Dry type transformers up to 25 MVA and 36.2 kV
Transcription
Dry type transformers up to 25 MVA and 36.2 kV
Resimold Resiglas Dry type transformers up to 25 MVA and 36.2 kV PM102242 PM102242 Distribution Transformers Make the most of your energy 01 Distribution Transformers Resimold / Resiglas PM102236 PM102237 Dry type ransformers up to 25 MVA and 36.2 kV Resimold dry type transformers are what you need for all standard applications. Resiglas dry type transformers are the perfect solution for special applications Worldwide, customers are demanding more efficient solutions both to protect their users and to ensure the reliability of their electrical installations and networks. As an added constraint, new equipment must have a reduced environmental impact and preserve the Earth’s natural resources - We have the solution. The safe and green solution for all distribution applications Schneider Electric produces safe and environmentally friendly equipment. Resiglas and Resimold dry type transformers have been specifically designed for infrastructure projects such as: distribution substations, public and commercial buildings and industrial and custom applications. Schneider Electric’s dry type transformers meet all national and international standards: • IEC 60076-11 • NBR 10295 • NBR 5356 • NR10 • NBR 14039 Distribution Transformers 02 Resimold Main characteristics • Single and three-phase units • Ratings up to 5 MVA, 36.2 kV • Frequency: 50/60 Hz • AN cooling for continuous indoor service (with AF and outdoor options) • Normal or reduced losses Cost savings and safety are our priorities Encapsulated in epoxy resin under vacuum, Resimold dry type transformers ensure high performance, safety and cost savings. With no risk of explosion or release of toxic fumes, they comply with rigorous international safety standards. The metallic enclosures developed by Schneider Electric offer various levels of protection and provide maximum operator and equipment safety. This permits installation next to the load center, thus providing power-savings and reduced low voltage cable requirements. In addition, insurance costs are reduced. They don’t require special storage construction and are maintenance-free. Their design is well adapted for shopping malls, office buildings, hospitals, airports, industrial plants and auxiliary services in power-supply plants. Resimold dry type transformers are the right choice when cost-savings and safety are required in a single product. Flame resistant and self-extinguishing, Resimold provides an effective solution for infrastructure projects and public buildings confronted by fire hazards. PM102238 Applications • Skyscrapers • Airports • Railway stations • Wind farms • Substations • Commercial or public buildings • Industrial factories PM102236 Resimold for a modern world Minimizing space requirements and associated civil works costs is a major issue in most building projects today. Whether it is for a new city center office block, an expansion in industrial process capacity or a wind farm project, the compact design of Resimold provides a cost-effective solution. Distribution Transformers 03 Resimold HV winding The exclusive casting system and advanced technology used in our HV windings give Resimold transformers the reliability and operating characteristics needed in high-technology applications which demand maximum availability of electricity supply. This HV winding technology results in a compact single block. Casting system In the face of increasingly strict regulations with regard to the risk of fire and pollution, Schneider Electric practices a policy of permanent research on the behavior of insulating materials in fires. This has led to the exclusive Class F casting system (temperature of insulation system: 155°C) developed in our laboratories. This system is comprised of three main components: • Epoxy resin • Hardener • Mineral filler When polymerized, the epoxy resins associated with the hardener form a stable three-dimensional network. These systems have better properties than most plastics. Their use in transformers is justified owing to their: • Excellent resistance to thermal aging • Remarkable adherence to almost all known materials. Exceptional performance renders the windings resistant to many chemicals. Mechanical strength and a high-thermal conductivity are achieved by incorporating selected mineral fillers. This enables heat to be evacuated during use, improving fire resistance and dramatically reducing the quantity of combustible materials. After hardening by polymerization, the casting system becomes permanent. It offers excellent fire behavior and immediate self-extinction, well beyond the rated conditions of use. Resimold transformers can hence be qualified as truly flame-resistant and self-extinguishing. PM102240 The HV winding design is in disc format with a choice of aluminum strips or insulated aluminum wire (or copper for special projects) cast under vacuum in molds. The solid insulation is obtained by vacuum casting in pre-heated molds, followed by a hardening period under controlled temperatures. Distribution Transformers 04 Resiglas Resiglas - the perfect solution for special applications Resiglas is flame resistant and self-extinguishing. It is designed for flexibility and sturdiness in order to meet special needs. It is suitable for industrial installations susceptible to fire hazards and for special applications such as wind farms and off-shore oil and gas platforms. • • • • Resiglas is the innovative transformer suited to special applications in industrial installations such as mining plants, and oil & gas refineries. It complies with all your distribution network specificities. The Resiglas range of dry type encapsulated resin transformers complies with all distribution transformer requirements, and is the perfect replacement for PCB transformers. PM102237 Applications • Off-shore oil and gas platforms • Off-shore vessels • Refining mills • Paper & cellulose mills • Steel & mining plants • Car manufacturers • Power supply plants • Railways (trains, subway) PM102241 Main characteristics • Single and three-phase units • Ratings up to 25 MVA, 36.2 kV • Frequency: 50/60 Hz • AN cooling for continuous indoor service (with AF and outdoor options) • Normal or reduced losses Resiglas - flexibility and sturdiness for special requirements With all the intrinsic features of encapsulated epoxy resin dry transformers (flame-resistant, no toxic fumes, no partial discharges as per standard IEC 60076-11), Resiglas brings you even more. Thanks to the epoxy resin encapsulated coils reinforced with fiberglass, as well as immunity to environmental conditions and its fire-resistant categories E1/F1/C1, Resiglas technology presents considerable advantages over conventional dry transformers: • Higher mechanical sturdiness since the encapsulating process consists of continuous fiberglass filaments • Higher resistance to short-circuits and earthquake strains Higher resistance to transient over-voltages Safe for long-distance shipments The exclusive cooling ducts designed for this technology provide for optimal performance when forced ventilation is required Design flexibility in order to meet system requirements (dimensions, impedance, etc). 05 Resiglas Resiglas adapted to special applications Resiglas dry type transformers can be designed to meet special requirements, such as: • Power distribution on off-shore oil platforms to supply heavy-duty machinery • Generator static excitement (6-pulse rectifiers) • Power supply to low and medium voltage drives for frequency inverters (6, 12, 18, 24, 36 pulses) • Installation in outdoor locations and in rooms with aggressive conditions • Power supply of non-linear loads with high harmonic contents (transformers with kfactor) • Grounding systems • Set-up transformers for generating group outputs • Power supply for induction furnaces • Electrical drive systems for railway lines HV winding The winding consists of round or rectangular copper or aluminum wires. It is wound continuously. The coil is formed by blocks, typically from 2 to 3 blocks of insulating material and winding, which allows cooling ducts to be formed in the mediumvoltage coil itself. These cooling