AAC BARE OVERHEAD SUPPORTING NEUTRAL

Transcription

AAC BARE OVERHEAD SUPPORTING NEUTRAL
AAC BARE OVERHEAD SUPPORTING NEUTRAL
AAC - All Aluminum Conductor - 1350 Series Alloy
Engineering Specifications:
Standards:
ASTM B230: Standard Specification for Aluminum 1350-H19 Wire for Electrical Purposes.
ASTM B231: Standard Specification for Concentric-Lay-Stranded Aluminum 1350 Conductors.
Construction:
Conductors:
Stranded, Concentric-Lay Aluminum Conductors,1350 Series Alloy per ASTM B231.
Assembly:
AAC bare overhead supporting neutrals are concentric-lay-stranded aluminum alloy 1350 conductors with a straight, round central wire surrounded by one or more layers of helically
applied wires. Outer layer has right-handed lay.
APPLICATIONS:
Suitable for overhead transmission and distribution applications that do not require the rated strength of ACSR type neutrals. Encore's AAC overhead neutrals include Class AA for
bare conductors usually used in overhead lines, and/or Class A for conductors to be covered with weather-resistant materials. Class A also for bare conductors where greater
flexibility is required.
➊Concentric Stranded All Aluminum Conductor (AAC),
1350 Series Alloy
AAC BARE OVERHEAD SUPPORTING NEUTRAL
AAC - ALL ALUMINUM CONDUCTOR - 1350 SERIES ALLOY
AWG Area
Code Word KCMIL (mm²)
Peachbell
Rose
Iris
Pansy
Poppy
Aster
Phlox
Oxlip
Daisy
Tulip
Canna
Cosmos
Dahlia
Orchid
Petunia
Arbutus
Magnolia
Bluebell
6
4
2
1
1/0
2/0
3/0
4/0
266.8
336.4
397.5
477.0
556.5
636.0
750.0
795.0
954.0
1033.5
13.3
21.1
33.6
42.4
53.5
67.4
85.0
107.2
135.2
170.5
201.4
241.1
282.0
322.3
380.0
402.8
483.4
523.7
Resistance
DC Resistance at 20C
AC Resistance at 60 Hz
(Ohms/1000ft)
Nominal
Diameters
Conductor Sizes
Area
(in²)
No. of
Strands
0.0206
0.0328
0.0522
0.0657
0.0829
0.1045
0.1317
0.1662
0.2095
0.2644
0.3124
0.3744
0.4369
0.4995
0.5893
0.6245
0.7495
0.8114
7
7
7
7
7
7
7
7
7
19
19
19
19
37
37
37
37
37
Reactance
@ 60 Hz
1 ft. equiv. spacing
(Megohms/1000ft)
Class
Each Finished Approximate Rated
Net Weight Strength
Strand
OD
(lbs)
(in)
(in) (lbs/1000 ft)
DC
20°C
AC
25°C
AC
50°C
AC
50°C
Capacitive
Inductive
Ampacity
(Amps)
A
A
AA, A
AA, A
AA, A
AA, A
AA, A
AA, A
AA
A
AA, A
AA
AA
AA, A
AA
AA
AA
AA
0.0612
0.0772
0.0974
0.1093
0.1228
0.1379
0.1548
0.1739
0.1953
0.1331
0.1446
0.1584
0.1711
0.1311
0.1424
0.1466
0.1606
0.1671
0.661
0.416
0.261
0.207
0.164
0.130
0.103
0.0820
0.0648
0.0513
0.0435
0.0363
0.0311
0.0272
0.0230
0.0217
0.0181
0.0167
0.673
0.423
0.266
0.211
0.167
0.133
0.105
0.0835
0.0663
0.0527
0.0445
0.0373
0.0320
0.0282
0.0251
0.0227
0.0191
0.0177
0.739
0.465
0.293
0.232
0.184
0.146
0.116
0.0917
0.0727
0.0578
0.0489
0.0409
0.0352
0.0309
0.0263
0.0248
0.0208
0.0193
0.806
0.506
0.318
0.253
0.200
0.159
0.126
0.100
0.0794
0.0629
0.0534
0.0445
0.0383
0.0335
0.0286
0.0269
0.0227
0.0210
0.7660
0.7296
0.6929
0.6716
0.6550
0.6346
0.6188
0.6029
0.5810
0.5600
0.5490
0.5330
0.5220
0.5110
0.4980
0.4940
0.4790
0.0473
0.1193
0.1140
0.1087
0.1061
0.1034
0.1008
0.0981
0.0955
0.0926
0.0888
0.0869
0.0848
0.0830
0.0811
0.0792
0.0780
0.0763
0.0756
103
138
185
214
247
286
331
383
443
513
570
639
703
765
847
878
982
1031
0.184
0.232
0.292
0.328
0.368
0.414
0.464
0.522
0.586
0.665
0.723
0.792
0.856
0.918
0.997
1.026
1.124
1.170
24.6
39.1
62.2
78.4
98.9
124.8
157.2
198.4
250.2
315.5
372.9
446.8
521.4
596.0
703.2
745.3
894.5
968.4
563
881
1350
1640
1990
2510
3040
3830
4830
6150
7110
8360
9750
11400
13100
13900
16400
17700
DC Resistance based on 16.95 Ohms-cmil/ft (20°C); 61.20% IACS per ASTM B231.
AC Resistance at 60Hz.
Ampacity based on 75°C conductor temp; 25°C ambient temp; 0.5 coefficients emissivity and absorption; 2ft./sec wind; 961 watts/sq. foot sun.
46
800.962.9473 www.encorewire.com
TYPE duplex - EC-1350 SERIES ALUMINUM - overhead service DROP / 600V
AAC 1350 - ALL ALUMINUM CONDUCTOR SUPPORTING NEUTRAL
Engineering Specifications:
Standards:
ANSI/ICEA S-76-474; ASTM B233; ASTM B836; ARRA 2009 Section 1605 “Buy American” Compliant.
Construction:
Conductors:
Insulated Conductor: Compact Stranded Conductors, Aluminum Alloy 1350 Series per ASTM B230; ASTM B609; ASTM B231; ASTM B836.
Neutral Conductor: Stranded All Aluminum Conductor (AAC), 1350 Series Alloy Bare Neutral Conductor per ASTM B230; ASTM B609; ASTM B231.
Insulation:
Cross-link polyethylene (XLPE) black insulation per ANSI/ICEA S-76-474, rated 90°C wet or dry.
Applications:
Duplex overhead service drop cable with AAC Series 1350 alloy neutral is designed for applications not exceeding 600 volts with a maximum conductor operating temperature of 90°C.
Primarily used for delivering single phase power from secondary power lines or pole mounted transformers to service entrance heads of a building or structure. Suitable for 120 volt aerial
service for outdoor lighting or for temporary service at construction sites.
Features:
Duplex overhead service drop cable has one black XLPE insulated aluminum conductor cabled around a bare stranded AAC 1350 alloy supporting neutral. Superior weather-, abrasion-,
crush-, and sunlight-resistant XLPE insulation rated 90°C operation. Manufactured and tested according to ANSI/ICEA S-76-474: Standard for Neutral Supported Power Cable Assemblies
with Weather-Resistant Extruded Insulations Rated 600 Volts. Conductor is surface printed for identification.
