FirePoint Datasheet Pack v4

Transcription

FirePoint Datasheet Pack v4
FirePoint Control Panel Features
■ Analogue/addressable detection devices
■ Digital processing based
■ LED zone indication
■ Keyswitch access
■ Laptop programming
■ Configurable system code
■ Device isolate
■ VHF remote receiver facility
■ Keypad programming
■ Integral pager transmitter
Overview
5000 FirePoint is designed using EMS radio technology allowing flexibility and
expansion of wireless fire detection systems. There are various panel options
available with the added benefits of wireless installation.
The fire alarm control panel incorporates state of the art radio technology,
coupled with the panel features, providing the user with a cost effective and
practical fire alarm panel.
5000 FirePoint uses industry standard devices such as the Ziton detector, KAC
call point and the Signature Industries sounder.
The analogue/addressable detectors, callpoints and sounders are alkaline
battery powered with up to 5 years typical life cycle.
The panel technology meets the requirements of BS5839 and EN54 standards
and has been fully tested by the DTI to satisfy the requirements of MPT 1305
and 1328 radio standards. VHF technology is used for receiving information
from devices and is combined with UHF (at 500mW) for command signals to
radio sounders and personal pagers.
The fire panel and its peripheral equipment benefit from over 20 years of design,
development and manufacturing experience, providing leading edge solutions to
complex radio technology problems.
Optional system support facilities
• Optional wireless (radio) local area network
• Optional modem technical support
• Interface compatibility with the EMS fire detection range
Specification
Dimensions:
330 x 450 x 116mm (Including back box)
Fascia:
Injection moulded, with steel backbox
Colour:
Two-tone contrasting beige
Operating Temperature:
-10 to 55 °C
Humidity:
Up to 75% non-condensing
Power:
230Vac, 50Hz
Battery Space:
2 x 12volt 9AH batteries (not supplied)
Operating Frequencies:
VHF - 173.2 MHz -173.5 MHz (receiver)
UHF - 458.5 MHz - 459.5 MHz (transmitter)
Channel Spacing:
25 kHz
Output Transmitter Power:
0.75W (500 Mw) (+27DBH)
Outputs:
2 x .25amp 24v DC sounder output circuits individually fused
with end of line by reverse polarity, open circuit & short circuit
monitoring.
1 x hardwire call point with end of line, open circuit and short
circuit monitoring.
2 x sets of auxiliary fire contacts.
2 x sets of auxiliary fault contacts.
1 x RS485 serial port
1 x RS232 serial port
1 x Power supply and charger 230VAC 50 Hz Transformer
giving a total of 3 amps.
Standards:
Designed to comply with relevant parts of BS5839 and EN54
Ordering Information
Addressable 4 Zone Controller:
Analogue Addressable 12 Zone Controller:
Analogue Addressable 24 Zone Controller:
Analogue Addressable 96 Zone Controller:
Part
Part
Part
Part
Number
Number
Number
Number
53
53
53
53
-
5004
5012
5024
5096
An ISO9001:2008 approved company
EMS Group Head Office
Technology House
Sea Street
Herne Bay
Kent CT6 8JZ
England
Tel: +44 (0) 1227 369570
Fax: +44 (0) 1227 369679
Email: [email protected]
www.emsgroup.co.uk
Part No: FirePoint 1, v1.2
Dealer Information:
The
information
contained
within
this
literature is correct at time of publishing. The
EMS Group reserves the right to change any
information regarding products as part of its
continual
development
enhancing
new
technology and reliability. The EMS Group
advises that any product literature issue
numbers are checked with its head office prior
to any formal specifications being written.
FirePoint Optical Detector Features
■ Analogue/addressable
■ Proprietary sensor
■ Protected sensing chamber
■ Universal transmitter module
■ Up to 5 Years battery life
■ Detector / transmitter tamper
■ Range in excess of 250 metres
Overview
The model 53-5100 Analogue Addressable Optical Smoke Detector is bayonet
fitted to a radio address/transmitter module, incorporating alkaline batteries and
supplied with a surface-mount base unit. Removal of the detector or
address/transmitter module will indicate a fault condition. The detector is
manufactured by Ziton and complies with BS5839 Part 5 and EN54 Part 7.
The Optical Smoke Detector operates on an advanced light scattering principle,
using a wide-angle light beam together with an extra high sensitivity photodiode
receiver. An internal polling system checks for smoke particles every 5 seconds,
initial detection of smoke traces accelerates polling to every 2 seconds. The
alarm is verified twice to ensure freedom from false alarms.
The detector incorporates a selectable automatic lock, which, if enabled locks it
into its base when plugged in, preventing unauthorised removal. Each unit has a
unique address configured during manufacture and is individually addressable
by the system controller. The radio address module is programmed to report at
regular intervals of 5 – 9 minutes.
Designed and manufactured using the latest techniques and surface-mount
technology ensures component count is kept to a minimum, thereby maximising
reliability.
