FI302 OPERATION & MAINTENANCE INSTRUCTIONS MANUAL

Transcription

FI302 OPERATION & MAINTENANCE INSTRUCTIONS MANUAL
OPERATION & MAINTENANCE
INSTRUCTIONS MANUAL
FI302
F I
3 0 2 M E
smar
www.smar.com
Specifications and information are subject to change without notice.
Up-to-date address information is available on our website.
web: www.smar.com/contactus.asp
Introduction
INTRODUCTION
The FI302 is part of Smar´s first generation of FOUNDATION™ fieldbus field equipment. It is a
converter intended to connect Foundation Fieldbus systems with actuators and positioners for 4 -20
mA control valves. The FI302 produces a 4 -20 mA output proportional to the input received by the
Fieldbus network. Its digital technology enables an easy interface between the field and the control
room, while offering several types of transference functions and interesting features that reduce
installation, operation and maintenance costs.
Foundation Fieldbus is a digital communication system that enables distributing control functions for
field equipment and advantageously replaces conventional technology.
Other protocols only disclose maintenance data, as they were not devised for control data. The main
Fieldbus goal was to overcome this situation. Closed loop control with a 4 -20 mA performance
requires high speed, which means higher power consumption – a feature that is not compatible with
intrinsic safety. This fact led to the use of a moderately high communication speed and to devise a
system with a minimum communication capability. Using scheduling synchronization, the system
controls variable sampling, algorithm execution and communication. The network treatment is
optimized and high circuit loop performance is achieved.
Using Foundation Fieldbus Technology with its capability to interconnect several devices, very large
projects can be constructed. The function block concept allows the user to easily construct the
programming and overview complex control strategies (Smar CD600 users are familiar with this
concept, since it was implemented a few years ago). Another advantage is flexibility, as the control
strategy may be edited without having to rewire or change any hardware.
The FI302 and the Smar FOUNDATION™ fieldbus family have function blocks that avoid the need for
separate equipment and facilitate implementing the control strategy. Among these function blocks,
the following may be enhanced: PID controller, Input Selector, Arithmetic, Signal Characterizer and
Integrator. These built-in blocks improve control, reduce communication, dead-time and costs.
Any FOUNDATION™ fieldbus equipment with Master Backup rapidity may work as a network master
and be locally configured using a magnetic screwdriver in several situations. This tool eliminates the
need for a configurator in many basic applications.
Read carefully these instructions to get the best result from the FI302.
III
FI302 - Operation and Maintenance Instruction Manual
NOTE
This manual is compatible with version 3.XX. The 3 indicates the software version and the XX indicates the
release. The 3.XX sign means that this manual is compatible with any release of software version-3
Waiver of responsibility
The contents of this manual abides by the hardware and software used on the current equipment
version. Eventually there may occur divergencies between this manual and the equipment. The
information from this document are periodically reviewed and the necessary or identified corrections
will be included in the following editions. Suggestions for their improvement are welcome.
Warning
For more objectivity and clarity, this manual does not contain all the detailed information on the
product and, in addition, it does not cover every possible mounting, operation or maintenance
cases.
Before installing and utilizing the equipment, check if the model of the acquired equipment complies
with the technical requirements for the application. This checking is the user’s responsibility.
If the user needs more information, or on the event of specific problems not specified or treated in
this manual, the information should be sought from Smar. Furthermore, the user recognizes that the
contents of this manual by no means modify past or present agreements, confirmation or judicial
relationship, in whole or in part.
All of Smar’s obligation result from the purchasing agreement signed between the parties, which
includes the complete and sole valid warranty term. Contractual clauses related to the warranty are
not limited nor extended by virtue of the technical information contained in this manual.
Only qualified personnel are allowed to participate in the activities of mounting, electrical connection,
startup and maintenance of the equipment. Qualified personnel are understood to be the persons
familiar with the mounting, electrical connection, startup and operation of the equipment or other
similar apparatus that are technically fit for their work. Smar provides specific training to instruct and
qualify such professionals. However, each country must comply with the local safety procedures,
legal provisions and regulations for the mounting and operation of electrical installations, as well as
with the laws and regulations on classified areas, such as intrinsic safety, explosion proof, increased
safety and instrumented safety systems, among others.
The user is responsible for the incorrect or inadequate handling of equipments run with pneumatic
or hydraulic pressure or, still, subject to corrosive, aggressive or combustible products, since their
utilization may cause severe bodily harm and/or material damages.
The field equipment referred to in this manual, when acquired for classified or hazardous areas, has
its certification void when having its parts replaced or interchanged without functional and approval
tests by Smar or any of Smar authorized dealers, which are the competent companies for certifying
that the equipment in its entirety meets the applicable standards and regulations. The same is true
when converting the equipment of a communication protocol to another. In this case, it is necessary
sending the equipment to Smar or any of its authorized dealer. Moreover, the certificates are
different and the user is responsible for their correct use.
Always respect the instructions provided in the Manual. Smar is not responsible for any losses
and/or damages resulting from the inadequate use of its equipments. It is the user’s responsibility to
know and apply the safety practices in his country.
IV
Table of Contents
TABLE OF CONTENTS
SECTION 1 - INSTALLATION ..........................................................................................................................................................1.1
GENERAL...................................................................................................................................................................................... 1.1
MOUNTING ................................................................................................................................................................................... 1.1
ELECTRIC CONNECTION ............................................................................................................................................................ 1.2
OUTPUT CONNECTION ........................................................................................................................................................... 1.2
CONNECTING THE FI302 TO THE FOUNDATION™ FIELDBUS ................................................................................................ 1.3
PREPARING THE FI302 BEFORE CONNECTING IT TO NETWORK ......................................................................................... 1.3
POWER CONSUMPTION ............................................................................................................................................................. 1.5
TERMINATOR ............................................................................................................................................................................... 1.5
CABLING ....................................................................................................................................................................................... 1.5
TOTAL CABLE LENGTH ............................................................................................................................................................... 1.6
CABLE SHIELDING ....................................................................................................................................................................... 1.7
GROUNDING ............................................................................................................................................................................ 1.7
COMMISSIONING ......................................................................................................................................................................... 1.7
COMMISSIONING STAGES ..................................................................................................................................................... 1.7
USE OF NON-PRECONFIGURED TO DEVICES ..................................................................................................................... 1.7
USE OF PRECONFIGURED EQUIPMENTS ............................................................................................................................ 1.8
LINKING DEVICE ...................................................................................................................................................................... 1.8
ERROR MONITORING AND DETECTION WITH LIVE LIST .................................................................................................... 1.8
INSTALLATION IN HAZARDOUS AREAS .................................................................................................................................... 1.8
EXPLOSION/FLAME PROOF ....................................................................................................................................................... 1.9
INTRINSICALLY SAFE .................................................................................................................................................................. 1.9
SECTION 2 - FUNCTIONAL DESCRIPTION ....................................................................................................................................2.1
FUNCTIONAL DESCRIPTION ...................................................................................................................................................... 2.1
SECTION 3 - OPERATION ...............................................................................................................................................................3.1
LIQUID CRYSTAL DISPLAY ........................................................................................................................................................ 3.1
MONITORING ............................................................................................................................................................................... 3.1
SECTION 4 - CONFIGURATION ......................................................................................................................................................4.1
TRANSDUCER BLOCK ................................................................................................................................................................. 4.1
HOW TO CONFIGURE A TRANSDUCER BLOCK ..................................................................................................................4.1
DISPLAY BLOCK .......................................................................................................................................................................... 4.2
HOW TO CONFIGURE A DISPLAY BLOCK ...........................................................................................................................4.2
SECTION 5 - CALIBRATION ............................................................................................................................................................5.1
SECTION 6 - MAINTENANCE ..........................................................................................................................................................6.1
DIAGNOSTIC BLOCK – DIAG ...................................................................................................................................................... 6.1
TROUBLESHOOTING .................................................................................................................................................................. 6.1
PHYSICAL INSPECTION......................................................................................................................................................... 6.1
PARAMETERS USED FOR TROUBLESHOOTING ................................................................................................................ 6.1
DISASSEMBLE PROCEDURE ..................................................................................................................................................... 6.3
EXPLODED VIEW ........................................................................................................................................................................ 6.3
ELECTRONIC CIRCUIT ............................................................................................................................................................... 6.4
ASSEMBLY PROCEDURE ........................................................................................................................................................... 6.4
INTERCHANGEABILITY............................................................................................................................................................... 6.4
SPARES ....................................................................................................................................................................................... 6.5
SPARE PART LIST ....................................................................................................................................................................... 6.5
SECTION 7 - ADVANCED CONFIGURATION .................................................................................................................................7.1
CHARACTERIZATION CURVE ..................................................................................................................................................... 7.1
DEFINITION OF PARAMETERS AND VALUES ........................................................................................................................... 7.3
SECTION 8 - LOCAL ADJUSTMENT ...............................................................................................................................................8.1
JUMPER CONFIGURATION ......................................................................................................................................................... 8.1
JUMPER J1 CONNECTION .......................................................................................................................................................... 8.1
JUMPER W1 CONNECTION......................................................................................................................................................... 8.2
SECTION 9 - TECHNICAL CHARACTERISTICS .............................................................................................................................9.1
ORDERING CODE ........................................................................................................................................................................ 9.2
V
FI302 - Operation and Maintenance Instruction Manual
APPENDIX A - CERTIFICATIONS INFORMATION ........................................................................................................................ A.1
MANUFACTURING LOCATION APPROVED ............................................................................................................................... A.1
EUROPEAN DIRECTIVE INFORMATION..................................................................................................................................... A.1
HAZARDOUS LOCATIONS GENERAL INFORMATION.............................................................................................................. .A.1
HAZARDOUS LOCATIONS APPROVALS ................................................................................................................................... .A.2
IDENTIFICATION PLATE AND CONTROL DRAWING ................................................................................................................. A.5
APPENDIX B – SRF – SERVICE REQUEST FORM ....................................................................................................................... B.1
RETURNING MATERIALS ............................................................................................................................................................ B.2
VI
FOUNDATION Fieldbus Blocks
Fieldbus to Current Converter Transducer Block – Parameter Description
Description of Parameter Description
Valid Range
Default/ Init
Value
Unit
Description
Positive
0
None
Indicates the level of static data.
TAG_DESC
Null
Na
Description of Transducer Block.
3
STRATEGY
0
None
4
ALERT_KEY
0
v
5
MODE_BLK
3
AUTO
None
6
BLOCK_ERR
5
7
UPDATE_EVT
Na
8
BLOCK_ALM
Na
9
TRANSDUCER_DIRECTORY
0
None
It is used to select several Transducer Blocks.
10
TRANSDUCER_TYPE
65535
None
Indicates the type of Transducer according to its
class.
11
XD_ERROR
16
None
It is used to indicate calibration status.
12
COLLECTION_DIRECTORY
None
Specifies the number of transducer index into
Transducer Block.
13
FINAL_VALUE
0
FVR
It is the current value and status that comes from AO
block.
14
FINAL_VALUE_RANGE
4.0 to 20.0 mA
FVR
The High and Low range limit values, the
engineering unit code and the number of digits to the
right of the decimal point to be used for Final Value.
15
CAL_POINT_HI
4
12.5 to 20.5 mA
20.0
mA
The highest calibrated value.
16
CAL_POINT_LO
4
3.99 to 11.5 mA
4.0
mA
The lowest calibrated value.
Index
Parameter
1
ST_REV
2
Manual
Section
1 to 255
E
5
5
This parameter is not checked and processed by
Transducer Block.
Number of identification in the plant.
Indicates the operation mode of Transducer Block.
Indicates the status associated with hardware or
software in the Transducer.
It is the alert for any static data.
It is used for configuration, hardware and other
failures.
17
CAL_MIN_SPAN
1.0
mA
The minimum calibration span value allowed. This
minimum span information is necessary to ensure
that when calibration is done, the two calibrated
points (high and low) are not too close together.
18
CAL_UNIT
mA
mA
The Device Description engineering units code index
for the calibration values.
19
ACT_SN
0
None
20
CAL_METHOD
Factory
None
21
CAL_LOC
NULL
None
22
CAL_DATE
23
SENSOR_CAL_WHO
24
RETURN
5
25
TERMINAL_NUMBER
3
26
BACKUP_RESTORE
27
CHARACTERIZATION_TYPE
0 to 2
32
None
Indicates the actuator serial number.
The method of last sensor calibration. ISO defines
several standard methods of calibration.
This
parameter is intended to record that method, or if
some other method was used.
The location of last sensor calibration.
This
describes the physical location at which the
lib ti
f
d
The date of the last sensor calibration.
The name of person who is in charge of last
calibration.
NULL
None
0
mA
0
None
Indicates the input terminal number (1, 2 and 3).
5
0
None
This parameter is used to do backup or to restore
configuration data.
6
255
None
Indicates the type of characterization curve.
1, 2, 3
This is the current value that goes to the AO Block.
VII
FI302 - Operation and Maintenance Instruction Manual
Index
28
Parameter
Manual
Section
Valid Range
Default/ Init
Value
Unit
6
True/False
False
None
Enable and disable the characterization curve.
2a8
Indicates the length of characterization curve.
CURVE _BYPASS
Description
29
CURVE_LENGTH
6
8
None
30
CURVE_X
6
%
%
Input points of characterization curve.
31
CURVE_Y
6
%
%
Output points of characterization curve.
32
FEEDBACK_CAL
4
0
mA
33
CAL_CONTROL
4
Disable
None
34
CAL_POINT_HI_BACKUP
20.0
mA
Indicates the backup for high calibration point.
En/Dis
The measured current value used by the calibration
method.
Enable and disable for calibration process.
35
CAL_POINT_LO_ BACKUP
4.0
mA
Indicates the last high calibration point.
35
CAL_POINT_HI_FACTORY
20.0
mA
Indicates the last low calibration point.
37
CAL_POINT_LO_FACTORY
4.0
mA
Indicates the low factory calibration point.
38
ORDERING_CODE
None
Indicates information about factory production.
CAPTION









