FLOWAY
Dual-flow AHU
FLOWAY
The dual-flow air handling unit
with heat recovery guaranteeing an
Economical and Durable solution
Air flow rate:
Use
FLOWAY is a PLUG & PLAY dual-flow ventilation unit
equipped with a highly efficient heat recovery unit with plug
fans and high performance EC motors, designed to meet all
the requirements of recent thermal regulations.
Unit supplied ready to use, prewired, preprogrammed in the
factory and supplied with a remote control.
FLOWAY draws clean, fresh air indoors using, on average,
80% less energy than that needed for air conditioning (cooling
and heating).
These machines are designed for use in the following
applications:
é Service sector Buildings:
o Administrative buildings, Offices
o Education facilities, libraries, community centres
o Cafés, hotels, restaurants
Range
500 to 8500 m3/h
o Shops
o Nursing homes, healthcare facilities
o Collective housing
é All facilities where ventilation is required.
Classic model: 9 sizes, air flow from 300 to 8500 m3/h.
Floor-mounted horizontal unit with horizontal air flows and air
connections on the sides.
Vertical model: 4 sizes, air flow from 300 to 2600 m3/h.
Floor-mounted vertical unit with vertical air flows and air
connections on the top.
Ceiling-mounted model: 3 sizes, air flow from 300 to 1900 m3/h.
Ceiling-mounted horizontal unit with vertical air flows and air
connections on the sides.
FLOWAY "Classic"
MODELS
1000
1500
2000
2500
3000
4000
5000
6000
7500
Nominal Flow Rate
(m3/h)
1000
1500
2000
2500
3000
4000
5000
6000
7500
Max. power*
(Kw)
2 x 0.42
2 x 0.99
2 x 0.99
2 x 1.7
2 x 1.7
2 x 1.85
2 x 1.85
2 x 2.73
2 x 2.73
Max current*
(A)
6,2
3,6
3,6
5,5
5,5
6,1
6,1
8,7
8,7
Voltage
(V)
1-Ph 230
3-Ph 400
3-Ph 400
3-Ph 400
3-Ph 400
3-Ph 400
3-Ph 400
3-Ph 400
3-Ph 400
Nominal Flow Rate
(m3/h)
700
1000
1500
2000
Max. power*
(Kw)
2 x 0.42
2 x 0.42
2 x 0.99
2 x 0.99
Max current*
(A)
6,2
6,2
3,6
3,6
Voltage
(V)
1-Ph 230
1-Ph 230
3-Ph 400
3-Ph 400
Max. power*
(Kw)
2 x 0.42
2 x 0.42
2 x 0.99
Max current*
(A)
6,2
6,2
3,6
Voltage
(V)
1-Ph 230
1-Ph 230
3-Ph 400
FLOWAY "Vertical"
MODELS
700
1000
1500
2000
FLOWAY "Ceiling-mounted version"
MODELS
700
1200
1600
Nominal Flow Rate
(m3/h)
700
1200
1600
* These values are given as a guide for a dual-flow unit fitted as standard, without standard option (electric heater).
HEAT PUMPS - AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 12.674 A
1
Dual-flow AHU
FLOWAY
Electric heaters
nElectric elements encased in a copper finned layer to ensure uniform distribution of heat.
nHigh-limit safety thermostat with automatic and manual reset.
nControl by 2-stage on/off operation (3 stages, depending on the model) fully controlled by "Floway Control".
MODELS
Classic 1000
Vertical 700 & 1000
Ceiling-mounted 700 & 1200
Classic 1500
Vertical 1500 (external)
Ceiling-mounted 1600
Vertical 1500 (internal)
Classic 2000 & 2500
Classic 3000
Classic 4000
Classic 5000
Classic 6000
Classic 7500
Power (kW)
Voltage (V)
Current (A)
4,5
1-Ph 230
20
7,2
3-Ph 400
11
8,1
10,8
12,6
16,8
19,8
22,8
31,2
3-Ph 400
3-Ph 400
3-Ph 400
3-Ph 400
3-Ph 400
3-Ph 400
3-Ph 400
12
16
19
25
29
34
46
Description
Casing
nDouble-skin panels made from sheet steel, galvanised on both
sides, thickness 8/10 mm.
nRAL 7035 and RAL 7024 grey lacquer coated finish on external
panels.
nM0/A1 fire rating
nMineral wool, thickness 50 mm.
Filtration
nF5, F7, F8 or F9 filters.
nFilter cells kept compressed by a special system to ensure a
leaktight seal.
nFilter fouling value monitored by analogue sensor and
displayed by controller.
