AD009 Manual Click for

Transcription

AD009 Manual Click for
www.adcocontrols.com
AD009 PROGRAMMING MANUAL
Features:
Features:
No of Stop
G+7 Auto Door Down Collective.
G+5 Fully Collective Selective Auto Door.
If Extension card used.
G+15 Auto Door Down Collective.
G+10 Fully Collective Selective Auto Door.
Operations:
Operations:
Universal
Simplex down Collective
Simplex full Collective
Speed:
Speed:
Up to 2 m/sec
TWO SEVEN SEGMENT and Keypad Interface
Using 2 SEGMENT and Keypad user can set
parameter as per they requirement.
All are password protected so other can not
change the parameter. Manual will carry the list of
parameter and instruction of programming.
Call Register LED and Call Push Button are
on single wire.
On board Seven Segment Display.
All the Input and Output are Opto-isolated and
available in both 12VDC and 24VDC.
All the Input and Output are carrying LED indication
on board.
3
[email protected]
www.adcocontrols.com
AD009 PROGRAMMING MANUAL
Group A:
Group A:
A0 (CAM ON TIME): 0 to 99 Second: Default: 0
R-Cam Operating Time Setting
A1 (CAM OFF TIME): 0 to 99 Second: Default: 2
R-Cam De-energize time setting
GROUP
GROUP
A2 (FAN OFF TIME): 0 to 99 Second: Default: 4
Auto light and FAN time setting. This time start after all call become zero, interlock circuit ok.
A3 (DO ON TIME)
Door Open Command Operating Time Setting
A4 (DO ON HOLD TIME): 0 to 99 Second Default 10 Sec (if 0 Disable)
Time during which Do Command will remain on. After this time Do command become off.
A5 (DC ON TIME) : 0 to 99 Second
Door Close Command Operating Time Setting
GROUP-A
A0
A1
A2
A3
A4
A5
A6
A7
A8
A9
AA
AB
AC
AD
AE
AF
CAM ON TIME
CAM OFF TIME
FAN OFF TIME
DO ON TIME
DO ON HOLD TIME
DC ON TIME
DC ON HOLD TIME
DO ATTEMPT
UP ON TIME
UP OFF TIME
DOWN ON TIME
DOWN OFF TIME
WAIT AT FLOOR
FIRE FLOOR
NO OF FLOOR
FACTORY RESET
GROUP-B
B0 to BF FLOOR0
to No of Floor
Segment display setting
GROUP-C
C0 REED SIGNAL
C1 AUTO/MANUAL
C2 SPEED
C3 LOCK TYPE
C4 DOWN COLLECTIVE
C5 UP COLLECTIVE
C6 COUNT REED SELECTION
C7 STOP REED SELECTION
C8 CARE COUNT
C9 FAST TRAVEL TIME
CA SLOW TRAVEL TIME
CB INS TRAVEL TIME
CC DO AFTER LIMIT
CD DC AFTER LIMIT
CE SAFETY TIMER
CF PASSWORD CHANGE
GROUP-D
D0 Up Final2
D1 Down Final2
D2 Up Final1
D3 Down Final1
D4 All Reed
D5 DO LIMIT
D6 DC LIMIT
D7 DC ON CONT.
D8 VERSION
D9 DO DC WITH
DOOR ZONE
DA BAUD RATE
DB SERIAL COP
DC PG FEEDBACK
DD DOB FUNCTION
DE SEGMENT BLINK
DF CALL CLEAR
AUTO TO ATTEND
GROUP-E
E0 CARE COUNT FLOOR
E1 CAM ON OFF ATTEMPT
E2 THIRD SPEED
E3
E4
E5
E6
E7
E8
E9
EA
Eb
EC
Ed
EE
EF
CIL BREAK DELAY
PG ON Time
DIRECTION SELECTION
POWER ON DELAY
SECOND SPEED
REVERSE
A6 (DC ON HOLD TIME): 0 to 99 Second Default 10 Sec (if 0 Disable)
Time in which doors must be closed. Before this time to zero if DC Limit or Interlock Come Door
Close Operation will be complete. After This time if Interlock is not Ok then door will reopen again.
After three attempts without a result the door error will activate, and after this time there will be
one attempt to close and lock the doors Also the error will be logged in the error table.
A7 (DO ATTEMPT)
No of time Door open and close function retry.
A8 (UP ON TIME): 0.1 to 9.9 Second: Default: 0
Up Command Operating Time setting
A9 (UP OFF TIME): 0.1 to 9.9 Second: Default: 0
Up command off time setting. These time starts after floor level stop command come.
AA (DN ON TIME): 0.1 to 9.9 Second: Default: 0
Down Command Operating Time setting
Ab (DN OFF TIME): 0.1 to 9.9 Second: Default: 0
Down command off time setting. These time starts after floor level stop command come.
Ac (WAIT AT FLOOR): 0 to 99 Second: Default: 4
Wait at floor between two calls. This timer is only applicable for V3F and Regular
Lift not for Auto Door.
Ad (FIRE FLOOR): 0 to No Of Floor: Default: 0
In Fire Mode Lift will go the above selected floor? Default it is Ground floor
AE (NO OF FLOOR): 0 to 16 : Default : 8 (G+7)
No of Stop
AF (FACTORY RESET):
For Factory Reset you have to enter a password and wait a second all the default
parameter will be restore.
