Quietline Manual
Transcription
Quietline Manual
KEETON INDUSTRIES AERATION OWNER’S MANUAL POND & LAKE 1 TABLE OF CONTENTS FIND IT FAST 3 CONGRATS! IMPORTANT 17 SOLAER INSTALLATION BATTERY CONNECTION 4 SYSTEM CHECKLIST MAKE SURE EVERYTHING IS PRESENT 18 SOLAER INSTALLATION BATTERY CONNECTION DIAGRAM 5 LEVEL-AER INSTALLING 19 SOLAER INSTALLATION BATTERY CONNECTION DIAGRAM 6 SECURITY KIT INSTALLATION 20 SOLAER INSTALLATION READING THE INDICATORS 7 QUIET LINE INSTALLATION EQUIPMENT AND PROCEDURE 21 SOLAER INSTALLATION PRO STAR CONTROLLER 8 QUIET LINE INSTALLATION ELECTRICAL HOOKUP 22 SOLAER BATTERY BATTERY CHARGING 9 QUIET LINE INSTALLATION SETTING TIME, DATES AND CYCLES 23 SOLAER TIMER SETTING TIME, DATE AND CYCLES 10 QUIET LINE INSTALLATION DIFFUSER ADJUSTMENT 24 SOLAER COMPRESSOR MAINTENANCE AND REPAIR 11 QUIET LINE COMPRESSOR MAINTENANCE AND REPAIR 25 SOLAER COMPRESSOR MAINTENANCE AND REPAIR 12 QUIET LINE COMPRESSOR EXPLODED DIAGRAM QUIET LINE COMPRESSOR EXPLODED DIAGRAM 26 WARRANTY COVERAGE AND POLICIES 27 TROUBLESHOOTING QUIETLINE AND SOLAER SOLAER INSTALLATION EQUIPMENT AND SOLAR PANEL 28 SOLAR AERATION MONITORING SYSTEM TROUBLESHOOTING THE SOLAR PANELS 13 14 15 SOLAER INSTALLATION 29 BENEFICIAL MICROBES TILTING THE SOLAR PANEL FOR SOLAR SOUTH IMPROVE WATER QUALITY 16 SOLAER INSTALLATION EQUIPMENT AND PROCEDURE 2 31 REGISTRATION CARD DETACH AND MAIL OR GO ONLINE CONGRATS! IMPORTANT Congratulations on your purchase of a Keeton Industries Lake Bed Aeration System! In the following pages you will find detailed information about the system you have purchased. These include a system checklist, installation instructions, required maintenance, warranty information and much more. IMPORTANT. This equipment was thoroughly inspected and carefully packaged in our facility. Upon acceptance by the carrier (UPS, USPS, Motor Freight or Other) they assume responsibility for the goods in transit and their ultimate safe arrival. Should you receive your shipment in a damaged condition, either apparent or concealed; a damage claim must be made by you, the customer, directly with the shipping carrier. Keeton Industries cannot make this claim for you. APPARENT LOSS OR DAMAGE Should visual inspection upon receipt of goods show loss or damage, it must be noted on the freight bill, express receipt, or UPS driver’s record and signed by the driver or agent. Failure to do so will result in the carrier refusing to honor your damage claim. The carrier will furnish you the necessary form(s) for filing a claim should they be needed. CONCEALED DAMAGE When damage is not apparent until the equipment is unpackaged, a claim for concealed damage is to be made to the carrier. When damage is discovered, make a written or phone request to the carrier for inspection. You must make this request for inspection within fortyeight (48) hours of delivery. Immediately inspect all packages for exterior and interior damage upon receipt and make any claims as soon as possible. NOTICE There are no returns on Custom Designed equipment or Manufactured equipment for specific applications. Keep all cartons and packaging material to show the inspector. The carrier will furnish you with an inspection report and necessary forms for filling a concealed damage claim, since such damage is the carrier’s responsibility. RETURNS If you are unhappy with your order for any reason, Keeton Industries will gladly exchange items; issue credit or refund the purchase price to you (less restocking charges) within 7 days of receiving the product. In all cases, return freight costs are the responsibility of the customer. Please call or write for Return Authorization Number so that we may handle your return as quickly and efficiently as possible. We will not accept any returned merchandise without a Return Authorization Number being displayed on the package. 3 SYSTEM CHECKLIST MAKE SURE EVERYTHING IS PRESENT INSIDE THE CABINET: 1. Tork Timer 2. Adjustable Manifold 3. Sound Reduction Foam 4. Cooling Fan 5. Rocking Piston Compressor 6. Air Intake Filter Our 100% recycled plastic cabinets, acoustical foam and sound dampening isolators work to eliminate escaping sound. The high capacity cooling blower works to maintain proper temperatures for optimum performance even in the most inhospitable locations. A digital timer offers flexibility and allows the system to run during certain times, such as at night only. The systems also include a fully adjustable aluminum distribution manifold. THE DIFFUSER Our aeration systems use Duraplate™ self-cleaning, non-clogging membrane diffusers. Due to their design, the Duraplate diffusers will not need to be removed for cleaning and are backed by a lifetime warranty. The diffuser shell is also fishhook resistant, making them an ideal choice for fishing ponds and lakes. THE TUBING (OPTIONAL) Keeton Industries Alpine™ self-weighted feeder tubing offers the perfect balance of flexibility and weight. Alpine tubing sinks directly to the bottom and will not kink or break. Alpine tubing is a high density, flexible tubing that features a thick, ¼” sidewall. Available in 100’ rolls and 500’ reels. 