Copeland Electrical Handbook
Transcription
Copeland Electrical Handbook
For more Copeland literature please visit www.HVACRinfo.com Electrical Handbook 2008-2009 Edition Note: This CD requires Adobe Acrobat Reader 7.0 or higher in order to display and search correctly. You should see a search panel at right, and links should have a simple underline rather than a box. If you are using an earlier version of Acrobat Reader, go to http://www.adobe.com/products/ acrobat/readstep2.html for a free download of the latest version. FOREWORD The progress of Emerson Climate Technologies, Inc., as well as that of refrigeration and air conditioning in general, has been greatly aided by good field service. Everyone at Emerson Climate Technologies, Inc. recognizes and appreciates the important contribution of the service engineer upon whose talents we and all refrigeration equipment manufacturers depend to assure complete user satisfaction. This booklet covers in detail electrical service information on welded compressors, Copelametic®, Copeland Scroll®, and Copeland Screw™ compressors. In addition, electrical service information is provided for Copeland® Condensing Units. The booklet is designed to assist the service engineer to better understand the function of such items as motors, relays, starting capacitors, running capacitors and motor protectors. In addition to electrical information, a brief section dealing with diagnosing the causes of compressor failures has been added. TABLE OF CONTENTS Motors and Electrical Components ..................................................................... A • Single and Three Phase Motors • Capacitors • Measuring Motor Temperature • Measuring Winding Resistance Electrical Motor Protection ................................................................................... B Fuse Selection ....................................................................................................... C Compressor Nomenclature .................................................................................. D • Welded Compressors • HFC Welded Compressors • A-Line • CRKQ, CIKQ • CR7, CR6, CRKF, CS, CF • Coplematic® • Copeland Discus™ • Refrigeration Copeland Scroll® • A/C Copeland Scroll® • Condensing Unit (All models except M-Line) • M-Line Condensing Unit • Copeland Screw™ Electrical Component Nomenclature and Data .................................................. E • Potential Relay Nomenclature • G.E. Numbering System • Potential Relay Data • Current Relay Data • Start Capacitor Data • Run Capacitor Data Compressor Electrical Data.................................................................................. F • A-Line .............................................................................................................. FA • Welded Compressors .................................................................................... FB • Copelametic® Air-Cooled .............................................................................. FC • Copelametic® Small Refrigerant-Cooled ..................................................... FD • Copelametic® Large Refrigerant-Cooled ..................................................... FE • Copeland Scroll® ........................................................................................... FF • Copeland Screw™ .......................................................................................... FG Wiring Diagrams .................................................................................................... G Electrical Troubleshooting Procedures............................................................... H Identifying Compressors Failures ....................................................................... I SECTION A MOTORS AND ELECTRICAL COMPONENTS TOPICS Single Phase Motors ...................................................A2 Start Relays .................................................................A3 Start Capacitors ...........................................................A5 Run Capacitors ............................................................A7 Parallel and Series Capacitors ....................................A9 Measuring Motor Temperature ..................................A10 Measuring Winding Resistance ................................. A11 Resistance Measurements for Single Voltage Motors................................................A13 Resistance Measurements for Dual Voltage Motors .............................................A15 Section A.indd 1 2/6/2008 10:46:30 AM SINGLE PHASE MOTORS There are four basic types of single phase motors used in hermetic and semi-hermetic compressors: • Split Phase or Resistance start - Induction Run (RSIR) • Capacitor Start - Induction Run (CSIR) • Capacitor Start - Capacitor Run (CSCR) • Permanent Split Capacitor (PSC) • Schematic diagrams of each type are shown in Figures 1,2,3 and 6 Figure 1 A2 Section A.indd 2 2/6/2008 10:46:41 AM START RELAYS Current and potential relays are used to actuate components that provide the torque to start single phase motors. Figure 2 A3 Section A.indd 3 2/6/2008 10:46:41 AM The Current Relay Current relays are used on small fractional horsepower compressor motors. The current relay contacts are normally open when de-energized. Its coil is wound with heavy wire and is placed in series with the incoming power line (Figure 1). The connections to the current relay are L, M, and S. Alternate connections are 1,5, and 2. When the compressor is energized inrush currents pass through the current relay coil, and its contacts close and connect the start winding to the motor circuit. The start winding is wound with a higher resistance than the run winding. This changes its phase current with respect to the run winding and produces the torque required for motor starting. The relay’s contacts open when current drops as the compressor comes up to speed, and the start winding is disconnected from the motor circuit. The Potential Relay The potential (voltage sensing) relay places the start capacitor in series with the start winding. It does so by sensing voltage across the start winding, rather than line current as does the current relay. The contacts of the potential relay are normally closed (Figures 2, and 3), and the start capacitor is connected to the start winding as soon as power is applied to the compressor motor. The relay’s coil senses the voltage developed across the start winding. It is designed to pick up, open its contacts, and disconnect the start capacitor from the start winding, when sufficient voltage is generated. Since the voltage or back-EMF generated by the start winding is proportional to motor speed, the relay will open only when the motor has started and is approaching normal running speed. A4 Section A.indd 4 2/6/2008 10:46:41 AM Figure 3 START CAPACITORS Start capacitors are used on compressors where system designs require high starting torque. Start capacitors are designed for intermittent service only and have a high microfarad (MFD) rating. Their construction is of the electrolytic type in order to obtain high capacitance. All standard Copeland® start capacitors are supplied with bleed-resistors securely attached and soldered to their terminals as shown in Figure 4. A5 Section A.indd 5 2/6/2008 10:46:41 AM Figure 4 The use of capacitors without these resistors will result in sticking relay contacts and/or erratic relay operation especially where short cycling is likely to occur. This is due to the start capacitor discharging through the relay contacts as they close, following a very short running cycle. The resistor permits the capacitor charge to bleed down at a much faster rate, preventing arcing and overheating of the relay contacts. The use of capacitors supplied by Emerson Climate Technologies, Inc. is recommended. In case of an emergency exchange, a 15,000-18,000 ohm, two watt resistor should be soldered across the terminals of each start capacitor. Care should be taken to prevent their shorting to the case or other nearby metallic objects. If sticking contacts are encountered on any start relay, the first item to check is the start capacitor resistor. If damaged, or not provided, install a new resistor, and clean the relay contacts or replace the relay. Suitable resistors can be obtained from any electronic parts wholesaler or retailer. A6 Section A.indd 6 2/6/2008 10:46:41 AM RUN CAPACITORS Run capacitors are used on compressors to improve efficiency, raise the motor’s power factor, and lower noise. Run capacitors are continuously in the operating circuit and are normally of the metallized film type. They are manufactured in oval (Figure 5) or round cans. Figure 5 THE PTC START ASSIST The PTC (Positive Temperature Coefficient) resistor is used for applications where high starting torque is not required. The PTC resistor is connected in parallel with the run capacitor, placing it in series with the start winding (Figure 6). The PTC has a low resistance when it is cold. When the motor starts, the low resistance causes a large current to flow through the resistor. The current drawn by the resistor is out of phase with the current drawn by the motor windings, and this provides the torque to start. As soon as the resistor draws current, it begins to heat, and the positive temperature effect of the resistor causes it to rapidly increase its resistance. By the time the motor reaches full speed, very little current is drawn by the reA7 Section A.indd 7 2/6/2008 10:46:42 AM sistor. Although it remains connected to the motor circuit, it has no significance in the operation of the compressor. Figure 6 Capacitor Voltage The voltage rating of a capacitor indicates the highest nominal voltage at which it is designed to operate. Use of a capacitor at voltages below its rating will do no harm. Run capacitors must not be subject to voltages exceeding 10 percent of the nominal rating, and start capacitors must not be subjected to voltages exceeding 30 percent of the nominal rating. A8 Section A.indd 8 2/6/2008 10:46:42 AM The voltage to which a capacitor is subjected is not line voltage, but is a much higher potential (often called back electromotive force or back EMF) which is generated in the start winding. On a typical 230 volt motor, the generated voltage may be as high as 400 volts and is determined by the start winding characteristics, the compressor speed, and the applied voltage. PARALLEL AND SERIES CAPACITORS Capacitors, either start or run, can be connected in series or parallel to provide the desired characteristics if the voltage and MFD are properly selected. When two capacitors having the same MFD rating are connected in series, the resulting total capacitance will be one half the rated capacitance of a single capacitor. The formula for determining capacitance (MFD) when capacitors are connected in a series is as follows: 1 = _____+ 1 1 ____ ____ MFDt MFD1 MFD2 For example, if a 20 MFD and a 30 MFD capacitor are connected in series, the resultant capacitance will be: 1 1 1 ____= _____+ ____ MFDt 20 30 1 3 2 1 ____= _____+ ____= ____ MFDt 60 60 12 MFDt = 12MFD A9 Section A.indd 9 2/6/2008 10:46:42 AM The voltage rating of similar capacitors connected in series is equal to the sum of the voltage of the two capacitors. However, since the voltage across individual capacitors in series will vary with the rating of the capacitor, for emergency field replacements, it is recommended that only capacitors of like voltage and capacitance be connected in series to avoid the possibility of damage due to voltage beyond the capacitor limits. When capacitors are connected in parallel, their MFD rating is equal to the sum of the individual capacitances. The voltage rating is equal to the lowest voltage rating of the individual capacitors. It is possible to use any combination of single, series, or parallel start capacitors, with single or parallel run capacitors (run capacitors are seldom used in series). MEASURING MOTOR TEMPERATURE During system engineering development or in attempting to evaluate the ability of a compressor motor to operate under severe conditions, it is often desirable to measure motor temperatures under extreme conditions. In the laboratory during compressor development, temperature measurements of this type are made by means of thermocouples embedded in the motor windings with the leads brought out through gasketed surfaces. In evaluating a production compressor in a system, thermocouple readings are not usually feasible, and the only means of checking motor temperatures is by checking resistance values. The resistance through the motor windings varies in a ratio to the change in winding temperature. By establishA10 Section A.indd 10 2/6/2008 10:46:42 AM ing a base resistance value at a given base temperature (normally room temperature after storage for a prolonged period without operation) any change in the temperature of the motor windings can be calculated by determining the change in winding resistance. The resistance method, since it reads the overall resistance of the winding, is an average reading and does not accurately reflect the temperature that might exist at hot spots. In some cases, there may be hot spots that can reach temperatures of 40°F or more above the average reading so resistance readings must be evaluated very conservatively. Motors may be wound with either copper or aluminum wire, and it is necessary to know the motor construction since the resistance change varies depending on the type of wire. The basic formula for calculating winding temperature is as follows: Rh (T + K) - K Th = ___ c Rc Th = Temperature hot Tc = Temperature cold Rh = Resistance hot (ohms) Rc = Resistance cold (ohms) Kcopper = 390.1 for °F, 234.5 for °C Kaluminum = 365.8 for °F, 221.0 for °C MEASURING WINDING RESISTANCE DISCONNECT ALL SOURCES OF POWER TO THE COMPRESSOR BEFORE MAKING ANY RESISTANCE MEASUREMENT A11 Section A.indd 11 2/6/2008 10:46:42 AM Compressor Wiring Diagrams Compressor wiring diagrams with motor winding connections and numbering are often used as a reference for compressor motor winding resistance measurements. Electrical Handbook wiring diagrams show the compressor motor with its windings connected for its design voltages. The compressor motor windings are also shown unwired and labeled so that if it is necessary, individual winding resistances can be measured and compared to each other. The pages of Section G of the Electrical Handbook that are headed Copelametic Wiring Diagrams and Welded Compressors Wiring Diagrams list applicable wiring diagrams. They are indexed by the portion of the Copeland® compressor model number that references: 1. Compressor Model 2. The Compressor Electrical Characteristics: the type of motor, type of overload protection, voltage and phase. A typical compressor model number 4DH3R22ME-TSK indicates a 4D Compressor Model with TSK Compressor Electrical Characteristics (see Section D of the Electrical Handbook for further compressor model nomenclature). Ohmmeter Resistance Measurements. Electrical Handbook (See Section F) pages designated Electrical Data-Copelametic Compressors, Electrical Data-Copeland Scroll Compressors, and Electrical Data-Welded Compressors have columns that are headed Winding Resistance (Ohms). A12 Section A.indd 12 2/6/2008 10:46:42 AM The resistances shown are compressor motor resistances measured when the motor is connected for the voltage shown in the Electrical Data column headed Volts. Measurements must be taken with all external connections removed from the winding terminal blocks, but winding connection jumpers (if system voltage has been selected) inplace. Resistance measurements should be within plus or minus 10% of the listed resistance. The most satisfactory instrument for all winding resistance measurements is a low range digital ohmmeter since many of the winding resistances listed are in fractions of an ohm. MEASURING RESISTANCES OF SINGLE VOLTAGE RANGE MOTORS (Single Phase and Three Phase) Measurements are straightforward for single phase and three phase compressors that can only be wired across the line for a single voltage. A13 Section A.indd 13 2/6/2008 10:46:42 AM 1. Single phase motors have a Start Winding, a Run Winding, and a Common connection between them. Therefore, the measurements are listed as: Start Winding: “C” (Common) to “S” (Start), and Run Winding: “C” (Common) to “R” (Run). See Figure 7. Figure 7 2. On Three phase motors having a single voltage range the resistance measured is actually twice that of an individual winding since the centers of 3 lead, Wye wound motors are internally connected and cannot be reached for measurement. See Figure 8. A14 Section A.indd 14 2/6/2008 10:46:42 AM Figure 8 MEASURING RESISTANCES AND ELECTRICAL CONNECTIONS OF DUAL VOLTAGE THREE PHASE MOTORS (Single Contactor and Part-Winding or Two Contactor) The resistances listed in Section F, under the column headed WINDING RESISTANCE IN OHMS, LINE TO LINE are the values for a one contactor, across-theline start. When a six or nine lead motor is connected for a two contactor part winding start or across-the-line start, the phase-to- phase ohm value will be twice (x2) the value listed. When a nine lead motor is connected for high voltage, 460 volts, the phase-to-phase ohm value will be four times (x4) the listed value of the 230 volt value. If individual resistance measurements are needed, for a nine-lead motor, disconnect all jumpers and refer to Figure 9. A15 Section A.indd 15 2/6/2008 10:46:42 AM There are three individual windings (1-4, 2-5, and 3-6) and one wye-connected winding (7-8-9). The individual winding resistances are equal to the compressor’s 230 volt connected resistance measurement of Section F. The wye winding value is twice the 230 volt resistance measurement of Section F. Figure 9 Electrical connections are made through contactors to the compressor motor terminals. Brass jumper bars must be connected to the motor terminals to allow one or two contactors to be used for either across-the-line or part-winding starts. If the windings are connected out of phase, in any application, or if the jumper bars are not positioned correctly, motor overheating and failure will occur. A16 Section A.indd 16 2/6/2008 10:46:42 AM Six-lead motors are single voltage motors such as 200 or 460 volts. Nine-lead motors are dual voltage motors such as 208-230/460 volts. Figure 10 shows the electrical connections for a six lead 200 or 460 volt single contactor application. Figure 10 Figure 11 shows the electrical connections for a six lead 200 or 460 volt two contactor across-the-line or partwinding start application. The dotted lines mean power connections are made electrically rather than by jumper bars. Figure 11 A17 Section A.indd 17 2/6/2008 10:46:43 AM Figure 12 Figure 12 (top) shows the electrical connections for a nine lead, 208-230/460 volt, single contactor application when connected to 208 or 230 volts. It also shows (bottom) the electrical connections for a two contactor application when connected to 208 or 230 volts for an across-the-line or part- winding start. A18 Section A.indd 18 2/6/2008 10:46:43 AM Figure 13 Figure 13 shows the electrical connections for a ninelead 208-230/460 volt single contactor application when connected to 460 volts. Part-winding starts require a time delay relay. The time delay relay used in a part-winding start application, for either six- or nine-lead motors, must have a one second A19 Section A.indd 19 2/6/2008 10:46:43 AM delay and must be used between the pull in of the first and second contactors. Part-winding contactors must be sized based on the compressor motor Rated Load Amps (RLA) and the Part Winding Start, Locked Rotor Amp (LRA) rating. See Section F. Measurements Using The Megohmeter or “MEGGER” When using a megohmeter to evaluate the motor insulation of compressors, it is important to understand that they are not intended to be used for a single reading. They were developed to establish a trend. In other words, “meggers” are best used as part of a regular maintenance program where periodic readings can be recorded and a long term insulation resistance trend established. There are many factors that affect megohm readings including contaminated refrigerant, oil level, and current leakage through electrical fusites or terminal plates. Before making a measurement, all external wiring should be removed, and all electrical terminal bolts cleaned and torqued to specifications. Measurements Using The High Potential Or “Hi-Pot” Tester Ohmmeter readings usually determine if a motor is shorted or open, but a motor that has passed ohmmeter resistance checks may still have repeated overload or short circuit protector trips. The motor may have a weakened winding that shorts to ground when the compressor is called on to run. The winding breakdown can be caused because of the system voltage applied to it, heat build up, or mechaniA20 Section A.indd 20 2/6/2008 10:46:43 AM cal stresses. It may also have a terminal board that has developed an insulation breakdown from a terminal to ground or from a terminal to another terminal. A “Hi-Pot” tester can be used in conjunction with an ohmmeter to check for insulation failure on both welded compressors and Copelametic compressors. The terminal board check can only be made on Copelametic compressors. A “Hi-Pot” tester develops a high voltage, low current power source and is used to check for an insulation breakdown that the ohmmeter with its low voltage power source may miss. It measures winding insulation resistance to ground and (where applicable) terminal board resistance from terminal to ground and from terminal to terminal. To measure winding insulation resistance, all wiring is removed from the motor winding terminals. To measure terminal board resistance, all wiring is removed from the terminal board. The “Hi-Pot tester” should never be: 1. Operated alone or by an inexperienced service person. 2. Set at a voltage of more than twice the compressor operating voltage plus 1000 volts. 3. Be set for more than 5 milliamps without consulting Emerson Climate Technologies, Inc. 4. Applied for more than the time it takes to obtain a reading (no more than a few seconds). 5. Used as a phase-to-phase winding check. 6. Used on any other part of the compressor. 7. Used when the compressor (system) is in a vacuum. A21 Section A.indd 21 2/6/2008 10:46:43 AM SECTION B ELECTRONIC MOTOR PROTECTION Scroll Compressor Applications All Emerson Climate Technologies, Inc. Electronic Motor Protectors are manufactured by Kriwan Industries and Texas Instruments. Scroll Compressor Applications In all applications using Copeland Scroll® compressors, each protector monitors motor temperature, supply power voltage. In all applications, utilizing the Kriwan Module, the motor temperature is monitored using 4 positive temperature coefficient sensors (PTC) wired in series. Four sensors are embedded in the motor and one is located inside the scroll set and is used to monitor the discharge gas temperature. The sensors have a positive temperature coefficient, and their resistance increases as the internal temperature of the compressor motor rises. The control module will compare the sensor resistance to a predetermined safe level; and if the total sensor resistance is too high, the module control contact opens and breaks the circuit for the contactor coil control voltage, which then opens the contactor and removes line voltage from the compressor. After a trip, when the motor has cooled to a level that allows for the sensor resistances to return to safe levels, the module will reset and close the control contacts, which will allow the motor to restart. All motor protector modules monitor power supplied to the module and will trip if the power supplied to T1-T2 terminals are too low. B1 Section B.indd 1 2/6/2008 10:48:20 AM In refrigeration applications using scroll compressors, each protector additionally monitors 3 phase incoming power phase rotation and phase loss. The module is continuously monitoring the phases by checking the phase sequencing. If the phase drops below a level that is detectable by the electronics, the module will detect a phase loss and will trip. The module monitors the phase angle differences between the phases. The supply voltage can be 24VDC, 24VAC or 120/240VAC depending on the model of motor protector module. Refer to AE Bulletin AE 4-1302 and AE 4-1318 for specifications. Semi-Hermetic Compressor Applications In all applications using Semi-Hermetic compressors, each protector monitors motor temperature, supply power voltage. Each protector consists of three temperature sensors (embedded in the compressor motor windings) connected to an electronic control module. The sensors have a positive temperature coefficient, and their resistance increases as the internal temperature of the compressor motor rises. The control module compares the sensor resistance to a predetermined safe level; and if any sensor resistance is too high, the module control contact opens and breaks the circuit for the contactor coil control voltage, which then opens the contactor and removes line voltage from the compressor. After a trip, when the motor has cooled to a level that allows for the sensor resistances to return to safe levels, the module will reset and close the control contacts, which will allow the motor to restart. B2 Section B.indd 2 2/6/2008 10:48:26 AM All motor protector modules monitor power supplied to the module and will trip (open the contacts between M1 and M2) if the power supplied to L1-L2 terminals are too low. See AE Bulletin AE 10-1264 for specifications and wiring diagrams. Screw Compressor Applications In all applications using Screw compressors, each module monitors motor temperature, phase sequence control for direction of rotation, manual reset lock-out and oil temperature protection by PTC sensor. In all applications, the motor temperature is monitored using nine sensors embedded into the motor windings which are in series and connected to the module. The sensors have a positive temperature coefficient and their resistance increases as the internal temperature of the compressor rises. The control module compares the sensor resistance to a predetermined safe level and if any sensor resistance is too high. The module control contact opens and breaks the circuit for the contactor coil control voltage, which then opens the contactor and removes line voltage from the compressor. After a trip, the module “must” be manually reset by interruption of the supply voltage to the module for a minimum of 2 seconds. The other features of the module are: Direction of Rotation / Phase Sequence. When the module senses incorrect rotation or a phase sequence fault the module will immediately shutdown the compressor and lockout. After the correction of the fault, the module must be manually reset. Oil protection by the PTC sensor. An oil sensor is installed in the oil sump of the compressor and pre-wired B3 Section B.indd 3 2/6/2008 10:48:26 AM to the module in series with the motor windings PTC’s. If the temperature of the oil rises to an unsafe condition, the compressor will shutdown. The supply voltage can be 24VDC, 24VAC, 120volt or 220volt. Refer to AE Bulletin AE4-1322 and/or Operating Instruction 2001-71 for specifications. Type Of Protection The Motor Protector Provides: Motor Over Temperature and Running Over Current • It protects the compressor by opening it’s control contact when it senses dangerous motor over temperatures and/or over currents, which convert to over temperatures. Primary Single Phasing • The protector sensors detect the sharp rise of temperature in compressor motor windings caused by the high current resulting from a transformer primary single phase condition. Voltage Unbalance • The protector protects against dangerous over-currents caused by system voltage unbalance. Low Voltage Protection • The electronic motor protector is designed so that it will not allow the compressor to start with low voltage at the protector module. When running, if the module voltage drops below operating minimums, the module control contact will immediately open and a two-minute delay before a restart is attempted. If any of these occurrences result in a dangerous motor temperature rise, the protector will immediately open it’s control contact. B4 Section B.indd 4 2/6/2008 10:48:26 AM Short Cycle Protection • Since the electronic protector has been designed to provide a two-minute time delay before restart after a low voltage or no voltage condition, it can be used as protection against compressor short cycling. For short cycling protection, the compressor control circuit must be designed so the temperature or pressure controller turns the electronic protector power on and off, and the protector contact control the compressor contactor. Each time protector power is cycled, it provides a two-minute time delay before it’s contact closes and restarts the compressor. Phase Loss Protection • The scroll refrigeration module and the screw module will sense the correct phase sequence of L1, L2 and L3 incoming power. The three phase power must be wired in the correct 120 degree phase sequence that will ensure the compressor will start and operate in the correct clockwise rotation. When the module trips on phase loss, a delay of 5 minutes is activated and then there is a new attempt to restart. If all three phases are present, then the compressor will continue to run. If not the module will lock out. There can be 10 attempts to restart before the module will lock out and then only can be reset by reestablishing incoming power to the module. ELECTRONIC PROTECTOR SPECIFICATIONS: Low Voltage Protection 24 VAC Module (Texas Instruments) Cut-Out Voltage is 16 volts plus or minus 1.5 volts at normal ambients. B5 Section B.indd 5 2/6/2008 10:48:26 AM Cut-In Voltage is 2 volts higher than cut-out. 120 VAC Module Cut-Out Voltage is 85 volts plus or minus 4.5 volts at normal ambients. Cut-In Voltage is 4 volts higher than cut-out. 240 VAC Module Cut-Out Voltage is 170 volts plus or minus 8 volts at normal ambients. Cut-In Voltage is 4 volts higher than cut-out. For all Modules, the low Voltage Response Delay is .2 seconds plus or minus .15 seconds. Off Cycle Timer 120 seconds plus or minus 15 percent at normal ambients. Contact Rating The TI (15AA) and the Kriwan (INT369) have a contact rating of 275VA for either 120 VAC or 240 VAC. The 24VAC module has a rating of 72VA. Sensor Resistances See individual protector check-out procedures. B6 Section B.indd 6 2/6/2008 10:48:27 AM B7 Section B.indd 7 2/6/2008 10:48:27 AM B8 Section B.indd 8 2/6/2008 10:48:28 AM B9 Section B.indd 9 2/6/2008 10:48:29 AM B10 Section B.indd 10 2/6/2008 10:48:29 AM B11 Section B.indd 11 2/6/2008 10:48:29 AM B12 Section B.indd 12 2/6/2008 10:48:29 AM SECTION C FUSE SELECTION FOR WELDED COMPRESSORS AND COPELAMETIC COMPRESSORS Motor Running Overload Protection and Branch Circuit Short Circuit Protection are required for every compressor electrical branch circuit. These are detailed in Articles 430 and 440 of The National Electrical Code (NEC). All installations and fuse selections must conform to the NEC and any specific local code requirements. In case of questions, contact a qualified electrician. The fuse selection procedures of the Electrical Handbook are based on time delay (dual element) sizes that will meet the requirements of most compressor installations. The selections conform to the National Electrical Code short circuit requirements for single motor protection. The manufacturer of the compressor system should be consulted in cases of multiple motor or group fusing, extreme ambient temperatures, or unusual operating conditions where a larger fuse size than recommended may be required. Each compressor nameplate lists compressor data that is needed to size short circuit protection: The Phase of the motor, Locked Rotor Amps (LRA), and Rated Load Amps (RLA). (RLA is not provided on welded compressor nameplates.) This data is also available in Section F. C1 Section C.indd 1 2/5/2008 8:00:59 AM The Electrical Handbook Fuse Selection Charts adjust this nameplate data so that all that is necessary for standard compressor short circuit time delay fuse protection sizing is to answer the Selection Chart questions, determine a multiplier for RLA, and size the compressor fuse accordingly. FUSE SELECTION PROCEDURE CHART FOR WELDED COMPRESSORS AND COPELAND SCROLL COMPRESSORS 1. Determine Rated Load Amps (RLA) from nameplate or Section F. 2. Determine Locked Rotor Amps (LRA) from nameplate or Section F. 3. Divide LRA/RLA for Inrush Ratio. 4. If fuse ambient temperature is greater than 120°F, multiply Inrush Ratio by 1.08. 5. For Single Phase compressors, multiply RLA by: 1.6 if Inrush Ratio is 5 or less, or 1.7 if Inrush Ratio is more than 5. 6. For Three Phase compressors, multiply RLA by: 1.5 if Inrush Ratio is 4 or less, or 1.6 if Inrush Ratio is more than 4. 7. Use the next higher Time Delay fuse rating above the adjusted RLA value calculated in step 5 or step 6. NOTE: IN NO CASE MAY FUSE RATING EXCEED 225% OF COMPRESSOR RLA! C2 Section C.indd 2 2/5/2008 8:01:07 AM FUSE SELECTION PROCEDURE CHART FOR COPELAMETIC COMPRESSORS 1. Determine Rated Load Amps (RLA) from nameplate or Section F. 2. Determine Locked Rotor Amps(LRA) from nameplate or Section F. 3. Divide LRA/RLA for Inrush Ratio. 4. If fuse ambient temperature is greater than 120°F, multiply Inrush Ratio by 1.08. 5. For Single Phase compressors, multiply RLA by: 1.5 if Inrush Ratio is 5 or less, or 1.6 if Inrush Ratio is more than 5. 6. For Three Phase compressors, multiply RLA by: 1.4 if Inrush Ratio is 4 or less, or 1.5 if Inrush Ratio is more than 4. 7. Use the next higher Time Delay fuse rating above the adjusted RLA value calculated in step 5 or step 6. NOTE: IN NO CASE MAY FUSE RATING EXCEED 225% OF COMPRESSOR RLA! C3 Section C.indd 3 2/5/2008 8:01:07 AM SECTION D COMPRESSOR NOMENCLATURE TOPICS Welded Compressors .................................................. D2 HFC Welded Compressors.......................................... D4 A-Line .......................................................................... D6 CRKQ, CIKQ ............................................................... D8 CR7, CR6, CRKF, CS, CF ......................................... D10 Copelametic® ............................................................. D12 Copeland Discus™ ..................................................... D14 Refrigeration Copeland Scroll® .................................. D16 A/C Copeland Scroll®................................................. D18 Condensing Unit (All models except M-Line) ............ D20 M-Line Condensing Unit ............................................ D22 Copeland Screw™ ...................................................... D24 This section contains current information on Copeland® brand products. Information on obsolete models can be obtained from your local Emerson Climate Technologies, Inc. wholesaler. For individual model designations, visit On-Line Product Information at www.emersonclimatecustomer.com. NOMENCLATURE • WELDED COMPRESSORS Code E F R T S Description = High Efficiency = Low Temperature = High Temperature = Two Speed = Medium Temperature X X X X - XXXX Comp. Motor Rating Compressor Family Series Either a number or a letter established for each product model. Displacement A letter only, arbitrarily assigned for each different displacement within any one family series. Model Variation A number only, assigned to indicate different model types within any one family series. D2 Nominal (HP) Code ¼ 1/3 ½ ½ ¾ 1 1 1-1/4 1-1/2 1-3/4 2 2-1/4 2-3/4 3 3-1/2 4 4-1/2 5 7-1/2 9 10 12 0025 0033 0050 0051 0075 0100 0100 0125 0150 0175 0200 0225 0275 0275 0350 0400 0450 0500 7500 0900 1000 1200 NOMENCLATURE • WELDED COMPRESSORS Compressor Motor Protection Compressor Motor Types Phase Description Type Protection Code 1 Capacitor Run - Capacitor Start C 1 Induction Run - Capacitor Start I 1 Capacitor Run - Permanent Split Capacitor P 3 Three Phase T - X X X Code External Inherent ProtectionOne Protector (Line Break) Use with Contactor A Internal Thermal Protection – Electronic Sensors; and Control Module External Use with Contactor S Internal Inherent Protection – One Protector (Line Break) F - X X X Electrical Codes 60 HZ 115-1 230-1 208/230-3 460-3 575-3 265-1 208/230-1 200/230-3 50HZ Code 200/240-1 200/220-3 380/420-3 500-3 220/240-1 380/420-3 200-1 220/240-1 200/240-3 A B C D E J M V Z 5 (Refer to model data or nameplate for specific nominal voltage.) Product Variations Numbers will be assigned as follows: 1. Number – 100 is standard compressor used in Copeland brand Condensing units. 2. Number – 200 indicates a STANDARD Compressor and Component Parts B/M and Model No. 3. Number – 700 and –900 series indicate OEM and Wholesaler service B/M and model number. 4. Number – 201 and larger will be assigned for all other variations of a given model. D3 NOMENCLATURE • HFC WELDED COMPRESSORS Code R S F T V Description =High or Medium Temperature, Air Conditioning and Heat Pump =Medium Temperature =Low Temperature =Two Speed =Variable Speed Oil Identifier “E” designates Polyol Ester. No digit if Mineral Oil X X X X X X X Model Variation A number or letter, assigned to indicate different model types within any one family series. Compressor Family Series Either a number or a letter established for each product model. Compressor nominal capacity at rating conditions to two significant digits. D4 Capacity Multiplier C = 100 K = 1000 NOMENCLATURE • HFC WELDED COMPRESSORS Compressor Motor Types - Phase Description Code 1 1 1 3 Capacitor Run – Capacitor Start Induction Run – Capacitor Start Capacitor Run – Permanent Capacitor Run – Split Capacitor C I P T X X X Bill of Material Product Variations - X X X Typical Electrical Codes 60 HZ 50HZ Codes 115-1 230-1 208/230-3 460-3 575-3 265-1 208/230-1 200/230-3 200/240-1 200/230 380/420-3 550-3 220/240-1 220/240-3 380/420-3 200-1 220/240-1 200/240-3 A B C D E J R M V Z 5 (Refer to model data or nameplate for specific nominal voltage.) Compressor Motor Protection Type Code External Inherent ProtectionOne Protector (Line Break) Use with Contactor A Internal Inherent ProtectionOne Protector (Line Break) Use with Contactor F D5 NOMENCLATURE • A-LINE COMPRESSORS Application Range Code Description Rating Point S Medium & Extended Temperature R-404A, R-22 Extended Medium R-134a, R-404A High Temperature R-134a -10/120 45/130 F R 20/120 Compressor Shell Series A S E 2 4 C 3 E Compressor Family Series Capacity Compressor nominal capacity at 60 Hertz rating condition to two significant digits. Capacity Multiplier C: 100 K: 1,000 Model Series Variation A number or letter arbitrarily assigned to indicate different model types within any one family series. Oil Identifier “E” designates Polyol Ester. D6 NOMENCLATURE • A-LINE COMPRESSORS Compressor Motor Protection Type Protection Code Internal Thermal Protection – Electronic Sensors; and Control Module External S Internal Inherent Protection – One Protector (Line Break) Use with Contactor F External Inherent Protection – One Protector (Line Break) Use with Contactor A Compressor Motor Types Phase 1 1 1 Description Capacitor Run – Capacitor Start Induction Run – Capacitor Start Capacitor Run – Permanent Split Capacitor Three Phase Induction Run – Split Phase 3 1 - I Product Variations Three-digit Bill of Material number that indicates compressor configuration and may include accessories. Code A C I P T S A – 2 0 1 Voltage Ranges (Typical) Voltage Family C, R A All All All All C, R A C, R A All C 60 Hertz Rating 50 Hertz Rating Code Rating Min. Max. Rating Min. Max. A A C D E J V V Z Z 5 T 115-1 115-1 208/230-3 460-3 575-3 265-1 208/230-1 208/230-1 200/230-3 - 103 103 207 414 518 239 197 187 187 - 127 127 253 506 633 292 253 244 253 - 100 200/220-3 380/420-3 500-3 220/240-1 200-1 200-1 220/240-1 220-240-1 200-240-3 200/240-1 90 180 342 450 198 180 180 198 198 180 180 110 240 462 550 264 200 220 264 254 264 252 BTU Model Families 22 134a 404A 507 A R CRK6 CRKQ CS X X X X X X X X X X X D7 NOMENCLATURE • CRKQ, CIKQ MODELS Compressor Family Series Letter “C” established for this family of compressors. Capacity Compressor nominal 60 Hertz capacity at ARI rating condition to two significant digits. X Code R X X X Indicates compressors with polyol ester oil. X Application Range Description High and medium temp. Model Series Variation Letter “Q” assigned to indicate “Quiet Compressors.” Capacity Multiplier K = 1000 D8 X E NOMENCLATURE • CRKQ, CIKQ MODELS Compressor Motor Types Phase Description Code 1 Capacitor Run – Permanent Spilt Capacitor Three Phase General3 Lead Single Voltage 6 Lead Part Winding P 3 T Product Variations Three-digit Bill of Material number that indicates compressor configuration and accessories included. -X X X - X X X X X Typical Electrical Codes 50 HZ 200-1 200/240-1 220/240-1 380/420-3 200/240-3 60 HZ 208/230-1 460-3 200/230-3 Code V T Z D 5 External Variations Optional alpha letters that indicate external accessories. Compressor Motor Protection Type Protection Internal inherent protection – One protector, Use with contactor (single or three phase) Code F D9 NOMENCLATURE • CR7, CR6, CRKF, CS, CF MODELS Compressor Family Series Either a number or a letter established for each product model. Compressor nominal capacity at rating conditions to two significant digits. Indicates compressors with polyol ester oil. X X X X X X E Application Range Code Refrig. R R-22 S R-404A F R-404A Description Model Variation A number or letter, assigned to indicate different model types within any one family series. High Temp. A/C & Heat Pump Med. Temp. Refrigeration Low Temp. Refrigeration Capacity Multiplier K = 1000 D10 NOMENCLATURE • CR7, CR6, CRKF, CS, CF MODELS Compressor Motor Types Phase Description Code 1 Capacitor Run – Permanent Split Capacitor P 3 Three Phase General – 3 Lead Single Voltage 6 Lead Part Winding (575 Volt) T Product Variations Numbers will be assigned as follows: 1. Number –230 indicates a standard compressor B/M and model number. 2. Number –270 indicates a standard compressor B/M with crankcase heater. 3. Number –500 series indicates international standard compressor B/M and model number. 4. Number –730 indicates a standard OEM service B/M and model number. 5. Number –700 and –900 series indicate standard OEM and Wholesaler service B/M and model number. 6. For B/M different from –230, -270, and –730, contact Emerson Climate Technologies, Inc. Sales and Service. - X X X - X X X Electrical Codes 60 Hz. 208/230-3 460-3 575-3 265-1 208/230-1 200/230-3 50 Hz. Code 200/220-3 380/420-3 500-3 220/240-1 380/420-3 200-1 220/240-1 360/460-3 180/260-1 200/240-3 C D E J M V Z 1* 2* 5 * Wide voltage range for India produced products Compressor Motor Protection Type Protection Code Internal Inherent Protection – One Protector (Single or three phase) F D11 NOMENCLATURE • COPELAMETIC MODELS Air-Cooled Code Description A = Std. Air Cooled Code R Code W Refrigerant-Cooled Description = Std. Refrig. Cooled Water-Cooled Description = Std. Water Cooled K A T A – 0 1 0 0 Compressor Family Series Either a number or a letter established for each product model. Comp. Motor Rating Displacement and Valve Plate A letter only, assigned for each different displacement valve plate combination within any one family series. Model Variation A number assigned to indicate major variations within any one family series. D12 Nominal (HP) Code 1/3 ½ ½ ¾ 1 1-1/2 2 2 3 3 3 4 5 20 25 30 35 40 0033 0050 0051 0075 0100 0150 0200 0210 0300 0310 0311 0400 0500 2000 2500 3000 3500 4000 NOMENCLATURE • COPELAMETIC MODELS Compressor Motor Types Phase Description Code 1 Capacitor Run – Capacitor Start 1 Induction Run – Capacitor Start C I 3 Three Phase T 3 Wye (star) Delta E 3 6 Lead Part Winding or Across The Line – except 575V F Product Variations Numbers will be assigned as follows: 1. Number –100 is standard compressor used in Copeland brand Condensing Units. 2. Number –200 indicates a STANDARD Compressor Parts B/M and Model No. 3. Number –201 and larger will be assigned for all other variations of a given model. 4. Number –800 indicates a standard replacement Compressor and Component Parts B/M and Model No. –240 volt control. 5. Number –801 indicates a standard replacement Compressor and Component Parts B/M and Model No. –120 volt control. - C A V - 2 0 1 Electrical Codes Compressor Motor Protection Type Protection Code External Inherent ProtectionOne Protector, (Line Break) Use with Contactor A Internal Inherent ProtectionOne Protector (Line Break) Use with Contactor F Internal Thermal ProtectorsElectronic Sensors; and Control Module External Use with Contactor S 60 Hz. 115-1 230-1 208/230-3 460-3 575-3 208/230/460-3 230/460-3 200-3 208/230-1 200/220/380-3 50 Hz. Code 200/220-3 380/420-3 550-3 200/380/400-3 210/240/380/420-3 380/420-3 200/400-3 200/220-1 220/240-1 200/380-3 A B C D E K L M N U V Z 8 D13 NOMENCLATURE • COPELAND DISCUS MODELS Primary Application Range R = ARI High Temp, Rated @ 45/130 S = ARI Med Temp, Rated @ 20/120 F = ARI Low Temp, Rated @ -25/105 Compressor Cooling Code Description A D R T W Air cooled Discus Refrigerant cooled Std. two stage Water cooled May also be “0” (Mineral Oil) “E” (POE Oil) “L” (Less Oil) Tandem Style Models Indicated by the digit representing the comp. model series connected in tandem with a comp. of the model series indicated by the first digit. XXXX X XXXX Nominal Capacity at Rating Condition 2 numeric characters Compressor Family Series Either a number of a letter extablished for each product family. Capacity Multiplier K - 1,000 M - 10,000 Displacement and Valve Plate A letter only, arbitrarily assigned for each different displacement valve plate combination within any one family series Model Variation Either a number or a letter assigned to indicate major variations within any one family series. D14 NOMENCLATURE • COPELAND DISCUS MODELS Compressor Motor Types Single Phase Motors Capacitor run - capacitor start Induction run - capacitor start Induction run - split phase Induction run - capacitor start, low torque Three Phase Motors General 3 Lead single voltage 6 Lead part winding (575 volt) 9 Lead dual voltage Star (wye) delta 6 Lead motors Part winding or across the line Code C I S X Product Variations Numbers will be assigned as follows: 1. Numbers -001 through -199 are reserved for sub-b/m numbers. 2. Numbers -200 indicates a standard compressor and component parts b/m and model no. 3. Numbers -201 and larger will be assigned for all other variations of a given model. Code T E F - X X X X X X Electrical Codes 60 Hz. * 50 Hz. (Typical) Code Compressor Motor Protection Type Protection Code External inherent protection-one protector (line break) use with contactor A Internal inherent protection-one protector use with contactor F Internal thermostat(s); and ext. supplementary protector(s) use with contactor H Internal thermostat(s); and three ext. supplementary protectors use with contactor L Internal thermal protectorselectronic sensors; and control module external. Use with contactor. S Internal thermal protectors-electronic sensors; and control module external. Use with contactor (For European use only) W 115-1 230-1 208-230-3 460-3 575-3 --208-1 -208/230/460-3 --230/460-3 ----200-3 208-230-1 -Misc. A.C. Ratings --200-1 100-1 200-230-3 230-3 380 200/220/380 100-1 200-1 200/220-3 380/400-3 500-3 115-1 230-1 200-1 208/230-1 200/400-3 210/240/380-3 380/420-3 200/400-3 200/380-3 200/240-3 220-1 200-1 -200-1 200/220-3 X 500-3 220/240-1 200-1 100-1 --346 200/346 A B C D E F G H I K L M N P R S T U V W Y Z 3 4 5 6 7 8 D15 NOMENCLATURE • REFRIGERATION SCROLL MODELS Compressor Family Series Either a number or a letter established for each product model. Z = Scroll Compressor nominal capacity at rating conditions to two significant digits Type of Oil G = PAG E = POE “blank” = Mineral Oil X X X X X X X X X Capacity Multiplier M: 10,000 K: 1,000 C: SCFM Application Range Code Description B High/Medium Temperature Medium Temp. Low Temp. with Injection port Helium Marinized Gas Booster Asia Condensing Unit Heat Pump S F C M N X H Model Variation A number or letter, assigned to indicate different model types within any one family series. Optional Modulation Code D H HV D16 Description Digital Horizontal Horizontal Variable Speed NOMENCLATURE • REFRIGERATION SCROLL MODELS Product Variations Numbers will be assigned as follows: 1. 230/231 - Standard Compressor & Component Parts w/ Flag Terminal 2. 250/251 - Standard Compressor & Component Parts w/ Screw Terminal 3. 240/241 - Rotalock Compressor & Component Parts w/ Flag Terminal 4. 261/265 - Rotalock Compressor & Component Parts w/ Screw Terminal 5. 900 series indicates standard OEM and wholesaler service. 6. Other numbers designate variations. Compressor Motor Types Phase Description Code 1 Capacitor Run – Permanent Split Capacitor P 3 General 3 Lead Single Voltage 6 Lead Part Winding (575 Volt) T - X X X - X X X Voltage Ranges (Typical) Voltage Code C D E V 5 7 J R 60 Hertz Rating Rating 208/230-3 460-3 575-3 208/230-1 200/230-3 380-3 265-1 - 50 Hertz Rating Min. Max. 187 414 518 197 180 342 239 - 253 506 633 253 253 418 292 - Rating 200-3 380/420-3 500-3 200-1 200/220-3 220/240-1 220/240-3 Min. Max. 180 342 450 180 180 198 180 220 462 550 220 242 264 264 Compressor Motor Protection Type Protection Code Internal Inherent ProtectionOne Protector Use with Contactor (Single or Three Phase) F External Electronic Protection (Three Phase) W D17 NOMENCLATURE • A/C SCROLL MODELS Compressor Family Series Either a number or a letter established for each product model. Type of Oil E – 3MA POE Oil Compressor nominal capacity at rating conditions 2 – 3 numeric characters. Modulation D – Digital DU – Digital Uneven Tandem DT – Digital Even Tandem H – Horizontal I – Heating J – Digital Heating S – UltraTech T – Even Tandem U – Uneven Tandem V – Velocity Variable X X X X X X X X X Application Range Code Refrig. Capacity Multiplier K: 1,000 M: 10,000 Description P R-410A High Temperature Ultra High Pressure R R-22/407C/134a High Temperature Model Variation A number or a letter, assigned to indicate different model types within any one family series. D18 NOMENCLATURE • A/C SCROLL MODELS Compressor Motor Types Phase Description Code 1 Capacitor Run – Permanent Split Capacitor P 3 General 3 Lead Single Voltage 6 Lead Part Winding (575 Volt) T Product Variations 1. 130/135/160 - Molded Plug 2. 230/235/260 - Quick Terminals T-box 3. 250/265 - Screw Terminals T-box 4. 7xx/9xx - T-box Service 5. 8xx - Molded Plug Service - X X X - X X X Compressor Motor Protection Electrical Codes Type Protection Code 60 Hz. Internal Inherent ProtectionOne Protector Use with Contactor (Single or Three Phase) F External Electronic ProtectionKriwan Module (Three Phase) W 208/230-3 460-3 575-3 265-1 208/230-1 Misc. 200/230-3 380-3 50 Hz. 200-3 380/420-3 220/240-1 380-420-3 220/240-3 Misc. 200/220-3 220/240-1 Code C D E J M R V X 5 7 Z D19 NOMENCLATURE • CONDENSING UNIT Design Series and Refrigerant Letters (Except K,L,M) K, L M Numbers (Except 6 & 7) 6, 7 X, 9 R-12 R-22 LT R-22 LT Discus R-22/R-502 R-12/R-502 Special Design All Models Except M-Line (Different series type may indicate a major design revision. New HFC Refrigerant Indicator Pressure Rating Approved Refrigerants Standard Models Medium High and Medium High T P J Special Designs R N E X X X X - X X X X Application Temperature* Temperature Range Condensing Unit Family Series Type of Design Type Code Air Cooled No condenser Water cooled Evaporating Pan Base Discus A N W E D Typical Motor Rating Code Nominal (HP) Code High Temperature 45ºF Max.; 0ºF Min. H Medium Temperature 25ºF Max.; -5ºF Min. M Medium Temperature 25ºF Max.; -25ºF Min. F 1/4 1/3 1/2 3/4 1 1-1/2 2 2-1/2 3 3-1/2 4 5 6 7-1/2 9 10 15 20 22 25 27 30 40 50 60 70 80 0025 0033 0050 0075 0100 0150 0200 0250 0300 0350 0400 0500 0600 0750 0900 1000 1500 2000 2200 2500 2700 3000 4000 5000 6000 7000 8000 Low Temperature 0ºF Max.; -40ºF Min. L Extra Low Temperature -20ºF Max.; -40ºF Min. E Two Stage 0ºF Max.; -40ºF Min. T Two Stage (Extra Low) -30ºF Max.; -80ºF Min. U Commercial Application High & Med. Temperature Single Refrigerant C Dual Application R-22 HT, R-502 MT D Multiple Application R-12 H/MT, R-502 LT B NOTE: Limited or extended range will be shown in performance data tables. D20 *NOTE: Left hand position may contain a letter indicating a revision (on units less than 10 HP). Right hand position may contain the letter “Z” indicating a Glacier™ scroll compressor. NOMENCLATURE • CONDENSING UNIT Compressor Motor Type Single Phase Motors Code Capacitor Run-Capacitor Start Induction Run-Capacitor Start Induction Run-Split Phase Induction Run-Capacitor Start, Low Torque Capacitor Run-Permanent Split Capacitor Bill of Material Product Variations C I S X P Three Phase Motors Variation (B/M) Number UL/CSA Eligibility 001 thru 099 Intended for UL Listing and CSA Certified. 100 thru 299 Intended for UL Recognition and CSA Certified. 