➊
➋
➊XLPE Insulation
➋Compact Stranded Aluminum Conductor, EC-1350 Series
➌Concentric Stranded All Aluminum Conductor (AAC),
➌
EC-1350 Series Supporting Neutral
TYPE DUPLEX - EC-1350 SERIES ALUMINUM - OVERHEAD ALUMINUM SERVICE DROP - 600V
AAC 1350 - ALL ALUMINUM CONDUCTOR SUPPORTING NEUTRAL
Phase Conductors
Code Word
Conductor
Sizes
(AWG)
Collie
Spaniel
Doberman
Malemute
6-6
4-4
2-2
1/0-1/0
Bare Neutral Conductor
Insulation Outside
Size
No. of Thickness Diameter
(AWG) Strands
(in)
(in)
6
4
2
1/0
7
7
7
10
0.045
0.045
0.045
0.060
0.259
0.303
0.358
0.456
Type
Size
(AWG)
No. of
Strands
Rated
Strength
(lbs)
AAC
AAC
AAC
AAC
6
4
2
1/0
7
7
7
7
563
881
881
881
Diameter of
Final
Approximate
Finished
*Ampacity Construction Net Weight
OD
(XLPE)
(in)
(lbs/1000 ft)
(in)
0.169
0.213
0.268
0.336
110
145
195
260
0.428
0.516
0.626
0.792
65
90
150
235
Standard
Packaging
Reels
(ft)
500' 1000' 1500'
500' 1000' 1500'
500' 1000' 1500'
500' 1000' 1500'
*Ampacities shown are for non-NEC applications and are based on the following factors:
a) conductor temperature of 65°C over 25°C ambient temperature
b) 2 ft./sec crosswind
c) .9 coefficient of emissivity, no sun
For NEC® type applications, consult appropriate NEC ampacity section.
The above data is approximate and subject to normal manufacturing tolerances.
Print Legend: ENCORE WIRE CORP (SIZE) AWG EC-1350 AL CDR XLPE SUN RES 600 VOLT DATE/TIME/OPERATOR/QC
800.962.9473 www.encorewire.com
47
TYPE TRIplex - EC-1350 series ALUMINUM - overhead service DROP - 600V
AAC 1350 - all aluminum conductor supporting neutral
Engineering Specifications:
Standards:
ANSI/ICEA S-76-474; ASTM 233; ASTM B836; ARRA 2009/FAR Subpart 25.6 “Buy American” Compliant.
Construction:
Conductors:
Insulated Conductors: Compact Stranded Conductors, Aluminum Alloy 1350 Series per ASTM B230; ASTM B609; ASTM B231; ASTM B836.
Neutral Conductor: Stranded All Aluminum Conductor (AAC), 1350 Series Alloy Bare Neutral Conductor per ASTM B230; ASTM B609; ASTM B231.
Insulation:
Cross-link polyethylene (XLPE) black insulation per ANSI/ICEA S-76-474, rated 90°C wet or dry.
Applications:
Triplex overhead service drop cable with AAC 1350 Series alloy neutral is designed for applications not exceeding 600 volts with a maximum conductor operating temperature of 90°C.
Primarily used for delivering single phase power from secondary power lines or pole mounted transformers to service entrance heads of a building or structure. Suitable for 120 volt aerial
service for outdoor lighting or for temporary service at construction sites.
Features:
Triplex overhead service drop cable has two black XLPE insulated aluminum conductors cabled around a bare stranded AAC 1350 Series alloy supporting neutral. Superior weather-,
abrasion-, crush-, and sunlight-resistant XLPE insulation rated 90°C for operation. Manufactured and tested according to ANSI/ICEA S-76-474: Standard for Neutral Supported Power
Cable Assemblies with Weather-Resistant Extruded Insulations Rated 600 Volts. Insulated conductors are surface printed for identification.
➊
➌
➊XLPE Insulation
➋Compact Stranded Conductor, EC-1350 Series
➌Concentric Stranded All Aluminum Conductor (AAC),
1350 Series Supporting Neutral
➋
TYPE TRIPLEX - EC-1350 SERIES ALUMINUM - OVERHEAD SERVICE DROP - 600V
AAC 1350 - ALL ALUMINUM CONDUCTOR SUPPORTING NEUTRAL
Phase Conductors
Code Word
Conductor
Sizes
(AWG)
Patella
Oyster
Clam
Purpura
Nassa
Melita
Portunus
6-6-6
4-4-4
2-2-2
1/0-1/0-1/0
2/0-2/0-2/0
3/0-3/0-3/0
4/0-4/0-4/0
Bare Neutral Conductor
XLPE
Outside
Size
No. of Thickness Diameter
(AWG) Strands
(in)
(in)
6
4
2
1/0
2/0
3/0
4/0
7
7
7
10
12
15
19
0.045
0.045
0.045
0.060
0.060
0.060
0.060
0.259
0.303
0.358
0.456
0.496
0.543
0.595
Type
Size
(AWG)
No. of
Strands
Rated
Strength
(lbs)
AAC
AAC
AAC
AAC
AAC
AAC
AAC
6
4
2
1/0
2/0
3/0
4/0
7
7
7
7
7
7
7
563
881
1350
1990
2510
3310
4020
Diameter of
Final
Approximate
Finished
*Ampacity Construction Net Weight
OD
(XLPE)
(in)
(lbs/1000 ft)
(in)
0.169
0.213
0.268
0.336
0.376
0.423
0.475
110
145
195
260
300
350
405
0.552
0.645
0.763
0.971
1.056
1.157
1.267
120
160
240
375
470
560
700
Standard
Packaging
Reels
(ft)
500' 1000' 1500'
500' 1000' 1500'
500' 1000' 1500'
500' 1000' 1500'
500' 1000' 1500'
500' 1000' 1500'
500' 1000' 1500'
*Ampacities shown are for non-NEC applications and are based on the following factors:
a) conductor temperature of 65°C over 25°C ambient temperature
b) 2 ft./sec crosswind
c) .9 coefficient of emissivity, no sun
For NEC® type applications, consult appropriate NEC ampacity section.
The above data is approximate and subject to normal manufacturing tolerances.
Print Legend: ENCORE WIRE CORP (SIZE) AWG EC-1350 AL CDR XLPE SUN RES 600 VOLT DATE/TIME/OPERATOR/QC
48
800.962.9473 www.encorewire.com
TYPE QUADRUPLEX - EC-1350 series aluminum - overhead service DROP - 600V
AAC 1350 - ALL ALUMINUM CONDUCTOR SUPPORTING NEUTRAL
Engineering Specifications:
Standards:
ANSI/ICEA S-76-474; ASTM 233; ASTM B836; ARRA 2009 Section 1605 “Buy American” Compliant.
Construction:
Conductors:
Insulated Conductors: Compact Stranded Conductors, Aluminum Alloy 1350 Series per ASTM B230; ASTM B609; ASTM B231; ASTM B836.