4
5
www.adcocontrols.com
[email protected]
GROUP B SEGMENT DISPLAY SETTING (B0 to BF)
Floor Segment value change at every floor
GROUP C :
GROUP C :
C0 REED SIGNAL: Type of Floor Signal
CO = 00 : Every Floor Reed (All Reed)
CO = 01 : Cabin Top Reed (Three Reed)
C1 AUTO/MANUAL: Type of Lift
C1 = 00 : Manual Door
C1 = 01 : Auto Door
CC DO ON AFTER LIMIT
Cd DC ON AFTER LIMIT
CE SAFETY TIMER
C2 SPEED
C2 = 00 : Single Speed
C2 = 01 : Two Speed
CF PASSWORD CHANGE:
Enter new password then press Enter key new password will set
C3 LOCK TYPE
C3 = 00 : Simple Lock
C3 = 01 : Otis Type Lock
C4 & C5 COLLECTIVE
C4 = 01 & C5 = 00 Down Collective
C5 = 01 & C4 = 00 Up Collective
C4 & C5 = 00 Up Down Collective
C4 & C5 = 01 Fully Collective Selective
C6 COUNT REED SELECTION (This is only for Cabin Top Reed option)
C6 = 00 : Mono-Stable Reed Switch
C6 = 01 : Bi-Stable Reed Switch
C7 STOP REED SELECTION
(This is only for Cabin Top Reed option)
C7 = 00 : Mono-Stable Reed Switch
C7 = 01 : Bi-Stable Reed Switch
C8 CARE COUNT : (0 to 99 ) X 20 : Default : 0(Disable)
After care count is activation lift will count the no of times lift go for Care Count floor
as per EO Parameter if it equal to care count it will ask for maintenance.
C9 FAST TRAVEL TIME: 0 to 99 Second: Default: 15
This timer started after Up or Down Fast Command Come. If in between any
Floor reed signal come they will restart. If time out occurs it will stop the output.
CA SLOW TRAVEL TIME: 0 to 99 Second: Default: 15
This timer started after up or Down Slow Command Come. If in between any
Floor reed signal come they will restart. If time out occurs it will stop the output.
6
Cb INS TRAVEL TIME: 0 to 99 Second: Default: 15
This timer started after up or Down Maintenance Command Come. If in between any Floor reed
signal come they will restart. If time out occurs it will stop the output.
GROUP D
GROUP D
d0 UFC2
d0 = 00 : UFC2 = NO
d0 = 01 : UFC2 = NC
d1 DFC2
d1 = 00 : DFC2 = NO
d1 = 01 : DFC2 = NC
d2 UFC1
d2 = 00 : UFC1 = NO
d2 = 01 : UFC1 = NC
d3 DFC1
d3 = 00 : DFC1 = NO
d3 = 01 : DFC1 = NC
d4 ALL REED
d4 = 00 : ALL REED = NO
d4 = 01 : ALL REED = NC
d5 DO LIMIT
d5 = 00 : DO LIMIT = NO
d5 = 01 : DO LIMIT = NC
d6 DC LIMIT
d6 = 00 : DC LIMIT = NO
d6 = 01 : DC LIMIT = NC
d7 DC ON CONT
ON/OFF
d8 VERSION
Current Version
GROUP E
Please check parameter list
Keys Configuration:
UP
BACK
DN
ENTER
KEY PAD
7
[email protected]
www.adcocontrols.com
Parameter
List :
Parameter List :
Programming
Step :
Programming Step :
Using Two Segments and 4 Keys Enter, Back, Up and Down. User can program the parameter.
Press the Enter key for 3 Sec to enter into Program Mode. Very first it will ask for password.
After entering password correct you can access board parameter. If password enters incorrect
three times system gets block off.
ALL PARAMETER ARE DIVIDED INTO FIVE GROUP A, B, C, D AND E.
Using UP and DN key User can change group of parameter as per your requirement.
And press enter key on your required group you will get list of parameter related that group.
E.g. suppose you want to change a FAN Off timing.
Step 1: Press Enter Key for 3 Sec you will get P on segment. After that enter a correct password.
Then go to Group A using UP/DN Key.
Step 2: Press Enter On A Group you will got list of A group parameter. Now using UP/DOWN
Key go to A2 Parameter and press enter key you will get value of FAN OFF TIME.
Step 3: Now as per your requirement set time in Sec using UP/DOWN Key. After that press
Enter Key to Store a Data. Or Back key to come out without storing a Data.
Above example for setting of FAN OFF TIME
Step 1: Press Enter Key for 3 Sec You will got P
Enter
Password
Default is
09
Within Sec
Password
Screen
Will Come
Using
UP Key
go to
A2
Press
Enter
Key
8
Press
Enter
Key
Using
UP/DN
Key Set
Parameter
Press Enter
Key To
store value
Sr. No.
