NH-EL Series - Nortec Humidity
Transcription
NH-EL Series - Nortec Humidity
Your guide to selecting and specifying Nortec Electrode Humidifiers. NH-EL Series Engineering Manual Includes technical specifications, guidelines, and options for selection and application of NH-EL electrode humidifiers. 2577597_A | MAY 2014 Thank you for choosing Nortec. Proprietary Notice This document and the information disclosed herein are proprietary data of Nortec Humidity Ltd. Neither this document nor the information contained herein shall be reproduced, used, or disclosed to others without the written authorization of Nortec Humidity Ltd., except to the extent required for installation or maintenance of recipient’s equipment. Liability Notice Nortec does not accept any liability for installations of humidity equipment installed by unqualified personnel or the use of parts/components/equipment that are not authorized or approved by Nortec. Copyright Notice Copyright 2014, Nortec Humidity Ltd. All rights reserved. Contents 4 40 6 Humidifier Components Operation Humidifier Installation Requirements 7 Sequence Of Operation 40 Mounting with Keyholes 8 Drain Cycles 41 Location 10 Cylinders 43 Plumbing 12 User Interface 44 Electrical 45 Steam Distribution Systems 45 Steam Distributors 13 NH-EL Humidifier Models 45 Duct Distributors 14 Double Unit (150-200 lb/hr) 47 Blower Packs 15 Humidifier Features 48 17 Options Atmospheric Steam Distribution Lines 18 Accessories 48 Condensate 20 Humidifier Specification 51 Control System Design 20 24 Checklist Dimensions 50 NH-EL Control Inputs 50 Multi-Mode 29 Model Specifications 51 Analog Controls 32 Sample Specification 55 Digital Control 56 35 Total Humidification Load Duct Distribution Control Design 57 35 Base Humidification Load Calculating Space Distribution Control Design 57 Nortec Online 38 Moisture Content Equilibrium 59 Remote Fault Option 59 Warranty 38 Condensate Loss Table of Contents | 3 Humidifier Components High Water Sensor Plug Condensate Return Fill Cup Steam Outlet TEST NOTE: NH-EL 005-030 shown, component location may vary slightly for other models. Control Terminal Strip Cylinder Plug Cylinder Cylinder Strap Touch Screen Display Fill Valve Auxiliary Drain Switch On/Off Switch Drain Canal Door Interlock Switch Drain Valve Driver Board Contactor Remote Relay Board High Voltage Terminal Block Integrated Controller Transformer TEST Figure 1: NH-EL Humidifier Components 4 | Humidifier Components Description of Components Table 1: Humidifier Components Plumbing Cabinet Component Auxiliary Drain Switch Function of Component Drains water from cylinder by activating drain valve without software. Condensate Return Provides a connection to return condensate to the humidifier. Cylinder Plug Power connectors to the electrodes in the cylinder. Cylinder strap Reusable strap that securely holds the cylinder in place. Cylinder Water reservoir that supports the electrodes in the water. Prevents contactor from engaging when door is removed (pull out to override this safety feature while troubleshooting). Combines cylinder drain water and fill cup overflow into a single drain outlet. Supports the cylinder, drains water from humidifier, and provides a port for filling the cylinder from the fill cup. Door Interlock Switch Drain Canal Drain Valve Fill Cup Fill Valve High Water Sensor Plug Steam Outlet Contactor Electrical Cabinet Control Terminal Strip Driver Board High Voltage Terminal Block Integrated Controller On/Off Switch Remote Relay Board (option) Touch Screen Display Transformer Provides an air gap for backflow prevention and provides a gravity feed hose connection to the cylinder via the drain valve. Controls flow of water into the humidifier. Used to detect max water level in cylinder. Connects to atmospheric steam distribution system. Activated/Deactivates power to cylinder electrodes. Terminal strip for connecting external controls and blower pack to the humidifier. Provides input and output connections to humidifier components. Primary power connection from the disconnect to the humidifier. Controls all functions of the humidifier operation, provides a user interface for configuration of the humidifier. Switches power On/Off to the humidifier electronics. Note: Turn off humidifier disconnect to shut off primary power to the humidifier. Provides wiring connections to dry contacts which switch to indicate that the humidifier is on, humidifying, needs service, or is in a fault condition. User interface for configuring the humidifier. Steps primary voltage down to 24 VAC to power the low voltage electronics. Humidifier Components | 5 Operation The NH-EL is an atmospheric steam humidifier that generates steam with heat created from resistance to an electrical charge between multiple electrodes immersed in water. The NHEL is designed for air humidification with an atmospheric steam distribution system that Steam Line vents the generated steam into the conditioned environment. The electrode steam system produces pure uncontaminated steam with variable output of Steam Distributor 25% to 100% (inclusive) of the units rated capacity with a stability of +/-5%. Water borne minerals remain in the cylinder as water evaporates. Minerals are periodically flushed outCondensate Return through the adaptive cylinder drains. The adaptive drains operate based upon trending unit Fill Cup boil down cycles. This allows for better adaption to various water conditions and ensures Control Board Cylinder that system drains are only carried out when necessary, creating minimum waste water in Steam Line order to maintain optimum operating conditions. If not operated for three days the NH-ELOverflow Current Sensor High models drain automatically, this empties the steam cylinder asWater a preventative measure to Sensor Steam Distributor any excess scale organic growth. Solid mineral scale electrically insulates the electrodes, sinks to the bottom of the cylinder. When the electrodes are completely insulated the Electrodes Contactor Condensate Return cylinder is easily removed and replaced. Fill Cup Control Board Cylinder Drain Valve Steam Line Overflow Drain Canal Current Sensor External Air Gap High Water Sensor Internal Air Gap Steam Distributor Electrodes Contactor Condensate Return Fill Cup Fill Valve Control Board Cylinder Drain Valve Current Sensor Overflow Air Gap Drain Canal External Air Gap Internal Air Gap High Water Sensor Electrodes Contactor Fill Valve Drain Valve Air Gap External Air Gap Drain Canal Internal Air Gap Figure 2: Humidifier Schematic Air Gap 6 | Operation Fill Valve Sequence Of Operation Automated machinery may operate differently depending upon the various inputs and user configurable parameters. The sequence of operation detailed below may vary from observations depending upon the unique operating conditions of each humidifier. Note: When water in the cylinder makes contact with the energized electrodes, current flows between the electrodes through the water. The resistance of the water to the electrical current heats the water and turns it to steam. 1. When the humidifier receives electric input from external controls to produce steam, the humidifier will display the “Filling” status and power the contactor(s), passing electricity to the cylinder(s). The current transformer on the Driver Board monitors the flow of current (amps) to the cylinder for 60 seconds. As the current draw between the cylinder electrodes equates to the amount of heat and therefore steam produced, the current draw must be regulated to control steam production. 2. Active monitoring of the current draw will result in one of several possible outcomes, the two most common are detailed here: If the measured current draw is lower than the current draw that equates to the system demand and the high water sensor is not made, the system operation will continue to step 3. If the high water sensor is made system operation will skip to step 4. If the measured current draw is higher than the current draw that equates to the system demand but does not exceed 115% of the Full Load Amps, the system operation will skip ahead to step 5. Note: Two factors affect the current draw of the cylinder. (1) The surface area of the electrode exposed to water, greater exposure will increase current draw. (2) The total dissolved solids (TDS) of the supply water, higher TDS will result in increased conductivity of the water. Low TDS may prevent unit operation. 3. The humidifier will display the “Filling” status. The fill valve will activate and water will flow into the fill cup. Water from the fill cup flows into the bottom of the cylinder through a hose connected to the drain valve housing. The humidifier will continue to fill until the current draw matches the current draw that equates to system demand (100% demand equates to Full Load Amps) or the high water sensor detects that the cylinder is full. 4. Once the filling/draining cycles have stopped, the humidifier will display the “Humidifying” status. Water will continue to evaporate reducing the surface area of the electrodes exposed to the conductive water and therefore the current draw. If the filling cycle in step 3 was interrupted by the high water sensor activating, system operation will return to step 2 once the water evaporates below the high water sensor pin. Otherwise continue onto step 5. Operation | 7 5. As evaporation of the water continues and the current draw decreases accordingly, the control software measures the time for the current to decrease across a predetermined threshold (For further details see Drain Cycles on page 8). One of two outcomes will result from this measurement. The most common outcomes are detailed here: If the time for the boil down cycle is shorter than optimal, the Auto Adaptive Control System will initiate a drain cycle to replace the high conductivity water in the cylinder with fresh supply water. The fill valve will be active during these drain cycles to reduce waste water below 140°F/60°C. If the time for this boil down cycle is optimal or longer, the humidifier will not perform a mineral dilution drain. 6. To maintain steam production, system operation will loop back to step 2. Drain Cycles Concentrations of minerals will adhere to the cylinder electrodes, electrically insulating them and preventing efficient operation and shortening cylinder life. To minimize this while maintaining efficiency, the humidifier will initiate a draining process that will dilute the mineral content in the cylinder only when required and only the minimum volume to maintain optimal operation. Drain Activation Once the humidifier has achieved the desired current draw, the water in the cylinder will evaporate reducing the water level and therefore the current draw. This reduction in current draw will happen at different speeds depending upon the conductivity and volume of the water. More dissolved minerals will reduce the resistance of the water and allow for a smaller volume of water to maintain the same heat production/evaporation rate as a larger volume of lower conductivity water. The water level change associated to evaporating the smaller volume of more conductive water will have a greater impact on current draw and therefore reduce the current draw faster with higher conductivity water. The control board monitors the time required for the current draw to cross a pre-determined threshold. If the Actual Time (Ta) for the boil down across the predetermined thresholds is longer than the predetermined Optimal Time (To), this indicates that the water has not yet concentrated excessive amounts of minerals and a mineral dilution drain is not yet required. If the Actual Time (Ta) is shorter than a predetermined Optimal Time (To) it is indicative of water that has concentrated an excessive amount of dissolved minerals and a demineralization drain is initiated (see Figure 2). 