Neutral Conductor: Stranded All Aluminum Conductor (AAC), 1350 Series Alloy Bare Neutral Conductor per ASTM B230; ASTM B609; ASTM B231.
Insulation:
Cross-link polyethylene (XLPE) black insulation per ANSI/ICEA S-76-474, rated 90°C wet or dry.
Applications:
Quadruplex overhead service drop cable with AAC 1350 alloy neutral is designed for applications not exceeding 600 volts with a maximum conductor operating temperature of 90°C.
Primarily used for delivering single phase power from secondary power lines or pole mounted transformers to service entrance heads of a building or structure. Suitable for 120 volt aerial
service for outdoor lighting or for temporary service at construction sites.
Features:
Quadruplex overhead service drop cable has three black XLPE insulated aluminum conductors cabled around a bare stranded AAC 1350 alloy supporting neutral. Superior weather-,
abrasion-, crush-, and sunlight-resistant XLPE insulation rated 90°C for operation. Manufactured and tested according to ANSI/ICEA S-76-474: Standard for Neutral Supported Power
Cable Assemblies with Weather-Resistant Extruded Insulations Rated 600 Volts. Insulated conductors are surface printed for identification.
➊
➊XLPE Insulation
➋Compact Stranded Conductor, EC-1350 Series
➌Concentric Stranded All Aluminum Conductor (AAC),
➌
EC-1350 Series Supporting Neutral
➋
TYPE QUADRUPLEX - EC-1350 ALUMINUM - OVERHEAD SERVICE DROP - 600V
AAC 1350 - ALL ALUMINUM CONDUCTOR SUPPORTING NEUTRAL
Phase Conductors
Code Word
Conductor
Sizes
(AWG)
Pinto
Mustang
Shire
Criollo
Percheron
Hanoverian
Oldenburg
4-4-4-4
2-2-2-2
1-1-1-1
1/0-1/0-1/0-1/0
2/0-2/0-2/0-2/0
3/0-3/0-3/0-3/0
4/0-4/0-4/0-4/0
Bare Neutral Conductor
XLPE
Outside
Size
No. of Thickness Diameter
(AWG) Strands
(in)
(in)
4
2
1
1/0
2/0
3/0
4/0
7
7
8
10
12
15
19
0.045
0.045
0.045
0.060
0.060
0.060
0.060
0.303
0.358
0.389
0.456
0.496
0.543
0.595
Type
Size
(AWG)
No. of
Strands
Rated
Strength
(lbs)
AAC
AAC
AAC
AAC
AAC
AAC
AAC
4
2
1
1/0
2/0
3/0
4/0
7
7
7
7
7
7
7
881
1350
1640
1990
2510
3040
3830
Finished
OD
(in)
Ampacity
(XLPE)
0.213
0.268
0.299
0.336
0.376
0.423
0.475
135
175
205
240
280
325
375
Diameter of
Final
Approximate
Construction Net Weight
(in)
(lbs/1000 ft)
0.727
0.859
0.934
1.094
1.190
1.303
1.428
210
320
410
500
635
775
960
Standard
Packaging
Reels
(ft)
500' 1000' 1500'
500' 1000' 1500'
500' 1000' 1500'
500' 1000' 1500'
500' 1000' 1500'
500' 1000' 1500'
500' 1000' 1500'
*Ampacities shown are for non-NEC applications and are based on the following factors:
a) conductor temperature of 65°C over 25°C ambient temperature
b) 2 ft./sec crosswind
c) .9 coefficient of emissivity, no sun
For NEC® type applications, consult appropriate NEC ampacity section.
The above data is approximate and subject to normal manufacturing tolerances.
Print Legend: ENCORE WIRE CORP (SIZE) AWG EC-1350 AL CDR XLPE SUN RES 600 VOLT DATE/TIME/OPERATOR/QC
800.962.9473 www.encorewire.com
49
ACSR BARE OVERHEAD SUPPORTING NEUTRAL
ACSR - ALUMINUM CONDUCTOR STEEL REINFORCED - 1350 SERIES ALLOY WITH STEEL SUPPORT CENTER WIRE
ENGINEERING SPECIFICATIONS
Standards
ASTM B230: Standard Specification for Aluminum 1350-H19 Wire for Electrical Purposes
ASTM B232: Standard Specification for Concentric-Lay-Stranded Aluminum Conductors, Coated-Steel Reinforced (ACSR)
CONSTRUCTION
Conductors
Stranded, Concentric-Lay Aluminum 1350 Series Conductors with Steel Support Center Wire(s) per ASTM B232
Assembly
ACSR bare overhead supporting neutrals are concentric-lay-stranded conductors with a single steel core wire or stranded steel core wires surrounded by one
or more layers of helically applied aluminum alloy 1350 wires. Outer layer has right-handed lay.
APPLICATIONS
Suitable for overhead transmission and distribution applications that require rated strengths for steel support. Encore's ACSR overhead neutrals include Class AA for bare conductors
commonly used in overhead lines, and/or Class A for conductors to be covered with weather-resistant materials.
Please inquire about availability on sizes and constructions not listed below.
➊
➊Aluminum Coated Steel Reinforced (ACSR), 1350 Series Alloy
➋Steel Support Center Wire
➋
ACSR BARE OVERHEAD SERVICE DROP NEUTRAL
ACSR - ALUMINUM CONDUCTOR STEEL REINFORCED - 1350 SERIES ALLOY WITH STEEL SUPPORT CENTER WIRE
Conductor
Sizes
Nominal
Diameters
Strands
Code Name KCMIL AWG (Alum/Stl) Class
Turkey
Swan
Swanate
Sparrow
Sparate
Robin
Raven
Quail
Pigeon
Penguin
Waxwing
Merlin
Chickadee
Pelican
Osprey
Kingbird
Coot
Skylark
26.24
41.40
41.74
66.36
66.36
83.69
105.60
133.10
167.80
211.60
266.80
336.40
397.50
477.00
556.20
636.00
795.00
1272.00
6
4
4
2
2
1
1/0
2/0
3/0
4/0
-
6/1
6/1
7/1
6/1
7/1
6/1
6/1
6/1
6/1
6/1
18/1
18/1
18/1
18/1
18/1
18/1
36/1
36/1
AA, A
AA, A
AA, A
AA, A
AA, A
AA, A
AA, A
AA, A
AA, A
AA, A
AA
AA
AA
AA
AA
AA
AA
AA
Alum
Diam
Steel
Diam
0.0661
0.0834
0.0772
0.1052
0.0974
0.1181
0.1327
0.1489
0.1672
0.1878
0.1217
0.1367
0.1486
0.1628
0.1758
0.1880
0.1486
0.1880
0.0661
0.0834
0.1029
0.1052
0.1299
0.1181
0.1327
0.1489
0.1672
0.1878
0.1217
0.1367
0.1486
0.1628
0.1758
0.1880
0.1486
0.1880
Content %
of Weight
Finished Alum Steel
OD
%
%
0.198
0.250
0.257
0.316
0.325
0.354
0.398
0.447
0.502
0.563
0.609
0.684
0.743
0.814
0.879
0.940
1.040
1.316
67.8
