[PSS 1-8A1 D] Foxboro Model 83F Flanged Body Vortex Flowmeters

Transcription

[PSS 1-8A1 D] Foxboro Model 83F Flanged Body Vortex Flowmeters
Product Specifications
PSS 1-8A1 D
Foxboro Model 83F Flanged Body Vortex Flowmeters
Foxboro Model 83W Wafer Body Vortex Flowmeters
with 4 to 20 mA Analog and Pulse Outputs
83W
83F
83F
STANDARD
TEMPERATURE
VERSION
EXTENDED TEMPERATURE
VERSION WITH DIGITAL
INDICATOR/CONFIGURATOR
STANDARD TEMPERATURE VERSION
WITH ISOLATION VALVE
The Models 83F-A and 83W-A are part of a family of high performance, flanged and wafer body vortex
flowmeters. They transmit a user-selectable 4 to 20 mA analog or a pulse output signal. An on-board flowrate
indicator is provided with a selection of scales for either the analog or pulse output.
FEATURES
• Used on liquids, gases, and steam.
• 4 to 20 mA and pulse flowmeter outputs; userselectable.
• Outputs compatible with all types of totalizing and
control loops.
• Rangeablility up to 100:1.
• Wide temperature range up to 800°F (430°C).
• Field adjustable low flow cut-in selections.
• Pulse train smoothing enhances low flow
measurement.
• Isolation valve offered to allow sensor replacement without interrupting flow in pipe.
• Rapid response time.
• Temperature K-factor correction.
• Flow rate indicator with a selection of scales for
both 4 to 20 mA and pulse output.
• Dual measurement capability (83F only).
• Hastelloy C or stainless steel bodies and flanges.
• FlowExpertPro™ sizing program greatly
simplifies flowmeter selection.
• Can be used in hazardous area locations.
• A very wide selection of sizes:
– Flanged Body: 3/4 to 12 in (DN 15 to DN 300)
– Water Body: 3/4 to 8 in (DN 15 to DN 200)
• Conforms to applicable European Union
directives (including PED).
LIFETIME WARRANTY
Sensor Warranty against workmanship and material
defects for lifetime of flowmeter – contact Invensys
Foxboro.
PSS 1-8A1 D
Page 2
FlowExpertPro™
FlowExpertPro is a program primarily used to size
Foxboro flowmeters. It also ensures that the user has
selected the proper flowmeter type for his application.
Invensys provides this meter selection tool as a free
web site to all users, without the need for registration.
In addition to flowmeter selection and sizing,
FlowExpertPro includes the following features:
• Incorporates a large library of the physical
properties of typical process fluids.
• Displays results in tabular or graphic format.
• Allows user to save, print, or E-mail results.
• Provides reference to applicable flowmeter PSSs
and other related flowmeter documentation.
The program calculates minimum and maximum flow
rates, rangeability, pressure loss, and Reynolds
Number, using established flow equations. It also
allows for material and flange selection, and provides
ANSI or metric flange recommendations for predicted
flow pressures and temperatures. You are invited to
visit www.FlowExpertPro.com to access this program,
or contact Invensys for further information, and
technical support.
HIGH PERFORMANCE AT LOWER COST
The Invensys Foxboro patented family of vortex
flowmeters has the high accuracy and rangeability of
positive displacement and turbine flowmeters without
the mechanical complexity and high cost. Maximum
rangeability up to 100:1 is possible as compared to
3:1 for a nonlinear differential pressure producer
(orifice plate). Because these Flowmeters have no
moving parts, they are very durable and reliable. This
simplicity of design ensures low initial cost, low
operating and maintenance costs, and therefore
contributing to an overall low cost of ownership.
SIMPLIFIED START-UP
Invensys Foxboro pre-configures the flowmeter using
flow data supplied by the customer. No primary
device calculations or mechanical calibrations are
required if the flow data is supplied when placing the
order. This allows the user to simply install the flowcalibrated flowmeter and connect wiring to the proper
power source and readout or control instrumentation,
and the 83F-A or 83W-A is ready to measure flow.
When flow data is not provided, flowmeter is shipped
partially configured. On-site configuration can be
completed using easily accessible DIP-switches.
OUTPUT IS COMPATIBLE WITH ALL TYPES OF
TOTALIZING AND CONTROL LOOPS
These flowmeters transmit two different types of
output signals that are linearly proportional to
volumetric flow rate. The flowmeters produce a pulse
rate signal for totalizing and batching, or an electronic
analog 4 to 20 mA dc signal for recording and control
of flow rate.
OTHER Foxboro VORTEX FLOWMETERS (Table Below)
Model Description
Output
Reference
83F-D
Flanged
FoxCom or PSS 1-8A1 E
83W-D Wafer
Pulse
83F-T
Flanged
HART or
83W-T
Wafer
Pulse
83F-F
Flanged
FOUNDATION PSS 1-8A1 F
83W-F
Wafer
Fieldbus
83S-D
Sanitary
FoxCom or PSS 1-8A2 D
Pulse
83S-T
Sanitary
HART or
Pulse
83S-A
Sanitary
4 to 20 mA PSS 1-8A2 E
or Pulse
84F-T
Flanged
HART or
PSS 1-8A3 A
84W-T
Wafer
Pulse
84S-T
Sanitary
HART or
PSS 1-8A5 A
Pulse
WIDE VARIETY OF APPLICATIONS
The 83F Flowmeter is available in 3/4 to 12 in (DN 15
to DN 300) line sizes. The 83W Flowmeter is
available in nominal 3/4 to 8 in (DN 15 to DN 200) line
sizes. Water velocities (at standard conditions) up to
25.3 ft/s (7.7 m/s), and gas or steam velocities up to
600 ft/s (185 m/s) can be measured. These
flowmeters set the example for industry standards
whether the application requires accuracy for
totalizing and batching; utility metering of fluids in the
process industries; fuel, air, steam, or gas metering
for the measurement of energy in any high use
application; or stability and repeatability for process
control.
COMPACT, EFFICIENT, AND DURABLE DESIGN
The flowmeter mounts between ANSI or metric raised
face flanges. See Model Code section for end
connections offered with each line size. Other flange
face surfaces can be used as a custom design.
The electronics housing is of explosionproof and
flameproof construction and provides environmental
protection to the enclosed electronics. It is offered
integrally mounted to the flowtube, or can be mounted
remotely.
The flowmeter’s simple, modular design requires
minimum maintenance. Common, field replaceable
parts are used, including the sensor assembly and
amplifier. The amplifier can be replaced without
interrupting the flow in the pipe, and sensor can be
replaced without process shutdown when an isolation
valve is installed. Since a single device is used for
multiprocess-fluid applications, ordering is simplified
and spare part needs minimized.
ISOLATION VALVE
An isolation valve allows the sensor to be removed or
replaced without interrupting the flow in the pipe.
PSS 1-8A1 D
Page 3
FLOW RATE INDICATOR
DESIGNED FOR USE IN HAZARDOUS LOCATIONS
A Flow Rate Indicator is available for both the analog
(4 to 20 mA) and pulse output flowmeters. Linear
indicator scales, either 0 to 100% or with ten equally
spaced divisions, are offered for both output versions.
The Flow Rate Indicator is a Model Code Selection.
These flowmeters have been designed to meet the
approval requirements of many certifying agencies for
use in hazardous area locations. Refer to “Product
Safety Specifications” section.
REMOTE MOUNTED ELECTRONICS HOUSING
Remote mounting is offered to allow access to the
amplifier and other housing electronics when the
measurement is not in an easily accessible location.
The remote housing is supported by a bracket, which
in turn mounts to a surface or to a nominal 2-in or
DN 50 pipe. This housing can be located up to a
cable length of 50 ft (15.2 m) from the flowtube
without loss of low level signal.
This family of flowmeters displays the CE designation
indicating conformance to the applicable European
Community Standards for immunity to sources of
electromagnetic interference. This compliance also
includes conformance to a maximum level of selfgenerated electromagnetic energy, and includes PED
(Harmonized Pressure Equipment Directive for the
European Community). See table below for details.
DUAL MEASUREMENT FLOWMETER (84F ONLY)
Dual Measurement Vortex Flowmeters provide the
user with redundant sensors and electronics. Two
electronics housings and sensors are mounted to a
common flowmeter body assembly. Should one
transmitter fail, the redundant measurement avoids
the necessity of shutting down the process. The failed
transmitter can then be replaced at some later
noncritical time. Applications include Safety Shutdown
Systems (independent of Process Measurement
Network), Safety Backup for critical flow loops,
Comparative Verification of Measurement for high
accuracy precision loops, or just for dual
communications paths with the same primary
element.
Invensys Foxboro has elected to offer the PED
(Harmonized Pressure Equipment Directive for the
European Community) certification only with meters
ordered with the ATEX Electrical Safety Code Model
Code selections. ATEX electrical certifications are in
place for N and E codes. Therefore the CE marking
carries the ATEX number.
CE COMPLIANCE
PED
Meter
Size
3/4 and 1 in (DN 15
and DN 25) (a)
1 1/2 in (DN 40)
and larger
Electrical
Safety
Design Code
CE
Marking
N or E
CE 0344
N or E
CE 0344,
CE 0575
(a) Line sizes 1 inch and smaller are only required to meet SEP Sound Engineering Practice to be compliant with the PED
directive.
