Room and Small Commercial Air Conditioners
Transcription
Room and Small Commercial Air Conditioners
Technical Study Report ROOM AND SMALL COMMERCIAL AIR CONDITIONERS This report was produced under the project entitled “Supporting Action on Climate Change through a Network of National Climate Change Focal Points in South-east Asia” (SEAN-CC) implemented by UNEP and funded by Ministry of Foreign Affairs of the Government of Finland. Dec 2011 Room and Small Commercial Air Conditioners Contents SECTION 1: INTRODUCTION 1 1.1 Types of air conditioner2 1.2 Major manufacturers and market shares in ASEAN3 1.3 Efficiency of air conditioner4 SECTION 2: OUTLINE OF AIR CONDITIONER 5 2.1 Major components of air conditioner6 2.2 Refrigeration cycle7 2.3 Characteristics of refrigerant8 SECTION 3: COMPRESSOR 9 3.1 Types of compressor10 3.2 Compressor efficiency18 3.3 Latest technology in development and commercially available19 SECTION 4: EXPANSION DEVICE 20 4.1 Types of expansion device21 4.2 Capillary tube22 4.3 Thermostatic expansion valve22 4.4 Automatic expansion valve25 SECTION 5: HEAT EXCHANGER 27 5.1 Types and sub components of heat exchanger28 5.2 Evaporator30 5.3 Condenser32 SECTION 6: FAN, MOTOR AND INVERTER 33 6.1 Fan34 6.2 Motor35 6.3 Inverter37 SECTION 7: REFRIGERANT 39 7.1 Types of refrigerant40 7.2 Properties and characteristics of refrigerants41 7.3 Technological developments in refrigerant use46 Room and Small Commercial Air Conditioners 8 THE TECHNOLOGY FOR AIR CONDITIONER IN ASEAN REGION, 47 AND LIFE-CYCLE ASSESSMENT OF AIR CONDITIONER 8.1 The most commonly used technology for room and small commercial air conditioners in the ASEAN region 49 8.2 The alternative technology of ASEAN countries under the Montreal protocol 50 8.3 The policies and market incentives based on low- or zero-GWP refrigerant in ASEAN region 52 8.4 Life-cycle assessment of energy and green house gas for air conditioner 52 REFERENCES 56 Room and Small Commercial Air Conditioners LIST OF TABLES Table 1-1 Differences between room and small commercial air conditioners 2 Table 1-2 Major air conditioner manufacturers in ASEAN countries 3 Table 3-1 Comparison of inverter compressor and conventional compressor 19 Table 7-1 Refrigerant safety classification 41 Table 7-2 General information of several commonly used refrigerants 43 Table 7-3 Operational information of several commonly used refrigerant 44 Table 7-4 Thermal physics and environmental characteristics for possible R22 substitutes 45 Table 7-5 Thermal performance of various kinds of R22 substitutes 46 Table 7-6 Inflammable limits of several kinds of inflammable R22 substitutes46 Table 8-1 Table 8.1 Results of life-cycle assessment 55 LIST OF FIGURES Figure 2-1 Window-type air conditioner6 Figure 2-2 Split-type air conditioner6 Figure 2-3 Major components in an inverter split-type air conditioner6 Figure 2-4 Basic vapor-compression refrigeration cycle7 Figure 2-5 The saturated pressure with temperature of some refrigerants8 Figure 3-1 Five major types of compressors10 Figure 3-2 Fully welded hermetic compressor and semi-hermetic compressor11 Figure 3-3 The internal working of a fully welded hermetic compressor11 Figure 3-4 The working parts of a semi-hermetic compressor12 Figure 3-5 Events inside a reciprocating compressor during the pumping action12 Figure 3-6 Cross section of a scroll compressor 14 Figure 3-7 Process of forming continuous crescent-shape gas pockets in the scroll 14 Figure 3-8 Scroll orbit in a real scroll compressor 15 Figure 3-9 Cross section of a rotary compressor15 Figure 3-10 Operation of a stationary van rotary compressor16 Figure 3-11 One stage of compression as refrigerant moves through the screw compressor17 Figure 3-12 Centrifugal compressor18 Figure 3-13 Smooth speed charge scroll compressor with neodymium DC motor19 Figure 4-1 Capillary tube connected with liquid-line21 Figure 4-2 Thermostatic expansion valve21 Figure 4-3 Automatic expansion valve21 Figure 4-4 Capillary tube in a refrigerating system22 Figure 4-5 A filter-drier protects the capillary tube from circulating particles 22 Room and Small Commercial Air Conditioners Figure 4-6 An exploded view of the thermostatic expansion valve23 Figure 4-7 The valve opening is affected by the inlet pressure of evaporator24 Figure 4-8 The valve opening is affected by the outlet pressure of evaporator25 Figure 4-9 Section of automatic expansion valve25 Figure 4-10 An automatic expansion valve installed in a refrigeration system 26 Figure 5-1 Plain finned tube heat exchanger28 Figure 5-2 Wave finned tube heat exchanger28 Figure 5-3 Finned tube heat exchanger with louver fin 29 Figure 5-4 Slit fin29 Figure 5-5 Typical micro-channel heat exchanger30 Figure 5-6 Multiport tube30 Figure 5-7 Shape of fins in micro-channel heat exchanger30 Figure 5-8 Evaporator of air conditioner30 Figure 5-9 Multi-flow path evaporator31 Figure 5-10 Evaporator with a refrigerant distributor31 Figure 5-11 Finned tube condenser of a room air conditioner32 Figure 5-12 Side-air-discharge condenser of a room air conditioner32 Figure 5-13 Equipment with air discharged out of the top of the cabinet32 Figure 6-1 A propeller-type fan33 Figure 6-2 A centrifugal fan33 Figure 6-3 Improvement of fan shape33 Figure 6-4 A electric motor34 Figure 6-5 The windings of electric motor34 Figure 6-6 Poles (north and south) on a rotation magnet36 Figure 6-7 A simple sketch of a squirrel cage rotor36 Figure 6-8 Inverter controller for compressor 38 Figure 6-9 Signal to the base connection on the transistor38 Figure 6-10 The chock coil stabilizes current flow38 Figure 6-11 Modulation of sine-coded and pulse-width38 Figure 8-1 The energy efficiency label in Philippines49 Figure 8-2 The energy efficiency label in Singapore49 Figure 8-3 Finned-tube heat exchanger with 5mm diameter tube 51 Room and Small Commercial Air Conditioners SECTION 1 Room and Small Commercial Air Conditioners << 1 Section 1 INTRODUCTION 1.1 Types of Air Conditioner The definitions of room air conditioner and small commercial air conditioner are always different among different countries, even manufacturers. Depending on the refrigeration capacity and refrigerant used in some major ASEAN countries, the differences between room air conditioner and small commercial air conditioner are shown in Table 1-1. Table 1-1 Differences between room and small commercial air conditioners Country Capacity range (kW) Refrigerants use VIETNAM Small commercial air conditioner Room air conditioner 15 - 300 2-15 R22, R134a, R407C, etc. Country R22, R134a, R407C, etc. MALAYSIA Small commercial air conditioner Capacity range (kW) Refrigerants use 2.3 - 4.4 0.7-1.8 R22 and R410A R22 and R410A Country Capacity range (kW) Refrigerants use THAILAND Small commercial air conditioner Room air conditioner >12 <12 R-22, R-134a,R-12, R-11, R-717 R-22, R-134a, R-12, R-11, R-717 Country PHILIPPINES Small commercial air conditioner Capacity range (kW) Refrigerants use Room air conditioner Room air conditioner 0.735-3.7 0.37-2.2 R-22, R-134a, R-12, R-11, R-717 R-22, R-134a, R-12, R-11, R-717 Room and Small Commercial Air Conditioners << 2 Section 1 1.2 Major Manufacturers and Market Shares in ASEAN To provide information on the demand for air conditioners from consumers, the major air conditioner manufacturers and their approximate market shares of ASEAN countries are listed in Table 1-2. Table 1-2 Major air conditioner manufacturers in ASEAN countries VIETNAM No. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 1 2 3 4 1 2 3 4 5 6 7 8 9 Manufacturers DAIKIN LG REETECH TRANE CARRIER PANASONIC YORK AIKIBI ACSENT MITSUBISHI HEAVY FUJITSU NAGAKAWA MITSUBISHI ELECTRIC MIDEA KASUN TOSHIBA GREE SAMSUNG SANYO GENERAL OTHERS Market Share in April 2011 11.19% 6.81% 6.36% 6.33% 5.50% 5.08% 4.35% 3.98% 3.79% 3.79% 3.39% 3.25% 3.09% 3.02% 2.85% 2.82% 2.79% 2.73% 2.66% 2.60% 13.64% MALAYSIA PANASONIC YORK (American brand designed by OYL) MITSUBISHI, HITACHI, LG, SAMSUNG, others ACSON (local brand by OYL) THAILAND 30% 28% 28% 14% MITSUBISHI LG SAMSUNG PANASONIC DAIKIN SAIJO DENKI UNIAIR CARRIER Others e.g. HITACHI, TOSHIBA, YORK, FUJITSU 25% 17% 15% 13% 10% 6% 4% 2% 8% Room and Small Commercial Air Conditioners << 3 Section 1 1.3 Efficiency of Air Conditioner Methods that are commonly used to evaluate the performance of an air conditioner include: (1) EER, (2) COP, and (3) SEER. EER (energy efficiency ratio) is the ratio of the total cooling capacity to the effective power input to the device. The larger the EER value, the more efficient the equipment. The EER rating is a steady-state rating for refrigerating performance and does not account for the time the unit operates before reaching peak efficiency. This operating time has an unknown efficiency. It also does not account for shutting the system down at the end of the cycle. COP (coefficient of performance) is defined as the ratio of the heating capacity to the effective power input to the device. The larger the COP value, the more efficient the equipment. The COP rating is a steady-state rating for heating performance. Just like EER, the COP rating does not account for the time the unit operates before reaching peak efficiency. SEER (seasonal energy efficiency ratio) is the cooling capacity during a typical cooling-season divided by the total electric energy input during the same period. The larger the SEER value, the more efficient the equipment. The SEER rating includes the start-up and shutdown cycles, and so it is more reasonable for the performance evaluation than the EER rating. In the meantime, the SEER rating is more complicated than the EER rating. Room and Small Commercial Air Conditioners << 4 SECTION 2 Room and Small Commercial Air Conditioners << 5 Section 2 OUTLINE OF AIR CONDITIONER 2.1 Major Components of Air Conditioner There are two types of air-conditioners: • window-type air conditioner – all components in a single unit, as shown in Figure 2-1; • split-type air conditioner – components separated in two units (i.e. indoor unit and outdoor unit), as shown in Figure 2-2. Figure 2-1 Window-type air conditioner Air conditioners can be divided into another two types according to their function of cooling or heating: • single cooling air conditioner – having the only function for cooling; • heat-pump type air conditioner – can also run as heat pump for heating. Figure 2-2 Split-type air conditioner Inverter Compressor Outdoor heat exchanger Fan-motor Fan-motor Indoor heat exchanger 4 way valve Throttling device Figure 2-3 Major components in an inverter split-type air conditioner Room and Small Commercial Air Conditioners << 6 Section 2 The components in different type air conditioners are not the same. But all air conditioners should contain the following main components: (1) compressor, (2) evaporator, (3) condenser, (4) expansion device, and (5) fan. These components are briefly introduced in this chapter and will be described in later chapters. Compressor The compressor is a vapor pump that pumps the heat-laden refrigerant vapor from the low-pressure side of the system (the evaporator side) to the highpressure side (the condenser side) by increasing pressure and temperature. The types of compressors commonly used in air conditioners include: reciprocation, screw, rotary, scroll and centrifugal. Evaporator The evaporator is the component that absorbs heat into the refrigeration system. The most commonly used evaporator type is finned tube heat exchanger consisting of copper tubes and aluminum fins. Condenser The condenser for air conditioner is the component that rejects the heat from the system. Most air conditioners are air cooled and reject heat to the air. The most commonly used condenser type is fin and tube heat exchanger consisting of copper tubes and aluminum fins. 2.2 Refrigeration Cycle Air conditioning systems adopt vapor compression refrigeration cycle. Figure 2-4 schematically shows a basic vapor-compression refrigeration cycle. The refrigerant leaving the evaporator enters the compressor as a saturated vapor, and it is compressed to relatively high pressure and temperature by the compressor. The compressor is driven by the motor. The refrigerant leaving the compressor enters the condenser, where the refrigerant condenses and there is heat transfer from the refrigerant to the surroundings. The refrigerant leaving the condenser enters the expansion valve and expands to the evaporator pressure. This pressure decreasing process is an irreversible process, and it accompanies with the increase of entropy. The refrigerant leaves the expansion valve as a two-phase liquid-vapor mixture. The refrigerant leaving the expansion valve enters the evaporator. It vaporizes as it absorbs heat from the refrigerated space. Heat rejection 3 Expansion device The expansion device controls the refrigerant to the evaporator. The commonly used expansion devices include: thermostatic expansion valve, automatic expansion valve, and the capillary tube. Fan The air flowing across the evaporator (or condenser) is usually driven by a fan. The fans used in air conditioner have two types: propeller fan and squirrel cage fan. Depending on to structure and noise, propeller fan is used in condenser and squirrel cage fan is used in evaporator. Room and Small Commercial Air Conditioners 1. Evaporator 4 2 5 Work input 2. Expansion device 3. Condenser 4. Compressor 5. Motor 1 Heat removal Figure 2-4 Basic vapor-compression