Concrete Form Design - Home - KSU Faculty Member websites
Transcription
Concrete Form Design - Home - KSU Faculty Member websites
12 Concrete Form Design 12-1 DESIGN PRINCIPLES The design of concrete formwork that has adequate strength to resist failure and will not deflect excessively when the forms are filled is a problem in structural design. Unless commercial forms are used, this will usually involve the design of wall, column, or slab forms constructed of wood or plywood. In such cases, after the design loads have been established, each of the primary form components may be analyzed as a beam to determine the maximum bending and shear stresses and the maximum deflection that will occur. Vertical supports and lateral bracing are then analyzed for compression and tension loads. The procedures and applicable equations are presented in this chapter. 12-2 DESIGN LOADS Wall and Column Forms For vertical forms (wall and column forms), design load consists of the lateral pressure of the concrete against the forms. The maximum lateral pressure that concrete exerts against a form has been found to be a function of the type of concrete, temperature of the concrete, vertical rate of placing, and height of the form. For ordinary (150 lb/cu ft: 2403 kg/m3) internally vibrated concrete, the American Concrete Institute (ACI) recommends the use of the following formulas. to determine the maximum lateral concrete pressure. 335 336 Chapter · 12 For all columns and for walls with a vertical rate of placement of 7 ft/h (2.1 m/h) or less: p [P = 150 + 9000R T (12-lA) = 7.2 + 785R (12-lB) T + 18] where p = lateral pressure (lb/sq ft or kPa) R T h = rate of vertical placement = temperature (OF or °C) = height of form (ft or m) Maximum pressure (ft/h or m/h) = 3000 lb/sq ft (143.6 kPa) for columns, 2000 lb/sq ft (95.8 kPa) for walls, or 150 h (23.6h), whicheveris least. Minimum pressure = 600 lb/sq ft (28.7 kPa). · For walls with a vertical rate of placement of 7 to 10 ft/h (2.1 to 3.0 m/h): _ 150 43,400 2800R p+ T + T (12-2A) 1154 244R [ P = 7.2 + T + 18 + T + 18 ] (12-28) Maximum pressure = 2000 lb/sq ft (95.8 kPa) or 150 h, whichever is less. Minimum pressure = 600 lb/sq ft (28.7 kPa) · For walls with a vertical rate of placement greater than 10 ft/h (3.1 m/h): = 150 h [p = 23.6 h] pressure = 600 lb/sq ft p Minimum (l2-3A) (12-3B) (28.7 kPa) When forms are vibrated externally, it is recommended that a design load twice that given by Equations 12-1 and 12-2 be used. When a retarder, pozzolan, or superplasticizer has been added to the concrete, Equation 12-3 should be used. When concrete is pumped into vertical forms from the bottom (both column and wall forms), Equation 12-3 should be used and a minimum additional pressure of 25% should be added to allow for pump surge pressure. Floor and Roof Slab Forms The design load to be used for elevated slabs consists of the weight of concrete and reinforcing steel, the weight of the forms themselves, and any live loads (equipment, workers, material, etc.). For normal reinforced concrete, the design load for concrete and steel is based on a unit weight of 150 lb/cu ft 12-2 Design Loads (2403 kg/m3). The American Concrete Institute (AC!) recommends that a minimum live load of 50 lb/sq ft (2.4 kPa) be used for the weight of equipment, materials, and workers. When motorized concrete buggies are utilized, the live load should be increased to at least 75 lb/sq ft (3.6 kPa). Any unusual loads would be in addition to these values. ACI also recommends that a minimum design load (dead load plus live load) of 100 lb/sq ft (4.8 kPa) be used. This should be increased to 125lb/sq ft (6.0 kPa) when motorized buggies are used. Lateral Loads Formwork must be designed to resist lateral loads such as those imposed by wind, the movement of equipment on the forms, and the placing of concrete into the forms. Such forces are usually resisted by lateral bracing whose design is covered in Section 12-6. The minimum lateral design loads recommended for tied wall forms are given in Table 12-1. When form ties are not used, bracing must be designed to resist the internal concrete pressure as well as external loads. For slab forms, the minimum lateral design load is expressed as follows: H = 0.02 x dl x ws (12-4) where H = lateral force applied along the edge of the slab (lb/ft) [kN/m]; minimum value = 100 lb/ft [1.46 kN/m] dl = design dead load (lb/sqft) [kPa] ws = width of slab perpendicular to form edge (ft) [m] In using Equation 12-4, design dead load includes the weight of concrete plus formwork. In determining the value of ws, consider only that part of the slab being placed at one time. TABLE 12-1 Recommendedminimum lateral design load for wall forms Wall Height, h (ft) em] Design Lateral Force Applied at Top of Form (lb/ft) [kN/m] less than 8 [2.4] hxwf* 2 8 [2.4] or over but less than 22 [6.7] 100 [1.46] but hxwf* at least :- 22 [6.7] or over 7.5 h [0.358 h] but at least hxwf* :- *wf = wind force prescribed by local code (lb/sq it) [kPa] but minimum of 15lb/sq it [0.72 kPa] 337 338 Chapter 12-3 12 METHOD OF ANALYSIS Basis of Analysis After appropriate design loads have been selected, the sheathing, joists or studs, and stringers or wales are analyzed in turn, considering each member to be a uniformly loaded beam supported in one of three conditions (singlespan, two-span, or three-span or larger) and analyzed for bending, shear, and deflection. Vertical supports and lateral bracing must be checked for compression and tension stresses. Except for sheathing, bearing stresses must be checked at supports to ensure against crushing. Using the methods of engineering mechanics, the maximum values expressed in customary units of bending moment, shear, and deflection developed in a uniformly loaded, simply supported beam of uniform cross section are given in Table 12-2. The maximum fiber stresses (expressed in conventional units) developed in bending, shear, and compression resulting from a specified load may be determined from the following equations: Bending: M (12-5) fb=S Shear: fv = 1.