The address/transmitter module is powered by a low-voltage dual supply
alkaline battery pack. The battery pack condition is continually monitored. The
battery pack has been tested to provide up to 5 years life at normal site
operations (10 - 30°C). The system indicates remaining battery capacity and a
low battery condition is indicated to the controller as a fault, allowing 30 days
for the battery pack to be changed before unit failure.
Specification
Dimensions:
106x75 mm with transmitter/address module
Weight:
119g
Operating Temperature:
-10 to 85 °C
Humidity:
Up to 95% non-condensing
Supply:
6 x 1.5 volt alkaline AAA cells
Battery life up to 5 years (at normal site conditions 10 - 30°C)
Operating Frequencies:
VHF - 173.2 MHz -173.5 MHz (transmitter)
Channel Spacing:
25 kHz
Output Transmitter Power:
1 mW ERP
Outputs:
Detector alarm – Fire and Fault
Detector identity
Battery condition
Auto report signal
Standards:
Designed to comply with relevant parts of BS5839 and EN54
Ordering Information
Detector / address module complete:
Part Number 53 - 5100
An ISO9001:2008 approved company
EMS Group Head Office
Technology House
Sea Street
Herne Bay
Kent CT6 8JZ
England
Tel: +44 (0) 1227 369570
Fax: +44 (0) 1227 369679
Email: [email protected]
www.emsgroup.co.uk
Part No: FirePoint 2, v1.2
Dealer Information:
The
information
contained
within
this
literature is correct at time of publishing. The
EMS Group reserves the right to change any
information regarding products as part of its
continual
development
enhancing
new
technology and reliability. The EMS Group
advises that any product literature issue
numbers are checked with its head office prior
to any formal specifications being written.
FirePoint Callpoint Features
■ Fully addressable
■ Wireless activation
■ LED activation indication
■ Up to 5 Years battery life
■ Rear tamper protection
■ Range in excess of 250 metres
Overview
The model 5200 Radio Callpoint is battery operated, incorporating a radio address module.
This eliminates the need for wiring back to the fire alarm control panel.
The callpoint is designed to meet BS5839 part 2.
The callpoint is fitted into an industry standard ABS moulding which allows for testing by
insertion of a test key. When the glass is broken, the micro-switch is released, triggering an
alarm transmission by radio, to the alarm panel.
Each unit has a unique address configured during manufacture and is individually
addressable by the system controller during commissioning. The unit is programmed to
report at regular intervals of 5 – 9 minutes.
Designed and manufactured using the latest techniques and surface-mount technology
ensures component count is kept to a minimum, thereby maximising reliability.
The Callpoint is powered by a low-voltage dual supply alkaline battery pack. The battery
pack condition is continually monitored. The battery board has been tested to provide up to
5 years of normal site operations. The system indicates remaining battery capacity and a
low battery condition is indicated to the controller as a fault, allowing 30 days for the battery
pack to be replaced before unit failure.
Specification
Dimensions:
87 x 87 x 61.5mm
Weight:
276g
Operating Temperature:
-10 to 55 °C
Supply:
6 x 1.5 volt alkaline AAA cells
Battery life up to 5 years (at normal site conditions 10 - 30°C)
Operating Frequencies:
Channel Spacing:
Output Transmitter Power:
Outputs:
Standards:
VHF - 173.2 MHz -173.5 MHz (transmitter)
25 kHz
1 mW ERP
Alarm signal
Callpoint identity
Battery condition
Auto report signal
LED to confirm alarm transmission
Designed to comply with relevant parts of BS5839 and EN54
Ordering Information
Red Radio Callpoint:
White Radio Callpoint:
Blue Radio Callpoint:
Yellow Radio Callpoint:
Green Radio Callpoint:
Part
Part
Part
Part
Part
Number
Number
Number
Number
Number
53
53
53
53
53
–
–
–
–
–
5200/R
5200/W
5200/B
5200/Y
5200/G
An ISO9001:2008 approved company
EMS Group Head Office
Technology House
Sea Street
Herne Bay
Kent CT6 8JZ
England
Tel: +44 (0) 1227 369570
Fax: +44 (0) 1227 369679
Email: [email protected]
www.emsgroup.co.uk
Part No: FirePoint 3, v1.2
Dealer Information:
The
information
contained
within
this
literature is correct at time of publishing. The
EMS Group reserves the right to change any
information regarding products as part of its
continual
development
enhancing
new
technology and reliability. The EMS Group
advises that any product literature issue
numbers are checked with its head office prior
to any formal specifications being written.
FirePoint Sounder Features
■ Fully addressable
■ Wireless activation
■ 2-way radio communication
■ 96Db(adjustable at 1 metre)
■ Sounder/Visual indicator option
■ Hardwired Callpoint option
■ Up to 5 Years battery life
Overview
The model 5300 Radio Sounder is a battery operated sounder remotely activated and
monitored by the system 5000 FirePoint controller. Each unit has a unique address
configured during manufacture and is individually addressable by the system controller.
