ECOFIT
Medium & Low Voltage Distribution
Modernisation of switchboards
Catalogue 2016
schneider-electric.com/electricaldistributionservices
™
Standard solutions
Index
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
1
Medium Voltage ECOFIT™ standard solutions
How to find an ECOFIT™ solution?
1
2
Select the " generic family ".
Original Brand
1
MV CB or
Contactor or
3
Select the " Panel type ".
MV Panel MV Cradle Panel type
2
3
Select the " Original device type ".
Original device type
New device type
Flyer SERED N°
Page
to Cradle
Disconnector
Square D
✓
5-15 kV MC switchgear
VAD2-3
Magnum CB
111036EN
A-2
✓
AHA
ECA
HVX-O2
111168EN
A-3
Other brand
✓
All with fixed CB
All fixed CB types
HVXUW
111102EN
A-4
Alsthom
✓
Alliance
FP - GFA
FP - GFA
111122EN
A-5
Merlin Gerin
✓
Belledonne B200-B400
DSE22 to DSE78
LF2 - LF3 - SF1 - Evolis
111009EN
A-6
Merlin Gerin
✓
Belledonne B200G
DSE22K-DSE23K
LF1 - Evolis
111010EN
A-7
Merlin Gerin
✓
Belledonne B650
DIS
LF1 - R400 - R400D - Evolis
111007EN
A-8
Merlin Gerin
✓
Belledonne B900
DIS
SF1
111008EN
A-9
✓
BVP 17
BVP 17
VMX
111060EN
A-10
CB
FP
111026EN
A-11
CS - CX - FPR
FPR
111028EN
A-12
AEG, Alsthom,
Alstom
AEI,
GEC Alsthom
CEM
✓
CEM
✓
Nuova Magrini
CemablocC23mc 15 & 27
CemablocC26.0
✓
Composit
MG
SF1
111048EN
A-13
✓
CSIM 1-12
SCI-4
VEIVACUUM F
111044EN
A-14
✓
CSIM 3-12
SCI-4
VEIVACUUM F - VA
111073EN
A-15
Alsthom
✓
DNF4-2E
FP - GFA
FP - HVX - CVX
111088EN
A-16
Alsthom
✓
DNF4 MI&FI
FP
FP - HVX
111089EN
A-17
Alsthom
✓
DNF5/DNF5-2B
FP
FP - HVX
111092EN
A-18
Alsthom
✓
DNF6
FP
FP - HVX
111093EN
A-19
Alsthom
✓
DNF7
FP
FP - HVX-O2
111090EN
A-20
✓
Epoclad
DHF -F
LF1 - LF2 - LF3 - SF1
111049EN
A-21
Merlin Gerin
✓
Fluair F100-F200
FG1 - FG2
LF2 - LF3 - Evolis
111012EN
A-22
Merlin Gerin
✓
Fluair F100C
R400-R400D
R400 - R400D
111013EN
A-23
Merlin Gerin
✓
Fluair F300
FG3
SF1 - SF2
111101EN
A-24
Merlin Gerin
✓
Fluair F400C
FC4
SF2
111014EN
A-25
Merlin Gerin
✓
Fluair F400G
FG4
SF1 - SF2
111015EN
A-26
✓
Fluokit M24
FP
FP
111138EN
A-27
✓
Fluokit M24 +
FP
FP
111141EN
A-28
✓
Fluokit M36
FP
FP
111136EN
A-29
✓
GS-10
111041EN
A-30
111061EN
A-31
Galileo
VEB
Otto Buchwitz
VEB
Otto Buchwitz
Nuova Magrini
Galileo
GEC, GEC
Alstom, Alstom
GEC, GEC
Alstom, Alstom
GEC, GEC
Alstom, Alstom
AEG
GE
VA - VAA
HMC 400 -
HMC 400 -
HMC 410
HMC 410
GEC Alstom
✓
HMC 400 & HMC 410
GEC Alstom
✓
HMC 1072
HMC 1072
HMC 1072
111062EN
A-32
GEC Alstom
✓
HMC 1172
HMC 1172
HMC 1172
111063EN
A-33
GEC Alstom
✓
HMX 36
HMX 36
HMX36
111064EN
A-34
✓
HP
HP-W-TW-TM
HVX
111078EN
A-35
✓
HWX
HWX
HWX
111166EN
A-36
Concordia
Sprecher
GEC, GEC
Alsthom, Alstom,
NEW
NEW
Areva
2
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
1
Original Brand
MV CB or
2
MV Panel MV Cradle Panel type
3
Original device type
New device type
Flyer SERED N°
Page
to Cradle
Contactor or
Disconnector
GOST standard
✓
K104
K104
LF1 - Evolis
111164EN
A-37
NEW
✓
KAD
KAD
VMX-540
111162EN
A-38
NEW
GOST standard
✓
KRU 2-10
KRU 2-10
LF1 - Evolis
111165EN
A-39
NEW
Merlin Gerin
✓
MC500
SF1T
SF1T
111156EN
A-40
NEW
Federal Pioneer
✓
Metalclad switchgear
DST 2 & 5
DST 2V & 5V
111067EN
A-41
Merlin Gerin
✓
Motorstart P50D
C - CD
R400 - R400D - CTV1
111005EN
A-42
GEC, GEC
Alsthom, Alstom
Merlin Gerin
✓
Motorstart P500D
C1 - CD1
R400 - R400D - CTV1
111006EN
A-43
GEC Alstom
✓
MX 51 & MX 81
MX 51 - MX 81
MX 51 - MX 81
111065EN
A-44
Delle Alsthom
✓
Normabloc N1347
HL
HVX - FPX
111033EN
A-45
✓
Normaclad PX
FPX
FPX
111139EN
A-46
✓
PX 12 - 24
FPX
FPX
111124EN
A-47
✓
PIX SF6
FPX
FPX
111137EN
A-48
✓
PNX 36
HVX 36
HVX 36
111127EN
A-49
VA - VAA - Contactor
111042EN
A-50
GEC, GEC
Alstom, Alstom
Alsthom
GEC, GEC
Alstom, Alstom
AEG
IMC - MC - FAL - IFAL - VA
AEG
R
✓
- VAA - IVA - BAL - ALF AL - TG
GOST standard
✓
RSW
RSW
LF1 - Evolis
111163EN
A-51
Ansaldo
✓
Siclad
MAG II
LF1 - LF2
111050EN
A-52
Square D
✓
DSE
Magnum CB
111037EN
A-53
Nuova Magrini
Solenarc DSE Metal-Clad
switchgear
✓
Venus
GI-GL
LF1-LF3
111051EN
A-54
✓
VISAX
BLV
BLV
111140EN
A-55
✓
VM6 DM12
FB4
SF1
111018EN
A-56
✓
VMX
VMX
VMX
111154EN
A-57
AEG
✓
WBA
VA - VAA - ECA - BAL - AL
VA - VAA - Contactor
111082EN
A-58
AEG
✓
WBB
VA - VAA - ECA - BAL - AL
VA - VAA - Contactor
111084EN
A-59
AEG
✓
WBD
VA - VAA - HVX
VA - VAA
111129EN
A-60
AEG
✓
WK (C/E/B/A)
VA - MC - BAL
VA - VAA - Contactor
111086EN
A-61
✓
YSF6
YSF6
YSF6 Evolis
111066EN
A-62
✓
AHA
AHA panel
AHA panel
111167EN
A-63
✓
DNF7
DNF7 panel
DNF7 panel
111100EN
A-64
Galileo
GEC, GEC
Alsthom, Alstom
Merlin Gerin
GEC, GEC
Alsthom, Alstom
Yorkshire
Switchgear
AEG, Alsthom,
Areva
Alsthom
Merlin Gerin
✓
F100/200
F100/200 panel
F100/200 panel
111071EN
A-65
Alstom
✓
PIX SF6
PIX SF6 panel
PIX SF6 panel
111157EN
A-66
Areva
✓
PNX36
PNX36 panel
PNX36 panel
111126EN
A-67
Alstom
✓
PX 12-24
PX 12-24 panel
PX 12-24 panel
111091EN
A-68
AEG
✓
R
R panel
R panel
111079EN
A-69
GEC Alstom
✓
VISAX
VISAX panel
VISAX panel
111123EN
A-70
✓
VMX
VMX panel
VMX panel
111097EN
A-71
AEG
✓
WBA
WBA panel
WBA panel
111081EN
A-72
AEG
✓
WBB
WBB panel
WBB panel
111083EN
A-73
AEG
✓
WBD
WBD panel
WBD panel
111128EN
A-74
AEG
✓
GEC, GEC
Alstom, Alstom
WK
WK panel
WK panel
111085EN
A-75
Other brand
✓
All
All breaker types
Evolis MC Cassette
111105EN
A-76
Other brand
✓
All
All breaker types
F400 Cassette
111106EN
A-77
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
NEW
NEW
NEW
3
Low Voltage ECOFIT™ standard solutions
How to find an ECOFIT™ solution?
1
2
Select the " generic family ".
Original Brand
1
LV CB or
LV Drawer
Select the " Panel type ".
Panel type
2
3
3
Select the " Original device type ".
Original device type
New device type
Flyer SERED N°
Page
Contactor
Nuova Magrini Galileo
✓
NA
B Control
Masterpact NW
111053EN
B-2
Merlin Gerin
✓
NA
Compact C801-C1251
Compact NS
111022EN
B-3
Merlin Gerin
✓
NA
DA
Masterpact NW
111019EN
B-4
Square D
✓
NA
DS
Masterpact NW
111038EN
B-5
Federal Pioneer
✓
NA
H series
Masterpact NT - NW
111068EN
B-6
Merlin Gerin
✓
NA
Masterpact M
Masterpact NW
111021EN
B-7
✓
NA
SE
Masterpact NW
111039EN
B-8
Merlin Gerin
✓
NA
Selpact
Masterpact NT - NW
111020EN
B-9
Unelec-Areva
✓
Normabloc 660
Unelec CNP
Masterpact NW
111023EN
B-10
Merlin Gerin
✓
NA
Visucompact CM
Masterpact NW
111024EN
B-11
Square D,
Westinghouse
Merlin Gerin
✓
T140
T140 drawers
T140 drawers
111094EN
B-13
Merlin Gerin
✓
MB400
MB400 drawers
MB400 drawers
111095EN
B-14
4
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
Protection relays ECOFIT™ standard solutions
How to find an ECOFIT™ solution?
1
2
Select the " generic family ".
1
Original Brand
Protection relay
GE
Select the " Panel type ".
2
3
Panel type
✓
3
Select the " Original device type ".
Original device type
New device type
Flyer SERED N°
Page
CO
MiCOM P111/115
111131EN
C-3
CDG - CAG - CTMM -
MiCOM P1x-P2x
CTMFM
or Vamp 5x
111147EN
C-4
Alstom
✓
ABB
✓
DPU 445
MiCOM P123
111134EN
C-5
ABB
✓
HCB
MiCOM P521
111133EN
C-6
GE
✓
IAC
MiCOM P122
111132EN
C-7
GEC Alstom, Areva
✓
All
KCGG 122 & 142
MiCOM P123R
111070EN
C-8
Areva or older
✓
all / draw out
MiCOM P120H
111104EN
C-9
Areva or older
✓
all / draw out
MiCOM P821MF
111103EN
C-10
Alstom
✓
MCGG 62
MiCOM P126
111135EN
C-11
Merlin Gerin
✓
All
Sepam 2000
Sepam 60/80
111087EN
C-12
Merlin Gerin
✓
RM6+
VIP
VIP + ECOFIT™ kit
111046EN
C-13
Merlin Gerin
✓
Various equipment
VIP & Vigirex
VIP & Sepam
111146EN
C-14
M range MCGG 11, 21 & 22
M range relay
MCTI 39-40
Substation automation ECOFIT™ standard solutions
How to find an ECOFIT™ solution?
1
2
Select the " generic family ".
Select the " Original device type ".
1.
Original Brand
2.
Control System
Original device type
New device type
Ref. ECOFIT™ centre
Flyer
Page
SERED N°
AREVA or older
✓
AREVA or older
✓
AREVA or older
✓
✓
Schneider
Electric
Bay Controler BM9x00
MiCOM C624
FR EAC Lattes*
111144EN
D-3
PACiS EcoSUI
FR EAC Lattes*
113543EN
D-4
PSCN3020 HMI
EcoSUI HMI
FR EAC Lattes*
113562EN
D-5
Seefox HMI
EcoSUI HMI
FR EAC Lattes*
111143EN
D-6
PACIS OI
(V3.x up to V4.6)
* Not current ECOFIT™ reference centre
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
5
6
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
Customised solutions
Index
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
7
Medium Voltage ECOFIT™ customised solutions
Those solutions have been manufactured and installed all over the world to answer specific customer request.
Schneider Electric can help you to identify the right solution to modernise your installation, with a site visit if required.
Original Brand
ABB
ABB
ABB
ABB
ABB
ABB
ABB
ABB
ABB
ABB
ABB
ABB
ABB
ABB
ABB
ABB
ABB
ABB
AEG
AEG
AEG
AEG
ALIND
Allis-Chalmers & Siemens-Allis
Allis-Chalmers & Siemens-Allis
Allis-Chalmers & Siemens-Allis
Allis-Chalmers & Siemens-Allis
Allis-Chalmers & Siemens-Allis
ALSTHOM
ALSTHOM
ALSTOM
ALSTOM
ALSTOM
ALSTOM / AREVA / Schneider Electric
ALSTOM / AREVA / Schneider Electric
ASEA
CGL
Calor Emag
Calor Emag
CONCORDIA SPRECHER
CONCORDIA SPRECHER
CONCORDIA SPRECHER
CONCORDIA SPRECHER
CONCORDIA SPRECHER
DELLE
DELLE
DELLE
DELLE
DELLE
DELLE
DELLE
DELLE
DELLE
DELLE
DELLE
DELLE
DELLE
DELLE
DELLE
DELLE
EIB
Federal Pacific
Federal Pacific
FUJI
GEC
General Electric
General Electric
General Electric
General Electric
General Electric
General Electric
General Electric
General Electric
General Electric
ITE
8
Panel type
AIS
AIS
AIS
AIS
AIS
AIS
VHE800
VHE800
VHE950
AIS
AIS
AIS
AIS
AIS
AIS
AIS
VHA-12S
HA3zc
FKCM4/24-2
FKCM5/12-2
FKEM4/24-2/721
FKEM4/24-2/723
AIS
AIS
AIS
AIS
AIS
AIS
NORMABLOC-DNL4
WBS
GMA Version 1
NORMAFLUOR-DNF4
AHA
Fluokit-M9
Fluokit-M9
VHE-800
AIS
AIS
AIS
PIC-106
PID 104/105/106
SC - SD 204/206
SCC 204/206
SCD 204
NORMABLOC-DN6S
NORMABLOC-DN6S
NORMABLOC-DNL4
NORMABLOC-DNTL
NORMABLOC-DNTC
NORMABLOC-DNTG
NORMABLOC-N142
NORMABLOC-N143
NORMABLOC-N340
NORMABLOC-N342
NORMABLOC-N1147
NORMABLOC-ND3
NORMABLOC-ND5
NORMASEPT-N740
NORMASEPT-N1742
FLUOMATIC-N962
Modulec CT 17.5
AIS
AIS
HF55
BVX
AIS
AIS
AIS
AIS
AIS
AIS
AIS
AIS
AIS
AIS
Original device type
E7512/10
EKU5012/10
EKU5016/10
EKU5025/10
GR256
HB12-12-40
HKK12/1226
HKK12/1240
HKK12/3140
JVE301
MS 2
MS 3
MT1
MT2
OD1M
S F ASG
VRC
GCB
VA/VAA/LTRI/AL
VA/VAA/LTRI/AL
VA/VAA/LTRI/AL
VA/VAA/LTRI/AL
HL430
FA
MA
FB
FC, MC
FC
HL
VB6
GMA
FP
ECA
VBL
DPIL
HKK
SFG-40S
OD3
OD4
HP
HP
HVTW(z)
HPCTW
HPDTW
HG
HL
HK & HL
HL
CHT
HL
RA
HK
FJ
RA
HL
HG or HK or HL
HG
HL
RA
SFC
A
DST-DST2
DST-DST2
OCB
KAD
AM
AM
AM
AM
AM-7.2
AM-13.8 Tall-Boy
AM-4.16
AMH
AMH-4.76
5-HV
Un (kV)
10
10
10
10
12
24
12
12
12
12
12
12
12
12
12
12-16
7,2
12
24kV
12kV
24kV
24kV
12
4,16
4,16
7,2 &13,8
13,8
13,8
12
24
12
17,5
up to 17,5
12-17,5
12-17,5
12
7,2
12
12
12-24
12-24
12-24
12-24
12-24
24
24
12
12
7,2
7,2
17,5
17,5
23
23
12
7,2
17,5
24
24
7,2
12 to 24
4,16
13,8
7.2
12
4,16
4,16
7,2
13,8
7,2
13,8
4,16
4,76
4,76
4,16
In (A)
1250
1250
1600
2500
630
1600
1250
1250
2500
400
1250
1600
1250
1250
400
1250 to 2500
400
630 to 2500
up to 1250
up to 1250
up to 1250
up to 1250
1250
3000
1200, 2000
1200, 2000
1200, 2000, 3000
1200, 2000
2500
1250A
2000
2500
1250
630-1250
630-1250
1600
1250
630 to 1250
630 to 1250
up to 1600
up to 1600
up to 1600
up to 1600
up to 1600
2500
1250
2500
1250
200
3200
400
630
400
200
1250
1250
1250
400
200
400
630 - 1250
1200, 2000,3000
1200, 2000
600A
400 to 1250
400
1200, 2000,3000
1200, 2000, 3000
1200, 2000
1200, 2000, 3000
3000
600, 1200
1200, 2000
1200, 2000
1200, 2000
Isc (kA)
40
50
50
50
13,1
25
26,3
40
40
40
40
40
26,3
26,3
26,3
26-40
25
40
up to 25
up to 25
up to 25
up to 25
40
41
40 & 50
18
18 - 28
37
40
25KA
25
25
31,5
up to 25
up to 25
40
31,5
31.5
31.5
up to 25
up to 25
up to 25
up to 25
up to 25
25
25
40
40
25
40
25
16
12,5
12,5
40
12,5
12,5
14,5
16
12,5
up to 25
29-41
18-28
25KA
up to 20
Fused
40
33
18 up to 37
33
37
20
29
29
29 to 40
New device type
HWX
HWX
HWX
HWX
HWX
Evolis
HWX
HWX
HWX
HWX
HWX
HWX
HWX
HWX
HWX
HWX
LF
LF
VA/VAA
VA/VAA
VA/VAA
VA/VAA
HWX
Magnum
Magnum
Magnum
Magnum
Magnum
FPX
HVX-O2
GMA Version 2
HVX
HVXO²
Evolis or SF1
SFset
Evolis
Rollarc
Evolis
Evolis
HVX
HVX
HVX
HVX
HVX
FP
FP
HVX
FPX
GFA
FP
GFA or FP
FP
FP
FP
FPX
FP
FP
FP
FP
GFA
SF/HVX
Magnum
Magnum
Evolis
VMX
Magnum
Magnum
Magnum
Magnum
Magnum
Magnum
Magnum
Magnum
Magnum
Magnum
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
Medium Voltage ECOFIT™ customised solutions
Those solutions have been manufactured and installed all over the world to answer specific customer request.
Schneider Electric technician will require a visit to customer premises to validate the solution.
Original Brand
ITE / ABB
ITE / ABB
ITE / ABB
JYOTI
LG
McGraw
McGraw
Merlin Gerin
Merlin Gerin / Lorenzetti Inebrasa
Merlin Gerin / Lorenzetti Inebrasa
Merlin Gerin / Lorenzetti Inebrasa
Merlin Gerin / Lorenzetti Inebrasa
Merlin Gerin / Lorenzetti Inebrasa
Mitsubishi
Mitsubishi
NGEF
NGEF
NGEF
NGEF
NGEF
NGEF
NGEF
NGEF
NGEF
NGEF
NISSIN
NMG
SACE
SIEMENS
SIEMENS
SIEMENS
SIEMENS
SIEMENS
SIEMENS
Square D
Square D
Square D
Square D
Square D
Square D
Square D
Square D
Square D
VOLTAS
VOLTAS
VOLTAS
VOLTAS
VOLTAS
VOLTAS
VOLTAS
VOLTAS
VOLTAS
VOLTAS
VOLTAS
VOLTAS
VOLTAS
VOLTAS
VOLTAS
VOLTAS
VOLTAS
VOLTAS
Westinghouse
Westinghouse
Westinghouse
Westinghouse
Westinghouse
Westinghouse
Westinghouse
Westinghouse
Westinghouse
Westinghouse
Westinghouse
Westinghouse
Westinghouse
Westinghouse
Panel type
AIS
AIS
AIS
AIS
AIS
AIS
AIS
V23-60
Flurin
Lorin
Flurin
CCM III
CCM II
AIS
AIS
AIS
AIS
AIS
AIS
AIS
AIS
AIS
AIS
AIS
AIS
AIS
AIS
AIS
8BD1
8BD1
AIS
AIS
8BD1
8BD1
AIS
AIS
AIS
AIS
AIS
AIS
AIS
AIS
AIS
AIS
AIS
AIS
AIS
AIS
AIS
AIS
AIS
AIS
AIS
AIS
AIS
AIS
AIS
AIS
AIS
AIS
AIS
AIS
AIS
AIS
AIS
AIS
AIS
AIS
AIS
AIS
AIS
AIS
AIS
AIS
AIS
Original device type
5-HK
7.5-HK
15-HK
MT2-1208-20
GVB
PSD
WSA
DIS23-D3
FG1
FG1, FG2
FG2
VC TOYO
C1
VF/ FM
6 DHE 32 M
E7512
E7525
EKU5012
EKU5016
EKU5025
EKU5025
EKU5025/10
EKU-GR256
EKU 5012/10
GR256
VSR
10 MG 500
D6
3AC
3AC
H512/H515
3TL / 1BF
3AC
CB
DSE
DSE23
DSE25
DSE-65
DSE-68
VAD2
VAD2
VAD3
VAD3
BMTT
BE
BEC
BMTT
FB4
FB4
FB4 Kiosk
FG2
FG2
FG2
FG2
FG2
FP
GHM
HF
HKK
HKO
HL
50-DH
75-DH
150-DH
150-DH
50-DH
50-DHP
75-DHP
75-DHP
150-DHP
150-DHP
5WYB
8WYB
15WYB
15WYB
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
Un (kV)
4,16
7,2
13,8
12
7.2
13,8
13,8
24kV
17,5
17,5
17,5
7.2
7,2
12
4.76
12
12
12
12
7,2
12
10
12
6.6
12
7.2
7.2
17,5
7,2
12
12
7.2
7.2
7.2
4,16
4,16
4,16
13,8
13,8
4,16
13,8
4,16
13,8
12
12
12
12
24
36
22
12
7,2
7,2
12
12
12
12
12
12
12
12
4,16
7,2
13,8
13,8
4,16
4,16
7,2
7,2
13,8
13,8
4,16
7,2
13,8
13,8
In (A)
1200, 2000, 3000
1200, 2000
1200, 2000, 3000
1250
630
1200, 2000
1200, 2000
630A
1250
1250
1250
400
400
1250A
1200 to 2000
1600
1250
2500
2500
2500
1250
2500
1250
1250A
1250
400A
630A
1250
630
1250 to 2500
1250
450
630 to 2000
630 to 2000
1200
2000
3000
1200
3000
1200
1200, 3000
1200, 2000
1200, 2000
1250
1250
1250
1250
2000
1250
630
1250
2000,2500,3150
1250
1250
1250
1250
1250
1250
1250
1250
1250
1200, 2000
1200, 2000
1200, 2000
1200, 2000, 3000
1200, 2000
1200, 2000, 3000
1200, 2000, 3000
320
1200, 2000
3000
1200, 2000, 3000
1200, 2000, 3000
1200, 2000
3000
Isc (kA)
40 to 50
33
18 to 37
25
31.5
18
18
25
25
25
25
50
50
31.5
29
25
40
40
40
40
40
50
31,5
30.6
31,5
4
25
25
40
40
31,5
6
25
40
29
29
41
up to 28
37
up to 41
37
up to 41
up to 28
26,3
40
40
40
25
25
25
40
40
31,5/ 40
40
40
40
40
40
40
40
40
29 / 41
33
18 / 28
37
29 / 41
41
33
Fused
18 / 28
33
41
33
18 / 28
33
New device type
Magnum
Magnum
Magnum
Evolis
Evolis
Magnum
Magnum
SF
LF
LF
LF
Rollarc
Rollarc
Evolis
LF
Evolis
Evolis
Evolis
Evolis
Evolis
Evolis
Evolis
Evolis
Evolis
Evolis
CTV
LF
LF
Evolis
HWX
Evolis
CVX
Evolis
Evolis
Magnum
Magnum
Magnum
Magnum
Magnum
Magnum
Magnum
Magnum
Magnum
HWX
HWX
HWX
HWX
Evolis
SF
Evolis
Evolis or LF
Evolis or LF
Evolis or LF
Evolis or LF
HWX
HWX
Evolis
Evolis
HWX
HWX
Evolis
Magnum
Magnum
Magnum
Magnum
Magnum
Magnum
Magnum
Magnum
Magnum
Magnum
Magnum
Magnum
Magnum
Magnum
9
Low Voltage ECOFIT™ customised solutions
Those solutions have been manufactured and installed all over the world to answer specific customer request.