~ V for rectangular wood members (12-6) fi I fv=~ Ib/Q or p ywood (12-7) Compression: p fc or fc.L (12-8) =A Tension: P ft=A (12-9) where fb = actual unit stress for extreme fiber in bending (psi) fc = actual unit stress in compression parallel to grain (psi) = actual unit stress in compression perpendicular ft = actual unit stress in tension (psi) fv = actual unit stress in horizontal shear (psi) A = section area (sq in.) M = maximum moment (in.-Ib) fc.L P = concentrated load (lb) S = section modulus (cu in.) to grain (psi) 12-3 TABLE 12-2 Maximum bending, shear, and deflection in a uniformly Support Type Conditions 2 Spans 3 Spans wZ2 96 M=- wZ2 wZ2 M= 120 V = 5wZ 96 wZ4 Ll= 2220EI V= wZ 20 wZ4 Ll = 1740EI M=- Shear (lb) V= wZ 24 5wZ4 Ll loaded beam 1 Span Bending moment (in.-Ib) Deflection (in.) Method of Analysis = 4608EI 96 Notation: l w E I = length of span (in.) = uniform load per foot of span = of inertia elasticity(in.<p,si) = modulus moment of ) Ob/ft) v =maximum Ib / Q = rolling shear (lb) shear constant (sq in./ft) Since the grain of a piece of timber runs parallel to its length, axial compressive forces result in unit compressive stresses parallel to the grain. Thus, a compression force in a formwork brace (Figure 12-4) will result in unit compressive stresses parallel to the grain (fe)in the member. Loads applied to the top or sides of a beam, such as a joist resting on a stringer (Figure 12-1b), will result in unit compressive stresses perpendicular to the grain (fc.l)in the beam. Equating allowable unit stresses in bending and shear to the maximum unit stresses developed in a beam subjected to a uniform load of w pounds per linear foot [kN/m] yields the bending and shear equations of Tables 12-3 and 12-3A. When design load and beam section properties have been specified, these equations may be solved directly for the maximum allowable span. Given a design load and span length, the equations may be solved for the required size of the member. Design properties for Plyform (plywood especially engineered for use in concrete formwork) are given in Table 12-4 and section properties for dimensioned lumber and timber are given in Table 12-5. The properties of plywood, lumber, and timber are described in Section 13-2. However, typical allowable stress values for lumber are given in Table 12-6. The allowable unit stress values in Table 12-6 (but not modulus of elasticity values) may be multiplied by a load duration factor of 1.25 (7-day load) when designing formwork for light construction and single use or very limited reuse of forms. However, allowable stresses for lumber sheathing (not Plyform) should be reduced by the factors given in Table 12-6 for wet conditions. The values for Plyform properties presented in Table 12-4 are based on wet strength and 7-day load duration, so no further adjustment in these values is required. 339 340 Chapter 12 TABLE 12-3 Concrete form design equations Support Conditions Design Condition Bending Wood 1 Span 2 Spans (F;b t2 1 = 4.0d(F;bt2 1= 4.46d (F;bt2 1= 9.8 (FSrl2 1= 9.8 (FSt2 1= 10.95(FSt2 1= 9.8 (Fb:;St2 1= 9.8 (Fb:;St2 1= 10.95(Fb:;St2 Wood 1= 16 FvA + 2d w 1= 12.8 FvA + 2d w 1= 13.3 FvA + 2d w Plywood 1= 24 F.Ib/Q + 2d w 1= 19.2 F.Ib/Q + 2d w 1= 20 F.Ib/Q + 2d w 1= 5.51 (E 1= 6.86 (E 1= 6.46 (E 1 = 4.0d Plywood Shear Deflection If~=h8o If ~ = Y240 If ~ = Y360 Compression Tension t4 t4 l = 1.72(t3 1= 2.31 (t3 l = 2.13 (t3 1= 1.57(t3 1= 2.10 (t3 1= 1.94(t3 1= 1.37(t3 P te or tel.= A P ft =-A 1=1.83(t3 1= 1.69(t3 Notation: = length of span, center to center of supports (in.) l Fb FbKS = allowable = plywood unit stress in bending (psi) section capacity in bending (lb x in./ft) Fe = allowable unit stress in compression parallel to grain (psi) FcJ. = allowable unit stress in compression perpendicular to grain (psi) F.Jb / Q = plywood section capacity in rolling shear (lb/ft) =allowable unit stress in horizontal shear (psi) Fv fc = actual unit stress in compression parallel to grain (psi) feJ. ft A E I P S ~ b d w 3 or More Spans = actual unit stress in compression perpendicular = actual unit stress in tension (psi) = area of section (in.2)* = modulus of elasticity = moment of inertia (in.(p,si) )* = applied force (compression or tension) (lb) = section modulus (in.3)* to grain =deflection (in.) = width of member =depth of member (in.) (in.) = uniform load per foot of span (lb/ft) *For a rectangular member: A = bd, S = bd2/6,I = bd3/12. (psi) t4 12-3 341 Method of Analysis TABLE 12-3A Metric (SI) concrete form design equations Support Design Conditions 1 Span Conditions 3 or More Spans 2 Spans Bending 112 1 = 36.5 d Fbb 1000 W Wood 112 1 = 36.5 d Fbb 1000 w 112 1 = 89.9 Fbb 1000 w ( ) ( ) 1 = 89.9 FbS 1000 W Plywood Shear ( ) ( ) 112 1 = 2.83(F~St2 1 = 2.83(F~St2 Wood 1 = 1.34 FvA Plywood 1 = 2.00 Fslb/Q + 2d 1000 w + 2d w 1 = 526 1000 If ~ = hao If ~ = Y240 If ~ = Y360 EI!::I. 1I4 (EIw ) 1 = 75.1 1000 (w ) EI = 1 1000 (w ) EI = 1 1000 (w ) p Deflection 1I3 1I3 59.8 Compression tc or tel. 1 = 1.11 FvA 2d 1000 w + 1= 1.60 Fslb/Q + 