300 thru 399 Not Eligible for either UL Listing, LU Recognition, or CSA Certified. Code T General 3 Lead Single Voltage 6 Lead Part Winding 575 V 9 Lead Dual Voltage Star (Wye) Delta 6 Lead Motors Part Winding or Across the Line E F - X X X - X X X Typical Electrical Codes Compressor Motor Protection Type Protection Code External Inherent Protection – One Protector, (Line Break) Use with Contactor (single or three phase) A Internal Inherent Protection – One Protector, Use with Contactor. (single or three phase) F Internal Thermostat(s); and External Supplementary Protector(s). (Two for 3Ø, one for 1Ø.) Use with Contactor. H Internal Thermostat(s); and Three External Supplementary Protectors. Use with Contactor. L Internal Thermal Protectors – Electronic Sensors; and Control Module External. Use with Contactor. S Internal Thermal Protectors – Electronic sensors; and control module external. Use with contactor. (For European use only). W 60 Hz. 50 Hz. Code 115-1 230-1 208/230-3 460-3 575-3 208-1 265-1 208/230/460-3 230/460-3 All D.C. Ratings 200-3 208/230-1 Misc. A.C. Ratings 200-1 100-1 200/230-3 230-3 100-1 200-1 200/220-3 380/400-3 500-3 115-1 230-1 200-1 208/230-1 220/240-1 200/400-3 210/240/380-3 380/420-3 200/400-3 A B C D E F G H I J K L M N O P R S T U V W X Y Z 3 4 5 6 200/380-3 200/240-3 220-1 200-1 200-1 200/220-3 200/220-3 220/240-1 200-1 100-1 - *NOTE: When applicable, specific 50 Hz ratings (not necessarily identical to typical shown above) will be shown as alternate on 60 Hz rated models. D21 NOMENCLATURE • M-LINE CONDENSING UNIT Base Size A – 13” x 17” Steel B – 10” x 12” Steel E – 14-1/4” x 16” Copevap F – 12” x 17-1/2” Steel G – 10” x 21” Steel H – 6-1/2” x 15-1/2” Steel K – 15-1/2” x 18” Steel N – 10” x 12” Copevap P – 11” x 20” Copevap Y – 10-1/4” x 14” Steel Indicates M-Line Condensing Unit Series M A A H Temperature Application H High Temperature M Medium Temperature L Low Temperature CFC & HCFC Construction & Refrigerant Indicator (All Model Codes Signify UL Recognized Units) R-12 A G I J K L U V R-22 R-502 E M Y D P Q S T Construction Style Power Cord Receiver Fan Guard BX X X X X X X X X X X X X X X X X New HFC Refrigerant Indicator No reference to Construction and UL or CSA Pressure Rating of Approved Refrigerants Medium High and Medium High D22 M-Line 2 3 4 NOMENCLATURE • M-LINE CONDENSING UNIT Common Bill of Material Variations CFC & HCFC Models 010 100’s 200’s Wholesale (Single Pack) OEM (Single Pack) OEM (Multi Pack) HFC Models Hot Gas Evaporator Tube O E M New HFC products have the same B.O.M. structure as F-Line. No Tube Epoxy Coated Copper Tube Monel Tube - 0 033 - IAA - XXX Nominal HP M-Line 013 017 020 to 023 024 to 027 032 to 037 049 to 051 075 100 HP 1/8 1/6 1/5 1/4 1/3 1/2 3/4 1 Voltage (Start Torque) IAA SAA PAA IAV CAV IAS IAZ SAZ 115-1-60 115-1-60 115-1-60 208/230-1-60 208/230-1-60 220-1-50 220/240-1-50 220/240-1-50 (High) (Low) (Low) (High) (High) (High) (High) (Low) D23 NOMENCLATURE • COPELAND SCREW COMPRESSOR Body Type Code C H D Description Lubricant O = R22 E = HFC Compact Semi-hermetic Open Drive S C H 2 - 9 0 0 0 Copeland Screw Compressor Comp. Motor Rating Temperature Application H = High M = Medium L = Low A = Optimized for R-134a (COMPACT ONLY) Model Variation A number assigned to indicate major variations within any one family series. A number assigned to individual major variations within any one family series, for screw compressors 1 or 2. D24 Nominal (HP) Code 20 25 30 35 40 50 60 70 75 80 80 90 90 110 125 140 160 180 210 240 280 300 200 250 300 350 400 500 600 700 750 800 801* 900 901* 11H 12H 14H 16H 18H 21H 24H 28H 30H *801 and 901 Frame 2 SCA2 Only NOMENCLATURE • COPELAND SCREW COMPRESSOR Compressor Motor Types Phase Description Code 3 6 Lead Part Winding or Across The Line – except 575 V F 3 Misc. 3 Phase • Single voltage 3 lead • Dual voltage 9 lead • 575 V 60 H/500 V 50 HZ 20 H.P. & up 6 lead Part Winding T 3 Star (WYE) Delta E Product Variations Numbers will be assigned as follows: 1. Number –200 indicates a STANDARD Compressor and Component Parts B/M and Model No. 2. Number – 800 indicates a standard replacement compressors and component parts and model no. - F W D - 2 0 0 Compressor Motor Protection Type Protection Internal Thermal ProtectorsElectronic Sensors; and Control Module External Use with Contactor Electrical Codes Code 60 Hz. 50 Hz. Code W 208/230-3 460-3 575-3 208/230/460-3 200/220-3 380/420-3 550-3 200/380/400-3 C D E K D25 SECTION E ELECTRICAL COMPONENT NOMENCLATURE AND DATA TOPICS Potential Relay Nomenclature.....................................E1 G.E. Numbering System .............................................E1 Potential Relay Data ...................................................E2 Current Relay Data .....................................................E7 Start Capacitor Data..................................................E16 Run Capacitor Data...................................................E22 This section contains current information on Copeland® products. Information on obsolete models can be obtained from your local wholesaler carrying Copeland brand products. Section E TOC.indd 1 2/21/2008 7:40:03 AM Potential Relay Nomenclature General Electric has somewhat of a complicated numbering system for potential relays. Without a complete catalog, the numbering designations are not self-explanatory, but a basic understanding of the nomenclature is helpful in identifying potential replacements in an emergency situation. G.E. Numbering System A typical General Electric potential relay number is as follows: 3ARRA3CT6D5 3ARR3 CT 3 D 5 Mounting Position Electrical Specifications Coil Rating Mounting Bracket & Terminal Connection Relay Type E1 Section E TOC.indd 2 2/21/2008 7:40:25 AM Potential Relay Data Wholesaler P/N 940-0001-48 940-0001-53 940-0001-54 940-0001-55 940-0001-56 940-0001-59 940-0001-60 940-0001-62 940-0001-63 940-0001-64 940-0001-69 940-0001-71 940-0001-78 940-0001-79 940-0001-80 940-0001-82 940-0001-83 940-0001-84 940-0001-64 940-0001-88 Copeland® Brand P/N 040-0001-48 040-0001-53 040-0001-54 040-0001-55 040-0001-56 040-0001-59 040-0001-60 040-0001-62 040-0001-63 040-0001-64 040-0001-69 040-0001-71 040-0001-78 040-0001-79 040-0001-80 040-0001-82 040-0001-83 040-0001-84 040-0001-85 040-0001-86 040-0001-87 040-0001-88 GE P/N 3ARR3KC7M5 3ARR3KC10A5 3ARR3KC10V5 3ARR3KC10S5 3ARR3KC3T5 3ARR3KC6W5 3ARR3KC24S5 3ARR3KC5M5 3ARR3KC10C5 3ARR3KC6A5 3ARR3KC4D5 3ARR3KC10B5 3ARR3KC10AS5 3ARR3KC3P5 3ARR3KC2L5 3ARR3KC3U5 3ARR3K6A5 3ARR3K6B5 3ARR3K4B5 3ARR3K4A5 3ARR3J6A5 Pick-up Volts 150 - 160 260 - 280 240 - 260 190 - 200 200 - 220 210 - 230 190 - 200 150 - 160 300 - 320 260 - 280 320 - 340 280 - 300 190 - 200 170 - 180 140 - 150 220 - 240 260 - 280 280 - 300 280 - 300 260 - 280 260 - 280 220 - 240 Drop Out Volts 15 - 45 50 - 110 60 - 121 40 - 105 40 - 90 60 - 125 55 - 115 35 - 77 50 - 110 60 - 121 60 - 135 50 - 110 40 - 105 40 - 90 20 - 45 40 - 90 60 - 121 60 - 121 60 - 135 60 - 135 60 - 121 60 - 121 Cont. Volt Rating 130 375 375 375 332 420 383 253 375 420 500 375 338 332 168 332 420 420 500 500 420 420 Freq. 60 60 60 60 60 60 60 60 60 60 60 60 50 60 60 60 60 60 60 60 60 60 E2 Section E.indd 2 2/26/2008 11:02:10 AM Potential Relay Data Wholesaler P/N 940-0007-00 940-0007-02 940-0007-04 940-0046-18 940-0046-19 940-0046-21 940-0046-22 940-0046-23 940-0140-00 940-0140-07 940-0140-00 940-0140-02 940-0140-03 940-0140-04 940-0140-05 940-0140-06 940-0140-07 940-0140-08 940-0001-48 940-0001-49 Copeland® Brand P/N GE P/N 040-0007-00 040-0007-02 040-0007-04 040-0046-18 040-0046-19 040-0046-20 040-0046-21 040-0046-22 040-0046-23 040-0046-24 040-0140-00 040-0140-07 040-0166-00 040-0166-01 040-0166-02 040-0166-03 040-0166-04 040-0166-05 040-0166-06 040-0166-07 040-0166-08 040-0166-09 3ARR3C7M2 3ARR3C5AA2 3ARR3C24E2 3ARR22J24E5 3ARR22J6D5 3ARR22J5P5 3ARR22J7M5 3ARR22J25AC5 3ARR22J10B5 3ARR22J4AD5 3ARR3KC6AC5 3ARR3T6AC5 3ARR3T4AA5 3ARR3T25S5 3ARR3T3S5 3ARR3T6AA5 3ARR3T10AT5 3ARR3T3AA5 3ARR3KC3L5 3ARR3T7M5 3ARR3T3E5 Pick-up Volts 150 - 160 260 - 280 340 - 360 340 - 360 320 - 340 170 - 180 150 - 160 300 - 320 280 - 300 320 - 340 300 - 320 260 - 280 300 - 320 260 - 280 190 - 200 190 - 200 260 - 280 200 - 220 260 - 280 140 - 150 150 - 160 340 - 360 Drop Out Volts 15 - 45 35 - 77 55 - 125 55 - 125 60 - 121 35 - 77 15 - 45 60 - 133 50 - 110 60 - 135 60 - 121 40 - 90 60 - 121 60 - 135 60 - 130 40 - 90 60 - 121 40 - 105 40 - 90 40 - 90 15 - 45 50 - 100 Cont. Volt Rating 130 228 336 383 420 253 130 400 375 0 378 299 343 395 395 290 343 296 261 290 114 290 Freq. 60 50 60 60 60 60 60 50 60 50 50 50 50 60 60 50 50 50 60 60 60 E3 Section E.indd 3 2/26/2008 11:02:31 AM Potential Relay Data Wholesaler P/N 940-0001-50 940-0001-51 940-0001-52 940-0001-53 940-0001-54 940-0001-55 940-0001-57 940-0001-59 940-0001-60 940-0001-61 940-0001-62 940-0001-63 940-0001-64 940-0001-65 940-0001-66 940-0001-68 940-0001-69 940-0001-70 940-0001-71 940-0001-72 940-0001-73 Copeland® Brand P/N GE P/N 040-0166-10 040-0166-11 040-0166-12 040-0166-13 040-0166-14 040-0166-15 040-0166-17 040-0166-18 040-0166-19 040-0166-20 040-0166-21 040-0166-22 040-0166-23 040-0166-24 040-0166-25 040-0166-26 040-0166-27 040-0166-28 040-0166-29 040-0166-30 040-0166-31 040-0166-32 3ARR3T24E5 3ARR3T5P5 3ARR3T25AC5 3ARR3T10A5 3ARR3T10V5 3ARR3T10S5 3ARR3T23AA5 3ARR3T6W5 3ARR3T24S5 3ARR3T6D5 3ARR3T5M5 3ARR3T10C5 3ARR3T6A5 3ARR3T10AA5 3ARR3T3C5 3ARR3T10AB5 3ARR3T6V5 3ARR3T4D5 3ARR3T3AV5 3ARR3T10B5 3ARR3T6AB5 3ARR3T3AU5 Pick-up Volts 340 - 360 170 - 180 300 - 320 260 - 280 240 - 260 190 - 200 260 - 280 210 - 230 190 - 200 320 - 340 150 - 160 300 - 320 260 - 280 260 - 280 300 - 320 280 - 300 240 - 260 320 - 340 240 - 260 280 - 300 280 - 300 220 - 240 Drop Out Volts 55 - 125 35 - 77 60 - 133 50 - 110 60 - 121 40 - 105 45 - 109 60 - 125 55 - 115 60 - 121 35 - 77 50 - 110 60 - 121 50 - 110 55 - 100 50 - 110 60 - 121 60 - 135 40 - 90 50 - 110 60 - 121 40 - 90 Cont. Volt Rating 336 221 406 375 375 375 262 420 383 420 253 375 420 338 332 338 420 500 299 375 378 299 Freq. 60 60 50 60 60 60 50 60 60 60 60 60 60 50 60 50 60 60 50 60 50 50 E4 Section E.indd 4 2/26/2008 11:02:31 AM Potential Relay Data Wholesaler P/N 940-0001-75 940-0001-77 940-0001-78 940-0001-79 940-0001-80 940-0001-82 940-0001-83 940-0001-84 940-0001-64 940-0001-88 Copeland® Brand P/N GE P/N 040-0166-33 040-0166-34 040-0166-35 040-0166-36 040-0166-37 040-0166-38 040-0166-39 040-0166-40 040-0166-41 040-0166-42 040-0166-43 040-0166-44 040-0166-45 3ARR3T7J5 3ARR3T7AL5 3ARR3T5V5 3ARR3T10AS5 3ARR3T3P5 3ARR3T2L5 3ARR3T3U5 3ARR3K6A5 3ARR3K6B5 3ARR3K4B5 3ARR3K4A5 3ARR3T6A5 3ARR3T6U5 Pick-up Volts 120 - 130 140 - 150 240 - 260 190 - 200 170 - 180 140 - 150 220 - 240 260 - 280 280 - 300 280 - 300 260 - 280 260 - 280 220 - 240 Drop Out Volts 15 - 40 15 - 40 35 - 77 40 - 105 40 - 90 20 - 45 40 - 90 60 - 121 60 - 121 60 - 135 60 - 135 60 - 121 60 - 121 Cont. Volt Rating 130 117 253 338 332 168 332 420 420 500 500 420 420 Freq. 60 50 60 50 60 60 60 60 60 60 60 60 E5 Section E.indd 5 2/26/2008 11:02:31 AM Current Relay Data Wholesaler P/N 940-0088-00 940-0088-03 940-0088-04 940-0088-05 940-0088-06 940-0090-00 940-0090-04 940-0090-06 940-0098-01 940-0098-02 940-0102-02 940-0115-00 940-C411-49 940-C411-18 940-C411-38 Copeland® Brand P/N 040-0088-00 040-0088-03 040-0088-04 040-0088-05 040-0088-06 040-0089-04 040-0089-06 040-0090-00 040-0090-01 040-0090-04 040-0090-05 040-0090-06 040-0090-07 040-0098-01 040-0098-02 040-0102-02 040-0115-00 040-0115-01 040-0115-02 040-0128-01 040-0141-00 040-0141-01 040-0141-02 GE P/N Texas Inst. P/N 6409-26-196 6409-26-176 6409-26-935 6409-26-189 6409-26-900 3CR-203-171B 3CR-203-186B 3CR-206-174B 3CR-206-181B 3CR-206-191B 3CR-206-165B 3CR-206-189B 3CR206-154B 6409-40-935 6409-40-180 6409-51-176 3CR-111-269 3CR-111-239 3CR-111-272 3CR234-181B Max. Pick-up Amps 28.9 14.9 33.6 21.8 42 12.9 22.5 14.1 17.9 27.2 10.4 24.75 8.25 33.6 17.4 14.9 12.2 6.3 13.3 17.9 7.7 3.8 6.2 Min. Drop Out Amps 23.7 12.6 27.8 17.9 36 10.8 18.7 11.9 15.1 22.7 8.6 20.45 6.9 27.8 14.3 12.6 10.2 5.25 11.1 15.1 6.5 3.25 5.25 E6 Section E.indd 6 2/26/2008 11:02:31 AM Current Relay Data Wholesaler P/N 940-C411-47 940-C411-58 940-C411-82 940-C411-52 940-C411-66 940-C411-72 940-C411-73 940-C411-79 940-C411-80 940-C411-83 940-C411-82 940-C411-82 940-C411-82 940-C411-66 940-C411-49 940-C411-45 940-C411-45 940-C411-58 940-C411-83 940-C411-83 940-C411-83 940-C411-13 940-C411-18 Copeland® Brand P/N 040-0141-03 040-0141-04 040-0141-05 040-0141-10 040-0141-14 040-0141-17 040-0141-18 040-0141-20 040-0141-21 040-0141-22 040-0150-01 040-0150-01 040-0150-01 040-0150-02 040-0150-03 040-0150-04 040-0150-04 040-0150-05 040-0150-06 040-0150-06 040-0150-06 040-0150-07 040-0150-08 GE P/N Texas Inst. P/N 9660A-467-1822 9660C-3018-182 9660A-467-183 9660C-3018-183 Max. Pick-up Amps 7.45 9.15 17.8 8.2 11 13.2 13.4 16.5 16.7 18.2 17.8 17.8 17.8 11 7.7 7.1 7.1 9.15 18.2 18.2 18.2 3.25 3.8 Min. Drop Out Amps 6.3 7.7 14.9 7 9.35 11.1 11.4 13.8 14 15.3 14.9 14.9 14.9 9.35 6.5 6 6 7.7 15.5 15.5 15.5 2.75 3.25 E7 Section E.indd 7 2/26/2008 11:02:31 AM Current Relay Data Wholesaler P/N 940-C411-35 940-C411-63 940-C411-89 940-C411-89 940-C411-89 940-C411-89 940-C411-91 940-C411-91 940-C411-91 940-C411-78 940-C411-47 940-C411-61 940-C411-52 940-C411-85 940-C411-85 940-C411-85 940-C411-73 940-C411-72 940-C411-71 940-C411-40 940-C411-38 940-0150-24 Copeland® Brand P/N 040-0150-09 040-0150-10 040-0150-11 040-0150-11 040-0150-11 040-0150-11 040-0150-12 040-0150-12 040-0150-12 040-0150-13 040-0150-14 040-0150-15 040-0150-16 040-0150-17 040-0150-17 040-0150-17 040-0150-18 040-0150-19 040-0150-20 040-0150-21 040-0150-22 040-0150-23 040-0150-24 GE P/N Texas Inst. P/N 9660-467-191 9660C-3018-191 9660A-467-185 9660C-3018-185 Max. Pick-up Amps 5.8 10.3 21.9 21.9 21.9 21.9 24.4 24.4 24.4 15.8 7.45 9.75 8.2 19.2 19.2 19.2 13.35 13.2 12.7 6.5 6.2 21.9 15.8 Min. Drop Out Amps 4.95 8.6 18.2 18.2 18.2 18.2 20.3 20.3 20.3 13.3 6.3 8.2 7 16.2 16.2 16.2 11.35 11.1 10.8 5.5 5.25 18.2 13.3 E8 Section E.indd 8 2/26/2008 11:02:31 AM Current Relay Data Wholesaler P/N 940-C411-55 940-0152-00 940-0152-03 940-C401-82 940-0102-02 940-C401-25 940-C401-35 940-C401-82 940-0152-05 940-C401-58 Copeland® Brand P/N 040-0150-25 040-0150-31 040-0150-31 040-0150-32 040-0150-33 040-0150-34 040-0150-34 040-0150-35 040-0150-35 040-0150-36 040-0150-36 040-0150-37 040-0150-37 040-0152-00 040-0152-03 040-0152-13 040-0159-02 040-0162-00 040-0162-01 040-0162-02 040-0162-03 040-0162-04 040-0162-05 GE P/N Texas Inst. P/N Max. Pick-up Amps 8.5 13.7 13.7 12.1 18.2 11 11 14 14 14.7 14.7 19.9 19.9 7.7 3.76 17.8 14.9 4.65 13.2 5.8 17.8 4.2 9.15 Min. Drop Out Amps 7.15 11.5 11.5 10.3 15.5 9.35 9.35 11.9 11.9 12.5 12.5 16.6 16.6 6.5 3.15 14.9 12.6 3.95 11.1 4.95 14.9 3.55 7.7 E9 Section E.indd 9 2/26/2008 11:02:31 AM Current Relay Data Wholesaler P/N 940-C401-66 940-C401-40 940-0152-03 940-0152-01 940-0152-00 940-0152-04 940-0162-13 940-0162-14 940-0163-00 940-0163-01 940-C411-79 940-C411-70 940-C411-80 940-C411-89 940-C411-91 940-C411-85 940-C411-49 940-C411-83 940-C411-38 940-0088-00 940-0088-02 940-0088-03 940-0088-04 Copeland® Brand P/N 040-0162-07 040-0162-08 040-0162-09 040-0162-10 040-0162-11 040-0162-12 040-0162-13 040-0162-14 040-0163-00 040-0163-01 040-0163-02 040-0163-03 040-0163-04 040-0163-05 040-0163-07 040-0163-08 040-0167-03 040-0167-06 040-0167-22 040-0168-00 040-0168-01 040-0168-02 040-0168-03 GE P/N Texas Inst. P/N Max. Pick-up Amps 11 6.5 3.35 2.29 7.7 3.76 9.75 13.2 9.15 11 16.5 12.1 16.7 21.9 24.4 19.2 7.7 18.2 6.2 28.9 17.4 14.9 33.6 Min. Drop Out Amps 9.35 5.5 2.85 1.96 6.5 3.15 8.2 11.1 7.7 9.35 13.8 10.3 14 18.2 20.3 16.2 6.5 15.5 5.25 23.7 14.3 12.6 27.8 E10 Section E.indd 10 2/26/2008 11:02:32 AM Current Relay Data Wholesaler P/N 940-0088-05 940-0088-07 940-0102-00 940-0102-02 940-0102-03 940-0102-07 940-0163-00 940-C411-83 940-C016-00 940-0102-04 940-C016-03 940-C016-03 940-C016-00 940-0152-01 940-0152-03 940-0152-05 940-C401-25 Copeland® Brand P/N 040-0168-04 040-0168-06 040-0169-00 040-0169-01 040-0169-02 040-0169-03 040-0169-06 040-0171-00 040-0171-06 040-0172-00 040-0172-02 040-0172-03 040-0172-03 040-0172-04 040-0172-04 040-0172-05 040-0172-05 040-C016-00 040-C401-01 040-C401-11 040-C401-14 040-C401-21 040-C401-25 GE P/N Texas Inst. P/N 3CR-763-188B 9660-040-101 9660-040-111 9660-040-114 9660-040-121 9660-040-125 Max. Pick-up Amps 21.8 13.3 28.9 17.4 14.9 33.6 13.3 9.15 18.2 24 24.75 30.3 30.3 18.4 18.4 22.1 22.1 24 2.29 3 3.35 4.2 4.65 Min. Drop Out Amps 17.9 11.1 23.7 14.3 12.6 27.8 11.1 7.7 15.5 19.8 20.45 25.1 25.1 15.4 15.4 18.4 18.4 19.8 1.96 2.56 2.85 3.55 3.95 E11 Section E.indd 11 2/26/2008 11:02:32 AM Current Relay Data Wholesaler P/N 940-C401-35 940-C401-40 940-0152-00 940-C401-58 940-C401-66 940-C401-72 940-C401-82 940-C411-13 940-C411-18 940-C411-35 940-C411-38 940-C411-45 940-C411-47 940-C411-49 940-C411-52 940-C411-61 940-C411-63 940-C411-66 940-C411-71 940-C411-73 940-C411-79 940-C411-82 Copeland® Brand P/N 040-C401-35 040-C401-40 040-C401-49 040-C401-55 040-C401-58 040-C401-66 040-C401-72 040-C401-82 040-C411-13 040-C411-18 040-C411-35 040-C411-38 040-C411-45 040-C411-47 040-C411-49 040-C411-52 040-C411-61 040-C411-63 040-C411-66 040-C411-71 040-C411-73 040-C411-79 040-C411-82 GE P/N Texas Inst. P/N 9660-040-135 9660-040-140 9660-040-149 9660-040-155 9660-040-158 9660-040-166 9660-040-172 9660-040-182 9660B-041-113 9660B-041-135 9660-041-138 9660A-041-145 9660-041-147 9660-041-149 9660-041-161 9660-041-163 9660-041-166 9660A-041-173 9660A-041-182 Max. Pick-up Amps Min. Drop Out Amps 5.9 6.5 7.7 8.5 9.15 11 13.2 17.8 3.25 3.8 5.9 6.2 7 7.4 7.7 8.1 9.75 10.3 11 12.9 13.7 16.5 17.8 5 5.5 6.5 7.15 7.7 9.2 11.1 14.9 2.77 3.25 5 5.25 5.9 6.2 6.5 6.8 8.2 8.6 9.2 10.8 11.5 13.8 14.9 E12 Section E.indd 12 2/26/2008 11:02:32 AM Current Relay Data Wholesaler P/N 940-C411-83 940-C411-83 940-C411-91 940-C411-91 Copeland® Brand P/N 040-C411-83 040-C411-83 040-C411-91 040-C411-91 GE P/N Texas Inst. P/N 9660A-041-183 9660C-3027-183 9660A-041-191 9660C-3027-191 Max. Pick-up Amps 18.2 18.2 24.4 24.4 Min. Drop Out Amps 15.3 15.3 20.3 E13 Section E.indd 13 2/26/2008 11:02:32 AM Start Capacitor Data Wholesaler P/N Copeland® Brand P/N MFD-Low 914-0006-02 914-0006-03 914-0006-09 914-0006-10 914-0006-11 914-0006-12 914-0006-03 914-0006-09 914-0006-10 914-0006-11 014-0006-12 914-0008-48 914-0008-50 914-0008-51 914-0008-61 914-0008-62 914-0008-63 914-0008-64 914-0008-65 914-0008-66 914-0008-70 914-0008-71 014-0006-02 014-0006-03 014-0006-09 014-0006-10 014-0006-11 014-0006-12 014-0006-13 014-0006-14 014-0006-15 014-0006-16 014-0006-17 014-0008-47 014-0008-48 014-0008-50 014-0008-51 014-0008-61 014-0008-62 014-0008-63 014-0008-64 014-0008-65 014-0008-66 014-0008-68 014-0008-70 014-0008-71 88 189 216 270 145 175 189 216 270 145 175 460 124 161 145 88 53 540 43 64 108 88 43 189 MFD-High 106 227 259 324 174 216 227 259 324 174 216 552 149 193 174 106 64 648 52 77 130 106 52 227 Cap Volts 330 330 330 330 330 330 330 330 330 330 330 115 220 220 220 220 220 115 220 330 220 115 330 220 E14 Section E.indd 14 2/26/2008 11:02:32 AM Start Capacitor Data Wholesaler P/N Copeland® Brand P/N MFD-Low 914-0008-72 014-0008-72 64 914-0008-73 014-0008-73 43 914-0008-74 014-0008-74 72 914-0008-78 014-0008-78 108 914-0008-79 014-0008-79 270 914-0032-00 014-0032-00 233 914-0032-06 014-0032-06 233 014-0032-07 41 914-0036-00 014-0036-00 53 914-0036-01 014-0036-01 88 914-0036-03 014-0036-03 88 914-0036-04 014-0036-04 145 914-0036-05 014-0036-05 108 914-0036-07 014-0036-07 130 914-0036-11 014-0036-11 72 914-0036-13 014-0036-13 21 914-0036-00 014-0036-16 53 914-0036-01 014-0036-17 88 914-0036-02 014-0036-18 130 914-0036-03 014-0036-19 88 914-0036-04 014-0036-20 145 914-0036-05 014-0036-21 108 914-0036-07 014-0036-22 130 914-0036-08 014-0036-23 340 MFD-High 77 52 86 130 324 280 280 53 64 106 106 174 130 156 88 25 64 106 156 106 174 130 156 408 Cap Volts 250 250 330 250 165 110 125 250 330 250 330 250 330 330 220 330 330 250 250 330 250 330 330 110 E15 Section E.indd 15 2/26/2008 11:02:32 AM Start Capacitor Data Wholesaler P/N Copeland® Brand P/N MFD-Low 914-0036-09 014-0036-24 243 914-0036-11 014-0036-25 72 914-0036-12 014-0036-26 189 914-0036-15 014-0036-28 189 914-0053-00 014-0038-00 145 914-0053-01 014-0038-01 145 914-0053-02 014-0038-02 53 014-0038-03 43 914-0053-04 014-0038-04 189 914-0053-05 014-0038-05 88 914-0053-06 014-0038-06 50 914-0053-07 014-0038-07 43 914-0053-10 014-0038-10 145 914-0053-10 014-0038-17 145 914-0053-13 014-0053-13 64 914-0053-00 014-0053-18 145 914-0053-01 014-0053-19 145 914-0053-02 014-0053-20 53 914-0053-04 014-0053-21 189 914-0053-05 014-0053-22 88 914-0053-06 014-0053-23 50 914-0053-07 014-0053-24 43 914-0053-09 014-0053-25 189 914-0053-10 014-0053-26 145 MFD-High 292 88 227 227 175 175 64 52 227 106 60 53 174 174 77 175 175 64 227 106 60 52 227 174 Cap Volts 165 220 250 165 165 110 250 250 165 250 330 330 250 250 330 165 110 250 165 250 330 330 250 250 E16 Section E.indd 16 2/26/2008 11:02:32 AM Start Capacitor Data Wholesaler P/N Copeland® Brand P/N MFD-Low 914-0053-13 014-0053-29 64 914-0053-14 014-0053-30 88 014-0053-31 53 914-0053-16 014-0053-32 130 914-0006-03 014-0058-00 189 914-0006-09 014-0058-01 216 914-0006-10 014-0058-02 270 914-0006-11 014-0058-03 145 914-0006-12 014-0058-04 175 014-0058-05 460 914-0008-48 014-0058-06 124 914-0008-49 014-0058-07 400 914-0008-50 014-0058-08 161 914-0008-51 014-0058-09 145 914-0008-52 014-0058-10 430 914-0008-57 014-0058-11 243 914-0008-58 014-0058-12 324 914-0008-59 014-0058-13 590 914-0008-61 014-0058-14 88 014-0058-15 53 914-0008-63 014-0058-16 540 914-0008-64 014-0058-17 43 914-0008-65 014-0058-18 64 914-0008-66 014-0058-19 108 MFD-High 77 108 64 156 227 259 324 174 216 552 149 480 193 174 516 292 389 708 106 64 648 52 77 130 Cap Volts 330 330 330 330 330 330 330 330 330 110 220 110 220 220 125 110 110 110 220 220 110 220 330 220 E17 Section E.indd 17 2/26/2008 11:02:32 AM Start Capacitor Data Wholesaler P/N Copeland® Brand P/N MFD-Low 914-0008-69 014-0058-20 270 914-0008-70 014-0058-21 43 914-0008-71 014-0058-22 189 914-0008-72 014-0058-23 64 914-0008-73 014-0058-24 43 914-0008-74 014-0058-25 72 914-0008-78 014-0058-26 108 914-0008-79 014-0058-27 270 914-0036-00 014-0058-28 53 914-0036-01 014-0058-29 88 914-0036-02 014-0058-30 130 914-0036-03 014-0058-31 88 914-0036-04 014-0058-32 145 914-0036-05 014-0058-33 108 914-0036-07 014-0058-34 130 914-0036-08 014-0058-35 340 914-0036-09 014-0058-36 243 914-0036-11 014-0058-37 72 914-0036-12 014-0058-38 189 914-0036-15 014-0058-40 189 014-0058-41 340 014-0058-43 243 914-0053-00 014-0059-00 145 914-0053-01 014-0059-01 145 MFD-High 324 52 227 77 52 86 130 324 64 106 156 106 174 130 156 408 292 88 227 227 408 292 175 175 Cap Volts 110 330 220 250 250 330 250 165 330 250 250 330 250 330 330 110 165 220 250 165 165 250 165 110 E18 Section E.indd 18 2/26/2008 11:02:33 AM Start Capacitor Data Wholesaler P/N Copeland® Brand P/N MFD-Low 914-0053-02 014-0059-02 53 914-0053-04 014-0059-03 189 914-0053-05 014-0059-04 88 914-0053-06 014-0059-05 50 914-0053-07 014-0059-06 43 914-0053-09 014-0059-07 189 914-0053-10 014-0059-08 145 914-0053-11 014-0059-09 72 914-0053-13 014-0059-11 64 914-0053-14 014-0059-12 88 914-0053-15 014-0059-13 53 914-0053-16 014-0059-14 130 014-0059-18 130 014-0059-20 243 014-0061-00 460 914-0008-48 014-0061-01 124 914-0008-49 014-0061-02 400 914-0008-50 014-0061-03 161 914-0008-51 014-0061-04 145 914-0008-52 014-0061-05 430 914-0008-57 014-0061-06 243 914-0008-58 014-0061-07 324 914-0008-59 014-0061-08 590 914-0008-61 014-0061-09 88 MFD-High 64 227 106 60 52 227 174 88 77 106 64 156 156 292 552 149 480 193 174 516 292 389 708 106 Cap Volts 250 165 250 330 330 250 250 330 330 330 330 330 250 165 110 220 110 220 220 125 110 110 110 220 E19 Section E.indd 19 2/26/2008 11:02:33 AM Start Capacitor Data Wholesaler P/N Copeland® Brand P/N MFD-Low 014-0061-10 53 914-0008-63 014-0061-11 540 914-0008-64 014-0061-12 43 914-0008-65 014-0061-13 64 914-0008-66 014-0061-14 108 914-0008-69 014-0061-15 270 914-0008-70 014-0061-16 43 914-0008-72 014-0061-18 64 914-0008-73 014-0061-19 43 914-0008-74 014-0061-20 72 914-0008-78 014-0061-21 108 914-0008-79 014-0061-22 270 914-0037-07 014-0064-26 60 MFD-High 64 648 52 77 130 324 52 77 52 86 130 324 0 Cap Volts 220 110 220 330 220 110 330 250 250 330 250 165 370 E20 Section E.indd 20 2/26/2008 11:02:33 AM Run Capacitor Data Wholesaler P/N 914-0037-04 914-0037-06 914-0037-07 914-0037-08 914-0037-09 914-0037-10 914-0037-11 914-0037-12 914-0037-13 914-0037-14 914-0037-16 914-0037-17 914-0037-18 914-0037-19 914-0037-22 914-0037-11 914-0037-36 914-0037-37 914-0037-38 914-0037-39 914-0037-40 Copeland® Brand P/N 014-0011-01 014-0011-04 014-0037-04 014-0037-05 014-0037-06 014-0037-07 014-0037-08 014-0037-09 014-0037-10 014-0037-11 014-0037-12 014-0037-13 014-0037-14 014-0037-16 014-0037-17 014-0037-18 014-0037-19 014-0037-22 014-0037-28 014-0037-36 014-0037-37 014-0037-38 014-0037-39 014-0037-40 MFD 5 11 10 12.5 15 17.5 20 25 30 35 40 15 20 30 35 40 45 60 35 45 60 80 55 50 Cap Volts 330 330 370 370 370 370 370 370 370 370 370 440 440 440 440 440 440 440 370 370 370 370 370 370 Wholesaler P/N 914-0036-03 914-0037-04 Copeland® Brand P/N 014-0041-00 014-0041-01 014-0048-12 014-0048-18 014-0048-20 014-0048-21 014-0048-22 014-0048-36 014-0048-37 014-0048-38 014-0048-39 014-0048-40 014-0048-51 014-0054-12 014-0054-18 014-0054-20 014-0054-36 014-0054-37 014-0054-39 014-0054-40 014-0057-00 014-0058-31 014-0064-00 014-0064-01 MFD 60 80 40 40 50 55 60 45 60 80 55 50 70 40 40 50 45 60 55 50 100 88 10 12.5 Cap Volts 370 370 370 440 440 440 440 370 370 370 370 370 370 370 440 440 370 370 370 370 440 330 370 370 E21 Section E.indd 21 2/26/2008 11:02:33 AM Run Capacitor Data Wholesaler P/N 914-0037-06 914-0037-07 914-0037-08 914-0037-09 914-0037-10 914-0037-11 914-0037-12 914-0037-13 914-0037-14 914-0037-15 914-0037-16 914-0037-17 914-0037-18 914-0037-19 914-0037-20 914-0037-21 914-0037-22 914-0037-23 914-0037-29 914-0037-30 914-0037-36 914-0037-37 914-0037-38 914-0037-39 Copeland® Brand P/N 014-0064-02 014-0064-03 014-0064-04 014-0064-05 014-0064-06 014-0064-07 014-0064-08 014-0064-09 014-0064-10 014-0064-11 014-0064-12 014-0064-13 014-0064-14 014-0064-15 014-0064-16 014-0064-17 014-0064-18 014-0064-19 014-0064-23 014-0064-24 014-0064-25 014-0064-26 014-0064-27 014-0064-28 MFD 15 17.5 20 25 30 35 40 15 20 25 30 35 40 45 50 55 60 25 7.5 5 45 60 80 55 Cap Volts 370 370 370 370 370 370 370 440 440 440 440 440 440 440 440 440 440 482 330 330 370 370 370 370 Wholesaler P/N 914-0037-40 914-0037-46 914-0037-48 914-0037-49 914-0037-50 914-0037-51 914-0037-52 Copeland® Brand P/N 014-0064-29 014-0064-30 014-0064-31 014-0064-32 014-0064-33 014-0064-34 014-0064-35 014-0064-36 MFD 50 80 15 20 17.5 70 80 10 Cap Volts 370 370 440 440 440 370 440 440 E22 Section E.indd 22 2/26/2008 11:02:33 AM SECTION F COMPRESSOR ELECTRICAL DATA TOPICS Introduction .................................................................. F2 A-Line .......................................................................... FA Welded Compressors .................................................. FB Copelametic Air-Cooled ...............................................FC Copelametic Small Refrigerant-Cooled .......................FD Copelametic Large Refrigerant-Cooled ....................... FE Copeland Scroll ........................................................... FF Copeland Screw ..........................................................FG This section contains current information on Copeland® products. Information on obsolete models can be obtained from your local Emerson Climate Technologies, Inc. wholesaler. Section F TOC.indd 1 2/5/2008 10:00:51 AM Introduction The electrical data is listed as an aid to the serviceman in determining compressor characteristics. As required by U.L. requirements based on the National Electric Code, the terms nameplate amperage and full load amps have been replaced by the term “Rated Load Amps” (RLA). The value shown on the compressor nameplate is complicated by the fact that while normal operating amperage draw can be determined on a complete system by test, a compressor could really have an infinite number of operating conditions depending on its application. In order to provide a uniform basis of 71% of maximum continuous current allowed by the motor protection system. This will allow the compressor to draw 140% of the rated load amp value prior to the protector tripping. Rated Load Amp values are not marked on new Copelametic, welded or scroll compressor nameplates unless otherwise specified by an equipment manufacturer. Since one motor design may be used in a number of different compressor models, using different refrigerants, for different operating ranges, the Rated Load Amp value shown in the handbook may vary from the value marked on individual compressor nameplates. The handbook value is usually selected as the highest nameplate value used for a given motor, so it is always a conservative value which may be safely used in the event exact nameplate values are not known. If refrigerant application specific RLA is required, this can be calculated from refrigerant application specific Maximum Continuous Current (MCC) listed in Emerson Climate Technologies, Inc. Online Product Information (OPI). F2 Section F TOC.indd 2 2/5/2008 10:00:56 AM Explanation of Section F Electrical Data Notes The following notes can be found in the headings for the data tables which are found later in this section: Copelametic compressors may have the ninth digit changed to represent variations that do not affect performance. An “E” at the ninth digit means the compressor was originally shipped with polyolester oil. An “A” at the ninth digit means the compressor was originally shipped with alkyl benzene oil. A “number” at the ninth digit means the compressor was originally shipped with mineral oil. An “L” at the ninth digit means the compressor was originally shipped with no oil. Information on Line to Line winding resistances is found in Section A “Measuring Winding Resistance”. Capacitor values are found in Section E. Potential and Current relay values are found in Section E. * RP = Relay Potential * RC = Relay Current Large refrigerant cooled compressors whose overload protectors are not listed have Emerson Climate Technologies part numbers: F3 Section F TOC.indd 3 2/5/2008 10:00:56 AM 071-0424-01 071-0424-00 071-0524-00 071-0464-01 071-0464-00 120V 240V 120V/240V 120V 240V (Texas Instruments) (Texas Instruments) (Texas Instruments) (Kriwan) (Kriwan) 071-0441-01 120V 071-0441-00 240V (Robertshaw) (Robertshaw) 071-0520-03 071-0520-00 071-0520-01 071-0520-02 071-0520-04 071-0520-05 071-0550-00 071-0550-01 071-0582-00 071-0581-00 (Texas Instruments) (Texas Instruments) (Kriwan) (Kriwan) (Kriwan) (Kriwan) (Kriwan) (Texas Instruments) (Kriwan) (Kriwan) 24V 120V/240V 230V 115V 24V 120V/240V 120V/240V 24V 120/240V 120/240V F4 Section F TOC.indd 4 2/5/2008 10:00:56 AM Electrical Data - A-Line Model AFB04C3E-SAA AFB05C3E-IAA AFB05C3E-SAA AFB06C3E-IAA AFB09C3E-IAA AFB09C3E-IAB AFE06C4E-IAA AFE07C3E-IAA AFE08C4E-IAA AFE10C3E-IAA AFE11C3E-IAA AFE11C4E-IAA AFE12C3E-IAA AFE13C3E-IAA AFE13C3E-IAV AFE13C4E-IAA AFE17C4E-CAA AFE17C4E-IAA AFJ23C1-IAA AFJ23C2-IAA AFJ31C1E-CFV AFJ31C2E-CFV AFJ37C1E-CFV AFJ37C2E-CFV AFT12C1-IAA Max LRA Volts PH RLA 115 115 115 115 115 230 115 115 115 115 115 115 115 115 208/230 115 115 115 115 115 208/230 208/230 208/230 208/230 115 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 2.8 2.7 3.1 4.8 1.7 3.1 4.4 3.9 4.9 5.6 4.2 4.8 5.8 3.2 5.6 7.8 7.8 7.2 9.2 5.4 7.5 6.2 8 5 20 26.5 27.5 25 34.6 15 28.5 29 26.5 38 29 26.5 33 33 21.7 37.5 41.5 41.5 59 54 40 44 40 46 30 Resistance Start or Run Line/Line 10.5 8.5 8.5 7.4 9 36 6.14 9 6.14 9 7.3 6.14 6.1 6.1 21.9 6.1 4.5 4.5 4.771 4.771 6 6 6 6 6.51 2.7 1.9 1.9 1.55 1.05 5.85 1.24 1.3 1.24 1.2 1.2 1.24 0.96 0.96 3.4 0.96 0.77 0.77 0.611 0.611 1.2 1.2 1.2 1.2 0.99 Start Cap P/N Run Cap P/N 014-0053-21 014-0053-26 014-0053-26 014-0059-13 014-0053-18 014-0053-26 014-0053-18 014-0053-26 014-0053-18 014-0053-18 014-0053-21 014-0053-21 014-0059-13 014-0053-21 014-0036-28 014-0053-21 014-0036-24 014-0036-24 014-0053-18 014-0064-12 014-0064-10 014-0064-10 014-0064-10 014-0064-10 Relay P/N Part Type* Protector P/N 040-0162-13 040-0150-05 040-0162-05 040-0150-02 040-0150-20 040-0150-03 040-0150-19 040-0150-01 040-0150-31 040-0150-11 040-0150-01 040-0150-19 040-0150-06 040-0150-06 040-0150-14 040-0150-06 040-0166-21 040-0150-11 040-0166-38 040-0166-38 040-0166-29 040-0166-29 040-0166-29 040-0166-29 040-0150-06 RC RC RC RC RC RC RC RC RC RC RC RC RC RC RC RC RP RC RP RP RP RP RP RP RC 071-0561-13 071-0561-08 071-0561-08 071-0561-11 071-0561-15 071-0561-30 071-0561-29 071-0561-02 071-0561-23 071-0561-24 071-0561-16 071-0561-21 071-0561-28 071-0561-03 071-0561-04 071-0561-47 071-0561-48 071-0561-48 071-0605-03 071-0644-02 071-0603-14 * See Section F Introduction for more information. FA1 Section_Fa.indd 1 3/4/2008 7:45:36 AM Electrical Data - A-Line Model AFT12C1E-IAA AFT12C1E-IAV AFT18C1E-IAA AFT18C1E-IAV AFT22C1E-CFV AFT22C1E-IAA AFT26C1E-CFA AFT26C1E-CFV AFT29C1E-CFA AFT29C1E-CFV ARB10C3-SAA ARB13C3-SAA ARB13C3E-IAA ARB13C3E-SAA ARB17C3-SAA ARB17C3E-IAA ARB17C3E-SAA ARB21C3-IAA ARB26C3-IAA ARB26C3-IAV ARE25C3-SAA ARE25C3E-IAA ARE25C3E-SAA ARE27C3-IAA ARE27C3-SAA Max LRA Volts PH RLA 115 208/230 115 208/230 208/230 115 115 208/230 115 208/230 115 115 115 115 115 115 115 115 115 208/230 115 115 115 115 115 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 5.1 3.5 7.9 4.1 3.7 9.2 8.8 4.6 9.7 5 2.5 2.8 2.8 2.8 3.8 3.5 3.8 4.6 5 3.1 4.5 4.7 4.5 4.9 5 30 21.5 51 30 32.5 55 72 32.2 74 33 17 20 15.1 20 23 19.3 23 26.5 29 15.5 25 21.5 25 25 31 Resistance Start or Run Line/Line 6.51 6.4 4.25 9 5.3 3.8 4.03 5.3 3.91 5.3 14.85 10.5 10.7 10.5 13.2 9.1 13.2 8 7.3 21.35 18.45 8.3 18.45 7.4 11.1 0.99 3.54 0.7 2.3 2.1 0.54 0.6 2.3 0.49 2.3 3.3 2.7 3 2.7 2.4 2.4 2.4 1.4 1.4 5.1 2 2 2 1.55 1.55 Start Cap P/N 014-0053-21 014-0059-09 014-0053-26 014-0053-30 014-0058-31 014-0053-18 014-0058-32 014-0058-38 014-0058-31 014-0053-18 014-0053-18 014-0053-18 014-0059-14 014-0059-13 014-0053-18 014-0053-18 Run Cap P/N 014-0064-09 014-0064-11 014-0064-09 014-0064-11 014-0064-09 Relay P/N Part Type* Protector P/N 040-0163-08 040-0163-01 040-0163-07 040-0163-02 040-0166-39 040-0172-00 040-0166-37 040-0166-13 040-0166-37 040-0166-13 040-0162-08 040-0162-08 040-0150-16 040-0162-08 040-0162-11 040-0150-15 040-0162-11 040-0150-19 040-0150-24 040-0163-00 040-0162-01 040-0150-10 040-0162-01 040-0150-02 040-0162-07 RC RC RC RC RP RC RP RP RP RP RC RC RC RC RC RC RC RC RC RC RC RC RC RC RC 071-0603-08 071-0603-01 071-0603-11 071-0603-03 071-0605-00 071-0561-18 071-0561-25 071-0561-25 071-0561-25 071-0561-09 071-0561-09 071-0561-09 071-0561-01 071-0561-26 071-0561-09 071-0561-23 071-0561-23 071-0561-23 071-0561-23 071-0561-23 * See Section F Introduction for more information. FA2 Section_Fa.indd 2 3/4/2008 7:45:46 AM Electrical Data - A-Line Model ARE27C3E-IAA ARE27C3E-SAA ARE29C4E-IAA ARE34C4E-IAA ARE35C3-IAA ARE35C3-IAV ARE36C3-IAA ARE36C3-SAA ARE37C3-IAA ARE37C3-SAA ARE37C3E-IAA ARE37C3E-IAV ARE37C3E-SAA ARE40C4E-IAA ARE41C3-IAA ARE41C3-SAA ARE41C3E-IAA ARE41C3E-IAV ARE43C3-IAA ARE46C4E-IAA ARE47C3-IAA ARE47C3-IAV ARE59C3-CAA ARE59C3-CAV ARJ10K1-CAV Max LRA Volts PH RLA 115 115 115 115 115 208/230 115 115 115 115 115 208/230 115 115 115 115 115 208/230 115 115 115 208/230 115 208/230 208/230 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 4.9 5 3.9 4.6 7 3.6 6.7 6.5 7.2 7.2 7.2 3.4 7.2 7 7.5 4.7 7.5 3.9 7.1 9 7 4.5 8 4 7 25 31 28.5 37 34.6 18.2 29 34 29 35 29 17.3 35 37 37.5 41 37.5 23.8 29 40 38.5 25.8 36 25.9 37 Resistance Start or Run Line/Line 7.4 11.1 6.14 6.1 9 25.6 7.3 13.55 7.3 13.65 7.3 21.4 13.65 6.1 10.6 8.8 10.6 21.25 7.3 5.5 5.62 21.86 7.5 10.45 7.6 1.55 1.55 1.24 0.96 1.05 4.7 1.2 1.4 1.2 1.2 1.2 4.8 1.2 0.96 1 1.1 1 3.4 1.2 0.86 0.85 2.92 1.2 3.05 1.8 Start Cap P/N Run Cap P/N Relay P/N Part Type* Protector P/N 014-0064-10 014-0064-09 014-0064-10 040-0150-02 040-0162-07 040-0150-19 040-0150-06 040-0150-20 040-0150-25 040-0150-01 040-0162-03 040-0150-01 040-0162-03 040-0150-01 040-0150-04 040-0162-03 040-0150-33 040-0150-06 040-0162-14 040-0150-06 040-0150-18 040-0150-01 040-0150-11 040-0150-01 040-0150-13 040-0166-45 040-0166-30 040-0166-27 RC RC RC RC RC RC RC RC RC RC RC RC RC RC RC RC RC RC RC RC RC RC RP RP RP 071-0561-23 071-0561-23 071-0561-21 071-0561-50 071-0561-03 071-0561-01 071-0561-16 071-0561-16 071-0561-16 071-0561-16 071-0561-16 071-0561-00 071-0561-16 071-0561-03 071-0561-32 071-0561-17 071-0561-32 071-0561-00 071-0561-17 071-0561-51 071-0561-17 071-0561-00 071-0561-07 071-0561-10 071-0563-00 014-0053-18 014-0053-18 014-0053-21 014-0053-18 014-0059-13 014-0059-01 014-0053-18 014-0053-21 014-0053-30 014-0053-25 014-0053-21 014-0053-21 014-0053-29 014-0053-18 014-0053-25 014-0053-26 014-0053-29 014-0058-37 014-0058-25 014-0058-31 * See Section F Introduction for more information. FA3 Section_Fa.indd 3 3/4/2008 7:45:46 AM Electrical Data - A-Line Model ARJ10K1-TFD ARJ11K1-CAV ARJ11K1E-CAV ARJ11K1E-TFD ARJ11K2-CAV ARJ11K2E-CAV ARJ13K1-CAB ARJ84C1-IAA ARJ84C1-IAV ARJ84C1E-IAV ARJ84C1E-TFD ARJ84C2-IAA ARJ84C2-IAV ARJ84C2E-IAV ART51C1-IAA ART51C1E-IAA ART51C1E-IAV ART62C1-IAA ART62C1E-IAA ART62C1E-IAV ART64C1E-IAA ART64C1E-IAV ART69C1-IAA ART69C1-IAV ART82C1-CAA Max LRA Volts PH RLA 440/480 208/230 208/230 440/480 208/230 208/230 230 115 208/230 208/230 440/480 115 208/230 208/230 115 115 208/230 115 115 208/230 115 208/230 115 208/230 115 3 1 1 3 1 1 1 1 1 1 3 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2.1 7.3 7.4 2.3 8.5 8.5 6 13.6 7.2 7.4 1.8 11.4 8 8 9.3 9.3 5 10.3 10.2 5.4 11 6 13 6.1 11.8 10 40 43 13 41 41 40 72 38 42 10 73 42 42 36 36 30 51 51 30 51 30 55 30 72 Resistance Start or Run Line/Line 18.6 8.1 8.1 14.87 8.1 8.1 5.4 2.85 11.2 8.09 18.6 2.85 8.09 8.09 3.4 3.4 9 4.25 4.25 9 4.25 16 4.1 9 4.15 0 1.45 1.45 0 1.45 1.45 1.75 0.44 2 1.4 0 0.44 1.4 1.4 1.05 1.05 2.3 0.7 0.7 2.3 0.7 2.21 0.54 2.3 0.6 Start Cap P/N Run Cap P/N Relay P/N Part Type* Protector P/N 014-0058-25 014-0058-25 014-0064-03 014-0064-33 040-0166-24 040-0166-24 RP RP 071-0604-05 071-0604-04 014-0058-25 014-0058-25 014-0058-31 014-0036-23 014-0058-31 014-0058-31 014-0064-33 014-0064-33 014-0064-10 040-0166-24 040-0166-24 040-0166-05 040-0166-38 040-0172-02 040-0172-02 RP RP RP RP RC RC 071-0604-11 071-0604-11 071-C100-10 071-0605-01 071-0604-03 071-0604-03 040-0166-38 040-0172-02 040-0172-02 040-0163-04 040-0163-04 040-0163-02 040-0163-05 040-0163-05 040-0163-02 040-0163-07 040-0163-02 040-0172-03 040-0163-02 040-0166-37 RP RC RC RC RC RC RC RC RC RC RC RC RC RP 071-0605-01 071-0604-11 071-0604-11 071-0603-02 071-0603-02 071-0603-09 071-0603-05 071-0603-05 071-0603-07 071-0603-10 071-0603-15 071-0605-05 071-0603-13 071-0605-03 014-0036-23 014-0058-31 014-0058-31 014-0053-21 014-0038-04 014-0058-18 014-0053-25 014-0053-25 014-0058-18 014-0053-25 014-0058-32 014-0053-30 014-0058-32 014-0064-13 * See Section F Introduction for more information. FA4 Section_Fa.indd 4 3/4/2008 7:45:47 AM Electrical Data - A-Line Model ART82C1-CAV ART82C1-CFB ART97C1-CAA ART97C1-CAV ART97C1-PAA ART97C1-PAV ASB12C3E-IAA ASB14C3E-IAA ASE19C3E-IAA ASE19C4E-IAA ASE20C4E-CAA ASE20C4E-IAA ASE21C3E-IAA ASE24C3E-IAA ASE24C3E-IAV ASE26C4E-CAA ASE26C4E-IAA ASE32C3E-CAA ASE32C3E-CAV ASE35C4E-CAA ASE35C4E-IAA ASJ58C1E-CAV AST40C1E-IAA AST40C1E-IAV AST45C1E-CAV Max LRA Volts PH RLA 208/230 230 115 208/230 115 208/230 115 115 115 115 115 115 115 115 208/230 115 115 115 208/230 115 115 208/230 115 208/230 208/230 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 5.9 30 5.1 31 14 71 7 34 11.2 50 5.6 31.5 5.2 26.5 6.8 29.75 8 34.6 5.6 26.5 5.5 30.5 5.2 26.5 7 29 6 29 4.2 16.8 7.5 38 7.5 38 9.2 33.6 4.9 24.8 12 51 12 51 8.4 34 13 55 6.9 30 6.5 30 Resistance Start or Run Line/Line 9.06 11.6 3.944 9.68 6.28 2.94 2.5 0.461 1.97 0.58 8 7.3 9 6.14 6.14 6.14 7.3 7.3 7.48 6.1 6.1 7.3 11.6 5.2 5.2 7.6 3.8 16 9.06 1.4 1.2 1.05 1.24 1.24 1.24 1.2 1.2 4.55 0.96 0.96 1.2 3.2 0.67 0.67 1.8 0.54 2.21 2.94 Start Cap P/N Run Cap P/N Relay P/N Part Type* Protector P/N 014-0058-21 014-0058-31 014-0058-38 014-0058-21 014-0036-13 014-0036-13 014-0053-26 014-0053-18 014-0053-18 014-0053-18 014-0058-32 014-0053-26 014-0053-26 014-0053-26 014-0059-09 014-0036-28 014-0053-21 014-0058-25 014-0058-31 014-0036-28 014-0053-21 014-0058-31 014-0058-32 014-0058-31 014-0058-21 014-0064-09 014-0064-09 014-0064-11 014-0064-09 014-0064-11 014-0064-10 040-0166-27 040-0166-04 040-0166-03 040-0166-27 040-0166-37 040-0166-27 040-0150-19 040-0150-01 040-0150-20 040-0150-32 040-0166-21 040-0150-19 040-0150-01 RP RP RP RP RP RP RC RC RC RC RP RC RC 071-0604-01 040-0150-04 040-0166-21 040-0163-04 040-0166-45 040-0166-13 040-0166-37 040-0150-11 040-0166-18 040-0172-03 040-0163-02 040-0166-27 RC RP RC RP RP RP RC RP RC RC RP 014-0064-10 014-0064-11 014-0064-10 014-0064-09 014-0064-12 014-0064-10 014-0064-09 071-0605-02 071-0604-08 071-0605-02 071-0604-06 071-0561-01 071-0561-26 071-0561-21 071-0561-21 071-0561-21 071-0561-21 071-0561-21 071-0561-07 071-0561-29 071-0561-03 071-0561-03 071-0561-07 071-0561-12 071-0561-49 071-0561-49 071-0563-00 071-0605-05 071-0603-13 071-0604-01 * See Section F Introduction for more information. FA5 Section_Fa.indd 5 3/4/2008 7:45:47 AM Electrical Data - A-Line Model AST45C1E-IAA AST54C1E-CAA AST54C1E-CAV Max LRA Volts PH RLA 115 115 208/230 1 1 1 15 15 5.8 55 71 34 Resistance Start or Run Line/Line 4.1 3.944 9.68 0.54 0.461 1.97 Start Cap P/N Run Cap P/N Relay P/N Part Type* Protector P/N 014-0058-32 014-0058-38 014-0058-21 014-0064-11 014-0064-09 040-0172-03 040-0166-03 040-0166-27 RC RP RP 071-0605-03 071-0605-04 071-0604-07 * See Section F Introduction for more information. FA6 Section_Fa.indd 6 3/4/2008 7:45:48 AM Electrical Data - Welded Compressors Model Volts AFB04C3E-SAA AFB05C3E-IAA AFB05C3E-SAA AFB06C3E-IAA AFB09C3E-IAA AFB09C3E-IAB AFE06C4E-IAA AFE07C3E-IAA AFE08C4E-IAA AFE10C3E-IAA AFE11C3E-IAA AFE11C4E-IAA AFE12C3E-IAA AFE13C3E-IAA AFE13C3E-IAV AFE13C4E-IAA AFE17C4E-CAA AFE17C4E-IAA AFJ23C1-IAA AFJ23C2-IAA AFJ31C1E-CFV AFJ31C2E-CFV AFJ37C1E-CFV AFJ37C2E-CFV AFT12C1-IAA AFT12C1E-IAA 115 115 115 115 115 230 115 115 115 115 115 115 115 115 208/230 115 115 115 115 115 208/230 208/230 208/230 208/230 115 115 Resistance Max PH RLA LRA Start or Run Line/Line 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 2.8 2.7 3.1 4.8 1.7 3.1 4.4 3.9 4.9 5.6 4.2 4.8 5.8 3.2 5.6 7.8 7.8 7.2 9.2 5.4 7.5 6.2 8 5 5.1 20 2.7 26.5 1.9 27.5 1.9 25 1.55 34.6 1.05 15 5.85 28.5 1.24 29 1.3 26.5 1.24 38 1.2 29 1.2 26.5 1.24 33 0.96 33 0.96 21.7 3.4 37.5 0.96 41.5 0.77 41.5 0.77 59 0.611 54 0.611 40 1.2 44 1.2 40 1.2 46 1.2 30 0.99 30 0.99 10.5 8.5 8.5 7.4 9 36 6.14 9 6.14 9 7.3 6.14 6.1 6.1 21.9 6.1 4.5 4.5 4.771 4.771 6 6 6 6 6.51 6.51 Start Cap P/N Run Cap P/N 014-0053-21 014-0053-26 014-0053-26 014-0059-13 014-0053-18 014-0053-26 014-0053-18 014-0053-26 014-0053-18 014-0053-18 014-0053-21 014-0053-21 014-0059-13 014-0053-21 014-0036-28 014-0053-21 014-0036-24 014-0036-24 014-0053-18 014-0053-21 014-0064-12 014-0064-10 014-0064-10 014-0064-10 014-0064-10 Relay P/N Part Type* 040-0162-13 040-0150-05 040-0162-05 040-0150-02 040-0150-20 040-0150-03 040-0150-19 040-0150-01 040-0150-31 040-0150-11 040-0150-01 040-0150-19 040-0150-06 040-0150-06 040-0150-14 040-0150-06 040-0166-21 040-0150-11 040-0166-38 040-0166-38 040-0166-29 040-0166-29 040-0166-29 040-0166-29 040-0150-06 040-0163-08 RC RC RC RC RC RC RC RC RC RC RC RC RC RC RC RC RP RC RP RP RP RP RP RP RC RC Protector P/N 071-0561-13 071-0561-08 071-0561-08 071-0561-11 071-0561-15 071-0561-30 071-0561-29 071-0561-02 071-0561-23 071-0561-24 071-0561-16 071-0561-21 071-0561-28 071-0561-03 071-0561-04 071-0561-47 071-0561-48 071-0561-48 071-0605-03 071-0644-02 071-0603-14 071-0603-08 * See Section F Introduction for more information. FB1 Section_Fb.indd 1 3/4/2008 7:57:08 AM Electrical Data - Welded Compressors Model Volts AFT12C1E-IAV AFT18C1E-IAA AFT18C1E-IAV AFT22C1E-CFV AFT22C1E-IAA AFT26C1E-CFA AFT26C1E-CFV AFT29C1E-CFA AFT29C1E-CFV ARB10C3-SAA ARB13C3-SAA ARB13C3E-IAA ARB13C3E-SAA ARB17C3-SAA ARB17C3E-IAA ARB17C3E-SAA ARB21C3-IAA ARB26C3-IAA ARB26C3-IAV ARE25C3-SAA ARE25C3E-IAA ARE25C3E-SAA ARE27C3-IAA ARE27C3-SAA ARE27C3E-IAA ARE27C3E-SAA 208/230 115 208/230 208/230 115 115 208/230 115 208/230 115 115 115 115 115 115 115 115 115 208/230 115 115 115 115 115 115 115 Resistance Max PH RLA LRA Start or Run Line/Line 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 3.5 7.9 4.1 3.7 9.2 8.8 4.6 9.7 5 2.5 2.8 2.8 2.8 3.8 3.5 3.8 4.6 5 3.1 4.5 4.7 4.5 4.9 5 4.9 5 21.5 51 30 32.5 55 72 32.2 74 33 17 20 15.1 20 23 19.3 23 26.5 29 15.5 25 21.5 25 25 31 25 31 3.54 0.7 2.3 2.1 0.54 0.6 2.3 0.49 2.3 3.3 2.7 3 2.7 2.4 2.4 2.4 1.4 1.4 5.1 2 2 2 1.55 1.55 1.55 1.55 6.4 4.25 9 5.3 3.8 4.03 5.3 3.91 5.3 14.85 10.5 10.7 10.5 13.2 9.1 13.2 8 7.3 21.35 18.45 8.3 18.45 7.4 11.1 7.4 11.1 Start Cap P/N 014-0059-09 014-0053-26 014-0053-30 014-0058-31 014-0053-18 014-0058-32 014-0058-38 014-0058-31 014-0053-18 014-0053-18 014-0053-18 014-0059-14 014-0059-13 014-0053-18 014-0053-18 014-0053-18 Run Cap P/N 014-0064-09 014-0064-11 014-0064-09 014-0064-11 014-0064-09 Relay P/N 040-0163-01 040-0163-07 040-0163-02 040-0166-39 040-0172-00 040-0166-37 040-0166-13 040-0166-37 040-0166-13 040-0162-08 040-0162-08 040-0150-16 040-0162-08 040-0162-11 040-0150-15 040-0162-11 040-0150-19 040-0150-24 040-0163-00 040-0162-01 040-0150-10 040-0162-01 040-0150-02 040-0162-07 040-0150-02 040-0162-07 Part Type* RC RC RC RP RC RP RP RP RP RC RC RC RC RC RC RC RC RC RC RC RC RC RC RC RC RC Protector P/N 071-0603-01 071-0603-11 071-0603-03 071-0605-00 071-0561-18 071-0561-25 071-0561-25 071-0561-25 071-0561-09 071-0561-09 071-0561-09 071-0561-01 071-0561-26 071-0561-09 071-0561-23 071-0561-23 071-0561-23 071-0561-23 071-0561-23 071-0561-23 071-0561-23 * See Section F Introduction for more information. FB2 Section_Fb.indd 2 3/4/2008 7:57:14 AM Electrical Data - Welded Compressors Model Volts ARE29C4E-IAA ARE34C4E-IAA ARE35C3-IAA ARE35C3-IAV ARE36C3-IAA ARE36C3-SAA ARE37C3-IAA ARE37C3-SAA ARE37C3E-IAA ARE37C3E-IAV ARE37C3E-SAA ARE40C4E-IAA ARE41C3-IAA ARE41C3-SAA ARE41C3E-IAA ARE41C3E-IAV ARE43C3-IAA ARE46C4E-IAA ARE47C3-IAA ARE47C3-IAV ARE59C3-CAA ARE59C3-CAV ARJ10K1-CAV ARJ10K1-TFD ARJ11K1-CAV ARJ11K1E-CAV 115 115 115 208/230 115 115 115 115 115 208/230 115 115 115 115 115 208/230 115 115 115 208/230 115 208/230 208/230 440/480 208/230 208/230 Resistance Max PH RLA LRA Start or Run Line/Line 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 3 1 1 3.9 4.6 7 3.6 6.7 6.5 7.2 7.2 7.2 3.4 7.2 7 7.5 4.7 7.5 3.9 7.1 9 7 4.5 8 4 7 2.1 7.3 7.4 28.5 37 34.6 18.2 29 34 29 35 29 17.3 35 37 37.5 41 37.5 23.8 29 40 38.5 25.8 36 25.9 37 10 40 43 1.24 0.96 1.05 4.7 1.2 1.4 1.2 1.2 1.2 4.8 1.2 0.96 1 1.1 1 3.4 1.2 0.86 0.85 2.92 1.2 3.05 1.8 0 1.45 1.45 6.14 6.1 9 25.6 7.3 13.55 7.3 13.65 7.3 21.4 13.65 6.1 10.6 8.8 10.6 21.25 7.3 5.5 5.62 21.86 7.5 10.45 7.6 18.6 8.1 8.1 Start Cap P/N Run Cap P/N Relay P/N Part Type* 014-0053-21 014-0053-29 014-0053-18 014-0053-25 014-0053-26 014-0053-29 014-0058-37 014-0058-25 014-0058-31 014-0064-10 014-0064-09 014-0064-10 040-0150-19 040-0150-06 040-0150-20 040-0150-25 040-0150-01 040-0162-03 040-0150-01 040-0162-03 040-0150-01 040-0150-04 040-0162-03 040-0150-33 040-0150-06 040-0162-14 040-0150-06 040-0150-18 040-0150-01 040-0150-11 040-0150-01 040-0150-13 040-0166-45 040-0166-30 040-0166-27 RC RC RC RC RC RC RC RC RC RC RC RC RC RC RC RC RC RC RC RC RP RP RP 071-0561-21 071-0561-50 071-0561-03 071-0561-01 071-0561-16 071-0561-16 071-0561-16 071-0561-16 071-0561-16 071-0561-00 071-0561-16 071-0561-03 071-0561-32 071-0561-17 071-0561-32 071-0561-00 071-0561-17 071-0561-51 071-0561-17 071-0561-00 071-0561-07 071-0561-10 071-0563-00 014-0058-25 014-0058-25 014-0064-03 014-0064-33 040-0166-24 040-0166-24 RP RP 071-0604-05 071-0604-04 014-0053-18 014-0053-21 014-0053-18 014-0059-13 014-0059-01 014-0053-18 014-0053-21 014-0053-30 014-0053-25 014-0053-21 Protector P/N * See Section F Introduction for more information. FB3 Section_Fb.indd 3 3/4/2008 7:57:14 AM Electrical Data - Welded Compressors Model Volts ARJ11K1E-TFD ARJ11K2-CAV ARJ11K2E-CAV ARJ13K1-CAB ARJ84C1-IAA ARJ84C1-IAV ARJ84C1E-IAV ARJ84C1E-TFD ARJ84C2-IAA ARJ84C2-IAV ARJ84C2E-IAV ART51C1-IAA ART51C1E-IAA ART51C1E-IAV ART62C1-IAA ART62C1E-IAA ART62C1E-IAV ART64C1E-IAA ART64C1E-IAV ART69C1-IAA ART69C1-IAV ART82C1-CAA ART82C1-CAV ART82C1-CFB ART97C1-CAA ART97C1-CAV 440/480 208/230 208/230 230 115 208/230 208/230 440/480 115 208/230 208/230 115 115 208/230 115 115 208/230 115 208/230 115 208/230 115 208/230 230 115 208/230 Resistance Max PH RLA LRA Start or Run Line/Line 3 1 1 1 1 1 1 3 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2.3 8.5 8.5 6 13.6 7.2 7.4 1.8 11.4 8 8 9.3 9.3 5 10.3 10.2 5.4 11 6 13 6.1 11.8 5.9 5.1 14 7 13 0 41 1.45 41 1.45 40 1.75 72 0.44 38 2 42 1.4 10 0 73 0.44 42 1.4 42 1.4 36 1.05 36 1.05 30 2.3 51 0.7 51 0.7 30 2.3 51 0.7 30 2.21 55 0.54 30 2.3 72 0.6 30 2.94 31 2.5 71 0.461 34 1.97 14.87 8.1 8.1 5.4 2.85 11.2 8.09 18.6 2.85 8.09 8.09 3.4 3.4 9 4.25 4.25 9 4.25 16 4.1 9 4.15 9.06 11.6 3.944 9.68 Start Cap P/N 014-0058-25 014-0058-25 014-0058-31 014-0036-23 014-0058-31 014-0058-31 Run Cap P/N 014-0064-33 014-0064-33 014-0064-10 014-0036-23 014-0058-31 014-0058-31 014-0053-21 014-0038-04 014-0058-18 014-0053-25 014-0053-25 014-0058-18 014-0053-25 014-0058-32 014-0053-30 014-0058-32 014-0058-21 014-0058-31 014-0058-38 014-0058-21 014-0064-13 014-0064-09 014-0064-09 014-0064-11 014-0064-09 Relay P/N Part Type* Protector P/N 040-0166-24 040-0166-24 040-0166-05 040-0166-38 040-0172-02 040-0172-02 RP RP RP RP RC RC 071-0604-11 071-0604-11 071-C100-10 071-0605-01 071-0604-03 071-0604-03 040-0166-38 040-0172-02 040-0172-02 040-0163-04 040-0163-04 040-0163-02 040-0163-05 040-0163-05 040-0163-02 040-0163-07 040-0163-02 040-0172-03 040-0163-02 040-0166-37 040-0166-27 040-0166-04 040-0166-03 040-0166-27 RP RC RC RC RC RC RC RC RC RC RC RC RC RP RP RP RP RP 071-0605-01 071-0604-11 071-0604-11 071-0603-02 071-0603-02 071-0603-09 071-0603-05 071-0603-05 071-0603-07 071-0603-10 071-0603-15 071-0605-05 071-0603-13 071-0605-03 071-0604-01 071-0605-02 071-0604-08 * See Section F Introduction for more information. FB4 Section_Fb.indd 4 3/4/2008 7:57:15 AM Electrical Data - Welded Compressors Model Volts ART97C1-PAA ASB12C3E-IAA ASB14C3E-IAA ASE19C3E-IAA ASE19C4E-IAA ASE20C4E-CAA ASE20C4E-IAA ASE21C3E-IAA ASE24C3E-IAA ASE24C3E-IAV ASE26C4E-CAA ASE26C4E-IAA ASE32C3E-CAA ASE32C3E-CAV ASE35C4E-CAA ASE35C4E-IAA ASJ58C1E-CAV AST40C1E-IAA AST40C1E-IAV AST45C1E-CAV AST45C1E-IAA AST54C1E-CAA AST54C1E-CAV CF04K6E-PFV CF04K6E-TF5 CF04K6E-TFD 115 115 115 115 115 115 115 115 115 208/230 115 115 115 208/230 115 115 208/230 115 208/230 208/230 115 115 208/230 208/230 200/230 380/460 Resistance Max PH RLA LRA Start or Run Line/Line 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 3 3 11.2 5.2 6.8 8 5.6 5.5 5.2 7 6 4.2 7.5 7.5 9.2 4.9 12 12 8.4 13 6.9 6.5 15 15 5.8 9.6 6.8 3.3 50 0.58 26.5 1.4 29.75 1.2 34.6 1.05 26.5 1.24 30.5 1.24 26.5 1.24 29 1.2 29 1.2 16.8 4.55 38 0.96 38 0.96 33.6 1.2 24.8 3.2 51 0.67 51 0.67 34 1.8 55 0.54 30 2.21 30 2.94 55 0.54 71 0.461 34 1.97 59.2 1.107 52 0 26 0 6.28 8 7.3 9 6.14 6.14 6.14 7.3 7.3 7.48 6.1 6.1 7.3 11.6 5.2 5.2 7.6 3.8 16 9.06 4.1 3.944 9.68 3.044 1.71 7.4 Start Cap P/N Run Cap P/N Relay P/N Part Type* 014-0036-13 014-0053-26 014-0053-18 014-0053-18 014-0053-18 014-0058-32 014-0053-26 014-0053-26 014-0053-26 014-0059-09 014-0036-28 014-0053-21 014-0058-25 014-0058-31 014-0036-28 014-0053-21 014-0058-31 014-0058-32 014-0058-31 014-0058-21 014-0058-32 014-0058-38 014-0058-21 014-0061-04 014-0064-11 040-0166-37 040-0150-19 040-0150-01 040-0150-20 040-0150-32 040-0166-21 040-0150-19 040-0150-01 RP RC RC RC RC RP RC RC 040-0150-04 040-0166-21 040-0163-04 040-0166-45 040-0166-13 040-0166-37 040-0150-11 040-0166-18 040-0172-03 040-0163-02 040-0166-27 040-0172-03 040-0166-03 040-0166-27 040-0166-15 RC RP RC RP RP RP RC RP RC RC RP RC RP RP RP 014-0064-10 014-0064-11 014-0064-10 014-0064-09 014-0064-12 014-0064-10 014-0064-09 014-0064-11 014-0064-09 014-0064-06 Protector P/N 071-0605-02 071-0561-01 071-0561-26 071-0561-21 071-0561-21 071-0561-21 071-0561-21 071-0561-21 071-0561-07 071-0561-29 071-0561-03 071-0561-03 071-0561-07 071-0561-12 071-0561-49 071-0561-49 071-0563-00 071-0605-05 071-0603-13 071-0604-01 071-0605-03 071-0605-04 071-0604-07 071-0508-38 071-0501-44 071-0496-27 * See Section F Introduction for more information. FB5 Section_Fb.indd 5 3/4/2008 7:57:15 AM Electrical Data - Welded Compressors Model CF06K6E-PFV CF06K6E-TF5 CF06K6E-TFD CF09K6E-PFV CF09K6E-TF5 CF09K6E-TFD CF12K6E-PFV CF12K6E-TF5 CF12K6E-TFD CF12K6E-TFE CP25K8E-PFV CR14K7-PFV CR16K6-PFJ CR16K6-PFV CR16K7-PFV CR16KQ-PFV CR18K6-PFJ CR18K6-PFV CR18K7-PFV CR18KQ-PFV CR18KQ-TF5 CR18KQ-TFD CR18KQE-PFV CR18KQE-TF5 CR18KQE-TFD CR19K7-PFV Volts 208/230 200/230 380/460 208/230 200/230 380/460 208/230 200/230 380/460 575 208/230 208/230 265 208/230 208/230 208/230 265 208/230 208/230 208/230 200/230 380/460 208/230 200/230 380/460 208/230 Resistance Max PH RLA LRA Start or Run Line/Line 1 3 3 1 3 3 1 3 3 3 1 1 1 1 1 1 1 1 1 1 3 3 1 3 3 1 11.4 7 3.7 16.7 10.2 5.5 20.5 12.3 6.6 5.4 11.3 6.9 9 9.6 8.4 7.9 9.1 10.4 8.6 9 6.1 3.1 9 6.1 3.1 10.2 59.2 52 25.4 87 72.2 35.8 105 85 42 35 51 35 44 49 39 38 44 49 40 41 49 23 41 49 23 43 1.107 0 0 0.715 0 0 0.553 0 0 0 2.1 1.85 1.741 1.268 1.647 2.214 1.741 1.268 1.592 2.092 0 0 2.092 0 0 1.491 3.044 1.71 7.4 2.82 1.256 4.95 1.979 0.945 3.78 5.99 1.04 2.392 3.619 3.661 2.538 5.084 3.619 3.661 2.519 4.215 1.9 7.437 4.215 1.9 7.437 2.698 Start Cap P/N Run Cap P/N Relay P/N Part Type* 014-0061-04 014-0064-06 040-0166-15 RP 014-0058-32 014-0064-08 040-0166-15 RP 014-0058-00 014-0064-14 040-0166-19 RP 014-0061-04 014-0058-32 014-0058-31 014-0058-22 014-0058-32 014-0058-03 014-0058-31 014-0058-32 014-0058-32 014-0058-03 014-0064-06 014-0064-07 014-0064-05 014-0064-05 014-0064-07 014-0064-11 014-0064-11 014-0064-05 014-0064-07 014-0064-12 040-0166-19 040-0166-15 040-0166-15 040-0166-15 040-0166-15 040-0166-15 040-0166-15 040-0166-15 040-0166-15 040-0166-15 RP RP RP RP RP RP RP RP RP RP 014-0058-03 014-0064-12 040-0166-15 RP 014-0061-04 014-0064-06 040-0166-19 RP Protector P/N 071-0508-38 071-0501-44 071-0501-46 071-0546-04 071-0501-45 071-0501-47 071-0546-08 071-0501-56 071-0496-20 071-0614-00 071-0546-25 071-0546-19 071-0508-34 071-0508-72 071-0546-10 071-0521-17 071-0508-34 071-0508-72 071-0546-20 071-0521-18 071-0501-60 071-0501-63 071-0521-18 071-0501-60 071-0501-63 071-0508-38 * See Section F Introduction for more information. FB6 Section_Fb.indd 6 3/4/2008 7:57:15 AM Electrical Data - Welded Compressors Model Volts CR20K6-PFV CR20KQ-PFV CR20KQE-PFV CR21K7-PFV CR22K6-PFJ CR22K6-PFV CR22K6-TF5 CR22K6-TFD CR22KQ-PFV CR22KQE-PFV CR23K7-PFV CR24K6-PFJ CR24K6-PFV CR24K6-TF5 CR24K6-TFD CR24K7-PFV CR24KQ-PFV CR24KQ-TF5 CR24KQ-TFD CR24KQE-PFV CR24KQE-TF5 CR24KQE-TFD CR28K6-PFJ CR28K6-PFV CR28K6-TF5 CR28K6-TFD 208/230 208/230 208/230 208/230 265 208/230 200/230 380/460 208/230 208/230 208/230 265 208/230 200/230 380/460 208/230 208/230 200/230 380/460 208/230 200/230 380/460 265 208/230 200/230 460 Resistance Max PH RLA LRA Start or Run Line/Line 1 1 1 1 1 1 3 3 1 1 1 1 1 3 3 1 1 3 3 1 3 3 1 1 3 3 10.6 10.4 10.4 11.3 9.9 10.9 7.5 3.9 11.1 11.1 10.8 10.9 12.4 7.7 4 12 13.6 7.5 3.7 13.6 7.5 3.7 13.9 15.3 10 4.8 50 54 54 51 55 50 51 25 51.5 51.5 49 58 61 55 28 60 70.5 51 25 70.5 51 25 73 75 68 34 1.268 1.529 1.529 1.322 1.332 1.268 0 0 1.626 1.626 1.251 1.346 0.999 0 0 1.163 0.862 0 0 0.862 0 0 0.986 0.74 0 0 3.661 4.003 4.003 2.538 3.807 3.661 1.77 7.4 3.424 3.424 2.026 2.646 2.594 1.609 6.386 2.101 3.337 1.97 7.4 3.337 1.97 7.4 3.649 2.3 1.3 5.43 Start Cap P/N Run Cap P/N Relay P/N Part Type* 014-0061-04 014-0058-32 014-0058-32 014-0061-04 014-0058-34 014-0061-04 014-0064-06 014-0064-06 014-0064-06 014-0064-06 014-0064-06 014-0064-06 040-0166-19 040-0166-15 040-0166-15 040-0166-19 040-0166-15 040-0166-19 RP RP RP RP RP RP 014-0058-03 014-0058-03 014-0058-00 014-0058-26 014-0058-03 014-0064-13 014-0064-13 014-0064-08 014-0064-13 014-0064-07 040-0166-44 040-0166-44 040-0166-15 040-0166-19 040-0166-15 RP RP RP RP RP 014-0058-00 014-0058-03 014-0064-08 014-0064-13 040-0166-15 040-0166-15 RP RP 014-0058-03 014-0064-13 040-0166-15 RP 014-0036-18 014-0061-04 014-0064-13 014-0064-07 040-0166-15 040-0166-19 RP RP Protector P/N 071-0508-72 071-0521-14 071-0521-14 071-0508-38 071-0508-50 071-0508-72 071-0501-01 071-0501-00 071-0521-16 071-0521-16 071-0546-12 071-0508-52 071-0508-35 071-0502-08 071-0502-00 071-0546-12 071-0521-20 071-0501-62 071-0501-00 071-0521-20 071-0501-62 071-0501-00 071-0508-48 071-0521-02 071-0501-05 071-0502-12 * See Section F Introduction for more information. FB7 Section_Fb.indd 7 3/4/2008 7:57:16 AM Electrical Data - Welded Compressors Model CR28K7-PFV CR28K7-TF5 CR28KQ-PFV CR28KQ-TF5 CR28KQ-TFD CR28KQE-PFV CR28KQE-TF5 CR28KQE-TFD CR30K6-PFJ CR30K6-PFV CR30K6-TF5 CR30K6-TFD CR30KQ-PFV CR30KQ-TFD CR30KQE-PFV CR30KQE-TFD CR31K7-PFV CR31K7-TF5 CR32K6-PFJ CR32K6-PFV CR32K6-TF5 CR32K6-TFD CR32K6-TFE CR32KQ-PFV CR32KQ-TF5 CR32KQ-TFD Volts 208/230 200/230 208/230 200/230 380/460 208/230 200/230 380/460 265 208/230 200/230 460 208/230 380/460 208/230 380/460 208/230 200/230 265 208/230 200/230 460 575 208/230 200/230 380/460 Resistance Max PH RLA LRA Start or Run Line/Line 1 3 1 3 3 1 3 3 1 1 3 3 1 3 1 3 1 3 1 1 3 3 3 1 3 3 13.6 10 15 8.9 4.4 15 8.9 4.4 13.6 16 10.4 4.9 15.4 4.7 15.4 4.7 16.1 9.1 15 16.1 10 5.1 3.8 17 9.9 5.1 73 65.5 70.5 60.5 30 70.5 60.5 30 64 82 65.5 33 78 32 78 32 82 66 83 82 70 33 27 83 63 32 0.847 0 0.862 0 0 0.862 0 0 1.096 0.715 0 0 0.82 0 0.82 0 0.715 0 0.91 0.751 0 0 0 0.721 0 0 2.131 1.256 3.337 1.28 5.05 3.337 1.28 5.05 3.02 2.82 1.256 4.95 3.045 4.96 3.045 4.96 2.82 1.256 2.955 3.2 1.133 4.3 7.48 2.775 1.24 4.99 Start Cap P/N Run Cap P/N Relay P/N Part Type* 014-0058-32 014-0064-13 040-0166-15 RP 014-0058-03 014-0064-13 040-0166-15 RP 014-0058-03 014-0064-13 040-0166-15 RP 014-0058-32 014-0058-32 014-0064-14 014-0064-07 040-0166-15 040-0166-15 RP RP 014-0058-03 014-0064-13 040-0166-15 RP 014-0058-03 014-0064-13 040-0166-15 RP 014-0058-32 014-0064-13 040-0166-15 RP 014-0058-32 014-0058-32 014-0064-13 014-0064-13 040-0166-14 040-0166-14 RP RP 040-0166-15 RP 014-0058-32 Protector P/N 071-0546-17 071-0477-06 071-0521-20 071-0501-62 071-0501-00 071-0521-20 071-0501-62 071-0501-00 071-0508-63 071-0508-31 071-0477-06 071-0501-25 071-0521-19 071-0501-26 071-0521-19 071-0501-26 071-0508-31 071-0501-68 071-0508-51 071-0492-02 071-0501-20 071-0501-25 071-0496-21 071-0521-11 071-0501-59 071-0501-64 * See Section F Introduction for more information. FB8 Section_Fb.indd 8 3/4/2008 7:57:16 AM Electrical Data - Welded Compressors Model Volts CR32KQE-PFV CR32KQE-TF5 CR32KQE-TFD CR33KQ-PFV CR33KQ-TF5 CR33KQ-TFD CR33KQE-PFV CR33KQE-TF5 CR33KQE-TFD CR34K6-PFV CR34KQ-PFV CR34KQ-TF5 CR34KQ-TFD CR34KQE-PFV CR34KQE-TF5 CR34KQE-TFD CR35K6-PFV CR35K6-TF5 CR35K6-TFD CR35K6-TFE CR35K7-PFV CR36KQ-PFV CR36KQ-TF5 CR36KQ-TFD CR36KQE-PFV CR36KQE-TF5 208/230 200/230 380/460 208/230 200/230 460 208/230 200/230 460 208/230 208/230 200/230 460 208/230 200/230 460 208/230 200/230 460 575 208/230 208/230 200/230 460 208/230 200/230 Resistance Max PH RLA LRA Start or Run Line/Line 1 3 3 1 3 3 1 3 3 1 1 3 3 1 3 3 1 3 3 3 1 1 3 3 1 3 17 9.9 5.1 16 10.6 4.7 16 10.6 4.7 16.6 16.7 11.8 5.4 16.7 11.8 5.4 18 11.4 4.8 4.1 18.2 17.6 12.4 5.5 17.6 12.4 83 63 32 75 69 31.6 75 69 31.6 96 84 67 29.2 84 67 29.2 96 75 40 31 89 93 68 34.5 93 68 0.721 0 0 0.865 0 0 0.865 0 0 0.639 0.74 0 0 0.74 0 0 0.623 0 0 0 0.61 0.711 0 0 0.711 0 2.775 1.24 4.99 3.626 1.28 5.05 3.626 1.28 5.05 1.911 3.352 1.24 5.85 3.352 1.24 5.85 2.333 1.058 4.11 6.5 2.08 3.152 1.13 4.43 3.152 1.13 Start Cap P/N Run Cap P/N 014-0058-32 Relay P/N Part Type* 040-0166-15 RP 014-0058-00 014-0064-14 040-0166-14 RP 014-0058-00 014-0064-14 040-0166-14 RP 014-0058-00 014-0058-00 014-0064-29 014-0064-14 040-0166-15 040-0166-14 RP RP 014-0058-00 014-0064-14 040-0166-14 RP 014-0058-00 014-0064-08 040-0166-15 RP 014-0058-00 014-0058-00 014-0064-13 014-0064-14 040-0166-15 040-0166-14 RP RP 014-0058-00 014-0064-14 040-0166-14 RP Protector P/N 071-0521-11 071-0501-59 071-0501-64 071-0508-77 071-0501-36 071-0501-35 071-0508-77 071-0501-36 071-0501-35 071-0508-30 071-0508-79 071-0501-16 071-0501-32 071-0508-79 071-0501-16 071-0501-32 071-0508-30 071-0501-13 071-0496-13 071-0477-15 071-0508-78 071-0508-78 071-0501-38 071-0501-37 071-0508-78 071-0501-38 * See Section F Introduction for more information. FB9 Section_Fb.indd 9 3/4/2008 7:57:17 AM Electrical Data - Welded Compressors Model CR36KQE-TFD CR37KQ-PFV CR37KQ-TF5 CR37KQ-TFD CR37KQ-TFE CR37KQE-PFV CR37KQE-TF5 CR37KQE-TFD CR38K6-PFV CR38K6-TF5 CR38K6-TFD CR38K6-TFE CR41KQ-PFV CR41KQ-TF5 CR41KQ-TFD CR41KQE-PFV CR41KQE-TF5 CR41KQE-TFD CR42K6-PFV CR42K6-TF5 CR42K6-TFD CR42K6-TFE CR47KQ-PFV CR47KQ-TF5 CR47KQ-TFD CR47KQ-TFE Volts 460 208/230 200/230 380/460 575 208/230 200/230 380/460 208/230 200/230 380/460 575 208/230 200/230 380/460 208/230 200/230 380/460 208/230 200/230 460 575 208/230 200/230 380/460 575 Resistance Max PH RLA LRA Start or Run Line/Line 3 1 3 3 3 1 3 3 1 3 3 3 1 3 3 1 3 3 1 3 3 3 1 3 3 3 5.5 18.6 11.1 5.6 4.8 18.6 11.1 5.6 19 11.9 5.9 4.8 19.4 13.1 5.9 19.4 13.1 5.9 20.4 14 6.4 5.2 24.6 16.1 8.2 5.6 34.5 100 85 39 34.39 100 85 39 105 85 42 34 109.6 80 42 109.6 80 42 102 91 42 39 132 97 50 38.6 0 0.664 0 0 0 0.664 0 0 0.553 0 0 0 0.601 0 0 0.601 0 0 0.585 0 0 0 0.457 0 0 0 4.43 2.431 1.07 3.693 5.99 2.431 1.07 3.693 1.979 0.945 3.78 5.9 2.324 1.04 4.06 2.324 1.04 4.06 2.37 0.875 3.45 5.315 2.148 0.82 3.22 5.026 Start Cap P/N Run Cap P/N Relay P/N Part Type* 014-0058-00 014-0064-08 040-0166-19 RP 014-0058-00 014-0064-08 040-0166-19 RP 014-0058-00 014-0064-14 040-0166-19 RP 014-0058-00 014-0064-16 040-0166-27 RP 014-0058-00 014-0064-16 040-0166-27 RP 014-0058-00 014-0064-14 040-0166-27 RP 014-0058-00 014-0064-15 040-0166-18 RP Protector P/N 071-0501-37 071-0508-12 071-0501-31 071-0496-09 071-0614-02 071-0508-12 071-0501-31 071-0496-09 071-0508-42 071-0502-09 071-0496-20 071-0477-12 071-0508-12 071-0501-33 071-0501-29 071-0508-12 071-0501-33 071-0501-29 071-0508-19 071-0501-18 071-0477-09 071-0477-14 071-0546-07 071-0501-53 071-0501-57 071-0614-01 * See Section F Introduction for more information. FB10 Section_Fb.indd 10 3/4/2008 7:57:17 AM Electrical Data - Welded Compressors Model CR47KQE-PFV CR47KQE-TF5 CR47KQE-TFD CR53KQ-PFV CR53KQ-TF5 CR53KQ-TFD CR53KQ-TFE CR53KQE-PFV CR53KQE-TF5 CR53KQE-TFD CR60K5-PFV CR60K5-TF5 CR60K5-TFD CR60KQ-PFV CR60KQ-TFD CRN5-0500-PFV CRN5-0500-TF5 CRN5-0500-TFD CRN5-0500-TFE CRNQ-0500-PFV CRNQ-0500-TF5 CRNQ-0500-TFD CRNQ-0500-TFE CRNQ-050E-TF5 CRNQ-050E-TFD CRP5-0450-PFV Volts 208/230 200/230 380/460 208/230 200/230 380/460 575 208/230 200/230 380/460 208/230 200/230 380/460 208/230 380/460 208/230 200/230 380/460 575 208/230 200/230 380/460 575 200/230 380/460 208/230 Resistance Max PH RLA LRA Start or Run Line/Line 1 3 3 1 3 3 3 1 3 3 1 3 3 1 3 1 3 3 3 1 3 3 3 3 3 1 24.6 132 0.457 16.1 97 0 8.2 50 0 28.9 140 0.424 18.2 107 0 9.1 55 0 6 45.6 0 28.9 140 0.424 18.2 107 0 9.1 55 0 30.7 135 0.405 19.6 105 0 10.4 55 0 30.7 135 0.405 10.4 55 0 34.3 142 0.382 21.4 130 0 9.6 65 0 7.9 52 0 34.3 142 0.382 21.4 130 0 9.6 65 0 7.9 52 0 21.4 130 0 9.6 65 0 30.7 135 0.405 2.148 0.82 3.22 2.022 0.705 2.77 4.4 2.022 0.705 2.77 1.33 0.79 2.83 1.33 2.83 1.36 0.639 2.47 4.35 1.36 0.639 2.47 4.35 0.639 2.47 1.33 Start Cap P/N Run Cap P/N Relay P/N Part Type* 014-0058-00 014-0064-15 040-0166-18 RP 014-0058-00 014-0064-18 040-0166-18 RP 014-0058-00 014-0064-18 040-0166-18 RP 014-0058-00 014-0064-15 040-0166-27 RP 014-0058-00 014-0064-15 040-0166-27 RP 014-0006-15 014-0064-17 040-0166-27 RP 014-0006-15 014-0064-17 040-0166-27 RP 014-0058-00 014-0064-15 040-0166-27 RP Protector P/N 071-0546-07 071-0501-53 071-0501-57 071-0509-02 071-0501-53 071-0501-48 071-0614-01 071-0509-02 071-0501-53 071-0501-48 071-0508-09 071-0428-07 071-0428-02 071-0508-09 071-0428-02 071-0483-00 071-0526-00 071-0526-01 071-0428-05 071-0483-00 071-0526-00 071-0526-01 071-0428-05 071-0526-00 071-0526-01 071-0508-09 * See Section F Introduction for more information. FB11 Section_Fb.indd 11 3/4/2008 7:57:18 AM Electrical Data - Welded Compressors Model Volts CRP5-0450-TF5 CRP5-0450-TFD CRP5-0450-TFE CRPQ-0450-PFV CRPQ-0450-TF5 CRPQ-0450-TFD CRPQ-0450-TFE CRT5-0450-PFV CRT5-0450-TF5 CRT5-0450-TFD CRT5-0450-TFE CRTQ-0450-PFV CRTQ-0450-TF5 CRTQ-0450-TFD CRTQ-0450-TFE CRTQ-045E-TF5 CRTQ-045E-TFD CS08KQE-PFV CS10K6E-PFJ CS10K6E-PFV CS10K6E-TF5 CS10K6E-TFD CS12K6E-PFJ CS12K6E-PFV CS12K6E-TF5 CS13K6E-PFV 200/230 380/460 575 208/230 200/230 380/460 575 208/230 200/230 380/460 575 208/230 200/230 380/460 575 200/230 380/460 208/230 265 208/230 200/230 380/460 265 208/230 200/230 208/230 Resistance Max PH RLA LRA Start or Run Line/Line 3 3 3 1 3 3 3 1 3 3 3 1 3 3 3 3 3 1 1 1 3 3 1 1 3 1 19.6 10.4 7 30.7 19.6 10.4 7 30.7 19.6 10.4 7 30.7 19.6 10.4 7 19.6 10.4 10.1 8.6 10.9 7.5 3.6 10.9 10.9 7.5 14.4 105 55 45 135 105 55 45 135 105 55 45 135 105 55 45 105 55 54 55 56 51 25 55 56 51 73 0 0 0 0.405 0 0 0 0.405 0 0 0 0.405 0 0 0 0 0 1.107 1.332 1.107 0 0 1.332 1.107 0 0.847 0.79 2.83 4.71 1.33 0.79 2.83 4.71 1.33 0.79 2.83 4.71 1.33 0.79 2.83 4.71 0.79 2.83 3.044 3.807 3.044 1.77 7.4 3.807 3.044 1.77 2.131 Start Cap P/N Run Cap P/N Relay P/N Part Type* 014-0058-00 014-0064-15 040-0166-27 RP 014-0058-00 014-0064-15 040-0166-27 RP 014-0058-00 014-0064-15 040-0166-27 RP 014-0058-32 014-0036-18 014-0061-04 014-0064-06 014-0064-06 014-0064-06 040-0166-15 040-0166-15 040-0166-19 RP RP RP 014-0036-18 014-0061-04 014-0064-06 014-0064-06 040-0166-15 040-0166-19 RP RP 014-0058-00 014-0064-13 040-0166-15 RP Protector P/N 071-0428-07 071-0428-02 071-0428-11 071-0508-09 071-0428-07 071-0428-02 071-0428-11 071-0508-09 071-0428-07 071-0428-02 071-0428-11 071-0508-09 071-0428-07 071-0428-02 071-0428-11 071-0428-07 071-0428-02 071-0508-38 071-0508-50 071-0508-38 071-0501-01 071-0501-00 071-0508-50 071-0508-38 071-0501-01 071-0546-17 * See Section F Introduction for more information. FB12 Section_Fb.indd 12 3/4/2008 7:57:18 AM Electrical Data - Welded Compressors Model Volts CS13K6E-TF5 CS14K6E-PFJ CS14K6E-PFV CS14K6E-TF5 CS14K6E-TFD CS16K6E-PFV CS17K6E-PFV CS18K6E-PFJ CS18K6E-PFV CS18K6E-TF5 CS18K6E-TFD CS18K6E-TFE CS20K6E-PFV CS20K6E-TF5 CS20K6E-TFD CS24K6E-PFV CS24K6E-TF5 CS27K3E-TF5 CS27K3E-TFD CS27K6E-PFV CS27K6E-TF5 CS27K6E-TFD CS33K3E-PFV CS33K3E-TF5 CS33K3E-TFC CS33K3E-TFD 200/230 265 208/230 200/230 380/460 208/230 208/230 265 208/230 200/230 460 575 208/230 200/230 460 208/230 200/230 200/230 380/460 208/230 200/230 460 208/230 200/230 208/230 380/460 Resistance Max PH RLA LRA Start or Run Line/Line 3 1 1 3 3 1 1 1 1 3 3 3 1 3 3 1 3 3 3 1 3 3 1 3 3 3 9 66 0 12.5 58 1.346 12.5 61 0.999 9.1 55 0 4.7 28 0 15.5 73 0.847 16 82 0.727 13.6 64 1.096 16 82 0.715 8.8 65.5 0 4.7 33 0 4.4 25.4 0 18.6 96 0.623 11.4 75 0 5.1 40 0 23.9 121 0.5 14 105 0 15.6 82 0 8.4 41 0 23.9 121 0.5 13.4 105 0 8.4 52 0 30.7 125 0.44 20.7 90 0 20.7 90 0 9.9 45 0 1.256 2.646 2.594 1.609 6.386 2.131 2.367 3.02 2.82 1.256 4.95 7.48 2.333 1.058 4.11 2.302 0.853 0.994 3.96 2.302 0.853 3.413 2.1 0.853 0.853 3.413 Start Cap P/N Run Cap P/N Relay P/N Part Type* 014-0061-04 014-0058-03 014-0064-13 014-0064-07 040-0166-19 040-0166-15 RP RP 014-0061-16 014-0058-00 014-0058-32 014-0058-32 014-0064-13 014-0064-13 014-0064-14 014-0064-07 040-0166-14 040-0166-15 040-0166-15 RP RP RP 014-0058-00 014-0064-08 040-0166-15 RP 014-0058-00 014-0064-14 040-0166-23 RP 014-0058-00 014-0064-14 040-0166-23 RP 014-0058-00 014-0064-16 040-0166-27 RP Protector P/N 071-0501-68 071-0508-52 071-0508-35 071-0502-08 071-0502-00 071-0546-17 071-0521-03 071-0508-63 071-0508-31 071-0477-06 071-0501-26 071-0614-03 071-0508-30 071-0501-13 071-0496-13 071-0546-03 071-0501-49 071-0417-01 071-0417-06 071-0546-03 071-0501-49 071-0501-50 071-0508-37 071-0417-00 071-0417-00 071-0417-12 * See Section F Introduction for more information. FB13 Section_Fb.indd 13 3/4/2008 7:57:18 AM Electrical Data - Welded Compressors Model Volts CS33K6E-PFV CS33K6E-TF5 CS33K6E-TFD CTH1-0275-CSV CTH1-0275-TSC CTL1-0350-CSV CTL1-0350-TSC CTM1-0400-CSV CTM1-0400-TSC CTN1-0500-TSC CTN1-0501-CSV REBQ-0150-PFJ REBQ-0150-PFV REKQ-0125-PFJ REKQ-0125-PFV RF18C1E-IAA RF18C1E-IAV RF18C2E-IAA RF18C2E-IAV RF40C1E-CAA RF40C1E-CAV RF41C1E-CAA RF41C1E-CAV RF41C5E-CAA RF41C5E-CAV RF42C1E-CAA 208/230 200/230 460 208/230 208/230 208/230 208/230 208/230 208/230 208/230 208/230 265 208/230 265 208/230 115 208/230 115 208/230 115 208/230 115 208/230 115 208/230 115 Resistance Max PH RLA LRA Start or Run Line/Line 1 3 3 1 3 1 3 1 3 3 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 30.7 18.7 9.9 19.6 14.1 24.1 17.6 34.3 22.1 25.2 35.7 7.4 7.9 6.9 8.5 12.9 7.1 12.9 7.1 15.4 6.1 15.4 7.9 15.4 7.9 16 125 0.424 102 0 48 0 3.8 0 2.81 0 2.18 0 0 2.02 39.6 1.97 49.7 1.58 40 1.97 49.7 1.58 66.3 0.455 25 3.09 66.3 0.455 25 3.09 64 0.51 24.1 2.1 76.5 0.415 40 1.65 64 0.51 40 1.65 72.5 0.409 2.022 0.853 3.413 0.933 2.04 0.751 1.48 0.674 1.39 1.14 0.574 5.37 4.353 5.37 4.353 2.245 13.32 2.245 13.32 2.8 18.3 3.22 6.3 2.8 6.3 5.39 Start Cap P/N Run Cap P/N Relay P/N Part Type* 014-0006-15 014-0064-17 040-0166-27 RP 014-0058-03 014-0064-13 040-0001-84 RP 014-0058-13 014-0064-15 040-0001-86 RP 014-0058-04 014-0064-16 040-0001-83 RP 014-0058-04 014-0036-17 014-0064-17 014-0064-12 014-0064-05 014-0064-12 014-0064-05 040-0001-85 040-0166-14 RP RP 040-0166-14 RP 040-0168-03 040-0168-06 040-0168-03 040-0168-06 040-0166-14 040-0166-14 040-0166-15 040-0166-14 040-0166-14 040-0166-14 040-0166-19 RC RC RC RC RP RP RP RP RP RP RP 014-0036-17 014-0058-27 014-0058-27 014-0058-31 014-0058-17 014-0058-22 014-0058-19 014-0058-31 014-0058-19 014-0058-31 014-0064-08 014-0064-00 014-0064-07 014-0064-02 014-0064-08 014-0064-02 014-0064-05 Protector P/N 071-0546-05 071-0496-28 071-0501-54 071-0582-00 071-0582-00 071-0582-00 071-0582-00 071-0582-00 071-0582-00 071-0582-00 071-0582-00 071-0512-12 071-0512-15 071-0512-12 071-0512-15 071-0127-06 071-0329-26 071-0127-06 071-0329-26 071-0518-03 071-0527-07 071-0518-09 071-0518-10 071-0518-03 071-0518-10 071-0127-46 * See Section F