrow keys and then press the [ENTER] key ð The adjustment display for the analog output [Iout], which is to be set, appears. 6. Using the vertical arrow keys, set the corresponding control output [lout2] or [lout4] [ControlCirculation] (1 or 2) and then press the [ENTER]key ð The configuration menu for your A module is now dis‐ played. 7. Now press the [F5] key [BACK-UP] and answer the following query by pressing the [ENTER] key ð A controller writes the values of the changed parameters into its control. 8. Now press the [ENTER] key ð The configuration menu for your A module is now dis‐ played. 9. Using the [F3] key now select the circulating pump 1 [Parameter circulation 1] or select circulating pump 2 [Parameter circulation 2] using the [F1] key ð You can now see the configuration menu of the selected circulating pump 10. Select the desired parameters using the arrow keys and then press the [ENTER] key Make the following adjustments: n Range: 0-20 mA / 4-20 mA n Value 0/4 mA: minimum circulation capacity of the installed circulating pump 1 or 2 in m3/h n Value 20 mA: maximum value circulation capacity of the installed circulating pump 1 or 2 in m3/h 312 Circulation quantity allocation 2.1 Specification of the respective circulating operating conditions The additional circulating operating conditions: n Circulation capacity normal operation – in %, adjustable 0 ... 100 % n Backwashing circulation capacity – in %, adjustable 0 ... 100 % n ECO Mode min circulation capacity – in %, adjustable 0 ... 100 % n DIN error ➨ Circulation ➨ 100 %: – Active / inactive n [Redox ➨ Circulation (dependency) cor.: inactive] – Active / inactive n Circulation reduction = – in %, adjustable 0 ... 100 % n Circulation reduction time = – 0 ... 9999 seconds CAUTION! Thermal overloading of the pump motor Consequence: The pump motor and its surroundings could be damaged Measure: Provide the pump motor and/or the fre‐ quency converter with a suitable thermal protection switch and possibly a fan. In this respect observe the peculiarities of your local ambient conditions and your national regulations and standards. The operating mode [ECO Mode min. circulation capacity] speci‐ fies how far the circulation capacity of the circulating pumps is reduced in [ECO Mode]. Operating mode [DIN Error ➨ 100%], immediately sets the circula‐ tion operating mode to [normal mode] if the active ECO limit value settings are breached. Otherwise the circulation increases in par‐ allel with the values of the reduction mode. Operating mode [Redox ➨ Circulation (dependency) cor.: active]: In this operating mode, the reduction rate is influenced by the actual redox value Start and end redox values are defined. Reduc‐ tion mode is started from the start Redox value. Reduction mode lowers the circulating pump capacity in steps up until the End redox value the [ECO Mode min] value is reached. If the water redox value falls below the start redox value, then the circulation starts again at 100% capacity. Operating mode [Redox ➨ Circulation (dependency) cor.: inactive]: In this operating mode, the reduction rate [Circulation reduction %] and the time period [Circulation reduction time = seconds ] are set. This reduction [Step reductions] is continued downwards until the set value [ECOMode min] is reached. The operating mode [Circulation reduction in %] in which the time period in [sec] is set. This reduction [Step reductions] is continued until the set [ECO Mode min] value is reached. 313 Flow control [water flow] 3 Flow control [water flow] NOTICE! Alarm during logical checking Cause: Alarm during logical checking. Fault: The flow control reports that a water flow exists, although the circulating pump is off. Measure: The controller triggers an alarm. The flow control must be checked. NOTICE! No flow Cause: No flow in the water circulation system. Fault: There is for example no water in the system or a ball valve is closed. The controller switches the circulating pump off and triggers an alarm. Timer adjustments with two circulating pumps If two circulating pumps are connected, then they must always be started simultaneously via the time. A delayed switching on of the pumps, resulting in switching on at different times, is not permitted because this leads to an error message at the control so that consequently the second circulating pump does not start. Example: Both circulating pumps are stopped by the timer. The pool has status [Stop] and consequently the paddle switch signals are not evaluated by the con‐ troller. If the timer now starts Circulating pump 1, then within 30 seconds paddle switch [1] must deliver feed‐ back relating to the water flow. The paddle switch [2] delivers the signal [no water flow] (which is indeed cor‐ rect), but the control reports the error [No flow]. Hence the circulating pump [2] cannot be automatically started by the timer. Remedy: Adjust the timer so that both circulating pumps are started simultaneously. This prevents one of the two circulating pumps from not starting. The flow control [Water flow] monitors the circulating pump flow. The [Flow Control] is used with a paddle switch or a thermo switch. The [Water flow] flow control should prevent running dry of the system or delivery from the circulating pump against a closed gate valve. If the [water flow] flow control is activated in the A module, then a closed [NC] contact is necessary, to