Series 70 ePODs: Type-P
Transcription
Series 70 ePODs: Type-P
Series 70 ePODs: Type-P Static Transfer Switch with Distribution Technical Specifications Series 70 ePODs: Type-P 2 Basic Purpose The Series 70 ePODs: Type-P provides switching between two independent power sources on the primary side of the transformer, while providing power distribution capabilities, featuring a solid-state transfer switch on the primary side of the transformer. The Series 70 ePODs: Type-P provides the ability to transfer power between two or three sources in quarter of an electrical cycle, while delivering that power to up to twelve subfeed circuit breakers. This automatically or manually provides static transfers between two AC sources in less than a quarter cycle, and safely transfers this power downstream. The Series 70 ePODs: Type-P performs open-transition transfer in such a manner that the connected load disruption is minimized without ever cross-connecting the power sources. A power source is specified as the preferred source, and if the preferred source fails, the unit will automatically connect to the alternative source until the preferred source is available again. Power sources are not required to be synchronized with our patented dynamic phase compensation technique. All components of the machine are safely replaceable without the need to de-energize the load. © 2013 LayerZero Power Systems, Inc. Series 70 ePODs: Type-P Technical Specifications Series 70 ePODs: Type-P eSTS: Size: 250A, 400A, 600A, 800A Voltage: 480V, 3-W, 600V, 3-W Redundancy: Triple Modular Redundant (TMR) Single Module Redundant (SMR) Output Switch: Redundant, Non-redundant 3 Main Circuit Breaker Section: MCB optional Mounting: Fixed, Plug-In Type: Molded Case Switch 65kA, 100kA Electronic Trip 65kAIC, 100kAIC Accessories: CB Shunt-trip 120VAC, 24VDC CB Position Indication: Open, Tripped, Closed Transformer section: Size: 150kVA; 225kVA; 300kVA; 400kVA; 500kVA Type: Normal Efficiency, TP-1 high efficiency Inrush: Low-inrush Distribution Section: Non-linear thermal rating: Sub-feed distribution K-9, K-13, K-20 1200A SafePanel 800A I-Line Panel Up to six (6) 42-circuit, 225A or 400A panel boards Reliability Safety • Triple modular redundancy • Serialized circuit boards • Fail-safe mechanics • Waveform capture • “Black box” forensic diagnostics • Voice guided bypass • Insulated, epoxy coated buswork • Silver plated terminals • Brazed invisible joints • Machined cap screws & disc springs • Helicoil & PEM inserts • Staggered heat sink arrangement • Fanless operation • Optical fiber based controls • Isolated input interface • InSight IR portholes • Front-only access • Dead-front hinged doors • Clear Translucent Polycarbonate window to view LEDs • NFPA 70E friendly Information Centricity • Access to eBOSS portal • Project tracking • Incident logging • Access to test reports & documentation • Touch screen interface Connectivity • Ethernet • Modbus/TCP • NTP time clock synchronization © 2013 LayerZero Power Systems, Inc. Agency Certification The Series 70 ePODs: Type-P is ETL listed to UL 1008 AND to UL 60950 Series 70 ePODs: Type-P Technical Specifications Series 70 ePODs: Type-P 4 Seamless Integration With Existing Systems Far too often coordination with existing systems are afterthoughts. As a result, many data centers resort to makeshift solutions that are inefficient and lacking in harmonization with existing monitoring software. LayerZero offers a wide choice of product options, all designed to coordinate with your existing power infrastructure. Our products fully support open protocols, so that the information generated from LayerZero equipment seamlessly fits in to existing monitoring