Schneider Electric technician will require a visit to customer premises to validate the solution.
Original Brand
Range
Original device type
In (A)
New device type
Allis Chalmers
LA-600 / LA-800
LASB1-D2
800
Masterpact NT
Allis Chalmers
LAF-600 / LAF-800
LASB2-D2
800
Masterpact NT
Allis Chalmers
LAF-800
LASB2
800
Masterpact NT
Allis Chalmers
LA-1600
LASB3
1600
Masterpact NW
ASEA/ABB
VMG
ALG08
800
Masterpact NT
ASEA/ABB
VMG
ALG12
1250
Masterpact NT
ASEA/ABB
VMG
ALG16
1600
Masterpact NT
ASEA/ABB
VMG
ALG20
2000
Masterpact NW
ASEA/ABB
VMG
ALG25
2500
Masterpact NW
ASEA/ABB
VMG
ALG32
3200
Masterpact NW
Federal Pacific
FM-600 Fused
LFSB9
600
Masterpact NW
Federal Pacific
FM-1600 Fused
LFSB8
1600
Masterpact NW
Federal Pacific
FP-25 / FPS-25
LFSB4
800
Masterpact NT
Federal Pacific
FPS-30
LFSB7
800
Masterpact NW
Federal Pacific
FP-50
LSFB5
1600
Masterpact NW
Federal Pacific
FP-50-H3, 14" Frame (IEC)
SE Can
800
Masterpact NT
Federal Pacific
FP-50-H3, 21" Frame (ANSI)
SE Can
800
Masterpact NW
Federal Pacific
FP-50-H3, 21" Frame (IEC & ANSI)
SE Can
2000
Masterpact NW
Federal Pacific
FP-75
LFSB6
3200
Masterpact NW
Federal Pioneer
25HL-2
SE Can
800
Masterpact NT
Federal Pioneer
25HL-2
SE Can
600
Masterpact NT
Federal Pioneer
35HL-2
LFSB1
800
Masterpact NW
Federal Pioneer
50HL-2
SE Can
1600
Masterpact NW
Federal Pioneer
65HL-2
SE Can
2000
Masterpact NW
Federal Pioneer
75HL-2
SE Can
3000
Masterpact NW
General Electric
AE-1B (M.O.)
LGSB18
800
Masterpact NT
General Electric
AK-(1/2/3/4/5)-15/25
LGSB6
800
Masterpact NT
General Electric
AK-(2A/3A/4A/5A)-15/25
LGSB1/7/11
800
Masterpact NT
General Electric
AK-(1/2/3/4/5)-50
LGSB10
1600
Masterpact NW
General Electric
AK-(2A/3A/4A/5A)-50
LGSB4
1600
Masterpact NW
General Electric
AKR-30 (AKD-6 swgr)
LGSB2D
800
Masterpact NW
General Electric
AKR-30 (AKD-6 swgr)
LGSB13
800
Masterpact NT
General Electric
AKR-30 DC
LGSB5
800
Masterpact NW
General Electric
AKR-30 (Powell swgr)
LGSB8
800
Masterpact NT
General Electric
AKR/AKRT-30 (AKD-8 swgr)
LGSB2C
800
Masterpact NW
General Electric
AKR with Contactor
LGSC2
540
Masterpact
General Electric
AKRU-30 (1 Position)
LGSB14
800
Masterpact NW
General Electric
AKR-50 (AKD-6 swgr)
LGSB2
1600
Masterpact NW
General Electric
AKR/AKRT-50 (AKD-8 swgr)
LGSB2C
1600 - 2000
Masterpact NW
General Electric
AKR-50 (Powell swgr)
LGSB9/9A
2000
Masterpact NW
General Electric
AKR-50 DC (Hatch swgr)
LGSB22
2000
Masterpact NW
General Electric
AKRU-50 (1 Position)
LGSB17
1600
Masterpact NW
General Electric
AKR-75 (3 Pos./Ver. Bus)
LGSB12
3200
Masterpact NW
General Electric
AL-2-50 (M.O.)
LGSB19
1600
Masterpact NW
ITE / ABB / BBC
K-225
LISB9
225
Masterpact NT
ITE / ABB / BBC
K-600 / K-800
LISBA1
800
Masterpact NT
ITE / ABB / BBC
K-600 / K-800 with MOC/TOC
LISB8
800
Masterpact NT
ITE / ABB / BBC
K-Don 600/800
LISB11
800
Masterpact NT
ITE / ABB / BBC
K-Don 1600
LISB12
1600
Masterpact NW
ITE / ABB / BBC
K-1600 / K-1600S
LISB2
1600
Masterpact NW
ITE / ABB / BBC
K-2000 / K-2000S with TOC
LISB5
2000
Masterpact NW
ITE / ABB / BBC
KB
LISB3
600
Masterpact NT
ITE / ABB / BBC
KC
LISB4
1600
Masterpact NW
ITE / ABB / BBC
MB-8 / MBE-8
LBSB1
800
Masterpact NT
ITE / ABB / BBC
MB-16 / MBE-16
LBSB2
1600
Masterpact NW
ITE / ABB / BBC
LKE-8
LISB6
800
Masterpact NT
KAFAK
KAFAK
SFBY
250
Compact NSX
KAFAK
KAFAK
SFBY
630
Compact NSX
Merlin Gerin
Compact CM
CM 1250 3P Fixed Front
1250
Compact NS
Merlin Gerin
Compact CM
CM 1600 4P HH Fixed
1600
Masterpact NW
Merlin Gerin
Interpact IN
IN2500A 3P Fixed
2500
Interpact INS
10
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
Low Voltage ECOFIT™ customised solutions
Those solutions have been manufactured and installed all over the world to answer specific customer request.
Schneider Electric technician will require a visit to customer premises to validate the solution.
Original Brand
Range
Original device type
In (A)
New device type
Siemens
SBS
1200
1200
Masterpact NT
Siemens
SBS
800
800
Masterpact NT
Square D
MP-08 / MP-16
LSSB2
800 - 1600
Masterpact NW
Square D
MP-20
LSSB3
2000
Masterpact NW
Square D
MP-25 / MP-30
LSSB4
2500 - 3000
Masterpact NW
Square D
SED
LSSB1
800 - 3000
Masterpact NW
Square D
SEM (SED-M)
LSS5B
800 - 2000
Masterpact NW
Square D
DS-206
LWSB7
800
Masterpact NT
Square D
DS-206H
LWSB9
800
Masterpact NW
Square D
DS-206E
LWSB9
800
Masterpact NW
Square D
DS-416
LWSB9
1600
Masterpact NW
Square D
DS-416S
LWSB9
1600
Masterpact NW
Square D
DS-416H
LWSB9
1600
Masterpact NW
Square D
DS-420
LWSB9
2000
Masterpact NW
Square D
DSII-308
LWSB8
800
Masterpact NW
Square D
DSII-508
LWSB8
800
Masterpact NW
Square D
DSII-608
LWSB8
800
Masterpact NW
Square D
DSII-516
LWSB8
1600
Masterpact NW
Square D
DSII-616
LWSB8
1600
Masterpact NW
Square D
DSII-620
LWSB8
2000
Masterpact NW
Westinghouse / Cutler Hammer / Eaton
DB-15 Three Position (in DB-25 cell)
LWSB6
225
Masterpact NT
Westinghouse / Cutler Hammer / Eaton
DB-25 Three Position
LWSB1
800
Masterpact NT
Westinghouse / Cutler Hammer / Eaton
DB-25 Single Position
LWSB5
800
Masterpact NT
Westinghouse / Cutler Hammer / Eaton
DBL-25 Three Position
LWSB2
800
Masterpact NT
Westinghouse / Cutler Hammer / Eaton
DB-50 Single Position
LWSB4
1600
Masterpact NW
Westinghouse / Cutler Hammer / Eaton
DB-50 Three Position
LWSB3
1600
Masterpact NW
Westinghouse / Cutler Hammer / Eaton
DS-206
LWSB7
800
Masterpact NT
Westinghouse / Cutler Hammer / Eaton
DS-206H
LWSB9
800
Masterpact NW
Westinghouse / Cutler Hammer / Eaton
DS-206E
LWSB9
800
Masterpact NW
Westinghouse / Cutler Hammer / Eaton
DS-416
LWSB9
1600
Masterpact NW
Westinghouse / Cutler Hammer / Eaton
DS-416S
LWSB9
1600
Masterpact NW
Westinghouse / Cutler Hammer / Eaton
DS-416H
LWSB9
1600
Masterpact NW
Westinghouse / Cutler Hammer / Eaton
DS-420
LWSB9
2000
Masterpact NW
Westinghouse / Cutler Hammer / Eaton
DSII-308
LWSB8
800
Masterpact NW
Westinghouse / Cutler Hammer / Eaton
DSII-508
LWSB8
800
Masterpact NW
Westinghouse / Cutler Hammer / Eaton
DSII-608
LWSB8
800
Masterpact NW
Westinghouse / Cutler Hammer / Eaton
DSII-516
LWSB8
1600
Masterpact NW
Westinghouse / Cutler Hammer / Eaton
DSII-616
LWSB8
1600
Masterpact NW
Westinghouse / Cutler Hammer / Eaton
DSII-620
LWSB8
2000
Masterpact NW
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
11
Contents
12
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
ECOFITTM
Contents
Medium Voltage Distribution
A-1
Low Voltage Distribution
B-1
Protection relays
C-1
Substation automation
D-1
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
13
ew
n
e
R
How do I
operate and
maintain?
Op
e ra
How do I
install and
commission?
a ll
How do I
optimize?
st
Asset
Management
Life Cycle
In
Optimize
What are
my options?
n
Pla
How do I
renew my
solution?
te
What does
Renew mean?
14
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
Schneider Electric is helping
you to get the most of your
equipment and installations
Schneider Electric helps you define and implement
the best solution evolvement, increasing performance
and flexibility, while controlling aging infrastructures
associated costs.
Keeping Masterpact M original craddle
Adapted Masterpact NW
Masterpact M
ECOFITTM is the economical complement
to maintenance operations
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
15
For
which benefits?
16
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
There are two main possibilities
when considering modernization
The first one
would be to completely replace existing electrical installation with new equipments.
This solution might not be the most cost effective.
The second option
would be to replace only active components, while leaving switchgear structure
intact. Retrofit or retrofitting is the general term that is used to define this process.
Several different retrofit solutions exist for adapting modern circuit breakers into
existing switchgear.
COSTS
2 to 6 days
From few minutes to 1 hour
New equipment
Retrofit
Cost of process downtime
Material cost
Site work cost
A retrofit approach offers cost advantages in three important areas:
•materials,
•lost production time,
•site preparation.
• Enhances your process dependability.
• Optimizes your maintenance service costs & limits your investments.
• Maintains compliance with evolving industry standards and legislation.
• Ensures the safety of your personnel and surrounding equipment by using the latest technology.
• Access to Energy Management.
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
17
Modernization
solutions
18
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
The main advantages of
implementing a retrofit solution
Optimisation of assets
The life of existing electrical equipment is extended thereby increasing the return on
investment.
Reduced production stoppage
A retrofit full panel replacement will take anywhere from only a few minutes
to one hour. When considering whether to maintain equipment or replace it,
facility managers must take into account the initial capital cost, along with potential
disruption to the facility’s processes and workflow during the course of changing out
the equipment. Unless process loads can be rerouted temporarily during
the demolition of old equipment and installation of the new switchgear, the cost
of lost production can be substantial.
Improved cash flow
A full retrofit of an industrial site could spread over several years. Oftentimes,
when new equipment is purchased, the on-site physical plant also needs
to be modified to accommodate the new equipment, which adds to the cost.
Reduced risk
Installing new switchgear involves more cabling (requires that existing cabling
above and below the equipment be moved). In some cases, cabling may need
to be replaced or spliced, which introduces a higher element of risk.
Peace of Mind
Pre-tested solutions from established manufacturers provide a high degree
confidence in a retrofit solution. Established players like Schneider Electric have
managed thousands of switchgear retrofit projects and have an extensive library
of lessons learned. Qualified personnel and up-to-date tools reduce the risk
of accidents and delays. Accompanying safety improvements and updated
warranties also contribute to overall power network peace of mind.
Digitization
Retrofit solutions also open the door to enhanced equipment connectivity.
This then allows access to more detailed levels of energy management date which
enables better monitoring of energy consumption.
Less environmental impact
Since a retrofit solution replaces only a portion of the existing electrical equipment,
fewer waste materials need to be processed than if a complete replacement
were to occur.
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
19
Why modernize?
20
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
Electrical Distribution equipment
obsolescence and limited
availability of spare parts
The only solution to extend Electrical Distribution (ED)
equipment life cycle is by carrying out an intense
maintenance while planning a modernisation solution
thanks to ECOFIT solution.
There are three major phases in the product life cycle:
1. Commercialisation period:
The product is launched onto the market and is included in the Schneider Electric
catalogue.
2. Full spare parts availability period:
The product is withdrawn from the market. Schneider Electric continues
to supply spare parts for a period of time. Generally speaking, the average full
spare part supply period after the end of
commercialisation is :
• Medium Voltage equipment: 12 years.
• Low Voltage equipment: 10 years.
When the end of the full spare part supply date is reached, the product
is considered as at the end of its life.
Maintennance costs
3. Modernisation period with ECOFIT™ solution:
When spare parts are no longer readily available, the continuity of service
and support is at risk. If a device breaks down, no parts may be available to fix it.
At this stage, launching ECOFIT solution is recommanded.
Corrective, Preventive Maintenance
and spare parts guaranteed
Modernisation
Installation
& commissioning
End of
commercialisation
End of full
spare parts
availability
End of
spare parts
Product life
End of
Services
ECOFIT™ spare parts
Schneider Electric provides spare parts or subassembly replacement associated
to supplied ECOFIT equipments in order to ensure continuity of service.
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
21
ECOFIT
reference
centers
™
22
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
Our main legacies and
ECOFIT™ reference centers
brand responsibilities
BRAND
FRANCE
Grenoble
FRANCE
Mâcon
GERMANY
Regensburg
UK
Warrington
USA
West Chester
ITALY
Stezzano*
CANADA
Toronto*
✓
✓
AREVA
✓
✓
ALSTOM
✓
✓
CEM
✓
DELLE
✓
AEG
✓
Sprecher +
Schuh
✓
Concordia
Sprecher
✓
VEM
✓
GEC
✓
✓
✓
GEC
ALSTHOM
✓
✓
AEI
✓
✓
✓
✓
✓
✓
Competitors**
✓
✓
✓
✓
✓
✓
✓
* Not current ECOFIT™ reference centre
** ABB, Ansaldo, General Electric, Otto Buchwitz, VEB, Westinghouse, Siemens...
ECOFIT™ Reference Centers are in charge of
• Design and development of ECOFIT™ offers using Schneider Offer Creation
Process methodology.
• Industrialise, manufacture and optimise ECOFIT™ offers to answer
the customers’ requests with optimum conditions.
• Test, validation and certification of ECOFIT™ offers using a standard quality
directive procedure linked to international standards.
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
23
EOL, the
complementary
offer
24
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
End-of-life:
environment in mind!
98%
of a medium-voltage cubicle
can be recovered.
A legal requirement
for the SF6,
an environmental duty.
In complement to ECOFIT™, EOL our high
environmental treatment package: recovery and
recycling for re-use of all medium-voltage equipment,
including SF6 gas.
EOL's 4 steps
1.
Collection of medium-voltage equipment from your site.
2.
Dismantling of the equipment in a Schneider Electric factory.
The different ferrous and non-ferrous materials (copper, aluminium, etc.) are
separated and sent to specialised recycling centres.
3.
When applicable, the SF6 is evacuated until the residual pressure is less
than 20 mbar, in accordance with the IEC standard, using adequate engineered
tools. The gas is stored in bottles before being sent for recycling.
The epoxy enclosure is crushed for recovery purposes.
4.
A certificate of destruction compliant with the regulations is sent to you.
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
25
Schneider
Electric
know-how
26
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
Benefit from Schneider Electric
image and know-how
Our common values
Schneider Electric’s policy has always been to
provide its customers with very close support in their
daily activities to enable them to achieve operational
excellence.
•Quality
•Safety
•Professionalism
The experience of a world leader in Low & Medium Voltage
Local support all over the worl. There are always
Schneider Electric people close to you:
A long history of innovation for a global offer
6200
Based on this experience as world leader, Schneider Electric has developed a large
and comprehensive range of innovative devices.
With one of the world leaders, you take benefit of a global leader experience and
know-how in electric distribution, automation and Power & Control.
services people in more than
88
Schneider Electric has been manufacturing LV and MV products for more than 50
years and its installed base amounts to thousand millions products and devices.
The Schneider Electric brand is known worldwide and recognized
by the most demanding customers.
All the devices included in this overview have been designed and manufactured to
incorporate the benefits of this extensive experience.
Schneider Electric, a brand you can trust
countries
5%
of sales devoted to R&D
More than
60,000
ECOFIT™ in services/delivered in various business segments
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
27
Medium Voltage
Distribution
Medium Voltage Distribution
Contents
MV CB or Contactor or Disconnector
5-15 kV MC switchgear
AHA
All with fixed CB
Alliance
Belledonne B200-B400
Belledonne B200G
Belledonne B650
Belledonne B900
BVP 17
Cemabloc-C23mc 15 & 27
Cemabloc-C26.0
Composit
CSIM 1-12
CSIM 3-12
DNF4-2E
DNF4 MI&FI
DNF5/DNF5-2B
DNF6
DNF7
Epoclad
Fluair F100-F200
Fluair F100C
Fluair F300
Fluair F400C
Fluair F400G
Fluokit M24
Fluokit M24+
Fluokit M36
GS-10
HMC 400 & HMC 410
HMC 1072
HMC 1172
HMX 36
HP
HWX
K104
KAD
KRU 2-10
MC500
Metalclad switchgear
Motorstart P50D
Motorstart P500D
MX 51 & MX 81
Normabloc N1347
Normaclad PX
PIX 12 - 24
PIX SF6
PNX 36
R
RSW
Siclad
Solenarc DSE Metal-Clad switchgear
Venus
VISAX
VM6 DM12
VMX
WBA
WBB
WBD
WK
YSF6
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
MV Panel
A-2
A-3
A-4
A-5
A-6
A-7
A-8
A-9
A-10
A-11
A-12
A-13
A-14
A-15
A-16
A-17
A-18
A-19
A-20
A-21
A-22
A-23
A-24
A-25
A-26
A-27
A-28
A-29
A-30
A-31
A-32
A-33
A-34
A-35
A-36
A-37
A-38
A-39
A-40
A-41
A-42
A-43
A-44
A-45
A-46
A-47
A-48
A-49
A-50
A-51
A-52
A-53
A-54
A-55
A-56
A-57
A-58
A-59
A-60
A-61
A-62
AHA
DNF7
F100/200
PIX
PNX36
PX 12-24
R
VISAX
VMX
WBA
WBB
WBD
WK
A-63
A-64
A-65
A-66
A-67
A-68
A-69
A-70
A-71
A-72
A-73
A-74
A-75
MV Cradle to Cradle
All
All
A-76
A-77
A-1
Medium Voltage Distribution
5 - 15 kV MC switchgear / VAD2 - 3 by MAGNUM
Square D
ECOFIT™ proposal
PE90543
PE90542
Original brand:
With ECOFIT™, a true extended life time
< 1985
1995
2004
2006
VAD2-3
Magnum
ECOFIT™ solution
VAD2-3
Circuit Breaker
End of commercialisation
End of spare parts
PE90544
Commercialisation
Main technical characteristics
Rated current (Ir)
Short circuit current (Isc)
Rated voltage Un (50/60 Hz)
Magnum
Circuit Breaker
Magnum 5SSB
VAD2
VAD3
VAD2
VAD3
1200 - 3000 A
29 kA
5 kV
41 kA
18 - 28 kA
15 kV
37 kA
Magnum 5SSB
Magnum 15SSB
Magnum 15SSB
Technology
Vacuum
Vacuum
Rated current Ir (A)
1200 - 3000
1200 - 3000
Rated voltage Ur (kV)
5
15
Short circuit current Isc (kA)
29 - 41
18 - 28
Surge withstand voltage Up (kV) 60
95
Switching sequence
O-0.3 s-CO-15 s-CO
O-0.3 s-CO-15 s-CO
Nominal frequency (Hz)
60
Opening time (ms)
60
60
60
Magnum CB main characteristics
Built with totally new components and tested to ANSI standards, Magnum circuit breakers correctly interface with
the existing breaker compartment components and maintain safety interlocks inherent in the original equipment
design.
•New circuit breakers are installed in existing switchgear.
•Original footprint is left intact, saving time and money.
•Installation expense is a fraction of new equipment costs.
--Less down time for installation.
--Enhanced equipment reliability.
• Manufactured with new components.
• Undergoes complete factory testing.
• Backed by our standard equipment warranty.
• New, easy-to-maintain operating mechanism.
• No bulky arc chutes to handle and maintain.
• Reduced need for difficult to obtain spare parts.
Offer extension
PE90437
PE90542
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
Sepam series 10, 20, 40, 60 , 80
PE90488
or
A-2
MICOMP series 10, 20, 30, 40
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
Medium Voltage Distribution
AHA / ECA by HVX-O2
Original brand:
AEG - Alsthom - Alstom
PE91041
ECOFIT™ proposal
With ECOFIT™, a true extended life time
PE91042
1997
2005
2012
2015
ECA
HVX-O2
ECOFIT™ solution
Commercialisation
End of commercialisation
End of spare parts
PE91040
ECA Circuit Breaker
Main technical characteristics
ECA Rated current (Ir)
Intensity short circuit (Isc)
Rated voltage Un (50/60 Hz)
HVX-O2
Circuit Breaker
630 - 1250 A
25 - 31.5 kA
12 - 17.5 kV
HVX-O2
Technology
Vacuum
Rated voltage Ur (kV)
17.5
HVX-O2
Switching sequence
O-0.3 s-CO-3 min-CO
Surge withstand voltage Up (kV) 95
Closing time (ms)
35
Nominal frequency (Hz)
50
Opening time (ms)
53
Rated current Ir (A)
Up to 1250
31.5
Number of switching
operations
10.000
Short circuit current Isc (kA)
Short circuit duration Tk (s)
3 Service temperature (°C)
- 5 / + 40
Offer extension
PE90437
PE91041
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
Sepam series 10, 20, 40, 60 , 80
PE90488
or
MICOMP series 10, 20, 30, 40
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
A-3
Medium Voltage Distribution
All with fixed CB / All fixed CB types by HVXUW
Original brand:
all brands
ECOFIT™ proposal
All breaker types
Compatible with
all open Air
Insulated
Switchgear legacy
and no legacy
cubicles
with minimum
inside panel
width ≥ 650 mm
With ECOFIT™, a true extended life time
PE9075
This solution consist in fitting a cradle inside an existing panel.
- It is particularly adapted for non Schneider Installed Base.
- ECOFIT™ solution with shutters and mechanical interlocks embedded.
- Only the fixed connections (between the cradle and existing busbar) are customized.
- No age condition of the existing equipment.
- Only the width of the existing panel has to be considered.
