Installation and Operating Manual

Transcription

Installation and Operating Manual
COMBINATION BOILER
Heating only (system)
Heating + sanitary hot water together (system plus)
Fanned Flue System
Installation and Operating Manual
TH
ER
M O R E G U L AT I
ON
MODE
MAN
AUTO
TEMP
C O M PAT I
GB
BL
E
C
Contents
Installer’s instruction
Page
12345678910 11 12 -
description...........................................................................................................
dimensions ..........................................................................................................
water specifications .............................................................................................
installation requirements .....................................................................................
air intake and burnt gas outlet connections.........................................................
fitting the boiler....................................................................................................
electrical connections..........................................................................................
starting up ...........................................................................................................
fitting the casing ..................................................................................................
gas conversion ....................................................................................................
fault codes ..........................................................................................................
points to note.......................................................................................................
3
4
4
5
6
8
9
10
12
13
14
15
User’s instruction
Page
13 14 15 16 17 18 19 20 -
controls................................................................................................................
operation .............................................................................................................
maintenance........................................................................................................
safe evacuation of combustion products .............................................................
warranty...............................................................................................................
practical advice ...................................................................................................
operating faults....................................................................................................
technical specifications .......................................................................................
2
16
17
18
18
18
18
19
20
INSTALLER’S INSTRUCTION
1. Description
1
1.- sheet steel frame with expansion vessel
2.- sealed casing
3.- hood with extractor fan
4.- copper main heat exchanger
5.- combustion chamber
6.- multigas burner comprising:
•
a removable injector manifold
•
an ignition electrode
•
a flame detection electrode
7.- gas valve assembly comprising:
•
two safety solenoid valves
•
a control solenoid valve
8.- circulating pump with automatic vent
9.- overheat sensor
10.- main heat exchanger inlet thermistor
11.- main heat exchanger outlet thermistor
12.- electronic control unit
14.- flue gas pressure control switch
15.- ignitor
16.- central heating pressure relief valve
19. - heating circuit pressure gauge
2
3
14
4
9
5
11
10
6
8
12
20. - ON/OFF push button and ON indicator light
21.- sanitary accumulation start button and tank
temperature setting button
22.- heating function ON and heating temperature
adjustment knob
23.- heating temperature and operating faults indicator
24.- orange burner operating indicator light
25.- reset push button and red locking indicator light
Fig.1
7
16
15
Fig.2
23
24
C
Fig.3
19
20
21 (system plus)
22
3
25
2. Dimensions
Measurements in mm
289
21
Safety valve outlet
Heating flow and tank
K
Tank backflow (system plus)
L
Gas inlet
M
Cold water supply
N
Heating backflow
Weight with packaging:
24 kW: 32 kg
30 kW: 33 kg
691,5
720
141
I
J
172,5
121,5
4,7
I
JKLM N
I
450
forpour
maintenance
450min.
mini
entretien
32
296
440
390
54 54 54 54
▲
Fig.4
J K L M N
3. Hydraulic characteristics
Pressure available
Pression disponible
mCE
6
The boiler is fitted with an automatic by-pass as standard.
Minimum
flow(robinets
rate withthermostatiques
the heating thermostatic
valves closed
Débit mini
fermés)
The graph (fig. 5) shows the development of the pressure
available in relation to flow (on exit from the boiler).
5
3
To ensure correct operation, the minimum flow of the
installation must be 300 l/h. (Thermostatic taps closed).
2
Capacity of the installation.
1
The boiler is fitted with an expansion vessel.
4
0
100
200
300
400
500
600
700
800
900
1000
1100
1200
Maximum. volume of expansion vessel: 6 litres.
l/h
Pressure: 0,7 bar.
Fig. 5
The volume of the expansion vessel in a pressurised
installation varies according to:
Pression àcircuit
froid pour
le circuitwhen
chauffage
bar)
Heating
pressure
cold(en
(bar)
PfPf
- the average operating temperature in °C
2,0
1,9
1,8
- the static height (which is the difference in metres
between the highest point of the installation and the
expansion vessel axis).
40°C
1,7
1,6
50°C
1,5
The minimum cold filling pressure of the installation is 0,7
bar (recommended pressure between 1.2 and 1.7 bar).