packages. LayerZero supports open connectivity utilizing open protocols. Power distribution issues in the data center industry include: Opportunity to Enhance Operator Safety Need for Open Connectivity and Monitoring Our Series 70 product line was developed to provide a safe environment for the operator; and to assist critical sites with staying in compliance with the stringent safety requirements of NFPA 70E. Coordinating information is difficult when clusters of connected equipment are based on proprietary protocols, and LayerZero solves this by basing the equipment off of open technologies. Lack of True System Redundancy Lack of Comprehensive Diagnostics Tools All of our equipment is truly redundant, so that if individual components were to fail the systems will remain fully operational. LayerZero equipment does not contain any single points of failure. To prevent future problems in facilities our systems provide easy to read alarms with clear indications on the sources of offending conditions, so that root-cause analysis can be performed. © 2013 LayerZero Power Systems, Inc. Series 70 ePODs: Type-P Technical Specifications Reliability 5 Triple Modular Redundancy The Series 70 ePODs: Type-P occupies a unique architectural location in mission critical infrastructure systems, in that their tolerance for failure is virtually zero. The units are available in SMR (Single Modular Redundancy) or TMR (Triple Modular Redundancy) configurations, both of which are architectures that eliminate single points of failure. The TMR configuration will continue its mission of being a static transfer switch even if any one control element were to fail. As such, it is known to improve reliability by an order of magnitude. Triple Modular Redundant products serve the needs of elite, mission-critical infrastructure requirements. With our Triple Modular Redundant STS topology we can provide products that are at least ten times more reliable than alternative solutions. Serialized circuit boards We serialize and track all critical circuit boards and memory cards through our eBOSS portal, which allows customers to reference which components their machines are made from, who tested the components, as well as the ability to view notes generated from testing. Serialized components offer the ability to drill-down on prospective component failure utilizing predictive modeling techniques, so if part fails, the instance can be cross-referenced with similar parts. This preventative maintenance helps ensure maximum uptime. Fail-safe mechanics The bypass procedure employs a fail-safe measure to improve system reliability in that the procedure can only be physically completed in the correct sequence. A mechanical “double goalpost” interlock bar constrains the operators behavior so that breakers can only be manipulated in an order maintain continuity of power to the load. The restraint rotates downward for manual transfer testing purposes. Waveform capture Each transfer event and overload transfer-inhibit event is captured and stored in non-volatile memory. The Waveform Capture tool is standard in all eSTS products. It provides 3-phase current and 3-phase voltage waveform analysis of Source 1, Source 2, (Source 3 in a 3-source system) and Output Precise voltage and current data is necessary to understand why a transfer was made. Detailed records of transfers help operators better understand the root cause of events, helping engineers properly eradicate problems. Without waveform capture, this is not possible in a live environment. The 6-cycle capture is displayed on the control panel or can be viewed remotely on a standard webbrowser. © 2013 LayerZero Power Systems, Inc. Series 70 ePODs: Type-P