Introduction for more information. FB14 Section_Fb.indd 14 3/4/2008 7:57:19 AM Electrical Data - Welded Compressors Model Volts RF42C1E-CAV RFT12C1E-IAA RFT12C1E-IAB RFT22C1E-CAA RFT22C1E-IAA RFT26C1E-CAA RFT26C1E-CAB RFT26C1E-IAA RFT26C1E-IAB RFT29C1E-CAA RFT29C1E-IAA RFT32C1E-CAA RFT32C1E-IAA RR10K1E-CAA RR10K1E-CAV RR10K2-CAA RR10K2-CAV RR10K2E-CAA RR10K2E-CAV RR12K1-PFV RR14K1-PFJ RR14K1-PFV RR16K1-PFJ RR16K1-PFV RR17K1-PFJ RR17K1-PFV 208/230 115 230 115 115 115 230 115 230 115 115 115 115 115 208/230 115 208/230 115 208/230 208/230 265 208/230 265 208/230 265 208/230 Resistance Max PH RLA LRA Start or Run Line/Line 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 8.4 6.1 2.5 7.9 7.9 10.8 5.7 10.8 5.7 13 13 15 15 15 7.3 16.9 8.3 16.9 8.3 7.1 6.9 8.5 8.4 9.5 8.2 10.4 46 1.36 33.7 0.72 15.8 2.71 54.5 0.43 54.5 0.43 66 0.04 26 2.3 66 0.04 26 2.3 66 0.4 66 0.4 56 0.34 56 0.34 78 0.412 40 1.65 78 0.412 40 1.65 78 0.412 40 1.65 35 1.96 35 2.84 40 2.09 36.1 2.44 43.3 1.52 44 2.16 48.2 1.54 4.45 4.11 13.8 2.66 2.66 2.6 8.8 2.6 8.8 2.6 2.6 2.59 2.59 4.83 6.3 4.83 6.3 4.83 6.3 4.89 5.25 4.87 4.77 4.39 4.06 3.82 Start Cap P/N Run Cap P/N Relay P/N Part Type* 014-0058-00 014-0059-14 014-0059-09 014-0058-36 014-0058-36 014-0058-36 014-0058-31 014-0058-36 014-0053-30 014-0058-36 014-0058-36 014-0058-36 014-0058-36 014-0058-26 014-0058-19 014-0058-26 014-0058-19 014-0058-26 014-0058-19 014-0058-19 014-0058-31 014-0058-19 014-0036-16 014-0058-25 014-0058-25 014-0058-25 014-0064-10 040-0166-14 040-0150-37 040-0150-04 040-0166-21 040-0172-03 040-0166-21 040-0166-26 040-0172-03 040-0150-34 040-0166-21 040-0172-03 040-0166-37 040-0166-37 040-0166-14 040-0166-14 040-0166-14 040-0166-14 040-0166-14 040-0166-14 040-0166-19 040-0166-14 040-0166-19 040-0166-15 040-0166-19 040-0166-14 040-0166-37 RP RC RC RP RC RP RP RC RC RP RC RP RP RP RP RP RP RP RP RP RP RP RP RP RP RP 014-0064-13 014-0064-13 014-0064-09 014-0064-13 014-0064-13 014-0064-06 014-0064-02 014-0064-06 014-0064-02 014-0064-06 014-0064-02 014-0064-04 014-0064-05 014-0064-05 014-0064-11 014-0064-05 014-0064-12 014-0064-06 Protector P/N 071-0127-37 071-0561-66 071-0561-64 071-0645-01 071-0645-00 071-0604-18 071-0647-09 071-0605-10 071-0561-28 071-0604-16 071-0605-05 071-0605-09 071-0605-08 071-0127-30 071-0127-05 071-0127-30 071-0127-05 071-0127-30 071-0127-05 071-0421-22 071-0512-09 071-0512-04 071-0432-16 071-0432-10 071-0512-13 071-0432-10 * See Section F Introduction for more information. FB15 Section_Fb.indd 15 3/4/2008 7:57:19 AM Electrical Data - Welded Compressors Model Volts RR17K1-TFC RR20K1-PFV RR81C1E-IAA RR81C1E-IAV RR81C2-IAA RR81C2-IAV RR81C2E-IAA RR81C2E-IAV RRG4-0100-PAA RRG4-0100-PAV RRL4-0100-CAV RRS4-0075-IAA RRS4-0075-IAV RRT62C1E-IAA RRT62C1E-IAB RRT64C1E-CAA RRT64C1E-IAA RRT73C1E-CAA RRT73C1E-IAA RS40C1E-IAA RS40C1E-IAV RS40C2-IAA RS40C2-IAV RS40C2E-IAA RS40C2E-IAV RS43C1E-CAA 208/230 208/230 115 208/230 115 208/230 115 208/230 115 208/230 208/230 115 208/230 115 230 115 115 115 115 115 208/230 115 208/230 115 208/230 115 Resistance Max PH RLA LRA Start or Run Line/Line 3 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 6.5 12.1 13.3 7.9 15.2 9 15.2 9 13.2 6.7 7.3 13.3 6.5 9.5 4.5 11 11 11 11 9 4.9 10.1 5.6 10.1 5.6 10.1 41 65 66.3 33.5 66.3 33.5 66.3 33.5 60 33.5 40 66.3 33.5 44 21 45 45 54.5 54.5 51 24.1 51 24.1 51 24.1 51 0 0.955 0.416 1.55 0.416 1.55 0.416 1.55 0.551 1.55 1.65 0.416 1.55 0.6 2.7 0.51 0.51 0.43 0.43 0.687 2.1 0.687 2.1 0.687 2.1 0.59 2.4 4.085 3.15 7.92 3.15 7.92 3.15 7.92 4.8 7.92 6.3 3.15 7.92 4.3 12.7 2.62 2.62 2.66 2.66 4.07 18.3 4.07 18.3 4.07 18.3 4.08 Start Cap P/N 014-0061-18 014-0058-22 014-0061-18 014-0058-22 014-0061-18 014-0058-22 014-0061-18 014-0058-06 014-0061-18 014-0058-19 014-0058-09 014-0061-18 014-0053-18 014-0036-24 014-0058-43 014-0058-43 014-0058-36 014-0058-36 014-0058-22 014-0058-17 014-0058-22 014-0058-17 014-0058-22 014-0058-17 014-0058-11 Run Cap P/N 014-0064-05 014-0064-05 014-0064-02 014-0064-02 014-0037-17 014-0064-13 014-0064-02 Relay P/N 040-0166-19 040-0168-03 040-0168-01 040-0168-03 040-0168-01 040-0168-03 040-0168-01 040-0166-19 040-0166-14 040-0166-14 040-0168-03 040-0168-01 040-0150-11 040-0150-04 040-0166-03 040-0172-04 040-0166-21 040-0172-03 040-0168-00 040-0168-02 040-0168-00 040-0168-02 040-0168-00 040-0168-02 040-0166-21 Part Type* RP RC RC RC RC RC RC RP RP RP RC RC RC RC RP RC RP RC RC RC RC RC RC RC RP Protector P/N 071-0481-01 071-0432-15 071-0127-18 071-0329-07 071-0127-18 071-0329-07 071-0127-18 071-0329-07 071-0127-40 071-0329-00 071-0127-05 071-0127-18 071-0329-07 071-0561-61 071-0647-11 071-0561-60 071-0647-04 071-0644-01 071-0605-01 071-0127-41 071-0329-11 071-0127-41 071-0329-11 071-0127-41 071-0329-11 071-0329-15 * See Section F Introduction for more information. FB16 Section_Fb.indd 16 3/4/2008 7:57:20 AM Electrical Data - Welded Compressors Model Volts RS43C1E-CAV RS43C1E-IAA RS43C1E-IAV RS43C2-CAA RS43C2E-CAA RS43C2E-CAV RS43C2E-IAA RS43C2E-IAV RS43CAE-CAA RS47C2-IAA RS47C2-IAV RS54C1E-IAA RS54C1E-IAV RS54C2-IAA RS54C2-IAV RS54C2E-IAA RS54C2E-IAV RS55C1E-CAV RS55C1E-PAA RS55C1E-PAV RS55C2-CAA RS55C2-CAV RS55C2E-CAA RS55C2E-CAV RS64C1E-CAA RS64C1E-CAV 208/230 115 208/230 115 115 208/230 115 208/230 115 115 208/230 115 208/230 115 208/230 115 208/230 208/230 115 208/230 115 208/230 115 208/230 115 208/230 Resistance Max PH RLA LRA Start or Run Line/Line 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 5.4 10.1 5.7 10.1 10.1 5.4 10.1 5.7 10.1 14.3 7.1 11.8 6.8 11.8 6.8 11.8 6.8 6.7 13.2 6.7 13.2 6.1 13.2 6.1 15.1 7.7 24.1 51 24.1 51 51 24.1 51 24.1 51 66.3 35.5 66.3 33.5 66.3 33.5 66.3 33.5 33.5 60 33.5 60 40 60 40 59 37 2.1 0.59 2.1 0.59 0.59 2.1 0.59 2.1 0.59 0.416 1.55 0.455 1.55 0.455 1.55 0.455 1.55 1.55 0.551 1.55 0.66 3.09 0.66 3.09 0.573 1.55 18.3 4.08 18.3 4.08 4.08 18.3 4.08 18.3 4.08 3.15 7.92 2.245 7.92 2.245 7.92 2.245 7.92 7.92 4.8 7.92 4.2 3.82 4.2 3.82 5.68 7.92 Start Cap P/N Run Cap P/N Relay P/N Part Type* 014-0058-17 014-0058-11 014-0058-17 014-0058-11 014-0058-11 014-0058-17 014-0058-11 014-0058-17 014-0058-11 014-0058-27 014-0058-19 014-0058-27 014-0058-18 014-0058-27 014-0058-18 014-0058-27 014-0058-18 014-0061-18 014-0058-06 014-0061-18 014-0058-00 014-0058-04 014-0058-00 014-0058-04 014-0058-25 014-0058-14 014-0064-00 040-0166-14 040-0168-00 040-0168-02 040-0166-21 040-0166-21 040-0166-14 040-0168-00 040-0168-02 040-0166-21 040-0168-03 040-0168-01 040-0168-03 040-0168-01 040-0168-03 040-0168-01 040-0168-03 040-0168-01 040-0166-14 040-0166-19 040-0166-14 040-0166-19 040-0166-14 040-0166-19 040-0166-14 040-0166-02 040-0166-14 RP RC RC RP RP RP RC RC RP RC RC RC RC RC RC RC RC RP RP RP RP RP RP RP RP RP 014-0064-02 014-0064-02 014-0064-00 014-0064-02 014-0064-02 014-0064-05 014-0064-02 014-0064-05 014-0064-05 014-0064-05 014-0064-05 014-0064-12 014-0064-02 Protector P/N 071-0329-10 071-0329-15 071-0329-11 071-0329-15 071-0329-15 071-0329-10 071-0329-15 071-0329-11 071-0329-15 071-0127-30 071-0370-29 071-0127-06 071-0329-04 071-0127-06 071-0329-04 071-0127-06 071-0329-04 071-0329-30 071-0127-40 071-0329-30 071-0518-02 071-0527-08 071-0518-02 071-0527-08 071-0127-43 071-0329-16 * See Section F Introduction for more information. FB17 Section_Fb.indd 17 3/4/2008 7:57:20 AM Electrical Data - Welded Compressors Model RS64C1E-IAV RS64C1E-PAA RS64C1E-PFA RS64C2-CAA RS64C2-CAV RS64C2-IAV RS64C2-PAA RS64C2E-CAA RS64C2E-CAV RS64C2E-IAV RS64C2E-PAA RS70C1-PAA RS70C1-PFJ RS70C1-PFV RS70C1-TFC RS70C1-TFD RS70C1E-PFJ RS70C1E-PFV RS70C1E-TFC RS70C1E-TFD RS73C1E-PFJ RS80C1E-CAA RS80C1E-CAV RS80C1E-TF5 RS80C1E-TFD RS80C2-CAA Volts 208/230 115 115 115 208/230 208/230 115 115 208/230 208/230 115 115 265 208/230 208/230 460 265 208/230 208/230 460 265 115 208/230 200/230 460 115 Resistance Max PH RLA LRA Start or Run Line/Line 1 1 1 1 1 1 1 1 1 1 1 1 1 1 3 3 1 1 3 3 1 1 1 3 3 1 9.2 15.1 15.1 13.2 7.7 9.2 13.2 15.1 7.7 9.2 15.1 16.7 6 7 4.7 2.6 6 7 4.7 2.6 8.2 18.6 9.6 6.4 2.5 18.6 45 59 59 59 37 45 59 59 37 45 59 72.5 30 34.2 31 15 30 34.2 31 15 39.6 72.5 46 41 15 72.5 1.56 0.573 0.573 0.573 1.55 1.56 0.573 0.573 1.55 1.56 0.573 0.409 3.42 1.96 0 0 3.42 1.96 0 0 1.97 0.409 1.36 0 0 0.409 7.45 5.68 5.68 5.68 7.92 7.45 5.68 5.68 7.92 7.45 5.68 5.39 5.1 4.89 3.72 14.3 5.1 4.89 3.72 14.3 5.37 5.39 4.45 2.4 14.3 5.39 Start Cap P/N 014-0058-19 014-0058-25 014-0058-25 014-0058-25 014-0058-14 014-0058-19 014-0058-25 014-0058-25 014-0058-14 014-0058-19 014-0058-25 014-0058-18 014-0036-17 014-0058-19 Run Cap P/N Relay P/N Part Type* 014-0064-12 014-0064-06 014-0064-05 014-0064-05 040-0168-00 040-0166-02 040-0166-02 040-0166-02 040-0166-14 040-0168-00 040-0166-02 040-0166-02 040-0166-14 040-0168-00 040-0166-02 040-0166-19 040-0166-19 040-0166-19 RC RP RP RP RP RC RP RP RP RC RP RP RP RP 014-0036-17 014-0058-19 014-0064-05 014-0064-05 040-0166-19 040-0166-19 RP RP 014-0036-17 014-0058-31 014-0058-00 014-0064-12 014-0064-05 014-0064-10 040-0166-14 040-0166-19 040-0166-14 RP RP RP 014-0058-31 014-0064-05 040-0166-19 RP 014-0064-12 014-0064-12 014-0064-12 014-0064-02 014-0064-12 014-0064-12 014-0064-02 Protector P/N 071-0127-37 071-0127-43 071-0546-13 071-0127-43 071-0329-16 071-0127-37 071-0127-43 071-0127-43 071-0329-16 071-0127-37 071-0127-43 071-0127-18 071-0432-11 071-0432-09 071-0481-00 071-0481-02 071-0432-11 071-0432-09 071-0481-00 071-0481-02 071-0512-12 071-0127-46 071-0127-37 071-0481-01 071-0481-02 071-0127-46 * See Section F Introduction for more information. FB18 Section_Fb.indd 18 3/4/2008 7:57:20 AM Electrical Data - Welded Compressors Model Volts RS80C2-CAV RS80C2-TF5 RS80C2-TFD RS80C2E-CAA RS80C2E-CAV RS80C2E-TF5 RS80C2E-TFD RS86C1E-PFJ RS86C1E-PFV RS86C2E-PFV RS97C1E-CAA RS97C1E-CAV RS97C1E-TFC RS97C2-CAA RS97C2-CAV RS97C2-TFC RS97C2E-CAA RS97C2E-CAV RS97C2E-TFC RSE4-0075-IAA RSE4-0075-IAV RSE4-0076-IAA RSE4-0076-IAV RSF5-0075-CAA RSL2-0075-IAA RSL2-0075-IAV 208/230 200/230 460 115 208/230 200/230 460 265 208/230 208/230 115 208/230 208/230 115 208/230 208/230 115 208/230 208/230 115 208/230 115 208/230 115 115 208/230 Resistance Max PH RLA LRA Start or Run Line/Line 1 3 3 1 1 3 3 1 1 1 1 1 3 1 1 3 1 1 3 1 1 1 1 1 1 1 9.6 6.4 2.5 18.6 9.6 6.4 2.5 8.9 9.8 9.8 20.7 11 7 20.7 10.4 7 20.7 11 7 14.3 7.1 14.3 7.1 13.5 11.8 6.8 46 41 15 72.5 46 41 15 36.1 43.3 43.3 95 51 35 95 51 35 95 51 35 66.3 35.5 66.3 35.5 72.7 66.3 33.5 1.36 0 0 0.409 1.36 0 0 2.44 1.41 1.41 0.324 1.12 0 0.324 1.12 0 0.324 1.12 0 0.416 1.55 0.416 1.55 0.416 0.455 1.55 4.45 2.4 14.3 5.39 4.45 2.4 14.3 4.77 2.65 2.65 4.142 4.92 2.58 4.142 4.92 2.58 4.142 4.92 2.58 3.15 7.92 3.15 7.92 3.15 2.245 7.92 Start Cap P/N Run Cap P/N Relay P/N Part Type* 014-0058-00 014-0064-10 040-0166-14 RP 014-0058-31 014-0058-00 014-0064-05 014-0064-10 040-0166-19 040-0166-14 RP RP 014-0036-16 014-0058-25 014-0058-25 014-0061-04 014-0036-17 014-0064-11 014-0064-06 014-0064-06 014-0064-07 014-0064-11 040-0166-15 040-0166-19 040-0166-19 040-0166-18 040-0166-14 RP RP RP RP RP 014-0061-04 014-0036-17 014-0064-07 014-0064-11 040-0166-18 040-0166-14 RP RP 014-0061-04 014-0036-17 014-0064-07 014-0064-11 040-0166-18 040-0166-14 RP RP 040-0168-03 040-0168-01 040-0168-03 040-0168-01 040-0166-21 040-0168-03 040-0168-01 RC RC RC RC RP RC RC 014-0058-27 014-0058-19 014-0058-27 014-0058-19 014-0058-27 014-0058-27 014-0061-18 014-0064-17 Protector P/N 071-0127-37 071-0481-01 071-0481-02 071-0127-46 071-0127-37 071-0481-01 071-0481-02 071-0432-16 071-0421-21 071-0546-01 071-0127-45 071-0127-24 071-0404-01 071-0127-45 071-0127-24 071-0404-01 071-0127-45 071-0127-24 071-0404-01 071-0127-30 071-0370-29 071-0127-30 071-0370-29 071-0506-00 071-0127-06 071-0329-04 * See Section F Introduction for more information. FB19 Section_Fb.indd 19 3/4/2008 7:57:21 AM Electrical Data - Welded Compressors Model Volts RSL2-0100-CAA RSL2-0100-CAV RSL2-0101-CAA RSL2-0101-CAV RSL5-0100-CAV RSL5-0100-TFC RSL5-0101-CAV RSL5-0101-TFC RSN4-0050-IAA RSN4-0050-IAV RSN4-0075-CAV RSN4-0075-IAA RSN4-0075-IAV RSN4-0075-PAA RSN4-0100-CAV RSN4-0100-PAA RSN6-0075-CAA RSN6-0075-IAA RSN6-0075-IAV RST40C1E-CAA RST40C1E-CAB RST40C1E-CAV RST40C1E-IAA RST40C1E-IAB RST40C1E-IAV RST45C1E-CAA 115 208/230 115 208/230 208/230 208/230 208/230 208/230 115 208/230 208/230 115 208/230 115 208/230 115 115 115 208/230 115 230 208/230 115 230 208/230 115 Resistance Max PH RLA LRA Start or Run Line/Line 1 1 1 1 1 3 1 3 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 18 10.4 18 10.4 9.4 5.7 9.4 5.7 9 4.9 7.7 14.9 8.8 10.3 7.7 10.3 12.1 14.3 6.9 9 5.3 5.1 9 5.3 5.1 10.5 78 51 78 51 51 35 51 35 51 24.1 37 66.3 45 50 37 50 75 66.3 45 50 25 27 50 25 27 54.5 0.412 1.12 0.412 1.12 1.12 0 1.12 0 0.687 2.1 1.55 0.416 1.56 0.585 1.55 0.585 0.483 0.416 1.56 0.51 2.7 1.91 0.51 2.7 1.91 0.43 4.83 4.92 4.83 4.92 4.92 2.58 4.92 2.58 4.07 18.3 7.92 3.15 7.45 5.07 7.92 5.07 5.54 3.15 7.45 2.62 12.7 6.38 2.62 12.7 6.38 2.66 Start Cap P/N Run Cap P/N Relay P/N Part Type* 014-0058-26 014-0036-17 014-0058-26 014-0036-17 014-0036-17 014-0064-06 014-0064-11 014-0064-06 014-0064-11 014-0064-11 040-0166-14 040-0166-14 040-0166-14 040-0166-14 040-0166-14 RP RP RP RP RP 014-0036-17 014-0064-11 040-0166-14 RP 040-0168-00 040-0168-02 040-0166-14 040-0168-03 040-0168-04 040-0166-19 040-0166-14 040-0166-19 040-0166-15 040-0168-03 040-0168-04 040-0166-03 040-0166-26 040-0166-18 040-0150-37 040-0150-14 040-0150-31 040-0166-21 RC RC RP RC RC RP RP RP RP RC RC RP RP RP RC RC RC RP 014-0058-22 014-0058-17 014-0058-14 014-0058-27 014-0058-14 014-0058-06 014-0058-14 014-0058-06 014-0061-04 014-0058-27 014-0058-14 014-0036-24 014-0036-24 014-0058-31 014-0059-20 014-0059-09 014-0053-30 014-0036-24 014-0064-02 014-0064-05 014-0064-02 014-0064-05 014-0064-02 014-0064-13 014-0064-13 014-0064-33 014-0064-13 Protector P/N 071-0127-30 071-0127-24 071-0127-30 071-0127-24 071-0127-24 071-0404-01 071-0127-24 071-0404-01 071-0127-34 071-0329-11 071-0329-16 071-0127-30 071-0127-05 071-0127-19 071-0329-16 071-0127-19 071-0127-42 071-0127-30 071-0127-05 071-0561-48 071-0561-57 071-0561-23 071-0561-56 071-0561-12 071-0561-65 071-0604-10 * See Section F Introduction for more information. FB20 Section_Fb.indd 20 3/4/2008 7:57:21 AM Electrical Data - Welded Compressors Model Volts RST45C1E-CAV RST45C1E-IAA RST45C1E-IAV RST55C1E-CAA RST55C1E-CAB RST55C1E-IAA RST55C1E-IAB RST64C1E-CAV RST64C1E-CFA RST64C1E-IAV RSU4-0050-CAA RSU4-0050-IAA RSU5-0050-IAA RSU5-0050-IAV 208/230 115 208/230 115 230 115 230 208/230 115 208/230 115 115 115 208/230 Resistance Max PH RLA LRA Start or Run Line/Line 1 1 1 1 1 1 1 1 1 1 1 1 1 1 5.1 10.5 5.1 15 7 15 7 8.9 14.6 8.9 9.6 9.6 9.6 5.4 26.5 54.5 26.5 70 37 70 37 43 77 43 51 51 51 24.1 1.69 0.43 1.69 0.4 1.75 0.4 1.75 1.18 0.36 1.18 0.59 0.59 0.59 2.1 6.49 2.66 6.49 2.6 10.1 2.6 10.1 5.94 2.39 5.94 4.08 4.08 4.08 18.3 Start Cap P/N Run Cap P/N Relay P/N Part Type* 014-0058-25 014-0058-36 014-0059-09 014-0058-36 014-0036-18 014-0058-41 014-0059-18 014-0058-25 014-0058-43 014-0058-31 014-0058-27 014-0061-15 014-0061-15 014-0058-17 014-0064-09 040-0166-27 040-0172-03 040-0150-36 040-0166-21 040-0166-26 040-0172-03 040-0150-35 040-0166-30 040-0166-37 040-0172-05 040-0166-11 040-0168-03 040-0168-03 040-0168-02 RP RC RC RP RP RC RC RP RP RC RP RC RC RC 014-0064-13 014-0064-33 014-0064-10 014-0064-14 014-0064-02 Protector P/N 071-0561-28 071-0605-09 071-0561-16 071-0605-05 071-0647-02 071-0605-08 071-0561-55 071-0604-13 071-0604-14 071-0329-15 071-0329-15 071-0329-15 071-0329-11 * See Section F Introduction for more information. FB21 Section_Fb.indd 21 3/4/2008 7:57:22 AM Electrical Data - Copelametic - Air Cooled Model 3AB1-0300-TAE 3AB1-0310-TAC 3AB1-0310-TAD 3AB1-0311-TAC 3AB1-0311-TAD 3AB1-031A-TAC 3AB1-031A-TAD 3AB2-0310-CAB 3AB2-031A-CAB 3ABA-031E-TAC 3ABA-031E-TAD 3ABA-031L-TAC 3ABB-032E-CAB 3ABB-032L-CAB 3AH1-0200-TAC 3AH1-0200-TAD 3AH1-0200-TAE 3AH1-020A-TAC 3AH1-020A-TAD 3AH2-0200-CAB 3AH2-0200-CAH 3AH2-020A-CAB 3AH2-020A-CAH Volts PH 575 208/230 460 208/230 460 208/230 460 230 230 208/230 460 208/230 230 230 208/230 460 575 208/230 460 230 208 230 208 3 3 3 3 3 3 3 1 1 3 3 3 1 1 3 3 3 3 3 1 1 1 1 Max LRA RLA 4.4 8.2 5.5 10 5.1 10 5.1 14.7 14.7 10 5.1 10 14.7 14.7 6.6 3.7 2.3 6.6 3.7 9.3 12.4 9.3 12.4 30 82 41 82 41 82 41 86 86 82 41 82 86 86 46 23 20 46 23 58 57.2 58 57.2 Resistance Run or Start or Line to WYE Line to Line 2.7 0.47 1.9 0.42 1.653 0.42 1.653 0.61 0.61 0.42 1.653 0.42 0.595 0.595 0.84 3.1 4.905 0.84 3.1 1.125 0.74 1.125 0.74 5.4 0.9 3.6 0.837 3.309 0.837 3.309 2.54 2.54 0.837 3.309 0.837 2.41 2.41 1.675 6 9.3 1.675 6 2.7 2.836 2.7 2.836 Start Cap Run Cap P/N P/N Relay P/N Part Protector Type* P/N 014-0006-13 014-0064-12 040-0166-28 014-0006-13 014-0064-12 040-0166-28 RP RP 014-0006-13 014-0064-14 040-0166-28 014-0006-13 014-0064-14 040-0166-28 RP RP 014-0036-22 014-0036-22 014-0036-22 014-0036-22 RP RP RP RP 014-0064-11 014-0064-11 014-0064-11 014-0064-11 040-0166-20 040-0166-20 040-0166-20 040-0166-20 071-0090-16 071-0090-01 071-0090-03 071-0090-37 071-0090-03 071-0090-37 071-0090-03 071-0119-01 071-0119-01 071-0090-37 071-0090-03 071-0090-37 071-0119-02 071-0119-02 071-0090-00 071-0090-08 071-0090-15 071-0090-00 071-0090-08 071-0092-18 071-0089-00 071-0092-18 071-0089-00 * See Section F Introduction for more information. FC1 Section_Fc.indd 1 3/4/2008 7:59:55 AM Electrical Data - Copelametic - Air Cooled Model 3AJ1-0200-TAC 3AJ1-0200-TAD 3AJ1-0200-TAE 3AJ1-020A-TAC 3AJ1-020A-TAD 3AJ2-0200-CAB 3AJ2-0200-CAH 3AJ2-020A-CAB 3AJ2-0310-CAB 3AJA-0210-TAC 3AJA-021A-TAC 3AJA-021L-TAC 3AJB-0210-CAB 3AJB-021A-CAB 3WB1-0300-TAE 3WB1-0310-TAC 3WB1-0310-TAD 3WB1-0311-TAC 3WB1-031A-TAC 3WB2-0310-CAB 3WH1-0200-TAC 3WH1-0200-TAD 3WH1-0200-TAE Volts PH 208/230 460 575 208/230 460 230 208 230 230 208/230 208/230 208/230 230 230 575 208/230 460 208/230 208/230 230 208/230 460 575 3 3 3 3 3 1 1 1 1 3 3 3 1 1 3 3 3 3 3 1 3 3 3 Max LRA RLA 5.6 3 2.3 5.6 3 9.5 12.4 9.5 12.6 9.2 9.2 9.2 14.4 14.4 4.4 8.2 5.5 10 10 14.7 6.6 3.7 2.3 46 23 20 46 23 58 57.2 58 86 82 82 82 86 86 30 82 41 82 82 86 46 23 20 Resistance Run or Start or Line to WYE Line to Line 0.84 3.1 4.905 0.84 3.1 1.125 0.74 1.125 0.61 0.444 0.444 0.444 0.595 0.595 2.7 0.47 1.9 0.42 0.42 0.61 0.84 3.1 4.905 1.675 6 9.3 1.675 6 2.7 2.836 2.7 2.54 0.944 0.944 0.944 2.41 2.41 5.4 0.9 3.6 0.837 0.837 2.54 1.675 6 9.3 Start Cap Run Cap P/N P/N 014-0036-22 014-0064-11 014-0036-22 014-0064-11 014-0036-22 014-0064-11 014-0006-13 014-0064-12 Relay P/N Part Protector Type* P/N 040-0166-20 040-0166-20 040-0166-20 040-0166-28 RP RP RP RP 014-0006-13 014-0064-12 040-0166-28 014-0006-13 014-0064-12 040-0166-28 RP RP 014-0006-13 014-0064-12 040-0166-28 RP 071-0090-00 071-0090-08 071-0090-15 071-0090-00 071-0090-08 071-0092-18 071-0092-18 071-0092-18 071-0119-01 071-0090-44 071-0090-44 071-0090-44 071-0119-05 071-0119-05 071-0090-16 071-0090-01 071-0090-03 071-0090-37 071-0090-37 071-0119-01 071-0090-00 071-0090-08 071-0090-15 * See Section F Introduction for more information. FC2 Section_Fc.indd 2 3/4/2008 8:00:01 AM Electrical Data - Copelametic - Air Cooled Model 3WH1-020A-TAD 3WH2-0200-CAB 3WH2-0200-CAH 3WJ1-0200-TAC 3WJ1-0200-TAD 3WJ1-0200-TAE 3WJ2-0200-CAB 3WJ2-0200-CAH EAA1-0150-TAC EAA1-0150-TAE EAA1-015L-TAC EAA2-0150-CAB EAA2-0150-CAH EAA2-015A-CAH EAAA-015A-TAC EAAB-015A-CAB EAAB-015A-CAH EAB1-0150-TAC EAB1-0150-TAE EAB1-015A-TAC EAB2-0150-CAB EAB2-0150-CAH EAB2-015A-CAB Volts PH 460 230 208 208/230 460 575 230 208 208/230 575 208/230 230 208 208 208/230 230 208 208/230 575 208/230 230 208 230 3 1 1 3 3 3 1 1 3 3 3 1 1 1 3 1 1 3 3 3 1 1 1 Max LRA RLA 3.7 9.3 12.4 5.6 3 2.3 9.5 12.4 5.9 2.2 5.9 8.9 8.3 8.3 5.9 8.9 8.3 5.8 2.2 5.8 6.4 5.6 6.4 23 58 57.2 46 23 20 58 57.2 38 14.3 38 41 44 44 38 41 44 38 14.3 38 41 44 41 Resistance Run or Start or Line to WYE Line to Line 3.1 1.125 0.74 0.84 3.1 4.905 1.125 0.74 1.008 6.2 1.008 1.703 1.345 1.345 1.008 1.703 1.345 1.008 6.2 1.008 1.703 1.345 1.703 6 2.7 2.836 1.675 6 9.3 2.7 2.836 2.01 12.4 2.01 4.363 4.61 4.61 2.01 4.363 4.61 2.01 12.4 2.01 4.363 4.61 4.363 Start Cap Run Cap P/N P/N Relay P/N Part Protector Type* P/N 014-0036-22 014-0036-22 014-0064-11 040-0166-20 014-0064-11 040-0166-20 RP RP 014-0036-22 014-0036-22 014-0064-11 040-0166-20 014-0064-11 040-0166-20 RP RP 014-0036-21 014-0064-10 040-0166-20 014-0036-21 014-0064-10 040-0166-30 014-0036-21 014-0064-10 040-0166-30 RP RP RP 014-0036-21 014-0064-10 040-0166-20 014-0036-21 014-0064-10 040-0166-30 RP RP 014-0036-21 014-0064-10 040-0166-20 014-0036-21 014-0064-10 040-0166-30 014-0036-21 014-0064-10 040-0166-20 RP RP RP 071-0090-08 071-0092-18 071-0089-00 071-0090-00 071-0090-08 071-0090-15 071-0092-18 071-0092-18 071-0090-03 071-0090-21 071-0090-03 071-0092-18 071-0092-18 071-0092-18 071-0090-03 071-0092-16 071-0092-18 071-0090-03 071-0090-21 071-0090-03 071-0092-16 071-0092-16 071-0092-16 * See Section F Introduction for more information. FC3 Section_Fc.indd 3 3/4/2008 8:00:01 AM Electrical Data - Copelametic - Air Cooled Model EABA-0200-TAC EABA-0200-TAD EABA-0200-TAE EABA-020A-TAC EABB-0200-CAB EABB-020A-CAB EAC1-0150-TAC EAC1-0150-TAE EAC2-0150-CAB EAC2-0150-CAH EAC2-015A-CAB EACA-0200-TAC EACA-0200-TAD EACA-0200-TAE EACA-020A-TAC EACA-020A-TAD EACB-0200-CAB EACB-0200-CAH EAD1-0200-TAC EAD1-0200-TAD EAD1-0200-TAE EAD1-020L-TAC EAD1-0320-TAC Volts PH 208/230 460 575 208/230 230 230 208/230 575 230 208 230 208/230 460 575 208/230 460 230 208 208/230 460 575 208/230 208/230 3 3 3 3 1 1 3 3 1 1 1 3 3 3 3 3 1 1 3 3 3 3 3 Max LRA RLA 6.8 3.6 2.3 6.8 8.4 8.4 6 2.2 7.1 6.4 7.1 6.6 3.5 2.3 6.6 3.5 8.4 11.9 NA NA NA 6.8 12.4 46 23 20 46 58 58 38 14.3 41 44 41 46 23 20 46 23 58 57.2 46 23 20 46 85 Resistance Run or Start or Line to WYE Line to Line 0.84 3.346 4.905 0.84 1.125 1.125 1.008 6.2 1.703 1.345 1.703 0.84 3.346 4.905 0.84 3.346 1.125 0.74 0.84 3.346 4.905 0.84 0.419 1.675 6.692 9.3 1.675 2.7 2.7 2.01 12.4 4.363 4.61 4.363 1.675 6.692 9.3 1.675 6.692 2.7 2.836 1.675 6.692 9.3 1.675 0.838 Start Cap Run Cap P/N P/N 014-0036-22 014-0036-22 Relay P/N Part Protector Type* P/N 014-0064-11 040-0166-20 014-0064-11 040-0166-20 RP RP 014-0036-21 014-0064-10 040-0166-20 014-0036-21 014-0064-10 040-0166-30 014-0036-21 014-0064-10 040-0166-20 RP RP RP 014-0036-22 014-0036-22 RP RP 014-0064-11 040-0166-20 014-0064-11 040-0166-20 071-0090-00 071-0090-08 071-0090-15 071-0090-00 071-0092-18 071-0092-18 071-0090-03 071-0090-21 071-0092-16 071-0092-16 071-0092-16 071-0090-00 071-0090-08 071-0090-15 071-0090-00 071-0090-08 071-0092-18 071-0092-18 071-0090-00 071-0090-08 071-0090-15 071-0090-00 071-0090-38 * See Section F Introduction for more information. FC4 Section_Fc.indd 4 3/4/2008 8:00:01 AM Electrical Data - Copelametic - Air Cooled Model EAD1-0320-TAD EAD1-032A-TAC EAD1-032A-TAD EAD1-032L-TAC EAD1-032L-TAD EAD2-0200-CAB EAD2-0200-CAH EAD2-020A-CAH EAD2-020L-CAB EAD2-0320-CAB EADA-0200-TAC EADA-0200-TAD EADA-020A-TAC EADA-020A-TAD EADA-020E-TAC EADA-020L-TAC EADB-0200-CAB EADB-020A-CAB EADB-021E-CAB EADB-021L-CAB EAJ1-0150-TAC EAJ1-0150-TAE EAJ2-0150-CAB Volts PH 460 208/230 460 208/230 460 230 208 208 230 230 208/230 460 208/230 460 208/230 208/230 230 230 230 230 208/230 575 230 3 3 3 3 3 1 1 1 1 1 3 3 3 3 3 3 1 1 1 1 3 3 1 Max LRA RLA 5.2 12.4 5.2 12.4 5.2 NA NA 12.4 8.4 16 6.8 3.1 6.8 3.1 6.8 6.8 8.5 8.5 10 10 5.9 2.2 6.6 42 85 42 85 42 58 57.2 57.2 58 102 46 20.4 46 20.4 46 46 58 58 58 58 38 14.3 41 Resistance Run or Start or Line to WYE Line to Line 1.641 0.419 1.641 0.419 1.641 1.125 0.74 0.74 1.125 0.519 0.84 0 0.84 0 0.84 0.84 1.125 1.125 1.125 1.125 1.008 6.2 1.703 3.282 0.838 3.282 0.838 3.282 2.7 2.836 2.836 2.7 2.435 1.675 6.765 1.675 6.765 1.675 1.675 2.7 2.7 2.7 2.7 2.01 12.4 4.363 Start Cap Run Cap P/N P/N Relay P/N Part Protector Type* P/N 014-0036-22 014-0064-11 014-0036-22 014-0064-11 014-0036-22 014-0064-11 014-0036-22 014-0064-11 014-0006-13 014-0064-14 040-0166-20 040-0166-20 040-0166-20 040-0166-20 040-0166-28 RP RP RP RP RP 014-0036-22 014-0036-22 014-0036-22 014-0036-22 040-0166-20 040-0166-20 040-0166-20 040-0166-20 RP RP RP RP 014-0036-21 014-0064-10 040-0166-20 RP 014-0064-11 014-0064-11 014-0064-11 014-0064-11 071-0090-03 071-0090-38 071-0090-03 071-0090-38 071-0090-03 071-0092-18 071-0092-18 071-0092-18 071-0092-18 071-0119-06 071-0090-00 071-0090-15 071-0090-00 071-0090-15 071-0090-00 071-0090-00 071-0092-18 071-0092-18 071-0099-03 071-0099-03 071-0090-03 071-0090-21 071-0092-16 * See Section F Introduction for more information. FC5 Section_Fc.indd 5 3/4/2008 8:00:02 AM Electrical Data - Copelametic - Air Cooled Model EAJ2-0150-CAH EAJA-015A-TAC EAJB-015A-CAB EAJB-015A-CAH EAL1-0200-TAC EAL1-0200-TAD EAL1-0200-TAE EAL1-020A-TAD EAL2-0200-CAB EAL2-0200-CAH EALA-020A-TAC EALB-020A-CAB EALB-020A-CAH EAV1-0150-TAC EAV1-0150-TAE EAV1-015A-TAC EAV1-0200-TA7 EAV1-0200-TAC EAV1-0200-TAD EAV1-0200-TAE EAV1-0200-TAU EAV1-020L-TAC EAV1-020L-TAD Volts PH 208 208/230 230 208 208/230 460 575 460 230 208 208/230 230 208 208/230 575 208/230 380 208/230 460 575 200 208/230 460 1 3 1 1 3 3 3 3 1 1 3 1 1 3 3 3 3 3 3 3 3 3 3 Max LRA RLA 5.9 5.9 6.6 5.9 NA NA NA NA NA NA 7.1 8.7 12.9 5.6 2.2 5.6 NA NA NA NA NA 6.6 3.5 44 38 41 44 46 23 20 23 58 57.2 46 58 57.2 38 14.3 38 31.5 46 23 20 57.1 46 23 Resistance Run or Start or Line to WYE Line to Line 1.345 1.008 1.703 1.345 0.84 3.346 4.905 3.346 1.125 0.74 0.84 1.125 0.74 1.008 6.2 1.008 0 0.84 3.346 4.905 0 0.84 3.346 4.61 2.01 4.363 4.61 1.675 6.692 9.3 6.692 2.7 2.836 1.675 2.7 2.836 2.01 12.4 2.01 3.38 1.675 6.692 9.3 0.994 1.675 6.692 Start Cap Run Cap P/N P/N Relay P/N Part Protector Type* P/N 014-0036-21 014-0064-10 040-0166-30 RP 014-0036-21 014-0064-10 040-0166-20 014-0036-21 014-0064-10 040-0166-30 RP RP 014-0036-22 014-0036-22 014-0064-11 040-0166-20 014-0064-11 040-0166-20 RP RP 014-0036-22 014-0036-22 014-0064-11 040-0166-20 014-0064-11 040-0166-20 RP RP 071-0092-16 071-0090-03 071-0092-16 071-0092-16 071-0090-00 071-0090-08 071-0090-15 071-0090-08 071-0092-18 071-0092-18 071-0090-00 071-0092-18 071-0092-18 071-0090-03 071-0090-21 071-0090-03 071-0090-03 071-0090-00 071-0090-08 071-0090-15 071-0090-17 071-0090-00 071-0090-08 * See Section F Introduction for more information. FC6 Section_Fc.indd 6 3/4/2008 8:00:02 AM Electrical Data - Copelametic - Air Cooled Model EAV2-0150-CAB EAV2-0150-CAH EAV2-015A-CAB EAV2-0200-CAB EAV2-0200-CAH EAVA-0200-TAU EAVA-020E-TA7 EAVA-020E-TAU EAVA-020L-TA7 EAVA-020L-TAU EAVA-0210-TAC EAVA-0210-TAD EAVA-021A-TAC EAVA-021A-TAD EAVA-021E-TAC EAVA-021E-TAD EAVA-021E-TAE EAVA-021L-TAC EAVA-021L-TAD EAVB-015A-CAH EAVB-020A-CAB EAVB-020A-CAH EAVB-0210-CAV Volts PH 230 208 230 230 208 200 380 200 380 200 208/230 460 208/230 460 208/230 460 575 208/230 460 208 230 208 208/230 1 1 1 1 1 3 3 3 3 3 3 3 3 3 3 3 3 3 3 1 1 1 1 Max LRA RLA 6.4 5.5 6.4 NA NA 9.7 4.7 9.7 4.7 9.7 7.4 3.9 7.4 3.9 7.4 3.9 3.1 7.4 3.9 5.5 9.6 12.4 14.7 41 44 41 58 57.2 57.1 31.5 57.1 31.5 57.1 50 26.6 50 26.6 50 26.6 20 50 26.6 44 58 57.2 102 Resistance Run or Start or Line to WYE Line to Line 1.703 1.345 1.703 1.125 0.74 0 0 0 0 0 0 0 0 0 0 0 4.905 0 0 1.345 1.125 0.74 0.519 4.363 4.61 4.363 2.7 2.836 0.994 3.38 0.994 3.38 0.994 1.2 4.73 1.2 4.73 1.2 4.73 9.3 1.2 4.73 4.61 2.7 2.836 2.435 Start Cap Run Cap P/N P/N Relay P/N Part Protector Type* P/N 014-0036-21 014-0064-10 040-0166-20 014-0036-21 014-0064-10 040-0166-30 014-0036-21 014-0064-10 040-0166-20 014-0036-22 014-0064-11 040-0166-20 014-0036-22 014-0064-11 040-0166-20 RP RP RP RP RP 014-0036-21 014-0064-10 040-0166-30 014-0036-22 014-0064-11 040-0166-20 014-0036-22 014-0064-11 040-0166-20 014-0006-13 014-0064-14 040-0166-28 RP RP RP RP 071-0092-16 071-0092-16 071-0092-16 071-0099-01 071-0099-02 071-0090-17 071-0090-03 071-0090-17 071-0090-03 071-0090-17 071-0090-35 071-0090-13 071-0090-35 071-0090-13 071-0090-35 071-0090-13 071-0090-52 071-0090-35 071-0090-13 071-0092-16 071-0099-01 071-0099-02 071-0119-05 * See Section F Introduction for more information. FC7 Section_Fc.indd 7 3/4/2008 8:00:03 AM Electrical Data - Copelametic - Air Cooled Model EAVB-021A-CAV EAVB-021E-CAV EAVB-021L-CAV EWA1-0150-TAC EWA1-0150-TAE EWA2-0150-CAB EWA2-0150-CAH EWB1-0150-TAC EWB2-0150-CAB EWBA-0200-TAC EWBA-0200-TAD EWBA-0200-TAE EWBB-0200-CAB EWC1-0150-TAC EWCA-0200-TAC EWCA-0200-TAD EWCA-0200-TAE EWCA-020A-TAC EWCA-020A-TAD EWCB-0200-CAB EWCB-0200-CAH EWD1-0200-TAC EWD1-0200-TAD Volts PH 208/230 208/230 208/230 208/230 575 230 208 208/230 230 208/230 460 575 230 208/230 208/230 460 575 208/230 460 230 208 208/230 460 1 1 1 3 3 1 1 3 1 3 3 3 1 3 3 3 3 3 3 1 1 3 3 Max LRA RLA 14.7 14.7 14.7 5.9 2.2 8.9 8.3 5.8 6.4 6.8 3.6 2.3 8.4 6 6.6 3.5 2.3 6.6 3.5 8.4 11.9 NA 3.4 102 102 102 38 14.3 41 44 38 41 46 23 20 58 38 46 23 20 46 23 58 57.2 46 23 Resistance Run or Start or Line to WYE Line to Line 0.519 0.519 0.519 1.008 6.2 1.703 1.345 1.008 1.703 0.84 3.346 4.905 1.125 1.008 0.84 3.346 4.905 0.84 3.346 1.125 0.74 0.84 3.346 2.435 2.435 2.435 2.01 12.4 4.363 4.61 2.01 4.363 1.675 6.692 9.3 2.7 2.01 1.675 6.692 9.3 1.675 6.692 2.7 2.836 1.675 6.692 Start Cap Run Cap P/N P/N Relay P/N Part Protector Type* P/N 014-0006-13 014-0064-14 040-0166-28 014-0006-13 014-0064-14 040-0166-28 014-0006-13 014-0064-14 040-0166-28 RP RP RP 014-0036-21 014-0064-10 040-0166-20 014-0036-21 014-0064-10 040-0166-30 RP RP 014-0036-21 014-0064-10 040-0166-20 RP 014-0036-22 014-0064-11 040-0166-20 RP 014-0036-22 014-0036-22 014-0064-11 040-0166-20 014-0064-11 040-0166-20 RP RP 071-0119-05 071-0119-05 071-0119-05 071-0090-03 071-0090-21 071-0092-18 071-0092-18 071-0090-03 071-0092-16 071-0090-00 071-0090-08 071-0090-15 071-0092-18 071-0090-03 071-0090-00 071-0090-08 071-0090-15 071-0090-00 071-0090-08 071-0092-18 071-0092-18 071-0090-00 071-0090-08 * See Section F Introduction for more information. FC8 Section_Fc.indd 8 3/4/2008 8:00:03 AM Electrical Data - Copelametic - Air Cooled Model EWDA-020A-TAC EWJ1-0150-TAC EWJ1-0150-TAE EWJ2-0150-CAB EWJ2-0150-CAH EWL1-0200-TAC EWL1-0200-TAD EWL1-0200-TAE EWL1-020A-TAC EWL2-0200-CAB EWL2-0200-CAH EWV1-0150-TAC EWV1-0200-TAC EWV1-0200-TAD EWV1-0200-TAE EWV1-020A-TAC EWV1-020A-TAD EWV2-0150-CAB EWV2-0150-CAH EWV2-0200-CAB EWV2-0200-CAH EWVA-021E-TAC EWVA-021E-TAD Volts PH 208/230 208/230 575 230 208 208/230 460 575 208/230 230 208 208/230 208/230 460 575 208/230 460 230 208 230 208 208/230 460 3 3 3 1 1 3 3 3 3 1 1 3 3 3 3 3 3 1 1 1 1 3 3 Max LRA RLA 6.8 5.9 2.2 6.6 5.9 7.1 3.7 2.3 7.1 8.7 12.9 5.6 6.6 3.5 2.3 6.6 3.5 6.4 5.5 9.6 12.4 7.4 3.9 46 38 14.3 41 44 46 23 20 46 58 57.2 38 46 23 20 46 23 41 44 58 57.2 50 26.6 Resistance Run or Start or Line to WYE Line to Line 0.84 1.008 6.2 1.703 1.345 0.84 3.346 4.905 0.84 1.125 0.74 1.008 0.84 3.346 4.905 0.84 3.346 1.703 1.345 1.125 0.74 0 0 1.675 2.01 12.4 4.363 4.61 1.675 6.692 9.3 1.675 2.7 2.836 2.01 1.675 6.692 9.3 1.675 6.692 4.363 4.61 2.7 2.836 1.2 4.73 Start Cap Run Cap P/N P/N Relay P/N Part Protector Type* P/N 014-0036-21 014-0064-10 040-0166-20 014-0036-21 014-0064-10 040-0166-30 RP RP 014-0036-22 014-0036-22 014-0064-11 040-0166-20 014-0064-11 040-0166-20 RP RP 014-0036-21 014-0064-10 040-0166-20 014-0036-21 014-0064-10 040-0166-30 014-0036-22 014-0064-11 040-0166-20 014-0036-22 014-0064-11 040-0166-20 RP RP RP RP 071-0090-00 071-0090-03 071-0090-21 071-0092-16 071-0092-16 071-0090-00 071-0090-08 071-0090-15 071-0090-00 071-0092-18 071-0092-18 071-0090-03 071-0090-00 071-0090-08 071-0090-15 071-0090-00 071-0090-08 071-0092-16 071-0092-16 071-0099-01 071-0099-02 071-0090-35 071-0090-13 * See Section F Introduction for more information. FC9 Section_Fc.indd 9 3/4/2008 8:00:03 AM Electrical Data - Copelametic - Air Cooled Model EWVB-021E-CAV HAF2-0025-IAA HAF2-0025-IAB HAF2-0025-SAA HAF2-0033-IAA HAF2-0033-IAB HAFB-0033-IAA HAFB-0034-IAA HAFB-003E-IAA HAFB-003L-IAA HAG1-0050-TAC HAG1-005L-TAC HAG2-0050-CAA HAG2-0050-CAV HAG2-005L-CAV HAGA-005E-TAC HAGA-005L-TAC HAGB-005E-CAV HAGB-005L-CAV HAJ1-0050-TAC HAJ1-005L-TAC HAJ2-0025-IAA HAJ2-0025-IAB Volts PH 208/230 115 230 115 115 230 115 115 115 115 208/230 208/230 115 208/230 208/230 208/230 208/230 208/230 208/230 208/230 208/230 115 230 1 1 1 1 1 1 1 1 1 1 3 3 1 1 1 3 3 1 1 3 3 1 1 Max LRA RLA 14.7 3.9 2.3 3.9 5.4 2.5 5.4 5.9 5.4 5.4 2.4 2.4 8.6 4 4 2.4 2.4 4 4 2.2 2.2 4.1 2.1 102 23 12.2 22.5 31 12 31 43.5 31 31 13 13 44 22 22 13 13 22 22 13 13 23 12.2 Resistance Run or Start or Line to WYE Line to Line 0.519 1.76 6.76 1.82 1.23 5.07 1.23 0.875 1.23 1.23 3.62 3.62 0.755 3 3 3.62 3.62 3 3 3.62 3.62 1.76 6.76 2.435 4.48 17.87 17.24 3.1 12.505 3.1 2.39 3.1 3.1 7.24 7.24 2.36 9.455 9.455 7.24 7.24 9.455 9.455 7.24 7.24 4.48 17.87 Start Cap Run Cap P/N P/N Relay P/N Part Protector Type* P/N 014-0006-13 014-0064-14 040-0166-28 014-0061-06 040-0115-00 014-0061-13 040-0115-01 040-0115-00 014-0061-07 040-0166-08 014-0061-12 040-0166-19 014-0061-07 040-0166-08 014-0061-07 040-0166-08 014-0061-07 040-0166-08 014-0061-07 040-0166-08 RP RC RC RC RP RP RP RP RP RP 014-0061-02 014-0064-00 040-0166-33 014-0036-21 014-0064-00 040-0166-09 014-0036-21 014-0064-00 040-0166-09 RP RP RP 014-0036-21 014-0064-00 040-0166-09 014-0036-21 014-0064-00 040-0166-09 RP RP 014-0061-06 014-0061-13 RC RC 040-0115-00 040-0115-01 071-0119-05 071-0092-37 071-0092-32 071-0092-37 071-0092-04 071-0092-31 071-0092-04 071-0092-35 071-0092-04 071-0092-04 071-0090-42 071-0090-42 071-0099-03 071-0092-27 071-0092-27 071-0090-42 071-0090-42 071-0092-27 071-0092-27 071-0090-42 071-0090-42 071-0092-37 071-0092-32 * See Section F Introduction for more information. FC10 Section_Fc.indd 10 3/4/2008 8:00:04 AM Electrical Data - Copelametic - Air Cooled Model HAJ2-0025-SAA HAJ2-0033-IAA HAJ2-0033-IAB HAJ2-0050-CAA HAJ2-0050-CAV HAJ2-0050-IAA HAJ2-005L-CAV HAJA-005E-TAC HAJA-005L-TAC HAJB-003E-IAA HAJB-003L-IAA HAJB-005E-CAV HAJB-005L-CAV HAK2-0033-IAA HAK2-0033-IAB HAK2-0050-IAA HAK2-0050-IAB HAT2-0033-IAA HAT2-0033-IAB HAT2-0050-IAA HAT2-0050-IAB HATB-0051-CAA HATB-005E-CAA Volts PH 115 115 230 115 208/230 115 208/230 208/230 208/230 115 115 208/230 208/230 115 230 115 230 115 230 115 230 115 115 1 1 1 1 1 1 1 3 3 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Max LRA RLA 4.1 5.2 2.5 8.5 3.7 7.1 3.7 2.2 2.2 4.7 4.7 3.7 3.7 5 2.4 6.6 4 5.2 2.4 6.9 3.9 8.9 10.4 22.5 31 12 44 22 43.5 22 13 13 31 31 22 22 31 12 43.5 20.2 31 12 43.5 20.2 58 58 Resistance Run or Start or Line to WYE Line to Line 1.82 1.23 5.07 0.755 3 0.875 3 3.62 3.62 1.23 1.23 3 3 1.23 5.07 0.875 3.48 1.23 5.07 0.875 3.48 0.509 0.509 17.24 3.1 12.505 2.36 9.455 2.39 9.455 7.24 7.24 3.1 3.1 9.455 9.455 3.1 12.505 2.39 9.6 3.1 12.505 2.39 9.6 2.155 2.155 Start Cap Run Cap P/N P/N Relay P/N Part Protector Type* P/N 040-0115-00 014-0061-07 040-0166-08 014-0061-12 040-0166-19 014-0061-02 014-0064-00 040-0166-33 014-0036-21 014-0064-00 040-0166-09 014-0061-02 040-0166-08 014-0036-21 014-0064-00 040-0166-09 RC RP RP RP RP RP RP 014-0061-07 014-0061-07 014-0036-21 014-0036-21 014-0061-07 014-0061-12 014-0061-02 014-0061-09 014-0061-07 014-0061-12 014-0061-02 014-0061-09 014-0061-02 014-0061-02 RP RP RP RP RP RP RP RP RP RP RP RP RP RP 014-0064-00 014-0064-00 014-0064-04 014-0064-04 040-0166-08 040-0166-08 040-0166-09 040-0166-09 040-0166-08 040-0166-19 040-0166-08 040-0166-09 040-0166-08 040-0166-19 040-0166-08 040-0166-09 040-0166-11 040-0166-11 071-0092-37 071-0092-04 071-0092-31 071-0099-03 071-0092-27 071-0092-35 071-0092-27 071-0090-42 071-0090-42 071-0092-04 071-0092-04 071-0092-27 071-0092-27 071-0092-04 071-0092-31 071-0092-35 071-0092-05 071-0092-04 071-0092-31 071-0092-35 071-0092-05 071-0099-03 071-0099-03 * See Section F Introduction for more information. FC11 Section_Fc.indd 11 3/4/2008 8:00:04 AM Electrical Data - Copelametic - Air Cooled Model HATB-005E-CAV HATB-005L-CAA HWF2-0025-IAA HWF2-0025-IAB HWF2-0033-IAA HWF2-0033-IAB HWFB-003E-IAA HWG1-0050-TAC HWG2-0050-CAA HWG2-0050-CAV HWGA-005E-TAC HWGA-005L-TAC HWGB-005E-CAV HWGB-005L-CAV HWJ1-0050-TAC HWJ2-0025-IAA HWJ2-0025-IAB HWJ2-0033-IAA HWJ2-0033-IAB HWJ2-0050-CAA HWJ2-0050-CAV HWJA-005E-TAC HWJA-005L-TAC Volts PH 208/230 115 115 230 115 230 115 208/230 115 208/230 208/230 208/230 208/230 208/230 208/230 115 230 115 230 115 208/230 208/230 208/230 1 1 1 1 1 1 1 3 1 1 3 3 1 1 3 1 1 1 1 1 1 3 3 Max LRA RLA 3.3 10.4 3.9 2.3 5.4 2.5 5.4 2.4 8.6 4 2.4 2.4 4 4 2.2 4.1 2.1 5.2 2.5 8.5 3.7 2.2 2.2 22 58 23 12.2 31 12 31 13 44 22 13 13 22 22 13 23 12.2 31 12 44 22 13 13 Resistance Run or Start or Line to WYE Line to Line 3 0.509 1.76 6.76 1.23 5.07 1.23 3.62 0.755 3 3.62 3.62 3 3 3.62 1.76 6.76 1.23 5.07 0.755 3 3.62 3.62 9.455 2.155 4.48 17.87 3.1 12.505 3.1 7.24 2.36 9.455 7.24 7.24 9.455 9.455 7.24 4.48 17.87 3.1 12.505 2.36 9.455 7.24 7.24 Start Cap Run Cap P/N P/N Relay P/N Part Protector Type* P/N 014-0036-21 014-0064-00 040-0166-25 014-0061-02 014-0064-04 040-0166-11 014-0061-06 040-0115-00 014-0061-13 040-0115-01 014-0061-07 040-0166-08 014-0061-12 040-0166-19 014-0061-07 040-0166-08 RP RP RC RC RP RP RP 014-0061-02 014-0064-00 040-0166-33 014-0036-21 014-0064-00 040-0166-09 RP RP 014-0036-21 014-0064-00 040-0166-09 014-0036-21 014-0064-00 040-0166-09 RP RP 014-0061-06 040-0115-00 014-0061-13 040-0115-01 014-0061-07 040-0166-08 014-0061-12 040-0166-19 014-0061-02 014-0064-00 040-0166-33 014-0036-21 014-0064-00 040-0166-09 RC RC RP RP RP RP 071-0092-27 071-0099-03 071-0092-37 071-0092-32 071-0092-04 071-0092-31 071-0092-04 071-0090-42 071-0099-03 071-0092-27 071-0090-42 071-0090-42 071-0092-27 071-0092-27 071-0090-42 071-0092-37 071-0092-32 071-0092-04 071-0092-31 071-0099-03 071-0092-27 071-0090-42 071-0090-42 * See Section F Introduction for more information. FC12 Section_Fc.indd 12 3/4/2008 8:00:05 AM Electrical Data - Copelametic - Air Cooled Model HWJB-005E-CAV HWK2-0033-IAA HWK2-0033-IAB HWK2-0050-IAA HWK2-0050-IAB HWT2-0033-IAA HWT2-0033-IAB HWT2-0050-IAA HWT2-0050-IAB KAA1-0075-TAC KAA1-007A-TAC KAA2-0075-CAA KAA2-0075-CAV KAA2-0075-IAA KAA2-0075-IAB KAA2-0075-IAH KAA2-0076-CAA KAA2-007A-IAA KAA2-007A-IAB KAA2-007A-IAH KAAB-0075-IAA KAAB-007A-CAV KAAB-007A-IAA Volts PH 208/230 115 230 115 230 115 230 115 230 208/230 208/230 115 208/230 115 230 208 115 115 230 208 115 208/230 115 1 1 1 1 1 1 1 1 1 3 3 1 1 1 1 1 1 1 1 1 1 1 1 Max LRA RLA 3.7 5 2.4 6.6 4 5.2 2.4 6.9 3.9 2.6 2.6 NA 5.2 10.2 5.4 5.6 8.9 10.2 5.4 5.6 10.2 5.2 10.2 22 31 12 43.5 20.2 31 12 43.5 20.2 19.9 19.9 44 36 59.8 30.4 34.1 65 59.8 30.4 34.1 59.8 36 59.8 Resistance Run or Start or Line to WYE Line to Line 3 1.23 5.07 0.875 3.48 1.23 5.07 0.875 3.48 2.28 2.28 0.57 1.9 0.59 2.34 2 0.519 0.59 2.34 2 0.59 1.9 0.59 9.455 3.1 12.505 2.39 9.6 3.1 12.505 2.39 9.6 4.551 4.551 7 4.24 1.4 5.53 5.15 1.266 1.4 5.53 5.15 1.4 4.24 1.4 Start Cap Run Cap P/N P/N Relay P/N Part Protector Type* P/N 014-0036-21 014-0064-00 040-0166-09 014-0061-07 040-0166-08 014-0061-12 040-0166-19 014-0061-02 040-0166-08 014-0061-09 040-0166-09 014-0061-07 040-0166-08 014-0061-12 040-0166-19 014-0061-02 040-0166-08 014-0061-09 040-0166-09 RP RP RP RP RP RP RP RP RP 014-0061-14 014-0061-04 014-0061-11 014-0061-04 014-0061-04 014-0061-11 014-0061-11 014-0061-04 014-0061-04 014-0061-11 014-0061-04 014-0061-11 RP RP RP RP RP RP RP RP RP RP RP RP 014-0064-02 040-0166-11 014-0064-00 040-0166-09 040-0166-08 040-0166-09 040-0166-09 014-0064-06 040-0166-33 040-0166-08 040-0166-09 040-0166-09 040-0166-08 014-0064-00 040-0166-09 040-0166-08 071-0092-27 071-0092-04 071-0092-31 071-0092-35 071-0092-05 071-0092-04 071-0092-31 071-0092-35 071-0092-05 071-0090-05 071-0090-05 071-0092-20 071-0092-29 071-0099-00 071-0092-27 071-0092-27 071-0092-38 071-0099-00 071-0092-27 071-0092-27 071-0099-00 071-0092-29 071-0099-00 * See Section F Introduction for more information. FC13 Section_Fc.indd 13 3/4/2008 8:00:05 AM Electrical Data - Copelametic - Air Cooled Model KAAB-007E-CAA KAAB-007E-CAV KAAB-007L-CAA KAD1-0075-TAC KAD2-0075-CAA KAD2-0075-CAV KAE1-0050-TAC KAE1-0075-TAC KAE1-007L-TAC KAE2-0050-CAV KAE2-0050-IAA KAE2-0050-IAB KAE2-0050-IAH KAE2-005A-IAB KAE2-005A-IAH KAE2-0075-CAA KAE2-0075-CAV KAE2-007L-CAV KAEA-005A-TAC KAEA-0075-TAC KAEA-007A-TAC KAEA-007E-TAC KAEA-007L-TAC Volts PH 115 208/230 115 208/230 115 208/230 208/230 208/230 208/230 208/230 115 230 208 230 208 115 208/230 208/230 208/230 208/230 208/230 208/230 208/230 1 1 1 3 1 1 3 3 3 1 1 1 1 1 1 1 1 1 3 3 3 3 3 Max LRA RLA 10.2 5.8 10.2 2.4 9.9 5.1 1.9 3.4 3.4 3.4 7.8 4.1 4.1 4.1 4.1 10.9 5.4 5.4 1.9 3.4 3.4 3.4 3.4 59.8 36 59.8 19.9 65 36 13.2 19.9 19.9 24 45 22.5 25.5 22.5 25.5 65 36 36 13.2 19.9 19.9 19.9 19.9 Resistance Run or Start or Line to WYE Line to Line 0.59 1.9 0.59 2.28 0.519 1.9 3.34 2.28 2.28 2.9 0.835 3.305 2.92 3.305 2.92 0.519 1.9 1.9 3.34 2.28 2.28 2.28 2.28 1.4 4.24 1.4 4.551 1.266 4.24 6.69 4.551 4.551 5.785 2.42 9.585 7.9 9.585 7.9 1.266 4.24 4.24 6.69 4.551 4.551 4.551 4.551 Start Cap Run Cap P/N P/N Relay P/N Part Protector Type* P/N 014-0061-11 014-0064-11 040-0166-08 014-0061-04 014-0064-00 040-0166-09 014-0061-11 014-0064-11 040-0166-08 RP RP RP 014-0061-11 014-0064-06 040-0166-33 014-0061-04 014-0064-00 040-0166-09 RP RP 014-0036-21 014-0061-02 014-0061-09 014-0061-09 014-0061-09 014-0061-09 014-0061-11 014-0061-04 014-0061-04 RP RP RP RP RP RP RP RP RP 014-0064-00 040-0166-09 040-0166-08 040-0166-09 040-0166-09 040-0166-09 040-0166-09 014-0064-06 040-0166-33 014-0064-00 040-0166-09 014-0064-00 040-0166-09 071-0099-00 071-0092-29 071-0099-00 071-0090-05 071-0099-07 071-0092-29 071-0090-06 071-0090-41 071-0090-41 071-0092-37 071-0092-06 071-0092-05 071-0092-05 071-0092-05 071-0092-05 071-0099-06 071-0092-29 071-0092-29 071-0090-06 071-0090-41 071-0090-41 071-0090-41 071-0090-41 * See Section F Introduction for more information. FC14 Section_Fc.indd 14 3/4/2008 8:00:06 AM Electrical Data - Copelametic - Air Cooled Model KAEB-005A-CAV KAEB-005A-IAA KAEB-007A-CAA KAEB-007A-CAV KAEB-007E-CAA KAEB-007E-CAV KAEB-007L-CAA KAEB-007L-CAV KAG1-0050-TAC KAG1-005A-TAC KAG1-0075-TAC KAG1-0100-TAC KAG1-0100-TAD KAG2-0050-CAV KAG2-0050-IAA KAG2-0050-IAB KAG2-0050-IAH KAG2-005A-IAA KAG2-0075-CAA KAG2-0075-CAV KAG2-0075-IAA KAG2-0075-IAB KAG2-0075-IAH Volts PH 208/230 115 115 208/230 115 208/230 115 208/230 208/230 208/230 208/230 208/230 460 208/230 115 230 208 115 115 208/230 115 230 208 1 1 1 1 1 1 1 1 3 3 3 3 3 1 1 1 1 1 1 1 1 1 1 Max LRA RLA 3.4 7.8 10.9 5.4 10.9 5.4 10.9 5.4 1.9 1.9 2.6 4.1 1.6 3.6 7.8 4.1 4.1 7.8 NA 5.4 9.5 5.4 5.6 24 45 65 36 65 36 65 36 13.2 13.2 19.9 27 13.5 24 45 22.5 25.5 45 44 36 59.8 30.4 34.1 Resistance Run or Start or Line to WYE Line to Line 2.9 0.835 0.519 1.9 0.519 1.9 0.519 1.9 3.34 3.34 2.28 1.59 6.24 2.9 0.835 3.305 2.92 0.835 0.57 1.9 0.59 2.34 2 5.785 2.42 1.266 4.24 1.266 4.24 1.266 4.24 6.69 6.69 4.551 3.179 12.48 5.785 2.42 9.585 7.9 2.42 7 4.24 1.4 5.53 5.15 Start Cap Run Cap P/N P/N 014-0036-21 014-0061-02 014-0061-11 014-0061-04 014-0061-11 014-0061-04 014-0061-11 014-0061-04 Relay P/N Part Protector Type* P/N 014-0064-00 040-0166-09 040-0166-08 014-0064-06 040-0166-33 014-0064-00 040-0166-09 014-0064-06 040-0166-33 014-0064-00 040-0166-09 014-0064-06 040-0166-33 014-0064-00 040-0166-09 RP RP RP RP RP RP RP RP 014-0036-21 014-0064-00 040-0166-09 014-0061-02 040-0166-08 014-0061-09 040-0166-09 014-0061-09 040-0166-09 014-0061-02 040-0166-08 014-0061-14 014-0064-02 040-0166-11 014-0061-04 014-0064-00 040-0166-09 014-0061-11 040-0166-08 014-0061-04 040-0166-09 014-0061-04 040-0166-09 RP RP RP RP RP RP RP RP RP RP 071-0092-37 071-0092-06 071-0099-06 071-0092-29 071-0099-06 071-0092-29 071-0099-06 071-0092-29 071-0090-06 071-0090-06 071-0090-05 071-0090-16 071-0090-07 071-0092-37 071-0092-06 071-0092-05 071-0092-05 071-0092-06 071-0092-20 071-0092-29 071-0099-00 071-0092-27 071-0092-27 * See Section F Introduction for more information. FC15 Section_Fc.indd 15 3/4/2008 8:00:06 AM Electrical Data - Copelametic - Air Cooled Model KAG2-0075-XAA KAG2-0075-XAB KAG2-007A-IAH KAG2-0100-CAA KAG2-0100-CAV KAGA-007A-TAC KAGA-008E-TAC KAGA-010A-TAC KAGA-010E-TAC KAGA-010L-TAC KAGA-011E-TAD KAGA-011L-TAD KAGA-0150-TAC KAGA-0150-TAD KAGA-015A-TAC KAGA-015A-TAD KAGA-015L-TAC KAGA-015L-TAD KAGB-0050-IAA KAGB-005A-CAV KAGB-005A-IAA KAGB-005E-CAV KAGB-005E-IAA Volts PH 115 230 208 115 208/230 208/230 208/230 208/230 208/230 208/230 460 460 208/230 460 208/230 460 208/230 460 115 208/230 115 208/230 115 1 1 1 1 1 3 3 3 3 3 3 3 3 3 3 3 3 3 1 1 1 1 1 Max LRA RLA 9.3 5.4 5.6 11.9 6.4 2.6 3.6 4.3 4.3 4.3 2.1 2.1 5.5 2.5 5.5 2.5 5.5 2.5 7.8 4.1 7.8 4.1 7.8 43.9 23.2 34.1 85.5 40 19.9 23.1 27 27 27 15 15 35.5 18.2 35.5 18.2 35.5 18.2 45 24 45 24 45 Resistance Run or Start or Line to WYE Line to Line 0.615 2.41 2 0.405 1.37 2.28 2.28 1.59 1.59 1.59 6.62 6.62 1.325 4.72 1.325 4.72 1.325 4.72 0.835 2.9 0.835 2.9 0.835 3.26 13.45 5.15 2.248 4.525 4.551 4.551 3.179 3.179 3.179 13.24 13.24 2.375 9.44 2.375 9.44 2.375 9.44 2.42 5.785 2.42 5.785 2.42 Start Cap Run Cap P/N P/N Relay P/N Part Protector Type* P/N 014-0061-06 040-0166-33 014-0061-10 040-0166-35 014-0061-04 040-0166-09 014-0061-05 014-0064-08 040-0166-11 014-0061-04 014-0064-10 040-0166-10 RP RP RP RP RP 014-0061-02 040-0166-08 014-0036-21 014-0064-00 040-0166-09 014-0061-02 040-0166-08 014-0036-21 014-0064-00 040-0166-09 014-0061-02 040-0166-08 RP RP RP RP RP 071-0092-10 071-0092-15 071-0092-27 071-0092-40 071-0092-39 071-0090-05 071-0090-13 071-0090-50 071-0090-50 071-0090-50 071-0090-42 071-0090-42 071-0090-39 071-0090-27 071-0090-39 071-0090-27 071-0090-39 071-0090-27 071-0092-06 071-0092-37 071-0092-06 071-0092-37 071-0092-06 * See Section F Introduction for more information. FC16 Section_Fc.indd 16 3/4/2008 8:00:06 AM Electrical Data - Copelametic - Air Cooled Model KAGB-005L-IAA KAGB-007A-CAV KAGB-007A-IAA KAGB-010E-CAV KAGB-010L-CAV KAGB-0150-CAV KAGB-015A-CAV KAGB-015L-CAV KAJ1-0075-TAC KAJ1-0100-TAC KAJ1-0100-TAD KAJ1-010L-TAC KAJ1-010L-TAD KAJ3-0075-CAV KAJ3-0075-IAA KAJ3-0075-IAB KAJ3-0075-IAH KAJ3-0075-XAA KAJ3-0075-XAB KAJ3-007A-IAB KAJ3-0100-CAA KAJ3-0100-CAB KAJ3-0100-CAH Volts PH 115 208/230 115 208/230 208/230 208/230 208/230 208/230 208/230 208/230 460 208/230 460 208/230 115 230 208 115 230 230 115 230 208 1 1 1 1 1 1 1 1 3 3 3 3 3 1 1 1 1 1 1 1 1 1 1 Max LRA RLA 7.8 5.4 9.5 7.5 7.5 9.6 9.6 9.6 2.7 NA NA 3.4 2.1 5.1 9.1 5.4 5.9 8.9 5.2 5.4 NA NA NA 45 36 59.8 40 40 55 55 55 19.9 25 15 25 15 36 59.8 30.4 34.1 43.9 23.2 30.4 85.5 33.5 36.4 Resistance Run or Start or Line to WYE Line to Line 0.835 1.9 0.59 1.37 1.37 0.94 0.94 0.94 2.28 2.145 6.62 2.145 6.62 1.9 0.59 2.34 2 0.615 2.41 2.34 0.405 2.27 1.885 2.42 4.24 1.4 4.525 4.525 3.45 3.45 3.45 4.551 4.29 13.24 4.29 13.24 4.24 1.4 5.53 5.15 3.26 13.45 5.53 2.248 4.935 4.59 Start Cap Run Cap P/N P/N Relay P/N Part Protector Type* P/N 014-0061-02 014-0061-04 014-0061-11 014-0061-04 014-0061-04 014-0036-22 014-0036-22 014-0036-22 040-0166-08 014-0064-00 040-0166-09 040-0166-08 014-0064-14 040-0166-10 014-0064-14 040-0166-10 014-0064-19 040-0166-20 014-0064-19 040-0166-20 014-0064-19 040-0166-20 RP RP RP RP RP RP RP RP 014-0061-04 014-0061-11 014-0061-04 014-0061-04 014-0061-06 014-0061-10 014-0061-04 014-0061-05 014-0061-04 014-0061-04 014-0064-00 040-0166-09 040-0166-08 040-0166-09 040-0166-09 040-0166-33 040-0166-35 040-0166-09 014-0064-08 040-0166-11 014-0064-00 040-0166-10 014-0064-00 040-0166-25 RP RP RP RP RP RP RP RP RP RP 071-0092-06 071-0092-29 071-0099-00 071-0092-42 071-0092-42 071-0099-04 071-0099-04 071-0099-04 071-0090-05 071-0090-04 071-0090-07 071-0090-04 071-0090-07 071-0092-29 071-0099-00 071-0092-27 071-0092-27 071-0092-10 071-0092-15 071-0092-27 071-0092-23 071-0092-25 071-0092-14 * See Section F Introduction for more information. FC17 Section_Fc.indd 17 3/4/2008 8:00:07 AM Electrical Data - Copelametic - Air Cooled Model KAJ3-0100-CAV KAJ3-010L-CAV KAJ8-0075-TAC KAJA-007A-TAC KAJA-0100-TAC KAJA-0101-TAC KAJA-010A-TAC KAJA-010L-TAC KAJA-011A-TAC KAJA-011A-TAD KAJA-011E-TAC KAJA-011E-TAD KAJA-011L-TAC KAJA-011L-TAD KAJB-007A-CAV KAJB-007A-IAA KAJB-007E-IAA KAJB-007L-IAA KAJB-0100-CAA KAJB-0100-CAV KAJB-010A-CAA KAJB-010A-CAV KAJB-010E-CAV Volts PH 208/230 208/230 208/230 208/230 208/230 208/230 208/230 208/230 208/230 460 208/230 460 208/230 460 208/230 115 115 115 115 208/230 115 208/230 208/230 1 1 3 3 3 3 3 3 3 3 3 3 3 3 1 1 1 1 1 1 1 1 1 Max LRA RLA NA 6.9 2.7 2.7 NA 4.5 NA 3.4 4.6 2.1 4.6 2.1 4.6 2.1 5.1 10.4 10.4 10.4 NA NA NA 6.9 6.9 40 40 19.9 19.9 25 27 25 25 27 15 27 15 27 15 36 59.8 59.8 59.8 85.5 40 85.5 40 40 Resistance Run or Start or Line to WYE Line to Line 1.37 1.37 2.28 2.28 2.145 1.59 2.145 2.145 1.59 6.62 1.59 6.62 1.59 6.62 1.9 0.59 0.59 0.59 0.405 1.37 0.405 1.37 1.37 4.525 4.525 4.551 4.551 4.29 3.179 4.29 4.29 3.179 13.24 3.179 13.24 3.179 13.24 4.24 1.4 1.4 1.4 2.248 4.525 2.248 4.525 4.525 Start Cap Run Cap P/N P/N Relay P/N Part Protector Type* P/N 014-0061-04 014-0064-10 040-0166-10 014-0061-04 014-0064-10 040-0166-10 RP RP 014-0061-04 014-0061-11 014-0061-11 014-0061-11 014-0061-05 014-0061-04 014-0061-05 014-0061-04 014-0061-04 RP RP RP RP RP RP RP RP RP 014-0064-00 040-0166-09 040-0166-08 040-0166-08 040-0166-08 014-0064-08 040-0166-11 014-0064-10 040-0166-10 014-0064-08 040-0166-11 014-0064-10 040-0166-10 014-0064-10 040-0166-10 071-0092-39 071-0092-39 071-0090-05 071-0090-05 071-0090-04 071-0090-16 071-0090-04 071-0090-04 071-0090-50 071-0090-42 071-0090-50 071-0090-42 071-0090-50 071-0090-42 071-0092-29 071-0099-00 071-0099-00 071-0099-00 071-0092-23 071-0092-39 071-0092-23 071-0092-39 071-0092-39 * See Section F Introduction for more information. FC18 Section_Fc.indd 18 3/4/2008 8:00:07 AM Electrical Data - Copelametic - Air Cooled Model KAJB-010L-CAV KAJC-0100-TAC KAJC-0101-TAC KAJC-011L-TAC KAK1-0100-TAC KAK1-0100-TAD KAK2-0100-CAA KAK2-0100-CAB KAK2-0100-CAH KAK2-0100-CAV KAK2-010A-CAA KAK4-0075-CAV KAK4-0075-IAA KAK4-0075-IAB KAK8-0100-TAC KAKA-0100-TAC KAKA-010A-TAC KAKA-010A-TAD KAKA-010L-TAC KAKA-011E-TAD KAKA-012E-TAC KAKA-0150-TAU KAKA-0200-TAC Volts PH 208/230 208/230 208/230 208/230 208/230 460 115 230 208 208/230 115 208/230 115 230 208/230 208/230 208/230 460 208/230 460 208/230 200 208/230 1 3 3 3 3 3 1 1 1 1 1 1 1 1 3 3 3 3 3 3 3 3 3 Max LRA RLA 6.9 NA 4.5 4.6 NA NA NA NA NA NA 11.4 NA NA NA 3.3 NA 3.3 NA 3.3 2.4 4.6 6.6 6.8 40 25 27 27 25 15 85.5 33.5 36.4 40 85.5 36 59.8 30.4 25 25 25 15 25 15 27 48.2 50 Resistance Run or Start or Line to WYE Line to Line 1.37 2.145 1.59 1.59 2.145 6.62 0.405 2.27 1.885 1.37 0.405 1.9 0.59 2.34 2.145 2.145 2.145 6.62 2.145 6.62 1.59 0 0.795 4.525 4.29 3.179 3.179 4.29 13.24 2.248 4.935 4.59 4.525 2.248 4.24 1.4 5.53 4.29 4.29 4.29 13.24 4.29 13.24 3.179 1.463 1.589 Start Cap Run Cap P/N P/N Relay P/N Part Protector Type* P/N 014-0061-04 014-0064-10 040-0166-10 RP 014-0061-05 014-0061-04 014-0061-04 014-0061-04 014-0061-05 014-0061-04 014-0061-11 014-0061-04 RP RP RP RP RP RP RP RP 014-0064-08 014-0064-00 014-0064-00 014-0064-10 014-0064-08 014-0064-00 040-0166-11 040-0166-10 040-0166-25 040-0166-10 040-0166-11 040-0166-09 040-0166-08 040-0166-09 071-0092-39 071-0090-04 071-0090-16 071-0090-50 071-0090-04 071-0090-07 071-0092-23 071-0092-25 071-0092-14 071-0092-39 071-0092-23 071-0092-29 071-0099-00 071-0092-27 071-0090-04 071-0090-04 071-0090-04 071-0090-07 071-0090-04 071-0090-42 071-0090-03 071-0090-28 071-0090-35 * See Section F Introduction for more information. FC19 Section_Fc.indd 19 3/4/2008 8:00:08 AM Electrical Data - Copelametic - Air Cooled Model KAKA-0200-TAD KAKA-020A-TAC KAKA-020A-TAD KAKA-020E-TAC KAKA-020L-TAC KAKA-020L-TAD KAKA-022E-TAD KAKB-011A-CAV KAKB-011E-CAV KAKB-011L-CAV KAKB-012E-CAA KAKB-0150-CAB KAKB-0151-CAB KAKB-015A-CAB KAKB-0200-CAV KAKB-020L-CAV KAKB-021A-CAV KAKB-021E-CAV KAKB-021L-CAV KAKC-0150-TAU KAKC-0200-TAC KAKC-020L-TAC KAKD-011E-CAV Volts PH 460 208/230 460 208/230 208/230 460 460 208/230 208/230 208/230 115 230 230 230 208/230 208/230 208/230 208/230 208/230 200 208/230 208/230 208/230 3 3 3 3 3 3 3 1 1 1 1 1 1 1 1 1 1 1 1 3 3 3 1 Max LRA RLA 3 6.8 3 6.8 6.5 3 3 7.9 7.9 7.9 11.4 7.5 8.5 7.5 9.1 9.1 9.1 10.6 10.1 6.6 6.8 6.5 7.9 25 50 25 50 50 25 25 40 40 40 85.5 44 44 44 55 55 55 55 55 48.2 50 50 40 Resistance Run or Start or Line to WYE Line to Line 3.165 0.795 3.165 0.795 0.795 3.165 3.165 1.37 1.37 1.37 0.405 1.65 1.28 1.65 0.94 0.94 0.94 0.94 0.94 0 0.795 0.795 1.37 6.329 1.589 6.329 1.589 1.589 6.329 6.329 4.525 4.525 4.525 2.248 4.19 4.105 4.19 3.45 3.45 3.45 3.45 3.45 1.463 1.589 1.589 4.525 Start Cap Run Cap P/N P/N 014-0061-04 014-0061-04 014-0061-04 014-0061-05 014-0036-21 014-0036-21 014-0036-21 014-0036-22 014-0036-22 014-0036-22 014-0036-22 014-0036-22 014-0064-14 014-0064-14 014-0064-14 014-0064-08 014-0064-11 014-0064-19 014-0064-11 014-0064-19 014-0064-19 014-0064-19 014-0064-14 014-0064-14 Relay P/N Part Protector Type* P/N 040-0166-10 040-0166-10 040-0166-10 040-0166-11 040-0166-20 040-0166-20 040-0166-20 040-0166-20 040-0166-20 040-0166-20 040-0166-20 040-0166-20 RP RP RP RP RP RP RP RP RP RP RP RP 014-0061-04 014-0064-14 040-0166-10 RP 071-0090-16 071-0090-35 071-0090-16 071-0090-35 071-0090-35 071-0090-16 071-0090-16 071-0092-42 071-0092-42 071-0092-42 071-0092-23 071-0092-29 071-0099-03 071-0092-29 071-0099-04 071-0099-04 071-0099-04 071-0099-04 071-0099-04 071-0090-28 071-0090-35 071-0090-35 071-0092-42 * See Section F Introduction for more information. FC20 Section_Fc.indd 20 3/4/2008 8:00:08 AM Electrical Data - Copelametic - Air Cooled Model KAL1-0100-TAC KAL1-0100-TAD KAL2-0100-CAA KAL2-0100-CAB KAL2-0100-CAH KAL2-0100-CAV KALA-0100-TAC KALA-0100-TAD KALA-010A-TAC KALA-010A-TAD KALA-0150-TAC KALA-0150-TAD KALA-0150-TAU KALA-015A-TAC KALA-015A-TAD KALA-015L-TAC KALA-015L-TAD KALA-016E-TAC KALA-016E-TAD KALA-016L-TAC KALA-016L-TAD KALB-0100-CAA KALB-0100-CAB Volts PH 208/230 460 115 230 208 208/230 208/230 460 208/230 460 208/230 460 200 208/230 460 208/230 460 208/230 460 208/230 460 115 230 3 3 1 1 1 1 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 1 1 Max LRA RLA NA NA NA NA NA NA 3.3 1.8 3.3 1.8 NA NA NA 5.4 2.9 5.4 2.9 6.6 3.4 6.6 3.4 10.9 5.5 25 15 85.5 33.5 36.4 40 25 15 25 15 35.5 18.2 48.2 35.5 18.2 35.5 18.2 50 25 50 25 85.5 33.5 Resistance Run or Start or Line to WYE Line to Line 2.145 6.62 0.405 2.27 1.885 1.37 2.145 6.62 2.145 6.62 1.325 4.72 0 1.325 4.72 1.325 4.72 0.795 3.165 0.795 3.165 0.405 2.27 4.29 13.24 2.248 4.935 4.59 4.525 4.29 13.24 4.29 13.24 2.375 9.44 1.463 2.375 9.44 2.375 9.44 1.589 6.329 1.589 6.329 2.248 4.935 Start Cap Run Cap P/N P/N 014-0061-05 014-0061-04 014-0061-04 014-0061-04 014-0064-08 014-0064-00 014-0064-00 014-0064-10 Relay P/N Part Protector Type* P/N 040-0166-11 040-0166-10 040-0166-25 040-0166-10 RP RP RP RP 014-0061-05 014-0064-08 040-0166-11 014-0061-04 014-0064-00 040-0166-10 RP RP 071-0090-04 071-0090-07 071-0092-23 071-0092-25 071-0092-14 071-0092-39 071-0090-04 071-0090-07 071-0090-04 071-0090-07 071-0090-03 071-0090-27 071-0090-28 071-0090-03 071-0090-27 071-0090-03 071-0090-27 071-0090-35 071-0090-16 071-0090-35 071-0090-16 071-0092-23 071-0092-25 * See Section F Introduction for more information. FC21 Section_Fc.indd 21 3/4/2008 8:00:08 AM Electrical Data - Copelametic - Air Cooled Model KALB-0100-CAH KALB-0100-CAV KALB-010A-CAA KALB-010A-CAB KALB-010A-CAV KALB-010E-CAV KALB-010L-CAV KALB-0150-CAB KALB-0150-CAH KALB-0150-CAV KALB-0151-CAB KALB-015A-CAB KALB-015A-CAH KALB-015A-CAV KALB-015E-CAV KALB-015L-CAV KALC-0150-TAU KALC-016L-TAC KAM1-0050-TAC KAM1-0075-TAC KAM1-0100-TAC KAM1-0100-TAD KAM1-010A-TAD Volts PH 208 208/230 115 230 208/230 208/230 208/230 230 208 208/230 230 230 208 208/230 208/230 208/230 200 208/230 208/230 208/230 208/230 460 460 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 3 3 3 3 3 3 3 Max LRA RLA 6.8 6.9 10.9 5.5 6.9 6.9 6.9 NA NA NA 8.9 5.6 8.1 9.9 9.9 9.9 NA 6.6 1.7 NA 4.5 2.2 2.2 36.4 40 85.5 33.5 40 40 40 44 45 55 44 44 45 55 55 55 48.2 50 13.2 19.9 27 13.5 13.5 Resistance Run or Start or Line to WYE Line to Line 1.885 1.37 0.405 2.27 1.37 1.37 1.37 1.65 1.32 0.94 1.28 1.65 1.32 0.94 0.94 0.94 0 0.795 3.34 2.28 1.59 6.24 6.24 4.59 4.525 2.248 4.935 4.525 4.525 4.525 4.19 4.19 3.45 4.105 4.19 4.19 3.45 3.45 3.45 1.463 1.589 6.69 4.551 3.179 12.48 12.48 Start Cap Run Cap P/N P/N 014-0061-04 014-0061-04 014-0061-05 014-0061-04 014-0061-04 014-0061-04 014-0061-04 014-0036-21 014-0036-21 014-0036-22 014-0036-21 014-0036-21 014-0036-21 014-0036-22 014-0036-22 014-0036-22 014-0064-00 014-0064-10 014-0064-08 014-0064-00 014-0064-10 014-0064-10 014-0064-10 014-0064-10 014-0064-10 014-0064-19 014-0064-19 014-0064-10 014-0064-10 014-0064-19 014-0064-19 014-0064-19 Relay P/N 040-0166-25 040-0166-10 040-0166-11 040-0166-10 040-0166-10 040-0166-10 040-0166-10 040-0166-20 040-0166-30 040-0166-20 040-0166-20 040-0166-20 040-0166-30 040-0166-20 040-0166-20 040-0166-20 Part Protector Type* P/N RP RP RP RP RP RP RP RP RP RP RP RP RP RP RP RP 071-0092-14 071-0092-39 071-0092-23 071-0092-25 071-0092-39 071-0092-39 071-0092-39 071-0092-16 071-0092-18 071-0099-04 071-0099-03 071-0092-16 071-0092-18 071-0099-04 071-0099-04 071-0099-04 071-0090-28 071-0090-35 071-0090-06 071-0090-05 071-0090-40 071-0090-43 071-0090-43 * See Section F Introduction for more information. FC22 Section_Fc.indd 22 3/4/2008 8:00:09 AM Electrical Data - Copelametic - Air Cooled Model KAM1-010L-TAC KAM1-010L-TAD KAM2-0050-CAV KAM2-0050-IAA KAM2-0050-IAB KAM2-0050-IAH KAM2-0075-CAV KAM2-0075-IAA KAM2-0075-IAB KAM2-0075-IAH KAM2-0075-XAA KAM2-0075-XAB KAM2-0100-CAA KAM2-0100-CAV KAM2-010A-CAA KAM2-010L-CAV KAMA-0050-TAC KAMA-005A-TAC KAMA-0075-TAC KAMA-007A-TAC KAMA-007E-TAC KAMA-007L-TAC KAMA-0100-TAC Volts PH 208/230 460 208/230 115 230 208 208/230 115 230 208 115 230 115 208/230 115 208/230 208/230 208/230 208/230 208/230 208/230 208/230 208/230 3 3 1 1 1 1 1 1 1 1 1 1 1 1 1 1 3 3 3 3 3 3 3 Max LRA RLA 4.5 2.2 3.7 7.2 3.8 3.8 5.6 NA NA 6.1 8.9 6 15.5 7.5 15.5 7.5 1.7 1.7 NA 3.2 3.2 3.2 4.5 27 13.5 24 45 22.5 25.5 36 59.8 30.4 34.1 43.9 23.2 93 40 93 40 13.2 13.2 19.9 19.9 19.9 19.9 27 Resistance Run or Start or Line to WYE Line to Line 1.59 6.24 2.9 0.835 3.305 2.92 1.9 0.59 2.34 2 0.615 2.41 0.376 1.37 0.376 1.37 3.34 3.34 2.28 2.28 2.28 2.28 1.59 3.179 12.48 5.785 2.42 9.585 7.9 4.24 1.4 5.53 5.15 3.26 13.45 1.837 4.525 1.837 4.525 6.69 6.69 4.551 4.551 4.551 4.551 3.179 Start Cap Run Cap P/N P/N 014-0036-21 014-0061-02 014-0061-09 014-0061-09 014-0061-04 014-0061-11 014-0061-04 014-0061-04 014-0061-06 014-0061-10 014-0061-05 014-0061-04 014-0061-05 014-0061-04 Relay P/N 014-0064-00 040-0166-09 040-0166-08 040-0166-09 040-0166-09 014-0064-00 040-0166-09 040-0166-08 040-0166-09 040-0166-09 040-0166-33 040-0166-35 014-0064-08 040-0166-11 014-0064-10 040-0166-10 014-0064-08 040-0166-11 014-0064-10 040-0166-10 Part Protector Type* P/N RP RP RP RP RP RP RP RP RP RP RP RP RP RP 071-0090-40 071-0090-43 071-0092-37 071-0092-06 071-0092-05 071-0092-05 071-0092-29 071-0099-00 071-0092-27 071-0092-27 071-0092-10 071-0092-15 071-0099-05 071-0092-39 071-0099-05 071-0092-39 071-0090-06 071-0090-06 071-0090-41 071-0090-41 071-0090-41 071-0090-41 071-0090-40 * See Section F Introduction for more information. FC23 Section_Fc.indd 23 3/4/2008 8:00:09 AM Electrical Data - Copelametic - Air Cooled Model KAMA-010A-TAC KAMB-0050-CAV KAMB-0050-IAA KAMB-0050-IAB KAMB-0050-IAH KAMB-005A-CAV KAMB-005A-IAA KAMB-005A-IAB KAMB-005A-IAH KAMB-0075-CAA KAMB-0075-CAV KAMB-0075-IAB KAMB-0075-IAH KAMB-007A-CAA KAMB-007A-CAV KAMB-007E-CAA KAMB-007E-CAV KAMB-007E-IAA KAMB-007L-CAA KAMB-007L-CAV KAMB-010A-CAV KAMC-0075-TAC KAMD-007E-CAA Volts PH 208/230 208/230 115 230 208 208/230 115 230 208 115 208/230 230 208 115 208/230 115 208/230 115 115 208/230 208/230 208/230 115 3 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 3 1 Max LRA RLA 4.5 3.7 7.2 3.8 3.8 3.7 7.2 3.8 3.8 NA NA NA NA NA 5.6 10.9 5.6 10.1 10.9 5.6 7.5 NA 10.9 27 24 45 22.5 25.5 24 45 22.5 25.5 85.5 36 30.4 34.1 85.5 36 85.5 36 59.8 85.5 36 40 19.9 85.5 Resistance Run or Start or Line to WYE Line to Line 1.59 2.9 0.835 3.305 2.92 2.9 0.835 3.305 2.92 0.405 1.9 2.34 2 0.405 1.9 0.405 1.9 0.59 0.405 1.9 1.37 2.28 0.405 3.179 5.785 2.42 9.585 7.9 5.785 2.42 9.585 7.9 2.248 4.24 5.53 5.15 2.248 4.24 2.248 4.24 1.4 2.248 4.24 4.525 4.551 2.248 Start Cap Run Cap P/N P/N 014-0036-21 014-0061-02 014-0061-09 014-0061-09 014-0036-21 014-0061-02 014-0061-09 014-0061-09 014-0061-05 014-0061-04 014-0061-04 014-0061-04 014-0061-05 014-0061-04 014-0061-05 014-0061-04 014-0061-11 014-0061-05 014-0061-04 014-0061-04 Relay P/N Part Protector Type* P/N 014-0064-00 040-0166-09 040-0166-08 040-0166-09 040-0166-09 014-0064-00 040-0166-09 040-0166-08 040-0166-09 040-0166-09 014-0064-08 040-0166-11 014-0064-00 040-0166-09 040-0166-09 040-0166-09 014-0064-08 040-0166-21 014-0064-00 040-0166-09 014-0064-08 040-0166-21 014-0064-00 040-0166-09 040-0166-08 014-0064-08 040-0166-21 014-0064-00 040-0166-09 014-0064-10 040-0166-10 RP RP RP RP RP RP RP RP RP RP RP RP RP RP RP RP RP RP RP RP 014-0061-05 014-0064-08 040-0166-21 RP 071-0090-40 071-0092-37 071-0092-06 071-0092-05 071-0092-05 071-0092-37 071-0092-06 071-0092-05 071-0092-05 071-0092-40 071-0092-29 071-0092-27 071-0092-27 071-0092-40 071-0092-29 071-0092-40 071-0092-29 071-0099-00 071-0092-40 071-0092-29 071-0092-39 071-0090-41 071-0092-40 * See Section F Introduction for more information. FC24 Section_Fc.indd 24 3/4/2008 8:00:10 AM Electrical Data - Copelametic - Air Cooled Model KAMD-007E-CAV KAN1-0050-TAC KAN1-0075-TAC KAN1-007L-TAC KAN2-0050-CAV KAN2-0050-IAA KAN2-0050-IAB KAN2-0050-IAH KAN2-0075-CAA KAN2-0075-CAV KAN2-007A-CAA KAN2-007L-CAV KANA-006E-TAC KANA-006L-TAC KANA-0075-TAC KANA-007E-TAC KANB-0050-CAV KANB-0050-IAA KANB-005A-CAV KANB-005A-IAA KANB-005E-CAV KANB-005E-IAA KANB-005L-CAV Volts PH 208/230 208/230 208/230 208/230 208/230 115 230 208 115 208/230 115 208/230 208/230 208/230 208/230 208/230 208/230 115 208/230 115 208/230 115 208/230 1 3 3 3 1 1 1 1 1 1 1 1 3 3 3 3 1 1 1 1 1 1 1 Max LRA RLA 5.6 2.1 3.5 3.5 3.6 8.1 4.2 4.2 11.7 6.1 11.7 6.1 2.2 2.2 3.5 3.5 3.6 NA 3.6 8 3.6 8 3.6 36 13.2 19.9 19.9 24 45 22.5 25.5 65 36 65 36 13.2 13.2 19.9 19.9 24 45 24 