AUTO - Automatic
FACTORY - Standard of factory
NULL - No standard value
NONE - No unit or no value
Na - Non-dimentional parameter
E - Parameter list
FVR - Final_Value_Range,
True/False - Accepts true/false values
En/Dis - Enables/Disables parameter
Display Block Parameters
Index
Parameter
Manual
Section
Range/Options
This is a tag of the block to which the parameter belongs to
use up to a maximum of 32 characters.
7
BLOCK_TAG_PARAM
3
8
INDEX_RELATIVE
3
0 a 65535
This is the index related to the parameter to be actuated or
viewed (1, 2...).
9
SUB_INDEX
6
1 a 255
To visualize a certain tag, opt for the index relative equal to
zero, and for the sub-index equal to one.
10
MNEMONIC
11
INC_DEC
12
DECIMAL_POINT_NUMBER
This is the mnemonic for the parameter identification
(maximum of 16 characters). Choose the mnemonic,
preferably with no more than 5 characters because, this
way, it will not necessary to rotate it on display.
6
6
13
ACCESS
14
ALPHA_NUM
63
DISPLAY_REFRESH
6
6
It is the increment and decrement in decimal units when the
parameter is Float or Float Status time, or integer, when the
parameter is in whole units.
0a4
Monit/
Action
Mnem/
Value
3
True/
False
CAPTION


VIII
Description
Monit – Monitoring
Mnem – Mnemonic
This is the number of digits after the decimal point (0 to 3
decimal digits)
The access allows the user to read, in the case of the
“Monitoring” option, and to write when “action” option is
selected, and then the display will show the increment and
decrement arrows.
These parameters include two options: value and
mnemonic. In option value it is possible to display data both
in the alphanumeric and in the numeric fields, this way, in
the case of a data higher than 10000, it will be shown in the
alphanumeric field.
It allows updating the local adjustment tree.
FOUNDATION Fieldbus Blocks
Diagnostic Block Parameters
Manual
Section
Valid Range
Default/ Init
Value
0
Spaces
0
0
O/S
Index
Parameter
1
2
3
4
5
6
ST_REV
TAG_DESC
STRATEGY
ALERT_KEY
MODE_BLK
BLOCK_ERR
5
7
EXE_TIME_TAG
5
Spaces
Na
Block tag of the selected block to measure the
execution time.
8
MIN_EXE_TIME
5
+INF
ms
Minimum execution time of the selected block.
9
10
11
12
13
14
CUR_EXE_TIME
MAX_EXE_TIME
HW_REV
FIRMWARE_REV
DEV_SN
MAIN_BOARD_SN
5
0
0
ms
ms
15
BEHAVIOR
5
0
E
16
PUB_SUB_STATUS
Current execution time of the selected block.
Maximum execution time of the selected block.
Hardware revision.
Firmware revision.
Device serial number.
Main board serial number.
Select the initial values for parameters, there are two
options Adapted and Spec.
Indicate if all external links is good or if at least one is
bad.
17
LINK_SELECTION
18
LINK_NUMBER
Number of the external link selected.
19
LINK_STATUS
Status of the external link selected (see table below)
20
LINK_RECOVER
21
BLOCK_ALM
22
SAVING_CONFIG
1 a 255
Unit
Null
Na
Null
Null
Na
E
5
5
5
0 - Adapted
1 - Spec
0 - bom
1 - ruim
0 - First
1 - Next
2 - Previous
0 - No Action
1 - Action
E
0
No Action
E
E
Na
0 - No save
1 - save
0
E
Description
See Mode Parameter.
Select an external link.
Command a recovery process to the external link
selected.
The block alarm is used for all configuration, hardware,
and connection failure or system problems in the block.
The cause of the alert is entered in the subcode field.
The first alert to become active will set the Active status
in the Status attribute. As soon as the Unreported
status is cleared by the alert reporting task, another
block alert may be reported without clearing the Active
status, if the subcode has changed.
It indicates if the device is saving the configuration in a
non-volatile memory.
CAPTION




NULL - Has no standard value
Na - Non-dimensional parameter
E - Parameter list.
ms - Milisecond
IX
FI302 - Operation and Maintenance Instruction Manual
X
Installation Flowchart
Installation Flowsheet
Start
Was the converter
configured on the bench
to match the application?
Yes
Install the converter on the field
following the instructions below.
Install the converter preferably
on wether-protected areas.
No
Configure the engineering unit.
Check the area classification
and its practices.
Configure the terminal(s)
and output scale(s) .
(Section 5 - Calibration)
Install the converter (mechanically
and electrically) according to the
application after checking the best
position for the LCD
(Section 6 - Maintenance).
Configure the LCD reading.
(Section 4 - Configuration)
Simulate the values in the Fieldbus
input according to output scale
and verify the signals of the
4 a 20 mA output current.
Yes
Is the indication correct?
Power-up the converter properly.
FI302 needs a external power supply
for supply the 4 - 20 mA equipment .
No
See section 6 - Maintenance
OK
XI
FI302 - Operation and Maintenance Instruction Manual
XII
Section 1
INSTALLATION
General
NOTE
The installation carried out in hazardous areas should follow the recommendations of the IEC60079-14 standard.
The FI302 is a high end device and thus, in order to take advantage to its maximum, the FI302
requires an appropriate installation.
Many factors may affect the converter accuracy, among which environment conditions are the most
difficult to control. In order to reduce the effects from temperature, humidity and vibration, avoid its
installation in aggressive areas.
The effects from temperature variation may be minimized by assembling the converter in areas
protected from weather changes. If necessary, use thermal insulation against external heat sources.
Humidity is harmful to the electric circuits. In areas with high relative humidity levels, the correct
placing of the housing cover o-ring must be assured and hand-tight shut to press the o-ring. The
housing cover should not be removed on the field so that its threads are not damaged, as they are
not protected by painting.
A flexible sealing material should be applied on the electric connections to avoid humidity. See
details on how to connect the FI302 to Fieldbus.
Mounting
The display may be rotated at 90º to 90º angles for easier visualization. See figure 6.2 on section 6
– Maintenance. To access the display, unlock the locking screw on the display cover by rotating it
clockwise. See figure 1.1 to locate the locking screw.
COVER
LOCKING
SCREW
HOUSING ROTATION
SET SCREW
Figure 1.1 - Display lid locking screw
The mounting bracket makes it easier to adjust the converter in several positions, as shown on
Figure 1.2 – Mounting Positions and Dimensional Drawing
1.1
FI302 - Operation and Maintenance Instruction Manual
ALLOW 150 MM MINIMUM FOR LOCAL
ZERO AND SPAN ADJUSTMENT WITH
MAGNETIC TOOL.
PLUG
CONDUIT
CONNECTION
COMMUNICATIONS
TERMINAL
PLUG
WALL OR
PANEL MOUNTING
MOUNTING BRACKET
PIPE 2"
FOR WALL MOUNTING
2 EXPANSION ANCHOR - S8
2 HEXAGON SCREW - 3/16”X70
FOR PANEL MOUNTING
2 BOLT AND NUTS - 1/4”X30
NOT INCLUDED
Figure 1.2 - Mounting Positions and Dimensional Drawing.
Electric Connection
Output Connection
To access the terminal block, loosen the cover locking screw to release it. Rotate the cover anticlockwise and remove it (See Figure 1.3).
COVER
LOCKING
SCREW
Figure 1.3 – Terminal Block Cover Locking Screw
The housing has two threaded openings where to insert the signal cables of the connection terminal
block. The threads allow connecting the wiring conduit or the cable gland.
For more convenience, there are three ground terminals: one internal and two externals close to the
terminal block.
Figure 1.4 shows the three terminals of the converter current output channels, which are marked
with numbers 1, 2 and 3. Terminal 4 is the power supply common ground to the loop controlled by
the channels. The converter H1 (IEC-61158-2) power supply must be connected to the terminals
marked by (+) and (-).
The current output is limited by the power supply voltage on the current loop and by the conditions
of the classified area. Refer to the load curve to determine the maximum equipment quantity allowed
for the bus.
If power fails, the outputs status will be uncertain and in case of communication loss, communication
1.2
Installation
lacks, the outputs will move to fixed pre-configured values or to safety default values.
BUS AND POWER
SUPPLY TERMINALS
GROUND CONNECTION
FOR SURGE PROTECTION
GROUND TERMINAL
(OPTIONAL SCREW)
-
+
1
2
3
GROUND TERMINAL
4
COMM.
+
COMMUNICATION
TERMINALS
-
LOCK
Figure 1.4 – Terminal Block
Connecting the FI302 to the FOUNDATION™ fieldbus
The FI302 may be connected to or removed from a fieldbus network in operation. Take due
precaution with this operation and prevent signal cables from touching the shielding, the ground
cables or one another. Insert the FI302 on the network with communication speed equal to its own
(31,25 kbps), FOUNDATION™ fieldbus protocol.
Preparing the FI302 before connecting it to network
The FI302 may be configured on-line or off-line by a fieldbus configuration like the Smar SYSCON
installed on a Engineering station, for instance.


