Dry type transformers up to 25 MVA and 36.2 kV

Transcription

Dry type transformers up to 25 MVA and 36.2 kV
Resimold
Resiglas
Dry type transformers
up to 25 MVA and 36.2 kV
PM102242
PM102242
Distribution Transformers
Make the most of your energy
01
Distribution Transformers
Resimold / Resiglas
PM102236
PM102237
Dry type ransformers up to 25 MVA and 36.2 kV
Resimold dry type transformers are what you need for
all standard applications.
Resiglas dry type transformers are the perfect solution
for special applications
Worldwide, customers are demanding more
efficient solutions both to protect their users
and to ensure the reliability of their electrical
installations and networks. As an added constraint, new equipment must have a reduced
environmental impact and preserve the Earth’s
natural resources - We have the solution.
The safe and green solution for all distribution
applications
Schneider Electric produces safe and environmentally friendly equipment.
Resiglas and Resimold dry type transformers
have been specifically designed for infrastructure
projects such as: distribution substations, public
and commercial buildings and industrial and custom applications.
Schneider Electric’s dry type transformers
meet all national and international standards:
• IEC 60076-11
• NBR 10295
• NBR 5356
• NR10
• NBR 14039
Distribution Transformers
02
Resimold
Main characteristics
• Single and three-phase units
• Ratings up to 5 MVA, 36.2 kV
• Frequency: 50/60 Hz
• AN cooling for continuous indoor service
(with AF and outdoor options)
• Normal or reduced losses
Cost savings and safety are our priorities
Encapsulated in epoxy resin under vacuum,
Resimold dry type transformers ensure high performance, safety and cost savings. With no risk of
explosion or release of toxic fumes, they comply
with rigorous international safety standards.
The metallic enclosures developed by Schneider Electric offer various levels of protection and
provide maximum operator and equipment safety.
This permits installation next to the load center,
thus providing power-savings and reduced low
voltage cable requirements.
In addition, insurance costs are reduced. They
don’t require special storage construction and are
maintenance-free. Their design is well adapted
for shopping malls, office buildings, hospitals,
airports, industrial plants and auxiliary services in
power-supply plants.
Resimold dry type transformers are the right
choice when cost-savings and safety are required
in a single product.
Flame resistant and self-extinguishing,
Resimold provides an effective solution for
infrastructure projects and public buildings
confronted by fire hazards.
PM102238
Applications
• Skyscrapers
• Airports
• Railway stations
• Wind farms
• Substations
• Commercial or public buildings
• Industrial factories
PM102236
Resimold for a modern world
Minimizing space requirements and associated
civil works costs is a major issue in most building
projects today. Whether it is for a new city center
office block, an expansion in industrial process
capacity or a wind farm project, the compact
design of Resimold provides a cost-effective solution.
Distribution Transformers
03
Resimold
HV winding
The exclusive casting system and advanced technology used in our HV windings give Resimold
transformers the reliability and operating characteristics needed in high-technology applications
which demand maximum availability of electricity
supply.
This HV winding technology results in a compact
single block.
Casting system
In the face of increasingly strict regulations with
regard to the risk of fire and pollution, Schneider
Electric practices a policy of permanent research
on the behavior of insulating materials in fires.
This has led to the exclusive Class F casting
system (temperature of insulation system: 155°C)
developed in our laboratories.
This system is comprised of three main components:
• Epoxy resin
• Hardener
• Mineral filler
When polymerized, the epoxy resins associated
with the hardener form a stable three-dimensional
network.
These systems have better properties than most
plastics. Their use in transformers is justified owing to their:
• Excellent resistance to thermal aging
• Remarkable adherence to almost all known
materials.
Exceptional performance renders the windings
resistant to many chemicals. Mechanical strength
and a high-thermal conductivity are achieved by
incorporating selected mineral fillers. This enables
heat to be evacuated during use, improving fire
resistance and dramatically reducing the quantity
of combustible materials.
After hardening by polymerization, the casting
system becomes permanent. It offers excellent
fire behavior and immediate self-extinction, well
beyond the rated conditions of use. Resimold
transformers can hence be qualified as truly
flame-resistant and self-extinguishing.
