1
Professional Solution with High Performance
2
System Overview
3Application
4
Technical Data
5Feature
9Structure
14
Dimension and Arrangement
15
Main Components
16
Standard and Certificates
17
Standard Solution
21
Primary Scheme
Professional Solution with High Performance
SEN Plus is a new generation low voltage switchgear based on GEA Plus series, which has significant improvement on system
performance and safety.
SEN Plus has passed full type test according to latest international standards, especially IEC61439-2, IEC/TR3 61641 and IEC60529.
System running continuity and stability are available.
SEN Plus provides safe, efficient and intelligent solution as an integrated low voltage distribution platform.
1
System Overview
SEN Plus has passed full type test according to new IEC standard, delivers high reliability, safety, flexibility, together with intelligence
solution. SEN Plus is the advisable choice for low voltage distribution system.
The System Includes Following Parts:
•Power Center
Reliability
Safety
Main distribution panel, modular construction, rated current up to 6300A.
•Motor Control Center
Intelligence
Motor control center can provide fixed type, plug-in and withdrawable modules for
feeder and motor starter application. The range of module size varies from 4E to 36E.
•Bus-Coupler, Transition Panel, Corner Panel
Optimize busbar connection between panels and transformer.
•Motor Protection Relay
Intelligence motor protection relay can be integrated into motor control center, which
provides comprehensive protection, control, field bus and Ethernet communication function.
•Key Components
High performance distribution and motor control components, includes air circuit breaker
EntelliGuardTM G, M-Pact, MCCB Record Plus and motor starter Surion.
2
Flexibility
Application
• Industrial
• Infrastructure
• Commercial Building
Oil & Gas
Transportation
Office
Automotive
Waste management
Data center
Printing
Water treatment
Warehouses
Pharmaceutical
Power plant
Supermarket
Chemical
Airport
School
Mechanism
Hospital
3
Technical Data
SEN Plus Specification
Standard
Test Report
Type-tested low voltage switchgear and controlgear
combinations (TTA)
IEC61439-2; GB7251.1-2005; IEC60068-2-57; IEC/TR3 61641
KEMA, CCC, IPH, Seismic test, Arc protection
Rated insulation voltage (Ui)
1000V
Rated voltage (Ue)
400V/690V
Rated frequency
50Hz
Rated impulse withstand voltage
8kV
Main busbar
Electrical Data
Main busbar rated current (Ie)
1000-7600A
Short time withstabdard current (Icw)
Up to 100kA
Rated peak withstabard current (Ipk)
Up to 220kA
Vertical busbar
Structure Feature
44
Vertical busbar rated current (MCC)
850-1900A
Short time withstabdard current (Icw)
Up to 100kA
Rated peak withstabard current (Ipk)
Up to 176kA
Height
2200mm
Width
400, 500, 600, 800, 1000, 1200mm
Depth
600, 800, 1200mm
Unit module
1E=25mm
Max modules
80E
Protection degree
IP30-IP54
Internal separation form
Up to form 4b
Enclosure
Hot-dip zinc coated steel sheet, epoxy polyester powder
Feature
Protect Operator and Equipment Effectively
SEN Plus secures high safety level during operation. The arc proof design is able to withstand high pressure inside the enclosure during
arc conditions. RELT reduce hazard in short circuit accident. Internal separation sheets protect the operator against contact with
hazardous parts.
• Arc Protection Design
SEN Plus passed tests under conditions of arcing due to an internal fault
according to IEC/TR 61641:2008-01, satisfied the five safety criteria in standard.
The arcs proof design ensures the enclosure withstand high pressure in arc
condition, and protect the operator on site effectively. Arc proof version is
available for Power Centers as well as for Motor Control Centers with module
sizes from 5E up to 36E.
• Relt Protection
STDB
17 timing options
from 90 to 1000
Milliseconds
In order to protect service personnel against the hazards of short circuits
whilst working on a power distribution system, SEN Plus can provide Reduced
Energy Let-Through (RELT) protection by using EntelliGuard
TM
0.1
G circuit breaker
Iselective
Trips within
50-60 Milliseconds
according to customers' requirement. This allows the air circuit breaker to be
switched to its lowest short-circuit settings on service(40ms), thus limiting the
IRELT
Trips within
40-50 Milliseconds
Seconds (s)
hazards concerned.
IHI Speed
Trips within
40 Milliseconds
0.01
1000
• Separation Sheet
10000
100000
Amps
Internal separation sheet is installed between busbar and equipment
compartment. Finger proof sheets and barriers prevents accidental contacts
with hazardous parts.
