SHEET S0.1 – GENERAL NOTES SHEET S0.3 – ROOF SNOW
Transcription
SHEET S0.1 – GENERAL NOTES SHEET S0.3 – ROOF SNOW
ADDENDUM NO. 03 TO THE Corner Greer & Associates, Inc. 716 South Main Street Joplin, MO 64801 Telephone 417-206-3134 DLR Group Architecture Engineering Design 7290 West 133rd Street Overland Park, Kansas 66213 Telephone 913-897-7811 PROJECT MANUAL AND DRAWINGS FOR October 8, 2012 JOPLIN HIGH SCHOOL PACKAGE 2 – FOUNDATIONS AND STRUCTURAL STEEL JOPLIN, MISSOURI FOR SEPARATE CONTRACTS NOTICE TO BIDDERS: The Project Manual and Drawings for the above referenced project are hereby amended as follows: PROJECT MANUAL (NO ITEMS) DRAWINGS ITEM NO. 1 a. SHEET S0.1 – GENERAL NOTES ITEM NO. 2 a. SHEET S0.3 – ROOF SNOW DRIFT PLAN ITEM NO. 3 a. SHEET S1.1A – FIRST LEVEL FOUNDATION PLAN-AREA A ITEM NO. 4 a. SHEET S1.1B – FIRST LEVEL FOUNDATION PLAN-AREA B ITEM NO. 5 a. SHEET S1.1C – FIRST LEVEL FOUNDATION PLAN-AREA C ITEM NO. 6 a. SHEET S1.1D – FIRST LEVEL FOUNDATION PLAN-AREA D Sheet S0.1 is revised and reissued with Addendum No. 03 dated October 8, 2012. Sheet S0.3 is issued with Addendum No. 03 dated October 8, 2012. Sheet S1.1A is revised and reissued with Addendum No. 03 dated October 8, 2012. Sheet S1.1B is revised and reissued with Addendum No. 03 dated October 8, 2012. Sheet S1.1C is revised and reissued with Addendum No. 03 dated October 8, 2012. Sheet S1.1D is revised and reissued with Addendum No. 03 dated October 8, 2012. ADDENDUM NO. 03 Page - 1 ITEM NO. 7 a. SHEET S1.1E – FIRST LEVEL FOUNDATION PLAN-AREA E ITEM NO. 8 a. SHEET S1.1F – FIRST LEVEL FOUNDATION PLAN-AREA F Sheet S1.1E is revised and reissued with Addendum No. 03 dated October 8, 2012. Sheet S1.1F is revised and reissued with Addendum No. 03 dated October 8, 2012. ITEM NO. 9 SHEET S1.1G – FIRST LEVEL FOUNDATION PLAN-AREA G a. Sheet S1.1G is revised and reissued with Addendum No. 03 dated October 8, 2012. ITEM NO. 10 a. SHEET S1.1H – FIRST LEVEL FOUNDATION PLAN-AREA H ITEM NO. 11 a. SHEET S1.1J – FIRST LEVEL FOUNDATION PLAN-AREA J ITEM NO. 12 a. SHEET S1.1K – FIRST LEVEL FOUNDATION PLAN-AREA K ITEM NO. 13 a. SHEET S1.1L – FIRST LEVEL FOUNDATION PLAN-AREA L ITEM NO. 14 a. SHEET S1.1M– FIRST LEVEL FOUNDATION PLAN-AREA M ITEM NO. 15 a. SHEET S1.2B – SECOND LEVEL FLOOR FRAMING PLAN-AREA B ITEM NO. 16 a. SHEET S1.2C – SECOND LEVEL FLOOR FRAMING PLAN-AREA C ITEM NO. 17 a. SHEET S1.2D – SECOND LEVEL FLOOR FRAMING PLAN-AREA D ITEM NO. 18 a. SHEET S1.2E – SECOND LEVEL FLOOR FRAMING PLAN-AREA E ITEM NO. 19 a. SHEET S1.2F – SECOND LEVEL FLOOR FRAMING PLAN-AREA F ITEM NO. 20 a. SHEET S1.2G – SECOND LEVEL FLOOR FRAMING PLAN-AREA G ITEM NO. 21 a. SHEET S1.2H – MEZZANINE LEVEL FLOOR FRAMING PLAN-AREA H ITEM NO. 22 a. SHEET S1.2J – MEZZANINE LEVEL FLOOR FRAMING PLAN-AREA J ITEM NO. 23 a. SHEET S1.2K – SECOND LEVEL FLOOR FRAMING PLAN-AREA K ITEM NO. 24 a. SHEET S1.2L – SECOND LEVEL FLOOR FRAMING PLAN-AREA L Sheet S1.1H is revised and reissued with Addendum No. 03 dated October 8, 2012. Sheet S1.1J is revised and reissued with Addendum No. 03 dated October 8, 2012. Sheet S1.1K is revised and reissued with Addendum No. 03 dated October 8, 2012. Sheet S1.1L is revised and reissued with Addendum No. 03 dated October 8, 2012. Sheet S1.1M is revised and reissued with Addendum No. 03 dated October 8, 2012. Sheet S1.2B is revised and reissued with Addendum No. 03 dated October 8, 2012. Sheet S1.2C is revised and reissued with Addendum No. 03 dated October 8, 2012. Sheet S1.2D is revised and reissued with Addendum No. 03 dated October 8, 2012. Sheet S1.2E is revised and reissued with Addendum No. 03 dated October 8, 2012. Sheet S1.2F is revised and reissued with Addendum No. 03 dated October 8, 2012. Sheet S1.2G is revised and reissued with Addendum No. 03 dated October 8, 2012. Sheet S1.2H is revised and reissued with Addendum No. 03 dated October 8, 2012. Sheet S1.2J is revised and reissued with Addendum No. 03 dated October 8, 2012. Sheet S1.2K is revised and reissued with Addendum No. 03 dated October 8, 2012. Sheet S1.2L is revised and reissued with Addendum No. 03 dated October 8, 2012. ADDENDUM NO. 03 Page - 2 ITEM NO. 25 a. SHEET S1.3B – THIRD LEVEL FLOOR FRAMING PLAN-AREA B ITEM NO. 26 a. SHEET S1.3C – THIRD LEVEL FLOOR FRAMING PLAN-AREA C ITEM NO. 27 a. SHEET S1.3D – THIRD LEVEL FLOOR FRAMING PLAN-AREA D ITEM NO. 28 a. SHEET S1.3E – THIRD LEVEL FLOOR FRAMING PLAN-AREA E ITEM NO. 29 a. SHEET S1.3F – THIRD LEVEL FLOOR FRAMING PLAN-AREA F ITEM NO. 30 a. SHEET S1.3G – THIRD LEVEL FLOOR FRAMING PLAN-AREA G ITEM NO. 31 a. SHEET S1.3H – THIRD LEVEL FLOOR FRAMING PLAN-AREA H ITEM NO. 32 a. SHEET S1.3J – THIRD LEVEL FLOOR FRAMING PLAN-AREA J ITEM NO. 33 SHEET S1.3K – THIRD LEVEL EQUIPMENT PLATFORM FRAMING PLAN- Sheet S1.3B is revised and reissued with Addendum No. 03 dated October 8, 2012. Sheet S1.3C is revised and reissued with Addendum No. 03 dated October 8, 2012. Sheet S1.3D is revised and reissued with Addendum No. 03 dated October 8, 2012. Sheet S1.3E is revised and reissued with Addendum No. 03 dated October 8, 2012. Sheet S1.3F is revised and reissued with Addendum No. 03 dated October 8, 2012. Sheet S1.3G is revised and reissued with Addendum No. 03 dated October 8, 2012. Sheet S1.3H is revised and reissued with Addendum No. 03 dated October 8, 2012. Sheet S1.3J is revised and reissued with Addendum No. 03 dated October 8, 2012. AREA K a. ITEM NO. 34 Sheet S1.3K is revised and reissued with Addendum No. 03 dated October 8, 2012. SHEET S1.3L – THIRD LEVEL EQUIPMENT PLATFORM FRAMING PLAN- AREA L a. Sheet S1.3L is revised and reissued with Addendum No. 03 dated October 8, 2012. ITEM NO. 35 a. SHEET S1.4A – ROOF LEVEL FRAMING PLAN-AREA A ITEM NO. 36 a. SHEET S1.4B – ROOF LEVEL FRAMING PLAN-AREA B ITEM NO. 37 a. SHEET S1.4C – ROOF LEVEL FRAMING PLAN-AREA C ITEM NO. 38 a. SHEET S1.4D – ROOF LEVEL FRAMING PLAN-AREA D ITEM NO. 39 a. SHEET S1.4E – ROOF LEVEL FRAMING PLAN-AREA E ITEM NO. 40 a. SHEET S1.4F – ROOF LEVEL FRAMING PLAN-AREA F ITEM NO. 41 a. SHEET S1.4K – ROOF LEVEL FRAMING PLAN-AREA K Sheet S1.4A is revised and reissued with Addendum No. 03 dated October 8, 2012. Sheet S1.4B is revised and reissued with Addendum No. 03 dated October 8, 2012. Sheet S1.4C is revised and reissued with Addendum No. 03 dated October 8, 2012. Sheet S1.4D is revised and reissued with Addendum No. 03 dated October 8, 2012. Sheet S1.4E is revised and reissued with Addendum No. 03 dated October 8, 2012. Sheet S1.4F is revised and reissued with Addendum No. 03 dated October 8, 2012. Sheet S1.4K is revised and reissued with Addendum No. 03 dated October 8, 2012. ADDENDUM NO. 03 Page - 3 ITEM NO. 42 a. SHEET S1.4L – ROOF LEVEL FRAMING PLAN-AREA L ITEM NO. 43 a. SHEET S2.1 – FOUNDATION TYPICAL DETAILS ITEM NO. 44 a. SHEET S2.2 – FOUNDATION TYPICAL DETAILS ITEM NO. 45 a. SHEET S3.4 – FOUNDATION SECTIONS ITEM NO. 46 a. SHEET S3.5 – FOUNDATION SECTIONS ITEM NO. 47 a. SHEET S3.6 – FOUNDATION SECTIONS ITEM NO. 48 a. SHEET S4.1 – FLOOR FRAMING TYPICAL DETAILS ITEM NO. 49 a. SHEET S4.2 – FLOOR FRAMING TYPICAL DETAILS ITEM NO. 50 a. SHEET S5.3 – FLOOR FRAMING SECTIONS ITEM NO. 51 a. SHEET S6.1 – ROOF FRAMING TYPICAL DETAILS ITEM NO. 52 a. SHEET S6.2 –ROOF FRAMING TYPICAL DETAILS ITEM NO. 53 a. SHEET S8.3 –BRACE ELEVATIONS AND DETAILS ITEM NO. 54 a. SHEET S8.4 – BRACE ELEVATIONS ITEM NO. 55 a. SHEET S8.5 –BRACE ELEVATIONS ITEM NO. 56 a. SHEET S8.6 – BRACE ELEVATIONS ITEM NO. 57 a. SHEET S9.2 – MASONRY TYPICAL DETAILS Sheet S1.4L is revised and reissued with Addendum No. 03 dated October 8, 2012. Sheet S2.1 is revised and reissued with Addendum No. 03 dated October 8, 2012. Sheet S2.2 is revised and reissued with Addendum No. 03 dated October 8, 2012. Sheet S3.4 is revised and reissued with Addendum No. 03 dated October 8, 2012. Sheet S3.5 is revised and reissued with Addendum No. 03 dated October 8, 2012. Sheet S3.6 is revised and reissued with Addendum No. 03 dated October 8, 2012. Sheet S4.1 is revised and reissued with Addendum No. 03 dated October 8, 2012. Sheet S4.2 is revised and reissued with Addendum No. 03 dated October 8, 2012. Sheet S5.3 is revised and reissued with Addendum No. 03 dated October 8, 2012. Sheet S6.1 is revised and reissued with Addendum No. 03 dated October 8, 2012. Sheet S6.2 is revised and reissued with Addendum No. 03 dated October 8, 2012. Sheet S8.3 is revised and reissued with Addendum No. 03 dated October 8, 2012. Sheet S8.4 is revised and reissued with Addendum No. 03 dated October 8, 2012. Sheet S8.5 is revised and reissued with Addendum No. 03 dated October 8, 2012. Sheet S8.6 is revised and reissued with Addendum No. 03 dated October 8, 2012. Sheet S9.2 is revised and reissued with Addendum No. 03 dated October 8, 2012. END OF ADDENDUM 03 ADDENDUM NO. 03 Page - 4 LOCATION PRECAST UNIT TOPPING SLAB CONCRETE OVER STEEL DECK WALLS AND COLUMNS ELEVATED SLABS AND BEAMS SLABS-ON-GRADE DRILLED PIERS (CAISSONS) FOUNDATIONS GRADE BEAM 28 DAY F'c 4,000 PSI 4,000 PSI 4,000 PSI 4,000 PSI 3,500 PSI 4,000 PSI 3,000 PSI 4,000 PSI UNIT WT NWT NWT NWT NWT NWT NWT NWT NWT W/C RATIO 0.48 0.48 0.45 0.45 0.48 0.55 0.55 0.48 MAX SLUMP 4" 4" 4" 4" 4" 4" MIN, 7" MAX 4" 4" MAX AGG 3/4" 3/4" 1" 1" 1" 1" 1" 3/4" CONCRETE CONTAINING SUPERPLASTICIZING ADMIXTURE SHALL HAVE A SLUMP NOT EXCEEDING 3" PRIOR TO ADDING ADMIXTURE AND NOT EXCEEDING 8" AT PLACEMENT. 3. THE ADDITION OF WATER TO A CONCRETE BATCH WITH INSUFFICIENT SLUMP SHALL NOT BE PERMITTED. 4. SUBSTITUTION OF FLYASH FOR PORTLAND CEMENT IN SLABS-ON-GRADE AND STRUCTURAL SLABS SHALL NOT BE PERMITTED. 5. WITH EXCEPTION OF DRILLED PIERS AND COLUMNS, ALL CONCRETE SHALL BE PROPORTIONED FOR A MAXIMUM ALLOWABLE UNIT SHRINKAGE OF 0.04% MEASURED AT 28 DAYS AFTER CURING IN LIME WATER AS DETERMINED BY ASTM C157 USING AIR STORAGE. PROVIDE TEST RESULTS WITH MIXTURE DESIGN. DRILLED PIERS: 1. DRILLED PIERS SHALL EXTEND INTO MATERIAL CAPABLE OF MEETING GEOTECHNICAL REQUIREMENTS AND AS NOTED ON THE DRAWINGS. HEAVY DUTY DRILL BITS MAY BE NEEDED TO INSTALL PIERS TO FINAL BEARING ELEVATION AND SHOULD BE ANTICIPATED IN THE CONTRACT PRICE. SEE GEOTECHNICAL REPORT FOR BORINGS. CONTRACTOR COORDINATE ALL LOFT BLOCK AND HEAD BLOCK BEAM LATERAL BRACING SHOWN ON DRAWINGS TO AVOID CONFLICTS WITH RIGGING LINE CONNECTIONS. 1 3 1 SEE STRUCTURAL PLANS FOR LOCATION OF SAFE ROOM. STRUCTURAL DESIGN IS BASED ON STRUCTURAL RECOMMENDATIONS LISTED IN FEMA 361 : DESIGN AND CONSTRUCTION GUIDANCE FOR COMMUNITY SAFE ROOMS, SECOND ED., AUG 2008" AND ICC 500-08 "ICC/NSSA STANDARD FOR THE DESIGN AND CONSTRUCTION OF STORM SHELTERS". NO INTENT TO MEET ALL OF THE FEMA GUIDELINES IS IMPLIED OR STATED UNLESS THE STRUCTURAL DRAWINGS SPECIFICALLY SATE THAT A "FEMA 361 SAFE ROOM" HAS BEEN PROVIDED. 2. THE MINIMUM 28-DAY COMPRESSIVE STRENGTH OF THE CLAY MASONRY UNITS SHALL BE 3,350 PSI ON THE NET AREA, PROVIDING A STRUCTURAL DESIGN COMPRESSIVE STRENGTH OF 1,500 PSI PER THE INTERNATIONAL BUILDING CODE, TABLE 2105.2.2.1.1. 3. MORTAR SHALL BE TYPE S IN ACCORD WITH THE INTERNATIONAL BUILDING CODE, TABLE 2103.8(1), MORTAR PROPORTIONS, USING CEMENT LIME OR MORTAR CEMENT MIXES (MASONRY CEMENT IS NOT ACCEPTABLE). 4. MINIMUM 28-DAY COMPRESSIVE STRENGTH OF GROUT SHALL BE THE GREATER OF 2,000 PSI OR THE COMPRESSIVE STRENGTH OF THE MASONRY UNITS. AIR ENTRAINMENT AND OTHER ADDITIVES ARE NOT ACCEPTABLE IN GROUT MIX. GROUT SHALL HAVE A SLUMP OF 8 TO 11 INCHES. 5. MASONRY REINFORCING STEEL SHALL BE ASTM A615, GRADE 60. REINFORCING STEEL TO BE WELDED SHALL BE ASTM A706, GRADE 60. 6. HORIZONTAL JOINT REINFORCING SHALL BE STANDARD LADDER TYPE, GALVANIZED, AT 16-INCHES ON CENTER, UNLESS OTHERWISE NOTED ON PLAN. SPACE JOINT REINFORCING AT 8-INCHES ON CENTER AT NON-CAVITY MULTIWYTHE WALLS. COLLAR JOINT BETWEEN WYTHES OF NON-CAVITY MULTIWYTHE WALLS ARE TO BE MORTARED/GROUTED SOLID. 7. MINIMUM BOND BEAM REINFORCING SHALL BE (1) #4 IN 6" WIDE BOND BEAMS, (2) #5 IN 8" WIDE BOND BEAMS AND (2) #6 IN 12" WIDE BOND BEAMS. BOND BEAM REINFORCING SHALL BE CONTINUOUS THROUGH CONTROL JOINTS EXCEPT AS NOTED ON TYPICAL MASONRY WALL OPENING DETAIL. 8. COMPOSITE DECK SHALL BE ATTACHED TO SUPPORTING STRUCTURAL MEMBERS BY 5/8” PUDDLE WELDS PLACED AT EACH DECK RIB OR 12 INCHES ON CENTER MAX, DEPENDING ON THE DECK ORIENTATION RELATIVE TO THE SUPPORTING MEMBERS. THIS WELD CAN BE OMITTED IN RIBS THAT HAVE SHEAR STUD CONNECTORS. SIDE LAPS BETWEEN ADJACENT UNITS ARE TO BE WITH #10 TEK SCREWS AT 36 INCHES MAXIMUM (MINIMUM 2 SCREWS PER SPAN). 9. PROVIDE 2 INCHES MINIMUM BEARING AT DECK SUPPORTS. 13. PROVIDE VERTICAL REINFORCING AT JAMB OPENINGS, ENDS AND CORNERS OF ALL WALLS AND EACH SIDE OF CONTROL JOINTS. SPECIAL JAMB REINFORCING, WHERE REQUIRED, IS CALLED OUT ON THE PLANS. HOLES SHALL BE DRILLED TO A PLUMBNESS TOLERANCE OF 2" IN ANY 10'-0" LENGTH. TOLERANCE FOR PLAN LOCATION SHALL BE A MAXIMUM OF 5 PERCENT OF THE PIER DIAMETER, 2 1/2" MAX. 4. DRILLED PIERS SHALL BEAR ON MACHINE CLEANED, INSPECTED SOIL STRATA. 17. GROUT SHALL BE MECHANICALLY CONSOLIDATED IN A MANNER TO FILL THE GROUT SPACE AND RECONSOLIDATED IN ACCORD WITH THE INTERNATIONAL BUILDING CODE. 5. THE GEOTECHNICAL ENGINEER/TESTING LABORATORY SHALL VERIFY SHAFT DIAMETER, DEPTH, BEARING STRATA, AND PROPER CLEANING OF INSTALLATION. 18. PROVIDE GROUT AND MASONRY UNIT TESTING PRIOR TO AND DURING CONSTRUCTION IN ACCORD WITH THE INTERNATIONAL BUILDING CODE. 6. REBAR CAGE POSITION IN CENTER OF SHAFT SHALL BE HELD IN PLACE BY MEANS OF "WAGON WHEEL" REBAR POSITIONERS OR EQUIVALENT. 19. TESTING LABORATORY, IN ACCORD WITH IBC REQUIREMENTS, SHALL INSPECT REINFORCEMENT PLACEMENT, GROUT SPACES AND GROUTING OPERATION. MORTAR FIN PROJECTION INTO THE GROUT SPACE SHALL NOT EXCEED 1/2 INCH. 7. CONCRETE SHALL BE PLACED IN SHAFT USING A CONTINUOUS TREMIE PIPE TO AVOID STRIKING REBAR CAGE AND SHAFT SIDES DURING PLACEMENT. MAXIMUM HEIGHT OF FREE-FALL SHALL BE 10'-0". THE TOP 5'-0" OF DRILLED PIERS SHALL BE MECHANICALLY VIBRATED. 20. WHERE STONE IS VENEERED TO MASONRY, PROVIDE TRUSS TYPE (GALV.) JOINT REINFORCING AT 16 INCHES ON CENTER WITH "EYES". 16. ALL MASONRY BELOW HIGHEST ADJACENT GRADE SHALL BE GROUTED SOLID. 21. SPACE CONTROL JOINTS IN MASONRY WALLS SUCH THAT NO STRAIGHT RUN OF WALL EXCEEDS 24'-0". REGARDLESS OF JOINT LAYOUT SHOWN ON ARCHITECTURAL DRAWINGS, THE CONTRACTOR SHALL NOT PLACE CONTROL JOINTS ABOVE / BELOW OPENINGS OR WITHIN SCHEDULED JAMB EXTENTS. CONTROL JOINTS SHALL NOT JOG HORIZONTALLY. 22. SUBMIT SHOP DRAWINGS WITH PLANS AND ELEVATIONS CLEARLY INDICATING REBAR SIZE, SPACING, LAP LENGTH, LINTELS, JAMBS, CONTROL JOINT LOCATIONS, FOOTING, SLAB, AND ROOF ELEVATIONS, WALL PENETRATION WITH DIMENSIONS, BOND BEAM ELEVATIONS, ETC. FOR REVIEW AND APPROVAL IN ADDITION TO ANY OTHER REQUIREMENTS LISTED IN THE SPECIFICATIONS. 3. CONSTRUCTION JOINT LOCATIONS SHALL NOT OCCUR WITHIN EXTENTS OF ISOLATED SPREAD FOOTINGS 4. CONTINUOUS FOOTINGS SHALL NOT HAVE CONSTRUCTION JOINTS IN A HORIZONTAL PLANE. 23. ALL CMU WALL OPENINGS REQUIRE LINTELS AS DEFINED IN THE “TYPICAL MASONRY LINTEL DETAIL/ SCHEDULE.” 5. SIDES OF FOOTINGS SHALL BE FORMED. IF EXCAVATIONS ARE MADE NEATLY AND FOOTING WIDTHS ARE INCREASED A MINIMUM OF TWO INCHES, SIDES MAY BE CAST AGAINST THE EARTH CUT. THE ADDITIONAL WIDTH IS NECESSARY TO PROVIDE THE PROPER REINFORCING COVER FOR THIS CONSTRUCTION METHOD. 24. REFER TO TYPICAL DETAILS FOR MASONRY DETAILS AND REQUIREMENTS NOT SHOWN IN SECTIONS OR PLANS. LATERAL RESISTANCE SYSTEM: 1. LATERAL LOAD SYSTEM CONSISTS OF FLOOR/ROOF DIAPHRAGMS TRANSFERRING LATERAL LOADS TO MASONRY/CONCRETE SHEAR WALLS/STRUCTRUAL STEEL X-BRACING. 2. LATERAL LOAD SYSTEM CONSISTS OF FLOOR/ROOF DIAPHRAGMS TRANSFERRING LATERAL LOADS TO MOMENT RESISTING STEEL FRAMES. 3. STEEL FRAME IS A "NON-SELF-SUPPORTING" STEEL FRAME REQUIRING INTERACTION OF THE STEEL FRAMING, FLOOR/ROOF DIAPHRAGMS AND SHEAR WALLS/X-BRACING. CONTRACTOR SHALL PROVIDE TEMPORARY BRACING AS NECESSARY TO PROVIDE SUPPORT OF FRAMING UNTIL ALL ATTACHMENTS ARE COMPLETE, INCLUDING STRUCTURAL STEEL, STRUCTURAL STEEL TO DIAPHRAGM/SHEAR WALLS, AND DIAPHRAGM TO SHEAR WALLS/BRACED FRAMES. FOUNDATIONS: 1. FOUNDATION DESIGN IS BASED ON GEOTECHNICAL INVESTIGATION PERFORMED BY PALMERTON & PARRISH, INC., JOB NO. 207620, DATED JUNE 14, 2012. A COPY OF THE GEOTECHNICAL INVESTIGATION REPORT IS INCLUDED IN THE PROJECT SPECIFICATIONS. BASED ON THE GEOTECHNICAL REPORT, THE FOLLOWING HAS BEEN ASSUMED: - MINIMUM FROST DEPTH = ALLOWABLE SOIL BEARING PRESSURE SPREAD FOOTING (MAT) CONTINUOUS FOOTING EQUIVALENT ACTIVE (UNRESTRAINED) FLUID PRESSURE = EQUIVALENT AT-REST (RESTRAINED) FLUID PRESSURE = EQUIVALENT PASSIVE FLUID PRESSURE = COEFFICIENT OF FRICTION = PIER SKIN FRICTION PRESSUE SHALE LIMESTONE PIER END BEARING PRESSURE SHALE LIMESTONE SUBGRADE SHALL BE PREPARED IN ACCORDANCE WITH THE PROJECT SPECIFICATIONS. CONTRACTOR SHALL READ AND FAMILIARIZE HIMSELF WITH THE GEOTECHNICAL REPORT. IF DISCREPANCIES EXIST BETWEEN PROJECT SPECIFICATIONS AND GEOTECHNICAL REPORT, THE GEOTECHNICAL REPORT SHALL SUPERCEDE THE SPECIFICATIONS. 3. ALL SLABS SHOWN ON STRUCTURAL DRAWINGS REQUIRE REINFORCING. UNLESS OTHERWISE CALLED OUT ON DRAWINGS, REINFORCE SLABS WITH 6x6/W2.1xW2.1 WELDED WIRE REINFORCING. 3,000 PSF 2,500 PSF 45 PCF 70 PCF 600 PSF 0.4 1,000 PSF 2,000 PSF SUBGRADE SHALL BE PREPARED IN ACCORDANCE WITH THE PROJECT SPECIFICATIONS. CONTRACTOR SHALL READ AND FAMILIARIZE HIMSELF WITH THE GEOTECHNICAL REPORT. IF DISCREPANCIES EXIST BETWEEN PROJECT SPECIFICATIONS AND GEOTECHNICAL REPORT, THE GEOTECHNICAL REPORT SHALL SUPERCEDE THE SPECIFICATIONS. 3. ALL FOUNDATION WALLS ARE DESIGNED TO BE RESTRAINED IN THE COMPLETED STRUCTURE, UNLESS OTHERWISE NOTED. CONNECTING CONSTRUCTION SHALL BE INSTALLED, INCLUDING INSTALLATION OF FLOOR/ROOF DIAPHRAGM AND THEIR ATTACHMENTS, PRIOR TO BACKFILLING WALL. CONCRETE DIAPHRAGMS SHALL REACH 75% OF REQUIRED 28 DAY COMPRESSIVE STRENGTH PRIOR TO BACKFILLING. 4. WALLS ARE NOT DESIGNED TO WITHSTAND TEMPORARY CONSTRUCTION LOADS, INCLUDING WIND AND SEISMIC. CONTRACTOR'S ENGINEER IS RESPONSIBLE FOR DESIGN OF TEMPORARY SHORING. 5. BACKFILLING AGAINST FOUNDATION WALLS WHERE GRADE IS PRESENT ON BOTH SIDES SHALL BE PREFORMED SUCH THAT THE DIFFERENCE IN SOIL HEIGHT ON EACH SIDE DOES NOT EXCEED 2 FEET. 6. TEMPORARY FROST PROTECTION SHALL BE PROVIDED DURING COLD WEATHER FOR ALL FOUNDATIONS. 7. CONTRACTOR SHALL PROVIDE FOR PROPER DEWATERING OF ALL EXCAVATIONS. 8. NEW FOOTINGS LOCATED IMMEDIATELY ADJACENT TO EXISTING FOOTINGS SHALL BE FOUNDED AT THE SAME ELEVATIONS AS THE EXISTING FOUNDATIONS UNLESS OTHERWISE NOTED. UNDER NO CIRCUMSTANCE SHALL THE EXISTING FOOTINGS BE UNDERMINED BY NEW CONSTRUCTION. CONCRETE CONSTRUCTION: 1. CONCRETE WORK SHALL BE IN ACCORDANCE WITH THE REQUIREMENTS OF ACI 301 AND ACI 318. PROVIDE A FORMED CONSTRUCTION KEYWAY BETWEEN ALL HORIZONTAL AND VERTICAL POUR EDGES EXCEPT CONCRETE TOPPING SLABS. PROVIDE WATERSTOPS FOR ALL CONSTRUCTION JOINTS BELOW WATER TABLE AND WHERE INTERIOR SLAB-ON-GRADE IS BELOW EXTERIOR GRADE. 3. CONCRETE SHALL BE MECHANICALLY CONSOLIDATED IN ACCORD WITH ACI 309. 4. CONTROL (CONTRACTION OR CONSTRUCTION) JOINTS SHALL BOUND ALL CONCRETE SLAB-ON-GRADE AS SHOWN ON THE DRAWINGS. 5. PROVIDE DOVETAIL ANCHOR SLOTS WHERE MASONRY/STONE IS VENEERED TO CONCRETE. PLACE SLOTS VERTICALLY AT 32 INCHES OC MAXIMUM. PROVIDE DOVETAIL ANCHOR FOR EACH TWO SQUARE FEET OF VENEER SURFACE. MANUFACTURER SHALL SUBMIT CALCULATIONS AND DRAWINGS SEALED BY A CIVIL OR STRUCTURAL ENGINEER REGISTERED IN THE STATE IN WHICH THE PROJECT IS LOCATED FOR ALL JOISTS AND JOIST GIRDERS. CALCULATIONS SHALL INCLUDE DEFLECTION AND CAMBER REQUIREMENTS AND CLEARLY SHOW ALL DESIGN LOADS. SHOP DRAWINGS SUBMITTED WITHOUT SIGNED AND SEALED CALCULATIONS ARE GROUNDS FOR REJECTION. 7. LIVE LOAD DEFLECTIONS SHALL BE LIMITED TO SPAN/240 AT SIMPLE SPAN ROOF MEMBERS AND TO SPAN/360 AT SIMPLE SPAN FLOOR MEMBERS. ALL JOISTS AND JOIST GIRDERS SHALL BE CAMBERED FOR THE DESIGN DEAD LOAD. 8. ALL JOISTS AND JOIST GIRDERS SHALL BE DESIGNED, FABRICATED, AND ERECTED IN ACCORDANCE WITH THE APPLICABLE U.L. LISTINGS PER THE ARCHITECTURAL DRAWINGS. 9. PROVIDE SLOPED AND/OR SLOPED AND SKEWED BEARING SEATS AS REQUIRED FOR ROOF SLOPE. STEEL PIPE SHALL MEET ASTM A53, TYPE E OR S. 6. STEEL PLATE FOR PLATE GIRDERS SHALL MEET ASTM A992 (GRADE 50). STEEL PLATE MEETING ASTM A572, GRADE 50 IS AN ACCEPTABLE SUBSTITUTE. A QUALIFIED ENGINEER REGISTERED IN THE STATE WHERE THE PROJECT IS LOCATED SHALL DESIGN THE UNITS. UNITS SHALL BE DESIGNED FOR CONSTRUCTION, HANDLING, ERECTION, AND IN-PLACE CODE PRESCRIBED LOADS AND ANY ADDITIONAL LOADS SHOWN ON THE DRAWINGS. ALL CONNECTIONS AND EMBEDS SHALL BE BY THE UNIT MANUFACTURER INCLUDING CONNECTION TO THE FOUNDATIONS. 7. BOLTS AT STEEL TO STEEL CONNECTIONS SHALL BE 3/4-INCH DIAMETER, ASTM A325-N, AND TIGHTENED TO THE SNUG TIGHT CONDITION AS DEFINED BY AISC UNLESS OTHERWISE NOTED. WHERE CONNECTIONS ARE NOTED TO BE ASTM A 325-SC, BOLTS SHALL BE TIGHTENED TO THE MINIMUM PRETENSION FOR FULLY TIGHTENED BOLTS BY ONE OF THE AISC APPROVED METHODS. DESIGN WALL PANEL UNITS FOR VERTICAL DEAD AND LIVE LOADS, WIND/SEISMIC LOADS PERPENDICULAR TO PANEL FACE, AS PREVIOUSLY NOTED, AND SEISMIC LOAD PARALLEL TO PANEL FACE TO MATCH DIAPHRAGM CONNECTION CAPACITY (SEE DETAILS FOR CONNECTION CAPACITY). IN ADDITION, DESIGN FOR SPECIAL LOADS WHERE SHOWN ON THE DRAWINGS. 8. ANCHOR BOLTS IN CONCRETE OR MASONRY SHALL BE 3/4-INCH DIAMETER ASTM F1554 GRADE 55, WELDABLE, UNLESS NOTED OTHERWISE. 9. FIELD BOLTING INSTALLATION SHALL BE INSPECTED IN ACCORD WITH THE BUILDING CODE AND THE AISC MANUAL. 5. PRECAST SUPPLIER IS RESPONSIBLE FOR DESIGN, DETAILING AND FURNISHING OF ALL HEADERS, POUR STRIPS, UNIT LAYOUT, OPENINGS THROUGH FLOOR, ETC., AS NECESSARY TO PROVIDE FOR A COMPLETE INSTALLATION. 6. UNITS SHALL HAVE ONE HOUR UNRESTRAINED FIRE RESISTANCE RATING IN ACCORD WITH UL J949 AND SHALL HAVE UL LABELS. 10. ALL WELDING SHALL CONFORM TO THE PROVISIONS OF THE AMERICAN WELDING SOCIETY CODE AWS D1.1. ELECTRODES SHALL MATCH BASE METALS AS SPECIFIED IN IBC. ALL WELDING OF ASTM A706 REINFORCING STEEL TO STRUCTURAL STEEL SHALL BE IN ACCORD WITH AWS D1.4 USING E70 ELECTRODES. 7. ALL OPENINGS REQUIRING CUTTING OF STRANDS SHALL BE BY UNIT MANUFACTURER. COORDINATE WITH MECHANICAL, ELECTRICAL AND OTHER TRADES INVOLVED. 8. DEFLECTION OF PRECAST FLOOR FRAMING MEMBERS SUPPORTING MASONRY BEARING OR PARTITION WALLS ABOVE SHALL NOT EXCEED SPAN/480 FOR FULL DEAD AND LIVE LOAD INCLUDING LONG TERM DEFLECTIONS DUE TO ALL SUSTAINED LOADS. 9. DEFLECTION OF PRECAST ROOF OR FLOOR FRAMING MEMBERS NOT SUPPORTING MASONRY WALLS ABOVE SHALL NOT EXCEED SPAN/600 FOR LIVE LOAD ONLY, AND NOT TO EXCEED SPAN/240 FOR DEAD AND LIVE LOADS. 20,000 PSF 60,000 PSF 11. THE TESTING LABORATORY SHALL VISUALLY INSPECT ALL FIELD WELDING. ALL COMPLETE PENETRATION WELDS SHALL BE TESTED AND CERTIFIED BY AN INDEPENDENT TESTING LABORATORY. 12. ALL BOLTS (HIGH STRENGTH, ANCHOR BOLTS, EXPANSION BOLTS, ADHESIVE ANCHORS, ETC.) SHALL BE INSTALLED WITH STEEL WASHERS. 13. ALL WELDS SHOWN ON THE DRAWINGS SHALL BE SHOP WELDS UNLESS NOTED OTHERWISE. CONTRACTOR MAY SUBSTITUTE FIELD WELDS FOR SHOP WELDS AT HIS DISCRETION. SHOP DRAWINGS SHALL CLEARLY NOTE SHOP AND FIELD WELDS. 10. PRECAST DESIGN SHALL COMPLY WITH ALL FEMA 361 REQUIREMENTS AND A SET OF CALCULATIONS SHALL BE SUBMITTED TO FEMA FOR REVIEW. (SEE ALSO "FEMA 361 SAFE ROOM LOADS AND CRITERIA" SECTION). 14. THE CONTRACTOR SHALL RETAIN A PROFESSIONAL ENGINEER LICENSED IN THE STATE WHICH THE PROJECT IS LOCATED TO DESIGN ALL STEEL CONNECTIONS NOT FULLY DETAILED IN THE DRAWINGS. CONNECTION DESIGN CALCULATIONS BEARING THE SEAL AND SIGNATURE OF THE ENGINEER RESPONSIBLE FOR THEIR PREPARATION SHALL BE SUBMITTED WITH THE SHOP DRAWING SUBMITTAL. 11. PRECAST SHOP DRAWINGS SHALL BE SIGNED AND SEALED BY THE LICENSED ENGINEER RESPONSIBLE OF THEIR PREPARATION. 15. CONTRACTOR IS RESPONSIBLE FOR THE STABILITY OF THE BUILDING SYSTEM AT ALL TIMES DURING THE ERECTION PROCESS. CONTRACTOR SHALL CONSIDER EFFECTS FROM WIND, SEISMIC, AND OTHER LOADING DURING CONSTRUCTION. 12. COORDINATE WITH ALL OTHER TRADES WHICH PRECAST CONCRETE INTERACTS. THIS INCLUDES BUT IS NOT LIMITED TO COORDINATING WITH MASONRY, STEEL, CAST-IN-PLACE CONCRETE, JOIST, AND METAL DECK SUPPLIER. WHERE MISALIGNMENT OF STEEL EMBEDDED PLATES DUE TO IMPROPER COORDINATION OCCURS, THE CONTRACTOR SHALL HIRE AN ENGINEER LICENSED IN THE STATE IN WHICH THE PROJECT IS LOCATED TO PRODUCE A REPAIR AND SUBMIT THE REPAIR DETAIL WITH CALCULATIONS TO THE ENGINEER OF RECORD FOR REVIEW AND APPROVAL PRIOR TO INSTALLATION. 16. CONNECTIONS SHALL BE DESIGNED TO SUSTAIN THE FACTORED (LRFD) REACTIONS NOTED. WHERE NO REACTION HAS BEEN PROVIDED, THE CONNECTION CAPACITY SHALL NOT BE LESS THAN ONE-HALF THE MAXIMUM FACTORED UNIFORM LOAD LISTED IN THE AISC CONSTRUCTION MANUAL FOR THE GIVEN SPAN. 13. PRECAST SEATING UNITS SHALL BE DESIGNED WITH FIXED CONNECTIONS AT ONE END AND ALLOWED TO SLIP SLIGHTLY AT THE OTHER END. ALL PRECAST SEATING UNITS SHALL BE DESIGNED TO HAVE A MINIMUM FUNDAMENTAL FREQUENCY OF 4HZ AND SHALL BE CHECKED FOR VIBRATION. PRECAST SUPPLIER SHALL REVIEW ALL CONNECTIONS TO RAKERS BY OTHER TRADES AND SHALL PROVIDE ANY ADDITIONAL HARDWARE NOT SHOWN ON DRAWINGS NECESSARY FOR ADEQUATE SUPPORT. 1 ALL STEEL JOISTS AND JOIST GIRDERS SHALL BE DESIGNED, FABRICATED AND ERECTED IN ACCORD WITH IBC SECTION 2208, OPEN WEB STEEL JOISTS AND THE STANDARD SPECIFICATIONS FOR STEEL JOIST, K-SERIES, LH-SERIES, DLH-SERIES AND JOIST GIRDERS, PUBLISHED BY THE STEEL JOIST INSTITUTE. 6. 5. 4. 2. JOIST SHOE DEPTH SHALL BE 2 1/2" AT K SERIES JOIST, 6 1/2" LH SERIES JOISTS, UNLESS OTHERWISE NOTED. IF SHOE DEPTH IS DIFFERENT THAN NOTED, JOIST SUPPLIER SHALL COORDINATE TOP OF STEEL BEAM ELEVATIONS WITH STEEL SUPPLIER PRIOR TO FABRICATION. PROVIDE UNITS AS SHOWN ON THE DRAWINGS. MINIMUM 28-DAY CONCRETE COMPRESSIVE STRENGTH SHALL NOT BE LESS THAN 5,000 PSI. HOLLOW CORE JOINTS SHALL BE GROUTED SOLID. DOUBLE TEE FLANGES SHALL BE CONNECTED IN ACCORD WITH MANUFACTURER'S STANDARD DETAIL TO RESIST A SHEAR LOAD OF 1,000 LBS/FT VERTICALLY AND HORIZONTALLY. 3. STEEL JOISTS AND JOIST GIRDERS: 1. FABRICATOR SHALL BE AN "APPROVED FABRICATOR" IN ACCORD WITH IBC SECTION 1704.2, REGISTERED AND APPROVED BY THE LOCAL BUILDING DEPARTMENT. 5. STEEL TUBE SHALL MEET ASTM A500, GRADE B. 17. ALL BOLTED MOMENT CONNECTIONS SHALL UTILIZE HIGH STRENGTH SLIP CRITICAL BOLTS. 18. CONNECTIONS SHOWN ON CONSTRUCTION DOCUMENTS ARE FOR CONCEPTUAL PURPOSES ONLY. 19. COORDINATE WITH ALL OTHER TRADES WITH WHICH STEEL INTERACTS. THIS INCLUDES BUT IS NOT LIMITED TO COORDINATING WITH MASONRY, CAST-IN-PLACE CONCRETE, JOIST, AND METAL DECK SUPPLIER. WHERE MISALIGNMENT OF STEEL EMBEDDED PLATES DUE TO IMPROPER COORDINATION OCCURS, THE CONTRACTOR SHALL HIRE AN ENGINEER LICENSED IN THE STATE IN WHICH THE PROJECT IS LOCATED TO PRODUCE A REPAIR AND SUBMIT THE REPAIR DETAIL WITH CALCULATIONS TO THE ENGINEER OF RECORD FOR REVIEW AND APPROVAL PRIOR TO INSTALLATION. 20. CONTRACTOR IS RESPONSIBLE FOR DESIGNING ALL STEEL TRUSS AND/OR BRACE CONNECTIONS FOR THE ULTIMATE MEMBER FORCES SHOWN IN ACCORDANCE WITH AISC LRFD SPECIFICATIONS. IF A MEMBER FORCE IS NOT SHOWN, THE CONNECTION SHALL BE DESIGNED FOR THE FULL TENSION CAPACITY OF THE MEMBER. CONNECTIONS SHALL BE DESIGNED TO TRANSFER THE MAXIMUM COMBINATION OF THE FORCES OF ALL MEMBERS FRAMING INTO THE JOINT. 21. ALL MEMBER FORCES SHOWN ARE TO BE TRANSFERRED TO THE WORK POINT. THE WORK POINT IS DEFINED AS THE INTERSECTION OF ALL CENTROIDS OF THE MEMBERS FRAMING INTO THE JOINT. AT BRACED FRAMES WHERE HORIZONTAL MEMBERS FRAMING INTO THE JOINT HAVE VARYING DEPTHS, AND SIMILAR TOP OF STEEL ELEVATIONS, THE WORK POINT SHALL BE BASED ON THE CENTER LINE OF THE HORIZONTAL MEMBER OF LEAST DEPTH (IE, THE WORKPOINT WILL NOT NECESSARILY CORRESPOND TO THE DEEPER MEMBER). 22. THE MEMBER SIZES SHOWN ON THE DRAWINGS DO NOT ACCOUNT FOR NET AREA REDUCTION DUE TO BOLT HOLES. PROVIDE SHOP WELDED MEMBER END SUPPLEMENT PLATES WHERE REQUIRED FOR BOLT HOLE NET-AREA REDUCTION. ALL MEMBER END SUPPLEMENT PLATES, SPLICE PLATES, FILLER PLATES AND GUSSET PLATES OF TRUSS CONNECTIONS SHALL BE ASTM A572, GRADE 50. REVIEW OF SHOP DRAWINGS DOES NOT RELIEVE THE CONTRACTOR FROM CONFORMANCE WITH THE INTENT OF THE DRAWINGS. REVIEW DOES NOT IMPLY OR STATE THAT THE FABRICATOR HAS CORRECTLY INTERPRETTED THE CONSTRUCTION DOCUMENTS. 4. CONTRACTOR SHALL SUBMIT CALCULATIONS WITH THE SHOP DRAWING SUBMITTALS, SIGNED AND SEALED BY THE ENGINEER, LICENSED IN THE STATE WHICH THE PROJECT IS LOCATED, RESPONSIBLE FOR THEIR PREPARATION WHEN REQUIRED IN THE SPECIFICATIONS (SEE ALSO 'DEFERRED SUBMITTALS'). 5. COPIES OF THE CONTRACT DOCUMENTS SHALL NOT BE SUBMITTED AS SHOP DRAWINGS. CONTRACT DRAWINGS SHOW ONLY GENERAL DESIGN INTENT. FINAL SHOP DRAWING SECTIONS SHALL PROVIDE SIZES, LAYOUT, EXACT DIMENSIONS, ELEVATIONS, GRADES OF MATERIALS, ETC., SPECIFIC TO EACH LOCATION. 6. SHOP DRAWINGS SHALL BE REVIEWED AND STAMPED BY THE GENERAL CONTRACTOR OR CONSTRUCTION MANAGER PRIOR TO SUBMITTING TO DLR GROUP. REQUEST FOR INFORMATION FOR ITEMS SUCH AS OVERALL BUILDING GEOMETRY, ELEVATIONS, ETC. SUBMITTED THROUGH SHOP DRAWINGS SHALL BE DETERMINED BY THE CONTRACTOR. IF GEOMETRY CANNOT BE DETERMINED FROM THE DRAWINGS, THE CONTRACTOR SHALL SUBMIT AN RFI AND COORDINATE THE RESPONSE WITH ALL AFFECTED TRADES PRIOR TO FABRICATION. 2. DEFERRED SUBMITTAL CALCULATIONS AND/OR SHOP DRAWINGS SHALL BE SIGNED AND SEALED BY THE ENGINEER RESPONSIBLE FOR THEIR PREPARATION AND SHALL BE SUBMITTED TO THE ENGINEER FOR REVIEW WITH THE SHOP DRAWING SUBMITTAL. ONCE REVIEWED, CONTRACTOR SHALL FORWARD TO THE BUILDING DEPARTMENT FOR APPROVAL. FABRICATION AND/OR INSTALLATION OF DEFERRED SUBMITTAL ITEMS SHALL NOT OCCUR UNTIL APPROVAL OF THE BUILDING DEPARTMENT IS RECEIVED. 3. REFER TO SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS. 15. METAL DECK ATTACHMENTS SHALL BE INSPECTED BY TESTING LABORATORY. DESIGN JOISTS AND BRIDGING TO RESIST A NET UPLIFT OF 15 PSF. JOISTS WITHIN 10'-0" OF BUILDING EDGES AND RIDGES SHALL BE DESIGNED FOR A NET WIND UPLIFT LOAD OF 25 PSF. 4. 3. 14. CONCRETE TOPPING SLABS AND THICKNESSES SHOWN ON PLANS AND DETAILS ARE NOMINAL THICKNESSES. ACTUAL THICKNESSES WILL VARY DUE TO BEAM CAMBERS AND DECK/ BEAM DEFLECTIONS. PROVIDE THICKNESSES AS REQUIRED TO ACHIEVE A LEVEL FLOOR WITH A MINIMUM ACTUAL THICKNESS NOT LESS THAN THE THICKNESS CALLED OUT ON PLANS MINUS 1/4”. 4. STRUCTURAL STEEL SHALL MEET ASTM A36 UNLESS NOTED OTHERWISE. STRUCTURAL STEEL WIDE FLANGE SHAPES SHALL MEET ASTM A992 (GRADE 50). THE SUBMITTAL SCHEDULE PROVIDED BY THE CONTRACTOR IS NECESSARY TO PROVIDE REASONABLE TIME TO STAFF APPROPRIATELY FOR THE SCHEDULED SUBMITTALS. THE SUBMITTAL ENGINEER'S REVIEW SCHEDULE IS SUBJECT STRICTLY TO THE SUBMITTAL SCHEDULE PROVIDED BY THE CONTRACTOR. 13. LOADS EXCEEDING 50 LBS SHALL NOT BE PERMITTED TO BE HUNG FROM METAL DECKING. HANGERS FOR DUCTWORK, PIPING, ELECTRICAL CONDUITS, ETC SHALL BE HUNG DIRECTLY FROM STRUCTURAL STEEL OR ANCHORS EMBEDDED IN CONCRETE. SUBMIT HANGING LOAD LAYOUT FOR REVIEW. 26. ALL CMU LOAD BEARING WALLS REQUIRE IBC LEVEL 1 SPECIAL INSPECTION AND SHALL BE SPECIAL INSPECTED FOR REINFORCING PLACEMENT, SIZE, POSITIONERS, AND LAP LENGTHS PRIOR TO POURING GROUT. 3. 2. 12. CONCRETE REQUIRED FOR COMPOSITE ACTION SHALL MEET 28-DAY COMPRESSIVE STRENGTH PRIOR TO SUPPORTING TOPPING SLABS AND/OR MASONRY WALLS OR OTHER HEAVY LOADS. SIZE, TYPE AND SPACING OF JOIST BRIDGING TO BE IN ACCORDANCE WITH STEEL JOIST INSTITUTE RECOMMENDATIONS. USE 'X'-BRIDGING AT DISCONTINUOUS ENDS OF BRIDGING. LOCATE BRIDGING TO AVOID MECHANICAL OPENINGS. STRUCTURAL STEEL: 1. FABRICATOR SHALL BE AISC CERTIFIED AND AN "APPROVED FABRICATOR" IN ACCORDANCE WITH IBC SECTION 1704.2, REGISTERED AND SPPROVED BY THE LOCAL BUILDING DEPARTMENT. AISC CERTIFICATION SHALL BE SHOWN CLEARLY ON THE SHOP DRAWINGS TO AVOID SHOP DRAWINGS BEING REJECTED. 2. DEFERRED SUBMITTALS: 1. THE FOLLOWING ITEMS ARE DEFERRED SUBMITTAL ITEMS: CONCRETE MIXTURE DESIGN MORTAR AND GROUT DESIGN PRECAST CONCRETE UNITS STEEL JOISTS METAL STAIRS STRUCTURAL STEEL CONNECTIONS COLD-FORMED METAL FRAMING 11. COMPOSITE DECK DESIGN IS INTENDED TO BE UNSHORED UNLESS OTHERWISE NOTED. IT IS THE CONTRACTOR’S RESPONSIBILITY TO CHECK ALL DECKING CONDITIONS TO DETERMINE IF THE DECKING HAS SUFFICIENT STRENGTH AND STIFFNESS FOR CONSTRUCTION LOADING. CONTRACTOR SHOULD CONSIDER USING SHORING WHERE FLOOR FLATNESS AND LEVELNESS NUMBERS ARE REQUIRED. FLOOR FLATNESS AND LEVELNESS NUMBERS CAN BE MEASURED IN THE SHORED CONDITION WHEN SHORES ARE USED. WHEN SHORING IS USED, CONTRACTOR SHALL PROVIDE ALL ENGINEERING DESIGN OF SHORING AND SUBMIT FOR REVIEW. 3. ALL COMPLETE JOINT PENETRATION WELDS SHALL BE ULTRASONIC TESTED BY THE INSPECTION AGENCY. STRUCTURAL PRECAST CONCRETE: 1. FABRICATOR SHALL BE AN "APPROVED FABRICATOR" IN ACCORD WITH IBC SECTION 1704.2, REGISTERED AND APPROVED BY THE LOCAL BUILDING DEPARTMENT. 10. ALL DECK SHALL BE CONTINUOUS OVER 3 SPANS UNLESS OTHERWISE NOTED. WHERE LESS THAN 3 SPANS IS AVAILABLE, PROVIDE, FOR THE ACTUAL SPAN CONDITION, DECK GAGE CAPABLE OF SUPPORTING PUBLISHED DEAD AND LIVE LOAD CAPACITIES AND CONSTRUCTION SPANS NOTED FOR 3 SPAN CONDITIONS. THE DECK SUPPLIER SHALL VERIFY THAT THE DECK SUPPLIED MEETS OR EXCEEDS THE REQUIRED CLEAR SPANS FOR THE ACTUAL PROJECT AND SHALL POST THE ALLOWABLE CONSTRUCTION CLEAR SPANS CLEARLY ON THE SHOP DRAWINGS. IF LOCATIONS EXIST ON THE PROJECT THAT EXCEED THE ALLOWABLE CONSTRUCTION CLEAR SPAN, THE SUPPLIER SHALL INCREASE THE DECK THICKNESS AS NECESSARY TO ACCOMMODATE ACTUAL SPAN CONDITION. 25. CONTRACTOR SHALL REMOVE AND REPLACE WALL AT HIS COST IF WALL IS FOUND TO BE CONSTRUCTED WITHOUT REBAR POSITIONERS. 2. 2'-6" 2. 2. 2. ROOF DECK SHALL HAVE A MINIMUM YIELD STRENGTH, FY =33 KSI ROOF DECK SHALL BE ATTACHED TO SUPPORTING STRUCTURAL MEMBERS TO RESIST 300 PLF DIAPHRAGM SHEAR, UNLESS OTHERWISE NOTED ON DRAWINGS. ATTACH DECK AT PERIMETER TO MEET OR EXCEED THE MINIMUM FACTORY MUTUAL REQUIREMENTS DESIGNATED BY THE ARCHITECT WHERE APPLICABLE. 23. REFER TO ARCHITECTURAL DRAWINGS FOR ALL NON-LOAD BEARING CMU WALLS AND REINFORCE AS FOLLOWS, UNLESS OTHERWISE NOTED: 6” AND 8” CMU: (1) #4 @48” OC 12” CMU: (2) #4 @48”OC SEISMIC LOAD: SEISMIC DESIGN IS IN ACCORD WITH IBC, OCCUPANCY CATEGORY PER TABLE 1604.5 IS CATEGORY III, S1 = 0.075 SS = 0.152 I = 1.25 SITE CLASS = C SDS = 0.12 SD1 = 0.09 DESIGN CATEGORY 'B' R = 3.0 Ωo = 3.0 Cd = 3.0 STEEL SYSTEM NOT SPECIFICALLY DETAILED FOR SEISMIC RESISTANCE R = 4.0 Ωo = 2.5 Cd = 4.0 INTERMEDIATE REINFORCED MASONRY SHEAR WALLS R = 4.0 Ωo = 2.5 Cd = 4.0 ORDINARY PRECAST CONCRETE SHEAR WALLS R = 5.0 Ωo = 2.5 Cd = 4.5 ORDINARY REINFORCED CONCRETE SHEAR WALLS 2. SUBMITTALS GENERAL 1. THE CONTRACTOR SHALL DEVELOP AND SUBMIT A SUBMITTAL SCHEDULE CLEARLY INDICATING THE NUMBER OF STEEL SHOP DRAWINGS, CONCRETE REINFORCING DRAWINGS, AND OTHER SHOP DRAWINGS TO BE SUBMITTED EACH WEEK OVER THE DURATION OF THE PROJECT. 7. 15. ELECTRICAL PANELS, CONDUITS, PIPES, FIRE EXTINGUISHER CABINETS, ETC., ARE TO BE LOCATED SO AS NOT TO INTERFERE WITH REINFORCED AND/OR GROUTED CELLS. PIPES AND CONDUITS PASSING HORIZONTALLY THROUGH WALLS SHALL BE SLEEVED. MINIMUM SPACING OF SLEEVES SHALL BE THREE DIAMETERS. 1 STRUCTURAL OBSERVATIONS: 1. IN ACCORDANCE WITH 2012 IBC, SECTION 1704 STRUCTURAL OBSERVATION SHALL BE PERFORMED BY ENGINEER OF RECORD FOR SPECIAL MOMENT RESISTING FRAMES, SPECIAL CONCENTRICALLY BRACED FRAMES, AND CONCRETE SHEAR WALLS. A LETTER SHALL BE SUBMITTED TO BUILDING OFFICIAL STATING SITE VISITS HAVE BEEN MADE AND ANY DEFICIENCIES HAVE BEEN NOTED. STEEL DECK: 1. STEEL DECK AND ACCESSOCRES SHALL BE FROM STEEL CONFORMING TO ASTM A1008 OR ASTM A653. ALL METAL DECKING SHALL BE IN ACCORDANCE WITH THE STEEL DECK INSTITUTE SPECIFICATIONS AND RECOMMENDATIONS. DECK WELDING SHALL COMPLY WITH THE BUILDING CODE AND AWS D1.1 USING E70XX ELECTRODES. 14. VERTICAL REINFORCING REQUIRED BY THESE NOTES OR SHOWN ON THE FOUNDATION PLANS SHALL EXTEND FROM FOUNDATION TO TOP OF WALL UNLESS OTHERWISE NOTED. FIRE RATINGS: 1. FOR FIRE-RATING REQUIREMENTS AND METHODS, SEE ARCHITECTURAL DRAWINGS. CAMBER BEAMS NOTED THUS (+1"). THIS EXAMPLE INDICATES A POSITIVE (UPWARD) CAMBER OF 1 INCH. 6. TOP FOOTING REINFORCING SHALL TERMINATE AT TEE AND CORNER INTERSECTIONS WITH A STANDARD 90 DEGREE HOOK. ALL REINFORCING AT INTERSECTIONS SHALL EXTEND TO THE FAR FACE OF THE INTERSECTING FOOTING. THE COLLAPSE OF UPPER STRUCTURES WAS CONSIDERED IN THE DESIGN OF THE FEMA SHELTERS. WHEN THE REQUIRED NUMBER OF STUDS EXCEEDS WHAT CAN BE PLACED AT 4 1/2", PLACE A SECOND ROW OF STUDS AT 4 1/2", STARTING AT THE POINT NEAREST THE END OF THE BEAM, UNTIL THE REQUIRED NUMBER OF STUDS IS REACHED. WHEN TWO STUDS ARE REQUIRED, PLACE STUDS 1 1/2" EACH SIDE OF THE BEAM WEB CENTERLINE. 11. VERTICAL REINFORCING SHALL BE AS FOLLOWS, UNLESS OTHERWISE NOTED ON THE PLANS OR DETAILS. 6" CONC. BLOCK (1) #5 @ 4'-0" OC (ONLY WHERE SPECIFIED ON STRUCT. PLANS/ SECTIONS) 8" CONC. BLOCK (1) #5 @ 4'-0" OC 12" CONC. BLOCK (2) #5 @ 3'-4" OC 3. 7. b. COMPOSITE DECK SHALL BE 20 GAGE MINIMUM UNLESS OTHERWISE NOTED. REFER TO DRAWINGS FOR OTHER REQUIREMENTS. 3. SLABS ON GRADE AND ELEVATED SLABS: 1. ALL SLABS ON GRADE SHALL BE CAST ON A 15 MIL VAPOR BARRIER (RE:SPECS) INSTALLED PER MANUFACTURER'S WRITTEN INSTRUCTIONS, PLACED OVER CRUSHED ROCK DRAINAGE MATERIAL TO FORM A CAPILARY BREAK OF THICKNESS NOTED ON DRAWINGS, BUT NOT LESS THAN THAT PRESCRIBED BY THE GEOTECHNICAL ENGINEER. POST-INSTALLED ANCHORS ARE NOT TO BE INSTALLED UNTIL CONCRETE OR GROUT HAS REACHED ITS DESIGN STRENGTH. 5. PROVIDE CLASS 'A' LAP SPLICES FOR ALL TOP AND BOTTOM BARS WHERE LAP SPLICES ARE REQUIRED. PER ICC 500-08, A 100 PSF LIVE LOAD WAS USED FOR THE DESIGN OF FEMA LIDS AND SUPPORT STEEL MEMBERS. 6. 10. REINFORCING SHALL BE HELD IN PLACE PRIOR TO GROUTING WITH AT LEAST TWO WIRE POSITIONERS PER GROUT POUR AND AT REINFORCING SPLICES. 2. 6. PLACE STUDS UNIFORMLY ALONG THE BEAM OR PORTION OF BEAM INDICATED. CENTER THE STUDS OVER THE WEB AND PROVIDE A MAXIMUM SPACING OF 2'-0" AND A MINIMUM SPACING OF 4 1/2". IF THE REQUIRED NUMBER OF STUDS EXCEEDS THE NUMBER OF STUDS PLACED AT A SPACING OF 4 1/2", SEE FOLLOWING NOTE. ALL STEEL DECK SHALL BE HOT DIP GALVANIZED IN ACCORDANCE WITH ASTM A653 WITH MINIMUM COATING OF G60, UNLESS OTHERWISE NOTED. ALL COMPONENTS THAT MAKE UP THE SAFE ROOM INCLUDING DEFERRED SUBMITTALS SHALL BE DESIGNED IN STRICT ACCORDANCE WITH FEMA 361. CALCULATIONS SHALL BE PROVIDED AT EACH CONNECTION FOR VERIFICATION OF LOAD PATH. 3 a. 4. 3. FEMA WALLS AND LIDS WERE DESIGN FOR THE DEBRIS IMPACT OF A 15LB 2X4 BOARD AT 100 MPH AT VERTICAL SURFACES AND 67 MPH AT HORIZONTAL SURFACES. MASONRY CELLS SHALL BE FULLY GROUTED FOR INSTALLATION OF POST-INSTALLED ANCHORS. PROVIDE BOND BEAMS AT TOP OF ALL WALLS, AT ROOFS, STRUCTURAL FLOORS, AND WHERE SHOWN ON THE DRAWINGS. REFER TO ARCHITECTURAL, CIVIL, AND MEP DRAWINGS FOR DOOR AND WINDOW HARDWARE, USEABLE SAFE ROOM CAPACITY, VENTED AREAS, ETC TO COMPLY WITH FEMA 361 SAFE ROOM REQUIREMENTS. 5. 5. 9. 2. SAFE ROOM WALL AND SLAB ASSEMBLIES HAVE BEEN SELECTED BASED ON FEMA 361 APPENDIX E. NO ADDITIONAL TESTING OR ANALYSIS HAS BEEN PERFORMED TO ESTIMATE DYNAMIC IMPACT OF OBJECTS FOUND IN THE ACTUAL ENVIRONMENT AGAINST THE SAFE ROOM STRUCTURE. STUD PLACEMENT WHEN DECK VALLEYS ARE PARALLEL TO BEAM: COMPOSITE DECK SHALL HAVE A MIMIMUM YIELD STRENGTH, FY = 40 KSI 12. PROVIDE BOND BEAMS AT 48"OC (MAXIMUM) VERTICALLY WHERE STACK BOND CMU WALLS OCCUR. (REFER TO ARCHITECTURAL DRAWINGS) SCREW ANCHORS: EMBEDMENT OF POST-INSTALLED ANCHORS SHALL BE PER "TYP ANCHOR, EXPANSION, & ADHESIVE BOLT SHEDULE" ON THE DRAWINGS OR EMBEDMENT AS RECOMMENDED BY MANUFACTORURER WHERE NO EMBEDMENT IS SHOWN. 3. CONTINUOUS FOOTINGS: 1. CONTINUOUS FOOTING REINFORCING SHALL CONTINUE THROUGH ISOLATED SPREAD FOOTINGS WHERE THEY OCCUR. 4. 5. ADHESIVE ANCHORS: SIMPSON STRONG-TIE STRONG-BOLT WEDGE ANCHORS (ICC ESR-1771) HILTI KWIK BOLT TZ CONCRETE ANCHORS (ICC ESR-1917) SIMPSON STRONG-TIE SET-XP ADHESIVE ANCHORS (ICC ESR-2508) HILTI HY-150 MAX-SD ADHESIVE ANCHORS (ICC ESR-3013) SIMPSON STRONG-TIE TITEN HD ANCHORS (ICC ESR-2713) 4. SPLICE LENGTHS FOR MASONRY REINFORCEMENT SHALL BE IN 72 TIMES THE REINFORCING BAR DIAMETER, TYPICAL. HOLES SHOULD BE FILLED WITH CONCRETE WITHIN 12 HOURS OF BEING DRILLED. HOLES WILL NEED TO BE CLEANED, REBAR CAGE INSTALLED, AND INSPECTED PRIOR TO PLACING CONCRETE. CONTRACTOR SHOULD DETERMINE THE NEED FOR REMOVABLE STEEL CASINGS TO MAINTAIN DRILLED PIER SHAPE IN UNSTABLE SOIL STRATA AND INCLUDE COST IN THE CONTRACT PRICE. SEE GEOTECHNICAL REPORT FOR BORING LOGS. 4. EXPANSION ANCHORS: WHEN THE REQUIRED NUMBER OF STUDS EXCEEDS THE NUMBER OF DECK VALLEYS, ADD A SECOND STUD IN DECK VALLEYS UNIFORMLY ALONG THE BEAM OR PORTION OF BEAM INDICATED UNTIL THE REQUIRED NUMBER OF STUDS IS REACHED. WHEN TWO STUDS ARE REQUIRED IN A DECK VALLEY, PLACE THE STUDS 1 1/2" EACH SIDE OF THE BEAM WEB CENTERLINE. 8. 2. 8. b. CONCRETE: 10. CONTRACTOR SHALL SUBMIT SHOP DRAWINGS AND CALCULATIONS FOR REVIEW PRIOR TO FABRICATION. 11. STEEL JOISTS ARE CALLED OUT ON PLAN SIMILAR TO THUS: "20LH". THIS EXAMPLE INDICATES A 20-INCH DEEP LH SERIES JOIST. 2 12. STEEL JOISTS ARE CALLED OUT ON PLAN SIMILAR TO THUS: "20SP". THIS EXAMPLE INDICATES A 20-INCH DEEP STEEL JOIST WITH LOADS AS SNOW DRIFT, EQUIPMENT LOADS, ETC. SEE PLANS FOR SUCH LOADS. 13. MANUFACTURER SHALL DESIGN JOISTS AND JOIST GIRDERS FOR THE LOADS NOTED ON THE DRAWINGS PLUS AN ADDITIONAL 400 POUND CONCENTRATED DEAD LOAD TO OCCUR ANYWHERE ALONG THE SPAN. DO NOT ALTER DEPTHS SHOWN ON PLANS UNLESS REQUESTED AND APPROVED IN WRITING PRIOR TO SHOP DRAWING SUBMITTAL. 14. COORDINATE EXACT MECHANICAL EQUIPMENT WEIGHT AND LOCATION WITH MECHANICAL CONTRACTOR AND DESIGN JOISTS AND JOIST GIRDERS FOR TRIBUTARY LOADS. COORDINATE JOIST WEBS WHERE MECHANICAL DUCTS SHOWN ON MECHANICAL DRAWINGS ARE DESIGNED TO PENETRATE THROUGH JOIST WEBS. 15. REFER TO SNOW DRIFT DIAGRAM FOR SNOW DRIFT LOADS. LOADS SHALL BE COMBINED WITH OTHER ROOF LOADS INDICATED IN ACCORDANCE WITH THE BUILDING CODE. SNOW DRIFT LOADS SHALL BE DISTRIBUTED OVER THE TRIBUTARY WIDTH OF ROOF SUPPORTED BY THE JOIST. GRADE BEAMS: 1. TOP GRADE BEAM REINFORCING SHALL BE SPLICED ONLY AT MIDSPAN AND BOTTOM GRADE BEAM REINFORCING SHALL BE SPLICED ONLY AT SUPPORTS. SIDE BARS MAY BE SPLICED WHEREVER CONVENIENT. 2. TOP GRADE BEAM REINFORCING SHALL TERMINATE AT TEE AND CORNER INTERSECTIONS WITH A STANDARD 90 DEGREE HOOK. ALL REINFORCING AT INTERSECTIONS SHALL EXTEND TO THE FAR FACE OF THE INTERSECTING GRADE BEAMS. 3. CONSTRUCTION JOINT LOCATIONS SHALL BE APPROVED BY THE STRUCTURAL ENGINEER PRIOR TO CONSTRUCTION AND TYPICALLY SHALL OCCUR WITHIN THE CENTER THIRD OF THE GRADE BEAM SPAN. CONSTRUCTION JOINT SURFACES SHALL BE ROUGHENED AND TREATED TO IMPROVE BOND IN ACCORDANCE WITH THE SPECIFICATIONS. 4. GRADE BEAMS SHALL NOT HAVE CONSTRUCTION JOINTS IN A HORIZONTAL PLANE. 5 SIDES OF GRADE BEAMS SHALL BE FORMED. IF EXCAVATIONS ARE MADE NEATLY AND GRADE BEAM WIDTHS ARE INCREASED A MINIMUM OF TWO INCHES, SIDES MAY BE CAST AGAINST THE EARTH CUT. THE ADDITIONAL WIDTH IS NECESSARY TO PROVIDE THE PROPER REINFORCING COVER FOR THIS CONSTRUCTION METHOD. 1 © 2012, DLR Group of Missouri inc., a Missouri corporation CA No. 001614, ALL RIGHTS RESERVED. MECHANICAL COUPLERS SHALL BE TYPE 2 COUPLERS CAPABLE OF SUSTAINING 125% Fy. CONCRETE MASONRY UNITS (CMU): 1. THE MINIMUM 28-DAY COMPRESSIVE STRENGTH OF THE CONCRETE MASONRY UNITS SHALL BE 1,900 PSI ON THE NET AREA, PROVIDING A STRUCTURAL DESIGN COMPRESSIVE STRENGTH OF 1,500 PSI PER THE INTERNATIONAL BUILDING CODE, TABLE 2105.2.2.1.2. 3. PLACE ONE STUD IN DECK VALLEYS, UNIFORMLY ALONG THE BEAM OR PORTION OF BEAM INDICATED, CENTERED OVER THE BEAM WEB. IF THE REQUIRED NUMBER OF STUDS IS LESS THAN THE NUMBER OF DECK VALLEYS, ADD STUDS AS REQUIRED TO PROVIDE A MAXIMUM STUD SPACING OF 2'-0". IF THE REQUIRED NUMBER OF STUDS EXCEEDS THE NUMBER OF DECK VALLEYS, SEE FOLLOWING NOTE. JOPLIN, JASPER COUNTY, MISSOURI 6. 2. STAGE RIGGING: LOFT BLOCK SUPPORT BEAMS VERTICAL AND HORIZONTAL LIVE LOAD = 750 PLF HEAD BLOCK BEAM VERTICAL AND HORIZONTAL LIVE LOAD = 3,000 PLF LOADING BRIDGE VERTICAL LOAD = 3,000 PLF LOADING BRIDGE HORIZONTAL LOAD = 300 PLF BENJAMIN TALPOS LAP ALL WELDED WIRE REINFORCING AT LEAST ONE FULL WIRE SPACING PLUS 2 INCHES. * 6% ±1 1/2% AIR ENTRAINED CONCRETE AT ALL EXTERIOR CONDITIONS INCLUDING SHALLOW FOUNDATIONS. FLOORS: 40 PSF (CLASSROOMS) 50 PSF (OFFICE) 100 PSF (CORRIDORS) 125 PSF (STORAGE ROOMS) 125 PSF (MECHANICAL ROOMS) 150 PSF (ELEVATOR MACHINE ROOM) 40 PSF (CATWALKS) 10/8/2012 4:50:02 PM 5. NWT = NORMAL WEIGHT CONCRETE (UNIT WEIGHT = 145 PCF) LWT = LIGHT WEIGHT CONCRETE (UNIT WEIGHT = 110 PCF) 1 DESIGN LIVE LOADS: ROOF: 20 PSF (REDUCIBLE IN ACCORD WITH IBC 1607.12.2) ROOF: SNOW LOADS IN ACCORD WITH INTERNATIONAL BUILDING CODE SECTION 1608, INCLUDING DRIFT SNOW LOADS Pf = Ce x I x Pg Ce = 1.0 I = 1.10 Pg = 30 PSF Pf = 30 PSF (NOT REDUCIBLE PER JOPLIN, MISSOURI AMENDMENTS) DRIFTING SNOW LOADS - SEE SNOW DRIFT PLANS: DRIFT SHALL BE COMBINED WITH OTHER LOADS NOTED IN ACCORDANCE 2 WITH BUILDING CODE PRESCRIBED COMBINATIONS. C:\Users\rrobley\Desktop\Revit 2013 Projects\Joplin HS\13-12102-00_LOCAL_struct_2012_PAC__RDR_DENVER.rvt ALL REINFORCING SHALL BE PROPERLY CHAIRED BY THE CONTRACTOR. a. CONTRACTOR TO SUBMIT CONTROL JOINT LOCATIONS IN TOPPING SLAB TO ENGINEER FOR APPROVAL. CONTROL JOINT DEPTH SHALL BE NO MORE THAN 1/4 TOPPING THICKNESS. SEE TYPICAL DETAILS FOR MAX CONTROL JOINT SPACING. SCREW ANCHORS: STUD PLACEMENT WHEN DECK VALLEYS ARE PERPENDICULAR TO BEAM: 3 10-8-12 ADD #3 DESIGN DEAD LOADS: 2 ROOF: 25 PSF (UNLESS NOTED OTHERWISE) FLOORS: 100 PSF (INCLUDES PARTITION WALLS) 2 4. CLASS A B C D F G H I CONSTRUCTION DOCUMENTS SHALL NOT BE REPRODUCED FOR USE OF SHOP DRAWING SUBMITTALS OR ANY OTHER PROJECT WITHOUT WRITTEN CONSENT BY DLR GROUP. [FEMA 361] SAFE ROOM LOADS & CRITERIA: BASIC WIND SPEED, V = 250 MPH (ULTIMATE) (PER ASCE 7, METHOD 2) EXPOSURE "C" 2 Iw = 1.0 Kd = 1.0 Kzt = 1.0 GCpi = ±0.55 REINFORCING BAR SPLICES SHALL BE IN ACCORDANCE WITH THE REQUIREMENTS OF ACI 318-11 AND THE REINFORCING SPLICE LENGTH TABLE SHOWN ON THE DRAWINGS. PROVIDE CLASS 'B' LAP SPLICE, UNLESS NOTED OTHERWISE. CAST-IN-PLACE CONCRETE: 1. PROPORTION EACH INDIVIDUAL CONCRETE MIX TO HAVE THE FOLLOWING PROPERTIES: THESE DOCUMENTS SHALL NOT BE CONSTRUED AS STAND-ALONE DOCUMENTS. CONTRACTOR SHALL COORDINATE WITH ALL OTHER CONSULTANTS' WORK. WIND LOAD: 2 BASIC WIND SPEED, V = 120 MPH (ULTIMATE) EXPOSURE "C" (OCCUPANCY CATEGORY PER TABLE 1604.5 IS CATEGORY III) 3. 4. 3. ADHESIVE ANCHORS: SIMPSON STRONG-TIE WEDGE-ALL ANCHORS (ICC ESR-1396) HILTI KWIK BOLT 3 MASONRY ANCHORS (ICC ESR-1385) SIMPSON STRONG-TIE SET ADHESIVE ANCHORS (ICC ESR-1772) HILTI HY-150 MAX ADHESIVE ANCHORS (ICC ESR-1967) SIMPSON STRONG-TIE TITEN HD ANCHORS (ICC ESR-1056) 2 10-4-12 ADD #2 WHERE DISCREPANCIES OCCUR BETWEEN GENERAL NOTES, PLANS, DETAILS, AND SPECIFICATIONS, THE MOST STRINGENT REQUIREMENTS SHALL GOVERN, UNLESS VERIFIED OTHERWISE BY THE ARCHITECT AND ENGINEER IN WRITING. 10. IF THE STRUCTURAL ENGINEER'S SEAL AND SIGNATURE IS NOT AFFIXED TO THESE DRAWINGS, THESE DRAWINGS ARE INTENDED FOR PRELIMINARY PURPOSES ONLY AND SHALL NOT BE USED FOR CONSTRUCTION. 1. ALL TOPPING SLABS SHALL BE REINFORCED WITH 6X6 W2.1XW2.1 WELDED WIRE REINFORCEMENT, UNLESS OTHERWISE NOTED. WELDED WIRE FABRIC IN THE TOPPING SHALL BE FLAT SHEETS CENTERED IN THE TOPPING THICKNESS AND CHAIRED TO MAINTAIN ITS CORRECT LOCATION. LAP ONE FULL MESH AT SPLICES AND WIRE TOGETHER. EXPANSION ANCHORS: 7290 West 133rd Street Overland Park, Kansas 66213 tel: (913)897-7811 THESE NOTES SHALL SUPPLEMENT THE PROJECT SPECIFICATIONS, WHICH SHALL BE REFERRED TO FOR ADDITIONAL REQUIREMENTS. 1. 3. NUMBER OF SHEAR STUDS INDICATED THUS (#) ON PLAN. WHERE THE NUMBER OF STUDS FOR A BEAM IS INDICATED ON THE PLAN BY ONE NUMBER, STUDS SHALL BE PLACED SYMMETRICALLY WITH RESPECT TO THE BEAM CENTER LINE WITH 1/2 OF THE STUDS ON EACH HALF OF THE BEAM SPAN. WHERE NUMBER OF STUDS IS INDICATED BY MORE THAN ONE NUMBER, PLACE THE NUMBER OF STUDS INDICATED BY EACH NUMBER UNIFORMLY IN THAT PORTION OF THE BEAM. Architecture Engineering Planning Interiors DETAILS THAT ARE NOTED AS "TYP" ON DETAIL TITLES ARE TO BE APPLIED TO THE PROJECT CONSTRUCTION AS GENERAL CONSTRUCTION METHODS UNLESS NOTED OTHERWISE. THESE DETAILS ARE NOT CUT AT ALL LOCATIONS THEY OCCUR AND MAY NOT BE CUT AT ALL. WHERE NO SPECIFIC DETAILS ARE SHOWN CONSTRUCTION SHALL CONFORM TO SIMILAR CONDITIONS ELSEWHERE ON THE PROJECT. 6. 9. 2. CONSTRUCTION MATERIAL AND EQUIPMENT PLACED ON FRAMED CONSTRUCTION SHALL BE SUCH THAT THE LOAD DOES NOT EXCEED THE DESIGN LIVE LOAD OF THE CONSTRUCTION. PROVIDE SHORING OF CONSTRUCTION WHERE NECESSARY FOR LOADS. DO NOT SCALE DRAWINGS. 8. UNLESS OTHERWISE NOTED ON PLAN OR DETAIL, PROVIDE 1 #4 IN TOPPING SLAB EACH SIDE OF OPENINGS EXCEEDING 12 INCHES IN SIZE. EXTEND REINFORCING 1'-6" PAST CORNER OF OPENING. CONTRACTOR IS TO ESTABLISH AND VERIFY OPENINGS AND INSERTS FOR ITEMS TO BE INSTALLED BY OTHER TRADES PRIOR TO SUBMITTAL OF SHOP DRAWINGS AND CONSTRUCTION. 5. 7. 2. CONCRETE COVER REQUIREMENTS FOR CAST-IN-PLACE , NON-PRESTRESSED CONCRETE UNLESS OTHERWISE NOTED ON DETAILS: a. CONCRETE CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH: 3" b. FORMED CONCRETE EXPOSED TO EARTH OR WEATHER: #6 BARS AND LARGER: 2" #5 BARS AND SMALLER: 1 1/2" c. CONCRETE NOT EXPOSED TO WEATHER OR IN CONTACT WITH EARTH: SLABS, WALLS, AND JOISTS: #14 AND #18 BARS: 1 1/2" #11 BARS AND SMALLER: 1" d. BEAMS, COLUMNS: PRIMARY REINFORCEMENT: 2" TIES, STIRRUPS, SPIRALS: 1 1/2" 1 MASONRY: JOPLIN HIGH SCHOOL 4. 2. 2. 1 9-25-12 ADD #1 GENERAL NOTES: 1. THE DRAWINGS REPRESENT THE FINISHED STRUCTURE, NOT THE METHOD OF CONSTRUCTION. THE CONTRACTOR SHALL PROVIDE ALL MEASURES NECESSARY TO PROTECT THE STRUCTURE DURING CONSTRUCTION INCLUDING, BUT NOT LIMITED TO, BRACING, SHORING FOR CONSTRUCTION LOADS AND EQUIPMENT, ETC. THE ARCHITECT-ENGINEER IS NOT RESPONSIBLE FOR THE CONTRACTOR'S MEANS AND METHODS, SEQUENCES OF CONSTRUCTION, OR THE SAFETY PROGRAM. OBSERVATION VISITS TO THE SITE BY THE ARCHITECT-ENGINEER WILL NOT INVOLVE REVIEW OF THESE ITEMS. 1 POST-INSTALLED ANCHORS: 1. ALL POST INSTALLED ANCHORS SHALL BE INSTALLED IN ACCORDANCE WITH MANUFACTORER'S RECOMMENDATIONS AND ICC EVALUATION REPORTS CORRESPONDING TO THAT ANCHOR. 13-12102-00 9/25/2012 INTERNATIONAL BUILDING CODE, 2012 EDITION AS AMENDED BY THE CITY OF JOPLIN, MISSOURI 3. COMPOSITE BEAM SHEAR CONNECTOR STUDS: 1. SHEAR STUDS SHALL BE 3/4-INCH DIAMETER X LENGTH SHOWN ON PLANS, WITH A FINAL LENGTH NOT LESS THAN DEPTH WITH A FINAL LENGTH EQUAL TO DEPTH OF DECK PLUS 1.5" CONFORMING TO AWS D1.1. BEAMS SUPPORTING SLAB WITHOUT DESIGNATED STUD QUANTITY ARE TO BE NONCOMPOSITE BEAMS. PROVIDE SHEAR STUDS @ 2'-0" O.C. MAXIMUM AT ALL NONCOMPOSITE BEAMS. GERNERAL NOTES CODE: 2. CONCRETE REINFORCEMENT: 1. REINFORCING STEEL SHALL BE ASTM A615, GRADE 60. REINFORCING STEEL TO BE WELDED SHALL BE ASTM A706, GRADE 60. CONCRETE TOPPING SLABS: 1. TOPPING THICKNESS SHOWN ON PLAN IS NOMINAL. ACTUAL THICKNESS WILL VARY DUE TO PRECAST CAMBER AND/OR STRUCTURE DEFLECTIONS. PROVIDE THICKNESS AS REQUIRED TO ACHIEVE A LEVEL FLOOR WITH A MINIMUM ACTUAL THICKNESS EQUAL TO THE THICKNESS CALLED OUT ON PLAN MINUS 1/2-INCH. 2 S0.1 GENERAL NOTES G L K NORTH NORTH H1 Revisions 11' - 0" 47 PSF JOPLIN, JASPER COUNTY, MISSOURI JOPLIN HIGH SCHOOL K12 JOIST SUPPLIER SHALL DESIGN JOISTS FOR ALL LOADS INDICATED IN THE GENERAL NOTES (S0.1, S0.2), ROOF SNOW DRIFT PLAN (S0.3), ON THE PLAN SHEETS AND ON THE DETAILS / SECTION SHEETS. CONTRACTOR TO COORDINATE ALL WEIGHTS AND LOCATIONS OF EQUIPMENT WITH THE JOIST SUPPLIER PRIOR TO SUBMITTING JOIST SHOP DRAWINGS. 