4 LEVEL-AER INSTALLING EQUIPMENT NEEDED SHOVEL LEVEL LEVEL-AER PAD • • • STEP 1. Find a suitable location for the aeration unit. STEP 2. Using the shovel, dig a flat surface to place the level-aer pad. STEP 3. Use the level to make sure the level-aer pad is level. If it’s not level, continue to use the shovel to flatten the surface. This will ensure a secure surface for the aeration unit. 5 SECURITY KIT INSTALLATION EQUIPMENT NEEDED KEETON SECURITY KIT LEVEL-AER PAD • • STEP 1. Complete the Level-Aer Installation found on page 5 of this manual or simply place the aeration unit in its desired location. STEP 2. Place the anchor rod inside of the anchor bullet. Locate the placement for the anchor bullet and drive the bullet into the ground with the anchor rod, pull the cable to turn the bullet in place. figure 1 STEP 3. Take the cable and pull it through the loop located on the bottom of the aeration unit and secure it with the padlock. figure 1 6 KEETON SECURITY KIT QUIET LINE INSTALLATION EQUIPMENT AND PROCEDURE EQUIPMENT NEEDED SCREW DRIVER TUBING CUTTER WRENCH SHOVEL A BOAT WITH A MOTOR OR OARS • • • • • CAUTION: It is dangerous to work in and around open water. Please wear safty equipment when using tools, shovels, etc. and be sure to wear a life vest while operating a boat. Be careful of ice covered lakes in the winter, aeration systems weaken the ice and it is never safe to walk on aerated lakes. STEP 1. Open the lid and inspect all equipment to ensure no evident damage has occurred during shipping. You will find all necessary installation hardware enclosed within the cabinet or in a separate package that was shipped with this unit. Your cabinet is 100% recycled plastic. STEP 2. All Cabinets are designed to be mounted on the provided legs. Make sure the system is level and firmly sitting on all four (4) legs. Systems can either be placed on a Level-aer Equipment Pad, concrete pad, concrete blocks or mounted directly on the ground. Systems can be fastened down so they are securely in place with a Keeton Security Kit (found on page 6) or the Owner can purchase their own security materials. STEP 3. Alpine Self-Weighted tubing requires no additional weight and will sink gently to the bottom by itself. Stainless steel hose clamps and tubing couplers are provided for splicing tubing together and attaching the tubing to the Aeration Unit as well as the diffuser(s). STEP 4. Connect the Alpine tubing to the airline from the compressor housing. Put the roll of tubing in the boat. As you proceed to the desired diffuser location, feed the tubing over the side of the boat. When you reach the desired diffuser location, connect the Alpine tubing to the diffuser inlet, secure with stainless steel clamp and lower it into place. Watch the Video! 7 QUIET LINE INSTALLATION ELECTRICAL HOOKUP Electrical Shock Hazard Disconnect electrical power supply cord before installing Service Kit. STEP FIVE. Electrical Hookup: After the cabinet has been set in place and the feeder tubing and diffuser If product is hard wired into system, disconnect have been installed the system is ready to have the electricity hooked up. all or valves inside the electrical power at theMake circuitsure breaker fuse box cabinet are wide open and the timer is placed in the off before position. MostService systems installing Kit. will come with a standard electrical plug (120V/60Hz units) and can be plugged into any outlet pressure. with GFCI protection. All Vent all electrical air lines to release other systems will require a Professional Electrician to power the system (Provided by the Owner). Once Failure to follow these instructions can result in the system is hooked up to electrical power it is now ready forfire start up. death, or electrical shock. Minimum gage for extension cords Amps Volts 120v 240v 0-2 2-3 3-4 4-5 5-6 6-8 8-10 10-12 12-14 14-16 16-18 18-20 Length of cord in feet 25 50 50 100 100 200 150 300 200 400 250 500 300 600 400 500 800 1000 18 18 18 18 18 18 18 16 16 16 14 14 18 18 18 18 16 16 14 14 12 12 12 12 18 16 16 14 14 12 12 10 10 10 8 8 16 14 1 4 1 2 1 2 1 0 10 8 8 8 8 6 16 14 12 12 10 10 8 8 6 6 6 6 14 12 12 10 10 8 8 6 6 6 4 4 14 12 10 10 8 6 6 6 6 4 4 4 12 10 10 8 8 6 6 4 4 4 2 2 12 10 8 8 8 6 4 4 2 2 2 2 Grounded Plug Grounding Pin 120-volt grounded connectors shown. 220/240-volt grounded connectors will differ in shape. Grounded Outlet EF DEmake S C R IP Tsure IO N the valves on the manifold Q T Y 75R 6are STEP SIX. Start Up: The system is now ready for start up. RAgain fully opened. To manually start and/or run your system, use the timer’s “On Auto Off” switch 4located at BB516C 1 C AP S C R E W the top left of the timer. The compressor and cooling fan2should It will take a little time before BB570 C A Pturn S C R Eon. W 4 3 Hrun E A D with the valves fully open for 1 a few A P 200A air can be seen bubbling up from the diffusers. Let the system 4Δ H E A D O -R IN G 2 A P 201A minutes, then visually inspect the diffuser locations to ensure each diffuser is operating (See Step 8A-P 110 5 VAL V E L IMIT E R 2 Diffuser Adjustment). 