PSS 1-8A1 D
Page 4
OPERATING CONDITIONS(a)
Influence
Process Fluid
Process Temperature
Ambient Temperature
(Electronics Housing)
Relative Humidity
Supply Voltage:
• Pulse
• Analog(c)
Loop Load:
• Pulse
• Analog(c)
Calibration Operating
Conditions(b)
Normal Operating
Condition Limits
Operative Limits
Clear Water
70 to 85°F
(20 to 30°C)
70 to 85°F
(20 to 30°C)
50 to 90% RH
Liquid
0 and 400°F
(–18 and +200°C)
–40 and +185°F (d)
(–40 and +85°C) (d)
0 and 100%
Liquid
0 and 400°F
(–18 and +200°C)
–40 and +185°F (d)
(–40 and +85°C) (d)
0 and 100%
24 V dc
24 V dc
10.5 and 50 V dc
10.5 and 50 V dc
10.5 and 50 V dc
10.5 and 50 V dc
R = 100 kΩ, C = 0 µF
300 Ω (c)
R = 100 kΩ, C = 0.05 µF 0
and 1925 Ω (c)
R = 10 kΩ min, C = 0.05 µF 0
and 1925 Ω (c)
(a) Limited to nonflashing, noncavitating conditions. Flow rate and temperature of process may induce flashing and cavitation which is
dependent on pressure drop and process vapor pressure. A minimum positive back-pressure is required for proper operation.
(b) Assumes compatible process piping and fittings; gaskets not protruding into process line; a minimum of thirty pipe diameters of
straight pipe upstream of flowmeter and eight pipe diameters downstream; clear water free of air or particles.
(c) The loop load can vary as listed, depending on the supply voltage used. See Figure 2 for a plot of supply voltage vs. loop load.
(d) Refer to Electrical Safety Specifications section for a restriction in ambient temperature with certain electrical certifications.
PERFORMANCE SPECIFICATIONS
(Under Calibration Operating Conditions unless Otherwise Stated)
Factory Calibrated Flow Ranges
Factory-Calibrated Flow Range for Water (c)
Nominal Meter
Size
Nominal Mean
K-Factor in
Pulses/ft3 (Pulses/L) (a)
Range in
US gpm
Range in L/s
Reynolds Number
Range
3/4 in (DN 15)
1 in (DN 25)
1 1/2 in (DN 40)
2 in (DN 50)
3 in (DN 80)
4 in (DN 100)
6 in (DN 150)
8 in (DN 200)
10 in (DN 250) (b)
12 in (DN 300) (b)
5580 (197)
2250 (79.5)
570 (20.1)
258 (9.11)
78.7 (2.78)
34.8 (1.23)
10.00 (0.353)
4.26 (0.150)
1.99 (0.0703)
1.16 (0.0410)
6.9 to 34
8.9 to 56
14 to 140
18 to 230
34 to 500
59 to 890
140 to 2000
240 to 3600
390 to 5800
560 to 8400
0.43 to 2.1
0.56 to 3.5
0.88 to 8.7
1.1 to 15
2.1 to 32
3.7 to 56
8.5 to 130
15 to 220
24 to 370
36 to 530
30 000 to 150 000
30 000 to 190 000
30 000 to 300 000
30 000 to 380 000
38 000 to 570 000
50 000 to 750 000
76 000 to 1 100 000
100 000 to 1 500 000
130 000 to 1 900 000
160 000 to 2 300 000
(a) The K-factor is the relationship between input (volumetric flow rate) and the output (pulse rate).
Reference K-factor: The arithmetic mean value of K-factor over a designated flow rate range (reference conditions).
The mean K-factor is derived as:
Mean K-factor = (KMAX + KMIN) / 2
Where KMAX is the Maximum K-factor and KMIN is the Minimum K-factor over the calibrated flow range.
(b) The 10 and 12 in (DN 250 and DN 300) flowmeters are available with the Model 83F only.
(c) Factory calibrated Reynolds Number range applies to standard temperature sensor without isolation valve. Other sensor
selections and manifold selections may alter the calibration range. See FlowExpertPro for specific calibration ranges.
PSS 1-8A1 D
Page 5
PERFORMANCE SPECIFICATIONS (Cont.)
The accuracy below 20 000 RD is not specified
because the K-factor deviates from its reference
value at low flows. For applications below 20 000 RD,
the I/A Series Intelligent Vortex Flowmeter is
recommended. See PSS 1-8A1 E.
Accuracy for Liquids (see Figure 1 and NOTE)
Accuracy within factory-calibrated Reynolds Number
range is ±0.5%. Outside the calibrated range, the
accuracy is ±1% of reading for flow rates with
Reynolds Number of 20 000 or greater.
Accuracy for Gases and Steam (see NOTE)
Accuracy is ±1% of reading for flow rates with
Reynolds Number of 20 000 or greater.
NOTE
To achieve the accuracies stated for the fluids
above, the flowing density and viscosity must
be input during meter configuration.
Relative Humidity Effect
There is no effect due to relative humidity as long as
the covers and seals are properly installed.
Process Liquid Viscosity Effect
The viscosity of liquids must be known when
choosing a vortex flowmeter for low flow
applications. High viscosity will reduce the ability of
the flowmeter to measure low flow. Below
RD 30 000, the accuracy is affected by an increasing
positive linearity error reaching about +2% at
10 000 RD . Below an RD of 10 000, accuracy is not
easily predictable - however, calibration of a given
flowmeter is repeatable. An indication of flow may be
possible to as low as 5 000 Reynolds Number. Use
the FlowExpertPro Sizing Program for process
viscosity/Reynolds Number limits.
SEE FACTORY CALIBRATION
FLOW RANGES TABLE FOR
REYNOLDS NUMBER RANGE
+2%
ACCURACY
Accuracy - General
The accuracy of the meters, stated in next
paragraphs, is under calibration operating conditions
(see Operating Conditions table). Installation
parameters such as location of valves, proximity to
elbows, etc., will affect the accuracy of the flow
measurement. Data is presented in MI 019-189 to
correct the measurement for these effects.
+1%
+
_ 0.5%
-1%
-2%
5
0
20
10 000
30 100 000
REYNOLDS NUMBER
1 000 000
Figure 1. Flowmeter Accuracy for Liquids
Flow Overrange Effect
Overranges beyond 25% of maximum velocity could
result in sensor damage with subsequent loss of
signal.
WITH PULSE OUTPUT
No significant effect on accuracy or loss of signal.
WITH ANALOG OUTPUT
Analog signal is limited to 20 mA dc maximum,
and, therefore, may not reproduce true flow rate
measurement above 20 mA.
Process Temperature Effect on K-Factor
The K-factor reference is factory-determined at
reference conditions. When the actual process
temperature is provided, Invensys Foxboro
calculates the flowing K-factor to correct for
temperature effects. Calculation procedures to
manually change the flowing K-factor are contained
in Master Instruction MI 019-189.
Ambient Temperature Effect (Amplifier only)
WITH PULSE OUTPUT
No pulse rate change above low flow cut-in.
WITH ANALOG OUTPUT
For 55°C (100°F) change in ambient temperature
within operative limits.
Zero (4 mA): ±0.25% of span maximum
Span (16 mA): ±0.25% of span maximum
Supply Voltage Effect (Within Stated Limits)
WITH PULSE OUTPUT
No effect on accuracy
WITH ANALOG OUTPUT
Less than 0.01% per 1.0% voltage change.
PSS 1-8A1 D
Page 6
PERFORMANCE SPECIFICATIONS (Cont.)
Vibration Effect
Vibration can affect the flow measurement output of
a Vortex flowmeter in the form of added pulses, but
with the built-in Tuning functions and Low Flow Cutin adjustability, these effects can be minimized.
Invensys Foxboro has tested this meter with
vibrations up to 3 “g” of acceleration with no physical
damage, no shift in calibration after the test, and no
loss of communications throughout the test.
Emission Effect
Radiated and conducted electromagnetic emissions
meet the requirements of North America and
NAMUR.
Electromagnetic Compatibility (RFI)
The output error from RFI at radio frequencies
ranging from 27 to 1 000 MHz is less than ±1% of
span at a field intensity of 10 V/m; and less than
±2% of span at a field intensity of 30 V/m. This
applies only when the electronics housing is
properly earthed (grounded).
Position Effect (Filled Pipe Conditions)
For most applications, the flowmeter can be
mounted in a pipeline which may run in any direction
from the vertical (flow in upward direction) to the
horizontal. Measurement of liquid and gas streams
is not affected by the pipeline orientation or the
flowmeter orientation in the pipeline.
For saturated steam, the recommended flowmeter
position is in a horizontal pipe with the electronics
housing located below the pipeline.
For superheated steam, the flowmeter is usually
best mounted in a horizontal or inclined pipe with the
electronics housing located above the pipeline.
Measuring superheated steam in vertical pipelines
requires that the electronics housing and sensor
compartment be free of intermittent condensate. It is
recommended that the sensor be insulated to insure
at least 10°F (6°C) of superheat.
Refer to recommended Mounting Arrangements
section for further information.
PSS 1-8A1 D
Page 7
FUNCTIONAL SPECIFICATIONS
Power Supply Requirements
PULSE MODE
Supply Voltage Limits: See Figure 2.
Supply Current: 15 mA dc.
ANALOG MODE
Supply Voltage Limits: See Figure 2.
Supply Current: 22 mA dc
European Union Directives
• Complies with Electromagnetic Compatibility
Requirements of European EMC Directive
89/336/EEC by conforming to the following
CENELEC and IEC Standards: EN 50081-2,
EN 50082-2, EN 61326, and IEC 61000-4-2
through 61000-4-6.