67.9
58.2
67.9
58.1
67.9
67.9
67.9
67.9
67.9
86.4
86.4
86.4
86.4
86.4
86.4
92.7
92.7
32.2
32.1
41.8
32.1
41.9
32.1
32.1
32.1
32.1
32.1
13.6
13.6
13.6
13.6
13.6
13.6
7.3
7.3
Approximate Rated
Net Weight Strength
(lbs/1000 ft)
(lbs)
36
57
67
91
107
115
145
183
231
291
289
365
431
517
603
690
804
1286
1190
1860
2360
2850
3640
3550
4380
5300
6620
8350
6880
8700
9900
11800
13700
15700
16800
26400
Resistance
DC Resistance at 20C
AC Resistance at 60 Hz
(Ohms/1000 ft)
Reactance
25°C / @ 60 Hz
1ft. equiv. spacing
(Megohms/1000 ft)
DC
20°C
AC
25°C
AC
50°C
AC
50°C
Capacitive
Inductive
Ampacity
(amps)
0.642
0.403
0.399
0.253
0.251
0.201
0.159
0.127
0.100
0.080
0.0644
0.0510
0.0432
0.0360
0.0309
0.0269
0.0217
0.0135
0.655
0.412
0.407
0.259
0.256
0.206
0.163
0.130
0.103
0.082
0.0657
0.0523
0.0443
0.0369
0.0318
0.0278
0.0225
0.0145
0.750
0.479
0.463
0.308
0.297
0.247
0.197
0.162
0.121
0.107
0.0723
0.0574
0.0487
0.0405
0.0348
0.0306
0.0247
0.0159
0.816
0.522
0.517
0.336
0.330
0.270
0.216
0.176
0.145
0.116
0.0788
0.0625
0.0528
0.0441
0.0379
0.0332
0.0268
0.0173
0.751
0.715
0.710
0.679
0.674
0.660
0.642
0.624
0.606
0.597
0.576
0.560
0.544
0.528
0.518
0.507
0.492
0.455
0.1201
0.1152
0.1153
0.1100
0.1081
0.1068
0.1040
0.1017
0.0992
0.0964
0.0934
0.0877
0.0856
0.0835
0.0818
0.0805
0.0780
0.0720
105
140
140
185
185
210
240
275
315
365
445
515
575
640
710
773
884
1084
DC Resistance based on 16.95 Ohms-cmil/ft (20°C); 61.20% IACS for EC-1350; 8% of ACS for steel
AC Resistance at 60Hz
Ampacity based on 75°C conductor temp; 25°C ambient temp; 0.5 coefficients emissivity and absorption; 2ft./sec wind; 96 watts /sq. ft sun
50
800.962.9473 www.encorewire.com
TYPE duplex - EC-1350 SERIES ALUMINUM - overhead service DROP - 600V
ACSR - ALUMINUM CONDUCTOR STEEL REINFORCED supporting neutral
Engineering Specifications:
Standards:
ANSI/ICEA S-76-474; ASTM B233; ASTM B836; ASTM B232; ARRA 2009 Section 1605 “Buy American” Compliant.
Construction:
Conductors:
Insulated Conductor: Compact Stranded Conductors, Aluminum Alloy 1350 Series per ASTM B230; ASTM B609; ASTM B231; ASTM B836.
Neutral Conductor: Stranded Aluminum Conductor Steel Reinforced (ACSR), 1350 Series Alloy Bare Supporting Neutral with Steel Support Center Wire
per ASTM B230; ASTM B232.
Insulation:
Cross-link polyethylene (XLPE) black insulation per ANSI/ICEA S-76-474, rated 90°C wet or dry.
Applications:
Duplex overhead service drop cable with ACSR 1350 Series alloy supporting neutral is designed for applications not exceeding 600 volts with a maximum conductor operating
temperature of 90°C wet or dry. Primarily used for delivering single phase power from secondary power lines or pole mounted transformers to service entrance heads of a building or
structure. Suitable for 120 volt aerial service for outdoor lighting or for temporary service at construction sites.
Features:
Duplex overhead service drop cable has one black XLPE insulated aluminum conductor cabled around a bare stranded ACSR 1350 Series alloy supporting neutral with steel support
center wire. Superior weather-, abrasion-, crush-, and sunlight-resistant XLPE insulation rated 90°C operation wet or dry. Manufactured and tested according to ANSI/ICEA S-76-474:
Standard for Neutral Supported Power Cable Assemblies with Weather-Resistant Extruded Insulations Rated 600 Volts. Insulated conductor is surface printed for identification.
➊
➊XLPE Insulation
➋Compact Stranded Conductor, EC-1350 Series
➌Aluminum Conductor Steel Reinforced Supporting Neutral (ACSR),
➋
EC-1350 Series
➍Steel Support Center Wire
➍
➌
TYPE DUPLEX- EC-1350 SERIES ALUMINUM - OVERHEAD SERVICE DROP - 600V
ACSR - ALUMINUM CONDUCTOR STEEL REINFORCED SUPPORTING NEUTRAL
Phase Conductors
Code Word
Conductor
Sizes
(AWG)
Shepard
Terrier
Chow
Bull
6-6
4-4
2-2
1/0-1/0
Bare Neutral Conductor
Insulation Outside
Size
No. of Thickness Diameter
(AWG) Strands
(in)
(in)
6
4
2
1/0
7
7
7
10
0.045
0.045
0.045
0.060
0.259
0.303
0.358
0.456
Type
Size
(AWG)
ACSR
ACSR
ACSR
ACSR
6
4
2
1/0
Diameter of
Final
Approximate
Rated Finished
*Ampacity Construction Net Weight
No. of Strength
OD
(XLPE)
(in)
(lbs/1000 ft)
Strands
(lbs)
(in)
6+1
6+1
6+1
6+1
1190
1860
2850
4380
0.198
0.250
0.316
0.398
110
145
195
260
0.457
0.553
0.674
0.854
75
110
180
280
Standard
Packaging
Reels
(ft)
500' 1000' 1500'
500' 1000' 1500'
500' 1000' 1500'
500' 1000' 1500'
*Ampacities shown are for non-NEC applications and are based on the following factors:
a) conductor temperature of 65°C over 25°C ambient temperature
b) 2 ft./sec crosswind
c) .9 coefficient of emissivity, no sun
For NEC® type applications, consult appropriate NEC ampacity section.
The above data is approximate and subject to normal manufacturing tolerances.
Print Legend: ENCORE WIRE CORP (SIZE) AWG EC-1350 AL CDR XLPE SUN RES 600 VOLT DATE/TIME/OPERATOR/QC
800.962.9473 www.encorewire.com
51
TYPE TRIplex - EC-1350 SERIES aluminum - overhead service DROP - 600V
ACSR - ALUMINUM CONDUCTOR STEEL REINFORCED supporting neutral
Engineering Specifications:
Standards:
ANSI/ICEA S-76-474; ASTM B233; ASTM B836; ASTM B232; ARRA 2009 Section 1605 “Buy American” Compliant.
Construction:
Conductors:
Insulated Conductors: Compact Stranded Aluminum Alloy 1350 Series per ASTM B230; ASTM B609; ASTM B231; ASTM B836.