6Δ L E A F VA LV E 4 A F 817 7 8 9 10 Δ 11 Δ use12the Δ 13 14 Δ 15 15A VA LV E P L AT E VA LV E R E TA IN E R VA LV E S C R E W C Y L IN DE R O -R IN G C Y L IN DE R timer R E TA IN“ON/OFF” ER SCREW R E TA IN E R P L AT E P IS TO N C U P FA N FA N - L E A D E N D DO NOT UNPLUG THE SYSTEM WHILE IT IS RUNNING If you must turn the system off, 8 button. 2 2 2 2 2 4 2 2 1 1 A P 101A A F 819A B B 330A AT 276 A P 275 AT 283 AT 566A AT 280 A P 108A A P 108 QUIET LINE INSTALLATION SETTING TIME, DATE AND CYCLES STEP SEVEN: THE TIMER NOTE: All timers are pre-set on your Quiet Line™ Aeration System to run 20 hours, 2:00 p.m. to 10:00 a.m. This is our reccomended time of use. Use the below information if you would like to increase or decrease according to the vitality of your pond or lake. STEP 1. SETTING THE TIMER. Set the “RUN” switch to the button. Push the button to set the day Minimum gage“1…7” for extension cords (Ex:Volts Sunday = 1, Monday Amps Length of cord in feet =2, Etc.) Use 120v the “h”25and set300 the400 current 50 “m” 100buttons 150 200 to250 500 time 50 100 200 300 400 500 600 800 1000 Slide240v “RUN” switch back to the center position (SEE A). • • • • 0-2 2-3 18 18 18 18 18 16 16 14 16 14 14 12 14 12 12 10 A 12 10 STEP 2. SETTING THE16ON1AND 3-4 18 18 4 12OFF 12 CYCLES: 10 10 8 4-5 Set the “RUN” 18 18 14 to 1 2the 12right 10 position 10 8 8 switch 5-6 18 16 14 1 2 10 10 8 8 8 6-8 Set the number 18 16 of12run1 days 0 10(1-7). 8 6 6 6 8-10 18 14 12 10 8 8 6 6 4 Press the “1…7” button until all arrows are lit for each day of the 10-12 16 14 10 8 8 6 6 4 4 12-14 16 12 10 8 6 6 6 4 2 week. 14-16 16 12 10 8 6 6 4 4 2 Use the “h”14and 16-18 12 “m” 8 buttons 8 6 to4 set 4the 2“On” 2 time. A light bulb will 18-20 14 the 12 display 8 6 (SEE 6 4 4 2 2 be visible on B). Press the P button to set the “Off” time. Please note that the number in the bottom right hand side of the display will change from 1 to 2. Also, no light bulb will be displayed. Set the number of run days (1-7). Press the “1…7” button until all arrows are lit for each day of the week (SEE C). C Use the “h” and “m” buttons to set the “Off” time. Slide the Run switch back to the center position. • • B • • • • • STEP 3. RESET TIMER. If program is not working correctly, press and hold down the “R” button. Repeat steps 1 and 2. 9 QUIET LINE INSTALLATION DIFFUSER ADJUSTMENT STEP EIGHT. Diffuser Adjustment: You will most likely need to adjust the airflow to each diffuser. Some diffusers may be receiving more air than others, this valve will need to be closed down a little to increase the flow to the remaining diffusers. Continue this process until each of the diffusers receives approximately the same amount of airflow. Every system includes a pressure gauge, this gauge will help you monitor the system pressure. The system pressure does not need to be set, the running pressure is dependant upon the water depth and the length of tubing runs. Most systems balance out at around 6 to 12psi. In case of over pressuring, each system includes an automatic pressure relief valve that has been preset by our technicians. Do not adjust this valve without consulting Keeton Industries first. This valve will bleed off any excess pressure; this will protect your compressor from over pressuring. CONGRATULATIONS ON COMPLETION! Your Installation is now complete. If you have any problems, see “TROUBLESHOOTING” on the back page. If you have questions or concerns please feel free to contact us at 800.493.4831. Our professional staff will be more then happy to help you with any problems you may be experiencing. 10 QUIET LINE COMPRESSOR MAINTENANCE AND REPAIR On a monthly basis you should check the system to ensure it is functioning properly. This monthly check up should include checking that air inlet filters are not dirty and restricting airflow, making sure the cooling fan is working properly and the air intake vents are not plugged with debris. Filters should be cleaned or replaced when they become soiled and air intake vents need to have all debris removed to allow unrestricted airflow. System failure is almost always a result of the compressor overheating due to clogged inlet filters and/or air intake vents or cooling fan failure. Every eighteen (18) to twentyfour (24) months the compressor should have a repair kit installed. This is a fairly simple process that usually takes about an hour to complete. If you’re not very mechanically inclined it might be best to have a service professional do this for you. This process usually involves changing gaskets, seals, piston sleeves and filters. This will eliminate much of the day to day wear and tear your compressor unit will experience and will greatly