• Complies with NAMUR NE 21 Interference
Immunity Requirement (EMC).
• Conforms to Applicable European Union
Directives (“CE” Logo marked on product).
Low Flow Cut-in Adjustment
Pulse and analog versions have low flow cut-ins to
optimize amplifier performance as a function of fluid
density and minimum fluid velocity. Field-adjustable
by low flow cut-in switches. Flow rate settings will
change by a nominal factor of 2 for each sequence
of cut-in switch position.
Span Adjustment
Not required for pulse version. For analog version,
the output is factory set and is field-adjustable with
coarse and fine span potentiometer.
Zero Adjustment
No suppression or elevation. The analog output
version is factory set to 4.00±0.01 mA and has a
potentiometer to adjust the zero to 4.00 mA.
Reference K-Factor
The reference K-factor is a coefficient that specifies
the flowmeter calibration and is expressed as the
ratio of pulses per unit volume, where pulses/unit
volume = pulses per second divided by volume flow
per second. The reference K-factor is the specific
factor for a given flowmeter body and is the
arithmetic mean value of K over the factorycalibrated flow range.
1925
EXTERNAL LOAD RESISTANCE, (Ω)
Output Signal
PULSE OUTPUT
Square wave voltage equals supply voltage minus
two volts. Maximum current is 10 mA (sink or
source). Shielded and twisted cable is
recommended.
ANALOG OUTPUT
4 to 20 mA dc into a maximum of 1925 Ω
depending on power supply. See Figure 2.
TYPICAL SUPPLY
VOLTAGE AND
LOAD LIMITS
V dc
LOAD Ω
1000
800
0 & 657
0 & 950
0 & 1047
24
30
32
600
400
OPERATING
AREA
200
0
0
10
10.5
20
30
40
50
SUPPLY VOLTAGE, V dc
Figure 2. Supply Voltage vs. Load Resistance
Reference K-Factor Determination
The reference K-factor is determined at the factory
flow facility by actual flow calibration with water by
comparison to a master flowmeter calibration or by
actual static weight. Both calibrations are traceable
to NIST (National Institute of Standards and
Technology). The reference K-factor embedded in
the flowmeter data base and is stamped on the data
plate.
Flowing K-Factor
The flowing K-factor is computed from the
K-reference expressed in specific flowing units, and
can be corrected for the following:
– Process Temperature
– Mating Pipe
– Upstream Disturbances
Nominal Flow Velocity Limits
These limits can be calculated using Table 1 below.
In the table, ρ f is the process fluid density at flowing
conditions in lb/ft3 or kg/m3, as applicable. The
specifications apply for most applications, but can
deviate slightly for some combinations of density
and line size. Also refer to FlowExpertPro.Com.
Table 1. Nominal Flow Velocity Limits
Std.Temperature
High Temperature
Range
Range
Range
Limit
ft/s
m/s
ft/s
m/s
Lower
2.0/ ρ f
2.4/ ρ f
4.0/ ρ f
4.8/ ρ f
Upper
200/ ρ f
240/ ρ f
200/ ρ f
240/ ρ f
PSS 1-8A1 D
Page 8
FUNCTIONAL SPECIFICATIONS (Cont.)
Flowmeter Rangeability
The flowmeter has an enhanced rangeability
compared to other Vortex Flowmeters due to its
lower LFCI capability and improved frequency
filtering. Rangeability of up to 100:1 is achievable.
Flowmeter Ranges
Flowmeter is shipped with flow range specified in the
sales order or with a default flow range equal to the
meter capacity. It can be reranged by the user
keeping the same flowrate units, choosing new
flowrate units from a built-in menu-selectable list, or
entering custom flowrate units. Also refer to
FlowExpertPro.Com.
Static Pressure Limits
MINIMUM
The minimum static pressure is that pressure
which is sufficient to prevent flashing, and meet the
pressure drop requirements to attain maximum
flow rate. Refer to FlowExpertPro sizing programs.
MAXIMUM
1500 psi (10 340 kPa) or that imposed by flange
rating piping.
Approximate Pressure Loss (Pressure Drop)
The maximum pressure loss at maximum flow for
every flowmeter with any fluid is 8 psi (55 kPa). For
many flow conditions, however, the actual pressure
loss is much less than 8 psi (55 kPa). Use the
FlowExpertPro Sizing Program to determine actual
pressure loss for a given set of conditions.
Minimum Back Pressure (Volatile Liquids or Low
Pressure Conditions)
Any condition that tends to contribute to the release
of vapor from the liquid (flashing, which may also
induce cavitation) shall be avoided by proper system
design and operation of the flow-meter within the
rated flow rate range. Location of flowmeter should
determine the need for incorporating or considering
a back-pressure valve, or for increasing inlet
pressure. To avoid flashing and to ensure stable
vortex generation, the minimum back pressure
should be:
PG = (3)(∆P) + (1.25)(pv) - (patm)
where
PG = Gauge pressure in psi or kPa five pipe
diameters downstream of the flowmeter
∆P = Calculated pressure loss in psi or kPa (see
“Approximate Pressure Loss” section)
pv = Vapor pressure at line conditions in psi or
kPa absolute
patm = Atmospheric pressure in psi or kPa
absolute
Flange Pressure-Temperature Ratings
See Figures 3 to 8 for ANSI and metric flange
pressure-temperature ratings. Also see Figure 9 for
pressure-temperature limits when isolation valves
are used. Also note the temperature limit when
fluorolube fill (200°F/90°C) or silicone fill
(400°F/200°C) is used, or when no fill (800°F/430°C)
is used with extended temperature applications. The
flange ratings in Figures 3 through 8 are also
embedded in the FlowExpertPro sizing program.
PSS 1-8A1 D
Page 9
FUNCTIONAL SPECIFICATIONS (Cont.)
200°F
FLUOROLUBE
SENSOR
LIMIT
400°F
SILICON
SENSOR
LIMIT
800°F
EXTENDED
TEMP. LIMIT
(NO FILL)
1600
CLASS 600
1440
1400
CAST TUBES
FLANGE MAT’L
3/4 TO 4 in: CF8M
04S1: 316 ss
PROCESS PRESSURE, psig
1200
1000
CLASS 300
845 psig
800
720
600
420 psig
400
CLASS 150
275
200
80 psig
0
-20
0
100
200
300
400
500
600
PROCESS TEMPERATURE, °F
700
800
Figure 3. ANSI Flange Ratings; per ASME B16.5; Group 2.2 Materials
200°F
FLUOROLUBE
SENSOR
LIMIT
SILICON
SENSOR
LIMIT
400°F
800°F
EXTENDED
TEMP. LIMIT
(NO FILL)
1600
CLASS 600
1440
1400
FABRICATED TUBES
FLANGE MAT’L
6 TO 12 in: 304 ss
PROCESS PRESSURE, psig
1200
1000
CLASS 300
810 psig
800
720
600
400
405 psig
CLASS 150
275
200
80 psig
0
-20
0
100
200
300
400
500
600
PROCESS TEMPERATURE, °F
700
800
Figure 4. ANSI Flange Ratings; per ASME B16.5; Group 2.1 Materials
PSS 1-8A1 D
Page 10
FUNCTIONAL SPECIFICATIONS (Cont.)
200°F
FLUOROLUBE
SENSOR
LIMIT
1600
1480
400°F
SILICON
SENSOR
LIMIT
800°F
EXTENDED
TEMP. LIMIT
(NO FILL)
CLASS 600
FABRICATED TUBES
FLANGE MAT’L
6 TO 12 in: cs
1400
PROCESS PRESSURE, psig
1200
1000
CLASS 300
825 psig
800
740
600
410 psig
400
CLASS 150
285
200
80 psig
0
-20
0
100
200
300
400
500
600
PROCESS TEMPERATURE, °F
700
800
Figure 5. ANSI Flange Ratings; per ASME B16.5; Group 1.1 Materials
90°C
FLUOROLUBE
SENSOR
LIMIT
120
200°C
SILICON
SENSOR
LIMIT
430°C
EXTENDED
TEMP. LIMIT
(NO FILL)
CAST TUBES
PN 100
PROCESS PRESSURE, bar
100
FLANGE MAT’L
DN 15 TO
DN 100: CF8M
04S1: 316 ss
80
67.8 bar
PN 64
64
60
42.7 bar
PN 40
40
27.1 bar
PN 16
20
10.8 bar
16
0
0
-10
90
100
200
300
PROCESS TEMPERATURE, °C
400
450
430
Figure 6. Metric Flange Ratings; Material Group 14E0
PSS 1-8A1 D
Page 11
FUNCTIONAL SPECIFICATIONS (Cont.)
90°C
FLUOROLUBE
SENSOR
LIMIT
120
200°C
430°C
EXTENDED
TEMP. LIMIT
(NO FILL)
SILICON
SENSOR
LIMIT
FABRICATED TUBES
FLANGE MAT’L
DN 150 TO
DN 300: 304 ss
PN 100
PROCESS PRESSURE, bar
100
80
PN 64
64
54.2 bar
60
PN 40
34.1 bar
40
21.6 bar
PN 16
20
8.6 bar
16
0
0
-10
90
100
200
300
PROCESS TEMPERATURE, °C
400
450
430
Figure 7. Metric Flange Ratings; Material Group 10E0
90°C
FLUOROLUBE
SENSOR
LIMIT
120
200°C
SILICON
SENSOR
LIMIT
430°C
EXTENDED
TEMP. LIMIT
(NO FILL)
FABRICATED TUBES
PN 100
PROCESS PRESSURE, bar
100
FLANGE MAT’L
DN 150 TO DN 300: cs
80
PN 64
64
60
42.5 bar
PN 40
40
26.8 bar
PN 16
17.0 bar
20
6.8 bar
16
0
0
-10
90
100
200
300
PROCESS TEMPERATURE, °C
400
450
430
Figure 8. Metric Flange Ratings; Material Group 3E0
PSS 1-8A1 D
Page 12
FUNCTIONAL SPECIFICATIONS (Cont.)
