Hayward_FM EPM3-120 Version A 011409.indd
Transcription
Hayward_FM EPM3-120 Version A 011409.indd
Field Manual EPM3-120 On/Off/Jog Control ISO5211 F03/F05 8P14 Actuator Specifications Torque lb/Nm Supply Voltage Max Inrush Current Running Current Runtime (90O@60/50Hz) Weight Mechanical Connections Electrical Entry Electrical Terminations Environmental Rating Manual Override Control Case material Motor Protection 120vac Operation Ambient Temperature Operating Range EPM3-120 300”lbs / 35Nm 120vac 1.5A 0.5A 12sec / 13sec 5lbs / 2kg ISO5211 F03/F05 8pt14mm (2) 1/2” NPT 14 - 18 Ga. 4, 4X 8mm Wrench Drive On/Off/Jog Aluminum Alloy, Powder Coated Split Phase Capacitor 275OF/135OC Thermal H Class -22oF to +150oF -30oC to +65oC The following procedure is to be followed for set-up, calibration, testing and use of the EMP3-120 Series quarter-turn electric actuators. Each unit is shipped from the factory with initial calibration of mechanical stops, cams and switches completed. However, these are general settings and serve as a starting point for proper calibration of the actuator in its’ real-world application. There are no mechanical stops on this model. Hayward_FM EPM3-120 Version A 011409 1. The actuator is shipped from the factory in its fully CLOSED position. This can be verified by the observing the red/yellow top indicator. RED will be showing when fully closed. 2. Make the electrical connections as shown at right. For operation only four connections are needed. The balance of the connections are used for options and features. Terminals A,B & C are an aux switch for the closed position (adjustable), and terminals A,E & F are an aux switch for the open position (adjustable). Both Switches share a common terminal “A”. This actuator has been factory calibrated to operate between 00 and 900. Most quarter-turn products will not require recalibration of these settings. Page 1 of 4 EPM3-120 * CONNECTIONS OPTIONAL FIELD CONTROL DEVICE 120/230VAC LINE IN CLOSED* E NOT CLOSED* F NOT OPEN* C AUX SW COM* A OPEN* B RUN CLOSED 4 CLOSED PILOT* 6 RUN OPEN 3 OPEN PILOT* 5 NEUTRAL 1 HOT 7 GND SW4 AUXILIARY SWITCH (STANDARD) SW3 AUXILIARY SWITCH (STANDARD) SW2 SW1 HEATER M AC DRIVE MOTOR ALL SWITCHES SHOWN WITH ACTUATOR IN FULL OPEN POSITION GND Screw FIELD WIRING (BY OTHERS) THERMAL SWITCH INTERNAL WIRING (FACTORY) 1. The lower cam is the OPEN end-of-travel adjustment. Once the actuator is at its required OPEN position, with POWER OFF, use a 2.5mm hex key to free up the cam set screw. Once it is free, rotate the hex key to the LEFT a few degrees to reset the switch roller arm. Then snug the set screw up against the camshaft (CW) until slight pressure is felt. Then SLOWLY rotate the hex key pushing the cam to the RIGHT until you hear the “click” on the bottom switch indicating that correct adjustment has been achieved. Tighten the cam. 2. Apply power to the actuator and drive CLOSED at least 15-20 degrees. Then drive the actuator OPEN until the cam stops the electrical travel. Check to be sure this is the correct OPEN position you require. Repeat step 1 if further adjustment is needed. 4. The second cam is the CLOSED end of travel adjustment. Once the actuator is at its required CLOSED position with POWER OFF, use a 2.5mm hex key to free up the cam set screw. Once it is free, rotate the hex key to the RIGHT a few degrees to reset the switch roller arm. Then snug the set screw up against the camshaft (CW) until slight pressure is felt. Then SLOWLY rotate the hex key to the LEFT until you hear the “click” on the second switch indicating that correct adjustment has been achieved. Tighten the cam set screw. 5. Apply power to the actuator and drive OPEN at least 15-20 degrees. Then drive the actuator CLOSED until the cam stops the electrical travel. Check to be sure this is the correct CLOSED position you require. Repeat step 4 if further adjustment is needed. Remove power from the actuator. Page 2 of 4 EPM3-120 Hayward_FM EPM3-120 Version A 011409 3. Apply power to the actuator and drive the actuator fully CLOSED. 