Name
1
2
A0
A1
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
Parameter
Range
CAM ON TIME
CAM OFF TIME
0-99 Sec
0-99 Sec
0
1
0-99 Sec
0-99 Sec
0-99 Sec
00-99 Sec
0-99 Sec
0-99
0.0-9.9 Sec
0.0-9.9 Sec
0.0-9.9 Sec
0.0-9.9 Sec
0-99 Sec
0-15
1-16
00
0 to 15
ALL/THREE REED
AUTO/MANUAL DOOR
SINGLE/TWO
SIMPLE/OTIS LOCK
DOWN COLLECTIVE
UP COLLECTIVE
MONO/BISTABLE SW
MONO/BISTABLE SW
(0-99 ) X 20 COUNT
0-99 Sec
0-99 Sec
0-99 Sec
1.0-9.9 Sec
1.0-9.9 Sec
4
1
4
1
4
8
0
0
0
0
4
0
8
0 TO 15
1-THREE REED
1-AUTO DOOR
1-TWO SPEED
1-OTIS LOCK
00 (UPDOWN
COLLECTIVE )
MONO SW
MONO SW
0 COUNT
0
0
0
0
0
0-99 Sec
00
2 ( 0 ) NO/( 1 ) NC
2 ( 0 ) NO/( 1 ) NC
1 ( 0 ) NO/( 1 ) NC
1 ( 0 ) NO/( 1 ) NC
( 0 ) NO/( 1 ) NC
( 0 ) NO/( 1 ) NC
( 0 ) NO/( 1 ) NC
( 0 ) OFF/( 1 ) ON
Current Version
2
09
( 1 ) NC
( 1 ) NC
( 1 ) NC
( 1 ) NC
( 0 ) NO
( 0 ) NO
( 0 ) NO
( 0 ) OFF
08
( 0 ) OFF/( 1 ) ON
( 0 ) OFF
See The Chart
( 0 ) OFF/( 1 ) ON
( 0 ) OFF/ ( 1 ) ON
( 0 ) OFF/ ( 1 ) ON
(3) 19200 bps
( 0) OFF
( 0 ) OFF
( 0 ) OFF
FAN OFF TIME
A2
A3
DO ON TIME
A4
DO ON HOLD TIME
A5
DC ON TIME
A6
DC ON HOLD TIME
A7
DO ATTEMPT
A8
UP ON TIME
A9
UP OFF TIME
AA
DOWN ON TIME
Ab
DOWN OFF TIME
Ac
WAIT AT FLOOR
Ad
FIRE FLOOR
AE
NO OF FLOOR
AF
FACTORY RESET
B 0 to B F
SEGMENT SETTING
REED SIGNAL
C0
C1
AUTO/MANUAL
SPEED
C2
C3
LOCK TYPE
C4
DOWN COLLECTIVE
C5
UP COLLECTIVE
C6
COUNTING REED SELECTION
C7
STOPING REED SELECTION
C8
CARE COUNT
FAST TRAVEL TIME
C9
CA
SLOW TRAVEL TIME
INS TRAVEL TIME
CB
CC
DO ON AFTER LIMIT
CD
DC ON AFTER LIMIT
32
33
34
35
36
37
38
39
40
41
42
CE
CF
D0
D1
D2
D3
D4
D5
D6
D7
D8
43
D9
SAFETY TIMER
PASSWORD
UP FINAL 2
DOWN FINAL 2
UP FINAL 1
DOWN FINAL 1
ALL REED
DOLIMIT
DCLIMIT
DC ON CONT
VERSION
AUTO DOOR COMMAND
WITH DRIVE STOP
44
45
46
47
DA
DB
DC
DD
BAUD RATE
Serial COP
PGFeedback
DOB FUNCTION
Default
9
[email protected]
www.adcocontrols.com
Parameter
Range
Default
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
DE
DF
E0
E1
E2
E3
E4
E5
E6
E7
E8
E9
EA
Eb
EC
Ed
EE
EF
SEGMENT BLINKING
CALL CLEAR AUTO TO ATTND
CARE COUNT FLOOR
CAM ON OFF ATTEMPT
THIRD SPEED FOR HIGH SPEED
CIL BREAK DELAY
PG ON Time
DIRECTION SELECTION
POWER ON DELAY
SECOND SPEED REVERSE
( 0 ) OFF / ( 1 ) ON
( 0 ) OFF / ( 1 ) ON
0-15
00-99
0-15
0-99
0.0-9.9 Sec
( 0 ) OFF / ( 1 ) ON
00-99 SEC
( 0 ) OFF / ( 1 ) ON
( 1 ) ON
( 1 ) ON
0
16
2
3
1.0 Sec
( 0 ) OFF
2 SEC
( 1 ) ON
21
22
23
24
25
26
27
28
29
30
10
9
8
7
6
5
4
3
2
1
Name
20
19
18
17
16
15
14
13
12
11
Sr.No.