8 | Operation Figure 2: Conductivity Measurement Drain Volume The volume of water that must be drained is calculated by the Auto Adaptive Control System. This algorithm establishes a proportional drain component based on the difference between the actual time of the latest boil down cycle (Ta) minus an optimal time (To). It then adds an integral drain component accumulated from previous drain cycles that will increase or decrease subsequent drain cycles ensuring more stable prolonged operation. In cases where a long drain is required the Control System breaks the drain time down into several small drains to prevent a reduction in the humidifier output capacity that would otherwise result from a long drain. During multi drains the system maintains the fill valve operation to assist in reducing the drain water temperature below 140°F/60°C and pulses the drain valve on for each partial drain (see figure 3). Figure 3: Multiple Short Drains Operation | 9 Cylinders A cylinder is the water reservoir for the humidifier. It consists of a plastic canister with a steam outlet, water inlet/outlet with strainer, separators and mounts for various electrodes to be immersed into the water. The NH-EL humidifiers ship with the standard cylinder indicated in Table 8 and Table 9 on page 29. The standard cylinder has been developed for optimum performance in the conductivity range of most potable water systems 330 – 670 µSiemens(µS). If required, the humidifier is easily adapted to operate with water conductivities outside this ideal range. This allows for operation with a total range of 1501250 µS. Consult with factory for details on adapting the humidifiers operation to accommodate water conductivities outside the standard operating range. Low Conductivity Cylinder - For improved operation on potable water between 150 and 330 µS, select a lower conductivity cylinder. (Alternative not available for 208-277v units with exception for 200 series cylinders) High Conductivity Cylinder - For improved operation on potable water between 670 and 1250 µS, select a higher conductivity cylinder. (Alternative not available for 480-600v units) Water Conditions Versus Cylinder Life The atmospheric steam output of the humidifier is pure and clean steam. During operation the dissolved minerals from the water supply are left behind in the cylinder. Many of these minerals will be removed during periodic flush cycles of the cylinder (for drain frequencies see Drain Cycles on page 8). Figure 4: Water Condition Versus Cylinder Life and Drains generalizes the effect of water hardness, and demand on cylinder life. Cylinder life is ultimately determined by the water chemistry, the unit running time, and output capacity setting. Cylinder Life Expectancy Capacity Adjustment Setting 100% 50% 25% 400 200 10 CaCO mg /L (p pm) Grains of Hardness 20 Conductivity of Water (µS/cm) 500 700 1000 600 800 500 600 400 400 300 200 200 100 100 5 500 1000 2000 4000 8000 Average Operating Hours Note: Other parameters may affect cylinder life. 0 0% 20% 40% 80% 0 100% Drain Rate as a Percentage of Steam Output Figure 4: Water Condition Versus Cylinder Life and Drains 10 | Operation 60% Total Dissolved Solids (ppm) 30 Nortec Electrode Drain Rates vs Water Conductivity with Auto-Adaptive Control 900 1200 800 Output Versus Cylinder Life Percent Of Full Steam Output The NH-EL series humidifier maintains full output capacity for the full life of the cylinder. Figure 5: Output Versus Cylinder Life illustrates the expected end of cylinder life performance. As minerals build-up on the electrodes in the cylinder, the patented AutoAdaptive Control System automatically raises the water level slightly in the cylinder. This exposes fresh electrode surface to water and maintains peak output and efficiency from the humidifier. Once the electrode surface is completely electrically insulated the user is alerted to change the cylinder. Other humidifiers’ performance may degrade gradually as the minerals adhere to the cylinder. By increasing the water level to expose fresh electrode surface, the NH Series will maintain maximum output throughout cylinder life. 100% 80% The nortec humidifiers maintain full output throughout its life. 60% Typical output of other types of humidifiers. Ability to produce steam decreases throughout its life. 40% 20% 0% NEW 3/4 1/2 1/4 REPLACE Cylinder Life Figure 5: Output Versus Cylinder Life Operation | 11 User Interface The NH-EL controller provides a large interactive touchscreen display, integrated digital communication protocols for building management system connectivity (BACnet, Modbus), and Internet monitoring via Nortec Online (NortecOnline.com). See Nortec Online on page 55 for more information. Touch Screen Display Provides status information as well as a user interface for configuring the humidifier. Status LED Single LED changes color to indicate status. Auxiliary Drain Switch (Can be used to drain cylinder without software) On/Off Switch (Turns humidifier On/Off) Door Interlock Switch (prevents contactor from engaging when door is open) NOTE: Pull out with door off to override. Figure 6: User Interface The Touch Screen Display - Allows for easy configuration of all features of the NH-EL humidifier and provides information indicating operating status, configurations, trend graphs and data of recent operation, service and fault messages, and troubleshooting information. One of the key features of the NH-EL controller is tracking operation and providing information about service requirements to make the humidifier easy to service and maintain. 12 | Operation NH-EL Humidifier Models The NH-EL is available in two different models; The standard model with distributor sold separately, and the “Space” model which comes with a blower pack distributor system attached directly to the top of the humidifier that facilitates direct humidification of the conditioned environment (See Figure 7: NH-EL Models). The NH-EL models come in capacities ranging from 5 lb/hr (2 kg/hr) to 200 lb/hr (90 kg/hr). For capacities exceeding 200lb/hr, up to 16 humidifiers can be linked together to operate from one set of control signals. NH-EL humidifiers are packaged in three different cabinets depending upon capacity. Table 8 on page 29 provides specifications for the NH-EL product line. NH-EL Space 050-100 NH-EL Space 010-050 NH-EL 010-050 NH-EL 050-100 NH-EL 150-200 Figure 7: NH-EL Models Humidifier Models | 13 Double Unit (150-200 lb/hr) NH-EL double units have two cylinders. The construction and installation of double units is identical to units with a single cylinder with the following exceptions: Two Cylinder units have two fill/drain connects and two driver boards (designated A and B). One driver board controls each cylinder (see Figure 7: NH-EL Models). Double units can operate both cylinders in sequence or parallel from a single set of control signals or independently based on two sets of control signals. Independent Operation – Each cylinder will operate independent of the other. Two sets of controls must be provided, one for each cylinder. Control wiring for each cylinder must be connected to the cylinder’s corresponding driver board/terminal strip. Parallel Operation – Both cylinders will respond equally to one set of controls. The control wiring must be connected to the A driver board/terminal strip. Sequence Operation –Both cylinders will respond in a staged fashion to one set of controls. Cylinder A’s output range is 0-100% of demand and Cylinder B’s output range is 50-100% of demand. The advantage of this configuration is that it allows the unit to achieve the lowest steam output of single control configurations by disabling one cylinder entirely and ramping down to the minimum 25% output capacity of the other cylinder. 14 | Humidifier Models Humidifier Features The NH-EL includes many advanced features that set it apart from other humidifiers. The following list outlines some of the NH-EL series features. For help in determining selection options use the Specification Checklist on page 20. Table 2: NH-EL Features Feature Touch screen interface Digital graphic display On/Off control Control and User Interface Features Up to two modulating control inputs per cylinder. Integrated PI controller Demand signal acceptance Digital communication protocols BTL certified Remote Fault Indication Nortec Online Independent circuits on multicylinder humidifiers Status indicator LED Adjustable units of measure Manual output adjustment Description Provides intuitive interface for configuring system features and settings. See page 12. Displays visual feedback on the humidifier inputs (conditioned environment humidity and set-points). See page 12. Provides the capability of regulating system operation with simple on/off controls. See page 50. Allows modulating humidifier output to improve accuracy of supply humidity. See page 54. Provides direct compatibility with humidity transducers ( RH sensor) with adjustable set points and P/I parameters. See page 50. Provides direct compatibility with modulating demand signals. See page 50. Allows for BMS interface with integrated BACnet IP/MSTP and Modbus protocols. See page 55. Provides BTL certified BACnet IP/MSTP & enables use of Lonworks. See page 55. Allows dry contact feedback on unit operation. See page 59. Complimentary access to the Nortec Online systems which allow remote access to view the operational status and history of the humidifier. See page 57. Allows for independent control of multiple humidifier cylinders through a common control system. See page 50. Provides quick reference feedback on system performance. See page 12. Display settings in Metric or Imperial units of measure. Provides the ability to limit the maximum steam production of the humidifier. NH-EL Standard Option Humidifier Models | 15 Table 2: NH-EL Features (Continued) Feature Auto pulse drain valve Full system drain Disposable cylinder Operation and Maintenance Auto Adaptive control system Drain water cooling Extreme drain water cooling Potable water operation Foam detection Advanced foam detection Backflow prevention Extended fill cup Safety door interlock switch Other Keep Warm Function Short cycling detection and correction Description Clears potential drain obstructions. Anti-fungal cylinder drain after three days with no demand. Time period is adjustable. Allows for fast, clean, simple service of the humidifier. See page 10. Efficient water consumption and humidifier performance. See page 88. 140°F/60°C tempered drain during normal and manual operation. See page 88. 120°F/49°C tempered drain during normal and manual operation. Compatible with standard potable water supplies. Standard foam detection and correction capability. Advanced foam detection and correction capability. Integrated air gap in fill cup provides protection for supply water systems. Allows for operation in excess of 5.5 in. W.C. See page 47. Reduces hazards to service personnel. Provides improved humidifier response time. Prevents operational problems associated to seasonal shifts in humidity load Certified to meet product standards as C-UL-US Listed detailed by Underwriters Laboratories. Provides guarantee against manufacturer Warranty defects. See Warranty on page 60. Allows for distribution to the conditioned Choice of steam distribution* environment directly with the Space model or indirectly via duct distributors. Provides convenient means of integrating Wall Mounting humidification needs. *NH-EL Space model includes distributor. 