Busduct System
Schneider Busway
Common Application of Busduct
„ Transformer to Switchboard
Schneider Busway
Common Application of Busduct
„ Horizontal Plug-in Busduct
– Large Scale Factory, e.g. HAECO
Schneider Busway
Common Application of Busduct
„ Vertical Plug-in Riser
– Typical Comm., Ind., Res. in HK
Schneider Busway
Common Application of Busduct
„ Switchboard to Switchboard
– Example: Main Sw Bd to A/C Plant
Schneider Busway
Basic Construction of Busduct
„ Sandwich type construction
„ Less space requirement
„ Improve heat dissipation
„ Reduce temperature rise
„ Higher current rating available
„ Various IP rating available
Schneider Busway
High Grade Copper Busbar
„ High conductivity copper
„ Silver plated over full length, enhance low
contact resistance and high conductivity
„ Thickness of copper bar = 6.3 mm
„ Rectangular design enhance heat dissipation
Schneider Busway
Temperature Rise
„ Sandwich construction and high conductivity
copper busbar Ætemp.rise less than 55oC at
full load
Schneider Busway
Busbar Insulation
„ 2 layers 0.2mm Mylar insulation
(IEC requires 1 layer)
„ Excellent dielectric properties
„ 0.1mm Mylar can withstand 7000V
„ Class B insulation (130oC)
Schneider Busway
Integral Ground Bus
„ 1.6mm Aluminum enclosure
as ground bus
„ 50% continuous capacity
„ Lower ground impedance
„ Comply with international
requirement, UL, IEC, IEE
wiring regulation
Schneider Busway
EZ Joint Pak
„ Schneider Patten Design
„ Single bolt connection
– Double head
– Visible tighten torque
– Belleville washer
– Tighten torque = 105N-m (70
lb-ft)
Schneider Busway
EZ Joint Pak
„ Electroplated surface reduce
contact resistance
„ Each joint pak allows 3 mm
adjustment for thermal
expansion
„ Reduce installation time and
equipment
„ Improve reliability
Schneider Busway
Product Range
„ Feeder, Riser , Plug-in
„ Common Rating 200A-600A & 800A-5000A
„ Rated Voltage = 600V
„ IP rating:
– Feeder : IP40, IP41, IP54, IP65, IP66
– Plug-in / Riser : IP40, IP54
Schneider Busway
Common Fitting
„ Elbows
– Standard 90o
Schneider Busway
Common Fitting
„ Elbows
– Other shape available upon request e.g.
Double elbows, Offset, Elbow + flanged end
Schneider Busway
Common Fitting
„ Flanged End
– For connection to Switchboard
– For connection cable to busduct
Schneider Busway
Common Fitting
„ Expansion Joint
– Allow ±38mm expansion
– Apply where busduct pass through structural
expansion joint
Schneider Busway
Vertical Hangers
„ Fixed hangers
„ Spring Hangers
– Apply in new building
– Eliminate the effect of
settlement
Schneider Busway
Plug-in Units
„ Fusible PIU (30A-1600A)
„ MCCB PIU (16-1600A)
Schneider Busway
Plug-in Units
„ High level of safety
– Complete insulated conductor
– Interlocks
– Contact earth terminal first
Schneider Busway
System Design
„ Cable Vs busduct
„ Choice of breaking capacity, IP rating
„ Earthing system arrangement
„ Voltage drop consideration
„ Provision for expansion
„ Harmonic issue
Schneider Busway
Cable Vs Busduct
„ Busduct system have advantage in high ampere
range, say 600A or up
„ Comparison between cable & busduct
Cable
Busduct
Space requirement
High
Low
Heat Dissipation
Poor
Good
Temperature rise
Poor
Good
Voltage Drop
High
Fair
Electromagnetic Interference
High
Low
Labour Cost
Higher
Lower
Schneider Busway
Choice of Breaking Capacity
„ Breaking Capacity
– Main distribution Vs Submain Distribution
– 1 sec and 3 sec requirement
Schneider Busway
Choice of IP Rating
„ Minimize water hazard
„ Horizontal Vs Vertical
„ Corridor Vs meter room
Schneider Busway
Earthing System Arrangement
„ IGB through out the whole run of busduct
„ No need for additional or external earthing
conductor
„ Each tap-off box bond to IGB
Schneider Busway
Voltage Drop Consideration
„ 4% Voltage drop from source to final circuit
(IEE Wiring Regualtion)
„ Longer the busduct length, Higher the voltage
drop
„ Try to shorten length of busduct
„ Upgrade the busduct, e.g use 1200A busduct
for 1000A circuit
Schneider Busway
Provision of Expansion
„ Thermal expansion
– Busbar thermal expansion absorbed by joint
pack
– No need to install any expansion joint
„ Structural expansion
– Busduct cannot absorb expansion
– Shear force can damage busduct
– Expansion fitting should be installed
Schneider Busway
Harmonic Issues
„ Generated by Non-linear load, e.g. UPS,
Inverters, High frequency lamps
„ Can overheat neutral conductor