1,4
60°C
1,3
70°C
1,2
The pressure of the expansion vessel should always be
greater than the static height (in metres) divided by 10.
80°C
1,1
1,0
20
40
60
80
100
120
140
160
180
200
220
240
280
C
Maximum
system
capacity
(litres)(en litres)
Capacité
maximale
de l'installation
Water content diagram.
Pf = Cold pressure in bar
C = System capacity in litres
260
Fig. 6
4
4. Installation requirements
4.1 REGULATIONS
4.2 BOILER LOCATION
PRIVATE HOMES
- the centre line of the external flue duct must be placed at a
distance of at least 0.40 m from any opening window and
a distance of at least 0.60 m from any ventilation hole
(depending on the type of outlet chosen, refer to the flue
kit instructions)
- if the boiler is installed in a bathroom, comply with the special safety regulations in French standard NF C 15-100
(section 7)
- never install the boiler above hot-plates or ovens or in
general over any equipment producing greasy vapours
which could make the boiler dirty and affect its operation
- prepare a wall and mountings able to support the weight of
the boiler (weight: approx. 35 kg)
- take precautions to reduce noise
STATUTORY REQUIREMENTS FOR INSTALLATION AND
MAINTENANCE
Installation and maintenance of the equipment must be carried out by a qualified professional in accordance with current legislative texts and state of the art, including:
- law of 2 August 1977
Technical and Safety rules applicable to combustible gas
and liquefied gas petroleum installations located inside
buildings or outbuildings
- law of 5 February 1999 modifying the law of 2 August
1977
after replacing a boiler with an identical one (same alignment and area as the previous equipment), the installer
must make out a "model 4" certificate of conformity
- Standard DTU P 45-204 gas installations (previously DTU N°61-1 - Gas
Installations - April 1982 + additional clause N°1 of July
1984)
- Regional Health Regulations
4.3 DESIGNING AND CARRYING OUT THE INSTALLATION
Domestic hot water circuit (system plus)
- Avoid excessive loss of charge in preheating circuit
- if the water hardness is more than TH 25, install a water
softener
- if a non-return valve is present, a device allowing for
expansion is required (available as an option)
See domestic hot water technical directive (DTU)
Protection of the drinking water network:
• articles 16-7 and 16-8 of the Regional Health Regulations
require the installation to have a CB type disconnection
device with various non-controllable pressure zones,
conforming to the functional requirements of French
Standard NF P 43-011, to prevent heating water being
returned to the drinking water network
• an NF backflow preventer is fitted in the boiler's tap fittings unit
Central heating circuit
Circulation flow rate:
- when working out the measurements, be careful to maintain a minimum flow rate of 300 I/h with the thermostats
closed
• French Standard NF C 15-100 - Low voltage electrical
installations - Rules
Precautions against corrosion
Operating faults due to corrosion are likely to occur if the
system is built with components made of different materials.
To prevent such problems it is advisable to use a corrosion
inhibitor.
Take every precaution to prevent the treated water from
becoming corrosive.
Old installation:
- fit a sediment trap to the lowest point on the return and
treat the system correctly
Recommendation:
- fit bleed valves on all radiators and to high points of the
installation; also fit drain cocks to low points
PUBLIC BUILDINGS
STATUTORY REQUIREMENTS FOR INSTALLATION
Installation and maintenance of the equipment must be carried out by a qualified professional in accordance with current legislative texts and state of the art, including:
- fire safety and panic control regulations for public
buildings:
a) General requirements
for all equipment:
• GZ articles
combustible gas and liquefied gas petroleum installations
• CH articles
heating, ventilation, refrigeration, air conditioning, steam
and domestic hot water production
b) Special requirements for each type of building with
public access (hospitals, shops, etc.)
Recommendation:
if the area is exposed to the risk of lightning (isolated installation at the end of an electricity line, etc.) install a lightning conductor
Our warranty is subject to this requirement.
5
5. Connecting gas intake and exhaust ducts
The boiler should only be installed with a fresh air inlet and smoke outlet device supplied by the boiler manufacturer.
The kits are supplied separately from the boiler to meet the requirements of various types of installation. For more information
about inlet/outlet accessories, refer to the accessories catalogue and the installation instructions inside the kits. The boiler is
pre-equipped for connection to coaxial or twin flow air intake and burnt gas outlet systems.