Then, use the configuration device to attribute a tag to the converter, using the “Assign Tag”
option on the menu.
Download the configuration for the equipment or for the entire network.
NOTE
The Assign Tag may be applied on-line or off-line for specific equipment connected to a fieldbus network
with other equipments.
ATTENTION
To attribute a new Tag to the equipment, the system configuration must be changed. This may bring some
inconveniences on the control configuration. For example, the addressees configured on the previous
functional blocks and links are deactivated. Therefore, if the tags are modified, the entire configuration must
be revised and when applicable, the TAG list from OPC Servers shall be updated.
The FI302 is protected against reverse polarity and may support ±35 VDC without causing any
damage, but it will not work under these conditions. Although the FI302 cannot be affected by
polarity, try and keep the polarity in all connections.
In hazardous areas, the number of equipments is limited by the intrinsic safety restrictions. Consult
the documents related to the use of equipment for this area.
1.3
FI302 - Operation and Maintenance Instruction Manual
DCS/PLC
Interface
(LC700)
DC Power Supply
(see cargo line)
Terminator
Terminator
DC barrier
COMM
C1
C2
Output 2
Equipment with
4 – 20 mA Input
DC Power Supply
(see cargo line)
DC barrier
For C1 and C2
C1
C2
The components inside the gray area are normally
located in the control room
Output 1
Equipment with
4 – 20 mA Input
+
1
2
3
4
COMM.
-
+
HART I.S.
Communicator
FI302 Junction Box
Figure 1.5 – FI302 Output connections for Classified Areas.
The FI302 connection for non-classified areas must follow the diagram on figure 1.6. The three
available output channels may be used for that area.
Terminator
DC Power Supply
(PS302 ou DF50)
DCS/PLC
Interface
(LC700)
Terminator
Impedance
Conditioner
Barreira
(DF49,DC
DF53 or
PSI302P)
COMM
C1
C2
Output 2
Equipment with
4 – 20 mA Input
DC Power Supply
(see cargo line)
DC barrier
For C1 and C2
ou C3 e C4
The components inside the gray area are normally
located in the control room
C3
C4
Output 1
Equipment with
4 – 20 mA Input
+
1
2
3
4
COMM.
HART
Communicator
Figure 1.6 – FI302 Output Connections
1.4
+
-
FI302 Junction Box
Installation
Figure 1.7 shows a typical fieldbus network with equipments for different functions connected.
DCS/PLC
Terminator Interface
DC Power
Supply
(PS302 or Df50)
Terminator
Impedance
Conditioner
(DF 49, DF53
or PSI302P)
smar
DC302-10
STCOM
LOAD
FLASH
VEX A
INA 0
INA 1
INA 2
INA 3
INA 4
INA 5
INA 6
INA 7 VEX B
GND A INB 0
INB 1
INB 2
INB 3
INB 4
VEXA
VEXB
VEXOUT
INA INB OUT
0
0
0
1
1
1
2
3
2
3
2
3
4
4
4
5
5
5
6
6
6
7
7
7
INB 5 INB 7 VEXOUT OUT 1 OUT 3 OUT 5 OUT 7 +BUS
INB 6 GND B OUT 0 OUT 2 OUT 4 OUT 6 GNDOUT -BUS
FI302
DC302
LD302
TP302
LD292
FY302
Figure 1.7 – Typical Fieldbus Equipment Network
Power Consumption
The FI302 converter must be properly powered as follows:
* Minimum 9 V voltage;
* 12 mA Operating Current (lq)
The power supply must provid the minimum voltage wherever theFI302 is located in the H1
segment. An independent power supply shall be used to power the 4 – 20 mA equipments
connected to the converter output.
Low current consumption equipments should be used for intrinsically safety applications. Choose
low resistance cables to reduce drop in voltage on the junction box and on each equipment.
Terminator
The terminators are impedances with the same values as the specific bus impedance to avoid signal
reflection and, consequently their distortion or loss. Each bus segment must have only two
terminators positioned on its ends. Some equipments, especially for power source, output/input,
fieldbus test or PC simulation card, etc, include the option for an internal terminator connection.
Before connecting a terminator to the bus, check if the equipment already has an internal terminator
on one end, and install the other terminator.
Each terminator has a 100 Ohm impedance and the equivalent impedance of both will be 50 Ohm.
The terminator causes a 250- to-500 mV amplitude tension drop on the bus.
Smar has the terminator model BT302.
Cabling
The FOUNDATION™ fieldbus protocol works with several types of cable and the best they are, the
longer the lengths and the greater the number of equipments to be connected to it. Table 1.1 shows
the regular cable types used when installing FOUNDATION™ fieldbus equipments and their
characteristics.
Pair
Single
Shielding
Yes
Twisted
Yes
Size
Maximum Length
Type
0,75 mm²
1900 m
A
Multicables
yes
yes
0,32 mm²
1200 m
B
Multicables
no
yes
0,13 mm²
400 m
C
Multicables
yes
no
1,25 mm²
200 m
D
Table 1.1 – Types of Cables.
1.5
FI302 - Operation and Maintenance Instruction Manual
NOTE
The length of non-twisted cables decreases regardless of their diameter and shielding (see D type data). It
is recommended not to use these cables, but if you do, do not leave them too close to power cables or noisy
equipments.
The Fieldbus Foundation recommends the “A” type cable. Table 1.2 shows its main characteristics
for a bus project.
“A” TYPE CABLE
Characteristic impedance on the 31,25 kHz frequency
Maximum attenuation on the 39 kHz frequency
Maximum capacitance outbalance for shielding
Maximum DC resistance per conductor lenght
Maximum propagation delay change
Conductor transversal area
100 Ohm  20%
3 dB/km
2 nF/km
22 Ohm/km
1,7 us/km
0,75 mm2
Table 1.2 – “A Type” Cable Characteristics
Total Cable Length
The cable(s) total length vary (ries) according to its/their quality. The total length is the sum of the
trunk and the spur lengths. For instance, use the diagram on figure 1.8 and the table 1.3 to
determine the total length of a hypothetical bus.
Trunk
Terminator A
Terminator B
Spur 2
Spur 3
Spur 1
FY302
LD292
FI302
Figure 1.8 – Total Cable Length
Segment A, B
Trunk
Length
Spur 1
120 m
Spur 2
40 m
240 m
Spur 3
80 m
Total
480 m
Table 1.3 – Examples of Total Cable Lengths
The cable types should combine according to the equation below:
L1 / L1max + L2 / L2max + … < 1
Example: the network has the following cables:
L1: is the type 1 cable length
L2: is the type 2 cable length
L1max: is the type 1 maximum cable length (see table 1.1).
L2max: is the type 2 maximum cable length (see table 1.1).
1.6
Installation
L1 = 1000 m of A type cable
L2 = 100 m of B type cable
1000 / 1900 + 100 / 1200 = 0,61
The hypothetical combination on last example satisfies the above equation: 0,61 < 1
Cable shielding
Shielding must be used, especially at noisy sites with high EMI/RFI near to the bus. Connect the
spur shielding with the trunk shielding. The shielding should cover a minimum 90% cable length to
guarantee good protection.
Grounding
The shielding is grounded only at the power supply negative terminal. Do not ground it at the other
terminal, in order to avoid a secondary current circulation that could induce noise onto the bus. If the
cable is not shielded install it on a tray and ground it only at one end. Do not use shielding as power
conductor. Signal cables should NOT be grounded.
Commissioning
This item will explain the commissioning related to the configuration of the converter in the network.
Before receiving or installing the converter and after the plant’s detailing project conclusion, it is
suggested to initiate the offline configuration. Once accompli shed those steps proceed with the
device configuration download.
In FOUNDATION™ fieldbus the database configuration is made on user-defined tags with no
association with the physical devices. Therefore, the devices must be associated to their respective
configurations.
Each device has a unique Device ID with 32 characters as hardware address, and meant to
distinguish a device from another. This address is engraved on the circuit board by the manufacturer
and cannot be changed. A field device is associated to its configuring system when correlates its
configuration tag to the device ID. If the factory tag is identical to the configured tag on the
configuring systems they will be automatically associated by the configurator system. Once it is
connected to the network, the factory tag may be named, if not done yet.
When all the devices are associated to their respective tags, the configuration may be completely or
partially unloaded on the network equipments.
If possible, use the configuring system to simulate the control and the operation. Then, you may
start, stop and go through the control strategies and check if the plant is operating normally before
the start-up.
Commissioning stages



Connect the electrically converter to the segment, so that the fieldbus will recognize it as an
equipment with a non-commissioned tag;
Use the configuration software to instantiate the newly-connected equipment. This creates ties
between the physical equipment in the plant and the database configuration;
Upload the equipment internal data on the configuration system and its strategy control on the
equipment.
NOTE
The Fieldbus requires that the measuring unit be the same, both on the equipment transducer block and the
function blocks, in order to avoid commissioning error.
Use of non-preconfigured to devices
Devices with non-configured tags are configured during commissioning. To do it, follow the
procedure:




Connect each adequate equipment to a fieldbus segment. The system will recognize them as
non-commissioned equipments;
Instantiate each equipment on the adequate segment in the configuration software;
Name a TAG to the specific device according to the plant process flowchart (P&ID);
Download the configuration to the equipment.
1.7
FI302 - Operation and Maintenance Instruction Manual
Use of preconfigured equipments
The devices with preconfigured tags identify themselves automatically with the configuration and
save commissioning time. The user must simply install them and check when they appear on the
system configurator screen.
Each preconfigured device must be installed on the specific plant site where it was configured for.
Linking Device
The linking device, for instance, the Smar DFI302 or other interface, addresses all the devices on
each network automatically. For practical purpose, the node address may be hidden, once it is not
of interest to most users, whose interaction is based on tags. However, the node address is typically
shown on the live list for the use of specialists. As a result, the Foundation Fieldbus devices may be
commissioned directly from the control room. Once the device is connected to the network it will be
detected in seconds. The devices may be connected or disconnected at any time without disturbing
the network.
Error monitoring and detection with Live List
If the device does not appear on the configuration system live list, it most probably was connected to
the wrong network or was not commissioned. In this case, it may be located in the live list of the
others networks. Another possibility is that the device cable is not connected or the device is not
operating properly. The live list, thus, is an excellent commissioning tool, as it facilitates checking
the cable connection to the field devices. To make sure that a device was not mistaken for another
on the same network or that it was installed at the wrong place, the device may be disconnected
temporarily from the network, so that the user check if the right tag disappears from the live list.
For more safety, use the configuration system to obtain detailed ID information from any device
connected to the network. This information helps checking the tag, the description, the
manufacturer, the type, the version and instrument general condition in order to confirm if it is the
right device and if it is working properly.
Installation in Hazardous Areas
WARNING
Explosions could result in death or serious injury, besides financial damage. Installation of this
converter in explosive areas must be carried out in accordance with the local standards and the
protection type adopted .Before continuing the installation make sure the certificate parameters are
In accordance with the classified area where the equipment will be installed.
The instrument modification or parts replacement supplied by other than authorized representative
of Smar is prohibited and will void the certification.
The converters are marked with options of the protection type. The certification is valid only when
the protection type is indicated by the user. Once a particular type of protection is selected, any
other type of protection can not be used.
The electronic housing and the sensor installed in hazardous areas must have a minimum of 6 fully
engaged threads. Lock the housing using the locking screw (Figure 1.3).
The cover must be tighten with at least 8 turns to avoid the penetration of humidity or corrosive
gases. The cover must be tighten until it touches the housing. Then, tighten more 1/3 turn (120) to
guarantee the sealing. Lock the covers using the locking screw (Figure 1.3).
Consult the Appendix A for further information about certification.
1.8
Installation
Explosion/Flame Proof
WARNING
In Explosion-Proof installations the cable entries must be connected or closed using metal cable
gland and metal blanking plug, both with at least IP66 and Ex-d certification.
The standard plugs provided by Smar are certified according to CEPEL certificate. If the plug
needs to be replaced, a certified plug must be used.
The electrical connection with NPT thread must use waterproofing sealant. A non-hardening
silicone sealant is recommended.
For NEMKO ATEX certificate please to follow the installation guidelines in hazardous locations
below: Group II Category 2G, Ex d, Group IIC, Temperature Class T6, EPL Gb U = 28VDC
Ambient Temperature: -20 to 60ºC for T6
Environmental Protection: IP66/687 or IP66W/687W
The electrical connection available are ½ - 14NPT and M20x1,5.
Cable entries must be connected or closed using metal cable gland and metal blanking plug,
both with at least IP66 and Ex-d certification or any appropriate ATEX approved metal cable
gland and metal blanking plug. Do not remove the transmitter covers when power is ON.
Intrinsically Safe
WARNING
In hazardous zones with intrinsically safe or non-incendive requirements, the circuit entity
parameters and applicable installation procedures must be observed.
To protect the application the transmitter must be connected to a barrier. Match the parameters
between barrier and the equipment (Consider the cable parameters). Associated apparatus
ground bus shall be insulated from panels and mounting enclosures. Shield is optional. If used, be
sure to insulate the end not grounded. Cable capacitance and inductance plus Ci and Li must be
smaller than Co and Lo of the associated Apparatus.
It is not recommended to remove the transmitter cover when the power is ON.
1.9
FI302 - Operation and Maintenance Instruction Manual
1.10
Section 2
FUNCTIONAL DESCRIPTION
Functional Description
See Figure 2.1.
MAIN CIRCUIT BOARD
OUTPUT CIRCUIT BOARD
POWER
ISOLATION
SUPLLY
FIRMWARE
DOWNLOAD
INTERFACE
LOCAL ADJUST
CORRENT CONTROL
1
EPROM
FLASH
POWER
SUPLLY
CPU
. EEPROM
RAM
SIGNAL
SHAPING
. RAM
SIGNAL ISOLATION
D/A
CONTROLER
COMUNICATION
2
D/A
3
D/A
4
DISPLAY BOARD
DISPLAY
CONTROLLER
Figure 2.1 – FI302 Block Diagram
D/A
Receives signal from the CPU and converts it to an analog signal to be used by the current control
Current Control
Controls the channel current according to the data received from the CPU.
Signal Isolator
Isolates the data signal between the output and the CPU.
Central Processing Unit (CPU), RAM and FLASH
The CPU is the converter intelligent part, and is responsible for the management and operation of
the blocks, auto-diagnosis and communication. The program is stored in FLASH memory. For the
temporary storing of data there is a RAM. The RAM data will be lost if energy fails, although the
device has a non-volatile EEPROM where the valid data are stored, as for calibration, configuration
and identification.
Communication Controller
It controls the line activity, modulates and demodulates communication signals and inserts or delete
initial and final delimiters.
Power Supply
Uses energy from the control loop to power the converter circuit.
Power Insulation
The power must be insulated as the output signals sent or received by the output
2.1
FI302 - Operation and Maintenance Instruction Manual
Signal Conditioner
Prepares the signals from the network or from the communication controller at acceptable levels by
the communication controller or the fieldbus network, respectively.
Display Controller
Receives CPU data and controls the Liquid Crystal Display.
Local Adjustment
The power must be insulated once signals are sent and received by the output.
2.2
Section 3
OPERATION
Liquid Crystal Display
The liquid crystal display shows up to three variables that may be selected by the user. When two or
three variables are chosen, the display will alternate the sampling from both with an interval of
approximately 3 seconds.
The LCD is made of a field with 4½ numerical digits, a field with 5 alphanumeric digits and an
information field, as shown on Figure 3.1.
INDICATES THAT THE
COMMUNICATION IS
ACTIVE
INDICATES THAT THE OPERATION
IS LOCALLY ADJUSTED
MD
F (t)
5
INDICATES THAT THE EEPROM
IS ACTIVE AND THE OPERATION
IS SAVED
INDICATES THE POSSIBILITY
FOR VARIABLE/MODE
ADJUSTMENT/CHANGE
VARIABLE FIELD
MNEMONIC FIELD
Figure 3.1 - Display
Monitoring
During normal operation, the FI302 is in monitoring mode and the indication alternates between the
variables, as configured by the user. See Figure 3.2. The display shows the engineering units,
values and parameters simultaneously with the majority of status indicators, depending on the local
adjustment configuration.
Figure 3.2 – Typical Monitoring Mode displaying the current inferior value, namely 4.0 mA.
3.1
FI302 - Operation and Maintenance Instruction Manual
The monitoring mode is interrupted when the user makes the local adjustment. The display also
shows messages and errors (See Table 3.1).
DISPLAY
DESCRIPTION
Init , FI302 & Version
The FI302 is powered and initiated
Blk OOS
OOS block not configured and link ineffective
bad
Communication or signal failure or bad signal
Table 3.1 – Display Messages and Errors.
3.2
Section 4
CONFIGURATION
The FI302 may be configured by any Foundation Fieldbus configuration tool or by an operational
console.
The FI302 has three output transducer blocks, one resource block, one display block, one
diagnostic block and other instant able function blocks.
This manual deals with the parameters of transducer blocks, display block and diagnostic block. The
function blocks are described in the specific function block manual.
Transducer Block
The transducer block insulates the hardware input/output function block like sensors and actuators.
The transducer blocks controls the input and output access through the specific manufacturer
implementation.
Usually, transducer block execute linearization function, characterization.
The connection between the transducer block and function blocks is called channel.
How to Configure a Transducer Block
When instantiating the FI302 on the configuration tool, the transducer block is automatically
instantiated.
The Transducer block has an algorithm, an internal parameter group and a channel that connects it
to the analog output function block.
The algorithm describes how the transducer transfers information from the hardware input/output to
other function blocks. The internal parameters, which cannot be linked to other blocks and published
on the link via communication, define the user interface for the transducer block. They are divided in
Standards that comply with the Foundation Fieldbus standard and those specified by manufacturers
and made according to their needs.
Every standard routine (e.g. calibration) follows a step by step method, which defines generally the
rules that will help the user.
The transducer, display and diagnostic blocks have several parameters that could be configured.
Here will treat of the most usual. The others are similar.
NOTE
The parameters ending with an “n” mean that they are the same for the other groups, and are distinguished by
their group number instead of the letter “n”.
For the FI302 basic configuration, use the Transducer and Display blocks parameters.
The Transducer Block parameters are configured as follows:
MODE_BLOCK
The MODE-BLOCK parameter configures the transducer block mode of operation. There are two
options: Out of Service or AUTO (automatic).
TERMINAL_NUMBER
The TERMINAL_NUMBER parameter relates a value for the channel. It starts with 1 to the
transducer number 1 and goes up to 3 to the transducer number 3. The FI302 has 3 current
channels and the current value will be sent internally to a specific transducer output from the analog
output function block. The number of the analog output block (AO) is related to the transducer
terminal number (TERMINAL_NUMBER). The channels with numbers 1, 2, 3 correspond to the
terminal block numbers 1, 2, 3. Select the combinations (1 - 1), (2 - 2), (3 - 3) for the channel and
the terminal block number where the output will occur (channel number – terminal block number).
The TERMINAL_NUMBER parameter chooses which of the three terminals of the terminal block will
supply the output. At least one of them must be chosen or otherwise the FI302 will issue the error
message “Blk_error”.
4.1
FI302 - Operation and Maintenance Instruction Manual
Display Block
The FI302 display block shows the variable chosen on monitoring mode or the option menu on the
local adjustment mode.
The display block is default-configured to make it possible to adjust the Upper Trim (UPPER) and
the Lower Trim (LOWER), to monitor the input transducer output and check the Tag.
The options of the FI302 local adjustment tree may be entirely configured by any fieldbus
configuration tool. Use them for the configuration, but for certain operations the local adjustment is
easier and faster, because it does not depend on network and communication connections. The
parameter options to work with the local adjustment are: Mode Block, Output Monitoring, Tag
Visualization and Tuning Parameter Adjustments.
Before using the magnetic tool for local adjustment, use the fieldbus configuration tool to prepare
the parameters that enable this operation.
How to Configure a Display Block
There are seven parameter groups indexed to the Block_Tag_Param_n parameter that may be
preconfigured by the user to enable a configuration by local adjustment. If it is not necessary to
display this group of tag-indexed parameters, write an invalid tag for the Block_Tag_Param_n
parameter. With this procedure the equipment does not recognize it as a valid parameter nor the
parameters indexed to it.
The Display Block parameters are configured as follows:
MODE_BLOCK
The configuration is identical to the previous transducer block.
BLOCK_TAG_PARAM_n
The is the block tag where the parameter belongs. The FI302 enables inserting up to 7 block tags.
Use a maximum of 32 characters.
INDEX_RELATIVE_n
This is the index related to the parameter that will be activated or visualized (0, 1, 2…6). See the
Function Block manual to know the required indices, or visualize them on the configuration tool by
opening the desired block. The FI302 accepts up to 7 parameter indices, configuring up to 7
parameter in the LCD.
DISPLAY_REFRESH
This parameter updates the new configuration.
4.2
Section 5
CALIBRATION
If necessary, it is possible to adjust the FI302 output channel current. The trim adjustment is used if
the indication on the transducer block output is different from the reference standard adopted.
Possible causes are:


The user Amperemeter is different from the plant standard.
The converter had its default characterization altered by overload or by the time of use.
To analyze the transducer output calibration, measure the channel output current with an accurate
Amperemeter and compare it with the indication on the FI302. Adjust the trim in case of difference.
The trim may be adjusted in two levels:
Lower Trim: At the range lower level.
Upper Trim: At the range upper level.
These points define the linear output characteristics. The trim adjustments are independent.
The Transducer Block parameters used for the FI302 calibration or current Trim are:
CAL_POINT_HI, CAL_POINT_LO, FEEDBACK_CAL e CAL_CONTROL.
Parameter description:
CAL_POINT_HI
This parameter configures the calibration range upper value.
CAL_POINT_LO
This parameter configures the calibration range lower value.
FEEDBACK_CAL
This is the current measured value used by the calibration method. It is used to apply the current
trim. To apply the lower or upper values, write the value read by the amperemeter in the parameter
during the calibration of the values. Repeat this operation until the measure is the same as the value
read. See figure 5.1.
CAL_CONTROL
It enables and disables the calibration process with options Enable and Disable. After initiating the
calibration method, the CAL_CONTROL parameter is used to return to the previous normal
operation.
The calibration will be enabled if the AO block output has a valid value and the status is different
from “Bad”. If “Bad” appears, the message “Calibration Failed” will appear on the XD_ERROR
parameter.
Figure 5.1 shows how to connect the converter to calibrate its lower value on 4 mA and its upper
value on 20mA.
5.1
FI302 - Operation and Maintenance Instruction Manual
FI302
-
+
1
2
3
4
COMM.
+
-
LOCK
Power
Power
Supply
Supply
Ampere Meter
Amperimeter
P
30 mA
I
Figure 5.1 – Current Measuring Connection Diagram
There are two ways to apply the trim: use a magnetic tool for one of them and a fieldbus
configuration tool, like the Smar Syscon for the other.
It is possible to calibrate the conveter by means of parameters CAL_POINT_LO and CAL-POINTHI.
Let’s take the lower value as an example: write 4 mA or the lower value in parameter
CAL_POINT_LO.
This parameter
indicates where the
converter should be
when the setpoint
lower value is 0%.
The desired value
should be
entered.
Figure 5.2 - Calibrating the CAL_POINT_LO – FI302
5.2
Calibração
Always keep in mind that, simply by writing in this parameter, the trim procedure is initialized.
Read the current in the multimeter and write that value in parameter FEEDBACK_CAL. Write in this
parameter until it reads 4.0 mA or the lower value readout of the multimeter.
This parameter
should be set with the
actual output current
during the calibration
procedure.
The value should
be entered here.
Figure 5.3 - Feedback of Current Lo Value
In order to end the trim procedure, choice DISABLE in the parameter CAL_CONTROL.
This parameter ends
the calibration
procedure.
The enable option
indicates that the
calibration process is
being done. In order to
finalize its procedure,
the user should set it to
disable.
Figure 5.4 - Closing the Calibration Lo Procedure
Let’s take the upper value as an example:
Write 20 mA in parameter CAL_POINT_HI. Always keep in mind that, simply by writing in this
parameter, the trim procedure is initialized.
5.3
FI302 - Operation and Maintenance Instruction Manual
This parameter
indicates where the
converter should be
when the setpoint is
100%.
The desired value
should be entered.
Figure 5.5 - Calibrating the Cal Point Hi – FI302
Read the current in the multimeter and write that value in parameter FEEDBACK_CAL. Write in this
parameter until it reads 20.00 mA or the upper value readout of the multimeter.
This parameter
should be set with
the actual output
current during the
calibration
procedure.
The value
should be
entered here.
Figure 5.6 - Feedback of CAL_POINT_HI – FI302
In order to end the trim procedure, choice DISABLE in the parameter CAL_CONTROL.
5.4
Calibração
This parameter
ends the
calibration
procedure.
The enable option
indicates that the
calibration process is
being done. In order
to finalize its
procedure, the user
should set it to
disable.
Figure 5.7 - Closing the Calibration High Procedure
The calibration will be enabled only if the output of AO block has a valid value and status different of
"Bad" In this case, the following message can be seen in the parameter XD_ERROR.
This parameter
indicates de Error
Code Operation
associated to
calibration procedure.
It indicates that the
calibration
procedure was not
sucessfull.
Figure 5.8- Calibration Error Message – FI302
5.5
FI302 - Operation and Maintenance Instruction Manual
5.6
Section 6
MAINTENANCE
NOTE
Equipment installed in hazardous atmospheres must be inspected in compliance with the IEC60079-17
standard.
Diagnostic Block – DIAG
This transducer block provides the following characteristics:





Online measuring time for the functional blocks execution;
Hardware revision
Firmware revision
Equipment serial number
Main board serial number
The BEHAVIOR parameter defines the initial parameter values that will be used after block
instantiation. The Adapted option selects a group of initial values more proper for the parameters,
thus avoiding invalid values. The Spec option also allows defining initial values.
Troubleshooting
Physical Inspection
After connecting the FI302 to the network, if it loses communication or slows down. e.g., due to
multiple tentative communication, the error may be caused by poor installation procedure, by the
configuration or by poor equipment performance.
Causes for communication errors

Badly fit connections

Installation problems, repeated equipment addresses, bad configuration, etc.

Terminator located at the wrong place, with or without terminator

Power supply with too low or unstable voltage value

Too long or too many Spurs

Wrong ground or no ground

Water infiltration in the equipment due to connections with wrong sealing and/or loose clamps

Low isolation
After carrying out the procedures for detecting network defects, act as follows:





Insulate the segment or equipment that causes the problem
Check if the polarity is correct
Check is the address is correct
Check the the Network integrity
Check if the tension on the converter terminals is at least 9.5 V during communication
Remove the equipment to a bench and test it. If it presents malfunctioning, contact Smar.
Parameters used for Troubleshooting
The FI302Transducer Block parameters used for troubleshooting are:
BLOCK_ERR, XD_ERROR, FINAL_VALUE, RETURN e BACKUP_RESTORE
Caution messages may appear on the status of the Return parameter or Block Error parameter, in
given circumstances such as presented below, in two modes, OOS and AUTO.
BLOCK_ERR
This transducer BLOCK_ERR parameter shows the following errors:

Block Configuration – When XD_SCALE has an improper range or unit;
6.1
FI302 - Operation and Maintenance Instruction Manual

Output Failures – When the loop current open;

Out of Service – When the block is on out of service mode (OOS)
Limit Conditions for Calibration
Lower
3.99 < NEW_LOWER < 11.5 mA, otherwise XD_ERROR = 22
Upper
12.5 < NEW_UPPER < 20.01 mA, otherwise XD_ERROR = 22
FINAL_VALUE
The desired current value and the status written by the AO block;
RETURN
Current output value coming from the AO block;
RETURN STATUS
The transducer block Return Status indicates the following errors:
 Bad::NonSpecific:NotLimited – When the loop current is interrupted (open loop);
 XD_ERROR – This parameter is used to indicate the calibration status;
BACKUP_RESTORE
This parameter is used as backup or to recover configuration data.
Table 6.1 has the information to determine the converter or network failures.
NOTE
It is recommended not to repair printed circuit boards. Keep spare parts or buy them from Smar, if necessary.
Symptom
PROBABLE SOURCE OF ERROR
Diagnostic
Converter Fieldbus Connections
Check power supply polarity and continuity
No turn on
Power Supply
Check power supply output. The voltage at the FI302 terminal block must be between 9 and 32 Vdc
Electronic circuit failure
Check circuit boards for defects and replace them for spare ones.
Network Connection
Check equipment, power supply and terminator connections.
Network equipment impedance
Check power supply and terminator impedance.
No communication
Converter configuration
Check the converter communication parameters setting
Network Configuration
Check the network communications settings
Electronic Circuit Failure
Replace the main board and the input board matched pairs.
Output Terminal Connection
Check power supply, channels, terminal box polarity and continuity
Incorrect Outputs
(the
power
supply
indicated aside is for 4-20
mA equipments)
Power Supply
Check power supply output. The FI 302 output voltage must be between 3 and 45 Vdc.
Load Resistance
Must be between 0 and 2000 Ohm. The higher value depends on the output power supply voltage.
Calibration
Check the converter calibration
Table 6.1 – Failure Diagnostic.
6.2
Maintenance
If the failure is not on table 6.1 use the Factory Init. The note below shows how to do it.
NOTE
Use factory init as the last option to recover control over the device when it presents problems related to
function blocks or the communication. Only authorized personnel should do it and the converter must
be offline. This procedure will enable the standard configuration values of the plant and disable the
previous equipment configuration.
To access the letters S and Z use two magnetic screwdrivers and loosen the screw that holds the
identification plate.
Proceed as follows:
1) Turn off the equipment and insert the magnetic screw drive handles in the openings S and Z and leave
them there;
2) Power the equipment;
When the display shows factory init, remove them and wait for the “S” symbol on the right upper corner
to unlit, indicating the end of the operation.
After running the factory init, download partially the configuration, which characterizes the equipment
functional behavior on the fieldbus.
Disassemble Procedure
See Figure 6.1 for guidance on this procedure. Turn off the power supply before disassembling the
converter.
Exploded View
12
11
10
9
8
7
15
6
5
14
4
2
16
3
13
1
Figure 6.1 – FI302 Exploded View
6.3
FI302 - Operation and Maintenance Instruction Manual
Electronic Circuit
The main board (5) and output board (7) are matched pairs and must be replaced together should it
be needed.
Tighten the locking screw cap (8) located on the opposite side of the enclosure housing marked by
"Field Terminals" and unscrew the cap (1) to access the display and circuit boards. To remove the
motherboard (5) and the display, release the two screws (3) that hold them. Disconnect the display
of the motherboard (5) and that the board's output signal. To remove the entry (7), loosen the
screws (6) that hold the housing (9).
CAUTION
The boards have CMOS components that may be damaged by electrostatic discharges. Follow the right
procedure for handling the CMOS components. Store the circuit boards in electrostatic-proof packaging.
Assembly Procedure
See Figure 6.1 for guidance on this procedure.





