Electrical Power Quality Analysis of the KGHM
Transcription
Electrical Power Quality Analysis of the KGHM
AGH – University of Science and Technology Faculty of Electrical Engineering, Automatics, Computer Science and Biomedical Engineering Department of Power Electronics and Energy Conversion Systems Automation Postgraduate Studies Electrical Power Quality DIPLOMA THESIS Electrical Power Quality Analysis of the KGHM PM S.A Distribution System Operator Network Name: M.Sc. Eng. Radosław Rymkiewicz Place of employment: KGHM PM S.A. Thesis supervisor: Ph.D. Eng. Andrzej Firlit Krakow 2012/2013 Contents 1 2 3 4 Introduction ............................................................................................................................ 2 Configuration of the KGHM PM S.A. Division DSO network .................................................. 2 The measurement points and rationale of their selection....................................................... 3 The measurements and their analysis ................................................................................... 4 4.1 Measurement I at the KGHM PM S.A. Division and the Company "A" feeder ................ 6 4.1.1 The measurement data ........................................................................................... 6 4.1.2 Analysis according to the standard PN-EN 50160 ................................................... 7 4.1.3 Correlation analysis ................................................................................................. 9 4.2 Conclusions drawn from the measurement No. I .......................................................... 11 4.3 Measurement II at the KGHM PM S.A. Division and the Company "B" feeder ............. 12 4.3.1 The measurement data ......................................................................................... 12 4.3.2 Analysis according to the standard PN-EN 50160 ................................................. 13 4.3.3 Correlation analysis ............................................................................................... 17 4.4 Conclusions drawn from the measurement No. II ......................................................... 19 4.5 Measurement III at the Company "C" feeder, the MV feed point .................................. 20 4.5.1 The measurement data ......................................................................................... 20 4.5.2 Analysis according to the standard PN-EN 50160 ................................................. 20 4.5.3 Correlation analysis ............................................................................................... 22 4.6 Conclusions drawn from the measurement No. III ........................................................ 23 5 Measures that should be taken to improve power quality - mitigation of voltage fluctuations and power factor improvement............................................................................................ 24 5.1 Mitigation of voltage fluctuations (long-term flicker severity index Plt)........................... 24 5.2 Maintaining the required level of power factor tgφ ........................................................ 28 5.3 Summary and conclusions ............................................................................................ 29 References.................................................................................................................................. 30 1 1 Introduction The objective of the thesis is to investigate the quality electrical of power in the KGHM Polska Miedź S.A. Division network at selected external customers feed points, as well as at the plant feeder at the medium voltage side. The network is operated by the KGHM Polska Miedź S.A. Distribution System Operator. KGHM Polska Miedź S.A., while complying with provisions of the Energy Law Act of April 10, 1997 (uniform text Dz.U. [Journal of Laws] 2012, item 1059) and the Regulation of the Minister of Economy of May 4, 2007 on detailed conditions for the operation of the power system (Dz.U. [Journal of Laws] No. 93, item 623 of May 29, 2007) shall also, as the Distribution System Operator, be compliant with the requirements regarding the quality of electrical power supply. The study was carried out according to the power quality related standard: PN-EN 501601. It will be determined whether the quality of electrical power supplied by the KGHM PM S.A. DSO meets the requirements of this standard, and solutions for power quality improvement will be presented, if such improvement is needed. 2 Configuration of the KGHM PM S.A. Division DSO network The Main Transformer Station supplying the KGHM PM S.A. Division, denoted as GST 110/6kV, is located at the Division site. It is supplied from two 110kV radial feeder lines: S-437 and S-438 from the 110kV substation operated by the TAURON Dystrybucja S.A. Company. Under normal operating conditions the Division utilizes only a single 110kV feeder line while the second feed point supplies the external Company "A". Such configuration allows avoiding disturbances introduced to the plant grid in the case the Division and Company "A" are supplied from the same transformer and improves security of supply. Where both plants are supplied from the same transformer the security and reliability of supply are jeopardized: in the case of a power failure in the 110kV line the Division is in danger of temporary shutdown, while a failure of the cable supplying the Company "A" plant may result in the transformer emergency tripping off. Considering the case of a power failure in one of the 110kV lines it has been decided that after modification of connections both: the Division and Company "A" will be supplied from the same transformer under the condition of limiting or shutdown the Company's "A" production where necessary. Apart of the risk of power failures, each year in the summer season are carried out maintenance works scheduled for three days, and during that period both: Division and Company "A" plant are supplied from the same transformer. It should be noted that it is not possible to provide independent feeders for each division 6kV substation and providing them with automatic stand-by switching at the 6kV level. At the KGHM PM S.A. Division premises is located a coal/natural gas fired power plant, owned by the Energetyka Company. The Division is connected with the power plant by means of five 6kV feed points and one LV feed point. Normally the power plant utilizes generator No. 2; generator No. 1 is only sporadically used; generator No. 3 is currently at the commissioning phase and it was several times turned on for periods from several to over ten hours. 