Main technical characteristics
All types
Rated current (Ir)
Short circuit current (Isc)
Rated voltage Un (50/60 Hz)
Withdrawable
HVXUW
Circuit Breaker
630 - 2500 A
Up to 31.5 kA
12 kV
Up to 31.5 kA
24 kV
HVXUW
Technology
SF6
Rated voltage Ur (kV)
12 - 24
HVXUW
Switching sequence
O-0.3 s-CO-3min-CO
Surge withstand voltage Up (kV) 75 - 125
Closing time (ms)
45 - 63
Nominal frequency (Hz)
50 - 60
Opening time (ms)
35 - 53
Rated current Ir (A)
630 - 2500
16 - 50
Number of switching
operations
10.000
Short circuit current Isc (kA)
Short circuit duration Tk (s)
3
Service temperature (°C)
- 5 / + 40
Offer extension
PE90437
PE90487
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
Sepam series 10, 20, 40, 60 , 80
PE90488
or
A-4
MICOMP series 10, 20, 30, 40
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
Medium Voltage Distribution
ALLIANCE / FP - GFA by FP - GFA
Original brand:
Alsthom
PE90760
ECOFIT™ proposal
With ECOFIT™, a true extended life time
1995
2013
2027
PE90761
FP - GFA
FP - GFA
ECOFIT™ solution
Commercialisation
End of spare parts
PE90761
FP - GFA
Circuit Breaker
Main technical characteristics
Rated current (Ir)
Short circuit current (Isc)
Rated voltage Un (50/60 Hz)
FP - GFA
Circuit Breaker
FP
GFA
Technology
SF6
SF6
Rated voltage Ur (kV)
7.2 - 12
7.2 FP GFA
400 - 3150 A
16 - 50 kA
60 - 75 kV
400 A
10 kA
60 kV
FP
GFA
Switching sequence
O-3 min-CO-3 min-CO C/O
CO-15 s-CO
O-0.3 s-CO-3 min-CO
Surge withstand voltage Up (kV) 60 - 75
60
Closing time (ms)
50
45 - 175
Nominal frequency (Hz)
50 - 60
50 - 60
Opening time (ms)
70
90 - 120
Rated current Ir (A)
400 - 3150
400
300000 (mechanical)
16 - 50
10
Number of switching
operations
10000 (mechanical)
Short circuit current Isc (kA)
Short circuit duration Tk (s)
1 1 Service temperature (°C)
- 5 / + 40
- 5 / + 40
Offer extension
PE90437
PE90760
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
Sepam series 10, 20, 40, 60 , 80
PE90488
or
MICOMP series 10, 20, 30, 40
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
A-5
Medium Voltage Distribution
Belledonne B200-B400 / DSE22 to DSE78
Original brand: Merlin Gerin
by LF2 -LF3- SF1 - Evolis
ECOFIT™ proposal
With ECOFIT™, a true extended life time
PE90400
1972
1986
1988
2001
DSE22 to DSE78
LF2 - LF3 - SF1 - Evolis
ECOFIT™ solution
Commercialisation
End of commercialisation
End of spare parts
PE90401
DSE22 to DSE78
Circuit Breaker
Main technical characteristics
DSE to DSE78
Rated current (Ir)
Short circuit current (Isc)
Rated voltage Un (50/60 Hz)
LF2 - LF3 - SF1 Evolis
Circuit Breaker
LF2 / LF3
LF2 / LF3
SF1
630 - 3500 A
29 - 50 kA
7.2 kV
630 - 3150 A
24 - 48 kA
12 kV
Evolis
15 - 46 kA
17.5 kV
LF2
Technology
SF6
SF6
SF6
Vacuum
Rated voltage Ur (kV)
7.2 - 12 17.5
24
7.2 - 12 - 17.5
Surge withstand voltage Up (kV) 60 - 75
95
125
Nominal frequency (Hz)
50 - 60
50 - 60
50 - 60
Rated current Ir (A)
630 - 3150 630 - 3150 630 - 1250 630 - 2500
Short circuit current Isc (kA)
29 - 50
29 - 40
10 - 25
Short circuit duration Tk (s)
3 3 3 10 - 29 kA
24 kV
LF3
SF1
Evolis
Switching sequence
O-3 min-CO-3 min-CO
O-0.3 s-CO-3 min-CO
O-0.3 s-CO-15 s-CO
60 - 75 - 95
Closing time (ms)
< 72
< 65
< 65
50 - 60
Opening time (ms)
< 654
< 50
< 50
Number of switching
operations
10000
10000
10000
10000*
40
4 Service temperature (°C)
- 25 / + 40
- 25 / + 40
- 25 / + 40
- 25 / + 40
* class MI: 2000 operations for Isc:40 kA
Offer extension
PE90415
PE90437
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
or
PE90488
A-6
Sepam series 10, 20, 40, 60 , 80
MICOMP series 10, 20, 30, 40
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
Medium Voltage Distribution
Belledonne B200G / DSE22K - DSE23K by LF1 - Evolis
Original brand:
Merlin Gerin
ECOFIT™ proposal
PE90403
With ECOFIT™, a true extended life time
1971
1988
1992
DSE22K - DSE23K
LF1 - Evolis
ECOFIT™ solution
Commercialisation
End of commercialisation
End of space parts
PE90404
DSE22K - DSE23K
Circuit Breaker
Main technical characteristics
DSE22K - DSE23K
Rated current (Ir)
Short circuit current (Isc)
Rated voltage Un (50/60 Hz)
LF1 - Evolis
Circuit Breaker
LF1
Evolis
Technology
SF6
Vacuum
Rated voltage Ur (kV)
7.2 7.2 630 - 1250 A
25 -31.5 kA
7.2 kV
LF1
Evolis
Switching sequence
O-3 min-CO-3 min-CO O-3 min-CO-3 min-CO
O-0.3 s-CO-3 min-CO O-0.3 s-CO-3 min-CO
O-0.3 s-CO-15 s-CO O-0.3 s-CO-15 s-CO
Surge withstand voltage Up (kV) 60
60
Closing time (ms)
< 72
< 65
Nominal frequency (Hz)
50 - 60
50 - 60
Opening time (ms)
< 54
< 50
Rated current Ir (A)
630 - 1250
630 - 1250
2000* - 10.000
25 - 31.5
25 - 31.5
Number of switching
operations
10000
Short circuit current Isc (kA)
Short circuit duration Tk (s)
3 3 Service temperature (°C)
- 25 / + 40
- 25 / + 40
* Class M1: 2000 operations for Isc = 40 kA
Offer extension
PE90437
PE90403
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
Sepam series 10, 20, 40, 60 , 80
PE90488
or
MICOMP series 10, 20, 30, 40
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
A-7
Medium Voltage Distribution
Belledonne B650 / DIS by LF1 - R400 - R400D - EVOLIS
Original brand:
Merlin Gerin
PE90396
ECOFIT™ proposal
With ECOFIT™, a true extended life time
1976
PE90397
1958
1986
1988
DIS
LF1 - R400 - R400D - Evolis
ECOFIT™ solution
Commercialisation
End of commercialisation
End of spare parts
PE90398
DIS
Circuit Breaker
Main technical characteristics
DIS
Rated current (Ir)
Short circuit current (Isc)
Rated voltage Un (50/60 Hz)
LF1 - R400 - R400D - EVOLIS
Circuit Breaker
LF1
R400
R400D
400 - 1250 A
25 - 31.5 kA
7.2 kV
Evolis
LF1
Technology
SF6
SF6
SF6
Vacuum
Rated voltage Ur (kV)
7.2 7.2 7.2 7.2 Surge withstand voltage Up (kV) 60
60
60
Nominal frequency (Hz)
50 - 60
50 - 60
50 - 60
Rated current Ir (A)
630 - 1250 80 - 250
Short circuit current Isc (kA)
31.5
50*
Short circuit duration Tk (s)
3 3 3 R400
R400D
Evolis
Switching sequence
O-3 min-CO-3 min-CO
O-0.3 s-CO-3 min-CO
O-0.3 s-CO-15 s-CO
60
Closing time (ms)
< 72
75 - 155
75 - 155
< 65
50 - 60
Opening time (ms)
< 54
20 - 50
20 - 50
< 50
80 - 250
630 - 2500
300000
100000
10000
25 - 31.5
Number of switching
operations
10000
50*
3 Service temperature (°C)
- 25 / + 40
- 25 / + 40
- 25 / + 40
- 25 / + 40
* With fuses
Offer extension
PE90437
PE90396
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
Sepam series 10, 20, 40, 60 , 80
PE90488
or
A-8
MICOMP series 10, 20, 30, 40
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
Medium Voltage Distribution
Belledonne B900 / DIS by SF1
Original brand:
Merlin Gerin
PE90396
ECOFIT™ proposal
With ECOFIT™, a true extended life time
PE90397
1961
1978
1988
1992
DIS
SF1
ECOFIT™ solution
Commercialisation
End of commercialisation
End of spare parts
PE90399
DIS
Circuit Breaker
Main technical characteristics
DIS
Rated current (Ir)
Short circuit current (Isc)
Rated voltage Un (50/60 Hz)
SF1
Circuit Breaker
400 - 1250 A
12.5 kA
23 kV
SF1
Technology
SF6
Rated voltage Ur (kV)
24 SF1
Switching sequence
O-3 min-CO-3 min-CO
O-0.3 s-CO-3 min-CO
O-0.3 s-CO-15 s-CO
Surge withstand voltage Up (kV) 125
Closing time (ms)
< 65
Nominal frequency (Hz)
50 - 60
Opening time (ms)
< 50
Rated current Ir (A)
630 - 1250
10.000
Short circuit current Isc (kA)
25
Number of switching
operations
Short circuit duration Tk (s)
3 Service temperature (°C)
- 25 / + 40
Offer extension
PE90437
PE90396
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
Sepam series 10, 20, 40, 60 , 80
PE90488
or
MICOMP series 10, 20, 30, 40
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
A-9
Medium Voltage Distribution
BVP 17 / BVP 17 by VMX
Original brand:
AEI - GEC - GEC Alsthom
PE90604
ECOFIT™ proposal
With ECOFIT™, a true extended life time
PE90605
1965
1984
2001
2006
BVP 17
VMX
ECOFIT™ solution
Commercialisation
End of commercialisation
End of spare parts
PE90606
BVP 17
Circuit Breaker
Main technical characteristics
BVP 17
Rated current (Ir)
Short circuit current (Isc)
Rated voltage Un (50/60 Hz)
VMX
Circuit Breaker
400 - 1250 A
25 kA
11 kV
VMX
Technology
Vacuum
Rated voltage Ur (kV)
11
VMX
Switching sequence
O-3 min-CO-3 min-CO
O-0.3 s-CO-3 min-CO
O-0.3 s-CO-15 s-CO
Surge withstand voltage Up (kV) Up to 75
Closing time (ms)
< 52
Nominal frequency (Hz)
50 - 60
Opening time (ms)
< 61
Rated current Ir (A)
400 - 1250
10.000
Short circuit current Isc (kA)
Up to 25
Number of switching
operations
Short circuit duration Tk (s)
3 Service temperature (°C)
- 25 / + 40
Offer extension
PE90437
PE90604
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
Sepam series 10, 20, 40, 60 , 80
PE90488
or
A-10
MICOMP series 10, 20, 30, 40
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
Medium Voltage Distribution
Cemabloc C23mc 15 & 27 / CB by FP
Original brand:
CEM
PE90461
ECOFIT™ proposal
With ECOFIT™, a true extended life time
PE90462
1963
1984
1994
2010
CB
FP
ECOFIT™ solution
Commercialisation
End of commercialisation
End of spare parts
PE90463
CB
Circuit Breaker
Main technical characteristics
CB
Rated current (Ir)
Short circuit current (Isc)
Rated voltage Un (50/60 Hz)
FP
Circuit Breaker
400 - 1250 A
12.5 - 16/25 kA
23 kV
FP
Technology
SF6
Rated voltage Ur (kV)
24
FP
Switching sequence
O-3 min-CO-3 min-CO
O-0.3 s-CO-3 min-CO
O-0.3 s-CO-15 s-CO
Surge withstand voltage Up (kV) 125
Closing time (ms)
50
Nominal frequency (Hz)
50 - 60
Opening time (ms)
70
Rated current Ir (A)
400 - 3150
10.000
Short circuit current Isc (kA)
12.5 - 40
Number of switching
operations
Short circuit duration Tk (s)
3 Service temperature (°C)
- 5 / + 40
Offer extension
PE90437
PE90461
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
Sepam series 10, 20, 40, 60 , 80
PE90488
or
MICOMP series 10, 20, 30, 40
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
A-11
Medium Voltage Distribution
PE90763
PE90762
PE90466
Cemabloc - C26.0 / CS by FPR - C26.1 / CX by FPR
Original brand: CEM
- C26.2 /FPR by FPR
ECOFIT™ proposal
With ECOFIT™, a true extended life time
1982
PE90467
1976
1985
1991
CS - CX - FPR
FPR
ECOFIT™ solution
Commercialisation
End of commercialisation
End of spare parts
PE90468
CS
Circuit Breaker
Main technical characteristics
CS
FPR
Circuit Breaker
Rated current (Ir)
Short circuit current (Isc)
Rated voltage Un (50/60 Hz)
400 - 1250 A
14.5 kA
24 kV
FPR
Technology
SF6
Rated voltage Ur (kV)
24
CX
FPR
400 - 1250 A
12.5 kA
24 kV
FPR
Switching sequence
O-3 min-CO-3 min-CO
O-0.3 s-CO-15 s-CO
Surge withstand voltage Up (kV) 125
Closing time (ms)
50
Nominal frequency (Hz)
50 - 60
Opening time (ms)
80
Rated current Ir (A)
400 - 1250
10.000
Short circuit current Isc (kA)
12.5
Number of switching
operations
Short circuit duration Tk (s)
1
Service temperature (°C)
- 25 / + 40
Offer extension
PE90437
PE90466
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
Sepam series 10, 20, 40, 60 , 80
PE90488
or
A-12
MICOMP series 10, 20, 30, 40
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
Medium Voltage Distribution
Composit (860mm width) / MG by SF1
Original brand:
Nuova Magrini Galileo
PE90575
ECOFIT™ proposal
With ECOFIT™, a true extended life time
1993
2000
PE90576
1966
2010
MG
SF1
ECOFIT™ solution
Commercialisation
End of commercialisation
End of spare parts
MG
Circuit Breaker
PE90232
Main technical characteristics
MG
SF1
Circuit Breaker
150-500
150-750
350-750
150-750
350-750
Rated current (Ir)
630 - 1250 A
630 - 1250 A
630 - 1250 A
630 - 1250 A
630 - 1250 A
Short circuit current (Isc)
Rated voltage Un (50/60 Hz)
8.7 - 28.9 kA
10 kV
5 - 29 kA
15 kV
12.5 - 29 kA
17 kV
3.6 - 24 kA
20 kV
6.3 - 21.7 kA
24 kV
SF1
Technology
SF6
Rated voltage Ur (kV)
17.5 - 24 SF1
Switching sequence
O-3 min-CO-3 min-CO
O-0.3 s-CO-3 min-CO
O-0.3 s-CO-15 s-CO
Surge withstand voltage Up (kV) 95 - 125
Closing time (ms)
< 65
Nominal frequency (Hz)
50 - 60
Opening time (ms)
< 50
Rated current Ir (A)
630 - 1250
10.000
Short circuit current Isc (kA)
25
Number of switching
operations
Short circuit duration Tk (s)
3 Service temperature (°C)
- 25 / + 40
Offer extension
PE90437
PE90575
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
Sepam series 10, 20, 40, 60 , 80
PE90488
or
MICOMP series 10, 20, 30, 40
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
A-13
Medium Voltage Distribution
CSIM 1-12 / SCI-4 by VEIVACUUM F
Original brand:
VEB " Otto Buchwitz "
PE90560
ECOFIT™ proposal
With ECOFIT™, a true extended life time
PE90561
1975
1991
2006
SCI-4
VEIVACUUM F
ECOFIT™ solution
Commercialisation
End of commercialisation
End of spare parts
PE90562
SCI-4
Circuit Breaker
Main technical characteristics
SCI-4
Rated current (Ir)
Short circuit current (Isc)
Rated voltage Un (50/60 Hz)
VEIVACUUM F
Circuit Breaker
630 - 1250 A
16 - 31.5 kA
12 kV
VEIVACUUM F
Technology
Vacuum
Rated voltage Ur (kV)
12
VEIVACUUM F
Switching sequence
O-0.3 s-CO-3min-CO
Surge withstand voltage Up (kV) 75
Closing time (ms)
65
Nominal frequency (Hz)
50 - 60
Opening time (ms)
50
Rated current Ir (A)
600 - 1250
10.000
Short circuit current Isc (kA)
25 Number of switching
operations
Short circuit duration Tk (s)
3 Service temperature (°C)
- 25 / + 40
Offer extension
PE90437
PE90563
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
Sepam series 10, 20, 40, 60 , 80
PE90488
or
A-14
MICOMP series 10, 20, 30, 40
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
Medium Voltage Distribution
CSIM 3-12 / SCI-4 by VEIVACUUM F - VA
Original brand:
VEB " Otto Buchwitz "
PE90640
ECOFIT™ proposal
With ECOFIT™, a true extended life time
1975
1991
2006
2012
SCI-4
VEIVACUUM F - VA
ECOFIT™ solution
SCI-4
Circuit Breaker
End of commercialisation
End of spare parts
PE90641
Commercialisation
Main technical characteristics
SCI-4
Rated current (Ir)
Intensity short circuit (Isc)
Rated voltage Un (50/60 Hz)
VEIVACUUM F - VA
Circuit Breaker
630 - 2500 A
16 - 31.5 kA
12 kV
VEIVACUUM F - VA
Technology
Vacuum
Rated voltage Ur (kV)
12
VEIVACUUM F - VA
Switching sequence
O-0.3 s-CO-3min-CO
Surge withstand voltage Up (kV) 75
Closing time (ms)
45 - 65
Nominal frequency (Hz)
50 - 60
Opening time (ms)
45 - 65
Rated current Ir (A)
600 - 3150
10.000
Short circuit current Isc (kA)
25 - 40
Number of switching
operations
Short circuit duration Tk (s)
3
Service temperature (°C)
- 25 / + 40
Offer extension
PE90437
PE90563
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
Sepam series 10, 20, 40, 60 , 80
PE90488
or
MICOMP series 10, 20, 30, 40
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
A-15
Medium Voltage Distribution
DNF4-2E / FP - GFA by FP - HVX - CVX
Original brand:
Alsthom
PE90667
ECOFIT™ proposal
With ECOFIT™, a true extended life time
1983
1997
2007
2009
PE90668
FP - GFA
FP - HVX - CVX
ECOFIT™ solution
Commercialisation
End of commercialisation
End of spare parts
PE90669
FP - GFA
Circuit Breaker
Main technical characteristics
FP - GFA
Rated current (Ir)
Short circuit current (Isc)
Rated voltage Un (50/60 Hz)
FP - HVX - CVX
Circuit Breaker
FP
HVX
400 - 2000 A
40 kA
12 kV
CVX
Technology
SF6
Vacuum
Vacuum
Rated voltage Ur (kV)
12
12
12
Surge withstand voltage Up (kV) 75
75
Nominal frequency (Hz)
50 - 60
50 - 60
Rated current Ir (A)
400 - 3150
Short circuit current Isc (kA)
12 - 50
Short circuit duration Tk (s)
3 FP
HVX
CVX
Switching sequence
O-3 min-CO-3 min-CO
O-0.3 s-CO-3 min-CO*
CO-15s-CO
O-0.3 s-CO-15 s-CO*
O-0.3 s-CO-3min-CO**
C/O
75
Closing time (ms)
50
35 - 53
40 - 80
50 - 60
Opening time (ms)
70
45 - 63
100 - 200
630 - 3150
400
10.000
4
Number of switching
operations
10.000
16 - 50
300.000
(mech.)
500.000 (elec.)