Neutral Conductor: Stranded Aluminum Conductor Steel Reinforced (ACSR), 1350 Series Alloy Bare Supporting Neutral with Steel Support Center Wire
per ASTM B230; ASTM B232.
Insulation:
Cross-link polyethylene (XLPE) black insulation per ANSI/ICEA S-76-474, rated 90°C wet or dry.
Applications:
Triplex overhead service drop cable with ACSR 1350 Series alloy supporting neutral is designed for applications not exceeding 600 volts with a maximum conductor operating
temperature of 90°C wet or dry. Primarily used for delivering single phase power from secondary power lines or pole mounted transformers to service entrance heads of a building or
structure. Suitable for 120 volt aerial service for outdoor lighting or for temporary service at construction sites.
Features:
Triplex overhead service drop cable has two black XLPE insulated aluminum conductors cabled around a bare stranded ACSR 1350 Series alloy supporting neutral with steel support
center wire. Superior weather-, abrasion-, crush-, and sunlight-resistant XLPE insulation rated 90°C operation wet or dry. Manufactured and tested according to ANSI/ICEA S-76-474:
Standard for Neutral Supported Power Cable Assemblies with Weather-Resistant Extruded Insulations Rated 600 Volts. Insulated conductors are surface printed for identification.
➌
➊XLPE Insulation
➋Compact Stranded Conductor, EC-1350 Series
➌Aluminum Conductor Steel Reinforced Supporting Neutral (ACSR),
➍
EC-1350 Series
➍Steel Support Center Wire
➋
➊
TYPE TRIPLEX - EC-1350 SERIES ALUMINUM - OVERHEAD SERVICE DROP - 600V
ACSR - ALUMINUM CONDUCTOR STEEL REINFORCED SUPPORTING NEUTRAL
Phase Conductors
Code Word
Conductor
Sizes
(AWG)
Voluta
Strombus
Periwinkle
Cockle
Conch
Janthina
Clio
Neritina
Runcina
Aega
Mursia
Cerapsus
Zuzara
6-6-6
4-4-6
4-4-4
2-2-4
2-2-2
1/0-1/0-2
2/0-2/0-1
1/0-1/0-1/0
2/0-2/0-2/0
3/0-3/0-1/0
3/0-3/0-3/0
4/0-4/0-2/0
4/0-4/0-4/0
Bare Neutral Conductor
XLPE
Outside
Size
No. of Thickness Diameter
(AWG) Strands
(in)
(in)
6
4
4
2
2
1/0
2/0
1/0
2/0
3/0
3/0
4/0
4/0
7
7
7
7
7
10
12
10
12
15
15
19
19
0.045
0.045
0.045
0.045
0.045
0.060
0.060
0.060
0.060
0.060
0.060
0.060
0.060
0.259
0.303
0.303
0.358
0.358
0.456
0.496
0.456
0.496
0.543
0.543
0.595
0.595
Type
Size
(AWG)
ACSR
ACSR
ACSR
ACSR
ACSR
ACSR
ACSR
ACSR
ACSR
ACSR
ACSR
ACSR
ACSR
6
6
4
4
2
2
1
1/0
2/0
1/0
3/0
2/0
4/0
Diameter of
Final
Approximate
Rated Finished
*Ampacity Construction Net Weight
No. of Strength
OD
(XLPE)
(in)
(lbs/1000 ft)
Strands
(lbs)
(in)
6+1
6+1
6+1
6+1
6+1
6+1
6+1
6+1
6+1
6+1
6+1
6+1
6+1
1190
1190
1860
1860
2850
2850
3550
4380
5300
4380
6620
5300
8350
0.198
0.198
0.250
0.250
0.316
0.316
0.354
0.398
0.447
0.398
0.502
0.447
0.563
110
115
115
150
150
200
230
200
230
350
350
405
405
0.558
0.648
0.653
0.761
0.771
0.967
1.052
0.980
1.066
1.151
1.167
1.261
1.279
105
160
175
230
270
375
450
430
520
560
645
690
800
Standard
Packaging
Reels
(ft)
500' 1000' 1500'
500' 1000' 1500'
500' 1000' 1500'
500' 1000' 1500'
500' 1000' 1500'
500' 1000' 1500'
500' 1000' 1500'
500' 1000' 1500'
500' 1000' 1500'
500' 1000' 1500'
500' 1000' 1500'
500' 1000' 1500'
500' 1000' 1500'
*Ampacities shown are for non-NEC applications and are based on the following factors:
a) conductor temperature of 65°C over 25°C ambient temperature
b) 2 ft./sec crosswind
c) .9 coefficient of emissivity, no sun
For NEC® type applications, consult appropriate NEC ampacity section.
The above data is approximate and subject to normal manufacturing tolerances.
Print Legend: ENCORE WIRE CORP (SIZE) AWG EC-1350 AL CDR XLPE SUN RES 600 VOLT DATE/TIME/OPERATOR/QC
52
800.962.9473 www.encorewire.com
TYPE QUADRUPLEx - EC-1350 SERIES Aluminum - overhead service DROP - 600V
ACSR - ALUMINUM CONDUCTOR STEEL REINFORCED SUPPORTING NEUTRAL
Engineering Specifications:
Standards:
ANSI/ICEA S-76-474; ASTM B233; ASTM B836; ASTM B232; ARRA 2009 Section 1605 “Buy American” Compliant.
Construction:
Conductors:
Insulated Conductors: Compact Stranded Conductors, Aluminum Alloy 1350 Series per ASTM B230; ASTM B609; ASTM B231; ASTM B836.
Neutral Conductor: Stranded Aluminum Conductor Steel Reinforced (ACSR), 1350 Series Alloy Bare Supporting Neutral with Steel Support Center Wire
per ASTM B230; ASTM B232.
Insulation:
Cross-link polyethylene (XLPE) black insulation per ANSI/ICEA S-76-474, rated 90°C wet or dry.
Applications:
Quadruplex overhead service drop cable with ACSR 1350 Series alloy supporting neutral is designed for applications not exceeding 600 volts with a maximum conductor operating
temperature of 90°C wet or dry. Primarily used for delivering single phase power from secondary power lines or pole mounted transformers to service entrance heads of a building or
structure. Suitable for 120 volt aerial service for outdoor lighting or for temporary service at construction sites.
Features:
Quadruplex overhead service drop cable has three black XLPE insulated aluminum conductors cabled around a bare stranded ACSR 1350 Series alloy supporting neutral with steel support
center wire. Superior weather-, abrasion-, crush-, and sunlight-resistant XLPE insulation rated 90°C operation wet or dry. Manufactured and tested according to ANSI/ICEA S-76-474:
Standard for Neutral Supported Power Cable Assemblies with Weather-Resistant Extruded Insulations Rated 600 Volts. Insulated conductors are surface printed for identification.