2 10-08-12 ADD #3 14' - 0" 60 PSF J4 J7 K2 20' - 0" 79 PSF C. ROOF SNOW DRIFT PLAN J2 6' - 6" 13 PSF 15' - 0" 80 PSF H9 LF KC ALL SPECIAL JOIST CALCULATIONS MUST BE SIGNED AND SEALED BY THE ENGINEER RESPONSIBLE FOR THE WORK AND SUBMITTED WITH SHOP DRAWINGS FOR REVIEW. SUBMIT A REQUEST FOR INFORMATION (RFI) FOR INFORMATION NOT SPECIFICALLY NOTED ON THE DRAWINGS. 13-12102-00 09/10/12 S0.3 14' - 8" 89 PSF JJ 10' - 8" 54 PSF H3 F2 EJ F3 KA B. © 2012, DLR Group of Missouri inc., a Missouri corporation CA No. 001614, ALL RIGHTS RESERVED. SCALE: 1/32" = 1'-0" J1 11' - 6" 48 PSF C14 B14 JOIST SUPPLIER SHALL DISTRIBUTE LOADS TO JOIST BASED ON TRIBUTARY SPACING OF JOISTS. 7290 West 133rd Street Overland Park, Kansas 66213 tel: (913)897-7811 JC 14' - 8" 89 PSF ROOF SNOW DRIFT PLAN HF 11' - 6" 48 PSF HA 11' - 0" 47 PSF D12 BA 10' - 8" 54 PSF 16' - 3" 104 PSF A. Architecture Engineering Planning Interiors J H E F E1 90 PSF D1 90 PSF C1 90 PSF B1 11' - 0" 47 PSF 18' - 4" 104 PSF 1 D C B A KEY PLAN EL 70 PSF EC DJ 70 PSF DC CM 70 PSF CB BJ 90 PSF 11' - 0" 47 PSF 70 PSF 10' - 8" 54 PSF 11' - 0" 47 PSF 11' - 0" 47 PSF BC 18' - 4" 104 PSF 11' - 0" 47 PSF 11' - 0" 47 PSF 10' - 8" 54 PSF 10' - 8" 54 PSF 14' - 0" 60 PSF 14' - 0" 60 PSF 10' - 8" 54 PSF 11' - 0" 47 PSF BENJAMIN TALPOS 14' - 0" 60 PSF 10/8/2012 6:11:51 PM 11' - 6" 47 PSF C:\Users\BrionP\Documents\9-2013-Revit Projects\Joplin\13-12102-00_central_struct_2012.rvt PLAN NOTES: GB-20 GB-19 P-89 C-31 P-88 C-30 S3.1 BUILT-UP SEATING ON GEOFOAM. REINFORCE SLAB & WALLS W/ #4 @ 12"OC, TYP P-87 C-29 P-25 11 T.O. FTG 90'-0" T.O. SLAB 90'-8" P-86 C-28 AJ T.O. SLAB 98'-0" 1 2' - 0" 15 7' - 0" 3' - 11 3/8" 1' - 6" S3.2 S3.2 21 S3.2 2 STEP FTG 2 AL 1 51 HSS12x2x1/4 1 GB-59 P-53 P-52 14 P-51 P-50 S3.1 12" THICK PRECAST CONCRETE WALL 4 P-66 25 S3.1 1 12" THICK PRECAST CONCRETE WALL P-67 15 S3.1 STEP BOTT OF GR. BM 26 S3.1 P-97 15 14 P-98 S3.1 GB-38 3 P-64 P-77 C-23 S3.1 P-75 P-79 C-25 25 25 S3.1 S3.1 3 GB-81 3 T.O. SLAB 98'-0" 1 GB-7 8" CMU WALL W/ 1-#5 @ 16"O.C. S3.1 1 9" 1 1 3 S3.2 P-19 T.O. SLAB 98'-0" 25 4 1 3 13 GB-65 S3.1 P-70 AY 54 FEMA DOOR PER ARCH S3.1 P-15 P-62 P-18 C-11 1' - 1" 3 28' - 2" P-105 14 GB-3 8 " THICK PRECAST CONCRETE WALL, TYP 2 1 GB-67 GB-68 GB-69 GB-69 GB-70 GB-71 GB-72 GB-73 GB-74 GB-75 GB-76 3 GB-77 GB-1 GB-2 3 P-3 P-1 P-104 A1 A2 P-4 P-6 P-2 26' - 7 5/8" A3 A4 P-5 P-7 35' - 4 3/8" 33' - 8" 1' - 4" 8" 13 P-8 A5 P-9 S3.1 A6 A7 P-10 17' - 5 5/8" 23' - 9 5/8" A8 2' - 7 1/2" S3.2 9' - 8 3/8" P-12 24' - 1" A10 11' - 5 5/8" S3.2 6' - 4 5/8" 11 P-13 16 A9 32 P-11 1 10" 8" AZ A11 1 5' - 11 3/8" A12 S3.1 A13 4' - 7 5/8" 8' - 5" 8' - 6" 16' - 0" A16 MATCHLINE AREA A MATCHLINE AREA B P-17 C-9 P-14 A14 A15 5' - 1" 1' - 8 5/8" B12 B13 B12 B13 2 1 PLAN NOTES: KEY NOTES: 2 E. REFER TO GEOTECHNICAL REPORT FOR ALL SUBGRADE PREPARATION REQUIREMENTS. A. SEE CIVIL DRAWINGS FOR COORESPONDING SITE ELEVATIONS. B. SEE ARCHITECTURAL DRAWINGS FOR LOCATION OF THICKENED, SLOPED, RAISED, DEPRESSED SLABS AND DRAINS. F. SEE ARCHITECTURAL DRAWINGS FOR PANEL JOINT LOCATIONS. G. REFER TO SHEET S2.3 FOR PIER, GRADE BEAM, COLUMN AND BASE PLATE SCHEDULES. C. REFER TO GENERAL NOTES SHEETS S0.1 AND S0.2 FOR GENERAL NOTES, ABBREVIATIONS AND SYMBOLS. BENJAMIN TALPOS D. TOP OF GRADE BEAM ELEVATION = 97'-4", UNLESS NOTED OTHERWISE. 1 H. DENOTES FEMA 361 SAFE ROOM FLOOR. 2 I. WHERE THE CLEAR DISTANCE BETWEEN ANY TWO PIERS IS LESS THAN OR EQUAL TO TWO PIER DIAMETERS, DO NOT DRILL SECOND PIER UNTIL FIRST PIER HAS REACHED 3/4*f'c. 1 J. ALL CLADDING, SUPPORT, AND ATTACHMENTS ARE TO BE COORD WITH THE PRECAST SUPPLIER AND DESIGNED BY THE CONTRACTOR. 2 3 4" NORMAL WEIGHT CONCRETE SLAB-ON-GRADE W/ 6x6-W2.1xW2.1 WELDED WIRE REINFORCEMENT ON 15 MIL VAPOR RETARDER OVER 4" GRANULAR FILL. 5" LIGHT WEIGHT CONCRETE SLAB OVER 3" DEEP X 16 GA COMPOSITE GALVANIZED METAL DECK (8" TOTAL THICKNESS). REINFORCE SLAB WITH #4@12" OC EACH WAY LOCATED 2" FROM TOP OF SLAB. TYPICAL PIER CAP, 4'-0"x4'-0" - 3'-0" DEEP. 5-#7 TOP & BOTTOM. 1 4 WALL TYPE A, SEE SHEET S0.2 FOR FEMA WIND LOADS. 5 WALL TYPE B, SEE SHEET S0.2 FOR FEMA WIND LOADS. 6 FOUNDATIONS ARE DESIGNED TO BEAR ON SOIL. (SEE S0.1 FOR FOUNDATION DESIGN PARAMETERS). 7 PIER CAP, 4'-0"X4'-8 1/2" X 5'-0" DEEP. 5-#7 TOP & BOTTOM. FIRST LEVEL FOUNDATION PLAN - AREA A 2 SCALE: 1/8" = 1'-0" NORTH AZ 2' - 0 1/4" GB-35 GB-66 CONTRACTOR TO PROVIDE TEMPORARY SHORING OF ALL BASEMENT WALLS UNTIL ROOF SLAB HAS BEEN INSTALLED AND CONCRETE COMPRESSIVE STRENGTH, f'C HAS REACHED 3000 PSI MINIMUM. GB-55 S3.2 10/8/2012 4:50:11 PM C:\Users\rrobley\Desktop\Revit 2013 Projects\Joplin HS\13-12102-00_LOCAL_struct_2012_PAC__RDR_DENVER.rvt 1 16 8" CMU WALL P-57 1' - 0 1/4" S3.1 2" EJ 12" THICK PRECAST CONCRETE WALL AX 9" GB-6 TYP@W-SHAPE COL AV 12 P-100 8" CMU WALL P-101 GB-36 S3.1 P-63 C-5 GB-4 51 P-20 C-12 P-73 3 P-61 C-4 8' - 7 5/8" GB-79 GB-80 GB-56 P-59 C-2 GB-65 P-58 C-1 AT AU AW P-71 P-60 C-3 AS GB-78 8" CMU WALL P-56 2' - 4 3/4" 28.79 ° P-22 C-14 GB-57 GB-38 3 P-65 P-78 C-24 GB-61 FEMA DOOR PER ARCH GB-37 GB-64 GB-42 GB-39 1' - 6" P-54 GB-41 2' - 1 3/4" 1' - 2 5/8" 31.7 92° 30° GB-58 P-55 GB-40 1' - 11 3/4" GB-10 5° 2' 6" P-72 GB-53 S3.2 AQ AR 2' - 5 3/4" GB-54S3.2 21.365 ° 2' 6" P-99 2 41 AP 16' - 5 1/4" GB-52 10" THICH PRECAST CONCRETE WALL, TYP AO 6' - 2 1/2" 4 P-96 FEMA DOOR HSS12x2x1/4 PER ARCH 31 GB-63 P-76 C-21 AN 22' - 3 1/2" FEMA DOOR PER ARCH GB-51 P-81 C-19 S8.1 1' - 1 1/4" GB-32 P-82 C-20 P-80 C-18 23 P-84 C-26 1 GB-8 GB-33 STAIR PER ARCH TOF 96'-2" 1 STAIRS PER ARCH 35.6 37° GB-34 1 12" THICK PRECAST CONCRETE WALL STEP BOTT OF GR. BM P-83 C-22 GB-60 FEMA DOOR PER ARCH T.O. FTG 90'-8" 2" EJ 11 S3.1 TOF S3.1 6 93'-10" T.O. SLAB 2 98'-0" S3.1 10 " THICK PRECAST CONCRETE WALL, TYP S3.1 6 21 43 2 FTG STEP 2 S3.2 GB-50 GB-31 PRECAST SUPPLIER TO DESIGN CORNER CONNECTIONS TO CAST-IN-PLACE WALL. Structural Foundations 2 COORD FINAL PENETRATION FOR MECH DUCT W/ MECH CONTRACTOR. 11 S3.1 33 1 FTG STEP 2 53 2' - 0" P-49 2" EJ 2 2 10" THICK PRECAST CONCRETE WALL, TYP 26.52 S3.1 P-23 C-15 4" CONC TOPPING SLAB ON GEOFOAM 7' - 4" TOF 95'-0" HSS16x4x3/8 TOF 93'-10" 24 X-B RA CE P-68 AM 2 S3.2 2 P-48 P-85 C-27 S3.2 45 HSS16x4x3/8 GB-49 GB-30 P-103 10' - 0" © 2012, DLR Group of Missouri inc., a Missouri corporation CA No. 001614, ALL RIGHTS RESERVED. 2 3 10-8-12 ADD #3 SEE MECH FOR LOUVER, TYP GB-11 P-47 P-46 JOPLIN, JASPER COUNTY, MISSOURI P-24 C-16 2 10-4-12 ADD #2 S3.1 1 7290 West 133rd Street Overland Park, Kansas 66213 tel: (913)897-7811 S3.1 AK DN Architecture Engineering Planning Interiors 56 JOPLIN HIGH SCHOOL 55 10.682° 1 6 1 9-25-12 ADD #1 6 S3.1 11 2 13-12102-00 9/25/2012 23 FIRST LEVEL FOUNDATION PLAN - AREA A GB-29 2 5 1 AH S1.1A GB48 7' - 0" T.O. SLAB 98'-0" 1 T.O. SLAB 97'-6" 1 T.O. SLAB 94'-6" 2' - 0" 11" AG P-95 S3.1 GB-12 2 AE AF GB-13 DN SLOPE T.O. FTG 90'-0" 2 THICKENED SLAB (REINF PER 55/S3.1) S3.1 AI 10" THICK PRECAST CONCRETE WALL P-45 P-44 AC 11 P-26 10.682° GB-47 T.O. PIT = 94'-0" (VERIFY W/ SUPPLIER) TOF 96'-2" 53 AB AD GB-14 31' - 5" P-94 C-32 ° 21.365 2" EJ 8" THICK PRECAST WALL, TYP 3 SIDES. 5° 26.52 GB-28 2'-0"X2'-0"X2'-0" DP SUMP PIT (COORD W/ ELEV SUPPLIER) AA S3.1 RECESS STAGE FLOOR PER ARCH DWGS. FEMA DOOR PER ARCH 2 S3.1 H ARC PER 21 SEE MECH FOR LOUVER, TYP 5 6" 2' - 15 1 41 1 8" CONC STAIR WALL W/ #4 @ 12" O.C. EW, CENTERED P-42 T.O. SLAB 98'-0" 1 2 GB-63 S8.1 2 STEP FTG P-27 1 2 S3.1 2 GB-16 FTG STEP P-43 12" THICK PRECAST CONCRETE WALL 1 S3.1 46 1 31 FTG STEP TOF 95'-0" 2 PERFORATED METAL RETURN AIR GRILL 31 2 S3.1 P-91 C-36 6 TOF 93'-10" 24 P-102 P-69 TYP GB-46 P-41 2 33 S3.1 S3.2 5 S3.1 46 1'-0" THICKENED SLAB REINF W/ #5@12" OC 3" CLEAR FROM BOTT AT STAIR 8" THICK PRECAST CONCRETE WALL P-40 2 TYP@STAIR P-90 C-35 GB-17 P-28 P-92 C-37 S3.2 S3.2 GB-45 21 2 16 GB-44 6 S3.1 8' - 0" FEMA DOORS PER ARCH TOF 93'-10" 43 6" 2' - S3.1 HSS4X3X5/16 NESTED UNDER DECK FLUTE EA SIDE, TYP COORD FINAL PENETRATION FOR MECH DUCT W/ MECH CONTRACTOR. 8' - 0" GB-43 11 T.O. SLAB 98'-0" P-93 C-38 P-29 7 1 ° 28.79 1 S3.1 CE RA X-B S3.2 TYP@HSS COL 92° 31.7 16 T.O. FTG 90'-8" 2 S3.1 52 HSS12x2x1/4 STAIR PER ARCH 14 T.O. SLAB 98'-0" S3.2 3 30° GB-27 P-35 10" THICK PRECAST CONCRETE WALL, TYP 8" THICK PRECAST CONCRETE WALL GB-18 1 23 2' - 0" 1' - 3" HSS12x2x1/4 2 P-30 C-33 11 S3.1 2' - 6" GB-21 P-31 C-34 4' - 6 1/2" P-32 11 5/8" GB-23 P-33 P-34 8' - 7 3/4" GB-24 P-35 2' - 0" P-36 14' - 11 3/8" S3.2 PROVIDE L8X4X1/2 AT EACH EDGE, TYP GB-22 S3.1 17' - 7 5/8" GB-25 1 37° 35.6 GB-26 16 10' - 3 1/8" P-37 STEP GR BM 7' - 4 3/8" P-38 STEP GR BM 45 7' - 7 1/2" S3.1 P-39 STEP BOTT OF GR. BM 1' - 1 1/4" 11 10" THICK PRECAST CONCRETE WALL, TYP GB-15 1' - 2 7/8" STEP BOTT OF GR. BM AZ AZ MATCHLINE RE: S1.1A A2 A3 A4 A5 A6 A7 A8 A9 MATCHLINE RE: S1.1B A16 A10 A11 A12 A13 15' - 8" A1 A14 A15 97'-0" TO FTG 2 25 BA TYP S3.6 CC10 FF14 32' - 6" CC10 FF14 97'-0" TO FTG CC10 FF14 FTG STEP BB 99'-4" TO FTG 99'-4" TO FTG 15' - 4" 2' - 0" CC5 FF10 S3.4 S3.5 1 24' - 4" 1 1 CC25 1 CC25 2 11' - 4" 2 CC14 FF6 1 BF 1 1 6' - 0" PP1 97'-7" 70'-7" PP1 99'-4" 74'-4" 1 1 CC5 FF6 1 PP1 97'-7" 72'-7" S3.4 1 CC25 HSS10x6x3/8 (TOS = 108'-0 1/2") 2 2 1 CC25 99'-4" TO FTG 1 45 PP1 99'-4" 74'-4" BG 99'-4" TO FTG CC7 FF15 CC7 FF6 96'-0" TO FTG 2' - 6" 2 1 CC16 FF6 S3.4 CC21 2 HSS6x6x1/4 (TOS = 101'-4 1/2") S3.3 2' - 6" MECH UNITS PER MECH, TYP 1 1 PP1 97'-7" 70'-7" 2 PP1 97'-7" 70'-7" 2 PP1 97'-1" 70'-7" 2' - 6" 6' - 0" 1 2 99'-4" TO FTG 25' - 4" 25' - 4" B7 B8 41 S3.2 CC21 52 STEP BOT OF FTG 29' - 8" S3.4 20' - 0" B9 B10 99'-4" TO FTG CC21 CA FTG STEP 16' - 0"CC10 CC10 FF13 21 S3.5 HSS6x6x1/4 (TOS = 101'-4 1/2") CC21 CC5 FF13 14 S3.3 SIM (RE: ARCH) 2 16' - 0" 101'-4" TO FTG HSS6x6x1/4 (TOS = 101'-4 1/2") 2' - 0" 103'-4" TO FTG CC21 S3.3 15' - 4" BJ 1 98'-8" TO FTG 44 RE: 24/S2.1, TYP 5' - 0" PP1 97'-7" 70'-7" 7' - 6" 3' - 0" 2 BH STAIR STRINGER RE: LEVEL ABOVE (RE: 31/S5.4) 2 2' - 0" PP1 97'-7" 70'-7" FTG STEP FTG STEP SEE SHEET S1.2B FOR CONTINUATION CONTROL / CONSTRUCTION JT RE: TYPICAL DETAIL 15/S2.1 AND GENERAL NOTES, TYP. 1 5' - 0" 5' - 0" CC5 FF15 12 SUMP PIT RE: 11/S2.1 1 52 24' - 0" 7 CC5 FF13 98'-8" TO FTG MATCHLINE RE: S1.1B 12 S3.4 MATCHLINE RE: S1.1C B13 16' - 0" FF13 S1.1B 1 99'-4" TO FTG B13 1 98'-8" TO FTG B11 B12 KEY PLAN B 1 KEY NOTES: PLAN NOTES: A. FINISHED FLOOR ELEVATION = VARIES PER PLAN. 100'-0" EQUAL TO SURVEY ELEVATION = 1018.0'. B. SEE ARCHITECTURAL DRAWINGS FOR LOCATION OF SLOPED, RAISED, DEPRESSED SLABS AND DRAINS. C. D. E. F. REFER TO GENERAL NOTES SHEET S0.1 AND S0.2 FOR GENERAL NOTES, ABBREVIATIONS AND SYMBOLS. REFER TO SPECIFICATIONS FOR ALL SUBGRADE PREPARATION REQUIREMENTS. REFER TO ARCHITECTURAL DRAWINGS FOR OVERALL BUILDING GEOMETRY, WALL LOCATIONS, STAIR GEOMETRY AND ADDITIONAL PARTITION WALL REQUIREMENTS.AND ADDITIONAL PARTITION WALL REQUIREMENTS. REFER TO 52/S2.1 FOR COLUMN AND FOOTING SCHEDULES. G. H. J. K. L. REFER TO ARCHITECTURAL DRAWINGS FOR NON-LOAD BEARING PARTITION WALLS. REFER TO SHEETS S0.1, S0.2, S2.1, S2.2, AND S9.2 TYPICAL DETAILS FOR REINFORCING, THICKENED SLABS AND OTHER REQUIREMENTS. ALL CONCRETE BASEMENT WALLS HAVE BEEN DESIGNED AS CANTILEVERED, UNLESS OTHERWISE NOTED ON SECTIONS, NO TEMPORARY SHORING IS REQUIRED. BACKFILL WALLS PRIOR TO INSTALLING CONNECTING CONSTRUCTION. COORDINATE ALL PENETRATIONS THRU CONTINUOUS FOOTINGS WITH MEP DRAWINGS. REFERENCE TYPICAL DETAILS 34/S2.1 & 41/S2.1. ALL OPENINGS IN CMU WALLS REQUIRE A LINTEL. REFER TO SHEET S9.2 FOR TYPICAL MASONRY LINTEL DETAILS AND SCHEDULES. ALL EXTERIOR EXPOSED STEEL SHALL BE GALVANIZED. M. REFER TO ARCHITECTURAL DRAWINGS FOR PRECAST JOINT LOCATIONS. VERIFY JOINT LOCATIONS WITH PRECASTER. N. COORDINATE ALL FOOTING STEP LOCATIONS AND BRICK LEDGES WITH ARCHITECTURAL ELEVATIONS. C 4" NORMAL WEIGHT CONCRETE SLAB-ON-GRADE W/ 6x6-W2.1xW2.1 WELDED WIRE REINFORCEMENT ON 15 MIL VAPOR RETARDER OVER 4" GRANULAR FILL. 9 12" CMU WALL, SOLID GROUT WITH 2-#6 @ 2'-8"OC. 10 8" CMU WALL, SOLID GROUT WITH 1-#5 @ 3'-4"OC. 2 20"x20" CONCRETE PILASTER. RE: 31/S2.2 FOR REINFORCEMENT. 11 NOT USED. 3 20"x32" CONCRETE PILASTER. RE: 31/S2.2 FOR REINFORCEMENT. 12 16"x36" CMU PILASTER. RE: 31/S2.2 FOR REINFORCEMENT. 4 16"x16" CMU PILASTER. RE: 31/S2.2 FOR REINFORCEMENT. 5 16"x24" CMU PILASTER. RE: 31/S2.2 FOR REINFORCEMENT. 6 12" CMU WALL REINFORCE PER GENERAL NOTES, UNLESS NOTED OTHERWISE.. 7 8" CMU WALL REINFORCE PER GENERAL NOTES, UNLESS NOTED OTHERWISE. 1 D F P. ALL PRECAST CONNECTIONS SHALL BE DESIGNED BY THE PRECAST SUPPLIER. Q. ALL HSS MEMBERS SHALL HAVE 1/4" CAP PLATES AT ENDS. R. REFER TO 15/S2.2 FOR PIER SCHEDULE. S. DENOTES FEMA 361 SAFE ROOM AREA. REFER TO TYPICAL DETAILS (ON S4.3) AND GENERAL NOTES. 2 8 K E G L H 12" CMU WALL, SOLID GROUT WITH 2-#6 @ 1'-4"OC. FIRST LEVEL FOUNDATION PLAN - AREA B J SCALE: 1/8" = 1'-0" BENJAMIN TALPOS 10/8/2012 6:11:58 PM C:\Users\BrionP\Documents\9-2013-Revit Projects\Joplin\13-12102-00_central_struct_2012.rvt A NORTH NORTH © 2012, DLR Group of Missouri inc., a Missouri corporation CA No. 001614, ALL RIGHTS RESERVED. 1 PP1 97'-7" 72'-7" 2 10-08-12 ADD #3 BE PP1 99'-4" 74'-4" 7290 West 133rd Street Overland Park, Kansas 66213 tel: (913)897-7811 PP1 99'-4" 74'-4" Architecture Engineering Planning Interiors 2' - 6" PP1 97'-7" 70'-7" HSS10x6x3/8 (TOS = 108'-0 1/2") 99'-4" TO FTG 5' - 0" JOPLIN, JASPER COUNTY, MISSOURI 21 JOPLIN HIGH SCHOOL 98'-8" TO FTG 21 PP1 97'-7" 70'-7" 1 CC7 FF15 HSS8x6x3/8 (TOS = 108'-0 1/2") Revisions 1 2 1 10-04-12 ADD #2 2' - 6" 5' - 0" 3 2 PP1 97'-7" 70'-7" PP1 97'-1" 72'-7" 1 2 2 1 13-12102-00 09/10/12 2 9' - 8" 16' - 0" 1 2' - 6" FTG STEP BD 21 5' - 0" 2 5' - 0" 5' - 0" PP1 97'-7" 70'-7" 99'-4" TO FTG S3.5 S3.4 S3.3 5' - 0" 6' - 0" 103'-4" TO FTG 7' - 6" 5' - 0" S3.3 CC10 FF14 23 52 2' - 6" 52 BC STEP BOT OF FTG PP1 97'-7" 70'-7" PP1 97'-7" 70'-7" 3' - 0" FTG STEP SEE SHEET S1.2B FOR CONTINUATION 1 FIRST LEVEL FOUNDATION PLAN - AREA B 101'-4" TO FTG 2 PP1 97'-1" 70'-7" BJ 25' - 4" B7 2 SIM (RE: ARCH) CC21 CC21 STEP BOT OF FTG CC5 FF13 98'-8" TO FTG B10 16' - 0"CC10 12 B13 S3.4 16' - 0" 7' - 3" FF13 CC10 FF13 99'-4" TO FTG FTG STEP S3.4 20' - 0" B9 HSS6x6x1/4 (TOS = 101'-4 1/2") CC21 CC5 FF13 14 29' - 8" B8 HSS6x6x1/4 (TOS = 101'-4 1/2") 2 99'-4" TO FTG 25' - 4" 1 2' - 0" 2' - 6" 2 PP1 97'-7" 70'-7" 15' - 4" 1 PP1 97'-7" 70'-7" 5' - 0" 1 PP1 97'-7" 70'-7" RE: 24/S2.1, TYP 2' - 0" 2 B13 B14 CA 1 30' - 8" 98'-8" TO FTG FTG STEP FTG STEP SEE SHEET S1.2C FOR CONTINUATION 3' - 0" 52 2 2 PP1 1 97'-7" 70'-7" 101'-4" TO FTG CC10 FF13 98'-8" TO FTG 2 5' - 0" 2' - 6" CC 103'-4" TO FTG 99'-4" TO FTG S3.3 1 1 PP1 97'-7" 70'-7" 1 43 CC10 FF13 25 S3.5 41 S3.5 25 CD S3.5 99'-4" TO FTG 52 S3.6 99'-4" TO FTG S3.3 1 2 52 S3.4 99'-4" TO FTG 10' - 2 1/4" 99'-4" TO FTG S3.4 1 PP1 97'-7" 70'-7" PP1 97'-7" 70'-7" CC25 12' - 9 1/4" 45 5' - 0" 99'-4" TO FTG 2' - 0" CC21 12 99'-4" TO FTG 11' - 4" 2 5' - 0" 6' - 0" CC14 FF7 99'-4" TO FTG 1 99'-4" TO FTG PP1 99'-4" 74'-4" 17' - 7 3/4" 24' - 0" 52 22' - 9 7/8" 5' - 0" CL 99'-4" TO FTG 45 3 PP1 97'-7" 70'-7" 1 5' - 0" 2' - 6" 2 52 FTG STEP CC5 FF15 2 CC21 CC7 FF7 7 CC21 HSS6x6x1/4 (TOS = 101'-4 1/2") CC21 STAIR STRINGER RE: LEVEL ABOVE (RE: 31/S5.4) CONTROL / CONSTRUCTION JT RE: TYPICAL DETAIL 15/S2.1 AND GENERAL NOTES, TYP. 8' - 4 1/2" 5' - 0" CC5 FF7 SUMP PIT RE: 11/S2.1 1 2' - 6" S3.4 5' - 0" 3' - 0" 44 S3.3 1 CC14 FF16 2 CC14 FF15 CC21 CC5 FF13 1 41 HSS6x6x1/4 (TOS = 101'-4 1/2") CC21 2 S3.2 SIM (RE: ARCH) CC5 FF13 CC5 FF13 HSS6x6x1/4 (TOS = 101'-4 1/2") CC21 C10 20' - 0" C12 99'-4" TO FTG 16' - 0" 32 14 S3.3 S3.4 SIM 16' - 0" FTG STEP S3.4 S3.3 MATCHLINE RE: S1.1D 12 B12 B12 D10 C13 2 10-08-12 ADD #3 C9 29' - 8" 7290 West 133rd Street Overland Park, Kansas 66213 tel: (913)897-7811 C8 STEP BOT OF FTG Architecture Engineering Planning Interiors 53 25' - 4" MATCHLINE RE: S1.1C Revisions 99'-4" TO FTG CC21 CC21 98'-8" TO FTG 1 10-04-12 ADD #2 C7 25' - 4" PP1 97'-1" 70'-7" 13' - 8" S1.1C 29' - 8" PP1 97'-7" 70'-7" 13-12102-00 09/10/12 S3.3 101'-4" TO FTG 2' - 0" 6' - 0" 103'-4" TO FTG 45 99'-4" TO FTG CC21 HSS6x6x1/4 (TOS = 101'-4 1/2") 1 S3.4 2' - 6" CM 1 PP1 97'-7" 70'-7" 5' - 0" 99'-4" TO FTG 2' - 6" PP1 97'-7" 70'-7" 2 2' - 6" FTG STEP SEE SHEET S1.2C FOR CONTINUATION CC7 FF7 1 CC14 FF7 FTG STEP 1 CC7 FF7 99'-4" TO FTG CC14 FF7 PP1 97'-7" 70'-7" PP1 97'-7" 70'-7" S3.3 1 99'-4" TO FTG 9' - 9 1/2" 5' - 0" 1 CC7 FF7 96'-0" TO FTG 99'-4" TO FTG 2' - 6" FF5 MECH UNITS PER MECH, TYP 1 CC14 FF7 CK 1 CC14 FF7 1 1 PP1 97'-7" 70'-7" CC25 HSS6x6x1/4 (TOS = 101'-4 1/2") 2 RE: 24/S2.1, TYP PP1 97'-7" 70'-7" 98'-8" TO FTG CC6 FF15 S3.4 CC21 2' - 6" 1 FF6 CC21 99'-4" TO FTG 1 CJ S3.4 2' - 0" CH PP1 99'-4" 74'-4" 12 2' - 0" 1 PP1 97'-7" 70'-7" 1 1 HSS6x6x1/4 (TOS = 101'-4 1/2") JOPLIN, JASPER COUNTY, MISSOURI 5' - 0" 45 CC21 STEP BOT OF FTG 99'-4" TO FTG STEP BOT OF FTG 99'-4" TO FTG CC7 2 STEP BOT OF FTG 3 CC7 JOPLIN HIGH SCHOOL 2' - 6" S3.4 5' - 6" 2 FIRST LEVEL FOUNDATION PLAN - AREA C 24' - 4" PP1 97'-1" 70'-7" 2' - 6" PP1 97'-7" 70'-7" CC7 2' - 0" 1 45 2 CC6 FF14 CC21 2' - 0" 3 2 5' - 6" 3 PP1 97'-7" 70'-7" FF6 S3.4 2' - 0" 5' - 0" S3.3 1 PP1 97'-7" 70'-7" 2' - 6" 6' - 0" PP1 97'-7" 70'-7" 1 52 99'-4" TO FTG CF FTG STEP 1 5' - 6" S3.3 1 17' - 6" CE CC21 14 5' - 0" 2' - 6" 2 99'-4" TO FTG HSS6x6x1/4 (TOS = 101'-4 1/2") 16' - 0" 52 1 17' - 6" 2' - 0" 5' - 0" 1 FF6 5' - 0" 1 2' - 6" 15' - 4" 5' - 0" 2' - 6" 17' - 6" 18' - 8" S3.3 B11 B 1 KEY NOTES: PLAN NOTES: A. FINISHED FLOOR ELEVATION = VARIES PER PLAN. 100'-0" EQUAL TO SURVEY ELEVATION = 1018.0'. B. SEE ARCHITECTURAL DRAWINGS FOR LOCATION OF SLOPED, RAISED, DEPRESSED SLABS AND DRAINS. C. D. E. F. REFER TO GENERAL NOTES SHEET S0.1 AND S0.2 FOR GENERAL NOTES, ABBREVIATIONS AND SYMBOLS. REFER TO SPECIFICATIONS FOR ALL SUBGRADE PREPARATION REQUIREMENTS. REFER TO ARCHITECTURAL DRAWINGS FOR OVERALL BUILDING GEOMETRY, WALL LOCATIONS, STAIR GEOMETRY AND ADDITIONAL PARTITION WALL REQUIREMENTS.AND ADDITIONAL PARTITION WALL REQUIREMENTS. REFER TO 52/S2.1 FOR COLUMN AND FOOTING SCHEDULES. G. H. J. K. L. REFER TO ARCHITECTURAL DRAWINGS FOR NON-LOAD BEARING PARTITION WALLS. REFER TO SHEETS S0.1, S0.2, S2.1, S2.2, AND S9.2 TYPICAL DETAILS FOR REINFORCING, THICKENED SLABS AND OTHER REQUIREMENTS. ALL CONCRETE BASEMENT WALLS HAVE BEEN DESIGNED AS CANTILEVERED, UNLESS OTHERWISE NOTED ON SECTIONS, NO TEMPORARY SHORING IS REQUIRED. BACKFILL WALLS PRIOR TO INSTALLING CONNECTING CONSTRUCTION. COORDINATE ALL PENETRATIONS THRU CONTINUOUS FOOTINGS WITH MEP DRAWINGS. REFERENCE TYPICAL DETAILS 34/S2.1 & 41/S2.1. ALL OPENINGS IN CMU WALLS REQUIRE A LINTEL. REFER TO SHEET S9.2 FOR TYPICAL MASONRY LINTEL DETAILS AND SCHEDULES. ALL EXTERIOR EXPOSED STEEL SHALL BE GALVANIZED. M. REFER TO ARCHITECTURAL DRAWINGS FOR PRECAST JOINT LOCATIONS. VERIFY JOINT LOCATIONS WITH PRECASTER. N. COORDINATE ALL FOOTING STEP LOCATIONS AND BRICK LEDGES WITH ARCHITECTURAL ELEVATIONS. C 4" NORMAL WEIGHT CONCRETE SLAB-ON-GRADE W/ 6x6-W2.1xW2.1 WELDED WIRE REINFORCEMENT ON 15 MIL VAPOR RETARDER OVER 4" GRANULAR FILL. 9 12" CMU WALL, SOLID GROUT WITH 2-#6 @ 2'-8"OC. 10 8" CMU WALL, SOLID GROUT WITH 1-#5 @ 3'-4"OC. 2 20"x20" CONCRETE PILASTER. RE: 31/S2.2 FOR REINFORCEMENT. 11 NOT USED. 3 20"x32" CONCRETE PILASTER. RE: 31/S2.2 FOR REINFORCEMENT. 12 16"x36" CMU PILASTER. RE: 31/S2.2 FOR REINFORCEMENT. 4 16"x16" CMU PILASTER. RE: 31/S2.2 FOR REINFORCEMENT. 5 16"x24" CMU PILASTER. RE: 31/S2.2 FOR REINFORCEMENT. 6 12" CMU WALL REINFORCE PER GENERAL NOTES, UNLESS NOTED OTHERWISE.. 7 8" CMU WALL REINFORCE PER GENERAL NOTES, UNLESS NOTED OTHERWISE. 1 D F P. ALL PRECAST CONNECTIONS SHALL BE DESIGNED BY THE PRECAST SUPPLIER. Q. ALL HSS MEMBERS SHALL HAVE 1/4" CAP PLATES AT ENDS. R. REFER TO 15/S2.2 FOR PIER SCHEDULE. S. DENOTES FEMA 361 SAFE ROOM AREA. REFER TO TYPICAL DETAILS (ON S4.3) AND GENERAL NOTES. 2 8 K E G L H 12" CMU WALL, SOLID GROUT WITH 2-#6 @ 1'-4"OC. FIRST LEVEL FOUNDATION PLAN - AREA C J SCALE: 1/8" = 1'-0" BENJAMIN TALPOS 10/8/2012 6:12:04 PM C:\Users\BrionP\Documents\9-2013-Revit Projects\Joplin\13-12102-00_central_struct_2012.rvt A NORTH NORTH © 2012, DLR Group of Missouri inc., a Missouri corporation CA No. 001614, ALL RIGHTS RESERVED. KEY PLAN PP1 97'-7" 70'-7" 2 99'-4" TO FTG 1 PP1 97'-7" 70'-7" 1 45 5' - 0" CC14 FF16 S3.4 FTG STEP 30' - 0" PP1 97'-7" 70'-7" 29' - 8" 5' - 0" 2 101'-4" TO FTG C6 1 2' - 6" 103'-4" TO FTG CM 3 5' - 0" 3' - 0" 6' - 0" 2' - 6" PP1 97'-7" 70'-7" C7 53 C8 CC5 FF13 1 SIM (RE: ARCH) HSS6x6x1/4 (TOS = 101'-4 1/2") CC21 2 13' - 8" PP1 97'-1" 70'-7" 99'-4" TO FTG 25' - 4" CC14 FF15 25' - 4" STEP BOT OF FTG C9 C10 S3.3 CC5 FF13 CC21 29' - 8" 20' - 0" 15' - 4" CL 16' - 0" 99'-4" TO FTG C12 32 14 S3.3 S3.4 SIM CC5 FF13 CC21 2' - 0" FTG STEP SEE SHEET S1.2C FOR CONTINUATION CC21 98'-8" TO FTG 16' - 0" FTG STEP 12 S3.4 B12 CC10 FF18 CC10 FF17 B12 CC10 FF14 1 DA 98'-8" TO FTG 30' - 8" 98'-8" TO FTG 98'-8" TO FTG 98'-8" TO FTG 1 CC10 FF18 2 CC10 FF17 25 DB S3.6 1 1 CC5 CC6 FF14 S3.3 HSS8x6x3/8 (TOS = 108'-0 1/2") 3 21 S3.4 1 98'-8" TO FTG 1 99'-4" TO FTG CC14 FF7 99'-4" TO FTG 99'-4" TO FTG CC14 FF7 CC14 FF7 HSS10x6x3/8 (TOS = 108'-0 1/2") CC7 FF6 CC14 FF6 CC6 FF16 1 DE 11' - 4" 2 99'-4" TO FTG 99'-4" TO FTG 99'-4" TO FTG 1 1 CC14 FF7 CC14 FF8 1 1 96'-0" TO FTG CC14 FF7 CC5 FF6 CC16 FF6 6' - 0" DF HSS10x6x3/8 (TOS = 108'-0 1/2") MATCHLINE RE: S1.1D 99'-4" TO FTG MATCHLINE RE: S1.1F CC5 FF14 CC8 FF15 DG 2 99'-4" TO FTG 1 RE: 24/S2.1, TYP 1 1 FTG STEP 1 MECH UNITS PER MECH, TYP 5' - 0" 5' - 6" 3' - 0" 6' - 0" 1 DJ CC21 2 2 25' - 4" 25' - 4" D7 D8 S3.3 CC14 FF7 CC8 FF7 CC5 FF6 99'-4" TO FTG 2 2' - 0" FTG STEP SEE SHEET S1.2D FOR CONTINUATION 44 SUMP PIT RE: 11/S2.1 2 103'-4" TO FTG 2 CC21 99'-4" TO FTG 7 96'-0" TO FTG 3 FTG STEP DH 1 1 41 S3.6 101'-4" TO FTG S3.3 MATCHLINE RE: S1.1D MECH UNITS PER MECH, TYP 1 CC5 FF7 29' - 8" MATCHLINE RE: S1.1E CC14 FF16 D9 CC5 FF4 99'-4" TO FTG 36' - 0" 16' - 0" 99'-4" TO FTG D10 99'-4" TO FTG CC14 FF8 CC14 FF16 E10 D11 1 S1.1D 24' - 0" 6' - 0" 12 S3.4 99'-4" TO FTG 99'-4" TO FTG 19' - 0" 33 2' - 0" 2 99'-4" TO FTG 12' - 0" 99'-4" TO FTG B11 1 C13 CC8 FF6 CC7 FF4 1 KEY PLAN F1 B 1 KEY NOTES: PLAN NOTES: A. FINISHED FLOOR ELEVATION = VARIES PER PLAN. 100'-0" EQUAL TO SURVEY ELEVATION = 1018.0'. B. SEE ARCHITECTURAL DRAWINGS FOR LOCATION OF SLOPED, RAISED, DEPRESSED SLABS AND DRAINS. C. D. E. F. REFER TO GENERAL NOTES SHEET S0.1 AND S0.2 FOR GENERAL NOTES, ABBREVIATIONS AND SYMBOLS. REFER TO SPECIFICATIONS FOR ALL SUBGRADE PREPARATION REQUIREMENTS. REFER TO ARCHITECTURAL DRAWINGS FOR OVERALL BUILDING GEOMETRY, WALL LOCATIONS, STAIR GEOMETRY AND ADDITIONAL PARTITION WALL REQUIREMENTS.AND ADDITIONAL PARTITION WALL REQUIREMENTS. REFER TO 52/S2.1 FOR COLUMN AND FOOTING SCHEDULES. G. H. J. K. L. REFER TO ARCHITECTURAL DRAWINGS FOR NON-LOAD BEARING PARTITION WALLS. REFER TO SHEETS S0.1, S0.2, S2.1, S2.2, AND S9.2 TYPICAL DETAILS FOR REINFORCING, THICKENED SLABS AND OTHER REQUIREMENTS. ALL CONCRETE BASEMENT WALLS HAVE BEEN DESIGNED AS CANTILEVERED, UNLESS OTHERWISE NOTED ON SECTIONS, NO TEMPORARY SHORING IS REQUIRED. BACKFILL WALLS PRIOR TO INSTALLING CONNECTING CONSTRUCTION. COORDINATE ALL PENETRATIONS THRU CONTINUOUS FOOTINGS WITH MEP DRAWINGS. REFERENCE TYPICAL DETAILS 34/S2.1 & 41/S2.1. ALL OPENINGS IN CMU WALLS REQUIRE A LINTEL. REFER TO SHEET S9.2 FOR TYPICAL MASONRY LINTEL DETAILS AND SCHEDULES. ALL EXTERIOR EXPOSED STEEL SHALL BE GALVANIZED. M. REFER TO ARCHITECTURAL DRAWINGS FOR PRECAST JOINT LOCATIONS. VERIFY JOINT LOCATIONS WITH PRECASTER. N. COORDINATE ALL FOOTING STEP LOCATIONS AND BRICK LEDGES WITH ARCHITECTURAL ELEVATIONS. P. 2 ALL PRECAST CONNECTIONS SHALL BE DESIGNED BY THE PRECAST SUPPLIER. Q. ALL HSS MEMBERS SHALL HAVE 1/4" CAP PLATES AT ENDS. R. REFER TO 15/S2.2 FOR PIER SCHEDULE. S. DENOTES FEMA 361 SAFE ROOM AREA. REFER TO TYPICAL DETAILS (ON S4.3) AND GENERAL NOTES. C 4" NORMAL WEIGHT CONCRETE SLAB-ON-GRADE W/ 6x6-W2.1xW2.1 WELDED WIRE REINFORCEMENT ON 15 MIL VAPOR RETARDER OVER 4" GRANULAR FILL. 9 12" CMU WALL, SOLID GROUT WITH 2-#6 @ 2'-8"OC. 10 8" CMU WALL, SOLID GROUT WITH 1-#5 @ 3'-4"OC. 2 20"x20" CONCRETE PILASTER. RE: 31/S2.2 FOR REINFORCEMENT. 11 NOT USED. 3 20"x32" CONCRETE PILASTER. RE: 31/S2.2 FOR REINFORCEMENT. 12 16"x36" CMU PILASTER. RE: 31/S2.2 FOR REINFORCEMENT. 4 16"x16" CMU PILASTER. RE: 31/S2.2 FOR REINFORCEMENT. 5 16"x24" CMU PILASTER. RE: 31/S2.2 FOR REINFORCEMENT. 6 12" CMU WALL REINFORCE PER GENERAL NOTES, UNLESS NOTED OTHERWISE.. 7 8" CMU WALL REINFORCE PER GENERAL NOTES, UNLESS NOTED OTHERWISE. 1 8 D F K E G L H 12" CMU WALL, SOLID GROUT WITH 2-#6 @ 1'-4"OC. FIRST LEVEL FOUNDATION PLAN - AREA D J SCALE: 1/8" = 1'-0" BENJAMIN TALPOS 10/8/2012 6:12:10 PM C:\Users\BrionP\Documents\9-2013-Revit Projects\Joplin\13-12102-00_central_struct_2012.rvt A NORTH NORTH © 2012, DLR Group of Missouri inc., a Missouri corporation CA No. 001614, ALL RIGHTS RESERVED. 24' - 4" CONTROL / CONSTRUCTION JT RE: TYPICAL DETAIL 15/S2.1 AND GENERAL NOTES, TYP. 2 10-08-12 ADD #3 1 FIRST LEVEL FOUNDATION PLAN - AREA D 2 33 1 5' - 0" 5' - 0" 2 2 16' - 0" 2 1 5' - 6" DD 17' - 6" 6' - 0" 103'-4" TO FTG 101'-4" TO FTG 3' - 0" DC JOPLIN, JASPER COUNTY, MISSOURI CC14 FF15 7290 West 133rd Street Overland Park, Kansas 66213 tel: (913)897-7811 STEP BOT OF FTG FTG STEP CC14 FF15 CC14 FF15 Architecture Engineering Planning Interiors 99'-4" TO FTG S3.3 98'-8" TO FTG Revisions 32 1 10-04-12 ADD #2 16' - 0" 13-12102-00 09/10/12 FTG STEP SEE SHEET S1.2D FOR CONTINUATION JOPLIN HIGH SCHOOL 21 S3.6 15' - 4" S3.6 2' - 0" 99'-4" TO FTG 23 FTG STEP CC10 FF14 MECH UNITS PER MECH, TYP 1 2 DJ 2 2 25' - 4" 25' - 4" D8 99'-4" TO FTG MATCHLINE RE: S1.1D MECH UNITS PER MECH, TYP 1 CC5 FF7 29' - 8" MATCHLINE RE: S1.1E CC5 FF4 99'-4" TO FTG 36' - 0" CC14 FF16 D9 20' - 8" D7 CC5 FF6 2 2' - 0" FTG STEP SEE SHEET S1.2D FOR CONTINUATION CC14 FF7 16' - 0" 99'-4" TO FTG D10 99'-4" TO FTG 1 99'-4" TO FTG CC14 FF8 CC14 FF16 B11 CC7 FF4 1 EA 1 99'-4" TO FTG 19' - 9 1/2" 2 99'-4" TO FTG STAIR STRINGER RE: LEVEL ABOVE (RE: 31/S5.4) CC7 FF8 CC14 FF16 1 1 EB SIM (RE: ARCH) CONTROL / CONSTRUCTION JT RE: TYPICAL DETAIL 15/S2.1 AND GENERAL NOTES, TYP. 1 CC14 FF6 2' - 0" MATCHLINE RE: S1.1E 1 CC14 FF7 99'-4" TO FTG CC14 FF6 99'-4" TO FTG CC14 FF7 CC14 FF6 1 CC6 FF7 99'-4" TO FTG EF 1 11' - 4" 2 99'-4" TO FTG 99'-4" TO FTG CC14 FF8 1 7 CC14 FF8 6' - 0" EG 96'-0" TO FTG 1 24 1 7 STAIR STRINGER RE: LEVEL ABOVE (RE: 31/S5.4) 2 EH 99'-4" TO FTG 1 S3.3 44 S3.3 1 7 CC16 FF6 35' - 9 3/16" 24' - 0" 96'-0" TO FTG Structural Framing 2 SUMP PIT RE: 11/S2.1 FTG STEP 97'-4" TO FTG FTG STEP 1 RE: 24/S2.1, TYP 101'-4" TO FTG 2 1 2 6' - 0" 3' - 0" 6' - 0" 103'-4" TO FTG MECH UNITS PER MECH, TYP 1 2 1 STEP BOT OF FTG 5' - 0" EK 99'-4" TO FTG 2 99'-4" TO FTG 41 SIM (RE: ARCH) S3.2 24 S3.3 15 99'-4" TO FTG S3.3 STEP BOT OF FTG STEP BOT OF FTG 1 7 PP1 97'-7" 70'-7" FTG STEP E8 29' - 8" E9 E10 20' - 0" 2' - 6" 25' - 4" MATCHLINE RE: S1.1G FTG STEP SEE SHEET S1.2E FOR CONTINUATION MATCHLINE RE: S1.1E EL PP1 97'-1" 77'-7" 99'-4" TO FTG E11 G1 PP1 97'-7" 16' - 0" 77'-7" 99'-4" TO FTG PP1 97'-7" 16' - 0" 77'-7" 46 S3.4 EJ 99'-4" TO FTG 1 2' - 6" 41 1 7 6' - 0" 7 1 1 S3.6 7 S1.1E 22' - 5" 2 6' - 0" 2 C13 2 RE: 24/S2.1, TYP MECH UNITS PER MECH, TYP E12 D11 2 10-08-12 ADD #3 12' - 3" 6' - 0" 99'-4" TO FTG 7290 West 133rd Street Overland Park, Kansas 66213 tel: (913)897-7811 99'-4" TO FTG 19' - 0" 99'-4" TO FTG Architecture Engineering Planning Interiors 24' - 4" S3.5 Revisions 21 JOPLIN, JASPER COUNTY, MISSOURI 99'-4" TO FTG 1 10-04-12 ADD #2 2 99'-4" TO FTG 12' - 3" 2 1 99'-4" TO FTG 99'-4" TO FTG 13-12102-00 09/10/12 103'-4" TO FTG 101'-4" TO FTG 5' - 0" ED JOPLIN HIGH SCHOOL 1 FIRST LEVEL FOUNDATION PLAN - AREA E 2 5' - 0" CC5 FF7 CC14 FF6 MATCHLINE RE: S1.1F 16' - 0" 3' - 0" FTG STEP 6' - 0" EC CC7 FF4 99'-4" TO FTG CC14 FF6 S3.2 1 20' - 10 1/2" 99'-4" TO FTG FTG STEP SEE SHEET S1.2E FOR CONTINUATION 99'-4" TO FTG 41 G2 B 1 KEY NOTES: PLAN NOTES: A. FINISHED FLOOR ELEVATION = VARIES PER PLAN. 100'-0" EQUAL TO SURVEY ELEVATION = 1018.0'. B. SEE ARCHITECTURAL DRAWINGS FOR LOCATION OF SLOPED, RAISED, DEPRESSED SLABS AND DRAINS. C. D. E. F. REFER TO GENERAL NOTES SHEET S0.1 AND S0.2 FOR GENERAL NOTES, ABBREVIATIONS AND SYMBOLS. REFER TO SPECIFICATIONS FOR ALL SUBGRADE PREPARATION REQUIREMENTS. REFER TO ARCHITECTURAL DRAWINGS FOR OVERALL BUILDING GEOMETRY, WALL LOCATIONS, STAIR GEOMETRY AND ADDITIONAL PARTITION WALL REQUIREMENTS.AND ADDITIONAL PARTITION WALL REQUIREMENTS. REFER TO 52/S2.1 FOR COLUMN AND FOOTING SCHEDULES. G. H. J. K. L. REFER TO ARCHITECTURAL DRAWINGS FOR NON-LOAD BEARING PARTITION WALLS. REFER TO SHEETS S0.1, S0.2, S2.1, S2.2, AND S9.2 TYPICAL DETAILS FOR REINFORCING, THICKENED SLABS AND OTHER REQUIREMENTS. ALL CONCRETE BASEMENT WALLS HAVE BEEN DESIGNED AS CANTILEVERED, UNLESS OTHERWISE NOTED ON SECTIONS, NO TEMPORARY SHORING IS REQUIRED. BACKFILL WALLS PRIOR TO INSTALLING CONNECTING CONSTRUCTION. COORDINATE ALL PENETRATIONS THRU CONTINUOUS FOOTINGS WITH MEP DRAWINGS. REFERENCE TYPICAL DETAILS 34/S2.1 & 41/S2.1. ALL OPENINGS IN CMU WALLS REQUIRE A LINTEL. REFER TO SHEET S9.2 FOR TYPICAL MASONRY LINTEL DETAILS AND SCHEDULES. ALL EXTERIOR EXPOSED STEEL SHALL BE GALVANIZED. M. REFER TO ARCHITECTURAL DRAWINGS FOR PRECAST JOINT LOCATIONS. VERIFY JOINT LOCATIONS WITH PRECASTER. N. COORDINATE ALL FOOTING STEP LOCATIONS AND BRICK LEDGES WITH ARCHITECTURAL ELEVATIONS. P. ALL PRECAST CONNECTIONS SHALL BE DESIGNED BY THE PRECAST SUPPLIER. Q. ALL HSS MEMBERS SHALL HAVE 1/4" CAP PLATES AT ENDS. R. REFER TO 15/S2.2 FOR PIER SCHEDULE. S. DENOTES FEMA 361 SAFE ROOM AREA. REFER TO TYPICAL DETAILS (ON S4.3) AND GENERAL NOTES. 2 C 4" NORMAL WEIGHT CONCRETE SLAB-ON-GRADE W/ 6x6-W2.1xW2.1 WELDED WIRE REINFORCEMENT ON 15 MIL VAPOR RETARDER OVER 4" GRANULAR FILL. 9 12" CMU WALL, SOLID GROUT WITH 2-#6 @ 2'-8"OC. 10 8" CMU WALL, SOLID GROUT WITH 1-#5 @ 3'-4"OC. 2 20"x20" CONCRETE PILASTER. RE: 31/S2.2 FOR REINFORCEMENT. 11 NOT USED. 3 20"x32" CONCRETE PILASTER. RE: 31/S2.2 FOR REINFORCEMENT. 12 16"x36" CMU PILASTER. RE: 31/S2.2 FOR REINFORCEMENT. 4 16"x16" CMU PILASTER. RE: 31/S2.2 FOR REINFORCEMENT. 5 16"x24" CMU PILASTER. RE: 31/S2.2 FOR REINFORCEMENT. 6 12" CMU WALL REINFORCE PER GENERAL NOTES, UNLESS NOTED OTHERWISE.. 7 8" CMU WALL REINFORCE PER GENERAL NOTES, UNLESS NOTED OTHERWISE. 1 8 D F K E G L H 12" CMU WALL, SOLID GROUT WITH 2-#6 @ 1'-4"OC. FIRST LEVEL FOUNDATION PLAN - AREA E J SCALE: 1/8" = 1'-0" BENJAMIN TALPOS 10/8/2012 6:12:16 PM C:\Users\BrionP\Documents\9-2013-Revit Projects\Joplin\13-12102-00_central_struct_2012.rvt A NORTH NORTH © 2012, DLR Group of Missouri inc., a Missouri corporation CA No. 001614, ALL RIGHTS RESERVED. KEY PLAN CC6 FF16 PLAN NOTES: DE MATCHLINE RE: S1.1F CC8 FF15 C. REFER TO GENERAL NOTES SHEET S0.1 AND S0.2 FOR GENERAL NOTES, ABBREVIATIONS AND SYMBOLS. CC10 FF12 D. REFER TO SPECIFICATIONS FOR ALL SUBGRADE PREPARATION REQUIREMENTS. E. REFER TO ARCHITECTURAL DRAWINGS FOR OVERALL BUILDING GEOMETRY, WALL LOCATIONS, STAIR GEOMETRY AND ADDITIONAL PARTITION WALL REQUIREMENTS.AND ADDITIONAL PARTITION WALL REQUIREMENTS. F. REFER TO 52/S2.1 FOR COLUMN AND FOOTING SCHEDULES. G. REFER TO ARCHITECTURAL DRAWINGS FOR NON-LOAD BEARING PARTITION WALLS. REFER TO SHEETS S0.1, S0.2, S2.1, S2.2, AND S9.2 TYPICAL DETAILS FOR REINFORCING, THICKENED SLABS AND OTHER REQUIREMENTS. H. ALL CONCRETE BASEMENT WALLS HAVE BEEN DESIGNED AS CANTILEVERED, UNLESS OTHERWISE NOTED ON SECTIONS, NO TEMPORARY SHORING IS REQUIRED. BACKFILL WALLS PRIOR TO INSTALLING CONNECTING CONSTRUCTION. CC17 FF16 J. COORDINATE ALL PENETRATIONS THRU CONTINUOUS FOOTINGS WITH MEP DRAWINGS. REFERENCE TYPICAL DETAILS 34/S2.1 & 41/S2.1. 1 K. ALL OPENINGS IN CMU WALLS REQUIRE A LINTEL. REFER TO SHEET S9.2 FOR TYPICAL MASONRY LINTEL DETAILS AND SCHEDULES. L. ALL EXTERIOR EXPOSED STEEL SHALL BE GALVANIZED. M. REFER TO ARCHITECTURAL DRAWINGS FOR PRECAST JOINT LOCATIONS. VERIFY JOINT LOCATIONS WITH PRECASTER. N. COORDINATE ALL FOOTING STEP LOCATIONS AND BRICK LEDGES WITH ARCHITECTURAL ELEVATIONS. P. ALL PRECAST CONNECTIONS SHALL BE DESIGNED BY THE PRECAST SUPPLIER. Q. ALL HSS MEMBERS SHALL HAVE 1/4" CAP PLATES AT ENDS. R. REFER TO 15/S2.2 FOR PIER SCHEDULE. S. DENOTES FEMA 361 SAFE ROOM AREA. REFER TO TYPICAL DETAILS (ON S4.3) AND GENERAL NOTES. CC14 FF12 10" 12 S3.4 HSS6x6x1/4 (TOS = 102'-0 1/2") 98'-8" TO FTG CC8 FF13 CC10 FF12 2 CC21 S3.6 F3 98'-8" TO FTG CC8 FF13 F4 2 KC KD CC21 HSS6x6x1/4 (TOS = 102'-0 1/2") CC21 1 24' - 0" 99'-4" TO FTG S3.3 1 1 DJ 10 23 KB 98'-8" TO FTG 98'-8" TO FTG CC8 FF7 CC10 FF12 25 FA CC21 98'-8" TO FTG 1' - 6" 2' - 0" HSS6x6x1/4 (TOS = 102'-0 1/2") 1 98'-8" TO FTG 14' - 6" CC21 CC8 FF6 98'-8" TO FTG 98'-8" TO FTG CC21 DH SEE ARCHITECTURAL DRAWINGS FOR LOCATION OF SLOPED, RAISED, DEPRESSED SLABS AND DRAINS. KA D12 CC21 B. 10' - 0" S3.4 FINISHED FLOOR ELEVATION = VARIES PER PLAN. 100'-0" EQUAL TO SURVEY ELEVATION = 1018.0'. 2' - 7" S3.3 A. 15' - 4" 16' - 0" 33 CC10 FF12 CC8 FF11 98'-8" TO FTG 12 33' - 1 5/8" 10' - 0" DG 98'-8" TO FTG 1 2' - 0" DF 15' - 4" MATCHLINE RE: S1.1K 37' - 4" MATCHLINE RE: S1.1F HSS10x6x3/8 (TOS = 108'-0 1/2") MATCHLINE RE: S1.1D 1 1 98'-8" TO FTG CC21 CC17 FF16 CC8 FF13 1 2 1 2 CC21 EA KE 2 20"x20" CONCRETE PILASTER. RE: 31/S2.2 FOR REINFORCEMENT. 3 20"x32" CONCRETE PILASTER. RE: 31/S2.2 FOR REINFORCEMENT. 4 16"x16" CMU PILASTER. RE: 31/S2.2 FOR REINFORCEMENT. 5 16"x24" CMU PILASTER. RE: 31/S2.2 FOR REINFORCEMENT. 6 12" CMU WALL REINFORCE PER GENERAL NOTES, UNLESS NOTED OTHERWISE. 7 8" CMU WALL REINFORCE PER GENERAL NOTES, UNLESS NOTED OTHERWISE. 8 12" CMU WALL, SOLID GROUT WITH 2-#6 @ 1'-4"OC. 9 12" CMU WALL, SOLID GROUT WITH 2-#6 @ 2'-8"OC. 10 8" CMU WALL, SOLID GROUT WITH 1-#5 @ 3'-4"OC. 11 NOT USED 12 16"x36" CMU PILASTER. RE: 31/S2.2 FOR REINFORCEMENT. 99'-4" TO FTG 98'-8" TO FTG CC8 FF13 1 CC17 FF17 1 EB 12 KF S3.4 HSS6x6x1/4 (TOS = 102'-0 1/2") CC21 98'-8" TO FTG CC8 FF14 1 24' - 0" 10 CC21 1 1 3 CC21 KG HSS6x6x1/4 (TOS = 102'-0 1/2") 98'-8" TO FTG 12 S3.3 S3.4 HSS6x6x1/4 (TOS = 102'-0 1/2") CC8 FF7 1 35 S8.5 CC18 FF18 12 S3.4 CC21 CC8 FF13 1 1 3 EF KH 21 S3.4 7 MATCHLINE RE: S1.1G HSS8x6x3/8 (TOS = 108'-0 1/2") 21 CC6 FF5 KJ S3.4 KK CC5 FF12 EJ 23 S3.3 1 12 CC21 S3.4 CC5 FF10 CC5 FF14 CC12 FF6 HSS6x6x1/4 (TOS = 102'-0 1/2") 1 97'-4" TO FTG A 21 S3.4 CC17 FF15 HSS8x6x3/8 (TOS = 108'-0 1/2") EL 2 1 B 12 99'-4" TO FTG S3.4 98'-8" TO FTG 37' - 4" HSS6x6x1/4 (TOS = 102'-0 1/2") F1 F2 KL SIM STEP BOT OF FTG 23 S3.3 C K1 D F K2 K E G L H FIRST LEVEL FOUNDATION PLAN - AREA F J SCALE: 1/8" = 1'-0" BENJAMIN TALPOS 10/8/2012 6:12:22 PM C:\Users\BrionP\Documents\9-2013-Revit Projects\Joplin\13-12102-00_central_struct_2012.rvt KEY PLAN 10 26' - 0" 99'-4" TO FTG EK 1 2 2' - 7" STEP BOT OF FTG 14' - 5" 6' - 0" 7 CC18 FF18 2' - 0" EH S1.1F EG MATCHLINE RE: S1.1F 99'-4" TO FTG 1 24' - 0" 99'-4" TO FTG 98'-8" TO FTG NORTH NORTH © 2012, DLR Group of Missouri inc., a Missouri corporation CA No. 001614, ALL RIGHTS RESERVED. 99'-4" TO FTG 33 2' - 0" CC21 2 24' - 0" 2' - 0" 2 10-08-12 ADD #3 CC21 MATCHLINE RE: S1.1F MATCHLINE RE: S1.1E 99'-4" TO FTG 7290 West 133rd Street Overland Park, Kansas 66213 tel: (913)897-7811 ED CC17 FF17 Architecture Engineering Planning Interiors EC Revisions CC8 FF7 1 10-04-12 ADD #2 CC21 99'-4" TO FTG 1 2 CC21 13-12102-00 09/10/12 CC8 FF6 97'-4" TO FTG 24' - 0" 1 JOPLIN, JASPER COUNTY, MISSOURI 4" NORMAL WEIGHT CONCRETE SLAB-ON-GRADE W/ 6x6-W2.1xW2.1 WELDED WIRE REINFORCEMENT ON 15 MIL VAPOR RETARDER OVER 4" GRANULAR FILL. JOPLIN HIGH SCHOOL 1 FIRST LEVEL FOUNDATION PLAN - AREA F KEY NOTES: 96'-0" TO FTG Structural Framing 2 RE: 24/S2.1, TYP S3.6 S3.6 MECH UNITS PER MECH, TYP 1 3' - 0" 6' - 0" 2 99'-4" TO FTG 1 2 1 STEP BOT OF FTG 5' - 0" 2 103'-4" TO FTG 41 99'-4" TO FTG 101'-4" TO FTG 7 99'-4" TO FTG SIM (RE: ARCH) E8 S3.3 15 99'-4" TO FTG CC5 FF10 CC5 FF14 S3.3 1 STEP BOT OF FTG CC12 FF6 STEP BOT OF FTG HSS6x6x1/4 (TOS = 102'-0 1/2") 21 S3.4 7 PP1 97'-7" 70'-7" HSS8x6x3/8 (TOS = 108'-0 1/2") 12 2' - 6" E10 E9 CC21 S3.4 20' - 0" PP1 97'-1" 77'-7" 99'-4" TO FTG E11 PP1 97'-7" 16' - 0" 77'-7" 99'-4" TO FTG PP1 97'-7" 16' - 0" 77'-7" 46 S3.4 C13 RE: 24/S2.1, TYP 2 MECH UNITS PER MECH, TYP PP1 97'-7" 77'-7" CC21 37' - 4" 98'-8" TO FTG HSS6x6x1/4 (TOS = 102'-0 1/2") CC12 FF6 2 2 2' - 6" CC5 FF13 21 99'-4" TO FTG 5' - 0" S3.4 1 20' - 0" 1 S3.4 28' - 0" PP1 97'-7" 77'-7" 1 GA 99'-4" TO FTG 18' - 0 3/8" FTG STEP 29' - 8" MATCHLINE RE: S1.1G FTG STEP SEE SHEET E7 S1.2E FOR CONTINUATION 25' - 4" 20' - 0" E6 25' - 4" MATCHLINE RE: S1.1E 19' - 0" E5 29' - 8" 12 1 24 EL 30' - 0" CC5 FF12 99'-4" TO FTG 1 2' - 6" 2 1 6' - 0" 7 1 1 41 EK 7 FTG STEP 97'-4" TO FTG FTG STEP 1 CC6 FF5 CC12 FF6 1 1 PP1 97'-7" 77'-7" PP1 97'-7" 77'-7" CC5 FF14 HSS8x6x3/8 (TOS = 108'-0 1/2") GB 2 1 CC5 FF10 1 CC5 FF14 HSS8x6x3/8 (TOS = 108'-0 1/2") GC 2 2 1 S3.4 98'-8" TO FTG 1 99'-4" TO FTG 20' - 4" 21 CC5 FF10 99'-4" TO FTG CC21 12 S3.4 HSS6x6x1/4 (TOS = 102'-0 1/2") CC12 FF4 PP1 97'-7" 77'-7" CC5 FF13 12 CC5 FF11 HSS6x6x1/4 (TOS = 102'-0 1/2") S3.4 2' - 0" PP1 97'-7" 77'-7" CC21 GD 2 2' - 6" 33 1 S5.2 PP1 97'-7" 77'-7" PP1 97'-7" 77'-7" 2' - 0" 45 98'-8" TO FTG 1 S3.4 CC21 PP1 97'-7" 77'-7" 98'-8" TO FTG 25 99'-4" TO FTG 7 MATCHLINE RE: S1.1G MATCHLINE RE: S1.1H 2' - 0" S3.3 3' - 0" 14' - 0 3/16" PP1 97'-7" 77'-7" HSS6x6x1/4 (TOS = 102'-0 1/2") 5' - 0" MATCHLINE RE: S1.1H PP1 97'-7" 77'-7" 2' - 6" PP1 97'-1" 77'-7" CC21 12 S3.4 MATCHLINE RE: S1.1G 98'-8" TO FTG 12 CC21 99'-4" TO FTG 30' - 2 5/8" STEP BOT OF FTG 1 CC21 S3.4 14' - 0 3/16" 5' - 0" 1 99'-4" TO FTG 2 HA STEP BOT OF FTG 7 18' - 2 1/2" G1 99'-4" TO FTG 46 16' - 0" E12 S3.4 17' - 1 1/2" 99'-4" TO FTG 7 STEP BOT OF FTG 26' - 10 1/2" 20' - 9" 16' - 7" STEP BOT OF FTG 21 23' - 4" 1 D11 1 F1 S3.4 CC5 FF10 G3 HSS8x6x3/8 (TOS = 108'-0 1/2") F2 H9 S1.1G G2 2 10-08-12 ADD #3 1 JOPLIN, JASPER COUNTY, MISSOURI HSS6x6x1/4 (TOS = 102'-0 1/2") 7290 West 133rd Street Overland Park, Kansas 66213 tel: (913)897-7811 PP1 97'-7" 77'-7" Architecture Engineering Planning Interiors CC12 FF7 S3.4 JOPLIN HIGH SCHOOL PP1 97'-7" 77'-7" 12 CC21 Revisions CONTROL / CONSTRUCTION JT RE: TYPICAL DETAIL 15/S2.1 AND GENERAL NOTES, TYP. 1 10-04-12 ADD #2 20' - 0" 1 13-12102-00 09/10/12 1 99'-4" TO FTG FIRST LEVEL FOUNDATION PLAN - AREA G 2 B 1 KEY NOTES: PLAN NOTES: A. FINISHED FLOOR ELEVATION = VARIES PER PLAN. 100'-0" EQUAL TO SURVEY ELEVATION = 1018.0'. B. SEE ARCHITECTURAL DRAWINGS FOR LOCATION OF SLOPED, RAISED, DEPRESSED SLABS AND DRAINS. C. D. E. F. REFER TO GENERAL NOTES SHEET S0.1 AND S0.2 FOR GENERAL NOTES, ABBREVIATIONS AND SYMBOLS. REFER TO SPECIFICATIONS FOR ALL SUBGRADE PREPARATION REQUIREMENTS. REFER TO ARCHITECTURAL DRAWINGS FOR OVERALL BUILDING GEOMETRY, WALL LOCATIONS, STAIR GEOMETRY AND ADDITIONAL PARTITION WALL REQUIREMENTS.AND ADDITIONAL PARTITION WALL REQUIREMENTS. REFER TO 52/S2.1 FOR COLUMN AND FOOTING SCHEDULES. G. H. J. K. L. REFER TO ARCHITECTURAL DRAWINGS FOR NON-LOAD BEARING PARTITION WALLS. REFER TO SHEETS S0.1, S0.2, S2.1, S2.2, AND S9.2 TYPICAL DETAILS FOR REINFORCING, THICKENED SLABS AND OTHER REQUIREMENTS. ALL CONCRETE BASEMENT WALLS HAVE BEEN DESIGNED AS CANTILEVERED, UNLESS OTHERWISE NOTED ON SECTIONS, NO TEMPORARY SHORING IS REQUIRED. BACKFILL WALLS PRIOR TO INSTALLING CONNECTING CONSTRUCTION. COORDINATE ALL PENETRATIONS THRU CONTINUOUS FOOTINGS WITH MEP DRAWINGS. REFERENCE TYPICAL DETAILS 34/S2.1 & 41/S2.1. ALL OPENINGS IN CMU WALLS REQUIRE A LINTEL. REFER TO SHEET S9.2 FOR TYPICAL MASONRY LINTEL DETAILS AND SCHEDULES. ALL EXTERIOR EXPOSED STEEL SHALL BE GALVANIZED. M. REFER TO ARCHITECTURAL DRAWINGS FOR PRECAST JOINT LOCATIONS. VERIFY JOINT LOCATIONS WITH PRECASTER. N. COORDINATE ALL FOOTING STEP LOCATIONS AND BRICK LEDGES WITH ARCHITECTURAL ELEVATIONS. P. ALL PRECAST CONNECTIONS SHALL BE DESIGNED BY THE PRECAST SUPPLIER. Q. ALL HSS MEMBERS SHALL HAVE 1/4" CAP PLATES AT ENDS. R. REFER TO 15/S2.2 FOR PIER SCHEDULE. S. DENOTES FEMA 361 SAFE ROOM AREA. REFER TO TYPICAL DETAILS (ON S4.3) AND GENERAL NOTES. 2 C 4" NORMAL WEIGHT CONCRETE SLAB-ON-GRADE W/ 6x6-W2.1xW2.1 WELDED WIRE REINFORCEMENT ON 15 MIL VAPOR RETARDER OVER 4" GRANULAR FILL. 9 12" CMU WALL, SOLID GROUT WITH 2-#6 @ 2'-8"OC. 10 8" CMU WALL, SOLID GROUT WITH 1-#5 @ 3'-4"OC. 2 20"x20" CONCRETE PILASTER. RE: 31/S2.2 FOR REINFORCEMENT. 11 NOT USED. 3 20"x32" CONCRETE PILASTER. RE: 31/S2.2 FOR REINFORCEMENT. 12 16"x36" CMU PILASTER. RE: 31/S2.2 FOR REINFORCEMENT. 4 16"x16" CMU PILASTER. RE: 31/S2.2 FOR REINFORCEMENT. 5 16"x24" CMU PILASTER. RE: 31/S2.2 FOR REINFORCEMENT. 6 12" CMU WALL REINFORCE PER GENERAL NOTES, UNLESS NOTED OTHERWISE.. 7 8" CMU WALL REINFORCE PER GENERAL NOTES, UNLESS NOTED OTHERWISE. 1 8 D F K E G L H 12" CMU WALL, SOLID GROUT WITH 2-#6 @ 1'-4"OC. FIRST LEVEL FOUNDATION PLAN - AREA G J SCALE: 1/8" = 1'-0" BENJAMIN TALPOS 10/8/2012 6:12:29 PM C:\Users\BrionP\Documents\9-2013-Revit Projects\Joplin\13-12102-00_central_struct_2012.rvt A NORTH NORTH © 2012, DLR Group of Missouri inc., a Missouri corporation CA No. 001614, ALL RIGHTS RESERVED. KEY PLAN S3.4 CC21 PP1 97'-7" 77'-7" 98'-8" TO FTG 25 3' - 0" S3.3 99'-4" TO FTG 7 MATCHLINE RE: S1.1G MATCHLINE RE: S1.1H 5' - 0" MATCHLINE RE: S1.1H PP1 97'-7" 77'-7" 2' - 0" PP1 97'-7" 77'-7" 2' - 6" PP1 97'-1" 77'-7" MATCHLINE RE: S1.1G HA 6' - 0" 18' - 2 1/2" G1 19' - 5 3/8" 99'-4" TO FTG 46 16' - 0" S3.4 E12 17' - 1 1/2" 1 99'-4" TO FTG 7 STEP BOT OF FTG 26' - 10 1/2" 16' - 7" STEP BOT OF FTG 20' - 9" 21 23' - 4" F1 G3 S3.4 CC5 FF10 1 D11 1 HSS8x6x3/8 (TOS = 108'-0 1/2") F2 2 1 FF12 1 STEP BOT OF FTG 7 1 MECH UNITS PER MECH, TYP CC12 FF3 2 1 FF3 RE: 24/S2.1, TYP, UNO HB FF3 CC12 FF2 1 98'-8" TO FTG CC5 FF11 CC12 FF2 12 5 99'-4" TO FTG 99'-4" TO FTG 1 99'-4" TO FTG 5 G2 20' - 0" 6 24' - 0" 99'-4" TO FTG 99'-4" TO FTG 3' - 0" 1 11 1 S3.3 11 S3.3 RE: 24/S2.2 6 3' - 0" S3.6 RE: 24/S2.2 7 RE: 24/S2.2 2' - 0" 2' - 0" 14 S3.3 S3.4 S3.3 16 S3.3 S3.3 CC5 FF12 CC12 FF3 3' - 0" 2' - 0" 21 3' - 0" 3' - 0" 19' - 0" STEP BOT OF FTG 99'-4" TO FTG 21 14 3' - 0" 3' - 0" 11 CC5 FF10 1 2 6 HSS6x6x1/4 (TOS = 102'-0 1/2") CC21 19' - 10 3/8" 1 S3.3 CC5 FF11 7 HC 41 S3.4 CC21 HSS6x6x1/4 (TOS = 102'-0 1/2") 1 110' - 8" 99'-4" TO FTG 5 HSS8x6x3/8 (TOS = 108'-0 1/2") 3' - 0" 99'-4" TO FTG 8 3' - 0" 1 S3.3 1 33 H7 S3.3 3' - 0" 3' - 0" 99'-4" TO FTG 1 20' - 0" 9 99'-4" TO FTG 1 CC14 FF6 6 FF4 CC12 FF5 1 FF4 CC12 FF4 99'-4" TO FTG FF4 7 F CC5 FF13 99'-4" TO FTG 7 1 1 5 1 1 12 1 12 12 5' - 0" 1 16' - 0" 21 99'-4" TO FTG S3.5 7 99'-4" TO FTG CONTROL / CONSTRUCTION JT RE: TYPICAL DETAIL 15/S2.1 AND GENERAL NOTES, TYP. 1 1 20' - 0" 2' - 0" 14 S3.3 PP2 96'-10" 73'-10" STEP BOT OF FTG 1 1 1 PP2 96'-10" 73'-10" STEP BOT OF FTG CC5 FF10 HG 6 1 1 12 3' - 0" HSS6x6x1/4 (TOS = 102'-0 1/2") S3.4 15 S3.5 S3.3 8 1 STEP BOT OF FTG 1 8 STEP BOT OF FTG 3' - 0" PP2 96'-10" 73'-10" STEP BOT OF FTG PP2 96'-10" 73'-10" PP2 96'-10" 71'-10" PP2 96'-10" 71'-10" 8 1 36 S3.3 STEP BOT OF FTG CC2 99'-4" TO FTG 41 S3.3 CC5 FF13 CC5 FF10 28' - 10" H2 46' - 8" CC5 33 S3.3 2' - 0" H4 3' - 0" 98'-8" TO FTG 99'-4" TO FTG PP2 96'-10" 71'-10" 1 CC5 FF11 1 CC5 FF10 KEY PLAN CC21 HSS6x6x1/4 (TOS = 102'-0 1/2") MATCHLINE RE: S1.1H MATCHLINE RE: S1.1J 12 S3.4 44' - 4 1/4" CC21 2' - 0" HL 33 98'-8" TO FTG A 10' - 4 1/4" S3.3 H5 H8 CC21 H9 2' - 0" B H6 1 KEY NOTES: PLAN NOTES: A. FINISHED FLOOR ELEVATION = VARIES PER PLAN. 100'-0" EQUAL TO SURVEY ELEVATION = 1018.0'. B. SEE ARCHITECTURAL DRAWINGS FOR LOCATION OF SLOPED, RAISED, DEPRESSED SLABS AND DRAINS. C. D. E. F. REFER TO GENERAL NOTES SHEET S0.1 AND S0.2 FOR GENERAL NOTES, ABBREVIATIONS AND SYMBOLS. REFER TO SPECIFICATIONS FOR ALL SUBGRADE PREPARATION REQUIREMENTS. REFER TO ARCHITECTURAL DRAWINGS FOR OVERALL BUILDING GEOMETRY, WALL LOCATIONS, STAIR GEOMETRY AND ADDITIONAL PARTITION WALL REQUIREMENTS.AND ADDITIONAL PARTITION WALL REQUIREMENTS. REFER TO 52/S2.1 FOR COLUMN AND FOOTING SCHEDULES. G. H. J. K. L. REFER TO ARCHITECTURAL DRAWINGS FOR NON-LOAD BEARING PARTITION WALLS. REFER TO SHEETS S0.1, S0.2, S2.1, S2.2, AND S9.2 TYPICAL DETAILS FOR REINFORCING, THICKENED SLABS AND OTHER REQUIREMENTS. ALL CONCRETE BASEMENT WALLS HAVE BEEN DESIGNED AS CANTILEVERED, UNLESS OTHERWISE NOTED ON SECTIONS, NO TEMPORARY SHORING IS REQUIRED. BACKFILL WALLS PRIOR TO INSTALLING CONNECTING CONSTRUCTION. COORDINATE ALL PENETRATIONS THRU CONTINUOUS FOOTINGS WITH MEP DRAWINGS. REFERENCE TYPICAL DETAILS 34/S2.1 & 41/S2.1. ALL OPENINGS IN CMU WALLS REQUIRE A LINTEL. REFER TO SHEET S9.2 FOR TYPICAL MASONRY LINTEL DETAILS AND SCHEDULES. ALL EXTERIOR EXPOSED STEEL SHALL BE GALVANIZED. M. REFER TO ARCHITECTURAL DRAWINGS FOR PRECAST JOINT LOCATIONS. VERIFY JOINT LOCATIONS WITH PRECASTER. N. COORDINATE ALL FOOTING STEP LOCATIONS AND BRICK LEDGES WITH ARCHITECTURAL ELEVATIONS. C 4" NORMAL WEIGHT CONCRETE SLAB-ON-GRADE W/ 6x6-W2.1xW2.1 WELDED WIRE REINFORCEMENT ON 15 MIL VAPOR RETARDER OVER 4" GRANULAR FILL. 9 12" CMU WALL, SOLID GROUT WITH 2-#6 @ 2'-8"OC. 10 8" CMU WALL, SOLID GROUT WITH 1-#5 @ 3'-4"OC. 2 20"x20" CONCRETE PILASTER. RE: 31/S2.2 FOR REINFORCEMENT. 11 NOT USED. 3 20"x32" CONCRETE PILASTER. RE: 31/S2.2 FOR REINFORCEMENT. 12 16"x36" CMU PILASTER. RE: 31/S2.2 FOR REINFORCEMENT. 4 16"x16" CMU PILASTER. RE: 31/S2.2 FOR REINFORCEMENT. 5 16"x24" CMU PILASTER. RE: 31/S2.2 FOR REINFORCEMENT. 6 12" CMU WALL REINFORCE PER GENERAL NOTES, UNLESS NOTED OTHERWISE.. 7 8" CMU WALL REINFORCE PER GENERAL NOTES, UNLESS NOTED OTHERWISE. 1 D F P. ALL PRECAST CONNECTIONS SHALL BE DESIGNED BY THE PRECAST SUPPLIER. Q. ALL HSS MEMBERS SHALL HAVE 1/4" CAP PLATES AT ENDS. R. REFER TO 15/S2.2 FOR PIER SCHEDULE. S. DENOTES FEMA 361 SAFE ROOM AREA. REFER TO TYPICAL DETAILS (ON S4.3) AND GENERAL NOTES. 2 8 K E G L H 12" CMU WALL, SOLID GROUT WITH 2-#6 @ 1'-4"OC. FIRST LEVEL FOUNDATION PLAN - AREA H J SCALE: 1/8" = 1'-0" NORTH BENJAMIN TALPOS 10/8/2012 6:12:35 PM C:\Users\BrionP\Documents\9-2013-Revit Projects\Joplin\13-12102-00_central_struct_2012.rvt 98'-8" TO FTG S3.4 20' - 10" TRENCH FOOTINGS 2'-8" WIDE x 3'-0" DEEP, TYP H3 CC21 12 CC5 105' - 4" H1 3' - 0" 3' - 0" S3.3 99'-4" TO FTG 1 PP2 96'-10" 71'-10" HH HJ HK 11 HSS6x6x1/4 (TOS = 102'-0 1/2") CC21 STEP BOT OF FTG 8 23' - 8" 23' - 5 1/2" 1 23' - 8" 98'-8" TO FTG S3.3 S1.1H 25 1' - 1 13/16" 1' - 1 1/4" 2' - 6" 36 1' - 3 3/4" 15 S3.3 CC21 3' - 0" 1 2' - 0" 99'-4" TO FTG PP2 96'-10" 73'-10" S3.3 3' - 0" 9' - 8" 1 3' - 0" 5' - 0" 36 27' - 0 5/8" 7 2' - 6" NORTH © 2012, DLR Group of Missouri inc., a Missouri corporation CA No. 001614, ALL RIGHTS RESERVED. 3' - 0" HE JOPLIN, JASPER COUNTY, MISSOURI 16 S3.3 2 10-08-12 ADD #3 1 16 S3.3 7290 West 133rd Street Overland Park, Kansas 66213 tel: (913)897-7811 S3.3 6' - 0" 98'-8" TO FTG CC5 FF10 16 Architecture Engineering Planning Interiors 1 JOPLIN HIGH SCHOOL 1 1 Revisions 7 16' - 11 3/4" 1 10-04-12 ADD #2 7 7 S3.3 13-12102-00 09/10/12 14 FIRST LEVEL FOUNDATION PLAN - AREA H 20' - 1 5/8" S3.3 99'-4" TO FTG 3' - 0" 14 14 1 8 2' - 0" STEP BOT OF FTG 2' - 0" 99'-4" TO FTG 2' - 0" 99'-4" TO FTG 8 STEP BOT OF FTG 3' - 0" 6' - 0" HD PLAN NOTES: 1 A. FINISHED FLOOR ELEVATION = VARIES PER PLAN. 100'-0" EQUAL TO SURVEY ELEVATION = 1018.0'. B. SEE ARCHITECTURAL DRAWINGS FOR LOCATION OF SLOPED, RAISED, DEPRESSED SLABS AND DRAINS. C. REFER TO GENERAL NOTES SHEET S0.1 AND S0.2 FOR GENERAL NOTES, ABBREVIATIONS AND SYMBOLS. D. REFER TO SPECIFICATIONS FOR ALL SUBGRADE PREPARATION REQUIREMENTS. E. REFER TO ARCHITECTURAL DRAWINGS FOR OVERALL BUILDING GEOMETRY, WALL LOCATIONS, STAIR GEOMETRY AND ADDITIONAL PARTITION WALL REQUIREMENTS.AND ADDITIONAL PARTITION WALL REQUIREMENTS. F. REFER TO 52/S2.1 FOR COLUMN AND FOOTING SCHEDULES. G. REFER TO ARCHITECTURAL DRAWINGS FOR NON-LOAD BEARING PARTITION WALLS. REFER TO SHEETS S0.1, S0.2, S2.1, S2.2, AND S9.2 TYPICAL DETAILS FOR REINFORCING, THICKENED SLABS AND OTHER REQUIREMENTS. H. ALL CONCRETE BASEMENT WALLS HAVE BEEN DESIGNED AS CANTILEVERED, UNLESS OTHERWISE NOTED ON SECTIONS, NO TEMPORARY SHORING IS REQUIRED. BACKFILL WALLS PRIOR TO INSTALLING CONNECTING CONSTRUCTION. J. COORDINATE ALL PENETRATIONS THRU CONTINUOUS FOOTINGS WITH MEP DRAWINGS. REFERENCE TYPICAL DETAILS 34/S2.1 & 41/S2.1. K. ALL OPENINGS IN CMU WALLS REQUIRE A LINTEL. REFER TO SHEET S9.2 FOR TYPICAL MASONRY LINTEL DETAILS AND SCHEDULES. L. ALL EXTERIOR EXPOSED STEEL SHALL BE GALVANIZED. M. REFER TO ARCHITECTURAL DRAWINGS FOR PRECAST JOINT LOCATIONS. VERIFY JOINT LOCATIONS WITH PRECASTER. N. COORDINATE ALL FOOTING STEP LOCATIONS AND BRICK LEDGES WITH ARCHITECTURAL ELEVATIONS. P. ALL PRECAST CONNECTIONS SHALL BE DESIGNED BY THE PRECAST SUPPLIER. Q. ALL HSS MEMBERS SHALL HAVE 1/4" CAP PLATES AT ENDS. R. REFER TO 15/S2.2 FOR PIER SCHEDULE. S. DENOTES FEMA 361 SAFE ROOM AREA. REFER TO TYPICAL DETAILS (ON S4.3) AND GENERAL NOTES. CC21 98'-8" TO FTG S3.4 44' - 4 1/4" H5 H8 CC21 HSS6x6x1/4 (TOS = 102'-0 1/2") 2' - 0" CC21 HSS6x6x1/4 (TOS = 102'-0 1/2") CC21 PP2 96'-10" 73'-10" 33 2' - 0" 1 41 S3.3 1 S3.4 8 3' - 0" 98'-8" TO FTG 12 1 H9 S3.3 JA CC21 12 STEP BOT OF FTG CC2 FF10 CC5 FF12 S3.4 HSS6x6x1/4 (TOS = 102'-0 1/2") 2' - 0" CC21 172' - 11 5/8" 28' - 3" 3' - 0" HSS6x6x1/4 (TOS = 102'-0 1/2") 11 11 S3.3 CC2 FF10 CC5 FF12 S3.3 CC21 STEP BOT OF FTG 8 1 STEP BOT OF FTG 16 16 1 7 99'-4" TO FTG 3' - 0" 3' - 0" HSS6x6x1/4 (TOS = 102'-0 1/2") 172' - 11 5/8" 18' - 8" S3.3 CC2 FF10 CC5 FF12 14 7 1 1 CC12 FF5 S3.4 HSS6x6x1/4 (TOS = 102'-0 1/2") 1 2' - 0" 33 9 CC21 CONTROL / CONSTRUCTION JT RE: TYPICAL DETAIL 15/S2.1 AND GENERAL NOTES, TYP. 12 8" CMU WALL REINFORCE PER GENERAL NOTES, UNLESS NOTED OTHERWISE. 8 12" CMU WALL, SOLID GROUT WITH 2-#6 @ 1'-4"OC. 9 12" CMU WALL, SOLID GROUT WITH 2-#6 @ 2'-8"OC. 10 8" CMU WALL, SOLID GROUT WITH 1-#5 @ 3'-4"OC. 11 NOT USED 12 16"x36" CMU PILASTER. RE: 31/S2.2 FOR REINFORCEMENT. CC5 FF11 CC5 FF13 7 33 S3.3 2' - 0" 3' - 0" 98'-8" TO FTG 1 14 14 7 2' - 0" S3.3 38' - 6" S3.3 1 99'-4" TO FTG S3.3 14 S3.3 16 12 S3.3 3' - 0" 1 1 CC21 1 8 STEP BOT OF FTG S3.3 CC5 FF11 CC5 FF11 S3.3 JF M1 HSS6x6x1/4 (TOS = 102'-0 1/2") CC21 M3 M4 M2 STEP BOT OF FTG JG S3.3 SIM 12 S3.4 54 CC21 FTG STEP S3.3 2' - 0" 51 1' - 6" S3.3 99'-4" TO FTG 32 CC5 FF11 S3.3 CC5 FF11 24' - 0" 1' - 6" 10' - 1 1/2" J1 54 CC5 FF10 2' - 0" S3.3 99'-4" TO FTG 1' - 6" 11 3' - 0" 9' - 4" 99'-4" TO FTG 3' - 0" MA 32 S3.3 24' - 0" 2' - 0" 16' - 4 5/8" JH J5 7' - 11 1/2" H6 FF1 15' - 7 7/8" J6 1 KEY PLAN J7 A FF1 1' - 6" S3.3 1 99'-4" TO FTG CC21 2' - 0" CC5 FF11 2' - 0" CC5 FF10 HSS6x6x1/4 (TOS = 102'-0 1/2") JJ 99'-4" TO FTG 51 B S3.3 1 MATCHLINE RE: S1.1J 14 CC5 FF10 S3.4 24' - 0" 20' - 6 1/2" 99'-4" TO FTG HSS6x6x1/4 (TOS = 102'-0 1/2") C MATCHLINE RE: S1.1M 51 D S3.3 99'-4" 32 TO FTG S3.3 26' - 2 5/8" J2 CC21 14 K S3.4 FF1 24' - 3 3/8" J3 F CC21 E FF1 G MC L J4 99'-4" TO FTG H 1' - 6" FIRST LEVEL FOUNDATION PLAN - AREA J J SCALE: 1/8" = 1'-0" BENJAMIN TALPOS 10/8/2012 6:12:41 PM C:\Users\BrionP\Documents\9-2013-Revit Projects\Joplin\13-12102-00_central_struct_2012.rvt MB 32 NORTH NORTH © 2012, DLR Group of Missouri inc., a Missouri corporation CA No. 001614, ALL RIGHTS RESERVED. 8 99'-4" TO FTG CC5 FF11 16 2 10-08-12 ADD #3 3' - 0" 2' - 0" 99'-4" TO FTG S3.4 7290 West 133rd Street Overland Park, Kansas 66213 tel: (913)897-7811 2' - 0" 14 Architecture Engineering Planning Interiors 1 2' - 0" 11 7 JE 1 2' - 0" 99'-4" TO FTG 12" CMU WALL REINFORCE PER GENERAL NOTES, UNLESS NOTED OTHERWISE. 98'-8" TO FTG S3.3 1 3' - 0" 6 22' - 1 1/2" 98'-8" TO FTG CC21 HSS6x6x1/4 (TOS = 102'-0 1/2") 1 FF5 7 16"x24" CMU PILASTER. RE: 31/S2.2 FOR REINFORCEMENT. 12 CC21 99'-4" TO FTG 1 99'-4" TO FTG 5 Revisions CC12 FF5 2' - 0" 21' - 4" 99'-4" TO FTG 2' - 0" 5 16"x16" CMU PILASTER. RE: 31/S2.2 FOR REINFORCEMENT. 2' - 0" 1 21' - 10 1/8" HSS6x6x1/4 (TOS = 102'-0 1/2") 6 14 JD 4 CC21 CC21 1 FF14 20"x32" CONCRETE PILASTER. RE: 31/S2.2 FOR REINFORCEMENT. S3.3 2' - 0" 8 3 33 99'-4" TO FTG S3.3 20"x20" CONCRETE PILASTER. RE: 31/S2.2 FOR REINFORCEMENT. 