A CLEAN COMBINATION FINEST FILTRATION AND WATER SEPARATION FUEL TREATMENT SYSTEMS

Transcription

A CLEAN COMBINATION FINEST FILTRATION AND WATER SEPARATION FUEL TREATMENT SYSTEMS
A CLEAN COMBINATION
FINEST FILTRATION AND WATER SEPARATION
FUEL TREATMENT SYSTEMS
“Dies el Oil Pest” – a serious problem
Efficient fuel treatment
Diesel fuel tanks can become contaminated
The hindrance of diesel oil pest can be
with microorganisms (bacteria, yeasts, fungi
achieved by implementing continuous fuel
and algae) during storage and transport, partic-
treatment to prevent the water content from ris-
ularly when damp air inside the tank con-
ing above 70 mg/l (ppm). Mechanical separa-
denses to water. Thereby developing water
tors which use centrifugal separation cannot
phases build the basis for exponential growth
provide the necessary level of dewatering.
of microorganisms.
None of the systems which comply with the
Microbiological contamination can have very
Microbiological swabs of
insufficiently dewatered
diesel samples
serious consequences. Microorganisms and
dards of the mineral oil industry and NATO offer
their metabolisms block filter elements and
complete security, as they allow a water con-
diesel pipes. Water in the fuel courses corro-
tent of 500 ppm and 200 ppm respectively.
sion damages on the fuel injection systems up
Microorganism growth with the mentioned
to complete failure of the engine and the con-
effects already starts at water concentration of
sequential high costs for repair.
about 100 ppm.
Corrosion is further accelerated by hydrogen
A truly effective and lasting method of protect-
sulphide, a by-product of metabolism in combi-
ing fuel and lubricants against increasing water
nation with the existing water and it also dam-
concentration, and thus against contamination
ages the material of the tank inner walls. The
by microorganisms, is to employ MAHLE fuel
diesel oil pest problem can only be addressed
treatment systems.
by reducing the amount of water which is the
culture medium for microorganisms in the fuel.
Surface damage inside a
ship's diesel oil tank
2
applicable DIN standards or the delivery stan-
How fuel treatment systems work
1. The tanks contain one or multiple filter coalescer elements
depending on the flow capacity. The separated water is heavier than the medium being pumped through and it collects in
a water container at the bottom of the tank.
2. Water droplets collect in the variably structured fibre bed
layers. The size of the droplets increases in the flow direction.
These droplets flow together to form a coherent water phase
which is removed. All solids are held back.
EFFICIENT AND COST-EFFECTIVE FOR
FUEL TREATMENT SYSTEMS
KFWA
Single and multiple-stage fuel treatment
Configuration and design
systems for all needs
MAHLE Industriefiltration supplies fuel treat-
MAHLE fuel treatment systems can be used for
ment systems with a wide range of flow ca -
all types of middle distillates, e.g. diesel fuel,
pacities. The systems consist of a pump with a
marine diesel oil MDO, Marine Gas Oil (MGO)
downstream filter coalescer or depth filter and
and others. For all the most common contami-
coalescer elements as well as a central control
nations in these media, including solid and sus-
box and full differential pressure monitoring
pended particles - such as dust and sediments
system.
as well as water - the systems represent the
most efficient and cost-effective solution.
The automatic water detection and outlet sys-
The single stage fuel treatment system (type
versions the systems can be offered cus-
KFWA)
tomized in configuration and construction.
tem is standard benefit. Additional to standard
is—due
to
its
compact
design—
equipped with combined filter coalescer elePTS
ments. The dual stage version (type FTS) of the
They can be installed on the storage tank to
filter coalescer is applicable to treat heavy con-
continuously treat the medium or they can be
tamination with solids. In the first stage this ver-
used to clean the medium prior to usage, i.e.
sion has an upstream filter which can be
before it is pumped into the day tank or the
exchanged independently and which can vary
engine.
in the degrees of fineness; these systems can
be customized to meet specific requirements.
In the second stage the water separation
occurs via coalescer elements.
FTS
3
The advantages at a glance:
Filtration and water separation in one
Reliable reduction of free water content
system
down to 70 ppm
High flow capacities in a compact
Unproblematic customization of con-
design
struction
Operation without interruption due to
Flexible and customized design
automatic water detection including out-
Reduction of operating costs
let system, no need of venting
MIDDLE DISTILLATES
MAHLE fuel treatment systems in overview
Type
Flow rate (ca.)
KFWA 1 by
KFWA 1 main
700 l/h
0
KFWA 2 by
KFWA 2 main
2000 l/h
0
KFWA 3 by
KFWA 3 main
KFWA 4 by
PTS
4000 l/h
0
8000 l/h
On request
FTS 600
600 l/h
FTS 1800
1800 l/h
FTS 2400
2400 l/h
4
MAHLE Industriefiltration
The products of MAHLE Industriefiltration
develops and builds advanced filtration
are used in the following applications:
and separation technology for use in a
Bilge water separation
wide range of industrial applications such
Ballast water treatment
as power plants, civil and military ship-
Cooling lubricant and detergent pro-
building.
cessing
The company is part of the MAHLE Group,
Separation systems (petrochem. industry)
Industrial waste water cleaning
one of the top 30 automotive suppliers
Oil and fuel treatment for engines, tur-
globally and the world market leader for
bines and gears, heavy oil filtration
combustion engine components, systems
Protection of hydraulic units, pipe lines,
and peripherals.
transfer and circulation systems
CAREFUL FUEL TREATMENT
PROTECTS ENGINES AND TURBINES
MAHLE Industriefiltration supports their
treatment to ensure that these engines,
customers with fuel and oil treatment sys-
and particularly the injection systems, can
tems that benefit from our more than 40
run continuously for long periods of time.
years of experience. At the same time we
aim to lower costs while improving per-
Turbines
formance. The outstanding reliability of our
All over the world turbine power plants
filter coalescer separation technology is an
fired with diesel oils are increasingly being
invaluable asset in tough day-to-day pro-
used as an alternative to coal and nuclear
duction.
power as well as for propulsion in the shipping industry. The state-of-the-art, high-
Engines
efficiency turbine technology requires spe-
Piston engines are the drive assemblies of
cially treated fuels to function optimally.
choice for engine units that are in permanent operation, e.g. ships engines and
MAHLE matches the requirements of this
engines in combined heat and power
technology with its fuel treatment systems
plants. The fuel used requires careful
and assures smoothly and safe operation.
5
www.mahle-industrialfiltration.com
MAHLE Industriefiltration GmbH
Plant Hamburg
Tarpenring 31–33
D-22419 Hamburg
Phone +49 40 530040-0
Fax +49 40 530040-24191
[email protected]
www.mahle-industrialfiltration.com
Schleifbachweg 45
D-74613 Öhringen
Phone +49 7941 67-0
Fax +49 7941 67-23429
[email protected]
www.mahle-industrialfiltration.com
EN 70370372.04/2012