45 24 45 24 Resistance Run or Start or Line to WYE Line to Line 1.9 3.34 2.28 2.28 2.9 0.835 3.305 2.92 0.519 1.9 0.519 1.9 3.34 3.34 2.28 2.28 2.9 0.835 2.9 0.835 2.9 0.835 2.9 4.24 6.69 4.551 4.551 5.785 2.42 9.585 7.9 1.266 4.24 1.266 4.24 6.69 6.69 4.551 4.551 5.785 2.42 5.785 2.42 5.785 2.42 5.785 Start Cap Run Cap P/N P/N Relay P/N Part Protector Type* P/N 014-0061-04 014-0064-00 040-0166-09 RP 014-0036-21 014-0061-02 014-0061-09 014-0061-09 014-0061-11 014-0061-04 014-0061-11 014-0061-04 014-0064-00 040-0166-09 040-0166-08 040-0166-09 040-0166-09 014-0064-06 040-0166-33 014-0064-00 040-0166-09 014-0064-06 040-0166-33 014-0064-00 040-0166-09 RP RP RP RP RP RP RP RP 014-0036-21 014-0061-02 014-0036-21 014-0061-02 014-0036-21 014-0061-02 014-0036-21 014-0064-00 040-0166-09 040-0166-08 014-0064-00 040-0166-09 040-0166-08 014-0064-00 040-0166-09 040-0166-08 014-0064-00 040-0166-09 RP RP RP RP RP RP RP 071-0092-29 071-0090-06 071-0090-41 071-0090-41 071-0092-37 071-0092-06 071-0092-05 071-0092-05 071-0099-06 071-0092-41 071-0099-06 071-0092-41 071-0090-21 071-0090-21 071-0090-41 071-0090-41 071-0092-37 071-0092-06 071-0092-37 071-0092-06 071-0092-37 071-0092-06 071-0092-37 * See Section F Introduction for more information. FC25 Section_Fc.indd 25 3/4/2008 8:00:10 AM Electrical Data - Copelametic - Air Cooled Model KANB-005L-IAA KANB-007E-CAV KAR1-0100-TAC KAR1-0100-TAD KAR1-010L-TAC KAR1-010L-TAD KAR2-0100-CAA KAR2-0100-CAV KAR2-010A-CAA KAR2-010L-CAV KARA-0100-TAC KARA-010A-TAC KARA-010E-TAC KARA-010L-TAC KARA-011A-TAD KARA-011E-TAD KARA-011L-TAD KARB-010A-CAV KARB-010E-CAV KARB-010L-CAV KAT4-0100-CAA KAT4-0100-CAB KAT4-0100-CAV Volts PH 115 208/230 208/230 460 208/230 460 115 208/230 115 208/230 208/230 208/230 208/230 208/230 460 460 460 208/230 208/230 208/230 115 230 208/230 1 1 3 3 3 3 1 1 1 1 3 3 3 3 3 3 3 1 1 1 1 1 1 Max LRA RLA 8 NA 4.3 2.2 4.3 2.2 15.4 7.4 15.4 7.4 4.3 4.3 4.3 4.3 2 2 2 7.4 7.4 7.4 NA NA NA 45 36 27 13.5 27 13.5 93 40 93 40 27 27 27 27 15 15 15 40 40 40 85.5 33.5 40 Resistance Run or Start or Line to WYE Line to Line 0.835 1.9 1.59 6.24 1.59 6.24 0.376 1.37 0.376 1.37 1.59 1.59 1.59 1.59 6.62 6.62 6.62 1.37 1.37 1.37 0.405 2.27 1.37 2.42 4.24 3.179 12.48 3.179 12.48 1.837 4.525 1.837 4.525 3.179 3.179 3.179 3.179 13.24 13.24 13.24 4.525 4.525 4.525 2.248 4.935 4.525 Start Cap Run Cap P/N P/N Relay P/N Part Protector Type* P/N 014-0061-02 040-0166-08 014-0061-04 014-0064-00 040-0166-09 RP RP 014-0061-05 014-0061-04 014-0061-05 014-0061-04 014-0064-08 014-0064-10 014-0064-08 014-0064-10 040-0166-11 040-0166-10 040-0166-11 040-0166-10 RP RP RP RP 014-0061-04 014-0061-04 014-0061-04 014-0061-05 014-0061-04 014-0061-04 014-0064-10 014-0064-10 014-0064-10 014-0064-08 014-0064-00 014-0064-10 040-0166-10 040-0166-10 040-0166-10 040-0166-11 040-0166-10 040-0166-10 RP RP RP RP RP RP 071-0092-06 071-0092-41 071-0090-40 071-0090-43 071-0090-40 071-0090-43 071-0099-05 071-0092-39 071-0099-05 071-0092-39 071-0090-40 071-0090-40 071-0090-40 071-0090-40 071-0090-42 071-0090-42 071-0090-42 071-0092-39 071-0092-39 071-0092-39 071-0092-23 071-0092-25 071-0092-39 * See Section F Introduction for more information. FC26 Section_Fc.indd 26 3/4/2008 8:00:11 AM Electrical Data - Copelametic - Air Cooled Model KATA-0100-TAC KATA-0100-TAD KATA-010A-TAC KATA-010A-TAD KATA-0150-TAC KATA-0150-TAD KATA-0151-TAC KATA-015A-TAC KATA-015A-TAD KATA-015E-TAC KATA-015E-TAD KATA-015L-TAC KATA-0200-TAU KATA-020E-TAU KATA-020L-TAU KATB-0100-CAA KATB-0100-CAB KATB-0100-CAH KATB-0100-CAV KATB-010A-CAA KATB-010A-CAB KATB-010A-CAV KATB-0150-CAB Volts PH 208/230 460 208/230 460 208/230 460 208/230 208/230 460 208/230 460 208/230 200 200 200 115 230 208 208/230 115 230 208/230 230 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 1 1 1 1 1 1 1 1 Max LRA RLA 3.9 2.1 3.9 2.1 NA NA 6 5 2.9 5 2.9 5 6.4 6.4 6.4 12.4 5.5 7.3 7.2 12.4 5.5 7.2 NA 25 15 25 15 35.5 18.2 50 35.5 18.2 35.5 18.2 35.5 51 51 51 85.5 33.5 36.4 40 85.5 33.5 40 44 Resistance Run or Start or Line to WYE Line to Line 2.145 6.62 2.145 6.62 1.325 4.72 0.795 1.325 4.72 1.325 4.72 1.325 0 0 0 0.405 2.27 1.885 1.37 0.405 2.27 1.37 1.65 4.29 13.24 4.29 13.24 2.375 9.44 1.589 2.375 9.44 2.375 9.44 2.375 1.44 1.44 1.44 2.248 4.935 4.59 4.525 2.248 4.935 4.525 4.19 Start Cap Run Cap P/N P/N 014-0061-05 014-0061-04 014-0061-04 014-0061-04 014-0061-05 014-0061-04 014-0061-04 014-0036-21 014-0064-08 014-0064-00 014-0064-00 014-0064-10 014-0064-08 014-0064-00 014-0064-10 014-0064-10 Relay P/N 040-0166-11 040-0166-10 040-0166-25 040-0166-10 040-0166-11 040-0166-10 040-0166-10 040-0166-20 Part Protector Type* P/N RP RP RP RP RP RP RP RP 071-0090-04 071-0090-07 071-0090-04 071-0090-07 071-0090-03 071-0090-27 071-0090-22 071-0090-03 071-0090-27 071-0090-03 071-0090-27 071-0090-03 071-0090-31 071-0090-31 071-0090-31 071-0092-23 071-0092-25 071-0092-14 071-0092-39 071-0092-23 071-0092-25 071-0092-39 071-0092-18 * See Section F Introduction for more information. FC27 Section_Fc.indd 27 3/4/2008 8:00:11 AM Electrical Data - Copelametic - Air Cooled Model KATB-0150-CAH KATB-0150-CAV KATB-0151-CAB KATB-015A-CAB KATB-015A-CAH KATB-015A-CAV KATB-015E-CAV KATB-015L-CAV KATC-0150-TAC KATC-0200-TAU KATC-020E-TAD KATC-020E-TAU KATC-020L-TAU KATD-015E-CAV KWA1-0075-TAC KWA2-0075-CAV KWA2-0075-IAA KWA2-0075-IAB KWA2-0075-IAH KWD1-0075-TAC KWD2-0075-CAA KWD2-0075-CAV KWE1-0050-TAC Volts PH 208 208/230 230 230 208 208/230 208/230 208/230 208/230 200 460 200 200 208/230 208/230 208/230 115 230 208 208/230 115 208/230 208/230 1 1 1 1 1 1 1 1 3 3 3 3 3 1 3 1 1 1 1 3 1 1 3 Max LRA RLA 7.8 NA 7.4 6.1 7.8 NA 9 9 NA 6.4 3.5 6.4 6.4 9 2.6 5.2 10.2 5.4 5.6 2.4 9.9 5.1 1.9 45 55 44 44 45 55 55 55 35.5 51 25 51 51 55 19.9 36 59.8 30.4 34.1 19.9 65 36 13.2 Resistance Run or Start or Line to WYE Line to Line 1.32 0.94 1.28 1.65 1.32 0.94 0.94 0.94 1.325 0 3.165 0 0 0.94 2.28 1.9 0.59 2.34 2 2.28 0.519 1.9 3.34 4.19 3.45 4.105 4.19 4.19 3.45 3.45 3.45 2.375 1.44 6.329 1.44 1.44 3.45 4.551 4.24 1.4 5.53 5.15 4.551 1.266 4.24 6.69 Start Cap Run Cap P/N P/N 014-0036-21 014-0036-22 014-0036-21 014-0036-21 014-0036-21 014-0036-22 014-0036-22 014-0036-22 014-0064-10 014-0064-19 014-0064-19 014-0064-10 014-0064-10 014-0064-19 014-0064-19 014-0064-19 Relay P/N Part Protector Type* P/N 040-0166-30 040-0166-20 040-0166-20 040-0166-20 040-0166-30 040-0166-20 040-0166-20 040-0166-20 RP RP RP RP RP RP RP RP 014-0036-22 014-0064-19 040-0166-20 RP 014-0061-04 014-0064-00 040-0166-09 014-0061-11 040-0166-08 014-0061-04 040-0166-09 014-0061-04 040-0166-09 RP RP RP RP 014-0061-11 014-0064-06 040-0166-33 014-0061-04 014-0064-00 040-0166-09 RP RP 071-0092-18 071-0099-04 071-0092-18 071-0092-18 071-0092-18 071-0099-04 071-0099-04 071-0099-04 071-0090-03 071-0090-31 071-0090-13 071-0090-31 071-0090-31 071-0099-04 071-0090-05 071-0092-29 071-0099-00 071-0092-27 071-0092-27 071-0090-05 071-0099-07 071-0092-29 071-0090-06 * See Section F Introduction for more information. FC28 Section_Fc.indd 28 3/4/2008 8:00:11 AM Electrical Data - Copelametic - Air Cooled Model KWE1-0075-TAC KWE2-0050-CAV KWE2-0050-IAA KWE2-0050-IAB KWE2-0050-IAH KWE2-0075-CAA KWE2-0075-CAV KWG1-0050-TAC KWG1-0075-TAC KWG1-0100-TAC KWG1-0100-TAD KWG2-0050-CAV KWG2-0050-IAA KWG2-0050-IAB KWG2-0050-IAH KWG2-0075-CAV KWG2-0075-IAA KWG2-0075-IAB KWG2-0075-IAH KWG2-0100-CAA KWG2-0100-CAV KWGA-010E-TAC KWGA-010L-TAC Volts PH 208/230 208/230 115 230 208 115 208/230 208/230 208/230 208/230 460 208/230 115 230 208 208/230 115 230 208 115 208/230 208/230 208/230 3 1 1 1 1 1 1 3 3 3 3 1 1 1 1 1 1 1 1 1 1 3 3 Max LRA RLA 3.4 3.4 7.8 4.1 4.1 10.9 5.4 1.9 2.6 4.1 1.6 3.6 7.8 4.1 4.1 5.4 9.5 5.4 5.6 11.9 6.4 4.3 4.3 19.9 24 45 22.5 25.5 65 36 13.2 19.9 27 13.5 24 45 22.5 25.5 36 59.8 30.4 34.1 85.5 40 27 27 Resistance Run or Start or Line to WYE Line to Line 2.28 2.9 0.835 3.305 2.92 0.519 1.9 3.34 2.28 1.59 6.24 2.9 0.835 3.305 2.92 1.9 0.59 2.34 2 0.405 1.37 1.59 1.59 4.551 5.785 2.42 9.585 7.9 1.266 4.24 6.69 4.551 3.179 12.48 5.785 2.42 9.585 7.9 4.24 1.4 5.53 5.15 2.248 4.525 3.179 3.179 Start Cap Run Cap P/N P/N Relay P/N Part Protector Type* P/N 014-0036-21 014-0064-00 040-0166-09 014-0061-02 040-0166-08 014-0061-09 040-0166-09 014-0061-09 040-0166-09 014-0061-11 014-0064-06 040-0166-33 014-0061-04 014-0064-00 040-0166-09 RP RP RP RP RP RP 014-0036-21 014-0061-02 014-0061-09 014-0061-09 014-0061-04 014-0061-11 014-0061-04 014-0061-04 014-0061-05 014-0061-04 RP RP RP RP RP RP RP RP RP RP 014-0064-00 040-0166-09 040-0166-08 040-0166-09 040-0166-09 014-0064-00 040-0166-09 040-0166-08 040-0166-09 040-0166-09 014-0064-08 040-0166-11 014-0064-10 040-0166-10 071-0090-41 071-0092-37 071-0092-06 071-0092-05 071-0092-05 071-0099-06 071-0092-29 071-0090-06 071-0090-05 071-0090-16 071-0090-07 071-0092-37 071-0092-06 071-0092-05 071-0092-05 071-0092-29 071-0099-00 071-0092-27 071-0092-27 071-0092-40 071-0092-39 071-0090-50 071-0090-50 * See Section F Introduction for more information. FC29 Section_Fc.indd 29 3/4/2008 8:00:12 AM Electrical Data - Copelametic - Air Cooled Model KWGA-011E-TAD KWGA-011L-TAD KWGA-0150-TAC KWGA-0150-TAD KWGA-015A-TAC KWGB-010E-CAV KWGB-010L-CAV KWGB-0150-CAV KWJ1-0075-TAC KWJ1-0100-TAC KWJ1-0100-TAD KWJ3-0075-CAV KWJ3-0075-IAA KWJ3-0075-IAB KWJ3-0075-IAH KWJ3-0100-CAA KWJ3-0100-CAB KWJ3-0100-CAH KWJ3-0100-CAV KWJA-0101-TAC KWJA-010A-TAC KWJA-011A-TAC KWJA-011A-TAD Volts PH 460 460 208/230 460 208/230 208/230 208/230 208/230 208/230 208/230 460 208/230 115 230 208 115 230 208 208/230 208/230 208/230 208/230 460 3 3 3 3 3 1 1 1 3 3 3 1 1 1 1 1 1 1 1 3 3 3 3 Max LRA RLA 2.1 2.1 5.5 2.5 5.5 7.5 7.5 9.6 2.7 3.4 2.1 5.1 9.1 5.4 5.9 12.4 5.4 6.9 6.9 4.5 NA 4.6 2 15 15 35.5 18.2 35.5 40 40 55 19.9 25 15 36 59.8 30.4 34.1 85.5 33.5 36.4 40 27 25 27 15 Resistance Run or Start or Line to WYE Line to Line 6.62 6.62 1.325 4.72 1.325 1.37 1.37 0.94 2.28 2.145 6.62 1.9 0.59 2.34 2 0.405 2.27 1.885 1.37 1.59 2.145 1.59 6.62 13.24 13.24 2.375 9.44 2.375 4.525 4.525 3.45 4.551 4.29 13.24 4.24 1.4 5.53 5.15 2.248 4.935 4.59 4.525 3.179 4.29 3.179 13.24 Start Cap Run Cap P/N P/N Relay P/N Part Protector Type* P/N 014-0061-04 014-0064-14 040-0166-10 014-0061-04 014-0064-14 040-0166-10 014-0036-22 014-0064-19 040-0166-20 RP RP RP 014-0061-04 014-0061-11 014-0061-04 014-0061-04 014-0061-05 014-0061-04 014-0061-04 014-0061-04 RP RP RP RP RP RP RP RP 014-0064-00 040-0166-09 040-0166-08 040-0166-09 040-0166-09 014-0064-08 040-0166-11 014-0064-00 040-0166-10 014-0064-00 040-0166-25 014-0064-10 040-0166-10 071-0090-42 071-0090-42 071-0090-39 071-0090-27 071-0090-39 071-0092-42 071-0092-42 071-0099-04 071-0090-05 071-0090-04 071-0090-07 071-0092-29 071-0099-00 071-0092-27 071-0092-27 071-0092-23 071-0092-25 071-0092-14 071-0092-39 071-0090-16 071-0090-04 071-0090-50 071-0090-42 * See Section F Introduction for more information. FC30 Section_Fc.indd 30 3/4/2008 8:00:12 AM Electrical Data - Copelametic - Air Cooled Model KWJA-011E-TAC KWJA-011E-TAD KWJB-0100-CAV KWJB-010E-CAV KWJC-011E-TAC KWK1-0100-TAC KWK1-0100-TAD KWK2-0100-CAA KWK2-0100-CAB KWK2-0100-CAH KWK2-0100-CAV KWKA-010A-TAC KWKA-011E-TAD KWKA-0200-TAC KWKA-0200-TAD KWKA-020A-TAC KWKA-020A-TAD KWKA-020E-TAC KWKB-0150-CAB KWKB-0200-CAV KWKB-020A-CAV KWKB-021E-CAV KWL1-0100-TAC Volts PH 208/230 460 208/230 208/230 208/230 208/230 460 115 230 208 208/230 208/230 460 208/230 460 208/230 460 208/230 230 208/230 208/230 208/230 208/230 3 3 1 1 3 3 3 1 1 1 1 3 3 3 3 3 3 3 1 1 1 1 3 Max LRA RLA 4.6 2.1 6.9 6.9 4.6 3.3 1.9 11.4 5.4 7 7.3 3.3 2.4 6.8 3 6.8 3 6.5 7.5 9.1 9.1 10.6 3.3 27 15 40 40 27 25 15 85.5 33.5 36.4 40 25 15 50 25 50 25 50 44 55 55 55 25 Resistance Run or Start or Line to WYE Line to Line 1.59 6.62 1.37 1.37 1.59 2.145 6.62 0.405 2.27 1.885 1.37 2.145 6.62 0.795 3.165 0.795 3.165 0.795 1.65 0.94 0.94 0.94 2.145 3.179 13.24 4.525 4.525 3.179 4.29 13.24 2.248 4.935 4.59 4.525 4.29 13.24 1.589 6.329 1.589 6.329 1.589 4.19 3.45 3.45 3.45 4.29 Start Cap Run Cap P/N P/N Relay P/N Part Protector Type* P/N 014-0061-04 014-0064-10 040-0166-10 014-0061-04 014-0064-10 040-0166-10 RP RP 014-0061-05 014-0061-04 014-0061-04 014-0061-04 040-0166-11 040-0166-10 040-0166-25 040-0166-10 RP RP RP RP 014-0036-21 014-0064-11 040-0166-20 014-0036-22 014-0064-19 040-0166-20 014-0036-22 014-0064-19 040-0166-20 014-0036-22 014-0064-14 040-0166-20 RP RP RP RP 014-0064-08 014-0064-00 014-0064-00 014-0064-10 071-0090-50 071-0090-42 071-0092-39 071-0092-39 071-0090-50 071-0090-04 071-0090-07 071-0092-23 071-0092-25 071-0092-14 071-0092-39 071-0090-04 071-0090-42 071-0090-35 071-0090-16 071-0090-35 071-0090-16 071-0090-35 071-0092-29 071-0099-04 071-0099-04 071-0099-04 071-0090-04 * See Section F Introduction for more information. FC31 Section_Fc.indd 31 3/4/2008 8:00:13 AM Electrical Data - Copelametic - Air Cooled Model KWL1-0100-TAD KWL2-0100-CAA KWL2-0100-CAB KWL2-0100-CAH KWL2-0100-CAV KWLA-0100-TAD KWLA-010A-TAC KWLA-010A-TAD KWLA-0150-TAC KWLA-0150-TAD KWLA-0150-TAU KWLA-015A-TAC KWLA-015A-TAD KWLA-016E-TAC KWLA-016E-TAD KWLB-0100-CAV KWLB-0150-CAB KWLB-0150-CAH KWLB-0150-CAV KWLB-015A-CAB KWLB-015A-CAV KWLB-015E-CAV KWM1-0050-TAC Volts PH 460 115 230 208 208/230 460 208/230 460 208/230 460 200 208/230 460 208/230 460 208/230 230 208 208/230 230 208/230 208/230 208/230 3 1 1 1 1 3 3 3 3 3 3 3 3 3 3 1 1 1 1 1 1 1 3 Max LRA RLA 1.8 10.9 5.5 6.8 6.9 1.8 3.3 1.8 5.4 2.9 6.6 5.4 2.9 6.6 3.4 6.9 5.6 8.1 9.9 5.6 9.9 9.9 1.7 15 85.5 33.5 36.4 40 15 25 15 35.5 18.2 48.2 35.5 18.2 50 25 40 44 45 55 44 55 55 13.2 Resistance Run or Start or Line to WYE Line to Line 6.62 0.405 2.27 1.885 1.37 6.62 2.145 6.62 1.325 4.72 0 1.325 4.72 0.795 3.165 1.37 1.65 1.32 0.94 1.65 0.94 0.94 3.34 13.24 2.248 4.935 4.59 4.525 13.24 4.29 13.24 2.375 9.44 1.463 2.375 9.44 1.589 6.329 4.525 4.19 4.19 3.45 4.19 3.45 3.45 6.69 Start Cap Run Cap P/N P/N Relay P/N Part Protector Type* P/N 014-0061-05 014-0061-04 014-0061-04 014-0061-04 014-0064-08 014-0064-00 014-0064-00 014-0064-10 040-0166-11 040-0166-10 040-0166-25 040-0166-10 RP RP RP RP 014-0061-04 014-0036-21 014-0036-21 014-0036-22 014-0036-21 014-0036-22 014-0036-22 014-0064-10 014-0064-10 014-0064-10 014-0064-19 014-0064-10 014-0064-19 014-0064-19 040-0166-10 040-0166-20 040-0166-30 040-0166-20 040-0166-20 040-0166-20 040-0166-20 RP RP RP RP RP RP RP 071-0090-07 071-0092-23 071-0092-25 071-0092-14 071-0092-39 071-0090-07 071-0090-04 071-0090-07 071-0090-03 071-0090-27 071-0090-28 071-0090-03 071-0090-27 071-0090-35 071-0090-16 071-0092-39 071-0092-16 071-0092-18 071-0099-04 071-0092-16 071-0099-04 071-0099-04 071-0090-06 * See Section F Introduction for more information. FC32 Section_Fc.indd 32 3/4/2008 8:00:13 AM Electrical Data - Copelametic - Air Cooled Model KWM1-0075-TAC KWM1-0100-TAC KWM1-0100-TAD KWM2-0050-CAV KWM2-0050-IAA KWM2-0050-IAB KWM2-0050-IAH KWM2-0075-CAV KWM2-0075-IAA KWM2-0075-IAB KWM2-0075-IAH KWM2-0100-CAA KWM2-0100-CAV KWMA-0075-TAC KWMA-007E-TAC KWMB-0075-CAA KWMB-0075-CAV KWMB-007E-CAA KWMB-007E-CAV KWMC-007E-TAC KWN1-0050-TAC KWN1-0075-TAC KWN2-0050-CAV Volts PH 208/230 208/230 460 208/230 115 230 208 208/230 115 230 208 115 208/230 208/230 208/230 115 208/230 115 208/230 208/230 208/230 208/230 208/230 3 3 3 1 1 1 1 1 1 1 1 1 1 3 3 1 1 1 1 3 3 3 1 Max LRA RLA 2.7 4.5 2.2 3.7 7.2 3.8 3.8 5.6 9.2 6 6.1 15.5 7.5 3.2 3.2 10.9 5.6 10.9 5.6 3.2 2.1 3.5 3.6 19.9 27 13.5 24 45 22.5 25.5 36 59.8 30.4 34.1 93 40 19.9 19.9 85.5 36 85.5 36 19.9 13.2 19.9 24 Resistance Run or Start or Line to WYE Line to Line 2.28 1.59 6.24 2.9 0.835 3.305 2.92 1.9 0.59 2.34 2 0.376 1.37 2.28 2.28 0.405 1.9 0.405 1.9 2.28 3.34 2.28 2.9 4.551 3.179 12.48 5.785 2.42 9.585 7.9 4.24 1.4 5.53 5.15 1.837 4.525 4.551 4.551 2.248 4.24 2.248 4.24 4.551 6.69 4.551 5.785 Start Cap Run Cap P/N P/N Relay P/N Part Protector Type* P/N 014-0036-21 014-0061-02 014-0061-09 014-0061-09 014-0061-04 014-0061-11 014-0061-04 014-0061-04 014-0061-05 014-0061-04 014-0064-00 040-0166-09 040-0166-08 040-0166-09 040-0166-09 014-0064-00 040-0166-09 040-0166-08 040-0166-09 040-0166-09 014-0064-08 040-0166-11 014-0064-10 040-0166-10 RP RP RP RP RP RP RP RP RP RP 014-0061-05 014-0061-04 014-0061-05 014-0061-04 014-0064-08 014-0064-00 014-0064-08 014-0064-00 040-0166-11 040-0166-09 040-0166-21 040-0166-09 RP RP RP RP 014-0036-21 014-0064-00 040-0166-09 RP 071-0090-05 071-0090-40 071-0090-43 071-0092-37 071-0092-06 071-0092-05 071-0092-05 071-0092-29 071-0099-00 071-0092-27 071-0092-27 071-0099-05 071-0092-39 071-0090-41 071-0090-41 071-0092-40 071-0092-29 071-0092-40 071-0092-29 071-0090-41 071-0090-06 071-0090-41 071-0092-37 * See Section F Introduction for more information. FC33 Section_Fc.indd 33 3/4/2008 8:00:14 AM Electrical Data - Copelametic - Air Cooled Model KWN2-0050-IAA KWN2-0050-IAB KWN2-0050-IAH KWN2-0075-CAA KWN2-0075-CAV KWNA-006E-TAC KWNA-007E-TAC KWNB-0050-CAV KWNB-0050-IAA KWNB-005A-CAV KWNB-005E-CAV KWNB-005E-IAA KWNB-007E-CAV KWR1-0100-TAC KWR1-0100-TAD KWR2-0100-CAA KWR2-0100-CAV KWRA-010E-TAC KWRA-011E-TAD KWRA-011L-TAD KWRB-010E-CAV KWTA-0100-TAC KWTA-0100-TAD Volts PH 115 230 208 115 208/230 208/230 208/230 208/230 115 208/230 208/230 115 208/230 208/230 460 115 208/230 208/230 460 460 208/230 208/230 460 1 1 1 1 1 3 3 1 1 1 1 1 1 3 3 1 1 3 3 3 1 3 3 Max LRA RLA 8.1 4.2 4.2 11.7 6.1 2.2 3.5 3.6 8 3.6 3.6 8 NA 4.3 2.2 15.4 7.4 4.3 2 2 7.4 3.9 2.1 45 22.5 25.5 65 36 13.2 19.9 24 45 24 24 45 36 27 13.5 93 40 27 15 15 40 25 15 Resistance Run or Start or Line to WYE Line to Line 0.835 3.305 2.92 0.519 1.9 3.34 2.28 2.9 0.835 2.9 2.9 0.835 1.9 1.59 6.24 0.376 1.37 1.59 6.62 6.62 1.37 2.145 6.62 2.42 9.585 7.9 1.266 4.24 6.69 4.551 5.785 2.42 5.785 5.785 2.42 4.24 3.179 12.48 1.837 4.525 3.179 13.24 13.24 4.525 4.29 13.24 Start Cap Run Cap P/N P/N Relay P/N Part Protector Type* P/N 014-0061-02 040-0166-08 014-0061-09 040-0166-09 014-0061-09 040-0166-09 014-0061-11 014-0064-06 040-0166-33 014-0061-04 014-0064-00 040-0166-09 RP RP RP RP RP 014-0036-21 014-0061-02 014-0036-21 014-0036-21 014-0061-02 014-0061-04 014-0064-00 040-0166-09 040-0166-08 014-0064-00 040-0166-09 014-0064-00 040-0166-09 040-0166-08 014-0064-00 040-0166-09 RP RP RP RP RP RP 014-0061-05 014-0064-08 040-0166-11 014-0061-04 014-0064-10 040-0166-10 RP RP 014-0061-04 014-0064-10 040-0166-10 RP 071-0092-06 071-0092-05 071-0092-05 071-0099-06 071-0092-41 071-0090-21 071-0090-41 071-0092-37 071-0092-06 071-0092-37 071-0092-37 071-0092-06 071-0092-41 071-0090-40 071-0090-43 071-0099-05 071-0092-39 071-0090-40 071-0090-42 071-0090-42 071-0092-39 071-0090-04 071-0090-07 * See Section F Introduction for more information. FC34 Section_Fc.indd 34 3/4/2008 8:00:14 AM Electrical Data - Copelametic - Air Cooled Model KWTA-010A-TAC KWTA-010A-TAD KWTA-0150-TAC KWTA-0150-TAD KWTA-015A-TAC KWTA-015A-TAD KWTB-0100-CAA KWTB-0100-CAB KWTB-0100-CAH KWTB-0100-CAV KWTB-010A-CAH KWTB-010A-CAV KWTB-0150-CAB KWTB-0150-CAH KWTB-0150-CAV LAC1-0300-TAE LAC1-0310-CAB LAC1-0310-TAC LAC1-0310-TAD LAC1-0310-TAU LACA-031A-TAC LACA-032A-TAD LACA-032E-TAC Volts PH 208/230 460 208/230 460 208/230 460 115 230 208 208/230 208 208/230 230 208 208/230 575 230 208/230 460 200 208/230 460 208/230 3 3 3 3 3 3 1 1 1 1 1 1 1 1 1 3 1 3 3 3 3 3 3 Max LRA RLA 3.9 2.1 5 2.9 5 2.9 12.4 5.5 7.3 7.2 7.3 7.2 6.1 7.8 9.6 NA NA NA NA NA 9.2 6 12.8 25 15 35.5 18.2 35.5 18.2 85.5 33.5 36.4 40 36.4 40 44 45 55 30 86 82 41 99.7 82 56 112 Resistance Run or Start or Line to WYE Line to Line 2.145 6.62 1.325 4.72 1.325 4.72 0.405 2.27 1.885 1.37 1.885 1.37 1.65 1.32 0.94 2.7 0.61 0.47 1.9 0 0.47 1.145 0.291 4.29 13.24 2.375 9.44 2.375 9.44 2.248 4.935 4.59 4.525 4.59 4.525 4.19 4.19 3.45 5.4 2.54 0.9 3.6 0.056 0.9 2.29 0.581 Start Cap Run Cap P/N P/N 014-0061-05 014-0061-04 014-0061-04 014-0061-04 014-0061-04 014-0061-04 014-0036-21 014-0036-21 014-0036-22 014-0064-08 014-0064-00 014-0064-00 014-0064-10 014-0064-00 014-0064-10 014-0064-10 014-0064-10 014-0064-19 Relay P/N Part Protector Type* P/N 040-0166-11 040-0166-10 040-0166-25 040-0166-10 040-0166-25 040-0166-10 040-0166-20 040-0166-30 040-0166-20 RP RP RP RP RP RP RP RP RP 014-0006-13 014-0064-14 040-0166-28 RP 071-0090-04 071-0090-07 071-0090-03 071-0090-27 071-0090-03 071-0090-27 071-0092-23 071-0092-25 071-0092-14 071-0092-39 071-0092-14 071-0092-39 071-0092-18 071-0092-18 071-0099-04 071-0090-14 071-0119-01 071-0090-01 071-0090-03 071-0090-30 071-0090-01 071-0090-54 071-0090-47 * See Section F Introduction for more information. FC35 Section_Fc.indd 35 3/4/2008 8:00:14 AM Electrical Data - Copelametic - Air Cooled Model LACA-032E-TAD LACA-032L-TAC LACA-032L-TAD LACB-031A-CAB LACB-032E-CAB LACB-032L-CAB LAH1-0300-TAE LAH1-0310-CAB LAH1-0310-TA7 LAH1-0310-TAC LAH1-0310-TAD LAHA-0310-TAC LAHA-0310-TAD LAHA-031A-TAC LAHA-031A-TAD LAHA-031E-TAC LAHA-031L-TAC LAHA-031L-TAD LAHA-0320-TA7 LAHA-0320-TAC LAHA-0320-TAU LAHA-032A-TAE LAHA-032E-TAC Volts PH 460 208/230 460 230 230 230 575 230 380 208/230 460 208/230 460 208/230 460 208/230 208/230 460 380 208/230 200 575 208/230 3 3 3 1 1 1 3 1 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 Max LRA RLA 6 12.8 6 15.4 15.5 15.5 4 15.1 6.9 9.9 5.7 9.9 NA 8.5 5.1 8.5 8.5 5.1 6.1 12.8 12.8 4.1 12.8 56 112 56 86 105 105 30 86 46 82 41 82 41 82 41 82 82 41 56 112 112 30 112 Resistance Run or Start or Line to WYE Line to Line 1.145 0.291 1.145 0.61 0.472 0.472 2.7 0.61 0 0.47 1.9 0.47 1.675 0.444 1.675 0.444 0.444 1.675 1.145 0.291 0.291 2.7 0.291 2.29 0.581 2.29 2.54 1.36 1.36 5.4 2.54 2.76 0.9 3.6 0.9 3.35 0.943 3.35 0.943 0.943 3.35 2.29 0.581 0.581 5.4 0.581 Start Cap Run Cap P/N P/N Relay P/N Part Protector Type* P/N 014-0006-13 014-0064-14 040-0166-28 014-0006-13 014-0064-18 040-0166-28 014-0006-13 014-0064-18 040-0166-28 RP RP RP 014-0006-13 014-0064-12 040-0166-28 RP 071-0090-54 071-0090-47 071-0090-54 071-0119-01 071-0119-05 071-0119-05 071-0090-14 071-0119-01 071-0090-33 071-0090-19 071-0090-03 071-0090-19 071-0090-03 071-0090-19 071-0090-03 071-0090-19 071-0090-19 071-0090-03 071-0090-46 071-0090-47 071-0090-47 071-0090-14 071-0090-47 * See Section F Introduction for more information. FC36 Section_Fc.indd 36 3/4/2008 8:00:15 AM Electrical Data - Copelametic - Air Cooled Model LAHA-032E-TAD LAHA-032E-TAE LAHA-032L-TAC LAHA-032L-TAD LAHA-032L-TAE LAHB-0311-CAB LAHB-031A-CAB LAHB-031E-CAB LAHB-031L-CAB LAHB-032E-CAB LAHB-032L-CAB LAL1-0300-TAE LAL1-0310-CAB LAL1-0310-TAC LAL1-0310-TAD LAL1-031L-TAC LAL1-031L-TAD LALA-031A-TAC LALA-032E-FXX LALA-032E-TAC LALA-032E-TAD LALA-032L-TAC LALA-032L-TAD Volts PH 460 575 208/230 460 575 230 230 230 230 230 230 575 230 208/230 460 208/230 460 208/230 55 208/230 460 208/230 460 3 3 3 3 3 1 1 1 1 1 1 3 1 3 3 3 3 3 3 3 3 3 3 Max LRA RLA 6 4.1 12.8 6 4.1 16.6 16.6 16.6 16.6 16.7 16.7 NA NA NA NA 10.9 5 10.9 NA 12.6 6.2 12.6 6.2 56 30 112 56 30 93 93 93 93 105 105 30 86 82 41 82 41 82 320 112 56 112 56 Resistance Run or Start or Line to WYE Line to Line 1.145 2.7 0.291 1.145 2.7 0.574 0.574 0.574 0.574 0.472 0.472 2.7 0.61 0.47 1.9 0.47 1.9 0.47 0 0.291 1.145 0.291 1.145 2.29 5.4 0.581 2.29 5.4 1.899 1.899 1.899 1.899 1.36 1.36 5.4 2.54 0.9 3.6 0.9 3.6 0.9 0.12 0.581 2.29 0.581 2.29 Start Cap Run Cap P/N P/N 014-0006-13 014-0006-13 014-0006-13 014-0006-13 014-0006-13 014-0006-13 014-0064-14 014-0064-14 014-0064-14 014-0064-14 014-0064-18 014-0064-18 Relay P/N Part Protector Type* P/N 040-0166-28 040-0166-28 040-0166-28 040-0166-28 040-0166-28 040-0166-28 RP RP RP RP RP RP 014-0006-13 014-0064-14 040-0166-28 RP 071-0090-54 071-0090-14 071-0090-47 071-0090-54 071-0090-14 071-0119-05 071-0119-05 071-0119-05 071-0119-05 071-0119-05 071-0119-05 071-0090-14 071-0119-01 071-0090-18 071-0090-03 071-0090-18 071-0090-03 071-0090-18 071-0090-47 071-0090-46 071-0090-47 071-0090-46 * See Section F Introduction for more information. FC37 Section_Fc.indd 37 3/4/2008 8:00:15 AM Electrical Data - Copelametic - Air Cooled Model Volts PH LALB-031A-CAB 230 LALB-032E-CAB 230 LALB-032L-CAB 230 LAM1-0300-TAE 575 LAM1-0310-CAB 230 LAM1-0310-TAC 208/230 LAM1-0310-TAD 460 LAMA-031A-TAC 208/230 LAMA-031A-TAD 460 LAMB-031A-CAB 230 1 1 1 3 1 3 3 3 3 1 Max LRA RLA 14.2 15 15 4 12.7 10 4.7 10 4.7 12.7 86 105 105 30 86 82 41 82 41 86 Resistance Run or Start or Line to WYE Line to Line 0.61 0.472 0.472 2.7 0.61 0.47 1.9 0.47 1.9 0.61 2.54 1.36 1.36 5.4 2.54 0.9 3.6 0.9 3.6 2.54 Start Cap Run Cap P/N P/N Relay P/N Part Protector Type* P/N 014-0006-13 014-0064-14 040-0166-28 014-0006-13 014-0064-18 040-0166-28 014-0006-13 014-0064-18 040-0166-28 RP RP RP 014-0006-13 014-0064-12 040-0166-28 RP 014-0006-13 014-0064-12 040-0166-28 RP 071-0119-01 071-0119-05 071-0119-05 071-0090-13 071-0119-01 071-0090-01 071-0090-03 071-0090-01 071-0090-03 071-0119-01 * See Section F Introduction for more information. FC38 Section_Fc.indd 38 3/4/2008 8:00:16 AM Electrical Data - Copelametic Small Refrigerant-Cooled Compressors Model 2DA3-060E-TFE 2DA3F23K0-TFC 2DA3F23K0-TFD 2DA3F23K0-TFE 2DA3F23KE-TFC 2DA3F23KE-TFD 2DA3F23KE-TFE 2DA3F23KL-TFC 2DA3F23KL-TFD 2DA3F23KL-TFE 2DA3R58K0-TFC 2DA3R58K0-TFD 2DA3R89K0-TFC 2DA3R89K0-TFD 2DA3R89K0-TFE 2DA3R89KE-TFC 2DA3R89KE-TFD 2DA3R89KE-TFE 2DA3R89KL-TFC 2DA3R89KL-TFD 2DA3R89KL-TFE 2DA8F23KE-TFD 2DB3F25K0-TFC Max LRA Volts PH RLA 575 208/230 460 575 208/230 460 575 208/230 460 575 208/230 460 208/230 460 575 208/230 460 575 208/230 460 575 460 208/230 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 9.1 28.8 9.7 9.1 28.8 9.7 9.1 28.8 9.7 9.1 22.3 10.4 32 14.1 13.3 32 14.1 13.3 32 14.1 13.3 9.7 28.2 49 161 60 49 161 60 49 161 60 49 120 60 169 85 67 169 85 67 169 85 67 60 161 Resistance Start Cap Run Cap Start or Run or P/N P/N Line to Line Line to WYE 3.714 0.419 2.382 3.714 0.419 2.382 3.714 0.419 2.382 3.714 0.595 2.382 0.386 1.508 2.518 0.386 1.508 2.518 0.386 1.508 2.518 2.382 0.419 * See Section F Introduction for more information. Section_Fd.indd 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Relay P/N Part Protector Type* P/N 071-0429-18 071-0429-08 071-0429-10 071-0429-18 071-0429-08 071-0429-10 071-0429-18 071-0429-08 071-0429-10 071-0429-18 071-0429-02 071-0429-10 071-0429-08 071-0429-05 071-0429-25 071-0429-08 071-0429-05 071-0429-25 071-0429-08 071-0429-05 071-0429-25 071-0429-10 071-0429-08 FD1 3/4/2008 8:02:47 AM Electrical Data - Copelametic Small Refrigerant-Cooled Compressors Model 2DB3F25K0-TFD 2DB3F25K0-TFE 2DB3F25KE-TFC 2DB3F25KE-TFD 2DB3F25KE-TFE 2DB3F25KL-TFC 2DB3F25KL-TFD 2DB3F25KL-TFE 2DB3R61K0-TFC 2DB3R61K0-TFD 2DB8F25KE-TFD 2DC3-0500-TFD 2DC3-050E-TFC 2DC3-050E-TFD 2DC3R53K0-CFB 2DC3R53K0-TFC 2DC3R53K0-TFD 2DC3R53K0-TFE 2DC3R53KE-TFC 2DC3R53KE-TFD 2DC3R53KE-TFE 2DC3R53KL-CFB 2DC3R53KL-TFC FD2 Max LRA Volts PH RLA 460 575 208/230 460 575 208/230 460 575 208/230 460 460 460 208/230 460 230 208/230 460 575 208/230 460 575 230 208/230 3 3 3 3 3 3 3 3 3 3 3 3 3 3 1 3 3 3 3 3 3 1 3 13.3 9.6 28.2 13.3 9.6 28.2 13.3 9.6 19.1 10.2 13.3 10.4 22.3 10.4 30.2 22.3 10.4 7.7 22.3 10.4 7.7 30.2 22.3 80 63 161 80 63 161 80 63 120 60 80 60 120 60 125 120 60 49 120 60 49 125 120 Resistance Start Cap Run Cap Start or Run or P/N P/N Line to Line Line to WYE 1.674 2.614 0.419 1.674 2.614 0.419 1.674 2.614 0.595 2.382 1.674 2.382 0.595 2.382 1.4 0.595 2.382 3.714 0.595 2.382 3.714 1.4 0.595 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0.37 0 0 0 0 0 0 0.37 0 Relay P/N Part Protector Type* P/N 014-0006-14 014-0064-18 040-0166-23 RP 014-0006-14 014-0064-18 040-0166-23 RP 071-0429-05 071-0429-26 071-0429-08 071-0429-05 071-0429-26 071-0429-08 071-0429-05 071-0429-26 071-0429-02 071-0429-10 071-0429-05 071-0429-10 071-0429-13 071-0429-10 071-0476-01 071-0429-13 071-0429-10 071-0429-23 071-0429-13 071-0429-10 071-0429-23 071-0476-01 071-0429-13 * See Section F Introduction for more information. Section_Fd.indd 2 3/4/2008 8:02:52 AM Electrical Data - Copelametic Small Refrigerant-Cooled Compressors Model 2DC3R53KL-TFD 2DC3R53KL-TFE 2DCJR53K0-TFC 2DD3-050E-TFD 2DD3R63K0-TFC 2DD3R63K0-TFD 2DD3R63K0-TFE 2DD3R63KE-TFC 2DD3R63KE-TFD 2DD3R63KE-TFE 2DD3R63KL-TFC 2DD3R63KL-TFD 2DD3R63KL-TFE 2DD8R63K0-TFC 2DF3-0300-CFB 2DF3-0300-TFC 2DF3-030E-CFB 2DF3-030E-TFC 2DF3F16K0-CFB 2DF3F16K0-TFC 2DF3F16K0-TFD 2DF3F16K0-TFE 2DF3F16KE-CFB Max LRA Volts PH RLA 460 575 208/230 460 208/230 460 575 208/230 460 575 208/230 460 575 208/230 230 208/230 230 208/230 230 208/230 460 575 230 3 3 3 3 3 3 3 3 3 3 3 3 3 3 1 3 1 3 1 3 3 3 1 10.4 7.7 22.3 10.5 22.3 10.5 7.9 22.3 10.5 7.9 22.3 10.5 7.9 22.3 25.7 16.9 25.7 16.9 25.7 16.9 8.1 6.7 25.7 60 49 120 60 120 60 49 120 60 49 120 60 49 120 125 102 125 102 125 102 52 41 125 Resistance Start Cap Run Cap Start or Run or P/N P/N Line to Line Line to WYE 2.382 3.714 0.595 2.382 0.595 2.382 3.714 0.595 2.382 3.714 0.595 2.382 3.714 0.595 1.4 0.67 1.4 0.67 1.4 0.67 2.68 4.406 1.4 * See Section F Introduction for more information. Section_Fd.indd 3 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0.37 0 0.37 0 0.37 0 0 0 0.37 Relay P/N Part Protector Type* P/N 014-0006-14 014-0064-18 040-0166-23 RP 014-0006-14 014-0064-18 040-0166-23 RP 014-0006-14 014-0064-18 040-0166-23 RP 014-0006-14 014-0064-18 040-0166-23 RP 071-0429-10 071-0429-23 071-0429-13 071-0429-10 071-0429-24 071-0429-10 071-0429-23 071-0429-24 071-0429-10 071-0429-23 071-0429-24 071-0429-10 071-0429-23 071-0429-24 071-0476-01 071-0429-22 071-0476-01 071-0429-22 071-0476-01 071-0429-22 071-0429-23 071-0429-27 071-0476-01 FD3 3/4/2008 8:02:52 AM Electrical Data - Copelametic Small Refrigerant-Cooled Compressors Model 2DF3F16KE-TFC 2DF3F16KE-TFD 2DF3F16KE-TFE 2DF3F16KL-TFC 2DF3F16KL-TFD 2DF3F16KL-TFE 2DL3-075E-TFC 2DL3F20K0-TFC 2DL3F20K0-TFD 2DL3F20K0-TFE 2DL3F20KE-TFC 2DL3F20KE-TFD 2DL3F20KE-TFE 2DL3F20KL-TFC 2DL3F20KL-TFD 2DL3F20KL-TFE 2DL3R78K0-TFC 2DL3R78K0-TFD 2DL3R78K0-TFE 2DL3R78KE-TFC 2DL3R78KE-TFD 2DL3R78KE-TFE 2DL3R78KL-TFC FD4 Max LRA Volts PH RLA 208/230 460 575 208/230 460 575 208/230 208/230 460 575 208/230 460 575 208/230 460 575 208/230 460 575 208/230 460 575 208/230 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 16.9 8.1 6.7 16.9 8.1 6.7 31.6 26.3 8.7 7.7 26.3 8.7 7.7 26.3 8.7 7.7 31.6 13.9 13.2 31.6 13.9 13.2 31.6 102 52 41 102 52 41 169 161 60 49 161 60 49 161 60 49 169 85 67 169 85 67 169 Resistance Start Cap Run Cap Start or Run or P/N P/N Line to Line Line to WYE 0.67 2.68 4.406 0.67 2.68 4.406 0.386 0.419 2.382 3.714 0.419 2.382 3.714 0.419 2.382 3.714 0.386 1.508 2.518 0.386 1.508 2.518 0.386 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Relay P/N Part Protector Type* P/N 071-0429-22 071-0429-23 071-0429-27 071-0429-22 071-0429-23 071-0429-27 071-0429-08 071-0429-08 071-0429-10 071-0429-23 071-0429-08 071-0429-10 071-0429-23 071-0429-08 071-0429-10 071-0429-23 071-0429-08 071-0429-05 071-0429-25 071-0429-08 071-0429-05 071-0429-25 071-0429-08 * See Section F Introduction for more information. Section_Fd.indd 4 3/4/2008 8:02:52 AM Electrical Data - Copelametic Small Refrigerant-Cooled Compressors Model 2DL3R78KL-TFD 2DL3R78KL-TFE 3DA3A0500-TFC 3DA3A0500-TFD 3DA3A0500-TFE 3DA3A0600-TFC 3DA3A0600-TFD 3DA3A0600-TFE 3DA3A060E-TFC 3DA3A060E-TFD 3DA3A060E-TFE 3DA3A060L-TFC 3DA3A060L-TFD 3DA3A060L-TFE 3DA3A0750-TFC 3DA3A0750-TFD 3DA3A0750-TFE 3DA3A0750-TFU 3DA3A075E-TFC 3DA3A075E-TFD 3DA3A075E-TFE 3DA3A075L-TFC 3DA3A075L-TFD Max LRA Volts PH RLA 460 575 208/230 460 575 208/230 460 575 208/230 460 575 208/230 460 575 208/230 460 575 200 208/230 460 575 208/230 460 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 13.9 13.2 18.6 9.1 7.9 30.3 13.7 10.5 30.3 13.7 10.5 30.3 13.7 10.5 41 20 16.4 34.9 41 20 16.4 41 20 85 67 115 58 43 150 77 62 150 77 62 150 77 62 215 106 84 196 215 106 84 215 106 Resistance Start Cap Run Cap Start or Run or P/N P/N Line to Line Line to WYE 1.508 2.518 0.603 2.412 3.794 0.419 1.676 2.6 0.419 1.676 2.6 0.419 1.676 2.6 0.295 1.178 1.835 0.294 0.295 1.178 1.835 0.295 1.178 * See Section F Introduction for more information. Section_Fd.indd 5 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Relay P/N Part Protector Type* P/N 071-0429-05 071-0429-25 071-0429-02 071-0429-03 071-0429-19 071-0429-08 071-0429-05 071-0429-03 071-0429-08 071-0429-05 071-0429-03 071-0429-08 071-0429-05 071-0429-03 071-0429-06 071-0429-17 071-0429-11 071-0429-04 071-0429-06 071-0429-17 071-0429-11 071-0429-06 071-0429-17 FD5 3/4/2008 8:02:53 AM Electrical Data - Copelametic Small Refrigerant-Cooled Compressors Model 3DA3A075L-TFE 3DA3F18K0-TFC 3DA3F18K0-TFD 3DA3F28K0-TFC 3DA3F28K0-TFD 3DA3F28K0-TFE 3DA3F28KE-TFC 3DA3F28KE-TFD 3DA3F28KE-TFE 3DA3F28KL-TFC 3DA3F28KL-TFD 3DA3F28KL-TFE 3DA3R10M0-TFC 3DA3R10M0-TFD 3DA3R10M0-TFE 3DA3R10M0-TFU 3DA3R10ME-TFC 3DA3R10ME-TFD 3DA3R10ME-TFE 3DA3R10ML-TFC 3DA3R10ML-TFD 3DA3R10ML-TFE 3DA8A0500-TFD FD6 Max LRA Volts PH RLA 575 208/230 460 208/230 460 575 208/230 460 575 208/230 460 575 208/230 460 575 200 208/230 460 575 208/230 460 575 460 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 16.4 18.6 9.1 30.3 13.7 10.5 30.3 13.7 10.5 30.3 13.7 10.5 41 20 16.4 34.9 41 20 16.4 41 20 16.4 9.1 84 115 58 150 77 62 150 77 62 150 77 62 215 106 84 196 215 106 84 215 106 84 58 Resistance Start Cap Run Cap Start or Run or P/N P/N Line to Line Line to WYE 1.835 0.603 2.412 0.419 1.676 2.6 0.419 1.676 2.6 0.419 1.676 2.6 0.295 1.178 1.835 0.294 0.295 1.178 1.835 0.295 1.178 1.835 2.412 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Relay P/N Part Protector Type* P/N 071-0429-11 071-0429-02 071-0429-03 071-0429-08 071-0429-05 071-0429-03 071-0429-08 071-0429-05 071-0429-03 071-0429-08 071-0429-05 071-0429-03 071-0429-06 071-0429-17 071-0429-11 071-0429-04 071-0429-06 071-0429-17 071-0429-11 071-0429-06 071-0429-17 071-0429-11 071-0429-03 * See Section F Introduction for more information. Section_Fd.indd 6 3/4/2008 8:02:53 AM Electrical Data - Copelametic Small Refrigerant-Cooled Compressors Model 3DA8A0501-TFD 3DA8A051E-TFD 3DA8A060E-TFD 3DA8F28KE-TFD 3DB3A0500-TFC 3DB3A0500-TFD 3DB3A0500-TFE 3DB3A0750-TFC 3DB3A0750-TFD 3DB3A0750-TFE 3DB3A075E-TFC 3DB3A075E-TFD 3DB3A075E-TFE 3DB3A075L-TFC 3DB3A075L-TFD 3DB3A075L-TFE 3DB3A0900-TFU 3DB3A1000-TFC 3DB3A1000-TFD 3DB3A1000-TFE 3DB3A100E-TFC 3DB3A100E-TFD 3DB3A100E-TFE Max LRA Volts PH RLA 460 460 460 460 208/230 460 575 208/230 460 575 208/230 460 575 208/230 460 575 200 208/230 460 575 208/230 460 575 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 9.1 9.1 13.7 13.7 18 10.1 7.5 31.4 16.1 11 31.4 16.1 11 31.4 16.1 11 36.8 43.6 20 16.5 43.6 20 16.5 58 58 77 77 115 58 43 161 83 67 161 83 67 161 83 67 196 215 106 84 215 106 84 Resistance Start Cap Run Cap Start or Run or P/N P/N Line to Line Line to WYE 2.412 2.412 1.676 1.676 0.603 2.412 3.794 0.385 1.54 2.508 0.385 1.54 2.508 0.385 1.54 2.508 0.294 0.295 1.178 1.835 0.295 1.178 1.835 * See Section F Introduction for more information. Section_Fd.indd 7 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Relay P/N Part Protector Type* P/N 071-0429-03 071-0429-03 071-0429-05 071-0429-05 071-0429-02 071-0429-03 071-0429-19 071-0429-04 071-0429-09 071-0429-03 071-0429-04 071-0429-09 071-0429-03 071-0429-04 071-0429-09 071-0429-03 071-0429-20 071-0429-06 071-0429-17 071-0429-11 071-0429-06 071-0429-17 071-0429-11 FD7 3/4/2008 8:02:53 AM Electrical Data - Copelametic Small Refrigerant-Cooled Compressors Model 3DB3A100L-TFC 3DB3A100L-TFD 3DB3A100L-TFE 3DB3F22K0-TFC 3DB3F22K0-TFD 3DB3F27K0-TFU 3DB3F33K0-TFC 3DB3F33K0-TFD 3DB3F33K0-TFE 3DB3F33KE-TFC 3DB3F33KE-TFD 3DB3F33KE-TFE 3DB3F33KL-TFC 3DB3F33KL-TFD 3DB3F33KL-TFE 3DB3R12M0-TFC 3DB3R12M0-TFD 3DB3R12M0-TFE 3DB3R12ME-TFC 3DB3R12ME-TFD 3DB3R12ME-TFE 3DB3R12ML-TFC 3DB3R12ML-TFD FD8 Max LRA Volts PH RLA 208/230 460 575 208/230 460 200 208/230 460 575 208/230 460 575 208/230 460 575 208/230 460 575 208/230 460 575 208/230 460 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 43.6 20 16.5 18 10.1 36.8 31.4 16.1 11 31.4 16.1 11 31.4 16.1 11 43.6 20 16.5 43.6 20 16.5 43.6 20 215 106 84 115 58 196 161 83 67 161 83 67 161 83 67 215 106 84 215 106 84 215 106 Resistance Start Cap Run Cap Start or Run or P/N P/N Line to Line Line to WYE 0.295 1.178 1.835 0.603 2.412 0.294 0.385 1.54 2.508 0.385 1.54 2.508 0.385 1.54 2.508 0.295 1.178 1.835 0.295 1.178 1.835 0.295 1.178 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Relay P/N Part Protector Type* P/N 071-0429-06 071-0429-17 071-0429-11 071-0429-02 071-0429-03 071-0429-20 071-0429-04 071-0429-09 071-0429-03 071-0429-04 071-0429-09 071-0429-03 071-0429-04 071-0429-09 071-0429-03 071-0429-06 071-0429-17 071-0429-11 071-0429-06 071-0429-17 071-0429-11 071-0429-06 071-0429-17 * See Section F Introduction for more information. Section_Fd.indd 8 3/4/2008 8:02:53 AM Electrical Data - Copelametic Small Refrigerant-Cooled Compressors Model 3DB3R12ML-TFE 3DB4A1000-TFC 3DB4A1000-TFD 3DB4R12M0-TFC 3DB8A075E-TFD 3DB8F33KE-TFD 3DE3A0500-TFC 3DE3A0500-TFD 3DE3A0500-TFE 3DE3A0750-TFC 3DE3A0750-TFD 3DE3A0750-TFE 3DE3A0750-TFU 3DE3A075E-TFC 3DE3A075E-TFD 3DE3A075E-TFE 3DE3A075L-TFC 3DE3A075L-TFD 3DE3A075L-TFE 3DE3R10M0-TFC 3DE3R10M0-TFD 3DE3R10M0-TFE 3DE3R10ME-TFC Max LRA Volts PH RLA 575 208/230 460 208/230 460 460 208/230 460 575 208/230 460 575 200 208/230 460 575 208/230 460 575 208/230 460 575 208/230 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 16.5 43.6 20 43.6 16.1 16.1 18.6 11 7.9 41 20 16.4 34.9 41 20 16.4 41 20 16.4 41 20 16.4 41 84 215 106 215 83 83 115 58 43 215 106 84 196 215 106 84 215 106 84 215 106 84 215 Resistance Start Cap Run Cap Start or Run or P/N P/N Line to Line Line to WYE 1.835 0.295 1.178 0.295 1.54 1.54 0.603 2.412 3.794 0.295 1.178 1.835 0.294 0.295 1.178 1.835 0.295 1.178 1.835 0.295 1.178 1.835 0.295 * See Section F Introduction for more information. Section_Fd.indd 9 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Relay P/N Part Protector Type* P/N 071-0429-11 071-0429-06 071-0429-17 071-0429-06 071-0429-09 071-0429-09 071-0429-02 071-0429-03 071-0429-19 071-0429-06 071-0429-17 071-0429-11 071-0429-04 071-0429-06 071-0429-17 071-0429-11 071-0429-06 071-0429-17 071-0429-11 071-0429-06 071-0429-17 071-0429-11 071-0429-06 FD9 3/4/2008 8:02:54 AM Electrical Data - Copelametic Small Refrigerant-Cooled Compressors Model 3DE3R10ME-TFD 3DE3R10ME-TFE 3DE3R10ML-TFC 3DE3R10ML-TFD 3DE3R10ML-TFE 3DE8A0500-TFC 3DE8A0500-TFD 3DE8A060E-TFD 3DE8A0750-TFD 3DEHA075E-TFC 3DEHA075E-TFD 3DEHA075E-TFE 3DEHA075L-TFC 3DEHA075L-TFD 3DEHA075L-TFE 3DEHR10ME-TFC 3DEHR10ME-TFD 3DEHR10ME-TFE 3DEHR10ML-TFC 3DEHR10ML-TFD 3DEHR10ML-TFE 3DETA050E-TFD 3DETR70KE-TFD FD10 Max LRA Volts PH RLA 460 575 208/230 460 575 208/230 460 460 460 208/230 460 575 208/230 460 575 208/230 460 575 208/230 460 575 460 460 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 20 16.4 41 20 16.4 18.6 11 13.7 20 41 20 16.4 41 20 16.4 41 20 16.4 41 20 16.4 11 11 106 84 215 106 84 115 58 77 106 215 106 84 215 106 84 215 106 84 215 106 84 58 58 Resistance Start Cap Run Cap Start or Run or P/N P/N Line to Line Line to WYE 1.178 1.835 0.295 1.178 1.835 0.603 2.412 1.676 1.178 0.295 1.178 1.835 0.295 1.178 1.835 0.295 1.178 1.835 0.295 1.178 1.835 2.412 2.412 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Relay P/N Part Protector Type* P/N 071-0429-17 071-0429-11 071-0429-06 071-0429-17 071-0429-11 071-0429-02 071-0429-03 071-0429-05 071-0429-17 071-0429-06 071-0429-17 071-0429-11 071-0429-06 071-0429-17 071-0429-11 071-0429-06 071-0429-17 071-0429-11 071-0429-06 071-0429-17 071-0429-11 071-0429-03 071-0429-03 * See Section F Introduction for more information. Section_Fd.indd 10 3/4/2008 8:02:54 AM Electrical Data - Copelametic Small Refrigerant-Cooled Compressors Model 3DF3A0750-TFC 3DF3A0750-TFD 3DF3A0900-TFC 3DF3A0900-TFD 3DF3A0900-TFE 3DF3A090E-TFC 3DF3A090E-TFD 3DF3A090E-TFE 3DF3A090L-TFC 3DF3A090L-TFD 3DF3A090L-TFE 3DF3A1200-TFC 3DF3A1200-TFD 3DF3A120E-TFC 3DF3A120E-TFD 3DF3A120L-TFC 3DF3A120L-TFD 3DF3F26K0-TFC 3DF3F26K0-TFD 3DF3F40K0-TFC 3DF3F40K0-TFD 3DF3F40K0-TFE 3DF3F40KE-TFC Max LRA Volts PH RLA 208/230 460 208/230 460 575 208/230 460 575 208/230 460 575 208/230 460 208/230 460 208/230 460 208/230 460 208/230 460 575 208/230 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 30.7 15 39 16.9 16.4 39 16.9 16.4 39 16.9 16.4 48.1 23.6 48.1 23.6 48.1 23.6 30.7 15 39 16.9 16.4 39 161 83 215 106 84 215 106 84 215 106 84 275 138 275 138 275 138 161 83 215 106 84 215 Resistance Start Cap Run Cap Start or Run or P/N P/N Line to Line Line to WYE 0.385 1.54 0.295 1.178 1.835 0.295 1.178 1.835 0.295 1.178 1.835 0.229 0.908 0.229 0.908 0.229 0.908 0.385 1.54 0.295 1.178 1.835 0.295 * See Section F Introduction for more information. Section_Fd.indd 11 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Relay P/N Part Protector Type* P/N 071-0429-04 071-0429-09 071-0429-00 071-0429-09 071-0429-11 071-0429-00 071-0429-09 071-0429-11 071-0429-00 071-0429-09 071-0429-11 071-0504-05 071-0504-02 071-0504-05 071-0504-02 071-0504-05 071-0504-02 071-0429-04 071-0429-09 071-0429-00 071-0429-09 071-0429-11 071-0429-00 FD11 3/4/2008 8:02:54 AM Electrical Data - Copelametic Small Refrigerant-Cooled Compressors Model 3DF3F40KE-TFD 3DF3F40KE-TFE 3DF3F40KL-TFC 3DF3F40KL-TFD 3DF3F40KL-TFE 3DF3R15M0-TFC 3DF3R15M0-TFD 3DF3R15ME-TFC 3DF3R15ME-TFD 3DF3R15ML-TFC 3DF3R15ML-TFD 3DF4A0900-TFC 3DF4A0900-TFD 3DF4A1200-TFC 3DF4A1200-TFD 3DF4A120E-TFC 3DF4A120E-TFD 3DF4A120L-TFC 3DF4A120L-TFD 3DF4R15M0-TFC 3DF4R15ME-TFC 3DF4R15ME-TFD 3DF4R15ML-TFC FD12 Max LRA Volts PH RLA 460 575 208/230 460 575 208/230 460 208/230 460 208/230 460 208/230 460 208/230 460 208/230 460 208/230 460 208/230 208/230 460 208/230 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 16.9 16.4 39 16.9 16.4 48.1 23.6 48.1 23.6 48.1 23.6 39 16.9 48.1 23.6 48.1 23.6 48.1 23.6 48.1 48.1 23.6 48.1 106 84 215 106 84 275 138 275 138 275 138 215 106 275 138 275 138 275 138 275 275 138 275 Resistance Start Cap Run Cap Start or Run or P/N P/N Line to Line Line to WYE 1.178 1.835 0.295 1.178 1.835 0.229 0.908 0.229 0.908 0.229 0.908 0.295 1.178 0.229 0.908 0.229 0.908 0.229 0.908 0.229 0.229 0.908 0.229 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Relay P/N Part Protector Type* P/N 071-0429-09 071-0429-11 071-0429-00 071-0429-09 071-0429-11 071-0504-05 071-0504-02 071-0504-05 071-0504-02 071-0504-05 071-0504-02 071-0429-00 071-0429-09 071-0504-05 071-0504-02 071-0504-05 071-0504-02 071-0504-05 071-0504-02 071-0504-05 071-0504-05 071-0504-02 071-0504-05 * See Section F Introduction for more information. Section_Fd.indd 12 3/4/2008 8:02:54 AM Electrical Data - Copelametic Small Refrigerant-Cooled Compressors Model 3DF4R15ML-TFD 3DF4S11M0-TFC 3DF4S11M0-TFD 3DF4S11ME-TFC 3DF4S11ME-TFD 3DF4S11ML-TFC 3DF4S11ML-TFD 3DF8A0750-TFC 3DF8A0750-TFD 3DF8A0751-TFD 3DF8A075E-TFC 3DF8A076E-TFD 3DF8R98KE-TFC 3DFTA075E-TFD 3DG3A0900-TFC 3DG3A0900-TFD 3DG3A0900-TFE 3DG3A090E-TFC 3DG3A090E-TFD 3DG3A090E-TFE 3DG3A090L-TFC 3DG3A090L-TFD 3DG3A090L-TFE Max LRA Volts PH RLA 460 208/230 460 208/230 460 208/230 460 208/230 460 460 208/230 460 208/230 460 208/230 460 575 208/230 460 575 208/230 460 575 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 23.6 38.6 18.6 42.6 20.4 42.6 20.4 30.7 15 15 30.7 15 30.7 15 35.7 15.6 15.7 35.7 15.6 15.7 35.7 15.6 15.7 138 240 115 240 115 240 115 161 83 83 161 83 161 83 215 106 84 215 106 84 215 106 84 Resistance Start Cap Run Cap Start or Run or P/N P/N Line to Line Line to WYE 0.908 0.255 1.02 0.255 1.02 0.255 1.02 0.385 1.54 1.54 0.385 1.54 0.385 1.54 0.295 1.178 1.835 0.295 1.178 1.835 0.295 1.178 1.835 * See Section F Introduction for more information. Section_Fd.indd 13 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Relay P/N Part Protector Type* P/N 071-0504-02 071-0429-35 071-0429-33 071-0429-35 071-0429-33 071-0429-35 071-0429-33 071-0429-04 071-0429-09 071-0429-09 071-0429-04 071-0429-09 071-0429-04 071-0429-09 071-0429-00 071-0429-09 071-0429-11 071-0429-00 071-0429-09 071-0429-11 071-0429-00 071-0429-09 071-0429-11 FD13 3/4/2008 8:02:55 AM Electrical Data - Copelametic Small Refrigerant-Cooled Compressors Model 3DG3F40K0-TFC 3DG3F40K0-TFD 3DG3F40K0-TFE 3DG3F40KE-TFC 3DG3F40KE-TFD 3DG3F40KE-TFE 3DG3F40KL-TFC 3DG3F40KL-TFD 3DG3F40KL-TFE 3DGHA090E-TFC 3DGHA090E-TFD 3DGHA090E-TFE 3DGHA090L-TFC 3DGHA090L-TFD 3DGHA090L-TFE 3DGHF40KE-TFC 3DGHF40KE-TFD 3DGHF40KE-TFE 3DGHF40KL-TFC 3DGHF40KL-TFD 3DGHF40KL-TFE 3DH3A0600-TFC 3DH3A0600-TFD FD14 Max LRA Volts PH RLA 208/230 460 575 208/230 460 575 208/230 460 575 208/230 460 575 208/230 460 575 208/230 460 575 208/230 460 575 208/230 460 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 35.7 15.6 15.7 35.7 15.6 15.7 35.7 15.6 15.7 37 16.7 15.7 37 16.7 15.7 37 16.7 15.7 37 16.7 15.7 30.3 13.7 215 106 84 215 106 84 215 106 84 215 106 84 215 106 84 215 106 84 215 106 84 150 77 Resistance Start Cap Run Cap Start or Run or P/N P/N Line to Line Line to WYE 0.295 1.178 1.835 0.295 1.178 1.835 0.295 1.178 1.835 0.295 1.178 1.835 0.295 1.178 1.835 0.295 1.178 1.835 0.295 1.178 1.835 0.419 1.676 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Relay P/N Part Protector Type* P/N 071-0429-00 071-0429-09 071-0429-11 071-0429-00 071-0429-09 071-0429-11 071-0429-00 071-0429-09 071-0429-11 071-0429-00 071-0429-09 071-0429-11 071-0429-00 071-0429-09 071-0429-11 071-0429-00 071-0429-09 071-0429-11 071-0429-00 071-0429-09 071-0429-11 071-0429-08 071-0429-05 * See Section F Introduction for more information. Section_Fd.indd 14 3/4/2008 8:02:55 AM Electrical Data - Copelametic Small Refrigerant-Cooled Compressors Model 3DH3A0600-TFE 3DH3A060E-TFC 3DH3A060E-TFD 3DH3A060E-TFE 3DH3A060L-TFC 3DH3A060L-TFD 3DH3A060L-TFE 3DH3F28K0-TFC 3DH3F28K0-TFD 3DH3F28K0-TFE 3DH3F28KE-TFC 3DH3F28KE-TFD 3DH3F28KE-TFE 3DH3F28KL-TFC 3DH3F28KL-TFD 3DH3F28KL-TFE 3DHHA060E-TFC 3DHHA060E-TFD 3DHHA060E-TFE 3DHHA060L-TFC 3DHHA060L-TFD 3DHHA060L-TFE 3DHHF28KE-TFC Max LRA Volts PH RLA 575 208/230 460 575 208/230 460 575 208/230 460 575 208/230 460 575 208/230 460 575 208/230 460 575 208/230 460 575 208/230 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 10.5 30.3 13.7 10.5 30.3 13.7 10.5 30.3 13.7 10.5 30.3 13.7 10.5 30.3 13.7 10.5 26.8 12 10.5 26.8 12 10.5 26.8 62 150 77 62 150 77 62 150 77 62 150 77 62 150 77 62 150 77 62 150 77 62 150 Resistance Start Cap Run Cap Start or Run or P/N P/N Line to Line Line to WYE 2.6 0.419 1.676 2.6 0.419 1.676 2.6 0.419 1.676 2.6 0.419 1.676 2.6 0.419 1.676 2.6 0.419 1.676 2.6 0.419 1.676 2.6 0.419 * See Section F Introduction for more information. Section_Fd.indd 15 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Relay P/N Part Protector Type* P/N 071-0429-03 071-0429-08 071-0429-05 071-0429-03 071-0429-08 071-0429-05 071-0429-03 071-0429-08 071-0429-05 071-0429-03 071-0429-08 071-0429-05 071-0429-03 071-0429-08 071-0429-05 071-0429-03 071-0429-08 071-0429-05 071-0429-03 071-0429-08 071-0429-05 071-0429-03 071-0429-08 FD15 3/4/2008 8:02:55 AM Electrical Data - Copelametic Small Refrigerant-Cooled Compressors Model 3DHHF28KE-TFD 3DHHF28KE-TFE 3DHHF28KL-TFC 3DHHF28KL-TFD 3DHHF28KL-TFE 3DJ3A0750-TFC 3DJ3A0750-TFD 3DJ3A0750-TFE 3DJ3A075E-TFC 3DJ3A075E-TFD 3DJ3A075E-TFE 3DJ3A075L-TFC 3DJ3A075L-TFD 3DJ3A075L-TFE 3DJ3A0900-TFU 3DJ3F33K0-TFC 3DJ3F33K0-TFD 3DJ3F33K0-TFE 3DJ3F33KE-TFC 3DJ3F33KE-TFD 3DJ3F33KE-TFE 3DJ3F33KL-TFC 3DJ3F33KL-TFD FD16 Max LRA Volts PH RLA 460 575 208/230 460 575 208/230 460 575 208/230 460 575 208/230 460 575 200 208/230 460 575 208/230 460 575 208/230 460 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 12 10.5 26.8 12 10.5 30.7 14.3 11 30.7 14.3 11 30.7 14.3 11 34.6 30.7 14.3 11 30.7 14.3 11 30.7 14.3 77 62 150 77 62 161 83 67 161 83 67 161 83 67 196 161 83 67 161 83 67 161 83 Resistance Start Cap Run Cap Start or Run or P/N P/N Line to Line Line to WYE 1.676 2.6 0.419 1.676 2.6 0.385 1.54 2.508 0.385 1.54 2.508 0.385 1.54 2.508 0.294 0.385 1.54 2.508 0.385 1.54 2.508 0.385 1.54 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Relay P/N Part Protector Type* P/N 071-0429-05 071-0429-03 071-0429-08 071-0429-05 071-0429-03 071-0429-04 071-0429-09 071-0429-03 071-0429-04 071-0429-09 071-0429-03 071-0429-04 071-0429-09 071-0429-03 071-0429-20 071-0429-04 071-0429-09 071-0429-03 071-0429-04 071-0429-09 071-0429-03 071-0429-04 071-0429-09 * See Section F Introduction for more information. Section_Fd.indd 16 3/4/2008 8:02:55 AM Electrical Data - Copelametic Small Refrigerant-Cooled Compressors Model 3DJ3F33KL-TFE 3DJHA075E-TFC 3DJHA075E-TFD 3DJHA075E-TFE 3DJHA075L-TFC 3DJHA075L-TFD 3DJHA075L-TFE 3DJHF33KE-TFC 3DJHF33KE-TFD 3DJHF33KE-TFE 3DJHF33KL-TFC 3DJHF33KL-TFD 3DJHF33KL-TFE 3DK3A0750-TFC 3DK3A0750-TFD 3DK3A0900-TFC 3DK3A0900-TFD 3DK3A0900-TFE 3DK3A1200-TFC 3DK3A1200-TFD 3DK3A120E-TFC 3DK3A120E-TFD 3DK3A120L-TFC Max LRA Volts PH RLA 575 208/230 460 575 208/230 460 575 208/230 460 575 208/230 460 575 208/230 460 208/230 460 575 208/230 460 208/230 460 208/230 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 11 30.7 15.7 11 30.7 15.7 11 30.7 15.7 11 30.7 15.7 11 30.7 15 39 16.9 16.4 48.1 23.6 48.1 23.6 48.1 67 161 83 67 161 83 67 161 83 67 161 83 67 161 83 215 106 84 275 138 275 138 275 Resistance Start Cap Run Cap Start or Run or P/N P/N Line to Line Line to WYE 2.508 0.385 1.54 2.508 0.385 1.54 2.508 0.385 1.54 2.508 0.385 1.54 2.508 0.385 1.54 0.295 1.178 1.835 0.229 0.908 0.229 0.908 0.229 * See Section F Introduction for more information. Section_Fd.indd 17 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Relay P/N Part Protector Type* P/N 071-0429-03 071-0429-04 071-0429-09 071-0429-03 071-0429-04 071-0429-09 071-0429-03 071-0429-04 071-0429-09 071-0429-03 071-0429-04 071-0429-09 071-0429-03 071-0429-04 071-0429-09 071-0429-00 071-0429-09 071-0429-11 071-0504-05 071-0504-02 071-0504-05 071-0504-02 071-0504-05 FD17 3/4/2008 8:02:56 AM Electrical Data - Copelametic Small Refrigerant-Cooled Compressors Model 3DK3A120L-TFD 3DK3R15M0-TFC 3DK3R15M0-TFD 3DK3R15ME-TFC 3DK3R15ME-TFD 3DK3R15ML-TFC 3DK3R15ML-TFD 3DK4A1200-TFD 3DK4A120L-TFC 3DK4A120L-TFD 3DK4S11M0-TFC 3DK4S11M0-TFD 3DK4S11ML-TFC 3DK4S11ML-TFD 3DK8A0750-TFC 3DK8A0750-TFD 3DK8A075E-TFD 3DKAA120L-TFC 3DKAA120L-TFD 3DKHA120E-TFC 3DKHA120E-TFD 3DKHA120L-TFC 3DKHA120L-TFD FD18 Max LRA Volts PH RLA 460 208/230 460 208/230 460 208/230 460 460 208/230 460 208/230 460 208/230 460 208/230 460 460 208/230 460 208/230 460 208/230 460 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 23.6 48.1 23.6 48.1 23.6 48.1 23.6 23.6 48.1 23.6 38.6 18.6 38.6 18.6 30.7 15 15 48.1 23.6 48.1 23.6 48.1 23.6 138 275 138 275 138 275 138 138 275 138 240 115 240 115 161 83 83 275 138 275 138 275 138 Resistance Start Cap Run Cap Start or Run or P/N P/N Line to Line Line to WYE 0.908 0.229 0.908 0.229 0.908 0.229 0.908 0.908 0.229 0.908 0.255 1.02 0.255 1.02 0.385 1.54 1.54 0.229 0.908 0.229 0.908 0.229 0.908 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Relay P/N Part Protector Type* P/N 071-0504-02 071-0504-05 071-0504-02 071-0504-05 071-0504-02 071-0504-05 071-0504-02 071-0504-02 071-0504-05 071-0504-02 071-0429-35 071-0429-33 071-0429-35 071-0429-33 071-0429-04 071-0429-09 071-0429-09 071-0504-05 071-0504-02 071-0504-05 071-0504-02 071-0504-05 071-0504-02 * See Section F Introduction for more information. Section_Fd.indd 18 3/4/2008 8:02:56 AM Electrical Data - Copelametic Small Refrigerant-Cooled Compressors Model 3DKHR15ME-TFC 3DKHR15ME-TFD 3DKHR15ML-TFC 3DKHR15ML-TFD 3DKHS11ME-TFC 3DKHS11ME-TFD 3DKHS11ML-TFC 3DKHS11ML-TFD 3DP3A0500-TFC 3DP3A0500-TFD 3DP3A0500-TFE 3DP3A0750-TFC 3DP3A0750-TFD 3DP3A0750-TFE 3DP3A075E-TFD 3DP3A0900-TFU 3DP3A1000-TFC 3DP3A1000-TFD 3DP3A1000-TFE 3DP3A100E-TFC 3DP3A100E-TFD 3DP3A100E-TFE 3DP3A100L-TFC Max LRA Volts PH RLA 208/230 460 208/230 460 208/230 460 208/230 460 208/230 460 575 208/230 460 575 460 200 208/230 460 575 208/230 460 575 208/230 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 48.1 23.6 48.1 23.6 42.6 20.4 42.6 20.4 18 10.1 7.5 31.4 16.1 11 16.1 36.8 43.6 20 16.5 43.6 20 16.5 43.6 275 138 275 138 240 115 240 115 115 58 43 161 83 67 83 196 215 106 84 215 106 84 215 Resistance Start Cap Run Cap Start or Run or P/N P/N Line to Line Line to WYE 0.229 0.908 0.229 0.908 0.255 1.02 0.255 1.02 0.603 2.412 3.794 0.385 1.54 2.508 1.54 0.294 0.295 1.178 1.835 0.295 1.178 1.835 0.295 * See Section F Introduction for more information. Section_Fd.indd 19 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Relay P/N Part Protector Type* P/N 071-0504-05 071-0504-02 071-0504-05 071-0504-02 071-0429-35 071-0429-33 071-0429-35 071-0429-33 071-0429-02 071-0429-03 071-0429-19 071-0429-04 071-0429-09 071-0429-03 071-0429-09 071-0429-20 071-0429-06 071-0429-17 071-0429-11 071-0429-06 071-0429-17 071-0429-11 071-0429-06 FD19 3/4/2008 8:02:56 AM Electrical Data - Copelametic Small Refrigerant-Cooled Compressors Model 3DP3A100L-TFD 3DP3A100L-TFE 3DP3R12M0-TFC 3DP3R12M0-TFD 3DP3R12M0-TFE 3DP3R12ME-TFC 3DP3R12ME-TFD 3DP3R12ME-TFE 3DP3R12ML-TFC 3DP3R12ML-TFD 3DP3R12ML-TFE 3DPHA100E-TFC 3DPHA100E-TFD 3DPHA100E-TFE 3DPHA100L-TFC 3DPHA100L-TFD 3DPHA100L-TFE 3DPHR12ME-TFC 3DPHR12ME-TFD 3DPHR12ME-TFE 3DPHR12ML-TFC 3DPHR12ML-TFD 3DPHR12ML-TFE FD20 Max LRA Volts PH RLA 460 575 208/230 460 575 208/230 460 575 208/230 460 575 208/230 460 575 208/230 460 575 208/230 460 575 208/230 460 575 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 20 16.5 43.6 20 16.5 43.6 20 16.5 43.6 20 16.5 43.6 20 16.5 43.6 20 16.5 43.6 20 16.5 43.6 20 16.5 106 84 215 106 84 215 106 84 215 106 84 215 106 84 215 106 84 215 106 84 215 106 84 Resistance Start Cap Run Cap Start or Run or P/N P/N Line to Line Line to WYE 1.178 1.835 0.295 1.178 1.835 0.295 1.178 1.835 0.295 1.178 1.835 0.295 1.178 1.835 0.295 1.178 1.835 0.295 1.178 1.835 0.295 1.178 1.835 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Relay P/N Part Protector Type* P/N 071-0429-17 071-0429-11 071-0429-06 071-0429-17 071-0429-11 071-0429-06 071-0429-17 071-0429-11 071-0429-06 071-0429-17 071-0429-11 071-0429-06 071-0429-17 071-0429-11 071-0429-06 071-0429-17 071-0429-11 071-0429-06 071-0429-17 071-0429-11 071-0429-06 071-0429-17 071-0429-11 * See Section F Introduction for more information. Section_Fd.indd 20 3/4/2008 8:02:56 AM Electrical Data - Copelametic Small Refrigerant-Cooled Compressors Model 3DR3A1000-TFC 3DR3A1000-TFD 3DR3A1000-TFE 3DR3A100E-TFC 3DR3A100E-TFD 3DR3A100E-TFE 3DR3A100L-TFC 3DR3A100L-TFD 3DR3A100L-TFE 3DR3F46K0-TFC 3DR3F46K0-TFD 3DR3F46K0-TFE 3DR3F46KE-TFC 3DR3F46KE-TFD 3DR3F46KL-TFC 3DR3F46KL-TFD 3DR3F46KL-TFE 3DRHA100E-TFC 3DRHA100E-TFD 3DRHA100E-TFE 3DRHA100L-TFC 3DRHA100L-TFD 3DRHA100L-TFE Max LRA Volts PH RLA 208/230 460 575 208/230 460 575 208/230 460 575 208/230 460 575 208/230 460 208/230 460 575 208/230 460 575 208/230 460 575 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 41.4 18.6 15.4 41.4 18.6 15.4 41.4 18.6 15.4 41.4 18.6 15.4 41.4 18.6 41.4 18.6 15.4 41.4 18.6 16.2 41.4 18.6 16.2 215 106 84 215 106 84 215 106 84 215 106 84 215 106 215 106 84 215 106 84 215 106 84 Resistance Start Cap Run Cap Start or Run or P/N P/N Line to Line Line to WYE 0.295 1.178 1.835 0.295 1.178 1.835 0.295 1.178 1.835 0.295 1.178 1.835 0.295 1.178 0.295 1.178 1.835 0.295 1.178 1.835 0.295 1.178 1.835 * See Section F Introduction for more information. Section_Fd.indd 21 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Relay P/N Part Protector Type* P/N 071-0429-00 071-0429-09 071-0429-11 071-0429-00 071-0429-09 071-0429-11 071-0429-00 071-0429-09 071-0429-11 071-0429-00 071-0429-09 071-0429-11 071-0429-00 071-0429-09 071-0429-00 071-0429-09 071-0429-11 071-0429-00 071-0429-09 071-0429-11 071-0429-00 071-0429-09 071-0429-11 FD21 3/4/2008 8:02:57 AM Electrical Data - Copelametic Small Refrigerant-Cooled Compressors Model 3DRHF46KE-TFC 3DRHF46KE-TFD 3DRHF46KE-TFE 3DRHF46KL-TFC 3DRHF46KL-TFD 3DRHF46KL-TFE 3DS3A0750-TFC 3DS3A0750-TFD 3DS3A0750-TFE 3DS3A1000-TFC 3DS3A1000-TFD 3DS3A1000-TFE 3DS3A100E-TFC 3DS3A100E-TFD 3DS3A100E-TFE 3DS3A100L-TFC 3DS3A100L-TFD 3DS3A100L-TFE 3DS3A1500-TFC 3DS3A1500-TFD 3DS3A1500-TFE 3DS3A150E-TFC 3DS3A150E-TFD FD22 Max LRA Volts PH RLA 208/230 460 575 208/230 460 575 208/230 460 575 208/230 460 575 208/230 460 575 208/230 460 575 208/230 460 575 208/230 460 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 41.4 18.6 16.2 41.4 18.6 16.2 32 16.4 11.5 42 18.6 16.8 42 18.6 16.8 42 18.6 16.8 59.6 29 23.6 59.6 29 215 106 84 215 106 84 161 83 67 215 106 84 215 106 84 215 106 84 275 138 110 275 138 Resistance Start Cap Run Cap Start or Run or P/N P/N Line to Line Line to WYE 0.295 1.178 1.835 0.295 1.178 1.835 0.385 1.54 2.508 0.295 1.178 1.835 0.295 1.178 1.835 0.295 1.178 1.835 0.229 0.908 1.433 0.229 0.908 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Relay P/N Part Protector Type* P/N 071-0429-00 071-0429-09 071-0429-11 071-0429-00 071-0429-09 071-0429-11 071-0429-04 071-0429-09 071-0429-03 071-0429-00 071-0429-09 071-0429-11 071-0429-00 071-0429-09 071-0429-11 071-0429-00 071-0429-09 071-0429-11 071-0504-04 071-0504-00 071-0504-01 071-0504-04 071-0504-00 * See Section F Introduction for more information. Section_Fd.indd 22 3/4/2008 8:02:57 AM Electrical Data - Copelametic Small Refrigerant-Cooled Compressors Model 3DS3A150E-TFE 3DS3A150L-TFC 3DS3A150L-TFD 3DS3A150L-TFE 3DS3F30K0-TFC 3DS3F30K0-TFD 3DS3F46K0-TFC 3DS3F46K0-TFD 3DS3F46K0-TFE 3DS3F46KE-TFC 3DS3F46KE-TFD 3DS3F46KE-TFE 3DS3F46KL-TFC 3DS3F46KL-TFD 3DS3F46KL-TFE 3DS3R17M0-TFC 3DS3R17M0-TFD 3DS3R17M0-TFE 3DS3R17ME-TFC 3DS3R17ME-TFD 3DS3R17ME-TFE 3DS3R17ML-TFC 3DS3R17ML-TFD Max LRA Volts PH RLA 575 208/230 460 575 208/230 460 208/230 460 575 208/230 460 575 208/230 460 575 208/230 460 575 208/230 460 575 208/230 460 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 23.6 59.6 29 23.6 32 16.4 42 18.6 16.8 42 18.6 16.8 42 18.6 16.8 59.6 29 23.6 59.6 29 23.6 59.6 29 110 275 138 110 161 83 215 106 84 215 106 84 215 106 84 275 138 110 275 138 110 275 138 Resistance Start Cap Run Cap Start or Run or P/N P/N Line to Line Line to WYE 1.433 0.229 0.908 1.433 0.385 1.54 0.295 1.178 1.835 0.295 1.178 1.835 0.295 1.178 1.835 0.229 0.908 1.433 0.229 0.908 1.433 0.229 0.908 * See Section F Introduction for more information. Section_Fd.indd 23 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Relay P/N Part Protector Type* P/N 071-0504-01 071-0504-04 071-0504-00 071-0504-01 071-0429-04 071-0429-09 071-0429-00 071-0429-09 071-0429-11 071-0429-00 071-0429-09 071-0429-11 071-0429-00 071-0429-09 071-0429-11 071-0504-04 071-0504-00 071-0504-01 071-0504-04 071-0504-00 071-0504-01 071-0504-04 071-0504-00 FD23 3/4/2008 8:02:57 AM Electrical Data - Copelametic Small Refrigerant-Cooled Compressors Model 3DS3R17ML-TFE 3DS4A0750-TFC 3DS4A0750-TFD 3DS4A1000-TFC 3DS4A1000-TFD 3DS4A1500-TFC 3DS4A1500-TFD 3DS4A1500-TFE 3DS4S12M0-TFC 3DS4S12M0-TFD 3DS4S12ME-TFC 3DS4S12ME-TFD 3DS4S12ML-TFC 3DS4S12ML-TFD 3DS8A0750-TFD 3DS8A0751-TFD 3DS8A076E-TFD 3DS8A1000-TFC 3DS8A100E-TFC 3DS8F30K1-TFD 3DS8R11ME-TFD 3DSTA075E-TFC 3DSTA075E-TFD FD24 Max LRA Volts PH RLA 575 208/230 460 208/230 460 208/230 460 575 208/230 460 208/230 460 208/230 460 460 460 460 208/230 208/230 460 460 208/230 460 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 23.6 32 16.4 42 18.6 59.6 29 23.6 41.9 21.3 47.1 22.8 47.1 22.8 16.4 16.4 16.4 42 42 16.4 16.4 32 16.4 110 161 83 215 106 275 138 110 280 136 280 136 280 136 83 83 83 215 215 83 83 161 83 Resistance Start Cap Run Cap Start or Run or P/N P/N Line to Line Line to WYE 1.433 0.385 1.54 0.295 1.178 0.229 0.908 1.433 0.22 0.823 0.22 0.823 0.22 0.823 1.54 1.54 1.54 0.295 0.295 1.54 1.54 0.385 1.54 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Relay P/N Part Protector Type* P/N 071-0504-01 071-0429-04 071-0429-09 071-0429-00 071-0429-09 071-0504-04 071-0504-00 071-0504-01 071-0504-08 071-0429-34 071-0504-08 071-0429-34 071-0504-08 071-0429-34 071-0429-09 071-0429-09 071-0429-09 071-0429-00 071-0429-00 071-0429-09 071-0429-09 071-0429-04 071-0429-09 * See Section F Introduction for more information. Section_Fd.indd 24 3/4/2008 8:02:57 AM Electrical Data - Copelametic Small Refrigerant-Cooled Compressors Model 3DSTR11ME-TFD 3DT3A0750-TFC 3DT3A0750-TFD 3DT3A0750-TFE 3DT3A1000-TFC 3DT3A1000-TFD 3DT3A1000-TFE 3DT3A1500-TFC 3DT3A1500-TFD 3DT3A1500-TFE 3DT3A150E-TFC 3DT3A150E-TFD 3DT3A150E-TFE 3DT3A150L-TFC 3DT3A150L-TFD 3DT3A150L-TFE 3DT3R11M0-TFC 3DT3R11M0-TFD 3DT3R11M0-TFE 3DT3R17M0-TFC 3DT3R17M0-TFD 3DT3R17M0-TFE 3DT3R17ME-TFC Max LRA Volts PH RLA 460 208/230 460 575 208/230 460 575 208/230 460 575 208/230 460 575 208/230 460 575 208/230 460 575 208/230 460 575 208/230 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 16.4 32 16.4 11.5 42 18.6 16.8 59.6 29 23.6 59.6 29 23.6 59.6 29 23.6 42 18.6 16.8 59.6 29 23.6 59.6 83 161 83 67 215 106 84 275 138 110 275 138 110 275 138 110 215 106 84 275 138 110 275 Resistance Start Cap Run Cap Start or Run or P/N P/N Line to Line Line to WYE 1.54 0.385 1.54 2.508 0.295 1.178 1.835 0.229 0.908 1.433 0.229 0.908 1.433 0.229 0.908 1.433 0.295 1.178 1.835 0.229 0.908 1.433 0.229 * See Section F Introduction for more information. Section_Fd.indd 25 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Relay P/N Part Protector Type* P/N 071-0429-09 071-0429-04 071-0429-09 071-0429-03 071-0429-00 071-0429-09 071-0429-11 071-0504-04 071-0504-00 071-0504-01 071-0504-04 071-0504-00 071-0504-01 071-0504-04 071-0504-00 071-0504-01 071-0429-00 071-0429-09 071-0429-11 071-0504-04 071-0504-00 071-0504-01 071-0504-04 FD25 3/4/2008 8:02:58 AM Electrical Data - Copelametic Small Refrigerant-Cooled Compressors Model 3DT3R17ME-TFD 3DT3R17ME-TFE 3DT3R17ML-TFC 3DT3R17ML-TFD 3DT3R17ML-TFE 3DT4S12M0-TFC 3DT4S12M0-TFD 3DT4S12ML-TFC 3DT4S12ML-TFD 3DT8A0750-TFD 3DT8A075E-TFD 3DT8R11ME-TFD 3DTHA100E-TFD 3DTHA150E-TFC 3DTHA150E-TFD 3DTHA150E-TFE 3DTHA150L-TFC 3DTHA150L-TFD 3DTHA150L-TFE 3DTHR11ME-TFD 3DTHR17ME-TFC 3DTHR17ME-TFD 3DTHR17ME-TFE FD26 Max LRA Volts PH RLA 460 575 208/230 460 575 208/230 460 208/230 460 460 460 460 460 208/230 460 575 208/230 460 575 460 208/230 460 575 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 29 23.6 59.6 29 23.6 41.9 21.3 41.9 21.3 16.4 16.4 16.4 18.6 59.6 29 23.6 59.6 29 23.6 18.6 59.6 29 23.6 138 110 275 138 110 280 136 280 136 83 83 83 106 275 138 110 275 138 110 106 275 138 110 Resistance