98'-8" TO FTG 2' - 0" 1 2 HSS6x6x1/4 (TOS = 102'-0 1/2") CC21 S3.3 S3.3 JC 4" NORMAL WEIGHT CONCRETE SLAB-ON-GRADE W/ 6x6-W2.1xW2.1 WELDED WIRE REINFORCEMENT ON 15 MIL VAPOR RETARDER OVER 4" GRANULAR FILL. 28' - 11" 7 1 99'-4" TO FTG 1 1 KEY NOTES: 1 10-04-12 ADD #2 STEP BOT OF FTG CC21 STEP BOT OF FTG 13-12102-00 09/10/12 8 99'-4" TO FTG S1.1J 3' - 0" JB 99'-4" TO FTG 2 JOPLIN, JASPER COUNTY, MISSOURI CC21 10' - 4 1/4" JOPLIN HIGH SCHOOL MATCHLINE RE: S1.1J 12 FIRST LEVEL FOUNDATION PLAN - AREA J HSS6x6x1/4 (TOS = 102'-0 1/2") MATCHLINE RE: S1.1H 42' - 0 3/8" 12' - 10" 23' - 6" 24' - 0" 24' - 0" 24' - 0" 24' - 0" 24' - 0" 26' - 4" PLAN NOTES: S3.3 CC14 FF12 1 FINISHED FLOOR ELEVATION = VARIES PER PLAN. 100'-0" EQUAL TO SURVEY ELEVATION = 1018.0'. B. SEE ARCHITECTURAL DRAWINGS FOR LOCATION OF SLOPED, RAISED, DEPRESSED SLABS AND DRAINS. C. REFER TO GENERAL NOTES SHEET S0.1 AND S0.2 FOR GENERAL NOTES, ABBREVIATIONS AND SYMBOLS. CC17 FF14 2' - 0" 97'-4" TO FTG D. REFER TO SPECIFICATIONS FOR ALL SUBGRADE PREPARATION REQUIREMENTS. CC18 FF16 1 12 STAIR STRINGER RE: LEVEL ABOVE (RE: 24/S5.5) 1 1 2 CC18 FF13 CC18 FF16 1 S8.5 E. REFER TO ARCHITECTURAL DRAWINGS FOR OVERALL BUILDING GEOMETRY, WALL LOCATIONS, STAIR GEOMETRY AND ADDITIONAL PARTITION WALL REQUIREMENTS.AND ADDITIONAL PARTITION WALL REQUIREMENTS. F. REFER TO 52/S2.1 FOR COLUMN AND FOOTING SCHEDULES. G. REFER TO ARCHITECTURAL DRAWINGS FOR NON-LOAD BEARING PARTITION WALLS. REFER TO SHEETS S0.1, S0.2, S2.1, S2.2, AND S9.2 TYPICAL DETAILS FOR REINFORCING, THICKENED SLABS AND OTHER REQUIREMENTS. H. ALL CONCRETE BASEMENT WALLS HAVE BEEN DESIGNED AS CANTILEVERED, UNLESS OTHERWISE NOTED ON SECTIONS, NO TEMPORARY SHORING IS REQUIRED. BACKFILL WALLS PRIOR TO INSTALLING CONNECTING CONSTRUCTION. J. COORDINATE ALL PENETRATIONS THRU CONTINUOUS FOOTINGS WITH MEP DRAWINGS. REFERENCE TYPICAL DETAILS 34/S2.1 & 41/S2.1. K. ALL OPENINGS IN CMU WALLS REQUIRE A LINTEL. REFER TO SHEET S9.2 FOR TYPICAL MASONRY LINTEL DETAILS AND SCHEDULES. L. ALL EXTERIOR EXPOSED STEEL SHALL BE GALVANIZED. M. REFER TO ARCHITECTURAL DRAWINGS FOR PRECAST JOINT LOCATIONS. VERIFY JOINT LOCATIONS WITH PRECASTER. N. COORDINATE ALL FOOTING STEP LOCATIONS AND BRICK LEDGES WITH ARCHITECTURAL ELEVATIONS. P. ALL PRECAST CONNECTIONS SHALL BE DESIGNED BY THE PRECAST SUPPLIER. Q. ALL HSS MEMBERS SHALL HAVE 1/4" CAP PLATES AT ENDS. R. REFER TO 15/S2.2 FOR PIER SCHEDULE. S. DENOTES FEMA 361 SAFE ROOM AREA. REFER TO TYPICAL DETAILS (ON S4.3) AND GENERAL NOTES. S3.3 CC26 FF2 S8.4 35 97'-4" TO FTG 95'-4" TO FTG KB CC17 FF3 94'-0" TO FTG CC11 FF5 CC11 FF5 CC11 FF5 CC11 FF5 CC11 FF5 2' - 7" CC11 FF4 CC18 FF14 97'-4" TO FTG CC11 FF4 1 2 7 53 1 97'-4" TO FTG 97'-4" TO FTG 97'-4" TO FTG 97'-4" TO FTG S8.3 44 1 S3.3 CC11 FF5 1 CC17 FF16 97'-4" TO FTG CC19 FF9 CC11 FF4 1 2 CC17 FF14 KE 2 RK2 RK1 1 97'-4" TO FTG 31 24' - 0" 97'-4" TO FTG CC19 FF19 CC11 FF5 4" NORMAL WEIGHT CONCRETE SLAB-ON-GRADE W/ 6x6-W2.1xW2.1 WELDED WIRE REINFORCEMENT ON 15 MIL VAPOR RETARDER OVER 4" GRANULAR FILL. 2 20"x20" CONCRETE PILASTER. RE: 31/S2.2 FOR REINFORCEMENT. 3 20"x32" CONCRETE PILASTER. RE: 31/S2.2 FOR REINFORCEMENT. 4 16"x16" CMU PILASTER. RE: 31/S2.2 FOR REINFORCEMENT. 5 16"x24" CMU PILASTER. RE: 31/S2.2 FOR REINFORCEMENT. 6 12" CMU WALL REINFORCE PER GENERAL NOTES, UNLESS NOTED OTHERWISE. 7 8" CMU WALL REINFORCE PER GENERAL NOTES, UNLESS NOTED OTHERWISE. 8 12" CMU WALL, SOLID GROUT WITH 2-#6 @ 1'-4"OC. 9 12" CMU WALL, SOLID GROUT WITH 2-#6 @ 2'-8"OC. 10 8" CMU WALL, SOLID GROUT WITH 1-#5 @ 3'-4"OC. 11 NOT USED 12 16"x36" CMU PILASTER. RE: 31/S2.2 FOR REINFORCEMENT. CC17 FF14 1 2 1 CONTROL / CONSTRUCTION JT RE: TYPICAL DETAIL 15/S2.1 AND GENERAL NOTES, TYP. 1 CC17 FF17 KEY NOTES: 1 S8.6 KF 1 97'-4" TO FTG 97'-4" TO FTG 24' - 0" S8.4 10 45 10 1 1 CC17 FF17 CC19 FF19 CC11 FF5 1 CC17 FF14 1 3 KG 97'-4" TO FTG 1 2 97'-4" TO FTG 1 24' - 0" 33 35 S8.6 S8.5 1 CC18 FF18 CC19 FF19 RK4 RK3 CC11 FF4 1 3 CC17 FF14 KH CC11 FF5 97'-4" TO FTG 24' - 0" 97'-4" TO FTG CC18 FF18 2' - 0" CC11 FF5 CC11 FF3 CC19 FF19 1 CC11 FF5 CC11 FF5 96'-4" TO FTG CC11 FF5 S8.4 CC11 FF4 CC11 FF5 55 STAIR STRINGER RE: LEVEL ABOVE (RE: 15/S5.5) 23 S3.3 10 26' - 0" 97'-4" TO FTG 97'-4" TO FTG 97'-4" TO FTG 97'-4" TO FTG 2 RE: 16/S2.2 1 STEP BOT OF FTG 23 S3.3 97'-4" TO FTG S3.4 24' - 8" 5' - 0" 2' - 6" PP1 95'-1" 75'-7" 53 8' - 8 1/2" MATCHLINE RE: S1.1K MATCHLINE RE: S1.1L PP1 95'-7" 75'-7" 1 10 97'-4" TO FTG PP1 95'-7" 5' - 0" 75'-7" 97'-4" TO FTG 2' - 6" 97'-4" TO FTG CC14 FF8 97'-4" TO FTG 97'-4" TO FTG CC14 FF7 97'-4" TO FTG CC14 FF8 1 A 6' - 8 5/8" B 97'-4" TO FTG K10 CC14 FF7 97'-4" TO FTG 45 21' - 0 3/16" C S3.4 1 5' - 0" CC13 FF7 51 2' - 6" PP1 95'-7" 75'-7" LA CC17 FF8 CC26 FF2 S3.3 KM CC18 FF8 STEP BOT OF FTG K1 1 CC18 FF8 5' - 9 5/8" SIM CC18 FF8 KEY PLAN CC17 FF15 1 1 45 KL CC17 FF6 CC17 FF9 2' - 0" 2 CC17 FF8 CC17 FF9 33 5' - 6" CC17 FF15 97'-4" TO FTG S8.4 STAIR STRINGER RE: LEVEL ABOVE (RE: 24/S5.5) PP1 95'-7" 73'-7" 97'-4" TO FTG CC11 FF3 S8.5 2' - 0" 53 1 97'-4" TO FTG 97'-4" TO FTG MATCHLINE RE: S1.1K 97'-4" TO FTG S8.5 D MATCHLINE RE: S1.1L 10 F K E G L H K3 K4 L1 K5 K6 K7 L2 K8 K9 K11 K12 FIRST LEVEL FOUNDATION PLAN - AREA K J SCALE: 1/8" = 1'-0" BENJAMIN TALPOS 10/8/2012 6:12:48 PM K2 NORTH NORTH © 2012, DLR Group of Missouri inc., a Missouri corporation CA No. 001614, ALL RIGHTS RESERVED. 1 97'-4" TO FTG C:\Users\BrionP\Documents\9-2013-Revit Projects\Joplin\13-12102-00_central_struct_2012.rvt 97'-4" TO FTG S1.1K 97'-4" TO FTG 1 2' - 0" KK CC18 FF14 1 2 2' - 7" KJ JOPLIN, JASPER COUNTY, MISSOURI 24' - 0" SUMP PIT RE: 11/S2.1 97'-4" TO FTG 2 10-08-12 ADD #3 KD 7290 West 133rd Street Overland Park, Kansas 66213 tel: (913)897-7811 10' - 0" 10' - 0" STAIR STRINGER RE: LEVEL ABOVE (RE: 15/S5.5) 1 2 KC 1 CC17 FF16 Architecture Engineering Planning Interiors FA 1 CC17 FF16 JOPLIN HIGH SCHOOL 1' - 6" 1 CC17 FF14 CC17 FF16 Revisions S3.3 CC18 FF16 S8.5 6' - 8 5/8" 1 10-04-12 ADD #2 10 23 CC18 FF16 31 10 5' - 6" CC17 FF12 13-12102-00 09/10/12 16' - 0" CC10 FF12 33 97'-4" TO FTG 14' - 6" 98'-8" TO FTG F4 A. 10" KA 98'-8" TO FTG 97'-4" TO FTG 12 2' - 0" DG CC10 FF12 MATCHLINE RE: S1.1K 98'-8" TO FTG MATCHLINE RE: S1.1F 2' - 3" FIRST LEVEL FOUNDATION PLAN - AREA K 15' - 4" 45 53 S3.4 S3.3 8' - 8 1/2" MATCHLINE RE: S1.1K MATCHLINE RE: S1.1L 1 5' - 0" PP1 95'-7" 75'-7" LA CC13 FF7 51 2' - 6" PP1 95'-7" 73'-7" 97'-4" TO FTG CC11 FF3 S8.5 MATCHLINE RE: S1.1K 2' - 0" 53 1 97'-4" TO FTG 97'-4" TO FTG S8.5 97'-4" TO FTG MATCHLINE RE: S1.1L 10 2' - 0" KM 1 2 2 15' - 0" 1 CC13 FF7 1 5' - 0" 97'-4" TO FTG 97'-4" TO FTG 13 2' - 6" 30' - 0" PP1 95'-7" 75'-7" CC17 FF14 22 PP1 95'-7" 73'-7" 2' - 0" S3.3 S3.3 15' - 0" 97'-4" TO FTG 97'-4" TO FTG 1 LB 97'-4" TO FTG PP1 95'-7" 75'-7" PP1 95'-7" 75'-7" 2 2 1 CC11 FF5 CC14 FF6 1 CONTROL / CONSTRUCTION JT RE: TYPICAL DETAIL 15/S2.1 AND GENERAL NOTES, TYP. 1 13 1 97'-4" TO FTG CC18 FF13 9 1 24' - 0" 51 97'-4" TO FTG PP1 95'-7" 75'-7" PP1 95'-7" 75'-7" 2 2 S8.3 S3.3 1 2' - 0" 35 S8.6 CC11 FF4 1 S8.4 CC14 FF5 31 CC18 FF13 LC 97'-4" TO FTG 1 2' - 6" 1 10 1 CC13 FF5 CC17 FF13 2 18' - 4 3/4" 97'-4" TO FTG 1 S3.3 10 97'-4" TO FTG 2' - 0" 1 97'-4" TO FTG 41 1 97'-4" TO FTG S8.3 CC11 FF3 14 S3.3 2' - 0" 26' - 8" 1 STEP BOT OF FTG 56 LE 23 CC18 FF16 S3.3 2 CC17 FF12 1 CC17 FF13 1 2' - 0" STAIR STRINGER RE: LEVEL ABOVE (RE: 15/S5.5) 22 1 S8.3 CC18 FF12 1 10 1 S3.3 STEP BOT OF FTG CC18 FF12 CC17 FF13 CC18 FF12 1 10 55 S8.3 CC18 FF12 CC17 FF11 43 12 97'-4" TO FTG S3.3 11' - 8" 42' - 0 3/8" K3 23' - 6" K4 L1 S3.3 4' - 2" 24' - 0" K5 24' - 0" K6 19' - 10" K7 28' - 2" L2 13 K8 24' - 0" 26' - 4" K9 K11 K12 S1.1L K2 12' - 10" 2' - 0" 2' - 0" LF JOPLIN, JASPER COUNTY, MISSOURI LD CC11 FF4 2 10-08-12 ADD #3 5' - 0" 2 PP1 95'-7" 75'-7" 2' - 6" 1 97'-4" TO FTG 7290 West 133rd Street Overland Park, Kansas 66213 tel: (913)897-7811 PP1 95'-7" 75'-7" Architecture Engineering Planning Interiors 21' - 0 3/16" PP1 95'-7" 75'-7" JOPLIN HIGH SCHOOL S3.3 Revisions 1 53 S3.4 1 10-04-12 ADD #2 1 56 13-12102-00 09/10/12 FIRST LEVEL FOUNDATION PLAN - AREA L 24' - 0" 5' - 0" B 1 KEY NOTES: PLAN NOTES: A. FINISHED FLOOR ELEVATION = VARIES PER PLAN. 100'-0" EQUAL TO SURVEY ELEVATION = 1018.0'. B. SEE ARCHITECTURAL DRAWINGS FOR LOCATION OF SLOPED, RAISED, DEPRESSED SLABS AND DRAINS. C. D. E. F. REFER TO GENERAL NOTES SHEET S0.1 AND S0.2 FOR GENERAL NOTES, ABBREVIATIONS AND SYMBOLS. REFER TO SPECIFICATIONS FOR ALL SUBGRADE PREPARATION REQUIREMENTS. REFER TO ARCHITECTURAL DRAWINGS FOR OVERALL BUILDING GEOMETRY, WALL LOCATIONS, STAIR GEOMETRY AND ADDITIONAL PARTITION WALL REQUIREMENTS.AND ADDITIONAL PARTITION WALL REQUIREMENTS. REFER TO 52/S2.1 FOR COLUMN AND FOOTING SCHEDULES. G. H. J. K. L. REFER TO ARCHITECTURAL DRAWINGS FOR NON-LOAD BEARING PARTITION WALLS. REFER TO SHEETS S0.1, S0.2, S2.1, S2.2, AND S9.2 TYPICAL DETAILS FOR REINFORCING, THICKENED SLABS AND OTHER REQUIREMENTS. ALL CONCRETE BASEMENT WALLS HAVE BEEN DESIGNED AS CANTILEVERED, UNLESS OTHERWISE NOTED ON SECTIONS, NO TEMPORARY SHORING IS REQUIRED. BACKFILL WALLS PRIOR TO INSTALLING CONNECTING CONSTRUCTION. COORDINATE ALL PENETRATIONS THRU CONTINUOUS FOOTINGS WITH MEP DRAWINGS. REFERENCE TYPICAL DETAILS 34/S2.1 & 41/S2.1. ALL OPENINGS IN CMU WALLS REQUIRE A LINTEL. REFER TO SHEET S9.2 FOR TYPICAL MASONRY LINTEL DETAILS AND SCHEDULES. ALL EXTERIOR EXPOSED STEEL SHALL BE GALVANIZED. M. REFER TO ARCHITECTURAL DRAWINGS FOR PRECAST JOINT LOCATIONS. VERIFY JOINT LOCATIONS WITH PRECASTER. N. COORDINATE ALL FOOTING STEP LOCATIONS AND BRICK LEDGES WITH ARCHITECTURAL ELEVATIONS. P. ALL PRECAST CONNECTIONS SHALL BE DESIGNED BY THE PRECAST SUPPLIER. Q. ALL HSS MEMBERS SHALL HAVE 1/4" CAP PLATES AT ENDS. R. REFER TO 15/S2.2 FOR PIER SCHEDULE. S. DENOTES FEMA 361 SAFE ROOM AREA. REFER TO TYPICAL DETAILS (ON S4.3) AND GENERAL NOTES. 2 C 4" NORMAL WEIGHT CONCRETE SLAB-ON-GRADE W/ 6x6-W2.1xW2.1 WELDED WIRE REINFORCEMENT ON 15 MIL VAPOR RETARDER OVER 4" GRANULAR FILL. 9 12" CMU WALL, SOLID GROUT WITH 2-#6 @ 2'-8"OC. 10 8" CMU WALL, SOLID GROUT WITH 1-#5 @ 3'-4"OC. 2 20"x20" CONCRETE PILASTER. RE: 31/S2.2 FOR REINFORCEMENT. 11 NOT USED. 3 20"x32" CONCRETE PILASTER. RE: 31/S2.2 FOR REINFORCEMENT. 12 16"x36" CMU PILASTER. RE: 31/S2.2 FOR REINFORCEMENT. 4 16"x16" CMU PILASTER. RE: 31/S2.2 FOR REINFORCEMENT. 5 16"x24" CMU PILASTER. RE: 31/S2.2 FOR REINFORCEMENT. 6 12" CMU WALL REINFORCE PER GENERAL NOTES, UNLESS NOTED OTHERWISE.. 7 8" CMU WALL REINFORCE PER GENERAL NOTES, UNLESS NOTED OTHERWISE. 1 8 D F K E G L H 12" CMU WALL, SOLID GROUT WITH 2-#6 @ 1'-4"OC. FIRST LEVEL FOUNDATION PLAN - AREA L J SCALE: 1/8" = 1'-0" BENJAMIN TALPOS 10/8/2012 6:12:55 PM C:\Users\BrionP\Documents\9-2013-Revit Projects\Joplin\13-12102-00_central_struct_2012.rvt A NORTH NORTH © 2012, DLR Group of Missouri inc., a Missouri corporation CA No. 001614, ALL RIGHTS RESERVED. KEY PLAN M1 M3 M4 M2 1' - 6" 51 S3.3 1 MATCHLINE RE: S1.1J 14 S3.4 MATCHLINE RE: S1.1M JJ 51 S3.3 32 14 S3.3 S3.4 1 FF1 FF1 MC J4 99'-4" TO FTG 24' - 0" 1' - 6" 1 FF1 FF1 MD 51 S3.3 1' - 6" ME 12' - 0" 12' - 0" 51 S3.3 12' - 0" JOPLIN, JASPER COUNTY, MISSOURI 1' - 6" JOPLIN HIGH SCHOOL 24' - 0" FIRST LEVEL FOUNDATION PLAN - AREA M 99'-4" TO FTG 2 10-08-12 ADD #3 Architecture Engineering Planning Interiors 7290 West 133rd Street Overland Park, Kansas 66213 tel: (913)897-7811 Revisions 1 10-04-12 ADD #2 13-12102-00 09/10/12 S1.1M 1 B KEY NOTES: PLAN NOTES: A. FINISHED FLOOR ELEVATION = VARIES PER PLAN. 100'-0" EQUAL TO SURVEY ELEVATION = 1018.0'. B. SEE ARCHITECTURAL DRAWINGS FOR LOCATION OF SLOPED, RAISED, DEPRESSED SLABS AND DRAINS. C. D. E. F. REFER TO GENERAL NOTES SHEET S0.1 AND S0.2 FOR GENERAL NOTES, ABBREVIATIONS AND SYMBOLS. REFER TO SPECIFICATIONS FOR ALL SUBGRADE PREPARATION REQUIREMENTS. REFER TO ARCHITECTURAL DRAWINGS FOR OVERALL BUILDING GEOMETRY, WALL LOCATIONS, STAIR GEOMETRY AND ADDITIONAL PARTITION WALL REQUIREMENTS.AND ADDITIONAL PARTITION WALL REQUIREMENTS. REFER TO 52/S2.1 FOR COLUMN AND FOOTING SCHEDULES. G. H. J. K. L. REFER TO ARCHITECTURAL DRAWINGS FOR NON-LOAD BEARING PARTITION WALLS. REFER TO SHEETS S0.1, S0.2, S2.1, S2.2, AND S9.2 TYPICAL DETAILS FOR REINFORCING, THICKENED SLABS AND OTHER REQUIREMENTS. ALL CONCRETE BASEMENT WALLS HAVE BEEN DESIGNED AS CANTILEVERED, UNLESS OTHERWISE NOTED ON SECTIONS, NO TEMPORARY SHORING IS REQUIRED. BACKFILL WALLS PRIOR TO INSTALLING CONNECTING CONSTRUCTION. COORDINATE ALL PENETRATIONS THRU CONTINUOUS FOOTINGS WITH MEP DRAWINGS. REFERENCE TYPICAL DETAILS 34/S2.1 & 41/S2.1. ALL OPENINGS IN CMU WALLS REQUIRE A LINTEL. REFER TO SHEET S9.2 FOR TYPICAL MASONRY LINTEL DETAILS AND SCHEDULES. ALL EXTERIOR EXPOSED STEEL SHALL BE GALVANIZED. M. REFER TO ARCHITECTURAL DRAWINGS FOR PRECAST JOINT LOCATIONS. VERIFY JOINT LOCATIONS WITH PRECASTER. N. COORDINATE ALL FOOTING STEP LOCATIONS AND BRICK LEDGES WITH ARCHITECTURAL ELEVATIONS. P. ALL PRECAST CONNECTIONS SHALL BE DESIGNED BY THE PRECAST SUPPLIER. Q. ALL HSS MEMBERS SHALL HAVE 1/4" CAP PLATES AT ENDS. R. REFER TO 15/S2.2 FOR PIER SCHEDULE. S. DENOTES FEMA 361 SAFE ROOM AREA. REFER TO TYPICAL DETAILS (ON S4.3) AND GENERAL NOTES. 2 C 4" NORMAL WEIGHT CONCRETE SLAB-ON-GRADE W/ 6x6-W2.1xW2.1 WELDED WIRE REINFORCEMENT ON 15 MIL VAPOR RETARDER OVER 4" GRANULAR FILL. 9 12" CMU WALL, SOLID GROUT WITH 2-#6 @ 2'-8"OC. 10 8" CMU WALL, SOLID GROUT WITH 1-#5 @ 3'-4"OC. 2 20"x20" CONCRETE PILASTER. RE: 31/S2.2 FOR REINFORCEMENT. 11 NOT USED. 3 20"x32" CONCRETE PILASTER. RE: 31/S2.2 FOR REINFORCEMENT. 12 16"x36" CMU PILASTER. RE: 31/S2.2 FOR REINFORCEMENT. 4 16"x16" CMU PILASTER. RE: 31/S2.2 FOR REINFORCEMENT. 5 16"x24" CMU PILASTER. RE: 31/S2.2 FOR REINFORCEMENT. 6 12" CMU WALL REINFORCE PER GENERAL NOTES, UNLESS NOTED OTHERWISE.. 7 8" CMU WALL REINFORCE PER GENERAL NOTES, UNLESS NOTED OTHERWISE. 1 8 D F K E G L H 12" CMU WALL, SOLID GROUT WITH 2-#6 @ 1'-4"OC. J FIRST LEVEL FOUNDATION PLAN - AREA M SCALE: 1/8" = 1'-0" BENJAMIN TALPOS 10/8/2012 6:13:00 PM C:\Users\BrionP\Documents\9-2013-Revit Projects\Joplin\13-12102-00_central_struct_2012.rvt A NORTH NORTH © 2012, DLR Group of Missouri inc., a Missouri corporation CA No. 001614, ALL RIGHTS RESERVED. KEY PLAN AZ AZ A6 A7 A8 A9 A16 A10 A11 A12 A13 14k A14 A15 W12x26 (14) 14k W16x31 17k 60 k-ft MATCHLINE RE: S1.2B 17k 60 k-ft 8' - 1 1/2" 33k 325 k-ft BA MATCHLINE RE: S1.2A 218 k-ft 26k W16x77 A5 7k 325 k-ft 33k A4 W12x26 (14) 7' - 8" A3 26k W16x77 218 k-ft A2 15' - 8" A1 5' - 6" 7k W12x26 (14) 17k 17k B3 30' - 0" B4 B5 SPAN W16x77 300 k-ft 31k 12k 7' - 8" W14x34 (20) 11 25' - 4" 33 1 S5.2 B8 55 k-ft HSS6x6x5/16 (TOS = 116'-0") 23k HSS14x6x1/2 W18x40 (26) W16x26 (26) HSS12x2x1/4 STRINGER S5.4 10k 2 16 S5.4 S5.4 13 14 24k W16x26 (30) S5.4 HSS4x2x3/16 S5.4 10k CC5 16 S5.2 HSS6x6x3/8 15 24k HSS8x6x1/2 (TOS = 115'-6") 11 2k 15 LOW MATCHLINE RE: S1.2B S5.4 29' - 8" 20' - 0" B9 B10 16k 16k 16' - 0" 16k CA 166 k-ft 42 k-ft 29k W12x16 (16) MATCHLINE RE: S1.2C 16k B11 W16x31 B13 16' - 0" JOPLIN, JASPER COUNTY, MISSOURI W12x16 (26) 20k 7k 7k W14x22 (10) 7' - 7" 27k 10k W12x26 (14) 18k 11 JOPLIN HIGH SCHOOL SECOND LEVEL FLOOR FRAMING PLAN - AREA B 7k c=1" 295 k-ft 130 k-ft 19k 50k SPAN 1 7' - 7" W14x26 (26) W18x35 (30) 30k 7k 7' - 7" c=3/4" c=1" W16x26 (26) 26k W12x16 (10) 18k 30k 107 k-ft 19k W18x60 21 W14x22 10k S5.4 W14x30 (24) 14k c=1" c=1" 85 k-ft 22k W18x60 10k S5.2 25' - 4" B7 W14x26 (28) 47k 245 k-ft 12k 7' - 8" 7' - 7" 30k 26k 29k W16x36 (26) 30k STAIR STRINGER RE: LEVEL ABOVE W16x26 (26) c=1 1/4" W18x86 (28) W18x76 (28) W18x76 (28) S5.2 12k 21k 43k 44k 44k CC21 S5.2 29' - 8" B6 34 25k W12x16 (10) 7' - 3" B13 B14 16k 42 k-ft 2 10-08-12 ADD #3 32' - 6" CC24 CC24 18k W12x16 (16) 7290 West 133rd Street Overland Park, Kansas 66213 tel: (913)897-7811 B2 27' - 2" CC21 18k 2k FTG STEP SEE SHEET S1.1B FOR CONTINUATION 31k 181 k-ft Architecture Engineering Planning Interiors B1 9' - 8" 109 k-ft W18x60 (26) Revisions 4' - 5" 107'-4" TO FTG S5.2 24k 1 10-04-12 ADD #2 111'-4" TO FTG S3.4 CC24 W18x60 9k 13-12102-00 09/10/12 S3.3 W12x16 (10) 16k S1.2B FTG STEP S3.3 105'-4" TO FTG 12 HSS6x6x1/4 (TOS = 118'-8 1/2") W16x26 (20) 11k 109'-4" TO FTG 33 CC24 10k 11k W16x36 (28) S3.4 168 k-ft 166 k-ft 29k 32 CC21 23k 11k 32 FTG STEP CC21 43k CC21 S3.4 S3.4 14 W12x16 (16) 16k MECH UNIT PER MECH. MAX WT = 750# 15' - 4" BJ 115'-4" 32 TO FTG S3.3 2' - 0" 6' - 0" 14 W16x26 (20) 30k CC24 BH 14 W18x76 (28) W18x76 (28) W18x76 (28) 1 10k 11k W16x36 (28) CC21 CC21 CC21 CC21 FTG STEP 10k 31k W16x26 (26) CC21 CC16 FF4 CC21 10k W16x26 (10) 10k 50k CC21 113'-4" TO FTG 52k CC21 HSS6x6x1/4 (TOS = 118'-8 1/2") CC14 FF12 47k S3.3 CC21 43k HSS6x6x1/4 (TOS = 118'-8 1/2") CC14 FF11 W18x76 (28) W18x76 (28) 24' - 0" 32 CC21 CC14 FF13 HSS6x6x1/4 (TOS = 118'-8 1/2") W14x22 W14x22 10k 10k W16x26 (10) 10k RE:24/S2.1, TYP 25k 30k 1 10k MECH UNIT PER MECH. MAX WT = 500#, TYP 26k W16x26 (20) CC24 2 1 W16x31 (16) 18k 28k 26k 83k 50k 30k 27k W21x101 (28) 52k 246 k-ft 79k 47k 25k 70k 43k 25k 25k 275 k-ft W18x86 18k W12x16 (16) W14x38 (16) W14x38 (16) W14x34 (16) W14x34 (16) W14x34 (16) W14x34 (16) 1 1 HSS6x6x1/4 (TOS = 118'-8 1/2") 23k 10k HSS6x6x5/16 (TOS = 119'-7 1/2") 69k 44k CC24 69k 43k BG W18x86 (24) 25k 70k 115'-4" TO FTG 29k W18x46 8' - 8" 1 1 44k 3 W14x34 (16) W14x38 (16) CC14 FF5 25k CC14 FF5 43k 2' - 0" 6' - 0" CC14 FF12 26k W18x46 1 SPAN 1 26k 18k CC24 26k 18k W16x31 (24) 18k 26k 18k 84k 28k 30k W21x101 (28) 29k 31k 51k 53k 38k 80k 61k 9k 9k 4 CC9 FF12 CC14 FF5 c=3/4" c=1 1/4" W16x26 (26) W18x86 (30) W18x86 (30) W14x61 (24) W14x61 (24) 35k 35k W18x76 (24) 60k 17k W18x60 95 k-ft W12x16 (10) 16k 160 k-ft 1 31k 11' - 4" 60k 1 BF 20k 67 k-ft 9k 32k W18x76 (24) 25k CC24 115'-4" TO FTG W18x60 CC24 SPAN 1 1 HSS6x6x5/16 (TOS = 116'-0") 1 61k 115'-4" TO FTG 16k W12x16 (16) 16k CC21 CC21 CC14 FF6 25k CC14 FF6 W14x61 (24) 115'-4" TO FTG W14x61 (24) W14x61 (24) 115'-4" TO FTG BE 115'-4" TO FTG CC16 W12x26 (14) W14x26 (30) CC21 1 CC14 FF6 STAIR STRINGER RE: LEVEL ABOVE (RE: 35/S5.4) S3.3 CC21 CC21 CC24 1 35k 32 CC21 35k CC9 FF13 CC24 S5.2 24' - 4" 115'-4" TO FTG CC21 CC16 1 W18x76 11 CONTROL / CONSTRUCTION JT RE: TYPICAL DETAIL 15/S2.1 AND GENERAL NOTES, TYP. 115'-4" TO FTG W14x34 (20) 12k CC24 25k CC14 FF13 1 15' - 4" 12k FTG STEP W14x61 (24) CC14 FF13 CC21 CC24 HSS6x6x1/4 (TOS = 118'-8 1/2") 1 CC21 41 S5.2 S5.2 35k HSS6x6x1/4 (TOS = 118'-8 1/2") HSS6x6x1/4 (TOS = 118'-8 1/2") 17k 60 k-ft 7' - 7" CC21 S5.2 25k CC20 113'-4" TO FTG S3.4 17k 8' - 8" CC14 FF13 BD CC21 FTG STEP CC16 FF4 HSS6x6x1/4 (TOS = 118'-8 1/2") 31k CC21 35k CC21 12k HSS6x6x1/4 (TOS = 118'-8 1/2") 36 35k CC21 33 35k CC21 CC14 FF12 16 35k S3.3 CC21 CC21 S5.2 25k 6' - 0" S3.4 CC16 CC21 32 115'-4" TO FTG 14 2' - 0" BC S3.4 16k 51 HSS6x6x1/4 (TOS = 118'-8 1/2") S5.2 36 51k S3.4 1 33 S3.4 FTG STEP 1 53k HSS6x6x5/16 (TOS = 119'-7 1/2") 115'-4" TO FTG S3.3 107'-4" TO FTG 34 38k HSS6x6x1/4 (TOS = 118'-8 1/2") 14 S3.3 111'-4" TO FTG 35k 32 2' - 0" 1 32 FTG STEP SEE SHEET S1.1B FOR CONTINUATION W12x26 (14) W16x31 17k 60 k-ft BB 105'-4" TO FTG 17k 8' - 1 1/2" 31k 300 k-ft 17k 109'-4" TO FTG W12x26 (14) 8' - 1 1/2" W16x77 32' - 6" 17k 1 8' - 1 1/2" 1 16k B12 B 1 KEY NOTES: PLAN NOTES: A. FINISHED FLOOR ELEVATION IS 116'-0", UNLESS NOTED OTHERWISE. B. TOP OF STEEL ELEVATION IS TYPICALLY 115'-6", UNLESS NOTED OTHERWISE ON PLANS AND SECTIONS. TOP OF STEEL THAT OCCURS ON A SLOPE AND IS NOT SPECIFICALLY NOTED ON THE PLANS SHALL BE LINEARLY INTERPOLATED FROM TOP OF STEEL NOTED ON THE PLANS. C. SEE SHEET S4.1 AND S4.2 "FLOOR FRAMING TYPICAL DETAILS" FOR ADDITIONAL FRAMING REQUIREMENTS AND INFORMATION. D. JOIST SUPPLIER TO COORDINATE WITH MECHANICAL CONTRACTOR FOR RTU WEIGHTS, LOCATIONS AND PENETRATIONS. E. JOIST SUPPLIER SHALL DESIGN JOISTS FOR ALL LOADS INDICATED IN S0.1 & S0.2 'GENERAL NOTES', S0.3 'ROOF SNOW DRIFT PLAN', ON THE PLAN SHEETS, AND THE SECTION/DETAIL SHEETS. CONTRACTOR TO COORDINATE ALL WEIGHTS, LOCATIONS, AND PENETRATIONS OF EQUIPMENT WITH THE JOIST SUPPLIER PRIOR TO SUBMITTING JOIST SHOP DRAWINGS. G. SEE ARCHITECTURAL DRAWINGS FOR LOCATION OF SLOPED, RAISED, DEPRESSED SLABS AND DRAINS. M. ALL PRECAST CONNECTIONS SHALL BE DESIGNED BY THE PRECAST SUPPLIER. T. COORDINATE ALL PENETRATIONS THRU CONTINUOUS FOOTINGS WITH MEP DRAWINGS. REFERENCE TYPICAL DETAILS 34/S2.1 & 41/S2.1. H. REFER TO ARCHITECTURAL DRAWINGS FOR OVERALL BUILDING GEOMETRY, WALL LOCATIONS, STAIR GEOMETRY AND ADDITIONAL PARTITION WALL REQUIREMENTS. N. ALL HSS MEMBERS SHALL HAVE 1/4" CAP PLATES AT ENDS. U. ALL EXTERIOR EXPOSED STEEL SHALL BE GALVANIZED. J. REFER TO ARCHITECTURAL DRAWINGS FOR NON-LOAD BEARING PARTITION WALLS. REFER TO SHEETS S0.1, S0.2, S2.1, S2.2, AND S9.2 TYPICAL DETAILS FOR REINFORCING, THICKENED SLABS AND OTHER REQUIREMENTS. K. ALL OPENINGS IN CMU WALLS (PARTITION AND LOAD BEARING) REQUIRE A LINTEL. REFER TO SHEET S9.2 FOR TYPICAL MASONRY LINTEL DETAILS AND SCHEDULES. L. SEE SHEET S6.1 AND S6.2 "ROOF FRAMING TYPICAL DETAILS" FOR ADDITIONAL REQUIREMENTS AND INFORMATION. O. P. PROVIDE HSS3 1/2x2 1/2x1/4 (LLH) BETWEEN ALL JOIST WITH 2 1/2" SEATS TO SUPPORT ROOF DECK WHERE DECK SWITCHES DIRECTION. (RE: 44/S6.1) REFER TO SPECIFICATIONS FOR ALL SUBGRADE PREPARATION REQUIREMENTS. Q. SEE SHEET S2.1 AND S2.2 "TYPICAL FOUNDATION SECTIONS" FOR ADDITIONAL REQUIREMENTS AND INFORMATION. R. REFER TO 52/S2.1 FOR COLUMN AND FOOTING SCHEDULES. S. REFER TO ARCHITECTURAL DRAWINGS FOR PRECAST JOINT LOCATIONS. VERIFY JOINT LOCATIONS WITH PRECASTER. V. COORDINATE ALL FOOTING STEP LOCATIONS AND BRICK LEDGES WITH ARCHITECTURAL ELEVATIONS. 1 2 C 6 6" NORMAL WEIGHT AIR ENTRAINED CONCRETE SLAB-ON-GRADE REINFORCE WITH #4 @ 12"OC EACH WAY ON 15 MIL VAPOR RETARDER OVER 4" GRANULAR FILL. 1 1/2" DEEP, 20 GAGE, GALVANIZED WIDE RIB STEEL ROOF DECK. PROVIDE 5/8" DIAMETER PUBBLE WELDS IN 36/5 PATTERN AND 2 #10 TEK SCREWS AT SIDELAPS PER SPAN. 7 8" HOLLOW CORE WITH 2" TOPPING SLAB. REINFORCE TOPPING SLAB WITH 6x6/W2.1xW2.1 WELDED WIRE REINFORCEMENT. PRECAST SUPPLIER TO DESIGN FOR 125 PSF. 4" NORMAL WEIGHT CONCRETE SLAB-ON-GRADE W/ 6x6-W2.1xW2.1 WELDED WIRE REINFORCEMENT ON 15 MIL VAPOR RETARDER OVER 4" GRANULAR FILL. 8 12" CMU WALL REINFORCE PER GENERAL NOTES, UNLESS NOTED OTHERWISE. 9 8" CMU WALL REINFORCE PER GENERAL NOTES, UNLESS NOTED OTHERWISE. 3" NORMAL WEIGHT CONCRETE SLAB ON 3" DEEP, 20 GAGE, GALVANIZED COMPOSITE STEEL FLOOR DECK (6" TOTAL THICKNESS). REINFORCE WITH 6x6/W2.1xW2.1 WELDED WIRE REINFORCEMENT. 2 D 2 W. DENOTES FEMA 361 SAFE ROOM AREA. REFER TO TYPICAL DETAILS (ON S4.3) AND GENERAL NOTES. 3 4 6" NORMAL WEIGHT CONCRETE SLAB ON 3" DEEP, 20 GAGE, GALVANIZED COMPOSITE STEEL FLOOR DECK (9" TOTAL THICKNESS). REINFORCE WITH 6x6/W2.1xW2.1 WELDED WIRE REINFORCEMENT. 5 DOWEL FOOTING AND WALL TOGETHER WITH 2-#6, TOP & BOTTTOM. PROVIDE 'CLASS B' LAP SPLICE. HOOK BARS 1'-0" INTO WALL. SECOND LEVEL FRAMING PLAN - AREA B F K E G L H J SCALE: 1/8" = 1'-0" BENJAMIN TALPOS 10/8/2012 6:13:08 PM C:\Users\BrionP\Documents\9-2013-Revit Projects\Joplin\13-12102-00_central_struct_2012.rvt A NORTH NORTH © 2012, DLR Group of Missouri inc., a Missouri corporation CA No. 001614, ALL RIGHTS RESERVED. KEY PLAN 105'-4" TO FTG B2 32' - 6" B3 B4 W16x26 (30) 10k 21k 30k 30k 31k 50k 52k 47k 43k 24k 24k CC21 11 S5.2 33 11 S5.2 S5.2 25' - 4" B6 25' - 4" B7 20' - 0" B9 15 LOW MATCHLINE RE: S1.2B S5.4 29' - 8" B8 2k HSS8x6x1/2 (TOS = 115'-6") 11k 11k FTG STEP SEE SHEET S1.1B FOR CONTINUATION 29' - 8" B5 S5.2 HSS4x2x3/16 S5.4 2k 107'-4" TO FTG 30' - 0" 14 16k B10 W12x16 (16) 16k 16' - 0" W16x31 16k CA 16' - 0" 7' - 3" B13 B14 16k 42 k-ft 42 k-ft 166 k-ft 29k MATCHLINE RE: S1.2C B13 11k W16x36 (28) B1 27' - 2" S5.2 S5.4 166 k-ft 29k 9' - 8" CC24 CC5 16 34 11k W16x36 (28) 111'-4" TO FTG 4' - 5" CC24 16 S5.4 13 CC24 CC21 S5.2 109'-4" TO FTG FTG STEP CC21 CC24 12 CC21 HSS6x6x1/4 (TOS = 118'-8 1/2") 15' - 4" BJ FTG STEP 115'-4" TO FTG CC21 1 CC24 44k FTG STEP CC21 CC21 43k CC21 44k CC21 43k CC21 16k W12x16 (16) 16k 16k W12x16 (16) 16k 16k W12x16 (16) 16k W16x31 16k W16x57 SPAN 166 k-ft 29k 11k W16x36 (28) 7k 10k W18x60 21k 22k W12x26 51 25' - 4" S5.2 CC21 15 35 S5.2 C8 13' - 8" CC21 25' - 4" S5.2 C9 C10 20' - 0" C12 40k 40k 27k c=1" W12x26 (38) W16x26 (20) 8k 14k 84k 44k D10 16k C13 W12x16 (16) S5.4 W14x26 (14) HSS4x2x3/16 S5.4 HSS8x6x5/16 2k 15 8k 16' - 0" 14k 7k 16 S5.4 17k W12x16 (16) HSS6x6x3/8 10k 17k HSS12x2x1/4 STRINGER S5.4 LOW MATCHLINE RE: S1.2C 7' - 3" S5.4 B12 MATCHLINE RE: S1.2D C14 B12 c=1" 44k HSS6x6x5/16 (TOS = 116'-0") 23k 13 16' - 0" 514 k-ft 66k W18x35 (34) S5.4 15 21k 30k 31k W16x26 (26) 19k 22k 29' - 8" 102 k-ft S5.4 14 W18x35 (34) 22k 82 k-ft 11 W14x30 (32) MECH UNIT PER MECH. MAX WT = 750# W18x35 (26) 19k 2 c=1" 10k W16x26 (26) c=1" W14x22 c=1 1/4" 40k 14k 18k W18x60 20k W12x26 (30) W18x60 18k W12x16 (16) 12k W12x16 (26) 21 30k 10k W16x26 (10) 10k 38k W21x44 (46) 38k STAIR STRINGER RE: LEVEL ABOVE 10k W16x26 (26) 10k W16x26 (10) 10k RE:24/S2.1, TYP 10k W16x26 (26) 2 W14x22 W14x22 10k c=1" c=1 1/4" MECH UNIT PER MECH. MAX WT = 500#, TYP W16x26 (36) 2 10k W16x26 (22) 14k 25k 30k 30k 31k 45k 38k 41k c=1" W16x26 (36) c=1 1/4" 15k W16x26 (20) 25k 18k 296 k-ft W16x26 (26) c=1" W16x26 (26) 15k HSS6x6x1/4 (TOS = 118'-8 1/2") 26k W12x16 (16) HSS14x6x5/16 W16x26 (20) 26k 18k 19k W12x16 (16) W12x16 (16) 20k W14x30 (16) 22k 20k W12x16 (16) W12x16 (16) 21k 18k 363 k-ft 43k 26k 15k 55k 10k W12x22 (14) 16k 16k CC24 W18x76 57k 265 k-ft 22k 1 W14x30 (32) W12x16 (16) W12x16 (16) 17k W14x30 (32) 18k 15k 43k 18k 105 k-ft 180 k-ft 9k 19k 18k 18k 19k 20k 19k 19k 20k 18k 15k 17k 1 7k 31k W18x60 14k B11 2 10-08-12 ADD #3 0" 7290 West 133rd Street Overland Park, Kansas 66213 tel: (913)897-7811 W16x26 (20) Architecture Engineering Planning Interiors 10k Revisions 11k 7k W16x31 (24) W14x26 (14) 11k 270 k-ft 1 64k 9k JOPLIN, JASPER COUNTY, MISSOURI W12x16 (16) 7k 168 k-ft 9k JOPLIN HIGH SCHOOL 0" 29k W18x46 W14x26 (14) 47k W18x35 54k 25k 21k 32k c=1" 2k 1 203 k-ft 5' - 7 1/8" 5' - 7 1/8" W18x35 (26) W21x55 (46) 5' - 7 1/8" 54k 32k c=1 1/4" W16x26 (26) W14x30 (26) 5' - 7 1/8" 25k 21k W14x30 (26) W12x26 (26) 13k 8k 18k W14x30 (10) 18k 17k W12x22 (26) 10k W12x16 (26) 36k CC24 29' - 8" C7 0" 9k 1 10-04-12 ADD #2 C6 S5.2 W12x16 (16) 13-12102-00 09/10/12 C5 30' - 0" S5.2 26k S1.2C C3 C4 FTG STEP S3.4 SEE SHEET CC21 S1.1C FOR CONTINUATION W18x46 (26) W24x76 32' - 6" 109'-4" TO FTG S3.4 14 W12x16 (26) 24k 180 k-ft FTG STEP STEP FTG 11 16k W18x60 63 k-ft 9k W18x46 W18x86 25' - 7 5/8" 111'-4" TO FTG S5.2 26k W12x16 (26) 660 k-ft C2 1' - 6 3/8" S3.4 25 34 63 k-ft W18x46 6' - 6 1/4" 9' - 8" 115'-4" S3.3 TO FTG S3.4 S3.3 CC21 W18x46 (52) W18x97 CM 14 32 2' - 0" 6' - 0" 14 33 21k 16k CC24 CL 32 53k 38k CC21 W18x76 26k W12x22 (14) 16k 31k W16x57 (22) W16x67 (24) 21k CC21 34k 26k CC21 CC16 FTG STEP W14x30 (14) HSS6x6x1/4 (TOS = 118'-8 1/2") CC21 CC21 HSS6x6x1/4 (TOS = 118'-8 1/2") 21k CC21 CC21 107'-4" TO FTG W14x30 (14) HSS6x6x1/4 (TOS = 118'-8 1/2") CC16 FF4 c=3/4" 125 k-ft 21k S3.3 113'-4" TO FTG CC14 FF12 31k CC14 FF11 32 33k 1 32k 24' - 0" W16x67 (24) 105'-4" TO FTG 17k 1k SPAN 1 C1 W12x30 (24) 16k 4 2' - 0" W12x16 RAKER 37k (6) W12x22 (14) 115'-4" TO FTG 115'-4" TO FTG 4' - 5" 39k 17k W12x16 (16) W18x86 57k 32k 33k 115'-4" TO FTG W12x16 RAKER W18x46 9k W14x38 (44) 28k W12x16 RAKER HSS8x6x3/8 SPAN 1k HSS6x6x5/16 (TOS = 119'-7 1/2") 16k CC16 HSS8x6x3/8 16k HSS6x6x5/16 (TOS = 116'-0") 105 k-ft W14x38 (16) W18x86 (22) 55k CK C11 W12x16 RAKER 17k CC16 1 W14x38 (16) CC14 FF5 CC16 14 16k W18x60 1k 22k 6' - 0" CC14 FF5 S5.2 7' - 5" 22k 1 CC14 FF12 7' - 5" W14x38 (16) 2' - 0" CC9 FF12 7' - 2 7/8" S5.2 54k W12x30 (24) 15k 22k 23k 115'-4" TO FTG 23k 11' - 4" 115'-4" TO FTG 22k 1k 1 (6) 13 W12x16 (16) 27 k-ft W18x76 57k 11 18k W18x76 (22) 55k CH CJ S5.2 S5.2 22k W14x30 (14) CC16 CC24 17k W14x30 (10) 17k 31k 1 31k S3.3 1 32k CC14 FF6 STAIR STRINGER RE: LEVEL ABOVE (RE: 35/S5.4) CC14 FF6 34k CC9 FF13 W16x57 (24) W16x67 (24) 24' - 4" 3 W16x67 (24) 1 CONTROL / CONSTRUCTION JT RE: TYPICAL DETAIL 15/S2.1 AND GENERAL NOTES, TYP. 32 32k 115'-4" TO FTG CC14 FF13 2' - 0" 5 16k W18x76 (24) 57k 34k CF 37k CC24 115'-4" TO FTG CC20 5 S3.4 13k W12x22 (26) 13k CC14 FF4 17k W14x30 (10) 17k 6' - 0" 2' - 0" S3.3 32 22 S3.4 SPAN S3.3 32 115'-4" TO FTG 4 CC24 2' - 0" 26 16k W18x76 (26) CC16 2' - 0" 10k 1 S3.4 W16x67 (24) W16x67 (24) CC14 FF6 32 CE 1 52k 18' - 8" 2' - 0" 42 k-ft 26 1 CC14 FF4 42 k-ft 115'-4" TO FTG 1 HSS6x6x5/16 (TOS = 119'-7 1/2") W16x57 1 S5.2 16k CD SECOND LEVEL FLOOR FRAMING PLAN - AREA C 113'-4" TO FTG 1 CC24 S3.4 11k 42 S3.4 12 SPAN 115'-4" TO FTG 26 CC24 7k CC14 FF11 105'-4" TO FTG HSS10x6x3/8 (TOS = 122'-0 1/2") 7k CC14 FF11 FTG STEP 109'-4" TO FTG CC16 FF2 FTG STEP W14x22 (10) CC14 FF11 HSS10x6x3/8 (TOS = 122'-0 1/2") S5.2 2' - 0" 115'-4" TO FTG 31 S3.4 CC CC3 FF10 29k 111'-4" TO FTG 114'-8" TO FTG CC3 FF10 166 k-ft 1 S3.3 STEP FTG 41 FTG STEP SEE SHEET S1.1C FOR CONTINUATION 114'-8" TO FTG CC3 FF10 11k 2' - 0" 7' - 10" S3.4 S3.6 32 HSS8x6x3/8 (TOS = 122'-0 1/2") 41 107'-4" TO FTG 114'-8" TO FTG CC3 FF10 11k W16x36 (28) HSS10x6x3/8 (TOS = 122'-0 1/2") 25 114'-8" TO FTG CC3 FF10 15' - 4" 2 CB 114'-8" TO FTG CC3 FF10 2' - 0" 114'-8" TO FTG CC3 FF10 39k 114'-8" TO FTG CC3 FF10 37k 114'-8" TO FTG 30' - 8" 17' - 6" B 1 KEY NOTES: PLAN NOTES: A. FINISHED FLOOR ELEVATION IS 116'-0", UNLESS NOTED OTHERWISE. B. TOP OF STEEL ELEVATION IS TYPICALLY 115'-6", UNLESS NOTED OTHERWISE ON PLANS AND SECTIONS. TOP OF STEEL THAT OCCURS ON A SLOPE AND IS NOT SPECIFICALLY NOTED ON THE PLANS SHALL BE LINEARLY INTERPOLATED FROM TOP OF STEEL NOTED ON THE PLANS. C. SEE SHEET S4.1 AND S4.2 "FLOOR FRAMING TYPICAL DETAILS" FOR ADDITIONAL FRAMING REQUIREMENTS AND INFORMATION. D. JOIST SUPPLIER TO COORDINATE WITH MECHANICAL CONTRACTOR FOR RTU WEIGHTS, LOCATIONS AND PENETRATIONS. E. JOIST SUPPLIER SHALL DESIGN JOISTS FOR ALL LOADS INDICATED IN S0.1 & S0.2 'GENERAL NOTES', S0.3 'ROOF SNOW DRIFT PLAN', ON THE PLAN SHEETS, AND THE SECTION/DETAIL SHEETS. CONTRACTOR TO COORDINATE ALL WEIGHTS, LOCATIONS, AND PENETRATIONS OF EQUIPMENT WITH THE JOIST SUPPLIER PRIOR TO SUBMITTING JOIST SHOP DRAWINGS. G. SEE ARCHITECTURAL DRAWINGS FOR LOCATION OF SLOPED, RAISED, DEPRESSED SLABS AND DRAINS. M. ALL PRECAST CONNECTIONS SHALL BE DESIGNED BY THE PRECAST SUPPLIER. T. COORDINATE ALL PENETRATIONS THRU CONTINUOUS FOOTINGS WITH MEP DRAWINGS. REFERENCE TYPICAL DETAILS 34/S2.1 & 41/S2.1. H. REFER TO ARCHITECTURAL DRAWINGS FOR OVERALL BUILDING GEOMETRY, WALL LOCATIONS, STAIR GEOMETRY AND ADDITIONAL PARTITION WALL REQUIREMENTS. N. ALL HSS MEMBERS SHALL HAVE 1/4" CAP PLATES AT ENDS. U. ALL EXTERIOR EXPOSED STEEL SHALL BE GALVANIZED. J. REFER TO ARCHITECTURAL DRAWINGS FOR NON-LOAD BEARING PARTITION WALLS. REFER TO SHEETS S0.1, S0.2, S2.1, S2.2, AND S9.2 TYPICAL DETAILS FOR REINFORCING, THICKENED SLABS AND OTHER REQUIREMENTS. K. ALL OPENINGS IN CMU WALLS (PARTITION AND LOAD BEARING) REQUIRE A LINTEL. REFER TO SHEET S9.2 FOR TYPICAL MASONRY LINTEL DETAILS AND SCHEDULES. L. SEE SHEET S6.1 AND S6.2 "ROOF FRAMING TYPICAL DETAILS" FOR ADDITIONAL REQUIREMENTS AND INFORMATION. O. P. PROVIDE HSS3 1/2x2 1/2x1/4 (LLH) BETWEEN ALL JOIST WITH 2 1/2" SEATS TO SUPPORT ROOF DECK WHERE DECK SWITCHES DIRECTION. (RE: 44/S6.1) REFER TO SPECIFICATIONS FOR ALL SUBGRADE PREPARATION REQUIREMENTS. Q. SEE SHEET S2.1 AND S2.2 "TYPICAL FOUNDATION SECTIONS" FOR ADDITIONAL REQUIREMENTS AND INFORMATION. R. REFER TO 52/S2.1 FOR COLUMN AND FOOTING SCHEDULES. S. REFER TO ARCHITECTURAL DRAWINGS FOR PRECAST JOINT LOCATIONS. VERIFY JOINT LOCATIONS WITH PRECASTER. V. COORDINATE ALL FOOTING STEP LOCATIONS AND BRICK LEDGES WITH ARCHITECTURAL ELEVATIONS. 1 2 C 6 6" NORMAL WEIGHT AIR ENTRAINED CONCRETE SLAB-ON-GRADE REINFORCE WITH #4 @ 12"OC EACH WAY ON 15 MIL VAPOR RETARDER OVER 4" GRANULAR FILL. 1 1/2" DEEP, 20 GAGE, GALVANIZED WIDE RIB STEEL ROOF DECK. PROVIDE 5/8" DIAMETER PUBBLE WELDS IN 36/5 PATTERN AND 2 #10 TEK SCREWS AT SIDELAPS PER SPAN. 7 8" HOLLOW CORE WITH 2" TOPPING SLAB. REINFORCE TOPPING SLAB WITH 6x6/W2.1xW2.1 WELDED WIRE REINFORCEMENT. PRECAST SUPPLIER TO DESIGN FOR 125 PSF. 4" NORMAL WEIGHT CONCRETE SLAB-ON-GRADE W/ 6x6-W2.1xW2.1 WELDED WIRE REINFORCEMENT ON 15 MIL VAPOR RETARDER OVER 4" GRANULAR FILL. 8 12" CMU WALL REINFORCE PER GENERAL NOTES, UNLESS NOTED OTHERWISE. 9 8" CMU WALL REINFORCE PER GENERAL NOTES, UNLESS NOTED OTHERWISE. 3" NORMAL WEIGHT CONCRETE SLAB ON 3" DEEP, 20 GAGE, GALVANIZED COMPOSITE STEEL FLOOR DECK (6" TOTAL THICKNESS). REINFORCE WITH 6x6/W2.1xW2.1 WELDED WIRE REINFORCEMENT. 2 D 2 W. DENOTES FEMA 361 SAFE ROOM AREA. REFER TO TYPICAL DETAILS (ON S4.3) AND GENERAL NOTES. 3 4 6" NORMAL WEIGHT CONCRETE SLAB ON 3" DEEP, 20 GAGE, GALVANIZED COMPOSITE STEEL FLOOR DECK (9" TOTAL THICKNESS). REINFORCE WITH 6x6/W2.1xW2.1 WELDED WIRE REINFORCEMENT. 5 DOWEL FOOTING AND WALL TOGETHER WITH 2-#6, TOP & BOTTTOM. PROVIDE 'CLASS B' LAP SPLICE. HOOK BARS 1'-0" INTO WALL. SECOND LEVEL FRAMING PLAN - AREA C F K E G L H J SCALE: 1/8" = 1'-0" BENJAMIN TALPOS 10/8/2012 6:13:17 PM C:\Users\BrionP\Documents\9-2013-Revit Projects\Joplin\13-12102-00_central_struct_2012.rvt A NORTH NORTH © 2012, DLR Group of Missouri inc., a Missouri corporation CA No. 001614, ALL RIGHTS RESERVED. KEY PLAN c=1 1/4" 40k SIM (RE: ARCH) 47k 1 7' - 8" c=1" 89k 7' - 8" 48k 21k 50k 23k W24x68 (50) 1 c=1" W16x26 (26) S5.2 25' - 4" D7 D8 25' - 4" 29' - 8" D9 W18x35 (16) 56 15k W18x35 (14)50k S5.4 46 S5.4 36' - 0" D10 19k 16' - 0" 34k 532 k-ft 12' - 0" B11 9' - 4" HSS4x2x3/16 E10 D11 C13 W27x129 63k 25k 22k 27k 19k W16x26 (20) 25k 38k 27k 55k 19k 20k 31k 27 k-ft 30k STAIR STRINGER RE: LEVEL ABOVE MATCHLINE RE: S1.2D MATCHLINE RE: S1.2E W18x35 (26) F1 KEY PLAN B 1 KEY NOTES: PLAN NOTES: A. FINISHED FLOOR ELEVATION IS 116'-0", UNLESS NOTED OTHERWISE. B. TOP OF STEEL ELEVATION IS TYPICALLY 115'-6", UNLESS NOTED OTHERWISE ON PLANS AND SECTIONS. TOP OF STEEL THAT OCCURS ON A SLOPE AND IS NOT SPECIFICALLY NOTED ON THE PLANS SHALL BE LINEARLY INTERPOLATED FROM TOP OF STEEL NOTED ON THE PLANS. C. SEE SHEET S4.1 AND S4.2 "FLOOR FRAMING TYPICAL DETAILS" FOR ADDITIONAL FRAMING REQUIREMENTS AND INFORMATION. D. JOIST SUPPLIER TO COORDINATE WITH MECHANICAL CONTRACTOR FOR RTU WEIGHTS, LOCATIONS AND PENETRATIONS. E. JOIST SUPPLIER SHALL DESIGN JOISTS FOR ALL LOADS INDICATED IN S0.1 & S0.2 'GENERAL NOTES', S0.3 'ROOF SNOW DRIFT PLAN', ON THE PLAN SHEETS, AND THE SECTION/DETAIL SHEETS. CONTRACTOR TO COORDINATE ALL WEIGHTS, LOCATIONS, AND PENETRATIONS OF EQUIPMENT WITH THE JOIST SUPPLIER PRIOR TO SUBMITTING JOIST SHOP DRAWINGS. G. SEE ARCHITECTURAL DRAWINGS FOR LOCATION OF SLOPED, RAISED, DEPRESSED SLABS AND DRAINS. M. ALL PRECAST CONNECTIONS SHALL BE DESIGNED BY THE PRECAST SUPPLIER. T. COORDINATE ALL PENETRATIONS THRU CONTINUOUS FOOTINGS WITH MEP DRAWINGS. REFERENCE TYPICAL DETAILS 34/S2.1 & 41/S2.1. H. REFER TO ARCHITECTURAL DRAWINGS FOR OVERALL BUILDING GEOMETRY, WALL LOCATIONS, STAIR GEOMETRY AND ADDITIONAL PARTITION WALL REQUIREMENTS. N. ALL HSS MEMBERS SHALL HAVE 1/4" CAP PLATES AT ENDS. U. ALL EXTERIOR EXPOSED STEEL SHALL BE GALVANIZED. J. REFER TO ARCHITECTURAL DRAWINGS FOR NON-LOAD BEARING PARTITION WALLS. REFER TO SHEETS S0.1, S0.2, S2.1, S2.2, AND S9.2 TYPICAL DETAILS FOR REINFORCING, THICKENED SLABS AND OTHER REQUIREMENTS. K. ALL OPENINGS IN CMU WALLS (PARTITION AND LOAD BEARING) REQUIRE A LINTEL. REFER TO SHEET S9.2 FOR TYPICAL MASONRY LINTEL DETAILS AND SCHEDULES. L. SEE SHEET S6.1 AND S6.2 "ROOF FRAMING TYPICAL DETAILS" FOR ADDITIONAL REQUIREMENTS AND INFORMATION. O. P. PROVIDE HSS3 1/2x2 1/2x1/4 (LLH) BETWEEN ALL JOIST WITH 2 1/2" SEATS TO SUPPORT ROOF DECK WHERE DECK SWITCHES DIRECTION. (RE: 44/S6.1) REFER TO SPECIFICATIONS FOR ALL SUBGRADE PREPARATION REQUIREMENTS. Q. SEE SHEET S2.1 AND S2.2 "TYPICAL FOUNDATION SECTIONS" FOR ADDITIONAL REQUIREMENTS AND INFORMATION. R. REFER TO 52/S2.1 FOR COLUMN AND FOOTING SCHEDULES. S. REFER TO ARCHITECTURAL DRAWINGS FOR PRECAST JOINT LOCATIONS. VERIFY JOINT LOCATIONS WITH PRECASTER. V. COORDINATE ALL FOOTING STEP LOCATIONS AND BRICK LEDGES WITH ARCHITECTURAL ELEVATIONS. 1 2 C 6 6" NORMAL WEIGHT AIR ENTRAINED CONCRETE SLAB-ON-GRADE REINFORCE WITH #4 @ 12"OC EACH WAY ON 15 MIL VAPOR RETARDER OVER 4" GRANULAR FILL. 1 1/2" DEEP, 20 GAGE, GALVANIZED WIDE RIB STEEL ROOF DECK. PROVIDE 5/8" DIAMETER PUBBLE WELDS IN 36/5 PATTERN AND 2 #10 TEK SCREWS AT SIDELAPS PER SPAN. 7 8" HOLLOW CORE WITH 2" TOPPING SLAB. REINFORCE TOPPING SLAB WITH 6x6/W2.1xW2.1 WELDED WIRE REINFORCEMENT. PRECAST SUPPLIER TO DESIGN FOR 125 PSF. 4" NORMAL WEIGHT CONCRETE SLAB-ON-GRADE W/ 6x6-W2.1xW2.1 WELDED WIRE REINFORCEMENT ON 15 MIL VAPOR RETARDER OVER 4" GRANULAR FILL. 8 12" CMU WALL REINFORCE PER GENERAL NOTES, UNLESS NOTED OTHERWISE. 9 8" CMU WALL REINFORCE PER GENERAL NOTES, UNLESS NOTED OTHERWISE. 3" NORMAL WEIGHT CONCRETE SLAB ON 3" DEEP, 20 GAGE, GALVANIZED COMPOSITE STEEL FLOOR DECK (6" TOTAL THICKNESS). REINFORCE WITH 6x6/W2.1xW2.1 WELDED WIRE REINFORCEMENT. 2 D 2 W. DENOTES FEMA 361 SAFE ROOM AREA. REFER TO TYPICAL DETAILS (ON S4.3) AND GENERAL NOTES. 3 4 6" NORMAL WEIGHT CONCRETE SLAB ON 3" DEEP, 20 GAGE, GALVANIZED COMPOSITE STEEL FLOOR DECK (9" TOTAL THICKNESS). REINFORCE WITH 6x6/W2.1xW2.1 WELDED WIRE REINFORCEMENT. 5 DOWEL FOOTING AND WALL TOGETHER WITH 2-#6, TOP & BOTTTOM. PROVIDE 'CLASS B' LAP SPLICE. HOOK BARS 1'-0" INTO WALL. SECOND LEVEL FRAMING PLAN - AREA D F K E G L H J SCALE: 1/8" = 1'-0" BENJAMIN TALPOS 10/8/2012 6:13:25 PM C:\Users\BrionP\Documents\9-2013-Revit Projects\Joplin\13-12102-00_central_struct_2012.rvt A NORTH NORTH © 2012, DLR Group of Missouri inc., a Missouri corporation CA No. 001614, ALL RIGHTS RESERVED. 1 S5.2 37k 2 10-08-12 ADD #3 16 59k 7290 West 133rd Street Overland Park, Kansas 66213 tel: (913)897-7811 W16x26 (30) 20k c=3/4" W16x26 (14) 18k c=1" W16x26 (14) c=1" W16x26 (14) c=1" 8' - 0" c=3/4" D12 SPAN Architecture Engineering Planning Interiors 50k 18k ? k-ft JOPLIN, JASPER COUNTY, MISSOURI 6k 15k W18x60 25k 22k ? k-ft MATCHLINE RE: S1.2F Revisions 6k W14x26 (30) 19k W18x60 159 k-ft 27 k-ft W12x16 (26) 10k 105 k-ft W12x26 21k 22k 0" 30k 175 k-ft 2 18k 1 10-04-12 ADD #2 106 k-ft W12x16 (26) MATCHLINE RE: S1.2D JOPLIN HIGH SCHOOL 5k 6k 6k 253 k-ft 48k W18x60 (26) 10k 10k 158 k-ft 19k 24k 101 k-ft 35 k-ft 13k 10k 34k SPAN 1 W18x35 W12x16 (26) 0" W12x16 (26) 0" W12x26 (26) 34k W14x22 10k 10k W14x26 (28) W18x35 (40) 26k 29k 30k 11k W18x60 W8x10 (10) 199 k-ft 45k c=3/4" 16k SECOND LEVEL FLOOR FRAMING PLAN - AREA D W18x40 (28) 10k 32k 7' - 8" W16x26 (26) W16x36 (42) 146 k-ft 13-12102-00 09/10/12 34 W18x40 (26) 48k ?k 36k 38k W18x35 (26) 37k 28k 28k 27k 28k 27k CC16 21k FTG STEP SEE SHEET S1.1D FOR CONTINUATION 29' - 8" D6 27k W18x46 S1.2D D5 25k 138 k-ft 8' - 0" W14x22 10k W12x19 (20) D4 W12x16 (26) 16k W12x19 (20) 30' - 0" CC16 14 S5.2 23k 107'-4" TO FTG 105'-4" TO FTG 111'-4" TO FTG 15k W18x60 78 k-ft W16x77 (26) D3 S3.4 W12x16 (16) W18x46 1 W12x19 (20) 32' - 6" S3.4 33 W12x19 (20) D2 27' - 2" 113'-4" TO FTG CC21 W12x19 (20) 9' - 8" S3.3 CC21 23k S3.3 33 W12x19 (20) D1 32 HSS6x6x5/16 (TOS = 116'-0") 20k 18k W12x16 (16) W16x26 (26) 10k W16x26 (10) 10k 10k W16x50 RE:24/S2.1, TYP W14x22 1 MECH UNIT PER MECH. MAX WT = 750# W12x19 (20) 4' - 5" 14 S3.4 W18x60 7k 22k W16x26 (26) 16 13k S3.3 115'-4" TO FTG W16x26 (20) 10k 10k W16x26 (10) 10k 10k W12x19 (20) DJ 32 c=1" c=3/4" c=1 1/4" W16x26 (26) 31k 0" W12x16 (26) 2 W16x26 (26) MECH UNIT PER MECH. MAX WT = 500#, TYP c=1 1/4" 10k W18x71 2 0" 31k 36k 40k W16x26 (26) S3.4 2' - 0" 6' - 0" 14 S3.4 26k 29k 31k 31k c=3/4" W14x30 (26) W14x30 (26) 14k W16x26 (26) W14x26 (26) W14x26 (26) W14x26 (26) CC21 W14x26 (26) CC16 22k DH 32 16k 26k CC21 W12x16 (16) 16k 116 k-ft 14 S3.4 26k 30k CC21 CC16 FF4 FTG STEP 10k 7' - 8" 26k CC21 FTG STEP W16x31 (24) 26k 22k CC21 CC14 FF13 CC21 47k W12x19 (20) CC21 CC21 15k 10k 83 k-ft CC14 FF11 HSS6x6x1/4 (TOS = 118'-8 1/2") CC14 FF12 HSS6x6x1/4 (TOS = 118'-8 1/2") CC21 W14x26 (26) CC21 HSS6x6x1/4 (TOS = 118'-8 1/2") 47k W14x30 (26) W14x30 18k 43k c=1 1/4" c=1 1/4" c=1 1/4" c=1 1/4" c=1 1/4" c=1 1/4" W14x26 (26) 24' - 0" 32 S3.3 c=1" 19k 83 k-ft 23k 17k W12x16 (16) 17k 1 1 1 109'-4" TO FTG W12x26 17k 7' - 3" 26k 32k 31k 23k 23k W12x16 (16) 17k 115'-4" TO FTG HSS6x6x1/4 (TOS = 118'-8 1/2") 16k 10k W21x101 (26) 1 2' - 0" STAIR STRINGER RE: LEVEL ABOVE (RE: 35/S5.4) W12x16 (16) 16k 9' - 10" W18x76 (78) 45k SPAN 115'-4" TO FTG W18x35 (34) 47k W16x40 (46) W14x48 (26) W14x26 (30) W14x26 (30) W14x48 (26) 29k 10' - 0" c=1 1/4" 115'-4" TO FTG 16k 16k W12x16 (16) W18x86 (26) 36k 28k 27k 115'-4" TO FTG HSS6x6x5/16 (TOS = 119'-7 1/2") 29k 176 k-ft 47k 16k W12x26 (16) 273 k-ft CC16 37k 28k W18x86 (26) 41k DG W14x30 CC16 14k CC14 FF5 27k CC14 FF5 W12x16 (16) CC14 FF5 17k 2' - 0" 6' - 0" DF CC14 FF12 W18x76 (78) 36k CC14 FF6 3 17k CC9 FF12 CC14 FF6 28k CC14 FF6 W12x16 (16) 11' - 4" 17k 1 36k 17k W18x76 (78) 37k DE 19k CC16 23k 115'-4" TO FTG 1 16k CC21 CC21 9' - 10" 17k 115'-4" TO FTG W14x26 (30) W14x26 (30) 115'-4" TO FTG STAIR STRINGER RE: LEVEL ABOVE (RE: 35/S5.4) 41 W18x65 31k CC16 CC21 1 23k 24' - 4" CONTROL / CONSTRUCTION JT RE: TYPICAL DETAIL 15/S2.1 AND GENERAL NOTES, TYP. CC9 FF13 S3.3 W24x55 (28) 15' - 4" CC21 CC21 c=1 1/4" CC21 CC14 FF13 1 32 31k 32k 46 W16x26 (26) CC16 CC21 115'-4" TO FTG 16k 60 k-ft 1 2' - 0" W12x16 (16) 16k S3.2 c=1" W18x35 (34) 374 k-ft 71k 47k 268 k-ft c=1 1/4" CC21 HSS6x6x1/4 (TOS = 118'-8 1/2") CC14 FF13 33 k-ft S5.2 2' - 0" S3.4 HSS6x6x1/4 (TOS = 118'-8 1/2") B12 W24x76 7' - 8" W18x35 (34) W18x97 30' - 8" c=1" 2 47k 31k 33 S5.2 S3.4 W16x26 (26) CC16 FF4 CC21 CC16 FTG STEP SEE SHEET S1.1D FOR CONTINUATION c=1" FTG STEP 111'-4" TO FTG CC14 FF13 CC21 W16x31 (30) FTG STEP 41k CC21 14k 12k 19k CC14 FF12 CC21 W12x35 49 k-ft HSS6x6x1/4 (TOS = 118'-8 1/2") 23k CC21 16 16k B12 25k 132 k-ft W18x35 (34) 47k CC16 52 6' - 0" CC21 CC20 HSS6x6x1/4 (TOS = 118'-8 1/2") 32 S3.3 DD FTG STEP 18k S3.4 S3.3 1 23k 115'-4" TO FTG 14 113'-4" TO FTG 23k DC S3.3 32 23k 1 HSS6x6x5/16 (TOS = 119'-7 1/2") 115'-4" TO FTG S3.4 2' - 0" 32 105'-4" TO FTG 14k 101k 639 k-ft 7' - 8" 503 k-ft 81k 256 k-ft 1 FTG STEP W12x16 (16) 24k 180 k-ft 6' - 6 1/4" 66k 514 k-ft 44k 253 k-ft 1 14k S5.4 c=1" W18x65 44k 16' - 0" W24x76 C12 40k LOW 15 16' - 0" W18x86 C10 DB S3.4 HSS8x6x5/16 2k 8k 660 k-ft S5.2 C9 20' - 0" W12x16 (16) 8k W18x86 29' - 8" 47k 14 30k 22k 480 k-ft C8 25' - 4" 35 S5.2 W18x35 (34) 22k 84k 25' - 4" S5.2 13' - 8" CC21 47k 107'-4" TO FTG 17k 32k 29' - 8" CC21 15 DA 109'-4" TO FTG W16x26 (20) 17k W18x40 (30) 51 C7 34 19k 30k 1 W18x35 (34) HSS6x6x1/4 (TOS = 118'-8 1/2") 30k W18x35 (26) 19k 10k W16x26 (26) 31k 38k 36k 38k 21k 22k 40k HSS4x2x3/16 S5.4 2k 30' - 0" C6 W21x44 (46) 38k 35k C5 W16x26 (22) 14k 15k 13 S5.4 W18x35 C3 C4 CC24 49k 32' - 6" S5.2 CC24 16 S5.4 S5.4 14 12k 25' - 7 5/8" 109'-4" TO FTG 14 S5.2 HSS6x6x3/8 15 MECH UNIT PER MECH. MAX WT = 750# W12x19 (20) C2 FTG STEP S3.4 STEP FTG 11 2 6' - 6 1/4" 1' - 6 3/8" 111'-4" TO FTG S5.2 FTG STEP S3.4 SEE SHEET CC21 S1.1C FOR CONTINUATION 10k SPAN C1 9' - 8" S3.4 25 34 W18x97 4' - 5" 115'-4" S3.3 TO FTG S3.4 S3.3 CC21 HSS6x6x1/4 (TOS = 118'-8 1/2") 15' - 4" CM 14 32 33 1 37k 14 32 2' - 0" 6' - 0" CL 10k 26k CC24 22k W14x30 (14) CC21 W14x30 (14) 21k CC21 21k CC21 CC16 FTG STEP W14x30 (14) CC21 HSS6x6x1/4 (TOS = 118'-8 1/2") 21k CC21 HSS6x6x1/4 (TOS = 118'-8 1/2") CC21 107'-4" TO FTG 31k CC21 HSS6x6x1/4 (TOS = 118'-8 1/2") CC16 FF4 32k S3.3 113'-4" TO FTG CC14 FF12 33k CC14 FF11 32 S5.2 25' - 4" D6 D7 D9 19k W18x35 (16) 63k 532 k-ft S5.4 19k 55k 12k 20k 18k 56 15k W18x35 (14)50k S5.4 46 36' - 0" D10 25k 26k 116 k-ft 49k 30k 22k 27k 22k 20k 19k 83 k-ft 38k 31k 21k 27 k-ft 23k 48k 36k 23k 29' - 8" MATCHLINE RE: S1.2E D8 W16x26 (20) 27k STAIR STRINGER RE: LEVEL ABOVE MATCHLINE RE: S1.2D 25' - 4" 30k 16' - 0" B11 W16x77 (26) 1 S5.2 W18x35 (26) 37k W12x19 (20) 16 29' - 8" D5 38k 13k 34 59k W12x19 (20) D4 W18x40 (26) W12x19 (20) D3 30' - 0" ?k W12x19 (20) D2 32' - 6" FTG STEP SEE SHEET S1.1D FOR CONTINUATION W18x35 (26) W12x19 (20) 27' - 2" 107'-4" TO FTG 105'-4" TO FTG 111'-4" TO FTG CC16 W12x19 (20) D1 9' - 8" S5.2 W12x19 (20) 4' - 5" 113'-4" TO FTG CC21 W12x19 (20) DJ CC16 14 CC21 37k 115'-4" TO FTG MECH UNIT PER MECH. MAX WT = 750# 20' - 8" CC21 28k CC21 CC16 FF4 FTG STEP 28k CC21 FTG STEP 27k CC21 CC14 FF13 CC21 28k CC21 CC14 FF12 27k CC14 FF11 HSS4x4x3/16 19k 12k 5k 17 k-ft S5.5 29' - 8" E6 FTG STEP SEE SHEET S1.1E FOR CONTINUATION 16 42 S3.4 S5.2 25' - 4" E7 CC21 54 42 S5.2 S5.2 25' - 4" E8 29' - 8" E9 W14x30 (28) 18k 47k-ft W16x26 (26) 17k 41k-ft 85k JOPLIN HIGH SCHOOL 21k 21k c=1 1/4" c=1 1/4" W16x26 (26) W14x22 (12) 15 33 57k JOPLIN, JASPER COUNTY, MISSOURI 34k 21k 21k 10k W16x26 (10) 21k W12x16 (16) 21k 21k 34k W12x16 (16) W18x35 (32) 30k 7k 7k 36k 34k 98 k-ft 33k 30k 11k W12x16 (10) 11k W14x22 (10) W12x16 12k 11k W12x19 (10) 8k (10) 8k 98 k-ft 33k 21k MATCHLINE RE: S1.2F 34k W16x26 (26) W16x26 (26) W18x55 W16x26 (26) W18x50 (26) c=1 1/4" MATCHLINE RE: S1.2E c=1 1/4" c=1" c=1" W16x26 (26) 7k 8k W12x19 (10) 99 k-ft 48k c=1" SECOND LEVEL FLOOR FRAMING PLAN - AREA E 6k 12k 12k 34k 34k 92 k-ft 33k 30k 92 k-ft 33k 26k 92 k-ft 33k W16x57 33k W18x35 31k W12x16 (16) 20k 31k W18x35 (24) W18x76 (26) E10 W12x16 (26) 12k 12k 22k 20k 19k 12k W12x16 (26) W12x19 (20) W12x19 (20) 21k 23k 31k c=1 1/4" W16x26 (26) 21k W14x30 (32) 27k W14x30 (32) 21k W14x30 (32) 21k 28k 43k W21x48 (36) S5.4 S5.4 20' - 0" 16' - 0" W27x146 (52) 77k E11 16' - 0" 77k C13 G1 E12 D11 2 10-08-12 ADD #3 E5 HSS4x2x3/16 S5.4 7290 West 133rd Street Overland Park, Kansas 66213 tel: (913)897-7811 34 HSS6x6x3/8 16 S5.4 S5.4 Architecture Engineering Planning Interiors E4 15 Revisions E3 30' - 0" EJ 1 10-04-12 ADD #2 32' - 6" HSS12x2x1/4 STRINGER S5.4 13-12102-00 09/10/12 E2 27' - 2" 21 11k E1 9' - 8" 21k 21k 20k W14x30 (32) c=1" CC16 S3.4 4' - 5" 10k W16x26 (10) 10k 37k HSS6x6x1/4 (TOS = 118'-8 1/2") 111'-4" TO FTG 604 k-ft S1.2E 113'-4" TO FTG 11 S5.4 13 CC16 527 k-ft 82k 22k 115'-4" TO FTG 52 k-ft 2 c=3/4" 498 k-ft 22k S3.4 (8) 67k 34k S3.3 8k W16x26 W18x35 (10) 28k W21x83 22k S3.4 c=3/4" 81k W12x19 (20) S3.3 STAIR STRINGER RE: LEVEL ABOVE 228 k-ft 33k 22k S3.4 33k 1k W18x35 (14) 24k 34k S3.3 54k 9' - 4" 22k S3.4 CC21 14k 433 k-ft W12x19 (20) 14 1k 52 k-ft CC16 CC21 W21x68 22k 32 (8) W18x60 2k 11k 14 CC16 CC21 CL FTG HSS6x6x1/4 (TOS = 118'-8 1/2") 27k SPAN 21k 32 W12x19 34k 14 26k CC16 FF21 105'-4" TO FTG 26k 27k W12x19 (20) EL 32 W16x26 (20) 27k S3.4 CC21 14 26k MATCHLINE RE: S1.2G S3.3 W18x60 (26) 24' - 0" 6' - 0" 32 RE:24/S2.1, TYP 28k CC21 EK MECH UNIT PER MECH. MAX WT = 500#, TYP MATCHLINE RE: S1.2E CC21 33 1 2 28k CC21 FTG STEP S3.4 107'-4" TO FTG FTG STEP 28k CC21 CC14 FF13 34 28k CC21 CC14 FF13 CC21 109'-4" TO FTG 28k HSS6x6x1/4 (TOS = 118'-8 1/2") CC14 FF12 CC21 3' - 1" CC21 CC21 W18x60 (26) FTG STEP 2' - 0" HSS6x6x1/4 (TOS = 118'-8 1/2") CC14 FF11 S3.3 CC21 W18x60 (26) 1 HSS6x6x1/4 (TOS = 118'-8 1/2") 32 58k 108'-0" TO FTG 1 2' - 0" SPAN W21x101 (26) 57k 115'-4" TO FTG 1 W16x31 (24) c=1" 115'-4" TO FTG 42k W18x60 (26) 115'-4" TO FTG 28k CC16 115'-4" TO FTG 17k W18x86 (82) 41k EH 1 28k 1 25k CC14 FF5 28k CC16 FF6 1 HSS6x6x5/16 (TOS = 119'-7 1/2") 26k 1 W14x30 (32) CC14 FF5 48k 16k W16x36 10k W12x16 (10) 10k 108'-0" TO FTG 17k 3 CC14 FF5 CC12 FF11 2' - 0" 6' - 0" EG 115'-4" TO FTG 28k 115'-4" TO FTG W14x30 (32) 115'-4" TO FTG 17k 11' - 4" CC16 17k 48k 1 92 k-ft 26k 26k W18x76 (78) 10k W12x16 (10) 10k 37k 98 k-ft W18x76 (78) W18x60 (38) 27k 1 101 k-ft 36k EF 32k 1 CC9 FF12 W12x19 (22) W12x19 (20) 33k 31k CC16 FF6 31k CC14 FF6 23k 9' - 8" 33k STAIR STRINGER RE: LEVEL ABOVE (RE: 35/S5.4) CC14 FF6 10' - 0" 25k S3.3 CC14 FF6 23k CC9 FF13 10' - 0" 28k 1 32 8' - 4" W16x26 (26) 24' - 4" CONTROL / CONSTRUCTION JT RE: TYPICAL DETAIL 15/S2.1 AND GENERAL NOTES, TYP. 8' - 4" W16x26 (20) 23k 9' - 4" 20k 8' - 2" 28k 8' - 0" CC16 31k 115'-4" TO FTG 8' - 0" 98 k-ft 1 FTG STEP SEE SHEET S1.1E FOR CONTINUATION CC16 FF21 CC21 CC21 W16x45 CL FTG CC16 CC21 23k 13k S3.4 CC21 CC21 W16x31 (40) CC14 FF13 CC21 8' - 0" W24x68 (48) 42 k-ft 35k CC21 109'-4" TO FTG 34 W16x31 (24) c=1 1/4" S3.4 8' - 0" 40k W18x76 (62) CC16 S5.2 HSS6x6x1/4 (TOS = 118'-8 1/2") 1 53 10' - 0" 31k CC14 FF13 37k S5.2 W18x76 (90) 33 HSS6x6x1/4 (TOS = 118'-8 1/2") S3.4 W16x26 (26) S3.4 CC21 CC21 CC14 FF13 34 32k FTG STEP CC21 25k CC21 28k HSS6x6x1/4 (TOS = 118'-8 1/2") 55 W14x48 (48) CC20 10' - 0" W14x48 (48) CC21 CC14 FF13 HSS6x6x1/4 (TOS = 118'-8 1/2") CC16 11k 1 23k CC14 FF12 S3.3 ED CC21 105'-4" TO FTG 24k 6' - 0" S3.4 25 32 2' - 0" S3.4 CC21 14 2' - 0" 115'-4" TO FTG 14 S3.3 115'-4" TO FTG 32 HSS6x6x1/4 S3.3 (TOS = 118'-8 1/2") 3' - 1" EC 14 S3.4 W14x48 (48) HSS6x6x5/16 (TOS = 119'-7 1/2") 32 107'-4" TO FTG FTG STEP 2' - 0" 1 113'-4" TO FTG W12x19 (20) FTG STEP 24k 1 20' - 10 1/2" 1 136 k-ft 12k W12x19 (34) SPAN 111'-4" TO FTG 264 k-ft 162 k-ft 22k 1 61k 23k 13k 43 k-ft 6k 63 k-ft W12x19 (20) 122 k-ft 18k W14x30 (34) 7k W12x19 (20) 12k W12x19 (20) W12x19 (20) 19k 21k W27x129 20k 19k 21k 23k 23k 473 k-ft 13k 413 k-ft 18k 25k W12x26 72k W12x19 (20) 19' - 9 1/2" 12k W30x148 67k EB HSS16x4x3/8 STAIR STRINGER 244 k-ft 18k 18k W12x19 (20) 18k 62 k-ft 62k 32k 20k W12x19 (20) 20k W27x102 14 7k 22k W12x19 (20) 22k S5.4 12k 22k W12x19 (20) 22k 122 k-ft 19k 12k 18k 15 12k 25k W12x26 472 k-ft W12x19 (20) 408 k-ft 22k 72k 20k W30x148 19k 21k 23k 66k 21k EA 23k 13k HSS4x2x3/16 G2 B 1 KEY NOTES: PLAN NOTES: A. FINISHED FLOOR ELEVATION IS 116'-0", UNLESS NOTED OTHERWISE. B. TOP OF STEEL ELEVATION IS TYPICALLY 115'-6", UNLESS NOTED OTHERWISE ON PLANS AND SECTIONS. TOP OF STEEL THAT OCCURS ON A SLOPE AND IS NOT SPECIFICALLY NOTED ON THE PLANS SHALL BE LINEARLY INTERPOLATED FROM TOP OF STEEL NOTED ON THE PLANS. C. SEE SHEET S4.1 AND S4.2 "FLOOR FRAMING TYPICAL DETAILS" FOR ADDITIONAL FRAMING REQUIREMENTS AND INFORMATION. D. JOIST SUPPLIER TO COORDINATE WITH MECHANICAL CONTRACTOR FOR RTU WEIGHTS, LOCATIONS AND PENETRATIONS. E. JOIST SUPPLIER SHALL DESIGN JOISTS FOR ALL LOADS INDICATED IN S0.1 & S0.2 'GENERAL NOTES', S0.3 'ROOF SNOW DRIFT PLAN', ON THE PLAN SHEETS, AND THE SECTION/DETAIL SHEETS. CONTRACTOR TO COORDINATE ALL WEIGHTS, LOCATIONS, AND PENETRATIONS OF EQUIPMENT WITH THE JOIST SUPPLIER PRIOR TO SUBMITTING JOIST SHOP DRAWINGS. G. SEE ARCHITECTURAL DRAWINGS FOR LOCATION OF SLOPED, RAISED, DEPRESSED SLABS AND DRAINS. M. ALL PRECAST CONNECTIONS SHALL BE DESIGNED BY THE PRECAST SUPPLIER. T. COORDINATE ALL PENETRATIONS THRU CONTINUOUS FOOTINGS WITH MEP DRAWINGS. REFERENCE TYPICAL DETAILS 34/S2.1 & 41/S2.1. H. REFER TO ARCHITECTURAL DRAWINGS FOR OVERALL BUILDING GEOMETRY, WALL LOCATIONS, STAIR GEOMETRY AND ADDITIONAL PARTITION WALL REQUIREMENTS. N. ALL HSS MEMBERS SHALL HAVE 1/4" CAP PLATES AT ENDS. U. ALL EXTERIOR EXPOSED STEEL SHALL BE GALVANIZED. J. REFER TO ARCHITECTURAL DRAWINGS FOR NON-LOAD BEARING PARTITION WALLS. REFER TO SHEETS S0.1, S0.2, S2.1, S2.2, AND S9.2 TYPICAL DETAILS FOR REINFORCING, THICKENED SLABS AND OTHER REQUIREMENTS. K. ALL OPENINGS IN CMU WALLS (PARTITION AND LOAD BEARING) REQUIRE A LINTEL. REFER TO SHEET S9.2 FOR TYPICAL MASONRY LINTEL DETAILS AND SCHEDULES. L. SEE SHEET S6.1 AND S6.2 "ROOF FRAMING TYPICAL DETAILS" FOR ADDITIONAL REQUIREMENTS AND INFORMATION. O. P. PROVIDE HSS3 1/2x2 1/2x1/4 (LLH) BETWEEN ALL JOIST WITH 2 1/2" SEATS TO SUPPORT ROOF DECK WHERE DECK SWITCHES DIRECTION. (RE: 44/S6.1) REFER TO SPECIFICATIONS FOR ALL SUBGRADE PREPARATION REQUIREMENTS. Q. SEE SHEET S2.1 AND S2.2 "TYPICAL FOUNDATION SECTIONS" FOR ADDITIONAL REQUIREMENTS AND INFORMATION. R. REFER TO 52/S2.1 FOR COLUMN AND FOOTING SCHEDULES. S. REFER TO ARCHITECTURAL DRAWINGS FOR PRECAST JOINT LOCATIONS. VERIFY JOINT LOCATIONS WITH PRECASTER. V. COORDINATE ALL FOOTING STEP LOCATIONS AND BRICK LEDGES WITH ARCHITECTURAL ELEVATIONS. 