3 1 Service temperature (°C)
- 5 / + 40
- 5 / + 40
- 25 / + 40
* HVX only / ** FP only
Offer extension
PE90437
PE90670
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
Sepam series 10, 20, 40, 60 , 80
PE90488
or
A-16
MICOMP series 10, 20, 30, 40
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
Medium Voltage Distribution
DNF4 MI & FI / FP by FP - HVX
Original brand:
Alsthom
PE90671
ECOFIT™ proposal
With ECOFIT™, a true extended life time
1997
PE90672
1983
2007
2010
FP FP - HVX ECOFIT™ solution
Commercialisation
End of commercialisation
End of spare parts
PE90673
FP Circuit Breaker
Main technical characteristics
FP Rated current (Ir)
Short circuit current (Isc)
Rated voltage Un (50/60 Hz)
FP - HVX
Circuit Breaker
FP
400 - 2500 A
40 kA
12 kV
HVX
Technology
SF6
Vacuum
Rated voltage Ur (kV)
12
12
FP
HVX
Switching sequence
O-3 min-CO-3 min-CO O-3 min-CO-3 min-CO
CO-15s-CO
O-0.3 s-CO-3 min-CO
O-0.3 s-CO-3 min-CO CO-15s-CO
O-0.3 s-CO-15 s-CO
Surge withstand voltage Up (kV) 75
75
Closing time (ms)
50
35 - 53
Nominal frequency (Hz)
50 - 60
50 - 60
Opening time (ms)
70
45 - 63
Rated current Ir (A)
400 - 3150
630 - 3150
10.000
16 - 50
25 - 50
Number of switching
operations
10.000
Short circuit current Isc (kA)
Short circuit duration Tk (s)
3 3 Service temperature (°C)
- 5 / + 40
- 5 / + 40
Offer extension
PE90437
PE90671
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
Sepam series 10, 20, 40, 60 , 80
PE90488
or
MICOMP series 10, 20, 30, 40
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
A-17
Medium Voltage Distribution
DNF5 - DNF5-2B / FP by FP - HVX
Original brand:
Alsthom
PE90678
ECOFIT™ proposal
With ECOFIT™, a true extended life time
1997
PE90672
1983
2007
2011
FP FP - HVX ECOFIT™ solution
Commercialisation
End of commercialisation
End of spare parts
PE90673
FP Circuit Breaker
Main technical characteristics
FP Rated current (Ir)
Short circuit current (Isc)
Rated voltage Un (50/60 Hz)
FP - HVX
Circuit Breaker
FP
HVX
Technology
SF6
Vacuum
Rated voltage Ur (kV)
17.5
17.5
630 - 2000 A
40 kA
17.5 kV
FP
Switching sequence
HVX
O-3 min-CO-3 min-CO O-3 min-CO-3 min-CO
CO-15s-CO
O-0.3 s-CO-3 min-CO
O-0.3 s-CO-3 min-CO CO-15s-CO
O-0.3 s-CO-15 s-CO
Surge withstand voltage Up (kV) 75
75
Closing time (ms)
50
35 - 53
Nominal frequency (Hz)
50 - 60
50 - 60
Opening time (ms)
70
45 - 63
Rated current Ir (A)
400 - 3150
630 - 3150
10.000
16 - 40
25 - 40
Number of switching
operations
10.000
Short circuit current Isc (kA)
Short circuit duration Tk (s)
3 3
Service temperature (°C)
- 5 / + 40
- 5 / + 40
Offer extension
PE90437
PE90678
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
Sepam series 10, 20, 40, 60 , 80
PE90488
or
A-18
MICOMP series 10, 20, 30, 40
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
Medium Voltage Distribution
DNF6 / FP by FP - HVX
Original brand:
Alsthom
PE90679
ECOFIT™ proposal
With ECOFIT™, a true extended life time
1997
PE90680
1987
2007
2011
FP FP - HVX ECOFIT™ solution
Commercialisation
End of commercialisation
End of spare parts
PE90673
FP Circuit Breaker
Main technical characteristics
FP Rated current (Ir)
Short circuit current (Isc)
Rated voltage Un (50/60 Hz)
FP - HVX
Circuit Breaker
FP
400 - 2000 A
31.5 kA
24 kV
HVX
Technology
SF6
Vacuum
Rated voltage Ur (kV)
24
24
FP
HVX
Switching sequence
O-3 min-CO-3 min-CO O-3 min-CO-3 min-CO
CO-15s-CO
O-0.3 s-CO-3 min-CO
O-0.3 s-CO-3 min-CO CO-15s-CO
O-0.3 s-CO-15 s-CO
Surge withstand voltage Up (kV) 75
75
Closing time (ms)
50
35 - 53
Nominal frequency (Hz)
50 - 60
50 - 60
Opening time (ms)
70
45 - 63
Rated current Ir (A)
400 - 3150
630 - 2500
10.000
16 - 40
25 - 40
Number of switching
operations
10.000
Short circuit current Isc (kA)
Short circuit duration Tk (s)
3
3
Service temperature (°C)
- 5 / + 40
- 5 / + 40
Offer extension
PE90437
PE90679
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
Sepam series 10, 20, 40, 60 , 80
PE90488
or
MICOMP series 10, 20, 30, 40
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
A-19
Medium Voltage Distribution
DNF7 / FP by FP - HVX-O2
Original brand:
Alsthom
PE90674
ECOFIT™ proposal
With ECOFIT™, a true extended life time
2013
2024
PE90675
1983
FP
FP - HVX-O2
ECOFIT™ solution
Commercialisation
PE90676
FP Circuit Breaker
End of commercialisation
End of spare parts
Main technical characteristics
FP Rated current (Ir)
Intensity short circuit (Isc)
Rated voltage Un (50/60 Hz)
FP - HVX-O2
Circuit Breaker
FP
400 - 2000 A
31.5 kA
36 kV
HVX-O2
Technology
SF6
Vacuum
Rated voltage Ur (kV)
36
40.5
Switching sequence
FP
HVX-O2
O-0.3 s-CO-3 min-CO
O-0.3 s-CO-15s-CO
CO-15 s-CO
O-3 min-CO-3 min-CO
O-0.3 s-CO-3 min-CO
O-3 min-CO-3 min-CO
O-0.3 s-CO-15s-CO
CO-15 s-CO
Surge withstand voltage Up (kV) 170
185
Closing time (ms)
50
45 - 53
Nominal frequency (Hz)
50 - 60
50 - 60
Opening time (ms)
70
45 - 63
Rated current Ir (A)
Up to 2500
Up to 2500
10.000
31.5
31.5
Number of switching
operations
5.000
Short circuit current Isc (kA)
Short circuit duration Tk (s)
3 3 Service temperature (°C)
- 5 / + 40
- 5 / + 40
Offer extension
PE90437
PE90674
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
Sepam series 10, 20, 40, 60 , 80
PE90488
or
A-20
MICOMP series 10, 20, 30, 40
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
Medium Voltage Distribution
Epoclad / DHF & F by LF1 - LF2 - LF3 - SF1
Original brand:
Nuova Magrini Galileo
PE90577
ECOFIT™ proposal
With ECOFIT™, a true extended life time
DHF - F
Circuit Breaker
1969
1997
2005
2011
DHF & F
LF1 - LF2 - LF3 - SF1
ECOFIT™ solution
End of commercialisation
End of spare parts
PE90579
Commercialisation
Main technical characteristics
DHF & F
6DHF
6DHF/N
250-500
7F/N
250-350
10DHF
250-750
7F
350-750
15DHF
350-850
12F
12F/N
350-750
24DHF
350-500
20DHF
350-750
24F
500-750
Rated current (Ir)
630 - 3150 A
630 - 3150 A
630 - 3150 A
630 - 3150 A
630 - 1250 A
630 - 3150 A
630 - 3150 A
630 - 1250 A
Short circuit current (Isc)
20 - 48 kA
29 - 34 kA
12 - 43 kA
18 - 48 kA
13.5 - 32.5 kA
12.5 - 48 kA
9.2 - 14.5 kA
Rated voltage Un (50/60 Hz)
6 kV
7.2 kV
10 kV
12 kV
15 kV
17 kV
20 kV
LF1 - LF2 LF3 - SF1
Circuit Breaker
LF1
LF2
LF3*
SF1
LF1
Technology
SF6
SF6
SF6
SF6
Rated voltage Ur (kV)
7.2 7.2 - 12 17.5
24
Surge withstand voltage Up (kV) 60
60 - 75
95
Nominal frequency (Hz)
50 - 60
50 - 60
50 - 60
Rated current Ir (A)
630 - 1250 2000 / 630 - 3150 630 - 1250
up to 2000
Short circuit current Isc (kA)
31.5
50 - 40
40
25
Short circuit duration Tk (s)
3 3 3 3 LF2
8 - 18 kA /20DHF
12.5 - 18 kA /24F
24 kV
LF3*
SF1
Switching sequence
O-3 min-CO-3 min-CO
O-0.3 s-CO-3 min-CO
O-0.3 s-CO-15 s-CO
125
Closing time (ms)
< 72
< 72
< 72
< 65
50 - 60
Opening time (ms)
< 54
< 54
< 54
< 50
Number of switching
operations
10.000
10.000
10.000
10.000
Service temperature (°C)
- 25 / + 40
- 25 / + 40
- 25 / + 40
- 25 / + 40
* Ur: 7.2 / 12, A: 3150, kA: 50
Offer extension
PE90577
PE90437
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
Sepam series 10, 20, 40, 60 , 80
PE90488
or
MICOMP series 10, 20, 30, 40
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
A-21
Medium Voltage Distribution
Fluair F100 - F200 / FG1 - FG2 by LF2 - LF3 - Evolis
Original brand:
Merlin Gerin
PE90409
ECOFIT™ proposal
With ECOFIT™, a true extended life time
1980
1998
1999
2011
FG1 - FG2
LF2 - LF3 - Evolis
ECOFIT™ solution
Commercialisation
PE90411
FG1 - FG2
Circuit Breaker
End of commercialisation
End of spare parts
Main technical characteristics
FG1 - FG2
Rated current (Ir)
Short circuit current (Isc)
Rated voltage Un (50/60 Hz)
LF2 - LF3 - EVOLIS
Circuit Breaker
LF2 - LF3
630 - 3150 A
25 - 50 kA
7.2 kV
630 - 3150 A
25 - 50 kA
12 kV
Evolis
630 - 3150 A
25 - 31.5 kA
17.5 kV
LF2 - LF3
Technology
SF6
SF6
Vacuum
Rated voltage Ur (kV)
7.2 - 12
17.5
up to 17.5
Evolis
Switching sequence
O-3 min-CO-3 min-CO
O-0.3 s-CO-3 min-CO
O-0.3 s-CO-15 s-CO
Surge withstand voltage Up (kV) 60 - 75
95
up to 95
Closing time (ms)
< 72
< 72
< 65
Nominal frequency (Hz)
50 - 60
50 - 60
50 - 60
Opening time (ms)
< 54
< 54
< 50
Rated current Ir (A)
630 - 3150
630 - 3150
630 - 2500
10.000
25 - 50
31.5
40
Number of switching
operations
10.000
Short circuit current Isc (kA)
2000 (Isc =
40 kA / M1
class) - 10.000
Short circuit duration Tk (s)
3 3 3 Service temperature (°C)
- 25 / + 40
- 25 / + 40
- 25 / + 40
Offer extension
PE90437
PE90409
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
Sepam series 10, 20, 40, 60 , 80
PE90488
or
A-22
MICOMP series 10, 20, 30, 40
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
Medium Voltage Distribution
Fluair F100C / R400 - R400D by R400 - R400D
Original brand:
Merlin Gerin
PE90412
ECOFIT™ proposal
With ECOFIT™, a true extended life time
1980
1998
R400 - R400D
R400 - R400D
ECOFIT™ solution
Commercialisation
End of spare parts
PE90413
R400 - R400D
Circuit Breaker
R400 - R400D
Circuit Breaker
Main technical characteristics
R400
R400D
Technology
SF6
SF6
Rated voltage Ur (kV)
7.2
7.2
R400
R400D
Switching sequence
Surge withstand voltage Up (kV) 60
60
Closing time (ms)
75 - 155
75 - 155
Nominal frequency (Hz)
50 - 60
50 - 60
Opening time (ms)
20 - 50
20 - 50
Rated current Ir (A)
80 - 250
80 - 250
100.000
50 (with fuses)
50 (with fuses)
Number of switching
operations
300.000
Short circuit current Isc (kA)
Short circuit duration Tk (s)
3
3 Service temperature (°C)
- 25 / + 40
- 25 / + 40
Offer extension
PE90437
PE90412
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
Sepam series 10, 20, 40, 60 , 80
PE90488
or
MICOMP series 10, 20, 30, 40
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
A-23
Medium Voltage Distribution
Fluair F300 / FG3 (1000mm width) by SF1 - SF2
Original brand:
Merlin Gerin
PE90742
ECOFIT™ proposal
With ECOFIT™, a true extended life time
1980
1998
1999
2009
FG3
SF1 - SF2
ECOFIT™ solution
Commercialisation
PE90744
FG3
Circuit Breaker
End of commercialisation
End of spare parts
Main technical characteristics
FG3
Rated current (Ir)
Short circuit current (Isc)
Rated voltage Un (50/60 Hz)
SF1 - SF2
Circuit Breaker
SF1
SF2
Technology
SF6
SF6
Rated voltage Ur (kV)
24
24
630 - 2500 A
25 - 31.5 kA
24 kV
SF1
Switching sequence
SF2
O-3 min-CO-3 min-CO
O-0.3 s-CO-3 min-CO
O-0.3 s-CO-15 s-CO
Surge withstand voltage Up (kV) 125
125
Closing time (ms)
< 65
< 65
Nominal frequency (Hz)
50 - 60
50 - 60
Opening time (ms)
< 50
< 50
Rated current Ir (A)
630 - 1250
1250 - 2500
10.000
25
25 - 31.5
Number of switching
operations
10.000
Short circuit current Isc (kA)
Short circuit duration Tk (s)
3 3 Service temperature (°C)
- 25 / + 40
- 25 / + 40
Offer extension
PE90437
PE90409
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
Sepam series 10, 20, 40, 60 , 80
PE90488
or
A-24
MICOMP series 10, 20, 30, 40
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
Medium Voltage Distribution
Fluair F400C / FC4 by SF2
Original brand:
Merlin Gerin
PE90414
ECOFIT™ proposal
With ECOFIT™, a true extended life time
1980
1987
1991
2000
FC4
SF2
ECOFIT™ solution
Commercialisation
PE90416
FC4
Circuit Breaker
End of commercialisation
End of spare parts
Main technical characteristics
FC4
Rated current (Ir)
Short circuit current (Isc)
Rated voltage Un (50/60 Hz)
SF2
Circuit Breaker
1250 - 2500 A
31.5 - 40 kA
36 kV
SF2
Technology
SF6
Rated voltage Ur (kV)
36
SF2
Switching sequence
O-3 min-CO-3 min-CO
O-0.3 s-CO-3 min-CO
O-0.3 s-CO-15 s-CO
Surge withstand voltage Up (kV) 170
Closing time (ms)
< 65
Nominal frequency (Hz)
50 - 60
Opening time (ms)
< 50
Rated current Ir (A)
1250 - 2500
10.000
Short circuit current Isc (kA)
31.5 - 40
Number of switching
operations
Short circuit duration Tk (s)
3 Service temperature (°C)
- 25 / + 40
Offer extension
PE90437
PE90414
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
Sepam series 10, 20, 40, 60 , 80
PE90488
or
MICOMP series 10, 20, 30, 40
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
A-25
Medium Voltage Distribution
Fluair F400G / FG4 by SF1 - SF2
Original brand:
Merlin Gerin
PE90417
ECOFIT™ proposal
With ECOFIT™, a true extended life time
1986
2002
2004
2009
FG4
SF1 - SF2
ECOFIT™ solution
Commercialisation
PE90450
FG4
Circuit Breaker
End of commercialisation
End of spare parts
Main technical characteristics
FG4
Rated current (Ir)
Short circuit current (Isc)
Rated voltage Un (50/60 Hz)
SF1 - SF2
Circuit Breaker
1250 - 2500 A
40 kA
24 kV
1250 - 3150 A
25 - 40 kA
36 kV
SF1 - SF2
Technology
SF6
Rated voltage Ur (kV)
24 - 36
SF1 - SF2
Switching sequence
O-3 min-CO-3 min-CO
O-0.3 s-CO-3 min-CO
O-0.3 s-CO-15 s-CO
Surge withstand voltage Up (kV) 125 - 170
Closing time (ms)
< 65
Nominal frequency (Hz)
50 - 60
Opening time (ms)
< 50
Rated current Ir (A)
1250 - 2500
10.000
Short circuit current Isc (kA)
25 - 40
Number of switching
operations
Short circuit duration Tk (s)
3 Service temperature (°C)
- 25 / + 40
Offer extension
PE90437
PE90417
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
Sepam series 10, 20, 40, 60 , 80
PE90488
or
A-26
MICOMP series 10, 20, 30, 40
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
Medium Voltage Distribution
Fluokit M24 / FP by FP
Original brand:
DELLE ALSTHOM
PE90864
ECOFIT™ proposal
With ECOFIT™, a true extended life time
1987
2007
2011
2014
PE90863
FP FP
ECOFIT™ solution
Commercialisation
End of commercialisation
End of spare parts
FP
Circuit Breaker
PE90863
Main technical characteristics
FP
Rated current (Ir)
Short circuit current (Isc)
Rated voltage Un (50/60 Hz)
FP
Circuit Breaker
400 - 3150 A
16 - 20 - 25 - 31.5 - 40 kA
12 kV
FP
400 - 3150 A
16 - 20 - 25 - 31.5 - 40 kA
24 kV
FP
Technology
SF6
SF6
Rated voltage Ur (kV)
12
24
Switching sequence
O-3mn-CO-3mn-CO
CO-15 s-CO
O-0.3 s-CO-3mn-CO
Surge withstand voltage Up (kV) 75
125
Closing time (ms)
70 Nominal frequency (Hz)
50 - 60
50 - 60
Opening time (ms)
50
Rated current Ir (A)
400 - 3150
400 - 3150
16 - 20 - 25 - 31.5 - 40
16 - 20 - 25 - 31.5 - 40
Number of switching
operations
10.000
Short circuit current Isc (kA)
Short circuit duration Tk (s)
3
3
Service temperature (°C)
- 5 / + 40
Offer extension
PE90437
PE90864
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
Sepam series 10, 20, 40, 60 , 80
PE90488
or
MICOMP series 10, 20, 30, 40
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
A-27
Medium Voltage Distribution
Fluokit M24+ / FP by FP
Original brand:
DELLE ALSTHOM
PE90862
ECOFIT™ proposal
With ECOFIT™, a true extended life time
2005
2014
2024
PE90863
FP
FP
ECOFIT™ solution
Commercialisation
End of commercialisation
End of spare parts
FP
Circuit Breaker
PE90863
Main technical characteristics
FP
Rated current (Ir)
Short circuit current (Isc)
Rated voltage Un (50/60 Hz)
FP
Circuit Breaker
400 - 3150 A
16 - 20 - 25 - 31.5 - 40 kA
12 kV
FP
400 - 3150 A
16 - 20 - 25 - 31.5 - 40 kA
24 kV
FP
Technology
SF6
SF6
Rated voltage Ur (kV)
12
24
Switching sequence
O-3mn-CO-3mn-CO
CO-15 s-CO
O-0.3 s-CO-3mn-CO
Surge withstand voltage Up (kV) 75
125
Closing time (ms)
70 Nominal frequency (Hz)
50 - 60
50 - 60
Opening time (ms)
50
Rated current Ir (A)
400 - 3150
400 - 3150
16 - 20 - 25 - 31.5 - 40
16 - 20 - 25 - 31.5 - 40
Number of switching
operations
10.000
Short circuit current Isc (kA)
Short circuit duration Tk (s)
3
3
Service temperature (°C)
- 5 / + 40
Offer extension
PE90437
PE90862
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
Sepam series 10, 20, 40, 60 , 80
PE90488
or
A-28
MICOMP series 10, 20, 30, 40
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
Medium Voltage Distribution
Fluokit M36 / FP by FP
Original brand:
DELLE ALSTHOM
PE90860
ECOFIT™ proposal
With ECOFIT™, a true extended life time
1987
2014
2024
PE90861
FP
FP
ECOFIT™ solution
Commercialisation
End of commercialisation
End of spare parts
FP
Circuit Breaker
PE90861
Main technical characteristics
FP
Rated current (Ir)
Short circuit current (Isc)
Rated voltage Un (50/60 Hz)
FP
Circuit Breaker
400 - 3150 A
16 - 20 - 25 - 31.5 kA
36 kV
FP
Technology
SF6
Rated voltage Ur (kV)
36
FP
Switching sequence
O-3mn-CO-3mn-CO
CO-15 s-CO
O-0.3 s-CO-3mn-CO
Surge withstand voltage Up (kV) 170
Closing time (ms)
70
Nominal frequency (Hz)
50 - 60
Opening time (ms)
50
Rated current Ir (A)
400 - 3150
16 - 20 - 25 - 31.5
Number of switching
operations
10.000
Short circuit current Isc (kA)
Short circuit duration Tk (s)
3
Service temperature (°C)
- 5 / + 40
Offer extension
PE90437
PE90860
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
Sepam series 10, 20, 40, 60 , 80
PE90488
or
MICOMP series 10, 20, 30, 40
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
A-29
Medium Voltage Distribution
GS-10 / GE by VA - VAA
Original brand:
AEG
PE90550
ECOFIT™ proposal
With ECOFIT™, a true extended life time
PE90551
1966
1978
2004
2009
GE
VA - VAA ECOFIT™ solution
Commercialisation
PE90552
GE
Circuit Breaker
End of commercialisation
End of spare parts
Main technical characteristics
GE
Rated current (Ir)
Short circuit current (Isc)
Rated voltage Un (50/60 Hz)
VA - VAA
Circuit Breaker
630 - 3000 A
16 - 40 kA
12 kV
VA - VAA Technology
Vacuum
Rated voltage Ur (kV)
12 VA - VAA Switching sequence
O-0.3 s-CO-3min-CO
Surge withstand voltage Up (kV) 75 Closing time (ms)
45 - 65
Nominal frequency (Hz)
50 - 60
Opening time (ms)
45 - 65
Rated current Ir (A)
600 - 1250
10.000
Short circuit current Isc (kA)
40
Number of switching
operations
Short circuit duration Tk (s)
3 Service temperature (°C)
- 5 / + 40
Offer extension
PE90437
PE90553
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
Sepam series 10, 20, 40, 60 , 80
PE90488
or
A-30
MICOMP series 10, 20, 30, 40
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
Medium Voltage Distribution
HMC400 - HMC410 / HMC400 - HMC410
Original brand: GEC Alstom
by HMC400 - HMC410
PE90597
ECOFIT™ proposal
With ECOFIT™, a true extended life time
PE90594
1960
1970
2015
HMC400 - HMC410
HMC400 - HMC410
ECOFIT™ solution
PE90595
HMC400 - HMC410 Circuit Breaker
Commercialisation
End of commercialisation
End of spare parts
Main technical characteristics
HMC400 - HMC410 HMC400 - HMC410
Circuit Breaker
Rated current (Ir)
Short circuit current (Isc)
Rated voltage Un (50/60 Hz)
400 A
43.8 kA
3.3 kV
400 A
26.3 kA
6.6 kV
HMC400 - HMC410 Technology
Vacuum
Rated voltage Ur (kV)
Up to 6.6
HMC400 - HMC410 Switching sequence
O-3 min-CO-3 min-CO
O-0.3 s-CO-3 min-CO
O-0.3 s-CO-15 s-CO
Surge withstand voltage Up (kV) Up to 75
Closing time (ms)
< 52
Nominal frequency (Hz)
50 - 60
Opening time (ms)
< 61
Rated current Ir (A)
400
10.000
Short circuit current Isc (kA)
26.3 - 43.8
Number of switching
operations
Short circuit duration Tk (s)
3
Service temperature (°C)
- 25 / + 40
PE90681
Refurbishment
In-house refurbishment, including vacuum contactors and control scheme utlilising Gemstart unit, on site
maintenance
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
A-31
Medium Voltage Distribution
HMC1072 /HMC1072 by HMC1072
Original brand:
GEC Alstom
PE90599
ECOFIT™ proposal
With ECOFIT™, a true extended life time
1968
1983
1992
2015
HMC1072
HMC1072
ECOFIT™ solution
Commercialisation
End of commercialisation
End of spare parts
Main technical characteristics
HMC1072
Rated current (Ir)
Short circuit current (Isc)
Rated voltage Un (50/60 Hz)
HMC1072
400 A
63 kA rms/1s - 50 kA rms/3s
7.2 kV
HMC1072
Technology
Vacuum
Rated voltage Ur (kV)
7.2
HMC1072
Switching sequence
O-3 min-CO-3 min-CO
O-0.3 s-CO-3 min-CO
O-0.3 s-CO-15 s-CO
Surge withstand voltage Up (kV) Up to 75
Closing time (ms)
< 52
Nominal frequency (Hz)
50 - 60
Opening time (ms)
< 61
Rated current Ir (A)
400
10.000
Short circuit current Isc (kA)
50 - 63
Number of switching
operations
Short circuit duration Tk (s)
3 to 1
Service temperature (°C)
- 25 / + 40
Offer extension
PE90437
PE90599
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
Sepam series 10, 20, 40, 60 , 80
PE90488
or
A-32
MICOMP series 10, 20, 30, 40
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
Medium Voltage Distribution
HMC1172 /HMC1172 by HMC1172
Original brand:
GEC Alstom
ECOFIT™ proposal
PE90600
With ECOFIT™, a true extended life time
1980
2006
2008
On-going
HMC1172
HMC1172
ECOFIT™ solution
HMC1172
Commercialisation
End of commercialisation
End of spare parts
Main technical characteristics
HMC1172
Rated current (Ir)
Short circuit current (Isc)
Rated voltage Un (50/60 Hz)
VCB
400 A
63 kA rms/1s - 50 kA rms/3s
7.2 kV
Contactor
Technology
Vacuum
Vacuum
Rated voltage Ur (kV)
7.2
7.2
Surge withstand voltage Up (kV) 60
63
VCB
Contactor
Switching sequence
O-3 min-CO-3 min-CO O/C
O-0.3 s-CO-3 min-CO
O-0.3 s-CO-15 s-CO
Closing time (ms)
90 - 120
90 - 120
Nominal frequency (Hz)
50 - 60
50 - 60
Opening time (ms)
< 61
< 61
Rated current Ir (A)
1000 - 2000
400
10.000
1.000.000
Short circuit current Isc (kA)
25 - 31.5
9
Number of switching
operations
Short circuit duration Tk (s)
3
1
Service temperature (°C)
- 25 / + 40
- 25 / + 40
Offer extension
PE90437
PE90601
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
Sepam series 10, 20, 40, 60 , 80
PE90488
or
MICOMP series 10, 20, 30, 40
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
A-33
Medium Voltage Distribution
HMX36 /HMX36 by HMX36
Original brand:
GEC Alstom
PE90602
ECOFIT™ proposal
With ECOFIT™, a true extended life time
1980
2003
On-going
HMX36
HMX36
ECOFIT™ solution
HMX36
Commercialisation
End of commercialisation
End of spare parts
Offer extension
PE90437
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
Sepam series 10, 20, 40, 60 , 80
PE90488
or
A-34
MICOMP series 10, 20, 30, 40
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
Medium Voltage Distribution
HP / HP - W - TW - TM by HVX
Original brand:
Concordia Sprecher
ECOFIT™ proposal
With ECOFIT™, a true extended life time
PE90653
1976
2002
2007
2012
HP - W - TW - TM
HVX
ECOFIT™ solution
Commercialisation
PE90652
HP - W - TW - TM Circuit Breaker
End of commercialisation
End of spare parts
Main technical characteristics
HP - W - TW - TM
Rated current (Ir)
Short circuit current (Isc)
Rated voltage Un (50/60 Hz)
HVX
Circuit Breaker
1250 - 3150 A
12.5 - 40 kA
7.2 - 12 kV
800 - 1250 A
8.4 - 21.7 kA
24 kV
HVX
Technology
Vacuum
Rated voltage Ur (kV)
12 - 24
HVX
Switching sequence
O-0.3 s-CO-3 min-CO
Surge withstand voltage Up (kV) 75 - 125
Closing time (ms)
45 - 63
Nominal frequency (Hz)
50 - 60
Opening time (ms)
35 - 53
Rated current Ir (A)
630 - 2500
16 - 31.5
Number of switching
operations
10.000
Short circuit current Isc (kA)
Short circuit duration Tk (s)
3 Service temperature (°C)
- 5 / + 40
Offer extension
PE90437
PE90654
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
Sepam series 10, 20, 40, 60 , 80
PE90488
or
MICOMP series 10, 20, 30, 40
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
A-35
Medium Voltage Distribution
HWX / HWX by HWX
Original brand:
GEC, GEC Alsthom, Alstom, Areva
ECOFIT™ proposal
With ECOFIT™, a true extended life time
PE91027
1996
2016
2020
HWX
HWX
ECOFIT™ solution
Commercialisation
PE91027
HWX Circuit Breaker
End of commercialisation
End of spare parts
Main technical characteristics
HWX
Rated current (Ir)
Short circuit current (Isc)
Rated voltage Un (50/60 Hz)
HWX
Circuit Breaker
3150 A
50 kA
12 kV
HWX
Technology
Vacuum
Rated voltage Ur (kV)
12 HWX
Switching sequence
O-0.3 s-CO-3 min-CO
Surge withstand voltage Up (kV) 75 Closing time (ms)
≤ 60
Nominal frequency (Hz)
50 Opening time (ms)
≤ 60
Rated current Ir (A)
3150
Short circuit current Isc (kA)
50
Number of switching
operations
Short circuit duration Tk (s)
3 Service temperature (°C)
- 5 / + 40
Offer extension
PE90437
PE91027
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
Sepam series 10, 20, 40, 60 , 80
PE90488
or
A-36
MICOMP series 10, 20, 30, 40
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
Medium Voltage Distribution
K104/ K104 by LF - Evolis
Original brand:
GOST standard
ECOFIT™ proposal
PE91043
With ECOFIT™, a true extended life time
<1980
2000
2012
K104 LF-Evolis
ECOFIT™ solution
Commercialisation
End of commercialisation &
End of spare parts
PE91006
K104
Circuit Breaker
Main technical characteristics
K104
LF - Evolis
Circuit Breaker
Rated current (Ir)
Short circuit current (Isc)
Rated voltage Un (50/60 Hz)
LF
Evolis
Technology
SF6
Vacuum
Rated voltage Ur (kV)
6 - 10 6 - 17.5 630 - 1000 - 1600 A
25 -31.5 kA
6 - 10 kV
LF
Evolis
Switching sequence
O-0,3 c-C/O-15 c-C/O O-0,3 c-C/O-15 c-C/O
3 min
3 min
Surge withstand voltage Up (kV) 60 - 75
60 - 75
Closing time (ms)
< 65
< 65
Nominal frequency (Hz)
50
50 Opening time (ms)
< 50
< 50
Rated current Ir (A)
630 - 1250 - 2000
630 - 1250 - 1600
20.000
25 - 31.5
25 - 31.5
Number of switching
operations
10000
Short circuit current Isc (kA)
Short circuit duration Tk (s)
3 3 Service temperature (°C)
- 25 / + 40
- 25 / + 40
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
A-37
Medium Voltage Distribution
KAD/ KAD/KAC by VMX-540
Original brand:
GEC, GEC Alsthom, Alstom
ECOFIT™ proposal
PE91028
With ECOFIT™, a true extended life time
< 1980
2002
2012
KAD
VMX-540
ECOFIT™ solution
KAD
Circuit Breaker
End of commercialisation
End of spare parts
PE91028
Commercialisation
Main technical characteristics
KAD
VMX-540
Circuit Breaker
Rated current (Ir)
Short circuit current (Isc)
Rated voltage Un (50/60 Hz)
800 A
25 kA
12 kV
VMX-540
Technology
Vacuum
Rated voltage Ur (kV)
12 VMX-540
Switching sequence
O-0.3 s-CO-3 min-CO
Surge withstand voltage Up (kV) 75 Closing time (ms)
≤ 60
Nominal frequency (Hz)
50 Opening time (ms)
≤ 60
Rated current Ir (A)
1250
Short circuit current Isc (kA)
25
Number of switching
operations
Short circuit duration Tk (s)
3 Service temperature (°C)
A-38
- 5 / + 40
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
Medium Voltage Distribution
KRU / KRU 2-10 by LF - Evolis
Original brand:
GOST standard
ECOFIT™ proposal
With ECOFIT™, a true extended life time
PE91007
<1970
2000
2012
KRU 2-10 LF-Evolis
ECOFIT™ solution
Commercialisation
End of commercialisation &
End of spare parts
PE91008
KRU 2-10
Circuit Breaker
Main technical characteristics
KRU 2-10
LF - Evolis
Circuit Breaker
Rated current (Ir)
Short circuit current (Isc)
Rated voltage Un (50/60 Hz)
LF
Evolis
Technology
SF6
Vacuum
Rated voltage Ur (kV)
6 - 17.5 6 - 10 630 - 1000 - 1600 A
25 -31.5 kA
6 - 10 kV
LF
Evolis
Switching sequence
O-0,3 c-C/O-15 c-C/O O-0,3 c-C/O-15 c-C/O
3 min
3 min
Surge withstand voltage Up (kV) 60 - 75
60 - 75
Closing time (ms)
< 65
< 65
Nominal frequency (Hz)
50
50 Opening time (ms)
< 50
< 50
Rated current Ir (A)
630 - 1250 - 2000
630 - 1250 - 1600
20.000
40 - 50 (6kV) - 40 (10 kV) 25 - 45
Number of switching
operations
10000
Short circuit current Isc (kA)
Short circuit duration Tk (s)
3 Service temperature (°C)
- 25 / + 40
- 25 / + 40
3 Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
A-39
Medium Voltage Distribution
MC500 / SF1T by SF1T
Original brand:
Merlin Gerin
PE91005
ECOFIT™ proposal
With ECOFIT™, a true extended life time
PE90397
1997
2015
2034
SF1T
SF1T
ECOFIT™ solution
Commercialisation
End of commercialisation
End of spare parts
PE90399
SF1T
Circuit Breaker
Main technical characteristics
SF1T
Rated current (Ir)
Short circuit current (Isc)
Rated voltage Un (50/60 Hz)
SF1T
Circuit Breaker
1250 - 4000 A
12.5 - 16.5 kA
24 kV
SF1T
Technology
SF6
Rated voltage Ur (kV)
24 SF1T
Switching sequence
O-3 min-CO-3 min-CO
O-0.3 s-CO-15 s-CO
O-0.3 s-CO-3 min-CO
Surge withstand voltage Up (kV) 125 Closing time (ms)
70
Nominal frequency (Hz)
50 - 60
Opening time (ms)
50
Rated current Ir (A)
1250 - 4000
10.000
Short circuit current Isc (kA)
12.5 - 16.5
Number of switching
operations
Short circuit duration Tk (s)
1
Service temperature (°C)
- 5 / + 40
Offer extension
PE90437
PE91005
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
Sepam series 10, 20, 40, 60 , 80
PE90488
or
A-40
MICOMP series 10, 20, 30, 40
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
Medium Voltage Distribution
Metalclad switchgear / DST2 & 5 by DST2V & 5V
Original brand:
Federal Pioneer
PE90618-2
ECOFIT™ proposal
With ECOFIT™, a true extended life time
1970
1985
1999
2000
PE90618
DST2 & 5 - DST2
FP
DST2V & 5V
ECOFIT™ solution
Commercialisation
End of commercialisation
End of spare parts
PE90619
DST2 & 5 Circuit Breaker
Main technical characteristics
DST2V & 5V Circuit Breaker
Rated current (Ir)
3-phase MVA rating
Rated voltage Un
DST2 V
DST5 V
Technology
Vacuum
Vacuum
Rated voltage Ur (kV)
5
15
Surge withstand voltage Up (kV) 60
DST2 & 5
DST2
1200 - 3000 A
250 - 350 MVA
5 kV
1200 - 3000 A
500 - 750 MVA
15 kV
DST2 V
DST5 V
Rated current Ir (A)
1200 - 3000
1200 - 3000
3-phase rating (MVA)
350
500 - 750
95
PE90619
Offer extension
Magnum circuit breakers correctly interface with
the existing breaker compartment components and
maintain safety interlocks inherent in the original
equipment design.