Start Cap Run Cap Start or Run or P/N P/N Line to Line Line to WYE 0.908 1.433 0.229 0.908 1.433 0.22 0.823 0.22 0.823 1.54 1.54 1.54 1.178 0.229 0.908 1.433 0.229 0.908 1.433 1.178 0.229 0.908 1.433 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Relay P/N Part Protector Type* P/N 071-0504-00 071-0504-01 071-0504-04 071-0504-00 071-0504-01 071-0504-08 071-0429-34 071-0504-08 071-0429-34 071-0429-09 071-0429-09 071-0429-09 071-0429-09 071-0504-04 071-0504-00 071-0504-01 071-0504-04 071-0504-00 071-0504-01 071-0429-09 071-0504-04 071-0504-00 071-0504-01 * See Section F Introduction for more information. Section_Fd.indd 26 3/4/2008 8:02:58 AM Electrical Data - Copelametic Small Refrigerant-Cooled Compressors Model 3DTHR17ML-TFC 3DTHR17ML-TFD 3DTHR17ML-TFE 3DTHS12ME-TFC 3DTHS12ME-TFD 3DTHS12ML-TFC 3DTHS12ML-TFD 3RA1-0310-TAC 3RA1-0310-TAD 3RA1-0310-TAU 3RA1-0311-TAC 3RA1-0311-TAD 3RA1-031A-TAC 3RA1-031A-TAD 3RA1-031L-TAC 3RA1-031L-TAD 3RA2-0310-CAB 3RA2-031A-CAB 3RA2-031L-CAB 3RAA-0310-TAU 3RAA-031E-TAC 3RAA-031E-TAD 3RAA-031L-TAC Max LRA Volts PH RLA 208/230 460 575 208/230 460 208/230 460 208/230 460 200 208/230 460 208/230 460 208/230 460 230 230 230 200 208/230 460 208/230 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 1 1 1 3 3 3 3 59.6 29 23.6 47.1 22.8 47.1 22.8 NA NA 11.4 14.1 6.3 14.1 6.3 13.1 6.6 NA NA 17.8 13.1 14.1 6.3 14.1 275 138 110 280 136 280 136 82 41 82 82 41 82 41 82 41 86 86 86 82 82 41 82 Resistance Start Cap Run Cap Start or Run or P/N P/N Line to Line Line to WYE 0.229 0.908 1.433 0.22 0.823 0.22 0.823 0.9 3.6 0.944 0.837 3.309 0.837 3.309 0.9 3.6 2.54 2.54 2.54 0.9 0.837 3.309 0.837 * See Section F Introduction for more information. Section_Fd.indd 27 0 0 0 0 0 0 0 0.47 1.9 0.444 0.42 1.653 0.42 1.653 0.47 1.9 0.61 0.61 0.61 0.47 0.42 1.653 0.42 Relay P/N 014-0036-22 014-0064-14 040-0166-28 014-0036-22 014-0064-14 040-0166-28 014-0036-22 014-0064-14 040-0166-28 Part Protector Type* P/N RP RP RP 071-0504-04 071-0504-00 071-0504-01 071-0504-08 071-0429-34 071-0504-08 071-0429-34 071-0090-17 071-0090-22 071-0090-32 071-0090-32 071-0090-22 071-0090-32 071-0090-22 071-0090-17 071-0090-22 071-0119-02 071-0119-02 071-0119-02 071-0090-17 071-0090-32 071-0090-22 071-0090-32 FD27 3/4/2008 8:02:58 AM Electrical Data - Copelametic Small Refrigerant-Cooled Compressors Model 3RAA-031L-TAD 3RK1-0300-TAE 3RK1-0310-TAC 3RK1-0310-TAD 3RK1-031A-TAC 3RK1-031A-TAD 3RK2-0310-CAB 3RK2-031A-CAB 3RKA-031E-FXX 9RA1-0505-TFC 9RA1-0505-TFD 9RA1-0505-TFE 9RA1-0506-CFB 9RA1-050A-CFB 9RA1-050A-TFC 9RA1-050A-TFD 9RB1-0505-TFC 9RB1-0505-TFD 9RB1-0505-TFE 9RB1-050A-TFC 9RB1-050A-TFD 9RB1-0765-TFC 9RB1-0765-TFD FD28 Max LRA Volts PH RLA 460 575 208/230 460 208/230 460 230 230 55 208/230 460 575 230 230 208/230 460 208/230 460 575 208/230 460 208/230 460 3 3 3 3 3 3 1 1 3 3 3 3 1 1 3 3 3 3 3 3 3 3 3 6.3 5.1 11.8 5.2 11.8 5.2 19.6 19.6 NA 16.7 8.6 7.8 26.9 26.9 16.7 8.6 15.9 7.9 7.8 15.9 7.9 32.1 15.4 41 30 82 41 82 41 86 86 320 115 53 42 125 125 115 53 115 53 42 115 53 164 82 Resistance Start Cap Run Cap Start or Run or P/N P/N Line to Line Line to WYE 3.309 5.4 0.9 3.6 0.9 3.6 2.54 2.54 0.17 0.519 2.08 3.17 1.4 1.4 0.519 2.08 0.519 2.08 3.17 0.519 2.08 0.338 1.351 1.653 2.7 0.47 1.9 0.47 1.9 0.61 0.61 0 0.26 1.015 1.585 0.37 0.37 0.26 1.015 0.26 1.015 1.585 0.26 1.015 0.169 0.675 Relay P/N 014-0036-22 014-0064-14 040-0166-28 014-0036-22 014-0064-14 040-0166-28 014-0006-14 014-0064-18 040-0166-23 014-0006-14 014-0064-18 040-0166-23 Part Protector Type* P/N RP RP RP RP 071-0090-22 071-0090-16 071-0090-02 071-0090-03 071-0090-02 071-0090-03 071-0119-00 071-0119-00 071-0086-09 071-0086-17 071-0086-29 071-0476-01 071-0476-01 071-0086-09 071-0086-17 071-0086-09 071-0086-17 071-0086-29 071-0086-09 071-0086-17 071-0086-22 071-0086-20 * See Section F Introduction for more information. Section_Fd.indd 28 3/4/2008 8:02:59 AM Electrical Data - Copelametic Small Refrigerant-Cooled Compressors Model 9RB1-0765-TFE 9RB1-0765-TFU 9RB1-076A-TFC 9RB1-076A-TFD 9RB1-076L-TFC 9RB1-076L-TFD 9RB2-0765-TFC 9RB2-0765-TFD 9RB2-0765-TFE 9RB2-076A-TFC 9RB4-0505-TFC 9RB4-0505-TFD 9RB6-0505-TFC 9RC1-0765-TFC 9RC1-0765-TFD 9RC1-0765-TFE 9RC1-0765-TFU 9RC1-076A-TFC 9RC1-076A-TFD 9RC1-1015-TF7 9RC1-1015-TFC 9RC1-1015-TFD 9RC1-1015-TFE Max LRA Volts PH RLA 575 200 208/230 460 208/230 460 208/230 460 575 208/230 208/230 460 208/230 208/230 460 575 200 208/230 460 380 208/230 460 575 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 14 NA 32.1 15.4 32.1 15.4 32.1 15.4 14 32.1 15.9 7.9 15.9 32.9 15.8 14 NA 32.9 15.8 NA 44 20 17.5 63.8 141 164 82 164 82 164 82 63.8 164 115 53 115 164 82 63.8 141 164 82 110 208 110 88.2 Resistance Start Cap Run Cap Start or Run or P/N P/N Line to Line Line to WYE 2.16 0.3 0.338 1.351 0.338 1.351 0.338 1.351 2.16 0.338 0.519 2.08 0.519 0.338 1.351 2.16 0.3 0.338 1.351 0.878 0.219 0.878 1.48 * See Section F Introduction for more information. Section_Fd.indd 29 1.08 0.151 0.169 0.675 0.169 0.675 0.169 0.675 1.08 0.169 0.26 1.015 0.26 0.169 0.675 1.08 0.151 0.169 0.675 0 0 0 0 Relay P/N Part Protector Type* P/N 071-0086-40 071-0086-43 071-0086-22 071-0086-20 071-0086-22 071-0086-20 071-0086-22 071-0086-20 071-0086-40 071-0086-22 071-0086-09 071-0086-17 071-0086-09 071-0086-22 071-0086-20 071-0086-40 071-0086-43 071-0086-22 071-0086-20 071-0429-17 071-0504-06 071-0429-17 071-0429-11 FD29 3/4/2008 8:02:59 AM Electrical Data - Copelametic Small Refrigerant-Cooled Compressors Model 9RC1-101A-TFC 9RC1-101A-TFD 9RC3-1015-TFD 9RC3-1015-TFE 9RC3-101L-TFD 9RJ1-0505-TFC 9RJ1-0505-TFD 9RJ1-0505-TFE 9RJ1-050A-TFC 9RJ1-0765-TFC 9RJ1-0765-TFD 9RJ1-0765-TFE 9RJ1-076A-TFC 9RJ1-076A-TFD 9RJ1-076L-TFC 9RJ1-076L-TFD 9RJ2-0765-TFC 9RJ2-0765-TFE 9RP2-0765-TFC 9RP2-0765-TFD 9RP2-0765-TFE 9RP2-1015-TFC 9RP2-1015-TFD FD30 Max LRA Volts PH RLA 208/230 460 460 575 460 208/230 460 575 208/230 208/230 460 575 208/230 460 208/230 460 208/230 575 208/230 460 575 208/230 460 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 44 20 20 17.5 20 15.9 7.9 7.8 15.9 31.7 14.7 10.7 31.7 14.7 31.7 14.7 31.7 10.7 32.9 14.1 14 44 20 208 110 110 88.2 110 115 53 42 115 164 82 63.8 164 82 164 82 164 63.8 164 82 63.8 208 110 Resistance Start Cap Run Cap Start or Run or P/N P/N Line to Line Line to WYE 0.219 0.878 0.878 1.48 0.878 0.519 2.08 3.17 0.519 0.338 1.351 2.16 0.338 1.351 0.338 1.351 0.338 2.16 0.338 1.351 2.16 0.219 0.878 0 0 0 0 0 0.26 1.015 1.585 0.26 0.169 0.675 1.08 0.169 0.675 0.169 0.675 0.169 1.08 0.169 0.675 1.08 0 0 Relay P/N Part Protector Type* P/N 071-0504-06 071-0429-17 071-0429-17 071-0429-11 071-0429-17 071-0086-09 071-0086-17 071-0086-29 071-0086-09 071-0086-21 071-0086-20 071-0086-40 071-0086-21 071-0086-20 071-0086-21 071-0086-20 071-0086-21 071-0086-40 071-0086-22 071-0086-20 071-0086-40 071-0504-06 071-0429-17 * See Section F Introduction for more information. Section_Fd.indd 30 3/4/2008 8:02:59 AM Electrical Data - Copelametic Small Refrigerant-Cooled Compressors Model 9RP2-1015-TFE 9RP2-101A-TFC 9RP3-1015-TFD 9RP3-1015-TFE 9RS1-1015-TSU 9RS1-1505-TF7 9RS1-1505-TFD 9RS1-1505-TFE 9RS1-1505-TSC 9RS1-150A-TFD 9RS1-150A-TSC 9RS2-0765-TFC 9RS2-0765-TFD 9RS2-0765-TFE 9RS2-076A-TFC 9RS2-076A-TFD 9RS2-1015-TFD 9RS3-0765-TFC 9RS3-0765-TFD 9RS3-0765-TFE 9RS3-076A-TFC 9RS3-076A-TFD 9RS3-1015-TFC Max LRA Volts PH RLA 575 208/230 460 575 200 380 460 575 208/230 460 208/230 208/230 460 575 208/230 460 460 208/230 460 575 208/230 460 208/230 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 17.5 44 20 17.5 NA NA 28.5 22.5 56.4 28.5 56.4 29.4 16.5 14 29.4 16.5 19 29.4 16.5 14 29.4 16.5 41 88.2 208 110 88.2 203 144 144 127 284 144 284 164 82 63.8 164 82 110 164 82 63.8 164 82 208 Resistance Start Cap Run Cap Start or Run or P/N P/N Line to Line Line to WYE 1.48 0.219 0.878 1.48 0.204 0.908 0.908 1.036 0.229 0.908 0.229 0.338 1.351 2.16 0.338 1.351 0.878 0.338 1.351 2.16 0.338 1.351 0.219 * See Section F Introduction for more information. Section_Fd.indd 31 0 0 0 0 0 0 0 0 0 0 0 0.169 0.675 1.08 0.169 0.675 0 0.169 0.675 1.08 0.169 0.675 0 Relay P/N Part Protector Type* P/N 071-0429-11 071-0504-06 071-0429-17 071-0429-11 071-0581-02 071-0504-00 071-0504-00 071-0504-01 071-0581-02 071-0504-00 071-0581-02 071-0086-23 071-0086-20 071-0086-26 071-0086-23 071-0086-20 071-0429-17 071-0086-23 071-0086-20 071-0086-26 071-0086-23 071-0086-20 071-0504-06 FD31 3/4/2008 8:02:59 AM Electrical Data - Copelametic Small Refrigerant-Cooled Compressors Model 9RS3-1015-TFD 9RS3-1015-TFE 9RS3-1015-TSU 9RS5-0765-TFC 9RS7-0765-TFC 9RS7-0765-TFD 9RSB-076A-TFC 9RSC-0765-TFC 9RSC-0765-TFD 9RSD-0765-TFC 9RSD-0765-TFD 9RT1-1505-TFD 9RT1-1505-TFE 9RT1-1505-TSC 9RT1-150A-TFD 9RZ1-0765-TFU 9TH1-1015-TFC 9TH1-1015-TFD 9TH1-101A-TFC 9TH1-101A-TFD 9TH2-101E-TFC 9TH2-101E-TFD 9TK1-0505-TFC FD32 Max LRA Volts PH RLA 460 575 200 208/230 208/230 460 208/230 208/230 460 208/230 460 460 575 208/230 460 200 208/230 460 208/230 460 208/230 460 208/230 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 19 110 15.5 88.2 NA 203 29.4 164 29.4 164 16.5 82 29.4 164 29.4 164 16.5 82 29.4 164 16.5 82 28.5 144 22.5 127 56.4 284 28.5 144 NA 141 37.4 208 17.5 110 37.4 208 17.5 110 40.7 220 17.9 110 19.6 115 Resistance Start Cap Run Cap Start or Run or P/N P/N Line to Line Line to WYE 0.878 1.48 0.204 0.338 0.338 1.351 0.338 0.338 1.351 0.338 1.351 0.908 1.036 0.229 0.908 0.3 0.219 0.878 0.219 0.878 0.219 0.878 0.519 0 0 0 0.169 0.169 0.675 0.169 0.169 0.675 0.169 0.675 0 0 0 0 0.151 0 0 0 0 0 0 0.26 Relay P/N Part Protector Type* P/N 071-0429-17 071-0429-11 071-0581-02 071-0086-23 071-0086-23 071-0086-20 071-0086-23 071-0086-23 071-0086-20 071-0086-23 071-0086-20 071-0504-00 071-0504-01 071-0581-02 071-0504-00 071-0086-43 071-0504-06 071-0429-17 071-0504-06 071-0429-17 071-0504-06 071-0429-17 071-0086-38 * See Section F Introduction for more information. Section_Fd.indd 32 3/4/2008 8:03:00 AM Electrical Data - Copelametic Small Refrigerant-Cooled Compressors Model 9TK1-0505-TFD 9TK1-0505-TFE 9TK1-050A-TFC 9TK1-050A-TFD 9TK2-050E-TFC 9TK2-050E-TFD 9TL1-0765-TFC 9TL1-0765-TFE 9TL1-076A-TFC 9TL1-076A-TFD 9TL2-076E-TFC 9TL2-076E-TFD ERA1-0200-TAC ERA1-0200-TAD ERA1-0200-TAE ERA1-020A-TAD ERA2-0200-CAB ERA2-020A-CAB ERC1-0200-TAC ERC1-0200-TAD ERC1-0200-TAE ERC1-020L-TAC ERC1-020L-TAD Max LRA Volts PH RLA 460 575 208/230 460 208/230 460 208/230 575 208/230 460 208/230 460 208/230 460 575 460 230 230 208/230 460 575 208/230 460 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 1 1 3 3 3 3 3 8.3 53 7.8 42 19.6 115 8.3 53 20.3 115 8.3 53 30 164 9.7 63.8 30 164 14.5 82 28.9 164 13.1 82 6.6 46 3.5 23 3.5 20 3.5 23 10.4 58 10.4 58 6.8 46 3.6 23 NA 20 6.8 46 3.6 23 Resistance Start Cap Run Cap Start or Run or P/N P/N Line to Line Line to WYE 2.08 3.17 0.519 2.08 0.519 2.08 0.338 2.16 0.338 1.351 0.338 1.351 1.675 6.692 9.3 6.692 2.7 2.7 1.675 6.692 9.3 1.675 6.692 * See Section F Introduction for more information. Section_Fd.indd 33 1.015 1.585 0.26 1.015 0.26 1.015 0.169 1.08 0.169 0.675 0.169 0.675 0.84 3.346 4.905 3.346 1.125 1.125 0.84 3.346 4.905 0.84 3.346 Relay P/N 014-0036-22 014-0064-11 040-0166-20 014-0036-22 014-0064-11 040-0166-20 Part Protector Type* P/N RP RP 071-0086-17 071-0086-29 071-0086-38 071-0086-17 071-0086-38 071-0429-31 071-0086-22 071-0086-40 071-0086-22 071-0086-20 071-0086-22 071-0086-20 071-0090-00 071-0090-08 071-0090-15 071-0090-08 071-0103-02 071-0103-02 071-0090-00 071-0090-08 071-0090-15 071-0090-00 071-0090-08 FD33 3/4/2008 8:03:00 AM Electrical Data - Copelametic Small Refrigerant-Cooled Compressors Model ERC2-0200-CAB ERC2-020A-CAB ERC2-020L-CAB ERCA-020A-TAC ERCA-020E-TAD ERCA-020E-TAE ERCA-020L-TAD ERCA-020L-TAE ERCA-021E-TAC ERCA-021L-TAC ERF1-0300-TAE ERF1-0310-FXX ERF1-0310-TAC ERF1-0310-TAD ERF1-0311-TAC ERF1-0311-TAD ERF1-031L-TAC ERF1-031L-TAD ERF2-0310-CAB ERF2-031L-CAB ERFA-0311-TAD ERFA-031E-TAC ERFA-031E-TAD FD34 Max LRA Volts PH RLA 230 230 230 208/230 460 575 460 575 208/230 208/230 575 55 208/230 460 208/230 460 208/230 460 230 230 460 208/230 460 1 1 1 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 1 1 3 3 3 10.9 10.9 10.9 6.8 3.5 3.1 3.5 3.1 8.8 8.8 5.2 NA 11.7 6.4 12.4 5.8 11.7 6.4 18.3 18.3 5.8 12.4 5.8 58 58 58 46 23 20 23 20 46 46 30 320 82 41 82 41 82 41 86 86 41 82 41 Resistance Start Cap Run Cap Start or Run or P/N P/N Line to Line Line to WYE 2.7 2.7 2.7 1.675 6.692 9.3 6.692 9.3 1.675 1.675 5.4 0.17 0.9 3.6 0.837 3.309 0.9 3.6 2.54 2.54 3.309 0.837 3.309 1.125 1.125 1.125 0.84 3.346 4.905 3.346 4.905 0.84 0.84 2.7 0 0.47 1.9 0.42 1.653 0.47 1.9 0.61 0.61 1.653 0.42 1.653 Relay P/N 014-0036-22 014-0064-11 040-0166-20 014-0036-22 014-0064-11 040-0166-20 014-0036-22 014-0064-11 040-0166-20 014-0036-22 014-0064-14 040-0166-28 014-0036-22 014-0064-14 040-0166-28 Part Protector Type* P/N RP RP RP RP RP 071-0099-01 071-0099-01 071-0099-01 071-0090-00 071-0090-08 071-0090-15 071-0090-08 071-0090-15 071-0090-49 071-0090-49 071-0090-16 071-0090-02 071-0090-10 071-0090-36 071-0090-10 071-0090-02 071-0090-10 071-0119-00 071-0119-00 071-0090-10 071-0090-36 071-0090-10 * See Section F Introduction for more information. Section_Fd.indd 34 3/4/2008 8:03:00 AM Electrical Data - Copelametic Small Refrigerant-Cooled Compressors Model ERFA-031E-TAE ERFA-031L-TAC ERFA-031L-TAD ERFB-031E-CAB ERFB-031L-CAB ERJ1-0200-TAC ERJ1-0200-TAD ERJ1-0200-TAE ERJ1-020A-TAC ERJ1-020A-TAD ERJ2-0200-CAB ERJ2-0200-CAH ERJ2-020A-CAB MRA2-0500-TFC MRA2-0500-TFD MRA2-0500-TFE MRA2-0500-TFU MRA2-0506-CFB MRA2-050A-CFB MRA2-050A-TFC MRA2-050A-TFD MRA2-050L-TFC MRA2-050L-TFD Max LRA Volts PH RLA 575 208/230 460 230 230 208/230 460 575 208/230 460 230 208 230 208/230 460 575 200 230 230 208/230 460 208/230 460 3 3 3 1 1 3 3 3 3 3 1 1 1 3 3 3 3 1 1 3 3 3 3 5.2 30 12.4 82 5.8 41 17 86 17 86 6.3 46 3.4 23 3.5 20 6.3 46 3.4 23 10.1 58 13.4 57.2 10.1 58 NA 115 NA 53 NA 42 NA 110 NA 125 27.5 125 22 115 8.6 53 22 115 8.6 53 Resistance Start Cap Run Cap Start or Run or P/N P/N Line to Line Line to WYE 5.4 0.837 3.309 2.41 2.41 1.675 6.692 9.3 1.675 6.692 2.7 2.836 2.7 0.519 2.08 3.17 0.415 1.4 1.4 0.519 2.08 0.519 2.08 * See Section F Introduction for more information. Section_Fd.indd 35 2.7 0.42 1.653 0.595 0.595 0.84 3.346 4.905 0.84 3.346 1.125 0.74 1.125 0.26 1.015 1.585 0.207 0.37 0.37 0.26 1.015 0.26 1.015 Relay P/N Part Protector Type* P/N 014-0036-22 014-0064-14 040-0166-28 014-0036-22 014-0064-14 040-0166-28 RP RP 014-0036-22 014-0064-11 040-0166-20 014-0036-22 014-0064-11 040-0166-20 014-0036-22 014-0064-11 040-0166-20 RP RP RP 014-0006-14 014-0064-18 040-0166-23 014-0006-14 014-0064-18 040-0166-23 RP RP 071-0090-16 071-0090-36 071-0090-10 071-0119-00 071-0119-00 071-0090-00 071-0090-08 071-0090-15 071-0090-00 071-0090-08 071-0103-02 071-0099-02 071-0103-02 071-0086-38 071-0086-17 071-0086-29 071-0086-42 071-0476-01 071-0476-01 071-0086-38 071-0086-17 071-0086-38 071-0086-17 FD35 3/4/2008 8:03:00 AM Electrical Data - Copelametic Small Refrigerant-Cooled Compressors Model MRA8-0500-TFC MRA8-0500-TFD MRB1-0500-TFC MRB1-0500-TFD MRB1-0500-TFE MRB1-050A-TFC MRB1-050A-TFD MRC1-0500-TFC MRC1-0500-TFD MRC8-0500-TFC MRC8-0500-TFD MRF2-0500-TFC MRF2-0500-TFD MRF2-0500-TFE MRF2-0506-CFB MRF2-050A-CFB MRF2-050A-TFC MRF2-050A-TFD MRF8-0500-TFC MRH4-0760-FSC MRH4-0760-TF7 MRH4-0760-TFC MRH4-0760-TFD FD36 Max LRA Volts PH RLA 208/230 460 208/230 460 575 208/230 460 208/230 460 208/230 460 208/230 460 575 230 230 208/230 460 208/230 230 380 208/230 460 3 3 3 3 3 3 3 3 3 3 3 3 3 3 1 1 3 3 3 3 3 3 3 NA NA 21.2 12.1 NA 21.2 12.1 18.4 9.2 18.4 9.2 21 8.6 7.8 25.2 25.2 21 8.6 21 NA NA NA NA 115 53 115 53 42 115 53 115 53 115 53 115 53 42 125 125 115 53 115 130 82 164 82 Resistance Start Cap Run Cap Start or Run or P/N P/N Line to Line Line to WYE 0.519 2.08 0.519 2.08 3.17 0.519 2.08 0.519 2.08 0.519 2.08 0.519 2.08 3.17 1.4 1.4 0.519 2.08 0.519 0.82 1.208 0.338 1.351 0.26 1.015 0.26 1.015 1.585 0.26 1.015 0.26 1.015 0.26 1.015 0.26 1.015 1.585 0.37 0.37 0.26 1.015 0.26 0.41 0.604 0.169 0.675 Relay P/N 014-0006-14 014-0064-18 040-0166-23 014-0006-14 014-0064-18 040-0166-23 Part Protector Type* P/N RP RP 071-0086-38 071-0086-17 071-0086-38 071-0086-35 071-0086-36 071-0086-38 071-0086-35 071-0086-38 071-0086-35 071-0086-38 071-0086-35 071-0086-38 071-0086-17 071-0086-29 071-0476-01 071-0476-01 071-0086-38 071-0086-17 071-0086-38 071-0581-02 071-0086-20 071-0086-21 071-0086-20 * See Section F Introduction for more information. Section_Fd.indd 36 3/4/2008 8:03:01 AM Electrical Data - Copelametic Small Refrigerant-Cooled Compressors Model MRH4-0760-TFE MRH4-076A-TFC MRH4-076A-TFD MRH4-076L-TFC MRH4-076L-TFD MRJ1-0500-TFU NRA2-0310-TFU NRA2-0500-TF7 NRA2-0500-TFC NRA2-0500-TFD NRA2-0500-TFE NRA2-050A-TFC NRA2-050A-TFD NRA3-0500-TFC NRA3-0500-TFD NRA3-050L-TFC NRA3-050L-TFD NRB2-0310-TFC NRB2-0310-TFD NRB2-031A-TFC NRB2-031A-TFD NRB2-0400-TFC NRB2-0400-TFD Max LRA Volts PH RLA 575 208/230 460 208/230 460 200 200 380 208/230 460 575 208/230 460 208/230 460 208/230 460 208/230 460 208/230 460 208/230 460 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 NA 30.3 13.5 30.3 13.5 NA NA NA NA NA NA 19.2 9.6 NA NA 19.2 9.6 12.9 6.4 12.9 6.4 21.9 11.3 63.8 164 82 164 82 110 79.6 62.5 141 62.5 53.4 141 62.5 141 62.5 141 62.5 82 41 82 41 141 62.5 Resistance Start Cap Run Cap Start or Run or P/N P/N Line to Line Line to WYE 2.16 0.338 1.351 0.338 1.351 0.415 0.721 2.14 0.546 2.14 3.23 0.546 2.14 0.546 2.14 0.546 2.14 0.9 3.6 0.9 3.6 0.514 1.987 * See Section F Introduction for more information. Section_Fd.indd 37 1.08 0.169 0.675 0.169 0.675 0.207 0.384 1.07 0.273 1.07 1.615 0.273 1.07 0.273 1.07 0.273 1.07 0.47 1.9 0.47 1.9 0.257 0.99 Relay P/N Part Protector Type* P/N 071-0086-40 071-0086-21 071-0086-20 071-0086-21 071-0086-20 071-0086-42 071-0086-41 071-0086-14 071-0086-39 071-0086-14 071-0086-17 071-0086-39 071-0086-14 071-0086-39 071-0086-14 071-0086-39 071-0086-14 071-0086-11 071-0086-37 071-0086-11 071-0086-37 071-0086-39 071-0086-14 FD37 3/4/2008 8:03:01 AM Electrical Data - Copelametic Small Refrigerant-Cooled Compressors Model NRB2-0400-TFE NRB2-040A-TFC NRB2-040A-TFD NRB2-040E-TFC NRB2-040E-TFD NRB2-040L-TFC NRB2-040L-TFD NRB3-0400-TFC NRB3-0400-TFD NRB3-040L-TFC NRB3-040L-TFD NRD1-0310-TFC NRD1-0310-TFD NRD1-0310-TFU NRD1-031A-TFC NRD1-031A-TFD NRD1-032E-TFC NRD1-032E-TFD NRD1-032L-TFC NRD1-032L-TFD NRD1-0406-CFB NRD1-040A-CFB NRD1-040E-CFB FD38 Max LRA Volts PH RLA 575 208/230 460 208/230 460 208/230 460 208/230 460 208/230 460 208/230 460 200 208/230 460 208/230 460 208/230 460 230 230 230 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 1 1 1 9.2 21.9 11.3 21.9 9 21.9 9 21.9 11.3 21.9 11.3 NA NA NA NA 7.3 16.3 8.4 16.3 8.4 23.6 23.6 27.7 53.4 141 62.5 141 62.5 141 62.5 141 62.5 141 62.5 82 41 79.6 82 41 82 41 82 41 115 115 115 Resistance Start Cap Run Cap Start or Run or P/N P/N Line to Line Line to WYE 3.23 0.514 1.987 0.546 1.987 0.546 1.987 0.514 1.987 0.514 1.987 0.9 3.6 0.721 0.9 3.6 0.9 3.6 0.9 3.6 2.32 2.32 2.32 1.615 0.257 0.99 0.273 0.99 0.273 0.99 0.257 0.99 0.257 0.99 0.47 1.9 0.384 0.47 1.9 0.47 1.9 0.47 1.9 0.417 0.417 0.417 Relay P/N 014-0006-14 014-0064-14 040-0166-28 014-0006-14 014-0064-14 040-0166-28 014-0006-14 014-0064-14 040-0166-28 Part Protector Type* P/N RP RP RP 071-0086-17 071-0086-39 071-0086-14 071-0086-39 071-0429-18 071-0086-39 071-0429-18 071-0086-39 071-0086-14 071-0086-39 071-0086-14 071-0086-11 071-0086-37 071-0086-41 071-0086-11 071-0086-37 071-0429-30 071-0429-31 071-0429-30 071-0429-31 071-0476-01 071-0476-01 071-0476-01 * See Section F Introduction for more information. Section_Fd.indd 38 3/4/2008 8:03:01 AM Electrical Data - Copelametic Small Refrigerant-Cooled Compressors Model NRD1-040L-CFB NRD2-032E-TFC NRD2-032E-TFD NRM1-0500-TFC NRM1-0500-TFD NRM1-0500-TFE NRM1-050A-TFC NRM1-050A-TFD NRM1-050L-TFC NRM1-050L-TFD NRN2-0310-TFC NRN2-0310-TFD NRN2-031A-TFC NRN2-031A-TFD Max LRA Volts PH RLA 230 208/230 460 208/230 460 575 208/230 460 208/230 460 208/230 460 208/230 460 1 3 3 3 3 3 3 3 3 3 3 3 3 3 27.7 16.3 8.4 24.3 12.1 9.2 24.3 12.1 24.3 12.1 13 6.5 13 6.4 115 82 41 141 62.5 53.4 141 62.5 141 62.5 82 41 82 41 Resistance Start Cap Run Cap Start or Run or P/N P/N Line to Line Line to WYE 2.32 0.9 3.6 0.546 2.14 3.23 0.546 2.14 0.546 2.14 0.9 3.6 0.9 3.6 * See Section F Introduction for more information. Section_Fd.indd 39 0.417 0.47 1.9 0.273 1.07 1.615 0.273 1.07 0.273 1.07 0.47 1.9 0.47 1.9 Relay P/N 014-0006-14 014-0064-14 040-0166-28 Part Protector Type* P/N RP 071-0476-01 071-0429-30 071-0429-31 071-0086-39 071-0086-14 071-0086-17 071-0086-39 071-0086-14 071-0086-39 071-0086-14 071-0086-11 071-0086-37 071-0086-11 071-0086-37 FD39 3/4/2008 8:03:01 AM Electrical Data - Copelametic Large Refrigerant-Cooled Compressors Model Volts PH 3DA3A0710-ESX 3DA3A0710-ESX 3DA3A071E-ESX 3DA3A071E-ESX 3DA3A071L-ESX 3DA3A071L-ESX 3DB3A0750-ES8 3DB3A0750-ES8 3DB3A0910-ESX 3DB3A0910-ESX 3DB3A091E-ESX 3DB3A091E-ESX 3DB3A1000-ES8 3DB3A1000-ES8 3DB3F33K0-ES8 3DB3F33K0-ES8 3DB3R12M0-ES8 3DB3R12M0-ES8 3DP3A1000-ES8 3DP3A1000-ES8 3DP3R12M0-ES8 3DP3R12M0-ES8 200/220 380 200/220 380 200/220 380 200/220 380 220 380 220 380 200/220 380 200/220 380 200/220 380 200/220 380 200/220 380 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 Across the Line Max RLA LRA 25.7 15.6 31.8 18.9 31.8 18.9 29.2 16.4 38.1 20.4 47.4 27.7 48 27.4 29.2 16.4 48 27.4 48 27.4 48 27.4 167 96 167 96 167 96 167 96 228 132 228 132 228 132 167 96 228 132 228 132 228 132 Part Winding Start Max RLA LRA 58 58 58 58 74 74 74 58 74 74 74 Winding Resistance Line to Line (Ohms) 0.36 1.08 0.36 1.08 0.36 1.08 0.36 1.08 0.279 0.837 0.279 0.837 0.279 0.837 0.36 1.08 0.279 0.837 0.279 0.837 0.279 0.837 See Section F Introduction for more information. FE1 Section_Fe.indd 1 3/4/2008 8:06:37 AM Electrical Data - Copelametic Large Refrigerant-Cooled Compressors Model Volts PH 3DR3A1000-ES8 3DR3A1000-ES8 3DS3A1000-ES8 3DS3A1000-ES8 3DS3A1210-ESX 3DS3A1210-ESX 3DS3A121E-ESX 3DS3A121E-ESX 3DS3A1500-ES8 3DS3A1500-ES8 3DS3F46K0-ES8 3DS3F46K0-ES8 3DS3R17M0-ES8 3DS3R17M0-ES8 3DT3A1000-ES8 3DT3A1000-ES8 3DT3A1500-ES8 3DT3A1500-ES8 3DT3R17M0-ES8 3DT3R17M0-ES8 4DA1A1000-FSD 4DA1A1000-TSE 200/220 380 200/220 380 220 380 220 380 200/220 380 200/220 380 200/220 380 200/220 380 200/220 380 200/220 380 460 575 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 Across the Line Max RLA LRA 41.7 24.1 47.1 25.7 42.1 24.1 53.4 31.2 57.6 32.9 47.1 25.7 57.6 32.9 47.1 25.7 57.6 32.9 57.6 32.9 25.7 20 228 132 228 132 228 132 228 132 316 180 228 132 316 180 228 132 316 180 316 180 110 106 Part Winding Start Max RLA LRA 74 74 74 74 108 74 108 74 108 108 12.9 66 Winding Resistance Line to Line (Ohms) 0.279 0.837 0.279 0.837 0.279 0.837 0.279 0.837 0.191 0.573 0.279 0.837 0.191 0.573 0.279 0.837 0.191 0.573 0.191 0.573 1.02 1.6 See Section F Introduction for more information. FE2 Section_Fe.indd 2 3/4/2008 8:06:41 AM Electrical Data - Copelametic Large Refrigerant-Cooled Compressors Model Volts PH 4DA1A1000-TSK 4DA1A1000-TSK 4DA1A2000-FSD 4DA1A2000-TSE 4DA1A2000-TSK 4DA1A2000-TSK 4DA1A2000-TXK 4DA1A2000-TXK 4DA1R18M0-TSK 4DA1R18M0-TSK 4DA3A1000-FSD 4DA3A1000-TSE 4DA3A1000-TSK 4DA3A1000-TSK 4DA3A100E-FSD 4DA3A100E-TSE 4DA3A100E-TSK 4DA3A100E-TSK 4DA3A100L-FSD 4DA3A100L-TSE 4DA3A100L-TSK 4DA3A100L-TSK 208/230 460 460 575 208/230 460 208/230 460 208/230 460 460 575 208/230 460 460 575 208/230 460 460 575 208/230 460 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 Across the Line Max RLA LRA 53.6 26.8 32.1 28.6 70 35 NA NA 70 35 20 17.4 42 21 20 17.4 42 21 20 17.4 42 21 240 120 140 135 308 154 308 154 308 154 115 106 240 120 115 106 240 120 115 106 240 120 Part Winding Start Max RLA LRA 26.8 140 16.1 14.3 35 84 81 188 35 188 35 188 10 70 21 140 10 70 21 140 10 70 21 140 Winding Resistance Line to Line (Ohms) 0.259 1.036 0.757 2.2 0.174 0.696 0.174 0.696 0.174 0.696 1.012 1.6 0.259 1.036 1.012 1.6 0.259 1.036 1.012 1.6 0.259 1.036 See Section F Introduction for more information. FE3 Section_Fe.indd 3 3/4/2008 8:06:41 AM Electrical Data - Copelametic Large Refrigerant-Cooled Compressors Model Volts PH 4DA3A1010-TSE 4DA3A1010-TSK 4DA3A1010-TSK 4DA3A101E-TSE 4DA3A101E-TSK 4DA3A101E-TSK 4DA3A101L-TSE 4DA3A101L-TSK 4DA3A101L-TSK 4DA3A2000-FSD 4DA3A2000-FXD 4DA3A2000-TSE 4DA3A2000-TSK 4DA3A2000-TSK 4DA3A2000-TXE 4DA3A2000-TXK 4DA3A2000-TXK 4DA3A200E-FSD 4DA3A200E-TSE 4DA3A200E-TSK 4DA3A200E-TSK 4DA3A200L-FSD 575 208/230 460 575 208/230 460 575 208/230 460 460 460 575 208/230 460 575 208/230 460 460 575 208/230 460 460 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 Across the Line Max RLA LRA 17.4 42 21 17.4 45.6 22.8 17.4 45.6 22.8 33.6 NA 24.7 66.6 33.3 NA NA NA 33.6 24.7 82.9 41.4 33.6 106 220 110 106 220 110 106 220 110 173 173 135 308 154 135 308 154 173 135 308 154 173 Part Winding Start Max RLA LRA 22.6 134 22.6 134 22.6 134 16.8 12.4 33 104 104 81 188 33 81 188 16.8 12.4 33 104 81 188 16.8 104 Winding Resistance Line to Line (Ohms) 1.6 0.244 0.976 1.6 0.244 0.976 1.6 0.244 0.976 0.603 0.603 2.2 0.174 0.696 1.1 0.174 0.696 0.603 2.2 0.174 0.696 0.603 See Section F Introduction for more information. FE4 Section_Fe.indd 4 3/4/2008 8:06:42 AM Electrical Data - Copelametic Large Refrigerant-Cooled Compressors Model Volts PH 4DA3A200L-TSE 4DA3A200L-TSK 4DA3A200L-TSK 4DA3F47K0-TSE 4DA3F47K0-TSK 4DA3F47K0-TSK 4DA3F47KE-TSE 4DA3F47KE-TSK 4DA3F47KE-TSK 4DA3F47KL-TSE 4DA3F47KL-TSK 4DA3F47KL-TSK 4DA3R12M0-FSD 4DA3R12ME-FSD 4DA3R12ME-TSK 4DA3R12ME-TSK 4DA3R18M0-FSD 4DA3R18M0-TSE 4DA3R18M0-TSK 4DA3R18M0-TSK 4DA3R18ME-FSD 4DA3R18ME-TSE 575 208/230 460 575 208/230 460 575 208/230 460 575 208/230 460 460 460 208/230 460 460 575 208/230 460 460 575 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 Across the Line Max RLA LRA 24.7 82.9 41.4 17.4 42 21 17.4 45.6 22.8 17.4 45.6 22.8 20 20 42 21 33.6 24.7 66.6 33.3 33.6 24.7 135 308 154 106 220 110 106 220 110 106 220 110 115 115 240 120 173 135 308 154 173 135 Part Winding Start Max RLA LRA 12.4 33 81 188 22.6 134 22.6 134 22.6 134 10 10 21 70 70 140 16.8 12.4 33 104 81 188 16.8 12.4 104 81 Winding Resistance Line to Line (Ohms) 2.2 0.174 0.696 1.6 0.244 0.976 1.6 0.244 0.976 1.6 0.244 0.976 1.012 1.012 0.259 1.036 0.603 2.2 0.174 0.696 0.603 2.2 See Section F Introduction for more information. FE5 Section_Fe.indd 5 3/4/2008 8:06:42 AM Electrical Data - Copelametic Large Refrigerant-Cooled Compressors Model Volts PH 4DA3R18ME-TSK 4DA3R18ME-TSK 4DA3R18ML-FSD 4DA3R18ML-TSE 4DA3R18ML-TSK 4DA3R18ML-TSK 4DA3S13ME-TSK 4DA3S13ME-TSK 4DA3S13ML-TSK 4DA3S13ML-TSK 4DA5A1000-TSK 4DA5A1000-TSK 4DAGA1010-TSK 4DAGA1010-TSK 4DAJA2000-TSK 4DAJA2000-TSK 4DB3A2200-FSD 4DB3A2200-TSE 4DB3A2200-TSK 4DB3A2200-TSK 4DB3A220E-FSD 4DB3A220E-TSE 208/230 460 460 575 208/230 460 208/230 460 208/230 460 208/230 460 208/230 460 208/230 460 460 575 208/230 460 460 575 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 Across the Line Max RLA LRA 82.9 41.4 33.6 24.7 82.9 41.4 57.1 27.1 57.1 27.1 53.6 26.8 42 21 66.6 33.3 32.5 26.5 65.6 32.8 32.5 31.4 308 154 173 135 308 154 278 139 278 139 240 120 220 110 308 154 180 135 374 187 180 135 Part Winding Start Max RLA LRA 33 188 16.8 12.4 33 104 81 188 26.8 140 22.6 134 33 188 16.3 13.3 32.8 108 81 222 16.3 13.3 108 81 Winding Resistance Line to Line (Ohms) 0.174 0.696 0.603 2.2 0.174 0.696 0 0.204 0 0.204 0.259 1.036 0.244 0.976 0.174 0.696 0.558 1.94 0.14 0.56 0.558 1.94 See Section F Introduction for more information. FE6 Section_Fe.indd 6 3/4/2008 8:06:43 AM Electrical Data - Copelametic Large Refrigerant-Cooled Compressors Model Volts PH 4DB3A220E-TSK 4DB3A220E-TSK 4DB3A220L-FSD 4DB3A220L-TSE 4DB3A220L-TSK 4DB3A220L-TSK 4DB3R20M0-FSD 4DB3R20M0-TSE 4DB3R20M0-TSK 4DB3R20M0-TSK 4DB3R20ME-FSD 4DB3R20ME-TSE 4DB3R20ME-TSK 4DB3R20ME-TSK 4DB3R20ML-FSD 4DB3R20ML-TSE 4DB3R20ML-TSK 4DB3R20ML-TSK 4DC3A2200-FSD 4DC3A2200-TSE 4DC3A2200-TSK 4DC3A2200-TSK 208/230 460 460 575 208/230 460 460 575 208/230 460 460 575 208/230 460 460 575 208/230 460 460 575 208/230 460 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 Across the Line Max RLA LRA 92.9 46.4 32.5 31.4 92.9 46.4 32.5 26.5 65.6 32.8 32.5 31.4 92.9 46.4 32.5 31.4 92.9 46.4 32.5 26.5 65.6 32.8 374 187 180 135 374 187 180 135 374 187 180 135 374 187 180 135 374 187 180 135 374 187 Part Winding Start Max RLA LRA 32.8 222 16.3 13.3 32.8 108 81 222 16.3 13.3 32.8 108 81 222 16.3 13.3 32.8 108 81 222 16.3 13.3 32.8 108 81 222 16.3 13.3 32.8 108 81 222 Winding Resistance Line to Line (Ohms) 0.14 0.56 0.558 1.94 0.14 0.56 0.558 1.94 0.14 0.56 0.558 1.94 0.14 0.56 0.558 1.94 0.14 0.56 0.558 1.94 0.14 0.56 See Section F Introduction for more information. FE7 Section_Fe.indd 7 3/4/2008 8:06:43 AM Electrical Data - Copelametic Large Refrigerant-Cooled Compressors Model Volts PH 4DC3A220E-FSD 4DC3A220E-TSE 4DC3A220E-TSK 4DC3A220E-TSK 4DC3A220L-FSD 4DC3A220L-TSE 4DC3A220L-TSK 4DC3A220L-TSK 4DC3R20M0-FSD 4DC3R20M0-TSE 4DC3R20M0-TSK 4DC3R20M0-TSK 4DC3R20ME-FSD 4DC3R20ME-TSE 4DC3R20ME-TSK 4DC3R20ME-TSK 4DC3R20ML-FSD 4DC3R20ML-TSE 4DC3R20ML-TSK 4DC3R20ML-TSK 4DE1A1000-TSE 4DE1A1000-TSK 460 575 208/230 460 460 575 208/230 460 460 575 208/230 460 460 575 208/230 460 460 575 208/230 460 575 208/230 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 Across the Line Max RLA LRA 32.5 31.4 92.9 46.4 32.5 31.4 92.9 46.4 32.5 26.5 65.6 32.8 32.5 31.4 92.9 46.4 32.5 31.4 92.9 46.4 20 53.6 180 135 374 187 180 135 374 187 180 135 374 187 180 135 374 187 180 135 374 187 106 240 Part Winding Start Max RLA LRA 16.3 13.3 32.8 108 81 222 16.3 13.3 32.8 108 81 222 16.3 13.3 32.8 108 81 222 16.3 13.3 32.8 108 81 222 16.3 13.3 32.8 108 81 222 26.8 140 Winding Resistance Line to Line (Ohms) 0.558 1.94 0.14 0.56 0.558 1.94 0.14 0.56 0.558 1.94 0.14 0.56 0.558 1.94 0.14 0.56 0.558 1.94 0.14 0.56 1.6 0.259 See Section F Introduction for more information. FE8 Section_Fe.indd 8 3/4/2008 8:06:43 AM Electrical Data - Copelametic Large Refrigerant-Cooled Compressors Model Volts PH 4DE1A1000-TSK 4DE1A2000-FSD 4DE1A2000-TSE 4DE1A2000-TSK 4DE1A2000-TSK 4DE1A2000-TXK 4DE1A2000-TXK 4DE1R18M0-FSD 4DE1R18M0-TSK 4DE1R18M0-TSK 4DE3A100E-TSK 4DE3A100E-TSK 4DE3A100L-TSK 4DE3A100L-TSK 4DE3A2000-FSD 4DE3A2000-FXD 4DE3A2000-TSE 4DE3A2000-TSK 4DE3A2000-TSK 4DE3A2000-TXE 4DE3A2000-TXK 4DE3A2000-TXK 460 460 575 208/230 460 208/230 460 460 208/230 460 208/230 460 208/230 460 460 460 575 208/230 460 575 208/230 460 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 Across the Line Max RLA LRA 26.8 32.1 28.6 70 35 NA NA 32.1 70 35 42 21 42 21 33.6 NA 24.7 66.6 33.3 NA NA NA 120 140 135 308 154 308 154 140 308 154 240 120 240 120 173 173 135 308 154 135 308 154 Part Winding Start Max RLA LRA 16.1 14.3 35 84 81 188 35 188 16.1 35 84 188 21 140 21 140 16.8 12.4 33 104 104 81 188 33 81 188 Winding Resistance Line to Line (Ohms) 1.036 0.757 2.2 0.174 0.696 0.174 0.696 0.757 0.174 0.696 0.259 1.036 0.259 1.036 0.603 0.603 2.2 0.174 0.696 1.1 0.174 0.696 See Section F Introduction for more information. FE9 Section_Fe.indd 9 3/4/2008 8:06:44 AM Electrical Data - Copelametic Large Refrigerant-Cooled Compressors Model Volts PH 4DE3A200E-FSD 4DE3A200E-TSE 4DE3A200E-TSK 4DE3A200E-TSK 4DE3A200L-FSD 4DE3A200L-TSE 4DE3A200L-TSK 4DE3A200L-TSK 4DE3R12ME-TSK 4DE3R12ME-TSK 4DE3R12ML-TSK 4DE3R12ML-TSK 4DE3R18M0-FSD 4DE3R18M0-TSE 4DE3R18M0-TSK 4DE3R18M0-TSK 4DE3R18ME-FSD 4DE3R18ME-TSE 4DE3R18ME-TSK 4DE3R18ME-TSK 4DE3R18ML-FSD 4DE3R18ML-TSE 460 575 208/230 460 460 575 208/230 460 208/230 460 208/230 460 460 575 208/230 460 460 575 208/230 460 460 575 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 Across the Line Max RLA LRA 33.6 24.7 82.9 41.4 33.6 24.7 82.9 41.4 42 21 42 21 33.6 24.7 66.6 33.3 33.6 24.7 82.9 41.4 33.6 24.7 173 135 308 154 173 135 308 154 240 120 240 120 173 135 308 154 173 135 308 154 173 135 Part Winding Start Max RLA LRA 16.8 12.4 33 104 81 188 16.8 12.4 33 104 81 188 21 140 21 140 16.8 12.4 33 104 81 188 16.8 12.4 33 104 81 188 16.8 12.4 104 81 Winding Resistance Line to Line (Ohms) 0.603 2.2 0.174 0.696 0.603 2.2 0.174 0.696 0.259 1.036 0.259 1.036 0.603 2.2 0.174 0.696 0.603 2.2 0.174 0.696 0.603 2.2 See Section F Introduction for more information. FE10 Section_Fe.indd 10 3/4/2008 8:06:44 AM Electrical Data - Copelametic Large Refrigerant-Cooled Compressors Model Volts PH 4DE3R18ML-TSK 4DE3R18ML-TSK 4DE3S13ME-TSK 4DE3S13ME-TSK 4DE3S13ML-TSK 4DE3S13ML-TSK 4DE5A2000-TSK 4DE5A2000-TSK 4DE8A101E-TSK 4DE8A101E-TSK 4DE8A2000-FSD 4DE8A200E-TSK 4DE8A200E-TSK 4DE8F47KE-TSK 4DE8F47KE-TSK 4DH1A1500-FSD 4DH1A1500-TSE 4DH1A1500-TSK 4DH1A1500-TSK 4DH1A2500-ES8 4DH1A2500-ES8 4DH1A2500-FSD 208/230 460 208/230 460 208/230 460 208/230 460 208/230 460 460 208/230 460 208/230 460 460 575 208/230 460 200/220 380 460 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 Across the Line Max RLA LRA 82.9 41.4 57.1 27.1 57.1 27.1 70 35 45.6 22.8 33.6 58.7 29.4 45.6 22.8 32.9 24.3 61.4 30.7 99.3 58.6 46.4 308 154 278 139 278 139 308 154 220 110 173 308 154 220 110 136 113 278 139 438 251 195 Part Winding Start Max RLA LRA 33 188 35 188 22.6 134 16.8 33 104 188 22.6 134 16.5 81.6 30.7 170 142 23.2 117 Winding Resistance Line to Line (Ohms) 0.174 0.696 0 0.204 0 0.204 0.174 0.696 0.244 0.976 0.603 0.174 0.696 0.244 0.976 0.84 0.97 0.208 0.832 0.345 0.115 0.575 See Section F Introduction for more information. FE11 Section_Fe.indd 11 3/4/2008 8:06:44 AM Electrical Data - Copelametic Large Refrigerant-Cooled Compressors Model Volts PH 4DH1A2500-FXD 4DH1A2500-TSE 4DH1A2500-TSK 4DH1A2500-TSK 4DH1A2500-TXE 4DH1A2500-TXK 4DH1A2500-TXK 4DH1R22M0-ES8 4DH1R22M0-ES8 4DH1R22M0-FSD 4DH1R22M0-TSK 4DH1R22M0-TSK 4DH3A150E-TSE 4DH3A150E-TSK 4DH3A150E-TSK 4DH3A150L-TSE 4DH3A150L-TSK 4DH3A150L-TSK 4DH3A2500-ES8 4DH3A2500-ES8 4DH3A2500-FSD 4DH3A2500-FXD 460 575 208/230 460 575 208/230 460 200/220 380 460 208/230 460 575 208/230 460 575 208/230 460 200/220 380 460 460 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 Across the Line Max RLA LRA NA 34.3 85.7 42.9 NA NA NA 99.3 58.6 46.4 85.7 42.9 24.3 57.9 28.9 24.3 57.9 28.9 NA NA 40.6 NA 195 172 428 214 172 428 214 438 251 195 428 214 113 278 139 113 278 139 438 251 206 206 Part Winding Start Max RLA LRA 17.2 42.9 117 103 250 103 250 142 23.2 42.9 117 250 29 170 29 170 142 20.3 132 132 Winding Resistance Line to Line (Ohms) 0.575 1.538 0.132 0.528 0.769 0.132 0.528 0.345 0.115 0.575 0.132 0.528 1.28 0.208 0.832 1.28 0.208 0.832 0.345 0.115 0.524 0.524 See Section F Introduction for more information. FE12 Section_Fe.indd 12 3/4/2008 8:06:45 AM Electrical Data - Copelametic Large Refrigerant-Cooled Compressors Model Volts PH 4DH3A2500-TSE 4DH3A2500-TSK 4DH3A2500-TSK 4DH3A2500-TXE 4DH3A2500-TXK 4DH3A2500-TXK 4DH3A250E-ES8 4DH3A250E-ES8 4DH3A250E-FSD 4DH3A250E-TSE 4DH3A250E-TSK 4DH3A250E-TSK 4DH3A250L-ES8 4DH3A250L-ES8 4DH3A250L-FSD 4DH3A250L-TSE 4DH3A250L-TSK 4DH3A250L-TSK 4DH3R16ME-TSK 4DH3R16ME-TSK 4DH3R16ML-TSK 4DH3R16ML-TSK 575 208/230 460 575 208/230 460 200/220 380 460 575 208/230 460 200/220 380 460 575 208/230 460 208/230 460 208/230 460 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 Across the Line Max RLA LRA 34.4 82.1 41.1 NA NA NA NA NA 40.6 34.4 82.1 52.9 NA NA 40.6 34.4 82.1 52.9 57.9 28.9 57.9 28.9 172 428 214 172 428 214 438 251 206 172 428 214 438 251 206 172 428 214 278 139 278 139 Part Winding Start Max RLA LRA 17.2 41.1 103 250 103 250 142 20.3 17.2 41.1 132 103 250 142 20.3 17.2 41.1 132 103 250 29 170 29 170 Winding Resistance Line to Line (Ohms) 1.538 0.132 0.528 0.769 0.132 0.528 0.345 0.115 0.524 1.538 0.132 0.528 0.345 0.115 0.524 1.538 0.132 0.528 0.208 0.832 0.208 0.832 See Section F Introduction for more information. FE13 Section_Fe.indd 13 3/4/2008 8:06:45 AM Electrical Data - Copelametic Large Refrigerant-Cooled Compressors Model Volts PH 4DH3R22M0-ES8 4DH3R22M0-ES8 4DH3R22M0-FSD 4DH3R22M0-TSE 4DH3R22M0-TSK 4DH3R22M0-TSK 4DH3R22M0-TXE 4DH3R22ME-FSD 4DH3R22ME-TSE 4DH3R22ME-TSK 4DH3R22ME-TSK 4DH3R22ML-FSD 4DH3R22ML-TSE 4DH3R22ML-TSK 4DH3R22ML-TSK 4DH3S16ME-TSK 4DH3S16ME-TSK 4DH3S16ML-TSK 4DH3S16ML-TSK 4DJ1A2000-FSD 4DJ1A2000-TSE 4DJ1A2000-TSK 200/220 380 460 575 208/230 460 575 460 575 208/230 460 460 575 208/230 460 208/230 460 208/230 460 460 575 208/230 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 Across the Line Max RLA LRA NA NA 40.6 34.4 82.1 41.1 NA 40.6 34.4 82.1 52.9 40.6 34.4 82.1 52.9 65.7 32.1 NA NA 32.9 30 71.4 438 251 206 172 428 214 172 206 172 428 214 206 172 428 214 308 154 308 154 173 135 346 Part Winding Start Max RLA LRA 142 20.3 17.2 41.1 132 103 250 20.3 17.2 41.1 103 132 103 250 20.3 17.2 41.1 132 103 250 16.5 15 35.7 104 81 208 Winding Resistance Line to Line (Ohms) 0.345 0.115 0.524 1.538 0.132 0.528 0.769 0.524 1.538 0.132 0.528 0.524 1.538 0.132 0.528 0 0.179 0 0.179 0.603 1.94 0.142 See Section F Introduction for more information. FE14 Section_Fe.indd 14 3/4/2008 8:06:46 AM Electrical Data - Copelametic Large Refrigerant-Cooled Compressors Model Volts PH 4DJ1A2000-TSK 4DJ1A3000-ES8 4DJ1A3000-ES8 4DJ1A3000-FSD 4DJ1A3000-TSE 4DJ1A3000-TSK 4DJ1A3000-TSK 4DJ1A3000-TXE 4DJ1A3000-TXK 4DJ1A3000-TXK 4DJ1R28M0-TSK 4DJ1R28M0-TSK 4DJ2A2000-TSK 4DJ2A2000-TSK 4DJ2A3000-TSK 4DJ2A3000-TSK 4DJ2R28M0-TSK 4DJ2R28M0-TSK 4DJ3A200E-TSE 4DJ3A200E-TSK 4DJ3A200E-TSK 4DJ3A200L-TSE 460 200/220 380 460 575 208/230 460 575 208/230 460 208/230 460 208/230 460 208/230 460 208/230 460 575 208/230 460 575 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 Across the Line Max RLA LRA 35.7 123.6 71.4 59 42.9 117.9 58.9 NA NA NA 117.9 58.9 71.4 35.7 117.9 58.9 117.9 58.9 30 66 33 30 173 500 289 235 200 470 235 200 470 235 470 235 346 173 470 235 470 235 135 346 173 135 Part Winding Start Max RLA LRA 164 29.5 21.5 59 141 130 292 130 292 59 292 35.7 208 59 292 59 292 15 33 81 208 15 81 Winding Resistance Line to Line (Ohms) 0.568 0.294 0.098 0.45 1.46 0.111 0.444 0.731 0.111 0.444 0.111 0.444 0.142 0.568 0.111 0.444 0.111 0.444 1.94 0.142 0.568 1.94 See Section F Introduction for more information. FE15 Section_Fe.indd 15 3/4/2008 8:06:46 AM Electrical Data - Copelametic Large Refrigerant-Cooled Compressors Model Volts PH 4DJ3A200L-TSK 4DJ3A200L-TSK 4DJ3A270E-TSK 4DJ3A270E-TSK 4DJ3A270L-TSK 4DJ3A270L-TSK 4DJ3A3000-FSD 4DJ3A3000-FXD 4DJ3A3000-TSE 4DJ3A3000-TSK 4DJ3A3000-TSK 4DJ3A3000-TXE 4DJ3A3000-TXK 4DJ3A3000-TXK 4DJ3A300E-FSD 4DJ3A300E-TSE 4DJ3A300E-TSK 4DJ3A300E-TSK 4DJ3A300L-FSD 4DJ3A300L-TSE 4DJ3A300L-TSK 4DJ3A300L-TSK 208/230 460 208/230 460 208/230 460 460 460 575 208/230 460 575 208/230 460 460 575 208/230 460 460 575 208/230 460 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 Across the Line Max RLA LRA 66 33 94 55 94 55 45 NA 39.3 94 47 NA NA NA 45 39.3 94 55 45 39.3 94 55 346 173 470 235 470 235 235 235 200 470 235 200 470 235 235 200 470 235 235 200 470 235 Part Winding Start Max RLA LRA 33 208 47 292 47 292 22.5 141 141 130 292 19.7 47 130 292 22.5 19.7 47 141 130 292 22.5 19.7 47 141 130 292 Winding Resistance Line to Line (Ohms) 0.142 0.568 0.111 0.444 0.111 0.444 0.45 0.45 1.46 0.111 0.444 0.731 0.111 0.444 0.45 1.46 0.111 0.444 0.45 1.46 0.111 0.444 See Section F Introduction for more information. FE16 Section_Fe.indd 16 3/4/2008 8:06:46 AM Electrical Data - Copelametic Large Refrigerant-Cooled Compressors Model Volts PH 4DJ3R19ME-TSK 4DJ3R19ME-TSK 4DJ3R19ML-TSK 4DJ3R19ML-TSK 4DJ3R28M0-FSD 4DJ3R28M0-TSE 4DJ3R28M0-TSK 4DJ3R28M0-TSK 4DJ3R28ME-FSD 4DJ3R28ME-TSE 4DJ3R28ME-TSK 4DJ3R28ME-TSK 4DJ3R28ML-FSD 4DJ3R28ML-TSE 4DJ3R28ML-TSK 4DJ3R28ML-TSK 4DJ8A3000-TSK 4DJ8A3000-TSK 4DK1A1500-TSK 4DK1A1500-TSK 4DK1A2500-ES8 4DK1A2500-ES8 208/230 460 208/230 460 460 575 208/230 460 460 575 208/230 460 460 575 208/230 460 208/230 460 208/230 460 200/220 380 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 Across the Line Max RLA LRA 66 33 66 33 45 39.3 94 47 45 39.3 94 55 45 39.3 94 55 94 47 61.4 30.7 99.3 58.6 346 173 346 173 235 200 470 235 235 200 470 235 235 200 470 235 470 235 278 139 438 251 Part Winding Start Max RLA LRA 33 208 33 208 22.5 19.7 47 141 130 292 22.5 19.7 47 141 130 292 22.5 19.7 47 141 130 292 47 292 30.7 170 142 Winding Resistance Line to Line (Ohms) 0.142 0.568 0.142 0.568 0.45 1.46 0.111 0.444 0.45 1.46 0.111 0.444 0.45 1.46 0.111 0.444 0.111 0.444 0.208 0.832 0.345 0.115 See Section F Introduction for more information. FE17 Section_Fe.indd 17 3/4/2008 8:06:47 AM Electrical Data - Copelametic Large Refrigerant-Cooled Compressors Model Volts PH 4DK1A2500-FSD 4DK1A2500-FXD 4DK1A2500-TSE 4DK1A2500-TSK 4DK1A2500-TSK 4DK1A2500-TXE 4DK1A2500-TXK 4DK1A2500-TXK 4DK1R22M0-FSD 4DK1R22M0-TSE 4DK1R22M0-TSK 4DK1R22M0-TSK 4DK3A150E-TSE 4DK3A150E-TSK 4DK3A150E-TSK 4DK3A150L-TSE 4DK3A150L-TSK 4DK3A150L-TSK 4DK3A2500-ES8 4DK3A2500-ES8 4DK3A2500-FSD 4DK3A2500-FXD 460 460 575 208/230 460 575 208/230 460 460 575 208/230 460 575 208/230 460 575 208/230 460 200/220 380 460 460 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 Across the Line Max RLA LRA 46.4 NA 34.3 85.7 42.9 NA NA NA 46.4 34.3 85.7 42.9 24.3 57.9 28.9 24.3 57.9 28.9 NA NA 40.6 NA 195 195 172 428 214 172 428 214 195 172 428 214 113 278 139 113 278 139 438 251 206 206 Part Winding Start Max RLA LRA 23.2 17.2 42.9 117 117 103 250 103 250 23.2 17.2 42.9 117 103 250 29 170 29 170 142 20.3 132 132 Winding Resistance Line to Line (Ohms) 0.575 0.575 1.538 0.132 0.528 0.769 0.132 0.528 0.575 1.538 0.132 0.528 1.28 0.208 0.832 1.28 0.208 0.832 0.345 0.115 0.524 0.524 See Section F Introduction for more information. FE18 Section_Fe.indd 18 3/4/2008 8:06:47 AM Electrical Data - Copelametic Large Refrigerant-Cooled Compressors Model Volts PH 4DK3A2500-TSE 4DK3A2500-TSK 4DK3A2500-TSK 4DK3A2500-TXE 4DK3A2500-TXK 4DK3A2500-TXK 4DK3A250E-ES8 4DK3A250E-ES8 4DK3A250E-FSD 4DK3A250E-TSE 4DK3A250E-TSK 4DK3A250E-TSK 4DK3A250L-ES8 4DK3A250L-ES8 4DK3A250L-FSD 4DK3A250L-TSE 4DK3A250L-TSK 4DK3A250L-TSK 4DK3R16ME-TSK 4DK3R16ME-TSK 4DK3R22M0-ES8 4DK3R22M0-ES8 575 208/230 460 575 208/230 460 200/220 380 460 575 208/230 460 200/220 380 460 575 208/230 460 208/230 460 200/220 380 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 Across the Line Max RLA LRA 34.4 82.1 41.1 NA NA NA NA NA 40.6 34.4 82.1 52.9 NA NA 40.6 34.4 82.1 52.9 57.9 28.9 NA NA 172 428 214 172 428 214 438 251 206 172 428 214 438 251 206 172 428 214 278 139 438 251 Part Winding Start Max RLA LRA 17.2 41.1 103 250 103 250 142 20.3 17.2 41.1 132 103 250 142 20.3 17.2 41.1 132 103 250 29 170 142 Winding Resistance Line to Line (Ohms) 1.538 0.132 0.528 0.769 0.132 0.528 0.345 0.115 0.524 1.538 0.132 0.528 0.345 0.115 0.524 1.538 0.132 0.528 0.208 0.832 0.345 0.115 See Section F Introduction for more information. FE19 Section_Fe.indd 19 3/4/2008 8:06:48 AM Electrical Data - Copelametic Large Refrigerant-Cooled Compressors Model Volts PH 4DK3R22M0-FSD 4DK3R22M0-TSE 4DK3R22M0-TSK 4DK3R22M0-TSK 4DK3R22ME-FSD 4DK3R22ME-TSE 4DK3R22ME-TSK 4DK3R22ME-TSK 4DK3R22ML-FSD 4DK3R22ML-TSE 4DK3R22ML-TSK 4DK3R22ML-TSK 4DK3S16ME-TSK 4DK3S16ME-TSK 4DK3S16ML-TSK 4DK3S16ML-TSK 4DL1A1500-ES8 4DL1A1500-ES8 4DL1A1500-FSD 4DL1A1500-TSE 4DL1A1500-TSK 4DL1A1500-TSK 460 575 208/230 460 460 575 208/230 460 460 575 208/230 460 208/230 460 208/230 460 200/220 380 460 575 208/230 460 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 Across the Line Max RLA LRA 40.6 34.4 82.1 41.1 40.6 34.4 82.1 52.9 40.6 34.4 82.1 52.9 65.7 32.1 NA NA NA NA 28.6 22.8 60 30 206 172 428 214 206 172 428 214 206 172 428 214 308 154 308 154 295 175 136 113 278 139 Part Winding Start Max RLA LRA 20.3 17.2 41.1 132 103 250 20.3 17.2 41.1 132 103 250 20.3 17.2 41.1 132 103 250 107 14.3 81.6 30 170 Winding Resistance Line to Line (Ohms) 0.524 1.538 0.132 0.528 0.524 1.538 0.132 0.528 0.524 1.538 0.132 0.528 0 0.179 0 0.179 0.546 0.182 0.84 1.28 0.208 0.832 See Section F Introduction for more information. FE20 Section_Fe.indd 20 3/4/2008 8:06:48 AM Electrical Data - Copelametic Large Refrigerant-Cooled Compressors Model Volts PH 4DL1F63K0-FSD 4DL1F63K0-TSK 4DL1F63K0-TSK 4DL3A1500-ES8 4DL3A1500-ES8 4DL3A1500-FSD 4DL3A1500-TSE 4DL3A1500-TSK 4DL3A1500-TSK 4DL3A150E-FSD 4DL3A150E-TSE 4DL3A150E-TSK 4DL3A150E-TSK 4DL3A150L-FSD 4DL3A150L-TSE 4DL3A150L-TSK 4DL3A150L-TSK 4DL3F63K0-ES8 4DL3F63K0-ES8 4DL3F63K0-FSD 4DL3F63K0-TSE 4DL3F63K0-TSK 460 208/230 460 200/220 380 460 575 208/230 460 460 575 208/230 460 460 575 208/230 460 200/220 380 460 575 208/230 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 Across the Line Max RLA LRA 28.6 60 30 NA NA 24.5 20.9 52.6 26.3 24.5 20.9 52.6 26.3 24.5 20.9 52.6 26.3 NA NA 24.5 20.9 52.6 136 278 139 295 175 136 113 278 139 136 113 278 139 136 113 278 139 295 175 136 113 278 Part Winding Start Max RLA LRA 14.3 30 81.6 170 107 12.3 81.6 26.3 170 12.3 81.6 26.3 170 12.3 81.6 26.3 170 107 12.3 81.6 26.3 170 Winding Resistance Line to Line (Ohms) 0.84 0.208 0.832 0.546 0.182 0.84 1.28 0.208 0.832 0.84 1.28 0.208 0.832 0.84 1.28 0.208 0.832 0.546 0.182 0.84 1.28 0.208 See Section F Introduction for more information. FE21 Section_Fe.indd 21 3/4/2008 8:06:48 AM Electrical Data - Copelametic Large Refrigerant-Cooled Compressors Model Volts PH 4DL3F63K0-TSK 4DL3F63KE-FSD 4DL3F63KE-TSE 4DL3F63KE-TSK 4DL3F63KE-TSK 4DL3F63KL-FSD 4DL3F63KL-TSE 4DL3F63KL-TSK 4DL3F63KL-TSK 4DL8A1500-TSK 4DL8A1500-TSK 4DN1A1000-FSD 4DN1A1000-TSE 4DN1A1000-TSK 4DN1A1000-TSK 4DN3A1000-FSD 4DN3A1000-TSE 4DN3A1000-TSK 4DN3A1000-TSK 4DN3A100E-FSD 4DN3A100E-TSE 4DN3A100L-FSD 460 460 575 208/230 460 460 575 208/230 460 208/230 460 460 575 208/230 460 460 575 208/230 460 460 575 460 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 Across the Line Max RLA LRA 26.3 24.5 20.9 52.6 26.3 24.5 20.9 52.6 26.3 52.6 26.3 25.7 20 53.6 26.8 20 17.4 42 21 20 17.4 20 139 136 113 278 139 136 113 278 139 278 139 110 106 240 120 115 106 240 120 115 106 115 Part Winding Start Max RLA LRA 12.3 81.6 26.3 170 12.3 81.6 26.3 170 26.3 170 12.9 66 26.8 140 10 70 21 140 10 70 10 70 Winding Resistance Line to Line (Ohms) 0.832 0.84 1.28 0.208 0.832 0.84 1.28 0.208 0.832 0.208 0.832 1.02 1.6 0.259 1.036 1.012 1.6 0.259 1.036 1.012 1.6 1.012 See Section F Introduction for more information. FE22 Section_Fe.indd 22 3/4/2008 8:06:49 AM Electrical Data - Copelametic Large Refrigerant-Cooled Compressors Model Volts PH 4DN3A100L-TSE 4DN3A1010-TSE 4DN3A1010-TSK 4DN3A1010-TSK 4DN3A101E-TSE 4DN3A101E-TSK 4DN3A101E-TSK 4DN3A101L-TSE 4DN3A101L-TSK 4DN3A101L-TSK 4DN3F47K0-TSE 4DN3F47K0-TSK 4DN3F47K0-TSK 4DN3F47KE-TSE 4DN3F47KE-TSK 4DN3F47KE-TSK 4DN3F47KL-TSE 4DN3F47KL-TSK 4DN3F47KL-TSK 4DP1A1500-ES8 4DP1A1500-ES8 4DP1A1500-FSD 575 575 208/230 460 575 208/230 460 575 208/230 460 575 208/230 460 575 208/230 460 575 208/230 460 200/220 380 460 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 Across the Line Max RLA LRA 17.4 17.4 42 21 17.4 45.6 22.8 17.4 45.6 22.8 17.4 42 21 17.4 45.6 22.8 17.4 45.6 22.8 NA NA 28.6 106 106 220 110 106 220 110 106 220 110 106 220 110 106 220 110 106 220 110 295 175 136 Part Winding Start Max RLA LRA 22.6 134 22.6 134 22.6 134 22.6 134 22.6 134 22.6 134 107 14.3 81.6 Winding Resistance Line to Line (Ohms) 1.6 1.6 0.244 0.976 1.6 0.244 0.976 1.6 0.244 0.976 1.6 0.244 0.976 1.6 0.244 0.976 1.6 0.244 0.976 0.546 0.182 0.84 See Section F Introduction for more information. FE23 Section_Fe.indd 23 3/4/2008 8:06:49 AM Electrical Data - Copelametic Large Refrigerant-Cooled Compressors Model Volts PH 4DP1A1500-TSK 4DP1A1500-TSK 4DP3A1500-FSD 4DP3A1500-TSE 4DP3A1500-TSK 4DP3A1500-TSK 4DP3A150E-FSD 4DP3A150E-TSE 4DP3A150E-TSK 4DP3A150E-TSK 4DP3A150L-FSD 4DP3A150L-TSE 4DP3A150L-TSK 4DP3A150L-TSK 4DP3F63K0-FSD 4DP3F63K0-TSE 4DP3F63K0-TSK 4DP3F63K0-TSK 4DP3F63KE-FSD 4DP3F63KE-TSE 4DP3F63KE-TSK 4DP3F63KE-TSK 208/230 460 460 575 208/230 460 460 575 208/230 460 460 575 208/230 460 460 575 208/230 460 460 575 208/230 460 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 Across the Line Max RLA LRA 60 30 24.5 20.9 52.6 26.3 24.5 20.9 52.6 26.3 24.5 20.9 52.6 26.3 24.5 20.9 52.6 26.3 24.5 20.9 52.6 26.3 278 139 136 113 278 139 136 113 278 139 136 113 278 139 136 113 278 139 136 113 278 139 Part Winding Start Max RLA LRA 30 170 12.3 81.6 26.3 170 12.3 81.6 26.3 170 12.3 81.6 26.3 170 12.3 81.6 26.3 170 12.3 81.6 26.3 170 Winding Resistance Line to Line (Ohms) 0.208 0.832 0.84 1.28 0.208 0.832 0.84 1.28 0.208 0.832 0.84 1.28 0.208 0.832 0.84 1.28 0.208 0.832 0.84 1.28 0.208 0.832 See Section F Introduction for more information. FE24 Section_Fe.indd 24 3/4/2008 8:06:50 AM Electrical Data - Copelametic Large Refrigerant-Cooled Compressors Model Volts PH 4DP3F63KL-FSD 4DP3F63KL-TSE 4DP3F63KL-TSK 4DP3F63KL-TSK 4DP8A1500-TSK 4DP8A1500-TSK 4DP8A150E-TSK 4DP8A150E-TSK 4DP8A150L-TSK 4DP8A150L-TSK 4DP8F63KE-TSK 4DP8F63KE-TSK 4DR1A2000-TSE 4DR1A2000-TSK 4DR1A2000-TSK 4DR1A3000-ES8 4DR1A3000-ES8 4DR1A3000-FSD 4DR1A3000-FXD 4DR1A3000-TSE 4DR1A3000-TSK 4DR1A3000-TSK 460 575 208/230 460 208/230 460 208/230 460 208/230 460 208/230 460 575 208/230 460 200/220 380 460 460 575 208/230 460 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 Across the Line Max RLA LRA 24.5 20.9 52.6 26.3 52.6 26.3 52.6 26.3 52.6 26.3 52.6 26.3 30 71.4 35.7 123.6 71.4 59 NA 42.9 117.9 58.9 136 113 278 139 278 139 278 139 278 139 278 139 135 346 173 500 289 235 235 200 470 235 Part Winding Start Max RLA LRA 12.3 81.6 26.3 170 26.3 170 26.3 170 26.3 170 26.3 170 15 35.7 81 208 164 29.5 21.5 59 141 141 130 292 Winding Resistance Line to Line (Ohms) 0.84 1.28 0.208 0.832 0.208 0.832 0.208 0.832 0.208 0.832 0.208 0.832 1.94 0.142 0.568 0.294 0.098 0.45 0.45 1.46 0.111 0.444 See Section F Introduction for more information. FE25 Section_Fe.indd 25 3/4/2008 8:06:50 AM Electrical Data - Copelametic Large Refrigerant-Cooled Compressors Model Volts PH 4DR1A3000-TXE 4DR1A3000-TXK 4DR1A3000-TXK 4DR1R28M0-FSD 4DR1R28M0-TSE 4DR1R28M0-TSK 4DR1R28M0-TSK 4DR3A200E-TSE 4DR3A200E-TSK 4DR3A200E-TSK 4DR3A200L-TSE 4DR3A200L-TSK 4DR3A200L-TSK 4DR3A270E-TSK 4DR3A270E-TSK 4DR3A270L-TSK 4DR3A270L-TSK 4DR3A3000-ES8 4DR3A3000-FSD 4DR3A3000-FXD 4DR3A3000-TSE 4DR3A3000-TSK 575 208/230 460 460 575 208/230 460 575 208/230 460 575 208/230 460 208/230 460 208/230 460 380 460 460 575 208/230 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 Across the Line Max RLA LRA NA NA NA 59 42.9 117.9 58.9 30 66 33 30 66 33 94 55 94 55 71.4 45 NA 39.3 94 200 470 235 235 200 470 235 135 346 173 135 346 173 470 235 470 235 289 235 235 200 470 Part Winding Start Max RLA LRA 130 292 29.5 21.5 59 141 130 292 15 33 81 208 15 33 81 208 47 292 47 292 22.5 141 141 130 292 19.7 47 Winding Resistance Line to Line (Ohms) 0.731 0.111 0.444 0.45 1.46 0.111 0.444 1.94 0.142 0.568 1.94 0.142 0.568 0.111 0.444 0.111 0.444 0.098 0.45 0.45 1.46 0.111 See Section F Introduction for more information. FE26 Section_Fe.indd 26 3/4/2008 8:06:50 AM Electrical Data - Copelametic Large Refrigerant-Cooled Compressors Model Volts PH 4DR3A3000-TSK 4DR3A3000-TXE 4DR3A3000-TXK 4DR3A3000-TXK 4DR3A300E-FSD 4DR3A300E-TSE 4DR3A300E-TSK 4DR3A300E-TSK 4DR3A300L-FSD 4DR3A300L-TSE 4DR3A300L-TSK 4DR3A300L-TSK 4DR3R19ME-TSK 4DR3R19ME-TSK 4DR3R28M0-ES8 4DR3R28M0-FSD 4DR3R28M0-TSE 4DR3R28M0-TSK 4DR3R28M0-TSK 4DR3R28ME-FSD 4DR3R28ME-TSE 4DR3R28ME-TSK 460 575 208/230 460 460 575 208/230 460 460 575 208/230 460 208/230 460 380 460 575 208/230 460 460 575 208/230 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 Across the Line Max RLA LRA 47 NA NA NA 45 39.3 94 55 45 39.3 94 55 66 33 71.4 45 39.3 94 47 45 39.3 94 235 200 470 235 235 200 470 235 235 200 470 235 346 173 289 235 200 470 235 235 200 470 Part Winding Start Max RLA LRA 130 292 22.5 19.7 47 141 130 292 22.5 19.7 47 141 130 292 33 208 22.5 19.7 47 141 130 292 22.5 19.7 47 141 130 292 Winding Resistance Line to Line (Ohms) 0.444 0.731 0.111 0.444 0.45 1.46 0.111 0.444 0.45 1.46 0.111 0.444 0.142 0.568 0.098 0.45 1.46 0.111 0.444 0.45 1.46 0.111 See Section F Introduction for more information. FE27 Section_Fe.indd 27 3/4/2008 8:06:51 AM Electrical Data - Copelametic Large Refrigerant-Cooled Compressors Model Volts PH 4DR3R28ME-TSK 4DR3R28ML-FSD 4DR3R28ML-TSE 4DR3R28ML-TSK 4DR3R28ML-TSK 4DR8A200E-TSK 4DR8A200E-TSK 4DS1A2200-FSD 4DS1A2200-TSE 4DS1A2200-TSK 4DS1A2200-TSK 4DS3A2200-ES8 4DS3A2200-ES8 4DS3A2200-FSD 4DS3A2200-TSE 4DS3A2200-TSK 4DS3A2200-TSK 4DS3A220E-FSD 4DS3A220E-TSE 4DS3A220E-TSK 4DS3A220E-TSK 4DS3A220L-FSD 460 460 575 208/230 460 208/230 460 460 575 208/230 460 200/220 380 460 575 208/230 460 460 575 208/230 460 460 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 Across the Line Max RLA LRA 55 45 39.3 94 55 66 33 32.9 28.6 71.4 35.7 68.9 40 33.9 24.1 66 33 33.9 24.1 66 33 33.9 235 235 200 470 235 346 173 180 135 374 187 405 235 180 135 374 187 180 135 374 187 180 Part Winding Start Max RLA LRA 22.5 19.7 47 141 130 292 33 208 16.5 14.3 35.7 108 81 222 134 17 12.1 33 108 81 222 17 12.1 33 108 81 222 17 108 Winding Resistance Line to Line (Ohms) 0.444 0.45 1.46 0.111 0.444 0.142 0.568 0.558 1.94 0.14 0.56 0.375 0.125 0.558 1.94 0.14 0.56 0.558 1.94 0.14 0.56 0.558 See Section F Introduction for more information. FE28 Section_Fe.indd 28 3/4/2008 8:06:51 AM Electrical Data - Copelametic Large Refrigerant-Cooled Compressors Model Volts PH 4DS3A220L-TSE 4DS3A220L-TSK 4DS3A220L-TSK 4DS3F76K0-FSD 4DS3F76K0-TSE 4DS3F76K0-TSK 4DS3F76K0-TSK 4DS3F76KE-FSD 4DS3F76KE-TSE 4DS3F76KE-TSK 4DS3F76KE-TSK 4DS3F76KL-FSD 4DS3F76KL-TSE 4DS3F76KL-TSK 4DS3F76KL-TSK 4DT1A2200-FSD 4DT1A2200-TSE 4DT1A2200-TSK 4DT1A2200-TSK 4DT1F76K0-TSK 4DT1F76K0-TSK 4DT3A2200-ES8 575 208/230 460 460 575 208/230 460 460 575 208/230 460 460 575 208/230 460 460 575 208/230 460 208/230 460 200/220 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 Across the Line Max RLA LRA 24.1 66 33 33.9 24.1 66 33 33.9 24.1 66 33 33.9 24.1 66 33 32.9 28.6 71.4 35.7 71.4 35.7 68.9 135 374 187 180 135 374 187 180 135 374 187 180 135 374 187 180 135 374 187 374 187 405 Part Winding Start Max RLA LRA 12.1 33 81 222 17 12.1 33 108 81 222 17 12.1 33 108 81 222 17 12.1 33 108 81 222 16.5 14.3 35.7 108 81 222 35.7 222 134 Winding Resistance Line to Line (Ohms) 1.94 0.14 0.56 0.558 1.94 0.14 0.56 0.558 1.94 0.14 0.56 0.558 1.94 0.14 0.56 0.558 1.94 0.14 0.56 0.14 0.56 0.375 See Section F Introduction for more information. FE29 Section_Fe.indd 29 3/4/2008 8:06:51 AM Electrical Data - Copelametic Large Refrigerant-Cooled Compressors Model Volts PH 4DT3A2200-ES8 4DT3A2200-FSD 4DT3A2200-TSE 4DT3A2200-TSK 4DT3A2200-TSK 4DT3A220E-FSD 4DT3A220E-TSE 4DT3A220E-TSK 4DT3A220E-TSK 4DT3A220L-FSD 4DT3A220L-TSE 4DT3A220L-TSK 4DT3A220L-TSK 4DT3A2510-ESX 4DT3A2510-ESX 4DT3A251E-ESX 4DT3A251E-ESX 4DT3A251L-ESX 4DT3A251L-ESX 4DT3F76K0-ES8 4DT3F76K0-ES8 4DT3F76K0-FSD 380 460 575 208/230 460 460 575 208/230 460 460 575 208/230 460 220 380 220 380 220 380 200/220 380 460 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 Across the Line Max RLA LRA 40 33.9 24.1 66 33 33.9 24.1 66 33 33.9 24.1 66 33 72.1 41.9 89.3 49.6 89.3 49.6 68.9 40 33.9 235 180 135 374 187 180 135 374 187 180 135 374 187 405 235 405 235 405 235 405 235 180 Part Winding Start Max RLA LRA 17 12.1 33 108 81 222 17 12.1 33 108 81 222 17 12.1 33 108 81 222 134 134 134 134 17 108 Winding Resistance Line to Line (Ohms) 0.125 0.558 1.94 0.14 0.56 0.558 1.94 0.14 0.56 0.558 1.94 0.14 0.56 0.375 0.125 0.375 0.125 0.375 0.125 0.375 0.125 0.558 See Section F Introduction for more information. FE30 Section_Fe.indd 30 3/4/2008 8:06:52 AM Electrical Data - Copelametic Large Refrigerant-Cooled Compressors Model Volts PH 4DT3F76K0-TSE 4DT3F76K0-TSK 4DT3F76K0-TSK 4DT3F76KE-FSD 4DT3F76KE-TSE 4DT3F76KE-TSK 4DT3F76KE-TSK 4DT3F76KL-FSD 4DT3F76KL-TSE 4DT3F76KL-TSK 4DT3F76KL-TSK 4DT8A220E-TSE 4RA3-1000-TSE 4RA3-1000-TSK 4RA3-1000-TSK 4RA3-100A-TSK 4RA3-100A-TSK 4RA3-100L-TSK 4RA3-100L-TSK 4RA3-2000-ES8 4RA3-2000-ES8 4RA3-2000-FSD 575 208/230 460 460 575 208/230 460 460 575 208/230 460 575 575 208/230 460 208/230 460 208/230 460 200/220 380 460 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 Across the Line Max RLA LRA 24.1 66 33 33.9 24.1 66 33 33.9 24.1 66 33 24.1 19.8 54.9 27.4 54.9 27.4 54.9 27.4 68.4 38.9 32.4 135 374 187 180 135 374 187 180 135 374 187 135 106 240 120 240 120 240 120 335 189 135 Part Winding Start Max RLA LRA 12.1 33 81 222 17 12.1 33 108 81 222 17 12.1 33 108 81 222 12.1 81 27.4 140 27.4 140 27.4 140 113 16.2 82 Winding Resistance Line to Line (Ohms) 1.94 0.14 0.56 0.558 1.94 0.14 0.56 0.558 1.94 0.14 0.56 1.94 1.6 0.259 1.036 0.259 1.036 0.259 1.036 0.483 0.161 0.757 See Section F Introduction for more information. FE31 Section_Fe.indd 31 3/4/2008 8:06:52 AM Electrical Data - Copelametic Large Refrigerant-Cooled Compressors Model 4RA3-2000-TSE 4RA3-2000-TSK 4RA3-2000-TSK 4RA3-200A-TSK 4RA3-200A-TSK 4RA4-1000-TSE 4RA4-1000-TSK 4RA4-1000-TSK 4RA4-2000-TSE 4RA4-2000-TSK 4RA4-2000-TSK 4RA4-200A-TSK 4RA4-200A-TSK 4RA4-200L-TSK 4RA4-200L-TSK 4RE2-1000-TSE 4RE2-1000-TSK 4RE2-1000-TSK 4RE2-2000-ES8 4RE2-2000-ES8 4RE2-2000-FSD 4RE2-2000-TSE Volts PH 575 208/230 460 208/230 460 575 208/230 460 575 208/230 460 208/230 460 208/230 460 575 208/230 460 200/220 380 460 575 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 Across the Line Max RLA LRA 29.2 71.4 35.7 71.4 35.7 19.8 54.9 27.4 29.2 71.4 35.7 71.4 35.7 71.4 35.7 19.8 54.9 27.4 68.4 38.9 32.4 29.2 135 308 154 308 154 106 240 120 135 308 154 308 154 308 154 106 240 120 335 189 135 135 Part Winding Start Max RLA LRA 14.6 35.7 74 188 35.7 188 27.4 140 14.6 35.7 74 188 35.7 188 35.7 188 27.4 140 113 16.2 14.6 82 74 Winding Resistance Line to Line (Ohms) 2.2 0.173 0.69 0.173 0.69 1.6 0.259 1.036 2.2 0.173 0.69 0.173 0.69 0.173 0.69 1.6 0.259 1.036 0.483 0.161 0.757 2.2 See Section F Introduction for more information. FE32 Section_Fe.indd 32 3/4/2008 8:06:53 AM Electrical Data - Copelametic Large Refrigerant-Cooled Compressors Model Volts PH 4RE2-2000-TSK 4RE2-2000-TSK 4RE2-200A-FSD 4RE2-200A-TSK 4RE2-200A-TSK 4RE4-2000-TSK 4RE4-2000-TSK 4RE5-2000-TSK 4RE5-2000-TSK 4RH1-1500-TSE 4RH1-1500-TSK 4RH1-1500-TSK 4RH1-150A-TSK 4RH1-150A-TSK 4RH1-2500-ES8 4RH1-2500-ES8 4RH1-2500-FSD 4RH1-2500-TSE 4RH1-2500-TSK 4RH1-2500-TSK 4RH1-250A-FSD 4RH1-250A-TSK 208/230 460 460 208/230 460 208/230 460 208/230 460 575 208/230 460 208/230 460 200/220 380 460 575 208/230 460 460 208/230 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 Across the Line Max RLA LRA 71.4 35.7 32.4 71.4 35.7 71.4 35.7 71.4 35.7 24.1 63 31.5 63 31.5 99.1 59.9 45 34.9 88.6 44.3 45 88.6 308 154 135 308 154 308 154 308 154 113 278 139 278 139 438 251 165 160 428 214 165 428 Part Winding Start Max RLA LRA 35.7 188 16.2 35.7 82 188 35.7 188 35.7 188 31.5 170 31.5 170 142 22.5 17.4 44.3 100 113 250 22.5 44.3 100 250 Winding Resistance Line to Line (Ohms) 0.173 0.69 0.757 0.173 0.69 0.173 0.69 0.173 0.69 1.255 0.208 0.832 0.208 0.832 0.345 0.115 0.575 1.76 0.132 0.528 0.575 0.132 See Section F Introduction for more information. FE33 Section_Fe.indd 33 3/4/2008 8:06:53 AM Electrical Data - Copelametic Large Refrigerant-Cooled Compressors Model Volts PH 4RH1-250A-TSK 4RH1-250L-TSK 4RH1-250L-TSK 4RH2-1500-TSK 4RH2-1500-TSK 4RH5-1500-TSK 4RH5-1500-TSK 4RJ1-3000-ES8 4RJ1-3000-ES8 4RJ1-3000-FSD 4RJ1-3000-TSE 4RJ1-3000-TSK 4RJ1-3000-TSK 4RJ1-300A-FSD 4RJ1-300A-TSK 4RJ1-300A-TSK 4RJ2-3000-ES8 4RJ2-3000-ES8 4RJ2-3000-FSD 4RJ2-3000-TSE 4RJ2-3000-TSK 4RJ2-3000-TSK 460 208/230 460 208/230 460 208/230 460 200/220 380 460 575 208/230 460 460 208/230 460 200/220 380 460 575 208/230 460 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 Across the Line Max RLA LRA 44.3 88.6 44.3 63 31.5 63 31.5 119.3 68.4 59 42.1 96.4 50.7 59 96.4 50.7 119.3 68.4 59 42.1 96.4 50.7 214 428 214 278 139 278 139 500 289 200 200 470 235 200 470 235 500 289 200 200 470 235 Part Winding Start Max RLA LRA 44.3 250 31.5 170 31.5 170 164 29.5 21.1 51 121 130 292 29.5 51 121 292 164 29.5 21.1 51 121 130 292 Winding Resistance Line to Line (Ohms) 0.528 0.132 0.528 0.208 0.832 0.208 0.832 0.294 0.098 0.475 1.46 0.108 0.43 0.475 0.108 0.43 0.294 0.098 0.475 1.46 0.108 0.43 See Section F Introduction for more information. FE34 Section_Fe.indd 34 3/4/2008 8:06:53 AM Electrical Data - Copelametic Large Refrigerant-Cooled Compressors Model Volts PH 4RJ2-300A-TSK 4RJ2-300A-TSK 4RK2-1500-TSE 4RK2-1500-TSK 4RK2-1500-TSK 4RK2-2500-ES8 4RK2-2500-ES8 4RK2-2500-FSD 4RK2-2500-TSE 4RK2-2500-TSK 4RK2-2500-TSK 4RK2-250A-FSD 4RK2-250A-TSE 4RK2-250A-TSK 4RK2-250A-TSK 4RK5-2500-TSK 4RK5-2500-TSK 4RL1-1500-TSE 4RL1-1500-TSK 4RL1-1500-TSK 4RL1-150A-TSK 4RL1-150A-TSK 208/230 460 575 208/230 460 200/220 380 460 575 208/230 460 460 575 208/230 460 208/230 460 575 208/230 460 208/230 460 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 Across the Line Max RLA LRA 96.4 50.7 24.1 63 31.5 102.5 59.9 45 34.9 88.6 44.3 45 34.9 88.6 44.3 88.6 44.3 24.1 62.6 31.4 62.6 31.4 470 235 113 278 139 438 251 165 160 428 214 165 160 428 214 428 214 113 278 139 278 139 Part Winding Start Max RLA LRA 51 292 31.5 170 142 22.5 17.4 44.3 100 113 250 22.5 17.4 44.3 100 113 250 44.3 250 31.3 170 31.3 170 Winding Resistance Line to Line (Ohms) 0.108 0.43 1.255 0.208 0.832 0.345 0.115 0.575 1.76 0.132 0.528 0.575 1.76 0.132 0.528 0.132 0.528 1.255 0.208 0.832 0.208 0.832 See Section F Introduction for more information. FE35 Section_Fe.indd 35 3/4/2008 8:06:54 AM Electrical Data - Copelametic Large Refrigerant-Cooled Compressors Model Volts PH 4RL1-1900-TSU 4RL2-1500-TSE 4RL2-1500-TSK 4RL2-1500-TSK 4RL2-150A-TSK 4RL2-150A-TSK 4RL5-1900-TSU 4RR1-3000-ES8 4RR1-3000-ES8 4RR1-3000-FSD 4RR1-3000-TSE 4RR1-3000-TSK 4RR1-3000-TSK 4RR1-300A-FSD 4RR1-300A-TSK 4RR1-300A-TSK 4RR2-3000-ES8 4RR2-3000-ES8 4RR2-3000-FSD 4RR2-3000-TSE 4RR2-3000-TSK 4RR2-3000-TSK 200 575 208/230 460 208/230 460 200 200/220 380 460 575 208/230 460 460 208/230 460 200/220 380 460 575 208/230 460 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 Across the Line Max RLA LRA NA 24.1 62.6 31.4 62.6 31.4 NA 119.3 68.4 59 42.1 101.4 50.7 59 101.4 50.7 119.3 68.4 59 42.1 101.4 50.7 350 113 278 139 278 139 350 500 289 200 200 470 235 200 470 235 500 289 200 200 470 235 Part Winding Start Max RLA LRA 32.5 205 31.3 170 31.3 170 32.5 205 164 29.5 21.1 51 121 130 292 29.5 51 121 292 164 29.5 21.1 