make possible contin‐ uous operation of the circulation. The two core cable of the flow checking device (paddle switch or thermo switch) must be connected in the A-module to the [R2] ter‐ minal. If the contact remains set on [passive] during circulating pump control, then the circulating pump is stopped after a delay period and the control produces an error message. This error mes‐ sage can only be deleted in manual operating mode. 314 Flow control [water flow] System 1 DXMaA R1 R2 R3 K1 K2 K3 Iout1 Iout2 Iout3 Iout4 Pump connectors recorder R1: free Iout1: pH value K1: Liquid level Iout2 : ControlCirculation 1 K1 Type:NC Iout3 :Chlorine value Time: 30 s Iout4 : ControlCirculation 2 free R2: K2 Water_flow_1 K2 Type: NC R3: free K3 Water_flow_2 K3 Type NC Circ. 2 CONFIG Circ. 1 SERVICE CONFIG DEFAULT SAVE A1130 Fig. 4: R1, R2 and R3 to [free] and K1 type, K2 type and K3 type to [NC] Necessary parameters of the terminals and relays Relay Terminal Terminal type K1 type NC K2 type NC K3 type NC R1 free K1 R2 free K2 R3 free K3 Water_flow_1 System 1 A DXMaA R1 R2 R3 K1 K2 K3 Iout1 Iout2 Iout3 Iout4 Pump terminals Recorder R1: Acid pump Iout1: pH Value Max . freq. = 180 Str/min Iout2 :ORP value K1 type NO Iout3 :free chlorine R2: ORP pump Iout4 :ph lower dosing Max . freq. = 180 Str/min K2 type NO R3: Flocculant pump = 180 Str/min Max . freq. Capacity= 1,40 l/h K3 type NO Circulation SERVICE CONFIG DEFAULT SAVE A0192 Fig. 5: Configuring module DXMaA 1. In the [continuous display] press the [ENTER] key ð You can now see the [Central menu item]. 2. In the [Central menu item] display press the [F4] [CONFIG] key ð The configuration menu is now displayed. 3. Using the horizontal arrow keys, select the [A] tab and then press the [ENTER] key ð You must now enter your password. 315 Flow control [water flow] 4. Using the arrow keys enter your password and then press the [ENTER] key ð The configuration menu for your A module is now dis‐ played. 5. Select the desired parameters to be changed using the arrow keys and then press the [ENTER] key ð The adjustment display for the parameter to be set appears. 6. Using the vertical arrow keys enter the corresponding value and then press the [ENTER] key ð The configuration menu for your A module is now dis‐ played. 7. Now press the [F5] key [BACK-UP] and answer the following query by pressing the [ENTER] key ð A controller writes the values of the changed parameters into its control. 8. Now press the [ENTER] key ð The configuration menu for your A module is now dis‐ played. 9. 316 Repeat this process for all parameters that are to be changed. Timer settings 4 Timer settings Cause: Timer setting, this means the circulation is only active if the operator activates this circulation for bathing/swimming operation. The operating status of your overall system can change at any time during the automatic operation of the controller. In this respect for example, the circu‐ lating pump, heating etc., can start or stop at any time. The functions and operating times, circulation and backwashing can be set at any time using via the timer setting. In operating mode [Actuator module] under [Options], in operating mode [Circulation] the various timer adjustments can be made by activating circulation. When setting the timer, you must check that you save the settings after each timer adjustment. If timers 1 ... 6 are set and then saved, then only timer 6 is saved. There are 12 timer functions available for a pool circuit: n Timer 1 ... 6 when using Circulation 1 n Timer 7 ... 12 when using Circulation 2 Timer configuration Timer adjustments with two circulating pumps If two circulating pumps are connected, then they must always be started simultaneously via the time. A delayed switching on of the pumps, resulting in switching on at different times, is not permitted because this leads to an error message at the control so that consequently the second circulating pump does not start. Example: Both circulating pumps are stopped by the timer. The pool has status [Stop] and consequently the paddle switch signals are not evaluated by the con‐ troller. If the timer now starts Circulating pump 1, then within 30 seconds paddle switch [1] must deliver feed‐ back relating to the water flow. The paddle switch [2] delivers the signal [no water flow] (which is indeed cor‐ rect), but the control reports the error [No flow]. Hence the circulating pump [2] cannot be automatically started by the timer. Remedy: Adjust the timer so that both circulating pumps are started simultaneously. This prevents one of the two circulating pumps from not starting. 1. In the [continuous display] press the [ENTER] key ð You can now see the [Central menu item]. 2. In the [Central menu item] display press the [F4] [CONFIG] key ð The configuration menu is now displayed. 3. Using the horizontal arrow keys, select the [A] tab and then press the [F2] key [OPTION] ð You must now enter your password. 317 Timer settings 4. Using the arrow keys enter your password and then press the [ENTER] key ð You can now see the configuration menu of the A module [OPTION] 5. Select the desired file card [Circ.] using the horizontal arrow keys and then press the [ENTER] key ð You can now see the file card [Circ.] Circ. Timer Interval : Timer type : Start time : Reduction time : Backwash time : Mo. Backwash 1 2 : 00 s 0s 120 s=2min INFO Timer 1 - 6 for : Circ 1 and Backwash 1 Timer 1 - 12 for : Circ 2 and Backwash 2 CLEAR SAVE Fig. 6: A1105 A1105 6. Using the horizontal arrow keys, you can now select the desired timer (1 ... 