Technical Specifications Reliability 6 “Black box” forensic diagnostics The black box capabilities of LayerZero equipment are extremely useful for analyzing root cause analysis, enabling operators to pinpoint exactly where a fault occurred. “Black box” forensics provide successive event information with ten microsecond resolution, supplies a brief snapshot of the event with a lead-in for further inquiry, and furnishes a real-time status indicator of all machine parameters at the time of the event. The technology in our “black box” event history is one of the most useful recording schemes in the mission critical power machine industry. Voice guided bypass To help prevent operators from completing the bypass procedure out-of-sequence, our products feature a voice prompted bypass procedure. This instructs the operator in a step-by-step course of action of the process, with only one operation per screen. Voice guided bypass slows down operators and compels them to think about the process, significantly reducing the probability of operator error. Visual and audio cues provide clear instructions on the bypassing sequence. Epoxy coated buswork Silver plated terminals Our usage of epoxy coated buswork helps ensure safety, protecting operators from being exposed to live parts. LayerZero utilizes silver plating on all of its machine components to be able to provide the highest performance. Silver has high conductivity and low resistance which makes for a great contact. Brazed invisible joints Machined cap screws & disc springs Electrical copper bus joints that cannot be accessed by the operator for thermal scanning and maintenance are brazed. This creates a maintenance-free joint. LayerZero systems are durable, sturdy, and built to last. © 2013 LayerZero Power Systems, Inc. Our systems utilize machined cap screws and engineered disc springs with a flat pressure vs deflection profile to ensure that all bolted connections maintain constant torque through the life of the product. Series 70 ePODs: Type-P Technical Specifications Reliability 7 Optical fiber controls Fanless operation Fiber optic based controls eliminate noise and interference, while isolating components from high voltage. Optical fiber allows service to be reliably connected, while protecting the equipment. Fans and fan sensors are one of the most common components to fail. Staggered heat sink The heat sink arrangement is staggered between sources and phases to minimize the creation of extreme thermal gradients between heat sink columns when conducting on one source or the other. For maximum uptime, Type-P systems do not contain any fans, filters, or fan fuses. PEM inserts Helicoil inserts About LayerZero Field Service Engineers LayerZero Certified Field Service Engineers are responsible for supporting installations, PMs, equipment upgrades, technical support, documentation management, and training. Located nationwide and available 24/7, our certified field service engineers are well-trained to keep your equipment reliable. © 2013 LayerZero Power Systems, Inc. Series 70 ePODs: Type-P Technical Specifications Safety 8 InSight IR Portholes Strategically positioned IR-scan portholes to enable safe thermal scanning of all bolted connections with the deadfront closed, without exposing the operator to power circuit voltage. The IR window swivels upward and unlocks with key-hole access to revel an arc-proof mesh, allowing the operator to point-and-shoot thermal cameras to obtain accurate readings. LayerZero provides extensive documentation and training for proper thermal scanning procedures. Sectionalized Components Normal operator sections (breakers/switches) are physically separated from the power electronics