5
Feature
High Reliability
With outstanding derating feature, elaborate critical parts, rigid framework, high protection and internal separation level, SEN Plus
switchgear fulfills high customer expectations. • Derating performance
The busbar system and breaker connection part of SEN Plus are optimized,
which ensure very limited derating coefficient. The derating performance is
completely tested according to IEC IEC61439-2 and GB7251.1-2005. High
adaptability and reliability can be achieved.
• Reliable Critical Parts
The critical parts, such as main contact, insulation parts and busbar support,
influence the quality of switchgear directly. The selected critical parts all
passed strict test to ensure satisfying electric and mechanical performance.
• Rigid Frame Construction
The framework is non-welded self-supporting construction, Doors and covers
are made of 2mm sheet steel with powder painted. The maximum degree of
protection is IP54 (according to IEC 60529). The maximum form of internal
separation is up to Form 4b (according to IEC 61439-1).
6
Flexible System
User-friendly design of SEN Plus allows flexible operation and installation. Maintenance free busbar system can be easily connected on
site. Different types of motor control and feeder modules can combine in same column.
• Maintenance Free Busbar System
All jointing points of the busbars are torque set for optimum contact pressure.
By use of washer and spring washers, the connections are maintenance free.
Main busbar separation links are accessible from the front. It is easy to connect
busbar of different panel at site by means of the fish plate.
• Flexible Configuration and Operation
According to specific needs, all available modules (fixed type, plug-in and
withdrawable) can be combined in the same column. The fully withdrawble unit
design allows fast replacement of the modules. A special mechanism allows
full operation of the module while the door is closed. Withdrawable modules
have connected, test, stand by, disconnected and removed position to satisfy
operation requirement.
• Fast and Easy Cabling
The 24 pole auxiliary contact plug is designed to facilitate the easy connection
of the control cabling. Internal separation is up to form 4b. Cable trays for
servicing of all cables are provided as standard.
7
Feature
Intelligence MCC Solution
Intelligence MCC solution combines control, protection, monitor and communication function together, which help customer to reduce
operation cost and shorten system downtime.
• Comprehensive Motor Protection and Control
Function
SEN Plus integrates intelligence motor protection and control devices
(MM200/MM300) in MCC, which provide advanced protection such as
overload, short circuit, phase unbalance and stalled rotor. Multiple motor
control schemes can be easily offered, including DOL, Reverse, Y/Δ and soft
starter. Electronic protection relay is powerful and more reliable.
• System Monitoring and Fault Diagnose
All kinds of system parameters, such as current, voltage, frequency, power
factor and device status, can be measured in time. Motor protection device
will alarm and take proper actions to avoid serious accident happening.
System maintenance times and cost can be reduced. Data analysis and
diagnose function provides accurate and effective information, which help
to eliminate fault rapidly and reduce system downtime.
• Communication Network
Motor protection relay supports multiple protocols, has independent RS485
and Ethernet interface. The information captured from motor protection
relay, electronic trip unit and meters can be accessed by field bus and
Ethernet communication network. Real-time monitoring, remote control and
parameter configuration can be achieved.
8
Structure
Frame
High strength framework, non-welded self supporting construction and
supporting parts are adopted. Basically the frame contains out of just 4 parts:
frame tubes in only two different types, corners and corner connection plates.
The frame tubes, made out of rolled sheet steel, are foreseen of tapped and
punched fastening holes to fix internal parts and covers at intervals at 25mm.
Enclosure
All external covers and doors are made out off 2mm steel sheet with epoxy
polyester painting. Standard color is RAL 7035. The edges of the covers are
bent over and flush mounted to the frame structure by means of spacers and
self tapping screws. Overall dimensions will not increase. The standard covers
are of multi-function and can be mounted at the side or the back of the column.
Screws with cutting rings secures sufficient earthing.
The doors are provided with inside hinges to mount them to the frame. All doors
are prepunched for door locks, instrument plates for auxillary components and
ventilation openings. The opening angle of the doors is 130 degrees.
Frame tubes, structure parts, roof plates, internal covers and partitions sheets
are made of hot-dip zinc coated steel sheets. Front and side covers use epoxy
polyester powder painting. Ferrous parts use electro-galvanic zinc protecting.
Protection has been verified in accordance with IEC 61439-1: Section 10.38.38.2
Severity test A.
Protection degree
The roof construction is multifunctional design. The two standard arrangements
are IP30(ventilated roof plate) and IP40 (closed roof plate). Add on materials
enables a simple upgrade to either IP41 by using a rain canopy with an
additional sealing (for roof and between columns) or to IP54 by using the
rain canopy with an additional rubber sealing (for covers, roof and between
columns).