1 2 C 6 6" NORMAL WEIGHT AIR ENTRAINED CONCRETE SLAB-ON-GRADE REINFORCE WITH #4 @ 12"OC EACH WAY ON 15 MIL VAPOR RETARDER OVER 4" GRANULAR FILL. 1 1/2" DEEP, 20 GAGE, GALVANIZED WIDE RIB STEEL ROOF DECK. PROVIDE 5/8" DIAMETER PUBBLE WELDS IN 36/5 PATTERN AND 2 #10 TEK SCREWS AT SIDELAPS PER SPAN. 7 8" HOLLOW CORE WITH 2" TOPPING SLAB. REINFORCE TOPPING SLAB WITH 6x6/W2.1xW2.1 WELDED WIRE REINFORCEMENT. PRECAST SUPPLIER TO DESIGN FOR 125 PSF. 4" NORMAL WEIGHT CONCRETE SLAB-ON-GRADE W/ 6x6-W2.1xW2.1 WELDED WIRE REINFORCEMENT ON 15 MIL VAPOR RETARDER OVER 4" GRANULAR FILL. 8 12" CMU WALL REINFORCE PER GENERAL NOTES, UNLESS NOTED OTHERWISE. 9 8" CMU WALL REINFORCE PER GENERAL NOTES, UNLESS NOTED OTHERWISE. 3" NORMAL WEIGHT CONCRETE SLAB ON 3" DEEP, 20 GAGE, GALVANIZED COMPOSITE STEEL FLOOR DECK (6" TOTAL THICKNESS). REINFORCE WITH 6x6/W2.1xW2.1 WELDED WIRE REINFORCEMENT. 2 D 2 W. DENOTES FEMA 361 SAFE ROOM AREA. REFER TO TYPICAL DETAILS (ON S4.3) AND GENERAL NOTES. 3 4 6" NORMAL WEIGHT CONCRETE SLAB ON 3" DEEP, 20 GAGE, GALVANIZED COMPOSITE STEEL FLOOR DECK (9" TOTAL THICKNESS). REINFORCE WITH 6x6/W2.1xW2.1 WELDED WIRE REINFORCEMENT. 5 DOWEL FOOTING AND WALL TOGETHER WITH 2-#6, TOP & BOTTTOM. PROVIDE 'CLASS B' LAP SPLICE. HOOK BARS 1'-0" INTO WALL. SECOND LEVEL FRAMING PLAN - AREA E F K E G L H J SCALE: 1/8" = 1'-0" BENJAMIN TALPOS 10/8/2012 6:13:34 PM C:\Users\BrionP\Documents\9-2013-Revit Projects\Joplin\13-12102-00_central_struct_2012.rvt A NORTH NORTH © 2012, DLR Group of Missouri inc., a Missouri corporation CA No. 001614, ALL RIGHTS RESERVED. KEY PLAN W14 W18x60 (26) 10" 1' - 6" 10' - 0" 44k 51 k-ft 15k 25k W21x48 (48) 24' - 0" W12x26 47 k-ft 15k 51k 24' - 0" 56 k-ft 16k W24x55 (44) W12x26 W12x19 (20) 25k 25k 25k 1 70k 51k 121 k-ft 24k 34k 34k 40k J. REFER TO ARCHITECTURAL DRAWINGS FOR NON-LOAD BEARING PARTITION WALLS. REFER TO SHEETS S0.1, S0.2, S2.1, S2.2, AND S9.2 TYPICAL DETAILS FOR REINFORCING, THICKENED SLABS AND OTHER REQUIREMENTS. K. ALL OPENINGS IN CMU WALLS (PARTITION AND LOAD BEARING) REQUIRE A LINTEL. REFER TO SHEET S9.2 FOR TYPICAL MASONRY LINTEL DETAILS AND SCHEDULES. L. SEE SHEET S6.1 AND S6.2 "ROOF FRAMING TYPICAL DETAILS" FOR ADDITIONAL REQUIREMENTS AND INFORMATION. M. ALL PRECAST CONNECTIONS SHALL BE DESIGNED BY THE PRECAST SUPPLIER. N. ALL HSS MEMBERS SHALL HAVE 1/4" CAP PLATES AT ENDS. O. PROVIDE HSS3 1/2x2 1/2x1/4 (LLH) BETWEEN ALL JOIST WITH 2 1/2" SEATS TO SUPPORT ROOF DECK WHERE DECK SWITCHES DIRECTION. (RE: 44/S6.1) P. REFER TO SPECIFICATIONS FOR ALL SUBGRADE PREPARATION REQUIREMENTS. Q. SEE SHEET S2.1 AND S2.2 "TYPICAL FOUNDATION SECTIONS" FOR ADDITIONAL REQUIREMENTS AND INFORMATION. R. REFER TO 52/S2.1 FOR COLUMN AND FOOTING SCHEDULES. S. REFER TO ARCHITECTURAL DRAWINGS FOR PRECAST JOINT LOCATIONS. VERIFY JOINT LOCATIONS WITH PRECASTER. T. COORDINATE ALL PENETRATIONS THRU CONTINUOUS FOOTINGS WITH MEP DRAWINGS. REFERENCE TYPICAL DETAILS 34/S2.1 & 41/S2.1. U. ALL EXTERIOR EXPOSED STEEL SHALL BE GALVANIZED. V. COORDINATE ALL FOOTING STEP LOCATIONS AND BRICK LEDGES WITH ARCHITECTURAL ELEVATIONS. W. DENOTES FEMA 361 SAFE ROOM AREA. REFER TO TYPICAL DETAILS (ON S4.3) AND GENERAL NOTES. 1 3" NORMAL WEIGHT CONCRETE SLAB ON 3" DEEP, 20 GAGE, GALVANIZED COMPOSITE STEEL FLOOR DECK (6" TOTAL THICKNESS). REINFORCE WITH 6x6/W2.1xW2.1 WELDED WIRE REINFORCEMENT. 2 1 1/2" DEEP, 20 GAGE, GALVANIZED WIDE RIB STEEL ROOF DECK. PROVIDE 5/8" DIAMETER PUBBLE WELDS IN 36/5 PATTERN AND 2 #10 TEK SCREWS AT SIDELAPS PER SPAN. 3 4" NORMAL WEIGHT CONCRETE SLAB-ON-GRADE W/ 6x6-W2.1xW2.1 WELDED WIRE REINFORCEMENT ON 15 MIL VAPOR RETARDER OVER 4" GRANULAR FILL. 4 6" NORMAL WEIGHT CONCRETE SLAB ON 3" DEEP, 20 GAGE, GALVANIZED COMPOSITE STEEL FLOOR DECK (9" TOTAL THICKNESS). REINFORCE WITH 6x6/W2.1xW2.1 WELDED WIRE REINFORCEMENT. 5 DOWEL FOOTING AND WALL TOGETHER WITH 2-#6, TOP & BOTTTOM. PROVIDE 'CLASS B' LAP SPLICE. HOOK BARS 1'-0" INTO WALL. 6 6" NORMAL WEIGHT AIR ENTRAINED CONCRETE SLAB-ON-GRADE REINFORCE WITH #4 @ 12"OC EACH WAY ON 15 MIL VAPOR RETARDER OVER 4" GRANULAR FILL. 7 8" HOLLOW CORE WITH 2" TOPPING SLAB. REINFORCE TOPPING SLAB WITH 6x6/W2.1xW2.1 WELDED WIRE REINFORCEMENT. PRECAST SUPPLIER TO DESIGN FOR 125 PSF. 8 12" CMU WALL REINFORCE PER GENERAL NOTES, UNLESS NOTED OTHERWISE. 9 8" CMU WALL REINFORCE PER GENERAL NOTES, UNLESS NOTED OTHERWISE. 51k 2 35 S8.5 49k 51k 59k 40k 51k 13k KH W12x26 (30) HSS6x6x5/16 (TOS = 115'-1 1/2") 49k 13k 24' - 0" W21x48 (48) 21k W12x16 (16) 21k 21k W12x16 (16) 21k W21x48 (48) 24' - 0" W14x53 79 k-ft 21k c=1 1/4" W16x26 (26) 34k c=1 1/4" W16x26 (26) 34k c=1 1/4 W16x26 (26) 34k W12x16 (16) 21k 21k REFER TO ARCHITECTURAL DRAWINGS FOR OVERALL BUILDING GEOMETRY, WALL LOCATIONS, STAIR GEOMETRY AND ADDITIONAL PARTITION WALL REQUIREMENTS. 49k 49k 186 k-ft W12x26 (30) 21k 604 k-ft 21k 21k EG W21x122 H. KEY NOTES: 287 k-ft 34k 136 k-ft 162 k-ft 36k W16x57 MATCHLINE RE: S1.2F MATCHLINE RE: S1.2E 34k 21k 527 k-ft 82k SEE ARCHITECTURAL DRAWINGS FOR LOCATION OF SLOPED, RAISED, DEPRESSED SLABS AND DRAINS. 51k 50 k-ft 15k 25k 25k W12x19 (20) W12x19 (20) W12x30 (40) 32k 34k 34k 498 k-ft 67k G. 49k KG EF REFER TO GENERAL NOTES SHEETS S0.1 AND S0.2 FOR GENERAL NOTES, ABBREVIATIONS AND SYMBOLS. 51k 47 k-ft 15k 24k 24k 24k W12x19 (20) W12x19 (20) W12x19 (20) 25k 23k 6k W14x30 (28) 6k 12k 40k KF ED 2 10-08-12 ADD #3 7290 West 133rd Street Overland Park, Kansas 66213 tel: (913)897-7811 13k B W18x46 K1 F2 K2 D F K E G L H SECOND LEVEL FRAMING PLAN - AREA F J SCALE: 1/8" = 1'-0" NORTH NORTH © 2012, DLR Group of Missouri inc., a Missouri corporation CA No. 001614, ALL RIGHTS RESERVED. A C BENJAMIN TALPOS Architecture Engineering Planning Interiors W24x55 LINTEL W14x30 KEY PLAN 26' - 0" MATCHLINE RE: S1.2G 37' - 4" 10/8/2012 6:13:42 PM Revisions MATCHLINE RE: S1.2F KL F1 1 10-04-12 ADD #2 10k 10k 20k 40k 13-12102-00 09/10/12 51k 2' - 7" 14' - 5" W16x26 (16) W18x35 (16) 35k EJ 25k-ft 10k W16x26 (26) 34k KK 85k 22k 22k 22k KJ W16x26 24k-ft 10k W18x35 (16) c=1 1/4" c=1 1/4" W18x35 (26) 34k 34k W24x84 (64) 85k 22k 57k 22k c=1 1/4" 21k 18k 47k-ft W16x26 17k 41k-ft 34k EK EL SPAN W18x35 (26) W16x26 (18) c=1 1/4" W16x26 (26) 10k 10k 1 S1.2F 49k EH C:\Users\BrionP\Documents\9-2013-Revit Projects\Joplin\13-12102-00_central_struct_2012.rvt 49k 2 SPAN 433 k-ft F. JOPLIN, JASPER COUNTY, MISSOURI W21x48 (48) 24' - 0" W12x26 45k 36k KE 228 k-ft W27x146 JOIST SUPPLIER SHALL DESIGN JOISTS FOR ALL LOADS INDICATED IN S0.1 & S0.2 'GENERAL NOTES', S0.3 'ROOF SNOW DRIFT PLAN', ON THE PLAN SHEETS, AND THE SECTION/DETAIL SHEETS. CONTRACTOR TO COORDINATE ALL WEIGHTS, LOCATIONS, AND PENETRATIONS OF EQUIPMENT WITH THE JOIST SUPPLIER PRIOR TO SUBMITTING JOIST SHOP DRAWINGS. 5' - 0" 35k 41k 50 k-ft 15k 36k 61k 264 k-ft 81k E. 5' - 0" 1 W24x55 2' - 7" KD 1 54k JOIST SUPPLIER TO COORDINATE WITH MECHANICAL CONTRACTOR FOR RTU WEIGHTS, LOCATIONS AND PENETRATIONS. 26k KC 14k 12k W21x68 W27x129 61k 13k 43 k-ft W24x68 (48) EC 24k 18k W12x19 (20) W14x30 (34) 7k W27x129 D. 14' - 6" 8' - 0" 36k 49k EB SEE SHEET S4.1 AND S4.2 "FLOOR FRAMING TYPICAL DETAILS" FOR ADDITIONAL FRAMING REQUIREMENTS AND INFORMATION. 8' - 0" 43k 45k W21x44 (40) W12x22 (26) 8k 210 k-ft 26k W30x99 (26) 25k 8k 13k W12x22 (26) 6' - 6 1/4" 13k 183 k-ft 32k 16' - 0" W16x36 (26) W12x22 (26) 15k 6' - 6 1/4" 15k 17k 17k W12x22 (26) 8' - 3" F4 36 k-ft 12k 34k 25k 26k W30x99 (26) 210 k-ft 10' - 0" W16x36 F3 265 k-ft 24k 18k 32k KA 183 k-ft KB 62k 244 k-ft 24k 5k 17 k-ft C. 9' - 4" W27x102 62k W30x99 (26) TOP OF STEEL ELEVATION IS TYPICALLY 115'-6", UNLESS NOTED OTHERWISE ON PLANS AND SECTIONS. TOP OF STEEL THAT OCCURS ON A SLOPE AND IS NOT SPECIFICALLY NOTED ON THE PLANS SHALL BE LINEARLY INTERPOLATED FROM TOP OF STEEL NOTED ON THE PLANS. 239 k-ft W12x19 (20) W12x19 (20) 25k 9' - 4" 25k 19k 12k W27x102 7k 9' - 4" 1 17k 172 k-ft 30k 68k 25k 25k W12x19 (20) W12x19 (20) W16x77 (26) 19k 55k 532 k-ft 8' - 4 5/8" 17k 106 k-ft 18k W30x99 17k 16k 16k 17k 3 k-ft 4k 16 k-ft 10k FA W27x129 63k 9' - 4" EA 34k 34k 20k 18k 25k DJ 56 15k W18x35 (14)50k S5.4 8' - 3" W12x22 (26) W16x36 (26) 8' - 3" W30x99 (26) SPAN DH 19k 17k 30k 172 k-ft 7' - 8" W12x22 (26) W12x22 (26) c=1" W16x26 (26) W16x26 (26) W16x26 (26) W16x26 (30) c=1" c=3/4" c=3/4" W16x26 (14) c=1" 7' - 8" D12 18k 106 k-ft 16k 4k W30x99 (26) 3 k-ft 16k 17k 50k 34k W24x68 (50) 34k 34k 50k 23k 50k B. 15' - 4" 15k W18x60 ? k-ft FINISHED FLOOR ELEVATION IS 116'-0", UNLESS NOTED OTHERWISE. JOPLIN HIGH SCHOOL 33' - 1 5/8" MATCHLINE RE: S1.2F 15' - 4" MATCHLINE RE: S1.2K 37' - 4" MATCHLINE RE: S1.2F 6k 27 k-ft 10k 25k 19k W14x26 (30) W12x16 (26) A. SECOND LEVEL FLOOR FRAMING PLAN - AREA F 6k 106 k-ft MATCHLINE RE: S1.2D DF DG PLAN NOTES: 10k 10k 158 k-ft 18k 18k 6k 253 k-ft 48k 24k 19k DE c=1 1/4" c=1 1/4" W18x35 (26) W16x26 (26) 34k 34k 25k-ft 10k c=1 1/4" W18x35 (26) 34k 17k 41k-ft 24k-ft 10k W18x35 (16) 21k 18k 47k-ft W16x26 13k 22k 22k 22k 22k c=1 1/4" 22k W18x35 (20) W12x19 (20) 22k 58k 249k-ft W24x84 (64) 13k W18x35 (20) 78k 617k-ft 22k 22k W18x35 (20) W12x19 (20) 22k W12x19 (20) 45k 297k-ft W21x68 35k-ft 12k 22k 22k 22k 22k CC22 W12x26 42k W18x35 W12x19 (20) 22k 35k-ft 22k W12x19 (20) 68k 22k WT8x13 22k WT8x13 4' - 10" W18x35 (20) 13k 23k W12x19 (20) W12x19 (20) 22k W18x35 (20) 4' - 10" 4' - 10" 4' - 10" W18x40 11k 21k-ft 4' - 10" 2' - 11" 3' - 0" 20K4 20K4 20K4 20K4 20K4 20K4 20K4 20K4 20K4 82k MATCHLINE RE: S1.2G MATCHLINE RE: S1.2H MATCHLINE RE: S1.2H 4k MATCHLINE RE: S1.2G W16x45 HA 9 18' - 2 1/2" 16' - 0" 17' - 1 1/2" 26' - 10 1/2" 20' - 9" 3k 16' - 7" 23' - 4" 1 G1 E12 D11 F1 G3 F2 H9 S1.2G G2 2 10-08-12 ADD #3 W27x146 (52) 20K4 W16x26 (4) 20K4 W16x26 (10) W12x30 W16x26 (10) 30' - 2 5/8" SPAN 22k W18x35 (20) W12x19 (20) 4' - 10" 2 22K6 2' - 0" 4' - 0" 6 19k 21k-ft SPAN 82k S3.4 4' - 10" 85k S3.5 8" 8" c=3/4" 4' - 10" S3.4 6' - 0" 2' - 0" 8' - 10 5/8" 13 4' - 0" W27x129 (52) 85k 13 51 30k 123k-ft W18x40 7290 West 133rd Street Overland Park, Kansas 66213 tel: (913)897-7811 4' - 8 1/2" 24' - 0" 111'-0" TO FTG 30k 123k-ft 4k 4' - 0" 5' - 0" 22k 229k-ft W21x57 CC22 8" 21' - 0" 89k 229k-ft Architecture Engineering Planning Interiors 86k Revisions GD c=3/4" 1 10-04-12 ADD #2 W27x129 (52) 86k CC22 22k 12k 7' - 3" 22k 86k 22k 20' - 4" c=3/4" W12x19 (20) W27x129 (52) 86k W18x35 (20) CC22 13-12102-00 09/10/12 12k W24x84 (64) 68k JOPLIN, JASPER COUNTY, MISSOURI 44k-ft 22k 22k 22k 22k 72k-ft 22k W18x40 (42) JOPLIN HIGH SCHOOL 44k-ft 13k 22k 22k 22k CC22 SECOND LEVEL FLOOR FRAMING PLAN - AREA G 45k 13k 85k 23k GC c=3/4" 22k W27x129 (52) 12k 37k-ft 1 SPAN 22k 85k W12x26 20' - 0" c=3/4" 111'-0" TO FTG 85k 67k 1 W18x35 (20) W27x129 (52) 85k W24x84 (64) 67k 22k 4 S3.4 41k SPAN 2' - 0" 54 12k 37k-ft CC22 W18x40 (42) W18x35 S3.4 CC22 44k 72k-ft 22k 51 22k GB STEP BOT OF FTG W12x19 (20) 85k 22k c=3/4" W12x19 (20) W27x129 (52) 22k 85k 46 S3.5 W12x19 (20) 85k W12x19 (20) c=3/4" W12x19 (20) W27x129 (52) 11k 2' - 0" S3.4 4' - 7" 52 42k 207k-ft SPAN 4' - 0" 56 85k 10' - 0" 20' - 0" 6 8" S3.4 85k CC22 4' - 0" 111'-0" TO FTG 2' - 0" c=3/4" 37' - 4" 8" 2' - 0" S3.4 85k S3.4 111'-0" TO FTG STEP BOT OF FTG W27x129 (52) 85k 6' - 8" 52 34k 34k 77k C13 11k 15' - 3" 13 GA 22k 28' - 0" W27x146 (52) 77k E11 16' - 0" 11k 2 W16x26 (26) W14x22 (12) W18x35 (24) 16' - 0" 1 36' 1 - 2" c=1 1/4" c=1" E10 E9 20' - 0" W12x19 (20) E8 MATCHLINE RE: S1.2G S5.4 22k E7 29' - 8" W24x84 (64) 85k MATCHLINE RE: S1.2F S5.4 22k 25' - 4" 15 33 22k S5.2 W16x26 (26) 21k W18x76 (26) W18x60 (26) S5.2 25' - 4" E6 42 57k 22k S5.2 54 W12x19 (20) S3.4 CC21 22k E5 29' - 8" 42 22k 30' - 0" 16 W12x19 (20) S3.4 FTG STEP SEE SHEET S1.1E FOR CONTINUATION 22k 34 22k CC16 W18x35 (20) 111'-4" TO FTG 22k 113'-4" TO FTG W21x48 (36) 22k 115'-4" TO FTG CC16 HSS6x6x1/4 (TOS = 118'-8 1/2") 11k S3.4 W12x19 (20) S3.3 W12x19 (20) S3.4 HSS4x2x3/16 21k S3.3 HSS6x6x3/8 16 S5.4 S5.4 S5.4 34k S3.4 CC21 31k S3.3 CC21 15 13 35k 14 HSS12x2x1/4 STRINGER CC16 MATCHLINE RE: S1.2G 32 CC16 CC21 CL FTG HSS6x6x1/4 (TOS = 118'-8 1/2") 20' - 0" 14 105'-4" TO FTG 28k 32 CC16 FF21 MATCHLINE RE: S1.2E EL 14 RE:24/S2.1, TYP S3.4 CC21 32 MECH UNIT PER MECH. MAX WT = 500#, TYP 28k CC21 EK S3.4 33 1 28k CC21 FTG STEP 107'-4" TO FTG FTG STEP 28k CC21 CC14 FF13 34 28k CC14 FF13 CC21 109'-4" TO FTG 3' - 1" CC21 CC21 2' - 0" HSS6x6x1/4 (TOS = 118'-8 1/2") CC14 FF12 CC21 W18x60 (26) FTG STEP HSS6x6x1/4 (TOS = 118'-8 1/2") W18x60 (26) 1 W18x60 (26) 1 2 B 1 KEY NOTES: PLAN NOTES: A. FINISHED FLOOR ELEVATION IS 116'-0", UNLESS NOTED OTHERWISE. B. TOP OF STEEL ELEVATION IS TYPICALLY 115'-6", UNLESS NOTED OTHERWISE ON PLANS AND SECTIONS. TOP OF STEEL THAT OCCURS ON A SLOPE AND IS NOT SPECIFICALLY NOTED ON THE PLANS SHALL BE LINEARLY INTERPOLATED FROM TOP OF STEEL NOTED ON THE PLANS. C. SEE SHEET S4.1 AND S4.2 "FLOOR FRAMING TYPICAL DETAILS" FOR ADDITIONAL FRAMING REQUIREMENTS AND INFORMATION. D. JOIST SUPPLIER TO COORDINATE WITH MECHANICAL CONTRACTOR FOR RTU WEIGHTS, LOCATIONS AND PENETRATIONS. E. JOIST SUPPLIER SHALL DESIGN JOISTS FOR ALL LOADS INDICATED IN S0.1 & S0.2 'GENERAL NOTES', S0.3 'ROOF SNOW DRIFT PLAN', ON THE PLAN SHEETS, AND THE SECTION/DETAIL SHEETS. CONTRACTOR TO COORDINATE ALL WEIGHTS, LOCATIONS, AND PENETRATIONS OF EQUIPMENT WITH THE JOIST SUPPLIER PRIOR TO SUBMITTING JOIST SHOP DRAWINGS. G. SEE ARCHITECTURAL DRAWINGS FOR LOCATION OF SLOPED, RAISED, DEPRESSED SLABS AND DRAINS. M. ALL PRECAST CONNECTIONS SHALL BE DESIGNED BY THE PRECAST SUPPLIER. T. COORDINATE ALL PENETRATIONS THRU CONTINUOUS FOOTINGS WITH MEP DRAWINGS. REFERENCE TYPICAL DETAILS 34/S2.1 & 41/S2.1. H. REFER TO ARCHITECTURAL DRAWINGS FOR OVERALL BUILDING GEOMETRY, WALL LOCATIONS, STAIR GEOMETRY AND ADDITIONAL PARTITION WALL REQUIREMENTS. N. ALL HSS MEMBERS SHALL HAVE 1/4" CAP PLATES AT ENDS. U. ALL EXTERIOR EXPOSED STEEL SHALL BE GALVANIZED. J. REFER TO ARCHITECTURAL DRAWINGS FOR NON-LOAD BEARING PARTITION WALLS. REFER TO SHEETS S0.1, S0.2, S2.1, S2.2, AND S9.2 TYPICAL DETAILS FOR REINFORCING, THICKENED SLABS AND OTHER REQUIREMENTS. K. ALL OPENINGS IN CMU WALLS (PARTITION AND LOAD BEARING) REQUIRE A LINTEL. REFER TO SHEET S9.2 FOR TYPICAL MASONRY LINTEL DETAILS AND SCHEDULES. L. SEE SHEET S6.1 AND S6.2 "ROOF FRAMING TYPICAL DETAILS" FOR ADDITIONAL REQUIREMENTS AND INFORMATION. O. P. PROVIDE HSS3 1/2x2 1/2x1/4 (LLH) BETWEEN ALL JOIST WITH 2 1/2" SEATS TO SUPPORT ROOF DECK WHERE DECK SWITCHES DIRECTION. (RE: 44/S6.1) REFER TO SPECIFICATIONS FOR ALL SUBGRADE PREPARATION REQUIREMENTS. Q. SEE SHEET S2.1 AND S2.2 "TYPICAL FOUNDATION SECTIONS" FOR ADDITIONAL REQUIREMENTS AND INFORMATION. R. REFER TO 52/S2.1 FOR COLUMN AND FOOTING SCHEDULES. S. REFER TO ARCHITECTURAL DRAWINGS FOR PRECAST JOINT LOCATIONS. VERIFY JOINT LOCATIONS WITH PRECASTER. V. COORDINATE ALL FOOTING STEP LOCATIONS AND BRICK LEDGES WITH ARCHITECTURAL ELEVATIONS. 1 2 C 6 6" NORMAL WEIGHT AIR ENTRAINED CONCRETE SLAB-ON-GRADE REINFORCE WITH #4 @ 12"OC EACH WAY ON 15 MIL VAPOR RETARDER OVER 4" GRANULAR FILL. 1 1/2" DEEP, 20 GAGE, GALVANIZED WIDE RIB STEEL ROOF DECK. PROVIDE 5/8" DIAMETER PUBBLE WELDS IN 36/5 PATTERN AND 2 #10 TEK SCREWS AT SIDELAPS PER SPAN. 7 8" HOLLOW CORE WITH 2" TOPPING SLAB. REINFORCE TOPPING SLAB WITH 6x6/W2.1xW2.1 WELDED WIRE REINFORCEMENT. PRECAST SUPPLIER TO DESIGN FOR 125 PSF. 4" NORMAL WEIGHT CONCRETE SLAB-ON-GRADE W/ 6x6-W2.1xW2.1 WELDED WIRE REINFORCEMENT ON 15 MIL VAPOR RETARDER OVER 4" GRANULAR FILL. 8 12" CMU WALL REINFORCE PER GENERAL NOTES, UNLESS NOTED OTHERWISE. 9 8" CMU WALL REINFORCE PER GENERAL NOTES, UNLESS NOTED OTHERWISE. 3" NORMAL WEIGHT CONCRETE SLAB ON 3" DEEP, 20 GAGE, GALVANIZED COMPOSITE STEEL FLOOR DECK (6" TOTAL THICKNESS). REINFORCE WITH 6x6/W2.1xW2.1 WELDED WIRE REINFORCEMENT. 2 W. DENOTES FEMA 361 SAFE ROOM AREA. REFER TO TYPICAL DETAILS (ON S4.3) AND GENERAL NOTES. 3 4 6" NORMAL WEIGHT CONCRETE SLAB ON 3" DEEP, 20 GAGE, GALVANIZED COMPOSITE STEEL FLOOR DECK (9" TOTAL THICKNESS). REINFORCE WITH 6x6/W2.1xW2.1 WELDED WIRE REINFORCEMENT. 5 DOWEL FOOTING AND WALL TOGETHER WITH 2-#6, TOP & BOTTTOM. PROVIDE 'CLASS B' LAP SPLICE. HOOK BARS 1'-0" INTO WALL. 2 D SECOND LEVEL FRAMING PLAN - AREA G F K E G L H J SCALE: 1/8" = 1'-0" BENJAMIN TALPOS 10/8/2012 6:13:50 PM C:\Users\BrionP\Documents\9-2013-Revit Projects\Joplin\13-12102-00_central_struct_2012.rvt A NORTH NORTH © 2012, DLR Group of Missouri inc., a Missouri corporation CA No. 001614, ALL RIGHTS RESERVED. KEY PLAN 8" 13 6 SPAN S3.4 20K 20K 20K 20K 20K 20K 20K 20K 20K 20K 82k MATCHLINE RE: S1.2G MATCHLINE RE: S1.2G MATCHLINE RE: S1.2H MATCHLINE RE: S1.2H 4k 4' - 0" 20K 22K 82k W16x45 HA 9 18' - 2 1/2" 16' - 0" 17' - 1 1/2" 26' - 10 1/2" 20' - 9" 3k 16' - 7" 23' - 4" 1 G1 E12 D11 2 4' - 8" 4' - 8" 4' - 8" 4' - 8" W18x40 27k 4' - 10" 4' - 10" 4' - 10" 4' - 4 1/8" 4' - 10" 4' - 4" 4' - 4" W18x40 28k 4' - 4" 4' - 5 1/2" W18x50 4' - 10 1/2" 20k 4' - 4" 4' - 4" 4' - 4" 4' - 8 1/8" 4' - 6 1/4" W18x50 21k 4' - 6 1/4" 4' - 6 1/4" W18x50 11k 4' - 10 1/2" 4' - 10 1/2" 4' - 10 1/2" 4' - 10 1/2" 4' - 10 1/2" 4' - 10 1/2" W12x22 14K1 14K1 14K1 14K1 14K1 14K1 14K1 14K1 14K1 14K1 14K1 14K1 14K1 14K1 14K1 14K1 14K1 14K1 14K1 14K1 14K1 14K1 14K1 4' - 10" F2 4' - 11 1/2" W24x68 34k 34k 9k-ft 3k HB 14K1 14K1 14K1 14KSP 4' - 8" G3 3k 4' - 8" 14KSP 14KSP 19' - 5 3/8" F1 2 SPAN 33 S5.3 S5.3 S5.3 2 MECH UNIT PER MECH. MAX WT = 500#, TYP 31k H7 35 S5.3 35 S5.3 MECH UNIT PER MECH. MAX WT = 750#, TYP 35 S5.3 1 1 RE: 24/S2.1, TYP 1 MECH UNIT PER MECH. MAX WT = 500#, TYP HE 20' - 0" MECH UNIT PER MECH. MAX WT = 500#, TYP 2 MECH UNIT PER MECH. MAX WT = 750#, TYP MECH UNIT PER MECH. MAX WT = 750#, TYP 2 HF RE: 24/S2.1, TYP 1 7 7 7 SPAN SPAN SPAN 8 20' - 0" 110'-2" TO TOPPING SLAB MECH UNIT PER MECH. MAX WT = 500#, TYP 110'-2" TO TOPPING SLAB RE: 24/S2.1, TYP 110'-2" TO TOPPING SLAB HG MECH UNIT PER MECH. MAX WT = 500#, TYP 27' - 0 5/8" MECH UNIT PER MECH. MAX WT = 500#, TYP 34 S5.3 34 S5.3 JOPLIN, JASPER COUNTY, MISSOURI 33 W16x57 31k 20' - 1 5/8" 33 10k 3k W16x26 10k HD JOPLIN HIGH SCHOOL 4' - 11 1/2" MEZZANINE LEVEL FLOOR FRAMING PLAN - AREA H 19' - 10 3/8" 3k 26KSP 26KSP 26KSP 26KSP 26KSP 26KSP 26KSP 26KSP 26KSP 26KSP 26KSP 26KSP 26KSP 26KSP 26KSP 26KSP 26KSP 26KSP 26KSP 26KSP 26KSP 26KSP 26KSP 26KSP 26KSP 26KSP W12x22 4' - 9 1/8" 10K1 4' - 9 1/8" 10K1 10K1 4' - 9 1/8" 10K1 4' - 9 1/8" 26KSP 26KSP HC 26KSP 9k-ft 3k W12x22 20' - 0" G2 34 4' - 8" 4' - 8" 4' - 8" 4' - 8" 4' - 8" W12x26 18KSP 18KSP 18KSP 18KSP 18KSP 18KSP 18KSP 18KSP SPAN 23' - 5 1/2" 2 2 10-08-12 ADD #3 4' - 8" 7290 West 133rd Street Overland Park, Kansas 66213 tel: (913)897-7811 4' - 8" Architecture Engineering Planning Interiors 4' - 8" H4 18KSP H3 18KSP H2 31k 170k-ft W16x67 20' - 10" W12x26 H1 46' - 8" 4' - 8" 18KSP 28' - 10" 4' - 8" 18KSP 105' - 4" 4' - 8" 18KSP 31 S5.3 18KSP 31 S5.3 46k 200k-ft 5k W16x36 Revisions HH HJ HK 21k 200k-ft 1 10-04-12 ADD #2 W16x31 LINTEL 1' - 3 3/4" W16x31 LINTEL 18KSP W16x31 LINTEL 13-12102-00 09/10/12 S5.3 S1.2H 1' - 1 1/4" 33 S5.3 3' - 8 5/8" 3' - 8 5/8" 3' - 8 5/8" 3k 44' - 4 1/4" H5 A. FINISHED FLOOR ELEVATION IS 116'-0", UNLESS NOTED OTHERWISE. B. TOP OF STEEL ELEVATION IS TYPICALLY 115'-6", UNLESS NOTED OTHERWISE ON PLANS AND SECTIONS. TOP OF STEEL THAT OCCURS ON A SLOPE AND IS NOT SPECIFICALLY NOTED ON THE PLANS SHALL BE LINEARLY INTERPOLATED FROM TOP OF STEEL NOTED ON THE PLANS. C. SEE SHEET S4.1 AND S4.2 "FLOOR FRAMING TYPICAL DETAILS" FOR ADDITIONAL FRAMING REQUIREMENTS AND INFORMATION. D. JOIST SUPPLIER TO COORDINATE WITH MECHANICAL CONTRACTOR FOR RTU WEIGHTS, LOCATIONS AND PENETRATIONS. E. KEY NOTES: JOIST SUPPLIER SHALL DESIGN JOISTS FOR ALL LOADS INDICATED IN S0.1 & S0.2 'GENERAL NOTES', S0.3 'ROOF SNOW DRIFT PLAN', ON THE PLAN SHEETS, AND THE SECTION/DETAIL SHEETS. CONTRACTOR TO COORDINATE ALL WEIGHTS, LOCATIONS, AND PENETRATIONS OF EQUIPMENT WITH THE JOIST SUPPLIER PRIOR TO SUBMITTING JOIST SHOP DRAWINGS. G. SEE ARCHITECTURAL DRAWINGS FOR LOCATION OF SLOPED, RAISED, DEPRESSED SLABS AND DRAINS. M. ALL PRECAST CONNECTIONS SHALL BE DESIGNED BY THE PRECAST SUPPLIER. T. COORDINATE ALL PENETRATIONS THRU CONTINUOUS FOOTINGS WITH MEP DRAWINGS. REFERENCE TYPICAL DETAILS 34/S2.1 & 41/S2.1. H. REFER TO ARCHITECTURAL DRAWINGS FOR OVERALL BUILDING GEOMETRY, WALL LOCATIONS, STAIR GEOMETRY AND ADDITIONAL PARTITION WALL REQUIREMENTS. N. ALL HSS MEMBERS SHALL HAVE 1/4" CAP PLATES AT ENDS. U. ALL EXTERIOR EXPOSED STEEL SHALL BE GALVANIZED. J. REFER TO ARCHITECTURAL DRAWINGS FOR NON-LOAD BEARING PARTITION WALLS. REFER TO SHEETS S0.1, S0.2, S2.1, S2.2, AND S9.2 TYPICAL DETAILS FOR REINFORCING, THICKENED SLABS AND OTHER REQUIREMENTS. K. ALL OPENINGS IN CMU WALLS (PARTITION AND LOAD BEARING) REQUIRE A LINTEL. REFER TO SHEET S9.2 FOR TYPICAL MASONRY LINTEL DETAILS AND SCHEDULES. L. SEE SHEET S6.1 AND S6.2 "ROOF FRAMING TYPICAL DETAILS" FOR ADDITIONAL REQUIREMENTS AND INFORMATION. O. P. PROVIDE HSS3 1/2x2 1/2x1/4 (LLH) BETWEEN ALL JOIST WITH 2 1/2" SEATS TO SUPPORT ROOF DECK WHERE DECK SWITCHES DIRECTION. (RE: 44/S6.1) REFER TO SPECIFICATIONS FOR ALL SUBGRADE PREPARATION REQUIREMENTS. Q. SEE SHEET S2.1 AND S2.2 "TYPICAL FOUNDATION SECTIONS" FOR ADDITIONAL REQUIREMENTS AND INFORMATION. R. REFER TO 52/S2.1 FOR COLUMN AND FOOTING SCHEDULES. S. REFER TO ARCHITECTURAL DRAWINGS FOR PRECAST JOINT LOCATIONS. VERIFY JOINT LOCATIONS WITH PRECASTER. V. COORDINATE ALL FOOTING STEP LOCATIONS AND BRICK LEDGES WITH ARCHITECTURAL ELEVATIONS. 1 2 H6 6 6" NORMAL WEIGHT AIR ENTRAINED CONCRETE SLAB-ON-GRADE REINFORCE WITH #4 @ 12"OC EACH WAY ON 15 MIL VAPOR RETARDER OVER 4" GRANULAR FILL. 1 1/2" DEEP, 20 GAGE, GALVANIZED WIDE RIB STEEL ROOF DECK. PROVIDE 5/8" DIAMETER PUBBLE WELDS IN 36/5 PATTERN AND 2 #10 TEK SCREWS AT SIDELAPS PER SPAN. 7 8" HOLLOW CORE WITH 2" TOPPING SLAB. REINFORCE TOPPING SLAB WITH 6x6/W2.1xW2.1 WELDED WIRE REINFORCEMENT. PRECAST SUPPLIER TO DESIGN FOR 125 PSF. 4" NORMAL WEIGHT CONCRETE SLAB-ON-GRADE W/ 6x6-W2.1xW2.1 WELDED WIRE REINFORCEMENT ON 15 MIL VAPOR RETARDER OVER 4" GRANULAR FILL. 8 12" CMU WALL REINFORCE PER GENERAL NOTES, UNLESS NOTED OTHERWISE. 9 8" CMU WALL REINFORCE PER GENERAL NOTES, UNLESS NOTED OTHERWISE. 3" NORMAL WEIGHT CONCRETE SLAB ON 3" DEEP, 20 GAGE, GALVANIZED COMPOSITE STEEL FLOOR DECK (6" TOTAL THICKNESS). REINFORCE WITH 6x6/W2.1xW2.1 WELDED WIRE REINFORCEMENT. 2 DENOTES FEMA 361 SAFE ROOM AREA. REFER TO TYPICAL DETAILS (ON S4.3) AND GENERAL NOTES. 3 4 6" NORMAL WEIGHT CONCRETE SLAB ON 3" DEEP, 20 GAGE, GALVANIZED COMPOSITE STEEL FLOOR DECK (9" TOTAL THICKNESS). REINFORCE WITH 6x6/W2.1xW2.1 WELDED WIRE REINFORCEMENT. 5 DOWEL FOOTING AND WALL TOGETHER WITH 2-#6, TOP & BOTTTOM. PROVIDE 'CLASS B' LAP SPLICE. HOOK BARS 1'-0" INTO WALL. H8 H9 C D 2 W. 10' - 4 1/4" B EQUIPMENT PLATFORM LEVEL FRAMING PLAN - AREA H F K E G L H J SCALE: 1/8" = 1'-0" BENJAMIN TALPOS 10/8/2012 6:13:58 PM C:\Users\BrionP\Documents\9-2013-Revit Projects\Joplin\13-12102-00_central_struct_2012.rvt MATCHLINE RE: S1.2J PLAN NOTES: 12k A MATCHLINE RE: S1.2H 1 W24x55 NORTH NORTH © 2012, DLR Group of Missouri inc., a Missouri corporation CA No. 001614, ALL RIGHTS RESERVED. W24x76 HL 4k KEY PLAN 44' - 4 1/4" 10' - 4 1/4" H9 W12x30 W12x30 20K3 20K3 20K3 H8 20K3 20K3 20K3 20K3 20K3 20K3 20K3 H5 W12x30 TOP OF STEEL ELEVATION IS TYPICALLY 115'-6", UNLESS NOTED OTHERWISE ON PLANS AND SECTIONS. TOP OF STEEL THAT OCCURS ON A SLOPE AND IS NOT SPECIFICALLY NOTED ON THE PLANS SHALL BE LINEARLY INTERPOLATED FROM TOP OF STEEL NOTED ON THE PLANS. C. SEE SHEET S4.1 AND S4.2 "FLOOR FRAMING TYPICAL DETAILS" FOR ADDITIONAL FRAMING REQUIREMENTS AND INFORMATION. D. JOIST SUPPLIER TO COORDINATE WITH MECHANICAL CONTRACTOR FOR RTU WEIGHTS, LOCATIONS AND PENETRATIONS. E. JOIST SUPPLIER SHALL DESIGN JOISTS FOR ALL LOADS INDICATED IN S0.1 & S0.2 'GENERAL NOTES', S0.3 'ROOF SNOW DRIFT PLAN', ON THE PLAN SHEETS, AND THE SECTION/DETAIL SHEETS. CONTRACTOR TO COORDINATE ALL WEIGHTS, LOCATIONS, AND PENETRATIONS OF EQUIPMENT WITH THE JOIST SUPPLIER PRIOR TO SUBMITTING JOIST SHOP DRAWINGS. F. REFER TO GENERAL NOTES SHEETS S0.1 AND S0.2 FOR GENERAL NOTES, ABBREVIATIONS AND SYMBOLS. 2 G. SEE ARCHITECTURAL DRAWINGS FOR LOCATION OF SLOPED, RAISED, DEPRESSED SLABS AND DRAINS. H. REFER TO ARCHITECTURAL DRAWINGS FOR OVERALL BUILDING GEOMETRY, WALL LOCATIONS, STAIR GEOMETRY AND ADDITIONAL PARTITION WALL REQUIREMENTS. J. REFER TO ARCHITECTURAL DRAWINGS FOR NON-LOAD BEARING PARTITION WALLS. REFER TO SHEETS S0.1, S0.2, S2.1, S2.2, AND S9.2 TYPICAL DETAILS FOR REINFORCING, THICKENED SLABS AND OTHER REQUIREMENTS. K. ALL OPENINGS IN CMU WALLS (PARTITION AND LOAD BEARING) REQUIRE A LINTEL. REFER TO SHEET S9.2 FOR TYPICAL MASONRY LINTEL DETAILS AND SCHEDULES. L. SEE SHEET S6.1 AND S6.2 "ROOF FRAMING TYPICAL DETAILS" FOR ADDITIONAL REQUIREMENTS AND INFORMATION. M. ALL PRECAST CONNECTIONS SHALL BE DESIGNED BY THE PRECAST SUPPLIER. N. ALL HSS MEMBERS SHALL HAVE 1/4" CAP PLATES AT ENDS. O. PROVIDE HSS3 1/2x2 1/2x1/4 (LLH) BETWEEN ALL JOIST WITH 2 1/2" SEATS TO SUPPORT ROOF DECK WHERE DECK SWITCHES DIRECTION. (RE: 44/S6.1) P. REFER TO SPECIFICATIONS FOR ALL SUBGRADE PREPARATION REQUIREMENTS. Q. SEE SHEET S2.1 AND S2.2 "TYPICAL FOUNDATION SECTIONS" FOR ADDITIONAL REQUIREMENTS AND INFORMATION. R. REFER TO 52/S2.1 FOR COLUMN AND FOOTING SCHEDULES. S. REFER TO ARCHITECTURAL DRAWINGS FOR PRECAST JOINT LOCATIONS. VERIFY JOINT LOCATIONS WITH PRECASTER. T. COORDINATE ALL PENETRATIONS THRU CONTINUOUS FOOTINGS WITH MEP DRAWINGS. REFERENCE TYPICAL DETAILS 34/S2.1 & 41/S2.1. U. ALL EXTERIOR EXPOSED STEEL SHALL BE GALVANIZED. V. COORDINATE ALL FOOTING STEP LOCATIONS AND BRICK LEDGES WITH ARCHITECTURAL ELEVATIONS. W. DENOTES FEMA 361 SAFE ROOM AREA. REFER TO TYPICAL DETAILS (ON S4.3) AND GENERAL NOTES. SPAN S5.3 S5.3 S5.3 W27x94 JB 4k W16x31 LINTEL 6k W12x19 6k (LOW) 3k 35 2' - 6" 2' - 7 7/8" RE: 24/S2.1, TYP 2 S5.3 28' - 3" 20K9 W12x30 (LOW) W14x26 (HIGH) W14x26 20K3 20K3 20K3 20K3 20K3 20K3 20KSP 20KSP W16x31 LINTEL W12x30 2' - 7 7/8" 4k W16x31 LINTEL 5' - 3 5/8" 16k-ft 32 17k-ft 31 3k W16x31 LINTEL 31 20KSP W14x26 20KSP 3k 3k 3k W12x19 3k (LOW) 8k-ft W27x84 JA 34 28' - 11" 20K6 W12x30 W12x30 (LOW) W14x26 (HIGH) 20K3 20K3 20K3 20K3 20K3 20K4 W27x84 SPAN W12x19 KEY NOTES: 8k-ft S5.3 3k 33 7 JC 2 MECH UNIT PER MECH. MAX WT = 500#, TYP S5.3 2 W14x26 1 110'-2" TO TOPPING SLAB 3k 1 22KSP 26KSP 5' - 3 5/8"2' - 7 7/8" 3k (LOW) 3k 110'-2" TO TOPPING SLAB 4' - 8" 4' - 8" 4' - 8" 22' - 1 1/2" 21' - 10 1/8" RE: 24/S2.1, TYP 2 W12x22 W12x22 16K2 16K2 16K2 16K2 16K2 16K2 22KSP SPAN MECH UNIT PER MECH. MAX WT = 750#, TYP 20KSP 7 1 3" NORMAL WEIGHT CONCRETE SLAB ON 3" DEEP, 20 GAGE, GALVANIZED COMPOSITE STEEL FLOOR DECK (6" TOTAL THICKNESS). REINFORCE WITH 6x6/W2.1xW2.1 WELDED WIRE REINFORCEMENT. 2 1 1/2" DEEP, 20 GAGE, GALVANIZED WIDE RIB STEEL ROOF DECK. PROVIDE 5/8" DIAMETER PUBBLE WELDS IN 36/5 PATTERN AND 2 #10 TEK SCREWS AT SIDELAPS PER SPAN. 3 4" NORMAL WEIGHT CONCRETE SLAB-ON-GRADE W/ 6x6-W2.1xW2.1 WELDED WIRE REINFORCEMENT ON 15 MIL VAPOR RETARDER OVER 4" GRANULAR FILL. 4 6" NORMAL WEIGHT CONCRETE SLAB ON 3" DEEP, 20 GAGE, GALVANIZED COMPOSITE STEEL FLOOR DECK (9" TOTAL THICKNESS). REINFORCE WITH 6x6/W2.1xW2.1 WELDED WIRE REINFORCEMENT. 5 DOWEL FOOTING AND WALL TOGETHER WITH 2-#6, TOP & BOTTTOM. PROVIDE 'CLASS B' LAP SPLICE. HOOK BARS 1'-0" INTO WALL. 6 6" NORMAL WEIGHT AIR ENTRAINED CONCRETE SLAB-ON-GRADE REINFORCE WITH #4 @ 12"OC EACH WAY ON 15 MIL VAPOR RETARDER OVER 4" GRANULAR FILL. 7 8" HOLLOW CORE WITH 2" TOPPING SLAB. REINFORCE TOPPING SLAB WITH 6x6/W2.1xW2.1 WELDED WIRE REINFORCEMENT. PRECAST SUPPLIER TO DESIGN FOR 125 PSF. 1 8 12" CMU WALL REINFORCE PER GENERAL NOTES, UNLESS NOTED OTHERWISE. 9 8" CMU WALL REINFORCE PER GENERAL NOTES, UNLESS NOTED OTHERWISE. SPAN JD W27x84 JE 46k W16x26 15k 7k 17k 2 MECH UNIT PER MECH. MAX WT = 500#, TYP 4' - 8" 3' - 0" 3' - 0" 28KSP MECH UNIT PER MECH. MAX WT = 500#, TYP 30KSP MECH UNIT PER MECH. MAX WT = 750#, TYP 4' - 8" 4' - 8" 4' - 3 3/8" 3' - 4" 34 34 S5.3 38' - 6" W14x53 24K8 24K7 24K7 24K7 24K7 24K7 24K7 24K7 24K7 26K7 32LH07 33 S5.3 24K7 S5.3 33 7k S5.3 JOPLIN, JASPER COUNTY, MISSOURI MATCHLINE RE: S1.2H MATCHLINE RE: S1.2J B. JOPLIN HIGH SCHOOL 12k FINISHED FLOOR ELEVATION IS 116'-0", UNLESS NOTED OTHERWISE. 4k 3k A. MEZZANINE LEVEL FLOOR FRAMING PLAN - AREA J PLAN NOTES: 5' - 0" 5' - 0" 5' - 0" 5' - 0" 3k J6 J7 MB 16K2 16K2 W12x22 C 3k 7k-ft 12k 16K2 16K2 16K2 16K2 7k-ft 13k B W16x31 7k F K 26' - 2 5/8" J2 24' - 3 3/8" J3 MC E J4 G L H EQUIPMENT PLATFORM LEVEL FRAMING PLAN - AREA J J BENJAMIN TALPOS SCALE: 1/8" = 1'-0" NORTH NORTH © 2012, DLR Group of Missouri inc., a Missouri corporation CA No. 001614, ALL RIGHTS RESERVED. 3k W16x31 16K2 16K2 16K2 16K2 W12x22 3k 20' - 6 1/2" H6 KEY PLAN 15' - 7 7/8" D 10/8/2012 6:14:06 PM C:\Users\BrionP\Documents\9-2013-Revit Projects\Joplin\13-12102-00_central_struct_2012.rvt 7' - 11 1/2" A SPAN 8k 16' - 4 5/8" J5 2 JJ 8K1 8K1 8K1 24' - 0" 39k 3k JH 5k Revisions 4' - 1 3/8" 4' - 3 3/8" W27x84 40k M2 W12x22 16KSP 16KSP 16KSP 16KSP 16KSP 4' - 5" 15k M4 2 10-08-12 ADD #3 4' - 5" M3 7290 West 133rd Street Overland Park, Kansas 66213 tel: (913)897-7811 4' - 5" 16KSP 16KSP 16KSP 4' - 5" W16x26 W16x26 15k Architecture Engineering Planning Interiors 4' - 5" 5k 4' - 1 5/8" 16KSP 16KSP W12x19 10' - 1 1/2" J1 8K1 8K1 5k JG 2k MA M1 10k 1 10-04-12 ADD #2 4' - 2" W16x26 13-12102-00 09/10/12 4' - 2" 12k 2k W14x22 4' - 2" 9' - 4" 5k 4' - 2" 27k S1.2J W18x35 JF 24' - 0" 26' - 4" MATCHLINE RE: S1.2K 15k (8) 33k 1 x124 W30 ER RAK 3k W16x26 4k 6k 25k 4k 20 k-ft 25k 23k 18k W16x26 (30) 18k 18k W16x26 (30) 18k W16x26 (30) 21k 22k W24x55 (48) 22k 30k W21x44 (26) 15k W12x22 (26) 25k W16x26 (26) 18k 13k 21k 44k (4) W16x 26 2k 15° 28k (4) W16x 26 15° 12k 27k 18k 64k W18x35 (34) c=1" 28k 17k W30x108 RAKER W16x26 18k RKD (4) W24x55 (48) 23k W24x55 (30) 23k W18x40 (46) 32k 32k 99k 25k HSS 6x6x 1/4 5k 51 6k 14k W12x26 (30) 14k W16x31 (36) 18k CC18 16k 18k 25k K10 W24x55 (48) 18k 6k 5k /4 HSS x6x1 6x6x 6 S S8.5 1/4 HS W24x55 (26) 7k 7k W16x26 (30) 25k 6k N. ALL HSS MEMBERS SHALL HAVE 1/4" CAP PLATES AT ENDS. O. PROVIDE HSS3 1/2x2 1/2x1/4 (LLH) BETWEEN ALL JOIST WITH 2 1/2" SEATS TO SUPPORT ROOF DECK WHERE DECK SWITCHES DIRECTION. (RE: 44/S6.1) P. REFER TO SPECIFICATIONS FOR ALL SUBGRADE PREPARATION REQUIREMENTS. Q. SEE SHEET S2.1 AND S2.2 "TYPICAL FOUNDATION SECTIONS" FOR ADDITIONAL REQUIREMENTS AND INFORMATION. R. REFER TO 52/S2.1 FOR COLUMN AND FOOTING SCHEDULES. S. REFER TO ARCHITECTURAL DRAWINGS FOR PRECAST JOINT LOCATIONS. VERIFY JOINT LOCATIONS WITH PRECASTER. T. COORDINATE ALL PENETRATIONS THRU CONTINUOUS FOOTINGS WITH MEP DRAWINGS. REFERENCE TYPICAL DETAILS 34/S2.1 & 41/S2.1. U. ALL EXTERIOR EXPOSED STEEL SHALL BE GALVANIZED. V. COORDINATE ALL FOOTING STEP LOCATIONS AND BRICK LEDGES WITH ARCHITECTURAL ELEVATIONS. W. DENOTES FEMA 361 SAFE ROOM AREA. REFER TO TYPICAL DETAILS (ON S4.3) AND GENERAL NOTES. W16x 26 2k 28k 65k W12x22 (26) 5k 12k 77 k-ft 12k 2 1 1/2" DEEP, 20 GAGE, GALVANIZED WIDE RIB STEEL ROOF DECK. PROVIDE 5/8" DIAMETER PUBBLE WELDS IN 36/5 PATTERN AND 2 #10 TEK SCREWS AT SIDELAPS PER SPAN. 3 4" NORMAL WEIGHT CONCRETE SLAB-ON-GRADE W/ 6x6-W2.1xW2.1 WELDED WIRE REINFORCEMENT ON 15 MIL VAPOR RETARDER OVER 4" GRANULAR FILL. 4 6" NORMAL WEIGHT CONCRETE SLAB ON 3" DEEP, 20 GAGE, GALVANIZED COMPOSITE STEEL FLOOR DECK (9" TOTAL THICKNESS). REINFORCE WITH 6x6/W2.1xW2.1 WELDED WIRE REINFORCEMENT. 5 DOWEL FOOTING AND WALL TOGETHER WITH 2-#6, TOP & BOTTTOM. PROVIDE 'CLASS B' LAP SPLICE. HOOK BARS 1'-0" INTO WALL. 6 6" NORMAL WEIGHT AIR ENTRAINED CONCRETE SLAB-ON-GRADE REINFORCE WITH #4 @ 12"OC EACH WAY ON 15 MIL VAPOR RETARDER OVER 4" GRANULAR FILL. 7 8" HOLLOW CORE WITH 2" TOPPING SLAB. REINFORCE TOPPING SLAB WITH 6x6/W2.1xW2.1 WELDED WIRE REINFORCEMENT. PRECAST SUPPLIER TO DESIGN FOR 125 PSF. 8 12" CMU WALL REINFORCE PER GENERAL NOTES, UNLESS NOTED OTHERWISE. 9 8" CMU WALL REINFORCE PER GENERAL NOTES, UNLESS NOTED 1 OTHERWISE. RKE CC1 W16x 26 W16x26 (2) 9k 9k 20 k-ft 98k 2k W16x26 (4) 4k 4k 20 k-ft 3' - 9 7/8" 26k 1 3k S5.5 W12x22 (18) S8.4 W12x26 17k 33 HSS12x2x1/4 STAIR STRINGER HSS4x4x3/16 KEY PLAN 16k 33 S5.5 W16x67 (26) 79k HSS4x2x3/16 36k W18x60 25k W21x73 203 k-ft 1 A 6k W12x16 (10) 6k 29k W18x60 (26) B 193 k-ft 42k 293 k-ft 5k HSS 6x6x S8.5 1/4 W24x55 3" NORMAL WEIGHT CONCRETE SLAB ON 3" DEEP, 20 GAGE, GALVANIZED COMPOSITE STEEL FLOOR DECK (6" TOTAL THICKNESS). REINFORCE WITH 6x6/W2.1xW2.1 WELDED WIRE REINFORCEMENT. (4) W30x90 (150) 9k (6) W12x22 2k (4) 37k W21x73 (26) 280 k-ft 53 5k 1 56 S5.4 16k W12x22 (18) HSS12x2x1/4 STAIR STRINGER 24k 18k 6k 53 CC18 ALL PRECAST CONNECTIONS SHALL BE DESIGNED BY THE PRECAST SUPPLIER. 2 RK9 22 W12x22 (18) 16k 1/4 6x6x HSS M. 15° W24x55 (26) 3k 14k W12x22 (26) 14k W30x90 (48) 26k 30k W16x26 (2) 9k 9k 20 k-ft (4) W24x55 (26) W24x55 LINTEL W18x35 (40) 30k SEE SHEET S6.1 AND S6.2 "ROOF FRAMING TYPICAL DETAILS" FOR ADDITIONAL REQUIREMENTS AND INFORMATION. 7k 55k 55k 21k L. 34k 16k W12x22 (26) 6k 17k W33x141 W12x26 (30) W24x55 (58) 21k 16k 51 CC18 25k W24x55 (48) HSS 6x6x 1/4 16k 17k W16x26 (30) W33x141 W24x55 25k ALL OPENINGS IN CMU WALLS (PARTITION AND LOAD BEARING) REQUIRE A LINTEL. REFER TO SHEET S9.2 FOR TYPICAL MASONRY LINTEL DETAILS AND SCHEDULES. CC1 W16x26 95k W24x55 (48) 27k 25k K. 1 C MATCHLINE RE: S1.2K MATCHLINE RE: S1.2L 6k W16x45 22k 79k 41k W16x26 (30) 51k c=1" 25k W33x141 38k SPAN 41k 69k W18x40 (46) 41k c=1" REFER TO ARCHITECTURAL DRAWINGS FOR NON-LOAD BEARING PARTITION WALLS. REFER TO SHEETS S0.1, S0.2, S2.1, S2.2, AND S9.2 TYPICAL DETAILS FOR REINFORCING, THICKENED SLABS AND OTHER REQUIREMENTS. 2k 28k 41k 6k 12k 77 k-ft 44k W18x40 (46) 55k D F 8k W12x16 (10) 8k K E CC18 G L S8.4 K3 15k W12x22 (16) 12k 7' - 0" 27k 28k CC23 W16x26 (26) J. 4k 70k 21k 4k W16x26 (10) c=3/4" 18k 66k W24x76 (48) 1 1 W21x101 (40) 25k 97k 21k 31k 70k W30x99 RAKER W30x108 RAKER W21x44 (26) REFER TO ARCHITECTURAL DRAWINGS FOR OVERALL BUILDING GEOMETRY, WALL LOCATIONS, STAIR GEOMETRY AND ADDITIONAL PARTITION WALL REQUIREMENTS. K4 L1 K5 K6 S8.4 K7 L2 K8 K9 K11 K12 SECOND LEVEL FRAMING PLAN - AREA K H J BENJAMIN TALPOS SCALE: 1/8" = 1'-0" NORTH NORTH © 2012, DLR Group of Missouri inc., a Missouri corporation CA No. 001614, ALL RIGHTS RESERVED. 18k 95k 51k W16x31 (38) 40k CC23 65k MATCHLINE RE: S1.2L W16x26 (10) 8' - 8 1/2" 25k H. W14x30 (26) W16x26 (30) 6k K2 25k SEE ARCHITECTURAL DRAWINGS FOR LOCATION OF SLOPED, RAISED, DEPRESSED SLABS AND DRAINS. 3k 18k W33x141 67k 2k (4) (4) 2k W16x 26 26k 18k MATCHLINE RE: S1.2K LA W21x44 (26) W16x31 (26) 25k ) (26 27k 25k 7' - 0" W21x44 (26) W30x108 RAKER W30x108 RAKER W30x108 RAKER W16x26 (30) W24x55 (58) c=3/4" W24x55 (48) 24' - 8" 25k 8' - 8" 69k 38k K1 10/8/2012 6:14:16 PM 24k 43k W18x46 15k W21x101 (40) RK8 15° 14k 14k W16x26 (4) 77 k-ft SIM k 100 W12x22 (12) KL C:\Users\BrionP\Documents\9-2013-Revit Projects\Joplin\13-12102-00_central_struct_2012.rvt W21x44 (26) 18 x1 3 3 W 15k 6k 8k W12x22 (26) 13k 18k HSS4x4x3/16 67k W21x44 5' - 8 1/2" 13k HSS4x2x3/16 KM W21x44 5' - 8 1/2" HSS16x4x3/8 STAIR STRINGER 1 24k W12x22 W12x22 (12) 48k W14x30 W24x55 LINTEL 22 S5.5 13k 17k 26' - 0" S5.4 W18x46 (48) 21 8' - 8" 13k W16x26 (26) W12x22 (12) S5.5 W21x44 15k 42k 15 W21x44 8' - 8" 31k W16x26 (10) 10k 10k 20k W16x26 (10) 10k 10k W24x62 (56) W21x44 ER RAK x124 W30 40k W24x131 54k 452 k-ft 56k 441 k-ft W30x90 RAKER W24x131 35k 14k 61k W14x22 (10) 10k 10k W16x26 (10) 10k 10k 2' - 7" 51k W14x22 (10) 10k 10k 55 8' - 0" 2 S8.4 12k W18x35 (40) 12k 1 4 x4 21 W 6k W12x22 (12) PRECAST TREAD AND RISER UNITS PER PRECAST SUPPLIER, TYP 8k 49k W30 x124 RAK ER 12k W12x22 (10) c=3/4" W24x55 (42) 8' - 0" 24' - 0" W21x48 (48) W24x55 (62) G. KEY NOTES: W16x26 (2) 9k 9k 20 k-ft W16x26 (4) 4k 20 k-ft 63k W12x22 (12) 49k W16x26 (30) c=3/4" 14k 25k W30x99 RAKER W21x44 61k W24x131 52k 431 k-ft 12k 49k KK 14k 25k 14k 14k 4k 14k 61k W24x55 (62) 14k 14k W16x26 (4) 77 k-ft W16x26 8' - 0" 51k 61k 446 k-ft REFER TO GENERAL NOTES SHEETS S0.1 AND S0.2 FOR GENERAL NOTES, ABBREVIATIONS AND SYMBOLS. CC1 2k W16x 26 12k EQ 51k W24x131 49k KJ W18x40 (26) W12x22 (12) W21x44 S8.6 RK4 RK3 40k RKC 1 12k 12k KH 4k 20 k-ft 83k 25k 61k 12k 33 F. 2 (4) 6k 49k 12k W12x22 (12) 49k c=3/4" W30x108 RAKER W16x26 (30) W24x55 (62) 49k W24x131 52k 431 k-ft W24x55 (42) S8.5 (4) 15° 14k 61k c=3/4" EQ W21x48 (48) 24' - 0" 35 SPAN 1 EQ W24x55 (62) 49k 12k 77 k-ft 12k EQ 51k 51k KG RK7 2k (4) W16x26 W24x55 (44) W21x44 45 S8.4 4k 61k 446 k-ft W16x26 (2) 9k 9k 20 k-ft 1 W16x26 W24x131 CC1 2k W16x 26 14k 14k W16x26 (4) 77 k-ft W24x55 (26) W12x22 (12) 12k 40k RKB 12k W18x40 (26) 49k 4k 20 k-ft 41k 6k 1 W16x26 (30) c=3/4" W24x55 (42) EQ 24' - 0" W24x55 (44) W24x55 (62) 12k W12x22 (12) 49k 12k 49k 12k 77 k-ft (4) (4) 83k 25k 14k 61k 14k 25k 61k 14k W30x108 RAKER EQ c=3/4" W16x26 2k (4) 15° EQ 51k W24x55 (62) 49k 2k W16x 26 W24x55 (48) W24x55 (26) W21x44 PRECAST TREAD AND RISER UNITS PER PRECAST SUPPLIER, TYP W24x131 52k 431 k-ft 61k 446 k-ft JOIST SUPPLIER SHALL DESIGN JOISTS FOR ALL LOADS INDICATED IN S0.1 & S0.2 'GENERAL NOTES', S0.3 'ROOF SNOW DRIFT PLAN', ON THE PLAN SHEETS, AND THE SECTION/DETAIL SHEETS. CONTRACTOR TO COORDINATE ALL WEIGHTS, LOCATIONS, AND PENETRATIONS OF EQUIPMENT WITH THE JOIST SUPPLIER PRIOR TO SUBMITTING JOIST SHOP DRAWINGS. RK6 15° 14k 14k W16x26 (4) 77 k-ft 4k 51k KF W16x26 (2) 9k 9k 20 k-ft 1 12k E. CC1 (4) 64k W18x40 (26) W12x22 (12) JOIST SUPPLIER TO COORDINATE WITH MECHANICAL CONTRACTOR FOR RTU WEIGHTS, LOCATIONS AND PENETRATIONS. 1 5' - 8 1/2" W16x26 W24x131 RKA 87k 14k W12x22 (26) 22k S8.6 12k 40k W16x26 (4) 12k 12k 77 k-ft 12k W16x26 (30) 49k 12k 31 W24x55 (42) c=3/4" 56 2kS5.4 (4) W12x22 (12) 49k EQ W24x55 (62) 49k 2k W16x 26 22k 14k 14k W16x26 (4) 77 k-ft 5' - 8 1/2" 14k 61k 7' - 0" W30x99 RAKER EQ c=3/4" RK5 15° RK2 RK1 W24x55 (62) D. SIM 14k PRECAST TREAD AND RISER UNITS PER PRECAST SUPPLIER, TYP SEE SHEET S4.1 AND S4.2 "FLOOR FRAMING TYPICAL DETAILS" FOR ADDITIONAL FRAMING REQUIREMENTS AND INFORMATION. JOPLIN, JASPER COUNTY, MISSOURI S8.3 12k 43k 8' - 0" 51k W18x40 (38) W21x44 W24x131 59k 519 k-ft 60k 489 k-ft 22k 53 12k W12x22 (12) W21x44 35 S8.4 S5.5 W21x44 45k W24x55 (26) c=3/4" W21x44 C. 22 6k W12x22 (12) 36k W21x44 c=1 1/4" 2 W21x44 TOP OF STEEL ELEVATION IS TYPICALLY 115'-6", UNLESS NOTED OTHERWISE ON PLANS AND SECTIONS. TOP OF STEEL THAT OCCURS ON A SLOPE AND IS NOT SPECIFICALLY NOTED ON THE PLANS SHALL BE LINEARLY INTERPOLATED FROM TOP OF STEEL NOTED ON THE PLANS. HSS12x2x1/4 STAIR STRINGER 16k 8k 12k 16k W12x22 (26) 15k B. 2 10-08-12 ADD #3 12k HSS4x4x3/16 W12x22 (26) 16k FINISHED FLOOR ELEVATION IS 116'-0", UNLESS NOTED OTHERWISE. 15° W30x99 RAKER W30x108 RAKER W30x108 RAKER W30x108 RAKER W30x108 RAKER 24k 8k W30 x124 RAK ER 12k 28k 6k W12x22 15° W12x22 (26) W16x26 15k 3k 25k W16x 26 ( 13) W21x44 (26) 2k 25k 108k 25k W30x90 (150) W21x44 (26) 25k 7k 49k 25k 26 S5.5 41k W21x44 (26) 25k 15k HSS6x6x5/16 (TOS = 115'-1 1/2") 11k 25k 6k W12x22 (26) 15k 10k W12x22 (16) W21x44 (26) (8) 24k 25k W12x22 12k W18x35 (40) W12x22 (16) S8.5 13k k 74 W21x48 (48) 18k A. 33 S5.5 W18x35 (20) 2k W12x22 (26) W16x26 (30) 31 19k SPAN 18k 92k 1 18k W30x90 (156) 104 k 97k W16x26 (30) 34k W12x22 (26) 24k W30x90 RAKER W18x46 (26) W12x22 (12) 12k W24x131 49k 24' - 0" 11k 7' - 0" 18k W12x19 (20) 6' - 3 1/2" 18k 11k 7' - 0" W16x26 (30) 18k SPAN 1 18k 11k W12x19 (20) 76k 11k 97k 97k 95k 5' - 8 1/2" W16x26 (30) 11k W12x19 (20) W24x55 (50) W21x44 (26) 5' - 8 1/2" W18x46 (26) 33 18k 11k W16x26 (26) 8' - 0" 18k 12k 4 x4 21 W 8' - 0" 24k 6k 47k W24x104 472 k-ft 12k 44k W24x62 (48) W12x22 (12) W14x22 (10) 10k 10k 36k 12k 6k 12k W24x55 (62) 13k S8.5 6k W12x22 (12) c=3/4" 45k W16x26 (30) 6k 21k W16x26 (10) 10k 10k W16x26 (10) 10k 10k W16x31 (26) W18x40 (46) W21x48 (48) 21 S5.5 W24x55 10' - 0" S5.4 HSS4x2x3/16 41k 2' - 7" W12x26 (36) 50k 10" 1' - 6" 8' - 0" 35k 5' - 0" 10' - 0" 15 S5.5 W12x22 (12) 60k 401 k-ft 22 36k 24' - 0" 45k HSS16x4x3/8 STAIR STRINGER HSS4x4x3/16 W24x104 36k W24x55 KE 58k ) (26 KD c=3/4" 1 26k KC 8k W18x35 (12) 15k 08 x1 30 W F4 25k 8' - 0" W24x55 (62) 5' - 0" KB c=3/4" 18k 14' - 6" W12x22 (26) W12x22 (26) 13k 16' - 0" 210 k-ft 26k W30x99 (26) 45k W21x44 (40) FA 6' - 6 1/4" W24x55 (42) k 87 183 k-ft 32k 15k 17k W16x36 (26) 6' - 6 1/4" 25k 43k 26k W30x99 (26) 210 k-ft 8k 15k 17k 32k KA 183 k-ft 13k DG PLAN NOTES: HSS4x2x3/16 HSS12x2x1/4 STAIR STRINGER 8k MATCHLINE RE: S1.2F 2' - 3" 7290 West 133rd Street Overland Park, Kansas 66213 tel: (913)897-7811 24' - 0" Architecture Engineering Planning Interiors 24' - 0" JOPLIN HIGH SCHOOL 24' - 0" Revisions 24' - 0" 1 10-04-12 ADD #2 23' - 6" 13-12102-00 09/10/12 12' - 10" SECOND LEVEL FLOOR FRAMING PLAN - AREA K 42' - 0 3/8" S1.2K 15' - 4" 70k 65k W12x26 (30) 14k W16x31 (36) 18k CC18 18k 293 k-ft 37k W21x73 (26) MATCHLINE RE: S1.2K 280 k-ft 53 5k MATCHLINE RE: S1.2L 5k HSS 6x6x S8.5 1/4 W24x55 6k 6k 53 CC18 42k W14x30 (26) 1 W24x55 (48) W21x73 16k 1/4 6x6x HSS 6k W24x55 LINTEL W33x141 W24x55 (58) 14k 16k 25k W16x45 22k 8k W12x16 (10) 8k CC18 S8.4 1 W18x40 W16x36 W12x26 1 4k 4k 27k 12k W30x108 RAKER 4k 95k 70k 8' - 0" c=3/4" 35 S8.4 31 W16x36 70k S8.6 W16x31 c=3/4" W18x35 (30) W21x101 (40) 27k 70k W16x26 (30) c=3/4" 12k W21x101 (40) S8.3 W24x55 70k W14x34 W14x34 4k 4k 4k W12x26 4k W12x26 4k 4k W12x22 4k W12x26 4k 4k 4k W12x22 4k 4k W12x26 4k 4k HSS4x2x3/16 HSS6x6x5/16 (TOS = 129'-1 1/2") HSS6x6x5/16 (TOS = 129'-1 1/2") 11' - 8" 42' - 0 3/8" 12' - 10" K4 L1 24' - 0" K5 24' - 0" 19' - 10" K6 K7 28' - 2" L2 24' - 0" K8 26' - 4" K9 K11 K12 S1.2L K3 4' - 2" 23' - 6" JOPLIN, JASPER COUNTY, MISSOURI 43 2 10-08-12 ADD #3 55 21 S5.5 7290 West 133rd Street Overland Park, Kansas 66213 tel: (913)897-7811 S5.4 Architecture Engineering Planning Interiors S8.3 JOPLIN HIGH SCHOOL 4k S8.3 15 Revisions 22 S5.5 4k K2 W12x26 W16x31 HSS16x4x3/8 STAIR STRINGER W30x108 RAKER 4k 43k 27k 27k W16x26 (26) 27k HSS4x4x3/16 4k 4k W16x26 W16x31 (30) S8.3 W24x55 LF 4k 27k 27k W24x55 (30) 18' - 4 3/4" 26' - 8" 41 40k LE W30x108 RAKER 4k 80k LD 4k CC24 1 10-04-12 ADD #2 W12x22 W16x26 PRECAST TREAD AND RISER UNITS PER PRECAST SUPPLIER, TYP W16x31 W18x35 (30) 71k 8' - 2" 1 CC23 c=3/4" 27k W21x101 (40) 71k W16x26 (30) 70k 8' - 1" 24' - 0" c=3/4" 12k W21x101 (40) 70k 13-12102-00 09/10/12 SECOND LEVEL FLOOR FRAMING PLAN - AREA L 4k 4k 4k 27k 12k W30x108 RAKER 8' - 1" CC23 90k 4k 8' - 0" 70k LC 6k 18k 4k 4 c=3/4" 8' - 0" 24' - 0" 1 51 CC18 51 CC23 HSS 6x6x 1/4 5k 51 5k HSS 6x6x S8.5 1/4 W24x55 (26) 7k W24x55 (48) 18k 1 W21x101 (40) 70k 32k 6k 1/4 6x6x HSS 7k W18x40 (46) 32k SPAN 70k 10' - 0" W21x101 (40) 70k 17k 23k 16k c=3/4" c=3/4" CC23 70k LB W16x26 17k W30x108 RAKER W16x26 (30) W16x26 (10) 1 CC23 28k W24x55 (30) 70k W16x26 (10) 10' - 0" 30' - 0" W21x101 (40) 70k c=1" 16k 23k S8.4 c=3/4" W16x26 (10) W21x101 (40) 70k 55k CC23 W16x26 (10) 10' - 0" W16x26 (10) W16x26 (10) W18x35 (34) 28k 64k c=3/4" 31k W21x101 (40) 70k LA 31k CC23 40k 1 W16x26 (48) MATCHLINE RE: S1.2L 18k 79k HSS 6x6x 1/4 6k 22k 8' - 8 1/2" MATCHLINE RE: S1.2K W24x55 (48) 18k 193 k-ft 4k 27k W33x141 W24x55 27k 51k 41k W33x141 c=1" W33x141 W18x40 (46) 41k W24x55 (58) 67k 4k KM c=3/4" W24x55 (48) W21x101 (40) 67k 203 k-ft B KEY NOTES: PLAN NOTES: 1 A. FINISHED FLOOR ELEVATION IS 116'-0", UNLESS NOTED OTHERWISE. B. TOP OF STEEL ELEVATION IS TYPICALLY 115'-6", UNLESS NOTED OTHERWISE ON PLANS AND SECTIONS. TOP OF STEEL THAT OCCURS ON A SLOPE AND IS NOT SPECIFICALLY NOTED ON THE PLANS SHALL BE LINEARLY INTERPOLATED FROM TOP OF STEEL NOTED ON THE PLANS. C. SEE SHEET S4.1 AND S4.2 "FLOOR FRAMING TYPICAL DETAILS" FOR ADDITIONAL FRAMING REQUIREMENTS AND INFORMATION. D. JOIST SUPPLIER TO COORDINATE WITH MECHANICAL CONTRACTOR FOR RTU WEIGHTS, LOCATIONS AND PENETRATIONS. E. JOIST SUPPLIER SHALL DESIGN JOISTS FOR ALL LOADS INDICATED IN S0.1 & S0.2 'GENERAL NOTES', S0.3 'ROOF SNOW DRIFT PLAN', ON THE PLAN SHEETS, AND THE SECTION/DETAIL SHEETS. CONTRACTOR TO COORDINATE ALL WEIGHTS, LOCATIONS, AND PENETRATIONS OF EQUIPMENT WITH THE JOIST SUPPLIER PRIOR TO SUBMITTING JOIST SHOP DRAWINGS. G. SEE ARCHITECTURAL DRAWINGS FOR LOCATION OF SLOPED, RAISED, DEPRESSED SLABS AND DRAINS. M. ALL PRECAST CONNECTIONS SHALL BE DESIGNED BY THE PRECAST SUPPLIER. T. COORDINATE ALL PENETRATIONS THRU CONTINUOUS FOOTINGS WITH MEP DRAWINGS. REFERENCE TYPICAL DETAILS 34/S2.1 & 41/S2.1. H. REFER TO ARCHITECTURAL DRAWINGS FOR OVERALL BUILDING GEOMETRY, WALL LOCATIONS, STAIR GEOMETRY AND ADDITIONAL PARTITION WALL REQUIREMENTS. N. ALL HSS MEMBERS SHALL HAVE 1/4" CAP PLATES AT ENDS. U. ALL EXTERIOR EXPOSED STEEL SHALL BE GALVANIZED. J. REFER TO ARCHITECTURAL DRAWINGS FOR NON-LOAD BEARING PARTITION WALLS. REFER TO SHEETS S0.1, S0.2, S2.1, S2.2, AND S9.2 TYPICAL DETAILS FOR REINFORCING, THICKENED SLABS AND OTHER REQUIREMENTS. K. ALL OPENINGS IN CMU WALLS (PARTITION AND LOAD BEARING) REQUIRE A LINTEL. REFER TO SHEET S9.2 FOR TYPICAL MASONRY LINTEL DETAILS AND SCHEDULES. L. SEE SHEET S6.1 AND S6.2 "ROOF FRAMING TYPICAL DETAILS" FOR ADDITIONAL REQUIREMENTS AND INFORMATION. O. P. PROVIDE HSS3 1/2x2 1/2x1/4 (LLH) BETWEEN ALL JOIST WITH 2 1/2" SEATS TO SUPPORT ROOF DECK WHERE DECK SWITCHES DIRECTION. (RE: 44/S6.1) REFER TO SPECIFICATIONS FOR ALL SUBGRADE PREPARATION REQUIREMENTS. Q. SEE SHEET S2.1 AND S2.2 "TYPICAL FOUNDATION SECTIONS" FOR ADDITIONAL REQUIREMENTS AND INFORMATION. R. REFER TO 52/S2.1 FOR COLUMN AND FOOTING SCHEDULES. S. REFER TO ARCHITECTURAL DRAWINGS FOR PRECAST JOINT LOCATIONS. VERIFY JOINT LOCATIONS WITH PRECASTER. V. 2 W. COORDINATE ALL FOOTING STEP LOCATIONS AND BRICK LEDGES WITH ARCHITECTURAL ELEVATIONS. DENOTES FEMA 361 SAFE ROOM AREA. REFER TO TYPICAL DETAILS (ON S4.3) AND GENERAL NOTES. C 6 6" NORMAL WEIGHT AIR ENTRAINED CONCRETE SLAB-ON-GRADE REINFORCE WITH #4 @ 12"OC EACH WAY ON 15 MIL VAPOR RETARDER OVER 4" GRANULAR FILL. 1 1/2" DEEP, 20 GAGE, GALVANIZED WIDE RIB STEEL ROOF DECK. PROVIDE 5/8" DIAMETER PUBBLE WELDS IN 36/5 PATTERN AND 2 #10 TEK SCREWS AT SIDELAPS PER SPAN. 7 8" HOLLOW CORE WITH 2" TOPPING SLAB. REINFORCE TOPPING SLAB WITH 6x6/W2.1xW2.1 WELDED WIRE REINFORCEMENT. PRECAST SUPPLIER TO DESIGN FOR 125 PSF. 4" NORMAL WEIGHT CONCRETE SLAB-ON-GRADE W/ 6x6-W2.1xW2.1 WELDED WIRE REINFORCEMENT ON 15 MIL VAPOR RETARDER OVER 4" GRANULAR FILL. 8 12" CMU WALL REINFORCE PER GENERAL NOTES, UNLESS NOTED OTHERWISE. 9 8" CMU WALL REINFORCE PER GENERAL NOTES, UNLESS NOTED OTHERWISE. 1 3" NORMAL WEIGHT CONCRETE SLAB ON 3" DEEP, 20 GAGE, GALVANIZED COMPOSITE STEEL FLOOR DECK (6" TOTAL THICKNESS). REINFORCE WITH 6x6/W2.1xW2.1 WELDED WIRE REINFORCEMENT. 2 2 3 4 6" NORMAL WEIGHT CONCRETE SLAB ON 3" DEEP, 20 GAGE, GALVANIZED COMPOSITE STEEL FLOOR DECK (9" TOTAL THICKNESS). REINFORCE WITH 6x6/W2.1xW2.1 WELDED WIRE REINFORCEMENT. 5 DOWEL FOOTING AND WALL TOGETHER WITH 2-#6, TOP & BOTTTOM. PROVIDE 'CLASS B' LAP SPLICE. HOOK BARS 1'-0" INTO WALL. SECOND LEVEL FRAMING PLAN - AREA L D F K E G L H J SCALE: 1/8" = 1'-0" BENJAMIN TALPOS 10/8/2012 6:14:24 PM C:\Users\BrionP\Documents\9-2013-Revit Projects\Joplin\13-12102-00_central_struct_2012.rvt A NORTH NORTH © 2012, DLR Group of Missouri inc., a Missouri corporation CA No. 001614, ALL RIGHTS RESERVED. KEY PLAN 4' - 8" 4' - 8" 14K1 2 4' - 6" 14K1 14K1 4' - 8" 16k W12x16 (16) 47k W12x16 (16) 10k 8' - 0" 6k 26k W18x46 W18x40 (30) 36k c=3/4" 45k 26k W16x26 (20) W16x26 (20) 24k W18x60 1 106 k-ft 180 k-ft 19k 86 k-ft 21k 18k 67 k-ft 10k 31k W18x60 W18x55 39k W21x44 (38) 39k 19k W16x26 (26) 24k W16x26 (30) B7 25' - 4" B8 29' - 8" 20' - 0" B9 B10 HSS4x2x3/16 S5.4 11k 7' - 8" HSS8x6x5/16 (TOS = 129'-6") 2k LOW 15 MATCHLINE RE: S1.3B S5.4 W12x16 (26) 16k 16' - 0" 16k CA W14x26 (26) 9k S5.4 24k W12x22 29k 167 k-ft 42 k-ft 16k B11 11k W18x40 (28) B6 25' - 4" 16k 26 k-ft W12x26 19k 30k 18k HSS6x6x3/8 16 S5.4 MATCHLINE RE: S1.3C B13 16' - 0" 7' - 3" B13 B14 16k 42 k-ft 167 k-ft 29k B5 7k HSS12x2x1/4 STRINGER 13 7' - 8" 29' - 8" HSS6x6x5/16 (TOS = 130'-0") 18k W14x30 (32) 15 11k B4 30' - 0" S5.4 S5.4 11k W18x40 (28) 32' - 6" 11 10k 30k 31k 201 k-ft 37k 107 k-ft W18x40 (50) c=1" W16x26 (26) c=1" 9k 20k W18x60 86 k-ft 7k W14x22 (10) 23k 30k 10k 14 15' - 4" 27' - 2" 22k 12k W18x60 25k 10k S1.3B 21k 283 k-ft 21k 49k W18x55 37k 200 k-ft 37k 10k HSS14x6x5/16 W14x22 W12x16 (16) 10k 39 k-ft 16k W12x26 W12x16 (16) 18k W16x26 (20) MECH UNIT PER MECH. MAX WT = 750# 37k 6' - 0" W14x22 W16x26 (26) 10k W16x26 (10) 10k W16x26 (26) RE:24/S2.1, TYP W16x67 W16x26 (26) W16x26 (26) W16x26 (26) W16x26 (26) W16x26 (26) W16x26 (26) W16x26 (26) MECH UNIT PER MECH. MAX WT = 500#, TYP 28k 37k c=3/4" 25k 30k c=1 1/4" c=1 1/4" 10k W16x26 (10) 10k 24k 26k W18x40 (36) 27k 28k 27k 28k c=3/4" 27k W18x40 (30) 26k 26k 28k 27k 33k 26k 18k W12x16 (16) 269 k-ft c=1 1/4" c=1" c=1" c=1" c=1" c=1" W16x26 (26) W12x26 (30) W12x26 (26) W12x26 (26) W12x26 (26) W12x26 (26) W12x26 (26) 19k 22k 22k W18x65 18k 2k B3 W18x35 221 k-ft 10k 23k 2 27k 33k 45 k-ft 18k W12x26 W12x16 (16) W16x26 (20) W14x22 10k 370 k-ft 26k 10k W12x35 (26) W12x26 (26) W12x26 (26) W12x26 (30) 20k 19k 21k W12x26 W12x16 (16) W12x16 (16) 51k W21x83 10k 28k 21k 18k 59k 275 k-ft 27k 27k 27k 27k 24k 26k 26k 26k 138 k-ft 30k W12x26 W12x16 (16) 45k W21x55 31k 36k 17k W12x16 (16) 17k 32 k-ft 15k W12x26 W12x16 (16) 40k W21x44 (34) 37k 40k 17k W12x16 (16) 17k 72 k-ft W12x26 41k 38k c=3/4" 39k W21x50 (52) BJ 9' - 8" SPAN 1 W18x65 37k 26k 202 k-ft 23k 20k 20k 88 k-ft 25k 19k 19k 78 k-ft 23k 17k 17k 57 k-ft 18k 19k W12x16 (16) 19k W12x16 (16) 20k W12x26 24k 79 k-ft W12x16 (26) 40k c=3/4" W12x19 (26) 26k 22k 18k 24k 24k 15k 26k 111 k-ft 10k BH W16x26 (26) W16x57 36k 31k 157 k-ft 32k 31k W21x55 (58) 46k 43k W21x50 (38) 20k W12x16 (26) 20k 48k c=1" 22k 22k 22k 122 k-ft W21x55 W12x26 (30) W12x26 (30) W21x55 (48) 24' - 0" W16x26 (26) W16x50 W14x22 (22) W16x26 (26) 36k 31k 100 k-ft 25k 23k 23k 93 k-ft 36k SPAN c=1" W21x50 (38) 52 k-ft 17k 48k 29k 24k 24k 15k 10k 2 W21x50 (42) W12x16 (16) 267 k-ft W18x40 (30) 36k 23k 23k 23k 46k HSS6x6x5/16 POST 26k 168 k-ft 16k W12x16 (16) 253 k-ft 20k 15k 20k 20k 59 k-ft 18k W12x26 (26) W12x16 (26) W12x16 (26) 52 k-ft 17k 38k W21x44 (46) 1 16k 10k 29k W18x46 50k W21x73 46k 19k 31k 31k 46k 17k c=3/4" 17k W21x55 (42) 46k 25k 31k 31k 203 k-ft 54k 161 k-ft HSS6x6x5/16 (TOS = 129'-6") W14x38 W12x26 (30) W12x26 (30) W12x30 W12x26 (30) W12x26 (30) W14x38 W16x26 (26) W16x26 (26) W16x57 W16x26 (26) W16x26 (26) W16x57 36k 27k c=1" 49 k-ft 17k 18k 18k 18k 4k 37k BG B2 16k SPAN W12x16 (26) 7k HSS10x6x5/16 B1 18k W18x60 96 k-ft 1 14k W24x55 (42) 54k W12x26 S5.4 W14x22 11 HSS6x6x1/4 HANGER 27k 27k 93 k-ft 52k W12x16 (26) 7k W12x16 (26) 18k 7k W14x22 (10) 53 4' - 5" 12k 58 k-ft JOPLIN, JASPER COUNTY, MISSOURI 4' - 6" W18x60 16k 2 10-08-12 ADD #3 c=1 3/4" 5k 7290 West 133rd Street Overland Park, Kansas 66213 tel: (913)897-7811 8' - 0" 14K1 Architecture Engineering Planning Interiors 10' - 0" HSS6x6x5/16 (TOS = 130'-0") JOPLIN HIGH SCHOOL 10' - 0" 14K1 Revisions 10' - 0" c=1 1/4" 9' - 10" c=1" 9' - 10" 14K1 4' - 7" 5k 26k 16k 57 k-ft 7 k-ft 31k 16k W16x26 57 k-ft 31k 31k 143 k-ft 31k 31k 19k W16x26 (20) c=1 1/4" 8' - 5" 92 k-ft 24k 8' - 6" 23k 8' - 5" 19k 25k W16x31 (24) 23k 8' - 5" 88 k-ft 23k 8' - 6" 23k 8' - 5" 23k 137 k-ft 30k 9' - 8" 25k 33k W21x44 (38) c=1 1/4" 10' - 0" 25k W16x31 (24) 33k 31k W12x19 (26) W12x19 (26) 31k 31k 207 k-ft 39k 31k 10' - 0" c=1 1/4" c=1" 10' - 0" c=1 1/4" 10' - 0" c=1 1/4" 10' - 0" 22k c=1 3/4" 24k 24k 24k 24k 15k 57 k-ft 11' - 4" 16 S5.4 SIM 31k 23k 27k 8' - 1 1/2" W16x26 (26) W16x26 (26) W16x26 (26) W12x30 W12x26 (30) W12x26 (30) W12x26 (30) W16x26 (26) 24' - 4" S5.4 S5.4 6' - 0" 8' - 1 1/2" 251 k-ft 51 HSS6x6x1/4 HANGER HSS4x2x3/16 33k W21x50 (48) 9' - 8" W18x50 (38) 47k 43 S5.4 BF 27k 8' - 1 1/2" c=1" 8' - 1 1/2" c=1" 9' - 0" HSS12x2x1/4 STAIR STRINGER BE 33k 4k 160 k-ft 1 HSS10x6x5/8 (TOS = 124'-6") 33k W21x50 (38) 25k 89 k-ft 9' - 0" 24k 24k 24k 15k 58 k-ft 9' - 2" 33k 37k W21x55 (42) 23k 36k 27k W12x19 (26) 6' - 0" BD 40k 224 k-ft W18x60 4' - 7" 15' - 4" W18x40 4k 7 k-ft HSS6x6x5/16 (TOS = 129'-1 1/2") W21x73 14K1 4' - 8" 10k 47 k-ft 4' - 8" 14K1 1 10-04-12 ADD #2 32' - 6" W18x60 4' - 8" 14K1 13-12102-00 09/10/12 11k 58 k-ft 7 k-ft 4k 1 40k 224 k-ft 4k 7 k-ft BB BC W18x60 THIRD LEVEL FLOOR FRAMING PLAN - AREA B 4k BA 14K1 W14x26 (26) A14 A15 W14x26 (26) A13 214 k-ft A12 58 k-ft 11k A11 MATCHLINE RE: S1.3B W18x60 A10 14K1 69 k-ft 9k W18x60 A16 4k A9 W18x40 A8 5k A7 MATCHLINE RE: S1.3A SPAN A6 W12x26 47 k-ft 10k A5 4' - 4" A4 4' - 4" A3 9k W18x60 69 k-ft A2 15' - 8" A1 AZ 4' - 6" AZ B12 B PLAN NOTES: 1 A. FINISHED FLOOR ELEVATION IS 130'-0", UNLESS NOTED OTHERWISE. B. TOP OF STEEL ELEVATION IS TYPICALLY 129'-6", UNLESS NOTED OTHERWISE ON PLANS AND SECTIONS. TOP OF STEEL THAT OCCURS ON A SLOPE AND IS NOT SPECIFICALLY NOTED ON THE PLANS SHALL BE LINEARLY INTERPOLATED FROM TOP OF STEEL NOTED ON THE PLANS. C. D. E. SEE SHEET S4.1 AND S4.2 "FLOOR FRAMING TYPICAL DETAILS" FOR ADDITIONAL FRAMING REQUIREMENTS AND INFORMATION. JOIST SUPPLIER TO COORDINATE WITH MECHANICAL CONTRACTOR FOR RTU WEIGHTS, LOCATIONS AND PENETRATIONS. JOIST SUPPLIER SHALL DESIGN JOISTS FOR ALL LOADS INDICATED IN S0.1 & S0.2 'GENERAL NOTES', S0.3 'ROOF SNOW DRIFT PLAN', ON THE PLAN SHEETS, AND THE SECTION/DETAIL SHEETS. CONTRACTOR TO COORDINATE ALL WEIGHTS, LOCATIONS, AND PENETRATIONS OF EQUIPMENT WITH THE JOIST SUPPLIER PRIOR TO SUBMITTING JOIST SHOP DRAWINGS. KEY NOTES: F. REFER TO GENERAL NOTES SHEETS S0.1 AND S0.2 FOR GENERAL NOTES, ABBREVIATIONS AND SYMBOLS. L. SEE SHEET S6.1 AND S6.2 "ROOF FRAMING TYPICAL DETAILS" FOR ADDITIONAL REQUIREMENTS AND INFORMATION. G. SEE ARCHITECTURAL DRAWINGS FOR LOCATION OF SLOPED, RAISED, DEPRESSED SLABS AND DRAINS. M. ALL HSS MEMBERS SHALL HAVE 1/4" CAP PLATES AT ENDS. H. J. K. REFER TO ARCHITECTURAL DRAWINGS FOR OVERALL BUILDING GEOMETRY, WALL LOCATIONS, STAIR GEOMETRY AND ADDITIONAL PARTITION WALL REQUIREMENTS. REFER TO ARCHITECTURAL DRAWINGS FOR NON-LOAD BEARING PARTITION WALLS. REFER TO SHEETS S0.1, S0.2, S2.1, S2.2, AND S9.2 TYPICAL DETAILS FOR REINFORCING, THICKENED SLABS AND OTHER REQUIREMENTS. N. PROVIDE HSS3 1/2x2 1/2x1/4 (LLH) BETWEEN ALL JOIST WITH 2 1/2" SEATS TO SUPPORT ROOF DECK WHERE DECK SWITCHES DIRECTION. (RE: 44/S6.1) P. REFER TO 52/S2.1 FOR COLUMN AND FOOTING SCHEDULES. Q. ALL EXTERIOR EXPOSED STEEL SHALL BE GALVANIZED. 