Ventilation
n"Plug Fan" type direct drive FMA.
nPlug fan driven by an electronically commutated motor with
built-in speed control.
Heat recovery units
nCounter-flow plate heat exchanger with motorised partial
bypass (ceiling-mounted and vertical models).
é Efficiency greater than 80% across the range of air flows.
nRotary heat exchanger equipped with speed control
("Classic" model).
é Efficiency greater than 80% at nominal flow rate.
Electrics box
nElectrics box for power, control and internal regulation of
the unit, comprising:
-P
ower supply (3-Ph/400 V/Earth or 1-Ph/230 V/Earth).
-M
ain disconnect switch.
-P
rotected transformer.
-
Protection and control of all electrical components by a
circuit-breaker and contact switch.
-P
eripheral options and power terminal block.
-C
ontrol by factory pre-programmed CAREL pCO3 PLC.
-
Hand-held cabled micro-terminal (cable length provided:
6 m).
- Fault summary contact.
- 3 temperature sensors.
- 4 pressure sensors.
Accessories
Damper with airfoil blades driven by an on/off spring-return
actuator.
Flexible sleeve
Adjustable feet
CO2 air quality sensor
Sound trap
Roof
Canopy
Mixing section
Indoor environment switch
Hydraulic Coil
Copper pipes, aluminium fins.
nCoil can be integrated or additional (cased)
nWith the accessory fitted, 3-way control valve and 0-10V
actuator controlled by "Floway Control" for setpoint accuracy.
nGalvanised condensate drain pan (cooling coil or mixed coil
only).
2
HEAT PUMPS - AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 12.674 A
Dual-flow AHU
Control
FLOWAY Control
"FLOWAY CONTROL" control function (software V2.2)
Fan Timer programming
Safety
Alarms
Control mode
Hot air and/or Cold air
production
Free cooling operation
Night cooling operation
Included Options*
Integrated clock: management in series
4 events per year, and per week and per day
X
Frost protection
By Fresh Air Temperature control
By Exhaust air flow pressure on heat recovery unit delta control
(pressure sensor)
X
X
Monitoring of sensor status
Monitoring operation values (thresholds)
Operating control of EC fan motor assemblies via a fault summary contact
"Control of filter fouling (automatic calculation of "Dirty filter" and "Blocked filter" alarm thresholds)
Main and ordinary fault summary
Fire monitoring (potential free (dry) contact available (normally closed))
Management of alarms and log (100)
Control of return air or supply air temperature
X
X
X
X
X
X
X
X
Regulated temperature control based on Outdoor temperature
X
Control of room temperature with a room terminal (Th-Tune)
Gradual action on the 3V hydraulic coil control valve
Gradual action on the electric heater TRIAC
On/Off action on the various stages of the electric heaters
Rotary heat exchanger stop (CLASSIC model)
Open bypass on counter flow plate recovery unit (VERTICAL & CEILING-MOUNTED model)
Rotary heat exchanger stop (CLASSIC model)
Open bypass on counter flow plate recovery unit (VERTICAL & CEILING-MOUNTED model)
X
X
X
X
X
X
X
X
Morning heating operation Control degree of opening of mixing bypass (CLASSIC model)
X
ECO recirculation operation Control degree of opening of mixing bypass (CLASSIC model)
X
Optimisation of output
Configuration of the air
flow rate
Variation of the rotation speed of the rotary recovery unit (CLASSIC model)
2 air flow rate setpoints per air flow
Display of the air flow rate
Overpressure/negative pressure management
Constant flow rate operation Keeps the air flow rate constant regardless of how fouled the filters are
Modulation of flow rates
operation
Communicating mode
Miscellaneous
CO2 sensor
Presence contact
contact
External contact
Multi zone
Intake duct constant pressure operation
MODBUS protocol
LON protocol
Management by CMS
KNX protocol
TCP/IP protocol
Languages supported (French/English/German/Dutch/Spanish/Italian)
Integrated temperature sensors (*3: fresh air supply and extraction, exhaust air extraction)
Integrated pressure sensors (*4: fresh air and exhaust air filter fouling level, fresh air and exhaust air fan)
Damper control
Information provided to the user via the hand-held micro terminal
Contact for controlling the pumps for the hydraulic coils (with operating control)
Contact for controlling an external outdoor heat production system (boiler, etc.)
Contact for controlling a humidifier
Single zone
X
X
X
X
X
signal 0-10V
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
Option*: Requires the component to be selected as an option_damper, coil, CO2 sensor,...
HEAT PUMPS - AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 12.674 A
3
FLOWAY
FLOWAY features, as standard, an electrics box equipped with a factory-programmed PLC and a hand-held micro-terminal.