Warning
The exhaust gas ducts should not be in contact with or close to
inflammable material and should not pass through building structures or
walls made of inflammable material.
When replacing an old appliance, the gas intake and exhaust duct system
will also have to be changed.
Important
Ensure that the gas intake and exhaust
passages are not blocked.
Ensure that the exhaust gas ducts do not
have leaks.
5.1 TYPE OF COAXIAL OUTLET (C12, C32, C42) xx
118
Lmax =L 4 m
Ø 60/100
60/100mm
mm
Concentric outlet
60/100
Restrictor
Ø 41 - 24 kW
Ø 42 - 30 kW
Restrictor
ø 45
Without Restrictor
24 kW
L 0.3 to 0.75 m
L = > 0.75 to 2.5 m
L = > 2.5 to 4 m
30 kW
L 0.3 to 0.5 m
L = > 0,5 to 2 m
L = > 2 to 4 m
5.2 TWIN FLOW FLUE TYPE (C12, C32, C42, C52, C82) xy
There is also the possibility of using an exhaust gas duct with separate tubes by using
an adaptor on the outlet header and by inserting the tube in the air intake envisaged for
this purpose.
In order to use the air intake, you should:
1) Take the air intake cover off
2) Assemble the flange on the header supplied with the boiler
3) Assemble the membrane, if necessary, on the tube or the elbow
4) Insert the header on the tube or the elbow up until the lower stop
(you do not have to use the washer).
5) Insert the elbow/header in the boiler air intake hole and fasten it with screws.
162
200
123,5
123,5
200
25
107
230 MIN *
132
If the two elbows or in
the same lateral
direction and if you
need to reduce the
required space, the
minimum 230 mm
measurement can be
reduced by carefully
cutting the elbow below
the air inlet by 25 mm.
6
ø 100
In the special case where the connection
is with separate tubes and with the boiler
installed at a minimum distance of 6 cm
from the wall, make a 10 cm ø hole, thus
enabling better assembly between the
fresh air elbow and the tube outside the
wall (see diagram).
60 mm
24 kW twin flow outlet
Ø 41 Restrictor
Ø 45 Restrictor
Without Restrictor
C12, C32, C42 80/80
L = 0 to 5.5 m
L = 5.5 to 21 m
L = 21 to 33 m
C52, C82 80/80
Fresh air intake length 1 m.
L = 0 to 9 m
L = 9 to 43 m
L = 43 to 67 m
30 kW twin flow outlet
Restrictor ø 45
Without Restrictor
C12, C32, C42 80/80
L = 0 to 5,5 m
L = 5,5 to 20 m
C52, C82 80/80
Fresh air intake length 1 m.
L = 0 to 17 m
L = 17 to 43 m
L = total length of air intake and burnt gas exhaust ducts.
If the burnt gas flue length is over 5.5 m, install a condensate trap.
The maximum development value L, mentioned in the table includes the exhaust gas/fresh air terminal and for the coaxial
system also takes into account an elbow. The C52 outlets should respect the following instructions:
1- Keep the same 80 mm ø for the gas intakes and exhaust gas ducts.
2- If you need to insert elbows in the gas intake and exhaust gas ducts, you should consider for each one the equivalent length
to be included in the calculation of developed length.
3- The exhaust gas duct should jut above the roof by at least 0.5 m.
4- The intake and exhaust gas ducts in C52 cannot be installed on opposite walls of the building.
Diagrams illustrating some typical coaxial and twin flow
installations.
For more detailed information concerning exhaust gas ducts and
fresh air intakes, consult our accessory catalogues.
Concentric
5.3 FITTING THE RESTRICTOR
Warning
If the selected exhaust gas duct is planned
to be fitted with a restrictor as indicated in
the corresponding tables, then the
installation of the restrictor is compulsory.
7
twin flow
6. Fitting the boiler
- place the paper installation jig in the selected position on the wall
- fit the hanging bracket
- bring the water pipes and the electrical connection to the locations shown on the fitting template
- remove the 2 locking screws A which secure the front panel (fig. 7)
- remove the front panel
- offer the boiler up to its bracket and allow it to drop into position while pressing on it (fig. 8)
- ensure water and gas connections using the various seals required (rubber seal for gas) and position the metal filter in the
heating backflow connection.
