Vigilohm System - engineering site
Transcription
Vigilohm System - engineering site
423E0000_Guilding.fm Page 4 Lundi, 24. juillet 2006 9:35 09 Insulation monitoring Vigilohm Catalogue 2006 0 The Guiding System, the new way to create your electrical installations A comprehensive offer of products with consistent design The Guiding System is first and foremost a Merlin Gerin product offer covering all electrical distribution needs. However, what makes all the difference is that these products have been designed to operate togheter: mechanical and electrical compatibility, interoperability, modularity, communication. Thus the electrical installation is both optimised and more efficient: better continuity of supply, enhanced safety for people and equipment, guaranteed upgradeability, effective monitoring and control. Tools to simplify design and implementation With the Guiding System, you have a comprehensive range of tools - the Guiding Tools - that will help you increase your product knowledge and product utilisation. Of course this is in compliance with current standards and procedures. These tools include technical booklets and guides, design aid software, training courses, etc. and are regularly updated. For a genuine partnership with you Because each electrical installation is unique, there is no standard solution. With the Guiding System, the variety of combinations allows for genuine customisation solutions. You can create and implement electrical installations to meet your creative requirements and design knowledge. You and Merlin Gerin’s Guiding System form a genuine partnership. For more details on the Guiding System, consult www.merlin-gerin.com 180E1000_Ver3.1.fm Page 1 Lundi, 24. juillet 2006 11:25 11 0 A consistent design of offers from Medium Voltage to Low Voltage All Merlin Gerin offers are designed according to electrical, mechanical and communication consistency rules. The products express this consistency by their overall design and shared ergonomics. Electrical consistency: Discrimination guarantees co-ordination between the operating characteristics of serial-connected circuit-breakers. Should a fault occurs downstream, only the circuit-breaker placed immediately upstream from the fault will trip. Each product complies with or enhances system performance at coordination level: breaking capacity, Isc, temperature rise, etc. for more safety, continuity of supply (discrimination) or economic optimisation (cascading). The leading edge technologies employed in Merlin Gerin’s Guiding System ensure high performance levels in discrimination and cascading of protection devices, electrodynamic withstand of switches and current distributors, heat loss of devices, distribution blocks and enclosures. Likewise, inter-product ElectroMagnetic Compatibilty (EMC) is guaranteed. Mechanical consistency: Each product adopts dimensional standards simplifying and optimising its use within the system. It shares the same accessories and auxiliaries and complies with global ergonomic choices (utilisation mode, operating mode, setting and configuration devices, tools, etc.) making its installation and operation within the system a simpler process. Direct connection of the Canalis KT busbar trunking on the Masterpact 3200 A circuit breaker. Communication consistency: Thanks to the use of standard Web technologies, you can offer your customers intelligent Merlin Gerin switchboards allowing easy access to information: follow-up of currents, voltages, powers, consumption history, etc. Each product complies with global choices in terms of communication protocols (Modbus, Ethernet, etc.) for simplified integration in the management, supervision and monitoring systems. Guiding Tools for more efficient design and implementation of your installations. 1 180E1000_Ver3.1.fm Page 2 Lundi, 24. juillet 2006 11:25 11 0 SM6 Sepam Masterpact Medium voltage switchboard system from 1 to 36 kV Protection relays Protection switchgear from 100 to 6300 A Trihal MV/LV dry cast resin transformer from 160 to 5000 kVA Evolis MV vacuum switchgear and components from 1 to 24 kV. 2 The Technical guide CAD software and tools These technical guides help you comply with installation standards and rules i.e.: The electrical installation guide, the protection guide, the switchboard implementation guide, the technical booklets and the co-ordination tables all form genuine reference tools for the design of highperformance electrical installations. For example, the LV protection co-ordination guide - discrimination and cascading optimises choice of protection and connection devices while also increasing markedly continuity of supply in the installations. The CAD software and tools enhance productivity and safety. They help you create your installations by simplifying product choice through easy browsing in the Guiding System offers. Last but not least, they optimise use of our products while also complying with standards and proper procedures. 180E1000_Ver3.1.fm Page 3 Lundi, 24. juillet 2006 11:25 11 0 Compact Multi 9 Prisma Plus Protection switchgear system from 100 to 630 A Modular protection switchgear system up to 125 A Functional system for electrical distribution switchboards up to 3200 A Pragma Enclosures for distribution switchboards up to 160 A Canalis Prefabricated Busbar Trunking from 25 to 4000 A PowerLogic Power management Training merlin-gerin.com Training allows you to acquire the Merlin Gerin expertise (installation design, work with power on, etc.) for increased efficiency and a guarantee of improved customer service. The training catalogue includes beginner’s courses in electrical distribution, knowledge of MV and LV switchgear, operation and maintenance of installations, design of LV installations to give but a few examples. This international site allows you to access all the Merlin Gerin products in just 2 clicks via comprehensive range data-sheets, with direct links to: b complete library: technical documents, catalogs, FAQs, brochures… b selection guides from the e-catalog b product discovery sites and their Flash animations. You will also find illustrated overviews, news to which you can subscribe, the list of country contacts… 3 4 423E2000.PM6 16 insulation monitoring monitoring Vigilohm page 1/ presentation 6 2/ functions and characteristics 17 3/ installation and connection 45 4/ catalogue numbers 55 5 423E1000.PM6 5 24/07/06, 9:27 Vigilohm: presentation IO316_123 insulation monitoring and associated functions continuity of supply principle Insulation monitoring is provided on IT systems to detect and indicate insulation faults as soon as they occur. The basic function is carried out by an Insulation Monitoring Device (IMD), also referred to in certain documentation as a permanent or continuous insulation monitor (PIM or CIM respectively). The monitoring device injects a DC or low-frequency AC voltage between the installation and earth. The insulation resistance is determined from the resulting current. This technique can be used on all types of installations: AC, DC, rectified, mixed AC/DC, etc. DB100664 Continuity of supply is a need that must always be satisfied by electrical installations, along with the protection of life and property. The IT system provides the best guarantee in terms of continuity of supply. Even when a first insulation fault is present, the installation can continue to supply power without endangering human life. The first fault must however be detected and repaired before a second fault occurs. measuring, indicating and locating insulation faults Vigilohm System, with or without a communication bus, fulfils the following basic functions: c measurement of insulation level on all types of installations c manual or automatic locating of insulation faults. Vigilohm System with a communication bus The communication bus adds the following possibilities: c measurement of the insulation resistance and earth leakage capacitance of each circuit c centralisation of fault locating measurements on the IMD display units c communication with a supervisor (transmission of measurements and reception of settings). 6 423E1010.PM6 6 24/07/06, 9:27 Vigilohm: presentation Vigilohm System with or without a communication bus Vigilohm System without a communication bus Vigilohm System with a communication bus DB100955 DB100662 supervision and event logging printer supervisor interfaces XAS XLI300 XAS MERLIN GERIN XTU300 MERLIN GERIN MERLIN GERIN vigilohm system XLI300 vigilohm system XAS d faut vigilohm system XTU300 d faut d faut insulation monitoring XML308/316 XM300c MERLIN GERIN MERLIN GERIN vigilohm system XM300c vigilohm system XML316 test test 3 4 5 6 7 8 1 2 9 10 11 12 13 14 15 16 valeur d'isolement 040 K MENU TEST valeur d'isolement 040 K MENU TEST insulation fault detection and locating XD301 XL308 / 316 XD308c XRM XD312 MERLIN GERIN MERLIN GERIN vigilohm system XD308c vigilohm system XL316 test test MERLIN GERIN vigilohm system XD301 1 2 3 4 5 6 7 8 9 MERLIN GERIN 1 reset 4 5 6 7 8 on 3 4 5 6 7 8 1 2 9 10 11 12 13 14 15 16 test test reset M 10 11 12 M 50507 3 vigilohm system XD312 test 2 reset P12 on 50536 test/reset P50 P100 M M MERLIN GERIN vigidix RM 10N sensors MERLIN GERIN GO S1 S2 MERLIN GERIN PO S1 MERLIN GERIN vigirex - vigidix S2 MERLIN GERIN vigirex - vigidix MERLIN GERIN vigirex - vigidix 7 423E1010.PM6 7 24/07/06, 9:28 Vigilohm: presentation Vigilohm System without a communication bus DB100650 Vigilohm System without a communication bus insulation monitoring E18812 This solution offers: c automatic fault detection; c accurate measurements of the insulation level for all types of installations. Insulation monitoring devices inject a DC or low-frequency AC voltage between the installation and earth. The insulation resistance is determined by measuring the resulting leakage current. c Vigilohm EM9 devices use an indicator light to signal the presence of an insulation fault within the installation. They are modular devices (Multi 9 format) designed for small installations or sub-systems isolated from earth; c the TR22A and TR22AH (for hospitals) devices detect insulation faults and, in addition, continuously indicate the value of the insulation resistance on a digital display; c the XM200 is part of the Vigilohm System range and can be associated with automatic fault locating devices. TR22A MERLIN GERIN vigilohm TR 22A K E27136 test The failure of a motor to start can have serious consequences. This is especially true in the following applications: c safety equipment (fire pumps, smoke extractors, etc.); c production (glass works, cement plants, etc.); c manufacturing processes (rolling mills, etc.). Motors often fail to start due to insulation problems caused by the humidity that accumulates in the microscopic cracks of the insulation during periods when the motor is not running. The SM21 device monitors the insulation of critical motors while they are off-line. Insulation faults give rise to an alarm or motor starting lock-out. SM21 E27112 off-line insulation monitoring 1 7 6 5 4 3 2 MERLIN GERIN vigilhom SM21 AL. REL. OK 1,5 8 Sa 9 MΩ on 7,5 10 0,5 2,0 0,25 test 5,0 1,5 1,75 1,0 0,5 off 3,0 2,0 1,25 1,0 0,75 50761 Sp 10 11 12 13 AL. REL. 14 8 423E1020.PM6 8 24/07/06, 9:28 Vigilohm: presentation Vigilohm System without a communication bus Manual fault locating Manual fault locating The fault is located by testing different points in the installation, one after another, using a Vigilohm System XRM mobile receiver and a current probe. The receiver captures the low-frequency fault locating signal. Two cases may be encountered: c the installation is equipped with an XM200 or XM300C insulation monitoring device (Vigilohm System). In this case, the manual system is used to fine-tune the results of the automatic locating system c the installation (relatively small or an isolated sub-system) is equipped with an insulation monitoring device for DC injection. In this case, a Vigilohm XGR portable generator is used together with an XRM receiver. XM300C MERLIN GERIN vigilohm system XM100 test valeur 040 K TEST MENU P50 P100 P12 on d'isolement MERLIN GERIN v ig id ix RM 10N XRM DB110935 Once detected, an insulation fault must be located and eliminated in order to guarantee maximum continuity of supply. DB100950 fault locating XGR P12 on P50¥ P100 MERLIN GERIN ix vigid RM 10N XRM Automatic fault locating E27110 Automatic locating: For easy locating of insulation faults, the Vigilohm System makes it possible to combine the XM200 insulation monitoring device with: c XD301/XD312 fault detectors to monitor the different circuits of the installation; c XRM receivers for mobile fault locating. XM200 MERLIN GERIN vigilohm system XM200 test R C Sp Sa S menu ok test XD312 1 2 3 4 5 6 7 8 9 MERLIN GERIN vigilohm system XD312 test M 10 11 12 reset 50536 M P12 on P50 P100 MERLIN GERIN vigidix RM 10N XRM 9 423E1020.PM6 9 24/07/06, 9:28 Vigilohm: presentation Vigilohm System with a communication bus DB100956 Vigilohm System with a communication bus The communication bus adds the following possibilities: c communication with a supervisor (transmission of measurements and reception of settings) c measure the insulation resistance and earth leakage capacitance of each circuit c centralisation of the locator measurements on the insulation monitoring device displays. supervision and event logging supervisor printer interfaces XLI200/XLI300 XAS MERLIN GERIN XTU300 MERLIN GERIN MERLIN GERIN vigilohm system XLI300 vigilohm system XAS défaut vigilohm system XTU300 défaut défaut insulation monitoring XML308/316 XM300c MERLIN GERIN MERLIN GERIN vigilohm system XM300c vigilohm system XML316 test test 3 4 5 6 7 8 1 2 9 10 11 12 13 14 15 16 valeur 040 K TEST d'isolement valeur 040 K TEST MENU d'isolement MENU insulation fault detection and locating XD301 XRM XD312 XD308c XL308 / 316 MERLIN GERIN MERLIN GERIN vigilohm system XD308c vigilohm system XL316 test test MERLIN GERIN vigilohm system XD301 1 2 3 4 5 6 7 8 9 MERLIN GERIN 1 3 4 5 6 7 8 on 3 4 5 6 7 8 1 2 9 10 11 12 13 14 15 16 test test reset M 10 11 12 reset 2 vigilohm system XD312 test M 50507 reset P12 on 50536 test/reset P50 P100 M M MERLIN GERIN vigidix RM 10N sensors MERLIN GERIN GO S1 S2 MERLIN GERIN PO S1 MERLIN GERIN vigirex - vigidix S2 MERLIN GERIN vigirex - vigidix MERLIN GERIN vigirex - vigidix communication features E17057 insulation monitoring and associated functions In addition to displaying the insulation values it measures for the installation as a whole, an insulation monitoring device can also provide a centralised display for information concerning specific circuits. It receives this information from communicating insulation fault locators and detectors distributed throughout the installation. All this information may also be transmitted to a remote supervisory system. These communication features satisfy the operating requirements of modern electrical installations. All information concerning the insulation can be transmitted via a communication bus for display on a centralised insulation monitoring device or to a supervision system for centralised processing and management. Prevention is the best way to ensure the continuity of supply of electrical installations. It may be applied in two ways: c the insulation monitoring device signals a drop in the insulation resistance below a non-critical prevention threshold determined by the user; c the measurements are transmitted to a supervisor, which can then process them to predict insulation faults on ageing cables. These indications can be used to schedule preventive maintenance. centralisation on an IMD local display measurements E17059 prevention of insulation faults centralisation on a supervisor preventive level fault level fault prevention 10 423E1030.PM6 10 24/07/06, 9:28 Vigilohm: presentation Other functions c measurement of the true insulation resistance c measurement of the earth leakage capacitance