Dual-flow AHU
Dimensions
FLOWAY
and directions of air flows
FLOWAY "CLASSIC"
MODELS
DIMENSIONS
Length
1360
557+847
557+847
800+800
800+800
800+800
800+800
800+800
800+800
Height
908
1158
1158
1359
1359
1659
1659
1959
1959
1000
1500
2000
2500
3000
4000
5000
6000
7500
* Without internal option
WEIGHT *
Width
810
1010
1010
1210
1210
1510
1510
1810
1810
201
303
309
413
432
558
604
702
751
Size 1000
Sizes 1500 and 2000
1404
1009
404
303
1310
302
271
47.2
1073
1159
85
421
467
55
n3
55
n3
Sizes 2500 to 7500
B
D
A
E
C
MODELS
2500
3000
4000
5000
6000
7500
4
A
1600
1600
1600
1600
1600
1600
B
1210
1210
1510
1510
1810
1810
Dimensions (mm)
C
1359
1359
1659
1659
1959
1959
D
990
990
1284
1284
1584
1584
E
510
510
612
612
762
762
HEAT PUMPS - AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 12.674 A
Dual-flow AHU
FLOWAY
Direction of air flow
ROTS 1.1
ROTS 2.2
ROTS 1.2
ROTS 2.1
WHITE ARROW = FRESH AIR
BLACK ARROW = EXTRACTED AIR
HEAT PUMPS - AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 12.674 A
5
Dual-flow AHU
FLOWAY
FLOWAY "VERTICAL"
DIMENSIONS
MODELS
Height
1385
1526
1758
1901
700
1000
1500
2000
Length
1313
1456
1593
1735
WEIGHT *
Width
730
730
832
832
202
243
330
389
Ø 16 mm condensate drain pipe
* Without internal option
Size 700
1313
730
702
47
1270
584.5
193
231
492.5
n250
239
1238
n2
50
50
n2
70
231
1385
1338
n250
6
n4
584.5
492.5
100
272
193
124
Size 1000
1456
730
701
47
1411
660
222
n315
231
529
239
1379
15
n3
231
70
223
660
529
313
n46
100
1526
5
n315
1479
n3
1
124
6
HEAT PUMPS - AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 12.674 A
Dual-flow AHU
Size 1500
1550
805
730
248
253
572
n355
295
1611
n35
5
55
n3
70
253
1758
1711
n355
248
730
572
100
349
6
n4
124
Size 2000
832
1735
805
47
1692
620
824
253
n35
5
n35
5
70
253
1754
295
n35
5
824
620
385
248
n35
5
100
1901
1854
n46
248
124
WHITE ARROW = FRESH AIR
BLACK ARROW = EXTRACTED AIR
HEAT PUMPS - AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 12.674 A
7
FLOWAY
832
47
1593
Dual-flow AHU
FLOWAY
FLOWAY "CEILING-MOUNTED VERSION"
DIMENSIONS
MODELS
Height
585
585
585
700
1200
1600
Length
1453
1592
1850
WEIGHT
Width
896
1174
1456
161
206
279
Ø 16 mm condensate drain pipe
Size 700
WHITE ARROW = FRESH AIR
BLACK ARROW = EXTRACTED AIR
n
Size 1200
1498
1224
1174
1202
47
1592
280
8
938
280
HEAT PUMPS - AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 12.674 A
47
Dual-flow AHU
n13
.5
Size 1600
WHITE ARROW = FRESH AIR
1456
1484
1506
FLOWAY
BLACK ARROW = EXTRACTED AIR
47
1762
47
1856
280
601
280
B
253
A
601
6
n1
474.5
AIR CIRCULATION DIMENSIONS (mm)
A
B
C
D
700
306
306
Ø160
Ø315
1200
398
398
Ø250
Ø355
1600
499.5
499.5
Ø250
Ø400
71
C
C
D
MODELS
HEAT PUMPS - AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 12.674 A
9
Dual-flow AHU
FLOWAY
ADDITIONAL CASING (MUST ONLY BE POSITIONED IN A HORIZONTAL AIR FLOW.)