extend its service life. Every repair kit comes with its own set of instructions for proper servicing. If you feel you are not able to perform these duties on your own you can send your compressor into Keeton Industries for maintenance or repair. WARNING Electrical Shock Hazard Disconnect power supply cord before Turn systemelectrical off, using the timer, then disconnect electrical installing Service power supply cordKit. before installing repair kit. If product is hard wired into system, disconnect electrical the circuit breaker or fuse box Vent all airpower lines toatrelease pressure. before installing Service Kit. Quiet Line Compressor Repair Kit. Call A Keeton Representative Today to Purchase A Kit. Vent all air lines to release pressure. Failure to follow these instructions can result in death, Failure to followshock. these instructions can result in fire or electrical death, fire or electrical shock. 11 QUIET LINE COMPRESSOR EXPLODED DIAGRAM DESCRIPTION QTY 87R 1 BODY* 2 * 2 FAN COVER 2 AP709 3 HEAD SCREW 8 AP136 4 HEAD 2 AP704A 5 HEAD O-RING 4 K964 6 MOTOR BOLTS* 1 * BEARING* 2 * CYLINDER O-RING 2 K964 SET SCREW 2 BB602C FAN 1 AP108A 11 PIPE PLUG 2 BA503 13 VALVE PLATE 1 VARIES 14 LEAF VALVE 2 K964 e the We re serv NO. 7 9 10 y alte ke an ht to ma rig 8 ration s y be which ma due t © 2014, o any G 12 QUIET LINE COMPRESSOR EXPLODED DIAGRAM 15 VALVE LIMITER 2 AP110A 16 VALVE SCREW 2 AP305 17 LEAF VALVE 2 K964 18 VALVE SCREW 2 AP305 19 RETAINER VALVE 2 AF819A 20 PLUG 1 AP711 22 BEARING 6006* 1 INCLUDED 23 CUP 1 INCLUDED 24 RETAINER PLATE* 1 INCLUDED 25 ECCENTRIC 1 INCLUDED 26 ROD 1 INCLUDED 27 CYLINDER 2 K963 28 RETAINER SCREW 4 INCLUDED 29 MOTOR* 1 * 30 FAN 1 AP108 86R & 13 8 SOLAER INSTALLATION EQUIPMENT AND SOLAR PANEL EQUIPMENT NEEDED QUIKRETE SCREW DRIVER TUBING CUTTER WRENCH SHOVEL HAMMER SOCKET SET OPEN END WRENCHES 7/16” AND 1/2” A BOAT WITH A MOTOR OR OARS • • • • • • • • • NOTE: To keep the pole from turning in the wind, we suggest you cut at least two pieces of re-bar at lengths equal to the full diameter of the hole. Weld re-bar (or drill holes and insert through pipe) to the underground portion of the pipe so that the pieces of re-bar are perpendicular to each other and remain parallel to the ground. When the mounting pole is installed, the re-bar will protrude radially outward into the concrete foundation. SOLAR PANEL STEP 1. Determine the installation location, which must have unobstructed views of solar south and out of the shadow path of any nearby structures or vegetation. STEP 2. Inspect top pole mount to determine the outside diameter size of schedule 40 steel pole to be purchased locally. Mount this pole into the ground; please see top pole mount instructions to determine the total pole length and the amount to be buried in the ground. It is very common to have as much as 6’ of pole above ground. In areas with very heavy snow fall, a longer pole may be required. It is recommended to secure the solar panel mounting pole by filling the hole with concrete. Allow enough time for the concrete to cure before proceeding with the solar panel mounting instructions. STEP 3. Place the compressor housing (cabinet) next to the mounting pole. The cabinet comes with four legs and is a free standing unit. You can pour a concrete pad to set the cabinet on if desired. Otherwise, the cabinet can be placed directly on level ground or on concrete pavers. In some situations (36”L by 36”W, large cabinets), it may be necessary to support the bottom of the cabinet with concrete blocks due to the weight of the batteries in the cabinet. STEP 4. Mount Panel to top pole mount. Please refer to panel mounting instructions included in top pole mount box. All hardware has been included with panel mount. The solar panel will be prewired and ready for electrical hookup. 14 SOLAER INSTALLATION TILTING THE SOLAR PANEL FOR SOLAR SOUTH SOLAR PANEL STEP 5. Set solar module tilt angle. Solar panels produce the most power when they are pointed directly at the sun. The module tilt angle is measured between the solar modules and the ground. Panel angle will need to be determined using the provided chart. STEP 6. Solar Panel Connection: Interlocking cables are provided with the system. Male and female connections from the panels will be connected directly to the cables pre-installed on the ProStar controller - positive ( + ) to negative ( - ). SOLAR AERATION UNIT STEP 1. Open the lid and inspect all equipment to ensure no evident damage has occurred during shipping. You will find all necessary installation hardware enclosed within the cabinet or in a separate package that was shipped with this unit. Your cabinet is 100% recycled plastic. STEP 2. All Cabinets are designed to be mounted on the provided legs. Make sure the system is level and firmly sitting on all four (4) legs. Systems can either be placed on a Level-aer Equipment Pad, concrete pad, concrete blocks or mounted directly on the ground. Systems can be fastened down so they are securely in place with a Keeton Security Kit (found on page 6) or the Owner can purchase their own security materials. Recommended Tilt Angles for a Fixed System Site Latitude in Degrees Fixed Tilt Angle in Degrees 0° to 15° 15° 15° to 25° Same as Latitude 25° to 30° Latitude + 5° 30° to 35° Latitude - 10° 35° to 40° Latitude - 15° 40°+ Latitude - 20° STEP 3. Alpine Self-Weighted tubing requires no additional weight and will sink gently to the bottom by itself. Stainless steel hose clamps and tubing couplers are provided for splicing tubing together and attaching the tubing to the Aeration Unit as well as the diffuser(s). 