Or the PDF
Transcription
Or the PDF
VACUUM COLLECTION SYSTEM DESIGN MANUAL FOR SUPERMARKETS GENERAL SYSTEM INFORMATION Provides general system information including the benefits of the EVAC system, operation, typical components used and their location. 1 PRELIMINARY DESIGN Proposes questions for the designer in order to layout the system. The section also provides a design checklist and the general rules of design for the vacuum drainage piping. VACUUM COLLECTION SYSTEM DESIGN MANUAL FOR SUPERMARKETS The purpose of this Design Manual is to not only present our product, but to also provide the necessary information for an engineering consultant firm or for a customer engineering department to layout and properly document the installation of an EVAC collection system for a supermarket. The EVAC Vacuum Collection System Design Manual will take the designer through a stepby-step process for design of an EVAC vacuum collection system. This step-by-step process is divided into the following sections 2 SIZING OF THE EVAC VACUUM SYSTEM Teaches the designer how to size the waste pipe in an EVAC collection system and enables the user to choose the proper vacuum central. 3 DESIGN INFORMATION Provides the designer with specific design details for connection to fixtures. 4 PRODUCT CATALOG SHEETS Provides the designer with specific product information and selection. 5 INSTALLATION INSTRUCTION SHEETS Contains the fixture and product installation cut sheets. 6 SAMPLE SPECIFICATIONS Envirovac, Inc. 1260 Turret Drive Rockford, IL 61115 USA 888 438 3822 815 654 8300 Fax 815 654 8306 Contains sample specifications that can be used by the designer for construction documentation. WARRANTY 7 8 SECTION 1 GENERAL SYSTEM INFORMATION This section provides general system information including the benefits of the EVAC system, operation, typical components used, and their location. 1.1 PURPOSE The EVAC vacuum collection system is designed to eliminate or significantly reduce the under-floor drainage piping in the supermarket’s sales area. 1.2 BENEFITS The following are the basic benefits of an EVAC vacuum collection system for supermarkets. 1.2.1 Complete floor plan design flexibility. 1.2.2 Easy and less costly relocation of refrigerated display cases. 1.2.3 For retrofits — the EVAC system eliminates the additional cost and inconvenience associated with concrete cutting and floor patching. 1.3 PRINCIPLES OF OPERATION The EVAC collection system uses differential air pressure to transport waste as opposed to a gravityinduced flow of a conventional wastewater collection system. A vacuum collection system consists of four components: 1. Vacuum central collection tanks 2. Interface valves a. Activator b. Discharge valve 3. Buffers 4. Vacuum drainage piping. An EVAC collection system uses a vacuum central similar to that of a gravity lift station or pumping station. The vacuum central is equipped with vacuum pumps in order to maintain a negative pressure in the drainage piping feeding into the vacuum central. Vacuum is maintained in the drainage piping with the installation of normally-closed interface valves. As the 1260 Turret Drive • Rockford, IL 61115 USA 888 438 3822 • 815 654 8300 • Fax 815 654 8306 interface valve is opened, wastewater is pushed through the piping by in-rushing air into the vacuum drainage piping. The valve then closes and waits for another cycle. The interface valves are pneumaticallyoperated using the negative pressure contained in the vacuum drainage piping. The buffer collects the wastewater from a fixture(s). The accumulation of wastewater in the buffer is sensed, pneumatically, by the interface valve’s activator. The interface valve’s cycle begins when the amount of water reaches a preset level. The vacuum drainage piping is simple to install compared to gravity drainage piping. Vacuum drainage piping is smaller in diameter, requires no venting and no continuous slope. Vacuum drainage piping is designed with vertical lifts resulting in design flexibility and installation savings. Generally, a mechanical/refrigeration contractor installs the vacuum drainage piping. The design criteria for the EVAC Vacuum Collection System are contained in the following sections. 1.4 EVAC VACUUM SYSTEM COMPONENTS 1.4.1 Vacuum Central The EVAC vacuum central is a single unit consisting of a set of vacuum pumps, collection tank(s), an electrical control panel, and the necessary valves and piping. 1.4.2 Interface Valve The Interface Valve consists of a discharge valve and an activator. The interface valve is used in conjunction with an EVAC Buffer. The activator senses wastewater in a buffer and opens the discharge valve to transport the wastewater toward the vacuum central. The interface valve uses no electrical components and operates using the negative pressure available in the vacuum drainage piping. 1.4.3 EVAC Buffer The EVAC Buffer is a component supplied by EVAC that collects wastewater from a fixture(s) so it can be sensed © 1998 Envirovac, Inc. Section 1.0.0 SECTION 1 GENERAL SYSTEM INFORMATION by the interface valve. A contractor installs it according to the installation sheets contained in Section 6. 1.4.4 EVAC Check Valves Vacuum check valves are supplied by EVAC to prevent back-flow in the vacuum drainage piping. The EVAC check valves are typically installed in only a few locations. In most cases, the interface valve acts as the check valve. 1.5.5 Isolation Valves Typically, isolation valves are installed directly in the vacuum waste piping where a main or branch splits to service another section of the store. The design engineer determines the quantity and location of the isolation valves. 1.6 VACUUM DRAINAGE PIPING LAYOUT 1.4.5 Isolation Valves As an option, full-port ball valves may be specified in the vacuum drainage piping for isolation. Isolation valves allow for maintenance or re-modeling to be performed on the system without losing use of the whole system. 1.5 TYPICAL LOCATION COMPONENTS OF 1.5.1 Vacuum Central It is recommended to install the vacuum central at the back of the store in either a dedicated mechanical space or on a mezzanine level. Please refer to Section 6. 1.5.2 Interface Valve Mounting of the activator and discharge valve is dependent upon the type of refrigerated display case or fixture. Please refer to Section 6. 1.5.3 EVAC Buffer The EVAC Buffer is installed beneath or behind a refrigerated display case or fixture enabling it to be gravity fed. The location of the buffer is dependent upon the type of refrigerated display case or plumbing fixture. Please refer to Section 6. 1.6.1 General Routing of Vacuum Drainage Piping Typically, vacuum drainage piping is located above a dropped ceiling or near the roof joists in an open ceiling. The vacuum drainage piping is strategically installed with lateral branches to provide future flexibility and connection to the system. Risers from refrigerated display cases are located near support columns or in false columns. As a general rule, the vacuum drainage piping follows the refrigeration piping. Some customers may prefer not to have false columns installed for island refrigerated display cases. In these instances the waste piping from the island cases may be installed as gravity plumbing in a shallow trench that contains the electrical and refrigeration piping. At a point at which a riser is acceptable, the gravity plumbing enters a buffer for collection by the vacuum waste system. Using trenches reduces the vacuum waste collection system’s benefits by reducing the flexibility of moving the island cases in the future. 1.6.2 Location of Valving 1.5.4 EVAC Check Valves The type of case determines the location of the interface valves. The details in Section 6 show the typical location of the interface valve components. These details may be referred to after the system is installed to facilitate service and/or maintenance. Typically, EVAC check valves are installed at the top of a vertical riser pipe when the interface valve is mounted low in the same vertical riser piping. All EVAC valves located in the store must be installed in areas that are readily accessible for future service and/or maintenance. © 1998 Envirovac, Inc. Section 1.0.0 1260 Turret Drive • Rockford, IL 61115 USA 888 438 3822 • 815 654 8300 • Fax 815 654 8306 SECTION 2 PRELIMINARY DESIGN Design Questions, Check List and General Rules This section identifies questions for the designer for layout of the system. The section also provides a design checklist and the general rules of design for the vacuum drainage piping. If no When the EVAC Collection System is used solely to collect condensate waste from display cases there are typically no air gaps at each case. A single air gap is located at the discharge pipe of the vacuum central prior to entering into the gravity sanitary drainage piping. 2.1 SYSTEM DESIGN PREPARATION If yes 2.1.1 Determine the scope of the project or usage. The EVAC Collection System is being used to collect sanitary fixtures, air gaps may be required by code at the refrigerated cases. This is a critical issue as there are several types of cases with low profiles that may require shimming to provide space for an air gap prior to entering into the EVAC Buffer. Shimming must be coordinated with the installer of the refrigerated cases. The purpose of the EVAC Collection System is to eliminate or significantly reduce the under-floor piping within the sales area of a supermarket. The customer must be consulted in order to facilitate design: (Check the appropriate boxes.) 2.1.2 Vacuum Central Design Considerations a. Will utility trenches be eliminated and will all electrical and refrigerant piping be routed from above for all cases? a. Will the vacuum central be located in a mechanical room or allocated space in the stocking room or mezzanine level? q Yes q No q Mechanical room q Stock room/mezzanine b. Are false columns containing the electrical, refrigerant piping and vacuum waste piping acceptable for island cases? q Yes q No If located on mezzanine, the vacuum drainage piping must always enter the vacuum central from above. b. Will back-up emergency power be available for the vacuum central? q Yes If not, the waste piping would need to be under-floor or in a shallow utilities trench. c. c. Does the customer want the refrigeration units contained in the walk-in coolers to be connected to the vacuum waste system? q Yes q No q No Will the vacuum central alarms be connected to the building management system for the refrigerated display cases? q Yes q No 2.1.3 EVAC Buffer Design Considerations Typically, there is no advantage to collect the units at the back of a store on the vacuum system as the units can be easily connected to a near-by gravity waste line. d. Will sanitary and gray water fixtures, such as hand sinks or prep sinks, be collected by the vacuum waste system? q Yes q No 1260 Turret Drive • Rockford, IL 61115 USA 888 438 3822 • 815 654 8300 • Fax 815 654 8306 The EVAC Buffer, EB-025, requires an installation space of 4.25" in height and 4.50" in width. For each refrigerated case the following considerations needs to be made with regard to space under the case. Typically, low profile cases such as specialty end cases, dairy, reach-in frozen food, and specialty deli-bakery cases require considerations. © 1998 Envirovac, Inc. Section 2.0.0 SECTION 2 PRELIMINARY DESIGN Design Questions, Check List and General Rules a. Will the EVAC Buffer fit under the case either from the front or slide in from one end of the case? q Yes q No If no There are two options, 1. 2. Detail the location of the buffer at the side of the case or behind the case. The customer must have the case manufacturer furnish an elevated base. b. Will the drainage piping from the case line-up have a continuous slope prior to entering the buffer? Various cases may have very limited space from the drain to the floor or end base frames that make it difficult to maintain a continuous slope from case to case. q Yes q No There are three options, Specify additional valve kits and buffers for the case line-up to insure that there is a continuous slope of the drainage piping feeding the buffer. 2. Detail the drainage piping behind the case. 3. The customer must have the case manufacturer furnish an elevated base. 2.1.4 Determine any Code Restrictions a. Condensate Collection System Does your local plumbing authority and/or public health department require system intention use to be submitted? q Yes Does your local plumbing authority and/or public health department require system intention use to be submitted? q Yes q No Using an EVAC Collection System to collect sanitary fixtures, such as sinks, may require a submittal of the intended use to the local plumbing authority and/or the public health office. Consult your local EVAC representative for any questions regarding this issue. 