ducts also allow a separation of the superimposed winding. Casting system The Resiglas technology consists of the encapsulation of the medium-voltage coils with epoxy resin and fiberglass without the need to use steel molds. The winding occurs over an expandable radius cylinder, which is adjusted according to design needs. The epoxy resin has the function of assuring the dielectric strength of the coil, while the fiberglass, in continuous strings, provides mechanical strength in the coils. Medium voltage drives Cost-savings, quality and system reliability With the technological improvements in medium voltage starters for heavy-duty motors, the Resiglas dry transformers are now equipped with intelligent solutions. One example is dephasing transformers, supplying drives with medium voltage. Our dry transformers are capable of withstanding those electrical and mechanical strains resulting from harmonic currents and voltage transients caused by the rectifying system - while maintaining excellent performance levels. Our design flexibility allows for the adjustment of impedances, obtaining proper angular dephasing and voltage relationships, thus optimizing the drive operation with a minimum of harmonic distortion in the power supply mains. Resiglas can be used with rectifiers of 6,12,18,24 and 36 pulses, meaning that the dephasing obtained for each of the rectifier types allows for a significant reduction in the harmonics returning to the mains. All Schneider Electric transformers, when requested, can be specially designed for non-linear loads in order to minimize losses caused by harmonic currents and generate less heat to be dissipated. Examples of k-factor applicable to a few types of loads: • Excitement of power generators: k = 6 or k=8 • Frequency rectifiers / converters: k = 8 • No breaks: k = 13 or k = 20 PM102243 Distribution Transformers Distribution Transformers Resimold / Resiglas Resiglas • Power rating: 0.15 to 25 MVA • Voltage class: 7.2 / 15 / 24.2 / 36.2 kV • Protection class: IP-00 / IP-21 / IP-44 / IP-54 (others available on request) • Temperature class: F / H • Temperature rise: B / F / H • Impedance: as required by the project • Category: E1 / F1 / C1 (or as specified by the customer) • Winding material: copper or aluminum • Noise level as per NBR 10295 • Standards: IEC 60076-11 / NBR 10295 / NBR 5356 / NR10 / NBR 14039 So safe To ensure total compliance with most national and international standards, our transformers have been put through the most stringent tests: • C1 Resistant to thermal shocks • E1 Immune to corrosive environments: Very resistant to polluted environments andhumidity. • F1 Fire behavior Flame proof and self-extinguishing Excellent classification according to HD 464 S1 standards. So eco-friendly Because preserving the environment is one of the most important issues today, we have designed our products to help you meet the latest international environmental protection guidelines and regulations. Resimold & Resiglas dry-type cast resin transformers are not only flame resistant and selfextinguishing, they are also free from the risk of leakage of flammable or contaminating substances. Using non-toxic, high quality materials, Resimold components are designed for maximum recyclability. Resiglas is the best solution to replace existing PCB transformers. Main technical features Resimold • Power rating: 30 to 5000 kVA • Class 15 kV (others on request) • HV winding: 13.8 / 13.2 / 12.6 / 12.0 / 11.4 kV (Delta) • LV winding: 380/220 or 220/127 V (Star) • Insulation class HV/LV: 15 / 0.6 kV • Temperature class HV/LV: F(155ºC) • Temperature rise HV/LV: 105ºC • Connection group: Dyn-1 • Frequency: 60 Hz NBI: 95 kV • Protection degree: IP-00 or IP-21 (others on request) • Class: E1 / F1 / C1 • Noise level as per NBR 10295 • Standards: IEC 60076-11 / NBR 10295 / NBR 5356 / NR10 / NBR 14039 PM102244 Safe and eco-friendly Resimold and Resiglas are the best solutions for public safety: whether for industrial plants susceptible to fire hazards or for use in public buildings and high rise developments 06 Distribution Transformers 07 Resimold / Resiglas Technical