15 SOLAER INSTALLATION EQUIPMENT AND PROCEDURE STEP 4. Connect the Alpine tubing to the airline from the compressor housing. Put the roll of tubing in the boat. As you proceed to the desired diffuser location, feed the tubing over the side of the boat. When you reach the desired diffuser location, connect the Alpine tubing to the diffuser inlet, secure with stainless steel clamp and lower it into place. STEP 5. Start Up: After connecting the battery (page 5) and the solar panel (page 3) the system is now ready for start up. Again, make sure the valves on the manifold are fully opened. The timer has been pre-set for you, but see page 21 for proper timer use. The compressor and cooling fan should turn on. It will take a little time before air can be seen bubbling up from the diffusers. Let the system run with the valves fully open for a few minutes, then visually inspect the diffuser locations to ensure each diffuser is operating. STEP 6. Diffuser Adjustment: You will most likely need to adjust the airflow to each diffuser. Some diffusers may be receiving more air than the others, this valve will need to be closed down a little to increase the flow to the remaining diffusers. Continue this process until each of the diffusers receives approximately the same amount of airflow. CAUTION It is dangerous to work in and around open water. Please wear safty equipment when using tools, shovels, etc. and be sure to wear a life vest while operating a boat. Be careful of ice covered lakes in the winter, aeration systems weaken the ice and it is never safe to walk on aerated lakes. 16 SOLAER INSTALLATION BATTERY CONNECTION BATTERY CONNECTION THE BATTERY MUST BE CONNECTED PRIOR TO STARTING THE SYSTEM. PLEASE READ ALL INSTRUCTIONS CAREFFULLY PRIOR TO INSTALLING YOUR LAKE BED AERATION SYSTEM. Use Diagrams on pages 18 - 19 for help. Connect the negative terminal of battery A to the positive terminal of battery B using the BLUE Jumper Connection. This creates a 24V battery. A positive (RED) and a negative (BLACK) lead have already been connected to the ProStar and are ready to be connected to the positive and negative terminals on the batteries. Be sure to attach the positive lead (RED) to the positive terminal on battery A and the negative lead (BLACK) to the negative terminal on battery B. Observe that the Battery Status LEDs blink in sequence one time. Torque all the ProStar terminals tightly, but do not exceed 35 in-ib. Solar panel imput has already been connected to the ProStar. With sunlight, the green Charging LED will light. *BATTERY TYPE is pre-set for Type 1 - Gel. See page 18 for the SB-1 and SB-2 Diagram See page 19 for the SB-3 and SB-4 Diagram 17 SOLAER INSTALLATION BATTERY CONNECTION DIAGRAM SB-1 AND SB-2 < < RED BLACK A B < BLUE Jumper Connection 18 SOLAER INSTALLATION BATTERY CONNECTION DIAGRAM SB-3 AND SB-4 B RED C D BLUE Jumper Connection < < < A BLACK 19 SOLAER INSTALLATION READING THE INDICATORS LED INDICATORS CHARGING (LED 1 - GREEN) ON: battery charging during sunlight (always on during sunlight) OFF: normal during night (off during sunlight indicates solar reverse polarity or overcurrent) BATTERY STATUS (LEDS 2-4) GREEN: ON indicates battery is near full charge GREEN: BLINKING indicates PWM charging (regulation) YELLOW: ON indicates battery at middle capacity RED: BLINKING indicates a low charge state and a low voltage load disconnect (LVD) warning RED: ON indicates the load has been disconnected (LVD) FAULT INDICATORS (G = GREEN; Y = YELLOW; R = RED) G/Y/R blinking together – battery select fault R – Y sequencing – high temperature disconnect R – G sequencing – high voltage disconnect R/G – Y sequencing – load short circuit or overload LOAD OFF: A brief push of the button (less than 2 seconds) will disconnect the Load. The Solar remains on and charging. LOAD AND SOLAR OFF: If the button is held down for 2 seconds, the Solar will also be disconnected. SAFETY INFORMATION • Be very careful when working with batteries. Wear eye protection. Have fresh water available to wash and clean any contact with battery acid. • Charge only lead-acid batteries that are properly sized for the system. • Explosive battery gasses can be present during charging. Be certain there is enough ventilation to release the gasses. • Use insulated tools and avoid metal objects