200°F
FLUOROLUBE
SENSOR
LIMIT
800°F
400°F
SILICON
SENSOR
LIMIT
EXTENDED
TEMP. LIMIT
(NO FILL)
1600
1440
1400
EXTENDED TEMP.
VALVE WITH
GRAPHITE SEAT
P-T LIMITS
WITH
ISOLATION
VALVE
PROCESS PRESSURE, psig
1200
1000
845 psig
800
STANDARD TEMP.
VALVE WITH
GLASS-FILLED
ptfe SEAT
LINEARLY
INTERPOLATED
600
500
400
200
0
-20
0
100
200
300
400
500
600
PROCESS TEMPERATURE, °F
90°C
FLUOROLUBE
SENSOR
LIMIT
120
38°C
800
200°C
430°C
EXTENDED
TEMP. LIMIT
(NO FILL)
SILICON
SENSOR
LIMIT
EXTENDED TEMP.
VALVE WITH
GRAPHITE SEAT
100
PROCESS PRESSURE, bar
700
P-T LIMITS
WITH
ISOLATION
VALVE
80
58.3 bar
60
STANDARD TEMP.
VALVE WITH
GLASS-FILLED
ptfe SEAT
LINEARLY
INTERPOLATED
40
35
204°C
20
0
0
-10
50
90
100
150
250
350
200
300
PROCESS TEMPERATURE, °C
400
430
450
Figure 9. Pressure-Temperature Limits with Isolation Valve; U.S. Customary and Metric Units
PSS 1-8A1 D
Page 13
PHYSICAL SPECIFICATIONS
Process-Wetted Parts - Model 83F
FLOWMETER BODY, FLANGES, AND SHEDDING
BAR (ALSO SEE MODEL CODE)
316 ss up to 4 in (DN 100) sizes;
304 ss body and shedder, and cs or ss flange, for
sizes >4 in (>DN 100).
GASKETS AND FLOW DAM (SENSOR SEALS)
– Standard Temperature Sensor
- ptfe gasket and flow dam
– High Temperature Sensor
- 316 ss gasket; 316 ss/grafoil flow dam
- Hastelloy C gasket; Hastelloy C/grafoil flow dam
Process-Wetted Parts - Model 83W
FLOWMETER BODY AND SHEDDING BAR
(ALSO SEE MODEL CODE)
316 ss for all sizes; or
Hastelloy C for 3/4 to 4 in (DN 15 to DN 100) sizes.
GASKETS AND FLOW DAM (SENSOR SEALS)
– Standard Temperature Sensor
- ptfe gasket and flow dam
– High Temperature Sensor
- 316 ss gasket; 316 ss/grafoil flow dam
- Hastelloy C gasket; Hastelloy C/grafoil flow dam
Dual Measurement Manifold - Model 83F Only
CF8M stainless steel; pressure and temperature
rating of dual manifold same as flowmeter body.
Flowmeter Mounting
Flowmeter can be located in a pipeline which may
run in any direction from the vertical (upward flow) to
the horizontal. The electronics housing can also be
rotated 270° (in 90° increments) with respect to the
body. A vertical pipeline is preferred for batch
operations to provide improved full line assurance.
See Recommended Mounting Arrangements section.
Electrical Connections
Field wires enter through 1/2 NPT conduit threaded
entrances on either side of the electronics housing.
Wires terminate under screw terminals and washers
on terminal block (see Figure 14) in the field terminal
compartment. Unused entrance is plugged to insure
moisture and RFI/EMI protection.
TEST TERMINALS
TERMINAL BLOCK
MOUNTING HOLES.
TWO PLACES
(+) AND (-)
POWER
TERMINALS
PULSE
OUTPUT
TERMINALS
+
A
B
Figure 10. Terminal Block
Electronics Module
Printed wiring assemblies (PWAs) are conformally
coated for moisture and dust protection.
Environmental Protection
Electronics housing is dusttight and weatherproof
per IEC IP66 and provides the environmental and
corrosion resistant protection of NEMA Type 4X.
Isolation Valve (if specified, see Model Code for
Selection Options)
VALVE BODY
Grade CF8M stainless steel
VALVE BALL
316 ss
VALVE SEATS
Standard Temperature: Glass-Filled ptfe
Extended Temperature: Graphite
STEM SEAL
The valve stem seal meets the external leakage
requirements for fire safety per API Standard 607.
VALVE HANDLE
Use adjustable wrench.
SEAT LEAKAGE
Standard Temperature
Class IV – Less than 5 mL/h per MSS-SPG1.
High Temperature
Class IV per ANSI/FCI-70.2
FLOW VELOCITY LIMITS
See “Flow Velocity Limits” section.
APPLICATIONS
Recommended for use with clean liquids,
saturated steam, and all gases.
LIMITATIONS
Not recommended for use with superheated steam
without insulation, or liquids with suspended solids.
MOUNTING
See MI 019-202 for installation guidelines.
PRESSURE/TEMPERATURE RATING
Both standard and extended (high) temperature
isolation valves have a maximum pressure rating of
1440 psi at 100°F (100 bar at 38°C). The standard
temperature valve with ptfe seats is further limited
to a maximum pressure of 500 psi at 400°F (35 bar
at 204°C). The extended temperature valve has an
ANSI Class 600 temperature and pressure rating.
See Figure 9.
NACE Certification
The stainless steel material option has been
designed, and materials selected, to meet the
requirements of NACE (National Association of
Corrosion Engineers) Standard MR-01. A NACE
compliance certificate is available by selecting the
-Q option.
PSS 1-8A1 D
Page 14
PHYSICAL SPECIFICATIONS (Cont.)
Process Connections
83F FLANGED BODY FLOWMETERS
Refer to the 83F Model Code for the availability of
body material, flange material, flange types, and
body/flange construction for each line size.
83W WAFER BODY FLOWMETERS
Refer to the 83W Model Code for the availability of
body material and mounting/centering system for
each line size when mounted between the different
flange types. Wafer body flowmeters must be
properly aligned to provide optimum accuracy, and
alignment spacers are provided to achieve this
alignment. Carbon steel bolting kits can also be
provided as listed in the Optional Selections and
Accessories section.
Dimensions
Refer to Dimensions - Nominal section for general
outline data. For more dimensional details, refer to
the following Dimensional Prints (DPs).
Dimensional
Model
Configuration
Print
83F
Single Measurement
83F
Dual Measurement
83W (a) Single Measurement (a)
DP 019-150
DP 019-151
DP 019-152
(a) The 83W is not available as Dual Measurement Flowmeter.
Approximate Weight
See Tables 2 to 6.
Table 2. 83F Vortex Flowmeters – Flanged Body: Approximate Weight with ANSI Class 150 Flanges
Nominal
Line Size
in
DN
DN 15
3/4
DN 25
1
1 1/2 DN 40
DN 50
2
DN 80
3
DN 100
4
DN 150
6
DN 200
8
10 DN 250
12 DN 300
With Integral Mounted Electronics Housing With Remote Mounted Electronics Housing
Flowmeter Weight(a)
Flowmeter Weight(b)
Electronics
Sensor Types
Sensor Types
Sensor Types Sensor Types
Housing
D, F, R, & S
C&T
D, F, R, & S
C&T
Weight(c)
lb
kg
lb
kg
lb
kg
lb
kg
lb
kg
11.0
5.0
11.7
5.3
9.0
4.1
9.9
4.5
5.0
2.3
13.2
6.0
13.9
6.3
11.0
5.0
11.9
5.4
5.0
2.3
16.0
7.3
16.7
7.6
14.0
6.4
15.0
6.8
5.0
2.3
20.2
9.2
21.0
9.5
18.0
8.2
19.0
8.6
5.0
2.3
33.2
15.1
33.9
15.4
29.0
13.2
30.0
13.6
5.0
2.3
45.0
20.5
45.8
20.8
43.0
19.5
44.0
20.0
5.0
2.3
72.2
32.8
72.8
33.1
70.0
31.8
71.3
32.3
5.0
2.3
125.0
56.6
125.4
57.0
121.0 54.9 122.0 55.3
5.0
2.3
190
86.2
190.0
86.2
185.0 83.9 187.0 84.8
5.0
2.3
265.0
120.0
265.0
120.0
260.0 118.0 262.0 119.0
5.0
2.3
(a) Weight of complete flowmeter, including integral electronics housing.
(b) Flowmeter Weight is weight of flowtube with sensor plus bonnet plus junction box.
(c) Housing Assembly Weight (for all Sensor Type selections) is weight of electronics housing assembly plus mounting bracket.