9
Structure
Busbar System
The main horizontal busbar system, which can be executed as three phase four line or three phase five line system, is located in the
busbar zone at the rear of the column. Double busbar structure are used for the panel whose rated current equal or larger than 5000A.
Rated current of vertical busbar up to 1900A, three or four pole system can be configured. Internal separation sheets divide the busbar
zone from the equipment zone and protect the operator against contact with hazardous parts.
The standard positions are: rear top and rear middle up to 4000A, rear top and rear bottom for 5000 and 6300A. In three-pole busbar
systems, the neutral conductor of the main horizontal busbar system is located at the bottom of the column. In four pole busbar
systems the neutral conductor will be arranged under the phases.
The protection circuit is consisted of protection conductor and conducting structure. PE line runs through the whole panel. The
protection conductor, connected with all components , metal parts and framework, is earthed effectively. 10
Three-pole main busbar
Four-pole main busbar
(Rated current below 4000A)
(Rated current below 4000A)
Three-pole (double) main busbar
Four-pole (double) main busbar
(Rated current 5000,6300A)
(Rated current 5000,6300A)
Power Center
The Power Centre is subdivided in three functional zones: busbar zone, equipment zone and cable zone. The busbar zone is located at
the rear of the column and contains the main horizontal and vertical busbar system. Internal separation sheets are dividing the busbar
zone from the equipment zone and are protecting the operator against contact with hazardous parts. Additional separation sheet
can be provided to segregate the equipment zone from the cable zone. Two sets of busbar can be installed according to application
requirement.
Air circuit breakers are installed in equipment zone, rated current up to 6300A. The equipment zone can contain maximal 2 breakers
per column, rated current up to 2500A. High availability is secured by withdrawable technique for circuit breakers.
SEN Plus can install EntelliGuardTM G or M-Pact air circuit breaker, which are equipped with intelligent trip uint. Comprehensive
protection and control function, such as zone selective interlocking, Reduced Energy Let-through, wave capture and communication,
can be provided. Selectivity, high breaking capacity and reliability are available.
The cable zone is designed for fast and comfortable cabling. Cabling is through preconfigurated copper links. Control cabling through
terminal strips. Cables or busways can enter through the top or from the bottom.
11
Structure
Motor Control Center
The Control Centre is subdivided in three functional zones: busbar zone, equipment zone and cable zone. The busbar zone can be
equipped with maximal two main busbar systems. Standard positions are the top and the middle position. Provisions are taken as
standard to couple the main busbar system to adjacent columns from the front.
The effective stocking density in the equipment zone is 80E (1E=25mm). The standard separation to the busbar zone is by means of
moulded plastic finger proof sheets. Feeder and motor starter units are available for DOL, Reverse, Y/Delta, fuse or fuseless application.
Rated current in feeder circuit can be up to 630A, max control power in motor unit can be up to 220kW. Fixed type, plug-in and
withdrawable modules can be mixed in one column.
The cable zone is situated on the right hand side from the equipment zone. Cable trays for servicing of all cables are provided as
standard.
12
Motor Control Center
• Fixed Type Module
Fixed type module is used for feeder (fuseless) solution. Modules are available to fix three or four poles version of MCCB up to 630A. The
line side of breaker to be connected to VBB by means of rigid copper or cables. The range of module heights varies from 8E to 24E.
• Plug in Module
Plug in module is used for feeder or motor starter application (with fuse or fuseless) . The range of module sizes varies from 4E to 36E.
• Withdrawable Module
Withdrawable module (5E to 36E) can be used for all feeder or motor starter application (with fuse or fuseless). The module is easy to
use, change and maintain. The working status of the module can be indicated in front panel. Multi-function handle and interlocking
mechanism ensure reliability and prevent wrong operation.
Position
Position
Indication
Plug In Contact
Control Circuitinterlock
Control Circuit Switch Of Wormgear Mech
Module Position
Primary
Income
Primary
Outgoing
Connected
On
On
On
On
Inserted
Test
Off
On
On
On
Inserted
Standby
Off
On
On
Off
Inserted
Mech.