Safety valve drain hole 16 MUST be connected to a waste water pipe.
Fit the flue device according to the type of connection chosen, referring to section 5
Cleaning the appliance
Once the water has been connected, it is essential to clean the installation with an appropriate product (dispersing agent) to
remove filings, solder, and various factory oils and greases.
The use of any solvent or aromatic agent (petrol, oil etc.) is forbidden.
We recommend treating the whole heating system as soon as it is commissioned to maintain a pH between
9 and 9.5.
A
A
1
2
Fig. 7
Fig. 8
31. Central heating flow isolating valve and tank
32. Tank backflow (system plus)
33. Gas service tap
34. Cold water supply
35. Central heating return isolating valve
16
31
32
33
34
Fig. 9
35
8
7. Electrical connections
Regulations:
- in accordance with the regulations, an all-pole isolating device with a contact opening gap of at least
3 mm must be installed in the boiler's stationary
power supply installation
B
- the boiler must be connected to a fixed junction
box using the cable supplied
Location of connections:
- the 230 V supply lead and room thermostat inputs
must be fitted on the wall at the height specified
on the fitting template
P
• the boiler is supplied with 230 V by a twin and
earth lead supplied with the appliance
• room thermostat (TA): prepare a free length of
at least 50 cm where the TA lead meets the
wall
P
C
Fig.10
Access to the boiler room thermostat connection:
- the room thermostat is connected behind the boiler control unit
230 V and earth connection via the lead provided at J1
Important: If the power supply cable is damaged, it should be replaced by the manufacturer, the after-sales service or
a person with a similar status, in order to avoid potential danger.
Room thermostat connection
When it leaves the factory, the boiler is set to operate without a room thermostat: a shunt S is fitted on connector D. A room
thermostat can be connected to this connector
- lower the electronic control unit by releasing the side locking pins P, to gain access to the rear side
- remove screws B and remove cover C (fig. 10)
The room thermostat connection can then be accessed.
- remove connector D
- connect the thermostat in place of shunt S
- reconnect connector D
Connector J12 shown (fig. 11), is ready to connect an optional programmer (refer to the relevant instructions if necessary).
System Plus
System
T
J1
E
Shunt between
1 and 2
E
P2
P3
P1
B4
B3
B2
B1
A4
A3
P1
A2
A1
ON
OFF
B4
B3
B2
B1
A4
230 V 2P
+ E lead
A3
A2
J1
A1
D
Shunt between
2 and 3
J12
S
J12
Fig. 11
9
Cylinder
thermistor tank
thermistor
8. Operating
PRESSURISATION (fig. 12)
Heating circuit and tank:
- open cold water tap 34
- check that the heating flow 31, heating backflow 35 and tank backflow 32 taps (compy system plus) are open
- open filling tap 36
- close the tap again when the needle of pressure gauge 19 (fig. 3) is at the pressure specified in § 3
- drain the installation and re-establish the pressure
Gas circuit
- open gas tap 33
- flush the gas circuit
- check the whole gas line for leaks
31
Fig. 12
32
36
33
34
35
SETTINGS
The boiler is supplied with all the adjusting knobs set to OFF (fig. 13) and the potentiometers turned fully clockwise. It is
possible to adjust these settings if required.
In that case, it is necessary to open the electronic control unit.
Switch off the boiler, remove the casing and open the unit by pressing the 2 tabs P (fig. 10). The adjusting knobs are on the
electronic circuit board behind blanking cover E (fig. 11).
- A1 is used to set the Heating Anti-cycle Time (HAT) period to 30 seconds or 3 minutes
HAT: period during which restarting the burner is prohibited during a heating regulation phase
- A2 allows the speed of the pump in heating mode to be selected (high speed or adaptive speed)
- A3 is used to adjust the heating temperature setting to 40 °C whatever the position of the heating temperature adjustment
knob 22 (fig. 3)
- A4 enables operation in modulating heating mode or all or nothing mode
- B1 allows the duration of post-circulation in heating mode to be adjusted
- B2 allows the domestic hot water time delay (TIC) to be adjusted
- B3 not used
- B4 not used
N.B. After a power cut or a board reset, the HAT is cancelled for 3 minutes.