Table 3. 83W Vortex Flowmeters – Wafer Body: Approximate Weight
Nominal Line
Size
in
DN
3/4 DN 15
1
DN 25
1 1/2 DN 40
2
DN 50
3
DN 80
4
DN 100
6
DN 150
8
DN 200
With Integral Mounted Electronics Housing With Remote Mounted Electronics Housing
Flowmeter Weight(a)
Flowmeter Weight(b)
Electronics
Sensor Types
Sensor Types
Sensor Types Sensor Types
Housing
D, F, R, & S
C&T
D, F, R, & S
C&T
Weight(c)
lb
kg
lb
kg
lb
kg
lb
kg
lb
kg
7.0
3.2
7.3
3.3
5.0
2.3
5.5
2.5
5.0
2.3
8.1
3.7
8.4
3.8
6.0
2.7
6.4
2.9
5.0
2.3
9.0
4.1
9.2
4.2
7.0
3.2
7.5
3.4
5.0
2.3
12.0
5.4
12.3
5.6
10.0
4.5
10.3
4.7
5.0
2.3
17.2
7.8
17.4
7.9
15.0
6.8
15.4
7.0
5.0
2.3
25.0
11.3
25.3
11.5
23.0
10.4
23.5
10.7
5.0
2.3
37.0
16.8
37.2
16.9
35.0
16.0
35.6
16.2
5.0
2.3
61.1
27.7
61.3
27.8
59.0
26.8
59.4
27.0
5.0
2.3
(a) Weight of complete flowmeter, including electronics housing.
(b) Flowmeter Weight is weight of flowtube with sensor plus bonnet plus junction box.
(c) Housing Assembly Weight (for all Sensor Type selections) is weight of electronics housing assembly plus mounting bracket.
PSS 1-8A1 D
Page 15
PHYSICAL SPECIFICATIONS (Cont.)
Table 4. Additional Weight for Single Measurement Flowmeter with Isolation Valve
(Add Weight in this table to Tables 3 and 4 Weights as Applicable)
Nominal
Line
Size(a)
in
All
DN
All
With Integral Mounted Electronics Housing
With Remote Mounted Electronics Housing
Added Weight with Sensor Types
Added Weight with Sensor Types
D, F, R, & S
D, F, R, & S
lb
2.1
kg
1.0
C&T
lb
2.1
kg
1.0
lb
2.1
kg
1.0
C&T
lb
2.1
kg
1.0
(a) Sizes 10 and 12 in (DN 250 and DN 300) not available with wafer body flowmeter.
Table 5. Additional Weight for Dual Measurement Flowmeter without Isolation Valves
(Add Weight in this table to Table 3 Weight)
Nominal
Line
Size(a)
in
All
DN
All
With Integral Mounted Electronics Housing
With Remote Mounted Electronics Housing
Added Weight with Sensor Types(b)
Added Weight with Sensor Types(c)
D, F, R, & S
lb
11.9
C&T
kg
5.4
lb
12.6
D, F, R, & S
kg
5.7
lb
7.2
kg
3.3
C&T
lb
8.8
kg
4.0
(a) Dual Measurement Flowmeters are only available with Flanged Body Flowtubes.
(b) Added weight includes dual manifold without valves, one sensor, a bonnet, an electronics housing, and a support bracket.
(c) Added weight includes dual manifold without valves, one sensor, a bonnet, a junction box assembly, and a support bracket.
Table 6. Additional Weight for Dual Measurement Flowmeter with Isolation Valves
(Add Weight in this table to Table 3 Weight)
Nominal
Line
Size(a)
in
All
DN
All
With Integral Mounted Electronics Housing
With Remote Mounted Electronics Housing
Added Weight with Sensor Types(b)
Added Weight with Sensor Types(c)
D, F, R, & S
lb
15.0
kg
6.8
C&T
lb
15.7
D, F, R, & S
kg
7.1
lb
10.3
kg
4.7
C&T
lb
11.8
(a) Dual Measurement Flowmeters are only available with Flanged Body Flowtubes.
(b) Added weight includes dual manifold with valves, one sensor, a bonnet, an electronics housing, and a support bracket.
(c) Added weight includes dual manifold with valves, one sensor, a bonnet, a junction box assembly, and a support bracket.
kg
5.4
PSS 1-8A1 D
Page 16
PRODUCT SAFETY SPECIFICATIONS
Pressure Safety
Designed to withstand ANSI and metric pressuretemperature ratings as shown in Figures 3 to 8.
Note, for Wafer Body Flowmeters, the flowtube face
outside diameter is designed to center between
ANSI Class 150 flanges. For other flange ratings,
centering spacers are provided.
Personnel and Electrical Fire Safety
This device is designed to be a minimum fire hazard
by using low energy power and adequate insulation
and separation of electrical circuits. The required
standards of worldwide testing agencies such as
FM, ATEX, CSA, IEC and OSHA have been fulfilled.
Electrical Safety Specifications
Testing Laboratory, Types of
Protection and Area Classification
Application Conditions
Temperature Class T4 at 0.8 W,
at -20 to +80°C.
Temperature Class T5 at 0.7 W,
at -20 to +40°C.
Temperature Class T6 at 0.5 W,
at -20 to +40°C.
Temperature Class T4, -20 to +70°C
ATEX, II 3 G, EEx nL IIC
Temperature Class T5, -20 to +70°C
Temperature Class T6, -20 to +40°C
CSA intrinsically safe for Class I, Division 1, Groups A, B, Temperature Class T3C at 85°C and
C, and D; Class II, Division 1, Groups E, F, G; and
T4A at 40°C.
Class III, Division 1.
CSA explosionproof for Class I, Division 1, Groups C and Maximum ambient = 85°C.
D; dust-ignitionproof for Class II, Division 1, Groups E, F,
G; and Class III, Division 1.
Electrical
Safety
Design
Code
ATEX, II 2 G, EEx ib IIC
Suitable for Class I, Division 2, Groups A, B, C, D; Class II,
Division 2, Groups F, G; and Class III, Division 2.
FM intrinsically safe for Class I, Division 1, Groups A, B, C,
D; Class II, Division 1, Groups E, F, G; and Class III,
Division 1.
FM explosionproof for Class I, Division 1, Groups C and D;
dust-ignitionproof for Class II, Division 1, Groups E, F, G;
and Class III, Division 1.
FM nonincendive for Class I, Division 2, Groups A, B, C,
D; suitable for Class II, Division 2, Groups E, F, G; and
Class III, Division 2.
Temperature Class T3C, Ta = 85°C; and
T4A, Ta = 40°C.
E
N
A
Temperature Class T5, Ta = 85°C.
Temperature Class T5, Ta = 85°C.
NOTE
These I/A Series Intelligent Vortex Flowmeters have been designed to meet the electrical classifications
listed in the table above. Contact Invensys Foxboro for more approval and certification information.
PSS 1-8A1 D
Page 17
RECOMMENDED MOUNTING ARRANGEMENTS
Flowmeter Mounting Arrangement
Model 83F Single Measurement Flowmeter Shown
(Dual Measurement Flowmeters follow same arrangements)
Housing Above Pipe; Isolation
Valve and Dual Measurement
Flowmeter NOT Used.
Flowmeter for Use With:
Saturated Superheated
Steam
Steam
No
Yes
(2)
Liquid
Yes
(1)
Gas
Yes
Housing Above Pipe; Isolation
Valve and Dual Measurement
Flowmeter CAN be Used.
No
(5)
Yes
No
Yes
(2)
Housing Below Pipe.
Yes
(3)
(4)
(6)
Yes
(4)
Yes
Yes
(2)
Housing to Side of Pipe.
Yes
Yes
No
Yes
(2)
Housing to Side and Below
Pipe.
Yes
(6)
Yes
No
Yes
(2)
Vertical Pipe, Flow upward.
Yes
Yes
No
Yes
(2)
Vertical Pipe, Flow Downward.
Yes
(7)
Yes
No
Yes
(2)
(1) Possibility of temporary start-up error due to trapped air.
(2) Requires adequate insulation.
(3) Best choice when errors due to start-up cannot be
tolerated.
(4) Recommended only for clean fluids.
(5) Not recommended for liquids with isolation valve.
(6) Preferred for liquids with isolation valve.
(7) Not preferred; must maintain full pipe with no voids in fluid.
PSS 1-8A1 D
Page 18
OPTIONAL SELECTIONS AND ACCESSORIES
Options -B, -D, -E, -G; Cable Assembly to Remote
Electronics Housing
When selecting Code R for a Remote Mounted
Electronics Housing, an optional cable length
selection must also be made. Invensys Foxboro
offers four cable lengths as follows:
Optional Suffix
Cable Length
–B
20 ft (6 m)
–D
30 ft (9 m)
–E
40 ft (12 m)
–G
50 ft (15 m)
Option -N; Certified Calibration Certificate
A calibration and test certificate are provided
standard with each flowmeter. A certified flow
calibrated K-factor and pressure test certificate is
available by selecting Optional Suffix -N.
Option -C; Calibration Cable
A calibration cable that can be plugged into the
amplifier is available to connect to a frequency
generator to check the frequency-to-analog
calibration of amplifier. Available by selecting
Optional Suffix -C.
Options -R and -S; PG11 and PG13.5 Cable Glands
Cable glands with 1/2 NPT external thread provide
strain relieved support for field cable. The PG11 has
an I.D. of 0.50 in (12.7 mm) and the PG13.5 has an
I.D. of 0.53 in (13.5 mm). They are not for use with
units having explosionproof or flameproof
certifications. Available with Electrical Housing
Codes T and R only (1/2 NPT). Select Option -R for
the PG11 and Option -S for the PG13.5.