1 Polish Standard PN-EN 50160 "Voltage characteristics of electricity supplied by public distribution networks", Warsaw, 2010. 2 A number of external consumers, bound by contracts for electric power supply with the KGHM PM S.A. Division, are connected to the KGHM PM S.A. Division power grid. They are mostly manufacturing companies, linked through capital ties with KGHM PM S.A., and companies that provide services for the KGHM PM S.A Division. 3 The measurement points and rationale of their selection The selected measurement points are shown in a schematic diagram of the KGHM PM S.A. Division power network (Fig. 1). The pairs of measurements are marked with colours and are assigned subsequent numbers. Fig. 1 A schematic diagram of the KGHM PM S.A. Division power network 3 Considering the selection of measurement points the following factors were taken into account: Measurement I (7 days) - the measurement point at the Company "A" feeder was chosen because of the presence of fluctuating loads, i.e. arc furnaces. Disturbances emitted by arc furnaces will be examined at the measurement point at the Company "A" feeder, whereas the purpose of measurement at the KGHM PM S.A. Division feeder is to determine the quality of supply from Tauron S.A., check whether or not the disturbances generated within the KGHM PM S.A. Division network and propagated from outside are influencing each other and if so, to what extent, and also check if disturbances emitted by arc furnaces propagate through the 110kV side to the Division power supply. Measurement II (7 days) - its purpose is to measure power quality parameters at the KGHM PM S.A. Division feeder at the medium voltage side and the Division's power system influence (i.e. either worsening or improvement) on the quality of electric power sold to the Company "B", and check if induction furnaces installed close to the external load have a significant influence on the quality of electric power supplied to this external consumer. Measurement III (7 days) - its purpose is to measure the quality of electric power sold to the "C" consumer at the medium voltage side of the switchgear supplying several frequency converters at both: the medium and low voltage sides. Investigation of the influence of disturbances generated by frequency converters on the quality of power sold to the end customer. 4 The measurements and their analysis Measurements in the KGHM PM S.A. Division were carried out during the summer and winter season by means of two power quality analysers from different manufacturers: C.A. 8335 Qualistar+ supplied by the French company Chauvin Arnoux (Fig. 2) and the domestic company Sonel make PQM 701 (Fig. 3). Fig. 2 Power quality analyser C.A. 8335 Qualistar+, French company Chauvin Arnoux 4 Fig. 3 Power quality analyser PQM 701, Polish company Sonel The measurement arrangements are illustrated with photographs in figures 4 and 5 Fig. 4 An example of measurement using C.A. 8335 Qualistar+ analyser Fig. 5 An example of measurement using PQM 701 analyser 5 4.1 Measurement I at the KGHM PM S.A. Division and the Company "A" feeder 4.1.1 The measurement data Measurement I, actually a pair of measurements, indicated in the diagram (Fig. 1) by orange circles was started on 22.06.2012. According to the standard the measurement duration was 7 days and it was terminated on 29.06.2012. Since the measurements were carried out using two different instruments, employing different software, the measurement data were transferred to Microsoft Excel spreadsheet and processed according to the standard requirements in order to achieve clear analysis results. Also a correlation analysis of power quality parameters was performed2 using the Pearson coefficient of correlation for all measurement points. The analysis results are included in succeeding subsections. Figures 6 and 7 show example time characteristics obtained by means of the analysers' software. Fig. 6 - An example time characteristic of rms voltage value recorded using the C.A. 8335 Qualistar analyser software 2 Fig. 7 An example time characteristic of rms voltage value recorded using the PQM 701 analyser software K. Chmielowiec "Obróbka statystyczna wyników"; AGH-UST, Krakow 2012. 6 4.1.2 Analysis according to the standard PN-EN 50160 Company "A" Fig. 8 Schematic diagram of the KGHM PM S.A. Division power network – measurement I The analysis below takes into account solely the parameters whose values are not compliant with the standard requirements. 4.1.2.1 Long-term flicker indicator Plt At least 95.00% of values shall be contained within the interval 0.00 - 1.00. 95% 3,00 3,00 Plt L1 Plt L1 2,50 2,50 Plt L2 Plt L2 Plt L3 Plt L3 2,00 95% of values contained within the interval from 0 to 1 95% of values contained within the interval from 0 to1 2,00 1,50 1,50 1,00 1,00 0,50 0,00 00 .0 01 00 .0 45 0: time Fig. 9 Long-term flicker indicator Plt - Measurement I – the Company "A" Criterion: 95% of values contained within the interval from 0 to 1 82 79 76 73 70 67 64 61 58 55 52 49 46 43 40 37 34 31 28 25 22 19 16 7 13 4 10 0,00 1 .0 6. 28 22 :0 00 .0 47 0: 10 :0 28 .0 6. 20 12 00 .1 54 0: 22 :0 27 .0 6. 20 12 00 .1 31 0: 10 :0 27 .0 6. 20 12 00 .0 69 0: 22 :0 26 .0 6. 20 12 00 .0 87 0: 10 :0 26 .0 6. 20 12 00 .1 03 0: 22 :0 25 .0 6. 20 12 00 .0 59 0: 0: 10 :0 25 .0 6. 20 12 00 .1 83 22 :0 24 .0 6. 20 12 00 .1 88 0: 10 :0 24 .0 6. 20 12 00 .0 74 0: 0: 22 :0 23 .0 6. 20 12 00 .1 61 .0 6. 20 12 23 10 :0 0: 22 :0 20 12 22 .0 6. .0 6. 