- P1: potentiometer for reducing the heating power (see table page 11)
- P2: potentiometer for adjusting the ignition power (12,7 kW - 24 FF / 16 kW - 30 FF)
- P3: not used
Once adjustments have been made, replace blanking cover E, close the control unit cover and refit the casing.
10
8. Operating (continued)
P2
P1
P3
ON
ON
B4
Tempo Débistat Sanitaire 1,5 sec
TIC 3 min.
Tempo Débistat Sanitaire 0 sec
TIC 30 sec.
B1
Post-circulation
ss
Post circulation3030
Post-circulation
Post circulation3 3min.
mn
A4
Modulating
Operation
Fonctionnement
Modulant
A3
ON/OFF
operationTOUT OU RIEN
Fonctionnement
Heating
setting
to 40 °C
Consigne
chauffage
à 40 C
A2
Pompe speed
Petite Vitesse
Adaptive
pump
Pompe
Grande
High
speed
pumpVitesse
A1
30 s
30Anticycle
s anticycle
3 min
3Anticycle
min anticycle
B3
B2
ON
OFF
OFF
Célectic
Consigne chauffage
variable
35 °C
à 85 C
Adjustable
heating setting
35 de
to 85
OFF
Fig.13
Factory settings
Burner gas output setting
The values shown in the tables below are given for information purposes for a nominal gas distribution pressure, to allow any
adjustments to the boiler heating output according to the requirements of the appliance.
They cannot be used to calculate the precise regulated output of the water heater.
24 FF
Gas
G20
30 FF
PROPANE
BUTANE
Gas
Pressure
plate
(mm CE)
Working P.
(kW)
G20
PROPANE
BUTANE
Pressure
plate
(mm CE)
Working P.
(kW)
10
25
74
55
12
27
69
12,7
38
117
89
16
43
112
85
16
57
182
137
20
63
167
131
20
86
276
204
25
98
254
202
24
120
390
282
30
140
359
287
11
48
9. Fitting the casing
Fitting the casing
Remove the protective film on the casing:
- offer the casing up (fig. 14)
- engage hooks N in notches R operation 1
- fit the top of the panel in place
- close the panel mounting clamps (fig. 15)
N.B. It is essential to refit the locking screw A
1
A
R
Fig.14
N
Fig.15
12
10. Gas conversion
When changing to a gas different from the one for which the boiler is equipped, you should replace the parts supplied with the
conversion kit and adjust the gas valve in accordance with the method described below.
2
Adjusting the nominal output
• remove the protective cap from the adjusting
screws (fig. 16).
• remove screw 2 and fit a tube connected to a
pressure gaugeto the pressure connection point
(fig. 16).
• start the boiler at maximum output (hot water tap
on full) and maximum temperature setting.
• turn nut 3 using an 8-mm open-ended spanner
(fig. 17) while holding screw 4 still and adjust the
pressure to the value shown in the table
“nominal output table.”
Fig.16
Adjusting the minimum output
• disconnect a variable solenoid valve power
supply cable (fig. 18)
• turn screw 4 using a 5-mm open-ended spanner
while holding nut 3 (fig. 18) and adjust the
pressure to the value shown in the table
“minimum output table.”
3
Fig.17
4
• when the adjustment is finished, refit screw 2
and test for leaks.
• put the protective cap back on the adjustment
screws.
Adjusting the lighting power (only in FF)
The potentiometer P2 (fig. 14) on the printed circuit
is used for this adjustment
(12,7 kW - 24 FF / 16 kW - 30 FF)
(see tables page 11)
Fig.18
Nominal output
Minimun output
mmCE
G 20
G 30
G 31
mmCE
G 20
G 30
G 31
24 kW FF
120
282
390
24 kW FF
25
55
74
30 kW FF
140
287
359
30 kW FF
27
48
69
13
11. Fault codes - Information
If the equipment has an operating fault, one or more LEDs (23) flash according to the type of fault listed in the table below.
CODE
30 40 50 60 70 80
FAULT
INFORMATION
1
Locked - overheating.
3
Locked by ignition fault.
6
7
Water circulation absent.
8
Input water circulation fault.
11
Main exchanger outlet sensor open.
12
Main exchanger outlet sensor short-circuited.
13
Main exchanger inlet sensor open.