c indication of transient faults c prevention alarm when the insulation resistance falls below a non-critical threshold determined by the user; c remote interrogation and display, from the insulation monitoring device, of faults detected by the fault locators c setting of alarm thresholds from a supervisor easier operation of IT systems An installation implementing the IT system, i.e. isolated from earth or connected to earth through a sufficiently high impedance, gives top priority to continuity of supply. Today, the operation of such installations can be greatly facilitated by the use of devices that offer functions going far beyond the simple fault signalling imposed by standards. ... with Vigilohm System MERLIN GERIN vigilohm system XM200 test Sa Sp C R S menu test ok XD312 MERLIN GERIN 1 2 3 4 5 6 7 8 9 vigilohm system XD312 test M reset 10 11 12 50536 M The system evolves with the needs of the installation. New devices can be added at any time to adapt to installation modifications or provide higher levels of monitoring. insensitivity to electrical disturbances The Vigilohm System offers both measurement accuracy and insensitivity to electrical disturbances. Designed to operate on modern installations, it is not affected by the harmonics generated by loads such as variable speed drives, UPSs and switchmode power supplies. E20123 principle and functions Fault locating is the main function associated with insulation monitoring. Toroids placed on the various circuits capture a signal proportional to the current injected by the insulation monitoring device. This signal is transmitted to fault detection and locating devices which automatically identify any faulty circuit. XM200 c ... Vigilohm System is a range of Merlin Gerin products meeting the needs of IT systems in terms of performance, practical operation and continuity of supply. This range features modular design. It is made up of Insulation Monitoring Devices (IMDs) and fault detection and locating devices. Some of these devices make independent measurements of the insulation resistance on each circuit. In addition, the Vigilohm System can communicate with a supervisor or PLC. The basic device is the Insulation Monitoring Device (IMD). It injects a lowfrequency AC voltage between earth and the installation. Based on a measurement of the resulting current, the Vigilohm System accurately determines the true insulation resistance of the installation and its earth coupling capacitance. This technique can be used on all types of installations: AC, DC, rectified, mixed, etc. E20122 Vigilohm System: general information From automatic fault locating with local display ... insulation resistance 1.5 KΩ TEST MENU XM300c MERLIN GERIN MERLIN GERIN vigilohm system XM300c vigilohm system XLI300 test valeur 1,5 K TEST XLI300 d'isolement défaut supervisor insulation valeur d'isolement resistance K 1,5KΩ 1.5 MENU XL316 Distributed measurements of the insulation resistance and the earth leakage capacitance are possible on each circuit via the toroids used for fault locating. MERLIN GERIN vigilohm system XL308c test 3 4 5 6 7 8 1 2 9 10 11 12 13 14 15 16 test/reset Centralisation on a supervisor. Via a communication bus using JBUS protocol, the Vigilohm System can forward all measurements, information and events to a supervisor. In this way, the supervisor maintains full knowledge on the insulation status of the overall installation and the individually monitored circuits. The supervisor (or PLC) can be connected to a printer to log all events occurring on the installation, complete with location and timestamp. Adaptation to variable installation configurations. The system automatically excludes all but one insulation monitoring device connected to the same set of busbars. ... to distributed measurements with centralised display 11 423E1030.PM6 11 24/07/06, 9:28 Vigilohm: presentation Vigilohm System: choosing the system architecture what devices make up the system? how to choose the right system? c XM200 and XM300C insulation monitoring devices inject a signal that is used by the detection and locating devices; c XL308 and XL316 locators, connected to 8 or 16 toroids, measure the insulation resistance of each circuit (distributed measurements) and, in the event of a fault, automatically identify the faulty circuit. They can transmit this information to a supervisor; c XML308 and XML316 monitoring-locating devices combine the monitoring and locating functions in a single unit; c the XD308C communicating insulation fault detector automatically identifies the faulty circuit and transmits this information to a supervisor; c XD301 and XD312 non-communicating insulation fault detectors automatically identify the faulty circuit; c the XRM mobile receiver can be used to fine-tune the automatic locating results by identifying the faulty circuit at the final distribution level; c XLI200, XLI300 and XTU300 interfaces make communication possible between the Vigilohm System and a supervisor; c the XAS interface is used to supply power to the communication bus. The right system can be chosen in four steps, described in detail below: 1. define the required level of locating and measurement performance. 2. select the corresponding locating and measurement devices. 3. select the insulation monitoring devices compatible with the locating and measurement devices. 4. check whether or not an interface is required. Note: connect the insulation monitoring device to a PHT1000 subassembly if the installation voltage U is: A contact is provided for remote indications, v automatic fault locating with centralised display The faulty circuit is identified and indicated on the front face of the fault detector. The information is also transmitted to a supervisor or a PLC, v distributed measurements with local display c 760 < U < 1700 V AC (neutral distributed); c 440 < U < 1000 V AC (neutral not distributed); Faults are located and displayed locally. A contact is provided for remote indications, c 550 < U < 1200 V DC (DC or rectified voltage). v distributed measurements with centralised display 1 level of locating and measurement performance According to your need, select one of the five possibilities listed in part 1 of the table. The insulation measurement for each circuit and the indication of the faulty circuit are displayed on the front of the device and transmitted to a supervisor or PLC. The choice depends on: 2 selection of the locating and measurement devices c the required performance of the locating system to be associated with the fault detection function; On the line selected in part 1, select the fault locating or distributed measurement device in part 2 of the table. c the need for independent insulation measurements on each circuit. 3 selection of the insulation monitoring device The five possibilities are (in increasing order of performance): Similarly, determine the insulation monitoring devices, in part 3 of the table, that are compatible with the selected locating and measurement devices. The fault is located using a mobile receiver connected to a current probe placed at different points in the installation one after another. This type of system is recommended as an enhancement to the automatic system in order to determine the faulty portion of a circuit on which an insulation fault has been detected. 2 4 necessity of an interface For the column selected in part 2 of the table, part 4 indicates whether or not an interface is required. If required, the interface will be selected according to the installation and the devices making up the system. See the page entitled "choosing the communication interface". locating and measurement devices XRM receiver XD301/302 detector XD308C detector XL308/316 locator c v v c v level of performance c manual fault locating automatic fault locating with local display automatic fault locating with centralised display distributed measurements with local display distributed measurements with centralised display 3 The faulty circuit is identified and indicated on the front face of the fault detector. The devices measure the insulation resistance on each circuit independently. These measurements can be read on the front face of the device. v manual fault locating 1 v automatic fault locating with local display c c insulation monitoring device c v v XM200 XM300c XML308/316 XAS, XLI200, XLI300, XTU300 interfaces c v v c v c c c c 4 c device providing only the required function v device offering additional possibilities or higher performance. 12 423E1040.PM6 12 24/07/06, 9:28 Vigilohm: presentation Vigilohm System: choosing the fault locating system level 3: automatic fault detection, locating and measurement. level 4: automatic fault detection, locating and measurement with transmission to a supervisor. E24548 E24547 The Vigilohm System offers four fault locating performance levels. level 1: automatic fault detection and locating. level 2: automatic fault detection and locating with transmission to a supervisor. XM200 interface supervisor Manual fault locating with the XRM mobile receiver is generally used to fine-tune the automatic locating results. IMD printer MERLIN GERIN vigilohm system XAS MERLIN GERIN vigilohm system XM300c défaut test valeur d'isolement 040 K MENU TEST MERLIN GERIN vigilohm system XM200 test R Sp C Sa S menu test ok XRM XD312 1 2 3 4 5 6 7 8 9 XD308c XD308c MERLIN GERIN MERLIN GERIN vigilohm system MERLIN GERIN vigilohm system vigilohm system XD308c XD308c XD312 test test M 10 11 12 reset P12 1 P50 P100 2 3 4 5 6 7 8 test 1 on 2 3 4 5 6 7 8 on 50536 M MERLIN GERIN RM 10N reset test reset test level 1: automatic fault detection and locating XRM XD312 MERLIN GERIN P12 XD312 P50 P100 test MERLIN GERIN RM 10N reset E24549 E24550 level 2: automatic fault detection and locating with transmission to a supervisor. XM300c interface supervisor interface XML308/316 printer MERLIN GERIN vigilohm system XAS MERLIN GERIN vigilohm system XML316 défaut test MERLIN GERIN vigilohm system XAS MERLIN GERIN vigilohm system XM300c 3 4 5 6 7 8 1 2 9 10 11 12 13 14 15 16 défaut test valeur 040 K TEST valeur 040 K TEST d'isolement MENU d'isolement MENU XL308/316 XL308/316 MERLIN GERIN vigilohm system MERLIN GERIN XL316 vigilohm system XL308c test test 3 4 5 6 7 8 1 2 9 10 11 12 13 14 15 16 3 4 5 6 7 8 1 2 9 10 11 12 13 14 15 16 test/reset test/reset XD308c XRM XD312 MERLIN GERIN XD308c XD312 XD312 XRM MERLIN GERIN test reset P12 P50 P100 MERLIN GERIN XD312 MERLIN GERIN test RM 10N reset P12 P50 P100 MERLIN GERIN RM 10N level 3: automatic fault detection, locating and measurement level 4: automatic fault detection, locating and measurement with transmission to a supervisor. 13 423E1040.PM6 13 24/07/06, 9:28 Vigilohm: presentation Vigilohm System: choosing a communication interface the power of a communicating system The power of the Vigilohm System lies in the capacity it offers for communication between all its devices, thereby ensuring insulation monitoring and complementary functions such as automatic locating of faults or the anticipation of their occurrence. In addition, the Vigilohm System is capable of communicating with a supervisor or a PLC, i.e. it can both transmit data to and receive data from such units. The transfer of information takes place: c via the internal Vigilohm System bus for communication between the devices; c via the external JBUS for communication with a supervisor or PLC. In both cases, the use of an internal or external bus requires a communication interface. four interfaces The Vigilohm System offers four interfaces: c the XLI200 interface, for the transmission of information from the insulation monitoring device and XD308C detectors to a supervisor or PLC via JBUS. In this way, a PC can access information concerning the presence of faults and the identification of the faulty circuit. This interface cannot be used with XL308/316 or XML308/316 devices and connects only to the XM300C and XD308C (the XLI200 cannot be used with XML monitoring-locating devices or with XL locating devices). c the XLI300 interface, for the transmission of measurements and measurement parameters from the XM300C and XD308C devices to a supervisor. This interface is used on single busbar installations. The exclusion of other insulation monitoring devices found on the same installation is managed automatically; c the XTU300 interface, for communication between the Vigilohm System and a supervisor, like the XLI300 interface. This interface is required for installations with multiple busbars and bus coupler circuit breakers. It manages the exclusion of other insulation monitoring devices found on the same installation and the link between the locators and their corresponding insulation monitoring devices; c the XAS interface, indispensable for the operation of the communication bus in the absence of one of the three other interfaces. interface selection table one XML308/316 device IMD with at least 1 locator + 1 set of busbars ---XLI300 XAS XLI300 IMD with a least 1 locator + several sets of busbars with bus coupling XTU300 XTU300 E20791 E20790A without supervision with supervision IMD associated only with XD308C communicating detectors, whatever the installation configuration ---XLI200 MV/LV MV/LV supervisor or PLC XAS MV/LV XML308 MV/LV XM300c XLI300 XML308 XM300c XL308 XL308 supervisor or PLC DB100957 One set of busbars with supervisor E20792 One set of busbars without supervisor supervisor or PLC MT/BT MV/LV XTU300 XML308 MT/BT MV/LV XM300C XM300C XLI200 XM300c XD308C XD308C XL308 Several sets of busbars with bus coupling and with or without supervisor application of the measurement voltage internal Vigilohm System bus JBUS bus 14 423E1110.PM6 14 24/07/06, 9:28 Vigilohm: presentation E20788 Vigilohm System: two examples of installations MV/LV automatic fault locating with or without supervision MV/LV The following examples cover two typical installation configurations with insulation monitoring and fault locating systems. XM200 XM200 Example 1: c automatic fault locating with local display. The use of an XM200 insulation monitoring device together with XD301 and XD312 detectors represents the typical case providing basic detection and automatic locating of insulation faults on the main feeders as well as on certain secondary feeders. Fault locating can be fine-tuned using an XRM mobile receiver and a current probe to determine the exact location of the fault on the faulty circuit. The auto-exclusion of other XM200 insulation monitoring devices is controlled by the circuit breaker position indication contacts. XD312 XD301 XD301 E20786 XRM Example 2: c measurement and automatic fault locating with local and centralised display, for an installation with more than one set of busbars and a bus coupling circuit breaker. The measurement of the insulation resistance on the main feeders is provided in addition to fault detection with automatic locating (XL308/316 and XML308/316). The secondary feeders are monitored simply by an XD312/301 detector or by an XD308C detector that communicates detected faults to the supervisor (via the XTU300 interface). The architecture of the installation (several sources and sets of busbars) makes it necessary to use an XTU300 interface to handle the exclusion of other insulation monitoring devices and the link between the locators and their corresponding insulation monitoring devices. supervisor or PLC MV/LV MV/LV XML316 XML308 G XTU300 XM300c XL308 XD312 XD308c XRM application of the measurement voltage internal Vigilohm System bus JBUS bus 15 423E1110.PM6 15 24/07/06, 9:28 16 423E2000.PM6 16 24/07/06, 9:28 insulation monitoring Vigilohm 2/ functions and characteristics page choosing an insulation monitoring device for different types of installations and associated functions Vigilhom System XM300C insulation monitoring device XL308 and XL316 insulation fault locators XML308 and XML 316 monitoringlocating