and control electronics sections, so that maintenance on a section can be safely performed. If maintenance is required on a particular section, power can be bypassed to another section to allow for safe repairs to be made. All connections are optically isolated to minimize risk. Insulated Parts Operators are well-protected from exposed connections. Energized parts are all insulated, covered, recessed, &/or internally mounted for safer operation of the unit. In addition, sections that isolate machine components are insulated. Polycarbonate window to view diagnostic LEDs Operators can view the status of diagnostic LEDs without direct exposure to the energized power electronics section. NFPA 70E Our Series 70 product line was developed to exceed NFPA-70E regarding operator safety, to help data centers drastically reduce the risks of their energy distribution systems. © 2013 LayerZero Power Systems, Inc. Series 70 ePODs: Type-P Technical Specifications Safety 9 SafePanel distribution The Series 70 ePODs: Type-P features an IP-20, finger-safe panel board, meaning that the opening will not allow ingress of ½” (12.5mm) diameter probe, for maximum operator safety. An arc can form as two live conductors are separated – such as the removal of a circuit breaker from a panel board. The SafePanel design ensures that a potential arc would be contained in the connection well so that even if a branch breaker were to be removed, the arc would be contained in the connection well. The CB can only be disengaged/removed when in the off position, which eliminates the possibility of the creation of an arc or flash during breaker removal. When the CB is in the off position, access to the mounting screw is locked out. When the CB is in the on positions, access to the mounting screw is enabled via a sliding shutter. Insulated with the components deeply isolated, removal of the breaker is safe and easy. There is a convenience handle on the load side and a removable handle on the line side. The subfeed circuit breaker is installed by placing the CB into the panel board and engaging the lock with a screw. © 2013 LayerZero Power Systems, Inc. Series 70 ePODs: Type-P Technical Specifications Connectivity 10 Open protocols LayerZero utilizes open source protocols for its communications, which allows for: - An enhanced ability to customize software - Flexible software development options - Lower total cost of ownership (no per copy fees) - Elimination of vendor lock-in - No proprietary limitations - Provides a stable, well developed foundation The control path for the communications system gathers information from all aspects of the machine, isolated by fiber optics. Connectivity to a WAN allows for the information to be accessible from any location, offering a variety of monitoring options. Series 70 ePODs: Type P Modbus/TCP Standard Ethernet Dry Contacts http:// through a standard web browser - Summary Alarm - On Source 1 - On Source 2 - Source 1 Available - Source 2 Available - Meters - Alarms Network Time Protocol (NTP) Compliant - Meters - Alarms - Waveforms - History/Event Log - Diagnostics A Flexible Approach A variety of connectivity options provide operators with the ability to adapt LayerZero systems to fit existing networks without the complications of working with closed, proprietary systems. The Series 70 ePODs: Type-P is designed to make it easy to transfer and exchange power usage data, which is very useful towards making smart corporate decisions and policies. © 2013 LayerZero Power Systems, Inc. Series 70 ePODs: Type-P Technical Specifications Information Centricity 11 Touch screen interface The Dynamic Mimic Panel is presented on a 15” color touch screen Graphical User