1 3" NORMAL WEIGHT CONCRETE SLAB ON 3" DEEP, 20 GAGE, GALVANIZED COMPOSITE STEEL FLOOR DECK (6" TOTAL THICKNESS). REINFORCE WITH 6x6/W2.1xW2.1 WELDED WIRE REINFORCEMENT. 2 1 1/2" DEEP, 20 GAGE, GALVANIZED WIDE RIB STEEL ROOF DECK. PROVIDE 5/8" DIAMETER PUBBLE WELDS IN 36/5 PATTERN AND 2 #10 TEK SCREWS AT SIDELAPS PER SPAN. C D 3 JOIST SUPPLIER SHALL PROVIDE 6 1/2" DEEP JOIST SEAT AT THIS END OF JOIST. 4 OPERABLE PARTITION WALL MAX WEIGHT = 15 PSF F K E G L ALL OPENINGS IN CMU WALLS (PARTITION AND LOAD BEARING) REQUIRE A LINTEL. REFER TO SHEET S9.2 FOR TYPICAL MASONRY LINTEL DETAILS AND SCHEDULES. H THIRD LEVEL FRAMING PLAN - AREA B J SCALE: 1/8" = 1'-0" BENJAMIN TALPOS 10/8/2012 6:14:31 PM C:\Users\BrionP\Documents\9-2013-Revit Projects\Joplin\13-12102-00_central_struct_2012.rvt A NORTH NORTH © 2012, DLR Group of Missouri inc., a Missouri corporation CA No. 001614, ALL RIGHTS RESERVED. KEY PLAN 24k MECH UNIT PER MECH. MAX WT = 750# 39k 39k W21x44 (38) 19k 24k 19k 30k 18k W16x26 (26) 24k W16x26 (30) B7 29' - 8" B8 20' - 0" B9 B10 11k 7' - 8" 16' - 0" 16k CA 7' - 8" 5' - 0" 5' - 0" W12x16 (26) 6k W18x46 26k W18x46 160 k-ft W12x16 (26) 26k 26k W16x26 (20) 23k W16x26 (20) 23k 10k 281 k-ft 51k 221 k-ft 37k 26k 202 k-ft 36k 31k 148 k-ft 32k 45k c=3/4" 24k W18x60 31k SPAN W18x60 180 k-ft 19k 86 k-ft 21k 17k 19k 19k 78 k-ft 22k 1 1 21k 21k W18x55 39k 39k W21x44 (38) W16x26 (20) C6 C7 25' - 4" C8 25' - 4" W18x35 (26) 10k 29' - 8" C9 C10 20k 10k 9k 20' - 0" C12 20k W12x22 (16) W18x35 (26) 10k 20k W12x22 (26) 14k W12x16 (26) 72k 559 k-ft D10 21k C13 7k W14x26 (26) 26 k-ft W12x26 19k HSS14x6x5/16 HSS4x2x3/16 S5.4 17k 9k 16' - 0" 10k 7k 23k S5.4 HSS8x6x5/16 (TOS = 129'-6") 16' - 0" 2k 15 LOW MATCHLINE RE: S1.3C 7' - 3" S5.4 B12 14k 197 k-ft 26k W18x76 29' - 8" 37k W18x76 274 k-ft C5 30' - 0" 39k HSS6x6x3/8 16 S5.4 S5.4 17k HSS6x6x5/16 (TOS = 130'-0") 18k 13 38k W18x76 240 k-ft 32' - 6" W12x22 (26) 318 k-ft 48k W18x86 25' - 7 5/8" 39k 11 HSS12x2x1/4 STRINGER 30k 19k W16x26 (20) 102 k-ft S5.4 15 30k 31k 19k 18k W18x60 86 k-ft W14x30 (32) 14 283 k-ft 49k 37k 37k 37k 201 k-ft 37k 10k MATCHLINE RE: S1.3D C14 S1.3C W18x55 27k 200 k-ft 37k 10k 22k W18x60 W14x22 (10) 12k W18x40 (50) c=1" 10k W16x26 (26) W14x22 10k W14x22 W12x16 (16) 9k 39 k-ft 16k W12x26 W12x16 (26) 25k 9k c=1" 10k 18k W12x16 (16) 10k 10k c=1 1/4" 10k W16x26 (10) 10k W14x22 W16x26 (20) 30k 30k 31k 10k W16x26 (10) 10k W16x26 (26) RE:24/S2.1, TYP 25k W16x26 (26) 17k 37k 2 W16x67 MECH UNIT PER MECH. MAX WT = 500#, TYP W12x26 (26) W12x16 (26) W12x26 (26) W12x16 (16) 40k W16x26 (36) W16x26 (26) 10k c=1 1/4" 40k W16x26 (36) c=1" c=1" W16x26 (26) c=1" W16x57 W16x26 (26) c=1" W16x26 (26) c=1" W16x26 (26) W12x26 (30) 2 26k W16x26 (20) 28k 27k c=3/4" 274 k-ft 26k 24k W12x26 (30) W18x40 (36) 182 k-ft 28k 26k W12x26 (34) 26k W12x26 (34) 28k c=3/4" 34k W18x40 (30) 26k W12x26 (34) 26k 26k W12x26 (34) W12x26 (30) W12x35 19k 28k 52k MECH UNIT PER MECH. MAX WT = 750# 27k W18x65 22k W12x26 (30) 22k W12x26 (30) 22k W21x55 26k 196 k-ft 33k 27k W21x50 (42) 196 k-ft 33k 21k W12x16 (16) 20k 17k 375 k-ft W21x83 c=1 1/4" 276 k-ft 59k 43k 45k 18k B12 10k B11 2 10-08-12 ADD #3 W21x55 (58) W12x26 W12x16 (16) 17k 28k 17k W12x16 (16) 22k 161 k-ft W21x55 (26) 27k W12x26 W12x16 (16) 13k 36k 40k 27k 27k W21x44 (34) 17k W12x16 (16) 17k 72 k-ft W12x26 22k 24k 40k W12x19 (26) C3 C4 16k W12x16 (16) 29k 168 k-ft 7290 West 133rd Street Overland Park, Kansas 66213 tel: (913)897-7811 46k 31k 31k 99 k-ft 36k 17k 17k 72 k-ft 21k 19k W12x16 (16) 41k 26k c=3/4" 6' - 0" C2 W18x60 16k Architecture Engineering Planning Interiors W18x40 (30) 36k 25k 23k 23k 94 k-ft 36k 13' - 8" C1 SPAN W12x16 (16) 2k 1' - 6 3/8" 16k 90 k-ft 16k 111 k-ft CM 9' - 8" 61 k-ft Revisions W18x40 (30) 36k 23k 23k 23k 46k 19k W12x16 (16) 20k W21x50 (52) 26k 40k 26k 26k 79 k-ft 41k c=3/4" 24k W12x26 W12x16 (16) 20k W12x16 (16) W21x50 (38) 26k 20k 52 k-ft 41k 138 k-ft 30k 48k 17k W12x26 W12x16 (16) 16k c=1" 22k W12x16 (16) 16k W21x50 (38) 22k W12x16 (16) 22k 16k 52 k-ft 48k 122 k-ft 29k 38k 18k W12x26 (30) 24k W12x26 (30) 26k 4' - 5" 1 37 k-ft JOPLIN, JASPER COUNTY, MISSOURI 15k 58 k-ft 1 10-04-12 ADD #2 c=1 1/4" 15k W16x26 52 k-ft 18k 253 k-ft 20k 15k 20k 20k 59 k-ft 18k 16k 16k 16k 49 k-ft 17k 17k W12x26 W12x16 (16) 24k 18k W12x16 (16) 18k W21x44 (46) 24k W21x55 (48) 15k 24' - 0" W16x26 (20) 18k 16k HSS8x6x5/16 (TOS = 129'-0") CL 57k W18x60 109 k-ft W21x73 46k 19k 31k 31k 46k 17k c=3/4" 17k W21x55 (42) 46k 25k 31k 31k 36k 54k 14k c=1" 207 k-ft W24x55 (42) 54k 27k 27k 27k 93 k-ft 24k 52k 18k 18k 7k W14x22 (26) 37k HSS6x6x5/16 POST (HIGH) 18k W18x60 13-12102-00 09/10/12 W12x19 (10) W16x26 (26) 24k W12x26 (30) 23k 10k 31k 94 k-ft 10k 10k W12x19 W16x40 (34) (HIGH) 23k 31k (LOW) W12x26 (30) 5k 10k 87 k-ft W12x19 W12x30 23k 23k 30k W12x26 (30) 23k W12x26 (30) 137 k-ft W16x57 (26) 10k W21x62 (38)C11 39k W12x30 W12x19 (26) 30k 30k W14x38 31k 31k c=1 1/4" W16x26 (26) W16x67 W16x26 (26) c=1 1/4" 207 k-ft 39k 31k W16x26 (26) c=1 1/4" 31k W16x26 (26) W16x67 38k 15k 7k 24k HSS6x6x5/16 (TOS = 129'-6") HSS6x6x5/16 HSS6x6x5/16 CK HSS6x6x5/16 HSS10x6x5/16 7k 4k 11 S5.4 HSS6x6x1/4 HANGER c=1 3/4" W14x22 (10) 15k 53 CJ 24k 24k 25k 15k 57 k-ft 11' - 4" 16 S5.4 S5.4 W21x62 (26) 251 k-ft S5.4 HSS4x2x3/16 37k 10k HSS6x6x5/16 (TOS = 130'-0") SPAN 51 HSS6x6x1/4 HANGER 38k W12x16 (LOW) 16k W12x16 (26) 1 W18x50 (38) 47k 43 S5.4 W21x62 c=1 1/4" 23k 27k 38k c=1" 27k c=1" W16x26 (26) W12x30 W16x26 (26) c=1" 89 k-ft 23k 24k 38k 245 k-ft HSS12x2x1/4 STAIR STRINGER CH 6' - 0" W12x26 (30) 24k W12x26 (30) 25k W12x26 (30) 15k 58 k-ft W16x26 24' - 4" 1 W21x83 W16x26 (26) W12x19 (26) 4k 6' - 0" W21x73 (26) CF 38k 245 k-ft 27k 10k CE 16k JOPLIN HIGH SCHOOL 15' - 4" (LOW) W12x14 10k (HIGH) 18K3 18K3 18K3 4k 18K3 SPAN W12x14 2 W8x10 16K3 16K3 16K3 16K3 5k 5k 4k 16K3 W10x12 16K3 16K3 16K3 16K3 16K3 W8x10 16K2 16K2 16K2 16K2 16K2 W8x10 SPAN 18K3 18K3 18K3 18K3 18K3 W10x12 HSS6x6x5/16 (TOS = 129'-1 1/2") 16K2 18' - 8" 1 THIRD LEVEL FLOOR FRAMING PLAN - AREA C 5' - 2" 42 k-ft 1 5' - 0" 11k 5' - 0" 11k 5' - 0" 26k 5' - 2" 16k c=1" 5' - 0" W16x26 (26) 5' - 0" 23k 4' - 11" W16x57 4' - 11" 31k 4' - 11" c=1 1/4" 4' - 11" W16x26 (26) 5' - 0" 148 k-ft 5' - 0" 32k 5' - 0" W16x50 5' - 0" 31k 5' - 0" c=1 1/4" 5' - 0" W16x26 (26) 4' - 8" W12x14 4' - 8" W12x22 42 k-ft 10k 4' - 8" 20KSP 4' - 8" 31k 4' - 8" 20KSP 4' - 7" 2 20KSP 4' - 7" W12x14 4' - 3" 22KSP 4' - 3" 16k CD W14x26 (26) 4' - 4 1/2" 212 k-ft 4' - 4 1/2" 167 k-ft 29k 4' - 4 1/2" 2 22KSP 4' - 3" 16k 11k 4' - 4 1/2" 22KSP 4' - 3" W12x16 (16) SPAN 13k 13k 22KSP 4' - 3" B14 7' - 8" 16k 5' - 2" SPAN 4' - 4 5/8" W18x60 10k 10k 10k 10k 7' - 8" (HIGH) W12x16 7' - 8" W12x30 5' - 0" 16k 7' - 8" (LOW) 5' - 2" W12x16 (16) 29k 167 k-ft W12x30 10k B13 10k W8x18 8K1 8K1 8K1 13k 13k 10k W18x40 (28) W16x31 (HIGH) 8K1 10k 10k W8x18 8K1 8K1 8K1 8K1 15k 15k W12x19 10k 23k 231 k-ft 14k W12x30 (HIGH) 8K1 10k W8x18 8K1 8K1 8K1 8K1 8K1 10k 10k W8x18 10k 236 k-ft 14k W16x31 (LOW) 14k 14k 10k 16k W18x65 (HIGH) W12x30 (LOW) 15k 15k W12x14 10k W12x16 (16) 7' - 8" 16k 30' - 8" W16x36 SPAN 10k 10k (LOW) 8K1 8K1 W16x36 2 W12x19 10k 5k 15k 15k 8K1 8K1 8K1 10k W8x18 10k 8K1 14k 14k 10k 4k (HIGH) 4' - 3" W10x22 10k 4k W12x30 10k 4k (LOW) 4k W12x30 4' - 3" W14x22 10k 4k 13k 13k CC 4' - 3" 8K1 4' - 3" 8K1 8K1 4' - 3" 8K1 10k 10k W8x18 7' - 10" 4' - 4 5/8" 10k 8K1 W12x14 7' - 3" 42 k-ft 29k 167 k-ft 17' - 6" 10k 16' - 0" 16k W12x22 42 k-ft 16k CB 11k W18x40 (28) B6 25' - 4" 167 k-ft 29k B5 25' - 4" W18x40 (28) B4 29' - 8" LOW 15 B13 11k B3 30' - 0" 46k B2 32' - 6" 16k W12x16 (26) W18x65 27' - 2" 2k HSS8x6x5/16 (TOS = 129'-6") S5.4 7' - 8" 11k 11k W18x40 (28) 15' - 4" B1 9' - 8" 16k HSS4x2x3/16 S5.4 2k 4' - 5" HSS10x6x5/8 (TOS = 124'-6") S5.4 14 31k 283 k-ft 37k 37k 201 k-ft 37k W18x55 37k 27k 21k 49k 21k W18x55 16 S5.4 13 W14x26 (26) BJ 200 k-ft 37k 27k 28k 30k 26k 28k 27k 28k 27k 28k 27k 33k 26k 26k 19k 22k 33k W12x19 (26) 26k 22k 22k 18k 24k 24k 15k 26k B PLAN NOTES: 1 A. FINISHED FLOOR ELEVATION IS 130'-0", UNLESS NOTED OTHERWISE. B. TOP OF STEEL ELEVATION IS TYPICALLY 129'-6", UNLESS NOTED OTHERWISE ON PLANS AND SECTIONS. TOP OF STEEL THAT OCCURS ON A SLOPE AND IS NOT SPECIFICALLY NOTED ON THE PLANS SHALL BE LINEARLY INTERPOLATED FROM TOP OF STEEL NOTED ON THE PLANS. C. D. E. SEE SHEET S4.1 AND S4.2 "FLOOR FRAMING TYPICAL DETAILS" FOR ADDITIONAL FRAMING REQUIREMENTS AND INFORMATION. JOIST SUPPLIER TO COORDINATE WITH MECHANICAL CONTRACTOR FOR RTU WEIGHTS, LOCATIONS AND PENETRATIONS. JOIST SUPPLIER SHALL DESIGN JOISTS FOR ALL LOADS INDICATED IN S0.1 & S0.2 'GENERAL NOTES', S0.3 'ROOF SNOW DRIFT PLAN', ON THE PLAN SHEETS, AND THE SECTION/DETAIL SHEETS. CONTRACTOR TO COORDINATE ALL WEIGHTS, LOCATIONS, AND PENETRATIONS OF EQUIPMENT WITH THE JOIST SUPPLIER PRIOR TO SUBMITTING JOIST SHOP DRAWINGS. KEY NOTES: F. REFER TO GENERAL NOTES SHEETS S0.1 AND S0.2 FOR GENERAL NOTES, ABBREVIATIONS AND SYMBOLS. L. SEE SHEET S6.1 AND S6.2 "ROOF FRAMING TYPICAL DETAILS" FOR ADDITIONAL REQUIREMENTS AND INFORMATION. G. SEE ARCHITECTURAL DRAWINGS FOR LOCATION OF SLOPED, RAISED, DEPRESSED SLABS AND DRAINS. M. ALL HSS MEMBERS SHALL HAVE 1/4" CAP PLATES AT ENDS. H. J. K. REFER TO ARCHITECTURAL DRAWINGS FOR OVERALL BUILDING GEOMETRY, WALL LOCATIONS, STAIR GEOMETRY AND ADDITIONAL PARTITION WALL REQUIREMENTS. REFER TO ARCHITECTURAL DRAWINGS FOR NON-LOAD BEARING PARTITION WALLS. REFER TO SHEETS S0.1, S0.2, S2.1, S2.2, AND S9.2 TYPICAL DETAILS FOR REINFORCING, THICKENED SLABS AND OTHER REQUIREMENTS. N. PROVIDE HSS3 1/2x2 1/2x1/4 (LLH) BETWEEN ALL JOIST WITH 2 1/2" SEATS TO SUPPORT ROOF DECK WHERE DECK SWITCHES DIRECTION. (RE: 44/S6.1) P. REFER TO 52/S2.1 FOR COLUMN AND FOOTING SCHEDULES. Q. ALL EXTERIOR EXPOSED STEEL SHALL BE GALVANIZED. 1 3" NORMAL WEIGHT CONCRETE SLAB ON 3" DEEP, 20 GAGE, GALVANIZED COMPOSITE STEEL FLOOR DECK (6" TOTAL THICKNESS). REINFORCE WITH 6x6/W2.1xW2.1 WELDED WIRE REINFORCEMENT. 2 1 1/2" DEEP, 20 GAGE, GALVANIZED WIDE RIB STEEL ROOF DECK. PROVIDE 5/8" DIAMETER PUBBLE WELDS IN 36/5 PATTERN AND 2 #10 TEK SCREWS AT SIDELAPS PER SPAN. C D 3 JOIST SUPPLIER SHALL PROVIDE 6 1/2" DEEP JOIST SEAT AT THIS END OF JOIST. 4 OPERABLE PARTITION WALL MAX WEIGHT = 15 PSF F K E G L ALL OPENINGS IN CMU WALLS (PARTITION AND LOAD BEARING) REQUIRE A LINTEL. REFER TO SHEET S9.2 FOR TYPICAL MASONRY LINTEL DETAILS AND SCHEDULES. H THIRD LEVEL FRAMING PLAN - AREA C J SCALE: 1/8" = 1'-0" BENJAMIN TALPOS 10/8/2012 6:14:39 PM C:\Users\BrionP\Documents\9-2013-Revit Projects\Joplin\13-12102-00_central_struct_2012.rvt A NORTH NORTH © 2012, DLR Group of Missouri inc., a Missouri corporation CA No. 001614, ALL RIGHTS RESERVED. KEY PLAN W16x57 21k W18x55 21k 39k 39k W21x44 (38) W16x26 (20) S5.4 17k 17k W16x26 (20) 2k C6 25' - 4" C7 25' - 4" C8 29' - 8" C9 C10 20k 20' - 0" C12 20k W12x22 (16) 20k DA W18x35 (26) 10k W18x86 16' - 0" 72k 559 k-ft 21k W18x35 42k 263 k-ft 11 W12x22 (26) 24k 24k W12x22 (26) 24k 24k W12x22 (26) 24k S5.4 16k 16k W12x16 (16) 16k W18x76 151 k-ft 28k 20k W18x35 416 k-ft 12k 86 k-ft 21 k-ft 11k 27k 27k 15k 16k W12x16 (16) 25k 133 k-ft 60k W18x76 421 k-ft 16k W18x76 W18x86 27k 39k 213 k-ft W18x76 30' - 8" 67k DB B12 10k 16k W12x16 (16) HSS14x4x1/4 STAIR STRINGER B12 11 k-ft 1 24k S5.4 14k 99 k-ft 1 LOW 15 16' - 0" 14k W12x16 (26) 10k 345 k-ft 50k 580 k-ft 9k 197 k-ft 26k W18x76 C5 29' - 8" W12x22 (26) 188 k-ft 31k C3 C4 30' - 0" 9k 2k HSS8x6x5/16 (TOS = 129'-6") SPAN 32' - 6" 10k 38k W18x76 240 k-ft C2 25' - 7 5/8" W18x35 (26) 10k 39k 318 k-ft 48k W18x86 1' - 6 3/8" W12x22 (26) 37k W18x76 274 k-ft C1 9' - 8" 15' - 4" 4' - 5" 39k 29k 182 k-ft 13' - 8" HSS4x2x3/16 S5.4 19k 30k 19k 16 S5.4 13 30k 31k 19k HSS6x6x3/8 15 S5.4 14 283 k-ft 49k 37k 201 k-ft 37k W18x55 37k 37k 27k 6' - 0" CM 200 k-ft 37k 27k 28k c=3/4" 182 k-ft W18x40 (36) 24k 26k 26k 28k 34k 28k c=3/4" 10k MECH UNIT PER MECH. MAX WT = 750# 27k W18x40 (30) 26k 26k 26k 28k W12x19 (26) W18x65 19k 22k 22k 196 k-ft 33k 27k 26k W21x50 (42) 22k 18k 24k 24k 15k 26k CL 196 k-ft 33k 10k 111 k-ft 19k 7k MATCHLINE RE: S1.3D W14x26 (30) W12x16 8k W18x60 (26) W21x44 6k 18k c=1" W18x35 (40) W16x26 (26) W18x55 29k 29k 27k W16x26 D9 22k 20k 19k 21k 23k 22k E10 56 S5.4 17k 36' - 0" D10 W18x35 (26) 18k 30k 79 k-ft 17k 72 k-ft 16' - 0" W12x19 (20) D8 29' - 8" MATCHLINE RE: S1.3E W12x19 (20) D7 25' - 4" W12x19 (20) 25' - 4" MATCHLINE RE: S1.3D 26k D11 C13 12' - 0" B11 HSS6x6x3/8 15 S5.4 16 S5.4 F1 KEY PLAN B PLAN NOTES: 1 A. FINISHED FLOOR ELEVATION IS 130'-0", UNLESS NOTED OTHERWISE. B. TOP OF STEEL ELEVATION IS TYPICALLY 129'-6", UNLESS NOTED OTHERWISE ON PLANS AND SECTIONS. TOP OF STEEL THAT OCCURS ON A SLOPE AND IS NOT SPECIFICALLY NOTED ON THE PLANS SHALL BE LINEARLY INTERPOLATED FROM TOP OF STEEL NOTED ON THE PLANS. C. D. E. SEE SHEET S4.1 AND S4.2 "FLOOR FRAMING TYPICAL DETAILS" FOR ADDITIONAL FRAMING REQUIREMENTS AND INFORMATION. JOIST SUPPLIER TO COORDINATE WITH MECHANICAL CONTRACTOR FOR RTU WEIGHTS, LOCATIONS AND PENETRATIONS. JOIST SUPPLIER SHALL DESIGN JOISTS FOR ALL LOADS INDICATED IN S0.1 & S0.2 'GENERAL NOTES', S0.3 'ROOF SNOW DRIFT PLAN', ON THE PLAN SHEETS, AND THE SECTION/DETAIL SHEETS. CONTRACTOR TO COORDINATE ALL WEIGHTS, LOCATIONS, AND PENETRATIONS OF EQUIPMENT WITH THE JOIST SUPPLIER PRIOR TO SUBMITTING JOIST SHOP DRAWINGS. KEY NOTES: F. REFER TO GENERAL NOTES SHEETS S0.1 AND S0.2 FOR GENERAL NOTES, ABBREVIATIONS AND SYMBOLS. L. SEE SHEET S6.1 AND S6.2 "ROOF FRAMING TYPICAL DETAILS" FOR ADDITIONAL REQUIREMENTS AND INFORMATION. G. SEE ARCHITECTURAL DRAWINGS FOR LOCATION OF SLOPED, RAISED, DEPRESSED SLABS AND DRAINS. M. ALL HSS MEMBERS SHALL HAVE 1/4" CAP PLATES AT ENDS. H. J. K. REFER TO ARCHITECTURAL DRAWINGS FOR OVERALL BUILDING GEOMETRY, WALL LOCATIONS, STAIR GEOMETRY AND ADDITIONAL PARTITION WALL REQUIREMENTS. REFER TO ARCHITECTURAL DRAWINGS FOR NON-LOAD BEARING PARTITION WALLS. REFER TO SHEETS S0.1, S0.2, S2.1, S2.2, AND S9.2 TYPICAL DETAILS FOR REINFORCING, THICKENED SLABS AND OTHER REQUIREMENTS. N. PROVIDE HSS3 1/2x2 1/2x1/4 (LLH) BETWEEN ALL JOIST WITH 2 1/2" SEATS TO SUPPORT ROOF DECK WHERE DECK SWITCHES DIRECTION. (RE: 44/S6.1) P. REFER TO 52/S2.1 FOR COLUMN AND FOOTING SCHEDULES. Q. ALL EXTERIOR EXPOSED STEEL SHALL BE GALVANIZED. 1 3" NORMAL WEIGHT CONCRETE SLAB ON 3" DEEP, 20 GAGE, GALVANIZED COMPOSITE STEEL FLOOR DECK (6" TOTAL THICKNESS). REINFORCE WITH 6x6/W2.1xW2.1 WELDED WIRE REINFORCEMENT. 2 1 1/2" DEEP, 20 GAGE, GALVANIZED WIDE RIB STEEL ROOF DECK. PROVIDE 5/8" DIAMETER PUBBLE WELDS IN 36/5 PATTERN AND 2 #10 TEK SCREWS AT SIDELAPS PER SPAN. C D 3 JOIST SUPPLIER SHALL PROVIDE 6 1/2" DEEP JOIST SEAT AT THIS END OF JOIST. 4 OPERABLE PARTITION WALL MAX WEIGHT = 15 PSF F K E G L ALL OPENINGS IN CMU WALLS (PARTITION AND LOAD BEARING) REQUIRE A LINTEL. REFER TO SHEET S9.2 FOR TYPICAL MASONRY LINTEL DETAILS AND SCHEDULES. H THIRD LEVEL FRAMING PLAN - AREA D J SCALE: 1/8" = 1'-0" BENJAMIN TALPOS 10/8/2012 6:14:46 PM C:\Users\BrionP\Documents\9-2013-Revit Projects\Joplin\13-12102-00_central_struct_2012.rvt A NORTH NORTH © 2012, DLR Group of Missouri inc., a Missouri corporation CA No. 001614, ALL RIGHTS RESERVED. W16x26 (20) 2 10-08-12 ADD #3 38k 28k 31k 283 k-ft 59k c=1" 7290 West 133rd Street Overland Park, Kansas 66213 tel: (913)897-7811 W21x44 (36) 49k 37k 37k 59k OPP HAND S1.3D W18x55 11 S5.4 15k 21k 201 k-ft 37k Architecture Engineering Planning Interiors 30k 134 k-ft ?k Revisions 87 k-ft 20k 32k 30k c=1" 10k W16x26 (26) W14x22 30k 10k W16x26 (10) 10k W12x19 (20) D6 25k D12 W16x50 RE:24/S2.1, TYP W16x26 (26) 10k W16x26 (10) 10k 10k 81 k-ft 2 W14x22 175 k-ft 34k c=1 1/4" 10k SPAN W12x19 (20) 29' - 8" D5 25k W18x60 (32) ?k W16x67 MECH UNIT PER MECH. MAX WT = 500#, TYP W12x19 (20) D4 30' - 0" 25k MATCHLINE RE: S1.3F 1 10-04-12 ADD #2 W16x26 (20) W12x16 (16) 13-12102-00 09/10/12 65 k-ft 180 k-ft 8k 31k W18x60 25 k-ft 25k 18k 1 7k 260 k-ft 50k 218 k-ft 24k 18k W12x16 (16) W12x19 (20) 21k W18x55 37k 182 k-ft 200 k-ft 37k 14k 32' - 6" W12x26 (26) W12x16 (16) 18k 19k 26k W16x26 (20) 10k W12x19 (20) 27' - 2" D3 W12x16 (16) 116 k-ft 17k 61 k-ft 10k W18x60 9k 26k 58 k-ft W12x26 W12x16 (16) 20k 19k c=1 1/4" 2 W16x26 (36) c=1 1/4" W16x26 (36) c=1" W16x26 (26) c=1" W16x26 (26) 27k c=1" W16x26 (26) 27k W16x57 (26) 34k c=1" c=1" W12x26 (30) 28k W16x26 (26) c=3/4" 27k W18x40 (36) 6' - 0" 9' - 8" W14x26 (28) W18x76 SPAN 1 168 k-ft 274 k-ft 74 k-ft D2 16k W18x46 24k W12x26 (30) 26k W12x26 (34) 28k 26k W12x26 (34) 28k c=3/4" W16x26 (26) W18x40 (30) 26k W12x26 (34) 26k W12x26 (34) 28k 26k 19k W12x35 W12x26 (30) 197 k-ft 54k 27k W18x65 22k W12x26 (30) 22k W12x26 (30) 197 k-ft 54k 22k 26k W12x19 (26) W21x50 (42) 18k W21x55 W12x26 (30) 24k W12x26 (30) 26k W12x16 W12x16 (16) 21k W12x16 (16) 52k W21x83 375 k-ft W14x22 10k 28k 20k 18k 59k 276 k-ft 27k 22k 27k 27k 24k 26k 26k 26k 26k 26k 138 k-ft 30k 22k 22k 22k 24k W12x26 W12x16 (16) 45k W21x55 1 DJ D1 23k 18k W16x26 (20) 37k 26k 202 k-ft 36k 19k 23k 10k 36k 17k W12x16 (16) 17k 13k W12x26 W12x16 (16) 40k W21x44 (34) 31k 40k 17k W12x16 (16) 17k 72 k-ft 22k W12x26 W12x16 (16) 41k W21x50 (52) 37k 40k 19k W12x16 (16) 41k c=3/4" 20k 78 k-ft 24k W12x30 W12x16 (16) W21x50 (38) 40k 41k 20k W12x16 (16) 54k c=1" 20k 58 k-ft 19k W12x26 W12x16 (16) 16k W12x16 (16) W21x50 (38) 40k 54k 16k W12x16 (16) 16k 52 k-ft 19k W12x16 W12x16 (16) 38k W21x44 (46) 24k W21x55 (48) 15k DH 4' - 5" W18x65 W16x26 (26) W16x57 W16x26 (26) 26k W16x26 (20) 20k 25k 19k 19k 78 k-ft 26k 88 k-ft 45k W21x55 (58) 31k 32k 157 k-ft 31k 31k 100 k-ft 25k 23k 46k 17k 36k 17k 72 k-ft 23k 94 k-ft 23k W18x40 (30) 36k 21k 36k 17k 17k 23k 23k 23k 19k 19k W18x40 (30) 36k 14k 46k W21x55 (58) 20k 15k 45k 31k 31k 25k 46k c=3/4" 20k W21x55 (42) 20k 44 k-ft 17k 16k 46k 31k 31k 29k 27k 16k 93 k-ft 24k 27k 54k c=1" HSS6x6x5/16 POST 24' - 0" W16x50 W16x26 (26) W16x26 (26) W14x38 W12x26 (30) W12x26 (30) W12x30 W12x26 (30) W12x26 (30) W14x38 W16x26 (26) W16x26 (26) W16x67 W16x26 (26) W16x26 (26) W16x26 (26) W16x26 (26) W16x26 (26) W16x26 (26) W12x30 W12x26 (30) 27k 27k 16k W24x55 (42) 161 k-ft 15k HSS6x6x5/16 (TOS = 129'-6") 160 k-ft 16k W12x16 (16) 43k 37k DG 29k HSS6x6x1/4 HANGER 4k 6' - 0" HSS10x6x5/16 18k S5.4 DF 29k 7k W12x16 (16) 11 S5.4 7k 18k 53 HSS4x2x3/16 26k W18x46 W14x22 (10) W14x22 (26) 11' - 4" 16 S5.4 SPAN 54k 49 k-ft S5.4 24k HSS6x6x1/4 HANGER 7k 51 52k c=1 3/4" 18k W18x50 (38) 17k 47k43 S5.4 DE 18k 25k 27k HSS12x2x1/4 STAIR STRINGER 15k 57 k-ft HSS10x6x5/8 (TOS = 124'-6") 6k 1 122 k-ft 1 W12x26 (30) W12x26 (30) W16x26 24' - 4" 7k c=1" W12x16 (16) JOPLIN, JASPER COUNTY, MISSOURI 16k JOPLIN HIGH SCHOOL W18x35 (28) 47k 16k W12x16 (16) c=1 1/4" 18k W18x60 96 k-ft 63 k-ft THIRD LEVEL FLOOR FRAMING PLAN - AREA D 40 k-ft W14x26 (26) 74 k-ft 17k W18x60 HSS6x6x5/16 (TOS = 130'-0") 201 k-ft 68 k-ft 15k 16k 11k 23k 16k 26k 16k W16x26 (26) 23k W18x40 (42) 23k 16k W12x16 (16) 23k W18x40 (30) W18x35 (32) 23k 54k 31k 143 k-ft 31k 31k 33k W16x26 (30) 92 k-ft 23k 23k W21x44 (38) 33k 33k 24k W12x22 (26) 25k W16x31 (24) 24k 25k 87 k-ft 23k 137 k-ft 30k c=1 1/4" c=1 1/4" c=1 1/4" c=1 1/4" c=1" c=1" c=1" c=1" 25k W16x31 (24) 24k 25k 23k 31k 207 k-ft 33k W12x19 (26) W21x50 (48) 33k 39k 31k 31k 33k 31k W21x50 (38) 33k 29k 27k 27k 40k 224 k-ft 89 k-ft 24k 25k 15k 58 k-ft W21x73 37k W21x55 (42) 23k 36k 24k DD 40k 224 k-ft 27k 6' - 0" W12x19 (26) DC W12x19 (26) 15k HSS6x6x5/16 (TOS = 129'-1 1/2") 24k 31k 1 27k 15' - 4" W24x55 (28) 7' - 3" DJ 21k W18x55 21k W18x55 59k W21x44 (36) 59k c=1" 38k 29k W16x26 (20) 27k 26k W16x26 W18x35 (26) 56 S5.4 17k 15k 22k OPP HAND 18k 30k S5.4 72 k-ft 20k 19k 21k 23k 61 k-ft 19k 18k 14k 16 S5.4 S5.4 17k 122 k-ft HSS6x6x3/8 15 15k 26k W12x26 415 k-ft 20k 348 k-ft B11 W12x19 (20) W12x19 (20) 22k W12x19 (20) 20k W12x19 (20) 19k 38k W40x149 21k EA 16' - 0" 12 13 S5.5 S5.5 14k 38k W12x19 (20) D10 21k D9 W12x19 (20) D8 17k 36' - 0" 23k D7 29' - 8" MATCHLINE RE: S1.3E 22k D6 25' - 4" W12x19 (20) D5 25' - 4" 22k D4 29' - 8" 22k D3 30' - 0" W12x19 (20) D2 32' - 6" 14k 27' - 2" 11 HSS12x2x1/4 STRINGER MATCHLINE RE: S1.3D 20' - 8" D1 9' - 8" 22k 14k 74 k-ft 4' - 5" 79 k-ft 29k 30k 81 k-ft 28k 31k 283 k-ft 49k 37k 201 k-ft 37k 37k 37k 27k 27k 182 k-ft 34k 27k 200 k-ft 37k 27k W12x19 (26) 28k 24k 26k 28k 26k 28k 26k 26k 28k 26k 197 k-ft 54k 19k 22k 22k 197 k-ft 54k 22k 26k 18k 24k 24k 15k 26k 15 HSS4x2x3/16 HSS6x2x1/4 HANGER W12x19 (20) W12x19 (20) W12x19 (20) W12x19 (20) W12x19 (20) 1 14k 21k 11k 22k W18x50 (26) 104 k-ft 14k 16k 49k-ft 20k 32k 22k-ft 22k 3k-ft W14x22 (12) 32k 5k 21k c=1" 13 12KSP 16 S5.4 12KSP 12KSP 15 S5.4 S5.4 21k 34k 31k 256 k-ft 45k 22k HSS6x6x3/8 W18x35 23k 4k 16k EJ 4k 15 33 S5.4 S5.4 4' - 8" 4' - 8" 4' - 10 1/2" 4' - 6 3/8" 4' - 5 1/8" 4' - 5 1/8" 14K1 14K1 14K1 14K1 4' - 5 1/8" 4' - 5 1/8" G1 E12 D11 2 10-08-12 ADD #3 4' - 8" 7290 West 133rd Street Overland Park, Kansas 66213 tel: (913)897-7811 4' - 8" Architecture Engineering Planning Interiors 4' - 8" Revisions 4' - 8" 1 10-04-12 ADD #2 4' - 8" 13-12102-00 09/10/12 4' - 8" S1.3E 4' - 8" 3k 4' - 8" 16KSP C13 16KSP E11 14K1 16' - 0" 16KSP E10 16' - 0" W12x26 20' - 0" 16KSP E9 W18x35 37k MATCHLINE RE: S1.3G 29' - 8" W18x40 (26) 21k 16KSP E8 35k 35k 34k 27k 25' - 4" W21x44 (38) W18x35 (24) c=1 1/4" W16x26 (26) W16x67 W16x26 (26) W16x26 (26) W16x26 (26) c=1" c=1" W16x26 (26) W16x57 W16x26 (26) c=1" c=1" E7 37k 8' - 10 1/4" 21k 16KSP E6 104 k-ft 31k 16KSP E5 25' - 4" W18x55 (26) MATCHLINE RE: S1.3E 29' - 8" 179 k-ft 27k 10k W16x26 (10) 10k 3k 37k W16x36 (26) c=3/4" 16k S5.4 HSS12x2x1/4 STRINGER HSS4x2x3/16 16KSP E4 30' - 0" 177 k-ft 31k 16KSP E3 32' - 6" W18x55 16KSP E2 27' - 2" 127 k-ft 27k W12x19 E1 9' - 8" W16x26 (26) c=1" W16x26 (26) W12x26 (30) 6' - 0" EL 4' - 5" RE:24/S2.1, TYP 28k 27k c=3/4" MECH UNIT PER MECH. MAX WT = 500#, TYP 24k W12x26 (30) W18x40 (36) 182 k-ft 28k 26k W12x26 (34) 26k W12x26 (34) 28k 34k c=3/4" 26k W12x26 (34) W18x40 (30) 27k 28k 26k W12x26 (34) 26k 19k W12x35 W12x26 (30) 22k W12x26 (30) W12x26 (30) 22k W18x40 27k 26k 22k W21x55 18k W12x26 (26) 24k W12x26 (30) W21x50 (42) 196 k-ft 33k W12x19 (26) EK 24k W21x55 (48) 15k 24' - 0" 26k 196 k-ft 33k MATCHLINE RE: S1.3F MATCHLINE RE: S1.3E W18x50 27k 30k W18x35 (32) 34k 11k W12x16 (10) 11k W12x16 12k 8k (10) 8k 11 8' - 10 1/4" 2 2 JOPLIN, JASPER COUNTY, MISSOURI 12k 28k 121 k-ft 30k c=1" W16x26 (26) 132 k-ft 10k W12x16 (10) 10k W18x35 (10) (8) 12KSP 33k W16x26 10k W16x26 (10) 1k 12KSP 277 k-ft c=1 1/4" 7k (8) 1k JOPLIN HIGH SCHOOL 19k 22k W12x26 (20) W12x19 (20) 15k W12x26 (20) 26k 29k W18x50 28k 142 k-ft W12x19 18k 26k 99 k-ft 31k W16x26 (20) 26k 28k 1 W16x36 (26) 53k 378 k-ft HSS6x6x5/16 POST 24k W12x26 21k 24k 24k W12x26 28k W21x83 60k 277 k-ft 27k 22k 27k 27k 24k 26k 26k 26k 26k 26k 138 k-ft 30k 22k 22k 22k 29k 122 k-ft 21k 45k W21x55 c=3/4" 18k 36k 17k 17k W16x40 13k 40k W21x44 (34) 148 k-ft 28k 7k 40k 17k 17k 46 k-ft W12x26 17k 41k W18x35 (14) W18x60 138 k-ft 7k c=3/4" 13kW18x60 64 k-ft 35k W18x60 W14x22 (10) W21x50 (52) 16k 11k W12x19 (10) 40k 19k 20k 49 k-ft W12x26 41k 27k 8k W12x19 (10) c=3/4" 19k 20k W21x50 (38) 22k 10k W12x16 (10) 10k 28k W18x35 101 k-ft 21k W12x16 (16) W16x26 (20) 48k 41k 33k 83 k-ft W18x60 c=1" W16x26 (26) W16x50 30k 159 k-ft 32k 28k 22k W16x26 (20) 102 k-ft 21k W12x16 (16) 26k 31k 48k 20k 52 k-ft W12x26 17k 16k c=1" 22k 144 k-ft 26k 29k c=1 1/4" W16x26 (26) W16x50 c=1 1/4" W16x26 (26) 31k 21k W12x16 (16) 93 k-ft 17k W12x16 (16) 25k 17k 26k 47k 36k W21x50 (38) 23k W16x26 (20) 133 k-ft 31k 24k 61 k-ft SPAN c=3/4" 37k 48k 19k 18k 19k 19k W12x19 (20) 21k 21k W12x19 (20) 23k 23k 23k 143 k-ft 31k 27k W16x26 (20) c=1 1/4" 38k 24k 24k 15k W12x19 (20) 23k W12x19 (20) 15k 15k 31k c=1 1/4" 31k 103 k-ft 26k W16x26 (26) 87 k-ft 24k 23k W12x26 (30) W16x50 23k 23k W21x55 (58) 47k 36k W21x44 (46) 161 k-ft HSS6x6x5/16 (TOS = 129'-6") 28k 122 k-ft 1 36k W12x16 (16) 17k W12x16 (16) 75 k-ft 17k W12x16 (16) W18x40 (30) 36k 21k 36k W18x40 (30) 23k 99 k-ft 25k 23k 23k 97 k-ft 36k 55 k-ft 19k W12x16 (16) 46k 18k 20k W12x16 (16) 55 k-ft c=3/4" 25k 31k 31k 32k 155 k-ft W21x55 (58) 45k 21k 20k W12x16 (16) 46k 40k c=3/4" 17k 25k W16x31 (24) W12x26 (30) 76 k-ft 23k 23k W12x26 (30) W16x77 23k W12x26 (30) 94 k-ft 24k c=1 1/4" W16x26 (26) W12x30 c=1 1/4" W16x26 (26) W16x50 c=1 1/4" W16x26 (26) 31k 20k c=3/4" W12x16 (16) 49 k-ft 16k W12x16 (16) W21x55 (42) 46k 18k 16k 31k 203 k-ft 36k 27k 27k 93 k-ft 27k W12x16 (16) 54k SPAN W21x44 (46) 31k W12x19 (26) W12x19 (26) 31k 31k 144 k-ft 31k 31k c=1 1/4" W16x26 (26) W16x57 c=1" W16x26 (26) 25k 41k 37k EH 16k HSS6x6x1/4 HANGER c=1" 16k HSS10x6x5/16 16k EG W12x26 S5.4 25k W16x31 (24) 36k 7k 52 k-ft 11 S5.4 7k 17k 53 HSS4x2x3/16 33k W21x50 (48) W14x22 (10) 18k 11' - 4" 16 S5.4 17k 18k W12x16 (16) S5.4 W24x55 (42) 54k 49 k-ft 18k W12x16 (16) 18k 7k W14x22 (26) 4k 52k W12x16 (16) c=1 3/4" 24k 24k 24k 25k 15k 57 k-ft 51 HSS6x6x1/4 HANGER 33k 1 W18x50 (38) 47k 43 S5.4 EF 31k 23k 27k 27k c=1" 23k W12x26 W16x26 (26) 24k W12x19 (26) c=1" 24k W12x19 (26) HSS12x2x1/4 STAIR STRINGER HSS10x6x5/8 (TOS = 124'-6") 33k W21x50 (38) 25k W16x26 (26) 25k W12x19 (26) 15k 58 k-ft W16x26 24' - 4" 1 6' - 0" 37k W21x55 (42) 33k 90 k-ft 36k 27k W12x19 (26) 6' - 0" ED 40k 224 k-ft 26k W12x26 (26) 417 k-ft W12x19 (20) 20' - 10 1/2" HSS6x6x5/16 (TOS = 129'-1 1/2") W21x73 72k W40x149 (26) 349 k-ft 1 40k 224 k-ft SPAN 20k 67k EB EC 22k 14k 22k 1 THIRD LEVEL FLOOR FRAMING PLAN - AREA E W12x19 (20) W12x19 (20) W12x19 (20) 19' - 9 1/2" S5.4 G2 B PLAN NOTES: 1 A. FINISHED FLOOR ELEVATION IS 130'-0", UNLESS NOTED OTHERWISE. B. TOP OF STEEL ELEVATION IS TYPICALLY 129'-6", UNLESS NOTED OTHERWISE ON PLANS AND SECTIONS. TOP OF STEEL THAT OCCURS ON A SLOPE AND IS NOT SPECIFICALLY NOTED ON THE PLANS SHALL BE LINEARLY INTERPOLATED FROM TOP OF STEEL NOTED ON THE PLANS. C. D. E. SEE SHEET S4.1 AND S4.2 "FLOOR FRAMING TYPICAL DETAILS" FOR ADDITIONAL FRAMING REQUIREMENTS AND INFORMATION. JOIST SUPPLIER TO COORDINATE WITH MECHANICAL CONTRACTOR FOR RTU WEIGHTS, LOCATIONS AND PENETRATIONS. JOIST SUPPLIER SHALL DESIGN JOISTS FOR ALL LOADS INDICATED IN S0.1 & S0.2 'GENERAL NOTES', S0.3 'ROOF SNOW DRIFT PLAN', ON THE PLAN SHEETS, AND THE SECTION/DETAIL SHEETS. CONTRACTOR TO COORDINATE ALL WEIGHTS, LOCATIONS, AND PENETRATIONS OF EQUIPMENT WITH THE JOIST SUPPLIER PRIOR TO SUBMITTING JOIST SHOP DRAWINGS. KEY NOTES: F. REFER TO GENERAL NOTES SHEETS S0.1 AND S0.2 FOR GENERAL NOTES, ABBREVIATIONS AND SYMBOLS. L. SEE SHEET S6.1 AND S6.2 "ROOF FRAMING TYPICAL DETAILS" FOR ADDITIONAL REQUIREMENTS AND INFORMATION. G. SEE ARCHITECTURAL DRAWINGS FOR LOCATION OF SLOPED, RAISED, DEPRESSED SLABS AND DRAINS. M. ALL HSS MEMBERS SHALL HAVE 1/4" CAP PLATES AT ENDS. H. J. K. REFER TO ARCHITECTURAL DRAWINGS FOR OVERALL BUILDING GEOMETRY, WALL LOCATIONS, STAIR GEOMETRY AND ADDITIONAL PARTITION WALL REQUIREMENTS. REFER TO ARCHITECTURAL DRAWINGS FOR NON-LOAD BEARING PARTITION WALLS. REFER TO SHEETS S0.1, S0.2, S2.1, S2.2, AND S9.2 TYPICAL DETAILS FOR REINFORCING, THICKENED SLABS AND OTHER REQUIREMENTS. N. PROVIDE HSS3 1/2x2 1/2x1/4 (LLH) BETWEEN ALL JOIST WITH 2 1/2" SEATS TO SUPPORT ROOF DECK WHERE DECK SWITCHES DIRECTION. (RE: 44/S6.1) P. REFER TO 52/S2.1 FOR COLUMN AND FOOTING SCHEDULES. Q. ALL EXTERIOR EXPOSED STEEL SHALL BE GALVANIZED. 1 3" NORMAL WEIGHT CONCRETE SLAB ON 3" DEEP, 20 GAGE, GALVANIZED COMPOSITE STEEL FLOOR DECK (6" TOTAL THICKNESS). REINFORCE WITH 6x6/W2.1xW2.1 WELDED WIRE REINFORCEMENT. 2 1 1/2" DEEP, 20 GAGE, GALVANIZED WIDE RIB STEEL ROOF DECK. PROVIDE 5/8" DIAMETER PUBBLE WELDS IN 36/5 PATTERN AND 2 #10 TEK SCREWS AT SIDELAPS PER SPAN. C D 3 JOIST SUPPLIER SHALL PROVIDE 6 1/2" DEEP JOIST SEAT AT THIS END OF JOIST. 4 OPERABLE PARTITION WALL MAX WEIGHT = 15 PSF F K E G L ALL OPENINGS IN CMU WALLS (PARTITION AND LOAD BEARING) REQUIRE A LINTEL. REFER TO SHEET S9.2 FOR TYPICAL MASONRY LINTEL DETAILS AND SCHEDULES. H THIRD LEVEL FRAMING PLAN - AREA E J SCALE: 1/8" = 1'-0" BENJAMIN TALPOS 10/8/2012 6:14:54 PM C:\Users\BrionP\Documents\9-2013-Revit Projects\Joplin\13-12102-00_central_struct_2012.rvt A NORTH NORTH © 2012, DLR Group of Missouri inc., a Missouri corporation CA No. 001614, ALL RIGHTS RESERVED. KEY PLAN W14x26 7k SEE SHEET S4.1 AND S4.2 "FLOOR FRAMING TYPICAL DETAILS" FOR ADDITIONAL FRAMING REQUIREMENTS AND INFORMATION. D. JOIST SUPPLIER TO COORDINATE WITH MECHANICAL CONTRACTOR FOR RTU WEIGHTS, LOCATIONS AND PENETRATIONS. E. JOIST SUPPLIER SHALL DESIGN JOISTS FOR ALL LOADS INDICATED IN S0.1 & S0.2 'GENERAL NOTES', S0.3 'ROOF SNOW DRIFT PLAN', ON THE PLAN SHEETS, AND THE SECTION/DETAIL SHEETS. CONTRACTOR TO COORDINATE ALL WEIGHTS, LOCATIONS, AND PENETRATIONS OF EQUIPMENT WITH THE JOIST SUPPLIER PRIOR TO SUBMITTING JOIST SHOP DRAWINGS. F. REFER TO GENERAL NOTES SHEETS S0.1 AND S0.2 FOR GENERAL NOTES, ABBREVIATIONS AND SYMBOLS. G. SEE ARCHITECTURAL DRAWINGS FOR LOCATION OF SLOPED, RAISED, DEPRESSED SLABS AND DRAINS. H. REFER TO ARCHITECTURAL DRAWINGS FOR OVERALL BUILDING GEOMETRY, WALL LOCATIONS, STAIR GEOMETRY AND ADDITIONALPARTITION WALL REQUIREMENTS. J. REFER TO ARCHITECTURAL DRAWINGS FOR NON-LOAD BEARING PARTITION WALLS. REFER TO SHEETS S0.1, S0.2, S2.1, S2.2, AND S9.2 TYPICAL DETAILS FOR REINFORCING, THICKENED SLABS AND OTHER REQUIREMENTS. K. ALL OPENINGS IN CMU WALLS (PARTITION AND LOAD BEARING) REQUIRE A LINTEL. REFER TO SHEET S9.2 FOR TYPICAL MASONRY LINTEL DETAILS AND SCHEDULES. L. SEE SHEET S6.1 AND S6.2 "ROOF FRAMING TYPICAL DETAILS" FOR ADDITIONAL REQUIREMENTS AND INFORMATION. M. ALL HSS MEMBERS SHALL HAVE 1/4" CAP PLATES AT ENDS. N. PROVIDE HSS3 1/2x2 1/2x1/4 (LLH) BETWEEN ALL JOIST WITH 2 1/2" SEATS TO SUPPORT ROOF DECK WHERE DECK SWITCHES DIRECTION. (RE: 44/S6.1) P. REFER TO 52/S2.1 FOR COLUMN AND FOOTING SCHEDULES. Q. ALL EXTERIOR EXPOSED STEEL SHALL BE GALVANIZED. KEY NOTES: 15' - 4" HSS6x6x5/16 POST W12x22 14K1 14K1 14' - 6" 16' - 0" 4' - 4 1/2" 66 k-ft W18x50 11k 20k 2' - 7" KD HSS8x6x3/8 49k 52k HSS8x6x3/8 ?k ?k-ft 24' - 0" W18x40 (34) 10' - 0" 53k HSS8x6x3/8 54k 1 3" NORMAL WEIGHT CONCRETE SLAB ON 3" DEEP, 20 GAGE, GALVANIZED COMPOSITE STEEL FLOOR DECK (6" TOTAL THICKNESS). REINFORCE WITH 6x6/W2.1xW2.1 WELDED WIRE REINFORCEMENT. 2 1 1/2" DEEP, 20 GAGE, GALVANIZED WIDE RIB STEEL ROOF DECK. PROVIDE 5/8" DIAMETER PUBBLE WELDS IN 36/5 PATTERN AND 2 #10 TEK SCREWS AT SIDELAPS PER SPAN. 3 JOIST SUPPLIER SHALL PROVIDE 6 1/2" DEEP JOIST SEAT AT THIS END OF JOIST. 4 OPERABLE PARTITION WALL MAX WEIGHT = 15 PSF W12x26 ?k ?k-ft 53k 53k KF W18x40 (36) 24' - 0" HSS8x6x3/8 52k W12x26 ?k ?k-ft 20 k-ft 2k W12x26 1 2 53k 10k EC ED 10k 54k 20 k-ft 3k W14x22 (10) 10k 10k 54k MATCHLINE RE: S1.3F W18x40 (46) 24' - 0" W12x26 W12x26 55k W18x46 (34) 24' - 0" W16x26 W12x26 2k MATCHLINE RE: S1.3F 54k 2' - 7" 2 3k-ft W21x50 A 4k 3k 57k 23k 56k C K1 14K1 14K1 14K1 14K1 37' - 4" 14K1 14K1 SPAN 14K1 B 53k KL 14K1 10k 55k 2 14K1 KEY PLAN 10k W12x26 ?k ?k-ft 56k 26' - 0" 4k W12x26 W14x22 (10) 10k 10k W21x44 (50)57k 14' - 5" W12x19 W12x19 (26) 11k 55k 2k 23k-ft 12KSP 12KSP 12KSP KK EJ 32k 12KSP 12KSP 12KSP KJ 32k W21x48 23k F1 53k 8k 17k 9' - 4" 17k SPAN W16x36 (26) 17k 1 9' - 4" 17k 9' - 4" W24x62 (26) 12KSP W16x36 3k W16x36 (26) 17k 17k 49k-ft 32k 22k-ft 22k 5k 32k 16k EL W16x36 (26) 14k 20k 9' - 4" 22k 12KSP W18x35 12KSP W16x36 (26) 16k W16x36 (26) 10k 16k 8' - 10 1/4" W18x40 (26) 52k D F2 K2 F K E G L H THIRD LEVEL FRAMING PLAN - AREA F J SCALE: 1/8" = 1'-0" BENJAMIN TALPOS 10/8/2012 6:15:02 PM C:\Users\BrionP\Documents\9-2013-Revit Projects\Joplin\13-12102-00_central_struct_2012.rvt 53k MATCHLINE RE: S1.3G EH EK 54k HSS6x6x5/16 (TOS = 131'-7 1/2") RE: 24/S2.1 10k 54k 52k KH W16x26 ?k ?k-ft 2 EG S8.5 S1.3F 2k EF MECH UNIT PER MECH. MAX WT = 12,500# 35 55k 20 k-ft 3k MATCHLINE RE: S1.3E 56k KG NORTH NORTH © 2012, DLR Group of Missouri inc., a Missouri corporation CA No. 001614, ALL RIGHTS RESERVED. 20 k-ft 2k 55k EB 2 10-08-12 ADD #3 20 k-ft 2k W12x26 S5.4 W14x22 (10) 10k 10k 7290 West 133rd Street Overland Park, Kansas 66213 tel: (913)897-7811 20 k-ft 2k 55k KE Architecture Engineering Planning Interiors EA 15 52k Revisions W12x26 24' - 0" W18x35 (40) HSS8x6x3/8 ?k ?k-ft 20 k-ft 2k HSS6x6x3/8 1 1 10-04-12 ADD #2 20 k-ft 2k S5.2 47k HSS8x6x3/8 KC 56 S5.4 17k F4 27k F3 56 10' - 0" 20 k-ft 1k W12x26 20 k-ft 2k 18k CC15 HSS8x6x3/8 ?k ?k-ft 13-12102-00 09/10/12 52 k-ft 11k 4' - 4" 1' - 6" W18x50 4' - 4" W18x40 SPAN 4' - 9" W18x35 2 4' - 9" 14K1 4' - 9" 14K1 4' - 7 5/8" 14K1 4' - 9" 2k 53 k-ft 10k 4' - 9" 3k 6 k-ft 23 k-ft 5k W18x35 4' - 9" 14K1 3' - 10" 14K1 3' - 10" KB DH 10" 18k 3k 6 k-ft W18x50 11k 66 k-ft 2k 11k KA 52 k-ft W18x50 10k 53 k-ft 14K1 14K1 W21x44 ? k-ft 18k 6 k-ft 4k 3' - 10" W18x35 18k 5k 23 k-ft 1 3' - 10" FA W18x35 4k 6 k-ft 3k 7 k-ft 6k 14K1 W21x44 6k 14K1 ?k ? k-ft 18k ?k 3k 7 k-ft W18x60 (26) JOPLIN, JASPER COUNTY, MISSOURI C. 10k 33' - 1 5/8" HSS6x6x5/16 (TOS = 131'-10 1/2") JOPLIN HIGH SCHOOL TOP OF STEEL ELEVATION IS TYPICALLY 129'-6", UNLESS NOTED OTHERWISE ON PLANS AND SECTIONS. TOP OF STEEL THAT OCCURS ON A SLOPE AND IS NOT SPECIFICALLY NOTED ON THE PLANS SHALL BE LINEARLY INTERPOLATED FROM TOP OF STEEL NOTED ON THE PLANS. MATCHLINE RE: S1.3K 15' - 4" D12 DJ B. 8k 25 k-ft 9k 37' - 4" MATCHLINE RE: S1.3F MATCHLINE RE: S1.3F W14x26 (30) W12x16 (16) OPP HAND FINISHED FLOOR ELEVATION IS 130'-0", UNLESS NOTED OTHERWISE. 8k 111 k-ft MATCHLINE RE: S1.3D DF 25k A. 10k 1 180 k-ft 18k DG PLAN NOTES: 31k W18x60 THIRD LEVEL FLOOR FRAMING PLAN - AREA F 260 k-ft 50k 24k 19k DE 11k 4k 2k 23k-ft 3k 4' - 8" 4' - 8" 4' - 8" 4' - 8" 4' - 8" 199k-ft 36k-ft 4k 2 W12x26 14K1 14K1 14K1 14K1 14K1 14K1 W12x26 3k 2k 10k-ft 8k 28k-ft 7k 19k-ft W12x19 14K1 14K1 14K1 14K1 14K1 W12x22 5k 13k-ft W12x22 MATCHLINE RE: S1.3G MATCHLINE RE: S1.3G MATCHLINE RE: S1.3H MATCHLINE RE: S1.3H HA 16' - 7" 18' - 2 1/2" G1 16' - 0" E12 17' - 1 1/2" 26' - 10 1/2" 20' - 9" 23' - 4" D11 F1 G3 F2 H9 S1.3G G2 2 10-08-12 ADD #3 7k 29k-ft 14K1 14K1 W12x26 14K1 10k 46k-ft 3k W16x31 14K1 14K1 14K1 W12x26 14K1 9k 40k-ft 30' - 2 5/8" GD 21k W30x90 4k 21k 4k 14K1 14K1 14K1 14K1 14K1 14K1 14K1 14K1 14K1 14K1 W12x19 3k 20' - 4" SPAN 7290 West 133rd Street Overland Park, Kansas 66213 tel: (913)897-7811 2 Architecture Engineering Planning Interiors 2k 4k-ft 3k 25k JOPLIN, JASPER COUNTY, MISSOURI W12x26 14K1 14K1 14K1 14K1 14K1 14K1 W12x26 14K1 W21x50 25k 4k 17k 4k 3k 24k 4k 11k-ft 14K1 14K1 14K1 14K1 14K1 W12x26 14K1 14K1 14K1 14K1 14K1 14K1 14K1 14K1 14K1 14K1 4k 11k-ft W18x35 17k 36k W21x50 24k 4k 11k-ft 17k 4k 11k-ft 3k 7k-ft W12x26 20' - 0" 3k 7k-ft W30x90 36k GC W18x35 16k 36k 4k 4k 3k W30x90 36k GB SPAN 3k 10k-ft 2 JOPLIN HIGH SCHOOL 14K1 14K1 14K1 14K1 14K1 W12x26 14K1 14K1 14K1 14K1 14K1 14K1 14K1 14K1 14K1 14K1 MECH UNIT PER MECH. MAX WT = 1,500# Revisions 114k-ft 20k MECH UNIT PER MECH. MAX WT = 1,500# 14K1 4' - 7 1/2" W21x68 29k 2 W12x19 W12x19 14K1 14K1 14K1 14K1 14K1 14K1 4' - 8" 3k 19k 4k 3k 4' - 8 1/2" 2k 4k-ft W18x46 14k 36k 14K1 W12x26 4' - 5 1/8" 1 10-04-12 ADD #2 4' - 5 1/8" 13-12102-00 09/10/12 4' - 5 1/8" 37' - 4" THIRD LEVEL FLOOR FRAMING PLAN - AREA G 4' - 5 1/8" 14K1 14K1 14K1 14K1 14K1 4' - 5 1/8" 4k 4' - 6 3/8" 56k-ft 20' - 0" W12x26 12KSP 12KSP 12KSP 12KSP 4k 4k 4' - 10 1/2" W30x90 36k GA 23k 4k 4' - 8" 16KSP 4' - 8" 16KSP 4' - 8" 16KSP 16KSP 16KSP 16KSP 16KSP 4' - 8" 3k 4' - 8" SPAN 28' - 0" W12x26 16' - 0" C13 4' - 8" W12x26 ?k ?k-ft 2 E11 4' - 8" 12KSP W21x50 23k S5.4 16' - 0" 4' - 8" 12KSP 3k-ft 3k 21k 16k S5.4 4' - 8" 32k S5.4 15 4' - 8" 17k W21x48 12KSP W16x36 12KSP 12KSP 12KSP 12KSP 12KSP 16 S5.4 S5.4 13 33 20' - 0" 17k 32k 22k-ft 32k 17k 49k-ft 20k 16k 22k 5k W14x22 (12) W18x35 (24) 34k 31k 256 k-ft 32k SPAN 15 HSS4x2x3/16 16KSP E10 E9 22k HSS6x6x3/8 W18x35 W12x19 E8 W18x35 21k 37k 16KSP 29' - 8" 1 18k 21k c=1" W21x44 (38) 25' - 4" E7 45k 35k 35k 37k 16KSP 25' - 4" 34k 27k 27k 104 k-ft 31k W18x55 (26) HSS12x2x1/4 STRINGER 21k W16x26 (26) W16x67 W16x26 (26) c=1 1/4" c=1" c=1" W16x26 (26) c=1" W16x57 W16x26 (26) c=1" 179 k-ft 27k MATCHLINE RE: S1.3G E6 177 k-ft 31k W18x55 20' - 0" 29' - 8" 127 k-ft 27k MATCHLINE RE: S1.3E E5 W16x26 (26) c=1" W16x26 (26) W12x26 (30) EL 30' - 0" RE:24/S2.1, TYP 28k 182 k-ft c=3/4" MECH UNIT PER MECH. MAX WT = 500#, TYP 24k W12x26 (30) W18x40 (36) 34k 28k 26k W12x26 (34) 26k W12x26 (34) 28k 27k c=3/4" 26k W12x26 (34) W18x40 (30) 27k 28k 26k W12x26 (34) 26k 19k W12x35 W12x26 (30) 196 k-ft 33k W12x19 (26) W18x40 22k 22k 22k W12x26 (30) EK 196 k-ft 33k 2 B PLAN NOTES: 1 A. FINISHED FLOOR ELEVATION IS 130'-0", UNLESS NOTED OTHERWISE. B. TOP OF STEEL ELEVATION IS TYPICALLY 129'-6", UNLESS NOTED OTHERWISE ON PLANS AND SECTIONS. TOP OF STEEL THAT OCCURS ON A SLOPE AND IS NOT SPECIFICALLY NOTED ON THE PLANS SHALL BE LINEARLY INTERPOLATED FROM TOP OF STEEL NOTED ON THE PLANS. C. D. E. SEE SHEET S4.1 AND S4.2 "FLOOR FRAMING TYPICAL DETAILS" FOR ADDITIONAL FRAMING REQUIREMENTS AND INFORMATION. JOIST SUPPLIER TO COORDINATE WITH MECHANICAL CONTRACTOR FOR RTU WEIGHTS, LOCATIONS AND PENETRATIONS. JOIST SUPPLIER SHALL DESIGN JOISTS FOR ALL LOADS INDICATED IN S0.1 & S0.2 'GENERAL NOTES', S0.3 'ROOF SNOW DRIFT PLAN', ON THE PLAN SHEETS, AND THE SECTION/DETAIL SHEETS. CONTRACTOR TO COORDINATE ALL WEIGHTS, LOCATIONS, AND PENETRATIONS OF EQUIPMENT WITH THE JOIST SUPPLIER PRIOR TO SUBMITTING JOIST SHOP DRAWINGS. KEY NOTES: F. REFER TO GENERAL NOTES SHEETS S0.1 AND S0.2 FOR GENERAL NOTES, ABBREVIATIONS AND SYMBOLS. L. SEE SHEET S6.1 AND S6.2 "ROOF FRAMING TYPICAL DETAILS" FOR ADDITIONAL REQUIREMENTS AND INFORMATION. G. SEE ARCHITECTURAL DRAWINGS FOR LOCATION OF SLOPED, RAISED, DEPRESSED SLABS AND DRAINS. M. ALL HSS MEMBERS SHALL HAVE 1/4" CAP PLATES AT ENDS. H. J. K. REFER TO ARCHITECTURAL DRAWINGS FOR OVERALL BUILDING GEOMETRY, WALL LOCATIONS, STAIR GEOMETRY AND ADDITIONAL PARTITION WALL REQUIREMENTS. REFER TO ARCHITECTURAL DRAWINGS FOR NON-LOAD BEARING PARTITION WALLS. REFER TO SHEETS S0.1, S0.2, S2.1, S2.2, AND S9.2 TYPICAL DETAILS FOR REINFORCING, THICKENED SLABS AND OTHER REQUIREMENTS. N. PROVIDE HSS3 1/2x2 1/2x1/4 (LLH) BETWEEN ALL JOIST WITH 2 1/2" SEATS TO SUPPORT ROOF DECK WHERE DECK SWITCHES DIRECTION. (RE: 44/S6.1) P. REFER TO 52/S2.1 FOR COLUMN AND FOOTING SCHEDULES. Q. ALL EXTERIOR EXPOSED STEEL SHALL BE GALVANIZED. 1 3" NORMAL WEIGHT CONCRETE SLAB ON 3" DEEP, 20 GAGE, GALVANIZED COMPOSITE STEEL FLOOR DECK (6" TOTAL THICKNESS). REINFORCE WITH 6x6/W2.1xW2.1 WELDED WIRE REINFORCEMENT. 2 1 1/2" DEEP, 20 GAGE, GALVANIZED WIDE RIB STEEL ROOF DECK. PROVIDE 5/8" DIAMETER PUBBLE WELDS IN 36/5 PATTERN AND 2 #10 TEK SCREWS AT SIDELAPS PER SPAN. C D 3 JOIST SUPPLIER SHALL PROVIDE 6 1/2" DEEP JOIST SEAT AT THIS END OF JOIST. 4 OPERABLE PARTITION WALL MAX WEIGHT = 15 PSF F K E G L ALL OPENINGS IN CMU WALLS (PARTITION AND LOAD BEARING) REQUIRE A LINTEL. REFER TO SHEET S9.2 FOR TYPICAL MASONRY LINTEL DETAILS AND SCHEDULES. H THIRD LEVEL FRAMING PLAN - AREA G J SCALE: 1/8" = 1'-0" BENJAMIN TALPOS 10/8/2012 6:15:09 PM C:\Users\BrionP\Documents\9-2013-Revit Projects\Joplin\13-12102-00_central_struct_2012.rvt A NORTH NORTH © 2012, DLR Group of Missouri inc., a Missouri corporation CA No. 001614, ALL RIGHTS RESERVED. KEY PLAN MATCHLINE RE: S1.3G MATCHLINE RE: S1.3G MATCHLINE RE: S1.3H MATCHLINE RE: S1.3H H7 34' - 2 1/2" W24x76 2 28K7 4' - 6" 4' - 1 5/8" 5' - 0" 5' - 0" 5' - 0" 5' - 0" 5' - 0" 5' - 0" 5' - 0" 4' - 10 3/8" 4' - 6" 5' - 0" 5' - 0" 5' - 0" 5' - 0" 5' - 0" 5' - 0" 5' - 0" 5' - 0" 5' - 0" 5' - 0" 4' - 5" 4' - 5" 4' - 5" 4' - 5" 4' - 5" 4' - 5 3/8" 4' - 6" 4' - 10" 4' - 10" 4' - 10" 4' - 10" 4' - 10" 4' - 10" 4' - 10" 4' - 10" 4' - 10" 4' - 2" 4' - 2" 4' - 2" 4' - 2" 3' - 8 1/8" 5' - 2 1/4" 5' - 6" 5' - 6" 5' - 6" 5' - 6" 5' - 6" 5' - 6" 5' - 8 1/4" 5' - 3 3/4" 5' - 0 1/2" 1' - 4 3/8" W24x55 W36x135 W33x130 W21x44 W30x108 W18x35 W33x130 MECH UNIT PER MECH. MAX WT = 2,500# HF 2 SPAN W12x22 2 SPAN 2 W30x90 W18x35 1' - 1 1/4" W12x26 27' - 0 5/8" 32LH06 32LH06 32LH06 32LH06 32LH06 32LH06 32LH06 32LH06 32LH06 32LH06 32LH06 32LH06 32LH06 32LH06 32LH06 32LH06 32LH06 32LH06 32LH06 32LH06 32LH06 32LH06 32LH06 32LH06 32LH06 32LH06 32LH06 32LH06 32LH06 32LH06 32LH06 32LH06 32LH06 32LH06 32LH06 32LH06 32LH06 32LH06 32LH06 32LH06 32LH06 32LH06 32LH06 32LH06 32LH06 32LH06 32LH06 W27x129 32LHSP 32LHSP 32LHSP 32LHSP HG 32LHSP 32LHSP 32LH06 MECH EQUIP PER MECH. MAX WT = 1,500# W12x16 HH 1' - 3 3/4" HK 105' - 4" 28' - 10" H1 H2 46' - 8" 20' - 10" H3 H4 HJ 2 10-08-12 ADD #3 4' - 10" 7290 West 133rd Street Overland Park, Kansas 66213 tel: (913)897-7811 4' - 10" Architecture Engineering Planning Interiors 4' - 10" Revisions 4' - 10" 20' - 0" 4' - 10" W12x22 4' - 4" 20' - 0" MECH UNIT PER MECH. MAX WT = 2,500# 1 10-04-12 ADD #2 28K7 28K7 28K7 28K7 28K7 28K7 28K7 28K7 28K7 28K7 28K7 28K7 28K7 28K7 28K7 28K7 28K7 28K7 28K7 28K7 30KSP HE 13-12102-00 09/10/12 MECH UNIT PER MECH. MAX WT = 13,000# 30KSP 30KSP 30KSP 28K7 28K7 28K7 28K7 28K7 28K7 28K7 28K7 28K7 28K7 28K7 28K7 28K7 28K7 28K7 28K7 28K7 28K7 28K7 28K7 28K7 28K7 28KSP W27x114 28KSP 28KSP 28KSP 28KSP 28K7 28KSP 2 JOPLIN, JASPER COUNTY, MISSOURI W12x22 20' - 1 5/8" MECH EQUIP PER MECH. MAX WT = 1,500# JOPLIN HIGH SCHOOL 2 THIRD LEVEL FLOOR FRAMING PLAN - AREA H HD S1.3H W24x76 A MATCHLINE RE: S1.3J 44' - 4 1/4" H5 PLAN NOTES: 1 A. FINISHED FLOOR ELEVATION IS 130'-0", UNLESS NOTED OTHERWISE. B. TOP OF STEEL ELEVATION IS TYPICALLY 129'-6", UNLESS NOTED OTHERWISE ON PLANS AND SECTIONS. TOP OF STEEL THAT OCCURS ON A SLOPE AND IS NOT SPECIFICALLY NOTED ON THE PLANS SHALL BE LINEARLY INTERPOLATED FROM TOP OF STEEL NOTED ON THE PLANS. C. D. E. SEE SHEET S4.1 AND S4.2 "FLOOR FRAMING TYPICAL DETAILS" FOR ADDITIONAL FRAMING REQUIREMENTS AND INFORMATION. JOIST SUPPLIER TO COORDINATE WITH MECHANICAL CONTRACTOR FOR RTU WEIGHTS, LOCATIONS AND PENETRATIONS. JOIST SUPPLIER SHALL DESIGN JOISTS FOR ALL LOADS INDICATED IN S0.1 & S0.2 'GENERAL NOTES', S0.3 'ROOF SNOW DRIFT PLAN', ON THE PLAN SHEETS, AND THE SECTION/DETAIL SHEETS. CONTRACTOR TO COORDINATE ALL WEIGHTS, LOCATIONS, AND PENETRATIONS OF EQUIPMENT WITH THE JOIST SUPPLIER PRIOR TO SUBMITTING JOIST SHOP DRAWINGS. KEY NOTES: F. REFER TO GENERAL NOTES SHEETS S0.1 AND S0.2 FOR GENERAL NOTES, ABBREVIATIONS AND SYMBOLS. L. SEE SHEET S6.1 AND S6.2 "ROOF FRAMING TYPICAL DETAILS" FOR ADDITIONAL REQUIREMENTS AND INFORMATION. G. SEE ARCHITECTURAL DRAWINGS FOR LOCATION OF SLOPED, RAISED, DEPRESSED SLABS AND DRAINS. M. ALL HSS MEMBERS SHALL HAVE 1/4" CAP PLATES AT ENDS. H. J. K. REFER TO ARCHITECTURAL DRAWINGS FOR OVERALL BUILDING GEOMETRY, WALL LOCATIONS, STAIR GEOMETRY AND ADDITIONAL PARTITION WALL REQUIREMENTS. REFER TO ARCHITECTURAL DRAWINGS FOR NON-LOAD BEARING PARTITION WALLS. REFER TO SHEETS S0.1, S0.2, S2.1, S2.2, AND S9.2 TYPICAL DETAILS FOR REINFORCING, THICKENED SLABS AND OTHER REQUIREMENTS. N. PROVIDE HSS3 1/2x2 1/2x1/4 (LLH) BETWEEN ALL JOIST WITH 2 1/2" SEATS TO SUPPORT ROOF DECK WHERE DECK SWITCHES DIRECTION. (RE: 44/S6.1) P. REFER TO 52/S2.1 FOR COLUMN AND FOOTING SCHEDULES. Q. ALL EXTERIOR EXPOSED STEEL SHALL BE GALVANIZED. 1 3" NORMAL WEIGHT CONCRETE SLAB ON 3" DEEP, 20 GAGE, GALVANIZED COMPOSITE STEEL FLOOR DECK (6" TOTAL THICKNESS). REINFORCE WITH 6x6/W2.1xW2.1 WELDED WIRE REINFORCEMENT. 2 1 1/2" DEEP, 20 GAGE, GALVANIZED WIDE RIB STEEL ROOF DECK. PROVIDE 5/8" DIAMETER PUBBLE WELDS IN 36/5 PATTERN AND 2 #10 TEK SCREWS AT SIDELAPS PER SPAN. 3 JOIST SUPPLIER SHALL PROVIDE 6 1/2" DEEP JOIST SEAT AT THIS END OF JOIST. 4 OPERABLE PARTITION WALL MAX WEIGHT = 15 PSF ALL OPENINGS IN CMU WALLS (PARTITION AND LOAD BEARING) REQUIRE A LINTEL. REFER TO SHEET S9.2 FOR TYPICAL MASONRY LINTEL DETAILS AND SCHEDULES. 10' - 4 1/4" H8 H9 B C D F K E G L H ROOF LEVEL FRAMING PLAN - AREA H J SCALE: 1/8" = 1'-0" BENJAMIN TALPOS 10/8/2012 6:15:17 PM C:\Users\BrionP\Documents\9-2013-Revit Projects\Joplin\13-12102-00_central_struct_2012.rvt MATCHLINE RE: S1.3H NORTH NORTH © 2012, DLR Group of Missouri inc., a Missouri corporation CA No. 001614, ALL RIGHTS RESERVED. KEY PLAN PLAN NOTES: 1 MATCHLINE RE: S1.3H MATCHLINE RE: S1.3J H9 A. FINISHED FLOOR ELEVATION IS 130'-0", UNLESS NOTED OTHERWISE. B. TOP OF STEEL ELEVATION IS TYPICALLY 129'-6", UNLESS NOTED OTHERWISE ON PLANS AND SECTIONS. TOP OF STEEL THAT OCCURS ON A SLOPE AND IS NOT SPECIFICALLY NOTED ON THE PLANS SHALL BE LINEARLY INTERPOLATED FROM TOP OF STEEL NOTED ON THE PLANS. C. SEE SHEET S4.1 AND S4.2 "FLOOR FRAMING TYPICAL DETAILS" FOR ADDITIONAL FRAMING REQUIREMENTS AND INFORMATION. D. JOIST SUPPLIER TO COORDINATE WITH MECHANICAL CONTRACTOR FOR RTU WEIGHTS, LOCATIONS AND PENETRATIONS. E. JOIST SUPPLIER SHALL DESIGN JOISTS FOR ALL LOADS INDICATED IN S0.1 & S0.2 'GENERAL NOTES', S0.3 'ROOF SNOW DRIFT PLAN', ON THE PLAN SHEETS, AND THE SECTION/DETAIL SHEETS. CONTRACTOR TO COORDINATE ALL WEIGHTS, LOCATIONS, AND PENETRATIONS OF EQUIPMENT WITH THE JOIST SUPPLIER PRIOR TO SUBMITTING JOIST SHOP DRAWINGS. F. REFER TO GENERAL NOTES SHEETS S0.1 AND S0.2 FOR GENERAL NOTES, ABBREVIATIONS AND SYMBOLS. G. SEE ARCHITECTURAL DRAWINGS FOR LOCATION OF SLOPED, RAISED, DEPRESSED SLABS AND DRAINS. H. REFER TO ARCHITECTURAL DRAWINGS FOR OVERALL BUILDING GEOMETRY, WALL LOCATIONS, STAIR GEOMETRY AND ADDITIONALPARTITION WALL REQUIREMENTS. J. REFER TO ARCHITECTURAL DRAWINGS FOR NON-LOAD BEARING PARTITION WALLS. REFER TO SHEETS S0.1, S0.2, S2.1, S2.2, AND S9.2 TYPICAL DETAILS FOR REINFORCING, THICKENED SLABS AND OTHER REQUIREMENTS. K. ALL OPENINGS IN CMU WALLS (PARTITION AND LOAD BEARING) REQUIRE A LINTEL. REFER TO SHEET S9.2 FOR TYPICAL MASONRY LINTEL DETAILS AND SCHEDULES. L. SEE SHEET S6.1 AND S6.2 "ROOF FRAMING TYPICAL DETAILS" FOR ADDITIONAL REQUIREMENTS AND INFORMATION. M. ALL HSS MEMBERS SHALL HAVE 1/4" CAP PLATES AT ENDS. N. PROVIDE HSS3 1/2x2 1/2x1/4 (LLH) BETWEEN ALL JOIST WITH 2 1/2" SEATS TO SUPPORT ROOF DECK WHERE DECK SWITCHES DIRECTION. (RE: 44/S6.1) P. REFER TO 52/S2.1 FOR COLUMN AND FOOTING SCHEDULES. Q. ALL EXTERIOR EXPOSED STEEL SHALL BE GALVANIZED. 1 1/2" DEEP, 20 GAGE, GALVANIZED WIDE RIB STEEL ROOF DECK. PROVIDE 5/8" DIAMETER PUBBLE WELDS IN 36/5 PATTERN AND 2 #10 TEK SCREWS AT SIDELAPS PER SPAN. 3 JOIST SUPPLIER SHALL PROVIDE 6 1/2" DEEP JOIST SEAT AT THIS END OF JOIST. 4 OPERABLE PARTITION WALL MAX WEIGHT = 15 PSF 4' - 8" 4' - 6" 4' - 6" 4' - 6" 4' - 4 3/8" 32LH06 32LH06 32LH06 4' - 6" 32LH06 4' - 5 3/4" 32LH06 4' - 8" 32LH06 4' - 8" MECH UNIT PER MECH. MAX WT = 13,000# 2 2 2 SPAN W27x84 JD W33x118 W36x135 W16x36 2 MECH EQUIP PER MECH. MAX WT = 1,500# 26K7 26K7 26K7 26K7 26K7 26K7 26K7 26K7 26K7 26K7 26K7 26K7 26K7 26K7 26K7 26K7 26K7 26K7 26K7 26K7 26K7 28KSP 26KSP 26KSP 26KSP 26KSP 28KSP 28KSP 26KSP 26KSP 26KSP 28KSP 26K7 2 26K7 2 26K7 MECH UNIT PER MECH. MAX WT = 2,500# JOPLIN, JASPER COUNTY, MISSOURI 2 JOPLIN HIGH SCHOOL MECH UNIT PER MECH. MAX WT = 2,500# 3" NORMAL WEIGHT CONCRETE SLAB ON 3" DEEP, 20 GAGE, GALVANIZED COMPOSITE STEEL FLOOR DECK (6" TOTAL THICKNESS). REINFORCE WITH 6x6/W2.1xW2.1 WELDED WIRE REINFORCEMENT. 32LHSP 4' - 8 1/2" 4' - 8" 32LH06 4' - 8 1/2" 4' - 8" 32LH06 4' - 8 1/2" 4' - 8" 32LH06 4' - 8 1/2" 4' - 8" 32LH06 4' - 8 1/2" 4' - 8" 32LH06 4' - 8 1/2" 4' - 8" 32LH06 4' - 8 1/2" 4' - 8" 32LH06 4' - 8 1/2" 4' - 8" 32LH06 4' - 8 1/2" 32LH06 32LH06 32LH06 32LH06 32LHSP 4' - 7 5/8" 4' - 8 1/2" 32LH06 32LHSP 4' - 7" 32LH06 4' - 7" 32LHSP 32LHSP 4' - 7" 32LH06 4' - 7" 32LH06 4' - 7" 32LHSP 32LHSP 32LHSP 4' - 7" 32LH06 4' - 7" 32LH06 4' - 7" 2 32LH06 4' - 5 5/8" 32LHSP 32LHSP 2 1 THIRD LEVEL FLOOR FRAMING PLAN - AREA J KEY NOTES: 2 10-08-12 ADD #3 Architecture Engineering Planning Interiors 7290 West 133rd Street Overland Park, Kansas 66213 tel: (913)897-7811 M2 Revisions M4 1 10-04-12 ADD #2 M3 MA 13-12102-00 09/10/12 M1 2 S1.3J MECH UNIT PER MECH. MAX WT = 2,500# 108' - 6" J1 A B C D F K E MC G J3 L H ROOF LEVEL FRAMING PLAN - AREA J J SCALE: 1/8" = 1'-0" BENJAMIN TALPOS 10/8/2012 6:15:24 PM C:\Users\BrionP\Documents\9-2013-Revit Projects\Joplin\13-12102-00_central_struct_2012.rvt MB NORTH NORTH © 2012, DLR Group of Missouri inc., a Missouri corporation CA No. 001614, ALL RIGHTS RESERVED. KEY PLAN 1 24' - 0" 24' - 0" 24' - 0" 26' - 4" PLAN NOTES: W16x26 1k HSS8x6x5/16 W16x26 1k 1k W16x26 1k W16x26 1k 1k HSS8x6x5/16 W16x26 1k 1 1k 2k 4k-ft W16x45 2k 4k-ft W16x26 1k HSS8x6x5/16 HSS6x6x5/16 (TOS = 129'-1 1/2") 5' - 3 3/8" 3k 35 15k CC15 W14x22 (26) HSS8 x6x5/1 6 W16x26 (10) 10k 10k W18x35 (26) 53k 15° 1k RKB S8.6 RK7 8' - 0" 55k 8' - 0" ALL HSS MEMBERS SHALL HAVE 1/4" CAP PLATES AT ENDS. N. PROVIDE HSS3 1/2x2 1/2x1/4 (LLH) BETWEEN ALL JOIST WITH 2 1/2" SEATS TO SUPPORT ROOF DECK WHERE DECK SWITCHES DIRECTION. (RE: 44/S6.1) P. REFER TO 52/S2.1 FOR COLUMN AND FOOTING SCHEDULES. Q. ALL EXTERIOR EXPOSED STEEL SHALL BE GALVANIZED. 1 3" NORMAL WEIGHT CONCRETE SLAB ON 3" DEEP, 20 GAGE, GALVANIZED COMPOSITE STEEL FLOOR DECK (6" TOTAL THICKNESS). REINFORCE WITH 6x6/W2.1xW2.1 WELDED WIRE REINFORCEMENT. 2 1 1/2" DEEP, 20 GAGE, GALVANIZED WIDE RIB STEEL ROOF DECK. PROVIDE 5/8" DIAMETER PUBBLE WELDS IN 36/5 PATTERN AND 2 #10 TEK SCREWS AT SIDELAPS PER SPAN. 3 JOIST SUPPLIER SHALL PROVIDE 6 1/2" DEEP JOIST SEAT AT THIS END OF JOIST. 