PM102240
The HV winding design is in disc format with a
choice of aluminum strips or insulated aluminum
wire (or copper for special projects) cast under
vacuum in molds.
The solid insulation is obtained by vacuum casting in pre-heated molds, followed by a hardening
period under controlled temperatures.
Distribution Transformers
04
Resiglas
Resiglas - the perfect solution for special
applications
Resiglas is flame resistant and self-extinguishing. It is designed for flexibility and
sturdiness in order to meet special needs. It is
suitable for industrial installations susceptible
to fire hazards and for special applications
such as wind farms and off-shore oil and gas
platforms.
•
•
•
•
Resiglas is the innovative transformer suited
to special applications in industrial installations such as mining plants, and oil & gas
refineries. It complies with all your distribution
network specificities.
The Resiglas range of dry type encapsulated
resin transformers complies with all distribution
transformer requirements, and is the perfect
replacement for PCB transformers.
PM102237
Applications
• Off-shore oil and gas platforms
• Off-shore vessels
• Refining mills
• Paper & cellulose mills
• Steel & mining plants
• Car manufacturers
• Power supply plants
• Railways (trains, subway)
PM102241
Main characteristics
• Single and three-phase units
• Ratings up to 25 MVA, 36.2 kV
• Frequency: 50/60 Hz
• AN cooling for continuous indoor service
(with AF and outdoor options)
• Normal or reduced losses
Resiglas - flexibility and sturdiness for
special requirements
With all the intrinsic features of encapsulated
epoxy resin dry transformers (flame-resistant, no
toxic fumes, no partial discharges as per standard
IEC 60076-11), Resiglas brings you even more.
Thanks to the epoxy resin encapsulated coils
reinforced with fiberglass, as well as immunity to
environmental conditions and its fire-resistant categories E1/F1/C1, Resiglas technology presents
considerable advantages over conventional dry
transformers:
• Higher mechanical sturdiness since the
encapsulating process consists of continuous
fiberglass filaments
• Higher resistance to short-circuits and earthquake strains
Higher resistance to transient over-voltages
Safe for long-distance shipments
The exclusive cooling ducts designed for this
technology provide for optimal performance
when forced ventilation is required
Design flexibility in order to meet system
requirements (dimensions, impedance, etc).
05
Resiglas
Resiglas adapted to special applications
Resiglas dry type transformers can be
designed to meet special requirements, such as:
• Power distribution on off-shore oil platforms
to supply heavy-duty machinery
• Generator static excitement (6-pulse rectifiers)
• Power supply to low and medium voltage
drives for frequency inverters (6, 12, 18, 24,
36 pulses)
• Installation in outdoor locations and in rooms
with aggressive conditions
• Power supply of non-linear loads with high
harmonic contents (transformers with kfactor)
• Grounding systems
• Set-up transformers for generating group
outputs
• Power supply for induction furnaces
• Electrical drive systems for railway lines
HV winding
The winding consists of round or rectangular copper or aluminum wires. It is wound continuously.
The coil is formed by blocks, typically from 2 to 3
blocks of insulating material and winding, which
allows cooling ducts to be formed in the mediumvoltage coil itself. These cooling ducts also allow
a separation of the superimposed winding.
Casting system
The Resiglas technology consists of the encapsulation of the medium-voltage coils with epoxy
resin and fiberglass without the need to use steel
molds. The winding occurs over an expandable
radius cylinder, which is adjusted according to
design needs. The epoxy resin has the function of
assuring the dielectric strength of the coil, while
the fiberglass, in continuous strings, provides
mechanical strength in the coils.
Medium voltage drives
Cost-savings, quality and system reliability
With the technological improvements in medium voltage starters for heavy-duty motors, the
Resiglas dry transformers are now equipped with
intelligent solutions. One example is dephasing
transformers, supplying drives with medium voltage.
Our dry transformers are capable of withstanding
those electrical and mechanical strains resulting
from harmonic currents and voltage transients
caused by the rectifying system - while maintaining excellent performance levels.