characteristics and dimensions As per NBR 14039:2005 (medium voltage installations ranging from 1.0 kV to 36.2 kV), any transforming substation being part of any industrial building should use only dry transformers. Any transforming substation being part of any residential and/or business building should use only dry transformers, even if brick walls and fireproof doors are available. Resimold - dry type transformers encapsulated with epoxy resin under vacum Power Rate [ kVA ] Impedance [%] Noise Level [ dB ] Height [ mm ] Length [ mm ] Width [ mm ] AN IP-00 IP-21 IP-00 IP-21 IP-00 IP-21 Spacing between Wheels [ mm ] Total Mass [ kg ] IP-00 IP-21 45 4.0 58 1110 1335 790 1020 665 900 520 350 500 75 4.5 58 1200 1435 800 1020 665 900 520 390 560 112.5 4.5 58 1270 1565 920 1170 665 1000 520 550 770 150 4.5 58 1270 1565 970 1170 665 1000 520 650 870 225 4.0 58 1370 1665 1010 1270 665 1050 520 850 1100 300 4.5 58 1420 1735 1170 1420 665 1100 520 1200 1500 500 5.75 60 1560 1885 1325 1550 665 1100 520 1600 1950 750 5.75 64 1780 1925 1475 1700 815 1200 670 2200 2650 1000 5.75 64 1850 2135 1685 1900 815 1300 670 2670 3250 1250 5.75 65 1870 2250 1805 2000 910 1300 670 3250 3900 1500 5.75 65 1980 2350 1865 2100 1001 1300 820 4030 4730 2000 5.75 65 2160 2500 2025 2400 1001 1400 820 4900 5900 2500 6.5 65 2260 2520 2150 2450 1010 1500 820 6100 7600 3000 6.5 65 2350 2650 2300 2600 1020 1700 820 7500 8900 5000 6.5 71 3100 3700 2550 3250 2200 2350 1200 10500 12500 Resiglas - dry type transformers encapsulated with epoxy resin reinforced system with fiberglass Power Rate [ MVA ] Height [ mm ] Length [ mm ] Width [ mm ] IP-00 IP-21 IP-00 IP-21 IP-00 IP-21 2 2150 2600 2100 2450 1000 1500 2.5 2150 2600 2150 2450 1000 3 2200 2600 2200 2550 Spacing between wheels [ mm ] Total Mass [ kg ] IP-00 IP-21 820 4750 5500 1500 820 5350 6790 1000 1600 820 6800 8200 5 2850 3200 2500 2900 1500 2000 1000 10500 12500 7.5 3100 3600 2850 3200 1700 2200 1000 16000 19000 10 3250 3750 3200 1900 2200 1200 18600 20700 12.5 3650 4000 3450 3900 2000 2300 1400 26500 29000 15 4000 4500 3600 4000 2000 2500 1400 31000 33500 20 4500 5000 4000 4500 2500 2900 1500 40000 45000 25 4900 5500 4600 5200 2500 2900 1500 52000 58000 295 Resimold / Resiglas IP Liquids 0 - Not protected. 1 - Protected against vertical water drops. 2 - Protected against water drops at a maximum inclination of 15º. 3 - Protected against sprinkled water. 4 - Protected against water projections. 5 - Protected against jets of water. Accessories • Lifting lugs • Terminal busbars with NEMA drilling • Grounding terminals • Two-way wheels • Ratings nameplate Examples of IP-applications IP-00: Indoor installation, inside a brick substation, requiring the use of barrier against unintentional touching. IP-21: Indoor installation, has a grounded metallic housing that works as a barrier against unintentional touching, suitable to be installed coupled to the switchboards and next to the load center. IP-44: Suitable for either outdoor or indoor installation. PM102248 IP-55: Pressurized housing, being suitable for either outdoor installation or indoor facilities under aggressive conditions. PM102246 Protection classes NBR IEC 60529:2005 IP Solids 0 - Not protected. 1 - Protected against 50 mm-diameter solid objects. 2 - Protected against 12 mm-diameter solid objects. 3 - Protected against 2,5 mm-diameter solid objects. 4 - Protected against 1 mm-diameter solid objects. 5 - Protected against dust. IP-54: Suitable for installation in either outdoor locations or indoor facilities under aggressive conditions. PM102245 Options • Thermal protection relay • Metallic enclosure • Forced ventilation kit • Anti-vibrating wedges • Disconnectable HV terminals • Electrostatic shield • Dragging base • Seal Box for LV terminals • Flange and bars duct PM102247 Distribution Transformers 08 35 rue Joseph Monier 92500 Rueil Malmaison France Phone: + 33 (0) 1 41 29 71 00 Fax: + 33 (0) 1 41 29 71 00 http://www.schneider-electric.com Document Number NRJED311025EN This document has been printed on recycled paper 03/2011 © 2011 Schneider Electric. All rights reserved. Schneider Electric