➌
➍
➊XLPE Insulation
➋Compact Stranded Conductor EC-1350 Series
➌ Aluminum Conductor Steel Reinforced Supporting Neutral
(ACSR), EC-1350 Series
➍Steel Support Center Wire
➋
➊
TYPE QUADRUPLEX - EC-1350 SERIES ALUMINUM - OVERHEAD SERVICE DROP - 600V
ACSR - ALUMINUM CONDUCTOR STEEL REINFORCED SUPPORTING NEUTRAL
Phase Conductors
Code Word
Conductor
Sizes
(AWG)
XLPE
Outside
Size
No. of Thickness Diameter
(AWG) Strands
(in)
(in)
Bare Neutral Conductor
Type
Chola
6-6-6-6
6
7
0.045
0.259
ACSR
Hackney
4-4-4-4
4
7
0.045
0.303
ACSR
Palomino
2-2-2-2
2
7
0.045
0.358
ACSR
Costena
1/0-1/0-1/0-1/0 1/0
10
0.060
0.456
ACSR
Grullo
2/0-2/0-2/0-2/0 2/0
12
0.060
0.496
ACSR
Suffolk
3/0-3/0-3/0-3/0 3/0
15
0.060
0.543
ACSR
Appaloosa 4/0-4/0-4/0-4/0 4/0
19
0.060
0.595
ACSR
*Ampacities shown are for non-NEC applications and are based on the following factors:
a) conductor temperature of 65°C over 25°C ambient temperature
b) 2 ft./sec crosswind
c) .9 coefficient of emissivity, no sun
For NEC® type applications, consult appropriate NEC ampacity section.
The above data is approximate and subject to normal manufacturing tolerances.
Size
(AWG)
6
4
2
1/0
2/0
3/0
4/0
Rated Finished
No. of Strength
OD
Strands
(lbs)
(in)
6+1
6+1
6+1
6+1
6+1
6+1
6+1
1190
1860
2850
4380
5300
6620
8350
0.198
0.250
0.316
0.398
0.447
0.502
0.563
Diameter of
Final
Approximate
Ampacity Construction Net Weight
(XLPE)
(in)
(lbs/1000 ft)
105
135
175
240
280
325
375
0.623
0.729
0.861
1.097
1.193
1.306
1.431
150
215
350
560
690
850
1060
Standard
Packaging
Reels
(ft)
500' 1000' 1500'
500' 1000' 1500'
500' 1000' 1500'
500' 1000' 1500'
500' 1000' 1500'
500' 1000' 1500'
500' 1000' 1500'
Print Legend: ENCORE WIRE CORP (SIZE) AWG EC-1350 AL CDR XLPE SUN RES 600 VOLT DATE/TIME/OPERATOR/QC
800.962.9473 www.encorewire.com
53
AAAC BARE OVERHEAD SUPPORTING NEUTRAL
AAAC - ALL ALUMINUM ALLOY CONDUCTOR - 6201 ALLOY
Engineering Specifications:
Standards:
ASTM B398: Standard Specification for Aluminum-Alloy 6201-T81 Wire for Electrical Purposes.
ASTM B399: Standard Specification for Concentric-Lay-Stranded Aluminum-Alloy 6201-T81 Conductors.
Construction:
Conductors:
Stranded, Concentric-Lay Aluminum Alloy 6201 Conductors per ASTM B399.
Assembly:
AAAC bare overhead supporting neutrals are concentric-lay-stranded aluminum alloy 6201-T81 conductors in one or more layers wrapped helically around a central core.
Outer layer has right-handed lay.
Applications:
Suitable for overhead transmission and distribution applications that require rated strengths for 6201 alloy at a T81 temper. Encore's AAAC overhead neutrals include Class AA for bare
conductors usually used in overhead lines, and/or Class A for conductors to be covered with weather-resistant materials.
Please inquire about availability on sizes and constructions not listed below.
➊Concentric Stranded AAAC 6201 Alloy Supporting Neutral
AAAC BARE OVERHEAD SUPPORTING NEUTRAL
AAAC - ALL ALUMINUM ALLOY CONDUCTOR - 6201 ALLOY
Nominal
Diameters
Conductor Sizes
Code
Word
Akron
Alton
Ames
Azusa
Anaheim
Amherst
Alliance
Butte
Canton
Cairo
Darien
Elgin
Flint
Greely
Area
KCMIL (mm²)
30.58
48.69
77.47
123.30
155.40
195.70
246.90
312.80
394.50
465.40
559.50
652.40
740.80
927.20
15.5
24.7
33.6
62.4
78.6
99.3
125.0
159.0
200.0
236.0
522.0
331.0
375.0
470.0
Area
(in²)
0.0240
0.0382
0.0608
0.0968
0.1221
0.1537
0.1939
0.2456
0.3099
0.3655
0.4394
0.5124
0.5818
0.7282
No. of
Strands Class
7
7
7
7
7
7
7
19
19
19
19
19
37
37
A
A
AA, A
AA, A
AA, A
AA, A
AA
A
AA, A
AA
AA
AA
AA
AA
Resistance
DC Resistance at 20C
AC Resistance at 60 Hz
(Ohms/1000ft)
AAC 1350
Cdr Size with
Equivalent
Each Finished Approximate Rated
Net Weight Strength Resistance
Strand
OD
(lbs/1000 ft)
(lbs)
(AWG/KCMIL)
(in)
(in)
DC
20°C
AC
25°C
AC
50°C
AC
50°C
0.0661
0.0834
0.1052
0.1327
0.1490
0.1672
0.1878
0.1283
0.1441
0.1565
0.1716
0.1853
0.1415
0.1583
0.6589
0.4138
0.2600
0.1635
0.1297
0.1030
0.0816
0.0644
0.0511
0.0433
0.0360
0.0309
0.0272
0.0217
0.6700
0.4200
0.2650
0.1660
0.1320
0.1050
0.0831
0.0657
0.0523
0.0443
0.0369
0.0318
0.0280
0.0225
0.7270
0.4560
0.2880
0.1800
0.1430
0.1140
0.0902
0.0712
0.0566
0.0481
0.0400
0.0345
0.0305
0.0244
0.7840
0.4920
0.3110
0.1950
0.1550
0.1230
0.0973
0.0769
0.0610
0.0517
0.0431
0.0371
0.0328
0.0263
0.198
0.250
0.316
0.396
0.447
0.502
0.563
0.642
0.721
0.783
0.858
0.927
0.991
1.108
29
45
72
115
145
183
230
292
368
434
522
608
691
865
1110
1760
2800
4270
5390
6790
8560
10500
13300
15600
18800
21900
24400
30500
6
4
2
1/0
2/0
3/0
4/0
266.80
336.40
397.50
477.00
556.50
636.00
795.00
Reactance
25°C / @ 60 Hz
1 ft. equiv. spacing
(Megohms/1000ft)
Capacitive Inductive
0.7510
0.7150
0.6780
0.6420
0.6240
0.6060
0.5880
0.5670
0.5490
0.5360
0.5220
0.5100
0.4990
0.4820
0.1180
0.1120
0.1070
0.1020
0.0989
0.0963
0.0936
0.0896
0.0870
0.0851
0.0829
0.0812
0.0793
0.0768
DC Resistance based on 19.76 Ohms-cmil/ft (20°C); 52.5% IACS.
AC Resistance at 60Hz.
Ampacity based on 75°C conductor temp; 25°C ambient temp; 0.5 coefficients emissivity and absorption; 2ft./sec wind in sun.