Our design flexibility allows for the adjustment of
impedances, obtaining proper angular dephasing and voltage relationships, thus optimizing
the drive operation with a minimum of harmonic
distortion in the power supply mains.
Resiglas can be used with rectifiers of 6,12,18,24
and 36 pulses, meaning that the dephasing
obtained for each of the rectifier types allows for a
significant reduction in the harmonics returning to
the mains.
All Schneider Electric transformers, when requested, can be specially designed for non-linear loads
in order to minimize losses caused by harmonic
currents and generate less heat to be dissipated.
Examples of k-factor applicable to a few types of
loads:
• Excitement of power generators: k = 6 or
k=8
• Frequency rectifiers / converters: k = 8
• No breaks: k = 13 or k = 20
PM102243
Distribution Transformers
Distribution Transformers
Resimold / Resiglas
Resiglas
• Power rating: 0.15 to 25 MVA
• Voltage class: 7.2 / 15 / 24.2 / 36.2 kV
• Protection class: IP-00 / IP-21 / IP-44 / IP-54
(others available on request)
• Temperature class: F / H
• Temperature rise: B / F / H
• Impedance: as required by the project
• Category: E1 / F1 / C1 (or as specified by the
customer)
• Winding material: copper or aluminum
• Noise level as per NBR 10295
• Standards: IEC 60076-11 / NBR 10295 / NBR
5356 / NR10 / NBR 14039
So safe
To ensure total compliance with most national and
international standards, our transformers have
been put through the most stringent tests:
• C1 Resistant to thermal shocks
• E1 Immune to corrosive environments:
Very resistant to polluted environments andhumidity.
• F1 Fire behavior
Flame proof and self-extinguishing
Excellent classification according to HD 464
S1 standards.
So eco-friendly
Because preserving the environment is one of the
most important issues today, we have designed
our products to help you meet the latest international environmental protection guidelines and
regulations.
Resimold & Resiglas dry-type cast resin transformers are not only flame resistant and selfextinguishing, they are also free from the risk of
leakage of flammable or contaminating substances. Using non-toxic, high quality materials,
Resimold components are designed for maximum
recyclability.
Resiglas is the best solution to replace existing
PCB transformers.
Main technical features
Resimold
• Power rating: 30 to 5000 kVA
• Class 15 kV (others on request)
• HV winding: 13.8 / 13.2 / 12.6 / 12.0 / 11.4 kV
(Delta)
• LV winding: 380/220 or 220/127 V (Star)
• Insulation class HV/LV: 15 / 0.6 kV
• Temperature class HV/LV: F(155ºC)
• Temperature rise HV/LV: 105ºC
• Connection group: Dyn-1
• Frequency: 60 Hz NBI: 95 kV
• Protection degree: IP-00 or IP-21 (others on
request)
• Class: E1 / F1 / C1
• Noise level as per NBR 10295
• Standards: IEC 60076-11 / NBR 10295 / NBR
5356 / NR10 / NBR 14039
PM102244
Safe and eco-friendly
Resimold and Resiglas are the best solutions
for public safety: whether for industrial plants
susceptible to fire hazards or for use in public
buildings and high rise developments
06
Distribution Transformers
07
Resimold / Resiglas
Technical characteristics and dimensions
As per NBR 14039:2005 (medium voltage installations ranging from 1.0 kV to 36.2 kV), any
transforming substation being part of any industrial building should use only dry transformers.
Any transforming substation being part of any
residential and/or business building should use
only dry transformers, even if brick walls and
fireproof doors are available.