Each unit is controlled individually or by zone, dependant on the system design.
The Radio Sounder is housed in an industry standard, impact resistant ABS moulding.
The sounder has 2-way radio communication with the fire system controller using UHF
wavebands to receive command instructions and VHF for auto reporting.
The model 5320 Radio Sounder has a set of monitored contacts for the wiring of a
remote callpoint, thereby providing a very cost effective component.
Designed and manufactured using the latest techniques and surface-mount technology
ensures component count is kept to a minimum, thereby maximising reliability.
The sounder is powered by a low-voltage dual supply alkaline battery pack. The battery
pack condition is continually monitored. The battery board has been tested to provide up
to 5 years of normal site operations. The system indicates remaining battery capacity and
a low battery condition is indicated to the controller as a fault, leaving approximately
30 days for the battery pack to be changed.
Specification
Dimensions:
53-5300 = 88 x 88 x 93 mm
Weight:
379g
Operating Temperature:
Humidity:
-10 to 55 °C
Up to 95% non-condensing
Supply:
3 x 1.5 volt AA cells
3 x 1.5 volt C cells
Battery life up to 5 years (at normal site conditions 10 - 30°C)
Operating Frequencies:
VHF - 173.2 MHz -173.5 MHz (transmitter)
UHF - 458.5 MHz - 459.5 MHz (receiver)
Standard Fire Tone 1024Khz,819Khz
Channel Spacing:
25 kHz
1 mW ERP
Output Transmitter Power:
Outputs:
4 tone patterns
Sounder identity
Battery condition
Auto report signal
Standards:
Designed to comply with relevant parts of BS5839 and EN54
Ordering Information
Radio
Radio
Radio
Radio
Radio
Sounder
Sounder
Sounder
Sounder
Sounder
(red):
(red) weather resistant:
(white):
Visual indicator:
with Auxiliary contacts:
Part
Part
Part
Part
Part
Number
Number
Number
Number
Number
53
53
53
53
53
–
–
–
–
–
5300/R
5300/RWP
5300/W
5310
5320
An ISO9001:2008 approved company
EMS Group Head Office
Technology House
Sea Street
Herne Bay
Kent CT6 8JZ
England
Tel: +44 (0) 1227 369570
Fax: +44 (0) 1227 369679
Email: [email protected]
www.emsgroup.co.uk
Part No: FirePoint 4, v1.3
Dealer Information:
The
information
contained
within
this
literature is correct at time of publishing. The
EMS Group reserves the right to change any
information regarding products as part of its
continual
development
enhancing
new
technology and reliability. The EMS Group
advises that any product literature issue
numbers are checked with its head office prior
to any formal specifications being written.
FirePoint Heat Detector Features
■ Analogue/addressable
■ Proprietary sensor
■ Universal transmitter module
■ Up to 5 Years battery life
■ Detector / transmitter tamper
■ Range in excess of 250 metres
Overview
The model 5120 Analogue Addressable Heat Detector is bayonet fitted to a radio
address/transmitter module, incorporating alkaline batteries and supplied with a
surface-mount base unit. Removal of the detector or address/transmitter
module will indicate a fault condition. The detector is manufactured by Ziton
limited and complies with BS5839 Part 5 and EN54 Part 5 (Class B) and part 8
(Class B).
The Heat Detector operates on a highly sensitive thermistor, which measures
actual temperature and the rate of temperature rise change. At regular
intervals, the detector carries out a self test that checks and verifies every
function, including the thermistor and sensitivity to temperature. Any failure is
automatically reported to the control panel.
The detector incorporates a selectable automatic lock, which, if enabled locks it
into its base when plugged in, preventing unauthorised removal. Each unit has a
unique address configured during manufacture and is individually addressable by
the system controller. The radio address module is programmed to report at
regular intervals of 5 – 9 minutes.
Designed and manufactured using the latest techniques and surface-mount
technology ensures component count is kept to a minimum, thereby maximising
reliability.
The address/transmitter module is powered by a low-voltage dual supply
alkaline battery pack. The battery pack condition is continually monitored. The
battery pack has been tested to provide up to 5 years life at normal site
operations (10 - 30°C). The system indicates remaining battery capacity and a
low battery condition is indicated to the controller as a fault, leaving
approximately 30 days for the battery pack to be changed.