2.2. DESIGN CHECKLIST 2.2.1 Has the full scope of the project been identified? q Yes If no 1. b. Sanitary Collection System q No The EVAC Collection System is a process system for safe waste or condensate. Many jurisdictions require the intended use of the system to be submitted to the local plumbing authority and/or the public health office. Consult your local EVAC representative for any questions regarding this issue. EVAC has received approval for use of the collecting system in many jurisdictions. q No 2.2.2 Have all approval agencies and their requirements been identified? q Yes q No 2.2.3 Have all project guidelines and specifications been identified? q Yes q No 2.2.4 Has the configuration of the EVAC collection system been identified based upon available utilities and customer requirements? q Yes q No 2.2.5 Has the available electrical power, including emergency power, been identified? q Yes q No 2.2.6 Have instructions to other trades, such as refrigeration installers and electricians been Identified? q Yes © 1998 Envirovac, Inc. Section 2.0.0 q No 1260 Turret Drive • Rockford, IL 61115 USA 888 438 3822 • 815 654 8300 • Fax 815 654 8306 SECTION 2 PRELIMINARY DESIGN Design Questions, Check List and General Rules 2.3. GENERAL RULES OF DESIGN Reference the installation instruction sheet for vacuum drainage piping contained in Section 6.6.2. 2.3.1 Vacuum Drainage Piping 2.3.2 Piping Materials, refer to the sample specification in Section 7. a. Plastics, as permitted by Codes and Variances a.1. a.2. a.3. PVC Schedule 40 or Schedule 80 ABS Schedule 40 or Schedule 80 HDPE, rated for 100% vacuum pressure. Vacuum drainage piping begins at the buffer outlet. a. Pitch all horizontal vacuum piping at a minimum 1/16" per foot. This requirement may sometimes be met by using the pitch of the store roof from front to back. Minimum Required Drainage Slope 1/16" 1’-0" b. Support piping at 5’ intervals and within 1 foot of each change in direction. Sagging of the pipe between supports is not permitted. c. Use only long radius 90O elbows or (2) 45O elbows in the vacuum drainage piping. No standard 90O elbows are permitted. b. Metallic b.1. b.2. 2.3.3. Vertical Lift Rules a. Each buffer shall be provided with it’s own riser pipe except as follows: Reach-in frozen food refrigerated cases may have a common riser for a branch main located at the top of the case line-up. Reference the installation instructions for vacuum drainage piping in Section 6. b. Riser pipes must enter the tops of mains or branches through wye pattern fittings rolled not more than 45O from vertical see Figure 1. d. Risers are to enter mains from above using a wye pattern fitting. The wye fitting may be rolled a maximum of 45O from vertical see Figure 1. e. No tee fittings are permitted in the vacuum drainage piping. f. Copper, Type ‘M’, hard drawn tubing. Due to surface roughness, cast iron or steel pipe is not permitted. 45O Figure 1. Internal surfaces of the piping and joints must be smooth, free of burrs and obstructions. g. Locate clean-outs in the vacuum drainage piping at the ends of mains and branches and when there is a 90O change in direction in an overhead branch or main. h. Isolation and check valves are to be full-port valves, rated for vacuum. 1260 Turret Drive • Rockford, IL 61115 USA 888 438 3822 • 815 654 8300 • Fax 815 654 8306 © 1998 Envirovac, Inc. Section 2.0.0 SECTION 2 PRELIMINARY DESIGN Design Questions, Check List and General Rules c. A single offset is allowed in vertical risers. Note: An offset is not preferred and should only be used to bypass structural obstructions. See Figure 2. YES YES NO Offset 1’-0" Horizontal Maximum Offset Figure 2. © 1998 Envirovac, Inc. Section 2.0.0 1260 Turret Drive • Rockford, IL 61115 USA 888 438 3822 • 815 654 8300 • Fax 815 654 8306 SECTION 3.0 SIZING OF THE EVAC VACUUM COLLECTION SYSTEM This section instructs the designer how to size the vacuum waste pipe in an EVAC Vacuum Collection System and enables the user to choose the proper vacuum central. Table 3.1 Equivalent Interface Valve Drainage Fixture Units Buffer or Detail IVDFU Refrigerated Display Cases EB-025-R 0.5 Walk-in Cooler Refrig. Coils EB-025-R 0.5 Walk-in Cooler Refrig. Coils EB-025-R 0.5 Trench Drain for Refrig. Display Cases 2" Buffer Detail 0.5 Trench Drain for Refrig. Display Cases 2" Buffer Detail 0.5 Hand Sink, Plastic Drainage Piping EB-025-SP 5 Hand Sink, Plastic Drainage Piping EB-025-SP 5 Hand Sink, Copper Drainage Piping EB-025-SC 5 Hand Sink, Copper Drainage Piping EB-025-SC 5 Fixture or Configuration 3.1 INTERFACE VALVE DRAINAGE FIXTURE UNITS The interface valve drainage fixture units, IVDFU, contained in Table 3.1 are used to determine the size of the vacuum central and the vacuum drainage piping. Table 3.1 shows the equivalent interface valve drainage fixture units for fixtures or connections that may be connected to an EVAC vacuum waste system. All fixtures are to be connected to an EVAC Buffer or EVAC designed buffer. Reference the system sizing chart contained at the end of this section. 3.2 KEY SYSTEM PARAMETERS Table 3.1 provides a fixture unit equivalent for the EVAC Buffers. Once a fixture is connected to one of the buffers described above, the equivalent IVDFU for the buffer takes precedence over the IVDFU for the plumbing fixture. 3.2.1 Buffer assigned IVDFU value. IVDFU value assigned for the EVAC Buffer, Model EB025, is dependent upon the number of defrost cycles occurring at any given time in a store. An IVDFU value of 0.5 is based upon one defrost cycle occurring at one time with a maximum of (3) EVAC Buffers, EB-025, connected to the refrigerated cases effected by the defrost cycles. Scheduling more than one defrost cycle to occur at the same time increases the IVDFU value for the EVAC Buffer, EB-025. # of Defrost Cycles Occurring at Same Time EVAC Buffer EB-025 IVDFU 1 2 0.5 2.0 Note: It is not recommended to schedule more than one defrost cycle at the same time. 3.2.2 Wash-down assigned IVDFU value. A 2" vacuum drainage pipe is rated for 12 IVDFU and therefore can handle one wash-down of one refrigerated case. 3.3 CONDENSATE COLLECTION VS. CONDENSATE AND SANITARY COLLECTION An important design consideration for collecting strictly condensate waste versus condensate waste plus sanitary waste is the required air gaps for refrigerated display cases. In a gravity waste system each set of refrigerated display cases is connected to under-floor gravity sanitary waste piping through an air gap. When using an EVAC vacuum collection system to collect only condensate waste, there is only one air gap for the system, located at the discharge of the vacuum central. A wash-down of a single refrigerated display case creates a design load equivalent to 12 IVDFU. For pipe sizing ignore all other fixtures when sizing to accommodate wash-downs. 1260 Turret Drive • Rockford, IL 61115 USA 888 438 3822 • 815 654 8300 • Fax 815 654 8306 © 1998 Envirovac, Inc. Section 3.0.0 SECTION 3.0 SIZING OF THE EVAC VACUUM COLLECTION SYSTEM Once a single sanitary fixture is connected to the vacuum waste system, air gaps may be required at each set of case connections prior to entering a buffer. Under these circumstances, low profile cases will require special considerations in order to accommodate an air gap and the installation of an EVAC Buffer. Contact an EVAC Representative for assistance. Vacuum Drainage Pipe Sizing Examples. Example#1: Two branches connect into one main that is collecting all of the refrigerated display cases in the store. The store has 120 refrigerated cases all separated by defrost cycle time with 40 EVAC Buffers, Model EB-025. IVDFUs 3.4 DEFROST CYCLES Groups of refrigerated display cases in a supermarket are on a specific refrigeration circuit, (i.e., on a specific refrigeration compressor). The equivalent drainage fixture units in Table 3.1 are based upon one refrigeration circuit going into defrost at one particular time with a maximum of (3) EVAC Buffers connected to the refrigerated cases effected by the defrost cycle. = 40 (EB-025) x 0.5 IVDFU/buffer = 20 total The required pipe size for the main is 3" as a 2" pipe can only transport a maximum of 12 IVDFUs. Example#2: 2" 2" 2" A The sizing of the vacuum central and the vacuum piping in the system is based upon one defrost cycle occurring at any time. It is not recommended to schedule more than one defrost cycle at the same time. 3.5 VACUUM DRAINAGE PIPE SIZING Hand Sink (5 IVDFU) EB-025-R 3" D Hand Sink (5 IVDFU) EB-025-R EB-025-R Hand Sink (5 IVDFU) In this particular vacuum branch line there are (3) hand (general) sinks and (3) EVAC Buffers for refrigerated display cases. The hand sinks are connected to an EVAC Buffer, Model EB-025-SP. At Location A. 3.5.1 Mains and branches The maximum IVDFUs allowed on a particular pipe size are shown in Table 3.2. IVDFUs = 1 (Hand Sink thru EB-025-SP) x 5 IVDFU/buffer = 5 Total Pipe Size = 2" At Location D. When laying out the mains and branches begin with a 2" pipe. As fixtures are added increase the branch and main pipe sizes as specified in Table 3.2. Examples of vacuum drainage pipe sizing are contained in the following. IVDFUs = 3 (Hand Sink thru EB-025-SP) x 5 IVDFU/buffer + 3 (EB-025-R) x 0.5 IVDFU/buffer = 16.5 Total Pipe Size = 3" Therefore, a vacuum central that can accommodate 16.5 IVDFUs must be specified. Table 3.2 Pipe Size vs. IVDFUs Size of Vacuum Pipe (inches/mm) Maximum IVDFUs Maximum Horizontal Length (feet/meters) © 1998 Envirovac, Inc. Section 3.0.0 2/50 3/80 4/100 12 132 292 400/125 900/280 2000/650 1260 Turret Drive • Rockford, IL 61115 USA 888 438 3822 • 815 654 8300 • Fax 815 654 8306 SECTION 3.0 SIZING OF THE EVAC VACUUM COLLECTION SYSTEM Example #3: Total IVDFUs is 38, requiring vacuum central SM260-30H. 2" 2" 2" EB-025-R (0.5 IVDFU) 4, EB-025-R for Refrigerated Cases (0.5 IVDFU each) 2, Hand Sinks (5 IVDFU each) 3" EB-025-R (0.5 IVDFU) 3" Pipe size increases to 3" for upper portion and remains 2" for lower portion of layout. 2" Vacuum Central EB-025-R (0.5 IVDFU) 5, EB-025-R for Refrigerated Cases (0.5 IVDFU each) EB-025-R (0.5 IVDFU) 2" 2" EB-025-R (0.5 IVDFU) 2" EB-025-R (0.5 IVDFU) 5, EB-025-R for Refrigerated Cases (0.5 IVDFU each) 2" 2" EB-025-R (0.5 IVDFU) 7, EB-025-R for Refrigerated Cases (0.5 IVDFU each) 1260 Turret Drive • Rockford, IL 61115 USA 888 438 3822 • 815 654 8300 • Fax 815 654 8306 © 1998 Envirovac, Inc. Section 3.0.0 SECTION 3.0 SIZING OF THE EVAC VACUUM COLLECTION SYSTEM 3.5.2 Vacuum riser pipe sizing For vacuum riser pipe sizing refer to the details for installation provided in Section 6.6.2. 3.6 VACUUM CENTRAL SIZING The total number of interface valve drainage fixture units connected to the vacuum central determines its Size. Table 3.3 defines the maximum number of interface valve drainage fixture units that can be collected by an EVAC vacuum central: Table 3.3 Vacuum Central Sizing Vacuum Central Model # Max IVDFUs SM260-30H 80 SM260-30H 80 SM260-30H 80 3.7 INTERFACE VALVE SELECTION Selection of the proper EVAC interface valve is dependent upon the type of fixture that is to be connected to the EVAC Collection System. An interface valve is used in conjunction with an EVAC Buffer or EVAC buffer design. A system sizing chart contained at the end of this section provides a cross-reference between fixture type, interface valve and buffer. 3.8 EVAC BUFFER SELECTION Selection of the proper EVAC Buffer is dependent upon the type of fixture that is to be connected to the EVAC Collection System. An EVAC Buffer is used in conjunction with an EVAC Interface Valve. A system sizing chart contained at the end of this section provides a cross-reference between fixture type, interface valve and buffer. © 1998 Envirovac, Inc. Section 3.0.0 1260 Turret Drive • Rockford, IL 61115 USA 888 438 3822 • 815 654 8300 • Fax 815 654 8306 1260 Turret Drive • Rockford, IL 61115 USA 888 438 3822 • 815 654 8300 • Fax 815 654 8306 5 5 0.5 0.5 0.5 Unit IVDFU Total IVDFU: Total Quantity Extended IVDFU OF THE Vacuum Central Model Number EB-025-SC Hand Sink — Copper Drainage Piping IFV-1-3-R-B IFV-1-1-R-B EB-025-SP Hand Sink — Plastic Drainage Piping IFV-1-1-R-B IFV-1-1-R-B EB-025-R Walk-in Cooler Refrig. Coils, Plastic Pipe IFV-1-1-R-B Interface Valve SIZING Trench Drain for Refrig. Display Case, Plastic Pipe 2” Buffer Detail EB-025-R Buffer or Detail Refrig. Display Cases, Plastic Pipe Fixture or Configuration SYSTEM SIZING CHART EVAC COLLECTION SYSTEM SECTION 3.0 EVAC VACUUM COLLECTION SYSTEM © 1998 Envirovac, Inc. Section 3.0.0 SECTION 4 DESIGN DETAILS This section provides the designer with specific design details for connecting refrigerated cases, fixtures and the vacuum central 4.1 CONNECTION TO REFRIGERATED DISPLAY CASES Please refer to Section 6 for details showing the connection to various types of cases. The details outline the buffer size, buffer location, riser pipe size, and the locations of the valving. 