16 | Humidifier Models NH-EL Standard Option Options Note: Installation instructions are provided with each option and accessory. Table 3: NH-EL Options Availability Name Factory Installed Field Install Kit Application Blower packs are a distribution system capable of dispersing the steam created by the NH-EL directly into the conditioned environment. NH-EL Space models have these blower packs preinstalled with steam lines and condensate drainage. Remotely mounted blower packs are also available. See page 46 for more information. Remote Fault Indication Provides a PCB with four low voltage relays that operate depending upon the humidifier status. Status indicators include; Power Indication, Humidifying, Service, and Error relays. See Remote Fault Option on page 59 for more information. Control Setting at Factory Lonworks Digital Communication Built-On Blower Packs Provides a humidifier pre-configured for the requested control signal acceptances prior to leaving the factory. The humidifiers can be field reconfigured as needed. See page 21. Allows for digital communication via Lonworks communication protocol. Digital communication allows for detailed operational feedback and direct humidifier control. See page 55. For networks that require BTL certified BACnet digital communication instead of the integrated non BTL certified BACnet communication. Digital communication allows for detailed operational feedback and direct humidifier control. See page 55. BTL Certified BACnet Digital Communication Aux. Internal Fusing Advanced Foam Detection Provides an advanced level sensing control system for monitoring water levels inside the cylinder. Used to correct/prevent operational concerns associated with Foaming. Extreme Drain Water Cooling For installations where waste water must be cooler than the standard 140°F/60°C, this option reduces temperatures below 120°F/49°C. Fill Cup Extension For installations where duct static pressure exceeds 5.5 inches W.C (1.37 kPa). a fill cup extension kit can increase the maximum potential operating pressure of the humidifier to 10 inches W.C (2.49 kPa). Spare Cylinders Cylinders are the primary service component. Advisable to keep spare cylinders on site to ensure minimal down time. Provides extra internal protection to the humidifier, must always be used in conjunction with an external fused disconnect. See Table 5 on page 20 for part number information. Humidifier Models | 17 Accessories Table 4: Common Humidification Accessories Name Related Documentation Application External Condensate Cooling See pg. 47. Self-actuated and Electric condensate waste water coolers are available to reduce waste water temperatures below 140°F/60°C to meet regulations restricting the temperature of hot water that can be fed to drains. Steam Distributor Tubes 2556592 Steam Distributor Installation Manual Steam Distributor Tubes are used for adding steam into ventilation ducts. Available in three different steam capacities and various lengths to suit duct dimensions. SAM-e/Mini SAM-e Distributor Manifolds 1503529 SAMe Engineering Manual Remote Blower Pack 2572641 and pg. 46. The SAM-e Steam Distribution Manifolds are used for adding steam into ventilation ducts larger than 24 in (61 cm) where either higher steam capacity or short absorption is required. The Mini SAM-e is available in dimensions under 24 in (61 cm). Available in a range of sizes and steam capacities to match duct and humidifier requirements. Blower packs are used for direct humidification of the conditioned environment. Capable of dispersing up to 100lb/hr each, blower packs should be selected to match or exceed humidifier capacity. On/Off Humidistats See pg. 50. Nortec offers a range of digital and mechanical on/off duct and wall mounted humidistats for use with control and high limit applications. Modulating Humidistats See pg. 52. Nortec offers a range of digital modulating duct and wall mounted humidistats for use with control and high limit applications. Provides automatic humidistat set point reduction to prevent humidification that would cause condensation on windows/surfaces adjacent to outdoor air. 2520263 Duct Mount Temperature Sensor 2553858 Outdoor Mount Temperature Sensor Outdoor Temperature Sensors See pg. 52. Humidity Transducers See pg. 52. Nortec offers a range of digital humidity sensors for duct and wall mounting for use with control and high limit applications. Air Proving Switch See pg. 52. Provides a mechanical differential pressure switch to enable humidifier operation when ventilation ducts are operational. Adjustable for pressures 0.05 - 12” W.C (12.5-2989.1 Pa). See pg. 47. Provides a means of adapting steam line diameters to accommodate longer length steam lines from humidifier outlets to distributor inlet adapters. 1507846 – Steam Line Reducer 1.75” to 7/8 in. Copper 1508165 – Steam Line Reducer 1.75" to 7/8 in. S.S. Steam Line Reducers 18 | Humidifier Models Steam hoses are used as steam distribution lines or as couplers to copper or stainless steel steam distribution lines. When used for steam distribution the maximum recommended hose length is 10 ft (3 m). Steam hose is available in two sizes. Nortec Flexible Steam Hose Large / Small Condensate Trap See pg. 47. See pg. 47. Condensate hose can be used for draining condensate or coupling to copper or stainless steel condensate lines. 1328810 – Steam Supply Hose7/8 in. ID. per foot (30 cm) 1328820 - Steam Supply Hose 1 3/4 in.ID. per foot (30 cm) 1328840 – Condensate Hose 3/8 in. ID per foot (30 cm) Condensate traps must be used to remove condensate that forms in steam distribution lines. Nortec offers copper adapters to the condensate traps to match its large and small steam hose. 1329634 – Condensate Trap Small 7/8 x 7/8 x 3/8 1329635 – Condensate Trap Large 1 3/4 x 1 3/4 x 3/8 In-Line Water Filter and Replacement Filters N/A Inline water filter for supply water which contains sediment that could obstruct the fill valve strainer or drain fittings. 1329505 - In-Line Water Filter 5 Micron Filter 1329561 - Replacement Water Filters 1 Micron 1329506 - Replacement Water Filters 5 Micron Condensate Pump N/A High temperature condensate pump for pumping waste water from the NH-EL or condensate from the distributor systems. 1429527 - Drain Water Sump Pump, low flow Drain Air Gap Reducer Pocket HygroThermometer digital display Transformer, Plug In, 120 VAC to 24 VAC See pg. 43 N/A N/A All NH-EL humidifiers require an air gap on the drain line as close as possible to the humidifier. This air gap reducer is a copper 2:3/4 in. (19.05:50.8mm) OD fitting that can provide the drain air gap. 2522172 - External Drain Air-Gap Reducer The pocket hygro thermometer provides a means for easily checking the humidity and temperature in a space. Useful tool for troubleshooting humidity problems. 1469595 - Pocket Hygro-Thermometer Digital Display “Wall Wart” AC adapter 120 VAC to 24 VAC 40VA for providing power to remote electronics/controls. 1603032 - Transformer, Plug In, 120 VAC to 24 VAC Humidifier Models | 19 Humidifier Specification Checklist The following checklist can be used to specify the NH-EL Series Humidifier. It is strongly advised to use the free Nortec H.E.L.P. software (www.NortecHELP.com) to assist in humidifier sizing and accessory selection. Humidifier Humidifier Capacity - See Total Humidification Load on page 35. Select a humidifier, or combination of humidifiers that exceeds the total humidification load. 005 lb/hr 010 lb/hr 020 lb/hr 030 lb/hr 050 lb/hr Quantity: Quantity: Quantity: Quantity: Quantity: 075 lb/hr Quantity: 100 lb/hr Quantity: 150 lb/hr Quantity: 200 lb/hr Quantity: Humidifier Electrical - See on Table 3 on page 17. Voltage: Phase: Disconnect: Humidifier Part Number: Cylinder - Optimise performance with the correct cylinder for supply water conductivity. Standard (330-670µS) Low Conductivity (150-330µS)(alternative not available for 208-277v units) High Conductivity (670-1250µS)(alternative not available for 480-600v units) Optional Aux. Internal Fusing – Supplemental overcurrent protection. (Not a substitute for an external disconnect). Part Number: 3 Phase 1 Phase Table 5: Aux. Internal Fusing Part Numbers Capacity 005 110-120V 2574100 208V 220-240V 277V 380V 440-480V 550-600V 010 2574101 2574101 2574101 2574102 2574102 2574102 020 2574104 2574105 2574105 2574106 2574106 2574106 020 2574103 2574103 2574107 2574107 2574107 030 2574108 2574108 2574109 2574109 2574109 050 2574110 2574110 2574111 2574112 2574112 075 2574113 2574113 2574114 2574115 2574116 100 2574117 2574117 2574118 2574118 2574119 150 2574120 2574120 2574121 2574122 2574123 200 2574124 2574124 2574125 2574125 2574126 20 | Humidifier Specification Extreme Drain Water Cooler – Used to reduces waste water to below 120°F/49°C 2574078 – Factory installed for NH-EL 005-020lb/hr 2574080 – Factory installed for NH-EL 030 lb/hr 2574082 – Factory installed for NH-EL 050-075 lb/hr 2574084 – Factory installed for NH-EL 100 lb/hr 2574086 – Factory installed for NH-EL 150 lb/hr 2574088 – Factory installed for NH-EL 200 lb/hr Other Options - For more NH-EL options see Table 3 on page 17. Remote Fault Indicator (see page 59) – to provide remote operational feedback Advanced foam detection – for use with softened water. In-line water filters (see Table 4 on page 18) Controls Humidifier Control Signal Acceptance - Optional factory configuration of controls. Factory configuration eliminates the need to reconfigure the NH-EL in the field. See NH-EL Control Inputs on page 50. Part No: Table 6: Control Acceptance – Part Numbers Signal 0-5 VDC 0-20mA 4-20 mA 0-10 VDC 0-16 VDC 1-5 VDC 2-10 VDC 0-20 VDC Demand Acceptance Transducer Acceptance Single Channel Dual Channel Single Channel Dual Channel 2523060 2523062 2523064 2523066 2523090 2523092 2523094 2523096 2523061 2523063 2523065 2523089 2523091 2523093 2523095 2523097 2523100 2523102 2523105 2523110 2523112 2523114 2523116 2523118 2523101 2523104 2523107 2523111 2523113 2523115 2523117 2523119 Humidity Controls – Required for automated regulation of humidifier operation. See Control System Design on page 50. Air Proving Switch – Required for humidification into ventilation ducts/air handlers. 1603032 Optional Transformer, Plug In, 120 VAC to 24 VAC (see Table 4 on page 18). 2520263 Duct mount outdoor temperature setback sensor – prevents window condensation. 2553858 Exterior mount outdoor temperature setback sensor – prevents window condensation. Control Humidistat Part No: High Limit Humidistat Part No: Humidifier Specification | 21 Table 7: Nortec Humidistats Demand Part Num. Duct Mount 2548732 2548731 2520273* 1510142 2520266* 1329102 1329108 1509858 1509857 Wall Mount Transducer Duct Mount Wall Mount Digital Mech. 0-10 VDC 2-10 VDC On/Off Fan Start *Remotely mounted digital controller included to provide ease of access. Digital Communication Protocol – For interface with building automation systems(see Digital Control on page 55 or Nortec document 2574199 BACnet/Lonworks Supplemental manual). BACnet IP/MSTP (Standard) Modbus (Standard) Nortec Online (Standard) 2574194 BACnet Tested Laboratories certified BACnet IP – For BTL certified networks 2574193 BACnet Tested Laboratories certified BACnet MS/TP – For BTL certified networks 2574194 Lonworks Steam Distribution Select a distributor that exceeds the production capacity of the humidifier(s), fits the duct/air handler size (if applicable), and accommodates the steam outlet connections to the humidifier. Options - See Steam Distribution Systems on page 45. 