This instruction sheet provides procedures for installing the following framework hardware:
• Lower express troughs and jumper retainers
• Lower transition troughs
• Upper express troughs including: upper horizontal express troughs, upper horizontal through troughs,
and upper horizontal cross-aisle express troughs
• Cross-aisle bridging troughs and ramps.
These framework hardware piece parts are used with the DSX-1/1C Systems (Bantam Plus and 800- and
900-Series) and the Digital Interconnect and Cross-Connect Interface Systems (DIXI-1 and DIXI-3). All of the
hardware covered in this instruction sheet is designed to mount on 23-inch (584 mm) bay frames.
The express troughs and jumper retainers are also supplied with certain ED-6C157-31 groups. ED-6C15731framework groups consist of various ED-6C157-30 individual groups assembled to facilitate the engineering
and ordering of framework hardware needed to construct bays for specific applications.
For Cross-Aisle Troughs where adjacent lineups are not parallel, refer to ED-6C157-30, Grouping Offset
Cross-Aisle kit. The trough kit may be used with DSX1 and DSX3 equipment bay lineups with 2 ft.-3 in. and
3 ft-0 in. aisle spacing. See Page 13.
How to Contact Us
• To find out more about Carrier Apparatus products, visit us on the web at:
http://cw.commscope.com/
• For technical assistance regarding Carrier Apparatus products: contact your local CommScope account
representative or CommScope technical support at 1-800-344-0223.
• Report any missing or damaged parts to CommScope customer service in Omaha, Nebraska, at
1-866-539-2795.
References
•
•
•
•
•
•
•
•
•
•
365-301-120 — 800-Series and 900-Series DSX\1/1C, System Reference Guide
365-301-121 — DIXI-1 System, System Reference Guide
365-301-125 — Bantam Plus DSX-1/1C, System Reference Guide
365-301-131 — DIXI-3 System, System Reference Guide
ED-6C152-12 — 900-NSD System, Engineering and Ordering
ED-6C155-10 — DIXI-1 System, Engineering and Ordering
ED-6C155-11 — DIXI-3 System, Engineering and Ordering
ED-6C156-10 — Bantam Plus DSX-1/1C, System Engineering and Ordering
ED-6C157-10 — DSX-1/1C and DIXI System, Framework Engineering, Hardware and Ordering
ED-6C157-31 — DSX-1/1C and DIXI System, Framework Hardware Groups
Tools Required
• Screw-starter
• Flat-blade 0.2-inch (5 mm) wide, 6-inch (152 mm) long screwdriver
© 2007 CommScope, Inc.
All Rights Reserved
Printed in U.S.A.
Page 1
14 Pages
Material ID 847 441 664
Instruction Sheet
Ordering Information
Table 1: Information for Ordering Various Components
Apparatus Code
Material ID
Description
Lower Horizontal Express Troughs (see Page 4)
ED-6C157-30 Group 12
601 414 972
One 8-inch (203 mm) H by 8-inch (203 mm) D lower horizontal express
trough. Color: white.
ED-6C157-30 Group 25
601 415 102
One 6-inch (152 mm) H by 8-inch (203 mm) lower horizontal express trough.
Color: white.
ED-6C157-30 Group 29
601 415 144
One 4-inch (102 mm) H by 8-inch (203 mm) lower horizontal express trough.
Color: white.
ED-6C157-30 Group 55
601 438 542
One 6-inch (152 mm) H by 5-inch (127 mm) D lower horizontal express
trough, one 6-inch (152 mm) H by 5-inch (127 mm) D lower trough extension
bracket and guard rail cover. Color: white.
ED-6C157-30 Group 58
601 439 177
One 4-inch (102 mm) H by 5-inch (127 mm) D lower horizontal express
trough, one 4-inch (102 mm) H by 5-inch (127 mm) D lower trough extension
bracket and guard rail cover. Color: white.