Specification
Dimensions:
106 x 75 mm with transmitter/address module
Weight:
119g
Operating Temperature:
-10 to 85 °C
Humidity:
Up to 95% non-condensing
Supply:
6 x 1.5 volt Alkaline AAA cells
Up to 5 years battery life (at normal site conditions 10 - 30°C)
Operating Frequencies:
VHF - 173.2 MHz -173.5 MHz (transmitter)
Channel Spacing:
25 kHz
Output Transmitter Power:
1 mW ERP
Outputs:
Detector alarm – Fire and Fault
Detector identity
Battery condition
Auto report signal
Standards:
Designed to comply with relevant parts of BS5839 and EN54
Ordering Information
Detector / address module complete:
Part Number 53 - 5120
An ISO9001:2008 approved company
EMS Group Head Office
Technology House
Sea Street
Herne Bay
Kent CT6 8JZ
England
Tel: +44 (0) 1227 369570
Fax: +44 (0) 1227 369679
Email: [email protected]
www.emsgroup.co.uk
Part No: FirePoint 5, v1.2
Dealer Information:
The
information
contained
within
this
literature is correct at time of publishing. The
EMS Group reserves the right to change any
information regarding products as part of its
continual
development
enhancing
new
technology and reliability. The EMS Group
advises that any product literature issue
numbers are checked with its head office prior
to any formal specifications being written.
FirePoint Combined Detector Sounder Features
■ Analogue/addressable
■ Proprietary sensor
■ Unique 1st stage audible alert feature, designed for hotels
etc
■ 2-Way radio communication
■ Up to 5 Years battery life
■ Selectable tone patterns for: fire, fire evacuation, bomb
alert & class change
■ Device removal detection
■ Range in excess of 250 metres
Overview
Designed and manufactured using the latest techniques including surface-mount
technology, the combined detector / sounder offers easy and quick installation
with the added benefit of a lower quantity of physical devices required for a
system.
The sounder section of the unit consists of its own integral energy source of up
to 5 years and is remotely activated and monitored by the system 5000
FirePoint controller. Each unit has a unique address configured during
manufacture and is individually addressable by the system controller.
The address module base is compatible with the range of system 5000 FirePoint
heads; these include optical, heat and combined sensor heads.
The sounder element is designed to be omni – directional with an output of 90
dBA at 1 metre. Making it ideal for hotels, boarding schools and nursing homes
where a detector and sounder would be required in each room.
The internal polling of the sensor is every 5 seconds, which accelerates to every
2 seconds when traces of smoke are detected. The alarm is then verified twice
to ensure freedom from false alarms.
Specification
Dimensions:
145 x 90mm
Weight:
650g
Operating Temperature:
-10 to 85 °C
Humidity:
Up to 95% non-condensing
Supply:
Up to 5 years integral energy source
Operating Frequencies:
VHF - 173.2 MHz -173.5 MHz (transmitter)
UHF - 458.5 MHz - 459.5 MHz (receiver)
Channel Spacing:
25 kHz
Output Transmitter Power:
1 mW ERP
Outputs:
Detector alarm
Detector fault
Detector pre-alarm
Detector tamper
Battery condition
Call in signal
Standards:
Designed to comply with relevant parts of BS5839 and EN54
Ordering Information
Combined sounder & optical detector:
Combined sounder & heat detector:
Part Number 53 - 5191
Part Number 53 - 5192
An ISO9001:2008 approved company
EMS Group Head Office
Technology House
Sea Street
Herne Bay
Kent CT6 8JZ
England
Tel: +44 (0) 1227 369570
Fax: +44 (0) 1227 369679
Email: [email protected]
www.emsgroup.co.uk
Part No: FirePoint 6, v1.2
Dealer Information:
The
information
contained
within
this
literature is correct at time of publishing. The
EMS Group reserves the right to change any
information regarding products as part of its
continual
development
enhancing
new
technology and reliability. The EMS Group
advises that any product literature issue
numbers are checked with its head office prior
to any formal specifications being written.
FirePoint Input / Output Unit Features
■ Fully addressable
■ Wireless activation
■ 2-way radio communication
■ Volt free relay output
■ Monitored input for fire & fault
■ Up to 5 Years battery life
■ Rear tamper protection
■ Range in excess of 250 metres
Overview
The EMS wireless input/output device is a battery operated device remotely
activated and monitored by the System 5000 FirePoint controller. Each unit has
a unique address configured during manufacture and is individually addressable
by the system controller.
The input/output unit provides the facility to transmit alarm signals from a beam
smoke detector system, aspirating detection and reporting to other fire related
systems or products. The radio input transmitter is fully monitored for fire and
fault conditions.
The unit provides the facility to operate various contact operated devices such as
magnetic door holders. The standard unit is capable of switching 24 volts Dc at a
maximum of 1 amp. Mains switching units are also available.