1710010 –140°F/60°C Self-Actuated Condensate Cooler. 1710020 – 140°F/60°C 24V Electric Condensate Cooler. 2572615 – Remote blower pack 005-100lb/hr, 110-120V, 1 Phase. (see Blower Packs on page 46) SAM-e (See 1503529 SAM-e Engineering manual for selection information) Steam Inlet Adapter: SAM-e Header: Steam Tubes: Quantity: Insulation (Improves energy efficiency by as much as 70%) Mounting Frame (required for vertical duct installation) Steam Distributor (See 1506117 Steam Distributor Installation manual) Part Number: 22 | Humidifier Specification Quantity: Steam Hose (See Atmospheric Steam Distribution Lines on page 47.) 1328810 Hose 7/8 in. ID. 1328820 Hose 1 3/4 in. ID. 1328834 Hose 3/8 in. ID. Steam Tube Length: Steam Tube Length: Condensate Tube Length: Steam Line Reducers (For adapting the steam line diameter to various fittings) 1507846 –1¾ to 7/8 in. Copper 1508165 - 1¾"o 7/8 in. Stainless Steel Quantity: Quantity: Steam Line Tee (For steam line condensate drainage) 1329634 – Small Tee adapter 7/8 x 7/8 x 3/8 1329635 – Large Tee adapter 1 3/4 x 1 3/4 x 3/8 Quantity: Quantity: Humidifier Specification | 23 Dimensions Figure 8: NH-EL 005-030 Physical Data & Dimensions 24 | Humidifier Specification Figure 9: NH-EL 050-100 Physical Data & Dimensions Humidifier Specifications | 25 Figure 10: NH-EL 150-200 Physical Data & Dimensions 26 | Humidifier Specification Empty Weight 005-010 Full Weight 020 030 Water Inlet Pressure Clearance Front Clearance Left and Right Clearance Floor Clearance Ceiling 83lbs (38kg) 93 lbs (42kg) 103lbs (47kg) 118lbs (54kg) 30-80 PSI (2.07 – 5.52 BAR) Blower Pack Speed Setting LOW HIGH 132in. 120in. (355.3cm) (305cm) 12in. 12in. (30.5cm) (30.5cm) 12in. 12in. (30.5cm) (30.5cm) 24in. 24in. (61cm) (61cm) Clearances based upon 72°F (22.2°C), 43% RH with blower on High speed setting. See Location on page 41. Figure 11: NH-EL Space 005-030 Physical Data & Dimensions Humidifier Specifications | 27 Empty Weight Full Weight Water Inlet Pressure Clearance Front Clearance Left and Right Clearance Floor Clearance Ceiling 123lbs (56kg) 188 lbs (85kg) 30-80 PSI (2.07 – 5.52 BAR) Blower Pack Speed Setting LOW HIGH Not 248in. recommended (630cm) Not 30in. recommended (76cm) Not 24in. recommended (61cm) Not 36in. recommended (91cm) Clearances based upon 72°F (22.2°C), 43% RH with blower on High speed setting. See Location on page 41. Figure 12: NH-EL Space 050-100 Physical Data & Dimensions 28 | Humidifier Specification Model Specifications Table 8: NH-EL Specifications Phase Capacity lb (kg) 5 (2.3) 10 (4.5) 1 20 (9) 20 (9) 30 (13.5) 3 50 (22.5) 75 (34) 100 (45) Voltage NH-EL Part No. Amps Max Ext Fuse KW Standard Cylinder 110-120 208 220-240 277 380* 440-480 550-600 208 220-240 277 380* 440-480 550-600 208 220-240 380* 440-480 550-600 208 220-240 380* 440-480 550-600 208 220-240 380* 440-480 550-600 208 220-240 380* 440-480 550-600 208 220-240 380* 440-480 550-600 2573379 2573380 2573382 2573383 2573384 2573385 2573386 2573388 2573389 2573390 2573391 2573392 2573393 2573394 2573395 2573396 2573397 2573398 2573399 2573400 2573401 2573402 2573403 2573404 2573405 2573406 2573407 2573408 2573409 2573410 2573411 2573412 2573413 2573414 2573415 2573416 2573417 2573418 15.9 18.3 15.9 13.7 9.8 7.9 6.3 36.6 31.7 27.5 19.7 15.9 12.7 21.1 18.3 11.4 9.2 7.3 31.7 27.5 17.1 13.7 11.0 51.9 45.0 28.4 22.4 18.0 77.9 67.4 42.6 33.8 27.0 94.4 90.0 56.8 45.0 36.0 20 25 20 20 15 15 15 45 40 35 25 20 20 30 25 15 15 15 40 35 25 20 15 70 60 40 30 25 100 90 60 45 35 125 125 80 60 45 1.9 3.8 3.8 3.8 3.8 3.8 3.8 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 11.4 11. 4 11.4 11.4 11.4 18.7 18.7 18.7 18.7 18.7 28.1 28.1 28.1 28.1 28.1 34.0 37.4 37.4 37.4 37.4 202 202 202 202 203 204 204 321 321 321 305 309 309 303 303 311 311 311 421 421 407 411 411 621 621 603 605 605 621 621 603 605 605 621 621 603 605 605 * 50 Hertz, not UL listed Fill gal (l) per min 0.13 (0.5) 0.13 (0.5) Net/Full Weight lb (kg) 45/55 (21/25) 0.13 (0.5) 45/65 (21/30) 0.13 (0.5) 0.3 (1.2) 45/80 (21/37) 0.5 (2.0) 0.5 (2.0) 85/150 (39/68) 0.9 (3.3) ** Per cylinder basis. Humidifier Specifications | 29 Table 8: NH-EL Specifications Continued Phase Capacity lb (kg) 150 (68) 3 200 (90) Voltage NH-EL Part No. Amps Max Ext Fuse KW Standard Cylinder 208 220-240 380* 440-480 550-600 208 220-240 380* 440-480 550-600 2573419 2573420 2573421 2573422 2573423 2573424 2573425 2573426 2573427 2573428 155.8 135.0 85.2 67.4 54.0 188.7 180.0 113.7 90.0 72.0 200 175 110 90 70 250 225 150 125 90 56.1 56.1 56.1 56.1 56.1 68.0 74.8 74.8 74.8 74.8 621 621 603 605 605 621 621 603 605 605 * 50 Hertz, not UL listed 30 | Humidifier Specification ** Per cylinder basis. Fill gal (l) per min Net/Full Weight lb (kg) 0.5** (2.0**) 120/245 (55/112) 0.9** (3.3**) Table 9: NH-EL Space Specifications Phase Capacity lb (kg) 5 (2.3) 1 3 Volts 110-120 208 220-240 277 10 (4.5) 380* 440-480 550-600 208 220-240 277 20 (9) 380* 440-480 550-600 208 220-240 380* 20 (9) 440-480 550-600 208 220-240 30 380* (13.5) 440-480 550-600 208 220-240 50 380* (22.5) 440-480 550-600 208 220-240 380* 75 (34) 440-480 550-600 208 220-240 380* 100 (45) 440-480 550-600 NH-EL Space Part No. 2573429 2573430 2573431 2573432 2573433 2573434 2573435 2573436 2573437 2573438 2573439 2573440 2573441 2573442 2573443 2573444 2573445 2573446 2573447 2573448 2573449 2573450 2573451 2573452 2573453 2573454 2573455 2573456 2573457 2573458 2573459 2573460 2573461 2573462 2573463 2573464 2573465 2573466 Amps 17.2 19 16.5 14.2 10.2 8.2 6.6 37.3 32.3 28 20.3 16.2 13 21.8 18.9 11.9 9.5 7.6 32.4 28.1 17.8 14 11.3 52.6 45.6 28.7 22.7 18.3 78.6 68 43 34.1 27.3 95.1 90.6 57.1 45.3 36.3 Max Ext Fuse 25 25 25 20 15 15 15 45 40 35 25 20 20 30 25 15 15 15 40 35 25 20 15 70 60 40 30 25 100 90 60 45 35 125 125 80 60 45 KW 2.1 4 4 4 4 4 4 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 11.7 11.7 11.7 11.7 11.7 18.9 18.9 18.9 18.9 18.9 28.3 28.3 28.3 28.3 28.3 34.2 37.7 37.7 37.7 37.7 StandFill ard gal (l) Cylinder per min 202 0.13 (0.5) 202 202 202 203 204 204 321 321 321 305 309 309 303 303 311 311 311 421 421 407 411 411 621 621 603 605 605 621 621 603 605 605 621 621 603 605 605 Net/Full Weight lb (kg) 83/93 0.13 (0.5) (38/42) 0.13 (0.5) 83/103 (38/47) 0.13 (0.5) 0.3 (1.2) 83/118 (38/54) 0.5 (2.0) 0.5 (2.0) 123/188 (56/85) 0.9 (3.3) * 50 Hertz, not UL listed Humidifier Specifications | 31 Sample Specification PART 1 - GENERAL 1.1 Work Included: a. Nortec NH-EL Series electrode steam humidifier[s] as indicated on drawing[s] and as indicated on schedule[s]. b. Complete and operable humidification system [which meets applicable building codes] c. Equipment start-up and project inspection by qualified factory trained representative. 1.2 Quality Assurance: a. Certifications, C-UL US Listed. b. ISO 9001-2008. c. ANSI/NFPA 70 - National Electrical Code. d. ARI 640, "Standard for Commercial and Industrial Humidifiers. e. ASHRAE SSPC 135 BACnet 1.3 Related Sections: a. 23 Mechanical General b. 23[ ] Piping Installation c. 23[ ] Control System 1.4 Submittals: a. Submit product data under provisions of Section 23. Include product description, model, dimensions, component sizes, rough-in requirements, service sizes, and finishes. Include rated capacities, operating weights, furnished specialties, and accessories. b. Submit manufacturer's installation instructions. c. Submit operation and maintenance data. d. Submit coordination drawings. Detail fabrication and installation of humidifiers. Include piping details, plans, elevations, sections, details of components, and dispersion tubes. Detail humidifiers and adjacent equipment. Show support locations, type of support, weight on each support, and required clearances. e. Submit wiring diagrams including power, signal, and control wiring. Differentiate between manufacturer-installed and field-installed wiring. f. Submit minimum water quality requirements and water pressure requirements. 1.5 Schedules: a. Refer to information contained in schedule[s] attached to this specification. b. Humidifiers to be of type, capacity, and arrangement as listed in schedule[s]. c. Include accessories listed in schedule[s] and those accessories required for type of unit. ELECTRODE STEAM HUMIDIFICATION SYSTEM - NORTEC MODEL NH-EL PART 2 - PRODUCTS 2.1 Provide Nortec NH-EL electrode humidifier generating mineral-free, sterile steam from a potable water supply Packaged unit, wall mounted, atmospheric steam generation using an electrode steam cylinder[s]. Resistive element technology and boiler steam (pressure steam) technology not acceptable. 32 | Humidifier Specification 2.2 Unit[s] to be complete with: a. Touchscreen controller with standard building automation and Online connectivity: i. Intuitive touchscreen control with color graphic user interface. ii. Standard building automation communication protocols BACnet IP, BACnet MSTP and Modbus. Additional hardware required for building automation communication not acceptable. iii. Standard Nortec Online connectivity for remote monitoring and factory diagnostic. iv. Embedded web interface for easy configuration and remote monitoring from any computer with a web browser over a local area network (LAN) connection. v. USB interface for new software/feature upload and download of operational information. vi. Single or dual channel analog signal acceptance, supporting both demand and transducer control. Ability to control set point from humidifier control when using transducer controls. b. Standard remote monitoring with Nortec Online i. Integrated hardware and software allows for remote end-user and factory diagnostic of humidifier(s) via the internet. ii. Humidifier parameter data and performance trending data can be exported remotely using the internet. iii. Humidifier will be accessed via the internet by registering humidifier to www.norteconline.com. Controls contractor to provide internet access to humidifier through Ethernet cable with RJ-45 connection. c. Packaged system with Nortec electrode cylinder technology: i. Nortec cylinder optimized for humidifier capacity and supply voltage. Cylinder must have welded seam to ensure watertight and have high water sensor to prevent overfilling. ii. Durable powder coated steel cabinet with zero side clearance requirement for minimal footprint (excluding distribution attachments). iii. Insulating air gap between plumbing and electrical compartment for increased electronic reliability. iv. Standard internal drain water tempering to ensure maximum 140°F [60°C] drain water. External drain water cooler not acceptable. v. Integral fill cup with minimum 1-inch [25 mm] air gap to prevent back siphoning. vi. Full cylinder indication and pre-notification of automatic shutdown at end of cylinder life. vii. Automatic pulse feature to clean any obstruction from the drain solenoid valve if required. viii. Automatic off-season shut-down [after 3 days of "no call"] will completely drain the cylinder[s] and automatically restart on call for humidity. Adjustable on/off and time sequence. Provides extended cylinder life, while ensuring stagnant water does not remain in the system. ix. Plumbing door interlock safety switch to allow power interruption when installing or servicing the humidifier. d. Nortec Auto-Adaptive Control water management: i. Advanced water management utilizing the patented Proportional plus Integral Auto-Adaptive Control system for optimal energy efficiency, water usage and cylinder life. ii. 98% thermal efficiency from startup until end of cylinder life. iii. Drains automatically optimized to water conditions to maximize cylinder and reduce water usage. Humidifier Specifications | 33 iv. Modulating output between 20% and 100% of rated capacity. 