near the batteries. • Carefully read the battery manuals and other equipment manuals before installing the solar system. Observe ALL precautions when working with batteries and power electronics. • Fuses or DC disconnects may be required in the system. These protective devices are not part of the solar controller. • Avoid large voltage drops in the battery wires. Use the Battery Sense connection (see diagram) for best battery charging and system performance. • Do not allow water to enter the controller. • Avoid touching the controller heat sink. Under certain operating conditions, the heat sink can become hot. • Install the controller in a vertical position with adequate space for ventilation. • Ensure that the system is properly grounded. NOTE : Batteries provided are AGM style, not lead-acid. 20 SOLAER INSTALLATION PRO STAR CONTROLLER SOLAR CONTROLLER If the push button is held down for 4 seconds, the ProStar will go into automatic self-diagnostics. Note that the button must be released to start the self-test. NOTE: The push button can be used to toggle through the displays faster. The entire self-test takes 30 to 45 seconds. The load will be turned on for 0.1 second and may flash during the test. A short or overload condition could cause a controller restart. The following displays will occur (examples are used): 8.8.8 - self-test started, checking the digital meter segments 12u - the system voltage (12/24/48) 15A - current rating r1.5 - software version installed E04 - a fault has been detected (see list below) --- display if no fault is found 25c - temperature measured at the controller rP - remote temp probe is detected (if connected) 25c - temperature at the remote probe (if connected) SEn - battery sense detected (if connected) S-1 - battery select position (1,2, or 3) J-1 - telecom noise jumper cut (change to on-off regulation) end of the self-test End --- End - display continues if no error was detected. End End - display continues if an error has been detected. To terminate the self-test, push the button. The self-test can be repeated to confirm the result. Error List: E01 - Rotary switch battery selection failure E03 - Voltage reference test failed (circuit, malfunctions) E04 - Solar array current fault (circuit, FETs [Field-Effect Transistor]) E07 - Load FETs off test (load connection, FETs shorted) E08 - Load current fault (circuit, FETs) E09 - Load FETs on test (load circuit, FETs open) E10 - Internal temp sensor out of range high E11 - Internal temp sensor out of range low E12 - Remote temp probe out of range E13 - Battery sense fault (battery V drop over 5V, no Sense negative connection) 21 SOLAER BATTERY BATTERY CHARGING BATTERY CHARGING INFORMATION The ProStar uses 4 stages of charging for rapid, efficient and safe battery charging. These are shown in the diagram to the right: STEP 1. Recharging with 100% of available solar energy. STEP 2. PWM constant-voltage regulation to prevent heating and excessive battery gassing. Pulse charging to restore full battery capacity. STEP 3. Float: After battery is fully recharged, ProStar reduces to a float or trickle charge. The transition depends on battery history. A load that exceeds available solar output returns ProStar to the PWM mode. STEP 4. Equalize: A boost charge that depends on elapsed time and battery history. Flooded cells receive a vigorous equalization, sealed batteries a smaller boost to bring uneven cells into balance and extend the battery life. Gel cells are not equalized. 22 SOLAER TIMER SETTING TIME, DATE AND CYCLES THE TIMER NOTE: All timers are pre-set on your Solaer Aeration System to run 20 hours, 2:00 p.m. to 10:00 a.m. This is our reccomended time of use. Use the below information if you would like to increase or decrease according to the vitality of your pond or lake. STEP 1. SETTING THE TIMER. Set the “RUN” switch to the button. Push the “1…7” button to set the day (Ex: Sunday = 1, Monday =2, Etc.) Use the “h” and “m” buttons to set the current time Slide “RUN” switch back to the center position (SEE A). • • • • A STEP 2. SETTING THE ON AND OFF CYCLES: Set the “RUN” switch to the right position Set the number of run days (1-7). Press the “1…7” button until all arrows are lit for each day of the week. Use the “h” and “m” buttons to set the “On” time. A light bulb will be visible on the display (SEE B). Press the P button to set the “Off” time. Please note that the number in the bottom right hand side of the display will change from 1 to 2. Also, no light bulb will be displayed. Set the number of run days (1-7). Press the “1…7” button until all arrows are lit for each day of the week (SEE C). C Use the “h” and “m” buttons to set the “Off” time. Slide the Run switch back to the center position. • • B • • • • • STEP 3. RESET TIMER. If program is not working correctly, press and hold down the “R” button. Repeat steps 1 and 2. 