Modulating Temperature and Humidity Control

Transcription

Modulating Temperature and Humidity Control
Modulating Temperature
and Humidity Control
Modulating Temperature and Humidity Control
Temperature and humidity control are important to the quality of the
indoor environment. On-off type control has been prevalent for many
years; however, fluctuations in temperature and humidity are inherent
with this type of control system. The technology of the on-off control
system has evolved and superior modulating control systems are now
available. The following discussion demonstrates the improvements the
modulating compressor and modulating reheat systems provide to temperature and humidity control.
g
din
l
i
Bu
ing
fin
e
D
rt.
o
f
m
Co
Q
Temperature Control
Temperature and humidity fluctuations are common in buildings with an onoff compressor and on-off reheat air conditioning equipment. When the air
conditioning unit’s compressor turns on, it operates at full capacity. By providing cool air to the space, the unit begins to cool the area and the temperature
drifts downward toward, and then past, the setpoint. When the temperature in
the area drops below the lower limit of the dead band, the unit turns off. After the
unit turns off, the sensible load in the space causes the temperature to drift up,
past the setpoint, until the upper dead band is exceeded. When the upper limit of
the temperature dead band is exceed, the unit’s compressor will turn on and the
process will repeat.
Humidity Control
y.
alit
u
gQ
inin
f
e
D
lit
ort.
y. B
uilding Comf
When air is dehumidified, moisture is removed from the air. A common technique used
to remove the moisture is to condense the moisture onto a cold surface. Anyone
who has poured a cold beverage on a hot and humid day knows that moisture will
condense on the glass. As air is cooled, it loses its ability to hold moisture; in the
case of the cold glass, the moisture in the air condenses onto the glass. The
moisture in a building’s air is condensed in much the same way. A fan draws
air from the space over the cooling coil of the unit to condense the moisture.
At the same time moisture is condensed from the air, the temperature is
being decreased. The moisture condensing from the air is known as latent
cooling; the temperature change of the air is known as sensible cooling.
To increase the amount of moisture condensed from the air, and further
dehumidify the air, the temperature of the air must be decreased, sometimes past the desired setpoint (subcooled). To prevent overcooling the
space, the air can be heated back up before it enters the space. This is
done by passing the dry, cool air through a warm coil to reheat the air
back up to its desired temperature before it is returned to the space.
Def
ining Qua
To understand how temperature and humidity are controlled using a dehumidifier and reheat system, it is important to realize the cooling coil,
and corresponding compressor, affects both the temperature (sensible) and
humidity (latent) control while the reheat coil affects only the temperature
(sensible) control.
Note: The temperature and humidity data shown in Figures 1-3 are taken from an actual job site installation
in the central United States. The equipment was originally ordered with an on-off compressor and onoff reheat. The customer was not satisfied with the temperature and humidity swings associated with
on-off control. Improvements were made to the system to include modulating humidity control and a
modulating capacity compressor. The results of these enhancements can be seen graphically in the
following illustrations.
Figure 1: On-Off Hot Gas Reheat, Standard On-Off Compressor
11 AM
NOON
90
80
9A
M
70
PM
AM
60
8
2
M
1P
10 AM
Humidity
10
10
20
30
40
50
5 PM
30
40
50
60
90
60
70
80
90
20
4 AM
10
6 PM
20
80
5 AM
10
70
30
3A
M
40
M
7P
50
60
M
8P
6 AM
4 PM
20
30
M
7A
40
3P
M
50
Temperature
2
AM
70
80
M
1A
9P
M
90
Note: The “turn-on” and
“turn-off” temperatures
are deliberately made to
differ by a small amount,
known as the dead band,
to prevent the unit from
frequently switching on and
off when the temperature is
near the setpoint.
IGHT
MIDN
11 PM
10 PM
On-Off Reheat & Standard On-Off Compressor
Figure 1 displays the relationship of the on-off compressor and on-off reheat to the temperature and humidity values in the space. As the on-off compressor turns on, both the
temperature and humidity decrease. To prevent the temperature of the dehumidified air
from over-cooling the space, the reheat coil heats the air before it leaves the unit. With
an on-off reheat coil, the leaving temperature cannot be modulated; instead, the temperature in the space will fluctuate up and down, as shown in the blue line of Figure 1,
as the reheat coil cycles on and off. As the compressor turns on and off, the humidity will
also fluctuate; while the compressor is on, the air is dehumidified and the space humidity drops. When the compressor is off, the latent load in the space causes the humidity
to rise until the compressor turns on again and begins to dehumidify the air, as can be
seen with the green line of data in Figure 1.