14
Main exchanger inlet sensor short-circuited.
15
External sensor open.
16
External sensor short-circuited.
18
20
Wiring fault (or 1.25 A fuse fault).
21
No extraction flow.
22
Extraction sensor fault.
28
Clima Manager "Module Counter" memory card faulty.
29
Clima Manager room sensor open.
30
Clima Manager room sensor short-circuited.
31
Fault on display board.
32
Communication problem between main boards and display.
Frost protection.
Disappearance of current flame.
= LED off
= LED blinking
14
12. Particular characteristics
By-pass valve assembly direction
15
INSTRUCTIONS FOR THE USER
13. Controls
23
24
C
20
19
21 (system plus)
25
22
Fig.20
Control panel (fig. 20)
Taps and valves (fig. 21)
19. - heating circuit pressure gauge
31. Central heating flow isolating valve and tank
20. - ON/OFF push button and ON indicator light
32. Tank backflow (system plus)
21.- domestic hot water function ON and hot water
33: Gas tap
34: Cold water supply tap
temperature adjustment knob
35: Central heating return isolating valve
22.- heating function ON and heating temperature
36: Filling tap
adjustment knob
16: Heating safety valve
23.- heating temperature and operating fault indicator
24.- orange burner operating indicator light
25.- reset push button (reset) and red locking indicator light
16
31
32
33
34
Fig. 21
16
35
36
14. Operation
Starting up
1. check that the appliance's general gas shut-off tap is open and that the boiler is supplied with power.
2. check that there is sufficient pressure in the heating circuit: pressure gauge needle at least 1.2 bar with 1.7 bar at max. cold
3. open gas inlet tap 33 (fig. 21)
Your boiler is now ready to operate.
Important
When the appliance is operated after a prolonged period of inactivity, the presence of air in the gas flues may hinder the first
attempts at igniting the gas.
See § 20 Operating faults
To obtain heating and hot water (system plus):
Press ON/OFF button 20; the button lights up green.
- turn knob 21
to preheat the sanitary tank (compy system plus). This button allows you to adjust the hot water
temperature. While the tank is pre-heating, LEDs 23 light up 2 by 2 in sequence.
- turn knob 22
to authorise heating ignition. This knob allows you to adjust the water temperature in the heating circuit
according to seasonal requirements. Indicator 23
displays the temperature.
• Turn knob 22:
- towards Max. in cold weather
- towards Min in mild weather
Furthermore, if your home is fitted with a room thermostat, set it to the desired indoor temperature.
N.B. Orange indicator light 24
lights up every time the burner ignites
Stopping the heating
- Set knob 22 to the OFF position. The boiler then produces only hot water.
Setting to pilot
- Set knobs 21 and 22 to the OFF position, leaving button 20 (fig. 20) lit. The function remains active unless the boiler freezes.
Turn off the boiler completely
- press push button 20 and the light goes out
- turn off the electricity supply to the boiler heater.
- shut off the gas supply by turning tap 33 (fig. 21)
Note:
In certain cases of installation it is possible that, after reheating the tank (system plus), the pipes (and possibly a radiator) may
heat up slightly. To prevent this, simply close heating inlet tap 31 (fig. 21).
Remember to re-open it at the start of the heating season, when you switch the heating back on by pressing button 22 (fig. 20)
17
15. Maintenance
Current legislation requires a mandatory annual service of your water heater.
Once a year, have it checked by a qualified professional.
Annual service contract formats may be suggested to you by service providers for all boiler servicing. Contact your gas fitter or
our commercial services.
The manufacturer's warranty, which covers manufacturing faults, should not be confused with servicing operations.
16. Overflow safety device
This boiler is equipped with a flue gas extraction flow detection system which authorises operation of the burner.
If the flow is insufficient for a prolonged period of time, the boiler shuts down for safety reasons and indicator lights (23) 40, 60
and 80 flash.
Warning: this flue gas checking device must not be disconnected or have unwarranted work carried out on it.If it needs to be
replaced, only original parts may be used.
17. Warranty
Your boiler is under warranty. The warranty certificate specifies the warranty conditions: check that the detachable section of
this certificate has been returned to Chaffoteaux & Maury.