devices XD308C communicating automatic insulation fault detector XLI200, XLI300, XTU300, XAS communication interfaces XM200 insulation monitoring device XD301 and XD312 automatic insulation fault detectors XRM mobile fault locating receiver and current probes Vigilohm TR22A and TR22AH insulation monitoring devices EM9 and EM9B insulation monitoring devices EM9BV insulation monitoring device EM9T insulation monitoring device TR5A insulation monitoring device SM21 insulation monitoring device mobile fault locating kit XGR + XRM + probes toroids auxiliaries 18 20 22 24 26 28 29 30 32 33 34 35 36 37 38 39 40 41 43 17 423E2000.PM6 17 24/07/06, 9:28 Vigilohm: functions and characteristics choosing an insulation monitoring device for different types of installations 044147 044148 XM200 XM300C installation characteristics (1) device MV/LV L1 L2 L3 N P1 IMD MV/LV 440 to 1000 V AC* (1) 500 to 1200 V DC* E27427 E27336 Continuity of supply is the requirement that most often leads designers to chose the IT system for an electrical installation. This requirement may apply to the entire installation (e.g. chemical process plant, steel plant, etc.). Such an installation requires continuous monitoring of the insulation level. E27341 IT system for the entire installation PHT 1000 PHT 1000 IMD E27343 IMD MV/LV *with PHT 1000 subassembly i 440 V AC (1) i 500 V DC i 440 V AC (1) i 500 V DC i 440 V AC i 440 V AC i 500 V DC + i 500 V DC 500 to 1200 V DC* – *with PHT 1000 subassembly L1 L2 L3 N IMD - L L+ TN or TT MV/LV L1 L2 L3 N LV/LV IT L1 L2 L3 N IMD E27345 The requirement for continuity of supply may apply to only a part of an installation, for example a single shop or plant, or a circuit subject to special conditions (safety lighting). In this case, it is recommended to use the IT system for this part of the installation, whatever the system used for general distribution. E27344 IT system for part of an installation TN or TT MV/LV L1 L2 L3 machine tool or robot IMD LV/LV IT control/monitoring IT system for DC installations – IMD TR5A + E27339 500 to 1200 V + E27338 500 V E27337 In many cases, the use of direct current corresponds to a need for continuity of supply. The use of an IT system and insulation monitoring is therefore consistent with this choice. IMD – PHT 1000 IMD E27346 off-line insulation monitoring The use of motors in industrial processes creates a further need for insulation monitoring. By checking the insulation with power off, the presence of insulation faults can be determined before starting motors (fire pumps, smoke extractors, etc.). It is also possible to prevent motor starting automatically if the insulation resistance is below a certain threshold. L1 L2 L3 M IMD (1) Phase-to-phase voltage with IMD connected to one phase. Multiply these values by e if IMD is connected to neutral. (2) Installation without frequency converter. 18 423E2010.PM6 18 24/07/06, 9:28 044149 041850 043274 042578 042580 042582 042580 017422 051346 042581 XML 308/316 TR22A TR22AH EM9 EM9B EM9BV EM9T TR5A SM21 i 1 000 V AC (1) with P1 subassembly 440 to 1000 V AC* (1) 500 to 1200 V DC* *with PHT 1000 subassembly i 440 V AC (1) i 500 V DC i 440 V AC (1) i 440 V AC (1) i 440 V AC i 440 V AC i 440 V AC (2) (2) i 440 V AC i 440 V AC i 440 V AC i 220 V AC i 500 V DC 500 to 1200 V DC* i 420 V DC *with PHT 1000 subassembly i 690 V AC 19 423E2010.PM6 19 24/07/06, 9:28 Vigilohm: functions and characteristics choosing an insulation monitoring device and associated functions 044147 044148 installation characteristics device XM200 XM300C injected signal 2.5 Hz 2.5 Hz E27328 IT system for the entire installation MV/LV voltage (1) (2) 440 to 1000 V AC HV/MV i 400 V AC MV/LV with rectifiers (2) 440 to 1000 V AC i 440 V AC for hospitals i 440 V AC high insulation level i 440 V AC low insulation level i 440 V AC control and monitoring of machines i 220 V AC E27329 IT system for part of an installation LV/LV MV/LV E27330 DC installation 24 to 420 V DC + i 500 V DC - (2) 500 to 1200 V DC E27331 off-line monitoring (LV motors) i 690 V AC M communication functions insulation resistance measurement E27332 measurement display kΩ prevention indication insulation fault indication E27333 fault locating manual (4) (4) automatic (6) (7) (8) automatic + fault measurement E27335 communication with supervisor via JBUS communication bus (and interfaces) external BUS (1) Phase-to-phase voltage with IMD connected to one phase. Multiply these values by e if IMD is connected to neutral. (2) With PHT 1000 subassembly. (3) With P1 subassembly. (4) With XRM mobile receiver. (5) With XRM mobile receiver + XGR signal generator 20 423E2020.PM6 20 24/07/06, 9:28 044149 043274 042578 042580 XML 308/316 TR22A TR22AH EM9 EM9B 2.5 Hz DC DC DC DC 042580 042582 017422 051346 EM9BV EM9T TR5A SM21 DC DC NONE DC 042581 041850 (2) (3) (2) (9) (2) (4) (5) (5) (5) (5) (5) (5) (5) (7) (8) (6) With XD301/312 detector. (7) With XD301/312 detector or communicating XD308C detector. (8) With XL308/316 locator. (9) Remote test possible. 21 423E2020.PM6 21 24/07/06, 9:28 Vigilohm: functions and characteristics 044148 communicating Vigilohm System XM300C insulation monitoring device basic function: overall insulation monitoring The XM300C provides overall insulation monitoring of electrical installations by injecting a low-frequency AC voltage between the installation and earth. main functions c measurement: v insulation resistance, v earth leakage capacitance; c indications: v satisfactory insulation resistance (green light on bargraph), v drop in insulation resistance: – below prevention threshold (orange light on bargraph and relay actuated), – below fault threshold (red light on bargraph and two relays actuated, including one with a failsafe feature), v transient faults (orange light); c display: v measurements, v events detected by any XL308/316 locators connected. All this data is accessible locally on the LCD screen of the insulating monitoring device and remotely via the Vigilohm System bus. DB100958 additional functions with other devices Locating of faulty circuits This function is obtained by using the XM300C together with: c XL308 and XL316 locators connected to 8 or 16 toroids. They are linked to the XM300C by the Vigilohm System bus; c XD308C communicating detectors. They are linked to the XM300C by the Vigilohm System bus, and connected to the toroids placed on the circuits to be monitored; c XD301 and XD312 detectors connected to the toroids placed on the circuits to be monitored; c an XRM mobile receiver and a current probe to fine-tune the automatic locating results. All these devices can be combined on a given installation. interfaces MERLIN GERIN MERLIN GERIN MERLIN GERIN v ig ilo h m s y s te m v ig ilo h m s y s te m v ig ilo h m s y s te m XTU300 X L I3 0 0 XAS d é f a u t d insulation monitoring XML308/316 é f a u t d é f a u t Distributed measurements This function is provided by combining an XM300C monitoring device (or an XML308/316 monitoring-locating device) with XL308 or XL316 locators. These locators measure the insulation resistance and the earth leakage capacitance of each of the circuits. They have a fault alarm threshold that can be set to a different levels for each channel. XM300c MERLIN GERIN MERLIN GERIN v ig ilo h m s y s te m v ig ilo h m s y s te m XM 300c X M L 3 16 test test 2 3 4 5 6 7 8 1 1 0 1 1 1 2 1 3 1 4 1 5 1 6 9 valeur d'isolement 040 K MENU TEST valeur d'isolement 040 K MENU TEST P 100 insulation fault detection and locating MERLIN GERIN MERLIN GERIN v ig ilo h m s y s te m v ig ilo h m s y s te m XD308c XL316 test test MERLIN GERIN MERLIN GERIN 1 v ig ilo h m s y s t e m 2 3 X D 301 1 4 5 3 2 4 5 6 7 2 3 4 5 6 7 8 1 1 0 1 1 1 2 1 3 1 4 1 5 1 6 9 8 on v ig ilo h m s y s t e m X D 312 te s t te s t 6 7 8 9 10 11 12 test M reset M re s e t re s e t test/reset P 5 0 5 0 5 0 7 P 1 2 o n 5 0 5 3 6 M M MERLIN GERIN v ig id ix R M 1 0 N communication Communication with the supervision system. The XLI300 and XTU300 interfaces allow monitoring devices + locators + communicating detectors to exchange information with a supervision system via JBUS protocol. The XLI300 and XTU300 interfaces connect to the Vigilohm System bus and allow timestamping of insulation monitoring events. configuration management On installations with a number of insulation monitoring devices installed to cover variable configurations, only one device at a time can be allowed to inject a voltage between earth and the installation downstream of the incoming circuit breaker. For this reason, the system must manage the exclusion of other connected insulation monitoring devices. In addition, each locator must identify the monitoring device from which it is to capture the signal. The exclusion of monitoring devices and their identification by the locators is handled in one of the following manners: c by the XTU300 interface for multiple busbar installations; c by the XLI300 interface for single busbar installations. In both cases, the circuit breaker position indication contacts are wired to the all-ornothing inputs of the XM300C or XML308/316. If only XD308C detectors are associated with the XM300C, monitoring device exclusion is handled by the XLI200 interface. standards The XM300C insulation monitoring device complies with the following standards: c IEC 364, parts 4 and 5; c class CPI/XA of UTE C 63-080. It is implemented in accordance with standard NF C 15-100 paragraph 413.4; c IEC 61557-8. installation and connection c horizontal flush mounting on the front face of a cubicle or enclosure; c easy mounting in Prisma enclosures using the corresponding mounting plates and front plates that come with the appropriate cut-outs; c the devices are interconnected by shielded cables (double 0.75 mm2 twisted pairs). The resistance between the two most distant points must not exceed 12 Ω. The coupling capacitance between pairs must not exceed 250 nF; c if no XTU300 or XLI300 interface is included, operation of the Vigilohm System bus will require an XAS interface. sensors MERLIN GERIN G O S1 S2 MERLIN GERIN P O S1 MERLIN GERIN v ig ir e x - v ig id ix S2 MERLIN GERIN v ig ir e x - v ig id ix MERLIN GERIN v ig ir e x - v ig id ix 22 423E2030.PM6 22 24/07/06, 9:28 E19527 auxiliaries restrictions for use Cardew surge limiter: page 43. ZX limiting impedance to create an impedance-earthed neutral: page 44. PHT1000 subassembly if the device is to be used on 1000-1700 V installations: page 44. The XM300C operates by injecting lowfrequency signals (2.5 Hz). It should not be used for circuits that include variable speed drives if this equipment continuously generates a signal with a similar frequency (≤ 5 Hz). type of installation to be monitored AC or mixed AC/DC IT systems MERLIN GERIN XM300C test i DC or rectified IT systems phase-to phase voltage with XM300C connected to neutral with XM300C connected to phase frequency size of installation line voltage < 760 or 1700 V AC (1) < 440 or 1000 V AC (1) 45-400 Hz 0 to 30 km of cable < 500 or 1200 V DC (1) electrical characteristics 1 7 6 2 4 5 3 1. display indicating: c the value of the overall insulation resistance R; c other information as selected via function keys. 2. red self-test light, indicating internal XM300C faults. 3. light indicating that a transient fault has occurred. 4. 5 lights indicating the insulation level. 5. instruction manual stored in a drawer on the front face 6. sealable cover ensuring tamperproof settings. 7. function keys for: c accessing earth coupling capacitance readings c setting thresholds; c accessing three last values of transient insulation faults; c remote access to faults detected by XL308 or XL316 detectors; c choice of language. ohmmeter range for insulation resistance readings signalling number of thresholds threshold settings 1st threshold (prevent.) 2nd threshold (fault) dielectric strength auxiliary supply voltage 50/60 Hz auxiliary supply voltage tolerances maximum device consumption measurement voltage measurement current 50 Hz/DC impedance device test failsafe feature (2) changeover output contact breaking capacity of output contacts circuit breaker position indication contacts (3): (voltage and current supplied by XAS XLI or XTU interfaces) connection cross-sections digital 0.1 to 999 kΩ 2 (sealable settings) 1 to 299 kΩ 0.2 to 99.9 kΩ 2500 V 115/127 V AC 220/240 V AC 380/415 V AC 500/525 V AC - 15 % to + 10 % 30 VA 6V 5 mA max 22 kΩ self-test and manual test as standard quantity 3 (1 failsafe) AC 400 V p. f. = 0.7 3A 230 V p. f. = 0.7 5A DC 220 V L/R = 1 ms 0.45 A 120 V L/R = 1 ms 0.65 A 48 V L/R = 1 ms 2.5 A 24 V L/R = 1 ms 10 A voltage supplied 24 V max. current supplied 10 mA (short-circuit) rigid conductors flexible conductors 1 to 1.5 mm2 0.75 to 1.5 mm2 mechanical characteristics weight sheet-metal case (horizontal mounting) degree of protection 3.5 kg disconnectable screw terminal block flush mounting IP 30 other characteristics interfacing possible with multi-language display tamperproof settings temperature range supervisor English/French protected by access code or sealable cover operating - 5 °C to + 55 °C storage - 25 °C to + 70 °C (1) The upper limit is extended to the second value by adding a PHT1000 subassembly. (2) Failsafe feature: a failsafe relay operates in the event of an accidental interruption of auxiliary power or a fault. (3) This contact is an auxiliary switch mounted on the circuit breaker and used to indicate its operating status. 23 423E2030.PM6 23 24/07/06, 9:28 Vigilohm: functions and characteristics 044145 communicating Vigilohm System XL308 and XL316 insulation fault locators basic function: local insulation fault monitoring Used together with an XM300C or XML308/ 316 monitoring device, XL308 and XL316 locators monitor the insulation of 8 or 16 individual circuits and automatically locate any faults. main functions c measurement: v insulation resistance of each monitored circuit, v earth leakage capacitance of each monitored circuit; c indications: v satisfactory insulation resistance (green light), v drop in insulation resistance below fault threshold (red light and two relays actuated, including one with a failsafe feature). The fault threshold is adjustable for each of the 8 or 16 channels corresponding to the monitored circuits, v transient faults on each of the monitored circuits; c display: v faulty circuits are indicated by the corresponding LEDs (8 or 16 depending on the model), v a flashing LED indicates a transient fault on the corresponding circuit. communication Faults detected by XL308/316 locators can be displayed on the insulation monitoring device associated with the locator. The information transmitted to the insulation monitoring device can be transmitted to a supervisor via an XLI300 or XTU300 interface connect to the Vigilohm System bus. standards XL308 and XL316 locators comply with the following standards: c IEC 364, parts 4 and 5; c class DLD/M of UTE C 63-080; They are implemented in accordance with standard NF C 15-100 paragraph 413.4; c IEC 61557-8. toroids XL308 and XL316 locators operate with type A and OA toroids. installation and connection c horizontal flush mounting on the front face of a cubicle or enclosure; c easy mounting in Prisma enclosures using the corresponding mounting plates and front plates that come with the appropriate cut-outs; c the devices are interconnected by shielded cables (double 0.75 mm2 twisted pairs). The resistance between the two most distant points must not exceed 12 Ω. The coupling capacitance between pairs must not exceed 250 nF; c connection of toroids using twisted, shielded cable (1 pair); c if no XTU300 or XLI300 interface is included, operation of the Vigilohm System bus will require an XAS interface. DB100959 interfaces MERLIN GERIN MERLIN GERIN MERLIN GERIN v ig ilo h m s y s te m v ig ilo h m s y s te m v ig ilo h m s y s te m XTU300 X L I3 0 0 XAS d é f a u t d é f a u t d é f a u t insulation