2d w EI~ 1I4 1 = 655 1000 w = 101 EI 1I3 1 1000 w = 91.7 EI 1I3 1 1000 w 1 = 1.67 Fslb/Q + 2d w EI~ 1I4 1 = 617 ( ) ( ) ( ) = 79.9 EI 1 1000 (w ) 1I3 68.5 1= 1.07 FvA + 2d 1000 w 1I3 =A P !e=-A Tension Notation: I Fb = length of span, center to center of supports (mm) = allowable unit stress in bending (kPa) FtJ{S = plywood section capacity in bending (Nmmlm) Fe = allowable unit stress in compression parallel to grain (kPa) FcJ. = allowable unit stress in compression perpendicular to grain FJb / Q = plywood section capacity in rolling shear (N/m) = allowable unit stress in horizontal shear (kPa) tv te tel. ft A E I EI P S li b = actual unit stress in compression parallel to grain = actual unit stress in compression perpendicular =actual unit stress in tension (kPa) = area of section (mm2)* = modulus of elasticity (kPa) = moment of inertia (mm4)* = plywood stiffness capacity (kPamm4/m) = applied force (compression or tension) (N) = section modulus (mm3)* = deflection (mm) = width of member (mm) d = depth of member (mm) w = uniform load per meter of span (kPalm) *For a rectangular member: A = bd, S = bd2/6,I (kPa) (kPa) to grain (kPa) = bd3/12 (EIw ) = 93.0 1 1000 (w ) = 84.7 EI 1 1000 (w ) = 73.8 EI 1 1000 (w ) 1000 1I3 1I3 1I3 TABLE 12-4 continued Face Grain Across EI Approx. Weight psf (kglm2) Thickness in. (mm) Plyform (12.5) Structural Face Grain Supports F F ,)b/Q EI Parallel to Supports F F ,Jb/Q 104 Ibin2 ft 103 Ibin ft 103 Ib ft 104 Ibin2 ft 103 Ibin ft 103 Ib ft 109 kPamm4 m 103 Nmm m 103 N m 109 kPamm4 m 103 Nmm m 103 N m 0.523 (194) 0.697 (258) 0.896 (332) 1.208 (448) 1.596 (592) 1.843 (683) 0.501 (7.31) 0.536 (7.83) 0.631 (9.21) 0.769 (11.22) 0.814 (11.88) 0.902 (13.16) 0.344 (127) 0.459 (170) 0.807 (299) 1.117 (414) 1.679 (622) 2.119 (785) 0.278 (4.06) 0.313 (4.57) 0.413 (6.02) 0.611 (8.92) 0.712 (10.39) 0.854 (12.47) I 1.5 (7.3) % (16) 1.8 (8.8) % (19) 2.2 (10.7) % (22) 2.6 (12.7) 1 (25.4) 3.0 (14.6) 1-% (28.5) 3.3 (16.1) 0.117 (1102) 0.196 (1850) 0.303 (2853) 0.475 (4477) 0.718 (6765) 0.934 (8798) 0.043 (410) 0.067 (636) 0.162 (1525) 0.268 (2528) 0.481 (4533) 0.711 (6694) *All properties adjusted to account for reduced effectiveness of plies with grain perpendicular to applied stress. Stresses adjusted for wet conditions, load duration, and experience factors. Based on APA data. ~ ~ ~ 344 Chapter TABLE 12-5 Section properties Nominal Size (b x d) in. 1x3 1x4 1x6 1x8 1 x 10 1 x 12 2x3 2x4 2x6 2x8 2 x 10 2 x 12 2 x 14 3x4 3x6 3x8 3 x 10 3 x 12 3 x 14 3 x 16 4x4 4x6 4x8 4 x 10 4 x 12 4 x 14 4 x 16 6x6 6x8 6 x 10 6 x 12 6 x 14 6 x 16 12 of U.S. standard Actual Size (S4S) in. 0.75 x 2.5 0.75 x 3.5 0.75 x 5.5 0.75 x 7.25 0.75 x 9.25 0.75 x 11.25 1.5 x 2.5 1.5 x 3.5 1.5 x 5.5 1.5 x 7.25 1.5 x 9.25 1.5 x 11.25 1.5 x 13.25 2.5 x 3.5 2.5 x 5.5 2.5 x 7.25 2.5 x 9.25 2.5 x 11.25 2.5 x 13.25 2.5 x 15.25 3.5 x 3.5 3.5 x 5.5 3.5 x 7.25 3.5 x 9.25 3.5 x 11.25 3.5 x 13.25 3.5 x 15.25 5.5 x 5.5 5.5 x 7.5 5.5 x 9.5 5.5 x 11.5 5.5 x 13.5 5.5 x 15.5 mm 19 x 64 19 x 89 19 x 140 19 x 184 19 x 235 19 x 286 38 x 64 38 x 89 38 x 140 38 x 184 38 x 235 38 x 286 38 x 337 64 x 89 64 x 140 64 x 184 64 x 235 64 x 286 64 x 337 64 x 387 89x89 89 x 140 89 x 184 89 x 235 89 x 286 89 x 337 89 x 387 140 x 140 140 x 191 140 x 241 140 x 292 140 x 343 140 x 394 lumber and timber Area of Section A in.2 103 mm2 1.875 2.625 4.125 5.438 6.938 8.438 3.750 5.250 8.250 10.88 13.88 16.88 19.88 8.750 13.75 18.12 23.12 28.12 33.12 38.12 12.25 19.25 25.38 32.38 39.38 46.38 53.38 30.25 41.25 52.25 63.25 74.25 85.25 1.210 1.694 2.661 3.508 4.476 5.444 2.419 3.387 5.323 7.016 8.952 10.89 12.82 5.645 8.871 11.69 14.91 18.14 21.37 24.60 7.903 12.42 16.37 20.89 25.40 29.92 34.43 19.52 26.61 33.71 40.81 47.90 55.00 (b = width, d = depth) Section Modulus S . 3 ID. 105 mm3 0.7812 1.531 3.781 6.570 10.70 15.82 1.563 3.063 7.563 13.14 21.39 31.64 43.89 5.104 12.60 21.90 35.65 52.73 73.15 96.90 7.146 17.65 30.66 49.91 73.83 102.4 135.7 27.73 51.56 82.73 121.2 167.1 220.2 0.1280 0.2509 0.6196 1.077 1.753 2.592 0.2561 0.5019 1.239 2.153 3.505 5.185 7.192 0.8364 2.065 3.589 5.842 8.642 11.99 15.88 1.171 2.892 5.024 8.179 12.10 16.78 22.23 4.543 8.450 13.56 19.87 27.38 36.09 Moment of Inertia I in." 106 mm" 0.9766 2.680 10.40 23.82 49.47 88.99 1.953 5.359 20.80 47.63 98.93 178.0 290.8 8.932 34.66 79.39 164.9 296.6 484.6 738.9 12.50 48.53 111.1 230.8 415.3 678.5 1034 76.25 193.4 393.0 697.1 1128 1707 0.4065 1.115 4.328 9.913 20.59 37.04 0.8129 2.231 8.656 19.83 41.18 74.08 121.0 3.718 14.43 33.04 68.63 123.5 201.7 307.5 5.205 20.20 46.26 96.08 172.8 282.4 430.6 19.52 80.48 163.6 290.1 469.4 710.4 It should be noted that the deflection of plywood sheathing is precisely computed as the sum of bending deflection and shear deflection. While the deflection equations of Tables 12-3 and 12-3A consider only bending deflection, the modulus of elasticity values of Table 12-4 include an allowance for shear deflection. Thus, the deflection computed using these tables is sufficiently accurate in most cases. However, for very short spans (lid ratio of less than 15) it is recommended that shear deflection be computed separately and added to bending deflection. See Reference 3 for a recommended procedure. 