IDMTL OVERCURRENT RELAY RSH 207 Series Made In Japan KASUGA IDMTL TYPE RSH207 Overcurrent Relay is designed to protect equipment such as transformers, generators, motors and power distribution systems. This relay is simple to operate and test. At the same time it is extremely accurate, has a long service life and features reduced temperate error. The distinctive feature of 10 ideal current settings incorporated in the relay practically eliminates the need to use non-standard C.T. This relay comply with BS 142 and also IEC 255 in parts. Layout Red LED (trip: R) Red LED (trip: S) Red LED (trip: T) Instantaneous adjust (multiplier) Orange LED (Instantaneous: on) Red LED (Inverse time multipliers: 3/10) Test button Red LED (Inverse time multipliers: 1.3/10) Green LED (power supply) Knob (current setting) Digital SW (Inverse time setting) Trip & Reset button SPECIFICATIONS 1. Type IDMTL 2. Model RSH207 3. Supply voltage AC 110/240V 50/60Hz ±15% Other voltage upon request 4. Current setting 2.5, 3.0, 3.6, 3.75, 4.0, 4.375, 4.5, 5.0, 6.0, 7.5 5. Time multiplier 3/10 1.3/10 0.03 ~ 1.00 (Inverse time) 0.09 ~ 3 sec. (at 10 times of setting current) 0.039 ~ 1.3 sec. (at 10 times of setting current) 6. High-Set (Instantaneous protection) 2 - 10 times setting (see graph) 7. Pick up current 105% of setting 8. Reset current value not less than 95% of current setting 9. Contact output 2C, AC 250V, 5A (cosø=1) 12. Enclosure Standard DIN case DIN 96 x 96 x 98mm 10. LED Indication • Auxiliary Supply – Green • Phase Overcurrent – Red • Time multiplier – Red • Instantaneous On – Orange Protection structure IP50 (dust protection) 11. Life Electrical and mechanical more than 10,000 operations Weight Relay approx. 460g C.T. convertor approx. 1300g Material ABS resin complying with UL94V0 Characteristics 1. Ambient temperature -10 ~ +50°C 2. Ambient humidity 45 ~ 85%RH 3. Voltage accuracy ± 3% 4. Repeat accuracy ± 3% 5. 6. Time multiplier accuracy Temperature accuracy ± 2% or ± 30ms whichever is the greater less than 5% at -5°C/+40°C 7. Insulation resistance >1000MΩ 8. Withstand overcurrent 20 times for 5 sec. 9. Power consumption Approx. 4VA 10. C.T. input consumption Approx. IVA (at 7A) 11. Voltage withstand 2kV for 1 minute between all case terminals connected together and the case earth terminal. 2kV for 1 minute between independent circuit including contact circuits. Environmental Withstand 1. Impulse test 5kV peak, 1.2/50µs (0.5J) between all terminals and case, earth and between adjacent terminal. 2. Temperature IEC 68-2-1/68-2-2 Storage and transit -25°C to +70°C 3. Humidity IEC 68-2-3 56 days @93%RH and +40°C 4. Vibration IEC 255-21-1 0.5G between 10Hz and 150Hz 5. Electromagnetic wave Non-operation for radio frequency at 130-180 MHz and 400-500MHz and 900-l000MHz (by Walkie-talkie of 5W) IDMTL Overcurrent Relay RSH 207 DIMENSIONS (mm) for RSH 207 13.5 92 ± 0.5 80 11 90 96 98 max 92 ± 0.5 Scale Characteristics 1.3/10 Inverse Multiplies of Current X2 Time Multiplier (TM) X3 X5 Standard Operating Time 0.10 0.28 0.22 0.17 0.11 0.30 0.23 0.18 0.12 0.33 0.25 0.20 0.13 0.36 0.27 0.22 0.14 0.40 0.30 0.24 0.15 0.43 0.32 0.25 0.16 0.46 0.34 0.27 0.17 0.49 0.36 0.29 0.18 0.53 0.39 0.31 0.19 0.56 0.41 0.32 0.20 0.60 0.44 0.35 X3 X5 Scale Characteristics 3/10 Inverse Multiplies of Current X2 Time Multiplier (TM) Standard Operating Time 0.03 0.32 0.20 0.13 0.04 0.39 0.25 0.17 0.05 0.46 0.29 0.21 0.06 0.54 0.35 0.25 0.07 0.62 0.41 0.29 0.08 0.69 0.47 0.33 0.09 0.77 0.52 0.37 0.10 0.85 0.57 0.41 For other setting range, please refer to chart on back page IDMTL Overcurrent Relay RSH 207 Connection diagram for RSH207 R S T N k3 l3 k2 l2 k1 l1 cm A1 b c a Ta1 Ta2 240 110 0 TERMINAL A1 – CM OPEN X3 SHORT X 1.3 Connection diagram for RSH207 with earth fault R S T N RASP 18NB 1 8 3 4 2 5 7 6 k3 l3 k2 l2 k1 l1 cm A1 b c a Ta1 Ta2 240 110 0 TERMINAL A1 – CM OPEN X3 SHORT X 1.3 IDMTL Overcurrent Relay RSH207 IDMT characteristic as per IEC 255-4 and BS 142 TIME CURRENT CHARACTERISTIC TIME CURRENT CHARACTERISTIC 100 100 1.3/10 Inverse 3/10 Inverse 10 10 OPERATING TIME (sec) OPERATING TIME (sec) t=1.00 t=1.00 1 t=0.70 t=0.50 t=0.40 t=0.70 t=0.50 1 t=0.40 t=0.30 t=0.20 t=0.30 t=0.10 t=0.20 t=0.05 t=0.10 0.1 0.1 t=0.03 t=0.05 t=0.03 inst. 0.01 1 10 inst. 100 0.01 1 MULTIPLES OF SETTING CURRENT 10 100 MULTIPLES OF SETTING CURRENT Exclusive Agent: KASUGA ELECTRIC WORKS LTD 3-11 Shimorenjaku 8-Chome Mitaka, Tokyo 181-8518, Japan Tel: 0422-47-5881 Fax: 0422-44-6277 51 Kim Keat Road, Unit 05-02 Mun Hean Industrial Building, Singapore 328821 Tel: (65) 6250 0522 Fax: (65) 6253 6885/(65) 6253 5879 E-mail: [email protected] Website: http://www.munheansingapore.com
Similar documents
RSN200 RSN200
2 KV for 1 minute between all case terminals connected together and the case earth terminal 1.5KV for a minute between independent circuit including contact circuit
More information