ED-6C157-30 Group 68
601 458 151
One 8-inch (203 mm) H by 8-inch (203 mm) D lower horizontal express
trough. Color: blue.
ED-6C157-30 Group 70
601 458 177
One 8-inch (203 mm) H by 5-inch (127 mm) D lower horizontal express
trough. Color: blue.
Jumper Retainers (see Page 4)
ED-6C157-30 Group 3
601 414 873
Two 8-inch (203 mm) jumper retainers. Color: white.
ED-6C157-30 Group 56
601 438 559
Two 5-inch (127 mm) jumper retainers. Color: white.
ED-6C157-30 Group 76
601 458 524
Two 5-inch (127 mm) jumper retainers. Color: blue.
ED-6C157-30 Group 77
601 458 532
Two 8-inch (203 mm) jumper retainers. Color: blue.
Lower Transition Troughs and Upper Horizontal Express Troughs (see Page 5 and Page 6)
ED-6C157-30 Group 15
601 415 003
One 8-inch (203 mm) H by 8-inch (203 mm) H lower transition trough. Color:
white.
ED-6C157-30 Group 19
601 415 045
One 6-inch (152 mm) D by 8-inch (203 mm) H lower transition trough. Color:
white.
ED-6C157-30 Group 16
601 415 011
One 8-inch (203 mm) H by10-inch (254 mm) D upper horizontal express
trough. Color: white.
ED-6C157-30 Group 24
601 415 094
One 6-inch (152 mm) H by 10-inch (254 mm) H upper horizontal express
trough. Color: white.
ED-6C157-30 Group 28
601 415 136
One 4-inch (102 mm) H by 10-inch (254 mm) D upper horizontal express
trough. Color: white.
Page 2
14 Pages
Material ID 847 441 664
Issue 6, February 2004
Apparatus Code
Material ID
Description
ED-6C157-30 Group 54
601 438 534
One 6-inch (152 mm) H by 5-inch (127 mm) D upper horizontal express
trough. Color: white.
ED-6C157-30 Group 57
601 439 151
One 4-inch (102 mm) H by 5-inch (127 mm) D upper horizontal express
trough. Color: white.
ED-6C157-30 Group 67
601 458 144
One 8-inch (203 mm) H by 10-inch (254 mm) D upper horizontal express
trough. Color: blue.
ED-6C157-30 Group 69
601 458 169
One 8-inch (203 mm) H by 5-inch (254 mm) D upper horizontal express
trough. Color: blue.
Upper Horizontal Through Troughs (see Page 6)
ED-6C157-30 Group 11
601 414 964
One 8-inch (203 mm) H by 10-inch (254 mm) D upper horizontal through
trough. Color: white.
ED-6C157-30 Group 22
601 415 078
One 6-inch (152 mm) H by 10-inch (254 mm) D upper horizontal through
trough. Color: white.
ED-6C157-30 Group 26
601 415 110
One 4-inch (102 mm) H by 10-inch (254 mm) D upper horizontal through
trough. Color: white.
Upper Horizontal Cross-Aisle Through Troughs (see Page 7 through Page 9)
ED-6C157-30 Group 10
601 414 956
One 8-inch (102 mm) H by 10-inch (254 mm) D upper horizontal crossaisle
through trough. Color: white.
ED-6C157-30 Group 23
601 415 086
One 6-inch (152 mm) H by 10-inch (254 mm) D upper horizontal crossaisle
through trough. Color: white.
ED-6C157-30 Group 27
601 415 128
One 4-inch (102 mm) H by 10-inch (254 mm) D upper horizontal crossaisle
through trough. Color: white.
Cross-Aisle Bridging Troughs and Ramps (see Page 7 through Page 12)
ED-6C157-30 Group 4
601 414 881
Two 30° 8-inch (203 mm) H cross-aisle bridging trough ramps. Color: white
ED-6C157-30 Group 5
601 414 907
Two 15° 6-inch (152 mm) cross-aisle bridging trough ramps. Color: white.