51 121 130 292 Winding Resistance Line to Line (Ohms) 0.133 1.255 0.208 0.832 0.208 0.832 0.133 0.294 0.098 0.475 1.46 0.108 0.43 0.475 0.108 0.43 0.294 0.098 0.475 1.46 0.108 0.43 See Section F Introduction for more information. FE36 Section_Fe.indd 36 3/4/2008 8:06:54 AM Electrical Data - Copelametic Large Refrigerant-Cooled Compressors Model Volts PH 4RR2-300A-TSK 4RR2-300A-TSK 6DB3A3000-FSD 6DB3A3000-TSE 6DB3A3000-TSK 6DB3A3000-TSK 6DB3A300E-FSD 6DB3A300E-TSE 6DB3A300E-TSK 6DB3A300E-TSK 6DB3A300L-FSD 6DB3A300L-TSE 6DB3A300L-TSK 6DB3A300L-TSK 6DB3R32M0-FSD 6DB3R32M0-TSE 6DB3R32M0-TSK 6DB3R32M0-TSK 6DB3R32ME-FSD 6DB3R32ME-TSE 6DB3R32ME-TSK 6DB3R32ME-TSK 208/230 460 460 575 208/230 460 460 575 208/230 460 460 575 208/230 460 460 575 208/230 460 460 575 208/230 460 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 Across the Line Max RLA LRA 101.4 50.7 50 40 105 52.5 50 40 134.3 67.1 50 40 134.3 67.1 50 40 105 52.5 50 40 134.3 67.1 470 235 260 230 565 283 260 230 565 283 260 230 565 283 260 230 565 283 260 230 565 283 Part Winding Start Max RLA LRA 51 292 25 20 52.5 156 138 340 25 20 52.5 156 138 340 25 20 52.5 156 138 340 25 20 52.5 156 138 340 25 20 52.5 156 138 340 Winding Resistance Line to Line (Ohms) 0.108 0.43 0.39 1.16 0.087 0.348 0.39 1.16 0.087 0.348 0.39 1.16 0.087 0.348 0.39 1.16 0.087 0.348 0.39 1.16 0.087 0.348 See Section F Introduction for more information. FE37 Section_Fe.indd 37 3/4/2008 8:06:54 AM Electrical Data - Copelametic Large Refrigerant-Cooled Compressors Model Volts PH 6DB3R32ML-FSD 6DB3R32ML-TSE 6DB3R32ML-TSK 6DB3R32ML-TSK 6DC1A2700-TSE 6DC1A2700-TSK 6DC1A2700-TSK 6DC3A2700-ES8 6DC3A2700-ES8 6DC3A2700-FSD 6DC3A2700-TSE 6DC3A2700-TSK 6DC3A2700-TSK 6DC3A270E-FSD 6DC3A270E-TSE 6DC3A270E-TSK 6DC3A270E-TSK 6DC3A270L-FSD 6DC3A270L-TSE 6DC3A270L-TSK 6DC3A270L-TSK 6DC3F93K0-FSD 460 575 208/230 460 575 208/230 460 200/220 380 460 575 208/230 460 460 575 208/230 460 460 575 208/230 460 460 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 Across the Line Max RLA LRA 50 40 134.3 67.1 35 89.3 44.6 82.5 47.9 41.6 32.5 80.7 40.4 41.6 32.5 80.7 40.4 41.6 32.5 80.7 40.4 41.6 260 230 565 283 172 450 225 445 260 218 172 450 225 218 172 450 225 218 172 450 225 218 Part Winding Start Max RLA LRA 25 20 52.5 156 138 340 17.5 44.7 103 263 141 20.8 16.3 40.4 131 103 263 20.8 16.3 40.4 131 103 263 20.8 16.3 40.4 131 103 263 20.8 131 Winding Resistance Line to Line (Ohms) 0.39 1.16 0.087 0.348 1.538 0.114 0.456 0.336 0.112 0.457 1.538 0.114 0.456 0.457 1.538 0.114 0.456 0.457 1.538 0.114 0.456 0.457 See Section F Introduction for more information. FE38 Section_Fe.indd 38 3/4/2008 8:06:55 AM Electrical Data - Copelametic Large Refrigerant-Cooled Compressors Model Volts PH 6DC3F93K0-TSE 6DC3F93K0-TSK 6DC3F93K0-TSK 6DC3F93KE-FSD 6DC3F93KE-TSE 6DC3F93KE-TSK 6DC3F93KE-TSK 6DC3F93KL-FSD 6DC3F93KL-TSE 6DC3F93KL-TSK 6DC3F93KL-TSK 6DD1A2700-FSD 6DD1A2700-TSK 6DD1A2700-TSK 6DD3A2700-ES8 6DD3A2700-ES8 6DD3A2700-FSD 6DD3A2700-TSE 6DD3A2700-TSK 6DD3A2700-TSK 6DD3A270E-FSD 6DD3A270E-TSE 575 208/230 460 460 575 208/230 460 460 575 208/230 460 460 208/230 460 200/220 380 460 575 208/230 460 460 575 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 Across the Line Max RLA LRA 32.5 80.7 40.4 41.6 32.5 80.7 40.4 41.6 32.5 80.7 40.4 42.9 89.3 44.6 82.5 47.9 41.6 32.5 80.7 40.4 41.6 32.5 172 450 225 218 172 450 225 218 172 450 225 218 450 225 445 260 218 172 450 225 218 172 Part Winding Start Max RLA LRA 16.3 40.4 103 263 20.8 16.3 40.4 131 103 263 20.8 16.3 40.4 131 103 263 21.5 44.7 131 263 141 20.8 16.3 40.4 131 103 263 20.8 16.3 131 103 Winding Resistance Line to Line (Ohms) 1.538 0.114 0.456 0.457 1.538 0.114 0.456 0.457 1.538 0.114 0.456 0.457 0.114 0.456 0.336 0.112 0.457 1.538 0.114 0.456 0.457 1.538 See Section F Introduction for more information. FE39 Section_Fe.indd 39 3/4/2008 8:06:55 AM Electrical Data - Copelametic Large Refrigerant-Cooled Compressors Model Volts PH 6DD3A270E-TSK 6DD3A270E-TSK 6DD3A270L-FSD 6DD3A270L-TSE 6DD3A270L-TSK 6DD3A270L-TSK 6DD3F93K0-FSD 6DD3F93K0-TSE 6DD3F93K0-TSK 6DD3F93K0-TSK 6DD3F93KE-FSD 6DD3F93KE-TSE 6DD3F93KE-TSK 6DD3F93KE-TSK 6DD3F93KL-FSD 6DD3F93KL-TSE 6DD3F93KL-TSK 6DD3F93KL-TSK 6DE1A3000-ES8 6DE1A3000-ES8 6DE1A3000-TSK 6DE1A3000-TSK 208/230 460 460 575 208/230 460 460 575 208/230 460 460 575 208/230 460 460 575 208/230 460 200/220 380 208/230 460 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 Across the Line Max RLA LRA 80.7 40.4 41.6 32.5 80.7 40.4 41.6 32.5 80.7 40.4 41.6 32.5 80.7 40.4 41.6 32.5 80.7 40.4 95.9 55.6 110.9 55.5 450 225 218 172 450 225 218 172 450 225 218 172 450 225 218 172 450 225 500 289 470 235 Part Winding Start Max RLA LRA 40.4 263 20.8 16.3 40.4 131 103 263 20.8 16.3 40.4 131 103 263 20.8 16.3 40.4 131 103 263 20.8 16.3 40.4 131 103 263 164 55.5 292 Winding Resistance Line to Line (Ohms) 0.114 0.456 0.457 1.538 0.114 0.456 0.457 1.538 0.114 0.456 0.457 1.538 0.114 0.456 0.457 1.538 0.114 0.456 0.294 0.098 0.111 0.444 See Section F Introduction for more information. FE40 Section_Fe.indd 40 3/4/2008 8:06:56 AM Electrical Data - Copelametic Large Refrigerant-Cooled Compressors Model Volts PH 6DE3A3000-FSD 6DE3A3000-TSE 6DE3A3000-TSK 6DE3A3000-TSK 6DE3A300E-FSD 6DE3A300E-TSE 6DE3A300E-TSK 6DE3A300E-TSK 6DE3A300L-FSD 6DE3A300L-TSE 6DE3A300L-TSK 6DE3A300L-TSK 6DE3F11M0-FSD 6DE3F11M0-TSE 6DE3F11M0-TSK 6DE3F11M0-TSK 6DE3F11ME-FSD 6DE3F11ME-TSE 6DE3F11ME-TSK 6DE3F11ME-TSK 6DE3F11ML-FSD 6DE3F11ML-TSE 460 575 208/230 460 460 575 208/230 460 460 575 208/230 460 460 575 208/230 460 460 575 208/230 460 460 575 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 Across the Line Max RLA LRA 42.9 39.6 95.6 47.8 42.9 39.6 95.6 47.8 42.9 39.6 95.6 47.8 42.9 39.6 95.6 47.8 42.9 39.6 95.6 47.8 42.9 39.6 235 200 470 235 235 200 470 235 235 200 470 235 235 200 470 235 235 200 470 235 235 200 Part Winding Start Max RLA LRA 21.4 19.8 47.8 141 130 292 21.4 19.8 47.8 141 130 292 21.4 19.8 47.8 141 130 292 21.4 19.8 47.8 141 130 292 21.4 19.8 47.8 141 130 292 21.4 19.8 141 130 Winding Resistance Line to Line (Ohms) 0.45 1.46 0.111 0.444 0.45 1.46 0.111 0.444 0.45 1.46 0.111 0.444 0.45 1.46 0.111 0.444 0.45 1.46 0.111 0.444 0.45 1.46 See Section F Introduction for more information. FE41 Section_Fe.indd 41 3/4/2008 8:06:56 AM Electrical Data - Copelametic Large Refrigerant-Cooled Compressors Model Volts PH 6DE3F11ML-TSK 6DE3F11ML-TSK 6DF1A3000-ES8 6DF1A3000-ES8 6DF1A3000-FSD 6DF1A3000-TSK 6DF1A3000-TSK 6DF3A3000-FSD 6DF3A3000-TSE 6DF3A3000-TSK 6DF3A3000-TSK 6DF3A300E-FSD 6DF3A300E-TSE 6DF3A300E-TSK 6DF3A300E-TSK 6DF3A300L-FSD 6DF3A300L-TSE 6DF3A300L-TSK 6DF3A300L-TSK 6DF3F11M0-FSD 6DF3F11M0-TSE 6DF3F11M0-TSK 208/230 460 200/220 380 460 208/230 460 460 575 208/230 460 460 575 208/230 460 460 575 208/230 460 460 575 208/230 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 Across the Line Max RLA LRA 95.6 47.8 95.9 55.6 53.6 110.9 55.5 42.9 39.6 95.6 47.8 42.9 39.6 95.6 47.8 42.9 39.6 95.6 47.8 42.9 39.6 95.6 470 235 500 289 235 470 235 235 200 470 235 235 200 470 235 235 200 470 235 235 200 470 Part Winding Start Max RLA LRA 47.8 292 164 26.8 55.5 141 292 21.4 19.8 47.8 141 130 292 21.4 19.8 47.8 141 130 292 21.4 19.8 47.8 141 130 292 21.4 19.8 47.8 141 130 292 Winding Resistance Line to Line (Ohms) 0.111 0.444 0.294 0.098 0.45 0.111 0.444 0.45 1.46 0.111 0.444 0.45 1.46 0.111 0.444 0.45 1.46 0.111 0.444 0.45 1.46 0.111 See Section F Introduction for more information. FE42 Section_Fe.indd 42 3/4/2008 8:06:56 AM Electrical Data - Copelametic Large Refrigerant-Cooled Compressors Model Volts PH 6DF3F11M0-TSK 6DF3F11ME-FSD 6DF3F11ME-TSE 6DF3F11ME-TSK 6DF3F11ME-TSK 6DF3F11ML-FSD 6DF3F11ML-TSE 6DF3F11ML-TSK 6DF3F11ML-TSK 6DG3A3500-ES8 6DG3A3500-ES8 6DG3A3500-FSD 6DG3A3500-FSU 6DG3A3500-FXD 6DG3A3500-FXU 6DG3A3500-TSE 6DG3A3500-TSN 6DG3A3500-TSN 6DG3A3500-TXE 6DG3A3500-TXN 6DG3A3500-TXN 6DG3A350E-FSD 460 460 575 208/230 460 460 575 208/230 460 200/220 380 460 200 460 200 575 230 460 575 230 460 460 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 Across the Line Max RLA LRA 47.8 42.9 39.6 95.6 47.8 42.9 39.6 95.6 47.8 NA NA 66 135 NA NA 46 125 62.5 NA NA NA 66 235 235 200 470 235 235 200 470 235 633 365 315 650 315 650 245 594 297 245 594 297 315 Part Winding Start Max RLA LRA 21.4 19.8 47.8 141 130 292 21.4 19.8 47.8 141 130 292 212 33 67.5 23 62.5 195 400 195 400 152 340 152 340 33 195 Winding Resistance Line to Line (Ohms) 0.444 0.45 1.46 0.111 0.444 0.45 1.46 0.111 0.444 0.225 0.075 0.32 0.069 0.32 0.069 1.016 0.085 0.34 0.508 0.085 0.34 0.32 See Section F Introduction for more information. FE43 Section_Fe.indd 43 3/4/2008 8:06:57 AM Electrical Data - Copelametic Large Refrigerant-Cooled Compressors Model Volts PH 6DG3A350E-FSU 6DG3A350E-TSE 6DG3A350E-TSN 6DG3A350E-TSN 6DG3A350L-FSD 6DG3A350L-FSU 6DG3A350L-TSE 6DG3A350L-TSN 6DG3A350L-TSN 6DG3R37M0-ES8 6DG3R37M0-ES8 6DG3R37M0-FSD 6DG3R37M0-FSU 6DG3R37M0-TSE 6DG3R37M0-TSN 6DG3R37M0-TSN 6DG3R37ME-FSD 6DG3R37ME-FSU 6DG3R37ME-TSE 6DG3R37ME-TSN 6DG3R37ME-TSN 6DG3R37ML-FSD 200 575 230 460 460 200 575 230 460 200/220 380 460 200 575 230 460 460 200 575 230 460 460 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 Across the Line Max RLA LRA 135 46 168.6 84.3 66 135 46 168.6 84.3 NA NA 66 135 46 125 62.5 66 135 46 168.6 84.3 66 650 245 594 297 315 650 245 594 297 633 365 315 650 245 594 297 315 650 245 594 297 315 Part Winding Start Max RLA LRA 67.5 23 62.5 400 152 340 33 67.5 23 62.5 195 400 152 340 212 33 67.5 23 62.5 195 400 152 340 33 67.5 23 62.5 195 400 152 340 33 195 Winding Resistance Line to Line (Ohms) 0.069 1.016 0.085 0.34 0.32 0.069 1.016 0.085 0.34 0.225 0.075 0.32 0.069 1.016 0.085 0.34 0.32 0.069 1.016 0.085 0.34 0.32 See Section F Introduction for more information. FE44 Section_Fe.indd 44 3/4/2008 8:06:57 AM Electrical Data - Copelametic Large Refrigerant-Cooled Compressors Model Volts PH 6DG3R37ML-FSU 6DG3R37ML-TSE 6DG3R37ML-TSN 6DG3R37ML-TSN 6DG8A3500-TSE 6DG8A3500-TSN 6DG8A3500-TSN 6DH1A2000-FSD 6DH1A2000-TSE 6DH1A2000-TSK 6DH1A2000-TSK 6DH1A3500-ES8 6DH1A3500-ES8 6DH1A3500-FSD 6DH1A3500-FXD 6DH1A3500-TSE 6DH1A3500-TSK 6DH1A3500-TSK 6DH1A3500-TXE 6DH1A3500-TXK 6DH1A3500-TXK 6DH1R35M0-ES8 200 575 230 460 575 230 460 460 575 208/230 460 200/220 380 460 460 575 208/230 460 575 208/230 460 200/220 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 Across the Line Max RLA LRA 135 46 168.6 84.3 46 125 62.5 39.3 30 75 37.5 146.7 84.1 67.5 NA 50 125 62.5 NA NA NA 146.7 650 245 594 297 245 594 297 173 135 346 173 633 365 260 260 230 565 283 230 565 283 633 Part Winding Start Max RLA LRA 67.5 23 62.5 400 152 340 23 62.5 152 340 19.7 15 37.5 104 81 208 212 33.8 25 62.5 156 156 138 340 138 340 212 Winding Resistance Line to Line (Ohms) 0.069 1.016 0.085 0.34 1.016 0.085 0.34 0.603 1.94 0.142 0.568 0.225 0.075 0.4 0.4 1.076 0.088 0.352 0.538 0.088 0.352 0.225 See Section F Introduction for more information. FE45 Section_Fe.indd 45 3/4/2008 8:06:57 AM Electrical Data - Copelametic Large Refrigerant-Cooled Compressors Model Volts PH 6DH1R35M0-ES8 6DH1R35M0-FSD 6DH1R35M0-TSK 6DH1R35M0-TSK 6DH3A200E-TSE 6DH3A200E-TSK 6DH3A200E-TSK 6DH3A200L-TSE 6DH3A200L-TSK 6DH3A200L-TSK 6DH3A3500-FSD 6DH3A3500-TSE 6DH3A3500-TSK 6DH3A3500-TSK 6DH3A350E-FSD 6DH3A350E-TSE 6DH3A350E-TSK 6DH3A350E-TSK 6DH3A350L-FSD 6DH3A350L-TSE 6DH3A350L-TSK 6DH3A350L-TSK 380 460 208/230 460 575 208/230 460 575 208/230 460 460 575 208/230 460 460 575 208/230 460 460 575 208/230 460 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 Across the Line Max RLA LRA 84.1 67.5 125 62.5 30 75 37.5 30 75 37.5 62.6 42.5 125.1 62.6 62.6 42.5 147.1 73.6 62.6 42.5 147.1 73.6 365 260 565 283 135 346 173 135 346 173 260 230 565 283 260 230 565 283 260 230 565 283 Part Winding Start Max RLA LRA 33.8 62.5 156 340 15 37.5 81 208 15 37.5 81 208 31.3 21.3 62.6 156 138 340 31.3 21.3 62.6 156 138 340 31.3 21.3 62.6 156 138 340 Winding Resistance Line to Line (Ohms) 0.075 0.4 0.088 0.352 1.94 0.142 0.568 1.94 0.142 0.568 0.39 1.16 0.087 0.348 0.39 1.16 0.087 0.348 0.39 1.16 0.087 0.348 See Section F Introduction for more information. FE46 Section_Fe.indd 46 3/4/2008 8:06:58 AM Electrical Data - Copelametic Large Refrigerant-Cooled Compressors Model Volts PH 6DH3R23ME-TSK 6DH3R23ME-TSK 6DH3R23ML-TSK 6DH3R23ML-TSK 6DH3R35M0-FSD 6DH3R35M0-TSE 6DH3R35M0-TSK 6DH3R35M0-TSK 6DH3R35ME-FSD 6DH3R35ME-TSE 6DH3R35ME-TSK 6DH3R35ME-TSK 6DH3R35ML-FSD 6DH3R35ML-TSE 6DH3R35ML-TSK 6DH3R35ML-TSK 6DJ1A4000-ES8 6DJ1A4000-ES8 6DJ1A4000-FSD 6DJ1A4000-FSU 6DJ1A4000-FXU 6DJ1A4000-TSE 208/230 460 208/230 460 460 575 208/230 460 460 575 208/230 460 460 575 208/230 460 200/220 380 460 200 200 575 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 Across the Line Max RLA LRA 75 37.5 75 37.5 62.6 42.5 125.1 62.6 62.6 42.5 147.1 73.6 62.6 42.5 147.1 73.6 164.1 96.9 69.3 170 NA 57.1 346 173 346 173 260 230 565 283 260 230 565 283 260 230 565 283 633 365 300 660 660 235 Part Winding Start Max RLA LRA 37.5 208 37.5 208 31.3 21.3 62.6 156 138 340 31.3 21.3 62.6 156 138 340 31.3 21.3 62.6 156 138 340 212 34.7 85 28.6 170 400 400 135 Winding Resistance Line to Line (Ohms) 0.142 0.568 0.142 0.568 0.39 1.16 0.087 0.348 0.39 1.16 0.087 0.348 0.39 1.16 0.087 0.348 0.225 0.075 0.352 0.067 0.067 1.14 See Section F Introduction for more information. FE47 Section_Fe.indd 47 3/4/2008 8:06:58 AM Electrical Data - Copelametic Large Refrigerant-Cooled Compressors Model Volts PH 6DJ1A4000-TSN 6DJ1A4000-TSN 6DJ1A4000-TXE 6DJ1A4000-TXN 6DJ1A4000-TXN 6DJ1R40M0-FSD 6DJ1R40M0-TSE 6DJ1R40M0-TSN 6DJ1R40M0-TSN 6DJ3A300E-TSE 6DJ3A300E-TSK 6DJ3A300E-TSK 6DJ3A300L-TSE 6DJ3A300L-TSK 6DJ3A300L-TSK 6DJ3A4000-FSD 6DJ3A4000-FSU 6DJ3A4000-FXD 6DJ3A4000-FXU 6DJ3A4000-TSE 6DJ3A4000-TSN 6DJ3A4000-TSN 230 460 575 230 460 460 575 230 460 575 208/230 460 575 208/230 460 460 200 460 200 575 230 460 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 Across the Line Max RLA LRA 141.4 70.7 NA NA NA 69.3 57.1 141.4 70.7 40 100 50 40 100 50 70 150 NA NA 53.5 141.4 70.7 594 297 235 594 297 300 235 594 297 200 470 235 200 470 235 315 754 315 754 245 594 297 Part Winding Start Max RLA LRA 70.5 340 135 340 34.7 28.6 70.5 170 135 340 20 50 130 292 20 50 130 292 35 75 195 463 195 463 152 340 26.75 71 Winding Resistance Line to Line (Ohms) 0.085 0.34 0.569 0.085 0.34 0.352 1.14 0.085 0.34 1.46 0.111 0.444 1.46 0.111 0.444 0.32 0.059 0.32 0.059 1.016 0.085 0.34 See Section F Introduction for more information. FE48 Section_Fe.indd 48 3/4/2008 8:06:59 AM Electrical Data - Copelametic Large Refrigerant-Cooled Compressors Model Volts PH 6DJ3A4000-TXE 6DJ3A4000-TXN 6DJ3A4000-TXN 6DJ3A400E-FSD 6DJ3A400E-FSU 6DJ3A400E-TSE 6DJ3A400E-TSN 6DJ3A400E-TSN 6DJ3A400L-FSD 6DJ3A400L-FSU 6DJ3A400L-TSE 6DJ3A400L-TSN 6DJ3A400L-TSN 6DJ3R28ME-TSE 6DJ3R28ME-TSK 6DJ3R28ME-TSK 6DJ3R28ML-TSE 6DJ3R28ML-TSK 6DJ3R28ML-TSK 6DJ3R40M0-FSD 6DJ3R40M0-FSU 6DJ3R40M0-TSE 575 230 460 460 200 575 230 460 460 200 575 230 460 575 208/230 460 575 208/230 460 460 200 575 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 Across the Line Max RLA LRA NA NA NA 86.4 150 53.5 141.4 70.7 86.4 150 53.5 141.4 70.7 40 100 50 40 100 50 70 150 53.5 245 594 297 315 754 245 594 297 315 754 245 594 297 200 470 235 200 470 235 315 754 245 Part Winding Start Max RLA LRA 152 340 35 75 26.75 71 195 463 152 340 35 75 26.75 71 195 463 152 340 20 50 130 292 20 50 130 292 35 75 26.75 195 463 152 Winding Resistance Line to Line (Ohms) 0.508 0.085 0.34 0.32 0.059 1.016 0.085 0.34 0.32 0.059 1.016 0.085 0.34 1.46 0.111 0.444 1.46 0.111 0.444 0.32 0.059 1.016 See Section F Introduction for more information. FE49 Section_Fe.indd 49 3/4/2008 8:06:59 AM Electrical Data - Copelametic Large Refrigerant-Cooled Compressors Model Volts PH 6DJ3R40M0-TSN 6DJ3R40M0-TSN 6DJ3R40ME-FSD 6DJ3R40ME-FSU 6DJ3R40ME-TSE 6DJ3R40ME-TSN 6DJ3R40ME-TSN 6DJ3R40ML-FSD 6DJ3R40ML-FSU 6DJ3R40ML-TSE 6DJ3R40ML-TSN 6DJ3R40ML-TSN 6DJGA4000-FSU 6DK1A2000-TSK 6DK1A2000-TSK 6DK1A3500-ES8 6DK1A3500-ES8 6DK1A3500-FSD 6DK1A3500-TSE 6DK1A3500-TSK 6DK1A3500-TSK 6DK1A3500-TXE 230 460 460 200 575 230 460 460 200 575 230 460 200 208/230 460 200/220 380 460 575 208/230 460 575 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 Across the Line Max RLA LRA 141.4 70.7 86.4 150 53.5 141.4 70.7 86.4 150 53.5 141.4 70.7 150 75 37.5 146.7 84.1 67.5 50 125 62.5 NA 594 297 315 754 245 594 297 315 754 245 594 297 754 346 173 633 365 260 230 565 283 230 Part Winding Start Max RLA LRA 71 340 35 75 26.75 71 195 463 152 340 35 75 26.75 71 195 463 152 340 75 37.5 463 208 212 33.8 25 62.5 156 138 340 138 Winding Resistance Line to Line (Ohms) 0.085 0.34 0.32 0.059 1.016 0.085 0.34 0.32 0.059 1.016 0.085 0.34 0.059 0.142 0.568 0.225 0.075 0.4 1.076 0.088 0.352 0.538 See Section F Introduction for more information. FE50 Section_Fe.indd 50 3/4/2008 8:06:59 AM Electrical Data - Copelametic Large Refrigerant-Cooled Compressors Model Volts PH 6DK1A3500-TXK 6DK1A3500-TXK 6DK1A350E-TSK 6DK1A350E-TSK 6DK1R35M0-ES8 6DK1R35M0-ES8 6DK1R35M0-FSD 6DK1R35M0-TSE 6DK1R35M0-TSK 6DK1R35M0-TSK 6DK3A200E-TSE 6DK3A200E-TSK 6DK3A200E-TSK 6DK3A200L-TSE 6DK3A200L-TSK 6DK3A200L-TSK 6DK3A3500-FSD 6DK3A3500-TSE 6DK3A3500-TSK 6DK3A3500-TSK 6DK3A350E-FSD 6DK3A350E-TSE 208/230 460 208/230 460 200/220 380 460 575 208/230 460 575 208/230 460 575 208/230 460 460 575 208/230 460 460 575 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 Across the Line Max RLA LRA NA NA 125 62.5 146.7 84.1 67.5 50 125 62.5 30 75 37.5 30 75 37.5 62.6 42.5 125.1 62.6 62.6 42.5 565 283 565 283 633 365 260 230 565 283 135 346 173 135 346 173 260 230 565 283 260 230 Part Winding Start Max RLA LRA 340 62.5 340 212 33.8 25 62.5 156 138 340 15 37.5 81 208 15 37.5 81 208 31.3 21.3 62.6 156 138 340 31.3 21.3 156 138 Winding Resistance Line to Line (Ohms) 0.088 0.352 0.088 0.352 0.225 0.075 0.4 1.076 0.088 0.352 1.94 0.142 0.568 1.94 0.142 0.568 0.39 1.16 0.087 0.348 0.39 1.16 See Section F Introduction for more information. FE51 Section_Fe.indd 51 3/4/2008 8:07:00 AM Electrical Data - Copelametic Large Refrigerant-Cooled Compressors Model Volts PH 6DK3A350E-TSK 6DK3A350E-TSK 6DK3A350L-FSD 6DK3A350L-TSE 6DK3A350L-TSK 6DK3A350L-TSK 6DK3R23ME-TSK 6DK3R23ME-TSK 6DK3R35M0-FSD 6DK3R35M0-TSE 6DK3R35M0-TSK 6DK3R35M0-TSK 6DK3R35ME-FSD 6DK3R35ME-TSE 6DK3R35ME-TSK 6DK3R35ME-TSK 6DK3R35ML-FSD 6DK3R35ML-TSE 6DK3R35ML-TSK 6DK3R35ML-TSK 6DK8A3500-TSK 6DK8A3500-TSK 208/230 460 460 575 208/230 460 208/230 460 460 575 208/230 460 460 575 208/230 460 460 575 208/230 460 208/230 460 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 Across the Line Max RLA LRA 147.1 73.6 62.6 42.5 147.1 73.6 75 37.5 62.6 42.5 125.1 62.6 62.6 42.5 147.1 73.6 62.6 42.5 147.1 73.6 125.1 62.6 565 283 260 230 565 283 346 173 260 230 565 283 260 230 565 283 260 230 565 283 565 283 Part Winding Start Max RLA LRA 62.6 340 31.3 21.3 62.6 156 138 340 37.5 208 31.3 21.3 62.6 156 138 340 31.3 21.3 62.6 156 138 340 31.3 21.3 62.6 156 138 340 62.6 340 Winding Resistance Line to Line (Ohms) 0.087 0.348 0.39 1.16 0.087 0.348 0.142 0.568 0.39 1.16 0.087 0.348 0.39 1.16 0.087 0.348 0.39 1.16 0.087 0.348 0.087 0.348 See Section F Introduction for more information. FE52 Section_Fe.indd 52 3/4/2008 8:07:00 AM Electrical Data - Copelametic Large Refrigerant-Cooled Compressors Model Volts PH 6DL1A2700-FSD 6DL1A2700-TSE 6DL1A2700-TSK 6DL1A2700-TSK 6DL3A2700-ES8 6DL3A2700-ES8 6DL3A2700-FSD 6DL3A2700-TSE 6DL3A2700-TSK 6DL3A2700-TSK 6DL3A270E-FSD 6DL3A270E-TSE 6DL3A270E-TSK 6DL3A270E-TSK 6DL3A270L-FSD 6DL3A270L-TSE 6DL3A270L-TSK 6DL3A270L-TSK 6DL3F93K0-ES8 6DL3F93K0-ES8 6DL3F93K0-FSD 6DL3F93K0-TSE 460 575 208/230 460 200/220 380 460 575 208/230 460 460 575 208/230 460 460 575 208/230 460 200/220 380 460 575 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 Across the Line Max RLA LRA 42.9 35 89.3 44.6 82.5 47.9 41.6 32.5 80.7 40.4 41.6 32.5 80.7 40.4 41.6 32.5 80.7 40.4 82.5 47.9 41.6 32.5 218 172 450 225 445 260 218 172 450 225 218 172 450 225 218 172 450 225 445 260 218 172 Part Winding Start Max RLA LRA 21.5 17.5 44.7 131 103 263 141 20.8 16.3 40.4 131 103 263 20.8 16.3 40.4 131 103 263 20.8 16.3 40.4 131 103 263 141 20.8 16.3 131 103 Winding Resistance Line to Line (Ohms) 0.457 1.538 0.114 0.456 0.336 0.112 0.457 1.538 0.114 0.456 0.457 1.538 0.114 0.456 0.457 1.538 0.114 0.456 0.336 0.112 0.457 1.538 See Section F Introduction for more information. FE53 Section_Fe.indd 53 3/4/2008 8:07:00 AM Electrical Data - Copelametic Large Refrigerant-Cooled Compressors Model Volts PH 6DL3F93K0-TSK 6DL3F93K0-TSK 6DL3F93KE-FSD 6DL3F93KE-TSE 6DL3F93KE-TSK 6DL3F93KE-TSK 6DL3F93KL-FSD 6DL3F93KL-TSE 6DL3F93KL-TSK 6DL3F93KL-TSK 6DL8A2700-TSK 6DL8A2700-TSK 6DM3A3500-ES8 6DM3A3500-ES8 6DM3A3500-FSD 6DM3A3500-FSU 6DM3A3500-FXD 6DM3A3500-FXU 6DM3A3500-TSE 6DM3A3500-TSN 6DM3A3500-TSN 6DM3A3500-TXE 208/230 460 460 575 208/230 460 460 575 208/230 460 208/230 460 200/220 380 460 200 460 200 575 230 460 575 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 Across the Line Max RLA LRA 80.7 40.4 41.6 32.5 80.7 40.4 41.6 32.5 80.7 40.4 80.7 40.4 NA NA 66 135 NA NA 46 125 62.5 NA 450 225 218 172 450 225 218 172 450 225 450 225 633 365 315 650 315 650 245 594 297 245 Part Winding Start Max RLA LRA 40.4 263 20.8 16.3 40.4 131 103 263 20.8 16.3 40.4 131 103 263 40.4 263 212 33 67.5 23 62.5 195 400 195 400 152 340 152 Winding Resistance Line to Line (Ohms) 0.114 0.456 0.457 1.538 0.114 0.456 0.457 1.538 0.114 0.456 0.114 0.456 0.225 0.075 0.32 0.069 0.32 0.069 1.016 0.085 0.34 0.508 See Section F Introduction for more information. FE54 Section_Fe.indd 54 3/4/2008 8:07:01 AM Electrical Data - Copelametic Large Refrigerant-Cooled Compressors Model Volts PH 6DM3A3500-TXN 6DM3A3500-TXN 6DM3A350E-ES8 6DM3A350E-ES8 6DM3A350E-FSD 6DM3A350E-FSU 6DM3A350E-TSE 6DM3A350E-TSN 6DM3A350E-TSN 6DM3A350L-FSD 6DM3A350L-FSU 6DM3A350L-TSE 6DM3A350L-TSN 6DM3A350L-TSN 6DM3R37M0-FSD 6DM3R37M0-FSU 6DM3R37M0-TSE 6DM3R37M0-TSN 6DM3R37M0-TSN 6DM3R37ME-FSD 6DM3R37ME-FSU 6DM3R37ME-TSE 230 460 200/220 380 460 200 575 230 460 460 200 575 230 460 460 200 575 230 460 460 200 575 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 Across the Line Max RLA LRA NA NA NA NA 66 135 46 168.6 84.3 66 135 46 168.6 84.3 66 135 46 125 62.5 66 135 46 594 297 633 365 315 650 245 594 297 315 650 245 594 297 315 650 245 594 297 315 650 245 Part Winding Start Max RLA LRA 340 212 33 67.5 23 62.5 195 400 152 340 33 67.5 23 62.5 195 400 152 340 33 67.5 23 62.5 195 400 152 340 33 67.5 23 195 400 152 Winding Resistance Line to Line (Ohms) 0.085 0.34 0.225 0.075 0.32 0.069 1.016 0.085 0.34 0.32 0.069 1.016 0.085 0.34 0.32 0.069 1.016 0.085 0.34 0.32 0.069 1.016 See Section F Introduction for more information. FE55 Section_Fe.indd 55 3/4/2008 8:07:01 AM Electrical Data - Copelametic Large Refrigerant-Cooled Compressors Model Volts PH 6DM3R37ME-TSN 6DM3R37ME-TSN 6DM3R37ML-FSD 6DM3R37ML-FSU 6DM3R37ML-TSE 6DM3R37ML-TSN 6DM3R37ML-TSN 6DN3A3500-ES8 6DN3A3500-ES8 6DN3A3500-FSD 6DN3A3500-FSU 6DN3A3500-FXD 6DN3A3500-FXU 6DN3A3500-TSE 6DN3A3500-TSN 6DN3A3500-TSN 6DN3A3500-TXE 6DN3A3500-TXN 6DN3A3500-TXN 6DN3A350E-ES8 6DN3A350E-ES8 6DN3A350E-FSD 230 460 460 200 575 230 460 200/220 380 460 200 460 200 575 230 460 575 230 460 200/220 380 460 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 Across the Line Max RLA LRA 168.6 84.3 66 135 46 168.6 84.3 NA NA 66 135 NA NA 46 125 62.5 NA NA NA NA NA 66 594 297 315 650 245 594 297 633 365 315 650 315 650 245 594 297 245 594 297 633 365 315 Part Winding Start Max RLA LRA 62.5 340 33 67.5 23 62.5 195 400 152 340 212 33 67.5 23 62.5 195 400 195 400 152 340 152 340 212 33 195 Winding Resistance Line to Line (Ohms) 0.085 0.34 0.32 0.069 1.016 0.085 0.34 0.225 0.075 0.32 0.069 0.32 0.069 1.016 0.085 0.34 0.508 0.085 0.34 0.225 0.075 0.32 See Section F Introduction for more information. FE56 Section_Fe.indd 56 3/4/2008 8:07:02 AM Electrical Data - Copelametic Large Refrigerant-Cooled Compressors Model Volts PH 6DN3A350E-FSU 6DN3A350E-TSE 6DN3A350E-TSN 6DN3A350E-TSN 6DN3A350L-FSD 6DN3A350L-FSU 6DN3A350L-TSE 6DN3A350L-TSN 6DN3A350L-TSN 6DN3R37M0-FSD 6DN3R37M0-FSU 6DN3R37M0-TSE 6DN3R37M0-TSN 6DN3R37M0-TSN 6DN3R37ME-FSD 6DN3R37ME-FSU 6DN3R37ME-TSE 6DN3R37ME-TSN 6DN3R37ME-TSN 6DN3R37ML-FSD 6DN3R37ML-FSU 6DN3R37ML-TSE 200 575 230 460 460 200 575 230 460 460 200 575 230 460 460 200 575 230 460 460 200 575 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 Across the Line Max RLA LRA 135 46 168.6 84.3 66 135 46 168.6 84.3 66 135 46 125 62.5 66 135 46 168.6 84.3 66 135 46 650 245 594 297 315 650 245 594 297 315 650 245 594 297 315 650 245 594 297 315 650 245 Part Winding Start Max RLA LRA 67.5 23 62.5 400 152 340 33 67.5 23 62.5 195 400 152 340 33 67.5 23 62.5 195 400 152 340 33 67.5 23 62.5 195 400 152 340 33 67.5 23 195 400 152 Winding Resistance Line to Line (Ohms) 0.069 1.016 0.085 0.34 0.32 0.069 1.016 0.085 0.34 0.32 0.069 1.016 0.085 0.34 0.32 0.069 1.016 0.085 0.34 0.32 0.069 1.016 See Section F Introduction for more information. FE57 Section_Fe.indd 57 3/4/2008 8:07:02 AM Electrical Data - Copelametic Large Refrigerant-Cooled Compressors Model Volts PH 6DN3R37ML-TSN 6DN3R37ML-TSN 6DP1A2000-TSK 6DP1A2000-TSK 6DP1A3500-ES8 6DP1A3500-ES8 6DP1A3500-FSD 6DP1A3500-FXD 6DP1A3500-TSE 6DP1A3500-TSK 6DP1A3500-TSK 6DP1A3500-TXE 6DP1A3500-TXK 6DP1A3500-TXK 6DP1A350E-TSK 6DP1A350E-TSK 6DP1R35M0-ES8 6DP1R35M0-ES8 6DP1R35M0-FSD 6DP1R35M0-TSE 6DP1R35M0-TSK 6DP1R35M0-TSK 230 460 208/230 460 200/220 380 460 460 575 208/230 460 575 208/230 460 208/230 460 200/220 380 460 575 208/230 460 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 Across the Line Max RLA LRA 168.6 84.3 75 37.5 146.7 84.1 67.5 NA 50 125 62.5 NA NA NA 125 62.5 146.7 84.1 67.5 50 125 62.5 594 297 346 173 633 365 260 260 230 565 283 230 565 283 565 283 633 365 260 230 565 283 Part Winding Start Max RLA LRA 62.5 340 37.5 208 212 33.8 25 62.5 156 156 138 340 138 340 62.5 340 212 33.8 25 62.5 156 138 340 Winding Resistance Line to Line (Ohms) 0.085 0.34 0.142 0.568 0.225 0.075 0.4 0.4 1.076 0.088 0.352 0.538 0.088 0.352 0.088 0.352 0.225 0.075 0.4 1.076 0.088 0.352 See Section F Introduction for more information. FE58 Section_Fe.indd 58 3/4/2008 8:07:02 AM Electrical Data - Copelametic Large Refrigerant-Cooled Compressors Model Volts PH 6DP3A200E-TSE 6DP3A200E-TSK 6DP3A200E-TSK 6DP3A200E-TXK 6DP3A200E-TXK 6DP3A200L-TSE 6DP3A200L-TSK 6DP3A200L-TSK 6DP3A3500-FSD 6DP3A3500-TSE 6DP3A3500-TSK 6DP3A3500-TSK 6DP3A350E-FSD 6DP3A350E-TSE 6DP3A350E-TSK 6DP3A350E-TSK 6DP3A350L-FSD 6DP3A350L-TSE 6DP3A350L-TSK 6DP3A350L-TSK 6DP3R23ME-TSK 6DP3R23ME-TSK 575 208/230 460 208/230 460 575 208/230 460 460 575 208/230 460 460 575 208/230 460 460 575 208/230 460 208/230 460 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 Across the Line Max RLA LRA 30 75 37.5 NA NA 30 75 37.5 62.6 42.5 125.1 62.6 62.6 42.5 147.1 73.6 62.6 42.5 147.1 73.6 75 37.5 135 346 173 346 173 135 346 173 260 230 565 283 260 230 565 283 260 230 565 283 346 173 Part Winding Start Max RLA LRA 15 37.5 81 208 208 15 37.5 81 208 31.3 21.3 62.6 156 138 340 31.3 21.3 62.6 156 138 340 31.3 21.3 62.6 156 138 340 37.5 208 Winding Resistance Line to Line (Ohms) 1.94 0.142 0.568 0.142 0.568 1.94 0.142 0.568 0.39 1.16 0.087 0.348 0.39 1.16 0.087 0.348 0.39 1.16 0.087 0.348 0.142 0.568 See Section F Introduction for more information. FE59 Section_Fe.indd 59 3/4/2008 8:07:03 AM Electrical Data - Copelametic Large Refrigerant-Cooled Compressors Model Volts PH 6DP3R23ME-TXK 6DP3R23ME-TXK 6DP3R35M0-FSD 6DP3R35M0-TSE 6DP3R35M0-TSK 6DP3R35M0-TSK 6DP3R35ME-FSD 6DP3R35ME-TSE 6DP3R35ME-TSK 6DP3R35ME-TSK 6DP3R35ML-FSD 6DP3R35ML-TSE 6DP3R35ML-TSK 6DP3R35ML-TSK 6DP5A3500-FSD 6DP5A3500-TSE 6DR1A4000-ES8 6DR1A4000-ES8 6DR1A4000-FSD 6DR1A4000-FSU 6DR1A4000-FXU 6DR1A4000-TSE 208/230 460 460 575 208/230 460 460 575 208/230 460 460 575 208/230 460 460 575 200/220 380 460 200 200 575 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 Across the Line Max RLA LRA NA NA 62.6 42.5 125.1 62.6 62.6 42.5 147.1 73.6 62.6 42.5 147.1 73.6 67.5 50 164.1 96.9 69.3 170 NA 57.1 346 173 260 230 565 283 260 230 565 283 260 230 565 283 260 230 633 365 300 660 660 235 Part Winding Start Max RLA LRA 208 31.3 21.3 62.6 156 138 340 31.3 21.3 62.6 156 138 340 31.3 21.3 62.6 156 138 340 33.8 25 156 138 212 34.7 85 170 400 400 135 28.6 Winding Resistance Line to Line (Ohms) 0.142 0.568 0.39 1.16 0.087 0.348 0.39 1.16 0.087 0.348 0.39 1.16 0.087 0.348 0.4 1.076 0.225 0.075 0.352 0.067 0.067 1.14 See Section F Introduction for more information. FE60 Section_Fe.indd 60 3/4/2008 8:07:03 AM Electrical Data - Copelametic Large Refrigerant-Cooled Compressors Model Volts PH 6DR1A4000-TSN 6DR1A4000-TSN 6DR1A4000-TXE 6DR1A4000-TXN 6DR1A4000-TXN 6DR1A400E-ES8 6DR1A400E-ES8 6DR1R40M0-ES8 6DR1R40M0-ES8 6DR1R40M0-FSD 6DR1R40M0-TSN 6DR1R40M0-TSN 6DR3A300E-TSE 6DR3A300E-TSK 6DR3A300E-TSK 6DR3A300L-TSE 6DR3A300L-TSK 6DR3A300L-TSK 6DR3A4000-FSD 6DR3A4000-FSU 6DR3A4000-FXD 6DR3A4000-FXU 230 460 575 230 460 200/220 380 200/220 380 460 230 460 575 208/230 460 575 208/230 460 460 200 460 200 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 Across the Line Max RLA LRA 141.4 70.7 NA NA NA 164.1 96.9 164.1 96.9 69.3 141.4 70.7 40 100 50 40 100 50 70 150 NA NA 594 297 235 594 297 633 365 633 365 300 594 297 200 470 235 200 470 235 315 754 315 754 Part Winding Start Max RLA LRA 70.5 340 135 340 212 212 34.7 70.5 170 340 20 50 130 292 20 50 130 292 35 75 195 463 195 463 Winding Resistance Line to Line (Ohms) 0.085 0.34 0.569 0.085 0.34 0.225 0.075 0.225 0.075 0.352 0.085 0.34 1.46 0.111 0.444 1.46 0.111 0.444 0.32 0.059 0.32 0.059 See Section F Introduction for more information. FE61 Section_Fe.indd 61 3/4/2008 8:07:03 AM Electrical Data - Copelametic Large Refrigerant-Cooled Compressors Model Volts PH 6DR3A4000-TSE 6DR3A4000-TSN 6DR3A4000-TSN 6DR3A4000-TXE 6DR3A4000-TXN 6DR3A4000-TXN 6DR3A400E-FSD 6DR3A400E-FSU 6DR3A400E-TSE 6DR3A400E-TSN 6DR3A400E-TSN 6DR3A400L-FSD 6DR3A400L-FSU 6DR3A400L-TSE 6DR3A400L-TSN 6DR3A400L-TSN 6DR3R28ME-TSK 6DR3R28ME-TSK 6DR3R28ML-TSK 6DR3R28ML-TSK 6DR3R40M0-FSD 6DR3R40M0-FSU 575 230 460 575 230 460 460 200 575 230 460 460 200 575 230 460 208/230 460 208/230 460 460 200 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 Across the Line Max RLA LRA 53.5 141.4 70.7 NA NA NA 86.4 150 53.5 141.4 70.7 86.4 150 53.5 141.4 70.7 100 50 100 50 70 150 245 594 297 245 594 297 315 754 245 594 297 315 754 245 594 297 470 235 470 235 315 754 Part Winding Start Max RLA LRA 26.75 71 152 340 152 340 35 75 26.75 71 195 463 152 340 35 75 26.75 71 195 463 152 340 50 292 50 292 35 75 195 463 Winding Resistance Line to Line (Ohms) 1.016 0.085 0.34 0.508 0.085 0.34 0.32 0.059 1.016 0.085 0.34 0.32 0.059 1.016 0.085 0.34 0.111 0.444 0.111 0.444 0.32 0.059 See Section F Introduction for more information. FE62 Section_Fe.indd 62 3/4/2008 8:07:04 AM Electrical Data - Copelametic Large Refrigerant-Cooled Compressors Model Volts PH 6DR3R40M0-TSE 6DR3R40M0-TSN 6DR3R40M0-TSN 6DR3R40ME-FSD 6DR3R40ME-FSU 6DR3R40ME-TSE 6DR3R40ME-TSN 6DR3R40ME-TSN 6DR3R40ML-FSD 6DR3R40ML-FSU 6DR3R40ML-TSE 6DR3R40ML-TSN 6DR3R40ML-TSN 6DRGA4000-FSU 6DS1A4000-ES8 6DS1A4000-ES8 6DS1A4000-FSD 6DS1A4000-FSU 6DS1A4000-FXU 6DS1A4000-TSE 6DS1A4000-TSN 6DS1A4000-TSN 575 230 460 460 200 575 230 460 460 200 575 230 460 200 200/220 380 460 200 200 575 230 460 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 Across the Line Max RLA LRA 53.5 141.4 70.7 86.4 150 53.5 141.4 70.7 86.4 150 53.5 141.4 70.7 150 164.1 96.9 69.3 170 NA 57.1 141.4 70.7 245 594 297 315 754 245 594 297 315 754 245 594 297 754 633 365 300 660 660 235 594 297 Part Winding Start Max RLA LRA 26.75 71 152 340 35 75 26.75 71 195 463 152 340 35 75 26.75 71 195 463 152 340 75 463 212 34.7 85 170 400 400 135 340 28.6 70.5 Winding Resistance Line to Line (Ohms) 1.016 0.085 0.34 0.32 0.059 1.016 0.085 0.34 0.32 0.059 1.016 0.085 0.34 0.059 0.225 0.075 0.352 0.067 0.067 1.14 0.085 0.34 See Section F Introduction for more information. FE63 Section_Fe.indd 63 3/4/2008 8:07:04 AM Electrical Data - Copelametic Large Refrigerant-Cooled Compressors Model Volts PH 6DS1A4000-TXE 6DS1A4000-TXN 6DS1A4000-TXN 6DS1R40M0-ES8 6DS1R40M0-ES8 6DS1R40M0-FSD 6DS1R40M0-FSU 6DS1R40M0-TSE 6DS1R40M0-TSN 6DS1R40M0-TSN 6DS3A300E-TSE 6DS3A300E-TSK 6DS3A300E-TSK 6DS3A300L-TSE 6DS3A300L-TSK 6DS3A300L-TSK 6DS3A4000-FSD 6DS3A4000-FSU 6DS3A4000-FXD 6DS3A4000-FXU 6DS3A4000-TSE 6DS3A4000-TSN 575 230 460 200/220 380 460 200 575 230 460 575 208/230 460 575 208/230 460 460 200 460 200 575 230 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 Across the Line Max RLA LRA NA NA NA 164.1 96.9 69.3 170 57.1 141.4 70.7 40 100 50 40 100 50 70 150 NA NA 53.5 141.4 235 594 297 633 365 300 660 235 594 297 200 470 235 200 470 235 315 754 315 754 245 594 Part Winding Start Max RLA LRA 135 340 212 34.7 85 28.6 70.5 170 400 135 340 20 50 130 292 20 50 130 292 35 75 195 463 195 463 152 340 26.75 71 Winding Resistance Line to Line (Ohms) 0.569 0.085 0.34 0.225 0.075 0.352 0.067 1.14 0.085 0.34 1.46 0.111 0.444 1.46 0.111 0.444 0.32 0.059 0.32 0.059 1.016 0.085 See Section F Introduction for more information. FE64 Section_Fe.indd 64 3/4/2008 8:07:05 AM Electrical Data - Copelametic Large Refrigerant-Cooled Compressors Model Volts PH 6DS3A4000-TSN 6DS3A4000-TXE 6DS3A4000-TXN 6DS3A4000-TXN 6DS3A400E-FSD 6DS3A400E-FSU 6DS3A400E-TSE 6DS3A400E-TSN 6DS3A400E-TSN 6DS3A400L-FSD 6DS3A400L-FSU 6DS3A400L-TSE 6DS3A400L-TSN 6DS3A400L-TSN 6DS3R28ME-TSE 6DS3R28ME-TSK 6DS3R28ME-TSK 6DS3R28ML-TSE 6DS3R28ML-TSK 6DS3R28ML-TSK 6DS3R40M0-FSD 6DS3R40M0-FSU 460 575 230 460 460 200 575 230 460 460 200 575 230 460 575 208/230 460 575 208/230 460 460 200 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 Across the Line Max RLA LRA 70.7 NA NA NA 86.4 150 53.5 141.4 70.7 86.4 150 53.5 141.4 70.7 40 100 50 40 100 50 70 150 297 245 594 297 315 754 245 594 297 315 754 245 594 297 200 470 235 200 470 235 315 754 Part Winding Start Max RLA LRA 152 340 35 75 26.75 71 195 463 152 340 35 75 26.75 71 195 463 152 340 20 50 130 292 20 50 130 292 35 75 195 463 Winding Resistance Line to Line (Ohms) 0.34 0.508 0.085 0.34 0.32 0.059 1.016 0.085 0.34 0.32 0.059 1.016 0.085 0.34 1.46 0.111 0.444 1.46 0.111 0.444 0.32 0.059 See Section F Introduction for more information. FE65 Section_Fe.indd 65 3/4/2008 8:07:05 AM Electrical Data - Copelametic Large Refrigerant-Cooled Compressors Model Volts PH 6DS3R40M0-TSE 6DS3R40M0-TSN 6DS3R40M0-TSN 6DS3R40ME-FSD 6DS3R40ME-FSU 6DS3R40ME-TSE 6DS3R40ME-TSN 6DS3R40ME-TSN 6DS3R40ML-FSD 6DS3R40ML-FSU 6DS3R40ML-TSE 6DS3R40ML-TSN 6DS3R40ML-TSN 6DSGA4000-FSU 6DT1A3000-ES8 6DT1A3000-ES8 6DT1A3000-FSD 6DT1A3000-TSE 6DT1A3000-TSK 6DT1A3000-TSK 6DT1F11M0-ES8 6DT1F11M0-ES8 575 230 460 460 200 575 230 460 460 200 575 230 460 200 200/220 380 460 575 208/230 460 200/220 380 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 Across the Line Max RLA LRA 53.5 141.4 70.7 86.4 150 53.5 141.4 70.7 86.4 150 53.5 141.4 70.7 150 95.9 55.6 53.6 40 110.9 55.5 95.9 55.6 245 594 297 315 754 245 594 297 315 754 245 594 297 754 500 289 235 200 470 235 500 289 Part Winding Start Max RLA LRA 26.75 71 152 340 35 75 26.75 71 195 463 152 340 35 75 26.75 71 195 463 152 340 75 463 164 26.8 20 55.5 141 130 292 164 Winding Resistance Line to Line (Ohms) 1.016 0.085 0.34 0.32 0.059 1.016 0.085 0.34 0.32 0.059 1.016 0.085 0.34 0.059 0.294 0.098 0.45 1.46 0.111 0.444 0.294 0.098 See Section F Introduction for more information. FE66 Section_Fe.indd 66 3/4/2008 8:07:06 AM Electrical Data - Copelametic Large Refrigerant-Cooled Compressors Model Volts PH 6DT1F11M0-FSD 6DT3A3000-FSD 6DT3A3000-TSE 6DT3A3000-TSK 6DT3A3000-TSK 6DT3A300E-FSD 6DT3A300E-TSE 6DT3A300E-TSK 6DT3A300E-TSK 6DT3A300L-FSD 6DT3A300L-TSE 6DT3A300L-TSK 6DT3A300L-TSK 6DT3A3010-ESX 6DT3A3010-ESX 6DT3A301E-ESX 6DT3A301E-ESX 6DT3A301L-ESX 6DT3A301L-ESX 6DT3F11M0-FSD 6DT3F11M0-TSE 6DT3F11M0-TSK 460 460 575 208/230 460 460 575 208/230 460 460 575 208/230 460 200/220 380 200/220 380 200/220 380 460 575 208/230 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 Across the Line Max RLA LRA 53.6 42.9 39.6 95.6 47.8 42.9 39.6 95.6 47.8 42.9 39.6 95.6 47.8 94.6 68.8 94.6 81.7 94.6 81.7 42.9 39.6 95.6 235 235 200 470 235 235 200 470 235 235 200 470 235 500 289 500 289 500 289 235 200 470 Part Winding Start Max RLA LRA 26.8 21.4 19.8 47.8 141 141 130 292 21.4 19.8 47.8 141 130 292 21.4 19.8 47.8 141 130 292 21.4 19.8 47.8 141 130 292 Winding Resistance Line to Line (Ohms) 0.45 0.45 1.46 0.111 0.444 0.45 1.46 0.111 0.444 0.45 1.46 0.111 0.444 0.294 0.098 0.294 0.098 0.294 0.098 0.45 1.46 0.111 See Section F Introduction for more information. FE67 Section_Fe.indd 67 3/4/2008 8:07:06 AM Electrical Data - Copelametic Large Refrigerant-Cooled Compressors Model Volts PH 6DT3F11M0-TSK 6DT3F11ME-FSD 6DT3F11ME-TSE 6DT3F11ME-TSK 6DT3F11ME-TSK 6DT3F11ML-FSD 6DT3F11ML-TSE 6DT3F11ML-TSK 6DT3F11ML-TSK 6DW3A3000-FSD 6DW3A3000-TSE 6DW3A3000-TSK 6DW3A3000-TSK 6DW3A300E-FSD 6DW3A300E-TSE 6DW3A300E-TSK 6DW3A300E-TSK 6DW3A300L-FSD 6DW3A300L-TSE 6DW3A300L-TSK 6DW3A300L-TSK 6DW3R32M0-FSD 460 460 575 208/230 460 460 575 208/230 460 460 575 208/230 460 460 575 208/230 460 460 575 208/230 460 460 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 Across the Line Max RLA LRA 47.8 42.9 39.6 95.6 47.8 42.9 39.6 95.6 47.8 50 40 105 52.5 50 40 134.3 67.1 50 40 134.3 67.1 50 235 235 200 470 235 235 200 470 235 260 230 565 283 260 230 565 283 260 230 565 283 260 Part Winding Start Max RLA LRA 21.4 19.8 47.8 141 130 292 21.4 19.8 47.8 141 130 292 25 20 52.5 156 138 340 25 20 52.5 156 138 340 25 20 52.5 156 138 340 25 156 Winding Resistance Line to Line (Ohms) 0.444 0.45 1.46 0.111 0.444 0.45 1.46 0.111 0.444 0.39 1.16 0.087 0.348 0.39 1.16 0.087 0.348 0.39 1.16 0.087 0.348 0.39 See Section F Introduction for more information. FE68 Section_Fe.indd 68 3/4/2008 8:07:06 AM Electrical Data - Copelametic Large Refrigerant-Cooled Compressors Model Volts PH 6DW3R32M0-TSE 6DW3R32M0-TSK 6DW3R32M0-TSK 6DW3R32ME-FSD 6DW3R32ME-TSE 6DW3R32ME-TSK 6DW3R32ME-TSK 6DW3R32ML-FSD 6DW3R32ML-TSE 6DW3R32ML-TSK 6DW3R32ML-TSK 6DY3A3000-FSD 6DY3A3000-TSE 6DY3A3000-TSK 6DY3A3000-TSK 6DY3A300E-FSD 6DY3A300E-TSE 6DY3A300E-TSK 6DY3A300E-TSK 6DY3A300L-FSD 6DY3A300L-TSE 6DY3A300L-TSK 575 208/230 460 460 575 208/230 460 460 575 208/230 460 460 575 208/230 460 460 575 208/230 460 460 575 208/230 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 Across the Line Max RLA LRA 40 105 52.5 50 40 134.3 67.1 50 40 134.3 67.1 50 40 105 52.5 50 40 134.3 67.1 50 40 134.3 230 565 283 260 230 565 283 260 230 565 283 260 230 565 283 260 230 565 283 260 230 565 Part Winding Start Max RLA LRA 20 52.5 138 340 25 20 52.5 156 138 340 25 20 52.5 156 138 340 25 20 52.5 156 138 340 25 20 52.5 156 138 340 25 20 52.5 156 138 340 Winding Resistance Line to Line (Ohms) 1.16 0.087 0.348 0.39 1.16 0.087 0.348 0.39 1.16 0.087 0.348 0.39 1.16 0.087 0.348 0.39 1.16 0.087 0.348 0.39 1.16 0.087 See Section F Introduction for more information. FE69 Section_Fe.indd 69 3/4/2008 8:07:07 AM Electrical Data - Copelametic Large Refrigerant-Cooled Compressors Model Volts PH 6DY3A300L-TSK 6DY3R32M0-FSD 6DY3R32M0-TSE 6DY3R32M0-TSK 6DY3R32M0-TSK 6DY3R32ME-FSD 6DY3R32ME-TSE 6DY3R32ME-TSK 6DY3R32ME-TSK 6DY3R32ML-FSD 6DY3R32ML-TSE 6DY3R32ML-TSK 6DY3R32ML-TSK 6RA4-1000-TSE 6RA4-1000-TSK 6RA4-1000-TSK 6RA4-100A-TSK 6RA4-100A-TSK 6RA4-2000-FSD 6RA4-2000-TSE 6RA4-2000-TSK 6RA4-2000-TSK 460 460 575 208/230 460 460 575 208/230 460 460 575 208/230 460 575 208/230 460 208/230 460 460 575 208/230 460 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 Across the Line Max RLA LRA 67.1 50 40 105 52.5 50 40 134.3 67.1 50 40 134.3 67.1 17.5 43.6 21.8 43.6 21.8 38.9 28.2 67.4 33.7 283 260 230 565 283 260 230 565 283 260 230 565 283 106 240 120 240 120 135 135 308 154 Part Winding Start Max RLA LRA 25 20 52.5 156 138 340 25 20 52.5 156 138 340 25 20 52.5 156 138 340 21.8 140 21.8 140 19.4 14.1 33.7 82 74 188 Winding Resistance Line to Line (Ohms) 0.348 0.39 1.16 0.087 0.348 0.39 1.16 0.087 0.348 0.39 1.16 0.087 0.348 1.6 0.259 1.036 0.259 1.036 0.757 2.2 0.173 0.69 See Section F Introduction for more information. FE70 Section_Fe.indd 70 3/4/2008 8:07:07 AM Electrical Data - Copelametic Large Refrigerant-Cooled Compressors Model 6RA4-200A-TSK 6RA4-200A-TSK 6RA4-200L-TSK 6RA4-200L-TSK 6RA4-3000-ESX 6RA4-3000-ESX 6RA4-3000-FSD 6RA4-3000-TSE 6RA4-3000-TSK 6RA4-3000-TSK 6RA4-300A-TSK 6RA4-300A-TSK 6RA4-300L-TSK 6RA4-300L-TSK 6RA5-1000-TSK 6RA5-1000-TSK 6RA5-2000-TSK 6RA5-2000-TSK 6RB2-1000-TSK 6RB2-1000-TSK 6RB2-2000-FSD 6RB2-2000-TSE Volts PH 208/230 460 208/230 460 220 380 460 575 208/230 460 208/230 460 208/230 460 208/230 460 208/230 460 208/230 460 460 575 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 Across the Line Max RLA LRA 67.4 33.7 67.4 33.7 NA NA 50.6 42.9 104.3 52.1 104.3 52.1 104.3 52.1 43.6 21.8 67.4 33.7 43.3 21.6 28.9 25.4 308 154 308 154 432 249 200 200 470 235 470 235 470 235 240 120 308 154 240 120 135 135 Part Winding Start Max RLA LRA 33.7 188 33.7 188 25.3 21.5 52.5 121 130 292 52.5 292 52.5 292 21.8 140 33.7 188 21.7 140 14.5 12.7 82 74 Winding Resistance Line to Line (Ohms) 0.173 0.69 0.173 0.69 0.108 0.324 0.475 1.46 0.108 0.43 0.108 0.43 0.108 0.43 0.259 1.036 0.173 0.69 0.259 1.036 0.757 2.2 See Section F Introduction for more information. FE71 Section_Fe.indd 71 3/4/2008 8:07:08 AM Electrical Data - Copelametic Large Refrigerant-Cooled Compressors Model 6RB2-2000-TSK 6RB2-2000-TSK 6RB2-200A-TSK 6RB2-200A-TSK 6RE2-2000-FSD 6RE2-2000-TSE 6RE2-2000-TSK 6RE2-2000-TSK 6RE2-200A-TSK 6RE2-200A-TSK 6RE2-3000-ESX 6RE2-3000-ESX 6RE2-3000-FSD 6RE2-3000-TSE 6RE2-3000-TSK 6RE2-3000-TSK 6RE2-300A-TSK 6RE2-300A-TSK 6RF5-2000-FSD 6RF5-2000-TSE 6RH1-2000-TSE 6RH1-2000-TSK Volts PH 208/230 460 208/230 460 460 575 208/230 460 208/230 460 220 380 460 575 208/230 460 208/230 460 460 575 575 208/230 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 Across the Line Max RLA LRA 61.4 30.7 61.4 30.7 38.9 26.8 65.4 32.5 65.4 32.5 NA NA 50 42.9 104.3 52.1 104.3 52.1 38.9 28.2 28.8 72 308 154 308 154 135 135 308 154 308 154 432 249 200 200 470 235 470 235 135 135 135 308 Part Winding Start Max RLA LRA 30.7 188 30.7 188 19.4 14.1 33.7 82 74 188 33.7 188 25.3 21.5 52.5 121 130 292 52.5 292 19.4 14.1 14.4 36 82 74 74 188 Winding Resistance Line to Line (Ohms) 0.173 0.69 0.173 0.69 0.757 2.2 0.173 0.69 0.173 0.69 0.108 0.324 0.475 1.46 0.108 0.43 0.108 0.43 0.757 2.2 2.2 0.174 See Section F Introduction for more information. FE72 Section_Fe.indd 72 3/4/2008 8:07:08 AM Electrical Data - Copelametic Large Refrigerant-Cooled Compressors Model Volts PH 6RH1-2000-TSK 6RH1-200A-TSK 6RH1-200A-TSK 6RH1-3500-ES8 6RH1-3500-ES8 6RH1-3500-FSD 6RH1-3500-TSE 6RH1-3500-TSK 6RH1-3500-TSK 6RH1-350A-FSD 6RH1-350A-TSK 6RH1-350A-TSK 6RH5-2000-TSK 6RH5-2000-TSK 6RH5-3500-FSD 6RH5-3500-TSE 6RJ1-3000-FSD 6RJ1-4000-ES8 6RJ1-4000-ES8 6RJ1-4000-FSD 6RJ1-4000-FSU 6RJ1-4000-TSE 460 208/230 460 200/220 380 460 575 208/230 460 460 208/230 460 208/230 460 460 575 460 200/220 380 460 200 575 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 Across the Line Max RLA LRA 36 72 36 145.9 85.9 67.5 50.2 134.3 67.1 67.5 134.3 67.1 72 36 67.5 50.2 57.5 160 89.6 64.3 170 53.6 154 308 154 633 365 225 230 565 283 225 565 283 308 154 225 230 200 633 365 239 625 225 Part Winding Start Max RLA LRA 36 188 212 33.8 25.1 67.5 150 138 340 33.8 67.5 150 340 36 188 33.8 25.1 28.8 150 138 121 212 32.2 85 26.8 147 388 140 Winding Resistance Line to Line (Ohms) 0.696 0.174 0.696 0.225 0.075 0.4 1.16 0.087 0.348 0.4 0.087 0.348 0.174 0.696 0.4 1.16 0.475 0.225 0.075 0.375 0.066 1.14 See Section F Introduction for more information. FE73 Section_Fe.indd 73 3/4/2008 8:07:08 AM Electrical Data - Copelametic Large Refrigerant-Cooled Compressors Model 6RJ1-4000-TSN 6RJ1-4000-TSN 6RJ1-400A-FSD 6RJ1-400A-FSU 6RJ1-400A-TSN 6RJ1-400A-TSN 6RK2-2000-TSE 6RK2-2000-TSK 6RK2-2000-TSK 6RK2-3500-ES8 6RK2-3500-ES8 6RK2-3500-FSD 6RK2-3500-TSE 6RK2-3500-TSK 6RK2-3500-TSK 6RK2-350A-TSK 6RK2-350A-TSK 6RK5-3500-FSD 6RK5-3500-TSK 6RK5-3500-TSK 6RL1-2500-ES8 6RL1-2500-ES8 Volts PH 230 460 460 200 230 460 575 208/230 460 200/220 380 460 575 208/230 460 208/230 460 460 208/230 460 200/220 380 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 Across the Line Max RLA LRA 141.4 70.7 64.3 170 141.4 70.7 28.8 72 36 145.9 82.7 67.5 50.2 134.3 67.1 134.3 67.1 67.5 134.3 67.1 102.3 59.3 594 297 239 625 594 297 135 308 154 633 365 225 230 565 283 565 283 225 565 283 438 251 Part Winding Start Max RLA LRA 71 340 32.2 85 71 147 388 340 14.4 36 74 188 212 33.8 25.1 67.5 150 138 340 67.5 340 33.8 67.5 150 340 142 Winding Resistance Line to Line (Ohms) 0.085 0.34 0.375 0.066 0.085 0.34 2.2 0.174 0.696 0.225 0.075 0.4 1.16 0.087 0.348 0.087 0.348 0.4 0.087 0.348 0.345 0.115 See Section F Introduction for more information. FE74 Section_Fe.indd 74 3/4/2008 8:07:09 AM Electrical Data - Copelametic Large Refrigerant-Cooled Compressors Model Volts PH 6RL1-2500-TSE 6RL1-2500-TSK 6RL1-2500-TSK 6RL1-250A-TSK 6RL1-250A-TSK 6RL1-250L-TSK 6RL1-250L-TSK 6RL5-2500-TSE 6RN2-2000-FSD 6RN2-2000-TSE 6RN2-2000-TSK 6RN2-2000-TSK 6RN2-200A-TSK 6RN2-200A-TSK 6RN2-3000-ESX 6RN2-3000-ESX 6RN2-3000-FSD 6RN2-3000-TSE 6RN2-3000-TSK 6RN2-3000-TSK 6RN2-300A-TSK 6RN2-300A-TSK 575 208/230 460 208/230 460 208/230 460 575 460 575 208/230 460 208/230 460 220 380 460 575 208/230 460 208/230 460 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 Across the Line Max RLA LRA 34.9 96.9 48.5 96.9 48.5 96.9 48.5 34.9 38.9 26.8 65.4 32.7 65.4 32.7 NA NA 50 42.9 104.3 52.1 104.3 52.1 160 428 214 428 214 428 214 160 135 135 308 154 308 154 432 249 200 200 470 235 470 235 Part Winding Start Max RLA LRA 17.4 48.5 113 250 48.5 250 48.5 250 17.4 19.4 14.1 33.7 113 82 74 188 33.7 188 25.3 21.5 52.5 121 130 292 52.5 292 Winding Resistance Line to Line (Ohms) 1.76 0.132 0.528 0.132 0.528 0.132 0.528 1.76 0.757 2.2 0.173 0.69 0.173 0.69 0.108 0.324 0.475 1.46 0.108 0.43 0.108 0.43 See Section F Introduction for more information. FE75 Section_Fe.indd 75 3/4/2008 8:07:09 AM Electrical Data - Copelametic Large Refrigerant-Cooled Compressors Model Volts PH 6RN5-3000-TSK 6RN5-3000-TSK 6RP2-2000-TSE 6RP2-2000-TSK 6RP2-2000-TSK 6RP2-200A-TSK 6RP2-200A-TSK 6RP2-3500-ES8 6RP2-3500-ES8 6RP2-3500-FSD 6RP2-3500-TSE 6RP2-3500-TSK 6RP2-3500-TSK 6RP2-350A-FSD 6RP2-350A-TSK 6RP2-350A-TSK 6RP5-3500-FSD 6RP5-3500-TSK 6RP5-3500-TSK 6RR2-4000-ES8 6RR2-4000-ES8 6RR2-4000-FSD 208/230 460 575 208/230 460 208/230 460 200/220 380 460 575 208/230 460 460 208/230 460 460 208/230 460 200/220 380 460 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 Across the Line Max RLA LRA 104.3 52.1 28.8 72 36 72 36 145.9 82.7 67.5 50.2 134.3 67.1 67.5 134.3 67.1 67.5 134.3 67.1 160 89.6 62 470 235 135 308 154 308 154 633 365 225 230 565 283 225 565 283 225 565 283 633 365 239 Part Winding Start Max RLA LRA 52.5 292 14.4 36 74 188 36 188 212 33.8 25.1 67.5 150 138 340 33.8 67.5 150 340 33.8 67.5 150 340 212 32.2 147 Winding Resistance Line to Line (Ohms) 0.108 0.43 2.2 0.174 0.696 0.174 0.696 0.225 0.075 0.4 1.16 0.087 0.348 0.4 0.087 0.348 0.4 0.087 0.348 0.225 0.075 0.375 See Section F Introduction for more information. FE76 Section_Fe.indd 76 3/4/2008 8:07:10 AM Electrical Data - Copelametic Large Refrigerant-Cooled Compressors Model Volts PH 6RR2-4000-FSU 6RR2-4000-TSE 6RR2-4000-TSN 6RR2-4000-TSN 6RR2-400A-FSD 6RR2-400A-FSU 6RR2-400A-TSN 6RR2-400A-TSN 6RS2-4000-ES8 6RS2-4000-ES8 6RS2-4000-FSD 6RS2-4000-FSU 6RS2-4000-TSE 6RS2-4000-TSN 6RS2-4000-TSN 6RS2-400A-FSD 6RS2-400A-FSU 6RS2-400A-TSN 6RS2-400A-TSN 6RT1-3000-FSD 6RT1-3000-TSE 6RT1-3000-TSK 200 575 230 460 460 200 230 460 200/220 380 460 200 575 230 460 460 200 230 460 460 575 208/230 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 Across the Line Max RLA LRA 170 53.6 141.4 70.7 62 170 141.4 70.7 160 89.6 62 170 53.6 141.4 70.7 62 170 141.4 70.7 60.6 40 110.9 625 225 594 297 239 625 594 297 633 365 239 625 225 594 297 239 625 594 297 200 200 470 Part Winding Start Max RLA LRA 85 26.8 71 388 140 340 32.2 85 71 147 388 340 212 32.2 85 26.8 71 147 388 140 340 32.2 85 71 147 388 340 30 20 55.5 121 130 292 Winding Resistance Line to Line (Ohms) 0.066 1.14 0.085 0.34 0.375 0.066 0.085 0.34 0.225 0.075 0.375 0.066 1.14 0.085 0.34 0.375 0.066 0.085 0.34 0.475 1.46 0.108 See Section F Introduction for more information. FE77 Section_Fe.indd 77 3/4/2008 8:07:10 AM Electrical Data - Copelametic Large Refrigerant-Cooled Compressors Model Volts PH 6RT1-3000-TSK 6RT1-300A-TSK 6RT1-300A-TSK 6RT1-300L-TSK 6RT1-300L-TSK 6TM1-2000-TSE 6TM1-2000-TSK 6TM1-2000-TSK 8DP1R56M0-FSD 8DP1R56M0-TS7 8DP1R56M0-TSE 8DP1R56M0-TSK 8DP1R56M0-TSK 8DP3R56M0-FSD 8DP3R56M0-TSE 8DP3R56M0-TSK 8DP3R56M0-TSK 8DP3R56ME-FSD 8DP3R56ME-TSE 8DP3R56ME-TSK 8DP3R56ME-TSK 8DP3R56ML-FSD 460 208/230 460 208/230 460 575 208/230 460 460 380 575 208/230 460 460 575 208/230 460 460 575 208/230 460 460 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 Across the Line Max RLA LRA 55.5 110.9 55.5 110.9 55.5 28.2 65.7 32.9 90.7 114 75 180 90 90.7 75 180 90 90.7 75 180 90 90.7 235 470 235 470 235 135 308 154 510 740 405 1070 535 510 405 1070 535 510 405 1070 535 510 Part Winding Start Max RLA LRA 55.5 292 55.5 292 14.1 32.9 74 188 45.5 330 37.5 90 262 654 45.5 37.5 90 330 262 654 45.5 37.5 90 330 262 654 45.5 330 Winding Resistance Line to Line (Ohms) 0.43 0.108 0.43 0.108 0.43 2.2 0.174 0.696 0.147 0 0.456 0.039 0.156 0.147 0.456 0.039 0.156 0.147 0.456 0.039 0.156 0.147 See Section F Introduction for more information. FE78 Section_Fe.indd 78 3/4/2008 8:07:10 AM Electrical Data - Copelametic Large Refrigerant-Cooled Compressors Model Volts PH 8DP3R56ML-TSE 8DP3R56ML-TSK 8DP3R56ML-TSK 8DS1R67M0-FSD 8DS1R67M0-TS7 8DS1R67M0-TSE 8DS1R67M0-TSK 8DS1R67M0-TSK 8DS3R67M0-FSD 8DS3R67M0-TS7 8DS3R67M0-TSE 8DS3R67M0-TSK 8DS3R67M0-TSK 8DS3R67ME-FSD 8DS3R67ME-TS7 8DS3R67ME-TSE 8DS3R67ME-TSK 8DS3R67ME-TSK 8DS3R67ML-FSD 8DS3R67ML-TSE 8DS3R67ML-TSK 8DS3R67ML-TSK 575 208/230 460 460 380 575 208/230 460 460 380 575 208/230 460 460 380 575 208/230 460 460 575 208/230 460 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 Across the Line Max RLA LRA 75 180 90 96.4 130 80 224.3 112.1 96.4 130 80 224.3 112.1 96.4 130 80 224.3 112.1 96.4 80 224.3 112.1 405 1070 535 510 740 405 1070 535 510 740 405 1070 535 510 740 405 1070 535 510 405 1070 535 Part Winding Start Max RLA LRA 37.5 90 262 654 48.3 330 40 112 262 654 48.3 330 40 112 262 654 48.3 330 40 112 262 654 48.3 40 112 330 262 654 Winding Resistance Line to Line (Ohms) 0.456 0.039 0.156 0.147 0 0.456 0.039 0.156 0.147 0 0.456 0.039 0.156 0.147 0 0.456 0.039 0.156 0.147 0.456 0.039 0.156 See Section F Introduction for more information. FE79 Section_Fe.indd 79 3/4/2008 8:07:11 AM Electrical Data - Copelametic Large Refrigerant-Cooled Compressors Model Volts PH 9RS1-1015-TSU 9RS1-1505-TSC 9RS1-150A-TSC 9RS3-1015-TSU 9RT1-1505-TSC MRH4-0760-FSC 200 208/230 208/230 200 208/230 230 3 3 3 3 3 3 Across the Line Max RLA LRA NA 56.4 56.4 NA 56.4 NA 203 284 284 203 284 130 Part Winding Start Max RLA LRA 16.3 85 Winding Resistance Line to Line (Ohms) 0 0 0 0 0 0.41 See Section F Introduction for more information. FE80 Section_Fe.indd 80 3/4/2008 8:07:11 AM Electrical Data - Copeland Scroll® Model ZB10KCE-PFJ ZB10KCE-PFV ZB114KCE-TFD ZB114KCE-TW5 ZB114KCE-TW7 ZB114KCE-TWD ZB114KCE-TWE ZB114KQ-TFD ZB114KQ-TW5 ZB114KQ-TW7 ZB114KQ-TWD ZB114KQ-TWE ZB114KQE-TFD ZB114KQE-TW5 ZB114KQE-TW7 ZB114KQE-TWD ZB114KQE-TWE ZB11KCE-PFJ ZB11KCE-PFV ZB11MA-TW7 ZB11MA-TWC ZB11MA-TWD ZB11MA-TWE ZB11MC-TW7 ZB11MC-TWC ZB11MC-TWD Volts PH Max RLA LRA 265 208/230 460 200/230 380 460 575 460 200/230 380 460 575 460 200/230 380 460 575 265 208/230 380 208/230 460 575 380 208/230 460 1 1 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 1 1 3 3 3 3 3 3 3 8.2 10 28.6 65 42.9 32.1 25.7 27.9 58.6 35.7 28.6 23.6 28.6 65 42.9 32.1 25.7 8.6 10 36.4 53.6 26.4 23.6 27.9 51.6 24.3 38 41 179 340 196 173 132 179 340 196 173 132 179 340 196 173 132 39 45 239 425 187 148 239 425 187 Winding Resistance Start or Line/Line Run 3.4 2.73 0.833 0.226 0.56 0.833 1.268 0.833 0.226 0.56 0.833 1.268 0.833 0.226 0.56 0.833 1.268 3.24 2.27 0.52 0.19 0.72 1.08 0.52 0.19 0.72 2.16 1.77 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1.81 1.81 0 0 0 0 0 0 0 Run Cap PN 014-0064-07 014-0064-06 014-0064-07 014-0064-07 See Section F Introduction for more information. FF1 Section_Ff.indd 1 3/4/2008 8:09:50 AM Electrical Data - Copeland Scroll® Model ZB11MC-TWE ZB11MCE-TW7 ZB11MCE-TWC ZB11MCE-TWD ZB11MCE-TWE ZB13KCE-PFJ ZB13KCE-PFV ZB14KCE-PFJ ZB14KCE-PFV ZB15KC-PFJ ZB15KC-PFV ZB15KC-TF5 ZB15KC-TFD ZB15KCE-PFJ ZB15KCE-PFV ZB15KCE-TF5 ZB15KCE-TFD ZB15KQ-PFJ ZB15KQ-PFV ZB15KQ-TF5 ZB15KQ-TF7 ZB15KQ-TFD ZB15KQE-PFJ ZB15KQE-PFV ZB15KQE-TF5 ZB15KQE-TF7 Volts PH Max RLA LRA 575 380 208/230 460 575 265 208/230 265 208/230 265 208/230 200/230 460 265 208/230 200/230 460 265 208/230 200/230 380 460 265 208/230 200/230 380 3 3 3 3 3 1 1 1 1 1 1 3 3 1 1 3 3 1 1 3 3 3 1 1 3 3 19.4 32.5 60 28.2 22.5 10 12.9 11.1 13.6 11.4 13.6 8.9 4.3 13.2 15.7 8.9 5 11.4 13.6 8.9 5 4.3 13.2 15.7 8.9 5.1 148 239 425 187 148 55 54 52 63 58 61 55 27 58 61 55 27 58 61 55 23 27 58 61 55 27 Winding Resistance Start or Line/Line Run 1.08 0.52 0.19 0.72 1.08 2.75 2.67 2.86 2.45 3.34 2.28 1.79 7.1 3.34 2.28 1.79 7.1 3.34 2.28 1.79 7.1 7.1 3.34 2.28 1.79 7.1 0 0 0 0 0 1.81 1.31 1.5 1.17 1.26 1.01 0 0 1.26 1.01 0 0 1.26 1.01 0 0 0 1.26 1.01 0 0 Run Cap PN 014-0064-25 014-0064-07 014-0064-25 014-0064-07 014-0064-08 014-0064-08 014-0064-08 014-0064-08 014-0064-08 014-0064-08 014-0064-08 014-0064-08 See Section F Introduction for more information. FF2 Section_Ff.indd 2 3/4/2008 8:09:54 AM Electrical Data - Copeland Scroll® Model Volts PH Max RLA LRA ZB15KQE-TFD ZB19KC-PFJ ZB19KC-PFV ZB19KC-TF5 ZB19KC-TFD ZB19KCE-PFJ ZB19KCE-PFV ZB19KCE-TF5 ZB19KCE-TFD ZB19KQ-PFJ ZB19KQ-PFV ZB19KQ-TF5 ZB19KQ-TFD ZB19KQE-PFJ ZB19KQE-PFV ZB19KQE-TF5 ZB19KQE-TFD ZB21KC-PFJ ZB21KC-PFV ZB21KC-TF5 ZB21KC-TFD ZB21KCE-PFJ ZB21KCE-PFV ZB21KCE-TF5 ZB21KCE-TFD ZB21KQ-PFJ 460 265 208/230 200/230 460 265 208/230 200/230 460 265 208/230 200/230 460 265 208/230 200/230 460 265 208/230 200/230 460 265 208/230 200/230 460 265 3 1 1 3 3 1 1 3 3 1 1 3 3 1 1 3 3 1 1 3 3 1 1 3 3 1 5 12.9 15.7 8.2 4.3 13.2 17.9 8.2 5 12.9 15 10 4.3 14.6 17.1 10 5 16.4 17.9 11.4 5.7 16.4 20.7 12.1 6.1 16.4 27 61 73 63 31 61 73 63 31 61 72.5 63 31 61 72.5 63 31 83 100 77 39 83 100 77 39 83 Winding Resistance Start or Line/Line Run 7.1 2.23 2.71 1.46 5.94 2.23 2.71 1.46 5.94 2.23 1.72 1.46 5.94 2.23 1.72 1.46 5.94 1.84 2.82 1.234 4.83 1.84 2.82 1.234 4.83 1.84 0 1.2 0.908 0 0 1.2 0.908 0 0 1.2 0.905 0 0 1.2 0.905 0 0 0.887 0.64 0 0 0.887 0.64 0 0 0.887 Run Cap PN 014-0064-15 014-0064-25 014-0064-15 014-0064-25 014-0064-15 014-0064-25 014-0064-15 014-0064-25 014-0064-16 014-0064-29 014-0064-16 014-0064-29 014-0064-29 See Section F Introduction for more information. FF3 Section_Ff.indd 3 3/4/2008 8:09:54 AM Electrical Data - Copeland Scroll® Model Volts PH Max RLA LRA ZB21KQ-PFV ZB21KQ-TF5 ZB21KQ-TF7 ZB21KQ-TFD ZB21KQE-PFJ ZB21KQE-PFV ZB21KQE-TF5 ZB21KQE-TF7 ZB21KQE-TFD ZB26KC-PFJ ZB26KC-PFV ZB26KC-TF5 ZB26KC-TFD ZB26KCE-PFJ ZB26KCE-PFV ZB26KCE-TF5 ZB26KCE-TFD ZB26KQ-PFJ ZB26KQ-PFV ZB26KQ-TF5 ZB26KQ-TFD ZB26KQE-PFJ ZB26KQE-PFV ZB26KQE-TF5 ZB26KQE-TFD ZB29KQ-PFJ 208/230 200/230 380 460 265 208/230 200/230 380 460 265 208/230 200/230 460 265 208/230 200/230 460 265 208/230 200/230 460 265 208/230 200/230 460 265 1 3 3 3 1 1 3 3 3 1 1 3 3 1 1 3 3 1 1 3 3 1 1 3 3 1 18.4 11.4 7.5 5.7 16.4 20.7 12.1 7.4 7.4 17.1 20.7 13.9 7.1 18.9 23.6 13.9 7.1 17.1 20.4 13.9 7.1 18.9 23.6 13.2 6.4 19.3 95 77 39 39 83 95 77 39 39 98 127 88 44 98 127 88 44 98 109 88 44 98 109 88 44 113 Winding Resistance Start or Line/Line Run 1.39 1.234 4.83 4.83 1.84 1.39 1.234 4.83 4.83 1.65 2.15 0.995 4.03 1.65 2.15 0.995 4.03 1.65 1.28 0.995 4.03 1.65 1.28 0.995 4.03 1.67 0.65 0 0 0 0.887 0.65 0 0 0 0.691 0.506 0 0 0.691 0.506 0 0 0.691 0.54 0 0 0.691 0.54 0 0 0.586 Run Cap PN 014-0064-29 014-0064-29 014-0064-29 014-0064-18 014-0064-26 014-0064-18 014-0064-26 014-0064-18 014-0064-26 014-0064-18 014-0064-26 014-0064-18 See Section F Introduction for more information. FF4 Section_Ff.indd 4 3/4/2008 8:09:55 AM Electrical Data - Copeland Scroll® Model Volts PH Max RLA LRA ZB29KQ-PFV ZB29KQ-TF5 ZB29KQ-TF7 ZB29KQ-TFD ZB29KQE-PFJ ZB29KQE-PFV ZB29KQE-TF5 ZB29KQE-TF7 ZB29KQE-TFD ZB30KC-PFV ZB30KC-TF5 ZB30KC-TF7 ZB30KC-TFD ZB30KC-TFE ZB30KCE-PFV ZB30KCE-TF5 ZB30KCE-TF7 ZB30KCE-TFD ZB30KCE-TFE ZB30KQ-PFV ZB30KQ-TF5 ZB30KQ-TFD ZB30KQE-PFV ZB30KQE-TF5 ZB30KQE-TFD ZB38KC-PFV 208/230 200/230 380 460 265 208/230 200/230 380 460 208/230 200/230 380 460 575 208/230 200/230 380 460 575 208/230 200/230 460 208/230 200/230 460 208/230 1 3 3 3 1 1 3 3 3 1 3 3 3 3 1 3 3 3 3 1 3 3 1 3 3 1 22.1 16.4 9.3 7.9 20 25 17.1 9.6 7.9 25 15 8.6 7.4 6.4 26.8 15.7 8.8 7.5 6.4 25 15 7.4 26.8 15.7 8.6 30.1 137 91 54 50 113 137 91 54 50 132 115 57 47.5 40 132 115 57 47.5 40 132 115 47.5 132 115 47.5 175 Winding Resistance Start or Line/Line Run 1.34 0.994 2.76 3.88 1.67 1.34 0.994 2.76 3.88 2.089 0.808 2.77 3.58 5.72 2.089 0.808 2.77 3.58 5.72 2.089 0.808 3.65 2.089 0.808 3.65 1.204 0.46 0 0 0 0.586 0.46 0 0 0 0.454 0 0 0 0 0.454 0 0 0 0 0.454 0 0 0.454 0 0 0.327 Run Cap PN 014-0064-18 014-0064-18 014-0064-18 014-0064-26 014-0064-26 014-0064-26 014-0064-26 014-0064-27 See Section F Introduction for more information. FF5 Section_Ff.indd 5 3/4/2008 8:09:55 AM Electrical Data - Copeland Scroll® Model Volts PH Max RLA LRA ZB38KC-TF5 ZB38KC-TF7 ZB38KC-TFD ZB38KC-TFE ZB38KCE-PFV ZB38KCE-TF5 ZB38KCE-TF7 ZB38KCE-TFD ZB38KCE-TFE ZB38KQ-PFV ZB38KQ-TF5 ZB38KQ-TF7 ZB38KQ-TFD ZB38KQE-PFV ZB38KQE-TF5 ZB38KQE-TF7 ZB38KQE-TFD ZB42KC-PFJ ZB42KC-PFV ZB42KCE-PFJ ZB42KCE-PFV ZB45KC-TF5 ZB45KC-TFD ZB45KC-TFE ZB45KCE-TF5 ZB45KCE-TFD 200/230 380 460 575 208/230 200/230 380 460 575 208/230 200/230 380 460 208/230 200/230 380 460 265 208/230 265 208/230 200/230 460 575 200/230 460 3 3 3 3 1 3 3 3 3 1 3 3 3 1 3 3 3 1 1 1 1 3 3 3 3 3 20.7 10.4 8.9 7.1 31.1 22.1 10.4 9.6 7.1 30.1 20.7 10.7 9.6 30.8 24 12.4 10 28.2 27.9 31.4 31.4 20.7 11.5 7.9 22.5 11.5 115 64 63 50 175 115 64 63 50 144 128 64 63 144 128 64 63 160 129 160 129 156 70 54 156 70 Winding Resistance Start or Line/Line Run 0.671 2.3 2.65 4.31 1.204 0.671 2.3 2.65 4.31 1.328 0.726 2.3 2.72 1.328 0.726 2.3 2.72 1.921 0.779 1.921 0.779 0.562 2.27 3.56 0.562 2.27 0 0 0 0 0.327 0 0 0 0 0.383 0 0 0 0.383 0 0 0 0.415 0.432 0.415 0.432 0 0 0 0 0 Run Cap PN 014-0064-27 014-0064-27 014-0064-27 014-0064-16 014-0064-16 014-0064-16 014-0064-16 See Section F Introduction for more information. FF6 Section_Ff.indd 6 3/4/2008 8:09:55 AM Electrical Data - Copeland Scroll® Model Volts PH Max RLA LRA ZB45KCE-TFE ZB45KQ-TF5 ZB45KQ-TF7 ZB45KQ-TFD ZB45KQE-TF5 ZB45KQE-TF7 ZB45KQE-TFD ZB48KQ-TF5 ZB48KQ-TF7 ZB48KQ-TFD ZB48KQE-TF5 ZB48KQE-TFD ZB50KC-TF5 ZB50KC-TF7 ZB50KC-TFD ZB50KC-TFE ZB50KCE-TF5 ZB50KCE-TF7 ZB50KCE-TFD ZB50KCE-TFE ZB50KQ-TF5 ZB50KQ-TF7 ZB50KQ-TFD ZB50KQ-TFE ZB50KQE-TF5 ZB50KQE-TF7 575 200/230 380 460 200/230 380 460 200/230 380 460 200/230 460 200/230 380 460 575 200/230 380 460 575 200/230 380 460 575 200/230 380 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 7.9 20.7 10.7 11.5 23.1 12.6 10.1 25 12.1 12.1 26 13.6 28.6 15.7 14.3 9.6 28.6 18.2 15 9.6 28.6 15.7 14.3 9.6 28.6 18.2 54 156 70 75 156 70 75 164 100 100 164 100 196 135 100 90 196 135 100 90 196 135 100 90 196 135 Winding Resistance Start or Line/Line Run 3.56 0.562 1.92 2.27 0.562 1.92 2.27 0.501 1.79 1.79 0.501 1.79 0.44 1.174 1.764 2.989 0.44 1.174 1.764 2.989 0.44 1.174 1.764 2.989 0.44 1.174 Run Cap PN 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 See Section F Introduction for more information. FF7 Section_Ff.indd 7 3/4/2008 8:09:56 AM Electrical Data - Copeland Scroll® Model ZB50KQE-TFD ZB50KQE-TFE ZB56KA-TW7 ZB56KA-TWC ZB56KA-TWD ZB56KA-TWE ZB56KC-TW7 ZB56KC-TWC ZB56KC-TWD ZB56KC-TWE ZB56KCE-TW7 ZB56KCE-TWC ZB56KCE-TWD ZB56KCE-TWE ZB58KC-TF5 ZB58KC-TF7 ZB58KC-TFD ZB58KC-TFE ZB58KCE-TF5 ZB58KCE-TF7 ZB58KCE-TFD ZB58KCE-TFE ZB58KQ-TF5 ZB58KQ-TF7 ZB58KQ-TFD ZB58KQ-TFE Volts PH Max RLA LRA 460 575 380 208/230 460 575 380 208/230 460 575 380 208/230 460 575 200/230 380 460 575 200/230 380 460 575 200/230 380 460 575 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 15 9.6 16.6 26.4 13.9 10.1 16 25.8 13.5 9.9 18.6 30 15.7 9.9 32.1 16.7 16.4 12 32.1 17.1 16.4 12.9 32.1 16.7 16.4 12 100 90 112 189 99 74 112 189 99 74 112 189 99 74 195 123 95 80 195 123 95 80 195 123 95 80 Winding Resistance Start or Line/Line Run 1.764 2.989 1.03 0.37 1.41 2.3 1.03 0.37 1.41 2.3 1.03 0.37 1.41 2.3 0.4 1.051 1.799 2.55 0.4 1.051 1.799 2.55 0.4 1.051 1.799 2.55 Run Cap PN 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 See Section F Introduction for more information. FF8 Section_Ff.indd 8 3/4/2008 8:09:56 AM Electrical Data - Copeland Scroll® Model Volts PH Max RLA LRA ZB58KQE-TF5 ZB58KQE-TF7 ZB58KQE-TFD ZB58KQE-TFE ZB66KC-TF5 ZB66KC-TF7 ZB66KC-TFD ZB66KC-TFE ZB66KCE-TF5 ZB66KCE-TF7 ZB66KCE-TFD ZB66KCE-TFE ZB66KQ-TF5 ZB66KQ-TF7 ZB66KQ-TFD ZB66KQ-TFE ZB66KQE-TF5 ZB66KQE-TF7 ZB66KQE-TFD ZB66KQE-TFE ZB68KA-TW7 ZB68KA-TWC ZB68KA-TWD ZB68KA-TWE ZB75KA-TW7 ZB75KA-TWC 200/230 380 460 575 200/230 380 460 575 200/230 380 460 575 200/230 380 460 575 200/230 380 460 575 380 208/230 460 575 380 208/230 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 32.1 17.1 16.4 12.9 33.6 18.6 17.3 13.5 33.6 20.7 17.5 13.5 33.6 18.6 17.3 13.5 33.6 20.7 17.5 13.5 20.7 33.3 17 12.9 25.4 37.4 195 123 95 80 225 140 114 80 225 140 114 80 225 140 114 80 225 140 114 80 144 232 125 100 151 278 Winding Resistance Start or Line/Line Run 0.4 1.051 1.799 2.55 0.347 0.93 1.36 2.55 0.347 0.93 1.36 2.55 0.347 0.93 1.36 2.55 0.347 0.93 1.36 2.55 0.78 0.29 1.11 1.86 0.72 0.26 Run Cap PN 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 See Section F Introduction for more information. FF9 Section_Ff.indd 9 3/4/2008 8:09:56 AM Electrical Data - Copeland