4.3.3 Vacuum central pump exhaust The vacuum pump exhaust is to be a dedicated pipe, minimum 1-1/2". The exhaust pipe is to be metallic using cast iron, steel pipe or copper tubing. Do not use plastic piping as the plastic piping will begin to deform due to the heat generated from the vacuum pumps. Route the exhaust piping through the roof/(side wall) and terminate with a 180O/(90O) turn or an approved rain cap. No traps or sagging in the piping are allowed. 4.3.4 Electrical connection Installation instruction sheets are provided in Section 6 of this manual. 4.2 CONNECTION TO SANITARY FIXTURE Please refer to Section 6 for details showing the connection to various types of sanitary fixtures. 4.3 VACUUM CENTRAL Please refer to Section 6 for the installation instructions of the vacuum central: 4.3.1 Vacuum main connection A. Power Requirements Table 4.1 defines the electrical requirements of the EVAC vacuum central: Table 4.1. Electrical Power Requirements Electrical Power 230V/3PH/60Hz Required Amps 22 460V/3PH/60Hz 11 415V/3PH/50Hz 11 380V/3PH/60Hz 12 The owner must be consulted for connection to emergency back-up power. The vacuum main connection to the inlet of the vacuum central is to be from above. Do not design for a vacuum piping lift into the vacuum central manifold. 4.3.2 Vacuum central discharge The wastewater discharge pipe of the vacuum central is to be connected to a sanitary drain via a visible air gap as required by code, see Figure 1. 1260 Turret Drive • Rockford, IL 61115 USA 888 438 3822 • 815 654 8300 • Fax 815 654 8306 © 1998 Envirovac, Inc. Section 4.0.0 SECTION 4 DESIGN DETAILS B. Alarm Connection to Building Management System Many stores will have a building management system for monitoring the refrigerated display cases and the compressor racks. The EVAC vacuum central control panel may also be connected to the building management system. Consult the manufacturer of the building management system for interfacing the EVAC vacuum central. Air Gap Required. Check code for distance From Vacuum Central Discharge Drain to City Sewer System The following standard alarm conditions are provided by EVAC as dry contacts: 1. Low Vacuum 2. Vacuum Pump Motor Overload 3. Tank Block Level Figure 1. For condensate wastewater only. The maximum rating of the dry contacts is: 1 AMP at 115 VAC or 1 AMP at 24 VDC Please refer to the Installation Instructions provided in Section 6. Additional alarms may be provided as shown on the Product Submittal Sheet contained in Section 6. 3’ Maintenance Clear Space Provide a minimum maintenance clear space around the vacuum central of 3 feet on 3 sides as shown in Figure 2. 3’ Maintenance Clear Space 4.3.5 Maintenance clear space 3’ Maintenance Clear Space Figure 2. © 1998 Envirovac, Inc. Section 4.0.0 Maintenance clear space. 1260 Turret Drive • Rockford, IL 61115 USA 888 438 3822 • 815 654 8300 • Fax 815 654 8306 SECTION 5 PRODUCT CATALOG SHEETS Table of Contents This section contains the product catalog sheets. SECTION 5.1 — VACUUM CENTRALS 5.1.1 SM260-30H 5.1.2 5.1.3 SECTION 5.2 — EVAC VALVES 5.2.1 Interface Valve — Model IFV-1 5.2.2 Check Valve — Model CKV-2 5.2.3 Check Valve — Model CKV-4 SECTION 5.3 — EVAC BUFFERS 5.3.1 Model EB-025 1260 Turret Drive • Rockford, IL 61115 USA 888 438 3822 • 815 654 8300 • Fax 815 654 8306 © 1998 Envirovac, Inc. Section 5.0.0 SM260-30H - VACUUM CENTRAL VACUUM CENTRAL Model No. SM260-30H Model No. SM260-30H LV - DLX Model Number Vacuum Central (2) 60 gallon tanks (3) 2.0 HP pumps Standard Electrical Packages Code q LV q HV q IV1 q IV2 (check box) Voltage Low Voltage — 230 Volts, 3-Phase, 60 Hertz High Voltage — 460 Volts, 3-Phase, 60 Hertz International Voltage — 415 Volts, 3-Phase, 50 Hertz International Voltage — 380 Volts, 3-Phase, 60 Hertz The standard electrical package includes: • • • • • • • Nema 12 Enclosure Vacuum Pump Selector Switches, MAN/OFF/AUTO Power ON Light Low Vacuum Alarm Light Motor Overload Alarm light Block Level Alarm Light Alarm connections to remote monitoring - Low vacuum - Block Level - Motor Overload Optional Electrical Packages Code q DLX (check box) Package Alarm/Run-time Package The alarm/run-time package includes: • Phase monitor alarm • Alarm horn • Hour run meters for the vacuum pumps. APPLICATION OPERATION The Vacuum Central Model SM260-30H is designed to be installed in a supermarket for the purpose of collecting condensate wastewater and/or limited sanitary wastewater. The unit is to be installed in accordance with the installation instructions contained in Section 6 of the EVAC Design Manual for Supermarkets. The vacuum central maintains vacuum pressure throughout the waste piping system using vacuum pumps. The vacuum central collects wastewater from fixtures connected to the system. When wastewater in a collection tank reaches a predetermined level the tank will automatically vent to atmospheric pressure and discharge by gravity. CONSTRUCTION The vacuum central is a packaged unit containing rotaryvane, non-lubricated vacuum pumps with TEFC motors, an electrical control panel designed in accordance with NEC requirements, and plastic collection tanks all mounted on a steel frame. GUIDE SPECIFICATION Furnish and install EVAC Vacuum Central Model . The unit shall be framemounted; factory tested unit equipped with (3) 2.0 HP vacuum pumps and (2) 60-gallon collection tanks. Electrical requirements are as follows: Volts, 3 Phase, SELECTION SUMMARY APPROVED FOR MANUFACTURING Models & Options Company Title Quantity Signature Date Dimensions are subject to manufacturer’s tolerance of ± 1/4" and may change without notice. EVAC assumes no responsibility for use of void or superseded data. 1260 Turret Drive • Rockford, IL 61115 USA 888 438 3822 • 815 654 8300 • Fax 815 654 8306 © 1998 Envirovac, Inc. Section 5.1.1 Hertz. The unit shall have a 2" U.S. pipe waste inlet and 4" U.S. pipe outlet. Dimensions are subject to manufacturer’s tolerance of ± 1/4" and may change without notice. EVAC assumes no responsibility for use of void or superseded data. 1260 Turret Drive • Rockford, IL 61115 USA 888 438 3822 • 815 654 8300 • Fax 815 654 8306 © 1998 Envirovac, Inc. Section 5.1.1 Left Side View Top View 12.88" 327.5mm Vacuum Central System Diagram Vacuum Gauge Electrical Power to Enter Here. See Note #2. Vacuum Pump Exhaust Control Panel 17.45" 443.2mm VP3 15.81" 401.6mm VP2 11.75" 298.5mm 21.50" 546.1mm 25.85" 656.6mm VP1 (2) Collections Tanks 60 Gal. (227L) Each Vacuum Condensate Drain Inlet — 2" PVC Pipe Socket Connection. (2) Vacuum Switches Drain Outlet to Gravity Sewer — 4" PVC Pipe Spigot Connection to Each Tank. In 60 Gal. Tank 1 60 Gal. Tank 2 Front View Vacuum Release Valve (Each Tank) Level Probe (2) Each Tank 10.59"Typ. 269mm 26.71" Typ. 678.4mm 11.75" 298.5mm Out Tank 2 Tank 1 Vacuum Condensate Drain Inlet — 2" PVC Pipe Socket Connection. Right Side View 80.60" Max 2047.2mm Notes WEIGHTS: (Approximate) Dry — 550 lb. (249 kg.) Wet — 900 lb. (408 kg.) ELECTRICAL REQUIREMENTS 460 VAC, 3Ø, 60 Hz, 11 Amps 230 VAC, 3Ø, 60 Hz, 22 Amps 415 VAC, 3Ø, 50 Hz, 11 Amps 380 VAC, 3Ø, 60 Hz, 12 Amps Vacuum Pump Exhaust — 1" Copper Solder Joint Connection. (3) Vacuum Pumps w/ 2HP Motors VP3 68.20" Max 1732.3mm VP2 85.00" Max 2159mm Qty. 4 3.00" Sq. 76.2mm Mounting Foot Print 58.81" 1341.4mm VP1 20.50" 520.7mm Qty. 4 Ø 0.50" (12.7 mm) Mtg. Holes 42.00" 1066.8mm 38.46" Max. 976.9mm 45.00" 1143mm 23.50" 596.9mm 1.50" 38.1mm VACUUM INTERFACE VALVE Model No. IFV-1 PURPOSE OPERATION The Interface Valve, Model No. IFV-1, is designed to transfer wastewater from plumbing fixtures, refrigerated display cases, or refrigeration coils to the vacuum drainage piping. The valve has a rated capacity of 20 IVDFU’s and is to be used in accordance with the installation details contained in Section 6 of the EVAC Design Manual for Supermarkets. The Interface Valve is used in conjunction with an EVAC Buffer. Wastewater from a plumbing fixture, refrigerated display cases, or evaporator unit enters a section of pipe or a vessel called a "buffer". The activator senses the level of wastewater in the buffer, and sends a signal to open the discharge valve allowing the wastewater to enter the vacuum drainage piping. CONSTRUCTION GUIDE SPECIFICATION The Interface Valve is non-electric and uses the vacuum pressure contained in the downstream vacuum piping to operate. The Interface Valve is a kit consisting of the following: Furnish and install EVAC Interface Valve Model . The valve shall operate pneumatically using the vacuum pressure available in the system and shall be non-electric. 1. Discharge valve with an ABS housing and EPDM diaphragms. 2. Activator valve with an ABS housing and PVC adapters. 3. EPDM or Neoprene tubing. 4. Stainless steel activator mounting bracket. 5. ABS mini check valve. Dimensions are subject to manufacturer’s tolerance of ± 1/4" and may change without notice. EVAC assumes no responsibility for use of void or superseded data. 1260 Turret Drive • Rockford, IL 61115 USA 888 438 3822 • 815 654 8300 • Fax 815 654 8306 © 1998 Envirovac, Inc. Section 5.2.1 VACUUM INTERFACE VALVE Model No. IFV-1 IFV-1 Model Number Pipe Size - 4 Tubing (check box) Code Inlet Outlet Male Pipe for plastic piping 1-1/4" Body includes: discharge valve, activator w/mounting bracket, and mini check valve. q 1 q 2 1-1/2" 2" - R - R Valve Timing (check box) (check box) Code Type Code Timing q R EPDM or Neoprene q R q B q W Red-Blue Timing Jets Blue-Blue Timing Jets White-Blue Timing Jets 1-1/2" 2" Copper Tube, Shielded Coupling q 3 q 4 1-1/2" 2" 1-1/2" 2" Activator 1/4" ID Tubing Ø 0.281" Clearance Holes 2 Places (VACUUM) ) VE AL (V 1/4" ID Tubing Mini Check Valve Activator Mounting Bracket Inlet Outlet 1/4" ID Tubing (SENSING) Discharge Valve From Buffer SELECTION SUMMARY APPROVED FOR MANUFACTURING Models & Options Company Title Quantity Signature Date Dimensions are subject to manufacturer’s tolerance of ± 1/4" and may change without notice. EVAC assumes no responsibility for use of void or superseded data. © 1998 Envirovac, Inc. Section 5.2.1 1260 Turret Drive • Rockford, IL 61115 USA 888 438 3822 • 815 654 8300 • Fax 815 654 8306 VACUUM CHECK VALVE Model No. CKV-2 APPLICATION The Vacuum Check Valve, Model No. CKV-2, is designed to seal and prevent back-flow in a vacuum waste system. The valve is designed for use in a 2" vacuum waste pipe. GUIDE SPECIFICATION Furnish and install Evac Vacuum Check Valve Model . The check valve shall be a full-port, flapper-type, rated for vacuum service to 28 in-Hg. CONSTRUCTION The check valve has a PVC body and a Neoprene flapper. OPERATION The check valve is a full-port, flapper type. The valve is installed horizontally in a vacuum waste line at the top of a riser when a discharge valve is mounted low and at the point in which a branch vacuum line enters into a main. The check valve is used to prevent back-flow in a vacuum waste system. Dimensions are subject to manufacturer’s tolerance of ± 1/4" and may change without notice. EVAC assumes no responsibility for use of void or superseded data. 1260 Turret Drive • Rockford, IL 61115 USA 888 438 3822 • 815 654 8300 • Fax 815 654 8306 © 1998 Envirovac, Inc. Section 5.2.2 VACUUM CHECK VALVE Model No. CKV-2 CKV-2 - Model Number 2" Body 4 Pipe Size - S Optional Coupling (check box) Code Inlet Outlet Male Pipe for plastic piping q q 1 2 1-1/2" 2" Code q q 2" 2" S N (check box) Coupling Type Shielded Non-shielded Copper Tube, Shielded Coupling q 3 2" 2" Metric, Socket Ends q 4 63mm 63mm Check Valve Sheilded or Non-shielded Coupling Sheilded or Non-shielded Coupling Inlet Outlet 6.80" 173mm 12.40" 315mm SELECTION SUMMARY APPROVED FOR MANUFACTURING Models & Options Company Title Quantity Signature Date Dimensions are subject to manufacturer’s tolerance of ± 1/4" and may change without notice. EVAC assumes no responsibility for use of void or superseded data. © 1998 Envirovac, Inc. Section 5.2.2 1260 Turret Drive • Rockford, IL 61115 USA 888 438 3822 • 815 654 8300 • Fax 815 654 8306 BUFFER Model No. EB-025 PURPOSE OPERATION The EVAC Buffer is designed to receive wastewater from hand sinks and refrigerated display cases. It is also sized to handle intermittent heavy flow that is generated during a wash-down of a refrigerated display case. The EVAC buffer is to be installed in accordance with the installation instructions contained in Section 6 of the EVAC Design Manual for Supermarkets. Wastewater from a hand sink or refrigerated display case enters the EVAC Buffer. The wastewater begins to fill the EVAC Buffer creating head