2.3 Optional Accessories a. Refer to 'Option schedule' PART 3 - EXCECUTION 3.1 Installation: a. Install humidifiers per manufacturers' instructions. b. Install with required clearance for service and maintenance. 3.2 Accessories: a. Install accessories in accordance with manufacturer's recommendations. 3.3 Commissioning: a. Start-up of humidifier to be by factory trained technician. 34 | Humidifier Specification Total Humidification Load The total humidification load is the sum of three primary considerations: Base Humidification Load - The humidification load required to increase unconditioned supply air, from the worst case scenario, to meet the design requirements for the conditioned environment. This is typically the largest contributing factor to the total humidification load. See page 35. Moisture Content Equilibrium - Materials stored in a conditioned environments may retain moisture content out of equilibrium with the moisture content of that environment. Depending upon the hygroscopic principals of the material it may have an equalizing effect on the environment, thereby increasing or decreasing the relative humidity. See page 38. Condensate Losses – Convection heat transfer from steam in the steam distribution system will revert the steam to a liquid state, detracting from the gross humidifier output. See page 38. Safety Margin –Once all other considerations have been made, it may be prudent to increase the capacity of the humidifier if the design conditions are going to regularly keep the unit operating at or near or maximum operational capacity. Nortec provides a convenient method to calculate the humidification load for any application with our online program - Humidifier Engineering and Load-sizing Program (H.E.L.P.). Additionally this program can also assist with absorption distance calculations, selection of humidifiers, distributors, controls, and accessories. For access to this program please go to: www.NortecHelp.com There are tutorials on the use of this program available from the Literature & Media section of the Nortec website www.Humidity.com. Additional information on the effects of humidity, calculating relative humidity, load calculations and recommended design conditions can be found in the Nortec Humidification Load Calculation manual (2553856). Base Humidification Load Calculating Total Unconditioned Air Supply Volume The total volume of incoming unconditioned air per hour, forced and naturally ventilated, must be determined. The incoming volume depends on the construction of the conditioned environment and the type of air circulation system used. Forced Ventilation – Typically, an air handler system will exchange a fixed percentage of conditioned air for unconditioned air. This unconditioned air is the volume of air that requires humidification. Air handler systems vary by design but will rely upon adding or removing volumes of air from a controlled environment. Air handling systems that add air to the conditioned environment will have a total forced air volume equivalent to the unconditioned supply air volume. Air handling systems that exhaust air from the conditioned environment must have at least an equal volume of unconditioned air reintroduced; That equal volume of unconditioned air will be the total forced air volume. Humidification Load | 35 Accounting for Economizer Cycles - Under normal heating conditions the unconditioned supply air volume is usually relatively small to avoid large heating and conditioning treatments. However when the economizer cycle is in operation, the unconditioned air volume may be as high as 100% of the total ventilation. To calculate the humidification load for a system with an economizer cycle the air ventilation and thermal load must be calculated for each month in which the economizer mode may operate to determine the highest humidification load. Natural Ventilation – A system that does not rely upon direct mechanical means to provide air ventilation to the conditioned environment. Air will ventilate through openings in the building envelope. The amount of makeup air is calculated based on the volume of the conditioned space and an estimate of air changes per hour. Unconditioned Supply Air Moisture Once the total volume of unconditioned supply air is known, the moisture content of this air must be determined. To ensure the humidifier capacity will be able to satisfy design conditions, we must base our calculations off the lowest unconditioned supply air temperatures and humidity that can be expected on a yearly basis. In applications where the unconditioned supply air will be drawn from the local atmosphere, Nortec advises utilizing the weather data compiled by geographic location published by the ASHRAE Climate Data Centre. Once the lowest temperature for the given geographic location is known, use Table 10 (IP units) or Table 11 (SI units) on page 37 to determine the moisture (lb) per cubic foot of air at 100% humidity. Multiply the 100% moisture content by the lowest humidity levels for the geographic location. Max Supply Moisture(lb/cu.ft) = The 100% RH moisture content obtained from the tables on page 37 for the lowest anticipated supply air temperature for the unconditioned air source. Low Humidity(%) = The lowest anticipated humidity (percentage of Relative Humidity) for the unconditioned supply air source. Conditioned Air Moisture The moisture content for the designed air conditions must be determined. To ensure the humidifier capacity will be able to satisfy design conditions, we must base our calculations off the highest desired design air temperatures and humidity. Once the highest design temperature and highest humidity have been determined for the application, use Table 10 (IP units) or Table 11 (SI units) on page 37 to determine the moisture (lb) per cubic foot of air at 100% humidity. Multiply the 100% moisture content by the highest required humidity levels for the conditioned environment. Max Supply Moisture(lb/cu.ft) = The 100% RH moisture content obtained from the tables on page 37 for the highest design air temperature. Design Humidity(%) = The highest required humidity (percentage of RH) for the design conditions. 36 | Humidification Load Base Humidification Load The base humidification load equates to the difference between the Conditioned Air Moisture(lb/cu.ft) and Supply Air Moisture(lb/cu.ft) multiplied by the hourly Unconditioned Air Supply Volume (CFM). Base Load Base humidification load as determined by calculating the moisture required to bring the unconditioned supply air to meet the conditioned air requirements. Supply Air Unconditioned Air Supply Volume in cubic feet of air per hour as obtained from Total Unconditioned Air Supply Volume on page 35. Conditioned Air Moisture Conditioned Air Moisture in pounds per cubic foot as obtained from page36. Supply Moisture Unconditioned Supply Air Moisture in pounds per cubic foot as obtained on page 36. Table 10: Moisture Content of Air at 100% RH (IP units) °F -20 -10 -5 0 5 10 15 20 25 30 31 32 33 34 35 36 37 38 39 40 lb/cu.ft 0.0000343 0.0000414 0.0000500 0.0000686 0.0000871 0.000111 0.000141 0.000177 0.000223 0.000279 0.000291 0.000304 0.000316 0.000327 0.000340 0.000353 0.000366 0.000380 0.000394 0.000409 °F 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 lb/cu.ft 0.000424 0.000440 0.000457 0.000474 0.000491 0.000509 0.000527 0.000547 0.000567 0.000587 0.000609 0.000630 0.000651 0.000674 0.000699 0.000723 0.000747 0.000773 0.000800 0.000829 °F 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 lb/cu.ft 0.000857 0.000886 0.000916 0.000946 0.000979 0.00101 0.00104 0.00108 0.00111 0.00116 0.00119 0.00123 0.00127 0.00131 0.00135 0.00139 0.00144 0.00149 0.00154 0.00158 °F 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100 lb/cu.ft 0.00163 0.00168 0.00173 0.00178 0.00184 0.00190 0.00195 0.00201 0.00207 0.00213 0.00220 0.00226 0.00233 0.00240 0.00247 0.00254 0.00262 0.00269 0.00277 0.00285 °F 101 102 103 104 105 106 107 108 109 110 111 112 113 114 115 120 125 130 135 140 lb/cu.ft 0.00293 0.00302 0.00310 0.00319 0.00328 0.00337 0.00347 0.00356 0.00366 0.00376 0.00387 0.00397 0.00408 0.00419 0.00430 0.00491 0.00559 0.00634 0.00719 0.00812 Humidification Load | 37 Table 11: Moisture Content of Air at 100% RH (SI units) °C kg/cu.m °C kg/cu.m °C kg/cu.m °C kg/cu.m °C kg/cu.m -30 -29 -28 -27 -26 -25 -24 -23 -22 -21 -20 -19 -18 -17 -16 -15 -14 -13 -12 -11 0.000578 0.000553 0.000540 0.000540 0.000551 0.000573 0.000606 0.000650 0.000704 0.000769 0.000845 0.000931 0.00103 0.00113 0.00125 0.00138 0.00152 0.00167 0.00183 0.00200 -10 -9 -8 -7 -6 -5 -4 -3 -2 -1 0 1 2 3 4 5 6 7 8 9 0.00218 0.00238 0.00259 0.00281 0.00305 0.00330 0.00357 0.00385 0.00415 0.00447 0.00481 0.00516 0.00554 0.00594 0.00636 0.00680 0.00727 0.00777 0.00829 0.00884 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 0.00943 0.0100 0.0107 0.0114 0.0121 0.0129 0.0137 0.0145 0.0154 0.0163 0.0173 0.0183 0.0194 0.0206 0.0218 0.0230 0.0243 0.0257 0.0272 0.0287 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 0.0303 0.0320 0.0337 0.0356 0.0375 0.0395 0.0416 0.0438 0.0461 0.0485 0.0510 0.0536 0.0563 0.0592 0.0621 0.0652 0.0685 0.0718 0.0753 0.0790 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 0.0828 0.0867 0.0908 0.0951 0.0995 0.104 0.109 0.114 0.119 0.124 0.130 0.136 0.142 0.148 0.154 0.161 0.168 0.175 0.182 0.190 Moisture Content Equilibrium Materials stored in conditioned environments may retain moisture content out of equilibrium with the moisture content of that environment. Depending upon the hygroscopic principals of the material it may have an equalizing effect on the environment, thereby increasing (desorption) or decreasing (absorption) the Relative Humidity (RH) of the surrounding environment. Any materials stored in the conditioned environment that may emit or absorb significant moisture from the atmosphere should have the hygroscopic principals of that material assessed with the manufacturer. Once the severity of this influence is known it should be incorporated into the total humidification load. Hygroscopic Regain – is defined as the amount of water a completely dry material will absorb from the air through desorption or adsorption. Any hygroscopic product that is purchased and sold by weight must have a carefully controlled environment. Condensate Loss Convection heat transfer from steam in the steam distribution system will revert the steam to a liquid state, detracting from the gross humidifier output. An estimate of the condensate losses throughout the distribution system should be done to ensure the total humidifier capacity, less this condensation loss, will still satisfy the total load requirement. 