54
800.962.9473 www.encorewire.com
Ampacity
(Amps)
107
143
191
256
296
342
395
460
532
590
663
729
790
908
TYPE duplex - EC-1350 SERIES aLUMINUM - overhead service DROP - 600V
AAAC - aluminum conductor 6201 alloy supporting NEUTRAL
Engineering Specifications:
Standards:
ANSI/ICEA S-76-474; ASTM B233; ASTM B836; ASTM B399; ARRA 2009/FAR Subpart 25.6 “Buy American” Compliant.
Construction:
Conductors:
Insulated Conductor: Compact Stranded Conductors, Aluminum Alloy 1350 Series per ASTM B230; ASTM B609; ASTM B231; ASTM B836.
Neutral Conductor: Stranded Aluminum 6201 Alloy Conductor (AAAC) Bare Supporting Neutral per ASTM B398; ASTM B399.
Insulation:
Cross-link polyethylene (XLPE) black insulation per ANSI/ICEA S-76-474, rated 90°C wet or dry.
Applications:
Duplex overhead service drop cable with bare stranded AAAC 6201 aluminum alloy supporting neutral is designed for applications not exceeding 600 volts with a maximum conductor
operating temperature of 90°C wet or dry. Primarily used for delivering single phase power from secondary power lines or pole mounted transformers to service entrance heads of a
building or structure. Suitable for 120 volt aerial service for outdoor lighting or for temporary service at construction sites.
Features:
Duplex overhead service drop cable has one black XLPE insulated aluminum conductor cabled around a bare stranded AAAC 6201 aluminum alloy supporting neutral. Superior weather-,
abrasion-, crush-, and sunlight-resistant XLPE insulation rated 90°C operation wet or dry. Manufactured and tested according to ANSI/ICEA S-76-474: Standard for Neutral Supported
Power Cable Assemblies with Weather-Resistant Extruded Insulations Rated 600 Volts. Insulated conductor is surface printed for identification.
➊
➊XLPE Insulation
➋Compact Stranded Conductor, EC-1350 Series
➌Concentric Stranded AAAC 6201 Alloy Supporting Neutral
➋
➌
TYPE DUPLEX - EC-1350 SERIES ALUMINUM - OVERHEAD SERVICE DROP - 600V
AAAC - ALUMINUM CONDUCTOR 6201 ALLOY SUPPORTING NEUTRAL
Phase Conductors
Bare Neutral Conductor
Conductor
Insulation Outside
Sizes
Size
No. of Thickness Diameter
Code Word
(AWG)
(AWG) Strands
(in)
(in)
Vizsla
Whippet
Schnauzer
Heeler
6-6
4-4
2-2
1/0-1/0
6
4
2
1/0
7
7
7
10
0.045
0.045
0.045
0.060
0.259
0.303
0.358
0.456
Type
6201
6201
6201
6201
Size
Size
No. of
(AWG) (KCMIL) Strands
6
4
2
1/0
30.58
48.69
77.47
123.3
7
7
7
7
Rated
Strength
(lbs)
1110
1760
2800
4270
Diameter of
Final
Approximate
Finished
*Ampacity Construction Net Weight
OD
(XLPE)
(in)
(lbs/1000 ft)
(in)
0.198
0.250
0.316
0.398
110
145
195
260
0.462
0.558
0.679
0.864
68
102
156
249
Standard
Packaging
Reels
(ft)
500' 1000' 1500'
500' 1000' 1500'
500' 1000' 1500'
500' 1000' 1500'
*Ampacities shown are for non-NEC applications and are based on the following factors:
a) conductor temperature of 65°C over 25°C ambient temperature
b) 2 ft./sec crosswind
c) .9 coefficient of emissivity, no sun
For NEC® type applications, consult appropriate NEC ampacity section.
The above data is approximate and subject to normal manufacturing tolerances.
Print Legend: ENCORE WIRE CORP (SIZE) AWG EC-1350 AL CDR XLPE SUN RES 600 VOLT DATE/TIME/OPERATOR/QC
800.962.9473 www.encorewire.com
55
TYPE TRIplex - EC-1350 SERIES aluminum - overhead service DROP - 600V
AAAC - aluminum conductor 6201 alloy supporting neutral
Engineering Specifications:
Standards:
ANSI/ICEA S-76-474; ASTM B233; ASTM B836; ASTM B399; ARRA 2009 Section 1605 “Buy American” Compliant.
Construction:
Conductors:
Insulated Conductors: Compact Stranded Conductors, Aluminum Alloy 1350 Series per ASTM B230; ASTM B609; ASTM B231; ASTM B836.
Neutral Conductor: Stranded Aluminum 6201 Alloy Conductor (AAAC) Bare Supporting Neutral per ASTM B398; ASTM B399.
Insulation:
Cross-link polyethylene (XLPE) black insulation per ANSI/ICEA S-76-474, rated 90°C wet or dry.
Applications:
Triplex overhead service drop cable with bare stranded AAAC 6201 aluminum alloy supporting neutral is designed for applications not exceeding 600 volts with a maximum conductor
operating temperature of 90°C wet or dry. Primarily used for delivering single phase power from secondary power lines or pole mounted transformers to service entrance heads of a
building or structure. Suitable for 120 volt aerial service for outdoor lighting or for temporary service at construction sites.
Features:
Triplex overhead service drop cable has two black XLPE insulated aluminum conductors cabled around a bare stranded AAAC 6201 aluminum alloy supporting neutral. Superior weather-,
abrasion-, crush-, and sunlight-resistant XLPE insulation rated 90°C operation wet or dry. Manufactured and tested according to ANSI/ICEA S-76-474: Stranded For Neutral/Supported
Power Cable Assemblies With Weather-Resistant Extended Insulations Rated 600 Volts. Insulated conductors are surface printed for identification.