monitoring MERLIN GERIN MERLIN GERIN v ig ilo h m s y s te m v ig ilo h m s y s te m XM 300c X M L 3 16 test test 2 3 4 5 6 7 8 1 1 0 1 1 1 2 1 3 1 4 1 5 1 6 9 valeur d'isolement 040 K MENU TEST valeur d'isolement 040 K MENU TEST insulation fault detection and locating XD301 XD312 XRM XD308c XL308 / 316 MERLIN GERIN MERLIN GERIN v ig ilo h m s y s te m v ig ilo h m s y s te m XD308c XL316 test test MERLIN GERIN MERLIN GERIN 1 v ig ilo h m s y s t e m 2 3 X D 301 1 4 5 3 2 4 5 6 7 2 3 4 5 6 7 8 1 1 0 1 1 1 2 1 3 1 4 1 5 1 6 9 8 on v ig ilo h m s y s t e m X D 312 te s t te s t 6 7 8 9 10 11 12 test M reset M re s e t re s e t test/reset P 5 0 5 0 5 0 7 P 1 2 o n 5 0 5 3 6 P 1 0 0 M M MERLIN GERIN v ig id ix R M 1 0 N sensors MERLIN GERIN G O S1 S2 MERLIN GERIN P O S1 MERLIN GERIN v ig ir e x - v ig id ix S2 MERLIN GERIN v ig ir e x - v ig id ix MERLIN GERIN v ig ir e x - v ig id ix 24 423E2040.PM6 24 24/07/06, 9:28 locator electrical characteristics XL308 ohmmeter range for insulation resistance readings signalling signalling threshold and setting range (per channel) polling time device test dielectric strength auxiliary supply voltage digital 0.1 to 999 kΩ 8 lights (1 per channel) 16 lights (1 per channel) 1 0.2 to 99.9 kΩ 15 seconds per channel self-test and manual test 2500 V 115/127 V AC 220/240 V AC 380/415 V AC 500/525 V AC - 15 % to + 10 % 30 VA local or from insulation monitoring device 2 (1 failsafe) 3A 5A 0.45 A 0.65 A 2.5 A 10 A via 4-wire communication bus 1 to 1.5 mm2 0.75 to 1.5 mm2 auxiliary supply voltage tolerances maximum device consumption indicator and output relay output relays breaking capacity of output contacts link with insulation monitoring device connection crosssections fault threshold 50/60 Hz AC 400 V p.f. = 0.7 230 V p.f. = 0.7 DC 220 V L/R = 1 ms 120 V L/R = 1 ms 48 V L/R = 1 ms 24 V L/R = 1 ms rigid conductors flexible conductors XL316 mechanical characteristics weight sheet-metal case 3.5 kg horizontal mounting disconnectable screw terminal block other characteristics types of toroid to be used temperature range operating storage A and OA (XC compatible) - 5 °C to + 55 °C - 20 °C to + 70 °C DB100954 (1) The upper limit is extended to the second value by adding a PTH1000 subassembly. The same voltage limits apply to both the XL308 and the XL316. MERLIN GERIN XL31 6 1 2 3 4 5 6 7 8 i 9 10 1 12 13 14 15 16 1 ∝ - 1 2 + 9 test/rese t ∝F ! / 7 8 5 6 4 3 1. display indicating measured insulation resistance and earth coupling capacitance value. 2. light indicating measurement units for displayed value (kΩ, µF, etc.). 3. red self-test light, indicating device faults. 4. yellow light indicating that a transient fault has occurred. 5. 2 lights indicating the insulation level: c green light: normal; c red light: insulation resistance below fault threshold on one of the circuits. 6. instruction manual stored in a drawer on the front face 7. function keys for: c accessing earth leakage capacitance readings; c setting thresholds; c accessing three last values of transient insulation faults. 8. sealable cover ensuring tamperproof settings. 9. lights indicating faulty circuits. 25 423E2040.PM6 25 24/07/06, 9:28 Vigilohm: functions and characteristics communicating Vigilohm System XML308 and XML316 monitoring-locating devices 044149 basic function: overall and individual circuit insulation monitoring XML308 and XML316 monitoring-locating devices combine the functions of: c the XM300C insulation monitoring device; c XL308 or XL316 insulation fault locators. They monitor the insulation of: v the overall installation by injection of a lowfrequency AC voltage between the installation and earth, v 8 or 16 individual circuits via detection toroids. main functions DB100958 c measurement: v insulation resistance of the overall installation and each monitored circuit, v earth leakage capacitance of the overall installation and each monitored circuit; c indications: v satisfactory insulation resistance (green light), v drop in insulation resistance: – for the overall installation, below prevention threshold (orange light and relay actuated), – for the overall installation and each monitored circuit, below adjustable fault threshold (red light and two relays actuated, including one with a failsafe feature), v transient faults on the overall installation (orange light), with storage in memory of the three last values, v faulty circuit by 8 or 16 indicator lights (1 for each circuit); c display: v measurements, v events detected by any XL308/316 locators connected. All this data is accessible locally on the LCD screen of the insulating monitoring device and remotely via the Vigilohm System bus. interfaces MERLIN GERIN MERLIN GERIN MERLIN GERIN v ig ilo h m s y s te m v ig ilo h m s y s te m v ig ilo h m s y s te m XTU300 X L I3 0 0 XAS d é f a u t d insulation monitoring XML308/316 additional functions with other devices é f a u t d é f a u t XM300c MERLIN GERIN MERLIN GERIN v ig ilo h m s y s te m v ig ilo h m s y s te m XM 300c X M L 3 16 test test 2 3 4 5 6 7 8 1 1 0 1 1 1 2 1 3 1 4 1 5 1 6 9 valeur d'isolement 040 K MENU TEST valeur d'isolement 040 K MENU TEST P 100 insulation fault detection and locating MERLIN GERIN MERLIN GERIN v ig ilo h m s y s te m v ig ilo h m s y s te m XD308c XL316 test test MERLIN GERIN MERLIN GERIN 1 v ig ilo h m s y s t e m 2 3 X D 301 1 4 5 3 2 4 5 6 7 2 3 4 5 6 7 8 1 1 0 1 1 1 2 1 3 1 4 1 5 1 6 9 8 on v ig ilo h m s y s t e m X D 312 te s t te s t 6 7 8 9 10 11 12 test M reset M re s e t re s e t test/reset P 5 0 5 0 5 0 7 P 1 2 o n 5 0 5 3 6 M M MERLIN GERIN v ig id ix R M 1 0 N sensors It is possible to monitor more than 8 or 16 circuits by adding any of the following devices: c XL308 or XL316 locators that measure the insulation resistance on each additional circuit; c XD308C communicating detectors that automatically detect the faulty circuit and communicate via an XLI300 or XTU300 interface; c XD301 and XD312 detectors that automatically detect the faulty circuit and provide local indications. The communicating detectors and locators are connected to the XML308/316 via the Vigilohm System bus. communication Communication with the supervision system. The XLI300 and XTU300 interfaces allow monitoring devices + locators + communicating detectors to exchange information with a supervision system via JBUS protocol. The XLI300 and XTU300 interfaces connect to the Vigilohm System bus and allow timestamping of insulation monitoring events. configuration management On installations with a number of insulation monitoring devices installed to cover variable configurations, only one device at a time can be allowed to inject a voltage between earth and the installation downstream of the incoming circuit breaker. For this reason, the system must manage the exclusion of other connected insulation monitoring devices. In addition, each locator must identify the monitoring device from which it is to capture the signal. The exclusion of monitoring devices and their identification by the locators is handled in one of the following manners: c by the XTU300 interface for multiple busbar installations with bus coupling; c by the XLI300 interface for single busbar installations. In both cases, the circuit breaker position indication contacts are wired to the all-ornothing inputs of the XM300C or XML308/316. standards The XML308 and XML316 devices comply with the following standards: c IEC 364, parts 4 and 5; c class CPI/XA and DLD/M of UTE C 63-080. They are implemented in accordance with standard NF C 15-100 paragraph 413.4; c IEC 61557-8. toroids The XML308 and XML316 devices operate with type A and OA toroids. They are also compatible with type XS toroids. installation and connection c horizontal flush mounting on the front face of a cubicle or enclosure c easy mounting in Prisma enclosures using the corresponding mounting plates and front plates that come with the appropriate cutouts; c the devices are interconnected by shielded cables (double 0.75 mm2 twisted pairs). The resistance between the two most distant points must not exceed 12 Ω. The coupling capacitance between pairs must not exceed 250 nF; c connection of toroids using twisted, shielded cable (1 pair); c if no XTU300 or XLI300 interface is included, operation of the Vigilohm System bus will require an XAS interface. MERLIN GERIN G O S1 S2 MERLIN GERIN P O S1 MERLIN GERIN v ig ir e x - v ig id ix S2 MERLIN GERIN v ig ir e x - v ig id ix MERLIN GERIN v ig ir e x - v ig id ix 26 423E2050.PM6 26 24/07/06, 9:28 auxiliaries restrictions for use Cardew surge limiter: page 43. ZX limiting impedance to create an impedance-earthed neutral: page 44. PHT1000 subassembly if the device is to be used on 1000-1700 V installations: page 44. The XML308/316 operates by injecting lowfrequency signals (2.5 Hz). It should not be used for circuits that include variable speed drives if this equipment continuously generates a signal with a similar frequency (≤ 5 Hz). E19502 type of installation to be monitored AC or mixed AC/DC IT systems MERLIN GERIN XML316 test 1 2 3 4 5 6 7 8 i 9 10 11 12 13 14 15 16 DC or rectified IT systems phase-to phase voltage with XML308/316 connected to neutral with XML308/316 connected to phase frequency size of installation line voltage < 760 or 1700 V AC (1) < 440 or 1000 V AC (1) 45-400 Hz 0 to 30 km of cable < 500 or 1200 V DC (1) electrical characteristics 9 8 10 1 7 2 3 6 4 5 1. display indicating measurements concerning the overall installation or each monitored circuit, and information concerning the device settings; 2. red self-test light, indicating device faults. 3. light indicating that a transient fault has occurred. 4. 5 lights indicating the insulation level. 5. instruction manual stored in a drawer on the front face 6. sealable cover ensuring tamperproof settings. 7. function keys for: c accessing earth coupling capacitance readings; c setting thresholds; c accessing three last values of transient insulation faults; c reading measurements made on individual circuits by the internal locator; c remote access to faults detected by XL308 or XL316 detectors; c choice of language. 8. two indicator lights continuously display the insulation level of the overall installation. 9. 8 or 16 indicating lights indicate faulty circuits. 10. light indicating that a transient fault has occurred. ohmmeter range for insulation resistance readings signalling for overall instal. for each circuit threshold settings for overall instal. instal. and circuits number of toroids that can be connected (1 per channel) digital 0.1 to 999 kΩ number of thresholds 2 (sealable settings) number of thresholds 1 (sealable settings) 1st threshold (preven.) 1 to 299 kΩ 2nd threshold (fault) 0.2 to 99.9 kΩ XML308 8 XML316 16 polling time 15 s. per channel dielectric strength 2500 V auxiliary supply voltage 50/60 Hz 115/127 V AC 220/240 V AC 380/415 V AC 500/525 V AC auxiliary supply voltage tolerances -15 % to +10 % maximum device consumption 30 VA measurement voltage 6V measurement current 5 mA max. 50 Hz/DC impedance 22 kΩ device test self-test and manual test failsafe feature (2) as standard changeover output contact quantity 3 (1 failsafe) breaking capacity of AC 400 V p.f. = 0.7 3A output contacts 230 V p.f. = 0.7 5A DC 220 V L/R = 1 ms 0.45 A 120 V L/R = 1 ms 0.65 A 48 V L/R = 1 ms 2.5 A 24 V L/R = 1 ms 10 A circuit breaker position indication contacts (3): voltage supplied 24 V (voltage and current supplied by XAS, max. current supplied 10 mA (short-circuit) CLI or XTU interfaces) connection cross-sections rigid conductors 1 to 1.5 mm2 flexible conductors 0.75 to 1.5 mm2 mechanical characteristics weight sheet-metal case (horizontal mounting) degree of protection 4.5 kg disconnectable screw terminal block flush mounting IP 30 other characteristics types of toroid to be used interfacing possible with multi-language display tamperproof settings temperature range A, OA (XS compatible) supervisor English/French protected by access code or sealable cover operating - 5 °C to + 55 °C storage - 20 °C to + 70 °C (1) The upper limit is extended to the second value by adding a PHT1000 subassembly. (2) Failsafe feature: a failsafe relay operates in the event of an accidental interruption of auxiliary power or a fault. (3) This contact is an auxiliary switch mounted on the circuit breaker and used to indicate its operating status. 27 423E2050.PM6 27 24/07/06, 9:28 Vigilohm: functions and characteristics 044143 communicating Vigilohm System XD308C communicating automatic insulation fault detector electrical characteristics type of installation to be monitored operating threshold polling time fault indications operating tests functions tested clearing of memorised faults E19504 auxiliary supply voltage 50/60 Hz MERLIN GERIN XD308C 3 2 1 auxiliary supply voltage tolerances consumption dielectric strength connection with insulation monitoring device 8 7 6 5 4 reset test low voltage AC 45-400 Hz / DC 2.5 mA at 2.5 Hz (1) 20 s per channel 8 indicator lights local indicator lights and electronics local reset on front face or remote reset from supervisor 115/127 V AC 220/240 V AC 380/415 V AC 500/525 V AC - 15 % to + 10 % 6 VA 2500 V via 4-wire Vigilohm System bus mechanical characteristics 1 4 5 weight metal case with insulated front degree of protection flush mounting 3 2 6 1. lights indicating the faulty circuit. 2. power on 3. general fault indicator light. 4. test button for indicator lights. 5. device internal fault indication (self-test) 6. self-test fault indicator light. other characteristics temperature range storage operating types of toroid to be used The XD308C provides 3 functions: c detection of insulation faults; c automatic locating of the faulty circuit, identified by the number of the illuminated indicating light; c communication of this information to an XLI200 or XLI300 or XTU300 interface for transmission to a supervisor or PLC. DB100959 operation MERLIN GERIN MERLIN GERIN v ig ilo h m s y s te m é f a u t c XD308C insulation fault detectors are fixed receivers connected to XM300C or XML308/ 316 insulation monitoring devices via the Vigilohm System communication bus; c the XD308C detector, with 8 channels connected to a maximum of 12 toroids installed on different circuits of the installation, includes the following features on its front face: v 8 fault indicator lights corresponding to the 8 channels, v 1 general fault indicator light signalling that a fault has occurred, v 1 light indicating the operating status of the device, v 2 pushbuttons (self-test and reset). MERLIN GERIN v ig ilo h m s y s te m v ig ilo h m s y s te m XTU300 X L I3 0 0 d d é f a u t d é f a u t MERLIN GERIN MERLIN GERIN v ig ilo h m s y s te m v ig ilo h m s y s te m XM 300c X M L 3 16 test test XD301 2 3 4 5 6 7 8 1 1 0 1 1 1 2 1 3 1 4 1 5 1 6 9 valeur d'isolement 040 K MENU TEST valeur d'isolement 040 K MENU TEST XD312 XRM XD308c XL308 / 316 MERLIN GERIN MERLIN GERIN v ig ilo h m s y s te m v ig ilo h m s y s te m XD308c XL316 - 25 °C to + 70 °C - 5 °C to + 55 °C A (N and O compatible) (1) The operating threshold of the XD308C detectors is not adjustable. These devices are designed to detect low-impedance faults. The detection threshold varies between 100 Ω and 2 kΩ depending on the characteristics of the installation. basic function: local insulation fault detection XAS 0.6 kg vertical mounting IP 30 installation and connection c live parts in a disconnectable metal case; c vertical mounting on front plate; c tunnel terminals for 1.5 mm2 wires; c the devices are interconnected by shielded cables (double 0.75 mm2 twisted pairs). The resistance between the two most distant points must not exceed 12 Ω. The coupling capacitance between pairs must not exceed 250 nF; c if no XTU300 or XLI300 interface is included, operation of the Vigilohm System bus will require an XAS interface. toroids XD308C insulation fault detectors operate with type A and OA toroids. They are also compatible with the older type N and O toroids. test test MERLIN GERIN MERLIN GERIN 1 v ig ilo h m s y s t e m 2 3 X D 301 1 4 5 3 2 4 5 6 7 2 3 4 5 6 7 8 1 1 0 1 1 1 2 1 3 1 4 1 5 1 6 9 8 on v ig ilo h m s y s t e m X D 312 te s t te s t 6 7 8 9 10 11 12 test M reset M re s e t re s e t test/reset P 5 0 5 0 5 0 7 P 1 2 o n 5 0 5 3 6 P 1 0 0 M M MERLIN GERIN v ig id ix R M 1 0 N MERLIN GERIN G O S1 S2 MERLIN GERIN P O S1 MERLIN GERIN v ig ir e x - v ig id ix S2 MERLIN GERIN v ig ir e x - v ig id ix MERLIN GERIN v ig ir e x - v ig id ix 28 423E2060.PM6 28 24/07/06, 9:28 Vigilohm: functions and characteristics 044146 communicating Vigilohm System XLI200, XLI300, XTU300 and XAS communication interfaces use functions When two or more communicating devices (XM300C, XML308/316, XL308/316 or XD308C) are used or when communication with a supervisor is required, it is necessary to connect one (and only one) interface to the communication bus. If no XTU300 or XLI300 interface is included, operation of the Vigilohm System bus will require an XAS interface. The interface allows communication between the Vigilohm System and a supervisor or PLC using a JBUS type protocol (except X25). It transmits the information provided by the Vigilohm System: c prevention and fault alarms from XM300C or XML308/316 monitoring devices (only XM300C for XLI200); c fault alarms from XML308/316 or XM308/316 locators (except XLI200); c insulation resistance and capacitance measurements; c threshold settings; c fault alarms and faulty circuit identification from XD308C detectors. The interface also allows the thresholds to be set form the supervisor. device function XLI200 XLI300 XTU300 XAS interface between the Vigilohm System bus and a supervisor or PLC power supply to Vigilohm System bus operates with monitoring device XM300C mon.