12-4 Slab Form Design 345 TABLE 12-5 continued Nominal Size (b xd) in. in. mm 6 x 18 6 x 20 6 x 22 6 x 24 8x8 8 x 10 8 x 12 8 x 14 8 x 16 8 x 18 8 x 20 8 x 22 8 x 24 lOx 10 10 x 12 10 x 14 10 x 16 10 x 18 10 x 20 10 x 22 lOx24 12 x 12 12 x 14 12 x 16 12 x 18 12 x 20 12 x 22 12 x 24 14 x 14 14 x 16 14 x 18 14 x 20 14 x 22 14 x 24 5.5 x 17.5 5.5 x 19.5 5.5 x 21.5 5.5 x 23.5 7.5 x 7.5 7.5 x 9.5 7.5 x 11.5 7.5 x 13.5 7.5 x 15.5 7.5 x 17.5 7.5 x 19.5 7.5 x 21.5 7.5 x 23.5 9.5 x 9.5 9.5 x 11.5 9.5 x 13.5 9.5 x 15.5 9.5 x 17.5 9.5 x 19.5 9.5 x 21.5 9.5 x 23.5 11.5 x 11.5 11.5x 13.5 11.5x 15.5 11.5 x 17.5 11.5x 19.5 11.5x 21.5 11.5x 23.5 13.5 x 13.5 13.5 x 15.5 13.5 x 17.5 13.5 x 19.5 13.5 x 21.5 13.5 x 23.5 140 x 445 140 x 495 140 x 546 140 x 597 191 x 191 191 x 241 191 x 292 191 x 343 191 x 394 191 x 445 191 x 495 191 x 546 191 x 597 241 x 241 241 x 292 241 x 343 241 x 394 241 x 445 241 x 495 241 x 546 241 x 597 292 x 292 292 x 343 292 x 394 292 x 445 292 x 495 292 x 546 292 x 597 343 x 343 343 x 394 343 x 445 343 x 495 343 x 546 343 x 597 12-4 Method Actual Size (S4S) Area of Section A in.2 103 mm2 96.25 107.2 118.2 129.2 56.25 71.25 86.25 101.2 116.2 131.2 146.2 161.2 176.2 90.25 109.2 128.2 147.2 166.2 185.2 204.2 223.2 132.2 155.2 178.2 201.2 224.2 247.2 270.2 182.2 209.2 236.2 263.2 290.2 317.2 62.10 69.19 76.29 83.39 36.29 45.97 55.65 65.32 75.00 84.68 94.36 104.0 113.7 58.23 70.48 82.74 95.00 107.3 119.5 131.8 144.0 85.32 100.2 115.0 129.8 144.7 159.5 174.4 117.5 135.0 152.4 169.8 187.3 204.7 Section Modulus S in.3 105 mm3 280.7 348.6 423.7 506.2 70.31 112.8 165.3 227.8 300.3 382.8 475.3 577.8 690.3 142.9 209.4 288.6 380.4 484.9 602.1 731.9 874.4 253.5 349.3 460.5 587.0 728.8 886.0 1058 410.1 540.6 689.1 855.6 1040 1243 46.00 57.12 69.44 82.96 11.52 18.49 27.09 37.33 49.21 62.73 77.89 94.69 113.1 23.42 34.31 47.29 62.34 79.46 98.66 119.9 143.3 41.54 57.24 75.46 96.19 119.4 145.2 173.4 67.20 88.58 112.9 140.2 170.4 203.6 Moment of Inertia I in.4 104 mm4 2456 3398 4555 5948 263.7 535.9 950.5 1538 2327 3350 4634 6211 8111 678.8 1204 1948 2948 4243 5870 7868 10274 1458 2358 3569 5136 7106 9524 12437 2768 4189 6029 8342 11181 14600 SLAB FORM DESIGN of Analysis The procedure for applying the equations of Table 12-3 and 12-3A to the design of a deck or slab form is first to consider a strip of sheathing of the specified thickness and 1 ft (or 1 m) wide (see Figure 12-1a). Determine in turn the maximum allowable span based on the allowable values of bending stress, shear stress, and deflection. The lower of these values will, of course, 1022 1415 1896 2476 109.8 223.0 395.7 640.1 968.8 1394 1929 2585 3376 282.5 501.2 810.7 1227 1766 2443 3275 4276 594.2 981.4 1485 2138 2958 3964 4276 1152 1744 2510 3472 4654 6077 346 Chapter 12 TABLE 12-6 Typical values of allowable stress for lumber Allowable Unit Stress (psi)[kPa] (Moisture Content = 19%) Species (No.2 Grade, 4 x 4 [100 x 100 mm] or smaller) Douglas fir-larch Hemlock-fir Southern pine California redwood Eastern spruce Reduction factor for wet conditions Load duration factor (7-day load) Fb Fv FcJ. Fe Ft 1450 [9998] 1150 185 [1276] 150 385 [2655] 245 1000 [6895] 800 850 [5861] 675 [7929] [1034] [1689] [5516] [4654] 1400 180 405 975 825 [9653] [1241] [2792] [6723] [5688] 1400 160 425 1000 800 [9653] [1103] [2930] [6895] [5516] 1050 140 255 700 625 [7240] [965] [1758] [4827] [4309] E 1.7 x 106 [11.7 x 106] 1.4 x 106 [9.7 x 106] 1.6 x 106 [11.0 x 106] 1.3 X 106 [9.0 x 106] 1.2 x 106 [8.3 x 106] 0.86 0.97 0.67 0.70 0.84 0.97 1.25 1.25 1.25 1.25 1.25 1.00 determine the maximum spacing of the supports (joists). For simplicity and economy of design, this maximum span vaJue is usuaJly rounded down to the next lower integer or modular vaJue when selecting joist spacing. Based on the selected joist spacing, the joist itself is analyzed to determine its maximum allowable span. The load conditions for the joist are illustrated in Figure 12-1b. The joist span selected will be the spacing of the stringers. Again, an integer or moduJar value is selected for stringer spacing. Based on the selected stringer spacing, the process is repeated to determine the maximum stringer span (distance between vertical supports or shores). Notice in the design of stringers that the joist loads are actually applied to the stringer as a series of concentrated loads at the points where the joists rest on the stringer. However, it is simpler and sufficiently accurate to treat the load on the stringer as a uniform load. The width of the uniform design load applied to the stringer is equal to the stringer spacing as shown in Figure 12-1c. The calcuJated stringer span must next be checked against the capacity of the shores used to support the stringers. The load on each shore is equaJ to the shore spacing muJtiplied by the load per unit length of stringer. Thus the maximum shore spacing (or stringer span) is limited to the lower of these two maximum values. Although the effect of intermediate form members was ignored in determining allowable stringer span, it is necessary to check for crushing at the point where each joist rests on the stringer. This is done by dividing the load at 12-4 Section I I w I--- Slab Form Design Elevation I I 1 tt --1 (1m) . Joists £1 w = design load (Ib/sq tt) [kN/m2] w1 = 1 x w = w (Ib/tt) [kN/m] a. Sheathing Joists Stringers S2 = spacing of joists (tt) [m] w2 = w X S2(Ib/tt) [kN/m] b. Joists Joist Stringer Shores S3 = spacing of stringers (tt) [m] w3 = w X S3 (Ib/ft) [kN/m] c. Stringers FIGURE 12-1 Design analysis of form members. this point by the bearing area and comparing the resulting stress to the allowable unit stress in compression perpendicular to the grain. A similar procedure is applied at the point where each stringer rests on a vertical support. To preclude buckling, the maximum allowable load on a rectangular wood column is a function of its unsupported length and least