38 | Humidification Load Distributor Losses - The distributor system is often the largest contributor to condensate losses in a properly designed distributor system. These losses can be minimized by installing insulation kits available for most advanced distributors. The amount of humidification lost to condensation is dependent upon the design of the distributor system. Reference the engineering guide of the distributor for specific condensation loss information. Additional information on calculating condensate loss and the savings of insulating distributors can be found in Nortec white paper “Nortec Stainless Steel Air Gap Insulation R Value”. Supply Line Losses – Condensate losses per linear foot can be roughly estimated in a system with properly designed atmospheric steam lines. Total length of the atmospheric steam line must be taken into account, that is the sum of linear length of the tube and equivalent length of every fitting. For equivalent lengths of common fittings see Table 12. Once total equivalent linear length is determined, Table 13 can be used to estimate the humidifier capacity lost to supply line losses. For design information on steam lines see Atmospheric Steam Distribution Lines on page 47. Table 12: Approximate Equivalent Length of Atmospheric Steam Line Fittings Nominal tube Standard size 90° elbow 0.75” - 0.875” 2 ft 1.5” - 1.75” 3.5 ft 3” 5 ft 4” 8 ft *Valve in full open position. Standard 45° elbow 1 ft 1.75 ft 2.5 ft 4 ft Side-outlet tee 4 ft 7 ft 11 ft 15 ft Full Bore Gate valve* 0.4 ft 0.8 ft 1.1 ft 1.6 ft Globe valve* 18 ft 34 ft 54 ft 80 ft Note: Nortec stainless steel air-gap insulation provides one method for reducing a distributor losses and conserving energy. See Nortec publication 1503529 – SAM-e Engineering Manual for more information on specifying SAM-e insulation. Table 13: Approximate Condensate per Foot of Atmospheric Steam Line Steam MED-L copper tube Stainless steel Steam loss per capacity nominal steam line tube (thickness foot in (lbs/hr)* size 0.065”) condensation 4-30 0.75” 0.875” 0.06 lbs/ft 30-100 1.5” 1.75” 0.11 lbs/ft 200-300 3” 3” 0.16 lbs/ft 400-660 4” 4” 0.22 lbs/ft Note: Based on 1” pipe insulation at 3” W.C. duct static pressure. *Inclusive. Humidification Load | 39 Humidifier Installation Requirements Caution: The following sections provide an outline of the installation requirements. For detailed installation instructions refer to Document No. 2570435 NH-EL Installation Manual Mounting with Keyholes 1. The NH-EL Series humidifier is wall mounted using keyholes on the back of the cabinetry. 2. Use #12 x 3 in. (7.5 cm) screws mounted into 2x4 studs or better. Two screws are needed for a single unit (005 to 100lb/hr). Three screws are needed for a double unit (150 to 200lb/hr). 3. Fasten the “L” brackets to the top of the humidifier using the appropriate wood screw into the mounting studs to secure the unit from any upward motion. Note: Use screws longer than 3 in. (7.5 cm) if drywall or other spacer is present (supplied by others). SPACE B A Insert screws so that 1/4 in. (6 mm) exposed, hang unit, tighten screws. Install “L” bracket after hanging humidifier #12 x 3 in. (7.5 cm) Wood Screws Unit Size 5-30 50-100 150-200 Screws 2 2 3 Dim A in (cm) . 12 (30.5) 16 (40.6) 16 (40.6) Dim B in. (Cm) 16 (40.6) SPACE Figure 13: Mounting With Keyholes 40 | Humidifier Installation Location Mount on a suitable wall or vertical surface. Do not sit the unit on the floor. Allow clearances required for plumbing and electrical connections. Install only in areas with ambient temperature 41-104°F (5–40°C), relative humidity 5 - 95% RH (noncondensing). Blower packs should not be installed near cold surfaces or where dew point may be reached. The humidifier cannot be used as a structural member. All piping connected to the unit must be supported independently. Ensure mounting surface can support the full weight of the humidifier and accessories. Specific humidifier weights are detailed in Table 8 on page 29 and Table 9 on page 29. Install in a location that facilitates regular maintenance and where; electrical, water, drain (with proper slope), connections can be made to the humidifier. When possible, install below the steam distributor. Take care to provide proper steam line routing and proper condensate traps as per the Steam Distribution section on page 22. DO NOT locate the humidifier any further then absolutely necessary from the steam distributor. Net output will be reduced as a result of efficiency loss of steam lines. Clearance dimensions shown are for reference only and are the minimum required for maintenance of the humidifier. Consult local and national codes before final location and installation. Nortec does not accept responsibility for installation code violations. *Side clearance not required, only recommended for ease of service access. (See Table for Blowerpack clearances) (See Table for Blowerpack clearances) 5-95% (See Table for Blowerpack clearances) 6 in. (15 cm) Recommended Side Clearance Mount Humidifier Level 36 in. (91.5 cm) Min. Front Clearance If Blowerpack is used, mount so that the steam outlet is at least 96 in. (244 cm) above ground level. 24 in.(61 cm) Min Height Figure 14: Installation Location/Clearance Humidifier Installation | 41 Table 14: Minimum Clearances for Blower Packs Frontal Overhead Left side Clearance Clearance Clearance Inch (cm) Inch (cm) Inch (cm) 5-30 (2.3-13.6) Low 132 (336) 12(31) 12 (31) 5-30 (2.3-13.6) High 120 (305) 12(31) 12 (31) 50-100 (22.7-45.4) High* 248 (630) 36 (91) 30 (76) Based upon Nominal Conditions 72˚F (22.2˚C), 43% RH. *Low speed not advised for 100lb/hr. Supply steam lbs(kg) per hour 42 | Humidifier Installation Speed setting Right side Clearance Inch (cm) 12 (31) 12 (31) 30 (76) Plumbing 1.2 in. (30 mm). OD un-threaded outlet with factory supplied bent hose and clamp. Air gap required. 2 1/2 in. to 7/8 in. copper reducer is ideal. (NORTEC option P/N 2522172) Hose must not touch the bottom of the funnel. 1/2 in. NPT Use union to connect supply pipe to unit. Min. 7/8 in. OD drain line. Keep as short as possible. Slope down to floor drain or main drain. Increase size if combining multiple drains as in double unit. Always install a water shut-off valve. *Pipe and water shut-off valve not supplied by NORTEC. Figure 15: NH-EL Water Supply and Drain Connection Table 15: NH-EL Supply Water Requirements Conductivity (µSiemens) 150-1250* Hardness Range (GPG) Silica Range (ppm) Alkalinity Range (pH) 0-10 0-3 0-4 0-14 7-7.5 *Default humidifier configuration supports approximately 330-670µS Humidifier Installation | 43 All water supply and drain line connections should be installed in accordance with local plumbing codes. Supply cold potable water, not purified water such as reverse osmosis or demineralized. See Table 8 and Table 9 for supply water flow rates. Use material suitable for 212°F (100°C) for drain and condensate lines. The drain line should not end in a sink used frequently by personnel, or where plumbing codes prohibit. Route to a floor drain or equivalent for safety reasons. Ensure drain line is adequately sized to provide free and easy draining, an air gap must be installed as shown. A restricted drain can cause cylinder water to over concentrate and result in poor operation or result in water backing up at the air gap. Electrical Caution: Wiring to be performed by a licensed electrician. Three Phase NH-EL Three Phase Supply Ground Ground L1 L2 L3 Neutral L1 L2 L3 E X T Dedicated Circuit Breaker or Fused Disconect I N T Single Phase NH-EL Single Phase Supply Ground . Ground L1 L2 Note: 1 Install a disconnect within view of the humidifier. 2 Optional internal fuses are not a substitute for external fuses. 3 Dedicated external fused disconnect must be installed. Fusing must not exceed max circuit protection as indicated on the specification label. 4 Ensure that adequate power is available to carry full humidifier amp draw as indicated on the specification label. 5 All wiring to be in accordance with national and local electrical codes. L1 L2 E X T Three Phase Supply (Note: Load will be unbalanced) Ground Ground L1 L2 L3 Neutral L1 L2 E X T I N T Three Phase Supply (Note: Load will be unbalanced) Ground Ground L1 L2 L3 Neutral L1 Neutral E X T Figure 16: NH-EL Primary Power Connections 44 | Humidifier Installation I N T I N T . Steam Distribution Systems Steam Distributors The atmospheric steam generated by the NH-EL must be introduced into the conditioned environment to facilitate humidification. This is accomplished with either Blower Packs mounted directly in the conditioned environment, or by mounting Duct Distributors into air handlers or supply ducts feeding the conditioned environment. In all cases the steam distributor must be capable of dispersing equal to, or greater amounts of steam that the humidifier will produce. Use the free Nortec online program - Humidifier Engineering and Load-sizing Program (H.E.L.P.) to assist in distributor sizing and accessory selection. Additionally this program can also assist with absorption distance calculations, selection of humidifiers, controls, and accessories. For access to this program please go to: www.NortecHelp.com Additional information on the effects of humidity, calculating relative humidity, load calculations and recommended design conditions can be found in the Nortec Humidification Load Calculation manual (2553856). Duct Distributors A variety of duct distributor systems are available to accommodate duct dimensions, humidifier capacities, and steam absorption distances. To facilitate proper steam absorption and prevent condensation in duct the following criteria must be met: Steam distribution capacity must be equal to or greater than the humidifier steam production capacity, less steam line condensate losses. Multiple distributors can be utilized as needed. There must be laminar air flow in the duct across the distributor. Excessively turbulent air flow may cause air stream collisions with internal duct walls/components which must be avoided for the calculated absorption distance downstream. The duct air velocity must be greater than 300 fpm to prevent steam migrating to, and colliding with, the duct ceiling. An air proving switch and high limit humidistat must be utilized. See NH-EL Control Inputs on page 50. Duct static pressures must not exceed -2” WC to 5.5” WC (-0.5 to 1.37 kPa) or up to 10” WC (2.49 kPa) with fill cup extension. Atmospheric steam lines must be installed in order to provide steam from the NH-EL humidifier to the steam distributor as detailed in Atmospheric Steam Distribution Lines on page 47. For more information on duct distributor systems see the Nortec reference literature detailed by part number in Table 16. This literature is accessible from the Nortec website www.Humidity.com. Table 16: Duct Distributor Models Duct Dimensions Model Steam Capacities (lb/hr) Min** Max** ASD Tube BSD Tube CSD Tube SAM-e Mini SAM-e 0-25* 0-35 0-115 Max 1200** Max 210** 10” 12” 24” 18” X 18”W 8” x 12”W 66” 102” 138” 360” x 360”W 36” x 36”W *Max 22lb/hr for 10” ASD tubes. **Available in various standardized configurations. Nortec Reference Literature 2556592 1503529 Humidifier Installation | 45 Blower Packs Nortec Blower Packs create an air stream to facilitate absorption of the atmospheric steam in the conditioned environment. Once the steam is absorbed the humidity will disperse evenly throughout most conditioned environments without the need of further mechanical assistance with exception to; mechanical obstructions, localized variances in temperature, infiltrating air, or materials that have equalizing moisture effects on the surrounding atmosphere. See Space Distribution Control Design on page 57. Blower Packs are available in two configurations: Remotely Mounted (RM-BP) or Built-On (Space). Each has two speed settings, High speed provides shorter absorption distances, low speed offers quitter operation with longer absorption distance. The NH-EL Space model comes preassembled with the Blower Pack with steam line, condensate drainage, and wiring. This increases the standard installation tolerances of the humidifier as detailed on page 40. Figure 17: Blower Pack Configurations Each Remote Mounted Blower Pack (RM-BP) is capable of supporting 5-100lb/hr. These distribution methods will require; 120VAC 15 amp power supply, atmospheric steam lines, condensate drainage (See Atmospheric Steam Distribution Line on page 47). For more information on Blower Packs see Nortec document 2572641. 