Option -F, -V, -X; Welding Certificates - with
Flanged Body Flowtubes only
Three certificates are available. Option -F certifies
that the fabrication of 6 to 12 in (150 to 300 mm)
flowtubes by welders is to ASME Boiler Code,
Section IX. Option -V provides radiographic
examination (X-ray) certification of circumferential
welds (not available with ANSI Class 150 or Metric
PN16 flanges). And Option -X certifies that welding
is per ASME Boiler Code and Radiographic
Examination (except as noted for Option -F).
Option -H; Oxygen or Chlorine Service
Wetted parts are cleaned for oxygen or chlorine
service in compliance with Compressed Gas
Association's CGA-4.1 and ASTM G93. Cleaning is
not available when an isolation valve, or dual
measurement or extended temperature meters are
selected. Select Optional Suffix -H.
Option -J; Gold Plated Sensor
Ideally suited for H2 or extremely corrosive
processes. Specify Optional Suffix -J.
Options -L, -M, -Q; Certificates of Conformance
and Compliance
Three material certificates are offered. Optional
Suffix -L provides a certificate of compliance to
Invensys Foxboro specifications. The Invensys
Foxboro quality system conforms to ISO 9001.
Suffix -M is a certification of material for process
wetted metal (conforms to BS EN 10204-3.1). And,
Suffix -Q certifies that stainless steel materials meet
NACE Standard MR-01.
Option -P; Hawke-Type Cable Gland
Brass cable gland with 1/2 NPT external thread.
Provides support for field cable. Available with
Electrical Safety Codes E and Z only. Used with
Electrical Housing Codes T and R only (1/2 NPT).
Select Option -P.
AS Code MTS; Stainless Steel Customer Tag
This optional accessory adds a 40 x 90 mm
(1.5 x 3.5 in) stainless steel tag for customer data
that does not fit on the standard stainless steel data
plate. It is fastened to housing with stainless steel
wire. There can be a maximum of 10 lines of data
with 40 characters and spaces per line. This tag will
also show the K-factor specific to customer
application (information with flowing conditions being
submitted to Invensys Foxboro with the purchase
order). Specify AS Code MTS.
Bolting Kits – With Wafer Body Flowtubes Only
Sets of carbon steel studs and nuts which conform
to line size, and ANSI or metric size and rating, are
offered in 3/4 to 4 in line sizes for ANSI flanges, and
50 to 100 mm line sizes for metric flanges. See
tables below to select the kit and part number
required.
ANSI Flange Bolting Kits - Part Numbers
Size
Cl. 150
Cl. 300
Cl. 600
3/4 in
D0148ZF
D0148ZJ
D0148ZJ
1 in
D0148ZF
D0148ZJ
D0148ZJ
1 1/2 in D0148ZF
D0148ZK
D0148ZS
2 in
A2044HB
A2044HB (a) A2044HC (a)
3 in
A2044HC
A2044HD
A2044HD
4 in
A2044HC (a) A2044HD
A2044HE
(a) Two kits required.
Metric Flange Bolting Kits - Part Numbers
Size
PN 16
PN 40
PN 64 PN 100
50 mm
N/A
D0148ZU
N/A
N/A
80mm
N/A
D0148ZZ (a)
N/A
N/A
100 mm L0114NT L0114NT
N/A
N/A
(a) Two kits required.
PSS 1-8A1 D
Page 19
MODEL CODES
Model 83F Vortex Flowmeters – Flanged Body
Description
83F = Vortex Flowmeter – Flanged Body
-A
Electronics Type
= 4 to 20 mA Analog and Pulse Electronics
3Q
01
1H
02
03
04
06
08
10
12
=
=
=
=
=
=
=
=
=
=
Nominal Line Size
3/4 in (DN 15) Line Size
1 in (DN 25) Line Size
1 1/2 in (DN 40) Line Size
2 in (DN 50) Line Size
3 in (DN 80) Line Size
4 in (DN 100) Line Size
6 in (DN 150) Line Size
8 in (DN 200) Line Size
10 in (DN 250) Line Size
12 in (DN 300) Line Size
Body and Flange Material
S = Sizes 3Q to 04: Cast Body/Flange and Shedder (except Code 04S1); CF8M Material
Size 04S1: Fabricated from 316 ss Tubing and Flanges
Sizes 06 to 12: Body Fabricated from 304 ss Tubing with 304 ss Flanges
K = Sizes 06 to 12: Body Fabricated from 304 ss Tubing with Carton Steel (A105) Flanges
1
2
3
4
5
6
7
8
A
B
C
D
F
H
=
=
=
=
=
=
=
=
=
=
=
=
=
=
End Connections and Flange Rating
Description
ANSI Class 150 Flange, RF, per ASME B16.5
ANSI Class 300 Flange, RF, per ASME B16.5
ANSI Class 600 Flange, RF, per ASME B16.5
Metric PN 16 Flange, RF, Finish Form D, per ASME B16.5
Metric PN 40 Flange, RF, Finish Form D, per DIN 2501
Metric PN 64 Flange, RF, Finish Form E, per DIN 2501
Metric PN 100 Flange, RF, Finish Form E, per DIN 2501
Metric PN 40 Flange, RF, Finish Form C, per DIN 2501
Metric PN 40 Flange, RF, Finish Form N, per DIN 2501
Metric PN 64 Flange, RF, Finish Form N, per DIN 2501
Metric PN 100 Flange, RF, Finish Form N, per DIN 2501
Metric PN 16 Flange, RF, Finish Type B1, per EN 1092-1
Metric PN 40 Flange, RF, Finish Type B1, per EN 1092-1
Metric PN 100 Flange, RF, Finish Type B1, per EN 1092-1
S
D
K
L
=
=
=
=
Used with Line Sizes
All line sizes
All line sizes
Sizes 3Q through 08 only
Sizes 06 through 08 only
All line sizes
Sizes 02 through 12 only
Sizes 3Q through 08 only
Sizes 3Q through 04 only
All line sizes
Sizes 02 through 12 only
Sizes 3Q through 08 only
Sizes 06 through 08 only (e)
All line sizes (e)
All line sizes (e)
Single or Dual Measurement and Isolation Valve
Single Measurement; No Isolation Valve
Dual Measurement; Manifold with No Isolation Valve
Single Measurement; Manifold with one Isolation Valve; CF8M Stainless Steel
Dual Measurement; Manifold with two Isolation Valves; CF8M Stainless Steel
D
F
R
S
=
=
=
=
C
T
=
=
Sensor Fill, Temperature Range, and Material
Standard Temperature Range (with Fill Fluid)
Fluorolube Fill, 0 to 200 °F (–20 to +90°C) Hastelloy Type CW2M
Fluorolube Fill, 0 to 200 °F (–20 to +90°C) Stainless Steel Type CF3M
Silicone Fill, 0 to 400 °F (–20 to +200°C) Hastelloy Type CW2M
Silicone Fill, 0 to 400 °F (–20 to +200°C) Stainless Steel Type CF3M
High Temperature Range (No Fill Fluid) (d)
Unfilled, 400 to 800°F (200 to 430°C) Hastelloy Type CW2M
Unfilled, 400 to 800°F (200 to 430°C) Stainless Steel Type CF3M
Model 83F Code continued on next page
PSS 1-8A1 D
Page 20
MODEL CODES (Cont.)
Model 83F Vortex Flowmeters - Flanged Body (Cont.)
T
R
Electronics Housing Mounting, Material, and Conduit Connections
= Mounted to Flowtube; Aluminum Housing; 1/2 NPT Conduit Connections (a)
= Remote Mounted; Aluminum Housing; 1/2 NPT Conduit Connections (a)
Also must select Cable Length in Options Section.
N
A
B
E
D
=
=
=
=
=
Output Indicator
No Output Indicator (Blind Unit)
Analog Output Indicator, 4 to 20 mA, 0 to 100% Scale
Analog Output Indicator, Ten Equally Spaced Division
Pulse Output Indicator, 0 to 100% Scale
Pulse Output Indicator, Ten Equally Spaced Divisions
Electrical Safety (See Electrical Safety Specifications Section for further details)
A = CSA intrinsically safe, Division 1.
CSA explosionproof, Division 1.
CSA suitable for Class I, II, and III, Division 2.
FM intrinsically safe, Division 1.
FM explosionproof, Division 1.
FM nonincendive, Class I, II, and III, Division 2.
E = ATEX intrinsically safe, II 2 G, EEx ib IIC.