Specification
Dimensions:
250mm x 160mm x 40mm Injection moulded
Operating Temperature:
-10 to 55 °C
Humidity:
Up to 95% non-condensing
Supply:
Up to 5 years integral energy source
Operating Frequencies:
VHF - 173.2 MHz -173.5 MHz (transmitter)
UHF - 458.5 MHz - 459.5 MHz (receiver)
Channel Spacing:
25 kHz
Output Transmitter Power:
1 mW ERP
Outputs:
Standards:
Volt free contact rated 24vdc at 1 amp
“Call in” Signalling
Battery condition reporting
Designed to comply with EN54 part 18
Ordering Information
Addressable I/O unit:
I/O unit with external aerials:
Mains Switching I/O:
Part Number 53 - 5610
Part Number 53 - 5610/MH
Part Number 53 - 5620/230V
An ISO9001:2008 approved company
EMS Group Head Office
Technology House
Sea Street
Herne Bay
Kent CT6 8JZ
England
Tel: +44 (0) 1227 369570
Fax: +44 (0) 1227 369679
Email: [email protected]
www.emsgroup.co.uk
Part No: FirePoint 7, v1.3
Dealer Information:
The
information
contained
within
this
literature is correct at time of publishing. The
EMS Group reserves the right to change any
information regarding products as part of its
continual
development
enhancing
new
technology and reliability. The EMS Group
advises that any product literature issue
numbers are checked with its head office prior
to any formal specifications being written.
FirePoint Dual Sensor Features
■
Analogue/addressable
■
Proprietary sensor
■
Universal transmitter module
■
Up to 5 years battery life
■
Detector / transmitter tamper
■
Ziton Sensor alarm management (Verification)
using dual technology
■
Range in excess of 250 metres
Overview
The dual technology analogue addressable (combined) optical / heat detector is
bayonet fitted to a radio address / transmitter module incorporating an integral
energy source of up to 5 years. It is supplied with a surface-mount base unit.
Removal of the detector or address / transmitter module will indicate a fault
condition.
The heat detector section of the head operates on a highly sensitive thermistor,
which measures actual temperature and the rate of temperature rise change. At
regular intervals, the detector carries out a self- test that checks and verifies
every function.
The optical detector section of the head operates on an advanced light scattering
principle, using a wide-angle light beam together with an extra high sensitivity
photodiode receiver. The internal polling system checks for smoke particles
every 5 seconds, initial detection of smoke traces accelerates polling to every 2
seconds. The alarm is then verified twice to ensure freedom from false alarms.
When used in its dual technology verification mode, both heat and optical smoke
detection properties have to be activated again with 4 sensitivity levels, before
sending the alarm status to the controller.
Specification
Dimensions:
106 x 75 mm
Weight:
119g
Operating Temperature:
-10 to 55 °C
Humidity:
Up to 95% non-condensing
Supply:
Up to 5 years integral energy source
Operating Frequencies:
VHF - 173.2 MHz -173.5 MHz (transmitter)
Channel Spacing:
25 kHz
Output Transmitter Power:
1 mW ERP
Outputs:
Detector alarm
Detector fault
Detector pre-alarm
Battery condition
Call in signal
Standards:
Designed to comply with relevant parts of BS5839 and EN54
Ordering Information
Dual Sensor complete:
Part Number 53 - 5150
An ISO9001:2008 approved company
EMS Group Head Office
Technology House
Sea Street
Herne Bay
Kent CT6 8JZ
England
Tel: +44 (0) 1227 369570
Fax: +44 (0) 1227 369679
Email: [email protected]
www.emsgroup.co.uk
Part No: FirePoint 8, v1.2
Dealer Information:
The
information
contained
within
this
literature is correct at time of publishing. The
EMS Group reserves the right to change any
information regarding products as part of its
continual
development
enhancing
new
technology and reliability. The EMS Group
advises that any product literature issue
numbers are checked with its head office prior
to any formal specifications being written.
FirePoint Radio LAN Module Features
■ Typical range in excess of 500 metres
■ Fully monitored
■ Networking via radio (up to 27 panels)
■ Mains powered with battery backup
■ High strength steel enclosure
■ 485 bus connection to EMS System 5000 fire panel
Overview
The 5000 FirePoint range of controllers is capable of being expanded using
network signalling. This can be achieved with the connection of a 53-5438 Radio
LAN module to the RS-485 Bus of the control panel.
Up to 27 panels can be radio linked on a site, giving device and signal expansion
for up to 7560 radio devices.
The Radio LAN is fully monitored by the system controllers and gives the added
ability to control mimic / repeater panels
Utilising the functionality of the Radio LAN eliminates the need for excess cable
runs between control panels, this not only cuts the overall installation cost of the
system, but also considerably reduces the amount of time required for
installation.
Specification
Dimensions:
Operating Temperature:
390 x 320 x 80mm
-10 to 55 °C
Humidity:
Up to 75% non-condensing
Supply:
230 V
Operating Frequencies:
UHF - 458.5 MHz - 459.5 MHz (receiver)
Channel Spacing:
25 kHz
Output Transmitter Power:
500 mW ERP
Standards:
Designed to comply with relevant parts of BS5839 and EN54
Ordering Information
LAN Module
Part Number 53 - 5438
An ISO9001:2008 approved company
EMS Group Head Office
Technology House
Sea Street
Herne Bay
Kent CT6 8JZ
England
Tel: +44 (0) 1227 369570
Fax: +44 (0) 1227 369679
Email: [email protected]
www.emsgroup.co.uk
Part No: FirePoint 9, v1.2
Dealer Information:
The
information
contained
within
this
literature is correct at time of publishing. The
EMS Group reserves the right to change any
information regarding products as part of its
continual
development
enhancing
new
technology and reliability. The EMS Group
advises that any product literature issue
numbers are checked with its head office prior
to any formal specifications being written.