pressure. The head pressure generated inside the buffer box is sensed by the interface valve’s activator. The interface valve’s cycle begins when the amount of water reaches a preset level. At this level, the wastewater inside the EVAC Buffer will be evacuated to the vacuum drainage piping. CONSTRUCTION The EVAC Buffer is constructed of ABS material with an 1-1/2" female socket inlet and 1-1/2" male spigot outlet. GUIDE SPECIFICATION Furnish and install EVAC Buffer Model EB-025. The Buffer shall have an 1-1/2" US Pipe female-socket inlet and 1-1/2" US Pipe outlet. Dimensions are subject to manufacturer’s tolerance of ± 1/4" and may change without notice. EVAC assumes no responsibility for use of void or superseded data. 1260 Turret Drive • Rockford, IL 61115 USA 888 438 3822 • 815 654 8300 • Fax 815 654 8306 © 1998 Envirovac, Inc. Section 5.3.1 BUFFER Model No. EB-025 EB-025 - Model Number 1-1/2" Female-socket Inlet 1-1/2" Male Outlet Sensing Connection 1.05" 26.7mm R Buffer Application Code q q q R SP SC (check box) Application Refrigerated display cases or refrigeration coils Sink — Plastic vacuum drainage piping Sink — Copper vacuum drainage piping 9.30" 236mm 11.68" 296.7mm 4.30" 109mm 1-1/2" Male Outlet 1-1/2" Female Inlet 4.00" 100mm 1.91" 48.5mm 1.86" 47.2mm SELECTION SUMMARY APPROVED FOR MANUFACTURING Models & Options Company Title Quantity Signature Date Dimensions are subject to manufacturer’s tolerance of ± 1/4" and may change without notice. EVAC assumes no responsibility for use of void or superseded data. © 1998 Envirovac, Inc. Section 5.3.1 1260 Turret Drive • Rockford, IL 61115 USA 888 438 3822 • 815 654 8300 • Fax 815 654 8306 SECTION 6 INSTALLATION DETAILS Table of Contents This section provides specific installation details that are available on diskette from EVAC. These details are to be inserted directly onto the construction drawings for a specific supermarket. SECTION 6.1 — INSTALLATION INSTRUCTIONS FOR REFRIGERATED DISPLAY CASES 6.1.1 Bulk Produce Case, High Profile 6.1.2 Bulk Produce Case, High Profile. 6.1.3 Island Produce Case Also used for Salad Bars and Island Deli or Bakery Cases 6.1.4 Frozen Food Island Case, Low Profile 6.1.5 Frozen Food and Ice Cream Case, Low Profile 6.1.6 Dairy/Delicatessen, Low Profile 6.1.7 Meat Case, High Profile 6.1.8 Meat/Delicatessen, Low Profile 6.1.9 Meat Case, High Profile SECTION 6.2 — INSTALLATION INSTRUCTIONS FOR SANITARY 6.2.1 Hand Sink with P-trap Installation 6.2.2 Hand Sink without P-trap Installation OR GRAY WATER FIXTURES SECTION 6.3 — INSTALLATION INSTRUCTIONS FOR VACUUM CENTRALS 6.3.1 SM260-30H 6.3.2 6.3.3 SECTION 6.4 — INSTALLATION INSTRUCTIONS FOR INTERFACE VALVES 6.4.1 For Refrigerated Display Cases — Interface valve at top of riser 6.4.2 For Refrigerated Display Cases — Interface valve in riser w/o check valve 6.4.3 For Refrigerated Display Cases — Interface valve in riser with check valve SECTION 6.5 — COMPONENT INSTALLATION INSTRUCTIONS 6.5.1 EVAC Buffer, EB-025 6.5.2 EVAC Check Valve, CKV-2 SECTION 6.6 — OTHER INSTALLATION INSTRUCTIONS 6.6.1 Trench Drainage to EVAC Buffer Design 6.6.2 Vacuum Drainage Piping 1260 Turret Drive • Rockford, IL 61115 USA 888 438 3822 • 815 654 8300 • Fax 815 654 8306 © 1998 Envirovac, Inc. Section 6.0.0 INSTALLATION DETAILS BULK PRODUCE CASE, HIGH PROFILE Hussmann P2, P4 Series or Equivalent Activator 1-1/2" Riser From other cases Air Intake Tee Buffer DETAILS UNDER CASE CLEARANCE: 6" or greater. BUFFER MODEL NO.: EB-025-R BUFFER LOCATION: Under case. # CASES / BUFFER: Up to 4. INTERFACE VALVE MODEL NO: IFV-1-1-R-B for plastic piping DISCHARGE VALVE LOCATION: Top of riser or in riser. ACTUATOR LOCATION: Top of case. RISER LOCATION: End of lineup or behind case. 1260 Turret Drive • Rockford, IL 61115 USA 888 438 3822 • 815 654 8300 • Fax 815 654 8306 © 1998 Envirovac, Inc. Section 6.1.1 INSTALLATION DETAILS BULK PRODUCE CASE, HIGH PROFILE Hussmann P1, Series or Equivalent Activator 1-1/2" Riser From other cases Air Intake Tee Buffer DETAILS UNDER CASE CLEARANCE: 6" or greater. BUFFER MODEL NO.: EB-025-R BUFFER LOCATION: Under case, minimal space contraints. # CASES / BUFFER: Up to 4. INTERFACE VALVE MODEL NO: IFV-1-1-R-B for plastic pipe DISCHARGE VALVE LOCATION: Top of riser. ACTUATOR LOCATION: Top of case. RISER LOCATION: Back of case. 1260 Turret Drive • Rockford, IL 61115 USA 888 438 3822 • 815 654 8300 • Fax 815 654 8306 © 1998 Envirovac, Inc. Section 6.1.2 INSTALLATION DETAILS PRODUCE ISLAND Hussmann PWE, PW Series or Equivalent Activator From other cases 1-1/2" Riser Air Intake Tee Buffer DETAILS UNDER CASE CLEARANCE: 6" or greater. BUFFER MODEL NO.: EB-025-R BUFFER LOCATION: Under case, minimal space contraints. # CASES / BUFFER: Up to 4. INTERFACE VALVE MODEL NO: IFV-1-1-R-B for plastic piping DISCHARGE VALVE LOCATION: Top of riser. ACTUATOR LOCATION: Top of case, partition in fabricated accessible cover, or in partition with accessible panel. RISER LOCATION: Through partition. 1260 Turret Drive • Rockford, IL 61115 USA 888 438 3822 • 815 654 8300 • Fax 815 654 8306 © 1998 Envirovac, Inc. Section 6.1.3 INSTALLATION DETAILS FROZEN FOOD ISLAND CASE, LOW PROFILE Hussmann L Series or Equivalent 1-1/2" Riser From other cases Activator Buffer Air Intake Tee Partition DETAILS UNDER CASE CLEARANCE: 6" or less. BUFFER MODEL NO.: EB-025-R BUFFER LOCATION: Front, behind splashguard. # CASES / BUFFER: 2 or 4 (if 2 island cases and 2 end cases are piped or have common drain line). INTERFACE VALVE MODEL NO: IFV-1-1-R-B for plastic piping DISCHARGE VALVE LOCATION: Top of riser. ACTUATOR LOCATION: Top of case, partition in fabricated accessible cover, or in partition with accessible panel. RISER LOCATION: Through partition. 1260 Turret Drive • Rockford, IL 61115 USA 888 438 3822 • 815 654 8300 • Fax 815 654 8306 © 1998 Envirovac, Inc. Section 6.1.4 INSTALLATION DETAILS FROZEN FOOD & ICE CREAM CASE, LOW PROFILE Hussmann RL Series or Equivalent Discharge Valve 1-1/2" Riser Activator From other cases Air Intake Tee Buffer DETAILS UNDER CASE CLEARANCE: 6" or less. BUFFER MODEL NO.: EB-025-R BUFFER LOCATION: Front, behind splashguard or at back of case. # CASES / BUFFER: 2 INTERFACE VALVE MODEL NO: IFV-1-1-R-B for plastic piping DISCHARGE VALVE LOCATION: Top of case. ACTUATOR LOCATION: Top of case. RISER LOCATION: Back of case. 1260 Turret Drive • Rockford, IL 61115 USA 888 438 3822 • 815 654 8300 • Fax 815 654 8306 © 1998 Envirovac, Inc. Section 6.1.5 INSTALLATION DETAILS DAIRY/DELICATESSEN CASE, LOW PROFILE Hussmann D5, D6 Series or Equivalent 1-1/2" Riser Activator Buffer From other cases Air Intake Tee DETAILS UNDER CASE CLEARANCE: 6" or less. BUFFER MODEL NO.: EB-025-R BUFFER LOCATION: Front, behind splashguard or back of case. # CASES / BUFFER: 2 INTERFACE VALVE MODEL NO: IFV-1-1-R-B for plastic piping DISCHARGE VALVE LOCATION: Top of riser. ACTUATOR LOCATION: Top of case. RISER LOCATION: Back of case. 1260 Turret Drive • Rockford, IL 61115 USA 888 438 3822 • 815 654 8300 • Fax 815 654 8306 © 1998 Envirovac, Inc. Section 6.1.6 INSTALLATION DETAILS MEAT CASE, HIGH PROFILE Hussmann M1, M1G Series or Equivalent Activator 1-1/2" Riser From other cases Air Intake Tee Buffer DETAILS UNDER CASE CLEARANCE: 6" or greater. BUFFER MODEL NO.: EB-025-R BUFFER LOCATION: Under case. # CASES / BUFFER: Up to 4. INTERFACE VALVE MODEL NO: IFV-1-1-R-B for plastic piping DISCHARGE VALVE LOCATION: Top of riser. ACTUATOR LOCATION: Top of case in fabricated accessible cover or above dropped ceiling. RISER LOCATION: At end of lineup or behind case. 1260 Turret Drive • Rockford, IL 61115 USA 888 438 3822 • 815 654 8300 • Fax 815 654 8306 © 1998 Envirovac, Inc. Section 6.1.7 INSTALLATION DETAILS MEAT/DELICATESSEN CASE, LOW PROFILE Hussmann M2, M2G, C2 Series or Equivalent Activator 1-1/2" Riser From other cases Air Intake Tee Buffer DETAILS UNDER CASE CLEARANCE: 6" or less. BUFFER MODEL NO.: EB-025-R BUFFER LOCATION: Under case. # CASES / BUFFER: 2 INTERFACE VALVE MODEL NO: IFV-1-1-R-B for plastic piping DISCHARGE VALVE LOCATION: Top of riser. ACTUATOR LOCATION: Top of case. RISER LOCATION: At end of lineup or behind case. 1260 Turret Drive • Rockford, IL 61115 USA 888 438 3822 • 815 654 8300 • Fax 815 654 8306 © 1998 Envirovac, Inc. Section 6.1.8 INSTALLATION DETAILS MEAT CASE, HIGH PROFILE Hussmann M4, M4G, M5, M5G, M3, M3G Series or Equivalent Activator 1-1/2" Riser From other cases Air Intake Tee Buffer DETAILS UNDER CASE CLEARANCE: 6" or greater. BUFFER MODEL NO.: EB-025-R BUFFER LOCATION: Front, behind splashguard or back of case. # CASES / BUFFER: Up to 4. INTERFACE VALVE MODEL NO: IFV-1-1-R-B DISCHARGE VALVE LOCATION: Top of riser. ACTUATOR LOCATION: Top of case. RISER LOCATION: At end of lineup or behind case. 1260 Turret Drive • Rockford, IL 61115 USA 888 438 3822 • 815 654 8300 • Fax 815 654 8306 • www.evac.com © 1998 Envirovac, Inc. Section 6.1.9 INSTALLATION INSTRUCTIONS GENERAL SINK WITH EVAC Interface Valve, IFV-1 and EVAC Buffer, EB-025 SINK PIPING — With a sink P-trap 1. Pipe the sink using conventional gravity methods providing a sanitary vent through the roof. To Vacuum Central 2. Route the piping to the EVAC Buffer, EB-025, that is equipped with an air intake adapter. 3. Install an air intake pipe from the EVAC Buffer and connect the air intake to the sanitary vent for the sink. Check Valve 2" Pipe 6’ Max. Brace Vent to Roof 3’ Max. Activator 1-1/2" Riser 22’ Max. (SENSING) 6’ Min. (Typical) Discharge Valve (VACUUM) (VALVE) (Typical) 1/4" ID Tubing Supplied by EVAC 7’ Min. 3’ Max. 1-1/2" Pipe Figure 1. (Typical) Buffer Manual Operator Vacuum Supply Sensing Connection Inlet 45O To Buffer Sensor Figure 2. Pipe roll at wye. Figure 3. Activator. To Discharge Valve Figure 4. Activator. Figure 5. Buffer—Inlet End. Dimensions are subject to manufacturer’s tolerance of ± 1/4" and may change without notice. EVAC assumes no responsibility for use of void or superseded data. 1260 Turret Drive • Rockford, IL 61115 USA 888 438 3822 • 815 654 8300 • Fax 815 654 8306 © 1998 Envirovac, Inc. Section 6.2.1 INSTALLATION INSTRUCTIONS GENERAL SINK WITH EVAC Interface Valve, IFV-1 and EVAC Buffer, EB-025 PURPOSE The EVAC Interface Valve in conjunction with an EVAC Buffer are designed to transport wastewater from a plumbing fixture or refrigerated display case into an EVAC Collection System. INSTALLATION OF EVAC INTERFACE VALVE, IFV-01 1. Install a 45O-wye fitting from the vacuum branch or main in order to install the check valve. The wye fitting may be rolled a maximum of 45O from vertical as shown in Figure 2. Allow for the maximum riser height of 22 feet and a maximum distance of 3 feet from the riser to the wye fitting dropping into the main/branch. 2. Install the EVAC Check Valve, CKV-2, between the riser and the wye fitting that drops in to the main. The check valve has a minor offset of 1/16" that must be accounted for during installation. 3. Install the discharge valve in the riser pipe a minimum of 7 feet from the floor. The discharge valve is equipped with male pipe ends for gluing directly into plastic piping. For copper tubing — use a shielded coupling that provides a smooth transition from pipe to tubing. 4. Install a pipe brace on the branch piping or main within 1 foot of the 45O-wye fitting. Also, install a pipe brace between the riser pipe and the check valve, but within 6 inches of the riser pipe itself. 5. Install the 1-1/2" riser pipe allowing for no offsets. The riser must remain vertical. 6. Install the activator in an accessible location for future maintenance. 7. Connect the EVAC supplied vacuum tubing as shown in Figures 1, 3, 4, and 5. The activator ports are labeled for "sensor", "vacuum", and "discharge". Attach the vacuum tubing to the riser piping using wire ties. The tubing bending radius are to be a minimum of 3" inches to prevent kinking. Do not over-tighten the wire ties, or the tubing may kink or collapse. 8. Install the mini check valve in the vacuum source line of the discharge valve, as shown in Figure 1. Please note the proper direction of the mini check valve. Failure to install the mini check valve will result in damage to the activator that is not covered by EVAC’s warranty. 9. Do not paint IFV-01 components. INSTALLATION EB-025 OF EVAC BUFFER, 1. Install 1-1/2" drainage piping from a refrigerated display case or hand sink at a slope of 1/8" per foot to the EVAC Buffer. Required Drainage Slope 1/8" 1’-0" 2. Place the EVAC Buffer directly on the floor with the direction arrow pointing to the vacuum drainage riser. 3. Prior to the EVAC Buffer inlet connection install an air intake tee fitting, as shown in Figure 1. 4. Use a 1-1/2", 45O-street elbow to connect the 1-1/2" female socket inlet of the EVAC Buffer to the sink drain line. 5. Use a 1-1/2", 45O-elbow to connect to the 1-1/2" male spigot outlet of the EVAC Buffer to the vacuum drainage riser. 