ED-6C157-30 Group 6
601 414 915
Two 0° 4-inch (102 mm) H cross-aisle bridging trough ramps. Color: white.
ED-6C157-30 Group 8
601 414 931
One 17-inch (432 mm) L cross-aisle bridging trough. Color: white.
ED-6C157-30 Group 9
601 414 949
One 29-inch (737 mm) L cross-aisle bridging trough. Color: white.
ED-6C157-30 Group 32
601 418 353
One 41-inch (1041 mm) L cross-aisle bridging trough. Color: white.
ED-6C157-30 Group 33
601 418 361
One 53-inch (1346 mm) L cross-aisle bridging trough. Color: white.
The Offset Cross-Aisle Bridging Trough can be ordered by requesting Kit of Parts ED-6C157-30, Group 106.
This trough kit can be used with DSX1 and DSX3 equipment bay lineups with 2 ft.-3 in. and 3 ft.-0 in. aisle
spacing. See Page 13 for installation instructions.
Page 3
14 Pages
Material ID 847 441 664
Instruction Sheet
Installing Lower Horizontal Express Troughs And Jumper Retainers
Figure 1 shows how to install Group 12 and Group 3. Groups 25, 29, 55, 58, 68, and 70 lower express troughs,
and Groups 56, 76 and 77 jumper retainers are installed in the same way.
1. Align the lower horizontal express trough with the lowest holes on the bay frame.
2. Fasten the lower express trough to the frame with eight No. 12-24 by 3/8-inch (9.5 mm) long screws.
3. Fasten the jumper retainers to the lower express trough with four No. 12-24 by 3/8-inch (9.5 mm) long
screws.
Note:
Perform Step 4 only if required to span space between adjacent bays.
4. Fasten the lower trough extension bracket to the lower express trough with two No. 12-24 by 3/8-inch (9.5
mm) long screws.
Figure 1. Installing Lower Horizontal Express Trough and Jumper Retainers
Page 4
14 Pages
Material ID 847 441 664
Issue 6, February 2004
Installing Group 15 And 19 Lower Transition Troughs
The following steps describe how to install Group 15 and Group 19 lower transition troughs (see Figure 2).
1. Align the lower transition trough to the lowest holes on the bay frame.
2. Fasten the rear trough to the frame with four No. 12-24 by 3/8-inch (9.5 mm) long screws.
3. Fasten the front trough to the frame with four No. 12-24 by 3/8-inch (9.5 mm) long screws.
Figure 2. Installing Group 15 and 19 Lower Transition Troughs
Page 5
14 Pages
Material ID 847 441 664
Instruction Sheet
Installing Upper Horizontal Express Troughs And Upper Horizontal Through Troughs
Figure 3 shows Group 16 upper horizontal express trough installation. Groups 24 and 28, 54, 57, 67, and 69
upper horizontal express troughs and Groups 11, 22, and 26 upper horizontal through troughs are installed in
the same way.
1. Locate the mounting hole positions for the upper horizontal express trough. The top edge of trough is
aligned with the bottom edge of bay frame top.
2. Fasten the trough to the frame with four No. 12-24 by 3/8-inch (9.5 mm) long screws provided.
Note:
The 8-inch (203 mm) and 6-inch (152 mm) high troughs use eight screws (four per side) for
installation. The 4-inch (102 mm) high troughs use four screws (two per side)
.
Figure 3. Trough Installing Upper Horizontal Express Trough and Upper Horizontal Through
Page 6
14 Pages
Material ID 847 441 664
Issue 6, February 2004
Determining Cross-aisle Bridging Framework Hardware
1. Measure aisle distance between frame uprights (see Figure 4).
Figure 4. Measuring Cross-Aisle Distance
2. Select frame hardware groups needed from the following Table 2.
Note:
All recommended group configurations in Table 2 meet the OSHA standard for 80 inches
(2032 mm) of height.