Interface, which was carefully designed to be user-friendly, intuitive, and consistent. A well creative and well organized “page” based navigation helps operators quickly get to the information they need, without having to search around. The GUI is “Read-Only” unless a user has logged on. A walk-up user may examine the state of the switch, but can not change that state. This is “USER” level access. If a user has logged on by providing a valid password, then he or she is allowed to view additional pages (Page-Level Security) and to make changes to controls on pages (In-Page Security). Access expires in 10 minutes. The 10 minute period is renewed if any Page navigation (ROOT or PAGE) button is selected. Operators have instant access to real-time power usage information, which is valuable for making power-related decisions. A mimic panel graphically show that current state of the switch and power flow, while health meters provide operators with the capability to know the status of a TMR instantly. Alarms are visible on every screen. Alarms clear themselves when the offending condition is fixed. Until such time, Alarms persist. There is no “alarm clearing” button/capability. In a TMR system, when an alarm is posted by only one SCB the system continues to operate as a fully functional STS. Such an alarm points to a problem in only one of the three independent control systems. Each transfer event and overload transfer-inhibit event is captured and stored as part of the history of the machine. The transfer history can only be cleared by authenticated users. © 2013 LayerZero Power Systems, Inc. Series 70 ePODs: Type-P Technical Specifications Product Options 12 Options • • • • • • • • • Current Voltage Number of Sources Number of Output CBs Redundancy Number of Wires Number of Poles Frequency Withstand Specification Tables The Series 70 ePODs: Type-P line offers the following configurations: Current Voltage 250A 480V, 3-wire, 60Hz 600V, 3-wire, 60Hz Heat Dissipation Weight Dimensions 4,750 BTU/Hr 1,350 lbs 48”W x 36”D x 80”H 400A 7,000 BTU/Hr 1,400 lbs 48”W x 36”D x 80”H 600A 9,500 BTU/Hr 1,500 lbs 48”W x 36”D x 80”H 800A 12,500 BTU/Hr 1,950 lbs 58”W x 36”D x 80”H Available Withstand Ratings (kA) 480V 18kA 600V X 25kA X X 35kA X X 65kA X X 100kA X X 150kA X 200kA Typical System size (kVA) eSTS ratings 480V, 3-wire Output Voltage 600V, 3-wire Dimensions (Front/Right side access) 150kVA 250A 225kVA 400A 300kVA 400A or 600A 120Y/208V, 3-phase, 150A or 250A 4-wire + Ground 240Y/415V, 3-phase, 250A or 400A 4-wire + Ground 400A 480V eSTS 600V eSTS 96"W x 84"H x 36"D 96"W x 84"H x 36"D 96"W x 84"H x 36"D 96"W x 84"H x 36"D 96"W x 84"H x 36"D 96"W x 84"H x 36"D 400kVA 600A 400A or 600A 108"W x 84"H x 36"D 108"W x 84"H x 36"D 500kVA 800A 600A 168"W x 84"H x 48"D 158"W x 84"H x 48"D Notes: 1) Depth dimensions are valid for Sub-feed distribution. For panel board distribution, depth is 48". 2) Add 12" to width and Left side access for (5) or (6) 42-circuit panel boards 3) Rear access not required for installation; operation; and maintenance Contact LayerZero for custom sizes and designs. © 2013 LayerZero Power Systems, Inc. This document is subject to change without notice. Rev: 1/4/13 Series 70 ePODs: Type-P Technical Specifications © 2013 LayerZero Power Systems, Inc. A B C D 8 8 400A Series 70 eSTS Area 7 7 300KVA Transformer Area 6 6 5 5 4 Floor Stand (See Notes 2 & 3) Sub-Feed Circuit Breaker / NEU & GND Distribution Cabinet 4 3 3 A N/A NEW RELEASE DESCRIPTION REVISIONS 09/16/2010 DATE 1 APPROVED STEVE JANKO SPJ AJP SPJ DWN CHK APVD ANGULAR ± .1/2 TOLERANCES: .XX ± .03 .XXX ± .010 DATE DATE DATE 09/16/10 09/16/10 09/16/10 FIRST ANGLE PROJ. UNLESS OTHERWISE SPECIFIED