• New circuit breakers are installed in existing switchgear.
• Original footprint is left intact, saving time and money.
• Installation expense is a fraction of new equipment costs.
• Less down time for installation.
• Enhanced equipment reliability.
• Manufactured with new components.
• Undergoes complete factory testing.
• Backed by our standard equipment warranty.
• New, easy-to-maintain operating mechanism.
• No bulky arc chutes to handle and maintain.
• Reduced need for difficult to obtain spare parts.
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
Optional capabilities
• Increased fault current interruption rating.
• Relay upgrade, improved accuracy and repeatability,
and performance.
• Power metering, monitoring and communication.
• Ground and test devices available for various types
of switchgear.
Closed Door Electric Racking Mechanism
• Arc flash hazard reduced with remote operation.
• Maintenance shutdown time is significantly reduced.
• No storage space is required for the electrical racking
system.
• Require just a common 120VAC, 15A outlet for power up.
A-41
Medium Voltage Distribution
Motorstart P50D / C - CD by R400 - R400D - CTV1
Original brand:
Merlin Gerin
PE90390
ECOFIT™ proposal
With ECOFIT™, a true extended life time
1960
1980
1988
1992
PE90391
C - CD
R400 - R400D - CTV1
ECOFIT™ solution
Commercialisation
PE90392
C - CD
Circuit Breaker
End of commercialisation
End of spare parts
Main technical characteristics
C - CD
Rated current (Ir)
Short circuit current (Isc)
Rated voltage Un (50/60 Hz)
R400 - R400D - CTV1
Circuit Breaker
80 - 200 A
50 kA (with fuses)
7.2 kV
R400
R400D
CTV1
Technology
SF6
SF6
Vacuum
Rated voltage Ur (kV)
7.2
7.2
7.2
R400
R400D
CTV1
Switching sequence
Surge withstand voltage Up (kV) 60 60
60
Closing time (ms)
75 - 155
75 - 155
60 - 80
Nominal frequency (Hz)
50 - 60
50 - 60
50 - 60
Opening time (ms)
20 - 50
20 - 50
20 - 30
Rated current Ir (A)
80 - 250
80 - 250
80 - 250
Number of switching
50 (with fuses) 50 (with fuses) 50 (with fuses) operations
300.000
100.000
200.000
Short circuit current Isc (kA)
Short circuit duration Tk (s)
3 - 25 / + 40
- 25 / + 40
- 25 / + 40
3 3 Service temperature (°C)
Offer extension
PE90437
PE90390
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
Sepam series 10, 20, 40, 60 , 80
PE90488
or
A-42
MICOMP series 10, 20, 30, 40
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
Medium Voltage Distribution
Motorstart P500D / C1 - CD1 by R400 - R400D - CTV1
Original brand:
Merlin Gerin
PE90393
ECOFIT™ proposal
With ECOFIT™, a true extended life time
1971
1988
1998
C1 - CD1
R400 - R400D - CTV1
ECOFIT™ solution
Commercialisation
PE90395
C1 - CD1
Circuit Breaker
End of commercialisation
End of space parts
Main technical characteristics
C1 - CD1
Rated current (Ir)
Short circuit current (Isc)
Rated voltage Un (50/60 Hz)
R400 - R400D - CTV1
Circuit Breaker
80 - 250 A
50 kA (with fuses)
7.2 kV
R400
R400D
CTV1
Technology
SF6
SF6
Vacuum
Rated voltage Ur (kV)
7.2
7.2
7.2
R400
R400D
CTV1
Switching sequence
Surge withstand voltage Up (kV) 60 60
60
Closing time (ms)
75 - 155
75 - 155
60 - 80
Nominal frequency (Hz)
50 - 60
50 - 60
50 - 60
Opening time (ms)
20 - 50
20 - 50
20 - 30
Rated current Ir (A)
80 - 250
80 - 250
80 - 250
Number of switching
50 (with fuses) 50 (with fuses) 50 (with fuses) operations
300.000
100.000
200.000
Short circuit current Isc (kA)
Short circuit duration Tk (s)
3 - 25 / + 40
- 25 / + 40
- 25 / + 40
3 3 Service temperature (°C)
Offer extension
PE90437
PE90393
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
Sepam series 10, 20, 40, 60 , 80
PE90488
or
MICOMP series 10, 20, 30, 40
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
A-43
Medium Voltage Distribution
MX51 & MX81 by MX51 & MX81
Original brand:
GEC Alstom
ECOFIT™ proposal
PE90603
With ECOFIT™, a true extended life time
1974
1981
2012
MX51 & MX81
MX51 & MX81
ECOFIT™ solution
Commercialisation
End of commercialisation
End of spare parts
MX51 & MX81
Main technical characteristics
MX51
Rated current (Ir)
Short circuit current (Isc)
Rated voltage Un (50/60 Hz)
MX81
630 - 2000 A
25 - 31.5 kA
3.6 kV
630 - 2000 A
25 - 31.5 kA
17.5 kV
MX51 & MX81
Technology
Vacuum
Rated voltage Ur (kV)
Up to 17.5
630 - 1250 A
12.5 - 20 kA
3.6 kV
630 - 1250 A
12.5 - 20 kA
17.5 kV
MX51 & MX81
Switching sequence
O-3 min-CO-3 min-CO
O-0.3 s-CO-3 min-CO
O-0.3 s-CO-15 s-CO
Surge withstand voltage Up (kV) Up to 115
Closing time (ms)
< 52
Nominal frequency (Hz)
50 - 60
Opening time (ms)
< 61
Rated current Ir (A)
630 - 2000
10.000
Short circuit current Isc (kA)
Up to 31.5
Number of switching
operations
Short circuit duration Tk (s)
3
Service temperature (°C)
- 25 / + 40
Offer extension
PE90437
PE90603
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
Sepam series 10, 20, 40, 60 , 80
PE90488
or
A-44
MICOMP series 10, 20, 30, 40
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
Medium Voltage Distribution
Normabloc N1347 / HL by HVX -FPX
Original brand:
Delle Alsthom
PE90481
ECOFIT™ proposal
With ECOFIT™, a true extended life time
PE90482
1975
1981
1991
2009
HL HVX - FPX ECOFIT™ solution
Commercialisation
End of commercialisation
End of spare parts
PE90483
HL Circuit Breaker
Main technical characteristics
HL Rated current (Ir)
Short circuit current (Isc)
Rated voltage Un (50/60 Hz)
HVX - HPX Circuit Breaker
HVX
FPX
Technology
Vacuum
SF6
Rated voltage Ur (kV)
17.5
17.5
630 - 1250 A
25 & 40 kA
17.5 kV
HVX
FPX
Switching sequence
O-3 min-CO-3 min-CO O-3 min-CO-3 min-CO
O-0.3 s-CO-3 min-CO O-0.3 s-CO-3 min-CO
O-15 s-CO
O-0.3 s-CO-15s-CO
O-0.3 s-CO-15s-CO
Surge withstand voltage Up (kV) 95
95
Closing time (ms)
35 - 53
50
Nominal frequency (Hz)
50 - 60
50 - 60
Opening time (ms)
45 - 63
50
Rated current Ir (A)
630 - 1250
630 - 1250
10000
16 - 40
12.5 - 40
Number of switching
operations
10000
Short circuit current Isc (kA)
Short circuit duration Tk (s)
3
3 Service temperature (°C)
- 5 / + 40
- 5 / + 40
Offer extension
PE90437
PE90481
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
Sepam series 10, 20, 40, 60 , 80
PE90488
or
MICOMP series 10, 20, 30, 40
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
A-45
Medium Voltage Distribution
Normaclad PX / FPX by FPX
Original brand:
GEC ALSTHOM
PE90765
ECOFIT™ proposal
With ECOFIT™, a true extended life time
1993
1997
2024
PE90857
FPX
FPX
ECOFIT™ solution
Commercialisation
End of commercialisation
End of spare parts
PE90857
FPX
Circuit Breaker
Main technical characteristics
FPX
Rated current (Ir)
Short circuit current (Isc)
Rated voltage Un (50/60 Hz)
FPX
Circuit Breaker
Up to 3150 A
40 kA
12 kV
Up to 2500 A
31.5 kA
24 kV
FPX
FPX
Technology
SF6
SF6
Rated voltage Ur (kV)
12
24
Switching sequence
O-3mn-CO-3mn-CO
CO-0.3 s-CO-15 s-CO
O-0.3 s-CO-3mn-CO
Surge withstand voltage Up (kV) 75
125
Closing time (ms)
50 Nominal frequency (Hz)
50 - 60
50 - 60
Opening time (ms)
50
Rated current Ir (A)
Up to 3150
Up to 2500
Up to 40
Up to 31.5
Number of switching
operations
10.000
Short circuit current Isc (kA)
Short circuit duration Tk (s)
3
3
Service temperature (°C)
- 5 / + 40
Offer extension
PE90437
PE90765
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
Sepam series 10, 20, 40, 60 , 80
PE90488
or
A-46
MICOMP series 10, 20, 30, 40
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
Medium Voltage Distribution
PX 12 - 24 / FPX by FPX
Original brand:
Alstom
PE90765
ECOFIT™ proposal
With ECOFIT™, a true extended life time
1993
1997
1998
2023
PE90766
FPX
FP
FPX
ECOFIT™ solution
Commercialisation
End of commercialisation
End of spare parts
PE90766
FPX Circuit Breaker
Main technical characteristics
FPX Rated current (Ir)
Short circuit current (Isc)
Rated voltage Un (50/60 Hz)
FPX Circuit Breaker
3150 A
40 kA/3s
12 kV
2500 A
31.5 kA/3s
17.5 kV
FPX
2500 A
31.5 kA/3s
24 kV
FPX
Technology
SF6
SF6
SF6
Switching sequence
Rated voltage Ur (kV)
12
17.5
24
O-3 min-CO-3 min-CO
O-0.3 s-CO-3 min-CO
O-0.3 s-CO-15 s-CO
Surge withstand voltage Up (kV) 100
80
80
Closing time (ms)
50
50
50
Nominal frequency (Hz)
50 - 60
Rated current Ir (A)
3150
50 - 60
50 - 60
Opening time (ms)
50
50
50
2500
2500
10.000
10.000
10.000
40
31.5
31.5
Number of switching
operations
Short circuit current Isc (kA)
Short circuit duration Tk (s)
3
3
3
Service temperature (°C)
- 5 / + 40
- 5 / + 40
- 5 / + 40
Offer extension
PE90437
PE90765
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
Sepam series 10, 20, 40, 60 , 80
PE90488
or
MICOMP series 10, 20, 30, 40
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
A-47
Medium Voltage Distribution
PIX SF6 / FPX by FPX
Original brand:
ALSTOM
PE90859
ECOFIT™ proposal
With ECOFIT™, a true extended life time
1994
2014
2024
PE90857
FPX
FPX
ECOFIT™ solution
Commercialisation
End of commercialisation
End of spare parts
PE90857
FPX
Circuit Breaker
Main technical characteristics
FPX
Rated current (Ir)
Short circuit current (Isc)
Rated voltage Un (50/60 Hz)
FPX
Circuit Breaker
Up to 3150 A
40 kA
12 kV
Up to 2500 A
31.5 kA
17.5 kV
FPX
Up to 2500 A
31.5 kA
24 kV
FPX
Technology
SF6
SF6
SF6
Rated voltage Ur (kV)
12
17.5
24
Switching sequence
O-3mn-CO-3mn-CO
CO-0.3 s-CO-15 s-CO
O-0.3 s-CO-3mn-CO
Surge withstand voltage Up (kV) 75
95
125
Closing time (ms)
50 Nominal frequency (Hz)
50 - 60
50 - 60
50 - 60
Opening time (ms)
50
Rated current Ir (A)
Up to 3150
Up to 2500
Up to 2500
Up to 40
Up to 31.5
Up to 31.5
Number of switching
operations
10.000
Short circuit current Isc (kA)
Short circuit duration Tk (s)
3
3
3
Service temperature (°C)
- 5 / + 40
Offer extension
PE90437
PE90859
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
Sepam series 10, 20, 40, 60 , 80
PE90488
or
A-48
MICOMP series 10, 20, 30, 40
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
Medium Voltage Distribution
PNX36 / HVX36 by HVX36
Original brand:
AEG
PE90819
ECOFIT™ proposal
With ECOFIT™, a true extended life time
PE90818
1994
2015
HVX36
HVX36 ECOFIT™ solution
Commercialisation
End of commercialisation
PE90650
HVX36
Circuit Breaker
Main technical characteristics
HVX36
Rated current (Ir)
Intensity short circuit (Isc)
Rated voltage Un (50/60 Hz)
HVX36 Circuit Breaker
630 - 2500 A
25 - 31.5 kA
36 kV
HVX36
Technology
Vacuum
Rated voltage Ur (kV)
36
HVX36
Switching sequence
O-0.3 s-CO-3min-CO
Surge withstand voltage Up (kV) 70
Closing time (ms)
45 - 63
Nominal frequency (Hz)
50 - 60
Opening time (ms)
35 - 53
Rated current Ir (A)
630 - 2500
10.000
Short circuit current Isc (kA)
25 - 31.5
Number of switching
operations
Short circuit duration Tk (s)
3
Service temperature (°C)
- 5 / + 40
Offer extension
PE90437
PE90819
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
Sepam series 10, 20, 40, 60 , 80
PE90488
or
MICOMP series 10, 20, 30, 40
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
A-49
Medium Voltage Distribution
R / IMC - MC - FAL - IFAL - VA - VAA - IVA - BAL - ALF - AL - TG
Original brand: AEG
by VA - VAA - Contactor
PE90554
ECOFIT™ proposal
With ECOFIT™, a true extended life time
PE90555
1973
1985
1990
1999
2003
2007
2013
IMC - MC
FAL - IFAL
BAL - ALF - AL
VA - VAA - IVA - TG
IMC - MC - FAL - IFAL - VA - VAA - IVA - BAL - ALF - AL - TG
Circuit Breaker
End of
cialisation
IMC -MC
Commercialisation
VA - VAA - Contactor
ECOFIT™ solution
End of commercialisation
PE90556
End of spare parts
Main technical characteristics
IMC - MC - FAL - IFAL - VA - VAA - IVA - BAL - ALF - AL - TG
Rated current (Ir)
Short circuit current (Isc)
Rated voltage Un (50/60 Hz)
VA - VAA
Circuit Breaker
1250 - 4000 A
16 - 50 kA
12 - 36 kV
VA - VAA - Contactor
Technology
Vacuum
Rated voltage Ur (kV)
12 - 24
VA - VAA - Contactor
Switching sequence
O-0.3 s-CO-3min-CO
Surge withstand voltage Up (kV) 75 - 125
Closing time (ms)
20
Nominal frequency (Hz)
50 - 60
Opening time (ms)
20 - 50
Rated current Ir (A)
630 - 3550
10.000
Short circuit current Isc (kA)
16 - 50 Number of switching
operations
Short circuit duration Tk (s)
3
Service temperature (°C)
- 5 / + 40
Offer extension
PE90437
PE90554
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
Sepam series 10, 20, 40, 60 , 80
PE90488
or
A-50
MICOMP series 10, 20, 30, 40
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
Medium Voltage Distribution
RSW/ RSW by LF - Evolis
Original brand:
GOST standard
ECOFIT™ proposal
PE91009
With ECOFIT™, a true extended life time
<1980
2000
2012
RSW LF-Evolis
ECOFIT™ solution
Commercialisation
End of commercialisation &
End of spare parts
PE91010
RSW
Circuit Breaker
Main technical characteristics
RSW
LF - Evolis
Circuit Breaker
Rated current (Ir)
Short circuit current (Isc)
Rated voltage Un (50/60 Hz)
LF
Evolis
Technology
SF6
Vacuum
Rated voltage Ur (kV)
6 - 17.5 6 - 10 630 - 1250 A
25 -31.5 kA
6 - 10 kV
LF
Evolis
Switching sequence
O-0,3 c-C/O-15 c-C/O O-0,3 c-C/O-15 c-C/O
3 min
3 min
Surge withstand voltage Up (kV) 60 - 75
60 - 75
Closing time (ms)
< 65
< 65
Nominal frequency (Hz)
50
50 Opening time (ms)
< 50
< 50
Rated current Ir (A)
630 - 1250
630 - 1250
20.000
25 - 31.5
25 - 31.5
Number of switching
operations
10000
Short circuit current Isc (kA)
Short circuit duration Tk (s)
3 3 Service temperature (°C)
- 25 / + 40
- 25 / + 40
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
A-51
Medium Voltage Distribution
Siclad / MAG II by LF1 - LF2
Original brand:
Ansaldo
PE90580
ECOFIT™ proposal
With ECOFIT™, a true extended life time
1969
1997
2009
PE90581
MAG II
LF1 - LF2
ECOFIT™ solution
Commercialisation
MAG II
Circuit Breaker
End of commercialisation
End of spare parts
PE90582
Main technical characteristics
MAG II
Rated current (Ir)
Short circuit current (Isc)
Rated voltage Un (50/60 Hz)
LF1 - LF2
Circuit Breaker
MAG II - 6 - 250/400
MAG II - 10 - 500
MAG II - 15 - 6 - 300/350
630 - 1250 - 2000 A
20 - 48 kA
6 kV
630 - 1250 - 2000 A
20 - 28 kA
10 kV
630 - 1250 - 2000 A
12 - 30 kA
15 kV
LF1
LF2*
LF1
Technology
SF6
SF6
Rated voltage Ur (kV)
7.2 - 12
7.2 - 12 - 17.5
Switching sequence
O-3 min-CO-3 min-CO
O-0.3 s-CO-3 min-CO
O-0.3 s-CO-15 s-CO
LF2*
Surge withstand voltage Up (kV) 60 - 75
60 - 75 - 95
Closing time (ms)
< 72
< 72
Nominal frequency (Hz)
50 - 60
50 - 60
Opening time (ms)
< 54
< 54
Rated current Ir (A)
630 - 1250
2000
10.000
10.000
- 25 / + 40
- 25 / + 40
Short circuit current Isc (kA)
31.5
40
Number of switching
operations
Short circuit duration Tk (s)
3 3 Service temperature (°C)
* For Siclad panels 730mm & 850mm wide
Offer extension
PE90437
PE90580
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
Sepam series 10, 20, 40, 60 , 80
PE90488
or
A-52
MICOMP series 10, 20, 30, 40
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
Medium Voltage Distribution
Solenarc DSE Metal-Clad switchgear / DSE by Magnum CB
Original brand:
Square D
PE90539
ECOFIT™ proposal
With ECOFIT™, a true extended life time
<1975
1988
1999
2005
PE90540
DSE
Magnum CB
ECOFIT™ solution
Commercialisation
End of commercialisation
End of spare parts
PE90541
DSE
Circuit Breaker
Main technical characteristics
DSE Rated current (Ir)
3-phase MVA rating
Rated voltage Un
Magnum CB
Circuit Breaker
1200 - 3000 A
250 MVA
5 kV
5MGSB
15MGSB
Technology
Vacuum
Vacuum
Rated voltage Ur (kV)
5
15
95
Surge withstand voltage Up (kV) 60
1200 - 3000 A
250 - 1000 MVA
15 kV
5MGSB
15MGSB
Rated current Ir (A)
1200
1200 - 3000
3-phase rating (MVA)
250
250 - 1000
Interrupting time (ms)
100
60
Offer extension
PE90437
PE90539
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
Sepam series 10, 20, 40, 60 , 80
PE90488
or
MICOMP series 10, 20, 30, 40
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
A-53
Medium Voltage Distribution
Venus / GI - GL by LF1 - LF3
Nuova Magrini Galileo
ECOFIT™ proposal
With ECOFIT™, a true extended life time
GI - GL
Circuit Breaker
1989
2000
PE90583
PE90583
Original brand:
2008
2010
GI - GL
LF1 - LF3
ECOFIT™ solution
End of commercialisation
End of spare parts
PE90585
Commercialisation
Main technical characteristics
GI
LF1 - LF3
Circuit Breaker
GL
Rated current (Ir)
630 - 1250 A
630 - 1250 A
1600 - 3150 A
1600 - 3150 A
1600 - 3150 A
1600 - 3150 A
Short circuit current (Isc)
Rated voltage Un (50/60 Hz)
12.5 - 31.5 kA
7 - 12 kV
12 - 25 kA
17 - 24 - 36 kV
50 kA
7 kV
20 - 40 kA
12 kV
20 - 40 kA
24 kV
20 - 31.5 kA
36 kV
LF1
LF3
Technology
SF6
SF6
Panel width (mm)
600
900
Rated voltage Ur (kV)
12
17.5
LF1
Switching sequence
LF3
O-3 min-CO-3 min-CO
O-0.3 s-CO-3 min-CO
O-0.3 s-CO-15 s-CO
Surge withstand voltage Up (kV) 75
125
Closing time (ms)
< 72
< 72
Nominal frequency (Hz)
50 - 60
50 - 60
Opening time (ms)
< 54
< 54
Rated current Ir (A)
630 - 1250
1600 - 1250
10.000
10.000
Short circuit current Isc (kA)
31.5
50
Number of switching
operations
Short circuit duration Tk (s)
3
3
Service temperature (°C)
- 25 / + 40
- 25 / + 40
Offer extension
PE90437
PE90583
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
Sepam series 10, 20, 40, 60 , 80
PE90488
or
A-54
MICOMP series 10, 20, 30, 40
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
Medium Voltage Distribution
VISAX / BLV by BLV
Original brand:
GEC Alsthom
PE90219
ECOFIT™ proposal
With ECOFIT™, a true extended life time
1996
2015
2025
PE90865
BLV
BLV
ECOFIT™ solution
Commercialisation
End of commercialisation
End of spare parts
BLV
Circuit Breaker
PE90865
Main technical characteristics
BLV
Rated current (Ir)
Short circuit current (Isc)
Rated voltage Un (50/60 Hz)
BLV
Circuit Breaker
400 - 1250 A
16 - 40 kA
7.2 kV
400 - 1250 A
16 - 40 kA
12 kV
BLV
400 - 1250 A
16 - 40 kA
17.5 kV
BLV
Technology
SF6
SF6
SF6
SF6
Rated voltage Ur (kV)
7.2
12
17.5
24
Switching sequence
O-3mn-CO-3mn-CO
O-0.3 s-CO-3mn-CO
O-0.3 s-CO-15 s-CO
Surge withstand voltage Up (kV) 125
125
125
125
Closing time (ms)
51 Nominal frequency (Hz)
50 - 60
50 - 60
50 - 60
Opening time (ms)
40
50 - 60
400 - 1250 A
16 - 31.5 kA
24 kV
Rated current Ir (A)
400 - 1250 400 - 1250 400 - 1250 400 - 1250
16 - 40
16 - 40
16 - 40
16 - 31.5
Number of switching
operations
10.000
Short circuit current Isc (kA)
Short circuit duration Tk (s)
3
3
3
3
Service temperature (°C)
- 25 / + 40
Offer extension
PE90437
PE90219
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
Sepam series 10, 20, 40, 60 , 80
PE90488
or
MICOMP series 10, 20, 30, 40
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
A-55
Medium Voltage Distribution
VM6 DM12 / FB4 by SF1
Original brand:
Merlin Gerin
PE90421
ECOFIT™ proposal
With ECOFIT™, a true extended life time
PE90422
1975
1993
2009
2010
FB4
SF1
ECOFIT™ solution
Commercialisation
End of commercialisation
End of spare parts
PE90423
FB4
Circuit Breaker
Main technical characteristics
FB4
SF1
Circuit Breaker
Rated current (Ir)
400 - 1250 A
400 - 1250 A
400 - 1250 A
400 - 1250 A
Short circuit current (Isc)
Rated voltage Un (50/60 Hz)
12.5 - 31.5 kA
7.2 kV
12.5 - 25 kA
12 kV
12.5 - 20 kA
17.5 kV
12.5 - 20 kA
24 kV
SF1
Technology
SF6
Rated voltage Ur (kV)
Up to 24 SF1
Switching sequence
O-3 min-CO-3 min-CO
O-0.3 s-CO-3 min-CO
O-0.3 s-CO-15 s-CO
Surge withstand voltage Up (kV) Up to 125
Closing time (ms)
< 65
Nominal frequency (Hz)
50 - 60
Opening time (ms)
< 50
Rated current Ir (A)
400 - 1250
10.000
Short circuit current Isc (kA)
12.5 - 25
Number of switching
operations
Short circuit duration Tk (s)
3 Service temperature (°C)
- 25 / + 40
Offer extension
PE90437
PE90421
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
Sepam series 10, 20, 40, 60 , 80
PE90488
or
A-56
MICOMP series 10, 20, 30, 40
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
Medium Voltage Distribution
VMX / VMX by VMX
Original brand:
GEC Alstom
PE90692
ECOFIT™ proposal
With ECOFIT™, a true extended life time
1987
2004
PE90764
VMX
VMX
ECOFIT™ solution
Commercialisation
PE90764
VMX
Circuit Breaker
End of commercialisation
Main technical characteristics
VMX
Rated current (Ir)
Short circuit current (Isc)
Rated voltage Un (50/60 Hz)
VMX
Circuit Breaker
630 - 2000 A
Up to 25 kA/3s
11 kV
VMX
Technology
Vacuum
Rated voltage Ur (kV)
11
VMX
Switching sequence
O-3 min-CO-3 min-CO
O-0.3 s-CO-3 min-CO
O-0.3 s-CO-15 s-CO
Surge withstand voltage Up (kV) 95
Closing time (ms)
< 52
Nominal frequency (Hz)
50 - 60
Opening time (ms)
< 61
Rated current Ir (A)
630 - 1250
25
Number of switching
operations
10.000
Short circuit current Isc (kA)
Short circuit duration Tk (s)
3
Service temperature (°C)
- 25 / + 40
Offer extension
PE90437
PE90692
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
Sepam series 10, 20, 40, 60 , 80
PE90488
or
MICOMP series 10, 20, 30, 40
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
A-57
Medium Voltage Distribution