refrigeration cycle << 7 Section 2 2.3 Characteristics of Refrigerant Some properties of refrigerant may obviously affect the performance of vapor compression refrigeration cycles. The requirements on these properties are discussed as follows. Appropriate temperature and pressure characteristics The saturated pressure with temperature is an important property of refrigerant. An appropriate refrigerant should be in a reasonable pressure range for its applied cases. Figure 2-5 shows the saturated pressure with temperature of some refrigerants. Vapour pressure (bar) 25 20 15 10 80 70 60 50 40 30 20 0 10 -10 -20 -30 -40 -60 0 -50 5 Temperature (ºC) R12 R404A R134a R407C R600a R410A R290 Figure 2-5 The saturated pressure with temperature of some refrigerants • Low compression ratio is desirable, because the degree of complication and difficulty of a compressor increases directly with the compression ratio; • Discharge temperature of compressor should not be excessive, to avoid problems such as breakdown or dilution of the lubricating oil, decomposition of the refrigerant, or formation of contaminants such as sludge or acids. Otherwise, any of these problems may lead to compressor damage. High latent heat of vaporization and low specific volume A high latent heat of vaporization and a low specific volume of the refrigerant at the inlet of the compressor are desirable for smaller equipment and pipe size at a given cooling capacity. High latent heat means there is a high refrigeration effect. The refrigerating effect is the refrigerating capacity per unit mass flow rate of refrigerant, also called specific refrigerating effect. Low specific volume of the refrigerant at the inlet of the compressor means that it will result in a high volumetric refrigerating effect. Lower compression work In order to get high refrigeration efficiency, both high refrigeration effect and low compression work must be considered in combination. For air conditioners, the temperature and pressure of refrigerant should fulfill the following requirement: • It is desired for the pressure at the evaporating temperature to be higher than the atmospheric pressure, so as to avoid inward leakage of air; • The pressure at the condensing temperature should not be excessive, so that extra strength of the high-side equipment is not required; Room and Small Commercial Air Conditioners << 8 SECTION 3 Room and Small Commercial Air Conditioners << 9 Section 3 COMPRESSOR 3.1 Types of Compressor Reciprocating compressor Screw compressor Scroll compressor Rotary compressor Centrifugal compressor Figure 3-1 Five major types of compressors The compressor is considered as the heart of an air conditioning system, and can be described as a vapor pump. The function of compressor is increasing the pressure from the suction level to the discharge level. The cool refrigerant passes through the suction valve to fill the cylinder. This cool vapor contains the heat absorbed in the evaporator. The compressor pumps this heatladen vapor to the condenser so that the heat can be rejected from the system. Five major types of compressors are commonly used in the air conditioners, as shown in Figure 3-1. These are reciprocating, screw, rotary, scroll, and centrifugal. Reciprocating Room and Small Commercial Air Conditioners compressors are used most frequently in small and medium-sized commercial refrigeration systems. Screw compressors are used in commercial and industrial systems. Rotary compressors and scroll compressors, along with the reciprocating compressors, are used in residential and small commercial air conditioners. Centrifugal compressors are used extensively for air conditioning in large buildings; but recently small-size centrifugal compressors have been developed, and they can be used in air conditioners. << 10 Section 3 3.1.1 Reciprocating Compressor Reciprocating compressor compresses the vapor by moving piston cylinder to change the volume of the compression chamber. The main elements of a reciprocating compressor include piston, cylinder, valves, connection rod, crankshaft and casing. Reciprocating compressors are categorized by the compressor housing. The two housing categories are open and hermetic compressor. Room and small commercial air conditioners usually use hermetic compressors. Hermetic refers to the type that all the components of the compressor is contained in a single house, including fully welded hermetic compressor and semi-hermetic compressor, as shown in Figure 3-2. Hermetic compressors The motor and compressor are contained inside a single shell that is weld-closed when a welded hermetic compressor is manufactured. Characteristics of the fully welded hermetic compressor are as follows: • The only access to the inside of the shell is by cutting the shell open; • They usually have a pressure lubrication system, but smaller hermetic is splash lubricated; • The motor shaft and compressor crankshaft are one shaft. The combination motor and crankshaft are customarily in a vertical position with a bearing at the bottom of the shaft next to the oil pump. The second bearing is located about halfway on the shaft between the compressor and motor; • It is usually considered a low-side device because the suction gas is vented to the whole inside of the shell, which includes the crankcase. The discharge line is normally piped to the outside of the shell so that the shell only has to be rated at the low-side working-pressure value; • The pistons and rods work outward from the crankshaft, so they are working at a 90°angle in relation to the crankshaft, Figure 3-3. Suction Bag Fully welded hermetic compressor Rotor Suction Tube Stator Balance Iron Washer Connecting Rod Crankshaft Piston Cylinder Head Shell Valve Cover Cylinder Discharge Tube Semic-hermetic compressor Figure 3-2 Fully welded hermetic compressor and semi-hermetic compressor Room and Small Commercial Air Conditioners End Cover Lower Bearing Figure 3-3 The internal working of a fully welded hermetic compressor << 11 Section 3 Semi-hermetic compressors When a semi-hermetic compressor is manufactured, the motor and compressor are contained inside a single shell that is bolted together. This unit can be serviced by removing the bolts and opening the shell at the appropriate place. The inner structure of a semi-hermetic compressor is shown in Figure 3-4. Following are the characteristics of the semihermetic compressor: • The unit is bolted together at locations that facilitate service and repair. Gaskets separate the mating parts connected by the bolts, and the housing is normally cast-iron or steel, so they are normally heavier than the fully welded type; • They generally use a splash-type lubrication system in the smaller compressor and a pressure lubrication system in the large compressors; • They are often air cooled and can be recognized by the fins in the casting or extra sheet metal on the outside of the housing that give the shell more surface areas; • The motor and crankshaft combination are similar to the motor and crankshaft in the fully welded type except that the crankshaft is usually horizontal. • The piston heads are normally at the top or near the top of the compressor and work up and down from the center of the crankshaft. Discharge Tube Reciprocating compressor may be either singleacting or double-acting, and can be designed to accommodate practically any pressure of capacity. In a single-acting compressor, the vapor compression occurs only once in one side of the piston during each revolution of the crankshaft. In a double-acting compressor, the vapor compression occurs alternately in both sides of the piston so that the compression occurs twice for each revolution of the crankshaft. In reciprocating compressor, the piston is driven by a crankshaft via a connection rod. At the top of the cylinder are a suction valve and a discharge valve. A reciprocating compressor usually has several cylinders in it. To illustrate the principle of operation of reciprocating compressor, here we use singleacting piston as an example. The following sequence of events occurs inside a reciprocating compressor during the pumping action, as shown in Figure 3-5. Piston moves down Piston starts up Piston proceeds up Piston at top dead-center Valve Rod Inlet Filter Oil Pump Motor Oil Filter Shell Figure 3-4 The working parts of a semi-hermetic compressor Room and Small Commercial Air Conditioners Figure 3-5 Events inside a reciprocating compressor during the pumping action << 12 Section 3 Piston at the top of the stroke and starting down When the piston starts down, a low pressure is formed under the suction reed valve. When this pressure becomes less than the suction pressure and the valve spring tension, the cylinder will begin to fill. Gas will rush into the cylinder through the suction reed valve. Piston continues to the bottom of the stroke When the piston gets near the bottom of the stroke, the cylinder is nearly as full as it is going to get. There is a short time lag as the crankshaft circles through bottom dead-center, during which a small amount of gas can still flow into the cylinder. Piston is starting up The rod throw is past bottom dead-center, and the piston starts up. When the cylinder is as full as it is going to get, the suction flapper valve closes. The piston proceeds to the top of the stroke When the piston starts back up and gets just off the bottom of the cylinder, the suction valve will have closed, and pressure will begin to build in the cylinder. When the piston gets close to the top of the cylinder, the pressure will start to approach the pressure in the discharge line. When the pressure inside the cylinder is greater than the pressure on the top side of the discharge reed valve, the valve will open, and the discharge gas will empty out into the high pressure side of the system. The piston is at exactly top dead-center This is as close to the top of the head as it can go. There has to be a certain amount of clearance in the valve assemblies and between the piston and the head, otherwise they would touch. This clearance is known as clearance volume. A reciprocating compressor cylinder Room and Small Commercial Air Conditioners cannot completely empty because of the clearance volume at the top of the cylinder. The manufactures try to keep this clearance volume to a minimum but cannot completely do away with it. The piston is going to push as much gas out of the cylinder as time and clearance volume will allow. There will be a small amount of gas left in the clearance volume. When the piston starts back down, this gas will re-expand, and the cylinder will not start to fill until the cylinder pressure is lower than the suction pressure. This re-expanded refrigerant is part of the reason that the compressor is not 100% efficient. Valve design and the short period of time the cylinder has to fill at the bottom of the stroke are other reasons the compressor is not 100% efficient. 3.1.2 Scroll Compressor The scroll compressor compresses a gas by turning one scroll against another around a common axis. The scroll compressor is becoming more fine-tuned and is available in many more applications. A major hurdle in making the scroll compressor a viable product has been the ability to achieve a balance between the need for highvolume precision manufacturing and the need for consistent high performance and efficiency, low sound levels, and great reliability. Because of the scroll compressor’s fewer moving parts, it operates much more quietly than other compressor designs and technologies. Less noise and higher efficiencies have become two key selling points for installing the scroll compressor in air-conditioners. Comparing to piston-type compressor, the scroll compressor has higher efficiencies, reliability, and quieter operation. The characteristics of scroll compressor are summarized as follows: • There are no volumetric losses through gas reexpansion as with piston-type compressors; • The scroll compressor requires no reed valves, << 13 Section 3 • • • • so it does not have valve losses that contribute to inefficiencies as piston-type compressors; Separation of suction and discharge gases reduces heat-transfer losses; Centrifugal forces within the mating scrolls maintain nearly continuous compression and constant leak-free contact; Radial movement eliminates high-stress situations and allows for just the right amount of contact force between mating scroll surfaces. This acting allows the compressor to handle some liquid; Scroll compressors maintain a continuous compression process and have no reed valves to create valve noise. This creates very soft gas-pulsation noises and very little vibration as compared with piston-type compressors. Scroll compressor operation is relatively simple. Two spiral-shaped scrolls fit inside one another. The two mating parts are often referred to as involute spirals. One of the spiral-shaped parts stays stationary while the other orbits around the stationary member. The orbiting motion is created from the centers of the journal bearings and motor being offset, as shown in Figure 3-6. 