20 12 20 12 22 10 :0 0: 00 .1 13 0,50 sample Fig. 10 Long-term flicker indicator Plt - Measurement I - the Company "A" Criterion: 95% of values contained within the interval from 0 to1; samples arranged in ascending order 7 8 2012.06.29 05:10:00.014 2012.06.29 00:20:00.034 2012.06.28 19:30:00.191 2012.06.28 14:40:00.178 2012.06.28 09:50:00.080 2012.06.28 05:00:00.122 2012.06.28 00:10:00.071 2012.06.27 19:20:00.052 2012.06.27 14:30:00.043 2012.06.27 09:40:00.110 2012.06.27 04:50:00.146 L2 2012.06.27 00:00:00.132 2012.06.26 19:10:00.028 2012.06.26 14:20:00.087 2012.06.26 09:30:00.144 2012.06.26 04:40:00.100 2012.06.25 23:50:00.191 L1 2012.06.25 19:00:00.129 2012.06.25 14:10:00.015 2012.06.25 09:20:00.017 2012.06.25 04:30:00.120 2012.06.24 23:40:00.131 20 12 .0 6. 22 20 12 08 .0 :5 6. 0: 22 20 00 12 .1 16 21 .0 :2 6. 0: 22 20 00 12 .0 23 94 .0 : 50 6. :0 23 20 0. 12 07 06 .0 : 7 2 6. 0: 23 20 00 12 .1 14 84 .0 :5 6. 0: 23 20 00 12 .0 22 58 .0 :2 6. 0: 24 20 00 12 .0 05 15 .0 :5 6. 0 :0 24 20 0. 12 13 11 .0 :2 7 6. 0 :0 24 20 0. 12 20 00 .0 :5 7 6. 0 : 25 20 00 12 .0 04 66 .0 :2 6. 0: 25 20 00 12 .1 11 83 .0 :5 6. 0: 25 20 00 12 .1 19 52 .0 :2 6. 0: 26 20 00 12 .0 02 29 .0 :5 6. 0: 26 20 00 12 .0 10 07 .0 :2 6. 0 :0 26 20 0. 12 17 07 .0 :5 8 6. 0 :0 27 20 0. 12 01 11 .0 :2 1 6. 0: 27 20 00 12 .1 08 50 .0 :5 6. 0: 27 20 00 12 .1 16 75 .0 :2 6. 0: 27 20 00 12 .0 23 61 .0 :5 6. 0: 28 20 00 12 .0 07 40 .0 :2 6. 0 :0 28 20 0. 12 14 19 .0 :5 0 6. 0 :0 28 20 0. 12 22 07 .0 :2 9 6. 0 :0 29 0. 05 08 :5 1 0: 00 .1 09 1,00 2012.06.24 18:50:00.053 2012.06.24 14:00:00.086 2012.06.24 09:10:00.031 2012.06.24 04:20:00.060 2012.06.23 23:30:00.147 2012.06.23 18:40:00.084 2012.06.23 13:50:00.123 2012.06.23 09:00:00.102 2012.06.23 04:10:00.082 2012.06.22 23:20:00.057 2012.06.22 18:30:00.044 2012.06.22 13:40:00.104 2012.06.22 08:50:00.121 kV Numbers of samples meeting the above criterion: Plt Company "A" L3 66.25% 68.75% 66.25% Table 1 - The percentage contribution of samples meeting the standard PN-EN 50160 criterion for long-term flicker indicator Plt for the Company "A" 4.1.2.2 Power factor tgφ 1,20 tg φ= 0,4 tg φ Σ average 0,80 0,60 0,40 0,20 0,00 time Fig. 11 Time characteristic of tgφ - measurement I - the Company "A" The KGHM PM S.A. Division 4.1.2.3 Long-term flicker indicator Plt 6,60 6,40 6,20 6,00 5,80 U1 U2 U3 U1min U2min U3min U1max U2max U3max 5,60 5,40 time Fig. 12 Voltage magnitude time characteristic – Measurement I - the KGHM PM S.A. Division rms values – average, min., max. At least 95.00% of values shall be contained within the interval 0.00 - 1.00. 95% 3,00 3,00 Plt L1 2,50 Plt L1 2,50 Plt L2 Plt L2 Plt L3 2,00 Plt L3 95% of values contained within the interval from 0 to1 2,00 95% of values contained within the interval from 0 to 1 1,50 1,50 1,00 1,00 0,50 0,00 01 45 22 :0 0 :0 0 .0 47 .2 8 10 :0 0 :0 0 .0 82 79 76 73 70 67 64 61 58 55 52 49 46 43 40 37 34 31 28 25 22 19 16 13 7 10 20 4 12 .0 6 0,00 1 54 20 12 .0 6 .2 8 22 :0 0 :0 0 .0 31 20 12 .0 6 .2 7 10 :0 0 :0 0 .1 69 .1 .2 7 20 12 .0 6 .2 6 22 :0 0 :0 0 .0 87 20 12 .0 6 .2 6 10 :0 0 :0 0 .0 03 20 12 .0 6 .2 5 22 :0 0 :0 0 .1 59 20 12 .0 6 .2 5 10 :0 0 :0 0 .0 83 20 12 .0 6 .2 4 22 :0 0 :0 0 .1 88 20 12 .0 6 .2 4 10 :0 0 :0 0 .1 74 20 12 .0 6 .2 3 22 :0 0 :0 0 .0 61 .1 :0 0 .0 6 12 20 20 12 .0 6 .2 3 10 :0 0 :0 0 :0 0 22 .2 2 .0 6 12 20 20 12 .0 6 .2 2 10 :0 0 :0 0 .1 13 0,50 sample time Fig. 13 Long-term flicker indicator Plt - Measurement I – the KGHM PM S.A. Division; Criterion: 95% of values contained within the interval from 0 to 1 Fig. 14 Long-term flicker indicator Plt - Measurement I - the KGHM PM S.A. Division; Criterion: 95% of values contained within the interval from 0 to1; samples arranged in ascending order Numbers of samples meeting the above criterion: Plt KGHM PM S.A. Division L1 L2 L3 67.50% 68.75% 68.75% Table 2 - The percentage contribution of samples meeting the standard PN-EN 50160 criterion for long-term flicker indicator Plt for the KGHM PM S.A. Division 4.1.3 Correlation analysis Company "A" 3,50 Correlation between Plt and P 3,00 Liniowy (Correlation between Plt and P) 2,50 Fig. 15 Correlation between Plt and P - Measurement I - the Company "A" Plt 2,00 1,50 1,00 0,50 correlation coefficient 0,87 0,00 0 1 2 3 4 5 6 P 9 3,50 Correlation between Plt and Q Liniowy (Correlation between Plt and Q) 3,00 2,50 Fig. 16 Correlation between Plt and Q - Measurement I - the KGHM PM S.A. Division Plt 2,00 1,50 1,00 0,50 correlation coefficient 0,85 0,00 0 0,5 1 1,5 2 2,5 3 3,5 Q The KGHM PM S.A. Division 3,00 Correlation between Plt and P 2,50 Plt 2,00 Fig. 17 Correlation between Plt and P - Measurement I - the KGHM PM S.A. Division 1,50 1,00 0,50 correlation coefficient 0,10 0,00 0 2 4 6 8 10 12 14 16 P 3,00 Correlation between Plt and Q 2,50 Plt 2,00 Fig. 18 Correlation between Plt and Q - Measurement I - the KGHM PM S.A. Division 1,50 1,00 0,50 correlation coefficient -0,10 0,00 0 0,5 1 1,5 2 Q 10 2,5 3 3,5 4 Correlation of Plt between the Company "A" and the KGHM PM S.A. Division 3,00 Correlation of Plt between the Company A and the KGHM PM S.A. Division 2,50 Liniowy (Correlation of Plt between the Company A and the KGHM PM S.A. Division) Plt Company A 2,00 1,50 1,00 0,50 correlation coefficient 0,996 0,00 0,00 0,50 1,00 1,50 2,00 2,50 3,00 Plt KGHM PM S.A. Division Fig. 19 Correlation of Plt between the Company "A" and the KGHM PM S.A. Division 4.2 Conclusions drawn from the measurement No. I The summary of analysis of measurements at the measurement point No. I is provided in table below: Table 3 Power quality parameters at the measurement point No. I according to standard PN-EN 50160 The analysis of power quality parameters at the measurement point No. 1 shows that the key problem is the failure to comply with the requirements of standard PN-EN 50160 concerning the long-term flicker indicator Plt. Measurements at both: the KGHM PM S.A. Division and Company’s "A" feeders revealed results exceeding the limit values. Voltage fluctuations can be easily seen from the voltage magnitude time characteristic (Fig. 12). The correlation analysis allows concluding that the part responsible for this situation is the consumer - the Company "A", which operates electric arc furnaces. The correlation between reactive and active powers and 11 long-term flicker severity Plt at the Company "A" feed point is evident. In the case of the KGHM PM S.A. Division the measurements show no correlation. Furthermore, the