FirePoint High Gain Aerials
DIMENSIONS: 660mm Long
DIMENSIONS: 660mm Long
OPERATING FREQUENCIES:
OPERATING FREQUENCIES:
UHF 458.5 - 459.5 Mhz
UHF 458.5 – 459.5 Mhz
Ordering information :
5-5501 (UHF high gain aerial complete with 3m
RG58 cable and fixing bracket).
5-5501/BP10 (UHF high gain aerial complete with
mounting bracket, extension pole & 10m RG213
cable).
5-5501/BP20 (UHF high gain aerial complete with
mounting bracket, extension pole & 20m RG213
cable).
5-5501/BP30 (UHF high gain aerial complete with
mounting bracket, extension pole & 30m RG213
cable).
Ordering information :
5-7329 (UHF 3dB high gain aerial).
5-7329/BP10 (UHF 3dB high gain aerial c/w
mounting bracket, extension pole & 10m RG213
cable).
5-7329/BP20 (UHF 3dB high gain aerial c/w
mounting bracket, extension pole & 20m RG213
cable).
5-7329/BP30 (UHF 3dB high gain aerial c/w
mounting bracket, extension pole & 30m RG213
cable).
DIMENSIONS : 160mm Long
DIMENSIONS: 160mm Long
OPERATING FREQUENCY :VHF 173Mhz
OPERATING FREQUENCY :UHF 458Mhz
Ordering information :
Ordering information :
5-5521
(UHF helical aerial supplied with BNC connector)
5-5520
(VHF helical aerial supplied with BNC connector)
DIMENSIONS: 860mm Long
DIMENSIONS: 540mm
OPERATING FREQUENCY:
OPERATING FREQUENCY:
VHF 173 Mhz
UHF 458.5 – 459.5 Mhz
Ordering information :
Ordering information :
5-5500 (VHF high gain aerial complete with 10m RG58
cable and fixing bracket).
5-5500/BP10 (VHF high gain aerial complete with
mounting bracket, extension pole & 10m RG213 cable).
5-5500/BP20 (VHF high gain aerial complete with
mounting bracket, extension pole & 20m RG213 cable).
5-5500/BP30 (VHF high gain aerial complete with
mounting bracket, extension pole & 30m RG213 cable).
5-7326/BP10 (UHF directional aerial
bracket, extension pole & 10m RG213
5-7326/BP20 (UHF directional aerial
bracket, extension pole & 20m RG213
5-7326/BP30 (UHF directional aerial
bracket, extension pole & 30m RG213
An ISO9001:2008 approved company
EMS Group Head Office
Technology House
Sea Street
Herne Bay
Kent CT6 8JZ
England
Tel: +44 (0) 1227 369570
Fax: +44 (0) 1227 369679
Email: [email protected]
www.emsgroup.co.uk
Part No: FirePoint 10, v1.2
c/w mounting
cable).
c/w mounting
cable).
c/w mounting
cable).
Dealer Information:
The
information
contained
within
this
literature is correct at time of publishing. The
EMS Group reserves the right to change any
information regarding products as part of its
continual
development
enhancing
new
technology and reliability. The EMS Group
advises that any product literature issue
numbers are checked with its head office prior
to any formal specifications being written.
FirePoint Combined Voice Sounder Sensor Features
■ Proprietary sensor
st
■ Unique 1 stage audible alert feature, designed for hotels etc
■ Programmable Alert message
■ Up to Four messages
■ 2-Way radio communication
■ Up to 3 Years battery life
■ Device removal detection
■ Range in excess of 250 metres
Overview
Designed and manufactured using the latest techniques including surface-mount
technology, the combined detector / voice sounder offers quick and easy
installation with the added benefit of a lower quantity of physical devices
required for a system.
he wireless voice message evacuation / smoke detection device is a battery
operated unit, remotely activated and monitored by the 5000 FirePoint
controller. Each unit has a unique address configured during manufacture and is
individually addressable by the system controller. Each unit can produce up to 4
separate fully synchronised, locally stored audio messages. These messages can
be triggered either by a standard EMS 5000 FirePoint control panel or a separate
voice evacuation controller.
The sounder section of the unit consists of its own integral energy source,
typically lasting up to 3 years and is remotely activated and monitored by the
5000 FirePoint controller.
The detection section of the unit is available with various options; these include
optical, heat and combined sensor heads.