46 | Humidifier Installation *Not to scale Figure 18: Remote Mounted Blower Pack Atmospheric Steam Distribution Lines Atmospheric steam generated by the NH-EL must be introduced from the humidifier to the steam distribution system to facilitate humidification of the conditioned environment. If the atmospheric distribution system creates steam pressures outside -2” WC to 5.5” WC (-0.5 to 1.37 kPa), or up to 10” WC (2.49 kPa) with fill cup extension when combined with duct static pressures, operation of the humidifier will be impaired. To prevent this, ensure duct static pressures are within range and all steam line designs utilize the correct; steam line material, diameter, length, slope, insulation, and condensate drainage. For more steam line design information see the “Steam Lines and Condensate Returns” section of the 2570435 NH-EL Installation Manual. Material Only use Notec steam hose, MED-L copper tube, or stainless steel tube that meets the ID requirements based on humidifier capacity as detailed in Table 17 on page 48. Consult with the manufacturers of the steam line materials for information on applications with atmospheric steam. Length Maximum recommended steam line lengths are detailed in Table 17 on page 48. Minimize the length of steam lines to reduce efficiency losses to condensate. Table 12 on page 39 provides equivalent length of some common fittings that can be used when determining the total equivalent length of steam lines. See Condensate Loss starting on page 38 for information on calculating efficiency losses based on total equivalent steam line length. Condensate Condensate is formed in the steam line and steam distributor systems. Steam lines must be designed to minimize the condensate created, and to remove any condensate that will otherwise obstruct the free venting of the atmospheric steam. Insulation – a minimum 1 in. pipe insulation is recommended to reduce the condensate created as per Figure 19. Minimum Slope – Slope the steam line towards condensate drainage traps as per Figure 20. The minimum slope with the flow of steam is 2°, against the flow of steam the minimum slope is 10°. Condensate Traps – The distribution line must be drained at all low points and every 15 ft (4.5m) of linear steam line. Drainage from the steam line is accomplished with full size Tee fittings as per Figure 20. MAIN RULES FOR ATMOSPHERIC STEAM LINES Steam lines must not have any restrictions which could cause back pressure or more than 5.5 in. W.C. when combined with duct static pressure. Follow recommended materials, size and length (see Figure 17 on page 46). Only use Nortec steam hose for short steam runs, (<10 ft./3 m) and adapting to the cylinder steam outlet. Slope the steam lines and insulate with 1.0 in. (2.5 cm) pipe insulation minimum as indicated in Figure 19. Trap condensate using full size ‘T’ for Traps (see Figure 20). Operate units/tanks in parallel when installing multiple units or double unit to single steam distributor (See Double Unit (150-200 lb/hr) on page 14). Flush steam lines and supply water lines after construction. Humidifier Installation | 47 Use Appropriate Slope Insulate Pipe Minimal Slope (up) 10 Degrees n Directio Steam 2 in. (5 cm) 1 ft (30 cm) Minimal Slope (down) 2 Degrees Steam Directio Stea n m Dir ection 0.5 in. (12 mm) 1 in. (2.5 cm) pipe insulation 1ft (30 cm) Figure 19: Steam Line Slope and Insulation Condensate Returns Route condensate back to humidifier fill cup where possible. Clean condensate can be returned to cylinder from the fill cup. Condensate should not be routed to a sink used frequently by personnel. Route to a floor drain or equivalent. Condensate normally cools in traps but is still hot. A SAM-e or larger steam line generates more condensate and water may not cool in the trap. A drain water cooler option may be installed if required by code. Large volumes of condensate from multiple humidifiers or SAM-e systems should never be returned to a single humidifier. Multiple condensate drain points must be trapped individually prior to coupling Tee is same size as steam line Use a full size tee, not a 90 degree elbow for vertical to horizontal transitions. 12 in. (30 cm) min drop to top of ‘P’ Trap P Trap min 6 in. (15 cm) or duct static pressure + 2 in whichever is greater ‘P’ Traps Use: - NORTEC 0.375 in condensate hose - 1/4 in Med-L copper tubing, or - 0.375 in stainless steel tubing Minimum Slope. 1 ft (30 cm) 0.25 in (0.6 cm) Condensate drains must be sloped down. Figure 20: Condensate Traps 48 | Humidifier Installation Table 17: Recommended Steam Line Material*, Maximum Length, Losses NH-EL Model 5 10 20 30 50 75/150** 100/200** 5 10 20 30 50 75/150** 100/200** 5-30 50-200** Maximum Steam MED-L Stainless Possible Steam Losses Line Length Copper Steel (based on 1” insulated copper pipe) ft (m) Tube Tube lb/hr/ft (kg/hr/m) 7 (2) 12 (3.5) 0.75 0.875 X 0.049W 0.06 (0.09) 17 (5) 22 (6.5) 43 (13) 47 (14) 1.5 1.75 X 0.065W 0.11 (0.16) 50 (15) Oversized Steam Line (Use for longer steam runs)*** 14 (4) 24 (7) 1 1.125 X 0.049W 0.06 (0.09) 34 (10) 44 (13) 86 (26) 94 (28) 2 2.0 X 0.065W 0.11 (0.16) 100 (30) Nortec Steam Hose 5 (1.5) Pt No 1328810 (7/8”) 0.1 (0.15) 5 (1.5) Pt No. 1328820 (1 3/4”) 0.15 (0.22) Note: * The use of steam line other than copper, stainless steel tube or Nortec supplied steam line will void the warranty and may adversely affect the operation of the humidifier ** Use one steam line per cylinder for NH-EL150-200 humidifiers. Do not combine lines except at distributor using a Nortec adapter designed for that purpose and only if humidifiers are operated in parallel. *** These diameters require a reducer at humidifier and steam distributor connection Combining Steam Lines To combine multiple steam lines from a double unit or from multiple units, always use a Nortec supplied adapters at the steam distributor. Do not use common steam lines for double units or from multiple humidifiers. Always operate units or double tank units in parallel. See Double Unit (150-200 lb/hr) on page 14. Combine multiple steam lines at steam distributor using a Nortec Adapter Units must be controlled in parallel. Also applies for double tank models 150/200. Figure 21: Combining Multiple Steam Lines Humidifier Installation | 49 Control System Design The NH-EL is designed to be regulated by an automated control system interfaced to the humidifier’s control terminal strip, but operation may also be regulated with a computer or building management system with a compatible digital communication protocol. See Digital Control on page 55 for more information. Regardless the interface, control components for the conditioned environment will vary primarily depending upon Duct or Space distribution method. All modulating input signals to the humidifier must be of a matching type, either transducers (RH Sensor), or humidistats (demand signals). For wiring use a minimum of 18 AWG and keep as short as possible. NH-EL Control Inputs The NH-EL operation can be regulated with Analog Controls supporting up to two modulating inputs and multiple on/off devices for each cylinder, or with Digital Control using computer or building management system interface using standard digital communication protocols. For control system designs for the conditioned environment see Control System Design on page 50. Note: Regardless of selecting Analog or Digital controls, Nortec humidifiers must have a closed circuit across the on/off security loop(s) to operate. Nortec highly recommends the use of a High Limit humidistat and an Air Proving switch for duct installations. Multi-Mode The Multi-Mode function allows connection of up to 16 humidifiers to one control signal (Analog or Digital) to a designated Master unit. Humidifiers can be configured to operate in parallel or to come on in stages to match demand. Staged configuration of the units will allow for a lower turn down ratio by using the smallest capacity humidifier as the master. Parallel configuration allows for connections to common distributor systems and offers more even wear on all units. For more information see Double Unit (150200 lb/hr) on page 14. Connect up to 16 units (equivalent of 1600 lb/hr) using 18-24 AWG multi-strand, twisted pair, shielded cable. Connect humidistats/transducers and security loop to master unit only. Jump the security loops on slave units. When connecting double units connect only to driver board A. 50 | Humidifier Installation Master Slave 1 Slave X Daisy Chain up to 16 Humidifiers Daisy chain pole 1 and 2 of terminal J10 of the control board. Note: Do not reverse polarity. Figure 22: Multi Mode Wiring Analog Controls All analog controls will interface with the NH-EL on the low voltage control terminal strip. Controls can be supplied by Nortec or by others. The humidifier will not be capable of steam production until the security enable/disable loop has been satisfied. The control signal acceptance can be configured by Nortec at the factory or can be field configured with the digital touch screen user interface. See Table 6 on page 21 for ordering information for preconfigured control signal acceptances. Control configurations allow for enable/disable of both modulating inputs as well as selection from a range of signal acceptances detailed in Table 18. Humidifier Installation | 51 Table 18: NH-EL Viable Control Signals Control Type Control Signal NH-EL Modulating Control/High-Limit Signals On/Off Control/High-Limit Signals Demand or Transducer 0-5 V, 0-10 V, 1-5 V, 2-10 V, 0-20 V, 0-16 V, 3.2-16 V, 0-20mA, 4-20mA Dry Contact 24 VAC or 10 VDC Dry Contact 24 VAC On/Off Security Loop Double Units - Double humidifiers have two terminal strips and differentiate the controls for each cylinder with A/B designations as per Figure 7: NH-EL Models on page 13. If controlling double units in Series or Parallel configuration, only one set of controls will be required to terminal strip A. If controlling with Independent mode, one set of controls will be required for each terminal strip and each cylinder will operate independent of the other. Modulating Control The NH-EL can be operated with one or two modulating inputs per cylinder. If using two modulating inputs both signals must be of the same type: Demand signals as provided by an external controller, or Transducer (RH sensor) signals as provided by an external humidity sensor. In both cases, the humidifier will not start to produce steam until the calculated system demand exceeds 26%. Demand Signals When the humidifier receives a demand signal it will calculate the desired steam production as a percentage of total humidifier capacity proportional to the incoming demand signal as a percentage of the signal range. When two demand signal inputs are used, the humidifier will respond to the lowest of the two demand signals. Transducer Signals When using modulating transducers (RH Sensor), the humidifier will use an internal PI controller to calculate system demand for each channel input. The calculated system demand for each input channel will vary depending upon the configurable humidity set points, as well as proportional and integral functions of the internal controller. If using two transducer signals, two demand signals will be calculated and the humidifier will respond to the lowest of the two calculated demand signals. Transducers with a possible zero input are not recommended. The humidifier also supports an optional low and high humidity alarm warning with reconfigurable humidity triggers. Safety Control The NH-EL can be enabled for operation by closing the 24VAC safety loop (pin 1 to pin 2) on the low voltage control terminal strip. This loop also facilitates on/off control of the humidifier. This security loop can be used for safety feedbacks that indicate the functional status of the humidification system components critical to the correct and safe operation of the humidifier. 