3
Modulating Reheat & Standard On-Off Compressor
Figure 2 displays the relationship of the on-off compressor and modulating reheat to the temperature and humidity values in the space.
As the on-off compressor turns on, both the temperature and humidity decrease, however, by adding modulating control to the reheat coil,
tight temperature control is achieved. This improved temperature control
is accomplished by varying the amount of reheat applied to the dehumidified air so that temperature of the air leaving the air conditioning unit
matches the desired setpoint. However, while the modulating reheat control
improves the temperature variations, it does not affect the humidity swings.
That is because the humidity oscillations are in response to the on-off operation of the compressor.
To control precisely both temperature and humidity one must be able to vary both
the cooling coil temperature and the reheat coil temperature. In a direct expansion
refrigeration system, the most efficient way to modulate coil temperature is with a
modulating capacity compressor. AAON utilizes a compressor that can modulate its
capacity from 10% to 100%.
y.
alit
u
gQ
inin
f
e
D
lit
ort.
y. B
uilding Comf
g
din
l
i
Bu
ing
fin
e
D
rt.
o
f
m
Co
Q
At part load operation, the compressor must cycle off because of low suction
temperature. Even a unit equipped with hot gas bypass will cycle its compressor
because the system will not bypass enough hot gas to operate continuously at
low part load conditions.
Figure 2: Modulating Hot Gas Reheat, Standard On-Off Compressor
90
80
Humidity
70
PM
Temperature
60
2
9A
M
10
10
20
30
40
50
5 PM
30
40
50
60
90
60
70
80
90
20
4 AM
10
3A
M
40
M
7P
30
60
M
8P
50
2
70
AM
80
9P
M
90
M
1A
IGHT
MIDN
11 PM
10 PM
6 PM
20
80
5 AM
10
70
6 AM
4 PM
20
30
M
7A
40
3P
M
50
AM
ining Qua
M
1P
10 AM
8
Def
11 AM
NOON
Modulating Reheat & Modulating Compressor
Figure 3 displays the relationship of the modulating compressor and modulating reheat to the temperature and
humidity values in the space. This figure reveals the
improvements that are obtained by including a modulating
capacity compressor and modulating reheat into air conditioning equipment design.
The improved temperature control accomplished by varying the amount of
reheat applied to the dehumidified air is still present; in addition, it is now shown
that the humidity level is precisely controlled as well. Because the modulating compressor can adjust its capacity to match the required load of sensible or latent cooling,
the modulating compressor is not required to cycle on and off as a standard compressor would to match the load. The modulating compressor can therefore maintain much
longer run times with much tighter humidity and temperature control. The combination of the modulating reheat and the modulating compressor have completely
eliminated the temperature and humidity fluctuations seen in Figure 1 and Figure 2,
associated with on-off reheat and on-off compressor control.
Figure 3: Modulating Hot Gas Reheat, Modulating Compressor
10 AM
11 AM
9 AM
ON
NO
8A
M
Temperature
8
Humidity
70
7
70
10
60
40
50
4 AM
10
4 PM
30
20
10
20
30
40
50
60
10
3 AM
5 PM
5 AM
3 PM
20
80
90
30
40
M
6A
2P
M
50
60
AM
1
90
0
PM
70
20
80
30
2A
M
40
M
6P
90
50
AM
7
8
DN
MI
90
1
70
PM
60
0
5
IGH
T
8P
M
11 PM
10 PM
9 PM
Energy Savings with Modulating Compressor
In addition to stable temperature and humidity values, energy savings
are also gained, as can be seen in Figure 4. The part load efficiency
of equipment with a modulating compressor can be up to 35% more
efficient than equipment with a standard on-off compressor and hot gas
bypass. Most air conditioning equipment spends 95% or more time operating at less than full load, therefore, there are significant energy savings
throughout the year with a system containing a modulating compressor.