GND
+12V
Parameter
List :
Parameter List :
41
42
43
44
45
46
47
48
49
50
AD009_MAIN
31
32
33
34
35
36
37
38
39
40
51
52
53
54
55
56
57
BACK
UP
DOWN
RA
RB
ENTER
10
21
22
23
24
25
26
27
28
29
30
11
12
13
14
15
16
17
18
19
20
1
2
3
4
5
6
7
8
9
10
AD009 _EXT
11
[email protected]
www.adcocontrols.com
Ad009
Card Connection
AD009 MAIN CARDMain
CONNECTION
No
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
Input
Regular / Drive/Auto
4 Reed / 2 Reed
Fire
Inspection
Fire
Inspection
Fire
Inspection
DFC2
UFC2
Auto
Stop
DFC2
UFC2
Auto
Stop
DFC2
UFC2
Auto
Stop
LIL
CIL
Drive Stop
LIL
CIL
Drive Stop
LIL
CIL
Drive Stop
CDP
DCLimit
DOLimit
Dc Manual
Do Manual
Ins up
CDP
DCLimit
DOLimit
Dc Manual
Do Manual
Ins up
CDP
DCLimit
DOLimit
Dc Manual
Do Manual
Ins up
Ins Dn
R0
Ins Dn
DFC1
Ins Dn
DFC1
R1
R2
R3
R4
R5
R6
R7
DR
UR
SAFETY
Overload
DDP
UDP
UFC1
DR
UR
SAFETY
Overload
DDP
UDP
UFC1
C/s
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
Call Pushbutton and Call Register Connection
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
12
C0
C1
C2
C3
C4
C5
C6
C7
L0
L1
L2
L3
L4
L5
L6
L7
C0
C1
C2
C3
C4
C5
C6
C7
L0
L1
L2
L3
L4
L5
L6
L7
C/S up to 6 Stop
C/S above 6 Stop
C0
C1
C2
C3
C4
C5
LUP0
LUP1
LUP2
LUP3
LUP4
LDN1
LDN2
LDN3
LDN4
LDN5
C0
C1
C2
C3
C4
C5
C6
C7
LUP0
LUP1
LUP2
LUP3
LUP4
LUP5
LUP6
LUP7
Ad009
Ext Card Connection
AD009 EXT CARD CONNECTION
Output
No
Input
Regular / Drive/Auto
Input
4 Reed / 2 Reed
A
B
C
D
E
F
G
H
DC
LpBuzzer
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
C8
C9
C10
C11
C12
C13
C14
C15
L8
L9
L10
L11
L12
L13
L14
L15
R8
R9
R10
R11
R12
R13
R14
R15
C8
C9
C10
C11
C12
C13
C14
C15
L8
L9
L10
L11
L12
L13
L14
L15
25
26
27
28
29
30
X
RA
RB
X
+12V
GND
ILBUZZER/DO
Up Drive
Down Drive
CAM
Second Speed
FAN
Third Speed
Extra
C/S above 6 Stop
C8
C9
C10
LUP8
LUP9
LDN8
LDN9
LDN10
LDN1
LDN2
LDN3
LDN4
LDN5
LDN6
LDN7
13
www.adcocontrols.com
No of Configuration for Reed Signal:
1. Every Floor Reed Signal
For this configuration R0 to R15 will be input as every floor reed signal
DFC1 with R0 and UFC1 with R15
Floor Level Stopping at DRVSTP
2. Cabin Top Reed Signal
a. Simple Three Reed
For this configuration DFC1 at R0, UFC1 at R7
Down Counting Reed at R1,Up Counting Reed at R2
Floor Level Stopping at DRVSTP
b. Bi-stable Two Reed
For this configuration DFC1 at R0, UFC1 at R7
Counting Reed at R1
Floor Level Stopping at DRVSTP
Function Selection:
1. UP Collective/Down Collective/Up Down Collective
2. Fully Collective Selective
Note: Please Refer Input Output Chart for Connection
Fault Indication:
In Case of Fault it will blink a segment with that particular fault Indication
1. CIL (Car Interlock) For a Manual Door Configuration if Car Interlock circuit is
not complete within predefined time the segment will blink with particular Floor
indication and C.
[email protected]
Circuit
Diagram Layout :
CIRCUIT DIAGRAM LAYOUT :
PAGE NUMBER
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30 / 31
SHEET DESCRIPTION
COVER SHEET
SUPPLY CIRCUIT
DRIVE CONNECTION
SINGLE SPEED MOTOR & CONTACTOR
TWO SPEED MOTOR & CONTACTOR
PM GEARLESS MOTOR & CONTACTOR
SAFETY CIRCUIT
MAIN CARD CONNECTION
LANDING WIRING
CAR WIRING
RELAY CARD + SAFETY CIRCUIT
CABIN TOP REED SIGNAL & MAGNET
BI-STABLE SIGNAL & MAGNET
EVERY FLOOR REED & MAGNET
CONTRACTOR STRIP
RELAY CARD CONNECTIONS
2. LIL(Landing Interlock) For a Manual Door Configuration if Landing interlock
circuit is not complete within predefine time the segment will blink with that
particular Floor Indication and L
3. For Auto Door Configuration it will check the both interlock up to Do Attempt
Times. After that it will blink for interlock Fault Indication as per above.
4. Up Final Short if Up Final Short the segment blink t with particular floor
indication
5. Down Final Short if Down Final Short the Segment blink d with that particular
floor indication
6. Car Push Signal Stuck Up For Manual Door if Car Push Signal Button Stuck up
the Segment blink o with that particular floor indication.
Technical Specifications:
TECHNICAL SPECIFICATIONS:
CONTROL CARD
DRIVE TYPE
CAR INSTALLATION
SUPPLY VOLTAGE
SAFETY CIRCUIT VOLTAGE
SINGLE VOLTAGE
EMERGENCY LIGHT VOLTAGE
BRAKE VOLTAGE
R CAM VOLTAGE
AD009
V3F
PARALLEL
3 X 440V, 50Hz, E
110V, 50Hz
12V DC
12V DC
110V DC
110V DC
7. Landing Push Signal Stuck Up For Manual Door if Landing Push button stuck up
the segment blink n with that particular floor indication.