Table 2: Frame Hardware Groups
Upper Horizontal Cross-Aisle Through Trough (see note)
Cross-Aisle Distance
Group 10
Group 23
Group 27
52 inches to 64 inches
(1321 to 1626 mm)
Groups 4, 8
Groups 5, 8
Groups 6, 8
64 inches to 76 inches
(1626 to 1930 mm)
Groups 4, 9
Groups 5, 9
Groups 6, 9
76 inches to 88 inches
(1939 to 2235 mm)
Groups 4, 32
Groups 5, 32
Groups 6, 32
88 inches to 100 inches
(2235 to 2540 mm)
Groups 4, 33
Groups 5, 33
Groups 6, 33
Note:
Upper cross-aisle through troughs are not required for mounting the ramps and troughs to the
rear of the bay frame.
Page 7
14 Pages
Material ID 847 441 664
Instruction Sheet
Determining The Cross-aisle Bridging Framework Hardware Location
• Determine the location of the cross-aisle bridging hardware in the lineup (see Figure 5).
• Cross-aisle bridging troughs and ramps should be placed in every third bay in a lineup, starting with
bay No. 2.
• Cross-aisle troughs and ramps should not be mounted in bays equipped with ancillary equipment
mounted above the last (top) DSX panel.
Figure 5. Cross-Aisle Bridging Trough and Ramp Placement
Page 8
14 Pages
Material ID 847 441 664
Issue 6, February 2004
Installing Upper Horizontal Cross-aisle Through Troughs
Figure 6 shows Group 10 upper horizontal cross-aisle through trough installation. Groups 23 and 27 mount the
same way.
1. Locate the mounting hole positions for the upper horizontal cross-aisle through trough. Align the top edge
of the through trough with the bottom edge of the bay frame top.
2. Fasten the through trough to the frame with four No. 12-24 by 3/8-inch (9.5 mm) long screws.
Note:
The 8-inch (203 mm) and 6-inch (152 mm) high troughs (Groups 10 and 23) use eight screws
(four per side) for each through trough. The 4-inch (102 mm) high through trough (Group 27)
uses four screws (two per side).
3. If desired, fasten back plate to the through trough using four No. 12-24 by 3/8-inch (9.5 mm) long screws.
Note:
The backplate is not installed if jumpers are routed to the non cross-connect side of the bay
frame.
Figure 6. Installing Upper Horizontal Cross-Aisle Through Trough
Page 9
14 Pages
Material ID 847 441 664
Instruction Sheet
Installing Cross-aisle Bridging Trough And Bridging Trough Ramps To
Cross-connect Side Of Bay
Figure 7 shows Groups 4 and 9 installation. The other recommended cross-aisle group configurations install in
the same way. If necessary, refer to Table 2 on Page 7 for recommended cross-aisle bridging hardware
(bridging troughs, ramps, and upper horizontal thru troughs) configurations.
1. Fasten cross-aisle bridging trough ramp to upper horizontal cross-aisle through trough with six No. 12-24
by 3/8-inch (5.5 by 9.5 mm) screws (see Figure 7).
Note:
If frame is not equipped with upper horizontal cross-aisle through trough, or if the cross-aisle
bridging trough and ramps are being installed to the non cross-connect side of the bay frame, use
adapter brackets to secure bridging trough ramps to frames (see Figure 8 on Page 11).
2. Repeat Step 1 for other side of aisle.
3. Fasten cross-aisle bridging trough to bridging trough ramps with four No. 12-24 by 3/8-inch (9.5 mm)
screws and No. 12-24 acorn nuts.
4. Secure bridging trough to overhead support with 5/8-inch -11 (15.8 mm) threaded rod (see Figure 9 on
Page 12).