Figure 4: Equipment Part Load Efficiency
Def
ining Qua
AAON
14
10
8
6
4
om
10.4
Ca
pa
cit
y
C
12
e
Fix
12.8
sor
es
pr
Var
iab
le
Energy Efficiency Ratio
y.
alit
u
gQ
inin
f
e
D
lit
ort.
y. B
uilding Comf
g
din
l
i
Bu
ing
fin
e
D
rt.
o
f
m
Co
Q
16
t
aci
ap
C
d
ry
ust
d
In
re
mp
o
yC
r
sso
2
0
Reduced Load &
Ambient Temperature
Maximum Load &
Ambient Temperature
There are a number of factors that contribute to the modulating compressors increased part load efficiency:
Reduced Cycling Losses
To match the required cooling capacity of a given load, traditionally compressors are switched on and off as necessary to meet the load requirements. When an electrical motor starts, such as the motor that drives a
compressor, there is an inrush of current (amperage). When an electrical
motor is at rest, there is very little inductive resistance to current flow
through the windings. As the motor starts to turn, this inductive resistance
increases with the increase in RPM. This means that as power is applied to a
stopped motor, there is a spike of electrical current far greater in amplitude
than the design amp draw of the motor. (Figure 5) This temporarily increases
the amp draw, each time the motor starts, and leads to decreased efficiency
at part load operation when the compressor cycles on and off because the
increased amp draw requires increased power consumption but does not provide an increase in cooling capacity.
Instead of turning on and off the motor, the capacity of
the modulating compressor is controlled through a pulse
width modulated signal to a solenoid valve. The compressor motor operates continuously; however, the pumping output of the compressor operates in two stages - the
“loaded state” and the “unloaded state”. During the loaded
state, the compressor operates like a standard scroll compressor and delivers full capacity and mass flow. However, during the unloaded state, there is no capacity and no mass flow from the compressor.
Figure 5: Example of Motor Inrush Current
Surge Current
Amps
Ta is the time it takes for the motor
to spin to it’s operating speed.
Ta
Normal Operating Current
T0
Switch
Closes
The loaded and unloaded states are created by varying the width of the pulse to a solenoid valve that controls the pumping output of the compressor. This concept can be
seen graphically in Figure 6. The solenoid valve allows the scrolls inside the compressor
to separate, which results in no compression of the gas in the scrolls. When the solenoid
valve reengages the scrolls, compression is resumed. The separation of the top scroll is
very small (1.0 mm) and consequently the amount of energy required to reposition the
scroll, and vary the pumping output, is very little (Figure 7).
Figure 6: Concept of Modulating Compressor Cycle Time
100%
0%
100%
3
12
7.5
20% Loaded
7.5
50% Loaded
7
Q
The combination of the loaded and unloaded states, over a period of
time, determine the capacity modulation of the compressor. Example: In a 20-second cycle time, if the loaded state time is 4 seconds
and the unloaded state time is 16 seconds, the compressor modulation
is (4 seconds x 100% + 16 seconds x 0%)/ 20 second = 20%. If for
the same cycle time, the loaded state time is 10 seconds and the unloaded state time is 10 seconds, the compressor modulation is 50%. The
capacity is a time-averaged summation of the loaded state and unloaded state. By varying the loaded state time and unloaded
state time, any capacity (10%-100%) can be delivered by the
compressor.
1 mm
n
Separatio
Def
y.
alit
u
gQ
inin
f
e
D
lit
ort.
y. B
uilding Comf
g
din
l
i
Bu
ing
fin
e
D
rt.
o
f
m
Co
Figure 7: Loaded and Unloaded Stages of Modulating Compressor
ining Qua
Loaded Compressor
Unloaded Compressor
This wide capacity output is continuous and seamless and is an improvement over other modulation techniques, where capacity outputs can only
be achieved in steps, or the capacity modulation is energy intensive. The
seamless delivery of capacity by the modulating compressor ensures that
there is a very tight control on room air temperature. The wide capacity output also contributes to the high energy efficiency of the system.
Frequent start-stops of the compressor consume more energy. The wider
capacity output of the modulating compressor reduces the number of
start-stops and saves energy.