1. Fixed Scroll Member 5. Connection 2. Moving Scroll member 6. Sunction Hole 3. Compressor Case 7. Discharge Hole 4. Eccentric Bearing Figure 3-6 Cross section of a scroll compressor rotational motion. This orbiting motion causes continuous crescent-shaped gas pockets to be formed, as shown in Figure 3-7. The orbiting motion draws gas into the outer pocket and seals it as the orbiting continues. This continuous orbiting motion causes the crescent-shaped gas pocket to become smaller and smaller in volume as it nears the center of the scroll form. The gas pocket is fully compressed and is discharged out of a port of the nonorbiting scroll member, as shown in Figure 3-8. The orbital motion of one spiral-shaped is not a (1) (2) (3) (4) (1) Gas enters an outer opening as one scroll orbits the other (2) The open passage is sealed as gas is drawn into the compression chamber (3) As one scroll continues orbiting, the gas is compressed into an increasingly smaller “pocket” (4) Gas is continually compressed to the center of the scrolls, where it is discharged through precisely machined ports and returned to the system Figure 3-7 Process of forming continuous crescent-shape gas pockets in the scroll Room and Small Commercial Air Conditioners << 14 Section 3 Discharge port rotary compressor. Rotary compressors are manufactured in two basic design types: the stationary vane and the rotary vane. Figure 3-8 Scroll orbit in a real scroll compressor Several crescent-shaped gas pockets are compressed at the same time, which provides for a smooth and continuous compression cycle. Thus, the scroll compressor conducts its intake, compression, and discharge phases simultaneously. Unlike piston-type compressors, the scroll compressor has no re-expansion of discharge gas that can be trapped in a clearance volume. Re-expansion of discharge gas contributes to low volumetric efficiencies in piston-type compressors. 3.1.3 Rotary Compressor A rotary compressor is small and light. It is sometimes cooled with compressor discharge gas, which makes the compressor appear to be running too hot. A warning may be posted in the compressor compartment that the housing will appear to be too hot. The compressor and motor are pressed into the shell of a rotary compressor, and no vapor space is between the compressor and the shell. This also reduces the size of the rotary compressor as compared with a reciprocating compressor. A rotary compressor is generally more efficient than a reciprocating compressor, and it is widely used in small- to medium-sized systems. Figure 3-9 shows the inner structure of the Room and Small Commercial Air Conditioners 1. Discharge Tube 6. Sucion Tube 2. Cylinder 7. Sliding Vane 3. Rotary 8. Spring 4. Eccentric Shaft 9. Discharge Valve 5. Lubricating Oil Figure 3-9 Cross section of a rotary compressor Stationary vane rotary compressor The components for this compressor are the housing, a blade or vane, a shaft with an offcenter rotor, and a discharge valve. The shaft turns the off-center rotor so that it “rolls” around the cylinder, as shown in Figure 3-10. The blade or vane keeps the intake and compressor chambers of the cylinder separate. The tolerances between the rotor and cylinder must be very close, and the vane must be machined so that gas does not escape from the discharge side to the intake. As the rotor turns, the vane slides in and out to remain tight against the rotor. The valve at the discharge keeps the compressed gas from leaking back into the chamber and into the suction side during the off cycle. As the shaft turns, the rotor rolls around the cylinder, allowing suction gas to enter through << 15 Section 3 the intake and compresses the gas on the compression side. This is a continuous process as long as the compressor is running. The results are similar to those with a reciprocating compressor. Low-pressure suction gas enters the cylinder, is compressed, and leaves through the discharge opening. compressing is a continuous process as long as the compressor is running. All the refrigerant that enters the intake port is discharged through the exhaust or discharge port. There is no clearance volume as in the reciprocating compressor. This is the primary reason why the rotary compressor is highly efficient. 3.1.4 Screw Compressor Instead of a piston and cylinder, the rotary compressor uses two matching, tapered, machined screw-type gears that squeeze the refrigerant vapor from the inlet to the outlet. The rotary screw compressor uses an open motor instead of the hermetic design, and a shaft seal traps the refrigerant in the compressor housing where the rotating shaft leaves the compressor housing. A flexible coupling is used to connect the motor shaft to the compressor shaft to prevent minor misalignment from causing seal or bearing damage. 1. Discharge Tube 6. Sucion Tube 2. Cylinder 7. Sliding Vane 3. Rotary 8. Spring 4. Eccentric Shaft 9. Discharge Valve 5. Lubricating Oil Figure 3-10 Operation of a stationary van rotary compressor Rotary vane rotary compressor The rotary vane compressor has a rotor fitted to the center of the shaft. The rotor and the shaft have the same center. The rotor has two or more vanes that slide in and out and trap and compress the gas. The shaft and rotor are positioned off center in the cylinder. As a vane passes by the suction intake opening, low-pressure gas follows it. This gas continues to enter and is trapped by the next vane, which compresses it and pushes it out the discharge opening. The intake and Room and Small Commercial Air Conditioners Screw compressor applications are for large systems. The refrigerant may be any of the common refrigerants. The operating pressure on the low- and high- pressure sides of the system are the same as for a reciprocating system of like application. As shown in Figure 3-11, the compression of refrigerant in a screw compressor is accomplished by the enmeshing of two mating helically grooved rotors. The rotors are the main components of the screw compressor. As the rotors turn, vapour is drawn through the inlet opening to fill the space between the male lobe and the female flute. As the rotors continue to rotate, the vapor is moved through the suction port and sealed in the interlobes space. The vapor so trapped in the interlobe space is moved both axialy and radially << 16 Section 3 Figure 3-11 One stage of compression as refrigerant moves through the screw compressor and is compressed by direct volume reduction as the enmeshing of the lobes progressively reduced the space occupied by the vapor. Compression of the vapor continues until the interlobe space communicates with the discharge ports in the cylinder and the compressed vapor leaves the cylinder through these ports. The length and diameter of the rotors determine the capacity and discharge pressure. Longer rotors may result in higher pressure. The large the diameter of the rotors, the greater the capacity. After compression, the refrigerant vapor/ lubricant mixture enters a multi-stage separator which removes the lubricant from the refrigerant vapor. From the separator, the vapor flows to the aftercooler. The lubricant is also cooled, returning to the compressor through a thermostaticallycontrolled valve. Lubrication is crucial to the rotary screw compressor. Without proper lubrication, the screw could be worn out quickly. Many rotary screw models are equipped with internal capacity control and variable volume ratio systems to cope with variable load and pressure operation. Such systems are particularly desirable when the screw compressor is driven by a constant speed electric motor but operates under varying pressure conditions. The characteristics of screw compressor are listed as follow: Room and Small Commercial Air Conditioners 1.Screw compressor has fewer moving parts. So, there is no need to service the items such as compressor valves, packing and piston rings, and the associated downtime for replacement; 2.The absence of reciprocation inertial forces allows the screw compressor to run at high speeds, and so it could be constructed more compact; 3.The continuous flow of cooling lubricant allows much higher single-stage compression ratios; 4.The compactness tends to reduce package costs; 5.Low vibration due to reducing or elimination pulsations by screw technology; 6.Higher speeds and compression ratios help to maximize available production horsepower. 3.1.5 Centrifugal Compressor Centrifugal compressor has been designed for heating, ventilation, air-conditioning and refrigeration industries. A schematic diagram of centrifugal compressor is shown in Figure 3-12. Vapor enters axially at the inlet cavity (6) and flow through the passage in the impeller (3). The pressure and absolute velocity of the vapour rise when the vapor passes the impeller because of the centrifugal force. In the diffuser (8), the flow of vapor is decelerated to further raise the vapour pressure. The compressed vapor is collected in the volute (1) and discharge to the delivery pipe. << 17 Section 3 for the power consumption of the compressors. In order to reduce the power consumption, cooling between stages may be needed. 3.2 Compressor Efficiency 1. Volute 5. Rotor 2. Diffuser 6. Inlet Cavity 3. Impeller 7. Impeller 4. Seal 8. Diffuser Figure 3-12 Centrifugal compressor The centrifugal compressor consists of a housing and at least one rotor (5) of which the shaft is pivotally supported by the housing, with a free shaft end and a rotor connected with the other end of the rotor shaft. The free end of the rotor shaft facing away from the rotor projects into a pressure chamber connected with the housing, and is acted upon by a pressurized rotor. Thus, the starting friction of the compressor is lower and drive motors of lower output target can be utilized. To reduce leakage along the shaft where the vapor passes through the compressor housing, the centrifugal compressor must be sealed in a suitable manner. Centrifugal compressors are well suited to compress large volume of refrigerant for relatively low pressure lift. Since the compressive force generated by a single impeller wheel is small, multiple impeller wheels arranged in series can be employed for centrifugal compressors to increase compression ratio. The pressure ratio across each stage is determined by the required pressure lift of a compressor. However, it is also necessary to consider a suitable velocity increase in each impeller to reduce the possible momentum losses between the stages. The temperature of refrigerant at the inlet of each stage has a decisive significance Room and Small Commercial Air Conditioners The compressor’s overall efficiency can be improved by maintaining the correct working conditions. This involves keeping the suction pressure as high as practical and the keeping head pressure as low as practical within the design parameters. A dirty evaporator will cause the suction pressure to drop. When the suction pressure goes below normal, the vapor that the compressor is pumping becomes less dense, resulting in the compressor performance decreases. Low suction pressures also cause the high-pressure gases caught in the clearance volume of the compressor to expand more during the piston’s downstroke. This gives the compressor a lower volumetric efficiency. These gases have to expand to a pressure just below the suction pressure before the suction valve will open. Because more of the downward stroke is used for re-expansion, less of the stroke can be used for suction. Suction ends when the piston reaches bottom dead-center. Low evaporator pressures cause high compression ratios. The compression ratio is defined as follow: Compression ratio = Absolute discharge pressure / Absolute suction pressure If compression ratio is too high, compressor will not operate normally. Most manufacturers recommend that the compression not be more than 12:1. Dirty condensers also cause compression ratios to rise, but they do not rise as fast as with a dirty evaporator. << 18 Section 3 3.3 Latest Technology in Development and Commercially Available It is desirable to have an air-conditioner to operate at low noise, constant temperature control, all-day running, low frequency compensation and instantly achieving the set temperature. The emergence of inverter compressor makes them achievable in an energy efficient way. The inverter compressor changes its capacity by varying its rotation speed. When the compressor rotates at high speed, it delivers high capacity to speed up the cooling or heating without excessively consuming energy. This is because the speed of the compressor is controlled to maximize the efficiency and according to the cooling and heating load of a room. In contrast to conventional compressors, inverter compressor detects subtle changes in temperature and adjusts its speed automatically. When it operates at a low rotation speed, it efficiently maintains the desirable temperature with minimum temperature swings to provide a comfortable climate. For optimum performance inverter technology delivers only the energy needed to satisfy the cooling and heating load of a room, thereby reducing energy consumption. The comparison of inverter compressor and conventional compressor is listed in Table 3-1. Table 3-1 Comparison of inverter compressor and conventional compressor Inverter compressor Conventional compressor High rotation speed provides fast cooling and heating Requires a long time to reach desired temperature Low rotation speed efficiently maintains desired temperature Has uncomfortable temperature fluctuation Low rotation speed keeps starting current low, leaving other appliances unaffected Needs heavy energy usage every time compressor turns on Precise rotation speed control provides