-loc. device XML308/316 locator XL308/316 detector XD301/312 XD308C maximum configuration monitoring device XM300C and/or XML308/316 locator XL308/316 detector XD308C c c c c c c c c c c c c c c 4 (1) c 4 8 8 c 4 8 8 c 4 115/127 V AC 220/240 V AC 380/415 V AC 500/525 V AC c c 115/127 V AC 220/240 V AC 380/415 V AC 500/525 V AC c c c 2.228 kg 1.864 kg c 2.228 kg 1.864 kg c 2.228 kg 1.864 kg c c c c c c c c c c c c c c c c c c c c c c 300... 19200 9600 8 none 1 1 300... 19200 9600 8 none 1 1 300... 19200 9600 8 none 1 1 16 c c c c 8 electrical characteristics auxiliary supply voltage 50/60 Hz consumption dielectric strength 30 VA 2500 V 220/240 V AC 115/127 V AC 380/415 V AC 220/240 V AC 380/415 V AC 500/525 V AC c c c c mechanical characteristics weight gross net metal case with insulated front degree of protection degree of protection of front IP30 IP40 other characteristics interfacing possible with supervisor JBUS connector communication with other devices temperature range storage operation Sub D 9-pin (not supplied) via 4-wire data bus - 25 °C to + 70 °C - 5 °C to + 55 °C installation vertical mounting on front plate connection 1.5 mm2 tunnel terminals RS485 Vigilohm System bus external bus sub D9 female connector communication speed (bauds) adjustable per fault data length (bits) parity start bits stop bits (1) only XM300C. 29 423E2060.PM6 29 24/07/06, 9:28 Vigilohm: functions and characteristics 044147 Vigilohm System XM200 insulation monitoring device basic function: overall insulation monitoring The XM200 provides overall insulation monitoring of electrical installations by injecting a low-frequency AC voltage between the installation and earth. main functions c measurement: v insulation resistance, v earth leakage capacitance; c indications: v satisfactory insulation resistance (green light), v drop in insulation resistance: – below prevention threshold (orange light and failsafe relay actuated), – below fault threshold (red light and relay actuated), v transient faults (orange light); c display: v measurements accessible locally on the display unit of the device, v value of the last transient fault. additional functions with other devices E24554 Identification of faulty circuits This function is obtained by using the XM200 together with XD301/XD312 automatic insulation fault detectors. In addition, an XRM mobile receiver and a current probe can be used to determine the exact location of the fault on the faulty circuit. standards The XM200 insulation monitoring device complies with the following standards: c IEC 364, parts 4 and 5; c class CPI/XA of UTE C 63-080. It is implemented in accordance with standard NF C 15-100 paragraph 413.4; c IEC 61557-8. operating voltage c AC IT systems up to: v 440 V with neutral not distributed, v 760 V with neutral distributed; c DC systems up to 500 V. The XM200 cannot be adapted to installations with higher voltages by connecting it to a PHT1000 subassembly. For higher voltage, use an XM300C. installation c horizontal flush mounting on the front face of a cubicle or enclosure; c easy mounting in Prisma enclosures using the corresponding mounting plates and front plates that come with the appropriate cut-outs. auxiliaries Cardew surge limiter: page 43. ZX impedance: page 44. restrictions for use The XM200 operates by injecting lowfrequency signals (2.5 Hz). It should not be used for circuits that include variable speed drives if this equipment continuously generates a signal with a similar frequency (≤ 10 Hz). insuation monitoring XM200 MERLIN GERIN vigilohm system XM200 test R C Sp Sa S menu ok test insulation fault detection and locating MERLIN GERIN vigilohm system XD301 1 2 3 4 5 6 7 8 9 MERLIN GERIN vigilohm system XD312 test test M 10 11 12 M reset 50507 reset 50536 P12 on P50 P100 M M MERLIN GERIN vigidix RM 10N sensors MERLIN GERIN GO S1 S2 MERLIN GERIN PO S1 S2 MERLIN GERIN vigirex - vigidix MERLIN GERIN vigirex - vigidix MERLIN GERIN vigirex - vigidix 30 423E2070.PM6 30 24/07/06, 9:28 E19051 type of installation to be monitored AC or mixed AC/DC IT systems MERLIN GERIN XM200 test i Sp Sa O kΩ µF kΩ kΩ kΩ S R C menu test ok DC or rectified IT systems phase-to phase voltage with XM200 connected to neutral with XM200 connected to phase frequency size of installation line voltage < 760 V AC < 440 V AC 45-400 Hz 0 to 30 km of cable < 500 V DC electrical characteristics 1 6 2 4 5 3 1. display indicating: c the value of the overall insulation resistance R; c other information as selected via function keys. 2. red self-test light, indicating internal XM200 faults. ohmmeter range for insulation resistance readings signalling number of thresholds threshold settings 1st threshold (prevent) 2nd threshold (fault) time delay for signalling 3 settings dielectric strength auxiliary supply voltage 50/60 Hz 3. light indicating that a transient fault has occurred. 4. 3 lights indicating the insulation level. 5. sealable cover ensuring tamperproof settings. 6. function keys for: c accessing earth coupling capacitance readings; c setting thresholds; c displaying the value of the last transient insulation fault; c setting time delays. auxiliary supply voltage tolerances maximum device consumption measurement voltage measurement current 50 Hz/DC impedance device test failsafe feature (1) output contacts changeover breaking capacity of output contacts connection cross-sections digital 0.1 to 999 kΩ 2 (sealable settings) 10 to 100 kΩ 0.1 to 20 kΩ 0 s,15 s, 30 s 2500 V 115/127 V AC 220/240 V AC 380/415 V AC 500/525 V AC - 15 % to +10 % 30 VA variable 25 V max. 3 mA max. 33 kΩ self-test and manual test as standard quantity 2 (1 failsafe) AC 400 V p.f. = 0.7 3A 230 V p.f. = 0.7 5A DC 220 V L/R = 1 ms 0.45 A 120 V L/R = 1 ms 0.65 A 48 V L/R = 1 ms 2.5 A 24 V L/R = 1 ms 10 A rigid conductors 1 to 1.5 mm2 flexible conductors 0.75 to 1.5 mm2 mechanical characteristics weight sheet-metal case (horizontal mounting) degree of protection 2.5 kg disconnectable screw terminal block flush mounting IP 30 other characteristics tamperproof settings temperature range behind sealable cover operating - 5 °C to + 55 °C storage - 25 °C to + 70 °C fault locating with other devices automatic manual detectors XD301/312 mobile receiver XRM + probes (1) Failsafe feature: a failsafe relay operates in the event of an accidental interruption of auxiliary power or a fault. 31 423E2070.PM6 31 24/07/06, 9:28 Vigilohm: functions and characteristics 044144 Vigilohm System: XD301 and XD312 automatic insulation fault detectors E19500 basic function local fault detection 1 2 3 4 5 6 MERLIN GERIN XD312 test 7 8 9 10 11 12 reset 1 3 2 4 5 6 1. lights indicating the faulty circuit. 2. selector to enable or disable transient fault indication latching 3. sealable cover. 4. general fault indicator light. 5. test button for indicator lights and output relay. 6. reset button (to clear fault indications). installation and connection XD301 and XD312 insulation fault detectors have two functions: c fault detection (with respect to the fault threshold); c automatic locating of the faulty circuit. c live parts in an insulated case with a sealable transparent cover. Width equal to 8 (XD301) or 12 (XD312) 9 mm width modules; c horizontal flush or surface mounting on DIN rail; c tunnel terminals for 1.5 mm2 wires. operation toroids c XD301 and XD312 insulation fault detectors are fixed receivers used with (but not connected to) XM300C, XML308/316 and XM200 insulation monitoring devices. Via measurement toroids, they detect and automatically locate insulation faults c the XD312 detector, with 12 channels connected to a maximum of 12 toroids installed on different circuits of the installation, includes the following features on its front face: v 12 fault indicator lights corresponding to the 12 channels, v a selector to enable or disable latching of transient fault indications until reset; c detector XD301 is a single-channel version designed for use with one measurement toroid. XD301 and XD312 insulation fault detectors operate with type A and OA toroids. They are also compatible with the older type N and O toroids. insulation fault detectors electrical characteristics XD301 type of installation to be monitored operating threshold polling time fault indications low voltage AC 45-400 Hz / DC 2.5 mA at 2.5 Hz (1) 20 s 20 s per channel 1 indicator light 12 channel indicator lights (+ 1 general) for indicator lights and output relay reset button on device on/off via selector 1 failsafe 3A 5A 0.45 A 0.65 A 2.5 A 10 A 115/127 V AC 220/240 V AC 380/415 V AC 500/525 V AC - 15 % to + 10 % 6 VA 2500 V none local tests clearing of indications latching of transient fault indications output relay number of contacts breaking capacity AC 400 V p.f. = 0.7 of output contacts 230 V p.f. = 0.7 DC 220 V L/R = 1 ms 120 V L/R = 1 ms 48 V L/R = 1 ms 24 V L/R = 1 ms auxiliary 50/60 Hz supply voltage auxiliary supply voltage tolerances consumption dielectric strength connection with insulation monitoring device XD312 mechanical characteristics weight plastic case degree of protection flush/surface mounting 0.3 kg horizontal mounting IP 30 / IP 20 0.6 kg other characteristics temperature range storage operating types of toroid to be used toroid for direct connection to case - 25 °C to + 70 °C - 5 °C to + 55 °C A, OA (N and O compatible) 30 and 50 mm none type A toroid (1) The operating threshold of the XD301/312 detectors is not adjustable. These devices are designed to detect low-impedance faults. The detection threshold varies between 100 Ω and 2 kΩ depending on the characteristics of the installation. 32 423E2080.PM6 32 24/07/06, 9:28 Vigilohm: functions and characteristics XRM mobile fault locating receiver and current probes 051350 operation The XRM mobile receiver, used with a current probe, is mainly intended as an enhancement to automatic fault locating systems. It can be placed at various points along a faulty circuit, capturing the signal emitted by an XM300C, XML308/316 or XM200 insulation monitoring device to determine the exact location of the fault. Three current probes are available, the XM15, XP50 and XP100. The set of live conductors to be tested must have a maximum diameter of 12, 50 and 100 mm respectively. XRM receiver display PB100471 DB101070 The XRM receiver displays a number from 0 to 19, corresponding to the insulation level: c 0: no fault; c 19: solid fault (no insulation). XP15, XP50 and XP100 current probes. Note: the photographs are for information purposes only. There are two types of probes that function in the same way but are different in shape and colour. DB100959 interfaces MERLIN GERIN MERLIN GERIN MERLIN GERIN v ig ilo h m s y s te m v ig ilo h m s y s te m v ig ilo h m s y s te m XTU300 X L I3 0 0 XAS d é f a u t d é f a u t d é f a u t insulation monitoring E24555 insulation monitoring MERLIN GERIN v ig ilo h m s y s te m MERLIN GERIN MERLIN GERIN v ig ilo h m s y s te m v ig ilo h m s y s te m X M200 XM 300c X M L 3 16 test test test R C 2 3 4 5 6 7 8 1 1 0 1 1 1 2 1 3 1 4 1 5 1 6 9 valeur d'isolement 040 K MENU TEST valeur d'isolement 040 K MENU TEST Sp S menu ok test insulation fault detection and locating insulation fault detection and locating XD30 XD31 XD301 XRM XD312 XRM XD308c XL308 / 316 MERLIN GERIN MERLIN GERIN v ig ilo h m s y s te m v ig ilo h m s y s te m XD308c XL316 test test MERLIN GERIN MERLIN GERIN 1 v ig ilo h m s y s t e m 2 3 X D 301 MERLIN GERIN v ig ilo h m s y s t e m 4 5 MERLIN GERIN 1 v ig ilo h m s y s t e m X D 312 te s t te s t 7 8 9 10 11 12 2 3 X D 301 6 1 4 5 3 2 4 5 6 7 2 3 4 5 6 7 8 1 1 0 1 1 1 2 1 3 1 4 1 5 1 6 9 8 on v ig ilo h m s y s t e m X D 312 te s t te s t 6 7 8 9 10 11 12 test M reset M re s e t re s e t M M re s e t re s e t test/reset 5 0 5 0 7 P 5 0 P 5 0 5 0 5 3 6 P 1 2 o n P 1 0 0 5 0 5 0 7 P 1 2 o n 5 0 5 3 6 P 1 0 0 M M M M MERLIN GERIN MERLIN GERIN v ig id ix v ig id ix R M 1 0 N R M 1 0 N sensors sensors MERLIN GERIN G O MERLIN GERIN G O S1 S2 S1 S2 MERLIN GERIN P O MERLIN GERIN P O S1 S2 S1 MERLIN GERIN v ig ir e x MERLIN GERIN - v ig id ix v ig ir e x - v ig id ix S2 MERLIN GERIN v ig ir e x MERLIN GERIN - v ig id ix v ig ir e x MERLIN GERIN v ig ir e x - v ig id ix MERLIN GERIN - v ig id ix v ig ir e x - v ig id ix 33 423E2080.PM6 33 24/07/06, 9:28 Vigilohm: functions and characteristics 043274 Vigilohm TR22A and TR22AH insulation monitoring devices type of installation to be monitored LV AC IT systems phase-to-phase voltage with TR22A/AH connected to neutral with TR22A/AH connected to phase frequency limited in size i 760 V (i 1700 V (1)) i 440 V (i 1000 V (1)) 20 to 1000 Hz IT subsystem electrical characteristics ohmmeter fault signalling use IT systems: c LV AC installations up to: v neutral distributed: 760 V, v neutral not distributed: 440 V; c isolated from earth or connected to earth through a capacitive impedance. TR22H (hospitals) c high fault threshold up to 251 kΩ. response time device test failsafe feature (2) output changeover contact type reading range number thresholds threshold setting operation thresholds quantity breaking capacity One device only for each separate installation. operation c injection of DC voltage; c insulation measurement: using a microprocessor device, from the leakage current created by the voltage injected between the installation and earth. Earth coupling capacitances do not affect insulation measurement; c insulation reading: digital display; c 1 alarm threshold pre-set by the user. installation and connection c live part in disconnectable metal case; c vertical flush mounting on front plate (supplied); c connection: v disconnectable tunnel terminal block for 2.5 mm2 wiring. v lug for earthing of exposed conductive parts (supplied). TR22A TR22AH impedance maximum current injected maximum consumption auxiliary supply voltage AC 400 V p.f. = 0.7 DC 230 V L/R = 1 ms 120 V L/R = 1 ms 48 V L/R = 1 ms 24 V L/R = 1 ms 50/60 Hz auxiliary supply voltage tolerances locating signal changeover switch (3) front insulation digital 0 to 511 kΩ 1 (sealable) 0.7 to 100 kΩ 1 to 251 kΩ 3s yes yes yes 1 5A 0.45 A 0.65 A 2.5 A 10 A 100 kΩ 240 µA 5 VA 115/127 V AC 220/240 V AC 380/415 V AC 440/480 V AC 500/525 V AC - 15 % to + 10 % yes class 2 mechanical characteristics weight metal case with insulated front degree of protection disconnectable mounting 0.8 kg vertical flush mounted surface mounted IP 40 IP 40 other characteristics temperature range - 5 °C to + 55 °C - 40 °C to + 70 °C for operation for storage climatic conditions (4) fault locating with other devices mobile XGR portable generator and XRM receiver + probes (1) For the TR22A, the upper limit is extended to this value by adding a P1 subassembly. This is not possible for the TR22AH. (2) Failsafe: the relay is disactivated either on occurrence of a fault or if the auxiliary supply voltage accidentally fails. (3) Locating signal changeover switch: this device identifies the faulty feeder during locating by opening each feeder in turn. When the faulty feeder is opened, the alarm sounds. (4) Suitable for use in all climates: c damp heat, equipment not operating (IEC 60068-2-30) c damp heat, equipment operating (IEC 60068-2-56) c salt mist (IEC 60068-2-52). standards auxiliaries TR22A c IEC 364, chapters 4 and 5; c NF C 15-100, paragraphs 413 and 532; c UTE C 63-080 (class CPI/C); c IEC 61557-8. c Cardew C surge limiter. Compulsory downstream of an MV/LV transformer; c ZX impedance; c S3 inductive neutral point; c P1 additional subassembly for installations with voltages from 440 V to 1000 V AC. Can be used with TR22A only. TR22AH c UTE C 63-080 (class CPI/MC); c IEC 364, chapters 4 and 5; c NF C 15-100, paragraphs 413 and 532; c NF C 15-211; c IEC 61557-8. 