Technical Update EU86 Title KS1000 RW / LPCB insulated roof panel with FAWS (Factory Applied Weather Seals) Date June 2014 The purpose of this envirocare update is to ensure that you are aware of the revised end lap and side lap details for the KS1000 RW / LPCB insulated roof panel, when used in conjunction with FAWS (Factory Applied Weather Seals). The changes relate to the positioning of the panel stitching screws at the panel to panel end lap detail. The first change relates to the position of the first and second stitching screws with: The first stitching screw on the panel side lap (at the end laps) is now positioned 35mm up from the panel end lap; The second stitching screw now positioned 170mm up from the panel end lap. Thereafter the stitching screws are located at 450mm centres. The second change is that the end lap stitching screws, positioned on the intermediate crowns are positioned 35mm up from the panel end lap. Please find enclosed the full set of revised construction details for the KS1000 RW / LPCB insulated roof panel with FAWS (Factory Applied Weather Seals). We can also supply this Technical Update EU86 in Word format and DWG format should you require. Should you have any queries on the above or require further information, please do not hesitate to contact the undersigned. Regards James Patrick M.I.o.R envirocare Technical Services Manager Licensed BREEAM Industrial Assessor (e) [email protected] (t) 0800 587 0090 Page 1 of 6