Firestop Submittal

Transcription

Firestop Submittal
Firestop Submittal
Perimeter/Curtain Wall Joints
Project Name:
Date:
Submitted by:
Tremco Incorporated
2628 Pearl Road
Medina, OH 44256
USA
Phone (330) 273-8828
For MSDS and Spec Data
Fax (330) 220-7075
Sheets, visit our Web site:
www.tremcofirestop.com Toll-Free (866) 209-2404
Tremco Limited
215 Wicksteed Ave.
Toronto, Ontario M4H 1G7
Canada
Phone (416) 421-3300
Fax (416) 361-3514
Toll-Free (800) 263-6046
Tremco Fire Protection Systems Group
Submittal for Firestopping of Curtain Wall Systems
Section 07840
Product Data Sheets
TREMstop Acrylic Spray
TREMstop Fyre-Sil Self Leveling
General Certificate of Conformance
Systems
System Name
CEJ 197P
Products
TREMstop Acrylic SP
CEJ 198P
TREMstop Acrylic SP
CEJ 204P
TREMstop Acrylic SP
CEJ 217P
TREMstop Acrylic SP
TL/PH 120-01
Fyre-Sil Self Leveling, TREMstop Acrylic SP
Penetrant Details
6” Joint (+/- 15% Movement); Conc Floor to
Curtain Wall (Continuous Conc Panel);
4" Mineral Wool
8” Joint (+/- 15% Movement); Conc Floor to
Curtain Wall (Stud Framed, Gyp Interior,
Metal Panel Exterior), 4" Mineral Wool
6” Joint (+/- 15% Movement); Conc Floor to
Curtain Wall (Glass Vision and Insulated Glass
Spandrel Panels), 4" Mineral Wool
6” Joint (+/- 10% Movement); Conc Floor to
Curtain Wall (Continuous Concrete Panel),
4" Mineral Wool
6” Joint; Conc Floor to Curtain Wall
(Steel Panel), 4" Mineral Wool
F Rating
1-1/2 hr.
2 hr.
2 hr.
2 hr.
2 hr.
MSDS Sheets
TREMstop Acrylic Spray
TREMstop Fyre-Sil Self Leveling
www.tremcofirestop.com
Technical Services: 866-209-2404
Tremco Fire Protection Systems Group
2628 Pearl Road Medina, OH 44256
TREMstop Acrylic Spray
Acrylic Firestopping Sealant
PRODUCT DESCRIPTION:
ADVANTAGES:
TREMstop Acrylic SP is a single component, water-based, acrylic firestop sealant.
TREMstop Acrylic SP is a high performance, elastomeric, anti-fungal sealant used
in joints with plus or minus 25 percent movement in a fire-rated joint. TREMstop
Acrylic is available in a gun grade that is compatible with the sprayable grade.
• Easily applied with high pressure
airless spray equipment, brush or
trowel
TREMstop Acrylic SP is a specially formulated acrylic for firestop applications.
TREMstop Acrylic SP is ideal for head-of-wall applications with long joint runs
where a sprayable sealant offers significant labor savings.
• Used in joints with plus or minus
25% movement in fire-rated joints
• Extremely useful for head-of-wall
applications, specifically long joint
runs where a sprayable sealant
offers significant labor savings
• Easy clean up with water
• Paintable when fully cured
• Listed for up to 6 inch joints
• Listed up to a 3 hour fire rating in
joints
BASIC USES:
Penetrations
• Steel, copper, iron, and EMT pipe
(in Canada only)
Building Assemblies
• Concrete wall or floor
• Gypsum wallboard
• Fluted metal deck
• Joints
• Curtain walls
PHYSICAL PROPERTIES:
Color:
White, limestone, rust red
pH:
7.0 – 9.0
Shore “A” Hardness: 15 – 20
(ASTM C-661)
VOC (grams/liter):
65
Application
Temperature
40°F – 110°F
(Min./Max.):
(5°C – 43°C)
Flame Spread:
15
(ASTM E-84)
Smoke Develop:
0
(ASTM E-84)
Cure Time:
3 – 5 days
(ASTM C-679)
Skin Over Time:
Overnight
Movement Capability: Tested to
(UL 2079; class I, II, III) ±25%
Sound Transmission
(STC Rating):
43
Shelf Life:
1 year
Freeze sensitive:
Yes
Accepts Paint:
Yes
PACKAGING:
5 gal. (19 L, 1155 in3) pail
TREMstop Acrylic Spray
TREMstop Acrylic Spray
Acrylic Firestopping Sealant
LIMITATIONS:
• Not recommended for passive fire
containment systems not listed or
approved by Tremco.
INSTALLATION
TECHNIQUES:
Refer to the Tremco Firestop Manual or
the UL/ULC Fire Resistance Directory
for specific application instructions.
APPLICABLE TEST
STANDARDS:
UL 1479 (ASTM E-814)
UL 263 (ASTM E-119)
UL 723 (ASTM E-84)
UL 2079 (ASTM E-1966)
ASTM E-1399
CAN4-S115M
CAN/ULC-S101M
WARRANTY:
RECOMMENDED SPRAY
EQUIPMENT
SPECIFICATIONS:
Pump: Graco® Ultra Max II® Premium
Hi-Boy
Motor: 2 hp/15 Amps
Pressure: 3,300 psi
Flow Rate: .95 GPM
Lines: 1/4 in. (I.D.) x 50 ft. Blue Max
1/4 in. (I.D.) x 6 ft. Whip Hose
Spray Tip: .019 - .023 for 4 in. fan width
.021 - .025 for 6 in. fan width
Tip size may vary depending on
conditions. Larger tip size may be used
for high production rates if the pump
can support it.
Tremco warrants its Firestop Materials to be
free of defects, but makes no warranty as to
appearance or color. Since methods of
application and on-site conditions are
beyond our control and can affect
performance, Tremco makes no other
warranty, expressed or implied, including
warranties of MERCHANTABILITY and
FITNESS FOR A PARTICULAR PURPOSE
with respect to Firestop Materials. Tremco’s
sole obligation shall be, at its option, to
replace or to refund the purchase price of
the quantity of the Firestop Materials proved
to be defective and Tremco shall not be
liable for any loss or damage.
TECHNICAL SERVICES
For more information, contact technical
services:
Toll free:
(866) 209-2404
Fax:
(330) 220-7055
E-mail:
[email protected]
O R DER PLA CEM ENT:
To place an order, contact customer
service:
United States: (800) 321-7906
Canada:
T H E
T R E M C O
F A M I L Y
O F
P R O D U C T S
I S
R E C O G N I Z E D
(800) 363-3213
B Y
Tremco Incorporated • 2628 Pearl Road • Medina, Ohio 44256 USA
Phone: (330) 273-8828 • Fax: (330) 220-7075 • Toll Free: (866) 209-2404
Tremco Canada Division • 25 Wicksteed Ave. • Toronto, Ontario M4H 1G7 Canada
Phone: (416) 467-2455 • Fax: (800) 361-3514 • Toll Free: (800) 363-3213
For MSDS or additional Spec Data Sheets, contact customer service at
(800) 321-7906 or visit www.tremcofirestop.com
FPSG062 7/04
TREMstop Silicone (Fyre-ssil)
Single Component, Silicone Firestopping Sealant
PRODUCT DESCRIPTION:
TREMstop Silicone is a single component, neutral cure, silicone firestopping
sealant. This elastomeric, high performance sealant is capable of plus or minus 25
percent movement in a fire-rated joint. TREMstop Silicone is available in selfleveling (SL) or non-sag gun grade (GG) formula for ASTM E-814 through
penetrations. TREMstop Silicone is tested for up to a four hour fire rating by
independent laboratories and is approved for both through penetrations and joint
applications. This high grade sealant is both water-tight and naturally fungalresistant.