WBA / VA - VAA - ECA - BAL - AL by VA - VAA - Contactor
Original brand:
AEG
PE90657
ECOFIT™ proposal
With ECOFIT™, a true extended life time
PE90665
1989
2006
VA - VAA - ECA - BAL - AL
VA - VAA - Contactor
ECOFIT™ solution
Commercialisation
PE90666
VA - VAA - ECA - BAL - AL
Circuit Breaker
Main technical characteristics
Rated current (Ir)
Short circuit current (Isc)
Rated voltage Un (50/60 Hz)
VA - VAA
Circuit Breaker
BAL - AL
VAA
ECA
VA
250 A
20 kA
3.6 - 12 kV
630 - 1250 A
16 - 25 kA
12 - 24 kV
630 - 2500 A
20 - 50 kA
12 - 24 kV
630 - 2500 A
20 - 50 kA
12 - 38 kV
VA - VAA - Contactor
Technology
Vacuum
Rated voltage Ur (kV)
12 - 24
VA - VAA - Contactor
Switching sequence
O-0.3 s-CO-3 s-CO
Surge withstand voltage Up (kV) 75 - 125
Closing time (ms)
20
Nominal frequency (Hz)
50 - 60
Opening time (ms)
20 - 50
Rated current Ir (A)
630 - 2500
10.000
Short circuit current Isc (kA)
25 - 31.5 Number of switching
operations
Short circuit duration Tk (s)
3 Service temperature (°C)
- 5 / + 40
Offer extension
PE90437
PE90658
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
Sepam series 10, 20, 40, 60 , 80
PE90488
or
A-58
MICOMP series 10, 20, 30, 40
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
Medium Voltage Distribution
WBB / VA - VAA - ECA - BAL - AL by VA - VAA - Contactor
Original brand:
AEG
PE90659
ECOFIT™ proposal
With ECOFIT™, a true extended life time
1994
2004
2013
2014
PE90663
BAL - AL
ECA
VA - VAA
VAA
ECOFIT™ solution
VA - VAA - ECA - BAL - AL
Circuit Breaker
PE90664
Commercialisation
End of commercialisation
End of spare parts
Main technical characteristics
Rated current (Ir)
Short circuit current (Isc)
Rated voltage Un (50/60 Hz)
VA - VAA
Circuit Breaker
BAL - AL
VAA
ECA
VA
250 A
20 kA
3.6 - 12 kV
630 - 1250 A
16 - 25 kA
12 - 24 kV
630 - 2500 A
20 - 50 kA
12 - 24 kV
630 - 2500 A
20 - 50 kA
12 - 38 kV
VA - VAA - Contactor
Technology
Vacuum
Rated voltage Ur (kV)
12 - 15
VA - VAA - Contactor
Switching sequence
O-0.3 s-CO-3 s-CO
Surge withstand voltage Up (kV) 75 - 95
Closing time (ms)
20
Nominal frequency (Hz)
50 - 60
Opening time (ms)
20 - 50
Rated current Ir (A)
630 - 2500
10.000
Short circuit current Isc (kA)
25 - 31.5 Number of switching
operations
Short circuit duration Tk (s)
3 Service temperature (°C)
- 5 / + 40
Offer extension
PE90437
PE90660
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
Sepam series 10, 20, 40, 60 , 80
PE90488
or
MICOMP series 10, 20, 30, 40
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
A-59
Medium Voltage Distribution
WBD / VAA - VA - HVX by VAA - VA
Original brand:
AEG
PE90820
ECOFIT™ proposal
With ECOFIT™, a true extended life time
1992
2015
VA - VAA - HVX
PE90663
VA - VAA ECOFIT™ solution
Commercialisation
PE90821
VA - VAA - HVX
Circuit Breaker
End of commercialisation
Main technical characteristics
VA - VAA - HVX
Rated current (Ir)
Intensity short circuit (Isc)
Rated voltage Un (50/60 Hz)
VA - VAA Circuit Breaker
630 - 2500 A
25 - 31.5 kA
36 kV
VA - VAA
Technology
Vacuum
Rated voltage Ur (kV)
12
VA - VAA
Switching sequence
O-0.3 s-CO-3min-CO
Surge withstand voltage Up (kV) 80
Closing time (ms)
20
Nominal frequency (Hz)
50 - 60
Opening time (ms)
20 - 50
Rated current Ir (A)
630 - 3150
10.000
Short circuit current Isc (kA)
25 - 31.5
Number of switching
operations
Short circuit duration Tk (s)
3
Service temperature (°C)
- 5 / + 40
Offer extension
PE90437
PE90820
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
Sepam series 10, 20, 40, 60 , 80
PE90488
or
A-60
MICOMP series 10, 20, 30, 40
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
Medium Voltage Distribution
WK (C/E/B/A) / VA - MC - BAL by VA - VAA - Contactor
Original brand:
AEG
PE90661
ECOFIT™ proposal
With ECOFIT™, a true extended life time
PE90661
1987
2003
2013
MC
BAL
VA VA - VAA - Contactor
ECOFIT™ solution
VA - MC -BAL
PE90650
Commercialisation
End of commercialisation
End of spare parts
Main technical characteristics
VA - MC - BAL
Rated current (Ir)
Short circuit current (Isc)
Rated voltage Un (50/60 Hz)
VA - VAA - Contactor
630 - 2500 A
31.5 - 50 kA
Up to 24 kV
VA - VAA - Contactor
Technology
Vacuum
Rated voltage Ur (kV)
3.6 - 24 VA - VAA - Contactor
Switching sequence
O-0.3 s-CO-3 s-CO
Surge withstand voltage Up (kV) 60 - 110
Closing time (ms)
20
Nominal frequency (Hz)
50 - 60
Opening time (ms)
20 - 50
Rated current Ir (A)
400 - 4000
10.000
Short circuit current Isc (kA)
10 - 50 Number of switching
operations
Short circuit duration Tk (s)
3
Service temperature (°C)
- 5 / + 40
Offer extension
PE90437
PE90661
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
Sepam series 10, 20, 40, 60 , 80
PE90488
or
MICOMP series 10, 20, 30, 40
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
A-61
Medium Voltage Distribution
YSF6 / YSF6 by YSF6 Evolis
Original brand:
Yorkshire Switchgear
PE90607
ECOFIT™ proposal
With ECOFIT™, a true extended life time
1981
2001
2004
2021
PE90608
YSF6
YSF6 Evolis
ECOFIT™ solution
Commercialisation
End of commercialisation
End of spare parts
PE90609
YSF6 Circuit Breaker
Main technical characteristics
YSF6
Rated current (Ir)
Short circuit current (Isc)
Rated voltage Un (50/60 Hz)
YSF6 EVOLIS
Circuit Breaker
630 - 1250 A
Up to 25 kA
12 kV
YSF6 Evolis
Technology
Vacuum
Rated voltage Ur (kV)
11
YSF6 Evolis
Switching sequence
O-3 min-CO-3 min-CO
O-0.3 s-CO-3 min-CO
O-0.3 s-CO-15 s-CO
Surge withstand voltage Up (kV) 75
Closing time (ms)
< 50
Nominal frequency (Hz)
50 - 60
Opening time (ms)
< 65
Rated current Ir (A)
630 - 1250
10.000
Short circuit current Isc (kA)
25
Number of switching
operations
Short circuit duration Tk (s)
3 Service temperature (°C)
- 25 / + 40
Offer extension
PE90437
PE90607
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
Sepam series 10, 20, 40, 60 , 80
PE90488
or
A-62
MICOMP series 10, 20, 30, 40
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
Medium Voltage Distribution
AHA panel by AHA panel
Original brand:
AEG - Alsthom - Alstom
ECOFIT™ proposal
PE91041
With ECOFIT™, a true extended life time
1997
2005
2012
AHA
AHA
ECOFIT™ solution
Commercialisation
End of commercialisation
End of spare parts
AHA
Main technical characteristics
AHA Rated current (Ir)
Intensity short circuit (Isc)
Rated voltage Un (50/60 Hz)
630 - 1250 A
25 - 31.5 kA
12 - 17.5 kV
AHA
Rated insulation level (kV)
AHA
12 - 17.5
Rated current of busbar (A)
1250
Rated power frequency
38
withstand voltage/1mn (kVrms)
Rated short time withstand
current (3s) (kA)
25 - 31.5
Lightning impulse withstand
voltage (peak value) (kVp)
95
Internal Arc Classification 31.5
(1s) (AFLR)
Overall dimensions (wxhxd)
(mm)
700x2330x1450
Ingress Protection degree Enclosure IP42 - Compartment IP2X
(IP)
Offer extension
PE90437
PE91041
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
Sepam series 10, 20, 40, 60 , 80
PE90488
or
MICOMP series 10, 20, 30, 40
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
A-63
Medium Voltage Distribution
DNF7 panel by DNF7 panel
Original brand:
Alsthom
PE90748
ECOFIT™ proposal
With ECOFIT™, a true extended life time
1983
2013
2014
DNF7
DNF7
ECOFIT™ solution
Commercialisation
End of commercialisation
DNF7
Main technical characteristics
DNF7
Rated current (Ir)
Intensity short circuit (Isc)
Rated voltage Un (50/60 Hz)
400 - 2000 A
31.5 kA
36 kV
DNF7
Rated insulation level (kV)
DNF7
36
Rated current of busbar (A)
400 - 1250 (2500***)
Rated power frequency
70
withstand voltage/1mn (kVrms)
Rated short time withstand
current (4s) (kA)
16 - 31.5
Lightning impulse withstand
voltage (peak value) (kVp)
170
Internal Arc Classification 25 kA
(0.2s) (AFLR)
Overall dimensions (wxhxd)
(mm)
1300x2250*x2300**
Ingress Protection degree Enclosure IP3X
(IP)
* 2900 mm with busbar compartment - ** 2500 mm with internal arc withstand, 2750 mm with cables voltage compartment - *** With forced cooling (on request)
Offer extension
PE90437
PE90748
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
Sepam series 10, 20, 40, 60 , 80
PE90488
or
A-64
MICOMP series 10, 20, 30, 40
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
Medium Voltage Distribution
Fluair F100-200 panel by Fluair F100-200 panel
Original brand:
Merlin Gerin
ECOFIT™ proposal
PE90409
With ECOFIT™, a true extended life time
1980
1998
F100-200
F100-200
ECOFIT™ solution
Commercialisation
End of commercialisation
F100/200
Main technical characteristics
Rated current (Ir)
Short circuit current (Isc)
Rated voltage Un (50/60 Hz)
F100
F200
630 - 3150 A
25 - 50 kA
7.2 kV
630 - 3150 A
25 - 50 kA
12 - 17.5 kV
F100-200
Rated insulation level (kV)
F100-200
7.2 - 12 - 17.5
Rated current of busbar (A)
Up to 3150
Rated power frequency
20 - 28 - 38
withstand voltage/1mn (kVrms)
Rated short time withstand
current (3s) (kA)
Up to 50
Lightning impulse withstand
voltage (peak value) (kVp)
60 - 75 - 95
Internal Arc Classification
(1s) (AFLR)
Overall dimensions (wxhxd)
(mm)
≤1250A: 650x2100x1455/1700
2500 - 3150A: 900x2100x1700
Ingress Protection degree Enclosure IP3X
(IP)
Offer extension
PE90437
PE90677
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
Sepam series 10, 20, 40, 60 , 80
PE90488
or
MICOMP series 10, 20, 30, 40
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
A-65
Medium Voltage Distribution
PIX panel by PIX panel
Original brand:
Alstom
PE90217
ECOFIT™ proposal
With ECOFIT™, a true extended life time
PIX
PIX
ECOFIT™ solution
Commercialisation
End of commercialisation
PIX
Main technical characteristics
PIX
Rated current (Ir)
Short circuit current (Isc)
Rated voltage Un (50/60 Hz)
Up to 3150 A
40 kA/3s
12 kV
Up to 2500 A
31.5 kA/3s
17.5 kV
PIX
Rated insulation level (kV)
12
Up to 2500 A
31.5 kA/3s
24 kV
PIX
17.5
24
Rated current of busbar (A)
Up to 3150
Up to 2500
Up to 2500
Rated power frequency
28 withstand voltage/1mn (kVrms)
38
50
Rated short time withstand
current (3s) (kA)
40
31.5
31.5
Lightning impulse withstand
voltage (peak value) (kVp)
75
95
125
Internal Arc Classification 40
(1s) (AFLR)
40
40
Overall dimensions (wxhxd)
(mm)
1000x2130x1405 - 1000x2330x1605 1000x2330x1605
Ingress Protection degree IP3X
(IP)
IP3X
IP3X
* With forced cooling (on request)
Offer extension
PE90437
PE90217
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
Sepam series 10, 20, 40, 60 , 80
PE90488
or
A-66
MICOMP series 10, 20, 30, 40
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
Medium Voltage Distribution
PNX36 panel by PNX36 panel
Original brand:
Areva
PE90819
ECOFIT™ proposal
With ECOFIT™, a true extended life time
2009
2015
PNX36
PNX36
ECOFIT™ solution
Commercialisation
End of commercialisation
PNX36
Main technical characteristics
PNX36
Rated current (Ir)
Short circuit current (Isc)
Rated voltage Un (50/60 Hz)
630 - 2500 A
10 - 25 kA
36 kV
PNX36
Rated insulation level (kV)
PNX36
36
Rated current of busbar (A)
630 - 2500*
Rated power frequency
70
withstand voltage/1mn (kVrms)
Rated short time withstand
current (4s) (kA)
82
Lightning impulse withstand
voltage (peak value) (kVp)
170
Internal Arc Classification Arcing due to internal fault according to
(1s) (AFLR)
IEC 60298, 31.5 kA 1s, Type of accessibility A
Overall dimensions (wxhxd)
(mm)
120x2500x1600
Ingress Protection degree
(IP)
* With forced cooling (on request)
Offer extension
PE90437
PE90819
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
Sepam series 10, 20, 40, 60 , 80
PE90488
or
MICOMP series 10, 20, 30, 40
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
A-67
Medium Voltage Distribution
PX12-24 panel by PX12-24 panel
Original brand:
Alstom
PE90677
ECOFIT™ proposal
With ECOFIT™, a true extended life time
1993
1997
PX12-24 PX12-24
ECOFIT™ solution
Commercialisation
End of commercialisation
PX12-24
Main technical characteristics
Rated current (Ir)
Short circuit current (Isc)
Rated voltage Un (50/60 Hz)
PX12
PX24
400 - 3150 A
25 - 40 kA
12 kV
400 - 2500 A
16 - 25 - 31.5 kA
24 kV
PX12
PX24
PX12
PX24
12
24
Rated current of busbar (A)
630 - 3150
630 - 2500
Rated power frequency
28
withstand voltage/1mn (kVrms)
50
Rated short time withstand
current (3s) (kA)
25 - 40
25 - 31.5
Lightning impulse withstand
voltage (peak value) (kVp)
75
125
Internal Arc Classification 25
(1s) (AFLR)
Overall dimensions (mm)
(W x H x D)
<1250A: 650x2135x1320 ≤2000A: 750x2135x1320 Ingress Protection degree Enclosure IP3X
≤2000A: 750x2135x1320 >2000A: 900x2335x1570 (IP)
>2000A: 900x2135x1320
Rated insulation level (kV)
25
Enclosure IP3X
Offer extension
PE90437
PE90677
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
Sepam series 10, 20, 40, 60 , 80
PE90488
or
A-68
MICOMP series 10, 20, 30, 40
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
Medium Voltage Distribution
R panel by R panel
Original brand:
AEG
PE90655
ECOFIT™ proposal
With ECOFIT™, a true extended life time
1973
1990
1999
2000
R
R
ECOFIT™ solution
Commercialisation
End of commercialisation
End of spare parts
R
Main technical characteristics
R
Rated current (Ir)
Short circuit current (Isc)
Rated voltage Un (50/60 Hz)
400 - 2500 A
Up to 40 kA/3s
12 kV
400 - 2500 A
Up to 25 kA/3s
24 kV
R
Rated insulation level (kV)
R
12 - 24
Rated current of busbar (A)
630 - 3350
Rated power frequency
28 - 50
withstand voltage/1mn (kVrms)
Rated short time withstand
current (4s) (kA)
40 - 125
Lightning impulse withstand
voltage (peak value) (kVp)
75 - 125
Internal Arc Classification PEHLA
(1s) (AFLR)
Overall dimensions (wxhxd)
(mm)
700, 800, 1000, 1400, 1600x2330, 2420x1100,
1250, 1300, 1450
Ingress Protection degree Standard IP2X
(IP)
On request IP3X, IP4X
Offer extension
PE90437
PE90655
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
Sepam series 10, 20, 40, 60 , 80
PE90488
or
MICOMP series 10, 20, 30, 40
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
A-69
Medium Voltage Distribution
VISAX panel by VISAX panel
Original brand:
GEC Alstom
PE90219
ECOFIT™ proposal
With ECOFIT™, a true extended life time
1996
2015
2029
VISAX
VISAX
ECOFIT™ solution
Commercialisation
End of spare parts
VISAX
Main technical characteristics
VISAX
Rated current (Ir)
Short circuit current (Isc)
Rated voltage Un (50/60 Hz)
Up to 2500 A
25 kA/3s
12 kV
Up to 2500 A
25 kA/3s
17.5 kV
VISAX
Rated insulation level (kV)
12
Up to 2500 A
25 kA/3s
24 kV
VISAX
17.5
24
Rated current of busbar (A)
Up to 2500
Up to 2500
Up to 2500
Rated power frequency
28 withstand voltage/1mn (kVrms)
38
50
Rated short time withstand
current (3s) (kA)
25
25
25
Lightning impulse withstand
voltage (peak value) (kVp)
75
95
125
Internal Arc Classification 25
(1s) (AFLR)
25
25
Overall dimensions (wxhxd)
(mm)
800 - 1100x2150 - 2650x1250 - 1540
Ingress Protection degree IP3X - IP4X
(IP)
IP3X - IP4X
IP3X - IP4X
* With forced cooling (on request)
Offer extension
PE90437
PE90219
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
Sepam series 10, 20, 40, 60 , 80
PE90488
or
A-70
MICOMP series 10, 20, 30, 40
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
Medium Voltage Distribution
VMX panel by VMX panel
Original brand:
GEC Alstom
PE90692
ECOFIT™ proposal
With ECOFIT™, a true extended life time
1987
2004
VMX
VMX
ECOFIT™ solution
Commercialisation
End of commercialisation
VMX
Main technical characteristics
VMX
Rated current (Ir)
Short circuit current (Isc)
Rated voltage Un (50/60 Hz)
630 - 2000 A
Up to 25 kA/3s
11 kV
VMX
Rated insulation level (kV)
VMX
12
Rated current of busbar (A)
Up to 2000
Rated power frequency
28 - 35
withstand voltage/1mn (kVrms)
Rated short time withstand
current (4s) (kA)
Up to 26.3
Lightning impulse withstand
voltage (peak value) (kVp)
75
Internal Arc Classification 25
(3s) (AFLR)
Overall dimensions (wxhxd)
(mm)
606 - 540x2000 - 2000x1867 - 1360
Ingress Protection degree IP3X
(IP)
* With forced cooling (on request)
Offer extension
PE90437
PE90692
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
Sepam series 10, 20, 40, 60 , 80
PE90488
or
MICOMP series 10, 20, 30, 40
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
A-71
Medium Voltage Distribution
WBA panel by WBA panel
Original brand:
AEG
ECOFIT™ proposal
PE90657
With ECOFIT™, a true extended life time
1989
2006
WBA
WBA
ECOFIT™ solution
Commercialisation
WBA
End of commercialisation
Main technical characteristics
WBA
Rated current (Ir)
Short circuit current (Isc)
Rated voltage Un (50/60 Hz)
630 - 2500 A
16 - 25 kA & 20 - 50 kA
12 - 24 kV
WBA
Rated insulation level (kV)
630 - 2500 A
20 - 50 kA
12 - 38 kV
WBA
12 - 24
Rated current of busbar (A)
630 - 2500
Rated power frequency
28 - 50
withstand voltage/1mn (kVrms)
Rated short time withstand
current (4s) (kA)
63 - 80
Lightning impulse withstand
voltage (peak value) (kVp)
75 - 125
Internal Arc Classification PEHLA 31.5 kA
(1s) (AFLR)
Overall dimensions (wxhxd)
(mm)
600/800/1000x2330x1250/1300
Ingress Protection degree Standard IP2X
(IP)
On request IP3X, IP4X
Offer extension
PE90437
PE90658
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
Sepam series 10, 20, 40, 60 , 80
PE90488
or
A-72
MICOMP series 10, 20, 30, 40
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
Medium Voltage Distribution
WBB panel by WBB panel
Original brand:
AEG
ECOFIT™ proposal
PE90659
With ECOFIT™, a true extended life time
1990
2006
WBB
WBB
ECOFIT™ solution
Commercialisation
End of commercialisation
WBB
Main technical characteristics
WBB
Rated current (Ir)
Short circuit current (Isc)
Rated voltage Un (50/60 Hz)
630 - 2500 A
20 - 50 kA
12 - 24 - 38 kV
WBB
Rated insulation level (kV)
WBB
12 - 15
Rated current of busbar (A)
630 - 2500
Rated power frequency
28 - 38
withstand voltage/1mn (kVrms)
Rated short time withstand
current (4s) (kA)
63 - 80
Lightning impulse withstand
voltage (peak value) (kVp)
75 - 95
Internal Arc Classification PEHLA 31.5 kA
(1s) (AFLR)
Overall dimensions (wxhxd)
(mm)
600, 800, 1000x2330x1250, 1500
Ingress Protection degree Standard IP2X
(IP)
On request IP3X, IP4X
Offer extension
PE90437
PE90660
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
Sepam series 10, 20, 40, 60 , 80
PE90488
or
MICOMP series 10, 20, 30, 40
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
A-73
Medium Voltage Distribution
WBD panel by WBD panel
Original brand:
AEG
PE90820
ECOFIT™ proposal
With ECOFIT™, a true extended life time
1992
2015
WBD
WBD ECOFIT™ solution
Commercialisation
End of commercialisation
WBD
Main technical characteristics
WBD
Rated current (Ir)
Short circuit current (Isc)
Rated voltage Un (50/60 Hz)
630 - 3150 A
80 kA
12 kV
WBD
Rated insulation level (kV)
WBD
12
Rated current of busbar (A)
630 - 3150*
Rated power frequency
28
withstand voltage/1mn (kVrms)
Rated short time withstand
current (4s) (kA)
80
Lightning impulse withstand
voltage (peak value) (kVp)
80
Internal Arc Classification PEHLA 31.5 kA
(1s) (AFLR)
Overall dimensions (wxhxd)
(mm)
600, 800x3000x1750
Ingress Protection degree IP 2X even for open door and modul in
(IP)
disconnecting position, IP 3X to the busbar,
outside IP 52 possible
* With forced cooling (on request)
Offer extension
PE90437
PE90820
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
Sepam series 10, 20, 40, 60 , 80
PE90488
or
A-74
MICOMP series 10, 20, 30, 40
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
Medium Voltage Distribution
WK panel by WK panel
Original brand:
AEG
ECOFIT™ proposal
PE90661
With ECOFIT™, a true extended life time
1987
2003
WK
WK
ECOFIT™ solution
Commercialisation
End of commercialisation
WK
Main technical characteristics
WK
Rated current (Ir)
Short circuit current (Isc)
Rated voltage Un (50/60 Hz)
630 - 2500 A
20 - 50 kA/3s
12 - 24 - 38 kV
WK
Rated insulation level (kV)
WK
3.6 - 24
Rated current of busbar (A)
630 - 4000
Rated power frequency
28 - 38
withstand voltage/1mn (kVrms)
Rated short time withstand
current (4s) (kA)
63 - 80
Lightning impulse withstand
voltage (peak value) (kVp)
110
Internal Arc Classification PEHLA 31.5 kA
(1s) (AFLR)
Overall dimensions (wxhxd)
(mm)
600/1060x2330x1700/2100
Ingress Protection degree Standard IP2X
(IP)
On request IP3X, IP4X
Offer extension
PE90437
PE90661
Energy management: replacement of the old protection relay (Schneider Electric or competitors)
Sepam series 10, 20, 40, 60 , 80
PE90488
or
MICOMP series 10, 20, 30, 40
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
A-75
Medium Voltage Distribution
Cradle to Cradle / All breaker types Withdrawable CB by Evolis MC cassette
Original brand:
All
ECOFIT™ proposal
All breaker types
Compatible with
all open Air
Insulated
Switchgear legacy
and no legacy
cubicles
with minimum
inside panel
width ≥ 560 mm
With ECOFIT™, a true extended life time
PE57994
This solution consist in fitting a cradle inside an existing panel.