4 OPERABLE PARTITION WALL MAX WEIGHT = 15 PSF 57k 1k 57k 1k 56k c=1 1/4" 55k S8.4 33 W16x26 1 HSS8x6x5/16 56k W21x44 (48) 8' - 8" 8' - 8" SPAN W21x44 (42) S1.3K c=1 1/4" 3' - 9 7/8" W21x44 (54) c=1 1/4" 15° 1k 55k HSS8 x6x5/1 6 8' - 0" 1k 56k c=1 1/4" 8' - 0" W21x44 (54) W21x44 (42) RKE 55k W18x60 (36) W14x22 (10) 10k 10k MECH UNIT PER MECH. MAX WT = 7,500# 56k W16x26 (10) 10k 10k M. RK9 15° 1k (H HSS6 IGH) 1k x6x5/1 6 HSS6 x6x5/1 1k (LO 6 W) 1k 53k W16x26 (10) 10k10k 10k 10k W16x26 (10) 8' - 0" c=1 1/4" c=1 1/4" 2 55k SEE SHEET S6.1 AND S6.2 "ROOF FRAMING TYPICAL DETAILS" FOR ADDITIONAL REQUIREMENTS AND INFORMATION. S8.6 54k 55k 54k W18x46 (34) W21x44 (50)57k 33 HSS8 x6x5/1 6 52k W18x40 (46) W16x26 (10) 10k 10k c=1 1/4" W14x22 (10) 10k 10k MECH UNIT PER MECH. MAX WT = 17,000# 53k 26' - 0" W14x22 (10) 10k 10k L. 55k 2 54k 24' - 0" W21x44 (54) 55k 2 ALL OPENINGS IN CMU WALLS (PARTITION AND LOAD BEARING) REQUIRE A LINTEL. REFER TO SHEET S9.2 FOR TYPICAL MASONRY LINTEL DETAILS AND SCHEDULES. RKD 1k 55k c=1 1/4" W21x44 (52) 53k KK K. 2 52k KH REFER TO ARCHITECTURAL DRAWINGS FOR NON-LOAD BEARING PARTITION WALLS. REFER TO SHEETS S0.1, S0.2, S2.1, S2.2, AND S9.2 TYPICAL DETAILS FOR REINFORCING, THICKENED SLABS AND OTHER REQUIREMENTS. RK8 15° 1k (H IGH HSS6 ) 1k x6x5/1 6 HSS6 x 1k (LO 6x5/16 W) 1k 55k 10k 10k W16x26 (10) 8' - 0" W21x44 (52) J. 1k 56k c=1 1/4" MECH UNIT PER MECH. MAX WT = 6,000# 2 54k REFER TO ARCHITECTURAL DRAWINGS FOR OVERALL BUILDING GEOMETRY, WALL LOCATIONS, STAIR GEOMETRY AND ADDITIONALPARTITION WALL REQUIREMENTS. 15° c=1 1/4" MECH UNIT PER MECH. MAX WT = 17,000# 8' - 0" S8.5 H. RKC 1k W21x44 (54) HSS8 x6x5/1 6 54k W18x40 (52) c=1 1/4" W21x44 (52) SEE ARCHITECTURAL DRAWINGS FOR LOCATION OF SLOPED, RAISED, DEPRESSED SLABS AND DRAINS. 15° 55k SPAN 1 8' - 0" 56k W18x40 (46) 24' - 0" W21x44 (52) W21x44 (54) 55k 35 1k (H IG HSS6 H) 1k x6x5/1 6 HSS6 x 1k (LO 6x5/16 W) 1k 52k 8' - 0" 54k KG c=1 1/4" 8' - 0" W16x26 (10) 10k 10k 54k W14x22 (10) 10k 10k G. 1k 54k 55k 53k 24' - 0" W18x40 (36) 2 53k REFER TO GENERAL NOTES SHEETS S0.1 AND S0.2 FOR GENERAL NOTES, ABBREVIATIONS AND SYMBOLS. KEY PLAN W14x22 (6) 10k 10k c=3/4" 33k 30k W16x26 (26) 30k 31k W16x26 (26) 33k 34k 1k 33k 32k W14x22 (26) 2 MECH UNIT PER MECH. MAX WT = 6,000# 31k 17k W12x26 (26) 17k 14k W12x22 (26) 15k 76k W24x55 (26) 31k 19k W12x26 (26) 51 53 S8.4 S8.4 18k W14x22 (12) 18k W12x26 (12) 4' - 3" 10K1 20k 31k 31k 18k 61k W12x16 (26) 63k 19k 59k 26k 60k c=1" 77k 100k W16x26 (26) 26k 20k 10K1 10K1 W14x48 B W14x22 W16x26 (10) 10k 10k 20k SPAN W14x22 (26) 4' - 4" MECH UNIT PER MECH. MAX WT = 12,500# W14x22 (12) 30k 30k 2 30k 20k 32k 4' - 3" 32k 10K1 2 W14x22 (26) 32k 63k W16x26 (10) 10k 10k 10k 10k W16x26 (10) W14x22 (26) A W14x48 2k W14x22 MECH UNIT PER MECH. MAX WT = 500#, TYP, UNO 30k SPAN W16x26 (10) 10k 10k 10k 10k W16x26 (10) 2 30k W16x26 (26) W14x48 4' - 3" W16x26 (26) 30k W12x26 (12) 4' - 3" 34k 29k 18k W16x26 (26) 47k W16x26 (26) 16k W12x16 (26) W16x26 (26) c=1" MECH UNIT PER MECH. MAX WT = 12,500# 29k 16k W12x16 (26) W21x44 (26) W18x40 (46) 48k 2 29k 17k 1 2 2 MECH UNIT PER MECH. MAX WT = 6,000# W16x26 (26) SPAN MECH UNIT PER MECH. MAX WT = 6,000# c=1" 15k W12x16 (26) 1 W18x40 (46) 30k W21x44 (26) 46k 15k 62k 15k W21x44 (26) W12x16 (16) 62k 16k 80k 13k W21x50 (26) 103k 46k W24x55 (58) 7' - 11 3/4" W16x26 (10) 10k 10k W21x44 (52) 57k W14x43 (26) 17k W12x16 (26) W14x22 (10) 10k 10k 16k C MATCHLINE RE: S1.3K MATCHLINE RE: S1.3L D F W14x48 2k K E 1k 30k 20k c=1 1/4" 4k W14x43 (26) 1k 1k LA W21x44 (52) 20k W16x26 (20) 52k 8' - 8 1/2" 10k 10k W16x26 (10) MATCHLINE RE: S1.3L 54k 8' - 8 1/2" MATCHLINE RE: S1.3K c=1 1/4" W16x26 (10) 10k 10k 56k KM W21x44 (42) 10k 10k W16x26 (10) 24' - 8" W14x22 (10) 10k 10k W16x26 (10) 10k 10k 52k W18x40 (42) 10k 10k W16x26 (10) K1 2 16k 53k 7' - 11 3/4" W14x22 (10) 10k 10k G L K2 K3 K4 L1 K5 K6 K7 L2 K8 K9 K11 K12 H J THIRD LEVEL EQUIPMENT PLATFORM FRAMING PLAN - AREA K SCALE: 1/8" = 1'-0" BENJAMIN TALPOS 10/8/2012 6:15:32 PM C:\Users\BrionP\Documents\9-2013-Revit Projects\Joplin\13-12102-00_central_struct_2012.rvt 56k c=1 1/4" 65k 57k 57k W21x44 (42) 53k KL 2 W14x22 (10) 10k 10k W14x22 (10) 10k 10k 2 W21x44 (26) 8' - 8" 1 NORTH NORTH © 2012, DLR Group of Missouri inc., a Missouri corporation CA No. 001614, ALL RIGHTS RESERVED. 52k 31 HSS8 x6x5/1 6 c=1 1/4" W21x44 (52) 52k F. KEY NOTES: 53k 15° KF JOIST SUPPLIER SHALL DESIGN JOISTS FOR ALL LOADS INDICATED IN S0.1 & S0.2 'GENERAL NOTES', S0.3 'ROOF SNOW DRIFT PLAN', ON THE PLAN SHEETS, AND THE SECTION/DETAIL SHEETS. CONTRACTOR TO COORDINATE ALL WEIGHTS, LOCATIONS, AND PENETRATIONS OF EQUIPMENT WITH THE JOIST SUPPLIER PRIOR TO SUBMITTING JOIST SHOP DRAWINGS. 2 c=1 1/4" W21x44 (52) 53k E. 1k 37k 54k MECH UNIT PER MECH. MAX WT = 6,000# W21x44 (42) 54k RK6 15° 1k (H IGH HSS6 ) 1k x6x5/1 6 HSS6 x 1k (LO 6x5/16 W) 1k 54k c=1 1/4" W18x46 (46) W21x44 (42) MECH UNIT PER MECH. MAX WT = 6,000# JOIST SUPPLIER TO COORDINATE WITH MECHANICAL CONTRACTOR FOR RTU WEIGHTS, LOCATIONS AND PENETRATIONS. 2 10-08-12 ADD #3 10k 10k W16x26 (10) 8' - 0" W14x22 (10) 10k 10k 8' - 0" W18x40 (34) 24' - 0" c=1 1/4" 2 53k RKA 8' - 0" W16x26 (10) 10k 10k W14x22 (10) 10k 10k 8' - 0" 55k KE W21x44 (42) 10k 10k W16x26 (10) W18x35 (40) RE:24/S2.1, TYP 49k 24' - 0" 2 52k D. 2 W16x26 (26) 52k 1k (H IG HSS6 H) 1k x6x5/1 6 HSS6 x6 1k (LO x5/16 W) 1k 1k 8' - 0" 47k 54k KC SEE SHEET S4.1 AND S4.2 "FLOOR FRAMING TYPICAL DETAILS" FOR ADDITIONAL FRAMING REQUIREMENTS AND INFORMATION. 15° 1k 27k 1 C. RK5 15° W18x35 10' - 0" 10' - 0" F4 56 S5.2 TOP OF STEEL ELEVATION IS TYPICALLY 129'-6", UNLESS NOTED OTHERWISE ON PLANS AND SECTIONS. TOP OF STEEL THAT OCCURS ON A SLOPE AND IS NOT SPECIFICALLY NOTED ON THE PLANS SHALL BE LINEARLY INTERPOLATED FROM TOP OF STEEL NOTED ON THE PLANS. W16x26 (26) W21x44 14K1 14K1 14K1 14K1 14K1 14K1 14K1 1' - 6" S8.4 W24x76 20k B. 1k SPAN KB FINISHED FLOOR ELEVATION IS 130'-0", UNLESS NOTED OTHERWISE. HSS8x6x5/16 HSS8x6x5/16 2 A. 7290 West 133rd Street Overland Park, Kansas 66213 tel: (913)897-7811 5' - 3" 1k HSS8x6x5/16 1 HSS8x6x5/16 Architecture Engineering Planning Interiors 5' - 3" 2k 4k-ft HSS8x6x5/16 HSS8x6x5/16 Revisions 5' - 3" HSS8x6x5/16 HSS8x6x5/16 1 10-04-12 ADD #2 5' - 3" 14' - 6" 5' - 3" W16x45 2k 4k-ft HSS8x6x5/16 13-12102-00 09/10/12 5' - 3" W18x40 HSS8x6x5/16 HSS8x6x5/16 JOPLIN, JASPER COUNTY, MISSOURI HSS8x6x5/16 HSS8x6x5/16 W18x40 10" 18k 2k 66 k-ft W18x50 11k 24' - 0" 1k HSS6x6x5/16 POST 4' - 4 1/2" W12x22 4' - 4" 24' - 0" HSS8x6x5/16 2k 16' - 0" 3k 6 k-ft 14K1 52 k-ft 11k FA 4' - 4" W18x35 4' - 9" 23' - 6" HSS6x6x5/16 (TOS = 131'-10 1/2") 1k W18x50 11k 66 k-ft 14K1 3k 6 k-ft 11k KA 52 k-ft 14K1 DG 12' - 10" MATCHLINE RE: S1.3K MATCHLINE RE: S1.3F 42' - 0 3/8" THIRD LEVEL EQUIPMENT PLATFORM FRAMING PLAN AREA K HIGH SCHOOL JOPLIN 15' - 4" W14x22 (6) 10k 10k 30k 31k W16x26 (26) 33k W14x22 (26) 34k 33k 32k W14x22 (26) W14x22 (12) c=3/4" 17k W12x26 (26) 17k 14k W12x22 (26) 15k 76k W24x55 (26) 31k 19k W12x26 (26) 51 53 S8.4 S8.4 18k 18k W14x22 W14x22 20k MATCHLINE RE: S1.3K 10K1 W14x48 31k 31k 18k 61k W12x16 (26) 19k 63k 26k 59k c=1" 60k W16x26 (26) 26k 77k 32k 100k 20k 10K1 4' - 3" W16x26 (26) MECH UNIT PER MECH. MAX WT = 6,000# 31k 20k W16x26 (26) 30k MECH UNIT PER MECH. MAX WT = 12,500# 20k 2 W16x26 (26) 33k 30k 2 W21x44 (26) W16x26 (26) 34k 2 W21x44 (26) 47k W21x44 (26) c=1" MECH UNIT PER MECH. MAX WT = 12,500# W21x44 (26) W18x40 (46) 48k W21x50 (26) W24x55 (58) W16x26 (10) 10k 10k 10k 10k W16x26 (10) W21x44 (52) 2 MECH UNIT PER MECH. MAX WT = 6,000# MECH UNIT PER MECH. MAX WT = 500#, TYP, UNO MATCHLINE RE: S1.3L W14x48 W12x26 (12) 2k 1k 30k 20k W16x26 (20) 57k 2 1k 1k LA 20k c=1 1/4" 8' - 8 1/2" 10k 10k W16x26 (10) MATCHLINE RE: S1.3L 54k 8' - 8 1/2" MATCHLINE RE: S1.3K W21x44 (52) W16x26 (10) 10k 10k 56k KM W16x26 (10) 10k 10k W18x40 (42) 10k 10k W16x26 (10) W14x22 (10) 10k 10k MECH UNIT PER MECH. MAX WT = 6,000# 2 1k 1k W12x22 1k 1k 1k W12x22 W12x22 30' - 0" 2 W12x22 1k 1k W12x22 1k W12x22 1k 1k 2k W24x68 2k 1k W12x22 1k W12x22 1k 1k 2k W24x68 2k 1k W12x22 1k HSS6x6x5/16 (TOS = 129'-1 1/2") HSS6x6x5/16 (TOS = 129'-1 1/2") 4' - 2" 42' - 0 3/8" K3 23' - 6" 24' - 0" K4 K5 24' - 0" 19' - 10" K6 K7 28' - 2" L2 24' - 0" K8 K9 26' - 4" K11 K12 S1.3L K2 12' - 10" 2 10-08-12 ADD #3 1k LF 7290 West 133rd Street Overland Park, Kansas 66213 tel: (913)897-7811 43 Architecture Engineering Planning Interiors 55 1k S8.3 1k S8.3 Revisions W12x22 1k S8.3 W16x36 41 W12x22 26' - 8" 1k 1k 1k 1 10-04-12 ADD #2 1k 1k W12x22 W12x19 13-12102-00 09/10/12 1k LD 1k W12x22 1k 24' - 0" 1k LC JOPLIN, JASPER COUNTY, MISSOURI 1k THIRD LEVEL EQUIPMENT PLATFORM FRAMING PLAN AREA L HIGH SCHOOL JOPLIN 1k W16x36 31 1k W12x22 1k S8.4 1k 35 W12x22 24' - 0" S8.6 W16x36 1k LB B PLAN NOTES: 1 A. FINISHED FLOOR ELEVATION IS 130'-0", UNLESS NOTED OTHERWISE. B. TOP OF STEEL ELEVATION IS TYPICALLY 129'-6", UNLESS NOTED OTHERWISE ON PLANS AND SECTIONS. TOP OF STEEL THAT OCCURS ON A SLOPE AND IS NOT SPECIFICALLY NOTED ON THE PLANS SHALL BE LINEARLY INTERPOLATED FROM TOP OF STEEL NOTED ON THE PLANS. C. D. E. SEE SHEET S4.1 AND S4.2 "FLOOR FRAMING TYPICAL DETAILS" FOR ADDITIONAL FRAMING REQUIREMENTS AND INFORMATION. JOIST SUPPLIER TO COORDINATE WITH MECHANICAL CONTRACTOR FOR RTU WEIGHTS, LOCATIONS AND PENETRATIONS. JOIST SUPPLIER SHALL DESIGN JOISTS FOR ALL LOADS INDICATED IN S0.1 & S0.2 'GENERAL NOTES', S0.3 'ROOF SNOW DRIFT PLAN', ON THE PLAN SHEETS, AND THE SECTION/DETAIL SHEETS. CONTRACTOR TO COORDINATE ALL WEIGHTS, LOCATIONS, AND PENETRATIONS OF EQUIPMENT WITH THE JOIST SUPPLIER PRIOR TO SUBMITTING JOIST SHOP DRAWINGS. KEY NOTES: F. REFER TO GENERAL NOTES SHEETS S0.1 AND S0.2 FOR GENERAL NOTES, ABBREVIATIONS AND SYMBOLS. L. SEE SHEET S6.1 AND S6.2 "ROOF FRAMING TYPICAL DETAILS" FOR ADDITIONAL REQUIREMENTS AND INFORMATION. G. SEE ARCHITECTURAL DRAWINGS FOR LOCATION OF SLOPED, RAISED, DEPRESSED SLABS AND DRAINS. M. ALL HSS MEMBERS SHALL HAVE 1/4" CAP PLATES AT ENDS. H. J. K. REFER TO ARCHITECTURAL DRAWINGS FOR OVERALL BUILDING GEOMETRY, WALL LOCATIONS, STAIR GEOMETRY AND ADDITIONAL PARTITION WALL REQUIREMENTS. REFER TO ARCHITECTURAL DRAWINGS FOR NON-LOAD BEARING PARTITION WALLS. REFER TO SHEETS S0.1, S0.2, S2.1, S2.2, AND S9.2 TYPICAL DETAILS FOR REINFORCING, THICKENED SLABS AND OTHER REQUIREMENTS. N. PROVIDE HSS3 1/2x2 1/2x1/4 (LLH) BETWEEN ALL JOIST WITH 2 1/2" SEATS TO SUPPORT ROOF DECK WHERE DECK SWITCHES DIRECTION. (RE: 44/S6.1) P. REFER TO 52/S2.1 FOR COLUMN AND FOOTING SCHEDULES. Q. ALL EXTERIOR EXPOSED STEEL SHALL BE GALVANIZED. 1 3" NORMAL WEIGHT CONCRETE SLAB ON 3" DEEP, 20 GAGE, GALVANIZED COMPOSITE STEEL FLOOR DECK (6" TOTAL THICKNESS). REINFORCE WITH 6x6/W2.1xW2.1 WELDED WIRE REINFORCEMENT. 2 1 1/2" DEEP, 20 GAGE, GALVANIZED WIDE RIB STEEL ROOF DECK. PROVIDE 5/8" DIAMETER PUBBLE WELDS IN 36/5 PATTERN AND 2 #10 TEK SCREWS AT SIDELAPS PER SPAN. C D 3 JOIST SUPPLIER SHALL PROVIDE 6 1/2" DEEP JOIST SEAT AT THIS END OF JOIST. 4 OPERABLE PARTITION WALL MAX WEIGHT = 15 PSF F K E G L ALL OPENINGS IN CMU WALLS (PARTITION AND LOAD BEARING) REQUIRE A LINTEL. REFER TO SHEET S9.2 FOR TYPICAL MASONRY LINTEL DETAILS AND SCHEDULES. H THIRD LEVEL EQUIPMENT PLATFORM FRAMING PLAN - AREA L J SCALE: 1/8" = 1'-0" BENJAMIN TALPOS 10/8/2012 6:15:39 PM C:\Users\BrionP\Documents\9-2013-Revit Projects\Joplin\13-12102-00_central_struct_2012.rvt A NORTH NORTH © 2012, DLR Group of Missouri inc., a Missouri corporation CA No. 001614, ALL RIGHTS RESERVED. KEY PLAN 23 S7.1 W8x18 W8x18 W8x18 W24x104 (LOFT BLOCK BEAM) 2 20' - 5 1/2" CATWALK HANGER BEAM SERVICE LOAD REACTIONS, TYP DEAD LOAD = 3K LIVE LOAD =3 K W8x18 W24x104 (DOUBLE PITCH TOP CHORD 1/4" PER FT) TRUSS TOP CHORD (SEE 21/S8.2) 4' - 0" 60DLH14 (DOUBLE PITCH TOP CHORD 1/4" PER FT) 60DLH14 (DOUBLE PITCH TOP CHORD 1/4" PER FT) 60DLH14 (DOUBLE PITCH TOP CHORD 1/4" PER FT) 60DLH14 (DOUBLE PITCH TOP CHORD 1/4" PER FT) 60DLH14 (DOUBLE PITCH TOP CHORD 1/4" PER FT) 60DLH14 (DOUBLE PITCH TOP CHORD 1/4" PER FT) 60DLH14 (DOUBLE PITCH TOP CHORD 1/4" PER FT) 60DLH14 (DOUBLE PITCH TOP CHORD 1/4" PER FT) 60DLH14 (DOUBLE PITCH TOP CHORD 1/4" PER FT) 68DLHSP (DOUBLE PITCH TOP CHORD 1/4" PER FT) 68DLHSP (DOUBLE PITCH TOP CHORD 1/4" PER FT) SLOPE 1/4" PER FT. 68DLHSP (DOUBLE PITCH TOP CHORD 1/4" PER FT) 60DLH14 (DOUBLE PITCH TOP CHORD 1/4" PER FT) 45 3' - 7 1/4" AJ TRUSS FIELD SPLICE (ADJUST OUTRIGGER SPACING AS SHOWN TO ACCOMMODATE SPLICE) 21/S8.2 44 AK S9.1 W8x18 W8x18 W8x18 TYP @ BRACE W8x18 W8x18 7' - 4 3/8" AL W8x18 43 DIAG BRACE, TYP S8.2 TYP 18' - 4" 2 4' - 5" 5' - 0" 15' - 0" 5' - 0" W8x18 5' - 0" 5' - 0" 5' - 0" 5' - 0" W8x18 W8x18 W8x18 5' - 0" 5' - 0" 5' - 0" 5' - 0" W8x18 W8x18 W8x18 W8x18 W8x18 W8x18 W8x18 W8x18 5' - 0" 5' - 0" 5' - 0" 5' - 0" 5' - 0" 5' - 0" 5' - 0" 5' - 0" AM 2 PROVIDE HSS5X5X5/16 DIAPHRAGM CONN BETWEEN OUTRIGGERS, TYP 1' - 11" 1' - 11 3/4" R=36 K, TYP FOR SIM BEAMS W24x104 (LOFT BLOCK BEAM) DIAPHRAGM SHEAR: W=0.64 KLF, E=0.65 KLF W18x86 W21x44 DIAPHRAGM SHEAR: W=0.5 KLF, E=0.1 KLF W12x50 c=0" 3" EOD DECK BRG 144'- 7" (AT WALL) 34 41 AQ AR AS AT AU AV R=17 K S8.2 16' - 5 1/4" R=39 K AP 2' - 4 3/4" 2' - 1 3/4" 1' - 2 5/8" JST BRG 144'-1/2" 1' - 5 1/4" R=19 K 1' - 1 1/4" 13' - 7" (TYP) HSS4x4x5/16 6" EOD (TYP) HSS4x4x5/16 (LOFT BLOCK BEAM) 1' - 0 1/4" 8' - 7 5/8" 6' - 6" W8x18 W8x18 W8x18 W24x104 9' - 3" AO 2 W8x18 R=28 K AN 2' - 5 3/4" W8x18 2 S8.2 2 W8x18 1 SPAN 33 S7.1 10' - 0" AI 1 36 2 10' - 0" W8x18 W8x18 S7.1 S8.2 S7.1 R=52 K, TYP FOR SIM BEAMS W8x18 W8x18 W8x18 24 DIAG BRACE, TYP (LOFT BLOCK BEAM) 22 W8x18 W8x18 W8x18 W8x18 AH 7' - 7 1/2" W8x18 W8x18 W8x18 W8x18 W8x18 AG 7' - 4" W24x104 (LOFT BLOCK BEAM) W8x18 OUTRIGGER REACTION: (TYP) DEAD LOAD: 4.0 K LIVE LOAD: +/-4.5 K 1 RE DETAIL 51S6.1 FOR LOFT BLOCK FRAMING INFO 3 DIAPHRAGM SHEAR: W=0.42 KLF, E=0.2 KLF W8x18 DIAPHRAGM SHEAR: W=0.1 KLF, E=0.1 KLF W24x104 (LOFT BLOCK BEAM) DIAPHRAGM SHEAR: W=0.12 KLF, E=0.1 KLF 10' - 0" 2' - 0" 10' - 0" AISC STD SHEAR SPLICE 2' - 0" TYP W8x18 W8x18 68DLHSP (DOUBLE PITCH TOP CHORD 1/4" PER FT) 6' - 0" TYP W8x18 W8x18 SPAN 2 10' - 0" W8x18 W8x18 W8x18 40' - 0" 2' - 0" TYP W24x104 (LOFT BLOCK BEAM) 2 68DLHSP (DOUBLE PITCH TOP CHORD 1/4" PER FT) 10' - 0" TYP 60DLHSP (DOUBLE PITCH TOP CHORD 1/4" PER FT) 10' - 0" (LOFT BLOCK BEAM) 60DLHSP (DOUBLE PITCH TOP CHORD 1/4" PER FT) W24x104 60DLHSP (DOUBLE PITCH TOP CHORD 1/4" PER FT) 60DLH14 (DOUBLE PITCH TOP CHORD 1/4" PER FT) W8x18 10' - 0" W8x18 W8x18 2' - 3 1/2" AISC STD SHEAR SPLICE W8x18 W8x18 68DLHSP (DOUBLE PITCH TOP CHORD 1/4" PER FT) 146'-0" T.O. STEEL SLOPE 1/4" PER FT. 10' - 0" POST AND CONN TO W8 PER STAIR SUPPLIER HSS5X5X5/16 OUTRIGGER @5'-0" OC MAX, TYP (JOIST SUPPLIER TO COORDINATE LOCATIONS W/ JOIST DESIGN, TYP) SPAN W8x18 W8x18 AE AF 8' - 7 3/4" W8x18 AD 2' - 0" W8x18 S8.2 AC 14' - 11 3/8" W8x18 46 W8x18 AB 17' - 7 5/8" 5' - 0 1/4" W8x18 W8x18 W8x18 10' - 0" W8x31 W8x18 W8x18 AA 10' - 3 1/8" W8x18 S9.1 3 1/4" EOD 1' - 2 7/8"4' - 6 1/2" 9' - 7 1/4" 2' - 2" 8' - 9" OUTRIGGER REACTION: (TYP) DEAD LOAD: 0.5 K LIVE LOAD: +/-1.5 K 2 13 W8x18 W24x104 (LOFT BLOCK BEAM) S7.1 DIAPHRAGM SHEAR: W=0.5 KLF, E=0.22 KLF W24x104 (LOFT BLOCK BEAM) 10' - 0" A16 HSS5x5x5/16 10" EOD W24x104(HEAD BLOCK BEAM) DIAPHRAGM SHEAR: W=0.64 KLF, E=0.65 KLF (2)W24x104(HEAD BLOCK BEAM) 2 DECK BRG 144'- 7" (AT WALL) S7.1 23 S7.1 AW 28' - 6" AX 3 10-8-12 ADD #3 2 10-4-12 ADD #2 AY 1 9-25-12 ADD #1 33' - 8" 13-12102-00 9/25/2012 35' - 4 3/8" S1.4A 26' - 7 5/8" JOPLIN, JASPER COUNTY, MISSOURI R=19 K 2 144'-1/2" JST BRG 45 JOIST REACTIONS: DEAD LOAD = 7 K LIVE LOAD = 7.5 K TYP FOR SIM JOISTS JOPLIN HIGH SCHOOL R=28 K JOIST REACTIONS: DEAD LOAD = 18 K 2 LIVE LOAD = 19 K TYP FOR SIM JOISTS (CATWALK SUPPORT) TOP CHORD T/C AXIAL FORCES: W=0.5 KLF, E = 0.16 KLF VERIFY W/ RIGGING SUPPLIER ROOF LEVEL FRAMING PLAN - AREA A JOIST REACTIONS: DEAD LOAD = 13 K 2 LIVE LOAD = 13 K TYP FOR SIM JOISTS (CATWALK SUPPORT) S7.1 11 5/8" 32 MATCHLINE AREA A 8' - 5" A1 A2 A3 A4 A5 A6 A7 A8 A9 23' - 9 5/8" 2' - 7 1/2" 9' - 8 3/8" 24' - 1" MATCHLINE AREA B 16' - 0" C A16 A10 17' - 5 5/8" 8' - 6" AZ Architecture Engineering Planning Interiors AZ 11' - 5 5/8" A11 6' - 4 5/8" A12 10' - 6 7/8" A13 A14 A15 5' - 1" 1' - 8 5/8" B12 B13 D F 2 K PLAN NOTES: KEY NOTES: 1 B12 A. TOP OF STEEL ELEVATION AS SHOWN ON PLANS. F. PRECAST SUPPLIER TO DESIGN CONNECTIONS FOR DIAPHRAGM SHEAR LOADS SHOWN ON THE PLANS. B. REFER TO ARCHITECTURAL DRAWINGS FOR TOP OF WALL ELEVATIONS. C. BEAM REACTIONS SHOWN ARE FACTORED. D. JOIST REACTIONS SHOWN ARE UNFACTORED (SERVICE) LOADS. E 2 G. ALL CLADDING, SUPPORTS, AND ATTACHMENTS TO BE COORD WITH PRECAST SUPPLIER AND DESIGNED BY THE CONTRACTOR. 1 1 1/2" DEEP, 20 GAGE, PAINTED WIDE RIB STEEL ROOF DECK. PROVIDE 5/8" DIAMETER PUDDLE WELDS IN 36/5 PATTERN AND 2 SIDELAPS PER SPAN. 2 3" DEEP, 20 GAGE, PAINTED STEEL ROOF DECK. PROVIDE 24/4 PATTERN WITH 3/4" PUDDLE WELDS AT SUPPORTS AND (5) #10 TEK SCREWS AT SIDELAPS. G B13 L H E. DIAPHRAGM SHEAR LOADS SHOWN ARE ULTIMATE AND ARE APPLIED OVER GROSS DIAPHRAGM SECTION (NEGLECTING OPENINGS). ROOF LEVEL FRAMING PLAN - AREA A J BENJAMIN TALPOS SCALE: 1/8" = 1'-0" NORTH NORTH 7290 West 133rd Street Overland Park, Kansas 66213 tel: (913)897-7811 B © 2012, DLR Group of Missouri inc., a Missouri corporation CA No. 001614, ALL RIGHTS RESERVED. 28' - 2" A 10/8/2012 4:50:26 PM C:\Users\rrobley\Desktop\Revit 2013 Projects\Joplin HS\13-12102-00_LOCAL_struct_2012_PAC__RDR_DENVER.rvt KEY PLAN MATCHLINE RE: S1.4A MATCHLINE RE: S1.4B W21x44 (LOW) 13k 13k W21x44 (LOW) 13k 6k 58k-ft W21x44 (LOW) W10x33 4k 6 k-ft W10x33 4k 6 k-ft 7k W10x33 4k 6 k-ft 16 k-ft 4k 23 k-ft 5k 24 k-ft 20K6 W14x43 20K6 20K6 20K6 W10x33 20K6 20K6 20K6 W10x33 20K6 20K6 17k-ft 4k 26k-ft 6k 28k-ft 6k 7k-ft 2k 9k-ft 3k 10k-ft 4k 10k-ft 9k 8k W18x35 9k W16x26 9k B5 B6 25' - 4" B7 25' - 4" 29' - 8" B8 20' - 0" B9 B10 W18x35 29' - 8" W14x26 5k-ft 2k 12K3 W12x30 12K3 8k-ft 12K3 12K3 W10x33 W16x26 8k 4k 30' - 0" 3k 20KSP W12x35 6k 5k 8k 15' - 4" 32' - 6" 12K3 W10x33 4k 6 k-ft 20KSP W16x26 W18x35 W16x26 5k 82k-ft 16k W18x35 12K3 8k 5k 9k 12K3 W16x26 (LOW) W8x18 W18x35 9k-ft 4k 8k MECH UNIT PER MECH. MAX WT = 11,000# 5k 82k-ft 16k W10x33 12K3 12K3 12K3 9k-ft 9k 27k-ft SPAN 5k 12k (LOW) 7k W16x26 (LOW) 7k W10x33 4k 6 k-ft 18KSP 2 13k W18x35 5k 12k W12x19 12k 5k 5k W18x35 W16x26 W16x26 20KSP 20KSP W18x35 20KSP 20KSP 20KSP 20KSP 20KSP W12x35 20KSP 20KSP 20KSP 20KSP 20KSP 5k 1 1 12k W16x26 W10x33 4k 6 k-ft W12x26 18KSP 18KSP 18KSP 18KSP 18KSP W12x26 18KSP 18KSP 18KSP 18KSP 18KSP W12x26 18KSP 18KSP 18KSP 18KSP 18KSP 18KSP W16x26 18KSP 18KSP 18KSP 18KSP 18KSP 5k 76k-ft 13k 9k 30k-ft 17k 6k 6k 6k 6k 1 W10x33 4k 6 k-ft 6k 58k-ft 2k 9k 48k-ft B11 2k W12x19 W16x26 7k 7k MATCHLINE RE: S1.4B 14K1 16' - 0" 4k 8k-ft CA 8k 14K1 W18x60 JOPLIN, JASPER COUNTY, MISSOURI 13k MATCHLINE RE: S1.4C 16' - 0" 7' - 3" B13 B14 4k 8k-ft 2 10-08-12 ADD #3 12k 10k S1.4B (LOW) W24x103 (HIGH) 2k 5k W18x35 5k W16x36 12k W16x26 (HIGH) 4k 12k 3k 4' - 9" 20KSP (LOW) 5k 20KSP W18x35 6k 20KSP 12k (HIGH) 6k 13k W21x44 W18x40 (LOW) 6k 5k W18x35 B4 2' - 6" 2' - 6" 5k 13k 10k W18x35 11k 3k B3 4' - 6" W12x19 7k 4k W18x35 (LOW) W18x35 24' - 0" B2 4' - 6" 48k-ft 9k 11k 27' - 2" 4' - 6" 20KSP W21x44 (HIGH) 20KSP 10k 4' - 6" 9k 4' - 6" W21x44 (HIGH) 4' - 6" 8k 6' - 0" B1 9' - 8" 4' - 0" W16x26 11k 11k 7k 9k BJ 4' - 5" 4' - 0" HOIST BM W21x44 (HIGH) SPAN BH 13k 10KSP 9k 7k 10k W10x33 4k 6 k-ft W10x33 4k (HIGH) 21k W18x35 7k 10k 7k 10k 7k (HIGH) 21k W18x35 14k-ft 10k 1 12K3 12K3 12K3 12K3 9k-ft 3k 12K3 W10x33 12K3 12K3 12K3 12K3 46k-ft 9k 12K3 W10x33 12K3 12K3 12K3 12K3 12K3 13k-ft 4k 11k W18x40 4k 4k 3k 3k W10x33 12K3 12K3 12K3 12K3 12K3 14k-ft 4k W10x33 12K3 12K3 12K3 12K3 12K3 9k-ft 3k W10x22 12K3 12K3 12K3 12K3 12K3 (HIGH) 11k W16x26 13k SPAN W18x35 W18x35 5' - 0" 29k-ft 22k 1 11k 11k 5' - 0" 115k-ft 9k 76k-ft 13k 20K6 W10x33 20K6 20K6 20K6 20K6 20K6 6k 7k 35k-ft W21x44 22k W18x35 (HIGH) W10x33 4k 6 k-ft 5' - 0" 18K3 13k 9k W10x33 4k 6 k-ft 5' - 0" 1 8k-ft 3k 12K3 W10x22 10K1 10K1 10K1 10K1 10K1 W21x44 BG 6k 4' - 11" 7290 West 133rd Street Overland Park, Kansas 66213 tel: (913)897-7811 4' - 11" Architecture Engineering Planning Interiors 5' - 0" JOPLIN HIGH SCHOOL 5' - 0" Revisions 4' - 11" 9k W18x35 13k 4' - 0" W12x26 1 10-04-12 ADD #2 4' - 11" W12x26 13k 29 k-ft 6k 4' - 6" W10x33 18K3 W18x35 13k 4' - 0" 7k 8k 13-12102-00 09/10/12 4' - 2" W16x26 W14x26 4' - 2" W16x26 8k 9k 22k W10x33 11k 4' - 2" 8k 10k 47 k-ft W10x33 W10x33 61 k-ft 14k W10x33 W10x33 W10x33 54 k-ft W10x33 8k W10x33 W10x33 W10x33 8k 4' - 2" 10k-ft 1 4' - 2" W16x26 10k W10x33 4k 6 k-ft ROOF LEVEL FRAMING PLAN - AREA B W21x50 22k 3k 1 4' - 2" 5k 22k 10k-ft 4k 10k-ft 4k W10x33 W10x33 (HIGH) 2k 5 k-ft W10x33 (LOW) HSS10x6x5/8 11' - 4" 6' - 0" 4k HSS10x6x5/8 W10x33 1k W21x44 22k 4' - 2" W16x26 18K3 25k 5k 29 k-ft 6k 39k-ft W21x44 25k 4' - 2" W12x26 20K6 20K6 20K6 20K6 20K6 W10x33 20K6 20K6 20K6 20K6 20K6 W10x33 20K6 20K6 20K6 20K6 20K6 W12x26 8k 19k 4' - 2" 16k SPAN W10x33 4k 4' - 2" 8k 115k-ft BF 4' - 6" W18x40 W10x33 4k 6 k-ft 1k 4' - 8" 2k 5' - 0" 18K3 5' - 0" 2k 5' - 0" 18K3 5' - 0" 2k 5' - 0" 18K3 5' - 0" 1k 5' - 0" 18K3 5' - 0" 46k-ft 5' - 0" 11k 9k-ft 5' - 0" 1k 5' - 0" W16x26 13k 18K3 4' - 7" 2k 4' - 7" W10x33 4k 6 k-ft 16k 14k 18K3 4' - 8" 2k 4' - 8" 18K3 4' - 8" 2k 4' - 8" W10x33 W10x33 12k 4' - 8" W16x26 12k 60 k-ft 8k 43 k-ft 26 k-ft 6k 52k-ft 4' - 6" W10x33 4k 6 k-ft 16k 18K3 18K3 18K3 18K3 18K3 18K3 18K3 W18x40 16k 11k W24x55 14k BE 16k 100 k-ft W10x33 12k 4' - 6" W10x33 6k 31 k-ft HSS10x6x5/8 W18x40 16k W10x33 4k 6 k-ft 1k 1k 4' - 6" 1k 4' - 6" W18x35 10k 24' - 4" 1k 4' - 6" 2k 4' - 8" 1k 1k 4' - 10" W10x33 4k 6 k-ft 23k 10k 40 k-ft 4' - 10" 18k 100 k-ft W10x33 W10x33 W10x33 W10x33 W10x33 W10x33 W18x55 24k BD W18x46 18k W10x33 6' - 0" BC W10x33 4k 6 k-ft 20K6 3k W10x33 13 k-ft W10x33 4k 6 k-ft B12 B KEY NOTES: PLAN NOTES: 1 A. FINISHED FLOOR ELEVATION IS 116'-0", UNLESS NOTED OTHERWISE. B. TOP OF STEEL ELEVATION AS SHOWN ON PLANS. TOP OF STEEL THAT OCCURS ON A SLOPE AND IS NOT SPECIFICALLY NOTED ON THE PLANS SHALL BE LINEARLY INTERPOLATED FROM TOP OF STEEL NOTED ON THE PLANS. C. SEE SHEET S4.1 AND S4.2 "FLOOR FRAMING TYPICAL DETAILS" FOR ADDITIONAL FRAMING REQUIREMENTS AND INFORMATION. D. JOIST SUPPLIER TO COORDINATE WITH MECHANICAL CONTRACTOR FOR RTU WEIGHTS, LOCATIONS AND PENETRATIONS. E. JOIST SUPPLIER SHALL DESIGN JOISTS FOR ALL LOADS INDICATED IN S0.1 & S0.2 'GENERAL NOTES', S0.3 'ROOF SNOW DRIFT PLAN', ON THE PLAN SHEETS, AND THE SECTION/DETAIL SHEETS. CONTRACTOR TO COORDINATE ALL WEIGHTS, LOCATIONS, AND PENETRATIONS OF EQUIPMENT WITH THE JOIST SUPPLIER PRIOR TO SUBMITTING JOIST SHOP DRAWINGS. F. REFER TO GENERAL NOTES SHEETS S0.1 AND S0.2 FOR GENERAL NOTES, ABBREVIATIONS AND SYMBOLS. L. SEE SHEET S6.1 AND S6.2 "ROOF FRAMING TYPICAL DETAILS" FOR ADDITIONAL REQUIREMENTS AND INFORMATION. G. SEE ARCHITECTURAL DRAWINGS FOR LOCATION OF SLOPED, RAISED, DEPRESSED SLABS AND DRAINS. M. ALL HSS MEMBERS SHALL HAVE 1/4" CAP PLATES AT ENDS. H. J. K. REFER TO ARCHITECTURAL DRAWINGS FOR OVERALL BUILDING GEOMETRY, WALL LOCATIONS, STAIR GEOMETRY AND ADDITIONAL PARTITION WALL REQUIREMENTS. REFER TO ARCHITECTURAL DRAWINGS FOR NON-LOAD BEARING PARTITION WALLS. REFER TO SHEETS S0.1, S0.2, S2.1, S2.2, AND S9.2 TYPICAL DETAILS FOR REINFORCING, THICKENED SLABS AND OTHER REQUIREMENTS. N. PROVIDE HSS3 1/2x2 1/2x1/4 (LLH) BETWEEN ALL JOIST WITH 2 1/2" SEATS TO SUPPORT ROOF DECK WHERE DECK SWITCHES DIRECTION. (RE: 44/S6.1) P. ALL EXTERIOR EXPOSED STEEL SHALL BE GALVANIZED. Q. REFER TO TYPICAL DETAILS 11/S6.2 AND 12/S6.2 FOR FRAMING REQUIRED AT MECHANICAL UNIT CURBS. 1 1 1/2" DEEP, 20 GAGE, GALVANIZED WIDE RIB STEEL ROOF DECK. PROVIDE 5/8" DIAMETER PUBBLE WELDS IN 36/5 PATTERN AND 2 SIDELAPS PER SPAN. 2 3 1/2" DEEP, 20 GAGE, EPICORE ER3.5A OR EQUAL ACCOUSTICAL PAINTED ROOF DECK. PROVIDE 1/2" ARC SPOT WELDS IN 24/3 PATTERN AND 1/2" ARC SEAM WELDS OR 2" FILLET WELDS @ 18"OC AT SIDELAPS PER SPAN. C D 3 F K E 2" DEEP, 20 GAGE, EPICORE ER2A OR EQUAL ACCOUSTICAL PAINTED ROOF DECK. PROVIDE 1/2" ARC SPOT WELDS IN 24/3 PATTERN AND 1/2" ARC SEAM WELDS OR 2" FILLET WELDS @ 18"OC AT SIDELAPS PER SPAN. G L ALL OPENINGS IN CMU WALLS (PARTITION AND LOAD BEARING) REQUIRE A LINTEL. REFER TO SHEET S9.2 FOR TYPICAL MASONRY LINTEL DETAILS AND SCHEDULES. H ROOF LEVEL FRAMING PLAN - AREA B J SCALE: 1/8" = 1'-0" BENJAMIN TALPOS 10/8/2012 6:15:46 PM C:\Users\BrionP\Documents\9-2013-Revit Projects\Joplin\13-12102-00_central_struct_2012.rvt A NORTH NORTH © 2012, DLR Group of Missouri inc., a Missouri corporation CA No. 001614, ALL RIGHTS RESERVED. KEY PLAN B8 B9 B10 4' - 6" 14K1 16' - 0" W18x60 4k 8k-ft 4' - 5" 9k 48k-ft CA 4' - 5" 4' - 5" 1 4' - 5" W18x40 4' - 5" 14K1 4' - 5" W10x33 4k 6 k-ft 4k 3' - 10" 3' - 10" W18x35 4k W18x35 4k 5k 23 k-ft 6k 24 k-ft 6k 2k W14x26 12K3 12K3 2 W18x35 12k 12k 6' - 0" CM 87k-ft 16k W18x35 9k 9k W18x35 87k-ft 16k W18x35 8k C3 C4 25' - 7 5/8" 32' - 6" C5 30' - 0" 29' - 8" C6 C7 25' - 4" C8 25' - 4" C9 8k W10x33 4k 6 k-ft 5k-ft 2k 8k-ft 3k W16x26 (LOW) W16x26 10k 10k 8k 9k 29' - 8" C10 9k-ft 4k 8k W18x35 14K1 1' - 6 3/8" 8k 9k 13' - 8" 9' - 8" 9k 27k-ft 4k 20' - 0" C12 14K1 12k (LOW) MECH UNIT PER MECH. MAX WT = 11,000# 5k W18x35 5k 12k 15k 76k-ft 13k 5k W18x40 W12x19 76k-ft 13k 5k 11k 5k W18x35 9k-ft 4k W16x26 W16x26 20KSP 20KSP W18x35 20KSP 20KSP 20KSP 20KSP 20KSP W12x35 20KSP 20KSP 20KSP 20KSP 20KSP W12x26 18K3 18KSP 18KSP 18KSP 18KSP W12x26 18KSP 18KSP 18KSP 18KSP 18KSP W12x26 18KSP SPAN 5k CL 5k 3k 11k W16x26 W10x33 4k 6 k-ft 1 18KSP 18KSP 18KSP 18KSP 18KSP W16x26 18KSP 18KSP 18KSP 18KSP 18KSP W18x35 24' - 0" SPAN W10x33 4k 1 6 k-ft 9k 30k-ft 14K1 W10x33 4k 6 k-ft 6k 58k-ft 14K1 W10x33 4k 6 k-ft W21x44 (LOW) 14K1 W10x33 4k 6 k-ft 7k W10x33 4k 6 k-ft 6k 1 6k W10x33 4k 6 k-ft 6k 6k W10x33 4k 6 k-ft 6k 58k-ft 7k W16x26 (LOW) 7k W10x33 4k 6 k-ft W16x26 8k W18x35 4k 8k W16x26 16' - 0" 26k 26k D10 12k C13 8k 16' - 0" MATCHLINE RE: S1.4C 7' - 3" B12 MATCHLINE RE: S1.4D C14 8k B11 2 10-08-12 ADD #3 13k 78k 7290 West 133rd Street Overland Park, Kansas 66213 tel: (913)897-7811 W21x44 (LOW) S1.4C 13k 77k 5k 13k W16x36 W21x44 (LOW) 4k 13k 10k 20KSP 12k 20KSP (LOW) 20KSP W18x35 8k 12k W18x40 12k W24x103 (HIGH) 2k 6k (LOW) 20KSP W18x35 5k 14K1 12k W16x26 (HIGH) 20KSP 13k 5k 14K1 (LOW) 6k 20KSP W18x35 (HIGH) 14K1 13k W16x26 8k 11k 6k W12x35 (LOW) 10k 6k W18x35 W21x44 (HIGH) HOIST BM 11k 10k 10KSP 9k W8x18 W21x44 (HIGH) 18KSP 8k 14K1 9k 20KSP W21x44 (HIGH) 14K1 9k 7k 10k W16x26 (HIGH) 5k W18x35 24k 10k W18x35 10k 17k (HIGH) 7k W18x35 W16x26 10k 5k 11k 7k (HIGH) 7k W18x35 24k 11k 14k-ft 9k 9k-ft 3k 46k-ft 9k 13k-ft 4k 14k-ft 4k (HIGH) Architecture Engineering Planning Interiors 12K3 12K3 W10x33 12K3 12K3 12K3 W10x33 12K3 12K3 12K3 W10x33 12K3 12K3 12K3 12K3 12K3 W10x33 12K3 12K3 12K3 12K3 12K3 W10x33 12K3 12K3 12K3 12K3 12K3 W10x33 12K3 12K3 12K3 12K3 12K3 W10x33 12K3 12K3 12K3 12K3 12K3 9k-ft 3k 8k-ft 3k W18x35 Revisions 3k 9k-ft 4k 10k-ft 4k 10k-ft 10k-ft 4k 9k-ft 3k 3k 1 JOPLIN, JASPER COUNTY, MISSOURI W14x26 W12x26 JOPLIN HIGH SCHOOL 4k 7k 1 10-04-12 ADD #2 11k W16x26 13-12102-00 09/10/12 11k 26k-ft 6k 28k-ft 6k 13k W16x26 1 W10x33 12K3 12K3 20K6 20K6 20K6 20K6 W14x43 20K6 20K6 20K6 W10x33 20K6 20K6 20K6 W10x33 13k SPAN 12K3 12K3 12K3 12K3 29k-ft 6k 22k W21x44 115k-ft 1 C2 20K6 20K6 20K6 35k-ft 22k 9k 3k CK C1 1k 4k HSS10x6x5/8 4' - 5" W12x19 1 13k W18x35 20K6 W10x26 7k 13k 29 k-ft W10x33 11k W10x33 1k 18K3 18K3 18K3 18K3 46k-ft 18K3 W10x33 18K3 18K3 18K3 13k W18x35 1k7k 9k 20K6 13k 8k 47 k-ft W10x33 2k W10x33 2k W10x33 W10x33 1k 2k W10x33 W10x33 1k 14k W10x33 2k 61 k-ft W10x33 W10x33 2k 9k 22k W21x50 W16x26 8k 11k W16x26 8k 10k ROOF LEVEL FRAMING PLAN - AREA C 22k 3k 10k-ft 4k 10k-ft 4k 1 18K3 18K3 W10x26 22k W21x44 2k W10x33 1k 12k 22k 8k 5k 5k 29 k-ft 6k 39k-ft 25k W21x44 1 W10x33 10K1 10K1 10K1 10K1 10K1 W21x44 W10x33 W10x33 (HIGH) 2k 5 k-ft W12x19 (LOW) HSS10x6x5/8 11' - 4" 6' - 0" W16x26 W16x26 13k W16x26 10k W10x33 4k 14KSP 6 k-ft W12x26 20K6 20K6 20K6 20K6 20K6 W10x33 20K6 20K6 20K6 20K6 20K6 W10x33 20K6 20K6 20K6 20K6 20K6 20K6 W12x26 8k 25k 14k 16k SPAN W10x33 4k 60 k-ft W10x33 1k 18K3 19k W24x55 W16x26 8k 115k-ft CJ 8k W10x33 43 k-ft 8k 26 k-ft 6k 100 k-ft W18x40 16k 54 k-ft 16k 52k-ft W10x33 1k 18K3 18K3 18K3 18K3 18K3 18K3 W18x40 16k 12k 12k W10x33 1k W10x33 2k W10x33 W10x33 1k 1k W10x33 1k 10k 40 k-ft 6k 31 k-ft 14k CH 16k 11k W10x33 24' - 4" HSS10x6x5/8 W18x40 16k 23k W18x35 10k 18k 100 k-ft W10x33 W18x55 24k CF W18x46 18k 3k W10x33 13 k-ft 6' - 0" CE 4k 8k-ft 5k W10x33 4k 6 k-ft W18x60 14KSP 3' - 10" W10x33 4k 6 k-ft 5k 48k-ft 9k 14K1 3' - 10" W10x33 4k 6 k-ft B14 1 14K1 9k 48k-ft W10x33 4k 6 k-ft B13 14K1 14KSP 6k W10x33 4k 6 k-ft 15' - 4" W10x33 4k 6 k-ft 7' - 3" 14K1 4k 8k-ft CD 16' - 0" 4k 8k-ft 14K1 4' - 2" 30' - 8" W18x35 20' - 0" 4k B7 29' - 8" 16 k-ft B6 25' - 4" 17k-ft B5 25' - 4" 14K1 7k-ft B4 29' - 8" 7k 48k-ft 9k B3 30' - 0" 2k W12x19 W16x26 7k W12x30 B2 32' - 6" 8k W14x43 27' - 2" 4k B1 9' - 8" 2k W18x35 15' - 4" 4' - 5" W16x26 8k W18x40 9k 4k 6k W16x26 9k SPAN 8k 5k 18KSP W18x35 8k 5k 5k 82k-ft 16k W18x35 9k 4' - 6" 9k 4' - 6" W18x35 5k BJ 82k-ft 16k 17k SPAN 5k 12k 5k 12k 13k 12k 5k 12k W12x19 11k 5k 11k 76k-ft 13k 5k 5k 3k 1 76k-ft 13k B KEY NOTES: PLAN NOTES: 1 A. FINISHED FLOOR ELEVATION IS 116'-0", UNLESS NOTED OTHERWISE. B. TOP OF STEEL ELEVATION AS SHOWN ON PLANS. TOP OF STEEL THAT OCCURS ON A SLOPE AND IS NOT SPECIFICALLY NOTED ON THE PLANS SHALL BE LINEARLY INTERPOLATED FROM TOP OF STEEL NOTED ON THE PLANS. C. SEE SHEET S4.1 AND S4.2 "FLOOR FRAMING TYPICAL DETAILS" FOR ADDITIONAL FRAMING REQUIREMENTS AND INFORMATION. D. JOIST SUPPLIER TO COORDINATE WITH MECHANICAL CONTRACTOR FOR RTU WEIGHTS, LOCATIONS AND PENETRATIONS. E. JOIST SUPPLIER SHALL DESIGN JOISTS FOR ALL LOADS INDICATED IN S0.1 & S0.2 'GENERAL NOTES', S0.3 'ROOF SNOW DRIFT PLAN', ON THE PLAN SHEETS, AND THE SECTION/DETAIL SHEETS. CONTRACTOR TO COORDINATE ALL WEIGHTS, LOCATIONS, AND PENETRATIONS OF EQUIPMENT WITH THE JOIST SUPPLIER PRIOR TO SUBMITTING JOIST SHOP DRAWINGS. F. REFER TO GENERAL NOTES SHEETS S0.1 AND S0.2 FOR GENERAL NOTES, ABBREVIATIONS AND SYMBOLS. L. SEE SHEET S6.1 AND S6.2 "ROOF FRAMING TYPICAL DETAILS" FOR ADDITIONAL REQUIREMENTS AND INFORMATION. G. SEE ARCHITECTURAL DRAWINGS FOR LOCATION OF SLOPED, RAISED, DEPRESSED SLABS AND DRAINS. M. ALL HSS MEMBERS SHALL HAVE 1/4" CAP PLATES AT ENDS. H. J. K. REFER TO ARCHITECTURAL DRAWINGS FOR OVERALL BUILDING GEOMETRY, WALL LOCATIONS, STAIR GEOMETRY AND ADDITIONAL PARTITION WALL REQUIREMENTS. REFER TO ARCHITECTURAL DRAWINGS FOR NON-LOAD BEARING PARTITION WALLS. REFER TO SHEETS S0.1, S0.2, S2.1, S2.2, AND S9.2 TYPICAL DETAILS FOR REINFORCING, THICKENED SLABS AND OTHER REQUIREMENTS. N. 1 1 1/2" DEEP, 20 GAGE, GALVANIZED WIDE RIB STEEL ROOF DECK. PROVIDE 5/8" DIAMETER PUBBLE WELDS IN 36/5 PATTERN AND 2 SIDELAPS PER SPAN. 2 3 1/2" DEEP, 20 GAGE, EPICORE ER3.5A OR EQUAL ACCOUSTICAL PAINTED ROOF DECK. PROVIDE 1/2" ARC SPOT WELDS IN 24/3 PATTERN AND 1/2" ARC SEAM WELDS OR 2" FILLET WELDS @ 18"OC AT SIDELAPS PER SPAN. C D PROVIDE HSS3 1/2x2 1/2x1/4 (LLH) BETWEEN ALL JOIST WITH 2 1/2" SEATS TO SUPPORT ROOF DECK WHERE DECK SWITCHES DIRECTION. (RE: 44/S6.1) P. ALL EXTERIOR EXPOSED STEEL SHALL BE GALVANIZED. Q. REFER TO TYPICAL DETAILS 11/S6.2 AND 12/S6.2 FOR FRAMING REQUIRED AT MECHANICAL UNIT CURBS. 3 F K E 2" DEEP, 20 GAGE, EPICORE ER2A OR EQUAL ACCOUSTICAL PAINTED ROOF DECK. PROVIDE 1/2" ARC SPOT WELDS IN 24/3 PATTERN AND 1/2" ARC SEAM WELDS OR 2" FILLET WELDS @ 18"OC AT SIDELAPS PER SPAN. ALL OPENINGS IN CMU WALLS (PARTITION AND LOAD BEARING) REQUIRE A LINTEL. REFER TO SHEET S9.2 FOR TYPICAL MASONRY LINTEL DETAILS AND SCHEDULES. G L H ROOF LEVEL FRAMING PLAN - AREA C J SCALE: 1/8" = 1'-0" BENJAMIN TALPOS 10/8/2012 6:15:52 PM C:\Users\BrionP\Documents\9-2013-Revit Projects\Joplin\13-12102-00_central_struct_2012.rvt A NORTH NORTH © 2012, DLR Group of Missouri inc., a Missouri corporation CA No. 001614, ALL RIGHTS RESERVED. KEY PLAN 4' - 6" 4' - 6" 4' - 6" 4' - 6" W16x36 20KSP 20KSP 20KSP W18x40 20KSP 20KSP 20KSP 4k 6k 14K1 B12 8k 53k-ft 4' - 6" 4' - 0" 8k 21k-ft 4' - 0" 4' - 0" 4' - 0" W21x73 22K6 W21x73 30' - 8" 4' - 6" W16x26 16' - 0" 12k W18x60 26k 169k-ft 4' - 6" 14K1 C12 163k-ft 4' - 6" 4k 8k 16' - 0" W18x60 26k DA W18x35 20' - 0" 22K6 C10 4k 8k 14K1 C9 W12x35 6k 18KSP 9k W18x35 29' - 8" W16x26 22K6 C8 8k W21x73 C7 25' - 4" 22K6 C6 25' - 4" 14K1 C5 29' - 8" 10k 22K6 C3 C4 30' - 0" W16x26 14K1 32' - 6" 10k 22K6 C2 25' - 7 5/8" 14K1 1' - 6 3/8" 15' - 4" C1 9' - 8" 20KSP 9k 13' - 8" 4' - 5" 8k 22K6 W18x35 14K1 8k 5k 87k-ft 16k W18x35 14K1 9k 22K6 9k 17k W16x26 20KSP 20KSP W18x35 20KSP 20KSP 20KSP 20KSP 20KSP W12x35 20KSP 20KSP 20KSP 20KSP W18x35 14K1 6' - 0" CM 87k-ft 16k 22K6 12k 5k W18x35 14K1 12k 22K6 12k 5k W18x35 5k 12k 15k 5k 76k-ft 13k W18x40 5k 11k W12x19 W18x35 5k 11k CL 76k-ft 13k 5k 3k 5k 20KSP MECH UNIT PER MECH. MAX WT = 11,000# 2 1 1 15k-ft 5k 3k W21x73 3k 16KSP 16 k-ft W12x19 7k-ft 2k 9k-ft W14x26 12K3 W10x33 W10x33 W12x30 W21x44 (HIGH) 9k 10k W21x44 (HIGH) 11k W18x35 (LOW) 11k 13k W18x35 (LOW) 13k 12k W18x35 (LOW) 12k 12k W18x35 (LOW) 12k 13k W21x44 (LOW) 13k 13k W21x44 (LOW) 13k 6k 58k-ft W21x44 (LOW) W10x33 4k 6 k-ft 1 W12x26 W16x26 (HIGH) 5k 9k 30k-ft W16x26 (LOW) 9k 27k-ft 8k W16x26 (LOW) 8k W10x33 4k 6 k-ft 5k-ft 2k (LOW) W16x26 7k W10x33 4k 6 k-ft 4' - 0" (LOW) D12 4' - 0" W21x57 29k 178k-ft 4' - 0" 4' - 8" 4' - 8" ?k ?k ?k-ft 20KSP W24x76 35k 231k-ft 16K2 16K2 16K2 B11 S1.4D 12' - 0" 16K2 16K2 16K2 16K2 16' - 0" W16x26 26k 152k-ft 4k 13k-ft ?k-ft W16x45 5k 21k-ft 64k-ft 6k 29k-ft 4k 22k W16x45 98k-ft 20KSP W18x40 W16x36 20KSP W16x36 20KSP 20KSP 20KSP 8k 4k 18k-ft 16K2 16K2 D10 16K2 D9 W16x26 W12x22 W16x26 27k-ft 6k 8k 36' - 0" 16K2 D8 W18x40 20KSP 20KSP 20KSP 9k 16K2 W16x26 27k-ft 6k 5k 9k 29' - 8" MATCHLINE RE: S1.4E 16K2 D7 25' - 4" 16K2 D6 25' - 4" MATCHLINE RE: S1.4D 16K2 29' - 8" D5 10k 18KSP W16x26 W18x35 8k W12x35 20KSP W18x40 16K2 D4 30' - 0" W16x26 16K2 8k 17k 82k-ft 16k W18x35 3k D3 32' - 6" 7k 16K2 9k W16x26 27' - 2" W24x103 (HIGH) 2k 16K2 9k 19k-ft 9' - 8" 8k-ft 3k 9k-ft 4k 5k W21x44 W18x35 W16x26 6' - 0" DJ 82k-ft 16k 5k 12k W16x26 W18x35 5k 12k W16x26 12k 6k 20KSP 20KSP W18x35 20KSP 20KSP 20KSP 20KSP 20KSP W12x35 20KSP 20KSP 20KSP 20KSP 20KSP 18KSP 18KSP 18KSP 18KSP 18KSP W12x26 18KSP W18x35 5k 12k 13k 76k-ft 13k W18x35 5k 76k-ft 13k 5k 11k (HIGH) W24x76 W12x19 DH W18x35 5k 5k 3k 11k W16x26 W10x33 4k 6 k-ft MECH UNIT PER MECH. MAX WT = 12,500# 5k W12x26 18KSP SPAN 18KSP SPAN 18KSP 1 18KSP 1 18KSP 18KSP 18KSP 18KSP 18KSP 18KSP W16x26 18KSP 18KSP 18KSP 18KSP 18KSP W18x35 W10x33 4k 2 6 k-ft 6k 58k-ft 6k W8x18 W10x33 4k 6 k-ft 7k W10x33 4k 6 k-ft 6k W10x33 4k 6 k-ft 6k W10x33 4k 6 k-ft 6k 6k W10x33 4k 6 k-ft 10k 5' - 0" 5' - 0" 4' - 11" 4' - 11" 5' - 0" 5' - 0" 5' - 0" 4k 11k-ft 1 5' - 0" E10 D11 C13 2 10-08-12 ADD #3 8k 7290 West 133rd Street Overland Park, Kansas 66213 tel: (913)897-7811 9k W10x33 (HIGH) 8k 32k-ft W21x44 W10x33 9k 5k 10k 26k-ft (HIGH) 8k W18x35 35k-ft 10k 7k 10k HOIST BM (HIGH) 10KSP W18x35 7k 10k 21k 11k 7k (HIGH) 7k W18x35 7k 11k 21k 9k 9k-ft 4k 9k-ft 3k 46k-ft 9k (HIGH) 14k-ft W18x35 W10x33 12K3 12K3 12K3 W14x22 12K3 12K3 12K3 W12x19 12K3 12K3 12K3 W12x19 12K3 12K3 12K3 12K3 12K3 W10x33 Architecture Engineering Planning Interiors 3k 10k-ft 4k 10k-ft 4k 10k-ft W12x19 12K3 12K3 12K3 12K3 12K3 W12x19 12K3 12K3 12K3 12K3 12K3 13k-ft 4k 14k-ft 4k 9k-ft 3k 8k-ft 3k 9k 3k 24' - 0" 2 JOPLIN, JASPER COUNTY, MISSOURI 17k-ft 4k 7k JOPLIN HIGH SCHOOL W14x26 20K6 W14x43 20K6 20K6 20K6 26k-ft 11k W16x26 Revisions 11k 1 10-04-12 ADD #2 13k W16x26 6k 28k-ft 6k 13k 13-12102-00 09/10/12 22k W21x44 MATCHLINE RE: S1.4F 22k 29k-ft 6k 35k-ft 7k 13k W18x35 1 D2 W14x43 20K6 20K6 20K6 W12x35 20K6 20K6 20K6 W12x35 20K6 20K6 20K6 20K6 20K6 W12x26 SPAN 4k 3k W12x19 12K3 12K3 12K3 12K3 12K3 W10x22 12K3 12K3 12K3 12K3 12K3 W10x22 12K3 12K3 12K3 12K3 12K3 12K3 W10x22 10K1 10K1 10K1 10K1 10K1 6' - 0" DG D1 9k 26k-ft W16x26 (HIGH) 4k 7k 21k-ft 23 k-ft 6k ?k-ft 17k-ft 6k W12x19 (LOW) 4k HSS10x6x5/8 4' - 5" 16KSP W21x73 10k W16x26 (HIGH) 34k-ft 5k 24 k-ft 6k 29 k-ft 6k 22k-ft 7k 1 18K3 18K3 18K3 18K3 18k-ft 8k 1 46k-ft 18K3 (HIGH) 19k-ft W16x26 (LOW) 8k ROOF LEVEL FRAMING PLAN - AREA D W10x33 1k W10x33 18K3 18K3 13k W16x26 10k 47 k-ft W10x33 2k 11k W10x33 W10x33 2k 2k W10x33 1k 61 k-ft W10x33 1k W10x33 54 k-ft W10x33 W10x33 2k 14k W10x33 2k W10x33 2k 18K3 18K3 13k W18x35 (LOW) 9k 9k-ft 1 13k W16x26 115k-ft 3k 1 9k 22k W21x50 10k MATCHLINE RE: S1.4D 22k 16k 7' - 3" 11k W16x26 8k 3k 22k W21x44 10k-ft 4k 10k-ft 4k W21x44 W10x33 W10x33 (HIGH) 2k 5 k-ft W12x19 (LOW) HSS10x6x5/8 11' - 4" W10x33 W12x26 18K3 22k 8k 5k 5k 29 k-ft 6k 39k-ft 25k W21x44 W16x26 13k 20K6 20K6 20K6 20K6 20K6 W10x33 20K6 20K6 20K6 20K6 20K6 W10x33 20K6 20K6 20K6 20K6 20K6 20K6 W12x26 8k 25k 14k W16x26 W18x40 16k W10x33 4k 6 k-ft SPAN W10x33 4k 60 k-ft 12k W10x33 1k 18K3 19k W24x55 W16x26 8k 115k-ft DF 8k W10x33 43 k-ft 8k 26 k-ft 6k 100 k-ft 52k-ft W10x33 1k 18K3 18K3 18K3 18K3 18K3 18K3 16k 12k 12k W10x33 1k W10x33 2k W10x33 W10x33 1k 1k W10x33 1k 10k 40 k-ft 6k 31 k-ft 14k DE W18x40 16k 11k W10x33 24' - 4" HSS10x6x5/8 16k 23k W18x35 10k W18x40 16k 1k W18x55 24k DD 18k 100 k-ft W10x33 W10x33 3k 13 k-ft 6' - 0" DC W18x46 18k 25k-ft 5k 16KSP 16KSP 16KSP 16KSP 16KSP W10x33 4k 6 k-ft 16KSP W10x33 4k 6 k-ft 16KSP W10x33 4k 6 k-ft W21x73 W10x33 4k 6 k-ft W10x33 4k 6 k-ft 3k W10x33 4k 6 k-ft 10k 61k-ft 4k 187k-ft 3k 178k-ft 15' - 4" W10x33 4k 6 k-ft 14k W18x60 29k 16KSP W18x60 28k DB 18k-ft 5k 3k 13k-ft SPAN F1 B KEY NOTES: PLAN NOTES: 1 A. FINISHED FLOOR ELEVATION IS 116'-0", UNLESS NOTED OTHERWISE. B. TOP OF STEEL ELEVATION AS SHOWN ON PLANS. TOP OF STEEL THAT OCCURS ON A SLOPE AND IS NOT SPECIFICALLY NOTED ON THE PLANS SHALL BE LINEARLY INTERPOLATED FROM TOP OF STEEL NOTED ON THE PLANS. C. SEE SHEET S4.1 AND S4.2 "FLOOR FRAMING TYPICAL DETAILS" FOR ADDITIONAL FRAMING REQUIREMENTS AND INFORMATION. D. JOIST SUPPLIER TO COORDINATE WITH MECHANICAL CONTRACTOR FOR RTU WEIGHTS, LOCATIONS AND PENETRATIONS. E. JOIST SUPPLIER SHALL DESIGN JOISTS FOR ALL LOADS INDICATED IN S0.1 & S0.2 'GENERAL NOTES', S0.3 'ROOF SNOW DRIFT PLAN', ON THE PLAN SHEETS, AND THE SECTION/DETAIL SHEETS. CONTRACTOR TO COORDINATE ALL WEIGHTS, LOCATIONS, AND PENETRATIONS OF EQUIPMENT WITH THE JOIST SUPPLIER PRIOR TO SUBMITTING JOIST SHOP DRAWINGS. F. REFER TO GENERAL NOTES SHEETS S0.1 AND S0.2 FOR GENERAL NOTES, ABBREVIATIONS AND SYMBOLS. L. SEE SHEET S6.1 AND S6.2 "ROOF FRAMING TYPICAL DETAILS" FOR ADDITIONAL REQUIREMENTS AND INFORMATION. G. SEE ARCHITECTURAL DRAWINGS FOR LOCATION OF SLOPED, RAISED, DEPRESSED SLABS AND DRAINS. M. ALL HSS MEMBERS SHALL HAVE 1/4" CAP PLATES AT ENDS. H. J. K. REFER TO ARCHITECTURAL DRAWINGS FOR OVERALL BUILDING GEOMETRY, WALL LOCATIONS, STAIR GEOMETRY AND ADDITIONAL PARTITION WALL REQUIREMENTS. REFER TO ARCHITECTURAL DRAWINGS FOR NON-LOAD BEARING PARTITION WALLS. REFER TO SHEETS S0.1, S0.2, S2.1, S2.2, AND S9.2 TYPICAL DETAILS FOR REINFORCING, THICKENED SLABS AND OTHER REQUIREMENTS. N. PROVIDE HSS3 1/2x2 1/2x1/4 (LLH) BETWEEN ALL JOIST WITH 2 1/2" SEATS TO SUPPORT ROOF DECK WHERE DECK SWITCHES DIRECTION. (RE: 44/S6.1) P. ALL EXTERIOR EXPOSED STEEL SHALL BE GALVANIZED. Q. REFER TO TYPICAL DETAILS 11/S6.2 AND 12/S6.2 FOR FRAMING REQUIRED AT MECHANICAL UNIT CURBS. 1 1 1/2" DEEP, 20 GAGE, GALVANIZED WIDE RIB STEEL ROOF DECK. PROVIDE 5/8" DIAMETER PUBBLE WELDS IN 36/5 PATTERN AND 2 SIDELAPS PER SPAN. 2 3 1/2" DEEP, 20 GAGE, EPICORE ER3.5A OR EQUAL ACCOUSTICAL PAINTED ROOF DECK. PROVIDE 1/2" ARC SPOT WELDS IN 24/3 PATTERN AND 1/2" ARC SEAM WELDS OR 2" FILLET WELDS @ 18"OC AT SIDELAPS PER SPAN. C D 3 F K E 2" DEEP, 20 GAGE, EPICORE ER2A OR EQUAL ACCOUSTICAL PAINTED ROOF DECK. PROVIDE 1/2" ARC SPOT WELDS IN 24/3 PATTERN AND 1/2" ARC SEAM WELDS OR 2" FILLET WELDS @ 18"OC AT SIDELAPS PER SPAN. G L ALL OPENINGS IN CMU WALLS (PARTITION AND LOAD BEARING) REQUIRE A LINTEL. REFER TO SHEET S9.2 FOR TYPICAL MASONRY LINTEL DETAILS AND SCHEDULES. H ROOF LEVEL FRAMING PLAN - AREA D J SCALE: 1/8" = 1'-0" BENJAMIN TALPOS 10/8/2012 6:15:59 PM C:\Users\BrionP\Documents\9-2013-Revit Projects\Joplin\13-12102-00_central_struct_2012.rvt A NORTH NORTH © 2012, DLR Group of Missouri inc., a Missouri corporation CA No. 001614, ALL RIGHTS RESERVED. KEY PLAN W16x26 8k 6k 29k-ft 4k ?k ?k-ft ?k-ft W16x45 26k 152k-ft 35k 231k-ft 16' - 0" 16K2 16K2 16K2 W16x26 D10 16K2 D9 16K2 D8 36' - 0" 16K2 D7 29' - 8" MATCHLINE RE: S1.4E 16K2 D6 25' - 4" 16K2 D5 25' - 4" 16K2 D4 29' - 8" 16K2 D3 30' - 0" 16K2 D2 32' - 6" ?k 5k 21k-ft 3k 27' - 2" W16x26 D1 9' - 8" 20' - 8" 4' - 5" 22k W16x45 98k-ft 64k-ft 4k 18k-ft 19k-ft MATCHLINE RE: S1.4D 27k-ft 6k 8k 4k 13k-ft 9k B11 16K2 W16x26 27k-ft 6k 5k 9k 16K2 8k 18KSP W16x26 W18x35 17k W16x26 5k W18x40 16K2 8k W16x26 82k-ft 16k W18x35 16K2 9k 16K2 9k 16K2 W18x35 W21x44 DJ 82k-ft 16k 5k 12k W16x26 12k 5k 12k 13k 12k 5k 5k 76k-ft 13k W12x19 11k 5k 5k 76k-ft 13k 5k 3k 11k 4' - 11" 5' - 0" 5' - 0" 5' - 0" 5' - 0" 3k W24x84 229k-ft 32k 9k 42k-ft W16x50 23k 133k-ft 30k-ft 4k 3k 1 W16x26 10k 240k-ft 13k ?k-ft 4k 31k EA 25k 141k-ft 4k 11k-ft 4' - 11" 3k 4k-ft 5' - 0" 4k 8k-ft 5' - 0" 4k 11k-ft 1 1 16K2 16K2 16K2 16K2 16K2 16K2 W21x44 16K2 16K2 16K2 W16x26 16K2 16K2 16K2 16K2 16K2 16K2 16K2 16K2 W16x26 19' - 9 1/2" SPAN 32k 242k-ft 4k 11k-ft 8k 46k-ft W16x40 13k ?k-ft 21k-ft 24k 146k-ft 4k 8k-ft 4k 10k-ft 3k 230k-ft W16x26 11k 27k 184k-ft 4k 13k-ft W24x84 31k EB 4k 3k 4k 1 (HIGH) 4' - 0" 4' - 0" 16KSP 16KSP 16KSP 16KSP 4k 12k-ft 13k 49k-ft W16x36 (LOW) W24x55 (HIGH) 11k 60k-ft 15k 103k-ft 16k 96k-ft 22k 143k-ft 27k-ft W24x55 10k 49k-ft 6k 6k 4k 8k-ft (LOW) 16KSP 16KSP W21x44 16KSP W16x26 16 k-ft 5k 6k 4k (HIGH) 5k 23 k-ft W24x55 16KSP 16KSP 4k 14k-ft (LOW) 24 k-ft 6k 29 k-ft W16x26 16KSP 16KSP 16KSP 16KSP 16KSP 16KSP 16KSP 16KSP 6k W16x26 4' - 8" 20K6 20K6 20K6 20K6 W14x43 20K6 20K6 20K6 W14x43 20K6 20K6 20K6 W10x33 20K6 20K6 20K6 W10x33 20K6 20K6 2 SPAN 22k W21x44 13k 13k W16x26 11k 11k W16x26 7k 24k 143k-ft W16x45 28k-ft 18k 63k-ft W16x26 6k 17k-ft 4k 26k-ft 6k 28k-ft 6k 29k-ft 6k 35k-ft 32k 216k-ft 10k-ft 4k 10k-ft 4k 10k-ft 12K3 12K3 12K3 12KSP 12KSP 12K3 12KSP 12KSP 12K3 12KSP 12K3 12K3 12K3 12K3 12K3 12K3 12K3 12K3 W10x22 12K3 12K3 12K3 W10x22 12K3 12K3 W18x35 12k 6' - 0" 27' - 2" E3 32' - 6" E4 30' - 0" 85k-ft 16k 29' - 8" E5 E6 9k-ft 4k 9k-ft W10x33 4k 6 k-ft W10x33 4k 6 k-ft 6k W8x18 (LOW) W8x18 HOIST BM MECH UNIT PER MECH. MAX WT = 15,000# W18x35 10k 10k 25' - 4" E7 W18x35 86k-ft 16k 8k 25' - 4" E8 29' - 8" E9 8k 12k 20KSP 20KSP 20KSP 18KSP 18KSP 20KSP W12x35 20KSP W16x26 20KSP W18x35 W18x35 20KSP W18x35 20KSP 20KSP 20KSP 20KSP 20KSP W12x35 20KSP 20KSP 20KSP 20KSP 20KSP EL 9' - 8" W16x26 EJ 8k 20' - 0" E10 16' - 0" 16' - 0" E11 C13 G1 E12 D11 2 10-08-12 ADD #3 12k 8k W16x26 (LOW) 7290 West 133rd Street Overland Park, Kansas 66213 tel: (913)897-7811 12k 13k W18x35 5k 12k 9k S1.4E W12x26 18KSP 18KSP 18KSP 18KSP 18KSP W12x26 18KSP 18KSP 18KSP 18KSP 18KSP W12x26 77k-ft 14k W18x40 W12x19 77k-ft 14k (LOW) W12x26 5k 11k 5k 5k 3k EK W18x35 W16x26 SPAN 5k 18KSP 18KSP 18KSP 18KSP 18KSP 18KSP W16x26 18KSP 18KSP 18KSP 18KSP 18KSP W18x35 1 (HIGH) 9k 17k 24' - 0" 1 W21x44 3k 2 SPAN 11k 4k W10x33 4k 6 k-ft 6k 29k-ft 5k 7k W10x33 4k 6 k-ft W21x44 (LOW) 6k 34k-ft 6k 7k 16k 74k-ft (HIGH) 21k 9k-ft 3k W21x44 (LOW) 16k 72k-ft 7k W10x33 4k 6 k-ft 46k-ft 9k 13k W16x26 Architecture Engineering Planning Interiors 12K3 12K3 12K3 W10x22 12K3 12K3 12K3 12K3 12K3 W10x22 12K3 12K3 12K3 12K3 12K3 (LOW) W16x26 1 W21x44 5k W10x33 4k 6 k-ft 13k 6k MATCHLINE RE: S1.4G 12k 7k (LOW) 9k W16x26 W18x35 13k-ft 4k 12k (HIGH) 5k W10x33 4k 6 k-ft 12k 9k MATCHLINE RE: S1.4E W10x33 4k 6 k-ft W18x35 (LOW) 10k 7k 12k (HIGH) W16x26 13k 10k 49k-ft 10k W21x44 (HIGH) 5k (LOW) 14k-ft 4k 9k-ft 3k W18x35 10k 55k-ft 10k 20KSP 6k 3k W10x33 4k 6 k-ft 13k (HIGH) 44k-ft 9k W21x44 (HIGH) 21k 11k 10k 34k-ft 8k 7k (LOW) 11k W21x44 14k-ft W18x35 (HIGH) W18x35 6k 11k 11k W18x35 6k 9k W18x35 6k (HIGH) 8k-ft 3k 9k W18x35 Revisions 4k MECH UNIT PER MECH. MAX WT = 1,500# 1 10-04-12 ADD #2 7k 22k 13-12102-00 09/10/12 20K6 20K6 20K6 W12x26 1 18K3 18K3 18K3 4' - 8" JOPLIN, JASPER COUNTY, MISSOURI 4' - 8" JOPLIN HIGH SCHOOL 4' - 8" MATCHLINE RE: S1.4F 4' - 8" 20K6 4' - 0" MATCHLINE RE: S1.4E W10x33 1k 47 k-ft W10x33 2k 11k W10x33 2k W10x33 2k 18K3 (HIGH) 8k 4' - 0" 1 E2 W24x55 7k 1 13k W18x35 9k-ft 3k W10x22 12K3 12K3 12K3 12K3 12K3 W10x22 12K3 12K3 12K3 12K3 12K3 W10x22 12K3 12K3 12K3 12K3 12K3 12K3 W10x22 10K1 10K1 10K1 10K1 10K1 W21x44 EH E1 (LOW) MECH UNIT PER MECH. MAX WT = 1,500# 46k-ft 18K3 W10x33 13k W16x26 4k HSS10x6x5/8 4' - 5" 3k W10x33 54 k-ft W10x33 W10x33 1k 18K3 18K3 13k W18x35 1 1 1k W10x33 2k 14k W10x33 W10x33 2k 18K3 13k (HIGH) 9k 115k-ft 3k 10k-ft 4k 1 9k 22k W21x44 W24x55 7k W10x33 4k 6 k-ft ROOF LEVEL FRAMING PLAN - AREA E 22k (LOW) W10x33 4k 6 k-ft 9k MECH UNIT PER MECH. MAX WT = 1,500# 2 W18x40 W10x33 4k 6 k-ft 11k W16x26 8k 3k 22k W21x44 2k W10x33 1k W12x26 18K3 22k 8k 5k 5k 29 k-ft 6k 39k-ft 25k W21x44 10k-ft 4k W10x33 (HIGH) 2k W10x33 5 k-ft W10x33 (LOW) HSS10x6x5/8 11' - 4" 6' - 0" W16x26 W16x26 13k 20K6 20K6 20K6 20K6 20K6 W10x33 20K6 20K6 20K6 20K6 20K6 W10x33 20K6 20K6 20K6 20K6 20K6 20K6 W12x26 8k 25k 3k 14k W10x33 4k 6 k-ft SPAN W10x33 4k 60 k-ft 12k W10x33 1k 18K3 19k W24x55 W16x26 8k 115k-ft EG 8k W10x33 43 k-ft 8k 26 k-ft 6k 100 k-ft W10x33 16k 61 k-ft W18x40 16k 52k-ft W10x33 1k 18K3 18K3 18K3 18K3 18K3 18K3 EF 16k W10x33 4k 6 k-ft 12k 12k W10x33 1k W10x33 2k W10x33 W10x33 1k 1k W10x33 1k 10k 40 k-ft 6k 31 k-ft 14k W18x40 16k W10x33 4k 6 k-ft 11k W10x33 24' - 4" HSS10x6x5/8 W10x33 4k 6 k-ft 23k W18x35 10k 18k 100 k-ft W12x19 W18x35 24k ED W18x40 18k 3k W10x33 13 k-ft 6' - 0" EC W10x33 4k 6 k-ft 18K3 W10x33 4k 6 k-ft W16x26 20' - 10 1/2" 1 G2 B KEY NOTES: PLAN NOTES: 1 A. FINISHED FLOOR ELEVATION IS 116'-0", UNLESS NOTED OTHERWISE. B. TOP OF STEEL ELEVATION AS SHOWN ON PLANS. TOP OF STEEL THAT OCCURS ON A SLOPE AND IS NOT SPECIFICALLY NOTED ON THE PLANS SHALL BE LINEARLY INTERPOLATED FROM TOP OF STEEL NOTED ON THE PLANS. C. SEE SHEET S4.1 AND S4.2 "FLOOR FRAMING TYPICAL DETAILS" FOR ADDITIONAL FRAMING REQUIREMENTS AND INFORMATION. D. JOIST SUPPLIER TO COORDINATE WITH MECHANICAL CONTRACTOR FOR RTU WEIGHTS, LOCATIONS AND PENETRATIONS. E. JOIST SUPPLIER SHALL DESIGN JOISTS FOR ALL LOADS INDICATED IN S0.1 & S0.2 'GENERAL NOTES', S0.3 'ROOF SNOW DRIFT PLAN', ON THE PLAN SHEETS, AND THE SECTION/DETAIL SHEETS. CONTRACTOR TO COORDINATE ALL WEIGHTS, LOCATIONS, AND PENETRATIONS OF EQUIPMENT WITH THE JOIST SUPPLIER PRIOR TO SUBMITTING JOIST SHOP DRAWINGS. F. REFER TO GENERAL NOTES SHEETS S0.1 AND S0.2 FOR GENERAL NOTES, ABBREVIATIONS AND SYMBOLS. L. SEE SHEET S6.1 AND S6.2 "ROOF FRAMING TYPICAL DETAILS" FOR ADDITIONAL REQUIREMENTS AND INFORMATION. G. SEE ARCHITECTURAL DRAWINGS FOR LOCATION OF SLOPED, RAISED, DEPRESSED SLABS AND DRAINS. M. ALL HSS MEMBERS SHALL HAVE 1/4" CAP PLATES AT ENDS. H. J. K. REFER TO ARCHITECTURAL DRAWINGS FOR OVERALL BUILDING GEOMETRY, WALL LOCATIONS, STAIR GEOMETRY AND ADDITIONAL PARTITION WALL REQUIREMENTS. REFER TO ARCHITECTURAL DRAWINGS FOR NON-LOAD BEARING PARTITION WALLS. REFER TO SHEETS S0.1, S0.2, S2.1, S2.2, AND S9.2 TYPICAL DETAILS FOR REINFORCING, THICKENED SLABS AND OTHER REQUIREMENTS. N. 1 1 1/2" DEEP, 20 GAGE, GALVANIZED WIDE RIB STEEL ROOF DECK. PROVIDE 5/8" DIAMETER PUBBLE WELDS IN 36/5 PATTERN AND 2 SIDELAPS PER SPAN. 2 3 1/2" DEEP, 20 GAGE, EPICORE ER3.5A OR EQUAL ACCOUSTICAL PAINTED ROOF DECK. PROVIDE 1/2" ARC SPOT WELDS IN 24/3 PATTERN AND 1/2" ARC SEAM WELDS OR 2" FILLET WELDS @ 18"OC AT SIDELAPS PER SPAN. C D PROVIDE HSS3 1/2x2 1/2x1/4 (LLH) BETWEEN ALL JOIST WITH 2 1/2" SEATS TO SUPPORT ROOF DECK WHERE DECK SWITCHES DIRECTION. (RE: 44/S6.1) P. ALL EXTERIOR EXPOSED STEEL SHALL BE GALVANIZED. Q. REFER TO TYPICAL DETAILS 11/S6.2 AND 12/S6.2 FOR FRAMING REQUIRED AT MECHANICAL UNIT CURBS. 3 F K E 2" DEEP, 20 GAGE, EPICORE ER2A OR EQUAL ACCOUSTICAL PAINTED ROOF DECK. PROVIDE 1/2" ARC SPOT WELDS IN 24/3 PATTERN AND 1/2" ARC SEAM WELDS OR 2" FILLET WELDS @ 18"OC AT SIDELAPS PER SPAN. ALL OPENINGS IN CMU WALLS (PARTITION AND LOAD BEARING) REQUIRE A LINTEL. REFER TO SHEET S9.2 FOR TYPICAL MASONRY LINTEL DETAILS AND SCHEDULES. G L H ROOF LEVEL FRAMING PLAN - AREA E J SCALE: 1/8" = 1'-0" BENJAMIN TALPOS 10/8/2012 6:16:05 PM C:\Users\BrionP\Documents\9-2013-Revit Projects\Joplin\13-12102-00_central_struct_2012.rvt A NORTH NORTH © 2012, DLR Group of Missouri inc., a Missouri corporation CA No. 001614, ALL RIGHTS RESERVED. KEY PLAN 10" W10x33 4' - 8" REFER TO GENERAL NOTES SHEETS S0.1 AND S0.2 FOR GENERAL NOTES, ABBREVIATIONS AND SYMBOLS. G. SEE ARCHITECTURAL DRAWINGS FOR LOCATION OF SLOPED, RAISED, DEPRESSED SLABS AND DRAINS. H. REFER TO ARCHITECTURAL DRAWINGS FOR OVERALL BUILDING GEOMETRY, WALL LOCATIONS, STAIR GEOMETRY AND ADDITIONAL PARTITION WALL REQUIREMENTS. J. REFER TO ARCHITECTURAL DRAWINGS FOR NON-LOAD BEARING PARTITION WALLS. REFER TO SHEETS S0.1, S0.2, S2.1, S2.2, AND S9.2 TYPICAL DETAILS FOR REINFORCING, THICKENED SLABS AND OTHER REQUIREMENTS. K. ALL OPENINGS IN CMU WALLS (PARTITION AND LOAD BEARING) REQUIRE A LINTEL. REFER TO SHEET S9.2 FOR TYPICAL MASONRY LINTEL DETAILS AND SCHEDULES. L. SEE SHEET S6.1 AND S6.2 "ROOF FRAMING TYPICAL DETAILS" FOR ADDITIONAL REQUIREMENTS AND INFORMATION. M. ALL HSS MEMBERS SHALL HAVE 1/4" CAP PLATES AT ENDS. N. PROVIDE HSS3 1/2x2 1/2x1/4 (LLH) BETWEEN ALL JOIST WITH 2 1/2" SEATS TO SUPPORT ROOF DECK WHERE DECK SWITCHES DIRECTION. (RE: 44/S6.1) P. ALL EXTERIOR EXPOSED STEEL SHALL BE GALVANIZED. Q. REFER TO TYPICAL DETAILS 11/S6.2 AND 12/S6.2 FOR FRAMING REQUIRED AT MECHANICAL UNIT CURBS. 5' - 0" 5' - 0" 4' - 10" 4' - 8" 4' - 8" 4' - 10" 4' - 10" 16k 4' - 10" 4' - 8" W16x36 24' - 0" 8k KG 4' - 8" 4' - 10" MATCHLINE RE: S1.4F 1 4' - 10" W16x36 W14x43 S8.5 4' - 10" 18k-ft 4k 32k 216k-ft 16k EF 28k-ft 24k 143k-ft 6k 4' - 10" 20K6 20K6 20K6 20K6 20K6 20K6 20K6 W14x43 24' - 0" 35 W24x76 8k 4' - 10" 4' - 10" 12K3 W10x33 12KSP W12x19 W12x19 3k 3k 4' - 8" 12K3 12KSP W16x36 12K3 12KSP 24' - 0" 12K3 12KSP W10x33 12K3 12K3 12KSP EG 12K3 12K3 W10x33 16k KH 16k W21x44 14' - 5" 4' - 4" 17k 12KSP 12KSP 8k KK 4' - 4" 3k 12KSP W12x16 SPAN 12k 4' - 10" 1 1 8k S1.4F 4' - 10" EH EJ KEY PLAN 4' - 4" MATCHLINE RE: S1.4F 4' - 4" W16x26 26' - 0" MATCHLINE RE: S1.4G 4' - 4" 17k B 9k 16k KL 37' - 4" C K1 D F1 F2 K2 F K E G L H ROOF LEVEL FRAMING PLAN - AREA F J SCALE: 1/8" = 1'-0" BENJAMIN TALPOS 10/8/2012 6:16:11 PM C:\Users\BrionP\Documents\9-2013-Revit Projects\Joplin\13-12102-00_central_struct_2012.rvt 4' - 4" A NORTH NORTH © 2012, DLR Group of Missouri inc., a Missouri corporation CA No. 001614, ALL RIGHTS RESERVED. 4' - 8" 2 10-08-12 ADD #3 4' - 8" 7290 West 133rd Street Overland Park, Kansas 66213 tel: (913)897-7811 4' - 8" JOPLIN, JASPER COUNTY, MISSOURI 4' - 10" 2" DEEP, 20 GAGE, EPICORE ER2A OR EQUAL ACCOUSTICAL PAINTED ROOF DECK. PROVIDE 1/2" ARC SPOT WELDS IN 24/3 PATTERN AND 1/2" ARC SEAM WELDS OR 2" FILLET WELDS @ 18"OC AT SIDELAPS PER SPAN. 4' - 10" 20k 112k-ft SPAN W14x43 3 4' - 8" 4' - 8" 1 20K6 3 1/2" DEEP, 20 GAGE, EPICORE ER3.5A OR EQUAL ACCOUSTICAL PAINTED ROOF DECK. PROVIDE 1/2" ARC SPOT WELDS IN 24/3 PATTERN AND 1/2" ARC SEAM WELDS OR 2" FILLET WELDS @ 18"OC AT SIDELAPS PER SPAN. 4' - 10" (HIGH) 16k W24x62 15k 101k-ft 19k-ft (LOW) 16k 4' - 8" 2 4' - 10" 16k W12x22 W24x55 (LOW) 50k 98k-ft ED 4' - 8" 1 1/2" DEEP, 20 GAGE, GALVANIZED WIDE RIB STEEL ROOF DECK. PROVIDE 5/8" DIAMETER PUBBLE WELDS IN 36/5 PATTERN AND 2 #10 TEK SCREWS AT SIDELAPS PER SPAN. 8k KF 3k 8k-ft W24x55 4k 22k 143k-ft 1 4' - 8" W16x36 24' - 0" W12x22 3k 7k-ft 3k 8k-ft W10x33 4k 6 k-ft W12x22 16KSP 16KSP 16KSP 16KSP 16KSP 16KSP 16KSP 16k 96k-ft 27k-ft 15k 103k-ft 6k 11k 60k-ft KEY NOTES: 4' - 10" 16k 3k 7k-ft W12x22 16K2 16K2 16K2 4k 11k-ft W12x22 W10x33 4k 6 k-ft 4k 12k-ft 16KSP 16KSP F. W24x68 27k 184k-ft 4k 13k-ft 24k 146k-ft MATCHLINE RE: S1.4E JOIST SUPPLIER SHALL DESIGN JOISTS FOR ALL LOADS INDICATED IN S0.1 & S0.2 'GENERAL NOTES', S0.3 'ROOF SNOW DRIFT PLAN', ON THE PLAN SHEETS, AND THE SECTION/DETAIL SHEETS. CONTRACTOR TO COORDINATE ALL WEIGHTS, LOCATIONS, AND PENETRATIONS OF EQUIPMENT WITH THE JOIST SUPPLIER PRIOR TO SUBMITTING JOIST SHOP DRAWINGS. 