TREMstop is approved by Agriculture Canada and Health and Welfare Canada for
use in food processing plants.
ADVANTAGES:
• Single component, neutral cure
silicone firestopping sealant
• Capable of plus or minus 25%
movement in a fire-rated joint
• Easy gunning
• Approved for both through
penetrations and joint applications
• Available in self-leveling (SL) or
gun grade (GG)
• Approved for use in food
processing facilities in Canada
• Naturally fungal-resistant and
water-tight
• Listed up to a 4 hour fire rating
BASIC USES:
Penetrations
• Steel, iron, copper and EMT pipe
• Fiberglass insulated pipe
• Jacketed cables and bundles
• Bus ducts
• Mixed penetrations
Building Assemblies
• Concrete wall or floor
• Gypsum wallboard
• Joints
• Curtain wall
• Hollowcore concrete
• Wood floor/ceiling
• Fluted Metal Deck
PHYSICAL PROPERTIES:
Color:
Limestone,
rust red
pH:
7.0 - 9.0
Shore “A” Hardness: 15
(ASTM C-661)
VOC (grams/liter):
0
Application
Temperature
40°F – 110°F
(Min./Max.):
(5°C – 43°C)
Flame Spread:
0
(ASTM E-84)
Smoke Develop:
15
(ASTM E-84)
Cure Time:
7 – 14 days
(ASTM C-679)
Skin Over Time:
Overnight
Movement Capability: Tested to ±25%
(UL 2079; class I, II, III)
Sound Transmission
(STC Rating):
53
Shelf Life:
1 year
Accepts Paint:
No
PACKAGING:
For gun grade:
10.1 fl. oz. (300 ml, 18 in3) cartridge
30/case
20 fl. oz. (600 ml, 36 in3) sausage
15/case
28.7 fl. oz. (850 ml, 51 in3) cartridge
12/case
4.5 gallon (17 L, 1040 in3) pail
For self-leveling:
20 fl. oz. (600 ml, 36 in3) sausage
15/case
28.7 fl. oz. (850 ml, 51 in3) cartridge
12/case
4.5 gallon (17 L, 1040 in3) pail
TREMstop Silicone (Fyre-Sil)
TREMstop Silicone (Fyre-ssil)
Single Component, Silicone Firestopping Sealant
LIMITATIONS:
• Not recommended for use in passive
fire containment systems not listed
or approved by Tremco.
• Do not apply over damp or
contaminated surfaces.
APPLICABLE TEST
STANDARDS:
UL 1479 (ASTM E-814)
UL 263 (ASTM E-119)
UL 723 (ASTM E-84)
UL 2079 (ASTM E-1966)
ASTM E-1399
CAN4-S115M
CAN/ULC-S101M
INSTALLATION
TECHNIQUES:
WARRANTY:
Refer to the TREMco Firestop Manual
or the UL/ULC Fire Resistance
Directory for specific application
instructions.
The firestop system details will cover
the required sealant depth, necessary
amount of packing material and the
permitted joint size or annular space.
TREMstop Silicone is a gunnable
sealant, typically applied using
conventional caulking equipment.
TREMstop self-leveling allows for easy
application in hard to reach spaces or
configurations.
Tremco warrants its Firestop Materials to be
free of defects, but makes no warranty as to
appearance or color. Since methods of
application and on-site conditions are
beyond our control and can affect
performance, Tremco makes no other
warranty, expressed or implied, including
warranties of MERCHANTABILITY and
FITNESS FOR A PARTICULAR PURPOSE
with respect to Firestop Materials. Tremco’s
sole obligation shall be, at its option, to
replace or to refund the purchase price of
the quantity of the Firestop Materials proved
to be defective and Tremco shall not be
liable for any loss or damage.
TECHNICAL SERVICES
For more information, contact technical
services:
Toll free:
(866) 209-2404
Fax:
(330) 220-7055
E-mail:
[email protected]
O R DER PLA CEM ENT:
To place an order, contact customer
service:
United States: (800) 321-7906
Canada:
T H E
T R E M C O
F A M I L Y
O F
P R O D U C T S
I S
R E C O G N I Z E D
(800) 363-3213
B Y
Tremco Incorporated • 2628 Pearl Road • Medina, Ohio 44256 USA
Phone: (330) 273-8828 • Fax: (330) 220-7075 • Toll Free: (866) 209-2404
Tremco Canada Division • 215 Wicksteed Ave. • Toronto, Ontario M4H 1G7 Canada
Phone: (416) 467-2455 • Fax: (800) 361-3514 • Toll Free: (800) 363-3213
For MSDS or additional Spec Data Sheets, contact customer service at
(800) 321-7906 or visit www.tremcofirestop.com
FPSG064 7/04
Tremco Incorporated
2628 Pearl Road – Medina, Ohio 44256 Toll Free: 866.209.2404
_______
____
________________________
Sealant/Weatherproofing Division
Fire Protection Systems Group
GENERAL CERTIFICATE OF CONFORMANCE
DESCRIPTION: TREMCO FIRE STOP PRODUCTS
TREMstop Acrylic
TREMstop IA
TREMstop PS1 & PS2
TREMstop D
TREMstop UniCollar
TREMstop Quickstop Coupling
TREMstop Quickstop Sleeve
TREMstop Strap
TREMstop Acrylic SP
TREMstop WS wrap strips
TREMstop Fire Mortar
TREMstop MP
TREMstop Anchor Solid
TREMstop Split Anchor
TREMstop Putty
Fyre-Sil
Fyre-Can Device/Fyre-Can TM
Fyre-Sil S/L
Fyre-Can sleeve
TREMstop FS Blanket
Blueskin
Dymonic FC
THC-900
Dymeric 240FC
Vulkem 45SSL
THESE PRODUCTS ARE TESTED TO ONE OR MORE OF THE FOLLOWING STANDARDS:
•
ASTM E-119 (UL 263)
Fire Tests of Building Construction and Materials Time-Temperature Curve
•
ASTM E-814 (UL 1479)
Fire Tests of Through-Penetration Fire Stops (under positive furnace pressure of
minimum .01 inches of water column - 2.5+ Pascal)
•
ASTM E-84 (UL 723)
Surface Burning Characteristics of Building Materials
•
UL 2079
Test for Fire Resistance of Building Joint Systems
No asbestos or PCB’s are used or contained in these products.
11/19/2004
Senior Technical Engineer
Date:
Design No. CEJ 197P
February 27, 2003
PERIMETER FIRE BARRIER SYSTEM
T-Rating - 3/4 hr.
F-Rating - 1-1/2 hr
L-Rating N/A
Rated for ± 15% movement
1. CONCRETE FLOOR ASSEMBLY:
Two-hour rated concrete floor assembly made from either lightweight or normal weight concrete with a density of 100-150 pcf, with a min.
thickness of 4-1/2 -in. at the joint face. Overall slab thickness may vary to accommodate various blockout depths (longitudinal recesses)
formed in the concrete, to house the architectural cover plate. The blockout width may also vary without restriction.