Figure 7. Cross-Aisle Ramps and Bridging Trough Installation—Cross-Connect Side
Page 10
14 Pages
Material ID 847 441 664
Issue 6, February 2004
Installing Cross-aisle Bridging Trough And Ramps To Non Cross-connect
Side Of Bay
Figure 8 shows Groups 6 and 9 installation. The other recommended cross-aisle group configurations install in
the same way. If necessary, refer to the table on Page 7 for recommended cross-aisle bridging hardware
(bridging troughs, ramps, and upper horizontal through troughs) configurations.
1. Fasten cross-aisle bridging trough ramp to the adapter brackets using with six No. 12-24 by 3/8-inch (9.5
mm) screws.
2. Fasten cross-aisle bridging trough ramp to narrow flange side of the bay frame with six No. 12-24 by 3/8inch (9.5 mm) screws.
3. Repeat Step 1 for other side of aisle.
4. Fasten cross-aisle bridging trough to bridging trough ramps with four No. 12-24 by 3/8-inch (9.5 mm)
screws and No. 12-24 (5.5 mm) acorn nuts.
5. Secure bridging trough to overhead support with 5/8-inch -11 (15.8 mm) threaded rod (see Figure 9 on
Page 12).
Figure 8. Installing Cross-Aisle Ramps and Bridging Trough to Bay Frame
Page 11
14 Pages
Material ID 847 441 664
Instruction Sheet
Installing Threaded Rod Support For Cross-aisle Bridging Trough
Refer to Figure 9.
One threaded rod support (Material ID 800 682 288) is required for each Group 8 and 9 cross-aisle bridging
trough. Two threaded rod supports are required for each Group 32 and three supports for each Group 33
cross-aisle bridging trough.
1. Thread rod into cross-aisle bridging trough hex nut until rod is flush with the bottom of the trough.
2. Secure the rod by jamming.
Hex nut
5/8" - 11 (15.87 mm)
3 required
Threaded rod
5/8" - 11 x 24"
(15.87 x 610 mm)
800 682 288
Rack stringer
Insulator option
(as required)
Fiber tube
3/4" (19 mm)
Hex nut
5/8" - 11 (15.87 mm)
part of trough
Figure 9. Installing Threaded Rod for Cross-Aisle Bridging Trough
Page 12
14 Pages
Clip - 2 required
804 203 156
Rack stringer or
aux. framing
Threaded rod
5/8" - 11 x 24"
(15.87 x 610 mm)
800 682 288
Material ID 847 441 664
Issue 6, February 2004
Installing Offset Cross-aisle Bridging Trough (Ed-6c157-30, Group 106)
Refer to Figure 10 and Figure 11.
1. Install each Upper Express Trough (860061357) to the bay frame using 4 screws (901068031) and 4 acorn
nuts (901252080).
2. Mount the Cross-Aisle Support Brackets (860015841) to the Upper Express Trough using (4) screws
(901068031) and (4) acorn nuts (901252080).
Upper express
trough (860061357)
1 Install upper express
trough to bay frame
Cross-aisle
support brackets
(860015841)
Upper express
trough (860061357)
2 Mount cross-aisle
support brackets to
upper express troughs
Bay frame
Upper express
trough (860061357)
Figure 10. Installing Upper Express Troughs and Cross-Aisle Support Brackets
Page 13
14 Pages
Material ID 847 441 664
Instruction Sheet
3. Install Transition Pins (846137487) in six places as shown.
4. Mount Cross-Aisle Trough, Outer (860015825) and Cross-Aisle Trough, Inner (860015833) using (4)
screws (901068031) and (4) Acorn nuts (901252080).
5. Secure trough assembly using 5/8-in. threaded rod (not provided) into Central Office infrastructure. See
Figure 9.
5
3 Install transition pins
(848137487) six places
3
Cross-aisle
inner trough
(860015833)
4 Mount cross-aisle
inner and outer troughs
Cross-aisle
outer trough
(860015825)
Figure 11. Installing Transition Pins, Mounting Inner and Outer Cross-Aisle Troughs,
and Securing Assembly to Infrastructure
Page 14
14 Pages