P lt analysis performed for both feed points shows a noticeable relation. The correlation coefficient is close to unity. It is, therefore, apparent that the cause of worsening the long-term flicker index Plt are arc furnaces installed at the Company "A" plant. Proposed solutions for that problem are discussed in section 5. The analysis also shows that the power factor value at the Company "A" feed point is exceeded. According to the provisions of the connection agreement between the KGHM and TAURON S.A. the power factor is calculated as the sum of the transformer T1 and transformer T2 power factors, thus the Division power system dispatchers are controlling capacitor banks so as to prevent exceeding the value 0.4 set forth in the agreement. The Central System for Electricity Balancing and Settlement enables online monitoring of power network parameters, i.e.: active power, reactive power and power factor. The staff can, therefore, monitor the Division network on a continuous basis. The manual operation of capacitor banks should undoubtedly be supplanted by automatic control. 4.3 Measurement II at the KGHM PM S.A. Division and the Company "B" feeder 4.3.1 The measurement data The second pair of measurements indicated in the diagram by violet circles was started on 06.07.2012. According to the standard the measurement duration was 7 days and it was terminated on 29.06.2012. As formerly, the measurement data were transferred to Microsoft Excel spreadsheet and processed according to the standard requirements and for the purposes of correlation analysis. The analyses' results are included in succeeding subsections. In the succeeding subsections solely the parameters whose values are not compliant with the standard requirements are provided. 12 4.3.2 Analysis according to the standard PN-EN 50160 Company "B" Fig. 20 Schematic diagram of the KGHM PM S.A. Division power network – measurement II 4.3.2.1 Long-term flicker indicator - Plt At least 95.00% of values shall be contained within the interval 0.00 - 1.00. 95% 1,60 1,6 PLT L1 Plt L1 1,4 1,40 Plt L2 PLT L2 Plt L3 PLT L3 1,2 1,20 95% of values contained within the interval from 0 to 1 95% of values contained within the interval from 0 to1 1 Plt 1,00 Plt 0,8 0,80 0,6 0,60 0,4 0,40 0,2 0,20 25 82 79 76 73 70 67 64 61 58 55 52 49 46 43 40 37 34 31 28 25 22 19 16 7 13 4 10 1 .1 10 :0 0 :0 0 04 0,00 sample 20 12 .0 7 .1 3 16 :0 0 :0 0 .1 96 27 20 12 .0 7 .1 2 04 :0 0 :0 0 .0 32 20 12 .0 7 .1 2 16 :0 0 :0 0 .0 72 .0 :0 0 :0 0 04 .1 1 .0 7 12 20 20 12 .0 7 .1 1 16 :0 0 :0 0 .1 62 01 20 12 .0 7 .1 0 04 :0 0 :0 0 .0 03 20 12 .0 7 .1 0 16 :0 0 :0 0 .1 96 20 12 .0 7 .0 9 04 :0 0 :0 0 .1 73 .0 :0 0 :0 0 16 .0 9 .0 7 12 20 20 12 .0 7 .0 8 04 :0 0 :0 0 .1 51 20 .0 20 12 .0 7 .0 8 16 :0 0 :0 0 .1 :0 0 :0 0 04 .0 7 20 12 .0 7 .0 7 .0 7 12 20 20 12 .0 7 .0 6 16 :0 0 :0 0 .0 06 0 time Fig. 21 Fig. Long-term flicker indicator Plt - Measurement II – the Company "B" Criterion: 95% of values contained within the interval from 0 to 1 Fig. 22 - Fig. Long-term flicker indicator Plt - Measurement II - the Company "B" Criterion: 95% of values contained within the interval from 0 to1; samples arranged in 13 ascending order Numbers of samples meeting the above criterion: Plt Company "B" L1 L2 L3 93.75% 91.25% 92.50% Table 4 – T he percentage contribution of samples meeting the standard PN-EN 50160 criterion for longterm flicker indicator Plt - Company "B" 4.3.2.2 Events – voltage swells, dips, short supply interruptions, long supply interruptions During the measurement a single disturbance has occurred: a voltage dip in the phase U2. Date and time of the occurrence: 11.07.2012, 4:23:45 am; duration 0.110 s. The event was recorded in the power network dispatcher logbook: "4:22 am – a voltage dip occurred in the line S-438. The Plant Dispatch Centre informed that the dip source was the external 110 kV line". Fig. 23 The record of voltage dip waveforms and data; instantaneous values – measurement II – Company "B" Fig 24 The record of voltage dip waveforms and data; rms voltage values– measurement II - Company "B" 14 2012.07.13 12:00:00.110 2012.07.13 07:10:00.116 2012.07.13 02:20:00.120 2012.07.12 21:30:00.197 2012.07.12 16:40:00.081 2012.07.12 11:50:00.159 2012.07.12 07:00:00.028 2012.07.12 02:10:00.182 2012.07.11 21:20:00.124 2012.07.11 16:30:00.166 2012.07.11 11:40:00.065 2012.07.11 06:50:00.038 2012.07.11 02:00:00.198 2012.07.10 21:10:00.154 2012.07.10 16:20:00.120 2012.07.10 11:30:00.171 2012.07.10 06:40:00.058 2012.07.10 01:50:00.175 2012.07.09 21:00:00.124 2012.07.09 16:10:00.177 2012.07.09 11:20:00.174 2012.07.09 06:30:00.021 2012.07.09 01:40:00.052 2012.07.08 20:50:00.056 2012.07.08 16:00:00.096 2012.07.08 11:10:00.143 2012.07.08 06:20:00.180 2012.07.08 01:30:00.048 2012.07.07 20:40:00.109 2012.07.07 15:50:00.156 2012.07.07 11:00:00.178 2012.07.07 06:10:00.095 2012.07.07 01:20:00.059 2012.07.06 20:30:00.037 2012.07.06 15:40:00.129 kV .0 7. 20 06 12 15 .0 :5 7. 0: 20 06 00 12 23 .1 .0 22 :2 7. 0: 20 07 00 12 06 .0 .0 05 :5 7. 0: 20 07 00 12 14 .1 .0 84 :2 7. 0: 20 07 00 12 21 .0 .0 03 :5 7. 0: 20 08 00 12 05 .1 .0 52 :2 7. 0 20 08 :0 0. 12 12 13 .0 :5 2 7. 0 20 08 :0 0. 12 20 04 .0 :2 0 7. 0 20 09 :0 0. 12 03 00 .0 :5 1 7. 0: 20 09 00 12 11 .1 .0 38 :2 7. 0: 20 09 00 12 18 .1 .0 74 :5 7. 0: 20 10 00 12 02 .0 .0 98 :2 7. 0: 20 10 00 12 09 .1 .0 74 :5 7. 0: 20 10 00 12 17 .0 .0 23 :2 7. 0 20 11 :0 0. 12 00 01 .0 :5 5 7. 0 20 11 :0 0. 12 08 02 .0 :2 2 7. 0 20 11 :0 0. 12 15 11 .0 :5 7 7. 0: 20 11 00 12 23 .1 .0 82 :2 7. 0: 20 12 00 12 06 .0 .0 35 :5 7. 0: 20 12 00 12 14 .0 .0 27 : 2 7. 0: 20 12 00 12 21 .0 .0 80 :5 7. 0: 20 13 00 12 05 .0 .0 35 :2 7. 0: 13 00 12 .1 88 :5 0: 00 .1 63 20 12 tgφ 4.3.2.3 power factor tgφ 2,50 2,00 tg φ= 0,4 tg φ Σ average 1,50 1,00 0,50 0,00 time Fig. 25 Time characteristic of tgφ - measurement I - the Company "B" The KGHM PM S.A. Division (Common power supply with the Company "A" from a single transformer - the analyser is measuring only the Division’s power supply). 4.3.2.4 Long-term flicker indicator - Plt 6,600 6,400 6,200 6,000 5,800 5,600 U1 U2 U3 U1min U2min U3min U1max U2max U3max 5,400 5,200 5,000 time Fig. 26 Voltage magnitude time characteristic – Measurement II - the KGHM PM S.A. Division; Voltage rms values – average, min., max. 15 At least 95.00% of values shall be contained within the interval 0.00 - 1.00. 