23 SOLAER COMPRESSOR MAINTENANCE AND REPAIR EQUIPMENT NEEDED REPLACEMENT KIT FELT TIP PEN STEEL WOOL PHILLIPS HEAD SCREWDRIVER • • • • A: Headplate B: Head Screws (4 per head) C: Intermediate Plate D: Valveplate (2 per head) E: Seal Ring (2 per head) F: Diaphragm G: Shim Rings (Qty may vary) *Drawing is for reference only, and covers a variety of models. Use the same quantity of parts as originally supplied on your pump. 24 SOLAER COMPRESSOR MAINTENANCE AND REPAIR STEP 1. Disconnect the pump from electrical power. Remove interconnecting tubing only where necessary. STEP 2. Mark the position of the pump head plate A, intermediate plate C and crankcase L relative to each other by drawing a line on the edges with a pencil or other marker to assure proper reassembly. To access the counterweight N, remove the screws holding the compressor cover. Retain any gasketing for reuse. STEP 3. Remove the four screws and washers B and remove the headplate A. Note the positioning of the valveplates D and seal rings E in relation to the valve ports on the headplate A and intermediate plate C. Lift off the seal rings and valveplates. STEP 7. Turn the counterweight N until the diaphragm is flat across. Carefully center the diaphragm over the compressor housing L, firmly seating the diaphragm edge into housing groove. STEP 8. Place the clean intermediate plate C onto the compressor housing L, according to your previously drawn markings, then place the new valve plates D and seal rings E on top of the intermediate plate. Make sure the seal rings are properly seated in intermediate plate recesses to avoid pinching. STEP 4. Remove the intermediate plate C. Carefully clean the head and intermediate plates of any residue using fine steel wool. DO NOT scratch. STEP 9. Place the clean headplate A on top of the intermediate plate C according to your your previously drawn markings and the locating pin. Then tighten the four screws B in a crisscross pattern. Do not overtighten. Turn the counterweight or the fan by hand to ensure that the pump turns freely. STEP 5. Unscrew the old diaphragm F by turning it counterclockwise using both hands. DO NOT use tools! Take care not to lose any small parts such as the shim rings J, positioned between the diaphragm stud and connecting rod, as they must be replaced for proper pump operation. Parts removed must be replaced exactly as found. STEP 10. Remove any old Teflon® tape from all fittings. Carefully apply two layers of Teflon® tape around any fittings before reinstalling into the pump head. Install any tubing and fittings. Do not apply tape beyond threads, as excess tape may tear off and lodge in the valves. Do not substitute any other type of tape. STEP 6. Place the parts removed in step 5 onto the threaded stud of the new diaphragm. Carefully screw the new diaphragm F into the connecting rod C. Tighten firmly using both hands, NO TOOLS! 25 WARRANTY COVERAGE AND POLICIES Keeton Industries finished products, when properly installed and operated under normal conditions of use, are warranted by Keeton Industries to be free from defects in material and workmanship for a period of twenty-four (24) months from the date of purchase from Keeton Industries or an authorized Keeton Industries representative or dealer. In order to obtain performance under this warranty, the buyer must promptly (in no event later than thirty (30) days after discovery of the defect) give written notice of the defect to Keeton Industries, 1520 Aquatic Drive, Wellington, CO 80549, or an authorized service center. Buyer is responsible for freight charges both to and from Keeton Industries in all cases. Keeton Industries’ warranties also do not extend to any goods or parts which have been subjected to misuse, lack of maintenance, neglect, damage by accident or transit damage. Keeton industries will not be responsible or liable for indirect or consequential damages of any kind, however arising, including but not limited to those for use of any products, loss of time, inconvenience, lost profit, labor charges, or other incidental or consequential damages with respect to persons, business, or property, whether as a result of breach of warranty, negligence or otherwise. Notwithstanding any other provision of this warranty, buyer’s remedy against Keeton Industries for goods supplied or for non-delivered goods or failure to furnish goods, whether or not based on negligence, strict liability or breach of express or implied warranty is limited solely, at Keeton Industries’ option, to replacement of or cure of such nonconforming or non-delivered goods or return of the purchase price 26 for such goods and in no event shall exceed the price or charge for such goods. Keeton Industries expressly disclaims any warranty of merchantability or fitness for a particular use or purpose with respect to the goods sold. There are no warranties which extend beyond the descriptions set forth in this warranty, notwithstanding any knowledge of Keeton Industries regarding the use or uses intended to be made of goods, proposed