Disconnected
Off
Off
Off
Off
Connected
contacts
disconnected
Removed
Off
Off
Off
Off
Outside
the panel
13
Dimension and Arrangement
Power center
Motor control center
2200
2200
2200
2200
400/500/600
600/800/1000
1000/1200
600
200/400/600
SEN Plus Dimension
Width (mm)
Depth (mm)
Height (mm)
Below 2000A
400/500/600
600/800
2200
2500-4000A
600/800/1000
600/800/1000
2200
5000-6300A
1000/1200
1200
2200
Withdrawable
800/1000/1200
600/800
2200
Fixed type
800/1000/1200
600/800
2200
Plug-in
800/1000/1200
600/800
2200
Power center
Motor control center
Arrangement
100mm(*)
600/800/1000/
1200mm
Larger than
1200mm
The column is wall standing type what means that it can be installed at the wall, however, it is advised to keep 100 mm distances from
wall, and keep 500mm from the ceiling.
14
Main Components
Air Circuit Breaker EntelliguardTM G
EntelliGuard™ G is a line of three and four pole devices ranging from 400 to
6400A mp in three basic frames with fault interruption ratings of Up to 150kA,
complying with IEC, CCC, ANS and UL standard. A design offering a unique
combination of high fault current withstand ratings, short fault interruption times
and selectivity. EntelliGuard™ G TU trip unit that enables the circuit breaker with
the latest technology for system safety, reliability, measurement, relaying and
communications using the Modbus or Profibus Protocol.
Air Circuit Breaker M-Pact
Rated from 400 to 4000A, the M-PACT circuit breaker has been designed to meet
the strictest demands in fault detection and protection. The range has been
developed to be aesthetically and technically co-ordinated with other protective
devices. The breaker range has a common height and depth and is available in
both fixed pattern and drawout versions, which can be manually or electrically
operated. Designed to offer multiple mains connection options, it also comes with a
wide range of easy-to-install accessories.
MCCB Record Plus
Rated current from 3 to 630A, Record Plus MCCB is designed for distribution and
control system. Three and four poles, fixed, plug-in and withdrawable type are
available, breaking capacity ranging from 18 to 150kA.The breaker has excellent
current limiting capacity with circle double contact structur. Modularized design,
high reliability.
Intelligent Motor Protection Relay
MM200/300 are digital motor protection and control system, designed for Low
Voltage motor applications. MM200/300 can provide comprehensive protection
function including overload, ground fault, stalled and phase unbalance. The relay
includes high accuracy metering for all AC signals. Current and voltage parameters
are available as total RMS magnitude and angle. MM200/300 utilizes advanced
communications technologies, making it easy and flexible to use and integrate
into new and existing infrastructures. Multiple communication protocols, including
Modbus RTU, Profibus DP, Device net, are compatible.
15
Standard and Certificates
SEN Plus Complies with Following International Standards:
Type Test:
• IEC61439-2 Low-voltage switchgear and control assemblies-Part 2: Power switchgear and controlgear assemblies.
*The modified and updated standard released by International electrical committee in 2009, based on IEC60439 standard.
Special Test:
• IEC60068-2-57 Environment testing-Part 2-57:Test Ff: Vibration-Time history method
*Vibration environment test in horizontal and vertical direction.
• IEC/TR3 61641: 2008-01 Enclosed low-voltage switchgear and controlgear assemblies - Guide for testing under
conditions of arcing due to internal fault
*International arcing fault protection standard.
• IEC60529 Degrees of protection provided by enclosures
*Define IP numbers used to quantify the degree of protection provided by enclosures.
• IEC60068-2-30 Defining resistance to damp and heat
*Wet Heat, 6 cycle with 24 h, 400C, 95 % rel. humidity.
• IEC60068-2-11 Defining resistance to salt mist
*Salt fork, 2 cycle with 24 h, 350C.