34 423E2100.PM6 34 24/07/06, 9:28 Vigilohm: functions and characteristics 042578 Vigilohm EM9 and EM9B insulation monitoring devices type of installation to be monitored LV AC IT systems phase-to-phase voltage with EM9/EM9B connected to neutral with EM9/EM9B connected to phase frequency limited in size i 760 V i 440 V 50-60-400-1000 Hz IT subsystem electrical characteristics fault signalling use IT systems: c LV AC installations up to: v neutral distributed: 760 V, v neutral not distributed: 440 V; c one device only for each separate installation; c isolated from earth or connected to earth through a capacitive impedance; c EM9: for installations with a high insulation level; c EM9B: for installations with a low insulation level and capacitive installations. operation c injection of DC voltage; c an electronic device measures insulation from the leakage current created in the installation by the voltage injected between the installation and earth and trips the alarm threshold pre-set by the user. Earth coupling capacitances do not affect insulation measurement. installation and connection c live part in moulded, insulating, disconnectable, modular case, eight 9 mm modules wide, with transparent sealable cover; c horizontal or vertical mounting on symmetrical rail; c connection by tunnel terminals for 2.5 mm2 wiring, terminals 1 to 14. standards c UTE C 63-080; c IEC 364, chapters 4 and 5; c NF C 15-100 paragraphs 413 and 532; c NF C 15-211; c IEC 61557-8. number of thresholds 1 (sealable) threshold setting EM9: 10-20-40-60-80-100-120-150 kΩ EM9B: 1-2.5-5-10-25-50-75-100 kΩ response time i5s device operating test local failsafe feature (1) as an option output contact number 1 (standard or failsafe) type of contact changeover breaking capacity AC 400 V p.f. = 0.7 3A 230 V p.f. = 0,7 5A DC 220 V L/R = 1 ms 0.45 A 120 V L/R = 1 ms 0.65 A 48 V L/R = 1 ms 2.5 A 24 V L/R = 1 ms 10 A maximum consumption 5 VA impedance 100 kΩ maximum current injected 240 µA auxiliary supply voltage 50/60 Hz 115/127 V AC 220/240 V AC 380/415 V AC 440/480 V AC auxiliary supply voltage tolerances - 15 % + 10 % mechanical characteristics weight thermoplastic case mounting degree of protection front case 0.4 kg horizontal or vertical IP 30 IP 20 other characteristics temperature range climatic conditions for operation for storage - 5 °C to + 55 °C - 40 °C to + 70 °C (2) fault locating with other device mobile XGR portable generator and XRM receiver + probes (1) failsafe: the relay is disactivated either on occurrence of a fault or if the auxiliary supply voltage accidentally fails. (2) Suitable for use in all climates: c damp heat, equipment not operating (IEC 60068-2-30) c damp heat, equipment operating (IEC 60068-2-56) c salt mist (IEC 60068-2-52). auxiliaries c Cardew C surge limiter (only downstream of MV/LV transformer); c ZX impedance; c S3 inductive neutral point. 35 423E2100.PM6 35 24/07/06, 9:28 Vigilohm: functions and characteristics Vigilohm EM9BV insulation monitoring devices 042580 type of installation to be monitored LV AC IT systems phase-to-phase voltage with EM9BV connected to neutral with EM9BV connected to phase frequency limited in size < 760 V i 440 V 50-60-400-1000 Hz IT subsystem electrical characteristics 042581 ohmmeter use IT systems: c LV AC installations up to: v neutral distributed: 760 V, v neutral not distributed: 440 V; c one device only for each separate installation; c isolated from earth or connected to earth through a capacitive impedance. type range impedance maximum current injected fault number of thresholds signalling threshold setting response time device operating test fail safe device (1) output contact number type of contact breaking AC 400 V p.f. = 0.7 capacity 230 V p.f. = 0.7 DC 220 V L/R = 1 ms 120 V L/R = 1 ms 48 V L/R = 1 ms 24 V L/R = 1 ms maximum consumption auxiliary supply voltage 50/60 Hz auxiliary power supply operating range mechanical characteristics operation c injection of DC voltage; c an electronic device measures insulation from the leakage current created in the installation by the voltage injected and trips the alarm when insulation drops below the alarm threshold pre-set by the user. Earth coupling capacitances do not affect insulation measurement; c display of insulation resistance. installation and connection c live part in moulded, insulating, disconnectable, modular case, eight 9 mm modules wide, with transparent sealable cover; c mounting on symmetrical rail: v measurement module: horizontal or vertical, v display module: horizontal; c connection by tunnel terminals for 2.5 mm2 wiring, terminals 1 to 14. standards c UTE C 63-080; c IEC 364, chapters 4 and 5; c NF C 15-100 paragraphs 413 and 532; c NF C 15-211; c VDE 107; c VDE 413-2; c IEC 61557-8. weight thermoplastic case degree of protection measuring module display module mounting measurement module display module front case 36 0.4 kg 0.4 kg horizontal or vertical horizontal IP 30 IP 20 other characteristics temperature range - 5 °C to + 55 °C - 40 °C to + 70 °C for operation for storage climatic conditions (2) link between display module and measurement module shielded cable, 1 m max. length fault locating with other devices mobile XRG portable generator and XRM receiver + probes (1) failsafe: the relay is de-energized by occurrence of a fault or accidental failure of the auxiliary power supply voltage. (2) Suitable for use in all climates: c damp heat, equipment not operating (IEC 60068-2-30) c damp heat, equipment operating (IEC 60068-2-56) c salt mist (IEC 60068-2-52). auxiliaries c ZX impedance; c S3 inductive neutral point; c Cardew C surge limiter. 36 423E2110.PM6 digital 0 to 511 kΩ 100 kΩ 240 µA 1 (sealable) 1-2.5-5-10-25-50-75-100 kΩ i5s local optional 1 (stand. or fail safe) changeover 3A 5A 0.45 A 0.65 A 2.5 A 10 A 5 VA 115/127 V AC 220/240 V AC 380/415 V AC 440/480 V AC - 15 % to + 10 % 24/07/06, 9:28 Vigilohm: functions and characteristics 042582 Vigilohm EM9T insulation monitoring devices type of installation to be monitored LV AC IT systems phase-to-phase voltage with EM9T connected to neutral with EM9T connected to phase frequency limited in size i 380 V i 220 V 50-60-400-1000 Hz IT subsystem electrical characteristics impedance maximum current injected fault number of threshold signalling threshold setting use IT systems: c LV AC installations up to: v neutral distributed: 380 V, v neutral not distributed: 220 V; c one device only for each separate installation; c isolated from earth or connected to earth through a capacitive impedance; c specially designed for machine control and monitoring installations. operation c injection of DC voltage; c an electronic device measures insulation, from the leakage current created in the installation by the voltage injected and trips the alarm when insulation drops below the alarm threshold pre-set by the user. Earth coupling capacitances do not affect insulation measurement. installation and connection c live part in moulded, insulating, disconnectable, modular case, eight 9 mm modules wide, with transparent sealable cover; c horizontal or vertical mounting on symmetrical rail; c connection by tunnel terminals for 2.5 mm2 wiring, terminals 1 to 14. response time device operating test output contact number type of contact breaking capacity maximum consumption auxiliary supply voltage AC 400 V p.f. = 0.7 230 V p.f. = 0.7 DC 220 V p.f. = 1 ms 120 V L/R = 1 ms 48 V L/R = 1 ms 24 V L/R = 1 ms 50/60 Hz auxiliary supply voltage tolerances 100 kΩ 240 µA 1 (sealable) 10-20-40-60-80-100-120150 kΩ i5s local and remote 1 changeover 3A 5A 0.45 A 0.65 A 2.5 A 10 A 5 VA 24 V AC 48 V AC 115/127 V AC 220/240 V AC - 15 % to + 10 % mechanical characteristics weight thermoplastic case degree of protection mounting front case 0.4 kg horizontal or vertical IP 30 IP 20 for operation for storage - 5 °C to + 55 °C - 40 °C to + 70 °C other caractéristiques temperature range climatic conditions (1) fault locating with other devices mobile XRG portable generator and XRM receiver + probes (1) Suitable for use in all climates: c damp heat, equipment not operating (IEC 60068-2-30) c damp heat, equipment operating (IEC 60068-2-56) c salt mist (IEC 60068-2-52). standards c UTE C 63-080; c IEC 364, chapters 4 and 5; c NF C 15-100, paragraphs 413 and 532; c NF C 15- 211; c IEC 61557-8. auxiliaries c ZX impedance; c S3 inductive neutral point. 37 423E2110.PM6 37 24/07/06, 9:28 Vigilohm: functions and characteristics 017422 Vigilohm TR5A insulation monitoring device type of installation to be monitored LV DC voltage between polarities limited in size 24-42-48-120-220 260-420 V IT subsystem electrical characteristics fault signalling use IT systems: c LV DC installations up to 420 V; c isolated from earth. operation c a device with a high input impedance measures the variation in potential of the two polarities of the installation compared with earth. These variations are transformed into insulation signals; c auxiliary power comes from the monitored installation; c if monitoring and signalling are required, for an insulation fault evenly divided between both polarities, use the Vigilohlm System XM200. installation and connection c live part in moulded, insulating disconnectable, modular case eleven 9 mm modules wide, with transparent sealable cover; c horizontal flush or surface mounting on symmetrical rail; c connection by 6.35 mm tab connectors for 2.5 mm2 wiring. number of thresholds 1 (sealable) threshold setting DC 24 to 48 V installat. 5 to 25 kΩ DC 120 V installat. 10 to 50 kΩ DC 220 V installat. 30 to 150 kΩ DC 260 to 420 V installat. 30 to 150 kΩ response time on solid fault i1s device operating test yes failsafe feature (1) yes as an option changeover number 1 output contact breaking AC 230 V p.f. = 0.7 5A capacity DC 120 V L/R = 1 ms 0.65 A supply voltage tolerance (installation) - 20 % to + 20 % internal impedance between + or – DC 24 to 48 V installat. 24 kΩ polarity and earth DC 120 V installat. 46 kΩ DC 220 V installat. 154 kΩ DC 260 to 420 V installat. 166 kΩ between polarity DC 24 to 48 V installat. 38 kΩ DC 120 V installat. 55 kΩ DC 220 V installat. 82 kΩ DC 260 to 420 V installat. 132 kΩ mechanical characteristics weight plastic case degree of protection c UTE C 63-080; c IEC 364, chapters 4 and 5; c NF C 15-100, paragraphs 413.4-3; c IEC 61557-8. temperature range - 5 °C to + 55 °C - 40 °C to + 70 °C for operation for storage climatic conditions (2) fault locating with other devices XGR portable generator and XRM receiver + probes (1) failsafe: the relay is disactivated either on occurrence of a fault or if network voltage fails. (2) Suitable for use in all climates: c damp heat, equipment not operating (IEC 60068-2-30) c damp heat, equipment operating (IEC 60068-2-56) c salt mist (IEC 60068-2-52). 38 423E2120.PM6 38 0.5 kg horizontal IP 30 IP 20 other characteristics mobile standards mounting flush mounting surface mounting 24/07/06, 9:28 Vigilohm: functions and characteristics 051346 Vigilohm SM21 off-line insulation monitoring device type of de-energised installation to be monitored LV AC IT (de-energised) DC (de-energised) phase-to-phase voltage frequency voltage between polarities i 690 V (1) 50-60-400-1000 Hz i 690 V (1) electrical characteristics fault signalling number of thresholds threshold values ± 15 % prealarm alarm use monitors de-energised equipment (e.g. motors, fire pumps,...) whatever the earthing system. De-energised installations: c AC (up to 690 V) or DC (up to 690 V); c when associated with a circuit breaker possessing an MN or MX release or with a contactor, the SM21 protects motors against insulation faults that may be produced during operating shutdowns (e.g. due to condensation), by initiating an alarm or startup lock-out. response time device operating test alarm inoperative failsafe device (2) internal impedance changeover output contact yes DC AC 50-60 Hz alarm prealarm AC 230 V p.f. = 0.7 DC 120 V L/R = 1 ms 50/60 Hz number breaking capacity auxiliary supply voltage operation c injection of DC voltage. Voltage is applied, with the motor deenergised, between the stator and earth, thereby creating a leakage current in the motor insulation resistances; c 2 pre-set thresholds: v 1 prealarm threshold, adjustable in 8 steps from 0.5 to 10 MΩ, v 1 alarm threshold, adjustable in 8 steps from 0.25 to 2 MΩ. An electronic device measures insulation from the leakage current created by the voltage injected and activates the alarm or prevents starting when insulation drops below the corresponding threshold. installation and connection c live part in moulded, insulating, disconnectable, modular case, eight 9 mm modules wide, with transparent sealable cover; c horizontal or vertical mounting on symmetrical rail; c connection: wires up to 2.5 mm2; c the SM21 is used with a contact that opens to disconnect the device from the installation when the installation is energised. auxiliary supply voltage tolerances 2 0.5-1-1.5-2-3-57,5-10 MΩ 0.25-0.5-0.75-11.25-1.5-1.75-2 MΩ i1s yes by selector switch as standard (3) 1.6 MΩ 350 kΩ 1 standard 1 failsafe 5A 0.65 A 115/127 V AC 220/240 V AC 380/415 V AC 440/480 V AC 500/525 V AC - 15 % à + 10 % mechanical characteristics weight plastic case degree of protection mounting flush mounting surface mounting 0.3 kg horizontal/vertical IP 30 IP 20 other characteristics - 5 °C to + 55 °C - 40 °C to + 70 °C temperature withstand for operation for storage climatic conditions (4) (1) depends on rated voltage withstand of the contact used to disconnect the SM21 when the network is energised. (2) failsafe: the relay is disactivated on occurrence of a fault or if the auxiliary supply voltage accidentally fails. (3) only the first alarm contact. (4) Suitable for use in all climates: c damp heat, equipment not operating (IEC 60068-2-30) c damp heat, equipment operating (IEC 60068-2-56) c salt mist (IEC 60068-2-52). standards IEC 61557-8. 