ERICO INTERCEPTOR SI25i, SI40i or SI60i Installation Instructions
Transcription
ERICO INTERCEPTOR SI25i, SI40i or SI60i Installation Instructions
INSTRUCTION SHEET ERICO INTERCEPTOR SI25i, SI40i or SI60i ® Installation Instructions for 5m Stainless Steel Guyed Mast - SIM Series Mast Detail (ERICO Part # TCEC253) Copper Tape (ERICO Part # PDCUC) Tape Fasteners SIM28A2 Bonding Clamp (ERICO Part # TMCSS) SIMBASE2840 Typical Conductor Connection Not to Scale 2 - Detail "B" BASEADAPTER40 Stainless Steel Mast (ERICO Part # SIM28A2) 4 HOLES, Guy Kit (ERICO Part # GUYKIT4M/GRIP) Do not over-tension guy wires (Slightly sagging) 0.43 [ 11mm] TMCSS Mast Clamp Installing contractor to field adjust and insure a secure bond on highest SIM series mast Stainless Steel Mast (ERICO Part # SIM33B3) Downconductor Stainless Steel Base Adapter (ERICO Part # BASEADAPTER40) Stainless Steel Mast Base (ERICO Part # SIMBASE2840) Refer to Detail "B" 7.87 [200mm] SIM33B3 6.77 [170mm] 1 - ERICO INTERCEPTOR SI (ERICO® Part # SI25i, SI40i or SI60i 1 - Not to Scale Preferred Angle 45° - 60° Detail "A" 2 Stainless Steel Cable Tie (ERICO Part # CABTIESS) Three every 3.3FT [1M] Lightning Event Counter (ERICO Part # LECIV) Downconductor Two downconductors are required For complete grounding system refer to Detail "A" ERICO® CADWELD® Connection or mechanical connection Lightning Event Counter Refer to installation manual for alternate locations (ERICO Part # LECIV) Ground Inspection Well Crow's Foot 2 Minimum 2/0 (50 mm ) Conductor (3 x 20 FT [6.1M] length) Enclosed in GEM material Suggested three radial grounding system for each downconductor: Minimum 5/8" x 8' [16mm x 2.4M] long ground rod in four locations The grounding system shown in the detail is a suggested layout. Each radial consists of a trench approximately 1.5FT [.45M] deep. The conductor is laid in the trench and is connected to ground rods. The conductor in each trench is encased in GEM material. Ground rods must extend 10FT [3M] below ground level. Note: This is one of several alternative installation methods. Refer to ERICO instruction print IP79157 for more details. ERICO is not responsible for field installation of lightning protection systems. The installation integrity of each system should be approved and stamped by a structural professional engineer. WARNING: 1. ERICO products shall be installed and used only as indicated in ERICO product instruction sheets and training materials. Instruction sheets are available at www.erico.com and from your ERICO customer service representative. 2. ERICO products must never be used for a purpose other than the purpose for which they were designed or in a manner that exceeds specified load ratings. 3. All instructions must be completely followed to ensure proper and safe installation and performance. 4. Improper installation, misuse, misapplication or other failure to completely follow ERICO's instructions and warnings may cause product malfunction, property damage, serious bodily injury and death. SAFETY INSTRUCTIONS: All governing codes and regulations and those required by the job site must be observed. Always use appropriate safety equipment such as eye protection, hard hat, and gloves as appropriate to the application. CADDY, CADWELD, CRITEC, ERICO, ERIFLEX, ERITECH, and LENTON are registered trademarks of ERICO International Corporation. TECHNICAL SUPPORT www.erico.com IP79137_A 1 OF 1 © 2014 ERICO International Corporation.