Scroll® Model ZB75KA-TWD ZB75KA-TWE ZB75KC-TW7 ZB75KC-TWC ZB75KC-TWD ZB75KC-TWE ZB75KCE-TW7 ZB75KCE-TWC ZB75KCE-TWD ZB75KCE-TWE ZB76KC-TF5 ZB76KC-TF7 ZB76KC-TFD ZB76KC-TFE ZB76KCE-TF5 ZB76KCE-TF7 ZB76KCE-TFD ZB76KCE-TFE ZB76KQ-TF5 ZB76KQ-TF7 ZB76KQ-TFD ZB76KQ-TFE ZB76KQE-TF5 ZB76KQE-TF7 ZB76KQE-TFD ZB76KQE-TFE Volts PH Max RLA LRA 460 575 380 208/230 460 575 380 208/230 460 575 200/230 380 460 575 200/230 380 460 575 200/230 380 460 575 200/230 380 460 575 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 18.4 15.2 20.6 37.5 18.1 13.9 23.9 43.6 21.1 16.1 41.4 23.6 19.2 13.8 41.4 23.6 20 13.8 41.4 23.6 19.2 13.8 41.4 23.6 20 13.8 127 100 151 278 127 100 151 278 127 100 239 145 125 80 239 145 125 80 239 145 125 80 239 145 125 80 Winding Resistance Start or Line/Line Run 1.02 1.7 0.72 0.26 1.02 1.7 0.72 0.26 1.02 1.7 0.306 0.85 1.227 2.55 0.306 0.85 1.227 2.55 0.306 0.85 1.227 2.55 0.306 0.85 1.227 2.55 Run Cap PN 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 See Section F Introduction for more information. FF10 Section_Ff.indd 10 3/4/2008 8:09:57 AM Electrical Data - Copeland Scroll® Model ZB88KC-TF5 ZB88KC-TF7 ZB88KC-TFD ZB88KC-TFE ZB88KCE-TF5 ZB88KCE-TF7 ZB88KCE-TFD ZB88KCE-TFE ZB88KQ-TF5 ZB88KQ-TF7 ZB88KQ-TFD ZB88KQ-TFE ZB88KQE-TF5 ZB88KQE-TF7 ZB88KQE-TFD ZB88KQE-TFE ZB92KA-TW7 ZB92KA-TWC ZB92KA-TWD ZB92KA-TWE ZB92KC-TW7 ZB92KC-TWC ZB92KC-TWD ZB92KC-TWE ZB92KCE-TW7 ZB92KCE-TWC Volts PH Max RLA LRA 200/230 380 460 575 200/230 380 460 575 200/230 380 460 575 200/230 380 460 575 380 208/230 460 575 380 208/230 460 575 380 208/230 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 47.1 24.4 19.6 15.9 47.1 24.4 20.7 15.9 47.1 24.4 20.7 15.9 47.1 24.4 20.7 15.9 27.9 45.7 24.3 19.3 24.3 45.4 21.5 17.2 28.2 52.9 245 145 125 100 245 145 125 100 245 145 125 100 245 145 125 100 195 350 158 125 195 350 158 125 195 350 Winding Resistance Start or Line/Line Run 0.282 0.85 1.227 1.87 0.282 0.85 1.227 1.87 0.282 0.85 1.227 1.87 0.282 0.85 1.227 1.87 0.57 0.22 0.83 1.28 0.57 0.22 0.83 1.28 0.57 0.22 Run Cap PN 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 See Section F Introduction for more information. FF11 Section_Ff.indd 11 3/4/2008 8:09:57 AM Electrical Data - Copeland Scroll® Model ZB92KCE-TWD ZB92KCE-TWE ZB95KCE-TFD ZB95KCE-TW5 ZB95KCE-TW7 ZB95KCE-TWD ZB95KCE-TWE ZB95KQ-TFD ZB95KQ-TW5 ZB95KQ-TW7 ZB95KQ-TWD ZB95KQ-TWE ZB95KQE-TFD ZB95KQE-TW5 ZB95KQE-TW7 ZB95KQE-TWD ZB95KQE-TWE ZBD30KC-TF5 ZBD30KC-TF7 ZBD30KC-TFD ZBD30KCE-TF5 ZBD30KCE-TFD ZBD45KC-TF5 ZBD45KC-TF7 ZBD45KC-TFD ZBD45KCE-TF5 Volts PH Max RLA LRA 460 575 460 200/230 380 460 575 460 200/230 380 460 575 460 200/230 380 460 575 200/230 380 460 200/230 460 200/230 380 460 200/230 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 25 20 26.4 61.4 35 31.4 22.9 25 53.6 28.6 24.3 20.7 26.4 61.4 35 31.4 22.9 15 8 7.4 15.7 7.4 20.7 12.5 10 22.5 158 125 150 300 139 150 109 150 300 139 150 109 150 300 139 150 109 99 57 47.5 99 47.5 156 70 70 156 Winding Resistance Start or Line/Line Run 0.83 1.28 1.1 0.227 0.853 1.108 1.518 1.1 0.227 0.853 1.108 1.518 1.1 0.227 0.853 1.108 1.518 0.911 2.78 3.64 0.911 3.64 0.562 1.92 2.27 0.562 Run Cap PN 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 See Section F Introduction for more information. FF12 Section_Ff.indd 12 3/4/2008 8:09:58 AM Electrical Data - Copeland Scroll® Model ZBD45KCE-TFD ZBH30KJE-TF5 ZBH30KJE-TF7 ZBH30KJE-TFD ZBH30KJE-TFE ZBH38KJE-TF5 ZBH38KJE-TF7 ZBH38KJE-TFD ZBH45KJE-TF5 ZBH45KJE-TF7 ZBH45KJE-TFD ZC40C1G-TF5 ZC40C1G-TFD ZC60C1G-TF5 ZC60C1G-TFD ZCH22C1G-PFJ ZCH22C1G-PFV ZCH48C2G-TF5 ZCH48C2G-TFD ZCH68C1G-TF5 ZCH68C1G-TFD ZCH68C2G-TFD ZCH72C2G-TF5 ZCH72C2G-TFD ZCH81C2G-TF5 ZCH81C2G-TFD Volts PH Max RLA LRA 460 200/230 380 460 575 200/230 380 460 200/230 380 460 200/230 460 200/230 460 265 208/230 200/230 460 200/230 460 460 200/230 460 200/230 460 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 1 1 3 3 3 3 3 3 3 3 3 10 15 8.2 8.2 6.4 21.4 11.4 9.6 23.9 12.9 9.3 12.9 6.9 21.4 8.9 10.7 12.9 16.4 7.9 24.3 10 10 22.9 10 23.6 13.6 70 99 57 49.5 40 123 64 62 156 70 70 108 47.5 156 70 47 47 91 50 164 75 75 156 75 164 100 Winding Resistance Start or Line/Line Run 2.27 0.911 0.911 3.64 5.72 0.686 0.686 2.75 0.501 2.27 2.27 0.803 3.65 0.501 2.27 2.85 2.06 0.994 3.88 0.501 2.27 2.27 0.501 2.27 0.501 1.79 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1.62 1.18 0 0 0 0 0 0 0 0 0 Run Cap PN 014-0064-14 014-0064-25 See Section F Introduction for more information. FF13 Section_Ff.indd 13 3/4/2008 8:09:58 AM Electrical Data - Copeland Scroll® Model ZCH94C1G-TF5 ZCH94C1G-TFD ZF06K4-PFV ZF06K4-TF5 ZF06K4-TFD ZF06K4E-PFV ZF06K4E-TF5 ZF06K4E-TFD ZF08K4-PFV ZF08K4-TF5 ZF08K4-TFD ZF08K4E-PFV ZF08K4E-TF5 ZF08K4E-TFD ZF09K4-PFV ZF09K4-TF5 ZF09K4-TFD ZF09K4-TFE ZF09K4E-PFV ZF09K4E-TF5 ZF09K4E-TFD ZF09K4E-TFE ZF11K4-PFV ZF11K4-TF5 ZF11K4-TFD ZF11K4E-PFV Volts PH Max RLA LRA 200/230 460 208/230 200/230 460 208/230 200/230 460 208/230 200/230 460 208/230 200/230 460 208/230 200/230 460 575 208/230 200/230 460 575 208/230 200/230 460 208/230 3 3 1 3 3 1 3 3 1 3 3 1 3 3 1 3 3 3 1 3 3 3 1 3 3 1 NA NA 13.6 7.9 3.6 13.6 9.3 4.3 16.4 7.9 3.9 16.4 9.6 5 17.9 10 5 4.3 16.4 9.6 5.7 4.3 20.7 12.5 6.4 20.7 195 95 61 55 27 61 55 27 73 63 31 73 63 31 88 77 39 31 88 77 39 31 109 88 44 109 Winding Resistance Start or Line/Line Run 1.979 1.799 2.28 1.79 7.1 2.28 1.79 7.1 1.72 1.46 5.94 1.72 1.46 5.94 1.46 1.234 4.83 7.89 1.46 1.234 4.83 7.89 1.28 0.995 4.03 1.28 0.553 0 1.01 0 0 1.01 0 0 0.833 0 0 0.833 0 0 0.691 0 0 0 0.691 0 0 0 0.54 0 0 0.54 Run Cap PN 014-0064-08 014-0064-08 014-0064-25 014-0064-25 014-0064-29 014-0064-29 014-0064-26 014-0064-26 See Section F Introduction for more information. FF14 Section_Ff.indd 14 3/4/2008 8:09:58 AM Electrical Data - Copeland Scroll® Model Volts PH Max RLA LRA ZF11K4E-TF5 ZF11K4E-TFD ZF11K4E-TFE ZF13K4-TF5 ZF13K4-TF7 ZF13K4-TFD ZF13K4E-PFV ZF13K4E-TF5 ZF13K4E-TF7 ZF13K4E-TFD ZF13K4E-TFE ZF13KVE-TF5 ZF13KVE-TF7 ZF13KVE-TFD ZF13KVE-TFE ZF15K4-TF5 ZF15K4-TF7 ZF15K4-TFD ZF15K4E-PFV ZF15K4E-TF5 ZF15K4E-TF7 ZF15K4E-TFD ZF15K4E-TFE ZF18K4-TF5 ZF18K4-TF7 ZF18K4-TFD 200/230 460 575 200/230 380 460 208/230 200/230 380 460 575 200/230 380 460 575 200/230 380 460 208/230 200/230 380 460 575 200/230 380 460 3 3 3 3 3 3 1 3 3 3 3 3 3 3 3 3 3 3 1 3 3 3 3 3 3 3 8.9 7.1 5 15 7.1 6.8 26.8 15 8.2 8.2 8.2 19.3 10.7 9.3 7.9 16.4 9.5 8.6 31.8 21.4 9.5 9.6 7.9 20 11.3 8.9 88 44 34 99 57 49.5 129 99 57 49.5 40 123 64 62 50 123 64 62 169 123 64 62 50 156 70 70 Winding Resistance Start or Line/Line Run 0.995 4.03 6.28 0.911 2.78 3.64 0.779 0.911 2.78 3.64 5.72 0.686 2.28 2.75 4.31 0.686 2.28 2.75 0.605 0.686 2.28 2.75 4.31 0.501 1.92 2.27 0 0 0 0 0 0 0.432 0 0 0 0 0 0 0 0 0 0 0 0.329 0 0 0 0 0 0 0 Run Cap PN 014-0064-26 014-0064-27 See Section F Introduction for more information. FF15 Section_Ff.indd 15 3/4/2008 8:09:59 AM Electrical Data - Copeland Scroll® Model ZF18K4-TFE ZF18K4E-TF5 ZF18K4E-TF7 ZF18K4E-TFD ZF18K4E-TFE ZF18KVE-TF5 ZF18KVE-TF7 ZF18KVE-TFD ZF18KVE-TFE ZF24K4-TW7 ZF24K4-TWC ZF24K4-TWD ZF24K4-TWE ZF24K4E-TW7 ZF24K4E-TWC ZF24K4E-TWD ZF24K4E-TWE ZF24KVE-TW7 ZF24KVE-TWC ZF24KVE-TWD ZF24KVE-TWE ZF33K4-TW7 ZF33K4-TWC ZF33K4-TWD ZF33K4-TWE ZF33K4E-TW7 Volts PH Max RLA LRA 575 200/230 380 460 575 200/230 380 460 575 380 208/230 460 575 380 208/230 460 575 380 208/230 460 575 380 208/230 460 575 380 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 7.1 23.9 12.6 9.3 7.9 23.9 12.9 9.3 9.3 14.3 22.9 11.4 8.9 18.6 30 15.7 8.9 18.6 30 15.7 11.4 16.6 30.1 16.4 11.6 23.9 54 156 70 70 54 156 70 70 54 112 189 99 74 112 189 99 74 112 189 99 74 151 278 127 100 151 Winding Resistance Start or Line/Line Run 3.56 0.501 1.92 2.27 3.56 0.562 1.92 2.27 3.56 1.03 0.37 1.41 2.3 1.03 0.37 1.41 2.3 1.03 0.37 1.41 2.3 0.72 0.26 1.02 1.7 0.72 Run Cap PN 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 See Section F Introduction for more information. FF16 Section_Ff.indd 16 3/4/2008 8:09:59 AM Electrical Data - Copeland Scroll® Model ZF33K4E-TWC ZF33K4E-TWD ZF33K4E-TWE ZF33KVE-TW7 ZF33KVE-TWC ZF33KVE-TWD ZF33KVE-TWE ZF40K4-TW7 ZF40K4-TWC ZF40K4-TWD ZF40K4-TWE ZF40K4E-TW7 ZF40K4E-TWC ZF40K4E-TWD ZF40K4E-TWE ZF40KVE-TW7 ZF40KVE-TWC ZF40KVE-TWD ZF40KVE-TWE ZF48K4-TW7 ZF48K4-TWC ZF48K4-TWD ZF48K4-TWE ZF48K4E-TW7 ZF48K4E-TWC ZF48K4E-TWD Volts PH Max RLA LRA 208/230 460 575 380 208/230 460 575 380 208/230 460 575 380 208/230 460 575 380 208/230 460 575 380 208/230 460 575 380 208/230 460 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 43.6 21.1 16.1 23.9 43.6 21.1 16.1 22.9 40.7 20 15.4 28.2 52.9 25 20 28.2 52.9 25 20 25 48.2 22.1 17.9 32.5 60 28.2 278 127 100 151 278 127 100 195 350 158 125 195 350 158 125 195 350 158 125 239 425 187 148 239 425 187 Winding Resistance Start or Line/Line Run 0.26 1.02 1.7 0.72 0.26 1.02 1.7 0.57 0.22 0.83 1.28 0.57 0.22 0.83 1.28 0.57 0.22 0.83 1.28 0.52 0.19 0.72 1.1 0.52 0.19 0.72 Run Cap PN 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 See Section F Introduction for more information. FF17 Section_Ff.indd 17 3/4/2008 8:10:00 AM Electrical Data - Copeland Scroll® Model Volts ZF48K4E-TWE 575 ZF48KVE-TW7 380 ZF48KVE-TWC 208/230 ZF48KVE-TWD 460 ZF48KVE-TWE 575 ZFD18KVE-TF5 200/230 ZFD18KVE-TF7 380 ZFD18KVE-TFD 460 ZH09KVE-TFD 460 ZH11M4E-TWD 460 ZH13KVE-PFJ 265 ZH13KVE-TFD 460 ZH15K4E-PFJ 265 ZH15K4E-TFD 460 ZH18KVE-TF5 200/230 ZH18KVE-TFD 460 ZH19K4E-PFJ 265 ZH19K4E-TFD 460 ZH21K4E-PFJ 265 ZH21K4E-TFD 460 ZH24KVE-TWD 460 ZH26K4E-PFJ 265 ZH26K4E-TFD 460 ZH30K4E-PFJ 265 ZH30K4E-TFD 460 ZH33KVE-TWD 460 PH Max RLA LRA 3 3 3 3 3 3 3 3 3 3 1 3 1 3 3 3 1 3 1 3 3 1 3 1 3 3 22.5 32.5 60 28.2 22.5 24.3 12.5 10.7 NA 30.7 NA 9.6 12.1 4.3 21.4 10.4 16.8 5 16.1 5.7 17.7 19.6 7.1 19.3 8.2 20.1 148 239 425 187 148 156 70 70 39 187 NA 62 58 27 156 100 76 31 75 35 99 98 44 110 49.5 127 Winding Resistance Start or Line/Line Run 1.1 0.52 0.19 0.72 1.1 0.501 1.92 2.27 4.83 0.72 1.224 2.75 3.34 7.1 0.562 1.79 1.89 5.94 2.07 2.74 1.394 1.65 1.85 1.947 3.64 1.002 0 0 0 0 0 0 0 0 0 0 0.417 0 1.26 0 0 0 0.981 0 0.937 0 0 0.691 0 0.599 0 0 Run Cap PN 014-0064-26 014-0064-14 014-0064-15 014-0064-16 014-0064-18 014-0064-15 See Section F Introduction for more information. FF18 Section_Ff.indd 18 3/4/2008 8:10:00 AM Electrical Data - Copeland Scroll® Model Volts ZH38K4E-TFD 460 ZH40KVE-TWD 460 ZH45K4E-TFD 460 ZH48KVE-TWD 460 ZH56K4E-TWD 460 ZH75K4E-TWD 460 ZH92K4E-TWD 460 ZM18K4E-TFD 460 ZMD18KVE-TFD 460 ZMD26KVE-TFD 460 ZNH13C2A-KXX 275 ZNH16C2A-KXX 275 ZNH22C2A-KXX 275 ZNH22C3A-KXX 275 ZNH28C2A-KXX 275 ZO104KCE-TFD 460 ZO34K3E-TFD 460 ZO45K3E-TFD 460 ZO58K3E-TFD 460 ZP103KCE-TF5 200/230 ZP103KCE-TFD 460 ZP103KCE-TFE 575 ZP120KCE-TF5 200/230 ZP120KCE-TF7 380 ZP120KCE-TFD 460 ZP120KCE-TFE 575 PH Max RLA LRA 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 9.6 23.1 9.6 27.1 16.4 22.9 27.1 9.3 10.7 10.4 NA NA NA NA NA NA NA NA NA 33.6 18.6 13.6 37.1 26.4 20 14.3 62 158 70 198 94 127 158 70 70 75 125 125 125 110 125 NA 27 35 46 225 114 80 239 145 125 80 Winding Resistance Start or Line/Line Run 2.75 0.83 2.27 0.72 1.394 1.002 0.83 2.27 2.27 2.26 0.458 0.458 0.458 0.571 0.458 2.26 7.15 5.35 3.88 0.347 1.36 2.55 0.306 0.85 1.227 2.55 Run Cap PN 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 See Section F Introduction for more information. FF19 Section_Ff.indd 19 3/4/2008 8:10:00 AM Electrical Data - Copeland Scroll® Model ZP137KCE-TF5 ZP137KCE-TF7 ZP137KCE-TFD ZP137KCE-TFE ZP154KCE-TF7 ZP154KCE-TFD ZP154KCE-TW5 ZP154KCE-TW7 ZP154KCE-TWD ZP154KCE-TWE ZP16K3E-PFV ZP16K5E-PFJ ZP16K5E-PFV ZP180KCE-TW7 ZP180KCE-TWC ZP180KCE-TWD ZP180KCE-TWE ZP182KCE-TFD ZP182KCE-TW5 ZP182KCE-TW7 ZP182KCE-TWD ZP182KCE-TWE ZP20K3E-PFJ ZP20K3E-PFV ZP20K3E-TF5 ZP20K3E-TFD Volts PH Max RLA LRA 200/230 380 460 575 380 460 200/230 380 460 575 208/230 265 208/230 380 208/230 460 575 460 200/230 380 460 575 265 208/230 200/230 460 3 3 3 3 3 3 3 3 3 3 1 1 1 3 3 3 3 3 3 3 3 3 1 1 3 3 53.6 26.4 20.7 16.4 27.1 25 57.1 30 25.7 22.1 11.4 7.9 10 40.1 59.1 26.4 26 29.3 62.1 37.9 30 26.4 12.1 14.3 8.6 4.4 245 145 125 100 138 150 300 139 150 109 51 43 48 239 425 187 148 179 340 196 173 132 58 60 55 22.4 Winding Resistance Start or Line/Line Run 0.282 0.85 1.227 1.87 0.845 1.1 0.227 0.853 1.108 1.518 1.87 1.79 2.303 0.52 0.19 0.72 1.1 0.833 0.226 0.56 0.833 1.268 3.34 1.856 1.79 8.64 0 0 0 0 0 0 0 0 0 0 1.32 1.79 1.53 0 0 0 0 0 0 0 0 0 1.26 1.073 0 0 Run Cap PN 014-0064-08 014-0064-07 014-0064-06 014-0064-08 014-0064-07 See Section F Introduction for more information. FF20 Section_Ff.indd 20 3/4/2008 8:10:01 AM Electrical Data - Copeland Scroll® Model ZP20K5E-PFJ ZP20K5E-PFV ZP21K5E-PFJ ZP21K5E-PFV ZP22KCE-PFV ZP235KCE-TW5 ZP235KCE-TW7 ZP235KCE-TWC ZP235KCE-TWD ZP235KCE-TWE ZP23K3E-PFJ ZP23K3E-PFV ZP23K3E-TF5 ZP23K3E-TFD ZP24K5E-PFJ ZP24K5E-PFV ZP24K5E-TF5 ZP24K5E-TFD ZP24K5E-TFE ZP25K5E-PFJ ZP25K5E-PFV ZP25K5E-TF5 ZP25K5E-TFE ZP26K3E-PFJ ZP26K3E-PFV ZP26K3E-TF5 Volts PH Max RLA LRA 265 208/230 265 208/230 208/230 200/230 380 230 460 575 265 208/230 200/230 460 265 208/230 200/230 460 575 265 208/230 200/230 575 265 208/230 200/230 1 1 1 1 1 3 3 3 3 3 1 1 3 3 1 1 3 3 3 1 1 3 3 1 1 3 10 15 10.7 14.3 15 82.4 42.6 82.4 33.9 27.4 12.1 15 9.3 5 12.1 14.3 9.3 5.7 3.7 12.5 15.7 9.9 3.9 13.9 16.4 11.6 54 58.3 54 58.3 61 505 290 505 225 180 58 61 63 27 60 64 58 28 22.5 60 73 58 24 61 72.5 63 Winding Resistance Start or Line/Line Run Run Cap PN 2.17 1.47 2.17 1.47 2.28 0.14 0.44 0.14 0.63 0.97 3.34 2.28 1.46 7.1 2.6 1.57 1.48 1.23 1.48 1.23 1.01 0 0 0 0 0 1.26 1.01 0 0 1.33 1.12 014-0064-08 014-0064-07 014-0064-08 014-0064-08 014-0064-08 2.6 1.78 1.33 0.98 014-0064-08 014-0064-08 2.23 1.72 1.46 1.2 0.905 0 014-0064-15 014-0064-25 014-0064-14 014-0064-08 014-0064-08 014-0064-08 See Section F Introduction for more information. FF21 Section_Ff.indd 21 3/4/2008 8:10:01 AM Electrical Data - Copeland Scroll® Model ZP26KCE-PFV ZP285KCE-TW5 ZP285KCE-TW7 ZP285KCE-TWC ZP285KCE-TWD ZP285KCE-TWE ZP28K5E-PFV ZP28K5E-TF5 ZP295KCE-TW7 ZP295KCE-TWC ZP295KCE-TWD ZP295KCE-TWE ZP29K5E-PFJ ZP29K5E-PFV ZP29K5E-TF5 ZP29K5E-TFD ZP29K5E-TFE ZP31K5E-PFJ ZP31K5E-PFV ZP31K5E-TF5 ZP31K5E-TFD ZP31K5E-TFE ZP32K3E-PFJ ZP32K3E-PFV ZP32K3E-TF5 ZP32K3E-TFD Volts PH Max RLA LRA 208/230 200/230 380 208/230 460 575 208/230 200/230 380 208/230 460 575 265 208/230 200/230 460 575 265 208/230 200/230 460 575 265 208/230 200/230 460 1 3 3 3 3 3 1 3 3 3 3 3 1 1 3 3 3 1 1 3 3 3 1 1 3 3 17.1 99.3 60.7 99.3 47.9 35.7 17.9 11.1 57.9 95 46.7 38.7 13.6 15.7 10 6.3 4.2 15 18.6 11.6 6.4 4.2 17.1 17.1 12.9 5.7 73 500 305 500 250 198 77 71 353 605 272 240 72 77 71 38 36.5 72 79 73 38 36.5 83 83 77 35 Winding Resistance Start or Line/Line Run Run Cap PN 2.71 0.112 0.311 0.112 0.45 0.701 1.44 0.908 0 0 0 0 0 0.9 014-0064-13 0.36 0.12 0.51 0.805 1.22 1.44 0 0 0 0 1.15 0.9 014-0064-26 014-0064-25 1.22 1.465 1.15 0.869 014-0064-26 014-0064-25 1.84 1.69 1.38 5.35 0.887 0.722 0 0 014-0064-16 014-0064-25 014-0064-25 See Section F Introduction for more information. FF22 Section_Ff.indd 22 3/4/2008 8:10:01 AM Electrical Data - Copeland Scroll® Model ZP32K3E-TFE ZP32KCE-PFV ZP34K5E-PFV ZP34K5E-TF5 ZP34K5E-TFD ZP36K3E-PFJ ZP36K3E-PFV ZP36K3E-TF5 ZP36K3E-TFD ZP36K3E-TFE ZP36K5E-PFJ ZP36K5E-PFV ZP36K5E-TF5 ZP36K5E-TFD ZP36K5E-TFE ZP385KCE-TW5 ZP385KCE-TW7 ZP385KCE-TWC ZP385KCE-TWD ZP385KCE-TWE ZP38K3E-PFV ZP38K3E-TF5 ZP38K3E-TFD ZP38K3E-TFE ZP38K5E-PFV ZP38K5E-TF5 Volts PH 575 208/230 208/230 200/230 460 265 208/230 200/230 460 575 265 208/230 200/230 460 575 200/230 380 208/230 460 575 208/230 200/230 460 575 208/230 200/230 3 1 1 3 3 1 1 3 3 3 1 1 3 3 3 3 3 3 3 3 1 3 3 3 1 3 Max RLA LRA 4.8 20 20 14.7 6.6 20 20.7 15 7.1 5.7 17.9 20 15.1 6.6 5.5 122.1 77.1 122.1 60.7 55 21.4 15 7.9 5.6 22.1 15.1 31 100 112 88 44 98 105 88 39 34 87 112 88 44 34 599 358 599 310 239 104 88 46 34 109 83.1 Winding Resistance Start or Line/Line Run 7.89 2.82 1.253 0.995 4.03 1.65 1.36 0.995 4.83 6.28 1.167 1.253 0.995 4.03 6.28 0.096 0.244 0.096 0.349 0.555 1.38 0.995 3.88 6.28 1.215 1.034 0 0.64 0.556 0 0 0.691 0.605 0 0 0 0.719 0.556 0 0 0 0 0 0 0 0 0.57 0 0 0 0.552 0 Run Cap PN 014-0064-14 014-0064-25 014-0064-18 014-0064-28 014-0064-26 014-0064-25 014-0064-28 014-0064-25 See Section F Introduction for more information. FF23 Section_Ff.indd 23 3/4/2008 8:10:02 AM Electrical Data - Copeland Scroll® Model Volts PH Max RLA LRA ZP38K5E-TFD ZP38KCE-PFV ZP39K5E-PFV ZP39K5E-TF5 ZP39K5E-TFD ZP41K3E-PFJ ZP41K3E-PFV ZP41K3E-TF5 ZP41K3E-TFD ZP41K3E-TFE ZP42K5E-PFJ ZP42K5E-PFV ZP42K5E-TF5 ZP42K5E-TFD ZP44K3E-PFV ZP44K3E-TF5 ZP44K3E-TFD ZP44K3E-TFE ZP44KCE-PFV ZP50K3E-PFJ ZP50K3E-PFV ZP50K3E-TF5 ZP50K3E-TFD ZP50K3E-TFE ZP51K5E-PFV ZP51K5E-TF5 460 208/230 208/230 200/230 460 265 208/230 200/230 460 575 265 208/230 200/230 460 208/230 200/230 460 575 208/230 265 208/230 200/230 460 575 208/230 200/230 3 1 1 3 3 1 1 3 3 3 1 1 3 3 1 3 3 3 1 1 1 3 3 3 1 3 6.8 22.1 22.1 14.6 6.8 20 22.9 16.2 7.9 5.7 18.1 24.3 15.3 6.9 25.7 17.9 7.9 6.2 27.1 23.6 30 19.6 10.7 6.8 29.4 17.8 41 131 109 83.1 41 98 109 91 46 34 98 117 83.1 41 134 91 46 37 131 133 145 123 62 40 134 110 Winding Resistance Start or Line/Line Run 4.17 1.78 1.215 1.034 4.17 1.65 1.28 0.994 3.88 6.28 0.885 0.817 1.034 4.17 1.45 0.994 3.88 6.21 1.85 0.76 0.593 0.686 2.8 5.72 0.792 0.68 0 0.525 0.552 0 0 0.691 0.54 0 0 0 0.701 0.517 0 0 0.49 0 0 0 0.475 0.49 0.398 0 0 0 0.453 0 Run Cap PN 014-0064-14 014-0064-25 014-0064-18 014-0064-26 014-0064-27 014-0064-34 014-0064-26 014-0064-29 014-0064-27 014-0064-27 014-0064-34 See Section F Introduction for more information. FF24 Section_Ff.indd 24 3/4/2008 8:10:02 AM Electrical Data - Copeland Scroll® Model ZP51K5E-TFD ZP51K5E-TFE ZP54K3E-PFV ZP54K3E-TF5 ZP54K3E-TFD ZP54K3E-TFE ZP54K5E-PFV ZP54K5E-TF5 ZP54K5E-TFD ZP54K5E-TFE ZP57K3E-PFJ ZP57K3E-PFV ZP57K3E-TF5 ZP57K3E-TFD ZP57K3E-TFE ZP57KCE-PFV ZP61KCE-TF5 ZP61KCE-TFD ZP61KCE-TFE ZP67KCE-TF5 ZP67KCE-TFD ZP67KCE-TFE ZP70KWE-PFJ ZP70KWE-PFV ZP72KCE-TF5 ZP72KCE-TF7 Volts PH Max RLA LRA 460 575 208/230 200/230 460 575 208/230 200/230 460 575 265 208/230 200/230 460 575 208/230 200/230 460 575 200/230 460 575 265 208/230 200/230 380 3 3 1 3 3 3 1 3 3 3 1 1 3 3 3 1 3 3 3 3 3 3 1 1 3 3 8.6 6.4 30.7 20.2 10 7.6 29.3 17.4 8.6 6.5 27.3 33.6 22.9 10.7 8.5 33.6 21.2 10.9 8.3 25 11.8 8.6 34.6 35.7 25.9 13.6 52 38.9 158 137 62 50 134 110 52 38.9 157 158 155 75 54 172 123 62 50 149 75 54 170 148 164 73 Winding Resistance Start or Line/Line Run 3.199 5.4 0.553 0.612 2.8 4.31 0.792 0.68 3.199 5.4 1.17 0.553 0.58 2.27 3.56 0.58 0.686 2.8 4.31 0.562 2.27 3.56 0.667 0.667 0.501 1.96 0 0 0.37 0 0 0 0.453 0 0 0 0.4 0.37 0 0 0 0.34 0 0 0 0 0 0 0.362 0.362 0 0 Run Cap PN 014-0064-27 014-0064-27 014-0064-16 014-0064-27 014-0064-27 014-0064-35 014-0064-27 See Section F Introduction for more information. FF25 Section_Ff.indd 25 3/4/2008 8:10:02 AM Electrical Data - Copeland Scroll® Model Volts ZP72KCE-TFD 460 ZP83KCE-TF5 200/230 ZP83KCE-TF7 380 ZP83KCE-TFD 460 ZP83KCE-TFE 575 ZP83KWE-PFV 208/230 ZP90KCE-TF5 200/230 ZP90KCE-TF7 380 ZP90KCE-TFD 460 ZP90KCE-TFE 575 ZPD61KCE-TF5 200/230 ZPD61KCE-TF7 380 ZPD61KCE-TFD 460 ZPD72KCE-TF5 200/230 ZPD72KCE-TF7 380 ZPD72KCE-TFD 460 ZPD83KCE-TF7 380 ZPD83KCE-TFD 460 ZPDT14MCE-TF7 380 ZPDT14MCE-TFD 460 ZPDT16MCE-TFD 460 ZPDU13MCE-TFD 460 ZPS20K4E-PFV 208/230 ZPS26K4E-PFV 208/230 ZPS30K4E-PFV 208/230 ZPS30K4E-TF5 200/230 PH 3 3 3 3 3 1 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 1 1 1 3 Winding Resistance Start or Line/Line Run Max RLA LRA 12.5 27.9 15.5 13.6 10 35.7 32.9 18.6 16.4 13.6 22.7 12.1 10.9 25.9 13.6 12.5 15.9 14.1 75 164 94.3 100 78 185 195 123 95 80 156 64 62 164 73 75 94.3 100 2.26 0.501 1.64 1.79 2.76 0.874 0.4 1.051 1.59 2.55 0.562 2.3 2.8 0.501 1.96 2.26 1.64 1.79 0 0 0 0 0 0.312 0 0 0 0 0 0 0 0 0 0 0 0 11.4 15.7 18.6 12.4 52 70 82 58 1.4 1.249 1.29 1.562 1.32 0.891 0.892 0 Run Cap PN 014-0064-35 014-0064-07 014-0064-08 014-0064-08 See Section F Introduction for more information. FF26 Section_Ff.indd 26 3/4/2008 8:10:03 AM Electrical Data - Copeland Scroll® Model ZPS30K4E-TFD ZPS35K4E-PFV ZPS35K4E-TF5 ZPS35K4E-TFD ZPS40K4E-PFV ZPS40K4E-TF5 ZPS40K4E-TFD ZPS49K4E-PFV ZPS49K4E-TF5 ZPS49K4E-TFD ZPS51K4E-PFV ZPS51K4E-TF5 ZPS51K4E-TFD ZPS51K4E-TFE ZPS60K4E-PFV ZPT100K3E-TF5 ZPT100K3E-TF5 ZPT100K3E-TFD ZPT100K3E-TFD ZPT100K3E-TFE ZPT100K3E-TFE ZPT108K3E-TF5 ZPT108K3E-TF5 ZPT108K3E-TFD ZPT108K3E-TFD ZPT114K3E-PFV Volts PH 460 208/230 200/230 460 208/230 200/230 460 208/230 200/230 460 208/230 200/230 460 575 208/230 200/230 200/230 460 460 575 575 200/230 200/230 460 460 208/230 3 1 3 3 1 3 3 1 3 3 1 3 3 3 1 3 3 3 3 3 3 3 3 3 3 1 Max RLA LRA 5 18.6 15 6.8 23.6 15 7.1 25.6 19.6 10.3 28.6 19.6 10 8.2 30.4 29 96 88 44 96 88 41 118 123 62 118 123 62 50 150 Winding Resistance Start or Line/Line Run 6.02 1.547 0.995 4.03 1.52 0.995 4.17 0.601 0.686 2.8 0.601 0.686 2.8 4.31 0.533 0 0.621 0 0 0.635 0 0 0.49 0 0 0.49 0 0 0 0.37 Run Cap PN 014-0064-25 014-0064-25 014-0064-27 014-0064-27 014-0064-27 See Section F Introduction for more information. FF27 Section_Ff.indd 27 3/4/2008 8:10:03 AM Electrical Data - Copeland Scroll® Model Volts ZPT114K3E-TF5 200/230 ZPT114K3E-TF5 200/230 ZPT114K3E-TFD 460 ZPT114K3E-TFD 460 ZPT122KCE-TF5 200/230 ZPT122KCE-TF5 200/230 ZPT122KCE-TFD 460 ZPT122KCE-TFD 460 ZPT134KCE-TF5 200/230 ZPT134KCE-TF5 200/230 ZPT134KCE-TFD 460 ZPT134KCE-TFD 460 ZPT144KCE-TF5 200/230 ZPT144KCE-TF5 200/230 ZPT144KCE-TF7 380 ZPT144KCE-TF7 380 ZPT144KCE-TFD 460 ZPT144KCE-TFD 460 ZPT166KCE-TF5 200/230 ZPT166KCE-TF5 200/230 ZPT166KCE-TF7 380 ZPT166KCE-TF7 380 ZPT166KCE-TFD 460 ZPT166KCE-TFD 460 ZPT166KCE-TFE 575 ZPT166KCE-TFE 575 PH Max RLA LRA Winding Resistance Start or Line/Line Run Run Cap PN 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 See Section F Introduction for more information. FF28 Section_Ff.indd 28 3/4/2008 8:10:03 AM Electrical Data - Copeland Scroll® Model Volts ZPT180KCE-TF5 200/230 ZPT180KCE-TF5 200/230 ZPT180KCE-TFD 460 ZPT180KCE-TFD 460 ZPT180KCE-TFE 575 ZPT180KCE-TFE 575 ZPT206KCE-TF5 200/230 ZPT206KCE-TF5 200/230 ZPT206KCE-TFD 460 ZPT206KCE-TFD 460 ZPT206KCE-TFE 575 ZPT206KCE-TFE 575 ZPT240KCE-TF5 200/230 ZPT240KCE-TF5 200/230 ZPT240KCE-TFD 460 ZPT240KCE-TFD 460 ZPT240KCE-TFE 575 ZPT240KCE-TFE 575 ZPT274KCE-TF5 200/230 ZPT274KCE-TF5 200/230 ZPT274KCE-TFD 460 ZPT274KCE-TFD 460 ZPT274KCE-TFE 575 ZPT274KCE-TFE 575 ZPT308KCE-TFD 460 ZPT308KCE-TW5200/230 PH Max RLA LRA Winding Resistance Start or Line/Line Run Run Cap PN 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 See Section F Introduction for more information. FF29 Section_Ff.indd 29 3/4/2008 8:10:04 AM Electrical Data - Copeland Scroll® Model Volts ZPT308KCE-TWD 460 ZPT308KCE-TWE 575 ZPT360KCE-TW7 380 ZPT360KCE-TWC208/230 ZPT360KCE-TWD 460 ZPT360KCE-TWE 575 ZPT364KCE-TW5200/230 ZPT364KCE-TWD 460 ZPT364KCE-TWE 575 ZPT470KCE-TW7 380 ZPT470KCE-TWC 230 ZPT470KCE-TWD 460 ZPT470KCE-TWE 575 ZPT570KCE-TW5200/230 ZPT570KCE-TW7 380 ZPT570KCE-TWC208/230 ZPT570KCE-TWD 460 ZPT570KCE-TWE 575 ZPT590KCE-TW7 380 ZPT590KCE-TWC208/230 ZPT590KCE-TWD 460 ZPT590KCE-TWE 575 ZPT770KCE-TW5200/230 ZPT770KCE-TW5200/230 ZPT770KCE-TW7 380 ZPT770KCE-TW7 380 PH Max RLA LRA Winding Resistance Start or Line/Line Run Run Cap PN 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 See Section F Introduction for more information. FF30 Section_Ff.indd 30 3/4/2008 8:10:04 AM Electrical Data - Copeland Scroll® Model Volts ZPT770KCE-TWC208/230 ZPT770KCE-TWC208/230 ZPT770KCE-TWD 460 ZPT770KCE-TWD 460 ZPT770KCE-TWE 575 ZPT770KCE-TWE 575 ZPU223KCE-TFD 460 ZPU240KCE-TFD 460 ZPU257KCE-TFD 460 ZPU272KCE-TFD 460 ZPU272KCE-TXD 460 ZPU272KCE-TXE 575 ZPU274KCE-TFD 460 ZPU274KCE-TX5 200/230 ZPU274KCE-TXD 460 ZPU274KCE-TXE 575 ZPU285KCE-TFD 460 ZPU285KCE-TX5 200/230 ZPU285KCE-TXD 460 ZPU285KCE-TXE 575 ZPU302KCE-TFD 460 ZPU302KCE-TX5 200/230 ZPU302KCE-TXD 460 ZPU302KCE-TXE 575 ZPU319KCE-TFD 460 ZPU319KCE-TX5 200/230 PH Max RLA LRA Winding Resistance Start or Line/Line Run Run Cap PN 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 See Section F Introduction for more information. FF31 Section_Ff.indd 31 3/4/2008 8:10:04 AM Electrical Data - Copeland Scroll® Model Volts ZPU319KCE-TXD 460 ZPU319KCE-TXE 575 ZPU336KCE-TFD 460 ZPU336KCE-TW5200/230 ZPU336KCE-TW7 380 ZPU336KCE-TWD 460 ZPU336KCE-TWE 575 ZPU417KCE-TWC200/230 ZPU417KCE-TWC 230 ZPU417KCE-TWD 460 ZPU417KCE-TWE 575 ZPU520KCE-TWD 460 ZPU680KCE-TW7 380 ZPU680KCE-TWC208/230 ZPU680KCE-TWD 460 ZPU680KCE-TWE 575 ZPY115MCE-TW5200/230 ZPY115MCE-TW7 380 ZPY115MCE-TWC208/230 ZPY115MCE-TWD 460 ZPY115MCE-TWE 575 ZPY309KCE-TF5 200/230 ZPY309KCE-TFD 460 ZPY309KCE-TFE 575 ZPY360KCE-TF5 200/230 ZPY360KCE-TFD 460 PH Max RLA LRA Winding Resistance Start or Line/Line Run Run Cap PN 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 See Section F Introduction for more information. FF32 Section_Ff.indd 32 3/4/2008 8:10:05 AM Electrical Data - Copeland Scroll® Model Volts ZPY360KCE-TFE 575 ZPY411KCE-TF5 200/230 ZPY411KCE-TFD 460 ZPY411KCE-TFE 575 ZPY462KCE-TFD 460 ZPY462KCE-TW5200/230 ZPY462KCE-TW7 380 ZPY462KCE-TWD 460 ZPY462KCE-TWE 575 ZPY546KCE-TFD 460 ZPY546KCE-TW5200/230 ZPY546KCE-TW7 380 ZPY546KCE-TWD 460 ZPY546KCE-TWE 575 ZPY705KCE-TW7 380 ZPY705KCE-TWC 230 ZPY705KCE-TWD 460 ZPY705KCE-TWE 575 ZPY855KCE-TW5200/230 ZPY855KCE-TW7 380 ZPY855KCE-TWC208/230 ZPY855KCE-TWD 460 ZPY855KCE-TWE 575 ZR108KC-TF5 200/230 ZR108KC-TF7 380 ZR108KC-TFD 460 PH Max RLA LRA 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 33.6 18.6 17.3 225 140 114 Winding Resistance Start or Line/Line Run 0.347 0.93 1.36 Run Cap PN 0 0 0 See Section F Introduction for more information. FF33 Section_Ff.indd 33 3/4/2008 8:10:05 AM Electrical Data - Copeland Scroll® Model ZR108KC-TFE ZR108KCE-TF5 ZR108KCE-TF7 ZR108KCE-TFD ZR108KCE-TFE ZR11M3-TW7 ZR11M3-TWC ZR11M3-TWD ZR11M3-TWE ZR11M3E-TW7 ZR11M3E-TWC ZR11M3E-TWD ZR11M3E-TWE ZR125KC-TF5 ZR125KC-TF7 ZR125KC-TFD ZR125KC-TFE ZR125KCE-TF5 ZR125KCE-TF7 ZR125KCE-TFD ZR125KCE-TFE ZR12M3-TW5 ZR12M3-TW7 ZR12M3-TWC ZR12M3-TWD ZR12M3-TWE Volts PH Max RLA LRA 575 200/230 380 460 575 380 208/230 460 575 380 208/230 460 575 200/230 380 460 575 200/230 380 460 575 200/230 380 208/230 460 575 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 13.5 33.6 18.6 17.3 13.5 20.7 33.3 17 12.9 24.9 38.2 18.6 15.4 41.4 23.6 19.2 13.8 41.4 23.6 20 13.8 37.4 25.4 37.4 18.4 15.2 80 225 140 114 80 144 232 125 100 144 232 125 100 239 145 125 80 239 145 125 80 278 151 278 127 100 Winding Resistance Start or Line/Line Run 2.55 0.347 0.93 1.36 2.55 0.78 0.29 1.11 1.86 0.78 0.29 1.11 1.86 0.306 0.85 1.227 2.55 0.306 0.85 1.227 2.55 0.26 0.72 0.26 1.02 1.7 Run Cap PN 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 See Section F Introduction for more information. FF34 Section_Ff.indd 34 3/4/2008 8:10:06 AM Electrical Data - Copeland Scroll® Model ZR12M3E-TW5 ZR12M3E-TW7 ZR12M3E-TWC ZR12M3E-TWD ZR12M3E-TWE ZR144KC-TF5 ZR144KC-TF7 ZR144KC-TFD ZR144KC-TFE ZR144KCE-TF5 ZR144KCE-TF7 ZR144KCE-TFD ZR144KCE-TFE ZR160KC-TF7 ZR160KC-TFD ZR160KC-TW5 ZR160KC-TW7 ZR160KC-TWD ZR160KC-TWE ZR160KCE-TF7 ZR160KCE-TFD ZR160KCE-TW5 ZR160KCE-TW7 ZR160KCE-TWD ZR160KCE-TWE ZR16K4-PFJ Volts PH Max RLA LRA 200/230 380 208/230 460 575 200/230 380 460 575 200/230 380 460 575 380 460 200/230 380 460 575 380 460 200/230 380 460 575 265 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 1 41.1 30.3 41.1 22.1 18.3 47.1 24.4 19.6 15.9 47.1 24.6 20.7 15.9 27.1 25 53.6 28.6 24.3 20.7 27.1 25 55 30.7 25.7 21.4 8.6 278 151 278 127 100 245 145 125 100 245 145 125 100 138 150 300 139 150 109 138 150 300 139 150 109 38 Winding Resistance Start or Line/Line Run 0.26 0.72 0.26 1.02 1.7 0.282 0.85 1.227 1.87 0.282 0.85 1.227 1.87 0.845 1.1 0.227 0.853 1.108 1.518 0.845 1.1 0.227 0.853 1.108 1.518 3.4 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 2.16 Run Cap PN 014-0064-07 See Section F Introduction for more information. FF35 Section_Ff.indd 35 3/4/2008 8:10:06 AM Electrical Data - Copeland Scroll® Model ZR16K4-PFV ZR16K4E-PFJ ZR16K4E-PFV ZR16KA-PFV ZR16M3-TW5 ZR16M3-TW7 ZR16M3-TWC ZR16M3-TWD ZR16M3-TWE ZR16M3E-TW5 ZR16M3E-TW7 ZR16M3E-TWC ZR16M3E-TWD ZR16M3E-TWE ZR18K3-PFV ZR18K3E-PFV ZR18K4-PFJ ZR18K4-PFV ZR18K4E-PFJ ZR18K4E-PFV ZR18KC-PFV ZR190KC-TFD ZR190KC-TW5 ZR190KC-TW7 ZR190KC-TWD ZR190KC-TWE Volts PH Max RLA LRA 208/230 265 208/230 208/230 200/230 380 208/230 460 575 200/230 380 208/230 460 575 208/230 208/230 265 208/230 265 208/230 208/230 460 200/230 380 460 575 1 1 1 1 3 3 3 3 3 3 3 3 3 3 1 1 1 1 1 1 1 3 3 3 3 3 10 8.6 10 8.6 45.7 27.9 45.7 24.3 19.3 48.9 30 48.9 27.2 19.3 9.3 9.3 8.6 10.7 8.6 10.7 10.7 27.9 58.6 35.7 28.6 23.6 41 38 41 40.3 350 195 350 158 125 350 195 350 158 125 47 47 39 45 39 45 47 179 340 196 173 132 Winding Resistance Start or Line/Line Run 2.73 3.4 2.73 2.61 0.22 0.57 0.22 0.83 1.28 0.22 0.57 0.22 0.83 1.28 2.67 2.67 3.24 2.27 3.24 2.27 3.48 0.833 0.226 0.56 0.833 1.268 1.77 2.16 1.77 1.74 0 0 0 0 0 0 0 0 0 0 1.43 1.43 1.81 1.81 1.81 1.81 1.56 0 0 0 0 0 Run Cap PN 014-0064-06 014-0064-07 014-0064-06 014-0064-06 014-0064-06 014-0064-06 014-0064-13 014-0064-07 014-0064-13 014-0064-07 014-0064-06 See Section F Introduction for more information. FF36 Section_Ff.indd 36 3/4/2008 8:10:06 AM Electrical Data - Copeland Scroll® Model ZR190KCE-TFD ZR190KCE-TW5 ZR190KCE-TW7 ZR190KCE-TWD ZR190KCE-TWE ZR19M3-TW5 ZR19M3-TW7 ZR19M3-TWC ZR19M3-TWD ZR19M3-TWE ZR19M3E-TW5 ZR19M3E-TW7 ZR19M3E-TWC ZR19M3E-TWD ZR19M3E-TWE ZR21KA-PFV ZR22K3-PFJ ZR22K3-PFV ZR22K3-TF5 ZR22K3-TFD ZR22K3E-PFJ ZR22K3E-PFV ZR22K3E-TF5 ZR22K3E-TFD ZR22K4-PFJ ZR22K4-PFV Volts PH Max RLA LRA 460 200/230 380 460 575 200/230 380 208/230 460 575 200/230 380 208/230 460 575 208/230 265 208/230 200/230 460 265 208/230 200/230 460 265 208/230 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 1 1 1 3 3 1 1 3 3 1 1 27.9 60 37.1 31.4 25 53.6 36.4 53.6 26.4 23.6 55 37.1 55 32.1 25.7 11.6 9.6 11.4 7.9 3.9 9.6 11.4 7.9 3.9 10 12.1 179 340 196 173 132 425 239 425 187 148 425 239 425 187 148 54 47 56 45 22.4 47 56 45 22.4 55 54 Winding Resistance Start or Line/Line Run 0.833 0.226 0.56 0.833 1.268 0.19 0.52 0.19 0.72 1.1 0.19 0.52 0.19 0.72 1.1 2.14 2.85 2.06 2.15 8.64 2.85 2.06 2.15 8.64 2.75 2.67 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1.27 1.62 1.18 0 0 1.62 1.18 0 0 1.81 1.31 Run Cap PN 014-0064-07 014-0064-14 014-0064-25 014-0064-14 014-0064-25 014-0064-25 014-0064-07 See Section F Introduction for more information. FF37 Section_Ff.indd 37 3/4/2008 8:10:07 AM Electrical Data - Copeland Scroll® Model ZR22K4E-PFJ ZR22K4E-PFV ZR24K3-PFJ ZR24K3-PFV ZR24K3-TF5 ZR24K3-TFD ZR24K3E-PFJ ZR24K3E-PFV ZR24K3E-TF5 ZR24K3E-TFD ZR24K4-PFJ ZR24K4-PFV ZR24K4E-PFJ ZR24K4E-PFV ZR24KL-PFV ZR250KC-TW5 ZR250KC-TW7 ZR250KC-TWC ZR250KC-TWD ZR250KC-TWE ZR250KCE-TW5 ZR250KCE-TW7 ZR250KCE-TWC ZR250KCE-TWD ZR250KCE-TWE ZR26K3-PFJ Volts PH Max RLA LRA 265 208/230 265 208/230 200/230 460 265 208/230 200/230 460 265 208/230 265 208/230 208/230 200/230 380 208/230 460 575 200/230 380 208/230 460 575 265 1 1 1 1 3 3 1 1 3 3 1 1 1 1 1 3 3 3 3 3 3 3 3 3 3 1 10 12.1 11.4 13.6 8.6 4.3 11.4 13.6 8.6 4.3 10.4 13.6 10.4 13.6 13.6 81.4 42.1 81.4 33.6 27.1 81.4 42.1 81.4 37.9 32.1 12.1 55 54 58 61 55 27 58 61 55 27 52 63 52 63 61 505 280 505 225 180 505 280 505 225 180 58 Winding Resistance Start or Line/Line Run 2.75 2.67 3.34 2.28 1.79 7.1 3.34 2.28 1.79 7.1 2.86 2.45 2.86 2.45 2.28 0.14 0.44 0.14 0.63 0.97 0.14 0.44 0.14 0.63 0.97 2.94 1.81 1.31 1.26 1.01 0 0 1.26 1.01 0 0 1.5 1.17 1.5 1.17 1.01 0 0 0 0 0 0 0 0 0 0 1.23 Run Cap PN 014-0064-25 014-0064-07 014-0064-14 014-0064-08 014-0064-14 014-0064-08 014-0064-25 014-0064-07 014-0064-25 014-0064-07 014-0064-08 014-0064-14 See Section F Introduction for more information. FF38 Section_Ff.indd 38 3/4/2008 8:10:07 AM Electrical Data - Copeland Scroll® Model ZR26K3-PFV ZR26K3-TF5 ZR26K3-TFD ZR26K3E-PFJ ZR26K3E-PFV ZR26K3E-TF5 ZR26KA-PFV ZR26KA-TF5 ZR26KC-PFV ZR26KL-PFV ZR28K3-PFJ ZR28K3-PFV ZR28K3-TF5 ZR28K3-TFD ZR28K3E-PFJ ZR28K3E-PFV ZR28K3E-TF5 ZR28K3E-TFD ZR28KA-PFV ZR28KC-PFV ZR300KC-TW5 ZR300KC-TW7 ZR300KC-TWC ZR300KC-TWD ZR300KC-TWE ZR300KCE-TW5 Volts PH Max RLA LRA 208/230 200/230 460 265 208/230 200/230 208/230 200/230 208/230 208/230 265 208/230 200/230 460 265 208/230 200/230 460 208/230 208/230 208/230 380 208/230 460 575 208/230 1 3 3 1 1 3 1 3 1 1 1 1 3 3 1 1 3 3 1 1 3 3 3 3 3 3 13.6 8.6 4.3 12.1 13.6 8.6 15.7 8.6 15 13.6 12.9 15 10 5 12.9 15 10 5 15.7 15.7 87.9 54.3 87.9 42.9 34.3 81.4 67 55 27 58 67 55 68 58 73 67 61 72.5 63 31 61 72.5 63 31 68 73 500 305 500 250 198 500 Winding Resistance Start or Line/Line Run 1.96 1.79 7.1 2.94 1.96 1.79 1.34 0.94 0 0 1.23 0.94 0 0.92 3.16 1.96 2.23 1.72 1.46 5.94 2.23 1.72 1.46 5.94 1.34 2.71 0.112 0.311 0.112 0.45 0.701 0.112 0.99 0.94 1.2 0.905 0 0 1.2 0.905 0 0 0.92 0.908 0 0 0 0 0 0 Run Cap PN 014-0064-08 014-0064-14 014-0064-08 014-0064-25 014-0064-12 014-0064-08 014-0064-15 014-0064-25 014-0064-15 014-0064-25 014-0064-25 014-0064-13 See Section F Introduction for more information. FF39 Section_Ff.indd 39 3/4/2008 8:10:07 AM Electrical Data - Copeland Scroll® Model ZR300KCE-TW7 ZR300KCE-TWC ZR300KCE-TWD ZR300KCE-TWE ZR30K3-PFJ ZR30K3-PFV ZR30K3-TF5 ZR30K3-TFD ZR30K3-TFE ZR30K3E-PFJ ZR30K3E-PFV ZR30K3E-TF5 ZR30K3E-TFD ZR30K3E-TFE ZR30KC-PFV ZR30KS-TFD ZR310KC-TW7 ZR310KC-TWC ZR310KC-TWD ZR310KCE-TW7 ZR310KCE-TWC ZR310KCE-TWD ZR32K3-PFJ ZR32K3-PFV ZR32K3-TF5 ZR32K3-TFD Volts PH Max RLA LRA 380 208/230 460 575 265 208/230 200/230 460 575 265 208/230 200/230 460 575 208/230 460 380 208/230 460 380 208/230 460 265 208/230 200/230 460 3 3 3 3 1 1 3 3 3 1 1 3 3 3 1 3 3 3 3 3 3 3 1 1 3 3 61.4 81.4 48.6 36.4 14.3 15 10.7 5 4.3 14.3 15 10.7 5 4.3 16.4 5.7 55.7 93.6 41.4 55.7 87.1 43.6 14.3 16.4 10.7 5.4 305 500 250 198 76 73 63 31 24 76 73 63 31 24 84 44.4 353 605 272 353 605 272 76 83 77 35 Winding Resistance Start or Line/Line Run 0.311 0.112 0.45 0.701 1.89 1.72 1.46 5.94 9.2 1.89 1.72 1.46 5.94 9.2 2.51 0 0 0 0 0.981 0.833 0 0 0 0.981 0.833 0 0 0 0.787 0.36 0.12 0.51 0.36 0.12 0.51 1.89 1.69 1.38 5.35 0 0 0 0 0 0 0.981 0.722 0 0 Run Cap PN 014-0064-15 014-0064-25 014-0064-15 014-0064-25 014-0064-07 014-0064-15 014-0064-25 See Section F Introduction for more information. FF40 Section_Ff.indd 40 3/4/2008 8:10:08 AM Electrical Data - Copeland Scroll® Model Volts PH Max RLA LRA ZR32K3-TFE ZR32K3E-PFJ ZR32K3E-PFV ZR32K3E-TF5 ZR32K3E-TFD ZR32K3E-TFE ZR32KA-PFV ZR32KA-TF5 ZR32KA-TFD ZR32KA-TFE ZR32KS-TFD ZR34K3-PFJ ZR34K3-PFV ZR34K3-TF5 ZR34K3-TF7 ZR34K3-TFD ZR34K3-TFE ZR34K3E-PFJ ZR34K3E-PFV ZR34K3E-TF5 ZR34K3E-TF7 ZR34K3E-TFD ZR34K3E-TFE ZR34KA-PFV ZR34KA-TF5 ZR34KA-TFD 575 265 208/230 200/230 460 575 208/230 200/230 460 575 460 265 208/230 200/230 380 460 575 265 208/230 200/230 380 460 575 208/230 200/230 460 3 1 1 3 3 3 1 3 3 3 3 1 1 3 3 3 3 1 1 3 3 3 3 1 3 3 3.9 14.3 16.4 10.7 5.4 3.9 16.1 10.7 6.4 4.5 5.7 14.3 17.9 11.4 6.8 5.7 4.7 14.3 17.9 11.4 6.8 5.7 4.7 16.4 12.1 6.4 28 76 83 77 35 28 77 73 38 28 44.4 75 88 77 39 39 31 75 88 77 39 39 31 77 73 38 Winding Resistance Start or Line/Line Run 8.38 1.89 1.69 1.38 5.35 8.38 1.07 0 0.981 0.722 0 0 0 0.839 2.07 1.46 1.234 4.83 4.83 7.89 2.07 1.46 1.234 4.83 4.83 7.89 1.07 0.937 0.691 0 0 0 0 0.937 0.691 0 0 0 0 0.839 Run Cap PN 014-0064-15 014-0064-25 014-0064-29 014-0064-16 014-0064-29 014-0064-16 014-0064-29 014-0064-26 See Section F Introduction for more information. FF41 Section_Ff.indd 41 3/4/2008 8:10:08 AM Electrical Data - Copeland Scroll® Model ZR34KA-TFE ZR34KC-PFV ZR34KH-PFJ ZR34KH-TFD ZR34KL-PFV ZR34KL-TF5 ZR36K3-PFJ ZR36K3-PFV ZR36K3-TF5 ZR36K3-TFD ZR36K3-TFE ZR36K3E-PFJ ZR36K3E-PFV ZR36K3E-TF5 ZR36K3E-TFD ZR36K3E-TFE ZR36KC-PFV ZR36KH-PFJ ZR36KH-TFD ZR380KC-TW5 ZR380KC-TW7 ZR380KC-TWC ZR380KC-TWD ZR380KC-TWE ZR380KCE-TW5 ZR380KCE-TW7 Volts PH 575 208/230 265 460 208/230 200/230 265 208/230 200/230 460 575 265 208/230 200/230 460 575 208/230 265 460 200/230 380 208/230 460 575 200/230 380 3 1 1 3 1 3 1 1 3 3 3 1 1 3 3 3 1 1 3 3 3 3 3 3 3 3 Max RLA LRA 3.9 15.7 17.1 7.1 17.9 11.4 16.4 18.4 11.4 5.7 4.7 16.4 18.4 11.4 5.7 4.7 17.9 17.1 6.4 111.4 63.6 111.4 54.3 43.6 121.4 68.6 36.5 93 102 39 88 77 83 95 77 39 31 83 95 77 39 31 100 96 39 599 358 599 310 239 599 358 Winding Resistance Start or Line/Line Run 1.9 1.81 4.83 1.46 1.234 1.84 1.39 1.234 4.83 7.89 1.84 1.39 1.234 4.83 7.89 2.82 1.81 4.83 0.096 0.244 0.096 0.349 0.555 0.096 0.244 0.74 0.753 0 0.691 0 0.887 0.65 0 0 0 0.887 0.65 0 0 0 0.64 0.753 0 0 0 0 0 0 0 0 Run Cap PN 014-0064-08 014-0064-17 014-0064-29 014-0064-16 014-0064-29 014-0064-16 014-0064-29 014-0064-14 014-0064-17 See Section F Introduction for more information. FF42 Section_Ff.indd 42 3/4/2008 8:10:08 AM Electrical Data - Copeland Scroll® Model ZR380KCE-TWC ZR380KCE-TWD ZR380KCE-TWE ZR38KA-PFV ZR38KA-TF5 ZR38KA-TFD ZR38KA-TFE ZR39KH-PFJ ZR39KH-TFD ZR40K3-PFJ ZR40K3-PFV ZR40K3-TF5 ZR40K3-TFD ZR40K3-TFE ZR40K3E-PFJ ZR40K3E-PFV ZR40K3E-TF5 ZR40K3E-TFD ZR40K3E-TFE ZR40KC-PFV ZR42K3-PFJ ZR42K3-PFV ZR42K3-TF5 ZR42K3-TFD ZR42K3-TFE ZR42K3E-PFJ Volts PH 208/230 460 575 208/230 200/230 460 575 265 460 265 208/230 200/230 460 575 265 208/230 200/230 460 575 208/230 265 208/230 200/230 460 575 265 3 3 3 1 3 3 3 1 3 1 1 3 3 3 1 1 3 3 3 1 1 1 3 3 3 1 Max RLA LRA 121.4 59.3 47.1 21.4 13.6 6.4 4.6 22.9 7.9 17.1 20 13.9 6.4 5.4 17.1 20 13.9 6.4 5.4 20 17.1 20.4 13.9 7.1 5.4 17.1 599 310 239 104 88 44 33 113 44 96 104 88 44 34 96 104 88 44 34 103 98 109 88 44 34 98 Winding Resistance Start or Line/Line Run 0.096 0.349 0.555 1.38 0.995 4.03 6.32 1.67 4.03 1.81 1.38 0.995 4.03 6.28 1.81 1.38 0.995 4.03 6.28 2.94 1.65 1.28 0.995 4.03 6.28 1.65 0 0 0 0.57 0 0 0 0.586 0 0.753 0.57 0 0 0 0.753 0.57 0 0 0 0.598 0.691 0.54 0 0 0 0.691 Run Cap PN 014-0064-28 014-0064-18 014-0064-17 014-0064-28 014-0064-17 014-0064-28 014-0064-14 014-0064-18 014-0064-26 014-0064-18 See Section F Introduction for more information. FF43 Section_Ff.indd 43 3/4/2008 8:10:09 AM Electrical Data - Copeland Scroll® Model Volts PH Max RLA LRA ZR42K3E-PFV ZR42K3E-TF5 ZR42K3E-TFD ZR42K3E-TFE ZR42KA-PFV ZR42KA-TF5 ZR42KA-TFD ZR42KA-TFE ZR42KC-PFV ZR44KA-PFV ZR44KA-TF5 ZR44KA-TFD ZR44KA-TFE ZR45K3-PFJ ZR45K3-PFV ZR45K3-TF5 ZR45K3-TFD ZR45K3E-PFJ ZR45K3E-PFV ZR45KC-PFV ZR45KC-TF5 ZR45KC-TFD ZR45KC-TFE ZR45KCE-TFD ZR46K3-PFV ZR46K3-TF5 208/230 200/230 460 575 208/230 200/230 460 575 208/230 208/230 200/230 460 575 265 208/230 200/230 460 265 208/230 208/230 200/230 460 575 460 208/230 200/230 1 3 3 3 1 3 3 3 1 1 3 3 3 1 1 3 3 1 1 1 3 3 3 3 1 3 20.4 13.9 7.1 5.4 21.4 13.6 6.4 5.1 20.7 22.5 13.6 6.8 4.6 19.3 23.6 15.4 7.9 19.3 23.6 24.3 14.3 7.1 5.7 7.1 26.4 15 109 88 44 34 97 88 44 37 127 137 83.1 41 33 113 137 91 46 113 137 131 91 46 37 46 129 120 Winding Resistance Start or Line/Line Run 1.28 0.995 4.03 6.28 1.374 0.995 4.03 6.21 2.15 1.34 1.034 4.17 6.32 1.67 1.34 0.994 3.88 1.67 1.34 1.85 0.994 3.88 6.21 3.88 0.765 0.797 0.54 0 0 0 0.595 0 0 0 0.506 0.46 0 0 0 0.586 0.46 0 0 0.586 0.46 0.475 0 0 0 0 0.475 0 Run Cap PN 014-0064-26 014-0064-28 014-0064-14 014-0064-26 014-0064-18 014-0064-18 014-0064-18 014-0064-18 014-0064-08 014-0064-26 See Section F Introduction for more information. FF44 Section_Ff.indd 44 3/4/2008 8:10:09 AM Electrical Data - Copeland Scroll® Model Volts PH Max RLA LRA ZR46K3-TFD ZR46K3-TFE ZR46KC-TF5 ZR46KC-TF7 ZR46KC-TFD ZR46KCE-TF5 ZR47K3-PFJ ZR47K3-PFV ZR47K3-TF5 ZR47K3-TFD ZR47K3-TFE ZR47K3E-PFJ ZR47K3E-PFV ZR47K3E-TF5 ZR47K3E-TFD ZR47K3E-TFE ZR47KC-PFV ZR47KC-TF5 ZR47KC-TF7 ZR47KC-TFD ZR47KC-TFE ZR47KCE-TF5 ZR47KCE-TF7 ZR47KCE-TFD ZR47KCE-TFE ZR48K3-PFJ 460 575 200/230 380 460 200/230 265 208/230 200/230 460 575 265 208/230 200/230 460 575 208/230 200/230 380 380/460 575 200/230 380 380/460 575 265 3 3 3 3 3 3 1 1 3 3 3 1 1 3 3 3 1 3 3 3 3 3 3 3 3 1 8.2 6.4 15 8 7.4 16.1 19.3 21.4 16.4 7.9 5.7 19.3 21.4 16.4 7.9 5.7 24.3 14.3 9.3 7.1 5.7 14.3 9.3 7.1 5.7 19.3 49.5 40 108 57 47.5 115 113 137 91 50 37 113 137 91 50 37 131 91 54 46 37 91 54 46 37 113 Winding Resistance Start or Line/Line Run 3.64 5.72 0.803 2.77 3.58 0.808 1.67 1.34 0.994 3.88 6.21 1.67 1.34 0.994 3.88 6.21 1.85 0.994 2.76 3.88 6.21 0.994 2.76 3.88 6.21 1.67 0 0 0 0 0 0 0.586 0.46 0 0 0 0.586 0.46 0 0 0 0.475 0 0 0 0 0 0 0 0 0.586 Run Cap PN 014-0064-18 014-0064-18 014-0064-18 014-0064-18 014-0064-25 014-0064-18 See Section F Introduction for more information. FF45 Section_Ff.indd 45 3/4/2008 8:10:09 AM Electrical Data - Copeland Scroll® Model Volts PH Max RLA LRA ZR48K3-PFV ZR48K3-TF5 ZR48K3-TFD ZR48K3-TFE ZR48K3E-PFJ ZR48K3E-PFV ZR48K3E-TF5 ZR48K3E-TFD ZR48K3E-TFE ZR48KC-PFV ZR48KC-TF5 ZR48KC-TF7 ZR48KC-TFD ZR48KC-TFE ZR48KCE-PFV ZR48KCE-TF5 ZR48KCE-TF7 ZR48KCE-TFD ZR48KCE-TFE ZR49K3-PFV ZR49K3-TF5 ZR49K3-TFD ZR49K3-TFE ZR49K3E-TFD ZR49KC-PFV ZR49KC-TF5 208/230 200/230 460 575 265 208/230 200/230 460 575 208/230 200/230 380 460 575 208/230 200/230 380 460 575 208/230 200/230 460 575 460 208/230 200/230 1 3 3 3 1 1 3 3 3 1 3 3 3 3 1 3 3 3 3 1 3 3 3 3 1 3 22.1 16.4 7.9 5.7 19.3 22.1 16.4 7.9 5.7 23.6 16.4 9.3 7.9 6.4 23.6 16.4 9.3 7.9 6.4 26.4 15 8.2 6.4 8.2 25 15 137 91 50 37 113 137 91 50 37 132 91 54 50 37 132 91 54 50 37 129 120 49.5 40 49.5 132 115 Winding Resistance Start or Line/Line Run 1.34 0.994 3.88 6.21 1.67 1.34 0.994 3.88 6.21 2.75 0.994 2.76 3.88 6.21 2.75 0.994 2.76 3.88 6.21 0.779 0.797 3.64 5.72 3.64 2.089 0.808 0.46 0 0 0 0.586 0.46 0 0 0 0.437 0 0 0 0 0.437 0 0 0 0 0.432 0 0 0 0 0.454 0 Run Cap PN 014-0064-18 014-0064-18 014-0064-18 014-0064-14 014-0064-14 014-0064-26 014-0064-15 See Section F Introduction for more information. FF46 Section_Ff.indd 46 3/4/2008 8:10:10 AM Electrical Data - Copeland Scroll® Model Volts PH Max RLA LRA ZR49KC-TF7 ZR49KC-TFD ZR49KC-TFE ZR49KCE-PFV ZR49KCE-TF5 ZR49KCE-TF7 ZR49KCE-TFD ZR49KCE-TFE ZR52K3-PFV ZR52K3-TF5 ZR52K3-TFD ZR52K3-TFE ZR54K3-PFV ZR54K3-TF5 ZR54K3-TFD ZR54K3-TFE ZR54K3E-TF5 ZR54K3E-TFD ZR54K3E-TFE ZR54KA-PFV ZR54KA-TF5 ZR54KA-TFD ZR54KA-TFE ZR54KC-PFV ZR54KC-TF5 ZR54KC-TF7 380 460 575 208/230 200/230 380 460 575 208/230 200/230 460 575 208/230 200/230 460 575 200/230 460 575 208/230 200/230 460 575 208/230 200/230 380 3 3 3 1 3 3 3 3 1 3 3 3 1 3 3 3 3 3 3 1 3 3 3 1 3 3 8.8 7.4 5.9 25 15 8.8 7.4 5.9 27.9 17.1 7.5 5.7 27.9 19.3 7.5 6.4 19.3 7.5 6.4 28.2 17.1 7.9 5.9 28.6 16.4 9.3 57 47.5 37.5 132 115 57 47.5 37.5 148 128 49.5 40 148 123 49.5 40 123 49.5 40 141 110 52 38.9 150 124 65.8 Winding Resistance Start or Line/Line Run 2.77 3.58 6.26 2.089 0.808 2.77 3.58 6.26 0.572 0.686 3.64 5.72 0.572 0.686 3.64 5.72 0.686 3.64 5.72 0.768 0.68 3.199 5.4 1.12 0.735 2.46 0 0 0 0.454 0 0 0 0 0.406 0 0 0 0.406 0 0 0 0 0 0 0.461 0 0 0 0.386 0 0 Run Cap PN 014-0064-15 014-0064-27 014-0064-27 014-0064-27 014-0064-26 See Section F Introduction for more information. FF47 Section_Ff.indd 47 3/4/2008 8:10:10 AM Electrical Data - Copeland Scroll® Model Volts PH Max RLA LRA ZR54KC-TFD ZR54KC-TFE ZR54KCE-TF5 ZR54KCE-TF7 ZR54KCE-TFD ZR54KCE-TFE ZR54KS-TF5 ZR54KS-TF7 ZR54KS-TFD ZR54KSE-TF5 ZR54KSE-TFD ZR57K3-PFV ZR57K3-TF5 ZR57K3-TFD ZR57K3-TFE ZR57K3E-TF5 ZR57K3E-TFD ZR57K3E-TFE ZR57KC-PFV ZR57KC-TF5 ZR57KC-TF7 ZR57KC-TFD ZR57KC-TFE ZR57KCE-TF5 ZR57KCE-TFD ZR57KCE-TFE 460 575 200/230 380 460 575 200/230 380 460 200/230 460 208/230 200/230 460 575 200/230 460 575 208/230 200/230 380 380/460 575 200/230 380/460 575 3 3 3 3 3 3 3 3 3 3 3 1 3 3 3 3 3 3 1 3 3 3 3 3 3 3 8.3 6.6 16.4 9.3 8.3 6.6 18.3 9.9 10 18.3 10 32.1 19.3 9.1 7.9 19.3 9.1 7.9 27.9 17.2 10.7 8.3 6.6 17.2 8.3 6.6 59.6 49.4 124 65.8 59.6 49.4 125 65 59 125 59 148 123 62 50 123 62 50 150 124 75 59.6 49.4 124 59.6 49.4 Winding Resistance Start or Line/Line Run 2.9 4.74 0.735 2.46 2.9 4.74 0.69 2.13 2.78 0.69 2.78 0.667 0.686 2.75 4.31 0.686 2.75 4.31 1.12 0.735 1.98 2.9 4.74 0.735 2.9 4.74 0 0 0 0 0 0 0 0 0 0 0 0.362 0 0 0 0 0 0 0.386 0 0 0 0 0 0 0 Run Cap PN 014-0064-27 014-0064-26 See Section F Introduction for more information. FF48 Section_Ff.indd 48 3/4/2008 8:10:11 AM Electrical Data - Copeland Scroll® Model Volts PH Max RLA LRA ZR57KH-TFD ZR57KS-TF5 ZR57KS-TF7 ZR57KS-TFD ZR57KSE-TF5 ZR57KSE-TFD ZR61K3-PFV ZR61K3-TF5 ZR61K3-TFD ZR61K3-TFE ZR61K3E-PFV ZR61K3E-TF5 ZR61K3E-TFD ZR61K3E-TFE ZR61KC-PFV ZR61KC-TF5 ZR61KC-TF7 ZR61KC-TFD ZR61KC-TFE ZR61KCE-PFV ZR61KCE-TF5 ZR61KCE-TF7 ZR61KCE-TFD ZR61KCE-TFE ZR61KH-TFD ZR61KS-TF5 460 200/230 380 460 200/230 460 208/230 200/230 460 575 208/230 200/230 460 575 208/230 200/230 380 460 575 208/230 200/230 380 460 575 460 200/230 3 3 3 3 3 3 1 3 3 3 1 3 3 3 1 3 3 3 3 1 3 3 3 3 3 3 10 18 10.9 NA 18 NA 32.1 19.3 9.1 7.9 32.1 19.3 9.1 7.9 30.1 20.7 10.7 10 7.4 26.4 20.7 10.7 10 7.4 11.4 22.9 62 125 65 59 125 59 148 137 62 50 148 137 62 50 144 128 64 63 49 144 128 64 63 49 68 125 Winding Resistance Start or Line/Line Run 2.75 0.69 2.13 2.78 0.69 2.78 0.654 0.612 2.75 4.31 0.654 0.612 2.75 4.31 1.328 0.726 2.3 2.72 4.44 1.328 0.726 2.3 2.72 4.44 2.673 0.69 0 0 0 0 0 0 0.355 0 0 0 0.355 0 0 0 0.383 0 0 0 0 0.383 0 0 0 0 0 0 Run Cap PN 014-0064-27 014-0064-27 014-0064-34 014-0064-34 See Section F Introduction for more information. FF49 Section_Ff.indd 49 3/4/2008 8:10:11 AM Electrical Data - Copeland Scroll® Model Volts PH Max RLA LRA ZR61KS-TF7 ZR61KS-TFD ZR61KSE-TFD ZR67KW-PFV ZR68KC-PFJ ZR68KC-PFV ZR68KC-TF5 ZR68KC-TF7 ZR68KC-TFD ZR68KC-TFE ZR68KCE-PFJ ZR68KCE-PFV ZR68KCE-TF5 ZR68KCE-TF7 ZR68KCE-TFD ZR68KCE-TFE ZR72KC-TF5 ZR72KC-TF7 ZR72KC-TFD ZR72KC-TFE ZR72KCE-TF5 ZR72KCE-TF7 ZR72KCE-TFD ZR72KCE-TFE ZR72KS-TFD ZR80KW-PFV 380 460 460 208/230 265 208/230 200/230 380 460 575 265 208/230 200/230 380 460 575 200/230 380 460 575 200/230 380 460 575 380/460 208/230 3 3 3 1 1 1 3 3 3 3 1 1 3 3 3 3 3 3 3 3 3 3 3 3 3 1 11.8 10 10 27.9 30.7 32.1 20.7 10.7 10 8.2 30.7 32.1 20.7 10.7 10 8.2 20.7 10.7 10 8.2 20.7 10.7 10 8.2 10 31.4 65 56 56 129 160 176 156 70 75 54 160 176 156 70 75 54 156 70 75 54 156 70 75 54 75 176 Winding Resistance Start or Line/Line Run 2.13 2.78 2.78 0.779 1.921 1.408 0.562 1.92 2.27 3.56 1.921 1.408 0.562 1.92 2.27 3.56 0.562 1.92 2.27 3.56 0.562 1.92 2.27 3.56 2.27 1.408 0 0 0 0.432 0.415 0.346 0 0 0 0 0.415 0.346 0 0 0 0 0 0 0 0 0 0 0 0 0 0.346 Run Cap PN 014-0064-26 014-0064-16 014-0064-35 014-0064-16 014-0064-35 014-0064-35 See Section F Introduction for more information. FF50 Section_Ff.indd 50 3/4/2008 8:10:11 AM Electrical Data - Copeland Scroll® Model ZR81KC-TF5 ZR81KC-TF7 ZR81KC-TFD ZR81KC-TFE ZR81KCE-TF5 ZR81KCE-TF7 ZR81KCE-TFD ZR81KCE-TFE ZR84KC-TF5 ZR84KC-TF7 ZR84KC-TFD ZR84KC-TFE ZR84KCE-TF5 ZR84KCE-TF7 ZR84KCE-TFD ZR84KCE-TFE ZR90K3-TW5 ZR90K3-TW7 ZR90K3-TWC ZR90K3-TWD ZR90K3-TWE ZR90K3E-TW5 ZR90K3E-TW7 ZR90K3E-TWC ZR90K3E-TWD ZR90K3E-TWE Volts PH Max RLA LRA 200/230 380 460 575 200/230 380 460 575 200/230 380 460 575 200/230 380 460 575 200/230 380 208/230 460 575 200/230 380 208/230 460 575 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 25 12.1 12.1 9.3 25 12.1 12.1 9.3 28.6 15.7 14.3 9.6 28.6 15.7 14.3 9.6 26.4 16.6 26.4 13.9 10.1 33.6 16.6 33.6 15.4 11.4 164 100 100 78 164 100 100 78 196 135 100 90 196 135 100 90 189 112 189 99 74 189 112 189 99 74 Winding Resistance Start or Line/Line Run 0.501 1.79 1.79 2.76 0.501 1.79 1.79 2.76 0.44 1.174 1.764 2.989 0.44 1.174 1.764 2.989 0.348 1.03 0.37 1.41 2.3 0.348 1.03 0.37 1.41 2.3 Run Cap PN 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 See Section F Introduction for more information. FF51 Section_Ff.indd 51 3/4/2008 8:10:12 AM Electrical Data - Copeland Scroll® Model Volts ZR94KC-TF5 200/230 ZR94KC-TF7 380 ZR94KC-TFD 460 ZR94KC-TFE 575 ZR94KCE-TF5 200/230 ZR94KCE-TF7 380 ZR94KCE-TFD 460 ZR94KCE-TFE 575 ZRD125KC-TF5 200/230 ZRD125KC-TF7 380 ZRD125KC-TFD 460 ZRD125KC-TFE 575 ZRD125KCE-TF5 200/230 ZRD125KCE-TF7 380 ZRD125KCE-TFD 460 ZRD125KCE-TFE 575 ZRD36KC-PFV 208/230 ZRD36KC-TF5 200/230 ZRD36KCE-PFV 208/230 ZRD36KCE-TF5 200/230 ZRD42KC-TFD 460 ZRD42KCE-PFJ 265 ZRD42KCE-TFD 460 ZRD48KC-PFV 208/230 ZRD48KC-TF5 200/230 ZRD48KC-TF7 380 PH Max RLA LRA 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 1 3 1 3 3 1 3 1 3 3 32.1 16.7 16.4 12 32.1 17.1 16.4 12 41.4 23.6 19.2 13.8 41.4 23.6 19.2 13.8 18.6 12.1 18.6 11.4 7.1 19.3 7.1 22.9 17.1 9.3 195 123 95 80 195 123 95 80 239 145 125 80 239 145 125 80 95 77 95 77 44 98 44 137 110 54 Winding Resistance Start or Line/Line Run 0.4 1.051 1.799 2.55 0.4 1.051 1.799 2.55 0.306 0.85 1.227 2.55 0.306 0.85 1.227 2.55 1.39 1.234 1.39 1.234 4.03 1.65 4.03 1.339 0.432 2.76 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0.65 0 0.65 0 0 0.691 0 0.462 0 0 Run Cap PN 014-0064-29 014-0064-29 014-0064-18 014-0064-26 See Section F Introduction for more information. FF52 Section_Ff.indd 52 3/4/2008 8:10:12 AM Electrical Data - Copeland Scroll® Model ZRD48KC-TFD ZRD48KCE-PFV ZRD48KCE-TF5 ZRD48KCE-TF7 ZRD48KCE-TFD ZRD49KC-PFV ZRD49KC-TF5 ZRD49KC-TF7 ZRD49KC-TFD ZRD49KCE-TF5 ZRD49KCE-TF7 ZRD49KCE-TFD ZRD61KC-PFV ZRD61KC-TF5 ZRD61KC-TF7 ZRD61KC-TFD ZRD61KC-TFE ZRD61KCE-PFV ZRD61KCE-TF5 ZRD61KCE-TF7 ZRD61KCE-TFD ZRD68KC-TFD ZRD68KCE-TFD ZRD72KC-TF5 ZRD72KC-TF7 ZRD72KC-TFD Volts PH Max RLA LRA 460 208/230 200/230 380 460 208/230 200/230 380 460 200/230 380 460 208/230 200/230 380 460 575 208/230 200/230 380 460 460 460 200/230 380 460 3 1 3 3 3 1 3 3 3 3 3 3 1 3 3 3 3 1 3 3 3 3 3 3 3 3 7.9 22.9 17.1 9.3 7.9 26.4 15 8 7.4 15.7 8 7.4 32.1 20.7 10.7 10 7.1 32.1 20.7 10.7 9.1 11.1 11.1 20.7 12.5 10 46 137 110 54 46 129 115 57 47.5 115 57 47.5 148 137 64 62 53 148 137 64 62 75 75 156 70 70 Winding Resistance Start or Line/Line Run 3.88 1.339 0.432 2.76 3.88 0.779 0.911 2.78 3.64 0.911 2.78 3.64 0.667 0.612 2.3 2.8 4.333 0.667 0.612 2.3 2.8 2.27 2.27 0.562 1.92 2.27 0 0.462 0 0 0 0.432 0 0 0 0 0 0 0.362 0 0 0 0 0.362 0 0 0 0 0 0 0 0 Run Cap PN 014-0064-26 014-0064-26 014-0064-27 014-0064-27 See Section F Introduction for more information. FF53 Section_Ff.indd 53 3/4/2008 8:10:12 AM Electrical Data - Copeland Scroll® Model Volts ZRD72KCE-TF5 200/230 ZRD72KCE-TF7 380 ZRD72KCE-TFD 460 ZRD81KC-TF7 380 ZRD81KC-TFD 460 ZRD81KCE-TF7 380 ZRD81KCE-TFD 460 ZRD94KC-TF5 200/230 ZRD94KC-TF7 380 ZRD94KC-TFD 460 ZRD94KC-TFE 575 ZRD94KCE-TF5 200/230 ZRD94KCE-TF7 380 ZRD94KCE-TFD 460 ZRD94KCE-TFE 575 ZRDT12MC-TF5 200/230 ZRDT12MC-TF7 380 ZRDT12MC-TFD 460 ZRDT12MCE-TF5200/230 ZRDT12MCE-TF7 380 ZRDT12MCE-TFD 460 ZRDT14MC-TF5 200/230 ZRDT14MC-TF7 380 ZRDT14MC-TFD 460 ZRDT14MCE-TF5200/230 ZRDT14MCE-TF7 380 PH 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 Max RLA LRA 20.7 12.5 10 14.3 12.1 14.3 12.1 32.1 16.7 16.4 12 32.1 16.7 16.4 12 156 70 70 78 100 78 100 195 123 95 80 195 123 95 80 Winding Resistance Start or Line/Line Run 0.562 1.92 2.27 1.79 1.79 1.79 1.79 0.4 1.051 1.799 2.55 0.4 1.051 1.799 2.55 Run Cap PN 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 See Section F Introduction for more information. FF54 Section_Ff.indd 54 3/4/2008 8:10:13 AM Electrical Data - Copeland Scroll® Model Volts ZRDT14MCE-TFD 460 ZRDT16MC-TF7 380 ZRDT16MC-TFD 460 ZRDT16MCE-TF7 380 ZRDT16MCE-TFD 460 ZRDT96KC-TF7 380 ZRDT96KC-TFD 460 ZRDT96KCE-TF7 380 ZRDT96KCE-TFD 460 ZRDU11MC-TF5 200/230 ZRDU11MC-TF5 200/230 ZRDU11MC-TF7 380 ZRDU11MC-TF7 380 ZRDU11MC-TFD 460 ZRDU11MC-TFD 460 ZRDU11MCE-TF5200/230 ZRDU11MCE-TF7 380 ZRDU11MCE-TFD 460 ZRDU13MC-TF5 200/230 ZRDU13MC-TF5 200/230 ZRDU13MC-TF7 380 ZRDU13MC-TF7 380 ZRDU13MC-TFD 460 ZRDU13MC-TFD 460 ZRDU13MCE-TF5200/230 ZRDU13MCE-TF5200/230 PH Max RLA LRA Winding Resistance Start or Line/Line Run Run Cap PN 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 See Section F Introduction for more information. FF55 Section_Ff.indd 55 3/4/2008 8:10:13 AM Electrical Data - Copeland Scroll® Model Volts ZRDU13MCE-TF7 380 ZRDU13MCE-TF7 380 ZRDU13MCE-TFD 460 ZRDU13MCE-TFD 460 ZRH49KJE-TF5 200/230 ZRH49KJE-TF7 380 ZRH49KJE-TFD 460 ZRH49KJE-TFE 575 ZRH61KJE-TF5 200/230 ZRH61KJE-TF7 380 ZRH61KJE-TFD 460 ZRH72KJE-TF5 200/230 ZRH72KJE-TF7 380 ZRH72KJE-TFD 460 ZRI108KC-TF7 380 ZRI125KC-TF7 380 ZRI144KC-TF7 380 ZRI61KC-TFD 460 ZRJ61KC-TFD 460 ZRJ72KC-TFD 460 ZRJU13MC-TFD 460 ZRS43K4-PFV 208/230 ZRS43K4-TF5 200/230 ZRS43K4-TFD 460 ZRS52K4-PFV 208/230 ZRS52K4-TF5 200/230 PH 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 1 3 3 1 3 Winding Resistance Start or Line/Line Run Max RLA LRA 15 8.6 8.2 6.4 21.4 11.4 9.6 23.9 12.9 9.3 19.6 23.9 24.3 10.4 10.7 12.5 99 57 49.5 40 123 64 62 156 70 70 140 145 145 62 62 100 0.911 0.911 3.64 5.72 0.686 0.686 2.75 0.501 2.27 2.27 0.93 0.85 0.85 2.75 2.75 1.79 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 23.9 14.3 6.8 24.6 18.9 116 91 46 118 123 1.227 0.994 3.88 0.601 0.686 0.517 0 0 0.49 0 Run Cap PN 014-0064-25 014-0064-27 See Section F Introduction for more information. FF56 Section_Ff.indd 56 3/4/2008 8:10:13 AM Electrical Data - Copeland Scroll® Model Volts ZRS52K4-TFD 460 ZRT108K3-PFV 208/230 ZRT108K3-PFV 208/230 ZRT108K3-TF5 200/230 ZRT108K3-TF5 200/230 ZRT108K3-TFD 460 ZRT108K3-TFD 460 ZRT108K3-TFE 575 ZRT108K3-TFE 575 ZRT108K3E-TFD 460 ZRT108K3E-TFD 460 ZRT108K3E-TFE 575 ZRT108K3E-TFE 575 ZRT108KC-TF7 380 ZRT108KC-TF7 380 ZRT108KS-TFD 460 ZRT108KSE-TFD 460 ZRT114K3-PFV 208/230 ZRT114K3-PFV 208/230 ZRT114K3-TF5 200/230 ZRT114K3-TF5 200/230 ZRT114K3-TFD 460 ZRT114K3-TFD 460 ZRT114K3-TFE 575 ZRT114K3-TFE 575 ZRT114KS-TFD 460 PH 3 1 1 3 3 3 3 3 3 3 3 3 3 3 3 3 3 1 1 3 3 3 3 3 3 3 Max RLA LRA 9.4 62 Winding Resistance Start or Line/Line Run 2.8 Run Cap PN 0 See Section F Introduction for more information. FF57 Section_Ff.indd 57 3/4/2008 8:10:14 AM Electrical Data - Copeland Scroll® Model Volts ZRT114KSE-TFD 460 ZRT122K3-PFV 208/230 ZRT122K3-PFV 208/230 ZRT122K3-TF5 200/230 ZRT122K3-TF5 200/230 ZRT122K3-TFD 460 ZRT122K3-TFD 460 ZRT122K3-TFE 575 ZRT122K3-TFE 575 ZRT122K3E-PFV 208/230 ZRT122K3E-PFV 208/230 ZRT122K3E-TF5 200/230 ZRT122K3E-TF5 200/230 ZRT122K3E-TFD 460 ZRT122K3E-TFD 460 ZRT122KCE-TFD 460 ZRT122KCE-TFD 460 ZRT122KS-TF5 200/230 ZRT122KS-TFD 460 ZRT122KSE-TF5 200/230 ZRT122KSE-TFD 460 ZRT136KC-TF5 200/230 ZRT136KC-TF5 200/230 ZRT136KC-TF7 380 ZRT136KC-TF7 380 ZRT136KC-TFD 460 PH Max RLA LRA Winding Resistance Start or Line/Line Run Run Cap PN 3 1 1 3 3 3 3 3 3 1 1 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 See Section F Introduction for more information. FF58 Section_Ff.indd 58 3/4/2008 8:10:14 AM Electrical Data - Copeland Scroll® Model Volts ZRT136KC-TFD 460 ZRT136KC-TFE 575 ZRT136KC-TFE 575 ZRT136KCE-TF5 200/230 ZRT136KCE-TFD 460 ZRT136KCE-TFD 460 ZRT136KCE-TFE 575 ZRT136KCE-TFE 575 ZRT144KC-TF5 200/230 ZRT144KC-TF5 200/230 ZRT144KC-TF7 380 ZRT144KC-TF7 380 ZRT144KC-TFD 460 ZRT144KC-TFD 460 ZRT144KC-TFE 575 ZRT144KC-TFE 575 ZRT144KCE-TF5 200/230 ZRT144KCE-TF5 200/230 ZRT144KCE-TFD 460 ZRT144KCE-TFD 460 ZRT144KCE-TFE 575 ZRT144KCE-TFE 575 ZRT162KC-TF5 200/230 ZRT162KC-TF5 200/230 ZRT162KC-TF7 380 ZRT162KC-TFD 460 PH Max RLA LRA Winding Resistance Start or Line/Line Run Run Cap PN 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 See Section F Introduction for more information. FF59 Section_Ff.indd 59 3/4/2008 8:10:14 AM Electrical Data - Copeland Scroll® Model Volts ZRT162KC-TFD 460 ZRT162KCE-TF5 200/230 ZRT162KCE-TF5 200/230 ZRT162KCE-TF7 380 ZRT162KCE-TF7 380 ZRT162KCE-TFD 460 ZRT162KCE-TFD 460 ZRT168KC-TF5 200/230 ZRT168KC-TF5 200/230 ZRT168KC-TF7 380 ZRT168KC-TF7 380 ZRT168KC-TFD 460 ZRT168KC-TFD 460 ZRT168KC-TFE 575 ZRT168KC-TFE 575 ZRT168KCE-TF5 200/230 ZRT168KCE-TF5 200/230 ZRT168KCE-TF7 380 ZRT168KCE-TF7 380 ZRT168KCE-TFD 460 ZRT168KCE-TFD 460 ZRT168KCE-TFE 575 ZRT168KCE-TFE 575 ZRT180K3-TW5 200/230 ZRT180K3-TW7 380 ZRT180K3-TWC 208/230 PH Max RLA LRA Winding Resistance Start or Line/Line Run Run Cap PN 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 See Section F Introduction for more information. FF60 Section_Ff.indd 60 3/4/2008 8:10:15 AM Electrical Data - Copeland Scroll® Model Volts ZRT180K3-TWD 460 ZRT180K3-TWE 575 ZRT180K3E-TWC208/230 ZRT180K3E-TWD 460 ZRT180K3E-TWE 575 ZRT188KC-TF5 200/230 ZRT188KC-TF5 200/230 ZRT188KC-TF7 380 ZRT188KC-TF7 380 ZRT188KC-TFD 460 ZRT188KC-TFD 460 ZRT188KC-TFE 575 ZRT188KC-TFE 575 ZRT188KCE-TF5 200/230 ZRT188KCE-TF5 200/230 ZRT188KCE-TF7 380 ZRT188KCE-TF7 380 ZRT188KCE-TFD 460 ZRT188KCE-TFD 460 ZRT188KCE-TFE 575 ZRT188KCE-TFE 575 ZRT216KC-TF5 200/230 ZRT216KC-TF5 200/230 ZRT216KC-TF7 380 ZRT216KC-TF7 380 ZRT216KC-TFD 460 PH Max RLA LRA Winding Resistance Start or Line/Line Run Run Cap PN 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 See Section F Introduction for more information. FF61 Section_Ff.indd 61 3/4/2008 8:10:15 AM Electrical Data - Copeland Scroll® Model Volts ZRT216KC-TFD 460 ZRT216KC-TFE 575 ZRT216KC-TFE 575 ZRT216KCE-TF5 200/230 ZRT216KCE-TF5 200/230 ZRT216KCE-TF7 380 ZRT216KCE-TF7 380 ZRT216KCE-TFD 460 ZRT216KCE-TFD 460 ZRT216KCE-TFE 575 ZRT216KCE-TFE 575 ZRT220K3-TW7 380 ZRT220K3-TWC 208/230 ZRT220K3-TWD 460 ZRT220K3-TWE 575 ZRT220K3E-TW7 380 ZRT220K3E-TWC208/230 ZRT220K3E-TWD 460 ZRT240K3-TW5 200/230 ZRT240K3-TW7 380 ZRT240K3-TWC 208/230 ZRT240K3-TWD 460 ZRT240K3-TWE 575 ZRT240K3E-TWC208/230 ZRT240K3E-TWD 460 ZRT240K3E-TWE 575 PH Max RLA LRA Winding Resistance Start or Line/Line Run Run Cap PN 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 See Section F Introduction for more information. FF62 Section_Ff.indd 62 3/4/2008 8:10:15 AM Electrical Data - Copeland Scroll® Model Volts ZRT250KC-TF5 200/230 ZRT250KC-TF5 200/230 ZRT250KC-TF7 380 ZRT250KC-TF7 380 ZRT250KC-TFD 460 ZRT250KC-TFD 460 ZRT250KC-TFE 575 ZRT250KC-TFE 575 ZRT250KCE-TF5 200/230 ZRT250KCE-TF5 200/230 ZRT250KCE-TF7 380 ZRT250KCE-TF7 380 ZRT250KCE-TFD 460 ZRT250KCE-TFD 460 ZRT250KCE-TFE 575 ZRT250KCE-TFE 575 ZRT288KC-TF5 200/230 ZRT288KC-TF5 200/230 ZRT288KC-TF7 380 ZRT288KC-TF7 380 ZRT288KC-TFD 460 ZRT288KC-TFD 460 ZRT288KC-TFE 575 ZRT288KC-TFE 575 ZRT320K3-TW5 200/230 ZRT320K3-TW7 380 PH Max RLA LRA Winding Resistance Start or Line/Line Run Run Cap PN 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 See Section F Introduction for more information. FF63 Section_Ff.indd 63 3/4/2008 8:10:16 AM Electrical Data - Copeland Scroll® Model Volts ZRT320K3-TWC 208/230 ZRT320K3-TWD 460 ZRT320K3-TWE 575 ZRT320K3E-TWC208/230 ZRT320K3E-TWD 460 ZRT320K3E-TWE 575 ZRT320KC-TFD 460 ZRT320KC-TW5 200/230 ZRT320KC-TW7 380 ZRT320KC-TWD 460 ZRT320KC-TWE 575 ZRT320KCE-TFD 460 ZRT320KCE-TW5200/230 ZRT320KCE-TW7 380 ZRT320KCE-TWD 460 ZRT320KCE-TWE 575 ZRT380K3-TW5 200/230 ZRT380K3-TW7 380 ZRT380K3-TWC 208/230 ZRT380K3-TWD 460 ZRT380K3-TWE 575 ZRT380K3E-TWC208/230 ZRT380K3E-TWD 460 ZRT380K3E-TWE 575 ZRT380KC-TFD 460 ZRT380KC-TW5 200/230 PH Max RLA LRA Winding Resistance Start or Line/Line Run Run Cap PN 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 See Section F Introduction for more information. FF64 Section_Ff.indd 64 3/4/2008 8:10:16 AM Electrical Data - Copeland Scroll® Model Volts ZRT380KC-TW7 380 ZRT380KC-TWD 460 ZRT380KC-TWE 575 ZRT380KCE-TFD 460 ZRT380KCE-TW5200/230 ZRT380KCE-TW7 380 ZRT380KCE-TWD 460 ZRT380KCE-TWE 575 ZRT500KC-TW5 200/230 ZRT500KC-TW5 200/230 ZRT500KC-TW7 380 ZRT500KC-TW7 380 ZRT500KC-TWC 208/230 ZRT500KC-TWC 208/230 ZRT500KC-TWD 460 ZRT500KC-TWD 460 ZRT500KC-TWE 575 ZRT500KC-TWE 575 ZRT500KCE-TW5200/230 ZRT500KCE-TW5200/230 ZRT500KCE-TW7 380 ZRT500KCE-TW7 380 ZRT500KCE-TWC208/230 ZRT500KCE-TWC208/230 ZRT500KCE-TWD 460 ZRT500KCE-TWD 460 PH Max RLA LRA Winding Resistance Start or Line/Line Run Run Cap PN 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 See Section F Introduction for more information. FF65 Section_Ff.indd 65 3/4/2008 8:10:16 AM Electrical Data - Copeland Scroll® Model Volts ZRT500KCE-TWE 575 ZRT500KCE-TWE 575 ZRT600KC-TW5 208/230 ZRT600KC-TW5 208/230 ZRT600KC-TW7 380 ZRT600KC-TW7 380 ZRT600KC-TWC 208/230 ZRT600KC-TWC 208/230 ZRT600KC-TWD 460 ZRT600KC-TWD 460 ZRT600KC-TWE 575 ZRT600KC-TWE 575 ZRT600KCE-TW5208/230 ZRT600KCE-TW5208/230 ZRT600KCE-TW7 380 ZRT600KCE-TW7 380 ZRT600KCE-TWC208/230 ZRT600KCE-TWC208/230 ZRT600KCE-TWD 460 ZRT600KCE-TWD 460 ZRT600KCE-TWE 575 ZRT600KCE-TWE 575 ZRT760KC-TW5 200/230 ZRT760KC-TW5 200/230 ZRT760KC-TW7 380 ZRT760KC-TW7 380 PH Max RLA LRA Winding Resistance Start or Line/Line Run Run Cap PN 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 See Section F Introduction for more information. FF66 Section_Ff.indd 66 3/4/2008 8:10:17 AM Electrical Data - Copeland Scroll® Model Volts ZRT760KC-TWC 208/230 ZRT760KC-TWC 208/230 ZRT760KC-TWD 460 ZRT760KC-TWD 460 ZRT760KC-TWE 575 ZRT760KC-TWE 575 ZRT760KCE-TW5200/230 ZRT760KCE-TW5200/230 ZRT760KCE-TW7 380 ZRT760KCE-TW7 380 ZRT760KCE-TWC208/230 ZRT760KCE-TWC208/230 ZRT760KCE-TWD 460 ZRT760KCE-TWD 460 ZRT760KCE-TWE 575 ZRT760KCE-TWE 575 ZRT90K3-PFV 208/230 ZRT90K3-PFV 208/230 ZRT90K3-TF5 200/230 ZRT90K3-TF5 200/230 ZRT90K3-TFD 460 ZRT90K3-TFD 460 ZRT90K3E-PFV 208/230 ZRT90KC-PFV 208/230 ZRT90KC-PFV 208/230 ZRT90KC-TF5 200/230 PH Max RLA LRA Winding Resistance Start or Line/Line Run Run Cap PN 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 1 1 3 3 3 3 1 1 1 3 See Section F Introduction for more information. FF67 Section_Ff.indd 67 3/4/2008 8:10:17 AM Electrical Data - Copeland Scroll® Model ZRT90KC-TF5 ZRT90KC-TFD ZRT90KC-TFD ZRT90KC-TFE ZRT90KC-TFE ZRT92K3-PFV ZRT92K3-PFV ZRT92K3-TF5 ZRT92K3-TF5 ZRT92K3-TFD ZRT92K3-TFD ZRT92K3-TFE ZRT92K3-TFE ZRT96K3-PFV ZRT96K3-PFV ZRT96K3-TF5 ZRT96K3-TF5 ZRT96K3-TFD ZRT96K3-TFD ZRT96K3-TFE ZRT96K3E-PFV ZRT96K3E-PFV ZRT96K3E-TF5 ZRT96K3E-TF5 ZRT96K3E-TFD Volts PH 200/230 460 460 575 575 208/230 208/230 200/230 200/230 460 460 575 575 208/230 208/230 200/230 200/230 460 460 575 208/230 208/230 200/230 200/230 460 3 3 3 3 3 1 1 3 3 3 3 3 3 1 1 3 3 3 3 3 1 1 3 3 3 Max RLA LRA Winding Resistance Start or Line/Line Run Run Cap PN See Section F Introduction for more information. FF68 Section_Ff.indd 68 3/4/2008 8:10:17 AM Electrical Data - Copeland Scroll® Model ZRT96K3E-TFD ZRT96K3E-TFE ZRT96KC-PFV ZRT96KC-PFV ZRT96KC-TF5 ZRT96KC-TF5 ZRT96KC-TFD ZRT96KC-TFD ZRT96KCE-TF5 ZRT96KCE-TF5 ZRT96KCE-TFD ZRT96KCE-TFD ZRT98K3-PFV ZRT98K3-PFV ZRT98K3-TF5 ZRT98K3-TF5 ZRT98K3-TFD ZRT98K3-TFD ZRT98K3-TFE ZRT98K3-TFE ZRU103K3-TF5 ZRU103K3-TF5 ZRU103K3-TFD ZRU103K3-TFD ZRU103K3-TFE ZRU103K3-TFE Volts PH 460 575 208/230 208/230 200/230 200/230 460 460 200/230 200/230 460 460 208/230 208/230 200/230 200/230 460 460 575 575 200/230 200/230 460 460 575 575 3 3 1 1 3 3 3 3 3 3 3 3 1 1 3 