The sounder element is designed to be omni – directional with an output of 90
dBA at 1 metre. Making it ideal for hotels, boarding schools and nursing homes
where a detector and sounder would be required in each room.
The internal polling of the sensor is every 5 seconds, which accelerates to every
2 seconds when traces of smoke or heat are detected. The alarm is then verified
twice to ensure freedom from false alarms.
Specification
Dimensions:
145 x 90mm
Weight:
650g
Operating Temperature:
-10 to 85 °C
Humidity:
Up to 95% non-condensing
Supply:
Up to 3 years integral energy source
Operating Frequencies:
VHF - 173.2 MHz -173.5 MHz (transmitter)
UHF - 458.5 MHz - 459.5 MHz (receiver)
Channel Spacing:
25 kHz
Output Transmitter Power:
1 mW ERP
Outputs:
Detector alarm
Detector fault
Detector pre-alarm
Detector tamper
Battery condition
Call in signal
Standards:
Designed to comply with relevant parts of BS5839 and EN54
Ordering Information
Voice sounder with Optical Sensor:
Voice Sounder with Dual Sensor:
Voice Sounder with Heat Sensor:
Part Number 53 - 5196
Part Number 53 - 5165
Part Number 53 - 5197
An ISO9001:2008 approved company
EMS Group Head Office
Technology House
Sea Street
Herne Bay
Kent CT6 8JZ
England
Tel: +44 (0) 1227 369570
Fax: +44 (0) 1227 369679
Email: [email protected]
www.emsgroup.co.uk
Part No: FirePoint 11, v1.2
Dealer Information:
The
information
contained
within
this
literature is correct at time of publishing. The
EMS Group reserves the right to change any
information regarding products as part of its
continual
development
enhancing
new
technology and reliability. The EMS Group
advises that any product literature issue
numbers are checked with its head office prior
to any formal specifications being written.
FirePoint Transponder Features
■ Fully addressable
■ Wireless signalling path
■ Dual frequency radio communication
■ Monitored for fault
■ Mains powered
■ Tamper protection
■ Range in excess of 500 metres
Overview
The EMS wireless transponder is a mains powered device that is used to
enhance the signalling range of EMS 5000 FirePoint detection devices, without
the need to use hardwired range extenders.
The units are supplied with their own integral power supply and battery backup.
The 5000 FirePoint transponder is compatible with our entire range fire control
panels when the controller is coupled to a UHF remote receiver, connected to the
RS485 BUS of the 5000 FirePoint controller.
Specification
Dimensions:
Transponder
390mm x 320mm x 80mm
Remote Receiver
390mm x 320mm x 80mm
Operating Temperature:
-10 to 55 °C
Humidity:
Up to 95% non-condensing
Supply:
230v 50Hz
Operating Frequencies:
VHF - 173.2 MHz -173.5 MHz
UHF - 458.5 MHz - 459.5 MHz
Channel Spacing:
25 kHz
Output Transmitter Power:
500 mW ERP
Standards:
Designed to comply with relevant parts of BS5839 and EN54
Ordering Information
VHF Signal Transponder
UHF Remote Reciever
Part Number 53 – 5400
Part Number 53 – 5428
An ISO9001:2008 approved company
EMS Group Head Office
Technology House
Sea Street
Herne Bay
Kent CT6 8JZ
England
Tel: +44 (0) 1227 369570
Fax: +44 (0) 1227 369679
Email: [email protected]
www.emsgroup.co.uk
Part No: FirePoint 12, v1.2
Dealer Information:
The
information
contained
within
this
literature is correct at time of publishing. The
EMS Group reserves the right to change any
information regarding products as part of its
continual
development
enhancing
new
technology and reliability. The EMS Group
advises that any product literature issue
numbers are checked with its head office prior
to any formal specifications being written.
Radio Door Closer Features
■
Fast, automatic fire door release when alarm
sounds
■
Installs in under five minutes
■
Easy, foot-operated manual release / adjustment
operation
■
Reliable, acoustic detection
■
Smart, unobtrusive design
■
Integral power-on LED indicator
■
Low battery, automatic door release
■
Optional floor plate for especially heavy doors /
slippery floor surfaces
■
No unsightly cabling
Overview
Wedging open a fire door is illegal, dangerous and opens you, the employer, to the risk of
personal prosecution.
Because as an integral part of any building’s fire safety strategy, the fire doors are
routinely propped open with wedges, waste bins, fire extinguishers or whatever else may
be close at hand so people can move as quickly and as easily as possible, whatever they
may be carrying or pushing. Understandable perhaps, but incredibly dangerous and in
direct contravention of the UK Fire Precautions (Workplace) Regulations 1997.
In the event of a fire, this hazardous practice will almost certainly guarantee the fire
spreads more quickly, causes more damage and ultimately, puts people’s lives and
property under much greater threat. It can also count against subsequent insurance
claims.
There is a cost-effective alternative. One that can keep each and every one of your fire
doors open at any time of day or night, and can do so, easily, safely and legally.