1,80 Plt L1 1,80 Plt L2 1,60 95% 2,00 2,00 Plt L1 Plt L3 Plt L2 1,60 1,40 95% of values contained within the interval from 0 to 1 Plt L3 1,40 Plt 1,20 1,00 95% of values contained within the interval from 0 to1 1,20 Plt 0,80 1,00 0,60 0,40 0,80 0,20 0,60 0,00 20 12 .0 7. 06 16 20 :0 12 0: .0 00 7. .0 07 06 04 20 :0 12 0 :0 .0 0. 7. 12 07 0 16 20 :0 12 0: .0 00 7. .0 08 51 04 20 :0 12 0: .0 00 7. .1 08 73 16 20 :0 12 0: .0 00 7. . 09 09 6 04 20 :0 12 0: .0 00 7. .1 09 03 16 20 :0 12 0: .0 00 7. .1 10 01 04 20 :0 12 0: .0 00 7. . 06 10 2 16 20 :0 12 0: .0 00 7. .1 11 72 04 20 :0 12 0: .0 00 7. .0 11 32 16 20 :0 12 0: .0 00 7. . 02 12 7 04 20 :0 12 0: .0 00 7. .0 12 96 16 20 :0 12 0: .0 00 7. .1 13 10 04 :0 0: 00 .1 25 0,40 0,20 0,00 82 79 76 73 70 67 64 61 58 55 52 49 46 43 40 37 34 31 28 25 22 19 16 13 7 10 4 1 time sample Fig. 27 Long-term flicker indicator Plt - Measurement II – the KGHM PM S.A. Division Criterion: 95% of values contained within the interval from 0 to 1 Fig. 28 Long-term flicker indicator Plt - Measurement II - the KGHM PM S.A. Division: 95% of values contained within the interval from 0 to1; samples arranged in ascending order Numbers of samples meeting the above criterion: Plt the KGHM PM S.A. Division L1 L2 L3 91.25% 93.75% 91.25% Table 5 The percentage contribution of samples meeting the standard PN-EN 50160 criterion for long-term flicker indicator Plt - the KGHM PM S.A. Division 4.3.2.5 Events – voltage swells, dips, short supply interruptions, long supply interruptions During the measurement a single disturbance has occurred: a voltage dip in the phase U2. Date and time of the occurrence: 11.07.2012, 4:23:45 am; duration 0.110 s. 7.000 6.500 kV 6.000 5.500 5.000 4.500 2012-07-10 13:54:40.000 1:04:40:39 (d:h:min:s) 5 h/Div 2012-07-11 18:35:19.111 Fig. 29 The record of voltage dip waveforms; rms voltage values (average, min., max.) – measurement II - the KGHM PM S.A. Division (The rms max. and min. values are computed every half-cycle, averaging time: 10 minutes) 16 4.3.3 Correlation analysis Company "B" 1,60 Correlation between Plt and P 1,40 1,20 Fig. 30 Correlation between Plt and P - Measurement II – Company "B" Plt 1,00 0,80 0,60 0,40 correlation coefficient 0,24 0,20 0,00 0,00 0,01 0,01 0,02 0,02 0,03 0,03 0,04 0,04 0,05 P 1,60 Correlation between Plt and Q 1,40 1,20 Plt 1,00 Fig. 31 Correlation between Plt and Q - Measurement II - Company "B" 0,80 0,60 0,40 correlation coefficient 0,18 0,20 0,00 0 0,01 0,02 0,03 0,04 0,05 0,06 0,07 Q The KGHM PM S.A. Division 1,80 1,60 Correlation between Plt and P 1,40 1,20 Fig. 32 Correlation between Plt and P - Measurement II – the KGHM PM S.A. Division Plt 1,00 0,80 0,60 0,40 correlation coefficient -0,09 0,20 0,00 0,00 2,00 4,00 6,00 8,00 10,00 12,00 14,00 16,00 P 17 1,80 1,60 Correlation between Plt and Q 1,40 Fig 33 Correlation between Plt and Q - Measurement II – the KGHM PM S.A. Division 1,20 Plt 1,00 0,80 0,60 0,40 0,20 0,00 0,00 correlation coefficient -0,08 0,50 1,00 1,50 2,00 2,50 3,00 Q Correlation of Plt between the Company "B" and the KGHM PM S.A. Division 1,80 1,60 Correlation of Plt between the Company B and the KGHM PM S.A. Division Liniowy (Correlation of Plt between the Company B and the KGHM PM S.A. Division) Plt KGHM PM S.A. Division 1,40 1,20 1,00 0,80 0,60 0,40 0,20 0,00 0,00 correlation coefficient 0,88 0,20 0,40 0,60 0,80 1,00 1,20 1,40 1,60 Plt Company B Fig. 34 Correlation of Plt between the Company "B" and the KGHM PM S.A. Division 18 4.4 Conclusions drawn from the measurement No. II The summary of analysis of measurements at the measurement point No. II is provided in table below: Table 6 Power quality parameters at the measurement point No. II according to standard PN-EN 50160 The analysis of power quality parameters at the measurement point No. II shows that the key problem is the failure to comply with the requirements of standard PN-EN 50160 concerning the long-term flicker indicator Plt. Measurements at both: the KGHM PM S.A. Division and Company’s "B" feeders revealed results exceeding the limit values. The correlation analysis allows concluding that neither the Company "B" nor the KGHM PM S.A. Division are the sources of voltage fluctuations. In this configuration the KGHM PM S.A. Division was supplied from the same transformer as the Company "A", but the measurement range comprised only the Division’s feed point. Thus disturbances that result in exceeding the flicker severity limit are present in the network but the measured circuits are not their sources. Nevertheless there is a noticeable relation between the Company "B" flicker severity Plt and changes in the KGHM PM S.A. Division Plt. We should therefore, focus on improving the long-term flicker severity index Plt at the Company's "A" feeder (this is already known from the former conclusions, cf. section 4.2). It should be noted that when the KGHM PM S.A. Division and Company's "A" are fed from the same transformer, the Company "A" limits its output. Such solution improves security of supply and, as can be seen from the measurement results, limits the long-term flicker severity index Plt. The analysis shows also that the power factor value at the Company's "B" feed point is exceeded. The Company "B" is not a large consumer of electric power; nevertheless consideration should be given to reactive power compensation in order to improve power quality factors (see section 5). During the measurement a single voltage dip has occurred. Date and time of the voltage dip occurrence: 11.07.2012, 4:23:45 am; duration 0.110 s. The voltage dip parameters are shown in figures 23, 24 and 29. The voltage dip was an external event and the party responsible for it is the supplier of electric power, i.e. TAURON S.A. It should be, however, noted that such events at the feed point with TAURON S.A. are extremely rare and supply interruptions are contained with limits set forth in the connection agreement and the contract for electric power supply. 