6. The THIRD cam is the OPEN auxiliary switch adjustment. Drive the actuator to its OPEN position. Then use a 2.5mm hex key to free up the cam set screw. Once it is free, rotate the hex key to the LEFT a few degrees to reset the switch roller arm. Then snug the set screw up against the camshaft (CW) until slight pressure is felt. Then SLOWLY rotate the hex key and cam to the RIGHT until you hear the “click” on the third switch. Continue to rotate the cam between 3 and 5 degrees to the RIGHT to make sure the auxiliary cam switch changes state before the actuator reaches its end of travel electrically. Tighten the cam set screw. 7. The FOURTH cam is the CLOSED auxiliary switch adjustment. Drive the actuator to its CLOSED position. Then use a 2.5mm hex key to free up the cam set screw. Once it is free, rotate the hex key to the RIGHT a few degrees to reset the switch roller arm. Then snug the set screw up against the camshaft (CW) until slight pressure is felt. Then SLOWLY rotate the hex key to the LEFT until you hear the “click” on the fourth switch. Continue to rotate the cam between 3 and 5 degrees to the LEFT to make sure the auxiliary cam switch changes state before the actuator reaches its end of travel electrically. Tighten the cam set screw. Hayward_FM EPM3-120 Version A 011409 8. Refer to the wiring diagrams and current draw tables on the back page of this document to make sure you have properly sized wire. NOTE, THIS ACTUATOR MUST HAVE THE EMT FITTINGS WATER TIGHT WITH CONDUIT DRAINAGE INSTALLED AND POWER SUPPLIED TO UNIT TO KEEP THE HEATER WARM AT THE TIME OF INSTALLATION . This unit should NOT be stored outside unless it is powered up. When this unit is NOT powered up, it should be stored in a clean, dry environment at all times. Page 3 of 4 EPM3-120 Application Notes: 1. These actuators are designed to be used in either a horizontal or upright position. Do NOT mount the actuator with the top below a horizontal position. 2. When installing conduit, use proper techniques for entry into the actuator. Use drip loops to prevent conduit condensate from entering the actuator. 3. Both NPT conduit ports MUST use proper equipment to protect the NEMA 4x integrity of the housing. 4. The internal heater is to be used in ALL applications. 5. Do NOT install the actuator outdoors or in humid environments unless it is powered up and the heater is functioning. 6. Use proper wire size to prevent actuator failure (see chart below for proper wire sizing). Easily distinguishable yellow/red position indicator EPM3 Series Dimensional Data Aluminum Casting 4X Protection Modular Control Cards Heavy Duty Drive Motor Easily accessible switch & cam stacks On/Off Control Proportional Control NEMA 4 Cover Seal Aluminum Casting 4X Protection (2) 1/2” EMT Ports EPM3-120 Exploded View (Typical) Switch sequencing data is provided in the table below to show the change-of-state points during the rotation of the actuator from OPEN to CLOSED and back again. Switches for terminals 3 thru 6 are set at the factory and should NOT be changed. The INCLUDED auxiliary switches SW3 & SW4 are for terminals A thru F and those set points may be modified if need be. Wire sizing data is provided in the table below to assist in the selection of the proper wire size for Hayward EPM3-120 series actuators using various wire sizes over distance. Please make sure to reference the correct voltage and do not exceed the indicated length of the wire run for each model. Wire Sizing Data Switch Logic Map and Switch/Cam Arrangement MAX distance between Actuator and Supply (feet) P1-12 3.0A P1-24 0.8A P1-120 1.5A P1-230 1.0A 18 16 14 28 43 70 207 325 524 551 866 1399 1584 2489 6150 TB1 Terminal ID# Wire Gage -5 o 0 o 5 o F E C B 6 4 5 3 Page 4 of 4 EPM3-120 o o 85 90 95 o } } } } AUX SW4 (Factory Set - Adj) AUX SW3 (Factory Set - Adj) SW2 CLOSE Stop (Factory Set - Fixed) SW1 OPEN Stop (Factory Set - Fixed) Hayward_FM EPM3-120 Version A 011409 F03/05 ISO Flange