comfortable, consistent room temperature Requires high starting current that affects other appliances throughout household Smooth speed charge scroll compressor with neodymium concentrating winding DC motor, as shown in Figure 3-13, is developed in recent years, and this kind of compressor may have low vibration and high efficiency. Smooth Speed charge scroll New neodymium concentrating winding DC motor Figure 3-13 Smooth speed charge scroll compressor with neodymium DC motor Room and Small Commercial Air Conditioners << 19 SECTION 4 Room and Small Commercial Air Conditioners << 20 Section 4 EXPANSION DEVICE 4.1 Types of Expansion Device The expansion device is the component necessary for the compression refrigeration cycle to function. The expansion device can be either a valve or a fixed-bore device, and it is not as visible as the evaporator, the condenser, or the compressor. The fixed-bore device is referred to capillary tube as shown in Figure 4-1. The capillary tube is usually used in room air-conditioner. Expansion valves have two different types: (1) thermostatic expansion valve as shown in Figure 4-2 and (2) automatic expansion valve, as shown in Figure 4-3. The expansive valves are usually used in commercial air-conditioners. Figure 4-2 Thermostatic expansion valve Capillary tube Figure 4-3 Automatic expansion valve Figure 4-1 Capillary tube connected with liquid-line Room and Small Commercial Air Conditioners << 21 Section 4 4.2 Capillary Tube The capillary tube metering device controls refrigerant flow by pressure drop. It is a copper tube with a very small calibrated inside diameter, as shown in Figure 4-1. The diameter and the length of the tube determine how much liquid will pass through the tube at a given pressure drop. This length-to-pressure drop relationship is used by manufactures to arrive at the correct pressure drop that will allow the correct amount of refrigerant to pass through the capillary tube to correctly fill the evaporator, as shown in Figure 4-4. The capillary tube can be quite long on some installations and may be wound in a coil to store the extra tubing length. The capillary tube does not control superheat or pressure. It is a fixed-bore device with no moving parts, and it is weak in adjusting the refrigerant flow rate according to the load change. Therefore, it is used where the load is relatively constant (i.e. no large load fluctuation). The capillary tube is an inexpensive device for the control of refrigerant and is used often in small equipment. This device does not have a valve and does not stop the liquid from moving to the low side of system during the off cycle, so the pressure will equalize during the off cycle. This reduces the motor starting torque requirement for the compressor. Condensor Evaporator Compressor The capillary tube has no moving parts, and so it will not wear out. The only problem it may have would be small particles that may block or partially block the tube. The bore is so small that a small piece of carbon or solder entering the capillary tube would cause a problem. Manufacturers always place a strainer of filterdrier just before the capillary tube to prevent this from happening, as shown in Figure 4-5. Filter-drier Liquid line Capillary tube Evaporator Figure 4-5 A filter-drier protects the capillary tube from circulating particles 4.3 Thermostatic Expansion Valve A thermostatic expansion valve is normally installed in the liquid line between the condenser (high side of the system) and the evaporator (low side of the system), and it is responsible for metering the correct amount of refrigerant to the evaporator. The evaporator performs best when it is as full of liquid refrigerant as possible without leaving any in the suction line. A thermostatic expansion valve controls the refrigerant to the evaporator using a thermal sensing element to monitor the superheat. This valve opens or closes in response to a thermal element. The thermostatic expansion valve maintains a constant superheat in the evaporator. Excess superheat is not desirable, but a small amount is necessary with this valve to ensure that no liquid refrigerant leaves the evaporator. The thermostatic expansion valve can be adjusted to maintain a low superheat to ensure that the majority of evaporator surface is effectively used, resulting in a higher capacities and efficiencies. Capillary Tube Figure 4-4 Capillary tube in a refrigerating system Room and Small Commercial Air Conditioners << 22 Section 4 A thermostatic expansion valve consists of valve body, diaphragm, needle and seat, spring, adjustment and packing gland, and the sensing bulb and transmission tube, as shown in Figure 4-6. Sensing bulb connection External equlizer connection Refrigerant outlet Thermostatic element containing diaphragm Push rods Refrigerant inlet Valve body Seat Pin carrier Superheat spring Spring guide Bottom cap Adjustment Protective sealcap Figure 4-6 An exploded view of the thermostatic expansion valve The valve body is an accurately machined piece of solid brass or stainless steel that holds the rest of the components and fastens the valve to the refrigerant piping circuit. The diaphragm moves the needle in and out of the seat in response to system load changes. The diaphragm is made of thin metal and is under the round dome-like top of the valve. The needle and seat control the flow of refrigerant through the valve. They are normally made of some type of very hard metal, such as stainless Room and Small Commercial Air Conditioners steel, to prevent the refrigerant passing through from eroding the seat. The spring is one of the three forces that act on the diaphragm. It raises the diaphragm and closes the valve by pushing the needle into the seat. When a valve has an adjustment, the adjustment applies more or less pressure to the spring to change the tension for different superheat settings. The sensing bulb and transmission line are extensions of the valve diaphragm. The bulb detects the temperature at the end of the evaporator on the suction line and transmits this temperature, converted to pressure, to the top of the diaphragm. The bulb contains a fluid, such as refrigerant, that responds to a temperature/ pressure relationship chart just like any refrigerant would. When the suction line temperature goes up, this temperature change occurs inside the bulb. As the temperature of the thermostatic expansion valve’s sensing bulb increases, the valve will gradually open, letting more refrigerant into the evaporator. This will increase both the evaporator pressure and compressor’s suction pressure, while attempting to reduce the amount of superheat in the evaporator. At the condition of pressure variation, the transmission line allows the pressure between the bulb and diaphragm to equalize back and forth. The fluid inside the expansion valve bulb is known as the charge for the valve. Four types of charge can be obtained with the thermostatic expansion valve: liquid charge, cross liquid charge, vapor charge, and cross vapor charge. • The liquid charge bulb is a bulb charge with a fluid characteristic of the refrigerant in the system. The diaphragm and bulb are not actually full of liquid. The liquid will not all boil away. The temperature/pressure << 23 Section 4 relationship is almost a straight line on a graph. The liquid charge bulb is usually limited to narrow-operation-range applications or special functions like desuperheating in the high side of the system. • The cross liquid charge bulb has a fluid that is different from the system fluid. It does not follow the temperature/pressure relationship. It has a flatter curve and will close the valve faster on the rise in evaporator pressure. Liquid cross charges are good for low-temperature applications. • The vapor charge bulb is actually a valve that has only a small amount of liquid refrigerant in the bulb. When the bulb temperature rises, more and more of the liquid will boil to a vapor until there is no more liquid. The pressure curve will be flat. This acts to limit the maximum operating pressure the valve will allow the evaporator to experience. These valves are often referred to as maximum operating pressure valves. • The cross vapor charge bulb has a similar characteristic to the vapor charged valve, but it has a fluid different from the refrigerant in the system. This gives a different pressure and temperature relationship under different conditions. These special valves are applied to special systems. The seat in the valve is stationary in the valve body, and needle is moved by the diaphragm. One side of the diaphragm gets its pressure from the bulb, and the other side gets its pressure from the evaporator and the spring. The diaphragm moves up and down in response to three different pressures. These three different pressures act at the proper time to open, close, or modulate the valve needle between open and closed. These three pressures are the bulb pressure, the evaporator pressure, and the spring pressure. They all work as a team to position the valve needle at the correct position for the load conditions at any particular time. Pressure of Sensing bulb 0.414MPa Pressure of Spring 0.078MPa Pressure of Evaporator 0.336MPa Liquid Refrigerant Vapor Refrigerant 1.0ºC 1. The Spensing Bulb 2. Adjusting Screw 3. Spring 4. Push Ord 5. The diaphragm Figure 4-7 The valve opening is affected by the inlet pressure of evaporator Room and Small Commercial Air Conditioners << 24 Section 4 0.336MPa Liquid Refrigerant 0.096MPa Vapor Refrigerant 1. The Spensing Bulb 2. Adjusting Screw 3. Spring 4. Push Ord 5. The diaphragm Figure 4-8 The valve opening is affected by the outlet pressure of evaporator The pressure from the evaporator on the diaphragm could be the inlet pressure of the evaporator (as shown in Figure 4-7) or the outlet pressure of the evaporator (as shown in Figure 4-8). The structure of the thermostatic valve using the inlet pressure of the evaporator is simpler than that using the outlet pressure of the evaporator; while the superheat of the evaporator controlled by the type shown in Figure 4-7 is normally larger than the type shown in Figure 4-8. 5 6 7 7 4 3 2 1 4.4 Automatic Expansion Valve The automatic expansion valve is an expansion valve that meters the refrigerant to the evaporator by using one or more sensors. This device is also a valve that changes inside dimension in response to its sensing elements. The automatic expansion valve has the ability to maintain a constant pressure in the evaporator, and may not depend on the superheat. Figure 4-9 shows a section of automatic expansion valve. The automatic expansion valve is built much the same as the thermostatic expansion valve Room and Small Commercial Air Conditioners 1. Liquid and Vapor out 5. Push Rod 2. Spring 6. Winding 3. Need 7. Valve Body 4. Push Rod 8. Liquid in Figure 4-9 Section of automatic expansion valve except that it does not have a sensing bulb. The body is normally made of machined brass. The adjustment of this valve is normally at the top of the valve. There may be a cap to remove, or there may be a cap to turn. This adjustment changes the spring tension that supports the atmosphere << 25 Section 4 in pushing down on the diaphragm. When the tension is increased, the valve will feed more refrigerant and increase the suction pressure. The automatic expansion valve responds to load changes, depending on the detected parameters from the sensors. The sensors can be those of pressure or temperature. Figure 4-10 shows an example of using an automatic expansion valve in a refrigeration system, using temperature sensors by the automatic valve. Two temperature sensors for respectively measuring the wall temperatures at the middle position and the outlet of the evaporator, and the measured two temperatures are used to control the opening of the valve. 