16
Standard Solution
Power Center with ACB EntelliGuardTM G
Rated Current
(A)
Frame
3 Poles
4 Poles
Width
(mm)
Depth
(mm)
65kA
Breaking Capacity/400V AC
80kA
100kA
Withdrawable One Breaker: Incomer/Feeder or Buscoupler
1000
1600
2000
2500
3200
4000
5000
6300
1
1
1
2
2
2
3
3
500
600/800
600
600/800
500
600/800
600
600/800
500
600/800
600
600/800
600
600/800
800
600/800
800
800
800
800
1000
800
1000
800
1000
1200
1200
1200
1000
1200
1200
1200
Fixed One Breaker: Incomer/Feeder or Buscoupler
1000
1600
2000
2500
3200
1
1
1
2
2
400
600/800
600
600/800
500
600/800
600
600/800
500
600/800
600
600/800
600
600/800
800
600/800
800
800
800
800
17
Standard Solution
Power Center with ACB EntelliGuardTM G
Rated Current
(A)
Frame
1000
1
1600
1
1000
1
1600
1
1000
1
1600
1
2000
1
2500
2
Width
Depth
(mm)
(mm)
Withdrawable Two Breakers: Incomer Plus Buscoupler
500
600/800
600
600/800
500
600/800
600
600/800
Fixed Two Breakers: Incomer Plus Buscoupler
400
600/800
600
600/800
500
600/800
600
600/800
Fixed/Withdrawable Two Breakers: Two Feeders
600
800
800
800
600
800
800
800
800
800
800
800
800
800
800
800
3 Poles
4 Poles
Breaking Capacity/400V AC
65kA
80kA
Power Center with ACB M-Pact
18
Rated Current
(A)
Frame
1000
1
1600
1
2500
1
3200
2
4000
2
1000
1
1600
1
1000
1
1600
1
2500
1
Width
Depth
(mm)
(mm)
Withdrawable One Breaker: Incomer/Feeder Or Buscoupler
400
600/800
600
600/800
500
600/800
600
600/800
600
600/800
600
600/800
800
800
800
800
800
800
800
800
Two Breakers: Incomer Plus Buscoupler
400
600/800
600
600/800
500
600/800
600
600/800
Fixed Two Breakers: Two Feeders
600
800
600/800
600
600/800
800
600/800
800
600/800
800
600/800
3 Poles
4 Poles
Breaking Capacity/400V AC
65kA
80kA
Motor Control Center
Fixed Modules
Feeder (3 Poles)
Feeder (4 Poles)
Current (A)
Module size (E)
Current (A)
Module Size (E)
160
8
160
8
250
10
250
10
400
10
400
10
630
10
630
10
160
8
160
8
250
10
250
10
400
10
400
10
630
10
630
10
160
8
160
8
250
10
250
10
400
10
400
10
630
10
630
10
400Vac
500Vac
690Vac
Plug-in Modules
Motor Starter Dol
Max Load
(kW)
Motor Starter Reverse
Motor Starter Y/Δ
Feeder (3 Poles)
Feeder (4 Poles)
Module Size
(E)
Max Load
(kW)
Module Size
(E)
Max Load
(kW)
Module Size
(E)
Current
(A)
Module Size
(E)
Current
(A)
Module Size
(E)
4
30
4
30
4
63
4
63
8
400Vac
30
37
5
55
18
55
24
160
8
160
8
55
10
90
24
90
24
400
10
400
10
220
18
630
18
630
18
110
30
110
30
220
30
200
30
690Vac
11
10
11
10
15
18
63
8
63
8
30
10
30
10
75
24
160
8
160
8
75
18
75
18
132
24
400
24
400
24
132
18
160
24
220
36
630
24
630
24
220
18
250
36
250
36
19
Standard Solution
Motor Control Center
Withdrawable Modules
Motor Starter Dol
Max Load
(kW)
Motor Starter Reverse
Motor Starter Y/Δ
Feeder (3 Poles)
Feeder (4 Poles)
Module Size
(E)
Max Load
(kW)
Module Size
(E)
Max Load
(kW)
Module Size
(E)
Current
(A)
Module Size
(E)
Current
(A)
Module Size
(E)
5
30
8
30
10
63
5
63
6
400Vac
30
37
5
55
30
55
30
160
5
160
6
55
18
90
30
90
30
400
10
400
12
220
24
630
10
630
12
110
30
110
30
220
30
200
36
690Vac
20
11
12
11
12
15
18
63
5
63
10
30
12
30
12
75
30
160
10
160
10
75
12
75
12
132
30
400
10
400
12
132
18
160
24
220
30
630
10
630
12
220
30
250
36
250
36
Primary Scheme
Scheme No
01
02
03
04
05
06
Cubical Width (mm)
400
500
600
800
800
1000
Unit Height
80E
80E
80E
80E
80E
80E
Max.Working
Current (A)
1000
2000
2500
3200
4000
6300
MP-800~1000
EntelliGuardTM G