4' - 10" 15k 8k KE 16K2 16K2 16K2 16K2 W12x22 16K2 16K2 W16x40 4' - 10" W16x36 4' - 8" 24' - 0" W12x22 3k 8k-ft W24x68 25k 141k-ft 4k 11k-ft 13k ?k-ft (HIGH) E. 4' - 10" 15k 3k 8k-ft W12x22 16K2 16K2 16K2 16K2 16K2 16K2 16K2 W12x22 4k 11k-ft W16x50 10' - 0" 10' - 0" W12x19 2k 4k-ft KC W24x76 35k 231k-ft 6k 5k W16x36 5k 2k 4k-ft KB W12x19 20KSP 20KSP 20KSP 20KSP 20KSP 20KSP 20KSP W18x40 6k 29k-ft 26k 152k-ft 16K2 16K2 1' - 6" 3k 7k-ft FA W16x26 1 EC JOIST SUPPLIER TO COORDINATE WITH MECHANICAL CONTRACTOR FOR RTU WEIGHTS, LOCATIONS AND PENETRATIONS. Architecture Engineering Planning Interiors W10x33 W10x33 4' - 8" 4k 13k-ft W16x45 (LOW) D. JOPLIN HIGH SCHOOL 4' - 8" 1 EB SEE SHEET S4.1 AND S4.2 "FLOOR FRAMING TYPICAL DETAILS" FOR ADDITIONAL FRAMING REQUIREMENTS AND INFORMATION. 1 1 EA C. Revisions 4' - 8" W10x33 W10x33 W10x33 4' - 8" KA W10x33 W16x36 20KSP 4k ?k ?k-ft TOP OF STEEL ELEVATION AS SHOWN ON PLANS. TOP OF STEEL THAT OCCURS ON A SLOPE AND IS NOT SPECIFICALLY NOTED ON THE PLANS SHALL BE LINEARLY INTERPOLATED FROM TOP OF STEEL NOTED ON THE PLANS. 1 10-04-12 ADD #2 4' - 8" DH ?k B. 13-12102-00 09/10/12 4' - 8" W24x76 DJ FINISHED FLOOR ELEVATION IS 116'-0", UNLESS NOTED OTHERWISE. 14' - 6" 4' - 8" 30k 178k-ft 16' - 0" 4' - 0" W10x33 W10x33 8k 32k-ft D12 W10x33 29k 178k-ft (LOW) 4' - 0" W21x57 MATCHLINE RE: S1.4K MATCHLINE RE: S1.4F W10x33 W10x33 10k W16x26 7k A. ROOF LEVEL FRAMING PLAN - AREA F W14x26 7k-ft 37' - 4" W10x33 5k DG PLAN NOTES: 2 5k-ft 2k DF MATCHLINE RE: S1.4F MATCHLINE RE: S1.4D 17k-ft 4k 2k DE 15' - 4" 12' - 0" EQ EQ (LOW) W24x76 44k EQ 44k W24x76 (LOW) 44k EQ W8x31 (HIGH) 44k EQ W24x76 (LOW) 44k EQ EQ EQ 12' - 0" 44k 236k-ft W24x68 (LOW) 66k 65k 12' - 0" 8' - 9" 8' - 9" 5k W12x22 (HIGH) 15° W12x 22 W12x22 JOIST SUPPLIER TO COORDINATE WITH MECHANICAL CONTRACTOR FOR RTU WEIGHTS, LOCATIONS AND PENETRATIONS. E. JOIST SUPPLIER SHALL DESIGN JOISTS FOR ALL LOADS INDICATED IN S0.1 & S0.2 'GENERAL NOTES', S0.3 'ROOF SNOW DRIFT PLAN', ON THE PLAN SHEETS, AND THE SECTION/DETAIL SHEETS. CONTRACTOR TO COORDINATE ALL WEIGHTS, LOCATIONS, AND PENETRATIONS OF EQUIPMENT WITH THE JOIST SUPPLIER PRIOR TO SUBMITTING JOIST SHOP DRAWINGS. F. REFER TO GENERAL NOTES SHEETS S0.1 AND S0.2 FOR GENERAL NOTES, ABBREVIATIONS AND SYMBOLS. G. SEE ARCHITECTURAL DRAWINGS FOR LOCATION OF SLOPED, RAISED, DEPRESSED SLABS AND DRAINS. H. REFER TO ARCHITECTURAL DRAWINGS FOR OVERALL BUILDING GEOMETRY, WALL LOCATIONS, STAIR GEOMETRY AND ADDITIONAL PARTITION WALL REQUIREMENTS. J. REFER TO ARCHITECTURAL DRAWINGS FOR NON-LOAD BEARING PARTITION WALLS. REFER TO SHEETS S0.1, S0.2, S2.1, S2.2, AND S9.2 TYPICAL DETAILS FOR REINFORCING, THICKENED SLABS AND OTHER REQUIREMENTS. K. ALL OPENINGS IN CMU WALLS (PARTITION AND LOAD BEARING) REQUIRE A LINTEL. REFER TO SHEET S9.2 FOR TYPICAL MASONRY LINTEL DETAILS AND SCHEDULES. L. SEE SHEET S6.1 AND S6.2 "ROOF FRAMING TYPICAL DETAILS" FOR ADDITIONAL REQUIREMENTS AND INFORMATION. M. ALL HSS MEMBERS SHALL HAVE 1/4" CAP PLATES AT ENDS. N. PROVIDE HSS3 1/2x2 1/2x1/4 (LLH) BETWEEN ALL JOIST WITH 2 1/2" SEATS TO SUPPORT ROOF DECK WHERE DECK SWITCHES DIRECTION. (RE: 44/S6.1) P. ALL EXTERIOR EXPOSED STEEL SHALL BE GALVANIZED. Q. REFER TO TYPICAL DETAILS 11/S6.2 AND 12/S6.2 FOR FRAMING REQUIRED AT MECHANICAL UNIT CURBS. (DOUBLE PITCHED TOP CHORD, SLOPE 1/4" PER FOOT) 120SLH22 W12x 22 RK7 15° HSS6 x6x5/1 6 W12x 22 1 1 1/2" DEEP, 20 GAGE, GALVANIZED WIDE RIB STEEL ROOF DECK. PROVIDE 5/8" DIAMETER PUBBLE WELDS IN 36/5 PATTERN AND 2 #10 TEK SCREWS AT SIDELAPS PER SPAN. 2 3 1/2" DEEP, 20 GAGE, EPICORE ER3.5A OR EQUAL ACCOUSTICAL PAINTED ROOF DECK. PROVIDE 1/2" ARC SPOT WELDS IN 24/3 PATTERN AND 1/2" ARC SEAM WELDS OR 2" FILLET WELDS @ 18"OC AT SIDELAPS PER SPAN. 3 2" DEEP, 20 GAGE, EPICORE ER2A OR EQUAL ACCOUSTICAL PAINTED ROOF DECK. PROVIDE 1/2" ARC SPOT WELDS IN 24/3 PATTERN AND 1/2" ARC SEAM WELDS OR 2" FILLET WELDS @ 18"OC AT SIDELAPS PER SPAN. 15° (DOUBLE PITCHED TOP CHORD, SLOPE 1/4" PER FOOT) 120SLH22 KEY NOTES: RKC W12x 22 (DOUBLE PITCHED TOP CHORD, SLOPE 1/4" PER FOOT) 120SLH22 W12x22 (DOUBLE PITCHED TOP CHORD, SLOPE 1/4" PER FOOT) 120SLH22 120SLH22 SPAN RKB (DOUBLE PITCHED TOP CHORD, SLOPE 1/4" PER FOOT) (DOUBLE PITCHED TOP CHORD, SLOPE 1/4" PER FOOT) (DOUBLE PITCHED TOP CHORD, SLOPE 1/4" PER FOOT) 2 15° HSS6 x6x5/1 6 W12x 22 120SLH22 (DOUBLE PITCHED TOP CHORD, SLOPE 1/4" PER FOOT) (DOUBLE PITCHED TOP CHORD, SLOPE 1/4" PER FOOT) 1 RK6 15° HANGING BASKETBALL GOAL & CONNECTIONS TO STRUCTURE BY BASKETBALL GOAL SUPPLIER 120SLH22 (DOUBLE PITCHED TOP CHORD, SLOPE 1/4" PER FOOT) (DOUBLE PITCHED TOP CHORD, SLOPE 1/4" PER FOOT) 120SLH22 (DOUBLE PITCHED TOP CHORD, SLOPE 1/4" PER FOOT) 120SLH22 (DOUBLE PITCHED TOP CHORD, SLOPE 1/4" PER FOOT) (DOUBLE PITCHED TOP CHORD, SLOPE 1/4" PER FOOT) 120SLH22 (DOUBLE PITCHED TOP CHORD, SLOPE 1/4" PER FOOT) 6k SCOREBOARD SUPPORT STRUCTURE BY SCOREBOARD SUPPLIER W12x22 W12x 22 HANGING BASKETBALL GOAL & CONNECTIONS TO STRUCTURE BY BASKETBALL GOAL SUPPLIER JOIST SUPPLIER TO DESIGN JOISTS FOR 2,000# HANGING BASKETBALL GOAL RK8 15° 6k HSS6 x6x5/1 6 W12x 22 15° 6k 120SLH22 120SLH22 120SLH22 120SLH22 W12x22 (HIGH) 6k 6k W12x22 (MITERED)(HIGH) W16x36 16k 16k JOIST SUPPLIER TO DESIGN JOISTS FOR 2,000# HANGING BASKETBALL GOAL JOIST SUPPLIER TO DESIGN JOISTS FOR 3,000# HANGING SCOREBOARD JOIST SUPPLIER TO DESIGN JOISTS FOR 2,000# HANGING BASKETBALL GOAL 8k 26KSP 26KSP W12x 22 33 W12x22 W16x36 26KSP W12x22 (HIGH) (LOW) RKD S8.6 RK9 15° HSS6 x6x5/1 6 W12x 22 6k 2k 6k 16k 8k JOIST SUPPLIER TO DESIGN JOISTS FOR 2,000# HANGING BASKETBALL GOAL 15° W18x35 JOIST SUPPLIER TO DESIGN JOISTS FOR 2,000# HANGING BASKETBALL GOAL 6k 16k 26KSP 26KSP W12x 22 2k 26KSP HANGING BASKETBALL GOAL & CONNECTIONS TO STRUCTURE BY BASKETBALL GOAL SUPPLIER W12x22 W16x36 26KSP HANGING BASKETBALL GOAL & CONNECTIONS TO STRUCTURE BY BASKETBALL GOAL SUPPLIER W12x22 (HIGH) (LOW) RKE W18x35 7k 6k 16k 26KSP 2 10-08-12 ADD #3 44k 44k W24x55 44k 16K3 44k W24x55 44k 16K3 16K3 16K3 (HIGH) W16x45 16K3 16K3 16K3 16K3 C W27x84 11k 7k W24x55 7k 9k W21x44 9k W21x48 23k 11k 7k 51 W24x55 7k K W21x48 6k 6k G 30k 11k 40k 11k 69k W24x68 F E 8k 11k D MATCHLINE RE: S1.4L 19k 18k 18k 18k 18k B MATCHLINE RE: S1.4K 24k 16K3 SPAN 16K3 1 W12x22 W12x22 16K3 1 W16x45 16K3 W18x35 W16x45 16K3 A 64k 16K3 16K3 W18x35 1 W16x45 16K3 W12x22 W12x22 W18x35 W16x45 SPAN 1 W12x22 W16x45 1 23k 4' - 10" 15k 16K3 16K3 W18x35 W24x62 64k 53 S8.4 H K3 K4 L1 K5 K6 K7 L2 K8 K9 K11 K12 ROOF LEVEL FRAMING PLAN - AREA K J SCALE: 1/8" = 1'-0" NORTH NORTH © 2012, DLR Group of Missouri inc., a Missouri corporation CA No. 001614, ALL RIGHTS RESERVED. W24x55 24k 44k (HIGH) 44k 19k W24x55 5' - 0" W16x40 5' - 0" (HIGH) W16x45 W18x46 26K6 16k 44k 16K3 W18x46 W12x22 (LOW) 26KSP 44k 16K3 26K6 26KSP W24x55 18k 44k W16x45 26KSP W18x35 44k 18k W24x55 44k 18k 2k 18k W24x55 23k 2k 5' - 0" 9k 4' - 10" W18x35 5k 26KSP S8.4 BENJAMIN TALPOS Revisions KEY PLAN L K2 7290 West 133rd Street Overland Park, Kansas 66213 tel: (913)897-7811 33 Architecture Engineering Planning Interiors 26KSP S8.4 1 10-04-12 ADD #2 26KSP 1 W16x26 26KSP 13-12102-00 09/10/12 S1.4K 26KSP 3' - 9 7/8" 5k 7k W12x22 (HIGH) 7k 8k 20k 20k SCOREBOARD & CONNECTION TO STRUCTURE BY SCOREBOARD SUPPLIER HANGING BASKETBALL GOAL & CONNECTIONS TO STRUCTURE BY BASKETBALL GOAL SUPPLIER 26KSP 5' - 0" 8k HANGING BASKETBALL GOAL & CONNECTIONS TO STRUCTURE BY BASKETBALL GOAL SUPPLIER 120SLH22 6k W16x36 (LOW) 15k 16k W16x36 (LOW) 16k 16k (LOW) 26KSP 5' - 0" 4' - 10" MATCHLINE RE: S1.4L D. RIDGE 26KSP 16k 8' - 8 1/2" W12x22 (HIGH) 6k 6k W8x24 SPAN 26KSP 15k 4' - 4" 4' - 4" 4' - 4" 4' - 4" 4' - 4" 1 5' - 0" 4' - 10" 4' - 4" 17k 16k W16x45 24' - 8" MATCHLINE RE: S1.4K LA 10/8/2012 6:16:17 PM C:\Users\BrionP\Documents\9-2013-Revit Projects\Joplin\13-12102-00_central_struct_2012.rvt KM S8.6 8k 17k 4' - 8" 4' - 10" 4' - 10" 16k 17k W16x26 26' - 0" 9k KL 31 26KSP W16x26 (LOW) 4' - 10" 4' - 10" 16k W16x36 24' - 0" 8k KK 26KSP W18x35 (2) HSS6x6x5/16 TOS = FDASDF & TOS = HJSDFH 2 JOIST SUPPLIER TO DESIGN JOISTS FOR 2,000# HANGING BASKETBALL GOAL 17k 8k KH 26KSP 26KSP RK5 W12x 22 26KSP W18x35 SEE SHEET S4.1 AND S4.2 "FLOOR FRAMING TYPICAL DETAILS" FOR ADDITIONAL FRAMING REQUIREMENTS AND INFORMATION. 6k 4k 35 15° 8k 16k 4' - 10" 4' - 8" 4' - 10" 16k 4' - 10" 4' - 10" S8.5 26KSP SPAN 4' - 10" 4' - 10" 4' - 8" 4' - 10" 4' - 10" 4' - 10" 4' - 10" 4' - 8" 4' - 10" 4' - 10" 16k 16k W16x36 24' - 0" 35 26KSP W18x35 C. HSS6x6x5/16 RKA TOS = 26KSP 1 4' - 8" 4' - 10" 4' - 10" W16x36 15k 16k W16x36 16k 16k W16x36 24' - 0" 8k 26KSP 1 4' - 10" 4' - 10" 15k 24' - 0" 24' - 0" 8k KG 4k 26KSP 8k KF (LOW) 4k W16x36 5' - 0" 10' - 0" 26KSP KC KE 6k W16x36 5' - 0" 5k 5k W16x36 10' - 0" F4 6k TOP OF STEEL ELEVATION AS SHOWN ON PLANS. TOP OF STEEL THAT OCCURS ON A SLOPE AND IS NOT SPECIFICALLY NOTED ON THE PLANS SHALL BE LINEARLY INTERPOLATED FROM TOP OF STEEL NOTED ON THE PLANS. 8' - 10" S8.4 KB B. W8x31 (HIGH) (LOW) W24x55 44k 236k-ft FINISHED FLOOR ELEVATION IS 116'-0", UNLESS NOTED OTHERWISE. W8x24 W8x31 (HIGH) 44k 1 W8x24 W8x24 SPAN W8x31 (HIGH) 1 W8x24 W8x24 SPAN 44k 236k-ft 1 W8x31 A. JOPLIN, JASPER COUNTY, MISSOURI W24x55 (LOW) 44k 236k-ft W8x31 (HIGH) W8x31 PLAN NOTES: JOPLIN HIGH SCHOOL 11' - 6" 12' - 10" 44k W8x31 26' - 4" ROOF LEVEL FRAMING PLAN - AREA K W24x68 (LOW) 44k W8x31 24' - 0" 5k 2k W8x31 (HIGH) 24' - 0" W16x26 4k 16' - 0" W12x22 2k W24x68 (LOW) 1 W8x31 (HIGH) 24' - 0" W8x31 W8x24 W8x24 W8x18 (HIGH) KA 24' - 0" W8x31 W8x31 W8x24 W8x18 24' - 0" W8x24 23' - 6" 1 12' - 10" MATCHLINE RE: S1.4K MATCHLINE RE: S1.4F 42' - 0 3/8" W16x45 16K3 16K3 MATCHLINE RE: S1.4K 16K3 MATCHLINE RE: S1.4L 19k 18k 18k 18k 18k 24k 16K3 W16x45 16K3 W16x45 W18x35 W16x45 16K3 1 W12x22 W12x22 W12x22 16K3 W16x45 W16x45 16K3 7k W24x55 10' - 0" W21x48 23k 11k W24x55 7k 7k 6k W21x48 6k 53 S8.4 (DOUBLE PITCHED TOP CHORD, SLOPE 1/4" PER FOOT) 52DLH15 (DOUBLE PITCHED TOP CHORD, SLOPE 1/4" PER FOOT) (DOUBLE PITCHED TOP CHORD, SLOPE 1/4" PER FOOT) W24x76 10' - 0" 80SLH16 JOIST SUPPLIER TO DESIGN JOISTS FOR 2,000# HANGING BASKETBALL GOAL JOIST SUPPLIER TO DESIGN JOISTS FOR 2,000# HANGING BASKETBALL GOAL 52DLH15 W21x44 2 W24x68 (HIGH) W16x45 (LOW) 9k S8.4 5' - 0" 5' - 0" 5' - 0" 26KSP W21x44 9k 51 80SLH16 26KSP 7k 30k 11k 69k W27x84 11k 40k 11k 26KSP W16x36 W12x22 W12x22 16K3 23k 4' - 10" 16k 15k W24x68 11k 26KSP 30' - 0" W18x35 1 8k 5' - 0" 20k W18x35 20k 4' - 10" 16k 8k LA 4' - 10" 26K6 26KSP MATCHLINE RE: S1.4L 16K3 W16x45 W12x22 W16x40 W18x46 5' - 0" MATCHLINE RE: S1.4K 8' - 8 1/2" W16x45 W16x45 KM 26KSP 1 5' - 0" (DOUBLE PITCHED TOP CHORD, SLOPE 1/4" PER FOOT) 30k 18k 52DLH15 S8.4 31 W24x55 (DOUBLE PITCHED TOP CHORD, SLOPE 1/4" PER FOOT) 52DLH15 18k HANGING BATTING CAGE CONNECTIONS TO STRUCTURE BY BATTING CAGE SUPPLIER W8x31 4k W8x31 (HIGH) W8x24 W8x31 (HIGH) 5k W8x31 W12x22 (LOW) 4k 6k W12x26 (LOW) W8x31 (HIGH) W8x31 6k W8x31 (HIGH) 1 W8x31 5k 43 W12x26 (MITERED)(LOW) 5k 5k W8x31 (HIGH) W18x40 W12x26 (LOW) 5k 27k 55 W12x26 (LOW) HANGING BASKETBALL GOAL & CONNECTIONS TO STRUCTURE BY BASKETBALL GOAL SUPPLIER W8x31 (HIGH) W8x31 W8x31 W8x24 5k W8x24 5k SPAN W12x26 (MITERED)(LOW) W8x24 5k W8x24 W8x31 1 1 SPAN W8x18 7k W8x31 (HIGH) W8x24 W8x24 W8x18 (HIGH) W16x31 (LOW) S8.3 1 35k LF 7k (DOUBLE PITCHED TOP CHORD, SLOPE 1/4" PER FOOT) HANGING BASKETBALL GOAL & CONNECTIONS TO STRUCTURE BY BASKETBALL GOAL SUPPLIER S8.3 7k W16x31 (LOW) 7k 52DLH15 W8x24 (DOUBLE PITCHED TOP CHORD, SLOPE 1/4" PER FOOT) 61k 80SLH15 JOIST SUPPLIER TO DESIGN JOISTS FOR 2,000# HANGING BASKETBALL GOAL W24x62 JOIST SUPPLIER TO DESIGN JOISTS FOR 2,000# HANGING BASKETBALL GOAL W8x24 S8.3 W21x44 41 8' - 10 171/256" 26' - 8" (DOUBLE PITCHED TOP CHORD, SLOPE 1/4" PER FOOT) 4' - 2" 42' - 0 3/8" K3 23' - 6" 24' - 0" K4 K5 24' - 0" 19' - 10" K6 K7 28' - 2" L2 K8 24' - 0" 26' - 4" K9 K11 K12 S1.4L K2 12' - 10" JOPLIN, JASPER COUNTY, MISSOURI 52DLH15 (DOUBLE PITCHED TOP CHORD, SLOPE 1/4" PER FOOT) 2 10-08-12 ADD #3 HANGING BASKETBALL GOAL & CONNECTIONS TO STRUCTURE BY BASKETBALL GOAL SUPPLIER 7290 West 133rd Street Overland Park, Kansas 66213 tel: (913)897-7811 80SLH15 HANGING BASKETBALL GOAL & CONNECTIONS TO STRUCTURE BY BASKETBALL GOAL SUPPLIER Architecture Engineering Planning Interiors HANGING BASKETBALL GOAL & CONNECTIONS TO STRUCTURE BY BASKETBALL GOAL SUPPLIER 27k 62k 8' - 10 171/256" 36k (DOUBLE PITCHED TOP CHORD, SLOPE 1/4" PER FOOT) JOPLIN HIGH SCHOOL 52DLH15 Revisions 18k (DOUBLE PITCHED TOP CHORD, SLOPE 1/4" PER FOOT) 1 10-04-12 ADD #2 SPAN JOIST SUPPLIER TO DESIGN JOISTS FOR 2,000# HANGING BASKETBALL GOAL 13-12102-00 09/10/12 JOIST SUPPLIER TO DESIGN JOISTS FOR 2,000# HANGING BASKETBALL GOAL W16x36 W21x48 (DOUBLE PITCHED TOP CHORD, SLOPE 1/4" PER FOOT) 41k 12' - 0" 24k 80SLH16 2 52DLH15 JOIST SUPPLIER TO COORDINATE AND DESIGN JOISTS FOR BATTING CAGE LOADS. ROOF LEVEL FRAMING PLAN - AREA L (DOUBLE PITCHED TOP CHORD, SLOPE 1/4" PER FOOT) JOIST SUPPLIER TO DESIGN JOISTS FOR 2,000# HANGING BASKETBALL GOAL 6k 1 RIDGE 1 RIDGE SPAN 2 12' - 0" (HIGH) 80SLH17 18k 41k 24k (DOUBLE PITCHED TOP CHORD, SLOPE 1/4" PER FOOT) 26KSP W16x36 (DOUBLE PITCHED TOP CHORD, SLOPE 1/4" PER FOOT) W18x40 W16x36 (LOW) 26KSP 35 41k 80SLH17 8k 26KSP 26KSP HANGING BASKETBALL GOAL & CONNECTIONS TO STRUCTURE BY BASKETBALL GOAL SUPPLIER 12' - 0" 24k 16k 1 16k SPAN 26KSP W18x35 S8.6 (DOUBLE PITCHED TOP CHORD, SLOPE 1/4" PER FOOT) (DOUBLE PITCHED TOP CHORD, SLOPE 1/4" PER FOOT) W16x36 12' - 0" 80SLH17 52DLH15 41k HANGING BASKETBALL GOAL & CONNECTIONS TO STRUCTURE BY BASKETBALL GOAL SUPPLIER W18x40 (HIGH) 26KSP 69k 10' - 0" 40k (DOUBLE PITCHED TOP CHORD, SLOPE 1/4" PER FOOT) 24k 16k (LOW) W16x36 26KSP 16k 4' - 10" 4' - 10" 16k 4' - 10" 4' - 8" 4' - 10" 16k W16x36 24' - 0" 6k LD 80SLH16 26KSP 1 4' - 10" 4' - 8" 4' - 10" 16k 4' - 10" W16x36 24' - 0" 8k LC 8k 20k 5' - 0" W18x35 8k 16k LB 4' - 10" 20k 26KSP B KEY NOTES: PLAN NOTES: 1 A. FINISHED FLOOR ELEVATION IS 116'-0", UNLESS NOTED OTHERWISE. B. TOP OF STEEL ELEVATION AS SHOWN ON PLANS. TOP OF STEEL THAT OCCURS ON A SLOPE AND IS NOT SPECIFICALLY NOTED ON THE PLANS SHALL BE LINEARLY INTERPOLATED FROM TOP OF STEEL NOTED ON THE PLANS. C. SEE SHEET S4.1 AND S4.2 "FLOOR FRAMING TYPICAL DETAILS" FOR ADDITIONAL FRAMING REQUIREMENTS AND INFORMATION. D. JOIST SUPPLIER TO COORDINATE WITH MECHANICAL CONTRACTOR FOR RTU WEIGHTS, LOCATIONS AND PENETRATIONS. E. JOIST SUPPLIER SHALL DESIGN JOISTS FOR ALL LOADS INDICATED IN S0.1 & S0.2 'GENERAL NOTES', S0.3 'ROOF SNOW DRIFT PLAN', ON THE PLAN SHEETS, AND THE SECTION/DETAIL SHEETS. CONTRACTOR TO COORDINATE ALL WEIGHTS, LOCATIONS, AND PENETRATIONS OF EQUIPMENT WITH THE JOIST SUPPLIER PRIOR TO SUBMITTING JOIST SHOP DRAWINGS. F. REFER TO GENERAL NOTES SHEETS S0.1 AND S0.2 FOR GENERAL NOTES, ABBREVIATIONS AND SYMBOLS. L. SEE SHEET S6.1 AND S6.2 "ROOF FRAMING TYPICAL DETAILS" FOR ADDITIONAL REQUIREMENTS AND INFORMATION. G. SEE ARCHITECTURAL DRAWINGS FOR LOCATION OF SLOPED, RAISED, DEPRESSED SLABS AND DRAINS. M. ALL HSS MEMBERS SHALL HAVE 1/4" CAP PLATES AT ENDS. H. J. K. REFER TO ARCHITECTURAL DRAWINGS FOR OVERALL BUILDING GEOMETRY, WALL LOCATIONS, STAIR GEOMETRY AND ADDITIONAL PARTITION WALL REQUIREMENTS. REFER TO ARCHITECTURAL DRAWINGS FOR NON-LOAD BEARING PARTITION WALLS. REFER TO SHEETS S0.1, S0.2, S2.1, S2.2, AND S9.2 TYPICAL DETAILS FOR REINFORCING, THICKENED SLABS AND OTHER REQUIREMENTS. N. PROVIDE HSS3 1/2x2 1/2x1/4 (LLH) BETWEEN ALL JOIST WITH 2 1/2" SEATS TO SUPPORT ROOF DECK WHERE DECK SWITCHES DIRECTION. (RE: 44/S6.1) P. ALL EXTERIOR EXPOSED STEEL SHALL BE GALVANIZED. Q. REFER TO TYPICAL DETAILS 11/S6.2 AND 12/S6.2 FOR FRAMING REQUIRED AT MECHANICAL UNIT CURBS. 1 1 1/2" DEEP, 20 GAGE, GALVANIZED WIDE RIB STEEL ROOF DECK. PROVIDE 5/8" DIAMETER PUBBLE WELDS IN 36/5 PATTERN AND 2 SIDELAPS PER SPAN. 2 3 1/2" DEEP, 20 GAGE, EPICORE ER3.5A OR EQUAL ACCOUSTICAL PAINTED ROOF DECK. PROVIDE 1/2" ARC SPOT WELDS IN 24/3 PATTERN AND 1/2" ARC SEAM WELDS OR 2" FILLET WELDS @ 18"OC AT SIDELAPS PER SPAN. 3 C D F K E 2" DEEP, 20 GAGE, EPICORE ER2A OR EQUAL ACCOUSTICAL PAINTED ROOF DECK. PROVIDE 1/2" ARC SPOT WELDS IN 24/3 PATTERN AND 1/2" ARC SEAM WELDS OR 2" FILLET WELDS @ 18"OC AT SIDELAPS PER SPAN. G L ALL OPENINGS IN CMU WALLS (PARTITION AND LOAD BEARING) REQUIRE A LINTEL. REFER TO SHEET S9.2 FOR TYPICAL MASONRY LINTEL DETAILS AND SCHEDULES. H ROOF LEVEL FRAMING PLAN - AREA L J SCALE: 1/8" = 1'-0" BENJAMIN TALPOS 10/8/2012 6:16:22 PM C:\Users\BrionP\Documents\9-2013-Revit Projects\Joplin\13-12102-00_central_struct_2012.rvt A NORTH NORTH © 2012, DLR Group of Missouri inc., a Missouri corporation CA No. 001614, ALL RIGHTS RESERVED. KEY PLAN 10'-0" MIN WALL WIDTH WATERSTOP, TYP CUT EVERY OTHER WIRE/REINF BAR AT CONTROL JOINT 1/4" WIDE x1/2" DEEP GROOVE WITH SEALANT @ EXPOSED FL 1/2" DIA x3'-0" SMOOTH DWL W/ GREASED ONE END CENTERED ON JOINT @ 1'-6"OC. PLACE PERPENDICULAR TO SLAB JOINT JT SAWCUT JT A CONTROL (CONTRACTION) JOINT (CJ) 1 1/2 FTG WIDTH C CONSTRUCTION JOINT (CONST JT) 3/8" WIDE x1/2" DEEP GROOVE W/ SEALANT @ EXPOSED FL 1 COLUMN 3/8" WIDE x1/2" DEEP GROOVE WITH SEALANT @ EXPOSED FL BOTTOM OF EXCAVATION SHALL NOT EXTEND BELOW THIS LINE 2' - 0" MIN EXCEPT 5'-0" @ RETAINING WALLS 0' - 8" #4 @ 12"OC EA WAY NOTE: 1. THE CONTRACTOR SHALL BE RESPONSIBLE FOR SHORING, SHEATHING, OR OTHERWISE MAINTAINING THE SIDES OF THE EXCAVATION FROM CAVE-IN AND OTHER HAZARDS UNTIL ALL BACKFILL IS COMPLETED. BACKFILL AS PER SPECIFICATIONS. TYP ELEVATOR SUMP PIT DETAIL 12 SCALE: 1/2" = 1'-0" S2.1 TYP ELEVATOR SILL DETAIL SCALE: 3/4" = 1'-0" 3/8" EXP JT FILLER S2.1 B TYP SLAB-ON-GRADE JOINTS BEDDING PER SPECIFICATIONS 2 TYP INSTALLATION OF PIPES 13 1 SCALE: 3/4" = 1'-0" D ISOLATION JOINT @ COL TYP SLAB-ON-GRADE JOINTS 15 3/8" IJ SCALE: 3/4" = 1'-0" S2.1 REINF TO MATCH SLAB REINF WALL WIDTH CONC FTG TOP FOOTING REINFORCING (WHERE REQUIRED) 'D1' HOOK BARS AT DISCONTIUOUS ENDS, TYP 48 BAR DIA FTG DEPTH CONCRETE FOOTING FTG LAP DWLS TO MATCH FTG REINF, TYP 2 'D1' CONC FTG FOR FTG EL, DEPTH, AND REINF, SEE PLANS AND TYP FTG DET. TYP FTG REINF DETAIL S2.1 32 SCALE: 3/4" = 1'-0" S2.1 TYP BOT STEP FTG DETAIL SCALE: 3/4" = 1'-0" S2.1 1" 2" EXTER STD HOOK CORNER BAG CONC WALL CORNER BAR CONC WALL CONC WALL 1' - 0" NOTE: 1' - 0" FTG WIDTH PROVIDE SLEEVE 2" (NOMINAL) LARGER THAN PIPE O.D. NOTE: 1. FOR PIPES 3'-0" OR LESS BELOW FOOTING, PROVIDE SLEEVE AS SHOWN. 2. FOR PIPES AND CONDUITS MORE THAN 3'-0" BELOW FOOTING, PIPE SLEEVE MAY BE ELIMINATED. 3. COORDINATE WITH MECHANICAL, ELECTRICAL, AND ALL OTHER EFFECTED TRADES. SCALE: 1/2" = 1'-0" INTERSECTION BARS TO BE SAME SIZE AND SPACING AS THE HORIZONTAL BARS. NOTE: PIPE OR CONDUIT PERPENDICULAR TO FTG TYP BOTTOM STEP FOOTING DETAIL 33 CONST JOINT INTERSECTION BAR A DOUBLE LAYER PROVIDE TWO EQUAL STEPS IF D2 IS GREATER THAN TWO TIMES D1, OTHERWISE PROVIDE ONE STEP. 31 STD HOOK FOR PIPES IN THIS AREA, LOWER BOTTOM OF FOOTING TO ALLOW PIPE TO EXTEND THRU FOOTING FOOTING REINFORCING NOTE: FOR FOOTING ELEVATIONS, DEPTH AND REINFORCING, SEE PLANS AND TYPICAL FOOTING DETAIL. NOTE: REQD SPLICE 3'-0 MIN CONC FTG 0' - 6" `D2' 'D2' OPTIONAL CONST JT AREA OK FOR PIPE SLEEVE . OPTIONAL CONST JT ° 60 60 DEG SCALE: 3/4" = 1'-0" REQD SPLICE PIPE OR CONDUIT PERPENDICULAR TO FTG FOOTING LAP SEE SCHEDULE S2.1 TYP CONC WALL JOINT DETAIL PROVIDE SLEEVE 2" (NOMINAL) LARGER THAN PIPE OD TOF EL SEE PLANS 48 BAR DIAMETER 26 SCALE: 3/4" = 1'-0" FOR PIPES INT THIS AREA. LOWER ENTIRE FOOTING TO ALLOW PIPE TO EXTEND THRU WALL 0' - 6" TOF EL SEE PLANS `D1' FTG REINF TYP SLAB-ON-GRADE DETAIL 25 S2.1 35 S2.1 B SINGLE LAYER CORNER BARS TO BE SAME SIZE AND SPACING AS THE HORIZONTAL BARS. A DOUBLE LAYER TYP INTERSECTION REINF DETAIL 36 SCALE: 3/4" = 1'-0" S2.1 B SINGLE LAYER TYP WALL REINF DETAIL SCALE: 3/4" = 1'-0" CONCRETE FOOTING TYP FTG PENETRATION DETAIL 42 SCALE: 1/2" = 1'-0" S2.1 MIN EMBED CMU SIZE W #4 5" 8" CMU 1'-0" #5 6" 12" CMU 2'-0" #6 7" #7 8" CL NOTE 1 4-3/4" DIA x 1'-3" HEADED ANCHOR BOLTS UNO 2 4 SIDES 3/16 PL WASHER 5/16"x2 1/2"x2 1/2" W/ 13/16" DIA HOLES 1 1/2 1 1/2" NON-SHRINK GROUT 0' - 2" MIN 0'-4" MAX, TYP SLAB PER PLAN 2 SHIM PACK AS REQ'D PER SCHED 0' - 3" CLR FTG PER PLAN & SCHED 0' - 3" CLR 51 S2.1 TYP SPREAD FTG DET SCALE: 3/4" = 1'-0" 52 S2.1 TYP STEP FOOTING DETAIL 43 1 REMARKS COLUMN & FOOTING SCHEDULE SCALE: 3/4" = 1'-0" #4 @ 12"OC, CONT SCALE: 3/4" = 1'-0" 44 S2.1 TYP FLOOR SLAB STEP DETAIL SCALE: 1 1/2" = 1'-0" COLUMN SCHEDULE NOTES: 1. WELD SIZE SHALL BE 1/16" LESS THAN MINIMUM MEMBER THICKNESS JOINED TYPICAL, UNLESS NOTED OTHERWISE. SEE COLUMN SCHEDULE FOR OTHER INFORMATION. BENJAMIN TALPOS 10/8/2012 6:16:31 PM 0' - 5 1/2" PROJ UNO TOF SEE PLANS 31 40 46 60 24 31 36 46 #6 A B 37 48 55 72 28 37 43 55 #7 A B 54 70 81 105 42 54 62 81 #8 A B 62 80 92 120 47 62 71 92 #9 A B 70 90 104 136 54 70 80 104 #10 A B 78 102 117 153 60 78 90 117 #11 A B 87 113 130 170 67 87 100 130 1 1 1 MARK CC1 CC2 CC3 CC4 CC5 CC6 CC7 CC8 CC9 CC10 CC11 CC12 CC13 CC14 CC15 CC16 CC17 CC18 CC19 CC20 CC21 CC22 CC23 CC24 CC25 CC26 SIZE HSS6x6x5/8 HSS6x6x3/8 HSS6x6x5/16 HSS6x6x5/16 HSS8x8x1/2 HSS10x10x1/2 HSS10x10x5/8 HSS12x12x1/2 HSS12x12x5/8 HSS16x16x5/8 W8x28 W14x68 W14x74 W14x82 W14x38 W14x82 W14x74 W14x82 W14x90 HSS4x4x1/4 HSS6x6x5/16 W14x68 W14x74 W14x82 W14x82 HSS4x4x1/4 BASE PLATE SIZE 3/4"x8"x1'-2" 3/4"x14"x1'-2" 3/4"x14"x1'-2" 3/4"x14"x1'-2" 3/4"x16"x1'-4" 3/4"x18"x1'-6" 3/4"x18"x1'-6" 3/4"x20"x1'-8" 3/4"x20"x1'-8" 3/4"x24"x2'-0" 3/4"x16"x1'-4" 3/4"x18"x1'-10" 3/4"x18"x1'-10" 3/4"x18"x1'-10" 3/4"x18"x1'-10" 3/4"x16"x1'-4" 3/4"x12"x1'-6" 3/4"x12"x1'-6" 3/4"x18"x1'-10" 3/4"x6"x0'-8" BASE PLATE LAYOUT TYPE BP-6 BP-1 BP-1 BP-5 BP-1 BP-1 BP-1 BP-1 BP-1 BP-1 BP-4 BP-4 BP-4 BP-4 BP-5 BP-5 BP-5 BP-5 BP-4 BP-2 ANCHOR BOLTS (4) 3/4"DIA A325 BOLTS (4) 3/4"DIA x1'-3" (4) 3/4"DIA x1'-3" (4) 3/4"DIA x1'-3" (4) 3/4"DIA x1'-3" (4) 3/4"DIA x1'-3" (4) 3/4"DIA x1'-3" (4) 3/4"DIA x1'-3" (4) 3/4"DIA x1'-3" (4) 3/4"DIA x1'-3" (4) 3/4"DIA x1'-3" (4) 3/4"DIA x1'-3" (4) 3/4"DIA x1'-3" (4) 3/4"DIA x1'-3" (4) 3/4"DIA A325 BOLTS (4) 3/4"DIA x1'-3" (4) 3/4"DIA x1'-3" (4) 3/4"DIA x1'-3" (4) 3/4"DIA x1'-3" (4) 3/4"DIA x 1'-3" RE: SECTION 11/S5.3 RE: SECTION 24/S5.3 RE: SECTION 24/S5.3 RE: SECTION 24/S5.3 RE: SECTION 23/S5.3 3/4"x12"x1'-0" BP-1 (4) 3/4"DIA x 1'-3" 45 S2.1 4. 5. 6. 7. BEAMS OR CASE 1 COVER AT LEAST 1db AND c-c SPACING AT LEAST 2db COLUMNS CASE 2 COVER LESS THAN 1db AND c-c SPACING LESS THAN 2db ALL OTHERS CASE 1 COVER AT LEAST 1db AND c-c SPACING AT LEAST 3db CASE 2 COVER LESS THAN 1db AND c-c SPACING LESS THAN 3db LAP CLASS A VALUES ARE THE REQUIRED TENSION DEVELOPMENT LENGTH, ld; LAP SPLICE LENGTHS ARE MULTIPLES OF TENSION DEVELOPMENT LENGTHS. CLASS A = 1.0 ld AND CLASS B = 1.3 ld ACI 138-02, SECTION 12.15.1. TOP BARS ARE HORIZONTAL BARS WITH MORE THAN 12 INCHES OF CONCRETE CAST BELOW THE BARS. FOR LIGHTWEIGHT AGGREGATE CONCRETE, MULTIPLY THE TABULATED VALUES BY 1.3; OR WHEN fct IS SPECIFIED, THE FACTOR IS 6.7 √fc/fct ≥1.0. FOR EPOXY COATED BARS, MULTIPLY THE TABULATED VALUES BY ONE OF THE FOLLOWING FACTORS: CONCRETE COVER AND SPACING TOP BARS OTHER BARS COVER < 3db OR c-c SPACING < 7db 1.7/1.3=1.31 1.50 1.20 1.20 COVER ≥ 3db AND c-c SPACING ≥ 7db CONCRETE REINFORCING LAP SPLICE SCHEDULE SCALE: 3/4" = 1'-0" DETAILING DIMENSION DEVELOPMENT LENGTHS OF STANDARD HOOKS IN TENSION , GRADE 60 REINFORCEMENT IN NORMAL WEIGHT CONCRETE REMARKS NOTES: 1. ANCHOR BOLT LENGTH INCLUDES 5" PROJECTION, UNLESS NOTED OTHERWISE. 2. REFER TO GENERAL STRUCTURAL NOTES AND SPECIFICATIONS FOR ANCHOR BOLT TYPE. 3. PROVIDE AISC STANDARD PLATE WASHERS FOR ALL ANCHOR BOLTS. 4. REFERENCE DETAIL 52/S3.1 FOR BASE PLATE LAYOUT TYPES. 5. ALL EXTERIOR EXPOSED COLUMNS, BASE PLATES, AND ANCHOR BOLTS SHALL BE GALVANIZED. 6. ALL ANCHOR BOLTS SHALL BE ASTM F1554 GRADE 55, WELDABLE, UNLESS NOTED OTHERWISE. F'c = 3,000 F'c = 4,000 F'c = 5,000 F'c = 7,000 Lhb 0.7Lhb #3 8 6 7 6 6 6 6 6 6 6 6 6 #4 11 8 9 7 8 6 8 6 7 6 7 6 #5 14 10 12 8 11 7 10 7 9 6 8 6 #6 16 12 14 10 13 9 12 8 11 8 10 7 #7 19 13 17 12 15 10 14 9 13 9 12 8 #8 22 15 19 13 17 15 11 14 10 13 9 #9 25 17 21 15 19 13 17 12 16 11 15 11 #10 28 19 24 17 22 15 20 14 18 13 17 12 0.7Lhb Lhb 12 0.7Lhb Lhb 0.7Lhb Lhb 0.7Lhb #11 31 22 27 19 24 17 22 15 20 14 19 13 #14 37 NA 32 NA 29 NA 26 NA 24 NA 23 NA #18 49 NA 43 180° HOOK NA 38 NA 35 NA 32 NA 30 90° HOOK NA Ldh OUTSIDE FACE OF BAR Ldh 4db OR 2 1/2" MIN S2.1 180° HOOK RECOMMENDED END HOOKS, ALL GRADES OUTSIDE FACE OF BAR DEVELOP LENGTHS OF STD HOOKS SCALE: 3/4" = 1'-0" D = INSIDE DIAMETER OF BEND 90° HOOK NOTES: 1. Ldh = DEVELOPMENT LENGTH OF STANDARD HOOKS IN TENSION (INCHES). 2. Ldh = Lhd UNLESS CONDITIONS OF ITEM 3 ARE SATISFIED. 3. Ldh = 0.7 Lhd FOR #11 BARS AND SMALLER WHEN SIDE COVER (NORMAL TO PLANE OF HOOK) IS NOT LESS THAN 2 1/2" AND FOR 90° HOOKS, COVER ON BAR EXTENSION BEYOND HOOK IS NOT LESS THAN 2". 4. HOOKS ARE NOT CONSIDERED EFFECTIVE FOR DEVELOPING BARS IN COMPRESSION. 5. Ldh SHALL BE MULTIPLIED BY 1.2 FOR EPOXY-COATED HOOKED BARS. 55 HOOK A OR G F'c = 8,000 BAR SIZE Lhb 0.7Lhb Lhb F'c = 6,000 DETAILING DIMENSION D C:\Users\BrionP\Documents\9-2013-Revit Projects\Joplin\13-12102-00_central_struct_2012.rvt COAT STEEL BELOW GRADE W/ COLD-APPLIED ASPHALT EMULSION PER ASTM D1187 REINFORCEMENT 4 #5 EW T&B 6 #5 EW T&B 7 #5 EW T&B 6 #6 EW T&B 7 #6 EW T&B 8 #6 EW T&B 9 #6 EW T&B 11 #6 EW T&B 14 #6 EW T&B 4 #5 EW T&B 6 #5 EW T&B 7 #5 EW T&B 6 #6 EW T&B 11 #6 EW T&B 8 #6 EW T&B 9 #6 EW T&B 11 #6 EW T&B 14 #6 EW T&B 21 #6 EW T&B 14 #6 EW T&B #6 @ 8"OC EW T&B 0' - 6" NOTE: FOR FOOTING ELEVATION DEPTH, AND REINFORCING, SEE PLANS AND TYP FOOTING DETAIL. S2.1 SIZE 3'-0" x 3'-0" 4'-0" x 4'-0" 5'-0" x 5'-0" 6'-0" x 6'-0" 7'-0" x 7'-0" 8'-0" x 8'-0" 9'-0" x 9'-0" 10'-0" x 10'-0" 11'-0" x 11'-0" 3'-0" x 3'-0" 4'-0" x 4'-0" 5'-0" x 5'-0" 6'-0" x 6'-0" 7'-0" x 7'-0" 8'-0" x 8'-0" 9'-0" x 9'-0" 10'-0" x 10'-0" 11'-0" x 11'-0" 12'-0" x 12'-0" 9'-0" x 9'-0" 10'-2" x 6'-2" A B 2'-6" MAX `H' BAR SIZE SCALE: 3/4" = 1'-0" DEPTH 1'-6" 1'-6" 1'-6" 1'-6" 1'-6" 1'-6" 1'-6" 1'-6" 1'-6" 2'-6" 2'-6" 2'-6" 2'-6" 2'-6" 2'-6" 2'-6" 2'-6" 2'-6" 1'-6" 2'-0" 1'-6" #5 2 FOOTING LAP SEE SCHEDULE TYP CMU PARTITION WALL BASE MARK FF1 FF2 FF3 FF4 FF5 FF6 FF7 FF8 FF9 FF10 FF11 FF12 FF13 FF14 FF15 FF16 FF17 FF18 FF19 FF20 FF21 28 37 1 SPREAD FOOTING SCHEDULE STL COL & BASE PL PER PLAN & SCHED (PROVIDE 1-5/16" DIA HOLES IN BASE PLATE) 19 25 'D' 1' - 0" SEE SCHED NOTE: AT CONTRACTORS OPTIONS, DOWELS MAY BE EPOXIED INTO THICKENED SLAB PER SCHEDULE IN LIEU OF HOOKED DOWELS. 37 48 S2.1 W 25 32 D NO EXCAVATION FOR PIPE TRENCH PARALLEL TO FOOTING BELOW THIS LINE. STEP FOOTING AS REQUIRED BY THESE CONDITIONS. 1' - 0" A B FOOTING REINFORCING `D' 0' - 3 1/2" CLR 3'-0" MIN 6" MIN LEAN CONCRETE S2.1 2-#5 CONT f'c=4000 PSI LAP TOP BARS OTHER BARS CLAS CASE 1 CASE 2 CASE 1 CASE 2 S A 18 28 14 21 B 24 36 18 28 #4 2'-0" ° 60 OPTIONAL JOINT 41 SOLID GROUT CELLS AT REINFORCEMENT NOTES: 1. TABULATED VALUES ARE BASED ON GRADE 60 REINFORCING BARS AND NORMAL-WEIGHT CONCRETE. 2. TENSION DEVELOPMENT LENGTHS AND TENSION LAP SPLICE LENGTHS ARE BASED ON ACI 318-02, SECTIONS 12.2.2 AND 12.15, RESPECTIVELY. TABULATED VALUES FOR BEAMS OR COLUMNS ARE BASED ON TRANSVERSE REINFORCEMENT AND CONCRETE COVER MEETING THE MINIUM CODE REQUIREMENTS. LENGTHS ARE IN INCHES. 3. CASES 1 AND 2, WHICH DEPEND ON THE TYPE OF STRUCTURAL ELEMENT, CONCRETE COVER, AND THE CENTER-TO-CENTER SPACING OF THE BARS, ARE DEFINED AS: J REQ'D SPLICE 1' - 6" MIN 6" MIN 1 BAR SIZ E #3 #4 @ 12"OC 2'-0" 0' - 8" 2 SCALE: 3/4" = 1'-0" S2.1 DOWELS TO MATCH VERT WALL REINF ALTERNATE HOOK 1' - 0" IF PIPES ARE LOCATED IN THIS HEIGHT, THEN LOWER FOOTING ACI TENSION LAP SPLICE LENGTHS (IN) FOR f'c = 4,000 PSI TOF EL SEE PLANS CMU PIPE TO CLEAR SLEEVE BY 2" (TYP) TYP INSTALLATION OF PIPES 34 db FOOTING REINFORCING 12 db 2 `H' MINIMUM A OR G VERT MAS WALL REINF SEE PLANS AND STRUCTURAL NOTES. db EXCAVATION 56 S2.1 BAR SIZE FINISHED BEND DIAMETER (D)(IN) 180° HOOKS A OR G (IN) J (IN) A OR G (IN) #3 2 1/4 5 3 6 #4 3 6 4 8 #5 3 3/4 7 5 10 #6 4 1/2 8 6 12 #7 5 1/4 10 7 14 #8 6 11 8 16 #9 9 1/2 15 11 3/4 19 #10 10 3/4 17 13 1/4 22 #11 12 19 14 3/4 24 #14 18 1/4 27 21 3/4 31 #18 24 36 28 1/2 41 END HOOK TYPES SCALE: 3/4" = 1'-0" 90° HOOKS © 2012, DLR Group of Missouri inc., a Missouri corporation CA No. 001614, ALL RIGHTS RESERVED. SCALE: 3/4" = 1'-0" S2.1 JOPLIN, JASPER COUNTY, MISSOURI TYP INTEGRAL HOUSEKEEPING PAD 24 SCALE: 3/4" = 1'-0" 2 10-08-12 ADD #3 S2.1 7290 West 133rd Street Overland Park, Kansas 66213 tel: (913)897-7811 THICKENED SLAB DETAIL 23 SCALE: 3/4" = 1'-0" Architecture Engineering Planning Interiors S2.1 JOPLIN HIGH SCHOOL SCALE: 3/4" = 1'-0" TYP FLOOR SLAB RECESS NOTE: JOINTS SPACING SHALL NOT EXCEED THE SMALLER OF 25 FEET OR 3 TIMES THE WALL HEIGHT. Revisions S2.1 22 2' - 0" B WALL CONST JT 1 10-04-12 ADD #2 TYP SLAB-ON-GRADE A WALL CONTROL JT NOTE: FOLLOW GEOTECHNICAL ENGINEER'S RECOMMENDATIONS FOR PREPARATION OF SUBGRADE 3-#5 CONT REQD SPLICE NOTE: SEE ARCH FOR LOCATION OF RECESSED SLABS STOP ALTERNATE HORIZONTAL BARS AT JOINT. SEE ARCH FOR CJ LOCATIONS. (NOT APPLICABLE AT SHEAR WALLS) NOTE: VERIFY SIZE AND LOCATION WITH MECH OR ELECT CONTRACTOR 0' - 3" CLR A DISCONTINUOUS JT INTERSECTION NOTE: 13-12102-00 09/10/12 1' - 0" T 2-#4x2'-0" 2" BELOW SURFACE ROUGHENED SURFACE (1/4" AMPLITUDE) WATERSTOP REQD SPLICE 2" 2" 1 2 CONC WALL REQD SPLICE SLAB PER PLAN T 8" MAX CONST JT 0' - 4" 0' - 3" RE: PLAN 1 1/2" INTER CONN BY STAIR SUPPLIER SLAB-ON-GRADE (RE: SPECS) 2'-0" ENGINEERED FILL 0' - 4" #3 W/ STD HOOK EA END @ 12"OC AROUND PERIMETER #4 @ 12"OC 2'-0" A INTERNAL CORNER SLAB THICKNESS (RE: PLAN) 3/4" CHAMFER STEEL STAIR STRINGER FOUNDATION TYPICAL DETAILS 2" SLAB EDGE SEALANT W/ BACKER ROD 3/4" GRANULAR FILL CAPILLARY BREAK PER PLAN REQD SPLICE 2" 2-#4x2'-0" 2" BELOW SURFACE VAPOR BARRIER (RE: SPECS) 21 NOTES: 1. CONTROL JOINTS SHALL BE SPACED AT INTERVALS < 20'-0" OC IN EACH DIRECTION. 2. CONSTRUCTION JOINTS SHALL BE SPACED AT INTERVALS < 60 FEET IN EACH DIRECTION. 3. CONTRACTOR SHALL COORDINATE JOINT SPACING WITH ARCHITECTURAL REQUIREMENTS AS APPLICABLE. SUBMIT JOINT LAYOUT FOR ARCHITECT / ENGINEER'S REVIEW. 4. JOINT LAYOUT SHOULD BE RELATIVELY SQUARE WHENEVER POSSIBLE. LENGTH / WIDTH ASPECT RATIO SHALL BE LESS THAN 2:1. FACE OF WALL OR COL 3" CL R 1' - 6" 0' - 8" S2.1 JT FILLER & SEALANT @ EXPOSED FL DISCONTINUE WWR AT CONSTRUCTION JOINT TRENCH EXCAVATION SUMP PIT 2'-0" SQx 2'-0" DEEP (BEYOND) 11 GROUND LINE ELEVATOR SILL ANGLE AND FASTENERS PER ELEVATOR MANUFACTURER SLOPE TO DRAIN 1/4" @ EXPOSED FLOOR 1/8" ELSEWHERE 2 0' - 0 1/2" SYMETRICAL ABOUT THE CL BP-1 11 S2.2 3/4 SYMETRICAL ABOUT THE CL WIDE FLANGE COL BP-2 SYMETRICAL ABOUT THE CL 1/4 0' - 0 1/2" WIDE FLANGE COL 0' - 1 3/8". BP-4 BP-5 PIER SCHEDULE 1/4 0' - 1 3/8". BP-6 0' - 6" REMARKS RE: 53/S2.3 RE: 53/S2.3 PIER MARK TOP OF PIER ELEVATION BOTTOM OF PIER ELEVATION (ESTIMATE, FOR BIDDING PURPOSES ONLY) BP-7 DRAIN PER MEP COLUMN BASE PLATE DETAIL 15 SCALE: 3/4" = 1'-0" S2.2 PIER SCHEDULE (SOCKETED) 16 SCALE: 3/4" = 1'-0" S2.2 #4 @ 12" OC WITH 2'-0" LONG EXTENSIONS 2 1 PER PLAN PLAN MARK DIAMETER SHAFT STEEL SHAFT TIES PP1 36" 12-#11 #4 @ 9"OC PP2 30" 12-#7 #4 @ 14"OC * THESE PIERS ARE TO BE SOCKETED INTO FOOTING 3") PLAN MARK KEY: PPx XXX'-X" XXX'-X" PER PLAN MIN CL PER 1' - 0" SYMETRICAL ABOUT THE CL 0' - 4" HSS ROUND OR RECTANGULAR COL SEE SCHED CL 1 ANCHOR RODS PER SCHED IN OVS HOLES 0' - 4" SEE SCHED ANCHOR RODS PER SCHED IN OVS HOLES HSS ROUND OR RECTANGULAR COL 5/16 SYMETRICAL ABOUT THE CL SYMETRICAL ABOUT THE CL BP-3 0' - 2 1/2" 5/16 SEE SCHED 0' - 2" TYP 1' - 2" 1/4 ANCHOR RODS PER SCHED IN OVS HOLES CL NOTE: VERIFY ALL PLAN DIMENSIONS, TRENCH DIMENSIONS, AND LOCATIONS WITH ARCHITECTURAL AND WASHER/DRYER MANUFACTURER PRIOR TO CONSTRUCTION. 0' - 2" TYP 1/4 CL 0' - 1 3/8". TYP BASE PL 0' - 2" TYP 0' - 2" TYP SYMETRICAL ABOUT THE CL CL 0' - 2 1/2" ANCHOR RODS PER SCHED IN OVS HOLES WIDE FLANGE COL SEE SCHED SEE SCHED SLAB PER PLAN ISOLATION JT W/ COMPRESSIBLE FILLER ALL AROUND WASHER PAD EXT OF BUILDING BASE PL SEE SCHED CL 0' - 2 1/2" 0' - 2" TYP CL BASE PL SEE SCHED ANCHOR RODS PER SCHED IN OVS HOLES SEE SCHED HSS ROUND OR RECTANGULAR COL SEE SCHED 0' - 2" TYP CL ANCHOR RODS PER SCHED IN OVS HOLES 0' - 2" ANCHOR RODS PER SCHED IN OVS HOLES BASE PL 0' - 2" 0' - 2" 0' - 2" TYP SEE SCHED 0' - 2" TYP HSS ROUND OR RECTANGULAR COL 0' - 2" CL BASE PL SEE SCHED SEE SCHED 0' - 4 1/2" SEE SCHED CL 0' - 2 1/2" BASE PL CL 0' - 4 1/2" BASE PL CL EXT OF BUILDING SEE SCHED CL 0' - 2" TYP CL #5 @ 12"OC EA WAY, TOP & BOT TYPICAL WASHER PAD SCALE: 3/4" = 1'-0" TRENCH DRAIN FRAME AND GRATING PER SPECIFICATIONS 3/4" CHAMFER 6" 4" SLOPE 20"x20" CONC PILASTER REINF W/ 16 #9 VERTS AND #4 TIES @ 9" OC (6 TIES @ 3" OC AT TOP) 6" 10". SCALE: 1 1/2" = 1'-0" 25 S2.2 TRENCH DRAIN DETAIL SCALE: 1 1/2" = 1'-0" BENJAMIN TALPOS 10/8/2012 6:16:35 PM C:\Users\BrionP\Documents\9-2013-Revit Projects\Joplin\13-12102-00_central_struct_2012.rvt 2 10-08-12 ADD #3 SEE PLANS FOR ACTUAL ORIENTATION AND DIMENSIONS NOT SHOWN. POUR PILASTERS MONOLITHIC WITH WALL, UNLESS OTHERWISE NOTED. TOP OF PILASTER IS ALWAYS 8" BELOW FINISHED FLOOR ELEVATION. COORDINATE WITH STEEL SUPPLIER ALL ANCHOR BOLTS, BEAM EMBED PLATES, AND OTHER CONNECTIONS AROUND PILASTER. 7290 West 133rd Street Overland Park, Kansas 66213 tel: (913)897-7811 36"x16" PILASTER @ 12" CMU WALL 1. 2. 3. 4. Architecture Engineering Planning Interiors #8 TIES @ 8"OC NOTES: © 2012, DLR Group of Missouri inc., a Missouri corporation CA No. 001614, ALL RIGHTS RESERVED. S2.2 TYP ISOLATED EQUIPMENT PAD DETAIL JOPLIN, JASPER COUNTY, MISSOURI 24 JOPLIN HIGH SCHOOL SCALE: 3/4" = 1'-0" 10". S2.2 S2.2 NOTE: SEE MECHANICAL FOR DRAIN LINE Revisions #8 TIES @ 8"OC TYPICAL PILASTER DETAILS 10" 1 10-04-12 ADD #2 31 6" 13-12102-00 09/10/12 2-#6 VERT EA CELL IN SOLID GROUT (6 CELLS THUS) #8 TIES @ 8"OC 24"x16" PILASTER @ 12" CMU WALL 8" D 2-#6 VERT EA CELL IN SOLID GROUT (4 CELLS THUS) #8 TIES @ 8"OC 24"x16" PILASTER @ 8" CMU WALL 10". CONTINUE TYP WALL REINF, EF THROUGH PILASTER C 1-#6 VERT EA CELL IN SOLID GROUT (6 CELLS THUS) 6" 10". SECTIONS PER PLAN B 10" NOTE: VERIFY SIZE AND LOCATION WITH MECHANICAL OR ELECTRICAL CONTRACTOR CONTINUE TYP WALL REINF, EF THROUGH PILASTER A 16"x16" PILASTER @ 8" CMU WALL ISOLATION JOINT SEE TYPICAL DETAIL FOUNDATION TYPICAL DETAILS 10". SEE WALL CONTINUE TYP WALL REINF, EF THROUGH PILASTER 1-#6 VERT EA CELL IN SOLID GROUT (4 CELLS THUS) 2 - #4 1'-10". PER PLAN SECTIONS SEE WALL 10". 3" CLR 10". 20"x20" CONC PILASTER REINF W/ 16 #9 VERTS AND #4 TIES @ 9" OC (6 TIES @ 3" OC AT TOP) #4 @ 12" OC EACH WAY 10". 10". 20"x20" CONC PILASTER REINF W/ 16 #9 VERTS AND #4 TIES @ 9" OC (6 TIES @ 3" OC AT TOP) 10". 8" MIN. 10". SECTIONS 20"x32" CONC PILASTER POURED MONOLITHIC W/ WALL REINF W/ 20 #9 VERTS AND #4 TIES @ 9" OC (6 TIES @ 3" OC AT TOP) 1" CLR 10". 4" UNO SEE WALL PER PLAN WINDOW PER ARCH HSS PER PLAN MTL STUDS INFILL PER ARCH S5.3 HSS POST PER PLAN W/ 1/4" CAP PL BASE PL L4x4x1/4x0'-4" LONG CLIP EXT PER ARCH 2 SLAB PER PLAN GROUT SOLID BELOW GRADE 1' - 4" 2' - 6" 0' - 8" #4 SUPPORT TIES @ 16" OC #6 @ 12"OC, EA FACE INSUL PER ARCH SLAB PER PLAN 4" 13 SLAB PER PLAN S3.4 SCALE: 3/4" = 1'-0" 16 HSS POST PER PLAN W/ 1/4" CAP PL L4x4x1/4x0'-4" LONG CLIP S3.4 EXT PER ARCH 1-#4 CONT SECTION GROUT SOLID BELOW GRADE SCALE: 3/4" = 1'-0" #4x5'-0" @ 48"OC FIELD BEND 2'-6" INTO SLAB 4" 0' - 8" #4 @ 12"OC, EA FACE INSUL PER ARCH #6 @ 12"OC, EA FACE HSS POST PER PLAN W/ 1/4" CAP PL L4x4x1/4x0'-4" LONG CLIP 1' - 4" 3-#6 TOP & BOT PER PLAN MTL STUDS PER ARCH SCALE: 3/4" = 1'-0" GROUT SOLID BELOW GRADE EXT PER ARCH #4x5'-0" @ 48"OC FIELD BEND 2'-6" INTO SLAB 4" S3.4 SECTION 26 SCALE: 3/4" = 1'-0" S3.4 4" HSS PER PLAN #4 @ 12"OC, EA FACE #6 @ 12"OC, EA FACE 1' - 4" 1' - 4" DWLS TO MATCH VERT WALL REINF #4 SUPPORT TIES @ 16" OC HSS PER PLAN 3-#6 TOP & BOT DWLS TO MATCH VERT WALL REINF #4 SUPPORT TIES @ 16" OC 1' - 6" WINDOW PER ARCH #6 @ 12"OC, EA FACE 3-#6 TOP & BOT 1' - 0" EXP JT VARIES #6 @ 12"OC EA FACE PER PLAN MTL STUDS PER ARCH 1-#4 CONT 34 SCALE: 3/4" = 1'-0" S3.4 (3) #4 @ 6"OC, EA FACE @ BOT OF WALL SECTION SCALE: 3/4" = 1'-0" DWLS TO MATCH WALL VERTS S3.4 SECTION SCALE: 3/4" = 1'-0" 8" Revisions 2 2' - 0" #5 @ 12"OC, EA WAY 8" MIN 3" 0' - 8" SLAB PER CIVIL #4 SUPPORT TIES @ 12" OC PIER PER PLAN NOTE: THIS FOUNDATION IS A GRADE BEAM. REFER TO TYPICAL GRADE BEAM DETAILS FOR LAP & SPLICE INFORMATION. 8". 8". #3 SUPPORT TIES @ 16" OC PER PLAN PER PLAN 53 S3.4 SECTION SCALE: 3/4" = 1'-0" #4 SUPPORT TIES @ 16" OC 1' - 6" 2' - 6" #5 @ 12"OC EA FACE 3-#6 TOP & BOT PER PLAN 3-#6 TOP & BOT 54 S3.4 SECTION SCALE: 3/4" = 1'-0" PER PLAN 56 S3.4 SECTION SCALE: 3/4" = 1'-0" © 2012, DLR Group of Missouri inc., a Missouri corporation CA No. 001614, ALL RIGHTS RESERVED. 6" 1' - 6" PER ARCH TYP #5 DWLS @ 12"OC 5-#6 TOP & BOT PER PLAN SCALE: 3/4" = 1'-0" SCALE: 3/4" = 1'-0" SLAB PER CIVIL MIN 8'-0" MAX. REQ'D SPLICE 0' - 4" 3-#6 TOP & BOT S3.4 S3.4 SECTION 2' - 0" SLAB PER CIVIL #4 SUPPORT TIES @ 16" OC SECTION PER PLAN 46 SLAB PER PLAN 2 10-08-12 ADD #3 2 4-#11 EA FACE CONT GROUT SOLID ALL CELLS BELOW GRADE 52 PER PLAN COMPRESSIBLE FILLER DWLS TO MATCH WALL VERTS PER PLAN SCALE: 3/4" = 1'-0" COMPRESSIBLE FILLER, TYP 2 CMU WALL PER PLAN 1'-0" BENJAMIN TALPOS 51 SECTION 7290 West 133rd Street Overland Park, Kansas 66213 tel: (913)897-7811 0' - 8" EXT PER ARCH FTG & REINF PER OTHER DETAILS 2x4 KEYWAY, TYP PER PLAN SLAB PER PLAN, TYP DRAINAGE SYSTEM PER CIVIL #4x3'-0" DWLS @ 24"OC 2'-0" S3.4 DWLS TO MATCH WALL VERTS BOND BM DWLS TO MATCH VERT WALL REINF NOTE: THIS FOUNDATION IS A GRADE BEAM. REFER TO TYPICAL GRADE BEAM DETAILS FOR LAP & SPLICE INFORMATION. Architecture Engineering Planning Interiors SCALE: 3/4" = 1'-0" GRADE OR SLAB PER CIVIL 0' - 8" NOTE: THIS FOUNDATION IS A GRADE BEAM. REFER TO TYPICAL GRADE BEAM DETAILS FOR LAP & SPLICE INFORMATION. 45 2x4 KEYWAY CONT PER ARCH TO MASONRY WALL REINF PER OTHER DETAILS PIER PER PLAN 1 10-04-12 ADD #2 SECTION 2 PIER PER PLAN 1 PER PLAN PER ARCH TYP 1-#4 CONT #4 SUPPORT TIES @ 12" OC (3) #4 @ 6"OC, EA FACE @ BOT OF WALL 8" S3.4 STAIR TREAD & RISERS PER OTHER DETAILS 10/8/2012 6:16:43 PM C:\Users\BrionP\Documents\9-2013-Revit Projects\Joplin\13-12102-00_central_struct_2012.rvt #4 @ 12"OC EA FACE #4 SUPPORT TIES @ 12" OC 13-12102-00 09/10/12 VARIES 1' - 6" 2' - 6" 1' - 0" PER PLAN SLAB PER PLAN 2' - 0" DWLS TO MATCH WALL VERTS DWLS TO MATCH VERT WALL REINF #4 SUPPORT TIES @ 16" OC PER PLAN #4 x 5'-0" @ 24"OC FIELD BEND 2'-6" INTO SLAB 5-#6 TOP & BOT 3" VARIES 5-#6 TOP & BOT #6 @ 12"OC EA FACE PER PLAN 4-#11 EA FACE CONT 2' - 0" 1' - 4" 3-#6 TOP & BOT L4x4x1/4 CONT EMBED W/ 3/4" DIA HEADED STUDS @ 24"OC (GALV) SLAB PER PLAN, TYP 4-#11 EA FACE CONT #6 @ 12"OC, EA FACE 3-#6 TOP & BOT SCALE: 3/4" = 1'-0" COMPRESSIBLE FILLER, TYP 3" 0' - 8" #4 @ 12"OC, EA FACE 42 2x4 KEYWAY CONT SLAB PER PLAN, TYP INSUL PER ARCH SECTION GROUT SOLID ALL CELLS BELOW GRADE COMPRESSIBLE FILLER, TYP 8" #4 SUPPORT TIES @ 16" OC S3.4 (3) #4 @ 6"OC, EA FACE @ BOT OF WALL 2x4 KEYWAY CONT 8" 4" SLAB PER PLAN INSUL PER ARCH SECTION #4 @ 12"OC EA FACE 8" GRADE OR SLAB PER CIVIL #4x5'-0" @ 48"OC FIELD BEND 2'-6" INTO SLAB GRADE OR SLAB PER CIVIL #4 @ 12"OC EA FACE PER PLAN #6 @ 12"OC EA FACE CMU WALL PER PLAN SLAB PER PLAN 1-#4 CONT 4" S3.4 #4x5'-0" @ 48"OC FIELD BEND 2'-6" INTO SLAB GROUT SOLID BELOW GRADE MTL STUDS PER ARCH 33 1' - 0" JOPLIN HIGH SCHOOL #4 @ 12"OC, EA FACE INSUL PER ARCH FOUNDATION SECTIONS 8" VARIES 8" INSUL PER ARCH EXT PER ARCH SCALE: 3/4" = 1'-0" BASE PL WINDOW PER ARCH INSULATION PER ARCH SECTION SLAB PER PLAN GRADE OR SLAB PER CIVIL 8" 25 #4x5'-0" @ 48"OC FIELD BEND 2'-6" INTO SLAB GROUT SOLID BELOW GRADE SLAB PER PLAN GRADE OR SLAB PER CIVIL 1-#4 CONT S3.4 S3.4 INSULATION PER ARCH 1-#4 CONT VARIES SCALE: 3/4" = 1'-0" SECTION 1' - 6" 22 8" SECTION JOPLIN, JASPER COUNTY, MISSOURI #4 @ 12"OC, EA FACE S5.3 #4 SUPPORT TIES @ 16" OC 2' - 6" INSULATION PER ARCH INSUL PER ARCH WINDOW PER ARCH HSS PER PLAN MTL STUDS INFILL PER ARCH 11 EXT PER ARCH EXT PER ARCH SLAB PER PLAN GRADE OR SLAB PER CIVIL 8" C12x20.7 CONT BTWN BMS. ANCHOR W/ 3/4" DIA ANCHOR BOLTS @ 24"OC (EMBED 4") PER PLAN INSULATION PER ARCH #4x5'-0" @ 12"OC FIELD BEND 2'-6" INTO SLAB 8" SLAB PER PLAN GRADE OR SLAB PER CIVIL 1-#4 CONT WINDOW PER ARCH 8" 2' - 6" 1' - 0" #8 @ 9"OC, EA FACE 41 SCALE: 3/4" = 1'-0" 8" 1' - 8" GROUT SOLID BELOW GRADE SECTION BASE PL 2x4 CONT KEYWAY AND WATERSTOP, TYP 3-#6 TOP & BOT S3.4 S3.4 SECTION S5.3 PER PLAN #4x5'-0" @ 12"OC FIELD BEND 2'-6" INTO SLAB #4 SUPPORT TIES @ 16" OC 21 14 INSULATION PER ARCH PER PLAN WINDOW PER ARCH HSS PER PLAN MTL STUDS INFILL PER ARCH 11 1-#4 CONT SLAB PER PLAN INSUL PER ARCH 1' - 4" 3-#6 TOP & BOT #6 @ 12"OC, TOP & BOT DOOR PER ARCH 1' - 4" GRADE OR SLAB PER CIVIL #4 @ 12"OC, EA FACE 1' - 6" SCALE: 3/4" = 1'-0" 8" #6 @ 12"OC, TOP & BOT STD HOOK @ ENDS SLAB PER PLAN GRADE OR SLAB PER CIVIL INSUL PER ARCH 2x4 CONT KEYWAY, TYP 0' - 8" #4x5'-0" @ 48"OC FIELD BEND 2'-6" INTO SLAB SLAB PER PLAN DWLS TO MATCH VERT WALL REINF PER PLAN #4x5'-0" @ 48"OC FIELD BEND 2'-6" INTO SLAB GROUT SOLID BELOW GRADE GROUT SOLID BELOW GRADE 2' - 6" EXT PER ARCH HSS POST PER PLAN W/ 1/4" CAP PL BASE PL 1-#4 CONT EXT PER ARCH #5 @ 12"OC PER PLAN 1-#4 CONT INSULATION PER ARCH #4 @ 12"OC DRAINAGE SYSTEM PER CIVIL INSULATION PER ARCH 4" GRADE OR SLAB PER CIVIL 3-#6 TOP & BOT MTL STUDS PER ARCH WINDOW PER ARCH HSS PER PLAN MTL STUDS INFILL PER ARCH 1-#4 CONT #4x5'-0" @ 48"OC FIELD BEND 2'-6" INTO SLAB SLAB PER CIVIL INSUL PER ARCH SECTION S5.3 L4x4x1/4x0'-4" LONG CLIP 4" #4 SUPPORT TIES @ 16" OC S3.4 INSULATION PER ARCH EXT PER ARCH 1/2" COMPRESSIBLE FILLER 12 11 2'-0" MIN GRADE OR SLAB PER CIVIL HSS PER PLAN L4x4x1/4 CONT W/ 3/4" DIA HSA x 3" LONG @ 24"OC (GALV) 1-#4 CONT #4x5'-0" @ 48"OC FIELD BEND 2'-6" INTO SLAB GROUT SOLID BELOW GRADE #4x5'-0" @ 12"OC FIELD BEND 2'-6" INTO SLAB, TYP SLAB PER PLAN 0' - 8" WINDOW PER ARCH MTL STUDS PER ARCH 1-#4 CONT, TYP 8" INSULATION PER ARCH 2' - 6" 11 WINDOW PER ARCH 1-#4 CONT INSULATION PER ARCH #4x6'-0" @ 12"OC FIELD BEND 2'-6" INTO SLAB EXT PER ARCH STAIRS PER PLAN GROUT SOLID BELOW GRADE GRADE OR SLAB PER CIVIL 2x4 CONT KEYWAY AND WATERSTOP, TYP #4 @ 12"OC PER ARCH BRICK LEDGE EXT PER ARCH 8" 1' - 0" 2" EXT PER ARCH GRADE OR SLAB PER CIVIL GRADE OR SLAB PER CIVIL GROUT SOLID BELOW GRADE GROUT SOLID BELOW GRADE 1' - 0" 2" 8" #8 @ 9"OC EA FACE INSULATION PER ARCH #8 @ 9"OC EA FACE #8 @ 9"OC EA FACE #4 @ 12"OC EA FACE DWLS TO MATCH WALL VERTS #4 @ 12"OC EA FACE #4 @ 12"OC EA FACE DRAINAGE SYSTEM PER ARCH COMPRESSIBLE FILLER, TYP SLAB PER PLAN, TYP 8" 2-#5 CONT #6 @ 9"OC, TOP & BOT #6 @ 9"OC, TOP & BOT #5 @ 12"OC, TOP & BOT 2-#5 CONT 1' - 8" 2-#5 CONT PER PLAN 1' - 8" PER PLAN PER PLAN 1' - 8" PER PLAN SECTION 23 SCALE: 3/4" = 1'-0" WINDOW PER ARCH S3.5 1' - 0" #5 @ 12"OC, TOP & BOT 1' - 0" #5 @ 12"OC, TOP & BOT SLAB PER PLAN, TYP 2x4 CONT KEYWAY AND WATERSTOP, TYP 2' - 6" 2' - 6" 8" 2x4 CONT KEYWAY AND WATERSTOP, TYP COMPRESSIBLE FILLER, TYP 2' - 6" SLAB PER PLAN, TYP 2x4 CONT KEYWAY AND WATERSTOP, TYP 21 DRAINAGE SYSTEM PER ARCH COMPRESSIBLE FILLER, TYP 1' - 0" DRAINAGE SYSTEM PER ARCH DWLS TO MATCH WALL VERTS 8" DWLS TO MATCH WALL VERTS S3.5 GEOFOAM PER ARCH BRICK LEDGE INSULATION PER ARCH #6 @ 9"OC, TOP & BOT 2" 1' - 0" PER PLAN PER PLAN SECTION 25 SCALE: 3/4" = 1'-0" S3.5 SECTION SCALE: 3/4" = 1'-0" 1-#4 CONT INSULATION PER ARCH #4x6'-0" @ 12"OC FIELD BEND 2'-6" INTO SLAB EXT PER ARCH STAIRS PER PLAN GROUT SOLID BELOW GRADE #4 @ 12"OC 1' - 0" 1' - 8" GEOFOAM CMU WALL PER PLAN DWLS TO MATCH WALL VERT REINF SLAB PER PLAN #8 @ 9"OC EA FACE #8 @ 9"OC EA FACE L4x4x1/4 CONT EMBED W/ 3/4" DIA HEADED STUDS @ 24"OC (GALV) #4 @ 12"OC EA FACE #4 @ 12"OC EA FACE PER PLAN #4x3'-0" DWLS @ 24"OC 2'-0" COMPRESSIBLE FILLER, TYP 1/2" COMPRESSIBLE FILLER 2 10-08-12 ADD #3 Architecture Engineering Planning Interiors 7290 West 133rd Street Overland Park, Kansas 66213 tel: (913)897-7811 S3.5 FTG & REINF PER OTHER DETAILS 2x4 KEYWAY, TYP 1' - 0" 1 DRAINAGE SYSTEM PER CIVIL 1' - 6" 2' - 0" MIN 2' - 6" 8" DWLS TO MATCH VERT WALL REINF 2' - 6" 1' - 0" #5 @ 12"OC, TOP & BOT 2-#5 CONT 2-#5 CONT 1' - 8" 1' - 8" 0' - 8" SLAB PER CIVIL #8 @ 12"OC, TOP & BOT #5 @ 12"OC, TOP & BOT STAIR TREAD & RISERS PER OTHER DETAILS SLAB PER PLAN, TYP 2x4 CONT KEYWAY AND WATERSTOP, TYP SLAB PER PLAN, TYP 2x4 CONT KEYWAY AND WATERSTOP, TYP COMPRESSIBLE FILLER, TYP 8" DRAINAGE SYSTEM PER ARCH DRAINAGE SYSTEM PER ARCH 1'-0" DWLS TO MATCH WALL VERTS DWLS TO MATCH WALL VERTS #8 @ 12"OC, TOP & BOT WALL REINF PER OTHER DETAILS Revisions 2" 2" 1 10-04-12 ADD #2 8" 2 13-12102-00 09/10/12 PER ARCH BRICK LEDGE FOUNDATION SECTIONS 2x4 CONT KEYWAY AND WATERSTOP, TYP JOPLIN HIGH SCHOOL GRADE OR SLAB PER CIVIL JOPLIN, JASPER COUNTY, MISSOURI PER ARCH BRICK LEDGE 8" PER PLAN PER PLAN PER PLAN PER PLAN PER PLAN #4x5'-0" @ 12"OC FIELD BEND 2'-6" INTO SLAB, TYP SLAB PER PLAN 1/2" COMPRESSIBLE FILLER 0' - 8" 2 SLAB PER PLAN L4x4x1/4 CONT W/ 3/4" DIA HSA x 3" LONG @ 24"OC (GALV) 1-#4 CONT, TYP #5 @ 12"OC SLAB PER CIVIL DWLS TO MATCH VERT WALL REINF #5 @ 12"OC 2'-0" MIN 0' - 8" DWLS TO MATCH VERT WALL REINF (ALT HOOKS) 0' - 8" PER PLAN #6 @ 12"OC, TOP & BOT #6 @ 12"OC, TOP & BOT STD HOOK @ ENDS 1' - 6" 1' - 6" #3 SUPPORT TIES @ 16" OC 3-#6 TOP & BOT BENJAMIN TALPOS S3.5 SECTION SCALE: 3/4" = 1'-0" PER PLAN 2x4 CONT KEYWAY, TYP DRAINAGE SYSTEM PER CIVIL 2x4 CONT KEYWAY, TYP 0' - 8" SCALE: 3/4" = 1'-0" 46 S3.5 SECTION SCALE: 3/4" = 1'-0" #4x5'-0" @ 12"OC FIELD BEND 2'-6" INTO SLAB, TYP #4 @ 12"OC #4 @ 12"OC 51 S3.5 0' - 8" SCALE: 3/4" = 1'-0" SECTION PER PLAN © 2012, DLR Group of Missouri inc., a Missouri corporation CA No. 001614, ALL RIGHTS RESERVED. 43 L4x4x1/4 CONT W/ 3/4" DIA HSA x 3" LONG @ 24"OC (GALV) 10/8/2012 6:16:48 PM C:\Users\BrionP\Documents\9-2013-Revit Projects\Joplin\13-12102-00_central_struct_2012.rvt S3.5 SECTION 0' - 8" 41 2" 1' - 8" 2" CL 2 #8 @ 9"OC EA FACE #8 @ 9"OC EA FACE SQUARE CONC PEDESTAL CENTER ON COL (SIZE VARIES) #4 @ 12"OC EA FACE #4 @ 12"OC EA FACE 2-#4 U-BARS IN EACH DIRECTION 3' - 0" 1' - 8" DRAINAGE SYSTEM PER ARCH DRAINAGE SYSTEM PER ARCH COMPRESSIBLE FILLER, TYP SLAB PER PLAN, TYP NON-SHRINK GROUT COMPRESSIBLE FILLER, TYP SLAB PER CIVIL, TYP SLAB PER PLAN, TYP 8" 2x4 CONT KEYWAY AND WATERSTOP, TYP 8" 2x4 CONT KEYWAY AND WATERSTOP, TYP BASE PL, ANCHOR RODS, & GROUT PER SCHEDULE (GALV) VARIES DWLS TO MATCH WALL VERTS 8" TYP 4" DWLS TO MATCH WALL VERTS STL COL & BASE PL SEE SCHEDULE (GALV) PER SCHED 2' - 6" 2' - 6" TO FTG PER PLAN 2-#5 CONT PER PLAN 1' - 8" PER PLAN FTG & REINF PER PLAN & SCHED PER PLAN SECTION 23 SCALE: 3/4" = 1'-0" S3.6 1' - 8" SECTION 25 SCALE: 3/4" = 1'-0" S3.6 SECTION SCALE: 3/4" = 1'-0" FOUNDATION SECTIONS 2" #10 @ 6"OC EA FACE #4 @ 12"OC EA FACE DWLS TO MATCH WALL VERTS DRAINAGE SYSTEM PER ARCH COMPRESSIBLE FILLER, TYP SLAB PER PLAN, TYP 2 10-08-12 ADD #3 Architecture Engineering Planning Interiors 7290 West 133rd Street Overland Park, Kansas 66213 tel: (913)897-7811 #5 @ 12"OC, TOP & BOT 1' - 0" #8 @ 9"OC, TOP & BOT Revisions 1 S3.6 2' - 6" 8" 2x4 CONT KEYWAY AND WATERSTOP, TYP 1 10-04-12 ADD #2 21 S3.6 PER PLAN 13-12102-00 09/10/12 1' - 8" PER SCHED JOPLIN, JASPER COUNTY, MISSOURI 2-#5 CONT #5 @ 12"OC, TOP & BOT JOPLIN HIGH SCHOOL #8 @ 12"OC, TOP & BOT 1' - 0" #5 @ 12"OC, TOP & BOT 1' - 0" #6 @ 9"OC, TOP & BOT 2-#5 CONT 1' - 8" PER PLAN PER PLAN BENJAMIN TALPOS 10/8/2012 6:16:52 PM C:\Users\BrionP\Documents\9-2013-Revit Projects\Joplin\13-12102-00_central_struct_2012.rvt S3.6 SECTION SCALE: 3/4" = 1'-0" © 2012, DLR Group of Missouri inc., a Missouri corporation CA No. 001614, ALL RIGHTS RESERVED. 41 STUD PLACEMENT: B. GIRDERS: THE NUMBER SHOWN THUS (NO) FOLLOWING THE BEAM SIZE INDICATES THE NUMBER OF 3/4" HEADED STUDS TO BE PLACED ON THE BEAM. ALL BEAMS (AND GIRDERS) SHALL HAVE HEADED STUDS ATTACHED TO THE TOP FLANGE. IF NO SPECIFIC STUD QUANTITY IS NOTED ON PLANS. THE MAXIMUM STUD SPACING SHALL BE 2'-0. DECK VALLEYS WITHOUT STUDS SHALL BE WELDED. 2. STUD PLACEMENT SHALL BE AS FOLLOWS: A. NUMBER OF STUDS IS LESS THAN THE NUMBER OF DECK VALLEYS: UNIFORMLY SPACE STUDS SYMMETRICALLY WITH THE BEAM CENTERLINE. B. 2. NUMBER OF STUDS IS GREATER THAN THE NUMBER OF DECK VALLEYS: PLACE ONE STUD IN EACH VALLEY STARTING AT THE ENDS OF THE BEAM. ADD SECOND STUD STARTING AT EACH END OF BEAM UNTIL REQUIRED NUMBER OF STUDS ARE PLACED. WHEN TWO STUDS ARE REQUIRED PLACE STUDS 1 1/2" EACH SIDE OF THE BEAM WEB. NOTE: SPACE 'A' TO COORDINATE WITH DECK LAYOUT. A EQUAL SPACED STUDS THE SERIES OF NUMBERS SHOWN THUS [NO-NO-NO] FOLLOWING THE GIRDER SIZE WHEN ADDED TOGETHER REPRESENT THE TOTAL NUMBER OF STUDS TO BE PLACED ON THE GIRDER. FOR EXAMPLE, [10-3-10] REPRESENTS A TOTAL OF 23 STUDS TO BE LOCATED ON THE GIRDER. THE FIRST LAST NUMBERS REPRESENTS THE NUMBER OF STUDS TO BE PLACED BETWEEN THE END OF THE GIRDER AND THE FIRST (OR LAST) INTERSECTING BEAM. THE MIDDLE NUMBER REPRESENTS THE NUMBER OF STUDS TO BE LOCATED BETWEEN THE TWO INTERSECTING BEAMS. CL 2'-0" MAX A STEEL DECK SHEAR STUDS SW 1 1/2" #4X4'-0 @ 1'-6 OC WWF- SEE PLANS PLACE STUDS UNIFORMLY ALONG THE BEAM OR PORTION OF BEAM INDICATED. CENTER THE STUDS OVER THE WEB AND PROVIDE A MAXIMUM SPACING OF 2'-0" AND A MINMUM SPACING OF 4 1/2". IF THE REQUIRED NUMBER OF STUDS EXCEEDS WHAT CAN BE PLACED AT 4 1/2", PLACE A SECOND ROW OF STUDS SPACED AT 4 1/2" CENTERS, STARTING AT THE END OF THE BEAM, UNTIL THE REQUIRED NUMBER OF STUDS IS REACHED. WHEN TWO ROWS OF STUDS ARE REQUIRED, PLACE STUDS 1 1/2" EACH SIDE OF THE BEAM CENTER LINE. CL CL 3/4"DIAX4" WWF- SEE PLANS CONC OVER METAL DECK, DECK DIRECTION AND REINFORCING PER PLAN ANGLE 3" X 3" X 1/4" WELDED TO COLUMN AND BEAM AS REQUIRED TO SUPPORT STEEL DECK RIBS. 1" UNO PER PLAN 1. 1. PER PLAN A. BEAMS: CONTINUOUS BENT PL 1/4x6x0'-5" (LLV), WELD TO PERPINDICULAR BENT PL WITH 3/16 FILLET WELD FULL HEIGHT. WHERE EDGE OF SLAB IS GREATER THAN 6" FROM BM CL, INCREASE HORIZ LEG OF BENT PL ACCORDINGLY. EDGE OF SLAB TO BM CL SHALL NOT EXCEED 1'-1". CL STUDS ALTERNATE SIDES 10 STUDS UNIFRMLY SPACE 2'-0 MAX 3 STUDS UNIFORMLY SPACE EXAMPLE LAYOUT 10 STUDS UNIFORMLY SPACE FIELD CUT STEEL DECK TO CLEAR COLUMN. PROVIDE AND INSTALL SHEET METAL FILLERS, FLASHING CLOSURES, ETC., AS REQUIRED. TACK WELD IN PLACE NOTE: PROVIDE DECK GIRDER FILLER PL IF REQUIRED. A EXAMPLE LAYOUT @ COMP BMS B PLAN VIEW @ COMP GIRDERS 3/16 2 - 12 STEEL EDGE ANGLE FOR SIZE AND LOCATION, SEE PLAN AND DETAILS BEAM PER PLAN 0' - 6" TO BM CL TYP, UNO NOTE: THIS DETAIL APPLIES TO ALL ANGLE SPLICES AT ROOF DECK AND WHERE OTHERWISE NOTED. EXAMPLE: [10-3-10] 4 W21 5 W24 6 W27, W30 7 C8x11.5 TYPE B CONDITION TYP REINFORCING AT FLOOR PENETRATIONS 23 SCALE: 3/4" = 1'-0" S4.1 MINIMUM BOLT SCHEDULE 24 SCALE: 1" = 1'-0" S4.1 SEAT CONN TO PRECAST SEATING UNIT SCALE: 1 1/2" = 1'-0" 25 S4.1 1 3/4" 1 1/4" 1 3/4" 1 1/4" L L BOLTS @3"OC 1 1/2" 1 1/4" 2L CONN PER STL SUPPLIER SEE SCHED PLATE SIZE PER STEEL SUPPLIER PER STEEL NOTES: 1. STEEL SUPPLIER TO DESIGN PER LRFD REACTIONS AS SHOWN ON PLAN. 2. MINIMUM NUMBER OF BOLTS PER SCHEDULE. 3. IF NO REACTION IS PROVIDED, DESIGN CONNECTIONS TO RESIST 1/2 THE MAXIMUM TOTAL UNIFORM LRFD LOAD BASED ON SPAN LISTED IN TABLE 35.6 FOR THE AISC STEEL CONNECTION MANUAL (13TH EDITION) FIELD WELD OPTIONAL TYPICAL CONNECTION CHANNEL TO W SHAPE SECTION B 2L CONN PER STL SUPPLIER STL BM A PLAN PRECAST SEATING UNIT PER PRECAST SUPPLIER STL BM SUPPLIER B BOLTED CONN A WELDED CONN NOTES: 1. STEEL SUPPLIER TO DESIGN PER LRFD REACTIONS AS SHOWN ON PLAN. 2. MINIMUM NUMBER OF BOLTS PER SCHEDULE. 