1 3 θ1w θ1w -θ2w2 θ2w PM 4 1. Evaporator 2. Compressor 3. Condensor 4. Automatic expansion valve Figure 4-10 An automatic expansion valve installed in a efrigeration system Room and Small Commercial Air Conditioners << 26 SECTION 5 Room and Small Commercial Air Conditioners << 27 Section 5 HEAT EXCHANGER 5.1 Types and Sub Components of Heat Exchanger The heat exchangers in air conditioner are known as evaporator and condenser, depending on their functions. The function of evaporator is to transfer heat between high temperature room air and low temperature refrigerant. The function of condenser is to transfer heat between low temperature outdoor air and high temperature refrigerant. Four types of fins are widely used in finned tube heat exchangers for air conditioners, i.e. plain fin, wave fin, louver fin and slit fin. Among different types of finned tube heat exchangers, the plain fin heat exchanger has the lowest airside pressure drop, but it has the lowest capacity of heat exchange. Its low capacity of heat exchange results in that the plain fin is not extensive used in heat exchangers. Figure 5-1 shows a finned tube heat exchanger using plain fins. The heat exchangers have many variations in the shape and arrangement of heat transfer surface. Finned tube heat exchangers and micro-channel heat exchangers are the commonly used heat exchangers in air conditioners. The finned tube is the most common type used in air conditioner. The finned tube exchanger has the fins installed on the bare tube to enhance the heat transfer from the air to the refrigerant in the tube. The application of fins increases the overall evaporator surface and so the evaporator efficiency can be improved. Finned tube heat exchangers are used extensively in residential and commercial air conditioning applications. In order to make them effective, there must be good thermal contact between the fins and tubes. This can be accomplished by several ways. The most commonly used way is to slip the fin over the tubes and expand the tubes by pressure so that the fin locks onto the tube surface. As the finned tube provides more surface area per unit of length and width for the heat transfer, a finned tube evaporator occupies less space than a bare-tube or plate surface evaporator of the same capacity does. Figure 5-1 Plain finned tube heat exchanger The surface of wave fin is stamped in wave configuration, as shown in Figure 5-2. The capacity of heat exchange of wave fin is higher than plain fin, but less than that of slit fin and louver fin. The wave fin is extensive used in the outdoor condenser of air conditioner, because the dust will not accumulate in the wave fin as much as in the slit fin and louver fin. Figure 5-2 Wave finned tube heat exchanger Room and Small Commercial Air Conditioners << 28 Section 5 Figure 5-3 shows a finned tube heat exchanger with louver fin. The louver fin does not only break the boundary, but also make the wind have an angle with fin. So the louver fin has a high capacity of heat exchange. However, the airside pressure drop of louver fin is also high. Round tube The configuration of slit fin is shown in Figure 5-4. The slit fin can efficiently break the boundary layer near the fin. This will increase the capacity of heat exchange. But this also brings higher airside pressure drop. Louver Hole for round tube Louver Air flow Louver fin in finned tube heat exchanger Louver fin Figure 5-3 Finned tube heat exchanger with louver fin Hole for round tube Slite Figure 5-4 Slit fin Room and Small Commercial Air Conditioners << 29 Section 5 The micro channel heat exchanger is also one type of heat exchanger used in air conditioner. A typical micro channel heat exchanger consists of multiport tubes, multilouver fins and manifolds, as shown in Figure 5-5. The shape of the fins in a micro-channel heat exchangers is V-shape or square shape, as shown in Figure 5-7. Multilouver fin V-shape fin Manifold Multiport tube Cu-AI joint Figure 5-5 Typical micro-channel heat exchanger There are different types of multiport tubes, e.g. extruded tube, inner-finned tube and folded tube, as shown in Figure 5-6. Extruded tube Inner-finned tube Square shape fin Figure 5-7 Shape of fins in micro-channel heat exchanger 5.2 Evaporator The evaporator in a refrigerant system is responsible for absorbing heat into the refrigerant from indoor air. This heat-absorbing process is accomplished by maintaining the evaporator at a lower temperature than indoor air, and the temperature should be low enough for removing latent and sensible heat from cooler. There are three ways to increase heat exchange capacity of evaporator. The first method is to increase heat transfer area. For the limit space of indoor part of air conditioner, the finned tube area should be limited. However, the manufacturers can optimize the shape of the evaporator to increase the space for laying more finned tube, as shown in Figure 5-8. Folded tube Figure 5-6 Multiport tube Traditional arrangment With more finned tubeå Figure 5-8 Evaporator of air conditioner Room and Small Commercial Air Conditioners << 30 Section 5 The second method is to use enhanced fins, such as slit fin or louver fin, as shown in Figures 5-3 and 5-4. It should be noted that the evaporator operating under dehumidifying condition may produce water droplets or water films which can block the slit or louver, resulting in the decrease of heat exchange capacity and the increase of airside pressure drop. Inlet The third method is to optimize the refrigerant flow circuit. When a refrigerant flow path in an evaporator becomes too long and excessive pressure drop occurs, it is advisable to have more than one path in parallel, as schematically shown in Figure 5-9. However, when more paths are used, a distributor must be used to distribute the correct amount of refrigerant to the individual paths, as shown in Figure 5-10. Outlet Block 1 Inlet Block 1 12 Outlet 24 23 23 Air flow 10 22 10 21 Air flow 21 22 20 8 8 19 7 18 6 6 17 18 17 16 4 15 4 14 3 2 13 2 13 Figure 5-9 Multi-flow path evaporator Refrigerant distributor Evaporator Figure 5-10 Evaporators with a refrigerant distributor Room and Small Commercial Air Conditioners << 31 Section 5 5.3 Condenser The condenser is a heat exchange device similar to the evaporator, as shown in Figure 5-11. Different from the evaporator, it rejects the heat from the system absorbed. The heat is rejected from a hot superheated vapor in the first part of the condenser. The middle of the condenser rejects latent heat from the saturated vapor, which is in the process of phase changing to a saturated liquid. The last part of the condenser rejects heat from subcooled liquid, subcooling the liquid to below its condensing temperature. In fact, the three functions of a normal condenser are to desuperheat, condensate, and subcool the refrigerant. Air flow Figure 5-12 Side-air-discharge condenser of a room air conditioner Top-air-discharge condenser Some large room and small commercial air conditioner may use top-air-discharge condenser, as shown in Figure 5-13. In this type condenser, the hot air and noise are discharged from the top into the air. The fan and motor are on top of the equipment, and rain, snow, and leaves can fall directly into the unit, so the fan motor should be protected with a rain shield. Air discharge Figure 5-11 Finned tube condenser of a room air conditioner The condenser is operated at higher pressures and temperatures than the evaporator and is often located outside. Most air conditioner is air cooled and rejects heat to the air. Depending on the air discharging direction, condensers have two different types: side-air-discharge condenser and top-air-discharge condensers. Air Air suction suction Figure 5-13 Equipment with air discharged out of the top of the cabinet Side-air-discharge condenser Most room air conditioners use side-air-discharge condenser. This kind of air conditioner discharges the air out the side, as shown in Figure 5-12. Room and Small Commercial Air Conditioners << 32 SECTION 6 Room and Small Commercial Air Conditioners << 33 Section 6 FAN, MOTOR AND INVERTER 6.1 Fan A fan can be described as a device that produces airflow or movement. Several different types of blows produce this movement, but all can be described as non-positive-displacement air moves. applied. So the squirrel cage fan is commonly used in the indoor unit of a split-type air conditioner. In air conditioners, fans are known as two types: propeller fan and the forward curve centrifugal fan, also called the squirrel cage fan, or blower wheel. Propeller fan is used in condenser fan applications, as shown in Figure 6-1. It will handle large volume of air at low pressure differential. The propeller can be plastic, cast iron, aluminium, or stamped steel. The propeller fan makes more noise than the centrifugal fan so it is used in condenser where noise is not a factor. Figure 6-2 A centrifugal fan useless fan surface cut (efficiency 50% up) example (oil flow) Large fan surface Revolutions per minute (RPM) reduced, no change in air flow Figure 6-1 A propeller-type fan Squirrel cage fan or centrifugal fan, is shown in Figure 6-2. This fan has a forward curved blade and a cut-off to shear the air spinning around the fan wheel. This air is thrown by centrifugal action to the outer perimeter of the fan wheel. The centrifugal fan is very quiet when properly Room and Small Commercial Air Conditioners Long edge Figure 6-3 Improvement of fan shape << 34 Section 6 Optimization of fan shape in order to enhance the fan efficiency has been done. Cut useless fan surface and enlarge the fan edge, as shown in Figure 6-3, can help to increase the fan efficiency. 6.2 Motor Motors are used as the prime movers of air (i.e. fan) and refrigerant (i.e. compressor). Motors have a stator with windings, a rotor, bearings, end bells, housing, and some means to hold these parts in the proper position, as shown in Figure 6-4 and Figure 6-5. The stator is a winding that, when energized, will generate a magnetic field because there will be current flowing through it. The rotor is the rotating portion of the motor and is made of iron or copper bars bound on the ends with aluminium. The rotor is not wired to the power source like the stator is. The motor shaft is connected to the rotor; therefore, when the rotor turns, so does the motor shaft. The motor’s bearings allow for low-friction rotation of the rotor. Bearing help reduce the friction and the heat generated by the motor’s moving and rubbing parts and surfaces. The motor housing, end bells, and base hold the motor components in place and provide a means for securely mounting the motor itself. Figure 6-5 The windings of electric motor Electricity and magnetism are used to create the rotation of the electric motor to drive the fans and compressors. Magnets are known to have two different electrical poles, north and south. Unlike poles of a magnet attract each other, and like poles repel each other. If a stationary horseshoe magnet were placed with its two poles (north and south) at either end of a free-turning magnet as in Figure 6-6, one pole of the horseshoe magnet would line up with the opposite pole of the horseshoe magnet. If the horseshoe magnet were an electromagnet and the wires on the battery were reverses, the poles of this magnet would reverse, and the poles on the free magnet would be repelled, causing it to rotate until the unlike poles again were lined up. This is the basic principle of electric motor operation. In this example, the horseshoe magnet acts as the stator, and the free-rotation magnet acts as the rotor. In a two-pole split-phase motor the stator has two poles with insulated wire windings. When an electrical current is applied, these poles become an electromagnet with the polarity changing constantly. Figure 6-4 A electric motor Room and Small Commercial Air Conditioners The rotor may be constructed of bars, as shown in Figure 6-7. This type is called a squirrel cage rotor. The rotor is positioned between the run windings. When an alternating current (AC) is applied to these windings, a magnetic field is << 35 Section 6 produced in the windings and magnetic field is also induced in the rotor. The bars in the rotor actually form a coil. This is similar to the field induced in a transformer secondary by the magnetic field in the transformer primary. The field induced in the rotor has a polarity opposite to that in the run windings. The opposite poles of the run winding are wound in different directions. If one pole is wound clockwise, the opposite pole would be wound counterclockwise. This would set up opposite polarities for the attraction and repulsion forces that cause rotation. The attracting and repelling action between the poles of the run windings and the rotor sets up a rotating magnetic field and causes the rotor to turns. The motor starting method determines the direction of motor rotation. The motor will run equally well in either direction. Figure 6-6 Poles (north and south) on a rotation magnet Copper bars Copper end ring Shaft Welds at all joints Figure 6-7 A simple sketch of a squirrel cage rotor Single-speed motors Single-speed motors have types of single-phase, split-phase and three-phase. Single-phase motors usually use the power supply of either 115V or 208V to 230V. Some single- Room and Small Commercial Air Conditioners phase motors are dual voltage. The motor has two run windings and one start wingding. The two run windings have the same resistance, and the start winding has a high resistance. The motor will operate with the two run windings in parallel in the low-voltage mode. When it is required to run in the high-voltage mode, the technician changes the numbered motor leads according to the manufacturer’s instructions. Split-phase motors have two distinctly different windings. They have a medium amount of starting torque and a good operating efficiency. They split-phase motor is normally used for operation fans in the fractional horsepower range. The speed of motor is determined by the number of motor poles and by the method of wiring the motor poles. The technician can change the speed of a two-speed motor at the motor terminal box. Three-phase motors have some characteristics that make them popular for many applications from about 1hp into the thousands of horsepower. These motors are very efficient and require no start assist for high-torque applications. Three-phase motors have no starting windings or capacitors. They can be thought of as having three single-phase power supplies. Each of the phases can have either two or four poles. Each phase changes the direction of current flow at different times but always in the same order. A three phase motor has high starting torque because of the three phases of current that operate the motor. Three-phase motors are used mainly on commercial equipment. Two-speed motors Two-speed compressor motors are used by some manufactures to control the capacity required from small