-1000
MP-1600
EntelliGuardTM G
-1000~2000
MP-2500
EntelliGuardTM G
-2500
EntelliGuardTM G
-3200
MP3200~4000
EntelliGuardTM G
-4000~6300
Primary Scheme
Main Equipment
Application
Scheme No
Upper input (output) (three-pole switch)
07
08
09
10
11
Cubical Width (mm)
400
600
800
1000
1200
Unit Height
80E
80E
80E
80E
80E
800
2500
4000
4000
6300
MP800
MP- 1000~2500
EntelliGuardTM G
-1000~2000
MP-3200~4000
EntelliGuardTM G
-2500~3200
EntelliGuardTM G
-4000
EntelliGuardTM G
-5000~6300*
Primary Scheme
Max. Working
Current (A)
Main Equipment
Application
Upper input (output) (quadru-pole switch)
21
Primary Scheme
Scheme No
12
13
14
15
16
17
Cubical Width (mm)
400
500
600
800
800
1000
Unit Height
80E
80E
80E
80E
80E
80E
1000
2000
2500
3200
4000
6300
MP-800~1000
EntelliGuardTM G
-1000
MP-1600
EntelliGuardTM G
-1000~2000
MP-2500
EntelliGuardTM G
-2500
EntelliGuardTM G
-3200
MP3200~4000
EntelliGuardTM G
-4000~6300
Primary Scheme
Max. Working
Current (A)
Main Equipment
Application
Scheme No
Lower input (output) (three-pole switch)
18
19
20
21
22
Cubical Width (mm)
400
600
800
1000
1200
Unit Height
80E
80E
80E
80E
80E
800
2500
4000
4000
6300
MP-800
MP-1000~2500
EntelliGuardTM G
-1000~2000
MP-3200~4000
EntelliGuardTM G
-2500~3200
EntelliGuardTM G
-4000
EntelliGuardTM G
-5000~6300
Primary Scheme
Max. Working
Current (A)
Main Equipment
Application
22
lower input (output) (quadru-pole switch)
Scheme No
23
24
25
26
27
28
Cubical Width (mm)
400
500
600
800
1000
1000
Unit Height
80E
80E
80E
80E
80E
80E
1000
2000
2500
4000
6300
MP-800~1000
EntelliGuardTM G
-1000
MP-1600
EntelliGuardTM G
-1000~2000
MP-2500
EntelliGuardTM G
-2500
MP-3200~4000
EntelliGuardTM G
-3200
EntelliGuardTM G
-4000~6300
Primary Scheme
Max. Working
Current (A)
Main Equipment
Application
Scheme No
Busbar coupling (three-pole switch)
Busbar lifting
29
30
31
32
33
Cubical Width (mm)
400
600
800
1000
1200
Unit Height
80E
80E
80E
80E
80E
800
2500
4000
4000
6300
MP-800
MP-1000~2500
EntelliGuardTM G
-1000~2000
MP-3200~4000
EntelliGuardTM G
-2500~3200
EntelliGuardTM G
-4000
EntelliGuardTM G
-5000~6300
Primary Scheme
Max. Working
Current (A)
Main Equipment
Application
Busbar coupling (quadru-pole switch)
23
Primary Scheme
Scheme No
34
35
36
37
38
39
40
41
Cubical Width (mm)
400
500
600
500
600
600
800
800
Unit Height
80E
80E
80E
80E
80E
80E
80E
80E
1000
1600
1600
1000
1600
1600
2500
2500
MP-1000
EntelliGuardTM G
-1000
EntelliGuardTM G
-1600
MP-1600
EntelliGuardTM G
-1000~1600
MP-1000~1600
EntelliGuardTM G
-1000~2000
MP-2500
EntelliGuardTM G
-2000~2500
MP-1000~2500
EntelliGuardTM G
-1000~2500
Primary Scheme
Max. Working
Current (A)
Main Equipment
Application
Scheme No
MP-1600 MP-1000
Incomer plus Busbar coupling
(three-pole switch)
42
43
Incomer plus Busbar
coupling
(quadru-pole switch)
44
Feeder (Lower or Upper output)
(three-pole switch)
45
Feeder(Lower or
Upper output)
(quadru-pole
switch)
46
47
Primary Scheme
Cubical Width (mm)
Unit Height
Max.Working
Current (A)
Main Equipment
Application
24
800/1000/1200
800/1000/1200
8E
10E
5E
8E
10E
18E
160
630
63
160
400
630
Record Plus
FD160
Record Plus
FE250、FG400、
FG630
Record Plus
FD160
Record Plus
FD160
Record Plus
FG400
Record Plus
FG630
Fixed Feeder (Lower or Upper output)
(three/quadru-pole switch)
Plug-in Feeder (Lower or Upper output)
(three-pole switch)
Scheme No
48
49
50
51
52
53
54
Primary Scheme