A qualified professional must have installed, adjusted and commissioned your installation if you wish to take advantage of the
warranty. This assures you that the fitter complied with the installation manual and that regulatory and safety conditions have
been met.
Your first boiler technical inspection will be carried out free of charge at your request by a qualified Chaffoteaux & Maury technical station professional.
18. Practical advice
• Pump degumming system
With the boiler switched on (indicator light 20 lit), the circulating pump operates for 1 minute after it has been stopped for
longer than 23 hours, irrespective of the boiler's operating mode, to prevent the pump from sticking.
Precautions to take in freezing conditions
We recommend that you contact your gas fitter or After-Sales service, who will advise you of the measures to take according to
your circumstances.
• Domestic hot water circuit (system plus)
The hot water circuit is drained after closing the appliance's water counter and cold water tap:
- open a hot water tap
- Drain the tank
• Heating circuit
Take one of the following steps:
- 1) drain the circuit of the heating appliance
- 2) protect the heating installation with an antifreeze product. Periodically checking the level of protection provided by this
antifreeze is an additional warranty requirement.
- 3) allow your installation to run at low load by setting the room thermostat to the antifreeze position (between 5 and 10°C).
- 4) leave the power to the boiler on. It is fitted with an antifreeze device which activates the circulation pump, then the
burner.
18
19. Operating faults
Fault
Cause
Solution
The boiler doesn’t start
No gas, no water or no electricity
Air in the gas pipe
Follow procedure in chapter 8
Room thermostat switched off
Set up the room thermostat
Wait for a few minutes
Press on reset button 25 (fig.20) the red
led turn off and the boiler attempts to relight.
If red indicator alight too frequently,
please call your localfaîtes service centre.
Red indicator alight
Noises in CH system
Control gas, water and electrical
supply, fuses…
Air presence in CH system or. Insufficient Purge of air the system and rise up the
pressure
system pressure (chapter 7)
If all these actions are unsuccessful, call a qualified professional.
19
20. Technical specifications
Model
Heating power
Pn
Variable tank pre-heating power
24 kW FF
30 kW FF
10 to 24 kW
12 to 30 kW
24 kW
Pn max
30 kW
Category
II 2E+3+
Fresh air flow rate required for combustion
V
Associated BACD tank capacity
Specific domestic hot water flow rate (ΔT: 30 K)
D
43 m3h.
54 m3h.
120
150
120
150
22,2 l/mn
24,6 l/mn
23,0 l/mn
25,3 l/mn
Minimum central heating circuit flow rate
300 I/h.
Maximum heating circuit pressure
Adjustable heating flow temperature
Adjustable hot water temperature (system plus)
Electric voltage
300 I/h.
3 bar
3 bar
35 to 85 °C
35 to 85 °C
Pw max
40 to 60 °C
40 to 60 °C
230 volt, single phase
230 volt, single phase
50 Hz
50 Hz
Electrical power consumption
150 W
150 W
Electrical protection
IP X4D
IP X4D
Nominal gas flow rate (15 °C-1013 mbar)
Gas rate max Gas rate mini Gas rate max Gas rate mini
Qn
26,0 kW
12,0 kW
32 kW
14 kW
34,02 MJ/m3 at 20 mbar
Vr
2,75 m3/h
1,27 m3/h
3,44 m3/h
1,50 m3/h
G 30 (Butane)
45,6 MJ/kg at 28-30 mbar
Vr
2,05 kg/h
0,95 kg/h
2,56 kg/h
1,12 kg/h
G 31 (Propane)
46,4 MJ/kg 37 at mbar
Vr
2,02 kg/h
0,93 kg/h
2,52 kg/h
1,10 kg/h
Nat
Prop
Nat
Prop
G 20 (GN H -Lacq)
Feeder marking
Marking
NAT Gaz 135 LPG Gaz 80 NAT Gaz 130 LPG Gaz 80
Injector size in 1/100 of mm
135
80
130
80
No. of injectors
11
11
14
14
These boilers are designed to operate with natural gas or LPG. If the type of gas is changed, only a qualified professional is
authorised to carry out this operation.
MTS sa
Le Carré Pleyel
5 rue Pleyel
93521 SAINT DENIS Cedex
Tél. 01 55 84 94 94
Fax 01 55 84 96 10
www.chaffoteaux-maury.fr
420010058000 - 09/2006
C