„ Alter the operation of Tx, Capacity bank
„ Affect the normal operation of switchgear
Ænuisance tripping
„ 200% neutral busduct cannot solve the
problem
„ Apply power control equipment, like harmonic
filter OR Upgrade the whole busduct
Schneider Busway
Installation Procedure
„ Video of Installation (about 8 minutes)
Schneider Busway
Water / Dust Precaution
„ Provide alternative path / heating point
„ Damage insulation
„ Latent hazard of short circuit
„ Measurement
– Double packing (plastic bag+carton box)
– Apply “rain coat” provided by manufacturer
after installation each day
– Proper storage management
Schneider Busway
Water / Dust Precaution
„ Double packing (plastic bag+carton box)
Schneider Busway
Water / Dust Precaution
„ Double packing (plastic bag+carton box)
Schneider Busway
Water / Dust Precaution
„ Apply “rain coat” provided by manufacturer
after installation each day
Schneider Busway
Water / Dust Precaution
„ Proper storage management
Schneider Busway
Quality Project Management Services
„ Product Training
„ Site Measurement
„ Optimum busduct routing design
„ Detail shop drawing preparation
„ On site technical support
„ Training on installation procedure
„ “Missing Link” and “Remedial Units”
„ Joint inspection (not contractual service)
Schneider Busway
Missing Links / Remedial Units
„ Missing link – reserve 1 pc of busduct for final measurement
– Increase accuracy of busudct dimension
– Save time for rectifying installation mistake
– Streamline the installation
Missing Link
Schneider Busway
Missing Links / Remedial Units
„ A neighborhood factory enhance fast delivery of
missing links and remedial units (within 1 week
delivery to HK)
Schneider Busway
Contractor-Supplier Interaction
Project Start
Technical support
and routing deisgn
After sales services
and missing links
AutoCad Drawing
Installation support
We are not only a
busduct supplier
Project
Management
Support
BRASS and
manufacturing
instruction
Fabrication
Schneider Busway
Testing & Commissioning - Factory
„ Factory Test – 7500V dc Hi-pot
Test
„ 100% test before delivery
„ Insulation = 10MΩ/ ft
– (IEC require 1MΩ/ ft )
„ Check weak point of insulation
Schneider Busway
Testing & Commissioning – On Site
„ Mega test before any energization
– NEMA:
MΩ =100/ Length of Busduct in Ft (1000V)
– HK Code of Practice
0.5 MΩ at 500Vdc
„ Ductile test of entire length
„ Joint inspection by both contractor and supplier
– Alignment, Installation procedure,etc
Schneider Busway
Maintenance Issues
„ Vertical spring hanger adjustment
„ Bowing Symptom
„ Thermal checking/ scanning
Schneider Busway
Vertical Spring Hanger Adjustment
„ Adjustment need after a period of usage, esp
new building
„ Make compensation for settlement and
concrete shinkage
Schneider Busway
Vertical Spring Hanger Adjustment
„ Adjust the length of spring to provide adequate
vertical support to busduct
Schneider Busway
Bowing Symptom
Schneider Busway
Bowing Symptom
„ Common causes
– Misalignment
– Improper installation, e.g. loosen bolts
– Improper vertical support
„ Uneven pressure or expansion force the
busduct to bend at “weak points”
„ Bowing can make permanent deforming of
busduct
Schneider Busway
Thermal Checking / Scanning
„ Improper installation Æ poor contact
„ Abnormal temperature rise (usually
happened in joints)
„ Collect temperature data and compare
„ Find out the abnormal heating point and
rectify
Schneider Busway
Trouble shooting
„ Common causes of burnt busduct
– Water/dust ingress during installation stage
– Water ingress after energize (for IP40
mainly)
– Improper installation, e.g. misalignment,
lossen bolts
„ Some real examples
Schneider Busway
Some Real Examples
Schneider Busway
Some Real Examples
Schneider Busway
Some Real Examples
Schneider Busway
Some Real Examples
Schneider Busway
Some Real Examples
Schneider Busway
Some Real Examples
Schneider Busway
Some Real Examples
Schneider Busway
Some Real Examples
Schneider Busway
Some Real Examples
Schneider Busway
Some Real Examples
Schneider Busway
Some Real Examples
Schneider Busway
Some Real Examples
Schneider Busway
Trouble Shooting
„ Recommend spare parts
– 1 pair of flanged ends for each busduct
rating used
– A number of plug-in units
„ 24-hours services hotline provided by
Schneider Busway
– 7298 9771(for HK Market)
Schneider Busway
End of Presentation!
Thank you!
Schneider Busway