2. CURTAIN WALL ASSEMBLY: The concrete curtain wall assembly shall incorporate the following construction features:
A. Mounting Attachment: (Not shown) Attachment of the curtain wall framing to the structural framing shall be according to the curtain
wall manufacturer's instructions. If required, mounting attachments to the floor slab shall be connected to the joint face of the floor slab.
Max. distance between mounting attachments shall be 10 feet.
B. Steel-Stud Framing: Vertical framing members shall be a min. 3-5/8 in. by 1-5/8 in., 18 GA steel "C" studs. Attachment
shall be according to the curtain wall
system manufacturer's guidelines. Vertical framing not to exceed a spacing of 60 in. o.c. and shall be completely covered by the
concrete panels. If required, horizontal framing members shall be installed according to the curtain wall system manufacturer's
guidelines.
C. Concrete Panels: Any non-combustible exterior concrete based panel. Panels shall not be less than 2-1/2 in. thick, 12 in.
high or 12 in. long. Attachment to the framing shall be according to the curtain wall system manufacturer's guidelines.
D. Impaling Pins: When required by insulation manufacturer, use with insulation. The pins shall be located, sized and installed
according to the curtain
wall system manufacturer's guidelines.
E. Curtain Wall Insulation: (Optional) When curtain wall insulation is used, the perimeter joint treatment must be installed
before the insulation. Insulation may be butted to top and bottom of perimeter joint treatment but not deform the perimeter joint
treatment. Either mineral wool** or fiberglass batt insulation** may be used. (** Listed with Omega Point Laboratories)
F. Concrete Panel Join t: Vertical and horizontal concrete panel joints created between panels can be either flush type (butt
joint) or key way type (tongue and groove). Concrete panel edges must be in contact with each other. If required, the surface of
the panel joints can be sealed with gaskets or sealants.
G. Framing Covers: Framing covers used over the mullions and transoms are optional. When used, the framing covers shall be
located, sized and installed according to the curtain wall system manufacturer's guidelines. Framing covers do not pass through
the perimeter joint treatment. They are butted to the top and bottom surfaces of the perimeter joint treatment without deforming
it. Either mineral wool** or fiberglass batt insulation** may be used. (** Listed with Omega Point Laboratories)
*Reproduced courtesy of Omega Point Laboratories, Inc.
1
Tremco Inc., 2628 Pearl Road, Medina, Ohio 44256
www.tremcofirestop.com
3. PERIMETER JOINT PROTECTION:
The perimeter joint (linear opening) shall not exceed an 6 in. nom. joint width (joint width at installation) and the perimeter joint treatment
shall incorporate the following construction features:
A. Packing Material: Use a min. 4 in. thick, 4 pcf density, mineral wool batt insulation** installed with the fibers running
parallel to the slab edge and curtain wall. (** Listed with Omega Point Laboratories) The packing material shall be compressed
50% in the nominal joint width. Compress the batt insulation into the perimeter joint such that the top surface of the batt
insulation is flush with the top surface of the concrete floor slab. Splices (butt joints) in the lengths of mineral wool batt
insulation are to be tightly compressed together. Reference the Introduction to Fire Resistive Joint Systems Section of this
Directory for more details on how to determine the cut width of the insulation to be installed in the nominal joint width, and how
to determine t he compressed percentage of a
known insulation width installed in a known nominal joint width.
B. Fill, Void or Cavity Material: Liquid is to be applied, (sprayed, brushed, or painted) to cover the exposed surface of the
mineral wool installed in the perimeter joint. Apply a min. dry film thickness of 1/8 in. and overlap the material a min. 1/2 in.
onto the adjacent curtain wall assembly and concrete floor slab assembly. If the spraying process is stopped and the applied
liquid cures to an elastomeric film before process is restarted, then overlap the edge of the cured material at least 1/8 in. with the
spray. Reference Product Section of this Directory for more details about the Listed product.
Listed Manufacturer:
TREMCO, Inc. -Joint Sealant Spray
T REMstop Acrylic-SP
** Cycling: Before testing, the spliced, test
specimen was cycled 500 times at 30 cpm
in accordance with ICBO ES AC 30 (Jan.
1997) and ASTM E 1966.
2002 Product Directory, © Omega Point Laboratories, Inc.
*Reproduced courtesy of Omega Point Laboratories, Inc.
2
Tremco Inc., 2628 Pearl Road, Medina, Ohio 44256
www.tremcofirestop.com
Design No. CEJ 198P
February 26, 2003
PERIMETER FIRE BARRIER SYSTEM
T-Rating - 1-1/2 hr.
F-Rating - 2 hr
L-Rating NA
Rated for ± 15% movement
1. CONCRETE FLOOR ASSEMBLY:
Two-hour rated concrete floor assembly made from either lightweight or normal weight concrete with a density of 100-150 pcf, with a min.
thickness of 4-1/2 -in. at the joint face. Overall slab thickness may vary to accommodate various blockout depths (longitudinal recesses)
formed in the concrete, to house the architectural cover plate. The blockout width may also vary without restriction.
2. CURTAIN WALL ASSEMBLY: The curtain wall assembly shall incorporate the following construction features:
A. Mounting Attachment: (Not shown) Attachment of the curtain wall framing to the struct ural framing shall be according to
the curtain wall manufacturer's instructions. When required, the mounting attachments to the floor slab shall be connected to the
joint face of the floor slab, according to the curtain wall manufacturer's instructions. Max. distance between mounting
attachments shall be 10 feet.
B. Steel-Stud Framing: Vertical framing members shall be a min. 3-5/8 in. by 1-1/4 in., 18 GA steel "C" studs. Attachment
shall be according to the curtain wall system manufacturer's guidelines. Vertical framing shall not according to the curtain wall
system manufacturer's guidelines.
C. Steel Panels: Steel panels shall be installed to curtain wall framing according to the curtain wall system manufacturer's
guidelines or using selftapping 1-in. pan head framing screws, spaced nominally 8 in. o.c.. Use a min. 20 GA sheet steel panel
with max. dimensions of 48 in. by 144 in.
D. Impaling Pins: (Not shown) When curtain wall insulation is used, use impaling pins when required by
manufacturer's instructions. The pins shall be located, sized and installed according to the curtain wall system
manufacturer's guidelines.
E. Curtain Wall Insulation: (Optional) Mineral wool or fiberglass batt insulation** may be used. (** Listed with Omega Point
Laboratories) When curtain wall insulation is used, the perimeter joint treatment must be installed before the insulation.
Insulation may be butted to top and bottom of perimeter joint treatment but not deform the perimeter joint treatment.
F. Interior Curtain Wall Surface: Framing covered with one layer of 5/8 in. thick, Type X gypsum wallboard on interior face.
The face layer of gypsum wallboard fastened to steel studs with min. #6 1-1/8 in. long bugle-head phillips drywall screws spaced
12 in. o.c. Joint Tape and Compound - vinyl or casein, dry or premixed joint compound applied to face layers of gypsum
wallboard in two coats to all exposed screw heads and gypsum wallboard joints. A min. 2-in. wide paper, plastic or fiberglass
tape embedded in first layer of compound over joints in gypsum wallboard. A min. wall cavity depth of 3- 5/8 in. created from
unexposed side of gypsum wallboard to unexposed side of panel. The joint face of the curtain wall covered as shown with one
layer of gypsum wallboard.
*Reproduced courtesy of Omega Point Laboratories, Inc.