compressors. For example, a residence or small office building may have a high airconditioning load at the peak of the season and low load as a minimum. A two-speed compressor << 36 Section 6 may be desirable to accomplish the capacity control for this application. Two-speed operation is obtained by wiring the compressor motor to operate as a two-pole motor or a four-pole motor. The automatic changeover is accomplished with the space temperature thermostat and the proper compressor contactor for the proper speed. For all practical purposes, this can be considered two motors in one compressor housing. The compressor uses either motor, based on the capacity needs. This compressor has more than three motor terminals to operate the two motors in the compressor. Variable-speed motors Variable-speed motors are developed in order to meet the desire to control motors to provide a greater efficiency for the fans and compressors. Most motors do not need to operate at full speed and load except during the peak temperature of the season and could easily satisfy the airconditioning load at other times by operating at a slower speed. When the motor speed is reduced, the power to operate the motor reduces proportionately. When motors are initially started, they draw locked-rotor amperage, which can be five to seven times greater than the number of times the motor starts, and so the rate of power consumption is reduced. For example, if a home or building needs only 50% of the capacity of the air-conditioning unit to satisfy the space temperature, it would be advantageous to reduce the capacity of the unit rather than stop and restart the unit. When the power consumption can be reduce in this manner, the unit becomes more efficient. In addition, having (for example) a compressor motor operate at a lower speed for longer period of time will result in more even cooling of an occupied space. The frequency (cycles per second) of the power supply and this number of poles determine the Room and Small Commercial Air Conditioners speed of a conventional motor. The variablespeed motors can operate at different speeds with the use of electronic circuits. Several methods are used to vary the frequency of the power supply depending on the type of motor. The fan motors may be controlled through any number of speed combinations base on the needs of the system. Two types of motors that may be found in equipment today are the squirrel cage induction motor and the electronically commutated direct current (DC) motor. Instead of brushes rubbing on an armature, the motor is electronically commutated. This motor would be applied to a fin application as it is a fractional horsepower motor. Variable-speed AC motor operation can now be accomplished with electronic components. The electronic components can switch power on and off in microseconds without creating an arc; therefore, open-type contacts are not necessary for the switching purposes. 6.3 Inverter Inverters in air conditioners are mainly installed for compressor, and also used for fan. The inverter for compressor is driven by an AC power which is obtained by converting AC power from mains into DC power with the rectifier, and inverting the DC power into three phase AC power with the inverter based on a waveform signal form the waveform output circuit so as to have a desired frequency and voltage, as shown in Figure 6-8. The inverter compressor can reduce power consumption, power surges (from starting AC motors), and deliver constant pressure. Currently, these advantages are achieved with the technology at heavy expense associated with the drive and the sensitivity of these drives, particularly, to heat and moisture. << 37 Section 6 Compressor Motor Power Supply Inverter Control Unit Winding Voltage DC Motor Figure 6-8 Inverter controller for compressor Inverters have also been used for fan motor. The application of DC inverter fan motor may increase the efficiency of the fan motor from about 35% to about 75%. Inverters produce the correct frequency to the motor for the desired speed. Conventional motor speeds are controlled by the number of poles, and the frequency is a constant value. Inverters can actually control motor speeds down to about 10% of their rate speed and up to about 120% of their rated speed by adjusting the hertz to a desired value. There are different types of inverters. A common one is a six-step inverter, and there are two variations. One controls voltage and the other controls current. The six-step inverter has six switching components, two for each phase of a three-phase motor. This inverter receives regulated voltage from the converter, such as the phase-controlled inverter, and the frequency is regulated in the inverter. The voltage-controlled six-step converter has a large capacitor source at the output of the DC bus that maintains the output voltage, as shown in Figure 6-9. When the control system sends a signal to the base connection on the transistor, the transistor turns on and allows current to flow through the device. When the signal is dropped, the transistor turns off. Notice that the controllers are transistors that can be switched on and off. The current-controlled six-step inverter also has the voltage controlled at the input. It uses a large Room and Small Commercial Air Conditioners coil, often called a choke, in the DC output bus, as shown in Figure 6-10. This helps stabilize the current flow in the system. The pulse-width modulator inverter receives a fixed DC voltage from the converter, and then it pulses the voltage to the motor. At low speeds, the pulses are short; at high speeds, the pulses are longer. The pulse-width modulator pulses are sine coded to where they are narrower at the part of the cycle close to the ends. This makes the pulsating signal look more like a sine wave to the motor. Figure 6-11 shows the signal the motor receives. This motors speed can be controlled very closely. Motor Variable DC Coltage Capacitor Figure 6-9 Signal to the base connection on the transistor Choke Coil Motor DC Voltage controlled Figure 6-10 The chock coil stabilizes current flow Figure 6-11 Modulation of sine-coded and pulse-width << 38 SECTION 7 Room and Small Commercial Air Conditioners << 39 Section 7 REFRIGERANT A refrigerant is a working substance that circulates constantly in the refrigeration system. It achieves refrigeration through its own changes in state. In the evaporator, the refrigerant absorbs heat from the cooling medium (such as water or air) and changes to gaseous state. In the condenser, it condenses by transferring heat to the surrounding air or water. If compressor can be regard as the heart of the refrigeration system, then the refrigerant is the blood of the refrigeration system. The importance of the refrigerant is evidently clear. Once a refrigerant is selected for use, the other parts of the refrigeration system should be made compatible. All the designing would be to allow the refrigerant to perform even better. For example, the compressor would usually be designed and manufactured solely for a particular kind of refrigerant; the refrigeration system would also be redesigned and re-optimized for the refrigerant. 7.1 Types of Refrigerant Most refrigerants are made from two molecules, methane and ethane. These two molecules simply contain hydrogen and carbon and are referred to as pure hydrocarbons (HCs). Pure hydrocarbons were at one time considered good refrigerants, but were not used after the 1930s in any large scale because of their flammability. Any time some of the hydrogen atoms are removed from either the methane or ethane molecule and replaced with either chlorine or fluorine, the new molecule is said to be either chlorinated, fluorinated, or both. Abbreviations are used to describe refrigerants chemically and to make it simple for technicians to differentiate between them. The following are some Room and Small Commercial Air Conditioners common abbreviations: Chlorofluorocarbons (CFCs), Hydrochlorofluorocarbons (HCFCs), Hydrofluorocarbon (HFC), and Hydrocarbons (HCs). CFC refrigerants The CFCs contain chlorine, fluorine, and carbon and are considered the most damaging because their molecules cannot be destroyed as they reach the stratosphere. CFC molecules have a very long life when exposed to the atmosphere because of their stable chemical structure. This allows them to be blown up to the stratosphere by atmospheric winds where they react with ozone molecules and cause destruction. CFCs also contribute to global warming. As of July 1, 1992, it became illegal to intentionally vent CFC refrigerants into the atmosphere. HCFC refrigerants The HCFC refrigerants contain hydrogen, chlorine, fluorine, and carbon. They have a small amount of chlorine in them, but also have hydrogen in the compound that makes them less stable in the atmosphere. These refrigerants have much less potential for ozone depletion because they tend to break down in the atmosphere, releasing the chlorine before it reaches and reacts with the ozone in the stratosphere. R22, a widely used refrigerant in air conditioners, is of HCFC. However, the HCFC group is scheduled for total phase out by the year 2030. R22 is an exception, with an earlier phase out date for new equipment in 2010 and total production phase out in 2020 under the Montreal Protocol. As of July 1, 1992, it became illegal to intentionally vent HCFC refrigerants to the atmosphere. HCFCs do have some ozone-depletion potential, but it is much lower than most CFCs. << 40 Section 7 HFC refrigerants The third group of refrigerants is the HFC group. HFC molecules contain no chlorine atoms and will not deplete the earth’s protective ozone layer. HFCs contain hydrogen, fluorine, and carbon atoms. HFCs do have small global-warming potentials. HFCs are the long-term replacements for many CFC and HCFC refrigerants. It became unlawful to intentionally vent HFC refrigerants to the atmosphere on November 15, 1995. R134a, a pure HFC refrigerant, can be used in air conditioners, but is not widely considered as a suitable R22 substitute. R410A, a mixture of HFC-125 and HFC-32, is currently the most important HFC group refrigerant for air conditioners. As people become more knowledgeable about refrigerants and more concerned about environmental protection, they first added an important environmental performance evaluation standard- ODP (Ozone Depletion Potential). High ODP value means the refrigerant have more harm to ozone molecule. HC refrigerants The fourth group of refrigerants is the hydrocarbon group. These refrigerants have no fluorine or chlorine in their molecule; thus, they have no ozone depletion potential. They contain nothing but hydrogen and carbon. They do, however, contribute to global warming. Hydrocarbons are used as stand-alone refrigerants in Europe, but are not used as stand-alone refrigerants in the United States because they are flammable. Small percentages of hydrocarbons are used in many refrigerant blends in the United States but are not flammable when mixed in such small percentages. Some popular hydrocarbons include propane, butane, methane, and ethane. Table 7-1 shows the refrigerant safety classification according to the stipulations of ASHRAE Standard 34, where, “A” and “B” represent low toxicity and high/strong toxicity, respectively; “1”,”2” and “3” represent noninflammability, weak inflammability and high/ strong inflammability, respectively. People sometimes simplify things by saying that “A” represents no toxicity. 7.2 Properties and Characteristics of Refrigerants Regarding the evaluation criteria for a good refrigerant, there have been a lot of related documents and information on them. For example, safety aspect (non-toxic, noninflammable and non-explosive); cost aspect (cheap and easily obtainable); high efficiency; good environmental performance. Room and Small Commercial Air Conditioners Another important environmental performance evaluation standard is GWP (Global Warming Potential). The higher the GWP value is, the more harmful the refrigerant is. Besides ODP and GWP, the Flammability is another important evaluation standard of refrigerants. Table 7-1 Refrigerant safety classification* Lower Toxicity Higher Toxicity Higher Flammability A3 B3 Lower Flammability A2 B2 No Flammability A1 B1 *Note: Class A refers to refrigerants for which toxicity has not been identified at concentrations less than or equal to 400 ppm by volume, based on date used to determine Threshold Limit Value- << 41 Section 7 Time Weight Average (TLV-TWA) or consistent indices. Class B refers to refrigerants for which there is evidence of toxicity at concentrations below 400 ppm by volume. based on date used to determine Threshold Limit Value-Time Weight Average (TLV-TWA) or consistent indices. Class 1 refers to refrigerants that do not show flame propagation when test in air at 0.101MPa and 21ºC. Class 2 refers to refrigerants having a lower flammability limit (LFL) of more than 0.1 kg/ m3 at 0.101 MPa and 21ºC and the heat of combustion (HOC) less than 18936 KJ/kg. Class 3 refrigerants are highly flammable. They have a lower flammability limit (LFL) of less than 0.1 kg/m3 at 0.101 MPa and 21ºC or the heat of combustion (HOC) greater than or equal to 18936 KJ/kg. 7.2.1 Properties and characteristics of commonly used refrigerants Tables 7-2 and 7-3 show some information as well as concise performance comparison of several commonly used refrigerants. 