3 3 3 3 3 3 3 3 3 3 3 Max RLA LRA Winding Resistance Start or Line/Line Run Run Cap PN See Section F Introduction for more information. FF69 Section_Ff.indd 69 3/4/2008 8:10:18 AM Electrical Data - Copeland Scroll® Model Volts ZRU140KC-TF5 200/230 ZRU140KC-TF5 200/230 ZRU140KC-TF7 380 ZRU140KC-TF7 380 ZRU140KC-TFD 460 ZRU140KC-TFD 460 ZRU140KC-TFE 575 ZRU140KC-TFE 575 ZRU178KC-TF5 200/230 ZRU178KC-TF5 200/230 ZRU178KC-TF7 380 ZRU178KC-TF7 380 ZRU178KC-TFD 460 ZRU178KC-TFD 460 ZRU178KC-TFE 575 ZRU178KC-TFE 575 ZRU280K3-TW5 200/230 ZRU280K3-TW7 380 ZRU280K3-TWC 208/230 ZRU280K3-TWD 460 ZRU280K3-TWE 575 ZRU280K3E-TWC208/230 ZRU280K3E-TWD 460 ZRU280K3E-TWE 575 ZRU285KC-TFD 460 ZRU285KC-TX5 200/230 PH Max RLA LRA Winding Resistance Start or Line/Line Run Run Cap PN 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 See Section F Introduction for more information. FF70 Section_Ff.indd 70 3/4/2008 8:10:18 AM Electrical Data - Copeland Scroll® Model Volts ZRU285KC-TX7 380 ZRU285KC-TXD 460 ZRU285KC-TXE 575 ZRU285KCE-TFD 460 ZRU285KCE-TX5 200/230 ZRU285KCE-TX7 380 ZRU285KCE-TXD 460 ZRU285KCE-TXE 575 ZRU310K3-TW5 200/230 ZRU310K3-TW7 380 ZRU310K3-TWC 208/230 ZRU310K3-TWD 460 ZRU310K3-TWE 575 ZRU310K3E-TWC208/230 ZRU310K3E-TWD 460 ZRU310K3E-TWE 575 ZRU315KC-TFD 460 ZRU315KC-TX5 200/230 ZRU315KC-TX7 380 ZRU315KC-TXD 460 ZRU315KC-TXE 575 ZRU315KCE-TFD 460 ZRU315KCE-TX5 200/230 ZRU315KCE-TX7 380 ZRU315KCE-TXD 460 ZRU315KCE-TXE 575 PH Max RLA LRA Winding Resistance Start or Line/Line Run Run Cap PN 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 See Section F Introduction for more information. FF71 Section_Ff.indd 71 3/4/2008 8:10:18 AM Electrical Data - Copeland Scroll® Model Volts ZRU334KC-TFD 460 ZRU334KC-TX5 200/230 ZRU334KC-TX7 380 ZRU334KC-TXD 460 ZRU334KC-TXE 575 ZRU334KCE-TFD 460 ZRU334KCE-TX5 200/230 ZRU334KCE-TX7 380 ZRU334KCE-TXD 460 ZRU334KCE-TXE 575 ZRU350K3-TW5 200/230 ZRU350K3-TW7 380 ZRU350K3-TWC 208/230 ZRU350K3-TWD 460 ZRU350K3-TWE 575 ZRU350K3E-TWC208/230 ZRU350K3E-TWD 460 ZRU350K3E-TWE 575 ZRU350KC-TFD 460 ZRU350KC-TW5 200/230 ZRU350KC-TW7 380 ZRU350KC-TWD 460 ZRU350KC-TWE 575 ZRU350KCE-TFD 460 ZRU350KCE-TW5200/230 ZRU350KCE-TW7 380 PH Max RLA LRA Winding Resistance Start or Line/Line Run Run Cap PN 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 See Section F Introduction for more information. FF72 Section_Ff.indd 72 3/4/2008 8:10:19 AM Electrical Data - Copeland Scroll® Model Volts ZRU350KCE-TWD 460 ZRU350KCE-TWE 575 ZRU440KC-TW7 380 ZRU440KC-TW7 380 ZRU440KC-TWC 208/230 ZRU440KC-TWC 208/230 ZRU440KC-TWD 460 ZRU440KC-TWD 460 ZRU440KC-TWE 575 ZRU440KC-TWE 575 ZRU440KCE-TWD 460 ZRU440KCE-TWE 575 ZRU550KC-TW5 200/230 ZRU550KC-TW5 208/230 ZRU550KC-TW7 380 ZRU550KC-TWC 208/230 ZRU550KC-TWD 460 ZRU550KC-TWE 575 ZRU550KCE-TW5200/230 ZRU550KCE-TW5208/230 ZRU550KCE-TW7 380 ZRU550KCE-TWC208/230 ZRU550KCE-TWD 460 ZRU550KCE-TWE 575 ZRY114MC-TWD 460 ZRY114MCE-TWD 460 PH Max RLA LRA Winding Resistance Start or Line/Line Run Run Cap PN 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 See Section F Introduction for more information. FF73 Section_Ff.indd 73 3/4/2008 8:10:19 AM Electrical Data - Copeland Scroll® Model Volts ZRY324KC-TF5 200/230 ZRY324KC-TF7 380 ZRY324KC-TFD 460 ZRY324KC-TFE 575 ZRY324KCE-TF5 200/230 ZRY324KCE-TF7 380 ZRY324KCE-TFD 460 ZRY324KCE-TFE 575 ZRY375KC-TF5 200/230 ZRY375KC-TF7 380 ZRY375KC-TFD 460 ZRY375KC-TFE 575 ZRY375KCE-TF5 200/230 ZRY375KCE-TF7 380 ZRY375KCE-TFD 460 ZRY375KCE-TFE 575 ZRY432KC-TF5 200/230 ZRY432KC-TF7 380 ZRY432KC-TFD 460 ZRY432KC-TFE 575 ZRY432KCE-TF5 200/230 ZRY432KCE-TF7 380 ZRY432KCE-TFD 460 ZRY432KCE-TFE 575 ZRY480K3-TW5 200/230 ZRY480K3-TW7 380 PH Max RLA LRA Winding Resistance Start or Line/Line Run Run Cap PN 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 See Section F Introduction for more information. FF74 Section_Ff.indd 74 3/4/2008 8:10:19 AM Electrical Data - Copeland Scroll® Model Volts ZRY480K3-TWC 208/230 ZRY480K3-TWD 460 ZRY480K3-TWE 575 ZRY480K3E-TW5 200/230 ZRY480K3E-TW7 380 ZRY480K3E-TWC208/230 ZRY480K3E-TWD 460 ZRY480K3E-TWE 575 ZRY480KC-TFD 460 ZRY480KC-TW5 200/230 ZRY480KC-TW7 380 ZRY480KC-TWD 460 ZRY480KC-TWE 575 ZRY480KCE-TFD 460 ZRY480KCE-TW5200/230 ZRY480KCE-TW7 380 ZRY480KCE-TWD 460 ZRY480KCE-TWE 575 ZRY570K3-TW5 200/230 ZRY570K3-TW7 380 ZRY570K3-TWC 208/230 ZRY570K3-TWD 460 ZRY570K3-TWE 575 ZRY570K3E-TW5 200/230 ZRY570K3E-TW7 380 ZRY570K3E-TWC208/230 PH Max RLA LRA Winding Resistance Start or Line/Line Run Run Cap PN 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 See Section F Introduction for more information. FF75 Section_Ff.indd 75 3/4/2008 8:10:20 AM Electrical Data - Copeland Scroll® Model Volts ZRY570K3E-TWD 460 ZRY570KC-TFD 460 ZRY570KC-TW5 200/230 ZRY570KC-TW7 380 ZRY570KC-TWD 460 ZRY570KC-TWE 575 ZRY570KCE-TFD 460 ZRY570KCE-TW5200/230 ZRY570KCE-TW7 380 ZRY570KCE-TWD 460 ZRY570KCE-TWE 575 ZRY750KC-TW5 200/230 ZRY750KC-TW7 380 ZRY750KC-TWC 208/230 ZRY750KC-TWD 460 ZRY750KC-TWE 575 ZRY750KCE-TW5200/230 ZRY750KCE-TW7 380 ZRY750KCE-TWC208/230 ZRY750KCE-TWD 460 ZRY750KCE-TWE 575 ZRY900KC-TW5 208/230 ZRY900KC-TW7 380 ZRY900KC-TWC 208/230 ZRY900KC-TWD 460 ZRY900KC-TWE 575 PH Max RLA LRA Winding Resistance Start or Line/Line Run Run Cap PN 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 See Section F Introduction for more information. FF76 Section_Ff.indd 76 3/4/2008 8:10:20 AM Electrical Data - Copeland Scroll® Model Volts ZRY900KCE-TW5208/230 ZRY900KCE-TW7 380 ZRY900KCE-TWC208/230 ZRY900KCE-TWD 460 ZRY900KCE-TWE 575 ZRY930KC-TW7 380 ZRY930KC-TWC 208/230 ZRY930KC-TWD 460 ZRY930KCE-TW7 380 ZRY930KCE-TWC208/230 ZRY930KCE-TWD 460 ZS11M4-TW7 380 ZS11M4-TWC 208/230 ZS11M4-TWD 460 ZS11M4-TWE 575 ZS11M4E-TW7 380 ZS11M4E-TWC 208/230 ZS11M4E-TWD 460 ZS11M4E-TWE 575 ZS15K4-PFV 208/230 ZS15K4-TF5 200/230 ZS15K4-TFD 460 ZS15K4E-PFV 208/230 ZS15K4E-TF5 200/230 ZS15K4E-TFD 460 ZS19K4-PFV 208/230 PH Max RLA LRA 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 1 3 3 1 3 3 1 25 48.2 22.1 17.9 32.5 60 28.2 22.5 13.6 7.9 3.6 13.6 9.3 4.3 16.4 239 425 187 148 239 425 187 148 61 55 27 61 55 27 73 Winding Resistance Start or Line/Line Run 0.52 0.19 0.72 1.1 0.52 0.19 0.72 1.1 2.28 1.79 7.1 2.28 1.79 7.1 1.72 0 0 0 0 0 0 0 0 1.01 0 0 1.01 0 0 0.833 Run Cap PN 014-0064-08 014-0064-08 014-0064-25 See Section F Introduction for more information. FF77 Section_Ff.indd 77 3/4/2008 8:10:20 AM Electrical Data - Copeland Scroll® Model Volts PH Max RLA LRA ZS19K4-TF5 ZS19K4-TFD ZS19K4E-PFV ZS19K4E-TF5 ZS19K4E-TFD ZS21K4-PFV ZS21K4-TF5 ZS21K4-TFD ZS21K4E-PFV ZS21K4E-TF5 ZS21K4E-TFD ZS21K4E-TFE ZS26K4-PFV ZS26K4-TF5 ZS26K4-TFD ZS26K4E-PFV ZS26K4E-TF5 ZS26K4E-TFD ZS26K4E-TFE ZS30K4-PFV ZS30K4-TF5 ZS30K4-TFD ZS30K4E-PFV ZS30K4E-TF5 ZS30K4E-TF7 ZS30K4E-TFD 200/230 460 208/230 200/230 460 208/230 200/230 460 208/230 200/230 460 575 208/230 200/230 460 208/230 200/230 460 575 208/230 200/230 460 208/230 200/230 380 460 3 3 1 3 3 1 3 3 1 3 3 3 1 3 3 1 3 3 3 1 3 3 1 3 3 3 7.9 3.9 16.4 9.6 5 17.9 10 5 16.4 11.1 5.7 4.3 20.7 12.5 6.4 20.7 13.6 7.1 5 26.4 15 6.8 26.8 15 8.2 8.2 63 31 73 63 31 88 77 39 88 77 39 31 109 88 44 109 88 44 34 129 99 49.5 129 99 57 49.5 Winding Resistance Start or Line/Line Run 1.46 5.94 1.72 1.46 5.94 1.46 1.234 4.83 1.46 1.234 4.83 7.89 1.28 0.995 1.85 1.28 0.995 1.85 6.28 0.779 0.911 3.64 0.779 0.911 2.78 3.64 0 0 0.833 0 0 0.691 0 0 0.691 0 0 0 0.54 0 0 0.54 0 0 0 0.432 0 0 0.432 0 0 0 Run Cap PN 014-0064-25 014-0064-29 014-0064-29 014-0064-26 014-0064-26 014-0064-26 014-0064-26 See Section F Introduction for more information. FF78 Section_Ff.indd 78 3/4/2008 8:10:21 AM Electrical Data - Copeland Scroll® Model ZS30K4E-TFE ZS38K4-PFJ ZS38K4-TF5 ZS38K4-TFD ZS38K4E-PFJ ZS38K4E-PFV ZS38K4E-TF5 ZS38K4E-TF7 ZS38K4E-TFD ZS38K4E-TFE ZS45K4-TF5 ZS45K4-TFD ZS45K4E-TF5 ZS45K4E-TF7 ZS45K4E-TFD ZS45K4E-TFE ZS56K4-TW7 ZS56K4-TWC ZS56K4-TWD ZS56K4-TWE ZS56K4E-TW7 ZS56K4E-TWC ZS56K4E-TWD ZS56K4E-TWE ZS75K4-TW7 ZS75K4-TWC Volts PH Max RLA LRA 575 265 200/230 460 265 208/230 200/230 380 460 575 200/230 460 200/230 380 460 575 380 208/230 460 575 380 208/230 460 575 380 208/230 3 1 3 3 1 1 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 8.2 22.9 16.4 8.6 26.4 31.8 21.4 11.4 9.6 7.9 20 8.9 23.9 12.6 9.3 7.9 14.3 22.9 11.4 8.9 18.6 30 15.7 8.9 16.6 30.1 40 160 123 62 160 169 123 64 62 50 156 70 156 70 70 54 112 189 99 74 112 189 99 74 151 278 Winding Resistance Start or Line/Line Run 5.72 1.224 0.686 2.75 1.224 0.605 0.686 2.28 2.75 4.31 0.501 2.27 0.501 1.92 2.27 3.56 1.03 0.37 1.41 2.3 1.03 0.37 1.41 2.3 0.72 0.26 0 0.417 0 0 0.417 0.329 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Run Cap PN 014-0064-26 014-0064-26 014-0064-27 See Section F Introduction for more information. FF79 Section_Ff.indd 79 3/4/2008 8:10:21 AM Electrical Data - Copeland Scroll® Model ZS75K4-TWD ZS75K4-TWE ZS75K4E-TW7 ZS75K4E-TWC ZS75K4E-TWD ZS75K4E-TWE ZS92K4-TW7 ZS92K4-TWC ZS92K4-TWD ZS92K4-TWE ZS92K4E-TW7 ZS92K4E-TWC ZS92K4E-TWD ZS92K4E-TWE ZX15KC-TFD ZX15KCE-TFD ZX21KC-TFD ZX21KCE-TFD ZX30KC-TFD ZX30KCE-TFD ZX38KC-TFD ZX38KCE-TFD ZX45KC-TFD ZX45KCE-TFD ZX51KC-TFD ZX51KCE-TFD Volts PH Max RLA LRA 460 575 380 208/230 460 575 380 208/230 460 575 380 208/230 460 575 460 460 460 460 460 460 460 460 460 460 460 460 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 16.4 11.6 23.9 43.6 21.1 16.1 22.9 40.7 20 15.4 28.2 52.9 25 20 4.3 5 5.7 6.1 7.4 7.5 8.9 9.6 11.5 10.1 12.1 11.8 127 100 151 278 127 100 195 350 158 125 195 350 158 125 27 27 39 39 47.5 47.5 63 63 70 70 100 100 Winding Resistance Start or Line/Line Run 1.02 1.7 0.72 0.26 1.02 1.7 0.57 0.22 0.83 1.28 0.57 0.22 0.83 1.28 7.1 7.1 4.83 4.83 3.65 3.65 2.72 2.72 2.27 2.27 1.79 1.79 Run Cap PN 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 See Section F Introduction for more information. FF80 Section_Ff.indd 80 3/4/2008 8:10:22 AM Electrical Data - Copeland Scroll® Model ZXI09KC-TFD ZXI09KCE-TFD ZXI18KC-TFD ZXI18KCE-TFD Volts PH Max RLA LRA 460 460 460 460 3 3 3 3 5.7 6 11.1 11.1 41 41 70 70 Winding Resistance Start or Line/Line Run 2.26 2.26 Run Cap PN 0 0 See Section F Introduction for more information. FF81 Section_Ff.indd 81 3/4/2008 8:10:22 AM Electrical Data - Copeland Screw™ Model Voltage PH Max RLA LRA SCA2-11HE-FWC SCA2-11HE-FWD SCA2-11HE-TWE SCA2-12HE-FWC SCA2-12HE-FWD SCA2-12HE-TWE SCA2-14HE-FWC SCA2-14HE-FWD SCA2-14HE-TWE SCA2-16HE-EWD SCA2-16HE-EWE SCA2-18HE-EWD SCA2-18HE-EWE SCA2-21HE-EWD SCA2-21HE-EWE SCA2-24HE-EWD SCA2-24HE-EWE SCA2-350E-FWC SCA2-350E-FWD SCA2-350E-TWE SCA2-400E-FWC SCA2-400E-FWD SCA2-400E-TWE SCA2-500E-FWC SCA2-500E-FWD SCA2-500E-TWE SCA2-600E-FWC 208/230 460 575 208/230 460 575 208/230 460 575 460 575 460 575 460 575 460 575 208/230 460 575 208/230 460 575 208/230 460 575 208/230 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 265 132.9 105.7 325 162.1 130 312.9 175.7 140 NA NA NA NA NA NA NA NA 90 44.9 35.9 120 60 48 165 82.1 66 179.3 1807 814 648 2072 958 766 2336 1036 835 1364 1091 1442 1153 1853 1482 2029 1623 535 254 203 737 329 263 743 359 296 939 Half Wdg.RLA 224 Half Wdg.LRA 1250 563 449 1434 663 530 1612 716 577 786 628 831 664 1068 854 1169 935 286 136 108 394 176 141 466 226 186 559 FG1 Section_Fg.indd 1 3/4/2008 8:13:19 AM Electrical Data - Copeland Screw™ Model Voltage PH Max RLA LRA SCA2-600E-FWD SCA2-600E-TWE SCA2-700E-FWC SCA2-700E-FWD SCA2-700E-TWE SCA2-800E-FWC SCA2-800E-FWD SCA2-800E-TWE SCA2-801E-FWC SCA2-801E-FWD SCA2-801E-TWE SCA2-900E-FWC SCA2-900E-FWD SCA2-900E-TWE SCA2-901E-FWC SCA2-901E-FWD SCA2-901E-TWE SCH1-5000-FWC SCH1-5000-FWD SCH1-5000-TWE SCH1-6000-FWC SCH1-6000-FWD SCH1-6000-TWE SCH1-7000-FWC SCH1-7000-FWD SCH1-7000-TWE SCH1-8000-FWC 460 575 208/230 460 575 208/230 460 575 208/230 460 575 208/230 460 575 208/230 460 575 208/230 460 575 208/230 460 575 208/230 460 575 208/230 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 89.3 71.4 192.1 96.4 77.1 218.6 109.3 87.9 202.9 94.3 80 231.4 115.7 92.1 241.4 112.9 96.4 153.6 74 59.3 198.6 95 75.7 200 95.7 76.4 209.3 449 357 1021 485 412 1416 632 505 1386 556 483 1522 690 555 1506 703 603 743 355 281 939 449 322 1015 485 404 1224 Half Wdg.RLA Half Wdg.LRA 267 212 669 303 259 966 433 346 845 339 295 1053 477 384 918 426 367 431 206 180 559 267 208 607 290 260 732 FG2 Section_Fg.indd 2 3/4/2008 8:13:25 AM Electrical Data - Copeland Screw™ Model Voltage PH Max RLA LRA SCH1-8000-FWD SCH1-8000-TWE SCH1-9000-FWC SCH1-9000-FWD SCH1-9000-TWE SCH2-11H0-FWC SCH2-11H0-FWD SCH2-11H0-TWE SCH2-11HE-FWC SCH2-11HE-FWD SCH2-11HE-TWE SCH2-12H0-FWC SCH2-12H0-FWD SCH2-12H0-TWE SCH2-12HE-FWC SCH2-12HE-FWD SCH2-12HE-TWE SCH2-14H0-FWC SCH2-14H0-FWD SCH2-14H0-TWE SCH2-14HE-FWC SCH2-14HE-FWD SCH2-14HE-TWE SCH2-18H0-EWD SCH2-18H0-EWE SCH2-18HE-EWD SCH2-18HE-EWE 460 575 208/230 460 575 208/230 460 575 208/230 460 575 208/230 460 575 208/230 460 575 208/230 460 575 208/230 460 575 460 575 460 575 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 100 80 243.6 116.4 92.9 284.3 142.1 113.6 272.9 136.4 109.3 317.1 158.6 127.1 302.1 151.4 120.7 359.3 179.3 143.6 330.7 165.7 132.1 NA NA NA NA 585 433 1435 686 546 1988 895 713 1988 895 713 2279 1054 843 2279 1054 843 2569 1139 918 2569 1139 918 1546 1236 1546 1236 Half Wdg.RLA Half Wdg.LRA 350 279 885 423 358 1375 619 494 1375 619 494 1577 729 583 1577 729 583 1773 788 635 1773 788 635 515 412 515 412 FG3 Section_Fg.indd 3 3/4/2008 8:13:25 AM Electrical Data - Copeland Screw™ Model Voltage PH Max RLA LRA SCH2-21H0-EWD SCH2-21H0-EWE SCH2-21HE-EWD SCH2-21HE-EWE SCH2-24H0-EWD SCH2-24H0-EWE SCH2-24HE-EWD SCH2-24HE-EWE SCH2-28H0-EWD SCH2-28H0-EWE SCH2-28HE-EWD SCH2-28HE-EWE SCH2-30H0-EWD SCH2-30H0-EWE SCH2-30HE-EWD SCH2-30HE-EWE SCH2-5000-FWC SCH2-5000-FWD SCH2-5000-TWE SCH2-500E-FWC SCH2-500E-FWD SCH2-500E-TWE SCH2-6000-FWC SCH2-6000-FWD SCH2-6000-TWE SCH2-600E-FWC SCH2-600E-FWD 460 575 460 575 460 575 460 575 460 575 460 575 460 575 460 575 208/230 460 575 208/230 460 575 208/230 460 575 208/230 460 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA 115.7 57.9 46.4 137.1 68.6 55 164.3 82.1 65.7 164.3 82.1 1742 1393 1742 1393 2000 1600 2000 1600 2520 2016 2520 2016 2520 2016 2520 2016 939 411 329 939 411 329 1162 508 406 1162 508 Half Wdg.RLA Half Wdg.LRA 584 467 584 467 667 534 667 534 805 644 805 644 805 644 805 644 498 218 174 498 218 174 616 269 215 616 269 FG4 Section_Fg.indd 4 3/4/2008 8:13:25 AM Electrical Data - Copeland Screw™ Model Voltage PH Max RLA LRA SCH2-600E-TWE SCH2-7000-FWC SCH2-7000-FWD SCH2-7000-TWE SCH2-700E-FWC SCH2-700E-FWD SCH2-700E-TWE SCH2-8000-FWC SCH2-8000-FWD SCH2-8000-TWE SCH2-800E-FWC SCH2-800E-FWD SCH2-800E-TWE SCH2-9000-FWC SCH2-9000-FWD SCH2-9000-TWE SCH2-900E-FWC SCH2-900E-FWD SCH2-900E-TWE SHL1-12H0-FWC SHL1-12H0-FWD SHL1-12H0-TWE SHL1-2000-TWE SHL1-2000-TWK SHL1-2000-TWK SHL1-2500-TWE SHL1-2500-TWK 575 208/230 460 575 208/230 460 575 208/230 460 575 208/230 460 575 208/230 460 575 208/230 460 575 208/230 460 575 575 208/230 460 575 208/230 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 65.7 200 95.7 76.4 188.6 90.7 72.9 209.3 100 80 225.7 108.6 87.1 243.6 116.4 92.9 250.7 120.7 97.1 NA NA NA 32.9 81.4 40.7 34.3 85.7 406 1015 485 404 1015 485 404 1224 585 433 1224 585 433 1435 686 546 1435 686 546 943 943 943 183 492 246 166 436 Half Wdg.RLA Half Wdg.LRA 40.5 215 607 290 260 607 290 260 732 350 279 732 350 279 885 423 358 885 423 358 612 612 612 127 164 42.5 94 150 125.5 60 125.5 60 48 131.5 63 131.5 63 50.5 152.5 73 152.5 73 58 FG5 Section_Fg.indd 5 3/4/2008 8:13:26 AM Electrical Data - Copeland Screw™ Model Voltage PH Max RLA LRA SHL1-2500-TWK SHL1-3000-TWE SHL1-3000-TWK SHL1-3000-TWK SHL1-4000-FWC SHL1-4000-FWD SHL1-4000-TWE SHL1-5000-FWC SHL1-5000-FWD SHL1-5000-TWE SHL1-6000-FWC SHL1-6000-FWD SHL1-6000-TWE SHL1-7000-FWC SHL1-7000-FWD SHL1-7000-TWE SHL1-7500-FWC SHL1-7500-FWD SHL1-7500-TWE SHL2-2000-TWE SHL2-2000-TWK SHL2-2000-TWK SHL2-2500-FWD SHL2-2500-TWE SHL2-2500-TWK SHL2-2500-TWK SHL2-3000-TWE 460 575 208/230 460 208/230 460 575 208/230 460 575 208/230 460 575 208/230 460 575 208/230 460 575 575 208/230 460 460 575 208/230 460 575 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 42.9 41.4 84.3 52.1 162.9 77.9 62.1 171.4 82.1 70.7 176.4 91.4 84.3 213.6 82.9 80.7 224.3 95 85.7 32.9 81.4 40.7 42.9 34.3 85.7 42.9 41.4 218 204 532 266 655 313 222 743 355 281 939 449 322 1015 485 404 1224 585 433 183 492 246 218 166 436 218 204 Half Wdg.RLA Half Wdg.LRA 52 131 184 40.5 391 187 147 431 206 180 559 267 208 607 290 260 732 350 279 127 164 42.5 94 150 131 FG6 Section_Fg.indd 6 3/4/2008 8:13:26 AM Electrical Data - Copeland Screw™ Model Voltage PH Max RLA LRA SHL2-3000-TWK SHL2-3000-TWK SHM1-11H0-FWC SHM1-11H0-FWD SHM1-11H0-TWE SHM1-12H0-FWC SHM1-12H0-FWD SHM1-12H0-TWE SHM1-14H0-FWC SHM1-14H0-FWD SHM1-14H0-TWE SHM1-3000-TWE SHM1-3000-TWK SHM1-3000-TWK SHM1-3500-TWE SHM1-3500-TWK SHM1-3500-TWK SHM1-4000-TWE SHM1-4000-TWK SHM1-4000-TWK SHM1-5000-FWC SHM1-5000-FWD SHM1-5000-TWE SHM1-6000-FWC SHM1-6000-FWD SHM1-6000-TWE SHM1-7000-FWC 208/230 460 208/230 460 575 208/230 460 575 208/230 460 575 575 208/230 460 575 208/230 460 575 208/230 460 208/230 460 575 208/230 460 575 208/230 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 84.3 52.1 NA NA NA NA NA NA NA NA NA 37.1 92.9 46.4 48.6 98.6 60.7 52.1 130 65 184.3 88.6 70.7 238.6 95 91.4 210.7 532 266 801 801 801 943 943 943 1023 1023 1023 166 436 218 204 532 266 255 622 311 743 355 281 939 449 322 1015 Half Wdg.RLA Half Wdg.LRA 52 184 46 520 520 520 612 612 612 665 665 665 94 150 60 131 184 65 166 218 431 206 180 559 267 208 607 FG7 Section_Fg.indd 7 3/4/2008 8:13:26 AM Electrical Data - Copeland Screw™ Model Voltage PH Max RLA LRA SHM1-7000-FWD SHM1-7000-TWE SHM1-8000-FWC SHM1-8000-FWD SHM1-8000-TWE SHM1-9000-FWC SHM1-9000-FWD SHM1-9000-TWE SHM2-3000-TWE SHM2-3000-TWK SHM2-3000-TWK SHM2-3500-TWE SHM2-3500-TWK SHM2-3500-TWK SHM2-4000-TWE SHM2-4000-TWK SHM2-4000-TWK SHMS-4000-FWD 460 575 208/230 460 575 208/230 460 575 575 208/230 460 575 208/230 460 575 208/230 460 460 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 95.7 80.7 245 117.1 93.6 255.7 122.1 97.9 37.1 92.9 46.4 48.6 98.6 60.7 52.1 130 65 88.6 485 404 1224 585 433 1435 686 546 166 436 218 204 532 266 255 622 311 313 Half Wdg.RLA Half Wdg.LRA 46 290 260 732 350 279 885 423 358 94 150 60 131 184 65 166 218 187 FG8 Section_Fg.indd 8 3/4/2008 8:13:26 AM SECTION G WIRING DIAGRAMS The wiring diagram guide lists compressors by model designation. These are indexed against an Electrical Characteristics code. (The third group of numbers in the model number.) The third letter of third group of the model number may be missing. It may be any one of a number of letters representing electrical characteristics. These diagrams represent typical wiring connections for the compressors listed but may not be identical to the diagram in the compressor terminal box. Discontinued wiring diagrams listed in the back of this section are for compressors that are no longer available by Emerson Climate Technologies, Inc. The replacement wiring diagram is not necessary the same as the old wiring diagram show in the front of this section. Use caution when selecting the appropriate wiring diagram. This section contains current information on Copeland® brand products. Information on obsolete models can be obtained from your local Emerson Climate Technologies wholesaler. G1 WELDED COMPRESSORS DIAGRAMS MODEL TF* ES8 TS* (5) 0770 (1,5) 005-1211-01 CT 1319 MODEL IA* 0831/0832 0776/0777 0780 0769 A-LINE 0929 1223 (1) (2) (3) (4) (5) (6) 1318 0865 (1) 005-0670 0768 0833 0778/0779 R CSV (1,5) 005-1211 (5) 0782 (1,3) 005-1210 (1,3) 005-1212 CR , CS R (2) PF* SAA 0930 CA* (2) PA* 0767 0818/0819 0820 0774/0775 0834 0781 0932 0932 CF* TF* 0931 0980 DIAGRAM MOLDED IN COMPRESSOR TERMINAL BOX. MAY REQUIRE PTC THERMISTOR 59 FRAME 70 FRAME 63 FRAME 4 PIN SENSOR CONNECTION NOTE: ASTERISK AFTER FIRST TWO LETTERS INDICATES MAY BE ANY LETTER DEPENDING ON ELECTRICAL CHARACTERISTICS. G2 SCROLL DIAGRAMS MODEL TF* (2) PF* ZB30-45K, ZF13-18K, ZS30-45K, ZMD18K, ZBD30-45K, ZBH30-45K (REFR) ZR46-81K, ZRD49-72K, ZP54-57K (AC) (3) 0880 (1,3) 005-1213 ZF6-11K, ZS15-26K, ZB15-26K, ZBH21K (REFR) ZR28-48K, ZP32-44K (AC) (1,4,5) 005-1270 (1,4,5) 005-1270 ZB50-88K (REFR) ZR84-144K (AC) (1) 005-1271 ZC40,60C CRYO (3) 0880 TW* (1,3) 005-1213 ZR90K, ZR11-19M ZP180K (AC) 1201 ZF24-48K, ZB,ZS56-92K, ZB,ZS11M (REFR) 0906 ZB10-14K, ZBH11-14K (REFR) ZR16-24K, ZP16-23K (AC) (1,4,5)005-1270 (1,4,5) 005-1270 ZP235- ZP295K, ZR250,300K, ZR310,380K Large Commercial Scroll (LCS) ZR22 - ZR 61, ZF09 - 11, ZX21, ZS21-26, VR61 (1) (2) (3) (4) (5) 0953 1199 DIAGRAM MOLDED IN COMPRESSOR TERMINAL BOX. MAY REQUIRE PTC THERMISTOR 70 FRAME 63 FRAME FOR PROPER WIRING SEE SYSTEM WIRING DIAGRAM NOTE: ASTERISK AFTER FIRST TWO LETTERS INDICATES MAY BE ANY LETTER DEPENDING ON ELECTRICAL CHARACTERISTICS. G3 COPELAMETIC DIAGRAMS MODEL TF* ES* M 0803 N 0803 2D 0803 (5,6) 0897 3D 0803, 0816 (4) 0840 0837 (5,6) 0897 ESM TS* (6) 0900 4 (5,6) 0897 (6) 0900 (6) 2169 (7) 1851 6 (5,6) 0897 (6) 0900 (6) 2169 8 9 (6) 2169 0803 0837 (5,6) 0897 (6) 0900 MODEL XAA IA* SAA CAF/CAG H 0809 0809 0809 (3) 0822 K 0809 0809 (1) (2) (3) (4) (5) (6) (7) (3) 0822 SIX LEAD MOTOR THREE LEAD MOTOR 50 HERTZ APPLICATIONS VDE GROUNDING SMALLER VERSION OF 0899 DUAL VOLTAGE MODULE 24 VOLT MODULE NOTE: ASTERISK AFTER FIRST TWO LETTERS INDICATES MAY BE ANY LETTER DEPENDING ON ELECTRICAL CHARACTERISTICS. G4 COPELAMETIC DIAGRAMS MODEL CFB (1) FS* (1) TSE (1) TSU TA* E 0807 0821 0806 H 0807 0810 K 0807 0810 L 0802 0805 M 0804 N 0804 2D 0804 3 (2)TSE (2) TS7 (2)TSU (2) TSC (6) 2170 (5,6) 0914 (6) 2170 0807 0806 3D (6) 2170 4 (6) 2170 (6) 0902 (7)1852 (6) 2167 6 (6) 2170 (6) 0902 (6) 2167 8 (6) 2170 (6) 2167 (6) 2170 (6) 2167 9 (1) (2) (3) (4) (5) (6) (7) CA* 0804 SIX LEAD MOTOR THREE LEAD MOTOR 50 HERTZ APPLICATIONS VDE GROUNDING SMALLER VERSION OF 0899 DUAL VOLTAGE MODULE 24 VOLT MODULE NOTE: ASTERISK AFTER FIRST TWO LETTERS INDICATES MAY BE ANY LETTER DEPENDING ON ELECTRICAL CHARACTERISTICS. G5 The following tables lists discontinued wiring diagrams and their replacements. MODEL VOLTAGE OLD DIAGRAM NEW DIAGRAM JR IFA 0784 No Replacement J,XH IA* 005-0655 005-0697 No Replacement J,XH SAA 0813 No Replacement J,XH CA* 0820 No Replacement J,XH PA* 0781 No Replacement BR/QR ES* 0758 0875 BR/QR TS* 0716 0875 BR/QR EW8 0825 0875 (ES8) BR/QR TS* 0874 0948 BR/QR ES8 0875 0949 BR/QR TF* 005-0492 005-0922 BR/QR TF* 005-0637 005-0922 BR/QR ES* 0815 0875 BR/QR TF* 005-0922 005-1043 BR/QR TF* 005-1043 No Replacement BR/QR ES8 0883 No Replacement BR/QR TS* 0882 No Replacement BR/QR TS* 0948 No Replacement CR ES* 0757 0875 CR EW8 0825 0875 CR ES* 0876 0875 CR EW8 0823 No Replacement CR ES* 0811 0875 G6 MODEL VOLTAGE OLD DIAGRAM NEW DIAGRAM CR EW8 0824 0875 CR, CS ES* 0801 No Replacement CT CSV 0751 0884 CT TS* 0752 0885 CR 63FR PF* 005-0678 005-0799 CR PF* 005-0679 005-0799 CV TF* 0770 No Replacement CR ES8 0875 0917 CT CSV 0884 0918 CT TS* 0885 0919 CR ES8 0917 0949 CT TS* 0919 1319 CT CSV 0918 1318 ZF,ZS,ZB, ZR,ZP,ZB TF* 0826 0880 ASPEN PF* 005-0838 No Replacement ASPEN TF* 1196 No Replacement ASPEN PF* 005-0706 No Replacement ZF,ZS,ZB PF* 005-0788 005-0837 ZF,ZS,ZB PF* 005-0777 005-0819 ZF,ZS,ZB PF* 005-0819 005-0840 ASPEN PF* 0756 No Replacement ZB PF* 005-0788 005-0837 ZB PF* 005-0837 005-0860 ZB,ZF PF* 005-0777 005-0819 ZB,ZF,ZS PF* 005-0819 005-0840 ZR (AC) TW* 1825 1201 G7 MODEL VOLTAGE OLD DIAGRAM NEW DIAGRAM ZF,ZS,ZB (REFR) TW* 1825 0906 ZB PF* 005-0840 005-1062 ZB,ZR TF* 005-0868 005-0922 ZB,ZR TF* 005-0922 005-1043 ZB, ZS, ZF, ZRD, ZP PF* 005-0860 005-1071 9 THC,TLC 0748 0853 (TSC) 9 THC,TLC 0748 0803 (TFC) 9 THD,TLD 0748 0803 (TFD) 9 THE,TLE 0748 0803 (TFE) 9 FS* 0856 0899, See note 2 9 ESM 0858 0900, See note 2 9 TS* 0853 0896, See note 2 9 TSE,TSU,TSC,TS7 0896 2167 9 FS*,TSE,TSU 0899 2170 4/6 TSE 0759 No Replacement 4/6 FS*,TSE, TSU 0841 0857 4/6 TSE,TSU, TS7 0760 0853, See note 1 4/6 ES* 0762 0854, See note 1 4/6 ESM 0848 0858, See note 1 4/6,8 TS* 0763 0855, See note 1 4/6,8 FS* 0765 0856, See note 1 G8 MODEL VOLTAGE 4/6,8 TS* 4/6,8 4/6,8 OLD DIAGRAM NEW DIAGRAM 0898 2169 TSE,TSU,TSC,TS7 0896 2167 FS*,TSE,TSU 0899 2170 4/6 TSE/TSU 0765 0856, See note 1 4DK6, 4DS6 FSD 0902 1299, See note 2 4DK6, 4DS6 FSD 1299 2177, See note 2 4,6 FS* 0857 0902, See note 2 4,6 TSE 0853 0896, See note 2 4,6 TS* 0855 0898,See note 2 4,6 ESM 0858 0900, See note 2 8 TS* 0855 0898, See note 2 8 TS7 0853 0896, See note 2 M FSC 0849 0859, See Note 1 M FS* 0856 0899, See note 2 M FS* 0859 0914, See note 2 M ES* 0854 0897, See note 2 2D FS* 0856 0899, See note 2 2D ES* 0854 0897, See note 2 3D ES* 0854 0897, See note 2 Notes: 1. Models replaced with dual voltage 31aa module. (Requires a jumper wire from L2 to LO for 120V and L2 to HI for 240V) 2. Models replaced with dual voltage 41aa module. (Jumper wire not required) G9 Wiring Diagram 005-0670 G10 Wiring Diagram 0767 G11 Wiring Diagram 0768 G12 Wiring Diagram 0769 G13 Wiring Diagram 0770 G14 Wiring Diagram 0774/0775 G15 Wiring Diagram 005-0776, 005-0821 G16 Wiring Diagram 0776/0777 G17 Wiring Diagram 0778/0779 G18 Wiring Diagram 0780 G19 Wiring Diagram 0781 G20 Wiring Diagram 0782 G21 Wiring Diagram 0802 G22 Wiring Diagram 0803 G23 Wiring Diagram 0804 G24 Wiring Diagram 0805 G25 Wiring Diagram 0806 G26 Wiring Diagram 0807 G27 Wiring Diagram 0809 G28 Wiring Diagram 0810 G29 Wiring Diagram 0816 G30 Wiring Diagram 0818/0819 G31 Wiring Diagram 0820 G32 Wiring Diagram 0821 G33 USE COPPER CONDUCTORS ONLY. USE THIS EQUIPMENT ON A GROUNDED SYSTEM ONLY. USE MINIMUM 75 C WIRE FOR AMPACITY DETERMINATION. EXTERNAL MOTOR PROTECTION-ALLOW TIME FOR RESET. CRANKCASE HEATER, WHEN APPLIED, MUST BE CONNECTED ONLY TO ITS RATED VOLTAGE. ON 115 VOLT, CONNECT NEUTRAL TO TERMINAL "1". OVERCURRENT PROTECTION DEVICE RATING AND TYPE MUST BE IN ACCORDANCE WITH REGULATORY AGENCY END PRODUCT APPROVALS-SEE SYSTEM NAMEPLATE. C 2 1 LINE R S S R MOTOR WINDING CONNECTIONS START CAPACITOR RED BLUE BLACK 2 1 5 CURRENT RELAY C YELLOW RUN CAPACITOR 9-93 Wiring Diagram 0822 G34 052-0822-00 Wiring Diagram 0831/0832 G35 Wiring Diagram 0833 G36 Wiring Diagram 0834 G37 Wiring Diagram 0837 G38 Wiring Diagram 0840 G39 Wiring Diagram 0865 G40 Wiring Diagram 0880 G41 Wiring Diagram 0897 (Top) G42 Wiring Diagram 0897 (Bottom) G43 Wiring Diagram 0900 (Top) G44 Wiring Diagram 0900 (Bottom) G45 3 FOR USE WITH KRIWAN SCY (PHASE SENSING) MODULE ONLY MOTOR WINDING CONNECTIONS/ L2 BORNES DES ENROULEMENTS DU MOTEUR/ ANSCHLUSS DER MOTORWICKLUNGEN L1 INTERNAL THERMAL SENSORS/ CAPTEURS THERMIQUES INTERNES/ INTERNE TEMPERATURSENSOREN L1 L2 L3 L3 T2 T1 S2 S1 M2 M1 FOR USE WITH KRIWAN SCY (PHASE SENSING) MODULE ONLY 3 1 2 L1 1 2 3 PROTECTOR MODULE VOLTAGE/TENSION DU MODULE DU DISPOSITIF DE PROTECTION/ANSCHLUSSPANNUNG DES SCHUTZGERAETES TO CONTROL CIRCUIT/VERS LE CIRCUIT DE COMMANDE/ZUM STEUERSTROMKREIS F0R KRIWAN SCY (PHASE SENSING) MODULES ONLY TO MOTOR TERMINAL BLOCK/VERS BORNES DE BRANCHMENT DES BOUNES MOTEUR/ZUR BELEGUNG DER MOTOR KLEMMEN NOTE: SOLID STATE MODULE HAS 30 MINUTES TIME DELAY BEFORE RESET IN EVENT OF PROTECTOR TRIP. NOTE: EN CAS DE DECLENCHEMENT DU MODULE DE PROTECTION, LE REARMEMENT EST RETARDE A 30 MINUTES. NOTIZ: MOTORSCHUTZGERAET HAT EINE ZEITVERZOEGERUNG VON 30 MINUTEN ZUM RUECKSCHALTEN L2 USE COPPER CONDUCTORS ONLY. USE A TEMPERATURE OF 75C WHEN DETERMINING CROSS SECTION OF LEAD FOR MAX CURRENT. USE THIS EQUIPMENT ON A GROUNDED SYSTEM ONLY. PRIMARY SINGLE PHASE FAILURE PROTECTION IS PROVIDED. PROTECTOR MODULE AND OPTIONAL CRANKCASE HEATER MUST BE CONNECTED ONLY TO THEIR RATED VOLTAGE. OVERCURRENT PROTECTION DEVICE RATING AND TYPE MUST BE IN ACCORDANCE WITH REGULATION AND PRODUCT APPROVALS -SEE SYSTEM NAMEPLATE. N'UTILISER QUE DES CONDUCTEURS EN CUIVRE. UTILIER UNE TEMPERATURE ED 75C POUR DETERMINER LA SECTION DES CABLES POUR LE COURANT MAXIMUM. EMPLOYER CET EQUIPEMENT SEULEMENT SUR SYSTEME MIS A LA TERRE. PROTECTION PRIMAIRE MONOPHASEE FOURNIE. LE MODULE DU DISPOSITIF DE PROTECTION ET LE CHAUFFE-CARTER FACULTATIF DOIVENT ETRE BRANCHES A LA TENSION NOMINALE APPROPRIEE. LE TYPE ET LES CARACTERISTIQUES NOMINALES DU DISPOSITIF DE PROTECTION CONTRE LES SURINTENSITES DOIVENT ETRE CONFORMES AUX EXIGENCES DES POUVOIRS DE REGLEMENTATION VISANT LE PRODUIT FINI -VOIR LA PLAQUE SIGNALETIQUE. NUR KUPFERLEITUNGEN VERWENDEN. ZUR BESTIMMUNG DES LEITERQUERSCHNITTS MUESSEN KABEL VERWENDET WERDEN, DIE FUER EINE BELASTUNG VON HUECHSTENS 75C ZUGELASSEN SIND. ANLAGE NUR MIT ERDUNG VERWENDEN. SCHUTZ BEI PHASENAUSFALL AUF DER PRIMAERSEITE IST GEWAEHRLEISTET. SCHUTZGERAET UND KURBELGEHAEUSEHEIZER (FALLS VORHANDEN) DUERFEN NUR MIT NENNSPANNUNG BETRIEBEN WERDEN. NENNLEISTUNG UND TYP DES UEBERSTROMSCHUTZSCHALTERS MUESSEN IN UEBEREINSTIMMUNG MIT ZUTREFFENDEN VORSCHRIFTEN SEIN -BITTE TYPENSCHILD BEACHTEN. Wiring Diagram 0906 G46 L3 6/99 (8525681) 052-0906-00 This page is left blank intentionally. G47 Wiring Diagram 0914 (Top) G48 Wiring Diagram 0914 (Bottom) G49 Wiring Diagram 0929 G50 USE MINIMUM 75C COPPER WIRE FOR AMPACITY DETERMINATION. WHEN PROVIDED, CRANKCASE HEATER AND FAN MUST BE CONNECTED ONLY TO THEIR RATED VOLTAGE. SYSTEM OVERCURRENT PROTECTION DEVICE RATING AND TYPE MUST BE IN ACCORDANCE WITH REGULATORY AGENCY END PRODUCT APPROVALS - SEE SYSTEM NAMEPLATE. FAN LEADS ARE FACTORY PROVIDED ON CONDENSING UNITS. LINE (230V) NEUTRAL (115V) CURRENT RELAY LINE FAN LINE GND START CAPACITOR 052-0929-00 2 1 8-02 R S EXTERNAL PROTECTOR C BLK Wiring Diagram 0930 G51 Wiring Diagram 0931 G52 USE MINIMUM 75C INTERNAL PROTECTOR LINE GND COPPER WIRE FOR BLK C LINE AMPACITY FAN DETERMINATION. 5 LINE RED WHEN PROVIDED, 1 (230V) S CRANKCASE HEATER R AND FAN MUST BE NEUTRAL 2 CONNECTED ONLY TO (115V) START THEIR RATED VOLTAGE. BLU CAPACITOR SYSTEM OVERCURRENT PROTECTION YEL (WHEN PROVIDED) DEVICE RATING AND TYPE MUST RUN CAPACITOR BE IN ACCORDANCE WITH REGULATORY (WHEN PROVIDED) AGENCY END PRODUCT APPROVALS POTENTIAL RELAY -SEE SYSTEM NAMEPLATE. (WHEN PROVIDED) 11-02 052-0931-00 Wiring Diagram 0932 G53 EXTERNAL LINE GND USE MINIMUM 75C COPPER PROTECTOR WIRE FOR AMPACITY LINE C DETERMINATION. BLK WHEN PROVIDED, CRANKCASE 5 HEATER AND FAN MUST BE 1 RED FAN LINE S CONNECTED ONLY R (230V) TO THEIR RATED 2 NEUTRAL VOLTAGE. BLU (115V) SYSTEM OVERCURRENT START CAPACITOR PROTECTION DEVICE RATING (WHEN PROVIDED) AND TYPE MUST BE IN YEL RUN CAPACITOR ACCORDANCE WITH REGULATORY (WHEN PROVIDED) AGENCY END PRODUCT APPROVALS POTENTIAL RELAY -SEE SYSTEM NAMEPLATE. (WHEN PROVIDED) 11-02 052-0932-00 Wiring Diagram 0953 G54 Wiring Diagram 0980 G55 Wiring Diagram 1199 G56 INTERNAL THERMAL SENSORS/ CAPTEURS THERMIQUES INTERNES/ INTERNE TEMPERATURSENSOREN T2 T1 1 S2 S1 M2 MOTOR WINDING CONNECTIONS/ L2 BORNES DES ENROULEMENTS DU MOTEUR/ ANSCHLUSS DER MOTORWICKLUNGEN L1 L3 M1 2 L1 L3 L2 USE THIS EQUIPMENT ON A GROUNDED SYSTEM ONLY. PRIMARY SINGLE PHASE FAILURE PROTECTION IS PROVIDED. PROTECTOR MODULE AND OPTIONAL CRANKCASE HEATER MUST BE CONNECTED ONLY TO THEIR RATED VOLTAGE. OVERCURRENT PROTECTION DEVICE RATING AND TYPE MUST BE IN ACCORDANCE WITH REGULATION AND PRODUCT APPROVALS -SEE SYSTEM NAMEPLATE. 1 2 PROTECTOR MODULE VOLTAGE/TENSION DU MODULE DU DISPOSITIF DE PROTECTION/ANSCHLUSSPANNUNG DES SCHUTZGER-TES TO CONTROL CIRCUIT/VERS LE CIRCUIT DE COMMANDE/ZUM STEUERSTROMKREIS NOTE: SOLID STATE MODULE HAS 30 MINUTES TIME DELAY BEFORE RESET IN EVENT OF PROTECTOR TRIP. NOTE: EN CAS DE DECLENCHEMENT DU MODULE DE PROTECTION, LE REARMEMENT EST RETARDE DE 30 MINUTES. NOTIZ: MOTORSCHUTZGER-T HAT EINE ZEITVERZ+GERUNG VON 30 MINUTEN ZUM R_CKSCHALTEN EMPLOYER CET EQUIPEMENT SEULEMENT SUR SYSTEME MIS A LA TERRE. PROTECTION PRIMAIRE MONOPHASEE FOURNIE. LE MODULE DU DISPOSITIF DE PROTECTION ET LE CHAUFFE-CARTER FACULTATIF DOIVENT ETRE BRANCHES A LA TENSION NOMINALE APPROPRIEE. LE TYPE ET LES CARACTERISTIQUES NOMINALES DU DISPOSITIF DE PROTECTION CONTRE LES SURINTENSITES DOIVENT ETRE CONFORMES AUX EXIGENCES DES POUVOIRS DE REGLEMENTATION VISANT LE PRODUIT FINI -VOIR LA PLAQUE SIGNALETIQUE. ANLAGE NUR MIT ERDUNG VERWENDEN. SCHUTZ BEI PHASENAUSFALL AUF DER PRIM-RSEITE IST GEW-HRLEISTET. SCHUTZGER-T UND KURBELGEH-USEHEIZER (FALLS VORHANDEN) D_RFEN NUR MIT NENNSPANNUNG BETRIEBEN WERDEN. NENNLEISTUNG UND TYP DES _BERSTROMSCHUTZSCHALTERS M_SSEN IN _BEREINSTIMMUNG MIT ZUTREFFENDEN VORSCHRIFTEN SEIN -BITTE TYPENSCHILD BEACHTEN. 052-1201-00 Wiring Diagram 1201 G57 CONNECTOR CONNECTOR BLOCK BLOC K (WHEN REQD) REQD) 1 2 3 MOTOR WINDING WINDING CONNECTIONS CONNECTION S Wiring Diagram 005-1211-01 G58 8-06 T3 USE COPPER CONDUCTOR CONDUCTORSS ONLY.. ONLY USE THIS EQUIPMENT ON A GROUNDED SYSTEM ONLY. ONLY. FOR R USE MINIMUM 75 C WIRE FO AMPACITY DETERMINATION. DETERMINATION. PRIMARY SINGLE PHASE FAILURE FAILURE PROTECTION IS PROVIDED. PROVIDED. INTERNAL MOTOR PROTECTION-ALLOW PROTECTION-ALLOW TIME FOR RESET. RESET. CRANKCASE HEATER, WHEN APPLIED, APPLIED, MUST BE CONNECTED ONLY TO ITS ITS RATED VOLTAGE. VOLTAGE. OVERCURRENT PROTECTION DEVICE DEVICE RATING AND TYPE MUST BE IN IN ACCORDANCE WITH REGULATORY AGENCY AGENCY END PRODUCT APPROVALS- SEE SYSTEM SYSTEM NAMEPLATE. NAMEPLATE . 005-1211-01 T2 T1 005-1213-00 8-06 Wiring Diagram 005-1213 G59 Wiring Diagram 1223 G60 8-02 052-1223-00 START CAPACITOR NEUTRAL (115V) USE MINIMUM 75C COPPER LINE (230V) CURRENT WIRE FOR AMPACITY FAN RELAY DETERMINATION. WHEN PROVIDED, CRANKCASE LINE BLACK HEATER AND FAN MUST BE 4 CONNECTED ONLY TO THEIR RATED VOLTAGE. EXTERNAL SYSTEM OVERCURRENT PROTECTOR 2 1 C PROTECTION DEVICE RATING AND BLACK TYPE MUST BE IN ACCORDANCE YELLOW WITH REGULATORY AGENCY S R RED END PRODUCT APPROVALS -SEE SYSTEM NAMEPLATE. BLACK LINE GND BLA CK 005-1270-00 8-06 Wiring Diagram 005-1270 G61 Wiring Diagram 005-1271 G62 Wiring Diagram 1318 G63 Wiring Diagram 1319 G64 Wiring Diagram 1851 G65 Wiring Diagram 1852 G66 This page is left blank intentionally. G67 Wiring Diagram 2167 (Left Side) G68 Wiring Diagram 2167 (Right Side) G69 Wiring Diagram 2169 (Top) G70 Wiring Diagram 2169 (Bottom) G71 Wiring Diagram 2170 (Top) G72 Wiring Diagram 2170 (Bottom) G73 Wiring Diagram 2177 (Left Side) G74 Wiring Diagram 2177 (Right Side) G75 Discontinued Wiring Diagram 005-0492, 0637 G76 Discontinued Wiring Diagram 005-0655, 0697 G77 Discontinued Wiring Diagram 005-0678-00, 005-0679-00 G78 Discontinued Wiring Diagram 005-0706 G79 Discontinued Wiring Diagram 0716 G80 This page is left blank intentionally. G81 Discontinued Wiring Diagram 0748 (Left Side) G82 Discontinued Wiring Diagram 0748 (Right Side) G83 Discontinued Wiring Diagram 0751 G84 Discontinued Wiring Diagram 0752 G85 Discontinued Wiring Diagram 0756 G86 Discontinued Wiring Diagram 0757 G87 Discontinued Wiring Diagram 0758 G88 Discontinued Wiring Diagram 0759 G89 Discontinued Wiring Diagram 0760 G90 This page is left blank intentionally. G91 Discontinued Wiring Diagram 0762 (Left Side) G92 Discontinued Wiring Diagram 0762 (Right Side) G93 Discontinued Wiring Diagram 0763 (Left Side) G94 Discontinued Wiring Diagram 0763 (Right Side) G95 Discontinued Wiring Diagram 0765 (Left Side) G96 Discontinued Wiring Diagram 0765 (Right Side) G97 Discontinued Wiring Diagram 005-0777 G98 Discontinued Wiring Diagram 0784 G99 Discontinued Wiring Diagram 005-0788 G100 4-95 005-0799-00 Discontinued Wiring Diagram 005-0799-00, 005-0800-00 G101 CONNECTOR CONNECTOR BLOCK BLOC K (WHEN REQD) REQD) 1 2 3 MOTOR WINDING WINDING CONNECTIONS CONNECTION S Discontinued Wiring Diagram 005-0800-01 G102 4-95 T3 USE COPPER CONDUCTOR CONDUCTORSS ONLY.. ONLY USE THIS EQUIPMENT ON A GROUNDED SYSTEM ONLY ONLY. . FOR R USE MINIMUM 75 C WIRE FO AMPACITY DETERMINATION. DETERMINATION. PRIMARY SINGLE PHASE FAILURE FAILURE PROTECTION IS PROVIDED. PROVIDED. INTERNAL MOTOR PROTECTION-ALLOW PROTECTION-ALLOW TIME FOR RESET. RESET. CRANKCASE HEATER, WHEN APPLIED, APPLIED, MUST BE CONNECTED ONLY TO ITS ITS RATED VOLTAGE VOLTAGE. . OVERCURRENT PROTECTION DEVICE DEVICE RATING AND TYPE MUST BE IN IN ACCORDANCE WITH REGULATORY AGENCY AGENCY END PRODUCT APPROVALS- SEE SYSTEM SYSTEM NAMEPLATE. NAMEPLATE . 005-0800-01 T2 T1 Discontinued Wiring Diagram 0801 G103 Discontinued Wiring Diagram 0811 G104 U1 W3 V2 X4 RESISTANCE ACROSS MOTOR SENSORS SHOUL SHOULD BE APPROXIMATELY 1500 T0 7800 OHM OHMS WITH A MOTOR TEMPERATURE BELOW 60 C C. USE OHMMETER ONLY (6 VOLTS MAXIMUM) T TO CHECK SENSOR RESISTANCE. DO NOT SHOR SHORT ACROSS THE TERMINALS TERMINALS. WHEN CHECKING SOLID STATE MODULE: MODULE X S S1 LINE M2 T1 T2 CONTROL CIRCUIT M1 PROTECTOR MODULE MODUL VOLTAGE VOLTAG MAI MAIN L1 L2 L3 DELTA CONNECTED CONNECTE TO CONTROL CONTRO CIRCUIT CIRCUI Z6 M1 X S S1 LINE M2 T1 T2 CONTROL CIRCUIT U1 USE COPPER CONDUCTORS ONLY. ONLY USE MINIMUM 75 C WIRE FOR FO AMPACITY DETERMINATION. DETERMINATION USE THIS EQUIPMENT ON A GROUNDED GROUNDE SYSTEM ONLY. ONLY PRIMARY SINGLE PHASE FAILURE FAILUR PROTECTION IS PROVIDED. PROVIDED PROTECTOR MODULE AND OPTIONAL OPTIONA CRANKCASE HEATER MUST BE CONNECTED CONNECTE ONLY TO THEIR RATED VOLTAGE. VOLTAGE OVERCURRENT PROTECTION DEVICE DEVIC RATING AND TYPE MUST BE IN I ACCORDANCE WITH REGULATORY REGULATOR AGENCY END PRODUCT APPROVALSAPPROVALS SEE SYSTEM NAMEPLATE. NAMEPLATE SENSORS SENSOR Y5 PROTECTOR MODUL MODULE VOLTAGE VOLTAG L1 W3 MAI MAIN L2 L3 1 3 5 Z6 4 6 X4 9-93 Y5 2 SENSORS SENSOR 052-0811-00 052-0811-0 MOTOR WINDING WINDIN CONNECTIONS CONNECTION V2 STAR CONNECTED CONNECTE TO CONTROL CONTRO CIRCUIT CIRCUI Discontinued Wiring Diagram 0813 G105 Discontinued Wiring Diagram 0815 G106 Discontinued Wiring Diagram 005-0819 G107 DELTA CONNECTED PROTECTOR MODULE VOLTAGE TO CONTROL CIRCUIT M1 M2 L1 L1 STAR CONNECTED MAIN L2 L3 TO CONTROL CIRCUIT L2 V2 U1 X4 Y5 M1 M2 S1 S2 L1 L1 MAIN L2 L3 L2 V2 U1 PART No. 40AA300E ** X PROTECTOR MODULE VOLTAGE Y5 PART No. 40AA300E ** W3 Z6 X SENSORS 120 OR 240 VOLT MODULE WIRING WHEN CHECKING PROTECTOR USE OHMMETER ONLY (6 VOLTS MAXIMUM) TO CHECK SENSOR RESISTANCE. DO NOT SHORT ACROSS THE TERMINALS. RESISTANCE ACROSS MOTOR SENSORS SHOULD BE APPROXIMATELY 750 OHMS WITH A MOTOR TEMPERATURE BELOW 60 C. ** THE 40AA300E MODULE HAS A FOUR MINUTE TIME DELAY BEFORE RESET IN EVENT OF PROTECTOR TRIP OR LOSS OF MODULE POWER. THE 40AA100E MODULE IS NOT FURNISHED WITH A TIME DELAY DEVICE. S1 S2 Z6 W3 SENSORS 120 OR 240 VOLT MODULE WIRING USE COPPER CONDUCTORS ONLY. USE MINIMUM 75 C WIRE FOR AMPACITY DETERMINATION. U1 USE THIS EQUIPMENT ON A GROUNDED SYSTEM ONLY. PRIMARY SINGLE PHASE FAILURE PROTECTION IS PROVIDED. X4 Z6 PROTECTOR MODULE AND OPTIONAL CRANKCASE HEATER MUST BE CONNECTED ONLY TO THEIR RATED VOLTAGE. OVERCURRENT PROTECTION DEVICE RATING AND TYPE MUST BE IN ACCORDANCE WITH REGULATORY AGENCY END PRODUCT APPROVALSSEE SYSTEM NAMEPLATE. Discontinued Wiring Diagram 0823 Y5 V2 W3 MOTOR WINDING CONNECTIONS 6-00 G108 X4 052-0883-00 Discontinued Wiring Diagram 0824 G109 Discontinued Wiring Diagram 0825 G110 Discontinued Wiring Diagram 0826 G111 Discontinued Wiring Diagram 005-0837 G112 Discontinued Wiring Diagram 005-0838 G113 Discontinued Wiring Diagram 005-0840 G114 This page is left blank intentionally. G115 Discontinued Wiring Diagram 0841 (Left Side) G116 Discontinued Wiring Diagram 0841 (Right Side) G117 Discontinued Wiring Diagram 0848 G118 Discontinued Wiring Diagram 0849 G119 Discontinued Wiring Diagram 0853 (Left Side) G120 Discontinued Wiring Diagram 0853 (Right Side) G121 Discontinued Wiring Diagram 0854 (Top) G122 Discontinued Wiring Diagram 0854 (Bottom) G123 Discontinued Wiring Diagram 0855 G124 This page is left blank intentionally. G125 Discontinued Wiring Diagram 0856 (Top) G126 Discontinued Wiring Diagram 0856 (Bottom) G127 Discontinued Wiring Diagram 0857 (Left Side) G128 Discontinued Wiring Diagram 0857 (Right Side) G129 Discontinued Wiring Diagram 0858 (Top) G130 Discontinued Wiring Diagram 0858 (Bottom) G131 Discontinued Wiring Diagram 0859 (Left Side) G132 Discontinued Wiring Diagram 0859 (Right Side) G133 LINE S R Discontinued Wiring Diagram 005-0860 G134 XX 005-0860-00 C 3-96 USE COPPER CONDUCTORS ONLY. USE THIS EQUIPMENT ON A GROUNDED SYSTEM ONLY. USE MINIMUM 75C WIRE FOR AMPACITY DETERMINATION. INTERNAL MOTOR PROTECTIONALLOW TIME FOR RESET. OVERCURRENT PROTECTION DEVICE RATING AND TYPE MUST BE IN ACCORDANCE WITH REGULATORY AGENCY END PRODUCT APPROVALS-SEE SYSTEM NAMEPLATE. RUN CAPACITOR LINE Discontinued Wiring Diagram 005-0868 G135 Discontinued Wiring Diagram 0874 G136 Discontinued Wiring Diagram 0875 G137 Discontinued Wiring Diagram 0876 G138 Discontinued Wiring Diagram 0882 G139 Discontinued Wiring Diagram 0883 G140 Discontinued Wiring Diagram 0884 G141 Discontinued Wiring Diagram 0885 G142 This page is left blank intentionally. G143 Discontinued Wiring Diagram 0896 (Left Side) G144 Discontinued Wiring Diagram 0896 (Right Side) G145 Discontinued Wiring Diagram 0898 (Top) G146 Discontinued Wiring Diagram 0898 (Bottom) G147 Discontinued Wiring Diagram 0899 (Top) G148 Discontinued Wiring Diagram 0899 (Bottom) G149 Discontinued Wiring Diagram 0902 (Left Side) G150 Discontinued Wiring Diagram 0902 (Right Side) G151 Discontinued Wiring Diagram 0917 G152 TWO SPEED SINGLE PHASE LINE LINE T3 T8 T1 T7 T3 T8 T1 T2 LOW SPEED T7 T2 HIGH SPEED T2 T7 T8 T3 Part-No. XXXXXX 2 POLE START MAIN WINDING 4 POLE START EXTERNAL MAIN T1 L1 L2 S1 S2 M1 M2 PROTECTOR MODULE VOLTAGE MOTOR WINDING CONNECTIONS SENSORS TO CONTROL CIRCUIT USE COPPER CONDUCTORS ONLY. USE MINIMUM 75 C WIRE FOR AMPACITY DETERMINATION. USE THIS EQUIPMENT ON A GROUNDED SYSTEM ONLY. PROTECTOR MODULE AND OPTIONAL CRANKCASE HEATER MUST BE CONNECTED ONLY TO THEIR RATED VOLTAGE. OVERCURRENT PROTECTION DEVICE RATING AND TYPE MUST BE IN ACCORDANCE WITH REGULATORY AGENCY END PRODUCT APPROVALS-SEE SYSTEM NAMEPLATE. SEE SYSTEM MANUFACTURER'S WIRING DIAGRAM FOR START 1-00 052-0918-00 COMPONENT CONNECTIONS. Discontinued Wiring Diagram 0918 G153 TWO SPEED LINE LOW SPEED THREE PHASE T4 LINE HIGH SPEED T1 T3 T2 T5 T1 T2 T4 T3 T5 T6 MOTOR WINDING CONNECTIONS T6 Part-No. XXXXXX L1 L2 S1 S2 M1 M2 T4 T5 T1 T6 T2 T3 PROTECTOR MODULE VOLTAGE SENSORS USE COPPER CONDUCTORS ONLY. USE MINIMUM 75 C WIRE FOR AMPACITY DETERMINATION. USE THIS EQUIPMENT ON A GROUNDED SYSTEM ONLY. PRIMARY SINGLE PHASE FAILURE PROTECTION IS PROVIDED. PROTECTOR MODULE AND OPTIONAL CRANKCASE HEATER MUST BE CONNECTED ONLY TO THEIR RATED VOLTAGE. OVERCURRENT PROTECTION DEVICE RATING AND TYPE MUST BE IN ACCORDANCE WITH REGULATORY AGENCY END PRODUCT APPROVALS-SEE SYSTEM NAMEPLATE. 1-00 052-0919-00 Discontinued Wiring Diagram 0919 G154 TO CONTROL CIRCUIT Discontinued Wiring Diagram 005-0922 G155 PROTECTOR MODULE VOLTAGE TO CONTROL CIRCUIT L1 MAIN L2 L3 2 1 2 M1 M2 L1 L2 3 1 PART No. 40AA300E ** 3 X S1 S2 MOTOR WINDING CONNECTIONS SENSORS 120 OR 240 VOLT MODULE WIRING WHEN CHECKING PROTECTOR USE OHMMETER ONLY (6 VOLTS MAXIMUM) TO CHECK SENSOR RESISTANCE. DO NOT SHORT ACROSS THE TERMINALS. RESISTANCE ACROSS MOTOR SENSORS SHOULD BE APPROXIMATELY 750 OHMS WITH A MOTOR TEMPERATURE BELOW 60 C. ** THE 40AA300E MODULE HAS A FOUR MINUTE TIME DELAY BEFORE RESET IN EVENT OF PROTECTOR TRIP OR LOSS OF MODULE POWER. THE 40AA100E MODULE IS NOT FURNISHED WITH A TIME DELAY DEVICE. USE COPPER CONDUCTORS ONLY. USE MINIMUM 75 C WIRE FOR AMPACITY DETERMINATION. USE THIS EQUIPMENT ON A GROUNDED SYSTEM ONLY. PRIMARY SINGLE PHASE FAILURE PROTECTION IS PROVIDED. PROTECTOR MODULE AND OPTIONAL CRANKCASE HEATER MUST BE CONNECTED ONLY TO THEIR RATED VOLTAGE. OVERCURRENT PROTECTION DEVICE RATING AND TYPE MUST BE IN ACCORDANCE WITH REGULATORY AGENCY END PRODUCT APPROVALS-SEE SYSTEM NAMEPLATE. 6-00 Discontinued Wiring Diagram 0948 G156 052-0948-00 DELTA CONNECTED PROTECTOR MODULE VOLTAGE TO CONTROL CIRCUIT M1 M2 L1 L1 STAR CONNECTED MAIN L2 L3 TO CONTROL CIRCUIT L2 M1 V2 U1 X4 S1 S2 L1 M2 L1 MAIN L2 L3 L2 Y5 V2 U1 PART No. 40AA300E ** X PROTECTOR MODULE VOLTAGE X4 Y5 PART No. 40AA300E ** W3 Z6 X S1 S2 W3 Z6 SENSORS 120 OR 240 VOLT MODULE WIRING SENSORS 120 OR 240 VOLT MODULE WIRING WHEN CHECKING PROTECTOR USE OHMMETER ONLY (6 VOLTS MAXIMUM) TO CHECK SENSOR RESISTANCE. DO NOT SHORT ACROSS THE TERMINALS. RESISTANCE ACROSS MOTOR SENSORS SHOULD BE APPROXIMATELY 750 OHMS WITH A MOTOR TEMPERATURE BELOW 60 C. ** THE 40AA300E MODULE HAS A FOUR MINUTE TIME DELAY BEFORE RESET IN EVENT OF PROTECTOR TRIP OR LOSS OF MODULE POWER. THE 40AA100E MODULE IS NOT FURNISHED WITH A TIME DELAY DEVICE. USE COPPER CONDUCTORS ONLY. USE MINIMUM 75 C WIRE FOR AMPACITY DETERMINATION. USE THIS EQUIPMENT ON A GROUNDED SYSTEM ONLY. PRIMARY SINGLE PHASE FAILURE PROTECTION IS PROVIDED. PROTECTOR MODULE AND OPTIONAL CRANKCASE HEATER MUST BE CONNECTED ONLY TO THEIR RATED VOLTAGE. OVERCURRENT PROTECTION DEVICE RATING AND TYPE MUST BE IN ACCORDANCE WITH REGULATORY AGENCY END PRODUCT APPROVALSSEE SYSTEM NAMEPLATE. U1 X4 Z6 Y5 V2 W3 MOTOR WINDING CONNECTIONS 6-00 052-0949-00 Discontinued Wiring Diagram 0949 G157 Discontinued Wiring Diagram 005-1043 G158 Discontinued Wiring Diagram 005-1062 G159 Discontinued Wiring Diagram 005-1071 G160 Discontinued Wiring Diagram 1196 G161 Discontinued Wiring Diagram 1299 (Left Side) G162 Discontinued Wiring Diagram 1299 (Right Side) G163 Discontinued Wiring Diagram 1825, 0700-8503514 G164 SECTION H ELECTRICAL TROUBLESHOOTING PROCEDURES TOPICS If The Compressor Will Not Run ............................... H2 If The Compressor Starts But Trips Repeatedly ....... H5 If The Compressor Runs But Will Not Refrigerate .... H8 CAUTION Before attempting any electrical trouble-shooting, make sure all grounds are connected and secure and there is ground continuity throughout the compressor system. Also ensure the compressor system is correctly grounded to the power supply. If you are not a qualifed service person familiar with electrical troubleshooting techniques, DO NOT PROCEED until a qualifed service person is available. IF THE COMPRESSOR WILL NOT RUN If a compressor fails to start and run properly, it is important that the compressor be tested to determine its condition. It is possible that external electrical components may be defective, the protector may be open, a safety device may be tripped, or other conditions may be preventing compressor operation. If the compressor is not the source of the malfunction, replacing the compressor will only result in the unnecessary expenditure of time and money while the basic problem remains. 1. If there is no voltage at the compressor terminals, follow the wiring diagram and check back from the compressor to the power supply to find where the circuit is interrupted. Check the controls (low pressure, high pressure, thermostat, oil pressure safety, etc.) to see if the contact points are closed. If a contactor is used, check to see if the contacts are closed. Check for a blown fuse, open disconnect switch, or loose connections. 2. If voltage is available at the compressor terminals and it is below 90 percent of the nameplate voltage, it is possible the motor may not develop sufficient starting torque. Check to determine if wire sizes are adequate, electrical connections are loose, the circuit is overloaded, or if the power supply is adequate. 3. On units with single phase PSC motors, the suction and discharge pressures must be equalized before starting because of the low starting torque of the motor. Any change in the refrigerant metering device, H2 the addition of a drier, or other changes in the system components may delay pressure equalization and create difficulties. If PSC motor starting problems are being encountered, the addition of a hard start kit is recommended. 4. On single phase compressors, a defective start capacitor or relay may prevent the compressor from starting. If the compressor attempts to start, but is unable to do so or if there is a humming sound, check the relay to see if the relay contacts are damaged or its coil opened. The relay contacts should be closed during the initial starting cycle, but should open as the compressor comes up to speed. Remove the wires from the start relay and check continuity through the relay coil. Replace the relay if there is no continuity. Use an ohmmeter to check across the relay contacts. Potential relay contacts are normally closed when the relay is not energized, while current relay contacts are normally open. If either gives an incorrect reading, replace the relay. Do not attempt to run a compressor that has a capacitor that is bulging, leaking, or damaged. It must be replaced. Make sure capacitors are electrically discharged before checking. Start capacitors should have bleed resistors. Check for continuity between the capacitor terminals and between the capacitor terminals and the case. Continuity indicates a short, and the capacitor should be replaced. Substitute “a known to be good” start capacitor if available. If the compressor then starts and runs properly, replace the original start capacitor. On H3 PSC motors, substitute a “a known to be good” run capacitor if available. If the compressor then starts and run properly, replace the original run capacitor.If a capacitor tester is not available, an ohmmeter may be used to check run and start capacitors for shorts or open circuits. Use an ohmmeter set to its highest resistance scale and connect probes to capacitor terminals. a. With a good capacitor, the indicator should first move towards zero and then increase towards infinity. b. If there is no movement of the ohmmeter indicator, an open circuit is indicated. c. If the ohmmeter indicator moves to zero and remains there or on a low resistance reading, a short circuit is indicated. Defective capacitors should be replaced. 5. If the correct voltage is available at the compressor terminals and no current is drawn, remove power. Then remove all wires from the terminals and check for continuity through the motor winding. On single phase compressors, check for continuity from terminals C to R, and C to S and R to S. On three phase compressors, check for continuity between the terminals for connections to phases 1 and 2, 2 and 3, and 1 and 3. On compressors with line break inherent (internal) protectors, an open overload protector can cause a lack of continuity. If the compressor is warm, it may require consider-able time to cool down. If continuity cannot be established through all motor winding, the compressor should be replaced. H4 Check the motor for ground by means of a continuity check between the common terminal and the compressor shell. If there is a ground, replace the compressor. 6. If the compressor has an external protector, check for continuity through the protector or protectors. All external and internal inherent protectors on Copelametic compressor can be replaced in the field. On larger compressors with thermostats, thermotectors, or solid state sensors in the motor windings; H,L,S protection (see Section D for compressor nomenclature), the internal protective devices cannot be replaced, and the compressor must be changed if the internal protectors are defective or damaged. IF THE COMPRESSOR STARTS BUT TRIPS REPEATEDLY ON THE OVERLOAD PROTECTOR 1. Check the compressor suction and discharge pressures while the compressor is operating. Be sure the refrigerant is compatible with the compressor and the temperature range is within the limitations of the compressor. If pressures are excessive, it may be necessary to clean the condenser, remove noncondensables from the system, add a crankcase pressure regulating valve, modify the system control, or take such other action as may be necessary to avoid excessive pressures. If the fan motor is three phase, make sure it is running in the right direction. An excessively low suction pressure may indicate a loss of charge, and a suction gas cooled compressor may not be getting enough refrigerant vapor across the motor for proper cooling. On units with no service gauge ports where pressures can’t be checked, check the condenser to be sure it is H5 clean and fan is running. Excessive temperatures on suction and discharge lines may also indicate abnormal operating conditions. 2. Check the line voltage at the motor terminals while the compressor is operating. The voltage should be within 10 percent of the nameplate voltage rating. If outside those limits, the voltage supply must be brought within the proper range, or a compressor with different electrical characteristics must be used. 3. Check the amperage drawn while the compressor is operating. The amperage drawn should be within ±10 percent of the published compressor curve data for the given pressures the compressor is operating under. High amperage can be caused by low voltage, high head pressure, high suction pressure, high oil level, mechanical compressor damage, defective run capacitors, or a defective starting relay. On three phase compressors, check amperage in each line. One or two high amperage legs on a three phase motor indicates an unbalanced voltage supply, or a winding imbalance, which can cause motor overheating. If all three legs are not drawing approximately equal amperage, temporarily switch the leads to the motor to determine if the high leg stays with the line or stays with the terminal. If the high amperage reading stays with the line, the problem is in the line voltage supply. If the high amperage reading stays with the terminal, the problem is in the motor. If the amperage is sufficiently unbalanced to cause a protector trip (approximately 10%) and the voltage supply is unbalanced, check with the power company to see if the condition can be corrected. If the voltage supply is balanced, indicating a defective motor phase, H6 the compressor should be replaced. 4. Check for a defective run capacitor or starting relay in the same manner described in the previous section. 5. Check for wiring against the wiring diagram in the terminal box. On dual voltage motors, check the location of the terminal jumper bars to be sure phases are properly connected. 6. Overheating of the cylinders and head can be caused by a leaking valve plate or relief valve. To check, front seat the suction service valve and briefly pump the compressor into a vacuum. Stop the compressor and open the suction valve to allow the pressure on the suction gauge to build up to 0 psig. Again, close the valve. If the pressure on the gauge continues to increase steadily, the valve plate or relief valve is leaking. Remove the head and check the valve plate. Replace if necessary. 7. If all operating conditions are normal, the voltage supply at the compressor terminals balanced and within limits, the compressor crank-case temperature within normal limits, the amperage drawn within the specified range, the motor protector may be defective and should be replaced. If the operating conditions are normal and the compressor is running excessively hot for no observable reason, or if the amperage drawn is above the normal range and sufficient to repeatedly trip the protector, the compressor has internal damage and should be replaced. H7 IF THE COMPRESSOR RUNS BUT WILL NOT REFRIGERATE 1. Check the refrigerant charge and the operating pressures. Any abnormal operating conditions must be corrected. 2. If the suction pressure is high and the evaporator and condenser are functioning normally, check the compressor amperage draw. An amperage draw within ±5 percent of published rating data, corrected for actual measured voltage, indicates normal compressor operation. An amperage draw considerably below the published rating data indicates a possible broken suction valve, discharge valve, broken connecting rod blown gasket, or worn rings in the compressor. Check the pistons and valve plate on an accessible compressor. If no other reason for lack of capacity and low amperage can be found, replace a welded compressor. An amperage draw considerably above published rating data for the given operating pressures indicates possible bearing damage, and the compressor should be replaced. Published compressor rating data for each model can be obtained by your Emerson Climate Technologies Wholesaler. H8 SECTION I IDENTIFYING COMPRESSOR FAILURES Most compressors fail due to system malfunctions which must be corrected to prevent repeat failures. After a compressor fails, field examination of the failed compressor often will reveal symptoms of system problems. Proper corrections will help eliminate future failures. Field examination does not affect warranty as long as all access plates and heads are reinstalled with all internal components put back inside the compressor. REFRIGERANT FLOODBACK This is a result of liquid refrigerant returning to the compressor during the running cycle. The oil is diluted with refrigerant to the point it cannot properly lubricate the load bearing surfaces. • Air Cooled Compressors • Worn pistons and cylinders • No evidence of overheating The liquid washes the oil off the pistons and cylinder walls during the suction stroke causing them to wear during the compression stroke. I2 • Refrigerant Cooled Compressors • Center and rear bearings worn or seized • Dragging rotor, shorted stator • Progressively scored crankshaft • Worn or broken rods The liquid dilutes the oil in the crankcase and the refrigerant rich oil will be pumped to the rods and the bearings through the crankshaft. As the refrigerant boils off, there will not be enough oil for sufficient lubrication at bearings furthest from the oil pump. The center and rear bearings may seize or may wear enough to allow the rotor to drop and drag on the stator causing a short. • Corrections 1. Maintain proper evaporator and compressor superheat. 2. Correct abnormal low load conditions. 3. Install accumulators to stop uncontrolled liquid return. I3 FLOODED STARTS • Worn or scored rods or bearings • Rods broken from seizure • Erratic wear of crankshaft This is the result of refrigerant migrating to the crankcase oil during the off cycle. When the compressor starts, the diluted oil cannot properly lubricate the load bearing surfaces causing an erratic wear or seizure pattern. • Corrections 1. Locate compressor in warm ambient or install pump down. 2. Check crankcase heater operation. SLUGGING • Broken reeds, rods, or crankshaft • Loose or broken backer bolts • Blown head gaskets This is the result of trying to compress liquid refrigerant and/or oil in the cylinders. Slugging is caused by floodback on air cooled compressors and severe flooded starts on refrigerant cooled compressors. • Corrections 1. Maintain proper evaporator and compressor superheat. 2. Correct abnormal low load conditions. 3. Install accumulators to stop uncontrolled liquid return. 4. Locate compressor in warm ambient or install pump down. I4 HIGH DISCHARGE TEMPERATURE • Discolored valve plate • Burned valve reeds • Worn pistons, rings, and cylinders • Stator spot burn from metal debris This is the result of temperatures in the compressor head and cylinders becoming so hot that the oil loses its ability to lubricate properly. This causes rings, pistons, and cylinders to wear resulting in blow by, leaking valves, and metal debris in the oil. • Corrections 1. Correct abnormal low load conditions. 2. Correct high discharge pressure conditions. 3. Insulate suction lines. 4. Provide proper compressor cooling. LOSS OF OIL • All rods and bearings worn or scored. • Crankshaft uniformly scored. • Rods broken from seizure. • Little or no oil in crankcase. This is a result of insufficient oil in the crankcase to properly lubricate the load bearing surfaces. When there is not enough refrigerant mass flow in the system to return oil to the compressor as fast as it is pumped out, there will be a uniform wearing or scoring of all load bearing surfaces. I5 • Corrections 1. Check oil failure control operation if applicable. 2. Check system refrigerant charge. 3. Correct abnormally low load conditions or short cycling. 4. Check for incorrect pipe sizes and/or oil traps. 5. Check for inadequate defrosts. ELECTRICAL Many motors fail as a result of mechanical failure. Others are true electrical failures. GENERAL OR UNIFORM BURN All windings are uniformly overheated or burned. • Corrections 1. Check for proper voltage. 2. Check for unbalanced voltage. 3. Check for inadequate motor cooling. I6 SINGLE PHASE BURN Two phases of a three phase motor are overheated or burned. This is the result of high current through two of the three phases. • Corrections 1. Replace contactors. 2. Check for proper motor protection. HALF WINDING SINGLE PHASE BURN Half of two phases of a three phase motor overheated or burned due to one contactor opening one of its contacts on a two contactor application. • Correction 1. Replace contactors. HALF WINDING BURN Half of all phases of a two contactor three phase motor are over heated or burned. • Corrections 1. Replace contactors 2. Check for feedback circuit holding one contactor closed I7 PRIMARY SINGLE PHASE BURN Only one phase of a three phase motor is overheated or burned as the result of opening one phase on the primary side of a delta to wye transformer. • Correction 1. Check primary side of a delta to wye mainpower transformer. START WINDING BURN Only the start winding of a single phase motor is uniformly overheated or burned. • Corrections 1. Check for proper wiring of compressor. 2. Check starting capacitor and/or starting relay. 3. Check compressor overloading. SPOT BURN A localized burn within a winding, between windings, or from windings to ground. • Corrections 1. If not the result of mechanical problems, check for spikes or surges of high current flow. I8 SHORTED TERMINALS A breakdown of the insulation between terminals and compressor body. • Correction 1. Check for over torquing of terminals. I9
Similar documents
Copeland™ compressor
implied, regarding the products or services described herein or their use or applicability. Emerson Climate Technologies, Inc. and/or its affiliates (collectively “Emerson”), as applicable, reserve...
More informationLiebert XDC Parts Manual
rack. Individual modules can improve enclosure airflow or cool hot spots, or zones. The modules in the Liebert XD system use a unique heat rejection process, using a pumped refrigerant. It operates...
More information