dimension (or 1/d ratio). The 1/d ratio must not exceed 50 for a simple solid wood column. For 1/d ratios less than 50, the following equation applies: F' C - 0.3 E - (l / d)2 c<: F "" (12-10) C 347 348 Chapter 12 where Fc = allowable unit stress in compression parallel to the grain (psi) [kPa] F~= allowable unit stress in compression parallel to the grain, adjusted for 1/d ratio (psi) [kPa] E = modulus of elasticity (psi) [kPa] 1/d = ratio of member length to least dimension In using this equation, note that the maximum value used for F~ may not exceed the value of Fc. These design procedures are illustrated in the following example. Sheathing design employing plywood is illustrated in Example 12-2. EXAMPLE 12-1 Design the formwork (Figure 12-2) for an elevated concrete floor slab 6 in. (152 mm) thick. Sheathing will be nominal I-in. (25-mm) lumber while 2 x 8 in. (50 x 200 mm) lumber will be used for joists. Stringers will be 4 x 8 in. (100 x 200 mm) lumber. Assume that all members are continuous over three or more spans. Commercial 4000-lb (17.8-kN) shores will be used. It is estimated that the weight of the formwork will be 5 lb/sq ft (0.24 kPa). The adjusted allowable stresses for the lumber being used are as follows: Sheathing psi [kPa] 1075 [7412] 174 [1200] Fb Fv FcJ. Fe E 1.36 x 106 [9.4 X 106] Other Members psi [kPa] 1250 180 405 850 1.40 [9.7 [8619] [1241] [2792] [5861] X 106 X 106] Maximum deflection of form members will be limited to 11360.Use the minimum value of live load permitted by ACI. Determine joist spacing, stringer spacing, and shore spacing. Solution Design Load. Assume concrete density is 150 lb/cu ft (2403 kg/m3) Concrete = 1 sq ft x 6/12 ft x 150 lb/cu ft = 75 lb/sq ft Formwork = 5 lb/sq ft Live load = 50 lb/sq ft Design load = 130 lb/sq ft 12-4 FIGURE 12-2 Example 12-1. Slab Form Design Slab form, Sheathing Plan Pressure per m2: Concrete = 1 x 0.152 x 9.8 x 2403/1000 = 3.58 kPa Formwork = 0.24 Live load = 2.40 kPa = 6.22 kPa Design load kPa Deck Design. Consider a uniformly loaded strip of decking (sheathing) 12 in. (or 1 m) wide placed perpendicular to the joists (Figure 12-1a) and analyze it as a beam. Assume that the strip is continuous over three or more spans and use the appropriate equations of Table 12-3 and 12-3A. 349 350 Chapter 12 w [w = (1 sq ftJlin ft) x (130 lb/sq ft) = 130 lb/ft = (1 m2/m) x (6.21 kN/m2) = 6.21 kN/m] (a) Bending: 1 = 4.46 d (F~b)1I2 = (4.46) d Fbb 1 =~ 1000 (19) 1000 in. 112 (w ) ( = (40.7) [ = 33.3 (0.75) (1071~0(12)rf2 7412) (1000» 1/2 6.22 ) = 844 mm ] (b) Shear: 1 = 13.3 FvA + 2d w _ (13.3) (174) (12) (0.75) + (2) (0.75) l 130 =~ = 161.7 in. FvA + 2d 1000 w [ - (1.11) (1200) (1000) (19) + (2) (19) (1000) (6.22) (c) Deflection: = 4107 mm ] Ebd3 1 = 1.69 (~t3 = 1.69 (W 12 ) 1/3 1.36 x 106) (12) (0.75)3 (130) (12) ( EI _~ l- 1000 ( ) _ 73.8 ( [ = 1.69 1/3 W = ) Ebd3 =~ 1000 (w12 ) ) = 703 mm ] 27.7 in. 1/3 (9.4 x 106) (1000) (19)3 1000 1/3 1/3 (12) (6.22) Deflection governs in this case and the maximum allowable span is 27.7 in. (703 mm). We will select a 24-in. (610-mm) joist spacing as a modular value for the design. Joist design. Consider the joist as a uniformly loaded beam supporting a strip of design load 24 in. (610 mm) wide (same as joist spacing; see Figure 12-1b). Joists are 2 x 8 in. (50 x 200 mm) lumber. Assume that the joists are continuous over three spans. w = (2 ft) x (1) x (130 lb/sq ft) = 260 lb/ft [ w = (0.610 m) x (1) x (6.22 kPa) = 3.79 kN/m] 12-4 Slab Form Design (a) Bending: (F:YI2 1 = 10.95 = 10.95 ((1250~i~3.14»)1/2= 87.0 1= ...!QQ... 1000 [ = F bS (w ) ( (8619) (2.153 x 105) 3.79 100 1000 in. 1/2 ) = 2213 mm ] 1/2 (b) Shear: 1 = 13.3 FvA + 2d w = (13.3) = 114.7 in. (180) (10.88) + (2) (7.25) 1 =1Jl FvA + 2d 1000 w [ -_ 1.11 (1241) (7016) + (2)(184) = 2918 mm 1000 3.79 ] (c) Deflection: 1 = 1.69 (~t3 (1.4 x 106)(47.63» ( I: 1~:98EI 1/3 (w ) = 1000 ( 260 ) 113 = 107.4 in. 1000 73.8 [ 9.7 x 106) (19.83 X 106» 3.79 ) 1/3 = 2732 mm ] Thus bending governs and the maximum joist span is 87 in. (2213 mm). We will select a stringer spacing (joist span) of 84 in. (2134 mm). Stringer Design. To analyze stringer design, consider a strip of design load 7 ft (2.13 m) wide (equal to stringer spacing) as resting directly on the stringer (Figure 12-1c). Assume the stringer to be continuous over three spans. Stringers are 4 x 8 (100 x 200 mm) lumber. Now analyze the stringer as a beam and determine the maximum allowable span. = (7) (130) = 910 lb/ft [w = (2.13) (1) (6.22) = 13.25 w kN/m] 351 352 Chapter 12 (a) Bending: 112 FbS ( ) ( )= : 1;~:5 FbS 1 1000 ( w ) _ 100 13.25 [ - 1000 ( ) 1 = 10.95 --;;- 1250) (30.66) 112 71.1 in. ~210 (8619) (5.024 x 105) 112 = 1808 mm . ] (b) Shear: l= 13.3 FvA + 2d w = (13.3) l =l::!l 1000 [ -- 1.11 1000 (180) (25.38) + (2) (7.25) 910 = 81.3 in. FvA + 2d w (1241) (16.37 x 103) + (2) (184) 13.25 = 2070 mm J (c) Deflection: 1 = 1.69 (~t3 = 1.69 (1.4 x l~:b (111.1)t3 = 93.8 EI l =~ 1000 w [ = 73.8 1000 in. 1I3 () ( 9.7 x 106) (46.26 X 106) 13.25 ) 113 = 2388 mmJ Bending governs and the maximum span is 71.1 in. (1808 mm). Now we must check shore strength before selecting the stringer span (shore spacing). The maximum stringer span based on shore strength is equal to the shore strength divided by the load per unit length of stringer. 4000 . 1 = 910 x 12 = 52.7 m. [l = 1~~285 = 1.343m] Thus the maximum stringer span is limited by shore strength to 52.7 in. (1.343 m). We select a shore spacing of 4 ft (1.22 m) as a modular value. 