DIMENSIONS ARE IN INCHES DO NOT SCALE DRAWING SCALE D SIZE 2 1=1 FSCM NO. 1 SHEET 55-11-401493-01 94MD401493-01SHT1 DWG NO. 1 OF 5 A REV OUTLINE, MOUNTING, INSTALLATION DIAGRAM 400A, 480V, 60Hz, SMR/TMR, 2 Source Series 70 eSTS/ 300KVA Transformer/ Supplied with up to (6) 400A ABB-T5/T3 Sub-Feed Distribution Breakers / Type P ePODs Copyright © 2003, LayerZero Power Systems, Inc. 8. There is no shipping split from the factory to the end user. 7. The Output connection from the 2 Source Series 70 eSTS to the Transformer and the Output connection from the Transformer to the Sub-Feed Distribution Cabinet will be factory installed internally. 6. For the Sub-Feed Distribution with Sub-Feed Circuit Breaker Ratings of 400A unit is supplied with definition showing right side orientation. See Sht 2 for Cable Access Areas and recommended wire size (Table 1). See Sht 4 for Cable Landing Locations 5. Fork Lift provision from either the front or side of the assembly is available as shown. Provision for lifting with a crane is supplied at the top of the cabinet and is removable if additional clearance is necessary. 4. For the ePODs the unit is interconnected between the Series 70 eSTS / Transformer Cabinet and bolt-on Sub-Feed Distribution Cabinet. Sheet 3 will have a description of main components. 3. A separate outline of the floor stands is shown on Sheet 5 for installation layout purposes. 2. Sheets 2 through 4 will show the assembly in various forms with the floor stqnd assembly not shown in any views. 1. Front access only required for operation and servicing of Series 70 eSTS and Transformer. Side access only required for servicing of Sub-Feed Circuit Breakers and associated Neutral and Ground. Top or Bottom Access is available for the Series 70 eSTS and for the Sub-Feed Circuit Breaker Cabinet. NOTE: Dimensions for cable access apply to either top or bottom entry. Notes: REV ECN 2 A B C D Series 70 ePODs: Type-P Drawings 13 Series 70 ePODs: Type-P Technical Specifications © 2013 LayerZero Power Systems, Inc. A B C D 4 8 FORKLIFT PROVISION (FRONT ENTRY) 2.00 TYP SERIES 70 eSTS AIR EXHAUST OUTLET TOP / BOTTOM CABLE ACCESS AREA FOR eSTS INPUT 8 GUI 35 3.00 TYP 26 38 85 7 10.0 FRONT VIEW 96 12 38 TRANSFORMER AIR EXHAUST OUTLET 6 10.0 6 TRANSFORMER SUCTION INLET 340 SQ IN TOTAL (FRONT/BACK) SERIES70 eSTS / 300kVA XFMR AREA 19.25 TOP VIEW SERIES 70 ESTS SUCTION INLET 144 SQ IN TOTAL 7 85 9.25 33.00 2 7 5 SUB-FEED UNIT CB621 THRU CB624 88 TOP / BOTTOM CABLE ACCESS AREA FOR SUB-FEED PHASE / GND / NEU OUTPUT 22.25 5 8.0 6 8.0 4 FORKLIFT PROVISION (SIDE ENTRY) RIGHT SIDE VIEW 4 7 4.0 88 3 3 A N/A SPJ AJP SPJ DWN CHK APVD ANGULAR ± .1/2 TOLERANCES: .XX ± .03 .XXX ± .010 2 REVISIONS NEW RELEASE DESCRIPTION TABLE 1 #16GA EITHER SINGLE OR DUAL HOLE AVAILABLE SPECIFY AT TIME OF ORDER (24) #1/0 THRU 350KCM EA FOR GND AND NEU (2) 250MCM CABLE SIZE AND LUGS INPUT/ OUTPUT DATE 09/16/10 09/16/10 09/16/10 FIRST ANGLE PROJ. DATE DATE 1 APPROVED STEVE JANKO FACTORY PROVIDED MECHANICAL LUG BARRELL TYPE SINGLE / DUAL FACTORY PROVIDED MECHANICAL LUG BARRELL TYPE ILSCO SINGLE LANDINGS NEMA STANDARD C-C SPACING (2) 1/2DIA X 1-3/4 COMPRESSION LUG (75 DEG C WIRE MIN) 09/16/2010 DATE SCALE D SIZE 2 1=1 FSCM NO. 1 SHEET 55-11-401493-01 94MD401493-01SHT2 DWG NO. 2 OF 5 A REV OUTLINE, MOUNTING, INSTALLATION DIAGRAM 400A, 480V, 60Hz, SMR/TMR, 2 Source Series 70 eSTS/ 300KVA Transformer/ Supplied with up to (6) 400A ABB-T5/T3 Sub-Feed Distribution Breakers / Type P ePODs Copyright © 2003, LayerZero Power Systems, Inc. CONTROL WIRE SUB-FEED CIRCUIT BREAKERS CB621 THRU CB624 400A GND / NEU BUS SOURCE INPUT (Series 70 eSTS) 400A DESCRIPTION CLEARANCES: FRONT: 42IN REAR: 4IN LEFT SIDE: 0IN RIGHT SIDE: 