N = ATEX protection n, II 3 G, EEx nL IIC
Z = No Approval/Certification Required
-B
-D
-E
-G
Optional Selections
Cable Length Selection for Remote Electronics Housing
= 20 ft (6 m) Cable to Connect to Remote Electronics Housing
= 30 ft (9 m) Cable to Connect to Remote Electronics Housing
= 40 ft (12 m) Cable to Connect to Remote Electronics Housing
= 50 ft (15 m) Cable to Connect to Remote Electronics Housing
-C =
-H =
Calibration Cable
Cable used to Check Amplifier Calibration
Cleaning for Oxygen or Chlorine Service
Cleaning of Process Wetted Parts for Oxygen/Chlorine Service per CGA G–4.1 and ASTM G93
(Not with Measurement/Isolation Valve Codes “D”, “K”, and “L”, Extended Temperature Sensor
Codes “C” and “T”, or Size Codes “10” and “12”)
-J =
Sensor Plating
Gold Plated Sensor
-L =
-M =
-Q =
Invensys Foxboro Certificates of Compliance/Conformance
Standard Certificate of Compliance (ISO 9001)
Foxboro Material Certification of Process Wetted Metal (Conforms to BS EN 10204.3.1)
Process Wetted Parts Conform to NACE MR-01
-N =
Invensys Foxboro Certified Calibration Certificate
Foxboro Calibration and Pressure Test Certification
–P =
–R =
–S =
Cable Connections - with Electrical Housing Codes T and R (1/2 NPT)
Hawke-Type Cable Gland (with Electrical Safety Codes E and Z only)
PG11 Trumpet Gland (not with flameproof/explosionproof certifications)
PG13.5 Trumpet Gland (not with flameproof/explosionproof certifications)
-F =
-V =
-X =
Welding Certificate (Size Codes 06 through 12 only) (b)(c)
Welding Certified to the ASME Boiler Code
Radiographic Examination of Flange Welds (except ANSI 150 and Metric PN 16)
Welding Certified to the ASME Boiler Code; includes Radiographic Examination
Examples: 83F–D02S1SDTNA–X; 83F–T06K7DCRJE–GQNX
(a) ATEX intrinsically safe certifications not available with 1/2 NPT openings.
(b) Select one certificate only. Note that Certificate –X includes both –F and –V certifications.
(c) Not available when Size Code 06 or 08 is combined with End Connection Code 1 or 4.
(d) Application ALERT: for Extended Temperature Range sensors used in hazardous or volatile gas applications, there is the potential of
fugitive emissions to occur through the sensor vented restrictor if the sensor diaphragm were to fail.
(e) Contact Invensys Foxboro if metric flanges per EN 1092-1 are selected.
PSS 1-8A1 D
Page 21
MODEL CODES (Cont.)
Model 83W Vortex Flowmeters – Wafer Body
Description
83W = Vortex Flowmeter – Wafer Body
-A
Electronics Type
= 4 to 20 mA Analog and Pulse Electronics
3Q
01
1H
02
03
04
06
08
=
=
=
=
=
=
=
=
Nominal Line Size
3/4 in (DN 15) Line Size
1 in (DN 25) Line Size
1 1/2 in (DN 40) Line Size
2 in (DN 50) Line Size
3 in (DN 80) Line Size
4 in (DN 100) Line Size
6 in (DN 150) Line Size
8 in (DN 200) Line Size
Body Material
S = ASTM A351-CF8M (316 ss) Cast Body and Shedder
H = ASTM A494-CW2M (Hastelloy C) Cast Body and Shedder; with Size Codes 3Q to 04 only.
Mounting and Centering System
1 = Centering for the following Flanges:
ANSI Class 150 and ANSI Class 300
ANSI Class 600 with Sizes 3Q to 04 only
Metric PN 16 with Sizes 01 to 03 only
Metric PN 40 with Sizes 01 to 03, and 06, and 08
Metric PN 64 and Metric PN 100
S =
K =
Isolation Valve
No Isolation Valve
Isolation Valve, Type CF8M Stainless Steel
D
F
R
S
=
=
=
=
C
T
=
=
T
R
=
=
Sensor Fill, Temperature Range, and Material
Standard Temperature Range (with Fill Fluid)
Fluorolube Fill, 0 to 200 °F (–20 to +90 °C) Hastelloy Type CW2M
Fluorolube Fill, 0 to 200 °F (–20 to +90 °C) Stainless Steel Type CF3M
Silicone Fill, 0 to 400°F (–20 to +200 °C) Hastelloy Type CW2M
Silicone Fill, 0 to 400°F (–20 to +200 °C) Stainless Steel Type CF3M
High Temperature Range (No Fill Fluid) (b)
Unfilled, 400 to 800°F (200 to 430°C) Hastelloy Type CW2M
Unfilled, 400 to 800°F (200 to 430°C) Stainless Steel Type CF3M
Mounting for Electronics Housing
Mounted to Flowtube; Aluminum Housing; 1/2 NPT Conduit Connections (a)
Remote Mounted; Aluminum Housing; 1/2 NPT Conduit Connections (a)
Also must select Cable Length in Options Section.
Model 83W Code continued on next page
PSS 1-8A1 D
Page 22
MODEL CODES (Cont.)
Model 83W Vortex Flowmeters - Wafer Body (Cont.)
N
A
B
E
D
Local Digital Display/Configurator
= No Output Indicator (Blind Unit)
= Analog Output Indicator, 4 to 20 mA, 0 to 100% Scale
= Analog Output Indicator, Ten Equally Spaced Divisions
= Pulse Output Indicator, 0 to 100% Scale
= Pulse Output Indicator, Ten Equally Spaced Divisions
Electrical Safety (See Electrical Safety Specifications Section for further details)
A = CSA intrinsically safe, Division 1.
CSA explosionproof, Division 1.
CSA suitable for Class I, II, and III, Division 2.
FM intrinsically safe, Division 1.
FM explosionproof, Division 1.
FM nonincendive, Class I, II, and III, Division 2.
E = ATEX intrinsically safe, II 2 G, EEx ib IIC.
N = ATEX protection n, II 3 G, EEx nL IIC
Z = No Approval/Certification Required
-B
-D
-E
-G
Optional Selections
Cable Length Selection for Remote Electronics Housing
= 20 ft (6 m) Cable to Connect to Remote Electronics Housing
= 30 ft (9 m) Cable to Connect to Remote Electronics Housing
= 40 ft (12 m) Cable to Connect to Remote Electronics Housing
= 50 ft (15 m) Cable to Connect to Remote Electronics Housing
Calibration Cable
-C = Cable used to Check Amplifier Calibration
-H =
-J =
Cleaning for Oxygen or Chlorine Service
Cleaning Process Wetted Parts per CGA G–4.1 and ASTM G93
(Not available with Isolation Valve, Code K or Extended Temperature Sensor Codes “C” and “T”)
Sensor Plating
Gold Plated Sensor
-Q =
Invensys Foxboro Certificates of Compliance/Conformance
Standard Certificate of Compliance
Invensys Foxboro Material Certification of Process Wetted Metal
(Conforms to BS EN 10204-3.1)
Process Wetted Parts Conform to NACE MR-01
-N =
Invensys Foxboro Calibration Certificate
Invensys Foxboro Calibration and Pressure Test Certification
-P =
-R =
Cable Connections - with Electrical Housing Codes T and R (1/2 NPT)
Hawke Cable Gland
PG11 Trumpet Gland
-L =
-M =
Examples: 83W–D02S1KFTJA–Q; 83W–T06S4SDRJA–GNP
(a) ATEX intrinsically safe certification not available with 1/2 NPT openings.
(b) Application ALERT: for Extended Temperature Range sensors used in hazardous or volatile gas applications, there is the potential of
fugitive emissions to occur through the sensor vented restrictor if the sensor diaphragm were to fail.
PSS 1-8A1 D
Page 23
DIMENSIONS - NOMINAL
mm
in
83F AND 83W FLANGED AND WAFER BODY FLOWTUBES; INTEGRAL MOUNT; SINGLE MEASUREMENT
127
5.0
EXTENDED COVER
WHEN DIGITAL
INDICATOR IS
SELECTED.
83F WITH ISOLATION VALVE
STANDARD
TEMPERATURE
BONNET IS SHOWN,
SEE NOTE BELOW
191
7.5
152
6.0
B
FIELD
TERMINALS
ELECTRONICS
HOUSING
(TYPICAL)
83F FLANGED BODY
A
CL
FIELD
TERMINALS
83F FLANGED BODY
CL
ISOLATION
VALVE
CL
D
83W WAFER BODY
83W WITH ISOLATION VALVE
B
FIELD
TERMINALS
83W WAFER BODY
D
A
CL
CL
CL
C
C
Dimensions - Nominal Line Size Code (a)
Dimension
3Q
01
1H
02
03
04
06
08
10 (b)
12 (b)
A
188
---------7.4
188
---------7.4
188
---------7.4
188
---------7.4
188
---------7.4
188
---------7.4
188
---------7.4
188
---------7.4
188
---------7.4
188
---------7.4
B
257---------10.1
257---------10.1
257---------10.1
257---------10.1
257---------10.1
257---------10.1
257---------10.1
257---------10.1
257---------10.1
257---------10.1
C
79.5
----------3.13
79.5
----------3.13
79.5
----------3.13
79.5
----------3.13
95.3)
-------------3.75
121---------4.75
178
---------7.0
229
---------9.0
N/A
N/A
D
Dimension D varies with flange type, rating, and size. See Table 7 further in document for dimensions.
(a) Refer to Model Code section for nominal line sizes in DN or inches.
(b) Size Codes 10 and 12 are not available with wafer body flowtubes.
NOTE:
1. Dimensions A and B are shown with the standard temperature bonnet. With extended temperature
applications; add 2.6 in (66 mm) to Dimensions A and B because of the longer bonnet.
2. For additional dimensions, also refer to DP 019-150 for the Model 83F, and DP 019-152 for the
Model 83W.
PSS 1-8A1 D
Page 24
mm
in
DIMENSIONS - NOMINAL (Cont.)
83F FLANGED FLOWTUBE; INTEGRAL MOUNT; DUAL MEASUREMENT
B
FIELD
TERMINALS
A
VIBRATION-LIMITING
SUPPORT BRACKET
ELECTRONICS
HOUSING
(TYPICAL)
REFER TO DIMENSIONAL
PRINT DP 019-151 FOR
FLANGE DIMENSIONAL DATA.