Cubical Width (mm)
800/1000/1200
Unit Height
800/1000/1200
8E
10E
18E
5E
10E
6E
12E
160
400
630
160
630
160
630
Record Plus
FD160
Record Plus
FG400
Record Plus
FG630
Record Plus
FD160
Record Plus
FE250, FG400
FG630
Record Plus
FD160
Record Plus
FG400
FG630
Max. Working
Current (A)
Main Equipment
800/1000/1200
Application
Plug-in Feeder (Lower or Upper output)
(quadru-pole switch)
Scheme No
55
56
57
Withdrawable Feeder (Lower or
Upper output) (three-pole switch)
58
59
Withdrawable Feeder (Lower or Upper
output)(quadru-pole switch)
60
61
Primary Scheme
Cubical Width (mm)
Unit Height
Max. Control Power
(kw)
Main Equipment
Application
800/1000/1200
4E
6E
800/1000/1200
5E
8E
800/1000/1200
10E
18E
5E
8E
18E
24E
30
37
55
220
37
75
220
GPS1BHAE~
GPS2BHAU
CL00~CL07
FD160~FE160
CL08 RT2J
FD160~FE160
CK85B
RT2L~RT2M
FE160~FG630
CK95B~CK10C
RT3E~RT5D
GPS1BHAE~
GPS2BHAU
CL00~CL07
FD160 CL08 RT2J
FD160~FE160
CK85B~CK95B
RT2L~RT3E
FE250~FG630
CK95B~CK10C
RT4N~RT5D
Plug-in Motor Direct on line starter with circuit breaker
Withdrawble Motor Direct on line starter with circuit
breaker
25
Primary Scheme
Scheme No
62
63
64
65
66
67
68
69
Primary Scheme
Cubical Width (mm)
Unit Height
800/1000/1200
6E
18E
24E
30
37
55
132
15
GPS1BHAE~
GPS2BHAU
CL00~CL07
FD160~FE160
CL08 RT2J
FD160~FE160
CK85B
RT2L~RT2M
FE250
CK95B~CK10C
RT3E~RT4R
GPS1BHAE~
GPS2BHAR
CL00~CL04
(kw)
8E
800/1000/1200
12E
Max. Control Power
Main Equipment
800/1000/1200
Application
Fixed Motor Direct on line starter with circuit breaker
Scheme No
70
71
72
73
6E
8E
8E
800/1000/1200
10E
12E
24E
30
37
75
GPS1BHAS~
GPS2BHAU
CL04~CL07
FD160
CL07
RT2J
FD160~FE160
CK85B~CK95B
RT2J~RT3E
Fixed Motor Direct on line starter with circuit breaker/Reversible
74
75
76
77
78
Primary Scheme
Cubical Width (mm)
Unit Height
Max. Control Power
(kw)
Main Equipment
Application
26
800/1000/1200
4E
6E
8E
10E
800/1000/1200
18E
24E
30E
5E
8E
10E
30E
30
37
75
90
220
30
37
220
GPS1BHAE~
GPS2BHAU
CL00~CL07
FD160
CL07
RT2J
FD160~FE160
CK85B~CK95B
RT2L~RT3E
FE250
CK95B
RT4N
FE250~FG630
CK10C
RT4R~RT5D
GPS1BHAE~
GPS2BHAU
CL00~CL07
FD160
CL07
RT2J
FD160~FG630
CK85B~CK10C
RT2L~RT5D
Plug-in Motor Direct on line starter
with circuit breaker/Reversible
Withdrawable Motor Direct on line starter
with circuit breaker/Reversible
Scheme No
79
80
81
82
83
84
85
86
87
Primary Scheme
Cubical Width (mm)
Unit Height
Max. Control Power
(kw)
Main Equipment
Application
Scheme No
800/1000/1200
4E
6E
800/1000/1200
18E
24E
30E
10E
18E
24E
30E
36E
30
37
90
220
30
37
45
132
220
GPS1BHAE~
GPS2BHAU
CL00~CL07
FD160
CL07
CL04
RT4LJ
FD160~FE250
CK85B~CK95B
CL06~CL07
RT4LJ~RT4LM
FE250~FG630
CK10C
CK10~CK08C
RT5A~RT5B
GPS1MHAN~
GPS2MHAU
CL25~CL07
CL00~CL04
RT1N~RT2E
FD160
CL07
CL04
RT4LJ
FD160
CK85B
CL06
RT4LJ
FD160~FE250
CK85B~CK10C
CL06~CL10
RT4LK~RT5A
FG400~FG630
CK10C
CK75C~CK08C
RT5A~RT5B
Withdrawable Star-Delta Motor-starter
with circuit breaker
Plug-in Star-Delta Motor-starter
88
89
90
91
Cubical Width (mm)
800
1000
800
1000
Unit Height
80E
80E
80E
80E
30x10=300
30x12=360
30x8=240
30x10=300
FG630/3P
RT20-100A
FK800/3P
RT20-100A
FG400/3P
RT20-100A
FG630/3P
RT20-100A
Primary Scheme
Max.Compersation
Capacity
Main Equipment
Application
Reactive power compensation
Wave-filter type reactive power
compensation p=XL/XC=0.7%
27
REGIONAL OFFICES
BRANCH OFFICES
NORTH
Gurgaon
Chandigarh
Jaipur
Lucknow
GE India Industrial Pvt. Ltd.