6. Route the piping from the EVAC Buffer outlet to the location of the vacuum drainage riser. Maximum length from the buffer to the riser is 3 feet. 7. In order to transition to or turn the riser use (2) 45O elbows or a 90O long sweep radius elbow. 8. Provide bracing within 1 foot of the EVAC Buffer and within 1 foot of the 90O turn at the vacuum riser in accordance with the Installation Instructions for Vacuum Drainage Piping found in Section 6.6.2. Dimensions are subject to manufacturer’s tolerance of ± 1/4" and may change without notice. EVAC assumes no responsibility for use of void or superseded data. © 1998 Envirovac, Inc. Section 6.2.1 1260 Turret Drive • Rockford, IL 61115 USA 888 438 3822 • 815 654 8300 • Fax 815 654 8306 INSTALLATION INSTRUCTIONS GENERAL SINK WITH EVAC Interface Valve, IFV-1 and EVAC Buffer, EB-025 SINK PIPING — Without a sink P-trap 1. Pipe the sink directly to the EVAC Buffer providing no P-Trap. 2. Install an air intake pipe from the EVAC Buffer and terminate vertically 6 inches above the overflow rim of the sink. To Vacuum Central Check Valve 6’ Max. 3’ Max. 2" Pipe Brace Activator (Typical) Discharge Valve U M ) 6" Min. (Typical) (V AC U Air Intake 1-1/2" Riser 22’ Max. (SENSING) (VALVE) 1/4" ID Tubing Supplied by EVAC 7’ Min. 3’ Max. 1-1/2" Pipe Figure 1. (Typical) Buffer Manual Operator Vacuum Supply Sensing Connection Inlet 45O To Buffer Sensor Figure 2. Pipe roll at wye. Figure 3. Activator. To Discharge Valve Figure 4. Activator. Figure 5. Buffer—Inlet End. Dimensions are subject to manufacturer’s tolerance of ± 1/4" and may change without notice. EVAC assumes no responsibility for use of void or superseded data. 1260 Turret Drive • Rockford, IL 61115 USA 888 438 3822 • 815 654 8300 • Fax 815 654 8306 © 1998 Envirovac, Inc. Section 6.2.2 INSTALLATION INSTRUCTIONS GENERAL SINK WITH EVAC Interface Valve, IFV-1 and EVAC Buffer, EB-025 PURPOSE The EVAC Interface Valve in conjunction with an EVAC Buffer are designed to transport wastewater from a plumbing fixture or refrigerated display case into an EVAC Collection System. INSTALLATION OF EVAC INTERFACE VALVE, IFV-01 1. Install a 45O-wye fitting from the vacuum branch or main in order to install the check valve. The wye fitting may be rolled a maximum of 45O from vertical as shown in Figure 2. Allow for the maximum riser height of 22 feet and a maximum distance of 3 feet from the riser to the wye fitting dropping into the main/branch. 8. Install the mini check valve in the vacuum source line of the discharge valve, as shown in Figure 1. Please note the proper direction of the mini check valve. Failure to install the mini check valve will result in damage to the activator that is not covered by EVAC’s warranty. 9. Do not paint IFV-01 components. INSTALLATION EB-025 OF EVAC BUFFER, 1. Install 1-1/2" drainage piping from a refrigerated display case or hand sink at a slope of 1/8" per foot to the EVAC Buffer. Required Drainage Slope 1/8" 2. Install the EVAC Check Valve, CKV-2, between the riser and the wye fitting that drops into the main. The check valve has a minor offset of 1/16" that must be accounted for during installation. 3. Install the discharge valve in the riser pipe a minimum of 7 feet from the floor. The discharge valve is equipped with male pipe ends for gluing directly into plastic piping. For copper tubing — use a shielded coupling that provides a smooth transition from pipe to tubing. 4. Install a pipe brace on the branch piping or main within 1 foot of the 45O-wye fitting. Also, install a pipe brace between the riser pipe and the check valve, but within 6 inches of the riser pipe itself. 5. Install the 1-1/2" riser pipe allowing for no offsets. The riser must remain vertical. 6. Install the activator in an accessible location for future maintenance. 7. Connect the EVAC supplied vacuum tubing as shown in Figures 1, 3, 4, and 5. The activator ports are labeled for "sensor", "vacuum", and "discharge". Attach the vacuum tubing to the riser piping using wire ties. The tubing bending radius are to be a minimum of 3" inches to prevent kinking. Do not over-tighten the wire ties, or the tubing may kink or collapse. 1’-0" 2. Place the EVAC Buffer directly on the floor with the direction arrow pointing to the vacuum drainage riser. 3. Prior to the EVAC Buffer inlet connection install an air intake tee fitting, as shown in Figure 1. 4. Use a 1-1/2", 45O-street elbow to connect the 1-1/2" female socket inlet of the EVAC Buffer to the sink drain line. 5. Use a 1-1/2", 45O-elbow to connect to the 1-1/2" male spigot outlet of the EVAC Buffer to the vacuum drainage riser. 6. Route the piping from the EVAC Buffer outlet to the location of the vacuum drainage riser. Maximum length from the buffer to the riser is 3 feet. 7. In order to transition to or turn the riser use (2) 45O elbows or a 90O long sweep radius elbow. 8. Provide bracing within 1 foot of the EVAC Buffer and within 1 foot of the 90O turn at the vacuum riser in accordance with the Installation Instructions for Vacuum Drainage Piping found in Section 6.6.2. Dimensions are subject to manufacturer’s tolerance of ± 1/4" and may change without notice. EVAC assumes no responsibility for use of void or superseded data. © 1998 Envirovac, Inc. Section 6.2.2 1260 Turret Drive • Rockford, IL 61115 USA 888 438 3822 • 815 654 8300 • Fax 815 654 8306 INSTALLATION DETAILS INSTALLATION DETAILS VACUUM CENTRAL VACUUM CENTRAL SM260-30H SM260-30H PC1 CB1 TB2 See Detail 2 W R PL AL4 R R R AL1 AL2 AL3 OFF ON T1 AH PWR ETM 1 ETM 2 ETM 3 See Detail 1 Detail 1. Motor Trip Alarm High Level Block Alarm Detail 2. 29 1/4"-20 Threaded Ground Terminal on Panel 30 14# AWG Stranded Wire Minimum 10# AWG Stranded Wire Minimum for 230V 31 32 PURPOSE Required Amps 22 L1 L2 L3 DS 460V/3PH/60Hz 11 415V/3PH/50Hz 11 380V/3PH/60Hz 12 G G The Vacuum Central Model SM260-30H is designed to be installed in supermarkets for the purpose of collecting condensate wastewater and/or limited sanitary wastewater. INSTALLATION 74.46" 1891.3mm 3’ Maintenance Clear Space Electrical Power 230V/3PH/60Hz 3’ Maintenance Clear Space 3-Phase Abnormal Alarm 28 ØB ØC Low Vacuum Alarm ØA Common MECHANICAL 1. Install the vacuum central in an accessible location with a maintenance clear space of 3 feet from all sides of the unit as shown in Figure 1. Unpowered Contacts for Remote Alarm Switching Capacity Max: Min: 3’ Maintenance Clear Space 1 Amp @115 VAC (P.F. 1.0) 1 Amp @ 24 VDC 10 mA @ 5VDC 140.20" 3561.1mm Figure 1. © 1998 Envirovac, Inc. Section 6.3.1 1260 Turret Drive • Rockford, IL 61115 USA 888 438 3822 • 815 654 8300 • Fax 815 654 8306 1260 Turret Drive • Rockford, IL 61115 USA 888 438 3822 • 815 654 8300 • Fax 815 654 8306 Maintenance clear space. © 1998 Envirovac, Inc. Section 6.3.1 Left Side View INSTALLATION DETAILS Top View 12.88" 327.5mm VACUUM CENTRAL Vacuum Central System Diagram SM260-30H Vacuum Gauge Vacuum Pump Exhaust 2. Secure the unit to the floor using the ½" mounting holes located on the feet of the vacuum central frame. 3. Connect the vacuum drainage piping for the store to the inlet of the vacuum central. The inlet is a 2" PVC female socket connection. a. b. c. The vacuum drainage piping from the store must enter the vacuum central from above. No risers are allowed before entering the vacuum central. For 3" vacuum drainage piping reduce to 2" at the inlet connection of the vacuum central using normal plumbing practices. Brace the vacuum drainage piping at the inlet of the vacuum central in accordance with the Vacuum Drainage Piping Installation Instructions found in Section 6.6.2. Air Gap Required. Check code for distance. Figure 1. 4. Install a single 4" gravity line to route the outlet of each tank for connection to the gravity drainage piping using the following guidelines: a. b. ELECTRICAL POWER Drain to City Sewer System 1. Provide electrical power as detailed below: Electrical Power 230V/3PH/60Hz Required Amps 22 460V/3PH/60Hz 11 415V/3PH/50Hz 11 380V/3PH/60Hz 12 2. Connect (3)-wire electrical power cable with ground and connect to the DS location in the vacuum central electrical control panel as shown in Detail 1. From Vacuum Central Discharge OPTONAL REMOTE ALARM CONNECTION 1. Dry contacts are provided in the electrical control panel for the following alarms: a. Low Vacuum b. Vacuum Pump Motor Overload c. Tank Block Level d. Abnormal 3-Phase Power, (when purchased) Drain to City Sewer System Figure 3. For sanitary wastewater only. 2. Connect (2)-wire electrical cable to the terminal block labeled TB-2 inside the electrical control panel for the purpose of remote monitoring as shown in Detail 2. The maximum rating of the dry contacts is 1 Amp @ 115 VAC or 24 VDC. 17.45" 443.2mm 15.81" 401.6mm VP2 11.75" 298.5mm 21.50" 546.1mm 25.85" 656.6mm VP1 (2) Collections Tanks 60 Gal. (227L) Each Vacuum Central is Collecting Sanitary Wastewater: Hard pipe the vacuum central discharge to the gravity drainage piping as shown in Figure 3. From Vacuum Central Discharge For condensate wastewater only. Control Panel VP3 Vacuum Central is Collecting Condensate Wastewater Only: Route the piping to an approved receptor. Provide an air gap as required by code as shown in Figure 2. 5. Increase the 1" exhaust for the vacuum pump(s) to 1-1/2". The exhuast pipe is to be metallic using cast iron, steel pipe or copper tubing. Do not use plastic piping as the plastic piping will begin to deform due to the heat generated from the vacuum pumps. Route the exhaust piping through the roof/ (side wall) and terminate with a 180O/(90O) turn or an approved rain cap. No traps or sagging in the pipe are allowed. Electrical Power to Enter Here. See Note #2. Vacuum Condensate Drain Inlet — 2" PVC Pipe Socket Connection. (2) Vacuum Switches In 60 Gal. Tank 1 Drain Outlet to Gravity Sewer — 4" PVC Pipe Spigot Connection to Each Tank. 60 Gal. Tank 2 Front View Vacuum Release Valve (Each Tank) Level Probe (2) Each Tank 10.59" Typ. 269mm Out 26.71" Typ. 678.4mm 11.75" 298.5mm Tank 2 Tank 1 Vacuum Condensate Drain Inlet — 2" PVC Pipe Socket Connection. Right Side View 80.60" Max 2047.2mm Notes WEIGHTS: (Approximate) Dry — 550 lb. (249 kg.) Wet — 900 lb. (408 kg.) Vacuum Pump Exhaust — 1" Copper Solder Joint Connection. ELECTRICAL REQUIREMENTS 460 VAC, 3Ø, 60 Hz, 11 Amps 230 VAC, 3Ø, 60 Hz, 22 Amps 415 VAC, 3Ø, 50 Hz, 11 Amps 380 VAC, 3Ø, 60 Hz, 12 Amps (3) Vacuum Pumps w/ 2HP Motors VP3 68.20" Max 1732.3mm VP2 85.00" Max 2159mm Qty. 4 3.00" Sq. 76.2mm Mounting Foot Print 58.81" 1341.4mm VP1 20.50" 520.7mm Qty. 4 Ø 0.50" (12.7 mm) Mtg. Holes 42.00" 1066.8mm 38.46" Max. 976.9mm 45.00" 1143mm 23.50" 596.9mm 1.50" 38.1mm INSTALLATION INSTRUCTIONS REFRIGERATED CASE WITH EVAC Interface Valve, IFV-1 and EVAC Buffer, EB-025 OPTION 1 — Discharge valve at top of lift To Vacuum Central 6’ Max. 3’ Max. 2" Pipe Brace Activator (Typical) (Typical) (VACUUM) Discharge Valve 1-1/2" Riser (VALVE) 22’ Max. (SENSING) 1/4" ID Tubing Supplied by EVAC Bottom of Case 3’ Max. Air Intake Buffer Figure 1. 1-1/2" Pipe Manual Operator (Typical) Sensing Connection Vacuum Supply Inlet 45O To Buffer Sensor Figure 2. Pipe roll at wye. Figure 3. Activator. To Discharge Valve Figure 4. Activator. Figure 5. Buffer—Inlet End. Dimensions are subject to manufacturer’s tolerance of ± 1/4" and may change without notice. EVAC assumes no responsibility for use of void or superseded data. 1260 Turret Drive • Rockford, IL 61115 USA 888 438 3822 • 815 654 8300 • Fax 815 654 8306 © 1998 Envirovac, Inc. Section 6.4.1 INSTALLATION INSTRUCTIONS REFRIGERATED CASE WITH EVAC Interface Valve, IFV-1 and EVAC Buffer, EB-025 OPTION 1 — Discharge valve at top of lift PURPOSE The EVAC Interface Valve in conjunction with an EVAC Buffer are designed to transport wastewater from a plumbing fixture or refrigerated display case into an EVAC Collection System. INSTALLATION OF EVAC INTERFACE VALVE, IFV-01 1. Install a 45O-wye fitting in the vacuum branch or main. This allows for installation of the discharge valve. The wye fitting may be rolled a maximum of 45O from vertical as shown in Figure 2. Allow for the maximum riser height of 20 feet. result in damage to the activator that is not covered by EVAC’s warranty. 8. Do not paint IFV-01 components. INSTALLATION EB-025 OF EVAC BUFFER, 1. Install 1-1/2" drainage piping from a refrigerated display case or hand sink at a slope of 1/8" per foot to the EVAC Buffer. Required Drainage Slope 1/8" 1’-0" 2. Install the discharge valve at the top of the riser pipe in the horizontal position within 3 feet of the riser pipe. The discharge valve is equipped with male pipe ends for gluing directly into plastic piping. For copper tubing — use a shielded coupling that provides a smooth transition from pipe to tubing. 