12-5 Wall and Column Form Design Before completing our design, we should check for crushing at the point where each joist rests on a stringer. The load at this point is the load per unit length of joist multiplied by the joist span. P = (260) (84/12) = 1820 lb [P = (3.79) (2.134) = 8.09 kN] Bearing area (A) = (1.5)(3.5) [A = (38) (89) fc.L =~ [fc.L= = ;~:~ = 347 8.09 x 106 3382 = 5.25 sq in. = 3382 mm2 ] OK psi < 405 psi (Fc.L) 2392 kPa < 2792 kPa (fc.L) ] Final Design. Decking: nominal1-in. (25-mm) lumber Joists: 2 x 8's (50 x 200-mm) at 24-in. (610-mm) spacing Stringers: 4 x 8's (100 x 200-mm) at 84-in. (2.13-m) spacing Shore: 4000-lb (17.8-kN) commercial shores at 48-in. (1.22-m) intervals 12-5 WALLAND COLUMN FORM DESIGN Design Procedures The design procedure for wall and column forms is similar to that used for slab forms substituting studs for joists, wales for stringers, and ties for shores. First, the maximum lateral pressure against the sheathing is determined from the appropriate equation (Equation 12-1, 12-2, or 12-3). If the sheathing thickness has been specified, the maximum allowable span for the sheathing based on bending, shear, and deflection is-the maximum stud spacing. If the stud spacing is fixed, calculate the required thickness of sheathing. Next, calculate the maximum allowable stud span (wale spacing) based on stud size and design load, again considering bending, shear, and deflection. If the stud span has already been determined, calculate the required size of the stud. After stud size and wale spacing have been determined, determine the maximum allowable spacing of wale supports (tie spacing) based on wale size and load. If tie spacing has been preselected, determine the minimum wale size. Double wales are commonly used (see Figure 12-3) to avoid the necessity of drilling wales for tie insertion. Next, check the tie's ability to carry the load imposed by wale and tie spacing. The load (lb) [kN] on each tie is calculated as the design load (lb/sq ft) [kPa] multiplied by the product of tie spacing (ft) [m] and wale spacing 353 354 Chapter 12 Wale Stud Tie/ T Stud spacing ,>:~'.f, ,.»" .".> c'. . . ~.." .' . -: :.,:> .. r' . .Po: .: ..0 ~ T Wale spacing .;:/:f'~": J..:~ . .~ ': ',...o.~.:: 1 I :~.:: <\'-:': : ~~<.o~ :>. :'.':~ ',".: ':'~.'.".,' T Tie "'O~''': '4,:" I~: [it .::<.~.:;. . 0 .',.' ~ q...:. I, ')~. I Plan Section FIGURE 12-3 Wall form, Example 12-2. (£1)[m] . If the load exceeds tie strength, a stronger tie must be used or the tie spacing must be reduced. The next step is to check bearing stresses (or compression perpendicular to the grain) where the studs rest on wales and where tie ends bear on wales. Maximum bearing stress must not exceed the allowable compression stress perpendicular to the grain or crushing will result. Finally, design lateral bracing to resist any expected lateral loads, such as wind loads. EXAMPLE 12-2 Forms are being designed for an 8-ft (2.44-m) high concrete wall to be poured at a rate of 4 ftJh (1.219 mIh), internally vibrated, at 900 F (320 C) temperature (see Figure 12-3). Sheathing will be 4 x 8 ft (1.2 m x 2.4 m) sheets of 12-5 Wall and Column Form Design 5/8-in. (16-mm) thick Class I Plyform with face grain perpendicular to studs. Studs and double wales will be 2 x 4 in. (50 x 100 mm) lumber. Snap ties are 3000-lb (13.34-kN) capacity with 1-l/2-in. (38-mm) wide wedges bearing on wales. Deflection must not exceed 1/360. Determine stud, wale, and tie spacing. Use Plyform section properties and allowable stresses from Table 12-4 and lumber section properties from Table 12-5. Allowable stresses for the lumber being used for studs and wales are: Fb = 1810 psi (12480 kPa) Ff} = 120 psi (827 kPa) Fc.L= 485 psi (3340 kPa) E = 1.7 X 106 psi (11.7 x 106 kPa) Solution Design Load. p = 150 + 9000R T [ P =7 2 785R . + T + 18 = 150 =7 2 . + (9000) 90 (4) + = 550 lb/sq ft (785) (1.219) 32 + 18 = 26 3 kNl . 2 m Check: 550 < 150 h (= 1200 lb/sq ft) < 2000 lb/sq ft [26.3 < 23.6 h (= 57.5 kN/m2) < 95.8 kN/m2 ] Select Stud Spacing (Three or More Spans). Material: 5/8-in. (16-mm) Class I Plyform (Table 12-4) Consider a strip 12 in. wide (or 1 m wide): w [w (a) Bending: = 1 x 1 x 550 = 550 =1 x 1 x 26.3 = 26.3 lb/ft kN/m ] ] OK 355 356 Chapter 12 (b) Shear: Z = 20 Fslb/Q w + 2d x 103) + (2) (5/8) -_ (20) (0.412 550 = 14.98 + 1.25 = 16.23 Z = 1.67 FJb/Q in. + 2d w x 103) + (2) (16) -_ (1.67) (6.01 26.3 = 382 + 32 = 414 rom (c) Deflection: Z = 1.69 (~t3 = (1.69) z=~ [ (0.19:5~ 106t3 EI 1I3 1000 w = 73.8 1836 x 109 1000 26.3 ( ) ( Deflection governs. Maximum span mm) stud spacing. ) 113 = 12..0 in. = 304 = 12.0 in. rom ] (304 mm). Use a 12-in. (304- Select Wale Spacing (Three or More Spans). Since the stud spacing is 12 in. (304 mm), consider a uniform design load 1 ft (304 rom) wide resting on each stud. w = 1 x 1 x 550 = 550 lb/ft 304 [w = 1000 x 1 x 26.3 = 8.0 kN/m] (a) Bending: Z = 10.95 (F~Srl2 = (10.95) (1810~~~.063»)1/2 = 34.77 z= 1000 ...!QQ.. FbS in. 112 (w ) Z= 100 [ 1000 ( (12480) (0.5019 x 105) 8.0 ) 1/2 = 885 mm ] 12-5 Wall and Column Form Design (b) Shear: Z = 13.3 FuA + 2d w - (13.3) (120) (5.25) + (2) (3.5) = 22.23 in. 550 z= 1:.!l FuA + 2d 1000 w [ = (1.11) (827) (3.387 x 103) + (2) (88.9) (1000) (8.0) = 566 mm J (c) Deflection: Shear governs, so maximum span (wale spacing) is 22.23 in. (566 mm). Use a 16-in. (406-mm) wale spacing for modular units. Select Tie Spacing (Three or More Spans, Double Wales). wale spacing of 16 in. (406 mm): 16 w =12 x 550 = 733.3 lb/ft 406 [w = 304 x 8.0 = 10.68 kN/m ] (a) Bending: Z = 10.95 (F~St2 = 10.95 z= .lQQ... 1000 ((1810) 7C:3~33.063) t2 FbS = 42.58 (w ) = 100 1000 ( (12480) (2 x 0.5019 x 105) [ in. 1/2 10.68 ) 112 = 1083 mmJ Based on a 357 358 Chapter 12 (b) Shear: I = 13.3 FvA + 2d w = (13.3)(120)(2 733.3 x 5.25) + (2)(3.5) = 29.85 in. I =lJl FvA + 2d 1000 w x 3.387 [ = (1.11)(827)(2 (1000)(10.68) = 760 mm x 103) + (2)(88.9) ] (c) Deflection: 1=1.69(~r3 = 1 69 (1.7 x 106)(2 x 5.359) 1/3= 49 32 . ( . =~ EI w () = 73.8 [ 1000 ( I 1000 ) 733.3 1/3 . (11. 