5th Floor, Building No.7A
DLF Cyber City, DLF Phase-III
Sector 25 A, Gurgaon
Haryana – 122002
Ph: (0124) 4808000
Fax: (0124) 4226911 / 4226912
GE India Industrial Pvt. Ltd.
SCO No. 72 & 73, First Floor
Sector 8/C, Madhya Marg
Chandigarh-160008
Ph: (0172) 3982908-10
Fax: (0172) 3982905
GE India Industrial Pvt. Ltd.
448, 4th Floor, Ganapati Plaza
M.I. Road, Jaipur-302001
Ph: (0141) 5112802
Fax: (0141) 2389012
GE India Industrial Pvt. Ltd.
101, Ace Business Center
19, Vidhan Sabha Marg
Lucknow-226001
Ph: (0522) 3203808, 3012444/666
Fax: (0522) 4045909
Bangalore
Chennai
Coimbatore
Cochin
Hyderabad
GE India Industrial Pvt. Ltd.
The Millenia, Level-6, Tower B
1 & 2, Murphy Road, Ulsoor
Bangalore-560008
Ph: (080) 41434000
Fax: (080) 41434199
GE India Industrial Pvt. Ltd.
Temple Tower, 6th Floor
476, (New No. 672) Anna Salai
Nandanam
Chennai-600035
Ph: (044) 45070470-84
Fax: (044) 45070474
GE India Industrial Pvt. Ltd.
No.36/6 & 7, 1st Floor
Ashirwad Building
D.B.Road, R.S. Puram
Coimbatore-641002
Ph: (0422) 4393520 / 4393529
GE India Industrial Pvt. Ltd.
Mayur Business Center & Motel
Chittur Road, Pullepadi Junction
Cochin-682035
Ph: (0484) 2364139
Fax: (0484) 4031400
GE India Industrial Pvt. Ltd.
5-2-45, Hyderbasti, RP Road
Near Gujarati High School
Secunderabad-500003
Ph: (040) 27543162, 66311264
Fax: (040) 66339272
Mumbai
Ahmedabad
Pune
GE India Industrial Pvt. Ltd.
361/362, Solitaire Corporate Park
M. Vasanji Road, Chakala
Andheri (E), Mumbai-400093
Ph: (022) 40101610
Fax: (022) 40101611
GE India Industrial Pvt. Ltd.
405-406, Kirtiman Complex
Kinariwala House, Behind Citibank
Off C.G. Road, Ahmedabad-380006
Ph: (079) 65427385/65427389
Fax: (079) 26460637
GE Money Financial Services Limited
Shop No. 405-410, 4th Floor
City Point, Dhole Patil Road
Pune-411001
Ph: (020) 41266999
Fax: (020) 41266109
SOUTH
WEST
0112/CAT/SENPLUS
EAST
Kolkata
GE India Industrial Pvt. Ltd.
Horizon Building, 4th Floor
57, Chowringhee Road
Kolkata-700071
Ph: (033) 40034056
Fax: (033) 40034071
We are committed to continuous development and improvement of our products and the specifications are
subject to change without notice. For product availability and latest prices, please contact GE Sales Team.
For any further information, visit us at http://www.geindustrial.com
g and General Electric are registered trade marks of General Electric Co. USA
©
Works:
GE India Industrial Pvt. Ltd.
Plot No. 42/1 & 45/14
Electronic City - Phase II
Bangalore-560100
Ph: (080) 41113000
Fax: (080) 28528469/552
HO:
GE India Industrial Pvt. Ltd.
The Millenia, Level-6, Tower B
1 & 2, Murphy Road, Ulsoor
Bangalore-560008
Ph: (080) 41434000
Fax: (080) 41434199
Email: [email protected]
Toll Free No:
18001024343
Customer Care:
[email protected]

Similar documents

Spectronic SP Air Circuit Breaker

Spectronic SP Air Circuit Breaker Spectronic SP Air Circuit Breaker Protecting people, property & productivity

More information

Brochure - GE Industrial Solutions

Brochure - GE Industrial Solutions • Link modules for mechanical and electrical connection of the manual motor starter and the M / CL contactor range • Base plates for Din rail and busbar adapters • Wiring kits for reversing app...

More information