3. Install a pipe brace on the branch piping or main within 1 foot of the 45O-wye fitting. Also, install a pipe brace between the riser and the discharge valve, but within 6 inches of the riser pipe itself. 4. Install the 1-1/2" riser pipe allowing for no offsets. The riser must remain vertical. 5. Install the activator in an accessible location for future maintenance. 6. Connect the EVAC supplied vacuum tubing as shown in Figures 1, 3, 4, and 5. The activator ports are labeled for "sensor", "vacuum", and "discharge". Attach the vacuum tubing to the riser piping using wire ties. The tubing bending radius are to be a minimum of 3" inches to prevent kinking. Do not over-tighten the wire ties, or the tubing may kink or collapse. 7. Install the mini check valve in the vacuum source line of the discharge valve, as shown in Figure 1. Please note the proper direction of the mini check valve. Failure to install the mini check valve will 2. Place the EVAC Buffer directly on the floor with the direction arrow pointing to the vacuum drainage riser. 3. Prior to the EVAC Buffer inlet connection install an air intake tee fitting, as shown in Figure 1. 4. Use a 1-1/2", 45O-street elbow to connect the 1-1/2" female socket inlet of the EVAC Buffer to the case drain line. 5. Use a 1-1/2", 45O-elbow to connect to the 1-1/2" male spigot outlet of the EVAC Buffer to the vacuum drainage riser. 6. Route the piping from the EVAC Buffer outlet to the location of the vacuum drainage riser. Maximum length from the buffer to the riser is 3 feet. 7. In order to transition to the riser use (2) 45O elbows or a 90O long sweep radius elbow. 8. Provide bracing within 1 foot of the EVAC Buffer and within 1 foot of the 90O turn at the vacuum riser in accordance with the Installation Instructions for Vacuum Drainage Piping found in Section 6.6.2. Dimensions are subject to manufacturer’s tolerance of ± 1/4" and may change without notice. EVAC assumes no responsibility for use of void or superseded data. © 1998 Envirovac, Inc. Section 6.4.1 1260 Turret Drive • Rockford, IL 61115 USA 888 438 3822 • 815 654 8300 • Fax 815 654 8306 INSTALLATION INSTRUCTIONS REFRIGERATED CASE WITH EVAC Interface Valve, IFV-1 and EVAC Buffer, EB-025 OPTION 2 — Discharge valve in riser pipe with no check valve at the top of the lift To Vacuum Central 3’ Max. 2" Pipe Brace 5’ Max. Activator (Typical) (Typical) (V AC U U M ) Discharge Valve 1-1/2" Riser 22’ Max. (VALVE) (SENSING) 1/4" ID Tubing Supplied by EVAC Bottom of Case Air Intake 3’ Max. Buffer Figure 1. 1-1/2" Pipe Manual Operator (Typical) Sensing Connection Vacuum Supply Inlet 45O To Buffer Sensor Figure 2. Pipe roll at wye. Figure 3. Activator. To Discharge Valve Figure 4. Activator. Figure 5. Buffer—Inlet End. Dimensions are subject to manufacturer’s tolerance of ± 1/4" and may change without notice. EVAC assumes no responsibility for use of void or superseded data. 1260 Turret Drive • Rockford, IL 61115 USA 888 438 3822 • 815 654 8300 • Fax 815 654 8306 © 1998 Envirovac, Inc. Section 6.4.2 INSTALLATION INSTRUCTIONS REFRIGERATED CASE WITH EVAC Interface Valve, IFV-1 and EVAC Buffer, EB-025 OPTION 2 — Discharge valve in riser pipe with no check valve at the top of the lift PURPOSE The EVAC Interface Valve in conjunction with an EVAC Buffer are designed to transport wastewater from a plumbing fixture or refrigerated display case into an EVAC Collection System. INSTALLATION OF EVAC INTERFACE VALVE, IFV-01 O 1. Install a 45 -wye fitting from the vacuum branch or main in order to install the interface valve. The wye fitting may be rolled a maximum of 45O from vertical. Allow for the maximum riser height of 22 feet and a maximum distance of 3 feet from the riser to the wye fitting dropping into the main/branch. valve. Failure to install the mini check valve will result in damage to the activator that is not covered by EVAC’s warranty. 8. Do not paint IFV-01 components. INSTALLATION EB-025 OF EVAC BUFFER, 1. Install 1-1/2" drainage piping from a refrigerated display case or hand sink at a slope of 1/8" per foot to the EVAC Buffer. Required Drainage Slope 1/8" 1’-0" 2. Install the discharge valve in the riser pipe within 5 feet of the top of the riser. The discharge valve is equipped with male pipe ends for gluing directly into plastic piping. For copper tubing — use a shielded coupling that provides a smooth transition from pipe to tubing. 3. Install a pipe brace on the branch piping or main within 1 foot of the 45O-wye fitting. Also, install a pipe brace between the riser pipe and the 45O-wye fitting, but within 6 inches of the riser pipe itself. 4. Install the 1-1/2" riser pipe allowing for no offsets. The riser must remain vertical. 5. Install the activator in an accessible location for future maintenance. 6. Connect the EVAC supplied vacuum tubing as shown in Figures 1, 3, 4, and 5. The activator ports are labeled for "sensor", "vacuum", and "discharge". Attach the vacuum tubing to the riser piping using wire ties. The tubing bending radius are to be a minimum of 3" inches to prevent kinking. Do not over-tighten the wire ties, or the tubing may kink or collapse. 7. Install the mini check valve in the vacuum source line of the discharge valve, as shown in Figure 1. Please note the proper direction of the mini check 2. Place the EVAC Buffer directly on the floor with the direction arrow pointing to the vacuum drainage riser. 3. Prior to the EVAC Buffer inlet connection install an air intake tee fitting, as shown in Figure 1. 4. Use a 1-1/2", 45O-street elbow to connect the 1-1/2" female socket inlet of the EVAC Buffer to the case drain line. 5. Use a 1-1/2", 45O-elbow to connect to the 1-1/2" male spigot outlet of the EVAC Buffer to the vacuum drainage riser. 6. Route the piping from the EVAC Buffer outlet to the location of the vacuum drainage riser. Maximum length from the buffer to the riser is 3 feet. 7. In order to transition to the riser use (2) 45O elbows or a 90O long sweep radius elbow. 8. Provide bracing within 1 foot of the EVAC Buffer and within 1 foot of the 90O turn at the vacuum riser in accordance with the Installation Instructions for Vacuum Drainage Piping found in Section 6.6.2. Dimensions are subject to manufacturer’s tolerance of ± 1/4" and may change without notice. EVAC assumes no responsibility for use of void or superseded data. © 1998 Envirovac, Inc. Section 6.4.2 1260 Turret Drive • Rockford, IL 61115 USA 888 438 3822 • 815 654 8300 • Fax 815 654 8306 INSTALLATION INSTRUCTIONS REFRIGERATED CASE WITH EVAC Interface Valve, IFV-1 and EVAC Buffer, EB-025 OPTION 3 — Discharge valve in riser pipe with a check valve at the top of the lift To Vacuum Central Check Valve 6’ Max. 2" Pipe 3’ Max. Brace Activator (Typical) (Typical) AC U U M ) Discharge Valve (V 1-1/2" Riser (SENSING) 22’ Max. Bottom of Case (VALVE) 1/4" ID Tubing Supplied by EVAC 7’ - 12’ 3’ Max. Air Intake Buffer Figure 1. 1-1/2" Pipe Manual Operator (Typical) Sensing Connection Vacuum Supply Inlet 45O To Buffer Sensor Figure 2. Pipe roll at wye. Figure 3. Activator. To Discharge Valve Figure 4. Activator. Figure 5. Buffer—Inlet End. Dimensions are subject to manufacturer’s tolerance of ± 1/4" and may change without notice. EVAC assumes no responsibility for use of void or superseded data. 1260 Turret Drive • Rockford, IL 61115 USA 888 438 3822 • 815 654 8300 • Fax 815 654 8306 © 1998 Envirovac, Inc. Section 6.4.3 INSTALLATION INSTRUCTIONS REFRIGERATED CASE WITH EVAC Interface Valve, IFV-1 and EVAC Buffer, EB-025 PURPOSE The EVAC Interface Valve in conjunction with an EVAC Buffer are designed to transport wastewater from a plumbing fixture or refrigerated display case into an EVAC Collection System. 8. Install the mini check valve in the vacuum source line of the discharge valve, as shown in Figure 1. Please note the proper direction of the mini check valve. Failure to install the mini check valve will result in damage to the activator that is not covered by EVAC’s warranty. INSTALLATION OF EVAC INTERFACE VALVE, IFV-01 9. Do not paint IFV-01 components. 1. Install a 45O-wye fitting from the vacuum branch or main in order to install the interface valve. The wye fitting may be rolled a maximum of 45O from vertical. Allow for the maximum riser height of 22 feet and a maximum distance of 3 feet from the riser to the wye fitting dropping into the main/branch. 2. Install the EVAC Check Valve, CKV-2, between the riser and the wye fitting that drops in to the main. The check valve has a minor offset of 1/16" that must be accounted for during installation. 3. Install the discharge valve in the riser pipe between 7 and 12 feet from the floor. The discharge valve is equipped with male pipe ends for gluing directly into plastic piping. For copper tubing — use a shielded coupling that provides a smooth transition from pipe to tubing. INSTALLATION EB-025 OF EVAC BUFFER, 1. Install 1-1/2" drainage piping from a refrigerated display case or hand sink at a slope of 1/8" per foot to the EVAC Buffer. 2. Place the EVAC Buffer directly on the floor with the direction arrow pointing to the vacuum drainage riser. Required Drainage Slope 1/8" 1’-0" 3. Prior to the EVAC Buffer inlet connection install an air intake tee fitting, as shown in Figure 1. 4. Install a pipe brace on the branch piping or main within 1 foot of the 45O-wye fitting. Also, install a pipe brace between the riser pipe and the check valve, but within 6 inches of the riser pipe itself. 4. Use a 1-1/2", 45O-street elbow to connect the 1-1/2" female socket inlet of the EVAC Buffer to the case drain line. 5. Install the 1-1/2" riser pipe allowing for no offsets. The riser must remain vertical. 5. Use a 1-1/2", 45O-elbow to connect to the 1-1/2" male spigot outlet of the EVAC Buffer to the vacuum drainage riser. 6. Install the activator in an accessible location for future maintenance. Refer to the Installation Details provided in the EVAC Product Catalog for optimal locations. 6. Route the piping from the EVAC Buffer outlet to the location of the vacuum drainage riser. Maximum length from the buffer to the riser is 3 feet. 7. Connect the EVAC supplied vacuum tubing as shown in Figures 1, 3, 4, and 5. The activator ports are labeled for "sensor", "vacuum", and "discharge". Attach the vacuum tubing to the riser piping using wire ties. The tubing bending radius are to be a minimum of 3" inches to prevent kinking. Do not over-tighten the wire ties, or the tubing may kink or collapse. 7. In order to transition to the riser use (2) 45O elbows or a 90O long sweep radius elbow. 8. Provide bracing within 1 foot of the EVAC Buffer and within 1 foot of the 90O turn at the vacuum riser in accordance with the Installation Instructions for Vacuum Drainage Piping found in Section 6.6.2. Dimensions are subject to manufacturer’s tolerance of ± 1/4" and may change without notice. EVAC assumes no responsibility for use of void or superseded data. © 1998 Envirovac, Inc. Section 6.4.3 1260 Turret Drive • Rockford, IL 61115 USA 888 438 3822 • 815 654 8300 • Fax 815 654 8306 INSTALLATION INSTRUCTIONS EVAC BUFFER, EB-025 Sensing Connection 1.05" 26.7mm 9.30" 236mm 11.68" 296.7mm 4.30" 109mm 0.25" Gap 6.35mm Gap Bottom of case or fixture 1-1/2" Female Socket Inlet 1-1/2" Male Spigot Outlet 4.00" 100mm 1.91" 48.5mm 1.86" 47.2mm PURPOSE The EVAC Buffer is designed to receive wastewater from hand sinks and refrigerated display cases. It is also sized to handle intermittent heavy flow that is generated during a wash-down of a refrigerated display case. PRE-INSTALLATION INSTRUCTIONS 1. The EVAC Buffer, EB-025, requires a 1/4" air gap between the top of the buffer and the bottom of a case of fixture, see above figure. This air gap is required for proper function of the buffer. 2. The EVAC Buffer, EB-025, requires a space for install of 4.25" in height and 4.50" in width. Typically, low profile cases such as specialty end cases, dairy, reach-in frozen food, and specialty deli/bakery case require consideration. For these low profile cases the buffer may need to be installed from one end or at the back of the case. If the buffer does not fit under the case, STOP WORK, and coordinate resolution of the problem with the Job Site Manager. 3. Will the drainage piping from a case line-up have a continuous slope prior to entering the buffer? Various cases may have very limited space from the drain to the floor or end base frames that make it difficult to maintain a continuous slope from case to case. If a continuous slope cannot be achieved, STOP WORK, and coordinate resolution of the problem with the Job Site Manager. INSTALLATION 1. Install 1-1/2" drainage piping from a refrigerated display case or hand sink at a slope of 1/8" per foot to the EVAC Buffer. Required Drainage Slope 1/8" 1’-0" Dimensions are subject to manufacturer’s tolerance of ± 1/4" and may change without notice. EVAC assumes no responsibility for use of void or superseded data. 1260 Turret Drive • Rockford, IL 61115 USA 888 438 3822 • 815 654 8300 • Fax 815 654 8306 © 1998 Envirovac, Inc. Section 6.5.1 INSTALLATION INSTRUCTIONS EVAC BUFFER, EB-025 2. Place the EVAC Buffer directly on the floor with the direction arrow pointing to the vacuum drainage riser. 