1
Tremco Inc., 2628 Pearl Road, Medina, Ohio 44256
www.tremcofirestop.com
3. PERIMETER JOINT PROTECTION:
The perimeter joint (linear opening) shall not exceed an 8 in. nom. joint width (joint width at installation) and the perimeter joint treatment
shall incorporate the following construction features:
A. Packing Material: Use a min. 4 in. thick, 4 pcf density, mineral wool batt insulation** installed with the fibers running
parallel to the slab edge and curtain wall. (** listed with Omega Point Laboratories) The packing material shall be compressed
50% in the nominal joint width. Compress the batt insulation into the perimeter joint such that the top surface of the batt
insulation is flush with the top surface of the concrete floor slab. Splices (butt joints) in the lengths of mineral wool batt
insulation are to be tightly compressed together. Reference the Introduction to Fire Resistive Joint Systems Section of this
Directory for more details on how to determine the cut width of the insulation to be installed in the nominal joint width, and how
to determine the compressed percentage of a known insulation width installed in a known nominal joint width.
B. Fill, Void or Cavity Material: Liquid is to be applied, (sprayed, brushed, or painted) to cover the exposed surface of the
mineral wool installed in the perimeter joint. Apply a min. dry film thickness of 1/8 in. and overlap the material a min. 1/2 in.
onto the adjacent curtain wall assembly and concrete floor slab assembly. If the spraying process is stopped and the applied
liquid cures to an elastomeric film before process is restarted, then overlap the edge of the cured material at least 1/8 in. with the
spray. Reference Product Section of this Directory for more details about the Listed product.
Listed Manufacturer:
TREMCO, Inc. - Joint Sealant Spray
TREMstop Acrylic-SP
** Cycling: Before testing, the spliced, test specimen was cycled 500 times at 30 cpm in accordance with ICBO ES AC 30 (Jan. 1997) and
ASTM E 1966.
2002 Product Directory, © Omega Point Laboratories, Inc.
*Reproduced courtesy of Omega Point Laboratories, Inc.
2
Tremco Inc., 2628 Pearl Road, Medina, Ohio 44256
www.tremcofirestop.com
Design No. CEJ 204P
February 27, 2003
PERIMETER FIRE BARRIER SYSTEM
T-Rating - 1/2 hr.
F-Rating - 2 hr.
L-Rating N/A
Rated for ± 15% movement
1. FLOOR ASSEMBLY: Two -hour rated concrete floor assembly made from either
lightweight or normal weight concrete with a density of 100-150 pcf, with a min. thickness of 4-1/2 -in. at the joint face. Overall slab
thickness may increase to accommodate various blockout depths (longitudinal recesses) formed in the concrete, to house an architectural
cover plate. The blockout width may also vary without restriction.
2. CURTAIN WALL ASSEMBLY: The curtain wall assembly shall incorporate the following construction features:
A. Mounting Attachment: (Not shown) Attachment of the curtain wall framing to the structural framing is required at each
floor. The mounting attachments to the floor slab shall be either to the top surface of the floor slab or the joint face of the floor
slab, according to the curtain wall manufacturer's instructions. The distance between mounting attachments shall be a min. 60 in.
o.c. The mounting attachments shall be steel.
B. Aluminum Framing: Rectangular aluminum tubing mullions and transoms, sized according to the curtain wall system
manufacturer's guidelines. Min. overall dimensions of framing required is 0.100 in. thick aluminum with a min. 5-1/4 in. height
and a min. of 2-1/2 in. width of the extrusion. Mullions are to be spaced a min. 60 in. o.c. and transoms are to be spaced a min.
72 in. o.c. Transoms are to be located at a height of 33 in. above the top surface of the concrete floor assembly (as measured
from the bottom of the transom).
C. Glass Spandrel Panels: Glass spandrel panels shall be installed to curtain wall framing according to the curtain wall system
manufacturer's guidelines. Use a min. 1/4 in. thick, clear tempered glass with a max. width of 59 in. and height of 71 in. Panels
are secured with a thermal break (thermal-set rubber extrusion), pressure bar (aluminum extrusion), 1/4 -20 x 5/8 in. long screws,
and a snap face (aluminum extrusion). The spandrel panels shall be insulated according to 2F.
D. Glass Vision Panels: Glass vision panels shall be at least 35-1/2 in. above the top surface of the floor assembly and installed
to curtain wall framing according to the curtain wall system manufacturer's guidelines. Same min. requirements as in 2C.
E. Impaling Pins: When pins are used instead of screws, they shall be located in the same manner as the screws in 2F, sized and
installed according to the curtain wall system manufacturer's guidelines, or be a min. 4-1/2 in. long, 12 GA steel pin attached to a
nom. 2 in. by 2 in. galvanized sheet steel plate, a nom. 2 by 2 by 2 in. long angle, or directly attached to the steel panel using a
stud gun. Pins shall be spaced a max. of 12 in. o.c. and installed around the periphery (min.) so that the interior face of the
curtain wall insulation is flush with the interior face of the framing.
*Reproduced courtesy of Omega Point Laboratories, Inc.
1
Tremco Inc., 2628 Pearl Road, Medina, Ohio 44256
www.tremcofirestop.com
F. Curtain Wall Insulation: All spandrel panels shall be insulated with a min. 2 in. thick, 8 pcf, mineral wool batt insulation**
faced on one side with aluminum foil scrim (vapor retarder) which is exposed to the room interior. (**Listed with Omega Point
Laboratories) They are fitted tightly between vertical framing members, secured with screws placed a max. 8 in. o.c. attached to
a min. 16 GA angle around the entire perimeter of each batt. The vertical 16 GA angles are attached to the mullions with screws.
The horizontal angles are placed back to back to form a "T". The interior face of the batts is flush with the interior face of the
curtain wall framing. A min. 2-in. air space is created between the glass and the insulation. The 36-in. wide batts shall be
installed without vertical seams, spanning the full length between the vertical and horizontal curtain wall framing members,
which create the spandrel panel area. Horizontal seams in the insulation are to be at least 6 in. from the top surface of the
perimeter joint treatment.
G. Framing Covers : Strips made of 1 in. thick by 4 in. wide, 8 pcf, mineral wool batt insulation** faced on one side with
aluminum foil scrim (vapor retarder) which is exposed to the room interior. (**Listed with Omega Point Laboratories) Framing
covers are centered over each vertical framing member and secured to the member with impaling pins and clips spaced at least
12 in. o.c. Framing covers do not pass through the perimeter joint treatment. They are butted to the top and bottom surfaces of
the perimeter joint treatment. The sides of the mullion covers are sealed with aluminum foil tape.
3. PERIMETER JOINT PROTECTION:
The perimeter joint (linear opening) shall not exceed an 6 in. nom. joint width (joint width at installation) and the perimeter joint treatment
shall incorporate the following construction features:
A. Packing Material: Use a min. 4 in. thick, 4 pcf density, mineral wool batt insulation** installed with the fibers running
parallel to the slab edge and curtain wall. (** Listed with Omega Point Laboratories) The packing material shall be compressed
50% in the nominal joint width. Compress the batt insulation into the perimeter joint such that the top surface of the batt
insulation is flush with the top surface of the concrete floor slab. Splices (butt joints) in the lengths of mineral wool batt
insulation are to be tightly compressed together. Reference the Introduction to Fire Resistive Joint Systems Section of this
Directory for more details on how to determine the cut width of the insulation to be installed in the nominal joint width, and how
to determine the compressed percentage of a known insulation width installed in a known nominal joint width.
