AT02 - Anly Electronics Co., Ltd.
Transcription
AT02 - Anly Electronics Co., Ltd.
ɀNames and Functions of Partsɀ AT02 SERIES PID TEMPERATURE CONTROLLER User's Manual Upper Display AT-502 RESTRICTIONS ON USE LEDs When using this product in applications that require particular safety or when using this product in important facilities, please pay attention to the safety of the overall system and equipment. Install failsafe mechanisms, perform redundancy checks and periodic inspections and adopt other appropriate safety measures when it is necessary. This product is rated at Class Ⅱ . AT: Lit when the auto tuning is ON. OUT: Lit when the control output is ON. ALM: Lit when the alarm output is ON. LOCK: Lit when the key is locked. Displays PV values (current temperature, etc.) or setup items. o C PV SV Lower Display AT OUT ALM Displays SV values (set temperature, etc.) and other parameter values. LOCK SET Key : Used to change numeric values. ATTENTION ! SET 1.Please read the SAFETY PRECAUTION section on reverse side before use of this product. Key : Switches the display. Hold down for 3 seconds to switch modes. 2.Please read this user's manual before use for proper operation. Key : Used to shift setup items or parameter digits. 3.Please safe guard this user's manual. ɀFunction Settingɀ ɀUser Level Settingɀ Warning! Please make sure the power is off, before making any changes on the DIP switch. 1 Set the DIP switch to PID Control before proceeding. Power ON o C PV DIP Switch ON 1 2 3 4 5 1 6 2 3 4 5 All displays are lit for 3 seconds. 6 SV AT Input type K Type 0~1200 C J Type 0~500 C O O 0~1700 C PT-100 -50~400 C OFF ON ON is displayed for about 6 seconds. ON OFF ON o C PV PID CONTROL OUT ALM RELAY OFF DC 24V (for SSR) ON NONE SET key for 3 seconds to enter Parameter Mode. o C PV Current SV value SV OUT ALM ON LOCK 4 Press SET key once to setup Alarm Setting. SV+AS1 Deviation High Alarm OFF ON SV ON OFF OFF ON AS1 Process Low Alarm ON OFF AS1 SV-AS1 Deviation High/Low Alarm ON Band Alarm OFF ON PV 5 Press SET key once to setup Auto Tunning. PV OFF o C PV AT OUT ALM SET key once to setup PV Offset. o C PV AT O OUT ALM LOCK SET key once to setup SV Offset. o C PV SV OUT ALM LOCK Under User Level, press key for 3 seconds to enter Key Lock Mode. Set Lock Number according to the level of protection. SET key for 3 seconds to PV setup Proportional Band. AT o C 0022 ˕ 0 111 11 2 2 ˕ ˕ ǘ ˕ ˕ ˕ ǘ ǘ ˕ ˕ ǘ ǘ ǘ O OUT ALM LOCK o C PV o C AT OUT ALM LOCK ALM LOCK o C OUT ALM LOCK ALM LOCK C Under Operation Mode, press key for 3 seconds to lock the SV value. And press key for 3 seconds again to unlock the SV value. Ct1: Relay Cycle Time 0~65sec OUT ALM LOCK 8 Press SET key once to setup SSR Cycle Time. d1: Derivative Time (D) 0~1800sec (Set 0 for P Control) OUT o AT i1: Integral Time (I) 0~7200sec (Set 0 for P Control) OUT SET key once to setup PV Relay Cycle Time. o C PV Ct2: SSR Cycle Time 0~65sec SV OUT ALM LOCK 9 Press SET key once to setup Fuzzy. o C PV AT 10 Press Fuzzy On/OFF SV ˕ Symbol炼˕: Can display and can be set ǘ : Can't display nor can't be set LOCK 7 Press ɀSV Lock Settingɀ SV ALM PV Current PV value Current SV value SV PV OUT C AT ˕ O o AT P1: Proportional Band (P) 0.1~300.0 C SV SV SET key once to return to Operation Mode. AT Others LOCK PV 8 Press List of Key Lock Mode : usr Pid SEt ArG ALM 6 Press SET key once to setup Derivative Time. LVL Pid OUT 4 Press SoF: SV Offset -200.0~200.0 C SV C C SV SV 7 Press ɀKey Lock Settingɀ o o AT Process Low Alarm (Standby) Band Alarm (Standby) LOCK PV PoF: PV Offset -200.0~200.0 C SV Process High Alarm (Standby) Deviation High/Low Alarm (Standby) ALM SV 6 Press Deviation Low Alarm (Standby) key once and key once to enter Pid Level. SET key once to setup Integral Time. PV Deviation High Alarm (Standby) uSr OUT 5 Press LOCK LVL 3 Press AT YES / no SV C AT At: Auto Tunning PV SV+AS1 ON SV LOCK PV SV+AS1 OFF SV SV-AS1 ALM LOCK o AT O OUT ALM SV AS1: Alarm Setting 200.0~200.0 C SV AT SV Process High Alarm C PV SV+AS1 Deviation Low Alarm o PV Current PV value Current SV value OUT PV Current PV value OFF ALL EXCEPT SV PV C 2 Press LOCK 3 Operation Mode ON List of Alarm Function : AT tic OFF AT 1 2 3 4 5 6 7 8 9 10 11 12 o PV AT IC version SV O is displayed. Function Lock Operation Mode. LOCK 2 The IC version ON ON OFF ON/OFF CONTROL Output ALM SV AT Control Mode 1 Start with OUT ON OFF OFF R Type O ɀPID Control Settingɀ OUT ALM LOCK key for 3 seconds to return to Operation Mode. ɀSet Level Settingɀ ɀON/OFF Control