Radio door close is the simple, reliable acoustic device that holds a fire door open in any
position and then automatically releases the door should a fire alarm sound.
Inexpensive to buy, Radio door close is also quick and easy to install. It simply screw-fits
to the bottom of the chosen fire door in a matter of minutes with no risk to the fire door’s
integrity.
The unit’s rubber plunger/stopper is in contact with the floor and unlike magnetic
retainers, can hold the door open in any selected position. When a fire alarm sounds,
Radio door close’s integral audio-electronic device signals the plunger stopper to retract
and releases the door to close. Radio door close is battery operated so there is no need
for complex and expensive wiring.
Fast, simple and already effective in thousands of buildings across the UK today.
Recognised and endorsed by fire industry institutions, reduce your fire risk with Radio
door close – your automatic, inexpensive door retainer solution.
Specification
Dimensions:
153 x 195 x 45mm
Operating Temperature:
-10 to 55 °C
Humidity:
Up to 95% non-condensing
Supply:
Door Release: 2 x 1.5v “C” cells
Radio TX Unit: 2 x 1.5v “C” cells
Standards:
Designed to comply with relevant parts of BS5839 and EN54
Ordering Information
Acoustically Operated Door Close:
Doorgard X (Transmitter Unit):
Doorgard X (Radio Door Release Unit):
Part Number 53 - ADR/B
Part Number 53 - RDT/W
Part Number 53 - 53-RDR/B
An ISO9001:2008 approved company
EMS Group Head Office
Technology House
Sea Street
Herne Bay
Kent CT6 8JZ
England
Tel: +44 (0) 1227 369570
Fax: +44 (0) 1227 369679
Email: [email protected]
www.emsgroup.co.uk
Part No: FirePoint 13, v1.2
Dealer Information:
The
information
contained
within
this
literature is correct at time of publishing. The
EMS Group reserves the right to change any
information regarding products as part of its
continual
development
enhancing
new
technology and reliability. The EMS Group
advises that any product literature issue
numbers are checked with its head office prior
to any formal specifications being written.
FirePoint Sounder Sensor Visual Indicator Features
■
Analogue/addressable
■
Proprietary sensor
■
LED Flashing visual indicator
■
Unique 1st stage audible / visual alert feature, designed for
hotels, DDA, etc
■
2-Way radio communication
■
Up to 5 Years battery life
■
Selectable tone patterns for: fire evacuation, bomb, alert & class
change
■
Device removal detection
■
Range in excess of 250 metres
Overview
Designed and manufactured using the latest techniques, including surfacemount technology the combined detector / sounder / visual indicator offers
quick and easy installation with the added benefit of a lower quantity of physical
devices required for a system.
The sounder / visual indicator part of the unit consists of its own integral energy
source of up to 5 years and is remotely activated and monitored by the system
5000 FirePoint controller. Each unit has a unique address configured during
manufacture and is individually addressable by the system controller.
The device is available with detector options for optical, heat and multi-sensor
heads.
The sounder element is designed to be omni – directional with an Output of 90
dBA at 1 metre. Making it ideal for hotels, boarding schools and nursing homes
where a detector and sounder would be required in each room, with the added
benefit of the LED beacon designed to comply with the requirements of the DDA.
The internal polling of the sensor is every 5 seconds, which accelerates to every
2 seconds when traces of smoke are detected. The alarm is then verified twice
to ensure freedom from false alarms
Specification
Dimensions:
145 x 90mm
Operating Temperature:
-10 to 55 °C
Humidity:
Up to 95% non-condensing
Supply:
Up to 5 years integral energy source
Operating Frequencies:
VHF - 173.2 MHz -173.5 MHz (transmitter)
UHF - 458.5 MHz - 459.5 MHz (receiver)
Channel Spacing:
25 kHz
Output Transmitter Power:
1 mW ERP
Outputs:
Detector alarm
Detector fault
Detector pre-alarm
Detector tamper
Battery condition
Call in signal
Standards:
Designed to comply with relevant parts of BS5839 and EN54
Ordering Information
Combined Sounder Optical Sensor Visual
Indicator
Combined Sounder Heat Sensor Visual
Indicator
Part Number 53 – 5191/S
Part Number 53 – 5192/S
An ISO9001:2008 approved company
EMS Group Head Office
Technology House
Sea Street
Herne Bay
Kent CT6 8JZ
England
Tel: +44 (0) 1227 369570
Fax: +44 (0) 1227 369679
Email: [email protected]
www.emsgroup.co.uk
Part No: FirePoint 14, v1.3
Dealer Information:
The
information
contained
within
this
literature is correct at time of publishing. The
EMS Group reserves the right to change any
information regarding products as part of its
continual
development
enhancing
new
technology and reliability. The EMS Group
advises that any product literature issue
numbers are checked with its head office prior
to any formal specifications being written.