Insert the output signal board (7) into the housing (9) and fasten it with its screws.
Insert the main board (5) in the housing, making sure that all the pins are connected.
The display may be mounted in any of the 4 possible positions (see Figure 6.2). The “▲” sign
indicates the display upper position.
Hold firmly the main board and the display with their screws (3).
Fit the cover (1) according to the area classification and lock it with the locking screw (8).
Figure 6.2 – Four Possible Indicator Positions
Interchangeability
The output and the main boards are matched pairs, once the calibration data for the output board is
stored in the EEPROM of the main board. If for any reason, boards must be mixed to form a
functional pair, a new calibration procedure must be done in order to guarantee the outputs
accuracy.
6.4
Maintenance
Spares
SPARES
ORDER CODE
SD1
FDI302
DESCRIPTION
Magnetic Screwdriver for local adjustment
Field device interface
Spare Part List
SPARE PART LIST
DESCRIPTION OF PARTS
Cover Without Window (Included O-ring)
Cover With Window (Included O-ring)
Sealing ring (Note 2)
Aluminum Housing Main Board Screw
316 Stainless Steel Housing Main Board Screw
Aluminum
316 Stainless Steel
Aluminum
316 Stainless Steel
Cover, Buna-N
Units with indicator
Units without indicator
Units with indicator
Units without indicator
Digital Indicator
Main and Output Board
Output Board Screw
Aluminum Housing
316 Stainless Steel Housing
Cover Locking Screw
Housing, Aluminum (Note 1)
Housing, 316 Stainless Steel (Note 1)
1/2 - 14 NPT
M20 x 1.5
PG 13.5 DIN
½ - 14 NPT
M20 x 1.5
PG 13.5 DIN
Local Adjustment Protection Cap
Identification Plate Screw
Terminal Block Insulator
External Ground Screw
Terminal Block Insulator Screw
Six-Sided Plug 1/2" NPT Internal BR Ex
Six-Sided Plug 1/2" NPT Internal
Six-Sided Plug M20 X 1.5 External BR Ex d
Six-Sided Plug PG13.5 External BR Ex d
Mounting Bracket for 2” Pipe (Note 3)
1.
2.
3.
4.
Aluminum Housing
316 Stainless Steel Housing
Bichromated Carbon Steel
Bichromated 304 Stainless Steel
Bichromated Carbon Steel
Bichromated 304 Stainless Steel
316 Stainless Steel
316 Stainless Steel
Carbon Steel
316 Stainless Steel
Carbon Steel Bolts, Nuts, Washers
and U-clamp in Stainless Steel
POSITION
CODE
1 e 15
1 e 15
1
1
2
3
3
3
3
4
5e7
6
6
8
9
9
9
9
9
9
10
11
12
13
14
14
16
16
16
16
16
16
-
204-0102
204-0105
204-0103
204-0106
204-0122
304-0118
304-0117
204-0118
204-0117
214-0108
324-0140
314-0125
214-0125
204-0120
324-0130
324-0131
324-0132
324-0133
324-0134
324-0135
204-0114
204-0116
314-0123
204-0124
304-0119
204-0119
400-0808
400-0809
400-0583-11
400-0583-12
400-0810
400-0811
214-0801
214-0802
-
214-0803
CATEGORY
(NOTE 4)
B
A
NOTE
Includes terminal insulator, bolts (cover lock, grounding and terminal insulator), and I.D. plate without certification.
Sealing orings are packed in dozens.
Includes U-clamp, nuts, bolts and washers. Spare part list.
For category “A” it is recommended to keep in stock 1 set for each 25 installed pairs, and for category “B”, 1 set/50 pairs.
6.5
Section 7
ADVANCED CONFIGURATION
The transducer block allows some configurations through the parameters below that alter the
current output curve.
Parameter description
CHARACTERIZATION_TYPE
Indicates the characterization curve type;
CURVE_BYPASS
Enables and disables the characterization curve;
CURVE_LENGHT
Indicates the number of points the characterization curve;
CURVE_X
Characterization curve input points;
CURVE_Y
Characterization curve output points;
Characterization Curve
The transducer block also has a characterization curve, used to give a determined profile to the
output. This is useful, for example, when the FI302 controls a valve with a non-linear feature. The
characterization curve is applied to the input signal before being converted and sent to the analog
output by the transducer.
The CURVE_BYPASS parameter determines if the curve will be used or not. If the parameter is a
true Bypass, the curve is not used and the input value is transmitted directly to the output current
conversion routine.
"True" means that the
Characterization
Curve will be
bypassed.
This value "False"
enables the
Characterization Curve.
Figure 7.1 - Enabling the Characterization Curve
The characterization curve has 8 points. Each point has two coordinates (X and Y). These two
coordinates define the point location in the X – Y space, and the connection of adjacent points with
a linear segment forms the characterization curve. Extreme points are extrapolated.
7.1
FI302 - Operation and Maintenance Instruction Manual
This parameter
determines the
number of points valid
and configured.
The maximum number of
points is 8.
Figure 7.2 - Setting the Characterization Curve Length
These points are numbered from 1 to 8 and are contained in the CURVE_X (abscissas) and
CURVE_Y (ordinates) parameters. CURVE_X parameter requires points in crescent order, meaning
that the subsequent points must be greater than the preceding ones, or the parameter will not be
accepted. CURVE_Y parameter does not require this, and a non-monotonic curve is allowed.
NOTE
When writing on CURVE parameters remember to place the point coordinates in the correct order.
This parameter
defines the
coordinates X
The values should be
configured in crescent
order.
Figure 7.3 - Configuring the Characterization Curve X points
7.2
Configuração Avançada
This parameter
defines the
coordinates Y
It is not necessary to
follow any order. A
monotone curve is
allowed.
FI2EM312
CDR
Figure 7.4 - Configuring the Characterization Curve - Y points
The Display Block allows configure up to three variables her they be shown in the digital indicator,
or a tree with parameters that can be altered via local adjustment. This configuration is possible
through procedures below:
NOTE
The parameters with “n” at its end mean that they are the same for other groups and are differentiated by their
group number instead of the letter.
The Display Block parameters are:
SUB_INDEX_n, MNEMONIC_n, INC_DEC_n, DECIMAL_POINT_NUMBER_n e ACCESS_n
SUB_INDEX_n
To visualize a tag choose the relative index equal to zero and the sub index equal to 1
MNEMONIC_n
This mnemonic identifies the parameter (16 characters maximum). Preferably, choose the
mnemonic with up to 5 characters because it will be not necessary to rotate it on the display.
INC_DEC_n
It is the increase and the decrease in decimal units when the parameter is Float, Float Status, or
Integer when the parameter is expressed in total units;
DECIMAL_POINT_NUMBER_n
Number of digits after the decimal point (0 to 3 decimal digits);
ACCESS_n
On Monitoring, the parameter enables only this option and on Action the function shows on the
display the increment and decrement values.
Definition of Parameters and Values
Block_Tag_Param
This is tag of the block to which the parameter belongs. Use up to a maximum of 32 characters.
Index_Relative
This is the index related to the parameter to be actuated or viewed (0, 1, 2…). Refer to the Function
Blocks Manual to know the desired indexes, or visualize them on the SYSCON by opening the
desired block.
In case you wish to visualize a certain tag, opt for the index relative equal to zero, and for the subindex equal to one (refer to paragraph Structure Block in the Function Blocks Manual).
Sub_Index
7.3
FI302 - Operation and Maintenance Instruction Manual
This is the mnemonic for the parameter identification (it accepts a maximum of 16 characters in the
alphanumeric field of the display). Choose the mnemonic, preferably with no more than 5 characters
because, this way, it will not be necessary to rotate it on the display.
Inc_Dec
It is the increment and decrement in decimal units when the parameter is Float or Float Status time,
or integer, when the parameter is in whole units.
Decimal_Point_Numb.
This is the number of digits after the decimal point (0 to 3 decimal digits).
Access
The access allows the user to read, in the case of the “Monitoring” option, and to write when "action"
option is selected, then the display will show the increment and decrement arrows.
Alpha_Num
These parameters include two options: value and mnemonic. In option value, it is possible to display
data both in the alphanumeric and in the numeric fields; this way, in the case of a data higher than
10000, it will be shown in the alphanumeric field.
In option mnemonic, the display may show the data in the numeric field and the mnemonic in the
alphanumeric field.
In case you wish to visualize a certain tag, opt for the index relative equal to zero, and for the subindex equal to one (refer to paragraph Structure Block in the Function Blocks Manual).
Figure 7.5- Parameters for Local Adjustment Configuration
7.4
Configuração Avançada
Figure 7.6 - Parameters for Local Adjustment Configuration
Figure 7.7 - Parameters for Local Adjustment Configuration
7.5
FI302 - Operation and Maintenance Instruction Manual
Figure 7.8 - Parameters for Local Adjustment Configuration
This parameter updates the
local adjustment programming
tree configured on each
device.
The option "update" should be
selected in order to execute the
upgrade of local adjustment
programming tree.
After its step all the parameters
selected will be show on the LCD
display.
Figure 7.9 - Parameters for Local Adjustment Configuration
7.6
Section 8
LOCAL ADJUSTMENT
When using the local adjustment for calibration, configure the display block to show the following
parameters: CAL_POINT_HI (UPPER mnemonic), CAL_POINT_LO (LOWER mnemonic) and TAG
(TAG mnemonic).
The FI302 has three output transducers, although only the number 1 leaves Smar with factory
configuration. To configure the other transducers to work with local adjustment use the configuration
tool.
NOTE
The Trim mode is removed from local adjustment automatically if the magnetic tool is not used during
approximately 16 seconds.
Under its identification plate, the FI302 has two openings marked with S and Z at their side, giving
access to two Reed Switch magnetic tools. They are activated when the magnetic tool is inserted in
the orifices by its handle (See Figure 8.1).
The magnetic tool permits adjusting most block parameters.
Figure 8.1 – Local Adjustment Orifices.
Jumper Configuration
J1 and W1 Jumpers located on top of the main board must be coupled with the main board and the
converter must have a display to show the local adjustment options.
Table 8.1 shows the possible actions applied on openings S and Z when the local adjustment is
enabled.
OPENING
ACTION
S
Selects the function shown on the display
Z
Initializes the local adjustment and moves through the available options.
Table 8.1 – Function of the Openings on the Housing
J1 Jumper Connection
If J1 (see figure 8.2) is connected to the ON pins, it will be possible to simulate values and status
using the SIMULATE parameter on the functional blocks.
8.1
FI302 - Operation and Maintenance Instruction Manual
W1 Jumper Connection
If W1 (see figure 8.2) is connected to ON, the display may perform configurations through local
adjustment.
OFF
ON
OFF
ON
LOC
ADJ
WR
J1
W1
MAIN BOARD
Figure. 8.2 – J1 and W1 Jumpers
To calibrate the upper and lower current values by local adjustment follow the step-by-step example
below:
In order to initialize the local
adjustment, insert the
Insert it again in orifice S
and wait for 5 secs.
magnetic screwdriver. Insert
it in orifice Z and wait for the
letters MD to appear.
Figure 8.3 – FI302 Step 1
8.2
Local Adjustment
Remove it from opening S
Insert it again on
opening S. The
abbreviations LOC
ADJ will be displayed
Figure 8.4 – FI302 Step 2
The first option on the tree is
LOWER, with an arrow pointing
upwards. An arrow pointing
upwards () increments the
value and an arrow pointing
downwards () decrements the
value. This parameter is used to
calibrate the lower current
value. In order to adjust the
lower current value insert the
tool in orifice S. Leave it there
until the display shows 4,00 mA.
If the values are different, move
to FEED parameter and insert
the mili-amperimeter current
value to correct it.
Insert the magnetic tool in the
orifice Z. If it is the first option to
be configured, the option TAG
and its equivalent mnemonic will
be displayed. Otherwise, the last
option configured will be
displayed. By keeping the tool in
the opening, the local adjustment
menu will rotate through the
options on the local adjustment
tree.
Figure 8.5 – FI302 step 3
The UPPER option is used to
calibrate the upper current
value. Insert the magnetic tool
in the S and leave it there until
the display indicates 20,00
mA. Insert the miliamperimeter
in the output terminal of the
terminal block and measure
the current. If the values are
different, move to the FEED
parameter and insert the
current value read on the
meter to correct it.
In order to decrement the
lower value, insert the
magnetic tool in the orifice
Z to shift the arrow to the
downward position. Insert
the tool in opening S and
wait for the lower value to
decrement to 4,99 mA.
Insert the miliamperimeter
in the terminal block
output and measure the
current. If the values are
different, move to the
FEED parameter and
insert the miliamperimeter
current value to correct it.
Figure 8.6 – F302 Step 4
8.3
FI302 - Operation and Maintenance Instruction Manual
In order to decrement the
upper value, insert the
magnetic tool in the Z to
shift the arrow to the
downward position. Insert
the tool in the S and wait
for the lower value to
decrease to 20,00 mA.
Insert the miliamperimeter
in the output terminal of
theterminal block and
measure the current. If the
values are different, go to
the FEED parameter and
insert the miliamperimeter
current value to correct it.
The FEED option allows the
user to correct the current
shown on the display, when
the current is different from
the standard value
measured at the output. To
implement the correction,
read the current shown on
the meter and apply this
value. This option makes it
possible to correct the
calibration points on both
Upper and Lower currents.
An arrow pointing upwards
() increments the current.
Figure 8.7 – FI302 Step 5
Insert the magnetic tool in
the S to shift the arrow
downwards and decrement
the calibration current
according to the measured
value. An arrow pointing
downwards ()
willDecrement the current
value.
Figure 8.8 – FI302 Step 6
8.4
Section 9
TECHNICAL CHARACTERISTICS
Functional Specification
Output Signal
Three 4 - 20 mA current output, external supply, common ground.
Input Signal
FOUNDATION™ fieldbus, digital, voltage mode 31.25 Kbit/s with bus power.
Output Load Limitation
External 3 - 45 Vdc output supply.
Bus power 9 a 32 Vdc.
Quiescent current consumption 12 mA.
Non-intrinsic safety: 7.8 KHZ to 39 KHZ impedance must greater or equal to 3 K. With an
intrinsic safety, the output impedance should be greater or equal to 400 , on the assumption
that exists a power supply barrier of 7.8 KHz to 39KHz.
4½ digit LCD display.
Power Supply
Output Impedance
Display
Hazardous Area Certification
Explosion-proof and intrinsically safe (ATEX (NEMKO and DEKRA EXAM), FM, CEPEL, CSA
and NEPSI).
Designed to comply with European Regulations (ATEX 94/9/EC and LVD 2006/95/EC).
Temperature Limits
Operation:
-40
to
85 oC
(-40 to 185 °F);
Storage
Display:
-40
-10
to 120 oC
to 60 oC
(-40 to 250 °F);
( 14 to 140 °F)
Operation;
-40
to
85 oC
(-40 to 185 °F)
without damage.
Humidity Limits
0 a 100% RH.
Operation starting time
Approximately 10 seconds.
Update time
Approximately 0.2 seconds.
Performance Specification
Accuracy
0.1%.
Ambient Temperature Effect
For a 10º C variation: ± 0.05% .
Output Power Supply Effect
± 0.005% V.
Vibration Effect
Complies with SAMA PMC 31.1.
Electromagnetic interference Effect
Designed to comply with European Directive EMC 2004/108/EC.
Electrical connection
1/2 -14 NPT, PG 13.5 or M20 x 1.5.
Injected low copper aluminum and finishing with polyester painting or 316 stainless steel, with
Buna N O-rings on cover.
With an optional bracket, may be installed on a 2” pipe or on a wall or panel.
Without display and mounting brackets: 0.80 Kg.
Add 0.13 Kg for digital display.
Add 0.60 Kg for mounting bracket.
Physical Specification
Material of Construction
Mounting
Weight
9.1
FI302 - Operation and Maintenance Instruction Manual
Ordering Code
MODEL
FI302
TRIPLE CHANNEL FOUNDATION FIELDBUS TO CURRENT CONVERTER
COD. Local Indicator
0
1
Without Indicator
With Digital Indicator
COD. Mounting Bracket
0
Without Bracket
1
Carbon Steel. Accessories: Carbon Steel
2
316 Stainless Steel. Accessories: AI316
7
Carbon Steel. Accessories: AI316
COD. Electrical Connections
0
1/2 - 14 NPT
1
1/2"- 14 NPT X 3/4 NPT (AI316) - with adapter
2
1/2" - 14 NPT X 3/4 BSP ( AI316) - with adapter
3
1/2" - 14 NPT X 1/2 BSP (AI316) - with adapter
A
M20 X 1.5
B
PG 13.5 DIN
SPECIAL OPTIONS
COD. Housing
H0
Aluminum (IP/TYPE)
H1
316 Stainless Steel (IP/TYPE)
H2
Aluminum for saline atmosphere (IPW/TYPE X)
H3
316 Stainless Steel for saline atmosphere (IPW/TYPE X)
COD. Identification Plate
I1
FM: XP, IS, NI, DI
I3
CSA: XP, IS, NI, DI
I4
EXAM (DMT): Ex-ia; NEMKO: Ex-d
I5
CEPEL: Ex-d, Ex-ia
I6
Without Certification
IE
NEPSI: Ex-ia
COD. Painting
P0
Gray Munsell N 6,5 Polyester
P3
Black Polyester
P4
White Epoxi
P5
Yellow Polyester
P8
Without Painting
P9
Safety Blue Epoxy - Electrostatic Painting
PC
Safety Blue Polyester - Electrostatic Painting
PG
Safety Orange Epoxi Paint - Electrostatic Painting
COD. Output Signal
T0
3 output - 4 to 20 mA
COD. Tag Plate
J0
With tag
J1
Blank
J2
According to user’s notes
COD. Special
ZZ
FI302
1
1
0
* Leave it blank if not applicable
9.2
*
*
*
*
*
*
See Notes
TYPICAL MODEL
Appendix A
CERTIFICATIONS INFORMATION
Manufacturing Location Approved
Smar Equipamentos Industriais Ltda – Sertãozinho, São Paulo, Brasil.
European Directive Information
Consult www.smar.com for the EC declarations of conformity for all applicable European directives and certificates.
ATEX Directive 94/9/EC - “Electrical equipment and protective system intended for use in potential explosive
atmospheres”
The EC-Type Examination Certificate had been released by Nemko AS (CE0470) and/or DEKRA EXAM GmbH (CE0158),
according to European Standards.
The certification body for Production Quality Assurance Notification (QAN) and IECEx Quality Assessment Report (QAR) is Nemko
AS (CE0470).
LVD Directive 2006/95/EC - “Electrical Equipment designed for use within certain voltage limits”
According the LVD directive Annex II, electrical equipment for use in an explosive atmosphere is outside the scope of this directive.
According to IEC standard: IEC 61010-1:2010 - Safety requirements for electrical equipment for measurement, control, and
laboratory use - Part 1: General requirements.
EMC Directive 2004/108/EC - “Electromagnetic Compatibility”
The equipment is in compliance with the directive and EMC test was performed according to IEC standards: IEC61326-1:2005 and
IEC61326-2-3:2006.
To comply with the EMC directive the installation must follow these special conditions:


Use shielded, twisted-pair cable for powering the instrument and signal wiring.
Keep the shield insulated at the instrument side, connecting the other one to the ground.
Hazardous Locations General Information
Padrões Ex:
IEC 60079-0 General Requirements
IEC 60079-1 Flameproof Enclosures “d”
IEC 60079-11 Intrinsic Safety “i”
IEC 60079-26 Equipment with equipment protection level (EPL) Ga
IEC 60079-27 Fieldbus intrinsically safe concept (FISCO)
IEC 60529 Classification of degrees of protection provided by enclosures (IP Code)
Customer responsibility:
IEC 60079-10 Classification of Hazardous Areas
IEC 60079-14 Electrical installation design, selection and erection
IEC 60079-17 Electrical Installations, Inspections and Maintenance
Warning:
Explosions could result in death or serious injury, besides financial damage.
Installation of this instrument in an explosive environment must be in accordance with the national standards and according to
the local environmental protection method. Before proceeding with the installation match the certificate parameters according to
the environmental classification.
General Notes:
Maintenance and Repair
The instrument modification or replaced parts supplied by any other supplier than authorized representative of Smar
Equipamentos Industriais Ltda is prohibited and will void the Certification.
A.1
FI302 – Operation and Maintenance Instruction Manual
Marking Label
Once a device labeled with multiple approval types is installed, do not reinstall it using any other approval types. Scratch off or
mark unused approval types on the approval label.
For Ex-i protection application
 Connect the instrument to a proper intrinsically safe barrier.
 Check the intrinsically safe parameters involving the barrier, equipment including the cable and connections.
 Associated apparatus ground bus shall be insulated from panels and mounting enclosures.
 When using shielded cable, isolate the not grounded cable end.
 Cable capacitance and inductance plus Ci and Li must be smaller than Co and Lo of the Associated Apparatus.
For Ex-d protection application
 Only use Explosion Proof/Flameproof certified Plugs, Adapters and Cable glands.
 As the instrument is non-ignition capable under normal conditions, the statement “Seal Not Required” could be applied for
Explosion Proof version regarding to electric conduits connection. (CSA Approved)
 In an Explosion-Proof/Flame-Proof installation, do not remove the instrument housing covers when powered on.
 Electrical Connection
 In Explosion-Proof installations the cable entries must be connected through conduit with sealed unit or closed using metal
cable gland or closed using metal blanking plug, all with at least IP66 and Ex-d certification. For enclosure with saline
environment protection (W) and ingress protection (IP) applications, all NPT thread parts must apply a proper water-proof
sealant (a non-hardening silicone group sealant is recommended).
For Ex-d and Ex-i protection application