7 x 106)(2 x 2.231 x 106) 10.68 m. ) 1/3 = 1252 mm] Shear governs. Maximum span is 29.85 in. (760 mm). Select a 24-in. (610mm) tie spacing for a modular value. (d) Check tie load: P = wale spacing x tie spacing x p 16 24 = -12 -12 (550) = 14671b/tIe. < 3000 lb OK (406)(610) [P = (1000)(1000) x 26.3 = 6.51 kN < 13.34 kN ] Check Bearing. (a) Stud on wales: Bearing area (A) (double wales) [A Load at each panel point (P) = loadlft(m) = (2)(1.5)(1.5) = 4.5 sq in. = (2)(38)(38) = 2888 of stud x wale spacing (ft/m) 16 = 733 lb 12 406 P = (550) [P = (8.0) mm2) 1000 = 3.25 kN ] 12-6 j: = AP = 733 = 163 4.5 j: = 3.252888 X 106 = 1125 kPa Icl. [I cl. Design of Lateral Bracing psi < 485 psi (FcJ) OK < 3340 kPa (FCJ) ] (b) Tie wedges on wales: Tie load (P) = 1467 lb [6.51 kN] Bearing area (A) = (1.5)(1.5)(2) = 4.5 sq in. [A = (38)(38)(2) = 2888 mm2] = ~ = 1:.~7 = 326 psi < 485 psi (Fcl.) 6.51 x 106 fc.l= 2888 = 2254 kPa < 3340 kPa (Fcl.)] [ OK fc.l- Final Design. Sheathing: 4 x 8 ft (1.2 x 2.4 m) sheets of 5/8-in. (16-mm) Class I Plyform placed with the long axis horizontal. Studs: 2 x 4's (50 x 100 mm) at 12 in. (304 mm) on center. Wales: Double 2 x 4's (50 x 100 mm) at 16 in. (406 mm) on center. Ties: 3000-lb (13.34-kN) snap ties at 24 in. (610 mm) on center. 12-6 DESIGN OF LATERAL BRACING Many failures of formwork have been traced to omitted or inadequately designed lateral bracing. Minimum lateral design load values were given in Section 12-2. Design procedures for lateral bracing are described and illustrated in the following paragraphs. Lateral Braces for Wall and Column Forms For wall and column forms, lateral bracing is usually provided by inclined rigid braces or guy-wire bracing. Since wind loads, and lateral loads in general, may be applied in either direction perpendicular to the face of the form, guy-wire bracing must be placed on both sides of the forms. When rigid braces are used they may be placed on only one side of the form if designed to resist both tension and compression forces. When forms are placed on only one side of a wall with the excavation serving as the second form, lateral bracing must be designed to resist the lateral pressure of the concrete as well as other lateral forces. 359 360 Chapter 12 Inclined bracing will usually resist any wind uplift forces on vertical forms. However, uplift forces on inclined forms may require additional consideration and the use of special anchors or tiedowns. The strut load per foot of form developed by the design lateral load can be calculated by the use of Equation 12-11. The total load per strut is then P' multiplied by strut spacing. P' = H x h x 1 h' x l' 1 = (h,2 + l'2)1/2 ( 12-11 ) (12-12) where P' = strut load per foot of form (lb/ft) [kN/m] H = lateral load at top of form (lb/ft) [kN/m] of form (ft) [m] h' = height of top of strut (ft) [m] 1 = length of strut (ft) [m] h = height l' = horizontal distance from form to bottom of strut (ft) [m] If struts are used on only one side of the form, the allowable unit stress for strut design will be the lowest of the three possible allowable stress values (Fe, Fe, or Ft). EXAMPLE 12-3 Determine the maximum spacing of nominal 2 x 4 in. (50 x 100 mm) lateral braces for the wall form of Example 12-2 placed as shown in Figure 12-4. Assume that local code wind requirements are less stringent than Table 12-1. Allowable stress values for the braces are as follows. Allowable Stress psi Fe Ft E 850 725 1.4 x 106 kPa 5861 4999 9.7 X 106 Solution Determine the design lateral force per unit length of form. H = 100 lb/ft (Table 12-1) [H = 1.46 kN/m (Table 12-1)] Determine the length of the strut using Equation 12-12. 1 = (h,2 + l'2)1/2 = (62 + 52)112 = 7.81 it [l = (1.832 + 1.532)1/2= 2.38 m] The axial concentrated load on the strut produced by a unit length of form may now be determined from Equation 12-1. 12-6 Design of Lateral Bracing H ------- 8ft (2.44 m) r . 6 ft _ (1.83 m) ~5ft(1.53m)-1 FIGURE 12-4 Wall form bracing, Example 12-3. P' = H x h x I = = 208 3 lb/ft f fi . 0 orm (1008)(8)(7.81) h' x l' (6)(5) p' = (1.46)(2.44)(2.38) = 3 03 kN/ (1.83)(1.53) . m] [ Next, we determine the allowable compressive stress for each strut using Equation 12-10. To do this, we must determine the lid ratio of the strut. lid = (7.8:.~12) = 62.5> 50 [lid = (2.3~~.~000) = 62.5 > 50] Since the lid ratio exceeds 50, each strut must be provided lateral bracing to reduce its unsupported length. Try a single lateral support located at the mid- point of each strut, reducing I to 46.9 in. (1.19m). F, , _ 0.3 E _ (0.3)(1.4 X 106) - c D (lId)2 - , = (0.3)(9.7 [ L'C 430 (46.9/1.5)2 X 106) (1190/38)2 2 97 kP . a] As Fc' < Ft < Fc, the value of Fc' governs. The maximum allowable compressive force per strut is: P [p = (1.5)(3.5)(430) = 2257 lb = (38)(8~6~2967) = 10.03 . pSI kN] 361 362 Chapter 12 Thus maximum strut spacing is: p 2257 s = p' = 208.3 = 10.8ft 10.03 s = 3.03 = 3.31 m] [ Keep in mind that this design is based on providing lateral support to each strut at the midpoint of its length. Lateral Braces for Slab Forms For elevated floor or roof slab forms, lateral bracing may consist of cross