B. Fill, Void or Cavity Material: Liquid is to surface of the mineral wool installed in the perimeter joint. Apply a min. 1/16-in.
dry film thickness and overlap the material a min. 1/2 in. onto the adjacent curtain wall assembly and concrete floor slab
assembly. If the spraying process is stopped and the applied liquid cures to an elastomeric film before process is restarted, then
overlap the edge of the cured material at least 1/8 in. with the spray. Reference Product Section of this Directory for more details
about the Listed product.
Listed Manufacturer:
TREMCO, Inc. -Joint Sealant Spray
TREMstop Acrylic-SP
C. Cycling: Before testing, the spliced, test specimen was cycled 500 times at 30 cpm in accordance with ICBO ES AC 30 (Jan.
1997) and ASTM E 1966.
D. Support Clips : (Not Shown) Support clips are optional but recommended for installations subject to vertical shear
movement. Standard Z-shaped clips are
20 GA galvanized steel with the following dimensions: 1 in. wide by 3 in. high with a 2 in. upper leg and 3 in. lower leg.
2002 Product Directory, © Omega Point Laboratories, Inc.
*Reproduced courtesy of Omega Point Laboratories, Inc.
2
Tremco Inc., 2628 Pearl Road, Medina, Ohio 44256
www.tremcofirestop.com
Design No. CEJ 217 P
PERIMETER FIRE BARRIER SYSTEM
T-Rating - 3/4 hr.
F-Rating - 2 hr.
L-Rating NA
Rated for ± 10 % movement
1. CONCRETE FLOOR ASSEMBLY: Two -hour rated concrete floor assembly made from either lightweight or normal weight concrete
with a density of 100-150 pcf, with a min.thickness of 4-1/2 -in. at the joint face. Overall slab thickness may vary to accommodate various
blockout depths (longitudinal recesses) formed in the concrete, to house the architectural cover plate. The blockout width may also vary
without restriction.
2. CURTAIN WALL ASSEMBLY: The concrete curtain wall assembly shall incorporate the following construction features:
A. Mounting Attachment: (Not shown) Attachment of the curtain wall framing to the structural framin g shall be
according to the curtain wall manufacturer's instructions. If required, mounting attachments to the floor slab shall be connected
to the joint face of the floor slab. Max. distance between mounting attachments shall be 10 feet.
B. Steel-Stud Framing: Vertical framing members shall be a min. 3-5/8 in. by 1-5/8 in., 18 GA steel "C" studs. Attachment
shall be according to the curtain wall system manufacturer's guidelines. Vertical framing not to exceed a spacing of 60 in. o.c.
and shall be completely covered by the concrete panels. If required, horizontal framing embers shall be installed according to
the curtain wall system manufacturer's guidelines.
C. Concrete Panels: Any non-combustible exterior concrete based panel. Panels shall not be less t han 2-1/2 in. thick, 12 in. high
or 12 in. long. Attachment to the framing shall be according to the curtain wall system manufacturer's guidelines.
D . Impaling Pins: When required by insulation manufacturer, use with insulation. The pins shall be located, sized and installed
according to the curtain wall system manufacturer's guidelines.
E . Curtain Wall Insulation: (Optional) When curtain wall insulation is used, the perimeter joint treatment must be installed
before the insulation. Insulation may be butted to top and bottom of perimeter joint treatment but not deform the perimeter joint
treatment. Either
mineral wool** or fiberglass batt insulation** may be used. (** Listed with Omega Point Laboratories)
F. Concrete Panel Joint: Vertical and horizontal concrete panel joints created between panels can be either flush type (butt
joint) or key way type (tongue and groove). Concrete panel edges must be in contact with each other. If required, the surface of
the panel joints can be sealed with gaskets or sealants.
G. Framing Covers : Framing covers used over the mullions and transoms are optional. When used, the framing covers shall be
located, sized and installed according to the curtain wall system manufacturer's guidelines. Framing covers do not pass through
the perimeter joint treatment. They are butted to the top and bottom surfaces of the perimeter joint treatment without deforming
it. Either mineral wool** or fiberglass batt insulation** may be used. (** Listed with Omega Point Laboratories)
3 . PERIMETER JOINT PROTECTION: The perimeter joint (linear opening) shall not exceed an 6 in. nom. joint width (joint width at
installation) and the perimeter joint treatment shall incorporate the following construction features:
*Reproduced courtesy of Omega Point Laboratories, Inc.
1
Tremco Inc., 2628 Pearl Road, Medina, Ohio 44256
www.tremcofirestop.com
A. Packing Material: Use a min. 4 in. thick,
4 pcf density, mineral wool batt insulation** installed with the fibersrunning parallel to the slab edge andcurtain wall. (** Listed with
Omega Point Laboratories) The packing material shallbe compressed 50% in the nominal joint width. Compress the batt insulation intothe
perimeter joint such that the topsurface of the batt insulation is flush with the top surface of the concrete floor slab.Splices (butt joints) in
the lengths ofmineral wool batt insulation are to betightly compressed together. Referencethe Introduction to Fire Resistive JointSystems
Section of this Directory for more details on how to determine the cutwidth of the insulation to be installed inthe nominal joint width, and
how todetermine the compressed percentage of aknown insulation width installed in aknown nominal joint width.
A. Fill, Void or Cavity Material: Liquid is to be applied, (sprayed, brushed, or painted) to cover the exposed surface of the
mineral wool installed in the perimeter joint. Apply a min. dry film thickness of 1/8 in. and overlap the material a min. 1/2 in.
onto the adjacent curtain wall assembly and concrete floor slab assembly. If the spraying process is stopped and the applied
liquid cures to an elastomeric film before process is restarted, then overlap the edge of the cured material at least 1/8 in. with the
spray.
Reference Product
Section of this Directory for more details
about the Listed product.
Listed Manufacturer:
TREMCO, Inc. Joint Sealant
Spray
TREMstop Acrylic-SP
** Cycling: Before test ing, the spliced, test specimen was cycled 500 times at 30 cpm in accordance with ICBO ES AC 30 (Jan. 1997)
and ASTM E 1966.
Fire-Resistant Joint Systems
Look for the Omega Point Laboratories mark on the product
2003 Product Directory, © Omega Point Laboratories, Inc.
*Reproduced courtesy of Omega Point Laboratories, Inc.
2
Tremco Inc., 2628 Pearl Road, Medina, Ohio 44256
www.tremcofirestop.com
Design No. TL/PH 120-01
January 22, 2003
HORIZONTAL (FLOOR) - F RATING - 2 HOURS; T, H RATING - 0 HOUR
TEST PRESSURE DIFFERENTIAL - 2.5 Pa (0.01" OF WATER)
1. Floor: Minimum 4-1/2" thickness cast concrete floor/ceiling assembly providing a 2 hour rating. Maximum joint width of 6".
2. Firestop Sealant:
Option 1: Tremco FYRE-SIL S.L. self-leveling sealant applied to a depth of 1/4" minimum
Option 2: tremco TREMstop Acrylic-SP applied to a depth of 1/8" and overlapping adjacent surfaces by 1/2".
3. Mineral Wool Insulation: Minimum thickness 4". When FRYE-Sil S.L. is used, mineral wool shall be minimum 3.5 pcf density compress 25%.
when TREMstop Acrylic-SP is used, mineral wool shall be 6 pcf density compressed 35%.
4. Steel Curtain Wall: This design was tested from concrete slab edge to simulated steel curtain wall. However, possible deflection of the curtain wall
system due to fire exposure has not been evaluated. The design should ensure rigidity of the curtain wall system to prevent such movement.
Testing Standards: CAN/ULC-S115.