The transmitter has a double protection. In this case the transmitter shall be fitted with appropriate certified cable entries
Ex-d and the electric circuit supplied by a certified diode safety barrier as specified for the protection Ex-ia.
Environmental Protection
 Enclosure Types (Type X): Supplementary letter X meaning special condition defined as default by Smar the following:
Saline Environment approved - salt spray exposed for 200 hours at 35ºC. (Ref: NEMA 250)
 Ingress protection (IP W): Supplementary letter W meaning special condition defined as default by Smar the following: Saline
Environment approved - salt spray exposed for 200 hours at 35ºC. (Ref: IEC60529)
 Ingress protection (IP x8): Second numeral meaning continuous immersion in water under special condition defined as
default by Smar the following: 1 Bar pressure during 24hours. (Ref: IEC60529)
Hazardous Locations Approvals
CSA (Canadian Standards Association)
Class 2258 02 – Process Control Equipment – For Hazardous Locations (CSA1002882)
Class I, Division 1, Groups B, C and D
Class II, Division 1, Groups E, F and G
Class III, Division 1
Class I, Division 2, Groups A, B, C and D
Class II, Division 2, Groups E, F and G
Class III
CLASS 2258 03 - PROCESS CONTROL EQUIPMENT – Intrinsically Safe and Non-Incendive Systems - For Hazardous
Locations (CSA 1002882)
Class I, Division 2, Groups A, B, C and D
Model FI302 Fieldbus Converter; supply 12-42V dc, 4-20mA; Enclosure Type 4/4X; non-incendive with Fieldbus / FNICO Entity
parameters
@ Terminals + and - :
Vmax =24V, Imax =570 mA, Pmax = 9.98 W, Ci = 5 nF, Li = 12uH;
@ Terminals 1 - 4:
Vmax =30V, Imax =110mA, Ci = 5 nF, Li = 12uH;
when connected through CSA Certified Safety Barriers as per SMAR Installation drawing 102A0559; Temp. Code T3C.
Class 2258 04 – Process Control Equipment – Intrinsically Safe Entity – For Hazardous Locations (CSA 1002882)
Class I, Division 1, Groups A, B, C and D
Class II, Division 1, Groups E, F and G
Class III, Division 1
FISCO Field Device
A.2
Certifications Information
Model FI302 Fieldbus Converter; supply 12-42V dc, 4-20mA; Enclosure Type 4/4X; Intrinsically safe with Fieldbus/FISCO Entity
parameters
@ Terminals + and -:
Vmax = 24 V, Imax = 380 mA, Pi = 5.32 W, Ci = 5 nF, Li = 12 uH;
@ Terminals 1 – 4:
Vmax = 30 V, Imax = 110 mA, Ci = 5nF, Li = 12 u H;
when connected through CSA Certified Safety Barriers as per Smar Installation Drawing: 102A0559; Code T3C.
Note: Only models with stainless steel external fittings are Certified as Type 4X.
Special conditions for safe use:
Temperature Class T3C
Maximum Ambient Temperature: 40ºC (-20 to 40 ºC)
FM Approvals (Factory Mutual)
Intrinsic Safety (FM 0D7A9.AX)
IS Class I, Division 1, Groups A, B, C and D
IS Class II, Division 1, Groups E, F and G
IS Class III, Division 1
Explosion Proof (FM 0D7A9.AX)
XP Class I, Division 1, Groups A, B, C and D
Dust Ignition Proof (FM 0D7A9.AX)
DIP Class II, Division 1, Groups E, F and G
DIP Class III, Division 1
Non Incendive (FM 0D7A9.AX)
NI Class I, Division 2, Groups A, B, C and D
Environmental Protection (FM 0D7A9.AX)
Option: Type 4X/6/6P or Type 4/6/6P
Special conditions for safe use:
Entity Parameters Fieldbus Power Supply Input (report 3015629):
Vmax = 24 Vdc, Imax = 250 mA, Pi = 1.2 W, Ci = 5 nF, Li = 12 uH
Vmax = 16 Vdc, Imax = 250 mA, Pi = 2 W, Ci = 5 nF, Li = 12 uH
4-20 mA Current Loop:
Vmax = 30 Vdc, Imax = 110 mA, Pi = 0,825 W, Ci = 5 nF, Li = 12 uH
Temperature Class T4
Maximum Ambient Temperature: 60ºC (-20 to 60 ºC)
NEMKO (Norges Elektriske MaterielKontroll)
Explosion Proof (Nemko 13 ATEX 1570)
Group II, Category 2 G, Ex d, Group IIC, Temperature Class T6, EPL Gb
Ambient Temperature: -20 to 60 ºC
Environmental Protection (Nemko 13 ATEX 1570)
Options: IP66W/68W
The Essential Health and Safety Requirements are assured by compliance with:
EN 60079-0:2012 General Requirements
EN 60079-1:2007 Flameproof Enclosures “d”
EXAM (BBG Prüf - und Zertifizier GmbH)
Intrinsic Safety (DMT 00 ATEX E 065) - In Progress
Group I, Category M2, Ex ia, Group I, EPL Mb
Group II, Category 2 G, Ex ia, Group IIC, Temperature Class T4/T5/T6, EPL Ga
FISCO Field Device
Supply circuit for the connection to an intrinsically safe fieldbus-circuit:
Ui = 24Vdc, Ii = 380 mA, Pi = 5.32 W, Ci ≤ 5 nF, Li = neg
Parameter of the supply circuit complies with FISCO model according to EN 60079-27: 2008.
A.3
FI302 – Operation and Maintenance Instruction Manual
Output-signal-circuits; three 4-20 mA current sinks with common ground for external intrinsically safe supply
Effective internal capacitance Ci negligible
Effective internal inductance Ci negligible
Safety-relevant maximum values for certified intrinsically safe 4-20 mA current loop circuits as a function of ambient temperature
and temperature class;
Max. Ambient
temperature Ta
Temperature
Class
Voltage DC
Ui
Current
Ii
Power
Pi
60ºC
T4
28 V
93 mA
750 mW
50ºC
T5
28 V
93 mA
750 mW
40ºC
T6
28 V
93 mA
570 mW
The signal outputs are safely galvanically separated from the fieldbus circuit.
Ambient Temperature: -40ºC ≤ Ta ≤ 60ºC
The Essential Health and Safety Requirements are assured by compliance with:
EN 60079-0:2009 General Requirements
EN 60079-11:2007 Intrinsic Safety “i”
EN 60079-26:2007 Equipment with equipment protection level (EPL) Ga
EN 60079-27:2008 Fieldbus intrinsically safe concept (FISCO)
CEPEL (Centro de Pesquisa de Energia Elétrica)
Intrinsic Safety (CEPEL 97.0019X)
Ex ia, Group IIC, Temperature Class T4/T5, EPL Ga
FISCO Field Device
Entity Parameters:
Pi = 5.32 W, Ui = 30V, Ii = 380 mA, Ci = 5.0 nF, Li = Neg
Ambient Temperature:
-20 to 65ºC for T4
-20 to 50ºC for T5
Explosion Proof (CEPEL 97.0091)
Ex d, Group IIC, Temperature Class T6, EPL Gb
Maximum Ambient Temperature: 40ºC (-20 to 40 ºC)
Environmental Protection (CEPEL 97.0019X and CEPEL 97.0091)
Options: IP66/68W or IP66/68
Special conditions for safe use:
The certificate number ends with the letter "X" to indicate that for the version of FIELDBUS to current Converter model FI302
equipped with housing made of aluminum alloy, only can be installed in "Zone 0" if is excluded the risk of occurs impact or friction
between the housing and iron/steel itens.
The Essential Health and Safety Requirements are assured by compliance with:
ABNT NBR IEC 60079-0:2008 General Requirements
ABNT NBR IEC 60079-1:2009 Flameproof Enclosures “d”
ABNT NBR IEC 60079-11:2009 Intrinsic Safety “i”
ABNT NBR IEC 60079-26:2008 Equipment with equipment protection level (EPL) Ga
IEC 60079-27:2008 Fieldbus intrinsically safe concept (FISCO)
ABNT NBR IEC 60529:2005 Classification of degrees of protection provided by enclosures (IP Code)
NEPSI (National Supervision and Inspection Center for Explosion Protection and Safety of Instrumentation)
Intrinsic Safety (NEPSI GYJ071324)
Ex ia, Group IIC, Temperature Class T4/T5/T6
Supply terminals entity parameters:
A.4
Certifications Information
Ui = 16 V, Ii = 250 mA, Pi = 2.0 W, Ci = 5 nF, Li = 0
Terminals 1-4:
Pi = 0.75 W, Ui = 28 V, Ii = 93 mA, Ci = 0 nF, Li = 0
Ambient Temperature:
T4 40 ºC for Pi = 2.0W, Pi = 750 mW
T4 60 ºC for Pi = 865 mW, Pi = 750 mW
T5 40 ºC for Pi = 990 mW, Pi = 750 mW
T6 40 ºC for Pi = 630 mW, Pi = 570 mW
Identification Plate and Control Drawing
CSA (Canadian Standards Association)
FM Approvals (Factory Mutual)
NEMKO (Norges Elektriske MaterielKontroll) / EXAM (BBG Prüf - und Zertifizier GmbH)
A.5
FI302 – Operation and Maintenance Instruction Manual
CEPEL (Centro de Pesquisa de Energia Elétrica)
NEPSI (National Supervision and Inspection Center for Explosion Protection and Safety of Instrumentation)
A.6
Certifications Information
Canadian Standards Association (CSA)
A.7
FI302 – Operation and Maintenance Instruction Manual
A.8
MARCIAL
MISSAWA
20 10 08 20 10 08
MARCIAL
MISSAWA
6
16 07 07 16 07 07
MOACIR
CASSIOLATO
5
07 05 03 07 05 03
MOACIR
CASSIOLATO
4
08 02 00 08 02 00
REV. DESIGN
APPROVED
7
ALT DE
0049/08
AREA
DRAWING
+
DESIGN
-
+
VERIFIED
MELONI M.MISSAWA SINASTRE
ALT DE
0004/07 28 03 95 28 03 95 28 03
95
ALT DE CUSTOMER:
0043/03
EQUIPMENT:
FI302/303
ALT DE
0015/00
CONTROL DRAWING
28
03
FIELDBUS
GROUND BUS
4 to 20mA
I.S.
BARRIER
FIELDBUS
I.S.
BARRIER
OPTIONAL
SHIELDING
APPROVAL CONTROLLED BY C.A.R.
APPROVED
PELUSO
95
:
DRAWING N.
Voc
Isc
Po
24V
250mA
1,2W
Voc
Isc
Po
CABLE INDUCTANCE +12uh
La
FIELDBUS
CABLE CAPACITANCE +5nF
Ca
GROUPS A,B,C,D,E,F & G
CLASS I,II,III DIV.1
16V
250mA
2W
4-20mA
Voc
30V
Isc
110mA
ENTITY PARAMETERS FOR ASSOCIATED APPARATUS
POWER SUPPLY
-
POWER SUPPLY
ASSOCIATED APPARATUS
EARTH IN EXCESS OF 250VAC OR 250VDC.
SOURCE OF POTENTIAL IN RELATION TO
NORMAL OR ABNORMAL CONDITIONS, A
BE SUPPLIED FROM, NOR CONTAIN UNDER
UNSPECIFIED, EXCEPT THAT IT MUST NOT
SAFE AREA APPARATUS
NON HAZARDOUS OR DIVISION 2 AREA
TRANSMITTER SPECIFICATION MUST BE IN ACCORDANCE TO
APPROVAL LISTING.
2-
WIRES: TWISTED PAIR, 22AWG OR LARGER.
SHIELD IS OPTIONAL IF USED, BE SURE TO INSULATE THE END NOT
GROUNDED.
56-
4-20mA
Ci=5nF Li=12uH
Vmax
30V
Imax
110mA
FIELDBUS
Ci=5nF Li=12uH
Vmax
24V
Imax
250mA
ENTITY VALUES:
CLASS I,II,III DIV.1, GROUPS A,B,C,D,E,F & G
MODELS FI302 AND FI303 - SERIES
FIELDBUS
APPROVAL.
PREVIOUS MANUFACTURER
BE SUBSTITUTED WITHOUT
COMPONENTS CAN NOT
CABLE CAPACITANCE AND INDUTANCE PLUS Ci AND Li MUST BE
SMALLER THAN Ca AND La OF THE ASSOCIATED APPARATUS.
ASSOCIATED APPARATUS GROUND BUS RESISTANCE TO EARTH MUST BE
SMALLER THAN 1(ONE) OHM, IF NOT ISOLATED.
4-
7-
ASSOCIATED APPARATUS GROUND BUS TO BE INSULATED FROM PANELS
AND MOUNTING ENCLOSURES.
3-
FM
INSTALLATION MUST BE IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE
(ANSI/NFPA 70) AND ANSI/ISA-RP12.6
HAZARDOUS AREA
1-
REQUIREMENTS:
Certifications Information
Factory Mutual (FM)
FM
APPROVED
smar
O.S.
102A0080
REV
SH.01/01
07
A.9
FI302 – Operation and Maintenance Instruction Manual
A.10
Appendix B
SRF – Service Request Form
Converter from Fieldbus to 4-20mA
GENERAL DATA
Model:
Serial Number:
TAG:
FI302 ( )
FI303 ( )
______________________________________________________________________________________________________
______________________________________________________________________________________________________
How many
channels are
used in IF?
1( )
Configuration:
Magnetic Tool ( )
2( )
PC ( )
3( )
Software: _____________
Version: ________________ Other: _____________________
INSTALLATION DATA
Type/Model/Manufacturer of device
connected to the channel 1:
Type/Model/Manufacturer of device
connected to the channel 2:
Type/Model/Manufacturer of device
connected to the channel 3:
_____________________________________________________________________________________
_____________________________________________________________________________________
_____________________________________________________________________________________
PROCESS DATA
Hazardous Area
Classification:
( ) Yes, please specify: ______________________________________________________________________________
( ) No
More details: _______________________________________________________________________________________
Types of Interference
Without interference ( )
presents in the area:
Ambient
Temperature:
Temperature ( )
Vibration ( )
Others: ____________________________________
From __________ºC up to __________ºC
OCCURRENCE DESCRIPTION
_____________________________________________________________________________________________________________________
_____________________________________________________________________________________________________________________
_____________________________________________________________________________________________________________________
SERVICE SUGGESTION
Adjustment ( )
Cleaning ( )
Preventive Maintenance ( )
Update / Up-grade ( )
Other: _______________________________________________________________________________________________________________
USER INFORMATION
Company: ___________________________________________________________________________________________________________
Contact: _____________________________________________________________________________________________________________
Title: ________________________________________________________________________________________________________________
Section: _____________________________________________________________________________________________________________
Phone: _________ _________________________
_________ _________________________
E-mail: ________________________________________________________________________
Extension: __________________________
Date: ______/ ______/ _________________
For warranty or non-warranty repair, please contact your representative.
Further information about address and contacts can be found on www.smar.com/contactus.asp.
B.1
FI302 – Operation, Maintenance and Instructions Manual
Returning Materials
Should it be necessary to return the converter to Smar, simply contact your local Smar office
informing the defective equipment serial number and dispatch it to our factory.
For easier analysis and faster solution of the problem, the returned material should include the
documentation with a description of the failure observed in the field and the circumstances that
caused it. Other information, such as the installation site, type of measure taken and the process
conditions are also important for a prompt evaluation.
B.2