➌
➊XLPE Insulation
➋Compact Stranded Conductor, EC-1350 Series
➌Concentric Stranded AAAC 6201 Alloy Supporting Neutral
➋
➊
TYPE TRIPLEX - EC-1350 SERIES ALUMINUM - OVERHEAD SERVICE DROP - 600V
AAAC - ALUMINUM CONDUCTOR 6201 ALLOY SUPPORTING NEUTRAL
Phase Conductors
Bare Neutral Conductor
Conductor
Insulation Outside
Sizes
Size
No. of Thickness Diameter
Code Word
(AWG)
(AWG) Strands
(in)
(in)
Type
Hippa
Crab
Barnacles
Solaster
Shrimp
Echinus
Leda
Dungenese
Cyclops
Fulgar
Flustra
Arca
Lepas
6201
6201
6201
6201
6201
6201
6201
6201
6201
6201
6201
6201
6201
6-6-6
4-4-6
4-4-4
2-2-4
2-2-2
1/0-1/0-2
1/0-1/0-1/0
2/0-2/0-2/0
2/0-2/0-2/0
3/0-3/0-1/0
3/0-3/0-3/0
4/0-4/0-2/0
4/0-4/0-4/0
6
4
4
2
2
1/0
1/0
2/0
2/0
3/0
3/0
4/0
4/0
7
7
7
7
7
10
10
12
12
15
15
19
19
0.045
0.045
0.045
0.045
0.045
0.060
0.060
0.060
0.060
0.060
0.060
0.060
0.060
0.259
0.303
0.303
0.358
0.358
0.456
0.456
0.496
0.496
0.543
0.543
0.595
0.595
Diameter of
Final
Approximate
Rated Finished
*Ampacity Construction Net Weight
Size
Size
No. of Strength
OD
(XLPE)
(in)
(lbs/1000 ft)
(AWG) (KCMIL) Strands
(lbs)
(in)
6
6
4
4
2
2
1/0
2/0
2/0
1/0
3/0
2/0
4/0
30.58
30.58
48.69
48.69
77.47
77.47
123.3
155.4
155.4
123.3
195.7
155.4
246.9
7
7
7
7
7
7
7
7
7
7
7
7
7
1110
1110
1760
1760
2800
2800
4280
5390
5390
4280
6790
5390
8560
0.198
0.198
0.250
0.250
0.316
0.316
0.398
0.447
0.447
0.398
0.502
0.447
0.563
110
145
145
195
195
260
260
300
300
350
350
405
405
0.581
0.678
0.678
0.797
0.797
1.009
1.009
1.097
1.097
1.197
1.197
1.313
1.313
106
140
157
210
237
338
381
469
469
513
581
633
719
Standard
Packaging
Reels
(ft)
500' 1000' 1500'
500' 1000' 1500'
500' 1000' 1500'
500' 1000' 1500'
500' 1000' 1500'
500' 1000' 1500'
500' 1000' 1500'
500' 1000' 1500'
500' 1000' 1500'
500' 1000' 1500'
500' 1000' 1500'
500' 1000' 1500'
500' 1000' 1500'
*Ampacities shown are for non-NEC applications and are based on the following factors:
a) conductor temperature of 65°C over 25°C ambient temperature
b) 2 ft./sec crosswind
c) .9 coefficient of emissivity, no sun
For NEC® type applications, consult appropriate NEC ampacity section.
The above data is approximate and subject to normal manufacturing tolerances.
Print Legend: ENCORE WIRE CORP (SIZE) AWG EC-1350 AL CDR XLPE SUN RES 600 VOLT DATE/TIME/OPERATOR/QC
56
800.962.9473 www.encorewire.com
TYPE QUADRUPLEX - ec-1350 Series aluminum - overhead service DROP - 600v
AAAC - ALUMINUM CONDUCTOR 6201 ALLOY SUPPORTING NEUTRAL
Engineering Specifications:
Standards:
ANSI/ICEA S-76-474; ASTM B233; ASTM B836; ASTM B399; ARRA 2009 Section 1605 “Buy American” Compliant.
Construction:
Conductors:
Insulated Conductors: Compact Stranded Conductors, Aluminum Alloy 1350 Series per ASTM B230; ASTM B609; ASTM B231; ASTM B836.
Neutral Conductor: Stranded Aluminum 6201 Alloy Conductor (AAAC) Bare Supporting Neutral per ASTM B398; ASTM B399.
Insulation:
Cross-link polyethylene (XLPE) black insulation per ANSI/ICEA S-76-474, rated 90°C wet or dry.
Applications:
Quadruplex overhead service drop cable with bare stranded AAAC 6201 aluminum alloy supporting neutral is designed for applications not exceeding 600 volts with
a maximum conductor operating temperature of 90°C wet or dry. Primarily used for delivering single phase power from secondary power lines or pole mounted
transformers to service entrance heads of a building or structure. Suitable for 120 volt aerial service for outdoor lighting or for temporary service at construction sites.
Features:
Quadruplex overhead service drop cable has three black XLPE insulated aluminum conductors cabled around a bare stranded AAAC 6201 aluminum alloy supporting
neutral. Superior weather-, abrasion-, crush-, and sunlight-resistant XLPE insulation rated 90°C operation wet or dry. Manufactured and tested according to ANSI/
ICEA S-76-474: Standard for Neutral Supported Power Cable Assemblies with Weather-Resistant Extruded Insulations Rated 600 Volts. Insulated conductors are surface printed for
identification.
➌
➊XLPE Insulation
➋Compact Stranded Conductor, EC-1350 Series
➌Concentric Stranded AAAC 6201 Alloy Supporting Neutral
➋
➊
TYPE QUADRUPLEX - EC-1350 SERIES ALUMINUM - OVERHEAD SERVICE DROP - 600V
AAAC - ALUMINUM CONDUCTOR 6201 ALLOY SUPPORTING NEUTRAL
Phase Conductors
Code Word
Conductor
Sizes
(AWG)
French-Coat
Arabian
Belgian
Shetland
Thoroughbred
Trotter
Walking
6-6-6-6
4-4-4-4
2-2-2-2
1/0-1/0-1/0-1/0
2/0-2/0-2/0-2/0
3/0-3/0-3/0-3/0
4/0-4/0-4/0-4/0
Bare Neutral Conductor
Insulation Outside
Size
No. of Thickness Diameter
(AWG) Strands
(in)
(in)
6
4
2
1/0
2/0
3/0
4/0
7
7
7
10
12
15
19
0.045
0.045
0.045
0.060
0.060
0.060
0.060
0.259
0.303
0.358
0.456
0.496
0.543
0.595
Type
6201
6201
6201
6201
6201
6201
6201
Size
Size
No. of
(AWG) (KCMIL) Strands
6
4
2
1/0
2/0
3/0
4/0
30.58
48.69
77.47
123.3
155.4
195.7
246.9
7
7
7
7
7
7
7
Rated
Strength
(lbs)
1110
1760
2800
4270
5390
6790
8560
Diameter of
Final
Approximate
Finished
*Ampacity Construction Net Weight
OD
(XLPE)
(in)
(lbs/1000 ft)
(in)
0.169
0.213
0.268
0.336
0.376
0.423
0.475
105
135
175
240
280
325
375
0.635
0.745
0.886
1.113
1.212
1.323
1.448
140
210
330
515
640
790
970
Standard
Packaging
Reels
(ft)
500' 1000' 1500'
500' 1000' 1500'
500' 1000' 1500'
500' 1000' 1500'
500' 1000' 1500'
500' 1000' 1500'
500' 1000' 1500'
*Ampacities shown are for non-NEC applications and are based on the following factors:
a) conductor temperature of 65°C over 25°C ambient temperature
b) 2 ft./sec crosswind
c) .9 coefficient of emissivity, no sun
For NEC® type applications, consult appropriate NEC ampacity section.
The above data is approximate and subject to normal manufacturing tolerances.
Print Legend: ENCORE WIRE CORP (SIZE) AWG EC-1350 AL CDR XLPE SUN RES 600 VOLT DATE/TIME/OPERATOR/QC
800.962.9473 www.encorewire.com
57

Similar documents

Overhead Line Conductors

Overhead Line Conductors The current rating mentioned above is based on ambient temp. of 50° C and max. conductor temp. of 80° C.

More information

Bare Overhead Conductors

Bare Overhead Conductors (AWG/kcmil) (ohm/kft) (ohm/kft) (ohm/kft) (ohm/kft) (megohm-kft) (ohm/kft) (ohm/kft)

More information