Additional casing size
Weight
(kg)
Classic 1000
Vertical 700 & 1000
Ceiling-mounted 700
Size1
496x809x543
49 Kg
Classic 1500 & 2000
Vertical 1500 & 2000
Ceiling-mounted 1200 & 1600
Size 2
495x1009x642
64 Kg
Classic 2500 & 3000
Size3
400x759x1210
68 Kg
Classic 4000 & 5000
Size 4
400x909x1510
88 Kg
Classic 6000 & 7500
Size 5
400x1069x1810
112 Kg
FLOWAY MODELS
Size 1
Size 2
1009
809
504
405
505
321
371
221
271
404
Size 3
Size 4
793
759
906
1510
1210
Size 5
1069
1810
10
HEAT PUMPS - AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 12.674 A
Dual-flow AHU
Classic model performance
Operating pressure = f(flow)
Pa
1000
FLOWAY
800
3000
5000
2500
500
2000
4000
1500
1000
300
7500
6000
100
500
0.278
1000
1500
2000
2500
0.556
3000
3500
0.833
4000
1.111
4500
5000
5500
1.389
6000
1.667
6500
7000
7500
8000
1.944
m 3/h
8500
2.222
9000
m 3/s
Performancerecov = f(flow)
%
Clean F7 filter
Heat recovery unit conditions:
0°C / 90% & 20°C / 50%
90
86
82
78
7500
5000
3000
1000
2000
74
6000
4000
2500
1500
70
500
1000
0.278
SFPby
1500
2000
2500
0.556
fan
m 3/h
3000
0.833
3500
4000
1.111
4500
5000
5500
1.389
6000
1.667
6500
7000
1.944
7500
8000
8500
2.222
9000
m 3/h
= f(flow)
W/(m3/h)
0.35
Clean F7 filter
Heat recovery unit conditions:
0°C / 90% & 20°C / 50%
Duct pressure: 200Pa
SFPv=0.3 W/(m3/h)
RT reference output
1500
2000
1000
5000
3000
0.25
6000
4000
2500
7500
0.15
500
0.278
1000
1500
0.556
2000
2500
0.833
3000
3500
1.111
4000
4500
1.389
5000
5500
1.667
6000
6500
1.944
7000
7500
8000
2.222 m 3/s
HEAT PUMPS - AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 12.674 A
8500
9000
m3/h
11
Dual-flow AHU
FLOWAY
“Vertical” model performance
Operating pressure = f(flow)
Pa
1000 0.139
0.417
0.278
0.694
0.556
m3/s
800
1500
500
1000
700
2000
300
100
500
1000
1500
2000
2500
m3/h
Performancerecov = f(flow)
% 0.139
0.278
0.556
0.417
0.694 m3/s
Clean F7 filter
Heat recovery unit conditions:
0°C / 90% & 20°C / 50%
88
84
1000
700
1500
2000
80
500
SFPby
1000
fan
1500
2000
0.417
0.556
m3/h
2500
= f(flow)
W/(m3/h)
0.139
0.35
0.278
0.694
m3/s
Clean F7 filter
Heat recovery unit conditions:
0°C / 90% & 20°C / 50%
Duct pressure: 200Pa
SFPv=0.3 W/(m3/h)
RT reference output
2000
1500
0.25
700
1000
0.15
500
12
1000
1500
2000
2500
m3/h
HEAT PUMPS - AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 12.674 A
Dual-flow AHU
Ceiling model performance
Operating pressure = f(flow)
0.139
1000
m3/s
0.417
0.278
0.556
FLOWAY
Pa
800
1600
500
1200
700
300
100
500
1000
1500
m3/h 2000
Performancerecov = f(flow)
%
88
m3/s
0.278
0.139
0.556
0.417
Clean F7 filter
Heat recovery unit conditions:
0°C / 90% & 20°C / 50%
86
84
82
700
1200
1600
80
500
SFPby
1000
fan
1500
2000
m3/h
= f(flow)
W/(m3/s)
0.35
0.139
0.278
m3/s
0.556
0.417
Clean F7 filter
Heat recovery unit conditions:
0°C / 90% & 20°C / 50%
Duct pressure: 200Pa
=0.3 W/(m3/h)
SFPv
RT reference output
0.25
1600
1200
700
0.15
500
1000
1500
HEAT PUMPS - AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 12.674 A
2000
m3/h
13
Dual-flow AHU
FLOWAY
This document is not legally binding. As part of its policy for continual product improvement, CIAT reserves the right to make any technical modification it considers necessary without prior notice.
Registered address
Avenue Jean Falconnier - B.P. 14
01350 - Culoz - France
Tel.: +33 (0)4 79 42 42 42
Fax: +33 (0)4 79 42 42 10
[email protected] - www.ciat.com
CIAT Service
Tel.: 08 11 65 98 98 (0.15 €/min)
Fax: 08 26 10 13 63 (0.15 €/min)
Compagnie Industrielle d’Applications Thermiques - S.A. with a registered capital of 26,728,480 € - R.C.S. Bourg-en-Bresse B 545 620 114
14