The listed systems in this section have been evaluated to the following requirements:
ASTM E-814, Fire Tests of Through-Penetration Firestops
CAN4-S115, Fire Tests of Firestop Systems
Maintenance of integrity (stay-in-place and prevent passage of flame) when subjected to the test temperatures (standard fire exposure) in:
ASTM E-119, Fire Tests of Building Construction & Materials
CAN/ULC-S101, Fire Endurance Tests of Building Construction & Materials
Test Pressure Differential - Each listing indicates a "Test Pressure Differential" which is the amount by which the pressure on the fire
exposed side of the system exceeded the pressure on the unexposed side during test.
Annual Spacing - Where annual spacing is specified in these listings for through-penetration type systems it refers to the clearance between
the penetration and the opening. Where a specific distance is stated and not identified as "minimum", the penetration is centered in the
opening; where a distance is specified as "minimum", the maximum spacing is governed by the maximum opening size; where a range is
stated, the penetration may be offset in the copening within the clearance limitations of the spacing range given.
These systems are intended for use in the types of separations for which they are qualified in the listed design. The separations themselves
should be rated for the period required per ASTM E-119, CAN/ULC-S101 or equivalent.
Where only F and T ratings (ASTM E-814) are given for a system design, these correspond to FH and FTH ratings (CAN4-S115) and may
be read as such.
Systems are installed, unless otherwise noted, in accordance with the Manufacturer's Installation Instructions or Design Manual.
All listed components are identified with the WHI Certification Mark.
Manufacturers of listed components subscribe to an ITS follow-up factory inspection and certification program.
*Reproduced courtesy of Intertek Testing Services NA Inc.
1
Tremco Inc., 2628 Pearl Road, Medina, Ohio 44256
www.tremcofirestop.com
MATERIAL SAFETY DATA SHEET
TELEPHONE: (216)292-5000
3735 GREEN ROAD
BEACHWOOD, OHIO 44122-8068
EMERGENCIES: (216)765-6727 8:30-5:00 EST
AFTER HOURS: CHEMTREC (800)424-9300
-----------------------------------------------------------------------------------------------SECTION 1
-----------------------------------------------------------------------------------------------Order Code: 904874 805
Product Name:
Chemical Name:
Chemical Family:
Product Code:
MSDS Preparer:
TREMSTOP ACRYLIC SP
Sealant
904-8XX
R. A. MIKOL
Date Prepared:
Replaces Date:
04-MAR-04
17-NOV-03
Other Applications:
This Material Safety Data Sheet (MSDS) applies to all colors.
-------------------------------------------------------------------------------Section 2 - Molecular Composition
-------------------------------------------------------------------------------Common Name and Chemical Name
Weight %
CAS Number
Exposure Limits
ACRYLIC POLYMER
OSHA:TWA
ACGIH:TWA
-
STEL
STEL
-
WATER
OSHA:TWA
ACGIH:TWA
STEL
STEL
-
STEL
STEL
(mist)
10 mg/M3 (mist)
-
WHITE MINERAL OIL
OSHA:TWA
5 mg/M3
ACGIH:TWA
5 mg/M3
30.0-40.0 Trade Secret
SILICA, AMORPHOUS, FUMED
OSHA:TWA
15 mg/M3 STEL
ACGIH:TWA
10 mg/M3 STEL
-
TITANIUM DIOXIDE
OSHA:TWA
10 mg/M3
ACGIH:TWA
10 mg/M3
STEL
STEL
-
IRON OXIDE
OSHA:TWA
ACGIH:TWA
STEL
STEL
45.0-55.0
7732-18-5
3.0-7.0
8042-47-5
1.0-5.0
(total nuisance dust)
(total nuisance dust)
112945-52-5
0.0-5.0
13463-67-7
(total dust, no asbestos, <1% SiO2)
0.0-1.5
10 mg/M3
5 mg/M3
1309-37-1
(dust, fume as Fe)
(fume as Fe)
1,2-PROPANEDIOL (PROPYLENE GLYCOL)
1.0-3.0
57-55-6
OSHA:TWA
STEL
ACGIH:TWA
STEL
-----------------------------------------------------------------------------Section 3 - Hazards Identification
-----------------------------------------------------------------------------******************************************************************************
Emergency Overview:
Various colored viscous liquid. If inhaled can cause irritation to
respiratory system. Leave area to breathe fresh air.
******************************************************************************
Potential Hlth Effect/Rte of Entry:
----------------------------------Inhalation:
May cause irritation to respiratory system, headache, and nausea.
Eyes:
May cause irritation.
Ingestion:
May cause gastrointestinal discomfort including nausea, vomiting,
lethargy, and diarrhea and may be fatal. May produce CNS depression and
kidney damage, which may be fatal.
Skin:
May cause slight irritation.
Aggravated Medical Conditions:
Pre-existing skin, eye, and respiratory disorders may be aggravated
46 46
2
Product 904-8XX Page 1 of 5
Order Code: 904874 805
by exposure.
Acute Health Effects:
See effects described above.
Chronic Health Effects:
Prolonged overexposure to silica dust by inhalation may cause delayed lung
injury. Fillers are encapsulated and not expected to be released from product
under normal conditions of use.
-----------------------------------------------------------------------------Section 4 - First Aid Measures
-----------------------------------------------------------------------------Inhalation:
Leave area to breathe fresh air.
Eyes:
Flush immediately with running water for 15 minutes, lifting the upper and
lower lids occasionally. Get medical attention immediately.
Ingestion:
Get medical attention immediately.
Skin:
Wash with soap and water.
Notes to Physician:
N/A
-----------------------------------------------------------------------------Section 5 - Fire Fighting Measures
-----------------------------------------------------------------------------Flash Point:
N/A
Method:
N/A
Lower Flammability Limit:
N/A
Upper Flammability Limit:
N/A
Autoignition Temperature:
N/A
Extinguishing Media:
Not applicable. Water base compound, not expected to burn.
Fire and Explosion Hazards:
Not Applicable
Special Fire Fighting Procedures:
During a fire, personnel at the scene are to prevent exposure to fumes
using accepted fire fighting techniques.
Fire Fighting Equipment:
N/A
Other Precautions:
Not Applicable
-----------------------------------------------------------------------------Section 6 - Accidental Release Measures
-----------------------------------------------------------------------------Release Response Overview:
Absorb spill in sand, earth or other suitable material.Transfer to
appropriate container for disposal.
-----------------------------------------------------------------------------Section 7 - Handling and Storage
-----------------------------------------------------------------------------Handling and Storage Precautions:
Store under normal warehouse conditions. Handle in compliance with common
hygenic practices.
-----------------------------------------------------------------------------Section 8 - Exposure Controls/Personal Protection
-----------------------------------------------------------------------------Respiratory:
Wear appropriate, properly fitted, NIOSH/MSHA approved respirator with
combination particulate filter and vapor/gas removing cartridge a directed
by the manufacturer when the ventilation is not adequate and product is
spray applied.
Skin:
47 46
3
Product 904-8XX Page 2 of 5
Order Code: 904874 805
Protect hands with rubber or other suitable gloves. Wear typical full cover
clothing.
Eyes:
Wear suitable safety eyewear.
Face:
Not required.
Engineering:
Use local exhaust when the general ventilation is not adequate.
