Ammonia Vent Line Adaptor for Polytron 5200 SC05928

Transcription

Ammonia Vent Line Adaptor for Polytron 5200 SC05928
FIRE & GAS DETECTION SYSTEMS
CUSTOM PRODUCT
SC05928
Dräger 2” vent line adapter—LC
The Dräger 2” vent line adapter allows the Polytron 5200-LC
to be mounted directly to a 2 inch duct and provide the user
with low concentration (0-10% LEL) hydrocarbon gas monitoring. The vent line adapter allows easy calibration with a
standard stainless steel bulkhead fitting (supplied) without
having to remove the transmitter.
The adapter will further allow the use of Drager’s dual condulet system if remote mounting the sensor is needed. This
accessory was originally designed for the refrigeration industry, but can be adapted for many other uses.
Ordering Information
SC05928
2” Vent Line adapter—LC
ETA Process Instrumentation
119 Foster Street, Bldg #6
Peabody, MA 01960
Tel: (978) 532-1330
Fax: (978) 532-7325
w w w. e t a p i i . c o m
[email protected]
Installation Instructions
for 2” vent line adapter
SC05928
Tools needed:
2-4” pipe wrench / pliers
Electrical pliers / wire cutters
Small screwdriver
The instructions below are for the general installation of part number SC05928, 2” vent line adapter.
Variations within each application may occur. Please consult with the manufacture on other options if
needed. Pictures and drawings within this document are for reference only.
The 2” vent line adapter is designed to be placed into a “T” within the vent line system. This “T” should
be within 3-5 feet of the outlet. Please consult with local building codes to insure compliance. Please
NOTE: For best performance, the sensor should be mounted in a vertical position as shown within this
document.
2” adapter
Polytron 5200-LC
1
Once the Tee has been installed and secured, take the 2” adapter and screw the adapter onto the sensor
as shown below. If a “dual condulet” system is being used, then remote mount the sensor first into the
housing then follow the steps below. Please note the 35mm mounting hole on the adapter. The LC
sensor is designed to screw into this port.
Once the Transmitter or sensor is securly inserted into the adapter, you will now place the module into
the 2” NPT Tee on the vent line. Please note the location and position of the transmitter on the adapter.
This is necessary in order to screw the adapter into the vent line Tee. See illustrations below.
2
Once unit is mounted, remove the cover of the Polytron 5200-LC and perform the wiring of the
transmitter per the instructions in the manual. The calibration port located on the bottom of the
adapter should be kept clear and free of dirt and moisture. It is recommended to cap this port when not
in use (cap not supplied).
3