19 No significant influence of induction furnaces installed close to the external consumer (the Company "B") on electric power quality parameters was observed. Installation of power quality recorders in outgoing feeders to large electric power consumers such as the Company "A" or the Company "B" should be considered. Alternatively a portable instrument can be used which would provide necessary data depending on the nature of problems arising in the power network and location of their occurrence. 4.5 Measurement III at the Company "C" feeder, the MV feed point 4.5.1 The measurement data Measurement III indicated in the diagram by a green circle was started on 21.01.2013. According to the standard the measurement duration was 7 days and it was terminated on 28.01.2013. The measurement data were transferred to Microsoft Excel spreadsheet, processed according to the standard requirements and their correlation analysis was performed. As formerly, solely the parameters whose values are not compliant with the standard requirements are provided. 4.5.2 Analysis according to the standard PN-EN 50160 Company "C" Fig. 35. Schematic diagram of the KGHM PM S.A. Division power network – measurement III 20 4.5.2.1 Long-term flicker indicator - Plt 6600 6400 U1 U2 U3 U1max U2max U3max U1min U2min U3min V 6200 6000 5800 5600 09:00:00 04:10:00 23:20:00 18:30:00 13:40:00 08:50:00 04:00:00 23:10:00 18:20:00 13:30:00 08:40:00 03:50:00 23:00:00 18:10:00 13:20:00 08:30:00 03:40:00 22:50:00 18:00:00 13:10:00 08:20:00 03:30:00 22:40:00 17:50:00 13:00:00 08:10:00 03:20:00 22:30:00 17:40:00 12:50:00 08:00:00 03:10:00 22:20:00 17:30:00 12:40:00 5400 time Fig. 36. Voltage magnitude time characteristic – measurement III - the Company "C" rms voltage values – average, min., max. At least 95.00% of values shall be contained within the interval 0.00 - 1.00. 2,50 Plt L1 95% Plt L1 2,50 Plt L2 Plt L2 Plt L3 Plt L3 95% of values contained within the interval from 0 to 1 82 79 76 73 70 67 64 61 58 55 52 49 46 43 40 37 34 31 28 0,00 25 0,00 14:30:00 02:00:00 14:00:00 02:00:00 14:00:00 02:00:00 14:00:00 02:00:00 14:00:00 02:00:00 14:00:00 02:00:00 14:00:00 02:00:00 time 22 0,50 19 0,50 16 1,00 13 1,00 10 1,50 7 1,50 95% of values contained within the interval from 0 to1 4 2,00 1 2,00 sample Fig. 37 Long-term flicker indicator Plt - measurement III – the Company "C" Criterion: 95% of values contained within the interval from 0 to 1 Fig. 38 Long-term flicker indicator Plt - measurement III - the Company "V" Criterion: 95% of values contained within the interval from 0 to1; samples arranged in ascending order The number of samples meeting the above criterion: Plt Company "C" L1 L2 L3 100% 0.0% 0.0% Table 7 - The percentage contribution of samples meeting the standard PN-EN 50160 criterion for long-term flicker indicator Plt – the Company "C" 21 4.5.2.2 Power factor tgφ 6 tg φ= 0,4 tg φ Σ average 5 tgφ 4 3 2 1 12 :4 16 0:0 :5 0 21 0:0 :0 0 01 0:0 :1 0 05 0:0 :2 0 09 0:0 :3 0 13 0:0 :4 0 17 0:0 :5 0 22 0:0 :0 0 02 0:0 :1 0 06 0:0 :2 0 10 0:0 :3 0 14 0:0 :4 0 18 0:0 :5 0 23 0:0 :0 0 03 0:0 :1 0 07 0:0 :2 0 11 0:0 :3 0 15 0:0 :4 0 19 0:0 :5 0 00 0:0 :0 0 04 0:0 :1 0 08 0:0 :2 0 12 0:0 :3 0 16 0:0 :4 0 20 0:0 :5 0 01 0:0 :0 0 05 0:0 :1 0 09 0:0 :2 0 13 0:0 :3 0 17 0:0 :4 0 21 0:0 :5 0 02 0:0 :0 0 06 0:0 :1 0 10 0:0 :2 0 14 0:0 :3 0 18 0:0 :4 0 22 0:0 :5 0 03 0:0 :0 0 07 0:0 :1 0 11 0:0 :2 0 0: 00 0 time Fig. 39 Time characteristic of tgφ - measurement III - the Company "C" 4.5.3 Correlation analysis 1,60 1,40 1,20 Plt 1,00 Fig. 40 Correlation between Plt and P - Measurement III, Company "C" 0,80 0,60 0,40 Correlation between Plt and P correlation coefficient - 0,15 0,20 0,00 0,000 0,010 0,020 0,030 0,040 0,050 0,060 0,070 P 1,60 1,40 1,20 Plt 1,00 Fig. 41 Correlation between Plt and Q - Measurement III, Company "C" 0,80 0,60 0,40 Correlation between Plt and Q correlation coefficient - 0,15 0,20 0,00 0,000 0,020 0,040 0,060 0,080 Q 22 0,100 0,120 0,140 4.6 Conclusions drawn from the measurement No. III The summary of analysis of measurements at the measurement point No. I is provided in table below: Table 8 Power quality parameters at the measurement point No. III according to standard PN-EN 50160 The analysis of power quality parameters at the third measurement point shows that the key problem are exceeded limit values of the long-term flicker severity index Plt and power factor. Thus, in order to reduce tgφ, reactive power compensation should be implemented. The proposed measures for flicker severity index Plt improvement are described in section 5. It is interesting that frequency converters supplied from the same switchgear - connected at both: the low-voltage and medium-voltage side, have no significant influence on harmonic content. 23 5 Measures that should be taken to improve power quality - mitigation of voltage fluctuations and power factor improvement 5.1 Mitigation of voltage fluctuations (long-term flicker severity index Plt) Voltage fluctuations produce various effects that may adversely impact production processes, equipment operation and human health, “namely: - Voltage fluctuations at the terminals of induction motors cause changes in torque and slip, and consequently affect the production process. In the worst case they may lead to excessive vibration, reducing mechanical strength and shortening the motor service life. - In electrolysers both the useful life and the operational efficiency of equipment can be reduced in the presence of voltage fluctuations, process effectiveness can be reduced and product quality deteriorated. - Any change in supply voltage magnitude results in a change in the luminous flux of a light source. This is known as flicker, which is a subjective visual impression of unsteadiness of a light’s flux, when its luminance or spectral distribution fluctuates with time…The flicker caused by voltage fluctuations significantly impairs vision and causes general discomfort and fatigue… Flicker affects the vision process and human brain reaction. Flickering light sources can produce discomfort and deterioration in work quality, in extreme cases can be the cause of accidents in the workplace or epileptic seizures."4 If arc furnaces, connected as close to the HV/MV transformer as possible, are the cause of exceeding the