-----------------------------------------------------------------------------Section 9 - Physical and Chemical Properties
-----------------------------------------------------------------------------Odor/Appearance:
ACRYLIC/ VARIOUS COLORED VISCOUS LIQUID
Color:
VARIOUS
Physical State:
VISCOUS LIQUID
pH:
7.0-9.0
Vapor Pressure:
N/A
Vapor Density:
N/A
Boiling Point:
N/A
Melting Point:
N/A
Freezing Point:
<32 F
Solubility in Water: MISCIBLE
Specific Gravity:
1.06
% Volatile Weight:
52.7
-----------------------------------------------------------------------------Section 10 - Reactivity/Stability
-----------------------------------------------------------------------------Stability:
Stable
Incompatible Products:
Avoid contact with strong oxidizing agents, acids, bases.
Conditions to Avoid Polymerization:
Hazardous polymerization will not occur.
-----------------------------------------------------------------------------Section 11 - Toxicological Information
-----------------------------------------------------------------------------Eyes:
SEE SECTION 3
Ingestion:
"
"
"
Inhalation:
"
"
"
Skin:
"
"
"
Subchronic:
"
"
"
Chronic:
"
"
"
-----------------------------------------------------------------------------Section 12 - Ecological Information
-----------------------------------------------------------------------------Ecotoxicological Data:
N/A
Chemical Fate:
N/A
-----------------------------------------------------------------------------Section 13 - Disposal Considerations
-----------------------------------------------------------------------------RCRA Class:
N/A
Disposal Method:
Not regulated by RCRA. Dispose of in compliance with state and local
regulations.
EPA Reportable Quantities
------------------------N/A
-----------------------------------------------------------------------------Section 14 - Transportation Data
-----------------------------------------------------------------------------DOT Shipping Name:
NOT REGULATED
DOT Hazard Class:
48 46
4
Product 904-8XX Page 3 of 5
Order Code: 904874 805
DOT Label:
UN/NA Number:
Packing Group:
Special Provisions:
Packaging
--------Exceptions:
Non-Bulk:
Bulk:
Quantity Limitations
-------------------Passenger Aircraft or Railcar:
Cargo Aircraft:
Vessel Stowage Requirements
--------------------------Vessel Stowage:
Other Stowage:
Transportation Notes:
N/A
-----------------------------------------------------------------------------Section 15 - Regulatory Information
-----------------------------------------------------------------------------TSCA Status:
On the TSCA Inventory
OSHA Status:
Considered hazardous based on the following criteria:
Irritant
Target Organs
------------Central Nervous System
Lung
Eye
OSHA Hazardous Components
---------------------------------------------SILICA, AMORPHOUS, FUMED
TITANIUM DIOXIDE
* WHITE MINERAL OIL
IRON OXIDE
* - CHEMICAL IS LISTED AS AN IARC, NTP, OSHA,
CAS Number
-----------112945-52-5
13463-67-7
8042-47-5
1309-37-1
or ACGIH CARCINOGEN
Compliance Quantites
-------------------N/A
SARA 311 Ratings
---------------Immediate Health Hazard:
Delayed Health Hazard:
Fire Hazard:
Reactivity Hazard:
Sudden Release of Pressure Hazard:
N
Y
N
N
N
SARA 313 Ingredients
---------------------------------------------No SARA 313 Ingredients
CAS Number
------------
Proposition 65 Ingredients
-------------------------Chemicals known to the State of California to cause cancer, birth
defects and/or other reproductive harm.
CAS Number
---------------------------------------------------CHLOROTHALONIL (<0.2%)
1897-45-6
-----------------------------------------------------------------------------Section 16 - Other Information
------------------------------------------------------------------------------
49 46
5
Product 904-8XX Page 4 of 5
Order Code: 904874 805
FOR INDUSTRIAL USE ONLY. KEEP OUT OF REACH OF CHILDREN.
THE HAZARD INFORMATION HEREIN IS OFFERED SOLELY FOR THE CONSIDERATION
OF THE USER, SUBJECT TO HIS OWN INVESTIGATION OF COMPLIANCE WITH APPLICABLE
REGULATIONS, INCLUDING THE SAFE USE OF THE PRODUCT UNDER EVERY FORESEEABLE
CONDITION.
50 46
6
Product 904-8XX Page 5 of 5
MATERIAL SAFETY DATA SHEET
TELEPHONE: (216)292-5000
3735 GREEN ROAD
BEACHWOOD, OHIO 44122-8068
EMERGENCIES: (216)765-6727 8:30-5:00 EST
AFTER HOURS: CHEMTREC (800)424-9300
-----------------------------------------------------------------------------------------------SECTION 1
-----------------------------------------------------------------------------------------------Order Code: 939874 805
Product Name:
Chemical Name:
Chemical Family:
Product Code:
MSDS Preparer:
FYRE-SIL S.L.
939-8XX
R. A. MIKOL
Date Prepared:
Replaces Date:
02-APR-02
16-AUG-1998
Other Applications:
This Material Safety Data Sheet (MSDS) applies to 939-856(GREEN),
-874(RUST RED), -8XX (OTHER COLORS)
-------------------------------------------------------------------------------Section 2 - Molecular Composition
-------------------------------------------------------------------------------Common Name and Chemical Name
Weight %
CAS Number
Exposure Limits
CALCIUM CARBONATE (LIMESTONE)
OSHA:TWA
15 mg/M3 STEL
ACGIH:TWA
10 mg/M3 STEL
-
SILICONE POLYMER
OSHA:TWA
ACGIH:TWA
-
-
45.0-50.0
1317-65-3
(total dust, 5mg/M3 respirable fraction)
(total dust, no asbestos, <1% SiO2)
30.0-40.0 Trade Secret
STEL
STEL
POLYDIMETHYLSILOXANE, TRIMETHYL ENDCAP
OSHA:TWA
STEL
ACGIH:TWA
STEL
OXIMINO SILANE
OSHA:TWA
ACGIH:TWA
-
STEL
STEL
-
IRON OXIDE
OSHA:TWA
ACGIH:TWA
STEL
STEL
-
(dust, fume as Fe)
(fume as Fe)
CRYSTALLINE SILICA (QUARTZ)
OSHA:TWA 0.10 mg/M3 STEL
ACGIH:TWA 0.10 mg/M3 STEL
-
(respirable dust)
(respirable dust)
10 mg/M3
5 mg/M3
5.0-15.0
63148-62-9
1.0-5.0
Trade Secret
0.5-1.5
1309-37-1
0.5-1.0
14808-60-7
-----------------------------------------------------------------------------Section 3 - Hazards Identification
-----------------------------------------------------------------------------******************************************************************************
Emergency Overview:
Various colored pastes. If inhaled can cause headache, dizziness,
irritation to respiratory system. Leave area to breathe fresh air. Avoid
further overexposure. If symptoms persist, get medical attention
immediately. As a by product of curing up to 4% Methyl Ethyl Ketoxime
(MEKO) may be released within product. Due to extremely low vapor pressure
of MEKO (<8mmHg at 20C) relesae of high airborne concentration is not
expected under normal conditions of use.
******************************************************************************
Potential Hlth Effect/Rte of Entry:
----------------------------------Inhalation:
Can cause headache, dizziness, nausea, drowsiness, stupor, irritation to
respiratory system.
Eyes:
Can cause severe irritation.
73 52
2
Product 939-8XX Page 1 of 5
Order Code: 939874 805
Ingestion:
Can cause gastrointestinal irritation.
Skin:
Can cause irritation, possible dermal sensitization. Methyl Ethyl Ketoxime
may be absorbed through the skin.
Aggravated Medical Conditions:
Pre-existing eye, skin, respiratory, and liver disorders may be aggravated by
exposure. Sympathomimetic drugs may initiate cardiac arrythmias.