3. Prior to the EVAC Buffer inlet connection install an air intake tee fitting. 4. Use a 1-1/2", 45O-street elbow to connect the 1-1/2" female socket inlet of the EVAC Buffer to the case drain line. 5. Use a 1-1/2", 45O-elbow to connect to the 1-1/2" male spigot outlet of the EVAC Buffer to the vacuum drainage riser. 6. Route the piping from the EVAC Buffer outlet to the location of the vacuum drainage riser. Maximum length from the buffer to the riser is 3 feet. 7. In order to transition to the riser use (2) 45O elbows or a 90O long sweep radius elbow. 8. Provide bracing within 1 foot of the EVAC Buffer and within 1 foot of the 90O turn at the vacuum riser in accordance with the Installation Instructions for Vacuum Drainage Piping found in Section 6.6.2. Dimensions are subject to manufacturer’s tolerance of ± 1/4" and may change without notice. EVAC assumes no responsibility for use of void or superseded data. © 1998 Envirovac, Inc. Section 6.5.1 1260 Turret Drive • Rockford, IL 61115 USA 888 438 3822 • 815 654 8300 • Fax 815 654 8306 INSTALLATION INSTRUCTIONS EVAC CHECK VALVE, CKV-2 Check Valve Sheilded or Non-shielded Coupling Sheilded or Non-shielded Coupling Inlet Outlet 6.80" 173mm 12.40" 315mm PURPOSE 4. The check valve is equipped with customer specified couplings. EVAC Check Valves provide back-flow prevention in the vacuum drainage piping. The check valves are typically installed horizontally at the tops of risers. 5. The installing contractor must account for an vertical offset of 1/16" from the inlet to the outlet. INSTALLATION 1. The EVAC check valve is a flapper type that must be installed horizontally. 2. The top of the check valve is identified from the retaining screws for the top housing. 3. Install the check valve in the proper direction as identified by the directional arrow on the top housing. Dimensions are subject to manufacturer’s tolerance of ± 1/4" and may change without notice. EVAC assumes no responsibility for use of void or superseded data. 1260 Turret Drive • Rockford, IL 61115 USA 888 438 3822 • 815 654 8300 • Fax 815 654 8306 © 1998 Envirovac, Inc. Section 6.5.2 INSTALLATION INSTRUCTIONS TRENCH DRAIN FOR REFRIGERATED DISPLAY EVAC Interface Valve, IFV-1 CASES WITH To Vacuum Central Check Valve 6’ Max. 3’ Max. 1/4" ID Tubing Supplied by EVAC 2" Pipe Brace (VACUUM) (Typical) (Typical) Activator Discharge Valve (VALVE) (SENSING) 1-1/2" Riser 22’ Max. Distance allowed by code 2" x 1-1/2" Reducer 7’ Min. 4" Pipe Floor Line 2" Pipe From cases Buffer 4" Min. 4" x 2" Reducer Distance is from bottom of the 4" pipe to the top of the 2" pipe. To Vacuum Central 24" Discharge Valve Figure 1. 6’ Max. 3’ Max. (VACUUM) 1/4" ID Tubing Supplied by EVAC 2" Pipe Activator Brace (Typical) (Typical) (SENSING) 1-1/2" Riser (VALVE) Distance allowed by code 2" x 1-1/2" Reducer 20’ Max. 4" Min. Distance is from bottom of the 4" pipe to the top of the 2" pipe. 4" Pipe Floor Line 2" Pipe From cases Buffer 4" x 2" Reducer Figure 2. 24" 1260 Turret Drive • Rockford, IL 61115 USA 888 438 3822 • 815 654 8300 • Fax 815 654 8306 © 1998 Envirovac, Inc. Section 6.6.1 INSTALLATION INSTRUCTIONS TRENCH DRAIN FOR REFRIGERATED DISPLAY EVAC Interface Valve, IFV-1 PIPING CASES WITH The riser must remain vertical. 1. Install conventional plumbing from the refrigerated display case drain to an approved receptor. 5. Install the activator in an accessible location for future maintenance. 2. Provide under-slab or trench piping from the receptor to the location of a vacuum drainage riser. 6. Connect the EVAC supplied vacuum tubing as shown in Figures 1 through 5. The activator ports are labeled for "sensor", "vacuum", and "discharge". Attach the vacuum tubing to the riser piping using wire ties. The tubing bending radius are to be a minimum of 3" inches to prevent kinking. Do not over-tighten the wire ties, or the tubing may kink or collapse. 3. Near the riser make a drop into a section of piping called a buffer using (2) 90O. The drop is to be a minimum of 4" as detailed. 4. The buffer is configured using 2" pipe and fittings. As required reduce the under-slab piping using bushings. 5. Install a buffer section of piping as detailed and make a 90O turn into the vacuum drainage riser. INSTALLATION OF EVAC INTERFACE VALVE, IFV-01 7. Install the mini check valve in the vacuum source line of the discharge valve, as shown in Figure 1. Please note the proper direction of the mini check valve. Failure to install the mini check valve will result in damage to the activator that is not covered by EVAC’s warranty. 8. Do not paint IFV-01 components. 1. Install a 45O-wye fitting in the vacuum branch or main. This allows for installation of the discharge valve. The wye fitting may be rolled a maximum of 45O from vertical as shown in Figure 2. Allow for the maximum riser height of 22 feet and a maximum distance of 3 feet from the riser to the wye fitting dropping into the main/branch. 45O 2. Install the EVAC Check Valve, CKV-2, between the riser and the wye fitting that drops in to the main. The check valve has a minor offset of 1/16" that must be accounted for during installation. Figure 3. 3. Install the discharge valve in the riser pipe a minimum of 7 feet from the floor. The discharge valve is equipped with male pipe ends for gluing directly into plastic piping. For copper tubing — use a shielded coupling that provides a smooth transition from pipe to tubing. Pipe roll at wye. Manual Operator 4. Install a pipe brace on the branch piping or main within 1 foot of the 45O-wye fitting. Also, install a pipe brace between the riser and the discharge valve, but within 6 inches of the riser pipe itself. Vacuum Supply To Buffer Sensor Figure 4. Activator. To Discharge Valve Figure 5. Activator. 4. Install the 1-1/2" riser pipe allowing for no offsets. Dimensions are subject to manufacturer’s tolerance of ± 1/4" and may change without notice. EVAC assumes no responsibility for use of void or superseded data. © 1998 Envirovac, Inc. Section 6.6.1 1260 Turret Drive • Rockford, IL 61115 USA 888 438 3822 • 815 654 8300 • Fax 815 654 8306 INSTALLATION INSTRUCTIONS VACUUM DRAINAGE PIPING Check Valve Required Drainage Slope 1/16" Discharge Valve 12’ Max. 1’-0" Activator Activator Reformer Pocket 8’ Max. Figure 1. Discharge Valve Buffer Buffer Hanger Rod 3’ Max. 12" Max. Hanger Rod O 45 Strap Pipe Split-ring Hanger Uni-strut Other Utility Piping Figure 3. Figure 2. Dimensions are subject to manufacturer’s tolerance of ± 1/4" and may change without notice. EVAC assumes no responsibility for use of void or superseded data. 1260 Turret Drive • Rockford, IL 61115 USA 888 438 3822 • 815 654 8300 • Fax 815 654 8306 © 1998 Envirovac, Inc. Section 6.6.2 INSTALLATION INSTRUCTIONS VACUUM DRAINAGE PIPING 4. Vacuum drainage riser must enter mains from above using a wye pattern fitting. The wye fitting may be rolled 45 degree from vertical. No tee fittings. SCOPE The following are the general rules for installing vacuum drainage piping in a supermarket. INSTALLATION PIPING OF 5. Inside piping surfaces and joints must be smooth, free of burrs and obstructions. VACUUM DRAINAGE 6. Locate clean-outs in the vacuum piping at the ends of mains and branches and when there is a 90O change in direction in an overhead branch or main. 1. Pitch vacuum drainage piping at a minimum 1/16" per foot. This requirement may be met through the pitch of the store roof from the front to the back allowing for storm water drainage. 7. A single offset is allowed in vertical risers. Note: Offset is not preferred and should only be used to bypass structural obstructions. See Figure 4. Required Drainage Slope 1/16" 8. No common risers or ganged lifts are allowed except for frozen food island and reach-in cases as shown in Figure 1. 1’-0" 2. Brace piping at 5’ intervals and within 1 foot of each change in direction as shown in Figure 2. 9. Reformer pockets as shown in Figure 3 may be installed in order to recapture the slope of the vacuum drainage piping or to route under an obstruction. 3. Use only long radius elbows or (2) 45O elbows. YES YES NO Offset 1’-0" Horizontal Maximum Offset Figure 4. Dimensions are subject to manufacturer’s tolerance of ± 1/4" and may change without notice. EVAC assumes no responsibility for use of void or superseded data. © 1998 Envirovac, Inc. Section 6.6.2 1260 Turret Drive • Rockford, IL 61115 USA 888 438 3822 • 815 654 8300 • Fax 815 654 8306 SECTION 7 SAMPLE SPECIFICATIONS Table of Contents This section contains sample specifications that can be used by the designer for construction documentation. SECTION 7.1 — EVAC VACUUM COLLECTION SYSTEM DRAINAGE PIPING SECTION 7.2 — EVAC VACUUM COLLECTION SYSTEM 1260 Turret Drive • Rockford, IL 61115 USA 888 438 3822 • 815 654 8300 • Fax 815 654 8306 © 1998 Envirovac, Inc. Section 7.0.0 SAMPLE SPECIFICATIONS EVAC SECTION EVAC Vacuum Collection System Drainage Piping 1. GENERAL 2. EQUIPMENT 1.1 Installers scope of work 2.1 Vacuum collection system A. The intent of this specification, together with accompanying Drawings is to provide a complete operating installation, including, but not limited to the following principal items. 1. The EVAC System is to be separate from the sanitary plumbing system. As shown on the drawings, the refrigerated display case condensate collection system shall be EVAC and the sanitary system shall be plumbed conventional. 2. All waste and drain piping for the refrigerated display cases shall be a complete and operational vacuum (EVAC) system. 3. Vacuum drainage piping is reduced in size and also requires the use of specific materials in order to fully utilize the vacuum process. Installing Contractor is to pay close attention to sizing and shall not deviate from design. Note: Conventional venting is not required and shall be installed only as sized and shown on drawings. 5. The EVAC system is to include all fixtures and fittings as specified in the EVAC Fixture Schedule and the EVAC Vacuum System is to be provided complete to include but not limited to all interface valves and the Vacuum Central Module. 1260 Turret Drive • Rockford, IL 61115 USA 888 438 3822 • 815 654 8300 • Fax 815 654 8306 A. The vacuum collection system shall be by EVAC. The system is to include all fixtures and fittings as specified in the EVAC Fixture Schedule and the Central Vacuum System is to be provided complete to include but not limited to all interface valves and the Vacuum Central Module. 2.2 Piping (Supplied by Installer) A. Vacuum Drainage Piping 1. Vacuum drainage piping for the vacuum collection system through out the entire installation shall be as follows: a. Vacuum drainage piping shall be copper, hard drawn Type "M" tubing with wrought copper fittings, soldered (95.5). The wye fittings shall be DWV fittings. Installation drawings provide in detail the fitting requirements for this installation. Installing Contractor shall not deviate from these requirements. Failure to comply with the specified installation shall require the Installing Contractor to replace all improper fittings or piping arrangements with those specified at no additional cost. OR a. Vacuum drainage piping and fittings shall be schedule 40 PVC or equivalent. Wye fittings are the only fittings that may be DWV. Pipe and fittings shall be solvent welded with the use of a primer for visual joint inspections. Installation drawings provide in detail the fitting requirements for this installation. Installing Contractor shall not deviate from these requirements. Failure to comply with the specified installation shall require the Installing Contractor to replace all improper fittings or piping arrangements with those specified at no additional cost. © 1998 Envirovac, Inc. Section 7.1.0 SAMPLE SPECIFICATIONS EVAC SECTION EVAC Vacuum Collection System Drainage Piping b. For this vacuum collection system installation it is crucial that during the piping connection process that all burrs are removed and when using copper, that during the soldering procedure solder shall not be allowed to form on the inside of the pipe and fittings. Burrs or formation of solder can snag waste items and plug the system, therefore all fittings shall be carefully checked and any burrs or buildup of solder shall be removed prior to installing the next section of pipe or fitting. Failure to comply with the installation requirement shall require the Installing Contractor to replace all improper solder fittings or piping connections and reinstall as specified at no additional cost. 3. FACTORY SERVICES 3.1 An authorized EVAC service representative shall provide installation inspection and on site startup of the vacuum system. The EVAC service representative shall confirm to the owner’s project manager and design engineer that the vacuum drainage piping and collection system equipment have been installed in accordance with the plans, specifications and manufacturer’s recommendations. 