7.2.2 Properties and characteristics of several kinds of refrigerant candidates Currently there are several alternatives of R22, such as R410A, R290, R32, R161 and R1270. Because R410 has been well known, this section will introduce the properties and characteristics of other four refrigerants. All these four refrigerants are inflammable, although they have different the extent of inflammability. The ODP of R290 is 0 and its GWP is close to 0. Therefore, R290 has good environmental performance. However, R290 is a Class A3 refrigerant. It has strong inflammability. Technical problems still exist regarding how it can be used safely. In the European market, there are already a small number of air conditioners using R290. They are mostly closed air conditioning systems with small capacities such as portable air conditioners. Advantages of R290: Both ODP and GWP are 0; Ultimate substitution can be achieved in one step; Weak points of R290: Difficult to overcome problems resulting from inflammability. R32 R32 is considered as a Class A2 refrigerant and it has weak inflammability. The widely used refrigerant R410A is developed by mixing R32 with R125 in 50:50 proportion in order to overcome the problem of R32’s inflammability. R125 is a fire extinguishing agent, resulting in R410A being non-inflammable. Based on the latest trend of standard revisions in the United States, the inflammability of R32 may be labeled as A2L. This means it has weak inflammability within A2 or it is closer to A1 (non-inflammability). A brief comparison of R410A, R290 and R32 is listed as follows: 1.ODP is 0 for all; 2.R32 has intermediate inflammability; 3.R32’s GWP is 650 and this is also in the middle of 0 (R290) and 1730 (R410A). R290 R290 (i.e. propane) is a natural refrigerant. Room and Small Commercial Air Conditioners << 42 CHF2CF3 CF3CH2F CHF2CH2CF3 CH3CH2CH3 chlorodifuloromethane difluoromethane 2,2-dichloro-1,1,1-trifluoroethane Pentafluoroethane 1,1,1,2-tetrafluoroethane 1,1,2,2,3-Pentafluoropropane Propane R-125/143a/134A(44/52/4) R-32/125/134a(23/25/52) R-32/125(50/50) R-12/152a(73.8/26.2) R-125/143a(50/20) Butane Ammonia Water Carbon dioxide 22 32 123 125 134a 245fa 290 404a 407C 410A 500 507a 600 717 Room and Small Commercial Air Conditioners 718 744 CO2 H2O NH3 CH3CH2CH2CH3 CHCl2CF3 CH2F2 CHClF2 CCl2F2 dichlorodifluoromethane 12 CCl3F Chemical Formula trichlorofluoromethane Chemical Name 11 Refrigerant Number 44 18 17 58.1 44 134.05 102 120 153 52 86.5 120.9 137.4 Molecular Mass A1 A1 B2 A3 A1 A1 A1 A1 A1 A3 B1 A1 A1 B1 A2 A1 A1 A1 Safety Group N/A N/A N/A <1 <1 8.8 14.6 32.6 1.4 5.6 12.1 102 80 Atmospheric Lifetime (Yrs) Table 7-2 General information of several commonly used refrigerants 0 0 0 0 0.74 0 0 0 0 0 0 0.2 0 0.055 1 1 ODP 1 <1 0 ~0 6010 1730 1530 3260 ~0 820 1300 2800 90 650 1500 8100 3800 GWP Section 7 << 43 163.068 209.702 126.187 124.663 24 -30 -41 -52 28 11 12 22 32 123 Room and Small Commercial Air Conditioners 149.352 -1 -33 100 -78 600 717 718 744 -34 -52 410A -47 168.554 -44 404a 407C 500 144.170 -46 290 507a 220.370 15 -42 245fa 209.398 412.090 402.031 200.863 139.294 158.191 132.954 146.914 -48 -26 125 134a 136.550 135.026 Boiling Point (ºC) Refrigerant Number Velocity of Sound (m/s at 4ºC) 31 374 132 152 71 106 70 86 73 97 154 101 66 184 78 96 112 198 Temp (ºC) 7.38 22.06 11.33 3.80 3.72 4.43 4.79 4.64 3.78 4.25 3.63 4.06 3.63 3.66 5.78 4.99 4.14 4.41 Press (MPa) Critical Point 42.9 37 38.8 Bubble (ºC) 42.9 37 38.8 Dew (ºC) 0.3 10.8 1.0 Glide (ºC) 0.092 1.545 0.162 0.194 0.166 0.230 0.157 0.198 0.167 -.120 0.536 0.256 0.189 0.534 0.149 0.208 0.237 0.546 Viscosity (MPa/s at 4ºC) 2.705 4.419 4.645 2.340 1.395 1.080 1.529 1.425 1.402 2.544 1.307 0.919 1.275 0.996 1.300 1.300 0.943 0.862 Specific Heat (KJ/kg•K at 4ºC) Table 7-3 Operational information of several commonly used refrigerant 0.105 0.570 0.546 0.115 0.075 0.083 0.113 0.101 0.076 0.104 0.088 0.090 0.069 0.082 0.151 0.151 0.074 0.095 Thermal Cond (W/m•K at 4ºC) Section 7 << 44 Section 7 Compared to R290, R32 has weak inflammability. Its superiority lies in that: • With the same charge, the safety risk of R32 is lower; • With similar safety controls, a larger charge can be allowed for R32. This means that refrigeration and air conditioning equipment of larger capacities can be allowed. R161 It is China that proposes R161 as a refrigerant at the first time. R161 also has inflammability but its inflammability is weak compared to R290. Its inflammability is however significantly higher than that of R32 and it belongs to Class 3. R161 has already passed the acute/short-term toxicity tests to prove that it is non-toxic. As R32 has a GWP of 650, it is still not friendly enough to the environment. In addition, the compressor exhaust temperature of the R32 system is higher than those using R290 or R410A, resulting in a major challenge for the stability of the entire system. Advantages of R161: The inflammability of R161 is weaker than that of R290; Advantages of R32: The ODP of R32 is 0; GWP is 650 (lower than that of R410A); The inflammability is weaker than R290; R1270 The main reason to recommend R1270 (i.e. propylene) is that R1270 is highly compatible with R22 systems. Weak points of R32: Very possible to be replaced again in the future; Higher compressor exhaust temperature. Weak points of R161: R161 had never been considered as a refrigerant before. There are also few researches on its properties. Summarization of properties of several R22 substitutes The important properties of several R22 substitutes are summarized in Table 7-4 to Table 7-6. Table 7-4 Thermal physics and environmental characteristics for possible R22 Substitutes GWP Relative Charge Relative CO2 Emission Equivalent During Leak 86.47 1810 1.0 1810 -- 52.02 675 0.6 405 -77.6 -42.1 44.10 20 0.51 10.2 -99.4 R161 37.6 48.06 12 0.56 6.7 -99.6 R410A -51.4 72.58 2100 0.84 1764 -2.5 R407C -43.6 86.20 1800 1.0 1800 0 R134a -26.1 102.03 1430 1.18 1687 -0.1 R1234yf -29.4 114.01 4 1.32 5.3 -99.7 CO2 -78.4 44.01 1 0.51 0.51 -100 Boiling Point (ºC) Molar Mass R22 -40.8 R32 -51.7 R290 Refrigerant Room and Small Commercial Air Conditioners CO2 Emission Reduction Proportion (%) << 45 Section 7 Table 7-5 Thermal performance of various kinds of R22 substitutes pe/MPa pc/MPa t2 Δt COP q0 qv R22 Refrigerant 0.627 2.179 100.7 0 3.43 151.82 3779.61 R32 1.029 3.523 122.23 0 3.15 231.49 5876.06 R290 0.59 1.900 77.65 0 3.34 256.15 3095.94 R161 0.554 1.937 93.92 0 3.49 279.78 3386.42 R410A 0.104 3.485 97.55 0.1 2.99 142.40 5212.58 R407C 0.678 2.498 89.14 4.7 3.12 137.68 3750.77 R134a 0.378 1.481 78.41 0 3.44 138.84 2401.29 R1234yf 0.399 1.453 74.43 0 3.30 108.73 2262.59 Table 7-6 Inflammable limits of several kinds of inflammable R22 substitutes Refrigerant R32 R290 R161 R1234yf ISO Safety Class A2 A3 A3 A2 LFL (%) 14.4 2.1 3.8 6.2 LFL (kg/m3) 0.306 0.038 0.076 0.293 UFL (%) 29.3 10.0 - 12.3 HOC (KJ/kg) 9400 50400 26600 10300 7.3 Technological Developments in Refrigerant Use R22 has been used for many years and is still widely used because of its good thermal properties. But R22 is an Ozone depletion substance, and should be phased out. R410A does not deplete ozone, and is once thought as a successful R22 substitute. In order to replace R22 by R410A, the air conditioner should be redesigned, e.g., decreasing the tube diameter in order to bear the high pressure of R410A. As both R410A and R22 have high GWP, none of them can be used for long time, and new refrigerants to replace them are under searching. Room and Small Commercial Air Conditioners R1234yf is one alternative refrigerant for air conditioner because it is a low GWP substance. But application of R1234yf may obviously decrease the cooling capacity and energy efficiency of the air conditioner. In order to overcome the problems, R1234yf is used in a mixture with R32. Application of R1234yf-R32 mixture may result in better performance of the air conditioner than that using pure R1234yf, but the performance is still lower than that using R410A. Besides, the adding of R32 may result in higher GWP than pure R1234yf. R290 is a 0 ODP and 0 GWP substances, and it is really a good refrigerant from the viewpoint of environment protection. However it is very inflammable. In order to decrease the risk of firing caused by application of R290, the refrigerant charge should be strictly controlled. << 46 Section 7 One practical way for this purpose is to use smaller diameter tubes, such as 5 mm tubes, in heat exchangers of air conditioners. The limitation of the refrigerant charge of R290 in a single air conditioner result in that the application of R290 is limited in the range of small room air conditioners. R32 is also inflammable but its inflammability is weaker than R290. That is why R32 seems to have the possibility to be applied in the air conditioners which are too large to be charged by R290. But the application of R32 may result in too high refrigerant outlet temperature of compressor. One method to overcome the problem is to let the refrigerant status at the evaporator outlet be at two-phase, so that the compressor can be cooled by the refrigerant liquid unevaporated in the evaporator. Room and Small Commercial Air Conditioners In order to decrease the effect of refrigerant on the environment as well as other problems related to refrigerant, technologies to reduce the refrigerant charge is quite welcome. One approach to reduce the refrigerant charge is to use smaller diameter tubes in finned tube heat exchangers. Experimental results show that the finned tube heat exchanger using 5 mm diameter tubes can reduce refrigerant charge about 20%~30%, comparing with that of 7mm tube heat exchanger. Another approach is to use all-aluminum micro-channel heat exchangers. According to the claim of all-aluminum microchannel production enterprises, the reduction results from the application of micro-channel heat exchanger may decrease the refrigerant charge by 40%. However, there are still series of unresolved issues such as difficulty in removing condensate or frosting. So all-aluminum micro-channel heat exchangers can currently be used only on outdoor units of air conditioners limited for cooling, and cannot be used as heat exchangers in heat pumps. << 47 SECTION 8 Room and Small Commercial Air Conditioners << 48 Section 8 THE TECHNOLOGY FOR AIR CONDITIONER IN ASEAN REGION, AND LIFE-CYCLE ASSESSMENT OF AIR CONDITIONER 8.1 The Most Commonly Used Technology for Room and Small Commercial Air Conditioners in the Asean Region Technology level of air conditioner To illustrate and evaluate the technology level of air conditioner, the energy efficiency of air conditioner is employed as criterion. In this section, EER is used as evaluation criteria to represent the efficiency of air conditioner. Basing on the questionnaire results, the EER standards of different ASEAN countries are respectively shown as follows. In Philippines, the present lower limit of EER is 2.3. The energy efficiency label of Philippines is shown as Figure 8-1. In Thailand, the present lower limit of EER is 2.82 for air conditioner with refrigeration capacity below 8000 W, and the lower limit of EER is 2.53 for the air conditioner with refrigeration capacity from 8001 W to 12000 W. Starting from September, 2011, Singapore will ban the sale of low efficiency air conditioner in its market. The energy efficiency label of Singapore is shown as Figure 8-2 (The low efficiency air conditioner refers to those whose label has none hook, or some only one or two hook in its label). In 2010, Vietnam established the lower limit of EER as 2.5 for air conditioner. Although Indonesia does not have a clear efficiency standard until now, the government of Indonesia is considering establishing an energy standard. Malaysia does not have a clear efficiency standard until now. In ASEAN region, most countries have established or are considering establishing energy Room and Small Commercial Air Conditioners Figure 8-1 The energy efficiency label in Philippines Figure 8-2 The energy efficiency label in Singapore standard. Depending on the EER standard, the technology level of air conditioner in ASEAN region is lower than some Asia countries, such as Japan, Korea and China. << 49 Section 8 The most commonly used technology Refrigerant In ASEAN countries, although some air conditioners manufacturers are trying to promote R290 as alterative refrigerant, most air conditioner manufacturers are still using R22 and R410A, whose GWP are high, as the most commonly used refrigerant. Type of air conditioner In ASEAN region, the most commonly used air conditioners contain two types: the split type and the window type. And for ASEAN region’s hot climate, most of ASEAN countries adopt singlecool air conditioner. In Indonesia, the split type of air conditioner has about 98% market share, and most of these are single-cool air conditioner. In Philippines, the window type of air conditioner has about 80% market share, and the split type of air conditioner only has 20% market share. Most of air conditioners in Philippines are of single function for air cooling. In Vietnam, most air conditioners are split type, and 94% of split type are single-cool air conditioners because of its hot climate. In Thailand domestic market, the most commonly used air conditioners are of single-cool split type. In Malaysia, the most commonly type of air conditioner is single-cool split. Type of heat exchanger Because the energy standard is low or not established in most ASEAN countries, the commonly used finned tube heat exchangers are made of 7 mm or 9.52 mm diameter tubes, which are convenient to produce but require more material cost than smaller diameter tubes. However, with the increase of copper price, some air conditioner manufacturers are trying to develop finned tube heat exchangers with 5 mm diameter tubes to replace 7 mm diameter tubes. Room and Small Commercial Air Conditioners Depending on the manufacturing level in ASEAN region, the thickness of commonly used fin is 0.105 mm or larger. The fin with such a thickness requires more material cost and has a higher air-side pressure drop, comparing with fin with 0.095 mm thickness which is commonly used in Japan, China and Korea. 