12) 7. Using the vertical arrow keys, you can now select the desired parameters dependent on the selected [Timer Type] and select with the [- key]: n [Interval]l – Each weekday – free – Mo. - Fr. – Sa. - Su. – Mo. - Su. n [Timer type] – free – Circulation 1 or 2 – Backwashing 1 or 2 n [Start time] – 0 ... 24 n [Stop time] – 0 ... 24 n [Reduction time] – 0 ... 50 n [Backwashing time] – 0 ... 480 seconds in a total of 33 steps 318 8. Using the [F4] [Delete] key your can delete all entries [Status = free] or using the [F5] [Save] key you can save the entries in the controller Save = [Record parameters!!!] 9. Using the [ESC] key you can now jump back into the menu display up to the [Continuous display] Water top-up 5 Water top-up An automatic water top-up can be carried out in the skimmer or surge water tank using a level contact. Please note that the drinking water connection may not be con‐ nected to the pool circuit. See the corresponding DVGW (German Gas and Water Association) or FIGAWA (German Federal Associ‐ ation of Gas and Water Companies) regulations or your own national regulations. 1. Connect the single-stage level switch in the A module to ter‐ minal [K1 7/8] 2. In configuration on the A module set terminal [R1] to ‘free’ 3. Thereafter terminal [K1] can be activated as a water level 4. If the [TIME] [water level] is set to [0 s], then after 10 seconds constantly at the minimum level, the Level evaluation unit reacts by opening the water supply solenoid valve. After 10 seconds con‐ stantly at the maximum liquid level, the solenoid valve for the water supply is closed. If a [TIME] [water level] of for example [30 s] is set, then for this 30 seconds water continues to be supplied, so that the maximum liquid level is reached after this time. The [TIME] [water level] can be set from 0 ... 480 seconds in steps 5. To actuate a solenoid valve with 230 V, it is necessary to connect this solenoid valve to the PCB of the P module on terminal 2 (with one circulation) or terminal 1 (with two circu‐ lations) 6. Program the configuration menu of this relay using the func‐ tion [Water top-up] ð If water is topped up for longer than 180 minutes the controller enters fault mode and stops the topping up. This this function is active 7. If the control time has elapsed and the controller is in fault mode, then you must press the [F3] key for [Reset] in the A module configuration menu under service [F2]. This restarts water top-up in operating mode [AUTO] 319 Control of the backwashing valves 6 Control of the backwashing valves NOTICE! The default state of the backwashing valves is deener‐ gised (voltage free) Fault: No backwashing is possible if the backwashing valves cannot be controlled. Consequence: The hygiene parameters worsen and the hydraulic resistance of the filter increases. Measure: Regularly check (dependent on the applica‐ tion) the operation of filter backwash. An automatic 6-way valve cannot be used. For backwashing there is, for example, the option of controlling a Besgo® rod valve. To do this, the rod valve must be connected to terminal P3 in the P module. If two circuits are in operation, the second rod valve must be connected to terminal P2. To activate this function, the function [Backwash 1] or [Backwash 2] must be activated in the P module. Setting of the backwashing times is described under Timer set‐ tingÄ Chapter 4 ‘Timer settings’ on page 317. n n n n n 320 Which day or which sequence Which backwashing, 1 or 2 Start time Reduction time Duration of the backwashing backwash time Index 7 Index 1, 2, 3 ... 6-way valve........................................................ A Automatic water top-up...................................... B Backwashing parameters................................... F Filter back-pressure increasing.......................... G General non-discriminatory approach................ H Hygiene parameters worsening......................... N non-discriminatory approach.............................. O Operating status for your complete system........ Q Question: From which software version is MAP possible?................................................... Question: What causes or effects does incor‐ rect backwashing have?..................................... 320 319 320 320 307 320 307 317 Question: What functions does MAP give me?.. Question: What is the purpose of flow control?. Question: What setting options do I have with circulation quantity allocation?........................... Question: What settings can I make at the timer?................................................................. Question: Which parameters can I influence with the circulation operating conditions?.......... Question: Which parameters of the terminals and relays are necessary for flow control.......... S Setting the backwashing times.......................... Skimmer............................................................. Software versions............................................... Surge water tank................................................ T Thermal overloading of the pump motor............ Timer configuration............................................ 310 314 311 317 313 315 320 319 310 319 313 317 310 320 321 Index 322