Extended Operating Life
The benefit of starting up the motor fewer times not only allows greater
operating efficiency; it also can lead to longer motor life. The inrush current
(Figure 5), which occurs during the initial start up, can have a harmful effect
on motors. The initial inrush current forces the motor to spin to its operating speed immediately and abruptly. This places a great deal of stress on the
motor, thereby shortening the useful operating life of the motor. By stopping
and starting less, the motor of the modulating compressor has less strain on
it and can provide for a longer motor life and reduced maintenance costs for
the owner.
Improved Humidity Control
Optimum efficiency and effectiveness of an air conditioning
system is achieved at continuous running of the compressor; air conditioners are very inefficient when they first start
operation. It is far better for the air conditioner to run steadily for a period than to cycle for many shorter periods. The
efficiency of the typical air conditioner increases, the longer it runs,
until it reaches a steady operating point.
The ability of the air conditioner to remove moisture (latent capacity) is lowest when
the compressor first begins to operate. The moisture removed from the indoor air is
dependent upon the indoor coil temperature being below the dew point temperature of
the air. At startup, the unit’s indoor coil has not operated long enough to cool the air
to its dew point temperature; therefore, no dehumidification will occur. In addition,
for short cycles, the coil does not have time to operate at the dew point temperature
for an extended period and when the unit stops, the moisture on the coil evaporates
back into the indoor air. Thus, in humid climates, a unit with continuous operation
will do a far better job of removing moisture from the air than a unit that turns on
and off continuously.
Even at reduced capacity, the modulating compressor provides very good dehumidification because it operates at a lower suction pressure than other modulation techniques. As mentioned before, given any modulation output, the compressor operates
at full capacity during the loaded part of the cycle. This full capacity operation results
in a lower average suction pressure that leads to a lower coil temperature and greater
dehumidification.
Enhanced Compressor to Coil Surface Area Correlation
The efficiency of an air conditioning unit is the ratio of the amount of cooling produced
divided by the amount of power used - the higher the number, the greater the efficiency.
The capacity of an air conditioner is dependent not only on the outdoor conditions, but
also on indoor conditions such as temperature, humidity and airflow.
Modulating Compressor Power Usage Versus Capacity Range
90%
Percentage of Full Power
80%
70%
e
sag
60%
50%
40%
ng
ati
dul
sor
s
pre
Com
rU
we
Po
Mo
30%
20%
10%
10%
20%
30%
40%
50%
60%
70%
80%
90%
Percentage of Full Capacity
9
For a fixed capacity, on-off compressor it has been shown that
over sizing the indoor coil, in relation to the compressor, generally
reduces latent capacity (humidity removal), increases sensible capacity (temperature decrease), and improves overall efficiency. This
relationship implies that, assuming all other aspects of the system
remain constant, as the surface area of the coil increases in relation to
the capacity of the compressor the efficiency of the unit will increase because the area available for heat transfer has increased while the amount
of power used by the compressor has not.
ing
fin
e
D
rt.
o
f
m
Co
Q
The modulating capacity compressor takes advantages of this relationship
without the added cost of additional material for larger coils. As the capacity
of the compressor is modulated downward, the amount of power consumed by
the compressor also decreases (Figure 8). Therefore, in an air conditioning unit
with coils of a fixed area and a modulating capacity compressor, the reduced
amount of power used by the compressor at part load conditions will lead to
increased overall system efficiency, as shown previously in the Equipment Part
Load Efficiency of Figure 4.
ining Qua
Figure 9: Modulating Compressor Energy Savings Verses Hot Gas Bypass Energy Usage
Hot Gas Bypass Power Usage
90%
Energy Savings
80%
Percentage of Full Power
Def
y.
alit
u
gQ
inin
f
e
D
lit
ort.
y. B
uilding Comf
g
din
l
i
Bu
Modulating Compressor versus Hot Gas Bypass
A common method for modulating system capacity, until the arrival of the modulating compressor, was a technique referred to as, hot gas bypass (HGBP). Hot gas
bypass works by diverting hot, high-pressure refrigerant vapor from the discharge
line directly to the low-pressure side of the system. This keeps the compressor fully
loaded for a greater period while the cooling coil satisfies the part load condition. HGBP
greatly reduces operating efficiency because the bypassed vapor does no useful cooling and increases compressor energy usage. In fact, on-off systems equipped with
HGBP consume MORE energy than an equivalent on-off system without HGBP. The
load created by diverting a portion of hot gas away from the condenser and to
the cooling coil requires a longer runtime of the compressor and hence greater
energy usage. A standard on-off system would actually use less power than
the “modulating” HGBP system because the compressor would turn on and
off to match the load.