8.2 The Alternative Technology of ASEAN Countries Under the Montreal Protocol To decrease the emission of greenhouse gas and increase the energy efficiency of air conditioner, ASEAN manufactures improve their technology in two major ways: • Using environment friendly refrigerant; • Decreasing refrigerant charge by using new technologies, such as application of small diameter tubes. Using environment friendly refrigerant The “Montreal Protocol” signed in 1987 stipulates the restricting of using chlorofluorocarbons and other ozone-depleting chemical substances. There was research to show that, pertaining to the mitigation and control of global warming, the results of the “Montreal Protocol” are five to six times higher compared to the “Kyoto Protocol”. Because of this, the “Montreal Protocol” was praised by Kofi Annan, Secretary-General of United Nations, to be the “single most successful international agreement to date”. Currently, 191 developed countries and developing countries have signed the said agreement, and they are gradually phasing out 95% of the ozone-depleting chemical substances. In recent years, a new change is that some ASEAN countries are currently trying to more closely link refrigerant substitution with greenhouse gas emission control. << 50 Section 8 In Malaysia, the government created a National Steering Committee (NSC) to oversee the implementation of the national action plan, which paved the way for Malaysia’s ratification in 1989. The NSC is comprised of a Technical Committee and Industrial Working Groups (IWGs) on solvents, foam, aerosol, mobile air conditioning, refrigeration and fire protection. Other IWGs were established later to keep pace with the Protocol’s amendments. In 1996, the Department of the Environment created the Ozone Protection Unit (OPU) to serve as the focal point and monitor Malaysia’s phase-out activities. Malaysia’s local air conditioner uses R22 as well as R410A as refrigerant for commercial and residential units. There is an interest now to look into the use of small diameter 5mm tubes for the heat exchanger units. In Vietnam, the government made some strict policies to prohibit using refrigerant with highODP: • CFC (R11/R12, etc.) is prohibited from Jan. 1, 2010; • HCFC (R22/R123, etc.) is prohibited from Jan. 1, 2040; • Reducing the CFCs consumption in the refrigeration and air-conditioning service sector; • Complying with the phase-out schedule for CFCs under the Montreal Protocol. Decreasing refrigerant charge by application of small diameter tubes Owing to the concerns of inflammability, ODP and GWP, more attention will increasingly be given to technologies that can reduce refrigerant charge. One excellent way to reduce refrigerant charge is to use small diameter tube heat exchangers to replace current heat exchangers. In room air conditioners and small commercial air conditioners, the diameter of most tubes in heat exchanger is 7 mm or larger. To reduce the cost and refrigerant charge, some air conditioner manufactures are using 5 mm diameter tubes to replace 7 mm or larger diameter tubes in heat exchangers. To achieve the goal of application tube with 5 mm diameter, the fin should be optimized accordingly. In ASEAN countries, a very few manufacturers are researching on heat exchangers with 5 mm diameter tubes. The 5 mm finned tube heat exchanger is shown in Figure 8-3. In Thailand, the most likely alternative technologies of refrigerant are shown as follow: • Transition from CFC to HCFC and HFC alternatives; • R-12 (CFC) to be R-401A(HCFC) / R-401B(HCFC); • R-502(CFC) to be R-402A(HCFC) / R-402B(HCFC); • R-12 (CFC) to be R-134a(HFC). Figure 8-3 Finned-tube heat exchanger with 5 mm diameter tube Room and Small Commercial Air Conditioners << 51 Section 8 8.3 The Policies and Market Incentives Bbased on Low- or ZeroGWP Refrigerant in ASEAN Region 8.4 Life-cycle Assessment of Energy and Green House Gas for Air Conditioner According to the requirements of United Nations Framework Convention on Climate Change, the production and consumption of refrigerants with high-GWP should be reduced and eventually phase-out. To fulfill this responsibility, ASEAN countries’ air conditioner manufacturers have the responsibility to use refrigerants with lowor zero-GWP as replacement for refrigerants with high-GWP. However, for the limitation of technology and the increasing of cost, most ASEAN’s air conditioner manufacturers have not commonly used refrigerant with low- or zero-GWP. This section is to evaluate the energy and green house gas for air conditioners in ASEAN region, considering the influence of refrigerant type, air conditioner type and energy efficiency. Malaysia In Malaysia, the local air conditioner manufacturer tries to promote R290 (Propane), whose GWP is 20, as a drop-in replacement into R22 system during installation. But considering the increasing of cost coming with new refrigerant, R290 does not adopted by most of manufacturers. Vietnam In Vietnam, some air conditioner manufacturers try to transition from CFCs to the HCFC/HFC/ natural gas alternatives. But application of low GDP refrigerants in air conditioners is still not paid attention to. Thailand In Thailand, the most commonly used refrigerant was R22 and R410A. Some joint ventures for air conditioner producing are sharing research results of applying low-GWP refrigerants (e.g. HFO1234yf) from their father companies. However, these companies have no clear plan to apply these low-GWP refrigerants in their products. Room and Small Commercial Air Conditioners 8.4.1 Conditions of life-cycle assessment of air conditioner in ASEAN Air conditioner type, EER and refrigerant The most commonly used air conditioners contain two types: window type and split type. The range of EER of commonly sold air conditioners in markets is from 3.2 to 3.6. This section will take air conditioners respectively with EER of 3.2, 3.4 and 3.6 as examples to accomplish the life-cycle assessment. Considering the actual air conditioners sold in the markets, this section will take air conditioners respectively with three refrigerants of R22, R410A and R290 in analyzing. Service life and energy-consuming hours In ASEAN region, most of air conditioners may be used for 10 years, and some can be used for 15 years or longer. Related to the ASEAN’s climate type, air conditioners are used for averagely 8 hours per day in an entire year. During the operation of the air conditioner, the main energy consumption components (i.e. compressor and fan) might be stopped when the required temperature is achieved. It could be assumed that half of the operation duration of air conditioner is of nearly no energy consuming. Thus, the annual energy consuming hours of the air conditioner is: 365 x8x50%=1460 hours << 52 Section 8 Then, for air conditioner with a life of 10 years, the total energy-consuming hours are: 1460x10=14600 hours For air conditioner with a life of 15 years, the total energy-consuming hours are: 1460x15=21900 hours Green house effect resulted from refrigerant emission For a window type air conditioner, it could be assumed that all the refrigerant inside is not be collected when the air conditioner is disused. So the green house effect caused by the refrigerant emission is determined by the entire refrigerant charge in the air conditioners. For a split type air conditioner, it could still be assumed that all the refrigerant inside is not be collected when the air conditioner is disused. However, different from a window type air conditioner, there is unavoidable refrigerant leakage in a split type air conditioner because not all of pipelines are sealed. Assuming the total recharged refrigerant in the whole life is equal to the initial refrigerant charge in a split air conditioner, and then the green house effect caused by the refrigerant emission in the split type air conditioner is determined by two times of the initial refrigerant charge. 8.4.2 Calculation method for life-cycle assessment The evaluation of life-cycle assessment for air conditioner mainly output two values: the energy consumption and the emission of Green House Gas (GHG). The energy consumption is assessed by Eq. (8-1). Energy Consumption (kJ)= Refrigeration capacity (W) EER x Energy-consuming time (h) (8-1) The emission of Green House Gas is assessed by Eq. (8-2) to (8-4). Energy consumption (kJ) GHGEnergy(kg)= x GHGcoal (kg/kg) Combustion valuecoal(kJ/kg)(8-2) GHCRefrigerant (kg)=GWP (kg/kg) x Refrigerant charge (kg) (8-3) Green House GasTotal (kg)=GHGEnergy (kg) + GHGRefrigerant (kg)(8-4) where, GHGEnergy is the amount of green house gas due to energy consumption; Combustion valuecoal is the combustion value of coal with a value of 29260 kJ/kg; GHGcoal is green house gas emission due to coal combustion with a value of 2.62 kg per 1kg coal combustion; GHGRefrigerant is the amount of green house gas due to refrigerant; GWPs of R22, R410A and R290 are 1500, 1730 and 0, respectively. Room and Small Commercial Air Conditioners << 53 Section 8 8.4.3 Results of life-cycle assessment of air conditioner 1. Influence of EER • When EER changes from 3.2 to 3.4, the emission of green house gas decreases 5.4% at most; • When EER changes from 3.2 to 3.6, the emission of green house gas decreases 10.8% at most. 2. Influence of refrigerant type • When the refrigerant changes from R22 to R410A, the GHG emission of air conditioner decreases 3.9% at most; • When the refrigerant changes from R22 to R290, the GHG emission of air of air conditioner decreases 55.1% at most. 3. Influence of service life • When service life increases from 10 to 15 years, the energy consumption increases about 34%, and emission of green house gas decreases 34% at most; • When service life increasing, the proportion of refrigerant GHG emission in total GHG emission decreases in accord. So the GHG emission difference between air conditioners with different refrigerant decreases in accord, when service life increase from 10 to 15 years. Room and Small Commercial Air Conditioners << 54 Room and Small Commercial Air Conditioners 2500 R290 17 18 R22 R410A 16 3.6 R290 15 R22 R410A 14 3.4 13 15 R290 R410A 12 11 3.2 0.9 R22 R290 10 9 1.1 0.9 1.1 1.35 0.85 1.05 1.3 0.8 1 1.25 1.35 R22 R410A 8 3.6 7 0.85 R290 1.05 1.3 0.8 1 1.25 Regrigerant Charge(kg) 6 R22 R410A 5 3.4 4 10 R290 R410A 3.2 3 2 EER Refrigerant R22 Service Life (Year) 1 No. Capacity (W) 5.4x107 5.9x107 6.2x10 7 3.6x107 3.9x107 4.1x10 7 Energy Consumption (kJ) 5000 5300 5600 3300 3500 3700 GHG Energy (kg) Table 8.1 Results of life-cycle assessment 0 1954 2070 0 1833 1965 0 1730 1875 0 1903 2025 0 1816 1950 0 1730 1875 Window 0 3909 4140 0 3667 3930 0 3460 3750 0 3806 4050 0 3633 3900 0 3460 3750 Split GHG Refrigerant (kg) 5000 6954 7070 53200 7133 7265 5600 7330 7475 3300 5203 5325 3500 5316 5450 3700 5430 5575 Window 5000 8909 9140 5300 8967 9230 5600 9060 9350 3300 7106 7350 3500 7133 7400 3700 7160 7450 Split GHG Total (kg) Section 8 << 55 REFERENCES [1] International Copper Association & Shanghai Jiao Tong University. Air-Conditioner Questionnaire for ASEAN Countries. April, 2011. [2] MarchWIN. Report for International Copper Association - Development Direction for Next Generation of Environmentally Friendly Refrigerants. August, 2010. [3] Zezhao Hua, Hua Zhang, Baolin Liu, Shenyi Wu. Refrigerant Technology. Science Press, 2009. [4] Guoliang Ding, Chunlu Zhang, Li Zhao. Calculation methods, tables and diagrams for thermal properties of new refrigerants. Shangahi: Shangahai Jiaotong University Press, 2003. [5] Ruzhu Wang, Guoliang Ding. Novel technologies in refrigeration and air conditioning. Beijiang: Science Press, 2002. [6] Guoliang Ding, Hua Ouyang, Hongguang Li. Digital design for refrigeration and air conditioning appliances. Beijing: Architectural Industry Press, 2008. [7] William C. Whitman, William M. Johnson, John A. Tomczyk, Eugene Silberstein. Refrigeration & Air Conditioning Technology. Delmar CENGAGE Learning, 2009. [8] International Standard ISO 5151: Non-ducted air conditioners and heat pumps-Testing and rating for performance. 2010. [9] ASHRAE. ANSI/ASHRAE Standard 34-1997: Designation and Safety Classification of Refrigerants. Atlanta, Ga., ASHRAE, 1997. [10] Houghton et al. 1995 IPCC Report: HFCs Table 2.9; CFCs and HCFCs Table 2.2, 1996. [11] Ozone Secretariat UNEP, 1996. [12] ARTI Refrigerant Database, based on WMO and IPCC assessments, August 1998. GWP shown are for 100 year integrated time horizon. [13] NIST Standard Reference Database 23, Version 6.01 (NIST 1996). [14] ASHRAE Fundamentals Handbook chapter 20, 2001. Room and Small Commercial Air Conditioners << 56