- It is particularly adapted for non Schneider Installed Base.
- ECOFIT™ solution with shutters and mechanical interlocks embedded.
- Only the fixed connections (between the cradle and existing busbar) are customized.
- Only the width of the existing panel has to be considered.
Main technical characteristics
All types
Rated current (Ir)
Short circuit current (Isc)
Rated voltage Un (50/60 Hz)
Evolis
Circuit Breaker
630 - 1250 A
Up to 31.5 kA
7.2 - 12 kV
630 - 2500 A
Up to 40 kA
7.2 - 12 - 17.5 kV
Evolis
MC1
MC2
MC3
Evolis
MC1
Technology
Vacuum
Vacuum
Vacuum
Switching sequence
Rated voltage Ur (kV)
7.2 - 12
7.2 - 12 - 17.5
7.2 - 12 - 17.5
O-3 min-CO-3 min-CO
O-0.3 s-CO-3 min-CO
O-0.3 s-CO-15 s-CO
Surge withstand voltage Up (kV) 60 - 75
60 - 75 - 95
60 - 75 - 95
Closing time (ms)
< 65
< 65
< 65
Nominal frequency (Hz)
50 - 60
50 - 60
50 - 60
Opening time (ms)
< 50
< 50
< 50
Rated current Ir (A)
630 - 1250
630 - 1250
630 - 2500
Up to 31.5
Up to 40
Up to 40
Number of switching
operations
2.000 (for Isc= 40 kA class M1) - 10.000
Short circuit current Isc (kA)
Short circuit duration Tk (s)
3 3 1 Service temperature (°C)
- 25 / + 40
240
240
550
DE57194EN
285
H
805
370
Weight (kg)
300
W
A-76
Cassette
Phase to phase (mm)
Dimensions (mm)
321
611
D
E
W
H
D
MC2
- 25 / + 40
MC3
- 25 / + 40
MC1
MC2
MC3
145
556
980
1223
222
185
686
980
1223
255
240
886
980
1223
326
100
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
Medium Voltage Distribution
Cradle to Cradle / All breaker types Withdrawable CB by F400 cassette
Original brand:
All
ECOFIT™ proposal
All breaker types
Compatible with
all open Air
Insulated
Switchgear legacy
and no legacy
cubicles
with minimum
inside panel
width ≥ 1105 mm
With ECOFIT™, a true extended life time
DE57396
This solution consist in fitting a cradle inside an existing panel.
- It is particularly adapted for non Schneider Installed Base.
- ECOFIT™ solution with shutters and mechanical interlocks embedded.
- Only the fixed connections (between the cradle and existing busbar) are customized.
- Only the width of the existing panel has to be considered.
Main technical characteristics
All types
Rated current (Ir)
Short circuit current (Isc)
Rated voltage Un (50/60 Hz)
F400
Circuit Breaker
1250 - 2500 A
Up to 40kA
24 - 36 kV
F400 - SF
F400 cassette
Technology
SF6
SF6
Rated voltage Ur (kV)
24 - 36
40.5
1250 A
Up to 31.5 kA
40.5 kV
F400 - SF
F400 cassette
Switching sequence
O-3 min-CO-3 min-CO O-3 min-CO-3 min-CO
O-0.3 s-CO-3 min-CO O-0.3 s-CO-3 min-CO
O-0.3 s-CO-15 s-CO O-0.3 s-CO-15 s-CO
Surge withstand voltage Up (kV) 125 - 170
185
Closing time (ms)
< 65
< 65
Nominal frequency (Hz)
50 - 60
50 - 60
Opening time (ms)
< 50
< 50
Rated current Ir (A)
1250 - 2500
1250
10000
25 - 40
31.5
Number of switching
operations
10000
Short circuit current Isc (kA)
Short circuit duration Tk (s)
3
3
Service temperature (°C)
- 25 / + 40
- 25 / + 40
PE57431
Cassette
Dimensions (mm)
Weight (kg)
A
B
C
1250 A
2500A - 3000 A
738
540
2030
750
752
533
2030
850
New panel technical characteristics
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
A-77
Low Voltage
Distribution
Low Voltage Distribution
Contents
LV Circuit Breaker or Contactor
B Control
Compact C801-C1251
DA
DS
H Series
Masterpact M
SE
Selpact
Unelec CNP
Visucompact CM
Associated offers Energy Management
Associated offers Source-changeover systems
B-2
B-3
B-4
B-5
B-6
B-7
B-8
B-9
B-10
B-11
B-12
B-12
LV Drawer
T140
MB400
Offer Extension Drawer components
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
B-13
B-14
B-15
B-1
Low Voltage Distribution
B Control by Masterpact NT - NW
Original brand:
Nuova Magrini Galileo
ECOFIT™ proposal
PE90573
With ECOFIT™, a true extended life time
1972
1990
2005
2009
B Control (B1-35/B1-50/B3-50/B3-75/B3-90/B4-100)
Masterpact NT - NW
B Control
Circuit Breaker
ECOFIT™ solution
End of commercialisation
End of spare parts
PE90574
Commercialisation
Main technical characteristics
Masterpact NW
Circuit Breaker
Rated operational voltage (V AC 50/60 Hz) Ue
Rated current (A) In 40° C
Ultimate breaking capacity (kA rms, 220/415V AC 50/60Hz) Icu
B Control
Masterpact NT - NW
660 V
800 - 4000 A
32 - 100 kA
690 V
800 - 4000 A
42 - 150 kA
PE90574
B Control ECOFIT™ solution
The ECOFIT™ B Control solution enables to benefit from all the enhanced features of Masterpact NT or NW circuit
breakers and accessories.
Active Energy Management™ programme that includes an energy metering system
• Identify the device,
• Indicate status conditions,
• Control the device (with communication auxiliaries)
• Setting of the protection and alarm functions.
B-2
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
Low Voltage Distribution
Compact C801 - C1251 by Compact NS800 - NS1250
Original brand:
Merlin Gerin
With ECOFIT™, a true extended life time
PE90572
PE90430
ECOFIT™ proposal
1993
2007
2009
Compact C801 - C1251
Compact NS800 - NS1251
C801 - C1251
Circuit Breaker
ECOFIT™ solution
PE90431
Commercialisation
End of commercialisation
End of spare parts
Main technical characteristics
Rated operational voltage (V AC 50/60 Hz) Ue
Rated current (A) In 40° C
Ultimate breaking capacity (kA rms, 220/415V AC 50/60Hz) Icu
NS801 - NS1251
Circuit Breaker
Compact C801 - C1251
Compact NS800 - NS1251
690 V
800 - 1250 A
50 - 150 kA
690 V
800 - 1250 A
50 - 150 kA
Compact C801 - C1251 ECOFIT™ solutions
DE90252
Plug & Play
The ECOFIT™ Compact Plug & Play solution lets you retrofit the latest generation of Compact NS circuit breakers in
the existing Compact C chassis with very short onsite servicing times.
Solution available for withdrawable type only, 3p & 4p, 800A to 1250A.
PE90257
PE90256
Compactkit
1 Removal
2 Replacement
The ECOFIT™ Compactkit solution enables to benefit from all the enhanced features
of Compact NS circuit breakers and accessories.
It requires total shutdown of the installation to access the busbars.
Solution available for fixed type, 3p & 4p, 800A to 1250A.
PE90571
DB402068
Active Energy Management™ programme that includes an energy metering system
• Identify the device,
• Indicate status conditions,
• Control the device (with communication auxiliaries)
• Setting of the protection and alarm functions.
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
B-3
Low Voltage Distribution
DA (DSA1 - DNA1 - DSA2 - DNA2 - DRA - DNAH)
Original brand: Merlin Gerin
by MASTERPACT NW08 -NW63
ECOFIT™ proposal
PE90424
With ECOFIT™, a true extended life time
1986
1986
1997
1998
DA (DSA1 - DNA1 - DSA2 - DNA2 - DRA - DNAH)
DA
Circuit Breaker
Masterpact NW
ECOFIT™ solution
PE90427
Commercialisation
End of commercialisation
End of spare parts
Main technical characteristics
Rated operational voltage (V AC 50/60 Hz) Ue
Rated current (A) In 40° C
Ultimate breaking capacity (kA rms, 220/415V AC 50/60Hz) Icu
Masterpact NW
Circuit Breaker
DA
Masterpact NW
660 V
630 - 6300 A
42 - 100 kA
690 V
800 - 6300 A
42 - 150 kA
DA ECOFIT™ solution
PE90427
The ECOFIT™ DA solution enables to benefit from all the enhanced features of Masterpact NW circuit breakers and
accessories.
It requires total shutdown of the installation to access the busbars.
The kit solution (including circuit breaker) is available for fixed and withdrawable types, 3p & 4p,
630 to 6300A.
B-4
PE90571
DB402068
Active Energy Management™ programme that includes an energy metering system
• Identify the device,
• Indicate status conditions,
• Control the device (with communication auxiliaries)
• Setting of the protection and alarm functions.
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
Low Voltage Distribution
DS by Masterpact NT - NW
Original brand:
Square D, Westinghouse
ECOFIT™ proposal
PE90537
With ECOFIT™, a true extended life time
1983
1998
2007
2013
DS (DS206 - DS416S/H - DS420 - DS308/508/608 - DS516/616/620)
Masterpact NT - NW
DS
Circuit Breaker
ECOFIT™ solution
End of commercialisation
End of spare parts
PE90249
Commercialisation
Main technical characteristics
Masterpact NT - NW
Circuit Breaker
Rated operational voltage (V AC 50/60 Hz) Ue
Rated current (A) In 40° C
Ultimate breaking capacity (kA rms, 600V AC 50/60Hz) Icu
DS
Masterpact NT - NW
600 V
800 - 2000 A
42 - 65 kA
600 V
800 - 2000 A
42 - 65 kA
DS ECOFIT™ solution
PE90249
The ECOFIT™ DS solutions fixed or draw-out types enable to benefit from all the enhanced features of Masterpact
NT or NW circuit breakers and accessories.
PE90571
DB402068
Active Energy Management™ programme that includes an energy metering system
• Identify the device,
• Indicate status conditions,
• Control the device (with communication auxiliaries)
• Setting of the protection and alarm functions.
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
B-5
Low Voltage Distribution
H Series by Masterpact NT - NW
Original brand:
Federal Pioneer
PE90615
ECOFIT™ proposal
With ECOFIT™, a true extended life time
1960
2001
2003
2013
H Series (H3 - HL3 - H2 - HL2 - 1000HF1)
Masterpact NT - NW
H Series
Circuit Breaker
ECOFIT™ solution
End of commercialisation
End of spare parts
PE90616
Commercialisation
Main technical characteristics
Masterpact NT - NW
Circuit Breaker
Rated operational voltage (V AC 50/60 Hz) Ue
Rated current (A) In 40° C
Ultimate breaking capacity (kA rms, 600V AC 50/60Hz) Icu
H Series
Masterpact NT - NW
600 V
600 - 4000 A
30 - 200* kA
600 V
800 - 4000 A
30 - 200* kA
* with fuse
H Series ECOFIT™ solution
PE90616
The ECOFIT™ H series solutions fixed or draw-out types enable to benefit from all the enhanced features of
Masterpact NT or NW circuit breakers and accessories.
B-6
PE90571
DB402068
Active Energy Management™ programme that includes an energy metering system
• Identify the device,
• Indicate status conditions,
• Control the device (with communication auxiliaries)
• Setting of the protection and alarm functions.
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
Low Voltage Distribution
Masterpact M08 - M63 by Masterpact NW08 -NW63
Original brand:
Merlin Gerin
ECOFIT™ proposal
035928
With ECOFIT™, a true extended life time
1986
2003
2004
2013
Masterpact M
Masterpact NW
Masterpact M
Circuit Breaker
ECOFIT™ solution
PE90249
Commercialisation
End of commercialisation
End of spare parts
Main technical characteristics
Rated operational voltage (V AC 50/60 Hz) Ue
Rated current (A) In 40° C
Ultimate breaking capacity (kA rms, 220/415V AC 50/60Hz) Icu
Masterpact NW
Circuit Breaker
Masterpact M
Masterpact NW
690 V
800 - 6300 A
40 - 150 kA
690 V
800 - 6300 A
42 - 150 kA
Masterpact M ECOFIT™ solutions
PE90452
Plug & Play
The ECOFIT™ Masterpact Plug & Play solution lets you retrofit the latest generation of Masterpact NW circuit
breakers in the existing Masterpact M chassis.
Solution available for withdrawable type only, 3p & 4p, 800 A to 3200 A.
PE90454
PE90453
Masterkit
1 Removal
2 Replacement
The ECOFIT™ Masterkit solution enables to benefit from all the enhanced features of
Masterpact NW circuit breakers and accessories without modifying the busbars. It
requires total shutdown of the installation to access the busbars.
Solution available for fixed and withdrawable types, 3p & 4p, 800 A to 6300 A.
PE90571
DB402068
Active Energy Management™ programme that includes an energy metering system
• Identify the device,
• Indicate status conditions,
• Control the device (with communication auxiliaries)
• Setting of the protection and alarm functions.
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
B-7
Low Voltage Distribution
SE by Masterpact NW
Original brand:
Square D
ECOFIT™ proposal
PE90538
With ECOFIT™, a true extended life time
1983
2003
2010
2011
SE
Masterpact NW
SE
Circuit Breaker
ECOFIT™ solution
End of commercialisation
End of spare parts
PE90435
Commercialisation
Main technical characteristics
Masterpact NW
Circuit Breaker
Rated operational voltage (V AC 50/60 Hz) Ue
Rated current (A) In 40° C
Ultimate breaking capacity (kA rms, 600V AC 50/60Hz) Icu
SE
Masterpact NW
600 V
1250 - 3000 A
100 kA
600 V
1250 - 3000 A
85 kA
PE90435
SE ECOFIT™ solution
The ECOFIT™ SE solutions fixed or draw-out types enable to benefit from all the enhanced features
of Masterpact NT or NW circuit breakers and accessories.
Active Energy Management™ programme that includes an energy metering system
• Identify the device,
• Indicate status conditions,
• Control the device (with communication auxiliaries)
• Setting of the protection and alarm functions.
B-8
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
Low Voltage Distribution
Selpact by Masterpact NT-NW
Original brand:
Merlin Gerin
ECOFIT™ proposal
PE90428
With ECOFIT™, a true extended life time
1973
1989
1997
2009
Selpact (DN2 - DS2 - DR2 - DRS2)
Masterpact NT-NW
Selpact
Circuit Breaker
ECOFIT™ solution
End of commercialisation
End of spare parts
PE90426
Commercialisation
Main technical characteristics
Rated operational voltage (V AC 50/60 Hz) Ue
Rated current (A) In 40° C
Ultimate breaking capacity (kA rms, 220/415V AC 50/60Hz) Icu
Masterpact NW
Circuit Breaker
Selpact
Masterpact NT-NW
660 V
630 - 3200 A
42 - 100 kA
690 V
800 - 3200 A
42 - 100 kA
Selpact ECOFIT™ solution
PE90426
The ECOFIT™ Selpact solutions enable to benefit from all the enhanced features of Masterpact NT or NW circuit
breakers and accessories.
Plug & Play
The Plug&Play solution is available for withdrawable type only, 3p & 4p, 630 to 1600 A.
Kit
The kit solution (including circuit breaker) is available for fixed and withdrawable types, 3p & 4p,
630 to 3200 A.
PE90571
DB402068
Active Energy Management™ programme that includes an energy metering system
• Identify the device,
• Indicate status conditions,
• Control the device (with communication auxiliaries)
• Setting of the protection and alarm functions.
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
B-9
Low Voltage Distribution
Unelec CNP by Masterpact NW
Original brand:
Unelec - Areva
ECOFIT™ proposal
PE90432
With ECOFIT™, a true extended life time
1968
1986
2007
2009
CNP
Masterpact NW
CNP
Circuit Breaker
ECOFIT™ solution
End of commercialisation
End of spare parts
PE90433
Commercialisation
Main technical characteristics
Rated operational voltage (V AC 50/60 Hz) Ue
Rated current (A) In 40° C
Ultimate breaking capacity (kA rms, 220/415V AC 50/60Hz) Icu
Masterpact NW
Circuit Breaker
CNP
Masterpact NW
660 V
1250 - 2000 A
36 - 100 kA
690 V
1250 - 2000 A
42 - 100 kA
CNP ECOFIT™ solution
PE90433
The ECOFIT™ CNP solution enables to benefit from all the enhanced features of Masterpact NW circuit breakers
and accessories.
The solution is suitable for fixed type and only for Normabloc 660 switchboard.
B-10
PE90571
DB402068
Active Energy Management™ programme that includes an energy metering system
• Identify the device,
• Indicate status conditions,
• Control the device (with communication auxiliaries)
• Setting of the protection and alarm functions.
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
Low Voltage Distribution
Visucompact CM by Masterpact NW
Original brand:
Merlin Gerin
PE90434
ECOFIT™ proposal
With ECOFIT™, a true extended life time
1985
2001
2005
2010
Visucompact CM
Masterpact NW
ECOFIT™ solution
Commercialisation
End of commercialisation
End of spare parts
PE90435
Visu Compact CM
Circuit Breaker
Main technical characteristics
Rated operational voltage (V AC 50/60 Hz) Ue
Rated current (A) In 40° C
Ultimate breaking capacity (kA rms, 220/415V AC 50/60Hz) Icu
Masterpact NW
Circuit Breaker
Visucompact CM
Masterpact NW
440 V
1250 - 2500 A
70 - 85 kA
690 V
1250 - 2500 A
42 - 100 kA
Visucompact CM ECOFIT™ solution
PE90435
The ECOFIT™ Visucompact solution enables to benefit from all the enhanced features of
Masterpact NW circuit breakers and accessories.
PE90571
DB402068
Active Energy Management™ programme that includes an energy metering system
• Identify the device,
• Indicate status conditions,
• Control the device (with communication auxiliaries)
• Setting of the protection and alarm functions.
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
B-11
Low Voltage Distribution
LV Circuit Breaker & Contactor - Associated offers
Energy Management - Micrologic control units - Measurements and protections
Available for
ECOFIT™ solutions
using Masterpact
NT/NW and
Compact NS
Micrologic
2
5
6
7
Type
A-E
A-E-P-H
A-E-P-H
A-P-H
Functions
Long time
+ instantaneous
Long time
+ short time
+ instantaneous
Long time
+ short time
+ instantaneous
+ earth fault
Long time
+ short time
+ instantaneous
+ earth leakage up to 3200A
A: Current measurements, fault indications, display and current maximeter.
Specificities: 6.0 provides earth fault protection (residual or Source Ground Return); 7.0 provides earth leakage protection.
E: A + Instantaneous measurement of power and energy without earth leakage protection.
P: A + Calculation of power and energy value, voltage measurement, and programmable protection
H: P + Harmonics
Energy Management - Communication
Available for
ECOFIT™ solutions
using Masterpact
NT/NW and
Compact NS
• Identify the device.
• Indicate status conditions.
• Control the device
(with the communicating auxiliairies).
• Setting of the protection and alarms functions.