42IN TOP: 18IN GROSS WEIGHT: 5730# UNLESS OTHERWISE SPECIFIED DIMENSIONS ARE IN INCHES DO NOT SCALE DRAWING REV ECN A B C D Series 70 ePODs: Type-P Drawings 14 Series 70 ePODs: Type-P Technical Specifications © 2013 LayerZero Power Systems, Inc. A B C D 8 8 7 SOURCE INPUT/ XFMR OUTPUT CONTROLS SECTION (CIB/ROUTER) 7 6 6 T620 SERIES 70 eSTS EXHAUST AREA 240 SQ IN 5 TRANSFORMER TAPS 5 4 4 GROUND BUS ASSEMBLY 3 SUB-FEED CIRCUIT BREAKER BANK NEUTRAL BUS ASSEMBLY SUB-FEED DISTRIBUTION CABINET (CB621- CB624) TRANSFORMER EXHAUST AREA 360 SQ IN 3 A N/A SPJ AJP SPJ DWN CHK APVD ANGULAR ± .1/2 TOLERANCES: .XX ± .03 .XXX ± .010 NEW RELEASE DESCRIPTION REVISIONS DATE DATE 09/16/10 09/16/10 09/16/10 FIRST ANGLE PROJ. DATE 09/16/2010 DATE 1 APPROVED STEVE JANKO SCALE D SIZE 2 1=1 FSCM NO. 1 SHEET 55-11-401493-01 94MD401493-01SHT3 DWG NO. 3 OF 5 A REV OUTLINE, MOUNTING, INSTALLATION DIAGRAM 400A, 480V, 60Hz, SMR/TMR, 2 Source Series 70 eSTS/ 300KVA Transformer/ Supplied with up to (6) 400A ABB-T5/T3 Sub-Feed Distribution Breakers / Type P ePODs Copyright © 2003, LayerZero Power Systems, Inc. UNLESS OTHERWISE SPECIFIED DIMENSIONS ARE IN INCHES DO NOT SCALE DRAWING REV ECN 2 A B C D Series 70 ePODs: Type-P Drawings 15 Series 70 ePODs: Type-P Technical Specifications © 2013 LayerZero Power Systems, Inc. A B C D 8 INPUT PHASE LANDING (BOTTOM) INPUT GROUND LANDING INPUT PHASE LANDING (TOP) 73 13 INPUT PHASE LANDING 8 31 11 18 INPUT GROUND 8 30 7 36 1.831 TYP BETWEEN PHASES 41 7 SOURCE 1 A B C PHASE SOURCE 2 A B C PHASE INPUT GROUND TOP VIEW 3 6 FRONT VIEW 96 REF 6 5 5 9 GND / NEU VERT CL SUB-FEED LANDING CL FUTURE CB624 CB623 CB622 CB621 FUTURE FUTURE INCLUDES BREAKER BASE W/O PLUG-IN CB 4 4 PH C PH B PH A PH C PH B PH A PH C PH B PH A PH C PH B PH A PH C PH B PH A PH C PH B PH A 4 RIGHT SIDE VIEW 3 3 6 A REV 17 SPJ AJP SPJ DWN CHK APVD ANGULAR ± .1/2 TOLERANCES: .XX ± .03 .XXX ± .010 17 29 41 NEU BUS AREA 52 DATE DATE 09/16/10 09/16/10 09/16/10 FIRST ANGLE PROJ. DATE 64 APPROVED STEVE JANKO 76 1.812 BETWEEN PHASE CL 09/16/2010 DATE 1 D SCALE SIZE 2 1=1 FSCM NO. 1 SHEET 55-11-401493-01 94MD401493-01SHT4 DWG NO. 4 OF 5 A REV OUTLINE, MOUNTING, INSTALLATION DIAGRAM 400A, 480V, 60Hz, SMR/TMR, 2 Source Series 70 eSTS/ 300KVA Transformer/ Supplied with up to (6) 400A ABB-T5/T3 Sub-Feed Distribution Breakers / Type P ePODs Copyright © 2003, LayerZero Power Systems, Inc. OUTPUT GND 51 BUS AREA 24 OUTPUT GND / NEU CL 1.000 BETWEEN LUG CL (24 EA GND/NEU) 24 NEW RELEASE DESCRIPTION REVISIONS SUB-FEED CB LANDING UNLESS OTHERWISE SPECIFIED DIMENSIONS ARE IN INCHES DO NOT SCALE DRAWING 20 N/A ECN 2 A B C D Series 70 ePODs: Type-P Drawings 16 Series 70 ePODs: Type-P Technical Specifications © 2013 LayerZero Power Systems, Inc. A B C D 8 8 7 83.00 82.000 18.50 ACCESS AREA SOURCE INPUT 7 6 6 37.500 35.500 21.00 38.50 1.323 5 1.000 1.323 1.000 ACCESS AREA TRANSFORMER (NOT USED) 23.00 7.82 8.32 1.32 8.00 5 5.00 36.00 4 4 1.000 1.323 36.00 REV A ECN N/A 3 SPJ AJP SPJ CHK APVD ANGULAR ± .1/2 DWN DATE DATE DATE 09/16/10 09/16/10 09/16/10 FIRST ANGLE PROJ. UNLESS OTHERWISE SPECIFIED DIMENSIONS ARE IN INCHES DO NOT SCALE DRAWING TOLERANCES: .XX ± .03 .XXX ± .010 REVISIONS NEW RELEASE DESCRIPTION 2 09/16/2010 DATE 1 APPROVED STEVE JANKO D SCALE SIZE 2 1=1 FSCM NO. 1 SHEET 55-11-401493-01 94MD401493-01SHT5 DWG NO. 5 OF 5 A REV OUTLINE, MOUNTING, INSTALLATION DIAGRAM 400A, 480V, 60Hz, SMR/TMR, 2 Source Series 70 eSTS/ 300KVA Transformer/ Supplied with up to (6) 400A ABB-T5/T3 Sub-Feed Distribution Breakers / Type P ePODs Copyright © 2003, LayerZero Power Systems, Inc. NOTE: HEIGHT VARIABLE FROM NOMINAL u0.75 3 A B C D Series 70 ePODs: Type-P Drawings 17 Series 70 ePODs: Type-P Technical Specifications