flicker severity Plt limit at the terminals of KGHM PM S.A. Division loads it means, that voltage fluctuations propagate through the transformer and HV feed points. In that case the remedy measures are both difficult and costly. The following solutions can be considered: Increasing the network short-circuit capacity by installation of a new HV/MV transformer supplying arc furnaces. Since voltage fluctuations propagate through the 110 kV feed point in the Tauron S.A. station, the transformer should be supplied from a different 110 kV station or, where possible, from a different busbars system in the existing 110 kV station. Limiting reactive power changes by means of additional power factor compensation at the arc furnace point of connection. A follow-up compensator mitigates quick fluctuations, although only to a limited extent. Slow voltage fluctuations should be less perceptible. Another solution may consist in agreeing with the arc furnaces operator the time of furnaces operation. In other words the furnaces should be operated during the feeder least loading periods; consequently effects of voltage fluctuations will be minimized. "Appropriate electrode positioning control, segregation and preliminary preparation of furnace charge, the use of doped electrodes, etc."4 may considerably reduce voltage fluctuations. While considering these solutions both: the economic conditions and difficulty of installation shall be accounted for. 4 Joint publication "Poradnik Inżyniera Elektryka" vol. 3 Wydawnictwa Naukowo-Techniczne, 4th edition, Warsaw 2011; p. 832-835 24 The first solution is extremely costly since it requires installing an additional transformer that should be supplied from a different 110kV station than the one presently supplying the plant or, if practicable, from a different busbars system in the existing 110 kV Tauron S.A. station. An investment project, being currently implemented in the KGHM PM S.A. Division assumes the Company "A" will be supplied from a separate transformer. It is now in the design phase. The installation of a new transformer is first of all dictated by improvement of the supply reliability. It should be thus analysed if there is a possibility of supplying the new transformer from separate 110kV busbars. If such solution turns out to be reasonably practicable the additional cost would be relatively small in terms of the already commenced investment project. It should be emphasised that this solution will remedy the problem at the Division feed point but for other consumers, supplied from the same point of transformer connection at the Company "A" feeder, the problem will not be resolved. The second solution may be implemented independently from the first one because mitigation of voltage fluctuations at the 110kV busbars will improve not only the quality of the Division power supply but also of other consumers supplied from the Tauron S.A. station. Examples of solutions to the considered problem are illustrated in Fig. 42 that shows classification of follow-up voltage stabilisers. Follow-up reactive power compensators Dynamic voltage stabilisers Static Rotating (Synchronous machine) Power electronic systems Saturable reactors 25 Fig. 42 Classification of follow-up voltage stabilisers (older solutions, presently rarely used, are shaded in 4 grey) In the subject literature can be found many configurations of static compensators. "The most popular version is STATCOM compensator which is particularly effective in reduction of voltage fluctuations produced by fluctuating loads".4 The circuit diagram and phasor diagrams of a STATCOM compensator are shown in Fig. 43. Fluctuating load VSC Fig. 43 The STATCOM compensator: a) schematic diagram; phasor diagrams for various relationships 4 between U and Uvsc Where: Uvsc - voltage at the VSC converter input terminals U - voltage at the supply busbars Ux - voltage drop across the reactance Xr I - the compensator current Xr – the reactance of the VSC converter input reactor Figure 44 shows an example installation of a cheaper D-STATCOM compensator that is a perfect solution in the case of an arc furnace producing very strong voltage fluctuations. 4 Joint publication "Poradnik Inżyniera Elektryka" vol. 3; Wydawnictwa Naukowo-Techniczne, 4th edition, Warsaw 2011; p. 836-838 26 Fig. 44 A compact D-STATCOM application to an arc furnace - schematic diagram 5 "…it should be emphasised that implementation of D-STATCOM compensators requires much lower capital investments and their pay-back time is shorter than that of STATCOM compensators in transmission systems. Thus, besides large companies like Siemens, Toshiba, Mitsubishi Electric, Alstom, also smaller companies are entering the market. In Poland also domestic companies provide installation of D-STATCOM compensators.”5 It should be borne in mind that STATCOM applications are expensive and can be supplanted by a thyristor controlled reactor with fixed capacitor bank (FC/TCR). It is much cheaper solution, which in our case will perform sufficiently well. "The fixed capacitor bank (FC) with inductive current fundamental harmonic controller (TCR) is an example of the indirect compensation method in which, depending on the needs of the voltage restorer or the reactive power compensator function, the value of the sum of two current components is controlled (Fig. 45): the capacitor current iFC fundamental harmonic; the capacitor bank normally is operated as high harmonic filter(s) or a switched capacitor bank (TCR/TSC system); fundamental harmonic of the reactor current iTCR is controlled by means of a phasecontrolled thyristor AC switch (T). Figure 45a shows a single-line diagram of such installation and Figure 45b shows the reactor current waveforms for different values of the control angle α (with respect to voltage zerocrossing). The control angle and, consequently, the reactor current fundamental harmonic and the compensator current fundamental harmonic values (as well as the value and sign of voltage drop across the power system impedance) can vary during every half-cycle taking its values from the interval (0.5π; π)”8. PCC Load Fig. 45. a) Single-line equivalent diagram of the FC/TCR compensator; b) The voltage