39 423E2120.PM6 39 24/07/06, 9:28 Vigilohm: functions and characteristics Vigilohm mobile fault locating kit XGR + XRM + probes 053130 type of installation to be monitored LV AC or mixed AC/DC IT systems DC or rectified IT systems phase-to-phase voltage with XGR connected to neutral with XGR connected to phase frequency voltage between polarities 760 V 440 V 45 to 400 Hz 500 V electrical characteristics auxiliary supply XGR voltage 115 to 525 V AC maximum consumption 15 VA IEC alkaline 9 V cell PP3 or 6 LR61 type not supplied type digital scale 0 to 19 by potentiometer 40 kΩ 2.5 mA XRM presentation The mobile fault locating kit comes in the form of a case containing: c a locating signal generator, XGR, supplied with 220 - 240 V AC; c a locating signal receiver XRM; c three tong-type current probes: XP15, XP50 and XP100. The devices making up the kit and the XGR for other voltages are all available individually. See catalogue number tables. display XRM calibration impedance maximum current injected XRM XGR XGR mechanical characteristics weight case probes (1) XP15 XP50 XP100 for cables up to for cables up to for cables up to ø 12 mm ø 50 mm ø 100 mm 047166 DB101070 (1) Maximum diameter of all live conductors together. PB100471 operation XGR locating signal generator 051350 c the XGR generator injects a 2.5 Hz AC voltage between the installation and the earth, thereby creating a leakage current which passes through the installation insulation impedance; c the XRM mobile receiver is associated with one of the three tong-type probes, XP15, XP50 or XP100, and detects this leakage current at 2.5 Hz. It displays a value between 1 and 19 according to the current passing through the probe, thus detecting the leakage current; c three current probes are available, the XP15, XP50 and the XP100, for cables with diameters up to 12, 50 and 100 mm respectively. Older probe models are not compatible with the XRM. plastic plastic 0.85 kg 0.2 kg portable portable associated equipment use The kit is used on LV IT systems (i.e. installations with an unearthed or impedance-earthed neutral). It enables fault locating on: c AC installations 50 to 400 Hz; c DC installations. It is used mainly with insulation monitoring devices that inject DC currents (TR22A, EM9B or EM9BV, etc.). XGR XRM XGR XRM XP15, XP50 and XP100 probes. Note: the photographs are for information purposes only. There are two types of probes that function in the same way but are different in shape and colour. XRM locating signal receiver 40 423E2130.PM6 40 24/07/06, 9:29 Vigilohm: functions and characteristics 051352 toroids 042589 Closed toroids (type A) E24290 E24281 characteristics toroids electrical characteristics type A transformation ratio 1/1000 c maximum permissible current: 1 kA continuous - 5 kA/1.5 s - 100 kA/0.05 s type OA 1/1000 c mechanical characteristics weight (kg) Split toroids (type OA) use The toroids are used to detect the earth leakage currents. They are used with the Vigilohm System for the detection, locating and measurement of earth fault currents on IT systems. Closed toroids (type A) are suitable for new installations and extensions. Split toroids (type OA) are suitable for renovated installations and extensions. ø 30 ø 50 ø 80 ø 120 ø 200 ø 300 ø 46 ø 110 0.120 0.200 0.420 0.590 1.320 2.230 1.300 3.200 other characteristics temperature range degree of protection for storage for operation – 55 °C to + 85 °C – 35 °C to + 70 °C IP30 (IP20 connectors) – 55 °C to + 85 °C – 35 °C to + 70 °C IP30 (IP20 connectors) functions These toroids detect leakage current and transmit a proportional signal to the associated receiver. compatibility All type A and OA toroids are compatible with the various devices of the Vigilohm System range: XD301, XD312, XD308C, XL308, XL316, XML308 and XML316. installation and connection Closed toroids (type A) c enclosed in an insulated casing; c 2 possibilities for mounting: v diam. 30-50-80 mm on symmetrical rail, v all diameters on plate and cables; c connection: v diam. 30 to 200 mm by tunnel terminals for 0.22 mm2 wires (minimum), v diam. 300 mm by 6.35 mm tab connectors. Split toroids (type OA) c enclosed in an insulated casing; c mounting on plate and cable; c connection by 5 mm diam. screws for 0.22 mm2 wires. 41 423E2130.PM6 41 24/07/06, 9:29 23 PE Figure 1. E13856B E13856A N1 N1 23 PE installation precautions Immunity to line overcurrents Line overcurrents, due to motor starting or transformer energising, may result in unnecessary fault detection by the detector. A number of simple precautions can help prevent this from happening: when used together they are even more effective: c place the toroid on a straight part of the cable; c carefully centre the cable in the toroid; c use a toroid with a diameter far larger than the diameter of the cable (2 x diameter), (figure 1). For severe operating conditions, use of a mild steel sleeve placed around the cable, in the toroid, considerably increases immunity. Recommended characteristics c mild steel foil, 1/10 mm thick, to be wound several times around the cable in the toroid (at least 1 mm thick); c internal diameter of toroid > 1.4 x external diameter of the cable bundle (figure 2); c toroid-detector link: v resistance i 3 Ω, v cross-sectional area of wires: 0.75 mm2 to 1.5 mm2, v maximum length: 50 m. Figure 2. sensors general characteristics type A closed toroid type OA split toroid type of installation to be monitored insulation voltage Ui closed sensor split sensor operating temperature storage temperature degree of protection LV 50/60/400 Hz 1000 V b - 35 °C / + 70 °C - 55 °C / + 85 °C IP30 (IP20 connectors) LV 50/60/400 Hz 1000 V b - 35 °C / + 70 °C - 55 °C / + 85 °C - 1/1000 b b 1/1000 b b IV 12 IV 12 electrical characteristics transformation ratio 3-phase short-circuit withstand current Icw of 100 kA/0.5 s differential short-circuit withstand current IDw of 85 kA/0.5 s (as per IEC 60947-2 in kA rms) overvoltage category rated impulse withstand voltage Uimp (kV) sensor characteristics rated operational current Ie (A) max. cross-section area of conductors per phase (mm2 of copper) TA30 PA50 IA80 65 85 160 25 50 95 MA120 SA200 GA300 POA 250 400 630 85 240 2 x 185 2 x 240 50 GOA 250 240 Diameter ø (mm) 30 50 80 120 200 300 - Weight (kg) 0.120 0.200 0.420 0.590 1.320 2.230 - Weight (kg) 1.300 3.200 mechanical characteristics type of sensor toroid TA30 toroid PA50 toroid IA80 toroid MA120 toroid SA200 toroid GA300 toroid POA toroid GOA Diameter ø (mm) 46 110 mounting horizontally or vertically on symmetrical DIN rail on plain or slotted backplate or profiled sheet metal on cable TA30, PA50, IA80, MA120 TA30, PA50, IA80, MA120, SA200 IA80, MA120, SA200, GA300 POA, GOA - 28 cycles + 25 °C/+ 55 °C / HR 95 % 48 hours, environment category C2 KB test, severity 2 3 0.98 1.42 3.19 3.89 7.05 28 cycles + 25 °C/+ 55 °C / HR 95 % 48 hours, environment category C2 KB test, severity 2 3 8.02 16.35 environment damp heat, equipment not operating (IEC 60068-2-30) damp heat, equipment operating (IEC 60068-2-56) salt mist (IEC 60068-2-52) degree of pollution (IEC 60664-1) calorific value (MJ) - (1) Allows use in all climates. 42 423E2130.PM6 42 24/07/06, 9:29 Vigilohm: functions and characteristics auxiliaries accessories can be provided: c essential auxiliary; v optional auxiliary. selection of auxiliaries A number of accessories are required for Vigilohm installations; other optional Vigilohm XM200 XM300C XML308 XML316 U < 760 VAC (4) 760 à 1700 VAC (4) U < 440 VAC (5) 440 à 1000 VAC (5) U < 500 VDC (6) 500 à 1200 VDC (6) "250 V " Cardew C (1) or "440 V" Cardew C (1) or "660 V" Cardew C (1) or "1000 V" Cardew C (1) or Cardew C base P1 subassembly ZX limiting impedance S3 inductive neutral point i 380V PHT 1000 additional subassembly c c c XGR c v v v v TR22A TR22AH EM9 EM9B EM9T cat. No c c c c v c (3) v v c c c c v c c c c v v v v v 50170 50171 50172 50183 50169 50211 50159 50113 50248 (2) (2) (2) (2) c except XM200 auxiliary characteristics connection 041857 Cardew C surge limiter E12128 c on LV network with isolated or impedanceearthed neutral; c connected to the secondary of the MV/ LV transformer to discharge overvoltages to earth; c capable of withstanding the short-circuit current of the transformer; c its operation causes continuous indication on the insulation monitor. L3 L2 L1 N MV/LV cardew C E12043 (1) See choice of the type of Cardew C (250, 440, 600 or 1000 V) below. (2) The use of a Cardew C is unnecessary with the EM9T. (3) Necessary for TR22A used on installations with U > 440 V. (4) Neutral distributed. (5) Neutral not distributed. (6) DC installation. Characteristics c non-arcing voltage at 50 Hz i 1.6 x nominal U; c certain arcing voltage at 50 Hz u 2.5 x nominal U (3 x nominal U for 220 V); c maximum current after arcing: 40 kA/0.2 sec; c insulation resistance > 1010 ohms; c cartridge not reusable; c temperature range: v operating: - 5 °C to + 40 °C, v storage: - 25 °C to + 70 °C. Standards NF C 63-150, NF C 15-100. Weight: 1 kg. Cardew selection table The selection depends on: c the operating voltage Un of the installation; c the installation insulation level; c the connection point (neutral-earth or phase-earth). Un: ph.-ph. operat. voltage of the AC instal. neutral distributed neutral not distributed U i 380 V U i 220 V 380 V < U i 660 V 220 V < U i 380 V 660 V < U i 1000 V 380 V < U i 660 V 1000 V < U i 1560 V 660 V < U i 1000 V Connecting conductor size c cable or bar with a size adapted to the transformer rating c the connecting conductor should be considered to be a protective conductor (PE) and the calculation of its crosssectional area must satisfy applicable installation standards, considering that this part of the installation is protected by protective devices located upstream of the MV/LV transformer; c according to standard IEC 364, the formula for the calculation of the of the size of the PE conductor is: S = √I2t/k where S is the cross-sectional area of the 160 50 130 Ø70 2 Ø13 2 Ø7 M12 Ui arcing voltage 400 V < Ui i 750 V 700 V < Ui i 1100 V 1100 V < Ui i 1600 V 1600 V < Ui i 2400 V 100 Cardew C "type" "250 V" "440 V" "660 V" "1000 V" PE conductor in mm2, I is the fault current, t is the operating time of the protective device and k is a coefficient that depends on the metal and insulation material used for the conductor. c recommendation: if insulation monitoring is provided using the Vigilohm System, install a type A toroid on the Cardew earthing circuit in order to monitor operation of the Cardew. The toroid can be connected to an XD301/ 312 detector or an XL308/316 or XML308/ 316 locating device. 43 423E2140.PM6 43 24/07/06, 9:29 E24299 1 2 019303 Dimensions, mounting Weight: 3.500 kg E24300 Connection c creates an installation with an impedanceearthed neutral; c remains connected during fault locating at 2.5 Hz: v 1500 Ω at 50 Hz, v 1M Ω at 2.5 Hz; c U i 500 V AC. ZX limiting impedance subassembly 185 360 380 L3 L2 L1 N MV/LV 190 170 15 4 Ø8,2 1 ZX IMD 2 E24336 019301 Dimensions, mounting Weight: 1.750 kg E24337 Connection c creates an artificial neutral point for insulation monitoring, with the main circuitbreaker open; c U i 380 V AC. S3 inductive neutral point subassembly L3 L2 L1 N MV/LV 166 150 1 2 3 4 130 150 4 Ø6 15 70 1 2 3 IMD S3 4 E19507 044139 Dimensions, mounting Weight: 2 kg 4 holes Ø 7 110 E19524 Connection c for use with the Vigilohm System XM300C and XML 308/316 on the following installations: v 440 V AC i U i 1000 V AC, neutral not distributed, v 760 V AC i U i 1700 V AC, neutral distributed, v 500 V DC i U i 1200 V DC: installation. PHT1000 additional subassembly 200 184 220 MV/LV 3 13 PHT XM 2 26 1 14 80 150 22 Connection c can be used to connect a TR22A to installation > 440 V AC; v 440 V AC i U i 1000 V AC, neutral not distributed, v 760 V AC i U i 1700 V AC, neutral di distributed. 140 128 Neutral not distributed E24311 E24312 Neutral distributed Dimensions, mounting Weight: 0.400 kg E24330 019302 P1 subassembly 4 1 5 1 RC P1 6 cardew C = = 4 63 5 RC 1 CPI 6 P1 6 cardew C 1 IMD 6 44 423E2140.PM6 44 24/07/06, 9:29 Ø5,2 40 65 insulation monitoring Vigilohm 3/ installation and connection page dimensions 46 connection 49 45 423E3000.PM6 45 24/07/06, 9:29 Vigilohm: installation and connection dimensions XM200, XM300C, XL308, XL316 Flush mounting E24342 E24341 Cutout 129 112 153 9,5 12 148 192 XML308, XML316 Flush mounting E24344 E24343 Cutout 129 112 229 12 9,5 224 192 XD308C Flush mounting E24318 E24317 Cutout 129 112 76 9,5 94 12 71,5 XD301, XD312 Surface mounting Cutout 65 XD301 XD312 2 Ø4,2 2 Ø4,2 37,5 49,5 73,5 XD301 XD312 57 73 5 XD301 2 Ø4,2 XD312 2 Ø4,2 66 66 45 E26420 E26419 E26419 Flush mounting 46 46 6,5 10 7 81 81 66 93 107 4,5 57 72 66 11 6,5 XLI200, XLI300, XTU300, XAS Cutout E24318 E24319 Flush mounting 129 112 76 9,5 192 8 71,5 XRM + probes XP15, XP50 and XP100 probes E26421 E12095 XRM manual receiver 145 37 Inside dimensions XP15: ø 12 mm. XP50: ø 50 mm. XP100: ø 100 mm. 80 46 423E3010.PM6 46 24/07/06, 9:29 93 106 7,5 TR22A, TR22AH Cutout E26445 E26444 Flush mounting IP40 112 129 76 9,5 94 71,5 8 EM9, EM9B, EM9BV, EM9T, SM21 Cutout Mounting on panel: use fixing lugs 20269. E21457 E26422 Mounting on symmetrical rail IP20 45 46 81 44 60 65,5 72 73 TR5A Flush mounting IP30 Door cutout (behind panel) and holes Mounting on symm. rail IP20 Mounting on panel IP20 Auxiliary subassembly aa > 220 V 2 screws M4 E12139 E24297 Ø4,2 32 45 44,5 77 64 77 37 68 99 53 99 26 99 E26423 XGR 59 108 189 47 423E3010.PM6 47 24/07/06, 9:29 Vigilohm: installation and connection dimensions (cont.) toroids (type A and OA) Ø5 1 2 F H E G K B Ø L H D 8 J E B type TA30 PA50 29 ø 30 52 B 31 45 C 60 87 D 53 66 E 82 108 F 50 60 type IA80, IE80 MA120, ME120 SA200, SE200 Mounting examples for type A toroids On XD301detector, ø 30 to 50 D 35 35 37 E F G 150 80 55 190 80 55 274 120 90 H 40 40 60 J K L 126 65 44 166 65 44 255 104 46 type ø H L GA300 299 29 344 On rail, ø 30 to 80 mm 042593 044866 ø B C 80 122 26.5 120 164 26.5 196 256 29 type ø H L B C POA 46 68 148 57 38 GOA 110 68 224 76 44 On plate or section, type A, ø 30 to 200 mm 042590 042592 044865 On cable, ø 120 to 300 mm 48 423E3020.PM6 H C D L 4 21 Ø C B Ø L 042591 5 Ø5 3 16 F Ø type OA ø 46 and 110 E24294 2 Ø4,5 type A ø 300 E24293 E18644 types A ø 80 to 200 E24291 type A ø 30 and 50 48 24/07/06, 9:29 Vigilohm: installation and connection E25115 E19526 XM200 E19515 connection XM200 10 9 8 7 6 5 ut MERLIN GERIN vigilohm system XM200 MV/LV 3 2 1 N prevention (failsafe feature) 4 cardew C fault XM200 11 test MV/LV 3 2 Sp C R Sa 1 S menu ok test 4 Tunnel terminals for 1.5 mm2 wiring Legend aa: AC auxiliary supply a -15 %, +10 %, 50-60 Hz ut: application r: installation terminal 11: earth connection by round lug (4 mm diameter) to be crimped. cardew C r 4 3 aa 2 1 XM200 11 + 11 4 XM200 E27116 XM300C 12 11 10 9 8 7 6 5 4 ut MERLIN GERIN vigilohm system XM300c ut test valeur d'isolement 040 K MENU TEST fault (failsafe feature) E19506 XM300C 3 2 1 N MV/LV 1 E17296 DB101055 11 address ut 14 1 fault 12 11 10 9 8 7 6 5 4 cardew C XM300C 13 4 prevention fault (failsafe feature) fault 3 MV/LV 2 21 23 20 24 19 1 I1 14 I2 cardew C XM300C 13 Tunnel terminals for 1.5 mm2 wiring 2 1 aa Legend aa: AC auxiliary supply a -15 %, +10 %, 50-60 Hz ut: application r: installation terminal 13: earth connection by round lug (4 mm diameter) to be crimped. *connection supplied with PHT1000. 