52 | Humidifier Installation Digital Control The digital interface can be configured to control the humidifiers output or can be used to monitor operation, and change system configurations. Digital communication can be used in conjunction with Analog controls to regulate the humidifiers operation. With NH-EL humidifiers utilizing the digital communication features, it is recommended to use transducers for the control and high limit signals. The NH-EL supports standard communication protocols BACnet IP, MS/TP and Modbus RTU. The desired integrated communication protocol can be selected and configured using the digital touch screen interface. With optional hardware kits the humidifier can be adapted to communicate with Lonworks, or BTL certified BACnet IP/MSTP. See page Table 3: NH-EL Options on page 17 for optional communication packages and Nortec document 2574199 BACnet/Lonworks Supplemental manual. BACnet The NH-EL uses a standard RJ-45 connector and Category (CAT) 5,5E ,or 6 provided by others to connect to the Integrated Controller board to facilitate BACnet Internet Protocol (IP) and Master Slave Token Passing (MS/TP) communications. Refer to the Building Management System (BMS) supplier for maximum recommended communication line lengths. See Nortec document 2574199 – BACnet, LonWorks supplemental Installation and Operation Manual for control points and connection information. Modbus RTU The NH-EL uses a three pole terminal to the Integrated Controller board to facilitate the Modbus EIA-485, 2-wire communications. Connections can be made directly to the provided terminal with the recommended 18-24 AWG Shielded, twisted pair with 120 Ω impedance. Cables of superior quality are also considered acceptable. To minimize signal loss, a wire run should not exceed 2200 feet (670m). To ensure communication reliability, it is recommended that no more than 8 nodes are connected to a single chain/bus. See Nortec document 2560599 – Using Modbus with Nortec Humidifiers for a listing of Modbus parameters and connection/configuration information available with the NH-EL. Lonworks and BTL Certified BACnet IP/MSTP LonWorks and BTL certified BACnet systems require additional optional hardware. See Nortec document 2574199 – BACnet, LonWorks supplemental Installation and Operation Manual for required kits, control points and connection information. Humidifier Installation | 53 Duct Distribution Control Design When distributing into a supply air duct the humidifier system will require an Air Proving Switch, Duct High Limit, and a Humidity Controller. Environments with outdoor walls should consider the Outdoor Temperature Setback Sensor. Figure 23: Duct Control Location 1. Air Proving Device Steam vented from a duct distributor will require air flow over the distributor in order to be absorbed. Nortec air proving switches provide normally open dry contact feedback to the humidifiers security loop that will prevent humidification should the air handler not be operational. 2. High Limit Safety The high limit will allow for limiting supply air humidity in order to prevent the air from reaching saturated conditions that lead to water damage. Typically On/Off duct or wall humidistats suffice for this application, but there are several applications where modulating transducers or humidistats should be used: When using a variable air volume (VAV) air handling system. When installing the high limit after a bend or obstruction in the supply duct. With very high, or 100% outdoor air applications. Installations with short clearances for steam absorption. Nortec duct humidistats or transducers should be installed 10 ft / 3 m downstream of the duct distributor system or outside of the calculated absorption distance. Wall mount high limits should be used for space distribution and should be installed in the conditioned environment avoiding discharge diffusers, infiltrating air, and localized variations in temperatures. 3. Humidity Control The Humidity Control will detect the relative humidity in the conditioned environment and provide feedback to the humidifier. Must be installed in a location representative of the conditioned environment. Duct controls installed in exhaust or return ducts are preferred. Wall mount controls can also be installed in the conditioned environment avoiding discharge diffusers, infiltrating air, and localized variations in temperatures. The NH-EL is compatible with On/Off or modulating humidistats, and transducers (RH sensors), but there are several applications where modulating transducers or humidistats should be used: 54 | Humidifier Installation With very high, or 100% outdoor air applications. When using economizers or variable air volume air handling systems. Where narrow humidity tolerances are required. 4. Outdoor Temperature Setback This should be used to prevent condensation on windows or other surfaces that are adjacent to outdoor air. Must be installed in an area representative of the outdoor air temperatures such as a fresh air intake duct or directly outside. For use with Nortec humidistat humidity controller that limits set points based upon outdoor temperatures. Automatic setback is reconfigurable depending upon insulation quality of windows, default setback as per Figure 24. See Table 4 on page 20 for more information. Figure 24: Default Set Point Setback Space Distribution Control Design When distributing directly into the conditioned environment the humidification system will require a Control Humidistat, and a High Limit is recommended. Environments with outdoor walls should use the Outdoor Temperature Setback Sensor to prevent window sill/wall water damage. 1 Humidity Control (in location representative of the space) Figure 25: Space Control Location Humidifier Installation | 55 Nortec Online Nortec Online provides the ability to monitor the humidification system remotely. All Nortec NH-EL humidifiers ship ready to connect to Nortec Online over the internet without the need for additional gateways or factory installed options. Nortec Online provides humidifier operational status, system configuration information, fault history, trended steam production, trended control inputs, and trended humidity readings (with transducers) in addition to e-mail notification of any fault with the humidifier. Nortec Online also enables factory service technicians to assist facility staff with troubleshooting, diagnostics, and tuning of the system. Network Connections To take advantage of Nortec Online, the humidifier must be physically connected to the internet through a network (by others). The Nortec Online connection must then be enabled and the humidifier registered to a user account on NortecOnline.com. Multiple humidifiers can be connected to the same network, although each must be configured with an individual IP address. Figure 26: Nortec Online 56 | Humidifier Installation Wired connections are recommended for optimal reliability and quality of the connection. Wireless (“wifi”) connections can be achieved through the use of a Wireless Bridge, provided by others. Refer to the documentation provided with the bridge for configuration and setup. See Nortec publication 2553430 – NH-EL Online Installation Manual for detailed information about Nortec Online. Remote Fault Option The NH-EL remote fault option includes 4 relays that can provide remote status indication. The relays are mounted to a remote fault board which is located as shown in Figure 27. The PCB with the relays includes markings which indicate the function of each terminal on the board. The relays indicate the following status: Unit On The normally open relay is closed when the humidifier has power and the On/Off switch is set to On. Steam The normally open relay is closed when the control board detects that the cylinder is drawing current and steam is being produced. Service The relay can be wired to open (NC) or close (NO) when a warning is displayed on the humidifier display and the yellow service LED is illuminated. Error The relay can be wired to open (NC) or close (NO) when a fault is detected by the humidifier controls. NO COM NO COM NC NO COM NC NO COM Unit ON Steam Service Error Figure 27: Remote Fault Wiring Humidifier Installation | 57 Warranty Nortec Humidity Inc. and/or Nortec Humidity Ltd. (hereinafter collectively referred to as THE COMPANY), warrant for a period of two years after installation or 30 months from manufacturer’s ship date, whichever date is earlier, that THE COMPANY’s manufactured and assembled products, not otherwise expressly warranted (with the exception of the cylinder), are free from defects in material and workmanship. No warranty is made against corrosion, deterioration, or suitability of substituted materials used as a result of compliance with government regulations. THE COMPANY’s obligations and liabilities under this warranty are limited to furnishing replacement parts to the customer, F.O.B. THE COMPANY’s factory, providing the defective part(s) is returned freight prepaid by the customer. Parts used for repairs are warranted for the balance of the term of the warranty on the original humidifier or 90 days, whichever is longer. The warranties set forth herein are in lieu of all other warranties expressed or implied by law. No liability whatsoever shall be attached to THE COMPANY until said products have been paid for in full and then said liability shall be limited to the original purchase price for the product. Any further warranty must be in writing, signed by an officer of THE COMPANY. THE COMPANY’s limited warranty on accessories, not of the companies manufacture, such as controls, humidistats, pumps, etc. is limited to the warranty of the original equipment manufacturer from date of original shipment of humidifier. THE COMPANY makes no warranty and assumes no liability unless the equipment is installed in strict accordance with a copy of the catalog and installation manual in effect at the date of purchase and by a contractor approved by THE COMPANY to install such equipment. THE COMPANY makes no warranty and assumes no liability whatsoever for consequential damage or damage resulting directly from misapplication, incorrect sizing or lack of proper maintenance of the equipment. THE COMPANY makes no warranty and assumes no liability whatsoever for damage resulting from freezing of the humidifier, supply lines, drain lines, or steam distribution systems. THE COMPANY retains the right to change the design, specification and performance criteria of its products without notice or obligation 58 | Warranty U.S.A 826 Proctor Avenue Ogdensburg, NY 13669 CANADA 2740 Fenton Road Ottawa, Ontario K1T 3T7 TEL: 1.866.NORTEC1 FAX: 613.822.7964 EMAIL: [email protected] WEBSITE: www.humidity.com
Similar documents
LiveSteam - Nortec Humidity
This document and the information disclosed herein are proprietary data of NORTEC HUMIDITY LTD. Neither this document nor the information contained herein shall be reproduced, used, or disclosed to...
More information