14
15
16
2
1
YA
ADCO SPP
F1
FUSE
Y
1
3
5
2
4
6
E
NO
B
Y
R
35A
BB
CM
SS2
SS1
RW
FW
E
L3
L2
L1
-+
AC
DC
B0
B0
A1
B1
B2
V
W
U
MOV
SCON
B2 6 5 B1
A2
BREAK
ELEVATOR MACHINE
0110
--
BRIDGE
SCON
4 SCON 3
2
A2
MECHANICAL
BRAKE
A1
275V
U
M
YB
A0
3
230380 420440
E
0 24
A BC
N Y
5 6
BRAKE
0110
BP
110 AC
1
3
5
2
4
6
NO1
NO2
NC1
NC2
SAFETY
CONTACTOR
A2
A B C
110
A1
BREAKING
RESISTOR
FUSE
12VDC
GND 12
R
Y
B
NO
E
12
GND
0110
A0
TO MAIN CARD
SAFETY
MN
FROM RELAY CARD
Ad009
: Drive Connection
AD009 : DRIVE CONNECTION
A0
NC
COM
NO
110
SCON
0
T1
0
EXTERNAL SUPPLY
NOYO
IF PANEL IS V3F THEN NO
SPP
ADCO SMPS
IF PANEL IS V3F THEN NO
OVERLOAD. Y TO YO
F2
300VA TRANFORMER
0110 AO
DRVCOM
SP2
SSPEED
DNC
UPC
NC
COM
YO
OVER LOAD
GND 12
R
Y
B
NO
E
12
GND
0110
B
Y
R
YO
R Y B NO E
NO
Ad009
: Supply Circuit
AD009 : SUPPLY CIRCUIT
AD009 : SUPPLY CIRCUIT
1
www.adcocontrols.com
[email protected]
AD009 : DRIVE CONNECTION
SCON
5
6
SCON
MCB
17
A
A0
0110
R
Y
B
E
3
B
R
M
B
C
B
E
C
AA
A
A2
MECHANICAL
BRAKE
A1
275V
B0
B2
3
6
5
NC1
NC2
5
1
2
6
3
5
NO1
NO2
NC1
NC2
NO1
NO2
NC1
NC2
6
2
4
1
MAIN
DIRECTION
CONTACTOR
A1
110AC
A2
MN
2
MOV
275V
4
DN
DIRECTION
CONTACTOR
4
NO1
NO2
DC
DN
A1
110AC
A2
DN
3
MOV
275V
1
UP
DIRECTION
CONTACTOR
UP 110AC
A2
A1
DN
UC
0111
MOV
275V
UPC
DNC
MN
0110
A0
0110
R
Y
B
E
A4
A5
R
A A BB C C
SW7
OVERLOAD
AC
MECHANICAL
BRAKE
275V
MOV
DC
AO
UC
UP
DN A2
A1
MOV
275V 110AC
UP
DIRECTION
CONTACTOR
1
2
3
4
5
6
NO1
NO2
NO1
NO2
A1
110AC
UP A2
DN
DN
UP
NO1
NO1
MOV
275V
A1
110AC
MN A2
MN0
SSP
DOWN
DIRECTION
CONTACTOR
1
2
3
4
5
6
NO1
NO2
NO1
NO2
DC
A1
110AC
SSP A2
HIGH
SPEED
CONTACTOR
1
2
3
4
5
6
NO1
NO2
NO1
NO2
MOV
275V
MOV
275V
0110
UPC
DNC
MN
GND
A0
0110
SAFETY
R
Y
B
E
Ad009
: Two Speed Motor & Contactor Wiring
AD009 : TWO SPEED MOTOR & CONTACTOR WIRING
ELEVATOR MACHINE
CC
BB
E
B
C
B
A B C
B1
ELEVATOR MACHINE
DN
DN
SSP
1
3
5
2
4
6
1
3
5
2
4
6
NO1
A
MOV
-AC
DC
-+
SSP
SW7
OVERLOAD
B1
35A/1000V 0110
B1
B1
MN
NO1
BRIDGE
B2
NO1
B0
6
4
2
DN
MN
UP
NO1
5
3
1
NC1
6
4
2
NC1
UP
NC1
A0
0110
6
4
2
U
SSPEED
A4
A5
LOW
SPEED
CONTACTOR
1
2
3
4
5
6
NO1
NO2
NO1
NO2
NO1
R
Y
B
E
Ad009
: Single Speed Motor & Contactor
AD009 : SINGLE SPEED MOTOR & CONTACTOR
0110 35A/1000V
NO1
1
3
5
BRIDGE
UP
A0
DN
NO1
UP
2
4
6
NC1
1
3
5
NC1
MN
U
5
3
1
DN
2
4
6
U
18
U
5
3
1
NO1
UP
NO1
UP
No1
AD009 : SINGLE SPEED MOTOR & CONTACTOR
DN
www.adcocontrols.com
[email protected]
AD009 : TWO SPEED MOTOR & CONTACTOR WIRING
19
20
1
1
A3
LILn
LIL3
LIL0
LIL2
LIMIT SWITCH MOUNTING
INS UP
INS
A0
UP DN
INS TOGGLE
3
1
8
INSPECTION BOX
INS UP
INS
GND
DFC3
NC2
NC1
NO2
NO1
6
4
2
MOV
275V
INS ON
DFC2
A1
STOP
DFC2
BOTTOM FLOOR LEVEL
CIL
DFC3
5
3
1
BCON A1
110VAC
A2
INS ON
DFC1
PIT SW2
UFC1 : UP SLOW LIMIT SWITCH
UFC2 : UP TERMINAL LIMIT SWITCH
UFC3 : UP FINAL LIMIT SWITCH
DFC1 : DOWN SLOW LIMIT SWITCH