Resimold - dry type transformers encapsulated with epoxy resin under vacum
Power Rate
[ kVA ]
Impedance
[%]
Noise Level
[ dB ]
Height
[ mm ]
Length
[ mm ]
Width
[ mm ]
AN
IP-00 IP-21
IP-00 IP-21
IP-00 IP-21
Spacing
between
Wheels
[ mm ]
Total Mass
[ kg ]
IP-00 IP-21
45
4.0
58
1110 1335
790 1020
665
900
520
350 500
75
4.5
58
1200 1435
800 1020
665
900
520
390 560
112.5
4.5
58
1270 1565
920 1170
665 1000
520
550 770
150
4.5
58
1270 1565
970 1170
665 1000
520
650 870
225
4.0
58
1370 1665
1010 1270
665 1050
520
850 1100
300
4.5
58
1420 1735
1170 1420
665 1100
520
1200 1500
500
5.75
60
1560 1885
1325 1550
665 1100
520
1600 1950
750
5.75
64
1780 1925 1475 1700
815 1200
670
2200 2650
1000
5.75
64
1850 2135
1685 1900
815 1300
670
2670 3250
1250
5.75
65
1870 2250
1805 2000
910 1300
670
3250 3900
1500
5.75
65
1980 2350
1865 2100
1001 1300
820
4030 4730
2000
5.75
65
2160 2500
2025 2400
1001 1400
820
4900 5900
2500
6.5
65
2260 2520
2150 2450
1010 1500
820
6100 7600
3000
6.5
65
2350 2650
2300 2600
1020 1700
820
7500 8900
5000
6.5
71
3100 3700
2550 3250
2200 2350
1200
10500 12500
Resiglas - dry type transformers encapsulated with epoxy resin reinforced system
with fiberglass
Power Rate
[ MVA ]
Height
[ mm ]
Length
[ mm ]
Width
[ mm ]
IP-00
IP-21
IP-00
IP-21
IP-00
IP-21
2
2150
2600
2100
2450
1000
1500
2.5
2150
2600
2150
2450
1000
3
2200
2600 2200
2550
Spacing
between
wheels
[ mm ]
Total Mass
[ kg ]
IP-00
IP-21
820
4750
5500
1500
820
5350
6790
1000
1600
820
6800
8200
5
2850
3200 2500
2900 1500
2000
1000
10500
12500
7.5
3100
3600 2850
3200
1700
2200
1000
16000
19000
10
3250
3750
3200
1900
2200
1200
18600
20700
12.5
3650
4000 3450
3900
2000
2300
1400
26500
29000
15
4000
4500 3600
4000
2000
2500
1400
31000
33500
20
4500
5000
4000
4500 2500
2900
1500
40000
45000
25
4900
5500
4600
5200 2500
2900
1500
52000
58000
295
Resimold / Resiglas
IP Liquids
0 - Not protected.
1 - Protected against vertical water drops.
2 - Protected against water drops at a
maximum inclination of 15º.
3 - Protected against sprinkled water.
4 - Protected against water projections.
5 - Protected against jets of water.
Accessories
• Lifting lugs
• Terminal busbars with NEMA drilling
• Grounding terminals
• Two-way wheels
• Ratings nameplate
Examples of IP-applications
IP-00: Indoor installation, inside a brick substation, requiring the use of barrier against unintentional touching.
IP-21: Indoor installation, has a grounded metallic
housing that works as a barrier against unintentional touching, suitable to be installed coupled to
the switchboards and next to the load center.
IP-44: Suitable for either outdoor or indoor
installation.
PM102248
IP-55: Pressurized housing, being suitable for
either outdoor installation or indoor facilities
under aggressive conditions.
PM102246
Protection classes
NBR IEC 60529:2005
IP Solids
0 - Not protected.
1 - Protected against 50 mm-diameter solid
objects.
2 - Protected against 12 mm-diameter solid
objects.
3 - Protected against 2,5 mm-diameter solid
objects.
4 - Protected against 1 mm-diameter solid
objects.
5 - Protected against dust.
IP-54: Suitable for installation in either outdoor
locations or indoor facilities under aggressive
conditions.
PM102245
Options
• Thermal protection relay
• Metallic enclosure
• Forced ventilation kit
• Anti-vibrating wedges
• Disconnectable HV terminals
• Electrostatic shield
• Dragging base
• Seal Box for LV terminals
• Flange and bars duct
PM102247
Distribution Transformers
08
35 rue Joseph Monier
92500 Rueil Malmaison France
Phone: + 33 (0) 1 41 29 71 00
Fax: + 33 (0) 1 41 29 71 00
http://www.schneider-electric.com
Document Number NRJED311025EN
This document has been
printed on recycled paper
03/2011
© 2011 Schneider Electric. All rights reserved.
Schneider Electric