Settingɀ Set the DIP switch to ON/OFF Control before proceeding. C AT key for 3 seconds to enter Parameter Mode. Current PV value Current SV value OUT ALM LOCK SET o C PV key once and key once to enter Pid Level. OUT ALM C AT SET key for 3 seconds to setup Hysteresis. OUT ALM o C PV AT ALM 11 Press C SET key for 3 seconds to setup Alarm Function. OUT ALM o C OUT ALM C SET key once to setup Alarm Hysteresis. ALM LOCK 5 Press o C PV SET key once to setup Control Action. o C Current SV value SV AT key once to setup SV. Current PV value OUT ALM LOCK AT SET key once to setup Decimal Point. ALM o C PV C Current SV value SV AT Current PV value OUT ALM LOCK AT SET key once to setup Low Set Point. ALM C key to change value and press key to move the cursor. o C PV Current SV value SV AT Current PV value OUT ALM LOCK AT SET key once to setup High Set Point. OUT ALM LOCK 9 Press o C PV AT OUT ALM LOCK ɀTERMINAL LAYOUT ɀ LVL ArG OUT ALM LOCK o C SET key once to setup 1-3. OUT ALM 1-2 select 1: non, AS1, At, PoF, SoF SV LOCK 5 Press dP: Decimal Point o C PV SET key once to setup 1-4. OUT ALM 1-3 select 1: non, AS1, At, PoF, SoF SV LOCK 6 Press LSP: Low Set Point o C PV AT SET key once to setup 1-5. OUT ALM 1-4 select 1: non, AS1, At, PoF, SoF SV LOCK 7 Press HSP: High Set Point o C PV SV AT 8 Press AT-502 C PV Temperature range varies with Input type SV key once to return to Operation Mode. SET key for 3 seconds to setup 1-2. Temperature range varies with Input type SV 3 Press o AT o PV LOCK 4 Press Act: Control Action LOCK 8 Press ALM SV 0 / 0.0 OUT LVL uSr OUT PV AT SV o PV key once and key three times to enter ArG Level. LOCK 7 Press 2 Press 4 Press OUT C 3 Press AH1: Alarm Hysteresis Hearting / Cooling SV LOCK o AT C ALM SV LOCK o Current SV value OUT PV AT O ALM PV 1 Start with SET key for 3 seconds to enter Parameter Mode. Current PV value 2 Press AF1: Alarm Function -200.0~200.0 C SV OUT C SV 1~12 See List of Alarm Function SV OUT o PV AT o PV AT Operation Mode. LVL LOCK 6 Press PV key for 3 seconds to return to Operation Mode. SEt SV AT Operation Mode. LOCK 1 Start with key for 3 seconds to return to Operation Mode. ɀSV Value Settingɀ ALM This is used to display or hide arguments under user level. Arguments can be arranged in any order, but may not repeated. LOCK PV HSt: Hysteresis LOCK OUT ɀArgument Level Settingɀ LVL uSr SV 4 Press O OUT LOCK o AT 0.0~200.0 C SV ALM PV LVL LOCK 4 Press AT Filter value 0~120sec SV Current SV value OUT C SET key once and key twice to enter SEt Level. Pid SV key for 3 seconds to enter Parameter Mode. FiLt: o PV Current PV value 3 Press 3 Press o 2 Press AT LOCK PV AT LVL uSr SV AT 5 Press C SV o SV 2 Press o PV 1 Start with PV SET key once to setup Filter. 1 Start with Operation Mode. Operation Mode. 10 Press OUT ALM LOCK 1-5 select 1: non, AS1, At, PoF, SoF key for 3 seconds to return to Operation Mode. ɀDIMENSIONS(mm)ɀ A AT-402 / 602 / 902 B a Device b Panel Cutout AT02 series A B a b AT-402 48 96 45.5 +0.5 -0 91 +0.5 -0 AT-502 48 48 45.5 +0.5 -0 45.5 +0.5 -0 AT-602 96 48 AT-702 AT-902 72 96 72 96 91 +0.5 -0 67.5 91 +0.5 -0 +0.5 -0 45.5 +0.5 -0 67.5 +0.5 -0 91 +0.5 -0 ɀSAFETY PRECAUTIONɀ This manual uses the following symbols to ensure safe operation of this controller. AT-702 WARNING Warnings are indicated when mishandling this controller might result in death or serious injury to user. CAUTION Cautions are indicated when mishandling this controller might result in minor injury to the user, or only physical damage to the controller. WARNING Note this incorrect wiring of this controller can damage it and lead to other hazards. Make sure the controller has been correctly wired before turning the power ON. Before wiring, or removing / mounting the controller, be sure to turn the power OFF. Failure to do so might cause electric shock. Do not touch electrically charged parts such as the power terminals. Doing so might cause electric shock. Do not disassemble the controller. Doing so might cause electric shock or faulty operation. CAUTION Use the controller within the operating ranges recommended in the specification (temperature, humidity, voltage, shock, mounting direction, atmosphere and etc.). Failure to do so might cause fire or faulty operation. Do not block ventilation holes. Doing so might cause fire or faulty operation. Do not allow lead clippings, chips or water to enter the controller case. Doing so might cause fire or faulty operation. ANLY ELECTRONICS CO., LTD. http://www.anly.com.tw M-AT02-L-B Printed in Taiwan