70%
e
sag
60%
o
or P
50%
40%
ng
ati
dul
ss
pre
rU
we
Com
Mo
30%
20%
10%
10%
20%
30%
40%
50%
60%
70%
Percentage of Full Capacity
80%
90%
The modulating scroll compressor gives a direct expansion
(DX) system the precise cooling coil control capability of a
chilled water system, without sacrificing energy performance
like a HGBP DX system. It allows effective operation of VAV
airflow systems, as well as, low part load applications, without the concern of coil freeze-up associated with on-off compressor systems.
Why use modulating temperature
and humidity control?
Many applications can benefit from the modulating compressor and modulating humidity control offered by AAON. The following applications exhibit conditions in which
the modulating system would be an ideal cost-effective enhancement to a packaged
rooftop unit.
Supermarkets and Convenience Stores Doors that are constantly opening and closing,
allowing infiltration of outside air, add latent and
sensible loads to the space. Outside air, supplied
to the building to positively pressurize the interior, will affect the latent load in the space. High
humidity levels can cause inefficient operation of
refrigeration and freezer systems. High humidity, over cooling or temperature fluctuations can
cause significant discomfort for customers.
Schools - Varying occupancy levels depending
on the time of day, and time of year, requires
a system that can match varying sensible and
latent loads. When a classroom or auditorium is
full, the latent load will be very high and the air
conditioning equipment should control the load
in the most energy efficient manner possible.
Varying amounts of outside air to the space
may require maximum dehumidification control
at only part sensible load. High humidity, over
cooling or temperature fluctuations can cause
significant discomfort for students and staff.
Restaurants and Cafés - Kitchen areas that
have many humidity producing activities, such
as dish washing, cooking, and hot beverage service can easily result in humidity control problems and over cooling by conventional packaged
rooftop units or temperature swings by equipment with only on-off humidity control. The high
degree of variable occupancy requires a system
that can accurately match a range of latent and
sensible loads. High humidity, over cooling or
temperature fluctuations can cause discomfort
for customers and staff.
Churches and Auditoriums - Like schools,
the high degree of variable occupancy can
result in humidity control problems, over
cooling situations and temperature swings
by a conventional packaged rooftop unit or
units with on-off control. Uncontrolled humidity levels can cause furniture and floors in
the building to warp or rot and can cause paint
to peel. Modulating compressor capacity is ideally suited for variable loads because the unit
matches its capacity to the varying loads in the
space.
Health Clubs - Perspiration generated in weight
rooms and during cardiovascular exercise, as
well as, shower areas can cause uncomfortable
and higher humidity space conditions. In addition to human discomfort, these conditions can
propagate the growth of mold and mildew. Properly controlled temperature and humidity in the
gym provides a healthier environment for patrons and lower maintenance costs for owners.
Museums and Libraries - These applications
require a tight degree of temperature and humidity control during part load and full load operation. High humidity levels in these structures
can cause substantial damage to priceless books
and artifacts. When precious historical objects
are on display or being stored, precise humidity
control and temperature control are necessary.
The modulating compressor and modulating reheat offered by AAON meet the demands of this
type of application.
These buildings and applications are only a few of the many instances that may benefit
from modulating temperature and humidity control. Healthcare facilities, office buildings, lodging and many other applications have profited by the temperature and humidity control that AAON provides. Contact your local AAON representative to learn more
about the many ways that AAON can provide solutions for your application.
11
ing
ing
fin
e
.D
ort
f
om
gC
n
i
ld
Bui
lity.
al
a
u
Q
ity
ining
. Bui
lding Comfort. Def
ild
Bu
.
ty
ali
Qu
ModTemp/HumCntrl • R68130 • 110914
fining Qua
ort. De
f
m
Co
It is the intent of AAON to provide accurate and current product information. However, in the interest of product
improvement, AAON reserves the right to change pricing, specifications, and/or design of its product without notice,
obligation, or liability. Copyright © AAON, all rights reserved throughout the world. AAON® and AAONAIRE® are
registered trademarks of AAON, Inc., Tulsa, OK.
Def
ining Qu