1
24 V DC
7
1
Modbus network
2
CCM: Chassis
Communication Module
3
Breaker Universal Logic
Plug (ULP) cord
4
Breaker Communication
Module (BCM)
5
Prefabricated wiring
6
Micrologic trip unit
7
FDM21 display
8
Line terminator
2
8
3
Compact NS
or Masterpact
NT or NW
depending on
the device
5
4
6
Source-changeover systems
Available for
DA, Selpact and
Masterpact M
ECOFIT™ solutions
using Masterpact
NT/NW
B-12
Mechanical interlocking (2 types)
Automatic controllers
Using connecting rods or using
cables
IVE: Electrical interlocking
BA or UA automatic controllers
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
Low Voltage Distribution
T140 drawers by T140 drawers
Original brand:
Merlin Gerin
PE90687
ECOFIT™ proposal
With ECOFIT™, a true extended life time
1975
1990
1998
PE90688
T140 drawers
T140 drawers
ECOFIT™ solution
PE90685
T140 drawers
Commercialisation
End of commercialisation
End of spare parts
Main technical characteristics
T140 drawers
Rated operational voltage (V AC 50/60 Hz) Ue
Rated current (A) In 40° C
Number of modules
T140 drawers
T140 drawers
440 V
125 - 625 A
1 to 6
440 V
125 - 625 A
1 to 6
T140 drawers ECOFIT™ solution
PE90685
The ECOFIT™ T140 drawer solution enables to benefit from all the enhanced features of latest technology devices.
The drawer solutions are suitable for manual or electrical operations.
T140 drawers ECOFIT™ solution - Drawer components
102873
• Motor control command and protections - Functional units.
107395
• Control command auxiliaries for all types of drawers.
107429
11601
054047
106167
LC1D12
102870
102870
PB103354
• Electrical distribution - Functional units (NSX range with Micrologic).
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
B-13
Low Voltage Distribution
MB400 drawers by MB400 drawers
Original brand:
Merlin Gerin
PE90689
ECOFIT™ proposal
With ECOFIT™, a true extended life time
1991
2003
2013
PE90688
MB400 drawers
MB400 drawers
ECOFIT™ solution
PE90685
MB400 drawers
Commercialisation
End of commercialisation
End of spare parts
Main technical characteristics
MB400 drawers
Rated operational voltage (V AC 50/60 Hz) Ue
Rated current (A) In 40° C
Number of modules
MB400 drawers
MB400 drawers
440 V
125 - 625 A
1 to 6
440 V
125 - 625 A
1 to 6
MB400 drawers ECOFIT™ solution
PE90685
The ECOFIT™ MB400 drawer solution enables to benefit from all the enhanced features of latest technology
devices.
The drawer solutions are suitable for manual or electrical operations.
MB400 drawers ECOFIT™ solution - Drawer components
102873
• Motor control command and protections - Functional units.
107395
• Control command auxiliaries for all types of drawers.
107429
111601
054047
106167
LC1D12
102870
102870
PB103354
• Electrical distribution - Functional units (NSX range with Micrologic).
B-14
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
Low Voltage Distribution
LV Drawers - Associated offers
Specific spare parts: for any spare parts request for the fixe part, please contact your local
correspondant.
Available for
ECOFIT™ solutions
using Masterpact
NT/NW and
Compact NS
Drawer components
• Electrical distribution – Functional units (NSX range)
Micrologic
2.2 or 2.3
Type
Functions
LSI protection
5.2 or 5.3
6.2 or 6.3
A-E
A-E
LSI protection
Ammeter
Energy meter
LSI protection
Ammeter
Energy meter
A: Current measurements, fault indications, display and current maximeter. Specificities: 6.0 provides earth fault protection
(residual or Source Ground Return); 7.0 provides earth leakage protection.
E: A + Instantaneous measurement of power and energy without earth leakage protection.
• Motor control command and protections – Functional units
1 component motor feeder
2 components motor feeder
3 components motor feeder
Circuit breaker Contactor combination
Thermomagnetic circuit breaker +
Contactor
Thermomagnetic circuit breaker
or switch-disconnector fuse +
Contactor + Thermal protection
• Control command auxiliaries for all types of drawers
Miniature circuit-breaker
Protection auxiliary circuit
Auxiliary relays
Ground fault protection
Push buttons and lights
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
B-15
Protection relays
MV Protection relay
Contents
Protection relay upgrade benefits
CO
CDG
DPU 445
HCB
IAC
KCGG 122 & 142
M range - MCGG 11, 21 & 22
M range relay - MCTI 39-40
MCGG 62
Sepam 2000
VIP - RM6+
VIP & Vigirex - Various equipment
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
C-2
C-3
C-4
C-5
C-6
C-7
C-8
C-9
C-10
C-11
C-12
C-13
C-14
C-1
MV Protection relay
Protection upgrade benefits
Improve the performance of your system
with the latest technology in micro-processor
based integrated relays.
Why protection upgrade?
By replacing solid state and older type electromechanical protection relays
with technologically advanced multi-function microprocessor-based digital relays,
the performance accuracy and longevity of your system can be significantly improved.
With a number of different protection functions Schneider Electric's range of relays
can provide a range of options to include metering; communication; event capture;
monitoring and control. Units are self-diagnostic to provide enhanced reliability.
It is normally possible to use the existing current and potential transformers
and auxiliary digital relay inputs.
Schneider Electric's application based approach makes it easy to select
the appropriate relay for your needs.
What are the benefits?
Accuracy
System protection at the current level reduces unnecessary outages
and minimise stresses to equipment.
Increased accuracy of measurement assists in cost allocation
and understanding power demand requirements.
High reliability from advanced self supervision systems.
Flexibility
The integrated functions of the relay allow for communications and control
of the equipment either as a stand-alone unit or as part of networked systems.
All components in the protection chain are referenced and interface rapidly.
No constraints for integration in cubicles due to the compact size of the base unit.
C-2
Ease of use
Settings and adjustments are entered via the device's keypad
and visually displayed.
Reduced costs
The amalgamation of functions into one self-diagnosing meter
reduces expenditure and saves on space.
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
MV Protection relay
CO by MiCOM P111/115
Original brand:
General Electric
PE90866
ECOFIT™ proposal
With ECOFIT™, a true extended life time
2011
CO
MiCOM P111/115
CO
Protection Relay
ECOFIT™ solution
PE90867
Commercialisation
End of commercialisation
End of spare parts
Main technical characteristics
CO
MiCOM P111 & 115
Protection Relay
MiCOM P111/115
Case
FT-11 or FT 21
Fit FT-11 & FT 21 cutout
Replacement Type
-
1 for 3* with minimal rewiring
Type
Electromechanical
Numerical
Functionality
Single phase overcurrent
3 phase + Ground overcurrent
Power supply
-
24 VDC - 250 VDC
Communication
-
IEC 60870-5-103, Modbus RTU
*1 ECOFIT™ P111/115 – CO9 solution could replace 3 single phase CO9 units.
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
C-3
MV Protection relay
CDG - CAG - CTMM - CTMFM by MiCOM P1x –P2x
Original brand: Areva or older
or Vamp 5x
PE90881
ECOFIT™ proposal
With ECOFIT™, a true extended life time
CDG - CAG - CTM range relays
MiCOM or Vamp
ECOFIT™ solution
CDG type
Protection Relay
PE90882
Commercialisation
End of commercialisation
End of spare parts
Old relay models
ECOFIT™ solutions
CDG - CAG
MiCOM P122/P123
CTMM - CTMFM
MiCOM P211
CDG - CAG
VAMP 50/52
Descrition
Feeder protection relay
(Modbus/IEC103)
Motor protection relay
(Modbus/IEC103)
Feeder protection relay
(IEC 61850)
Main technical characteristics
MiCOM P
Protection Relay
C-4
CDG - CAG - CTM range relays
Case
Based on 1 or 3 independent units
Replacement Type
-
MiCOM or Vamp
20TE, 4U withdrawal case, mounted as
plug and play solution into the existing
DGC /CAG/ CTM range case
1 withdrawal relay for 3 individual units
Type
Electromechanical & induction disk relay type Numerical
Functionality
Selective earth & phase fault overcurrent 3 phase & earth overcurrent
Frequency range
Calibrated for 50 Hz or 60 Hz only
50 to 60 Hz +/- 20 %
Communication
-
IEC 60870-5-103, ModBus
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
MV Protection relay
DPU 445 by MiCOM P123
Original brand:
ABB
PE90872
ECOFIT™ proposal
With ECOFIT™, a true extended life time
2011
DPU 445
MiCOM P123
DPU 445
Protection Relay
ECOFIT™ solution
PE90873
Commercialisation
End of commercialisation
End of spare parts
Main technical characteristics
DPU 445
MiCOM P123
Protection Relay
MiCOM P123
Case
DPU 445
Fit existing cutout
Replacement Type
-
1 for 1 with minimal rewiring
Type
Digital
Numerical
Functionality
3 phase feeder
3 phase + ground feeder overcurrent
Power supply
24 VDC - 125 VDC
Communication
-
24 VDC - 250 VDC
Courier, DNP 3.0, IEC 60870-5-103,
ModBus RTU
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
C-5
MV Protection relay
HCB by MiCOM P521
Original brand:
ABB
PE90870
ECOFIT™ proposal
With ECOFIT™, a true extended life time
2009
HCB
MiCOM P521
HCB
Protection Relay
ECOFIT™ solution
PE90871
Commercialisation
End of commercialisation
Main technical characteristics
MiCOM P521
HCB
MiCOM P521
Protection Relay
C-6
End of spare parts
Case
FT-42
Fit existing cutout
Replacement Type
-
1 for 1 with minimal rewiring
Type
Electromechanical
Numerical
Functionality
3 phase differential
3 phase differential
Power supply
-
24 VDC - 250 VDC
Communication
-
IEC 60870-5-103, ModBus RTU
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
MV Protection relay
IAC by MiCOM P122
Original brand:
General Electric
PE90868
ECOFIT™ proposal
With ECOFIT™, a true extended life time
2011
IAC
MiCOM P122
IAC
Protection Relay
ECOFIT™ solution
PE90869
Commercialisation
End of commercialisation
End of spare parts
Main technical characteristics
MiCOM P122
Protection Relay
IAC
MiCOM P122
Fit S1, S2, L2 or M1 cutout
Case
S1, S2, L2 or M1
Replacement Type
-
1 for 3* with minimal rewiring
Type
Electromechanical
Numerical
Functionality
Single phase overcurrent
3 phase + Ground overcurrent
Power supply
-
Communication
-
24 VDC - 250 VDC
Courier, DNP3.0, IEC 60870-5-103,
ModBus RTU
*1 ECOFIT™ P122 – IAC solution could replace 3 single phase IAC units.
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
C-7
MV Protection relay
KCGG 122 & 142 by MiCOM P123R
Original brand:
Areva
PE90634
ECOFIT™ proposal
With ECOFIT™, a true extended life time
1997
2010
2011
2012
KCGG 122 & 142
MiCOM P123R
KCGG 122 & 142
Protection Relay
ECOFIT™ solution
End of commercialisation
End of support
PE90635
Commercialisation
MiCOM P123R
Protection Relay
Main technical characteristics
K range relay - KCGG 122 & 142
MiCOM P123R
20TE size flush mounting
Case
20TE size flush mounting
Installation
Withdrawable case
Withdrawable case
Language
English
Multilanguage
Communication
KBus / Courier
KBus / Courier, DNP3, IEC60870-5-103
Power supply
24 V / 125 VDC - 48 V / 250 VDC
24 V / 250 VDC - 48 V / 240 VDC
Digital input supply
48 VDC only
According to Power Supply (above)
ECOFIT™ KCGG 122 & 142 upgrades: diagnosis + implementation/installation of a fully industrialised solution
Improve the performance
of your system with
the latest technology in
micro-processor based
integrated relays.
C-8
Full retrofit solution
Sustainability
•Replacement of the protection relay and optimised maintenance.
•Access to spare parts, new communication protocols
and software facilities.
•Schneider Electric technical support and guarantee.
Manufacturer expertise
•Solution developed by our specialist engineers.
•Enhanced performance.
•Retrofit process optimised.
•Installation warranted by the manufacturer.
Consultancy and audit - Engineering solutions &
optimisation
Local support & assistance - Maintenance &
refurbishment
No mechanical or electrical impact on your
installation. Implementation and site test within a
very limited time.
New features enabled:
•Advanced HMI for local control functions.
•Standard communication protocols (Modbus,
IEC 60870-5-103, DNP3 or KBUS/Courier).
•Monitoring & Automation facilities.
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
MV Protection relay
M range - MCGG 11, 21 & 22 by MiCOM P120H
Original brand:
Areva
PE90752
ECOFIT™ proposal
With ECOFIT™, a true extended life time
< 1984
2010
2012
M range - MCGG 11, 21 & 22
MiCOM P120H
MCGG 22
Protection Relay
ECOFIT™ solution
End of spare parts
PE90635
Commercialisation
MiCOM P120H
Protection Relay
Main technical characteristics
M range relay - MCGG 11, 21 & 22
MiCOM P120H
Case
20TE size flush mounting
20TE size flush mounting
Installation
Withdrawable case
Withdrawable case
Language
English
Multilanguage
Communication
KBus / Courier
KBus / Courier, DNP3, IEC60870-5-103
Power supply
24 V / 125 VDC - 48 V / 250 VDC
24 V / 250 VDC - 48 V / 240 VDC
Digital input supply
48 VDC only
According to Power Supply (above)
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
C-9
MV Protection relay
M range - MCTI 39-40 by MiCOM P821MF
Original brand:
Areva
PE90751
ECOFIT™ proposal
With ECOFIT™, a true extended life time
1984
2010
2012
M range - MCTI 39-40
MiCOM P821MF
MCTI 39-40
Protection Relay
ECOFIT™ solution
End of spare parts
PE90635
Commercialisation
MiCOM P821MF
Protection Relay
C-10
Main technical characteristics
M range relay - MCTI 39-40
MiCOM P821MF
Case
20TE size flush mounting
20TE size flush mounting
Installation
Withdrawable case
Withdrawable case
Language
English
Multilanguage
Communication
KBus / Courier
KBus / Courier, DNP3, IEC60870-5-103
Power supply
24 V / 125 VDC - 48 V / 250 VDC
24 V / 250 VDC - 48 V / 240 VDC
Digital input supply
48 VDC only
According to Power Supply (above)
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
MV Protection relay
MCGG 62 by MiCOM P126
Original brand:
Areva or older
PE90874
ECOFIT™ proposal
With ECOFIT™, a true extended life time
< 1984
2010
2014
MCGG 62
MiCOM P126
MCGG 62
Protection Relay
ECOFIT™ solution
PE90875
Commercialisation
End of commercialisation
End of spare parts
Main technical characteristics
MCGG 62
MiCOM P126
Protection Relay
MiCOM P126
Case
Size 6
Fit existing cutout
Replacement Type
-
1 for 1 plug-and-play
Type
Static
Numerical
Functionality
3 phase overcurrent
3 phase + ground overcurrent
Power supply
24 VDC - 125 VDC
Communication
-
24 VDC - 250 VDC
DNP 3.0, IEC 60870-5-103,
ModBus RTU
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
C-11
MV Protection relay
Sepam 2000 by Sepam 60 - 80 series
Original brand:
Merlin Gerin
PE90638
ECOFIT™ proposal
With ECOFIT™, a true extended life time
1993
2006
2012
2015
Sepam 2000
Sepam 60 - 80 series
Sepam 2000
Protection Relay
ECOFIT™ solution
PE90639
Commercialisation
End of commercialisation
End of spare parts
Main technical characteristics
Sepam
serie 80
Sepam 2000
X
M06, M07, M08, M14
Motor Application
Sepam 60 - 80 series
Protection Relay
Sepam
serie 60*
X
M02 to M05, M09, M11, M15, M16, M20 to M23
X
S02, S03, S06 to S09
Sub-station Application
X
S01, S04, S05
Bus Bar Application
X
B02, B04, B07, B12
X
B01, B03
X
Transformer Application
without temp measurement
T01 to T03, T06, T07, T09, T10, T12 to T15, T17 to T19
Transformer Application
with temp measurement
T21, T22, T23, T26, T27, T29, T30, T32 to T35, T37 to T39
Generator Application
G01 to G08, G12, G13, G15 to G18
X
C02, C04, C06, C08
X
X
T04, T05, T11, T16
X
X
T24, T25, T31, T36
Capacitor bank Application
Transformer
Diff. Application
X
C01, C03
X
D02, D22
* Sepam serie 80 will be proposed in case of customised Logipam on the original Sepam 2000
ECOFIT™ Sepam 2000 upgrades: diagnosis + implementation/installation of a fully industrialised solution
C-12
2. Presentation of new
ECOFIT™ S2000
PE90637
1. Disconnection of existing
terminal blocks
PE90637
Improve the performance
of your system with
the latest technology in
micro-processor based
integrated relays.
No mechanical or electrical impact on your
installation. Implementation and site test
within a very limited time.
New features enabled:
•Advanced HMI for local control functions.
•Standard communication protocols (Modbus,
IEC 61850).
•Monitoring & advanced graphical interface
for automations and logics.
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
MV Protection relay
RM6+ / VIP by VIP + ECOFIT™ kit
Original brand:
Merlin Gerin
PE90567
ECOFIT™ proposal
A true extended life time
PE90568
1987
1998
2008
2012
VIP
VIP
VIP
Protection relays
ECOFIT™ solution
Commercialisation
End of commercialisation
End of spare parts
PE90570
Proposed substitution
PE90569
RM6+
VIP 300LL
Protection relays
Phase overcurrent protection IDMT
(Inverse Definite Minimum Time)
VIP 11R
VIP 300LL
Phase overcurrent protection IDMT
(Inverse Definite Minimum Time)
VIP 12R
VIP 300LL
Phase overcurrent and earth-fault protection
IDMT and DT IEC 60255
VIP 200
VIP 300LL
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
C-13
MV Protection relay
Various equipment / VIP & Vigirex by VIP & Sepam
Original brand:
Merlin Gerin
PE90835
ECOFIT™ proposal
A true extended life time
PE90568
1987
1998
2005*
2012
VIP & Vigirex
VIP & Sepam
VIP
Protection relays
Proposed substitution
Commercialisation
End of commercialisation
End of spare parts
* Depending on the range
Proposed substitution
PE90569
PE90835
Various equipments
VIP 300LL
Protection relays
C-14
Phase overcurrent and Earth-fault protection
IDMT and DT IEC 60255
VIP 200RMR
VIP 300LH
Sensitive earth-fault protection
Vigirex RH110
Sepam series 10
Phase overcurrent protection IDMT
VIP 13
VIP 30 - VIP 300 - TBC
Phase overcurrent protection DT
VIP 17
VIP 37
Phase overcurrent and Earth-fault protection
IDMT and DT IEC 60255
VIP 200
VIP 300
Sensitive earth-fault
VIP 50
Sepam series 10
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
MV Protection relay
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
C-15
Substation
automation
Substation Automation
Contents
Control System upgrade benefits
BAY Controler BM9x00
PACIS OI
PSCN3020 HMI
SEEFOX HMI
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
D-2
D-3
D-4
D-5
D-6
D-1
Substation Automation
Control System upgrade benefits
Improve the performance of your system
with the latest technology in micro-processor
based integrated relays.
Why Control Systems upgrade?
Upgrade solutions intend to improve the performance of your control system
with the latest technology in computers. This is also the opportunity to benefit from
computer and OS upgrading to Windows 7 to get enhances performances and
advanced features for the new HMI
Considering the large variety of legacy control systems still in operation with limited
extension and maintenance facilities, these Ecofit solutions provide an opportunity
to benefit of a unique HMI software and standard communication protocol based on
IEC61850.
What are the benefits?
Ready for future
extensions
Enables smooth and consistent legacy Control System solutions modernization.
Open, flexible and scalable architecture facilitating aggregation of several
systems at substation level.
Easiness for future extensions.
Ease of use
Fast implementing without substation shut down, original control systems can
remain in operation in most of cases
No modification of existing communication network protocol (Modbus TCP or IEC
61850, as well as protective relays communication protocol) . This could be done
step by step in further stages.
Enhance graphical
features
Realtime trends of analog values as tooltip
Zoom in/ Zoom out
Monitoring facilities by color bar graph status easy implementation
Costs
reduction
Cost effective solution providing advanced graphical interface features
and enhanced performances.
Secured migration managed by the manufacturer, thanks to an automatic migration
tool and the use of a standard protocol.
D-2
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
Substation Automation
Bay Controler BM9x00 by MiCOM C624
PE90877
Original brand:
Areva or older
ECOFIT™ proposal
With ECOFIT™, a true extended life time
1994
2009
2014
2018
BM9x00
MiCOM C624
ECOFIT™ solution
Commercialisation
End of sales
End of maintenance
Main characteristics and performances
BM9x00
MiCOM C624
Communication through legacy EFIP protocol with the
SCADA level
Standard communication through IEC61850 protocol to
SCADA level
Conection with Modbus, IEC870-5-103, IEC 870-5-101
Kbus (with K101CVT converter) and IEC61850 protocol
for downstream relays
Hardened to match substation cyber security
requirements.
Connection with Modbus, IEC103 or KBus
communication with protection relay protocol
No front side communication available for setting files
management
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
D-3
Substation Automation
PACIS OI V3.X UP TO V4.6
PE90879
Original brand:
Areva or older
by
PACIS EcoSUI
ECOFIT™ proposal
With ECOFIT™, a true extended life time
2003
2005
2013
2014
PACiS OI
PACIS EcoSUI
ECOFIT™ solution
Commercialisation
End of Windows® 2000, XP commercialisation
End of Microsoft support for Windows® XP
Main characteristics and performances
D-4
PACIS OI
PACIS EcoSUI
Windows® 2000 or XP
Windows® 7 (32/64bits)
Windows® server 2008 64bits
One Ethernet network management
Multi-LAN through IEC/IEC Gateways
Multiple IEC61850 client access points
Maximum handled dataflow 100 Measured
Values archived /sec / server
Direct IEC61850 configuration by import of
SCD file
Off-line modification & Time delayed deployment
of database after recompilation
Immediate deployment of database
modification
Redundancy switch over within 1 mn
Hot redundancy seamless switchover
Maximum handled dataflow 100 Measured
Values archived /sec / server
Handled dataflow up to 3000 MV
archived /sec /server
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
Substation Automation
PSCN3020 HMI
PE90878
Original brand:
by
EcoSUI HMI
Areva or older
ECOFIT™ proposal
With ECOFIT™, a true extended life time
1994
2004
2009
2013
PSCN3020 HMI
EcoSUI HMI
ECOFIT™ solution
Commercialisation
End of Microsoft support for Windows® XP
Obsolescence status
Main characteristics and performances
PSCN3020 HMI
EcoSUI HMI
Windows NT4 OS / 2
Windows® 7
®
One EFIP network management
Configuration & database generation using
proprietary & obsolete software
Redundancy switch over within 1 mn
Handled dataflow limited by EFIP protocol
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
Open to Ethernet IEC61850 for all future
extention and step by step replacement of bay
controllers
Direct IEC61850 configuration by import of
SCD file for all new extensions
Hot redundancy seamless switchover
Handled dataflow up to 3000 MV archived /sec
/server, once fully migrated to IEC61850
D-5
Substation Automation
Seefox HMI by EcoSUI HMI
PE90876
Original brand:
Schneider Electric
ECOFIT™ proposal
With ECOFIT™, a true extended life time
1992
2005
2014
2020
Seefox HMI
EcoSUI HMI
ECOFIT™ solution
End of commercialisation & Windows® XP support
Commercialisation
End of Windows® XP commercialisation
End of maintenance
Main characteristics and performances
Seefox HMI
EcoSUI HMI
Windows® XP
Full Schneider Electric HMI and tools design operating
on Windows® 7
Based on third party HMI limited to Modbus TCP or
Modbus + communication protocol
IEC 61850 native in modeling configuration and
communication
Configuration tools no more supported or with limited
upgrade facilities
Ready for all standard substation extension using
IEC61850 standard
Compliant with substation cyber security requirements
D-6
Medium & Low Voltage Distribution - Modernisation of switchboards - ECOFIT™ 2016
Medium & Low Voltage Distribution
Modernisation of switchboards
ECOFIT
All over the world
TM
Tested, validated and certified by Schneider Electric
Contact us!
www.schneider-electric.com/electricaldistributionservices
Discover the ECOFIT™ web selector:
www.schneider-electric.com/en/tools/ecofit-selector
The information contained in this document consists of general description of the available technical solutions and are for information purposes only.
Schneider Electric does not make any warranty, representation, guarantee or promise, expressed or implied, about the completeness, accuracy and reliability
of this information. The choice of the technical solutions will be defined in the contractual document and always subject to the proper installation and use
in accordance with the related installation guide, the installation manual and the prevailing standard and/or installation regulations.
The information is provided without liability and is subject to change without notice.
Schneider Electric Industries SAS
35, rue Joseph Monier
CS30323
F - 92505 Rueil-Malmaison cedex (France)
RCS Nanterre 954 503 439
Share capital: €928,298,512
www.schneider-electric.com
Internal documentation - 09/15
SERED111047EN
©2015 Schneider Electric. All Rights Reserved.
All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies
This document has been
printed on recycled paper

Similar documents

VG13000

VG13000 All are located at Inagawa, Itami city, Hyogo, Japan

More information

m470n

m470n W110 L217 H110 / W185 L217 H110 / W203 L217 H130 mattress size W90 L200 / W160 L200 / W180 L200

More information

Installation Guide

Installation Guide 7 Superseded Equipment - Installation Guide Index of Drawings DRAWING NUMBER DSM-7-01

More information