3. IF NO REACTION IS PROVIDED, DESIGN CONNECTIONS TO RESIST 1/2 THE MAXIMUM TOTAL UNIFORM LRFD LOAD BASED ON SPAN LISTED IN TABLE 35.6 FOR THE AISC STEEL CONNECTION MANUAL (13TH EDITION) TYP STL BM CONN DET 26 SCALE: 1" = 1'-0" B BOLTED CONN S4.1 TYP DOUBLE ANGLE CONN DETAIL SCALE: 1" = 1'-0" SLAB PER PLAN TYP B COLUMN TO PLATE 5/16 1 PLATE AND ANGLE SCHEDULE STEEL COLUMN SEE PLAN 3 SIDES PL3/8"x7x1'-0" TYP A 4-3/4"Ø A325N BOLTS TOP OF STEEL SEE PLAN 1/4 ANGLE (PER SCHED) x FLUTE SPACING + 4 1/2" WITH (2) 5/8" DIA EXPANSION ANCHORS (4 1/2" EMBEDMENT) 3 SIDES SEE DETALS FOR ANGLE SIZE AND SPACING BM PER PLAN 1/4 3/8" STIFFENER PLATES EACH SIDE CHANNEL PER SECTION BM PER PLAN 1/4 3/16 A A EQ EQ TYP A ANGLE PER SECTION SEE DETALS FOR ANGLE SIZE AND SPACING BM PER PLAN PL PER SCHED B 3/16" WELD SIZE ANGLE CONNECTION SIZE TO COMPOSITE SLAB L2x2x1/4 4"x4"x1/4" A 3/16" L2 1/2x2 1/2x1/4 4"x4"x1/4" 3/16" 3/16" L4x4x1/4 L3x3x1/4 4"x4"x1/4" 3/16" 3/16" L4x4x1/4 L4x4x1/4 5"x5"x1/4" 3/16" 3/16" L3x3x1/4 NOT APPLICABLE GRADE 60 BAR (A706) B STIFF PL PER SECTION STEEL BEAM SEE PLAN WELD TYP SLAB PER PLAN PL PER SCHED PLATE SIZE BRACE ANGLE SIZE PLATE THICKNESS STEEL COLUMN SEE PLAN BAR SIZE WELD SIZE (IN) MIN PLATE THICKNESS (IN) 3 1/4 5/16 4 5/16 5/16 5 3/8 5/16 6 7/16 3/8 7 1/2 1/2 8 9/16 1/2 9 5/8 5/8 10 11/16 5/8 11 3/4 3/4 NOTES: 1. FIELD WELDING OF CONNECTION PLATES SHALL BE AT FABRICATOR'S OPTION. 2. SEE PLANS AND DETAILS FOR LOCATIONS OF BRACES. ANGLE (PER SCHED) x FLUTE 3. CLIP CONNECTION PLATES TO CLEAR BEAM AND ANGLE SPACING + 4 1/2" WITH (2) 5/8" DIA FILLETS. EXPANSION ANCHORS (4 1/2" EMBEDMENT) TYP B S4.1 CONTINUITY PLATES FS. & NS. USE LARGER OF TF1 OR TF2 (SEE TYPICAL "CONTINUITY PL DETAIL") 4" MIN. CAP PL TO COL FLANGE L4x3x3/8 (NS & FS) HSS PER PLAN 'S' CJP U.T. 3/4" CONTINUITY PLATE S4.1 BEAM TO HSS COL MOMENT CONN SCALE: 3/4" = 1'-0" 3/8 7/16 1/2 MIN SPLICE LENGTH (IN) 3 1 1/2 1 1/2 1 1/2 1 1/2 1 1/2 3 C.P. TYP AT BEAM WEB TO COLUMN ELEVATION FRAME COLUMN SEE ELEVATION SHOWN ON PLAN THUS: ELEVATION 42 S4.1 TW BM TO COL FLANGE MOMENT CONN SCALE: 3/4" = 1'-0" 43 S4.1 'S' E70 CJP U.T. ERECTION PLATES AND BOLTS AS REQ'D BY STEEL FABRICATOR (2) 1" DIA A325X BOLTS, MIN SHEAR CONN PER STEEL SUPPLIER EMBED PL PER SCHED ELEVATION CONTINUITY PLATES FS. AND NS. USE LARGER OF TF1 OR TF2 SHOWN ON PLAN THUS: 5/16 5/16 3 SIDES BM TO WF COL MOMENT CONN 44 SCALE: 3/4" = 1'-0" S4.1 TYP MOMENT FRAME, BMS DIFF DEPTH BM PER PLAN SCALE: 3/4" = 1'-0" SLOPE STUDS WHERE TOP OF CIP COLUMN OR WALL IS LESS THAN 4" HIGHER THAN STEEL BEAM 0' - 0 1/2" L4x3x3/8 (NS & FS) 46 S4.1 4 2 2 2 2 2 4 1/2 5 2 1/2 2 1/2 2 1/2 2 1/2 2 1/2 5 1/4 6 3 3 3 3 3 6 7 3 3/4 3 1/4 3 1/4 3 1/4 3 1/4 6 3/4 8 5 4 3 3/4 3 3/4 3 3/4 7 1/2 9 6 1/4 5 4 1/4 4 1/4 4 1/4 9 10 8 6 1/4 5 1/4 4 3/4 4 3/4 9 3/4 11 9 3/4 7 3/4 6 1/2 5 1/2 5 3/4 10 1/2 WELD PARALLEL TO BAR SCHED SCALE: 3" = 1'-0" CL OF MEMBER & EMBED PL 'S' CL COL CL END OF BEAM WHERE OCCURS 1 BEAM SPAN UP TO 4'-0" 4'-0" ≤ L ≤ 8'-0" BENJAMIN TALPOS 51 S4.1 TYP BM TO BM MOMENT CONNECTION SCALE: 3/4" = 1'-0" L4x4x1/4 1 L6x4x3/8 (LLV) SPAN FRAME OPENING BM PER PLAN LOOSE LINTEL 0' - 6" COL PER PLAN BM PER PLAN WHERE APPLICABLE 0' - 1 1/2" 0' - 2" CL STD SHORT SLOTTED HORIZ HOLES FOR 3/4" DIA BOLTS (IN ANGLE ONLY) 1 WELD A HOT-DIPPED GALV LOOSE ANGLE LINTEL PER SCHEDULE C12, W12, W14 W16, W18 W21 W24 W27, W30 HSS10 HSS12 HSS6 'N' 3 4 6 7 8 NA NA NA 'L' 9" 12" 18" 21" 24" 8" 10" 5" EMBED PL 1/2x12x0'-10" 1/2x16x0'-10" 1/2x22x0'-10" 3/4x22x0'-10" 3/4x25x0'-10" 1/2x14x0'-10" 1/2x16x0'-10" 1/2x10x0'-10" STEEL BEAM EMBED PL PER SCHED 'S' 8" 6" 6" 6" 7" 5" 6" 6" HEADED STUDS GAGE SIZE 6" (4) 3/4" DIAx6" 6" (6) 3/4" DIAx6" 6" (8) 3/4" DIAx8" 6" (8) 3/4" DIAx6" 6" (8) 3/4" DIAx6" 6" (6) 3/4" DIAx6" 6" (6) 3/4" DIAx6" 6" (4) 3/4" DIAx6" TOS EL SEE PLANS REMARKS 1 33/64" 3 SIDES 3/16 NOTES: 1. WHEN WELDS A AND B ARE NOT SPECIFICALLY CALLED OUT, REFER TO AISC LRFD SPECIFICATIONS FOR REQUIRED WELD SIZE. 2. FABRICATOR TO SUPPLY ERECTION DEVICES AS REQUIRED TO HOLD COLUMN SECURELY IN PLACE DURING ERECTION. 52 S4.1 SECTION SCALE: 3/4" = 1'-0" 1 31/64" 1/2" CAP PLATE 4-3/4"Ø A325-N BOLTS STEEL COLUMN 53 S4.1 TYP LOOSE LINTEL SCHEDULE SCALE: 1" = 1'-0" 55 S4.1 TYP EMBED PLATE SCHEDULE SCALE: 3/4" = 1'-0" 56 S4.1 TYP BEAM TO COLUMN DETAIL SCALE: 1" = 1'-0" 7290 West 133rd Street Overland Park, Kansas 66213 tel: (913)897-7811 SUPPORTING WALL 1 0' - 2" SHEATHING PER ARCH WELD B 0' - 1 1/2" COL FINISH COL FINISH CJP WELD EA FLANGE, UT 3/8" STIFFENER PLATE EACH SIDE CLIP CORNERS Architecture Engineering Planning Interiors 'S' 'L' MASONRY VENEER PER ARCH COL PER PLAN # BOLTS 'N' @ 3"OC DOUBLE ANGLE SHEAR CONN PER SUPPLIER 10/8/2012 6:17:00 PM C:\Users\BrionP\Documents\9-2013-Revit Projects\Joplin\13-12102-00_central_struct_2012.rvt 5/16 'L' TYP AT SHEAR TAB TO COLUMN SHOWN ON PLAN THUS: 41 1/4 0' - 2" C.P. TYP AT BEAM WEB TO COLUMN ELEVATION FRAME COLUMN SEE ELEVATION SHOWN ON PLAN THUS: ERECTION PLATES AND BOLTS AS REQ'D BY STEEL FABRICATOR MINIMUM LENGTH OF WELD (IN) PL THICKNESS (IN) BAR SIZE CL OF MEMBER & EMBED PL 0' - 2" TW FRAME BEAM SEE ELEVATION 0' - 1 1/2" 0' - 1 1/2" TYP AT SHEAR TAB TO COLUMN SPLICE ELECTRODE 5/16 FRAME BEAM SEE ELEVATION SCALE: 3" = 1'-0" SLOPE STUDS WHERE TOP OF CIP COLUMN OR WALL IS LESS THAN 4" HIGHER THAN STEEL BEAM 0' - 0 1/2" SHEAR CONN PER STEEL SUPPLIER 5/16 5/16 5/16 3 SIDES 0' - 2" SHEAR CONN PER STEEL SUPPLIER BAR TO PLATE WELD SCHEDULE 4" MIN. k MIN TF1 M 36 SCALE: 3/4" = 1'-0" TF1 C.P. REMOVE BACK-UP BARS SYM ABOUT CL COLUMN 4" MIN. k MIN CAP PL TO COL FLANGE S4.1 CAP PL THICKNESS GREATER OF TF1+1/4" OR TF2+1/4" (1" MIN) TF1 M k MIN C.P. REMOVE BACK-UP BARS SYMM. ABOUT CL COLUMN 4" MIN. CONTINUITY PLATES FS. & NS. USE LARGER OF TF1 OR TF2 (SEE TYPICAL "CONTINUITY PL DETAIL") 4" MIN. k MIN 3/4" CAP PL SCALE: 3/4" = 1'-0" BRACE CONNECTION TO COMPOSITE DECK TYPICAL DETAIL k MIN S4.1 34 k MIN SCALE: 1" = 1'-0" TYP CHANNEL HANGDOWN WELDS TF1 33 TF1 S4.1 POST TO BEAM CONNECTION k MIN 31 © 2012, DLR Group of Missouri inc., a Missouri corporation CA No. 001614, ALL RIGHTS RESERVED. W16, W18 STL BM JOPLIN, JASPER COUNTY, MISSOURI 3 1 3/4" TYP(INCREASE TO CLEAR WEB COPE WHERE REQD) JOPLIN HIGH SCHOOL 2 PIPE OR HSS COL 1 1/2" Revisions W8, W10 W12, W14 1 1/2" . 1/2" 1 10-08-12 ADD #3 NOTE: OPENINGS OUTSIDE THE LIMITS ABOVE SHALL BE FRAMED WITH STRUCTURAL STEEL OPENING SIZES AND LOCATIONS TO BE SUBMITTED TO THE STRUCTURAL ENGINEER. MINIMUM NUMBER OF BOLTS 1/2" 3" 1/2" 13-12102-00 09/10/12 L4x3x3/8 EA SIDE SEAT & CONN PER SEAT SUPPLIER STL COL FLOOR FRAMING TYPICAL DETAILS S4.1 0' - 3" DIAMETER > 18" OR ANY DIAMETER PIPE WHERE PIPE SUPPORTS WILL BE INSTALLED DIA ≤ 18" TYPE A CONDITION 21 BEAM SIZE W SHAPE CHANNEL CL SEE SCHED COORDINATE CONN BY SEAT SUPPLIER W/ REBAR AND STRAND LOCATIONS TO AVOID CONFLICTS W/ SEAT CONNECTION. PRECAST SUPPLIER TO COORDINATE TYPE OF CONNECTION WITH SEAT SUPPLIER 1 3/4" TYP(INCREASE TO CLEAR WEB COPE WHERE REQD) S4.1 DECK SPAN BOLTED STEEL CONNECTION DESIGNED BY THE STEEL SUPPLIER SHALL MEET THE MINIMUM NUMBER OF BOLTS LISTED IN THE FOLLOWING TABLE BASED ON STEEL MEMBER SIZE. FIELD WELD OPTIONAL TYPICAL CONNECTION CHANNEL TO CHANNEL SECTION A 6'-0" MAXIMUM DECK SPAN SECTION B, TYP C8x11.5 C6x8.2 ROUND PENETRATIONS UP TO 6"DIA MAY BE CORED AT THE SPACING SHOWN. FOR PENETRATIONS > 6" OR AT SPACING < 3x DIAMETERS, REINFORCE CONCRETE SLAB AS FOR RECTANGULAR OPENING SHOWN ABOVE. > 3x DIA 6" < W ≤ 1'-6" 1' - 6" 1-#5 BAR C8x11.5 SCALE: 3/4" = 1'-0" 1 1/2" REINFORCING STEEL & TENDON FREE ZONE TO ALLOW ANCHORAGE OF SEATS SECTION A, TYP 1-#5 BAR S4.1 CL C8x11.5 6'-0" MAXIMUM SCALE: 3/4" = 1'-0" TYP CONT EDGE ANGLE SPLICE DET 1 1/2" 0' - 6" S4.1 16 0' - 3" C6x8.2 0' - 6" BLOCK OUTOPENING ON TOP OF METAL DECK. CUT METAL DECK AFTER CONCRETE HAS CURED 3/8" PL ON BACKSIDE SCALE: 3/4" = 1'-0" TYP FLOOR OPENING, UNO BOLTS @3"OC OF SUPPORTS CHANNEL S4.1 15 L OF SUPPORTS SCALE: 1" = 1'-0" TYP STL DECK FRAMING CL CENTER LINE 14 1 1/4" S4.1 CENTER LINE TYP COMPOSITE BM & GIRDER DET BOLTS @3"OC 13 C6x8.2 SCALE: 1" = 1'-0" 1' - 6" S4.1 TYP STUD PLACEMENT DETAIL 1'-6" < W ≤ 4'-0" 11 PRECAST HOLLOW CORE OR DOUBLE TEE PRECAST HOLLOW CORE WELD SIZE = 1/2 PL THICKNESS BUTT WELD (CP) 1 1/2" STIFFENER PLATE TO MATCH FLANGE THICKNESS EACH SIDE OF STEEL BEAM PRECAST HOLLOW CORE UNITS MORTAR JOINT CORRUGATED TIES @ 2'-8" OC ATTACHED TO HOLLOW CORE WITH 3/16"Øx1" SCREW ANCHOR BOND BEAM VERTICAL MASONRY REINFORCING. SEE PLANS AND STRUCTURAL NOTES STEEL BEAM S4.2 STEEL BEAM BEAM SPLICE DETAIL 12 SCALE: 1" = 1'-0" S4.2 1/2"Ø THREADED RODS 13 NON-LOAD BEARING MASONRY WALL TO STRUCTURE SCALE: 1" = 1'-0" S4.2 PARTITION WALL BRACING DETAIL SCALE: 3/4" = 1'-0" MECHANICAL UNITS 6'-0" MAX NOTE: 14 S4.2 TYP TYP 1/8 3/16 L3x3x1/4x0'-4" 1 1/2 3 HSS2 1/2x2 1/2x3/16 SCALE: 3/4" = 1'-0" 2-#5 AT EACH SIDE OF OPENING (1 EACH FACE) 15 S4.2 NOTE: SEE ARCHITECTURAL PLANS FOR WALLS TO STRUCTURE. TYP PARTITION BRACING DETAIL 16 SCALE: 3/4" = 1'-0" S4.2 TYP PARTITION BRACING DETAIL SCALE: 3/4" = 1'-0" CP TYP TOP AND BOTTOM FLANGES 2' - 0" CL 3/4"DIA A325N BOLTS BOND BEAM NON-LOAD BEARING MASONRY WALL TO STRUCTURE NOTE: 1. WALLS SHALL BE LATERALLY SUPPORTED AT A MAXIMUM OF 4'-0 OC BY PERPENDICULAR WALLS OR BRACES AS SHOWN. 2. SEE ARCHITECTURAL PLANS FOR WALLS TO STRUCTURE. TYP HANGING MECHANICAL UNIT DETAIL CUT MASONRY COURSE AS REQUIRED VERTICAL MASONRY REINFORCING. SEE PLANS AND STRUCTURAL NOTES BOND BEAM NON-LOAD BEARING MASONRY PARTITION WALL VERTICAL MASONRY REINFORCING. SEE PLANS AND STRUCTURAL NOTES NUT & WASHER 1. SHOWN FOR INFORMATION ONLY. SUPPLIED BY MECHANICAL CONTRACTOR 2. HANGERS MUST BE IN PLACE BEFORE SLABS ARE GROUTED 3. BY GENERAL CONTRACTOR. VERIFY SIZE AND LOCATION WITH MECHANICAL CONTRACTOR NOTE: SEE ARCHITECTURAL PLANS FOR WALLS TO STRUCTURE MITERED BEAM DETAIL 1 1 (MIN) NUT & WASHER PRECAST HOLLOW CORE OR DOUBLE TEE VARIES STIFFENER PLATE TO MATCH FLANGE THICKNESS. (EACH SIDE AT W-SHAPE) 11 L3x3x3/16x0'-6" WITH 2-1/4"Øx1 3/4" SCREW ANCHORS @ 3" OC 1" CLR CP FIELD DRILL 5/8"Ø HOLES THROUGH VOIDS OF HOLLOW CORE 1". CLR 1 WELD SIZE = 1/2 PL THICKNESS 2-1/4"Øx1 3/4" SCREW ANCHORS @ 3" OC L3x3x1/4x0'-4" @ 4'-0" OC MAX L2 1/2x2 1/2x3/16 PL WASHER 1/4x4x0'-4" ANGLE BEARING CLIPS ON HOLLOW CORE " 4'-0 SEE TYPICAL STEEL BEAM CONNECTION DETAIL 2' - 0" 13/16"DIA STD HOLES MATCH JOIST SHOE DEPTH S4.2 TYP REINFORCED WALL OPENING DETAIL SCALE: 3/8" = 1'-0" 23 S4.2 TAPERED HOLE (2" TO 1 1/2" DIA @ 5'-0"OC MAXIUM SPACING. FILL HOLE W/ EPOXY GROUT) TYP DECK BEARING BEAM CONNECTION SCALE: 1" = 1'-0" 24 S4.2 BM / BM MOMENT CONN DETAIL 25 SCALE: 1 1/2" = 1'-0" S4.2 TYP HOLLOW CORE CONNECTION DETAIL SCALE: 3/4" = 1'-0" 26 S4.2 TYP HOLLOW CORE OPENING SCALE: 3/4" = 1'-0" 4" #3 HAIRPIN BARS 2'-0" 0' - 4" 0' - 1"EQ EQ 0' - 0 3/4" 0' - 3" 0' - 3" 0' - 2 1/2" 0' - 3" RECESS SHIMS FOR CALKING 0' - 0 9/16" HORSESHOE SHIMS (1/16", 1/8", & 1/4" THICK) 0' - 4" 1/2" DIA ANCHOR BOLT @ 5'-0"OC (MAX SPACING) PRECAST TREAD AND RISER UNIT, TYP 0' - 6" TYP. UNO NEOPRENE PADS (6"x6"x1") (1/4" AND 1/2" THICK), TYP #3 HAIRPIN BARS PER CONN DETAIL 'A' 3/4" RADIUS, TYP 1/4 1/4 0' - 3 1/2" TYP, UNO 0' - 2" 0' - 2" DETAIL 'C' AT FIXED END CONNECTION PROVIDE TAPERED HOLE (3" DIA TO 2 1/2 DIA) IN PRECAST. PROVIDE 3/4" DIA THREADED ROD. FILL HOLE WITH EPOXY GROUT. AT SLOTTED HOLE CONNECTION INCREASE TAPERED HOLE IN PRECAST TO 3/4" EACH SIDE AND ENDS OF SLOTTED HOLE IN PLATE. COVER TOP OF 3/4" DIA SMOOTH BAR WITH SHEET METAL AND FILL TOP OF HOLE WITH EPOXY GROUT. DO NOT ALLOW GROUT TO COME INTO CONTACT WITH BAR. GROUT PLUG 0' - 3" 0' - 3" P 4" TY BEARING PADS PER OTHER DETAILS 0' - 3 1/2" SEE CONN DETAIL 'B' VARIES 0' - 6" 0' - 8" PRECAST FIXED END CONNECTION STANDARD LONG SLOTTED HOLE AT SLIP CONNECTION ONLY. STANDARD HOLE AT FIXED CONNECTION. 0' - 0 1/2"0' - 0 1/2" EQ SCALE: 3/4" = 1'-0" UNISTRUT CHANNEL "P1001" 1'-4" LONG BOTTOM OF CHANNEL EL. SEE ARCH. 9" NUT AND WASHER TYP PERABLE WALL SUPPORT 3/8" DIA THREADED RODS W/ SPRING LOADED NUTS @ 4'-0"OC SCALE: 3/4" = 1'-0" CL FOLDING PARTITION BM PER PLAN EQ 0' - 1" HSS4x4x1/4" AT 5'-0" MAX GEOMETRY EQ PRECAST TREAD AND RISER UNIT SHALL BE CLEANED BEFORE PLACING CAST-IN-PLACE CONCRETE STEPS EQ EQ BENJAMIN TALPOS PRECAST TREAD AND RISER UNIT TYPICAL DETAIL PL 3/16x2x2 3/8" DIA THREADED RODS W/ SPRING LOADED NUTS @ 4'-0"OC NOTES: 1. FOR AISL STEPS THAT CROSS A JOINT IN THE PRECAST TREAD A BOND BREAKER SHALL BE APPLIED TO PRECAST ON ONE SIDE OF THE JOINT. DOUBLE ANGLE 2-1/2x2-1/2x3/16 BRACE WITH PL1/4x4x0'-4" AT MIDPOINT. SEE DETAIL 44/S4.2 FOR ATTACHMENT TO STRUCTURE ABOVE. LOCATE BRACE @ 4'-0"OC. ALTERNATE BRACE EA SIDE OF PARTITION. CAST-IN-PLACE AISLE STEPS OVER PRECAST TREAD AND RISER UNITS 54 S4.2 TYP 1/8 TYP UNISTRUT BEAM CLAP "P1386" W/ 1/2" - 13x 1 1/2" MACHINE BOLT 1 (MIN) 1 1/8 RE: 44/S4.2 FOR BOT OF ASSEMBLY AND BRACING. WON-DOOR TRACK ASSEMBLY BY SUPPLIER CL WOND DOOR UNISTRUT CHANNEL "P1001" 1'-4" LONG 3/16 2 PL1/4"x4 AT BRACE C12x20.7 NUT AND WASHER BOTTOM OF CHANNEL EL. SEE ARCH. JST OR BM PER 3/8" DIA THREADED RODS W/ PLAN SPRING LOADED NUTS @ 4'-0"OC 9" TYP OPERABLE WALL SUPPORT SCALE: 3/4" = 1'-0" STEEL JOISTS OR BM PER PLAN CL WOND DOOR HSS4x4x1/4" AT 5'-0" MAX WHEN PARTITION IS LOCATED BTWN SUPPORTING MEMBERS. OMIT WHEN PARTITION IS DIRECTLY UNDER STL BM. STEEL JOISTS OR BM PER PLAN DIRECTION OF SLIP CONN MOVEMENT DIRECTION OF SLIP CONN MOVEMENT PRECAST TREAD AND RISER UNIT AND CONNECTION TO STEEL RAKER BOLT TO JST BOT CHORD W/ 5/8" DIA BOLTS @ 4'-0"OC STL BM WHERE OCCURS RE: ARCH FOR 0' - 1" 0' - 8" 0' - 8" CL RAKER BM DETAIL 'C' (PLAN VIEW) NOTES: 1. PRECAST SIZES SHOWN ARE MINIMUM. PRECASTER IS RESPONSIBLE FOR PRECAST DESIGN. ALL GEOMETRY OF PRECAST TREAD AND RISER UNITS SHALL BE VERIFIED WITH THE ARCHITECTURAL PRIOR TO FABRICATION. 2. PRECAST TREAD AND RISER UNIT AND ALL CONNECTIONS TO THE STRUCTURE SHALL BE DESIGNED BY THE PRECAST SUPPLIER. ALL CONNECTION INFORMATION SHOWN IS SCHEMATIC AND IS FOR DESIGN INTENT ONLY. 3. PRECASTER TO REFER TO 35/S4.1 FOR SEATING CONNECTION TO PRECAST TREAD AND RISER UNIT CRITERIA. 51 DOUBLE ANGLE 2-1/2x2-1/2x3/16 BRACE WITH PL1/4x4x0'-4" AT MIDPOINT. LOCATE BRACE @ 4'-0"OC. ALTERNATE BRACE EA SIDE OF PARTITION. S4.2 JST PER PLAN 3/8" DIA THREADED RODS W/ SPRING LOADED NUTS @ 4'-0"OC PL1/4x4 WELDED TO CHANNEL AT BRACE RE: ARCH FOR GEOMETRY PRECAST SLIP END CONNECTION S4.2 PL1/4x4x0'-4" 44 PRECAST TREAD AND RISER UNIT EQ 10/8/2012 6:17:06 PM C:\Users\BrionP\Documents\9-2013-Revit Projects\Joplin\13-12102-00_central_struct_2012.rvt CAST-IN-PLACE STEPS STEEL RAKER BM (BELOW) 1 (MIN) 1 C12x20.7xCONTINUOUS (BEND TO RADIUS OF TRACK OR SEGMENT AND WELD TOGETHER WITH COMPLETE PENETRATION WELD) CONNECTION DETAIL 'B' RAKER SEAT CONNECTION, TYP 1/4" PLATE WASHER AND NUT TOP AND BOTTOM OF JOIST CHORD JST OR BM PER PLAN NOTES: 1. SHEET METAL BARRIER (22 GAGE) 1/4" MINIMUM 1/2" MAXIMUM ABOVE BAR AT SLOTTED HOLE CONDITION. #3 AHIRPIN BARS, TYP 2 WELD ANCHOR TO BEARING PLATE 0' - 2"0' - 2" (1/4) 3/16 0' - 3" 0' - 3" 0' - 1" 5/8"x18"xVERT HEIGHT PLATE (GR 36) 0' - 6" 0' - 3" 0' - 3" (1/4) 1/4x6x0'-6" PL W/ (2) #3x1'-0". WELD BARS TO PL. PROVIDE SLOTTED HOLE AT SLIP ENDS AND STANDARD HOLES AT FIXED ENDS. CAST PLATE IN PRECAST TREAD AND RISER UNITS WITH SLOTTED HOLE IN DIRECTION OF MOVEMENT. 0' - 6" 0' - 3" 0' - 3" HSS3x3x3/16 BETWEEN JOISTS CL FOLDING PARTITION REINFORCEMENT ANGLE PER TYPICAL DETAIL TYP 0' -0'1"- 1" PLATE PER OTHER DETAILS DROP STEMS IF REQ'D BY PRECAST DESIGN (DAP AT SUPPORT ENDS) 1 SEE NOTE 1 (AT SLIP CONNECTION SIDE ONLY) 3/4"x18"xVARIES PLATE (GR 36) SEE NOTE 1 0' - 1" PER ARCH, TYP CONNECTION DETAIL 'A' S4.2 PER ARCH, TYP 55 S4.2 TYP OPERABLE WALL SUPPORT DETAIL SCALE: 1 1/2" = 1'-0" 56 S4.2 TYP WON-DOOR SUPPORT SCALE: 3/4" = 1'-0" REINFORCEMENT ANGLE PER TYPICAL DETAIL 1/4" PLATE WASHER AND NUT TOP AND BOTTOM OF JOIST CHORD RE: 44/S4.2 FOR BOT OF ASSEMBLY AND BRACING. WON-DOOR TRACK ASSEMBLY BY SUPPLIER © 2012, DLR Group of Missouri inc., a Missouri corporation CA No. 001614, ALL RIGHTS RESERVED. 22 SCALE: 3/4" = 1'-0" JOPLIN, JASPER COUNTY, MISSOURI TYP BEAM SPLICE DETAIL STEEL BEAM 7290 West 133rd Street Overland Park, Kansas 66213 tel: (913)897-7811 21 S4.2 JOIST BEARING BEAM Architecture Engineering Planning Interiors 2-#5 AT EACH SIDE OF OPENING (1 EACH FACE) NOTE: STEEL SUPPLIER TO DESIGN PER LRFD REACTIONS AS SEEN ON PLAN NOTE: 1. ANGLES, WELDS, ETC SHALL BE DESIGNED BY HOLLOW CORE SUPPLIER 2. DETAIL MAY BE MODIFIED FOR SPECIFIC HOLLOW CORE SYSTEM, SUBJECT TO APPROVAL BY THE ENGINEER 3. WHERE OPENINGS ARE ADJACENT TO EXPOSED CEILING AREA, EXERCISE CARE TO MAINTAIN PROPER APPEARANCE BREAKOUT SECTION AT REINFORCING LOCATIONS AND GROUT EDGE CORES SOLID SEE TYPICAL STEEL BEAM CONNECTION DETAIL UNO JOPLIN HIGH SCHOOL CL COL OR FACE OF MASONRY Revisions 1'-0" UNO 1 10-08-12 ADD #3 1 1/2" 13-12102-00 09/10/12 . CONTINUOUS ANGLE SUPPORT FOR HOLLOW CORE BEAM SIZE FOR CONN. SEE SCHEDULE 1/2" OPENING STL BM 6" TOP OF HC EL SEE PLANS 1 1/4" . 6" DECK BEARING BEAM FLOOR FRAMING TYPICAL DETAILS NO BOLTS @3"OC L 1 1/2" 1'-4" 1 1/4" 1 3/4" PLATE EACH SIDE SEE SCHEDULE TOS EL SEE PLANS #4 @ 8'-0" OC CL 6" 5" 2" 2 1/2" 3" 3" 2" 2" POST PER PLAN PER PLAN TOS POST PER PLAN (4) 3/4" DIA A325 BOLTS POST PER PLAN TYPICAL BASE PL TYPICAL BASE PL AT CORNER CONDITION DOOR JAMB SLAB EDGE WINDOW ABOVE 45° TYP SLAB PER PLAN EQ (8'-0"OC MAX) COL PER PLAN 3/16 3" TO CONC SECOND LEVEL PL 1/2" 2 1/2" 2 1/2" 5/16 9" 45° TYP SECTION COL PER PLAN 3/8 SCALE: 3/4" = 1'-0" PL 7/8"x12"x1'-8" 1/4 BASE PL 1 3/4"x20"x2'-2" W/ (6) 1 1/8" DIA A307 (36KSI) ANCHORS (EMBED 3'-0") SLAB PER PLAN COL PER PLAN PL 1/2"x7 3/4"x0'-9", NS & FS 3/8 PL 7/8"x9"x1'-4" FOUNDATION PER PLAN 3/8 PL 1/2"x3 1/4"x0'-9", NS & FS 3/8 BASE PL 1 1/4"x16"x1'-5" W/ (4) 1 1/8" DIA A307 (36KSI) ANCHORS (EMBED 3'-0") 1/4 2' - 0" S5.3 (4) 5/8" DIA A325 BOLTS PL 1/2"x3 1/4"x0'-9", NS & FS SLAB PER PLAN TYPICAL SPACING OF POSTS SECTION 'A' 11 EQ (8'-0"OC MAX) 3/8 5/16 3" 7 1/2" TYP 1/4 2' - 0" CLIP ANGLE, TYP BASE PL 1/2"x6"x1'-2" W/ (2) 5/8" DIA HAS ROD W/ HY-150 ADHESIVE (EMBED 3") COL PER PLAN PL 1/2" 8'-0"OC MAX 6" 3" 3" 1/2" THICK BASE PL 2 1/2" 3/16 3 1/2" 5" 4" 3" 3" 2" 2" 4" 2" 1/2" THICK BASE PL 6" 1' - 2" HSS PER PLAN, TYP TO CONC SECOND LEVEL 2 9" 8" TO CONC FIRST LEVEL SLAB PER PLAN 3/8 1 1/2" NON-SHRINK GROUT 1" NON-SHRINK GROUT 6" 4 1/2" 4 1/2" 4" 4" 7 1/2" ROOFING PER ARCH 1' - 4" 1' - 8" 7 1/2" INSULATION PER ARCH 4" EXT PER ARCH 4" 2 1/2" 6" PILASTER PER PLAN 24 SCALE: 3/4" = 1'-0" S5.3 3 1/2" SECTION SCALE: 3/4" = 1'-0" TOPPING SLAB PER PLAN GROUT COURSE SOLID FULL LENGTH #4 @ 4'-0" OC DWLS TO MATCH VERT WALL REINF 0' - 5" 2'-0" 2'-0" CMU WALL PER PLAN TOPPING SLAB PER PLAN TOPPING SLAB PER PLAN #4 @ 4'-0" OC #4 @ 4'-0" OC 2'-0" 2'-0" 2-#4 CONT 2'-0" STAIR PER SUPPLIER (WHERE APPLICABLE) HOLLOW CORE 0' - 5" TOPPING SLAB PER PLAN 2-#4 CONT 0' - 0" BRG #4 @ 4'-0" OC 2'-0" HOLLOW CORE 2'-0" BOND BM, TYP BOND BM, TYP 0' - 3" BRG GROUT HOLLOW CORE BEARING STRIP 1/8"x2". PLACE 1/2" BACK FROM FACE OF WALL BOND BM, TYP GROUT HOLLOW CORE BEARING STRIP PER HOLLOW CORE SUPPLIER CMU WALL PER PLAN CMU WALL PER PLAN NOTE: RE: TYPICAL DETAILS FOR TYPICAL INFORMATION NOT SHOWN 2'-0" HOLLOW CORE 0' - 3" BRG BOND BM, TYP BOND BM, TYP HOLLOW CORE 31 S5.3 SECTION SCALE: 3/4" = 1'-0" 32 S5.3 SECTION SCALE: 3/4" = 1'-0" 33 S5.3 SECTION SCALE: 3/4" = 1'-0" 34 S5.3 SECTION SCALE: 3/4" = 1'-0" 35 S5.3 SECTION SCALE: 3/4" = 1'-0" 36 S5.3 SECTION SCALE: 3/4" = 1'-0" BENJAMIN TALPOS 10/8/2012 6:17:11 PM C:\Users\BrionP\Documents\9-2013-Revit Projects\Joplin\13-12102-00_central_struct_2012.rvt 1 2 10-08-12 ADD #3 0' - 5" 7290 West 133rd Street Overland Park, Kansas 66213 tel: (913)897-7811 TOPPING SLAB PER PLAN 6" Architecture Engineering Planning Interiors EQ EQ MTL STUDS PER ARCH 6" JOPLIN HIGH SCHOOL CMU WALL PER PLAN #4 @ 4'-0" OC ATTACHMENT, EMBED, & CONNS PER STAIR SUPPLIER (WHERE APPLICABLE) NOTE: RE: TYPICAL DETAILS FOR TYPICAL INFORMATION NOT SHOWN CMU WALL PER PLAN 2'-0" Revisions BRG PL 3/8x6 1/2x0'-8" W/ (2) 1/2" DIA x4" HSA 2'-0" 1'-8" #4 @ 4'-0" OC 1'-8" CUT COURSE AS REQ'D 1 10-04-12 ADD #2 TOPPING SLAB PER PLAN SECTION 1' - 5" 13-12102-00 09/10/12 CMU WALL PER PLAN 3 1/2" COL PER PLAN 5" FLOOR FRAMING SECTIONS 0' - 5" 5" S5.3 INSULATION PER ARCH 0' - 5" EXT PER ARCH COL PER PLAN BOND BM, TYP 0' - 6 1/2" 0' - 1 1/2" 0' - 1 1/2" NOTE: RE: TYPICAL DETAILS FOR TYPICAL INFORMATION NOT SHOWN 2 1/2" 10 1/2" © 2012, DLR Group of Missouri inc., a Missouri corporation CA No. 001614, ALL RIGHTS RESERVED. 23 S5.3 JST PER PLAN 10 1/2" 2' - 2" L6x4x5/16 (LLV) CONT W/ 3/4" DIA EXP BOLTS @ 48"OC (EMBED 4") 0' - 0 1/2" 2 1/2" JOPLIN, JASPER COUNTY, MISSOURI 2 1/2" DECK PER PLAN ANGLE TO JST 1/8 DECK PER PLAN 5/8 BOND BM L6x4x5/16 (LLV) CONT W/ 3/4" DIA EXP BOLTS @ 24"OC (EMBED 4"), TYP (STAGGER ANCHORS HORIZ EA SIDE OF WALL) 'K' SERIES 1/8x2" 'LH' AND 'DLH' SERIES 1/4x3" SPACE AS REQ(D) FOR DIAPHRAGM OR 1'-6" OC MAX PER STEEL SUPPLIER 3/16 EXTEND TO WEB IF COLUMN IS TURNED 90 DEGREES CONN PER JOIST MANUF. SEE TYPICAL CONN. DETAIL ROOFING OR FLOOR 3/16 L4x4x1/4xCONTINUOUS UNO ON PLAN 1 1/2 1 1/2@1'-6" 5/8 STEEL JOIST DECK PER PLAN 'K' SERIES 1/8x2" 'LH' AND 'DLH' SERIES 1/4x3" SPACE AS REQ(D) FOR DIAPHRAGM OR 1'-6" OC METAL DECK TO STL PER PLAN JST BRG EL PER PLAN EXTEND JOISTS 1" MINIMUM BEYOND CL WHEN JOISTS ARE ON ONE SIDE ONLY OR WHEN THEY ARE NOT BUTTED DIRECTLY ACROSS PROVIDE ANGLE @ JOISTS BEARING ON MOMENT FRAME OR BRACED BAYS. L2 1/2x2 1/2x3/16 BETWEEN JOISTS. LOCATE SO THAT DECK CAN BE WELDED TO TOP LEG (AT 5" JOIST SEATS USE L5x5x5/16 IN LIEU OF L2 1/2x2 1/2) 1/4 'K' SERIES 1/8x2" 'LH' AND 'DLH' SERIES 1/4x3" 2@1'-0" METAL DECK STEEL DECK & CONN PER PLAN JST BRG EL SEE PLAN 1/2" 0' - 0 1/2" 'K' SERIES 1/8x2" 'LH' AND 'DLH' SERIES 1/4x3" JST BRG EL SEE PLANS JST BRG EL SEE PLANS STEEL JOIST EXTENDED ENDS STEEL BEAM WHERE SHOWN ON PLANS 3/16 BOND BM, TYP JST OR BM PER PLAN CMU WALL PER PLAN SCALE: 3/4" = 1'-0" S6.1 TYP JOIST BRG @ STL COL STEEL JOIST EXTENDED ENDS 14 SCALE: 3/4" = 1'-0" S6.1 SCALE: 1" = 1'-0" SPACE AS REQ(D) FOR DIAPHRAGM OR 1'-6" OC MAX 'K' SERIES 1/8x2" 'LH' AND 'DLH' SERIES 1/4x3" 3/16 3/16 5/8 TOS EL SEE PLAN HORIZONTAL OR DIAGONAL BRIDGING AS REQUIRED PL 1/4X3XCONT W/ 1/2"DIAX4" HEADED STUDS @ 1'-4 OC 1/2" NOTES: 1. USE ONLY WHERE DUCTS ARE SHOWN BETWEEN JOISTS ON MECHANICAL DRAWINGS. VERIFY LOCATION WITH CONTRACTOR. 2. DO NOT INSTALL DUCTS IN TWO ADJACENT JOIST SPACES. BOND BM CUT BLOCK AS REQD FOR BRG EL OR SLOPE STEEL JOIST BOND BEAM BEARING PL3/8"x0'-8" WITH 2-1/2"Ø x 4" HEADED STUDS @ 5" OC FOR 'K' SERIES. BEARING PL3/4"x 1'-0" WITH 3-1/2"Ø x 4" HEADED STUDS @ 4 1/2" OC FOR 'LH' AND 'DLH' SERIES. WIDTH OF PLATE DETERMINED BY WALL THICKNESS. VERTICAL MASONRY WALL REINFORCING. SEE PLANS AND STRUCTURAL NOTES. PROVIDE STANDARD 180° HOOK AT TOP OF WALL (SKEW AS REQ'D) STEEL BEAM 22 SCALE: 1" = 1'-0" VERTICAL MAS. REINF. SEE PLANS AND STRUCTURAL NOTES . 1/2" STEEL JOIST TYP JOIST BEARING DETAIL 1" S6.1 DECK BRG EL SEE PLANS 1 1/2 DUCTWORK STEEL BEAM 21 MET DECK TYP JST BRG EL SEE PLAN JST BRG EL SEE PLAN S6.1 5/8 SPACE AS REQD FOR DIAPHRAGM OR 1'-0 OC MAX METAL DECK 3/16 1 1/2@1'-6" EDGE OF DECK WHERE OCCURS L2x2x3/16 EACH SIDE 3/16" METAL DECK METAL DECK SCALE: 1" = 1'-0" CONCENTRATED LOAD AT TOP CHORD (>400 LBS) 'K' SERIES 1/8x2" 'LH' AND 'DLH' SERIES 1/4x3" 1/2" MAX 2@1'-0" SEE PLAN 1/2" MAX S6.1 TYP JOIST BEARING DETAIL TYP METAL DECK BEARING DETAIL 23 SCALE: 3/4" = 1'-0" S6.1 TYP BRIDGING INTERRUPTION DETAIL SCALE: 3/4" = 1'-0" 24 S6.1 TYP JOIST BEARING DETAIL STEEL JOIST NOTE: PROVIDE REINFORCEMENT WHEN CONCENTRATED LOAD IS MORE THAN 4" FROM PANEL POINT. 25 SCALE: 1" = 1'-0" S6.1 CONCENTRATED LOAD AT BOTTOM CHORD (>200 LBS) TYP JOIST REINFORCING DETAIL 26 SCALE: 1" = 1'-0" S6.1 TYP DECK BRG WALL DET SCALE: 3/4" = 1'-0" CL BEAM WORKING POINT 1/8 STEEL JOIST 1" MIN 0' - 2" 0' - 0 1/2" MAX OPENING SIZE 1/4 METAL ROOF DECK EACH JOIST 1/8 5/8 X TYP EA END 1 3/8"x1 5/8" UNI-STRUT CHANNEL BETWEEN DECK RIBS 12 'K' SERIES 1/8x2" 'LH' AND 'DLH' SERIES 1/4x3" 1/8 2-L3x3x1/4 TYP EA SIDE 1 2-3/4"Ø A325-N BOLTS ROOF DECK 3/16 1/2"Ø THREADED RODS S6.1 SCALE: 3/4" = 1'-0" S6.1 TYP ROOF OPENING DETAIL 33 SCALE: 3/4" = 1'-0" S6.1 5/8 NOTE: 1. GENERAL CONTRACTOR SHALL VERIFY SIZE AND LOCATION WITH MECHANICAL CONTRACTOR. 2. PROVIDE SEISMIC BRACING IN ACCORD WITH MECHANICAL SPECIFICATIONS AND DETAILS. 3. WEIGHT OF MECHANICAL UNIT EQUAL TO OR LESS THAN 400 LBS/ CHANNEL. STEEL BEAM TYP JOIST BEARING DETAIL 34 SCALE: 1" = 1'-0" S6.1 TYP HANGING MECHANICAL UNIT DETAIL SCALE: 1" = 1'-0" @ 12" OC DECK TO BENT PLATE SLOPE 5/8"Ø THREADED ROD WITH 1/4"x 0'-3" SQUARE WASHER TOP AND BOTTOM MECHANICAL UNIT 5'-0" MAX STEEL JOIST 32 2 STEEL JOIST OR STEEL BEAM 5'-0" MAX TYP BRIDGING DETAIL 1/4" BENT PL L6x6x1/2x0'-3" 1/4 31 1 PL3/4x4x0'-6" STEEL JOIST OR STEEL BEAM JST BRG EL SEE PLANS STEEL JOIST OR BEAM L4x4x3/8 1 PL3/16"x0'-5" x CONTINUOUS 1 1/2 METAL DECK BRIDGING BY JOIST MANUFACTURER. SEE JOIST SHOP DRAWINGS SPACE AS REQ(D) FOR DIAPHRAGM OR 1'-6" OC MAX VARIES STEEL BEAM 1/2" MAX 1/8 MECHANICAL UNIT BM PER PLAN NOTE: 1. GENERAL CONTRACTOR SHALL VERIFY SIZE AND LOCATION WITH MECHANICAL CONTRACTOR. 2. PROVIDE SEISMIC BRACING IN ACCORD WITH MECHANICAL SPECIFICATIONS AND DETAILS. 3. WEIGHT OF MECHANICAL UNIT GREATER THAN 400 LBS/ANGLE OR LESS THAN 700 LBS/ANGLE. 35 S6.1 TYP HANGING MECHANICAL UNIT DETAIL SCALE: 1" = 1'-0" 36 S6.1 SECTION SCALE: 1 1/2" = 1'-0" ROOFING PER ARCH ROOF DECK PER PLAN CL RIDGE PLATE 3/16 TYP 2 3/16 ANGLE PER SECTION WALL WIDTH SEE PLAN TOP OF PARAPET EL SEE PLAN EMBED PER PRECAST SUPPLIER 5/8 1/8 TOP OF PARAPET EL SEE PLAN 2 TYP 2 ANGLE PER SECTIONS WALL WIDTH SEE PLAN SPACE AS REQ(D) FOR DIAPHRAGM OR 1'-6" OC MAX WORKING POINT SPACE AS REQ(D) FOR DIAPHRAGM OR 1'-0" OC MAX 5/8 NOTES: 1. REFER TO ARCH FOR LOCATIONS AND SIZE OF WALL PANELS. RE TYP DET 15/S6.1 FOR ADDITIONAL JST BRACING REQUIREMENTS. 3/16 METAL DECK EMBED PER PRECAST SUPPLIER SPACE @ 4'-0" OC MAX CENTERED ON ANLGE JST BRG EL SEE PLAN HSS TO JST BOT CHORD HSS PER PLAN BEAR ON BOT CHORD OF JST, 3" MIN BEARING 'K' SERIES 1/8x2" 'LH' AND 'DLH' SERIES 1/4x3" 3/16 SCALE: 3/4" = 1'-0" 42 S6.1 TYP PRECAST CONNECTION 43 SCALE: 3/4" = 1'-0" S6.1 1/8 1 1/2 1 METAL DECK X 12 PL3/16"x0'-5" x CONTINUOUS RIDGE JST BRG EL SEE PLANS HSS3 1/2x2 1/2x1/4xCONT - FOR K-SERIES JSTS TYP NS & FS, CLIP TO HSS 0' - 1" 1 SLOPE 0' - 1" 1/4" BENT PL SLOPE JST PER PLAN 12 GA L3x3x3 W/ (4) #10 SCREWS EA SIDE OF HANGER STUDS 3/16 2-12 RIDGE MEMBER PER PLAN STEEL JOIST TYP AUDITORIUM WALL ASSEMBLY CONN SCALE: 3/4" = 1'-0" 44 S6.1 DECK DIRECTION CHANGE DETAIL SCALE: 1" = 1'-0" 45 S6.1 TYP RIDGE DETAIL 46 SCALE: 1" = 1'-0" S6.1 SECTION SCALE: 1 1/2" = 1'-0" ROOFING PER ARCH L4x4x3/8 BRACE HSS4x4x5/16 HSS4x4x5/16 1/4" FULL DEPTH STIFF PL L4x4x3/8 BRACE ROOF DECK PER PLAN HSS4x4x5/16 HSS4x4x5/16 HSS4x4x5/16 HSS4x4x5/16 PL 1/4"x4"x6" , TYP NOTE: COORDINATE AND FIELD LOCATE ALL BRACING ANGLES AND CONNECTIONS TO AVOID INTERFERENCE WITH RIGGING LINE SETS AND LOFT BLOCK CONNECTIONS. BENJAMIN TALPOS 51 S6.1 SECTION SCALE: 3/8" = 1'-0" HSS4x4x5/16 HSS4x4x5/16 HSS4x4x5/16 7290 West 133rd Street Overland Park, Kansas 66213 tel: (913)897-7811 1/4" FULL DEPTH STIFF PL BM PER PLAN, TYP Architecture Engineering Planning Interiors 1 10/8/2012 6:17:18 PM C:\Users\BrionP\Documents\9-2013-Revit Projects\Joplin\13-12102-00_central_struct_2012.rvt S6.1 TYP PRECAST CONNECTION 1 1/2@12 STEEL BEAM INSTALL LIGHT GAUGE BRACING AS REQ'D TO MAINTAIN MAX STUD UNBRACED LENGTH OF 8'-0" STIFFENED SEAT CONN PER STEEL SUPPLIER 41 1/8 MTL STUDS PER ARCH 3/16 EACH JOIST STEEL DECK & CONN PER PLAN METAL DECK PRECAST WALL PER PRECAST SUPPLIER TYP 5/8 SPACE AS REQ(D) FOR DIAPHRAGM OR 1'-6" OC MAX © 2012, DLR Group of Missouri inc., a Missouri corporation CA No. 001614, ALL RIGHTS RESERVED. PROVIDE ANGLE @ JOISTS BEARING ON MOMENT FRAME OR BRACED BAYS. L2 1/2x2 1/2x3/16 BETWEEN JOISTS. LOCATE SO THAT DECK CAN BE WELDED TO TOP LEG (AT 5" JOIST SEATS USE L5x5x5/16 IN LIEU OF L2 1/2x2 1/2) DIAGONAL BRIDGING SCALE: 1" = 1'-0" NOTE: OFFSET JOISTS EA SIDE OF CENTERLINE SHOWN ON PLAN IF MINIMUM BEARING DIMENSION CANNOT BE ACHIEVED. PROVIDE ANGLE @ ALL LOADING BEARING CMU THAT STOPS BELOW STRUCTURAL DECK. L2 1/2x2 1/2x3/16 BETWEEN JOISTS. LOCATE SO THAT DECK CAN BE WELDED TO TOP LEG (AT 5" JOIST SEATS USE L5x5x5/16 IN LIEU OF L2 1/2x2 1/2) CL 5/8 S6.1 16 JOPLIN, JASPER COUNTY, MISSOURI SPACE AS REQ(D) FOR DIAPHRAGM OR 1'-6" OC MAX TYP JOIST BEARING DETAIL 15 JOPLIN HIGH SCHOOL S6.1 13 CL STEEL BEAM AND JOIST REACTION POINT CL STEEL BEAM AND JOIST REACTION POINT Revisions SCALE: 1" = 1'-0" S6.1 TYP DECK TO CMU BRG DETAIL STEEL BEAM STEEL BEAM 1 10-08-12 ADD #3 12 STEEL JOIST STEEL JOIST 13-12102-00 09/10/12 TYP JOIST BEARING DETAIL 11 CL BEAM AND JOIST REACTION POINT PER TYPICAL CONN DETAIL FOR STL BEAM 1 1/2@1'-6" ROOF FRAMING TYPICAL DETAILS CMU WALL PER PLAN STL COLUMN JST OR BM PER PLAN 1 1/2@1'-6" 3/16 S6.1 JST PER PLAN STIFFENED SEAT PER STEEL SUPPLIER COORDINATE W/ JST MANUFACTURER PROVIDE ANGLE @ JOISTS BEARING ON MOMENT FRAME OR BRACED BAYS. L2 1/2x2 1/2x3/16 BETWEEN JOISTS. LOCATE SO THAT DECK CAN BE WELDED TO TOP LEG (AT 5" JOIST SEATS USE L5x5x5/16 IN LIEU OF L2 1/2x2 1/2) STEEL BEAM . CUT COURSE AS REQ'D, TYP OUTLINE OF MECHANICAL UNIT OUTLINE OF MECHANICAL UNIT CENTERLINE OF TYP FRAMING MEMBER. SEE PLAN 6' - 0" MAX A DECK OPENING FRAMING AROUND OPENING IN ROOF DECK PER STRUCTURAL NOTES 3/16 TYP 6' - 0" MAX 3/16 3/16 1/8 OPENING IN ROOF DECK L6x4x3/8 (LLV) (TYPICAL). CENTER ANGLE UNDER CENTER OF MECHANICAL UNIT BASE OR CURB TYPICAL ANGLE UNDER MECHANICAL UNIT L4x4x3/8x0'-6" L4x4x3/8 (TYPICAL). CENTER ANGLE UNDER CENTERLINE OF MECHANICAL UNIT BASE OR CURB TYP 3/16 STEEL JOIST OR BM 2 3/16 10'-0" MAX TYP FRAMING AROUND OPENING IN ROOF DECK PER STRUCTURAL FRAMING NOTES 1/8 10'-0" MAX CENTERLINE OF TYP FRAMING MEMBER. SEE PLAN CENTER LINE OF TYP FRAMING MEMBER SEE PLAN TYPICAL ANGLE UNDER MECHANICAL UNIT L6x4x3/8x0'-6" (LLV) A STEEL JOIST OR BM A 10'-0" MAX 10'-0" MAX 10'-0" MAX NOTE: MAX UNIT WEIGHT = 2000LB 11 S6.2 TYP FRAMING AT SMALL MECHANICAL UNIT 13 SCALE: 1/2" = 1'-0" S6.2 10'-0" MAX A TYP FRAMING AT LARGE MECHANICAL UNIT SCALE: 1/4" = 1'-0" JOPLIN, JASPER COUNTY, MISSOURI JOPLIN HIGH SCHOOL © 2012, DLR Group of Missouri inc., a Missouri corporation CA No. 001614, ALL RIGHTS RESERVED. 7290 West 133rd Street Overland Park, Kansas 66213 tel: (913)897-7811 Revisions 1 10-08-12 ADD #3 13-12102-00 09/10/12 Architecture Engineering Planning Interiors BENJAMIN TALPOS 10/8/2012 6:17:20 PM C:\Users\BrionP\Documents\9-2013-Revit Projects\Joplin\13-12102-00_central_struct_2012.rvt S6.2 ROOF FRAMING TYPICAL DETAILS 1 CL CONNECTION PER PLAN AND OTHER DETAILS SLOT BRACE FOR PLATE NS FS 1/4 3/16 4 PL TO BASE PL WORKING POINT 2" 2" STEEL BEAM. SEE PLAN CL OF BEAM COL TO BASE PL SIZE TO BE 1/16" LESS THAN COLUMN WALL THICKNESS BRACE. SEE BRACING ELEVATIONS 8" N MI FIN FLR EL SEE PLAN 2" EXTEND BASE PLATE AS REQUIRED TO ATTACH TO GUSSET PLATE 2" 12 SCALE: 3/4" = 1'-0" S8.3 13 SCALE: 1" = 1'-0" S8.3 TYP 'X' BRACING DETAIL 14 SCALE: 3/4" = 1'-0" S8.3 5/8" GUSSET PLATE TYP BRACING DETAIL 1/4 15 SCALE: 3/4" = 1'-0" S8.3 K11 K9 1/4 5/8" GUSSET PLATE BRACE CONNECTION DETAIL 16 SCALE: 1" = 1'-0" S8.3 BRACE CONNECTION DETAIL SCALE: 1" = 1'-0" CL STEEL COLUMN SEE TYPICAL BEAM TO COLUMN CONNECTION DETAIL TYP 1/4 3 3 STEEL BEAM 12 S8.3 12 S8.3 5/8" GUSSET PLATE CL OF BEAM HS S8 x8 x5 /16 T= C= 49 k 2" BRACE PER PLAN. SLOT BRACE AT PLATE 8" MIN 2" HS S8 x8x 5/1 6 T= C= 38k WORKING POINT 3 /16 x5 8 x S8 HS 9k =4 C T= HS S8 x8x 5/1 6 T= C= 38k 25 HS S8 x8 x5 /16 T= C= 49 k S8.3 TYP BRACING DETAIL SCALE: 3/4" = 1'-0" K7 THIRD LEVEL 130' - 0" K6 THIRD LEVEL 130' - 0" 15 S8.3 15 S8.3 HS S8x 8x5 /16 HS S8x 8x5 /16 T=C =48 k T=C =38 k /16 8x5 x 8 S HS k =38 C = T 3 12 S8.3 13 S8.3 13 S8.3 HS S8x 8x5 /16 HS S8x 8x5 /16 T=C =48 k 16 x5/ 8x8 S HS k =48 T=C T=C =38 k HS S8 x8 x5 /16 T= C= 48 k SECOND LEVEL 116' - 0" SECOND LEVEL 116' - 0" /16 x5 8 x S8 HS 8k =4 C T= HS S8 x8x 5/1 6 T= C= 55 k HS S8 x8 x5 /16 T= C= 48 k THIRD LEVEL 130' - 0" JOPLIN HIGH SCHOOL 16 x5/ 8 x S8 HS 38k C= = T JOPLIN, JASPER COUNTY, MISSOURI TYP EACH SIDE OF PL 3/16 BRACE ELEVATIONS AND DETAILS 1 LD 90° 1/4 90° 2 LF 8" ANCHOR BOLTS PER SCHED BRACE CONNECTION DETAIL STEEL BRACE. SEE ELEVATION 2" S8.3 TYP BRACING CONNECTION NOTES STEEL BRACE. SEE ELEVATION STEEL BEAM. SEE PLAN 8" 1/4 11 SLOT BRACE AT PLATE 1/2 5/8" GUSSET PLATE STEEL COLUMN. SEE PLAN 2" WORKING POINT HSS4x4x1/4 SLOT BRACE AT PLATE 2" 2" 1/4 90° WORKING POINT 2" NON-SHRINK GROUT 8" WORKING POINT 1/4 TOF EL SEE PLAN STEEL BRACE. SEE ELEVATION NOTES ARE SYMETRICAL ABOUT THIS LINE S RIE VA SLOT BRACE AT PLATE 1/4 2" SLOT BRACE AT PLATE 1/2" GUSSET PLATE CL OF BEAM 1/4 2" S RIE VA STEEL COLUMN. SEE PLAN 8" TY P 5/8" GUSSET PLATE CONNECTION PER PLAN AND OTHER DETAILS S RIE VA 3/16 STEEL BEAM. SEE PLAN 1 1/4 1 MI " N TYP EACH SIDE OF PL CL OF BEAM CL 1/4 1 PL TO COLUMN BRACING CONNECTION NOTES: 1. ALL CONNECTIONS SHOWN ARE SCHEMATIC ONLY. FINAL CONNECTION DESIGN CALCULATIONS AND DETAILING SHALL BE PROVIDED BY THE STEEL FABRICATOR'S ENGINEER. 2. REFER TO PLANS FOR ADDITIONAL SHEAR AND AXIAL REACTIONS NOT SHOWN. 3. ALL CONNECTIONS SHALL BE DESIGNED IN ACCORDANCE WITH AISC LOAD AND RESISTANCE FACTOR DESIGN (LRFD) TO RESIST FACTORED REACTIONS PROVIDED. 4. THE WORKPOINT SHALL BE DEFINED AS THE INTERSECTION OF ALL MEMBER CENTROIDS FRAMING INTO THE JOINT. STEEL SUPPLIER SHALL DESIGN THE CONNECITONS TO TRANSFER ALL FORCES TO THE WORKPOINT. CL CL NOTES ARE SYMETRICAL ABOUT THIS LINE STEEL COLUMN HS S8x 8x5 /16 k =48 T=C 2 10-04-12 ADD #2 /16 8x5 x 8 S HS 7290 West 133rd Street Overland Park, Kansas 66213 tel: (913)897-7811 13 S8.3 14 S8.3 Architecture Engineering Planning Interiors T=C =48 k FIRST LEVEL 100' - 0" Revisions 3 FIRST LEVEL 100' - 0" HS S8x 8x5 /16 13-12102-00 09/10/12 k 55 C= = T 1 09-25-12 ADD #1 HS S8 x8x 5/1 6 T= C= 55 k S8.3 6 5/1 x 8 x S8 HS 3 10-08-12 ADD #3 15 S8.3 T=C =48 k SECOND LEVEL 116' - 0" 43 SCALE: 1/4" = 1'-0" S8.3 LC BRACE ELEVATION SCALE: 1/4" = 1'-0" HS S8 x8x 5/1 6 T= C= 55 k LB K7 K8 2 25 S8.3 HSS 8x8x 5/16 T=C =15k 5/16 8x8x S S H =15k T=C 51 S8.3 BRACE ELEVATION SCALE: 1/4" = 1'-0" 16 x5/ 8 x S8 HS k 55 C= = T HSS 8x8x 5/16 3 13 S8.3 HSS 8x8x 5/16 25 S8.3 T=C =15k 5/16 8x8x HSS FIRST LEVEL 100' - 0" T=C =15k =15k T=C 53 S8.3 BRACE ELEVATION SCALE: 1/4" = 1'-0" HS S8 x8x 5/1 6 T= C= 55 k FIRST LEVEL 100' - 0" 3 13 S8.3 HSS 8x8x 5/16 14 S8.3 FIRST LEVEL 100' - 0" T=C =15k 14 S8.3 14 S8.3 BENJAMIN TALPOS 10/8/2012 6:17:46 PM C:\Users\BrionP\Documents\9-2013-Revit Projects\Joplin\13-12102-00_central_struct_2012.rvt S8.3 BRACE ELEVATION 55 S8.3 BRACE ELEVATION SCALE: 1/4" = 1'-0" 3 © 2012, DLR Group of Missouri inc., a Missouri corporation CA No. 001614, ALL RIGHTS RESERVED. 41 KK KC LC 3 3 3 12 S8.3 12 S8.3 12 S8.3 HS S8 x8x 5/1 6 T= C= 30 k 6 5/1 8x x S8 HS 2k =3 C T= HS S8 x8x 5/1 6 T= C= 30 k 16 x5/ 8 x S8 HS k 30 C= = T HS S8 x8x 5/1 6 T= C= 32 k 6 5/1 x 8 x S8 HS k 30 C= = T HS S8 x8x 5/1 6 T= C= 30 k THIRD LEVEL 130' - 0" THIRD LEVEL 130' - 0" THIRD LEVEL 130' - 0" 15 S8.3 15 S8.3 15 S8.3 HS S8x 8x5 /16 HS S8x 8x5 /16 T=C =30 k HS S8x 8x5 /16 T=C =32 k T=C =30 k 13 S8.3 13 S8.3 13 S8.3 /16 8x5 x 8 S HS k =32 T=C HS S8 x8x 5/1 6 T= C= 30 k /16 8x5 x 8 S HS HS S8 x8x 5/1 6 T=C =32 k k =30 T=C /16 8x5 x 8 S HS HS S8x 8x5 /16 HS S8x 8x5 /16 T=C =30 k k =30 T=C T=C =30 k SECOND LEVEL 116' - 0" SECOND LEVEL 116' - 0" SECOND LEVEL 116' - 0" HS S8 x8x 5/1 6 T= C= 36k HS S8 x8x 5/1 6 T= C= 32 k S8.4 K6 BRACE ELEVATION 35 SCALE: 1/4" = 1'-0" K7 S8.4 K9 BRACE ELEVATION SCALE: 1/4" = 1'-0" K11 2 KF KG 12 S8.3 HSS 8x8x 5/16 45 S8.4 THIRD LEVEL 130' - 0" T=C =15k BRACE ELEVATION SCALE: 1/4" = 1'-0" THIRD LEVEL 130' - 0" K8 16 S8.3 K7 16 S8.3 HS S8 x8 x5 /16 T= C= 74 k /16 x5 x8 S8 HS HSS 8x8x 5/16 k 74 C= T= /16 x5 x8 S8 k 70 HS C= T= HS S8 x8 x5 /16 T= C= 70 k 3 T=C =?k 25 S8.3 SECOND LEVEL 116' - 0" 5/16 8x8x HSS =?k T=C SECOND LEVEL 116' - 0" BENJAMIN TALPOS 10/8/2012 6:17:55 PM 14 S8.3 51 S8.4 BRACE ELEVATION SCALE: 1/4" = 1'-0" Revisions FIRST LEVEL 100' - 0" 14 S8.3 3 15 S8.3 HSS 8x8x 5/16 13-12102-00 09/10/12 =15k T=C 13 S8.3 S8.4 HS S8 x8x 5/1 6 T=C =25 k 6 5/1 x8x S8 HS 5/16 8x8x HSS 25k C= T= HS S8 x8 x5 /16 T= C= 20 k C:\Users\BrionP\Documents\9-2013-Revit Projects\Joplin\13-12102-00_central_struct_2012.rvt T=C =15k 25 S8.3 3 1 3 2 10-04-12 ADD #2 SCALE: 1/4" = 1'-0" 14 S8.3 7290 West 133rd Street Overland Park, Kansas 66213 tel: (913)897-7811 33 FIRST LEVEL 100' - 0" Architecture Engineering Planning Interiors S8.4 FIRST LEVEL 100' - 0" 14 S8.3 14 S8.3 BRACE ELEVATION 3 3 FIRST LEVEL 100' - 0" 31 HS S8 x8x 5/1 6 T= C= 36k 3 10-08-12 ADD #3 HS S8 x8x 5/1 6 T= C= 32 k 50k C= = T 1 09-25-12 ADD #1 16 x5/ 8 x S8 HS 36k C= = T BRACE ELEVATIONS 3 16 x5/ 8 x S8 HS k 32 C= = T JOPLIN HIGH SCHOOL 6 5/1 x8x 8 S HS 53 S8.4 BRACE ELEVATION SCALE: 1/4" = 1'-0" 55 S8.4 BRACE ELEVATION SCALE: 1/4" = 1'-0" 13 S8.3 HSS 8x8x 5/16 T=C =?k FIRST LEVEL 100' - 0" © 2012, DLR Group of Missouri inc., a Missouri corporation CA No. 001614, ALL RIGHTS RESERVED. HS S8 x8x 5/1 6 T= C= 32 k JOPLIN, JASPER COUNTY, MISSOURI LB KA KL KG /16 x5 x8 S8 HS k 25 C= T= HS S8 x8 x5 /16 T= C= 25 k KH THIRD LEVEL 130' - 0" K6 T= C= 94 k SECOND LEVEL 116' - 0" k 94 C= T= 2 2 15 S8.3 SECOND LEVEL 116' - 0" SECOND LEVEL 116' - 0" 12 S8.3 12 S8.3 16 S8.3 HS S8 x8x 5/1 6 T= C= 33 k 14 S8.3 FIRST LEVEL 100' - 0" FIRST LEVEL 100' - 0" 14 S8.3 K7 S8.5 K9 SCALE: 1/4" = 1'-0" K11 1 SECOND LEVEL 116' - 0" SECOND LEVEL 116' - 0" 16 S8.3 2 10-08-12 ADD #3 K6 SCALE: 1/4" = 1'-0" BRACE ELEVATION 7290 West 133rd Street Overland Park, Kansas 66213 tel: (913)897-7811 S8.5 35 Architecture Engineering Planning Interiors SCALE: 1/4" = 1'-0" BRACE ELEVATION Revisions 33 1 09-25-12 ADD #1 S8.5 BRACE ELEVATION 13-12102-00 09/10/12 31 JOPLIN HIGH SCHOOL FIRST LEVEL 100' - 0" HS S8 x8x 5/1 6 T= C= 33 k BRACE ELEVATIONS HS S8 x8x 5/1 6 T= C= 33 k S8.5 14 S8.3 16 x5/ 8 x S8 HS k 33 C= = T k 65 C= T= 13 S8.3 13 S8.3 16 x5/ 8 x S8 HS k 33 C= = T HS S8 x8 x5 /16 T= C= 65 k 2 /16 x5 x8 S8 HS HS S8 x8x 5/1 6 T= C= 33 k JOPLIN, JASPER COUNTY, MISSOURI K5 K11 HS S8 x8 x5 /16 K10 /16 x5 x8 S8 HS K9 16 S8.3 2 BENJAMIN TALPOS 10/8/2012 6:18:02 PM S8.5 BRACE ELEVATION SCALE: 1/4" = 1'-0" 53 S8.5 BRACE ELEVATION SCALE: 1/4" = 1'-0" © 2012, DLR Group of Missouri inc., a Missouri corporation CA No. 001614, ALL RIGHTS RESERVED. HS S8 x8x 5/1 6 T= C= 80 k HS S8 x8x 5/1 6 T= C= 80 k FIRST LEVEL 100' - 0" 14 S8.3 51 6 5/1 x8x S8 HS FIRST LEVEL 100' - 0" k 80 C= T= 6 5/1 x8x S8 HS 14 S8.3 k 80 C= T= C:\Users\BrionP\Documents\9-2013-Revit Projects\Joplin\13-12102-00_central_struct_2012.rvt 2 KH KF KG KE LB LC 2 HSS4x 4x1/4 HSS4 x4x1/4 T=C=3 0k 4x1/4 HSS4x HSS4 x4x1/4 T=C=3 0k 0k T=C=3 T=C=3 0k ROOF LEVEL 144' - 0" HS S8 x8x 5/1 6 T= C= 25 k HS S8 x8x 5/1 6 T=C =25 k 2 /16 x5 x8 S8 HS 13 S8.3 k 30 C= T= HS S8 x8 x5 /16 T= C= 30 k 12 S8.3 HSS4x 4x1/4 0k T=C=3 25 S8.3 2 13 S8.3 T=C=3 0k x4x1/4 4 HSS 25 S8.3 13 S8.3 16 x5/ 8 x S8 HS k 25 C= = T HS S8 x8x 5/1 6 T=C =25 k 16 x5/ 8 x S8 HS k =25 T=C HS S8 x8x 5/1 T= 6 C= 25 k THIRD LEVEL 130' - 0" THIRD LEVEL 130' - 0" THIRD LEVEL 130' - 0" 15 S8.3 15 S8.3 HS S8x 8x5 /16 T=C =50 k 16 S8.3 /16 x5 x8 S8 HS k 90 C= T= 13 S8.3 /16 8x5 x 8 S HS k =25 C = T 2 2 SECOND LEVEL 116' - 0" HS S8x 8x5 /16 T=C =25 k SECOND LEVEL 116' - 0" SECOND LEVEL 116' - 0" FIRST LEVEL 100' - 0" FIRST LEVEL 100' - 0" 15 S8.3 15 S8.3 SCALE: 1/4" = 1'-0" T= C= 70 k 14 S8.3 33 S8.6 BRACE ELEVATION SCALE: 1/4" = 1'-0" 35 S8.6 BRACE ELEVATIONS S8.6 BRACE ELEVATION FIRST LEVEL 100' - 0" BRACE ELEVATION SCALE: 1/4" = 1'-0" JOPLIN HIGH SCHOOL HS S8 x8x 5/1 6 T= C= 70 k HS S8 x8x 5/1 6 31 6 5/1 x8x S8 HS 14 S8.3 k 70 C= T= 6 5/1 x8x S8 HS k 70 C= T= 2 2 JOPLIN, JASPER COUNTY, MISSOURI T= C= 90 k HS S8 x8 x5 /16 HS S8x 8x5 /16 T=C =25 k BENJAMIN TALPOS 7290 West 133rd Street Overland Park, Kansas 66213 tel: (913)897-7811 © 2012, DLR Group of Missouri inc., a Missouri corporation CA No. 001614, ALL RIGHTS RESERVED. 2 10-08-12 ADD #3 Architecture Engineering Planning Interiors Revisions 13-12102-00 09/10/12 1 09-25-12 ADD #1 10/8/2012 6:18:15 PM C:\Users\BrionP\Documents\9-2013-Revit Projects\Joplin\13-12102-00_central_struct_2012.rvt S8.6 1 2 BENT BARS TO MATCH BOND BEAM REINFORCING DEPTH 3. MECHANICALLY VIBRATE GROUT. 4. SEE TYPICAL MASONRY BEAM/ LINTEL BEARING DETAIL FOR BEARING. SEE PLANS CUT OUT TOP 4" OF WEBS @ TOP OF COURSE SHEAR REINFORCING WHERE INDICATED. HOOK AROUND HORIZONTAL STEEL TOP AND BOTTOM. (NOT TYPICALLY REQD) 7 253/256" CL EMBED 1" CLR EMBED PL3/8x3x0'-8" WITH 2-5/8Øx5" HEADED STUDS 4" OC. HOT DIP GALVANIZED AFTER FABRICATION. SPACE EMBEDS @ 4'-0" OC 1/4 3/16 1/2" PLATE 1/2" PLATE 1/2" MASONRY LINTEL ML-3 ML-4 16" DEEP BOND BM W/ 2-#5 T&B 6'-0" ≤ L < 9'-4" ML-5 ML-6 24" DEEP BOND BM W/ 2-#5 T&B BOND BM 9'-4" ≤ L < 11'-4" W8X21 W8X21 PROVIDE 5/16" BOT PLATE AS REQD STL LINTEL BM 11'-4" ≤ L < 13'-4" W16X31 W16X31 PROVIDE 5/16" BOT PLATE AS REQD W24X55 13'-4" ≤ L < 20'-0" W24X55 PROVIDE 5/16" BOT PLATE AS REQD 8". TYP 1/8 1 1/2 L2 1/2X2 1/2X3/16 1 1/8 1 (MIN) 1 1/2 1 3/16 TYP 1" CLR TYP 1/4" THICK BENT PL OR ANGLE. PROVIDE 3" MIN BRG AT VERT FACE 1/8 1 (MIN) 1 1/2 3/16 3 L3X3X1/4X0'-4 TYP 3/16 3 CMU WALL BEYOND DECK PER PLAN A B PARTITION PARALLEL TO JST L3X3X1/4X0'-4 S9.2 TYP 3/16 BOND BM REINF W/ 2-#5 CONT SCALE: 3/4" = 1'-0" S9.2 TYP PARTITION WALL BRACING DETAIL 34 SCALE: 3/4" = 1'-0" S9.2 L3x3x1/4x0'-4" @ 4'-0" OC MAXIMUM STEEL BEAM PROVIDE WEDGE SHIM PLATES UNDER FULL BEARING AREA WHEN SLOPE EXCEEDS 1/2:12 2- 3/4"Øx1'-3" HEADED ANCHOR BOLTS CENTERED IN 3" LONG SLOTTED HOLE IN BEAM FLANGE. TIGHTEN NUTS FINGER TIGHT. STEEL BEAM AT MASONRY WALL 42 SCALE: 1" = 1'-0" S9.2 SCALE: 1" = 1'-0" PARTITION WALL NOTES: 1. THIS DETAIL IS TO BE USED ONLY IF INTERSECTING SUPPORT WALL EXCEEDS A SPACING OF 18'-0". 2. INTERSECTING WALL MUST BE 4'-0" MINIMUM IN LENGTH TO BE CONSIDERED A SUPPORTING WALL. BENJAMIN TALPOS TYP PARTITION WALL BRACE DETAIL TO WALL SCALE: 3/4" = 1'-0" 2. PROVIDE CONT 10 GA. PLATE, CONTINUOUS ANGLES, AND SCREWS @ 2'-0" OC AT EXPOSED AREA VERTICAL WALL REINFORCING SEE PLANS AND STRUCTURAL NOTES METAL DECK (DIRECTION VARIES) 43 S9.2 1 STEEL BEAM 1'-4" MIN NON-LOAD BEARING CMU WALL TO STRUCTURE 44 SCALE: 1" = 1'-0" S9.2 1 24" OC 3 32" OC 3 48" OC 2 8" MIN NOTES: 1. 2. 3. 4. LOAD-BEARING WALLS: LOCATE BETWEEN JOISTS AS SHOWN. IF OPENINGS MUST BE UNDER JOIST, TOP OF OPENING SHALL BE A MINIMUM OF 1/2 OF THE OPENING WIDTH + 8 INCHES BELOW THE JOIST BEARING OR CONTACT THE ENGINEER. SEE "TYPICAL MASONRY LINTEL DETAIL, SCHEDULE" FOR LINTEL REQUIREMENTS. WHERE VENEER OCCURS, PROVIDE SUPPORT PER TYPICAL LINTEL DETAILS. GENERAL CONTRACTOR SHALL COORDINATE LOCATION OF OPENINGS WITH MECHANICAL, ELECTRICAL AND OTHER CONTRACTORS BEFORE CONSTRUCTING WALLS. TYP MECH PENETRATION IN CMU 26 SCALE: 1/2" = 1'-0" S9.2 0' - 8" PROVIDE LONG SLOTTED HOLES IN BM FLANGE 1" NON-SHRINK GROUT, MIN 2' - 0" MIN 2 BRG UNO FULL HT REINF JAMB PER CMU JAMB SCHEDULE STL BM BOT PL SEE PLANS 1' - 4" MIN 2' - 0" MIN, UNO EXTENSION 8" TYP & 12" WHEN BRICK RETURNS & 1'-2" WHEN CAVITY & BRICK RETURNS . 0' - 4" FILL CAVITY WITH GROUT FULL HEIGHT IF BRG PL EXTENDS OVER CAVITY NOTE: FILL ALL CELLS WITH GROUT IN SHADED AREA 0' - 0 1/4" CLR PROVIDE LONG SLOTTED HOLES IN BM FLANGE BRG PL BOTTOM PLATE NOTES: 1. STOP PLATE AT EDGE OF OPENING WHEN NO CJ 2. EXTEND PLATE TO END OF BEAM WHEN THERE IS AS OFFSET CJ ABOVE THE OPENING. 3. NOTCH PLATE AROUND BRICK WHEN CJ IS AT EDGE OF OPENING IN BRICK AND OFFSET IN BLOCK. TYP STEEL LINTEL BEARING ON MASONRY SCALE: 3/4" = 1'-0" LOAD BEARING WALL OR NON-LOAD BEARING WALL 1" NON-SHRINK GROUT MIN BOND BEAM TYP PARTITION WALL BRACING DETAIL 35 S9.2 2- NO 12x3/4" SCREWS TIGHTENED TO A TORQUE OF 60 IN-POUNDS AT ROOF DECK AND FLOOR DECK PRIOR TO CONCRETE PLACEMENT. 2-3/16"Ø x 1 5/8" SCREW ANCHORS AT FLOOR DECK WHERE SCREWS FASTEN TO CONCRETE FILL ALL CELLS WITH GROUT IN SHADED AREA 48" OC 8" MIN SCALE: 1" = 1'-0" #4x2'-6" W/ STD 180 DEGREE HOOK @ EACH BOLT SCALE: 3/4" = 1'-0" 1'-4" MIN 2 BRICK WHERE OCCURS TYP PARTITION WALL BRACING DETAIL DECK BRG EL VARIES 0' - 4" 3/16 10'-0" MAX S9.2 2-#5x4'-0" LONG IN 8" DEEP BOND BEAM CENTERED UNDER BEAM BEARING NOTES: 1. SEE ARCHITECTURAL PLANS FOR WALLS TO STRUCTURE. 1 1/2" 1 BOND BM, TYP 51 2 LAYERS OF 15 POUND BUILDING PAPER STEEL BEAM AT MASONRY WALL BOND BM, TYP L3x3x1/4 W/ (1) 3/4" DIA EXP BOLT (EMBED 5"), TYP 2- 3/4"Øx1'-3" HEADED ANCHOR BOLTS CENTERED IN 3" LONG SLOTTED HOLE IN BEAM FLANGE. TIGHTEN NUTS FINGER TIGHT. 1" NON-SHRINK GROUT MINIMUM 1/2" NOTE: PROVIDE TOP CONNECTIONS WITHIN 2'-0" EACH SIDE OF VERTICAL CONTROL JOINTS. BEARING PLATE 1/2"x7"x0'-7" UNO ON PLANS CENTER ON WALL UNO L4x4x1/4 @ 8'-0"OC MAX EXCEPT WHERE INTERSECTING WALLS OCCUR. PROVIDE BRACE WITHIN 1'-0" EA SIDE OF CJ LOAD BRG WALL OR LATERALLY BRACED PARTITION WALL 10/8/2012 6:18:21 PM C:\Users\BrionP\Documents\9-2013-Revit Projects\Joplin\13-12102-00_central_struct_2012.rvt 5/8"x5"x1'-0" LONG BEARING PLATE @ 8" CMU WALL 5/8"x9"x1'-0" LONG BEARING PLATE @ 12" CMU WALL 5/8"x7"x1'-0" LONG BEARING PLATE CENTERED ON WALL, UNO 2-#5x4'-0" LONG IN 8" DEEP BOND BEAM CENTERED UNDER BEAM BEARING S9.2 2 129/256" WHERE SMALLER BEAM FRAMES INTO THE SAME LOCATION, SPLICE INTO LARGER BEAM. 1" NON-SHRINK GROUT MINIMUM 41 1 3/256" CLR 1" CLR STEEL BEAM 32" OC 2-3/4" DIA x 1'-3" HEADED ANCHOR RODS & WASHERS 2'-0" UNO CONTINUOUS BOND BEAM 2 BRG PL 1/2x7x0'-7" UNO ON PLANS FINGER TIGHTEN NUTS AND UPSET THREADS - TYPICAL UNO 3/16"x6"xLENGTH AS REQUIRED WITH TWO SCREWS EACH END WHERE DECK RIBS ARE PARALLEL TO WALL 24" OC TYP CMU JAMB SCHEDULE ADD'L REINF TO MATCH WALL REINF BELOW BRG PL 33 1" CLR 1 BOTT DR TOP PL WHERE REQ'D L6x4x3/8 @ 8'-0"OC CMU WALL REINF PER PLAN NOTE: PROVIDE TOP CONNECTIONS WITHIN 2'-0" EACH SIDE OF VERTICAL CONTROL JOINTS. CMU WALL REINF PER PLAN TYP PARTITION BRACING DETAIL 2 LAYERS OF 15 POUND BUILDING PAPER 48" OC STL BM WITH 3/4" DIA HSA @24" OC MAX IN BOND BEAM PER SCHEDULE. (NOT REQD WHEN LINTEL DIRECTLY SUPPORTS DECK) BM PER PLAN, TYP 1/4 BOND BM NOTES: 1. WALLS SHALL BE LATERALLY SUPPORTED AT A MAXIMUM SPACING OF 8'-0 BY PERPENDICULAR WALLS OR BRACING AS SHOWN. CONTINUOUS BOND BEAM 25 DECK PER PLAN 1/4" THICK BENT PL OR ANGLE. PROVIDE 3" MIN BRG AT VERT FACE 2. SEE ARCHITECTURAL DRAWING FOR PARTITION WALLS. 3. PROVIDE TOP CONNECTIONS WITHIN 2'-0" EACH SIDE OF VERTICAL CONTROL JOINTS. 31 8" DEEP BOND BM W/ 2#4 T&B L3X3X1/4X0'-4 PARTITION PERP TO JST 1 EQ BOND BEAM NOTES: 1. FOR EACH REINF CELL, PROVIDE SAME SIZE AND QTY OF BARS PER CELL AS NOTED FOR WALL WHICH OPENING IS LOCATED IN. 2. ALL JAMBS SHALL BE SOLID GROUTED AND REINFORCED FULL HEIGHT. SCHEDULE DENOTES NO. OF 8" LONG REINF CELLS. 3. JAMB REINFORCING APPLIES TO ALL OPENINGS. SEE OTHER DETAILS. TO STEEL PER PLAN TO STEEL PER PLAN BOND BM REINF W/ 2-#5 CONT BOND BM 32" OC OPENING OPENING S9.2 BM PER PLAN TYP 1 > 8'-0" TO ≤ 12'-0" L4x4x1/4 @ 8'-0"OC 0' - 1" CLR TYP 24" OC FINGER TIGHTEN NUTS & UPSET THREAD, TYP UNO MET DECK STL JST L2 1/2X2 1/2X3/16 EXTEND UNDER JSTS L2 1/2X231/2X3/16 (MIN) ≤ 4'-0" EQ NO. OF REINFORCED CELLS EACH JAMB OPENING SCALE: 1" = 1'-0" S9.2 WALL REINF SPACING > 4'-0" TO ≤ 8'-0" TYPICAL MASONRY OPENING 24 SCALE: 1" = 1'-0" MET DECK STL JST 4". SEE TYP CMU JAMB SHEDULE FOR NO. OF VERT CELLS TO BE REINFORCED. FULL HEIGHT, GROUT SOLID, TYP OPENING LINTEL SCHEDULE TYP MASONRY LINTEL BRG PL 3/16"X4"X4" LINTEL REINF - GROUT SOLID PER LINTEL SCHED SEE TYP LINTEL BRG DETAILS FOR BEARING CONDITIONS. 1. ALL OPENINGS REQUIRE A LINTEL. THE CONTRACTOR SHALL COORDINATE ALL OPENING AND PENETRATION LOCATIONS WITH OTHER CONSULTANTS' WORK AND REFER TO THIS SCHEDULE FOR LINTEL SIZES. 2. BOND BEAM REINFORCING SHALL BE CONTINUOUS, WITHOUT SPLICES. 3. DO NOT LOCATE CMU CONTROL JOINTS WITHIN OPENING OR JAMB EXTENTS. 4. STEEL LINTEL BOTTOM PLATES SHALL BE 1" LESS THAN THE NOMINAL WIDTH OF WALL (INCLUDES MASONRY VENEER). 5. STEEL LINTELS SHALL HAVE 5/8" DIA X 6" HEADED ANCHOR STUS @24" OC. INTO AN 8" DEEP BOND BEAM W/ 2#4 T&B. 6. REFER TO OTHER TYPICAL DETAILS FOR FURTHER INFORMATION. 7. SCHEDULE IS SUPERCEDED WHERE LINTEL SIZES ARE SPECIFICALLY NOTED ON PLANS. OPENING WIDTH STEEL JOIST 48 BAR DIA OR 2'-0" MIN, TYP NOTE: STEEL LINTEL 1" CLR 21 4'-0" ≤ L < 6'-0" VERTICAL PL5/16x6xCONTINUOUS WITH BOTTOM PL5/16xCONTINUOUS UNO HOT DIP GALVANIZED AFTER FABRICATION. 3/16 S9.2 HOOK WALL VERTS ABOVE INTO BOND BEAM WITH 180 DEG HOOK PLATE SHALL BE HOT DIP GALV WHEN IN EXTERIOR WALLS 1/2" 10" OR 12" CMU COMMENTS 8" DEEP BOND BM W/ 2-#4 T&B BOTT PL EL SEE PLANS BOND BM W/ REINF SEE PLANS 8" CMU ML-2 3@12 BOTT EL SEE PLANS SPAN TABLE ML-1 BOT PL 5/16", UNO ON PLANS SCALE: 3/4" = 1'-0" S9.2 JAMB REINFORCEMENT SCHEDULE 0' < 4'-0" ADJUSTABLE TRIANGLE MAS ANCHORS @ 8" OC VERT @ 2'-0" OC HORIZ CMU OPEN END UNITS 5. HORIZONTAL REINFORCEMENT SHALL NOT BE SPLICED. 6. 'T' PLATE TO STOP AT EDGE OF OPENING. SEE PLANS SCALE: 1 1/2" = 1'-0" 2-3/4"Ø x1'-3" HEADED ANCHOR BOLTS AND WASHERS. PROVIDE 3" LONG SLOTTED HOLES IN BEAM FLANGE TYP BEARING STEEL ON MASONRY SCALE: 3/4" = 1'-0" © 2012, DLR Group of Missouri inc., a Missouri corporation CA No. 001614, ALL RIGHTS RESERVED. 2. MONOLITHICALLY GROUT BOND BEAM AND ALL CELLS SOLID. GROUTING SHALL HAVE NO VERTICAL OR HORIZONTAL COLD JOINTS FULL HEIGHT AND LENGTH OF LINTEL INCLUDING END BEARINGS. BRICK AS REQD SEE PLANS S9.2 TYP MASONRY LINTEL BRG 16 JOPLIN, JASPER COUNTY, MISSOURI 1-#4 WHERE SHEAR REINFORCING REQUIRED (ALT HOOK) SCALE: 3/4" = 1'-0" S9.2 TYP INTERSECTION REINF DETAIL 2 10-08-12 ADD #3 1. PROVIDE SHORING UNDER BEAM FOR A MINIMUM OF 7 DAYS AFTER GROUTING LOCATE @ CL OF WALL UNO ON PLANS 15 0' - 8" 2' - 0" MIN, UNO 7290 West 133rd Street Overland Park, Kansas 66213 tel: (913)897-7811 VENEER AS REQD SEE PLANS NOTE: TYP BOND BEAM DETAIL 14 SCALE: 3/4" = 1'-0" JAMB REINF PER SCHEDULE Architecture Engineering Planning Interiors S9.2 CORNER DETAIL JOPLIN HIGH SCHOOL SCALE: 3/4" = 1'-0" S9.2 TYP LINTEL/BOND BM @ INTERSECTION B Revisions SCALE: 3/4" = 1'-0" 13 STEP DETAIL 1 10-04-12 ADD #2 TYP MASONRY WALL REINF PLACEMENT 12 A 'T' INTERSECTION 13-12102-00 09/10/12 TYP MASONRY CJ DETAIL CORNER RAKED CONTROL JOINT WITH SEALANT MASONRY TYPICAL DETAILS BLDG PAPER ONE SIDE & GROUT FULL STD 90 DEGREE HOOK, TYP S9.2 NOTES: 1. SEE PLANS AND STRUCTURAL NOTES FOR BAR SIZES. 2. LOCATE REINFORCEMENT AT ALL CORNERS, EACH SIDE OF OPENINGS AND CONTROL JOINTS, AND AT SPACING SHOWN ON PLANS AND STRUCTURAL NOTES. 3. PROVIDE WIRE REBAR POSITIONERS TO HOLD BARS IN PLACE SPACE VERTICALLY @ 32"OC MAXIMUM (2 PER GROUT LIFT). 0' - 8" BRG MIN, UNO CL OF BM LOCATE @ CL OF BLK UNO ON PLANS S9.2 B 0' - 1" CLR 11 BARS @ EDGE SHELF ANGLE WHERE INDICATED MESH WALL TIE (1/2"x16 GA). 4"x8" @ 16" OC SEE PLANS OPTION B BREAK OUT FACE SHELLS AND GROUT SOLID, TYP AS SHOWN 1 0' - 0 1/2" OR 5/16" A 2 BENT BAR TO MATCH BOND BEAM REINFORCING W/ LINTEL SCHED BAR @ CENTER MAX. FACE SHELL THICKNESS = 1 3/8" @ 8" WIDE UNITS VERIFY DEPTH PROVIDE REINF EACH SIDE OF CJ, SEE STRUCT. NOTES FOR SIZE 3/4" CLR TYP JOINT SEALANT, PER SPECIFICATIONS EQ OPTION A 1 1/2" CLR . MASONRY WALL REQ(D) SPLICE SEE SCHED FOR DEPTH REQ(D) SPLICE 2' - 0" 48 BAR DIA PR 2'-0" MIN, TYP BOND BEAM LAP MASONRY WALL CMU LINTEL VERTICAL MASONRY REINFORCING. SEE PLANS AND STRUCTURAL NOTES . OPEN END MASONRY UNITS AT MASONRY LINTEL 0' - 0 1/2" OR 5/16" EQ HORIZ. REINF (WHERE REQ'D) LOCATE INSIDE AND NEXT TO VERT 2' - 0" , UNO CONTROL JOINT KEY AS SPECIFIED TYP JOINT SEALANT, PER SPECIFICATIONS 3/4" CLR HORIZ REINF (WHERE REQ'D) WHERE SINGLE BAR IS REQ'D, LOCATE NEXT TO VERT FILL WITH GROUT AS SPECIFIED 1 1/2" CLR MAS CONTROL JOINT (SASH) BLOCK EXTEND REINF PER TYP CMU OPENING DETAIL