braces between shores or inclined bracing along the outside edge of the form similar to that used for wall forms. The following example illustrates the method of determining the design lateral load for slab forms. EXAMPLE 12-4 Determine the design lateral force for the slab form 6 in. (152 mm) thick, 20 ft (6.1 m) wide, and 100 ft (30.5 m) long shown in Figure 12-5. The slab is to be poured in one pour. Assume concrete density is 150 lb/cu ft (2403 kg/m3) and that the formwork weighs 15 lb/sq ft (0.72 kPa). Solution Dead load = (1/2)(1)(150) + 15 = 90 lb/sq ft [dl H = (0.152)(~~~~03)(9.8) = 0.02 x dl x ws + 0.72 = 4.30 kpa] For the 20-ft (6.1-m) face, the width of the slab is 100 ft (30.5 m). = (0.02)(90)(100) = 180 lb/lin ft [H = (0.02)(4.30)(30.5) = 2.62 kN/m] H20 For the 100-ft (30.5-m) face, the width of the slab is 20 ft (6.1 m). HIOO= (0.02)(90)(20) = 36 lb/ft < 100 lb/ft (minimum value) [H = (0.02)(4.29)(6.1) = 0.52 kN/m < 1.46 kN/ml Therefore, use HIOO= 100 lb/ft (1.46 kN/m) = minimum load. FIGURE 12-5 Slab form bracing design, Example 12-4. -r r 100 tt (30.5 m) 1 ....... 20 tt (6.1 m) ...L J ~ ~ ~ ~ ~ ~ ~ H100 Ib/tt (kN/m) ~ ~ -- ~....... H20 Ib/tt (kN/m) Problems PROBLEMS 1. Calculate the appropriate design load due to concrete pressure for a wall form 9 ft (2.75 m) high to be poured at a rate of 6.5 ft (2.0 m) per hour at a temperature of 68°F (20°C). 2. What should be the design load due to concrete pressure for a column form 15 ft (4.9 m) high that is to be filled by pumping concrete into the form from the bottom? 3. Determine the proper design load for a slab form 9 in. (229 mm) thick using motorized buggies for placing concrete. The formwork is estimated to weigh 10 lb/sq ft (48.8 kg/m2). /4. Calculate the maximum allowable span for 3/4-in. (19-mm) Class I Plyform decking with face grain across supports carrying a design load of 150 lb/sq ft (7.2 kPa). Assume that the decking is continuous over three or more spans and limit deflection to 1/240 of span length. S. Determine the maximum allowable spacing of nominal 2 x 4 in. (50 x 100 mm) studs for a wall form sheathed with nominal I-in. (25-mm) Hem-fir lumber. The design load is 500 lb/sq ft (23.9 kPa). Assume that the sheathing is continuous over three or more spans. Use the allowable stresses of Table 12-6 with 7-day load and wet conditions. Limit deflection to 1/360 of span length. 6. Determine the maximum allowable span of nominal 2 x 4 in. (50 x 100 mm) wall form studs carrying a design load of 1000 lb/sq ft (47.9 kPa). The stud spacing is 16 in. (406 mm) on center. Use the allowable stresses for Douglas Fir from Table 12-6 and 7-day load duration. Assume that studs are continuous over three or more spans. Limit deflection to 1/360 of span length. Based on the maximum allowable span, check for crushing of studs on double 2 x 4 in. (50 x 100 mm) wales. 7. Design the formwork for a wall 8 ft (2.44 m) high to be poured at the rate of 5 ft/h (1.53 m/h) at a temperature of 77°F (25°C). Sheathing will be 3/4-in. (19-mm) Class I Plyform with face grain across supports. All lumber is Southern Pine. Use nominal 2 x 4 in. (50 x 100 mm) studs, double 2 x 4 in. (50 x 100 mm) wales, and 3000-lb (13.3-kN) snap ties. Lateral wood bracing will be attached at a height of 5 ft (1.53 m) above the form bottom and anchored 4 ft (1.22 m) away from the bottom of the form. Use the allowable stresses of Table 12-6 adjusted for 7-day load. Limit deflection to 1/360 of the span length. Design wind load is 25 lb/sq ft (1.2 kPa). ~8. Design the formwork for a concrete slab 8 in. (203 mm) thick whose net width between beam faces is 15 ft (4.58 m). Concrete will be placed using a crane and bucket. The formwork is estimated to weigh 5 lb/sq ft (24.1 kg/m2). Decking will be 3/4-in (19-mm) Class I Plyform with face grain across supports. All lumber will be Southern Pine. Joists will be nominal 2-in. (50-mm) wide lumber. One 4-in. (lOO-mm) wide stringer will be placed between the beam faces. Limit deflection to 1/360 of span length. Commercial shores of 4500 lb (20 kN) capacity will be used. Lateral support will be provided by the beam forms. 363 364 Chapter 12 9. Derive the equations for bending given in Table 12-3 using the relationships of Table 12-2 and Equation 12-5. 10. Develop a computer program to calculate the maximum safe span of a wood formwork member as determined by bending, shear, and deflection based on the equations of Table 12-3 or 12-3A. Input should include support conditions, allowable deflection, allowable stresses, load per unit length of span, and dimensions of the member. REFERENCES 1. American Institute Of Timber Construction. Timber Construction Manual, 3rd ed. New York: Wiley, 1985. 2. American Plywood for Concrete Forms. APA-The Engineered WoodAssociation, Tacoma, WA, 1992. 3. Concrete Forming. APA-The Engineered Wood Association, Tacoma, WA, 1994. 4. Design of Wood Formwork for Concrete Structures (Wood Construction Data No.3). American Forest and Paper Products Association, Washington, D.C., 196!. 5. Guide to Formwork for Concrete (ACI 347R-94). American Concrete Institute, Detroit, MI, 1994. 6. Hurd, M. K. Formwork for Concrete, 6th ed. American Concrete Institute, Detroit, MI, 1995. 7. National Design Specification for Wood Construction. American Forest and Paper Products Association, Washington, D.C., 1982. 8. Peurifoy, Robert L., and Garold D. Oberlender. Formwork for Concrete Structures, 3rd ed. New York: McGraw-Hill, 1996. 9. Plywood Design Specifications. APA-The Engineered Wood Association, Tacoma, WA, 1995.