DFC2 : DOWN TERMINAL LIMIT SWITCH
DFC3 : DOWN FINAL LIMIT SWITCH
Ad009
Safety Circuit
AD009 : SAFETY:CIRCUIT
UFC2
A4
UFC1
PIT SW1
A2
MECHANICAL
BRAKE
A1
NC2
NC1
NO2
NO1
6
4
2
DFC1
A5
TOP FLOOR LEVEL
UFC3
CIL
IL2
DFC2
UFC2
DFC1
UFC1
ELEVATOR MACHINE
SLACK ROPE
110V
CIRCUTT
M
BREAK
UFC1
A6
EM. STOP
3
1N4007
A7
UFC2
SCON1
B C E
5
3
1
MN
5
UFC3
4 SCON13
NC2
NC1
NO2
NO1
6
4
2
MOV
275V
SCON
OSG
6 SCON15
B C
5
SCON2 A1
110VAC
A2
BRAKE
CONTACTOR
SAFETY
CONTROL PANEL
A0
2
275V
MOV
RECTIFIER CARD
A
W
V
U
3
1
MOV
275V
SAFETY
CONTACTOR 2
5
6 BP
BRAKE
PM GEARLESS MOTOR AND CONTACTOR WIRING
A2
A3
A4
A5
A6
A7
E
L3
L2
L1
B2
B1
A
BB
CM
SS2
SS1
RW
FW
A2
SCON2
A1
M2
A1
R1 12VDC
A2
1N4007
4
35A/1000V
3
Y1
BCON
5 B1
B0
5
BCON
2
5
+ B2 6
I
B3
6
BRAKE
PESISTOR
N1
12VDC
5
R1
SCON
0113
UV W
BCON
6
0111
NC
COM
NO
NO BCON
6
5
SCON1 A1
110VAC
A2
0110
DRIVE
SCON2
6
SAFETY
CONTACTOR 1
5
AC
0112
6
DC
R1
6
SCON1
5
6
BB
Y
5
0110
0110
GND
12
E
NO
B
Y
R
Pm Gearless
Motor
And Contactor
Wiring
PM GEARLESS MOTOR
AND CONTACTOR
WIRING
6
SCON2
DRVCOM
SP2
SSPEED
DNC
UPC
R
Y
B
N0
E
12
GND
0110
www.adcocontrols.com
[email protected]
AD009 : SAFETY CIRCUIT
GND
A1
A2
A2
A1
21
[email protected]
www.adcocontrols.com
LPn
CIL
Il2
STOP
AUTO
FIRE
L0 TO L15
C0 TO C15
DRVSTOP
DFC1, UFC1
DFC2, UFC2
22
POWER SUPPLY
:
:
:
:
:
:
:
:
:
:
CAR INTERLOCK
LANDING INTERLOCK
STOP PUSH BUTTON
AUTO/ATTEND KEY
FIREMEN SWITCH
LANDING CALL PUSH BUTTON
CAR CALL PUSH BUTTON
FLOOR LEVEL STOPING SIGNAL
DOWN & UP SLOW LIMIT SWITCH
DOWN & UP SLOW TERMINAL
LIMIT SWITCH FOR ALL REED
REFER INPUT OUTPUT CHART
OUTPUT
LL1
LL0
GND AND 12 : 12V DC POWER SUPPLY
AUTO DOOR SIGNAL
DOLIMIT
DCLIMIT
DOP
DCP
CDP
:
:
:
:
:
DOOR OPEN LIMIT
DOOR CLOSE LIMIT
DOOR OPEN PUSH
DOOR CLOSE PUSH
CAR DOOR SAFETY PAD
DO
DC
LPBUZZER
A TO H
SSPEED
ILBUZZER
:
:
:
:
:
:
UP
DN
CAM
FAN
:
:
:
:
DOOR OPEN COMMAND
DOOR CLOSE COMMAND
LANDING PUSH BUZZER
SEVEN SEGMENT OUTPUT
SECOND SPEED
INTERLOCK BUZZER
(ONLY FOR MANUAL DOOR)
UP COMMAND
DOWN COMMAND
RETERING CAM
AUTO LIGHT/FAN
LLn
GND
12
L0
L1
Ln
INPUT
TOP FLOOR
MIDDLE
FLOOR
LP0, LP1 ------- LPn : LANDING PUSH BUTTON
LL0, LL1 ------- LLn : LANDING CALL LED
DD0, DD1 ------- DDn : DOWN DIRECTION INDICATOR
UD0, UD1 ------- UDn : UP DIRECTION INDICATOR
LPn
LPn
DD0, DD1 ------- DDn : DOWN DIRECTION INDICATOR
DS0, DS1 ------- DSn : FLOOR INDICATOR (COMMON ANODE)
S-FIRE : FIRE SWITCH
12 : +12 Voltage DC
GND : GND OF +12 Voltage DC
S-FIRE
DSO
DS1
12
GND
RA
RB
11
12
13
14
15
16
17
18
19
20
L10
L11
L12
L13
L14
L15
21
22
23
24
25
26
27
28
29
30
1
2
3
4
5
6
7
8
9
10
C8
C9
C10
C11
C12
C13
C14
C15
L8
L9
AD009 EXT REV2
DD0
RA
UD0
41
42
43
44
RA
RB
RB
DD1
62
63
ENTER
DOWN
UD1
BACK
DO/ILBUZZER
UP
DOWN
CAM
SSPEED
FAN
DDn
CDP
DRVSTOP
CIL
IL2
STOP
AUTO
UFC2
DFC2
INS
FIRE
10
9
8
7
6
5
4
3
2