Acute Health Effects:
See effects described above.
Chronic Health Effects:
Methyl Ethyl Ketoxime (MEKO) has caused allergic skin reactions and liver
tumors in animals. Overexposure may cause blood effects (methemoglobinemia
and anemia). Inhalation of crystalline silica (quartz) can cause cancer
based on animal data, and IARC concludes sufficient evidence in humans
(Group 1). Prolonged and repeated overexposure to free crystalline silica
dust above the TLV level may cause scarring of the lungs with cough and
shortness of breath. A delayed lung injury, silicosis may result from
breathing free silica. Fillers are encapsulated and not expected to be
released from product under normal conditions of use.
-----------------------------------------------------------------------------Section 4 - First Aid Measures
-----------------------------------------------------------------------------Inhalation:
Leave area to breathe fresh air. Avoid further overexposure. If symptoms
persist, get medical attention immediately.
Eyes:
Flush immediately with running water for 15 minutes, lifting the upper and
lower lids occasionally. Get medical attention immediately.
Ingestion:
Get medical attention immediately.
Skin:
Wash area of contact thoroughly with hand cleaner followed by soap and
water. If irritation, rash or other disorders develop, get medical
attention immediately.
Notes to Physician:
N/A
-----------------------------------------------------------------------------Section 5 - Fire Fighting Measures
-----------------------------------------------------------------------------Flash Point:
160 F
Method:
TCC
Lower Flammability Limit:
N/A
Upper Flammability Limit:
N/A
Autoignition Temperature:
N/A
Extinguishing Media:
Water fog.
Fire and Explosion Hazards:
Not Applicable
Special Fire Fighting Procedures:
During a fire, personnel at the scene are to prevent exposure to fumes
using accepted fire fighting techniques.
Fire Fighting Equipment:
N/A
Other Precautions:
Not Applicable
-----------------------------------------------------------------------------Section 6 - Accidental Release Measures
-----------------------------------------------------------------------------Release Response Overview:
Absorb spill in sand, earth or other suitable material.Transfer to
appropriate container for disposal.
74 52
3
Product 939-8XX Page 2 of 5
Order Code: 939874 805
-----------------------------------------------------------------------------Section 7 - Handling and Storage
-----------------------------------------------------------------------------Handling and Storage Precautions:
Store under normal warehouse conditions. Prevent inhalation of vapor,
ingestion, and contact with skin and eyes. Keep container closed when not
in use. Precautions also apply to emptied containers. Change soiled
workclothes frequently. Clean hands thoroughly after handling.
-----------------------------------------------------------------------------Section 8 - Exposure Controls/Personal Protection
-----------------------------------------------------------------------------Respiratory:
Wear NIOSH/MSHA approved respirator as directed by the manufacturer when
the ventilation is not adequate.
Skin:
Protect hands with impervious rubber gloves and wear typical full cover
clothing. Prevent contact with skin.
Eyes:
Wear suitable safety eyewear.
Face:
Not required.
Engineering:
Use local exhaust when the general ventilation is not adequate.
-----------------------------------------------------------------------------Section 9 - Physical and Chemical Properties
-----------------------------------------------------------------------------Odor/Appearance:
OXIME/VARIOUS COLORED PASTE
Color:
VARIOUS
Physical State:
PASTE
pH:
Vapor Pressure:
N/A
Vapor Density:
N/A
Boiling Point:
N/A
Melting Point:
N/A
Freezing Point:
N/A
Solubility in Water: NEGLIGIBLE
Specific Gravity:
1.41
% Volatile Weight:
0.0
-----------------------------------------------------------------------------Section 10 - Reactivity/Stability
-----------------------------------------------------------------------------Stability:
Stable
Incompatible Products:
Avoid contact with strong oxidizing agents.
Conditions to Avoid Polymerization:
Hazardous polymerization will not occur.
Decomposition Products:
At temperatures over 300 F formaldehyde is a by product of oxidative
thermal decomposition of dimethylpolysiloxane. Formaldehyde is a skin
and respiratory sensitizer, eye and throat irritant, acute toxicant, and
potential cancer hazard.
-----------------------------------------------------------------------------Section 11 - Toxicological Information
-----------------------------------------------------------------------------Eyes:
SEE SECTION 3
Ingestion:
"
"
"
Inhalation:
"
"
"
Skin:
"
"
"
Subchronic:
"
"
"
Chronic:
"
"
"
------------------------------------------------------------------------------
75 52
4
Product 939-8XX Page 3 of 5
Order Code: 939874 805
Section 12 - Ecological Information
-----------------------------------------------------------------------------Ecotoxicological Data:
N/A
Chemical Fate:
N/A
-----------------------------------------------------------------------------Section 13 - Disposal Considerations
-----------------------------------------------------------------------------RCRA Class:
N/A
Disposal Method:
Not regulated by RCRA. Dispose of in compliance with state and local
regulations.
EPA Reportable Quantities
------------------------N/A
-----------------------------------------------------------------------------Section 14 - Transportation Data
-----------------------------------------------------------------------------DOT Shipping Name:
NOT REGULATED
DOT Hazard Class:
DOT Label:
UN/NA Number:
N/A
Packing Group:
Special Provisions:
Packaging
--------Exceptions:
Non-Bulk:
Bulk:
Quantity Limitations
-------------------Passenger Aircraft or Railcar:
Cargo Aircraft:
Vessel Stowage Requirements
--------------------------Vessel Stowage:
Other Stowage:
Transportation Notes:
N/A
-----------------------------------------------------------------------------Section 15 - Regulatory Information
-----------------------------------------------------------------------------TSCA Status:
On the TSCA Inventory
OSHA Status:
Considered hazardous based on the following criteria:
Irritant
Sensitizer
Target Organs
------------Kidney
Lung
Spleen
OSHA Hazardous Components
---------------------------------------------CALCIUM CARBONATE (LIMESTONE)
* CRYSTALLINE SILICA (QUARTZ)
IRON OXIDE
* - CHEMICAL IS LISTED AS AN IARC, NTP, OSHA,
CAS Number
-----------1317-65-3
14808-60-7
1309-37-1
or ACGIH CARCINOGEN
Compliance Quantites
-------------------No Compliance Quantities
SARA 311 Ratings
----------------
76 52
5
Product 939-8XX Page 4 of 5
Order Code: 939874 805
Immediate Health Hazard:
Delayed Health Hazard:
Fire Hazard:
Reactivity Hazard:
Sudden Release of Pressure Hazard:
SARA 313 Ingredients
-------------------No SARA 313 Ingredients
N
Y
N
N
N
Proposition 65 Ingredients
-------------------------Chemicals known to the State of California to cause cancer,
birth defects and/or other reproductive harm.
CAS Number
-------------------------------------------------------CRYSTALLINE SILICA (QUARTZ)
14808-60-7
-----------------------------------------------------------------------------Section 16 - Other Information
-----------------------------------------------------------------------------FOR INDUSTRIAL USE ONLY. KEEP OUT OF REACH OF CHILDREN.
THE HAZARD INFORMATION HEREIN IS OFFERED SOLELY FOR THE CONSIDERATION
OF THE USER, SUBJECT TO HIS OWN INVESTIGATION OF COMPLIANCE WITH APPLICABLE
REGULATIONS, INCLUDING THE SAFE USE OF THE PRODUCT UNDER EVERY FORESEEABLE
CONDITION.
77 52
6
Product 939-8XX Page 5 of 5