3.2 The EVAC service representative shall provide a maximum of two installation site inspections and one system start up at no addtional cost. Site visits exceeding the above will be billed to the owner. © 1998 Envirovac, Inc. Section 7.1.0 1260 Turret Drive • Rockford, IL 61115 USA 888 438 3822 • 815 654 8300 • Fax 815 654 8306 SAMPLE SPECIFICATIONS EVAC SECTION EVAC Vacuum Collection System 1.4 1. GENERAL 1.1 Related documents A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specifications Sections, apply to this Section. 1.2 A. Submit product data including rated capacities of selected models and weights (shipping, installation, and operation). Indicate materials, finishes, dimensions, required clearances, and methods of assembly of components; and piping and wiring connections for the equipment being provided by EVAC. 1. Vacuum central 2. Vacuum interface valve 3. Buffer piping Summary A. EVAC vacuum collection system including piping, specialties and controllers as provided by EVAC. B. Operating and Maintenance manuals: (EVAC Rep) (Phone #) B. Service: EVAC service representative to provide service as follows: 1. System start-up 2. Installation inspection C. Provide the following electrical work as work of this section, complying with requirements of Division-16 sections: 1. As required, control wiring between field installed controls, indicating devices, and unit control panels. 1. Complete vacuum system. C. Submit detailed installation drawings for complete system. The drawings are to clearly identify all components being supplied by EVAC and Installing Contractor. 1.5 System performance requirements A. Provide components and installation capable of producing piping systems with following minimum working pressure ratings, except where otherwise indicated: Quality assurance A. Comply with ASME B31.9, "Building Services Piping", for materials, products, and installation. B. Electrical Component Standard: NFPA 70, "National Electrical Code" C. Listing and Labeling: Provide equipment that is listed and labeled. 2. Power supply wiring from power source to the vacuum central electrical control panel. 1.3 Submittals 1. The Terms "Listed" and "Labeled" as defined in the "National Electrical Code," Article 100. 1.6 Material handling A. Contractor shall be responsible to protect all vacuum product as supplied by EVAC from the environment and construction debris, dust, and paint. No EVAC equipment shall be stored outdoors. 1. EVAC Vacuum Collection Systems: Subject to manufacturer’s recommendations. 1260 Turret Drive • Rockford, IL 61115 USA 888 438 3822 • 815 654 8300 • Fax 815 654 8306 © 1998 Envirovac, Inc. Section 7.2.0 SAMPLE SPECIFICATIONS EVAC SECTION EVAC Vacuum Collection System 1.7 b) The control panel shall provide the following alarms in the form of powered outputs from the logic controller: Extra materials A. Furnish extra materials matching products installed as described below to Owner. Package them with protective covering for storage and identify with labels clearly describing contents. 2. PRODUCTS 2.1 Manufacturer 1. Low Vacuum Alarm 2. Block Level Alarm 3. Motor O.L. Alarm a) A MANUAL/OFF/AUTO switch shall be provided for each vacuum pump. 3. Vacuum Interface Valve a) EVAC model number 2999799 . b) The interface valve shall be operated using the vacuum pressure from the vacuum piping as maintained by the vacuum central. A. The following components of the vacuum collection system shall be supplied by EVAC. 2.2 Vacuum collection system A. The vacuum collection system shall be a packaged unit consisting of vacuum tank(s), vacuum pump(s), electrical control panel and all necessary fittings and ancillary equipment to provide full automatic operation of the system. B. The following list delineates the major components being provided in this bid package by EVAC for the vacuum waste collection system. Reference drawings and other specifications for other components being supplied. 1. Vacuum Central a) EVAC Model SMC230-30H 2. Control Panel a) The control panel shall be designed in accordance with the National Electric Code and shall be constructed with a NEMA 12 enclosure. The control panel may be constructed of UL listed components. A logic controller mounted in the control panel shall operate system controls. The vacuum pump controls shall be arranged to provide automatic operation of the vacuum pumps be means of a vacuum switch. Electrical requirements: 230 VAC, 3 Phase, 60 Hz © 1998 Envirovac, Inc. Section 7.2.0 4. Buffer a) EVAC model number 2999799 3. EXECUTION 3.1 Vacuum collection system . A. General: Comply with unit manufacturer’s written installation instructions and with local authority for installation of complete system. B. Install units with clear space for servicing. C. Vacuum System Design Requirements: 1. The vacuum central discharge line is to flow in to the sanitary waste system with a minimum physical air gap as specified by code. 2. Vacuum drainage piping inside piping surfaces shall be smooth and free of burrs, weld bead protrusions, and abrupt changes in cross section. 3. Where a joint is made in which the inside diameter of the vacuum drainage pipe and fitting do not meet flush, then the inside of the pipe must be taper-reamed to produce a smooth transition. 1260 Turret Drive • Rockford, IL 61115 USA 888 438 3822 • 815 654 8300 • Fax 815 654 8306 SAMPLE SPECIFICATIONS EVAC SECTION EVAC Vacuum Collection System 12. Branch lines shall be sloped toward the collection main and the collection mains shall be sloped toward the vacuum tank. Slope shall be a positive 0.50%, (1/16" per foot), to the collection system (not including lifts associated with pockets). Please note this requirement may sometimes be met by following the slope of the roof as long as the roof is sufficiently pitched for storm water drainage. 4. All right-angle bends in the vacuum drainage piping shall use five diameter radius bends or two 45O elbow fittings. 5. Line clean-outs shall be located at no greater than 60-foot intervals in a vacuum line. There shall be no more than one 90O change in pipe direction between clean-outs. 6. A clean out shall be located at the end of all vacuum mains and at the end of a branch unless the branch line serves a single fixture that discharges into the main from above. 7. Wye-branch fitting in vacuum drainage piping shall be positioned so that branch lines enter the wye-branch fitting at a 45O angle measured in a vertical plane from the horizontal 8. Where vacuum drainage piping is to proceed vertically upward, a small pocket shall be placed in the horizontal pipeline immediately preceding the vertical rise. This pocket is placed to provide a collection point for liquid drainage that drains from the vertical pipe section while the system is static. These pipeline pockets shall be fabricated from 45O elbows and shall have a clean out at the inlet to the pocket unless the pocket is immediately adjacent to a fixture. 9. All risers shall enter the main from the top rather than from the bottom or side. 10. A transport pocket shall be located at approximately 140-foot intervals in a vacuum drainage pipe, measured from the farthest fixture in the vacuum main. 11. Vacuum tank to vacuum pump piping, and vacuum pump vents shall be installed without dips or pockets in which water can accumulate. A considerable amount of water vapor can be expected through this piping. The vacuum pump suction piping shall rise to the highest required elevation immediately after leaving the vacuum tank. The pipe shall connect to the vacuum pump inlet without another rise. 1260 Turret Drive • Rockford, IL 61115 USA 888 438 3822 • 815 654 8300 • Fax 815 654 8306 3.2 Connections A. Installing contractor is responsible for all final connections from fixtures; either owner supplied or contractor supplied to the vacuum collection system. B. Installing contractor is responsible for interconnecting the entire owner furnished equipment at the central module system. This includes waste and vacuum drainage piping and valves. C. Installing contractor is responsible for coordinating all electrical connections. 3.3 Field services A. An authorized EVAC service representative shall provide installation inspection and on site startup of the vacuum system. The EVAC service representative shall confirm to the owner’s project manager and design engineer that the vacuum drainage piping and collection system equipment have been installed in accordance with the plans, specifications and manufacturer’s recommendations. B. The EVAC service representative shall provide a maximum of two installation sinspections and one system start up at no addtional cost. Site visits exceeding the above will be billed to the owner. 3.4 Commissioning A. Preparation: Installing contractor to perform the following checks before startup: 1. Systems tests are complete including vacuum leak testing. © 1998 Envirovac, Inc. Section 7.2.0 SAMPLE SPECIFICATIONS EVAC SECTION EVAC Vacuum Collection System 2. Damaged and defective specialties and accessories have been replaced or repaired. 3. There is clear space for servicing of specialties. B. An authorized EVAC service representative shall perform system startup in accordance with manufacturer’s recommendations. The representative shall provide the owner’s project manager and design engineer verification of the completion of system startup. 3.5 Adjusting A. Adjust operation and correct deficiencies discovered during commissioning. 3.6 Demonstration A. Provide owner with Operating and Maintenance Manuals related to startup and servicing of all vacuum equipment. 3.7 Protection A. Protect equipment drain lines during remainder of construction period to avoid clogging with dirt and debris and to prevent damage from traffic and construction work. B. Place plugs in end of uncompleted piping at end of day or when work stops. © 1998 Envirovac, Inc. Section 7.2.0 1260 Turret Drive • Rockford, IL 61115 USA 888 438 3822 • 815 654 8300 • Fax 815 654 8306 SECTION 8.0 LIMITED WARRANTY STATEMENT Envirovac warrants to Buyer and any customer of Buyer or end user, if applicable, that the Products are free from defects in material or workmanship under normal use or service, for the sooner of (a) eighteen (18) months from the date of delivery of the Products by Seller to Buyer, and (b) twelve (12) months from the date of Initial Start Up by Buyer or a customer of Buyer or end user (the "Warranty"). The Warranty applies only where the Products have been properly stored, installed, operated and maintained in accordance with Envirovac’s instructions. FOR THE FULL SCOPE OF, AND LIMITATIONS UPON, ENVIROVAC’S WARRANTIES AND BUYER'S OR ANY END USER’S REMEDIES, PLEASE SEE ENVIROVAC’S STANDARD TERMS AND CONDITIONS. IN NO EVENT SHALL ENVIROVAC BE LIABLE FOR ANY CONSEQUENTIAL, INCIDENTAL OR SPECIAL DAMAGES WHATSOEVER. Except as provided in Envirovac’s terms and conditions, ENVIROVAC MAKES NO WARRANTY OF ANY KIND WHATSOEVER, ORAL OR WRITTEN, EXPRESS OR IMPLIED, BY COURSE OF DEALING OR USAGE OF TRADE, AND ALL IMPLIED WARRANTIES INCLUDING WARRANTIES OF MERCHANTABILITY AND FITNESS FOR PARTICULAR PURPOSE, ARE HEREBY DISCLAIMED BY ENVIROVAC. Envirovac’s sole obligations and Buyer’s sole remedies under its Warranty with respect to Products shall be to replace the Products or any part thereof sold by it which, in Envirovac’s judgment, is defective as set forth above with a similar Product or part, or at Envirovac’s option, to repair the Product or part(s) thereof subject to the terms and conditions set forth below. If Envirovac has received proper certification, and a warranty claim is made in accordance with the terms and conditions during the first ninety (90) days after initial start up, then Envirovac shall reimburse Buyer or the customer or end user for labor charges directly related to the cost to remove any defective Product or any part thereof and replace the same. Such reimbursement shall be based upon standard Product and component replacement times and labor rates as determined by Envirovac, in its sole discretion. 1260 Turret Drive • Rockford, IL 61115 USA 888 438 3822 • 815 654 8300 • Fax 815 654 8306 © 1998 Envirovac, Inc. Section 8.0.0