1
UP
55
56
57
58
59
60
61
DSn
SAFETY
UR
DR
DFC1
INSDN
INSUP
DOP
DCP
DOLIMIT
DCLIMIT
AD009
A
B
C
D
E
F
G
H
DC
LPBUZZER
UDn
31
32
33
34
35
36
37
38
39
40
45
46
47
48
49
50
51
52
53
54
Ad009
: Landing
Wiring
AD009 : LANDING
WIRING
C6
C7
L0
L1
L2
L3
L4
L5
L6
L7
20
19
18
17
16
15
14
13
12
11
GND
12
GND
+12V
UFC1
C0
C1
C2
C3
C4
C5
21
22
23
24
25
26
27
28
29
30
FIRE
AD009 : LANDING WIRING
GND
12
UL
DL
A
B
H
Ad009
: Main Card Connection
AD009 : MAIN CARD CONNECTION
AD009 : MAIN CARD CONNECTION
FIRST
FLOOR
23
24
CLO
CPn
CLn
12
12VDC
1N4007
12
A2
A1
A1
A1
12VDC
A2
A2
A1
A1
A1
12VDC
A2
12VDC
10
11
12
6 NO2
7 N03
8 NO4
11
12
9
10
5 NO1
9
RELAY
A1
CAM
4 CO
A2
A2
12VDC
1N4007
13
LILR
14
A2
6 NC4
5 NC3
6 NC2
5 NC1
CILR
8
7
6
5
2
2 CO
7
4 NC2
3 NC1
8 NO2
7 No1
RELAY
A1
1N4007
UFC2
DFC2
INS
DFC1R
A1
A2
1N4007
UFC1R
DC
DO
A1
12
12
12VDC
A2
12VDC
1N4007
FANR
A2
A1
SSPR
12VDC
1N4007
12VDC
1N4007
12VDC
1N4007
12VDC
1N4007
12VDC
1N4007
A2
A1
1N4007
12VDC
A2
12VDC
1N4007
12
A2
1N4007
CPO
A2
12
UP
A2
DNR
B
UPR
A
1N4007
STOP
UPD
DD
1
SSPEED
2
AUTO KEY
DND
1
FAN
OLL
UFC1
OVERLOAD
B1
B2
B3
AUTO KEY
OVERLOAD
12
:
:
:
:
:
:
LILR
7
5
NO1
CILR
5
7
NO1
LILR
6
8
NO2
CILR
8
6
NO2
12
GND
8
DNR
UFC2R
3
8
6
NC3 UFCIR NO2
6
4
UPR NC2 UFC2R
3
11
6
8
Nc2 DFCIR NO2
6
4
NC2
11
DOR
8
NC2 DOR
5
7
DCR
NC1
6
8
DCR
NC2
5
7
NC1
6
DNR
10 6
NC2
UPR
10 6
NC2
8
8
8
DFC2R
6
4
NC2
NO2
NO2
SS2R
SSPR
NO4
DNR
NO4
UFC2R
6
4
NC2
6
6
12
12
UPR
6
6
CAMR
8
NC2 CAMR
5
7
NC1
FANR
8
NC2 FANR
5
7
NC1
DL
CN
A2
FN
N0
OPDC
OPDO
DODCCOMON
MN
A3
SP2
SSPEDD
DNC
SSPEED
UPC
DRVCOMN
NO1
9 UPR 5
NO1
UL
9 UPR 5
GND
LANDING PUSH BUZZER
INTERLOCK BREAK (DOOR OPEN) BUZZER
OVERLOAD BUZZER
AUTO/ATTEND KEY
OVERLOAD SWITCH
+12 Voltage DC
RC1
RC0
DRVSTOP
UR
DR
FN
Y0
OL
DL
UL
AUTO
STOP
ILBUZZER
LPBUZZER
RCAM
U1
Ad009 :AD009
Relay
Card + Safety Circuit
: RELAY CARD + SAFETY CIRCUIT
FN
IL2
2
1
DFC1
DR
CIL
2
1
DSC
: FLOOR INDICATOR (COMMON ANODE) CAR
STOP
: STOP SWITCH
RCAM
: RETERING CAM
FN
: AUTO FAN / LIGHT
DR
: FLOOR COUNTING MAGNETIC SWITCH
UR
: FLOOR COUNTING MAGNETIC SWITCH
DRVSTOP : LEVEL STOP MAGNETIC SWITCH
B3
UR
CAR PUSH BUTTON
CAR CALL LED
DOWN DIRECTION INDICATOR
UP DIRECTION INDICATOR
B2
2
12
:
:
:
:
H
DSC
B1
Ad013 : Car Wiring
AD013 : CAR WIRING
2
1
DRVSTOP
A1
CP0, CP1 ------- CPn
CL0, CL1 ------- CLn
DD
UD
H
UL
DL
A
B
Cn
GND
12
C0
A2
A1
Ad013 : CAR WIRING
A2
www.adcocontrols.com
[email protected]
AD009 : RELAY CARD + SAFETY CIRCUIT
A1
A1
A1
25
[email protected]
www.adcocontrols.com
Ad013AD013
: Bi-stable
Switch & Magnet
: BI-STABLE SWITCH & MAGNET
FLOOR 2
MAGNET
MAGNET
FLOOR 0
REED SWITCH IS MONO-STABLE SWITCH
MAGNET
SWITCH CONNECTION
AD009 : BI-STABLE SWITCH & MAGNET
MAGNET
DISTANCE
FAST SPEED
DOWN
FLOOR 1
MAGNET
DISTANCE
FAST SPEED
UP
MAGNET
DISTANCE
SLOW SPEED
UP
DR
DR
REED SW