13 18 17 16 15 14 22 VB V+ S + - 14 XM300C 13 E27168 r XM300C 23 * 2 1 aa 13 PHT1000 24 18 17 16 15 14 22 VB V+ S 1 2 3 E32439 DB101056 XML308, XML316 12 11 10 9 8 7 6 5 4 ut ut MERLIN GERIN vigilohm system XML31 6 XML308 XML316 fault (failsafe feature) 1 address 1 fault 4 prevention 21 4 5 6 7 8 2 10 11 12 13 14 15 16 valeur d'isolement 040 K MENU TEST 23 24 2 1 aa 13 20 19 18 17 16 15 14 22 t16 t9 1 test 3 1 9 E19509 r I1 I2 VB V+ S 2 1 t1 2 9-1 9-2 10-1 10-2 11-1 11-2 12-1 12-2 13-1 13-2 14-1 14-2 15-1 15-2 16-1 16-2 1 t8 2 1 1-1 1-2 2-1 2-2 3-1 3-2 4-1 4-2 5-1 5-2 6-1 6-2 7-1 7-2 8-1 8-2 3 2 1 N MV/LV 2 14 cardew C XML316 13 3 MV/LV 2 1 14 cardew C XML316 13 + Tunnel terminals for 1.5 mm2 wiring - r E17296 Legend: aa: AC auxiliary supply a -15 %, +10 %, 50-60 Hz ut: application r: installation t: toroid A or OA terminal 13: earth connection by round lug (4 mm diameter) to be crimped. ut 12 11 10 9 8 7 6 5 4 14 XML316 fault (failsafe feature) 13 fault 49 423E3020.PM6 49 24/07/06, 9:29 Vigilohm: installation and connection E32441 XL308, XL316 12 11 10 9 8 7 6 5 4 ut MERLIN GERIN vigilohm system XL316 test 3 4 5 6 7 XL308 XL316 fault (failsafe fealure) 2 9 10 11 12 13 14 15 16 1 fault 2 1 t1 1 2 2 1 t8 2 1 2 1 address ut 3 1-1 1-2 2-1 2-2 3-1 3-2 4-1 4-2 5-1 5-2 6-1 6-2 7-1 7-2 8-1 8-2 9-1 9-2 10-1 10-2 11-1 11-2 12-1 12-2 13-1 13-2 14-1 14-2 15-1 15-2 16-1 16-2 test/reset aa t16 t9 8 1 E17296 E19510 connection (cont.) 8 18 17 16 15 13 12 11 10 9 8 7 6 5 4 fault (failsafe feature) fault VB V+ S Tunnel terminals for 1.5 mm2 wiring E19525 Legend: aa: AC auxiliary supply a -15 %, +10 %, 50-60 Hz ut: application t: toroid A or OA terminal 13: earth connection by round lug (4 mm diameter) to be crimped XD308C XD308c aa E32443 t1 1 2 t8 - V B V+ S MERLIN GERIN vigilohm system XD308c Tunnel terminals for 1.5 mm2 wiring Legend: aa: AC auxiliary supply a -15 %, +10 %, 50-60 Hz t: toroid A or OA test 1 4 3 2 6 5 7 8 on reset test 1 3 4 5 6 7 8 9 10 11 address 4 E19516 8 Tunnel terminals for 1.5 mm2 wiring E27125 XD301 t Legend: aa: AC auxiliary supply a -15 %, +10 %, 50-60 Hz ut: application t: toroid A or OA 5 6 XD301 MERLIN GERIN vigilohm system XD301 test M reset 50507 7 8 9 10 11 M aa E19517 XD312 ut E19520 n° 1 n° 2 n° 12 1 2 3 4 5 6 7 8 9 1 2 3 4 5 6 7 8 9 10 11 12 MERLIN GERIN vigilohm system XD312 XD312 test M 10 11 12 reset 50536 M 15 16 21 22 23 26 Tunnel terminals for 1.5 mm2 wiring aa ut Legend: aa: AC auxiliary supply a -15 %, +10 %, 50-60 Hz ut: application t: toroid A or OA 50 423E3030.PM6 50 24/07/06, 9:29 XLI200, XLI300, XTU300, XAS E32434 MERLIN GERIN vigilohm system XLI300 défaut E16124 XLI300 Sub D9 RS485 1 signal ground 4 received data – 5 transmitted data – 8 received data + 9 transmitted data + XLI200/XLI300/XTU300 H JBUS address =H L L 18 V17 B not used 1 6 5 9 16 V+ 15 S RS232 1 XTU300 Sub D9 RS232 2 received data 3 transmitted data 5 signal ground 5 1 : GND 6 4 : B'(RD-) 5 : B(TD-) 9 8 : A'(RD+) 9 : A(RT+) 1 2 RS485 aa 13 XAS E16126 c never connect more than one interface to the Vigilohm System bus c to connect devices to the communication bus (shielded, double twisted pair), it is recommended to interconnect their respective terminals S, B, V + and V–. 18 V17 B 16 V+ 15 S 13 1 aa 2 E19518 Example of line connection XM300c V- V- V- B B B XL308 XL316 V+ S V+ S XD308c V+ VXML308 XML316 S B V+ S VXLI300 XTU300 XAS B V+ S 51 423E3030.PM6 51 24/07/06, 9:29 Vigilohm: installation and connection E12008 connection (cont.) When coupling two installations, one of the two Vigilohm insulation monitors must be disconnected momentarily. MV LV MV LV IMD E18471 IMD E27111 TR22A/TR22AH aa 2.5 mm2 wiring r S3 P1 Legend: aa: AC auxiliary supply, 50-60 Hz -15 %, +10 % 5 6 10 1 2 3 TR22A TR22AH MERLIN GERIN vigilohm TR 22AH KΩ 1 3 380-415 V 500-525 V r: installation S3: S3 subassembly (optional) ut: application P1: P1 subassembly (optional) 8 9 7 4 1 2 110-127 V 220-240 V 440-480 V 110-127 V a 220/415 V a 440/525 V a test Use with failsafe feature: the normally excited output relay is de-energised in the event of an auxiliary voltage failure (of internal or external origin) or an insulation fault. ut 5 TR 22A cardew C cardew C 4 LV/LV L3 L2 L1 N LV/LV L3 L2 L1 L1 L2 L3 N L1 L2 L3 1 P1 1 5 5 5 TR 22A TR 22A TR 22A 4 4 4 P1 6 5 1 2 3 10 5 10 6 L3 L2 L1 N E24326 L3 L2 L1 E26346 MV/LV auxiliary: S3 inductive neutral point subassembly U < 1000 V U < 1700 V E26347 L3 L2 L1 N U < 440 V E24325 MV/LV U < 760 V E24324 U < 440 V E24323 E24322 U < 760 V S3 TR 22A 6 TR 22A 4 TR 22A 4 4 4 E26417 TR5A 2.5 mm2 wiring 6.35 mm tab connector r E27134 + 1 2 Legend: r: installation DC power supply, - 20 %, + 20 % ut: application TR5A TR5A 3 6 7 8 E18566 r > 220 V MERLIN GERIN r – 1 2 TR5A 3 E26418 9 u. t. E26348 alarm 1 pre-alarm 2.5 mm2 wiring Legend: aa: supply 1 7 6 5 4 3 2 1 2 3 5 6 7 E26349 E27112 SM21 + 2 TR 3 5A Note: for a TR5A with failsafe feature, use terminals 6 and 7. + 1 2 3 4 auxiliary plate TR5A 5 L1 L2 L3 N M MERLIN GERIN vigilhom SM21 AL. REL. OK 8 0,75 1,5 1,5 5,0 0,5 1,75 1,0 7,5 Sa 9 10 0,5 2,0 0,25 50761 off 3,0 2,0 1,25 1,0 MΩ test Sp 10 11 12 13 SM21 13 SM 21 on 8 9 11 13 11 AL. REL. 14 a. a. c. a. Note: make sure that the auxiliary contact of the motor control system can withstand the rated voltage when the contact is open. 52 423E3040.PM6 52 24/07/06, 9:29 1 2 3 7 6 5 4 2.5 mm2 wiring ut E18461 E18465A E27114 EM9, EM9B, EM9T 1 2 3 EM9/EM9B MERLIN GERIN cardew C vigilohm EM9T test on 60 80 10 150 kΩ 10 11 12 13 14 3 E18465B ut tad 1 2 3 4 5 MERLIN GERIN EM9T vigilohm EM9BV test on S3 10 25 1 100 S3 50 5 75 2,5 50558 kΩ 8 9 10 11 12 13 14 13 14 E27113 8 9 1 2 3 4 cardew C 13 EM 14 3 2 1 13 EM 14 5 6 r aa 7 13 EM 14 EM9, EM9B Use with failsafe feature: the normally excited output relay is de- energised in the event of an auxiliary voltage failure (of internal or external origin) or an insulation fault. EM9T c remote test: terminals 4 and 5; c compliance with standard UTE C63-080. 7 6 5 4 LV/LV 3 2 1 13 EM 14 r aa E27117 2 13 14 8 9 EM9BV 1 13 EM 14 MV/LV E18462 120 50582 9 3 2 1 N 100 40 20 8 MV/LV MERLIN GERIN E18556 vigilohm EM9BV ut 50570 8 9 1 2 3 10 11 12 13 14 5 6 7 5 6 7 EM9BV Legend: aa: auxiliary supply, - 15 % + 10 % ut: application r: installation tad: remote test 13 14 8 9 8 9 r aa aa MV/LV a.a 3 2 1 N E27424 E27423 E27426 XGR IMD a.a: auxiliary supply r.: installation XGR XGR MERLIN GERIN E27425 + r IMD XGR 53 423E3040.PM6 53 24/07/06, 9:29 54 423E5000.PM6 54 24/07/06, 9:29 insulation monitoring Vigilhom 4/ catalogue numbers page Vigilohm insulation monitoring Vigilohm System Vigilohm System: accessories 56 58 59 55 423E5000.PM6 55 24/07/06, 9:29 423E5010.FM Page 56 Lundi, 24. juillet 2006 9:31 09 Catalogue numbers Vigilohm insulation monitoring E27111 Vigilohm TR22A/TR22AH vigilohm TR 22AH KΩ test Installation voltage (neutral not distributed): < 440 V AC With rectifiers: balanced fault detection TR22AH: special hospital version TR22A Single phase auxiliary power 115/127 V AC 50/60 Hz supply (V) 220/240 V AC 50/60 Hz 380/415 V AC 50/60 Hz 440/480 V AC 50/60 Hz 500/525 V AC 50/60 Hz TR22AH Single phase auxiliary power 115/127 V AC 50/60 Hz supply (V) 220/240 V AC 50/60 Hz 380/415 V AC 50/60 Hz 440/480 V AC 50/60 Hz 500-525 V AC 50/60 Hz 50395 50396 50397 50398 50399 50391 E27114 Vigilohm EM9 1 2 3 7 6 5 4 MERLIN GERIN vigilohm EM9T test on 80 60 100 40 120 20 150 10 50582 8 kΩ 9 1 0 1 1 1 4 1 3 1 2 Installation voltage (neutral not distributed): < 440 V AC Installations with high installation levels (adjustable threshold 10-150 kΩ) EM9 Standard model Single phase auxiliary power 115/127 V AC 50/60 Hz 50595 supply (V) 220/240 V AC 50/60 Hz 50597 380/415 V AC 50/60 Hz 50599 440/480 V AC 50/60 Hz 50601 Fail safe model 50596 50598 50600 50602 Installation voltage (neutral not distributed): < 440 V AC Installations with low insulation levels and capacitive installations (adjustable threshold 1-100 kΩ) EM9B Standard model Single phase auxiliary power 115/127 V AC 50/60 Hz 50555 supply (V) 220/240 V AC 50/60 Hz 50557 380/415 V AC 50/60 Hz 50559 440/480 V AC 50/60 Hz0 Hz 50561 Fail safe model 50556 50558 50560 50562 Installation voltage (neutral not distributed): < 440 V AC Digital display of insulation resistance (adjustable threshold 1-100 kΩ) EM9BV Standard model Single phase auxiliary power 115/127 V AC 50/60 Hz 50568 supply (V) 220/240 V AC 50/60 Hz 50570 380/415 V AC 50/60 Hz 50572 440/480 V AC 50/60 Hz 50574 Fail safe model 50569 50571 50573 50575 Installation voltage (neutral not distributed): < 220 V AC Machine control and monitoring (adjustable threshold 10-150 kΩ) EM9T Single phase auxiliary power 24 V AC 50/60 Hz supply (V) 48 V AC 50/60 Hz 115/127 V AC 50/60 Hz 220/240 V AC 50/60 Hz 50581 50582 50583 50584 E27117 Vigilohm EM9B 1 2 3 7 6 5 4 MERLIN GERIN vigilohm EM9BV test on 50 75 S3 100 1 50558 8 S3 25 10 5 2,5 kΩ 9 1 0 1 1 1 4 1 3 1 2 E27117 Vigilohm EM9BV 1 2 3 7 6 5 4 MERLIN GERIN vigilohm EM9BV test on 50 75 S3 100 1 50558 E27113 S3 25 10 5 2,5 kΩ 8 9 1 0 1 1 1 2 1 3 1 4 1 2 3 4 5 6 7 1 0 1 1 1 2 1 3 1 4 MERLIN GERIN vigilohm EM9BV 50570 8 9 E27114 Vigilohm EM9T 1 2 3 7 6 5 4 MERLIN GERIN vigilohm EM9T test on 80 60 100 40 120 20 150 10 50582 8 56 kΩ 9 1 0 1 1 1 2 1 3 1 4 423E5010.FM Page 57 Lundi, 24. juillet 2006 9:31 09 Catalogue numbers Vigilohm insulation monitoring (cont.) Vigilohm TR5A Installation voltage (neutral not distributed): < 420 V DC (adjustable threshold 5-150 kΩ) TR5A 5 4 3 2 E32741 1 MERLIN GERIN vigilohm TR5A test 120V 4 3 2 1 5 20 8 7 6 9 10 10 50381 50 kΩ 1 0 9 8 7 6 35 Power supplied by monitored installation (V) 24 V DC 42/48 V DC 120 V DC 220 V DC 260 V DC 420 V DC (1) with supplied external subassembly. (1) (1) Standard model 50340 50341 50342 50343 50350 50351 Fail safe model 50344 50345 50346 50347 E58548 Vigilohm SM21 1 7 6 5 4 3 2 MERLIN GERIN vigilhom SM21 AL. REL. OK 1,5 8 Sa 9 7,5 1 10 0,5 2,0 0,25 Sp MΩ 1 on 5,0 1,5 1,75 1,0 0,5 off 3,0 2,0 1,25 1,0 0,75 50761 test 1 1 AL. REL. 1 Installation voltage: < 690 V (1) SM21 Single phase auxiliary power 115/127 V AC 50/60 Hz 50760 supply (V) 220/240 V AC 50/60 Hz 50761 380/415 V AC 50/60 Hz 50762 440/480 V AC 50/60 Hz 50763 500/525 V AC 50/60 Hz 50764 (1) this voltage is depends on the rated voltage withstand performance of the open auxiliary contact used to isolate the SM21 from the installation. Mobile 2.5 Hz fault locating Kit case Mobile fault locating kit case containing: XGR (220/240 V) + XRM + XP15 + XP50 + XP100 probes 50310 Single phase auxiliary power supply (V) 50281 50282 50283 50284 E32436 Mobile XGR generator MERLIN GERIN 115/127 V AC 50/60 Hz 220/240 V AC 50/60 Hz 380/415 V AC 50/60 Hz 500/525 V AC 50/60 Hz E27131 / 27129 Mobile detector and probes XRM and XP15 probe XRM and XP50 probe XRM and XP100 probe XRM and XP50 + XP100 probes P12 on 50277 50287 50288 50289 P50 P100 MERLIN GERIN vigidix RM 10N XP15 probe 50494 Empty case for mobile fault locating kit 50285 Auxiliaries Vigilohm TR22A TR22AH EM9 EM9B EM9BV EM9T b (1) b (1) b (1) b (1) v "250 V" Cardew C or b "440 V" Cardew C or b "660 V" Cardew C or b "1 000 V" Cardew C b Cardew C base v P1 subassembly b ZX limiting impedance v v S3 inductive neutral point v v b compulsory auxiliary v optional auxiliary (1) Use of the Cardew C is not compulsory with the EM9T. TR5A SM21 50170 50171 50172 50183 50169 50211 50159 50113 57 423E5020.FM Page 58 Lundi, 24. juillet 2006 9:33 09 Catalogue numbers Vigilohm System Monitors Type of installation to be monitored: AC or mixed IT DC or rectified XM300C Single phase auxiliary power supply (V) E27126 MERLIN GERIN vigilohm system XM300c test E27115 valeur d'isolement 040 K MENU TEST XM200 Single phase auxiliary power supply (V) MERLIN GERIN vigilohm system XM200 test Sa Sp C R S test ok menu Neutral distributed Neutral not distributed Line voltage Voltage < 760 V AC (45/400 Hz) Voltage < 440 V AC (45/400 Hz) < 500 V DC 115/127 V AC 50/60 Hz 220/240 V AC 50/60 Hz 380/415 V AC 50/60 Hz 500/525 V AC 50/60 Hz 50540 50541 50542 50543 115/127 V AC 50/60 Hz 220/240 V AC 50/60 Hz 380/415 V AC 50/60 Hz 500/525 V AC 50/60 Hz 50727 50728 50729 50730 Monitors-locators Type of installation to be monitored: see XM300C IMD XML308 Single phase auxiliary power 115/127 V AC 50/60 Hz supply (V) 220/240 V AC 50/60 Hz 380/415 V AC 50/60 Hz 500/525 V AC 50/60 Hz XML316 Single phase auxiliary power 115/127 V AC 50/60 Hz supply (V) 220/240 V AC 50/60 Hz 380/415 V AC 50/60 Hz 500/525 V AC 50/60 Hz E32439 MERLIN GERIN vigilohm system XML31 6 test 3 6 5 4 7 8 1 2 9 10 11 12 13 14 15 16 valeur d'isolement 040 K MENU TEST 50490 50491 50492 50493 50322 50323 50324 50325 E32441 Locators MERLIN GERIN vigilohm system XL316 test 3 4 5 6 7 8 1 2 9 10 11 12 13 14 15 16 test/reset Type of installation to be monitored: see XM300C IMD XL308 Single phase auxiliary power 115/127 V AC 50/60 Hz supply (V) 220/240 V AC 50/60 Hz 380/415 V AC 50/60 Hz 500/525 V AC 50/60 Hz XL316 Single phase auxiliary power 115/127 V AC 50/60 Hz supply (V) 220/240 V AC 50/60 Hz 380/415 V AC 50/60 Hz 500/525 V AC 50/60 Hz 50606 50607 50608 50609 50615 50616 50617 50618 Detectors E27125 E32443 MERLIN GERIN vigilohm system XD308c test 1 2 3 4 5 6 7 8 on reset test MERLIN GERIN vigilohm system XD301 test M reset 50507 E27126 M 1 2 3 4 5 6 7 8 9 MERLIN GERIN vigilohm system XD312 test M 10 11 12 reset 50536 M 58 Type of installation to be monitored: see XM300C IMD XD308C Single phase auxiliary power 115/127 V AC 50/60 Hz supply (V) 220/240 V AC 50/60 Hz 380/415 V AC 50/60 Hz 500/525 V AC 50/60 Hz Type of installation to be monitored: see XM200 IMD XD301 Single phase auxiliary power 115/127 V AC 50/60 Hz supply (V) 220/240 V AC 50/60 Hz 380/415 V AC 50/60 Hz 500/525 V AC 50/60 Hz XD312 Single phase auxiliary power 115/127 V AC 50/60 Hz supply (V) 220/240 V AC 50/60 Hz 380/415 V AC 50/60 Hz 500/525 V AC 50/60 Hz 50723 50724 50725 50726 50506 50507 50508 50509 50535 50536 50537 50538 423E5020.FM Page 59 Lundi, 24. juillet 2006 9:33 09 Catalogue numbers Vigilohm System: accessories Toroids E27127 Closed toroid TA30 PA50 IA80 MA120 SA200 GA300 50437 50438 50439 50440 50441 50442 POA GOA 50485 50486 E27128 Opening toroid Shielded pair coil Roll of 20 m Roll of 100 m 50137 50136 XAS For operation of Vigilohm System bus without XLI300 or XTU300 (bus power supply) Single phase auxiliary power 115/127 V AC 50/60 Hz supply (V) 220/240 V AC 50/60 Hz 380/415 V AC 50/60 Hz 500/525 V AC 50/60 Hz 50520 50521 50522 50523 E32433 Interfaces MERLIN GERIN vigilohm system XD308c test 1 2 3 4 5 E32434 test 6 7 8 on reset MERLIN GERIN vigilohm system XLI300 E32435 défaut MERLIN GERIN vigilohm system XTU300 défaut XLI300 External transmission of Vigilohm System information on Jbus (bus power supply) Single phase auxiliary power 115/127 V AC 50/60 Hz supply (V) 220/240 V AC 50/60 Hz 380/415 V AC 50/60 Hz 500/525 V AC 50/60 Hz XTU300 External transmission of Vigilohm System information on Jbus Controls a configuration with multi IMDs/locators/communicating detectors (bus power supply) Single phase auxiliary power 115/127 V AC 50/60 Hz supply (V) 220/240 V AC 50/60 Hz 380/415 V AC 50/60 Hz 500/525 V AC 50/60 Hz XLI200 External transmission of Vigilohm System information on Jbus (bus power supply) Single phase auxiliary power 220/240 V AC 50/60 Hz supply (V) 380/415 V AC 50/60 Hz (*) (*) 50515 50516 50517 50518 (*) 50545 50546 50547 50548 50501 50502 E27131 / 27129 Mobile detector and probes P12 on P50 P100 MERLIN GERIN vigidix RM 10N XRM mobile detector and XP15 probe XRM mobile detector and XP50 probe XRM mobile detector and XP100 probe XRM mobile detector and XP50 + XP100 probes Empty case for mobile fault locating kit Probe XP15 50277 50287 50288 50289 50285 50494 E36226 Cardew surge limitor Cardew base Cardew cartridge 50169 50170 50171 50172 50183 250 V 440 V 660 V 1000 V E36227 Additional subassembly Used with XM300C or CML308/316 IMDs Type XM300C or CML308/316 AC or mixed IT IMDs Neutral distributed Neutral not distributed DC or rectified Line voltage 760 V AC < U < 1700 V AC (45/400 Hz) 440 V AC < U < 1000 V AC (45/400 Hz) 500 V DC < U < 1200 V DC PHT1000 50248 Zx limiting impedance Zx subassembly 50159 (*) Consult us. 59 423E5020.FM Page 60 Lundi, 24. juillet 2006 9:33 09 60 Schneider Electric Industries SAS 89, boulevard Franklin Roosevelt F - 92500 Rueil-Malmaison (France) Tel : +33 (0)1 41 29 85 00 As standards, specifications and designs change from time to time, please ask for confirmation of the information given in this publication. Printed on ecological paper. http://www.schneider-electric.com http://www.merlin-electric.com PLSED304015EN Design: Schneider Electric Photos: Schneider Electric Printed: Pont de Claix/JPF - made in France 08-2006 ART804690 © 2006 - Schneider Electric - All rights reserved. 423E0000_Guilding.fm Page 3 Lundi, 24. juillet 2006 9:35 09