and current waveforms that illustrate its principle of operation 5 R.Strzelecki, G.Benysek "Układy STATCOM i ich rola w systemie elektroenergetycznym"; Uniwersytet Zielonogórski 2004; p. 11 8 Z. Hanzelka "Automatyka - Elektryka - Zakłócenia nr 5/2011"; WWW.ELEKTRO-INNOWACJE.PL 27 Power supply network Load Control circuit reference voltage/ reactive current Fig 46 Schematic diagram of the FC/TCR compensator a closed-loop control system of the FC/TCR compensator The third solution seems to be the cheapest one. It however requires the arc furnaces operator to comply with some requirements concerning segregation and preliminary preparation of furnace charge, observe specified time of furnaces operation and maintain proper automatic control. This solution also requires arrangements between the KGHM PM S.A. Division and the Company "A" on both the work organisation and incurred costs. That still does not guarantee that the problem will be successfully solved. Moreover, it does not seem real to influence operations of an external company, even if the company is linked through capital ties with KGHM PM S.A. 5.2 Maintaining the required level of power factor tgφ Speaking about maintaining the required level of power factor tgφ it should be mentioned that reactive power is compensated in the KGHM PM S.A. Division power network by means of capacitor banks installed at the Main Transformer Station at the medium voltage side and in low voltage switchgears or at individual LV loads. Since the Division does not exceed tgφ limit at the point of connection to the utility distribution system, it does not incur additional fees for failure to comply with requirements. In the case of Companies "A", "B" or "C" power factor tgφ limits are exceeded, thus reactive power compensation should be implemented. In view of the above, for each of discussed cases there should be performed a detailed cost analysis of installation of a capacitor bank or capacitor bank with reactive power controller. It should be born in mind that, similarly to reactive power charges, the cost of capacitor bank installation should be incurred by the consumer. 28 5.3 Summary and conclusions The conclusions and findings are summarised in the table below to provide a clear overview of proposed modifications. Measurement at the feed point: Company "A" Irregularities found Recommended solution Additional requirements Exceeded Plt and tgφ FC/TCR installation Company "B" Exceeded Plt and tgφ Capacitor bank installation Company "C" Exceeded Plt and tgφ Capacitor bank installation - Portable network analyser - Expansion of the Central System for Electricity Balancing and Settlement in order to include power quality parameters at 110kV feed points KGHM PM S.A. Division Exceeded Plt; capacitor bank manual switching Capacitor bank automatic control Table 9 Proposed solutions to detected irregularities Investigation of the power network in one of KGHM PM S.A. divisions was carried out in terms of electrical power quality at the supplier-customer level. This involves power quality issues, particularly voltage fluctuations and occurrences of exceeding long-term flicker severity Plt limit values. Detected anomalies allow handling the problems and, where possible, implementing solutions improving the quality of power. Whether the costs of such solutions should be born solely by customers (if they are the source of disturbances) or be shared with KGHM PM S.A., is a separate matter. Implementation of electrical power quality improvements may protect us in the future from unfavourable changes to contracts with utility companies or from claims raised by our customers. In order to get complete information on the quality of electrical power, both purchased and sold, the existing Central System for Electricity Balancing and Settlement should be expanded to include power quality parameters at 110kV feed points. Such data would enable in-depth analysis of electric power parameters, particularly within a long time-frame. The measurements should undoubtedly be continued not only at the points where electricity is sold but also on the Division's departments, e.g. Electrorefining Section where voltage fluctuations may adversely impact the electrolysis process. In order to take preventive remedy measures it is worth knowing where, and to what extent, we are dealing with the poor quality of electrical power. In such cases the use of a portable PQ analyser would be required. The economic effects of modernization and modifications, that certainly require substantial capital investment, will not be instantaneous and their impact is difficult to estimate. Production process effectiveness and quality, equipment lifetime and work accidents rate are influenced by many factors. Nevertheless improving even one of these factors may result in considerable improvement in both human working conditions and equipment operation. A costsbenefits analysis of the planned investment should minimise the investment risk and ensure that estimated effects will be close to real. 29 References [1] – Polish Standard PN-EN 50160: "Voltage characteristics of electricity supplied by public distribution networks", 2010. [2] – K.Chmielowiec "Obróbka statystyczna wyników"; AGH-UST Krakow 2012 [3] – K.Piątek "Sposoby redukcji wahań napięcia"; AGH-UST Krakow 2012 [4] – Joint publication "Poradnik Inżyniera Elektryka" vol 3; Wydawnictwa Naukowo-Techniczne, 4th edition, Warsaw 2011; [5] – R.Strzelecki, G.Benysek "Układy STATCOM i ich rola w systemie elektroenergetycznym"; Uniwersytet Zielonogórski 2004; [6] – A.Firlit, W.Łoziak, J.Bielewicz "Rozproszony system monitorowania jakości dostawy energii elektrycznej w sieci zasilającej AGH (RSM-JDEE) Power Quality Smart Metering"; AGH-UST, KrakOw 2011 [7] – A. Wetula „Analiza wahań napięcia i uciążliwości migotania” AGH-UST Krakow 2012 [8] – Z. Hanzelka "Automatyka - Elektryka - Zakłócenia nr 5/2011"; WWW.ELEKTRO-INNOWACJE.PL [9] – Energy Law Act of April 10, 1997 (uniform text Dz.U. [Journal of Laws] 2012, item 1059) [10] – Regulation of the Minister of Economy of May 4, 2007 on detailed conditions for the operation of the power system (Dz.U. [Journal of Laws] No. 93, item 623 of May 29, 2007). 30