GND
DR
DR
UR
REED SW
UR
NO
26
BLACK
WHITE
BLACK
WHITE
FLOOR 1
BLACK
DISTANCE
SLOW
SPEED
UP
WHITE
BLACK
DISTANCE
SLOW
SPEED
DOWN
WHITE
FLOOR 0
DR
NO
DR
DRVSTOP
UR
NO
DRVSTOP
NO
WHITE
FLOOR 2
DRVSTOP
Info
NC
NO
DR
UR
BLACK
DRIVERSTOP
NO
GND
WHITE
COUNTING REED
REED SW
DRVSTOP
BLACK
BI-STABLE SW
DRVSTOP
FLOOR n
STOPING REED
MAGNET
FLOOR n
DISTANCE
SLOW SPEED
DOWN
REED SWITCH IS BISTABLE SWITCH
SWITCHES CONNECTION
BI-STABLE SW
Ad009 : Cabin
Top
Reed
AD009 : CABIN
TOP REED
SIGNALSignal
& MAGNET & Magnet
AD009 : CABIN TOP REED SIGNAL & MAGNET
DRVSTOP
27
[email protected]
www.adcocontrols.com
AD009 EVERY FLOOR REED SIGNAL
AD009 : CONNECTOR STRIP
MAIN CONTROL PANEL
REED SWITCH IS MONO-STABLE SWITCH
C0
C1
C2
DISTANCE
SLOW SPEED
UP
Rn
C3
C4
REED
C5
C6
R2
REED
DISTANCE
SLOW
DOWN
FLOOR 2
DISTANCE
SLOW SPEED
UP
R2
R0
GND
REED
NO
R0
R1
NO
R1
R1
RN
REED
DISTANCE
SLOW
DOWN
NO
FLOOR 1
DISTANCE
SLOW SPEED
UP
R1
REED
DISTANCE
FAST
SPEED
DOWN
R0
REED
DISTANCE
SLOW
DOWN
DISTANCE
FAST
SPEED
UP
FLOOR 0
RN
Ad009
: Connector Strip
AD009 : CONNECTOR STRIP
Ad009 AD009
Every
Floor Reed Signal
EVERY FLOOR REED SIGNAL
FLOOR n
R
Y
B
N0
E
A
B
DRVCOM
A
B
C
D
E
F
G
H
UL
DL
LPBUZZER
GND
GND
RC1
FN
Y0
C9
C10
C11
C12
C13
C14
C15
L0
L1
L2
L3
L4
L6
L7
L8
L9
L10
B0
RC0
C8
L5
12
12
C
B1
C7
L11
A0
A1
A1
A2
A2
A3
A1
A4
A5
A6
A7
L12
L13
L14
L15
DR
DRVSTP
UR
AUTO
STOP
INS
INSUP
INSDN
MAGNET
REED
MAGNET PATO
DRIVESTOP
MAGNET
FIRE
DCP
DOP
DCLIMIT
DOLIMIT
CDP
OPDO
OPDC
DODCCOMON
28
29
[email protected]
www.adcocontrols.com
RELAY CARD FOR V3F AND AUTO DOOR DRIVE
No
Coil
Connection
No
Contact
Connection
1
DFC2
18
DNC
2
UFC2
19
UPC
3
DFC1
20
SSPEED
4
UFC1
21
SSPEEDNC
5
SSPEED
22
A3
6
INS
23
0110
7
IL2
24
A2
8
CIL
25
CN
9
CAM
26
SSPEED NO
10
27
11
DND
28
12
UPD
29
13
FAN
30
14
DO
31
15
DC
32
16
BPOINT
33
17
+12V
34
FN
35
N0
36
MN
37
DL
38
UL
39
GND
Note:
If DFC1 and UFC1 NC Give Jumper between SSPEED and SSPEED NC
If DFC1 and UFC1 NO Give Jumper between SSPEED and SSPEED NO
From the MN Operate Main Contactor
30
Relay Card
For V3f And Auto Door Drive
RELAY CARD FOR V3F AND AUTO DOOR DRIVE
Relay Card
For Regular And Two Speed
RELAY CARD FOR REGULAR AND TWO SPEED
RELAY CARD FOR REGULAR AND TWO SPEED
No
Coil
Connection
No
Contact
Connection
1
DFC2
18
DNC
2
UFC2
19
UPC
3
DFC1
20
SSPEED
4
UFC1
21
SSPEED NC
5
SSPEED
22
A3
6
INS
23
DRVCOM
7
IL2
24
A2
8
CIL
25
CN
9
CAM
10
26
SP2
27
SSPEED NO
11
DND
28
12
UPD
29
0110
13
FAN
30
BP
14
DO
31
OPDC
15
DC
32
OPDO
16
BPOINT
33
DODCCOM
17
+12V
34
FN
35
N0
36
MN
37
DL
38
UL
39
GND
Note:
If DFC1 and UFC1 NC Give Jumper between SSPEED and SSPEED NC
If DFC1 and UFC1 NO Give Jumper between SSPEED and SSPEED NO
From the MN Operate Main Contactor
31
[email protected]
www.adcocontrols.com
NOTE
32
NOTE
33
www.adcocontrols.com
NOTE
34