changes or additions to goods, or any assistance or suggestions that may have been made by Keeton Industries personnel. Unauthorized extensions of warranties by the customer/dealer shall remain the customer’s/dealer’s responsibility. DURAPLATE DIFFUSERS ARE COVERED BY A SEPERATE LIFE TIME WARRANTY AGAINST MATERIAL DEFECTS OR CRAFTSMANSHIP. This warranty can be modified only by authorized Keeton Industries Personnel by signing a specific, written description of any modifications. NOTE: THIS EXPRESS WARRANTY EXCLUDES ALL OTHER WARRANTIES OR REPRESENTATIONS EXPRESSED OR IMPLIED BY ANY LITERATURE, DATA, OR PERSON. KEETON INDUSTRIES MAXIMUM LIABILITY UNDER THIS EXCLUSIVE REMEDY SHALL NEVER EXCEED THE COST OF THE SUBJECT PRODUCT AND KEETON INDUSTRIES RESERVES THE RIGHT, AT ITS SOLE DISCRETION, TO REFUND THE PURCHASE PRICE IN LIEU OF REPAIR OR REPLACEMENT. TROUBLESHOOTING QUIETLINE AND SOLAER Low Pressure High Pressure • Pump Overheat Won’t Start • • Excess Noise Filter dirty. Clean or replace. • Valves closed. Clean or replace. • Worn cup. Repair or replace. • • • Relief valve set too high. Inspect and adjust. • • • Plugged pressure line. Inspect and repair. • • Low voltage, won’t start. Check power source. • • COMPRESSOR • • Relief valve set too low. Inspect and adjust. • • • DIFFUSERS • High Air Flow • • • Voltage wrong. Check power source. • Worn diaphragm hitting cylinder. Replace. • • • Uneven Air Flow • • Cylinder misadjustment. Realign. Leaky hose or check valve. Replace. • Dirt or liquid on top of diaphram. Inspect & Clean. • Timer set incorrectly. Inspect and adjust. • • Worn cooling fan. Clean or replace. Low Air Flow Won’t Start • • System Leak. Check connections, tubing & repair. • • Manifold not set correctly. Inspect and adjust. • • “Burping” Bubbles REASON & REMEDY Compressor Issue. See above. • • REASON & REMEDY Damaged or torn Membrane. Replace. Unbalanced Manifold. Inspect and adjust. 27 SOLAER AERATION MONITORING SYSTEM TROUBLESHOOTING THE SOLAR PANELS Another innovation making diagnosis easier than ever. With these indicator lights you’ll be able to check the solar system for normal operation with just a quick look. Yellow Indicator Solar Input. The yellow indicator lets you know the sun is shining and the solar photo-voltaic panel is operational. Blue Indicator Load - Compressor. Indicates air compressor motor is operational. Green Indicator Battery Status. Indicates batteries have power and are operational. GIVE US A CALL 800.493.4831 28 CALL US, F YOU HAVE QUESTIONS ABOUT OPERATING THE SOLAR UNIT. BENEFICIAL MICROBES IMPROVE WATER QUALITY AQUA-TRON® AQUA-TRON® COLD WATER WASTE AND SLUDGE REDUCER™ FISHERY PRIME Through years of field research, Keeton Industries is proud to offer an all natural and eco-friendly, effortless and simple solution to manage your pond and lake = beneficial microbes. Keeton Industries maintains complete control of our microbial products from fermentation to final packaging in water-soluble bags. Having the ability to control this in-house allows us to produce the highest quality products on the market today. CALL KEETON TODAY AND START IMPROVING YOUR WATER QUALITY. 800.493.4831 29 30 REGISTRATION CARD DETACH AND MAIL OR GO ONLINE DR DR DR DR DR Serial Number: ___________________________ KR Serial Number: ___________________________ KR Serial Number: ___________________________ KR Serial Number: ___________________________ KR Serial Number: ___________________________ KR Advertisment Friend Facebook Online Search DR Serial Number: ___________________________ KR How did you hear about this product? DR Serial Number: ___________________________ KR QR QR QR QR QR QR QR Tradeshow TR TR TR TR TR TR TR SB-2 SB-2 SB-2 SB-2 SB-2 SB-2 SB-2 SB-3 SB-3 SB-3 SB-3 SB-3 SB-3 SB-3 SB-4 SB-4 SB-4 SB-4 SB-4 SB-4 SB-4 Other__________________ SB-1 SB-1 SB-1 SB-1 SB-1 SB-1 SB-1 Please fill out the serial number(s) and check the box of the model number of the product(s) purchsed. Email:_________________________________________Sales Rep:_________________________________ City, State, Zip:__________________________________________________________________________ Address:_______________________________________________________________________________ Name:_________________________________________________________________________________ Date of Purchase:______________________________Telephone: _________________________________ REGISTRATION CARD TEAR HERE Thank you for buying a Keeton Industries aeration unit. To receive Technical Support, purchase accessories please fill out and return this card to the address on the card or go to our website and fill out the online form at http://keetonaquatics.com/product-registration/. 31 TEAR HERE __________________________________________ __________________________________________ __________________________________________ __________________________________________ KEETON INDUSTRIES, INC. 1520 AQUATIC DRIVE WELLINGTON, CO 80549 PLACE STAMP HERE 32