Integral Mount Dimensions
Standard Temperature Flowmeter
INTEGRAL MOUNT
STANDARD
TEMPERATURE
FLOWMETER,
AND MANIFOLD
WITH NO VALVES,
SHOWN
Extended Temperature Flowmeter
Dimension
No Isolation Valves
With Isolation Valves
No Isolation Vales
With Isolation Valves
A
198
---------7.8
216
---------8.5
262---------10.3
274---------10.8
B
394---------15.5
432---------17.0
495---------19.5
521---------20.5
83F FLANGED FLOWTUBE; REMOTE MOUNT; DUAL MEASUREMENT
B
JUNCTION BOX
ACCEPTS CABLE
FROM REMOTE
ELECTRONICS
HOUSING.
REMOTE MOUNT
STANDARD
TEMPERATURE,
AND MANIFOLD
WITH NO VALVES,
SHOWN
A
VIBRATION-LIMITING
SUPPORT BRACKET
JUNCTION
BOX
(TYPICAL)
REFER TO DIMENSIONAL
PRINT DP 019-151 FOR
FLANGE DIMENSIONAL DATA.
Remote Mount Dimensions
Standard Temperature Flowmeter
Extended Temperature Flowmeter
Dimension
No Isolation Valves
With Isolation Valves
No Isolation Vales
With Isolation Valves
A
211
---------8.3
236
---------9.3
265---------10.5
292---------11.5
B
401---------15.8
457---------18.0
503---------19.8
533---------21.0
NOTE:
Also refer to DP 019-151 for further dimensions.
PSS 1-8A1 D
Page 25
DIMENSIONS - NOMINAL (Cont.)
mm
in
83F AND 83W FLANGED AND WAFER BODY FLOWMETERS WITH REMOTE MOUNTED ELECTRONICS
REMOTE
ELECTRONICS
HOUSING
(TYPICAL)
191
7.5
152
6.0
127
5.0
F IELD
FIELD
TE
ER
R MI
M I NAL
NALS
10.34 mm
(0.407 in)
DIAMETER
HOLES, FOUR
PLACES.
BRACKET MAY BE
USED FOR PIPE OR
SURFACE MOUNTING.
CABLE TO
JUNCTION BOX
ON REMOTE
FLOWTUBE
BELOW.
325
12.8
208
8.2
69.9
2.75
FOR HORIZONTAL PIPE
MOUNTING, ROTATE
U-BOLT 90°.
69.9
2.75
99
3.9
83W WAFER BODY
83W WITH ISOLATION VALVE
CABLE TO REMOTE
ELECTRONICS HOUSING
ABOVE.
83F FLANGED BODY
83F WITH ISOLATION VALVE
STANDARD TEMPERATURE
BONNET (TYP.). SEE NOTE
BELOW.
A
B
B
A
CL
ISOLATION
VALVE
(TYPICAL)
CL
C
CL
CL
C
D
D
Dimensions - Nominal Line Size Code (a)
Dimension
3Q
01
1H
02
03
04
06
08
10 (b)
12 (b)
A
188
---------7.4
188
---------7.4
188
---------7.4
188
---------7.4
188
---------7.4
188
---------7.4
188
---------7.4
188
---------7.4
188
---------7.4
188
---------7.4
B
257---------10.1
257---------10.1
257---------10.1
257---------10.1
257---------10.1
257---------10.1
257---------10.1
257---------10.1
257---------10.1
257---------10.1
C
79.5
----------3.13
79.5
----------3.13
79.5
----------3.13
79.5
----------3.13
95.3)
-------------3.75
121---------4.75
178
---------7.0
229
---------9.0
N/A
N/A
D
Dimension D varies with flange type, rating, and size. See Table 7 further in document for dimensions.
(a) Refer to Model Code section for nominal line sizes in DN or inches.
(b) Size Codes 10 and 12 are not available with wafer body flowtubes.
NOTE:
1. Dimensions A and B are shown with the standard temperature bonnet. With extended temperature
applications; add 2.6 in (66 mm) to Dimensions A and B because of the longer bonnet.
2. For additional dimensions, also refer to DP 019-150 for the Model 83F, and DP 019-152 for the
Model 83W.
PSS 1-8A1 D
Page 26
DIMENSIONS - NOMINAL (Cont.)
Table 7.
Dimension “D” (Face-to-Face) for Model 83F Flanged Body Flowtubes
ANSI Flanges
Line Size
3/4 in
1 in
1 1/2 in
2 in
3 in
4 in
6 in
8 in
10 in
12 in
Metric Flanges
Flange Rating
Dimension “D” (a)
Class 150
Class 300
Class 600
Class 150
Class 300
Class 600
Class 150
Class 300
Class 600
Class 150
Class 300
Class 600
Class 150
Class 300
Class 600
Class 150
Class 300
Class 600
Class 150
Class 300
Class 600
Class 150
Class 300
Class 600
Class 150
Class 300
Class 150
Class 300
6.00 in
6.00 in
6.50 in
6.50 in
6.50 in
7.00 in
7.25 in
7.25 in
7.80 in
7.75 in
7.75 in
8.50 in
8.75 in
8.75 in
9.50 in
9.50 in
9.50 in
10.50 in
12.00 in
12.75 in
14.75 in
15.00 in
15.75 in
18.00 in
15.00 in
16.20 in
17.00 in
18.20 in
Line Size
DN 15
DN 25
DN 40
DN 50
DN 80
DN 100
DN 150
DN 200
DN 250
DN 300
(a) For 3/4 to 4 in sizes, overall face-to-face length (D) tolerance is ±0.05 in.
For 6 to 12 in sizes overall face-to-face length (D) tolerance is ±0.250 in.
(b) For DN 15 to DN 100 sizes, overall face-to-face length (D) tolerance is ±1.3 mm.
For DN 150 to DN 300 sizes, overall face-to-face length (D) tolerance is ±6.4 mm.
(c) The DN 50 PN 40 flange may be used with a PN 25 mating flange.
Flange Rating
Dimension “D” (b)
PN 40
PN 100
PN 40
PN 100
PN 40
PN 100
PN 40 (c)
PN 64
PN 100
PN 40
PN 64
PN 100
PN 40
PN 64
PN 100
PN 16
PN 40
PN 64
PN 100
PN 16
PN 40
PN 64
PN 100
PN 40
PN 64
PN 40
PN 64
152 mm
152 mm
166 mm
178 mm
179 mm
196 mm
195 mm
205 mm
205 mm
220 mm
230 mm
320 mm
240 mm
250 mm
260 mm
305 mm
320 mm
360 mm
360 mm
381 mm
396 mm
443 mm
443 mm
411 mm
481 mm
459 mm
513 mm
PSS 1-8A1 D
Page 27
PSS 1-8A1 D
Page 28
ORDERING INSTRUCTIONS
1. Model Number
2. Flow Data:
a. Maximum, minimum, and normal flow rate.
b. Fluid composition and viscosity at operating temperatures.
c. Fluid density or relative density (specific gravity).
d. Maximum, minimum, and normal operating temperatures.
e. Maximum, minimum, and normal operating pressures.
f. Mating pipe schedule.
g.Type and location (distance) of up-stream disturbances.
3. Calibration information (analog output only); maximum flow rate for 20 mA output.
4. Electrical Classification
5. Optional Features
6. Customer Tag Data
PATENT NOTICE
This product and its components are protected by
one or more of the following U.S. Patents.
3,948,098; 4,085,614; 4,520,678; 5,003,827 and
5,209,125. Corresponding patents have been issued
or are pending in other countries.
OTHER M&I PRODUCTS
Invensys Foxboro provides a broad range of measurement
and instrument products, including solutions for pressure,
flow, analytical, positioners, temperature, controlling and
recording. For a listing of these offerings, visit the Invensys
Foxboro web site at:
www.foxboro.com/instrumentation
33 Commercial Street
Foxboro, MA 02035-2099
United States of America
www.foxboro.com
Inside U.S.: 1-866-746-6477
Outside U.S.: 1-508-549-2424
or contact your local Foxboro
representative.
Facsimile: 1-508-549-4999
Invensys, Foxboro, FlowExpertPro, and I/A Series are trademarks of Invensys plc, its subsidiaries,
and affiliates.
All other brand names may be trademarks of their respective owners.
Copyright 1994-2008 Invensys Systems, Inc.
All rights reserved
MB 010
Printed in U.S.A.
0608

Similar documents

Foxboro Model 84 (Style B) Vortex Flowmeter - Mec

Foxboro Model 84 (Style B) Vortex Flowmeter - Mec The Foxboro® brand I/A Series® Model 84F (Style B) is part of a family of intelligent, high performance vortex flowmeters. It transmits a 4 to 20 mA or digital multidrop, and a pulse output signal,...

More information

[PSS 1-8A1 D] Foxboro Model 83F Flanged Body Vortex Flowmeters

[PSS 1-8A1 D] Foxboro Model 83F Flanged Body Vortex Flowmeters These flowmeters transmit two different types of output signals that are linearly proportional to volumetric flow rate. The flowmeters produce a pulse rate signal for totalizing and batching, or an...

More information

Model 84F Flanged Body Flowmeters

Model 84F Flanged Body Flowmeters Foxboro flowmeters. It also ensures that the user has selected the proper flowmeter type for his application. Invensys provides this meter selection tool as a free web site to all users, without th...

More information